Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:32:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1919.43 | 385.26 | 385.26 |
Net Site Energy | 1758.69 | 353.00 | 353.00 |
Total Source Energy | 5852.57 | 1174.70 | 1174.70 |
Net Source Energy | 5343.51 | 1072.52 | 1072.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 795.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 166.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 108.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1810.81 | 108.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 795.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 166.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 33.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 155.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 108.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 795.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 166.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 33.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 155.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 108.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.95 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 363.46 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.95 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 363.46 | 21.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 167.745 | 9.26 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.01 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 160.740 | 8.88 |
Electricity Coming From Utility | 1650.192 | 91.13 |
Surplus Electricity Going To Utility | 0.125 | 0.01 |
Net Electricity From Utility | 1650.067 | 91.12 |
Total On-Site and Utility Electric Sources | 1810.807 | 100.00 |
Total Electricity End Uses | 1810.807 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.33 |
Time Setpoint Not Met During Occupied Cooling | 574.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1380.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:30 | 09-JAN-12:39 | - | - | - | - | - | - | - | - | - | - | 24-APR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 116051.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38454.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 823.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23422.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9526.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 192662.18 | 9526.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 116051.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 3918.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 48.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 823.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 23422.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9526.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2519.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 526.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 491.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5734.82 | 117.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 505.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1151.07 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 505.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1151.07 | 23.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.39 | 0.314041 | 0.267000 | 0.637192 | 0.837443 | 0.500000 | 0.001213 |
CORE_MID VAV BOX COMPONENT | 2.06 | 0.364046 | 0.309000 | 0.636132 | 0.970790 | 0.500000 | 0.001047 |
CORE_TOP VAV BOX COMPONENT | 2.33 | 0.321227 | 0.273000 | 0.636937 | 0.856605 | 0.500000 | 0.001186 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.901597 | 0.175235 | 0.149000 | 0.134338 | 0.467294 | 0.500000 | 0.002174 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.711491 | 0.140581 | 0.119000 | 0.084667 | 0.374881 | 0.500000 | 0.002710 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.00 | 0.157689 | 0.134000 | 0.134258 | 0.420503 | 0.500000 | 0.002416 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.810371 | 0.123419 | 0.105000 | 0.085089 | 0.329117 | 0.500000 | 0.003087 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.762088 | 0.207314 | 0.176000 | 0.134128 | 0.552838 | 0.500000 | 0.001838 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.639466 | 0.156415 | 0.133000 | 0.085049 | 0.417106 | 0.500000 | 0.002436 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.854594 | 0.184873 | 0.157000 | 0.134171 | 0.492996 | 0.500000 | 0.002061 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.679285 | 0.147236 | 0.125000 | 0.084911 | 0.392630 | 0.500000 | 0.002588 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.770777 | 0.204977 | 0.174000 | 0.134115 | 0.546606 | 0.500000 | 0.001859 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.661580 | 0.403163 | 0.500000 | 0.002520 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.869320 | 0.181742 | 0.154000 | 0.133875 | 0.484644 | 0.500000 | 0.002096 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.717004 | 0.139491 | 0.119000 | 0.085323 | 0.371975 | 0.500000 | 0.002731 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21271.43 |
CORE_MID VAV BOX REHEAT COIL | 21236.06 |
CORE_TOP VAV BOX REHEAT COIL | 21262.92 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 7264.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4744.93 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 7229.03 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 4764.94 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4477.59 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2839.20 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4479.05 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2834.58 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5258.05 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 3467.59 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5230.96 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 3482.07 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.66 | 1.08 | 5.32 | 1.08 | 4.97 | 4.97 | 0.300000 | 0.216193 | 4.97 |
PACU_VAV_MID | 2.54 | 1.07 | 5.08 | 1.07 | 4.67 | 4.67 | 0.300000 | 0.230089 | 4.67 |
PACU_VAV_TOP | 2.88 | 1.08 | 5.76 | 1.22 | 5.60 | 5.60 | 0.300000 | 0.217320 | 5.60 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.97 |
PACU_VAV_MID_OA_CONTROLLER | 4.67 |
PACU_VAV_TOP_OA_CONTROLLER | 5.60 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.97 | 116534.04 | 0.719793 | 1.66 | 38840.80 | 0.719793 |
PACU_VAV_MID COOLING COIL | 4.67 | 111179.66 | 0.714702 | 1.56 | 37056.18 | 0.714702 |
PACU_VAV_TOP COOLING COIL | 5.60 | 127843.13 | 0.727681 | 1.87 | 42610.11 | 0.727681 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 0.000000 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.97 |
PACU_VAV_MID FAN | 4.67 |
PACU_VAV_TOP FAN | 5.60 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4296E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4635E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6887E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7167E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4486E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4698E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5578E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5722E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6220E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2028E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2708E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3184E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2613E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3760E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8099E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0520E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4309E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4714E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6901E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7253E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4501E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4767E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5576E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5721E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1837E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3527E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9154E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1486E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9954E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9683E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3022E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5557E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8234E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8362E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6164E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6257E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4487E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4522E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9854E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9904E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4722E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5037E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1032E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1285E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8332E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8508E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5576E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5721E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2493E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2592E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7599E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7337E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5795E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.7005E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8099E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0520E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4717E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5031E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1025E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1267E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8319E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8460E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5578E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5722E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4071E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0064E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9932E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7376E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2056E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6181E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3022E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5557E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3143E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3387E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0058E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0296E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9549E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9686E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9855E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9905E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0102E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0646E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.6112E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2210E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.7641E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1035E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2063E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4956E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0542E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2773E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.8020E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0822E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9057E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9140E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2406E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5186E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5930E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6764E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0694E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3379E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8837E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0026E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2063E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4956E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3003E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9469E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9070E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6904E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1382E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5793E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2406E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5186E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0098E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0641E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.6107E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2205E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.7635E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1031E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2060E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4955E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0541E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2771E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.8018E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0820E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9055E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9138E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2403E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5184E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5931E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6763E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0695E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3378E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8836E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0025E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2060E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4955E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3003E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9468E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9069E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6903E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1380E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5791E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2403E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5184E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 33123.50510 | 33123.50510 | 2.38649 | 2.38649 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 2454.18330 | 2454.18330 | 0.10423 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28594.80136 | 28594.80136 | 2.05868 | 2.05868 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 6831.51007 | 6831.51007 | 0.28582 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32096.43948 | 32096.43948 | 2.33310 | 2.33310 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 42.50900 | 1.07813E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 11805.46096 | 11805.46096 | 0.49840 | 0.49840 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12403.01257 | 12403.01257 | 0.90160 | 0.90160 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 5118.42308 | 5118.42308 | 0.21760 | 0.21760 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9787.78926 | 9787.78926 | 0.71149 | 0.71149 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 3342.75048 | 3342.75048 | 0.14214 | 0.14214 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13783.16667 | 13783.16667 | 1.00192 | 1.00192 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 5093.93795 | 5093.93795 | 0.21655 | 0.21655 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11148.07643 | 11148.07643 | 0.81037 | 0.81037 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 3356.76214 | 3356.76214 | 0.14274 | 0.14274 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10483.97335 | 10483.97335 | 0.76209 | 0.76209 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 2648.53136 | 2648.53136 | 0.11193 | 0.11193 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8797.09015 | 8797.09015 | 0.63947 | 0.63947 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 1758.53550 | 1758.53550 | 7.43647E-002 | 7.43647E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11756.57978 | 11756.57978 | 0.85459 | 0.85459 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 2639.50703 | 2639.50703 | 0.11154 | 0.11154 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9344.88780 | 9344.88780 | 0.67928 | 0.67928 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 1766.26684 | 1766.26684 | 7.46961E-002 | 7.46961E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10603.38829 | 10603.38829 | 0.77078 | 0.77078 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 3714.38376 | 3714.38376 | 0.15751 | 0.15751 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9101.22065 | 9101.22065 | 0.66158 | 0.66158 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2448.94898 | 2448.94898 | 0.10387 | 0.10387 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11959.03980 | 11959.03980 | 0.86932 | 0.86932 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 3695.35217 | 3695.35217 | 0.15669 | 0.15669 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9863.67967 | 9863.67967 | 0.71700 | 0.71700 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 2459.11544 | 2459.11544 | 0.10431 | 0.10431 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 89094.07 | 4.97448 | 4.97448 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 96.94 | 0.80151 | 0.80151 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 84916.51 | 4.67119 | 4.67119 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 114.54 | 0.94707 | 0.94707 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 97406.91 | 5.60193 | 5.60193 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 115.62 | 1.21741 | 1.21741 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.38649 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31404 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63719 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83744 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21322E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21271.42643 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05868 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36405 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63613 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97079 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04657E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21236.06456 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33310 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32123 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63694 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85660 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18608E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21262.91945 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90160 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17524 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14900 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13434 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46729 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17422E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7263.99753 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71149 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14058 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46675E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37488 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71019E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4744.93367 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00192 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15769 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13400 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13426 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42050 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41615E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7229.03103 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81037 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12342 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10500 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50890E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32912 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.08704E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4764.94134 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76209 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20731 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13413 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55284 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83779E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4477.59202 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63947 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15641 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13300 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50489E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41711 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43583E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2839.19622 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85459 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18487 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13417 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49300 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06087E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4479.05177 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67928 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14724 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12500 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49106E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39263 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58768E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2834.57882 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77078 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20498 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17400 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13412 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54661 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85874E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5258.05237 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66158 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40316 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52007E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3467.59095 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86932 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18174 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13388 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48464 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09638E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5230.95860 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71700 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13949 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53234E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37197 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73137E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3482.06774 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.66096 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07545 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.32192 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07545 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.97448 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.97448 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.21619 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.53868 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07479 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.07736 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07479 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.67119 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.67119 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.23009 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87924 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07529 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.75848 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21741 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.60193 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.60193 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.21732 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.97448 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.67119 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.60193 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.97448 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.97448 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 116534.04214 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71979 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65799 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38840.79625 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71979 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.97448 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.67119 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.67119 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 111179.66032 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71470 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.55691 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37056.18079 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71470 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.67119 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.60193 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.60193 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 127843.12605 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72768 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.86712 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 42610.11391 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72768 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.60193 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 116125.91 | 396238.06 | 12.03 | 3.08 | 3.45 | 3.63 | 3.78 | 10.52 | 11.76 | 12.40 | 12.89 | 5.7508 | 4.5665 | 3.0762 | 1.2978 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 110848.07 | 378229.31 | 12.07 | 3.09 | 3.46 | 3.65 | 3.79 | 10.54 | 11.80 | 12.44 | 12.92 | 5.4002 | 4.2825 | 2.8829 | 1.2241 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 127283.49 | 434309.29 | 11.98 | 3.07 | 3.43 | 3.62 | 3.77 | 10.48 | 11.71 | 12.34 | 12.85 | 6.4762 | 5.1460 | 3.4657 | 1.4526 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.2868543942E-002 | 0.1133958789 | Pass | Pass | 2.8938159384E-002 | 0.1665962556 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.3658431695E-002 | 4.8342001304E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3796560566E-002 | 7.9230663774E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3898956049E-002 | 1.6675829408E-002 | Pass | Pass | 9.6431952271E-002 | 0.4842095256 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.1712432485E-003 | 5.4211874362E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.3479501316E-002 | 1.2929852974E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.3889404825E-002 | 2.8101424217E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.6855181576E-002 | 2.6593874646E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.2577748638E-002 | 5.4732529424E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.5399095421E-002 | 4.4303055004E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.6039175843E-002 | 9.2097436174E-002 | Pass | Pass | 2.8620784417E-002 | 0.1655642337 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.9369485689E-002 | 9.3009133688E-002 | Pass | Pass | 2.8618749763E-002 | 0.1656356462 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.0004886628E-002 | 0.1224843641 | Pass | Pass | 3.7775058988E-002 | 0.2167807569 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.9079098166E-002 | 0.1043155114 | Pass | Pass | 2.8347124682E-002 | 0.1642055091 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.1495356557E-002 | 2.2458334202E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.5493702117E-002 | 2.2577560252E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.0575966994E-002 | 4.7591759663E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.1749371331E-002 | 3.8495253464E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2118.45 | -121.2 | 0.00 | -1066.1 | 3778.79 | 4710.04 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 195.79 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.26 | 0.0000 | Y | 4.80 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.21 | 0.0000 | Y | 3.03 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.05 | 0.0000 | Y | 4.76 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.19 | 0.0000 | Y | 3.03 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.22 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.18 | 0.0000 | Y | 3.03 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.03 | 0.0000 | Y | 4.75 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.15 | 0.0000 | Y | 3.03 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.26 | 0.0000 | Y | 4.80 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.21 | 0.0000 | Y | 3.03 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.05 | 0.0000 | Y | 4.76 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.19 | 0.0000 | Y | 3.03 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 166.22 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 41.85 | 41.85 | 4.26 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.85 | 62.85 | 3.31 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.85 | 46.68 | 26.31 | |
Exterior Lighting Total | 3824.74 | 33.87 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 116534.04 | 83880.33 | 32653.71 | 0.72 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 111179.66 | 79460.32 | 31719.34 | 0.71 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 127843.13 | 93029.04 | 34814.09 | 0.73 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 116125.9 | 3.08 | 10.52 | N/A | N/A | 12.03 | |
PACU_VAV_MID COOLING COIL | 110848.1 | 3.09 | 10.54 | N/A | N/A | 12.07 | |
PACU_VAV_TOP COOLING COIL | 127283.5 | 3.07 | 10.48 | N/A | N/A | 11.98 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21271.43 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21236.06 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 21262.92 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7264.00 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4744.93 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7229.03 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4764.94 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4477.59 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2839.20 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4479.05 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2834.58 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5258.05 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3467.59 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5230.96 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3482.07 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.97 | 10889.19 | 2189.01 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.67 | 10225.28 | 2189.01 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.60 | 12183.58 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 116125.91 | 3.08 | 10.52 | 12.03 | 5.7508 | 3.45 | 11.76 | 4.5665 | 3.63 | 12.40 | 3.0762 | 3.78 | 12.89 | 1.2978 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 110848.07 | 3.09 | 10.54 | 12.07 | 5.4002 | 3.46 | 11.80 | 4.2825 | 3.65 | 12.44 | 2.8829 | 3.79 | 12.92 | 1.2241 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 127283.49 | 3.07 | 10.48 | 11.98 | 6.4762 | 3.43 | 11.71 | 5.1460 | 3.62 | 12.34 | 3.4657 | 3.77 | 12.85 | 1.4526 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 33123.51 | 33123.51 | 33.68 | 2.386 | 2.386 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_MID | 28594.80 | 28594.80 | 29.07 | 2.059 | 2.059 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_TOP | 32096.44 | 32096.44 | 32.63 | 2.333 | 2.333 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00887 | 42.51 | 0.01078 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12403.01 | 12403.01 | 59.82 | 0.902 | 0.902 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00878 | 42.70 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9787.79 | 9787.79 | 74.57 | 0.711 | 0.711 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00873 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13783.17 | 13783.17 | 66.48 | 1.002 | 1.002 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11148.08 | 11148.08 | 84.94 | 0.810 | 0.810 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00870 | 41.96 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10483.97 | 10483.97 | 50.56 | 0.762 | 0.762 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00879 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8797.09 | 8797.09 | 67.02 | 0.639 | 0.639 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00872 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11756.58 | 11756.58 | 56.70 | 0.855 | 0.855 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00876 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9344.89 | 9344.89 | 71.20 | 0.679 | 0.679 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00871 | 41.83 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10603.39 | 10603.39 | 51.14 | 0.771 | 0.771 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00881 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9101.22 | 9101.22 | 69.34 | 0.662 | 0.662 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00874 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11959.04 | 11959.04 | 57.68 | 0.869 | 0.869 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00878 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9863.68 | 9863.68 | 75.15 | 0.717 | 0.717 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00872 | 41.96 | 0.01078 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 2454.18 | 2454.18 | 2.50 | 0.104 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 6831.51 | 6831.51 | 6.95 | 0.286 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 11805.46 | 11805.46 | 12.00 | 0.498 | 0.498 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 5118.42 | 5118.42 | 24.69 | 0.218 | 0.218 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 3342.75 | 3342.75 | 25.47 | 0.142 | 0.142 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 5093.94 | 5093.94 | 24.57 | 0.217 | 0.217 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 3356.76 | 3356.76 | 25.57 | 0.143 | 0.143 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 2648.53 | 2648.53 | 12.77 | 0.112 | 0.112 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00828 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 1758.54 | 1758.54 | 13.40 | 0.074 | 0.074 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 2639.51 | 2639.51 | 12.73 | 0.112 | 0.112 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00828 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 1766.27 | 1766.27 | 13.46 | 0.075 | 0.075 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00828 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 3714.38 | 3714.38 | 17.91 | 0.158 | 0.158 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2448.95 | 2448.95 | 18.66 | 0.104 | 0.104 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 3695.35 | 3695.35 | 17.82 | 0.157 | 0.157 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 2459.12 | 2459.12 | 18.74 | 0.104 | 0.104 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00829 | 12.70 | 0.00915 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.97 | 4.97 | 0.80 | 0.80 | 4.9745 | 1.0754 | 4.9745 | 0.2162 | 0.3000 |
PACU_VAV_MID | 4.67 | 4.67 | 0.95 | 0.95 | 4.6712 | 1.0748 | 4.6712 | 0.2301 | 0.3000 |
PACU_VAV_TOP | 5.60 | 5.60 | 1.22 | 1.22 | 5.6019 | 1.2174 | 5.6019 | 0.2173 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21271.426 | 21271.426 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21271.43 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800039 | 51.6953 | 2454.18 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21236.065 | 21236.065 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21236.06 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 6831.51 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 21262.919 | 21262.919 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21262.92 | 16638.14 | 0.498400 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11805.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 7263.998 | 7263.998 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7264.00 | 7264.00 | 0.217595 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00822993 | 53.1572 | 5118.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4744.934 | 4744.934 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4744.93 | 4744.93 | 0.142136 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00822993 | 53.1572 | 3342.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 7229.031 | 7229.031 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7229.03 | 7229.03 | 0.216548 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823137 | 53.1664 | 5093.94 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 4764.941 | 4764.941 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4764.94 | 4764.94 | 0.142735 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00822864 | 53.1490 | 3356.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4477.592 | 4477.592 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4477.59 | 3736.40 | 0.111925 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828349 | 53.4992 | 2648.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 2839.196 | 2839.196 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2839.20 | 2482.53 | 0.074365 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828595 | 53.5148 | 1758.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 4479.052 | 4479.052 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4479.05 | 3723.49 | 0.111538 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828436 | 53.5048 | 2639.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2834.579 | 2834.579 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2834.58 | 2493.59 | 0.074696 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828495 | 53.5085 | 1766.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5258.052 | 5258.052 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5258.05 | 5258.05 | 0.157506 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828884 | 53.5328 | 3714.38 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 3467.591 | 3467.591 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3467.59 | 3467.59 | 0.103873 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828871 | 53.5320 | 2448.95 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5230.959 | 5230.959 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5230.96 | 5230.96 | 0.156695 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829037 | 53.5426 | 3695.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 3482.068 | 3482.068 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3482.07 | 3482.07 | 0.104306 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828741 | 53.5237 | 2459.12 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 116534.042 | 83880.334 | 4.974478 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 108079.64 | 97463.72 | 4.974478 | 27.61 | 18.20 | 0.00919789 | 11.02 | 11.02 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 19.2201 | 24.00 | 0.00882087 | 47.4404 | 68411.10 | 0.00 | 120162.24 | 85273.13 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 0.00 | 0.00 | 1.492343 | 15.69 | 13.53 | 0.00877922 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 64.0670 | 21.00 | 0.00819012 | 52.9044 | 10994.80 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 111179.660 | 79460.317 | 4.671189 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 103462.69 | 92745.85 | 4.671189 | 27.85 | 18.33 | 0.00925127 | 11.02 | 11.02 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 20.4680 | 24.00 | 0.00885666 | 47.6304 | 64167.83 | 0.00 | 114641.15 | 80798.60 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.401357 | 15.26 | 13.42 | 0.00883761 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 68.2267 | 21.00 | 0.00818679 | 52.8829 | 19149.31 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 127843.126 | 93029.037 | 5.601932 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 118107.86 | 107081.75 | 5.601932 | 27.19 | 18.02 | 0.00914271 | 11.03 | 11.03 | 0.00850000 | 42.70 | 0.01078164 | 23.83 | 17.0673 | 24.00 | 0.00880491 | 47.3560 | 76968.34 | 0.00 | 131823.42 | 94530.08 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.680580 | 16.28 | 13.67 | 0.00868037 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 56.8911 | 21.00 | 0.00806058 | 52.0789 | 20628.55 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21271.426 | 21271.426 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21271.43 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21271.43 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.85 | 0.00800039 | 21.00 | 0.00800039 | 51.6953 | 2454.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21236.065 | 21236.065 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21236.06 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21236.06 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 6831.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 21262.919 | 21262.919 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21262.92 | 16638.14 | 1.0000 | 0.59987174 | 0.498400 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21262.92 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11805.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7263.998 | 7263.998 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7264.00 | 7264.00 | 1.0000 | 0.26189634 | 0.217595 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7264.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00822993 | 21.00 | 0.00822993 | 53.1572 | 5118.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4744.934 | 4744.934 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4744.93 | 4744.93 | 1.0000 | 0.17107395 | 0.142136 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4744.93 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00822993 | 21.00 | 0.00822993 | 53.1572 | 3342.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7229.031 | 7229.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7229.03 | 7229.03 | 1.0000 | 0.26063565 | 0.216548 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7229.03 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823137 | 21.00 | 0.00823137 | 53.1664 | 5093.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4764.941 | 4764.941 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4764.94 | 4764.94 | 1.0000 | 0.17179531 | 0.142735 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4764.94 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00822864 | 21.00 | 0.00822864 | 53.1490 | 3356.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4477.592 | 4477.592 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4477.59 | 3736.40 | 1.0000 | 0.13471242 | 0.111925 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4477.59 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00828349 | 21.00 | 0.00828349 | 53.4992 | 2648.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 2839.196 | 2839.196 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2839.20 | 2482.53 | 1.0000 | 0.08950503 | 0.074365 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2839.20 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00828595 | 21.00 | 0.00828595 | 53.5148 | 1758.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4479.052 | 4479.052 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4479.05 | 3723.49 | 1.0000 | 0.13424677 | 0.111538 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4479.05 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00828436 | 21.00 | 0.00828436 | 53.5048 | 2639.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 2834.579 | 2834.579 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2834.58 | 2493.59 | 1.0000 | 0.08990382 | 0.074696 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2834.58 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00828495 | 21.00 | 0.00828495 | 53.5085 | 1766.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5258.052 | 5258.052 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5258.05 | 5258.05 | 1.0000 | 0.18957394 | 0.157506 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5258.05 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00828884 | 21.00 | 0.00828884 | 53.5328 | 3714.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 3467.591 | 3467.591 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3467.59 | 3467.59 | 1.0000 | 0.12502061 | 0.103873 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3467.59 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00828871 | 21.00 | 0.00828871 | 53.5320 | 2448.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5230.959 | 5230.959 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5230.96 | 5230.96 | 1.0000 | 0.18859710 | 0.156695 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5230.96 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00829037 | 21.00 | 0.00829037 | 53.5426 | 3695.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 3482.068 | 3482.068 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3482.07 | 3482.07 | 1.0000 | 0.12554255 | 0.104306 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3482.07 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00828741 | 21.00 | 0.00828741 | 53.5237 | 2459.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 116534.042 | 83880.334 | 4.974478 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9384 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.974478 | 5.98725714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 108079.64 | 97463.72 | 0.9275 | 5.98725714 | 4.974478 | 27.61 | 18.20 | 0.00919789 | 51222.7 | 11.02 | 11.02 | 0.00850000 | 32505.8 | -999.0 | -999.00 | -999.00 | -999.00 | 10889.188 | 97190.46 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 19.2201 | 24.00 | 0.00882087 | 24.00 | 0.00882087 | 47.4404 | 68411.10 | 0.00 | 120162.24 | 85273.13 | 5.75080574 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.15 | 12.14 | 0.00880600 | 34427.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.974478 | 5.98725714 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.79617714 | 1.492343 | 15.69 | 13.53 | 0.00877922 | 37975.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 64.0670 | 21.01 | 0.00811200 | 21.00 | 0.00819012 | 52.9044 | 10994.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 111179.660 | 79460.317 | 4.671189 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0376 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.671189 | 5.62221905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 103462.69 | 92745.85 | 0.9306 | 5.62221905 | 4.671189 | 27.85 | 18.33 | 0.00925127 | 51603.1 | 11.02 | 11.02 | 0.00850000 | 32506.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10225.283 | 93237.40 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 20.4680 | 24.00 | 0.00885666 | 24.00 | 0.00885666 | 47.6304 | 64167.83 | 0.00 | 114641.15 | 80798.60 | 5.40018390 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.01 | 12.00 | 0.00872754 | 34093.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.671189 | 5.62221905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.68666572 | 1.401357 | 15.26 | 13.42 | 0.00883761 | 37682.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 68.2267 | 20.74 | 0.00815940 | 21.00 | 0.00818679 | 52.8829 | 19149.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 127843.126 | 93029.037 | 5.601932 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8358 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.601932 | 6.74245686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 118107.86 | 107081.75 | 0.9238 | 6.74245686 | 5.601932 | 27.19 | 18.02 | 0.00914271 | 50654.2 | 11.03 | 11.03 | 0.00850000 | 32517.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12183.576 | 105924.28 | 42.70 | 0.01078164 | 23.83 | 0.95610000 | 17.0673 | 24.00 | 0.00880491 | 24.00 | 0.00880491 | 47.3560 | 76968.34 | 0.00 | 131823.42 | 94530.08 | 6.47618078 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.38 | 12.35 | 0.00892687 | 34967.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.601932 | 6.74245686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.02273706 | 1.680580 | 16.28 | 13.67 | 0.00868037 | 38328.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 56.8911 | 21.00 | 0.00805606 | 21.00 | 0.00806058 | 52.0789 | 20628.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5227.17 | 5.00 | 0.00 |
CORE_MID | 4764.33 | 216.33 | 12.83 |
CORE_TOP | 4429.83 | 590.17 | 20.67 |
PERIMETER_TOP_ZN_3 | 4481.67 | 1315.67 | 477.83 |
PERIMETER_TOP_ZN_2 | 4791.50 | 1154.17 | 567.17 |
PERIMETER_TOP_ZN_1 | 4890.67 | 1123.83 | 577.50 |
PERIMETER_TOP_ZN_4 | 4690.17 | 1276.50 | 570.83 |
PERIMETER_BOT_ZN_3 | 4847.67 | 682.67 | 297.83 |
PERIMETER_BOT_ZN_2 | 5169.17 | 611.67 | 418.33 |
PERIMETER_BOT_ZN_1 | 5261.00 | 1331.00 | 1095.00 |
PERIMETER_BOT_ZN_4 | 5119.67 | 666.17 | 433.17 |
PERIMETER_MID_ZN_3 | 4688.00 | 1021.83 | 430.50 |
PERIMETER_MID_ZN_2 | 4151.17 | 912.50 | 524.33 |
PERIMETER_MID_ZN_1 | 5094.67 | 853.67 | 527.17 |
PERIMETER_MID_ZN_4 | 4896.17 | 992.67 | 531.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5547.33 | 2276.00 | 1380.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 104.17 | 0.00 | 64.33 |
PERIMETER_TOP_ZN_2 | 0.00 | 139.17 | 0.00 | 90.83 |
PERIMETER_TOP_ZN_1 | 0.00 | 131.83 | 0.00 | 88.83 |
PERIMETER_TOP_ZN_4 | 0.00 | 146.33 | 0.00 | 78.83 |
PERIMETER_BOT_ZN_3 | 0.00 | 60.33 | 0.00 | 43.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 109.83 | 0.00 | 78.67 |
PERIMETER_BOT_ZN_1 | 3.33 | 440.50 | 3.33 | 415.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 118.33 | 0.00 | 66.83 |
PERIMETER_MID_ZN_3 | 0.00 | 73.17 | 0.00 | 52.67 |
PERIMETER_MID_ZN_2 | 0.00 | 109.33 | 0.00 | 84.67 |
PERIMETER_MID_ZN_1 | 0.00 | 103.33 | 0.00 | 81.00 |
PERIMETER_MID_ZN_4 | 0.00 | 112.83 | 0.00 | 68.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.33 | 691.33 | 3.33 | 574.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 0.460 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.427 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.426 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.622 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.773 | 0.076 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 0.770 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.757 | 0.076 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.562 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.709 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 0.809 | 1.257 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.700 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.620 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.734 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 0.767 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.762 | 0.063 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.59 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.62 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7959012.98 | 0.00 | 7959012.98 | 0.00 | 7959012.98 | 13393058.27 | 7200.79 | 569.21 | 990.00 | 555.67 |
CORE_MID | 7346033.32 | 0.00 | 7346033.32 | 0.00 | 7346033.32 | 13393058.27 | 7665.01 | 775.46 | 319.53 | 488.56 |
CORE_TOP | 7420870.07 | 0.00 | 7420870.07 | 0.00 | 7420870.07 | 13393058.27 | 7549.42 | 928.62 | 281.96 | 558.50 |
PERIMETER_TOP_ZN_3 | 2230614.81 | 0.00 | 2230614.81 | 413457.77 | 2644072.58 | 2823374.22 | 4164.76 | 967.42 | 3627.82 | 558.50 |
PERIMETER_TOP_ZN_2 | 1727990.35 | 0.00 | 1727990.35 | 275636.86 | 2003627.20 | 1787429.43 | 3658.30 | 829.13 | 4272.57 | 558.50 |
PERIMETER_TOP_ZN_1 | 2719054.57 | 0.00 | 2719054.57 | 413457.77 | 3132512.35 | 2823374.22 | 3549.38 | 841.08 | 4369.54 | 558.50 |
PERIMETER_TOP_ZN_4 | 1711154.39 | 0.00 | 1711154.39 | 275636.86 | 1986791.25 | 1787312.18 | 3694.03 | 886.42 | 4179.55 | 558.50 |
PERIMETER_BOT_ZN_3 | 2020537.25 | 0.00 | 2020537.25 | 219835.62 | 2240372.87 | 2823374.22 | 5382.10 | 539.00 | 2838.91 | 555.67 |
PERIMETER_BOT_ZN_2 | 1590285.98 | 0.00 | 1590285.98 | 146556.20 | 1736842.18 | 1787429.43 | 3896.04 | 558.72 | 4305.24 | 555.67 |
PERIMETER_BOT_ZN_1 | 2831926.25 | 0.00 | 2831926.25 | 4198137.27 | 7030063.51 | 2823374.22 | 4070.55 | 463.70 | 4225.75 | 555.67 |
PERIMETER_BOT_ZN_4 | 1584550.69 | 0.00 | 1584550.69 | 146556.20 | 1731106.89 | 1787312.18 | 4194.63 | 504.93 | 4060.43 | 555.67 |
PERIMETER_MID_ZN_3 | 2192190.66 | 0.00 | 2192190.66 | 344173.66 | 2536364.32 | 2823374.22 | 4475.81 | 829.14 | 3455.05 | 488.56 |
PERIMETER_MID_ZN_2 | 1630303.42 | 0.00 | 1630303.42 | 229447.73 | 1859751.15 | 1601953.02 | 3486.78 | 800.07 | 4473.14 | 1397.56 |
PERIMETER_MID_ZN_1 | 2675670.22 | 0.00 | 2675670.22 | 344173.66 | 3019843.87 | 2823374.22 | 3792.87 | 666.93 | 4300.20 | 488.56 |
PERIMETER_MID_ZN_4 | 1697118.38 | 0.00 | 1697118.38 | 229447.73 | 1926566.10 | 1787312.18 | 3763.53 | 793.66 | 4202.81 | 488.56 |
Total Facility | 47337313.34 | 0.00 | 47337313.34 | 7236517.31 | 54573830.65 | 67658168.57 | 8528.80 | 1947.42 | 5254.07 | 1694.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3340 | 0.0000 | 0.3340 | 0.0000 | 0.3340 | 0.4247 | 4555.94 | 400.01 | 987.05 |
CORE_MID | 0.3100 | 0.0000 | 0.3100 | 0.0000 | 0.3100 | 0.4247 | 4979.56 | 646.17 | 317.27 |
CORE_TOP | 0.3092 | 0.0000 | 0.3092 | 0.0000 | 0.3092 | 0.4247 | 4947.88 | 714.43 | 280.69 |
PERIMETER_TOP_ZN_3 | 0.0950 | 0.0000 | 0.0950 | 0.0110 | 0.1060 | 0.0895 | 1702.34 | 740.96 | 3499.70 |
PERIMETER_TOP_ZN_2 | 0.0747 | 0.0000 | 0.0747 | 0.0073 | 0.0820 | 0.0567 | 1103.01 | 719.88 | 4120.12 |
PERIMETER_TOP_ZN_1 | 0.1177 | 0.0000 | 0.1177 | 0.0110 | 0.1287 | 0.0895 | 1080.40 | 632.11 | 4230.50 |
PERIMETER_TOP_ZN_4 | 0.0731 | 0.0000 | 0.0731 | 0.0073 | 0.0805 | 0.0567 | 1308.74 | 649.97 | 3984.30 |
PERIMETER_BOT_ZN_3 | 0.0858 | 0.0000 | 0.0858 | 0.0058 | 0.0917 | 0.0895 | 2762.37 | 406.20 | 2774.43 |
PERIMETER_BOT_ZN_2 | 0.0685 | 0.0000 | 0.0685 | 0.0039 | 0.0724 | 0.0567 | 1378.82 | 383.84 | 4180.34 |
PERIMETER_BOT_ZN_1 | 0.1233 | 0.0000 | 0.1233 | 0.1918 | 0.3151 | 0.0895 | 1495.74 | 330.37 | 4116.88 |
PERIMETER_BOT_ZN_4 | 0.0676 | 0.0000 | 0.0676 | 0.0039 | 0.0715 | 0.0567 | 1683.95 | 376.19 | 3882.86 |
PERIMETER_MID_ZN_3 | 0.0947 | 0.0000 | 0.0947 | 0.0091 | 0.1038 | 0.0895 | 1880.71 | 690.52 | 3371.77 |
PERIMETER_MID_ZN_2 | 0.0709 | 0.0000 | 0.0709 | 0.0064 | 0.0773 | 0.0567 | 1090.02 | 486.28 | 3457.70 |
PERIMETER_MID_ZN_1 | 0.1172 | 0.0000 | 0.1172 | 0.0091 | 0.1263 | 0.0895 | 1173.56 | 558.48 | 4210.96 |
PERIMETER_MID_ZN_4 | 0.0736 | 0.0000 | 0.0736 | 0.0061 | 0.0797 | 0.0567 | 1393.85 | 499.21 | 4049.95 |
Total Facility | 2.0152 | 0.0000 | 2.0152 | 0.2728 | 2.2880 | 2.1513 | 5742.45 | 1428.39 | 4916.41 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23158358.43 | 0.00 | 23158358.43 | 22614548.33 | 3155.03 | 1.25 | 5603.72 | 555.67 |
PACU_VAV_MID | 22513748.13 | 0.00 | 22513748.13 | 22429071.92 | 3241.45 | 1.81 | 5516.74 | 488.56 |
PACU_VAV_TOP | 22902502.36 | 0.00 | 22902502.36 | 22614548.33 | 3168.06 | 1.63 | 5590.32 | 558.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9838 | 0.0000 | 0.9838 | 0.7171 | 881.89 | 0.82 | 5060.30 |
PACU_VAV_MID | 0.9656 | 0.0000 | 0.9656 | 0.7084 | 902.13 | 1.01 | 5039.86 |
PACU_VAV_TOP | 0.9702 | 0.0000 | 0.9702 | 0.7171 | 894.45 | 0.96 | 5047.59 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 317.62 | 0.00 | 0.00 | 0.00 | 0.00 | 5329.03 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 229.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5330.90 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 220.82 | 0.00 | 0.00 | 0.00 | 0.00 | 5418.87 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.1707 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1474 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1157 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1325 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0772 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1371 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1810.81 | 11243.53 | 29-MAY-17:20 | 192662.18 | 10-AUG-15:30 |
Electricity:Building | 813.97 | 11073.68 | 29-MAY-17:10 | 57401.57 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 813.97 | 11073.68 | 29-MAY-17:10 | 57401.57 | 15-MAR-07:10 |
InteriorLights:Electricity | 166.22 | 772.31 | 01-JAN-09:50 | 16963.78 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 166.22 | 772.31 | 01-JAN-09:50 | 16963.78 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 166.22 | 772.31 | 01-JAN-09:50 | 16963.78 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 166.22 | 772.31 | 01-JAN-09:50 | 16963.78 | 15-MAR-07:10 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.13 | 405.59 | 02-APR-17:10 | 2100.77 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.80 | 19.49 | 01-JAN-09:50 | 665.53 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.80 | 19.49 | 01-JAN-09:50 | 665.53 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.44 | 257.50 | 29-MAY-17:10 | 1324.06 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.03 | 12.34 | 01-JAN-08:00 | 415.48 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.03 | 12.34 | 01-JAN-08:00 | 415.48 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.09 | 405.59 | 12-MAR-17:10 | 2099.36 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.76 | 19.49 | 01-JAN-08:00 | 664.12 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.76 | 19.49 | 01-JAN-08:00 | 664.12 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.43 | 256.75 | 12-MAR-17:10 | 1332.24 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.03 | 12.34 | 01-JAN-09:40 | 423.67 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.03 | 12.34 | 01-JAN-09:40 | 423.67 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.13 | 405.59 | 02-APR-17:10 | 2098.09 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.79 | 19.49 | 01-JAN-09:40 | 662.84 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.79 | 19.49 | 01-JAN-09:40 | 662.84 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.43 | 256.76 | 29-MAY-17:10 | 1322.40 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.03 | 12.34 | 01-JAN-08:00 | 413.83 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.03 | 12.34 | 01-JAN-08:00 | 413.83 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.08 | 405.59 | 12-MAR-17:10 | 2096.60 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.75 | 19.49 | 01-JAN-08:00 | 661.37 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.75 | 19.49 | 01-JAN-08:00 | 661.37 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.43 | 256.75 | 12-MAR-17:10 | 1330.96 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.03 | 12.34 | 01-JAN-09:40 | 422.39 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.03 | 12.34 | 01-JAN-09:40 | 422.39 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.13 | 405.59 | 02-APR-17:10 | 2100.77 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.80 | 19.49 | 01-JAN-09:50 | 665.52 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.80 | 19.49 | 01-JAN-09:50 | 665.52 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.44 | 257.50 | 29-MAY-17:10 | 1324.05 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.03 | 12.34 | 01-JAN-08:00 | 415.48 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.03 | 12.34 | 01-JAN-08:00 | 415.48 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.09 | 405.59 | 12-MAR-17:10 | 2099.35 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.76 | 19.49 | 01-JAN-08:00 | 664.11 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.76 | 19.49 | 01-JAN-08:00 | 664.11 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.43 | 256.75 | 12-MAR-17:10 | 1332.24 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.03 | 12.34 | 01-JAN-09:40 | 423.67 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.03 | 12.34 | 01-JAN-09:40 | 423.67 | 14-MAR-07:10 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 160.74 | -0.00 | 19-APR-18:30 | 24093.10 | 21-MAY-12:30 |
ElectricityProduced:Plant | 160.74 | -0.00 | 19-APR-18:30 | 24093.10 | 21-MAY-12:30 |
Photovoltaic:ElectricityProduced | 167.75 | 0.00 | 01-JAN-00:10 | 25071.34 | 21-MAY-12:30 |
PowerConversion:ElectricityProduced | -7.01 | -978.24 | 21-MAY-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 962.81 | 168.34 | 01-JAN-00:10 | 140297.40 | 10-AUG-15:30 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.85 | 15-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.85 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 1650.19 | 0.00 | 01-JAN-13:10 | 181707.10 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1650.19 | 0.00 | 01-JAN-13:10 | 181707.10 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1650.19 | 0.00 | 01-JAN-13:10 | 181707.10 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1650.19 | 0.00 | 01-JAN-13:10 | 181707.10 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.13 | 0.00 | 01-JAN-00:10 | 6708.28 | 02-JUL-12:10 |
ElectricitySurplusSold:Plant | 0.13 | 0.00 | 01-JAN-00:10 | 6708.28 | 02-JUL-12:10 |
Cogeneration:ElectricitySurplusSold | 0.13 | 0.00 | 01-JAN-00:10 | 6708.28 | 02-JUL-12:10 |
General:Cogeneration:ElectricitySurplusSold | 0.13 | 0.00 | 01-JAN-00:10 | 6708.28 | 02-JUL-12:10 |
ElectricityNet:Facility | 1650.07 | -6708.28 | 02-JUL-12:10 | 181707.10 | 10-AUG-16:00 |
ElectricityNet:Plant | 1650.07 | -6708.28 | 02-JUL-12:10 | 181707.10 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1650.07 | -6708.28 | 02-JUL-12:10 | 181707.10 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1650.07 | -6708.28 | 02-JUL-12:10 | 181707.10 | 10-AUG-16:00 |
Heating:Electricity | 0.42 | 0.00 | 01-JAN-00:10 | 4479.12 | 03-JAN-07:30 |
General:Heating:Electricity | 0.42 | 0.00 | 01-JAN-00:10 | 4479.12 | 03-JAN-07:30 |
Fans:Electricity | 155.17 | 0.00 | 01-JAN-00:10 | 25508.25 | 05-SEP-15:40 |
General:Fans:Electricity | 155.17 | 0.00 | 01-JAN-00:10 | 25508.25 | 05-SEP-15:40 |
ExteriorLights:Electricity | 33.87 | 0.00 | 01-JAN-07:10 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 33.87 | 0.00 | 01-JAN-07:10 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 795.60 | 0.00 | 01-JAN-00:10 | 116051.64 | 10-AUG-15:30 |
General:Cooling:Electricity | 795.60 | 0.00 | 01-JAN-00:10 | 116051.64 | 10-AUG-15:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
WIRED_LTG_ELECTRICITY | 4.67 | 0.00 | 01-JAN-00:10 | 476.68 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 108.62 | 1886.44 | 18-MAY-12:10 | 9526.98 | 09-JAN-12:40 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:Plant | 108.62 | 1886.44 | 18-MAY-12:10 | 9526.98 | 09-JAN-12:40 |
WaterSystems:NaturalGas | 108.62 | 1886.44 | 18-MAY-12:10 | 9526.98 | 09-JAN-12:40 |
Water Heater:WaterSystems:NaturalGas | 108.62 | 1886.44 | 18-MAY-12:10 | 9526.98 | 09-JAN-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-APR-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4781.21 | 0.00 | 01-JAN-00:10 | 530904.51 | 10-AUG-16:00 |
EnergyTransfer:Building | 1766.04 | 0.00 | 01-JAN-00:10 | 186966.83 | 05-SEP-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 267.55 | 0.00 | 01-JAN-00:10 | 23705.68 | 05-SEP-07:20 |
Heating:EnergyTransfer | 2.13 | 0.00 | 01-JAN-00:10 | 4701.89 | 02-JAN-07:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.13 | 0.00 | 01-JAN-00:10 | 4701.89 | 02-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1763.92 | 0.00 | 01-JAN-00:10 | 186966.83 | 05-SEP-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 267.55 | 0.00 | 01-JAN-00:10 | 23705.68 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 1763.92 | 0.00 | 01-JAN-00:10 | 186966.83 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 267.55 | 0.00 | 01-JAN-00:10 | 23705.68 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.78 | 0.00 | 01-JAN-00:10 | 14046.57 | 16-AUG-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.35 | 0.00 | 01-JAN-00:10 | 2234.35 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.35 | 0.00 | 01-JAN-00:10 | 2234.35 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 83.43 | 0.00 | 01-JAN-00:10 | 14046.57 | 16-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 83.43 | 0.00 | 01-JAN-00:10 | 14046.57 | 16-AUG-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 49.95 | 0.00 | 01-JAN-00:10 | 7273.84 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1335.73 | 16-JAN-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1335.73 | 16-JAN-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 49.71 | 0.00 | 01-JAN-00:10 | 7273.84 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 49.71 | 0.00 | 01-JAN-00:10 | 7273.84 | 05-SEP-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 53.45 | 0.00 | 01-JAN-00:10 | 7232.51 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.27 | 0.00 | 01-JAN-00:10 | 1318.59 | 01-JAN-13:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.27 | 0.00 | 01-JAN-00:10 | 1318.59 | 01-JAN-13:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 53.18 | 0.00 | 01-JAN-00:10 | 7232.51 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 53.18 | 0.00 | 01-JAN-00:10 | 7232.51 | 05-SEP-07:10 |
EnergyTransfer:Zone:CORE_MID | 217.89 | 0.00 | 01-JAN-00:10 | 20540.11 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 217.89 | 0.00 | 01-JAN-00:10 | 20540.11 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 217.89 | 0.00 | 01-JAN-00:10 | 20540.11 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 228.05 | 0.00 | 01-JAN-00:10 | 21625.06 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 228.05 | 0.00 | 01-JAN-00:10 | 21625.06 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 228.05 | 0.00 | 01-JAN-00:10 | 21625.06 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.41 | 0.00 | 01-JAN-00:10 | 9225.58 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.41 | 0.00 | 01-JAN-00:10 | 9225.58 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.41 | 0.00 | 01-JAN-00:10 | 9225.58 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.94 | 0.00 | 01-JAN-00:10 | 7908.04 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.94 | 0.00 | 01-JAN-00:10 | 7908.04 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.94 | 0.00 | 01-JAN-00:10 | 7908.04 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.34 | 0.00 | 01-JAN-00:10 | 11130.72 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.34 | 0.00 | 01-JAN-00:10 | 11130.72 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.34 | 0.00 | 01-JAN-00:10 | 11130.72 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.21 | 0.00 | 01-JAN-00:10 | 8096.51 | 09-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.21 | 0.00 | 01-JAN-00:10 | 8096.51 | 09-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.21 | 0.00 | 01-JAN-00:10 | 8096.51 | 09-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 75.00 | 0.00 | 01-JAN-00:10 | 8823.39 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 75.00 | 0.00 | 01-JAN-00:10 | 8823.39 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 75.00 | 0.00 | 01-JAN-00:10 | 8823.39 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.90 | 0.00 | 01-JAN-00:10 | 7470.74 | 31-JUL-10:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.90 | 0.00 | 01-JAN-00:10 | 7470.74 | 31-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 59.90 | 0.00 | 01-JAN-00:10 | 7470.74 | 31-JUL-10:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 113.16 | 0.00 | 01-JAN-00:10 | 18064.30 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.27 | 0.00 | 01-JAN-00:10 | 3492.30 | 13-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.27 | 0.00 | 01-JAN-00:10 | 3492.30 | 13-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 112.88 | 0.00 | 01-JAN-00:10 | 18064.30 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 112.88 | 0.00 | 01-JAN-00:10 | 18064.30 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 58.99 | 0.00 | 01-JAN-00:10 | 7471.20 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 58.99 | 0.00 | 01-JAN-00:10 | 7471.20 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 58.99 | 0.00 | 01-JAN-00:10 | 7471.20 | 05-SEP-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 71.81 | 0.00 | 01-JAN-00:10 | 8268.52 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 71.81 | 0.00 | 01-JAN-00:10 | 8268.52 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 71.81 | 0.00 | 01-JAN-00:10 | 8268.52 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.44 | 0.00 | 01-JAN-00:10 | 7639.03 | 31-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.44 | 0.00 | 01-JAN-00:10 | 7639.03 | 31-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.44 | 0.00 | 01-JAN-00:10 | 7639.03 | 31-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 87.34 | 0.00 | 01-JAN-00:10 | 10315.25 | 05-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 87.34 | 0.00 | 01-JAN-00:10 | 10315.25 | 05-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 87.34 | 0.00 | 01-JAN-00:10 | 10315.25 | 05-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.84 | 0.00 | 01-JAN-00:10 | 7490.96 | 31-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.84 | 0.00 | 01-JAN-00:10 | 7490.96 | 31-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.84 | 0.00 | 01-JAN-00:10 | 7490.96 | 31-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 31.56 | 0.00 | 01-JAN-00:10 | 4393.28 | 11-JAN-13:00 |
PlantLoopHeatingDemand:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4393.28 | 11-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4393.28 | 11-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 31.56 | 0.00 | 01-JAN-00:10 | 4393.28 | 11-JAN-13:00 |
EnergyTransfer:HVAC | 2983.61 | 0.00 | 01-JAN-00:10 | 357279.35 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.42 | 0.00 | 01-JAN-00:10 | 4479.12 | 03-JAN-07:30 |
CoolingCoils:EnergyTransfer | 2983.18 | 0.00 | 01-JAN-00:10 | 357279.35 | 10-AUG-16:00 |
EnergyTransfer:Plant | 31.56 | 0.00 | 01-JAN-00:10 | 4393.28 | 11-JAN-13:00 |
WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4393.28 | 11-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 31.56 | 0.00 | 01-JAN-00:10 | 4393.28 | 11-JAN-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -267.556 | 0.000 | 0.000 | 32.679 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 16.598 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -217.895 | 0.000 | 0.000 | 32.715 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 29.960 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -228.056 | 0.000 | 0.000 | 32.771 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 40.064 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -76.409 | 0.000 | 0.000 | 6.930 | 4.802 | 24.333 | 36.568 | 0.000 | 2.180 | 10.135 | 0.000 | -7.937 | 0.000 | -0.602 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -59.941 | 0.000 | 0.000 | 4.371 | 3.033 | 15.404 | 36.882 | 0.000 | 1.435 | 4.287 | 0.000 | -5.049 | 0.000 | -0.421 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -92.336 | 0.000 | 0.000 | 6.906 | 4.755 | 24.332 | 57.748 | 0.000 | 2.154 | 5.057 | 0.000 | -7.942 | 0.000 | -0.675 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -59.212 | 0.000 | 0.000 | 4.383 | 3.030 | 15.403 | 37.457 | 0.000 | 1.429 | 3.387 | 0.000 | -5.450 | 0.000 | -0.427 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -75.001 | 0.000 | 0.000 | 6.896 | 4.793 | 24.333 | 36.462 | 0.000 | 1.183 | 10.420 | 0.000 | -8.720 | 0.000 | -0.365 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -59.897 | 0.000 | 0.000 | 4.359 | 3.029 | 15.404 | 36.803 | 0.000 | 0.772 | 5.405 | 0.000 | -5.615 | 0.000 | -0.258 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.275 | -112.879 | 0.000 | 0.000 | 6.835 | 4.750 | 24.332 | 57.488 | 0.000 | 26.816 | 5.774 | 0.000 | -8.880 | 0.000 | -4.511 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -58.985 | 0.000 | 0.000 | 4.360 | 3.025 | 15.403 | 37.430 | 0.000 | 0.766 | 4.358 | 0.000 | -6.095 | 0.000 | -0.263 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -71.804 | 0.000 | 0.000 | 6.906 | 4.802 | 24.333 | 36.745 | 0.000 | 1.832 | 6.138 | 0.000 | -8.406 | 0.000 | -0.545 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -54.444 | 0.000 | 0.000 | 3.210 | 3.033 | 15.404 | 36.872 | 0.000 | 1.196 | 0.431 | 0.000 | -5.321 | 0.000 | -0.380 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -87.343 | 0.000 | 0.000 | 6.891 | 4.755 | 24.332 | 57.972 | 0.000 | 1.807 | 0.544 | 0.000 | -8.356 | 0.000 | -0.603 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -55.841 | 0.000 | 0.000 | 4.369 | 3.030 | 15.403 | 37.613 | 0.000 | 1.197 | 0.369 | 0.000 | -5.756 | 0.000 | -0.384 | -0.000 |
TOPFLOOR_PLENUM | 1.349 | -83.428 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.957 | 80.038 | 0.000 | 0.000 | 0.000 | -0.916 | 0.000 |
MIDFLOOR_PLENUM | 0.236 | -49.711 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.877 | 47.565 | 0.000 | 0.000 | 0.000 | -0.967 | 0.000 |
FIRSTFLOOR_PLENUM | 0.268 | -53.177 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.245 | 51.453 | 0.000 | 0.000 | 0.000 | -0.790 | 0.000 |
Total Facility | 1.854 | -186.316 | 0.275 | -1577.600 | 0.000 | 0.000 | 164.578 | 166.225 | 647.750 | 506.039 | 0.000 | 50.845 | 321.984 | 0.000 | -83.528 | 0.000 | -12.106 | -0.007 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 04-MAY-05:03 | 0.00 | 0.00 | 0.00 | -35890.44 | 0.00 | 0.00 | 307.95 | 211.73 | 4048.06 | 0.00 | 0.00 | 0.00 | 31322.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 15-MAY-05:14 | 0.00 | 0.00 | 0.00 | -33773.77 | 0.00 | 0.00 | 315.79 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 30044.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 23-OCT-04:02 | 0.00 | 0.00 | 0.00 | -35975.83 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 33146.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 21-MAY-13:02 | 0.00 | 0.00 | 0.00 | -15832.33 | 0.00 | 0.00 | 22.55 | 19.49 | 478.42 | 3279.23 | 0.00 | 2198.18 | 9834.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-JUL-09:21 | 0.00 | 0.00 | 0.00 | -13472.42 | 0.00 | 0.00 | 13.59 | 12.34 | 302.86 | 6916.85 | 0.00 | 235.31 | 5991.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 29-OCT-11:42 | 0.00 | 0.00 | 0.00 | -18084.45 | 0.00 | 0.00 | 24.00 | 19.49 | 478.41 | 8776.85 | 0.00 | 210.23 | 8575.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-SEP-16:42 | 0.00 | 0.00 | 0.00 | -14371.52 | 0.00 | 0.00 | 12.22 | 12.34 | 302.86 | 4208.79 | 0.00 | 427.84 | 9407.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-17:11 | 0.00 | 0.00 | 0.00 | -13584.45 | 0.00 | 0.00 | 0.00 | 20.79 | 386.10 | 2117.14 | 0.00 | 321.70 | 10738.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-09:21 | 0.00 | 0.00 | 0.00 | -11710.39 | 0.00 | 0.00 | 14.93 | 12.34 | 302.86 | 7012.36 | 0.00 | 131.04 | 4236.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | -18063.93 | 0.00 | 0.00 | 220.33 | 350.81 | 1275.77 | 5941.40 | 0.00 | 18520.37 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8244.75 |
PERIMETER_BOT_ZN_4 | 04-SEP-17:11 | 0.00 | 0.00 | 0.00 | -12747.42 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 3189.58 | 0.00 | 200.41 | 9100.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-SEP-17:11 | 0.00 | 0.00 | 0.00 | -13759.48 | 0.00 | 0.00 | 0.00 | 20.98 | 386.10 | 2141.03 | 0.00 | 498.19 | 10713.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-09:12 | 0.00 | 0.00 | 0.00 | -11983.92 | 0.00 | 0.00 | 14.77 | 12.34 | 302.86 | 5451.92 | 0.00 | 181.66 | 6020.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:32 | 0.00 | 0.00 | 0.00 | -15863.99 | 0.00 | 0.00 | 23.43 | 19.49 | 478.41 | 7945.06 | 0.00 | 206.30 | 7191.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-17:11 | 0.00 | 0.00 | 0.00 | -13416.17 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 3192.26 | 0.00 | 311.99 | 9655.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-AUG-13:30 | 0.00 | -14046.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.63 | 13773.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-12:04 | 0.00 | -7717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.72 | 7541.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:10 | 0.00 | -8549.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.40 | 8381.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:03 | 0.00 | -9981.52 | 0.00 | -217707.47 | 0.00 | 0.00 | 1555.13 | 1072.56 | 16350.06 | 4538.35 | 0.00 | 1536.68 | 202636.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-JAN-08:00 | 0.00 | 0.00 | 3492.51 | 0.00 | 0.00 | 0.00 | 184.79 | 116.94 | 637.88 | 778.91 | 0.00 | 0.00 | 3920.60 | 0.00 | -0.00 | 0.00 | -9131.62 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 25-SEP-04:02 | 4912.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -33.76 | -4878.28 |
MIDFLOOR_PLENUM | 28-JUL-04:02 | 3219.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3297.96 |
FIRSTFLOOR_PLENUM | 05-OCT-04:02 | 3607.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3632.02 |
Total Facility | 15-SEP-04:02 | -177363.51 | 186770.09 | 0.00 | -186770.09 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 99.47 | 0.00 | 698.21 | 161354.91 | 0.00 | -145.15 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.3219 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9745 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.0774 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6712 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7585 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6019 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6610 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0754 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5387 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0748 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8792 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0753 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3865 | 2.3865 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0587 | 2.0587 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3331 | 2.3331 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9016 | 0.9016 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7115 | 0.7115 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0019 | 1.0019 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8104 | 0.8104 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7621 | 0.7621 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6395 | 0.6395 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8546 | 0.8546 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6793 | 0.6793 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7708 | 0.7708 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6616 | 0.6616 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8693 | 0.8693 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7170 | 0.7170 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.3219 | 4.9745 | 5.3219 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.0774 | 4.6712 | 5.0774 | 1.0748 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7585 | 5.6019 | 5.7585 | 1.0753 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1932 | 1.1932 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0293 | 1.0293 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1666 | 1.1666 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4508 | 0.4508 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3557 | 0.3557 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5010 | 0.5010 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4052 | 0.4052 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3810 | 0.3810 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3197 | 0.3197 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4273 | 0.4273 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3396 | 0.3396 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3854 | 0.3854 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3308 | 0.3308 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4347 | 0.4347 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3585 | 0.3585 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6610 | 1.0754 | 1.0754 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5387 | 1.0748 | 1.0748 | 1.0748 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8792 | 1.0753 | 1.0753 | 1.0753 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 3.33 |
Number of hours cooling loads not met | 574.17 |
Number of hours not met | 577.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.42 | 4479.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 795.60 | 116051.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 166.22 | 16963.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 33.87 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 828.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 155.17 | 25508.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 108.62 | 9526.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1810.81 |
Natural Gas | 0.00 | 108.62 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1919.43 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 167.75 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.36 |
Space Heating | 0.09 |
Space Cooling | 159.69 |
Fans (All) | 31.14 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 363.46 |
Subtotal | 363.46 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 21.80 |
Miscellaneous (All) | 21.80 |
Subtotal | 21.80 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.66 |
Space Heating | 0.02 |
Space Cooling | 41.45 |
Fans (All) | 8.08 |
Service Water Heating | 5.66 |
Receptacle Equipment | 33.75 |
Miscellaneous | 2.38 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1019. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8724.83 | 35.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7781.33 | 978.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7605.17 | 1154.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7641.00 | 1119.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7544.17 | 1215.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8028.17 | 731.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7688.17 | 1071.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7606.50 | 1153.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7581.00 | 1179.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7800.67 | 959.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7594.67 | 1165.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7645.00 | 1115.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7513.83 | 1246.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7830.17 | 929.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8276.33 | 483.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8475.67 | 284.33 | 0.00 | 0.00 | 0.00 |
Min | 7513.83 | 9.17 | 0.00 | 0.00 | 0.00 |
Max | 8750.83 | 1246.17 | 0.00 | 0.00 | 0.00 |
Average | 7934.62 | 825.38 | 0.00 | 0.00 | 0.00 |
Sum | 142823.17 | 14856.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128302.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128289.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24457.33 | 451.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128302.00 | 451.67 | 0.00 | 0.00 | 0.00 |
Average | 34117.06 | 26.28 | 0.00 | 0.00 | 0.00 |
Sum | 614107.00 | 473.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7349.67 | 1410.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7245.00 | 1515.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7393.50 | 1366.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6377.00 | 2383.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6268.33 | 2491.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6249.17 | 2510.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6264.67 | 2495.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6363.50 | 2396.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6203.00 | 2557.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5432.00 | 3328.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6178.33 | 2581.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6266.33 | 2493.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6156.17 | 2603.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6133.33 | 2626.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6141.33 | 2618.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4473.17 | 4286.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 4947.17 | 3812.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 5616.00 | 3144.00 | 0.00 | 0.00 | 0.00 |
Min | 4473.17 | 1366.50 | 0.00 | 0.00 | 0.00 |
Max | 7393.50 | 4286.83 | 0.00 | 0.00 | 0.00 |
Average | 6169.87 | 2590.13 | 0.00 | 0.00 | 0.00 |
Sum | 111057.67 | 46622.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127586.00 | 718.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127527.33 | 776.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127525.00 | 779.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24790.17 | 118.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14011.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24791.50 | 117.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24800.00 | 109.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21013.33 | 3895.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24782.33 | 126.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24781.83 | 127.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127586.00 | 3895.67 | 0.00 | 0.00 | 0.00 |
Average | 33766.69 | 376.64 | 0.00 | 0.00 | 0.00 |
Sum | 607800.50 | 6779.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176780E+11 | 32471.52 | 17-JAN-07:02 | 16.08 | 12.60 | 0.199253E+10 | 2606.70 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.166522E+11 | 33008.29 | 21-FEB-07:02 | 13.92 | 13.01 | 0.180821E+10 | 2606.75 | 15-FEB-14:09 | 13.92 | 13.01 |
March | 0.205102E+11 | 34730.73 | 28-MAR-05:03 | 25.67 | 14.74 | 0.215933E+10 | 2606.81 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.203172E+11 | 35536.12 | 24-APR-05:12 | 21.67 | 13.88 | 0.191730E+10 | 2606.88 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.245515E+11 | 35891.09 | 04-MAY-05:03 | 24.00 | 18.14 | 0.207710E+10 | 2606.77 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.249472E+11 | 35784.81 | 06-JUN-04:03 | 25.92 | 21.78 | 0.207027E+10 | 2606.71 | 02-JUN-13:09 | 25.92 | 21.78 |
July | 0.259274E+11 | 31518.13 | 03-JUL-06:03 | 28.20 | 16.17 | 0.192283E+10 | 2606.85 | 03-JUL-09:30 | 35.10 | 24.31 |
August | 0.277431E+11 | 30922.43 | 07-AUG-05:03 | 32.82 | 23.16 | 0.215777E+10 | 2606.63 | 25-AUG-13:20 | 36.47 | 27.84 |
September | 0.247640E+11 | 35142.56 | 26-SEP-04:03 | 26.97 | 19.72 | 0.191746E+10 | 2606.65 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.242950E+11 | 35406.83 | 17-OCT-04:03 | 25.25 | 24.38 | 0.199424E+10 | 2606.64 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.215964E+11 | 35724.67 | 27-NOV-06:12 | 17.80 | 15.99 | 0.197503E+10 | 2606.68 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.185715E+11 | 33634.64 | 26-DEC-07:01 | 14.00 | 14.00 | 0.192326E+10 | 2606.69 | 08-DEC-10:39 | 14.00 | 14.00 |
Annual Sum or Average | 0.267554E+12 | 0.239153E+11 | ||||||||
Minimum of Months | 0.166522E+11 | 30922.43 | 13.92 | 12.60 | 0.180821E+10 | 2606.63 | 13.92 | 13.01 | ||
Maximum of Months | 0.277431E+11 | 35891.09 | 32.82 | 24.38 | 0.215933E+10 | 2606.88 | 36.47 | 27.84 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187437E+10 | 4967.12 | 31-JAN-14:05 | 23.00 | 16.33 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 16.33 |
February | 0.258999E+10 | 7860.33 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.438486E+10 | 10775.74 | 27-MAR-13:30 | 35.50 | 19.59 | 0.00 | 0.00 | 01-MAR-00:10 | 35.50 | 19.59 |
April | 0.600216E+10 | 11861.91 | 28-APR-12:40 | 38.47 | 22.15 | 0.00 | 0.00 | 01-APR-00:10 | 38.47 | 22.15 |
May | 0.967052E+10 | 12264.04 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.105982E+11 | 13052.09 | 12-JUN-13:05 | 40.25 | 27.32 | 0.00 | 0.00 | 01-JUN-00:10 | 40.25 | 27.32 |
July | 0.117999E+11 | 14002.02 | 21-JUL-12:02 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.124097E+11 | 14046.57 | 16-AUG-13:30 | 44.10 | 25.63 | 0.00 | 0.00 | 01-AUG-00:10 | 44.10 | 25.63 |
September | 0.949513E+10 | 13120.74 | 05-SEP-14:20 | 39.67 | 25.10 | 0.00 | 0.00 | 01-SEP-00:10 | 39.67 | 25.10 |
October | 0.745599E+10 | 11015.88 | 02-OCT-14:05 | 35.82 | 20.34 | 0.00 | 0.00 | 01-OCT-00:10 | 35.82 | 20.34 |
November | 0.470595E+10 | 9093.67 | 06-NOV-14:05 | 32.83 | 20.61 | 0.00 | 0.00 | 01-NOV-00:10 | 32.83 | 20.61 |
December | 0.244103E+10 | 6563.47 | 04-DEC-13:50 | 27.17 | 20.95 | 0.00 | 0.00 | 01-DEC-00:10 | 27.17 | 20.95 |
Annual Sum or Average | 0.834278E+11 | 0.00 | ||||||||
Minimum of Months | 0.187437E+10 | 4967.12 | 23.00 | 16.33 | 0.00 | 0.00 | 23.00 | 16.33 | ||
Maximum of Months | 0.124097E+11 | 14046.57 | 45.38 | 27.32 | 0.00 | 0.00 | 45.38 | 27.32 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104162E+10 | 2001.35 | 31-JAN-15:30 | 22.80 | 16.62 | 0.00 | 0.00 | 01-JAN-00:10 | 22.80 | 16.62 |
February | 0.145108E+10 | 3902.46 | 06-FEB-15:20 | 32.13 | 17.39 | 0.00 | 0.00 | 01-FEB-00:10 | 32.13 | 17.39 |
March | 0.252048E+10 | 5301.24 | 27-MAR-12:05 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.341521E+10 | 5435.59 | 24-APR-12:04 | 37.07 | 17.93 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 17.93 |
May | 0.567204E+10 | 7128.25 | 22-MAY-12:03 | 38.02 | 22.04 | 0.00 | 0.00 | 01-MAY-00:10 | 38.02 | 22.04 |
June | 0.615216E+10 | 7685.36 | 12-JUN-06:15 | 30.03 | 23.76 | 0.00 | 0.00 | 01-JUN-00:10 | 30.03 | 23.76 |
July | 0.670262E+10 | 7616.97 | 31-JUL-12:02 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.714558E+10 | 7486.68 | 21-AUG-06:15 | 30.00 | 28.39 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 28.39 |
September | 0.582841E+10 | 7717.33 | 05-SEP-12:04 | 40.98 | 24.12 | 0.00 | 0.00 | 01-SEP-00:10 | 40.98 | 24.12 |
October | 0.492977E+10 | 6209.27 | 10-OCT-15:20 | 34.70 | 20.18 | 0.00 | 0.00 | 01-OCT-00:10 | 34.70 | 20.18 |
November | 0.326022E+10 | 5191.44 | 06-NOV-15:20 | 31.80 | 21.81 | 0.00 | 0.00 | 01-NOV-00:10 | 31.80 | 21.81 |
December | 0.159226E+10 | 3240.37 | 04-DEC-15:20 | 26.73 | 21.25 | 0.00 | 0.00 | 01-DEC-00:10 | 26.73 | 21.25 |
Annual Sum or Average | 0.497114E+11 | 0.00 | ||||||||
Minimum of Months | 0.104162E+10 | 2001.35 | 22.80 | 16.62 | 0.00 | 0.00 | 22.80 | 16.62 | ||
Maximum of Months | 0.714558E+10 | 7717.33 | 40.98 | 28.39 | 0.00 | 0.00 | 40.98 | 28.39 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172173E+10 | 2627.85 | 30-JAN-14:00 | 23.00 | 20.89 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 20.89 |
February | 0.199852E+10 | 4184.69 | 06-FEB-15:50 | 31.58 | 17.52 | 0.00 | 0.00 | 01-FEB-00:10 | 31.58 | 17.52 |
March | 0.297369E+10 | 6550.79 | 27-MAR-12:09 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.363694E+10 | 6237.83 | 24-APR-12:09 | 37.07 | 17.93 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 17.93 |
May | 0.564932E+10 | 8047.49 | 30-MAY-12:06 | 36.22 | 27.34 | 0.00 | 0.00 | 01-MAY-00:10 | 36.22 | 27.34 |
June | 0.609060E+10 | 7826.32 | 05-JUN-12:06 | 37.18 | 23.51 | 0.00 | 0.00 | 01-JUN-00:10 | 37.18 | 23.51 |
July | 0.649685E+10 | 8549.42 | 31-JUL-12:10 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.698890E+10 | 8206.94 | 28-AUG-12:09 | 37.92 | 28.31 | 0.00 | 0.00 | 01-AUG-00:10 | 37.92 | 28.31 |
September | 0.594018E+10 | 7960.99 | 25-SEP-12:10 | 38.83 | 22.60 | 0.00 | 0.00 | 01-SEP-00:10 | 38.83 | 22.60 |
October | 0.532820E+10 | 6432.60 | 04-OCT-12:10 | 37.77 | 20.04 | 0.00 | 0.00 | 01-OCT-00:10 | 37.77 | 20.04 |
November | 0.400950E+10 | 5357.71 | 13-NOV-16:10 | 30.00 | 21.15 | 0.00 | 0.00 | 01-NOV-00:10 | 30.00 | 21.15 |
December | 0.234266E+10 | 4254.92 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.531771E+11 | 0.00 | ||||||||
Minimum of Months | 0.172173E+10 | 2627.85 | 23.00 | 17.52 | 0.00 | 0.00 | 23.00 | 17.52 | ||
Maximum of Months | 0.698890E+10 | 8549.42 | 40.98 | 28.31 | 0.00 | 0.00 | 40.98 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124021E+11 | 15951.63 | 30-JAN-07:03 | 20.17 | 17.39 | 0.198073E+10 | 2606.68 | 17-JAN-10:20 | 20.17 | 17.39 |
February | 0.122014E+11 | 24275.68 | 06-FEB-07:03 | 21.25 | 17.86 | 0.180115E+10 | 2606.73 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.157898E+11 | 29768.63 | 28-MAR-05:03 | 25.67 | 14.74 | 0.215522E+10 | 2606.80 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.165978E+11 | 30770.34 | 24-APR-05:12 | 21.67 | 13.88 | 0.191553E+10 | 2606.83 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.211568E+11 | 33777.74 | 15-MAY-05:14 | 23.00 | 17.48 | 0.207649E+10 | 2606.78 | 08-MAY-13:39 | 23.00 | 17.48 |
June | 0.216791E+11 | 31268.00 | 06-JUN-04:03 | 25.92 | 21.78 | 0.206987E+10 | 2606.76 | 02-JUN-13:09 | 25.92 | 21.78 |
July | 0.229935E+11 | 28753.92 | 03-JUL-06:03 | 28.20 | 16.17 | 0.192287E+10 | 2606.83 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.241452E+11 | 28185.58 | 15-AUG-06:03 | 29.85 | 21.21 | 0.215815E+10 | 2606.63 | 07-AUG-13:20 | 29.85 | 21.21 |
September | 0.208814E+11 | 31232.64 | 26-SEP-04:03 | 26.97 | 19.72 | 0.191747E+10 | 2606.66 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.199080E+11 | 31564.75 | 17-OCT-04:03 | 25.25 | 24.38 | 0.199382E+10 | 2606.64 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.166584E+11 | 31865.11 | 13-NOV-06:12 | 20.83 | 17.71 | 0.197270E+10 | 2606.69 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.134797E+11 | 28097.83 | 04-DEC-07:02 | 17.83 | 16.73 | 0.191561E+10 | 2606.67 | 08-DEC-10:20 | 23.20 | 18.74 |
Annual Sum or Average | 0.217893E+12 | 0.238796E+11 | ||||||||
Minimum of Months | 0.122014E+11 | 15951.63 | 17.83 | 13.88 | 0.180115E+10 | 2606.63 | 20.17 | 17.39 | ||
Maximum of Months | 0.241452E+11 | 33777.74 | 29.85 | 24.38 | 0.215815E+10 | 2606.83 | 35.57 | 23.66 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112462E+11 | 13573.62 | 30-JAN-14:50 | 22.17 | 20.62 | 0.195592E+10 | 2606.66 | 17-JAN-14:20 | 22.17 | 20.62 |
February | 0.115762E+11 | 17066.02 | 06-FEB-07:03 | 21.25 | 17.86 | 0.178751E+10 | 2606.74 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.156603E+11 | 34234.90 | 28-MAR-05:03 | 25.67 | 14.74 | 0.214784E+10 | 2606.81 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.173130E+11 | 34816.31 | 24-APR-05:12 | 21.67 | 13.88 | 0.191392E+10 | 2606.84 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.231176E+11 | 35195.39 | 01-MAY-05:12 | 20.87 | 20.87 | 0.207769E+10 | 2606.80 | 08-MAY-13:39 | 35.50 | 23.99 |
June | 0.239974E+11 | 35695.40 | 06-JUN-04:03 | 25.92 | 21.78 | 0.207116E+10 | 2606.79 | 02-JUN-13:09 | 25.92 | 21.78 |
July | 0.259954E+11 | 32775.51 | 10-JUL-06:03 | 31.98 | 24.04 | 0.192494E+10 | 2606.86 | 03-JUL-09:39 | 31.98 | 24.04 |
August | 0.271137E+11 | 32820.85 | 07-AUG-06:03 | 31.98 | 22.90 | 0.215970E+10 | 2606.61 | 03-AUG-13:20 | 31.98 | 22.90 |
September | 0.226621E+11 | 35928.79 | 25-SEP-04:02 | 24.17 | 23.10 | 0.191868E+10 | 2606.66 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.205642E+11 | 35977.81 | 23-OCT-04:02 | 25.42 | 23.19 | 0.199442E+10 | 2606.68 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.162939E+11 | 35766.69 | 20-NOV-05:02 | 26.00 | 18.81 | 0.197019E+10 | 2606.68 | 28-NOV-10:50 | 25.93 | 20.29 |
December | 0.125141E+11 | 15280.25 | 04-DEC-14:50 | 27.00 | 21.43 | 0.190082E+10 | 2606.67 | 01-DEC-14:20 | 27.00 | 21.43 |
Annual Sum or Average | 0.228054E+12 | 0.238228E+11 | ||||||||
Minimum of Months | 0.112462E+11 | 13573.62 | 20.87 | 13.88 | 0.178751E+10 | 2606.61 | 22.17 | 18.27 | ||
Maximum of Months | 0.271137E+11 | 35977.81 | 31.98 | 24.04 | 0.215970E+10 | 2606.86 | 35.57 | 24.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234846E+10 | 3935.59 | 23-JAN-14:10 | 27.50 | 16.66 | 0.400860E+09 | 549.50 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.273136E+10 | 5731.33 | 06-FEB-15:00 | 32.50 | 17.28 | 0.370614E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.427934E+10 | 7222.98 | 02-MAR-06:03 | 28.80 | 15.43 | 0.449406E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.549611E+10 | 12048.49 | 23-APR-14:13 | 32.00 | 18.41 | 0.403113E+09 | 549.54 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.860049E+10 | 15835.44 | 21-MAY-13:02 | 38.00 | 22.80 | 0.438989E+09 | 549.54 | 08-MAY-13:39 | 38.00 | 22.80 |
June | 0.949909E+10 | 14811.42 | 18-JUN-14:32 | 36.00 | 26.94 | 0.437712E+09 | 549.53 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.104663E+11 | 15776.67 | 30-JUL-14:01 | 43.50 | 24.98 | 0.407390E+09 | 549.55 | 03-JUL-09:39 | 43.50 | 24.98 |
August | 0.107676E+11 | 15119.31 | 06-AUG-15:02 | 40.85 | 24.99 | 0.456633E+09 | 549.49 | 04-AUG-13:20 | 40.85 | 24.99 |
September | 0.823568E+10 | 15491.93 | 04-SEP-16:42 | 40.12 | 23.11 | 0.405551E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.666206E+10 | 14304.00 | 09-OCT-14:42 | 37.00 | 20.65 | 0.421130E+09 | 549.51 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.450656E+10 | 7930.82 | 12-NOV-14:02 | 29.83 | 18.49 | 0.414543E+09 | 549.50 | 20-NOV-10:20 | 27.40 | 19.00 |
December | 0.281620E+10 | 4452.42 | 11-DEC-14:10 | 26.77 | 18.23 | 0.394693E+09 | 549.50 | 01-DEC-14:20 | 26.77 | 18.23 |
Annual Sum or Average | 0.764093E+11 | 0.500063E+10 | ||||||||
Minimum of Months | 0.234846E+10 | 3935.59 | 26.77 | 15.43 | 0.370614E+09 | 549.49 | 25.67 | 16.66 | ||
Maximum of Months | 0.107676E+11 | 15835.44 | 43.50 | 26.94 | 0.456633E+09 | 549.55 | 43.50 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189475E+10 | 2940.89 | 24-JAN-11:00 | 24.00 | 17.69 | 0.259930E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.222039E+10 | 6498.52 | 05-FEB-14:53 | 32.00 | 19.39 | 0.237979E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.344753E+10 | 7220.31 | 26-MAR-11:33 | 33.67 | 17.01 | 0.286094E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.455296E+10 | 11835.22 | 30-APR-12:13 | 37.03 | 20.80 | 0.255748E+09 | 347.91 | 25-APR-09:09 | 37.03 | 20.80 |
May | 0.680933E+10 | 12514.41 | 21-MAY-13:02 | 38.00 | 22.80 | 0.278077E+09 | 348.03 | 22-MAY-09:50 | 36.25 | 22.78 |
June | 0.721219E+10 | 12746.21 | 18-JUN-09:12 | 35.53 | 24.85 | 0.277186E+09 | 347.89 | 02-JUN-13:09 | 35.53 | 24.85 |
July | 0.785268E+10 | 13472.62 | 30-JUL-09:21 | 40.60 | 21.47 | 0.258024E+09 | 347.91 | 03-JUL-09:09 | 40.60 | 21.47 |
August | 0.826409E+10 | 12373.70 | 13-AUG-10:32 | 39.20 | 25.03 | 0.289179E+09 | 348.03 | 04-AUG-09:09 | 39.20 | 25.03 |
September | 0.648229E+10 | 12344.43 | 04-SEP-10:02 | 38.00 | 23.07 | 0.256893E+09 | 347.88 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.536807E+10 | 12134.58 | 01-OCT-10:32 | 32.73 | 26.12 | 0.266865E+09 | 347.88 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.363048E+10 | 9717.35 | 05-NOV-11:32 | 33.43 | 17.72 | 0.263255E+09 | 347.88 | 28-NOV-10:39 | 25.87 | 20.07 |
December | 0.220673E+10 | 3418.84 | 04-DEC-11:00 | 26.00 | 20.51 | 0.253170E+09 | 347.88 | 01-DEC-10:20 | 26.00 | 20.51 |
Annual Sum or Average | 0.599415E+11 | 0.318240E+10 | ||||||||
Minimum of Months | 0.189475E+10 | 2940.89 | 24.00 | 17.01 | 0.237979E+09 | 347.88 | 24.00 | 17.69 | ||
Maximum of Months | 0.826409E+10 | 13472.62 | 40.60 | 26.12 | 0.289179E+09 | 348.03 | 40.60 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434304E+10 | 10019.12 | 22-JAN-14:33 | 26.00 | 16.51 | 0.410689E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.458412E+10 | 17360.65 | 05-FEB-12:53 | 31.10 | 19.64 | 0.375116E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.590497E+10 | 12733.49 | 26-MAR-14:13 | 32.87 | 18.44 | 0.450940E+09 | 549.54 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.630261E+10 | 17038.59 | 30-APR-12:13 | 37.03 | 20.80 | 0.403358E+09 | 549.55 | 28-APR-13:09 | 37.03 | 20.80 |
May | 0.863921E+10 | 17551.00 | 21-MAY-13:02 | 38.00 | 22.80 | 0.438955E+09 | 549.54 | 08-MAY-13:39 | 38.00 | 22.80 |
June | 0.912545E+10 | 16283.57 | 18-JUN-14:32 | 36.00 | 26.94 | 0.437652E+09 | 549.53 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.103542E+11 | 17612.82 | 30-JUL-14:01 | 43.50 | 24.98 | 0.407358E+09 | 549.55 | 03-JUL-09:39 | 43.50 | 24.98 |
August | 0.113636E+11 | 16820.38 | 06-AUG-15:02 | 40.85 | 24.99 | 0.456665E+09 | 549.49 | 04-AUG-13:20 | 40.85 | 24.99 |
September | 0.985606E+10 | 17615.80 | 04-SEP-14:42 | 41.00 | 24.39 | 0.405729E+09 | 549.68 | 26-SEP-13:50 | 39.37 | 23.60 |
October | 0.938671E+10 | 18077.94 | 29-OCT-11:42 | 34.42 | 15.83 | 0.421628E+09 | 549.79 | 10-OCT-13:00 | 34.42 | 15.83 |
November | 0.739044E+10 | 18021.30 | 05-NOV-11:32 | 33.43 | 17.72 | 0.416060E+09 | 549.65 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.508638E+10 | 17527.44 | 03-DEC-12:43 | 29.50 | 17.81 | 0.400639E+09 | 549.51 | 01-DEC-14:09 | 29.50 | 17.81 |
Annual Sum or Average | 0.923367E+11 | 0.502479E+10 | ||||||||
Minimum of Months | 0.434304E+10 | 10019.12 | 26.00 | 15.83 | 0.375116E+09 | 549.49 | 24.00 | 15.83 | ||
Maximum of Months | 0.113636E+11 | 18077.94 | 43.50 | 26.94 | 0.456665E+09 | 549.79 | 43.50 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190672E+10 | 3620.55 | 31-JAN-16:20 | 22.73 | 16.79 | 0.254782E+09 | 347.85 | 23-JAN-14:00 | 22.73 | 16.79 |
February | 0.227352E+10 | 10192.97 | 05-FEB-15:32 | 32.00 | 19.08 | 0.235233E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.355043E+10 | 8466.94 | 26-MAR-15:32 | 32.07 | 18.56 | 0.284997E+09 | 347.88 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.439003E+10 | 12017.73 | 23-APR-14:13 | 32.00 | 18.41 | 0.255425E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.657121E+10 | 14044.82 | 21-MAY-16:22 | 37.25 | 23.23 | 0.278013E+09 | 347.88 | 04-MAY-13:00 | 37.25 | 23.23 |
June | 0.711305E+10 | 13686.96 | 18-JUN-14:32 | 36.00 | 26.94 | 0.277183E+09 | 347.87 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.774176E+10 | 14270.13 | 30-JUL-14:01 | 43.50 | 24.98 | 0.257992E+09 | 347.88 | 03-JUL-09:39 | 43.50 | 24.98 |
August | 0.812450E+10 | 13922.97 | 06-AUG-15:02 | 40.85 | 24.99 | 0.289173E+09 | 347.85 | 15-AUG-09:20 | 36.77 | 22.00 |
September | 0.638329E+10 | 14376.26 | 04-SEP-16:42 | 40.12 | 23.11 | 0.256876E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.525139E+10 | 13816.53 | 09-OCT-15:22 | 36.90 | 19.74 | 0.266777E+09 | 347.86 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.363251E+10 | 11153.86 | 12-NOV-16:03 | 29.08 | 17.59 | 0.262739E+09 | 347.86 | 20-NOV-10:20 | 27.40 | 19.00 |
December | 0.227435E+10 | 4313.43 | 06-DEC-15:30 | 26.85 | 20.67 | 0.250604E+09 | 347.86 | 01-DEC-14:20 | 26.85 | 20.67 |
Annual Sum or Average | 0.592128E+11 | 0.316979E+10 | ||||||||
Minimum of Months | 0.190672E+10 | 3620.55 | 22.73 | 16.79 | 0.235233E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.812450E+10 | 14376.26 | 43.50 | 26.94 | 0.289173E+09 | 347.88 | 43.50 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272894E+10 | 3855.31 | 23-JAN-14:10 | 27.50 | 16.66 | 0.414619E+09 | 549.51 | 17-JAN-10:20 | 27.50 | 16.66 |
February | 0.280967E+10 | 5023.08 | 06-FEB-15:00 | 32.50 | 17.28 | 0.377486E+09 | 549.51 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.389934E+10 | 6661.16 | 02-MAR-06:03 | 28.80 | 15.43 | 0.452448E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.471544E+10 | 6264.78 | 28-APR-12:50 | 37.58 | 22.61 | 0.403487E+09 | 549.55 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.747967E+10 | 10718.17 | 28-MAY-15:02 | 35.08 | 23.30 | 0.438718E+09 | 549.53 | 04-MAY-13:00 | 35.08 | 23.30 |
June | 0.847578E+10 | 12706.56 | 18-JUN-14:13 | 36.00 | 26.94 | 0.437527E+09 | 549.51 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.959581E+10 | 13126.57 | 23-JUL-11:22 | 38.50 | 24.78 | 0.407201E+09 | 549.55 | 03-JUL-09:09 | 38.50 | 24.78 |
August | 0.105057E+11 | 12912.67 | 06-AUG-15:02 | 40.85 | 24.99 | 0.456515E+09 | 549.50 | 04-AUG-13:00 | 40.85 | 24.99 |
September | 0.852677E+10 | 13589.64 | 04-SEP-17:11 | 39.33 | 23.70 | 0.405525E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.738149E+10 | 11645.01 | 08-OCT-11:52 | 34.00 | 27.29 | 0.421421E+09 | 549.50 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.542020E+10 | 10064.84 | 13-NOV-07:03 | 20.75 | 17.82 | 0.416329E+09 | 549.50 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.346192E+10 | 5865.89 | 11-DEC-07:03 | 21.50 | 18.56 | 0.403371E+09 | 549.51 | 08-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.750008E+11 | 0.503465E+10 | ||||||||
Minimum of Months | 0.272894E+10 | 3855.31 | 20.75 | 15.43 | 0.377486E+09 | 549.50 | 21.50 | 16.66 | ||
Maximum of Months | 0.105057E+11 | 13589.64 | 40.85 | 27.29 | 0.456515E+09 | 549.55 | 40.85 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230430E+10 | 3167.85 | 24-JAN-11:00 | 24.00 | 17.69 | 0.264524E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.235429E+10 | 3708.75 | 06-FEB-14:10 | 32.08 | 17.23 | 0.240304E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.323467E+10 | 5597.20 | 27-MAR-10:50 | 37.50 | 18.71 | 0.287287E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.402464E+10 | 7435.04 | 30-APR-10:23 | 31.50 | 22.64 | 0.256004E+09 | 347.91 | 28-APR-13:09 | 31.50 | 22.64 |
May | 0.608620E+10 | 9938.37 | 29-MAY-10:42 | 37.35 | 22.00 | 0.278005E+09 | 347.98 | 22-MAY-09:00 | 37.35 | 22.00 |
June | 0.655621E+10 | 11097.56 | 04-JUN-09:53 | 36.20 | 25.06 | 0.277122E+09 | 347.88 | 02-JUN-13:09 | 36.20 | 25.06 |
July | 0.733855E+10 | 11711.19 | 30-JUL-09:21 | 40.60 | 21.47 | 0.257947E+09 | 347.91 | 03-JUL-09:09 | 40.60 | 21.47 |
August | 0.818419E+10 | 10941.23 | 13-AUG-10:32 | 39.20 | 25.03 | 0.289141E+09 | 347.88 | 04-AUG-13:00 | 39.20 | 25.03 |
September | 0.677681E+10 | 11572.06 | 04-SEP-09:12 | 36.53 | 22.23 | 0.256917E+09 | 347.88 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.592943E+10 | 10717.88 | 08-OCT-11:52 | 34.00 | 27.29 | 0.267079E+09 | 347.88 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.433819E+10 | 8002.28 | 05-NOV-10:43 | 31.82 | 18.97 | 0.264022E+09 | 347.88 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.276986E+10 | 4499.95 | 11-DEC-07:03 | 21.50 | 18.56 | 0.256106E+09 | 347.88 | 08-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.598973E+11 | 0.319446E+10 | ||||||||
Minimum of Months | 0.230430E+10 | 3167.85 | 21.50 | 17.23 | 0.240304E+09 | 347.88 | 21.50 | 17.69 | ||
Maximum of Months | 0.818419E+10 | 11711.19 | 40.60 | 27.29 | 0.289141E+09 | 347.98 | 40.60 | 25.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429257E+10 | 10701.52 | 23-JAN-13:00 | 27.40 | 16.52 | 0.411813E+09 | 549.52 | 23-JAN-14:39 | 26.00 | 16.86 |
February | 0.456008E+10 | 14735.88 | 05-FEB-14:43 | 31.93 | 19.38 | 0.375940E+09 | 585.29 | 07-FEB-13:09 | 31.00 | 20.70 |
March | 0.608350E+10 | 15076.17 | 27-MAR-12:00 | 37.30 | 19.38 | 0.450769E+09 | 706.38 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.689854E+10 | 16378.57 | 28-APR-12:00 | 42.00 | 19.18 | 0.404775E+09 | 781.80 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.104607E+11 | 15998.75 | 09-MAY-12:00 | 41.00 | 19.42 | 0.446214E+09 | 758.05 | 09-MAY-12:09 | 41.02 | 19.49 |
June | 0.115625E+11 | 16880.35 | 12-JUN-12:00 | 43.00 | 24.56 | 0.447327E+09 | 800.77 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.130557E+11 | 17745.58 | 21-JUL-12:00 | 46.00 | 22.01 | 0.418433E+09 | 857.41 | 21-JUL-12:09 | 45.38 | 23.17 |
August | 0.152165E+11 | 18064.30 | 16-AUG-12:00 | 46.00 | 25.38 | 0.472366E+09 | 871.04 | 16-AUG-12:09 | 45.70 | 25.45 |
September | 0.130680E+11 | 16759.41 | 05-SEP-12:00 | 41.00 | 24.24 | 0.417360E+09 | 794.30 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.123275E+11 | 15579.09 | 04-OCT-12:00 | 38.00 | 19.81 | 0.430025E+09 | 731.61 | 04-OCT-12:09 | 37.77 | 20.04 |
November | 0.956855E+10 | 15376.42 | 12-NOV-13:12 | 29.53 | 19.09 | 0.419159E+09 | 643.49 | 06-NOV-13:09 | 29.53 | 19.09 |
December | 0.578599E+10 | 15025.99 | 25-DEC-13:23 | 27.25 | 17.58 | 0.401787E+09 | 559.75 | 04-DEC-13:09 | 27.25 | 17.58 |
Annual Sum or Average | 0.112880E+12 | 0.509597E+10 | ||||||||
Minimum of Months | 0.429257E+10 | 10701.52 | 27.25 | 16.52 | 0.375940E+09 | 549.52 | 26.00 | 16.86 | ||
Maximum of Months | 0.152165E+11 | 18064.30 | 46.00 | 25.38 | 0.472366E+09 | 871.04 | 45.70 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223243E+10 | 3476.18 | 31-JAN-16:30 | 22.80 | 16.92 | 0.263683E+09 | 347.86 | 17-JAN-10:20 | 22.80 | 16.92 |
February | 0.235237E+10 | 5169.73 | 05-FEB-14:43 | 31.93 | 19.38 | 0.239829E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.331804E+10 | 5868.64 | 26-MAR-16:12 | 31.60 | 18.63 | 0.287179E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.386146E+10 | 9595.19 | 02-APR-15:23 | 31.70 | 18.45 | 0.255886E+09 | 347.89 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.585330E+10 | 11612.33 | 28-MAY-15:02 | 35.08 | 23.30 | 0.277959E+09 | 347.88 | 04-MAY-13:00 | 35.08 | 23.30 |
June | 0.647548E+10 | 11509.73 | 18-JUN-14:13 | 36.00 | 26.94 | 0.277133E+09 | 347.86 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.723628E+10 | 11873.68 | 04-JUL-15:22 | 39.20 | 27.54 | 0.257927E+09 | 347.88 | 03-JUL-09:09 | 39.20 | 27.54 |
August | 0.805590E+10 | 11872.16 | 06-AUG-16:22 | 40.05 | 25.93 | 0.289149E+09 | 347.85 | 04-AUG-13:00 | 40.05 | 25.93 |
September | 0.668763E+10 | 12754.17 | 04-SEP-17:11 | 39.33 | 23.70 | 0.256920E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.581537E+10 | 11536.19 | 09-OCT-15:22 | 36.90 | 19.74 | 0.267046E+09 | 347.85 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.431057E+10 | 11604.87 | 05-NOV-15:22 | 31.70 | 21.27 | 0.263926E+09 | 347.86 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.278629E+10 | 4328.24 | 11-DEC-07:03 | 21.50 | 18.56 | 0.255942E+09 | 347.86 | 08-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.589851E+11 | 0.319258E+10 | ||||||||
Minimum of Months | 0.223243E+10 | 3476.18 | 21.50 | 16.92 | 0.239829E+09 | 347.85 | 21.50 | 16.92 | ||
Maximum of Months | 0.805590E+10 | 12754.17 | 40.05 | 27.54 | 0.289149E+09 | 347.89 | 40.05 | 27.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250564E+10 | 3785.80 | 23-JAN-14:10 | 27.50 | 16.66 | 0.409816E+09 | 549.50 | 17-JAN-10:20 | 27.50 | 16.66 |
February | 0.279937E+10 | 5298.98 | 06-FEB-15:00 | 32.50 | 17.28 | 0.375668E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.422017E+10 | 6970.53 | 02-MAR-06:03 | 28.80 | 15.43 | 0.452284E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.520500E+10 | 10808.69 | 30-APR-16:42 | 31.08 | 25.68 | 0.403796E+09 | 549.55 | 28-APR-13:09 | 31.08 | 25.68 |
May | 0.790180E+10 | 13286.41 | 21-MAY-13:02 | 38.00 | 22.80 | 0.438933E+09 | 549.53 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.866420E+10 | 13020.16 | 18-JUN-10:42 | 36.10 | 24.51 | 0.437629E+09 | 550.48 | 12-JUN-13:20 | 36.10 | 24.51 |
July | 0.935540E+10 | 13259.58 | 23-JUL-11:22 | 38.50 | 24.78 | 0.407299E+09 | 550.50 | 31-JUL-13:20 | 40.60 | 26.80 |
August | 0.972552E+10 | 12629.67 | 06-AUG-15:02 | 40.85 | 24.99 | 0.456545E+09 | 550.46 | 04-AUG-13:20 | 40.85 | 24.99 |
September | 0.761885E+10 | 13764.87 | 04-SEP-17:11 | 39.33 | 23.70 | 0.405461E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.635075E+10 | 12185.40 | 29-OCT-14:12 | 33.33 | 19.69 | 0.421143E+09 | 549.50 | 20-OCT-09:20 | 33.33 | 19.69 |
November | 0.450284E+10 | 7501.58 | 20-NOV-05:02 | 26.00 | 18.81 | 0.415491E+09 | 549.51 | 28-NOV-10:20 | 25.73 | 19.64 |
December | 0.295553E+10 | 4330.01 | 11-DEC-14:10 | 26.77 | 18.23 | 0.399987E+09 | 549.50 | 01-DEC-14:20 | 26.77 | 18.23 |
Annual Sum or Average | 0.718051E+11 | 0.502405E+10 | ||||||||
Minimum of Months | 0.250564E+10 | 3785.80 | 26.00 | 15.43 | 0.375668E+09 | 549.50 | 25.67 | 16.66 | ||
Maximum of Months | 0.972552E+10 | 13764.87 | 40.85 | 25.68 | 0.456545E+09 | 550.50 | 40.85 | 26.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187355E+10 | 4259.82 | 24-JAN-11:05 | 24.00 | 18.08 | 0.194439E+09 | 356.46 | 24-JAN-11:09 | 24.00 | 18.08 |
February | 0.212128E+10 | 5388.00 | 07-FEB-13:03 | 31.00 | 20.70 | 0.177457E+09 | 356.46 | 16-FEB-15:09 | 24.78 | 18.41 |
March | 0.320913E+10 | 9522.73 | 27-MAR-12:01 | 37.08 | 19.46 | 0.212468E+09 | 356.48 | 28-MAR-10:09 | 27.17 | 20.40 |
April | 0.413850E+10 | 10336.58 | 30-APR-10:02 | 29.83 | 22.89 | 0.190143E+09 | 356.48 | 28-APR-14:09 | 29.83 | 22.89 |
May | 0.610766E+10 | 11419.32 | 07-MAY-09:52 | 36.50 | 17.98 | 0.206547E+09 | 356.49 | 11-MAY-12:09 | 35.87 | 23.99 |
June | 0.642757E+10 | 11773.72 | 18-JUN-10:02 | 36.50 | 24.82 | 0.205637E+09 | 356.47 | 02-JUN-12:09 | 36.50 | 24.82 |
July | 0.689116E+10 | 11838.71 | 23-JUL-11:22 | 38.50 | 24.78 | 0.192087E+09 | 356.45 | 03-JUL-10:09 | 38.50 | 24.78 |
August | 0.732373E+10 | 11302.24 | 06-AUG-10:22 | 38.85 | 24.36 | 0.214505E+09 | 356.45 | 04-AUG-14:09 | 38.85 | 24.36 |
September | 0.584630E+10 | 11991.12 | 04-SEP-09:12 | 36.53 | 22.23 | 0.190959E+09 | 356.46 | 26-SEP-10:09 | 37.25 | 21.73 |
October | 0.492520E+10 | 11160.37 | 01-OCT-10:32 | 32.73 | 26.12 | 0.198510E+09 | 356.46 | 20-OCT-10:09 | 30.83 | 18.35 |
November | 0.342675E+10 | 7424.55 | 01-NOV-12:02 | 32.48 | 26.16 | 0.195836E+09 | 356.46 | 28-NOV-11:09 | 26.22 | 20.64 |
December | 0.215319E+10 | 4701.91 | 04-DEC-11:05 | 26.25 | 20.62 | 0.188970E+09 | 356.46 | 20-DEC-13:09 | 24.30 | 21.04 |
Annual Sum or Average | 0.544440E+11 | 0.236756E+10 | ||||||||
Minimum of Months | 0.187355E+10 | 4259.82 | 24.00 | 17.98 | 0.177457E+09 | 356.45 | 24.00 | 18.08 | ||
Maximum of Months | 0.732373E+10 | 11991.12 | 38.85 | 26.16 | 0.214505E+09 | 356.49 | 38.85 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455560E+10 | 7466.27 | 23-JAN-13:30 | 27.70 | 16.54 | 0.415850E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.463784E+10 | 12442.36 | 05-FEB-12:23 | 31.05 | 19.28 | 0.378401E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.579597E+10 | 12966.27 | 26-MAR-14:02 | 32.93 | 18.40 | 0.453286E+09 | 550.39 | 27-MAR-13:20 | 35.67 | 19.65 |
April | 0.595875E+10 | 14303.86 | 30-APR-12:02 | 37.02 | 20.74 | 0.404059E+09 | 549.55 | 28-APR-13:09 | 37.02 | 20.74 |
May | 0.793623E+10 | 14945.72 | 21-MAY-13:02 | 38.00 | 22.80 | 0.438897E+09 | 549.54 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.831181E+10 | 14451.33 | 18-JUN-10:42 | 36.10 | 24.51 | 0.437559E+09 | 549.52 | 02-JUN-13:09 | 36.10 | 24.51 |
July | 0.924586E+10 | 14831.32 | 23-JUL-11:22 | 38.50 | 24.78 | 0.407256E+09 | 549.55 | 03-JUL-09:09 | 38.50 | 24.78 |
August | 0.102838E+11 | 14256.01 | 06-AUG-15:02 | 40.85 | 24.99 | 0.456583E+09 | 550.55 | 29-AUG-13:20 | 37.40 | 29.98 |
September | 0.916021E+10 | 15638.86 | 04-SEP-17:11 | 39.33 | 23.70 | 0.405686E+09 | 550.53 | 07-SEP-13:20 | 37.43 | 29.94 |
October | 0.894716E+10 | 15871.90 | 29-OCT-13:32 | 34.37 | 18.20 | 0.421693E+09 | 550.43 | 23-OCT-13:20 | 34.37 | 18.20 |
November | 0.726882E+10 | 15355.05 | 12-NOV-12:53 | 29.30 | 19.32 | 0.416639E+09 | 550.36 | 13-NOV-14:20 | 33.00 | 16.90 |
December | 0.524171E+10 | 15380.76 | 03-DEC-13:02 | 29.33 | 18.32 | 0.403499E+09 | 549.51 | 26-DEC-14:20 | 25.67 | 19.16 |
Annual Sum or Average | 0.873437E+11 | 0.503941E+10 | ||||||||
Minimum of Months | 0.455560E+10 | 7466.27 | 27.70 | 16.54 | 0.378401E+09 | 549.51 | 24.00 | 16.90 | ||
Maximum of Months | 0.102838E+11 | 15871.90 | 40.85 | 24.99 | 0.456583E+09 | 550.55 | 38.50 | 29.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201039E+10 | 3517.07 | 31-JAN-16:20 | 22.73 | 16.79 | 0.260181E+09 | 347.86 | 17-JAN-10:20 | 22.73 | 16.79 |
February | 0.230593E+10 | 6527.31 | 05-FEB-16:23 | 31.50 | 18.69 | 0.238302E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.348615E+10 | 8749.46 | 26-MAR-16:02 | 31.70 | 18.58 | 0.286703E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.415447E+10 | 12330.49 | 30-APR-16:42 | 31.08 | 25.68 | 0.255863E+09 | 347.88 | 28-APR-13:09 | 31.08 | 25.68 |
May | 0.607803E+10 | 12337.87 | 21-MAY-16:22 | 37.25 | 23.23 | 0.277988E+09 | 347.88 | 04-MAY-13:00 | 37.25 | 23.23 |
June | 0.653384E+10 | 11970.92 | 11-JUN-16:42 | 36.90 | 26.08 | 0.277136E+09 | 347.87 | 02-JUN-13:09 | 36.90 | 26.08 |
July | 0.697835E+10 | 12313.96 | 02-JUL-16:12 | 37.93 | 23.27 | 0.257940E+09 | 347.88 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.739886E+10 | 12088.34 | 06-AUG-15:02 | 40.85 | 24.99 | 0.289124E+09 | 347.85 | 07-AUG-09:20 | 37.57 | 24.28 |
September | 0.593859E+10 | 13423.45 | 04-SEP-17:11 | 39.33 | 23.70 | 0.256836E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.500275E+10 | 12269.80 | 29-OCT-15:32 | 32.00 | 19.85 | 0.266801E+09 | 347.85 | 20-OCT-09:20 | 32.00 | 19.85 |
November | 0.359219E+10 | 11274.39 | 05-NOV-15:43 | 31.50 | 21.61 | 0.263318E+09 | 347.86 | 28-NOV-10:20 | 25.73 | 19.64 |
December | 0.236182E+10 | 4132.39 | 04-DEC-15:20 | 26.73 | 21.25 | 0.253752E+09 | 347.86 | 11-DEC-10:20 | 24.07 | 19.01 |
Annual Sum or Average | 0.558414E+11 | 0.318394E+10 | ||||||||
Minimum of Months | 0.201039E+10 | 3517.07 | 22.73 | 16.79 | 0.238302E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.739886E+10 | 13423.45 | 40.85 | 26.08 | 0.289124E+09 | 347.88 | 37.57 | 26.08 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394866E+09 | 2666.14 | 03-JAN-06:03 | 12.93 |
February | 0.243788E+09 | 2535.58 | 13-FEB-06:03 | 13.03 |
March | 0.201597E+09 | 4453.21 | 28-MAR-05:03 | 25.67 |
April | 82437187.45 | 4342.73 | 25-APR-05:03 | 23.83 |
May | 22061498.68 | 3952.35 | 04-MAY-05:03 | 24.00 |
June | 14245545.01 | 3371.39 | 13-JUN-04:02 | 28.50 |
July | 5543819.16 | 2481.15 | 06-JUL-04:02 | 29.17 |
August | 3750870.16 | 3001.22 | 31-AUG-04:02 | 28.83 |
September | 15265185.28 | 4912.30 | 25-SEP-04:02 | 24.17 |
October | 28720217.35 | 4866.55 | 16-OCT-04:02 | 25.83 |
November | 75541000.70 | 3823.88 | 20-NOV-05:02 | 26.00 |
December | 0.261071E+09 | 2531.63 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.134889E+10 | |||
Minimum of Months | 3750870.16 | 2481.15 | 12.93 | |
Maximum of Months | 0.394866E+09 | 4912.30 | 29.17 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28593024.79 | 2105.72 | 08-JAN-12:00 | 23.00 |
February | 14298114.99 | 2422.37 | 05-FEB-11:43 | 30.67 |
March | 11558507.94 | 2321.14 | 26-MAR-14:42 | 32.67 |
April | 16079785.61 | 2007.95 | 23-APR-14:13 | 32.00 |
May | 17097087.05 | 2949.00 | 12-MAY-04:02 | 28.67 |
June | 18308217.88 | 2686.99 | 28-JUN-04:02 | 29.00 |
July | 26106026.08 | 3219.03 | 28-JUL-04:02 | 30.67 |
August | 23904127.67 | 3143.82 | 25-AUG-04:02 | 31.17 |
September | 18867190.16 | 3110.93 | 08-SEP-04:02 | 30.62 |
October | 20657829.77 | 2542.01 | 29-OCT-13:32 | 34.37 |
November | 20203182.06 | 1980.54 | 20-NOV-05:02 | 26.00 |
December | 20671774.60 | 2173.42 | 03-DEC-12:23 | 28.90 |
Annual Sum or Average | 0.236345E+09 | |||
Minimum of Months | 11558507.94 | 1980.54 | 23.00 | |
Maximum of Months | 28593024.79 | 3219.03 | 34.37 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24873743.77 | 1739.55 | 01-JAN-13:25 | 22.65 |
February | 14839289.21 | 1729.93 | 05-FEB-14:43 | 31.93 |
March | 10452242.57 | 1778.36 | 12-MAR-11:47 | 27.80 |
April | 9774975.73 | 1674.67 | 02-APR-14:43 | 33.17 |
May | 15070237.02 | 2984.07 | 23-MAY-04:02 | 31.17 |
June | 16300528.15 | 2930.27 | 29-JUN-04:02 | 32.67 |
July | 32387822.29 | 3266.63 | 27-JUL-04:02 | 30.33 |
August | 34658403.43 | 3268.65 | 31-AUG-04:02 | 28.83 |
September | 28861097.62 | 3585.66 | 28-SEP-04:02 | 27.75 |
October | 28836848.66 | 3607.89 | 05-OCT-04:02 | 27.83 |
November | 27239965.43 | 3129.69 | 20-NOV-05:02 | 26.00 |
December | 25117104.23 | 1982.98 | 25-DEC-12:43 | 27.08 |
Annual Sum or Average | 0.268412E+09 | |||
Minimum of Months | 9774975.73 | 1674.67 | 22.65 | |
Maximum of Months | 34658403.43 | 3607.89 | 33.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128540E+09 | 3492.30 | 13-JAN-08:00 | 14.00 |
February | 88200129.28 | 3487.72 | 17-FEB-07:25 | 14.50 |
March | 30742842.87 | 3474.83 | 16-MAR-06:07 | 15.00 |
April | 81103.35 | 675.86 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 27261671.45 | 3477.68 | 18-DEC-07:20 | 14.00 |
Annual Sum or Average | 0.274826E+09 | |||
Minimum of Months | 0.00 | 0.00 | 14.00 | |
Maximum of Months | 0.128540E+09 | 3492.30 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.426387E+09 | 560.27 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.373920E+09 | 574.69 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.432429E+09 | 665.53 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.377330E+09 | 555.28 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.395590E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.389321E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.371602E+09 | 412.23 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.414972E+09 | 389.65 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.379932E+09 | 399.26 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.405333E+09 | 505.02 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.416032E+09 | 621.45 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.419022E+09 | 636.81 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.480187E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.371602E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.432429E+09 | 665.53 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.266562E+09 | 371.55 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.235511E+09 | 371.37 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272688E+09 | 415.48 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.238941E+09 | 321.69 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252133E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248532E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.236446E+09 | 252.02 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.263410E+09 | 222.09 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240428E+09 | 222.09 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.254782E+09 | 243.84 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.262241E+09 | 403.67 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.261734E+09 | 408.13 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303341E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.235511E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.272688E+09 | 415.48 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411589E+09 | 498.63 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.366585E+09 | 546.07 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.429702E+09 | 664.12 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.378152E+09 | 558.87 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.399637E+09 | 379.03 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.393763E+09 | 385.66 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.374829E+09 | 496.14 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.416882E+09 | 387.12 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.379346E+09 | 397.43 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.399925E+09 | 394.40 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.403241E+09 | 544.15 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.401720E+09 | 598.08 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.475537E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.366585E+09 | 379.03 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.429702E+09 | 664.12 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.264688E+09 | 352.15 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.234032E+09 | 335.25 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274361E+09 | 423.67 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.240255E+09 | 367.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252907E+09 | 252.90 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248802E+09 | 253.92 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.237490E+09 | 333.55 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.264491E+09 | 304.64 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241248E+09 | 315.71 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256415E+09 | 344.14 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.257754E+09 | 345.27 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.258045E+09 | 390.26 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303049E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.234032E+09 | 252.90 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.274361E+09 | 423.67 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.425020E+09 | 553.08 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.372963E+09 | 568.51 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.431581E+09 | 662.84 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.376892E+09 | 548.25 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.395295E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.389037E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.371218E+09 | 410.23 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.414633E+09 | 386.66 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.379488E+09 | 396.71 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.404407E+09 | 495.03 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.414802E+09 | 616.89 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.417267E+09 | 632.96 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.479260E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.371218E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.431581E+09 | 662.84 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.266039E+09 | 368.46 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.235077E+09 | 368.47 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272280E+09 | 413.83 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.238684E+09 | 316.54 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.251863E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248304E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.236141E+09 | 250.40 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.263135E+09 | 222.09 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240195E+09 | 222.09 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.254387E+09 | 242.33 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.261731E+09 | 401.71 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.261138E+09 | 406.34 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.302897E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.235077E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.272280E+09 | 413.83 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411186E+09 | 488.94 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.366101E+09 | 538.58 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.428902E+09 | 661.37 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.377647E+09 | 552.01 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.399106E+09 | 375.63 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.393330E+09 | 382.58 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.374318E+09 | 486.86 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.416381E+09 | 383.99 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.378907E+09 | 394.77 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.399538E+09 | 391.43 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.402915E+09 | 535.99 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.401189E+09 | 592.43 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.474952E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.366101E+09 | 375.63 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.428902E+09 | 661.37 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.263961E+09 | 348.63 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.233574E+09 | 331.25 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.273852E+09 | 422.39 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.239844E+09 | 364.13 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252580E+09 | 251.61 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248385E+09 | 252.65 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.237143E+09 | 329.52 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.264181E+09 | 299.84 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240849E+09 | 311.24 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.255915E+09 | 339.85 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.257269E+09 | 340.93 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.257497E+09 | 387.94 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.302505E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.233574E+09 | 251.61 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.273852E+09 | 422.39 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.426385E+09 | 560.26 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.373919E+09 | 574.68 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.432428E+09 | 665.52 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.377329E+09 | 555.27 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.395589E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.389321E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.371601E+09 | 412.23 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.414972E+09 | 389.64 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.379932E+09 | 399.26 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.405332E+09 | 505.00 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.416031E+09 | 621.45 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.419021E+09 | 636.80 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.480186E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.371601E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.432428E+09 | 665.52 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.266562E+09 | 371.55 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.235510E+09 | 371.36 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272688E+09 | 415.48 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.238940E+09 | 321.68 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252132E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248532E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.236445E+09 | 252.02 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.263409E+09 | 222.09 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240428E+09 | 222.09 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.254782E+09 | 243.84 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.262241E+09 | 403.67 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.261733E+09 | 408.13 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303340E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.235510E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.272688E+09 | 415.48 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411589E+09 | 498.61 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.366585E+09 | 546.06 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.429701E+09 | 664.11 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.378151E+09 | 558.85 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.399625E+09 | 379.03 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.393762E+09 | 385.65 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.374829E+09 | 496.11 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.416881E+09 | 387.12 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.379345E+09 | 397.42 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.399925E+09 | 394.40 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.403241E+09 | 544.14 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.401720E+09 | 598.07 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.475535E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.366585E+09 | 379.03 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.429701E+09 | 664.11 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.264687E+09 | 352.14 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.234031E+09 | 335.24 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274361E+09 | 423.67 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.240247E+09 | 367.13 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252907E+09 | 252.89 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248802E+09 | 253.92 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.237489E+09 | 333.54 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.264490E+09 | 304.63 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241248E+09 | 315.70 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256415E+09 | 344.14 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.257754E+09 | 345.26 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.258045E+09 | 390.26 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303048E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.234031E+09 | 252.89 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.274361E+09 | 423.67 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.426387E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2295416.19 | 0.153435E+09 |
February | 0.901968E+09 | 0.373920E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17034722.67 | 0.156437E+09 |
March | 0.107774E+10 | 0.432429E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42975731.43 | 86373123.90 |
April | 0.956342E+09 | 0.377330E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102355E+09 | 39649731.99 |
May | 0.103597E+10 | 0.395590E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253401E+09 | 4652678.16 |
June | 0.103308E+10 | 0.389321E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316160E+09 | 434951.11 |
July | 0.959235E+09 | 0.371602E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452588E+09 | 0.00 |
August | 0.107774E+10 | 0.414972E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433702E+09 | 0.00 |
September | 0.956342E+09 | 0.379932E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303481E+09 | 697406.31 |
October | 0.994195E+09 | 0.405333E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173134E+09 | 6546517.83 |
November | 0.984487E+09 | 0.416032E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71742391.87 | 40932613.36 |
December | 0.959235E+09 | 0.419022E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11527355.56 | 0.112897E+09 |
Annual Sum or Average | 0.119305E+11 | 0.480187E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218040E+10 | 0.602056E+09 |
Minimum of Months | 0.901968E+09 | 0.371602E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2295416.19 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.432429E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452588E+09 | 0.156437E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.266562E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 849772.02 | 0.108438E+09 |
February | 0.571020E+09 | 0.235511E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9994565.95 | 0.108822E+09 |
March | 0.682301E+09 | 0.272688E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27915430.57 | 60125197.72 |
April | 0.605444E+09 | 0.238941E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66280667.87 | 27332956.13 |
May | 0.655854E+09 | 0.252133E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167483E+09 | 3252043.99 |
June | 0.654023E+09 | 0.248532E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209816E+09 | 328271.61 |
July | 0.607275E+09 | 0.236446E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300205E+09 | 0.00 |
August | 0.682301E+09 | 0.263410E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287620E+09 | 0.00 |
September | 0.605444E+09 | 0.240428E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200266E+09 | 495614.54 |
October | 0.629407E+09 | 0.254782E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113285E+09 | 4797462.68 |
November | 0.623262E+09 | 0.262241E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44673614.42 | 29180103.82 |
December | 0.607275E+09 | 0.261734E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6612914.34 | 78502007.91 |
Annual Sum or Average | 0.755301E+10 | 0.303341E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143500E+10 | 0.421274E+09 |
Minimum of Months | 0.571020E+09 | 0.235511E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 849772.02 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.272688E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300205E+09 | 0.108822E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.411589E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 920046.89 | 0.177997E+09 |
February | 0.901968E+09 | 0.366585E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14584802.72 | 0.172390E+09 |
March | 0.107774E+10 | 0.429702E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41424909.14 | 93643732.06 |
April | 0.956342E+09 | 0.378152E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100257E+09 | 40677432.46 |
May | 0.103597E+10 | 0.399637E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253698E+09 | 4673091.07 |
June | 0.103308E+10 | 0.393763E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316987E+09 | 422743.34 |
July | 0.959235E+09 | 0.374829E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453218E+09 | 0.00 |
August | 0.107774E+10 | 0.416882E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433217E+09 | 0.00 |
September | 0.956342E+09 | 0.379346E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300522E+09 | 748970.95 |
October | 0.994195E+09 | 0.399925E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167380E+09 | 7721916.72 |
November | 0.984487E+09 | 0.403241E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63408690.61 | 46434903.01 |
December | 0.959235E+09 | 0.401720E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8475587.23 | 0.130251E+09 |
Annual Sum or Average | 0.119305E+11 | 0.475537E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215409E+10 | 0.674961E+09 |
Minimum of Months | 0.901968E+09 | 0.366585E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 920046.89 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.429702E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453218E+09 | 0.177997E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.264688E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128968.13 | 0.108959E+09 |
February | 0.570983E+09 | 0.234032E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10710412.17 | 0.109830E+09 |
March | 0.682256E+09 | 0.274361E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27815561.15 | 62243828.79 |
April | 0.605404E+09 | 0.240255E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65784198.14 | 28325452.15 |
May | 0.655811E+09 | 0.252907E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166733E+09 | 3357722.31 |
June | 0.653980E+09 | 0.248802E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208267E+09 | 336933.29 |
July | 0.607235E+09 | 0.237490E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299393E+09 | 0.00 |
August | 0.682256E+09 | 0.264491E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286718E+09 | 0.00 |
September | 0.605404E+09 | 0.241248E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199027E+09 | 506030.02 |
October | 0.629366E+09 | 0.256415E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112263E+09 | 4860926.26 |
November | 0.623221E+09 | 0.257754E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44564400.38 | 28930896.15 |
December | 0.607235E+09 | 0.258045E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6576658.80 | 80137997.34 |
Annual Sum or Average | 0.755252E+10 | 0.303049E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142898E+10 | 0.427489E+09 |
Minimum of Months | 0.570983E+09 | 0.234032E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128968.13 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.274361E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299393E+09 | 0.109830E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.425020E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1192952.68 | 95961134.38 |
February | 0.901968E+09 | 0.372963E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9729762.81 | 92559026.70 |
March | 0.107774E+10 | 0.431581E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24005316.17 | 48475162.54 |
April | 0.956342E+09 | 0.376892E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58242281.29 | 20950079.67 |
May | 0.103597E+10 | 0.395295E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138734E+09 | 2219056.36 |
June | 0.103308E+10 | 0.389037E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171585E+09 | 186614.43 |
July | 0.959235E+09 | 0.371218E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243926E+09 | 0.00 |
August | 0.107774E+10 | 0.414633E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233739E+09 | 0.00 |
September | 0.956342E+09 | 0.379488E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163780E+09 | 354302.05 |
October | 0.994195E+09 | 0.404407E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93037938.27 | 4162438.82 |
November | 0.984487E+09 | 0.414802E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38728765.89 | 27286037.85 |
December | 0.959235E+09 | 0.417267E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6076789.71 | 72841862.53 |
Annual Sum or Average | 0.119305E+11 | 0.479260E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118278E+10 | 0.364996E+09 |
Minimum of Months | 0.901968E+09 | 0.371218E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1192952.68 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.431581E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243926E+09 | 95961134.38 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.266039E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 440498.52 | 67825624.51 |
February | 0.571020E+09 | 0.235077E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5637021.72 | 64953740.64 |
March | 0.682301E+09 | 0.272280E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15305111.35 | 34191073.36 |
April | 0.605444E+09 | 0.238684E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36436685.03 | 14999329.70 |
May | 0.655854E+09 | 0.251863E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90679020.35 | 1713608.93 |
June | 0.654023E+09 | 0.248304E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113030E+09 | 161972.76 |
July | 0.607275E+09 | 0.236141E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160985E+09 | 0.00 |
August | 0.682301E+09 | 0.263135E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154287E+09 | 0.00 |
September | 0.605444E+09 | 0.240195E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107275E+09 | 278483.83 |
October | 0.629407E+09 | 0.254387E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60214765.31 | 3261840.32 |
November | 0.623262E+09 | 0.261731E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23888392.92 | 19841067.55 |
December | 0.607275E+09 | 0.261138E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3566968.98 | 50642061.59 |
Annual Sum or Average | 0.755301E+10 | 0.302897E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771746E+09 | 0.257869E+09 |
Minimum of Months | 0.571020E+09 | 0.235077E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 440498.52 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.272280E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160985E+09 | 67825624.51 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.411186E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21691439.61 | 0.150056E+10 |
February | 0.901968E+09 | 0.366101E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256972E+09 | 0.934805E+09 |
March | 0.107774E+10 | 0.428902E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888595E+09 | 0.594754E+09 |
April | 0.956342E+09 | 0.377647E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165081E+10 | 0.214513E+09 |
May | 0.103597E+10 | 0.399106E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341413E+10 | 36958769.71 |
June | 0.103308E+10 | 0.393330E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401854E+10 | 1360881.32 |
July | 0.959235E+09 | 0.374318E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426292E+10 | 0.00 |
August | 0.107774E+10 | 0.416381E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490047E+10 | 0.00 |
September | 0.956342E+09 | 0.378907E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341165E+10 | 3051488.46 |
October | 0.994195E+09 | 0.399538E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246484E+10 | 27549186.69 |
November | 0.984487E+09 | 0.402915E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132130E+10 | 0.315228E+09 |
December | 0.959235E+09 | 0.401189E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203894E+09 | 0.881857E+09 |
Annual Sum or Average | 0.119305E+11 | 0.474952E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268158E+11 | 0.451064E+10 |
Minimum of Months | 0.901968E+09 | 0.366101E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21691439.61 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.428902E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490047E+10 | 0.150056E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.263961E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 550782.79 | 68340681.75 |
February | 0.570983E+09 | 0.233574E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5850602.18 | 65778065.64 |
March | 0.682256E+09 | 0.273852E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15087001.23 | 35789132.61 |
April | 0.605404E+09 | 0.239844E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36013547.89 | 15567188.30 |
May | 0.655811E+09 | 0.252580E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90039798.52 | 1801340.91 |
June | 0.653980E+09 | 0.248385E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111918E+09 | 174520.75 |
July | 0.607235E+09 | 0.237143E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160304E+09 | 0.00 |
August | 0.682256E+09 | 0.264181E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153611E+09 | 0.00 |
September | 0.605404E+09 | 0.240849E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106422E+09 | 292325.87 |
October | 0.629366E+09 | 0.255915E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59549192.82 | 3373234.40 |
November | 0.623221E+09 | 0.257269E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23642881.64 | 19945959.81 |
December | 0.607235E+09 | 0.257497E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3505841.87 | 51601083.24 |
Annual Sum or Average | 0.755252E+10 | 0.302505E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766496E+09 | 0.262664E+09 |
Minimum of Months | 0.570983E+09 | 0.233574E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 550782.79 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.273852E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160304E+09 | 68340681.75 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.426385E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1979890.61 | 0.140828E+09 |
February | 0.901968E+09 | 0.373919E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14812770.25 | 0.140339E+09 |
March | 0.107774E+10 | 0.432428E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36363951.65 | 77108881.50 |
April | 0.956342E+09 | 0.377329E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87299712.53 | 34882223.04 |
May | 0.103597E+10 | 0.395589E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213179E+09 | 3982390.87 |
June | 0.103308E+10 | 0.389321E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265306E+09 | 338952.01 |
July | 0.959235E+09 | 0.371601E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378296E+09 | 0.00 |
August | 0.107774E+10 | 0.414972E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362867E+09 | 0.00 |
September | 0.956342E+09 | 0.379932E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254884E+09 | 579204.73 |
October | 0.994195E+09 | 0.405332E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146141E+09 | 5708451.27 |
November | 0.984487E+09 | 0.416031E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61211617.15 | 37820335.43 |
December | 0.959235E+09 | 0.419021E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9783746.92 | 0.103304E+09 |
Annual Sum or Average | 0.119305E+11 | 0.480186E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183213E+10 | 0.544891E+09 |
Minimum of Months | 0.901968E+09 | 0.371601E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1979890.61 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.432428E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378296E+09 | 0.140828E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.266562E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 670499.39 | 99065158.95 |
February | 0.421807E+09 | 0.235510E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8330472.88 | 97537076.42 |
March | 0.502994E+09 | 0.272688E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22840906.53 | 53634052.74 |
April | 0.447140E+09 | 0.238940E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55226185.06 | 24038061.07 |
May | 0.484071E+09 | 0.252132E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139935E+09 | 2790993.81 |
June | 0.482240E+09 | 0.248532E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175041E+09 | 260201.51 |
July | 0.448971E+09 | 0.236445E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249930E+09 | 0.00 |
August | 0.502994E+09 | 0.263409E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239522E+09 | 0.00 |
September | 0.447140E+09 | 0.240428E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167107E+09 | 410915.24 |
October | 0.465148E+09 | 0.254782E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94656862.19 | 4166601.36 |
November | 0.460569E+09 | 0.262241E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37190025.11 | 26758953.61 |
December | 0.448971E+09 | 0.261733E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5368698.83 | 71665486.33 |
Annual Sum or Average | 0.557719E+10 | 0.303340E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119582E+10 | 0.380328E+09 |
Minimum of Months | 0.421807E+09 | 0.235510E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 670499.39 | 0.00 |
Maximum of Months | 0.502994E+09 | 0.272688E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249930E+09 | 99065158.95 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.411589E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 772642.69 | 0.159968E+09 |
February | 0.901968E+09 | 0.366585E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12334214.75 | 0.153058E+09 |
March | 0.107774E+10 | 0.429701E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34687611.46 | 83013894.35 |
April | 0.956342E+09 | 0.378151E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84823242.44 | 35714668.97 |
May | 0.103597E+10 | 0.399625E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213520E+09 | 3999162.86 |
June | 0.103308E+10 | 0.393762E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266251E+09 | 327392.02 |
July | 0.959235E+09 | 0.374829E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379000E+09 | 0.00 |
August | 0.107774E+10 | 0.416881E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362414E+09 | 0.00 |
September | 0.956342E+09 | 0.379345E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251960E+09 | 622311.97 |
October | 0.994195E+09 | 0.399925E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140656E+09 | 6643445.00 |
November | 0.984487E+09 | 0.403241E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53135871.03 | 42379467.43 |
December | 0.959235E+09 | 0.401720E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7129631.25 | 0.116816E+09 |
Annual Sum or Average | 0.119305E+11 | 0.475535E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180668E+10 | 0.602543E+09 |
Minimum of Months | 0.901968E+09 | 0.366585E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 772642.69 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.429701E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379000E+09 | 0.159968E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.264687E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963962.77 | 99032382.47 |
February | 0.570983E+09 | 0.234031E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9083389.72 | 97922669.91 |
March | 0.682256E+09 | 0.274361E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23331492.52 | 55271450.59 |
April | 0.605404E+09 | 0.240247E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55395409.05 | 24791534.82 |
May | 0.655811E+09 | 0.252907E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139926E+09 | 2882155.39 |
June | 0.653980E+09 | 0.248802E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174580E+09 | 262612.84 |
July | 0.607235E+09 | 0.237489E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249938E+09 | 0.00 |
August | 0.682256E+09 | 0.264490E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239597E+09 | 0.00 |
September | 0.605404E+09 | 0.241248E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166642E+09 | 421013.05 |
October | 0.629366E+09 | 0.256415E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94277058.14 | 4209410.22 |
November | 0.623221E+09 | 0.257754E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37534037.77 | 26584008.18 |
December | 0.607235E+09 | 0.258045E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5588318.34 | 72629694.43 |
Annual Sum or Average | 0.755252E+10 | 0.303048E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119686E+10 | 0.384007E+09 |
Minimum of Months | 0.570983E+09 | 0.234031E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963962.77 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.274361E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249938E+09 | 99032382.47 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1371214.82 | 0.209399E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16393738.13 | 0.203618E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40408720.12 | 0.109525E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103785E+09 | 46419149.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263765E+09 | 4482824.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330614E+09 | 397769.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473888E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450497E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314606E+09 | 668619.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174453E+09 | 7718814.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66486267.10 | 53414064.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8995888.62 | 0.153995E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224526E+10 | 0.789638E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1371214.82 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473888E+09 | 0.209399E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2706879.45 | 0.250510E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22117833.36 | 0.250865E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52628565.90 | 0.136744E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132319E+09 | 60042741.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335018E+09 | 6226215.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421420E+09 | 568600.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604936E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577063E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402855E+09 | 958882.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224442E+09 | 9721514.23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88154204.46 | 65607529.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12986659.80 | 0.185451E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287665E+10 | 0.966695E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2706879.45 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604936E+09 | 0.250865E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816926.58 | 0.247180E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17828040.08 | 0.245104E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50487718.65 | 0.134937E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116895E+09 | 50950378.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340281E+09 | 4393799.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442655E+09 | 445545.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632751E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611129E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420644E+09 | 670132.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232410E+09 | 5912992.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82648218.71 | 50764159.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7979012.45 | 0.175453E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295652E+10 | 0.915811E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816926.58 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632751E+09 | 0.247180E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 560.27 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 149.88 | 29-JAN-12:00 | 387.83 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 574.69 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 368.77 | 05-FEB-15:00 | 336.02 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 665.53 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 325.33 | 26-MAR-13:53 | 342.24 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 555.28 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.60 | 30-APR-12:55 | 228.33 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2560.37 | 21-MAY-12:51 | 84.90 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.94 | 11-JUN-13:25 | 59.02 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 412.23 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.74 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 389.65 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.45 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 399.26 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.99 | 03-SEP-15:57 | 63.45 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 505.02 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.09 | 09-OCT-15:24 | 109.90 | 20-OCT-04:40 |
November | 1306.65 | 01-NOV-09:09 | 621.45 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.27 | 19-NOV-13:52 | 184.61 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 636.81 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.59 | 10-DEC-12:00 | 262.08 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 149.88 | 0.00 | |||||
Maximum of Months | 1306.65 | 665.53 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2560.37 | 387.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 371.55 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 29-JAN-12:00 | 259.15 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 371.37 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 249.90 | 05-FEB-14:58 | 225.26 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 415.48 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.19 | 26-MAR-13:53 | 234.69 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 321.69 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.01 | 30-APR-12:55 | 152.67 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.80 | 21-MAY-12:51 | 57.02 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 430.05 | 11-JUN-14:44 | 39.85 | 07-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 252.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.06 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 222.09 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.80 | 13-AUG-13:54 | 0.00 | 01-AUG-00:05 |
September | 827.22 | 01-SEP-09:09 | 222.09 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.46 | 03-SEP-15:53 | 42.83 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 243.84 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.80 | 09-OCT-15:24 | 73.45 | 20-OCT-04:50 |
November | 827.22 | 01-NOV-09:09 | 403.67 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.15 | 05-NOV-14:56 | 122.41 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 408.13 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.77 | 10-DEC-12:00 | 173.12 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 0.00 | |||||
Maximum of Months | 827.22 | 415.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.80 | 259.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 498.63 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.94 | 23-JAN-13:00 | 404.66 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 546.07 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 362.08 | 05-FEB-14:55 | 350.13 | 10-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 664.12 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.21 | 26-MAR-13:53 | 391.41 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 558.87 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 465.58 | 30-APR-12:55 | 231.26 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 379.03 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2554.52 | 21-MAY-12:51 | 85.65 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 385.66 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.61 | 11-JUN-13:25 | 59.20 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 496.14 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1002.01 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 387.12 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.45 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 397.43 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.99 | 03-SEP-15:57 | 64.63 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 394.40 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.84 | 09-OCT-15:00 | 113.46 | 20-OCT-04:40 |
November | 1306.65 | 01-NOV-09:09 | 544.15 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.72 | 05-NOV-14:54 | 187.98 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 598.08 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 139.36 | 10-DEC-12:57 | 262.96 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 379.03 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 46.94 | 0.00 | |||||
Maximum of Months | 1306.65 | 664.12 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2554.52 | 404.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 352.15 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.71 | 29-JAN-12:00 | 261.32 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 335.25 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 248.36 | 05-FEB-14:55 | 228.33 | 10-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 423.67 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.14 | 26-MAR-13:53 | 251.27 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 367.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.79 | 30-APR-12:55 | 156.05 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 252.90 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.29 | 21-MAY-12:51 | 57.79 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 253.92 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.97 | 11-JUN-13:25 | 40.96 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 333.55 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 665.17 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 304.64 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 623.69 | 13-AUG-13:54 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 315.71 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.32 | 03-SEP-16:00 | 43.28 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 344.14 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.14 | 09-OCT-15:24 | 74.88 | 20-OCT-04:40 |
November | 827.17 | 01-NOV-09:09 | 345.27 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.06 | 05-NOV-14:54 | 123.40 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 390.26 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.39 | 10-DEC-12:00 | 173.25 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 252.90 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 94.71 | 0.00 | |||||
Maximum of Months | 827.17 | 423.67 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1698.29 | 261.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 553.08 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.85 | 29-JAN-11:40 | 251.59 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 568.51 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.96 | 05-FEB-15:00 | 205.09 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 662.84 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 194.36 | 26-MAR-13:55 | 178.59 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 548.25 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.64 | 30-APR-12:53 | 128.47 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.13 | 21-MAY-12:51 | 42.91 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.91 | 11-JUN-14:55 | 31.93 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 410.23 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.43 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 386.66 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 506.89 | 13-AUG-13:54 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 396.71 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.33 | 03-SEP-16:00 | 36.59 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 495.03 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.22 | 09-OCT-15:24 | 74.14 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 616.89 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 | 19-NOV-13:52 | 120.34 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 632.96 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.09 | 10-DEC-12:10 | 166.90 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.85 | 0.00 | |||||
Maximum of Months | 1306.65 | 662.84 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.13 | 251.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 368.46 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 | 29-JAN-12:00 | 173.63 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 368.47 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.58 | 05-FEB-15:00 | 140.04 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 413.83 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.14 | 26-MAR-13:53 | 118.89 | 06-MAR-06:00 |
April | 827.22 | 03-APR-09:09 | 316.54 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.86 | 30-APR-13:07 | 87.70 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 | 21-MAY-13:00 | 30.22 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.20 | 11-JUN-14:55 | 22.55 | 07-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 250.40 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.17 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 222.09 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.17 | 13-AUG-13:54 | 0.00 | 01-AUG-00:05 |
September | 827.22 | 01-SEP-09:09 | 222.09 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.88 | 03-SEP-16:00 | 26.02 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 242.33 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.46 | 09-OCT-15:24 | 51.92 | 20-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 401.71 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.49 | 05-NOV-15:26 | 80.81 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 406.34 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 10-DEC-12:50 | 110.95 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 | 0.00 | |||||
Maximum of Months | 827.22 | 413.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 | 173.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 488.94 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.41 | 23-JAN-13:00 | 12372.40 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 538.58 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7389.09 | 07-FEB-13:00 | 10869.38 | 01-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 661.37 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15795.93 | 27-MAR-11:01 | 8959.55 | 16-MAR-06:02 |
April | 1306.65 | 03-APR-09:09 | 552.01 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18444.90 | 28-APR-11:01 | 6756.63 | 05-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 375.63 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18287.75 | 09-MAY-11:01 | 4394.32 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 382.58 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20283.07 | 12-JUN-11:01 | 541.52 | 22-JUN-08:00 |
July | 1306.65 | 03-JUL-09:09 | 486.86 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23313.76 | 21-JUL-11:01 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 383.99 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22616.10 | 16-AUG-11:01 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 394.77 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17858.93 | 12-SEP-11:01 | 1053.41 | 25-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 391.43 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14166.44 | 04-OCT-11:01 | 2697.90 | 30-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 535.99 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9237.96 | 01-NOV-11:02 | 7884.97 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 592.43 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4907.47 | 01-DEC-12:05 | 11591.76 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 375.63 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.41 | 0.00 | |||||
Maximum of Months | 1306.65 | 661.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23313.76 | 12372.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 348.63 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 | 29-JAN-11:40 | 174.07 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 331.25 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.07 | 05-FEB-14:48 | 141.26 | 10-FEB-23:20 |
March | 827.17 | 01-MAR-10:09 | 422.39 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 26-MAR-13:53 | 128.12 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 364.13 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.82 | 30-APR-13:07 | 89.91 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 251.61 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 | 21-MAY-13:00 | 30.75 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 252.65 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.69 | 11-JUN-12:57 | 23.55 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 329.52 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.17 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 299.84 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.89 | 13-AUG-13:54 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 311.24 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.88 | 03-SEP-16:00 | 26.44 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 339.85 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.79 | 09-OCT-15:24 | 53.00 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 340.93 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 05-NOV-14:43 | 81.81 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 387.94 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.80 | 10-DEC-12:10 | 111.05 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 251.61 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 | 0.00 | |||||
Maximum of Months | 827.17 | 422.39 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 946.75 | 174.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 560.26 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 123.69 | 29-JAN-11:47 | 361.81 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 574.68 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.33 | 05-FEB-14:50 | 307.29 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 665.52 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 271.52 | 26-MAR-13:53 | 282.29 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 555.27 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.97 | 30-APR-12:53 | 201.45 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2155.97 | 21-MAY-12:51 | 71.65 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.27 | 11-JUN-13:25 | 49.84 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 412.23 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 829.91 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 389.64 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 776.05 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 399.26 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 594.18 | 03-SEP-15:53 | 53.68 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 505.00 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 509.03 | 09-OCT-15:24 | 99.82 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 621.45 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.13 | 19-NOV-14:00 | 169.94 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 636.80 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.62 | 10-DEC-12:20 | 237.54 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 123.69 | 0.00 | |||||
Maximum of Months | 1306.65 | 665.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2155.97 | 361.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 371.55 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 29-JAN-11:50 | 241.80 | 18-JAN-04:00 |
February | 805.43 | 01-FEB-08:09 | 371.36 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 196.83 | 05-FEB-14:50 | 205.71 | 13-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 415.48 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.41 | 26-MAR-14:06 | 193.52 | 05-MAR-15:00 |
April | 805.43 | 03-APR-07:10 | 321.68 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.32 | 30-APR-12:53 | 134.82 | 05-APR-01:00 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.53 | 21-MAY-12:51 | 48.20 | 01-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.24 | 11-JUN-14:44 | 33.75 | 07-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 252.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.77 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 805.43 | 01-AUG-07:10 | 222.09 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.36 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 805.43 | 01-SEP-07:10 | 222.09 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.29 | 03-SEP-15:53 | 36.20 | 25-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 243.84 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.14 | 09-OCT-15:24 | 66.77 | 20-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 403.67 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.99 | 19-NOV-13:48 | 112.69 | 22-NOV-06:00 |
December | 805.43 | 01-DEC-08:09 | 408.13 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.34 | 10-DEC-13:00 | 157.15 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 0.00 | |||||
Maximum of Months | 805.43 | 415.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.53 | 241.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 498.61 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 23-JAN-13:00 | 375.08 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 546.06 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.58 | 05-FEB-15:07 | 318.10 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 664.11 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.08 | 26-MAR-14:04 | 320.60 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 558.85 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.95 | 30-APR-12:53 | 203.80 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 379.03 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.42 | 21-MAY-12:51 | 72.37 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 385.65 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.15 | 11-JUN-14:44 | 49.96 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 496.11 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 829.91 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 387.12 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 776.05 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 397.42 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 592.44 | 03-SEP-16:00 | 54.78 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 394.40 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.75 | 09-OCT-15:00 | 102.84 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 544.14 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.41 | 19-NOV-14:00 | 172.53 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 598.07 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.26 | 10-DEC-12:40 | 238.14 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 379.03 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 0.00 | |||||
Maximum of Months | 1306.65 | 664.11 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.42 | 375.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 352.14 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 29-JAN-11:43 | 243.17 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 335.24 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.62 | 05-FEB-15:07 | 206.93 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 423.67 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.92 | 26-MAR-14:04 | 207.05 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 367.13 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.31 | 30-APR-12:53 | 137.41 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 252.89 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1430.42 | 21-MAY-12:51 | 48.95 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 253.92 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.55 | 11-JUN-13:25 | 34.57 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 333.54 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.27 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 304.63 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.36 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 315.70 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.96 | 03-SEP-16:00 | 36.62 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 344.14 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.51 | 09-OCT-15:24 | 67.60 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 345.26 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.28 | 19-NOV-13:48 | 113.39 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 390.26 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.80 | 10-DEC-12:17 | 157.04 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 252.89 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 0.00 | |||||
Maximum of Months | 827.17 | 423.67 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1430.42 | 243.17 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.20 | 29-JAN-11:53 | 535.38 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.51 | 05-FEB-15:00 | 448.63 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.56 | 26-MAR-14:00 | 396.30 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.73 | 30-APR-12:53 | 279.36 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2745.79 | 21-MAY-12:51 | 90.42 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.16 | 11-JUN-13:20 | 61.46 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1028.75 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.74 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.30 | 03-SEP-16:00 | 68.27 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.58 | 09-OCT-15:10 | 133.78 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.32 | 19-NOV-13:52 | 246.04 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.51 | 10-DEC-12:13 | 344.23 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.20 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2745.79 | 535.38 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.64 | 29-JAN-11:53 | 645.74 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.38 | 05-FEB-14:53 | 554.05 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.21 | 26-MAR-13:53 | 493.23 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.68 | 30-APR-13:00 | 356.78 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3478.29 | 21-MAY-12:51 | 121.53 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.64 | 11-JUN-13:10 | 80.92 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.48 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 917.99 | 03-SEP-16:00 | 92.34 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.99 | 09-OCT-15:10 | 164.69 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.31 | 19-NOV-14:00 | 305.93 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.07 | 10-DEC-12:23 | 425.08 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.64 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3478.29 | 645.74 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.28 | 29-JAN-12:00 | 567.73 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.20 | 05-FEB-15:20 | 528.69 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.94 | 02-MAR-04:00 | 618.22 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.09 | 30-APR-13:00 | 319.66 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3122.64 | 21-MAY-12:51 | 118.00 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.59 | 09-JUN-03:00 | 67.84 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.16 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1143.56 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.87 | 04-SEP-17:00 | 81.29 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.91 | 09-OCT-15:10 | 137.87 | 20-OCT-04:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.08 | 19-NOV-13:52 | 255.75 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.28 | 10-DEC-11:55 | 389.68 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.28 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3122.64 | 618.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32471.52 | 17-JAN-07:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33008.29 | 21-FEB-07:02 | 6352.64 | 5814.50 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34730.73 | 28-MAR-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35536.12 | 24-APR-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35891.09 | 04-MAY-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35784.81 | 06-JUN-04:03 | 0.00 | 1550.53 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31518.13 | 03-JUL-06:03 | 3811.58 | 3488.70 | 18132.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30922.43 | 07-AUG-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35142.56 | 26-SEP-04:03 | 0.00 | 1550.53 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35406.83 | 17-OCT-04:03 | 0.00 | 1550.53 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35724.67 | 27-NOV-06:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33634.64 | 26-DEC-07:01 | 8893.70 | 8140.30 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 30922.43 | 0.00 | 846.94 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35891.09 | 8893.70 | 8140.30 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4967.12 | 31-JAN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 |
February | 7860.33 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.65 | 0.00 |
March | 10775.74 | 27-MAR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.48 | 0.00 |
April | 11861.91 | 28-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.45 | 0.00 |
May | 12264.04 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.47 | 0.00 |
June | 13052.09 | 12-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.96 | 0.00 |
July | 14002.02 | 21-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.86 | 0.00 |
August | 14046.57 | 16-AUG-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.63 | 0.00 |
September | 13120.74 | 05-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.15 | 0.00 |
October | 11015.88 | 02-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.24 | 0.00 |
November | 9093.67 | 06-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.57 | 0.00 |
December | 6563.47 | 04-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4967.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14046.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.45 | 31.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2001.35 | 31-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 |
February | 3902.46 | 06-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.94 | 0.00 |
March | 5301.24 | 27-MAR-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.50 | 0.00 |
April | 5435.59 | 24-APR-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.93 | 0.00 |
May | 7128.25 | 22-MAY-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.38 | 0.00 |
June | 7685.36 | 12-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 0.00 |
July | 7616.97 | 31-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.61 | 0.00 |
August | 7486.68 | 21-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.47 | 0.00 |
September | 7717.33 | 05-SEP-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.72 | 0.00 |
October | 6209.27 | 10-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.04 | 0.00 |
November | 5191.44 | 06-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.02 | 0.00 |
December | 3240.37 | 04-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2001.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7717.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.50 | 31.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2627.85 | 30-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
February | 4184.69 | 06-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.57 | 0.00 |
March | 6550.79 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.20 | 0.00 |
April | 6237.83 | 24-APR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 | 0.00 |
May | 8047.49 | 30-MAY-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 0.00 |
June | 7826.32 | 05-JUN-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.89 | 0.00 |
July | 8549.42 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.40 | 0.00 |
August | 8206.94 | 28-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.59 | 0.00 |
September | 7960.99 | 25-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 | 0.00 |
October | 6432.60 | 04-OCT-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 0.00 |
November | 5357.71 | 13-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | 0.00 |
December | 4254.92 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2627.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8549.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.20 | 14.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15951.63 | 30-JAN-07:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24275.68 | 06-FEB-07:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29768.63 | 28-MAR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30770.34 | 24-APR-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33777.74 | 15-MAY-05:14 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31268.00 | 06-JUN-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28753.92 | 03-JUL-06:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28185.58 | 15-AUG-06:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31232.64 | 26-SEP-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31564.75 | 17-OCT-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31865.11 | 13-NOV-06:12 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28097.83 | 04-DEC-07:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15951.63 | 0.00 | 846.94 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33777.74 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13573.62 | 30-JAN-14:50 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17066.02 | 06-FEB-07:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34234.90 | 28-MAR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34816.31 | 24-APR-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35195.39 | 01-MAY-05:12 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35695.40 | 06-JUN-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32775.51 | 10-JUL-06:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32820.85 | 07-AUG-06:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35928.79 | 25-SEP-04:02 | 0.00 | 1938.17 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35977.81 | 23-OCT-04:02 | 0.00 | 1938.17 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35766.69 | 20-NOV-05:02 | 0.00 | 1938.17 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15280.25 | 04-DEC-14:50 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13573.62 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35977.81 | 6198.29 | 3488.70 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3935.59 | 23-JAN-14:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 0.00 |
February | 5731.33 | 06-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 | 0.00 |
March | 7222.98 | 02-MAR-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 59.21 | 0.00 |
April | 12048.49 | 23-APR-14:13 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 242.22 | 0.00 |
May | 15835.44 | 21-MAY-13:02 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2198.18 | 0.00 |
June | 14811.42 | 18-JUN-14:32 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 425.24 | 0.00 |
July | 15776.67 | 30-JUL-14:01 | 468.72 | 136.41 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 929.26 | 0.00 |
August | 15119.31 | 06-AUG-15:02 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 579.92 | 0.00 |
September | 15491.93 | 04-SEP-16:42 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 665.07 | 0.00 |
October | 14304.00 | 09-OCT-14:42 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 577.58 | 0.00 |
November | 7930.82 | 12-NOV-14:02 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 151.61 | 0.00 |
December | 4452.42 | 11-DEC-14:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3935.59 | 267.84 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 | |
Maximum of Months | 15835.44 | 2613.31 | 701.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 2198.18 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2940.89 | 24-JAN-11:00 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
February | 6498.52 | 05-FEB-14:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 222.30 | 0.00 |
March | 7220.31 | 26-MAR-11:33 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 46.70 | 0.00 |
April | 11835.22 | 30-APR-12:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 181.93 | 0.00 |
May | 12514.41 | 21-MAY-13:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.00 | 0.00 |
June | 12746.21 | 18-JUN-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 193.55 | 0.00 |
July | 13472.62 | 30-JUL-09:21 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.31 | 0.00 |
August | 12373.70 | 13-AUG-10:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 496.10 | 0.00 |
September | 12344.43 | 04-SEP-10:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 287.74 | 0.00 |
October | 12134.58 | 01-OCT-10:32 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 0.00 |
November | 9717.35 | 05-NOV-11:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 86.21 | 0.00 |
December | 3418.84 | 04-DEC-11:00 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2940.89 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13472.62 | 827.22 | 222.09 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1463.00 | 0.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10019.12 | 22-JAN-14:33 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
February | 17360.65 | 05-FEB-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 245.27 | 0.00 |
March | 12733.49 | 26-MAR-14:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 293.79 | 0.00 |
April | 17038.59 | 30-APR-12:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 270.72 | 0.00 |
May | 17551.00 | 21-MAY-13:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.05 | 0.00 |
June | 16283.57 | 18-JUN-14:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 432.69 | 0.00 |
July | 17612.82 | 30-JUL-14:01 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 925.46 | 0.00 |
August | 16820.38 | 06-AUG-15:02 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 579.25 | 0.00 |
September | 17615.80 | 04-SEP-14:42 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 594.04 | 0.00 |
October | 18077.94 | 29-OCT-11:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 210.23 | 0.00 |
November | 18021.30 | 05-NOV-11:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 114.09 | 0.00 |
December | 17527.44 | 03-DEC-12:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10019.12 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18077.94 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2206.05 | 15.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3620.55 | 31-JAN-16:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
February | 10192.97 | 05-FEB-15:32 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 209.30 | 0.00 |
March | 8466.94 | 26-MAR-15:32 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 153.26 | 0.00 |
April | 12017.73 | 23-APR-14:13 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 158.40 | 0.00 |
May | 14044.82 | 21-MAY-16:22 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 373.90 | 0.00 |
June | 13686.96 | 18-JUN-14:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 270.33 | 0.00 |
July | 14270.13 | 30-JUL-14:01 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 616.04 | 0.00 |
August | 13922.97 | 06-AUG-15:02 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 377.06 | 0.00 |
September | 14376.26 | 04-SEP-16:42 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 427.84 | 0.00 |
October | 13816.53 | 09-OCT-15:22 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 382.58 | 0.00 |
November | 11153.86 | 12-NOV-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 0.00 |
December | 4313.43 | 06-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3620.55 | 169.55 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14376.26 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 616.04 | 11.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3855.31 | 23-JAN-14:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 0.00 |
February | 5023.08 | 06-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.21 | 0.00 |
March | 6661.16 | 02-MAR-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 0.00 |
April | 6264.78 | 28-APR-12:50 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 148.37 | 0.00 |
May | 10718.17 | 28-MAY-15:02 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 177.83 | 0.00 |
June | 12706.56 | 18-JUN-14:13 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 271.02 | 0.00 |
July | 13126.57 | 23-JUL-11:22 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 249.72 | 0.00 |
August | 12912.67 | 06-AUG-15:02 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 316.96 | 0.00 |
September | 13589.64 | 04-SEP-17:11 | 0.00 | 145.51 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 321.70 | 0.00 |
October | 11645.01 | 08-OCT-11:52 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 0.00 |
November | 10064.84 | 13-NOV-07:03 | 1071.35 | 699.01 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 |
December | 5865.89 | 11-DEC-07:03 | 803.52 | 674.76 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3855.31 | 0.00 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13589.64 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 321.70 | 9.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3167.85 | 24-JAN-11:00 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3708.75 | 06-FEB-14:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 0.00 |
March | 5597.20 | 27-MAR-10:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 | 0.00 |
April | 7435.04 | 30-APR-10:23 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 | 0.00 |
May | 9938.37 | 29-MAY-10:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 93.91 | 0.00 |
June | 11097.56 | 04-JUN-09:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 101.41 | 0.00 |
July | 11711.19 | 30-JUL-09:21 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.04 | 0.00 |
August | 10941.23 | 13-AUG-10:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 270.71 | 0.00 |
September | 11572.06 | 04-SEP-09:12 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 117.79 | 0.00 |
October | 10717.88 | 08-OCT-11:52 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 68.17 | 0.00 |
November | 8002.28 | 05-NOV-10:43 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 | 0.00 |
December | 4499.95 | 11-DEC-07:03 | 508.69 | 408.81 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3167.85 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11711.19 | 1654.44 | 444.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.71 | 5.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10701.52 | 23-JAN-13:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.41 | 0.00 |
February | 14735.88 | 05-FEB-14:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 170.26 | 0.00 |
March | 15076.17 | 27-MAR-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12084.32 | 0.00 |
April | 16378.57 | 28-APR-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15848.51 | 0.00 |
May | 15998.75 | 09-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15170.91 | 0.00 |
June | 16880.35 | 12-JUN-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 16464.72 | 0.00 |
July | 17745.58 | 21-JUL-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18606.80 | 0.00 |
August | 18064.30 | 16-AUG-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18520.37 | 0.00 |
September | 16759.41 | 05-SEP-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 14431.78 | 0.00 |
October | 15579.09 | 04-OCT-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12308.76 | 0.00 |
November | 15376.42 | 12-NOV-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 47.88 | 0.00 |
December | 15025.99 | 25-DEC-13:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10701.52 | 267.84 | 77.95 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 | |
Maximum of Months | 18064.30 | 687.71 | 350.81 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 18606.80 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3476.18 | 31-JAN-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
February | 5169.73 | 05-FEB-14:43 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 117.95 | 0.00 |
March | 5868.64 | 26-MAR-16:12 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 72.45 | 0.00 |
April | 9595.19 | 02-APR-15:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 82.51 | 0.00 |
May | 11612.33 | 28-MAY-15:02 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 115.19 | 0.00 |
June | 11509.73 | 18-JUN-14:13 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 176.36 | 0.00 |
July | 11873.68 | 04-JUL-15:22 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 173.51 | 0.00 |
August | 11872.16 | 06-AUG-16:22 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 176.86 | 0.00 |
September | 12754.17 | 04-SEP-17:11 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 200.41 | 0.00 |
October | 11536.19 | 09-OCT-15:22 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 206.81 | 0.00 |
November | 11604.87 | 05-NOV-15:22 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 99.57 | 0.00 |
December | 4328.24 | 11-DEC-07:03 | 508.66 | 431.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3476.18 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12754.17 | 805.38 | 431.28 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 206.81 | 5.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3785.80 | 23-JAN-14:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 0.00 |
February | 5298.98 | 06-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.10 | 0.00 |
March | 6970.53 | 02-MAR-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 49.65 | 0.00 |
April | 10808.69 | 30-APR-16:42 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 171.43 | 0.00 |
May | 13286.41 | 21-MAY-13:02 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.11 | 0.00 |
June | 13020.16 | 18-JUN-10:42 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 327.68 | 0.00 |
July | 13259.58 | 23-JUL-11:22 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 382.62 | 0.00 |
August | 12629.67 | 06-AUG-15:02 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 490.28 | 0.00 |
September | 13764.87 | 04-SEP-17:11 | 0.00 | 146.86 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 498.19 | 0.00 |
October | 12185.40 | 29-OCT-14:12 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 301.46 | 0.00 |
November | 7501.58 | 20-NOV-05:02 | 0.00 | 408.58 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 | 0.00 |
December | 4330.01 | 11-DEC-14:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3785.80 | 0.00 | 97.43 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 | 0.00 | |
Maximum of Months | 13764.87 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.11 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4259.82 | 24-JAN-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
February | 5388.00 | 07-FEB-13:03 | 2416.29 | 666.27 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 | 0.00 |
March | 9522.73 | 27-MAR-12:01 | 6443.43 | 1776.73 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 116.51 | 0.00 |
April | 10336.58 | 30-APR-10:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 38.48 | 0.00 |
May | 11419.32 | 07-MAY-09:52 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 97.45 | 0.00 |
June | 11773.72 | 18-JUN-10:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 196.85 | 0.00 |
July | 11838.71 | 23-JUL-11:22 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 242.09 | 0.00 |
August | 11302.24 | 06-AUG-10:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 190.65 | 0.00 |
September | 11991.12 | 04-SEP-09:12 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 181.66 | 0.00 |
October | 11160.37 | 01-OCT-10:32 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 0.00 |
November | 7424.55 | 01-NOV-12:02 | 4027.14 | 1110.46 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 0.00 |
December | 4701.91 | 04-DEC-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4259.82 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11991.12 | 6443.43 | 1776.73 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 242.09 | 0.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7466.27 | 23-JAN-13:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 0.00 |
February | 12442.36 | 05-FEB-12:23 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 201.96 | 0.00 |
March | 12966.27 | 26-MAR-14:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 253.10 | 0.00 |
April | 14303.86 | 30-APR-12:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 191.39 | 0.00 |
May | 14945.72 | 21-MAY-13:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.54 | 0.00 |
June | 14451.33 | 18-JUN-10:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 335.58 | 0.00 |
July | 14831.32 | 23-JUL-11:22 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 386.62 | 0.00 |
August | 14256.01 | 06-AUG-15:02 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 489.87 | 0.00 |
September | 15638.86 | 04-SEP-17:11 | 0.00 | 145.48 | 2702.70 | 0.00 | 0.00 | 0.00 | 0.00 | 493.58 | 0.00 |
October | 15871.90 | 29-OCT-13:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 206.30 | 0.00 |
November | 15355.05 | 12-NOV-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 75.54 | 0.00 |
December | 15380.76 | 03-DEC-13:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7466.27 | 0.00 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 | 0.00 | |
Maximum of Months | 15871.90 | 1272.23 | 350.81 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.54 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3517.07 | 31-JAN-16:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
February | 6527.31 | 05-FEB-16:23 | 127.16 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 143.74 | 0.00 |
March | 8749.46 | 26-MAR-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 115.69 | 0.00 |
April | 12330.49 | 30-APR-16:42 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 102.29 | 0.00 |
May | 12337.87 | 21-MAY-16:22 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 315.36 | 0.00 |
June | 11970.92 | 11-JUN-16:42 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 297.12 | 0.00 |
July | 12313.96 | 02-JUL-16:12 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 275.35 | 0.00 |
August | 12088.34 | 06-AUG-15:02 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 317.70 | 0.00 |
September | 13423.45 | 04-SEP-17:11 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 311.99 | 0.00 |
October | 12269.80 | 29-OCT-15:32 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 142.46 | 0.00 |
November | 11274.39 | 05-NOV-15:43 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 154.14 | 0.00 |
December | 4132.39 | 04-DEC-15:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3517.07 | 0.00 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13423.45 | 805.38 | 222.08 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 317.70 | 9.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.994600E+11 | 91720.45 | 23-JAN-13:00 | 0.989036E+10 | 9526.98 | 09-JAN-12:39 |
February | 0.958275E+11 | 112280.73 | 06-FEB-15:09 | 0.885688E+10 | 9511.31 | 01-FEB-12:09 |
March | 0.119220E+12 | 134555.88 | 27-MAR-10:00 | 0.977782E+10 | 9455.25 | 01-MAR-12:09 |
April | 0.126040E+12 | 147417.29 | 28-APR-12:09 | 0.884837E+10 | 9328.03 | 04-APR-11:09 |
May | 0.168129E+12 | 167370.98 | 30-MAY-15:09 | 0.889771E+10 | 9216.71 | 01-MAY-11:39 |
June | 0.186970E+12 | 177961.43 | 12-JUN-12:00 | 0.841885E+10 | 9130.27 | 01-JUN-11:09 |
July | 0.210222E+12 | 181817.05 | 31-JUL-14:09 | 0.837470E+10 | 9079.31 | 28-JUL-11:09 |
August | 0.227728E+12 | 192662.18 | 10-AUG-15:30 | 0.877116E+10 | 9139.82 | 31-AUG-11:20 |
September | 0.183947E+12 | 173018.25 | 05-SEP-15:30 | 0.856072E+10 | 9238.98 | 28-SEP-11:20 |
October | 0.158952E+12 | 147361.47 | 06-OCT-15:20 | 0.920809E+10 | 9359.14 | 31-OCT-11:20 |
November | 0.128411E+12 | 136228.17 | 01-NOV-14:09 | 0.931196E+10 | 9463.09 | 30-NOV-12:30 |
December | 0.105900E+12 | 107277.91 | 04-DEC-13:09 | 0.970813E+10 | 9519.41 | 29-DEC-12:39 |
Annual Sum or Average | 0.181081E+13 | 0.108625E+12 | ||||
Minimum of Months | 0.958275E+11 | 91720.45 | 0.837470E+10 | 9079.31 | ||
Maximum of Months | 0.227728E+12 | 192662.18 | 0.989036E+10 | 9526.98 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.948575E+10 | 16073.57 | 28-JAN-12:30 | 0.00 | 0.00 |
February | 0.102342E+11 | 18404.48 | 23-FEB-13:30 | 0.00 | 0.00 |
March | 0.133361E+11 | 20335.63 | 31-MAR-11:30 | 0.00 | 0.00 |
April | 0.149127E+11 | 22468.39 | 30-APR-11:30 | 0.00 | 0.00 |
May | 0.169547E+11 | 24093.10 | 21-MAY-12:30 | 0.00 | 0.00 |
June | 0.169981E+11 | 22040.82 | 27-JUN-11:30 | 0.00 | 0.00 |
July | 0.168557E+11 | 22939.98 | 20-JUL-13:30 | 0.00 | 0.00 |
August | 0.161647E+11 | 21839.39 | 16-AUG-11:30 | 0.00 | 0.00 |
September | 0.142823E+11 | 19430.68 | 06-SEP-12:30 | 0.00 | 0.00 |
October | 0.126552E+11 | 18045.55 | 19-OCT-12:09 | 0.00 | 0.00 |
November | 0.100800E+11 | 15554.98 | 04-NOV-12:09 | 0.00 | 0.00 |
December | 0.878022E+10 | 15450.37 | 25-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.160740E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.878022E+10 | 15450.37 | 0.00 | 0.00 | |
Maximum of Months | 0.169981E+11 | 24093.10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.140661E+11 | 0.340296E+10 | 0.545046E+11 | 0.976440E+09 | 0.551826E+10 | 12379742.02 | 0.195076E+09 | 0.207841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126636E+11 | 0.287051E+10 | 0.493409E+11 | 0.883654E+09 | 0.597434E+10 | 11196021.66 | 0.125976E+09 | 0.239573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149613E+11 | 0.291986E+10 | 0.567112E+11 | 0.102249E+10 | 0.857657E+10 | 12675672.10 | 52297701.77 | 0.349639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132931E+11 | 0.256346E+10 | 0.526212E+11 | 0.940474E+09 | 0.103254E+11 | 11960507.72 | 1242861.27 | 0.462828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142482E+11 | 0.243342E+10 | 0.556079E+11 | 0.999299E+09 | 0.167528E+11 | 12527707.06 | 0.00 | 0.780748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141385E+11 | 0.227383E+10 | 0.546110E+11 | 0.983639E+09 | 0.184136E+11 | 12231776.97 | 0.00 | 0.965373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133005E+11 | 0.239322E+10 | 0.536070E+11 | 0.955965E+09 | 0.195088E+11 | 12256437.81 | 0.00 | 0.120445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148141E+11 | 0.256800E+10 | 0.567112E+11 | 0.102238E+10 | 0.212120E+11 | 12675672.10 | 0.00 | 0.131388E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133121E+11 | 0.269153E+10 | 0.525990E+11 | 0.940244E+09 | 0.170124E+11 | 11960507.72 | 0.00 | 0.973795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139086E+11 | 0.305185E+10 | 0.545158E+11 | 0.976455E+09 | 0.145028E+11 | 12379742.02 | 0.00 | 0.719843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138595E+11 | 0.322242E+10 | 0.533244E+11 | 0.958233E+09 | 0.106597E+11 | 12059151.09 | 0.00 | 0.463747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136591E+11 | 0.348328E+10 | 0.535958E+11 | 0.956075E+09 | 0.671056E+10 | 12256437.81 | 49169963.45 | 0.274336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166225E+12 | 0.338743E+11 | 0.647750E+12 | 0.116153E+11 | 0.155167E+12 | 0.146559E+09 | 0.423762E+09 | 0.795605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126636E+11 | 0.227383E+10 | 0.493409E+11 | 0.883654E+09 | 0.551826E+10 | 11196021.66 | 0.00 | 0.207841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149613E+11 | 0.348328E+10 | 0.567112E+11 | 0.102249E+10 | 0.212120E+11 | 12675672.10 | 0.195076E+09 | 0.131388E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.989036E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.885688E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.977782E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.884837E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.889771E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.841885E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.837470E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.877116E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.856072E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.920809E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.931196E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.970813E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.108625E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.837470E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.989036E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 15467.97 | 23-JAN-16:00 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 826.61 | 09-JAN-08:20 | 9062.33 | 23-JAN-13:30 | 6.85 | 01-JAN-06:10 | 4479.12 | 03-JAN-07:30 |
February | 15896.49 | 09-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 826.18 | 09-FEB-08:20 | 14481.79 | 06-FEB-15:30 | 6.85 | 01-FEB-06:10 | 4479.05 | 01-FEB-07:19 |
March | 16963.78 | 15-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 828.85 | 15-MAR-07:19 | 18894.14 | 27-MAR-15:20 | 6.85 | 27-MAR-12:09 | 4479.05 | 07-MAR-07:19 |
April | 15852.96 | 18-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 827.39 | 18-APR-07:19 | 20504.89 | 24-APR-15:09 | 6.85 | 28-APR-11:09 | 591.02 | 05-APR-06:00 |
May | 14075.90 | 23-MAY-07:10 | 3824.74 | 01-MAY-05:10 | 40437.79 | 01-MAY-07:10 | 825.05 | 23-MAY-07:19 | 24006.88 | 30-MAY-15:30 | 6.85 | 05-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 14099.18 | 08-JUN-07:10 | 3824.74 | 01-JUN-05:10 | 40437.79 | 01-JUN-07:10 | 825.08 | 08-JUN-07:19 | 23849.55 | 12-JUN-15:09 | 6.85 | 01-JUN-11:09 | 0.00 | 01-JUN-00:10 |
July | 14930.95 | 20-JUL-07:10 | 3824.74 | 01-JUL-05:10 | 40437.79 | 03-JUL-07:10 | 826.17 | 20-JUL-07:19 | 24937.12 | 31-JUL-15:39 | 6.85 | 02-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 14365.66 | 29-AUG-07:10 | 3824.74 | 01-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 825.43 | 29-AUG-07:19 | 23544.84 | 10-AUG-15:00 | 6.85 | 02-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 14459.86 | 06-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 825.55 | 06-SEP-07:19 | 25508.25 | 05-SEP-15:39 | 6.85 | 03-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 14717.98 | 31-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 825.89 | 31-OCT-07:19 | 20313.50 | 10-OCT-15:20 | 6.85 | 04-OCT-12:09 | 0.00 | 01-OCT-00:10 |
November | 16137.57 | 29-NOV-16:00 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 826.00 | 29-NOV-08:20 | 16618.83 | 13-NOV-15:09 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 16490.00 | 15-DEC-16:00 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.05 | 15-DEC-08:20 | 12370.56 | 04-DEC-15:09 | 6.85 | 01-DEC-06:10 | 4479.05 | 18-DEC-07:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14075.90 | 3824.74 | 40437.79 | 825.05 | 9062.33 | 6.85 | 0.00 | |||||||
Maximum of Months | 16963.78 | 3824.74 | 40437.79 | 828.85 | 25508.25 | 6.85 | 4479.12 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 29461.03 | 30-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 45526.52 | 06-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 64528.97 | 27-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 77594.04 | 28-APR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 91160.81 | 31-MAY-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 102243.02 | 12-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 106936.93 | 21-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 116051.64 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 98640.44 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 76874.60 | 05-OCT-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 69203.63 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 42247.53 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29461.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 116051.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 91720.45 | 23-JAN-13:00 | 13903.46 | 38626.93 | 0.00 | 823.79 | 9023.62 | 6.85 | 0.00 | 29335.80 | 0.00 |
February | 112280.73 | 06-FEB-15:09 | 13903.46 | 37678.39 | 0.00 | 823.25 | 14342.26 | 6.85 | 0.00 | 45526.52 | 0.00 |
March | 134555.88 | 27-MAR-10:00 | 13903.46 | 38195.78 | 0.00 | 823.54 | 17097.28 | 6.85 | 0.00 | 64528.97 | 0.00 |
April | 147417.29 | 28-APR-12:09 | 13903.46 | 38626.93 | 0.00 | 823.79 | 16462.22 | 6.85 | 0.00 | 77594.04 | 0.00 |
May | 167370.98 | 30-MAY-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 23773.65 | 6.85 | 0.00 | 90408.86 | 0.00 |
June | 177961.43 | 12-JUN-12:00 | 13903.46 | 38626.93 | 0.00 | 823.79 | 22357.37 | 6.85 | 0.00 | 102243.02 | 0.00 |
July | 181817.05 | 31-JUL-14:09 | 13903.46 | 37678.39 | 0.00 | 823.25 | 24273.03 | 6.85 | 0.00 | 105132.06 | 0.00 |
August | 192662.18 | 10-AUG-15:30 | 13903.46 | 38454.47 | 0.00 | 823.69 | 23422.07 | 6.85 | 0.00 | 116051.64 | 0.00 |
September | 173018.25 | 05-SEP-15:30 | 13903.46 | 38454.47 | 0.00 | 823.69 | 25380.27 | 6.85 | 0.00 | 94449.51 | 0.00 |
October | 147361.47 | 06-OCT-15:20 | 13903.46 | 38454.47 | 0.00 | 823.69 | 17610.34 | 6.85 | 0.00 | 76562.66 | 0.00 |
November | 136228.17 | 01-NOV-14:09 | 13903.46 | 37678.39 | 0.00 | 823.25 | 14612.59 | 6.85 | 0.00 | 69203.63 | 0.00 |
December | 107277.91 | 04-DEC-13:09 | 13903.46 | 38626.93 | 0.00 | 823.79 | 11669.35 | 6.85 | 0.00 | 42247.53 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 91720.45 | 13903.46 | 37678.39 | 0.00 | 823.25 | 9023.62 | 6.85 | 0.00 | 29335.80 | 0.00 | |
Maximum of Months | 192662.18 | 13903.46 | 38626.93 | 0.00 | 823.79 | 25380.27 | 6.85 | 0.00 | 116051.64 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 9526.98 | 09-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 9511.31 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9455.25 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9328.03 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9216.71 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9130.27 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9079.31 | 28-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9139.82 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9238.98 | 28-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9359.14 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 9463.09 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 9519.41 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9079.31 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9526.98 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.47 | 3.67 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.70 | 9.67 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.66 | 8.83 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.66 | 14.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.58 | 9.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.70 | 9.50 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.56 | 8.17 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.67 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 104.17 | 27.64 | 64.33 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.70 | 14.00 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.53 | 1.83 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.63 | 10.00 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.94 | 12.17 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.81 | 10.67 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.83 | 15.83 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.70 | 10.50 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.89 | 12.00 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.75 | 13.17 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.39 | 4.17 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 139.17 | 27.78 | 90.83 | 27.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.94 | 15.83 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.37 | 1.00 | 27.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.65 | 2.33 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 3.00 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.61 | 7.17 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.73 | 9.33 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.65 | 8.33 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.67 | 13.00 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.64 | 9.33 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.92 | 10.33 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.99 | 11.50 | 28.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.80 | 9.83 | 27.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.58 | 3.67 | 27.58 |
Annual Sum or Average | 0.00 | 0.00 | 131.83 | 27.74 | 88.83 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.37 | 1.00 | 27.37 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.99 | 13.00 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 1.00 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 2.33 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.77 | 6.67 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.93 | 10.50 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.84 | 8.83 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 27.79 | 14.33 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 27.68 | 10.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.90 | 10.33 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.87 | 9.17 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.63 | 5.17 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 146.33 | 27.80 | 78.83 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 27.93 | 14.33 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.38 | 4.33 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.40 | 6.33 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.45 | 11.67 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.35 | 8.17 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.45 | 8.33 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.37 | 4.67 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 60.33 | 27.41 | 43.50 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.45 | 11.67 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.45 | 4.00 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.63 | 11.50 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.58 | 9.50 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.66 | 14.67 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.52 | 10.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.69 | 11.83 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.55 | 13.33 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.35 | 3.67 | 27.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 109.83 | 27.59 | 78.67 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.69 | 14.67 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.12 | 3.33 | 20.12 | 1.17 | 21.19 | 1.17 | 21.98 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.26 | 2.50 | 26.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 25.80 | 7.83 | 25.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.77 | 15.00 | 25.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 26.04 | 49.33 | 26.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 26.29 | 54.67 | 26.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 26.62 | 62.83 | 26.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 80.67 | 26.56 | 74.00 | 26.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 26.48 | 59.83 | 26.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 26.14 | 57.33 | 26.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 26.19 | 27.00 | 26.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.52 | 4.33 | 27.52 |
Annual Sum or Average | 3.33 | 20.12 | 3.33 | 20.12 | 440.50 | 26.26 | 415.83 | 26.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.19 | 1.17 | 21.98 |
Maximum of Months | 3.33 | 20.12 | 3.33 | 20.12 | 80.67 | 27.52 | 74.00 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 0.83 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.55 | 3.83 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.68 | 7.67 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.60 | 7.50 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.58 | 12.83 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.47 | 9.83 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.69 | 10.67 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.65 | 8.50 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.51 | 4.67 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 118.33 | 27.59 | 66.83 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.69 | 12.83 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.38 | 0.83 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.53 | 8.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.52 | 8.00 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.54 | 13.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.48 | 8.33 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.50 | 8.67 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.43 | 5.17 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 73.17 | 27.51 | 52.67 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.54 | 13.00 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.39 | 2.00 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.53 | 8.50 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.80 | 12.17 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.76 | 9.83 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.75 | 15.50 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.66 | 10.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.77 | 11.67 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.62 | 12.83 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.36 | 2.17 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 109.33 | 27.70 | 84.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.80 | 15.50 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.32 | 1.00 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.54 | 2.33 | 27.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.56 | 2.17 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.46 | 5.50 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.55 | 8.50 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.50 | 7.17 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.56 | 12.00 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.53 | 8.33 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.76 | 9.67 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.89 | 11.33 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.72 | 9.33 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.54 | 3.67 | 27.54 |
Annual Sum or Average | 0.00 | 0.00 | 103.33 | 27.63 | 81.00 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.32 | 1.00 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.89 | 12.00 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.46 | 0.67 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.58 | 1.50 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.64 | 5.33 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.82 | 9.17 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.72 | 8.33 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.72 | 13.17 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.66 | 9.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.77 | 9.83 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.79 | 7.67 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.54 | 4.17 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 112.83 | 27.72 | 68.83 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.82 | 13.17 | 27.88 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 23.98 | 274.33 | 24.58 | 0.00 | 24.58 |
February | 0.00 | 0.00 | 331.17 | 24.50 | 0.00 | 24.50 |
March | 0.00 | 0.00 | 367.17 | 24.45 | 0.00 | 24.45 |
April | 0.00 | 0.00 | 419.50 | 24.40 | 0.00 | 24.40 |
May | 0.00 | 0.00 | 492.17 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 496.17 | 24.34 | 0.00 | 24.34 |
August | 0.00 | 0.00 | 514.00 | 24.27 | 0.00 | 24.27 |
September | 0.00 | 0.00 | 485.00 | 24.37 | 0.00 | 24.37 |
October | 0.00 | 0.00 | 487.67 | 24.42 | 0.00 | 24.42 |
November | 0.00 | 0.00 | 474.17 | 24.43 | 0.00 | 24.43 |
December | 0.00 | 0.00 | 389.83 | 24.45 | 0.00 | 24.45 |
Annual Sum or Average | 5.00 | 23.98 | 5227.17 | 24.40 | 0.00 | 24.40 |
Minimum of Months | 0.00 | 0.00 | 274.33 | 24.27 | 0.00 | 24.27 |
Maximum of Months | 5.00 | 23.98 | 514.00 | 24.58 | 0.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.33 | 23.75 | 150.67 | 24.09 | 12.83 | 24.13 |
February | 41.33 | 23.66 | 234.83 | 24.28 | 0.00 | 24.28 |
March | 15.83 | 23.72 | 302.83 | 24.35 | 0.00 | 24.35 |
April | 3.50 | 23.89 | 393.17 | 24.35 | 0.00 | 24.35 |
May | 0.00 | 0.00 | 486.33 | 24.37 | 0.00 | 24.37 |
June | 0.00 | 0.00 | 496.00 | 24.33 | 0.00 | 24.33 |
July | 0.00 | 0.00 | 497.00 | 24.34 | 0.00 | 24.34 |
August | 0.00 | 0.00 | 514.00 | 24.28 | 0.00 | 24.28 |
September | 0.00 | 0.00 | 485.00 | 24.37 | 0.00 | 24.37 |
October | 0.00 | 0.00 | 481.17 | 24.40 | 0.00 | 24.40 |
November | 0.00 | 0.00 | 454.83 | 24.35 | 0.00 | 24.35 |
December | 41.33 | 23.64 | 268.50 | 24.26 | 0.00 | 24.26 |
Annual Sum or Average | 216.33 | 23.71 | 4764.33 | 24.33 | 12.83 | 24.33 |
Minimum of Months | 0.00 | 0.00 | 150.67 | 24.09 | 0.00 | 24.13 |
Maximum of Months | 114.33 | 23.89 | 514.00 | 24.40 | 12.83 | 24.40 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 239.50 | 23.42 | 87.67 | 23.59 | 12.83 | 23.60 |
February | 125.17 | 23.45 | 168.67 | 23.92 | 0.00 | 23.92 |
March | 67.50 | 23.56 | 256.83 | 24.14 | 0.00 | 24.14 |
April | 9.33 | 23.57 | 376.83 | 24.36 | 0.00 | 24.36 |
May | 0.17 | 26.67 | 483.67 | 24.43 | 0.17 | 24.43 |
June | 1.17 | 26.68 | 496.00 | 24.39 | 1.17 | 24.40 |
July | 3.00 | 26.63 | 496.17 | 24.44 | 3.00 | 24.45 |
August | 1.67 | 26.66 | 514.00 | 24.35 | 1.67 | 24.36 |
September | 1.83 | 26.66 | 485.00 | 24.43 | 1.83 | 24.44 |
October | 0.00 | 0.00 | 477.50 | 24.44 | 0.00 | 24.44 |
November | 5.17 | 23.61 | 402.67 | 24.32 | 0.00 | 24.32 |
December | 135.67 | 23.43 | 184.83 | 23.88 | 0.00 | 23.88 |
Annual Sum or Average | 590.17 | 23.49 | 4429.83 | 24.27 | 20.67 | 24.27 |
Minimum of Months | 0.00 | 0.00 | 87.67 | 23.59 | 0.00 | 23.60 |
Maximum of Months | 239.50 | 26.68 | 514.00 | 24.44 | 12.83 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.83 | 22.88 | 79.17 | 23.14 | 0.00 | 23.14 |
February | 177.33 | 23.02 | 170.33 | 23.62 | 0.67 | 23.62 |
March | 110.83 | 23.24 | 273.83 | 23.98 | 1.00 | 23.99 |
April | 54.50 | 24.65 | 398.33 | 24.49 | 29.50 | 24.57 |
May | 49.17 | 26.70 | 502.17 | 24.78 | 49.17 | 24.94 |
June | 72.17 | 26.56 | 496.00 | 24.83 | 72.17 | 25.03 |
July | 95.33 | 26.69 | 497.00 | 25.03 | 95.33 | 25.26 |
August | 70.67 | 26.63 | 514.00 | 24.82 | 70.67 | 25.01 |
September | 79.50 | 26.47 | 485.00 | 24.88 | 79.50 | 25.07 |
October | 68.33 | 26.17 | 487.33 | 24.77 | 66.83 | 24.93 |
November | 33.17 | 23.66 | 390.17 | 24.34 | 5.67 | 24.35 |
December | 203.83 | 23.06 | 188.33 | 23.60 | 7.33 | 23.59 |
Annual Sum or Average | 1315.67 | 24.26 | 4481.67 | 24.46 | 477.83 | 24.61 |
Minimum of Months | 33.17 | 22.88 | 79.17 | 23.14 | 0.00 | 23.14 |
Maximum of Months | 300.83 | 26.70 | 514.00 | 25.03 | 95.33 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 218.67 | 22.97 | 144.33 | 23.51 | 0.00 | 23.51 |
February | 124.83 | 23.08 | 224.33 | 23.90 | 1.50 | 23.91 |
March | 83.00 | 23.37 | 322.67 | 24.15 | 3.50 | 24.17 |
April | 69.33 | 25.76 | 430.50 | 24.70 | 53.17 | 24.87 |
May | 62.33 | 26.84 | 507.17 | 24.87 | 62.33 | 25.06 |
June | 78.33 | 26.67 | 496.00 | 24.88 | 78.33 | 25.09 |
July | 101.00 | 26.80 | 497.00 | 25.08 | 101.00 | 25.33 |
August | 77.83 | 26.75 | 514.00 | 24.88 | 77.83 | 25.09 |
September | 85.83 | 26.65 | 485.00 | 24.95 | 85.83 | 25.18 |
October | 79.83 | 26.51 | 495.67 | 24.89 | 79.67 | 25.09 |
November | 30.17 | 24.91 | 424.50 | 24.52 | 16.17 | 24.58 |
December | 143.00 | 23.15 | 250.33 | 23.87 | 7.83 | 23.88 |
Annual Sum or Average | 1154.17 | 24.82 | 4791.50 | 24.61 | 567.17 | 24.78 |
Minimum of Months | 30.17 | 22.97 | 144.33 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 218.67 | 26.84 | 514.00 | 25.08 | 101.00 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 199.83 | 23.10 | 212.83 | 23.85 | 4.83 | 23.89 |
February | 122.00 | 23.31 | 250.17 | 24.06 | 9.50 | 24.13 |
March | 94.83 | 23.52 | 318.17 | 24.17 | 8.00 | 24.23 |
April | 67.83 | 25.17 | 408.50 | 24.59 | 43.83 | 24.73 |
May | 47.67 | 26.70 | 499.50 | 24.77 | 47.67 | 24.93 |
June | 70.17 | 26.52 | 496.00 | 24.81 | 70.17 | 25.00 |
July | 94.67 | 26.66 | 497.00 | 25.02 | 94.67 | 25.24 |
August | 70.67 | 26.67 | 514.00 | 24.83 | 70.67 | 25.03 |
September | 83.83 | 26.59 | 485.00 | 24.93 | 83.83 | 25.15 |
October | 79.33 | 26.56 | 494.67 | 24.91 | 79.33 | 25.11 |
November | 55.00 | 25.92 | 429.67 | 24.70 | 41.50 | 24.86 |
December | 138.00 | 23.62 | 285.17 | 24.21 | 23.50 | 24.32 |
Annual Sum or Average | 1123.83 | 24.88 | 4890.67 | 24.63 | 577.50 | 24.80 |
Minimum of Months | 47.67 | 23.10 | 212.83 | 23.85 | 4.83 | 23.89 |
Maximum of Months | 199.83 | 26.70 | 514.00 | 25.02 | 94.67 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 258.50 | 22.87 | 138.83 | 23.41 | 0.33 | 23.41 |
February | 148.67 | 23.06 | 214.00 | 23.81 | 3.50 | 23.84 |
March | 102.00 | 23.48 | 306.67 | 24.13 | 7.67 | 24.19 |
April | 66.83 | 25.24 | 410.17 | 24.62 | 44.67 | 24.76 |
May | 57.00 | 26.80 | 501.00 | 24.85 | 57.00 | 25.03 |
June | 79.67 | 26.69 | 496.00 | 24.89 | 79.67 | 25.11 |
July | 101.17 | 26.77 | 497.00 | 25.08 | 101.17 | 25.32 |
August | 79.83 | 26.77 | 514.00 | 24.89 | 79.83 | 25.11 |
September | 90.50 | 26.61 | 485.00 | 24.96 | 90.50 | 25.19 |
October | 76.00 | 26.34 | 489.33 | 24.85 | 74.83 | 25.03 |
November | 45.33 | 24.92 | 408.00 | 24.51 | 23.00 | 24.60 |
December | 171.00 | 23.05 | 230.17 | 23.79 | 8.67 | 23.79 |
Annual Sum or Average | 1276.50 | 24.60 | 4690.17 | 24.57 | 570.83 | 24.74 |
Minimum of Months | 45.33 | 22.87 | 138.83 | 23.41 | 0.33 | 23.41 |
Maximum of Months | 258.50 | 26.80 | 514.00 | 25.08 | 101.17 | 25.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 163.67 | 23.47 | 142.17 | 23.80 | 0.00 | 23.80 |
February | 89.50 | 23.42 | 221.17 | 24.01 | 0.17 | 24.01 |
March | 74.00 | 23.51 | 292.83 | 24.11 | 0.00 | 24.11 |
April | 21.67 | 24.36 | 407.17 | 24.39 | 10.00 | 24.41 |
May | 24.50 | 26.66 | 506.00 | 24.64 | 24.50 | 24.73 |
June | 50.83 | 26.46 | 496.00 | 24.72 | 50.83 | 24.87 |
July | 70.00 | 26.67 | 497.00 | 24.93 | 70.00 | 25.12 |
August | 48.00 | 26.72 | 514.00 | 24.74 | 48.00 | 24.89 |
September | 57.50 | 26.61 | 485.00 | 24.82 | 57.50 | 24.99 |
October | 35.67 | 26.55 | 496.50 | 24.73 | 35.67 | 24.85 |
November | 1.17 | 25.28 | 473.17 | 24.45 | 1.17 | 24.45 |
December | 46.17 | 23.53 | 316.67 | 24.17 | 0.00 | 24.17 |
Annual Sum or Average | 682.67 | 24.83 | 4847.67 | 24.53 | 297.83 | 24.64 |
Minimum of Months | 1.17 | 23.42 | 142.17 | 23.80 | 0.00 | 23.80 |
Maximum of Months | 163.67 | 26.72 | 514.00 | 24.93 | 70.00 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.33 | 23.54 | 232.00 | 24.16 | 0.00 | 24.16 |
February | 42.00 | 23.42 | 283.67 | 24.26 | 0.17 | 24.26 |
March | 42.17 | 23.53 | 352.50 | 24.26 | 0.17 | 24.26 |
April | 29.17 | 26.03 | 450.50 | 24.59 | 24.33 | 24.68 |
May | 51.33 | 26.85 | 508.00 | 24.81 | 51.33 | 24.98 |
June | 58.83 | 26.69 | 496.00 | 24.80 | 58.83 | 24.99 |
July | 83.67 | 26.84 | 497.00 | 25.03 | 83.67 | 25.25 |
August | 63.00 | 26.88 | 514.00 | 24.84 | 63.00 | 25.04 |
September | 68.00 | 26.86 | 485.00 | 24.93 | 68.00 | 25.14 |
October | 59.17 | 26.84 | 502.00 | 24.90 | 59.17 | 25.08 |
November | 9.67 | 26.91 | 481.50 | 24.62 | 9.67 | 24.66 |
December | 20.33 | 23.55 | 367.00 | 24.33 | 0.00 | 24.33 |
Annual Sum or Average | 611.67 | 25.77 | 5169.17 | 24.68 | 418.33 | 24.83 |
Minimum of Months | 9.67 | 23.42 | 232.00 | 24.16 | 0.00 | 24.16 |
Maximum of Months | 84.33 | 26.91 | 514.00 | 25.03 | 83.67 | 25.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.67 | 22.74 | 297.50 | 24.17 | 4.33 | 24.19 |
February | 60.67 | 22.96 | 323.17 | 24.22 | 11.17 | 24.25 |
March | 70.50 | 23.05 | 352.50 | 24.18 | 16.67 | 24.18 |
April | 55.00 | 24.17 | 415.67 | 24.47 | 37.83 | 24.50 |
May | 65.50 | 25.49 | 503.67 | 24.79 | 65.50 | 24.87 |
June | 145.67 | 25.39 | 496.00 | 24.90 | 145.67 | 24.99 |
July | 201.33 | 25.57 | 497.00 | 25.12 | 201.33 | 25.22 |
August | 194.17 | 25.71 | 514.00 | 25.12 | 194.17 | 25.25 |
September | 173.33 | 25.82 | 485.00 | 25.14 | 173.33 | 25.28 |
October | 136.67 | 25.73 | 502.00 | 25.05 | 136.67 | 25.17 |
November | 80.50 | 25.54 | 482.67 | 24.79 | 78.67 | 24.89 |
December | 63.00 | 23.88 | 391.83 | 24.46 | 29.67 | 24.52 |
Annual Sum or Average | 1331.00 | 25.04 | 5261.00 | 24.78 | 1095.00 | 24.89 |
Minimum of Months | 55.00 | 22.74 | 297.50 | 24.17 | 4.33 | 24.18 |
Maximum of Months | 201.33 | 25.82 | 514.00 | 25.14 | 201.33 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.17 | 23.51 | 224.33 | 24.11 | 0.00 | 24.11 |
February | 54.50 | 23.44 | 280.33 | 24.22 | 0.33 | 24.22 |
March | 39.00 | 23.59 | 348.50 | 24.29 | 0.83 | 24.30 |
April | 31.33 | 25.65 | 433.67 | 24.57 | 24.50 | 24.65 |
May | 40.67 | 26.84 | 506.33 | 24.77 | 40.67 | 24.91 |
June | 63.83 | 26.70 | 496.00 | 24.83 | 63.83 | 25.02 |
July | 87.50 | 26.83 | 497.00 | 25.04 | 87.50 | 25.27 |
August | 69.17 | 26.90 | 514.00 | 24.87 | 69.17 | 25.08 |
September | 78.67 | 26.83 | 485.00 | 24.97 | 78.67 | 25.20 |
October | 52.50 | 26.79 | 500.50 | 24.87 | 52.50 | 25.04 |
November | 15.17 | 26.87 | 481.33 | 24.62 | 15.17 | 24.68 |
December | 29.67 | 23.56 | 352.67 | 24.34 | 0.00 | 24.34 |
Annual Sum or Average | 666.17 | 25.63 | 5119.67 | 24.68 | 433.17 | 24.83 |
Minimum of Months | 15.17 | 23.44 | 224.33 | 24.11 | 0.00 | 24.11 |
Maximum of Months | 104.17 | 26.90 | 514.00 | 25.04 | 87.50 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 240.50 | 23.24 | 108.17 | 23.52 | 0.00 | 23.52 |
February | 124.83 | 23.30 | 203.50 | 23.88 | 0.67 | 23.88 |
March | 73.00 | 23.45 | 301.17 | 24.12 | 0.17 | 24.12 |
April | 31.50 | 24.80 | 419.83 | 24.47 | 19.83 | 24.52 |
May | 44.17 | 26.67 | 506.00 | 24.74 | 44.17 | 24.89 |
June | 68.50 | 26.51 | 496.00 | 24.80 | 68.50 | 24.99 |
July | 93.00 | 26.60 | 497.00 | 25.00 | 93.00 | 25.21 |
August | 66.83 | 26.52 | 514.00 | 24.78 | 66.83 | 24.96 |
September | 74.17 | 26.41 | 485.00 | 24.84 | 74.17 | 25.02 |
October | 53.83 | 26.24 | 490.00 | 24.73 | 53.83 | 24.87 |
November | 8.67 | 24.02 | 433.50 | 24.37 | 3.00 | 24.38 |
December | 142.83 | 23.38 | 233.83 | 23.90 | 6.33 | 23.90 |
Annual Sum or Average | 1021.83 | 24.61 | 4688.00 | 24.52 | 430.50 | 24.65 |
Minimum of Months | 8.67 | 23.24 | 108.17 | 23.52 | 0.00 | 23.52 |
Maximum of Months | 240.50 | 26.67 | 514.00 | 25.00 | 93.00 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 162.17 | 23.30 | 134.67 | 23.83 | 0.50 | 23.84 |
February | 79.33 | 23.29 | 202.83 | 24.14 | 0.67 | 24.14 |
March | 52.50 | 23.63 | 280.50 | 24.32 | 2.83 | 24.34 |
April | 50.17 | 26.05 | 376.17 | 24.79 | 42.17 | 24.95 |
May | 59.83 | 26.82 | 430.00 | 24.98 | 59.83 | 25.18 |
June | 74.00 | 26.62 | 418.00 | 24.99 | 74.00 | 25.20 |
July | 99.17 | 26.73 | 422.00 | 25.21 | 99.17 | 25.45 |
August | 75.50 | 26.65 | 433.00 | 24.98 | 75.50 | 25.20 |
September | 79.50 | 26.63 | 410.00 | 25.06 | 79.50 | 25.28 |
October | 72.83 | 26.60 | 424.00 | 25.01 | 72.83 | 25.21 |
November | 12.17 | 25.97 | 384.33 | 24.63 | 10.33 | 24.68 |
December | 95.33 | 23.48 | 235.67 | 24.14 | 7.00 | 24.15 |
Annual Sum or Average | 912.50 | 25.23 | 4151.17 | 24.76 | 524.33 | 24.94 |
Minimum of Months | 12.17 | 23.29 | 134.67 | 23.83 | 0.50 | 23.84 |
Maximum of Months | 162.17 | 26.82 | 433.00 | 25.21 | 99.17 | 25.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 132.00 | 23.40 | 247.00 | 24.14 | 4.00 | 24.17 |
February | 75.50 | 23.60 | 286.50 | 24.26 | 7.50 | 24.31 |
March | 58.67 | 23.78 | 348.83 | 24.29 | 5.83 | 24.33 |
April | 43.67 | 25.46 | 428.33 | 24.58 | 32.50 | 24.68 |
May | 43.33 | 26.67 | 505.17 | 24.74 | 43.33 | 24.88 |
June | 64.83 | 26.45 | 496.00 | 24.77 | 64.83 | 24.95 |
July | 90.67 | 26.58 | 497.00 | 24.98 | 90.67 | 25.19 |
August | 67.50 | 26.55 | 514.00 | 24.79 | 67.50 | 24.98 |
September | 77.00 | 26.56 | 485.00 | 24.90 | 77.00 | 25.10 |
October | 73.33 | 26.63 | 497.67 | 24.90 | 73.33 | 25.10 |
November | 41.83 | 26.67 | 462.50 | 24.73 | 40.00 | 24.88 |
December | 85.33 | 24.08 | 326.67 | 24.42 | 20.67 | 24.52 |
Annual Sum or Average | 853.67 | 25.32 | 5094.67 | 24.67 | 527.17 | 24.82 |
Minimum of Months | 41.83 | 23.40 | 247.00 | 24.14 | 4.00 | 24.17 |
Maximum of Months | 132.00 | 26.67 | 514.00 | 24.98 | 90.67 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 190.50 | 23.22 | 166.17 | 23.75 | 0.00 | 23.75 |
February | 94.83 | 23.29 | 249.50 | 24.05 | 1.67 | 24.06 |
March | 61.67 | 23.66 | 339.50 | 24.25 | 4.33 | 24.28 |
April | 50.00 | 25.62 | 430.67 | 24.63 | 38.83 | 24.75 |
May | 52.33 | 26.78 | 506.00 | 24.81 | 52.33 | 24.98 |
June | 77.00 | 26.63 | 496.00 | 24.87 | 77.00 | 25.07 |
July | 101.17 | 26.70 | 497.00 | 25.06 | 101.17 | 25.30 |
August | 79.17 | 26.68 | 514.00 | 24.87 | 79.17 | 25.08 |
September | 85.67 | 26.57 | 485.00 | 24.93 | 85.67 | 25.15 |
October | 67.00 | 26.45 | 492.67 | 24.84 | 67.00 | 25.01 |
November | 21.83 | 25.92 | 448.33 | 24.53 | 17.00 | 24.60 |
December | 111.50 | 23.36 | 271.33 | 24.06 | 7.00 | 24.06 |
Annual Sum or Average | 992.67 | 25.04 | 4896.17 | 24.63 | 531.17 | 24.79 |
Minimum of Months | 21.83 | 23.22 | 166.17 | 23.75 | 0.00 | 23.75 |
Maximum of Months | 190.50 | 26.78 | 514.00 | 25.06 | 101.17 | 25.30 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35381 | 42.78857 | 0.46203 | 9.64426 |
February | 454.00000 | 24.37047 | 45.91763 | 0.49375 | 10.28395 |
March | 514.00000 | 24.33155 | 45.25710 | 0.49023 | 10.21057 |
April | 485.00000 | 24.35240 | 48.36455 | 0.52735 | 11.02676 |
May | 508.00000 | 24.36886 | 50.70923 | -0.2885 | 7.15678 |
June | 496.00000 | 24.34356 | 53.67875 | -0.2708 | 6.93634 |
July | 497.00000 | 24.34220 | 53.01597 | -0.2757 | 6.89330 |
August | 514.00000 | 24.26925 | 53.16878 | -0.2947 | 7.05874 |
September | 485.00000 | 24.36747 | 53.04298 | -0.2676 | 6.91329 |
October | 502.00000 | 24.40599 | 51.26576 | 0.57624 | 12.21964 |
November | 489.00000 | 24.41367 | 50.49742 | 0.56239 | 11.80779 |
December | 497.00000 | 24.36549 | 47.29649 | 0.50679 | 10.56711 |
Annual Sum or Average | 5943.00000 | 24.35661 | 49.59935 | 0.18187 | 9.21249 |
Minimum of Months | 454.00000 | 24.26925 | 42.78857 | -0.2947 | 6.89330 |
Maximum of Months | 514.00000 | 24.41367 | 53.67875 | 0.57624 | 12.21964 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08102 | 44.23079 | 0.38699 | 8.36903 |
February | 454.00000 | 24.17593 | 46.39999 | 0.43398 | 9.10879 |
March | 514.00000 | 24.21700 | 45.62973 | 0.45241 | 9.44112 |
April | 485.00000 | 24.29213 | 49.24646 | 0.51037 | 10.64165 |
May | 508.00000 | 24.35119 | 52.09756 | -0.2912 | 7.21530 |
June | 496.00000 | 24.33371 | 55.16826 | -0.2693 | 6.94718 |
July | 497.00000 | 24.34453 | 55.14961 | -0.2605 | 6.77172 |
August | 514.00000 | 24.28486 | 55.96977 | -0.2720 | 6.83994 |
September | 485.00000 | 24.36664 | 55.52765 | -0.2566 | 6.84965 |
October | 502.00000 | 24.38820 | 53.18511 | 0.57767 | 12.26373 |
November | 489.00000 | 24.33204 | 51.31686 | 0.53458 | 11.12910 |
December | 497.00000 | 24.16700 | 47.28187 | 0.44050 | 9.25407 |
Annual Sum or Average | 5943.00000 | 24.27821 | 50.95699 | 0.16262 | 8.72672 |
Minimum of Months | 454.00000 | 24.08102 | 44.23079 | -0.2912 | 6.77172 |
Maximum of Months | 514.00000 | 24.38820 | 55.96977 | 0.57767 | 12.26373 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77520 | 44.08724 | 0.30153 | 7.29166 |
February | 454.00000 | 23.97692 | 45.91314 | 0.37683 | 8.26763 |
March | 514.00000 | 24.11939 | 44.78260 | 0.42225 | 8.96283 |
April | 485.00000 | 24.28713 | 48.15591 | 0.50745 | 10.62482 |
May | 508.00000 | 24.40567 | 51.21350 | -0.2594 | 7.05208 |
June | 496.00000 | 24.38723 | 54.71579 | -0.2311 | 6.75082 |
July | 497.00000 | 24.42766 | 54.62243 | -0.2087 | 6.56742 |
August | 514.00000 | 24.34086 | 55.63735 | -0.2286 | 6.58824 |
September | 485.00000 | 24.42011 | 55.22900 | -0.2225 | 6.71201 |
October | 502.00000 | 24.42040 | 52.52015 | 0.58677 | 12.55258 |
November | 489.00000 | 24.28004 | 50.26999 | 0.51217 | 10.64576 |
December | 497.00000 | 23.94146 | 46.68479 | 0.37389 | 8.25195 |
Annual Sum or Average | 5943.00000 | 24.23319 | 50.34262 | 0.15832 | 8.34911 |
Minimum of Months | 454.00000 | 23.77520 | 44.08724 | -0.2594 | 6.56742 |
Maximum of Months | 514.00000 | 24.42766 | 55.63735 | 0.58677 | 12.55258 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.35573 | 46.37001 | 0.20727 | 6.97758 |
February | 454.00000 | 23.70394 | 49.20689 | 0.33214 | 8.19827 |
March | 514.00000 | 23.99005 | 46.66793 | 0.41438 | 9.24388 |
April | 485.00000 | 24.34307 | 49.89764 | 0.56141 | 12.30618 |
May | 508.00000 | 24.58423 | 51.69750 | -0.1110 | 6.82246 |
June | 496.00000 | 24.57776 | 55.66779 | -0.0552 | 6.65985 |
July | 497.00000 | 24.70836 | 55.18278 | 0.00426 | 6.94193 |
August | 514.00000 | 24.57063 | 56.30044 | -0.0348 | 6.55668 |
September | 485.00000 | 24.61644 | 56.79527 | -0.0637 | 6.85491 |
October | 502.00000 | 24.55583 | 54.43541 | 0.66846 | 15.19231 |
November | 489.00000 | 24.27331 | 52.34706 | 0.53589 | 11.47576 |
December | 497.00000 | 23.68695 | 49.99406 | 0.32902 | 8.12935 |
Annual Sum or Average | 5943.00000 | 24.25042 | 52.05455 | 0.23065 | 8.77286 |
Minimum of Months | 454.00000 | 23.35573 | 46.37001 | -0.1110 | 6.55668 |
Maximum of Months | 514.00000 | 24.70836 | 56.79527 | 0.66846 | 15.19231 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.65403 | 45.55328 | 0.29208 | 7.85468 |
February | 454.00000 | 23.91320 | 48.52403 | 0.40010 | 9.28010 |
March | 514.00000 | 24.10619 | 46.27354 | 0.46563 | 10.30543 |
April | 485.00000 | 24.43677 | 49.39811 | 0.61801 | 13.92811 |
May | 508.00000 | 24.62162 | 51.46851 | -0.0420 | 6.85467 |
June | 496.00000 | 24.59603 | 55.49825 | -0.0010 | 6.74628 |
July | 497.00000 | 24.73434 | 55.02124 | 0.06154 | 7.28586 |
August | 514.00000 | 24.59151 | 56.10332 | 0.02720 | 6.69934 |
September | 485.00000 | 24.65427 | 56.42641 | 0.00338 | 7.02570 |
October | 502.00000 | 24.62151 | 53.89809 | 0.71845 | 16.81842 |
November | 489.00000 | 24.41216 | 51.88544 | 0.59470 | 13.06437 |
December | 497.00000 | 23.89403 | 49.44280 | 0.39298 | 9.07388 |
Annual Sum or Average | 5943.00000 | 24.35537 | 51.63467 | 0.29253 | 9.56583 |
Minimum of Months | 454.00000 | 23.65403 | 45.55328 | -0.0420 | 6.69934 |
Maximum of Months | 514.00000 | 24.73434 | 56.42641 | 0.71845 | 16.81842 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.84958 | 43.88709 | 0.36134 | 9.37965 |
February | 454.00000 | 23.99285 | 47.49927 | 0.44060 | 10.36316 |
March | 514.00000 | 24.10726 | 45.85382 | 0.47408 | 10.61817 |
April | 485.00000 | 24.37863 | 49.62293 | 0.58693 | 13.06117 |
May | 508.00000 | 24.57830 | 51.72622 | -0.1121 | 6.84057 |
June | 496.00000 | 24.56694 | 55.77292 | -0.0695 | 6.66623 |
July | 497.00000 | 24.70195 | 55.22573 | -0.0009 | 6.93490 |
August | 514.00000 | 24.57533 | 56.19939 | -0.0178 | 6.60050 |
September | 485.00000 | 24.64606 | 56.41043 | -0.0077 | 7.02397 |
October | 502.00000 | 24.63576 | 53.64936 | 0.74028 | 17.57603 |
November | 489.00000 | 24.45890 | 51.05077 | 0.63938 | 14.50876 |
December | 497.00000 | 24.08046 | 47.79071 | 0.46598 | 10.96757 |
Annual Sum or Average | 5943.00000 | 24.38305 | 51.23890 | 0.28956 | 10.02896 |
Minimum of Months | 454.00000 | 23.84958 | 43.88709 | -0.1121 | 6.60050 |
Maximum of Months | 514.00000 | 24.70195 | 56.41043 | 0.74028 | 17.57603 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.52987 | 46.01627 | 0.26315 | 7.86663 |
February | 454.00000 | 23.83118 | 48.87350 | 0.38230 | 9.19297 |
March | 514.00000 | 24.07534 | 46.42038 | 0.46078 | 10.33134 |
April | 485.00000 | 24.40049 | 49.75828 | 0.60339 | 13.57353 |
May | 508.00000 | 24.61462 | 51.65822 | -0.0586 | 6.99054 |
June | 496.00000 | 24.60405 | 55.60914 | -0.0061 | 6.88033 |
July | 497.00000 | 24.73373 | 55.11526 | 0.05263 | 7.30024 |
August | 514.00000 | 24.59873 | 56.18946 | 0.02112 | 6.82064 |
September | 485.00000 | 24.65679 | 56.61604 | -0.0031 | 7.13055 |
October | 502.00000 | 24.60460 | 54.33032 | 0.71074 | 16.58765 |
November | 489.00000 | 24.34951 | 52.12847 | 0.57968 | 12.75492 |
December | 497.00000 | 23.82940 | 49.67445 | 0.37928 | 9.15479 |
Annual Sum or Average | 5943.00000 | 24.32184 | 51.87471 | 0.28043 | 9.53835 |
Minimum of Months | 454.00000 | 23.52987 | 46.01627 | -0.0586 | 6.82064 |
Maximum of Months | 514.00000 | 24.73373 | 56.61604 | 0.71074 | 16.58765 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.91087 | 45.97127 | 0.35402 | 7.95164 |
February | 454.00000 | 24.01284 | 49.32692 | 0.41255 | 8.87902 |
March | 514.00000 | 24.09454 | 47.56646 | 0.43712 | 9.29265 |
April | 485.00000 | 24.31565 | 50.19267 | 0.53731 | 11.37660 |
May | 508.00000 | 24.53790 | 51.17073 | -0.1630 | 6.60671 |
June | 496.00000 | 24.54626 | 54.19030 | -0.1037 | 6.40688 |
July | 497.00000 | 24.67960 | 52.90590 | -0.0445 | 6.52904 |
August | 514.00000 | 24.55361 | 52.97378 | -0.0704 | 6.33901 |
September | 485.00000 | 24.61148 | 53.47140 | -0.0836 | 6.57574 |
October | 502.00000 | 24.59550 | 51.96167 | 0.67459 | 15.21254 |
November | 489.00000 | 24.43533 | 51.53575 | 0.59338 | 12.63880 |
December | 497.00000 | 24.14404 | 49.79911 | 0.46003 | 9.70755 |
Annual Sum or Average | 5943.00000 | 24.37174 | 50.92209 | 0.24812 | 8.94919 |
Minimum of Months | 454.00000 | 23.91087 | 45.97127 | -0.1630 | 6.33901 |
Maximum of Months | 514.00000 | 24.67960 | 54.19030 | 0.67459 | 15.21254 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12553 | 45.31902 | 0.42484 | 9.16903 |
February | 454.00000 | 24.19238 | 48.72321 | 0.47666 | 10.16283 |
March | 514.00000 | 24.21270 | 47.15888 | 0.49020 | 10.45212 |
April | 485.00000 | 24.45161 | 49.60448 | 0.60337 | 13.22897 |
May | 508.00000 | 24.60295 | 50.81632 | -0.0832 | 6.50947 |
June | 496.00000 | 24.58099 | 53.92565 | -0.0425 | 6.41727 |
July | 497.00000 | 24.71914 | 52.67047 | 0.01899 | 6.77347 |
August | 514.00000 | 24.58571 | 52.71960 | -0.0016 | 6.40621 |
September | 485.00000 | 24.66138 | 53.08113 | -0.0095 | 6.71513 |
October | 502.00000 | 24.67058 | 51.49350 | 0.72972 | 17.01721 |
November | 489.00000 | 24.56197 | 51.15145 | 0.65244 | 14.41370 |
December | 497.00000 | 24.27539 | 49.42347 | 0.51097 | 10.84094 |
Annual Sum or Average | 5943.00000 | 24.47127 | 50.50914 | 0.31201 | 9.82499 |
Minimum of Months | 454.00000 | 24.12553 | 45.31902 | -0.0832 | 6.40621 |
Maximum of Months | 514.00000 | 24.71914 | 53.92565 | 0.72972 | 17.01721 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12465 | 44.70570 | 0.46538 | 10.66948 |
February | 454.00000 | 24.17186 | 48.74186 | 0.50689 | 11.27705 |
March | 514.00000 | 24.15614 | 47.27167 | 0.49266 | 10.81896 |
April | 485.00000 | 24.38703 | 50.63073 | 0.57606 | 12.55794 |
May | 508.00000 | 24.69660 | 52.46903 | -0.1084 | 6.49075 |
June | 496.00000 | 24.75636 | 57.28925 | -0.0354 | 6.40905 |
July | 497.00000 | 24.93728 | 57.57706 | 0.05727 | 6.83536 |
August | 514.00000 | 24.89671 | 58.41233 | 0.08317 | 7.00150 |
September | 485.00000 | 24.89992 | 57.29550 | 0.07986 | 7.02085 |
October | 502.00000 | 24.86179 | 53.95598 | 0.80907 | 19.63509 |
November | 489.00000 | 24.64589 | 52.70661 | 0.72401 | 16.70160 |
December | 497.00000 | 24.31866 | 49.39683 | 0.56826 | 12.75149 |
Annual Sum or Average | 5943.00000 | 24.57338 | 52.55461 | 0.34937 | 10.66230 |
Minimum of Months | 454.00000 | 24.12465 | 44.70570 | -0.1084 | 6.40905 |
Maximum of Months | 514.00000 | 24.93728 | 58.41233 | 0.80907 | 19.63509 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.09771 | 45.44481 | 0.41473 | 9.04301 |
February | 454.00000 | 24.17236 | 48.78829 | 0.47080 | 10.06621 |
March | 514.00000 | 24.22199 | 47.07155 | 0.49393 | 10.53314 |
April | 485.00000 | 24.42850 | 49.85797 | 0.59273 | 12.92057 |
May | 508.00000 | 24.59838 | 50.99965 | -0.0975 | 6.58071 |
June | 496.00000 | 24.59098 | 54.01367 | -0.0451 | 6.49915 |
July | 497.00000 | 24.72059 | 52.75385 | 0.01218 | 6.76204 |
August | 514.00000 | 24.59552 | 52.80580 | -0.0059 | 6.49582 |
September | 485.00000 | 24.67011 | 53.21546 | -0.0130 | 6.77497 |
October | 502.00000 | 24.66824 | 51.75414 | 0.72513 | 16.86862 |
November | 489.00000 | 24.53697 | 51.26437 | 0.64545 | 14.19398 |
December | 497.00000 | 24.27304 | 49.39328 | 0.50972 | 10.87138 |
Annual Sum or Average | 5943.00000 | 24.46598 | 50.61506 | 0.30641 | 9.78532 |
Minimum of Months | 454.00000 | 24.09771 | 45.44481 | -0.0975 | 6.49582 |
Maximum of Months | 514.00000 | 24.72059 | 54.01367 | 0.72513 | 16.86862 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67992 | 46.20415 | 0.29213 | 7.33841 |
February | 454.00000 | 23.91558 | 49.27725 | 0.38810 | 8.62238 |
March | 514.00000 | 24.10111 | 47.13709 | 0.44409 | 9.49434 |
April | 485.00000 | 24.37256 | 50.56692 | 0.56608 | 12.21035 |
May | 508.00000 | 24.57281 | 52.24981 | -0.1331 | 6.71370 |
June | 496.00000 | 24.56507 | 55.78152 | -0.0844 | 6.57402 |
July | 497.00000 | 24.69617 | 55.29431 | -0.0302 | 6.73773 |
August | 514.00000 | 24.55951 | 56.30273 | -0.0676 | 6.46647 |
September | 485.00000 | 24.59995 | 56.73031 | -0.0903 | 6.73227 |
October | 502.00000 | 24.55306 | 54.62453 | 0.66091 | 14.87065 |
November | 489.00000 | 24.33108 | 52.86087 | 0.55460 | 11.72340 |
December | 497.00000 | 23.91745 | 50.13085 | 0.39223 | 8.69255 |
Annual Sum or Average | 5943.00000 | 24.32441 | 52.27173 | 0.23902 | 8.83853 |
Minimum of Months | 454.00000 | 23.67992 | 46.20415 | -0.1331 | 6.46647 |
Maximum of Months | 514.00000 | 24.69617 | 56.73031 | 0.66091 | 14.87065 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.89139 | 45.30027 | 0.34937 | 8.25264 |
February | 385.00000 | 24.10116 | 48.54311 | 0.44028 | 9.73122 |
March | 433.00000 | 24.23737 | 46.42439 | 0.48509 | 10.51992 |
April | 410.00000 | 24.55325 | 49.96797 | 0.62692 | 14.11305 |
May | 430.00000 | 24.72455 | 51.83663 | -0.0502 | 6.91409 |
June | 418.00000 | 24.69541 | 55.57246 | -0.0161 | 6.84550 |
July | 422.00000 | 24.85500 | 54.81714 | 0.04724 | 7.32475 |
August | 433.00000 | 24.69320 | 55.97261 | 0.00739 | 6.78400 |
September | 410.00000 | 24.76139 | 56.29615 | -0.0056 | 7.13373 |
October | 427.00000 | 24.73360 | 53.99471 | 0.72259 | 16.97726 |
November | 417.00000 | 24.54374 | 51.74547 | 0.61312 | 13.48110 |
December | 422.00000 | 24.09072 | 49.42986 | 0.43946 | 9.65661 |
Annual Sum or Average | 5034.00000 | 24.49182 | 51.66535 | 0.30353 | 9.80248 |
Minimum of Months | 385.00000 | 23.89139 | 45.30027 | -0.0502 | 6.78400 |
Maximum of Months | 433.00000 | 24.85500 | 56.29615 | 0.72259 | 16.97726 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.09876 | 43.98814 | 0.43051 | 9.95058 |
February | 454.00000 | 24.17105 | 47.70251 | 0.48875 | 10.85458 |
March | 514.00000 | 24.21210 | 46.34323 | 0.50130 | 10.85996 |
April | 485.00000 | 24.41538 | 50.27451 | 0.59223 | 12.98606 |
May | 508.00000 | 24.56614 | 52.27452 | -0.1345 | 6.72087 |
June | 496.00000 | 24.55216 | 55.89270 | -0.0989 | 6.58713 |
July | 497.00000 | 24.68820 | 55.34202 | -0.0358 | 6.72929 |
August | 514.00000 | 24.56439 | 56.18949 | -0.0512 | 6.47361 |
September | 485.00000 | 24.63347 | 56.31090 | -0.0347 | 6.81255 |
October | 502.00000 | 24.63865 | 53.80388 | 0.73231 | 17.20489 |
November | 489.00000 | 24.51822 | 51.64023 | 0.65654 | 14.79751 |
December | 497.00000 | 24.25439 | 48.15666 | 0.51688 | 11.60821 |
Annual Sum or Average | 5943.00000 | 24.44405 | 51.50823 | 0.29448 | 10.11323 |
Minimum of Months | 454.00000 | 24.09876 | 43.98814 | -0.1345 | 6.47361 |
Maximum of Months | 514.00000 | 24.68820 | 56.31090 | 0.73231 | 17.20489 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.83485 | 45.86688 | 0.34354 | 8.26383 |
February | 454.00000 | 24.03411 | 48.94231 | 0.43571 | 9.63105 |
March | 514.00000 | 24.18368 | 46.86426 | 0.48906 | 10.57064 |
April | 485.00000 | 24.43865 | 50.41343 | 0.60926 | 13.50784 |
May | 508.00000 | 24.60665 | 52.20249 | -0.0801 | 6.79501 |
June | 496.00000 | 24.59309 | 55.71021 | -0.0351 | 6.70312 |
July | 497.00000 | 24.72424 | 55.20682 | 0.01849 | 7.00081 |
August | 514.00000 | 24.59056 | 56.17223 | -0.0115 | 6.63602 |
September | 485.00000 | 24.64598 | 56.52429 | -0.0290 | 6.91764 |
October | 502.00000 | 24.60753 | 54.50363 | 0.70373 | 16.26016 |
November | 489.00000 | 24.41394 | 52.64002 | 0.59875 | 13.02898 |
December | 497.00000 | 24.04299 | 49.82536 | 0.43844 | 9.70926 |
Annual Sum or Average | 5943.00000 | 24.39503 | 52.08219 | 0.28810 | 9.57207 |
Minimum of Months | 454.00000 | 23.83485 | 45.86688 | -0.0801 | 6.63602 |
Maximum of Months | 514.00000 | 24.72424 | 56.52429 | 0.70373 | 16.26016 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.328199E+11 | 0.781340E+10 | 405.28 | 0.272147E+11 | 0.560518E+10 | 0.00 | 1.00 | 23-JAN-12:50 | 0.00 | 01-JAN-00:10 | 50334.94 | 30-JAN-14:00 | 44024.75 | 23-JAN-14:00 | 13948.91 | 30-JAN-14:00 | 11017.91 | 30-JAN-14:00 | 0.00 |
February | 0.363245E+11 | 0.865423E+10 | 367.89 | 0.298406E+11 | 0.648390E+10 | 0.00 | 1.00 | 05-FEB-14:43 | 0.00 | 01-FEB-00:10 | 68225.60 | 07-FEB-13:03 | 56807.27 | 06-FEB-15:00 | 18210.71 | 06-FEB-12:10 | 17509.12 | 07-FEB-13:03 | 0.00 |
March | 0.497652E+11 | 0.121937E+11 | 433.72 | 0.427318E+11 | 0.703337E+10 | 0.00 | 1.00 | 01-MAR-09:50 | 0.00 | 01-MAR-00:10 | 74447.21 | 28-MAR-11:40 | 71968.47 | 02-MAR-06:03 | 23434.09 | 28-MAR-11:40 | 21591.22 | 27-MAR-12:09 | 0.00 |
April | 0.614728E+11 | 0.157282E+11 | 425.50 | 0.517436E+11 | 0.972918E+10 | 0.00 | 1.00 | 02-APR-14:43 | 0.00 | 01-APR-00:10 | 82647.51 | 10-APR-12:00 | 72315.57 | 28-APR-12:02 | 31136.30 | 10-APR-12:00 | 25971.70 | 28-APR-12:00 | 0.00 |
May | 0.964544E+11 | 0.265747E+11 | 491.21 | 0.786581E+11 | 0.177963E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 131472.12 | 24-MAY-05:03 | 89186.08 | 22-MAY-06:03 | 60403.17 | 24-MAY-05:03 | 34020.69 | 31-MAY-12:02 | 0.00 |
June | 0.119340E+12 | 0.330238E+11 | 499.96 | 0.857392E+11 | 0.336010E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:05 | 134272.12 | 14-JUN-04:03 | 87459.22 | 01-JUN-04:02 | 65904.63 | 14-JUN-04:03 | 35785.72 | 12-JUN-12:02 | 0.00 |
July | 0.147690E+12 | 0.414815E+11 | 569.11 | 0.965371E+11 | 0.511528E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 133452.63 | 06-JUL-04:02 | 93530.54 | 30-JUL-13:22 | 67572.42 | 05-JUL-04:02 | 38696.36 | 30-JUL-14:41 | 0.00 |
August | 0.165192E+12 | 0.464937E+11 | 600.03 | 0.105592E+12 | 0.596000E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:35 | 134033.22 | 21-AUG-04:12 | 94227.85 | 07-AUG-05:03 | 70863.53 | 21-AUG-04:12 | 39284.78 | 10-AUG-12:12 | 0.00 |
September | 0.130460E+12 | 0.350317E+11 | 517.54 | 0.861208E+11 | 0.443392E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:35 | 133189.55 | 28-SEP-04:02 | 89513.99 | 04-SEP-14:31 | 64354.85 | 10-SEP-12:02 | 37527.72 | 04-SEP-13:51 | 0.00 |
October | 0.102790E+12 | 0.264512E+11 | 497.44 | 0.756228E+11 | 0.271670E+11 | 0.00 | 1.00 | 01-OCT-07:37 | 0.00 | 01-OCT-00:10 | 131755.13 | 08-OCT-11:52 | 85544.99 | 11-OCT-04:02 | 61086.63 | 08-OCT-11:52 | 33478.76 | 08-OCT-11:52 | 0.00 |
November | 0.715328E+11 | 0.174232E+11 | 430.75 | 0.566164E+11 | 0.149164E+11 | 0.00 | 1.00 | 01-NOV-04:43 | 0.00 | 01-NOV-00:10 | 128246.73 | 02-NOV-06:03 | 84778.53 | 20-NOV-05:02 | 50631.66 | 02-NOV-06:03 | 27944.94 | 02-NOV-06:03 | 0.00 |
December | 0.437871E+11 | 0.102769E+11 | 408.22 | 0.353894E+11 | 0.839763E+10 | 0.00 | 1.00 | 01-DEC-10:20 | 0.00 | 01-DEC-00:10 | 77765.33 | 11-DEC-07:03 | 57549.59 | 11-DEC-07:03 | 25626.98 | 05-DEC-12:40 | 17067.43 | 04-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.105763E+13 | 0.281146E+12 | 5646.66 | 0.771807E+12 | 0.285822E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.328199E+11 | 0.781340E+10 | 367.89 | 0.272147E+11 | 0.560518E+10 | 0.00 | 1.00 | 0.00 | 50334.94 | 44024.75 | 13948.91 | 11017.91 | 0.00 | ||||||
Maximum of Months | 0.165192E+12 | 0.464937E+11 | 600.03 | 0.105592E+12 | 0.596000E+11 | 0.00 | 1.00 | 0.00 | 134272.12 | 94227.85 | 70863.53 | 39284.78 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.266295E+11 | 0.645841E+10 | 401.06 | 0.208622E+11 | 0.576727E+10 | 0.00 | 1.00 | 30-JAN-13:50 | 0.00 | 01-JAN-00:10 | 41031.43 | 30-JAN-14:00 | 36886.53 | 23-JAN-13:30 | 13014.57 | 30-JAN-15:10 | 8983.76 | 30-JAN-14:00 | 0.00 |
February | 0.310569E+11 | 0.750293E+10 | 368.61 | 0.246390E+11 | 0.641784E+10 | 0.00 | 1.00 | 06-FEB-07:03 | 0.00 | 01-FEB-00:10 | 62377.41 | 07-FEB-15:05 | 54916.80 | 06-FEB-15:05 | 17388.29 | 07-FEB-16:00 | 14788.15 | 06-FEB-15:05 | 0.00 |
March | 0.445871E+11 | 0.110102E+11 | 437.72 | 0.376684E+11 | 0.691871E+10 | 0.00 | 1.00 | 01-MAR-10:40 | 0.00 | 01-MAR-00:10 | 65772.91 | 27-MAR-12:01 | 65772.91 | 27-MAR-12:01 | 15684.79 | 31-MAR-18:00 | 20951.34 | 27-MAR-11:00 | 0.00 |
April | 0.569783E+11 | 0.145852E+11 | 432.14 | 0.477065E+11 | 0.927178E+10 | 0.00 | 1.00 | 01-APR-14:05 | 0.00 | 01-APR-00:10 | 118456.78 | 30-APR-16:42 | 68998.92 | 28-APR-12:02 | 53077.57 | 30-APR-16:42 | 28279.69 | 30-APR-16:42 | 0.00 |
May | 0.892344E+11 | 0.244563E+11 | 497.93 | 0.733260E+11 | 0.159084E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 126848.65 | 24-MAY-05:03 | 87199.05 | 21-MAY-13:02 | 61548.94 | 24-MAY-05:03 | 32518.72 | 31-MAY-12:01 | 0.00 |
June | 0.110075E+12 | 0.302478E+11 | 503.84 | 0.792172E+11 | 0.308577E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:05 | 129435.66 | 14-JUN-04:03 | 82669.60 | 01-JUN-04:02 | 65712.36 | 14-JUN-04:03 | 35800.92 | 12-JUN-12:01 | 0.00 |
July | 0.133644E+12 | 0.373851E+11 | 561.41 | 0.887841E+11 | 0.448598E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 128593.73 | 06-JUL-04:02 | 92767.63 | 30-JUL-14:12 | 63096.67 | 06-JUL-04:02 | 38033.72 | 30-JUL-14:12 | 0.00 |
August | 0.143883E+12 | 0.404070E+11 | 573.64 | 0.943748E+11 | 0.495080E+11 | 0.00 | 1.00 | 01-AUG-00:20 | 0.00 | 01-AUG-00:05 | 128084.32 | 09-AUG-04:02 | 89084.36 | 07-AUG-05:03 | 62578.44 | 08-AUG-05:03 | 38938.86 | 16-AUG-12:01 | 0.00 |
September | 0.111948E+12 | 0.299501E+11 | 491.60 | 0.750273E+11 | 0.369202E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:05 | 128800.84 | 28-SEP-04:02 | 91167.54 | 04-SEP-16:31 | 63811.29 | 10-SEP-13:23 | 36568.19 | 04-SEP-14:31 | 0.00 |
October | 0.859416E+11 | 0.220843E+11 | 471.92 | 0.640047E+11 | 0.219369E+11 | 0.00 | 1.00 | 01-OCT-07:15 | 0.00 | 01-OCT-00:10 | 126117.47 | 02-OCT-04:02 | 80884.69 | 16-OCT-04:02 | 57533.41 | 06-OCT-04:02 | 29991.32 | 01-OCT-13:52 | 0.00 |
November | 0.579254E+11 | 0.141803E+11 | 416.11 | 0.452192E+11 | 0.127062E+11 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 90333.11 | 02-NOV-06:03 | 68755.55 | 20-NOV-07:03 | 37627.50 | 02-NOV-06:03 | 22807.26 | 01-NOV-12:02 | 0.00 |
December | 0.354831E+11 | 0.848595E+10 | 404.08 | 0.271505E+11 | 0.833262E+10 | 0.00 | 1.00 | 01-DEC-11:50 | 0.00 | 01-DEC-00:10 | 60424.29 | 05-DEC-15:05 | 46144.25 | 04-DEC-13:05 | 19757.76 | 05-DEC-15:05 | 13687.01 | 05-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.927386E+12 | 0.246754E+12 | 5560.07 | 0.677980E+12 | 0.249405E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.266295E+11 | 0.645841E+10 | 368.61 | 0.208622E+11 | 0.576727E+10 | 0.00 | 1.00 | 0.00 | 41031.43 | 36886.53 | 13014.57 | 8983.76 | 0.00 | ||||||
Maximum of Months | 0.143883E+12 | 0.404070E+11 | 573.64 | 0.943748E+11 | 0.495080E+11 | 0.00 | 1.00 | 0.00 | 129435.66 | 92767.63 | 65712.36 | 38938.86 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.265097E+11 | 0.651233E+10 | 399.00 | 0.199888E+11 | 0.652088E+10 | 0.00 | 0.94 | 30-JAN-14:10 | 0.00 | 01-JAN-00:10 | 42597.39 | 30-JAN-14:10 | 39615.96 | 23-JAN-14:00 | 13622.50 | 30-JAN-15:00 | 9760.64 | 23-JAN-14:00 | 0.00 |
February | 0.319087E+11 | 0.780013E+10 | 368.00 | 0.248222E+11 | 0.708655E+10 | 0.00 | 1.00 | 05-FEB-12:53 | 0.00 | 01-FEB-00:10 | 66061.17 | 07-FEB-15:30 | 62961.74 | 05-FEB-15:32 | 17235.00 | 07-FEB-16:00 | 16762.79 | 05-FEB-15:32 | 0.00 |
March | 0.471310E+11 | 0.117600E+11 | 437.64 | 0.393394E+11 | 0.779159E+10 | 0.00 | 1.00 | 01-MAR-11:00 | 0.00 | 01-MAR-00:10 | 72924.80 | 27-MAR-13:10 | 72924.80 | 27-MAR-13:10 | 16613.40 | 31-MAR-18:00 | 22680.08 | 27-MAR-12:03 | 0.00 |
April | 0.617763E+11 | 0.159694E+11 | 435.33 | 0.515693E+11 | 0.102070E+11 | 0.00 | 1.00 | 01-APR-14:20 | 0.00 | 01-APR-00:10 | 95540.54 | 30-APR-12:13 | 85700.34 | 30-APR-12:13 | 34005.98 | 30-APR-14:53 | 28021.74 | 30-APR-12:13 | 0.00 |
May | 0.980308E+11 | 0.270437E+11 | 506.63 | 0.809918E+11 | 0.170390E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 143522.89 | 31-MAY-04:02 | 104211.22 | 21-MAY-13:02 | 69411.33 | 24-MAY-05:03 | 36325.06 | 29-MAY-14:42 | 0.00 |
June | 0.120377E+12 | 0.332657E+11 | 514.04 | 0.881497E+11 | 0.322269E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:05 | 148835.31 | 14-JUN-04:03 | 96115.85 | 01-JUN-04:02 | 79247.62 | 20-JUN-04:03 | 38842.18 | 04-JUN-14:22 | 0.00 |
July | 0.148103E+12 | 0.415782E+11 | 587.49 | 0.100226E+12 | 0.478765E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 147867.19 | 06-JUL-04:02 | 114891.80 | 30-JUL-13:22 | 71053.75 | 06-JUL-04:02 | 44392.57 | 30-JUL-14:01 | 0.00 |
August | 0.157873E+12 | 0.444869E+11 | 597.34 | 0.105742E+12 | 0.521303E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:35 | 146847.05 | 26-AUG-04:02 | 105520.34 | 06-AUG-15:02 | 68705.19 | 26-AUG-04:02 | 41909.09 | 06-AUG-15:02 | 0.00 |
September | 0.120538E+12 | 0.323977E+11 | 503.71 | 0.821269E+11 | 0.384109E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:05 | 148601.65 | 28-SEP-04:02 | 108585.39 | 04-SEP-16:02 | 74537.14 | 28-SEP-04:02 | 42049.95 | 04-SEP-14:42 | 0.00 |
October | 0.905330E+11 | 0.234488E+11 | 470.25 | 0.678711E+11 | 0.226618E+11 | 0.00 | 1.00 | 01-OCT-08:33 | 0.00 | 01-OCT-00:10 | 143808.74 | 02-OCT-04:02 | 97063.40 | 09-OCT-14:42 | 65228.95 | 06-OCT-04:02 | 35190.01 | 01-OCT-13:52 | 0.00 |
November | 0.596737E+11 | 0.147712E+11 | 415.61 | 0.460841E+11 | 0.135896E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 89716.48 | 01-NOV-14:00 | 67223.81 | 20-NOV-06:03 | 34307.75 | 03-NOV-05:03 | 23376.14 | 01-NOV-14:00 | 0.00 |
December | 0.357167E+11 | 0.867072E+10 | 403.64 | 0.264754E+11 | 0.924136E+10 | 0.00 | 1.00 | 01-DEC-13:20 | 0.00 | 01-DEC-00:10 | 61498.17 | 05-DEC-15:00 | 47330.56 | 04-DEC-14:05 | 19367.16 | 05-DEC-15:00 | 13895.22 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.998170E+12 | 0.267705E+12 | 5638.69 | 0.733388E+12 | 0.264783E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.265097E+11 | 0.651233E+10 | 368.00 | 0.199888E+11 | 0.652088E+10 | 0.00 | 0.94 | 0.00 | 42597.39 | 39615.96 | 13622.50 | 9760.64 | 0.00 | ||||||
Maximum of Months | 0.157873E+12 | 0.444869E+11 | 597.34 | 0.105742E+12 | 0.521303E+11 | 0.00 | 1.00 | 0.00 | 148835.31 | 114891.80 | 79247.62 | 44392.57 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.55 | 0.00 | 315.55 | 369.72 | 671.15 | 0.00 | 0.00 | 0.00 |
February | 361.71 | 0.00 | 361.71 | 504.66 | 565.46 | 0.00 | 0.00 | 0.00 |
March | 415.47 | 0.00 | 415.47 | 722.94 | 432.50 | 0.00 | 0.00 | 0.00 |
April | 468.10 | 0.96 | 467.13 | 1045.39 | 274.21 | 0.00 | 0.00 | 0.00 |
May | 526.89 | 15.45 | 511.43 | 1588.52 | 70.51 | 0.00 | 0.00 | 0.00 |
June | 564.13 | 31.32 | 532.81 | 1838.05 | 18.26 | 0.00 | 0.00 | 0.00 |
July | 517.65 | 14.91 | 502.73 | 2054.91 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 481.88 | 3.99 | 477.90 | 2027.68 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 438.95 | 0.05 | 438.90 | 1522.10 | 26.12 | 0.00 | 0.00 | 0.00 |
October | 389.12 | 0.00 | 389.12 | 1088.72 | 115.58 | 0.00 | 0.00 | 0.00 |
November | 334.05 | 0.00 | 334.05 | 691.38 | 312.79 | 0.00 | 0.00 | 0.00 |
December | 294.52 | 0.00 | 294.52 | 412.16 | 551.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.91 | 5.58 | 420.34 | 1159.57 | 251.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 294.52 | 0.00 | 294.52 | 369.72 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 564.13 | 31.32 | 532.81 | 2054.91 | 671.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.55 | 115.13 | 265.41 | 529.37 | 424.24 | 0.00 | 0.00 | 0.00 |
February | 414.71 | 112.39 | 302.32 | 637.55 | 360.27 | 0.00 | 0.00 | 0.00 |
March | 458.09 | 112.90 | 345.19 | 810.71 | 277.29 | 0.00 | 0.00 | 0.00 |
April | 557.74 | 162.51 | 395.23 | 1157.12 | 177.43 | 0.00 | 0.00 | 0.00 |
May | 623.29 | 198.58 | 424.71 | 1566.28 | 44.99 | 0.00 | 0.00 | 0.00 |
June | 610.42 | 186.67 | 423.75 | 1655.73 | 10.91 | 0.00 | 0.00 | 0.00 |
July | 569.73 | 164.25 | 405.48 | 1790.78 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 583.40 | 179.05 | 404.34 | 1851.30 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 548.46 | 169.52 | 378.94 | 1498.15 | 15.69 | 0.00 | 0.00 | 0.00 |
October | 497.67 | 162.59 | 335.08 | 1171.03 | 71.38 | 0.00 | 0.00 | 0.00 |
November | 417.05 | 132.10 | 284.95 | 812.53 | 198.80 | 0.00 | 0.00 | 0.00 |
December | 337.56 | 92.61 | 244.95 | 516.45 | 351.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 500.22 | 149.18 | 351.04 | 1169.51 | 160.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.56 | 92.61 | 244.95 | 516.45 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.29 | 198.58 | 424.71 | 1851.30 | 424.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1019.82 | 479.46 | 540.35 | 1624.82 | 658.59 | 0.00 | 0.00 | 0.00 |
February | 957.65 | 391.72 | 565.93 | 1620.60 | 565.96 | 0.00 | 0.00 | 0.00 |
March | 788.19 | 213.99 | 574.20 | 1492.60 | 442.28 | 0.00 | 0.00 | 0.00 |
April | 619.58 | 65.69 | 553.89 | 1392.71 | 280.65 | 0.00 | 0.00 | 0.00 |
May | 524.83 | 8.04 | 516.80 | 1583.76 | 71.03 | 0.00 | 0.00 | 0.00 |
June | 494.27 | 0.61 | 493.66 | 1685.40 | 14.70 | 0.00 | 0.00 | 0.00 |
July | 494.26 | 4.20 | 490.06 | 1992.18 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 573.30 | 40.62 | 532.68 | 2234.62 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 755.91 | 173.24 | 582.67 | 2203.28 | 26.11 | 0.00 | 0.00 | 0.00 |
October | 989.63 | 393.43 | 596.20 | 2284.71 | 115.69 | 0.00 | 0.00 | 0.00 |
November | 1091.76 | 526.31 | 565.45 | 2121.51 | 314.30 | 0.00 | 0.00 | 0.00 |
December | 1013.48 | 500.63 | 512.85 | 1720.20 | 550.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.80 | 232.32 | 543.49 | 1831.19 | 251.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.26 | 0.61 | 490.06 | 1392.71 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.76 | 526.31 | 596.20 | 2284.71 | 658.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 373.20 | 107.19 | 266.01 | 542.85 | 452.81 | 0.00 | 0.00 | 0.00 |
February | 426.15 | 121.52 | 304.63 | 679.87 | 382.11 | 0.00 | 0.00 | 0.00 |
March | 504.79 | 149.44 | 355.35 | 909.21 | 296.75 | 0.00 | 0.00 | 0.00 |
April | 551.65 | 154.98 | 396.67 | 1150.01 | 193.58 | 0.00 | 0.00 | 0.00 |
May | 600.47 | 179.74 | 420.72 | 1529.33 | 52.80 | 0.00 | 0.00 | 0.00 |
June | 620.53 | 195.61 | 424.92 | 1680.50 | 12.72 | 0.00 | 0.00 | 0.00 |
July | 569.27 | 162.86 | 406.41 | 1785.41 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 177.56 | 406.45 | 1840.80 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 555.54 | 174.54 | 381.01 | 1509.50 | 19.59 | 0.00 | 0.00 | 0.00 |
October | 493.72 | 159.48 | 334.23 | 1170.09 | 83.45 | 0.00 | 0.00 | 0.00 |
November | 424.29 | 138.76 | 285.53 | 846.50 | 216.78 | 0.00 | 0.00 | 0.00 |
December | 355.19 | 107.37 | 247.83 | 573.83 | 375.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.19 | 152.53 | 352.66 | 1187.75 | 172.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.19 | 107.19 | 247.83 | 542.85 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.53 | 195.61 | 424.92 | 1840.80 | 452.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 117.27 | 252.94 | 0.00 | 0.00 | 0.00 |
February | 120.56 | 0.00 | 120.56 | 166.42 | 205.70 | 0.00 | 0.00 | 0.00 |
March | 138.48 | 0.00 | 138.48 | 243.69 | 150.21 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.70 | 354.72 | 90.32 | 0.00 | 0.00 | 0.00 |
May | 175.62 | 5.15 | 170.47 | 535.64 | 21.92 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 616.39 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 172.54 | 4.97 | 167.57 | 686.74 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 160.62 | 1.33 | 159.29 | 672.64 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.31 | 0.02 | 146.29 | 502.60 | 10.02 | 0.00 | 0.00 | 0.00 |
October | 129.70 | 0.00 | 129.70 | 357.07 | 44.36 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 224.37 | 120.27 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 130.99 | 211.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.96 | 1.86 | 140.11 | 385.39 | 92.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 117.27 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 686.74 | 252.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 117.27 | 252.95 | 0.00 | 0.00 | 0.00 |
February | 120.57 | 0.00 | 120.57 | 166.43 | 205.71 | 0.00 | 0.00 | 0.00 |
March | 138.49 | 0.00 | 138.49 | 243.70 | 150.22 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.71 | 354.73 | 90.32 | 0.00 | 0.00 | 0.00 |
May | 175.63 | 5.15 | 170.48 | 535.67 | 21.92 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 616.42 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 172.55 | 4.97 | 167.58 | 686.78 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 160.63 | 1.33 | 159.30 | 672.68 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.32 | 0.02 | 146.30 | 502.63 | 10.02 | 0.00 | 0.00 | 0.00 |
October | 129.71 | 0.00 | 129.71 | 357.09 | 44.36 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 224.38 | 120.27 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 130.99 | 211.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.97 | 1.86 | 140.11 | 385.41 | 92.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 117.27 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 686.78 | 252.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 117.27 | 252.95 | 0.00 | 0.00 | 0.00 |
February | 120.57 | 0.00 | 120.57 | 166.43 | 205.71 | 0.00 | 0.00 | 0.00 |
March | 138.49 | 0.00 | 138.49 | 243.70 | 150.22 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.71 | 354.73 | 90.32 | 0.00 | 0.00 | 0.00 |
May | 175.63 | 5.15 | 170.48 | 535.67 | 21.92 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 616.42 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 172.55 | 4.97 | 167.58 | 686.78 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 160.63 | 1.33 | 159.30 | 672.68 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.32 | 0.02 | 146.30 | 502.63 | 10.02 | 0.00 | 0.00 | 0.00 |
October | 129.71 | 0.00 | 129.71 | 357.09 | 44.36 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 224.38 | 120.27 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 130.99 | 211.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.97 | 1.86 | 140.11 | 385.41 | 92.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 117.27 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 686.78 | 252.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 366.07 | 110.75 | 255.32 | 495.04 | 461.62 | 0.00 | 0.00 | 0.00 |
February | 398.93 | 108.11 | 290.82 | 609.33 | 380.62 | 0.00 | 0.00 | 0.00 |
March | 440.66 | 108.61 | 332.05 | 785.49 | 281.31 | 0.00 | 0.00 | 0.00 |
April | 536.52 | 156.32 | 380.20 | 1125.58 | 173.74 | 0.00 | 0.00 | 0.00 |
May | 599.58 | 191.03 | 408.55 | 1518.60 | 43.36 | 0.00 | 0.00 | 0.00 |
June | 587.19 | 179.57 | 407.62 | 1600.07 | 10.49 | 0.00 | 0.00 | 0.00 |
July | 548.05 | 158.00 | 390.05 | 1725.20 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 561.20 | 172.24 | 388.96 | 1773.58 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 527.59 | 163.07 | 364.52 | 1432.10 | 19.01 | 0.00 | 0.00 | 0.00 |
October | 478.74 | 156.40 | 322.33 | 1117.28 | 84.00 | 0.00 | 0.00 | 0.00 |
November | 401.18 | 127.07 | 274.11 | 770.72 | 224.49 | 0.00 | 0.00 | 0.00 |
December | 324.72 | 89.09 | 235.63 | 482.90 | 388.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.19 | 143.50 | 337.69 | 1122.62 | 171.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.72 | 89.09 | 235.63 | 482.90 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.58 | 191.03 | 408.55 | 1773.58 | 461.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.47 | 4.38 | 10.09 | 19.57 | 18.25 | 0.00 | 0.00 | 0.00 |
February | 15.77 | 4.27 | 11.50 | 24.09 | 15.05 | 0.00 | 0.00 | 0.00 |
March | 17.42 | 4.29 | 13.13 | 31.06 | 11.12 | 0.00 | 0.00 | 0.00 |
April | 21.21 | 6.18 | 15.03 | 44.50 | 6.87 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 7.55 | 16.15 | 60.04 | 1.71 | 0.00 | 0.00 | 0.00 |
June | 23.22 | 7.10 | 16.12 | 63.27 | 0.41 | 0.00 | 0.00 | 0.00 |
July | 21.67 | 6.25 | 15.42 | 68.21 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 22.19 | 6.81 | 15.38 | 70.13 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20.86 | 6.45 | 14.41 | 56.62 | 0.75 | 0.00 | 0.00 | 0.00 |
October | 18.93 | 6.18 | 12.74 | 44.18 | 3.32 | 0.00 | 0.00 | 0.00 |
November | 15.86 | 5.02 | 10.84 | 30.47 | 8.88 | 0.00 | 0.00 | 0.00 |
December | 12.84 | 3.52 | 9.32 | 19.09 | 15.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.03 | 5.67 | 13.35 | 44.39 | 6.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.84 | 3.52 | 9.32 | 19.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.71 | 7.55 | 16.15 | 70.13 | 18.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.93 | 159.82 | 180.12 | 539.53 | 249.24 | 0.00 | 0.00 | 0.00 |
February | 319.21 | 130.57 | 188.64 | 542.19 | 208.81 | 0.00 | 0.00 | 0.00 |
March | 262.73 | 71.33 | 191.40 | 501.97 | 155.63 | 0.00 | 0.00 | 0.00 |
April | 206.52 | 21.90 | 184.63 | 470.09 | 93.87 | 0.00 | 0.00 | 0.00 |
May | 174.94 | 2.68 | 172.26 | 530.01 | 22.96 | 0.00 | 0.00 | 0.00 |
June | 164.76 | 0.20 | 164.55 | 559.23 | 4.78 | 0.00 | 0.00 | 0.00 |
July | 164.75 | 1.40 | 163.35 | 659.20 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 191.10 | 13.54 | 177.56 | 732.21 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.97 | 57.74 | 194.22 | 723.55 | 11.31 | 0.00 | 0.00 | 0.00 |
October | 329.87 | 131.14 | 198.73 | 754.02 | 48.88 | 0.00 | 0.00 | 0.00 |
November | 363.91 | 175.43 | 188.48 | 703.45 | 125.67 | 0.00 | 0.00 | 0.00 |
December | 337.82 | 166.87 | 170.95 | 570.90 | 211.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.60 | 77.44 | 181.16 | 607.65 | 93.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.75 | 0.20 | 163.35 | 470.09 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.91 | 175.43 | 198.73 | 754.02 | 249.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.93 | 159.82 | 180.12 | 539.53 | 249.24 | 0.00 | 0.00 | 0.00 |
February | 319.21 | 130.57 | 188.64 | 542.19 | 208.81 | 0.00 | 0.00 | 0.00 |
March | 262.73 | 71.33 | 191.40 | 501.97 | 155.63 | 0.00 | 0.00 | 0.00 |
April | 206.52 | 21.90 | 184.63 | 470.09 | 93.87 | 0.00 | 0.00 | 0.00 |
May | 174.94 | 2.68 | 172.26 | 530.01 | 22.96 | 0.00 | 0.00 | 0.00 |
June | 164.76 | 0.20 | 164.55 | 559.23 | 4.78 | 0.00 | 0.00 | 0.00 |
July | 164.75 | 1.40 | 163.35 | 659.20 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 191.10 | 13.54 | 177.56 | 732.21 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.97 | 57.74 | 194.22 | 723.55 | 11.31 | 0.00 | 0.00 | 0.00 |
October | 329.87 | 131.14 | 198.73 | 754.02 | 48.88 | 0.00 | 0.00 | 0.00 |
November | 363.91 | 175.43 | 188.48 | 703.45 | 125.67 | 0.00 | 0.00 | 0.00 |
December | 337.82 | 166.87 | 170.95 | 570.90 | 211.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.60 | 77.44 | 181.16 | 607.65 | 93.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.75 | 0.20 | 163.35 | 470.09 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.91 | 175.43 | 198.73 | 754.02 | 249.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.91 | 159.81 | 180.10 | 539.50 | 249.22 | 0.00 | 0.00 | 0.00 |
February | 319.19 | 130.56 | 188.63 | 542.15 | 208.80 | 0.00 | 0.00 | 0.00 |
March | 262.71 | 71.32 | 191.39 | 501.94 | 155.62 | 0.00 | 0.00 | 0.00 |
April | 206.51 | 21.89 | 184.62 | 470.06 | 93.87 | 0.00 | 0.00 | 0.00 |
May | 174.93 | 2.68 | 172.25 | 529.98 | 22.96 | 0.00 | 0.00 | 0.00 |
June | 164.75 | 0.20 | 164.54 | 559.19 | 4.78 | 0.00 | 0.00 | 0.00 |
July | 164.74 | 1.40 | 163.34 | 659.16 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 191.09 | 13.54 | 177.55 | 732.16 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.95 | 57.74 | 194.21 | 723.51 | 11.31 | 0.00 | 0.00 | 0.00 |
October | 329.85 | 131.13 | 198.72 | 753.97 | 48.88 | 0.00 | 0.00 | 0.00 |
November | 363.89 | 175.42 | 188.47 | 703.41 | 125.66 | 0.00 | 0.00 | 0.00 |
December | 337.80 | 166.86 | 170.94 | 570.86 | 211.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.58 | 77.43 | 181.15 | 607.62 | 93.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.74 | 0.20 | 163.34 | 470.06 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.89 | 175.42 | 198.72 | 753.97 | 249.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 359.00 | 103.11 | 255.89 | 513.52 | 497.15 | 0.00 | 0.00 | 0.00 |
February | 409.94 | 116.90 | 293.04 | 653.65 | 406.60 | 0.00 | 0.00 | 0.00 |
March | 485.58 | 143.76 | 341.83 | 883.22 | 303.58 | 0.00 | 0.00 | 0.00 |
April | 530.66 | 149.09 | 381.57 | 1120.28 | 190.23 | 0.00 | 0.00 | 0.00 |
May | 577.62 | 172.90 | 404.72 | 1482.66 | 51.06 | 0.00 | 0.00 | 0.00 |
June | 596.92 | 188.17 | 408.76 | 1621.74 | 12.60 | 0.00 | 0.00 | 0.00 |
July | 547.61 | 156.66 | 390.95 | 1719.42 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 561.79 | 170.81 | 390.98 | 1763.96 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 534.41 | 167.89 | 366.51 | 1443.40 | 23.32 | 0.00 | 0.00 | 0.00 |
October | 474.93 | 153.42 | 321.52 | 1116.96 | 96.34 | 0.00 | 0.00 | 0.00 |
November | 408.14 | 133.48 | 274.67 | 805.81 | 245.46 | 0.00 | 0.00 | 0.00 |
December | 341.68 | 103.28 | 238.40 | 542.86 | 416.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.96 | 146.72 | 339.24 | 1141.75 | 185.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.68 | 103.11 | 238.40 | 513.52 | 0.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 596.92 | 188.17 | 408.76 | 1763.96 | 497.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 4.08 | 10.12 | 20.30 | 19.66 | 0.00 | 0.00 | 0.00 |
February | 16.21 | 4.62 | 11.59 | 25.84 | 16.08 | 0.00 | 0.00 | 0.00 |
March | 19.20 | 5.68 | 13.52 | 34.92 | 12.00 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 5.89 | 15.09 | 44.29 | 7.52 | 0.00 | 0.00 | 0.00 |
May | 22.84 | 6.84 | 16.00 | 58.62 | 2.02 | 0.00 | 0.00 | 0.00 |
June | 23.60 | 7.44 | 16.16 | 64.12 | 0.50 | 0.00 | 0.00 | 0.00 |
July | 21.65 | 6.19 | 15.46 | 67.98 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 22.21 | 6.75 | 15.46 | 69.75 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 21.13 | 6.64 | 14.49 | 57.07 | 0.92 | 0.00 | 0.00 | 0.00 |
October | 18.78 | 6.07 | 12.71 | 44.16 | 3.81 | 0.00 | 0.00 | 0.00 |
November | 16.14 | 5.28 | 10.86 | 31.86 | 9.71 | 0.00 | 0.00 | 0.00 |
December | 13.51 | 4.08 | 9.43 | 21.46 | 16.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.21 | 5.80 | 13.41 | 45.14 | 7.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.51 | 4.08 | 9.43 | 20.30 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.60 | 7.44 | 16.16 | 69.75 | 19.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.55 | 0.00 | 315.55 | 358.32 | 722.67 | 0.00 | 0.00 | 0.00 |
February | 361.71 | 0.00 | 361.71 | 498.69 | 602.22 | 0.00 | 0.00 | 0.00 |
March | 415.47 | 0.00 | 415.47 | 723.31 | 455.06 | 0.00 | 0.00 | 0.00 |
April | 468.10 | 0.96 | 467.13 | 1052.85 | 282.77 | 0.00 | 0.00 | 0.00 |
May | 526.89 | 15.45 | 511.43 | 1602.29 | 70.60 | 0.00 | 0.00 | 0.00 |
June | 564.13 | 31.32 | 532.81 | 1853.14 | 17.31 | 0.00 | 0.00 | 0.00 |
July | 517.65 | 14.91 | 502.73 | 2073.59 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 481.88 | 3.99 | 477.90 | 2044.76 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 438.95 | 0.05 | 438.90 | 1534.42 | 26.19 | 0.00 | 0.00 | 0.00 |
October | 389.12 | 0.00 | 389.12 | 1095.94 | 118.69 | 0.00 | 0.00 | 0.00 |
November | 334.05 | 0.00 | 334.05 | 691.26 | 330.97 | 0.00 | 0.00 | 0.00 |
December | 294.52 | 0.00 | 294.52 | 404.11 | 591.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.91 | 5.58 | 420.34 | 1165.17 | 266.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 294.52 | 0.00 | 294.52 | 358.32 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 564.13 | 31.32 | 532.81 | 2073.59 | 722.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.55 | 115.13 | 265.41 | 516.35 | 452.69 | 0.00 | 0.00 | 0.00 |
February | 414.71 | 112.39 | 302.32 | 628.93 | 381.26 | 0.00 | 0.00 | 0.00 |
March | 458.09 | 112.90 | 345.19 | 806.50 | 290.65 | 0.00 | 0.00 | 0.00 |
April | 557.74 | 162.51 | 395.23 | 1158.03 | 182.78 | 0.00 | 0.00 | 0.00 |
May | 623.29 | 198.58 | 424.71 | 1572.09 | 45.35 | 0.00 | 0.00 | 0.00 |
June | 610.42 | 186.67 | 423.75 | 1662.16 | 10.48 | 0.00 | 0.00 | 0.00 |
July | 569.73 | 164.25 | 405.48 | 1799.45 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 583.40 | 179.05 | 404.34 | 1858.71 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 548.46 | 169.52 | 378.94 | 1502.87 | 15.89 | 0.00 | 0.00 | 0.00 |
October | 497.67 | 162.59 | 335.08 | 1172.63 | 73.64 | 0.00 | 0.00 | 0.00 |
November | 417.05 | 132.10 | 284.95 | 808.61 | 209.61 | 0.00 | 0.00 | 0.00 |
December | 337.56 | 92.61 | 244.95 | 506.41 | 374.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 500.22 | 149.18 | 351.04 | 1169.19 | 168.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.56 | 92.61 | 244.95 | 506.41 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.29 | 198.58 | 424.71 | 1858.71 | 452.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1019.82 | 479.46 | 540.35 | 1614.76 | 701.51 | 0.00 | 0.00 | 0.00 |
February | 957.65 | 391.72 | 565.93 | 1617.31 | 598.76 | 0.00 | 0.00 | 0.00 |
March | 788.19 | 213.99 | 574.20 | 1495.09 | 463.95 | 0.00 | 0.00 | 0.00 |
April | 619.58 | 65.69 | 553.89 | 1400.89 | 289.59 | 0.00 | 0.00 | 0.00 |
May | 524.83 | 8.04 | 516.80 | 1598.03 | 71.63 | 0.00 | 0.00 | 0.00 |
June | 494.27 | 0.61 | 493.66 | 1700.31 | 14.14 | 0.00 | 0.00 | 0.00 |
July | 494.26 | 4.20 | 490.06 | 2011.34 | 0.22 | 0.00 | 0.00 | 0.00 |
August | 573.30 | 40.62 | 532.68 | 2252.50 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 755.91 | 173.24 | 582.67 | 2217.56 | 26.27 | 0.00 | 0.00 | 0.00 |
October | 989.63 | 393.43 | 596.20 | 2294.94 | 118.69 | 0.00 | 0.00 | 0.00 |
November | 1091.76 | 526.31 | 565.45 | 2124.09 | 330.49 | 0.00 | 0.00 | 0.00 |
December | 1013.48 | 500.63 | 512.85 | 1714.19 | 583.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.80 | 232.32 | 543.49 | 1838.29 | 264.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.26 | 0.61 | 490.06 | 1400.89 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.76 | 526.31 | 596.20 | 2294.94 | 701.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 373.20 | 107.19 | 266.01 | 536.83 | 486.10 | 0.00 | 0.00 | 0.00 |
February | 426.15 | 121.52 | 304.63 | 677.51 | 405.98 | 0.00 | 0.00 | 0.00 |
March | 504.79 | 149.44 | 355.35 | 911.17 | 311.56 | 0.00 | 0.00 | 0.00 |
April | 551.65 | 154.98 | 396.67 | 1156.11 | 199.58 | 0.00 | 0.00 | 0.00 |
May | 600.47 | 179.74 | 420.72 | 1539.53 | 53.11 | 0.00 | 0.00 | 0.00 |
June | 620.53 | 195.61 | 424.92 | 1691.24 | 12.21 | 0.00 | 0.00 | 0.00 |
July | 569.27 | 162.86 | 406.41 | 1798.56 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 177.56 | 406.45 | 1853.35 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 555.54 | 174.54 | 381.01 | 1518.67 | 19.56 | 0.00 | 0.00 | 0.00 |
October | 493.72 | 159.48 | 334.23 | 1175.95 | 85.45 | 0.00 | 0.00 | 0.00 |
November | 424.29 | 138.76 | 285.53 | 847.72 | 228.85 | 0.00 | 0.00 | 0.00 |
December | 355.19 | 107.37 | 247.83 | 570.06 | 400.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.19 | 152.53 | 352.66 | 1192.69 | 182.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.19 | 107.19 | 247.83 | 536.83 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.53 | 195.61 | 424.92 | 1853.35 | 486.10 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.990268E+09 | 0.179760E+10 |
February | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.122087E+10 | 0.136796E+10 |
March | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.193633E+10 | 0.115840E+10 |
April | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.270966E+10 | 0.710741E+09 |
May | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.425470E+10 | 0.188843E+09 |
June | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.476422E+10 | 47332653.53 |
July | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.550387E+10 | 1203284.75 |
August | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.543093E+10 | 197608.67 |
September | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.394529E+10 | 67707969.16 |
October | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.291604E+10 | 0.309556E+09 |
November | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.179205E+10 | 0.810755E+09 |
December | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.110393E+10 | 0.147656E+10 |
Annual Sum or Average | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.365682E+11 | 0.793687E+10 |
Minimum of Months | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.990268E+09 | 197608.67 |
Maximum of Months | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.550387E+10 | 0.179760E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.141786E+10 | 0.113629E+10 |
February | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.154237E+10 | 0.871562E+09 |
March | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.217141E+10 | 0.742694E+09 |
April | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.299924E+10 | 0.459893E+09 |
May | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.419513E+10 | 0.120500E+09 |
June | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.429166E+10 | 28288695.96 |
July | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.479642E+10 | 662142.42 |
August | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.495853E+10 | 73629.60 |
September | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.388319E+10 | 40670308.06 |
October | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.313650E+10 | 0.191197E+09 |
November | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.210609E+10 | 0.515297E+09 |
December | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.138326E+10 | 0.941919E+09 |
Annual Sum or Average | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.368817E+11 | 0.504904E+10 |
Minimum of Months | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.138326E+10 | 73629.60 |
Maximum of Months | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.495853E+10 | 0.113629E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.435193E+10 | 0.176398E+10 |
February | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.392055E+10 | 0.136918E+10 |
March | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.399779E+10 | 0.118459E+10 |
April | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.360989E+10 | 0.727447E+09 |
May | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.424194E+10 | 0.190234E+09 |
June | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.436857E+10 | 38106312.69 |
July | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.533585E+10 | 649010.69 |
August | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.598520E+10 | 102887.28 |
September | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.571091E+10 | 67665865.98 |
October | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.611936E+10 | 0.309868E+09 |
November | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.549896E+10 | 0.814662E+09 |
December | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.460739E+10 | 0.147545E+10 |
Annual Sum or Average | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.577483E+11 | 0.794194E+10 |
Minimum of Months | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.360989E+10 | 102887.28 |
Maximum of Months | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.611936E+10 | 0.176398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.145396E+10 | 0.121280E+10 |
February | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.164474E+10 | 0.924402E+09 |
March | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.243524E+10 | 0.794821E+09 |
April | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.298082E+10 | 0.501760E+09 |
May | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.409617E+10 | 0.141409E+09 |
June | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.435585E+10 | 32965386.48 |
July | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.478203E+10 | 725407.84 |
August | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.493041E+10 | 205611.89 |
September | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.391263E+10 | 50774873.40 |
October | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.313396E+10 | 0.223500E+09 |
November | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.219412E+10 | 0.561899E+09 |
December | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.153694E+10 | 0.100469E+10 |
Annual Sum or Average | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.374569E+11 | 0.544995E+10 |
Minimum of Months | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.145396E+10 | 205611.89 |
Maximum of Months | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.493041E+10 | 0.121280E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281707E+09 | 0.00 | 0.281707E+09 | 0.314095E+09 | 0.677477E+09 |
February | 0.291667E+09 | 0.00 | 0.291667E+09 | 0.402603E+09 | 0.497630E+09 |
March | 0.370914E+09 | 0.00 | 0.370914E+09 | 0.652690E+09 | 0.402319E+09 |
April | 0.404418E+09 | 833282.96 | 0.403585E+09 | 0.919424E+09 | 0.234103E+09 |
May | 0.470382E+09 | 13796024.38 | 0.456586E+09 | 0.143465E+10 | 58704612.02 |
June | 0.487387E+09 | 27058259.84 | 0.460329E+09 | 0.159768E+10 | 13998930.28 |
July | 0.462133E+09 | 13315161.00 | 0.448818E+09 | 0.183937E+10 | 402885.09 |
August | 0.430206E+09 | 3558230.40 | 0.426648E+09 | 0.180161E+10 | 70232.68 |
September | 0.379237E+09 | 43457.08 | 0.379193E+09 | 0.130274E+10 | 25975343.50 |
October | 0.347392E+09 | 0.00 | 0.347392E+09 | 0.956377E+09 | 0.118812E+09 |
November | 0.288608E+09 | 0.00 | 0.288608E+09 | 0.581554E+09 | 0.311732E+09 |
December | 0.262937E+09 | 0.00 | 0.262937E+09 | 0.350838E+09 | 0.565485E+09 |
Annual Sum or Average | 0.447699E+10 | 58604415.66 | 0.441838E+10 | 0.121536E+11 | 0.290671E+10 |
Minimum of Months | 0.262937E+09 | 0.00 | 0.262937E+09 | 0.314095E+09 | 70232.68 |
Maximum of Months | 0.487387E+09 | 27058259.84 | 0.460329E+09 | 0.183937E+10 | 0.677477E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281718E+09 | 0.00 | 0.281718E+09 | 0.314105E+09 | 0.677514E+09 |
February | 0.291678E+09 | 0.00 | 0.291678E+09 | 0.402619E+09 | 0.497657E+09 |
March | 0.370928E+09 | 0.00 | 0.370928E+09 | 0.652719E+09 | 0.402339E+09 |
April | 0.404434E+09 | 833305.35 | 0.403601E+09 | 0.919469E+09 | 0.234113E+09 |
May | 0.470401E+09 | 13796395.22 | 0.456604E+09 | 0.143473E+10 | 58705791.41 |
June | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.159776E+10 | 13998577.47 |
July | 0.462151E+09 | 13315518.92 | 0.448835E+09 | 0.183947E+10 | 402834.88 |
August | 0.430223E+09 | 3558326.05 | 0.426665E+09 | 0.180171E+10 | 70211.27 |
September | 0.379252E+09 | 43458.25 | 0.379209E+09 | 0.130281E+10 | 25975527.10 |
October | 0.347405E+09 | 0.00 | 0.347405E+09 | 0.956429E+09 | 0.118815E+09 |
November | 0.288619E+09 | 0.00 | 0.288619E+09 | 0.581583E+09 | 0.311746E+09 |
December | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.350852E+09 | 0.565514E+09 |
Annual Sum or Average | 0.447716E+10 | 58605990.96 | 0.441856E+10 | 0.121543E+11 | 0.290685E+10 |
Minimum of Months | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.314105E+09 | 70211.27 |
Maximum of Months | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.183947E+10 | 0.677514E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281718E+09 | 0.00 | 0.281718E+09 | 0.314105E+09 | 0.677514E+09 |
February | 0.291678E+09 | 0.00 | 0.291678E+09 | 0.402619E+09 | 0.497657E+09 |
March | 0.370928E+09 | 0.00 | 0.370928E+09 | 0.652719E+09 | 0.402339E+09 |
April | 0.404434E+09 | 833305.35 | 0.403601E+09 | 0.919469E+09 | 0.234113E+09 |
May | 0.470401E+09 | 13796395.22 | 0.456604E+09 | 0.143473E+10 | 58705791.41 |
June | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.159776E+10 | 13998577.47 |
July | 0.462151E+09 | 13315518.92 | 0.448835E+09 | 0.183947E+10 | 402834.88 |
August | 0.430223E+09 | 3558326.05 | 0.426665E+09 | 0.180171E+10 | 70211.27 |
September | 0.379252E+09 | 43458.25 | 0.379209E+09 | 0.130281E+10 | 25975527.10 |
October | 0.347405E+09 | 0.00 | 0.347405E+09 | 0.956429E+09 | 0.118815E+09 |
November | 0.288619E+09 | 0.00 | 0.288619E+09 | 0.581583E+09 | 0.311746E+09 |
December | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.350852E+09 | 0.565514E+09 |
Annual Sum or Average | 0.447716E+10 | 58605990.96 | 0.441856E+10 | 0.121543E+11 | 0.290685E+10 |
Minimum of Months | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.314105E+09 | 70211.27 |
Maximum of Months | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.183947E+10 | 0.677514E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.980477E+09 | 0.296641E+09 | 0.683836E+09 | 0.132593E+10 | 0.123641E+10 |
February | 0.965092E+09 | 0.261544E+09 | 0.703548E+09 | 0.147410E+10 | 0.920785E+09 |
March | 0.118026E+10 | 0.290890E+09 | 0.889372E+09 | 0.210385E+10 | 0.753463E+09 |
April | 0.139066E+10 | 0.405192E+09 | 0.985471E+09 | 0.291750E+10 | 0.450323E+09 |
May | 0.160591E+10 | 0.511648E+09 | 0.109426E+10 | 0.406741E+10 | 0.116127E+09 |
June | 0.152201E+10 | 0.465444E+09 | 0.105656E+10 | 0.414739E+10 | 27181899.98 |
July | 0.146791E+10 | 0.423193E+09 | 0.104472E+10 | 0.462078E+10 | 836339.62 |
August | 0.150311E+10 | 0.461324E+09 | 0.104179E+10 | 0.475036E+10 | 159653.25 |
September | 0.136752E+10 | 0.422681E+09 | 0.944836E+09 | 0.371202E+10 | 49282003.30 |
October | 0.128225E+10 | 0.418909E+09 | 0.863339E+09 | 0.299253E+10 | 0.224995E+09 |
November | 0.103987E+10 | 0.329375E+09 | 0.710490E+09 | 0.199772E+10 | 0.581866E+09 |
December | 0.869726E+09 | 0.238617E+09 | 0.631110E+09 | 0.129339E+10 | 0.104010E+10 |
Annual Sum or Average | 0.151748E+11 | 0.452546E+10 | 0.106493E+11 | 0.354030E+11 | 0.540153E+10 |
Minimum of Months | 0.869726E+09 | 0.238617E+09 | 0.631110E+09 | 0.129339E+10 | 159653.25 |
Maximum of Months | 0.160591E+10 | 0.511648E+09 | 0.109426E+10 | 0.475036E+10 | 0.123641E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38767169.86 | 11728917.87 | 27038251.99 | 52425881.31 | 48886355.71 |
February | 38158864.13 | 10341197.48 | 27817666.66 | 58284470.76 | 36406993.01 |
March | 46666517.65 | 11501534.46 | 35164983.19 | 83184420.10 | 29791240.16 |
April | 54985543.05 | 16020907.39 | 38964635.67 | 0.115355E+09 | 17805371.69 |
May | 63496079.79 | 20230091.31 | 43265988.49 | 0.160822E+09 | 4591560.23 |
June | 60178723.78 | 18403232.06 | 41775491.72 | 0.163984E+09 | 1074747.85 |
July | 58039777.31 | 16732677.45 | 41307099.86 | 0.182702E+09 | 33068.12 |
August | 59431730.36 | 18240318.79 | 41191411.57 | 0.187825E+09 | 6312.55 |
September | 54070390.91 | 16712442.13 | 37357948.79 | 0.146770E+09 | 1948566.04 |
October | 50698923.30 | 16563295.94 | 34135627.36 | 0.118322E+09 | 8896118.03 |
November | 41115338.64 | 13023186.67 | 28092151.97 | 78987923.06 | 23006473.16 |
December | 34388199.46 | 9434693.58 | 24953505.89 | 51139356.13 | 41124755.45 |
Annual Sum or Average | 0.599997E+09 | 0.178932E+09 | 0.421065E+09 | 0.139980E+10 | 0.213572E+09 |
Minimum of Months | 34388199.46 | 9434693.58 | 24953505.89 | 51139356.13 | 6312.55 |
Maximum of Months | 63496079.79 | 20230091.31 | 43265988.49 | 0.187825E+09 | 48886355.71 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910476E+09 | 0.428054E+09 | 0.482421E+09 | 0.144508E+10 | 0.667559E+09 |
February | 0.772236E+09 | 0.315877E+09 | 0.456359E+09 | 0.131166E+10 | 0.505150E+09 |
March | 0.703685E+09 | 0.191046E+09 | 0.512640E+09 | 0.134448E+10 | 0.416849E+09 |
April | 0.535307E+09 | 56752191.30 | 0.478555E+09 | 0.121847E+10 | 0.243318E+09 |
May | 0.468568E+09 | 7175566.92 | 0.461393E+09 | 0.141959E+10 | 61507352.95 |
June | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.144952E+10 | 12390066.36 |
July | 0.441272E+09 | 3749415.45 | 0.437522E+09 | 0.176561E+10 | 248813.98 |
August | 0.511839E+09 | 36265474.26 | 0.475574E+09 | 0.196115E+10 | 106456.85 |
September | 0.653094E+09 | 0.149674E+09 | 0.503419E+09 | 0.187545E+10 | 29308140.70 |
October | 0.883526E+09 | 0.351250E+09 | 0.532276E+09 | 0.201956E+10 | 0.130927E+09 |
November | 0.943266E+09 | 0.454723E+09 | 0.488543E+09 | 0.182335E+10 | 0.325731E+09 |
December | 0.904824E+09 | 0.446954E+09 | 0.457870E+09 | 0.152909E+10 | 0.566836E+09 |
Annual Sum or Average | 0.815514E+10 | 0.244205E+10 | 0.571309E+10 | 0.191630E+11 | 0.295993E+10 |
Minimum of Months | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.121847E+10 | 106456.85 |
Maximum of Months | 0.943266E+09 | 0.454723E+09 | 0.532276E+09 | 0.201956E+10 | 0.667559E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910476E+09 | 0.428054E+09 | 0.482421E+09 | 0.144508E+10 | 0.667559E+09 |
February | 0.772236E+09 | 0.315877E+09 | 0.456359E+09 | 0.131166E+10 | 0.505150E+09 |
March | 0.703685E+09 | 0.191046E+09 | 0.512640E+09 | 0.134448E+10 | 0.416849E+09 |
April | 0.535307E+09 | 56752191.30 | 0.478555E+09 | 0.121847E+10 | 0.243318E+09 |
May | 0.468568E+09 | 7175566.92 | 0.461393E+09 | 0.141959E+10 | 61507352.95 |
June | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.144952E+10 | 12390066.36 |
July | 0.441272E+09 | 3749415.45 | 0.437522E+09 | 0.176561E+10 | 248813.98 |
August | 0.511839E+09 | 36265474.26 | 0.475574E+09 | 0.196115E+10 | 106456.85 |
September | 0.653094E+09 | 0.149674E+09 | 0.503419E+09 | 0.187545E+10 | 29308140.70 |
October | 0.883526E+09 | 0.351250E+09 | 0.532276E+09 | 0.201956E+10 | 0.130927E+09 |
November | 0.943266E+09 | 0.454723E+09 | 0.488543E+09 | 0.182335E+10 | 0.325731E+09 |
December | 0.904824E+09 | 0.446954E+09 | 0.457870E+09 | 0.152909E+10 | 0.566836E+09 |
Annual Sum or Average | 0.815514E+10 | 0.244205E+10 | 0.571309E+10 | 0.191630E+11 | 0.295993E+10 |
Minimum of Months | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.121847E+10 | 106456.85 |
Maximum of Months | 0.943266E+09 | 0.454723E+09 | 0.532276E+09 | 0.201956E+10 | 0.667559E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910418E+09 | 0.428027E+09 | 0.482391E+09 | 0.144499E+10 | 0.667517E+09 |
February | 0.772188E+09 | 0.315857E+09 | 0.456330E+09 | 0.131158E+10 | 0.505118E+09 |
March | 0.703641E+09 | 0.191033E+09 | 0.512607E+09 | 0.134439E+10 | 0.416823E+09 |
April | 0.535274E+09 | 56748604.88 | 0.478525E+09 | 0.121839E+10 | 0.243302E+09 |
May | 0.468539E+09 | 7175113.46 | 0.461363E+09 | 0.141950E+10 | 61503466.03 |
June | 0.427022E+09 | 528448.65 | 0.426494E+09 | 0.144943E+10 | 12389283.38 |
July | 0.441244E+09 | 3749178.51 | 0.437495E+09 | 0.176550E+10 | 248798.26 |
August | 0.511807E+09 | 36263182.48 | 0.475544E+09 | 0.196103E+10 | 106450.13 |
September | 0.653053E+09 | 0.149665E+09 | 0.503388E+09 | 0.187533E+10 | 29306288.59 |
October | 0.883470E+09 | 0.351228E+09 | 0.532243E+09 | 0.201943E+10 | 0.130919E+09 |
November | 0.943206E+09 | 0.454694E+09 | 0.488512E+09 | 0.182324E+10 | 0.325711E+09 |
December | 0.904767E+09 | 0.446926E+09 | 0.457841E+09 | 0.152900E+10 | 0.566801E+09 |
Annual Sum or Average | 0.815463E+10 | 0.244189E+10 | 0.571273E+10 | 0.191618E+11 | 0.295975E+10 |
Minimum of Months | 0.427022E+09 | 528448.65 | 0.426494E+09 | 0.121839E+10 | 106450.13 |
Maximum of Months | 0.943206E+09 | 0.454694E+09 | 0.532243E+09 | 0.201943E+10 | 0.667517E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.961538E+09 | 0.276161E+09 | 0.685377E+09 | 0.137540E+10 | 0.133156E+10 |
February | 0.991722E+09 | 0.282798E+09 | 0.708924E+09 | 0.158131E+10 | 0.983646E+09 |
March | 0.130059E+10 | 0.385041E+09 | 0.915547E+09 | 0.236562E+10 | 0.813108E+09 |
April | 0.137547E+10 | 0.386432E+09 | 0.989039E+09 | 0.290376E+10 | 0.493081E+09 |
May | 0.154710E+10 | 0.463108E+09 | 0.108399E+10 | 0.397116E+10 | 0.136769E+09 |
June | 0.154723E+10 | 0.487725E+09 | 0.105950E+10 | 0.420356E+10 | 32648700.62 |
July | 0.146673E+10 | 0.419600E+09 | 0.104713E+10 | 0.460530E+10 | 1052254.72 |
August | 0.150470E+10 | 0.457491E+09 | 0.104721E+10 | 0.472459E+10 | 344318.31 |
September | 0.138518E+10 | 0.435183E+09 | 0.950000E+09 | 0.374130E+10 | 60451693.45 |
October | 0.127205E+10 | 0.410907E+09 | 0.861147E+09 | 0.299167E+10 | 0.258034E+09 |
November | 0.105791E+10 | 0.345969E+09 | 0.711940E+09 | 0.208866E+10 | 0.636219E+09 |
December | 0.915157E+09 | 0.276635E+09 | 0.638522E+09 | 0.145399E+10 | 0.111652E+10 |
Annual Sum or Average | 0.153254E+11 | 0.462705E+10 | 0.106983E+11 | 0.360063E+11 | 0.586343E+10 |
Minimum of Months | 0.915157E+09 | 0.276161E+09 | 0.638522E+09 | 0.137540E+10 | 344318.31 |
Maximum of Months | 0.154723E+10 | 0.487725E+09 | 0.108399E+10 | 0.472459E+10 | 0.133156E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38018247.76 | 10919117.73 | 27099130.02 | 54381862.08 | 52648460.92 |
February | 39211705.00 | 11181551.15 | 28030153.85 | 62523478.37 | 38892458.13 |
March | 51423957.87 | 15224122.20 | 36199835.67 | 93534352.80 | 32149526.00 |
April | 54384761.88 | 15279138.20 | 39105623.68 | 0.114812E+09 | 19495924.53 |
May | 61170809.08 | 18310794.40 | 42860014.69 | 0.157016E+09 | 5407723.05 |
June | 61175738.81 | 19284136.55 | 41891602.26 | 0.166205E+09 | 1290891.04 |
July | 57992905.15 | 16590541.44 | 41402363.71 | 0.182089E+09 | 41604.24 |
August | 59494269.60 | 18088714.83 | 41405554.77 | 0.186806E+09 | 13613.70 |
September | 54768728.67 | 17206686.11 | 37562042.56 | 0.147927E+09 | 2390193.83 |
October | 50295743.05 | 16246847.94 | 34048895.11 | 0.118288E+09 | 10202383.83 |
November | 41828685.86 | 13679270.35 | 28149415.51 | 82583545.77 | 25155502.06 |
December | 36184378.39 | 10937853.43 | 25246524.96 | 57489385.39 | 44146341.79 |
Annual Sum or Average | 0.605950E+09 | 0.182949E+09 | 0.423001E+09 | 0.142365E+10 | 0.231835E+09 |
Minimum of Months | 36184378.39 | 10919117.73 | 25246524.96 | 54381862.08 | 13613.70 |
Maximum of Months | 61175738.81 | 19284136.55 | 42860014.69 | 0.186806E+09 | 52648460.92 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.959726E+09 | 0.193561E+10 |
February | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.120644E+10 | 0.145688E+10 |
March | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.193732E+10 | 0.121885E+10 |
April | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.272898E+10 | 0.732945E+09 |
May | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.429157E+10 | 0.189108E+09 |
June | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.480334E+10 | 44861816.52 |
July | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.555389E+10 | 1131592.45 |
August | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.547669E+10 | 147871.44 |
September | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.397723E+10 | 67883649.87 |
October | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.293537E+10 | 0.317904E+09 |
November | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.179175E+10 | 0.857872E+09 |
December | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.108237E+10 | 0.158304E+10 |
Annual Sum or Average | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.367447E+11 | 0.840623E+10 |
Minimum of Months | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.959726E+09 | 147871.44 |
Maximum of Months | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.555389E+10 | 0.193561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.138298E+10 | 0.121249E+10 |
February | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.152151E+10 | 0.922345E+09 |
March | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.216014E+10 | 0.778488E+09 |
April | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.300161E+10 | 0.473775E+09 |
May | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.421068E+10 | 0.121454E+09 |
June | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.430831E+10 | 27175809.55 |
July | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.481963E+10 | 638568.87 |
August | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.497836E+10 | 54492.28 |
September | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.389544E+10 | 41189279.51 |
October | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.314078E+10 | 0.197238E+09 |
November | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.209591E+10 | 0.543298E+09 |
December | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.135636E+10 | 0.100265E+10 |
Annual Sum or Average | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.368717E+11 | 0.532079E+10 |
Minimum of Months | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.135636E+10 | 54492.28 |
Maximum of Months | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.497836E+10 | 0.121249E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.432498E+10 | 0.187893E+10 |
February | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.391259E+10 | 0.144853E+10 |
March | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.400444E+10 | 0.124264E+10 |
April | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.363109E+10 | 0.750628E+09 |
May | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.428017E+10 | 0.191862E+09 |
June | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.440721E+10 | 36652742.12 |
July | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.538717E+10 | 598909.19 |
August | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.603310E+10 | 66951.36 |
September | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.574792E+10 | 68091423.31 |
October | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.614677E+10 | 0.317910E+09 |
November | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.550563E+10 | 0.856622E+09 |
December | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.459129E+10 | 0.156387E+10 |
Annual Sum or Average | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.579724E+11 | 0.835640E+10 |
Minimum of Months | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.363109E+10 | 66951.36 |
Maximum of Months | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.614677E+10 | 0.187893E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.143785E+10 | 0.130196E+10 |
February | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.163903E+10 | 0.982143E+09 |
March | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.244048E+10 | 0.834493E+09 |
April | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.299663E+10 | 0.517300E+09 |
May | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.412347E+10 | 0.142240E+09 |
June | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.438369E+10 | 31647767.97 |
July | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.481725E+10 | 689868.48 |
August | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.496402E+10 | 192494.29 |
September | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.393639E+10 | 50705474.94 |
October | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.314966E+10 | 0.228858E+09 |
November | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.219728E+10 | 0.593169E+09 |
December | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.152685E+10 | 0.107276E+10 |
Annual Sum or Average | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.376126E+11 | 0.575616E+10 |
Minimum of Months | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.143785E+10 | 192494.29 |
Maximum of Months | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.496402E+10 | 0.130196E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 369.72 | 671.15 | 315.55 | 0.00 | 315.55 | 0.00 | 0.00 |
February | 504.66 | 565.46 | 361.71 | 0.00 | 361.71 | 0.00 | 0.00 |
March | 722.94 | 432.50 | 415.47 | 0.00 | 415.47 | 0.00 | 0.00 |
April | 1045.39 | 274.21 | 468.10 | 0.96 | 467.13 | 0.00 | 0.00 |
May | 1588.52 | 70.51 | 526.89 | 15.45 | 511.43 | 0.00 | 0.00 |
June | 1838.05 | 18.26 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
July | 2054.91 | 0.45 | 517.65 | 14.91 | 502.73 | 0.00 | 0.00 |
August | 2027.68 | 0.07 | 481.88 | 3.99 | 477.90 | 0.00 | 0.00 |
September | 1522.10 | 26.12 | 438.95 | 0.05 | 438.90 | 0.00 | 0.00 |
October | 1088.72 | 115.58 | 389.12 | 0.00 | 389.12 | 0.00 | 0.00 |
November | 691.38 | 312.79 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 412.16 | 551.29 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1159.57 | 251.68 | 425.91 | 5.58 | 420.34 | 0.00 | 0.00 |
Minimum of Months | 369.72 | 0.07 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2054.91 | 671.15 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 529.37 | 424.24 | 380.55 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 637.55 | 360.27 | 414.71 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 810.71 | 277.29 | 458.09 | 112.90 | 345.19 | 0.00 | 0.00 |
April | 1157.12 | 177.43 | 557.74 | 162.51 | 395.23 | 0.00 | 0.00 |
May | 1566.28 | 44.99 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
June | 1655.73 | 10.91 | 610.42 | 186.67 | 423.75 | 0.00 | 0.00 |
July | 1790.78 | 0.25 | 569.73 | 164.25 | 405.48 | 0.00 | 0.00 |
August | 1851.30 | 0.03 | 583.40 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1498.15 | 15.69 | 548.46 | 169.52 | 378.94 | 0.00 | 0.00 |
October | 1171.03 | 71.38 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 812.53 | 198.80 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 516.45 | 351.67 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1169.51 | 160.10 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 516.45 | 0.03 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1851.30 | 424.24 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1624.82 | 658.59 | 1019.82 | 479.46 | 540.35 | 0.00 | 0.00 |
February | 1620.60 | 565.96 | 957.65 | 391.72 | 565.93 | 0.00 | 0.00 |
March | 1492.60 | 442.28 | 788.19 | 213.99 | 574.20 | 0.00 | 0.00 |
April | 1392.71 | 280.65 | 619.58 | 65.69 | 553.89 | 0.00 | 0.00 |
May | 1583.76 | 71.03 | 524.83 | 8.04 | 516.80 | 0.00 | 0.00 |
June | 1685.40 | 14.70 | 494.27 | 0.61 | 493.66 | 0.00 | 0.00 |
July | 1992.18 | 0.24 | 494.26 | 4.20 | 490.06 | 0.00 | 0.00 |
August | 2234.62 | 0.04 | 573.30 | 40.62 | 532.68 | 0.00 | 0.00 |
September | 2203.28 | 26.11 | 755.91 | 173.24 | 582.67 | 0.00 | 0.00 |
October | 2284.71 | 115.69 | 989.63 | 393.43 | 596.20 | 0.00 | 0.00 |
November | 2121.51 | 314.30 | 1091.76 | 526.31 | 565.45 | 0.00 | 0.00 |
December | 1720.20 | 550.87 | 1013.48 | 500.63 | 512.85 | 0.00 | 0.00 |
Annual Sum or Average | 1831.19 | 251.84 | 775.80 | 232.32 | 543.49 | 0.00 | 0.00 |
Minimum of Months | 1392.71 | 0.04 | 494.26 | 0.61 | 490.06 | 0.00 | 0.00 |
Maximum of Months | 2284.71 | 658.59 | 1091.76 | 526.31 | 596.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 542.85 | 452.81 | 373.20 | 107.19 | 266.01 | 0.00 | 0.00 |
February | 679.87 | 382.11 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 909.21 | 296.75 | 504.79 | 149.44 | 355.35 | 0.00 | 0.00 |
April | 1150.01 | 193.58 | 551.65 | 154.98 | 396.67 | 0.00 | 0.00 |
May | 1529.33 | 52.80 | 600.47 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1680.50 | 12.72 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1785.41 | 0.27 | 569.27 | 162.86 | 406.41 | 0.00 | 0.00 |
August | 1840.80 | 0.08 | 584.01 | 177.56 | 406.45 | 0.00 | 0.00 |
September | 1509.50 | 19.59 | 555.54 | 174.54 | 381.01 | 0.00 | 0.00 |
October | 1170.09 | 83.45 | 493.72 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 846.50 | 216.78 | 424.29 | 138.76 | 285.53 | 0.00 | 0.00 |
December | 573.83 | 375.11 | 355.19 | 107.37 | 247.83 | 0.00 | 0.00 |
Annual Sum or Average | 1187.75 | 172.82 | 505.19 | 152.53 | 352.66 | 0.00 | 0.00 |
Minimum of Months | 542.85 | 0.08 | 355.19 | 107.19 | 247.83 | 0.00 | 0.00 |
Maximum of Months | 1840.80 | 452.81 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 351.82 | 758.85 | 315.54 | 0.00 | 315.54 | 0.00 | 0.00 |
February | 499.27 | 617.12 | 361.70 | 0.00 | 361.70 | 0.00 | 0.00 |
March | 731.08 | 450.64 | 415.46 | 0.00 | 415.46 | 0.00 | 0.00 |
April | 1064.18 | 270.96 | 468.09 | 0.96 | 467.12 | 0.00 | 0.00 |
May | 1606.97 | 65.75 | 526.88 | 15.45 | 511.42 | 0.00 | 0.00 |
June | 1849.23 | 16.20 | 564.12 | 31.32 | 532.80 | 0.00 | 0.00 |
July | 2060.30 | 0.45 | 517.64 | 14.91 | 502.72 | 0.00 | 0.00 |
August | 2018.01 | 0.08 | 481.87 | 3.99 | 477.89 | 0.00 | 0.00 |
September | 1507.86 | 30.06 | 438.94 | 0.05 | 438.89 | 0.00 | 0.00 |
October | 1071.25 | 133.08 | 389.11 | 0.00 | 389.11 | 0.00 | 0.00 |
November | 673.12 | 360.81 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 392.97 | 633.41 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1156.21 | 276.52 | 425.90 | 5.58 | 420.33 | 0.00 | 0.00 |
Minimum of Months | 351.82 | 0.08 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2060.30 | 758.85 | 564.12 | 31.32 | 532.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 514.62 | 479.87 | 380.54 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 633.42 | 395.66 | 414.70 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 816.55 | 292.43 | 458.08 | 112.90 | 345.18 | 0.00 | 0.00 |
April | 1170.08 | 180.61 | 557.73 | 162.50 | 395.23 | 0.00 | 0.00 |
May | 1578.64 | 45.07 | 623.28 | 198.58 | 424.70 | 0.00 | 0.00 |
June | 1663.34 | 10.90 | 610.41 | 186.67 | 423.74 | 0.00 | 0.00 |
July | 1793.42 | 0.32 | 569.72 | 164.25 | 405.47 | 0.00 | 0.00 |
August | 1843.71 | 0.06 | 583.39 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1488.73 | 19.76 | 548.45 | 169.52 | 378.93 | 0.00 | 0.00 |
October | 1161.46 | 87.33 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 801.20 | 233.36 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 501.99 | 403.68 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1167.01 | 178.05 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 501.99 | 0.06 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1843.71 | 479.87 | 623.28 | 198.58 | 424.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1618.56 | 747.70 | 1019.78 | 479.44 | 540.34 | 0.00 | 0.00 |
February | 1626.53 | 626.41 | 957.61 | 391.70 | 565.91 | 0.00 | 0.00 |
March | 1505.88 | 466.89 | 788.16 | 213.98 | 574.18 | 0.00 | 0.00 |
April | 1410.23 | 281.61 | 619.56 | 65.68 | 553.87 | 0.00 | 0.00 |
May | 1590.01 | 68.89 | 524.82 | 8.04 | 516.78 | 0.00 | 0.00 |
June | 1677.65 | 14.34 | 494.26 | 0.61 | 493.65 | 0.00 | 0.00 |
July | 1977.57 | 0.28 | 494.25 | 4.20 | 490.05 | 0.00 | 0.00 |
August | 2196.58 | 0.12 | 573.28 | 40.62 | 532.67 | 0.00 | 0.00 |
September | 2170.61 | 33.92 | 755.88 | 173.23 | 582.65 | 0.00 | 0.00 |
October | 2262.00 | 146.64 | 989.59 | 393.42 | 596.18 | 0.00 | 0.00 |
November | 2110.32 | 377.00 | 1091.72 | 526.29 | 565.43 | 0.00 | 0.00 |
December | 1712.66 | 634.88 | 1013.45 | 500.61 | 512.84 | 0.00 | 0.00 |
Annual Sum or Average | 1822.93 | 281.57 | 775.78 | 232.31 | 543.47 | 0.00 | 0.00 |
Minimum of Months | 1410.23 | 0.12 | 494.25 | 0.61 | 490.05 | 0.00 | 0.00 |
Maximum of Months | 2262.00 | 747.70 | 1091.72 | 526.29 | 596.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 533.82 | 516.80 | 373.19 | 107.18 | 266.01 | 0.00 | 0.00 |
February | 679.50 | 422.68 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 918.14 | 315.58 | 504.78 | 149.44 | 355.34 | 0.00 | 0.00 |
April | 1164.57 | 197.75 | 551.64 | 154.98 | 396.66 | 0.00 | 0.00 |
May | 1541.28 | 53.08 | 600.46 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1685.87 | 13.09 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1787.41 | 0.41 | 569.27 | 162.85 | 406.41 | 0.00 | 0.00 |
August | 1833.70 | 0.13 | 584.00 | 177.56 | 406.44 | 0.00 | 0.00 |
September | 1500.47 | 24.24 | 555.54 | 174.53 | 381.00 | 0.00 | 0.00 |
October | 1161.12 | 100.15 | 493.71 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 837.67 | 255.16 | 424.28 | 138.75 | 285.53 | 0.00 | 0.00 |
December | 564.32 | 433.34 | 355.19 | 107.37 | 247.82 | 0.00 | 0.00 |
Annual Sum or Average | 1186.90 | 193.28 | 505.18 | 152.52 | 352.65 | 0.00 | 0.00 |
Minimum of Months | 533.82 | 0.13 | 355.19 | 107.18 | 247.82 | 0.00 | 0.00 |
Maximum of Months | 1833.70 | 516.80 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.32 | 722.67 | 315.55 | 0.00 | 315.55 | 0.00 | 0.00 |
February | 498.69 | 602.22 | 361.71 | 0.00 | 361.71 | 0.00 | 0.00 |
March | 723.31 | 455.06 | 415.47 | 0.00 | 415.47 | 0.00 | 0.00 |
April | 1052.85 | 282.77 | 468.10 | 0.96 | 467.13 | 0.00 | 0.00 |
May | 1602.29 | 70.60 | 526.89 | 15.45 | 511.43 | 0.00 | 0.00 |
June | 1853.14 | 17.31 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
July | 2073.59 | 0.42 | 517.65 | 14.91 | 502.73 | 0.00 | 0.00 |
August | 2044.76 | 0.06 | 481.88 | 3.99 | 477.90 | 0.00 | 0.00 |
September | 1534.42 | 26.19 | 438.95 | 0.05 | 438.90 | 0.00 | 0.00 |
October | 1095.94 | 118.69 | 389.12 | 0.00 | 389.12 | 0.00 | 0.00 |
November | 691.26 | 330.97 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 404.11 | 591.04 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1165.17 | 266.56 | 425.91 | 5.58 | 420.34 | 0.00 | 0.00 |
Minimum of Months | 358.32 | 0.06 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2073.59 | 722.67 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 516.35 | 452.69 | 380.55 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 628.93 | 381.26 | 414.71 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 806.50 | 290.65 | 458.09 | 112.90 | 345.19 | 0.00 | 0.00 |
April | 1158.03 | 182.78 | 557.74 | 162.51 | 395.23 | 0.00 | 0.00 |
May | 1572.09 | 45.35 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
June | 1662.16 | 10.48 | 610.42 | 186.67 | 423.75 | 0.00 | 0.00 |
July | 1799.45 | 0.24 | 569.73 | 164.25 | 405.48 | 0.00 | 0.00 |
August | 1858.71 | 0.02 | 583.40 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1502.87 | 15.89 | 548.46 | 169.52 | 378.94 | 0.00 | 0.00 |
October | 1172.63 | 73.64 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 808.61 | 209.61 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 506.41 | 374.34 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1169.19 | 168.72 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 506.41 | 0.02 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1858.71 | 452.69 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1614.76 | 701.51 | 1019.82 | 479.46 | 540.35 | 0.00 | 0.00 |
February | 1617.31 | 598.76 | 957.65 | 391.72 | 565.93 | 0.00 | 0.00 |
March | 1495.09 | 463.95 | 788.19 | 213.99 | 574.20 | 0.00 | 0.00 |
April | 1400.89 | 289.59 | 619.58 | 65.69 | 553.89 | 0.00 | 0.00 |
May | 1598.03 | 71.63 | 524.83 | 8.04 | 516.80 | 0.00 | 0.00 |
June | 1700.31 | 14.14 | 494.27 | 0.61 | 493.66 | 0.00 | 0.00 |
July | 2011.34 | 0.22 | 494.26 | 4.20 | 490.06 | 0.00 | 0.00 |
August | 2252.50 | 0.02 | 573.30 | 40.62 | 532.68 | 0.00 | 0.00 |
September | 2217.56 | 26.27 | 755.91 | 173.24 | 582.67 | 0.00 | 0.00 |
October | 2294.94 | 118.69 | 989.63 | 393.43 | 596.20 | 0.00 | 0.00 |
November | 2124.09 | 330.49 | 1091.76 | 526.31 | 565.45 | 0.00 | 0.00 |
December | 1714.19 | 583.88 | 1013.48 | 500.63 | 512.85 | 0.00 | 0.00 |
Annual Sum or Average | 1838.29 | 264.98 | 775.80 | 232.32 | 543.49 | 0.00 | 0.00 |
Minimum of Months | 1400.89 | 0.02 | 494.26 | 0.61 | 490.06 | 0.00 | 0.00 |
Maximum of Months | 2294.94 | 701.51 | 1091.76 | 526.31 | 596.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 536.83 | 486.10 | 373.20 | 107.19 | 266.01 | 0.00 | 0.00 |
February | 677.51 | 405.98 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 911.17 | 311.56 | 504.79 | 149.44 | 355.35 | 0.00 | 0.00 |
April | 1156.11 | 199.58 | 551.65 | 154.98 | 396.67 | 0.00 | 0.00 |
May | 1539.53 | 53.11 | 600.47 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1691.24 | 12.21 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1798.56 | 0.26 | 569.27 | 162.86 | 406.41 | 0.00 | 0.00 |
August | 1853.35 | 0.07 | 584.01 | 177.56 | 406.45 | 0.00 | 0.00 |
September | 1518.67 | 19.56 | 555.54 | 174.54 | 381.01 | 0.00 | 0.00 |
October | 1175.95 | 85.45 | 493.72 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 847.72 | 228.85 | 424.29 | 138.76 | 285.53 | 0.00 | 0.00 |
December | 570.06 | 400.52 | 355.19 | 107.37 | 247.83 | 0.00 | 0.00 |
Annual Sum or Average | 1192.69 | 182.53 | 505.19 | 152.53 | 352.66 | 0.00 | 0.00 |
Minimum of Months | 536.83 | 0.07 | 355.19 | 107.19 | 247.83 | 0.00 | 0.00 |
Maximum of Months | 1853.35 | 486.10 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.990268E+09 | 0.179760E+10 | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.00 | 0.00 |
February | 0.122087E+10 | 0.136796E+10 | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.00 | 0.00 |
March | 0.193633E+10 | 0.115840E+10 | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.00 | 0.00 |
April | 0.270966E+10 | 0.710741E+09 | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.00 | 0.00 |
May | 0.425470E+10 | 0.188843E+09 | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.00 | 0.00 |
June | 0.476422E+10 | 47332653.53 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
July | 0.550387E+10 | 1203284.75 | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.00 | 0.00 |
August | 0.543093E+10 | 197608.67 | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.00 | 0.00 |
September | 0.394529E+10 | 67707969.16 | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.00 | 0.00 |
October | 0.291604E+10 | 0.309556E+09 | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.00 | 0.00 |
November | 0.179205E+10 | 0.810755E+09 | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.00 | 0.00 |
December | 0.110393E+10 | 0.147656E+10 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.365682E+11 | 0.793687E+10 | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.990268E+09 | 197608.67 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550387E+10 | 0.179760E+10 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141786E+10 | 0.113629E+10 | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.00 | 0.00 |
February | 0.154237E+10 | 0.871562E+09 | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.00 | 0.00 |
March | 0.217141E+10 | 0.742694E+09 | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.00 | 0.00 |
April | 0.299924E+10 | 0.459893E+09 | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.00 | 0.00 |
May | 0.419513E+10 | 0.120500E+09 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
June | 0.429166E+10 | 28288695.96 | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.00 | 0.00 |
July | 0.479642E+10 | 662142.42 | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.00 | 0.00 |
August | 0.495853E+10 | 73629.60 | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.00 | 0.00 |
September | 0.388319E+10 | 40670308.06 | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.00 | 0.00 |
October | 0.313650E+10 | 0.191197E+09 | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.00 | 0.00 |
November | 0.210609E+10 | 0.515297E+09 | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.00 | 0.00 |
December | 0.138326E+10 | 0.941919E+09 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368817E+11 | 0.504904E+10 | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.138326E+10 | 73629.60 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495853E+10 | 0.113629E+10 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.435193E+10 | 0.176398E+10 | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.00 | 0.00 |
February | 0.392055E+10 | 0.136918E+10 | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.00 | 0.00 |
March | 0.399779E+10 | 0.118459E+10 | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.00 | 0.00 |
April | 0.360989E+10 | 0.727447E+09 | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.00 | 0.00 |
May | 0.424194E+10 | 0.190234E+09 | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.00 | 0.00 |
June | 0.436857E+10 | 38106312.69 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
July | 0.533585E+10 | 649010.69 | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.00 | 0.00 |
August | 0.598520E+10 | 102887.28 | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.00 | 0.00 |
September | 0.571091E+10 | 67665865.98 | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.00 | 0.00 |
October | 0.611936E+10 | 0.309868E+09 | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.00 | 0.00 |
November | 0.549896E+10 | 0.814662E+09 | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.00 | 0.00 |
December | 0.460739E+10 | 0.147545E+10 | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.577483E+11 | 0.794194E+10 | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.00 | 0.00 |
Minimum of Months | 0.360989E+10 | 102887.28 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.611936E+10 | 0.176398E+10 | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145396E+10 | 0.121280E+10 | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.00 | 0.00 |
February | 0.164474E+10 | 0.924402E+09 | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.00 | 0.00 |
March | 0.243524E+10 | 0.794821E+09 | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.00 | 0.00 |
April | 0.298082E+10 | 0.501760E+09 | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.00 | 0.00 |
May | 0.409617E+10 | 0.141409E+09 | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.00 | 0.00 |
June | 0.435585E+10 | 32965386.48 | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.00 | 0.00 |
July | 0.478203E+10 | 725407.84 | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.00 | 0.00 |
August | 0.493041E+10 | 205611.89 | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.00 | 0.00 |
September | 0.391263E+10 | 50774873.40 | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.00 | 0.00 |
October | 0.313396E+10 | 0.223500E+09 | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.00 | 0.00 |
November | 0.219412E+10 | 0.561899E+09 | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.00 | 0.00 |
December | 0.153694E+10 | 0.100469E+10 | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374569E+11 | 0.544995E+10 | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145396E+10 | 205611.89 | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493041E+10 | 0.121280E+10 | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.942305E+09 | 0.203251E+10 | 0.845143E+09 | 0.00 | 0.845143E+09 | 0.00 | 0.00 |
February | 0.120784E+10 | 0.149294E+10 | 0.875023E+09 | 0.00 | 0.875023E+09 | 0.00 | 0.00 |
March | 0.195813E+10 | 0.120700E+10 | 0.111277E+10 | 0.00 | 0.111277E+10 | 0.00 | 0.00 |
April | 0.275836E+10 | 0.702328E+09 | 0.121329E+10 | 2499893.67 | 0.121079E+10 | 0.00 | 0.00 |
May | 0.430410E+10 | 0.176116E+09 | 0.141118E+10 | 41388814.81 | 0.136979E+10 | 0.00 | 0.00 |
June | 0.479320E+10 | 41996085.22 | 0.146220E+10 | 81176234.19 | 0.138102E+10 | 0.00 | 0.00 |
July | 0.551832E+10 | 1208554.85 | 0.138643E+10 | 39946198.84 | 0.134649E+10 | 0.00 | 0.00 |
August | 0.540503E+10 | 210655.22 | 0.129065E+10 | 10674882.49 | 0.127998E+10 | 0.00 | 0.00 |
September | 0.390837E+10 | 77926397.70 | 0.113774E+10 | 130373.59 | 0.113761E+10 | 0.00 | 0.00 |
October | 0.286923E+10 | 0.356442E+09 | 0.104220E+10 | 0.00 | 0.104220E+10 | 0.00 | 0.00 |
November | 0.174472E+10 | 0.935225E+09 | 0.865846E+09 | 0.00 | 0.865846E+09 | 0.00 | 0.00 |
December | 0.105254E+10 | 0.169651E+10 | 0.788831E+09 | 0.00 | 0.788831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.364622E+11 | 0.872041E+10 | 0.134313E+11 | 0.175816E+09 | 0.132555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.942305E+09 | 210655.22 | 0.788831E+09 | 0.00 | 0.788831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551832E+10 | 0.203251E+10 | 0.146220E+10 | 81176234.19 | 0.138102E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137835E+10 | 0.128529E+10 | 0.101924E+10 | 0.308370E+09 | 0.710874E+09 | 0.00 | 0.00 |
February | 0.153238E+10 | 0.957192E+09 | 0.100325E+10 | 0.271885E+09 | 0.731366E+09 | 0.00 | 0.00 |
March | 0.218704E+10 | 0.783254E+09 | 0.122693E+10 | 0.302392E+09 | 0.924537E+09 | 0.00 | 0.00 |
April | 0.303285E+10 | 0.468129E+09 | 0.144565E+10 | 0.421212E+09 | 0.102444E+10 | 0.00 | 0.00 |
May | 0.422823E+10 | 0.120719E+09 | 0.166940E+10 | 0.531878E+09 | 0.113752E+10 | 0.00 | 0.00 |
June | 0.431137E+10 | 28256647.83 | 0.158218E+10 | 0.483847E+09 | 0.109834E+10 | 0.00 | 0.00 |
July | 0.480349E+10 | 869407.74 | 0.152595E+10 | 0.439926E+09 | 0.108602E+10 | 0.00 | 0.00 |
August | 0.493818E+10 | 165965.79 | 0.156254E+10 | 0.479564E+09 | 0.108298E+10 | 0.00 | 0.00 |
September | 0.385879E+10 | 51230569.34 | 0.142159E+10 | 0.439394E+09 | 0.982194E+09 | 0.00 | 0.00 |
October | 0.311085E+10 | 0.233892E+09 | 0.133295E+10 | 0.435473E+09 | 0.897474E+09 | 0.00 | 0.00 |
November | 0.207670E+10 | 0.604873E+09 | 0.108098E+10 | 0.342398E+09 | 0.738583E+09 | 0.00 | 0.00 |
December | 0.134453E+10 | 0.108123E+10 | 0.904115E+09 | 0.248051E+09 | 0.656063E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368028E+11 | 0.561510E+10 | 0.157748E+11 | 0.470439E+10 | 0.110704E+11 | 0.00 | 0.00 |
Minimum of Months | 0.134453E+10 | 165965.79 | 0.904115E+09 | 0.248051E+09 | 0.656063E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493818E+10 | 0.128529E+10 | 0.166940E+10 | 0.531878E+09 | 0.113752E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.433514E+10 | 0.200264E+10 | 0.273137E+10 | 0.128414E+10 | 0.144723E+10 | 0.00 | 0.00 |
February | 0.393490E+10 | 0.151542E+10 | 0.231666E+10 | 0.947611E+09 | 0.136905E+10 | 0.00 | 0.00 |
March | 0.403334E+10 | 0.125052E+10 | 0.211101E+10 | 0.573124E+09 | 0.153789E+10 | 0.00 | 0.00 |
April | 0.365532E+10 | 0.729938E+09 | 0.160589E+10 | 0.170253E+09 | 0.143564E+10 | 0.00 | 0.00 |
May | 0.425867E+10 | 0.184518E+09 | 0.140567E+10 | 21526247.30 | 0.138415E+10 | 0.00 | 0.00 |
June | 0.434846E+10 | 37169416.09 | 0.128112E+10 | 1585412.74 | 0.127953E+10 | 0.00 | 0.00 |
July | 0.529672E+10 | 746426.22 | 0.132379E+10 | 11248009.42 | 0.131254E+10 | 0.00 | 0.00 |
August | 0.588333E+10 | 319363.84 | 0.153548E+10 | 0.108794E+09 | 0.142669E+10 | 0.00 | 0.00 |
September | 0.562623E+10 | 87922569.98 | 0.195924E+10 | 0.449014E+09 | 0.151023E+10 | 0.00 | 0.00 |
October | 0.605855E+10 | 0.392772E+09 | 0.265052E+10 | 0.105373E+10 | 0.159680E+10 | 0.00 | 0.00 |
November | 0.546995E+10 | 0.977174E+09 | 0.282974E+10 | 0.136414E+10 | 0.146560E+10 | 0.00 | 0.00 |
December | 0.458719E+10 | 0.170047E+10 | 0.271441E+10 | 0.134083E+10 | 0.137358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574878E+11 | 0.887961E+10 | 0.244649E+11 | 0.732599E+10 | 0.171389E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365532E+10 | 319363.84 | 0.128112E+10 | 1585412.74 | 0.127953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.605855E+10 | 0.200264E+10 | 0.282974E+10 | 0.136414E+10 | 0.159680E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142978E+10 | 0.138420E+10 | 0.999556E+09 | 0.287080E+09 | 0.712476E+09 | 0.00 | 0.00 |
February | 0.164384E+10 | 0.102254E+10 | 0.103093E+10 | 0.293980E+09 | 0.736954E+09 | 0.00 | 0.00 |
March | 0.245916E+10 | 0.845258E+09 | 0.135201E+10 | 0.400265E+09 | 0.951747E+09 | 0.00 | 0.00 |
April | 0.301857E+10 | 0.512576E+09 | 0.142986E+10 | 0.401712E+09 | 0.102814E+10 | 0.00 | 0.00 |
May | 0.412817E+10 | 0.142177E+09 | 0.160827E+10 | 0.481418E+09 | 0.112685E+10 | 0.00 | 0.00 |
June | 0.436976E+10 | 33939591.66 | 0.160840E+10 | 0.507009E+09 | 0.110139E+10 | 0.00 | 0.00 |
July | 0.478739E+10 | 1093858.95 | 0.152472E+10 | 0.436190E+09 | 0.108853E+10 | 0.00 | 0.00 |
August | 0.491139E+10 | 357932.02 | 0.156419E+10 | 0.475579E+09 | 0.108861E+10 | 0.00 | 0.00 |
September | 0.388922E+10 | 62841887.28 | 0.143995E+10 | 0.452390E+09 | 0.987562E+09 | 0.00 | 0.00 |
October | 0.310995E+10 | 0.268236E+09 | 0.132235E+10 | 0.427154E+09 | 0.895196E+09 | 0.00 | 0.00 |
November | 0.217124E+10 | 0.661375E+09 | 0.109974E+10 | 0.359649E+09 | 0.740090E+09 | 0.00 | 0.00 |
December | 0.151148E+10 | 0.116067E+10 | 0.951341E+09 | 0.287573E+09 | 0.663769E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374300E+11 | 0.609527E+10 | 0.159313E+11 | 0.481000E+10 | 0.111213E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142978E+10 | 357932.02 | 0.951341E+09 | 0.287080E+09 | 0.663769E+09 | 0.00 | 0.00 |
Maximum of Months | 0.491139E+10 | 0.138420E+10 | 0.160840E+10 | 0.507009E+09 | 0.112685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959726E+09 | 0.193561E+10 | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.00 | 0.00 |
February | 0.120644E+10 | 0.145688E+10 | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.00 | 0.00 |
March | 0.193732E+10 | 0.121885E+10 | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.00 | 0.00 |
April | 0.272898E+10 | 0.732945E+09 | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.00 | 0.00 |
May | 0.429157E+10 | 0.189108E+09 | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.00 | 0.00 |
June | 0.480334E+10 | 44861816.52 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
July | 0.555389E+10 | 1131592.45 | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.00 | 0.00 |
August | 0.547669E+10 | 147871.44 | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.00 | 0.00 |
September | 0.397723E+10 | 67883649.87 | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.00 | 0.00 |
October | 0.293537E+10 | 0.317904E+09 | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.00 | 0.00 |
November | 0.179175E+10 | 0.857872E+09 | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.00 | 0.00 |
December | 0.108237E+10 | 0.158304E+10 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367447E+11 | 0.840623E+10 | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.959726E+09 | 147871.44 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Maximum of Months | 0.555389E+10 | 0.193561E+10 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138298E+10 | 0.121249E+10 | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.00 | 0.00 |
February | 0.152151E+10 | 0.922345E+09 | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.00 | 0.00 |
March | 0.216014E+10 | 0.778488E+09 | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.00 | 0.00 |
April | 0.300161E+10 | 0.473775E+09 | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.00 | 0.00 |
May | 0.421068E+10 | 0.121454E+09 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
June | 0.430831E+10 | 27175809.55 | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.00 | 0.00 |
July | 0.481963E+10 | 638568.87 | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.00 | 0.00 |
August | 0.497836E+10 | 54492.28 | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.00 | 0.00 |
September | 0.389544E+10 | 41189279.51 | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.00 | 0.00 |
October | 0.314078E+10 | 0.197238E+09 | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.00 | 0.00 |
November | 0.209591E+10 | 0.543298E+09 | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.00 | 0.00 |
December | 0.135636E+10 | 0.100265E+10 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368717E+11 | 0.532079E+10 | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135636E+10 | 54492.28 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497836E+10 | 0.121249E+10 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432498E+10 | 0.187893E+10 | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.00 | 0.00 |
February | 0.391259E+10 | 0.144853E+10 | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.00 | 0.00 |
March | 0.400444E+10 | 0.124264E+10 | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.00 | 0.00 |
April | 0.363109E+10 | 0.750628E+09 | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.00 | 0.00 |
May | 0.428017E+10 | 0.191862E+09 | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.00 | 0.00 |
June | 0.440721E+10 | 36652742.12 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
July | 0.538717E+10 | 598909.19 | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.00 | 0.00 |
August | 0.603310E+10 | 66951.36 | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.00 | 0.00 |
September | 0.574792E+10 | 68091423.31 | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.00 | 0.00 |
October | 0.614677E+10 | 0.317910E+09 | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.00 | 0.00 |
November | 0.550563E+10 | 0.856622E+09 | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.00 | 0.00 |
December | 0.459129E+10 | 0.156387E+10 | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579724E+11 | 0.835640E+10 | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.00 | 0.00 |
Minimum of Months | 0.363109E+10 | 66951.36 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.614677E+10 | 0.187893E+10 | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143785E+10 | 0.130196E+10 | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.00 | 0.00 |
February | 0.163903E+10 | 0.982143E+09 | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.00 | 0.00 |
March | 0.244048E+10 | 0.834493E+09 | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.00 | 0.00 |
April | 0.299663E+10 | 0.517300E+09 | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.00 | 0.00 |
May | 0.412347E+10 | 0.142240E+09 | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.00 | 0.00 |
June | 0.438369E+10 | 31647767.97 | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.00 | 0.00 |
July | 0.481725E+10 | 689868.48 | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.00 | 0.00 |
August | 0.496402E+10 | 192494.29 | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.00 | 0.00 |
September | 0.393639E+10 | 50705474.94 | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.00 | 0.00 |
October | 0.314966E+10 | 0.228858E+09 | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.00 | 0.00 |
November | 0.219728E+10 | 0.593169E+09 | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.00 | 0.00 |
December | 0.152685E+10 | 0.107276E+10 | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376126E+11 | 0.575616E+10 | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143785E+10 | 192494.29 | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.496402E+10 | 0.130196E+10 | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.391020E+10 | -0.321813E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692070796.3 | 58.98 | 0.00 | 0.00 |
February | 0.346736E+10 | -0.284295E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -624417565.9 | 58.98 | 0.00 | 0.00 |
March | 0.381870E+10 | -0.312688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691821190.0 | 58.98 | 0.00 | 0.00 |
April | 0.319640E+10 | -0.252834E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668060994.3 | 58.98 | 0.00 | 0.00 |
May | 0.310589E+10 | -0.241531E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690578286.3 | 58.98 | 0.00 | 0.00 |
June | 0.285123E+10 | -0.218173E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669506904.0 | 58.98 | 0.00 | 0.00 |
July | 0.268582E+10 | -0.199164E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694181224.3 | 58.98 | 0.00 | 0.00 |
August | 0.300092E+10 | -0.230404E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696879843.0 | 58.98 | 0.00 | 0.00 |
September | 0.296709E+10 | -0.229733E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669759771.7 | 58.98 | 0.00 | 0.00 |
October | 0.335790E+10 | -0.266759E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690313363.1 | 58.98 | 0.00 | 0.00 |
November | 0.357137E+10 | -0.290454E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666828470.9 | 58.98 | 0.00 | 0.00 |
December | 0.376100E+10 | -0.307023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690763952.9 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.396939E+11 | -0.315487E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.814518E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.268582E+10 | -0.321813E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -696879843.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.391020E+10 | -0.199164E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -624417565.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4165.40 | 34.10 | 310.83 | 292.67 | 1091.39 | 24.99 | 288.50 | 280.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2142.31 | 24.98 | 142.00 | 274.00 | 971.87 | 20.80 | 176.33 | 243.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1573.30 | 18.39 | 5.00 | 313.33 | 824.91 | 20.36 | 144.83 | 276.83 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1224.30 | 17.39 | 0.00 | 321.50 | 653.43 | 19.46 | 84.17 | 283.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1037.58 | 17.33 | 0.00 | 348.00 | 572.30 | 19.45 | 16.50 | 303.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:10 | 992.35 | 17.23 | 0.00 | 343.50 | 556.25 | 19.40 | 7.50 | 296.33 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1043.82 | 17.15 | 0.00 | 343.50 | 578.05 | 19.30 | 41.00 | 302.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1228.01 | 17.65 | 0.00 | 342.67 | 663.58 | 19.78 | 132.83 | 302.83 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 1542.23 | 18.38 | 0.00 | 318.17 | 820.60 | 20.53 | 187.67 | 284.00 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 2072.38 | 20.36 | 34.50 | 317.00 | 996.12 | 21.43 | 230.50 | 287.83 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3503.94 | 31.74 | 256.33 | 297.50 | 1130.97 | 24.83 | 300.33 | 282.00 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4154.16 | 34.47 | 307.00 | 288.50 | 1165.61 | 26.17 | 287.67 | 275.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1963.57 | 21.89 | 1055.67 | 3800.33 | 815.15 | 21.19 | 1897.83 | 3418.50 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 992.35 | 17.15 | 0.00 | 274.00 | 556.25 | 19.30 | 7.50 | 243.83 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4165.40 | 34.47 | 310.83 | 348.00 | 1165.61 | 26.17 | 300.33 | 303.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1512.95 | 21.78 | 111.83 | 272.33 | 798.35 | 22.49 | 80.67 | 233.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1634.75 | 21.36 | 102.33 | 261.17 | 706.79 | 20.76 | 47.17 | 224.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1522.54 | 19.17 | 83.83 | 306.33 | 787.26 | 21.37 | 66.00 | 268.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1791.97 | 20.37 | 109.33 | 318.50 | 918.91 | 21.37 | 79.83 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2023.85 | 20.25 | 118.83 | 355.33 | 865.64 | 20.92 | 67.83 | 318.83 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1944.47 | 19.98 | 114.33 | 348.83 | 853.40 | 20.99 | 66.67 | 315.67 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1835.56 | 19.90 | 114.17 | 347.17 | 814.98 | 20.64 | 61.83 | 309.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1890.37 | 20.49 | 113.83 | 339.83 | 848.20 | 20.38 | 56.00 | 305.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1884.22 | 21.34 | 107.00 | 310.00 | 975.28 | 22.34 | 77.33 | 283.00 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1752.13 | 21.26 | 104.67 | 303.83 | 911.81 | 22.30 | 76.00 | 272.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1505.13 | 20.48 | 84.33 | 275.33 | 785.64 | 22.26 | 63.00 | 241.17 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1246.09 | 20.33 | 85.50 | 267.17 | 628.02 | 20.91 | 50.67 | 222.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1729.56 | 20.52 | 1250.00 | 3705.83 | 829.32 | 21.36 | 793.00 | 3276.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1246.09 | 19.17 | 83.83 | 261.17 | 628.02 | 20.38 | 47.17 | 222.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 2023.85 | 21.78 | 118.83 | 355.33 | 975.28 | 22.49 | 80.67 | 318.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:39 | 581.30 | 15.19 | 0.00 | 258.00 | 336.26 | 17.33 | 0.00 | 172.67 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 661.11 | 16.04 | 0.00 | 251.67 | 381.33 | 18.17 | 0.00 | 188.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 771.41 | 16.70 | 0.00 | 305.17 | 438.69 | 18.78 | 0.00 | 252.67 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 884.53 | 17.02 | 0.00 | 325.50 | 496.49 | 19.04 | 0.00 | 285.17 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1043.93 | 18.04 | 2.83 | 367.83 | 578.21 | 20.12 | 54.83 | 333.33 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:19 | 1155.84 | 21.18 | 77.67 | 366.00 | 631.89 | 21.73 | 157.00 | 336.83 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1117.31 | 19.00 | 27.00 | 357.33 | 611.95 | 21.14 | 128.50 | 327.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1010.71 | 17.69 | 0.00 | 348.83 | 566.63 | 19.81 | 53.33 | 315.00 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 880.62 | 17.38 | 0.00 | 316.67 | 505.49 | 19.49 | 0.00 | 273.17 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 727.75 | 16.49 | 0.00 | 298.33 | 427.45 | 18.63 | 0.00 | 245.33 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 630.06 | 16.11 | 0.00 | 260.33 | 371.49 | 18.32 | 0.00 | 193.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 563.66 | 15.28 | 0.00 | 247.33 | 326.72 | 17.46 | 0.00 | 150.17 |
Annual Sum or Average | 4323.33 | 0.52 | 854.57 | 17.31 | 107.50 | 3703.00 | 482.38 | 19.28 | 393.67 | 3073.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 563.66 | 15.19 | 0.00 | 247.33 | 326.72 | 17.33 | 0.00 | 150.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1155.84 | 21.18 | 77.67 | 367.83 | 631.89 | 21.73 | 157.00 | 336.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1465.81 | 21.39 | 108.17 | 273.17 | 766.99 | 22.11 | 77.17 | 233.00 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1434.95 | 19.78 | 76.33 | 260.33 | 728.09 | 20.67 | 48.33 | 222.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1636.32 | 19.43 | 85.83 | 307.67 | 840.51 | 21.39 | 65.67 | 270.00 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:20 | 1662.92 | 16.77 | 55.00 | 322.67 | 867.51 | 17.26 | 0.00 | 285.17 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:40 | 1747.35 | 14.42 | 0.00 | 348.83 | 904.71 | 17.57 | 0.00 | 311.67 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:30 | 1856.25 | 14.60 | 0.00 | 345.17 | 827.69 | 17.77 | 0.00 | 310.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1777.71 | 14.63 | 3.67 | 346.83 | 809.63 | 17.55 | 0.00 | 307.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1815.78 | 17.24 | 59.83 | 342.00 | 941.08 | 17.96 | 5.50 | 306.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1746.04 | 19.75 | 86.83 | 316.33 | 908.86 | 20.82 | 57.33 | 283.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1815.24 | 21.42 | 107.83 | 301.67 | 945.05 | 22.46 | 79.33 | 271.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1562.64 | 20.44 | 85.00 | 275.50 | 820.26 | 22.58 | 69.00 | 242.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:39 | 1365.77 | 19.99 | 87.33 | 266.83 | 716.56 | 22.16 | 71.17 | 225.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1670.30 | 18.11 | 755.83 | 3707.00 | 843.97 | 19.85 | 473.50 | 3269.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1365.77 | 14.42 | 0.00 | 260.33 | 716.56 | 17.26 | 0.00 | 222.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1856.25 | 21.42 | 108.17 | 348.83 | 945.05 | 22.58 | 79.33 | 311.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4068.03 | 33.81 | 310.17 | 292.00 | 1023.94 | 22.66 | 91.67 | 279.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2054.96 | 22.69 | 141.00 | 272.50 | 911.34 | 17.89 | 0.00 | 241.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1505.18 | 14.49 | 5.00 | 311.33 | 779.07 | 17.71 | 0.00 | 273.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1176.28 | 13.72 | 0.00 | 320.50 | 623.12 | 17.04 | 0.00 | 280.33 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:19 | 999.17 | 13.73 | 0.00 | 345.67 | 549.41 | 17.13 | 0.00 | 299.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:10 | 955.80 | 13.56 | 0.00 | 342.33 | 534.82 | 17.03 | 0.00 | 294.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1005.19 | 13.42 | 0.00 | 342.67 | 555.15 | 16.83 | 0.00 | 297.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 1180.43 | 14.00 | 0.00 | 341.67 | 634.30 | 17.39 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1477.18 | 14.67 | 0.00 | 317.17 | 777.94 | 18.09 | 0.00 | 281.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 1985.91 | 16.78 | 34.50 | 316.17 | 935.96 | 18.92 | 10.67 | 284.83 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3403.96 | 30.74 | 255.67 | 296.17 | 1059.69 | 22.44 | 76.67 | 280.50 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:30 | 4055.16 | 34.23 | 306.00 | 287.50 | 1096.76 | 24.01 | 113.17 | 274.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1898.14 | 19.01 | 1052.33 | 3785.67 | 771.61 | 18.75 | 292.17 | 3386.33 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 955.80 | 13.42 | 0.00 | 272.50 | 534.82 | 16.83 | 0.00 | 241.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4068.03 | 34.23 | 310.17 | 345.67 | 1096.76 | 24.01 | 113.17 | 299.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1470.74 | 21.32 | 111.83 | 271.00 | 767.44 | 22.27 | 80.83 | 229.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1591.03 | 20.90 | 102.33 | 259.33 | 674.70 | 20.54 | 47.17 | 221.83 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1479.80 | 18.68 | 83.83 | 303.50 | 753.22 | 21.17 | 66.00 | 264.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1737.78 | 19.93 | 109.33 | 316.33 | 881.83 | 21.20 | 79.83 | 277.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 1969.22 | 19.81 | 118.83 | 354.33 | 818.82 | 19.93 | 57.33 | 312.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1898.13 | 19.53 | 114.33 | 347.17 | 814.52 | 20.80 | 66.33 | 312.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1786.50 | 19.47 | 114.17 | 345.33 | 775.26 | 19.67 | 52.50 | 306.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1829.23 | 20.06 | 113.67 | 338.17 | 808.87 | 20.21 | 56.00 | 303.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1830.64 | 20.73 | 105.17 | 308.67 | 935.55 | 22.16 | 77.33 | 280.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1679.74 | 19.29 | 87.83 | 301.83 | 873.61 | 22.11 | 76.00 | 268.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1458.94 | 19.98 | 84.33 | 273.33 | 750.98 | 22.03 | 63.00 | 237.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1207.63 | 19.83 | 85.17 | 264.83 | 599.92 | 20.66 | 50.67 | 218.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1678.82 | 19.93 | 1230.83 | 3683.83 | 792.31 | 21.02 | 773.00 | 3230.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1207.63 | 18.68 | 83.83 | 259.33 | 599.92 | 19.67 | 47.17 | 218.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1969.22 | 21.32 | 118.83 | 354.33 | 935.55 | 22.27 | 80.83 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-09:50 | 560.47 | 11.54 | 0.00 | 253.50 | 324.54 | 15.00 | 0.00 | 160.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 637.65 | 12.30 | 0.00 | 250.00 | 368.10 | 15.80 | 0.00 | 182.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 744.27 | 13.02 | 0.00 | 302.50 | 423.19 | 16.46 | 0.00 | 246.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 852.99 | 13.47 | 0.00 | 324.00 | 478.20 | 16.82 | 0.00 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1005.79 | 14.40 | 2.83 | 366.33 | 555.59 | 17.84 | 1.17 | 328.17 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:30 | 1112.67 | 18.32 | 77.33 | 363.00 | 605.82 | 19.53 | 34.17 | 333.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:49 | 1075.97 | 15.54 | 26.83 | 356.33 | 587.19 | 18.86 | 27.33 | 324.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 973.41 | 14.11 | 0.00 | 347.50 | 544.82 | 17.55 | 0.00 | 310.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 848.55 | 13.94 | 0.00 | 315.00 | 487.17 | 17.35 | 0.00 | 270.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 701.31 | 13.04 | 0.00 | 295.83 | 412.65 | 16.51 | 0.00 | 239.67 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 606.97 | 12.51 | 0.00 | 256.67 | 358.64 | 16.09 | 0.00 | 184.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 543.18 | 11.51 | 0.00 | 243.50 | 315.21 | 15.05 | 0.00 | 136.67 |
Annual Sum or Average | 4323.33 | 0.52 | 823.44 | 13.78 | 107.00 | 3674.17 | 464.30 | 17.02 | 62.67 | 2996.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 543.18 | 11.51 | 0.00 | 243.50 | 315.21 | 15.00 | 0.00 | 136.67 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1112.67 | 18.32 | 77.33 | 366.33 | 605.82 | 19.53 | 34.17 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1424.55 | 21.01 | 108.17 | 271.00 | 736.54 | 22.00 | 77.17 | 228.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1389.30 | 19.36 | 76.33 | 258.83 | 694.80 | 20.55 | 48.33 | 218.17 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1589.53 | 18.99 | 85.83 | 306.50 | 802.73 | 21.27 | 65.83 | 265.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:20 | 1592.86 | 16.29 | 55.00 | 320.17 | 830.02 | 17.08 | 0.00 | 282.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:49 | 1691.85 | 13.87 | 0.00 | 347.83 | 866.89 | 17.36 | 0.00 | 309.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:40 | 1808.08 | 14.05 | 0.00 | 343.50 | 788.43 | 17.56 | 0.00 | 306.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1726.20 | 14.08 | 3.67 | 345.00 | 772.28 | 17.34 | 0.00 | 304.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1754.23 | 16.76 | 59.83 | 339.83 | 901.70 | 17.77 | 5.50 | 304.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1695.99 | 19.32 | 86.83 | 314.33 | 868.51 | 20.68 | 57.33 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-08:09 | 1764.55 | 21.02 | 107.83 | 300.00 | 907.15 | 22.34 | 79.33 | 268.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1515.72 | 20.01 | 85.00 | 273.17 | 785.33 | 22.47 | 69.00 | 239.83 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:50 | 1324.36 | 19.56 | 87.33 | 264.83 | 686.01 | 22.05 | 71.33 | 222.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1619.05 | 17.64 | 755.83 | 3685.00 | 807.36 | 19.69 | 473.83 | 3230.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1324.36 | 13.87 | 0.00 | 258.83 | 686.01 | 17.08 | 0.00 | 218.17 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1808.08 | 21.02 | 108.17 | 347.83 | 907.15 | 22.47 | 79.33 | 309.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4067.94 | 33.81 | 310.17 | 292.00 | 1023.85 | 22.66 | 91.67 | 279.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2054.84 | 22.70 | 141.00 | 272.50 | 911.26 | 17.89 | 0.00 | 241.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1505.07 | 14.49 | 5.00 | 311.33 | 779.00 | 17.71 | 0.00 | 273.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1176.20 | 13.72 | 0.00 | 320.50 | 623.06 | 17.04 | 0.00 | 280.33 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:19 | 999.11 | 13.73 | 0.00 | 345.67 | 549.37 | 17.13 | 0.00 | 299.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:10 | 955.75 | 13.56 | 0.00 | 342.33 | 534.78 | 17.03 | 0.00 | 294.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1005.13 | 13.42 | 0.00 | 342.67 | 555.10 | 16.83 | 0.00 | 297.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 1180.36 | 14.00 | 0.00 | 341.67 | 634.24 | 17.39 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1477.08 | 14.67 | 0.00 | 317.17 | 777.87 | 18.10 | 0.00 | 281.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 1985.79 | 16.78 | 34.50 | 316.17 | 935.88 | 18.92 | 10.67 | 284.83 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3403.85 | 30.74 | 255.67 | 296.17 | 1059.59 | 22.44 | 76.67 | 280.50 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:30 | 4055.08 | 34.23 | 306.00 | 287.50 | 1096.67 | 24.01 | 113.17 | 274.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1898.05 | 19.01 | 1052.33 | 3785.67 | 771.54 | 18.75 | 292.17 | 3386.17 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 955.75 | 13.42 | 0.00 | 272.50 | 534.78 | 16.83 | 0.00 | 241.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4067.94 | 34.23 | 310.17 | 345.67 | 1096.67 | 24.01 | 113.17 | 299.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1470.69 | 21.32 | 111.83 | 271.00 | 767.39 | 22.27 | 80.83 | 229.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1590.97 | 20.90 | 102.33 | 259.33 | 674.64 | 20.54 | 47.17 | 221.83 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1479.74 | 18.68 | 83.83 | 303.50 | 753.16 | 21.17 | 66.00 | 264.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1737.71 | 19.93 | 109.33 | 316.33 | 881.78 | 21.20 | 79.83 | 277.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 1969.15 | 19.81 | 118.83 | 354.33 | 818.76 | 19.93 | 57.33 | 312.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1898.06 | 19.53 | 114.33 | 347.17 | 814.47 | 20.80 | 66.33 | 312.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1786.43 | 19.47 | 114.17 | 345.33 | 775.20 | 19.67 | 52.50 | 306.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1829.16 | 20.06 | 113.67 | 338.17 | 808.81 | 20.22 | 56.00 | 303.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1830.57 | 20.73 | 105.17 | 308.67 | 935.49 | 22.16 | 77.33 | 280.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1679.69 | 19.30 | 87.83 | 301.83 | 873.56 | 22.11 | 76.00 | 268.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1458.89 | 19.98 | 84.33 | 273.33 | 750.93 | 22.03 | 63.00 | 237.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1207.59 | 19.83 | 85.33 | 264.83 | 599.87 | 20.66 | 50.67 | 218.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1678.76 | 19.93 | 1231.00 | 3683.83 | 792.26 | 21.02 | 773.00 | 3230.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1207.59 | 18.68 | 83.83 | 259.33 | 599.87 | 19.67 | 47.17 | 218.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1969.15 | 21.32 | 118.83 | 354.33 | 935.49 | 22.27 | 80.83 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-09:50 | 560.45 | 11.54 | 0.00 | 253.50 | 324.52 | 15.00 | 0.00 | 160.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 637.62 | 12.30 | 0.00 | 250.00 | 368.07 | 15.80 | 0.00 | 182.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 744.23 | 13.02 | 0.00 | 302.50 | 423.15 | 16.46 | 0.00 | 246.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 852.95 | 13.47 | 0.00 | 324.00 | 478.16 | 16.82 | 0.00 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1005.74 | 14.40 | 2.83 | 366.33 | 555.55 | 17.84 | 1.17 | 328.17 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:30 | 1112.61 | 18.32 | 77.33 | 363.00 | 605.77 | 19.53 | 34.17 | 333.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:49 | 1075.91 | 15.54 | 26.83 | 356.33 | 587.15 | 18.86 | 27.33 | 324.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 973.36 | 14.11 | 0.00 | 347.50 | 544.78 | 17.55 | 0.00 | 310.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 848.52 | 13.94 | 0.00 | 315.00 | 487.14 | 17.35 | 0.00 | 270.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 701.28 | 13.05 | 0.00 | 295.83 | 412.62 | 16.51 | 0.00 | 239.67 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 606.95 | 12.51 | 0.00 | 256.67 | 358.61 | 16.09 | 0.00 | 184.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 543.16 | 11.51 | 0.00 | 243.50 | 315.19 | 15.05 | 0.00 | 136.50 |
Annual Sum or Average | 4323.33 | 0.52 | 823.40 | 13.79 | 107.00 | 3674.17 | 464.26 | 17.02 | 62.67 | 2996.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 543.16 | 11.51 | 0.00 | 243.50 | 315.19 | 15.00 | 0.00 | 136.50 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1112.61 | 18.32 | 77.33 | 366.33 | 605.77 | 19.53 | 34.17 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1424.51 | 21.01 | 108.17 | 271.00 | 736.49 | 22.00 | 77.17 | 228.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1389.24 | 19.36 | 76.33 | 258.83 | 694.75 | 20.55 | 48.33 | 218.17 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1589.47 | 18.99 | 85.83 | 306.50 | 802.67 | 21.27 | 65.83 | 265.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:20 | 1592.79 | 16.29 | 55.00 | 320.17 | 829.96 | 17.08 | 0.00 | 282.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:49 | 1691.78 | 13.87 | 0.00 | 347.83 | 866.84 | 17.36 | 0.00 | 309.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:40 | 1808.01 | 14.05 | 0.00 | 343.50 | 788.37 | 17.56 | 0.00 | 306.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1726.12 | 14.09 | 3.67 | 345.00 | 772.22 | 17.34 | 0.00 | 304.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1754.16 | 16.76 | 59.83 | 339.83 | 901.64 | 17.77 | 5.50 | 304.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1695.93 | 19.32 | 86.83 | 314.33 | 868.45 | 20.68 | 57.33 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-08:09 | 1764.50 | 21.02 | 107.83 | 300.00 | 907.09 | 22.34 | 79.33 | 268.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1515.67 | 20.01 | 85.00 | 273.17 | 785.28 | 22.47 | 69.00 | 239.83 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:50 | 1324.31 | 19.56 | 87.33 | 264.83 | 685.96 | 22.05 | 71.33 | 221.83 |
Annual Sum or Average | 4323.33 | 0.52 | 1618.99 | 17.64 | 755.83 | 3685.00 | 807.30 | 19.69 | 473.83 | 3229.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1324.31 | 13.87 | 0.00 | 258.83 | 685.96 | 17.08 | 0.00 | 218.17 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1808.01 | 21.02 | 108.17 | 347.83 | 907.09 | 22.47 | 79.33 | 309.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195037E+09 | 4479.05 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125976E+09 | 4479.05 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52297701.77 | 4479.05 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1242861.27 | 1563.07 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49169963.45 | 4479.05 | 18-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195037E+09 | 4479.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39035.43 | 258.41 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39035.43 | 258.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.328199E+11 | 0.272147E+11 | 50334.94 | 30-JAN-14:00 | 36386.03 | 0.00 |
February | 0.00 | 0.00 | 0.363245E+11 | 0.298406E+11 | 68225.60 | 07-FEB-13:03 | 53658.83 | 0.00 |
March | 0.00 | 0.00 | 0.497652E+11 | 0.427318E+11 | 74447.21 | 28-MAR-11:40 | 51013.12 | 0.00 |
April | 0.00 | 0.00 | 0.614728E+11 | 0.517436E+11 | 82647.51 | 10-APR-12:00 | 51511.21 | 0.00 |
May | 0.00 | 0.00 | 0.964544E+11 | 0.786581E+11 | 131472.12 | 24-MAY-05:03 | 71068.95 | 0.00 |
June | 0.00 | 0.00 | 0.119340E+12 | 0.857392E+11 | 134272.12 | 14-JUN-04:03 | 68367.49 | 0.00 |
July | 0.00 | 0.00 | 0.147690E+12 | 0.965371E+11 | 133452.63 | 06-JUL-04:02 | 72978.80 | 0.00 |
August | 0.00 | 0.00 | 0.165192E+12 | 0.105592E+12 | 134033.22 | 21-AUG-04:12 | 63169.69 | 0.00 |
September | 0.00 | 0.00 | 0.130460E+12 | 0.861208E+11 | 133189.55 | 28-SEP-04:02 | 72044.48 | 0.00 |
October | 0.00 | 0.00 | 0.102790E+12 | 0.756228E+11 | 131755.13 | 08-OCT-11:52 | 70668.49 | 0.00 |
November | 0.00 | 0.00 | 0.715328E+11 | 0.566164E+11 | 128246.73 | 02-NOV-06:03 | 77615.08 | 0.00 |
December | 0.00 | 0.00 | 0.437871E+11 | 0.353894E+11 | 77765.33 | 11-DEC-07:03 | 57549.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105763E+13 | 0.771807E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.328199E+11 | 0.272147E+11 | 50334.94 | 36386.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.165192E+12 | 0.105592E+12 | 134272.12 | 77615.08 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.266295E+11 | 0.208622E+11 | 41031.43 | 30-JAN-14:00 | 29462.06 | 0.00 |
February | 0.00 | 0.00 | 0.310569E+11 | 0.246390E+11 | 62377.41 | 07-FEB-15:05 | 46715.93 | 0.00 |
March | 0.00 | 0.00 | 0.445871E+11 | 0.376684E+11 | 65772.91 | 27-MAR-12:01 | 65772.91 | 0.00 |
April | 0.00 | 0.00 | 0.569783E+11 | 0.477065E+11 | 118456.78 | 30-APR-16:42 | 65379.22 | 0.00 |
May | 0.00 | 0.00 | 0.892344E+11 | 0.733260E+11 | 126848.65 | 24-MAY-05:03 | 65299.71 | 0.00 |
June | 0.00 | 0.00 | 0.110075E+12 | 0.792172E+11 | 129435.66 | 14-JUN-04:03 | 63723.30 | 0.00 |
July | 0.00 | 0.00 | 0.133644E+12 | 0.887841E+11 | 128593.73 | 06-JUL-04:02 | 65497.06 | 0.00 |
August | 0.00 | 0.00 | 0.143883E+12 | 0.943748E+11 | 128084.32 | 09-AUG-04:02 | 66470.69 | 0.00 |
September | 0.00 | 0.00 | 0.111948E+12 | 0.750273E+11 | 128800.84 | 28-SEP-04:02 | 65459.40 | 0.00 |
October | 0.00 | 0.00 | 0.859416E+11 | 0.640047E+11 | 126117.47 | 02-OCT-04:02 | 73720.36 | 0.00 |
November | 0.00 | 0.00 | 0.579254E+11 | 0.452192E+11 | 90333.11 | 02-NOV-06:03 | 52705.61 | 0.00 |
December | 0.00 | 0.00 | 0.354831E+11 | 0.271505E+11 | 60424.29 | 05-DEC-15:05 | 40666.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.927386E+12 | 0.677980E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.266295E+11 | 0.208622E+11 | 41031.43 | 29462.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143883E+12 | 0.943748E+11 | 129435.66 | 73720.36 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.265097E+11 | 0.199888E+11 | 42597.39 | 30-JAN-14:10 | 30169.89 | 0.00 |
February | 0.00 | 0.00 | 0.319087E+11 | 0.248222E+11 | 66061.17 | 07-FEB-15:30 | 50097.80 | 0.00 |
March | 0.00 | 0.00 | 0.471310E+11 | 0.393394E+11 | 72924.80 | 27-MAR-13:10 | 72924.80 | 0.00 |
April | 0.00 | 0.00 | 0.617763E+11 | 0.515693E+11 | 95540.54 | 30-APR-12:13 | 85700.34 | 0.00 |
May | 0.00 | 0.00 | 0.980308E+11 | 0.809918E+11 | 143522.89 | 31-MAY-04:02 | 85350.47 | 0.00 |
June | 0.00 | 0.00 | 0.120377E+12 | 0.881497E+11 | 148835.31 | 14-JUN-04:03 | 69726.83 | 0.00 |
July | 0.00 | 0.00 | 0.148103E+12 | 0.100226E+12 | 147867.19 | 06-JUL-04:02 | 76813.44 | 0.00 |
August | 0.00 | 0.00 | 0.157873E+12 | 0.105742E+12 | 146847.05 | 26-AUG-04:02 | 78141.86 | 0.00 |
September | 0.00 | 0.00 | 0.120538E+12 | 0.821269E+11 | 148601.65 | 28-SEP-04:02 | 74064.51 | 0.00 |
October | 0.00 | 0.00 | 0.905330E+11 | 0.678711E+11 | 143808.74 | 02-OCT-04:02 | 84786.91 | 0.00 |
November | 0.00 | 0.00 | 0.596737E+11 | 0.460841E+11 | 89716.48 | 01-NOV-14:00 | 63647.17 | 0.00 |
December | 0.00 | 0.00 | 0.357167E+11 | 0.264754E+11 | 61498.17 | 05-DEC-15:00 | 42131.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.998170E+12 | 0.733388E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.265097E+11 | 0.199888E+11 | 42597.39 | 30169.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157873E+12 | 0.105742E+12 | 148835.31 | 85700.34 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1355.32 | 4624.86 | 13-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1329.60 | 4561.34 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1325.54 | 4380.94 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1129.99 | 3969.11 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 1058.77 | 3581.29 | 02-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 1000.87 | 3262.77 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 897.97 | 3095.17 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 1019.38 | 3313.70 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1040.59 | 3663.57 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1150.60 | 4054.21 | 30-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1276.06 | 4400.30 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1298.80 | 4590.19 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 1156.03 | ||||
Minimum of Months | 0.00 | 0.00 | 897.97 | 3095.17 | ||
Maximum of Months | 0.00 | 0.00 | 1355.32 | 4624.86 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.225221E+10 | 0.33 | 3866.19 | 23-JAN-13:30 | 0.94 |
February | 0.233706E+10 | 0.35 | 5379.06 | 06-FEB-15:50 | 1.15 |
March | 0.317768E+10 | 0.40 | 7288.46 | 27-MAR-12:09 | 1.39 |
April | 0.370799E+10 | 0.44 | 8170.06 | 24-APR-12:20 | 1.49 |
May | 0.589706E+10 | 0.57 | 10884.83 | 12-MAY-04:02 | 1.78 |
June | 0.641971E+10 | 0.62 | 10884.83 | 01-JUN-04:02 | 1.78 |
July | 0.650217E+10 | 0.65 | 10884.83 | 01-JUL-04:02 | 1.77 |
August | 0.688363E+10 | 0.69 | 10884.83 | 01-AUG-06:03 | 1.78 |
September | 0.577482E+10 | 0.60 | 10884.83 | 01-SEP-04:02 | 1.78 |
October | 0.525355E+10 | 0.54 | 10884.83 | 02-OCT-06:03 | 1.78 |
November | 0.433063E+10 | 0.47 | 10884.83 | 20-NOV-05:02 | 1.78 |
December | 0.284409E+10 | 0.37 | 5295.81 | 04-DEC-13:10 | 1.13 |
Annual Sum or Average | 0.553806E+11 | 0.50 | |||
Minimum of Months | 0.225221E+10 | 0.33 | 3866.19 | 0.94 | |
Maximum of Months | 0.688363E+10 | 0.69 | 10884.83 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167349E+10 | 0.31 | 2851.93 | 23-JAN-13:30 | 0.82 |
February | 0.187009E+10 | 0.34 | 5459.32 | 06-FEB-15:05 | 1.20 |
March | 0.276892E+10 | 0.39 | 8116.01 | 02-MAR-07:03 | 1.54 |
April | 0.336122E+10 | 0.43 | 7692.51 | 28-APR-12:02 | 1.49 |
May | 0.547678E+10 | 0.57 | 10221.19 | 08-MAY-04:02 | 1.78 |
June | 0.602039E+10 | 0.62 | 10221.19 | 01-JUN-04:02 | 1.78 |
July | 0.646342E+10 | 0.65 | 10221.19 | 01-JUL-04:02 | 1.77 |
August | 0.716246E+10 | 0.70 | 10221.19 | 02-AUG-06:03 | 1.78 |
September | 0.568836E+10 | 0.59 | 10221.19 | 01-SEP-04:02 | 1.78 |
October | 0.475824E+10 | 0.51 | 10221.19 | 16-OCT-04:02 | 1.78 |
November | 0.334538E+10 | 0.42 | 7696.04 | 13-NOV-07:03 | 1.49 |
December | 0.201523E+10 | 0.33 | 4405.05 | 04-DEC-13:05 | 1.05 |
Annual Sum or Average | 0.506040E+11 | 0.49 | |||
Minimum of Months | 0.167349E+10 | 0.31 | 2851.93 | 0.82 | |
Maximum of Months | 0.716246E+10 | 0.70 | 10221.19 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159256E+10 | 0.33 | 2398.45 | 23-JAN-14:00 | 0.68 |
February | 0.176719E+10 | 0.34 | 4647.09 | 06-FEB-15:00 | 0.97 |
March | 0.262997E+10 | 0.38 | 6777.06 | 27-MAR-14:30 | 1.22 |
April | 0.325614E+10 | 0.41 | 6845.54 | 24-APR-14:00 | 1.23 |
May | 0.537894E+10 | 0.53 | 12118.48 | 31-MAY-04:02 | 1.76 |
June | 0.597354E+10 | 0.58 | 12178.70 | 13-JUN-04:02 | 1.77 |
July | 0.654317E+10 | 0.64 | 12178.70 | 01-JUL-04:02 | 1.76 |
August | 0.716594E+10 | 0.67 | 12178.70 | 04-AUG-04:02 | 1.77 |
September | 0.554928E+10 | 0.56 | 12178.70 | 01-SEP-04:02 | 1.76 |
October | 0.449098E+10 | 0.47 | 12178.70 | 02-OCT-04:02 | 1.77 |
November | 0.298364E+10 | 0.39 | 6123.98 | 20-NOV-07:03 | 1.15 |
December | 0.185124E+10 | 0.33 | 3530.59 | 04-DEC-14:10 | 0.83 |
Annual Sum or Average | 0.491826E+11 | 0.47 | |||
Minimum of Months | 0.159256E+10 | 0.33 | 2398.45 | 0.68 | |
Maximum of Months | 0.716594E+10 | 0.67 | 12178.70 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.11 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.90 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 57.54 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.38 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.44 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:10 | 2.06 | 2.06 | 57.00 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.98 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 57.45 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 57.26 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.17 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.33 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.35 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.90 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.54 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.18 | 57.18 | 1355.32 | 4624.86 | 13-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.18 | 57.18 | 1329.60 | 4561.34 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.84 | 57.84 | 1325.54 | 4380.94 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.63 | 57.63 | 1129.99 | 3969.11 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.43 | 58.43 | 1058.77 | 3581.29 | 02-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.11 | 57.11 | 1000.87 | 3262.77 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.09 | 57.09 | 897.97 | 3095.17 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.58 | 57.58 | 1019.38 | 3313.70 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.38 | 57.38 | 1040.59 | 3663.57 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.72 | 56.72 | 1150.60 | 4054.21 | 30-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.56 | 57.56 | 1276.06 | 4400.30 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.64 | 57.64 | 1298.80 | 4590.19 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 1156.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.72 | 56.72 | 897.97 | 3095.17 | ||
Maximum of Months | 0.00 | 0.00 | 58.43 | 58.43 | 1355.32 | 4624.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102606E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111173E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154237E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194374E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.324718E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.394436E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.479837E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.533773E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.408065E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.317048E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.217539E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131702E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.336951E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102606E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.533773E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.813190E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.937302E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.137792E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.179465E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.299331E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362682E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.438485E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.475695E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.356384E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.268425E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.175256E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105012E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.297358E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.813190E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.475695E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.810494E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.956733E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143899E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.192255E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.324226E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.392392E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.481214E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.516528E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.379470E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.279398E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.177549E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.105220E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.316887E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.810494E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.516528E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.225221E+10 | 0.328199E+11 | 0.195037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233706E+10 | 0.363245E+11 | 0.125976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317768E+10 | 0.497652E+11 | 52297701.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.370799E+10 | 0.614728E+11 | 1242861.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.589706E+10 | 0.964544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.641971E+10 | 0.119340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.650217E+10 | 0.147690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.688363E+10 | 0.165192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577482E+10 | 0.130460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.525355E+10 | 0.102790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433063E+10 | 0.715328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284409E+10 | 0.437871E+11 | 49169963.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553806E+11 | 0.105763E+13 | 0.423723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.225221E+10 | 0.328199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.688363E+10 | 0.165192E+12 | 0.195037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167349E+10 | 0.266295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187009E+10 | 0.310569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276892E+10 | 0.445871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336122E+10 | 0.569783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.547678E+10 | 0.892344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.602039E+10 | 0.110075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.646342E+10 | 0.133644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.716246E+10 | 0.143883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568836E+10 | 0.111948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475824E+10 | 0.859416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334538E+10 | 0.579254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201523E+10 | 0.354831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506040E+11 | 0.927386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167349E+10 | 0.266295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716246E+10 | 0.143883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159256E+10 | 0.265097E+11 | 39035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176719E+10 | 0.319087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262997E+10 | 0.471310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325614E+10 | 0.617763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.537894E+10 | 0.980308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.597354E+10 | 0.120377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.654317E+10 | 0.148103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.716594E+10 | 0.157873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.554928E+10 | 0.120538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449098E+10 | 0.905330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298364E+10 | 0.596737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185124E+10 | 0.357167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491826E+11 | 0.998170E+12 | 39035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159256E+10 | 0.265097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716594E+10 | 0.157873E+12 | 39035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.225221E+10 | 0.00 | 0.00 | 0.00 | 0.781340E+10 | 0.195037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233706E+10 | 0.00 | 0.00 | 0.00 | 0.865423E+10 | 0.125976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317768E+10 | 0.00 | 0.00 | 0.00 | 0.121937E+11 | 52297701.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.370799E+10 | 0.00 | 0.00 | 0.00 | 0.157282E+11 | 1242861.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.589706E+10 | 0.00 | 0.00 | 0.00 | 0.265747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.641971E+10 | 0.00 | 0.00 | 0.00 | 0.330238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.650217E+10 | 0.00 | 0.00 | 0.00 | 0.414815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.688363E+10 | 0.00 | 0.00 | 0.00 | 0.464937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577482E+10 | 0.00 | 0.00 | 0.00 | 0.350317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.525355E+10 | 0.00 | 0.00 | 0.00 | 0.264512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433063E+10 | 0.00 | 0.00 | 0.00 | 0.174232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284409E+10 | 0.00 | 0.00 | 0.00 | 0.102769E+11 | 49169963.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553806E+11 | 0.00 | 0.00 | 0.00 | 0.281146E+12 | 0.423723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.225221E+10 | 0.00 | 0.00 | 0.00 | 0.781340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.688363E+10 | 0.00 | 0.00 | 0.00 | 0.464937E+11 | 0.195037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167349E+10 | 0.00 | 0.00 | 0.00 | 0.645841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187009E+10 | 0.00 | 0.00 | 0.00 | 0.750293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276892E+10 | 0.00 | 0.00 | 0.00 | 0.110102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336122E+10 | 0.00 | 0.00 | 0.00 | 0.145852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.547678E+10 | 0.00 | 0.00 | 0.00 | 0.244563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.602039E+10 | 0.00 | 0.00 | 0.00 | 0.302478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.646342E+10 | 0.00 | 0.00 | 0.00 | 0.373851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.716246E+10 | 0.00 | 0.00 | 0.00 | 0.404070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568836E+10 | 0.00 | 0.00 | 0.00 | 0.299501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475824E+10 | 0.00 | 0.00 | 0.00 | 0.220843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334538E+10 | 0.00 | 0.00 | 0.00 | 0.141803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201523E+10 | 0.00 | 0.00 | 0.00 | 0.848595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506040E+11 | 0.00 | 0.00 | 0.00 | 0.246754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167349E+10 | 0.00 | 0.00 | 0.00 | 0.645841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716246E+10 | 0.00 | 0.00 | 0.00 | 0.404070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159256E+10 | 0.00 | 0.00 | 0.00 | 0.651233E+10 | 39035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176719E+10 | 0.00 | 0.00 | 0.00 | 0.780013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262997E+10 | 0.00 | 0.00 | 0.00 | 0.117600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.325614E+10 | 0.00 | 0.00 | 0.00 | 0.159694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.537894E+10 | 0.00 | 0.00 | 0.00 | 0.270437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.597354E+10 | 0.00 | 0.00 | 0.00 | 0.332657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.654317E+10 | 0.00 | 0.00 | 0.00 | 0.415782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.716594E+10 | 0.00 | 0.00 | 0.00 | 0.444869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.554928E+10 | 0.00 | 0.00 | 0.00 | 0.323977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449098E+10 | 0.00 | 0.00 | 0.00 | 0.234488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298364E+10 | 0.00 | 0.00 | 0.00 | 0.147712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185124E+10 | 0.00 | 0.00 | 0.00 | 0.867072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491826E+11 | 0.00 | 0.00 | 0.00 | 0.267705E+12 | 39035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159256E+10 | 0.00 | 0.00 | 0.00 | 0.651233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.716594E+10 | 0.00 | 0.00 | 0.00 | 0.444869E+11 | 39035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.431633E+09 | 0.277948E+09 | 0.00 | 27833584.50 | 0.130649E+09 | 0.00 | 0.302560E+10 | 0.00 | 0.37 |
February | 0.238659E+09 | 0.935478E+09 | 0.00 | 19503499.83 | 0.137230E+09 | 0.00 | 0.158266E+10 | 0.00 | 0.36 |
March | 0.212318E+09 | 0.191062E+10 | 0.00 | 17196475.26 | 0.179352E+09 | 0.00 | 0.121606E+10 | 0.00 | 0.36 |
April | 91322050.02 | 0.399467E+10 | 0.00 | 5609157.44 | 0.100240E+10 | 0.00 | 0.403085E+09 | 0.00 | 0.33 |
May | 24095216.12 | 0.812167E+10 | 0.00 | 1356434.05 | 0.275234E+10 | 0.00 | 71448571.07 | 0.00 | 0.33 |
June | 4122030.24 | 0.130576E+11 | 0.00 | 253795.16 | 0.441025E+10 | 0.00 | 11565346.53 | 0.00 | 0.34 |
July | 1822815.42 | 0.166512E+11 | 0.00 | 0.00 | 0.944088E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.190902E+11 | 0.00 | 0.00 | 0.965847E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 263615.37 | 0.145597E+11 | 0.00 | 90539.43 | 0.614645E+10 | 0.00 | 1546874.55 | 0.00 | 0.34 |
October | 37683197.94 | 0.908982E+10 | 0.00 | 1017747.64 | 0.361093E+10 | 0.00 | 57260977.35 | 0.00 | 0.33 |
November | 21147422.02 | 0.474758E+10 | 0.00 | 3603446.77 | 0.789096E+09 | 0.00 | 0.115654E+09 | 0.00 | 0.31 |
December | 0.216693E+09 | 0.134052E+10 | 0.00 | 20733863.60 | 0.345462E+09 | 0.00 | 0.142913E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.127976E+10 | 0.937770E+11 | 0.00 | 97198543.69 | 0.386035E+11 | 0.00 | 0.791402E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.277948E+09 | 0.00 | 0.00 | 0.130649E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.431633E+09 | 0.190902E+11 | 0.00 | 27833584.50 | 0.965847E+10 | 0.00 | 0.302560E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.811955E+09 | 0.272948E+09 | 0.00 | 13557797.86 | 0.197057E+09 | 0.00 | 0.184945E+10 | 0.00 | 0.31 |
February | 0.372445E+09 | 0.844991E+09 | 0.00 | 10934435.27 | 0.193345E+09 | 0.00 | 0.102489E+10 | 0.00 | 0.30 |
March | 0.281521E+09 | 0.173745E+10 | 0.00 | 11180498.45 | 0.221936E+09 | 0.00 | 0.874796E+09 | 0.00 | 0.31 |
April | 0.114073E+09 | 0.354670E+10 | 0.00 | 4391364.33 | 0.104498E+10 | 0.00 | 0.345766E+09 | 0.00 | 0.31 |
May | 29808682.37 | 0.755388E+10 | 0.00 | 1407154.75 | 0.267458E+10 | 0.00 | 75281695.24 | 0.00 | 0.32 |
June | 6920154.27 | 0.124954E+11 | 0.00 | 294115.09 | 0.430418E+10 | 0.00 | 13650200.61 | 0.00 | 0.33 |
July | 3427837.76 | 0.163163E+11 | 0.00 | 0.00 | 0.862553E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.189109E+11 | 0.00 | 0.00 | 0.777420E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 309815.72 | 0.141935E+11 | 0.00 | 143699.71 | 0.484160E+10 | 0.00 | 3570436.61 | 0.00 | 0.33 |
October | 44273851.07 | 0.866693E+10 | 0.00 | 1040703.89 | 0.276930E+10 | 0.00 | 51856903.42 | 0.00 | 0.31 |
November | 32519882.28 | 0.459038E+10 | 0.00 | 2536078.97 | 0.622712E+09 | 0.00 | 87018036.25 | 0.00 | 0.30 |
December | 0.340320E+09 | 0.137052E+10 | 0.00 | 11433700.93 | 0.338207E+09 | 0.00 | 0.876961E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.203757E+10 | 0.904999E+11 | 0.00 | 56919549.26 | 0.336076E+11 | 0.00 | 0.520325E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.272948E+09 | 0.00 | 0.00 | 0.193345E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.811955E+09 | 0.189109E+11 | 0.00 | 13557797.86 | 0.862553E+10 | 0.00 | 0.184945E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102306E+10 | 0.306323E+09 | 0.00 | 9214062.06 | 0.238686E+09 | 0.00 | 0.108510E+10 | 0.00 | 0.30 |
February | 0.495766E+09 | 0.868005E+09 | 0.00 | 8106117.02 | 0.251742E+09 | 0.00 | 0.611644E+09 | 0.00 | 0.30 |
March | 0.345009E+09 | 0.181473E+10 | 0.00 | 7814034.20 | 0.209654E+09 | 0.00 | 0.537381E+09 | 0.00 | 0.31 |
April | 0.143100E+09 | 0.361894E+10 | 0.00 | 2904700.88 | 0.101498E+10 | 0.00 | 0.177810E+09 | 0.00 | 0.31 |
May | 26870914.57 | 0.754983E+10 | 0.00 | 1013775.25 | 0.274532E+10 | 0.00 | 45215332.54 | 0.00 | 0.33 |
June | 6399927.34 | 0.124902E+11 | 0.00 | 335918.98 | 0.436497E+10 | 0.00 | 13271672.54 | 0.00 | 0.34 |
July | 1230938.29 | 0.164610E+11 | 0.00 | 0.00 | 0.927328E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.188595E+11 | 0.00 | 0.00 | 0.869396E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 550436.43 | 0.141252E+11 | 0.00 | 96680.06 | 0.512832E+10 | 0.00 | 2519691.19 | 0.00 | 0.34 |
October | 42304099.25 | 0.859097E+10 | 0.00 | 897485.35 | 0.270966E+10 | 0.00 | 27133826.24 | 0.00 | 0.31 |
November | 24868702.80 | 0.476848E+10 | 0.00 | 1717327.58 | 0.631574E+09 | 0.00 | 44355252.64 | 0.00 | 0.30 |
December | 0.427426E+09 | 0.135486E+10 | 0.00 | 7204699.94 | 0.513408E+09 | 0.00 | 0.436752E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.253659E+10 | 0.908081E+11 | 0.00 | 39304801.31 | 0.357756E+11 | 0.00 | 0.298118E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.306323E+09 | 0.00 | 0.00 | 0.209654E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.102306E+10 | 0.188595E+11 | 0.00 | 9214062.06 | 0.927328E+10 | 0.00 | 0.108510E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.283636E+09 | 67496192.20 | 0.00 | 1640857.73 | 52087461.06 | 0.00 | 0.157901E+09 | 0.00 | 0.30 |
February | 0.127944E+09 | 0.195018E+09 | 0.00 | 1841098.68 | 73446851.56 | 0.00 | 0.116533E+09 | 0.00 | 0.32 |
March | 91486790.04 | 0.526535E+09 | 0.00 | 1825419.78 | 44627991.48 | 0.00 | 0.108787E+09 | 0.00 | 0.38 |
April | 41125790.88 | 0.130273E+10 | 0.00 | 708546.49 | 0.147771E+09 | 0.00 | 28839190.71 | 0.00 | 0.43 |
May | 4890167.98 | 0.339025E+10 | 0.00 | 283935.30 | 0.273373E+09 | 0.00 | 11785609.35 | 0.00 | 0.54 |
June | 1191740.09 | 0.597595E+10 | 0.00 | 120319.93 | 0.408490E+09 | 0.00 | 3454805.93 | 0.00 | 0.60 |
July | 230100.37 | 0.858664E+10 | 0.00 | 4385.31 | 0.877052E+09 | 0.00 | 34539.63 | 0.00 | 0.66 |
August | 0.00 | 0.918588E+10 | 0.00 | 0.00 | 0.915535E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 116093.98 | 0.609465E+10 | 0.00 | 21108.45 | 0.533469E+09 | 0.00 | 549091.75 | 0.00 | 0.54 |
October | 9055587.47 | 0.306068E+10 | 0.00 | 299627.18 | 0.379016E+09 | 0.00 | 6770222.78 | 0.00 | 0.45 |
November | 6394988.65 | 0.133015E+10 | 0.00 | 437137.58 | 0.137074E+09 | 0.00 | 10751283.32 | 0.00 | 0.37 |
December | 0.106099E+09 | 0.320033E+09 | 0.00 | 1473847.70 | 0.113459E+09 | 0.00 | 78535328.51 | 0.00 | 0.31 |
Annual Sum or Average | 0.672169E+09 | 0.400360E+11 | 0.00 | 8656284.13 | 0.395540E+10 | 0.00 | 0.523941E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 67496192.20 | 0.00 | 0.00 | 44627991.48 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.283636E+09 | 0.918588E+10 | 0.00 | 1841098.68 | 0.915535E+09 | 0.00 | 0.157901E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142492E+09 | 64842555.73 | 0.00 | 1786345.74 | 26265027.86 | 0.00 | 0.183128E+09 | 0.00 | 0.36 |
February | 68853195.85 | 0.166008E+09 | 0.00 | 1774796.00 | 31372301.75 | 0.00 | 0.117118E+09 | 0.00 | 0.40 |
March | 51338532.77 | 0.438852E+09 | 0.00 | 1636839.01 | 20896352.18 | 0.00 | 95475263.33 | 0.00 | 0.48 |
April | 23194179.65 | 0.109464E+10 | 0.00 | 717935.54 | 64547140.10 | 0.00 | 30299317.25 | 0.00 | 0.56 |
May | 2365748.79 | 0.262913E+10 | 0.00 | 243954.58 | 0.145868E+09 | 0.00 | 9386885.39 | 0.00 | 0.67 |
June | 750902.94 | 0.448911E+10 | 0.00 | 99937.79 | 0.236492E+09 | 0.00 | 2463056.61 | 0.00 | 0.71 |
July | 145022.38 | 0.638570E+10 | 0.00 | 3746.87 | 0.504607E+09 | 0.00 | 29521.36 | 0.00 | 0.77 |
August | 0.00 | 0.698825E+10 | 0.00 | 0.00 | 0.518640E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 37344.32 | 0.475700E+10 | 0.00 | 14200.58 | 0.280681E+09 | 0.00 | 390720.13 | 0.00 | 0.66 |
October | 2452985.47 | 0.254724E+10 | 0.00 | 462819.00 | 0.176322E+09 | 0.00 | 11646311.10 | 0.00 | 0.56 |
November | 3195217.74 | 0.110163E+10 | 0.00 | 382140.78 | 64872519.25 | 0.00 | 8822112.10 | 0.00 | 0.46 |
December | 55229092.40 | 0.274507E+09 | 0.00 | 1355521.62 | 54532618.58 | 0.00 | 77696088.25 | 0.00 | 0.37 |
Annual Sum or Average | 0.350055E+09 | 0.309369E+11 | 0.00 | 8478237.52 | 0.212510E+10 | 0.00 | 0.536455E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 64842555.73 | 0.00 | 0.00 | 20896352.18 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.142492E+09 | 0.698825E+10 | 0.00 | 1786345.74 | 0.518640E+09 | 0.00 | 0.183128E+09 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211378E+09 | 0.177687E+09 | 0.00 | 4654211.20 | 22211345.04 | 0.00 | 0.460663E+09 | 0.00 | 0.50 |
February | 0.107924E+09 | 0.356383E+09 | 0.00 | 3996005.19 | 29854137.60 | 0.00 | 0.249768E+09 | 0.00 | 0.50 |
March | 85449895.68 | 0.726277E+09 | 0.00 | 2907689.41 | 30381691.38 | 0.00 | 0.170755E+09 | 0.00 | 0.50 |
April | 40544475.19 | 0.153401E+10 | 0.00 | 826601.12 | 0.119614E+09 | 0.00 | 31619034.19 | 0.00 | 0.49 |
May | 4928118.59 | 0.337398E+10 | 0.00 | 282974.35 | 0.281677E+09 | 0.00 | 11643062.95 | 0.00 | 0.54 |
June | 1191026.63 | 0.567992E+10 | 0.00 | 116253.08 | 0.440037E+09 | 0.00 | 3417667.50 | 0.00 | 0.57 |
July | 229962.61 | 0.844215E+10 | 0.00 | 4159.23 | 0.911225E+09 | 0.00 | 31406.73 | 0.00 | 0.65 |
August | 0.00 | 0.966247E+10 | 0.00 | 0.00 | 0.903510E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 59217.04 | 0.729319E+10 | 0.00 | 21995.69 | 0.450365E+09 | 0.00 | 615426.33 | 0.00 | 0.63 |
October | 6684311.66 | 0.437289E+10 | 0.00 | 851930.71 | 0.234570E+09 | 0.00 | 14839277.70 | 0.00 | 0.61 |
November | 5387770.83 | 0.217525E+10 | 0.00 | 871242.60 | 67062210.12 | 0.00 | 19511434.67 | 0.00 | 0.57 |
December | 81927671.82 | 0.690262E+09 | 0.00 | 3721064.27 | 49646221.02 | 0.00 | 0.200722E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.545704E+09 | 0.444845E+11 | 0.00 | 18254126.83 | 0.354015E+10 | 0.00 | 0.116358E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.177687E+09 | 0.00 | 0.00 | 22211345.04 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.211378E+09 | 0.966247E+10 | 0.00 | 4654211.20 | 0.911225E+09 | 0.00 | 0.460663E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165522E+09 | 66702314.10 | 0.00 | 1669945.50 | 25406985.20 | 0.00 | 0.160586E+09 | 0.00 | 0.36 |
February | 76578039.93 | 0.177333E+09 | 0.00 | 1796680.47 | 28996035.47 | 0.00 | 0.115521E+09 | 0.00 | 0.40 |
March | 56142036.26 | 0.455332E+09 | 0.00 | 1678148.35 | 17454787.43 | 0.00 | 0.105496E+09 | 0.00 | 0.49 |
April | 25219944.36 | 0.113287E+10 | 0.00 | 538398.24 | 64192588.40 | 0.00 | 20653900.13 | 0.00 | 0.54 |
May | 2820416.79 | 0.272491E+10 | 0.00 | 205208.52 | 0.137568E+09 | 0.00 | 8204584.27 | 0.00 | 0.66 |
June | 704192.68 | 0.462346E+10 | 0.00 | 80953.32 | 0.213588E+09 | 0.00 | 2371426.57 | 0.00 | 0.71 |
July | 145744.39 | 0.652486E+10 | 0.00 | 3556.55 | 0.474063E+09 | 0.00 | 24955.86 | 0.00 | 0.77 |
August | 0.00 | 0.716257E+10 | 0.00 | 0.00 | 0.500119E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 37530.24 | 0.497484E+10 | 0.00 | 14553.86 | 0.245446E+09 | 0.00 | 396017.12 | 0.00 | 0.65 |
October | 5656019.19 | 0.252537E+10 | 0.00 | 220608.82 | 0.171757E+09 | 0.00 | 4642227.52 | 0.00 | 0.55 |
November | 3997853.58 | 0.109403E+10 | 0.00 | 391392.04 | 63627688.16 | 0.00 | 10217511.90 | 0.00 | 0.46 |
December | 62997988.12 | 0.288887E+09 | 0.00 | 1390076.37 | 55403983.84 | 0.00 | 77669101.63 | 0.00 | 0.38 |
Annual Sum or Average | 0.399822E+09 | 0.317512E+11 | 0.00 | 7989522.02 | 0.199762E+10 | 0.00 | 0.505783E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 66702314.10 | 0.00 | 0.00 | 17454787.43 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.165522E+09 | 0.716257E+10 | 0.00 | 1796680.47 | 0.500119E+09 | 0.00 | 0.160586E+09 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244684E+09 | 49310925.54 | 0.00 | 2813464.31 | 29327469.70 | 0.00 | 0.269276E+09 | 0.00 | 0.28 |
February | 0.130209E+09 | 0.171186E+09 | 0.00 | 2255604.49 | 39092040.50 | 0.00 | 0.151676E+09 | 0.00 | 0.28 |
March | 0.106230E+09 | 0.409916E+09 | 0.00 | 1959047.39 | 39980272.92 | 0.00 | 0.117883E+09 | 0.00 | 0.31 |
April | 48468083.40 | 0.101098E+10 | 0.00 | 677413.90 | 0.208489E+09 | 0.00 | 34371743.12 | 0.00 | 0.35 |
May | 6446081.62 | 0.288423E+10 | 0.00 | 261485.12 | 0.368852E+09 | 0.00 | 13726766.05 | 0.00 | 0.45 |
June | 867661.50 | 0.520554E+10 | 0.00 | 64538.40 | 0.492818E+09 | 0.00 | 2551535.27 | 0.00 | 0.51 |
July | 299731.75 | 0.779918E+10 | 0.00 | 3362.75 | 0.105617E+10 | 0.00 | 80665.19 | 0.00 | 0.59 |
August | 0.00 | 0.889569E+10 | 0.00 | 0.00 | 0.114512E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 66508.18 | 0.601150E+10 | 0.00 | 27937.68 | 0.782974E+09 | 0.00 | 402015.22 | 0.00 | 0.53 |
October | 7300457.90 | 0.313883E+10 | 0.00 | 253855.68 | 0.548400E+09 | 0.00 | 13671259.34 | 0.00 | 0.45 |
November | 9439817.02 | 0.125888E+10 | 0.00 | 636950.16 | 0.167097E+09 | 0.00 | 16506541.78 | 0.00 | 0.36 |
December | 98215875.66 | 0.283539E+09 | 0.00 | 2914118.08 | 72979504.43 | 0.00 | 0.176097E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.652227E+09 | 0.371188E+11 | 0.00 | 11867777.95 | 0.495130E+10 | 0.00 | 0.796242E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 49310925.54 | 0.00 | 0.00 | 29327469.70 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.244684E+09 | 0.889569E+10 | 0.00 | 2914118.08 | 0.114512E+10 | 0.00 | 0.269276E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108931E+09 | 43957108.95 | 0.00 | 3021483.72 | 17124963.35 | 0.00 | 0.293584E+09 | 0.00 | 0.35 |
February | 65692936.03 | 0.139089E+09 | 0.00 | 2330412.54 | 18014013.40 | 0.00 | 0.156299E+09 | 0.00 | 0.36 |
March | 55057751.35 | 0.347181E+09 | 0.00 | 1900408.88 | 21211919.69 | 0.00 | 0.112684E+09 | 0.00 | 0.40 |
April | 26302113.28 | 0.909142E+09 | 0.00 | 739119.36 | 80110441.20 | 0.00 | 37208561.20 | 0.00 | 0.46 |
May | 3084615.51 | 0.236000E+10 | 0.00 | 258650.66 | 0.167196E+09 | 0.00 | 11655550.56 | 0.00 | 0.57 |
June | 550175.46 | 0.405722E+10 | 0.00 | 51610.82 | 0.244720E+09 | 0.00 | 1891529.20 | 0.00 | 0.62 |
July | 160999.93 | 0.607830E+10 | 0.00 | 5001.01 | 0.530905E+09 | 0.00 | 98678.96 | 0.00 | 0.71 |
August | 0.00 | 0.700762E+10 | 0.00 | 0.00 | 0.604069E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 42172.17 | 0.486035E+10 | 0.00 | 20546.51 | 0.374214E+09 | 0.00 | 299179.47 | 0.00 | 0.65 |
October | 1404367.36 | 0.266969E+10 | 0.00 | 319865.24 | 0.229214E+09 | 0.00 | 16555463.22 | 0.00 | 0.56 |
November | 4493387.72 | 0.102934E+10 | 0.00 | 564225.61 | 73532473.80 | 0.00 | 15836273.48 | 0.00 | 0.44 |
December | 46725247.28 | 0.225831E+09 | 0.00 | 2653342.85 | 44668645.03 | 0.00 | 0.165204E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.312445E+09 | 0.297277E+11 | 0.00 | 11864667.20 | 0.240498E+10 | 0.00 | 0.811316E+09 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 43957108.95 | 0.00 | 0.00 | 17124963.35 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.108931E+09 | 0.700762E+10 | 0.00 | 3021483.72 | 0.604069E+09 | 0.00 | 0.293584E+09 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192740E+09 | 0.120527E+09 | 0.00 | 5193480.07 | 12607548.14 | 77922479.19 | 0.417008E+09 | 0.00 | 0.42 |
February | 0.103289E+09 | 0.322685E+09 | 0.00 | 4085439.87 | 16923223.81 | 35956613.03 | 0.238814E+09 | 0.00 | 0.43 |
March | 95597492.85 | 0.701549E+09 | 0.00 | 2939913.92 | 25875739.81 | 13700744.87 | 0.160177E+09 | 0.00 | 0.45 |
April | 53466342.03 | 0.151508E+10 | 0.00 | 861009.57 | 0.166666E+09 | 53192.55 | 33592131.31 | 0.00 | 0.47 |
May | 6526804.40 | 0.379943E+10 | 0.00 | 345133.86 | 0.378367E+09 | 0.00 | 15716180.59 | 0.00 | 0.58 |
June | 867944.36 | 0.646159E+10 | 0.00 | 73765.87 | 0.566232E+09 | 0.00 | 2800941.83 | 0.00 | 0.65 |
July | 299829.47 | 0.995460E+10 | 0.00 | 3336.38 | 0.108603E+10 | 0.00 | 80658.19 | 0.00 | 0.73 |
August | 0.00 | 0.122838E+11 | 0.00 | 0.00 | 0.106551E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 43934.39 | 0.904059E+10 | 0.00 | 37845.82 | 0.575736E+09 | 0.00 | 560448.07 | 0.00 | 0.75 |
October | 3889358.93 | 0.545726E+10 | 0.00 | 542739.98 | 0.274880E+09 | 0.00 | 22643910.55 | 0.00 | 0.70 |
November | 11316114.11 | 0.238304E+10 | 0.00 | 973213.29 | 69084993.18 | 0.00 | 21666672.52 | 0.00 | 0.59 |
December | 87934647.88 | 0.579864E+09 | 0.00 | 5001994.13 | 39145637.55 | 16529445.29 | 0.275162E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.555971E+09 | 0.526200E+11 | 0.00 | 20057872.78 | 0.427706E+10 | 0.144162E+09 | 0.118822E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.120527E+09 | 0.00 | 0.00 | 12607548.14 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.192740E+09 | 0.122838E+11 | 0.00 | 5193480.07 | 0.108603E+10 | 77922479.19 | 0.417008E+09 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128154E+09 | 46492145.74 | 0.00 | 2732607.35 | 16303939.96 | 0.00 | 0.258385E+09 | 0.00 | 0.34 |
February | 74421449.68 | 0.153568E+09 | 0.00 | 2168930.11 | 15514996.70 | 0.00 | 0.145346E+09 | 0.00 | 0.36 |
March | 56541132.11 | 0.377896E+09 | 0.00 | 1861496.40 | 13919200.39 | 0.00 | 0.119303E+09 | 0.00 | 0.41 |
April | 24956667.05 | 0.963054E+09 | 0.00 | 549226.80 | 68517114.46 | 0.00 | 30307189.94 | 0.00 | 0.45 |
May | 3501338.14 | 0.249159E+10 | 0.00 | 208546.77 | 0.132291E+09 | 0.00 | 10297661.81 | 0.00 | 0.56 |
June | 459649.07 | 0.426448E+10 | 0.00 | 51719.19 | 0.187783E+09 | 0.00 | 2055670.16 | 0.00 | 0.63 |
July | 160738.09 | 0.624457E+10 | 0.00 | 3346.24 | 0.492240E+09 | 0.00 | 97878.97 | 0.00 | 0.71 |
August | 0.00 | 0.723688E+10 | 0.00 | 0.00 | 0.551834E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 27803.99 | 0.511804E+10 | 0.00 | 21469.45 | 0.319124E+09 | 0.00 | 327127.02 | 0.00 | 0.65 |
October | 4527637.16 | 0.271896E+10 | 0.00 | 195017.19 | 0.206252E+09 | 0.00 | 9800416.94 | 0.00 | 0.55 |
November | 5075540.71 | 0.106675E+10 | 0.00 | 536459.49 | 64707308.81 | 0.00 | 14138670.36 | 0.00 | 0.44 |
December | 59199627.44 | 0.245232E+09 | 0.00 | 2499270.92 | 42700303.41 | 0.00 | 0.150157E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.357026E+09 | 0.309275E+11 | 0.00 | 10828089.90 | 0.211119E+10 | 0.00 | 0.740216E+09 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 46492145.74 | 0.00 | 0.00 | 13919200.39 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.128154E+09 | 0.723688E+10 | 0.00 | 2732607.35 | 0.551834E+09 | 0.00 | 0.258385E+09 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322718E+09 | 67009956.29 | 0.00 | 1988507.25 | 36456773.39 | 0.00 | 0.200784E+09 | 0.00 | 0.30 |
February | 0.154716E+09 | 0.200910E+09 | 0.00 | 1971252.08 | 50915750.27 | 0.00 | 0.136964E+09 | 0.00 | 0.32 |
March | 0.113346E+09 | 0.522904E+09 | 0.00 | 2085866.46 | 43566814.56 | 0.00 | 0.131757E+09 | 0.00 | 0.38 |
April | 50754374.13 | 0.128271E+10 | 0.00 | 834875.09 | 0.181857E+09 | 0.00 | 45321868.28 | 0.00 | 0.43 |
May | 7017677.10 | 0.339709E+10 | 0.00 | 370149.67 | 0.299756E+09 | 0.00 | 17268114.04 | 0.00 | 0.54 |
June | 1266515.57 | 0.602739E+10 | 0.00 | 99867.39 | 0.402455E+09 | 0.00 | 3497769.25 | 0.00 | 0.59 |
July | 553326.31 | 0.848192E+10 | 0.00 | 13981.82 | 0.815249E+09 | 0.00 | 222304.70 | 0.00 | 0.63 |
August | 0.00 | 0.917936E+10 | 0.00 | 0.00 | 0.835753E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 65318.14 | 0.603991E+10 | 0.00 | 28871.11 | 0.585962E+09 | 0.00 | 782979.41 | 0.00 | 0.53 |
October | 10428567.76 | 0.301718E+10 | 0.00 | 280703.38 | 0.450664E+09 | 0.00 | 10189511.54 | 0.00 | 0.44 |
November | 12356493.18 | 0.128638E+10 | 0.00 | 481384.94 | 0.138216E+09 | 0.00 | 13430035.55 | 0.00 | 0.36 |
December | 0.135741E+09 | 0.318705E+09 | 0.00 | 1880327.27 | 80658978.39 | 0.00 | 0.112493E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.808963E+09 | 0.398215E+11 | 0.00 | 10035786.46 | 0.392151E+10 | 0.00 | 0.672710E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 67009956.29 | 0.00 | 0.00 | 36456773.39 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.322718E+09 | 0.917936E+10 | 0.00 | 2085866.46 | 0.835753E+09 | 0.00 | 0.200784E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161309E+09 | 51882648.18 | 0.00 | 1912747.47 | 20206064.45 | 0.00 | 0.209772E+09 | 0.00 | 0.34 |
February | 82296900.94 | 0.151528E+09 | 0.00 | 1814090.73 | 21926534.13 | 0.00 | 0.131658E+09 | 0.00 | 0.37 |
March | 62713186.82 | 0.401321E+09 | 0.00 | 1796658.25 | 22776522.44 | 0.00 | 0.112005E+09 | 0.00 | 0.44 |
April | 28102532.34 | 0.103472E+10 | 0.00 | 809365.23 | 76939681.27 | 0.00 | 44937576.70 | 0.00 | 0.53 |
May | 3547353.85 | 0.255943E+10 | 0.00 | 325873.98 | 0.156500E+09 | 0.00 | 14272806.46 | 0.00 | 0.64 |
June | 792311.34 | 0.439018E+10 | 0.00 | 81234.41 | 0.239789E+09 | 0.00 | 2466512.28 | 0.00 | 0.68 |
July | 340445.43 | 0.616518E+10 | 0.00 | 12972.97 | 0.460554E+09 | 0.00 | 200405.95 | 0.00 | 0.73 |
August | 0.00 | 0.681305E+10 | 0.00 | 0.00 | 0.473021E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 41565.06 | 0.459753E+10 | 0.00 | 19602.40 | 0.293336E+09 | 0.00 | 508882.62 | 0.00 | 0.63 |
October | 3064938.08 | 0.242018E+10 | 0.00 | 418783.23 | 0.202637E+09 | 0.00 | 15328832.05 | 0.00 | 0.53 |
November | 6007043.60 | 0.988578E+09 | 0.00 | 426007.78 | 67237939.00 | 0.00 | 12785976.53 | 0.00 | 0.43 |
December | 70400128.76 | 0.235955E+09 | 0.00 | 1609855.07 | 44234018.60 | 0.00 | 0.103750E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.418616E+09 | 0.298095E+11 | 0.00 | 9227191.51 | 0.207916E+10 | 0.00 | 0.647686E+09 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 51882648.18 | 0.00 | 0.00 | 20206064.45 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.161309E+09 | 0.681305E+10 | 0.00 | 1912747.47 | 0.473021E+09 | 0.00 | 0.209772E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231121E+09 | 0.168082E+09 | 0.00 | 5176325.79 | 12327424.12 | 0.00 | 0.532449E+09 | 0.00 | 0.49 |
February | 0.128654E+09 | 0.362439E+09 | 0.00 | 4066586.72 | 13490609.00 | 0.00 | 0.278385E+09 | 0.00 | 0.49 |
March | 0.105093E+09 | 0.738909E+09 | 0.00 | 3190447.73 | 25754178.50 | 0.00 | 0.196066E+09 | 0.00 | 0.50 |
April | 49591325.41 | 0.154509E+10 | 0.00 | 926828.92 | 0.138466E+09 | 0.00 | 48529947.70 | 0.00 | 0.49 |
May | 7100867.25 | 0.338154E+10 | 0.00 | 362219.29 | 0.315826E+09 | 0.00 | 16861942.92 | 0.00 | 0.54 |
June | 1264250.38 | 0.570217E+10 | 0.00 | 95835.66 | 0.457117E+09 | 0.00 | 3453363.79 | 0.00 | 0.57 |
July | 552336.68 | 0.832744E+10 | 0.00 | 12853.76 | 0.858133E+09 | 0.00 | 214242.36 | 0.00 | 0.63 |
August | 0.00 | 0.969742E+10 | 0.00 | 0.00 | 0.819602E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 72343.57 | 0.736431E+10 | 0.00 | 30260.18 | 0.452120E+09 | 0.00 | 789290.76 | 0.00 | 0.62 |
October | 6384655.86 | 0.441721E+10 | 0.00 | 792344.68 | 0.266957E+09 | 0.00 | 19537708.94 | 0.00 | 0.61 |
November | 10161077.79 | 0.212423E+10 | 0.00 | 897323.90 | 51749002.03 | 0.00 | 24279496.84 | 0.00 | 0.56 |
December | 0.104790E+09 | 0.653684E+09 | 0.00 | 4382924.42 | 35432354.90 | 0.00 | 0.256214E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.644785E+09 | 0.444825E+11 | 0.00 | 19933951.06 | 0.344698E+10 | 0.00 | 0.137678E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.168082E+09 | 0.00 | 0.00 | 12327424.12 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.231121E+09 | 0.969742E+10 | 0.00 | 5176325.79 | 0.858133E+09 | 0.00 | 0.532449E+09 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184601E+09 | 63452307.77 | 0.00 | 1925072.89 | 18501982.12 | 0.00 | 0.197282E+09 | 0.00 | 0.36 |
February | 91178756.20 | 0.180746E+09 | 0.00 | 1840095.67 | 18086099.99 | 0.00 | 0.131990E+09 | 0.00 | 0.40 |
March | 68696823.32 | 0.463983E+09 | 0.00 | 1836488.16 | 15797122.10 | 0.00 | 0.122080E+09 | 0.00 | 0.49 |
April | 30540661.65 | 0.116487E+10 | 0.00 | 602814.78 | 66197964.26 | 0.00 | 31841594.12 | 0.00 | 0.54 |
May | 4348539.15 | 0.281599E+10 | 0.00 | 257047.34 | 0.131474E+09 | 0.00 | 11523322.04 | 0.00 | 0.66 |
June | 805751.54 | 0.475449E+10 | 0.00 | 66978.88 | 0.203890E+09 | 0.00 | 2346525.32 | 0.00 | 0.71 |
July | 340363.98 | 0.655934E+10 | 0.00 | 11076.52 | 0.426812E+09 | 0.00 | 178238.57 | 0.00 | 0.75 |
August | 0.00 | 0.728314E+10 | 0.00 | 0.00 | 0.437911E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 41555.11 | 0.505024E+10 | 0.00 | 19954.11 | 0.238615E+09 | 0.00 | 514029.38 | 0.00 | 0.65 |
October | 6424719.48 | 0.255217E+10 | 0.00 | 204157.50 | 0.189654E+09 | 0.00 | 6965493.13 | 0.00 | 0.55 |
November | 7725065.71 | 0.107391E+10 | 0.00 | 419362.53 | 56424086.71 | 0.00 | 11993382.19 | 0.00 | 0.45 |
December | 79856765.32 | 0.278539E+09 | 0.00 | 1674765.50 | 44288035.55 | 0.00 | 0.104366E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.474560E+09 | 0.322409E+11 | 0.00 | 8857813.87 | 0.184765E+10 | 0.00 | 0.621080E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 63452307.77 | 0.00 | 0.00 | 15797122.10 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.184601E+09 | 0.728314E+10 | 0.00 | 1925072.89 | 0.437911E+09 | 0.00 | 0.197282E+09 | 0.00 | 0.77 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.147636E+12 | 0.276228E+10 | 0.00 | 0.231572E+11 | 0.106743E+12 |
February | 0.162126E+12 | 0.113851E+10 | 0.00 | 0.750154E+10 | 0.123247E+12 |
March | 0.198200E+12 | -790721390.5 | 0.00 | -0.506104E+10 | 0.176447E+12 |
April | 0.207913E+12 | -0.480601E+10 | 0.00 | -0.390100E+11 | 0.226510E+12 |
May | 0.215358E+12 | -0.113686E+11 | 0.00 | -0.958161E+11 | 0.361794E+12 |
June | 0.204941E+12 | -0.188015E+11 | 0.00 | -0.158578E+12 | 0.446329E+12 |
July | 0.201809E+12 | -0.254748E+11 | 0.00 | -0.220037E+12 | 0.549882E+12 |
August | 0.196310E+12 | -0.273055E+11 | 0.00 | -0.237100E+12 | 0.598335E+12 |
September | 0.176237E+12 | -0.200548E+11 | 0.00 | -0.182365E+12 | 0.460325E+12 |
October | 0.153830E+12 | -0.116845E+11 | 0.00 | -0.111223E+12 | 0.351249E+12 |
November | 0.126806E+12 | -0.510387E+10 | 0.00 | -0.458111E+11 | 0.235507E+12 |
December | 0.127286E+12 | 0.334807E+09 | 0.00 | -0.173258E+10 | 0.142421E+12 |
Annual Sum or Average | 0.211845E+13 | -0.121155E+12 | 0.00 | -0.106608E+13 | 0.377879E+13 |
Minimum of Months | 0.126806E+12 | -0.273055E+11 | 0.00 | -0.237100E+12 | 0.106743E+12 |
Maximum of Months | 0.215358E+12 | 0.276228E+10 | 0.00 | 0.231572E+11 | 0.598335E+12 |