Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:32:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1769.67 | 355.20 | 355.20 |
Net Site Energy | 1609.77 | 323.11 | 323.11 |
Total Source Energy | 5365.06 | 1076.85 | 1076.85 |
Net Source Energy | 4858.66 | 975.21 | 975.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 6.23 | 2.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 642.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 175.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 112.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1654.70 | 114.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 6.23 | 2.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 642.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 175.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 136.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 112.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 6.23 | 2.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 642.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 175.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 33.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 136.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 112.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 157.69 | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 332.12 | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 157.69 | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 332.12 | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 166.952 | 10.09 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.05 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 159.898 | 9.66 |
Electricity Coming From Utility | 1495.013 | 90.35 |
Surplus Electricity Going To Utility | 0.215 | 0.01 |
Net Electricity From Utility | 1494.798 | 90.34 |
Total On-Site and Utility Electric Sources | 1654.696 | 100.00 |
Total Electricity End Uses | 1654.696 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 43.83 |
Time Setpoint Not Met During Occupied Cooling | 612.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1586.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.1264 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.1264 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.1264 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.1264 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.1264 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.1264 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.1264 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.1264 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.1264 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.1264 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.1264 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.1264 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.1264 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.1264 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.1264 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.1264 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.1264 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.1264 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.1264 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.1264 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.1264 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.1264 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.1264 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.1264 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.1264 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.1264 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.1264 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.1264 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.1264 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.1264 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.1264 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.1264 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.1264 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 6.1264 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.1264 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JUN-14:09 | 05-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 8313.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101436.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14675.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 37678.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 824.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25716.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9143.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 180338.26 | 17456.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 8313.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 101436.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 14675.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 3151.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 824.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 25716.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9143.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 19.74 | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2036.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 556.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 431.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 122.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5240.42 | 124.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 3.96 | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 408.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 111.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 86.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1051.83 | 25.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 3.96 | 0.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 408.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 111.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 86.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1051.83 | 25.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.45 | 0.306522 | 0.261000 | 0.638152 | 0.817392 | 0.500000 | 0.001243 |
CORE_MID VAV BOX COMPONENT | 2.11 | 0.355983 | 0.303000 | 0.637909 | 0.949288 | 0.500000 | 0.001070 |
CORE_TOP VAV BOX COMPONENT | 2.43 | 0.307872 | 0.262000 | 0.637788 | 0.820993 | 0.500000 | 0.001238 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.912274 | 0.173184 | 0.147000 | 0.134104 | 0.461825 | 0.500000 | 0.002200 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.691513 | 0.144642 | 0.123000 | 0.085056 | 0.385712 | 0.500000 | 0.002634 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.927223 | 0.170392 | 0.145000 | 0.134447 | 0.454380 | 0.500000 | 0.002236 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.773575 | 0.129290 | 0.110000 | 0.085093 | 0.344772 | 0.500000 | 0.002947 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.733546 | 0.215381 | 0.183000 | 0.134239 | 0.574349 | 0.500000 | 0.001769 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.596126 | 0.167786 | 0.143000 | 0.085246 | 0.447431 | 0.500000 | 0.002271 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.747104 | 0.211472 | 0.180000 | 0.134479 | 0.563926 | 0.500000 | 0.001802 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.624884 | 0.160054 | 0.136000 | 0.084984 | 0.426811 | 0.500000 | 0.002380 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.769804 | 0.205236 | 0.174000 | 0.133946 | 0.547297 | 0.500000 | 0.001856 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.634756 | 0.420200 | 0.500000 | 0.002418 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.786047 | 0.200995 | 0.171000 | 0.134414 | 0.535987 | 0.500000 | 0.001896 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.675765 | 0.148003 | 0.126000 | 0.085146 | 0.394675 | 0.500000 | 0.002574 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20775.87 |
CORE_MID VAV BOX REHEAT COIL | 20767.97 |
CORE_TOP VAV BOX REHEAT COIL | 27320.28 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 10907.99 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7101.03 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 10901.54 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7107.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7033.72 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4664.98 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7033.71 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4677.09 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8316.24 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5484.58 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8304.74 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5496.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.57 | 1.08 | 5.15 | 1.14 | 4.83 | 4.83 | 0.300000 | 0.236653 | 4.83 |
PACU_VAV_MID | 2.49 | 1.08 | 4.97 | 1.27 | 4.61 | 4.61 | 0.300000 | 0.276255 | 4.61 |
PACU_VAV_TOP | 2.87 | 1.08 | 5.74 | 2.00 | 5.64 | 5.64 | 0.300000 | 0.355619 | 5.64 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.83 |
PACU_VAV_MID_OA_CONTROLLER | 4.61 |
PACU_VAV_TOP_OA_CONTROLLER | 5.64 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.83 | 106288.07 | 0.740733 | 1.61 | 35425.81 | 0.740733 |
PACU_VAV_MID COOLING COIL | 4.61 | 102443.18 | 0.736945 | 1.54 | 34144.31 | 0.736945 |
PACU_VAV_TOP COOLING COIL | 5.64 | 120100.13 | 0.751579 | 1.88 | 40029.37 | 0.751579 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 2554.28 |
PACU_VAV_MID HEATING COIL | 3870.84 |
PACU_VAV_TOP HEATING COIL | 225.50 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.83 |
PACU_VAV_MID FAN | 4.61 |
PACU_VAV_TOP FAN | 5.64 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.126 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.964 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.126 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.126 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.126 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.126 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.196 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6025.565 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6025.565 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6025.565 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6025.565 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6025.565 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6025.565 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1270.242 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1270.242 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 804.168 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 804.168 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1270.242 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1270.242 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 804.115 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 804.115 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1270.242 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1270.242 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 804.168 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 804.168 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1270.242 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1270.242 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 804.115 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 804.115 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1270.242 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1270.242 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 804.168 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 804.168 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1270.242 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1270.242 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 804.115 | 6.126 | 113.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 804.115 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9610E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.9970E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3027E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3326E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7712E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7943E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6735E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6886E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5627E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6655E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.4045E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8650E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8135E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6249E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9381E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0999E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9625E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0063E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3044E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3428E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7729E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8022E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6734E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6884E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5076E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5376E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2512E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3353E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3320E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1387E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4526E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6264E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0821E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0960E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8790E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8891E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6926E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6963E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1204E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1256E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6205E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6539E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2206E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2474E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9418E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9611E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6734E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6884E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3994E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3511E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8695E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0403E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6987E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.2036E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9381E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0999E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6200E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6533E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2198E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2455E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9403E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9556E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6735E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6886E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6049E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1307E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1690E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8472E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4465E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7423E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4526E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6265E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4951E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5231E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1692E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1970E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1430E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1583E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1205E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1258E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.9431E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.6071E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.7259E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.8596E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.3448E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4033E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.3524E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.5637E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3668E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4557E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1266E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2623E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.2333E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0790E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3883E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5876E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7611E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7921E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.1944E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4243E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0199E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0720E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3524E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5637E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4908E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0673E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0766E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7967E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3730E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7000E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3883E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5876E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.9428E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.6066E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.7254E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.8590E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.3443E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4028E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.3521E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.5635E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3667E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4555E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1264E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2621E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.2330E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0788E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3880E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5874E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7612E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7920E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.1944E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4242E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0198E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0719E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3521E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5635E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4907E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0671E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0766E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7966E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3728E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6999E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3880E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5875E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 33092.64739 | 33092.64739 | 2.44503 | 2.44503 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5130.45153 | 5130.45153 | 0.22165 | 0.42469 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28515.52564 | 28515.52564 | 2.10531 | 2.10531 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 9864.15708 | 9864.15708 | 0.42605 | 0.42605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32659.23178 | 32659.23178 | 2.43430 | 2.43430 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 19282.90899 | 19282.90899 | 0.83917 | 0.83917 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12239.42743 | 12239.42743 | 0.91227 | 0.91227 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8338.83827 | 8338.83827 | 0.33505 | 0.33505 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9277.62338 | 9277.62338 | 0.69151 | 0.69151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5423.90092 | 5423.90092 | 0.21812 | 0.21812 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12439.98671 | 12439.98671 | 0.92722 | 0.92722 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8334.08559 | 8334.08559 | 0.33485 | 0.33485 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10378.62858 | 10378.62858 | 0.77358 | 0.77358 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5428.28402 | 5428.28402 | 0.21830 | 0.21830 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 9841.53023 | 9841.53023 | 0.73355 | 0.73355 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 4956.09910 | 4956.09910 | 0.21605 | 0.21605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7997.87419 | 7997.87419 | 0.59613 | 0.59613 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3286.05064 | 3286.05064 | 0.14329 | 0.14329 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10023.43529 | 10023.43529 | 0.74710 | 0.74710 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 4956.08710 | 4956.08710 | 0.21605 | 0.21605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8383.71502 | 8383.71502 | 0.62488 | 0.62488 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3294.52570 | 3294.52570 | 0.14366 | 0.14366 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10327.97819 | 10327.97819 | 0.76980 | 0.76980 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 5854.73586 | 5854.73586 | 0.25544 | 0.25544 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8516.15700 | 8516.15700 | 0.63476 | 0.63476 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 39.28400 | 9.15337E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3860.50072 | 3860.50072 | 0.16846 | 0.16846 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10545.90024 | 10545.90024 | 0.78605 | 0.78605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 5846.67640 | 5846.67640 | 0.25509 | 0.25509 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9066.34456 | 9066.34456 | 0.67576 | 0.67576 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3868.74594 | 3868.74594 | 0.16883 | 0.16883 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 84069.07 | 4.83297 | 4.83297 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 7328.57 | 1.14374 | 1.14374 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 21:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 81026.74 | 4.61120 | 4.61120 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 7096.58 | 1.27387 | 1.27387 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 94461.00 | 5.63558 | 5.63558 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 7027.01 | 2.00412 | 2.00412 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.44503 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30652 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63815 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81739 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24298E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20775.86582 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.10531 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35598 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63791 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94929 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07028E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20767.96728 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.43430 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30787 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63779 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82099 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23753E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27320.27984 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91227 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17318 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13410 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46183 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19997E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10907.99162 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69151 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14464 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12300 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50561E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38571 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63409E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7101.02984 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92722 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17039 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14500 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13445 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45438 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23602E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10901.53674 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77358 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12929 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50933E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34477 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94687E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7106.99788 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73355 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21538 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13424 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57435 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76896E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7033.72328 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59613 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16779 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14300 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52460E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44743 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27074E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4664.98006 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74710 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21147 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13448 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56393 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80166E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7033.70614 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62488 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16005 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13600 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49842E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42681 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38045E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4677.08982 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76980 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20524 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17400 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13395 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54730 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85640E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8316.23898 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63476 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42020 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41789E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5484.57708 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78605 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20100 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17100 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13441 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53599 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89557E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8304.73645 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67576 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14800 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51463E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39467 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57427E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5496.34775 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.57334 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07710 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.14669 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14374 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.83297 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.83297 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.23665 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.48584 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07647 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.97168 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27387 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.61120 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.61120 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.27625 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.86944 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07649 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.73889 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00412 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.63558 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.63558 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.35562 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.83297 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.61120 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.63558 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.83297 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.83297 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106288.07082 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74073 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.61083 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35425.81401 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74073 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 2554.27626 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.83297 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.61120 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.61120 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102443.17576 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73694 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53691 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34144.31048 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73694 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 3870.83614 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.61120 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.63558 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.63558 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 120100.12618 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75158 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.87834 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40029.37206 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75158 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 225.50183 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.63558 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 105687.04 | 360619.14 | 11.95 | 3.06 | 3.42 | 3.61 | 3.76 | 10.43 | 11.68 | 12.30 | 12.84 | 5.4488 | 4.3403 | 2.9217 | 1.2111 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 101900.18 | 347697.84 | 11.97 | 3.06 | 3.43 | 3.61 | 3.77 | 10.44 | 11.70 | 12.33 | 12.86 | 5.1988 | 4.1386 | 2.7851 | 1.1599 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 119286.00 | 407020.71 | 11.88 | 3.04 | 3.40 | 3.58 | 3.75 | 10.38 | 11.61 | 12.22 | 12.80 | 6.3537 | 5.0639 | 3.4088 | 1.4001 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.1326096691E-003 | 4.9013076130E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1637830257E-002 | 6.3517806869E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4356018621E-002 | 6.2570444798E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3016290052E-002 | 6.0483379421E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.2715478644E-003 | 5.2000402903E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.8735720273E-002 | 1.5260365498E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.7380935899E-002 | 2.6888800056E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.4437811541E-002 | 3.5192666009E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.3692558131E-002 | 5.4782606651E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.6690919715E-002 | 4.5043302771E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7117934483E-002 | 1.7372944010E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.2916096726E-002 | 3.0708189721E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.2679648765E-002 | 3.8296830137E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.9796342348E-002 | 3.1386701983E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.2014632742E-002 | 1.8097135868E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.9759232271E-002 | 3.6311329091E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.7318804562E-002 | 4.6752154792E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9767231109E-002 | 3.6286783208E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2471.17 | -55.0 | 0.00 | -692.6 | 3095.57 | 4819.13 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.229 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.229 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.229 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
North Total or Average | 195.79 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.865 | 0.230 | 0.253 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.1264 | 983.54 | 6025.56 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.13 | 0.0000 | Y | 42.00 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.1264 | 983.54 | 6025.56 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.13 | 0.0000 | Y | 42.00 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.1264 | 983.54 | 6025.56 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.13 | 0.0000 | Y | 42.00 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.1264 | 207.34 | 1270.24 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.44 | 0.0000 | Y | 5.11 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.1264 | 131.26 | 804.17 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.33 | 0.0000 | Y | 3.22 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.1264 | 207.34 | 1270.24 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.18 | 0.0000 | Y | 5.05 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.1264 | 131.25 | 804.12 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.33 | 0.0000 | Y | 3.22 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.1264 | 207.34 | 1270.24 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.39 | 0.0000 | Y | 5.10 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.1264 | 131.26 | 804.17 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.30 | 0.0000 | Y | 3.22 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.1264 | 207.34 | 1270.24 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.15 | 0.0000 | Y | 5.04 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.1264 | 131.25 | 804.12 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.29 | 0.0000 | Y | 3.21 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.1264 | 207.34 | 1270.24 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.44 | 0.0000 | Y | 5.11 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.1264 | 131.26 | 804.17 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.33 | 0.0000 | Y | 3.22 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.1264 | 207.34 | 1270.24 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.18 | 0.0000 | Y | 5.05 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.1264 | 131.25 | 804.12 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.33 | 0.0000 | Y | 3.22 |
Interior Lighting Total | 6.1264 | 4982.19 | 30523.00 | 175.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1270.24 | 487.14 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1270.24 | 177.20 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 804.17 | 308.40 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 804.17 | 112.18 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1270.24 | 487.14 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1270.24 | 177.20 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 804.12 | 308.38 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 804.12 | 112.17 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1270.24 | 487.14 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1270.24 | 177.20 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 804.17 | 308.40 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 804.17 | 112.18 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1270.24 | 487.14 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1270.24 | 177.20 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 804.12 | 308.38 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 804.12 | 112.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1270.24 | 487.14 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1270.24 | 177.20 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 804.17 | 308.40 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 804.17 | 112.18 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1270.24 | 487.14 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1270.24 | 177.20 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 804.12 | 308.38 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 804.12 | 112.17 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 41.75 | 41.75 | 4.25 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.75 | 62.75 | 3.30 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.75 | 46.80 | 26.37 | |
Exterior Lighting Total | 3824.74 | 33.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106288.07 | 78731.11 | 27556.96 | 0.74 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102443.18 | 75494.97 | 26948.21 | 0.74 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 120100.13 | 90264.77 | 29835.36 | 0.75 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 105687.0 | 3.06 | 10.43 | N/A | N/A | 11.95 | |
PACU_VAV_MID COOLING COIL | 101900.2 | 3.06 | 10.44 | N/A | N/A | 11.97 | |
PACU_VAV_TOP COOLING COIL | 119286.0 | 3.04 | 10.38 | N/A | N/A | 11.88 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20775.87 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 20767.97 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 27320.28 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10907.99 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7101.03 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10901.54 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7107.00 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7033.72 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4664.98 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7033.71 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4677.09 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8316.24 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5484.58 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8304.74 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5496.35 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 2554.28 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 3870.84 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 225.50 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.83 | 10579.42 | 2189.01 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.61 | 10093.97 | 2189.01 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.64 | 12256.75 | 2174.89 | 1.00 | 1.13 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105687.04 | 3.06 | 10.43 | 11.95 | 5.4488 | 3.42 | 11.68 | 4.3403 | 3.61 | 12.30 | 2.9217 | 3.76 | 12.84 | 1.2111 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101900.18 | 3.06 | 10.44 | 11.97 | 5.1988 | 3.43 | 11.70 | 4.1386 | 3.61 | 12.33 | 2.7851 | 3.77 | 12.86 | 1.1599 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 119286.00 | 3.04 | 10.38 | 11.88 | 6.3537 | 3.40 | 11.61 | 5.0639 | 3.58 | 12.22 | 3.4088 | 3.75 | 12.80 | 1.4001 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 33092.65 | 33092.65 | 33.65 | 2.445 | 2.445 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 28515.53 | 28515.53 | 28.99 | 2.105 | 2.105 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 32659.23 | 32659.23 | 33.21 | 2.434 | 2.434 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00887 | 41.81 | 0.00916 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12239.43 | 12239.43 | 59.03 | 0.912 | 0.912 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00872 | 41.61 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9277.62 | 9277.62 | 70.68 | 0.692 | 0.692 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00868 | 39.53 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12439.99 | 12439.99 | 60.00 | 0.927 | 0.927 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 24.00 | 24.00 | 0.00871 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10378.63 | 10378.63 | 79.07 | 0.774 | 0.774 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00866 | 41.16 | 0.00916 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9841.53 | 9841.53 | 47.47 | 0.734 | 0.734 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00876 | 41.71 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7997.87 | 7997.87 | 60.93 | 0.596 | 0.596 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00871 | 39.53 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10023.44 | 10023.44 | 48.34 | 0.747 | 0.747 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00876 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8383.72 | 8383.72 | 63.87 | 0.625 | 0.625 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00870 | 41.03 | 0.00916 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10327.98 | 10327.98 | 49.81 | 0.770 | 0.770 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00875 | 41.61 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8516.16 | 8516.16 | 64.88 | 0.635 | 0.635 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 24.00 | 24.00 | 0.00870 | 39.28 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10545.90 | 10545.90 | 50.86 | 0.786 | 0.786 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00875 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9066.34 | 9066.34 | 69.08 | 0.676 | 0.676 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00868 | 41.16 | 0.00916 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5130.45 | 5130.45 | 5.22 | 0.222 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_MID | 9864.16 | 9864.16 | 10.03 | 0.426 | 0.426 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_TOP | 19282.91 | 19282.91 | 19.61 | 0.839 | 0.839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8338.84 | 8338.84 | 40.22 | 0.335 | 0.335 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00789 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5423.90 | 5423.90 | 41.32 | 0.218 | 0.218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00790 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8334.09 | 8334.09 | 40.20 | 0.335 | 0.335 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00789 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5428.28 | 5428.28 | 41.36 | 0.218 | 0.218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00790 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 4956.10 | 4956.10 | 23.90 | 0.216 | 0.216 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3286.05 | 3286.05 | 25.03 | 0.143 | 0.143 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 4956.09 | 4956.09 | 23.90 | 0.216 | 0.216 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3294.53 | 3294.53 | 25.10 | 0.144 | 0.144 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 5854.74 | 5854.74 | 28.24 | 0.255 | 0.255 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 3860.50 | 3860.50 | 29.41 | 0.168 | 0.168 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 5846.68 | 5846.68 | 28.20 | 0.255 | 0.255 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3868.75 | 3868.75 | 29.48 | 0.169 | 0.169 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.83 | 4.83 | 1.14 | 1.14 | 4.8330 | 1.1437 | 4.8330 | 0.2367 | 0.3000 |
PACU_VAV_MID | 4.61 | 4.61 | 1.27 | 1.27 | 4.6112 | 1.2739 | 4.6112 | 0.2763 | 0.3000 |
PACU_VAV_TOP | 5.64 | 5.64 | 2.00 | 2.00 | 5.6356 | 2.0041 | 5.6356 | 0.3556 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20775.866 | 20775.866 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20775.87 | 13826.37 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 5130.45 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 20767.967 | 20767.967 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20767.97 | 13870.46 | 0.426045 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 9864.16 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27320.280 | 27320.280 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27320.28 | 27320.28 | 0.839170 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 19282.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 10907.992 | 10907.992 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 10907.99 | 10907.99 | 0.335050 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00789403 | 50.6925 | 8338.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7101.030 | 7101.030 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7101.03 | 7101.03 | 0.218115 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00789670 | 50.7101 | 5423.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 10901.537 | 10901.537 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 10901.54 | 10901.54 | 0.334852 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00789378 | 50.6909 | 8334.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7106.998 | 7106.998 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7107.00 | 7107.00 | 0.218299 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00789704 | 50.7123 | 5428.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7033.723 | 7033.723 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7033.72 | 7033.72 | 0.216048 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792707 | 49.9593 | 4956.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4664.980 | 4664.980 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4664.98 | 4664.98 | 0.143290 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792782 | 49.9640 | 3286.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7033.706 | 7033.706 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7033.71 | 7033.71 | 0.216047 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792707 | 49.9593 | 4956.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4677.090 | 4677.090 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4677.09 | 4677.09 | 0.143662 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792808 | 49.9656 | 3294.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8316.239 | 8316.239 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8316.24 | 8316.24 | 0.255442 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791615 | 49.8915 | 5854.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5484.577 | 5484.577 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5484.58 | 5484.58 | 0.168464 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791722 | 49.8983 | 3860.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8304.736 | 8304.736 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8304.74 | 8304.74 | 0.255088 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791597 | 49.8905 | 5846.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5496.348 | 5496.348 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5496.35 | 5496.35 | 0.168826 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791749 | 49.8999 | 3868.75 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 106288.071 | 78731.111 | 4.832968 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 98076.72 | 92642.28 | 4.832968 | 27.56 | 17.67 | 0.00888358 | 10.97 | 10.97 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 19.7829 | 24.00 | 0.00881583 | 46.2392 | 64770.52 | 0.00 | 109597.27 | 79055.59 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 2554.276 | 2554.276 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 21:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2554.28 | 2554.28 | 1.449891 | 11.31 | 9.39 | 0.00672411 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 65.9429 | 21.00 | 0.00797994 | 50.2879 | 15094.61 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 102443.176 | 75494.968 | 4.611202 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 94705.52 | 89286.98 | 4.611202 | 27.74 | 17.74 | 0.00890111 | 10.97 | 10.97 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 20.7343 | 24.00 | 0.00883368 | 46.3316 | 61680.40 | 0.00 | 105632.67 | 75815.03 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 3870.836 | 3870.836 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3870.84 | 3870.84 | 1.383361 | 10.43 | 8.89 | 0.00663429 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 69.1143 | 19.60 | 0.00784910 | 53.9457 | 17722.69 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 120100.126 | 90264.771 | 5.635575 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 110365.91 | 104750.84 | 5.635575 | 27.04 | 17.46 | 0.00883948 | 10.99 | 10.99 | 0.00850000 | 41.90 | 0.00915774 | 22.24 | 16.9654 | 24.00 | 0.00877428 | 46.0243 | 75436.79 | 0.00 | 123839.35 | 90561.68 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 225.502 | 225.502 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 225.50 | 225.50 | 1.690673 | 12.69 | 10.18 | 0.00689967 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 56.5515 | 19.08 | 0.00797314 | 56.6014 | 18247.05 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20775.866 | 20775.866 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20775.87 | 13826.37 | 1.0000 | 0.49849623 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20775.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.69 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 5130.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 20767.967 | 20767.967 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20767.97 | 13870.46 | 1.0000 | 0.50008580 | 0.426045 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20767.97 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.83 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 9864.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 27320.280 | 27320.280 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27320.28 | 27320.28 | 1.0000 | 0.98500601 | 0.839170 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27320.28 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 19282.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10907.992 | 10907.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 10907.99 | 10907.99 | 1.0000 | 0.39327698 | 0.335050 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10907.99 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00789403 | 20.70 | 0.00789403 | 50.6925 | 8338.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7101.030 | 7101.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7101.03 | 7101.03 | 1.0000 | 0.25602070 | 0.218115 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7101.03 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00789670 | 20.70 | 0.00789670 | 50.7101 | 5423.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10901.537 | 10901.537 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 10901.54 | 10901.54 | 1.0000 | 0.39304426 | 0.334852 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10901.54 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00789378 | 20.70 | 0.00789378 | 50.6909 | 8334.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7106.998 | 7106.998 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7107.00 | 7107.00 | 1.0000 | 0.25623587 | 0.218299 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7107.00 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00789704 | 20.70 | 0.00789704 | 50.7123 | 5428.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7033.723 | 7033.723 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7033.72 | 7033.72 | 1.0000 | 0.25359402 | 0.216048 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7033.72 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00792707 | 21.00 | 0.00792707 | 49.9593 | 4956.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4664.980 | 4664.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4664.98 | 4664.98 | 1.0000 | 0.16819130 | 0.143290 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4664.98 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00792782 | 21.00 | 0.00792782 | 49.9640 | 3286.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7033.706 | 7033.706 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7033.71 | 7033.71 | 1.0000 | 0.25359341 | 0.216047 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7033.71 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00792707 | 21.00 | 0.00792707 | 49.9593 | 4956.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4677.090 | 4677.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4677.09 | 4677.09 | 1.0000 | 0.16862791 | 0.143662 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4677.09 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00792808 | 21.00 | 0.00792808 | 49.9656 | 3294.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8316.239 | 8316.239 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8316.24 | 8316.24 | 1.0000 | 0.29983387 | 0.255442 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8316.24 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00791615 | 21.00 | 0.00791615 | 49.8915 | 5854.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5484.577 | 5484.577 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5484.58 | 5484.58 | 1.0000 | 0.19774107 | 0.168464 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5484.58 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00791722 | 21.00 | 0.00791722 | 49.8983 | 3860.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8304.736 | 8304.736 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8304.74 | 8304.74 | 1.0000 | 0.29941916 | 0.255088 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8304.74 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00791597 | 21.00 | 0.00791597 | 49.8905 | 5846.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5496.348 | 5496.348 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5496.35 | 5496.35 | 1.0000 | 0.19816545 | 0.168826 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5496.35 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00791749 | 21.00 | 0.00791749 | 49.8999 | 3868.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106288.071 | 78731.111 | 4.832968 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3541 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.832968 | 5.67286815 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 98076.72 | 92642.28 | 0.9227 | 5.67286815 | 4.832968 | 27.56 | 17.67 | 0.00888358 | 50369.7 | 10.97 | 10.97 | 0.00850000 | 32458.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10579.421 | 87497.30 | 42.00 | 0.00915790 | 22.26 | 0.95610000 | 19.7829 | 24.00 | 0.00881583 | 24.00 | 0.00881583 | 46.2392 | 64770.52 | 0.00 | 109597.27 | 79055.59 | 5.44883274 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.46 | 12.45 | 0.00898700 | 35208.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 2554.276 | 2554.276 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.832968 | 5.67286815 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 21:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2554.28 | 2554.28 | 1.0000 | 1.70186045 | 1.449891 | 11.31 | 9.39 | 0.00672411 | 28319.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2554.28 | 6.30 | 0.00607234 | 6.30 | 0.95610000 | 65.9429 | 21.00 | 0.00798608 | 21.00 | 0.00797994 | 50.2879 | 15094.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102443.176 | 75494.968 | 4.611202 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3867 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.611202 | 5.41256239 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 94705.52 | 89286.98 | 0.9245 | 5.41256239 | 4.611202 | 27.74 | 17.74 | 0.00890111 | 50596.9 | 10.97 | 10.97 | 0.00850000 | 32458.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10093.973 | 84611.55 | 42.00 | 0.00915790 | 22.26 | 0.95610000 | 20.7343 | 24.00 | 0.00883368 | 24.00 | 0.00883368 | 46.3316 | 61680.40 | 0.00 | 105632.67 | 75815.03 | 5.19880709 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.39 | 12.37 | 0.00893591 | 35003.8 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3870.836 | 3870.836 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.611202 | 5.41256239 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3870.84 | 3870.84 | 1.0000 | 1.62376872 | 1.383361 | 10.43 | 8.89 | 0.00663429 | 27198.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3870.84 | 6.30 | 0.00607234 | 6.30 | 0.95610000 | 69.1143 | 19.66 | 0.00789178 | 19.60 | 0.00784910 | 53.9457 | 17722.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 120100.126 | 90264.771 | 5.635575 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2722 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.635575 | 6.61495651 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 110365.91 | 104750.84 | 0.9189 | 6.61495651 | 5.635575 | 27.04 | 17.46 | 0.00883948 | 49725.6 | 10.99 | 10.99 | 0.00850000 | 32470.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12256.747 | 98109.16 | 41.90 | 0.00915774 | 22.24 | 0.95610000 | 16.9654 | 24.00 | 0.00877428 | 24.00 | 0.00877428 | 46.0243 | 75436.79 | 0.00 | 123839.35 | 90561.68 | 6.35371573 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.72 | 12.69 | 0.00913115 | 35831.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 225.502 | 225.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.635575 | 6.61495651 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 225.50 | 225.50 | 1.0000 | 1.98448695 | 1.690673 | 12.69 | 10.18 | 0.00689967 | 30166.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 225.50 | 6.30 | 0.00607234 | 6.30 | 0.95610000 | 56.5515 | 21.00 | 0.00797649 | 19.08 | 0.00797314 | 56.6014 | 18247.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4321.83 | 341.67 | 12.67 |
CORE_MID | 3917.67 | 1047.33 | 15.17 |
CORE_TOP | 3730.67 | 1516.67 | 47.83 |
PERIMETER_TOP_ZN_3 | 3854.00 | 2141.33 | 550.67 |
PERIMETER_TOP_ZN_2 | 4090.00 | 1881.50 | 579.83 |
PERIMETER_TOP_ZN_1 | 4380.00 | 1578.67 | 576.67 |
PERIMETER_TOP_ZN_4 | 4073.17 | 1967.00 | 626.17 |
PERIMETER_BOT_ZN_3 | 3780.50 | 1822.33 | 273.50 |
PERIMETER_BOT_ZN_2 | 4189.33 | 1419.33 | 382.33 |
PERIMETER_BOT_ZN_1 | 4537.33 | 2049.33 | 1219.17 |
PERIMETER_BOT_ZN_4 | 4152.50 | 1523.00 | 391.67 |
PERIMETER_MID_ZN_3 | 3840.83 | 1891.33 | 386.67 |
PERIMETER_MID_ZN_2 | 3445.00 | 1514.00 | 468.67 |
PERIMETER_MID_ZN_1 | 4484.17 | 1314.50 | 466.17 |
PERIMETER_MID_ZN_4 | 4104.83 | 1708.00 | 483.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5048.33 | 3226.17 | 1586.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.50 | 0.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.33 | 80.33 | 0.33 | 48.17 |
PERIMETER_TOP_ZN_2 | 0.33 | 110.83 | 0.33 | 74.67 |
PERIMETER_TOP_ZN_1 | 0.17 | 113.50 | 0.17 | 78.83 |
PERIMETER_TOP_ZN_4 | 0.33 | 116.33 | 0.33 | 64.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 34.67 | 0.00 | 23.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 79.67 | 0.00 | 58.67 |
PERIMETER_BOT_ZN_1 | 43.50 | 478.83 | 43.50 | 461.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 87.33 | 0.00 | 48.00 |
PERIMETER_MID_ZN_3 | 0.00 | 49.67 | 0.00 | 32.83 |
PERIMETER_MID_ZN_2 | 0.00 | 87.17 | 0.00 | 67.33 |
PERIMETER_MID_ZN_1 | 0.00 | 90.83 | 0.00 | 71.67 |
PERIMETER_MID_ZN_4 | 0.00 | 88.67 | 0.00 | 51.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 43.83 | 705.17 | 43.83 | 612.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 0.484 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.432 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.429 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.575 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.728 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 0.795 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.720 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.514 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.666 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 0.792 | 1.246 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.659 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.576 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.695 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 0.803 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.730 | 0.029 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.59 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.62 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8095765.08 | 0.00 | 8095765.08 | 0.00 | 8095765.08 | 13393058.27 | 6781.08 | 636.61 | 1342.31 | 393.58 |
CORE_MID | 7245877.92 | 0.00 | 7245877.92 | 0.00 | 7245877.92 | 13393058.27 | 7350.93 | 997.18 | 411.89 | 364.47 |
CORE_TOP | 7261917.23 | 0.00 | 7261917.23 | 0.00 | 7261917.23 | 13393058.27 | 7430.86 | 1129.29 | 199.85 | 420.08 |
PERIMETER_TOP_ZN_3 | 2028205.59 | 0.00 | 2028205.59 | 173897.85 | 2202103.44 | 2823374.22 | 4817.87 | 1063.34 | 2878.79 | 420.08 |
PERIMETER_TOP_ZN_2 | 1602879.63 | 0.00 | 1602879.63 | 115931.20 | 1718810.84 | 1787429.43 | 3915.97 | 1080.85 | 3763.18 | 420.08 |
PERIMETER_TOP_ZN_1 | 2753647.69 | 0.00 | 2753647.69 | 173897.85 | 2927545.54 | 2823374.22 | 3705.31 | 1046.24 | 4008.45 | 420.08 |
PERIMETER_TOP_ZN_4 | 1604403.91 | 0.00 | 1604403.91 | 115931.20 | 1720335.11 | 1787312.18 | 4102.52 | 1081.29 | 3576.19 | 420.08 |
PERIMETER_BOT_ZN_3 | 1809371.73 | 0.00 | 1809371.73 | 92461.45 | 1901833.18 | 2823374.22 | 5962.72 | 619.17 | 2178.12 | 393.58 |
PERIMETER_BOT_ZN_2 | 1464105.08 | 0.00 | 1464105.08 | 61640.59 | 1525745.68 | 1787429.43 | 4340.77 | 719.38 | 3699.85 | 393.58 |
PERIMETER_BOT_ZN_1 | 2720707.78 | 0.00 | 2720707.78 | 4106049.28 | 6826757.07 | 2823374.22 | 4247.66 | 616.02 | 3896.32 | 393.58 |
PERIMETER_BOT_ZN_4 | 1462878.52 | 0.00 | 1462878.52 | 61640.59 | 1524519.12 | 1787312.18 | 4741.18 | 603.00 | 3415.82 | 393.58 |
PERIMETER_MID_ZN_3 | 2003692.26 | 0.00 | 2003692.26 | 144757.29 | 2148449.55 | 2823374.22 | 5058.92 | 914.74 | 2786.34 | 364.47 |
PERIMETER_MID_ZN_2 | 1513617.31 | 0.00 | 1513617.31 | 96504.28 | 1610121.60 | 1601953.02 | 3943.30 | 937.50 | 3879.21 | 1273.47 |
PERIMETER_MID_ZN_1 | 2753199.33 | 0.00 | 2753199.33 | 144757.29 | 2897956.62 | 2823374.22 | 3787.40 | 930.67 | 4041.94 | 364.47 |
PERIMETER_MID_ZN_4 | 1605588.11 | 0.00 | 1605588.11 | 96504.28 | 1702092.39 | 1787312.18 | 4200.57 | 975.68 | 3583.74 | 364.47 |
Total Facility | 45925857.20 | 0.00 | 45925857.20 | 5383973.17 | 51309830.37 | 67658168.57 | 8358.87 | 1835.92 | 4943.18 | 1483.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3514 | 0.0000 | 0.3514 | 0.0000 | 0.3514 | 0.4247 | 4086.57 | 517.62 | 1338.82 |
CORE_MID | 0.3139 | 0.0000 | 0.3139 | 0.0000 | 0.3139 | 0.4247 | 4678.70 | 854.36 | 409.95 |
CORE_TOP | 0.3113 | 0.0000 | 0.3113 | 0.0000 | 0.3113 | 0.4247 | 4749.92 | 994.45 | 198.63 |
PERIMETER_TOP_ZN_3 | 0.0879 | 0.0000 | 0.0879 | 0.0050 | 0.0928 | 0.0895 | 2167.16 | 995.43 | 2780.41 |
PERIMETER_TOP_ZN_2 | 0.0704 | 0.0000 | 0.0704 | 0.0033 | 0.0737 | 0.0567 | 1326.11 | 968.13 | 3648.76 |
PERIMETER_TOP_ZN_1 | 0.1216 | 0.0000 | 0.1216 | 0.0050 | 0.1266 | 0.0895 | 1133.13 | 910.85 | 3899.02 |
PERIMETER_TOP_ZN_4 | 0.0696 | 0.0000 | 0.0696 | 0.0033 | 0.0729 | 0.0567 | 1557.91 | 965.98 | 3419.11 |
PERIMETER_BOT_ZN_3 | 0.0786 | 0.0000 | 0.0786 | 0.0026 | 0.0812 | 0.0895 | 3259.32 | 546.82 | 2136.86 |
PERIMETER_BOT_ZN_2 | 0.0644 | 0.0000 | 0.0644 | 0.0018 | 0.0661 | 0.0567 | 1747.39 | 572.60 | 3623.00 |
PERIMETER_BOT_ZN_1 | 0.1209 | 0.0000 | 0.1209 | 0.1902 | 0.3111 | 0.0895 | 1606.46 | 508.62 | 3827.92 |
PERIMETER_BOT_ZN_4 | 0.0636 | 0.0000 | 0.0636 | 0.0018 | 0.0654 | 0.0567 | 2125.83 | 532.92 | 3284.26 |
PERIMETER_MID_ZN_3 | 0.0879 | 0.0000 | 0.0879 | 0.0041 | 0.0920 | 0.0895 | 2354.58 | 861.70 | 2726.72 |
PERIMETER_MID_ZN_2 | 0.0672 | 0.0000 | 0.0672 | 0.0028 | 0.0700 | 0.0567 | 1319.89 | 820.34 | 2893.77 |
PERIMETER_MID_ZN_1 | 0.1228 | 0.0000 | 0.1228 | 0.0041 | 0.1270 | 0.0895 | 1171.64 | 797.32 | 3974.04 |
PERIMETER_MID_ZN_4 | 0.0705 | 0.0000 | 0.0705 | 0.0028 | 0.0733 | 0.0567 | 1656.71 | 828.18 | 3458.11 |
Total Facility | 2.0019 | 0.0000 | 2.0019 | 0.2268 | 2.2287 | 2.1513 | 5551.52 | 1549.60 | 4685.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21428193.45 | 0.00 | 21428193.45 | 22614548.33 | 3384.15 | 1.07 | 5374.78 | 393.58 |
PACU_VAV_MID | 20834607.21 | 0.00 | 20834607.21 | 22429071.92 | 3412.95 | 0.77 | 5346.28 | 364.47 |
PACU_VAV_TOP | 21012419.50 | 0.00 | 21012419.50 | 22614548.33 | 3366.77 | 1.54 | 5391.69 | 420.08 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9353 | 0.0000 | 0.9353 | 0.7171 | 950.83 | 0.62 | 4991.54 |
PACU_VAV_MID | 0.9122 | 0.0000 | 0.9122 | 0.7084 | 950.20 | 0.70 | 4992.10 |
PACU_VAV_TOP | 0.9103 | 0.0000 | 0.9103 | 0.7171 | 955.80 | 1.01 | 4986.19 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 591.60 | 0.00 | 0.00 | 0.00 | 0.00 | 4817.70 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 270.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5112.31 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 251.93 | 0.00 | 0.00 | 0.00 | 0.00 | 5184.81 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2381 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0921 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1476 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0771 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1240 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0768 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1654.70 | 11283.65 | 04-JUL-17:10 | 180338.26 | 12-JUN-14:10 |
Electricity:Building | 823.51 | 11115.10 | 21-MAY-17:10 | 58207.48 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 220.48 | 3058.24 | 01-JAN-00:10 | 16440.80 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 823.51 | 11115.10 | 21-MAY-17:10 | 58207.48 | 11-OCT-07:10 |
InteriorLights:Electricity | 175.76 | 815.21 | 01-JAN-09:30 | 17769.69 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 42.00 | 204.56 | 01-JAN-00:10 | 3682.52 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 175.76 | 815.21 | 01-JAN-09:30 | 17769.69 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 175.76 | 815.21 | 01-JAN-09:30 | 17769.69 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 42.00 | 204.56 | 01-JAN-00:10 | 3682.52 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 175.76 | 815.21 | 01-JAN-09:30 | 17769.69 | 11-OCT-07:10 |
Electricity:Zone:CORE_MID | 157.42 | 2036.10 | 01-JAN-00:10 | 10490.84 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 42.00 | 204.56 | 01-JAN-00:10 | 3682.52 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 42.00 | 204.56 | 01-JAN-00:10 | 3682.52 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 157.42 | 2036.10 | 01-JAN-00:10 | 10490.84 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 42.00 | 204.56 | 01-JAN-00:10 | 3682.52 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 42.00 | 204.56 | 01-JAN-00:10 | 3682.52 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.44 | 406.67 | 26-MAR-17:10 | 2125.12 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.11 | 20.57 | 01-JAN-09:30 | 689.88 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.11 | 20.57 | 01-JAN-09:30 | 689.88 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.62 | 257.44 | 21-MAY-17:10 | 1344.20 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.22 | 13.02 | 01-JAN-07:50 | 435.62 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.22 | 13.02 | 01-JAN-07:50 | 435.62 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.38 | 406.67 | 12-MAR-17:10 | 2121.50 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.05 | 20.57 | 01-JAN-08:00 | 686.26 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.05 | 20.57 | 01-JAN-08:00 | 686.26 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.62 | 257.44 | 12-MAR-17:10 | 1347.27 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.22 | 13.02 | 01-JAN-09:30 | 438.70 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.22 | 13.02 | 01-JAN-09:30 | 438.70 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.43 | 406.67 | 19-MAR-17:10 | 2121.82 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.10 | 20.57 | 01-JAN-09:20 | 686.58 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.10 | 20.57 | 01-JAN-09:20 | 686.58 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.62 | 257.44 | 30-APR-17:10 | 1342.42 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.22 | 13.02 | 01-JAN-07:50 | 433.85 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.22 | 13.02 | 01-JAN-07:50 | 433.85 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.37 | 406.67 | 12-MAR-17:10 | 2118.02 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.04 | 20.57 | 01-JAN-08:00 | 682.78 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.04 | 20.57 | 01-JAN-08:00 | 682.78 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.62 | 257.44 | 12-MAR-17:10 | 1345.65 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.21 | 13.02 | 01-JAN-09:20 | 437.08 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.21 | 13.02 | 01-JAN-09:20 | 437.08 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.44 | 406.67 | 26-MAR-17:10 | 2125.12 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.11 | 20.57 | 01-JAN-09:30 | 689.87 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.11 | 20.57 | 01-JAN-09:30 | 689.87 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.62 | 257.44 | 21-MAY-17:10 | 1344.19 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.22 | 13.02 | 01-JAN-07:50 | 435.62 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.22 | 13.02 | 01-JAN-07:50 | 435.62 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.38 | 406.67 | 12-MAR-17:10 | 2121.49 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.05 | 20.57 | 01-JAN-08:00 | 686.25 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.05 | 20.57 | 01-JAN-08:00 | 686.25 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.62 | 257.44 | 12-MAR-17:10 | 1347.26 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.22 | 13.02 | 01-JAN-09:30 | 438.69 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.22 | 13.02 | 01-JAN-09:30 | 438.69 | 11-OCT-07:10 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 159.90 | -0.00 | 03-JAN-17:30 | 26709.59 | 04-JUN-12:20 |
ElectricityProduced:Plant | 159.90 | -0.00 | 03-JAN-17:30 | 26709.59 | 04-JUN-12:20 |
Photovoltaic:ElectricityProduced | 166.95 | 0.00 | 01-JAN-00:10 | 27821.33 | 04-JUN-12:20 |
PowerConversion:ElectricityProduced | -7.05 | -1111.73 | 04-JUN-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 797.11 | 168.34 | 01-JAN-00:10 | 127977.15 | 12-JUN-14:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.91 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.91 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 1495.01 | 0.00 | 08-JAN-10:50 | 162864.60 | 12-JUN-16:00 |
ElectricityPurchased:Plant | 1495.01 | 0.00 | 08-JAN-10:50 | 162864.60 | 12-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1495.01 | 0.00 | 08-JAN-10:50 | 162864.60 | 12-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 1495.01 | 0.00 | 08-JAN-10:50 | 162864.60 | 12-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.22 | 0.00 | 01-JAN-00:10 | 8772.37 | 04-JUL-12:30 |
ElectricitySurplusSold:Plant | 0.22 | 0.00 | 01-JAN-00:10 | 8772.37 | 04-JUL-12:30 |
Cogeneration:ElectricitySurplusSold | 0.22 | 0.00 | 01-JAN-00:10 | 8772.37 | 04-JUL-12:30 |
General:Cogeneration:ElectricitySurplusSold | 0.22 | 0.00 | 01-JAN-00:10 | 8772.37 | 04-JUL-12:30 |
ElectricityNet:Facility | 1494.80 | -8772.37 | 04-JUL-12:30 | 162864.60 | 12-JUN-16:00 |
ElectricityNet:Plant | 1494.80 | -8772.37 | 04-JUL-12:30 | 162864.60 | 12-JUN-16:00 |
Cogeneration:ElectricityNet | 1494.80 | -8772.37 | 04-JUL-12:30 | 162864.60 | 12-JUN-16:00 |
General:Cogeneration:ElectricityNet | 1494.80 | -8772.37 | 04-JUL-12:30 | 162864.60 | 12-JUN-16:00 |
Heating:Electricity | 6.23 | 0.00 | 01-JAN-00:10 | 101690.96 | 02-JAN-07:10 |
General:Heating:Electricity | 6.23 | 0.00 | 01-JAN-00:10 | 101690.96 | 02-JAN-07:10 |
Fans:Electricity | 136.36 | 0.00 | 01-JAN-00:10 | 25716.37 | 12-JUN-14:10 |
General:Fans:Electricity | 136.36 | 0.00 | 01-JAN-00:10 | 25716.37 | 12-JUN-14:10 |
ExteriorLights:Electricity | 33.93 | 0.00 | 01-JAN-07:20 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 33.93 | 0.00 | 01-JAN-07:20 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 642.89 | 0.00 | 01-JAN-00:10 | 104855.53 | 12-JUN-15:30 |
General:Cooling:Electricity | 642.89 | 0.00 | 01-JAN-00:10 | 104855.53 | 12-JUN-15:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 4.94 | 0.00 | 01-JAN-00:10 | 499.33 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 114.98 | 1886.44 | 14-APR-17:10 | 17456.59 | 05-JAN-08:10 |
NaturalGas:HVAC | 2.25 | 0.00 | 01-JAN-00:10 | 8313.27 | 02-JAN-06:10 |
Heating:NaturalGas | 2.25 | 0.00 | 01-JAN-00:10 | 8313.27 | 02-JAN-06:10 |
General:Heating:NaturalGas | 2.25 | 0.00 | 01-JAN-00:10 | 8313.27 | 02-JAN-06:10 |
NaturalGas:Plant | 112.73 | 1886.44 | 02-JAN-06:20 | 9696.57 | 19-JAN-12:10 |
WaterSystems:NaturalGas | 112.73 | 1886.44 | 02-JAN-06:20 | 9696.57 | 19-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 112.73 | 1886.44 | 02-JAN-06:20 | 9696.57 | 19-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4076.76 | 0.00 | 01-JAN-00:10 | 491659.39 | 22-JUN-15:40 |
EnergyTransfer:Building | 1581.65 | 0.00 | 01-JAN-00:10 | 190321.76 | 12-JUN-15:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 247.49 | 0.00 | 01-JAN-00:10 | 23252.46 | 05-SEP-07:40 |
Heating:EnergyTransfer | 9.13 | 0.00 | 01-JAN-00:10 | 82078.91 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.13 | 0.00 | 01-JAN-00:10 | 82078.91 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1572.51 | 0.00 | 01-JAN-00:10 | 190321.76 | 12-JUN-15:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 247.49 | 0.00 | 01-JAN-00:10 | 23252.46 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer | 1572.51 | 0.00 | 01-JAN-00:10 | 190321.76 | 12-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 247.49 | 0.00 | 01-JAN-00:10 | 23252.46 | 05-SEP-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 83.35 | 0.00 | 01-JAN-00:10 | 16620.06 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.02 | 0.00 | 01-JAN-00:10 | 9178.10 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.02 | 0.00 | 01-JAN-00:10 | 9178.10 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 79.33 | 0.00 | 01-JAN-00:10 | 16620.06 | 12-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 79.33 | 0.00 | 01-JAN-00:10 | 16620.06 | 12-JUN-14:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 42.36 | 0.00 | 01-JAN-00:10 | 7183.18 | 12-JUN-12:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.39 | 0.00 | 01-JAN-00:10 | 2437.24 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.39 | 0.00 | 01-JAN-00:10 | 2437.24 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 40.97 | 0.00 | 01-JAN-00:10 | 7183.18 | 12-JUN-12:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 40.97 | 0.00 | 01-JAN-00:10 | 7183.18 | 12-JUN-12:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 44.29 | 0.00 | 01-JAN-00:10 | 6544.44 | 30-MAY-07:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.59 | 0.00 | 01-JAN-00:10 | 1603.36 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.59 | 0.00 | 01-JAN-00:10 | 1603.36 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.70 | 0.00 | 01-JAN-00:10 | 6544.44 | 30-MAY-07:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.70 | 0.00 | 01-JAN-00:10 | 6544.44 | 30-MAY-07:20 |
EnergyTransfer:Zone:CORE_MID | 198.81 | 0.00 | 01-JAN-00:10 | 20499.22 | 30-MAY-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 6211.60 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 6211.60 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 198.80 | 0.00 | 01-JAN-00:10 | 20499.22 | 30-MAY-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 198.80 | 0.00 | 01-JAN-00:10 | 20499.22 | 30-MAY-07:20 |
EnergyTransfer:Zone:CORE_TOP | 208.25 | 0.00 | 01-JAN-00:10 | 23066.81 | 12-JUN-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.18 | 0.00 | 01-JAN-00:10 | 16780.28 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.18 | 0.00 | 01-JAN-00:10 | 16780.28 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 208.07 | 0.00 | 01-JAN-00:10 | 23066.81 | 12-JUN-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 208.07 | 0.00 | 01-JAN-00:10 | 23066.81 | 12-JUN-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.99 | 0.00 | 01-JAN-00:10 | 9576.62 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.52 | 0.00 | 01-JAN-00:10 | 7673.19 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.52 | 0.00 | 01-JAN-00:10 | 7673.19 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.47 | 0.00 | 01-JAN-00:10 | 9576.62 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.47 | 0.00 | 01-JAN-00:10 | 9576.62 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.70 | 0.00 | 01-JAN-00:10 | 9334.13 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 4921.27 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 4921.27 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.49 | 0.00 | 01-JAN-00:10 | 9334.13 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.49 | 0.00 | 01-JAN-00:10 | 9334.13 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.34 | 0.00 | 01-JAN-00:10 | 12825.47 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 7331.66 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 7331.66 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.05 | 0.00 | 01-JAN-00:10 | 12825.47 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.05 | 0.00 | 01-JAN-00:10 | 12825.47 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.73 | 0.00 | 01-JAN-00:10 | 10143.84 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.32 | 0.00 | 01-JAN-00:10 | 4892.66 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.32 | 0.00 | 01-JAN-00:10 | 4892.66 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.41 | 0.00 | 01-JAN-00:10 | 10143.84 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.41 | 0.00 | 01-JAN-00:10 | 10143.84 | 08-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.99 | 0.00 | 01-JAN-00:10 | 8469.88 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2903.23 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2903.23 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.96 | 0.00 | 01-JAN-00:10 | 8469.88 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.96 | 0.00 | 01-JAN-00:10 | 8469.88 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.89 | 0.00 | 01-JAN-00:10 | 8119.43 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1683.35 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1683.35 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.89 | 0.00 | 01-JAN-00:10 | 8119.43 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.89 | 0.00 | 01-JAN-00:10 | 8119.43 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 98.14 | 0.00 | 01-JAN-00:10 | 15139.89 | 12-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.35 | 0.00 | 01-JAN-00:10 | 5916.92 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.35 | 0.00 | 01-JAN-00:10 | 5916.92 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 96.79 | 0.00 | 01-JAN-00:10 | 15139.89 | 12-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 96.79 | 0.00 | 01-JAN-00:10 | 15139.89 | 12-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.31 | 0.00 | 01-JAN-00:10 | 8470.93 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1629.73 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1629.73 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.30 | 0.00 | 01-JAN-00:10 | 8470.93 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.30 | 0.00 | 01-JAN-00:10 | 8470.93 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 60.73 | 0.00 | 01-JAN-00:10 | 8481.40 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 4223.63 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 4223.63 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 60.64 | 0.00 | 01-JAN-00:10 | 8481.40 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 60.64 | 0.00 | 01-JAN-00:10 | 8481.40 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.67 | 0.00 | 01-JAN-00:10 | 8722.60 | 12-JUN-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2715.42 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2715.42 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.64 | 0.00 | 01-JAN-00:10 | 8722.60 | 12-JUN-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.64 | 0.00 | 01-JAN-00:10 | 8722.60 | 12-JUN-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 82.09 | 0.00 | 01-JAN-00:10 | 11243.57 | 02-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3711.98 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 3711.98 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 82.05 | 0.00 | 01-JAN-00:10 | 11243.57 | 02-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 82.05 | 0.00 | 01-JAN-00:10 | 11243.57 | 02-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 49.52 | 0.00 | 01-JAN-00:10 | 9111.16 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2653.31 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2653.31 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 49.47 | 0.00 | 01-JAN-00:10 | 9111.16 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 49.47 | 0.00 | 01-JAN-00:10 | 9111.16 | 08-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 34.85 | 0.00 | 01-JAN-00:10 | 4895.65 | 18-JAN-13:00 |
PlantLoopHeatingDemand:Plant | 34.85 | 0.00 | 01-JAN-00:10 | 4895.65 | 18-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 34.85 | 0.00 | 01-JAN-00:10 | 4895.65 | 18-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 34.85 | 0.00 | 01-JAN-00:10 | 4895.65 | 18-JAN-13:00 |
EnergyTransfer:HVAC | 2460.26 | 0.00 | 01-JAN-00:10 | 324145.84 | 22-JUN-15:40 |
HeatingCoils:EnergyTransfer | 8.03 | 0.00 | 01-JAN-00:10 | 106815.35 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 2452.23 | 0.00 | 01-JAN-00:10 | 324145.84 | 22-JUN-15:40 |
EnergyTransfer:Plant | 34.85 | 0.00 | 01-JAN-00:10 | 4895.65 | 18-JAN-13:00 |
WaterSystems:EnergyTransfer | 34.85 | 0.00 | 01-JAN-00:10 | 4895.65 | 18-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 34.85 | 0.00 | 01-JAN-00:10 | 4895.65 | 18-JAN-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -247.488 | 0.000 | 0.000 | 32.709 | 41.996 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -5.700 |
CORE_MID | 0.000 | 0.000 | 0.009 | -198.800 | 0.000 | 0.000 | 32.870 | 41.996 | 115.425 | 0.000 | 0.000 | 0.000 | 8.500 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.176 | -208.075 | 0.000 | 0.000 | 33.168 | 41.996 | 115.425 | 0.000 | 0.000 | 0.000 | 17.310 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.525 | -64.470 | 0.000 | 0.000 | 7.062 | 5.111 | 24.333 | 30.154 | 0.000 | 0.755 | 10.197 | 0.000 | -13.298 | 0.000 | -0.369 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.208 | -52.488 | 0.000 | 0.000 | 4.417 | 3.221 | 15.404 | 34.963 | 0.000 | 0.493 | 2.510 | 0.000 | -8.463 | 0.000 | -0.264 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.288 | -86.052 | 0.000 | 0.000 | 6.966 | 5.050 | 24.332 | 63.006 | 0.000 | 0.743 | 0.002 | 0.000 | -13.243 | 0.000 | -0.429 | -0.662 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.316 | -52.413 | 0.000 | 0.000 | 4.455 | 3.220 | 15.403 | 35.367 | 0.000 | 0.493 | 2.470 | 0.000 | -9.049 | 0.000 | -0.262 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.034 | -60.959 | 0.000 | 0.000 | 6.993 | 5.100 | 24.333 | 30.265 | 0.000 | 0.413 | 8.495 | 0.000 | -14.457 | 0.000 | -0.217 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.009 | -50.885 | 0.000 | 0.000 | 4.384 | 3.215 | 15.404 | 34.935 | 0.000 | 0.266 | 2.165 | 0.000 | -9.337 | 0.000 | -0.157 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.349 | -96.787 | 0.000 | 0.000 | 6.892 | 5.042 | 24.332 | 62.919 | 0.000 | 20.259 | 0.002 | 0.000 | -14.739 | 0.000 | -8.846 | -0.422 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.013 | -50.295 | 0.000 | 0.000 | 4.404 | 3.214 | 15.403 | 35.420 | 0.000 | 0.265 | 1.770 | 0.000 | -10.037 | 0.000 | -0.157 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.082 | -60.643 | 0.000 | 0.000 | 7.003 | 5.111 | 24.333 | 30.257 | 0.000 | 0.636 | 7.858 | 0.000 | -14.299 | 0.000 | -0.338 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.034 | -47.637 | 0.000 | 0.000 | 3.236 | 3.221 | 15.404 | 34.856 | 0.000 | 0.411 | 0.000 | 0.000 | -9.033 | 0.000 | -0.240 | -0.252 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.039 | -82.050 | 0.000 | 0.000 | 6.927 | 5.050 | 24.332 | 63.116 | 0.000 | 0.625 | 0.000 | 0.000 | -14.105 | 0.000 | -0.384 | -3.549 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.048 | -49.467 | 0.000 | 0.000 | 4.420 | 3.220 | 15.403 | 35.457 | 0.000 | 0.413 | 0.441 | 0.000 | -9.698 | 0.000 | -0.238 | -0.000 |
TOPFLOOR_PLENUM | 4.019 | -79.334 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.983 | 74.912 | 0.000 | 0.000 | 0.000 | -0.580 | -0.001 |
MIDFLOOR_PLENUM | 1.392 | -40.968 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.992 | 39.185 | 0.000 | 0.000 | 0.000 | -0.601 | -0.001 |
FIRSTFLOOR_PLENUM | 0.593 | -43.700 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.775 | 42.827 | 0.000 | 0.000 | 0.000 | -0.495 | -0.000 |
Total Facility | 6.005 | -164.001 | 3.129 | -1408.509 | 0.000 | 0.000 | 165.907 | 175.762 | 647.750 | 490.714 | 0.000 | 28.521 | 218.644 | 0.000 | -139.757 | 0.000 | -13.576 | -10.590 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 15-MAY-04:02 | 0.00 | 0.00 | 0.00 | -36045.27 | 0.00 | 0.00 | 0.00 | 409.17 | 3464.19 | 0.00 | 0.00 | 0.00 | 32171.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-05:14 | 0.00 | 0.00 | 0.00 | -32778.09 | 0.00 | 0.00 | 315.88 | 409.17 | 3025.92 | 0.00 | 0.00 | 0.00 | 29027.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 15-MAY-04:02 | 0.00 | 0.00 | 0.00 | -36900.94 | 0.00 | 0.00 | 0.00 | 409.17 | 2442.06 | 0.00 | 0.00 | 0.00 | 34049.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 28-MAY-15:21 | 0.00 | 0.00 | 0.00 | -15536.75 | 0.00 | 0.00 | 23.34 | 20.57 | 478.42 | 3535.73 | 0.00 | 716.14 | 10762.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-09:52 | 0.00 | 0.00 | 0.00 | -12384.78 | 0.00 | 0.00 | 11.92 | 13.02 | 302.86 | 6400.26 | 0.00 | 349.85 | 5306.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:42 | 0.00 | 0.00 | 0.00 | -17238.39 | 0.00 | 0.00 | 22.28 | 20.57 | 478.41 | 9982.44 | 0.00 | 143.53 | 6591.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:33 | 0.00 | 0.00 | 0.00 | -14522.31 | 0.00 | 0.00 | 10.11 | 13.02 | 302.86 | 7420.98 | 0.00 | 138.14 | 6637.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -12400.45 | 0.00 | 0.00 | 26.18 | 20.57 | 478.42 | 4271.66 | 0.00 | 72.24 | 7531.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-09:01 | 0.00 | 0.00 | 0.00 | -10551.60 | 0.00 | 0.00 | 14.22 | 13.02 | 302.86 | 7730.87 | 0.00 | 184.25 | 2306.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 12-JUN-17:00 | 0.00 | 0.00 | 0.00 | -15140.93 | 0.00 | 0.00 | 132.12 | 205.72 | 797.35 | 3351.77 | 0.00 | 15896.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5242.37 |
PERIMETER_BOT_ZN_4 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -11325.96 | 0.00 | 0.00 | 12.89 | 13.02 | 302.86 | 7318.60 | 0.00 | 45.10 | 3633.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 28-MAY-16:31 | 0.00 | 0.00 | 0.00 | -13086.33 | 0.00 | 0.00 | 25.24 | 20.57 | 478.42 | 3643.10 | 0.00 | 542.47 | 8376.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 30-APR-08:42 | 0.00 | 0.00 | 0.00 | -11595.74 | 0.00 | 0.00 | 14.74 | 13.02 | 302.86 | 7914.79 | 0.00 | 0.00 | 3351.56 | 0.00 | -0.00 | 0.00 | -1.23 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:22 | 0.00 | 0.00 | 0.00 | -14660.58 | 0.00 | 0.00 | 23.31 | 20.57 | 478.41 | 10122.82 | 0.00 | 6.85 | 4008.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 28-MAY-16:31 | 0.00 | 0.00 | 0.00 | -12580.71 | 0.00 | 0.00 | 11.11 | 13.02 | 302.86 | 7938.69 | 0.00 | 327.76 | 3987.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 29-MAY-15:51 | 0.00 | -16789.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.41 | 16441.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 12-JUN-06:15 | 0.00 | -9068.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 8990.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 30-MAY-12:09 | 0.00 | -8237.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.18 | 8150.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-06:03 | 0.00 | -16777.19 | 0.00 | -197310.68 | 0.00 | 0.00 | 3471.76 | 5222.76 | 18346.02 | 18961.49 | 0.00 | 11437.13 | 156648.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 03-JAN-07:02 | 0.00 | 0.00 | 15581.72 | 0.00 | 0.00 | 0.00 | 897.96 | 1227.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20733.11 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 20747.09 | 0.00 | 0.00 | 0.00 | 505.47 | 409.17 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24687.64 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 9319.40 | 0.00 | 0.00 | 0.00 | 112.64 | 86.26 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1680.51 | 0.00 | 0.00 | -8475.67 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5895.77 | 0.00 | 0.00 | 0.00 | 71.29 | 54.61 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1122.49 | 0.00 | 0.00 | -5302.99 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 9092.00 | 0.00 | 0.00 | 0.00 | 111.46 | 86.26 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1734.28 | 0.00 | 0.00 | -8193.32 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5728.85 | 0.00 | 0.00 | 0.00 | 71.15 | 54.60 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1129.00 | 0.00 | 0.00 | -5129.42 |
PERIMETER_BOT_ZN_3 | 02-JAN-07:04 | 0.00 | 0.00 | 5346.19 | 0.00 | 0.00 | 0.00 | 193.28 | 258.77 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2130.75 | 0.00 | 0.00 | -4305.38 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:12 | 0.00 | 0.00 | 3825.30 | 0.00 | 0.00 | 0.00 | 63.58 | 54.61 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1433.74 | 0.00 | 0.00 | -2913.56 |
PERIMETER_BOT_ZN_1 | 02-JAN-07:04 | 0.00 | 0.00 | 5988.27 | 0.00 | 0.00 | 0.00 | 193.28 | 258.77 | 637.88 | 0.00 | 0.00 | 0.00 | 9590.79 | 0.00 | -2217.02 | 0.00 | -14451.97 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:12 | 0.00 | 0.00 | 3548.34 | 0.00 | 0.00 | 0.00 | 63.46 | 54.60 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1438.51 | 0.00 | 0.00 | -2631.70 |
PERIMETER_MID_ZN_3 | 02-JAN-06:12 | 0.00 | 0.00 | 6731.69 | 0.00 | 0.00 | 0.00 | 105.03 | 86.26 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1972.04 | 0.00 | 0.00 | -5588.81 |
PERIMETER_MID_ZN_2 | 02-JAN-06:14 | 0.00 | 0.00 | 4336.61 | 0.00 | 0.00 | 0.00 | 66.51 | 54.61 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1315.29 | 0.00 | 0.00 | -3546.25 |
PERIMETER_MID_ZN_1 | 02-JAN-06:12 | 0.00 | 0.00 | 6530.24 | 0.00 | 0.00 | 0.00 | 103.70 | 86.26 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2025.84 | 0.00 | 0.00 | -5332.24 |
PERIMETER_MID_ZN_4 | 02-JAN-06:14 | 0.00 | 0.00 | 4413.88 | 0.00 | 0.00 | 0.00 | 66.36 | 54.60 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1321.53 | 0.00 | 0.00 | -3617.12 |
TOPFLOOR_PLENUM | 02-JAN-06:17 | 11681.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11681.18 |
MIDFLOOR_PLENUM | 24-DEC-14:03 | 4061.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4120.04 |
FIRSTFLOOR_PLENUM | 31-AUG-04:02 | 3478.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3590.59 |
Total Facility | 02-JAN-07:04 | 9779.68 | 4599.84 | 96215.27 | -4599.84 | 0.00 | 0.00 | 4584.60 | 6218.03 | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20655.95 | 0.00 | -14451.97 | -100035.68 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1467 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8330 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.9717 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6112 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7389 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6356 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5733 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0771 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4858 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0765 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8694 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0765 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4450 | 2.4450 | 0.6382 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1053 | 2.1053 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4343 | 2.4343 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9123 | 0.9123 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6915 | 0.6915 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9272 | 0.9272 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7736 | 0.7736 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7335 | 0.7335 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5961 | 0.5961 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7471 | 0.7471 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6249 | 0.6249 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7698 | 0.7698 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6348 | 0.6348 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7860 | 0.7860 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6758 | 0.6758 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1467 | 4.8330 | 5.1467 | 1.0771 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.9717 | 4.6112 | 4.9717 | 1.0765 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7389 | 5.6356 | 5.7389 | 1.0765 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2225 | 1.2225 | 0.6382 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0527 | 1.0527 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2172 | 1.2172 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4561 | 0.4561 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3458 | 0.3458 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4636 | 0.4636 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3868 | 0.3868 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3668 | 0.3668 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2981 | 0.2981 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3736 | 0.3736 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3124 | 0.3124 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3849 | 0.3849 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3174 | 0.3174 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3930 | 0.3930 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3379 | 0.3379 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5733 | 1.0771 | 1.0771 | 1.0771 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4858 | 1.0765 | 1.0765 | 1.0765 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8694 | 1.0765 | 1.0765 | 1.0765 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 43.83 |
Number of hours cooling loads not met | 612.00 |
Number of hours not met | 655.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 6.23 | 101690.96 | 2.25 | 8313.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 642.89 | 104855.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 175.76 | 17769.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 33.93 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 829.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 136.36 | 25716.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 112.73 | 9696.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1654.70 |
Natural Gas | 0.00 | 114.98 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1769.67 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 166.95 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 35.28 |
Space Heating | 1.25 |
Space Cooling | 129.04 |
Fans (All) | 27.37 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 332.12 |
Subtotal | 332.12 |
Natural Gas [MJ/m2] | |
Space Heating | 0.45 |
Service Water Heating | 22.63 |
Miscellaneous (All) | 23.08 |
Subtotal | 23.08 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.93 |
Space Heating | 0.48 |
Space Cooling | 36.33 |
Fans (All) | 7.71 |
Service Water Heating | 6.37 |
Receptacle Equipment | 36.60 |
Miscellaneous | 2.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1058. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8711.83 | 48.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8109.00 | 651.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8007.17 | 752.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8036.17 | 723.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7906.17 | 853.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8274.33 | 485.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8005.67 | 754.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7910.67 | 849.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7865.33 | 894.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8136.00 | 624.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7996.33 | 763.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8038.00 | 722.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7874.17 | 885.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7999.67 | 760.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8437.17 | 322.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8594.83 | 165.17 | 0.00 | 0.00 | 0.00 |
Min | 7865.33 | 17.50 | 0.00 | 0.00 | 0.00 |
Max | 8742.50 | 894.67 | 0.00 | 0.00 | 0.00 |
Average | 8186.96 | 573.04 | 0.00 | 0.00 | 0.00 |
Sum | 147365.33 | 10314.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128300.67 | 3.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128295.33 | 8.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128273.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24593.17 | 315.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128300.67 | 315.83 | 0.00 | 0.00 | 0.00 |
Average | 34123.40 | 19.94 | 0.00 | 0.00 | 0.00 |
Sum | 614221.17 | 358.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7388.00 | 1372.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7391.00 | 1369.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7440.67 | 1319.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7060.00 | 1700.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7002.83 | 1757.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7008.83 | 1751.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6995.00 | 1765.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7055.33 | 1704.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6945.67 | 1814.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6183.17 | 2576.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6913.33 | 1846.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6983.83 | 1776.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6911.00 | 1849.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6922.83 | 1837.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6909.50 | 1850.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 5164.33 | 3595.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5940.33 | 2819.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6364.50 | 2395.50 | 0.00 | 0.00 | 0.00 |
Min | 5164.33 | 1319.33 | 0.00 | 0.00 | 0.00 |
Max | 7440.67 | 3595.67 | 0.00 | 0.00 | 0.00 |
Average | 6810.01 | 1949.99 | 0.00 | 0.00 | 0.00 |
Sum | 122580.17 | 35099.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127530.67 | 773.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127533.17 | 770.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127521.33 | 782.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24826.83 | 82.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14011.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24827.33 | 81.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24831.33 | 77.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20521.33 | 4387.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24821.67 | 87.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10131.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24822.17 | 86.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14013.50 | 2.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127533.17 | 4387.67 | 0.00 | 0.00 | 0.00 |
Average | 33746.46 | 396.87 | 0.00 | 0.00 | 0.00 |
Sum | 607436.33 | 7143.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121514E+11 | 14556.99 | 18-JAN-08:07 | 13.65 | 12.98 | 0.196983E+10 | 2606.64 | 13-JAN-14:20 | 13.65 | 12.98 |
February | 0.140664E+11 | 27308.04 | 23-FEB-07:02 | 15.45 | 14.06 | 0.180413E+10 | 2606.66 | 24-FEB-10:20 | 20.97 | 15.04 |
March | 0.203340E+11 | 35526.91 | 13-MAR-05:12 | 20.73 | 15.50 | 0.215840E+10 | 2606.67 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.218909E+11 | 35501.59 | 10-APR-05:12 | 18.37 | 13.16 | 0.191789E+10 | 2606.67 | 04-APR-09:20 | 18.37 | 13.16 |
May | 0.254600E+11 | 36042.75 | 15-MAY-04:02 | 24.27 | 18.74 | 0.207714E+10 | 2606.72 | 22-MAY-13:09 | 37.88 | 24.20 |
June | 0.251334E+11 | 35196.07 | 20-JUN-04:03 | 28.05 | 23.71 | 0.207014E+10 | 2606.70 | 20-JUN-13:09 | 33.57 | 27.49 |
July | 0.246213E+11 | 31660.16 | 19-JUL-05:03 | 26.00 | 25.06 | 0.192382E+10 | 2606.63 | 19-JUL-13:20 | 33.13 | 27.04 |
August | 0.253050E+11 | 33371.87 | 24-AUG-05:03 | 25.45 | 24.92 | 0.215988E+10 | 2606.65 | 21-AUG-13:20 | 25.45 | 24.92 |
September | 0.229060E+11 | 35100.04 | 26-SEP-04:03 | 25.35 | 21.31 | 0.191862E+10 | 2606.66 | 11-SEP-13:09 | 25.35 | 21.31 |
October | 0.224120E+11 | 35674.40 | 11-OCT-04:03 | 24.15 | 20.56 | 0.199482E+10 | 2606.68 | 30-OCT-09:20 | 21.73 | 16.89 |
November | 0.187843E+11 | 33484.31 | 13-NOV-07:02 | 16.07 | 12.01 | 0.197289E+10 | 2606.68 | 16-NOV-10:39 | 23.10 | 16.88 |
December | 0.144215E+11 | 16658.39 | 21-DEC-08:03 | 6.25 | 5.33 | 0.191779E+10 | 2606.66 | 18-DEC-10:20 | 6.25 | 5.33 |
Annual Sum or Average | 0.247486E+12 | 0.238854E+11 | ||||||||
Minimum of Months | 0.121514E+11 | 14556.99 | 6.25 | 5.33 | 0.180413E+10 | 2606.63 | 6.25 | 5.33 | ||
Maximum of Months | 0.254600E+11 | 36042.75 | 28.05 | 25.06 | 0.215988E+10 | 2606.72 | 37.88 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.949395E+09 | 3724.17 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.206340E+10 | 7808.02 | 22-FEB-14:40 | 27.07 | 16.24 | 0.00 | 0.00 | 01-FEB-00:10 | 27.07 | 16.24 |
March | 0.549760E+10 | 12280.11 | 28-MAR-15:40 | 35.53 | 18.66 | 0.00 | 0.00 | 01-MAR-00:10 | 35.53 | 18.66 |
April | 0.950691E+10 | 14564.01 | 26-APR-15:00 | 39.30 | 22.03 | 0.00 | 0.00 | 01-APR-00:10 | 39.30 | 22.03 |
May | 0.122371E+11 | 16789.73 | 29-MAY-15:51 | 41.30 | 21.57 | 0.00 | 0.00 | 01-MAY-00:10 | 41.30 | 21.57 |
June | 0.121060E+11 | 16692.88 | 05-JUN-12:09 | 41.43 | 22.34 | 0.00 | 0.00 | 01-JUN-00:10 | 41.43 | 22.34 |
July | 0.972186E+10 | 15089.94 | 10-JUL-13:50 | 39.20 | 26.60 | 0.00 | 0.00 | 01-JUL-00:10 | 39.20 | 26.60 |
August | 0.894153E+10 | 13672.93 | 07-AUG-14:40 | 37.27 | 26.48 | 0.00 | 0.00 | 01-AUG-00:10 | 37.27 | 26.48 |
September | 0.718436E+10 | 12240.24 | 26-SEP-15:00 | 36.10 | 22.69 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 22.69 |
October | 0.641028E+10 | 12469.32 | 02-OCT-14:05 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.351532E+10 | 8457.74 | 09-NOV-14:40 | 29.27 | 17.76 | 0.00 | 0.00 | 01-NOV-00:10 | 29.27 | 17.76 |
December | 0.120036E+10 | 5085.91 | 01-DEC-14:30 | 23.45 | 13.21 | 0.00 | 0.00 | 01-DEC-00:10 | 23.45 | 13.21 |
Annual Sum or Average | 0.793342E+11 | 0.00 | ||||||||
Minimum of Months | 0.949395E+09 | 3724.17 | 23.45 | 13.21 | 0.00 | 0.00 | 23.45 | 13.21 | ||
Maximum of Months | 0.122371E+11 | 16789.73 | 41.43 | 26.60 | 0.00 | 0.00 | 41.43 | 26.60 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181727E+09 | 2231.16 | 06-JAN-07:01 | 5.62 | 5.52 | 0.00 | 0.00 | 01-JAN-00:10 | 5.62 | 5.52 |
February | 0.685300E+09 | 2467.14 | 22-FEB-15:30 | 26.80 | 16.08 | 0.00 | 0.00 | 01-FEB-00:10 | 26.80 | 16.08 |
March | 0.258838E+10 | 4956.82 | 13-MAR-16:00 | 32.50 | 18.65 | 0.00 | 0.00 | 01-MAR-00:10 | 32.50 | 18.65 |
April | 0.468620E+10 | 6136.44 | 17-APR-15:10 | 34.65 | 21.60 | 0.00 | 0.00 | 01-APR-00:10 | 34.65 | 21.60 |
May | 0.630884E+10 | 7616.12 | 30-MAY-12:05 | 37.90 | 23.62 | 0.00 | 0.00 | 01-MAY-00:10 | 37.90 | 23.62 |
June | 0.610004E+10 | 9069.36 | 12-JUN-06:15 | 35.03 | 19.50 | 0.00 | 0.00 | 01-JUN-00:10 | 35.03 | 19.50 |
July | 0.549912E+10 | 7472.00 | 05-JUL-12:05 | 37.65 | 25.58 | 0.00 | 0.00 | 01-JUL-00:10 | 37.65 | 25.58 |
August | 0.523329E+10 | 7115.72 | 14-AUG-06:15 | 28.60 | 26.29 | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 26.29 |
September | 0.431210E+10 | 6609.08 | 05-SEP-06:15 | 26.23 | 25.18 | 0.00 | 0.00 | 01-SEP-00:10 | 26.23 | 25.18 |
October | 0.350437E+10 | 5885.46 | 02-OCT-16:00 | 35.90 | 21.25 | 0.00 | 0.00 | 01-OCT-00:10 | 35.90 | 21.25 |
November | 0.156887E+10 | 3424.36 | 13-NOV-15:50 | 27.70 | 16.51 | 0.00 | 0.00 | 01-NOV-00:10 | 27.70 | 16.51 |
December | 0.300031E+09 | 1989.58 | 21-DEC-07:01 | 5.68 | 4.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.68 | 4.75 |
Annual Sum or Average | 0.409683E+11 | 0.00 | ||||||||
Minimum of Months | 0.181727E+09 | 1989.58 | 5.62 | 4.75 | 0.00 | 0.00 | 5.62 | 4.75 | ||
Maximum of Months | 0.630884E+10 | 9069.36 | 37.90 | 26.29 | 0.00 | 0.00 | 37.90 | 26.29 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445518E+09 | 2619.96 | 05-JAN-07:01 | 4.93 | 4.82 | 0.00 | 0.00 | 01-JAN-00:10 | 4.93 | 4.82 |
February | 0.113646E+10 | 2949.65 | 22-FEB-16:10 | 26.37 | 15.92 | 0.00 | 0.00 | 01-FEB-00:10 | 26.37 | 15.92 |
March | 0.290839E+10 | 4889.00 | 28-MAR-17:09 | 34.60 | 18.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.60 | 18.91 |
April | 0.449428E+10 | 6520.65 | 17-APR-12:10 | 34.87 | 22.75 | 0.00 | 0.00 | 01-APR-00:10 | 34.87 | 22.75 |
May | 0.587412E+10 | 8238.02 | 30-MAY-12:09 | 37.90 | 23.62 | 0.00 | 0.00 | 01-MAY-00:10 | 37.90 | 23.62 |
June | 0.582975E+10 | 7954.06 | 12-JUN-07:07 | 35.90 | 20.13 | 0.00 | 0.00 | 01-JUN-00:10 | 35.90 | 20.13 |
July | 0.551904E+10 | 7781.77 | 05-JUL-07:08 | 33.75 | 24.52 | 0.00 | 0.00 | 01-JUL-00:10 | 33.75 | 24.52 |
August | 0.552262E+10 | 6786.62 | 07-AUG-17:09 | 36.48 | 26.95 | 0.00 | 0.00 | 01-AUG-00:10 | 36.48 | 26.95 |
September | 0.471673E+10 | 6524.25 | 05-SEP-06:15 | 26.23 | 25.18 | 0.00 | 0.00 | 01-SEP-00:10 | 26.23 | 25.18 |
October | 0.407993E+10 | 5476.57 | 02-OCT-16:00 | 35.90 | 21.25 | 0.00 | 0.00 | 01-OCT-00:10 | 35.90 | 21.25 |
November | 0.238769E+10 | 3953.08 | 13-NOV-16:30 | 27.00 | 16.63 | 0.00 | 0.00 | 01-NOV-00:10 | 27.00 | 16.63 |
December | 0.785116E+09 | 2270.94 | 01-DEC-15:20 | 23.03 | 13.49 | 0.00 | 0.00 | 01-DEC-00:10 | 23.03 | 13.49 |
Annual Sum or Average | 0.436996E+11 | 0.00 | ||||||||
Minimum of Months | 0.445518E+09 | 2270.94 | 4.93 | 4.82 | 0.00 | 0.00 | 4.93 | 4.82 | ||
Maximum of Months | 0.587412E+10 | 8238.02 | 37.90 | 26.95 | 0.00 | 0.00 | 37.90 | 26.95 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.842342E+10 | 10061.01 | 26-JAN-17:00 | 18.60 | 12.70 | 0.188234E+10 | 2606.63 | 12-JAN-14:20 | 18.60 | 12.70 |
February | 0.100522E+11 | 13079.19 | 22-FEB-17:00 | 25.70 | 15.75 | 0.178317E+10 | 2606.66 | 24-FEB-10:20 | 20.97 | 15.04 |
March | 0.158853E+11 | 31056.65 | 13-MAR-05:12 | 20.73 | 15.50 | 0.215410E+10 | 2606.67 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.186934E+11 | 31113.06 | 10-APR-05:12 | 18.37 | 13.16 | 0.191675E+10 | 2606.67 | 04-APR-09:20 | 18.37 | 13.16 |
May | 0.224553E+11 | 31103.32 | 15-MAY-04:02 | 24.27 | 18.74 | 0.207644E+10 | 2606.67 | 01-MAY-09:30 | 24.27 | 18.74 |
June | 0.219292E+11 | 30603.65 | 20-JUN-04:03 | 28.05 | 23.71 | 0.206943E+10 | 2606.65 | 12-JUN-09:30 | 28.05 | 23.71 |
July | 0.211471E+11 | 30742.38 | 11-JUL-04:03 | 26.73 | 24.05 | 0.192371E+10 | 2606.64 | 05-JUL-09:20 | 26.73 | 24.05 |
August | 0.210232E+11 | 31000.04 | 21-AUG-04:04 | 25.67 | 25.19 | 0.215933E+10 | 2606.63 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.185745E+11 | 31443.70 | 26-SEP-04:03 | 25.35 | 21.31 | 0.191792E+10 | 2606.62 | 11-SEP-13:20 | 25.35 | 21.31 |
October | 0.175568E+11 | 32779.57 | 02-OCT-05:14 | 21.80 | 17.53 | 0.199259E+10 | 2606.67 | 30-OCT-09:20 | 21.73 | 16.89 |
November | 0.134681E+11 | 28039.19 | 13-NOV-07:02 | 16.07 | 12.01 | 0.196524E+10 | 2606.68 | 06-NOV-10:09 | 16.07 | 12.01 |
December | 0.959020E+10 | 11762.87 | 01-DEC-17:00 | 21.20 | 14.26 | 0.188264E+10 | 2606.64 | 28-DEC-14:20 | 24.57 | 15.33 |
Annual Sum or Average | 0.198799E+12 | 0.237237E+11 | ||||||||
Minimum of Months | 0.842342E+10 | 10061.01 | 16.07 | 12.01 | 0.178317E+10 | 2606.62 | 16.07 | 12.01 | ||
Maximum of Months | 0.224553E+11 | 32779.57 | 28.05 | 25.19 | 0.215933E+10 | 2606.68 | 29.43 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.756872E+10 | 9858.57 | 26-JAN-16:20 | 19.67 | 13.02 | 0.177053E+10 | 2606.63 | 12-JAN-14:20 | 19.67 | 13.02 |
February | 0.931335E+10 | 14122.21 | 23-FEB-15:00 | 25.80 | 14.10 | 0.173027E+10 | 2606.65 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.158906E+11 | 27069.13 | 13-MAR-05:12 | 20.73 | 15.50 | 0.214363E+10 | 2606.68 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.204595E+11 | 35798.35 | 17-APR-04:02 | 24.68 | 19.16 | 0.191696E+10 | 2606.68 | 05-APR-09:20 | 24.68 | 19.16 |
May | 0.253795E+11 | 36897.12 | 15-MAY-04:02 | 24.27 | 18.74 | 0.207829E+10 | 2606.64 | 01-MAY-09:09 | 24.27 | 18.74 |
June | 0.250567E+11 | 34614.85 | 28-JUN-05:03 | 26.50 | 25.24 | 0.207092E+10 | 2606.65 | 05-JUN-13:20 | 26.50 | 25.24 |
July | 0.236670E+11 | 31658.05 | 19-JUL-05:03 | 26.00 | 25.06 | 0.192567E+10 | 2606.61 | 18-JUL-13:20 | 26.00 | 25.06 |
August | 0.229664E+11 | 34664.27 | 21-AUG-04:02 | 25.67 | 25.19 | 0.216062E+10 | 2606.61 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.195914E+11 | 34971.47 | 07-SEP-05:03 | 24.67 | 23.93 | 0.191826E+10 | 2606.63 | 27-SEP-09:20 | 28.93 | 20.86 |
October | 0.174717E+11 | 35872.48 | 10-OCT-05:12 | 19.90 | 18.09 | 0.198804E+10 | 2606.69 | 19-OCT-09:39 | 28.40 | 21.52 |
November | 0.122561E+11 | 15641.39 | 13-NOV-15:00 | 28.20 | 16.17 | 0.193909E+10 | 2606.67 | 13-NOV-10:20 | 28.20 | 16.17 |
December | 0.845329E+10 | 11409.57 | 01-DEC-16:20 | 21.93 | 13.92 | 0.178428E+10 | 2606.64 | 28-DEC-14:20 | 24.57 | 15.33 |
Annual Sum or Average | 0.208074E+12 | 0.234266E+11 | ||||||||
Minimum of Months | 0.756872E+10 | 9858.57 | 19.67 | 13.02 | 0.173027E+10 | 2606.61 | 19.67 | 13.02 | ||
Maximum of Months | 0.253795E+11 | 36897.12 | 28.20 | 25.24 | 0.216062E+10 | 2606.69 | 29.43 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119757E+10 | 2239.53 | 26-JAN-15:00 | 21.60 | 13.66 | 0.352681E+09 | 549.50 | 12-JAN-14:20 | 21.60 | 13.66 |
February | 0.185781E+10 | 4094.71 | 23-FEB-14:40 | 26.00 | 14.03 | 0.349730E+09 | 549.50 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.413779E+10 | 6798.21 | 12-MAR-16:02 | 31.18 | 19.88 | 0.446340E+09 | 549.51 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.669738E+10 | 15157.62 | 16-APR-14:42 | 39.67 | 22.23 | 0.404417E+09 | 549.51 | 21-APR-09:20 | 27.77 | 18.93 |
May | 0.930267E+10 | 15536.65 | 28-MAY-15:21 | 42.25 | 19.25 | 0.439144E+09 | 549.50 | 05-MAY-09:20 | 42.25 | 19.25 |
June | 0.946954E+10 | 15382.06 | 04-JUN-15:21 | 42.30 | 22.20 | 0.437554E+09 | 549.50 | 07-JUN-09:20 | 37.90 | 20.70 |
July | 0.861798E+10 | 15066.07 | 04-JUL-17:52 | 40.20 | 24.17 | 0.407149E+09 | 549.49 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.800227E+10 | 13906.37 | 06-AUG-16:12 | 36.20 | 26.31 | 0.456250E+09 | 549.49 | 28-AUG-09:20 | 31.07 | 27.59 |
September | 0.625989E+10 | 12419.42 | 25-SEP-04:02 | 26.32 | 23.72 | 0.404973E+09 | 549.50 | 26-SEP-09:20 | 28.90 | 21.08 |
October | 0.482758E+10 | 11859.85 | 01-OCT-15:42 | 35.58 | 20.12 | 0.417355E+09 | 549.51 | 03-OCT-09:20 | 28.77 | 19.61 |
November | 0.267376E+10 | 4502.75 | 09-NOV-14:30 | 29.30 | 17.79 | 0.398269E+09 | 549.50 | 13-NOV-10:20 | 23.03 | 14.78 |
December | 0.142604E+10 | 2301.89 | 01-DEC-15:00 | 23.40 | 13.35 | 0.355158E+09 | 549.50 | 28-DEC-14:20 | 24.57 | 15.33 |
Annual Sum or Average | 0.644703E+11 | 0.486902E+10 | ||||||||
Minimum of Months | 0.119757E+10 | 2239.53 | 21.60 | 13.35 | 0.349730E+09 | 549.49 | 21.60 | 13.66 | ||
Maximum of Months | 0.946954E+10 | 15536.65 | 42.30 | 26.31 | 0.456250E+09 | 549.51 | 42.25 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.989307E+09 | 1925.23 | 26-JAN-14:10 | 22.35 | 13.84 | 0.240054E+09 | 347.88 | 12-JAN-14:20 | 22.35 | 13.84 |
February | 0.170597E+10 | 3910.02 | 22-FEB-10:50 | 23.10 | 14.47 | 0.231360E+09 | 347.88 | 08-FEB-14:20 | 23.10 | 14.47 |
March | 0.389582E+10 | 7147.32 | 26-MAR-15:32 | 30.13 | 16.60 | 0.285921E+09 | 347.89 | 06-MAR-10:30 | 30.13 | 16.60 |
April | 0.611827E+10 | 12079.83 | 16-APR-10:02 | 35.32 | 21.70 | 0.256424E+09 | 348.04 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.773015E+10 | 12384.90 | 29-MAY-09:52 | 35.80 | 22.19 | 0.278190E+09 | 348.00 | 03-MAY-09:00 | 35.80 | 22.19 |
June | 0.721948E+10 | 12159.56 | 04-JUN-10:02 | 34.73 | 22.02 | 0.277102E+09 | 349.76 | 12-JUN-09:50 | 39.75 | 22.08 |
July | 0.627497E+10 | 11875.93 | 04-JUL-10:32 | 36.00 | 24.99 | 0.257854E+09 | 348.01 | 10-JUL-09:39 | 33.83 | 26.57 |
August | 0.580892E+10 | 11099.06 | 27-AUG-10:32 | 32.60 | 28.69 | 0.288917E+09 | 347.92 | 07-AUG-09:00 | 32.60 | 28.69 |
September | 0.490381E+10 | 11636.76 | 17-SEP-10:02 | 30.73 | 25.45 | 0.256488E+09 | 347.87 | 27-SEP-09:20 | 28.93 | 20.86 |
October | 0.424809E+10 | 11755.47 | 09-OCT-11:42 | 31.15 | 20.28 | 0.265288E+09 | 347.89 | 17-OCT-09:30 | 27.00 | 18.48 |
November | 0.243414E+10 | 3999.56 | 09-NOV-10:30 | 25.75 | 18.10 | 0.258447E+09 | 347.88 | 06-NOV-10:00 | 25.75 | 18.10 |
December | 0.115967E+10 | 2250.37 | 01-DEC-10:50 | 19.88 | 12.01 | 0.239607E+09 | 347.88 | 28-DEC-14:20 | 24.57 | 15.33 |
Annual Sum or Average | 0.524886E+11 | 0.313565E+10 | ||||||||
Minimum of Months | 0.989307E+09 | 1925.23 | 19.88 | 12.01 | 0.231360E+09 | 347.87 | 22.35 | 13.84 | ||
Maximum of Months | 0.773015E+10 | 12384.90 | 36.00 | 28.69 | 0.288917E+09 | 349.76 | 39.75 | 28.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318152E+10 | 7813.99 | 12-JAN-14:10 | 23.35 | 14.02 | 0.388279E+09 | 549.51 | 25-JAN-14:50 | 22.98 | 13.31 |
February | 0.415730E+10 | 15966.89 | 20-FEB-13:02 | 25.98 | 13.37 | 0.364067E+09 | 549.67 | 22-FEB-14:39 | 27.07 | 16.24 |
March | 0.697094E+10 | 16082.07 | 26-MAR-15:32 | 30.13 | 16.60 | 0.449677E+09 | 549.77 | 09-MAR-14:50 | 30.13 | 16.60 |
April | 0.844086E+10 | 16083.26 | 16-APR-14:42 | 39.67 | 22.23 | 0.404711E+09 | 549.68 | 21-APR-13:00 | 35.00 | 19.79 |
May | 0.969357E+10 | 15912.33 | 28-MAY-15:21 | 42.25 | 19.25 | 0.439155E+09 | 549.65 | 03-MAY-13:00 | 42.25 | 19.25 |
June | 0.940546E+10 | 15677.88 | 04-JUN-14:41 | 42.17 | 22.13 | 0.437537E+09 | 549.63 | 05-JUN-13:39 | 42.50 | 22.45 |
July | 0.867822E+10 | 15120.86 | 04-JUL-17:12 | 40.00 | 24.23 | 0.407148E+09 | 549.49 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.847098E+10 | 14283.28 | 06-AUG-16:12 | 36.20 | 26.31 | 0.456295E+09 | 549.60 | 07-AUG-13:00 | 37.20 | 26.26 |
September | 0.779790E+10 | 15859.52 | 24-SEP-13:32 | 34.93 | 24.63 | 0.405173E+09 | 549.65 | 26-SEP-13:00 | 35.70 | 22.91 |
October | 0.862140E+10 | 17240.10 | 15-OCT-12:42 | 32.60 | 18.71 | 0.419377E+09 | 567.11 | 02-OCT-13:39 | 32.60 | 18.71 |
November | 0.680958E+10 | 16499.23 | 23-NOV-13:32 | 25.67 | 14.23 | 0.408929E+09 | 549.76 | 06-NOV-14:00 | 25.67 | 14.23 |
December | 0.382435E+10 | 10395.37 | 03-DEC-14:53 | 23.60 | 14.22 | 0.383922E+09 | 549.51 | 01-DEC-14:09 | 23.60 | 14.22 |
Annual Sum or Average | 0.860521E+11 | 0.496427E+10 | ||||||||
Minimum of Months | 0.318152E+10 | 7813.99 | 23.35 | 13.37 | 0.364067E+09 | 549.49 | 22.98 | 13.31 | ||
Maximum of Months | 0.969357E+10 | 17240.10 | 42.25 | 26.31 | 0.456295E+09 | 567.11 | 42.50 | 26.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108482E+10 | 3232.96 | 31-JAN-16:10 | 20.95 | 11.21 | 0.229829E+09 | 347.85 | 26-JAN-14:20 | 20.95 | 11.21 |
February | 0.171711E+10 | 6943.93 | 20-FEB-17:03 | 24.33 | 14.52 | 0.223015E+09 | 347.85 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.384128E+10 | 13344.15 | 26-MAR-15:32 | 30.13 | 16.60 | 0.283270E+09 | 347.86 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.600648E+10 | 13988.53 | 30-APR-16:11 | 37.57 | 18.06 | 0.256287E+09 | 347.86 | 21-APR-09:20 | 37.57 | 18.06 |
May | 0.752890E+10 | 14523.89 | 29-MAY-16:33 | 41.03 | 21.41 | 0.278147E+09 | 347.85 | 05-MAY-09:20 | 41.03 | 21.41 |
June | 0.741134E+10 | 14251.94 | 04-JUN-16:02 | 42.22 | 22.27 | 0.277112E+09 | 347.86 | 07-JUN-09:20 | 37.90 | 20.70 |
July | 0.618891E+10 | 13285.82 | 04-JUL-16:32 | 39.83 | 24.41 | 0.257831E+09 | 347.85 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.575855E+10 | 12460.87 | 06-AUG-16:12 | 36.20 | 26.31 | 0.288904E+09 | 347.85 | 28-AUG-09:20 | 31.07 | 27.59 |
September | 0.489380E+10 | 13161.49 | 24-SEP-15:32 | 34.90 | 25.12 | 0.256506E+09 | 347.85 | 26-SEP-09:20 | 28.90 | 21.08 |
October | 0.416631E+10 | 13402.81 | 01-OCT-15:42 | 35.58 | 20.12 | 0.264637E+09 | 347.86 | 03-OCT-09:20 | 28.77 | 19.61 |
November | 0.253467E+10 | 9011.22 | 11-NOV-15:43 | 27.73 | 17.49 | 0.253408E+09 | 347.86 | 13-NOV-10:20 | 23.03 | 14.78 |
December | 0.128148E+10 | 3723.62 | 01-DEC-15:30 | 22.85 | 13.56 | 0.228881E+09 | 347.85 | 28-DEC-14:20 | 24.57 | 15.33 |
Annual Sum or Average | 0.524136E+11 | 0.309783E+10 | ||||||||
Minimum of Months | 0.108482E+10 | 3232.96 | 20.95 | 11.21 | 0.223015E+09 | 347.85 | 20.95 | 11.21 | ||
Maximum of Months | 0.752890E+10 | 14523.89 | 42.22 | 26.31 | 0.288904E+09 | 347.86 | 41.03 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148132E+10 | 1894.71 | 26-JAN-14:10 | 22.35 | 13.84 | 0.369406E+09 | 549.50 | 13-JAN-14:20 | 22.35 | 13.84 |
February | 0.178183E+10 | 3148.17 | 24-FEB-15:00 | 26.40 | 17.38 | 0.358713E+09 | 549.50 | 24-FEB-10:20 | 26.40 | 17.38 |
March | 0.320477E+10 | 4696.20 | 13-MAR-15:20 | 32.77 | 18.67 | 0.448580E+09 | 549.50 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.508911E+10 | 7830.68 | 17-APR-04:02 | 24.68 | 19.16 | 0.403831E+09 | 549.50 | 21-APR-09:20 | 27.77 | 18.93 |
May | 0.760055E+10 | 12297.88 | 29-MAY-15:01 | 41.30 | 21.88 | 0.438744E+09 | 549.52 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.830451E+10 | 12401.81 | 11-JUN-16:31 | 43.20 | 23.09 | 0.437360E+09 | 549.50 | 20-JUN-13:09 | 33.57 | 27.49 |
July | 0.827516E+10 | 12076.86 | 04-JUL-16:32 | 39.83 | 24.41 | 0.407030E+09 | 549.49 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.828419E+10 | 10730.45 | 28-AUG-04:02 | 29.27 | 27.32 | 0.456299E+09 | 549.50 | 21-AUG-13:20 | 29.27 | 27.32 |
September | 0.681892E+10 | 12192.43 | 24-SEP-15:12 | 35.00 | 24.98 | 0.405211E+09 | 549.50 | 11-SEP-13:20 | 35.00 | 24.98 |
October | 0.531414E+10 | 11959.72 | 01-OCT-14:01 | 35.92 | 19.87 | 0.420125E+09 | 549.51 | 30-OCT-09:20 | 21.73 | 16.89 |
November | 0.302397E+10 | 4162.29 | 09-NOV-14:10 | 29.37 | 17.83 | 0.411281E+09 | 549.51 | 06-NOV-10:20 | 29.37 | 17.83 |
December | 0.178084E+10 | 2417.47 | 01-DEC-15:00 | 23.40 | 13.35 | 0.380714E+09 | 549.49 | 27-DEC-14:20 | 23.27 | 15.14 |
Annual Sum or Average | 0.609593E+11 | 0.493729E+10 | ||||||||
Minimum of Months | 0.148132E+10 | 1894.71 | 22.35 | 13.35 | 0.358713E+09 | 549.49 | 21.73 | 13.84 | ||
Maximum of Months | 0.830451E+10 | 12401.81 | 43.20 | 27.32 | 0.456299E+09 | 549.52 | 39.90 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120136E+10 | 2031.86 | 26-JAN-11:00 | 19.70 | 13.19 | 0.251702E+09 | 347.87 | 13-JAN-14:20 | 19.70 | 13.19 |
February | 0.168968E+10 | 3541.74 | 22-FEB-10:40 | 22.60 | 14.39 | 0.235964E+09 | 347.88 | 24-FEB-10:20 | 20.97 | 15.04 |
March | 0.326591E+10 | 5215.80 | 28-MAR-10:30 | 29.80 | 18.26 | 0.286792E+09 | 347.88 | 27-MAR-09:20 | 29.80 | 18.26 |
April | 0.502668E+10 | 10158.25 | 16-APR-11:43 | 37.98 | 21.94 | 0.256316E+09 | 348.02 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.667433E+10 | 10550.62 | 29-MAY-09:01 | 34.05 | 21.14 | 0.278067E+09 | 347.98 | 26-MAY-09:00 | 34.05 | 21.14 |
June | 0.650265E+10 | 10283.58 | 11-JUN-09:51 | 36.60 | 25.06 | 0.277057E+09 | 352.98 | 12-JUN-09:00 | 40.00 | 22.14 |
July | 0.609261E+10 | 10123.55 | 04-JUL-09:52 | 35.20 | 25.12 | 0.257824E+09 | 347.87 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.602577E+10 | 10219.73 | 06-AUG-09:43 | 32.08 | 25.07 | 0.288991E+09 | 347.88 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.532746E+10 | 10090.76 | 24-SEP-10:32 | 32.10 | 25.28 | 0.256680E+09 | 347.88 | 11-SEP-13:20 | 32.10 | 25.28 |
October | 0.466877E+10 | 10133.37 | 09-OCT-11:12 | 30.40 | 20.43 | 0.266570E+09 | 347.88 | 30-OCT-09:20 | 21.73 | 16.89 |
November | 0.286842E+10 | 4233.50 | 13-NOV-10:30 | 23.45 | 14.94 | 0.262393E+09 | 347.88 | 06-NOV-10:20 | 23.45 | 14.94 |
December | 0.154146E+10 | 2789.37 | 01-DEC-10:30 | 19.25 | 11.77 | 0.250695E+09 | 347.88 | 18-DEC-10:20 | 20.37 | 13.79 |
Annual Sum or Average | 0.508851E+11 | 0.316905E+10 | ||||||||
Minimum of Months | 0.120136E+10 | 2031.86 | 19.25 | 11.77 | 0.235964E+09 | 347.87 | 19.70 | 13.19 | ||
Maximum of Months | 0.667433E+10 | 10550.62 | 37.98 | 25.28 | 0.288991E+09 | 352.98 | 40.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254495E+10 | 6811.29 | 30-JAN-13:07 | 19.05 | 11.06 | 0.383161E+09 | 549.51 | 25-JAN-14:00 | 19.05 | 11.06 |
February | 0.350180E+10 | 10147.07 | 20-FEB-11:53 | 24.50 | 13.21 | 0.361386E+09 | 549.67 | 23-FEB-14:09 | 26.30 | 13.93 |
March | 0.638933E+10 | 12668.60 | 12-MAR-16:12 | 31.07 | 19.87 | 0.449284E+09 | 648.03 | 28-MAR-12:09 | 33.22 | 18.26 |
April | 0.875218E+10 | 13556.52 | 28-APR-17:00 | 39.20 | 19.98 | 0.411872E+09 | 741.39 | 27-APR-12:09 | 39.20 | 19.98 |
May | 0.112468E+11 | 14809.23 | 01-MAY-16:50 | 43.07 | 22.15 | 0.454031E+09 | 809.63 | 01-MAY-12:09 | 43.07 | 22.15 |
June | 0.115507E+11 | 15139.89 | 12-JUN-17:00 | 43.90 | 22.35 | 0.451748E+09 | 830.87 | 12-JUN-12:09 | 43.90 | 22.35 |
July | 0.106464E+11 | 13864.41 | 03-JUL-17:00 | 39.50 | 25.70 | 0.414856E+09 | 758.10 | 07-JUL-12:09 | 39.13 | 24.79 |
August | 0.110931E+11 | 13032.69 | 07-AUG-16:50 | 36.68 | 26.89 | 0.462906E+09 | 698.78 | 07-AUG-12:09 | 36.68 | 26.89 |
September | 0.100336E+11 | 13308.84 | 24-SEP-15:12 | 35.00 | 24.98 | 0.414136E+09 | 714.72 | 29-SEP-12:09 | 35.52 | 22.70 |
October | 0.100516E+11 | 14111.18 | 01-OCT-14:01 | 35.92 | 19.87 | 0.433415E+09 | 744.20 | 02-OCT-12:09 | 35.70 | 21.30 |
November | 0.747074E+10 | 13773.42 | 05-NOV-13:32 | 29.23 | 17.18 | 0.414347E+09 | 613.25 | 09-NOV-13:09 | 29.32 | 18.15 |
December | 0.350713E+10 | 11302.84 | 03-DEC-14:33 | 23.90 | 14.21 | 0.387090E+09 | 549.67 | 01-DEC-14:00 | 23.90 | 14.21 |
Annual Sum or Average | 0.967883E+11 | 0.503823E+10 | ||||||||
Minimum of Months | 0.254495E+10 | 6811.29 | 19.05 | 11.06 | 0.361386E+09 | 549.51 | 19.05 | 11.06 | ||
Maximum of Months | 0.115507E+11 | 15139.89 | 43.90 | 26.89 | 0.462906E+09 | 830.87 | 43.90 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125130E+10 | 2688.62 | 31-JAN-16:30 | 20.65 | 11.16 | 0.242600E+09 | 347.85 | 26-JAN-14:20 | 20.65 | 11.16 |
February | 0.160142E+10 | 5068.19 | 20-FEB-16:33 | 24.93 | 14.44 | 0.231089E+09 | 347.85 | 24-FEB-10:20 | 20.97 | 15.04 |
March | 0.315124E+10 | 10612.28 | 12-MAR-16:12 | 31.07 | 19.87 | 0.285795E+09 | 347.86 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.489609E+10 | 10724.72 | 02-APR-16:01 | 33.83 | 20.60 | 0.256261E+09 | 347.86 | 21-APR-09:20 | 27.77 | 18.93 |
May | 0.646006E+10 | 11312.40 | 29-MAY-16:21 | 41.10 | 21.45 | 0.278041E+09 | 347.87 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.668697E+10 | 11327.50 | 11-JUN-16:31 | 43.20 | 23.09 | 0.277075E+09 | 347.86 | 20-JUN-13:09 | 33.57 | 27.49 |
July | 0.600800E+10 | 10776.24 | 04-JUL-16:32 | 39.83 | 24.41 | 0.257809E+09 | 347.85 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.597465E+10 | 10606.24 | 06-AUG-16:22 | 36.15 | 26.34 | 0.288983E+09 | 347.85 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.532018E+10 | 11296.54 | 24-SEP-15:52 | 34.80 | 25.26 | 0.256713E+09 | 347.85 | 11-SEP-13:20 | 34.80 | 25.26 |
October | 0.454909E+10 | 11184.75 | 01-OCT-16:42 | 34.58 | 20.20 | 0.266495E+09 | 347.86 | 30-OCT-09:20 | 21.73 | 16.89 |
November | 0.284843E+10 | 9689.91 | 12-NOV-15:12 | 27.97 | 15.72 | 0.261838E+09 | 347.86 | 06-NOV-10:20 | 27.97 | 15.72 |
December | 0.154824E+10 | 3438.96 | 01-DEC-15:40 | 22.67 | 13.61 | 0.245673E+09 | 347.85 | 01-DEC-10:20 | 22.67 | 13.61 |
Annual Sum or Average | 0.502957E+11 | 0.314837E+10 | ||||||||
Minimum of Months | 0.125130E+10 | 2688.62 | 20.65 | 11.16 | 0.231089E+09 | 347.85 | 20.65 | 11.16 | ||
Maximum of Months | 0.668697E+10 | 11327.50 | 43.20 | 26.34 | 0.288983E+09 | 347.87 | 39.90 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143733E+10 | 2225.56 | 26-JAN-14:40 | 21.90 | 13.73 | 0.366620E+09 | 549.49 | 12-JAN-14:20 | 21.90 | 13.73 |
February | 0.198194E+10 | 3797.71 | 23-FEB-14:40 | 26.00 | 14.03 | 0.361177E+09 | 549.50 | 24-FEB-10:20 | 20.97 | 15.04 |
March | 0.402547E+10 | 5680.80 | 13-MAR-15:20 | 32.77 | 18.67 | 0.450924E+09 | 549.51 | 30-MAR-09:20 | 25.33 | 18.26 |
April | 0.612636E+10 | 12607.16 | 30-APR-16:01 | 37.68 | 18.13 | 0.404631E+09 | 549.51 | 21-APR-09:20 | 37.68 | 18.13 |
May | 0.836577E+10 | 13086.31 | 28-MAY-16:31 | 41.90 | 19.53 | 0.439031E+09 | 549.51 | 01-MAY-09:30 | 41.90 | 19.53 |
June | 0.847331E+10 | 12922.21 | 11-JUN-16:41 | 43.15 | 23.06 | 0.437473E+09 | 549.51 | 12-JUN-09:30 | 39.25 | 21.97 |
July | 0.776336E+10 | 12455.81 | 04-JUL-17:12 | 40.00 | 24.23 | 0.407026E+09 | 549.51 | 07-JUL-09:30 | 36.30 | 24.34 |
August | 0.735851E+10 | 11399.52 | 06-AUG-16:12 | 36.20 | 26.31 | 0.456161E+09 | 549.50 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.591125E+10 | 11271.54 | 24-SEP-14:41 | 35.10 | 24.80 | 0.404972E+09 | 549.49 | 08-SEP-13:20 | 35.10 | 24.80 |
October | 0.471878E+10 | 10515.10 | 01-OCT-15:31 | 35.67 | 20.08 | 0.419285E+09 | 549.50 | 30-OCT-09:20 | 21.73 | 16.89 |
November | 0.280713E+10 | 4112.29 | 09-NOV-14:10 | 29.37 | 17.83 | 0.407630E+09 | 549.51 | 06-NOV-10:20 | 29.37 | 17.83 |
December | 0.167446E+10 | 2346.11 | 01-DEC-15:00 | 23.40 | 13.35 | 0.372316E+09 | 549.50 | 28-DEC-14:20 | 24.57 | 15.33 |
Annual Sum or Average | 0.606437E+11 | 0.492725E+10 | ||||||||
Minimum of Months | 0.143733E+10 | 2225.56 | 21.90 | 13.35 | 0.361177E+09 | 549.49 | 20.97 | 13.73 | ||
Maximum of Months | 0.847331E+10 | 13086.31 | 43.15 | 26.31 | 0.456161E+09 | 549.51 | 41.90 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.987315E+09 | 4532.05 | 27-JAN-13:02 | 16.08 | 11.85 | 0.182514E+09 | 356.45 | 23-JAN-11:09 | 16.08 | 11.85 |
February | 0.168228E+10 | 5137.09 | 22-FEB-11:05 | 23.90 | 14.68 | 0.173857E+09 | 356.46 | 24-FEB-11:09 | 22.55 | 15.56 |
March | 0.361491E+10 | 7934.22 | 28-MAR-12:02 | 33.22 | 18.26 | 0.212457E+09 | 356.46 | 27-MAR-10:09 | 33.22 | 18.26 |
April | 0.549144E+10 | 11594.42 | 30-APR-08:42 | 27.95 | 14.63 | 0.190640E+09 | 356.47 | 28-APR-10:09 | 27.95 | 14.63 |
May | 0.685657E+10 | 11417.34 | 28-MAY-09:11 | 34.93 | 19.83 | 0.206644E+09 | 356.70 | 03-MAY-10:09 | 34.93 | 19.83 |
June | 0.632874E+10 | 10904.49 | 11-JUN-10:02 | 36.98 | 25.11 | 0.205574E+09 | 356.69 | 05-JUN-10:09 | 36.98 | 25.11 |
July | 0.550479E+10 | 10890.71 | 02-JUL-09:31 | 35.03 | 25.92 | 0.191909E+09 | 356.45 | 07-JUL-12:09 | 39.13 | 24.79 |
August | 0.515402E+10 | 10120.62 | 27-AUG-10:32 | 32.60 | 28.69 | 0.214244E+09 | 356.45 | 21-AUG-14:09 | 32.60 | 28.69 |
September | 0.445293E+10 | 10555.74 | 17-SEP-09:53 | 30.50 | 25.41 | 0.190604E+09 | 356.45 | 13-SEP-14:09 | 30.50 | 25.41 |
October | 0.394366E+10 | 11139.22 | 01-OCT-10:12 | 30.47 | 19.50 | 0.197681E+09 | 356.46 | 30-OCT-10:09 | 24.07 | 17.44 |
November | 0.240328E+10 | 5271.81 | 01-NOV-10:05 | 23.77 | 15.01 | 0.193329E+09 | 356.46 | 16-NOV-11:09 | 24.57 | 17.22 |
December | 0.121728E+10 | 4455.28 | 15-DEC-13:02 | 17.33 | 13.63 | 0.181570E+09 | 356.45 | 11-DEC-11:09 | 17.33 | 13.63 |
Annual Sum or Average | 0.476372E+11 | 0.234102E+10 | ||||||||
Minimum of Months | 0.987315E+09 | 4455.28 | 16.08 | 11.85 | 0.173857E+09 | 356.45 | 16.08 | 11.85 | ||
Maximum of Months | 0.685657E+10 | 11594.42 | 36.98 | 28.69 | 0.214244E+09 | 356.70 | 39.13 | 28.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355174E+10 | 7655.60 | 12-JAN-14:00 | 23.30 | 13.98 | 0.399201E+09 | 549.50 | 12-JAN-14:20 | 23.40 | 14.05 |
February | 0.432518E+10 | 14007.37 | 20-FEB-14:12 | 26.37 | 13.66 | 0.371859E+09 | 550.06 | 28-FEB-14:20 | 24.73 | 15.58 |
March | 0.674893E+10 | 13723.14 | 12-MAR-12:23 | 30.20 | 18.77 | 0.452923E+09 | 550.84 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.776234E+10 | 13551.29 | 30-APR-12:02 | 35.98 | 18.37 | 0.404997E+09 | 550.31 | 12-APR-13:20 | 35.98 | 18.37 |
May | 0.872734E+10 | 13423.00 | 28-MAY-15:11 | 42.23 | 19.17 | 0.439062E+09 | 550.54 | 30-MAY-13:20 | 39.27 | 24.02 |
June | 0.841034E+10 | 13088.86 | 11-JUN-16:41 | 43.15 | 23.06 | 0.437456E+09 | 550.53 | 05-JUN-13:20 | 43.15 | 23.06 |
July | 0.781653E+10 | 12625.65 | 04-JUL-17:12 | 40.00 | 24.23 | 0.407029E+09 | 550.60 | 05-JUL-13:20 | 37.90 | 25.56 |
August | 0.779356E+10 | 12325.93 | 06-AUG-14:12 | 36.03 | 26.33 | 0.456221E+09 | 550.45 | 08-AUG-13:20 | 36.20 | 26.46 |
September | 0.736831E+10 | 13749.29 | 24-SEP-12:02 | 33.93 | 25.01 | 0.405242E+09 | 556.36 | 28-SEP-13:50 | 35.43 | 22.76 |
October | 0.830043E+10 | 14660.46 | 29-OCT-13:22 | 29.20 | 17.95 | 0.421650E+09 | 586.65 | 02-OCT-13:50 | 29.20 | 17.95 |
November | 0.697184E+10 | 14649.93 | 12-NOV-13:22 | 27.95 | 16.10 | 0.413607E+09 | 557.66 | 13-NOV-14:09 | 28.20 | 15.99 |
December | 0.427441E+10 | 10332.15 | 03-DEC-14:53 | 23.60 | 14.22 | 0.393860E+09 | 549.78 | 01-DEC-14:20 | 23.60 | 14.22 |
Annual Sum or Average | 0.820509E+11 | 0.500311E+10 | ||||||||
Minimum of Months | 0.355174E+10 | 7655.60 | 23.30 | 13.66 | 0.371859E+09 | 549.50 | 23.40 | 14.05 | ||
Maximum of Months | 0.872734E+10 | 14660.46 | 43.15 | 26.33 | 0.456221E+09 | 586.65 | 43.15 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124581E+10 | 3200.85 | 31-JAN-16:10 | 20.95 | 11.21 | 0.237930E+09 | 347.85 | 26-JAN-14:20 | 20.95 | 11.21 |
February | 0.178648E+10 | 9112.36 | 20-FEB-16:12 | 25.27 | 14.30 | 0.230017E+09 | 347.85 | 24-FEB-10:20 | 20.97 | 15.04 |
March | 0.371162E+10 | 11356.06 | 26-MAR-17:03 | 28.93 | 15.95 | 0.286027E+09 | 347.86 | 30-MAR-09:20 | 25.33 | 18.26 |
April | 0.554883E+10 | 12191.65 | 30-APR-16:01 | 37.68 | 18.13 | 0.256433E+09 | 347.86 | 21-APR-09:20 | 37.68 | 18.13 |
May | 0.685068E+10 | 12580.58 | 28-MAY-16:31 | 41.90 | 19.53 | 0.278090E+09 | 347.86 | 01-MAY-09:30 | 41.90 | 19.53 |
June | 0.670359E+10 | 12169.82 | 11-JUN-16:41 | 43.15 | 23.06 | 0.277072E+09 | 347.86 | 12-JUN-09:30 | 39.25 | 21.97 |
July | 0.560373E+10 | 12200.07 | 02-JUL-16:12 | 40.37 | 26.43 | 0.257768E+09 | 347.86 | 07-JUL-09:30 | 36.30 | 24.34 |
August | 0.530509E+10 | 10880.40 | 06-AUG-17:32 | 35.47 | 26.59 | 0.288861E+09 | 347.85 | 28-AUG-09:20 | 31.07 | 27.59 |
September | 0.461970E+10 | 11584.60 | 24-SEP-15:21 | 34.95 | 25.05 | 0.256520E+09 | 347.85 | 12-SEP-09:20 | 34.95 | 25.05 |
October | 0.402425E+10 | 11767.76 | 01-OCT-15:31 | 35.67 | 20.08 | 0.265808E+09 | 347.86 | 30-OCT-09:20 | 21.73 | 16.89 |
November | 0.260709E+10 | 10691.61 | 12-NOV-15:22 | 27.85 | 15.71 | 0.259023E+09 | 347.86 | 06-NOV-10:20 | 27.85 | 15.71 |
December | 0.146073E+10 | 3685.09 | 01-DEC-15:30 | 22.85 | 13.56 | 0.238711E+09 | 347.85 | 28-DEC-14:20 | 24.57 | 15.33 |
Annual Sum or Average | 0.494676E+11 | 0.313226E+10 | ||||||||
Minimum of Months | 0.124581E+10 | 3200.85 | 20.95 | 11.21 | 0.230017E+09 | 347.85 | 20.95 | 11.21 | ||
Maximum of Months | 0.685068E+10 | 12580.58 | 43.15 | 26.59 | 0.288861E+09 | 347.86 | 41.90 | 27.59 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114313E+10 | 11678.55 | 02-JAN-06:17 | 6.50 |
February | 0.648755E+09 | 4434.87 | 02-FEB-07:02 | 7.12 |
March | 0.353307E+09 | 3790.57 | 13-MAR-05:12 | 20.73 |
April | 83300157.71 | 4866.16 | 26-APR-05:03 | 24.50 |
May | 23247642.81 | 5802.25 | 15-MAY-04:02 | 24.27 |
June | 11171399.85 | 4016.18 | 28-JUN-05:03 | 26.50 |
July | 8838830.63 | 3607.14 | 19-JUL-05:03 | 26.00 |
August | 11854484.42 | 5065.22 | 21-AUG-04:02 | 25.67 |
September | 23843658.21 | 5885.26 | 25-SEP-04:02 | 26.32 |
October | 0.224423E+09 | 4441.73 | 04-OCT-05:03 | 25.07 |
November | 0.546971E+09 | 3347.39 | 24-NOV-06:03 | 10.50 |
December | 0.940186E+09 | 6957.26 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.401903E+10 | |||
Minimum of Months | 8838830.63 | 3347.39 | 6.25 | |
Maximum of Months | 0.114313E+10 | 11678.55 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.686525E+09 | 3057.29 | 02-JAN-07:02 | 6.78 |
February | 0.165748E+09 | 3478.11 | 05-FEB-13:43 | 23.23 |
March | 17450121.89 | 2476.73 | 26-MAR-14:23 | 30.30 |
April | 16707629.15 | 2295.69 | 02-APR-15:21 | 33.85 |
May | 17327089.95 | 2639.69 | 18-MAY-04:02 | 30.20 |
June | 19065030.71 | 2955.48 | 30-JUN-04:02 | 30.45 |
July | 20012415.38 | 2941.34 | 14-JUL-04:02 | 29.58 |
August | 15851101.65 | 2953.74 | 09-AUG-04:02 | 30.32 |
September | 15935873.44 | 1963.75 | 24-SEP-14:41 | 35.10 |
October | 23535374.74 | 2627.56 | 29-OCT-14:02 | 29.27 |
November | 46132294.60 | 3000.22 | 05-NOV-14:52 | 29.00 |
December | 0.348183E+09 | 4061.58 | 24-DEC-14:03 | 24.32 |
Annual Sum or Average | 0.139247E+10 | |||
Minimum of Months | 15851101.65 | 1963.75 | 6.78 | |
Maximum of Months | 0.686525E+09 | 4061.58 | 35.10 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293209E+09 | 1810.71 | 08-JAN-12:55 | 20.10 |
February | 38052168.88 | 1767.26 | 19-FEB-12:43 | 23.73 |
March | 9996223.10 | 1238.40 | 05-MAR-10:03 | 23.20 |
April | 10936950.88 | 1687.87 | 27-APR-04:03 | 29.08 |
May | 16263211.46 | 2392.34 | 18-MAY-04:02 | 30.20 |
June | 19072346.06 | 2899.03 | 23-JUN-04:02 | 30.55 |
July | 27586412.98 | 3314.66 | 14-JUL-04:02 | 29.58 |
August | 23371735.83 | 3478.83 | 31-AUG-04:02 | 28.85 |
September | 23931001.35 | 3159.03 | 01-SEP-04:03 | 26.77 |
October | 25159250.52 | 2716.25 | 04-OCT-04:03 | 25.08 |
November | 29341463.47 | 2364.25 | 26-NOV-11:13 | 24.33 |
December | 76301926.31 | 3119.31 | 24-DEC-13:53 | 24.30 |
Annual Sum or Average | 0.593222E+09 | |||
Minimum of Months | 9996223.10 | 1238.40 | 20.10 | |
Maximum of Months | 0.293209E+09 | 3478.83 | 30.55 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8712062.80 | 15581.83 | 03-JAN-07:02 | 5.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 8712062.80 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 8712062.80 | 15581.83 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165611E+09 | 20748.66 | 02-JAN-06:11 | 6.50 |
February | 2258330.44 | 15251.50 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 8553012.66 | 19689.93 | 21-DEC-07:01 | 5.68 |
Annual Sum or Average | 0.176423E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.68 | |
Maximum of Months | 0.165611E+09 | 20748.66 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360172E+09 | 9320.32 | 02-JAN-06:11 | 6.50 |
February | 47250480.58 | 8328.40 | 13-FEB-07:03 | 10.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 2894374.48 | 8147.27 | 27-NOV-07:02 | 10.02 |
December | 0.114348E+09 | 8461.48 | 27-DEC-07:03 | 11.38 |
Annual Sum or Average | 0.524665E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.360172E+09 | 9320.32 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146403E+09 | 5896.72 | 02-JAN-06:11 | 6.50 |
February | 16221876.88 | 5347.86 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 1133893.54 | 4568.49 | 27-NOV-07:02 | 10.02 |
December | 44250375.26 | 5401.08 | 27-DEC-07:03 | 11.38 |
Annual Sum or Average | 0.208010E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.146403E+09 | 5896.72 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204440E+09 | 9093.03 | 02-JAN-06:11 | 6.50 |
February | 25683798.71 | 8072.87 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 568309.61 | 3368.96 | 27-NOV-07:02 | 10.02 |
December | 57239961.63 | 8410.85 | 12-DEC-07:03 | 11.27 |
Annual Sum or Average | 0.287932E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.204440E+09 | 9093.03 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216325E+09 | 5729.89 | 02-JAN-06:11 | 6.50 |
February | 29084185.27 | 5387.17 | 13-FEB-07:03 | 10.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 1344945.43 | 4498.90 | 27-NOV-07:02 | 10.02 |
December | 69621945.25 | 5501.53 | 12-DEC-07:03 | 11.27 |
Annual Sum or Average | 0.316376E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.216325E+09 | 5729.89 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33687080.13 | 5346.84 | 02-JAN-07:04 | 6.78 |
February | 98457.05 | 984.57 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 189426.03 | 1262.84 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 33974963.21 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 33687080.13 | 5346.84 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9026221.60 | 3826.72 | 02-JAN-06:12 | 6.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 9026221.60 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 9026221.60 | 3826.72 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498296E+09 | 5991.48 | 02-JAN-07:04 | 6.78 |
February | 0.324597E+09 | 5916.92 | 02-FEB-08:00 | 7.70 |
March | 73792187.59 | 5401.38 | 03-MAR-07:08 | 14.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 87614866.42 | 5352.44 | 22-NOV-07:20 | 13.33 |
December | 0.364342E+09 | 5826.90 | 20-DEC-07:10 | 7.70 |
Annual Sum or Average | 0.134864E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.78 | |
Maximum of Months | 0.498296E+09 | 5991.48 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12781393.15 | 3549.62 | 02-JAN-06:12 | 6.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 12781393.15 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 12781393.15 | 3549.62 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75975966.54 | 6733.34 | 02-JAN-06:12 | 6.50 |
February | 1363720.53 | 4102.37 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 4349860.03 | 5999.00 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 81689547.10 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 75975966.54 | 6733.34 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31662098.14 | 4337.99 | 02-JAN-06:14 | 6.50 |
February | 840443.00 | 2755.88 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 1843190.57 | 4012.20 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 34345731.70 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 31662098.14 | 4337.99 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36830313.22 | 6532.02 | 02-JAN-06:12 | 6.50 |
February | 537614.41 | 2245.61 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 1579741.38 | 6077.06 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 38947669.01 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 36830313.22 | 6532.02 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44318893.48 | 4415.28 | 02-JAN-06:14 | 6.50 |
February | 796863.15 | 3012.31 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 2653105.91 | 4012.45 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 47768862.55 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 44318893.48 | 4415.28 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350405E+10 | 3682.52 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.317847E+10 | 3682.52 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.377661E+10 | 3682.52 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.337367E+10 | 3682.52 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.364033E+10 | 3682.52 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.362266E+10 | 3682.52 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.339134E+10 | 3682.52 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.377661E+10 | 3682.52 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.337367E+10 | 3682.52 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.350405E+10 | 3682.52 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.346281E+10 | 3682.52 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.339134E+10 | 3682.52 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.419956E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.317847E+10 | 3682.52 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.377661E+10 | 3682.52 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350405E+10 | 3682.52 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.317847E+10 | 3682.52 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.377661E+10 | 3682.52 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.337367E+10 | 3682.52 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.364033E+10 | 3682.52 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.362266E+10 | 3682.52 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.339134E+10 | 3682.52 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.377661E+10 | 3682.52 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.337367E+10 | 3682.52 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.350405E+10 | 3682.52 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.346281E+10 | 3682.52 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.339134E+10 | 3682.52 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.419956E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.317847E+10 | 3682.52 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.377661E+10 | 3682.52 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350405E+10 | 3682.52 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.317847E+10 | 3682.52 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.377661E+10 | 3682.52 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.337367E+10 | 3682.52 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.364033E+10 | 3682.52 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.362266E+10 | 3682.52 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.339134E+10 | 3682.52 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.377661E+10 | 3682.52 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.337367E+10 | 3682.52 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.350405E+10 | 3682.52 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.346281E+10 | 3682.52 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.339134E+10 | 3682.52 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.419956E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.317847E+10 | 3682.52 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.377661E+10 | 3682.52 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.453389E+09 | 645.94 | 18-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.399654E+09 | 632.40 | 10-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.451696E+09 | 638.32 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.395443E+09 | 411.51 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.417528E+09 | 436.67 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.415570E+09 | 435.91 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.398561E+09 | 613.57 | 26-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.447239E+09 | 633.74 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.407663E+09 | 653.94 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.434200E+09 | 689.88 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.444790E+09 | 673.23 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.445723E+09 | 679.50 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.511146E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.395443E+09 | 411.51 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.453389E+09 | 689.88 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282770E+09 | 404.54 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.250772E+09 | 402.24 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.284632E+09 | 362.70 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.250220E+09 | 234.43 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265713E+09 | 267.96 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.264415E+09 | 268.14 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.252636E+09 | 373.99 | 26-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.282700E+09 | 388.05 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.257111E+09 | 402.12 | 08-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.272076E+09 | 429.35 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279455E+09 | 435.62 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.278103E+09 | 433.34 | 29-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.322060E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.250220E+09 | 234.43 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.284632E+09 | 435.62 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435320E+09 | 620.17 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.390385E+09 | 611.71 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.448682E+09 | 630.54 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.396361E+09 | 415.64 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.421158E+09 | 516.03 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.419086E+09 | 521.10 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.401549E+09 | 622.92 | 26-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.448481E+09 | 637.88 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.406344E+09 | 652.71 | 08-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.427595E+09 | 686.26 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.429523E+09 | 612.76 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.425490E+09 | 646.33 | 29-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.504997E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.390385E+09 | 415.64 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.448682E+09 | 686.26 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280805E+09 | 411.85 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249046E+09 | 404.86 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.286015E+09 | 417.50 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251130E+09 | 332.64 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.266248E+09 | 345.79 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.264970E+09 | 346.50 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.254408E+09 | 399.28 | 26-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.285209E+09 | 409.07 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.258827E+09 | 418.98 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.274864E+09 | 438.70 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.274786E+09 | 393.72 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.273597E+09 | 403.78 | 29-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.321990E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.249046E+09 | 332.64 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.286015E+09 | 438.70 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451629E+09 | 640.95 | 18-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.398391E+09 | 626.89 | 10-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.450863E+09 | 632.86 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.395105E+09 | 408.41 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.417152E+09 | 434.66 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.415079E+09 | 433.84 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.397728E+09 | 607.27 | 26-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.446294E+09 | 628.24 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.406944E+09 | 649.24 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.433131E+09 | 686.58 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.443354E+09 | 669.07 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.443968E+09 | 675.75 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.509964E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.395105E+09 | 408.41 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.451629E+09 | 686.58 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281899E+09 | 401.84 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.250329E+09 | 399.50 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.284253E+09 | 357.40 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.249995E+09 | 234.43 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265467E+09 | 266.35 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.264107E+09 | 266.53 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.252216E+09 | 370.32 | 26-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.282259E+09 | 384.64 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.256732E+09 | 399.08 | 08-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.271626E+09 | 427.35 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.278915E+09 | 433.85 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.277531E+09 | 431.53 | 29-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.321533E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.249995E+09 | 234.43 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.284253E+09 | 433.85 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435002E+09 | 613.92 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.389815E+09 | 605.25 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.447988E+09 | 624.69 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.395953E+09 | 412.76 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.420584E+09 | 505.99 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.418522E+09 | 511.28 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.400658E+09 | 617.07 | 26-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.447522E+09 | 632.59 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.405688E+09 | 647.96 | 08-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.427012E+09 | 682.78 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.428845E+09 | 591.25 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.424818E+09 | 641.02 | 29-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.504241E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.389815E+09 | 412.76 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.447988E+09 | 682.78 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.279954E+09 | 409.39 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.248550E+09 | 402.20 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.285500E+09 | 415.24 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.250676E+09 | 327.28 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265961E+09 | 341.35 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.264527E+09 | 342.08 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.253882E+09 | 396.47 | 26-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.284641E+09 | 406.55 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.258214E+09 | 416.76 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.274352E+09 | 437.08 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.274325E+09 | 390.35 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.272952E+09 | 400.31 | 29-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.321353E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.248550E+09 | 327.28 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.285500E+09 | 437.08 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.453388E+09 | 645.93 | 18-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.399652E+09 | 632.38 | 10-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.451695E+09 | 638.30 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.395443E+09 | 411.51 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.417528E+09 | 436.67 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.415569E+09 | 435.90 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.398560E+09 | 613.55 | 26-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.447238E+09 | 633.72 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.407662E+09 | 653.93 | 08-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.434199E+09 | 689.87 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.444789E+09 | 673.22 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.445722E+09 | 679.49 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.511144E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.395443E+09 | 411.51 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.453388E+09 | 689.87 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.282770E+09 | 404.53 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.250771E+09 | 402.23 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.284632E+09 | 362.69 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.250220E+09 | 234.43 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265708E+09 | 267.96 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.264415E+09 | 268.13 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.252635E+09 | 373.98 | 26-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.282691E+09 | 388.04 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.257111E+09 | 402.12 | 08-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.272076E+09 | 429.35 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279455E+09 | 435.62 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.278103E+09 | 433.33 | 29-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.322059E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.250220E+09 | 234.43 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.284632E+09 | 435.62 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435320E+09 | 620.15 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.390385E+09 | 611.69 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.448681E+09 | 630.53 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.396361E+09 | 415.63 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.421157E+09 | 516.01 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.419085E+09 | 521.07 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.401547E+09 | 622.91 | 26-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.448479E+09 | 637.87 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.406344E+09 | 652.70 | 08-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.427594E+09 | 686.25 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.429522E+09 | 612.75 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.425489E+09 | 646.32 | 29-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.504996E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.390385E+09 | 415.63 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.448681E+09 | 686.25 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280804E+09 | 411.85 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249045E+09 | 404.85 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.286014E+09 | 417.50 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251122E+09 | 332.63 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.266247E+09 | 345.78 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.264969E+09 | 346.49 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.254408E+09 | 399.27 | 26-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.285208E+09 | 409.06 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.258826E+09 | 418.97 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.274863E+09 | 438.69 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.274786E+09 | 393.72 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.273597E+09 | 403.77 | 29-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.321989E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.249045E+09 | 332.63 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.286014E+09 | 438.69 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.350405E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.317847E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.377661E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.337367E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.364033E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.362266E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.339134E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.377661E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.337367E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.350405E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.346281E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.339134E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.419956E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.317847E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.377661E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.350405E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.317847E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.377661E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.337367E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.364033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.362266E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.339134E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.377661E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.337367E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.350405E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.346281E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.339134E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.419956E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.317847E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.377661E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.350405E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.317847E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.377661E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.337367E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.364033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.362266E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.339134E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.377661E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.337367E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.350405E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.346281E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.339134E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.419956E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.317847E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.377661E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.453389E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80902.89 | 87536516.10 |
February | 0.901968E+09 | 0.399654E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2309808.07 | 98273384.34 |
March | 0.107774E+10 | 0.451696E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21957783.03 | 65175257.14 |
April | 0.956342E+09 | 0.395443E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86919183.48 | 5750780.47 |
May | 0.103597E+10 | 0.417528E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186007E+09 | 2221146.08 |
June | 0.103308E+10 | 0.415570E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125964E+09 | 1237161.76 |
July | 0.959235E+09 | 0.398561E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155880E+09 | 464258.92 |
August | 0.107774E+10 | 0.447239E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87542846.26 | 897226.99 |
September | 0.956342E+09 | 0.407663E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52005977.17 | 1674649.04 |
October | 0.994195E+09 | 0.434200E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28352464.67 | 5313506.26 |
November | 0.984487E+09 | 0.444790E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6874346.52 | 20229088.14 |
December | 0.959235E+09 | 0.445723E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 800221.11 | 79943001.50 |
Annual Sum or Average | 0.119305E+11 | 0.511146E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754694E+09 | 0.368716E+09 |
Minimum of Months | 0.901968E+09 | 0.395443E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80902.89 | 464258.92 |
Maximum of Months | 0.107774E+10 | 0.453389E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186007E+09 | 98273384.34 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.282770E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3689.50 | 62395096.96 |
February | 0.571020E+09 | 0.250772E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 822175.72 | 70752789.66 |
March | 0.682301E+09 | 0.284632E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13255008.61 | 45875976.36 |
April | 0.605444E+09 | 0.250220E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56347210.45 | 4332656.33 |
May | 0.655854E+09 | 0.265713E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122480E+09 | 1545745.47 |
June | 0.654023E+09 | 0.264415E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83462806.29 | 852200.54 |
July | 0.607275E+09 | 0.252636E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103189E+09 | 307120.36 |
August | 0.682301E+09 | 0.282700E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57842338.45 | 608973.44 |
September | 0.605444E+09 | 0.257111E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34208604.02 | 1130925.20 |
October | 0.629407E+09 | 0.272076E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17834155.36 | 3918580.55 |
November | 0.623262E+09 | 0.279455E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3602804.42 | 14975776.26 |
December | 0.607275E+09 | 0.278103E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204166.11 | 57343739.36 |
Annual Sum or Average | 0.755301E+10 | 0.322060E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493252E+09 | 0.264040E+09 |
Minimum of Months | 0.571020E+09 | 0.250220E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3689.50 | 307120.36 |
Maximum of Months | 0.682301E+09 | 0.284632E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122480E+09 | 70752789.66 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.435320E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102812E+09 |
February | 0.901968E+09 | 0.390385E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1069941.37 | 0.114482E+09 |
March | 0.107774E+10 | 0.448682E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19320410.72 | 70898164.39 |
April | 0.956342E+09 | 0.396361E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85344409.36 | 6097659.96 |
May | 0.103597E+10 | 0.421158E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185840E+09 | 2251815.94 |
June | 0.103308E+10 | 0.419086E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126045E+09 | 1217725.48 |
July | 0.959235E+09 | 0.401549E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155869E+09 | 462050.03 |
August | 0.107774E+10 | 0.448481E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87197225.94 | 909812.05 |
September | 0.956342E+09 | 0.406344E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51145646.22 | 1734803.94 |
October | 0.994195E+09 | 0.427595E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25987999.15 | 5921185.75 |
November | 0.984487E+09 | 0.429523E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4710068.00 | 24743253.93 |
December | 0.959235E+09 | 0.425490E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19200.18 | 97080658.17 |
Annual Sum or Average | 0.119305E+11 | 0.504997E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742550E+09 | 0.428611E+09 |
Minimum of Months | 0.901968E+09 | 0.390385E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462050.03 |
Maximum of Months | 0.107774E+10 | 0.448682E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185840E+09 | 0.114482E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.280805E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62097608.83 |
February | 0.570983E+09 | 0.249046E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 816875.57 | 69966724.96 |
March | 0.682256E+09 | 0.286015E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13520128.09 | 46926071.81 |
April | 0.605404E+09 | 0.251130E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56607192.64 | 4283905.28 |
May | 0.655811E+09 | 0.266248E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122184E+09 | 1645655.61 |
June | 0.653980E+09 | 0.264970E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82922119.51 | 888321.25 |
July | 0.607235E+09 | 0.254408E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102832E+09 | 304929.76 |
August | 0.682256E+09 | 0.285209E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57593818.39 | 618779.86 |
September | 0.605404E+09 | 0.258827E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33918196.42 | 1168212.72 |
October | 0.629366E+09 | 0.274864E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18175522.55 | 3675728.96 |
November | 0.623221E+09 | 0.274786E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3795246.73 | 14311586.81 |
December | 0.607235E+09 | 0.273597E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171178.07 | 56333422.34 |
Annual Sum or Average | 0.755252E+10 | 0.321990E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492537E+09 | 0.262221E+09 |
Minimum of Months | 0.570983E+09 | 0.249046E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304929.76 |
Maximum of Months | 0.682256E+09 | 0.286015E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122184E+09 | 69966724.96 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.451629E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21327.81 | 53615898.62 |
February | 0.901968E+09 | 0.398391E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1505272.59 | 56223187.98 |
March | 0.107774E+10 | 0.450863E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13232584.53 | 34068503.80 |
April | 0.956342E+09 | 0.395105E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49438325.94 | 2662505.56 |
May | 0.103597E+10 | 0.417152E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102187E+09 | 941686.46 |
June | 0.103308E+10 | 0.415079E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68226483.48 | 596138.53 |
July | 0.959235E+09 | 0.397728E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84277687.69 | 289355.11 |
August | 0.107774E+10 | 0.446294E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47155558.20 | 533742.23 |
September | 0.956342E+09 | 0.406944E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27943852.52 | 1174496.65 |
October | 0.994195E+09 | 0.433131E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15568691.12 | 3380348.41 |
November | 0.984487E+09 | 0.443354E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3569806.50 | 12727552.25 |
December | 0.959235E+09 | 0.443968E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261771.43 | 50555936.28 |
Annual Sum or Average | 0.119305E+11 | 0.509964E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413388E+09 | 0.216769E+09 |
Minimum of Months | 0.901968E+09 | 0.395105E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21327.81 | 289355.11 |
Maximum of Months | 0.107774E+10 | 0.451629E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102187E+09 | 56223187.98 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.281899E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38477516.42 |
February | 0.571020E+09 | 0.250329E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 524605.64 | 40913563.29 |
March | 0.682301E+09 | 0.284253E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7633413.42 | 24854833.37 |
April | 0.605444E+09 | 0.249995E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30866201.07 | 2173899.07 |
May | 0.655854E+09 | 0.265467E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66252620.68 | 746979.94 |
June | 0.654023E+09 | 0.264107E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44824506.45 | 441843.47 |
July | 0.607275E+09 | 0.252216E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55401342.58 | 204710.98 |
August | 0.682301E+09 | 0.282259E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30853273.64 | 376007.85 |
September | 0.605444E+09 | 0.256732E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18258192.94 | 827743.25 |
October | 0.629407E+09 | 0.271626E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9664139.34 | 2491538.93 |
November | 0.623262E+09 | 0.278915E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1947914.45 | 9297293.22 |
December | 0.607275E+09 | 0.277531E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43877.52 | 35990993.55 |
Annual Sum or Average | 0.755301E+10 | 0.321533E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266270E+09 | 0.156797E+09 |
Minimum of Months | 0.571020E+09 | 0.249995E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204710.98 |
Maximum of Months | 0.682301E+09 | 0.284253E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66252620.68 | 40913563.29 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.435002E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272594E+10 |
February | 0.901968E+09 | 0.389815E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64035641.90 | 0.158881E+10 |
March | 0.107774E+10 | 0.447988E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895223E+09 | 0.731555E+09 |
April | 0.956342E+09 | 0.395953E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239179E+10 | 97674808.67 |
May | 0.103597E+10 | 0.420584E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387688E+10 | 1470061.11 |
June | 0.103308E+10 | 0.418522E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391634E+10 | 673195.87 |
July | 0.959235E+09 | 0.400658E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270167E+10 | 306576.94 |
August | 0.107774E+10 | 0.447522E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265588E+10 | 893151.62 |
September | 0.956342E+09 | 0.405688E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195578E+10 | 4443788.37 |
October | 0.994195E+09 | 0.427012E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136379E+10 | 0.322464E+09 |
November | 0.984487E+09 | 0.428845E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436898E+09 | 0.100696E+10 |
December | 0.959235E+09 | 0.424818E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 661254.54 | 0.236476E+10 |
Annual Sum or Average | 0.119305E+11 | 0.504241E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202590E+11 | 0.884594E+10 |
Minimum of Months | 0.901968E+09 | 0.389815E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306576.94 |
Maximum of Months | 0.107774E+10 | 0.447988E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391634E+10 | 0.272594E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.279954E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38353010.99 |
February | 0.570983E+09 | 0.248550E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 482662.08 | 40620560.74 |
March | 0.682256E+09 | 0.285500E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7564205.47 | 25644291.91 |
April | 0.605404E+09 | 0.250676E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30978993.38 | 2229092.92 |
May | 0.655811E+09 | 0.265961E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65895605.77 | 802215.16 |
June | 0.653980E+09 | 0.264527E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44360203.12 | 489381.35 |
July | 0.607235E+09 | 0.253882E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55143431.15 | 205829.24 |
August | 0.682256E+09 | 0.284641E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30714360.25 | 380650.89 |
September | 0.605404E+09 | 0.258214E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18059710.89 | 873209.06 |
October | 0.629366E+09 | 0.274352E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9738910.92 | 2405100.54 |
November | 0.623221E+09 | 0.274325E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945275.56 | 9097622.86 |
December | 0.607235E+09 | 0.272952E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22361.20 | 35749252.02 |
Annual Sum or Average | 0.755252E+10 | 0.321353E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264906E+09 | 0.156850E+09 |
Minimum of Months | 0.570983E+09 | 0.248550E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205829.24 |
Maximum of Months | 0.682256E+09 | 0.285500E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65895605.77 | 40620560.74 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.453388E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40594.13 | 81316551.52 |
February | 0.901968E+09 | 0.399652E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1970497.54 | 89336505.85 |
March | 0.107774E+10 | 0.451695E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19168816.80 | 57777626.90 |
April | 0.956342E+09 | 0.395443E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73740311.29 | 5214678.55 |
May | 0.103597E+10 | 0.417528E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156128E+09 | 1862292.48 |
June | 0.103308E+10 | 0.415569E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105463E+09 | 994668.17 |
July | 0.959235E+09 | 0.398560E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131146E+09 | 421804.86 |
August | 0.107774E+10 | 0.447238E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74152977.01 | 736056.93 |
September | 0.956342E+09 | 0.407662E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43923350.36 | 1463679.94 |
October | 0.994195E+09 | 0.434199E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24304996.63 | 4897520.68 |
November | 0.984487E+09 | 0.444789E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5663112.04 | 18919416.96 |
December | 0.959235E+09 | 0.445722E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 510215.82 | 74726989.12 |
Annual Sum or Average | 0.119305E+11 | 0.511144E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636211E+09 | 0.337668E+09 |
Minimum of Months | 0.901968E+09 | 0.395443E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40594.13 | 421804.86 |
Maximum of Months | 0.107774E+10 | 0.453388E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156128E+09 | 89336505.85 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.282770E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 | 57756555.31 |
February | 0.421807E+09 | 0.250771E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 653687.38 | 63886731.97 |
March | 0.502994E+09 | 0.284632E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11111803.21 | 40530895.11 |
April | 0.447140E+09 | 0.250220E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46961380.72 | 3894203.49 |
May | 0.484071E+09 | 0.265708E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102109E+09 | 1307379.25 |
June | 0.482240E+09 | 0.264415E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69356257.24 | 690576.42 |
July | 0.448971E+09 | 0.252635E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86103715.66 | 281677.25 |
August | 0.502994E+09 | 0.282691E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48369655.78 | 504458.32 |
September | 0.447140E+09 | 0.257111E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28417439.04 | 1001309.04 |
October | 0.465148E+09 | 0.272076E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14856364.30 | 3574253.88 |
November | 0.460569E+09 | 0.279455E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2879564.31 | 13817767.23 |
December | 0.448971E+09 | 0.278103E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106010.12 | 53105100.99 |
Annual Sum or Average | 0.557719E+10 | 0.322059E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410925E+09 | 0.240351E+09 |
Minimum of Months | 0.421807E+09 | 0.250220E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 | 281677.25 |
Maximum of Months | 0.502994E+09 | 0.284632E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102109E+09 | 63886731.97 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.435320E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92832237.08 |
February | 0.901968E+09 | 0.390385E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 910734.05 | 0.101927E+09 |
March | 0.107774E+10 | 0.448681E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16356192.55 | 62492941.29 |
April | 0.956342E+09 | 0.396361E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71868194.64 | 5506298.59 |
May | 0.103597E+10 | 0.421157E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155981E+09 | 1888862.49 |
June | 0.103308E+10 | 0.419085E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105584E+09 | 975161.49 |
July | 0.959235E+09 | 0.401547E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131185E+09 | 419957.49 |
August | 0.107774E+10 | 0.448479E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73822477.25 | 746595.05 |
September | 0.956342E+09 | 0.406344E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43099364.29 | 1514014.73 |
October | 0.994195E+09 | 0.427594E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21759943.69 | 5382319.55 |
November | 0.984487E+09 | 0.429522E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3940347.01 | 22354999.70 |
December | 0.959235E+09 | 0.425489E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17154.32 | 87798878.04 |
Annual Sum or Average | 0.119305E+11 | 0.504996E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624525E+09 | 0.383839E+09 |
Minimum of Months | 0.901968E+09 | 0.390385E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419957.49 |
Maximum of Months | 0.107774E+10 | 0.448681E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155981E+09 | 0.101927E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.280804E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57057771.54 |
February | 0.570983E+09 | 0.249045E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 697354.31 | 63096268.91 |
March | 0.682256E+09 | 0.286014E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11436470.57 | 41427115.98 |
April | 0.605404E+09 | 0.251122E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47637319.62 | 3860556.99 |
May | 0.655811E+09 | 0.266247E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102358E+09 | 1386985.03 |
June | 0.653980E+09 | 0.264969E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69286952.98 | 720468.91 |
July | 0.607235E+09 | 0.254408E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86343825.62 | 277596.87 |
August | 0.682256E+09 | 0.285208E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48676180.11 | 508635.92 |
September | 0.605404E+09 | 0.258826E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28542373.72 | 1019742.10 |
October | 0.629366E+09 | 0.274863E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15312738.28 | 3366556.81 |
November | 0.623221E+09 | 0.274786E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3118947.84 | 13247089.68 |
December | 0.607235E+09 | 0.273597E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75906.86 | 52152421.19 |
Annual Sum or Average | 0.755252E+10 | 0.321989E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413486E+09 | 0.238121E+09 |
Minimum of Months | 0.570983E+09 | 0.249045E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277596.87 |
Maximum of Months | 0.682256E+09 | 0.286014E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102358E+09 | 63096268.91 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121127E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911304.94 | 0.131148E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20115896.68 | 82003987.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87901029.80 | 6742883.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194039E+09 | 2162773.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131560E+09 | 1105582.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165485E+09 | 470366.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91530383.53 | 775046.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51693312.60 | 1370666.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26575380.40 | 7121839.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4651220.47 | 28668846.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83440.00 | 0.112491E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774545E+09 | 0.495188E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470366.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194039E+09 | 0.131148E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4390.60 | 0.142562E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1663062.70 | 0.160114E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26212406.76 | 0.104490E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112049E+09 | 8982821.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246455E+09 | 3113722.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168361E+09 | 1591076.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210755E+09 | 585969.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117145E+09 | 1000685.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66843327.57 | 1722681.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35085898.29 | 8820698.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6868784.81 | 34626174.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546907.08 | 0.133427E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991991E+09 | 0.601036E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4390.60 | 585969.93 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246455E+09 | 0.160114E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142263E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177042.43 | 0.160595E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17887619.62 | 95981820.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106192E+09 | 7170851.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254684E+09 | 2329601.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174154E+09 | 1412048.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213204E+09 | 459909.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117787E+09 | 1419505.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65613297.34 | 1374180.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29491048.30 | 6851545.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3337704.22 | 32176972.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128012E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982528E+09 | 0.580047E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459909.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254684E+09 | 0.160595E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3682.52 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3682.52 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3682.52 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3682.52 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3682.52 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3682.52 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3682.52 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3682.52 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3682.52 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3682.52 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3682.52 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3682.52 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3682.52 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3682.52 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3682.52 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3682.52 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3682.52 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3682.52 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3682.52 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3682.52 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3682.52 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3682.52 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3682.52 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3682.52 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3682.52 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3682.52 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3682.52 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3682.52 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3682.52 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3682.52 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3682.52 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3682.52 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3682.52 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3682.52 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3682.52 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3682.52 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3682.52 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3682.52 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 645.94 | 18-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 08-JAN-14:30 | 228.26 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 632.40 | 10-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 | 19-FEB-15:00 | 333.95 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 638.32 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 217.29 | 26-MAR-14:40 | 653.87 | 24-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 411.51 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.35 | 15-APR-17:08 | 98.29 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 436.67 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 766.75 | 28-MAY-15:00 | 76.01 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 435.91 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.60 | 03-JUN-17:10 | 60.93 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 613.57 | 26-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.15 | 02-JUL-11:44 | 47.15 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 633.74 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.46 | 06-AUG-14:14 | 58.93 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 653.94 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.84 | 24-SEP-14:54 | 24.15 | 19-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 689.88 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.15 | 15-OCT-11:52 | 95.34 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 673.23 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 12-NOV-13:52 | 155.11 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 679.50 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 | 24-DEC-13:57 | 360.70 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 411.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 24.15 | |||||
Maximum of Months | 1306.65 | 689.88 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 766.75 | 653.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 404.54 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 | 08-JAN-15:00 | 150.85 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 402.24 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.70 | 19-FEB-15:00 | 221.07 | 09-FEB-22:10 |
March | 827.22 | 01-MAR-10:09 | 362.70 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.01 | 26-MAR-15:36 | 445.62 | 24-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 234.43 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.47 | 15-APR-17:08 | 71.43 | 22-APR-18:10 |
May | 827.22 | 01-MAY-09:09 | 267.96 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.16 | 28-MAY-15:00 | 52.48 | 15-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 268.14 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.75 | 03-JUN-17:10 | 40.47 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 373.99 | 26-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.94 | 02-JUL-11:44 | 31.19 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 388.05 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.34 | 06-AUG-14:14 | 39.59 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 402.12 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.15 | 24-SEP-14:54 | 16.30 | 19-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 429.35 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.55 | 15-OCT-12:45 | 63.13 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 435.62 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 | 12-NOV-14:00 | 104.00 | 28-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 433.34 | 29-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 | 24-DEC-14:00 | 239.62 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 | 16.30 | |||||
Maximum of Months | 827.22 | 435.62 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 511.16 | 445.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 620.17 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 299.87 | 22-JAN-14:35 |
February | 1306.65 | 01-FEB-10:09 | 611.71 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 21-FEB-15:00 | 335.72 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 630.54 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.49 | 26-MAR-14:55 | 697.82 | 24-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 415.64 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.23 | 15-APR-17:08 | 104.42 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 516.03 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 766.75 | 28-MAY-15:00 | 77.48 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 521.10 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.09 | 17-JUN-20:40 | 60.58 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 622.92 | 26-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.86 | 02-JUL-11:44 | 47.05 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 637.88 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.91 | 06-AUG-14:00 | 59.34 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 652.71 | 08-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.98 | 24-SEP-15:00 | 24.91 | 19-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 686.26 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.83 | 15-OCT-12:45 | 96.13 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 612.76 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 13-NOV-14:00 | 165.20 | 29-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 646.33 | 29-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 28-DEC-14:00 | 499.35 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 415.64 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | |||||
Maximum of Months | 1306.65 | 686.26 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 766.75 | 697.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 411.85 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 152.41 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 404.86 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 19-FEB-13:53 | 221.85 | 09-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 417.50 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.80 | 26-MAR-14:55 | 465.62 | 24-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 332.64 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.86 | 15-APR-17:08 | 68.25 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 345.79 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.17 | 28-MAY-15:00 | 55.07 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 346.50 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.80 | 03-JUN-17:08 | 42.22 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 399.28 | 26-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.03 | 02-JUL-11:44 | 31.08 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 409.07 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.04 | 06-AUG-14:14 | 39.92 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 418.98 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.72 | 24-SEP-14:14 | 16.99 | 19-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 438.70 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.01 | 15-OCT-12:45 | 63.32 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 393.72 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 | 12-NOV-12:32 | 105.23 | 29-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 403.78 | 29-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 24-DEC-13:53 | 239.49 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 332.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | |||||
Maximum of Months | 827.17 | 438.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 511.17 | 465.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 640.95 | 18-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 08-JAN-15:00 | 139.52 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 626.89 | 10-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.84 | 19-FEB-15:00 | 192.33 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 632.86 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 149.75 | 26-MAR-14:50 | 363.18 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 408.41 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.26 | 15-APR-17:02 | 53.02 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 434.66 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.28 | 28-MAY-14:43 | 32.07 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 433.84 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.90 | 17-JUN-21:00 | 31.66 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 607.27 | 26-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.14 | 02-JUL-11:46 | 28.89 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 628.24 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.14 | 06-AUG-14:00 | 33.38 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 649.24 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.19 | 24-SEP-13:56 | 17.51 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 686.58 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.08 | 15-OCT-11:52 | 60.04 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 669.07 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 12-NOV-14:00 | 98.89 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 675.75 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 | 24-DEC-14:10 | 224.89 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 408.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 17.51 | |||||
Maximum of Months | 1306.65 | 686.58 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 415.28 | 363.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 401.84 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 94.42 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 399.50 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 | 19-FEB-15:10 | 130.00 | 09-FEB-22:10 |
March | 827.22 | 01-MAR-10:09 | 357.40 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.31 | 26-MAR-14:50 | 258.46 | 24-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 234.43 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.11 | 15-APR-17:02 | 41.09 | 22-APR-18:10 |
May | 827.22 | 01-MAY-09:09 | 266.35 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.48 | 28-MAY-14:43 | 25.46 | 15-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 266.53 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.72 | 17-JUN-20:55 | 22.18 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 370.32 | 26-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.99 | 02-JUL-11:44 | 19.31 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 384.64 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 | 06-AUG-14:25 | 22.83 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 399.08 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.85 | 24-SEP-13:56 | 11.74 | 08-SEP-22:10 |
October | 827.22 | 02-OCT-09:09 | 427.35 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 15-OCT-13:10 | 40.58 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 433.85 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 12-NOV-14:00 | 68.50 | 28-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 431.53 | 29-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 | 24-DEC-14:50 | 151.58 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | |||||
Maximum of Months | 827.22 | 433.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 277.48 | 258.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 613.92 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18959.81 | 05-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 605.25 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2950.40 | 22-FEB-13:00 | 15979.39 | 02-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 624.69 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12419.15 | 28-MAR-16:02 | 9007.90 | 01-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 412.76 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16944.65 | 27-APR-16:01 | 5143.59 | 10-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 505.99 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21299.52 | 03-MAY-16:01 | 136.14 | 15-MAY-05:05 |
June | 1306.65 | 01-JUN-09:09 | 511.28 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21528.42 | 07-JUN-16:01 | 98.27 | 27-JUN-11:05 |
July | 1306.65 | 03-JUL-09:09 | 617.07 | 26-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16987.31 | 07-JUL-16:01 | 29.06 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 632.59 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13899.13 | 07-AUG-16:01 | 106.13 | 16-AUG-05:03 |
September | 1306.65 | 01-SEP-09:09 | 647.96 | 08-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12361.29 | 26-SEP-16:02 | 542.77 | 27-SEP-05:03 |
October | 1306.65 | 02-OCT-09:09 | 682.78 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11661.68 | 02-OCT-16:02 | 9128.60 | 30-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 591.25 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4828.06 | 09-NOV-12:03 | 14458.59 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 641.02 | 29-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.84 | 28-DEC-14:00 | 18298.77 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 412.76 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | |||||
Maximum of Months | 1306.65 | 682.78 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21528.42 | 18959.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 409.39 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 95.14 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 402.20 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 | 19-FEB-13:43 | 130.40 | 09-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 415.24 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.39 | 26-MAR-13:22 | 269.06 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 327.28 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.53 | 15-APR-17:08 | 38.46 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 341.35 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 28-MAY-15:00 | 27.62 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 342.08 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.22 | 17-JUN-20:50 | 24.07 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 396.47 | 26-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.15 | 02-JUL-11:44 | 19.38 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 406.55 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.99 | 06-AUG-14:25 | 23.01 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 416.76 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.02 | 24-SEP-14:33 | 11.80 | 08-SEP-22:10 |
October | 827.17 | 02-OCT-09:09 | 437.08 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.88 | 15-OCT-11:52 | 40.54 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 390.35 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 | 12-NOV-12:53 | 68.69 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 400.31 | 29-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 24-DEC-13:43 | 151.82 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 327.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 | |||||
Maximum of Months | 827.17 | 437.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 272.70 | 269.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 645.93 | 18-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 08-JAN-15:00 | 209.67 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 632.38 | 10-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.99 | 19-FEB-15:00 | 299.14 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 638.30 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.78 | 26-MAR-14:50 | 593.20 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 411.51 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.97 | 15-APR-17:02 | 91.59 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 436.67 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.92 | 28-MAY-14:33 | 64.14 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 435.90 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.90 | 17-JUN-20:50 | 50.60 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 613.55 | 26-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.30 | 02-JUL-11:35 | 41.54 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 633.72 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.82 | 06-AUG-14:14 | 47.78 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 653.93 | 08-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.53 | 24-SEP-14:44 | 22.46 | 19-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 689.87 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.35 | 15-OCT-11:52 | 85.71 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 673.22 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.95 | 12-NOV-13:50 | 146.28 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 679.49 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.95 | 24-DEC-13:53 | 329.83 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 411.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 22.46 | |||||
Maximum of Months | 1306.65 | 689.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 639.92 | 593.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 404.53 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 08-JAN-15:00 | 138.67 | 15-JAN-17:00 |
February | 805.43 | 01-FEB-08:09 | 402.23 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 19-FEB-15:00 | 198.38 | 09-FEB-22:10 |
March | 805.43 | 01-MAR-08:09 | 362.69 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.44 | 26-MAR-14:50 | 402.63 | 24-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 234.43 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.43 | 15-APR-17:10 | 66.80 | 22-APR-18:00 |
May | 805.43 | 01-MAY-07:10 | 267.96 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.22 | 28-MAY-15:00 | 44.39 | 15-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 268.13 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.90 | 17-JUN-20:50 | 33.76 | 18-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 373.98 | 26-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.81 | 02-JUL-12:00 | 27.57 | 19-JUL-03:00 |
August | 805.43 | 01-AUG-07:10 | 388.04 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.72 | 06-AUG-14:14 | 32.26 | 15-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 402.12 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.06 | 24-SEP-14:44 | 15.18 | 19-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 429.35 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.01 | 15-OCT-13:10 | 56.88 | 12-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 435.62 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | 12-NOV-14:30 | 97.87 | 28-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 433.33 | 29-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 24-DEC-14:30 | 219.20 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 15.18 | |||||
Maximum of Months | 805.43 | 435.62 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 426.22 | 402.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 620.15 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 256.94 | 22-JAN-14:00 |
February | 1306.65 | 01-FEB-10:09 | 611.69 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 21-FEB-15:00 | 300.42 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 630.53 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 152.27 | 26-MAR-15:07 | 624.78 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 415.63 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.41 | 15-APR-17:10 | 96.74 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 516.01 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.92 | 28-MAY-14:33 | 65.49 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 521.07 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.00 | 17-JUN-20:50 | 50.20 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 622.91 | 26-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.10 | 02-JUL-11:33 | 41.45 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 637.87 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.30 | 06-AUG-14:14 | 48.13 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 652.70 | 08-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.53 | 24-SEP-14:44 | 23.07 | 19-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 686.25 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.31 | 15-OCT-13:00 | 86.36 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 612.75 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 12-NOV-14:46 | 152.53 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 646.32 | 29-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 28-DEC-14:00 | 418.49 | 31-DEC-14:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 415.63 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | |||||
Maximum of Months | 1306.65 | 686.25 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 641.92 | 624.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 411.85 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 139.83 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 404.85 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 | 19-FEB-13:33 | 198.60 | 09-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 417.50 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.87 | 26-MAR-13:22 | 415.49 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 332.63 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.49 | 15-APR-17:08 | 63.35 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 345.78 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.22 | 28-MAY-15:00 | 46.64 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 346.49 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.72 | 04-JUN-12:55 | 35.28 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 399.27 | 26-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.43 | 02-JUL-11:33 | 27.39 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 409.06 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.55 | 06-AUG-14:14 | 32.40 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 418.97 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.55 | 24-SEP-14:03 | 15.69 | 19-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 438.69 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.62 | 15-OCT-11:52 | 56.90 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 393.72 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | 12-NOV-13:02 | 98.46 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 403.77 | 29-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 | 24-DEC-13:43 | 218.84 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 332.63 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | |||||
Maximum of Months | 827.17 | 438.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 426.22 | 415.49 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 298.33 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.86 | 19-FEB-15:00 | 443.10 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.40 | 26-MAR-14:53 | 880.23 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.91 | 15-APR-17:02 | 119.91 | 22-APR-18:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.33 | 28-MAY-15:00 | 69.50 | 15-MAY-04:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.16 | 03-JUN-17:02 | 64.34 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.02 | 02-JUL-12:00 | 50.90 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.75 | 06-AUG-14:10 | 53.89 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.69 | 24-SEP-14:20 | 27.66 | 19-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.46 | 15-OCT-12:42 | 114.65 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.34 | 12-NOV-14:10 | 214.08 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 24-DEC-14:30 | 478.70 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.33 | 880.23 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 08-JAN-14:55 | 356.21 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.15 | 19-FEB-15:00 | 552.15 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.16 | 26-MAR-14:53 | 1117.69 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.94 | 15-APR-17:02 | 153.88 | 22-APR-18:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.89 | 28-MAY-15:00 | 103.49 | 15-MAY-04:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.67 | 03-JUN-17:02 | 88.24 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.00 | 02-JUL-12:00 | 63.85 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.22 | 06-AUG-14:00 | 68.92 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.16 | 24-SEP-13:52 | 35.74 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.41 | 15-OCT-12:02 | 141.87 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 | 12-NOV-13:52 | 259.87 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.81 | 24-DEC-14:00 | 586.43 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 35.74 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017.89 | 1117.69 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 353.46 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 | 24-FEB-16:00 | 531.35 | 09-FEB-22:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.58 | 26-MAR-14:40 | 908.98 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.19 | 15-APR-17:02 | 116.06 | 22-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.56 | 28-MAY-15:10 | 81.45 | 15-MAY-04:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.66 | 17-JUN-20:50 | 79.49 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.76 | 02-JUL-11:26 | 55.99 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.01 | 06-AUG-09:03 | 80.10 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.42 | 24-SEP-13:54 | 23.12 | 19-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.95 | 15-OCT-11:52 | 132.14 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 13-NOV-14:00 | 214.75 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 596.96 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.12 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.56 | 908.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14556.99 | 18-JAN-08:07 | 18105.02 | 11047.55 | 38274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27308.04 | 23-FEB-07:02 | 7623.17 | 7365.04 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35526.91 | 13-MAR-05:12 | 2541.06 | 1636.67 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35501.59 | 10-APR-05:12 | 2541.06 | 1636.67 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36042.75 | 15-MAY-04:02 | 0.00 | 2045.84 | 17320.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35196.07 | 20-JUN-04:03 | 0.00 | 1636.67 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31660.16 | 19-JUL-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33371.87 | 24-AUG-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35100.04 | 26-SEP-04:03 | 0.00 | 1636.67 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35674.40 | 11-OCT-04:03 | 0.00 | 1636.67 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33484.31 | 13-NOV-07:02 | 7623.17 | 7365.04 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16658.39 | 21-DEC-08:03 | 60350.08 | 36825.18 | 127582.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14556.99 | 0.00 | 846.94 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36042.75 | 60350.08 | 36825.18 | 127582.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3724.17 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 |
February | 7808.02 | 22-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
March | 12280.11 | 28-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14564.01 | 26-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.68 | 0.00 |
May | 16789.73 | 29-MAY-15:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.41 | 0.00 |
June | 16692.88 | 05-JUN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.60 | 0.00 |
July | 15089.94 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.52 | 0.00 |
August | 13672.93 | 07-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.07 | 0.00 |
September | 12240.24 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.19 | 0.00 |
October | 12469.32 | 02-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 | 0.00 |
November | 8457.74 | 09-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
December | 5085.91 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3724.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16789.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.41 | 24.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2231.16 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2467.14 | 22-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 | 0.00 |
March | 4956.82 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.40 | 0.00 |
April | 6136.44 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.98 | 0.00 |
May | 7616.12 | 30-MAY-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.69 | 0.00 |
June | 9069.36 | 12-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 0.00 |
July | 7472.00 | 05-JUL-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.85 | 0.00 |
August | 7115.72 | 14-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
September | 6609.08 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.00 |
October | 5885.46 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 | 0.00 |
November | 3424.36 | 13-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 | 0.00 |
December | 1989.58 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1989.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9069.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.98 | 23.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2619.96 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2949.65 | 22-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 | 0.00 |
March | 4889.00 | 28-MAR-17:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6520.65 | 17-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.49 | 0.00 |
May | 8238.02 | 30-MAY-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.18 | 0.00 |
June | 7954.06 | 12-JUN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 | 0.00 |
July | 7781.77 | 05-JUL-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.29 | 0.00 |
August | 6786.62 | 07-AUG-17:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 | 0.00 |
September | 6524.25 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
October | 5476.57 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 | 0.00 |
November | 3953.08 | 13-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 | 0.00 |
December | 2270.94 | 01-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2270.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8238.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 | 3.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10061.01 | 26-JAN-17:00 | 6035.01 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13079.19 | 22-FEB-17:00 | 6035.01 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31056.65 | 13-MAR-05:12 | 2541.06 | 1636.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31113.06 | 10-APR-05:12 | 2541.06 | 1636.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31103.32 | 15-MAY-04:02 | 0.00 | 2045.84 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30603.65 | 20-JUN-04:03 | 0.00 | 1636.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30742.38 | 11-JUL-04:03 | 0.00 | 1636.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31000.04 | 21-AUG-04:04 | 0.00 | 2045.84 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31443.70 | 26-SEP-04:03 | 0.00 | 1636.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32779.57 | 02-OCT-05:14 | 3176.32 | 2045.84 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28039.19 | 13-NOV-07:02 | 7623.17 | 7365.04 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11762.87 | 01-DEC-17:00 | 6035.01 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10061.01 | 0.00 | 1636.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32779.57 | 7623.17 | 7365.04 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9858.57 | 26-JAN-16:20 | 6035.01 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14122.21 | 23-FEB-15:00 | 6198.29 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27069.13 | 13-MAR-05:12 | 2541.06 | 1636.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35798.35 | 17-APR-04:02 | 0.00 | 2045.84 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36897.12 | 15-MAY-04:02 | 0.00 | 2045.84 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34614.85 | 28-JUN-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31658.05 | 19-JUL-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34664.27 | 21-AUG-04:02 | 0.00 | 2045.84 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34971.47 | 07-SEP-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35872.48 | 10-OCT-05:12 | 3176.32 | 2045.84 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15641.39 | 13-NOV-15:00 | 6198.29 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11409.57 | 01-DEC-16:20 | 6035.01 | 3682.52 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9858.57 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36897.12 | 6198.29 | 3682.52 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2239.53 | 26-JAN-15:00 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 |
February | 4094.71 | 23-FEB-14:40 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
March | 6798.21 | 12-MAR-16:02 | 334.80 | 102.85 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 74.48 | 0.00 |
April | 15157.62 | 16-APR-14:42 | 401.76 | 123.42 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 88.53 | 0.00 |
May | 15536.65 | 28-MAY-15:21 | 468.72 | 143.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 716.14 | 0.00 |
June | 15382.06 | 04-JUN-15:21 | 535.68 | 164.55 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 301.68 | 0.00 |
July | 15066.07 | 04-JUL-17:52 | 0.00 | 102.85 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 165.76 | 0.00 |
August | 13906.37 | 06-AUG-16:12 | 401.76 | 123.42 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 194.44 | 0.00 |
September | 12419.42 | 25-SEP-04:02 | 0.00 | 431.28 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.00 |
October | 11859.85 | 01-OCT-15:42 | 401.76 | 123.42 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 78.71 | 0.00 |
November | 4502.75 | 09-NOV-14:30 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 0.00 |
December | 2301.89 | 01-DEC-15:00 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2239.53 | 0.00 | 102.85 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15536.65 | 1306.65 | 431.28 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 716.14 | 15.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1925.23 | 26-JAN-14:10 | 1654.44 | 468.86 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
February | 3910.02 | 22-FEB-10:50 | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
March | 7147.32 | 26-MAR-15:32 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 110.97 | 0.00 |
April | 12079.83 | 16-APR-10:02 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 | 0.00 |
May | 12384.90 | 29-MAY-09:52 | 254.35 | 78.13 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 349.85 | 0.00 |
June | 12159.56 | 04-JUN-10:02 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 0.00 |
July | 11875.93 | 04-JUL-10:32 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 111.53 | 0.00 |
August | 11099.06 | 27-AUG-10:32 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 | 0.00 |
September | 11636.76 | 17-SEP-10:02 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 0.00 |
October | 11755.47 | 09-OCT-11:42 | 254.35 | 78.13 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 0.00 |
November | 3999.56 | 09-NOV-10:30 | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
December | 2250.37 | 01-DEC-10:50 | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1925.23 | 169.56 | 52.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12384.90 | 1654.44 | 468.86 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 349.85 | 7.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7813.99 | 12-JAN-14:10 | 2613.31 | 740.60 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 |
February | 15966.89 | 20-FEB-13:02 | 267.84 | 82.28 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 |
March | 16082.07 | 26-MAR-15:32 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 127.76 | 0.00 |
April | 16083.26 | 16-APR-14:42 | 401.76 | 123.42 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 84.28 | 0.00 |
May | 15912.33 | 28-MAY-15:21 | 468.72 | 143.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 710.81 | 0.00 |
June | 15677.88 | 04-JUN-14:41 | 468.72 | 143.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 311.70 | 0.00 |
July | 15120.86 | 04-JUL-17:12 | 0.00 | 123.42 | 2316.60 | 0.00 | 0.00 | 0.00 | 0.00 | 161.26 | 0.00 |
August | 14283.28 | 06-AUG-16:12 | 401.76 | 123.42 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 191.58 | 0.00 |
September | 15859.52 | 24-SEP-13:32 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 172.69 | 0.00 |
October | 17240.10 | 15-OCT-12:42 | 401.76 | 123.42 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 143.53 | 0.00 |
November | 16499.23 | 23-NOV-13:32 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 |
December | 10395.37 | 03-DEC-14:53 | 200.88 | 61.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7813.99 | 0.00 | 61.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17240.10 | 2613.31 | 740.60 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 710.81 | 13.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3232.96 | 31-JAN-16:10 | 805.38 | 234.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 |
February | 6943.93 | 20-FEB-17:03 | 127.16 | 39.06 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 |
March | 13344.15 | 26-MAR-15:32 | 211.94 | 65.11 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 | 0.00 |
April | 13988.53 | 30-APR-16:11 | 296.72 | 91.15 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 200.20 | 0.00 |
May | 14523.89 | 29-MAY-16:33 | 296.72 | 91.15 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 138.14 | 0.00 |
June | 14251.94 | 04-JUN-16:02 | 381.49 | 117.19 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 191.96 | 0.00 |
July | 13285.82 | 04-JUL-16:32 | 254.33 | 78.13 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 | 0.00 |
August | 12460.87 | 06-AUG-16:12 | 254.33 | 78.13 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 119.43 | 0.00 |
September | 13161.49 | 24-SEP-15:32 | 211.94 | 65.11 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 107.69 | 0.00 |
October | 13402.81 | 01-OCT-15:42 | 254.33 | 78.13 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 | 0.00 |
November | 9011.22 | 11-NOV-15:43 | 169.55 | 52.08 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 | 0.00 |
December | 3723.62 | 01-DEC-15:30 | 805.38 | 234.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3232.96 | 127.16 | 39.06 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14523.89 | 805.38 | 234.41 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 200.20 | 19.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1894.71 | 26-JAN-14:10 | 2613.31 | 740.60 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
February | 3148.17 | 24-FEB-15:00 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 0.00 |
March | 4696.20 | 13-MAR-15:20 | 1272.23 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 0.00 |
April | 7830.68 | 17-APR-04:02 | 0.00 | 431.28 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12297.88 | 29-MAY-15:01 | 669.60 | 205.69 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 213.77 | 0.00 |
June | 12401.81 | 11-JUN-16:31 | 669.60 | 205.69 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 72.24 | 0.00 |
July | 12076.86 | 04-JUL-16:32 | 401.76 | 123.42 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 86.22 | 0.00 |
August | 10730.45 | 28-AUG-04:02 | 0.00 | 431.28 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 0.00 |
September | 12192.43 | 24-SEP-15:12 | 401.76 | 123.42 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 95.87 | 0.00 |
October | 11959.72 | 01-OCT-14:01 | 468.72 | 143.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 0.00 |
November | 4162.29 | 09-NOV-14:10 | 2613.31 | 740.60 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
December | 2417.47 | 01-DEC-15:00 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1894.71 | 0.00 | 123.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12401.81 | 2613.31 | 740.60 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 213.77 | 6.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2031.86 | 26-JAN-11:00 | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 |
February | 3541.74 | 22-FEB-10:40 | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
March | 5215.80 | 28-MAR-10:30 | 805.43 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 0.00 |
April | 10158.25 | 16-APR-11:43 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 0.00 |
May | 10550.62 | 29-MAY-09:01 | 339.13 | 104.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 184.25 | 0.00 |
June | 10283.58 | 11-JUN-09:51 | 296.74 | 91.15 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 | 0.00 |
July | 10123.55 | 04-JUL-09:52 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 0.00 |
August | 10219.73 | 06-AUG-09:43 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 68.32 | 0.00 |
September | 10090.76 | 24-SEP-10:32 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 | 0.00 |
October | 10133.37 | 09-OCT-11:12 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
November | 4233.50 | 13-NOV-10:30 | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
December | 2789.37 | 01-DEC-10:30 | 827.22 | 234.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2031.86 | 169.56 | 52.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10550.62 | 827.22 | 234.43 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 184.25 | 10.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6811.29 | 30-JAN-13:07 | 3816.70 | 1110.90 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.74 |
February | 10147.07 | 20-FEB-11:53 | 200.88 | 61.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 |
March | 12668.60 | 12-MAR-16:12 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 | 0.00 |
April | 13556.52 | 28-APR-17:00 | 401.76 | 205.72 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12832.42 | 0.00 |
May | 14809.23 | 01-MAY-16:50 | 401.76 | 205.72 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 15518.68 | 0.00 |
June | 15139.89 | 12-JUN-17:00 | 401.76 | 205.72 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 15896.34 | 0.00 |
July | 13864.41 | 03-JUL-17:00 | 401.76 | 205.72 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12917.04 | 0.00 |
August | 13032.69 | 07-AUG-16:50 | 401.76 | 205.72 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 10973.54 | 0.00 |
September | 13308.84 | 24-SEP-15:12 | 401.76 | 123.42 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 84.00 | 0.00 |
October | 14111.18 | 01-OCT-14:01 | 468.72 | 143.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 0.00 |
November | 13773.42 | 05-NOV-13:32 | 401.76 | 123.42 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 0.00 |
December | 11302.84 | 03-DEC-14:33 | 200.88 | 61.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6811.29 | 200.88 | 61.71 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15139.89 | 3816.70 | 1110.90 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 15896.34 | 904.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2688.62 | 31-JAN-16:30 | 805.38 | 234.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 |
February | 5068.19 | 20-FEB-16:33 | 127.16 | 39.06 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 |
March | 10612.28 | 12-MAR-16:12 | 211.94 | 65.11 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
April | 10724.72 | 02-APR-16:01 | 339.11 | 104.17 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 96.35 | 0.00 |
May | 11312.40 | 29-MAY-16:21 | 423.88 | 130.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 75.52 | 0.00 |
June | 11327.50 | 11-JUN-16:31 | 423.88 | 130.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 45.10 | 0.00 |
July | 10776.24 | 04-JUL-16:32 | 254.33 | 78.13 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 | 0.00 |
August | 10606.24 | 06-AUG-16:22 | 211.94 | 65.11 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 66.40 | 0.00 |
September | 11296.54 | 24-SEP-15:52 | 254.33 | 78.13 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 45.91 | 0.00 |
October | 11184.75 | 01-OCT-16:42 | 254.33 | 78.13 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 0.00 |
November | 9689.91 | 12-NOV-15:12 | 211.94 | 65.11 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 0.00 |
December | 3438.96 | 01-DEC-15:40 | 805.38 | 234.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2688.62 | 127.16 | 39.06 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11327.50 | 805.38 | 234.41 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 96.35 | 6.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2225.56 | 26-JAN-14:40 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 |
February | 3797.71 | 23-FEB-14:40 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 | 0.00 |
March | 5680.80 | 13-MAR-15:20 | 1272.23 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 | 0.00 |
April | 12607.16 | 30-APR-16:01 | 669.60 | 205.69 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 287.84 | 0.00 |
May | 13086.31 | 28-MAY-16:31 | 669.60 | 205.69 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 542.47 | 0.00 |
June | 12922.21 | 11-JUN-16:41 | 468.72 | 143.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 111.00 | 0.00 |
July | 12455.81 | 04-JUL-17:12 | 0.00 | 123.42 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 135.54 | 0.00 |
August | 11399.52 | 06-AUG-16:12 | 401.76 | 123.42 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 165.46 | 0.00 |
September | 11271.54 | 24-SEP-14:41 | 468.72 | 143.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 166.22 | 0.00 |
October | 10515.10 | 01-OCT-15:31 | 535.68 | 164.55 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 0.00 |
November | 4112.29 | 09-NOV-14:10 | 2613.31 | 740.60 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 | 0.00 |
December | 2346.11 | 01-DEC-15:00 | 1306.65 | 370.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2225.56 | 0.00 | 123.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13086.31 | 2613.31 | 740.60 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 542.47 | 11.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4532.05 | 27-JAN-13:02 | 4027.14 | 1172.15 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 |
February | 5137.09 | 22-FEB-11:05 | 1610.86 | 468.86 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
March | 7934.22 | 28-MAR-12:02 | 4027.14 | 1172.15 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.31 | 0.00 |
April | 11594.42 | 30-APR-08:42 | 254.35 | 78.13 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
May | 11417.34 | 28-MAY-09:11 | 339.13 | 104.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 88.78 | 0.00 |
June | 10904.49 | 11-JUN-10:02 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 0.00 |
July | 10890.71 | 02-JUL-09:31 | 296.74 | 91.15 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 0.00 |
August | 10120.62 | 27-AUG-10:32 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 41.02 | 0.00 |
September | 10555.74 | 17-SEP-09:53 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 27.93 | 0.00 |
October | 11139.22 | 01-OCT-10:12 | 211.95 | 65.11 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 |
November | 5271.81 | 01-NOV-10:05 | 1610.86 | 468.86 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
December | 4455.28 | 15-DEC-13:02 | 4027.14 | 1172.15 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4455.28 | 169.56 | 52.09 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11594.42 | 4027.14 | 1172.15 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 23.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7655.60 | 12-JAN-14:00 | 1272.23 | 370.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
February | 14007.37 | 20-FEB-14:12 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
March | 13723.14 | 12-MAR-12:23 | 267.84 | 82.28 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 0.00 |
April | 13551.29 | 30-APR-12:02 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 190.98 | 0.00 |
May | 13423.00 | 28-MAY-15:11 | 669.60 | 205.69 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 599.79 | 0.00 |
June | 13088.86 | 11-JUN-16:41 | 468.72 | 143.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 111.79 | 0.00 |
July | 12625.65 | 04-JUL-17:12 | 0.00 | 123.42 | 2316.60 | 0.00 | 0.00 | 0.00 | 0.00 | 136.56 | 0.00 |
August | 12325.93 | 06-AUG-14:12 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 195.65 | 0.00 |
September | 13749.29 | 24-SEP-12:02 | 334.80 | 102.85 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 83.37 | 0.00 |
October | 14660.46 | 29-OCT-13:22 | 401.76 | 123.42 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 0.00 |
November | 14649.93 | 12-NOV-13:22 | 401.76 | 123.42 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
December | 10332.15 | 03-DEC-14:53 | 200.88 | 61.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7655.60 | 0.00 | 61.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14660.46 | 1272.23 | 370.30 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 599.79 | 10.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3200.85 | 31-JAN-16:10 | 805.38 | 234.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
February | 9112.36 | 20-FEB-16:12 | 169.55 | 52.08 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 |
March | 11356.06 | 26-MAR-17:03 | 0.00 | 52.08 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 52.76 | 0.00 |
April | 12191.65 | 30-APR-16:01 | 423.88 | 130.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 166.73 | 0.00 |
May | 12580.58 | 28-MAY-16:31 | 423.88 | 130.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 327.76 | 0.00 |
June | 12169.82 | 11-JUN-16:41 | 296.72 | 91.15 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 69.29 | 0.00 |
July | 12200.07 | 02-JUL-16:12 | 423.88 | 130.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 124.62 | 0.00 |
August | 10880.40 | 06-AUG-17:32 | 0.00 | 78.13 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 76.24 | 0.00 |
September | 11584.60 | 24-SEP-15:21 | 296.72 | 91.15 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 | 0.00 |
October | 11767.76 | 01-OCT-15:31 | 339.11 | 104.17 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 41.37 | 0.00 |
November | 10691.61 | 12-NOV-15:22 | 211.94 | 65.11 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 0.00 |
December | 3685.09 | 01-DEC-15:30 | 805.38 | 234.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3200.85 | 0.00 | 52.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12580.58 | 805.38 | 234.41 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 327.76 | 9.14 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.899005E+11 | 134206.57 | 02-JAN-07:10 | 0.118011E+11 | 17456.59 | 05-JAN-08:09 |
February | 0.868655E+11 | 94093.20 | 22-FEB-15:30 | 0.959427E+10 | 16810.98 | 02-FEB-07:10 |
March | 0.118836E+12 | 127499.68 | 28-MAR-15:00 | 0.102815E+11 | 9608.06 | 02-MAR-12:09 |
April | 0.141653E+12 | 149224.31 | 18-APR-15:09 | 0.924605E+10 | 9469.38 | 03-APR-11:00 |
May | 0.182322E+12 | 175378.27 | 01-MAY-15:09 | 0.925555E+10 | 9349.31 | 01-MAY-11:20 |
June | 0.189346E+12 | 180338.26 | 12-JUN-14:09 | 0.869514E+10 | 9212.82 | 02-JUN-11:20 |
July | 0.182991E+12 | 173304.84 | 10-JUL-14:09 | 0.858622E+10 | 9142.46 | 03-JUL-11:20 |
August | 0.182717E+12 | 168971.90 | 07-AUG-15:20 | 0.897193E+10 | 9201.63 | 31-AUG-11:20 |
September | 0.154579E+12 | 149177.67 | 14-SEP-15:20 | 0.877091E+10 | 9315.01 | 29-SEP-11:09 |
October | 0.131446E+12 | 141496.60 | 02-OCT-15:09 | 0.947991E+10 | 9457.34 | 31-OCT-11:20 |
November | 0.104733E+12 | 102653.81 | 06-NOV-13:00 | 0.966483E+10 | 10876.40 | 27-NOV-06:30 |
December | 0.893066E+11 | 82941.46 | 01-DEC-15:09 | 0.106280E+11 | 17412.15 | 21-DEC-08:30 |
Annual Sum or Average | 0.165470E+13 | 0.114975E+12 | ||||
Minimum of Months | 0.868655E+11 | 82941.46 | 0.858622E+10 | 9142.46 | ||
Maximum of Months | 0.189346E+12 | 180338.26 | 0.118011E+11 | 17456.59 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.960293E+10 | 18082.75 | 31-JAN-12:30 | 0.00 | 0.00 |
February | 0.106915E+11 | 20356.82 | 18-FEB-12:30 | 0.00 | 0.00 |
March | 0.150330E+11 | 22656.00 | 26-MAR-12:30 | 0.00 | 0.00 |
April | 0.178894E+11 | 25112.02 | 30-APR-11:00 | 0.00 | 0.00 |
May | 0.190552E+11 | 26193.05 | 28-MAY-12:30 | 0.00 | 0.00 |
June | 0.172887E+11 | 26709.59 | 04-JUN-12:20 | 0.00 | 0.00 |
July | 0.133641E+11 | 22303.38 | 04-JUL-12:30 | 0.00 | 0.00 |
August | 0.117815E+11 | 20722.02 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.116213E+11 | 20423.74 | 27-SEP-12:20 | 0.00 | 0.00 |
October | 0.131448E+11 | 20774.39 | 03-OCT-12:30 | 0.00 | 0.00 |
November | 0.111148E+11 | 18584.32 | 02-NOV-11:00 | 0.00 | 0.00 |
December | 0.931104E+10 | 16108.58 | 02-DEC-12:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.159898E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.931104E+10 | 16108.58 | 0.00 | 0.00 | |
Maximum of Months | 0.190552E+11 | 26709.59 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.148652E+11 | 0.347869E+10 | 0.545046E+11 | 0.977241E+09 | 0.382861E+10 | 12379742.02 | 0.386266E+10 | 0.837109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134022E+11 | 0.292329E+10 | 0.493409E+11 | 0.884392E+09 | 0.475918E+10 | 11196021.66 | 0.801782E+09 | 0.147426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157405E+11 | 0.292526E+10 | 0.567112E+11 | 0.102329E+10 | 0.903440E+10 | 12675672.10 | 0.100701E+09 | 0.332878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139990E+11 | 0.254304E+10 | 0.526212E+11 | 0.941195E+09 | 0.137984E+11 | 11960507.72 | 0.00 | 0.577380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150315E+11 | 0.237283E+10 | 0.556079E+11 | 0.100011E+10 | 0.182730E+11 | 12527707.06 | 0.00 | 0.900241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149583E+11 | 0.217053E+10 | 0.546110E+11 | 0.984469E+09 | 0.183855E+11 | 12231776.97 | 0.00 | 0.982243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140928E+11 | 0.233304E+10 | 0.536070E+11 | 0.956761E+09 | 0.164607E+11 | 12256437.81 | 0.00 | 0.955287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157178E+11 | 0.252635E+10 | 0.567112E+11 | 0.102330E+10 | 0.163008E+11 | 12675672.10 | 0.00 | 0.904247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141085E+11 | 0.268816E+10 | 0.525990E+11 | 0.941047E+09 | 0.133875E+11 | 11960507.72 | 0.00 | 0.708429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147357E+11 | 0.308857E+10 | 0.545158E+11 | 0.977285E+09 | 0.108142E+11 | 12379742.02 | 0.00 | 0.473018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146710E+11 | 0.328897E+10 | 0.533244E+11 | 0.959047E+09 | 0.697312E+10 | 12059151.09 | 0.146272E+09 | 0.253586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144391E+11 | 0.358655E+10 | 0.535958E+11 | 0.956841E+09 | 0.434691E+10 | 12256437.81 | 0.132236E+10 | 0.110468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175762E+12 | 0.339253E+11 | 0.647750E+12 | 0.116250E+11 | 0.136363E+12 | 0.146559E+09 | 0.623377E+10 | 0.642892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134022E+11 | 0.217053E+10 | 0.493409E+11 | 0.884392E+09 | 0.382861E+10 | 11196021.66 | 0.00 | 0.837109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157405E+11 | 0.358655E+10 | 0.567112E+11 | 0.102330E+10 | 0.183855E+11 | 12675672.10 | 0.386266E+10 | 0.982243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.143042E+10 | 0.00 | 0.103707E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.294286E+09 | 0.00 | 0.929998E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.102815E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.924605E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.925555E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.869514E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.858622E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.897193E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.877091E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.947991E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 16087646.31 | 0.00 | 0.964874E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.508224E+09 | 0.00 | 0.101198E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.224902E+10 | 0.00 | 0.112726E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.858622E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.143042E+10 | 0.00 | 0.103707E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17217.84 | 18-JAN-08:09 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 829.19 | 18-JAN-08:20 | 5345.04 | 12-JAN-15:30 | 6.85 | 02-JAN-07:10 | 101690.96 | 02-JAN-07:10 |
February | 17097.47 | 10-FEB-08:09 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 829.03 | 10-FEB-08:20 | 10810.83 | 22-FEB-15:50 | 6.85 | 01-FEB-08:09 | 28638.24 | 02-FEB-07:10 |
March | 17175.82 | 14-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 829.13 | 14-MAR-07:19 | 17050.26 | 13-MAR-15:00 | 6.85 | 01-MAR-06:10 | 6482.69 | 01-MAR-07:19 |
April | 15218.86 | 03-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 826.55 | 03-APR-07:19 | 21482.92 | 17-APR-15:09 | 6.85 | 01-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 15728.78 | 24-MAY-07:10 | 3824.74 | 01-MAY-05:10 | 40437.79 | 01-MAY-07:10 | 827.22 | 24-MAY-07:19 | 25445.14 | 30-MAY-14:20 | 6.85 | 07-MAY-09:50 | 0.00 | 01-MAY-00:10 |
June | 15744.52 | 23-JUN-07:10 | 3824.74 | 01-JUN-05:10 | 40437.79 | 01-JUN-07:10 | 827.24 | 23-JUN-07:19 | 25716.37 | 12-JUN-14:09 | 6.85 | 02-JUN-12:09 | 0.00 | 01-JUN-00:10 |
July | 17058.15 | 26-JUL-07:10 | 3824.74 | 01-JUL-05:10 | 40437.79 | 03-JUL-07:10 | 828.98 | 26-JUL-07:19 | 25277.28 | 05-JUL-15:20 | 6.85 | 02-JUL-14:00 | 0.00 | 01-JUL-00:10 |
August | 17237.00 | 16-AUG-07:10 | 3824.74 | 01-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 829.21 | 16-AUG-07:19 | 23871.38 | 07-AUG-15:30 | 6.85 | 06-AUG-15:30 | 0.00 | 01-AUG-00:10 |
September | 17416.07 | 08-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 829.45 | 08-SEP-07:19 | 20507.18 | 25-SEP-15:00 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 17769.69 | 11-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 829.91 | 11-OCT-07:19 | 17324.78 | 10-OCT-15:20 | 6.85 | 01-OCT-12:00 | 0.00 | 01-OCT-00:10 |
November | 17278.18 | 27-NOV-16:00 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 827.49 | 03-NOV-07:19 | 11523.19 | 13-NOV-15:00 | 6.85 | 01-NOV-05:10 | 12197.67 | 27-NOV-07:10 |
December | 17522.03 | 29-DEC-16:00 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.06 | 29-DEC-16:00 | 7992.85 | 01-DEC-15:20 | 6.85 | 21-DEC-17:10 | 38885.46 | 23-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15218.86 | 3824.74 | 40437.79 | 826.55 | 5345.04 | 6.85 | 0.00 | |||||||
Maximum of Months | 17769.69 | 3824.74 | 40437.79 | 829.91 | 25716.37 | 6.85 | 101690.96 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 18000.83 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30440.34 | 22-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 58053.19 | 28-MAR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 78582.66 | 26-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 101679.66 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 104855.53 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 96933.04 | 03-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 91169.73 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 77922.97 | 14-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 72464.96 | 02-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 39765.27 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 21872.34 | 01-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 18000.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 104855.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 134206.57 | 02-JAN-07:10 | 6218.03 | 18346.02 | 3824.74 | 243.28 | 3789.96 | 6.85 | 101690.96 | 86.73 | 0.00 |
February | 94093.20 | 22-FEB-15:30 | 14675.88 | 37678.39 | 0.00 | 824.26 | 10718.42 | 6.85 | 0.00 | 30189.41 | 0.00 |
March | 127499.68 | 28-MAR-15:00 | 14675.88 | 38454.47 | 0.00 | 824.70 | 15484.70 | 6.85 | 0.00 | 58053.08 | 0.00 |
April | 149224.31 | 18-APR-15:09 | 14675.88 | 38454.47 | 0.00 | 824.70 | 19645.88 | 6.85 | 0.00 | 75616.53 | 0.00 |
May | 175378.27 | 01-MAY-15:09 | 14675.88 | 38454.47 | 0.00 | 824.70 | 19736.71 | 6.85 | 0.00 | 101679.66 | 0.00 |
June | 180338.26 | 12-JUN-14:09 | 14675.88 | 37678.39 | 0.00 | 824.26 | 25716.37 | 6.85 | 0.00 | 101436.51 | 0.00 |
July | 173304.84 | 10-JUL-14:09 | 14675.88 | 37678.39 | 0.00 | 824.26 | 23944.98 | 6.85 | 0.00 | 96174.48 | 0.00 |
August | 168971.90 | 07-AUG-15:20 | 14675.88 | 38454.47 | 0.00 | 824.70 | 23840.26 | 6.85 | 0.00 | 91169.73 | 0.00 |
September | 149177.67 | 14-SEP-15:20 | 14675.88 | 38454.47 | 0.00 | 824.70 | 17292.80 | 6.85 | 0.00 | 77922.97 | 0.00 |
October | 141496.60 | 02-OCT-15:09 | 14675.88 | 38454.47 | 0.00 | 824.70 | 15470.11 | 6.85 | 0.00 | 72064.60 | 0.00 |
November | 102653.81 | 06-NOV-13:00 | 14675.88 | 38626.93 | 0.00 | 824.80 | 8754.08 | 6.85 | 0.00 | 39765.27 | 0.00 |
December | 82941.46 | 01-DEC-15:09 | 14675.88 | 37678.39 | 0.00 | 824.26 | 7883.75 | 6.85 | 0.00 | 21872.34 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 82941.46 | 6218.03 | 18346.02 | 0.00 | 243.28 | 3789.96 | 6.85 | 0.00 | 86.73 | 0.00 | |
Maximum of Months | 180338.26 | 14675.88 | 38626.93 | 3824.74 | 824.80 | 25716.37 | 6.85 | 101690.96 | 101679.66 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 8313.27 | 02-JAN-06:10 | 0.00 | 9696.57 | 19-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 8258.34 | 02-FEB-06:00 | 0.00 | 9676.72 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 9608.06 | 02-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9469.38 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9349.31 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9212.82 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9142.46 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9201.63 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9315.01 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9457.34 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 2667.22 | 27-NOV-06:10 | 0.00 | 9592.60 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 8313.27 | 20-DEC-06:10 | 0.00 | 9676.53 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9142.46 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 8313.27 | 0.00 | 9696.57 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.29 | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.29 | 0.17 | 19.29 | 0.50 | 23.42 | 0.00 | 23.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.29 | 0.17 | 19.29 | 0.33 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.03 | 0.33 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.64 | 5.00 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.72 | 9.83 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.63 | 6.83 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.63 | 11.67 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.55 | 6.83 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.50 | 4.50 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.43 | 3.00 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.03 | 0.33 | 19.03 | 80.33 | 27.55 | 48.17 | 27.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.03 | 0.33 | 19.03 | 21.33 | 27.72 | 11.67 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.00 | 0.33 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.50 | 3.83 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.88 | 11.67 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.98 | 12.83 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.76 | 9.00 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.80 | 13.33 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.71 | 8.33 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.69 | 6.33 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.65 | 9.33 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.00 | 0.33 | 19.00 | 110.83 | 27.74 | 74.67 | 27.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.00 | 0.33 | 19.00 | 23.50 | 27.98 | 13.33 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.89 | 0.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.68 | 3.67 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.81 | 5.50 | 27.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.86 | 8.50 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.79 | 9.83 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.62 | 7.00 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.66 | 11.17 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.67 | 6.83 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.80 | 5.67 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.22 | 10.67 | 28.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.91 | 8.50 | 27.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.48 | 1.50 | 27.48 |
Annual Sum or Average | 0.17 | 18.89 | 0.17 | 18.89 | 113.50 | 27.77 | 78.83 | 27.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 | 18.89 |
Maximum of Months | 0.17 | 18.89 | 0.17 | 18.89 | 20.67 | 28.22 | 11.17 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.99 | 0.33 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.84 | 3.67 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.11 | 7.00 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 28.04 | 10.67 | 28.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.86 | 8.17 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.87 | 11.83 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.78 | 7.33 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.81 | 5.67 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.03 | 6.67 | 28.07 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.54 | 2.17 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.99 | 0.33 | 18.99 | 116.33 | 27.86 | 64.33 | 27.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.99 | 0.33 | 18.99 | 24.33 | 28.11 | 11.83 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.42 | 5.50 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.36 | 3.17 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.37 | 8.17 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.30 | 4.00 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.22 | 2.17 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.67 | 27.36 | 23.50 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.42 | 8.17 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.39 | 0.50 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.67 | 6.50 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.72 | 12.00 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.54 | 6.83 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.53 | 12.33 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.49 | 7.83 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.42 | 4.83 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.53 | 7.83 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 79.67 | 27.57 | 58.67 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.72 | 12.33 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 18.60 | 19.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
February | 9.83 | 19.46 | 9.83 | 19.46 | 3.00 | 20.53 | 3.00 | 21.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 25.71 | 15.67 | 25.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 26.13 | 45.17 | 26.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 | 26.48 | 70.33 | 26.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 74.00 | 26.29 | 71.50 | 26.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 | 26.24 | 48.17 | 26.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 25.88 | 46.33 | 25.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 25.64 | 53.83 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 86.00 | 25.62 | 83.50 | 25.59 |
November | 0.67 | 20.40 | 0.67 | 20.40 | 21.33 | 25.80 | 21.33 | 25.96 |
December | 13.33 | 19.70 | 13.33 | 19.70 | 2.50 | 20.37 | 2.50 | 20.93 |
Annual Sum or Average | 43.50 | 19.16 | 43.50 | 19.16 | 478.83 | 24.99 | 461.33 | 25.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 0.00 | 18.60 |
Maximum of Months | 19.67 | 20.40 | 19.67 | 20.40 | 86.00 | 26.48 | 83.50 | 26.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.52 | 1.50 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.82 | 4.83 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.81 | 8.33 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.64 | 5.67 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.59 | 10.17 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.54 | 6.17 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.55 | 3.83 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.77 | 5.83 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.50 | 27.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 87.33 | 27.65 | 48.00 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.82 | 10.17 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.48 | 2.83 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.54 | 8.33 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.49 | 5.17 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.47 | 9.00 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.39 | 4.67 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.32 | 2.33 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 49.67 | 27.47 | 32.83 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.54 | 9.00 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.45 | 3.17 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.76 | 10.17 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.87 | 12.67 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.65 | 9.17 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.66 | 12.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.56 | 7.67 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.59 | 4.33 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.56 | 7.83 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 87.17 | 27.68 | 67.33 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.87 | 12.67 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.65 | 3.50 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.67 | 5.17 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.71 | 7.00 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.62 | 8.67 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.49 | 5.33 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.48 | 9.33 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.49 | 5.67 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.72 | 3.50 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.53 | 12.83 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.86 | 8.67 | 27.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.50 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 90.83 | 27.60 | 71.67 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.86 | 12.83 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.48 | 0.67 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.73 | 2.67 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.96 | 6.17 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.95 | 9.17 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.83 | 6.17 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.73 | 10.17 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.67 | 5.67 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.74 | 3.67 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.89 | 5.67 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.51 | 1.50 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 88.67 | 27.82 | 51.50 | 27.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.96 | 10.17 | 28.04 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 222.17 | 23.60 | 54.33 | 23.78 | 12.67 | 23.73 |
February | 48.00 | 23.80 | 128.33 | 24.43 | 0.00 | 24.43 |
March | 0.00 | 0.00 | 340.17 | 24.41 | 0.00 | 24.41 |
April | 0.00 | 0.00 | 417.83 | 24.43 | 0.00 | 24.43 |
May | 0.00 | 0.00 | 498.00 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 497.00 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 514.00 | 24.35 | 0.00 | 24.35 |
September | 0.00 | 0.00 | 485.00 | 24.42 | 0.00 | 24.42 |
October | 0.00 | 0.00 | 496.17 | 24.42 | 0.00 | 24.42 |
November | 0.00 | 0.00 | 328.17 | 24.49 | 0.00 | 24.49 |
December | 71.50 | 23.87 | 66.83 | 24.41 | 0.00 | 24.41 |
Annual Sum or Average | 341.67 | 23.68 | 4321.83 | 24.36 | 12.67 | 24.36 |
Minimum of Months | 0.00 | 0.00 | 54.33 | 23.78 | 0.00 | 23.73 |
Maximum of Months | 222.17 | 23.87 | 514.00 | 24.49 | 12.67 | 24.49 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.83 | 23.10 | 12.17 | 23.03 | 12.17 | 22.98 |
February | 184.33 | 23.42 | 58.67 | 23.69 | 0.00 | 23.69 |
March | 27.00 | 23.76 | 284.83 | 24.27 | 0.00 | 24.27 |
April | 0.00 | 0.00 | 405.50 | 24.39 | 0.00 | 24.39 |
May | 0.00 | 0.00 | 495.83 | 24.36 | 0.00 | 24.36 |
June | 0.00 | 0.00 | 496.00 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 497.00 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 514.00 | 24.33 | 0.00 | 24.33 |
September | 3.00 | 27.14 | 485.00 | 24.40 | 3.00 | 24.42 |
October | 0.00 | 0.00 | 461.33 | 24.37 | 0.00 | 24.37 |
November | 50.00 | 23.68 | 204.83 | 24.26 | 0.00 | 24.26 |
December | 338.17 | 23.42 | 2.50 | 23.43 | 0.00 | 23.43 |
Annual Sum or Average | 1047.33 | 23.31 | 3917.67 | 24.13 | 15.17 | 24.13 |
Minimum of Months | 0.00 | 0.00 | 2.50 | 23.03 | 0.00 | 22.98 |
Maximum of Months | 444.83 | 27.14 | 514.00 | 24.40 | 12.17 | 24.42 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 478.33 | 22.34 | 21.17 | 22.23 | 21.17 | 22.12 |
February | 287.50 | 23.01 | 37.17 | 23.15 | 0.00 | 23.15 |
March | 96.33 | 23.56 | 243.17 | 24.06 | 0.00 | 24.06 |
April | 4.33 | 24.88 | 394.00 | 24.44 | 1.67 | 24.45 |
May | 4.50 | 26.69 | 504.33 | 24.45 | 4.50 | 24.47 |
June | 3.50 | 26.64 | 496.00 | 24.39 | 3.50 | 24.40 |
July | 5.33 | 26.56 | 497.00 | 24.48 | 5.33 | 24.51 |
August | 3.17 | 26.55 | 514.00 | 24.40 | 3.17 | 24.41 |
September | 2.67 | 27.16 | 485.00 | 24.42 | 2.67 | 24.44 |
October | 16.50 | 23.46 | 411.00 | 24.32 | 0.00 | 24.32 |
November | 179.67 | 23.33 | 122.00 | 23.66 | 0.00 | 23.66 |
December | 434.83 | 22.71 | 5.83 | 22.69 | 5.83 | 22.66 |
Annual Sum or Average | 1516.67 | 22.84 | 3730.67 | 23.92 | 47.83 | 23.91 |
Minimum of Months | 2.67 | 22.34 | 5.83 | 22.23 | 0.00 | 22.12 |
Maximum of Months | 478.33 | 27.16 | 514.00 | 24.48 | 21.17 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.33 | 21.61 | 84.33 | 21.34 | 84.33 | 21.15 |
February | 330.33 | 22.39 | 60.50 | 22.48 | 18.17 | 22.37 |
March | 142.67 | 23.13 | 240.17 | 23.85 | 1.50 | 23.86 |
April | 33.33 | 25.37 | 415.00 | 24.61 | 17.33 | 24.70 |
May | 48.83 | 26.85 | 508.00 | 24.80 | 48.83 | 24.97 |
June | 53.67 | 26.59 | 496.00 | 24.75 | 53.67 | 24.91 |
July | 111.17 | 26.44 | 497.00 | 25.00 | 111.17 | 25.22 |
August | 80.33 | 26.25 | 514.00 | 24.75 | 80.33 | 24.93 |
September | 66.17 | 26.18 | 485.00 | 24.72 | 66.17 | 24.88 |
October | 64.17 | 23.81 | 378.83 | 24.31 | 11.50 | 24.37 |
November | 261.50 | 22.80 | 120.17 | 23.20 | 2.67 | 23.18 |
December | 459.83 | 21.94 | 55.00 | 21.73 | 55.00 | 21.57 |
Annual Sum or Average | 2141.33 | 22.98 | 3854.00 | 23.85 | 550.67 | 23.91 |
Minimum of Months | 33.33 | 21.61 | 55.00 | 21.34 | 1.50 | 21.15 |
Maximum of Months | 489.33 | 26.85 | 514.00 | 25.00 | 111.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.50 | 22.06 | 53.67 | 21.82 | 53.67 | 21.62 |
February | 240.17 | 22.57 | 111.00 | 22.99 | 11.83 | 22.89 |
March | 97.00 | 23.46 | 323.67 | 24.17 | 9.33 | 24.23 |
April | 51.00 | 26.38 | 441.67 | 24.80 | 41.17 | 24.97 |
May | 61.33 | 26.99 | 508.00 | 24.90 | 61.33 | 25.10 |
June | 57.50 | 26.73 | 496.00 | 24.79 | 57.50 | 24.97 |
July | 115.33 | 26.52 | 497.00 | 25.04 | 115.33 | 25.27 |
August | 84.00 | 26.33 | 514.00 | 24.79 | 84.00 | 24.98 |
September | 74.17 | 26.27 | 485.00 | 24.78 | 74.17 | 24.96 |
October | 71.67 | 24.98 | 415.83 | 24.58 | 35.33 | 24.74 |
November | 176.83 | 22.87 | 209.50 | 23.68 | 1.50 | 23.66 |
December | 390.00 | 22.29 | 34.67 | 22.10 | 34.67 | 21.94 |
Annual Sum or Average | 1881.50 | 23.48 | 4090.00 | 24.14 | 579.83 | 24.25 |
Minimum of Months | 51.00 | 22.06 | 34.67 | 21.82 | 1.50 | 21.62 |
Maximum of Months | 462.50 | 26.99 | 514.00 | 25.04 | 115.33 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 319.33 | 21.85 | 126.50 | 22.10 | 49.00 | 21.88 |
February | 215.67 | 22.61 | 175.17 | 23.37 | 17.50 | 23.36 |
March | 119.00 | 23.72 | 315.00 | 24.21 | 19.33 | 24.33 |
April | 44.17 | 25.95 | 423.67 | 24.72 | 29.67 | 24.86 |
May | 48.00 | 26.89 | 507.33 | 24.80 | 48.00 | 24.97 |
June | 52.67 | 26.58 | 496.00 | 24.74 | 52.67 | 24.90 |
July | 109.67 | 26.44 | 497.00 | 24.99 | 109.67 | 25.21 |
August | 81.00 | 26.29 | 514.00 | 24.76 | 81.00 | 24.95 |
September | 71.67 | 26.31 | 485.00 | 24.78 | 71.67 | 24.96 |
October | 81.17 | 25.26 | 419.83 | 24.68 | 42.67 | 24.86 |
November | 168.00 | 23.50 | 258.50 | 24.16 | 26.50 | 24.33 |
December | 268.33 | 22.15 | 162.00 | 22.80 | 29.00 | 22.63 |
Annual Sum or Average | 1578.67 | 23.67 | 4380.00 | 24.26 | 576.67 | 24.38 |
Minimum of Months | 44.17 | 21.85 | 126.50 | 22.10 | 17.50 | 21.88 |
Maximum of Months | 319.33 | 26.89 | 514.00 | 24.99 | 109.67 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.67 | 21.66 | 85.83 | 21.45 | 74.33 | 21.24 |
February | 277.00 | 22.36 | 115.00 | 22.79 | 17.00 | 22.70 |
March | 128.83 | 23.41 | 287.00 | 24.06 | 12.17 | 24.15 |
April | 45.17 | 26.09 | 430.00 | 24.75 | 32.17 | 24.89 |
May | 61.67 | 26.99 | 508.00 | 24.90 | 61.67 | 25.10 |
June | 65.83 | 26.75 | 496.00 | 24.84 | 65.83 | 25.04 |
July | 116.33 | 26.50 | 497.00 | 25.04 | 116.33 | 25.27 |
August | 86.67 | 26.34 | 514.00 | 24.80 | 86.67 | 24.99 |
September | 75.17 | 26.28 | 485.00 | 24.79 | 75.17 | 24.97 |
October | 76.00 | 24.58 | 395.67 | 24.50 | 27.83 | 24.63 |
November | 223.50 | 22.88 | 178.17 | 23.54 | 7.33 | 23.58 |
December | 390.17 | 21.99 | 81.50 | 21.93 | 49.67 | 21.75 |
Annual Sum or Average | 1967.00 | 23.30 | 4073.17 | 24.04 | 626.17 | 24.14 |
Minimum of Months | 45.17 | 21.66 | 81.50 | 21.45 | 7.33 | 21.24 |
Maximum of Months | 420.67 | 26.99 | 514.00 | 25.04 | 116.33 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.00 | 22.28 | 17.67 | 22.21 | 17.67 | 22.15 |
February | 348.33 | 22.86 | 24.50 | 22.95 | 0.00 | 22.95 |
March | 153.83 | 23.36 | 199.67 | 23.81 | 0.00 | 23.81 |
April | 15.83 | 24.12 | 389.00 | 24.43 | 2.00 | 24.45 |
May | 25.00 | 26.71 | 508.00 | 24.64 | 25.00 | 24.74 |
June | 39.00 | 26.42 | 496.00 | 24.66 | 39.00 | 24.78 |
July | 83.17 | 26.48 | 497.00 | 24.92 | 83.17 | 25.11 |
August | 54.50 | 26.45 | 514.00 | 24.71 | 54.50 | 24.86 |
September | 51.17 | 26.46 | 485.00 | 24.74 | 51.17 | 24.89 |
October | 2.33 | 25.11 | 466.67 | 24.42 | 1.00 | 24.43 |
November | 137.33 | 23.45 | 183.00 | 23.87 | 0.00 | 23.87 |
December | 422.83 | 22.84 | 0.00 | 22.84 | 0.00 | 22.84 |
Annual Sum or Average | 1822.33 | 23.30 | 3780.50 | 24.09 | 273.50 | 24.18 |
Minimum of Months | 2.33 | 22.28 | 0.00 | 22.21 | 0.00 | 22.15 |
Maximum of Months | 489.00 | 26.71 | 514.00 | 24.92 | 83.17 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.67 | 22.81 | 15.00 | 22.75 | 15.00 | 22.69 |
February | 205.50 | 23.05 | 106.83 | 23.50 | 0.00 | 23.50 |
March | 76.33 | 23.48 | 316.83 | 24.18 | 0.83 | 24.19 |
April | 20.67 | 26.78 | 438.33 | 24.67 | 18.83 | 24.77 |
May | 52.67 | 26.91 | 508.00 | 24.83 | 52.67 | 25.01 |
June | 49.50 | 26.68 | 496.00 | 24.75 | 49.50 | 24.91 |
July | 94.17 | 26.63 | 497.00 | 25.00 | 94.17 | 25.23 |
August | 62.50 | 26.63 | 514.00 | 24.78 | 62.50 | 24.96 |
September | 60.50 | 26.60 | 485.00 | 24.82 | 60.50 | 25.00 |
October | 28.33 | 26.91 | 488.17 | 24.69 | 28.33 | 24.80 |
November | 57.17 | 23.50 | 309.67 | 24.28 | 0.00 | 24.28 |
December | 287.33 | 23.11 | 14.50 | 23.19 | 0.00 | 23.19 |
Annual Sum or Average | 1419.33 | 23.98 | 4189.33 | 24.40 | 382.33 | 24.53 |
Minimum of Months | 20.67 | 22.81 | 14.50 | 22.75 | 0.00 | 22.69 |
Maximum of Months | 424.67 | 26.91 | 514.00 | 25.00 | 94.17 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 324.33 | 22.29 | 91.33 | 22.53 | 28.17 | 22.38 |
February | 174.50 | 22.47 | 176.83 | 23.50 | 4.83 | 23.48 |
March | 90.17 | 23.07 | 313.17 | 24.16 | 6.50 | 24.20 |
April | 35.00 | 25.51 | 427.00 | 24.80 | 25.33 | 24.89 |
May | 106.17 | 25.89 | 508.00 | 25.06 | 106.17 | 25.18 |
June | 168.00 | 25.37 | 496.00 | 24.98 | 168.00 | 25.06 |
July | 268.33 | 25.11 | 497.00 | 24.93 | 268.33 | 24.98 |
August | 280.17 | 24.83 | 514.00 | 24.73 | 280.17 | 24.76 |
September | 214.17 | 25.02 | 485.00 | 24.85 | 214.17 | 24.89 |
October | 92.67 | 25.70 | 487.83 | 24.98 | 87.00 | 25.10 |
November | 76.17 | 24.06 | 373.83 | 24.56 | 27.50 | 24.71 |
December | 219.67 | 22.70 | 167.33 | 23.57 | 3.00 | 23.55 |
Annual Sum or Average | 2049.33 | 24.10 | 4537.33 | 24.53 | 1219.17 | 24.63 |
Minimum of Months | 35.00 | 22.29 | 91.33 | 22.53 | 3.00 | 22.38 |
Maximum of Months | 324.33 | 25.89 | 514.00 | 25.06 | 280.17 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 409.00 | 22.53 | 24.33 | 22.51 | 14.50 | 22.46 |
February | 251.17 | 22.96 | 92.67 | 23.36 | 0.00 | 23.36 |
March | 93.17 | 23.52 | 285.83 | 24.12 | 2.83 | 24.15 |
April | 18.67 | 26.86 | 436.00 | 24.65 | 17.67 | 24.74 |
May | 47.33 | 26.91 | 508.00 | 24.81 | 47.33 | 24.98 |
June | 60.50 | 26.74 | 496.00 | 24.81 | 60.50 | 25.00 |
July | 98.00 | 26.62 | 497.00 | 25.01 | 98.00 | 25.24 |
August | 64.67 | 26.62 | 514.00 | 24.79 | 64.67 | 24.97 |
September | 62.50 | 26.61 | 485.00 | 24.84 | 62.50 | 25.03 |
October | 22.17 | 27.00 | 484.33 | 24.65 | 22.17 | 24.75 |
November | 72.00 | 23.58 | 275.33 | 24.23 | 1.50 | 24.24 |
December | 323.83 | 23.03 | 54.00 | 23.21 | 0.00 | 23.21 |
Annual Sum or Average | 1523.00 | 23.84 | 4152.50 | 24.35 | 391.67 | 24.49 |
Minimum of Months | 18.67 | 22.53 | 24.33 | 22.51 | 0.00 | 22.46 |
Maximum of Months | 409.00 | 27.00 | 514.00 | 25.01 | 98.00 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.67 | 22.10 | 29.67 | 21.98 | 29.67 | 21.87 |
February | 301.00 | 22.81 | 46.17 | 23.00 | 0.00 | 23.00 |
March | 103.67 | 23.42 | 265.50 | 24.01 | 0.00 | 24.01 |
April | 10.33 | 26.40 | 423.50 | 24.58 | 8.50 | 24.63 |
May | 41.67 | 26.77 | 508.00 | 24.75 | 41.67 | 24.89 |
June | 51.33 | 26.46 | 496.00 | 24.72 | 51.33 | 24.86 |
July | 106.17 | 26.36 | 497.00 | 24.96 | 106.17 | 25.17 |
August | 74.33 | 26.21 | 514.00 | 24.72 | 74.33 | 24.88 |
September | 64.17 | 26.20 | 485.00 | 24.72 | 64.17 | 24.87 |
October | 24.67 | 23.90 | 431.50 | 24.36 | 3.50 | 24.38 |
November | 193.83 | 23.21 | 137.17 | 23.60 | 0.00 | 23.60 |
December | 438.50 | 22.51 | 7.33 | 22.48 | 7.33 | 22.44 |
Annual Sum or Average | 1891.33 | 23.30 | 3840.83 | 24.07 | 386.67 | 24.18 |
Minimum of Months | 10.33 | 22.10 | 7.33 | 21.98 | 0.00 | 21.87 |
Maximum of Months | 481.67 | 26.77 | 514.00 | 24.96 | 106.17 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 377.50 | 22.40 | 18.67 | 22.29 | 18.50 | 22.18 |
February | 189.50 | 22.90 | 93.50 | 23.42 | 0.00 | 23.42 |
March | 65.00 | 23.74 | 273.33 | 24.34 | 6.33 | 24.39 |
April | 35.67 | 26.91 | 372.50 | 24.93 | 34.67 | 25.09 |
May | 57.67 | 26.94 | 430.00 | 25.01 | 57.67 | 25.21 |
June | 56.83 | 26.63 | 418.00 | 24.90 | 56.83 | 25.09 |
July | 111.33 | 26.47 | 422.00 | 25.15 | 111.33 | 25.38 |
August | 77.67 | 26.32 | 433.00 | 24.88 | 77.67 | 25.07 |
September | 72.67 | 26.32 | 410.00 | 24.91 | 72.67 | 25.09 |
October | 43.67 | 25.73 | 379.83 | 24.74 | 29.17 | 24.87 |
November | 118.50 | 23.22 | 185.50 | 24.02 | 0.00 | 24.02 |
December | 308.00 | 22.68 | 8.67 | 22.69 | 3.83 | 22.66 |
Annual Sum or Average | 1514.00 | 23.87 | 3445.00 | 24.40 | 468.67 | 24.56 |
Minimum of Months | 35.67 | 22.40 | 8.67 | 22.29 | 0.00 | 22.18 |
Maximum of Months | 377.50 | 26.94 | 433.00 | 25.15 | 111.33 | 25.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 292.50 | 22.40 | 106.83 | 22.86 | 9.17 | 22.79 |
February | 172.83 | 23.01 | 181.33 | 23.81 | 5.67 | 23.86 |
March | 78.50 | 24.05 | 343.33 | 24.33 | 14.67 | 24.42 |
April | 25.67 | 26.80 | 435.83 | 24.71 | 24.00 | 24.82 |
May | 43.17 | 26.81 | 508.00 | 24.76 | 43.17 | 24.91 |
June | 49.83 | 26.45 | 496.00 | 24.71 | 49.83 | 24.85 |
July | 104.33 | 26.36 | 497.00 | 24.95 | 104.33 | 25.16 |
August | 74.33 | 26.26 | 514.00 | 24.73 | 74.33 | 24.90 |
September | 68.00 | 26.32 | 485.00 | 24.77 | 68.00 | 24.94 |
October | 55.00 | 26.28 | 459.17 | 24.76 | 43.50 | 24.94 |
November | 118.67 | 24.17 | 299.17 | 24.47 | 27.83 | 24.63 |
December | 231.67 | 22.75 | 158.50 | 23.53 | 1.67 | 23.54 |
Annual Sum or Average | 1314.50 | 24.08 | 4484.17 | 24.45 | 466.17 | 24.59 |
Minimum of Months | 25.67 | 22.40 | 106.83 | 22.86 | 1.67 | 22.79 |
Maximum of Months | 292.50 | 26.81 | 514.00 | 24.95 | 104.33 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 404.00 | 22.17 | 39.50 | 22.12 | 24.17 | 22.01 |
February | 241.67 | 22.80 | 105.83 | 23.30 | 0.50 | 23.31 |
March | 87.33 | 23.71 | 314.83 | 24.21 | 8.17 | 24.27 |
April | 27.00 | 26.89 | 443.67 | 24.73 | 25.67 | 24.85 |
May | 55.00 | 26.93 | 508.00 | 24.85 | 55.00 | 25.04 |
June | 65.83 | 26.66 | 496.00 | 24.82 | 65.83 | 25.01 |
July | 114.50 | 26.45 | 497.00 | 25.01 | 114.50 | 25.24 |
August | 81.83 | 26.31 | 514.00 | 24.77 | 81.83 | 24.96 |
September | 74.17 | 26.31 | 485.00 | 24.80 | 74.17 | 24.97 |
October | 40.50 | 25.50 | 446.00 | 24.57 | 24.00 | 24.68 |
November | 151.50 | 23.27 | 202.33 | 23.91 | 2.50 | 23.93 |
December | 364.67 | 22.58 | 52.67 | 22.74 | 6.67 | 22.70 |
Annual Sum or Average | 1708.00 | 23.67 | 4104.83 | 24.26 | 483.00 | 24.41 |
Minimum of Months | 27.00 | 22.17 | 39.50 | 22.12 | 0.50 | 22.01 |
Maximum of Months | 404.00 | 26.93 | 514.00 | 25.01 | 114.50 | 25.24 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.97265 | 38.32076 | 0.28917 | 7.03291 |
February | 454.00000 | 24.24561 | 39.53037 | 0.39579 | 8.45955 |
March | 514.00000 | 24.29930 | 43.31363 | 0.46816 | 9.75910 |
April | 485.00000 | 24.37451 | 44.49889 | 0.51425 | 10.73984 |
May | 508.00000 | 24.37751 | 50.20462 | -0.2850 | 7.10371 |
June | 496.00000 | 24.33777 | 52.73217 | -0.2800 | 7.02234 |
July | 497.00000 | 24.38111 | 54.02570 | -0.2611 | 6.85360 |
August | 514.00000 | 24.35038 | 54.12472 | -0.2695 | 6.95499 |
September | 485.00000 | 24.41776 | 53.84704 | -0.2555 | 6.92404 |
October | 502.00000 | 24.41600 | 49.05068 | 0.55426 | 11.65474 |
November | 489.00000 | 24.34523 | 42.64990 | 0.47117 | 9.80526 |
December | 497.00000 | 24.20234 | 36.87160 | 0.35996 | 7.84168 |
Annual Sum or Average | 5943.00000 | 24.31010 | 46.65644 | 0.13908 | 8.34090 |
Minimum of Months | 454.00000 | 23.97265 | 36.87160 | -0.2850 | 6.85360 |
Maximum of Months | 514.00000 | 24.41776 | 54.12472 | 0.55426 | 11.65474 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.20732 | 40.86625 | 0.10869 | 5.91566 |
February | 454.00000 | 23.85748 | 41.11165 | 0.29882 | 7.25519 |
March | 514.00000 | 24.18211 | 44.21636 | 0.43530 | 9.14206 |
April | 485.00000 | 24.33170 | 45.72287 | 0.50823 | 10.61393 |
May | 508.00000 | 24.35132 | 51.92712 | -0.2838 | 7.08154 |
June | 496.00000 | 24.31320 | 54.81798 | -0.2778 | 6.96626 |
July | 497.00000 | 24.38058 | 56.13005 | -0.2521 | 6.80256 |
August | 514.00000 | 24.33236 | 56.57404 | -0.2690 | 6.94151 |
September | 485.00000 | 24.38606 | 56.00809 | -0.2641 | 7.03608 |
October | 502.00000 | 24.33870 | 49.87622 | 0.52907 | 11.05353 |
November | 489.00000 | 24.14457 | 43.15289 | 0.40637 | 8.62956 |
December | 497.00000 | 23.63307 | 38.58896 | 0.21453 | 6.32804 |
Annual Sum or Average | 5943.00000 | 24.12304 | 48.31045 | 0.09385 | 7.81391 |
Minimum of Months | 454.00000 | 23.20732 | 38.58896 | -0.2838 | 5.91566 |
Maximum of Months | 514.00000 | 24.38606 | 56.57404 | 0.52907 | 11.05353 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.41870 | 42.09063 | -0.0860 | 6.58283 |
February | 454.00000 | 23.40041 | 41.53456 | 0.18314 | 6.67883 |
March | 514.00000 | 24.06737 | 43.37934 | 0.40196 | 8.71329 |
April | 485.00000 | 24.36445 | 45.00387 | 0.52483 | 11.07494 |
May | 508.00000 | 24.42673 | 51.37451 | -0.2330 | 6.80910 |
June | 496.00000 | 24.37227 | 54.40670 | -0.2292 | 6.65341 |
July | 497.00000 | 24.46167 | 55.84102 | -0.2031 | 6.64176 |
August | 514.00000 | 24.38541 | 56.52161 | -0.2325 | 6.75840 |
September | 485.00000 | 24.40817 | 55.95823 | -0.2448 | 6.92164 |
October | 502.00000 | 24.27135 | 49.24581 | 0.50800 | 10.65766 |
November | 489.00000 | 23.81170 | 43.08649 | 0.31576 | 7.54988 |
December | 497.00000 | 22.87190 | 39.66636 | 0.02518 | 6.10551 |
Annual Sum or Average | 5943.00000 | 23.94208 | 48.23216 | 0.05921 | 7.59786 |
Minimum of Months | 454.00000 | 22.41870 | 39.66636 | -0.2448 | 6.10551 |
Maximum of Months | 514.00000 | 24.46167 | 56.52161 | 0.52483 | 11.07494 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.66654 | 45.63242 | -0.2667 | 8.64195 |
February | 454.00000 | 22.84873 | 44.54791 | 0.05788 | 7.05683 |
March | 514.00000 | 23.89082 | 44.63544 | 0.37289 | 8.87388 |
April | 485.00000 | 24.46533 | 44.98227 | 0.58558 | 12.90364 |
May | 508.00000 | 24.60307 | 51.38375 | -0.0850 | 6.64263 |
June | 496.00000 | 24.54668 | 54.66520 | -0.0695 | 6.43844 |
July | 497.00000 | 24.67459 | 56.94238 | -0.0378 | 6.99759 |
August | 514.00000 | 24.51672 | 57.51034 | -0.1086 | 6.65355 |
September | 485.00000 | 24.52379 | 57.40060 | -0.1459 | 6.87034 |
October | 502.00000 | 24.22378 | 49.82670 | 0.51126 | 11.21773 |
November | 489.00000 | 23.39765 | 45.09412 | 0.21956 | 7.34368 |
December | 497.00000 | 22.09426 | 42.91532 | -0.1603 | 7.56800 |
Annual Sum or Average | 5943.00000 | 23.79447 | 49.67206 | 0.07225 | 8.10078 |
Minimum of Months | 454.00000 | 21.66654 | 42.91532 | -0.2667 | 6.43844 |
Maximum of Months | 514.00000 | 24.67459 | 57.51034 | 0.58558 | 12.90364 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.21541 | 45.17421 | -0.1221 | 7.70278 |
February | 454.00000 | 23.32686 | 43.28608 | 0.19108 | 7.68412 |
March | 514.00000 | 24.10117 | 43.80752 | 0.46327 | 10.62426 |
April | 485.00000 | 24.55351 | 44.63336 | 0.66677 | 15.29698 |
May | 508.00000 | 24.64235 | 51.19475 | 0.00403 | 6.89094 |
June | 496.00000 | 24.56739 | 54.54441 | -0.0136 | 6.54559 |
July | 497.00000 | 24.69674 | 56.86731 | 0.00284 | 7.24531 |
August | 514.00000 | 24.53418 | 57.44927 | -0.0734 | 6.69537 |
September | 485.00000 | 24.55316 | 57.27807 | -0.0939 | 6.77610 |
October | 502.00000 | 24.37032 | 49.32115 | 0.58466 | 13.20821 |
November | 489.00000 | 23.76501 | 43.94843 | 0.33103 | 8.71354 |
December | 497.00000 | 22.66116 | 42.09496 | -0.0146 | 7.13628 |
Annual Sum or Average | 5943.00000 | 24.00361 | 49.18351 | 0.15961 | 8.70763 |
Minimum of Months | 454.00000 | 22.21541 | 42.09496 | -0.1221 | 6.54559 |
Maximum of Months | 514.00000 | 24.69674 | 57.44927 | 0.66677 | 15.29698 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.72204 | 41.57156 | 0.02254 | 8.52504 |
February | 454.00000 | 23.50577 | 41.69921 | 0.26200 | 9.25959 |
March | 514.00000 | 24.08028 | 43.44356 | 0.47344 | 11.13356 |
April | 485.00000 | 24.50969 | 44.67322 | 0.63177 | 14.30277 |
May | 508.00000 | 24.60386 | 51.34073 | -0.0743 | 6.68940 |
June | 496.00000 | 24.54312 | 54.67718 | -0.0725 | 6.45821 |
July | 497.00000 | 24.67376 | 56.93385 | -0.0362 | 7.02323 |
August | 514.00000 | 24.52404 | 57.39897 | -0.0936 | 6.68578 |
September | 485.00000 | 24.55663 | 57.04031 | -0.0906 | 6.85408 |
October | 502.00000 | 24.41772 | 48.68836 | 0.63258 | 14.81669 |
November | 489.00000 | 23.98394 | 42.18920 | 0.44038 | 11.41120 |
December | 497.00000 | 23.18814 | 38.84298 | 0.14337 | 8.73559 |
Annual Sum or Average | 5943.00000 | 24.11294 | 48.26495 | 0.18517 | 9.31437 |
Minimum of Months | 454.00000 | 22.72204 | 38.84298 | -0.0936 | 6.45821 |
Maximum of Months | 514.00000 | 24.67376 | 57.39897 | 0.63258 | 14.81669 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.05433 | 45.07424 | -0.1611 | 8.53725 |
February | 454.00000 | 23.10085 | 44.01968 | 0.13771 | 8.01840 |
March | 514.00000 | 23.99521 | 44.29299 | 0.43492 | 10.32050 |
April | 485.00000 | 24.53109 | 44.79039 | 0.65276 | 14.99093 |
May | 508.00000 | 24.64276 | 51.30886 | -0.0118 | 7.10665 |
June | 496.00000 | 24.58034 | 54.63040 | -0.0051 | 6.81067 |
July | 497.00000 | 24.69826 | 56.99772 | -0.0038 | 7.32922 |
August | 514.00000 | 24.53866 | 57.57570 | -0.0758 | 6.78678 |
September | 485.00000 | 24.56408 | 57.37696 | -0.0929 | 6.91928 |
October | 502.00000 | 24.30965 | 49.62121 | 0.56593 | 12.84740 |
November | 489.00000 | 23.61177 | 44.51816 | 0.29779 | 8.75851 |
December | 497.00000 | 22.44858 | 42.24618 | -0.0622 | 7.77319 |
Annual Sum or Average | 5943.00000 | 23.92875 | 49.41762 | 0.13901 | 8.84606 |
Minimum of Months | 454.00000 | 22.05433 | 42.24618 | -0.1611 | 6.78678 |
Maximum of Months | 514.00000 | 24.69826 | 57.57570 | 0.65276 | 14.99093 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.32677 | 44.53022 | -0.0912 | 6.25846 |
February | 454.00000 | 23.13359 | 44.63010 | 0.12682 | 6.32938 |
March | 514.00000 | 23.88406 | 45.87354 | 0.35390 | 8.08722 |
April | 485.00000 | 24.35470 | 45.01972 | 0.51785 | 10.95632 |
May | 508.00000 | 24.54214 | 50.27706 | -0.1681 | 6.56270 |
June | 496.00000 | 24.51656 | 52.78061 | -0.1302 | 6.33828 |
July | 497.00000 | 24.65604 | 54.28464 | -0.0732 | 6.64360 |
August | 514.00000 | 24.52360 | 54.34436 | -0.1207 | 6.44747 |
September | 485.00000 | 24.56007 | 54.46259 | -0.1386 | 6.60820 |
October | 502.00000 | 24.38927 | 49.58405 | 0.56234 | 11.93139 |
November | 489.00000 | 23.93096 | 45.02785 | 0.36283 | 8.09097 |
December | 497.00000 | 23.01138 | 41.72907 | 0.07503 | 5.89539 |
Annual Sum or Average | 5943.00000 | 23.99123 | 48.58249 | 0.10537 | 7.51480 |
Minimum of Months | 454.00000 | 22.32677 | 41.72907 | -0.1681 | 5.89539 |
Maximum of Months | 514.00000 | 24.65604 | 54.46259 | 0.56234 | 11.93139 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.99048 | 43.67605 | 0.07779 | 6.20790 |
February | 454.00000 | 23.67466 | 43.12106 | 0.27637 | 7.46558 |
March | 514.00000 | 24.15132 | 44.70510 | 0.45809 | 9.99420 |
April | 485.00000 | 24.52058 | 44.31995 | 0.61680 | 13.63172 |
May | 508.00000 | 24.61806 | 49.89525 | -0.0632 | 6.48915 |
June | 496.00000 | 24.55643 | 52.56199 | -0.0656 | 6.30417 |
July | 497.00000 | 24.69217 | 54.14044 | -0.0264 | 6.84565 |
August | 514.00000 | 24.55341 | 54.24195 | -0.0799 | 6.47933 |
September | 485.00000 | 24.60094 | 54.26086 | -0.0808 | 6.50803 |
October | 502.00000 | 24.54249 | 48.99693 | 0.63945 | 14.18661 |
November | 489.00000 | 24.21972 | 43.95938 | 0.46187 | 9.94226 |
December | 497.00000 | 23.53131 | 40.52457 | 0.21289 | 6.63198 |
Annual Sum or Average | 5943.00000 | 24.22421 | 47.91039 | 0.20086 | 8.38736 |
Minimum of Months | 454.00000 | 22.99048 | 40.52457 | -0.0808 | 6.20790 |
Maximum of Months | 514.00000 | 24.69217 | 54.26086 | 0.63945 | 14.18661 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.99216 | 40.59604 | 0.13323 | 7.57793 |
February | 454.00000 | 23.64363 | 41.70419 | 0.31285 | 8.97715 |
March | 514.00000 | 24.10059 | 43.87034 | 0.46341 | 10.53533 |
April | 485.00000 | 24.63306 | 43.86262 | 0.60966 | 13.57151 |
May | 508.00000 | 24.88423 | 51.55629 | -0.0517 | 6.67561 |
June | 496.00000 | 24.85089 | 56.24558 | -0.0145 | 6.55723 |
July | 497.00000 | 24.83631 | 60.46437 | 0.02440 | 6.61906 |
August | 514.00000 | 24.68291 | 61.90379 | -0.0067 | 6.31678 |
September | 485.00000 | 24.77819 | 59.48257 | 0.01110 | 6.46437 |
October | 502.00000 | 24.78852 | 49.33692 | 0.73945 | 17.50597 |
November | 489.00000 | 24.34277 | 42.23956 | 0.55861 | 12.85596 |
December | 497.00000 | 23.67387 | 38.02463 | 0.30399 | 8.74217 |
Annual Sum or Average | 5943.00000 | 24.35465 | 49.17768 | 0.25557 | 9.35753 |
Minimum of Months | 454.00000 | 22.99216 | 38.02463 | -0.0517 | 6.31678 |
Maximum of Months | 514.00000 | 24.88423 | 61.90379 | 0.73945 | 17.50597 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.82041 | 43.81295 | 0.03874 | 6.35262 |
February | 454.00000 | 23.52697 | 43.68239 | 0.23752 | 7.34270 |
March | 514.00000 | 24.09927 | 44.98624 | 0.44064 | 9.68788 |
April | 485.00000 | 24.50332 | 44.50849 | 0.60627 | 13.33335 |
May | 508.00000 | 24.61951 | 50.03771 | -0.0769 | 6.60429 |
June | 496.00000 | 24.57435 | 52.61457 | -0.0543 | 6.44932 |
July | 497.00000 | 24.69543 | 54.24997 | -0.0319 | 6.89025 |
August | 514.00000 | 24.55804 | 54.33663 | -0.0818 | 6.52997 |
September | 485.00000 | 24.61781 | 54.34327 | -0.0771 | 6.61753 |
October | 502.00000 | 24.52293 | 49.19629 | 0.63011 | 13.91712 |
November | 489.00000 | 24.17416 | 44.15070 | 0.44935 | 9.75359 |
December | 497.00000 | 23.41567 | 40.82516 | 0.18547 | 6.60105 |
Annual Sum or Average | 5943.00000 | 24.18125 | 48.10290 | 0.18757 | 8.33748 |
Minimum of Months | 454.00000 | 22.82041 | 40.82516 | -0.0818 | 6.35262 |
Maximum of Months | 514.00000 | 24.69543 | 54.34327 | 0.63011 | 13.91712 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.17922 | 44.82762 | -0.1272 | 6.74538 |
February | 454.00000 | 23.23592 | 44.12306 | 0.15825 | 6.68447 |
March | 514.00000 | 24.02861 | 45.18852 | 0.40871 | 8.96558 |
April | 485.00000 | 24.46963 | 45.39239 | 0.57488 | 12.43597 |
May | 508.00000 | 24.58575 | 51.55711 | -0.1203 | 6.53919 |
June | 496.00000 | 24.53551 | 54.70410 | -0.1054 | 6.38265 |
July | 497.00000 | 24.65547 | 56.91033 | -0.0705 | 6.83061 |
August | 514.00000 | 24.50072 | 57.25863 | -0.1364 | 6.60164 |
September | 485.00000 | 24.52041 | 57.18766 | -0.1618 | 6.82522 |
October | 502.00000 | 24.31276 | 50.27856 | 0.53468 | 11.37569 |
November | 489.00000 | 23.74409 | 45.08447 | 0.31051 | 7.59682 |
December | 497.00000 | 22.68573 | 42.17969 | -0.0054 | 6.16591 |
Annual Sum or Average | 5943.00000 | 23.95944 | 49.60502 | 0.10389 | 7.76318 |
Minimum of Months | 454.00000 | 22.17922 | 42.17969 | -0.1618 | 6.16591 |
Maximum of Months | 514.00000 | 24.65547 | 57.25863 | 0.57488 | 12.43597 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.58407 | 44.48617 | -0.0198 | 6.55835 |
February | 385.00000 | 23.59421 | 42.77520 | 0.25590 | 7.61992 |
March | 433.00000 | 24.24490 | 43.75980 | 0.48154 | 10.67959 |
April | 410.00000 | 24.67226 | 44.06369 | 0.65675 | 14.98530 |
May | 430.00000 | 24.74551 | 50.82186 | -0.0196 | 6.91317 |
June | 418.00000 | 24.66712 | 54.24611 | -0.0365 | 6.59567 |
July | 422.00000 | 24.80583 | 56.68003 | -0.0055 | 7.27335 |
August | 433.00000 | 24.62233 | 57.06934 | -0.0848 | 6.77233 |
September | 410.00000 | 24.65545 | 57.03589 | -0.0950 | 6.85273 |
October | 427.00000 | 24.53343 | 49.19837 | 0.60507 | 13.53400 |
November | 417.00000 | 24.03642 | 43.67165 | 0.39227 | 9.10825 |
December | 422.00000 | 23.06594 | 41.36670 | 0.09378 | 6.41133 |
Annual Sum or Average | 5034.00000 | 24.18818 | 48.80744 | 0.18428 | 8.60669 |
Minimum of Months | 385.00000 | 22.58407 | 41.36670 | -0.0950 | 6.41133 |
Maximum of Months | 433.00000 | 24.80583 | 57.06934 | 0.65675 | 14.98530 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17113 | 40.80068 | 0.14669 | 7.67139 |
February | 454.00000 | 23.82497 | 41.41288 | 0.34695 | 9.26199 |
March | 514.00000 | 24.20876 | 43.98007 | 0.50508 | 11.24366 |
April | 485.00000 | 24.52641 | 45.01713 | 0.62213 | 13.82502 |
May | 508.00000 | 24.58748 | 51.50110 | -0.1098 | 6.54623 |
June | 496.00000 | 24.53131 | 54.71569 | -0.1086 | 6.39886 |
July | 497.00000 | 24.65389 | 56.89815 | -0.0693 | 6.84335 |
August | 514.00000 | 24.50946 | 57.13022 | -0.1215 | 6.60759 |
September | 485.00000 | 24.55674 | 56.77672 | -0.1072 | 6.72598 |
October | 502.00000 | 24.51939 | 49.05548 | 0.65542 | 15.03571 |
November | 489.00000 | 24.23928 | 42.38156 | 0.51030 | 11.90840 |
December | 497.00000 | 23.64020 | 38.33951 | 0.26835 | 8.50055 |
Annual Sum or Average | 5943.00000 | 24.24984 | 48.22635 | 0.20965 | 9.20329 |
Minimum of Months | 454.00000 | 23.17113 | 38.33951 | -0.1215 | 6.39886 |
Maximum of Months | 514.00000 | 24.65389 | 57.13022 | 0.65542 | 15.03571 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.54150 | 44.25338 | -0.0279 | 6.91839 |
February | 454.00000 | 23.47404 | 43.58051 | 0.23416 | 7.71880 |
March | 514.00000 | 24.13544 | 44.79238 | 0.46981 | 10.41350 |
April | 485.00000 | 24.54646 | 45.17307 | 0.64343 | 14.50246 |
May | 508.00000 | 24.62953 | 51.46943 | -0.0466 | 6.81222 |
June | 496.00000 | 24.57244 | 54.64699 | -0.0407 | 6.60117 |
July | 497.00000 | 24.68348 | 56.94321 | -0.0356 | 7.08955 |
August | 514.00000 | 24.52675 | 57.30745 | -0.1030 | 6.68068 |
September | 485.00000 | 24.56586 | 57.15098 | -0.1084 | 6.80817 |
October | 502.00000 | 24.40893 | 50.05147 | 0.59022 | 13.03681 |
November | 489.00000 | 23.93795 | 44.49599 | 0.38324 | 9.03970 |
December | 497.00000 | 22.99916 | 41.52319 | 0.08317 | 6.67890 |
Annual Sum or Average | 5943.00000 | 24.08915 | 49.33212 | 0.16891 | 8.52129 |
Minimum of Months | 454.00000 | 22.54150 | 41.52319 | -0.1084 | 6.60117 |
Maximum of Months | 514.00000 | 24.68348 | 57.30745 | 0.64343 | 14.50246 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.123096E+11 | 0.311884E+10 | 321.09 | 0.101162E+11 | 0.219345E+10 | 0.00 | 0.79 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 27402.94 | 12-JAN-15:00 | 27402.94 | 12-JAN-15:00 | 6483.56 | 17-JAN-15:00 | 6323.21 | 12-JAN-15:00 | 0.00 |
February | 0.217976E+11 | 0.527423E+10 | 349.37 | 0.189199E+11 | 0.287767E+10 | 0.00 | 1.00 | 21-FEB-13:00 | 0.00 | 01-FEB-00:10 | 42223.51 | 22-FEB-15:00 | 42223.51 | 22-FEB-15:00 | 8162.17 | 25-FEB-17:00 | 9957.92 | 22-FEB-15:00 | 0.00 |
March | 0.451916E+11 | 0.111433E+11 | 439.43 | 0.414996E+11 | 0.369204E+10 | 0.00 | 1.00 | 01-MAR-14:50 | 0.00 | 01-MAR-00:10 | 64111.86 | 29-MAR-11:20 | 60509.87 | 28-MAR-15:50 | 17620.22 | 10-MAR-17:20 | 17987.26 | 28-MAR-15:50 | 0.00 |
April | 0.679275E+11 | 0.187534E+11 | 443.30 | 0.632451E+11 | 0.468241E+10 | 0.00 | 1.00 | 01-APR-13:30 | 0.00 | 01-APR-00:10 | 95329.49 | 27-APR-06:03 | 81865.75 | 17-APR-04:02 | 27110.74 | 26-APR-05:03 | 24910.72 | 18-APR-15:20 | 0.00 |
May | 0.102629E+12 | 0.298589E+11 | 511.81 | 0.847299E+11 | 0.178992E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:25 | 118662.58 | 24-MAY-05:03 | 88042.98 | 30-MAY-06:03 | 52627.11 | 24-MAY-05:03 | 32029.28 | 30-MAY-15:30 | 0.00 |
June | 0.117910E+12 | 0.333419E+11 | 511.64 | 0.862457E+11 | 0.316639E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 120023.80 | 26-JUN-04:02 | 91309.43 | 12-JUN-06:03 | 57420.68 | 28-JUN-12:02 | 34462.65 | 11-JUN-13:51 | 0.00 |
July | 0.129955E+12 | 0.334272E+11 | 525.43 | 0.791028E+11 | 0.508521E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:05 | 122423.65 | 20-JUL-04:03 | 80112.04 | 05-JUL-06:03 | 58690.02 | 20-JUL-04:03 | 34480.81 | 02-JUL-16:22 | 0.00 |
August | 0.131530E+12 | 0.326700E+11 | 504.99 | 0.776120E+11 | 0.539184E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 121060.84 | 10-AUG-04:02 | 78248.17 | 07-AUG-06:03 | 63695.39 | 27-AUG-10:32 | 31102.71 | 27-AUG-15:12 | 0.00 |
September | 0.105004E+12 | 0.259185E+11 | 461.31 | 0.672290E+11 | 0.377745E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 120036.37 | 17-SEP-16:22 | 79017.31 | 26-SEP-06:03 | 55280.30 | 09-SEP-05:03 | 31044.65 | 17-SEP-17:42 | 0.00 |
October | 0.689567E+11 | 0.171946E+11 | 451.28 | 0.582880E+11 | 0.106686E+11 | 0.00 | 1.00 | 01-OCT-10:02 | 0.00 | 01-OCT-00:10 | 110590.85 | 04-OCT-06:03 | 78296.24 | 02-OCT-05:12 | 37347.13 | 12-OCT-06:03 | 24959.42 | 04-OCT-06:03 | 0.00 |
November | 0.396415E+11 | 0.945659E+10 | 409.06 | 0.363591E+11 | 0.328241E+10 | 0.00 | 1.00 | 01-NOV-10:00 | 0.00 | 01-NOV-00:10 | 56008.63 | 06-NOV-14:00 | 51699.13 | 13-NOV-15:00 | 10187.90 | 08-NOV-17:10 | 13790.69 | 06-NOV-14:00 | 0.00 |
December | 0.173904E+11 | 0.429111E+10 | 363.15 | 0.152185E+11 | 0.217182E+10 | 0.00 | 0.98 | 01-DEC-15:00 | 0.00 | 01-DEC-00:10 | 35500.85 | 01-DEC-15:00 | 35500.85 | 01-DEC-15:00 | 5855.24 | 29-DEC-18:00 | 7773.70 | 01-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.860242E+12 | 0.224449E+12 | 5291.85 | 0.638566E+12 | 0.221677E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.123096E+11 | 0.311884E+10 | 321.09 | 0.101162E+11 | 0.217182E+10 | 0.00 | 0.79 | 0.00 | 27402.94 | 27402.94 | 5855.24 | 6323.21 | 0.00 | ||||||
Maximum of Months | 0.131530E+12 | 0.334272E+11 | 525.43 | 0.862457E+11 | 0.539184E+11 | 0.00 | 1.00 | 0.00 | 122423.65 | 91309.43 | 63695.39 | 34480.81 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.100643E+11 | 0.258230E+10 | 303.31 | 0.800305E+10 | 0.206126E+10 | 0.00 | 0.76 | 12-JAN-15:05 | 0.00 | 01-JAN-00:10 | 24905.71 | 12-JAN-15:05 | 24905.71 | 12-JAN-15:05 | 5533.73 | 17-JAN-15:05 | 5807.24 | 12-JAN-15:05 | 0.00 |
February | 0.190197E+11 | 0.464157E+10 | 345.11 | 0.161949E+11 | 0.282475E+10 | 0.00 | 1.00 | 21-FEB-13:05 | 0.00 | 01-FEB-00:10 | 41773.10 | 22-FEB-15:05 | 41773.10 | 22-FEB-15:05 | 7928.30 | 25-FEB-17:00 | 9826.44 | 22-FEB-15:05 | 0.00 |
March | 0.426947E+11 | 0.105562E+11 | 446.67 | 0.391426E+11 | 0.355211E+10 | 0.00 | 1.00 | 01-MAR-15:05 | 0.00 | 01-MAR-00:10 | 62459.13 | 13-MAR-12:02 | 61122.32 | 28-MAR-16:00 | 10490.30 | 10-MAR-21:00 | 18118.63 | 28-MAR-16:00 | 0.00 |
April | 0.661086E+11 | 0.182148E+11 | 453.83 | 0.622464E+11 | 0.386223E+10 | 0.00 | 1.00 | 01-APR-11:00 | 0.00 | 01-APR-00:10 | 93535.03 | 16-APR-16:02 | 82343.09 | 16-APR-15:22 | 26363.82 | 18-APR-12:01 | 29073.42 | 16-APR-16:02 | 0.00 |
May | 0.972228E+11 | 0.281984E+11 | 524.59 | 0.817743E+11 | 0.154484E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:15 | 115142.78 | 24-MAY-05:03 | 88241.40 | 07-MAY-15:51 | 50694.04 | 24-MAY-05:03 | 32415.14 | 28-MAY-15:51 | 0.00 |
June | 0.108080E+12 | 0.304524E+11 | 515.50 | 0.804883E+11 | 0.275921E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 116971.35 | 26-JUN-04:02 | 91741.72 | 12-JUN-06:03 | 52428.22 | 27-JUN-04:02 | 35394.49 | 11-JUN-16:01 | 0.00 |
July | 0.115215E+12 | 0.295489E+11 | 512.96 | 0.708379E+11 | 0.443772E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:05 | 118807.50 | 20-JUL-04:03 | 81889.89 | 04-JUL-17:12 | 60728.95 | 20-JUL-04:03 | 33244.45 | 02-JUL-16:11 | 0.00 |
August | 0.112293E+12 | 0.277984E+11 | 490.99 | 0.664754E+11 | 0.458179E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 118319.90 | 10-AUG-04:02 | 75799.14 | 07-AUG-04:02 | 64633.43 | 27-AUG-10:32 | 30711.46 | 06-AUG-14:52 | 0.00 |
September | 0.883910E+11 | 0.217464E+11 | 444.78 | 0.565870E+11 | 0.318040E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 115923.64 | 11-SEP-04:03 | 75280.26 | 25-SEP-04:02 | 55498.65 | 08-SEP-05:03 | 29915.53 | 24-SEP-15:21 | 0.00 |
October | 0.578738E+11 | 0.145403E+11 | 438.19 | 0.488767E+11 | 0.899711E+10 | 0.00 | 1.00 | 01-OCT-08:53 | 0.00 | 01-OCT-00:10 | 82895.39 | 11-OCT-05:03 | 73255.32 | 01-OCT-14:51 | 25165.04 | 11-OCT-05:03 | 23107.99 | 02-OCT-14:05 | 0.00 |
November | 0.322593E+11 | 0.782372E+10 | 402.33 | 0.289554E+11 | 0.330389E+10 | 0.00 | 1.00 | 01-NOV-10:50 | 0.00 | 01-NOV-00:10 | 51660.09 | 06-NOV-13:05 | 48031.87 | 13-NOV-15:05 | 8139.04 | 08-NOV-19:00 | 12814.54 | 09-NOV-13:03 | 0.00 |
December | 0.134785E+11 | 0.339142E+10 | 343.78 | 0.111189E+11 | 0.235954E+10 | 0.00 | 0.91 | 01-DEC-15:05 | 0.00 | 01-DEC-00:10 | 31411.79 | 01-DEC-15:05 | 31411.79 | 01-DEC-15:05 | 5240.35 | 29-DEC-17:00 | 7006.82 | 01-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.762701E+12 | 0.199495E+12 | 5222.03 | 0.570701E+12 | 0.192000E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.100643E+11 | 0.258230E+10 | 303.31 | 0.800305E+10 | 0.206126E+10 | 0.00 | 0.76 | 0.00 | 24905.71 | 24905.71 | 5240.35 | 5807.24 | 0.00 | ||||||
Maximum of Months | 0.115215E+12 | 0.304524E+11 | 524.59 | 0.817743E+11 | 0.458179E+11 | 0.00 | 1.00 | 0.00 | 118807.50 | 91741.72 | 64633.43 | 35394.49 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.103483E+11 | 0.266996E+10 | 290.39 | 0.799289E+10 | 0.235541E+10 | 0.00 | 0.68 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 25750.74 | 12-JAN-15:00 | 25750.74 | 12-JAN-15:00 | 5563.66 | 17-JAN-15:00 | 6129.80 | 12-JAN-15:00 | 0.00 |
February | 0.196269E+11 | 0.482684E+10 | 332.81 | 0.164351E+11 | 0.319180E+10 | 0.00 | 1.00 | 21-FEB-13:50 | 0.00 | 01-FEB-00:10 | 47115.58 | 22-FEB-15:00 | 47115.58 | 22-FEB-15:00 | 8639.83 | 25-FEB-16:40 | 11113.25 | 22-FEB-15:00 | 0.00 |
March | 0.464156E+11 | 0.115883E+11 | 446.64 | 0.420623E+11 | 0.435333E+10 | 0.00 | 1.00 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 74428.32 | 28-MAR-16:00 | 74428.32 | 28-MAR-16:00 | 11790.00 | 10-MAR-20:30 | 21958.47 | 28-MAR-16:00 | 0.00 |
April | 0.746683E+11 | 0.207698E+11 | 458.72 | 0.701876E+11 | 0.448069E+10 | 0.00 | 1.00 | 01-APR-11:50 | 0.00 | 01-APR-00:10 | 117572.12 | 16-APR-16:42 | 105989.03 | 16-APR-16:02 | 22225.52 | 26-APR-05:03 | 36403.11 | 16-APR-16:02 | 0.00 |
May | 0.109373E+12 | 0.319668E+11 | 535.41 | 0.930567E+11 | 0.163167E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:15 | 134861.33 | 24-MAY-05:03 | 119045.54 | 29-MAY-15:51 | 63150.17 | 24-MAY-05:03 | 41876.92 | 28-MAY-16:01 | 0.00 |
June | 0.121260E+12 | 0.344301E+11 | 530.69 | 0.923352E+11 | 0.289247E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 137194.78 | 27-JUN-04:02 | 118606.52 | 04-JUN-16:01 | 60212.97 | 27-JUN-04:02 | 41690.58 | 11-JUN-15:22 | 0.00 |
July | 0.126269E+12 | 0.325526E+11 | 532.82 | 0.798564E+11 | 0.464123E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:15 | 139284.98 | 20-JUL-04:03 | 100232.69 | 04-JUL-17:12 | 70994.29 | 20-JUL-04:03 | 38967.34 | 02-JUL-16:22 | 0.00 |
August | 0.120495E+12 | 0.299564E+11 | 499.13 | 0.736008E+11 | 0.468943E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 139079.33 | 10-AUG-04:02 | 91028.14 | 06-AUG-16:52 | 72095.57 | 27-AUG-10:32 | 36004.84 | 06-AUG-14:52 | 0.00 |
September | 0.935313E+11 | 0.231781E+11 | 448.14 | 0.612149E+11 | 0.323164E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 133644.34 | 17-SEP-15:22 | 88578.43 | 25-SEP-04:02 | 57095.55 | 08-SEP-05:03 | 34090.49 | 17-SEP-14:42 | 0.00 |
October | 0.612077E+11 | 0.155669E+11 | 438.75 | 0.518080E+11 | 0.939970E+10 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 | 87536.00 | 01-OCT-14:22 | 87536.00 | 01-OCT-14:22 | 19679.02 | 04-OCT-12:15 | 26113.66 | 02-OCT-14:50 | 0.00 |
November | 0.328617E+11 | 0.807833E+10 | 398.03 | 0.290041E+11 | 0.385760E+10 | 0.00 | 1.00 | 01-NOV-12:05 | 0.00 | 01-NOV-00:10 | 55348.60 | 09-NOV-13:40 | 54036.94 | 09-NOV-14:40 | 9260.04 | 08-NOV-18:40 | 13718.96 | 09-NOV-13:40 | 0.00 |
December | 0.132303E+11 | 0.336424E+10 | 324.29 | 0.104363E+11 | 0.279404E+10 | 0.00 | 0.83 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 | 32648.86 | 01-DEC-14:50 | 32648.86 | 01-DEC-14:50 | 5572.13 | 29-DEC-16:00 | 7459.82 | 01-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.829287E+12 | 0.218948E+12 | 5235.81 | 0.627990E+12 | 0.201297E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.103483E+11 | 0.266996E+10 | 290.39 | 0.799289E+10 | 0.235541E+10 | 0.00 | 0.68 | 0.00 | 25750.74 | 25750.74 | 5563.66 | 6129.80 | 0.00 | ||||||
Maximum of Months | 0.126269E+12 | 0.344301E+11 | 535.41 | 0.930567E+11 | 0.468943E+11 | 0.00 | 1.00 | 0.00 | 139284.98 | 119045.54 | 72095.57 | 41876.92 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.43 | 0.00 | 297.43 | 215.55 | 1076.69 | 18.00 | 0.00 | 0.00 |
February | 352.70 | 0.00 | 352.70 | 377.91 | 866.58 | 0.00 | 0.00 | 0.00 |
March | 425.01 | 0.00 | 425.01 | 694.45 | 527.03 | 0.00 | 0.00 | 0.00 |
April | 461.17 | 1.56 | 459.61 | 1201.81 | 189.72 | 0.00 | 0.00 | 0.00 |
May | 510.94 | 14.34 | 496.61 | 1671.38 | 35.96 | 0.00 | 0.00 | 0.00 |
June | 528.91 | 19.59 | 509.32 | 1818.12 | 26.23 | 0.00 | 0.00 | 0.00 |
July | 521.63 | 8.26 | 513.36 | 1609.55 | 5.47 | 0.00 | 0.00 | 0.00 |
August | 478.87 | 1.49 | 477.37 | 1356.71 | 18.82 | 0.00 | 0.00 | 0.00 |
September | 426.68 | 0.03 | 426.65 | 1057.02 | 78.20 | 0.00 | 0.00 | 0.00 |
October | 369.65 | 0.00 | 369.65 | 771.06 | 412.88 | 0.00 | 0.00 | 0.00 |
November | 313.09 | 0.00 | 313.09 | 432.01 | 781.30 | 0.00 | 0.00 | 0.00 |
December | 290.15 | 0.00 | 290.15 | 234.76 | 1064.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 415.00 | 3.79 | 411.21 | 956.18 | 421.66 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 290.15 | 0.00 | 290.15 | 215.55 | 5.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 528.91 | 19.59 | 513.36 | 1818.12 | 1076.69 | 18.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 424.77 | 170.50 | 254.28 | 486.84 | 666.22 | 18.50 | 0.00 | 0.00 |
February | 516.05 | 213.05 | 303.00 | 714.51 | 547.41 | 0.00 | 0.00 | 0.00 |
March | 629.52 | 259.84 | 369.68 | 1079.92 | 339.14 | 0.00 | 0.00 | 0.00 |
April | 748.97 | 349.21 | 399.76 | 1614.55 | 128.19 | 0.00 | 0.00 | 0.00 |
May | 737.19 | 326.83 | 410.36 | 1842.22 | 24.05 | 0.00 | 0.00 | 0.00 |
June | 599.98 | 199.07 | 400.90 | 1669.06 | 17.87 | 0.00 | 0.00 | 0.00 |
July | 504.26 | 106.49 | 397.78 | 1363.95 | 3.30 | 0.00 | 0.00 | 0.00 |
August | 454.36 | 79.07 | 375.29 | 1153.82 | 12.94 | 0.00 | 0.00 | 0.00 |
September | 485.44 | 135.38 | 350.06 | 1075.53 | 53.22 | 0.00 | 0.00 | 0.00 |
October | 531.01 | 214.49 | 316.52 | 1039.10 | 270.85 | 0.00 | 0.00 | 0.00 |
November | 470.82 | 202.10 | 268.72 | 744.37 | 498.46 | 0.00 | 0.00 | 0.00 |
December | 410.53 | 162.66 | 247.88 | 503.58 | 673.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 542.59 | 201.24 | 341.35 | 1108.67 | 268.36 | 18.50 | 0.00 | 0.00 |
Minimum of Months | 410.53 | 79.07 | 247.88 | 486.84 | 3.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 748.97 | 349.21 | 410.36 | 1842.22 | 673.50 | 18.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1352.72 | 821.95 | 530.77 | 1985.53 | 1031.34 | 16.00 | 0.00 | 0.00 |
February | 1286.24 | 714.41 | 571.83 | 2038.81 | 860.17 | 0.00 | 0.00 | 0.00 |
March | 1099.77 | 485.76 | 614.01 | 2037.44 | 540.87 | 0.00 | 0.00 | 0.00 |
April | 772.48 | 218.02 | 554.46 | 1918.98 | 201.29 | 0.00 | 0.00 | 0.00 |
May | 555.52 | 41.12 | 514.39 | 1791.37 | 34.84 | 0.00 | 0.00 | 0.00 |
June | 508.15 | 8.67 | 499.48 | 1776.19 | 26.16 | 0.00 | 0.00 | 0.00 |
July | 530.05 | 7.29 | 522.76 | 1635.50 | 4.88 | 0.00 | 0.00 | 0.00 |
August | 562.27 | 30.03 | 532.24 | 1538.07 | 19.29 | 0.00 | 0.00 | 0.00 |
September | 753.77 | 195.64 | 558.13 | 1724.81 | 83.36 | 0.00 | 0.00 | 0.00 |
October | 1296.79 | 724.12 | 572.67 | 2553.04 | 430.71 | 0.00 | 0.00 | 0.00 |
November | 1619.76 | 1070.62 | 549.13 | 2787.76 | 791.89 | 0.00 | 0.00 | 0.00 |
December | 1445.59 | 905.85 | 539.74 | 2198.17 | 1038.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 980.17 | 433.68 | 546.50 | 1997.89 | 419.93 | 16.00 | 0.00 | 0.00 |
Minimum of Months | 508.15 | 7.29 | 499.48 | 1538.07 | 4.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1619.76 | 1070.62 | 614.01 | 2787.76 | 1038.38 | 16.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.57 | 161.73 | 253.85 | 525.20 | 720.17 | 20.33 | 0.00 | 0.00 |
February | 475.22 | 175.13 | 300.09 | 688.68 | 587.42 | 0.00 | 0.00 | 0.00 |
March | 616.24 | 246.33 | 369.91 | 1079.62 | 364.69 | 0.00 | 0.00 | 0.00 |
April | 749.03 | 351.27 | 397.76 | 1621.25 | 137.66 | 0.00 | 0.00 | 0.00 |
May | 709.26 | 300.85 | 408.41 | 1795.62 | 27.49 | 0.00 | 0.00 | 0.00 |
June | 666.19 | 258.76 | 407.42 | 1791.59 | 19.23 | 0.00 | 0.00 | 0.00 |
July | 494.34 | 96.15 | 398.19 | 1337.64 | 3.99 | 0.00 | 0.00 | 0.00 |
August | 454.00 | 80.69 | 373.31 | 1153.96 | 13.48 | 0.00 | 0.00 | 0.00 |
September | 499.07 | 146.51 | 352.56 | 1102.79 | 57.27 | 0.00 | 0.00 | 0.00 |
October | 519.45 | 206.85 | 312.61 | 1035.66 | 286.74 | 0.00 | 0.00 | 0.00 |
November | 469.93 | 200.28 | 269.65 | 784.64 | 533.19 | 0.00 | 0.00 | 0.00 |
December | 402.12 | 153.34 | 248.78 | 525.38 | 708.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 539.11 | 197.90 | 341.21 | 1121.47 | 286.93 | 20.33 | 0.00 | 0.00 |
Minimum of Months | 402.12 | 80.69 | 248.78 | 525.20 | 3.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 749.03 | 351.27 | 408.41 | 1795.62 | 720.17 | 20.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.14 | 0.00 | 99.14 | 65.08 | 400.35 | 21.17 | 0.00 | 0.00 |
February | 117.56 | 0.00 | 117.56 | 125.70 | 305.89 | 0.00 | 0.00 | 0.00 |
March | 141.66 | 0.00 | 141.66 | 239.04 | 174.75 | 0.00 | 0.00 | 0.00 |
April | 153.72 | 0.52 | 153.19 | 413.84 | 57.30 | 0.00 | 0.00 | 0.00 |
May | 170.31 | 4.78 | 165.53 | 569.32 | 9.32 | 0.00 | 0.00 | 0.00 |
June | 176.29 | 6.53 | 169.76 | 614.05 | 7.84 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 2.75 | 171.11 | 539.73 | 2.21 | 0.00 | 0.00 | 0.00 |
August | 159.61 | 0.50 | 159.12 | 451.03 | 8.03 | 0.00 | 0.00 | 0.00 |
September | 142.22 | 0.01 | 142.21 | 349.78 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 123.21 | 0.00 | 123.21 | 254.97 | 150.81 | 0.00 | 0.00 | 0.00 |
November | 104.36 | 0.00 | 104.36 | 137.51 | 290.13 | 0.00 | 0.00 | 0.00 |
December | 96.71 | 0.00 | 96.71 | 67.36 | 403.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.33 | 1.26 | 137.06 | 319.88 | 152.80 | 21.17 | 0.00 | 0.00 |
Minimum of Months | 96.71 | 0.00 | 96.71 | 65.08 | 2.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 176.29 | 6.53 | 171.11 | 614.05 | 403.28 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.14 | 0.00 | 99.14 | 65.08 | 400.37 | 21.17 | 0.00 | 0.00 |
February | 117.57 | 0.00 | 117.57 | 125.70 | 305.91 | 0.00 | 0.00 | 0.00 |
March | 141.67 | 0.00 | 141.67 | 239.05 | 174.76 | 0.00 | 0.00 | 0.00 |
April | 153.72 | 0.52 | 153.20 | 413.86 | 57.30 | 0.00 | 0.00 | 0.00 |
May | 170.31 | 4.78 | 165.53 | 569.35 | 9.32 | 0.00 | 0.00 | 0.00 |
June | 176.30 | 6.53 | 169.77 | 614.09 | 7.84 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 2.75 | 171.12 | 539.75 | 2.21 | 0.00 | 0.00 | 0.00 |
August | 159.62 | 0.50 | 159.12 | 451.05 | 8.03 | 0.00 | 0.00 | 0.00 |
September | 142.23 | 0.01 | 142.22 | 349.80 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 123.21 | 0.00 | 123.21 | 254.98 | 150.82 | 0.00 | 0.00 | 0.00 |
November | 104.36 | 0.00 | 104.36 | 137.52 | 290.14 | 0.00 | 0.00 | 0.00 |
December | 96.72 | 0.00 | 96.72 | 67.36 | 403.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.33 | 1.26 | 137.07 | 319.90 | 152.81 | 21.17 | 0.00 | 0.00 |
Minimum of Months | 96.72 | 0.00 | 96.72 | 65.08 | 2.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 176.30 | 6.53 | 171.12 | 614.09 | 403.30 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.14 | 0.00 | 99.14 | 65.08 | 400.37 | 21.17 | 0.00 | 0.00 |
February | 117.57 | 0.00 | 117.57 | 125.70 | 305.91 | 0.00 | 0.00 | 0.00 |
March | 141.67 | 0.00 | 141.67 | 239.05 | 174.76 | 0.00 | 0.00 | 0.00 |
April | 153.72 | 0.52 | 153.20 | 413.86 | 57.30 | 0.00 | 0.00 | 0.00 |
May | 170.31 | 4.78 | 165.53 | 569.35 | 9.32 | 0.00 | 0.00 | 0.00 |
June | 176.30 | 6.53 | 169.77 | 614.09 | 7.84 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 2.75 | 171.12 | 539.75 | 2.21 | 0.00 | 0.00 | 0.00 |
August | 159.62 | 0.50 | 159.12 | 451.05 | 8.03 | 0.00 | 0.00 | 0.00 |
September | 142.23 | 0.01 | 142.22 | 349.80 | 31.27 | 0.00 | 0.00 | 0.00 |
October | 123.21 | 0.00 | 123.21 | 254.98 | 150.82 | 0.00 | 0.00 | 0.00 |
November | 104.36 | 0.00 | 104.36 | 137.52 | 290.14 | 0.00 | 0.00 | 0.00 |
December | 96.72 | 0.00 | 96.72 | 67.36 | 403.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.33 | 1.26 | 137.07 | 319.90 | 152.81 | 21.17 | 0.00 | 0.00 |
Minimum of Months | 96.72 | 0.00 | 96.72 | 65.08 | 2.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 176.30 | 6.53 | 171.12 | 614.09 | 403.30 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 408.61 | 164.01 | 244.60 | 444.08 | 723.88 | 21.67 | 0.00 | 0.00 |
February | 496.41 | 204.94 | 291.47 | 682.79 | 567.13 | 0.00 | 0.00 | 0.00 |
March | 605.57 | 249.96 | 355.61 | 1052.79 | 333.04 | 0.00 | 0.00 | 0.00 |
April | 720.47 | 335.92 | 384.55 | 1576.69 | 118.71 | 0.00 | 0.00 | 0.00 |
May | 709.14 | 314.39 | 394.75 | 1792.76 | 20.55 | 0.00 | 0.00 | 0.00 |
June | 577.15 | 191.50 | 385.65 | 1619.40 | 16.43 | 0.00 | 0.00 | 0.00 |
July | 485.08 | 102.43 | 382.64 | 1315.55 | 4.17 | 0.00 | 0.00 | 0.00 |
August | 437.07 | 76.06 | 361.01 | 1106.72 | 16.63 | 0.00 | 0.00 | 0.00 |
September | 466.96 | 130.22 | 336.74 | 1030.59 | 64.20 | 0.00 | 0.00 | 0.00 |
October | 510.80 | 206.33 | 304.47 | 995.43 | 290.89 | 0.00 | 0.00 | 0.00 |
November | 452.90 | 194.41 | 258.50 | 700.97 | 536.97 | 0.00 | 0.00 | 0.00 |
December | 394.91 | 156.47 | 238.45 | 454.54 | 739.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 521.95 | 193.59 | 328.36 | 1065.66 | 284.80 | 21.67 | 0.00 | 0.00 |
Minimum of Months | 394.91 | 76.06 | 238.45 | 444.08 | 4.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.47 | 335.92 | 394.75 | 1792.76 | 739.35 | 21.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.16 | 6.48 | 9.67 | 17.56 | 28.62 | 21.67 | 0.00 | 0.00 |
February | 19.63 | 8.10 | 11.52 | 27.00 | 22.42 | 0.00 | 0.00 | 0.00 |
March | 23.94 | 9.88 | 14.06 | 41.63 | 13.17 | 0.00 | 0.00 | 0.00 |
April | 28.49 | 13.28 | 15.20 | 62.34 | 4.69 | 0.00 | 0.00 | 0.00 |
May | 28.04 | 12.43 | 15.61 | 70.88 | 0.81 | 0.00 | 0.00 | 0.00 |
June | 22.82 | 7.57 | 15.25 | 64.03 | 0.65 | 0.00 | 0.00 | 0.00 |
July | 19.18 | 4.05 | 15.13 | 52.02 | 0.16 | 0.00 | 0.00 | 0.00 |
August | 17.28 | 3.01 | 14.27 | 43.76 | 0.66 | 0.00 | 0.00 | 0.00 |
September | 18.46 | 5.15 | 13.31 | 40.75 | 2.54 | 0.00 | 0.00 | 0.00 |
October | 20.20 | 8.16 | 12.04 | 39.36 | 11.50 | 0.00 | 0.00 | 0.00 |
November | 17.91 | 7.69 | 10.22 | 27.72 | 21.23 | 0.00 | 0.00 | 0.00 |
December | 15.61 | 6.19 | 9.43 | 17.97 | 29.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.64 | 7.65 | 12.98 | 42.14 | 11.26 | 21.67 | 0.00 | 0.00 |
Minimum of Months | 15.61 | 3.01 | 9.43 | 17.56 | 0.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.49 | 13.28 | 15.61 | 70.88 | 29.23 | 21.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.90 | 273.98 | 176.92 | 659.12 | 389.28 | 17.83 | 0.00 | 0.00 |
February | 428.74 | 238.13 | 190.61 | 682.83 | 311.77 | 0.00 | 0.00 | 0.00 |
March | 366.58 | 161.92 | 204.67 | 687.29 | 186.03 | 0.00 | 0.00 | 0.00 |
April | 257.49 | 72.67 | 184.82 | 647.78 | 64.33 | 0.00 | 0.00 | 0.00 |
May | 185.17 | 13.71 | 171.46 | 600.14 | 9.87 | 0.00 | 0.00 | 0.00 |
June | 169.38 | 2.89 | 166.49 | 590.97 | 8.02 | 0.00 | 0.00 | 0.00 |
July | 176.68 | 2.43 | 174.25 | 542.87 | 2.15 | 0.00 | 0.00 | 0.00 |
August | 187.42 | 10.01 | 177.41 | 507.24 | 8.59 | 0.00 | 0.00 | 0.00 |
September | 251.25 | 65.21 | 186.04 | 569.48 | 35.89 | 0.00 | 0.00 | 0.00 |
October | 432.26 | 241.37 | 190.89 | 846.20 | 164.89 | 0.00 | 0.00 | 0.00 |
November | 539.91 | 356.87 | 183.04 | 926.28 | 301.04 | 0.00 | 0.00 | 0.00 |
December | 481.86 | 301.94 | 179.91 | 724.69 | 395.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.72 | 144.56 | 182.16 | 665.06 | 155.80 | 17.83 | 0.00 | 0.00 |
Minimum of Months | 169.38 | 2.43 | 166.49 | 507.24 | 2.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.91 | 356.87 | 204.67 | 926.28 | 395.90 | 17.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.90 | 273.98 | 176.92 | 659.12 | 389.28 | 17.83 | 0.00 | 0.00 |
February | 428.74 | 238.13 | 190.61 | 682.83 | 311.77 | 0.00 | 0.00 | 0.00 |
March | 366.58 | 161.92 | 204.67 | 687.29 | 186.03 | 0.00 | 0.00 | 0.00 |
April | 257.49 | 72.67 | 184.82 | 647.78 | 64.33 | 0.00 | 0.00 | 0.00 |
May | 185.17 | 13.71 | 171.46 | 600.14 | 9.87 | 0.00 | 0.00 | 0.00 |
June | 169.38 | 2.89 | 166.49 | 590.97 | 8.02 | 0.00 | 0.00 | 0.00 |
July | 176.68 | 2.43 | 174.25 | 542.87 | 2.15 | 0.00 | 0.00 | 0.00 |
August | 187.42 | 10.01 | 177.41 | 507.24 | 8.59 | 0.00 | 0.00 | 0.00 |
September | 251.25 | 65.21 | 186.04 | 569.48 | 35.89 | 0.00 | 0.00 | 0.00 |
October | 432.26 | 241.37 | 190.89 | 846.20 | 164.89 | 0.00 | 0.00 | 0.00 |
November | 539.91 | 356.87 | 183.04 | 926.28 | 301.04 | 0.00 | 0.00 | 0.00 |
December | 481.86 | 301.94 | 179.91 | 724.69 | 395.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.72 | 144.56 | 182.16 | 665.06 | 155.80 | 17.83 | 0.00 | 0.00 |
Minimum of Months | 169.38 | 2.43 | 166.49 | 507.24 | 2.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.91 | 356.87 | 204.67 | 926.28 | 395.90 | 17.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.87 | 273.96 | 176.91 | 659.07 | 389.26 | 17.83 | 0.00 | 0.00 |
February | 428.71 | 238.12 | 190.59 | 682.79 | 311.75 | 0.00 | 0.00 | 0.00 |
March | 366.56 | 161.91 | 204.65 | 687.25 | 186.02 | 0.00 | 0.00 | 0.00 |
April | 257.47 | 72.67 | 184.81 | 647.73 | 64.32 | 0.00 | 0.00 | 0.00 |
May | 185.16 | 13.71 | 171.45 | 600.10 | 9.86 | 0.00 | 0.00 | 0.00 |
June | 169.37 | 2.89 | 166.48 | 590.93 | 8.02 | 0.00 | 0.00 | 0.00 |
July | 176.67 | 2.43 | 174.24 | 542.83 | 2.15 | 0.00 | 0.00 | 0.00 |
August | 187.41 | 10.01 | 177.40 | 507.20 | 8.58 | 0.00 | 0.00 | 0.00 |
September | 251.24 | 65.21 | 186.03 | 569.44 | 35.89 | 0.00 | 0.00 | 0.00 |
October | 432.23 | 241.35 | 190.87 | 846.14 | 164.88 | 0.00 | 0.00 | 0.00 |
November | 539.88 | 356.85 | 183.03 | 926.22 | 301.03 | 0.00 | 0.00 | 0.00 |
December | 481.82 | 301.92 | 179.90 | 724.64 | 395.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.70 | 144.55 | 182.15 | 665.02 | 155.79 | 17.83 | 0.00 | 0.00 |
Minimum of Months | 169.37 | 2.43 | 166.48 | 507.20 | 2.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 539.88 | 356.85 | 204.65 | 926.22 | 395.88 | 17.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 399.76 | 155.57 | 244.19 | 493.67 | 784.06 | 24.00 | 0.00 | 0.00 |
February | 457.14 | 168.47 | 288.67 | 663.72 | 611.35 | 0.00 | 0.00 | 0.00 |
March | 592.79 | 236.96 | 355.83 | 1054.33 | 360.44 | 0.00 | 0.00 | 0.00 |
April | 720.53 | 337.90 | 382.63 | 1582.54 | 128.89 | 0.00 | 0.00 | 0.00 |
May | 682.28 | 289.41 | 392.87 | 1744.94 | 24.06 | 0.00 | 0.00 | 0.00 |
June | 640.84 | 248.92 | 391.92 | 1734.86 | 18.29 | 0.00 | 0.00 | 0.00 |
July | 475.54 | 92.49 | 383.04 | 1290.68 | 4.88 | 0.00 | 0.00 | 0.00 |
August | 436.73 | 77.62 | 359.11 | 1106.21 | 17.20 | 0.00 | 0.00 | 0.00 |
September | 480.08 | 140.94 | 339.14 | 1057.05 | 69.16 | 0.00 | 0.00 | 0.00 |
October | 499.69 | 198.98 | 300.72 | 993.33 | 309.43 | 0.00 | 0.00 | 0.00 |
November | 452.05 | 192.66 | 259.39 | 744.80 | 579.05 | 0.00 | 0.00 | 0.00 |
December | 386.82 | 147.50 | 239.32 | 484.60 | 782.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 518.59 | 190.37 | 328.23 | 1080.45 | 306.16 | 24.00 | 0.00 | 0.00 |
Minimum of Months | 386.82 | 77.62 | 239.32 | 484.60 | 4.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.53 | 337.90 | 392.87 | 1744.94 | 784.06 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.81 | 6.15 | 9.66 | 19.52 | 31.00 | 24.00 | 0.00 | 0.00 |
February | 18.07 | 6.66 | 11.41 | 26.24 | 24.17 | 0.00 | 0.00 | 0.00 |
March | 23.44 | 9.37 | 14.07 | 41.69 | 14.25 | 0.00 | 0.00 | 0.00 |
April | 28.49 | 13.36 | 15.13 | 62.57 | 5.10 | 0.00 | 0.00 | 0.00 |
May | 26.98 | 11.44 | 15.53 | 68.99 | 0.95 | 0.00 | 0.00 | 0.00 |
June | 25.34 | 9.84 | 15.50 | 68.59 | 0.72 | 0.00 | 0.00 | 0.00 |
July | 18.80 | 3.66 | 15.15 | 51.03 | 0.19 | 0.00 | 0.00 | 0.00 |
August | 17.27 | 3.07 | 14.20 | 43.74 | 0.68 | 0.00 | 0.00 | 0.00 |
September | 18.98 | 5.57 | 13.41 | 41.79 | 2.73 | 0.00 | 0.00 | 0.00 |
October | 19.76 | 7.87 | 11.89 | 39.28 | 12.23 | 0.00 | 0.00 | 0.00 |
November | 17.87 | 7.62 | 10.26 | 29.45 | 22.90 | 0.00 | 0.00 | 0.00 |
December | 15.29 | 5.83 | 9.46 | 19.16 | 30.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.50 | 7.53 | 12.98 | 42.72 | 12.11 | 24.00 | 0.00 | 0.00 |
Minimum of Months | 15.29 | 3.07 | 9.46 | 19.16 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.49 | 13.36 | 15.53 | 68.99 | 31.00 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.43 | 0.00 | 297.43 | 196.21 | 1175.51 | 16.67 | 0.00 | 0.00 |
February | 352.70 | 0.00 | 352.70 | 364.22 | 933.41 | 0.00 | 0.00 | 0.00 |
March | 425.01 | 0.00 | 425.01 | 695.41 | 555.86 | 0.00 | 0.00 | 0.00 |
April | 461.17 | 1.56 | 459.61 | 1215.62 | 196.00 | 0.00 | 0.00 | 0.00 |
May | 510.94 | 14.34 | 496.61 | 1690.82 | 35.04 | 0.00 | 0.00 | 0.00 |
June | 528.91 | 19.59 | 509.32 | 1838.99 | 25.47 | 0.00 | 0.00 | 0.00 |
July | 521.63 | 8.26 | 513.36 | 1630.61 | 5.46 | 0.00 | 0.00 | 0.00 |
August | 478.87 | 1.49 | 477.37 | 1373.65 | 18.84 | 0.00 | 0.00 | 0.00 |
September | 426.68 | 0.03 | 426.65 | 1066.98 | 80.38 | 0.00 | 0.00 | 0.00 |
October | 369.65 | 0.00 | 369.65 | 774.47 | 435.30 | 0.00 | 0.00 | 0.00 |
November | 313.09 | 0.00 | 313.09 | 420.25 | 840.93 | 0.00 | 0.00 | 0.00 |
December | 290.15 | 0.00 | 290.15 | 211.09 | 1163.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 415.00 | 3.79 | 411.21 | 959.44 | 453.43 | 16.67 | 0.00 | 0.00 |
Minimum of Months | 290.15 | 0.00 | 290.15 | 196.21 | 5.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 528.91 | 19.59 | 513.36 | 1838.99 | 1175.51 | 16.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 424.77 | 170.50 | 254.28 | 462.01 | 723.49 | 19.00 | 0.00 | 0.00 |
February | 516.05 | 213.05 | 303.00 | 698.95 | 584.54 | 0.00 | 0.00 | 0.00 |
March | 629.52 | 259.84 | 369.68 | 1075.94 | 354.94 | 0.00 | 0.00 | 0.00 |
April | 748.97 | 349.21 | 399.76 | 1620.09 | 132.16 | 0.00 | 0.00 | 0.00 |
May | 737.19 | 326.83 | 410.36 | 1851.69 | 23.65 | 0.00 | 0.00 | 0.00 |
June | 599.98 | 199.07 | 400.90 | 1678.69 | 17.47 | 0.00 | 0.00 | 0.00 |
July | 504.26 | 106.49 | 397.78 | 1373.52 | 3.38 | 0.00 | 0.00 | 0.00 |
August | 454.36 | 79.07 | 375.29 | 1160.65 | 13.03 | 0.00 | 0.00 | 0.00 |
September | 485.44 | 135.38 | 350.06 | 1078.42 | 54.87 | 0.00 | 0.00 | 0.00 |
October | 531.01 | 214.49 | 316.52 | 1036.91 | 284.13 | 0.00 | 0.00 | 0.00 |
November | 470.82 | 202.10 | 268.72 | 730.91 | 531.30 | 0.00 | 0.00 | 0.00 |
December | 410.53 | 162.66 | 247.88 | 478.49 | 729.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 542.59 | 201.24 | 341.35 | 1105.29 | 286.42 | 19.00 | 0.00 | 0.00 |
Minimum of Months | 410.53 | 79.07 | 247.88 | 462.01 | 3.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 748.97 | 349.21 | 410.36 | 1851.69 | 729.73 | 19.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1352.72 | 821.95 | 530.77 | 1961.34 | 1116.46 | 15.17 | 0.00 | 0.00 |
February | 1286.24 | 714.41 | 571.83 | 2026.29 | 918.08 | 0.00 | 0.00 | 0.00 |
March | 1099.77 | 485.76 | 614.01 | 2040.37 | 567.20 | 0.00 | 0.00 | 0.00 |
April | 772.48 | 218.02 | 554.46 | 1934.03 | 207.63 | 0.00 | 0.00 | 0.00 |
May | 555.52 | 41.12 | 514.39 | 1811.16 | 34.10 | 0.00 | 0.00 | 0.00 |
June | 508.15 | 8.67 | 499.48 | 1797.21 | 25.26 | 0.00 | 0.00 | 0.00 |
July | 530.05 | 7.29 | 522.76 | 1656.69 | 4.95 | 0.00 | 0.00 | 0.00 |
August | 562.27 | 30.03 | 532.24 | 1555.27 | 19.25 | 0.00 | 0.00 | 0.00 |
September | 753.77 | 195.64 | 558.13 | 1736.24 | 85.40 | 0.00 | 0.00 | 0.00 |
October | 1296.79 | 724.12 | 572.67 | 2557.06 | 451.51 | 0.00 | 0.00 | 0.00 |
November | 1619.76 | 1070.62 | 549.13 | 2779.20 | 842.49 | 0.00 | 0.00 | 0.00 |
December | 1445.59 | 905.85 | 539.74 | 2171.92 | 1120.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 980.17 | 433.68 | 546.50 | 2001.38 | 447.28 | 15.17 | 0.00 | 0.00 |
Minimum of Months | 508.15 | 7.29 | 499.48 | 1555.27 | 4.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1619.76 | 1070.62 | 614.01 | 2779.20 | 1120.34 | 15.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.57 | 161.73 | 253.85 | 513.47 | 784.08 | 20.17 | 0.00 | 0.00 |
February | 475.22 | 175.13 | 300.09 | 681.36 | 631.07 | 0.00 | 0.00 | 0.00 |
March | 616.24 | 246.33 | 369.91 | 1081.65 | 383.74 | 0.00 | 0.00 | 0.00 |
April | 749.03 | 351.27 | 397.76 | 1631.24 | 142.13 | 0.00 | 0.00 | 0.00 |
May | 709.26 | 300.85 | 408.41 | 1808.76 | 26.94 | 0.00 | 0.00 | 0.00 |
June | 666.19 | 258.76 | 407.42 | 1805.77 | 18.82 | 0.00 | 0.00 | 0.00 |
July | 494.34 | 96.15 | 398.19 | 1351.50 | 3.92 | 0.00 | 0.00 | 0.00 |
August | 454.00 | 80.69 | 373.31 | 1165.21 | 13.41 | 0.00 | 0.00 | 0.00 |
September | 499.07 | 146.51 | 352.56 | 1109.84 | 58.64 | 0.00 | 0.00 | 0.00 |
October | 519.45 | 206.85 | 312.61 | 1038.24 | 301.57 | 0.00 | 0.00 | 0.00 |
November | 469.93 | 200.28 | 269.65 | 778.45 | 571.87 | 0.00 | 0.00 | 0.00 |
December | 402.12 | 153.34 | 248.78 | 510.43 | 771.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 539.11 | 197.90 | 341.21 | 1124.34 | 307.54 | 20.17 | 0.00 | 0.00 |
Minimum of Months | 402.12 | 80.69 | 248.78 | 510.43 | 3.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 749.03 | 351.27 | 408.41 | 1808.76 | 784.08 | 20.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796644E+09 | 0.00 | 0.796644E+09 | 0.577319E+09 | 0.288380E+10 |
February | 0.853263E+09 | 0.00 | 0.853263E+09 | 0.914239E+09 | 0.209644E+10 |
March | 0.113835E+10 | 0.00 | 0.113835E+10 | 0.186000E+10 | 0.141159E+10 |
April | 0.119535E+10 | 4053850.16 | 0.119130E+10 | 0.311510E+10 | 0.491759E+09 |
May | 0.136851E+10 | 38403034.35 | 0.133011E+10 | 0.447661E+10 | 96317594.73 |
June | 0.137093E+10 | 50779577.42 | 0.132015E+10 | 0.471256E+10 | 67981965.92 |
July | 0.139712E+10 | 22124250.60 | 0.137500E+10 | 0.431103E+10 | 14661210.01 |
August | 0.128260E+10 | 3997280.29 | 0.127860E+10 | 0.363382E+10 | 50419704.73 |
September | 0.110596E+10 | 77658.52 | 0.110589E+10 | 0.273979E+10 | 0.202699E+09 |
October | 0.990061E+09 | 0.00 | 0.990061E+09 | 0.206520E+10 | 0.110585E+10 |
November | 0.811540E+09 | 0.00 | 0.811540E+09 | 0.111978E+10 | 0.202514E+10 |
December | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.628788E+09 | 0.285091E+10 |
Annual Sum or Average | 0.130875E+11 | 0.119436E+09 | 0.129680E+11 | 0.301542E+11 | 0.132976E+11 |
Minimum of Months | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.577319E+09 | 14661210.01 |
Maximum of Months | 0.139712E+10 | 50779577.42 | 0.137500E+10 | 0.471256E+10 | 0.288380E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113771E+10 | 0.456663E+09 | 0.681052E+09 | 0.130395E+10 | 0.178441E+10 |
February | 0.124842E+10 | 0.515406E+09 | 0.733014E+09 | 0.172853E+10 | 0.132430E+10 |
March | 0.168611E+10 | 0.695968E+09 | 0.990144E+09 | 0.289247E+10 | 0.908361E+09 |
April | 0.194133E+10 | 0.905146E+09 | 0.103618E+10 | 0.418492E+10 | 0.332260E+09 |
May | 0.197449E+10 | 0.875382E+09 | 0.109911E+10 | 0.493421E+10 | 64414735.78 |
June | 0.155514E+10 | 0.515994E+09 | 0.103914E+10 | 0.432621E+10 | 46313925.60 |
July | 0.135062E+10 | 0.285215E+09 | 0.106541E+10 | 0.365320E+10 | 8837273.19 |
August | 0.121697E+10 | 0.211781E+09 | 0.100519E+10 | 0.309039E+10 | 34645750.09 |
September | 0.125825E+10 | 0.350894E+09 | 0.907354E+09 | 0.278777E+10 | 0.137949E+09 |
October | 0.142225E+10 | 0.574497E+09 | 0.847758E+09 | 0.278312E+10 | 0.725434E+09 |
November | 0.122036E+10 | 0.523832E+09 | 0.696524E+09 | 0.192940E+10 | 0.129201E+10 |
December | 0.109957E+10 | 0.435656E+09 | 0.663914E+09 | 0.134879E+10 | 0.180391E+10 |
Annual Sum or Average | 0.171112E+11 | 0.634643E+10 | 0.107648E+11 | 0.349630E+11 | 0.846285E+10 |
Minimum of Months | 0.109957E+10 | 0.211781E+09 | 0.663914E+09 | 0.130395E+10 | 8837273.19 |
Maximum of Months | 0.197449E+10 | 0.905146E+09 | 0.109911E+10 | 0.493421E+10 | 0.180391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362313E+10 | 0.220151E+10 | 0.142162E+10 | 0.531805E+10 | 0.276234E+10 |
February | 0.311167E+10 | 0.172831E+10 | 0.138336E+10 | 0.493229E+10 | 0.208091E+10 |
March | 0.294562E+10 | 0.130105E+10 | 0.164456E+10 | 0.545707E+10 | 0.144867E+10 |
April | 0.200227E+10 | 0.565102E+09 | 0.143717E+10 | 0.497401E+10 | 0.521740E+09 |
May | 0.148789E+10 | 0.110144E+09 | 0.137775E+10 | 0.479801E+10 | 93321669.55 |
June | 0.131713E+10 | 22476516.34 | 0.129466E+10 | 0.460388E+10 | 67805527.45 |
July | 0.141969E+10 | 19526701.18 | 0.140017E+10 | 0.438054E+10 | 13074866.59 |
August | 0.150599E+10 | 80431361.38 | 0.142556E+10 | 0.411957E+10 | 51660293.48 |
September | 0.195378E+10 | 0.507107E+09 | 0.144667E+10 | 0.447070E+10 | 0.216057E+09 |
October | 0.347332E+10 | 0.193949E+10 | 0.153383E+10 | 0.683807E+10 | 0.115361E+10 |
November | 0.419841E+10 | 0.277506E+10 | 0.142335E+10 | 0.722586E+10 | 0.205257E+10 |
December | 0.387187E+10 | 0.242622E+10 | 0.144565E+10 | 0.588758E+10 | 0.278119E+10 |
Annual Sum or Average | 0.309108E+11 | 0.136764E+11 | 0.172343E+11 | 0.630056E+11 | 0.132429E+11 |
Minimum of Months | 0.131713E+10 | 19526701.18 | 0.129466E+10 | 0.411957E+10 | 13074866.59 |
Maximum of Months | 0.419841E+10 | 0.277506E+10 | 0.164456E+10 | 0.722586E+10 | 0.278119E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111307E+10 | 0.433165E+09 | 0.679906E+09 | 0.140670E+10 | 0.192891E+10 |
February | 0.114965E+10 | 0.423677E+09 | 0.725972E+09 | 0.166606E+10 | 0.142109E+10 |
March | 0.165053E+10 | 0.659775E+09 | 0.990756E+09 | 0.289165E+10 | 0.976790E+09 |
April | 0.194149E+10 | 0.910484E+09 | 0.103100E+10 | 0.420228E+10 | 0.356816E+09 |
May | 0.189969E+10 | 0.805809E+09 | 0.109388E+10 | 0.480939E+10 | 73627066.49 |
June | 0.172675E+10 | 0.670718E+09 | 0.105604E+10 | 0.464381E+10 | 49854274.98 |
July | 0.132405E+10 | 0.257529E+09 | 0.106652E+10 | 0.358275E+10 | 10674333.46 |
August | 0.121600E+10 | 0.216121E+09 | 0.999882E+09 | 0.309077E+10 | 36109865.70 |
September | 0.129359E+10 | 0.379760E+09 | 0.913827E+09 | 0.285844E+10 | 0.148453E+09 |
October | 0.139131E+10 | 0.554016E+09 | 0.837290E+09 | 0.277391E+10 | 0.767995E+09 |
November | 0.121806E+10 | 0.519131E+09 | 0.698932E+09 | 0.203378E+10 | 0.138204E+10 |
December | 0.107705E+10 | 0.410703E+09 | 0.666345E+09 | 0.140718E+10 | 0.189639E+10 |
Annual Sum or Average | 0.170012E+11 | 0.624089E+10 | 0.107604E+11 | 0.353667E+11 | 0.904874E+10 |
Minimum of Months | 0.107705E+10 | 0.216121E+09 | 0.666345E+09 | 0.140670E+10 | 10674333.46 |
Maximum of Months | 0.194149E+10 | 0.910484E+09 | 0.109388E+10 | 0.480939E+10 | 0.192891E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265535E+09 | 0.00 | 0.265535E+09 | 0.174299E+09 | 0.107229E+10 |
February | 0.284408E+09 | 0.00 | 0.284408E+09 | 0.304084E+09 | 0.740011E+09 |
March | 0.379432E+09 | 0.00 | 0.379432E+09 | 0.640245E+09 | 0.468054E+09 |
April | 0.398433E+09 | 1351219.45 | 0.397081E+09 | 0.107267E+10 | 0.148520E+09 |
May | 0.456149E+09 | 12800405.81 | 0.443349E+09 | 0.152486E+10 | 24972566.18 |
June | 0.456955E+09 | 16925724.98 | 0.440030E+09 | 0.159163E+10 | 20312984.89 |
July | 0.465685E+09 | 7374401.28 | 0.458310E+09 | 0.144560E+10 | 5910575.16 |
August | 0.427512E+09 | 1332363.72 | 0.426180E+09 | 0.120804E+10 | 21496205.03 |
September | 0.368637E+09 | 25884.95 | 0.368612E+09 | 0.906638E+09 | 81052542.24 |
October | 0.330005E+09 | 0.00 | 0.330005E+09 | 0.682912E+09 | 0.403930E+09 |
November | 0.270500E+09 | 0.00 | 0.270500E+09 | 0.356430E+09 | 0.752009E+09 |
December | 0.259035E+09 | 0.00 | 0.259035E+09 | 0.180418E+09 | 0.108015E+10 |
Annual Sum or Average | 0.436229E+10 | 39810000.20 | 0.432248E+10 | 0.100878E+11 | 0.481870E+10 |
Minimum of Months | 0.259035E+09 | 0.00 | 0.259035E+09 | 0.174299E+09 | 5910575.16 |
Maximum of Months | 0.465685E+09 | 16925724.98 | 0.458310E+09 | 0.159163E+10 | 0.108015E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265546E+09 | 0.00 | 0.265546E+09 | 0.174304E+09 | 0.107235E+10 |
February | 0.284419E+09 | 0.00 | 0.284419E+09 | 0.304096E+09 | 0.740052E+09 |
March | 0.379447E+09 | 0.00 | 0.379447E+09 | 0.640275E+09 | 0.468078E+09 |
April | 0.398450E+09 | 1351255.78 | 0.397099E+09 | 0.107273E+10 | 0.148525E+09 |
May | 0.456169E+09 | 12800749.88 | 0.443368E+09 | 0.152495E+10 | 24972639.55 |
June | 0.456974E+09 | 16926179.95 | 0.440048E+09 | 0.159172E+10 | 20313680.03 |
July | 0.465702E+09 | 7374599.51 | 0.458328E+09 | 0.144568E+10 | 5910550.43 |
August | 0.427528E+09 | 1332399.54 | 0.426196E+09 | 0.120810E+10 | 21496557.14 |
September | 0.368652E+09 | 25885.64 | 0.368626E+09 | 0.906683E+09 | 81054638.80 |
October | 0.330018E+09 | 0.00 | 0.330018E+09 | 0.682948E+09 | 0.403949E+09 |
November | 0.270512E+09 | 0.00 | 0.270512E+09 | 0.356447E+09 | 0.752049E+09 |
December | 0.259045E+09 | 0.00 | 0.259045E+09 | 0.180424E+09 | 0.108021E+10 |
Annual Sum or Average | 0.436246E+10 | 39811070.30 | 0.432265E+10 | 0.100884E+11 | 0.481896E+10 |
Minimum of Months | 0.259045E+09 | 0.00 | 0.259045E+09 | 0.174304E+09 | 5910550.43 |
Maximum of Months | 0.465702E+09 | 16926179.95 | 0.458328E+09 | 0.159172E+10 | 0.108021E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.265546E+09 | 0.00 | 0.265546E+09 | 0.174304E+09 | 0.107235E+10 |
February | 0.284419E+09 | 0.00 | 0.284419E+09 | 0.304096E+09 | 0.740052E+09 |
March | 0.379447E+09 | 0.00 | 0.379447E+09 | 0.640275E+09 | 0.468078E+09 |
April | 0.398450E+09 | 1351255.78 | 0.397099E+09 | 0.107273E+10 | 0.148525E+09 |
May | 0.456169E+09 | 12800749.88 | 0.443368E+09 | 0.152495E+10 | 24972639.55 |
June | 0.456974E+09 | 16926179.95 | 0.440048E+09 | 0.159172E+10 | 20313680.03 |
July | 0.465702E+09 | 7374599.51 | 0.458328E+09 | 0.144568E+10 | 5910550.43 |
August | 0.427528E+09 | 1332399.54 | 0.426196E+09 | 0.120810E+10 | 21496557.14 |
September | 0.368652E+09 | 25885.64 | 0.368626E+09 | 0.906683E+09 | 81054638.80 |
October | 0.330018E+09 | 0.00 | 0.330018E+09 | 0.682948E+09 | 0.403949E+09 |
November | 0.270512E+09 | 0.00 | 0.270512E+09 | 0.356447E+09 | 0.752049E+09 |
December | 0.259045E+09 | 0.00 | 0.259045E+09 | 0.180424E+09 | 0.108021E+10 |
Annual Sum or Average | 0.436246E+10 | 39811070.30 | 0.432265E+10 | 0.100884E+11 | 0.481896E+10 |
Minimum of Months | 0.259045E+09 | 0.00 | 0.259045E+09 | 0.174304E+09 | 5910550.43 |
Maximum of Months | 0.465702E+09 | 16926179.95 | 0.458328E+09 | 0.159172E+10 | 0.108021E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109442E+10 | 0.439285E+09 | 0.655139E+09 | 0.118943E+10 | 0.193884E+10 |
February | 0.120092E+10 | 0.495793E+09 | 0.705124E+09 | 0.165182E+10 | 0.137201E+10 |
March | 0.162196E+10 | 0.669484E+09 | 0.952472E+09 | 0.281980E+10 | 0.892019E+09 |
April | 0.186746E+10 | 0.870701E+09 | 0.996758E+09 | 0.408677E+10 | 0.307707E+09 |
May | 0.189936E+10 | 0.842070E+09 | 0.105729E+10 | 0.480173E+10 | 55027831.62 |
June | 0.149597E+10 | 0.496358E+09 | 0.999609E+09 | 0.419749E+10 | 42592791.55 |
July | 0.129923E+10 | 0.274362E+09 | 0.102487E+10 | 0.352357E+10 | 11176428.75 |
August | 0.117066E+10 | 0.203722E+09 | 0.966940E+09 | 0.296423E+10 | 44544457.13 |
September | 0.121037E+10 | 0.337541E+09 | 0.872831E+09 | 0.267129E+10 | 0.166419E+09 |
October | 0.136814E+10 | 0.552635E+09 | 0.815503E+09 | 0.266617E+10 | 0.779125E+09 |
November | 0.117392E+10 | 0.503898E+09 | 0.670024E+09 | 0.181692E+10 | 0.139181E+10 |
December | 0.105773E+10 | 0.419077E+09 | 0.638654E+09 | 0.121743E+10 | 0.198027E+10 |
Annual Sum or Average | 0.164601E+11 | 0.610493E+10 | 0.103552E+11 | 0.336066E+11 | 0.898155E+10 |
Minimum of Months | 0.105773E+10 | 0.203722E+09 | 0.638654E+09 | 0.118943E+10 | 11176428.75 |
Maximum of Months | 0.189936E+10 | 0.870701E+09 | 0.105729E+10 | 0.480173E+10 | 0.198027E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43272557.31 | 17368935.93 | 25903621.38 | 47028898.07 | 76659943.49 |
February | 47483188.24 | 19603203.13 | 27879985.11 | 65311352.64 | 54247983.72 |
March | 64130679.23 | 26470796.42 | 37659882.80 | 0.111492E+09 | 35269619.92 |
April | 73837664.06 | 34426743.92 | 39410920.14 | 0.161587E+09 | 12166469.72 |
May | 75099087.98 | 33294691.38 | 41804396.60 | 0.189856E+09 | 2175750.92 |
June | 59149191.27 | 19625547.35 | 39523643.92 | 0.165965E+09 | 1684080.63 |
July | 51370442.64 | 10848015.67 | 40522426.98 | 0.139319E+09 | 441905.93 |
August | 46286898.17 | 8054970.18 | 38231927.99 | 0.117203E+09 | 1761247.73 |
September | 47857042.69 | 13346083.51 | 34510959.19 | 0.105620E+09 | 6580041.36 |
October | 54094958.52 | 21850698.24 | 32244260.28 | 0.105418E+09 | 30805899.41 |
November | 46415829.47 | 19923690.20 | 26492139.27 | 71839446.82 | 55031102.19 |
December | 41821736.51 | 16569946.41 | 25251790.11 | 48136191.04 | 78298255.81 |
Annual Sum or Average | 0.650819E+09 | 0.241383E+09 | 0.409436E+09 | 0.132878E+10 | 0.355122E+09 |
Minimum of Months | 41821736.51 | 8054970.18 | 25251790.11 | 47028898.07 | 441905.93 |
Maximum of Months | 75099087.98 | 34426743.92 | 41804396.60 | 0.189856E+09 | 78298255.81 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120769E+10 | 0.733820E+09 | 0.473868E+09 | 0.176538E+10 | 0.104265E+10 |
February | 0.103721E+10 | 0.576092E+09 | 0.461115E+09 | 0.165190E+10 | 0.754224E+09 |
March | 0.981857E+09 | 0.433676E+09 | 0.548181E+09 | 0.184085E+10 | 0.498268E+09 |
April | 0.667416E+09 | 0.188363E+09 | 0.479052E+09 | 0.167903E+10 | 0.166732E+09 |
May | 0.495961E+09 | 36714055.14 | 0.459247E+09 | 0.160740E+10 | 26423784.65 |
June | 0.439042E+09 | 7492019.03 | 0.431550E+09 | 0.153180E+10 | 20784143.63 |
July | 0.473226E+09 | 6508767.39 | 0.466717E+09 | 0.145401E+10 | 5748248.18 |
August | 0.501992E+09 | 26809905.97 | 0.475182E+09 | 0.135858E+10 | 22994814.36 |
September | 0.651250E+09 | 0.169032E+09 | 0.482218E+09 | 0.147609E+10 | 93020607.63 |
October | 0.115775E+10 | 0.646482E+09 | 0.511271E+09 | 0.226646E+10 | 0.441630E+09 |
November | 0.139944E+10 | 0.925001E+09 | 0.474444E+09 | 0.240091E+10 | 0.780308E+09 |
December | 0.129060E+10 | 0.808724E+09 | 0.481877E+09 | 0.194100E+10 | 0.106039E+10 |
Annual Sum or Average | 0.103034E+11 | 0.455872E+10 | 0.574472E+10 | 0.209734E+11 | 0.491318E+10 |
Minimum of Months | 0.439042E+09 | 6508767.39 | 0.431550E+09 | 0.135858E+10 | 5748248.18 |
Maximum of Months | 0.139944E+10 | 0.925001E+09 | 0.548181E+09 | 0.240091E+10 | 0.106039E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120769E+10 | 0.733820E+09 | 0.473868E+09 | 0.176538E+10 | 0.104265E+10 |
February | 0.103721E+10 | 0.576092E+09 | 0.461115E+09 | 0.165190E+10 | 0.754224E+09 |
March | 0.981857E+09 | 0.433676E+09 | 0.548181E+09 | 0.184085E+10 | 0.498268E+09 |
April | 0.667416E+09 | 0.188363E+09 | 0.479052E+09 | 0.167903E+10 | 0.166732E+09 |
May | 0.495961E+09 | 36714055.14 | 0.459247E+09 | 0.160740E+10 | 26423784.65 |
June | 0.439042E+09 | 7492019.03 | 0.431550E+09 | 0.153180E+10 | 20784143.63 |
July | 0.473226E+09 | 6508767.39 | 0.466717E+09 | 0.145401E+10 | 5748248.18 |
August | 0.501992E+09 | 26809905.97 | 0.475182E+09 | 0.135858E+10 | 22994814.36 |
September | 0.651250E+09 | 0.169032E+09 | 0.482218E+09 | 0.147609E+10 | 93020607.63 |
October | 0.115775E+10 | 0.646482E+09 | 0.511271E+09 | 0.226646E+10 | 0.441630E+09 |
November | 0.139944E+10 | 0.925001E+09 | 0.474444E+09 | 0.240091E+10 | 0.780308E+09 |
December | 0.129060E+10 | 0.808724E+09 | 0.481877E+09 | 0.194100E+10 | 0.106039E+10 |
Annual Sum or Average | 0.103034E+11 | 0.455872E+10 | 0.574472E+10 | 0.209734E+11 | 0.491318E+10 |
Minimum of Months | 0.439042E+09 | 6508767.39 | 0.431550E+09 | 0.135858E+10 | 5748248.18 |
Maximum of Months | 0.139944E+10 | 0.925001E+09 | 0.548181E+09 | 0.240091E+10 | 0.106039E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120761E+10 | 0.733774E+09 | 0.473838E+09 | 0.176526E+10 | 0.104259E+10 |
February | 0.103714E+10 | 0.576056E+09 | 0.461086E+09 | 0.165180E+10 | 0.754176E+09 |
March | 0.981795E+09 | 0.433648E+09 | 0.548147E+09 | 0.184073E+10 | 0.498236E+09 |
April | 0.667374E+09 | 0.188352E+09 | 0.479022E+09 | 0.167893E+10 | 0.166721E+09 |
May | 0.495930E+09 | 36711735.02 | 0.459218E+09 | 0.160730E+10 | 26422114.81 |
June | 0.439014E+09 | 7491545.57 | 0.431523E+09 | 0.153170E+10 | 20782830.19 |
July | 0.473196E+09 | 6508356.08 | 0.466688E+09 | 0.145392E+10 | 5747884.92 |
August | 0.501960E+09 | 26808211.74 | 0.475152E+09 | 0.135850E+10 | 22993361.22 |
September | 0.651209E+09 | 0.169022E+09 | 0.482188E+09 | 0.147600E+10 | 93014729.25 |
October | 0.115768E+10 | 0.646441E+09 | 0.511239E+09 | 0.226631E+10 | 0.441602E+09 |
November | 0.139936E+10 | 0.924942E+09 | 0.474414E+09 | 0.240075E+10 | 0.780259E+09 |
December | 0.129052E+10 | 0.808673E+09 | 0.481846E+09 | 0.194088E+10 | 0.106032E+10 |
Annual Sum or Average | 0.103028E+11 | 0.455843E+10 | 0.574436E+10 | 0.209721E+11 | 0.491287E+10 |
Minimum of Months | 0.439014E+09 | 6508356.08 | 0.431523E+09 | 0.135850E+10 | 5747884.92 |
Maximum of Months | 0.139936E+10 | 0.924942E+09 | 0.548147E+09 | 0.240075E+10 | 0.106032E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107072E+10 | 0.416683E+09 | 0.654039E+09 | 0.132226E+10 | 0.210004E+10 |
February | 0.110591E+10 | 0.407556E+09 | 0.698353E+09 | 0.160568E+10 | 0.147897E+10 |
March | 0.158773E+10 | 0.634670E+09 | 0.953063E+09 | 0.282393E+10 | 0.965403E+09 |
April | 0.186762E+10 | 0.875839E+09 | 0.991781E+09 | 0.410196E+10 | 0.334088E+09 |
May | 0.182741E+10 | 0.775147E+09 | 0.105226E+10 | 0.467364E+10 | 64445667.16 |
June | 0.166106E+10 | 0.645197E+09 | 0.101586E+10 | 0.449675E+10 | 47400296.29 |
July | 0.127368E+10 | 0.247730E+09 | 0.102595E+10 | 0.345695E+10 | 13079058.25 |
August | 0.116974E+10 | 0.207897E+09 | 0.961840E+09 | 0.296289E+10 | 46075842.00 |
September | 0.124437E+10 | 0.365310E+09 | 0.879059E+09 | 0.273988E+10 | 0.179259E+09 |
October | 0.133837E+10 | 0.532935E+09 | 0.805436E+09 | 0.266054E+10 | 0.828785E+09 |
November | 0.117172E+10 | 0.499378E+09 | 0.672342E+09 | 0.193053E+10 | 0.150090E+10 |
December | 0.103607E+10 | 0.395075E+09 | 0.640994E+09 | 0.129796E+10 | 0.209653E+10 |
Annual Sum or Average | 0.163544E+11 | 0.600342E+10 | 0.103510E+11 | 0.340730E+11 | 0.965498E+10 |
Minimum of Months | 0.103607E+10 | 0.207897E+09 | 0.640994E+09 | 0.129796E+10 | 13079058.25 |
Maximum of Months | 0.186762E+10 | 0.875839E+09 | 0.105226E+10 | 0.467364E+10 | 0.210004E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42335243.99 | 16475197.86 | 25860046.13 | 52280752.04 | 83033597.42 |
February | 43726500.61 | 16114329.10 | 27612171.51 | 63486762.43 | 58477214.80 |
March | 62777368.40 | 25094215.05 | 37683153.36 | 0.111655E+09 | 38171122.63 |
April | 73843811.15 | 34629772.49 | 39214038.66 | 0.162187E+09 | 13209500.32 |
May | 72253978.13 | 30648507.80 | 41605470.33 | 0.184791E+09 | 2548111.06 |
June | 65676552.45 | 25510413.38 | 40166139.07 | 0.177797E+09 | 1874160.40 |
July | 50359881.44 | 9794970.29 | 40564911.16 | 0.136684E+09 | 517130.97 |
August | 46250253.05 | 8220042.26 | 38030210.79 | 0.117150E+09 | 1821789.76 |
September | 49201115.86 | 14443985.75 | 34757130.11 | 0.108332E+09 | 7087698.30 |
October | 52917825.29 | 21071697.69 | 31846127.60 | 0.105195E+09 | 32769347.93 |
November | 46328608.88 | 19744882.92 | 26583725.95 | 76331292.31 | 59344345.20 |
December | 40965127.72 | 15620867.43 | 25344260.30 | 51319908.95 | 82894771.42 |
Annual Sum or Average | 0.646636E+09 | 0.237369E+09 | 0.409267E+09 | 0.134721E+10 | 0.381749E+09 |
Minimum of Months | 40965127.72 | 8220042.26 | 25344260.30 | 51319908.95 | 517130.97 |
Maximum of Months | 73843811.15 | 34629772.49 | 41605470.33 | 0.184791E+09 | 83033597.42 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796644E+09 | 0.00 | 0.796644E+09 | 0.525524E+09 | 0.314850E+10 |
February | 0.853263E+09 | 0.00 | 0.853263E+09 | 0.881126E+09 | 0.225810E+10 |
March | 0.113835E+10 | 0.00 | 0.113835E+10 | 0.186259E+10 | 0.148882E+10 |
April | 0.119535E+10 | 4053850.16 | 0.119130E+10 | 0.315090E+10 | 0.508028E+09 |
May | 0.136851E+10 | 38403034.35 | 0.133011E+10 | 0.452869E+10 | 93858409.50 |
June | 0.137093E+10 | 50779577.42 | 0.132015E+10 | 0.476666E+10 | 66012141.48 |
July | 0.139712E+10 | 22124250.60 | 0.137500E+10 | 0.436743E+10 | 14628265.68 |
August | 0.128260E+10 | 3997280.29 | 0.127860E+10 | 0.367918E+10 | 50466426.59 |
September | 0.110596E+10 | 77658.52 | 0.110589E+10 | 0.276562E+10 | 0.208334E+09 |
October | 0.990061E+09 | 0.00 | 0.990061E+09 | 0.207434E+10 | 0.116592E+10 |
November | 0.811540E+09 | 0.00 | 0.811540E+09 | 0.108930E+10 | 0.217968E+10 |
December | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.565386E+09 | 0.311702E+10 |
Annual Sum or Average | 0.130875E+11 | 0.119436E+09 | 0.129680E+11 | 0.302567E+11 | 0.142994E+11 |
Minimum of Months | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.525524E+09 | 14628265.68 |
Maximum of Months | 0.139712E+10 | 50779577.42 | 0.137500E+10 | 0.476666E+10 | 0.314850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113771E+10 | 0.456663E+09 | 0.681052E+09 | 0.123744E+10 | 0.193778E+10 |
February | 0.124842E+10 | 0.515406E+09 | 0.733014E+09 | 0.169090E+10 | 0.141411E+10 |
March | 0.168611E+10 | 0.695968E+09 | 0.990144E+09 | 0.288179E+10 | 0.950683E+09 |
April | 0.194133E+10 | 0.905146E+09 | 0.103618E+10 | 0.419927E+10 | 0.342570E+09 |
May | 0.197449E+10 | 0.875382E+09 | 0.109911E+10 | 0.495957E+10 | 63348377.36 |
June | 0.155514E+10 | 0.515994E+09 | 0.103914E+10 | 0.435117E+10 | 45276803.82 |
July | 0.135062E+10 | 0.285215E+09 | 0.106541E+10 | 0.367884E+10 | 9050466.13 |
August | 0.121697E+10 | 0.211781E+09 | 0.100519E+10 | 0.310869E+10 | 34901336.90 |
September | 0.125825E+10 | 0.350894E+09 | 0.907354E+09 | 0.279525E+10 | 0.142233E+09 |
October | 0.142225E+10 | 0.574497E+09 | 0.847758E+09 | 0.277726E+10 | 0.761014E+09 |
November | 0.122036E+10 | 0.523832E+09 | 0.696524E+09 | 0.189452E+10 | 0.137714E+10 |
December | 0.109957E+10 | 0.435656E+09 | 0.663914E+09 | 0.128159E+10 | 0.195451E+10 |
Annual Sum or Average | 0.171112E+11 | 0.634643E+10 | 0.107648E+11 | 0.348563E+11 | 0.903262E+10 |
Minimum of Months | 0.109957E+10 | 0.211781E+09 | 0.663914E+09 | 0.123744E+10 | 9050466.13 |
Maximum of Months | 0.197449E+10 | 0.905146E+09 | 0.109911E+10 | 0.495957E+10 | 0.195451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362313E+10 | 0.220151E+10 | 0.142162E+10 | 0.525325E+10 | 0.299032E+10 |
February | 0.311167E+10 | 0.172831E+10 | 0.138336E+10 | 0.490200E+10 | 0.222101E+10 |
March | 0.294562E+10 | 0.130105E+10 | 0.164456E+10 | 0.546493E+10 | 0.151919E+10 |
April | 0.200227E+10 | 0.565102E+09 | 0.143717E+10 | 0.501300E+10 | 0.538185E+09 |
May | 0.148789E+10 | 0.110144E+09 | 0.137775E+10 | 0.485102E+10 | 91338258.98 |
June | 0.131713E+10 | 22476516.34 | 0.129466E+10 | 0.465836E+10 | 65470664.44 |
July | 0.141969E+10 | 19526701.18 | 0.140017E+10 | 0.443727E+10 | 13261223.64 |
August | 0.150599E+10 | 80431361.38 | 0.142556E+10 | 0.416564E+10 | 51560939.43 |
September | 0.195378E+10 | 0.507107E+09 | 0.144667E+10 | 0.450033E+10 | 0.221356E+09 |
October | 0.347332E+10 | 0.193949E+10 | 0.153383E+10 | 0.684882E+10 | 0.120932E+10 |
November | 0.419841E+10 | 0.277506E+10 | 0.142335E+10 | 0.720368E+10 | 0.218375E+10 |
December | 0.387187E+10 | 0.242622E+10 | 0.144565E+10 | 0.581726E+10 | 0.300072E+10 |
Annual Sum or Average | 0.309108E+11 | 0.136764E+11 | 0.172343E+11 | 0.631156E+11 | 0.141055E+11 |
Minimum of Months | 0.131713E+10 | 19526701.18 | 0.129466E+10 | 0.416564E+10 | 13261223.64 |
Maximum of Months | 0.419841E+10 | 0.277506E+10 | 0.164456E+10 | 0.720368E+10 | 0.300072E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111307E+10 | 0.433165E+09 | 0.679906E+09 | 0.137527E+10 | 0.210007E+10 |
February | 0.114965E+10 | 0.423677E+09 | 0.725972E+09 | 0.164834E+10 | 0.152669E+10 |
March | 0.165053E+10 | 0.659775E+09 | 0.990756E+09 | 0.289709E+10 | 0.102781E+10 |
April | 0.194149E+10 | 0.910484E+09 | 0.103100E+10 | 0.422818E+10 | 0.368394E+09 |
May | 0.189969E+10 | 0.805809E+09 | 0.109388E+10 | 0.484459E+10 | 72166660.18 |
June | 0.172675E+10 | 0.670718E+09 | 0.105604E+10 | 0.468056E+10 | 48784083.18 |
July | 0.132405E+10 | 0.257529E+09 | 0.106652E+10 | 0.361984E+10 | 10499628.00 |
August | 0.121600E+10 | 0.216121E+09 | 0.999882E+09 | 0.312089E+10 | 35921171.66 |
September | 0.129359E+10 | 0.379760E+09 | 0.913827E+09 | 0.287670E+10 | 0.152005E+09 |
October | 0.139131E+10 | 0.554016E+09 | 0.837290E+09 | 0.278082E+10 | 0.807726E+09 |
November | 0.121806E+10 | 0.519131E+09 | 0.698932E+09 | 0.201774E+10 | 0.148229E+10 |
December | 0.107705E+10 | 0.410703E+09 | 0.666345E+09 | 0.136713E+10 | 0.206607E+10 |
Annual Sum or Average | 0.170012E+11 | 0.624089E+10 | 0.107604E+11 | 0.354571E+11 | 0.969843E+10 |
Minimum of Months | 0.107705E+10 | 0.216121E+09 | 0.666345E+09 | 0.136713E+10 | 10499628.00 |
Maximum of Months | 0.194149E+10 | 0.910484E+09 | 0.109388E+10 | 0.484459E+10 | 0.210007E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.55 | 1076.69 | 297.43 | 0.00 | 297.43 | 0.00 | 0.00 |
February | 377.91 | 866.58 | 352.70 | 0.00 | 352.70 | 0.00 | 0.00 |
March | 694.45 | 527.03 | 425.01 | 0.00 | 425.01 | 0.00 | 0.00 |
April | 1201.81 | 189.72 | 461.17 | 1.56 | 459.61 | 0.00 | 0.00 |
May | 1671.38 | 35.96 | 510.94 | 14.34 | 496.61 | 0.00 | 0.00 |
June | 1818.12 | 26.23 | 528.91 | 19.59 | 509.32 | 0.00 | 0.00 |
July | 1609.55 | 5.47 | 521.63 | 8.26 | 513.36 | 0.00 | 0.00 |
August | 1356.71 | 18.82 | 478.87 | 1.49 | 477.37 | 0.00 | 0.00 |
September | 1057.02 | 78.20 | 426.68 | 0.03 | 426.65 | 0.00 | 0.00 |
October | 771.06 | 412.88 | 369.65 | 0.00 | 369.65 | 0.00 | 0.00 |
November | 432.01 | 781.30 | 313.09 | 0.00 | 313.09 | 0.00 | 0.00 |
December | 234.76 | 1064.41 | 290.15 | 0.00 | 290.15 | 0.00 | 0.00 |
Annual Sum or Average | 956.18 | 421.66 | 415.00 | 3.79 | 411.21 | 0.00 | 0.00 |
Minimum of Months | 215.55 | 5.47 | 290.15 | 0.00 | 290.15 | 0.00 | 0.00 |
Maximum of Months | 1818.12 | 1076.69 | 528.91 | 19.59 | 513.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 486.84 | 666.22 | 424.77 | 170.50 | 254.28 | 0.00 | 0.00 |
February | 714.51 | 547.41 | 516.05 | 213.05 | 303.00 | 0.00 | 0.00 |
March | 1079.92 | 339.14 | 629.52 | 259.84 | 369.68 | 0.00 | 0.00 |
April | 1614.55 | 128.19 | 748.97 | 349.21 | 399.76 | 0.00 | 0.00 |
May | 1842.22 | 24.05 | 737.19 | 326.83 | 410.36 | 0.00 | 0.00 |
June | 1669.06 | 17.87 | 599.98 | 199.07 | 400.90 | 0.00 | 0.00 |
July | 1363.95 | 3.30 | 504.26 | 106.49 | 397.78 | 0.00 | 0.00 |
August | 1153.82 | 12.94 | 454.36 | 79.07 | 375.29 | 0.00 | 0.00 |
September | 1075.53 | 53.22 | 485.44 | 135.38 | 350.06 | 0.00 | 0.00 |
October | 1039.10 | 270.85 | 531.01 | 214.49 | 316.52 | 0.00 | 0.00 |
November | 744.37 | 498.46 | 470.82 | 202.10 | 268.72 | 0.00 | 0.00 |
December | 503.58 | 673.50 | 410.53 | 162.66 | 247.88 | 0.00 | 0.00 |
Annual Sum or Average | 1108.67 | 268.36 | 542.59 | 201.24 | 341.35 | 0.00 | 0.00 |
Minimum of Months | 486.84 | 3.30 | 410.53 | 79.07 | 247.88 | 0.00 | 0.00 |
Maximum of Months | 1842.22 | 673.50 | 748.97 | 349.21 | 410.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1985.53 | 1031.34 | 1352.72 | 821.95 | 530.77 | 0.00 | 0.00 |
February | 2038.81 | 860.17 | 1286.24 | 714.41 | 571.83 | 0.00 | 0.00 |
March | 2037.44 | 540.87 | 1099.77 | 485.76 | 614.01 | 0.00 | 0.00 |
April | 1918.98 | 201.29 | 772.48 | 218.02 | 554.46 | 0.00 | 0.00 |
May | 1791.37 | 34.84 | 555.52 | 41.12 | 514.39 | 0.00 | 0.00 |
June | 1776.19 | 26.16 | 508.15 | 8.67 | 499.48 | 0.00 | 0.00 |
July | 1635.50 | 4.88 | 530.05 | 7.29 | 522.76 | 0.00 | 0.00 |
August | 1538.07 | 19.29 | 562.27 | 30.03 | 532.24 | 0.00 | 0.00 |
September | 1724.81 | 83.36 | 753.77 | 195.64 | 558.13 | 0.00 | 0.00 |
October | 2553.04 | 430.71 | 1296.79 | 724.12 | 572.67 | 0.00 | 0.00 |
November | 2787.76 | 791.89 | 1619.76 | 1070.62 | 549.13 | 0.00 | 0.00 |
December | 2198.17 | 1038.38 | 1445.59 | 905.85 | 539.74 | 0.00 | 0.00 |
Annual Sum or Average | 1997.89 | 419.93 | 980.17 | 433.68 | 546.50 | 0.00 | 0.00 |
Minimum of Months | 1538.07 | 4.88 | 508.15 | 7.29 | 499.48 | 0.00 | 0.00 |
Maximum of Months | 2787.76 | 1038.38 | 1619.76 | 1070.62 | 614.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 525.20 | 720.17 | 415.57 | 161.73 | 253.85 | 0.00 | 0.00 |
February | 688.68 | 587.42 | 475.22 | 175.13 | 300.09 | 0.00 | 0.00 |
March | 1079.62 | 364.69 | 616.24 | 246.33 | 369.91 | 0.00 | 0.00 |
April | 1621.25 | 137.66 | 749.03 | 351.27 | 397.76 | 0.00 | 0.00 |
May | 1795.62 | 27.49 | 709.26 | 300.85 | 408.41 | 0.00 | 0.00 |
June | 1791.59 | 19.23 | 666.19 | 258.76 | 407.42 | 0.00 | 0.00 |
July | 1337.64 | 3.99 | 494.34 | 96.15 | 398.19 | 0.00 | 0.00 |
August | 1153.96 | 13.48 | 454.00 | 80.69 | 373.31 | 0.00 | 0.00 |
September | 1102.79 | 57.27 | 499.07 | 146.51 | 352.56 | 0.00 | 0.00 |
October | 1035.66 | 286.74 | 519.45 | 206.85 | 312.61 | 0.00 | 0.00 |
November | 784.64 | 533.19 | 469.93 | 200.28 | 269.65 | 0.00 | 0.00 |
December | 525.38 | 708.03 | 402.12 | 153.34 | 248.78 | 0.00 | 0.00 |
Annual Sum or Average | 1121.47 | 286.93 | 539.11 | 197.90 | 341.21 | 0.00 | 0.00 |
Minimum of Months | 525.20 | 3.99 | 402.12 | 80.69 | 248.78 | 0.00 | 0.00 |
Maximum of Months | 1795.62 | 720.17 | 749.03 | 351.27 | 408.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 195.23 | 1201.09 | 297.43 | 0.00 | 297.43 | 0.00 | 0.00 |
February | 377.10 | 917.71 | 352.70 | 0.00 | 352.70 | 0.00 | 0.00 |
March | 717.14 | 524.27 | 425.00 | 0.00 | 425.00 | 0.00 | 0.00 |
April | 1241.56 | 171.90 | 461.16 | 1.56 | 459.60 | 0.00 | 0.00 |
May | 1708.02 | 27.97 | 510.93 | 14.34 | 496.60 | 0.00 | 0.00 |
June | 1842.23 | 23.51 | 528.90 | 19.59 | 509.31 | 0.00 | 0.00 |
July | 1619.24 | 6.62 | 521.61 | 8.26 | 513.35 | 0.00 | 0.00 |
August | 1353.14 | 24.08 | 478.86 | 1.49 | 477.36 | 0.00 | 0.00 |
September | 1049.38 | 93.81 | 426.67 | 0.03 | 426.64 | 0.00 | 0.00 |
October | 764.94 | 452.44 | 369.64 | 0.00 | 369.64 | 0.00 | 0.00 |
November | 412.55 | 870.41 | 313.09 | 0.00 | 313.09 | 0.00 | 0.00 |
December | 202.09 | 1209.89 | 290.14 | 0.00 | 290.14 | 0.00 | 0.00 |
Annual Sum or Average | 959.68 | 458.42 | 414.99 | 3.79 | 411.21 | 0.00 | 0.00 |
Minimum of Months | 195.23 | 6.62 | 290.14 | 0.00 | 290.14 | 0.00 | 0.00 |
Maximum of Months | 1842.23 | 1209.89 | 528.90 | 19.59 | 513.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 461.64 | 752.50 | 424.77 | 170.50 | 254.27 | 0.00 | 0.00 |
February | 709.79 | 589.56 | 516.04 | 213.04 | 302.99 | 0.00 | 0.00 |
March | 1094.42 | 346.21 | 629.51 | 259.84 | 369.67 | 0.00 | 0.00 |
April | 1639.03 | 123.41 | 748.96 | 349.20 | 399.76 | 0.00 | 0.00 |
May | 1863.65 | 21.36 | 737.18 | 326.82 | 410.36 | 0.00 | 0.00 |
June | 1683.43 | 17.08 | 599.97 | 199.07 | 400.90 | 0.00 | 0.00 |
July | 1367.56 | 4.34 | 504.26 | 106.49 | 397.77 | 0.00 | 0.00 |
August | 1150.48 | 17.29 | 454.36 | 79.07 | 375.29 | 0.00 | 0.00 |
September | 1071.34 | 66.74 | 485.43 | 135.37 | 350.05 | 0.00 | 0.00 |
October | 1034.79 | 302.39 | 531.00 | 214.49 | 316.51 | 0.00 | 0.00 |
November | 728.69 | 558.20 | 470.81 | 202.09 | 268.72 | 0.00 | 0.00 |
December | 472.51 | 768.58 | 410.53 | 162.65 | 247.87 | 0.00 | 0.00 |
Annual Sum or Average | 1107.79 | 296.06 | 542.59 | 201.24 | 341.34 | 0.00 | 0.00 |
Minimum of Months | 461.64 | 4.34 | 410.53 | 79.07 | 247.87 | 0.00 | 0.00 |
Maximum of Months | 1863.65 | 768.58 | 748.96 | 349.20 | 410.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1977.31 | 1167.82 | 1352.67 | 821.91 | 530.75 | 0.00 | 0.00 |
February | 2048.44 | 935.28 | 1286.19 | 714.38 | 571.81 | 0.00 | 0.00 |
March | 2061.84 | 558.08 | 1099.73 | 485.74 | 613.99 | 0.00 | 0.00 |
April | 1943.29 | 192.97 | 772.46 | 218.01 | 554.45 | 0.00 | 0.00 |
May | 1800.37 | 29.60 | 555.50 | 41.12 | 514.38 | 0.00 | 0.00 |
June | 1772.88 | 24.06 | 508.14 | 8.67 | 499.47 | 0.00 | 0.00 |
July | 1628.56 | 6.44 | 530.04 | 7.29 | 522.75 | 0.00 | 0.00 |
August | 1521.68 | 25.76 | 562.25 | 30.03 | 532.23 | 0.00 | 0.00 |
September | 1708.40 | 107.66 | 753.75 | 195.64 | 558.11 | 0.00 | 0.00 |
October | 2538.54 | 494.65 | 1296.74 | 724.09 | 572.65 | 0.00 | 0.00 |
November | 2778.77 | 903.12 | 1619.69 | 1070.58 | 549.11 | 0.00 | 0.00 |
December | 2174.02 | 1187.69 | 1445.54 | 905.81 | 539.73 | 0.00 | 0.00 |
Annual Sum or Average | 1995.15 | 467.38 | 980.14 | 433.66 | 546.48 | 0.00 | 0.00 |
Minimum of Months | 1521.68 | 6.44 | 508.14 | 7.29 | 499.47 | 0.00 | 0.00 |
Maximum of Months | 2778.77 | 1187.69 | 1619.69 | 1070.58 | 613.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 513.19 | 815.07 | 415.57 | 161.72 | 253.85 | 0.00 | 0.00 |
February | 689.96 | 635.52 | 475.21 | 175.13 | 300.08 | 0.00 | 0.00 |
March | 1096.02 | 374.69 | 616.23 | 246.33 | 369.90 | 0.00 | 0.00 |
April | 1645.12 | 133.99 | 749.02 | 351.26 | 397.76 | 0.00 | 0.00 |
May | 1813.93 | 25.01 | 709.25 | 300.85 | 408.40 | 0.00 | 0.00 |
June | 1803.45 | 19.01 | 666.18 | 258.76 | 407.42 | 0.00 | 0.00 |
July | 1341.71 | 5.08 | 494.34 | 96.15 | 398.19 | 0.00 | 0.00 |
August | 1149.95 | 17.88 | 454.00 | 80.69 | 373.31 | 0.00 | 0.00 |
September | 1098.85 | 71.89 | 499.06 | 146.51 | 352.55 | 0.00 | 0.00 |
October | 1032.61 | 321.67 | 519.45 | 206.84 | 312.61 | 0.00 | 0.00 |
November | 774.25 | 601.95 | 469.93 | 200.28 | 269.65 | 0.00 | 0.00 |
December | 503.76 | 813.70 | 402.12 | 153.34 | 248.78 | 0.00 | 0.00 |
Annual Sum or Average | 1123.17 | 318.26 | 539.10 | 197.89 | 341.21 | 0.00 | 0.00 |
Minimum of Months | 503.76 | 5.08 | 402.12 | 80.69 | 248.78 | 0.00 | 0.00 |
Maximum of Months | 1813.93 | 815.07 | 749.02 | 351.26 | 408.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.21 | 1175.51 | 297.43 | 0.00 | 297.43 | 0.00 | 0.00 |
February | 364.22 | 933.41 | 352.70 | 0.00 | 352.70 | 0.00 | 0.00 |
March | 695.41 | 555.86 | 425.01 | 0.00 | 425.01 | 0.00 | 0.00 |
April | 1215.62 | 196.00 | 461.17 | 1.56 | 459.61 | 0.00 | 0.00 |
May | 1690.82 | 35.04 | 510.94 | 14.34 | 496.61 | 0.00 | 0.00 |
June | 1838.99 | 25.47 | 528.91 | 19.59 | 509.32 | 0.00 | 0.00 |
July | 1630.61 | 5.46 | 521.63 | 8.26 | 513.36 | 0.00 | 0.00 |
August | 1373.65 | 18.84 | 478.87 | 1.49 | 477.37 | 0.00 | 0.00 |
September | 1066.98 | 80.38 | 426.68 | 0.03 | 426.65 | 0.00 | 0.00 |
October | 774.47 | 435.30 | 369.65 | 0.00 | 369.65 | 0.00 | 0.00 |
November | 420.25 | 840.93 | 313.09 | 0.00 | 313.09 | 0.00 | 0.00 |
December | 211.09 | 1163.76 | 290.15 | 0.00 | 290.15 | 0.00 | 0.00 |
Annual Sum or Average | 959.44 | 453.43 | 415.00 | 3.79 | 411.21 | 0.00 | 0.00 |
Minimum of Months | 196.21 | 5.46 | 290.15 | 0.00 | 290.15 | 0.00 | 0.00 |
Maximum of Months | 1838.99 | 1175.51 | 528.91 | 19.59 | 513.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 462.01 | 723.49 | 424.77 | 170.50 | 254.28 | 0.00 | 0.00 |
February | 698.95 | 584.54 | 516.05 | 213.05 | 303.00 | 0.00 | 0.00 |
March | 1075.94 | 354.94 | 629.52 | 259.84 | 369.68 | 0.00 | 0.00 |
April | 1620.09 | 132.16 | 748.97 | 349.21 | 399.76 | 0.00 | 0.00 |
May | 1851.69 | 23.65 | 737.19 | 326.83 | 410.36 | 0.00 | 0.00 |
June | 1678.69 | 17.47 | 599.98 | 199.07 | 400.90 | 0.00 | 0.00 |
July | 1373.52 | 3.38 | 504.26 | 106.49 | 397.78 | 0.00 | 0.00 |
August | 1160.65 | 13.03 | 454.36 | 79.07 | 375.29 | 0.00 | 0.00 |
September | 1078.42 | 54.87 | 485.44 | 135.38 | 350.06 | 0.00 | 0.00 |
October | 1036.91 | 284.13 | 531.01 | 214.49 | 316.52 | 0.00 | 0.00 |
November | 730.91 | 531.30 | 470.82 | 202.10 | 268.72 | 0.00 | 0.00 |
December | 478.49 | 729.73 | 410.53 | 162.66 | 247.88 | 0.00 | 0.00 |
Annual Sum or Average | 1105.29 | 286.42 | 542.59 | 201.24 | 341.35 | 0.00 | 0.00 |
Minimum of Months | 462.01 | 3.38 | 410.53 | 79.07 | 247.88 | 0.00 | 0.00 |
Maximum of Months | 1851.69 | 729.73 | 748.97 | 349.21 | 410.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1961.34 | 1116.46 | 1352.72 | 821.95 | 530.77 | 0.00 | 0.00 |
February | 2026.29 | 918.08 | 1286.24 | 714.41 | 571.83 | 0.00 | 0.00 |
March | 2040.37 | 567.20 | 1099.77 | 485.76 | 614.01 | 0.00 | 0.00 |
April | 1934.03 | 207.63 | 772.48 | 218.02 | 554.46 | 0.00 | 0.00 |
May | 1811.16 | 34.10 | 555.52 | 41.12 | 514.39 | 0.00 | 0.00 |
June | 1797.21 | 25.26 | 508.15 | 8.67 | 499.48 | 0.00 | 0.00 |
July | 1656.69 | 4.95 | 530.05 | 7.29 | 522.76 | 0.00 | 0.00 |
August | 1555.27 | 19.25 | 562.27 | 30.03 | 532.24 | 0.00 | 0.00 |
September | 1736.24 | 85.40 | 753.77 | 195.64 | 558.13 | 0.00 | 0.00 |
October | 2557.06 | 451.51 | 1296.79 | 724.12 | 572.67 | 0.00 | 0.00 |
November | 2779.20 | 842.49 | 1619.76 | 1070.62 | 549.13 | 0.00 | 0.00 |
December | 2171.92 | 1120.34 | 1445.59 | 905.85 | 539.74 | 0.00 | 0.00 |
Annual Sum or Average | 2001.38 | 447.28 | 980.17 | 433.68 | 546.50 | 0.00 | 0.00 |
Minimum of Months | 1555.27 | 4.95 | 508.15 | 7.29 | 499.48 | 0.00 | 0.00 |
Maximum of Months | 2779.20 | 1120.34 | 1619.76 | 1070.62 | 614.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 513.47 | 784.08 | 415.57 | 161.73 | 253.85 | 0.00 | 0.00 |
February | 681.36 | 631.07 | 475.22 | 175.13 | 300.09 | 0.00 | 0.00 |
March | 1081.65 | 383.74 | 616.24 | 246.33 | 369.91 | 0.00 | 0.00 |
April | 1631.24 | 142.13 | 749.03 | 351.27 | 397.76 | 0.00 | 0.00 |
May | 1808.76 | 26.94 | 709.26 | 300.85 | 408.41 | 0.00 | 0.00 |
June | 1805.77 | 18.82 | 666.19 | 258.76 | 407.42 | 0.00 | 0.00 |
July | 1351.50 | 3.92 | 494.34 | 96.15 | 398.19 | 0.00 | 0.00 |
August | 1165.21 | 13.41 | 454.00 | 80.69 | 373.31 | 0.00 | 0.00 |
September | 1109.84 | 58.64 | 499.07 | 146.51 | 352.56 | 0.00 | 0.00 |
October | 1038.24 | 301.57 | 519.45 | 206.85 | 312.61 | 0.00 | 0.00 |
November | 778.45 | 571.87 | 469.93 | 200.28 | 269.65 | 0.00 | 0.00 |
December | 510.43 | 771.38 | 402.12 | 153.34 | 248.78 | 0.00 | 0.00 |
Annual Sum or Average | 1124.34 | 307.54 | 539.11 | 197.90 | 341.21 | 0.00 | 0.00 |
Minimum of Months | 510.43 | 3.92 | 402.12 | 80.69 | 248.78 | 0.00 | 0.00 |
Maximum of Months | 1808.76 | 784.08 | 749.03 | 351.27 | 408.41 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.577319E+09 | 0.288380E+10 | 0.796644E+09 | 0.00 | 0.796644E+09 | 0.00 | 0.00 |
February | 0.914239E+09 | 0.209644E+10 | 0.853263E+09 | 0.00 | 0.853263E+09 | 0.00 | 0.00 |
March | 0.186000E+10 | 0.141159E+10 | 0.113835E+10 | 0.00 | 0.113835E+10 | 0.00 | 0.00 |
April | 0.311510E+10 | 0.491759E+09 | 0.119535E+10 | 4053850.16 | 0.119130E+10 | 0.00 | 0.00 |
May | 0.447661E+10 | 96317594.73 | 0.136851E+10 | 38403034.35 | 0.133011E+10 | 0.00 | 0.00 |
June | 0.471256E+10 | 67981965.92 | 0.137093E+10 | 50779577.42 | 0.132015E+10 | 0.00 | 0.00 |
July | 0.431103E+10 | 14661210.01 | 0.139712E+10 | 22124250.60 | 0.137500E+10 | 0.00 | 0.00 |
August | 0.363382E+10 | 50419704.73 | 0.128260E+10 | 3997280.29 | 0.127860E+10 | 0.00 | 0.00 |
September | 0.273979E+10 | 0.202699E+09 | 0.110596E+10 | 77658.52 | 0.110589E+10 | 0.00 | 0.00 |
October | 0.206520E+10 | 0.110585E+10 | 0.990061E+09 | 0.00 | 0.990061E+09 | 0.00 | 0.00 |
November | 0.111978E+10 | 0.202514E+10 | 0.811540E+09 | 0.00 | 0.811540E+09 | 0.00 | 0.00 |
December | 0.628788E+09 | 0.285091E+10 | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.301542E+11 | 0.132976E+11 | 0.130875E+11 | 0.119436E+09 | 0.129680E+11 | 0.00 | 0.00 |
Minimum of Months | 0.577319E+09 | 14661210.01 | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.00 | 0.00 |
Maximum of Months | 0.471256E+10 | 0.288380E+10 | 0.139712E+10 | 50779577.42 | 0.137500E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130395E+10 | 0.178441E+10 | 0.113771E+10 | 0.456663E+09 | 0.681052E+09 | 0.00 | 0.00 |
February | 0.172853E+10 | 0.132430E+10 | 0.124842E+10 | 0.515406E+09 | 0.733014E+09 | 0.00 | 0.00 |
March | 0.289247E+10 | 0.908361E+09 | 0.168611E+10 | 0.695968E+09 | 0.990144E+09 | 0.00 | 0.00 |
April | 0.418492E+10 | 0.332260E+09 | 0.194133E+10 | 0.905146E+09 | 0.103618E+10 | 0.00 | 0.00 |
May | 0.493421E+10 | 64414735.78 | 0.197449E+10 | 0.875382E+09 | 0.109911E+10 | 0.00 | 0.00 |
June | 0.432621E+10 | 46313925.60 | 0.155514E+10 | 0.515994E+09 | 0.103914E+10 | 0.00 | 0.00 |
July | 0.365320E+10 | 8837273.19 | 0.135062E+10 | 0.285215E+09 | 0.106541E+10 | 0.00 | 0.00 |
August | 0.309039E+10 | 34645750.09 | 0.121697E+10 | 0.211781E+09 | 0.100519E+10 | 0.00 | 0.00 |
September | 0.278777E+10 | 0.137949E+09 | 0.125825E+10 | 0.350894E+09 | 0.907354E+09 | 0.00 | 0.00 |
October | 0.278312E+10 | 0.725434E+09 | 0.142225E+10 | 0.574497E+09 | 0.847758E+09 | 0.00 | 0.00 |
November | 0.192940E+10 | 0.129201E+10 | 0.122036E+10 | 0.523832E+09 | 0.696524E+09 | 0.00 | 0.00 |
December | 0.134879E+10 | 0.180391E+10 | 0.109957E+10 | 0.435656E+09 | 0.663914E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.349630E+11 | 0.846285E+10 | 0.171112E+11 | 0.634643E+10 | 0.107648E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130395E+10 | 8837273.19 | 0.109957E+10 | 0.211781E+09 | 0.663914E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493421E+10 | 0.180391E+10 | 0.197449E+10 | 0.905146E+09 | 0.109911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.531805E+10 | 0.276234E+10 | 0.362313E+10 | 0.220151E+10 | 0.142162E+10 | 0.00 | 0.00 |
February | 0.493229E+10 | 0.208091E+10 | 0.311167E+10 | 0.172831E+10 | 0.138336E+10 | 0.00 | 0.00 |
March | 0.545707E+10 | 0.144867E+10 | 0.294562E+10 | 0.130105E+10 | 0.164456E+10 | 0.00 | 0.00 |
April | 0.497401E+10 | 0.521740E+09 | 0.200227E+10 | 0.565102E+09 | 0.143717E+10 | 0.00 | 0.00 |
May | 0.479801E+10 | 93321669.55 | 0.148789E+10 | 0.110144E+09 | 0.137775E+10 | 0.00 | 0.00 |
June | 0.460388E+10 | 67805527.45 | 0.131713E+10 | 22476516.34 | 0.129466E+10 | 0.00 | 0.00 |
July | 0.438054E+10 | 13074866.59 | 0.141969E+10 | 19526701.18 | 0.140017E+10 | 0.00 | 0.00 |
August | 0.411957E+10 | 51660293.48 | 0.150599E+10 | 80431361.38 | 0.142556E+10 | 0.00 | 0.00 |
September | 0.447070E+10 | 0.216057E+09 | 0.195378E+10 | 0.507107E+09 | 0.144667E+10 | 0.00 | 0.00 |
October | 0.683807E+10 | 0.115361E+10 | 0.347332E+10 | 0.193949E+10 | 0.153383E+10 | 0.00 | 0.00 |
November | 0.722586E+10 | 0.205257E+10 | 0.419841E+10 | 0.277506E+10 | 0.142335E+10 | 0.00 | 0.00 |
December | 0.588758E+10 | 0.278119E+10 | 0.387187E+10 | 0.242622E+10 | 0.144565E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.630056E+11 | 0.132429E+11 | 0.309108E+11 | 0.136764E+11 | 0.172343E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411957E+10 | 13074866.59 | 0.131713E+10 | 19526701.18 | 0.129466E+10 | 0.00 | 0.00 |
Maximum of Months | 0.722586E+10 | 0.278119E+10 | 0.419841E+10 | 0.277506E+10 | 0.164456E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140670E+10 | 0.192891E+10 | 0.111307E+10 | 0.433165E+09 | 0.679906E+09 | 0.00 | 0.00 |
February | 0.166606E+10 | 0.142109E+10 | 0.114965E+10 | 0.423677E+09 | 0.725972E+09 | 0.00 | 0.00 |
March | 0.289165E+10 | 0.976790E+09 | 0.165053E+10 | 0.659775E+09 | 0.990756E+09 | 0.00 | 0.00 |
April | 0.420228E+10 | 0.356816E+09 | 0.194149E+10 | 0.910484E+09 | 0.103100E+10 | 0.00 | 0.00 |
May | 0.480939E+10 | 73627066.49 | 0.189969E+10 | 0.805809E+09 | 0.109388E+10 | 0.00 | 0.00 |
June | 0.464381E+10 | 49854274.98 | 0.172675E+10 | 0.670718E+09 | 0.105604E+10 | 0.00 | 0.00 |
July | 0.358275E+10 | 10674333.46 | 0.132405E+10 | 0.257529E+09 | 0.106652E+10 | 0.00 | 0.00 |
August | 0.309077E+10 | 36109865.70 | 0.121600E+10 | 0.216121E+09 | 0.999882E+09 | 0.00 | 0.00 |
September | 0.285844E+10 | 0.148453E+09 | 0.129359E+10 | 0.379760E+09 | 0.913827E+09 | 0.00 | 0.00 |
October | 0.277391E+10 | 0.767995E+09 | 0.139131E+10 | 0.554016E+09 | 0.837290E+09 | 0.00 | 0.00 |
November | 0.203378E+10 | 0.138204E+10 | 0.121806E+10 | 0.519131E+09 | 0.698932E+09 | 0.00 | 0.00 |
December | 0.140718E+10 | 0.189639E+10 | 0.107705E+10 | 0.410703E+09 | 0.666345E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.353667E+11 | 0.904874E+10 | 0.170012E+11 | 0.624089E+10 | 0.107604E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140670E+10 | 10674333.46 | 0.107705E+10 | 0.216121E+09 | 0.666345E+09 | 0.00 | 0.00 |
Maximum of Months | 0.480939E+10 | 0.192891E+10 | 0.194149E+10 | 0.910484E+09 | 0.109388E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.522907E+09 | 0.321699E+10 | 0.796627E+09 | 0.00 | 0.796627E+09 | 0.00 | 0.00 |
February | 0.912275E+09 | 0.222012E+10 | 0.853246E+09 | 0.00 | 0.853246E+09 | 0.00 | 0.00 |
March | 0.192080E+10 | 0.140421E+10 | 0.113833E+10 | 0.00 | 0.113833E+10 | 0.00 | 0.00 |
April | 0.321812E+10 | 0.445570E+09 | 0.119533E+10 | 4053731.01 | 0.119128E+10 | 0.00 | 0.00 |
May | 0.457476E+10 | 74917845.28 | 0.136849E+10 | 38401905.58 | 0.133009E+10 | 0.00 | 0.00 |
June | 0.477507E+10 | 60940344.96 | 0.137090E+10 | 50778084.87 | 0.132013E+10 | 0.00 | 0.00 |
July | 0.433696E+10 | 17731676.03 | 0.139709E+10 | 22123600.30 | 0.137497E+10 | 0.00 | 0.00 |
August | 0.362425E+10 | 64489319.31 | 0.128257E+10 | 3997162.80 | 0.127857E+10 | 0.00 | 0.00 |
September | 0.272000E+10 | 0.243162E+09 | 0.110594E+10 | 77656.24 | 0.110586E+10 | 0.00 | 0.00 |
October | 0.204881E+10 | 0.121183E+10 | 0.990041E+09 | 0.00 | 0.990041E+09 | 0.00 | 0.00 |
November | 0.106932E+10 | 0.225611E+10 | 0.811524E+09 | 0.00 | 0.811524E+09 | 0.00 | 0.00 |
December | 0.541265E+09 | 0.324057E+10 | 0.777124E+09 | 0.00 | 0.777124E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.302645E+11 | 0.144566E+11 | 0.130872E+11 | 0.119432E+09 | 0.129678E+11 | 0.00 | 0.00 |
Minimum of Months | 0.522907E+09 | 17731676.03 | 0.777124E+09 | 0.00 | 0.777124E+09 | 0.00 | 0.00 |
Maximum of Months | 0.477507E+10 | 0.324057E+10 | 0.139709E+10 | 50778084.87 | 0.137497E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123646E+10 | 0.201550E+10 | 0.113770E+10 | 0.456654E+09 | 0.681043E+09 | 0.00 | 0.00 |
February | 0.171713E+10 | 0.142626E+10 | 0.124840E+10 | 0.515396E+09 | 0.733004E+09 | 0.00 | 0.00 |
March | 0.293129E+10 | 0.927288E+09 | 0.168609E+10 | 0.695955E+09 | 0.990132E+09 | 0.00 | 0.00 |
April | 0.424836E+10 | 0.319874E+09 | 0.194130E+10 | 0.905128E+09 | 0.103617E+10 | 0.00 | 0.00 |
May | 0.499159E+10 | 57203582.54 | 0.197446E+10 | 0.875365E+09 | 0.109910E+10 | 0.00 | 0.00 |
June | 0.436345E+10 | 44276872.18 | 0.155512E+10 | 0.515984E+09 | 0.103913E+10 | 0.00 | 0.00 |
July | 0.366288E+10 | 11618334.68 | 0.135060E+10 | 0.285210E+09 | 0.106539E+10 | 0.00 | 0.00 |
August | 0.308143E+10 | 46305704.86 | 0.121695E+10 | 0.211777E+09 | 0.100517E+10 | 0.00 | 0.00 |
September | 0.277691E+10 | 0.172999E+09 | 0.125823E+10 | 0.350887E+09 | 0.907342E+09 | 0.00 | 0.00 |
October | 0.277159E+10 | 0.809931E+09 | 0.142223E+10 | 0.574486E+09 | 0.847747E+09 | 0.00 | 0.00 |
November | 0.188876E+10 | 0.144685E+10 | 0.122034E+10 | 0.523822E+09 | 0.696516E+09 | 0.00 | 0.00 |
December | 0.126557E+10 | 0.205857E+10 | 0.109955E+10 | 0.435647E+09 | 0.663905E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.349354E+11 | 0.933667E+10 | 0.171110E+11 | 0.634631E+10 | 0.107647E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123646E+10 | 11618334.68 | 0.109955E+10 | 0.211777E+09 | 0.663905E+09 | 0.00 | 0.00 |
Maximum of Months | 0.499159E+10 | 0.205857E+10 | 0.197446E+10 | 0.905128E+09 | 0.109910E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.529602E+10 | 0.312789E+10 | 0.362299E+10 | 0.220141E+10 | 0.142157E+10 | 0.00 | 0.00 |
February | 0.495560E+10 | 0.226262E+10 | 0.311156E+10 | 0.172824E+10 | 0.138332E+10 | 0.00 | 0.00 |
March | 0.552242E+10 | 0.149477E+10 | 0.294551E+10 | 0.130100E+10 | 0.164451E+10 | 0.00 | 0.00 |
April | 0.503700E+10 | 0.500185E+09 | 0.200220E+10 | 0.565078E+09 | 0.143713E+10 | 0.00 | 0.00 |
May | 0.482211E+10 | 79269684.11 | 0.148785E+10 | 0.110140E+09 | 0.137771E+10 | 0.00 | 0.00 |
June | 0.459530E+10 | 62351117.45 | 0.131710E+10 | 22475583.63 | 0.129462E+10 | 0.00 | 0.00 |
July | 0.436195E+10 | 17244381.27 | 0.141965E+10 | 19525890.87 | 0.140012E+10 | 0.00 | 0.00 |
August | 0.407566E+10 | 68982989.93 | 0.150594E+10 | 80428023.69 | 0.142551E+10 | 0.00 | 0.00 |
September | 0.442818E+10 | 0.279056E+09 | 0.195371E+10 | 0.507086E+09 | 0.144662E+10 | 0.00 | 0.00 |
October | 0.679923E+10 | 0.132486E+10 | 0.347319E+10 | 0.193940E+10 | 0.153378E+10 | 0.00 | 0.00 |
November | 0.720257E+10 | 0.234088E+10 | 0.419825E+10 | 0.277494E+10 | 0.142330E+10 | 0.00 | 0.00 |
December | 0.582288E+10 | 0.318110E+10 | 0.387172E+10 | 0.242612E+10 | 0.144560E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.629189E+11 | 0.147392E+11 | 0.309097E+11 | 0.136759E+11 | 0.172338E+11 | 0.00 | 0.00 |
Minimum of Months | 0.407566E+10 | 17244381.27 | 0.131710E+10 | 19525890.87 | 0.129462E+10 | 0.00 | 0.00 |
Maximum of Months | 0.720257E+10 | 0.318110E+10 | 0.419825E+10 | 0.277494E+10 | 0.164451E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137454E+10 | 0.218307E+10 | 0.111306E+10 | 0.433158E+09 | 0.679899E+09 | 0.00 | 0.00 |
February | 0.166916E+10 | 0.153745E+10 | 0.114963E+10 | 0.423670E+09 | 0.725965E+09 | 0.00 | 0.00 |
March | 0.293559E+10 | 0.100357E+10 | 0.165051E+10 | 0.659765E+09 | 0.990746E+09 | 0.00 | 0.00 |
April | 0.426414E+10 | 0.347297E+09 | 0.194146E+10 | 0.910469E+09 | 0.103099E+10 | 0.00 | 0.00 |
May | 0.485844E+10 | 66993778.22 | 0.189966E+10 | 0.805795E+09 | 0.109387E+10 | 0.00 | 0.00 |
June | 0.467455E+10 | 49274456.69 | 0.172673E+10 | 0.670707E+09 | 0.105603E+10 | 0.00 | 0.00 |
July | 0.359363E+10 | 13596189.22 | 0.132404E+10 | 0.257524E+09 | 0.106651E+10 | 0.00 | 0.00 |
August | 0.308003E+10 | 47897631.77 | 0.121599E+10 | 0.216117E+09 | 0.999871E+09 | 0.00 | 0.00 |
September | 0.284822E+10 | 0.186346E+09 | 0.129357E+10 | 0.379754E+09 | 0.913816E+09 | 0.00 | 0.00 |
October | 0.276573E+10 | 0.861554E+09 | 0.139129E+10 | 0.554007E+09 | 0.837282E+09 | 0.00 | 0.00 |
November | 0.200686E+10 | 0.156025E+10 | 0.121805E+10 | 0.519123E+09 | 0.698925E+09 | 0.00 | 0.00 |
December | 0.134928E+10 | 0.217942E+10 | 0.107703E+10 | 0.410696E+09 | 0.666338E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.354202E+11 | 0.100367E+11 | 0.170010E+11 | 0.624078E+10 | 0.107602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.134928E+10 | 13596189.22 | 0.107703E+10 | 0.216117E+09 | 0.666338E+09 | 0.00 | 0.00 |
Maximum of Months | 0.485844E+10 | 0.218307E+10 | 0.194146E+10 | 0.910469E+09 | 0.109387E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525524E+09 | 0.314850E+10 | 0.796644E+09 | 0.00 | 0.796644E+09 | 0.00 | 0.00 |
February | 0.881126E+09 | 0.225810E+10 | 0.853263E+09 | 0.00 | 0.853263E+09 | 0.00 | 0.00 |
March | 0.186259E+10 | 0.148882E+10 | 0.113835E+10 | 0.00 | 0.113835E+10 | 0.00 | 0.00 |
April | 0.315090E+10 | 0.508028E+09 | 0.119535E+10 | 4053850.16 | 0.119130E+10 | 0.00 | 0.00 |
May | 0.452869E+10 | 93858409.50 | 0.136851E+10 | 38403034.35 | 0.133011E+10 | 0.00 | 0.00 |
June | 0.476666E+10 | 66012141.48 | 0.137093E+10 | 50779577.42 | 0.132015E+10 | 0.00 | 0.00 |
July | 0.436743E+10 | 14628265.68 | 0.139712E+10 | 22124250.60 | 0.137500E+10 | 0.00 | 0.00 |
August | 0.367918E+10 | 50466426.59 | 0.128260E+10 | 3997280.29 | 0.127860E+10 | 0.00 | 0.00 |
September | 0.276562E+10 | 0.208334E+09 | 0.110596E+10 | 77658.52 | 0.110589E+10 | 0.00 | 0.00 |
October | 0.207434E+10 | 0.116592E+10 | 0.990061E+09 | 0.00 | 0.990061E+09 | 0.00 | 0.00 |
November | 0.108930E+10 | 0.217968E+10 | 0.811540E+09 | 0.00 | 0.811540E+09 | 0.00 | 0.00 |
December | 0.565386E+09 | 0.311702E+10 | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.302567E+11 | 0.142994E+11 | 0.130875E+11 | 0.119436E+09 | 0.129680E+11 | 0.00 | 0.00 |
Minimum of Months | 0.525524E+09 | 14628265.68 | 0.777140E+09 | 0.00 | 0.777140E+09 | 0.00 | 0.00 |
Maximum of Months | 0.476666E+10 | 0.314850E+10 | 0.139712E+10 | 50779577.42 | 0.137500E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123744E+10 | 0.193778E+10 | 0.113771E+10 | 0.456663E+09 | 0.681052E+09 | 0.00 | 0.00 |
February | 0.169090E+10 | 0.141411E+10 | 0.124842E+10 | 0.515406E+09 | 0.733014E+09 | 0.00 | 0.00 |
March | 0.288179E+10 | 0.950683E+09 | 0.168611E+10 | 0.695968E+09 | 0.990144E+09 | 0.00 | 0.00 |
April | 0.419927E+10 | 0.342570E+09 | 0.194133E+10 | 0.905146E+09 | 0.103618E+10 | 0.00 | 0.00 |
May | 0.495957E+10 | 63348377.36 | 0.197449E+10 | 0.875382E+09 | 0.109911E+10 | 0.00 | 0.00 |
June | 0.435117E+10 | 45276803.82 | 0.155514E+10 | 0.515994E+09 | 0.103914E+10 | 0.00 | 0.00 |
July | 0.367884E+10 | 9050466.13 | 0.135062E+10 | 0.285215E+09 | 0.106541E+10 | 0.00 | 0.00 |
August | 0.310869E+10 | 34901336.90 | 0.121697E+10 | 0.211781E+09 | 0.100519E+10 | 0.00 | 0.00 |
September | 0.279525E+10 | 0.142233E+09 | 0.125825E+10 | 0.350894E+09 | 0.907354E+09 | 0.00 | 0.00 |
October | 0.277726E+10 | 0.761014E+09 | 0.142225E+10 | 0.574497E+09 | 0.847758E+09 | 0.00 | 0.00 |
November | 0.189452E+10 | 0.137714E+10 | 0.122036E+10 | 0.523832E+09 | 0.696524E+09 | 0.00 | 0.00 |
December | 0.128159E+10 | 0.195451E+10 | 0.109957E+10 | 0.435656E+09 | 0.663914E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348563E+11 | 0.903262E+10 | 0.171112E+11 | 0.634643E+10 | 0.107648E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123744E+10 | 9050466.13 | 0.109957E+10 | 0.211781E+09 | 0.663914E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495957E+10 | 0.195451E+10 | 0.197449E+10 | 0.905146E+09 | 0.109911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525325E+10 | 0.299032E+10 | 0.362313E+10 | 0.220151E+10 | 0.142162E+10 | 0.00 | 0.00 |
February | 0.490200E+10 | 0.222101E+10 | 0.311167E+10 | 0.172831E+10 | 0.138336E+10 | 0.00 | 0.00 |
March | 0.546493E+10 | 0.151919E+10 | 0.294562E+10 | 0.130105E+10 | 0.164456E+10 | 0.00 | 0.00 |
April | 0.501300E+10 | 0.538185E+09 | 0.200227E+10 | 0.565102E+09 | 0.143717E+10 | 0.00 | 0.00 |
May | 0.485102E+10 | 91338258.98 | 0.148789E+10 | 0.110144E+09 | 0.137775E+10 | 0.00 | 0.00 |
June | 0.465836E+10 | 65470664.44 | 0.131713E+10 | 22476516.34 | 0.129466E+10 | 0.00 | 0.00 |
July | 0.443727E+10 | 13261223.64 | 0.141969E+10 | 19526701.18 | 0.140017E+10 | 0.00 | 0.00 |
August | 0.416564E+10 | 51560939.43 | 0.150599E+10 | 80431361.38 | 0.142556E+10 | 0.00 | 0.00 |
September | 0.450033E+10 | 0.221356E+09 | 0.195378E+10 | 0.507107E+09 | 0.144667E+10 | 0.00 | 0.00 |
October | 0.684882E+10 | 0.120932E+10 | 0.347332E+10 | 0.193949E+10 | 0.153383E+10 | 0.00 | 0.00 |
November | 0.720368E+10 | 0.218375E+10 | 0.419841E+10 | 0.277506E+10 | 0.142335E+10 | 0.00 | 0.00 |
December | 0.581726E+10 | 0.300072E+10 | 0.387187E+10 | 0.242622E+10 | 0.144565E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631156E+11 | 0.141055E+11 | 0.309108E+11 | 0.136764E+11 | 0.172343E+11 | 0.00 | 0.00 |
Minimum of Months | 0.416564E+10 | 13261223.64 | 0.131713E+10 | 19526701.18 | 0.129466E+10 | 0.00 | 0.00 |
Maximum of Months | 0.720368E+10 | 0.300072E+10 | 0.419841E+10 | 0.277506E+10 | 0.164456E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137527E+10 | 0.210007E+10 | 0.111307E+10 | 0.433165E+09 | 0.679906E+09 | 0.00 | 0.00 |
February | 0.164834E+10 | 0.152669E+10 | 0.114965E+10 | 0.423677E+09 | 0.725972E+09 | 0.00 | 0.00 |
March | 0.289709E+10 | 0.102781E+10 | 0.165053E+10 | 0.659775E+09 | 0.990756E+09 | 0.00 | 0.00 |
April | 0.422818E+10 | 0.368394E+09 | 0.194149E+10 | 0.910484E+09 | 0.103100E+10 | 0.00 | 0.00 |
May | 0.484459E+10 | 72166660.18 | 0.189969E+10 | 0.805809E+09 | 0.109388E+10 | 0.00 | 0.00 |
June | 0.468056E+10 | 48784083.18 | 0.172675E+10 | 0.670718E+09 | 0.105604E+10 | 0.00 | 0.00 |
July | 0.361984E+10 | 10499628.00 | 0.132405E+10 | 0.257529E+09 | 0.106652E+10 | 0.00 | 0.00 |
August | 0.312089E+10 | 35921171.66 | 0.121600E+10 | 0.216121E+09 | 0.999882E+09 | 0.00 | 0.00 |
September | 0.287670E+10 | 0.152005E+09 | 0.129359E+10 | 0.379760E+09 | 0.913827E+09 | 0.00 | 0.00 |
October | 0.278082E+10 | 0.807726E+09 | 0.139131E+10 | 0.554016E+09 | 0.837290E+09 | 0.00 | 0.00 |
November | 0.201774E+10 | 0.148229E+10 | 0.121806E+10 | 0.519131E+09 | 0.698932E+09 | 0.00 | 0.00 |
December | 0.136713E+10 | 0.206607E+10 | 0.107705E+10 | 0.410703E+09 | 0.666345E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.354571E+11 | 0.969843E+10 | 0.170012E+11 | 0.624089E+10 | 0.107604E+11 | 0.00 | 0.00 |
Minimum of Months | 0.136713E+10 | 10499628.00 | 0.107705E+10 | 0.216121E+09 | 0.666345E+09 | 0.00 | 0.00 |
Maximum of Months | 0.484459E+10 | 0.210007E+10 | 0.194149E+10 | 0.910484E+09 | 0.109388E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.429902E+10 | -0.359429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -704738060.0 | 58.98 | 0.00 | 0.00 |
February | 0.382663E+10 | -0.319780E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -628828549.6 | 58.98 | 0.00 | 0.00 |
March | 0.422302E+10 | -0.353023E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692787915.1 | 58.98 | 0.00 | 0.00 |
April | 0.351875E+10 | -0.285122E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667523435.9 | 58.98 | 0.00 | 0.00 |
May | 0.339405E+10 | -0.270307E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690983345.7 | 58.98 | 0.00 | 0.00 |
June | 0.307643E+10 | -0.240620E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670226447.8 | 58.98 | 0.00 | 0.00 |
July | 0.285354E+10 | -0.216167E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691865480.3 | 58.98 | 0.00 | 0.00 |
August | 0.316751E+10 | -0.247622E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691289115.6 | 58.97 | 0.00 | 0.00 |
September | 0.313540E+10 | -0.246826E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667140140.0 | 58.98 | 0.00 | 0.00 |
October | 0.357593E+10 | -0.288671E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689214802.0 | 58.98 | 0.00 | 0.00 |
November | 0.384561E+10 | -0.317625E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669359807.9 | 58.98 | 0.00 | 0.00 |
December | 0.409216E+10 | -0.339441E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -697750224.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.430080E+11 | -0.348463E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.816171E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.285354E+10 | -0.359429E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -704738060.0 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.429902E+10 | -0.216167E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -628828549.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5571.56 | 35.12 | 297.67 | 287.00 | 1260.39 | 24.90 | 235.67 | 266.33 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3339.98 | 28.51 | 197.00 | 271.00 | 1112.88 | 20.75 | 155.67 | 244.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1716.45 | 18.81 | 7.50 | 322.33 | 948.47 | 20.67 | 158.00 | 291.00 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1149.07 | 17.30 | 0.00 | 328.17 | 687.92 | 19.41 | 83.83 | 295.17 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 966.49 | 17.07 | 0.00 | 348.50 | 571.39 | 19.28 | 38.83 | 308.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-07:30 | 956.99 | 16.73 | 0.00 | 332.50 | 552.04 | 18.89 | 37.17 | 290.50 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:00 | 1080.94 | 17.16 | 0.00 | 331.67 | 566.93 | 19.23 | 38.50 | 280.00 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1220.21 | 17.16 | 0.00 | 320.50 | 619.07 | 19.20 | 85.50 | 270.67 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 1493.07 | 17.89 | 0.00 | 301.83 | 784.60 | 20.01 | 143.00 | 262.17 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2557.57 | 19.98 | 42.67 | 307.33 | 1074.09 | 20.49 | 150.33 | 279.67 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 7542.80 | 36.36 | 310.50 | 287.17 | 1328.88 | 24.23 | 202.67 | 270.83 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5884.84 | 36.46 | 308.83 | 286.00 | 1481.78 | 27.14 | 259.50 | 278.83 |
Annual Sum or Average | 4237.50 | 0.52 | 2628.93 | 22.60 | 1164.17 | 3724.00 | 890.17 | 21.01 | 1588.67 | 3338.00 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 956.99 | 16.73 | 0.00 | 271.00 | 552.04 | 18.89 | 37.17 | 244.17 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 7542.80 | 36.46 | 310.50 | 348.50 | 1481.78 | 27.14 | 259.50 | 308.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1622.34 | 21.88 | 106.83 | 265.83 | 865.74 | 22.60 | 77.33 | 219.50 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2015.78 | 21.88 | 100.17 | 256.33 | 1072.96 | 22.68 | 74.00 | 216.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 1910.84 | 19.84 | 88.17 | 316.00 | 1009.60 | 22.06 | 70.67 | 284.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2352.44 | 20.61 | 110.33 | 326.17 | 1244.80 | 21.59 | 81.17 | 297.50 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2430.14 | 19.95 | 116.50 | 354.17 | 952.48 | 20.56 | 66.50 | 320.50 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 1931.60 | 18.96 | 100.83 | 336.33 | 815.98 | 19.64 | 51.33 | 297.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1598.47 | 19.04 | 96.33 | 335.67 | 720.05 | 19.62 | 46.17 | 283.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1467.02 | 19.00 | 97.67 | 321.00 | 682.14 | 19.19 | 42.17 | 264.67 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1637.32 | 20.08 | 90.00 | 296.67 | 838.09 | 21.19 | 64.50 | 254.67 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-06:49 | 1804.14 | 20.85 | 100.83 | 295.67 | 920.82 | 21.61 | 70.17 | 262.50 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:10 | 1623.48 | 20.59 | 87.83 | 265.17 | 831.09 | 21.35 | 58.33 | 231.50 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-07:30 | 1698.35 | 22.55 | 112.50 | 260.50 | 912.56 | 23.24 | 81.67 | 223.17 |
Annual Sum or Average | 4237.50 | 0.52 | 1852.50 | 20.35 | 1208.00 | 3629.50 | 904.68 | 21.20 | 784.00 | 3155.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1467.02 | 18.96 | 87.83 | 256.33 | 682.14 | 19.19 | 42.17 | 216.17 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2430.14 | 22.55 | 116.50 | 354.17 | 1244.80 | 23.24 | 81.67 | 320.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:20 | 528.94 | 14.78 | 0.00 | 244.67 | 328.45 | 17.13 | 0.00 | 159.33 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-08:50 | 610.20 | 15.68 | 0.00 | 246.83 | 377.37 | 17.96 | 0.00 | 179.83 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:20 | 721.67 | 16.85 | 0.00 | 312.33 | 445.39 | 19.05 | 0.00 | 260.67 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 778.24 | 16.99 | 0.00 | 332.00 | 487.64 | 19.09 | 0.00 | 297.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 930.52 | 17.59 | 1.17 | 365.33 | 550.72 | 19.81 | 73.00 | 336.67 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1032.77 | 18.24 | 18.00 | 347.33 | 585.05 | 21.49 | 135.83 | 313.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1054.41 | 18.91 | 29.17 | 344.17 | 556.67 | 20.92 | 83.50 | 296.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 943.03 | 16.88 | 0.00 | 324.83 | 496.90 | 18.88 | 20.00 | 269.67 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 817.99 | 16.77 | 0.00 | 297.33 | 458.65 | 18.82 | 0.00 | 243.67 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:40 | 638.34 | 15.67 | 0.00 | 287.33 | 403.49 | 17.95 | 0.00 | 232.83 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:20 | 541.87 | 15.16 | 0.00 | 249.83 | 356.06 | 17.66 | 0.00 | 185.50 |
December | 315.50 | 0.55 | 0.48 | 01-DEC-08:50 | 520.91 | 14.86 | 0.00 | 240.83 | 326.67 | 17.28 | 0.00 | 155.17 |
Annual Sum or Average | 4237.50 | 0.53 | 774.47 | 16.63 | 48.33 | 3592.83 | 454.93 | 18.93 | 312.33 | 2930.67 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 520.91 | 14.78 | 0.00 | 240.83 | 326.67 | 17.13 | 0.00 | 155.17 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1054.41 | 18.91 | 29.17 | 365.33 | 585.05 | 21.49 | 135.83 | 336.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:20 | 1625.24 | 21.59 | 104.00 | 265.00 | 852.66 | 22.21 | 74.50 | 219.50 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-09:09 | 1927.96 | 21.52 | 103.50 | 260.50 | 778.92 | 20.69 | 48.00 | 220.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:30 | 1864.15 | 19.72 | 87.67 | 316.50 | 980.07 | 21.90 | 69.33 | 285.00 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:00 | 2147.17 | 18.59 | 84.50 | 330.67 | 1130.66 | 19.73 | 54.67 | 300.00 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:30 | 2064.72 | 13.85 | 0.00 | 350.00 | 1076.14 | 17.20 | 0.00 | 317.50 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2049.71 | 13.93 | 0.00 | 336.50 | 850.59 | 17.08 | 0.00 | 299.67 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:30 | 1550.00 | 14.64 | 3.50 | 334.33 | 710.23 | 17.42 | 0.00 | 284.50 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:49 | 1445.42 | 16.45 | 52.50 | 320.33 | 726.99 | 17.33 | 4.67 | 269.67 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:20 | 1600.61 | 19.11 | 80.33 | 299.33 | 818.07 | 20.17 | 52.33 | 256.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:00 | 1915.94 | 20.90 | 102.67 | 292.17 | 976.14 | 21.84 | 74.17 | 261.00 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1665.15 | 20.18 | 85.00 | 267.50 | 853.57 | 22.22 | 67.17 | 236.00 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:50 | 1461.62 | 20.36 | 87.67 | 265.00 | 773.60 | 22.34 | 70.00 | 228.50 |
Annual Sum or Average | 4237.50 | 0.52 | 1785.21 | 18.18 | 791.33 | 3637.83 | 882.15 | 19.86 | 514.83 | 3178.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1445.42 | 13.85 | 0.00 | 260.50 | 710.23 | 17.08 | 0.00 | 219.50 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2147.17 | 21.59 | 104.00 | 350.00 | 1130.66 | 22.34 | 74.50 | 317.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5454.07 | 34.84 | 297.00 | 286.17 | 1172.89 | 22.42 | 85.17 | 265.00 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3233.77 | 26.92 | 195.33 | 270.33 | 1034.83 | 17.81 | 0.00 | 241.67 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1634.21 | 15.10 | 7.50 | 320.67 | 889.33 | 18.27 | 0.00 | 287.50 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1099.13 | 13.87 | 0.00 | 325.33 | 654.67 | 17.30 | 0.00 | 291.50 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 930.92 | 13.46 | 0.00 | 346.17 | 550.48 | 16.96 | 0.00 | 305.00 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-07:40 | 922.99 | 13.03 | 0.00 | 331.33 | 532.43 | 16.45 | 0.00 | 285.00 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-07:10 | 1041.49 | 13.14 | 0.00 | 329.83 | 542.88 | 16.50 | 0.00 | 274.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1174.06 | 13.12 | 0.00 | 318.83 | 590.22 | 16.41 | 0.00 | 266.00 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 1429.28 | 13.92 | 0.00 | 299.83 | 742.08 | 17.34 | 0.00 | 258.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:19 | 2458.23 | 16.30 | 41.33 | 305.33 | 999.25 | 17.82 | 10.00 | 276.00 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 7412.07 | 35.29 | 301.67 | 283.50 | 1228.50 | 21.68 | 74.33 | 269.50 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:30 | 5748.73 | 35.30 | 298.67 | 284.17 | 1386.63 | 24.95 | 123.33 | 277.67 |
Annual Sum or Average | 4237.50 | 0.52 | 2553.54 | 19.65 | 1141.50 | 3701.50 | 837.23 | 18.49 | 292.83 | 3297.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 922.99 | 13.03 | 0.00 | 270.33 | 532.43 | 16.41 | 0.00 | 241.67 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 7412.07 | 35.30 | 301.67 | 346.17 | 1386.63 | 24.95 | 123.33 | 305.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1536.29 | 19.30 | 85.50 | 260.33 | 831.73 | 22.39 | 77.33 | 215.67 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 1962.93 | 21.42 | 100.00 | 254.33 | 1034.17 | 22.47 | 74.17 | 212.33 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:30 | 1856.52 | 19.35 | 88.17 | 313.50 | 964.30 | 21.87 | 70.67 | 281.50 |
April | 379.83 | 0.53 | 0.48 | 01-APR-06:49 | 2283.60 | 20.18 | 110.33 | 324.17 | 1197.00 | 21.42 | 81.17 | 294.50 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:10 | 2366.08 | 19.50 | 116.50 | 352.83 | 907.21 | 20.40 | 66.50 | 317.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 1884.37 | 18.52 | 100.83 | 335.00 | 779.28 | 19.48 | 51.67 | 293.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1553.74 | 18.59 | 96.33 | 334.67 | 687.51 | 19.45 | 46.17 | 278.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1421.92 | 18.55 | 97.67 | 319.50 | 651.63 | 19.00 | 42.17 | 261.17 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1589.94 | 19.43 | 88.17 | 296.00 | 803.31 | 21.00 | 64.50 | 250.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-06:49 | 1734.04 | 19.03 | 87.00 | 292.50 | 881.50 | 21.42 | 70.17 | 259.17 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-07:10 | 1574.76 | 20.10 | 87.83 | 263.67 | 793.76 | 21.13 | 58.33 | 226.83 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-07:30 | 1655.21 | 22.09 | 112.50 | 258.67 | 879.55 | 23.02 | 81.67 | 220.00 |
Annual Sum or Average | 4237.50 | 0.52 | 1796.50 | 19.61 | 1170.83 | 3605.17 | 866.56 | 21.01 | 784.50 | 3110.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1421.92 | 18.52 | 85.50 | 254.33 | 651.63 | 19.00 | 42.17 | 212.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2366.08 | 22.09 | 116.50 | 352.83 | 1197.00 | 23.02 | 81.67 | 317.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:30 | 508.87 | 11.25 | 0.00 | 239.83 | 317.69 | 14.86 | 0.00 | 149.00 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-08:00 | 587.70 | 12.16 | 0.00 | 245.17 | 365.30 | 15.75 | 0.00 | 173.17 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:20 | 695.54 | 13.52 | 0.00 | 309.83 | 431.35 | 17.06 | 0.00 | 256.00 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 750.91 | 13.78 | 0.00 | 330.17 | 473.18 | 17.24 | 0.00 | 293.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:40 | 898.05 | 13.96 | 1.17 | 364.17 | 532.55 | 17.56 | 1.17 | 333.33 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:19 | 996.19 | 14.70 | 17.00 | 346.33 | 563.69 | 19.43 | 40.83 | 311.33 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1016.12 | 14.30 | 14.50 | 342.17 | 533.83 | 18.48 | 29.83 | 291.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 909.65 | 12.91 | 0.00 | 323.00 | 476.81 | 16.22 | 0.00 | 264.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 788.59 | 13.08 | 0.00 | 296.17 | 441.73 | 16.45 | 0.00 | 235.50 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-07:40 | 614.95 | 12.27 | 0.00 | 284.33 | 391.15 | 15.79 | 0.00 | 227.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:20 | 521.12 | 11.64 | 0.00 | 247.17 | 345.39 | 15.40 | 0.00 | 176.17 |
December | 315.50 | 0.55 | 0.48 | 01-DEC-08:50 | 500.84 | 11.30 | 0.00 | 236.67 | 315.96 | 14.99 | 0.00 | 143.17 |
Annual Sum or Average | 4237.50 | 0.53 | 746.47 | 13.00 | 32.67 | 3565.00 | 439.26 | 16.70 | 71.83 | 2854.33 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 500.84 | 11.25 | 0.00 | 236.67 | 315.96 | 14.86 | 0.00 | 143.17 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1016.12 | 14.70 | 17.00 | 364.17 | 563.69 | 19.43 | 40.83 | 333.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:30 | 1541.14 | 19.28 | 84.17 | 259.83 | 819.08 | 22.11 | 74.50 | 215.83 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-09:09 | 1878.08 | 21.14 | 103.33 | 258.00 | 743.01 | 20.57 | 48.00 | 217.67 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:30 | 1809.45 | 19.28 | 87.67 | 315.17 | 935.94 | 21.77 | 69.33 | 282.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-08:09 | 2044.08 | 18.14 | 84.50 | 327.33 | 1081.97 | 19.58 | 54.67 | 296.33 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:30 | 1999.57 | 13.30 | 0.00 | 348.00 | 1033.23 | 17.00 | 0.00 | 314.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-08:09 | 1995.10 | 13.39 | 0.00 | 335.17 | 809.05 | 16.89 | 0.00 | 296.33 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-07:30 | 1503.66 | 14.07 | 3.50 | 332.33 | 678.22 | 17.20 | 0.00 | 280.00 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:49 | 1400.72 | 15.96 | 52.33 | 319.17 | 696.24 | 17.12 | 4.67 | 264.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:20 | 1555.63 | 18.67 | 80.17 | 297.67 | 782.10 | 20.02 | 52.33 | 251.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:00 | 1864.13 | 20.50 | 102.67 | 290.50 | 937.64 | 21.72 | 74.17 | 257.33 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1616.56 | 19.76 | 85.00 | 266.17 | 815.65 | 21.96 | 65.83 | 232.33 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-08:50 | 1417.45 | 19.95 | 87.67 | 262.83 | 727.48 | 21.24 | 59.33 | 223.17 |
Annual Sum or Average | 4237.50 | 0.52 | 1727.20 | 17.58 | 771.00 | 3612.17 | 843.06 | 19.62 | 502.83 | 3132.00 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1400.72 | 13.30 | 0.00 | 258.00 | 678.22 | 16.89 | 0.00 | 215.83 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2044.08 | 21.14 | 103.33 | 348.00 | 1081.97 | 22.11 | 74.50 | 314.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5454.01 | 34.84 | 297.00 | 286.17 | 1172.80 | 22.42 | 85.17 | 265.00 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3233.67 | 26.92 | 195.33 | 270.33 | 1034.75 | 17.81 | 0.00 | 241.50 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1634.12 | 15.11 | 7.50 | 320.67 | 889.26 | 18.27 | 0.00 | 287.50 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1099.08 | 13.87 | 0.00 | 325.33 | 654.62 | 17.30 | 0.00 | 291.50 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 930.88 | 13.46 | 0.00 | 346.17 | 550.44 | 16.96 | 0.00 | 305.00 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-07:40 | 922.94 | 13.03 | 0.00 | 331.33 | 532.39 | 16.45 | 0.00 | 285.00 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-07:10 | 1041.41 | 13.14 | 0.00 | 329.83 | 542.84 | 16.50 | 0.00 | 274.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1173.97 | 13.12 | 0.00 | 318.83 | 590.16 | 16.41 | 0.00 | 265.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 1429.18 | 13.92 | 0.00 | 299.83 | 742.01 | 17.34 | 0.00 | 258.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:19 | 2458.14 | 16.30 | 41.33 | 305.33 | 999.18 | 17.82 | 10.00 | 276.00 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 7412.00 | 35.29 | 301.67 | 283.50 | 1228.42 | 21.68 | 74.33 | 269.50 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:30 | 5748.68 | 35.30 | 298.67 | 284.17 | 1386.54 | 24.95 | 123.33 | 277.67 |
Annual Sum or Average | 4237.50 | 0.52 | 2553.47 | 19.65 | 1141.50 | 3701.50 | 837.16 | 18.49 | 292.83 | 3297.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 922.94 | 13.03 | 0.00 | 270.33 | 532.39 | 16.41 | 0.00 | 241.50 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 7412.00 | 35.30 | 301.67 | 346.17 | 1386.54 | 24.95 | 123.33 | 305.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1536.27 | 19.30 | 85.50 | 260.33 | 831.69 | 22.39 | 77.33 | 215.67 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 1962.90 | 21.42 | 100.00 | 254.33 | 1034.12 | 22.47 | 74.17 | 212.33 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:30 | 1856.48 | 19.35 | 88.17 | 313.50 | 964.25 | 21.87 | 70.67 | 281.50 |
April | 379.83 | 0.53 | 0.48 | 01-APR-06:49 | 2283.57 | 20.18 | 110.33 | 324.00 | 1196.95 | 21.42 | 81.17 | 294.50 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:10 | 2366.04 | 19.51 | 116.50 | 352.83 | 907.16 | 20.40 | 66.50 | 317.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 1884.32 | 18.52 | 100.83 | 335.00 | 779.23 | 19.48 | 51.67 | 293.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1553.65 | 18.59 | 96.33 | 334.67 | 687.45 | 19.45 | 46.17 | 278.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1421.84 | 18.55 | 97.67 | 319.50 | 651.57 | 19.00 | 42.17 | 261.17 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1589.87 | 19.44 | 88.17 | 296.00 | 803.25 | 21.00 | 64.50 | 250.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-06:49 | 1734.01 | 19.03 | 87.00 | 292.50 | 881.46 | 21.42 | 70.17 | 259.17 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-07:10 | 1574.74 | 20.11 | 87.83 | 263.67 | 793.73 | 21.13 | 58.33 | 226.83 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-07:30 | 1655.18 | 22.09 | 112.50 | 258.67 | 879.51 | 23.02 | 81.67 | 220.00 |
Annual Sum or Average | 4237.50 | 0.52 | 1796.45 | 19.61 | 1170.83 | 3605.00 | 866.51 | 21.01 | 784.50 | 3110.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1421.84 | 18.52 | 85.50 | 254.33 | 651.57 | 19.00 | 42.17 | 212.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2366.04 | 22.09 | 116.50 | 352.83 | 1196.95 | 23.02 | 81.67 | 317.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:30 | 508.86 | 11.26 | 0.00 | 239.83 | 317.67 | 14.86 | 0.00 | 149.00 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-08:00 | 587.69 | 12.17 | 0.00 | 245.17 | 365.28 | 15.75 | 0.00 | 173.17 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:20 | 695.53 | 13.52 | 0.00 | 309.83 | 431.32 | 17.06 | 0.00 | 256.00 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 750.89 | 13.79 | 0.00 | 330.17 | 473.16 | 17.24 | 0.00 | 293.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:40 | 898.01 | 13.97 | 1.17 | 364.17 | 532.51 | 17.56 | 1.17 | 333.33 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:19 | 996.14 | 14.70 | 17.00 | 346.33 | 563.65 | 19.43 | 40.83 | 311.33 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1016.05 | 14.30 | 14.50 | 342.17 | 533.79 | 18.49 | 29.83 | 291.00 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 909.59 | 12.91 | 0.00 | 322.83 | 476.77 | 16.22 | 0.00 | 264.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 788.55 | 13.08 | 0.00 | 296.17 | 441.69 | 16.45 | 0.00 | 235.50 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-07:40 | 614.94 | 12.27 | 0.00 | 284.33 | 391.12 | 15.79 | 0.00 | 227.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:20 | 521.12 | 11.65 | 0.00 | 247.17 | 345.37 | 15.40 | 0.00 | 176.17 |
December | 315.50 | 0.55 | 0.48 | 01-DEC-08:50 | 500.83 | 11.30 | 0.00 | 236.67 | 315.94 | 14.99 | 0.00 | 143.17 |
Annual Sum or Average | 4237.50 | 0.53 | 746.45 | 13.00 | 32.67 | 3564.83 | 439.23 | 16.70 | 71.83 | 2854.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 500.83 | 11.26 | 0.00 | 236.67 | 315.94 | 14.86 | 0.00 | 143.17 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1016.05 | 14.70 | 17.00 | 364.17 | 563.65 | 19.43 | 40.83 | 333.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:30 | 1541.12 | 19.29 | 84.17 | 259.83 | 819.04 | 22.11 | 74.50 | 215.83 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-09:09 | 1878.05 | 21.14 | 103.33 | 258.00 | 742.96 | 20.57 | 48.00 | 217.67 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:30 | 1809.41 | 19.28 | 87.67 | 315.17 | 935.89 | 21.77 | 69.33 | 282.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-08:09 | 2044.05 | 18.14 | 84.50 | 327.33 | 1081.93 | 19.58 | 54.67 | 296.33 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:30 | 1999.53 | 13.30 | 0.00 | 348.00 | 1033.18 | 17.00 | 0.00 | 314.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-08:09 | 1995.04 | 13.39 | 0.00 | 335.17 | 808.99 | 16.89 | 0.00 | 296.17 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-07:30 | 1503.57 | 14.07 | 3.50 | 332.33 | 678.16 | 17.20 | 0.00 | 280.00 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:49 | 1400.64 | 15.96 | 52.33 | 319.17 | 696.18 | 17.12 | 4.67 | 264.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:20 | 1555.56 | 18.67 | 80.17 | 297.67 | 782.05 | 20.02 | 52.33 | 251.33 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:00 | 1864.10 | 20.50 | 102.67 | 290.50 | 937.59 | 21.72 | 74.17 | 257.33 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1616.54 | 19.76 | 85.00 | 266.17 | 815.61 | 21.96 | 65.83 | 232.33 |
December | 315.50 | 0.53 | 0.48 | 01-DEC-08:50 | 1417.43 | 19.95 | 87.67 | 262.83 | 727.44 | 21.24 | 59.33 | 223.17 |
Annual Sum or Average | 4237.50 | 0.52 | 1727.16 | 17.58 | 771.00 | 3612.17 | 843.01 | 19.62 | 502.83 | 3131.67 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1400.64 | 13.30 | 0.00 | 258.00 | 678.16 | 16.89 | 0.00 | 215.83 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2044.05 | 21.14 | 103.33 | 348.00 | 1081.93 | 22.11 | 74.50 | 314.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.674852E+09 | 7033.71 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435065E+09 | 7033.71 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100701E+09 | 7033.71 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125999E+09 | 7033.71 | 22-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.494967E+09 | 7033.71 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.674852E+09 | 7033.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28202432.10 | 4664.98 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28202432.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28202432.10 | 4664.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107281E+09 | 7033.72 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 764640.89 | 1907.27 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1335433.10 | 2349.65 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107281E+09 | 7033.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39252438.02 | 4677.09 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79290.76 | 193.72 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39331728.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39252438.02 | 4677.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 36186000.06 | 20767.97 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36186000.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36186000.06 | 20767.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 80341272.69 | 8304.74 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1355609.61 | 3117.48 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4000246.59 | 7826.83 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85697128.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80341272.69 | 8304.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 66773701.00 | 5484.58 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1488218.72 | 3541.96 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3958488.20 | 5484.58 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72220407.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66773701.00 | 5484.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.178854E+09 | 8316.24 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7654584.86 | 5273.68 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17733431.48 | 8316.24 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178854E+09 | 8316.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102541E+09 | 5496.35 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4665075.95 | 3871.33 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10621603.19 | 5496.35 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102541E+09 | 5496.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.638593E+09 | 27320.28 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16991044.61 | 20632.01 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70581499.06 | 27320.28 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.726165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.638593E+09 | 27320.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.433644E+09 | 10901.54 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78595974.31 | 10901.54 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2124830.23 | 4484.85 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147794E+09 | 10901.54 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.662159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.433644E+09 | 10901.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304137E+09 | 7101.03 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48165451.44 | 7101.03 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2740277.50 | 6075.33 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114228E+09 | 7101.03 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304137E+09 | 7101.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.735863E+09 | 10907.99 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128414E+09 | 10907.99 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10234409.88 | 10907.99 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286314E+09 | 10907.99 | 02-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.735863E+09 | 10907.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.436139E+09 | 7107.00 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78622855.26 | 7107.00 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5173988.87 | 5983.05 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170745E+09 | 7107.00 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.690681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.436139E+09 | 7107.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.422834E+09 | 2554.28 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81138199.20 | 2554.28 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2334550.95 | 796.19 | 27-NOV-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119160E+09 | 2554.28 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.422834E+09 | 2554.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.648116E+09 | 3870.84 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129240E+09 | 3826.90 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5668660.63 | 1165.91 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238559E+09 | 3870.84 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648116E+09 | 3870.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 73389293.62 | 225.50 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25050518.76 | 225.50 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4866905.47 | 225.50 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48860734.59 | 225.50 | 01-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73389293.62 | 225.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.123096E+11 | 0.101162E+11 | 27402.94 | 12-JAN-15:00 | 27402.94 | 0.00 |
February | 0.00 | 0.00 | 0.217976E+11 | 0.189199E+11 | 42223.51 | 22-FEB-15:00 | 42223.51 | 0.00 |
March | 0.00 | 0.00 | 0.451916E+11 | 0.414996E+11 | 64111.86 | 29-MAR-11:20 | 47094.47 | 0.00 |
April | 0.00 | 0.00 | 0.679275E+11 | 0.632451E+11 | 95329.49 | 27-APR-06:03 | 76982.86 | 0.00 |
May | 0.00 | 0.00 | 0.102629E+12 | 0.847299E+11 | 118662.58 | 24-MAY-05:03 | 66035.47 | 0.00 |
June | 0.00 | 0.00 | 0.117910E+12 | 0.862457E+11 | 120023.80 | 26-JUN-04:02 | 70312.25 | 0.00 |
July | 0.00 | 0.00 | 0.129955E+12 | 0.791028E+11 | 122423.65 | 20-JUL-04:03 | 63733.63 | 0.00 |
August | 0.00 | 0.00 | 0.131530E+12 | 0.776120E+11 | 121060.84 | 10-AUG-04:02 | 67380.08 | 0.00 |
September | 0.00 | 0.00 | 0.105004E+12 | 0.672290E+11 | 120036.37 | 17-SEP-16:22 | 70029.10 | 0.00 |
October | 0.00 | 0.00 | 0.689567E+11 | 0.582880E+11 | 110590.85 | 04-OCT-06:03 | 75592.02 | 0.00 |
November | 0.00 | 0.00 | 0.396415E+11 | 0.363591E+11 | 56008.63 | 06-NOV-14:00 | 51225.37 | 0.00 |
December | 0.00 | 0.00 | 0.173904E+11 | 0.152185E+11 | 35500.85 | 01-DEC-15:00 | 35500.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.860242E+12 | 0.638566E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.123096E+11 | 0.101162E+11 | 27402.94 | 27402.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131530E+12 | 0.862457E+11 | 122423.65 | 76982.86 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100643E+11 | 0.800305E+10 | 24905.71 | 12-JAN-15:05 | 24905.71 | 0.00 |
February | 0.00 | 0.00 | 0.190197E+11 | 0.161949E+11 | 41773.10 | 22-FEB-15:05 | 41773.10 | 0.00 |
March | 0.00 | 0.00 | 0.426947E+11 | 0.391426E+11 | 62459.13 | 13-MAR-12:02 | 55754.14 | 0.00 |
April | 0.00 | 0.00 | 0.661086E+11 | 0.622464E+11 | 93535.03 | 16-APR-16:02 | 81412.09 | 0.00 |
May | 0.00 | 0.00 | 0.972228E+11 | 0.817743E+11 | 115142.78 | 24-MAY-05:03 | 64448.74 | 0.00 |
June | 0.00 | 0.00 | 0.108080E+12 | 0.804883E+11 | 116971.35 | 26-JUN-04:02 | 66272.57 | 0.00 |
July | 0.00 | 0.00 | 0.115215E+12 | 0.708379E+11 | 118807.50 | 20-JUL-04:03 | 58078.55 | 0.00 |
August | 0.00 | 0.00 | 0.112293E+12 | 0.664754E+11 | 118319.90 | 10-AUG-04:02 | 62242.05 | 0.00 |
September | 0.00 | 0.00 | 0.883910E+11 | 0.565870E+11 | 115923.64 | 11-SEP-04:03 | 62251.40 | 0.00 |
October | 0.00 | 0.00 | 0.578738E+11 | 0.488767E+11 | 82895.39 | 11-OCT-05:03 | 57730.35 | 0.00 |
November | 0.00 | 0.00 | 0.322593E+11 | 0.289554E+11 | 51660.09 | 06-NOV-13:05 | 45542.61 | 0.00 |
December | 0.00 | 0.00 | 0.134785E+11 | 0.111189E+11 | 31411.79 | 01-DEC-15:05 | 31411.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.762701E+12 | 0.570701E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.100643E+11 | 0.800305E+10 | 24905.71 | 24905.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115215E+12 | 0.817743E+11 | 118807.50 | 81412.09 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.103483E+11 | 0.799289E+10 | 25750.74 | 12-JAN-15:00 | 25750.74 | 0.00 |
February | 0.00 | 0.00 | 0.196269E+11 | 0.164351E+11 | 47115.58 | 22-FEB-15:00 | 47115.58 | 0.00 |
March | 0.00 | 0.00 | 0.464156E+11 | 0.420623E+11 | 74428.32 | 28-MAR-16:00 | 74428.32 | 0.00 |
April | 0.00 | 0.00 | 0.746683E+11 | 0.701876E+11 | 117572.12 | 16-APR-16:42 | 104000.11 | 0.00 |
May | 0.00 | 0.00 | 0.109373E+12 | 0.930567E+11 | 134861.33 | 24-MAY-05:03 | 71711.16 | 0.00 |
June | 0.00 | 0.00 | 0.121260E+12 | 0.923352E+11 | 137194.78 | 27-JUN-04:02 | 76981.81 | 0.00 |
July | 0.00 | 0.00 | 0.126269E+12 | 0.798564E+11 | 139284.98 | 20-JUL-04:03 | 68290.69 | 0.00 |
August | 0.00 | 0.00 | 0.120495E+12 | 0.736008E+11 | 139079.33 | 10-AUG-04:02 | 74772.11 | 0.00 |
September | 0.00 | 0.00 | 0.935313E+11 | 0.612149E+11 | 133644.34 | 17-SEP-15:22 | 81295.47 | 0.00 |
October | 0.00 | 0.00 | 0.612077E+11 | 0.518080E+11 | 87536.00 | 01-OCT-14:22 | 87536.00 | 0.00 |
November | 0.00 | 0.00 | 0.328617E+11 | 0.290041E+11 | 55348.60 | 09-NOV-13:40 | 52424.42 | 0.00 |
December | 0.00 | 0.00 | 0.132303E+11 | 0.104363E+11 | 32648.86 | 01-DEC-14:50 | 32648.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.829287E+12 | 0.627990E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.103483E+11 | 0.799289E+10 | 25750.74 | 25750.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126269E+12 | 0.930567E+11 | 139284.98 | 104000.11 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1495.64 | 5152.72 | 17-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1475.70 | 5100.12 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1475.81 | 4875.13 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1253.77 | 4442.30 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 1165.23 | 4022.25 | 01-MAY-11:12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1086.55 | 3571.09 | 02-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 960.96 | 3313.18 | 06-JUL-11:09 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1082.57 | 3502.87 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1106.78 | 3916.59 | 29-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1231.77 | 4402.33 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1380.47 | 4812.05 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1419.75 | 5092.76 | 29-DEC-12:08 |
Annual Sum or Average | 0.00 | 1260.08 | ||||
Minimum of Months | 0.00 | 0.00 | 960.96 | 3313.18 | ||
Maximum of Months | 0.00 | 0.00 | 1495.64 | 5152.72 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136309E+10 | 0.30 | 2101.37 | 12-JAN-15:00 | 0.70 |
February | 0.174808E+10 | 0.33 | 3952.71 | 21-FEB-16:10 | 0.99 |
March | 0.306994E+10 | 0.41 | 5313.34 | 13-MAR-10:30 | 1.18 |
April | 0.426994E+10 | 0.50 | 10575.19 | 17-APR-04:02 | 1.82 |
May | 0.573143E+10 | 0.60 | 10575.19 | 02-MAY-04:02 | 1.82 |
June | 0.593926E+10 | 0.63 | 10575.19 | 07-JUN-06:03 | 1.83 |
July | 0.565558E+10 | 0.60 | 10575.19 | 03-JUL-05:03 | 1.82 |
August | 0.592913E+10 | 0.60 | 10575.19 | 01-AUG-04:03 | 1.82 |
September | 0.502830E+10 | 0.55 | 10575.19 | 01-SEP-06:03 | 1.82 |
October | 0.410222E+10 | 0.47 | 10575.19 | 02-OCT-05:12 | 1.82 |
November | 0.275240E+10 | 0.39 | 4931.78 | 06-NOV-16:50 | 1.13 |
December | 0.168845E+10 | 0.31 | 3346.42 | 01-DEC-15:20 | 0.90 |
Annual Sum or Average | 0.472778E+11 | 0.47 | |||
Minimum of Months | 0.136309E+10 | 0.30 | 2101.37 | 0.70 | |
Maximum of Months | 0.593926E+10 | 0.63 | 10575.19 | 1.83 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117395E+10 | 0.29 | 2169.20 | 02-JAN-07:01 | 0.73 |
February | 0.150361E+10 | 0.33 | 3757.32 | 22-FEB-15:30 | 0.99 |
March | 0.301157E+10 | 0.42 | 6340.35 | 13-MAR-16:00 | 1.36 |
April | 0.468083E+10 | 0.53 | 10089.94 | 17-APR-04:02 | 1.82 |
May | 0.616725E+10 | 0.64 | 10089.94 | 05-MAY-04:02 | 1.82 |
June | 0.610980E+10 | 0.65 | 10089.94 | 05-JUN-04:02 | 1.83 |
July | 0.542599E+10 | 0.59 | 10089.94 | 01-JUL-04:02 | 1.82 |
August | 0.528649E+10 | 0.57 | 10089.94 | 01-AUG-04:03 | 1.82 |
September | 0.425309E+10 | 0.50 | 10089.94 | 05-SEP-06:03 | 1.82 |
October | 0.340499E+10 | 0.43 | 8850.23 | 02-OCT-05:12 | 1.68 |
November | 0.214585E+10 | 0.36 | 4495.57 | 13-NOV-16:00 | 1.10 |
December | 0.130987E+10 | 0.30 | 2819.23 | 01-DEC-15:05 | 0.84 |
Annual Sum or Average | 0.444733E+11 | 0.47 | |||
Minimum of Months | 0.117395E+10 | 0.29 | 2169.20 | 0.73 | |
Maximum of Months | 0.616725E+10 | 0.65 | 10089.94 | 1.83 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129157E+10 | 0.33 | 2344.43 | 02-JAN-06:12 | 0.68 |
February | 0.150750E+10 | 0.35 | 3476.11 | 22-FEB-15:00 | 0.84 |
March | 0.295289E+10 | 0.41 | 6759.17 | 13-MAR-15:40 | 1.25 |
April | 0.484764E+10 | 0.51 | 9665.46 | 27-APR-06:03 | 1.56 |
May | 0.637435E+10 | 0.61 | 12251.84 | 06-MAY-04:02 | 1.82 |
June | 0.633646E+10 | 0.62 | 12251.84 | 12-JUN-04:02 | 1.81 |
July | 0.537916E+10 | 0.56 | 12251.84 | 03-JUL-05:03 | 1.81 |
August | 0.508522E+10 | 0.52 | 12251.84 | 02-AUG-04:02 | 1.81 |
September | 0.410616E+10 | 0.46 | 11742.95 | 25-SEP-04:02 | 1.76 |
October | 0.330702E+10 | 0.41 | 6599.96 | 10-OCT-14:40 | 1.23 |
November | 0.207487E+10 | 0.36 | 4156.75 | 09-NOV-15:30 | 0.93 |
December | 0.134858E+10 | 0.33 | 2344.43 | 21-DEC-07:01 | 0.69 |
Annual Sum or Average | 0.446114E+11 | 0.46 | |||
Minimum of Months | 0.129157E+10 | 0.33 | 2344.43 | 0.68 | |
Maximum of Months | 0.637435E+10 | 0.62 | 12251.84 | 1.82 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.75 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.17 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.08 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.54 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 56.79 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.19 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:10 | 2.06 | 2.06 | 57.83 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 57.26 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 57.50 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.17 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.48 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.16 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.08 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.17 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.21 | 57.21 | 1495.64 | 5152.72 | 17-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.54 | 56.54 | 1475.70 | 5100.12 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.43 | 56.43 | 1475.81 | 4875.13 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.86 | 57.86 | 1253.77 | 4442.30 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.14 | 58.14 | 1165.23 | 4022.25 | 01-MAY-11:12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.35 | 57.35 | 1086.55 | 3571.09 | 02-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.95 | 57.95 | 960.96 | 3313.18 | 06-JUL-11:09 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.50 | 58.50 | 1082.57 | 3502.87 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.67 | 57.67 | 1106.78 | 3916.59 | 29-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.74 | 57.74 | 1231.77 | 4402.33 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.75 | 57.75 | 1380.47 | 4812.05 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.48 | 56.48 | 1419.75 | 5092.76 | 29-DEC-12:08 |
Annual Sum or Average | 0.00 | 1260.08 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.43 | 56.43 | 960.96 | 3313.18 | ||
Maximum of Months | 0.00 | 0.00 | 58.50 | 58.50 | 1495.64 | 5152.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.533152E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.745813E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143139E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.230234E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.355903E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.392811E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.390828E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.385991E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.309468E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.212968E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.123350E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.647595E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.273735E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.533152E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.392811E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.422094E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.616034E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.135678E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.228957E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.343656E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.365622E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.349749E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.330848E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.259995E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.179453E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.996957E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.473760E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.244484E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.422094E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.365622E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.650990E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.668513E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145412E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.256174E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.383411E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.407665E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.379318E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.350416E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.272842E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.188740E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101735E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.550249E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.267269E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.550249E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.407665E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136309E+10 | 0.123096E+11 | 0.127242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174808E+10 | 0.217976E+11 | 0.516968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306994E+10 | 0.451916E+11 | 0.100701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426994E+10 | 0.679275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573143E+10 | 0.102629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.593926E+10 | 0.117910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565558E+10 | 0.129955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.592913E+10 | 0.131530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.502830E+10 | 0.105004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410222E+10 | 0.689567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275240E+10 | 0.396415E+11 | 0.128333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168845E+10 | 0.173904E+11 | 0.615542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472778E+11 | 0.860242E+12 | 0.263397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136309E+10 | 0.123096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.593926E+10 | 0.131530E+12 | 0.127242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117395E+10 | 0.100643E+11 | 0.111281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150361E+10 | 0.190197E+11 | 0.144404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301157E+10 | 0.426947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468083E+10 | 0.661086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.616725E+10 | 0.972228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610980E+10 | 0.108080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.542599E+10 | 0.115215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.528649E+10 | 0.112293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.425309E+10 | 0.883910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340499E+10 | 0.578738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214585E+10 | 0.322593E+11 | 5668660.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130987E+10 | 0.134785E+11 | 0.274873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444733E+11 | 0.762701E+12 | 0.153776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117395E+10 | 0.100643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.616725E+10 | 0.115215E+12 | 0.111281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129157E+10 | 0.103483E+11 | 0.262177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150750E+10 | 0.196269E+11 | 0.375839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295289E+10 | 0.464156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.484764E+10 | 0.746683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.637435E+10 | 0.109373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.633646E+10 | 0.121260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.537916E+10 | 0.126269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.508522E+10 | 0.120495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410616E+10 | 0.935313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330702E+10 | 0.612077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207487E+10 | 0.328617E+11 | 25140411.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134858E+10 | 0.132303E+11 | 0.838522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.446114E+11 | 0.829287E+12 | 0.386127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129157E+10 | 0.103483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.637435E+10 | 0.126269E+12 | 0.262177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136309E+10 | 0.00 | 0.00 | 0.00 | 0.311884E+10 | 0.849588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174808E+10 | 0.00 | 0.00 | 0.00 | 0.527423E+10 | 0.435829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306994E+10 | 0.00 | 0.00 | 0.00 | 0.111433E+11 | 0.100701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426994E+10 | 0.00 | 0.00 | 0.00 | 0.187534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.573143E+10 | 0.00 | 0.00 | 0.00 | 0.298589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.593926E+10 | 0.00 | 0.00 | 0.00 | 0.333419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565558E+10 | 0.00 | 0.00 | 0.00 | 0.334272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.592913E+10 | 0.00 | 0.00 | 0.00 | 0.326700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.502830E+10 | 0.00 | 0.00 | 0.00 | 0.259185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410222E+10 | 0.00 | 0.00 | 0.00 | 0.171946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275240E+10 | 0.00 | 0.00 | 0.00 | 0.945659E+10 | 0.125999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168845E+10 | 0.00 | 0.00 | 0.00 | 0.429111E+10 | 0.496382E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472778E+11 | 0.00 | 0.00 | 0.00 | 0.224449E+12 | 0.200850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136309E+10 | 0.00 | 0.00 | 0.00 | 0.311884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.593926E+10 | 0.00 | 0.00 | 0.00 | 0.334272E+11 | 0.849588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117395E+10 | 0.00 | 0.00 | 0.00 | 0.258230E+10 | 0.464696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150361E+10 | 0.00 | 0.00 | 0.00 | 0.464157E+10 | 15163489.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301157E+10 | 0.00 | 0.00 | 0.00 | 0.105562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.468083E+10 | 0.00 | 0.00 | 0.00 | 0.182148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.616725E+10 | 0.00 | 0.00 | 0.00 | 0.281984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610980E+10 | 0.00 | 0.00 | 0.00 | 0.304524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.542599E+10 | 0.00 | 0.00 | 0.00 | 0.295489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.528649E+10 | 0.00 | 0.00 | 0.00 | 0.277984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.425309E+10 | 0.00 | 0.00 | 0.00 | 0.217464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340499E+10 | 0.00 | 0.00 | 0.00 | 0.145403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214585E+10 | 0.00 | 0.00 | 0.00 | 0.782372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130987E+10 | 0.00 | 0.00 | 0.00 | 0.339142E+10 | 36313769.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444733E+11 | 0.00 | 0.00 | 0.00 | 0.199495E+12 | 0.516173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117395E+10 | 0.00 | 0.00 | 0.00 | 0.258230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.616725E+10 | 0.00 | 0.00 | 0.00 | 0.304524E+11 | 0.464696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129157E+10 | 0.00 | 0.00 | 0.00 | 0.266996E+10 | 0.254838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150750E+10 | 0.00 | 0.00 | 0.00 | 0.482684E+10 | 0.350789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295289E+10 | 0.00 | 0.00 | 0.00 | 0.115883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.484764E+10 | 0.00 | 0.00 | 0.00 | 0.207698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.637435E+10 | 0.00 | 0.00 | 0.00 | 0.319668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.633646E+10 | 0.00 | 0.00 | 0.00 | 0.344301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.537916E+10 | 0.00 | 0.00 | 0.00 | 0.325526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.508522E+10 | 0.00 | 0.00 | 0.00 | 0.299564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410616E+10 | 0.00 | 0.00 | 0.00 | 0.231781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330702E+10 | 0.00 | 0.00 | 0.00 | 0.155669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207487E+10 | 0.00 | 0.00 | 0.00 | 0.807833E+10 | 20273506.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134858E+10 | 0.00 | 0.00 | 0.00 | 0.336424E+10 | 0.789661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.446114E+11 | 0.00 | 0.00 | 0.00 | 0.218948E+12 | 0.370910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129157E+10 | 0.00 | 0.00 | 0.00 | 0.266996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.637435E+10 | 0.00 | 0.00 | 0.00 | 0.344301E+11 | 0.254838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200502E+10 | 643758.11 | 0.00 | 20385648.95 | 633358.58 | 0.00 | 0.568370E+10 | 0.00 | 0.36 |
February | 0.514411E+09 | 28937978.47 | 0.00 | 25642893.25 | 17291569.80 | 0.00 | 0.416886E+10 | 0.00 | 0.39 |
March | 0.211644E+09 | 0.838658E+09 | 0.00 | 24628949.60 | 0.215456E+09 | 0.00 | 0.195107E+10 | 0.00 | 0.39 |
April | 22266412.20 | 0.342023E+10 | 0.00 | 4589209.60 | 0.997096E+09 | 0.00 | 0.102134E+09 | 0.00 | 0.33 |
May | 1030481.31 | 0.969445E+10 | 0.00 | 68251.51 | 0.251040E+10 | 0.00 | 3577098.39 | 0.00 | 0.34 |
June | 0.00 | 0.138241E+11 | 0.00 | 0.00 | 0.385028E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.166926E+11 | 0.00 | 0.00 | 0.724591E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.187066E+11 | 0.00 | 0.00 | 0.459056E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.132710E+11 | 0.00 | 0.00 | 0.331590E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 43588747.28 | 0.345550E+10 | 0.00 | 7477179.27 | 0.843180E+09 | 0.00 | 0.324468E+09 | 0.00 | 0.33 |
November | 0.339291E+09 | 0.139163E+09 | 0.00 | 30937931.00 | 0.123172E+09 | 0.00 | 0.268329E+10 | 0.00 | 0.36 |
December | 0.853857E+09 | 2651210.46 | 0.00 | 28370426.07 | 8847915.36 | 0.00 | 0.655515E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.399111E+10 | 0.800744E+11 | 0.00 | 0.142100E+09 | 0.237187E+11 | 0.00 | 0.214722E+11 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 643758.11 | 0.00 | 0.00 | 633358.58 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.200502E+10 | 0.187066E+11 | 0.00 | 30937931.00 | 0.724591E+10 | 0.00 | 0.655515E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449473E+10 | 0.00 | 0.00 | 4977186.01 | 4275747.28 | 30196506.76 | 0.168991E+10 | 0.00 | 0.29 |
February | 0.157483E+10 | 23885980.89 | 0.00 | 12784137.41 | 24299872.34 | 0.00 | 0.210147E+10 | 0.00 | 0.31 |
March | 0.255833E+09 | 0.634858E+09 | 0.00 | 17661298.99 | 0.228940E+09 | 0.00 | 0.147076E+10 | 0.00 | 0.32 |
April | 29199044.40 | 0.282818E+10 | 0.00 | 4693249.85 | 0.103894E+10 | 0.00 | 0.102843E+09 | 0.00 | 0.31 |
May | 1284933.10 | 0.886353E+10 | 0.00 | 121046.63 | 0.261121E+10 | 0.00 | 2979274.09 | 0.00 | 0.34 |
June | 0.00 | 0.130714E+11 | 0.00 | 0.00 | 0.390742E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.163222E+11 | 0.00 | 0.00 | 0.640924E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.183710E+11 | 0.00 | 0.00 | 0.389197E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.128190E+11 | 0.00 | 0.00 | 0.280809E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 66565735.21 | 0.318841E+10 | 0.00 | 5097940.77 | 0.697965E+09 | 0.00 | 0.193178E+09 | 0.00 | 0.30 |
November | 0.525760E+09 | 0.130735E+09 | 0.00 | 18808895.06 | 0.131369E+09 | 0.00 | 0.180754E+10 | 0.00 | 0.31 |
December | 0.317276E+10 | 0.00 | 0.00 | 9925304.14 | 23014016.09 | 0.00 | 0.243667E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.101210E+11 | 0.762531E+11 | 0.00 | 74069058.87 | 0.217767E+11 | 30196506.76 | 0.980535E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4275747.28 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.449473E+10 | 0.183710E+11 | 0.00 | 18808895.06 | 0.640924E+10 | 30196506.76 | 0.243667E+10 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.447419E+10 | 0.00 | 0.00 | 2559998.00 | 1013933.10 | 0.203666E+09 | 0.863883E+09 | 0.00 | 0.29 |
February | 0.183351E+10 | 24899310.40 | 0.00 | 8764361.93 | 24767461.64 | 873862.15 | 0.131387E+10 | 0.00 | 0.30 |
March | 0.322364E+09 | 0.625266E+09 | 0.00 | 14426115.85 | 0.251013E+09 | 0.00 | 0.107027E+10 | 0.00 | 0.31 |
April | 15490105.44 | 0.275038E+10 | 0.00 | 5667718.35 | 0.996019E+09 | 0.00 | 0.101359E+09 | 0.00 | 0.31 |
May | 359519.74 | 0.879900E+10 | 0.00 | 25460.84 | 0.260975E+10 | 0.00 | 745279.44 | 0.00 | 0.35 |
June | 0.00 | 0.129760E+11 | 0.00 | 0.00 | 0.428387E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.163706E+11 | 0.00 | 0.00 | 0.679067E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.183678E+11 | 0.00 | 0.00 | 0.388671E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.125443E+11 | 0.00 | 0.00 | 0.298233E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 48039595.25 | 0.314205E+10 | 0.00 | 2517661.37 | 0.711001E+09 | 0.00 | 49291467.29 | 0.00 | 0.30 |
November | 0.763499E+09 | 0.131659E+09 | 0.00 | 13342411.57 | 0.125533E+09 | 0.00 | 0.983772E+09 | 0.00 | 0.30 |
December | 0.354264E+10 | 0.00 | 0.00 | 4697268.16 | 9998186.46 | 6131990.66 | 0.120920E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.110001E+11 | 0.757320E+11 | 0.00 | 52000996.06 | 0.226727E+11 | 0.210672E+09 | 0.559239E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1013933.10 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.447419E+10 | 0.183678E+11 | 0.00 | 14426115.85 | 0.679067E+10 | 0.203666E+09 | 0.131387E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.798774E+09 | 0.00 | 0.00 | 235972.14 | 213194.27 | 0.307064E+09 | 74666947.61 | 0.00 | 0.29 |
February | 0.422249E+09 | 4926202.49 | 0.00 | 1635467.13 | 5600688.41 | 54836163.83 | 0.186603E+09 | 0.00 | 0.30 |
March | 94274597.54 | 0.187460E+09 | 0.00 | 3497085.66 | 47290686.30 | 0.00 | 0.232862E+09 | 0.00 | 0.36 |
April | 3547984.80 | 0.103362E+10 | 0.00 | 1850756.53 | 0.145656E+09 | 0.00 | 31812492.91 | 0.00 | 0.45 |
May | 100007.78 | 0.367243E+10 | 0.00 | 14059.49 | 0.272862E+09 | 0.00 | 209812.03 | 0.00 | 0.56 |
June | 0.00 | 0.556137E+10 | 0.00 | 0.00 | 0.505742E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.726854E+10 | 0.00 | 0.00 | 0.675310E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.709233E+10 | 0.00 | 0.00 | 0.408011E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.431836E+10 | 0.00 | 0.00 | 0.422099E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 11910275.88 | 0.877388E+09 | 0.00 | 597941.46 | 0.156662E+09 | 0.00 | 10615288.60 | 0.00 | 0.37 |
November | 0.215783E+09 | 25754421.29 | 0.00 | 2720376.65 | 30835870.17 | 1904912.54 | 0.150571E+09 | 0.00 | 0.31 |
December | 0.746873E+09 | 0.00 | 0.00 | 562819.43 | 2102265.04 | 0.119527E+09 | 0.117678E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.229351E+10 | 0.300422E+11 | 0.00 | 11114478.49 | 0.267238E+10 | 0.483332E+09 | 0.805019E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 213194.27 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.798774E+09 | 0.726854E+10 | 0.00 | 3497085.66 | 0.675310E+09 | 0.307064E+09 | 0.232862E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.451775E+09 | 7532.45 | 0.00 | 671221.19 | 127686.74 | 0.130017E+09 | 0.196740E+09 | 0.00 | 0.30 |
February | 0.207608E+09 | 3873082.01 | 0.00 | 2327231.75 | 3329873.22 | 18989392.39 | 0.315303E+09 | 0.00 | 0.39 |
March | 41650348.73 | 0.183605E+09 | 0.00 | 3619717.79 | 19655671.28 | 0.00 | 0.258908E+09 | 0.00 | 0.53 |
April | 1300337.34 | 0.101295E+10 | 0.00 | 1684834.45 | 62587702.41 | 0.00 | 30258420.87 | 0.00 | 0.64 |
May | 63430.27 | 0.303063E+10 | 0.00 | 9017.04 | 0.145283E+09 | 0.00 | 137100.91 | 0.00 | 0.72 |
June | 0.00 | 0.418745E+10 | 0.00 | 0.00 | 0.299427E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.530923E+10 | 0.00 | 0.00 | 0.393620E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.512444E+10 | 0.00 | 0.00 | 0.224208E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.336707E+10 | 0.00 | 0.00 | 0.218253E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 6761630.67 | 0.804370E+09 | 0.00 | 557040.36 | 71209276.83 | 0.00 | 9771783.46 | 0.00 | 0.50 |
November | 0.102561E+09 | 33616727.06 | 0.00 | 3033845.26 | 15327184.23 | 785142.30 | 0.204237E+09 | 0.00 | 0.42 |
December | 0.404225E+09 | 615766.52 | 0.00 | 1108925.69 | 733153.06 | 44749640.84 | 0.222820E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.121595E+10 | 0.230579E+11 | 0.00 | 13011833.54 | 0.145376E+10 | 0.194541E+09 | 0.123818E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 7532.45 | 0.00 | 0.00 | 127686.74 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.451775E+09 | 0.530923E+10 | 0.00 | 3619717.79 | 0.393620E+09 | 0.130017E+09 | 0.315303E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539711E+09 | 455709.26 | 0.00 | 5145649.82 | 0.00 | 0.183761E+09 | 0.122774E+10 | 0.00 | 0.51 |
February | 0.313720E+09 | 12655697.89 | 0.00 | 7105123.53 | 3849397.99 | 31326068.17 | 0.807147E+09 | 0.00 | 0.55 |
March | 71914561.00 | 0.326352E+09 | 0.00 | 6893668.06 | 27856145.24 | 0.00 | 0.460642E+09 | 0.00 | 0.57 |
April | 3557060.45 | 0.132103E+10 | 0.00 | 2561904.77 | 0.113894E+09 | 0.00 | 43903178.54 | 0.00 | 0.55 |
May | 100263.59 | 0.379929E+10 | 0.00 | 14081.55 | 0.273933E+09 | 0.00 | 211181.25 | 0.00 | 0.58 |
June | 0.00 | 0.549326E+10 | 0.00 | 0.00 | 0.520352E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.729452E+10 | 0.00 | 0.00 | 0.688430E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.750929E+10 | 0.00 | 0.00 | 0.383379E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.530369E+10 | 0.00 | 0.00 | 0.327617E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 11675394.02 | 0.155893E+10 | 0.00 | 1321180.47 | 94105626.06 | 0.00 | 20434879.17 | 0.00 | 0.62 |
November | 0.140531E+09 | 0.121386E+09 | 0.00 | 9994477.99 | 7692858.69 | 355060.94 | 0.625728E+09 | 0.00 | 0.66 |
December | 0.501199E+09 | 4726359.83 | 0.00 | 6257584.79 | 237181.76 | 58413837.39 | 0.120313E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.158241E+10 | 0.327456E+11 | 0.00 | 39293670.97 | 0.244135E+10 | 0.273856E+09 | 0.438894E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 455709.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.539711E+09 | 0.750929E+10 | 0.00 | 9994477.99 | 0.688430E+09 | 0.183761E+09 | 0.122774E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.425817E+09 | 162220.80 | 0.00 | 1041353.08 | 5604.76 | 0.183447E+09 | 0.253716E+09 | 0.00 | 0.34 |
February | 0.247540E+09 | 7675491.05 | 0.00 | 2157182.48 | 2716797.35 | 31618319.21 | 0.241768E+09 | 0.00 | 0.39 |
March | 54178091.91 | 0.188651E+09 | 0.00 | 3629929.89 | 20297564.69 | 0.00 | 0.249862E+09 | 0.00 | 0.51 |
April | 2228786.76 | 0.968878E+09 | 0.00 | 1812007.84 | 65676043.64 | 0.00 | 28361944.89 | 0.00 | 0.62 |
May | 45109.25 | 0.303722E+10 | 0.00 | 11035.60 | 0.136699E+09 | 0.00 | 172377.32 | 0.00 | 0.71 |
June | 0.00 | 0.439389E+10 | 0.00 | 0.00 | 0.273777E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.534400E+10 | 0.00 | 0.00 | 0.368712E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.520899E+10 | 0.00 | 0.00 | 0.208920E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.345108E+10 | 0.00 | 0.00 | 0.193177E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 7519848.99 | 0.769945E+09 | 0.00 | 615210.02 | 76888831.63 | 0.00 | 11269890.77 | 0.00 | 0.48 |
November | 0.121001E+09 | 36842888.53 | 0.00 | 3147695.36 | 11845048.14 | 1167956.35 | 0.179766E+09 | 0.00 | 0.41 |
December | 0.422144E+09 | 842417.53 | 0.00 | 1261553.56 | 797550.50 | 70104027.14 | 0.235992E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.128047E+10 | 0.234082E+11 | 0.00 | 13675967.82 | 0.135951E+10 | 0.286337E+09 | 0.120091E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 162220.80 | 0.00 | 0.00 | 5604.76 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.425817E+09 | 0.534400E+10 | 0.00 | 3629929.89 | 0.368712E+09 | 0.183447E+09 | 0.253716E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112155E+10 | 0.00 | 0.00 | 258695.57 | 268648.61 | 79266638.88 | 76638051.24 | 0.00 | 0.27 |
February | 0.537943E+09 | 4170971.76 | 0.00 | 1251435.15 | 4782981.19 | 162594.34 | 0.138253E+09 | 0.00 | 0.27 |
March | 0.132857E+09 | 0.159429E+09 | 0.00 | 2301208.56 | 50641883.46 | 0.00 | 0.166916E+09 | 0.00 | 0.29 |
April | 10830601.30 | 0.875928E+09 | 0.00 | 582390.40 | 0.213891E+09 | 0.00 | 9893111.06 | 0.00 | 0.35 |
May | 306709.49 | 0.318388E+10 | 0.00 | 19058.04 | 0.366227E+09 | 0.00 | 719179.45 | 0.00 | 0.46 |
June | 0.00 | 0.503808E+10 | 0.00 | 0.00 | 0.521879E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.677365E+10 | 0.00 | 0.00 | 0.834849E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.686736E+10 | 0.00 | 0.00 | 0.554815E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.430756E+10 | 0.00 | 0.00 | 0.518202E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 24125481.82 | 0.896698E+09 | 0.00 | 1004782.53 | 0.180480E+09 | 0.00 | 34434098.15 | 0.00 | 0.35 |
November | 0.225657E+09 | 29143319.56 | 0.00 | 3281157.82 | 25909912.64 | 0.00 | 0.209380E+09 | 0.00 | 0.28 |
December | 0.922861E+09 | 0.00 | 0.00 | 978156.97 | 2418667.98 | 313085.65 | 0.174996E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.297613E+10 | 0.281359E+11 | 0.00 | 9676885.04 | 0.327437E+10 | 79742318.87 | 0.811230E+09 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 268648.61 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.112155E+10 | 0.686736E+10 | 0.00 | 3281157.82 | 0.834849E+09 | 79266638.88 | 0.209380E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.565525E+09 | 85994.84 | 0.00 | 1081891.32 | 84605.64 | 23944719.69 | 0.282389E+09 | 0.00 | 0.30 |
February | 0.239823E+09 | 3370416.90 | 0.00 | 2373474.95 | 2717561.93 | 0.00 | 0.309277E+09 | 0.00 | 0.35 |
March | 57717059.77 | 0.155606E+09 | 0.00 | 3207035.31 | 26855535.57 | 0.00 | 0.229464E+09 | 0.00 | 0.44 |
April | 4798514.87 | 0.937679E+09 | 0.00 | 870545.84 | 77668404.06 | 0.00 | 16535128.03 | 0.00 | 0.53 |
May | 170539.62 | 0.285011E+10 | 0.00 | 16490.57 | 0.150330E+09 | 0.00 | 612587.19 | 0.00 | 0.63 |
June | 0.00 | 0.395489E+10 | 0.00 | 0.00 | 0.272457E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.514183E+10 | 0.00 | 0.00 | 0.410046E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.507429E+10 | 0.00 | 0.00 | 0.245880E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.339119E+10 | 0.00 | 0.00 | 0.260379E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 11738829.10 | 0.811242E+09 | 0.00 | 1174419.69 | 71337969.63 | 0.00 | 39155903.05 | 0.00 | 0.47 |
November | 90690796.52 | 27174931.06 | 0.00 | 4067755.94 | 16095885.49 | 0.00 | 0.294815E+09 | 0.00 | 0.39 |
December | 0.443327E+09 | 385105.70 | 0.00 | 1938621.18 | 1181926.90 | 0.00 | 0.371033E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.141379E+10 | 0.223479E+11 | 0.00 | 14730234.81 | 0.153503E+10 | 23944719.69 | 0.154328E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 85994.84 | 0.00 | 0.00 | 84605.64 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.565525E+09 | 0.514183E+10 | 0.00 | 4067755.94 | 0.410046E+09 | 23944719.69 | 0.371033E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.812388E+09 | 367443.10 | 0.00 | 3085954.71 | 109130.41 | 0.390187E+09 | 0.642855E+09 | 0.00 | 0.42 |
February | 0.359705E+09 | 13164913.24 | 0.00 | 5469532.17 | 2223610.08 | 0.167400E+09 | 0.521536E+09 | 0.00 | 0.46 |
March | 97783880.49 | 0.385184E+09 | 0.00 | 5259306.22 | 21434428.73 | 23562628.61 | 0.333190E+09 | 0.00 | 0.51 |
April | 11908782.39 | 0.157903E+10 | 0.00 | 1036075.58 | 0.137927E+09 | 0.00 | 13764266.47 | 0.00 | 0.55 |
May | 249837.58 | 0.453950E+10 | 0.00 | 31638.86 | 0.332790E+09 | 0.00 | 1274499.62 | 0.00 | 0.62 |
June | 0.00 | 0.662551E+10 | 0.00 | 0.00 | 0.517263E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.833136E+10 | 0.00 | 0.00 | 0.816554E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.890853E+10 | 0.00 | 0.00 | 0.465554E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.627686E+10 | 0.00 | 0.00 | 0.368222E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 29672397.34 | 0.183202E+10 | 0.00 | 1691537.78 | 70557054.73 | 0.00 | 41829893.99 | 0.00 | 0.62 |
November | 0.132359E+09 | 0.126428E+09 | 0.00 | 10588762.55 | 6957840.83 | 38121401.10 | 0.618715E+09 | 0.00 | 0.61 |
December | 0.596026E+09 | 3844550.48 | 0.00 | 5281494.36 | 514210.32 | 0.241088E+09 | 0.858382E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.204009E+10 | 0.386218E+11 | 0.00 | 32444302.24 | 0.274011E+10 | 0.860358E+09 | 0.303155E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 367443.10 | 0.00 | 0.00 | 109130.41 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.812388E+09 | 0.890853E+10 | 0.00 | 10588762.55 | 0.816554E+09 | 0.390187E+09 | 0.858382E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.637814E+09 | 109796.33 | 0.00 | 1057831.56 | 84345.88 | 30292729.88 | 0.221064E+09 | 0.00 | 0.31 |
February | 0.295383E+09 | 6647195.00 | 0.00 | 1871270.70 | 1743590.80 | 0.00 | 0.201286E+09 | 0.00 | 0.33 |
March | 66575232.57 | 0.187864E+09 | 0.00 | 2659672.10 | 18270151.53 | 0.00 | 0.191571E+09 | 0.00 | 0.42 |
April | 5860076.74 | 0.993542E+09 | 0.00 | 528930.24 | 64429850.84 | 0.00 | 8772023.30 | 0.00 | 0.53 |
May | 157885.62 | 0.293629E+10 | 0.00 | 19881.40 | 0.128713E+09 | 0.00 | 708362.77 | 0.00 | 0.62 |
June | 0.00 | 0.424292E+10 | 0.00 | 0.00 | 0.240698E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.522113E+10 | 0.00 | 0.00 | 0.363427E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.519657E+10 | 0.00 | 0.00 | 0.210503E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.354649E+10 | 0.00 | 0.00 | 0.215323E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 12495397.92 | 0.846588E+09 | 0.00 | 868508.28 | 68277473.50 | 0.00 | 29732071.94 | 0.00 | 0.46 |
November | 0.101496E+09 | 39749105.45 | 0.00 | 3540979.47 | 11604652.97 | 0.00 | 0.239285E+09 | 0.00 | 0.38 |
December | 0.495693E+09 | 572310.69 | 0.00 | 1752320.09 | 1178298.13 | 0.00 | 0.299719E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.161547E+10 | 0.232185E+11 | 0.00 | 12299393.84 | 0.132425E+10 | 30292729.88 | 0.119214E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 109796.33 | 0.00 | 0.00 | 84345.88 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.637814E+09 | 0.522113E+10 | 0.00 | 3540979.47 | 0.363427E+09 | 30292729.88 | 0.299719E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104701E+10 | 0.00 | 0.00 | 334867.08 | 897805.57 | 0.135929E+09 | 0.105859E+09 | 0.00 | 0.29 |
February | 0.523591E+09 | 5169747.52 | 0.00 | 1841938.47 | 5144227.57 | 1072882.36 | 0.209484E+09 | 0.00 | 0.30 |
March | 0.116386E+09 | 0.198050E+09 | 0.00 | 3532120.40 | 48962898.51 | 0.00 | 0.255025E+09 | 0.00 | 0.36 |
April | 10511895.06 | 0.110895E+10 | 0.00 | 1192398.55 | 0.162752E+09 | 0.00 | 20377899.20 | 0.00 | 0.45 |
May | 293436.25 | 0.381253E+10 | 0.00 | 42355.81 | 0.288746E+09 | 0.00 | 861641.51 | 0.00 | 0.55 |
June | 0.00 | 0.571399E+10 | 0.00 | 0.00 | 0.455779E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.722792E+10 | 0.00 | 0.00 | 0.654275E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.712156E+10 | 0.00 | 0.00 | 0.452840E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.437690E+10 | 0.00 | 0.00 | 0.449696E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 32576850.06 | 0.928174E+09 | 0.00 | 693142.90 | 0.147333E+09 | 0.00 | 14856832.38 | 0.00 | 0.36 |
November | 0.267421E+09 | 32686577.02 | 0.00 | 2812658.47 | 27371657.19 | 0.00 | 0.180579E+09 | 0.00 | 0.30 |
December | 0.958095E+09 | 0.00 | 0.00 | 807992.03 | 4832397.81 | 10649849.06 | 0.150477E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.295588E+10 | 0.305259E+11 | 0.00 | 11257473.70 | 0.269863E+10 | 0.147651E+09 | 0.937521E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 897805.57 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.104701E+10 | 0.722792E+10 | 0.00 | 3532120.40 | 0.654275E+09 | 0.135929E+09 | 0.255025E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.502382E+09 | 184049.81 | 0.00 | 854189.88 | 301699.77 | 47950734.13 | 0.235429E+09 | 0.00 | 0.27 |
February | 0.232163E+09 | 3761769.20 | 0.00 | 2425390.99 | 2994659.67 | 689254.59 | 0.334324E+09 | 0.00 | 0.37 |
March | 55837278.29 | 0.171191E+09 | 0.00 | 3726753.00 | 20790553.99 | 0.00 | 0.270748E+09 | 0.00 | 0.50 |
April | 4666291.79 | 0.103174E+10 | 0.00 | 1291588.08 | 65194984.24 | 0.00 | 24065021.34 | 0.00 | 0.62 |
May | 186335.82 | 0.306161E+10 | 0.00 | 28862.96 | 0.148388E+09 | 0.00 | 575909.01 | 0.00 | 0.70 |
June | 0.00 | 0.417468E+10 | 0.00 | 0.00 | 0.263432E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.513744E+10 | 0.00 | 0.00 | 0.363977E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.496715E+10 | 0.00 | 0.00 | 0.225452E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.325340E+10 | 0.00 | 0.00 | 0.232707E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 17119545.03 | 0.778267E+09 | 0.00 | 840606.58 | 59146616.37 | 0.00 | 20320942.29 | 0.00 | 0.47 |
November | 0.132870E+09 | 29334707.17 | 0.00 | 3073182.79 | 16424974.08 | 0.00 | 0.229851E+09 | 0.00 | 0.39 |
December | 0.451720E+09 | 868711.43 | 0.00 | 1293286.39 | 2050725.77 | 2377789.35 | 0.270722E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.139694E+10 | 0.226096E+11 | 0.00 | 13533860.66 | 0.140086E+10 | 51017778.07 | 0.138604E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 184049.81 | 0.00 | 0.00 | 301699.77 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.502382E+09 | 0.513744E+10 | 0.00 | 3726753.00 | 0.363977E+09 | 47950734.13 | 0.334324E+09 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.738922E+09 | 1377797.59 | 0.00 | 5881434.15 | 204052.79 | 52815724.28 | 0.130747E+10 | 0.00 | 0.54 |
February | 0.370219E+09 | 16485565.66 | 0.00 | 7186563.22 | 2301521.65 | 390214.47 | 0.825049E+09 | 0.00 | 0.56 |
March | 98845708.07 | 0.371254E+09 | 0.00 | 6728806.96 | 17690837.02 | 0.00 | 0.468637E+09 | 0.00 | 0.57 |
April | 10234532.62 | 0.148315E+10 | 0.00 | 1607922.70 | 0.112933E+09 | 0.00 | 26612061.90 | 0.00 | 0.55 |
May | 294461.82 | 0.397272E+10 | 0.00 | 42476.16 | 0.288271E+09 | 0.00 | 861469.86 | 0.00 | 0.57 |
June | 0.00 | 0.564651E+10 | 0.00 | 0.00 | 0.472943E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.725589E+10 | 0.00 | 0.00 | 0.673421E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.758655E+10 | 0.00 | 0.00 | 0.407666E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.545481E+10 | 0.00 | 0.00 | 0.351353E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 26704555.13 | 0.171549E+10 | 0.00 | 1358881.06 | 62185472.48 | 0.00 | 29022605.32 | 0.00 | 0.61 |
November | 0.176984E+09 | 0.146601E+09 | 0.00 | 9459424.17 | 6996080.55 | 0.00 | 0.651671E+09 | 0.00 | 0.65 |
December | 0.616269E+09 | 9221888.66 | 0.00 | 7075650.26 | 976235.68 | 1364186.57 | 0.135039E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.203847E+10 | 0.336601E+11 | 0.00 | 39341158.68 | 0.239694E+10 | 54570125.31 | 0.465972E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 1377797.59 | 0.00 | 0.00 | 204052.79 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.738922E+09 | 0.758655E+10 | 0.00 | 9459424.17 | 0.673421E+09 | 52815724.28 | 0.135039E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.593314E+09 | 415462.16 | 0.00 | 1153964.44 | 256528.74 | 79151617.60 | 0.256223E+09 | 0.00 | 0.34 |
February | 0.303036E+09 | 9392799.60 | 0.00 | 2234502.47 | 1655228.24 | 812110.57 | 0.249669E+09 | 0.00 | 0.38 |
March | 68489299.92 | 0.215827E+09 | 0.00 | 3483740.96 | 16211338.32 | 0.00 | 0.255658E+09 | 0.00 | 0.51 |
April | 6222820.75 | 0.111834E+10 | 0.00 | 1036309.40 | 59396221.64 | 0.00 | 16125465.65 | 0.00 | 0.64 |
May | 146808.24 | 0.327898E+10 | 0.00 | 32544.27 | 0.129939E+09 | 0.00 | 664228.31 | 0.00 | 0.72 |
June | 0.00 | 0.463442E+10 | 0.00 | 0.00 | 0.235469E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.540050E+10 | 0.00 | 0.00 | 0.331311E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.531238E+10 | 0.00 | 0.00 | 0.201513E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.355606E+10 | 0.00 | 0.00 | 0.199302E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 19460970.35 | 0.856875E+09 | 0.00 | 570047.39 | 57228924.50 | 0.00 | 12679756.76 | 0.00 | 0.48 |
November | 0.147834E+09 | 44508836.15 | 0.00 | 3006491.49 | 12397612.62 | 0.00 | 0.193250E+09 | 0.00 | 0.40 |
December | 0.544036E+09 | 1320024.13 | 0.00 | 1511523.37 | 2247820.12 | 6131740.17 | 0.264158E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.168254E+10 | 0.244290E+11 | 0.00 | 13029123.79 | 0.124693E+10 | 86095468.35 | 0.124843E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 415462.16 | 0.00 | 0.00 | 256528.74 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.593314E+09 | 0.540050E+10 | 0.00 | 3483740.96 | 0.331311E+09 | 79151617.60 | 0.264158E+09 | 0.00 | 0.73 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.164504E+12 | 0.419361E+10 | 0.00 | 0.676532E+11 | 0.413794E+11 |
February | 0.183224E+12 | 0.294316E+10 | 0.00 | 0.386563E+11 | 0.752456E+11 |
March | 0.242645E+12 | 0.553250E+09 | 0.00 | 0.808906E+10 | 0.167590E+12 |
April | 0.260124E+12 | -0.330735E+10 | 0.00 | -0.382735E+11 | 0.266442E+12 |
May | 0.270333E+12 | -0.959368E+10 | 0.00 | -0.102403E+12 | 0.399249E+12 |
June | 0.249368E+12 | -0.115111E+11 | 0.00 | -0.152865E+12 | 0.445474E+12 |
July | 0.207916E+12 | -0.163027E+11 | 0.00 | -0.204154E+12 | 0.466967E+12 |
August | 0.178515E+12 | -0.149551E+11 | 0.00 | -0.207000E+12 | 0.454743E+12 |
September | 0.195458E+12 | -0.957789E+10 | 0.00 | -0.153328E+12 | 0.357769E+12 |
October | 0.195242E+12 | -0.231282E+10 | 0.00 | -0.348055E+11 | 0.235340E+12 |
November | 0.173765E+12 | 0.108444E+10 | 0.00 | 0.236733E+11 | 0.130124E+12 |
December | 0.150072E+12 | 0.379022E+10 | 0.00 | 0.621091E+11 | 0.552476E+11 |
Annual Sum or Average | 0.247117E+13 | -0.549960E+11 | 0.00 | -0.692648E+12 | 0.309557E+13 |
Minimum of Months | 0.150072E+12 | -0.163027E+11 | 0.00 | -0.207000E+12 | 0.413794E+11 |
Maximum of Months | 0.270333E+12 | 0.419361E+10 | 0.00 | 0.676532E+11 | 0.466967E+12 |