Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:32:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1565.04 | 314.13 | 314.13 |
Net Site Energy | 1428.96 | 286.81 | 286.81 |
Total Source Energy | 4336.44 | 870.39 | 870.39 |
Net Source Energy | 3905.48 | 783.89 | 783.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 130.87 | 167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 190.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 85.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 130.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1267.37 | 297.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 130.87 | 167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 190.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 167.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 85.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 130.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 130.87 | 167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 190.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 167.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 85.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 130.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 81.68 | 59.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 254.38 | 59.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 81.68 | 59.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 254.38 | 59.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 142.412 | 11.24 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -6.34 | -0.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 136.076 | 10.74 |
Electricity Coming From Utility | 1132.142 | 89.33 |
Surplus Electricity Going To Utility | 0.846 | 0.07 |
Net Electricity From Utility | 1131.296 | 89.26 |
Total On-Site and Utility Electric Sources | 1267.372 | 100.00 |
Total Electricity End Uses | 1267.372 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 256.50 |
Time Setpoint Not Met During Occupied Cooling | 120.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2598.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 06-FEB-08:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 195134.77 | 86586.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6679.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9408.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 230126.34 | 95995.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 195134.77 | 86586.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2981.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 36.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6679.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9408.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 414.46 | 181.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 603.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 528.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 270.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 141.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4013.77 | 322.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 83.19 | 36.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 805.62 | 64.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 83.19 | 36.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 805.62 | 64.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.29 | 0.326569 | 0.278000 | 0.637993 | 0.870850 | 0.500000 | 0.001167 |
CORE_MID VAV BOX COMPONENT | 1.92 | 0.389470 | 0.331000 | 0.636941 | 1.00 | 0.500000 | 0.000978 |
CORE_TOP VAV BOX COMPONENT | 2.07 | 0.362564 | 0.308000 | 0.636667 | 0.966836 | 0.500000 | 0.001051 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.668926 | 0.236187 | 0.201000 | 0.134454 | 0.629832 | 0.500000 | 0.001613 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.734391 | 0.136197 | 0.116000 | 0.085189 | 0.363192 | 0.500000 | 0.002797 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.907471 | 0.174101 | 0.148000 | 0.134306 | 0.464269 | 0.500000 | 0.002188 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.795727 | 0.125690 | 0.107000 | 0.085143 | 0.335174 | 0.500000 | 0.003031 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.524001 | 0.301510 | 0.256000 | 0.134144 | 0.804028 | 0.500000 | 0.001264 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.604415 | 0.165485 | 0.141000 | 0.085223 | 0.441294 | 0.500000 | 0.002302 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.727913 | 0.217048 | 0.184000 | 0.133936 | 0.578794 | 0.500000 | 0.001755 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.621681 | 0.160879 | 0.137000 | 0.085170 | 0.429010 | 0.500000 | 0.002368 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.580163 | 0.272323 | 0.231000 | 0.134018 | 0.726194 | 0.500000 | 0.001399 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.715101 | 0.372989 | 0.500000 | 0.002724 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.821251 | 0.192379 | 0.164000 | 0.134685 | 0.513011 | 0.500000 | 0.001980 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.734506 | 0.136167 | 0.116000 | 0.085203 | 0.363111 | 0.500000 | 0.002798 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21298.17 |
CORE_MID VAV BOX REHEAT COIL | 21737.87 |
CORE_TOP VAV BOX REHEAT COIL | 37095.07 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18689.29 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12161.78 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18558.61 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12240.95 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13770.51 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9006.75 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13657.33 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9080.87 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 14885.03 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9726.28 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 14759.23 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9801.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.39 | 1.08 | 4.77 | 1.79 | 4.26 | 4.26 | 0.300000 | 0.420039 | 4.26 |
PACU_VAV_MID | 2.39 | 1.08 | 4.78 | 2.12 | 4.08 | 4.08 | 0.300000 | 0.520932 | 4.08 |
PACU_VAV_TOP | 2.59 | 1.08 | 5.17 | 2.96 | 4.74 | 4.74 | 0.300000 | 0.623791 | 4.74 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.26 |
PACU_VAV_MID_OA_CONTROLLER | 4.08 |
PACU_VAV_TOP_OA_CONTROLLER | 4.74 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.26 | 93069.13 | 0.743377 | 1.42 | 31019.94 | 0.743377 |
PACU_VAV_MID COOLING COIL | 4.08 | 90486.78 | 0.737248 | 1.36 | 30159.24 | 0.737248 |
PACU_VAV_TOP COOLING COIL | 4.74 | 101657.17 | 0.749887 | 1.58 | 33882.33 | 0.749887 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 23991.04 |
PACU_VAV_MID HEATING COIL | 24525.24 |
PACU_VAV_TOP HEATING COIL | 24216.11 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.26 |
PACU_VAV_MID FAN | 4.08 |
PACU_VAV_TOP FAN | 4.74 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5960 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5902 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7087 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.444 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.460 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.177 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.34210526E-12 | 0.10412655E-14 | -0.10417952E-12 | 0.10409145E-15 |
43 | 6 | 0.30802088E-07 | 0.17108976E-09 | 0.70383009E-08 | -0.14667926E-12 |
44 | 5 | -0.20086572E-03 | 0.14450046E-05 | -0.10316412E-03 | 0.69507809E-08 |
45 | 4 | 0.30464713 | 0.69501731E-03 | 0.10418329 | -0.35343869E-04 |
46 | 3 | -7.5136835 | 0.21306369E-01 | -2.4123261 | 0.30221796E-01 |
47 | 2 | 41.686696 | 0.75037385E-01 | 15.565716 | -0.34242481 |
48 | 1 | -81.170502 | 0.33581009E-01 | -29.411065 | 1.0919325 |
49 | 0 | 46.824335 | 0.67004661E-03 | 16.284887 | |
50 | 7 | -0.34244365E-12 | 0.92212740E-15 | -0.10449257E-12 | 0.10448628E-15 |
51 | 6 | 0.30869821E-07 | 0.16952917E-09 | 0.70532514E-08 | -0.14704533E-12 |
52 | 5 | -0.20120586E-03 | 0.14312561E-05 | -0.10333395E-03 | 0.69653235E-08 |
53 | 4 | 0.30503960 | 0.68816038E-03 | 0.10432471 | -0.35399819E-04 |
54 | 3 | -7.5214432 | 0.21089521E-01 | -2.4146296 | 0.30259860E-01 |
55 | 2 | 41.712273 | 0.74252889E-01 | 15.575132 | -0.34270975 |
56 | 1 | -81.190086 | 0.33221761E-01 | -29.419498 | 1.0923499 |
57 | 0 | 46.824335 | 0.66271842E-03 | 16.284691 | |
58 | 7 | -0.32374075E-12 | 0.12045207E-14 | -0.10360241E-12 | 0.16221974E-15 |
59 | 6 | 0.29475593E-07 | 0.20098913E-09 | 0.67455071E-08 | -0.13952197E-12 |
60 | 5 | -0.19418177E-03 | 0.17111334E-05 | -0.99823337E-04 | 0.66657971E-08 |
61 | 4 | 0.29690150 | 0.82890285E-03 | 0.10139402 | -0.34243177E-04 |
62 | 3 | -7.3604632 | 0.25571829E-01 | -2.3668478 | 0.29470418E-01 |
63 | 2 | 41.181572 | 0.90565943E-01 | 15.379610 | -0.33679792 |
64 | 1 | -80.783638 | 0.40729985E-01 | -29.244332 | 1.0836880 |
65 | 0 | 46.824337 | 0.81662197E-03 | 16.288791 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1124E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1187E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2194E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2249E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8114E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8556E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1337E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1567E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1563 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9739E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1765 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9275E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1119 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6836E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5658E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7130E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1124E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1190E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2194E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2251E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8115E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8575E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1335E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1565E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7428E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9320E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2596E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5853E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6333E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3432E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3611E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5268E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1671E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1914E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7866E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8041E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6390E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6450E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8245E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8324E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3163E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3697E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6094E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6519E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1524E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1828E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1335E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1565E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0803E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3362E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1402E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7783E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9035E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2280E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5658E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7130E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3164E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3700E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6094E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6517E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1521E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1813E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1337E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1567E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4526E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7922E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9000E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4113E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3865E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2276E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3611E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5268E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9946E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0637E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5721E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6477E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4945E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5233E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8247E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8326E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1550 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.6090E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1720 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1070 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1194 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9373E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2056E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4300E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5226E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8067E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0667E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4757E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4791E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2519E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2614E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4669E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6586E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0538E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6548E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3959E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4190E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7955E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2056E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4300E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2420E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6743E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7191E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3111E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2399E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1418E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2615E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4670E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1550 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.6081E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1720 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1069 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1194 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9365E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2051E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4297E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5225E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8064E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0666E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4754E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4787E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2515E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2609E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4667E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6588E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0537E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6549E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3958E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4187E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7954E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2051E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4297E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2419E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6741E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7190E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3109E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2395E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1415E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2610E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4667E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 31857.27117 | 31857.27117 | 2.29494 | 2.29494 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8675.61937 | 8675.61937 | 0.36536 | 0.42469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26735.84800 | 26735.84800 | 1.92429 | 1.92429 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 15373.82274 | 15373.82274 | 0.65116 | 0.65116 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28436.99731 | 28436.99731 | 2.06710 | 2.06710 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 26127.86864 | 26127.86864 | 1.11119 | 1.11119 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9201.52757 | 9201.52757 | 0.66893 | 0.66893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 13123.76116 | 13123.76116 | 0.55984 | 0.55984 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10102.09638 | 10102.09638 | 0.73439 | 0.73439 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8539.59603 | 8539.59603 | 0.36431 | 0.36431 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12482.93722 | 12482.93722 | 0.90747 | 0.90747 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 13032.22842 | 13032.22842 | 0.55593 | 0.55593 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10945.85073 | 10945.85073 | 0.79573 | 0.79573 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8595.05500 | 8595.05500 | 0.36668 | 0.36668 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7208.30174 | 7208.30174 | 0.52400 | 0.52400 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9676.87298 | 9676.87298 | 0.41250 | 0.41250 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8314.56375 | 8314.56375 | 0.60442 | 0.60442 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6328.62185 | 6328.62185 | 0.26980 | 0.26980 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10013.41246 | 10013.41246 | 0.72791 | 0.72791 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9597.61333 | 9597.61333 | 0.40911 | 0.40911 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8552.08296 | 8552.08296 | 0.62168 | 0.62168 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6380.52802 | 6380.52802 | 0.27202 | 0.27202 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7980.65320 | 7980.65320 | 0.58016 | 0.58016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 10458.38618 | 10458.38618 | 0.44589 | 0.44589 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9836.91059 | 9836.91059 | 0.71510 | 0.71510 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.41123E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6833.18801 | 6833.18801 | 0.29135 | 0.29135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11297.07434 | 11297.07434 | 0.82125 | 0.82125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10370.27146 | 10370.27146 | 0.44212 | 0.44212 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10103.85459 | 10103.85459 | 0.73451 | 0.73451 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6885.55757 | 6885.55757 | 0.29359 | 0.29359 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 67025.03 | 4.25703 | 4.25703 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 26947.21 | 1.78812 | 1.78812 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64592.90 | 4.07753 | 4.07753 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 26954.71 | 2.12411 | 2.12411 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73582.46 | 4.74190 | 4.74190 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 26649.61 | 2.95795 | 2.95795 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.29494 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32657 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63799 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87085 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16668E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21298.17463 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.92429 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38947 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63694 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.78252E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21737.87402 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.06710 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36256 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63667 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96684 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05085E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 37095.06526 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66893 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23619 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13445 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62983 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61313E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18689.28772 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73439 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13620 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51894E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36319 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79742E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12161.77521 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90747 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17410 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14800 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13431 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46427 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18838E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18558.61424 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79573 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12569 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10700 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51428E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33517 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03126E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12240.95084 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52400 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30151 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13414 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80403 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26364E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13770.51119 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60442 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16549 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14100 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52225E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44129 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30232E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9006.75246 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72791 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21705 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13394 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57879 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75538E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13657.33116 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62168 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16088 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51702E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42901 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36824E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9080.87228 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58016 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27232 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13402 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72619 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39908E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14885.03471 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71510 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37299 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72394E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9726.28315 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82125 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19238 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16400 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13469 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51301 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98046E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14759.23068 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73451 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13617 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52027E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36311 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79804E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9801.05411 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38647 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07647 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.77295 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.78812 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.25703 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.25703 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.42004 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38766 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07594 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.77532 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.12411 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.07753 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.07753 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.52093 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.58681 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07576 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.17361 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.95795 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.74190 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.74190 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.62379 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.25703 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.07753 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.74190 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.25703 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.25703 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93069.12802 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74338 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.41887 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31019.94037 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74338 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 23991.04345 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.25703 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.07753 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.07753 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 90486.77619 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73725 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.35904 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30159.24250 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73725 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 24525.24259 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.07753 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.74190 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.74190 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 101657.17018 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74989 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58047 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33882.33482 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74989 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 24216.11138 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.74190 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 92523.41 | 315702.97 | 11.88 | 3.05 | 3.40 | 3.58 | 3.75 | 10.42 | 11.61 | 12.23 | 12.79 | 4.9214 | 3.9217 | 2.6364 | 1.0884 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 90003.67 | 307105.26 | 11.92 | 3.06 | 3.41 | 3.60 | 3.75 | 10.44 | 11.65 | 12.27 | 12.81 | 4.7139 | 3.7442 | 2.5245 | 1.0486 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 100989.91 | 344591.89 | 11.84 | 3.04 | 3.39 | 3.57 | 3.74 | 10.39 | 11.57 | 12.18 | 12.76 | 5.4819 | 4.3699 | 2.9362 | 1.2061 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.8104015798E-002 | 1.6643822456E-002 | Pass | Pass | 0.4891550769 | 0.4956677506 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1617549530 | 0.1204026490 | Pass | Pass | 0.5284949727 | 0.5008698925 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.2760628467E-002 | 5.2429875955E-002 | Pass | Pass | 0.4965248903 | 0.4863617624 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.5438887921E-002 | 4.6431272763E-002 | Pass | Pass | 0.4879043596 | 0.4827416356 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.0537969625E-002 | 1.1615424801E-002 | Pass | Pass | 1.4781116315 | 7.7335177710 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1135172817 | 0.1287934755 | Pass | Pass | 4.9613306430 | 21.8224133745 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6363783380 | 0.5793869908 | Pass | Pass | 0.7096616971 | 0.6108857367 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5769221980 | 0.6195472611 | Pass | Pass | 0.8780163664 | 1.0258036159 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4777062422 | 0.5599052418 | Pass | Pass | 1.4866431490 | 6.6814323216 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6355879701 | 0.6493533624 | Pass | Pass | 0.8356915778 | 1.0029973942 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4097087947 | 0.3898317579 | Pass | Pass | 7.2464329315 | 49.2238833766 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3289564856 | 0.3870482270 | Pass | Pass | 11.7153216788 | 93.0614283488 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2419920019 | 0.2786769093 | Pass | Pass | 2.6242962610 | 18.3893174452 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4005739062 | 0.4144120024 | Pass | Pass | 23.0275552855 | 189.5091623786 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4902576912 | 0.4578795029 | Pass | Pass | 0.7594712224 | 0.6722451639 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4333709929 | 0.4881759666 | Pass | Pass | 8.8830535667 | 87.9908942929 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3684332907 | 0.4177884105 | Pass | Pass | 4.8926296694 | 37.5752972375 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4914132418 | 0.5043753349 | Pass | Pass | 15.4500010837 | 174.5268627047 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3534.25 | 132.99 | 0.00 | 1393.85 | 1025.87 | 6086.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.67 | 0.0000 | Y | 4.89 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.60 | 0.0000 | Y | 3.09 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.39 | 0.0000 | Y | 4.83 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.43 | 0.0000 | Y | 3.06 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.62 | 0.0000 | Y | 4.88 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.57 | 0.0000 | Y | 3.08 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.36 | 0.0000 | Y | 4.83 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.40 | 0.0000 | Y | 3.06 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.67 | 0.0000 | Y | 4.89 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.60 | 0.0000 | Y | 3.09 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.39 | 0.0000 | Y | 4.83 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.43 | 0.0000 | Y | 3.06 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 167.00 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.43 | 42.43 | 4.32 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.64 | 63.04 | 3.32 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.64 | 46.90 | 26.43 | |
Exterior Lighting Total | 3824.74 | 34.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93069.13 | 69185.44 | 23883.68 | 0.74 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 90486.78 | 66711.20 | 23775.58 | 0.74 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 101657.17 | 76231.43 | 25425.74 | 0.75 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 92523.4 | 3.05 | 10.42 | N/A | N/A | 11.88 | |
PACU_VAV_MID COOLING COIL | 90003.7 | 3.06 | 10.44 | N/A | N/A | 11.92 | |
PACU_VAV_TOP COOLING COIL | 100989.9 | 3.04 | 10.39 | N/A | N/A | 11.84 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21298.17 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21737.87 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 37095.07 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18689.29 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12161.78 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18558.61 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12240.95 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13770.51 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9006.75 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13657.33 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9080.87 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14885.03 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9726.28 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14759.23 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9801.05 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 23991.04 | 0.84 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 24525.24 | 0.84 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 24216.11 | 0.84 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.26 | 9318.69 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.08 | 8925.75 | 2189.01 | 1.00 | 1.15 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.74 | 10380.07 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 92523.41 | 3.05 | 10.42 | 11.88 | 4.9214 | 3.40 | 11.61 | 3.9217 | 3.58 | 12.23 | 2.6364 | 3.75 | 12.79 | 1.0884 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 90003.67 | 3.06 | 10.44 | 11.92 | 4.7139 | 3.41 | 11.65 | 3.7442 | 3.60 | 12.27 | 2.5245 | 3.75 | 12.81 | 1.0486 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 100989.91 | 3.04 | 10.39 | 11.84 | 5.4819 | 3.39 | 11.57 | 4.3699 | 3.57 | 12.18 | 2.9362 | 3.74 | 12.76 | 1.2061 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 31857.27 | 31857.27 | 32.39 | 2.295 | 2.295 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_MID | 26735.85 | 26735.85 | 27.18 | 1.924 | 1.924 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_TOP | 28437.00 | 28437.00 | 28.91 | 2.067 | 2.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00892 | 32.10 | 0.01412 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9201.53 | 9201.53 | 44.38 | 0.669 | 0.669 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00908 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10102.10 | 10102.10 | 76.96 | 0.734 | 0.734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00885 | 28.45 | 0.01411 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12482.94 | 12482.94 | 60.21 | 0.907 | 0.907 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00893 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10945.85 | 10945.85 | 83.39 | 0.796 | 0.796 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00882 | 31.26 | 0.01412 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7208.30 | 7208.30 | 34.77 | 0.524 | 0.524 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00906 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8314.56 | 8314.56 | 63.34 | 0.604 | 0.604 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00882 | 28.66 | 0.01411 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10013.41 | 10013.41 | 48.30 | 0.728 | 0.728 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00891 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8552.08 | 8552.08 | 65.16 | 0.622 | 0.622 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00881 | 31.06 | 0.01412 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7980.65 | 7980.65 | 38.49 | 0.580 | 0.580 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00911 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9836.91 | 9836.91 | 74.94 | 0.715 | 0.715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00883 | 28.03 | 0.01411 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11297.07 | 11297.07 | 54.49 | 0.821 | 0.821 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00893 | 31.73 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10103.85 | 10103.85 | 76.98 | 0.735 | 0.735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00882 | 31.26 | 0.01412 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8675.62 | 8675.62 | 8.82 | 0.365 | 0.425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_MID | 15373.82 | 15373.82 | 15.63 | 0.651 | 0.651 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_TOP | 26127.87 | 26127.87 | 26.57 | 1.111 | 1.111 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13123.76 | 13123.76 | 63.30 | 0.560 | 0.560 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8539.60 | 8539.60 | 65.06 | 0.364 | 0.364 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00731 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13032.23 | 13032.23 | 62.85 | 0.556 | 0.556 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8595.05 | 8595.05 | 65.48 | 0.367 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00731 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9676.87 | 9676.87 | 46.67 | 0.412 | 0.412 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6328.62 | 6328.62 | 48.21 | 0.270 | 0.270 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9597.61 | 9597.61 | 46.29 | 0.409 | 0.409 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6380.53 | 6380.53 | 48.61 | 0.272 | 0.272 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10458.39 | 10458.39 | 50.44 | 0.446 | 0.446 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00728 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6833.19 | 6833.19 | 52.06 | 0.291 | 0.291 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00727 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10370.27 | 10370.27 | 50.02 | 0.442 | 0.442 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00727 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6885.56 | 6885.56 | 52.46 | 0.294 | 0.294 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00727 | -10.70 | 0.00150 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.26 | 4.26 | 1.79 | 1.79 | 4.2570 | 1.7881 | 4.2570 | 0.4200 | 0.3000 |
PACU_VAV_MID | 4.08 | 4.08 | 2.12 | 2.12 | 4.0775 | 2.1241 | 4.0775 | 0.5209 | 0.3000 |
PACU_VAV_TOP | 4.74 | 4.74 | 2.96 | 2.96 | 4.7419 | 2.9580 | 4.7419 | 0.6238 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21298.175 | 21298.175 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21298.17 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 8675.62 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21737.874 | 21737.874 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21737.87 | 21737.87 | 0.651164 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 15373.82 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 37095.065 | 37095.065 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37095.07 | 37095.07 | 1.111193 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 26127.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18689.288 | 18689.288 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18689.29 | 18689.29 | 0.559843 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732289 | 47.3787 | 13123.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12161.775 | 12161.775 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12161.78 | 12161.78 | 0.364309 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00730889 | 47.2896 | 8539.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18558.614 | 18558.614 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18558.61 | 18558.61 | 0.555928 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731844 | 47.3502 | 13032.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12240.951 | 12240.951 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12240.95 | 12240.95 | 0.366681 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731303 | 47.3160 | 8595.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13770.511 | 13770.511 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13770.51 | 13770.51 | 0.412500 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00744854 | 48.1787 | 9676.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9006.752 | 9006.752 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9006.75 | 9006.75 | 0.269800 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00744848 | 48.1784 | 6328.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13657.331 | 13657.331 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13657.33 | 13657.33 | 0.409109 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00744154 | 48.1340 | 9597.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9080.872 | 9080.872 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9080.87 | 9080.87 | 0.272020 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00745480 | 48.2187 | 6380.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 14885.035 | 14885.035 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14885.03 | 14885.03 | 0.445885 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00727739 | 47.0867 | 10458.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9726.283 | 9726.283 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9726.28 | 9726.28 | 0.291354 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00726854 | 47.0304 | 6833.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 14759.231 | 14759.231 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14759.23 | 14759.23 | 0.442117 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00727085 | 47.0450 | 10370.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9801.054 | 9801.054 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9801.05 | 9801.05 | 0.293593 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00727428 | 47.0671 | 6885.56 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 93069.128 | 69185.445 | 4.257033 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 95130.39 | 74301.41 | 4.257033 | 25.82 | 18.33 | 0.01009695 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 22.4593 | 24.00 | 0.00893179 | 48.0293 | 58562.41 | 0.00 | 95966.76 | 70259.73 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 23991.043 | 23991.043 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23991.04 | 23991.04 | 1.277110 | -2.73 | -2.74 | 0.00300001 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 74.8644 | 17.63 | 0.00719527 | 57.4210 | 14945.39 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 90486.776 | 66711.200 | 4.077526 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 92720.62 | 71496.02 | 4.077526 | 25.90 | 18.44 | 0.01020053 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 23.4480 | 24.00 | 0.00900010 | 48.3921 | 56091.79 | 0.00 | 93304.01 | 67756.68 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 24525.243 | 24525.243 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24525.24 | 24525.24 | 1.223258 | -3.78 | -3.78 | 0.00274811 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 78.1601 | 17.54 | 0.00695354 | 55.8322 | 17421.73 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 101657.170 | 76231.429 | 4.741897 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 103578.18 | 81807.14 | 4.741897 | 25.63 | 18.19 | 0.00999640 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 20.1628 | 24.00 | 0.00895492 | 48.1528 | 65222.46 | 0.00 | 104822.19 | 77393.13 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 24216.111 | 24216.111 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24216.11 | 24216.11 | 1.422569 | -1.27 | -1.45 | 0.00328549 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 67.2094 | 15.85 | 0.00709775 | 63.4485 | 15364.17 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21298.175 | 21298.175 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21298.17 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21298.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 8675.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21737.874 | 21737.874 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21737.87 | 21737.87 | 1.0000 | 0.78373782 | 0.651164 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21737.87 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 15373.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 37095.065 | 37095.065 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37095.07 | 37095.07 | 1.0000 | 1.33742635 | 1.111193 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37095.07 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 26127.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18689.288 | 18689.288 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18689.29 | 18689.29 | 1.0000 | 0.67382402 | 0.559843 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18689.29 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732289 | 21.00 | 0.00732289 | 47.3787 | 13123.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12161.775 | 12161.775 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12161.78 | 12161.78 | 1.0000 | 0.43848093 | 0.364309 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12161.78 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00730889 | 21.00 | 0.00730889 | 47.2896 | 8539.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18558.614 | 18558.614 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18558.61 | 18558.61 | 1.0000 | 0.66911271 | 0.555928 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18558.61 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00731844 | 21.00 | 0.00731844 | 47.3502 | 13032.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12240.951 | 12240.951 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12240.95 | 12240.95 | 1.0000 | 0.44133553 | 0.366681 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12240.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00731303 | 21.00 | 0.00731303 | 47.3160 | 8595.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13770.511 | 13770.511 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13770.51 | 13770.51 | 1.0000 | 0.49648233 | 0.412500 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13770.51 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00744854 | 21.00 | 0.00744854 | 48.1787 | 9676.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9006.752 | 9006.752 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9006.75 | 9006.75 | 1.0000 | 0.32472966 | 0.269800 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9006.75 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00744848 | 21.00 | 0.00744848 | 48.1784 | 6328.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13657.331 | 13657.331 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13657.33 | 13657.33 | 1.0000 | 0.49240174 | 0.409109 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13657.33 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00744154 | 21.00 | 0.00744154 | 48.1340 | 9597.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9080.872 | 9080.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9080.87 | 9080.87 | 1.0000 | 0.32740198 | 0.272020 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9080.87 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00745480 | 21.00 | 0.00745480 | 48.2187 | 6380.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14885.035 | 14885.035 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14885.03 | 14885.03 | 1.0000 | 0.53666539 | 0.445885 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14885.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00727739 | 21.00 | 0.00727739 | 47.0867 | 10458.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9726.283 | 9726.283 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9726.28 | 9726.28 | 1.0000 | 0.35067164 | 0.291354 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9726.28 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00726854 | 21.00 | 0.00726854 | 47.0304 | 6833.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14759.231 | 14759.231 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14759.23 | 14759.23 | 1.0000 | 0.53212965 | 0.442117 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14759.23 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00727085 | 21.00 | 0.00727085 | 47.0450 | 10370.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9801.054 | 9801.054 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9801.05 | 9801.05 | 1.0000 | 0.35336743 | 0.293593 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9801.05 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00727428 | 21.00 | 0.00727428 | 47.0671 | 6885.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93069.128 | 69185.445 | 4.257033 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6097 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.257033 | 5.12374301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 95130.39 | 74301.41 | 1.0221 | 5.12374301 | 4.257033 | 25.82 | 18.33 | 0.01009695 | 51679.4 | 11.02 | 11.02 | 0.00850000 | 32508.7 | -999.0 | -999.00 | -999.00 | -999.00 | 9318.691 | 85811.70 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 22.4593 | 24.00 | 0.00893179 | 24.00 | 0.00893179 | 48.0293 | 58562.41 | 0.00 | 95966.76 | 70259.73 | 4.92139389 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.70 | 12.69 | 0.00913663 | 35822.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23991.043 | 23991.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.257033 | 5.12374301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23991.04 | 23991.04 | 1.0000 | 1.53712290 | 1.277110 | -2.73 | -2.74 | 0.00300001 | 4742.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23991.04 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 74.8644 | 21.00 | 0.00745607 | 17.63 | 0.00719527 | 57.4210 | 14945.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 90486.776 | 66711.200 | 4.077526 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8023 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.077526 | 4.90768979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 92720.62 | 71496.02 | 1.0247 | 4.90768979 | 4.077526 | 25.90 | 18.44 | 0.01020053 | 52025.3 | 11.02 | 11.02 | 0.00850000 | 32509.1 | -999.0 | -999.00 | -999.00 | -999.00 | 8925.749 | 83794.87 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 23.4480 | 24.00 | 0.00900010 | 24.00 | 0.00900010 | 48.3921 | 56091.79 | 0.00 | 93304.01 | 67756.68 | 4.71387315 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.60 | 12.57 | 0.00905975 | 35528.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24525.243 | 24525.243 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.077526 | 4.90768979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24525.24 | 24525.24 | 1.0000 | 1.47230694 | 1.223258 | -3.78 | -3.78 | 0.00274811 | 3058.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24525.24 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 78.1601 | 21.00 | 0.00720089 | 17.54 | 0.00695354 | 55.8322 | 17421.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 101657.170 | 76231.429 | 4.741897 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4228 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.741897 | 5.70732385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 103578.18 | 81807.14 | 1.0189 | 5.70732385 | 4.741897 | 25.63 | 18.19 | 0.00999640 | 51232.7 | 11.02 | 11.02 | 0.00850000 | 32508.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10380.065 | 93198.11 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 20.1628 | 24.00 | 0.00895492 | 24.00 | 0.00895492 | 48.1528 | 65222.46 | 0.00 | 104822.19 | 77393.13 | 5.48192770 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.85 | 12.83 | 0.00922288 | 36201.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24216.111 | 24216.111 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.741897 | 5.70732385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24216.11 | 24216.11 | 1.0000 | 1.71219715 | 1.422569 | -1.27 | -1.45 | 0.00328549 | 6928.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24216.11 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 67.2094 | 18.04 | 0.00693715 | 15.85 | 0.00709775 | 63.4485 | 15364.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.26 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.08 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2390.00 | 2744.50 | 110.33 |
CORE_MID | 2525.83 | 3185.67 | 503.17 |
CORE_TOP | 3029.00 | 3409.67 | 1171.67 |
PERIMETER_TOP_ZN_3 | 3803.83 | 3754.50 | 2105.67 |
PERIMETER_TOP_ZN_2 | 3819.67 | 3536.50 | 1867.33 |
PERIMETER_TOP_ZN_1 | 3586.33 | 3308.17 | 1550.17 |
PERIMETER_TOP_ZN_4 | 3837.33 | 3561.17 | 1931.83 |
PERIMETER_BOT_ZN_3 | 3590.83 | 3754.50 | 1869.00 |
PERIMETER_BOT_ZN_2 | 3534.33 | 3350.50 | 1461.00 |
PERIMETER_BOT_ZN_1 | 3311.83 | 3640.50 | 1503.17 |
PERIMETER_BOT_ZN_4 | 3628.17 | 3399.83 | 1561.17 |
PERIMETER_MID_ZN_3 | 3546.50 | 3555.33 | 1711.00 |
PERIMETER_MID_ZN_2 | 3051.83 | 2927.50 | 1367.83 |
PERIMETER_MID_ZN_1 | 3367.00 | 3078.67 | 1172.50 |
PERIMETER_MID_ZN_4 | 3603.50 | 3361.33 | 1552.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4873.17 | 4356.83 | 2598.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.83 | 0.00 | 1.67 | 0.00 |
CORE_MID | 2.83 | 0.00 | 2.33 | 0.00 |
CORE_TOP | 4.17 | 0.00 | 3.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 47.67 | 5.50 | 22.33 | 5.00 |
PERIMETER_TOP_ZN_2 | 31.83 | 36.00 | 6.67 | 35.33 |
PERIMETER_TOP_ZN_1 | 24.83 | 30.33 | 5.83 | 29.17 |
PERIMETER_TOP_ZN_4 | 32.33 | 30.67 | 8.50 | 22.17 |
PERIMETER_BOT_ZN_3 | 17.67 | 0.00 | 11.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 7.00 | 17.67 | 1.50 | 17.67 |
PERIMETER_BOT_ZN_1 | 243.33 | 33.83 | 238.50 | 33.67 |
PERIMETER_BOT_ZN_4 | 7.83 | 16.33 | 2.50 | 13.00 |
PERIMETER_MID_ZN_3 | 18.50 | 1.17 | 9.00 | 1.17 |
PERIMETER_MID_ZN_2 | 11.17 | 29.33 | 2.17 | 29.00 |
PERIMETER_MID_ZN_1 | 9.00 | 27.00 | 1.83 | 26.83 |
PERIMETER_MID_ZN_4 | 11.17 | 26.00 | 2.83 | 19.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 289.17 | 134.33 | 256.50 | 120.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.672 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.559 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.555 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.646 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.880 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.948 | 0.107 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.890 | 0.112 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.565 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.794 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.814 | 0.864 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.780 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.637 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.808 | 0.100 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.953 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.881 | 0.093 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.11 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 10587629.04 | 0.00 | 10587629.04 | 0.00 | 10587629.04 | 13393058.27 | 5430.41 | 733.49 | 2596.11 | 23.97 |
CORE_MID | 8837503.60 | 0.00 | 8837503.60 | 0.00 | 8837503.60 | 13393058.27 | 5707.58 | 1107.18 | 1945.23 | 46.29 |
CORE_TOP | 8781448.82 | 0.00 | 8781448.82 | 0.00 | 8781448.82 | 13393058.27 | 5752.35 | 1131.58 | 1876.07 | 49.69 |
PERIMETER_TOP_ZN_3 | 2152087.83 | 0.00 | 2152087.83 | 696839.46 | 2848927.29 | 2823374.22 | 4604.58 | 1034.96 | 3120.46 | 49.67 |
PERIMETER_TOP_ZN_2 | 1852359.85 | 0.00 | 1852359.85 | 464556.85 | 2316916.70 | 1787429.43 | 4531.22 | 971.78 | 3257.01 | 49.67 |
PERIMETER_TOP_ZN_1 | 3151474.89 | 0.00 | 3151474.89 | 696839.46 | 3848314.36 | 2823374.22 | 4422.29 | 1073.56 | 3264.15 | 49.67 |
PERIMETER_TOP_ZN_4 | 1875609.88 | 0.00 | 1875609.88 | 464556.85 | 2340166.73 | 1787312.18 | 4497.75 | 999.48 | 3262.77 | 49.67 |
PERIMETER_BOT_ZN_3 | 1880429.73 | 0.00 | 1880429.73 | 370505.73 | 2250935.46 | 2823374.22 | 5584.52 | 919.60 | 2255.88 | 23.97 |
PERIMETER_BOT_ZN_2 | 1670904.83 | 0.00 | 1670904.83 | 247002.33 | 1917907.16 | 1787429.43 | 4892.74 | 728.68 | 3138.58 | 23.97 |
PERIMETER_BOT_ZN_1 | 2709979.36 | 0.00 | 2709979.36 | 3064686.73 | 5774666.10 | 2823374.22 | 4770.68 | 873.55 | 3115.76 | 23.97 |
PERIMETER_BOT_ZN_4 | 1640982.05 | 0.00 | 1640982.05 | 247002.33 | 1887984.38 | 1787312.18 | 4896.93 | 746.60 | 3116.47 | 23.97 |
PERIMETER_MID_ZN_3 | 2122694.22 | 0.00 | 2122694.22 | 580065.25 | 2702759.46 | 2823374.22 | 4724.40 | 1167.48 | 2868.12 | 46.29 |
PERIMETER_MID_ZN_2 | 1700881.16 | 0.00 | 1700881.16 | 386707.84 | 2087589.00 | 1601953.02 | 4436.00 | 850.86 | 3473.15 | 955.29 |
PERIMETER_MID_ZN_1 | 3169383.73 | 0.00 | 3169383.73 | 580065.25 | 3749448.98 | 2823374.22 | 4351.54 | 888.37 | 3520.08 | 46.29 |
PERIMETER_MID_ZN_4 | 1854622.01 | 0.00 | 1854622.01 | 386707.84 | 2241329.85 | 1787312.18 | 4543.62 | 963.37 | 3253.01 | 46.29 |
Total Facility | 53987991.01 | 0.00 | 53987991.01 | 8185535.92 | 62173526.93 | 67658168.57 | 6400.50 | 1677.58 | 4137.32 | 996.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.4939 | 0.0000 | 0.4939 | 0.0000 | 0.4939 | 0.4247 | 2619.66 | 733.49 | 2589.86 |
CORE_MID | 0.4117 | 0.0000 | 0.4117 | 0.0000 | 0.4117 | 0.4247 | 2900.50 | 1107.18 | 1935.32 |
CORE_TOP | 0.4088 | 0.0000 | 0.4088 | 0.0000 | 0.4088 | 0.4247 | 2948.93 | 1131.58 | 1862.48 |
PERIMETER_TOP_ZN_3 | 0.1002 | 0.0000 | 0.1002 | 0.0166 | 0.1168 | 0.0895 | 1801.16 | 1034.96 | 3106.88 |
PERIMETER_TOP_ZN_2 | 0.0864 | 0.0000 | 0.0864 | 0.0111 | 0.0974 | 0.0567 | 1727.80 | 971.78 | 3243.42 |
PERIMETER_TOP_ZN_1 | 0.1470 | 0.0000 | 0.1470 | 0.0166 | 0.1636 | 0.0895 | 1618.88 | 1073.56 | 3250.57 |
PERIMETER_TOP_ZN_4 | 0.0874 | 0.0000 | 0.0874 | 0.0111 | 0.0984 | 0.0567 | 1694.33 | 999.48 | 3249.19 |
PERIMETER_BOT_ZN_3 | 0.0877 | 0.0000 | 0.0877 | 0.0088 | 0.0965 | 0.0895 | 2773.77 | 919.60 | 2249.63 |
PERIMETER_BOT_ZN_2 | 0.0780 | 0.0000 | 0.0780 | 0.0059 | 0.0839 | 0.0567 | 2082.02 | 728.68 | 3132.30 |
PERIMETER_BOT_ZN_1 | 0.1265 | 0.0000 | 0.1265 | 0.1348 | 0.2612 | 0.0895 | 1959.93 | 873.55 | 3109.51 |
PERIMETER_BOT_ZN_4 | 0.0765 | 0.0000 | 0.0765 | 0.0059 | 0.0824 | 0.0567 | 2086.20 | 746.60 | 3110.20 |
PERIMETER_MID_ZN_3 | 0.0989 | 0.0000 | 0.0989 | 0.0138 | 0.1127 | 0.0895 | 1917.32 | 1167.48 | 2858.20 |
PERIMETER_MID_ZN_2 | 0.0793 | 0.0000 | 0.0793 | 0.0098 | 0.0892 | 0.0567 | 1628.93 | 850.86 | 2554.21 |
PERIMETER_MID_ZN_1 | 0.1478 | 0.0000 | 0.1478 | 0.0138 | 0.1616 | 0.0895 | 1544.46 | 888.37 | 3510.16 |
PERIMETER_MID_ZN_4 | 0.0864 | 0.0000 | 0.0864 | 0.0092 | 0.0956 | 0.0567 | 1736.56 | 963.37 | 3243.07 |
Total Facility | 2.5166 | 0.0000 | 2.5166 | 0.2573 | 2.7739 | 2.1513 | 3588.45 | 1677.58 | 4121.53 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 26785257.34 | 0.00 | 26785257.34 | 22614548.33 | 4216.83 | 2.62 | 4540.55 | 23.97 |
PACU_VAV_MID | 25619341.46 | 0.00 | 25619341.46 | 22429071.92 | 4198.68 | 3.49 | 4557.84 | 46.29 |
PACU_VAV_TOP | 25804566.24 | 0.00 | 25804566.24 | 22614548.33 | 4213.21 | 1.30 | 4545.49 | 48.94 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2496 | 0.0000 | 1.2496 | 0.7171 | 1406.08 | 2.62 | 4534.30 |
PACU_VAV_MID | 1.1939 | 0.0000 | 1.1939 | 0.7084 | 1391.60 | 3.49 | 4547.92 |
PACU_VAV_TOP | 1.2020 | 0.0000 | 1.2020 | 0.7171 | 1409.79 | 1.30 | 4531.91 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 135.48 | 1804.06 | 0.00 | 0.00 | 0.00 | 2744.60 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 92.30 | 1814.79 | 0.00 | 0.00 | 0.00 | 2818.25 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 55.92 | 1815.97 | 0.00 | 0.00 | 0.00 | 2869.10 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3050 | 2.3672 | 0.0000 | 0.0000 | 0.0000 | 1.1067 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2705 | 2.2150 | 0.0000 | 0.0000 | 0.0000 | 1.0867 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2205 | 2.2244 | 0.0000 | 0.0000 | 0.0000 | 1.0965 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1267.37 | 11240.73 | 16-APR-17:10 | 230126.34 | 02-JAN-07:10 |
Electricity:Building | 814.75 | 11072.20 | 09-APR-17:10 | 57107.62 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 814.75 | 11072.20 | 09-APR-17:10 | 57107.62 | 03-JAN-08:10 |
InteriorLights:Electricity | 167.00 | 772.31 | 01-JAN-08:50 | 17672.30 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 167.00 | 772.31 | 01-JAN-08:50 | 17672.30 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 167.00 | 772.31 | 01-JAN-08:50 | 17672.30 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 167.00 | 772.31 | 01-JAN-08:50 | 17672.30 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.23 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.89 | 19.49 | 01-JAN-08:50 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.89 | 19.49 | 01-JAN-08:50 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.49 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.09 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.09 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.16 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.83 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.83 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.47 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.06 | 12.34 | 01-JAN-08:40 | 465.57 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.06 | 12.34 | 01-JAN-08:40 | 465.57 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.22 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.88 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.88 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.49 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.08 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.08 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.16 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.83 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.83 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.46 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.06 | 12.34 | 01-JAN-08:40 | 465.57 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.06 | 12.34 | 01-JAN-08:40 | 465.57 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.23 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.89 | 19.49 | 01-JAN-08:50 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.89 | 19.49 | 01-JAN-08:50 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.49 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.09 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.09 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.16 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.83 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.83 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.47 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.06 | 12.34 | 01-JAN-08:40 | 465.57 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.06 | 12.34 | 01-JAN-08:40 | 465.57 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 136.08 | -0.00 | 01-JAN-16:30 | 26130.14 | 02-JUN-11:50 |
ElectricityProduced:Plant | 136.08 | -0.00 | 01-JAN-16:30 | 26130.14 | 02-JUN-11:50 |
Photovoltaic:ElectricityProduced | 142.41 | 0.00 | 01-JAN-00:10 | 27211.52 | 02-JUN-11:50 |
PowerConversion:ElectricityProduced | -6.34 | -1081.38 | 02-JUN-11:50 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-12:20 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 418.41 | 168.53 | 26-MAR-17:10 | 202757.53 | 02-JAN-06:20 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.65 | 02-JAN-16:50 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.65 | 02-JAN-16:50 |
ElectricityPurchased:Facility | 1132.14 | 0.00 | 29-JAN-11:10 | 230126.34 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1132.14 | 0.00 | 29-JAN-11:10 | 230126.34 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1132.14 | 0.00 | 29-JAN-11:10 | 230126.34 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1132.14 | 0.00 | 29-JAN-11:10 | 230126.34 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.85 | 0.00 | 01-JAN-00:10 | 10679.06 | 14-MAY-12:00 |
ElectricitySurplusSold:Plant | 0.85 | 0.00 | 01-JAN-00:10 | 10679.06 | 14-MAY-12:00 |
Cogeneration:ElectricitySurplusSold | 0.85 | 0.00 | 01-JAN-00:10 | 10679.06 | 14-MAY-12:00 |
General:Cogeneration:ElectricitySurplusSold | 0.85 | 0.00 | 01-JAN-00:10 | 10679.06 | 14-MAY-12:00 |
ElectricityNet:Facility | 1131.30 | -10679.06 | 14-MAY-12:00 | 230126.34 | 02-JAN-07:10 |
ElectricityNet:Plant | 1131.30 | -10679.06 | 14-MAY-12:00 | 230126.34 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1131.30 | -10679.06 | 14-MAY-12:00 | 230126.34 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1131.30 | -10679.06 | 14-MAY-12:00 | 230126.34 | 02-JAN-07:10 |
Heating:Electricity | 130.87 | 0.00 | 01-JAN-00:40 | 195795.69 | 02-JAN-06:20 |
General:Heating:Electricity | 130.87 | 0.00 | 01-JAN-00:40 | 195795.69 | 02-JAN-06:20 |
Fans:Electricity | 85.46 | 0.00 | 01-JAN-00:40 | 25152.04 | 30-MAY-14:20 |
General:Fans:Electricity | 85.46 | 0.00 | 01-JAN-00:40 | 25152.04 | 30-MAY-14:20 |
ExteriorLights:Electricity | 34.07 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.07 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 190.47 | 0.00 | 01-JAN-00:10 | 73260.87 | 19-JUN-12:10 |
General:Cooling:Electricity | 190.47 | 0.00 | 01-JAN-00:10 | 73260.87 | 19-JUN-12:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-12:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-12:20 |
WIRED_LTG_ELECTRICITY | 4.69 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 297.67 | 1886.44 | 07-JAN-06:10 | 95995.00 | 06-FEB-08:20 |
NaturalGas:HVAC | 167.31 | 0.00 | 01-JAN-00:40 | 86586.19 | 06-FEB-08:10 |
Heating:NaturalGas | 167.31 | 0.00 | 01-JAN-00:40 | 86586.19 | 06-FEB-08:10 |
General:Heating:NaturalGas | 167.31 | 0.00 | 01-JAN-00:40 | 86586.19 | 06-FEB-08:10 |
NaturalGas:Plant | 130.36 | 1886.44 | 02-JAN-17:20 | 10205.25 | 06-FEB-12:10 |
WaterSystems:NaturalGas | 130.36 | 1886.44 | 02-JAN-17:20 | 10205.25 | 06-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 130.36 | 1886.44 | 02-JAN-17:20 | 10205.25 | 06-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2134.48 | 0.00 | 01-JAN-00:40 | 452435.15 | 02-JAN-07:10 |
EnergyTransfer:Building | 1005.54 | 0.00 | 01-JAN-00:40 | 197709.33 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 174.36 | 0.00 | 01-JAN-00:40 | 22625.40 | 05-SEP-07:20 |
Heating:EnergyTransfer | 112.77 | 0.00 | 01-JAN-00:40 | 197709.33 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.59 | 0.00 | 01-JAN-00:10 | 17282.49 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 112.77 | 0.00 | 01-JAN-00:40 | 197709.33 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.59 | 0.00 | 01-JAN-00:10 | 17282.49 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 892.77 | 0.00 | 01-JAN-00:40 | 159040.17 | 14-AUG-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 173.77 | 0.00 | 01-JAN-00:40 | 22625.40 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 892.77 | 0.00 | 01-JAN-00:40 | 159040.17 | 14-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 173.77 | 0.00 | 01-JAN-00:40 | 22625.40 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.14 | 0.00 | 01-JAN-00:40 | 14670.45 | 06-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.80 | 0.00 | 01-JAN-00:40 | 14670.45 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.80 | 0.00 | 01-JAN-00:40 | 14670.45 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.34 | 0.00 | 01-JAN-00:10 | 11276.41 | 19-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.34 | 0.00 | 01-JAN-00:10 | 11276.41 | 19-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.62 | 0.00 | 01-JAN-00:40 | 9290.79 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.46 | 0.00 | 01-JAN-00:40 | 9290.79 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.46 | 0.00 | 01-JAN-00:40 | 9290.79 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.16 | 0.00 | 01-JAN-00:10 | 5248.80 | 14-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.16 | 0.00 | 01-JAN-00:10 | 5248.80 | 14-AUG-14:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.01 | 0.00 | 01-JAN-00:40 | 8144.80 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.40 | 0.00 | 01-JAN-00:40 | 8144.80 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.40 | 0.00 | 01-JAN-00:40 | 8144.80 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.61 | 0.00 | 01-JAN-00:10 | 5116.70 | 14-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.61 | 0.00 | 01-JAN-00:10 | 5116.70 | 14-AUG-07:10 |
EnergyTransfer:Zone:CORE_MID | 136.27 | 0.00 | 01-JAN-00:40 | 18785.70 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.30 | 0.00 | 01-JAN-00:40 | 18785.70 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.30 | 0.00 | 01-JAN-00:40 | 18785.70 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 134.97 | 0.00 | 01-JAN-00:20 | 18592.88 | 05-SEP-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 134.97 | 0.00 | 01-JAN-00:20 | 18592.88 | 05-SEP-07:30 |
EnergyTransfer:Zone:CORE_TOP | 133.61 | 0.00 | 01-JAN-00:40 | 27288.56 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.96 | 0.00 | 01-JAN-00:40 | 27288.56 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.96 | 0.00 | 01-JAN-00:40 | 27288.56 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 127.66 | 0.00 | 01-JAN-00:20 | 19732.26 | 14-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 127.66 | 0.00 | 01-JAN-00:20 | 19732.26 | 14-AUG-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 41.65 | 0.00 | 01-JAN-00:40 | 9637.68 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 11.63 | 0.00 | 01-JAN-00:40 | 9637.68 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 11.63 | 0.00 | 01-JAN-00:40 | 9637.68 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.02 | 0.00 | 01-JAN-00:10 | 7515.57 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.02 | 0.00 | 01-JAN-00:10 | 7515.57 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 34.55 | 0.00 | 01-JAN-00:40 | 9095.24 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.04 | 0.00 | 01-JAN-00:40 | 9095.24 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.04 | 0.00 | 01-JAN-00:40 | 9095.24 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.51 | 0.00 | 01-JAN-00:10 | 9071.60 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.51 | 0.00 | 01-JAN-00:10 | 9071.60 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 55.98 | 0.00 | 01-JAN-00:40 | 12670.98 | 28-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.42 | 0.00 | 01-JAN-00:40 | 11848.93 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.42 | 0.00 | 01-JAN-00:40 | 11848.93 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 48.56 | 0.00 | 01-JAN-00:10 | 12670.98 | 28-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 48.56 | 0.00 | 01-JAN-00:10 | 12670.98 | 28-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.82 | 0.00 | 01-JAN-00:40 | 9448.84 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.93 | 0.00 | 01-JAN-00:40 | 9448.84 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.93 | 0.00 | 01-JAN-00:40 | 9448.84 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.89 | 0.00 | 01-JAN-00:10 | 9374.45 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.89 | 0.00 | 01-JAN-00:10 | 9374.45 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.37 | 0.00 | 01-JAN-00:40 | 7396.50 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.09 | 0.00 | 01-JAN-00:40 | 7396.50 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 6.09 | 0.00 | 01-JAN-00:40 | 7396.50 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 26.28 | 0.00 | 01-JAN-00:10 | 5867.82 | 14-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 26.28 | 0.00 | 01-JAN-00:10 | 5867.82 | 14-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.12 | 0.00 | 01-JAN-00:40 | 7521.47 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.71 | 0.00 | 01-JAN-00:40 | 7521.47 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.71 | 0.00 | 01-JAN-00:40 | 7521.47 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.41 | 0.00 | 01-JAN-00:20 | 7161.46 | 05-SEP-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.41 | 0.00 | 01-JAN-00:20 | 7161.46 | 05-SEP-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 55.71 | 0.00 | 01-JAN-00:40 | 12876.39 | 02-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.83 | 0.00 | 01-JAN-00:40 | 12876.39 | 02-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.83 | 0.00 | 01-JAN-00:40 | 12876.39 | 02-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.88 | 0.00 | 01-JAN-00:20 | 11890.92 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.88 | 0.00 | 01-JAN-00:20 | 11890.92 | 19-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 29.29 | 0.00 | 01-JAN-00:40 | 7645.65 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.11 | 0.00 | 01-JAN-00:40 | 7645.65 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 3.11 | 0.00 | 01-JAN-00:40 | 7645.65 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.18 | 0.00 | 01-JAN-00:20 | 7462.54 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.18 | 0.00 | 01-JAN-00:20 | 7462.54 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 36.49 | 0.00 | 01-JAN-00:40 | 8272.86 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.80 | 0.00 | 01-JAN-00:40 | 8272.86 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.80 | 0.00 | 01-JAN-00:40 | 8272.86 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 30.69 | 0.00 | 01-JAN-00:10 | 6773.01 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 30.69 | 0.00 | 01-JAN-00:10 | 6773.01 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.41 | 0.00 | 01-JAN-00:40 | 8924.62 | 26-JUN-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.96 | 0.00 | 01-JAN-00:40 | 8018.32 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.96 | 0.00 | 01-JAN-00:40 | 8018.32 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.45 | 0.00 | 01-JAN-00:10 | 8924.62 | 26-JUN-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.45 | 0.00 | 01-JAN-00:10 | 8924.62 | 26-JUN-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.48 | 0.00 | 01-JAN-00:40 | 11776.46 | 28-SEP-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.35 | 0.00 | 01-JAN-00:40 | 10402.18 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.35 | 0.00 | 01-JAN-00:40 | 10402.18 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.13 | 0.00 | 01-JAN-00:10 | 11776.46 | 28-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.13 | 0.00 | 01-JAN-00:10 | 11776.46 | 28-SEP-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.65 | 0.00 | 01-JAN-00:40 | 8974.29 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.40 | 0.00 | 01-JAN-00:40 | 8054.91 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.40 | 0.00 | 01-JAN-00:40 | 8054.91 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 29.25 | 0.00 | 01-JAN-00:10 | 8974.29 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 29.25 | 0.00 | 01-JAN-00:10 | 8974.29 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 48.91 | 0.00 | 01-JAN-00:10 | 6339.57 | 13-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6339.57 | 13-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6339.57 | 13-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6339.57 | 13-FEB-12:10 |
EnergyTransfer:HVAC | 1080.03 | 0.00 | 01-JAN-00:40 | 271276.44 | 16-AUG-12:30 |
HeatingCoils:EnergyTransfer | 271.41 | 0.00 | 01-JAN-00:40 | 262627.77 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 808.63 | 0.00 | 01-JAN-00:10 | 271276.44 | 16-AUG-12:30 |
EnergyTransfer:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6339.57 | 13-FEB-12:10 |
WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6339.57 | 13-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6339.57 | 13-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.590 | -173.774 | 0.000 | 0.000 | 33.346 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -78.441 |
CORE_MID | 0.000 | 0.000 | 1.302 | -134.972 | 0.000 | 0.000 | 34.365 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.915 |
CORE_TOP | 0.000 | 0.000 | 5.956 | -127.658 | 0.000 | 0.000 | 34.917 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -68.435 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 11.628 | -30.024 | 0.000 | 0.000 | 7.505 | 4.894 | 24.333 | 18.790 | 0.000 | 0.138 | 0.000 | 0.000 | -27.804 | 0.000 | -9.201 | -0.258 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 6.041 | -28.511 | 0.000 | 0.000 | 4.680 | 3.089 | 15.404 | 33.379 | 0.000 | 0.089 | 0.001 | 0.000 | -17.651 | 0.000 | -6.242 | -10.278 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 7.419 | -48.561 | 0.000 | 0.000 | 7.289 | 4.832 | 24.332 | 68.038 | 0.000 | 0.134 | 0.000 | 0.000 | -26.468 | 0.000 | -9.630 | -27.383 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 6.926 | -28.891 | 0.000 | 0.000 | 4.709 | 3.065 | 15.403 | 33.992 | 0.000 | 0.089 | 0.001 | 0.000 | -18.181 | 0.000 | -6.280 | -10.833 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 6.090 | -26.278 | 0.000 | 0.000 | 7.490 | 4.884 | 24.333 | 19.150 | 0.000 | 0.083 | 0.001 | 0.000 | -28.819 | 0.000 | -5.161 | -1.770 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.709 | -26.408 | 0.000 | 0.000 | 4.656 | 3.084 | 15.404 | 33.577 | 0.000 | 0.049 | 0.001 | 0.000 | -18.631 | 0.000 | -3.554 | -10.886 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 15.827 | -39.882 | 0.000 | 0.000 | 7.455 | 4.826 | 24.332 | 68.811 | 0.000 | 2.020 | 0.003 | 0.000 | -27.997 | 0.000 | -35.177 | -20.215 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 3.110 | -26.179 | 0.000 | 0.000 | 4.681 | 3.060 | 15.403 | 34.256 | 0.000 | 0.049 | 0.000 | 0.000 | -19.218 | 0.000 | -3.576 | -11.586 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 5.798 | -30.690 | 0.000 | 0.000 | 7.447 | 4.894 | 24.333 | 18.657 | 0.000 | 0.118 | 6.762 | 0.000 | -29.262 | 0.000 | -8.057 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.962 | -27.451 | 0.000 | 0.000 | 3.425 | 3.089 | 15.404 | 33.172 | 0.000 | 0.073 | 0.001 | 0.000 | -18.567 | 0.000 | -5.477 | -6.629 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.350 | -50.133 | 0.000 | 0.000 | 7.218 | 4.832 | 24.332 | 67.854 | 0.000 | 0.113 | 0.001 | 0.000 | -27.854 | 0.000 | -8.445 | -21.267 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 3.397 | -29.249 | 0.000 | 0.000 | 4.668 | 3.065 | 15.403 | 33.911 | 0.000 | 0.075 | 0.000 | 0.000 | -19.137 | 0.000 | -5.499 | -6.634 |
TOPFLOOR_PLENUM | 15.797 | -29.340 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.138 | 27.592 | 0.000 | 0.000 | 0.000 | -14.187 | -0.002 |
MIDFLOOR_PLENUM | 8.465 | -16.156 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.161 | 21.500 | 0.000 | 0.000 | 0.000 | -13.970 | -0.000 |
FIRSTFLOOR_PLENUM | 5.405 | -18.607 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.129 | 24.361 | 0.000 | 0.000 | 0.000 | -11.287 | -0.000 |
Total Facility | 29.666 | -64.103 | 83.103 | -828.663 | 0.000 | 0.000 | 173.851 | 167.000 | 647.750 | 463.586 | 0.000 | 3.457 | 80.224 | 0.000 | -279.591 | 0.000 | -145.744 | -330.531 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 07-AUG-05:12 | 0.00 | 0.00 | 0.00 | -35283.87 | 0.00 | 0.00 | 317.15 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 30531.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-05:14 | 0.00 | 0.00 | 0.00 | -31614.93 | 0.00 | 0.00 | 315.48 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 27885.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-05:04 | 0.00 | 0.00 | 0.00 | -33852.06 | 0.00 | 0.00 | 304.09 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 30310.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:52 | 0.00 | 0.00 | 0.00 | -11037.76 | 0.00 | 0.00 | 27.18 | 19.49 | 478.42 | 2476.88 | 0.00 | 117.46 | 7918.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:32 | 0.00 | 0.00 | 0.00 | -12922.33 | 0.00 | 0.00 | 13.64 | 12.34 | 302.86 | 10764.17 | 0.00 | 0.00 | 1869.11 | 0.00 | -0.00 | 0.00 | -39.78 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:12 | 0.00 | 0.00 | 0.00 | -16413.85 | 0.00 | 0.00 | 24.71 | 19.49 | 478.41 | 13889.19 | 0.00 | 0.00 | 2525.78 | 0.00 | -0.00 | 0.00 | -523.74 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-15:52 | 0.00 | 0.00 | 0.00 | -14202.07 | 0.00 | 0.00 | 12.87 | 12.34 | 302.86 | 10688.57 | 0.00 | 0.00 | 3294.65 | 0.00 | -0.00 | 0.00 | -109.21 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7180.59 | 0.00 | 0.00 | 145.16 | 116.94 | 637.89 | 2261.78 | 0.00 | 0.00 | 4026.50 | 0.00 | -0.00 | 0.00 | -7.68 | 0.00 |
PERIMETER_BOT_ZN_2 | 25-JUN-08:42 | 0.00 | 0.00 | 0.00 | -10704.73 | 0.00 | 0.00 | 16.85 | 12.34 | 302.86 | 10129.09 | 0.00 | 0.00 | 268.58 | 0.00 | -0.00 | 0.00 | -24.98 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:12 | 0.00 | 0.00 | 0.00 | -13043.37 | 0.00 | 0.00 | 26.03 | 19.49 | 478.41 | 14029.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -271.09 | -1239.36 |
PERIMETER_BOT_ZN_4 | 10-SEP-17:12 | 0.00 | 0.00 | 0.00 | -11241.66 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 7147.17 | 0.00 | 0.00 | 3950.67 | 0.00 | -0.00 | 0.00 | -112.94 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-14:41 | 0.00 | 0.00 | 0.00 | -8794.16 | 0.00 | 0.00 | 28.51 | 19.49 | 478.42 | 3694.49 | 0.00 | 55.45 | 4517.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:21 | 0.00 | 0.00 | 0.00 | -13863.59 | 0.00 | 0.00 | 13.72 | 12.34 | 302.86 | 11022.67 | 0.00 | 0.00 | 2569.24 | 0.00 | -0.00 | 0.00 | -57.24 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-11:12 | 0.00 | 0.00 | 0.00 | -14894.68 | 0.00 | 0.00 | 24.80 | 19.49 | 478.41 | 14108.82 | 0.00 | 0.00 | 533.47 | 0.00 | -0.00 | 0.00 | -270.31 | 0.00 |
PERIMETER_MID_ZN_4 | 18-JUN-16:31 | 0.00 | 0.00 | 0.00 | -14121.21 | 0.00 | 0.00 | 13.83 | 12.34 | 302.86 | 9402.31 | 0.00 | 0.00 | 4502.61 | 0.00 | -0.00 | 0.00 | -112.73 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:30 | 0.00 | -11275.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.89 | 11129.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-10:10 | 0.00 | -5366.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 | 5333.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-JUL-12:10 | 0.00 | -5434.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.86 | 5357.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:02 | 0.00 | 7057.81 | 0.00 | -192062.26 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 0.00 | 0.00 | 59.24 | 171036.07 | 0.00 | -1357.22 | 0.00 | -89.70 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 19815.37 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 3464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23667.19 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 21490.71 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24320.40 |
CORE_TOP | 02-JAN-00:02 | 0.00 | 0.00 | 30733.99 | 0.00 | 0.00 | 0.00 | 0.00 | 193.79 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33369.84 |
PERIMETER_TOP_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 10819.32 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3004.93 | 0.00 | -2186.17 | -6183.87 |
PERIMETER_TOP_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 11658.39 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1954.27 | 0.00 | -1487.42 | -8568.46 |
PERIMETER_TOP_ZN_1 | 02-JAN-00:02 | 0.00 | 0.00 | 14439.84 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2953.45 | 0.00 | -2225.52 | -9816.52 |
PERIMETER_TOP_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 12603.71 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2003.38 | 0.00 | -1491.00 | -9461.09 |
PERIMETER_BOT_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 8207.04 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3053.98 | 0.00 | -1201.16 | -4507.56 |
PERIMETER_BOT_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 9272.28 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2003.59 | 0.00 | -817.87 | -6802.57 |
PERIMETER_BOT_ZN_1 | 02-JAN-08:00 | 0.00 | 0.00 | 12876.27 | 0.00 | 0.00 | 0.00 | 251.63 | 116.94 | 637.88 | 1373.80 | 0.00 | 0.00 | 5422.47 | 0.00 | -0.00 | 0.00 | -20678.99 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 9485.68 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2041.04 | 0.00 | -815.34 | -6981.05 |
PERIMETER_MID_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 9205.74 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3060.43 | 0.00 | -1856.35 | -4844.62 |
PERIMETER_MID_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 10350.38 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1991.84 | 0.00 | -1261.13 | -7449.17 |
PERIMETER_MID_ZN_1 | 02-JAN-00:02 | 0.00 | 0.00 | 12813.38 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3012.11 | 0.00 | -1889.51 | -8467.42 |
PERIMETER_MID_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 10456.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2040.42 | 0.00 | -1259.52 | -7508.07 |
TOPFLOOR_PLENUM | 06-FEB-06:12 | 15152.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -806.92 | -14345.31 |
MIDFLOOR_PLENUM | 02-JAN-07:08 | 9456.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -232.97 | -9223.03 |
FIRSTFLOOR_PLENUM | 02-JAN-08:17 | 8337.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -257.34 | -8080.65 |
Total Facility | 02-JAN-05:01 | 17485.20 | 0.00 | 191656.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31892.89 | 0.00 | -9576.17 | -183029.03 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.7729 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2570 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.7753 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.0775 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.1736 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7419 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.3865 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0765 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.3877 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0759 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5868 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0758 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2949 | 2.2949 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9243 | 1.9243 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0671 | 2.0671 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6689 | 0.6689 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7344 | 0.7344 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9075 | 0.9075 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7957 | 0.7957 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5240 | 0.5240 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6044 | 0.6044 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7279 | 0.7279 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6217 | 0.6217 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5802 | 0.5802 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7151 | 0.7151 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8213 | 0.8213 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7345 | 0.7345 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.7729 | 4.2570 | 4.7729 | 1.0765 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.7753 | 4.0775 | 4.7753 | 1.0759 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.1736 | 4.7419 | 5.1736 | 1.0758 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1475 | 1.1475 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9621 | 0.9621 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0335 | 1.0335 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3345 | 0.3345 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3672 | 0.3672 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4537 | 0.4537 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3979 | 0.3979 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2620 | 0.2620 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3022 | 0.3022 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3640 | 0.3640 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3108 | 0.3108 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2901 | 0.2901 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3576 | 0.3576 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4106 | 0.4106 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3673 | 0.3673 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.3865 | 1.0765 | 1.0765 | 1.0765 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.3877 | 1.0759 | 1.0759 | 1.0759 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5868 | 1.0758 | 1.0758 | 1.0758 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 256.50 |
Number of hours cooling loads not met | 120.50 |
Number of hours not met | 377.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 130.87 | 195795.69 | 167.31 | 86586.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 190.47 | 73260.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 167.00 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.07 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 828.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 85.46 | 25152.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 130.36 | 10205.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1267.37 |
Natural Gas | 0.00 | 297.67 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1565.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 142.41 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.52 |
Space Heating | 26.27 |
Space Cooling | 38.23 |
Fans (All) | 17.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 254.38 |
Subtotal | 254.38 |
Natural Gas [MJ/m2] | |
Space Heating | 33.58 |
Service Water Heating | 26.16 |
Miscellaneous (All) | 59.75 |
Subtotal | 59.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.67 |
Space Heating | 19.05 |
Space Cooling | 12.17 |
Fans (All) | 5.46 |
Service Water Heating | 8.33 |
Receptacle Equipment | 41.39 |
Miscellaneous | 2.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 940. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8694.00 | 66.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8610.83 | 149.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8630.33 | 129.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8568.17 | 191.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8674.00 | 86.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8691.67 | 68.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8618.67 | 141.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8709.33 | 50.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8614.00 | 146.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8634.00 | 126.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8564.50 | 195.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8615.83 | 144.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8564.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 195.50 | 0.00 | 0.00 | 0.00 |
Average | 8674.23 | 85.77 | 0.00 | 0.00 | 0.00 |
Sum | 156136.17 | 1543.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128299.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 6.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.70 | 0.63 | 0.00 | 0.00 | 0.00 |
Sum | 614568.67 | 11.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8075.00 | 685.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8250.17 | 509.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8359.83 | 400.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7918.33 | 841.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7871.67 | 888.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7890.33 | 869.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7848.00 | 912.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8006.83 | 753.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7881.83 | 878.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7619.17 | 1140.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7822.00 | 938.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7897.50 | 862.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7818.33 | 941.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7854.17 | 905.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7803.50 | 956.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7372.67 | 1387.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7792.33 | 967.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7723.00 | 1037.00 | 0.00 | 0.00 | 0.00 |
Min | 7372.67 | 400.17 | 0.00 | 0.00 | 0.00 |
Max | 8359.83 | 1387.33 | 0.00 | 0.00 | 0.00 |
Average | 7878.04 | 881.96 | 0.00 | 0.00 | 0.00 |
Sum | 141804.67 | 15875.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127947.00 | 357.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128048.17 | 255.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128126.83 | 177.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24704.50 | 204.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13906.17 | 109.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24728.67 | 180.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13890.00 | 126.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24732.33 | 176.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 13941.00 | 75.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23219.50 | 1689.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 13915.17 | 100.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24799.83 | 109.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10106.33 | 27.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24814.17 | 94.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13936.83 | 79.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128126.83 | 1689.50 | 0.00 | 0.00 | 0.00 |
Average | 33934.25 | 209.08 | 0.00 | 0.00 | 0.00 |
Sum | 610816.50 | 3763.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.678537E+10 | 6908.37 | 27-JAN-16:30 | 5.00 | 2.53 | 0.172153E+10 | 2573.62 | 27-JAN-14:09 | 5.00 | 2.53 |
February | 0.709296E+10 | 7910.42 | 24-FEB-17:00 | 6.70 | 1.42 | 0.164066E+10 | 2606.57 | 03-FEB-14:30 | 6.70 | 1.42 |
March | 0.100328E+11 | 12940.40 | 30-MAR-07:20 | 2.40 | 1.23 | 0.210411E+10 | 2606.66 | 27-MAR-09:09 | 2.40 | 1.23 |
April | 0.119266E+11 | 18061.19 | 10-APR-06:03 | 15.78 | 13.94 | 0.189801E+10 | 2606.66 | 05-APR-09:39 | 15.78 | 13.94 |
May | 0.169991E+11 | 33558.48 | 30-MAY-05:12 | 18.53 | 14.51 | 0.207233E+10 | 2606.76 | 15-MAY-13:00 | 18.53 | 14.51 |
June | 0.205665E+11 | 33515.00 | 26-JUN-05:12 | 20.97 | 17.23 | 0.206991E+10 | 2606.66 | 23-JUN-09:20 | 20.97 | 17.23 |
July | 0.213194E+11 | 34650.44 | 24-JUL-05:12 | 20.97 | 20.39 | 0.192409E+10 | 2606.66 | 12-JUL-13:00 | 20.97 | 20.39 |
August | 0.231800E+11 | 35293.44 | 07-AUG-05:12 | 19.40 | 16.84 | 0.216043E+10 | 2606.67 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.194139E+11 | 33697.15 | 01-SEP-05:03 | 24.08 | 21.83 | 0.191732E+10 | 2606.72 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.175648E+11 | 31558.43 | 16-OCT-06:01 | 9.18 | 8.72 | 0.199136E+10 | 2606.73 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.107770E+11 | 15090.04 | 03-NOV-16:00 | 15.00 | 10.26 | 0.192915E+10 | 2606.69 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.811559E+10 | 9260.30 | 21-DEC-16:10 | 2.62 | -2.3 | 0.181905E+10 | 2606.63 | 22-DEC-10:39 | -1.5 | -4.4 |
Annual Sum or Average | 0.173774E+12 | 0.232479E+11 | ||||||||
Minimum of Months | 0.678537E+10 | 6908.37 | 2.40 | -2.3 | 0.164066E+10 | 2573.62 | -1.5 | -4.4 | ||
Maximum of Months | 0.231800E+11 | 35293.44 | 24.08 | 21.83 | 0.216043E+10 | 2606.76 | 25.60 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 588447.14 | 123.79 | 17-JAN-14:50 | 10.68 | 5.08 | 0.00 | 0.00 | 01-JAN-00:10 | 10.68 | 5.08 |
February | 12318482.38 | 457.82 | 18-FEB-15:00 | 6.70 | 3.14 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 3.14 |
March | 0.385933E+09 | 2364.31 | 03-MAR-14:30 | 15.00 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.51 |
April | 0.127816E+10 | 6736.57 | 07-APR-13:05 | 26.60 | 16.32 | 0.00 | 0.00 | 01-APR-00:10 | 26.60 | 16.32 |
May | 0.310001E+10 | 10195.56 | 30-MAY-14:00 | 29.40 | 16.93 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 16.93 |
June | 0.536827E+10 | 11276.41 | 19-JUN-13:30 | 34.70 | 23.81 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 23.81 |
July | 0.659690E+10 | 10568.64 | 10-JUL-13:50 | 32.70 | 20.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 20.82 |
August | 0.709454E+10 | 10064.52 | 01-AUG-14:40 | 30.97 | 22.94 | 0.00 | 0.00 | 01-AUG-00:10 | 30.97 | 22.94 |
September | 0.349865E+10 | 8796.31 | 01-SEP-14:40 | 30.77 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 30.77 | 17.43 |
October | 0.185509E+10 | 6184.66 | 04-OCT-14:50 | 23.98 | 19.09 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 19.09 |
November | 0.148928E+09 | 2045.81 | 03-NOV-14:20 | 17.60 | 10.78 | 0.00 | 0.00 | 01-NOV-00:10 | 17.60 | 10.78 |
December | 863197.94 | 150.13 | 16-DEC-14:30 | 10.30 | 4.45 | 0.00 | 0.00 | 01-DEC-00:10 | 10.30 | 4.45 |
Annual Sum or Average | 0.293402E+11 | 0.00 | ||||||||
Minimum of Months | 588447.14 | 123.79 | 6.70 | 3.14 | 0.00 | 0.00 | 6.70 | 3.14 | ||
Maximum of Months | 0.709454E+10 | 11276.41 | 34.70 | 23.81 | 0.00 | 0.00 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6157634.98 | 2239.29 | 05-JAN-05:01 | -7.8 | -9.6 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -9.6 |
February | 8323988.73 | 2134.76 | 09-FEB-05:01 | -8.3 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -9.9 |
March | 0.112167E+09 | 1683.72 | 22-MAR-05:01 | -2.3 | -5.1 | 0.00 | 0.00 | 01-MAR-00:10 | -2.3 | -5.1 |
April | 0.449862E+09 | 2049.80 | 10-APR-15:50 | 20.00 | 11.21 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.21 |
May | 0.138529E+10 | 4792.73 | 30-MAY-14:20 | 29.03 | 17.03 | 0.00 | 0.00 | 01-MAY-00:10 | 29.03 | 17.03 |
June | 0.295871E+10 | 4783.74 | 19-JUN-12:05 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.379938E+10 | 5110.86 | 10-JUL-10:10 | 30.18 | 20.97 | 0.00 | 0.00 | 01-JUL-00:10 | 30.18 | 20.97 |
August | 0.411893E+10 | 5367.00 | 14-AUG-10:10 | 27.88 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 27.88 | 23.11 |
September | 0.221734E+10 | 4947.66 | 05-SEP-15:20 | 25.93 | 21.57 | 0.00 | 0.00 | 01-SEP-00:10 | 25.93 | 21.57 |
October | 0.100175E+10 | 2834.61 | 04-OCT-15:40 | 23.17 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 23.17 | 19.12 |
November | 91712198.65 | 1360.06 | 22-NOV-06:01 | -2.2 | -3.5 | 0.00 | 0.00 | 01-NOV-00:10 | -2.2 | -3.5 |
December | 6413748.76 | 1552.86 | 23-DEC-06:11 | 2.93 | 2.42 | 0.00 | 0.00 | 01-DEC-00:10 | 2.93 | 2.42 |
Annual Sum or Average | 0.161560E+11 | 0.00 | ||||||||
Minimum of Months | 6157634.98 | 1360.06 | -8.3 | -9.9 | 0.00 | 0.00 | -8.3 | -9.9 | ||
Maximum of Months | 0.411893E+10 | 5367.00 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29002422.57 | 1561.02 | 19-JAN-06:11 | 2.40 | 1.71 | 0.00 | 0.00 | 01-JAN-00:10 | 2.40 | 1.71 |
February | 40338243.58 | 1827.59 | 25-FEB-06:01 | -4.4 | -7.2 | 0.00 | 0.00 | 01-FEB-00:10 | -4.4 | -7.2 |
March | 0.232476E+09 | 2196.88 | 09-MAR-06:11 | 2.20 | 1.95 | 0.00 | 0.00 | 01-MAR-00:10 | 2.20 | 1.95 |
April | 0.646132E+09 | 2187.03 | 21-APR-06:03 | 5.68 | 5.41 | 0.00 | 0.00 | 01-APR-00:10 | 5.68 | 5.41 |
May | 0.160153E+10 | 4662.66 | 30-MAY-12:10 | 29.50 | 17.65 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 17.65 |
June | 0.308732E+10 | 5433.44 | 19-JUN-12:08 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.388685E+10 | 5434.72 | 10-JUL-12:10 | 31.28 | 20.14 | 0.00 | 0.00 | 01-JUL-00:10 | 31.28 | 20.14 |
August | 0.438731E+10 | 5116.70 | 14-AUG-07:10 | 24.60 | 22.21 | 0.00 | 0.00 | 01-AUG-00:10 | 24.60 | 22.21 |
September | 0.273855E+10 | 5086.96 | 05-SEP-07:10 | 21.88 | 18.77 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 18.77 |
October | 0.167889E+10 | 3184.92 | 04-OCT-16:00 | 22.80 | 19.11 | 0.00 | 0.00 | 01-OCT-00:10 | 22.80 | 19.11 |
November | 0.232792E+09 | 1339.47 | 03-NOV-06:05 | 8.40 | 6.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8.40 | 6.00 |
December | 46344798.09 | 1758.93 | 21-DEC-07:02 | -0.6 | -3.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.6 | -3.3 |
Annual Sum or Average | 0.186075E+11 | 0.00 | ||||||||
Minimum of Months | 29002422.57 | 1339.47 | -4.4 | -7.2 | 0.00 | 0.00 | -4.4 | -7.2 | ||
Maximum of Months | 0.438731E+10 | 5434.72 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488254E+10 | 5849.03 | 20-JAN-17:00 | 5.60 | 3.19 | 0.155993E+10 | 2338.17 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.523824E+10 | 5906.66 | 24-FEB-17:00 | 6.70 | 1.42 | 0.145053E+10 | 2369.79 | 24-FEB-14:00 | 6.70 | 1.42 |
March | 0.799244E+10 | 8215.76 | 29-MAR-16:00 | 7.20 | 4.88 | 0.192117E+10 | 2606.63 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.924756E+10 | 12861.34 | 10-APR-16:00 | 20.00 | 11.13 | 0.183098E+10 | 2606.65 | 07-APR-13:20 | 20.00 | 11.13 |
May | 0.133964E+11 | 28249.04 | 30-MAY-05:12 | 18.53 | 14.51 | 0.206017E+10 | 2606.73 | 15-MAY-13:00 | 18.53 | 14.51 |
June | 0.165628E+11 | 31454.24 | 19-JUN-05:04 | 24.08 | 22.05 | 0.206766E+10 | 2606.70 | 26-JUN-09:20 | 25.37 | 19.69 |
July | 0.178075E+11 | 28673.13 | 24-JUL-05:12 | 20.97 | 20.39 | 0.192258E+10 | 2606.69 | 17-JUL-09:20 | 20.97 | 20.39 |
August | 0.189006E+11 | 31612.59 | 14-AUG-05:14 | 22.57 | 20.98 | 0.215884E+10 | 2608.21 | 14-AUG-09:20 | 27.40 | 22.88 |
September | 0.149008E+11 | 31314.00 | 05-SEP-05:14 | 20.60 | 18.00 | 0.191253E+10 | 2607.78 | 05-SEP-09:20 | 24.07 | 19.46 |
October | 0.124210E+11 | 14045.15 | 05-OCT-16:00 | 21.70 | 19.15 | 0.197625E+10 | 2606.71 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.737687E+10 | 10332.41 | 03-NOV-16:00 | 15.00 | 10.26 | 0.177780E+10 | 2606.65 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.624541E+10 | 6093.11 | 21-DEC-16:20 | 2.43 | -2.4 | 0.159051E+10 | 2445.62 | 21-DEC-14:00 | 2.43 | -2.4 |
Annual Sum or Average | 0.134972E+12 | 0.222290E+11 | ||||||||
Minimum of Months | 0.488254E+10 | 5849.03 | 2.43 | -2.4 | 0.145053E+10 | 2338.17 | 2.43 | -2.4 | ||
Maximum of Months | 0.189006E+11 | 31612.59 | 24.08 | 22.05 | 0.215884E+10 | 2608.21 | 27.40 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340787E+10 | 5620.39 | 20-JAN-16:40 | 6.13 | 3.40 | 0.150339E+10 | 2269.18 | 20-JAN-16:49 | 5.87 | 3.30 |
February | 0.362406E+10 | 5714.38 | 24-FEB-16:40 | 7.07 | 1.55 | 0.138713E+10 | 2311.76 | 02-FEB-14:00 | 7.07 | 1.55 |
March | 0.701829E+10 | 8221.05 | 29-MAR-16:00 | 7.20 | 4.88 | 0.182571E+10 | 2606.59 | 28-MAR-13:20 | 7.20 | 4.88 |
April | 0.866176E+10 | 13915.50 | 10-APR-15:40 | 20.00 | 11.28 | 0.177495E+10 | 2606.65 | 07-APR-13:20 | 20.00 | 11.28 |
May | 0.133577E+11 | 30456.95 | 30-MAY-05:12 | 18.53 | 14.51 | 0.204303E+10 | 2606.74 | 15-MAY-13:00 | 18.53 | 14.51 |
June | 0.172794E+11 | 33848.40 | 19-JUN-05:04 | 24.08 | 22.05 | 0.206596E+10 | 2606.66 | 23-JUN-09:20 | 27.80 | 18.74 |
July | 0.189753E+11 | 30971.44 | 24-JUL-05:12 | 20.97 | 20.39 | 0.192301E+10 | 2606.65 | 14-JUL-09:00 | 20.97 | 20.39 |
August | 0.197622E+11 | 31452.40 | 07-AUG-05:12 | 19.40 | 16.84 | 0.215810E+10 | 2606.70 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.144121E+11 | 31036.47 | 05-SEP-05:12 | 20.60 | 18.00 | 0.190456E+10 | 2606.67 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.110855E+11 | 14648.07 | 04-OCT-15:20 | 23.53 | 19.12 | 0.193522E+10 | 2606.70 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.594392E+10 | 9225.02 | 03-NOV-16:00 | 15.00 | 10.26 | 0.166807E+10 | 2606.62 | 03-NOV-13:20 | 15.00 | 10.26 |
December | 0.413008E+10 | 5636.17 | 21-DEC-16:20 | 2.43 | -2.4 | 0.148836E+10 | 2316.21 | 20-DEC-14:00 | 2.43 | -2.4 |
Annual Sum or Average | 0.127658E+12 | 0.216775E+11 | ||||||||
Minimum of Months | 0.340787E+10 | 5620.39 | 2.43 | -2.4 | 0.138713E+10 | 2269.18 | 2.43 | -2.4 | ||
Maximum of Months | 0.197622E+11 | 33848.40 | 24.08 | 22.05 | 0.215810E+10 | 2606.74 | 27.80 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102735E+09 | 948.67 | 20-JAN-15:20 | 7.60 | 3.92 | 0.305247E+09 | 422.45 | 20-JAN-14:00 | 7.60 | 3.92 |
February | 0.138280E+09 | 973.73 | 24-FEB-15:40 | 7.97 | 1.96 | 0.277901E+09 | 429.25 | 17-FEB-14:00 | 7.97 | 1.96 |
March | 0.789532E+09 | 1455.14 | 28-MAR-13:50 | 13.40 | 8.46 | 0.354590E+09 | 549.46 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.162295E+10 | 3843.85 | 07-APR-14:20 | 25.93 | 15.95 | 0.354427E+09 | 549.50 | 07-APR-13:20 | 25.93 | 15.95 |
May | 0.333459E+10 | 8608.40 | 30-MAY-06:03 | 20.47 | 15.45 | 0.425316E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.521332E+10 | 9346.21 | 26-JUN-05:12 | 20.97 | 17.23 | 0.435436E+09 | 549.51 | 20-JUN-13:09 | 20.97 | 17.23 |
July | 0.610239E+10 | 9828.76 | 04-JUL-13:32 | 27.80 | 18.52 | 0.406068E+09 | 549.59 | 10-JUL-13:00 | 32.80 | 20.89 |
August | 0.608509E+10 | 11038.43 | 13-AUG-15:52 | 30.00 | 20.46 | 0.454907E+09 | 549.51 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.360538E+10 | 6934.58 | 05-SEP-06:03 | 20.78 | 18.13 | 0.398086E+09 | 549.51 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.221897E+10 | 4014.28 | 04-OCT-13:50 | 24.50 | 18.89 | 0.392381E+09 | 549.50 | 02-OCT-13:20 | 24.50 | 18.89 |
November | 0.700028E+09 | 1479.71 | 03-NOV-14:20 | 17.60 | 10.78 | 0.325373E+09 | 549.47 | 03-NOV-13:00 | 17.60 | 10.78 |
December | 0.111576E+09 | 978.91 | 20-DEC-14:00 | 10.00 | 5.91 | 0.295357E+09 | 431.51 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.300249E+11 | 0.442509E+10 | ||||||||
Minimum of Months | 0.102735E+09 | 948.67 | 7.60 | 1.96 | 0.277901E+09 | 422.45 | 7.60 | 1.96 | ||
Maximum of Months | 0.610239E+10 | 11038.43 | 30.00 | 20.46 | 0.454907E+09 | 549.59 | 32.80 | 20.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149099E+09 | 758.42 | 19-JAN-10:20 | 7.80 | 4.36 | 0.196161E+09 | 311.59 | 19-JAN-10:20 | 7.80 | 4.36 |
February | 0.229371E+09 | 787.45 | 22-FEB-10:05 | 0.87 | -3.0 | 0.180653E+09 | 322.25 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.819396E+09 | 3391.34 | 29-MAR-09:30 | 6.15 | 3.19 | 0.244950E+09 | 347.88 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.171966E+10 | 6084.36 | 28-APR-08:40 | 15.53 | 8.75 | 0.237419E+09 | 347.89 | 26-APR-09:00 | 15.53 | 8.75 |
May | 0.340450E+10 | 12856.13 | 29-MAY-08:52 | 26.10 | 16.72 | 0.272528E+09 | 348.42 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.454141E+10 | 12367.85 | 25-JUN-08:52 | 25.60 | 23.63 | 0.276139E+09 | 348.41 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.525954E+10 | 12922.31 | 02-JUL-08:32 | 25.20 | 21.54 | 0.257430E+09 | 348.96 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.586593E+10 | 12349.91 | 13-AUG-09:12 | 28.17 | 19.21 | 0.288409E+09 | 348.50 | 02-AUG-09:00 | 28.17 | 19.21 |
September | 0.344474E+10 | 12787.74 | 04-SEP-08:32 | 23.53 | 18.61 | 0.253941E+09 | 348.50 | 05-SEP-09:50 | 24.32 | 19.54 |
October | 0.223241E+10 | 5375.05 | 05-OCT-09:10 | 19.08 | 16.88 | 0.257836E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.619778E+09 | 1994.57 | 03-NOV-09:30 | 13.05 | 8.24 | 0.216772E+09 | 347.88 | 08-NOV-10:20 | 11.67 | 9.14 |
December | 0.225804E+09 | 792.95 | 20-DEC-09:50 | 7.93 | 4.87 | 0.190504E+09 | 322.31 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.285116E+11 | 0.287274E+10 | ||||||||
Minimum of Months | 0.149099E+09 | 758.42 | 0.87 | -3.0 | 0.180653E+09 | 311.59 | 1.13 | -2.8 | ||
Maximum of Months | 0.586593E+10 | 12922.31 | 28.17 | 23.63 | 0.288409E+09 | 348.96 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.764221E+09 | 5461.11 | 19-JAN-13:25 | 9.40 | 3.94 | 0.337758E+09 | 549.50 | 30-JAN-14:30 | 2.80 | -1.1 |
February | 0.103383E+10 | 5899.62 | 02-FEB-13:50 | 5.78 | -0.8 | 0.312700E+09 | 549.49 | 03-FEB-14:00 | -1.7 | -5.1 |
March | 0.232884E+10 | 8351.12 | 03-MAR-13:30 | 14.70 | 8.33 | 0.394893E+09 | 549.51 | 23-MAR-13:00 | 5.00 | 1.08 |
April | 0.292650E+10 | 9641.49 | 07-APR-12:30 | 26.15 | 15.90 | 0.368261E+09 | 549.83 | 07-APR-13:09 | 26.60 | 16.32 |
May | 0.435695E+10 | 15769.72 | 29-MAY-11:32 | 28.53 | 18.30 | 0.426134E+09 | 550.16 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.598210E+10 | 12068.39 | 18-JUN-14:02 | 26.10 | 22.31 | 0.435329E+09 | 549.80 | 19-JUN-13:30 | 34.70 | 23.81 |
July | 0.712046E+10 | 15868.15 | 30-JUL-11:32 | 26.10 | 23.28 | 0.406198E+09 | 550.03 | 10-JUL-13:50 | 26.10 | 23.28 |
August | 0.871313E+10 | 15836.94 | 13-AUG-12:32 | 30.93 | 19.36 | 0.455304E+09 | 550.07 | 17-AUG-13:50 | 31.10 | 24.82 |
September | 0.646437E+10 | 16216.73 | 04-SEP-12:32 | 26.10 | 18.14 | 0.400743E+09 | 560.56 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.589909E+10 | 16411.80 | 15-OCT-12:12 | 20.20 | 13.39 | 0.408040E+09 | 551.32 | 04-OCT-13:09 | 20.20 | 13.39 |
November | 0.198084E+10 | 10273.97 | 02-NOV-13:00 | 15.60 | 8.21 | 0.363760E+09 | 549.68 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.991208E+09 | 5693.56 | 21-DEC-13:25 | 3.05 | -1.7 | 0.332842E+09 | 549.50 | 14-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.485615E+11 | 0.464196E+10 | ||||||||
Minimum of Months | 0.764221E+09 | 5461.11 | 3.05 | -1.7 | 0.312700E+09 | 549.49 | -1.7 | -5.1 | ||
Maximum of Months | 0.871313E+10 | 16411.80 | 30.93 | 23.28 | 0.455304E+09 | 560.56 | 34.70 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161770E+09 | 1177.61 | 20-JAN-15:40 | 7.40 | 3.86 | 0.198531E+09 | 338.68 | 20-JAN-16:30 | 6.40 | 3.51 |
February | 0.234156E+09 | 1886.03 | 24-FEB-15:30 | 8.05 | 2.04 | 0.183102E+09 | 347.82 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.967362E+09 | 5186.53 | 29-MAR-15:50 | 7.20 | 4.93 | 0.235393E+09 | 347.84 | 28-MAR-13:20 | 7.20 | 4.93 |
April | 0.180848E+10 | 7850.19 | 09-APR-16:03 | 17.02 | 14.08 | 0.227934E+09 | 347.85 | 07-APR-13:20 | 17.02 | 14.08 |
May | 0.325183E+10 | 11719.50 | 21-MAY-14:53 | 21.10 | 13.81 | 0.269776E+09 | 347.88 | 15-MAY-13:00 | 21.10 | 13.81 |
June | 0.476590E+10 | 13993.55 | 18-JUN-16:02 | 25.50 | 22.07 | 0.275819E+09 | 347.86 | 20-JUN-13:09 | 26.78 | 17.87 |
July | 0.525059E+10 | 14202.20 | 02-JUL-15:52 | 25.00 | 20.82 | 0.257280E+09 | 347.86 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.586464E+10 | 13939.78 | 13-AUG-15:52 | 30.00 | 20.46 | 0.288276E+09 | 347.86 | 08-AUG-13:50 | 30.00 | 20.46 |
September | 0.341855E+10 | 13742.07 | 10-SEP-16:02 | 23.22 | 12.85 | 0.252675E+09 | 347.86 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.239308E+10 | 10024.68 | 15-OCT-15:32 | 19.80 | 12.41 | 0.251130E+09 | 347.85 | 12-OCT-13:00 | 19.80 | 12.41 |
November | 0.592064E+09 | 3494.34 | 03-NOV-15:30 | 16.10 | 10.65 | 0.211383E+09 | 347.85 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.182745E+09 | 866.28 | 08-DEC-15:40 | 6.30 | 2.04 | 0.192074E+09 | 336.87 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.288912E+11 | 0.284337E+10 | ||||||||
Minimum of Months | 0.161770E+09 | 866.28 | 6.30 | 2.04 | 0.183102E+09 | 336.87 | 6.20 | 1.96 | ||
Maximum of Months | 0.586464E+10 | 14202.20 | 30.00 | 22.07 | 0.288276E+09 | 347.88 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133679E+09 | 922.77 | 20-JAN-15:00 | 7.80 | 3.97 | 0.305602E+09 | 417.08 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.129936E+09 | 937.85 | 24-FEB-14:10 | 9.22 | 3.12 | 0.278300E+09 | 421.34 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.751047E+09 | 1215.48 | 28-MAR-14:00 | 13.30 | 8.41 | 0.347042E+09 | 499.45 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.131642E+10 | 2012.06 | 10-APR-14:00 | 20.60 | 10.45 | 0.344686E+09 | 549.50 | 07-APR-13:20 | 20.60 | 10.45 |
May | 0.235706E+10 | 4248.51 | 30-MAY-13:10 | 29.90 | 17.82 | 0.419480E+09 | 549.51 | 15-MAY-13:00 | 29.90 | 17.82 |
June | 0.395721E+10 | 7131.93 | 26-JUN-06:03 | 21.97 | 17.81 | 0.434863E+09 | 549.50 | 23-JUN-09:20 | 21.97 | 17.81 |
July | 0.499711E+10 | 7181.15 | 17-JUL-06:03 | 22.48 | 19.71 | 0.405444E+09 | 549.50 | 12-JUL-13:00 | 22.48 | 19.71 |
August | 0.528798E+10 | 6978.15 | 14-AUG-06:03 | 23.48 | 21.76 | 0.454880E+09 | 549.51 | 08-AUG-13:20 | 23.48 | 21.76 |
September | 0.350925E+10 | 6462.25 | 05-SEP-06:03 | 20.78 | 18.13 | 0.401494E+09 | 549.51 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.240573E+10 | 3574.80 | 05-OCT-14:00 | 23.30 | 18.86 | 0.407208E+09 | 549.51 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.109848E+10 | 1507.24 | 03-NOV-14:00 | 17.80 | 10.67 | 0.343815E+09 | 549.49 | 03-NOV-13:20 | 17.80 | 10.67 |
December | 0.334642E+09 | 1018.92 | 20-DEC-13:50 | 9.90 | 5.86 | 0.298055E+09 | 443.16 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.262785E+11 | 0.444087E+10 | ||||||||
Minimum of Months | 0.129936E+09 | 922.77 | 7.80 | 3.12 | 0.278300E+09 | 417.08 | 7.80 | 2.95 | ||
Maximum of Months | 0.528798E+10 | 7181.15 | 29.90 | 21.76 | 0.454880E+09 | 549.51 | 29.90 | 21.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177078E+09 | 735.99 | 27-JAN-10:20 | 4.60 | 1.51 | 0.196972E+09 | 306.40 | 27-JAN-10:30 | 4.70 | 1.53 |
February | 0.245646E+09 | 739.83 | 22-FEB-10:10 | 0.87 | -3.0 | 0.180783E+09 | 308.02 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.806602E+09 | 2067.44 | 29-MAR-09:30 | 6.15 | 3.19 | 0.242040E+09 | 347.88 | 23-MAR-09:20 | 6.15 | 3.19 |
April | 0.139883E+10 | 3985.55 | 28-APR-09:10 | 16.28 | 8.96 | 0.237060E+09 | 347.88 | 26-APR-09:00 | 16.28 | 8.96 |
May | 0.260288E+10 | 10561.97 | 29-MAY-10:22 | 27.25 | 17.87 | 0.271494E+09 | 348.15 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.374238E+10 | 10702.32 | 25-JUN-08:42 | 25.40 | 23.51 | 0.276065E+09 | 348.15 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.456110E+10 | 9241.58 | 09-JUL-09:32 | 29.43 | 25.37 | 0.257309E+09 | 348.49 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.545034E+10 | 8645.84 | 20-AUG-10:32 | 25.37 | 15.92 | 0.288570E+09 | 348.26 | 18-AUG-09:30 | 25.37 | 15.92 |
September | 0.351668E+10 | 10511.20 | 10-SEP-09:12 | 20.57 | 13.59 | 0.255517E+09 | 348.07 | 06-SEP-09:30 | 20.57 | 13.59 |
October | 0.257433E+10 | 4819.97 | 05-OCT-09:20 | 19.27 | 16.99 | 0.263299E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.926638E+09 | 2313.00 | 03-NOV-09:30 | 13.05 | 8.24 | 0.230847E+09 | 347.88 | 08-NOV-10:20 | 11.67 | 9.14 |
December | 0.405700E+09 | 825.77 | 20-DEC-09:50 | 7.93 | 4.87 | 0.197111E+09 | 332.77 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.264082E+11 | 0.289707E+10 | ||||||||
Minimum of Months | 0.177078E+09 | 735.99 | 0.87 | -3.0 | 0.180783E+09 | 306.40 | 1.13 | -2.8 | ||
Maximum of Months | 0.545034E+10 | 10702.32 | 29.43 | 25.37 | 0.288570E+09 | 348.49 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313919E+09 | 1325.23 | 19-JAN-14:20 | 9.23 | 3.67 | 0.305153E+09 | 535.36 | 19-JAN-14:30 | 9.15 | 3.65 |
February | 0.381819E+09 | 2013.14 | 25-FEB-13:10 | 2.88 | -1.9 | 0.280390E+09 | 533.63 | 02-FEB-14:39 | 2.88 | -1.9 |
March | 0.103682E+10 | 4211.53 | 03-MAR-13:20 | 14.60 | 8.23 | 0.364060E+09 | 549.51 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.162751E+10 | 6506.74 | 07-APR-12:00 | 25.60 | 15.40 | 0.346151E+09 | 549.51 | 12-APR-13:20 | 11.47 | 3.03 |
May | 0.260468E+10 | 10330.00 | 30-MAY-12:00 | 29.40 | 17.58 | 0.405966E+09 | 553.09 | 30-MAY-12:09 | 29.50 | 17.65 |
June | 0.465733E+10 | 11890.92 | 19-JUN-12:00 | 36.70 | 24.28 | 0.432613E+09 | 641.17 | 19-JUN-12:09 | 36.42 | 24.23 |
July | 0.662741E+10 | 11327.53 | 07-JUL-12:00 | 33.90 | 23.31 | 0.406264E+09 | 607.51 | 07-JUL-12:09 | 33.72 | 23.31 |
August | 0.868154E+10 | 12817.65 | 20-AUG-12:32 | 27.43 | 15.69 | 0.456368E+09 | 611.62 | 18-AUG-12:09 | 27.43 | 15.69 |
September | 0.618655E+10 | 12906.20 | 10-SEP-14:32 | 24.40 | 14.07 | 0.401673E+09 | 595.47 | 01-SEP-12:09 | 24.40 | 14.07 |
October | 0.548774E+10 | 13041.31 | 15-OCT-12:12 | 20.20 | 13.39 | 0.411158E+09 | 569.93 | 04-OCT-13:20 | 20.20 | 13.39 |
November | 0.161850E+10 | 8183.05 | 02-NOV-12:10 | 15.10 | 8.04 | 0.352961E+09 | 549.62 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.658533E+09 | 2972.27 | 02-DEC-13:50 | 6.60 | 1.33 | 0.312572E+09 | 549.50 | 18-DEC-14:20 | 7.23 | 2.78 |
Annual Sum or Average | 0.398824E+11 | 0.447533E+10 | ||||||||
Minimum of Months | 0.313919E+09 | 1325.23 | 2.88 | -1.9 | 0.280390E+09 | 533.63 | 2.88 | -1.9 | ||
Maximum of Months | 0.868154E+10 | 13041.31 | 36.70 | 24.28 | 0.456368E+09 | 641.17 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178155E+09 | 839.91 | 20-JAN-16:00 | 7.20 | 3.80 | 0.197547E+09 | 328.44 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.219296E+09 | 1020.37 | 22-FEB-16:30 | 3.85 | -0.7 | 0.181635E+09 | 338.68 | 22-FEB-16:49 | 3.48 | -0.7 |
March | 0.850199E+09 | 3103.59 | 27-MAR-16:50 | 21.28 | 15.57 | 0.235125E+09 | 347.84 | 03-MAR-14:20 | 21.28 | 15.57 |
April | 0.138777E+10 | 5306.67 | 10-APR-16:00 | 20.00 | 11.13 | 0.229444E+09 | 347.85 | 07-APR-13:20 | 20.00 | 11.13 |
May | 0.238289E+10 | 6548.02 | 30-MAY-16:00 | 28.30 | 17.60 | 0.269115E+09 | 347.87 | 15-MAY-13:00 | 28.30 | 17.60 |
June | 0.393724E+10 | 10813.56 | 18-JUN-16:21 | 25.30 | 22.03 | 0.276061E+09 | 347.86 | 23-JUN-09:20 | 27.80 | 18.74 |
July | 0.455130E+10 | 10717.30 | 02-JUL-16:32 | 24.60 | 20.65 | 0.257236E+09 | 347.86 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.542909E+10 | 11052.06 | 20-AUG-16:32 | 25.20 | 17.51 | 0.288565E+09 | 347.86 | 08-AUG-13:20 | 25.20 | 17.51 |
September | 0.344013E+10 | 11240.63 | 10-SEP-17:12 | 22.43 | 12.33 | 0.255155E+09 | 347.86 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.262492E+10 | 8109.50 | 15-OCT-15:32 | 19.80 | 12.41 | 0.262165E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.842182E+09 | 3286.69 | 03-NOV-15:30 | 16.10 | 10.65 | 0.224011E+09 | 347.85 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.336582E+09 | 849.76 | 21-DEC-15:40 | 2.97 | -2.1 | 0.195177E+09 | 332.17 | 21-DEC-15:50 | 2.88 | -2.1 |
Annual Sum or Average | 0.261797E+11 | 0.287124E+10 | ||||||||
Minimum of Months | 0.178155E+09 | 839.91 | 2.97 | -2.1 | 0.181635E+09 | 328.44 | 2.88 | -2.1 | ||
Maximum of Months | 0.542909E+10 | 11240.63 | 28.30 | 22.03 | 0.288565E+09 | 347.87 | 28.30 | 19.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189513E+09 | 994.88 | 20-JAN-15:10 | 7.70 | 3.95 | 0.306609E+09 | 436.83 | 20-JAN-14:00 | 7.70 | 3.95 |
February | 0.235309E+09 | 1016.44 | 24-FEB-15:40 | 7.97 | 1.96 | 0.280071E+09 | 441.56 | 24-FEB-14:00 | 7.97 | 1.96 |
March | 0.107629E+10 | 1382.89 | 27-MAR-16:00 | 22.20 | 16.34 | 0.363038E+09 | 548.78 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.177756E+10 | 3380.86 | 10-APR-14:00 | 20.60 | 10.45 | 0.364971E+09 | 549.50 | 07-APR-13:20 | 20.60 | 10.45 |
May | 0.332508E+10 | 7996.38 | 30-MAY-06:03 | 20.47 | 15.45 | 0.430312E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.503334E+10 | 8094.75 | 26-JUN-05:12 | 20.97 | 17.23 | 0.435853E+09 | 550.35 | 19-JUN-13:20 | 20.97 | 17.23 |
July | 0.579052E+10 | 8795.69 | 09-JUL-14:41 | 27.95 | 24.21 | 0.406084E+09 | 550.46 | 25-JUL-13:20 | 28.53 | 24.38 |
August | 0.583273E+10 | 7734.46 | 22-AUG-06:03 | 25.18 | 17.71 | 0.455205E+09 | 549.93 | 14-AUG-09:20 | 25.18 | 17.71 |
September | 0.367905E+10 | 7328.83 | 05-SEP-06:03 | 20.78 | 18.13 | 0.401060E+09 | 549.77 | 05-SEP-09:20 | 24.07 | 19.46 |
October | 0.245147E+10 | 3849.21 | 05-OCT-14:00 | 23.30 | 18.86 | 0.404380E+09 | 549.51 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.983459E+09 | 1778.76 | 03-NOV-14:00 | 17.80 | 10.67 | 0.338605E+09 | 549.49 | 03-NOV-13:20 | 17.80 | 10.67 |
December | 0.315954E+09 | 1049.31 | 20-DEC-14:00 | 10.00 | 5.91 | 0.297823E+09 | 452.17 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.306903E+11 | 0.448401E+10 | ||||||||
Minimum of Months | 0.189513E+09 | 994.88 | 7.70 | 1.96 | 0.280071E+09 | 436.83 | 7.70 | 1.96 | ||
Maximum of Months | 0.583273E+10 | 8795.69 | 27.95 | 24.21 | 0.455205E+09 | 550.46 | 28.53 | 24.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175088E+09 | 812.12 | 27-JAN-10:00 | 4.40 | 1.46 | 0.146052E+09 | 322.15 | 27-JAN-11:09 | 5.00 | 1.60 |
February | 0.236921E+09 | 864.30 | 22-FEB-09:50 | 0.50 | -3.2 | 0.136141E+09 | 337.95 | 22-FEB-11:09 | 2.38 | -2.1 |
March | 0.863796E+09 | 5411.41 | 29-MAR-12:02 | 7.80 | 5.26 | 0.184812E+09 | 356.45 | 29-MAR-12:09 | 7.80 | 5.26 |
April | 0.171309E+10 | 6472.24 | 28-APR-10:05 | 17.30 | 9.69 | 0.178236E+09 | 356.47 | 26-APR-10:09 | 17.30 | 9.69 |
May | 0.323919E+10 | 12800.15 | 28-MAY-08:22 | 20.00 | 12.65 | 0.203175E+09 | 356.47 | 15-MAY-14:09 | 20.00 | 12.65 |
June | 0.423188E+10 | 13382.02 | 25-JUN-08:42 | 25.40 | 23.51 | 0.204823E+09 | 356.46 | 02-JUN-12:09 | 25.40 | 23.51 |
July | 0.487120E+10 | 13862.45 | 02-JUL-08:21 | 25.00 | 21.47 | 0.191571E+09 | 356.46 | 11-JUL-10:09 | 25.18 | 17.11 |
August | 0.549310E+10 | 12547.27 | 27-AUG-09:52 | 26.10 | 21.81 | 0.213892E+09 | 356.46 | 08-AUG-10:09 | 26.10 | 21.81 |
September | 0.334068E+10 | 12910.34 | 10-SEP-09:12 | 20.57 | 13.59 | 0.189147E+09 | 356.47 | 19-SEP-10:09 | 20.00 | 15.38 |
October | 0.231409E+10 | 6294.22 | 04-OCT-10:05 | 21.38 | 18.15 | 0.193183E+09 | 356.46 | 10-OCT-10:09 | 14.60 | 11.65 |
November | 0.698525E+09 | 5178.86 | 01-NOV-12:02 | 12.88 | 7.12 | 0.166376E+09 | 356.46 | 09-NOV-15:09 | 13.80 | 12.65 |
December | 0.273366E+09 | 1000.18 | 20-DEC-09:40 | 7.57 | 4.72 | 0.144899E+09 | 341.55 | 20-DEC-11:09 | 8.90 | 5.16 |
Annual Sum or Average | 0.274509E+11 | 0.215231E+10 | ||||||||
Minimum of Months | 0.175088E+09 | 812.12 | 0.50 | -3.2 | 0.136141E+09 | 322.15 | 2.38 | -2.1 | ||
Maximum of Months | 0.549310E+10 | 13862.45 | 26.10 | 23.51 | 0.213892E+09 | 356.47 | 26.10 | 23.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.993067E+09 | 5675.19 | 19-JAN-13:25 | 9.40 | 3.94 | 0.343223E+09 | 549.50 | 30-JAN-14:30 | 2.80 | -1.1 |
February | 0.128653E+10 | 6284.27 | 02-FEB-13:40 | 5.97 | -0.5 | 0.319838E+09 | 549.49 | 03-FEB-10:30 | -3.9 | -6.8 |
March | 0.270407E+10 | 8405.92 | 29-MAR-13:00 | 7.80 | 5.26 | 0.405362E+09 | 549.51 | 23-MAR-13:00 | 7.80 | 5.26 |
April | 0.310798E+10 | 9057.66 | 07-APR-12:30 | 26.15 | 15.90 | 0.377473E+09 | 550.28 | 07-APR-13:20 | 26.50 | 16.25 |
May | 0.432981E+10 | 14303.40 | 29-MAY-12:32 | 27.77 | 17.46 | 0.430851E+09 | 550.61 | 30-MAY-13:20 | 29.80 | 17.64 |
June | 0.577269E+10 | 9197.56 | 19-JUN-12:07 | 36.42 | 24.23 | 0.435893E+09 | 550.66 | 19-JUN-13:20 | 34.80 | 23.85 |
July | 0.678084E+10 | 14331.71 | 30-JUL-11:32 | 26.10 | 23.28 | 0.406291E+09 | 550.80 | 13-JUL-13:20 | 26.10 | 23.28 |
August | 0.842781E+10 | 14758.10 | 20-AUG-12:32 | 27.43 | 15.69 | 0.455704E+09 | 557.83 | 30-AUG-13:20 | 27.77 | 15.58 |
September | 0.654109E+10 | 14893.75 | 10-SEP-11:12 | 22.40 | 13.68 | 0.403203E+09 | 576.11 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.633504E+10 | 14579.39 | 22-OCT-12:02 | 21.28 | 16.35 | 0.414620E+09 | 568.15 | 04-OCT-13:20 | 21.28 | 16.35 |
November | 0.247713E+10 | 10707.22 | 02-NOV-12:40 | 15.40 | 8.14 | 0.377111E+09 | 549.63 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.137788E+10 | 6685.86 | 21-DEC-13:04 | 2.88 | -1.7 | 0.342953E+09 | 549.50 | 14-DEC-14:09 | 2.88 | -1.7 |
Annual Sum or Average | 0.501339E+11 | 0.471252E+10 | ||||||||
Minimum of Months | 0.993067E+09 | 5675.19 | 2.88 | -1.7 | 0.319838E+09 | 549.49 | -3.9 | -6.8 | ||
Maximum of Months | 0.842781E+10 | 14893.75 | 36.42 | 24.23 | 0.455704E+09 | 576.11 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226862E+09 | 1319.82 | 20-JAN-15:50 | 7.30 | 3.83 | 0.200284E+09 | 340.05 | 19-JAN-14:00 | 7.30 | 3.83 |
February | 0.310851E+09 | 2189.03 | 24-FEB-15:30 | 8.05 | 2.04 | 0.185253E+09 | 347.83 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.116226E+10 | 5197.58 | 29-MAR-15:50 | 7.20 | 4.93 | 0.241274E+09 | 347.84 | 29-MAR-13:20 | 7.20 | 4.93 |
April | 0.189292E+10 | 7697.11 | 09-APR-16:03 | 17.02 | 14.08 | 0.234606E+09 | 347.85 | 07-APR-13:20 | 17.02 | 14.08 |
May | 0.321846E+10 | 12678.14 | 28-MAY-15:02 | 26.23 | 15.49 | 0.272920E+09 | 347.87 | 15-MAY-13:00 | 26.23 | 15.49 |
June | 0.461634E+10 | 14119.69 | 18-JUN-16:31 | 25.20 | 22.01 | 0.276145E+09 | 347.86 | 26-JUN-09:20 | 25.37 | 19.69 |
July | 0.501709E+10 | 13823.32 | 04-JUL-16:41 | 25.18 | 18.20 | 0.257332E+09 | 347.86 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.567201E+10 | 13312.43 | 20-AUG-16:32 | 25.20 | 17.51 | 0.288461E+09 | 348.14 | 14-AUG-09:20 | 25.20 | 17.51 |
September | 0.346069E+10 | 13903.02 | 10-SEP-15:51 | 23.30 | 12.88 | 0.254432E+09 | 348.03 | 05-SEP-09:20 | 23.30 | 12.88 |
October | 0.257625E+10 | 6989.37 | 04-OCT-15:20 | 23.53 | 19.12 | 0.258048E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.786756E+09 | 3676.55 | 03-NOV-15:30 | 16.10 | 10.65 | 0.219791E+09 | 347.85 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.309456E+09 | 1135.73 | 08-DEC-15:40 | 6.30 | 2.04 | 0.195539E+09 | 347.78 | 21-DEC-14:00 | 3.30 | -1.8 |
Annual Sum or Average | 0.292500E+11 | 0.288409E+10 | ||||||||
Minimum of Months | 0.226862E+09 | 1135.73 | 6.30 | 2.04 | 0.185253E+09 | 340.05 | 3.30 | -1.8 | ||
Maximum of Months | 0.567201E+10 | 14119.69 | 26.23 | 22.01 | 0.288461E+09 | 348.14 | 27.97 | 21.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.586049E+09 | 19815.38 | 02-JAN-05:01 | -12.1 |
February | 3851209.53 | 16206.68 | 06-FEB-07:02 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.589901E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.586049E+09 | 19815.38 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434734E+10 | 14850.66 | 02-JAN-06:12 | -11.7 |
February | 0.348777E+10 | 15152.22 | 06-FEB-06:12 | -13.0 |
March | 0.155745E+10 | 9123.80 | 20-MAR-06:01 | -0.6 |
April | 0.744731E+09 | 7645.85 | 03-APR-06:02 | 2.38 |
May | 0.216079E+09 | 2937.09 | 30-MAY-05:12 | 18.53 |
June | 49171381.20 | 4524.23 | 19-JUN-05:02 | 24.08 |
July | 23620893.81 | 3784.28 | 25-JUL-05:02 | 23.90 |
August | 42464664.44 | 3388.69 | 01-AUG-05:03 | 23.90 |
September | 0.153592E+09 | 2716.32 | 01-SEP-05:03 | 24.08 |
October | 0.489089E+09 | 3137.93 | 19-OCT-05:03 | 5.37 |
November | 0.172231E+10 | 11115.50 | 24-NOV-06:13 | -4.4 |
December | 0.296300E+10 | 10456.47 | 11-DEC-06:12 | 1.70 |
Annual Sum or Average | 0.157966E+11 | |||
Minimum of Months | 23620893.81 | 2716.32 | -13.0 | |
Maximum of Months | 0.434734E+10 | 15152.22 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233970E+10 | 9455.99 | 02-JAN-07:08 | -11.6 |
February | 0.173784E+10 | 7716.41 | 06-FEB-07:11 | -13.1 |
March | 0.111912E+10 | 3298.47 | 01-MAR-11:05 | 13.90 |
April | 0.422873E+09 | 2921.97 | 16-APR-15:53 | 21.10 |
May | 89107477.77 | 3260.72 | 28-MAY-15:02 | 26.23 |
June | 16799494.57 | 2796.84 | 04-JUN-14:02 | 24.32 |
July | 24914681.05 | 3017.98 | 09-JUL-14:41 | 27.95 |
August | 18499008.57 | 3272.24 | 20-AUG-13:52 | 28.90 |
September | 24331817.60 | 3915.30 | 10-SEP-09:52 | 21.70 |
October | 0.140858E+09 | 4000.60 | 29-OCT-13:23 | 12.25 |
November | 0.102747E+10 | 3773.26 | 24-NOV-07:02 | -4.3 |
December | 0.150308E+10 | 3908.14 | 26-DEC-07:03 | 6.70 |
Annual Sum or Average | 0.846460E+10 | |||
Minimum of Months | 16799494.57 | 2796.84 | -13.1 | |
Maximum of Months | 0.233970E+10 | 9455.99 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175310E+10 | 8337.90 | 02-JAN-08:17 | -10.9 |
February | 0.114747E+10 | 4023.59 | 06-FEB-07:01 | -13.2 |
March | 0.654884E+09 | 1762.97 | 20-MAR-07:09 | -0.1 |
April | 0.192783E+09 | 1516.18 | 14-APR-07:05 | 5.18 |
May | 14398558.36 | 1419.71 | 14-MAY-14:33 | 14.07 |
June | 11137015.45 | 1818.58 | 19-JUN-05:02 | 24.08 |
July | 17040267.84 | 2066.39 | 25-JUL-05:02 | 23.90 |
August | 15275794.73 | 2262.46 | 20-AUG-13:52 | 28.90 |
September | 21736235.09 | 2375.56 | 10-SEP-15:11 | 24.03 |
October | 34690401.02 | 2484.34 | 09-OCT-13:43 | 13.80 |
November | 0.549837E+09 | 2049.17 | 24-NOV-08:08 | -3.5 |
December | 0.992127E+09 | 2133.26 | 17-DEC-13:25 | 12.20 |
Annual Sum or Average | 0.540448E+10 | |||
Minimum of Months | 11137015.45 | 1419.71 | -13.2 | |
Maximum of Months | 0.175310E+10 | 8337.90 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942449E+09 | 21490.73 | 02-JAN-05:01 | -12.1 |
February | 0.248181E+09 | 18708.74 | 06-FEB-06:01 | -12.9 |
March | 9943367.90 | 16456.32 | 20-MAR-06:01 | -0.6 |
April | 1367006.79 | 13670.07 | 03-APR-06:02 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 33329773.78 | 17729.01 | 24-NOV-06:01 | -4.4 |
December | 66265886.49 | 17145.39 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.130154E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.942449E+09 | 21490.73 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267381E+10 | 30733.76 | 02-JAN-00:02 | -10.7 |
February | 0.161293E+10 | 29815.57 | 06-FEB-05:01 | -13.2 |
March | 0.269368E+09 | 26829.90 | 20-MAR-05:01 | -1.5 |
April | 38440558.41 | 25688.51 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.502948E+09 | 27390.30 | 24-NOV-06:01 | -4.4 |
December | 0.858465E+09 | 28001.26 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.595596E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.267381E+10 | 30733.76 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399343E+10 | 10819.44 | 02-JAN-00:02 | -10.7 |
February | 0.321551E+10 | 10608.57 | 05-FEB-22:42 | -12.0 |
March | 0.847489E+09 | 9748.35 | 13-MAR-04:01 | -0.1 |
April | 0.156403E+09 | 9113.23 | 03-APR-05:11 | 2.60 |
May | 832600.40 | 4163.00 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 18290974.97 | 7884.00 | 10-OCT-06:02 | 8.58 |
November | 0.102960E+10 | 9731.34 | 20-NOV-05:01 | 0.50 |
December | 0.236628E+10 | 10301.65 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.116278E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.399343E+10 | 10819.44 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221617E+10 | 11658.54 | 02-JAN-00:02 | -10.7 |
February | 0.158843E+10 | 11352.35 | 05-FEB-22:42 | -12.0 |
March | 0.385756E+09 | 10534.72 | 13-MAR-04:01 | -0.1 |
April | 74294117.92 | 9835.54 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 8520933.99 | 6299.54 | 10-OCT-06:02 | 8.58 |
November | 0.518163E+09 | 10521.18 | 20-NOV-05:01 | 0.50 |
December | 0.124927E+10 | 11007.22 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.604060E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.221617E+10 | 11658.54 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270717E+10 | 14440.04 | 02-JAN-00:02 | -10.7 |
February | 0.192769E+10 | 13998.08 | 05-FEB-22:42 | -12.0 |
March | 0.549937E+09 | 12955.43 | 13-MAR-04:01 | -0.1 |
April | 0.134038E+09 | 12101.18 | 03-APR-05:11 | 2.60 |
May | 1332956.42 | 5341.75 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 7311864.10 | 8867.44 | 28-OCT-06:03 | 3.90 |
November | 0.590597E+09 | 13032.37 | 24-NOV-05:01 | -4.0 |
December | 0.150096E+10 | 13472.44 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.741903E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.270717E+10 | 14440.04 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242434E+10 | 12603.87 | 02-JAN-00:02 | -10.7 |
February | 0.188194E+10 | 12273.70 | 05-FEB-22:42 | -12.0 |
March | 0.462618E+09 | 11371.26 | 13-MAR-04:01 | -0.1 |
April | 96991624.56 | 10512.46 | 03-APR-05:11 | 2.60 |
May | 765317.18 | 3121.41 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 9951729.40 | 5858.81 | 28-OCT-06:03 | 3.90 |
November | 0.628556E+09 | 11399.77 | 20-NOV-05:01 | 0.50 |
December | 0.142088E+10 | 11832.45 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.692605E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.242434E+10 | 12603.87 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259236E+10 | 8207.12 | 02-JAN-00:02 | -10.7 |
February | 0.204500E+10 | 7645.55 | 13-FEB-05:01 | -9.0 |
March | 0.444924E+09 | 6930.08 | 13-MAR-05:01 | -0.6 |
April | 52012770.77 | 6667.51 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.216659E+09 | 6845.50 | 24-NOV-06:01 | -4.4 |
December | 0.739528E+09 | 6810.56 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.609049E+10 | |||
Minimum of Months | 0.00 | 0.00 | -10.7 | |
Maximum of Months | 0.259236E+10 | 8207.12 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131926E+10 | 9272.34 | 02-JAN-00:02 | -10.7 |
February | 0.823298E+09 | 8665.44 | 06-FEB-05:01 | -13.2 |
March | 0.134153E+09 | 7750.37 | 20-MAR-05:01 | -1.5 |
April | 14607135.31 | 7499.86 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 79461007.44 | 7646.49 | 24-NOV-06:01 | -4.4 |
December | 0.337918E+09 | 7754.43 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.270869E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.131926E+10 | 9272.34 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434420E+10 | 12876.39 | 02-JAN-08:00 | -11.1 |
February | 0.351793E+10 | 12382.15 | 06-FEB-08:00 | -12.8 |
March | 0.225396E+10 | 10801.13 | 23-MAR-06:10 | -4.7 |
April | 0.107565E+10 | 10061.49 | 03-APR-06:10 | 2.38 |
May | 0.304324E+09 | 8846.83 | 01-MAY-06:03 | 7.67 |
June | 238431.82 | 1133.68 | 02-JUN-06:08 | 13.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 3813860.70 | 4754.75 | 20-SEP-06:07 | 12.48 |
October | 0.196376E+09 | 8638.70 | 31-OCT-06:08 | 5.68 |
November | 0.145269E+10 | 10754.20 | 24-NOV-07:10 | -4.3 |
December | 0.267819E+10 | 10763.53 | 15-DEC-07:10 | -3.6 |
Annual Sum or Average | 0.158274E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.434420E+10 | 12876.39 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146133E+10 | 9485.74 | 02-JAN-00:02 | -10.7 |
February | 0.999152E+09 | 8815.81 | 06-FEB-05:01 | -13.2 |
March | 0.137385E+09 | 7829.22 | 13-MAR-05:01 | -0.6 |
April | 20130741.34 | 7486.85 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.107828E+09 | 7756.95 | 24-NOV-06:01 | -4.4 |
December | 0.383717E+09 | 7831.98 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.310954E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.146133E+10 | 9485.74 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242058E+10 | 9205.85 | 02-JAN-00:02 | -10.7 |
February | 0.171551E+10 | 8800.88 | 06-FEB-05:11 | -13.1 |
March | 0.277211E+09 | 7648.53 | 13-MAR-05:01 | -0.6 |
April | 28369580.42 | 7361.30 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 52564.84 | 350.43 | 28-OCT-06:03 | 3.90 |
November | 0.374939E+09 | 8082.37 | 24-NOV-05:01 | -4.0 |
December | 0.981222E+09 | 7906.21 | 31-DEC-22:22 | -7.5 |
Annual Sum or Average | 0.579788E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.242058E+10 | 9205.85 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131171E+10 | 10350.49 | 02-JAN-00:02 | -10.7 |
February | 0.808561E+09 | 9893.53 | 06-FEB-05:11 | -13.1 |
March | 0.123094E+09 | 8469.86 | 13-MAR-05:01 | -0.6 |
April | 10863506.62 | 8115.70 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.185249E+09 | 8989.90 | 24-NOV-05:01 | -4.0 |
December | 0.522453E+09 | 8754.62 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.296193E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.131171E+10 | 10350.49 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152325E+10 | 12813.53 | 02-JAN-00:02 | -10.7 |
February | 0.887869E+09 | 12312.44 | 06-FEB-05:11 | -13.1 |
March | 0.159554E+09 | 10716.92 | 13-MAR-05:01 | -0.6 |
April | 23216715.33 | 10183.85 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.182293E+09 | 10731.47 | 27-NOV-06:11 | 6.87 |
December | 0.573441E+09 | 10910.74 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.334963E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.152325E+10 | 12813.53 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145333E+10 | 10456.37 | 02-JAN-00:02 | -10.7 |
February | 0.971628E+09 | 9982.82 | 06-FEB-05:11 | -13.1 |
March | 0.143166E+09 | 8508.85 | 13-MAR-05:01 | -0.6 |
April | 17020046.35 | 8039.37 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.226525E+09 | 9008.52 | 24-NOV-05:01 | -4.0 |
December | 0.585226E+09 | 8734.88 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.339690E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.145333E+10 | 10456.37 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.464352E+09 | 735.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.390009E+09 | 667.35 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.434368E+09 | 531.16 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370981E+09 | 391.89 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.390957E+09 | 391.44 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.382864E+09 | 382.31 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.361354E+09 | 379.54 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407519E+09 | 398.27 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.378498E+09 | 470.79 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.409914E+09 | 583.53 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.444718E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.458810E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.489434E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.361354E+09 | 379.54 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.464352E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.290231E+09 | 465.60 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.245055E+09 | 427.17 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274259E+09 | 375.66 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.235270E+09 | 241.46 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.249049E+09 | 248.28 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244130E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.230237E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.258920E+09 | 241.47 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.239371E+09 | 253.88 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.258485E+09 | 372.55 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280012E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.284453E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308947E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.230237E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.290231E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447252E+09 | 735.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.379988E+09 | 663.06 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.429973E+09 | 476.86 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.371468E+09 | 389.60 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.392644E+09 | 392.34 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.385220E+09 | 385.63 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.363481E+09 | 383.18 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.408905E+09 | 398.25 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.377330E+09 | 411.26 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.404314E+09 | 561.61 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.433844E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.437148E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.483157E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.363481E+09 | 383.18 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.447252E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.286419E+09 | 465.57 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242142E+09 | 416.47 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271983E+09 | 331.89 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234881E+09 | 256.12 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246914E+09 | 253.05 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242401E+09 | 249.10 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229021E+09 | 248.83 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257744E+09 | 256.76 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238934E+09 | 316.62 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256869E+09 | 358.77 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.276033E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281313E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306465E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.229021E+09 | 248.83 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.286419E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462462E+09 | 735.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.388722E+09 | 664.74 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.433450E+09 | 522.83 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370592E+09 | 388.99 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.390687E+09 | 388.50 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.382566E+09 | 378.93 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.361012E+09 | 376.02 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407305E+09 | 395.66 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.377844E+09 | 412.18 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.409039E+09 | 577.70 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.443517E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.456469E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.488366E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.361012E+09 | 376.02 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.462462E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.289349E+09 | 465.60 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.244489E+09 | 425.97 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.273859E+09 | 372.93 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.235011E+09 | 239.55 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.248860E+09 | 246.63 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.243939E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.230008E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.258746E+09 | 239.34 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.239058E+09 | 252.50 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.258056E+09 | 369.68 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279461E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.283561E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308440E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.230008E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.289349E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.446352E+09 | 735.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.379584E+09 | 660.24 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.429547E+09 | 412.91 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.371083E+09 | 386.57 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.392360E+09 | 389.45 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.384835E+09 | 382.44 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.363111E+09 | 379.87 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.408652E+09 | 395.64 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.376784E+09 | 409.24 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.403967E+09 | 554.67 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.433292E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.436165E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.482573E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.363111E+09 | 379.87 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.446352E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285413E+09 | 465.57 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241639E+09 | 414.87 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271654E+09 | 327.80 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234608E+09 | 254.98 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246759E+09 | 251.61 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242233E+09 | 247.50 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.228830E+09 | 247.23 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257559E+09 | 255.48 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238639E+09 | 312.08 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256627E+09 | 355.50 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.275466E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.280233E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.305966E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.228830E+09 | 247.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.285413E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.464349E+09 | 735.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.390008E+09 | 667.34 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.434367E+09 | 531.15 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370980E+09 | 391.88 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.390957E+09 | 391.43 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.382864E+09 | 382.31 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.361354E+09 | 379.53 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407519E+09 | 398.26 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.378497E+09 | 470.77 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.409913E+09 | 583.52 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.444717E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.458807E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.489433E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.361354E+09 | 379.53 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.464349E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.290229E+09 | 465.60 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.245054E+09 | 427.16 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274259E+09 | 375.65 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.235269E+09 | 241.45 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.249049E+09 | 248.28 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244129E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.230236E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.258942E+09 | 241.46 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.239371E+09 | 253.88 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.258485E+09 | 372.54 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280012E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.284444E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308948E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.230236E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.290229E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447251E+09 | 735.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.379987E+09 | 663.06 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.429960E+09 | 476.84 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.371468E+09 | 389.60 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.392644E+09 | 392.33 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.385220E+09 | 385.62 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.363481E+09 | 383.17 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.408905E+09 | 398.25 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.377330E+09 | 411.25 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.404314E+09 | 561.59 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.433843E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.437147E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.483155E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.363481E+09 | 383.17 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.447251E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.286418E+09 | 465.57 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242141E+09 | 416.47 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271983E+09 | 331.88 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234881E+09 | 256.12 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246914E+09 | 253.05 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242400E+09 | 249.10 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229021E+09 | 248.83 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257744E+09 | 256.76 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238934E+09 | 316.60 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256869E+09 | 358.76 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.276033E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281312E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306465E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.229021E+09 | 248.83 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.286418E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.464352E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159843E+10 |
February | 0.901968E+09 | 0.390009E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142784E+10 |
March | 0.107774E+10 | 0.434368E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114805E+10 |
April | 0.956342E+09 | 0.370981E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 627453.28 | 0.771657E+09 |
May | 0.103597E+10 | 0.390957E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2749818.19 | 0.476822E+09 |
June | 0.103308E+10 | 0.382864E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20243448.50 | 0.250486E+09 |
July | 0.959235E+09 | 0.361354E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47935816.53 | 90932641.47 |
August | 0.107774E+10 | 0.407519E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58697862.40 | 0.112431E+09 |
September | 0.956342E+09 | 0.378498E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7221830.80 | 0.258346E+09 |
October | 0.994195E+09 | 0.409914E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108566.55 | 0.625413E+09 |
November | 0.984487E+09 | 0.444718E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110752E+10 |
December | 0.959235E+09 | 0.458810E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133258E+10 |
Annual Sum or Average | 0.119305E+11 | 0.489434E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137585E+09 | 0.920050E+10 |
Minimum of Months | 0.901968E+09 | 0.361354E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90932641.47 |
Maximum of Months | 0.107774E+10 | 0.464352E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58697862.40 | 0.159843E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.290231E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106686E+10 |
February | 0.571020E+09 | 0.245055E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960301E+09 |
March | 0.682301E+09 | 0.274259E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780075E+09 |
April | 0.605444E+09 | 0.235270E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 417436.55 | 0.535210E+09 |
May | 0.655854E+09 | 0.249049E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1553022.95 | 0.327518E+09 |
June | 0.654023E+09 | 0.244130E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13154263.22 | 0.170904E+09 |
July | 0.607275E+09 | 0.230237E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30921330.39 | 63072816.39 |
August | 0.682301E+09 | 0.258920E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38018075.77 | 78709469.56 |
September | 0.605444E+09 | 0.239371E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4788844.66 | 0.181826E+09 |
October | 0.629407E+09 | 0.258485E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72368.76 | 0.433863E+09 |
November | 0.623262E+09 | 0.280012E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750967E+09 |
December | 0.607275E+09 | 0.284453E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892874E+09 |
Annual Sum or Average | 0.755301E+10 | 0.308947E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88925342.30 | 0.624218E+10 |
Minimum of Months | 0.571020E+09 | 0.230237E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63072816.39 |
Maximum of Months | 0.682301E+09 | 0.290231E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38018075.77 | 0.106686E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.447252E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163871E+10 |
February | 0.901968E+09 | 0.379988E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149261E+10 |
March | 0.107774E+10 | 0.429973E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120448E+10 |
April | 0.956342E+09 | 0.371468E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 625976.82 | 0.808003E+09 |
May | 0.103597E+10 | 0.392644E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2334326.45 | 0.485122E+09 |
June | 0.103308E+10 | 0.385220E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19809290.28 | 0.252354E+09 |
July | 0.959235E+09 | 0.363481E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46779734.67 | 93528274.16 |
August | 0.107774E+10 | 0.408905E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56726519.68 | 0.118570E+09 |
September | 0.956342E+09 | 0.377330E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7164644.84 | 0.278981E+09 |
October | 0.994195E+09 | 0.404314E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106814.38 | 0.689399E+09 |
November | 0.984487E+09 | 0.433844E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116947E+10 |
December | 0.959235E+09 | 0.437148E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139927E+10 |
Annual Sum or Average | 0.119305E+11 | 0.483157E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133547E+09 | 0.963050E+10 |
Minimum of Months | 0.901968E+09 | 0.363481E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93528274.16 |
Maximum of Months | 0.107774E+10 | 0.447252E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56726519.68 | 0.163871E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.286419E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107145E+10 |
February | 0.570983E+09 | 0.242142E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964083E+09 |
March | 0.682256E+09 | 0.271983E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790525E+09 |
April | 0.605404E+09 | 0.234881E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 417481.09 | 0.535550E+09 |
May | 0.655811E+09 | 0.246914E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1788290.50 | 0.330060E+09 |
June | 0.653980E+09 | 0.242401E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13122446.55 | 0.176584E+09 |
July | 0.607235E+09 | 0.229021E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30818202.37 | 68533022.17 |
August | 0.682256E+09 | 0.257744E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37664667.52 | 81958103.19 |
September | 0.605404E+09 | 0.238934E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4783688.88 | 0.181911E+09 |
October | 0.629366E+09 | 0.256869E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72416.66 | 0.438125E+09 |
November | 0.623221E+09 | 0.276033E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744123E+09 |
December | 0.607235E+09 | 0.281313E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897063E+09 |
Annual Sum or Average | 0.755252E+10 | 0.306465E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88667193.57 | 0.627997E+10 |
Minimum of Months | 0.570983E+09 | 0.229021E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68533022.17 |
Maximum of Months | 0.682256E+09 | 0.286419E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37664667.52 | 0.107145E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.462462E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894597E+09 |
February | 0.901968E+09 | 0.388722E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792507E+09 |
March | 0.107774E+10 | 0.433450E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631527E+09 |
April | 0.956342E+09 | 0.370592E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 429218.01 | 0.416949E+09 |
May | 0.103597E+10 | 0.390687E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2500076.57 | 0.245359E+09 |
June | 0.103308E+10 | 0.382566E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12654703.01 | 0.126718E+09 |
July | 0.959235E+09 | 0.361012E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29493784.29 | 42241983.21 |
August | 0.107774E+10 | 0.407305E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33581084.52 | 58404783.13 |
September | 0.956342E+09 | 0.377844E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4076110.48 | 0.144657E+09 |
October | 0.994195E+09 | 0.409039E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65140.73 | 0.368274E+09 |
November | 0.984487E+09 | 0.443517E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664739E+09 |
December | 0.959235E+09 | 0.456469E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775488E+09 |
Annual Sum or Average | 0.119305E+11 | 0.488366E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82800117.62 | 0.516146E+10 |
Minimum of Months | 0.901968E+09 | 0.361012E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42241983.21 |
Maximum of Months | 0.107774E+10 | 0.462462E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33581084.52 | 0.894597E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.289349E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598846E+09 |
February | 0.571020E+09 | 0.244489E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538612E+09 |
March | 0.682301E+09 | 0.273859E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435638E+09 |
April | 0.605444E+09 | 0.235011E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229386.39 | 0.295274E+09 |
May | 0.655854E+09 | 0.248860E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 886482.23 | 0.174547E+09 |
June | 0.654023E+09 | 0.243939E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7454571.62 | 90120966.69 |
July | 0.607275E+09 | 0.230008E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17196861.14 | 32128730.79 |
August | 0.682301E+09 | 0.258746E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20638561.02 | 43874051.57 |
September | 0.605444E+09 | 0.239058E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2593722.74 | 0.104820E+09 |
October | 0.629407E+09 | 0.258056E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43422.43 | 0.258720E+09 |
November | 0.623262E+09 | 0.279461E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456698E+09 |
December | 0.607275E+09 | 0.283561E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524560E+09 |
Annual Sum or Average | 0.755301E+10 | 0.308440E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49043007.57 | 0.355384E+10 |
Minimum of Months | 0.571020E+09 | 0.230008E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32128730.79 |
Maximum of Months | 0.682301E+09 | 0.289349E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20638561.02 | 0.598846E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.446352E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577812E+10 |
February | 0.901968E+09 | 0.379584E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570267E+10 |
March | 0.107774E+10 | 0.429547E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509746E+10 |
April | 0.956342E+09 | 0.371083E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11068822.77 | 0.303512E+10 |
May | 0.103597E+10 | 0.392360E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45372781.07 | 0.180235E+10 |
June | 0.103308E+10 | 0.384835E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321137E+09 | 0.631647E+09 |
July | 0.959235E+09 | 0.363111E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680615E+09 | 0.102356E+09 |
August | 0.107774E+10 | 0.408652E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826099E+09 | 0.223790E+09 |
September | 0.956342E+09 | 0.376784E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134472E+09 | 0.887578E+09 |
October | 0.994195E+09 | 0.403967E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1707138.56 | 0.237604E+10 |
November | 0.984487E+09 | 0.433292E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433363E+10 |
December | 0.959235E+09 | 0.436165E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520640E+10 |
Annual Sum or Average | 0.119305E+11 | 0.482573E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202047E+10 | 0.351772E+11 |
Minimum of Months | 0.901968E+09 | 0.363111E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102356E+09 |
Maximum of Months | 0.107774E+10 | 0.446352E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826099E+09 | 0.577812E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.285413E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601037E+09 |
February | 0.570983E+09 | 0.241639E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538393E+09 |
March | 0.682256E+09 | 0.271654E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442331E+09 |
April | 0.605404E+09 | 0.234608E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232092.41 | 0.296423E+09 |
May | 0.655811E+09 | 0.246759E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1190793.17 | 0.176845E+09 |
June | 0.653980E+09 | 0.242233E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7264566.95 | 95294835.07 |
July | 0.607235E+09 | 0.228830E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17246780.98 | 36282191.70 |
August | 0.682256E+09 | 0.257559E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20554681.65 | 46245926.30 |
September | 0.605404E+09 | 0.238639E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2591811.99 | 0.105073E+09 |
October | 0.629366E+09 | 0.256627E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43449.06 | 0.262753E+09 |
November | 0.623221E+09 | 0.275466E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450177E+09 |
December | 0.607235E+09 | 0.280233E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524889E+09 |
Annual Sum or Average | 0.755252E+10 | 0.305966E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49124176.22 | 0.357575E+10 |
Minimum of Months | 0.570983E+09 | 0.228830E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36282191.70 |
Maximum of Months | 0.682256E+09 | 0.285413E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20554681.65 | 0.601037E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.464349E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137925E+10 |
February | 0.901968E+09 | 0.390008E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123289E+10 |
March | 0.107774E+10 | 0.434367E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100798E+10 |
April | 0.956342E+09 | 0.370980E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529787.38 | 0.680017E+09 |
May | 0.103597E+10 | 0.390957E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2566422.14 | 0.411504E+09 |
June | 0.103308E+10 | 0.382864E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17666321.03 | 0.213512E+09 |
July | 0.959235E+09 | 0.361354E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41320209.29 | 76107356.79 |
August | 0.107774E+10 | 0.407519E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49730307.82 | 96309886.26 |
September | 0.956342E+09 | 0.378497E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6117024.14 | 0.225787E+09 |
October | 0.994195E+09 | 0.409913E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95979.98 | 0.559023E+09 |
November | 0.984487E+09 | 0.444717E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997536E+09 |
December | 0.959235E+09 | 0.458807E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117735E+10 |
Annual Sum or Average | 0.119305E+11 | 0.489433E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118026E+09 | 0.805728E+10 |
Minimum of Months | 0.901968E+09 | 0.361354E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76107356.79 |
Maximum of Months | 0.107774E+10 | 0.464349E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49730307.82 | 0.137925E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.290229E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920421E+09 |
February | 0.421807E+09 | 0.245054E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833665E+09 |
March | 0.502994E+09 | 0.274259E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686920E+09 |
April | 0.447140E+09 | 0.235269E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 317788.47 | 0.471117E+09 |
May | 0.484071E+09 | 0.249049E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1258450.88 | 0.283358E+09 |
June | 0.482240E+09 | 0.244129E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10754469.56 | 0.146606E+09 |
July | 0.448971E+09 | 0.230236E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25426711.09 | 53390830.76 |
August | 0.502994E+09 | 0.258942E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31117533.66 | 67594147.07 |
September | 0.447140E+09 | 0.239371E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3802058.96 | 0.159080E+09 |
October | 0.465148E+09 | 0.258485E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36258.26 | 0.386194E+09 |
November | 0.460569E+09 | 0.280012E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677256E+09 |
December | 0.448971E+09 | 0.284444E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791704E+09 |
Annual Sum or Average | 0.557719E+10 | 0.308948E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72713270.89 | 0.547731E+10 |
Minimum of Months | 0.421807E+09 | 0.230236E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53390830.76 |
Maximum of Months | 0.502994E+09 | 0.290229E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31117533.66 | 0.920421E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.447251E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142085E+10 |
February | 0.901968E+09 | 0.379987E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129986E+10 |
March | 0.107774E+10 | 0.429960E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105656E+10 |
April | 0.956342E+09 | 0.371468E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 529485.92 | 0.709964E+09 |
May | 0.103597E+10 | 0.392644E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1982302.68 | 0.418949E+09 |
June | 0.103308E+10 | 0.385220E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16821517.82 | 0.215773E+09 |
July | 0.959235E+09 | 0.363481E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39652292.55 | 78985135.89 |
August | 0.107774E+10 | 0.408905E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47773390.07 | 0.101671E+09 |
September | 0.956342E+09 | 0.377330E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5995641.00 | 0.243186E+09 |
October | 0.994195E+09 | 0.404314E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71643.58 | 0.607408E+09 |
November | 0.984487E+09 | 0.433843E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105108E+10 |
December | 0.959235E+09 | 0.437147E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124076E+10 |
Annual Sum or Average | 0.119305E+11 | 0.483155E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112826E+09 | 0.844505E+10 |
Minimum of Months | 0.901968E+09 | 0.363481E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78985135.89 |
Maximum of Months | 0.107774E+10 | 0.447251E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47773390.07 | 0.142085E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.286418E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924935E+09 |
February | 0.570983E+09 | 0.242141E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833268E+09 |
March | 0.682256E+09 | 0.271983E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693431E+09 |
April | 0.605404E+09 | 0.234881E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 353203.14 | 0.471127E+09 |
May | 0.655811E+09 | 0.246914E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1592625.69 | 0.285180E+09 |
June | 0.653980E+09 | 0.242400E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11122641.96 | 0.151277E+09 |
July | 0.607235E+09 | 0.229021E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26050985.54 | 58206318.06 |
August | 0.682256E+09 | 0.257744E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31741411.90 | 70325347.16 |
September | 0.605404E+09 | 0.238934E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4024207.79 | 0.158839E+09 |
October | 0.629366E+09 | 0.256869E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64031.56 | 0.389268E+09 |
November | 0.623221E+09 | 0.276033E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669875E+09 |
December | 0.607235E+09 | 0.281312E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793240E+09 |
Annual Sum or Average | 0.755252E+10 | 0.306465E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74949107.59 | 0.549897E+10 |
Minimum of Months | 0.570983E+09 | 0.229021E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58206318.06 |
Maximum of Months | 0.682256E+09 | 0.286418E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31741411.90 | 0.924935E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189525E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172355E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141428E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521196.21 | 0.949535E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3066401.96 | 0.558146E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18865467.59 | 0.284639E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46569274.12 | 92486244.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54515459.53 | 0.126841E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5259125.30 | 0.317462E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9289.83 | 0.804783E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143748E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168270E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128806E+09 | 0.112872E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92486244.42 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54515459.53 | 0.189525E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234717E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213390E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175815E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658483.97 | 0.118528E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3560325.31 | 0.714731E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23332787.16 | 0.368885E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57382572.09 | 0.123079E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69440762.22 | 0.163831E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6805817.79 | 0.398899E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17867.53 | 0.993925E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173734E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204464E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161199E+09 | 0.139698E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123079E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69440762.22 | 0.234717E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238432E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216860E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179197E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159924.73 | 0.122237E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327020.64 | 0.764477E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19099537.85 | 0.399266E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47530515.97 | 0.141135E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63978663.69 | 0.166034E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5910769.22 | 0.413689E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100226E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170677E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202605E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138006E+09 | 0.141869E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141135E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63978663.69 | 0.238432E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2699.20 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 667.35 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.65 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 531.16 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2218.84 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 391.89 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 07-APR-13:00 | 1670.16 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 391.44 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.29 | 29-MAY-11:53 | 978.60 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 382.31 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.18 | 19-JUN-21:03 | 605.65 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 379.54 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.60 | 09-JUL-13:52 | 287.33 | 02-JUL-18:30 |
August | 1306.65 | 01-AUG-09:09 | 398.27 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.21 | 04-AUG-21:03 | 389.24 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 470.79 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 | 14-SEP-14:00 | 510.06 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 583.53 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 25-OCT-11:00 | 1394.73 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2172.46 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2919.04 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 379.54 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.33 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 349.21 | 2938.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1799.46 | 01-JAN-21:00 |
February | 827.22 | 01-FEB-10:09 | 427.17 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1959.09 | 06-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 375.66 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1480.53 | 21-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 241.46 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1110.20 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 248.28 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.43 | 29-MAY-11:35 | 654.11 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.22 | 19-JUN-21:03 | 404.16 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.18 | 09-JUL-13:52 | 205.56 | 02-JUL-18:30 |
August | 827.22 | 01-AUG-09:09 | 241.47 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.04 | 04-AUG-21:03 | 272.73 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 253.88 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 386.38 | 10-SEP-08:00 |
October | 827.22 | 02-OCT-09:09 | 372.55 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 1026.98 | 08-OCT-08:20 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1448.19 | 22-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1946.02 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.56 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 232.04 | 1959.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2703.28 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 663.06 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.66 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 476.86 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2228.52 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 389.60 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 07-APR-13:00 | 1693.63 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 392.34 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.91 | 29-MAY-11:53 | 991.54 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 385.63 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.97 | 19-JUN-21:03 | 606.43 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 383.18 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.28 | 09-JUL-13:52 | 296.14 | 02-JUL-18:30 |
August | 1306.65 | 01-AUG-09:09 | 398.25 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.13 | 04-AUG-21:03 | 391.79 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 411.26 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.94 | 14-SEP-14:00 | 540.20 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 561.61 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 25-OCT-11:00 | 1464.85 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2178.89 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2921.08 | 31-DEC-21:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 383.18 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.14 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 348.13 | 2938.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1799.46 | 01-JAN-21:00 |
February | 827.17 | 01-FEB-10:09 | 416.47 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1959.09 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 331.89 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1484.60 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 256.12 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1127.72 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 253.05 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.93 | 29-MAY-11:53 | 667.20 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 249.10 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.00 | 19-JUN-21:03 | 459.91 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 248.83 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.19 | 09-JUL-13:52 | 269.01 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 256.76 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.00 | 04-AUG-21:03 | 265.00 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 316.62 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 364.53 | 10-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 358.77 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 950.19 | 17-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1448.14 | 22-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1946.02 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 248.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.00 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 231.00 | 1959.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1536.82 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 664.74 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1559.66 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 522.83 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1183.17 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 388.99 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 | 07-APR-17:00 | 951.09 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 388.50 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 | 29-MAY-12:00 | 534.30 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 378.93 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.73 | 19-JUN-21:03 | 326.04 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 376.02 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.76 | 09-JUL-13:52 | 152.71 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 395.66 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.81 | 04-AUG-21:03 | 221.16 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 412.18 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.56 | 14-SEP-14:00 | 298.62 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 577.70 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 25-OCT-11:00 | 866.98 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1294.24 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1582.19 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 376.02 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.71 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.81 | 1582.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1034.88 | 31-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 425.97 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1062.65 | 05-FEB-08:40 |
March | 827.22 | 01-MAR-10:09 | 372.93 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 816.17 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 239.55 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 07-APR-13:00 | 651.22 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 246.63 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.55 | 29-MAY-11:48 | 377.42 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.07 | 19-JUN-21:03 | 227.26 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.61 | 09-JUL-13:52 | 108.47 | 11-JUL-05:00 |
August | 827.22 | 01-AUG-09:09 | 239.34 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.89 | 04-AUG-21:03 | 160.12 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 252.50 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 203.27 | 30-SEP-24:00 |
October | 827.22 | 02-OCT-09:09 | 369.68 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 640.03 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 878.64 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1063.55 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 123.89 | 1063.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 27357.32 | 02-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 660.24 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 29818.35 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 412.91 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 22061.35 | 23-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 386.57 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1704.55 | 07-APR-17:00 | 15328.34 | 03-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 389.45 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4075.53 | 30-MAY-12:00 | 10972.62 | 01-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 382.44 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9193.12 | 19-JUN-11:02 | 7079.09 | 02-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 379.87 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7124.23 | 07-JUL-11:03 | 2600.24 | 11-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 395.64 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7375.78 | 24-AUG-16:05 | 4725.54 | 08-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 409.24 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4428.90 | 14-SEP-16:10 | 9728.55 | 11-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 554.67 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 661.51 | 25-OCT-11:10 | 13621.06 | 31-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21695.71 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 22239.79 | 22-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 379.87 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2600.24 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9193.12 | 29818.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1036.43 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 414.87 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1039.77 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 327.80 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 793.90 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 254.98 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 07-APR-13:00 | 672.97 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 251.61 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 | 29-MAY-12:00 | 380.72 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 247.50 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.08 | 19-JUN-21:03 | 238.39 | 02-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 247.23 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.38 | 09-JUL-13:52 | 125.39 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 255.48 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.40 | 04-AUG-21:03 | 159.60 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 312.08 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 212.30 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 355.50 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 594.35 | 08-OCT-08:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 869.15 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1067.45 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 247.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.39 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 123.40 | 1067.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2331.36 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 667.34 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2443.98 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 531.15 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1855.03 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 391.88 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 07-APR-13:00 | 1495.62 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 391.43 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.43 | 29-MAY-12:00 | 876.65 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 382.31 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.15 | 19-JUN-21:03 | 521.73 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 379.53 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.26 | 09-JUL-13:52 | 246.38 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 398.26 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.29 | 04-AUG-21:03 | 347.27 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 470.77 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 | 14-SEP-14:00 | 451.68 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 583.52 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 25-OCT-11:00 | 1267.75 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1918.67 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.13 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 379.53 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.38 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 292.29 | 2443.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1554.04 | 31-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 427.16 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.31 | 06-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 375.65 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1303.82 | 12-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 241.45 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 07-APR-13:00 | 994.90 | 11-APR-04:00 |
May | 805.43 | 01-MAY-07:10 | 248.28 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 29-MAY-11:57 | 586.10 | 03-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.55 | 19-JUN-21:03 | 348.91 | 02-JUN-22:00 |
July | 805.43 | 03-JUL-07:10 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.16 | 09-JUL-13:50 | 167.66 | 11-JUL-05:00 |
August | 805.43 | 01-AUG-07:10 | 241.46 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.16 | 04-AUG-21:03 | 243.08 | 20-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 253.88 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.11 | 14-SEP-14:10 | 311.63 | 10-SEP-07:50 |
October | 805.43 | 02-OCT-07:10 | 372.54 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 25-OCT-11:00 | 952.76 | 08-OCT-08:00 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1279.78 | 23-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.07 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 194.16 | 1629.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2410.57 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 663.06 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.00 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 476.84 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1960.88 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 389.60 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 | 07-APR-13:00 | 1515.12 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 392.33 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 | 29-MAY-11:57 | 887.52 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 385.62 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.96 | 19-JUN-21:03 | 522.51 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 383.17 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.25 | 09-JUL-13:50 | 242.62 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 398.25 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.38 | 04-AUG-21:03 | 349.48 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 411.25 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.85 | 14-SEP-14:00 | 477.22 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 561.59 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 25-OCT-11:00 | 1366.24 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1968.43 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.14 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 383.17 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.62 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 291.38 | 2444.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1556.49 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 416.47 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.31 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 331.88 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1241.87 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 256.12 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 07-APR-13:00 | 1008.83 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 253.05 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 | 29-MAY-12:00 | 596.91 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 249.10 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.82 | 19-JUN-21:03 | 381.10 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 248.83 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.18 | 09-JUL-13:50 | 207.84 | 02-JUL-17:40 |
August | 827.17 | 01-AUG-09:09 | 256.76 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.39 | 04-AUG-21:03 | 236.32 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 316.60 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 14-SEP-14:00 | 314.37 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 358.76 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 25-OCT-11:00 | 850.00 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1277.86 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.07 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 248.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.84 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 193.39 | 1629.31 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3393.77 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3372.96 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2504.01 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | 07-APR-13:00 | 2149.26 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.08 | 29-MAY-12:00 | 1243.38 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.90 | 19-JUN-21:03 | 707.55 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.60 | 09-JUL-14:00 | 318.88 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.58 | 12-AUG-18:55 | 471.81 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.09 | 14-SEP-14:00 | 637.86 | 30-SEP-24:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 25-OCT-11:00 | 1853.06 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2837.45 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3472.31 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.58 | 3472.31 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4200.01 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4115.54 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3163.70 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 | 07-APR-13:00 | 2720.20 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.91 | 29-MAY-12:00 | 1571.11 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.82 | 19-JUN-21:03 | 909.70 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.59 | 09-JUL-13:52 | 412.29 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.16 | 12-AUG-18:55 | 600.79 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.63 | 14-SEP-14:00 | 796.29 | 30-SEP-24:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 | 25-OCT-11:00 | 2271.57 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3476.83 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4195.90 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.16 | 4200.01 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4035.57 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4133.71 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3329.85 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.16 | 08-APR-10:00 | 2548.56 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 | 30-MAY-13:00 | 1491.24 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.28 | 19-JUN-21:03 | 886.65 | 03-JUN-18:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.04 | 07-JUL-22:00 | 518.99 | 02-JUL-17:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.32 | 04-AUG-21:03 | 544.21 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.97 | 14-SEP-14:00 | 773.57 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2136.52 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3248.42 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4145.68 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.99 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.32 | 4145.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6908.37 | 27-JAN-16:30 | 12070.02 | 6977.40 | 21549.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7910.42 | 24-FEB-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12940.40 | 30-MAR-07:20 | 12070.02 | 6977.40 | 25516.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18061.19 | 10-APR-06:03 | 5082.11 | 4651.60 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33558.48 | 30-MAY-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33515.00 | 26-JUN-05:12 | 3176.32 | 1938.17 | 20240.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34650.44 | 24-JUL-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35293.44 | 07-AUG-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33697.15 | 01-SEP-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31558.43 | 16-OCT-06:01 | 10164.22 | 9303.20 | 48352.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15090.04 | 03-NOV-16:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9260.30 | 21-DEC-16:10 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6908.37 | 2541.06 | 846.94 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35293.44 | 12070.02 | 9303.20 | 48352.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 123.79 | 17-JAN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.18 |
February | 457.82 | 18-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.00 |
March | 2364.31 | 03-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.53 |
April | 6736.57 | 07-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 | 0.00 |
May | 10195.56 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | 0.00 |
June | 11276.41 | 19-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.89 | 0.00 |
July | 10568.64 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.51 | 0.00 |
August | 10064.52 | 01-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.04 | 0.00 |
September | 8796.31 | 01-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.84 | 0.00 |
October | 6184.66 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 |
November | 2045.81 | 03-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.33 |
December | 150.13 | 16-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 123.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11276.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.51 | 318.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2239.29 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1957.41 |
February | 2134.76 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2340.83 |
March | 1683.72 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.67 |
April | 2049.80 | 10-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.83 |
May | 4792.73 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.08 | 0.00 |
June | 4783.74 | 19-JUN-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.60 | 0.00 |
July | 5110.86 | 10-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.99 | 0.00 |
August | 5367.00 | 14-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 | 0.00 |
September | 4947.66 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 0.00 |
October | 2834.61 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.39 |
November | 1360.06 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.79 |
December | 1552.86 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1360.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5367.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.60 | 2340.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1561.02 | 19-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.72 |
February | 1827.59 | 25-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.13 |
March | 2196.88 | 09-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.88 |
April | 2187.03 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.06 |
May | 4662.66 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.81 | 0.00 |
June | 5433.44 | 19-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.88 | 0.00 |
July | 5434.72 | 10-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.86 | 0.00 |
August | 5116.70 | 14-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
September | 5086.96 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.06 |
October | 3184.92 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 |
November | 1339.47 | 03-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.42 |
December | 1758.93 | 21-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1339.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5434.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.88 | 450.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5849.03 | 20-JAN-17:00 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5906.66 | 24-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8215.76 | 29-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12861.34 | 10-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28249.04 | 30-MAY-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31454.24 | 19-JUN-05:04 | 3176.32 | 1058.67 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28673.13 | 24-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31612.59 | 14-AUG-05:14 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31314.00 | 05-SEP-05:14 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14045.15 | 05-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10332.41 | 03-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6093.11 | 21-DEC-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5849.03 | 2541.06 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31612.59 | 12070.02 | 6977.40 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5620.39 | 20-JAN-16:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5714.38 | 24-FEB-16:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8221.05 | 29-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13915.50 | 10-APR-15:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30456.95 | 30-MAY-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33848.40 | 19-JUN-05:04 | 3176.32 | 1058.67 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30971.44 | 24-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31452.40 | 07-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31036.47 | 05-SEP-05:12 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14648.07 | 04-OCT-15:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9225.02 | 03-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5636.17 | 21-DEC-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5620.39 | 2541.06 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33848.40 | 6035.01 | 3488.70 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 948.67 | 20-JAN-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.76 |
February | 973.73 | 24-FEB-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.51 |
March | 1455.14 | 28-MAR-13:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.37 |
April | 3843.85 | 07-APR-14:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 0.00 |
May | 8608.40 | 30-MAY-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 |
June | 9346.21 | 26-JUN-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.53 |
July | 9828.76 | 04-JUL-13:32 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 55.36 | 0.00 |
August | 11038.43 | 13-AUG-15:52 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 | 0.00 |
September | 6934.58 | 05-SEP-06:03 | 1071.35 | 518.34 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 |
October | 4014.28 | 04-OCT-13:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 0.00 |
November | 1479.71 | 03-NOV-14:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.80 |
December | 978.91 | 20-DEC-14:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 948.67 | 267.84 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11038.43 | 1306.65 | 518.34 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 | 304.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 758.42 | 19-JAN-10:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.17 |
February | 787.45 | 22-FEB-10:05 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.91 |
March | 3391.34 | 29-MAR-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.12 |
April | 6084.36 | 28-APR-08:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 |
May | 12856.13 | 29-MAY-08:52 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.27 |
June | 12367.85 | 25-JUN-08:52 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 |
July | 12922.31 | 02-JUL-08:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.78 |
August | 12349.91 | 13-AUG-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 | 0.00 |
September | 12787.74 | 04-SEP-08:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.68 |
October | 5375.05 | 05-OCT-09:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.54 |
November | 1994.57 | 03-NOV-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 |
December | 792.95 | 20-DEC-09:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 758.42 | 211.95 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12922.31 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 | 229.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5461.11 | 19-JAN-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.57 |
February | 5899.62 | 02-FEB-13:50 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.89 |
March | 8351.12 | 03-MAR-13:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.67 |
April | 9641.49 | 07-APR-12:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 | 0.00 |
May | 15769.72 | 29-MAY-11:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 64.25 | 0.00 |
June | 12068.39 | 18-JUN-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 |
July | 15868.15 | 30-JUL-11:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.75 |
August | 15836.94 | 13-AUG-12:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 139.24 | 0.00 |
September | 16216.73 | 04-SEP-12:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 |
October | 16411.80 | 15-OCT-12:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.74 |
November | 10273.97 | 02-NOV-13:00 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.64 |
December | 5693.56 | 21-DEC-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5461.11 | 267.84 | 77.95 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16411.80 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 139.24 | 523.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1177.61 | 20-JAN-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.14 |
February | 1886.03 | 24-FEB-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.27 |
March | 5186.53 | 29-MAR-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.64 |
April | 7850.19 | 09-APR-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.01 |
May | 11719.50 | 21-MAY-14:53 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.82 |
June | 13993.55 | 18-JUN-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.05 |
July | 14202.20 | 02-JUL-15:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.21 |
August | 13939.78 | 13-AUG-15:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 0.00 |
September | 13742.07 | 10-SEP-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.51 |
October | 10024.68 | 15-OCT-15:32 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.69 |
November | 3494.34 | 03-NOV-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
December | 866.28 | 08-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 866.28 | 169.55 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14202.20 | 805.38 | 222.08 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 332.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 922.77 | 20-JAN-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.77 |
February | 937.85 | 24-FEB-14:10 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.51 |
March | 1215.48 | 28-MAR-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.43 |
April | 2012.06 | 10-APR-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 |
May | 4248.51 | 30-MAY-13:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 | 0.00 |
June | 7131.93 | 26-JUN-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 |
July | 7181.15 | 17-JUL-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
August | 6978.15 | 14-AUG-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 |
September | 6462.25 | 05-SEP-06:03 | 1071.35 | 514.38 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
October | 3574.80 | 05-OCT-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
November | 1507.24 | 03-NOV-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 |
December | 1018.92 | 20-DEC-13:50 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 922.77 | 803.52 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7181.15 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 | 149.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 735.99 | 27-JAN-10:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.76 |
February | 739.83 | 22-FEB-10:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.43 |
March | 2067.44 | 29-MAR-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.21 |
April | 3985.55 | 28-APR-09:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 |
May | 10561.97 | 29-MAY-10:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
June | 10702.32 | 25-JUN-08:42 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 |
July | 9241.58 | 09-JUL-09:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 0.00 |
August | 8645.84 | 20-AUG-10:32 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
September | 10511.20 | 10-SEP-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.63 |
October | 4819.97 | 05-OCT-09:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 |
November | 2313.00 | 03-NOV-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.69 |
December | 825.77 | 20-DEC-09:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 735.99 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10702.32 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 124.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1325.23 | 19-JAN-14:20 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1772.47 |
February | 2013.14 | 25-FEB-13:10 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 |
March | 4211.53 | 03-MAR-13:20 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151.57 |
April | 6506.74 | 07-APR-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.68 | 0.00 |
May | 10330.00 | 30-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4075.53 | 0.00 |
June | 11890.92 | 19-JUN-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8376.35 | 0.00 |
July | 11327.53 | 07-JUL-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6726.65 | 0.00 |
August | 12817.65 | 20-AUG-12:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 |
September | 12906.20 | 10-SEP-14:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.22 |
October | 13041.31 | 15-OCT-12:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.09 |
November | 8183.05 | 02-NOV-12:10 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.31 |
December | 2972.27 | 02-DEC-13:50 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1325.23 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13041.31 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8376.35 | 1772.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 839.91 | 20-JAN-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 |
February | 1020.37 | 22-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.70 |
March | 3103.59 | 27-MAR-16:50 | 254.33 | 123.38 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
April | 5306.67 | 10-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 |
May | 6548.02 | 30-MAY-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
June | 10813.56 | 18-JUN-16:21 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.10 |
July | 10717.30 | 02-JUL-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 |
August | 11052.06 | 20-AUG-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 |
September | 11240.63 | 10-SEP-17:12 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.94 |
October | 8109.50 | 15-OCT-15:32 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.17 |
November | 3286.69 | 03-NOV-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
December | 849.76 | 21-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 839.91 | 0.00 | 49.34 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11240.63 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 174.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 994.88 | 20-JAN-15:10 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.17 |
February | 1016.44 | 24-FEB-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.08 |
March | 1382.89 | 27-MAR-16:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 |
April | 3380.86 | 10-APR-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.32 |
May | 7996.38 | 30-MAY-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
June | 8094.75 | 26-JUN-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.75 |
July | 8795.69 | 09-JUL-14:41 | 468.72 | 136.41 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 55.45 | 0.00 |
August | 7734.46 | 22-AUG-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 0.00 |
September | 7328.83 | 05-SEP-06:03 | 1071.35 | 518.33 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.62 |
October | 3849.21 | 05-OCT-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
November | 1778.76 | 03-NOV-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 |
December | 1049.31 | 20-DEC-14:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 994.88 | 468.72 | 136.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8795.69 | 1306.65 | 518.33 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 55.45 | 258.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 812.12 | 27-JAN-10:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.99 |
February | 864.30 | 22-FEB-09:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.38 |
March | 5411.41 | 29-MAR-12:02 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.97 |
April | 6472.24 | 28-APR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 |
May | 12800.15 | 28-MAY-08:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.46 |
June | 13382.02 | 25-JUN-08:42 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.30 |
July | 13862.45 | 02-JUL-08:21 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 |
August | 12547.27 | 27-AUG-09:52 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.14 |
September | 12910.34 | 10-SEP-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.47 |
October | 6294.22 | 04-OCT-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 |
November | 5178.86 | 01-NOV-12:02 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.12 |
December | 1000.18 | 20-DEC-09:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 812.12 | 211.95 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | |
Maximum of Months | 13862.45 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5675.19 | 19-JAN-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.57 |
February | 6284.27 | 02-FEB-13:40 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 |
March | 8405.92 | 29-MAR-13:00 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.92 |
April | 9057.66 | 07-APR-12:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 | 0.00 |
May | 14303.40 | 29-MAY-12:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 0.00 |
June | 9197.56 | 19-JUN-12:07 | 7633.40 | 2104.85 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 119.78 | 0.00 |
July | 14331.71 | 30-JUL-11:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 |
August | 14758.10 | 20-AUG-12:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 |
September | 14893.75 | 10-SEP-11:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.31 |
October | 14579.39 | 22-OCT-12:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.73 |
November | 10707.22 | 02-NOV-12:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.80 |
December | 6685.86 | 21-DEC-13:04 | 6361.16 | 1754.05 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5675.19 | 267.84 | 77.95 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14893.75 | 7633.40 | 2104.85 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 119.78 | 270.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1319.82 | 20-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.61 |
February | 2189.03 | 24-FEB-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.02 |
March | 5197.58 | 29-MAR-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.32 |
April | 7697.11 | 09-APR-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.31 |
May | 12678.14 | 28-MAY-15:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 |
June | 14119.69 | 18-JUN-16:31 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.73 |
July | 13823.32 | 04-JUL-16:41 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.94 |
August | 13312.43 | 20-AUG-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.59 |
September | 13903.02 | 10-SEP-15:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.45 |
October | 6989.37 | 04-OCT-15:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
November | 3676.55 | 03-NOV-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
December | 1135.73 | 08-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1135.73 | 169.55 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | |
Maximum of Months | 14119.69 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.31 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.124382E+12 | 230126.34 | 02-JAN-07:10 | 0.545438E+11 | 94796.75 | 02-JAN-09:09 |
February | 0.102869E+12 | 200871.81 | 06-FEB-07:10 | 0.533676E+11 | 95995.00 | 06-FEB-08:20 |
March | 0.903250E+11 | 125108.46 | 13-MAR-06:10 | 0.367618E+11 | 65636.76 | 23-MAR-06:10 |
April | 0.793846E+11 | 94741.65 | 03-APR-06:10 | 0.176154E+11 | 40981.20 | 03-APR-06:40 |
May | 0.909761E+11 | 134482.41 | 30-MAY-14:09 | 0.111877E+11 | 21438.06 | 01-MAY-06:10 |
June | 0.118543E+12 | 145872.20 | 19-JUN-12:09 | 0.104904E+11 | 9801.10 | 01-JUN-11:30 |
July | 0.135976E+12 | 138015.35 | 07-JUL-14:30 | 0.101657E+11 | 9686.88 | 03-JUL-11:09 |
August | 0.143412E+12 | 141164.51 | 16-AUG-15:09 | 0.105561E+11 | 9649.48 | 31-AUG-11:00 |
September | 0.104162E+12 | 121653.40 | 07-SEP-15:20 | 0.100318E+11 | 9719.06 | 29-SEP-11:00 |
October | 0.906240E+11 | 100983.96 | 04-OCT-15:30 | 0.118423E+11 | 32642.14 | 28-OCT-07:10 |
November | 0.864260E+11 | 138628.17 | 24-NOV-07:10 | 0.264031E+11 | 67218.60 | 24-NOV-07:19 |
December | 0.100293E+12 | 143602.19 | 11-DEC-07:10 | 0.447004E+11 | 67614.88 | 22-DEC-07:30 |
Annual Sum or Average | 0.126737E+13 | 0.297666E+12 | ||||
Minimum of Months | 0.793846E+11 | 94741.65 | 0.100318E+11 | 9649.48 | ||
Maximum of Months | 0.143412E+12 | 230126.34 | 0.545438E+11 | 95995.00 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.500277E+10 | 15147.85 | 31-JAN-11:50 | 0.00 | 0.00 |
February | 0.725621E+10 | 17924.98 | 22-FEB-11:30 | 0.00 | 0.00 |
March | 0.112953E+11 | 23381.33 | 29-MAR-11:00 | 0.00 | 0.00 |
April | 0.130305E+11 | 24882.48 | 12-APR-11:00 | 0.00 | 0.00 |
May | 0.163453E+11 | 25300.18 | 11-MAY-11:00 | 0.00 | 0.00 |
June | 0.168503E+11 | 26130.14 | 02-JUN-11:50 | 0.00 | 0.00 |
July | 0.166025E+11 | 24778.12 | 02-JUL-11:00 | 0.00 | 0.00 |
August | 0.170136E+11 | 23350.57 | 10-AUG-11:30 | 0.00 | 0.00 |
September | 0.117232E+11 | 21822.23 | 10-SEP-11:30 | 0.00 | 0.00 |
October | 0.105735E+11 | 18881.58 | 08-OCT-11:30 | 0.00 | 0.00 |
November | 0.595049E+10 | 14925.30 | 02-NOV-11:30 | 0.00 | 0.00 |
December | 0.443260E+10 | 12241.86 | 02-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.136076E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.443260E+10 | 12241.86 | 0.00 | 0.00 | |
Maximum of Months | 0.170136E+11 | 26130.14 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.144215E+11 | 0.391471E+10 | 0.545046E+11 | 0.976819E+09 | 0.357073E+10 | 12379742.02 | 0.469808E+11 | 95052.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128047E+11 | 0.313442E+10 | 0.493409E+11 | 0.883775E+09 | 0.308184E+10 | 11196021.66 | 0.336122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149660E+11 | 0.292145E+10 | 0.567112E+11 | 0.102246E+10 | 0.348566E+10 | 12675672.10 | 0.109113E+11 | 0.294322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132272E+11 | 0.233720E+10 | 0.526212E+11 | 0.940433E+09 | 0.413670E+10 | 11960507.72 | 0.324706E+10 | 0.286281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141867E+11 | 0.209590E+10 | 0.556079E+11 | 0.999272E+09 | 0.687328E+10 | 12527707.06 | 0.417854E+09 | 0.107828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140614E+11 | 0.189025E+10 | 0.546110E+11 | 0.983604E+09 | 0.114305E+11 | 12231776.97 | 1995274.97 | 0.355520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131921E+11 | 0.200552E+10 | 0.536070E+11 | 0.955912E+09 | 0.144641E+11 | 12256437.81 | 0.00 | 0.517395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147348E+11 | 0.225197E+10 | 0.567112E+11 | 0.102234E+10 | 0.160767E+11 | 12675672.10 | 0.00 | 0.526022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132913E+11 | 0.259477E+10 | 0.525990E+11 | 0.940233E+09 | 0.927243E+10 | 11960507.72 | 14308595.24 | 0.254377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139483E+11 | 0.324232E+10 | 0.545158E+11 | 0.976473E+09 | 0.663927E+10 | 12379742.02 | 0.373010E+09 | 0.109165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141451E+11 | 0.364237E+10 | 0.533244E+11 | 0.958545E+09 | 0.333114E+10 | 12059151.09 | 0.107328E+11 | 0.279591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140208E+11 | 0.403634E+10 | 0.535958E+11 | 0.956477E+09 | 0.309487E+10 | 12256437.81 | 0.245764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167000E+12 | 0.340672E+11 | 0.647750E+12 | 0.116163E+11 | 0.854573E+11 | 0.146559E+09 | 0.130868E+12 | 0.190467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128047E+11 | 0.189025E+10 | 0.493409E+11 | 0.883775E+09 | 0.308184E+10 | 11196021.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149660E+11 | 0.403634E+10 | 0.567112E+11 | 0.102246E+10 | 0.160767E+11 | 12675672.10 | 0.469808E+11 | 0.526022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.428383E+11 | 0.00 | 0.117055E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.427252E+11 | 0.00 | 0.106424E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.247441E+11 | 0.00 | 0.120177E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.668870E+10 | 0.00 | 0.109267E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 91808478.79 | 0.00 | 0.110958E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.104904E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.101657E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.105561E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1398079.12 | 0.00 | 0.100304E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.117900E+10 | 0.00 | 0.106633E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.156226E+11 | 0.00 | 0.107805E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.334164E+11 | 0.00 | 0.112840E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167307E+12 | 0.00 | 0.130358E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.100304E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.428383E+11 | 0.00 | 0.120177E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-16:40 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 828.65 | 02-JAN-16:49 | 6719.58 | 02-JAN-06:19 | 6.85 | 02-JAN-12:20 | 195795.69 | 02-JAN-06:19 |
February | 16969.69 | 15-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 827.46 | 15-FEB-16:00 | 5216.40 | 06-FEB-07:10 | 6.85 | 02-FEB-08:09 | 171763.46 | 06-FEB-07:10 |
March | 15082.41 | 02-MAR-16:00 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 826.37 | 16-MAR-07:19 | 4516.09 | 29-MAR-15:20 | 6.85 | 01-MAR-06:19 | 95849.99 | 20-MAR-06:10 |
April | 14229.36 | 21-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 825.25 | 21-APR-07:19 | 12014.23 | 10-APR-15:09 | 6.85 | 04-APR-07:10 | 68351.65 | 03-APR-06:10 |
May | 14264.07 | 08-MAY-07:10 | 2323.70 | 01-MAY-18:49 | 40437.79 | 01-MAY-07:10 | 825.30 | 08-MAY-07:19 | 25152.04 | 30-MAY-14:20 | 6.85 | 01-MAY-05:10 | 16315.26 | 01-MAY-06:10 |
June | 14175.33 | 29-JUN-07:10 | 2323.70 | 01-JUN-19:19 | 40437.79 | 01-JUN-07:10 | 825.18 | 29-JUN-07:19 | 23913.91 | 19-JUN-10:30 | 6.85 | 18-JUN-15:00 | 822.02 | 02-JUN-06:40 |
July | 14158.58 | 24-JUL-07:10 | 2323.70 | 01-JUL-19:30 | 40437.79 | 03-JUL-07:10 | 825.16 | 24-JUL-07:19 | 24805.99 | 10-JUL-15:30 | 6.85 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 14341.69 | 16-AUG-07:10 | 3824.74 | 16-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 825.40 | 16-AUG-07:19 | 24768.77 | 14-AUG-09:00 | 6.85 | 13-AUG-15:09 | 0.00 | 01-AUG-00:10 |
September | 14756.22 | 27-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 825.94 | 27-SEP-07:19 | 20836.68 | 05-SEP-15:20 | 6.85 | 01-SEP-05:10 | 1774.15 | 20-SEP-06:10 |
October | 16041.13 | 31-OCT-15:00 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 827.37 | 06-OCT-07:19 | 14554.05 | 04-OCT-15:50 | 6.85 | 16-OCT-06:10 | 18073.78 | 27-OCT-06:10 |
November | 17672.30 | 06-NOV-16:49 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 828.65 | 06-NOV-16:00 | 6274.73 | 03-NOV-14:09 | 6.85 | 07-NOV-17:10 | 111570.78 | 24-NOV-07:10 |
December | 17672.30 | 01-DEC-16:30 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.65 | 01-DEC-16:40 | 3461.13 | 26-DEC-07:10 | 6.85 | 01-DEC-06:19 | 111832.01 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14158.58 | 2323.70 | 40437.79 | 825.16 | 3461.13 | 6.85 | 0.00 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 40437.79 | 828.65 | 25152.04 | 6.85 | 195795.69 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 111.66 | 15-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 14021.40 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27241.28 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57695.49 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 73260.87 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 63218.34 | 07-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 68250.84 | 16-AUG-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 53653.49 | 07-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 37273.70 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6475.30 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 73260.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 230126.34 | 02-JAN-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6679.97 | 6.85 | 195134.77 | 0.00 | 0.00 |
February | 200871.81 | 06-FEB-07:10 | 5295.85 | 18346.02 | 0.00 | 243.23 | 5216.40 | 6.85 | 171763.46 | 0.00 | 0.00 |
March | 125108.46 | 13-MAR-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3141.05 | 6.85 | 93655.80 | 0.00 | 0.00 |
April | 94741.65 | 03-APR-06:10 | 4924.14 | 18346.02 | 0.00 | 243.12 | 2869.87 | 6.85 | 68351.65 | 0.00 | 0.00 |
May | 134482.41 | 30-MAY-14:09 | 13903.46 | 37678.39 | 0.00 | 823.25 | 24439.01 | 6.85 | 0.00 | 57631.45 | 0.00 |
June | 145872.20 | 19-JUN-12:09 | 13903.46 | 38626.93 | 0.00 | 823.79 | 19250.29 | 6.85 | 0.00 | 73260.87 | 0.00 |
July | 138015.35 | 07-JUL-14:30 | 13903.46 | 37678.39 | 0.00 | 823.25 | 22518.17 | 6.85 | 0.00 | 63085.23 | 0.00 |
August | 141164.51 | 16-AUG-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 22084.39 | 6.85 | 0.00 | 65891.65 | 0.00 |
September | 121653.40 | 07-SEP-15:20 | 13903.46 | 38454.47 | 0.00 | 823.69 | 19121.75 | 6.85 | 0.00 | 49343.17 | 0.00 |
October | 100983.96 | 04-OCT-15:30 | 13903.46 | 38454.47 | 0.00 | 823.69 | 14071.90 | 6.85 | 0.00 | 33723.59 | 0.00 |
November | 138628.17 | 24-NOV-07:10 | 5032.35 | 18346.02 | 0.00 | 243.14 | 3429.03 | 6.85 | 111570.78 | 0.00 | 0.00 |
December | 143602.19 | 11-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3458.57 | 6.85 | 111832.01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 94741.65 | 4924.14 | 18346.02 | 0.00 | 243.12 | 2869.87 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 230126.34 | 13903.46 | 38626.93 | 3824.74 | 823.79 | 24439.01 | 6.85 | 195134.77 | 73260.87 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 85355.49 | 02-JAN-09:09 | 0.00 | 10198.15 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 86586.19 | 06-FEB-07:49 | 0.00 | 10205.25 | 06-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 57327.73 | 23-MAR-06:19 | 0.00 | 10178.45 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 33618.67 | 03-APR-06:19 | 0.00 | 10080.27 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 12593.55 | 01-MAY-06:10 | 0.00 | 9952.32 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9801.10 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9686.88 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9649.48 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 675.60 | 30-SEP-06:10 | 0.00 | 9719.06 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 25067.86 | 28-OCT-06:40 | 0.00 | 9857.40 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 60591.78 | 24-NOV-07:30 | 0.00 | 10003.38 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 59240.53 | 22-DEC-07:19 | 0.00 | 10124.30 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9649.48 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 86586.19 | 0.00 | 10205.25 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.29 | 1.67 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 19.29 | 1.67 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.29 | 1.67 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 18.78 | 2.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 18.82 | 2.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.41 | 2.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.88 | 2.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 1.33 | 18.36 | 0.83 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 4.17 | 18.75 | 3.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.42 | 2.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.83 | 16.13 | 10.50 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
February | 19.00 | 16.36 | 8.50 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
March | 0.83 | 18.01 | 0.33 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
April | 0.17 | 19.37 | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.37 | 3.17 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.48 | 1.50 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 17.79 | 0.50 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
December | 4.50 | 16.22 | 2.33 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
Annual Sum or Average | 47.67 | 16.32 | 22.33 | 16.70 | 5.50 | 17.48 | 5.00 | 18.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.83 | 19.37 | 10.50 | 19.37 | 3.33 | 27.48 | 3.17 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.33 | 15.18 | 4.33 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
February | 11.50 | 15.24 | 1.50 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
March | 0.50 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.79 | 6.33 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.61 | 5.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.78 | 12.00 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.75 | 6.33 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.82 | 5.67 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
December | 3.67 | 15.55 | 0.83 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
Annual Sum or Average | 31.83 | 15.32 | 6.67 | 15.42 | 36.00 | 21.38 | 35.33 | 23.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.33 | 17.06 | 4.33 | 17.06 | 12.33 | 27.82 | 12.00 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 15.57 | 3.50 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
February | 8.33 | 15.72 | 1.67 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
March | 0.17 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.62 | 3.67 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.47 | 3.50 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.69 | 8.50 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.90 | 5.17 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.10 | 5.67 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.74 | 2.67 | 27.74 |
November | 1.00 | 17.42 | 0.17 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
December | 2.17 | 15.80 | 0.50 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
Annual Sum or Average | 24.83 | 15.73 | 5.83 | 16.01 | 30.33 | 21.86 | 29.17 | 23.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 17.42 | 3.50 | 17.71 | 8.83 | 28.10 | 8.50 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.33 | 15.05 | 5.00 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
February | 12.33 | 15.11 | 2.50 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
March | 0.17 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.64 | 1.00 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.70 | 4.17 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.01 | 3.67 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.04 | 6.33 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.04 | 3.50 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.19 | 3.00 | 28.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.65 | 0.50 | 27.65 |
November | 0.83 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
December | 3.67 | 15.46 | 1.00 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
Annual Sum or Average | 32.33 | 15.18 | 8.50 | 15.19 | 30.67 | 20.68 | 22.17 | 22.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 0.00 | 15.11 |
Maximum of Months | 15.33 | 16.88 | 5.00 | 16.88 | 9.50 | 28.19 | 6.33 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 16.76 | 8.33 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
February | 4.00 | 19.01 | 3.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.67 | 17.27 | 11.50 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.67 | 19.01 | 8.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 15.28 | 1.33 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
February | 0.83 | 17.23 | 0.17 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.55 | 2.50 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.33 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.60 | 5.33 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.54 | 3.83 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.63 | 4.67 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.00 | 15.52 | 1.50 | 15.76 | 17.67 | 23.74 | 17.67 | 25.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 17.23 | 1.33 | 17.58 | 5.33 | 27.63 | 5.33 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.83 | 17.77 | 62.33 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
February | 56.83 | 17.85 | 56.50 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
March | 37.83 | 18.76 | 37.83 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
April | 12.33 | 19.49 | 12.33 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
May | 0.33 | 20.26 | 0.33 | 20.26 | 0.33 | 22.60 | 0.33 | 23.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.70 | 1.00 | 25.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.99 | 5.83 | 25.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 25.66 | 12.50 | 25.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.47 | 10.00 | 26.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.53 | 4.00 | 27.53 |
November | 21.17 | 19.15 | 21.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 48.00 | 18.78 | 48.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
Annual Sum or Average | 243.33 | 18.35 | 238.50 | 18.38 | 33.83 | 18.90 | 33.67 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 0.00 | 17.85 |
Maximum of Months | 66.83 | 20.26 | 62.33 | 20.26 | 12.50 | 27.53 | 12.50 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 15.24 | 2.33 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
February | 0.83 | 17.19 | 0.17 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 1.00 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.61 | 2.67 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.71 | 4.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.76 | 2.33 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.82 | 2.50 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.83 | 15.45 | 2.50 | 15.68 | 16.33 | 23.04 | 13.00 | 24.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 17.19 | 2.33 | 17.53 | 5.33 | 27.82 | 4.00 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 16.08 | 6.33 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
February | 5.83 | 17.26 | 2.67 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.50 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.67 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
Annual Sum or Average | 18.50 | 16.42 | 9.00 | 16.86 | 1.17 | 17.28 | 1.17 | 17.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.17 | 17.26 | 6.33 | 17.98 | 0.67 | 27.28 | 0.67 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 15.14 | 2.17 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
February | 2.50 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.80 | 5.50 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 3.00 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.75 | 9.17 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.69 | 5.67 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.84 | 5.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
Annual Sum or Average | 11.17 | 15.15 | 2.17 | 15.20 | 29.33 | 23.83 | 29.00 | 25.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.33 | 15.20 | 2.17 | 15.21 | 9.33 | 27.84 | 9.17 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 15.35 | 1.67 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
February | 2.17 | 15.81 | 0.17 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.33 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.52 | 2.67 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.36 | 2.00 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.57 | 6.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.84 | 4.33 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.99 | 6.00 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.62 | 4.67 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
Annual Sum or Average | 9.00 | 15.46 | 1.83 | 15.69 | 27.00 | 24.25 | 26.83 | 25.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 15.81 | 1.67 | 16.07 | 6.50 | 27.99 | 6.50 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 15.06 | 2.83 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
February | 2.50 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.71 | 0.67 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.61 | 4.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.90 | 3.17 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.94 | 5.17 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.96 | 2.83 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.05 | 3.00 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.64 | 0.50 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
Annual Sum or Average | 11.17 | 15.08 | 2.83 | 15.12 | 26.00 | 23.42 | 19.33 | 24.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 15.16 | 2.83 | 15.16 | 7.83 | 28.05 | 5.17 | 28.08 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.01 | 94.17 | 21.76 | 94.17 | 21.57 |
February | 454.00 | 22.64 | 16.17 | 22.59 | 16.17 | 22.54 |
March | 496.67 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
April | 313.00 | 23.70 | 28.67 | 23.81 | 0.00 | 23.81 |
May | 55.67 | 23.95 | 190.50 | 24.36 | 0.00 | 24.36 |
June | 0.00 | 0.00 | 422.33 | 24.36 | 0.00 | 24.36 |
July | 0.00 | 0.00 | 497.00 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 471.00 | 24.39 | 0.00 | 24.39 |
September | 10.50 | 24.00 | 364.17 | 24.45 | 0.00 | 24.45 |
October | 86.33 | 24.02 | 258.00 | 24.31 | 0.00 | 24.31 |
November | 329.33 | 23.41 | 48.00 | 23.61 | 0.00 | 23.61 |
December | 497.00 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 2744.50 | 23.03 | 2390.00 | 23.60 | 110.33 | 23.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.76 | 0.00 | 21.57 |
Maximum of Months | 502.00 | 24.02 | 497.00 | 24.45 | 94.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.05 | 213.17 | 20.83 | 213.17 | 20.71 |
February | 454.00 | 21.47 | 154.00 | 21.31 | 154.00 | 21.22 |
March | 514.00 | 22.49 | 6.67 | 22.47 | 6.67 | 22.44 |
April | 391.00 | 23.11 | 14.33 | 23.16 | 0.00 | 23.16 |
May | 152.17 | 23.63 | 140.17 | 23.94 | 0.00 | 23.94 |
June | 0.33 | 24.00 | 408.33 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 494.50 | 24.33 | 0.00 | 24.33 |
August | 0.00 | 0.00 | 460.00 | 24.34 | 0.00 | 24.34 |
September | 32.67 | 23.70 | 310.17 | 24.30 | 0.00 | 24.30 |
October | 188.17 | 23.68 | 191.83 | 23.96 | 0.00 | 23.96 |
November | 454.33 | 22.55 | 47.00 | 22.41 | 43.67 | 22.29 |
December | 497.00 | 21.64 | 85.67 | 21.50 | 85.67 | 21.39 |
Annual Sum or Average | 3185.67 | 22.21 | 2525.83 | 22.81 | 503.17 | 22.63 |
Minimum of Months | 0.00 | 0.00 | 6.67 | 20.83 | 0.00 | 20.71 |
Maximum of Months | 514.00 | 24.00 | 494.50 | 24.34 | 213.17 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.57 | 333.33 | 20.40 | 333.33 | 20.33 |
February | 454.00 | 20.88 | 311.17 | 20.74 | 311.17 | 20.68 |
March | 514.00 | 21.87 | 83.00 | 21.70 | 83.00 | 21.57 |
April | 406.17 | 22.63 | 27.67 | 22.59 | 16.50 | 22.51 |
May | 191.50 | 23.44 | 120.17 | 23.76 | 0.00 | 23.76 |
June | 12.00 | 23.65 | 399.33 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 491.50 | 24.36 | 0.00 | 24.36 |
August | 1.83 | 23.70 | 437.17 | 24.35 | 0.00 | 24.35 |
September | 79.00 | 23.46 | 266.33 | 24.11 | 0.00 | 24.11 |
October | 273.33 | 23.15 | 131.67 | 23.46 | 0.00 | 23.46 |
November | 478.83 | 21.82 | 117.83 | 21.54 | 117.83 | 21.35 |
December | 497.00 | 20.90 | 309.83 | 20.73 | 309.83 | 20.66 |
Annual Sum or Average | 3409.67 | 21.73 | 3029.00 | 22.23 | 1171.67 | 21.95 |
Minimum of Months | 0.00 | 0.00 | 27.67 | 20.40 | 0.00 | 20.33 |
Maximum of Months | 514.00 | 23.70 | 491.50 | 24.36 | 333.33 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.94 | 444.67 | 19.87 | 444.67 | 19.85 |
February | 454.00 | 20.11 | 421.17 | 20.07 | 421.17 | 20.06 |
March | 513.17 | 20.95 | 253.50 | 20.71 | 253.50 | 20.58 |
April | 413.83 | 21.83 | 97.33 | 21.69 | 73.83 | 21.49 |
May | 234.67 | 23.08 | 132.17 | 23.53 | 11.17 | 23.54 |
June | 45.33 | 24.65 | 412.50 | 24.34 | 27.50 | 24.39 |
July | 79.00 | 25.86 | 495.83 | 24.68 | 79.00 | 24.82 |
August | 48.67 | 25.42 | 450.50 | 24.48 | 38.50 | 24.59 |
September | 140.17 | 23.27 | 256.83 | 23.92 | 12.00 | 23.94 |
October | 337.67 | 22.33 | 131.50 | 22.52 | 36.50 | 22.38 |
November | 489.00 | 20.89 | 242.50 | 20.60 | 242.50 | 20.46 |
December | 497.00 | 20.13 | 465.33 | 20.10 | 465.33 | 20.09 |
Annual Sum or Average | 3754.50 | 21.24 | 3803.83 | 21.70 | 2105.67 | 21.43 |
Minimum of Months | 45.33 | 19.94 | 97.33 | 19.87 | 11.17 | 19.85 |
Maximum of Months | 513.17 | 25.86 | 495.83 | 24.68 | 465.33 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 406.83 | 19.89 | 406.83 | 19.84 |
February | 454.00 | 20.34 | 361.17 | 20.20 | 361.17 | 20.15 |
March | 495.33 | 21.38 | 175.50 | 21.01 | 175.50 | 20.80 |
April | 346.67 | 22.06 | 125.67 | 22.26 | 50.33 | 22.07 |
May | 189.00 | 23.48 | 224.33 | 24.06 | 32.17 | 24.18 |
June | 50.17 | 25.70 | 446.50 | 24.51 | 42.00 | 24.63 |
July | 95.33 | 26.29 | 496.17 | 24.85 | 95.33 | 25.05 |
August | 55.67 | 26.26 | 479.50 | 24.63 | 53.50 | 24.79 |
September | 118.17 | 24.00 | 331.00 | 24.32 | 33.00 | 24.44 |
October | 258.17 | 22.60 | 176.50 | 23.07 | 21.33 | 22.95 |
November | 475.00 | 21.17 | 193.67 | 20.80 | 193.33 | 20.60 |
December | 497.00 | 20.28 | 402.83 | 20.17 | 402.83 | 20.12 |
Annual Sum or Average | 3536.50 | 21.50 | 3819.67 | 22.04 | 1867.33 | 21.79 |
Minimum of Months | 50.17 | 20.03 | 125.67 | 19.89 | 21.33 | 19.84 |
Maximum of Months | 502.00 | 26.29 | 496.17 | 24.85 | 406.83 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.67 | 20.52 | 328.33 | 20.17 | 328.33 | 20.02 |
February | 429.50 | 20.93 | 283.00 | 20.58 | 283.00 | 20.44 |
March | 428.67 | 21.33 | 186.83 | 21.12 | 163.50 | 20.91 |
April | 341.50 | 21.91 | 126.83 | 22.11 | 56.33 | 21.91 |
May | 219.67 | 23.16 | 192.50 | 23.74 | 21.50 | 23.81 |
June | 56.67 | 24.79 | 420.00 | 24.38 | 34.00 | 24.47 |
July | 88.67 | 26.02 | 494.83 | 24.74 | 88.67 | 24.91 |
August | 60.33 | 25.88 | 467.00 | 24.60 | 51.67 | 24.75 |
September | 115.83 | 24.07 | 336.50 | 24.33 | 33.83 | 24.46 |
October | 199.00 | 22.74 | 257.83 | 23.53 | 27.67 | 23.48 |
November | 409.83 | 21.34 | 178.83 | 21.09 | 154.00 | 20.85 |
December | 466.83 | 20.84 | 313.83 | 20.56 | 307.67 | 20.40 |
Annual Sum or Average | 3308.17 | 21.72 | 3586.33 | 22.28 | 1550.17 | 22.02 |
Minimum of Months | 56.67 | 20.52 | 126.83 | 20.17 | 21.50 | 20.02 |
Maximum of Months | 491.67 | 26.02 | 494.83 | 24.74 | 328.33 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.12 | 398.50 | 19.96 | 398.50 | 19.90 |
February | 453.83 | 20.42 | 359.17 | 20.24 | 359.17 | 20.17 |
March | 463.83 | 21.16 | 212.50 | 20.91 | 203.17 | 20.74 |
April | 361.33 | 21.85 | 122.67 | 21.96 | 64.67 | 21.77 |
May | 214.67 | 23.33 | 210.83 | 23.86 | 34.50 | 23.97 |
June | 58.67 | 25.15 | 436.33 | 24.46 | 40.83 | 24.57 |
July | 92.50 | 26.11 | 496.00 | 24.80 | 92.50 | 24.98 |
August | 58.33 | 25.92 | 472.33 | 24.61 | 51.00 | 24.75 |
September | 124.33 | 23.70 | 303.33 | 24.16 | 26.67 | 24.27 |
October | 266.50 | 22.40 | 200.00 | 22.92 | 35.67 | 22.79 |
November | 468.17 | 20.96 | 214.83 | 20.65 | 214.33 | 20.49 |
December | 497.00 | 20.33 | 410.83 | 20.20 | 410.83 | 20.15 |
Annual Sum or Average | 3561.17 | 21.43 | 3837.33 | 21.97 | 1931.83 | 21.72 |
Minimum of Months | 58.33 | 20.12 | 122.67 | 19.96 | 26.67 | 19.90 |
Maximum of Months | 502.00 | 26.11 | 496.00 | 24.80 | 410.83 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.21 | 446.33 | 20.16 | 446.33 | 20.15 |
February | 454.00 | 20.37 | 432.83 | 20.35 | 432.83 | 20.34 |
March | 514.00 | 20.94 | 264.83 | 20.80 | 264.83 | 20.73 |
April | 470.00 | 21.90 | 57.67 | 21.76 | 55.67 | 21.63 |
May | 358.33 | 23.09 | 71.83 | 23.26 | 13.17 | 23.28 |
June | 38.50 | 24.25 | 374.33 | 24.21 | 17.00 | 24.24 |
July | 42.83 | 25.41 | 496.83 | 24.46 | 42.83 | 24.53 |
August | 24.33 | 25.66 | 456.83 | 24.40 | 23.50 | 24.46 |
September | 91.33 | 23.66 | 292.00 | 24.12 | 8.33 | 24.14 |
October | 275.83 | 23.06 | 133.33 | 23.38 | 0.50 | 23.38 |
November | 486.33 | 21.66 | 137.00 | 21.39 | 137.00 | 21.22 |
December | 497.00 | 20.57 | 427.00 | 20.53 | 427.00 | 20.51 |
Annual Sum or Average | 3754.50 | 21.48 | 3590.83 | 21.91 | 1869.00 | 21.64 |
Minimum of Months | 24.33 | 20.21 | 57.67 | 20.16 | 0.50 | 20.15 |
Maximum of Months | 514.00 | 25.66 | 496.83 | 24.46 | 446.33 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 399.33 | 20.22 | 399.33 | 20.18 |
February | 454.00 | 20.65 | 343.33 | 20.54 | 343.33 | 20.49 |
March | 512.67 | 21.55 | 133.50 | 21.30 | 133.50 | 21.13 |
April | 372.67 | 22.31 | 55.50 | 22.40 | 21.50 | 22.30 |
May | 218.67 | 23.21 | 165.83 | 23.83 | 20.67 | 23.86 |
June | 22.17 | 25.50 | 441.33 | 24.41 | 18.67 | 24.46 |
July | 67.83 | 26.18 | 497.00 | 24.74 | 67.83 | 24.90 |
August | 37.50 | 26.42 | 498.17 | 24.59 | 37.50 | 24.71 |
September | 60.33 | 24.70 | 374.50 | 24.50 | 24.17 | 24.59 |
October | 168.33 | 23.45 | 227.17 | 23.90 | 0.83 | 23.90 |
November | 437.33 | 21.94 | 99.83 | 21.69 | 94.83 | 21.50 |
December | 497.00 | 20.86 | 298.83 | 20.69 | 298.83 | 20.61 |
Annual Sum or Average | 3350.50 | 21.71 | 3534.33 | 22.34 | 1461.00 | 22.10 |
Minimum of Months | 22.17 | 20.33 | 55.50 | 20.22 | 0.83 | 20.18 |
Maximum of Months | 512.67 | 26.42 | 498.17 | 24.74 | 399.33 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.23 | 341.67 | 19.99 | 341.67 | 19.89 |
February | 447.33 | 20.64 | 280.67 | 20.38 | 280.67 | 20.26 |
March | 489.00 | 21.24 | 132.00 | 20.99 | 130.17 | 20.82 |
April | 405.50 | 21.78 | 75.00 | 21.84 | 41.00 | 21.69 |
May | 335.00 | 22.62 | 84.17 | 23.01 | 17.33 | 23.01 |
June | 128.50 | 23.83 | 385.17 | 24.14 | 97.67 | 24.13 |
July | 134.17 | 24.76 | 494.17 | 24.53 | 134.17 | 24.57 |
August | 77.50 | 25.09 | 485.83 | 24.55 | 74.33 | 24.63 |
September | 107.17 | 24.18 | 383.33 | 24.44 | 60.33 | 24.52 |
October | 133.50 | 23.24 | 303.33 | 24.14 | 15.50 | 24.19 |
November | 401.33 | 21.68 | 93.00 | 21.60 | 66.33 | 21.42 |
December | 479.50 | 20.97 | 253.50 | 20.77 | 244.00 | 20.62 |
Annual Sum or Average | 3640.50 | 21.69 | 3311.83 | 22.29 | 1503.17 | 22.09 |
Minimum of Months | 77.50 | 20.23 | 75.00 | 19.99 | 15.50 | 19.89 |
Maximum of Months | 502.00 | 25.09 | 494.17 | 24.55 | 341.67 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 394.00 | 20.25 | 394.00 | 20.20 |
February | 454.00 | 20.66 | 357.67 | 20.53 | 357.67 | 20.48 |
March | 501.17 | 21.52 | 159.00 | 21.30 | 156.00 | 21.16 |
April | 391.67 | 22.20 | 66.33 | 22.27 | 31.50 | 22.15 |
May | 242.50 | 23.18 | 160.83 | 23.69 | 17.50 | 23.70 |
June | 34.83 | 25.48 | 444.00 | 24.45 | 27.33 | 24.53 |
July | 63.33 | 26.14 | 496.33 | 24.72 | 63.33 | 24.86 |
August | 33.83 | 26.34 | 496.33 | 24.58 | 33.83 | 24.69 |
September | 59.50 | 24.39 | 354.50 | 24.41 | 18.50 | 24.49 |
October | 165.17 | 23.38 | 238.50 | 23.90 | 0.83 | 23.91 |
November | 454.83 | 21.78 | 119.33 | 21.51 | 119.33 | 21.34 |
December | 497.00 | 20.82 | 341.33 | 20.68 | 341.33 | 20.62 |
Annual Sum or Average | 3399.83 | 21.68 | 3628.17 | 22.29 | 1561.17 | 22.04 |
Minimum of Months | 33.83 | 20.37 | 66.33 | 20.25 | 0.83 | 20.20 |
Maximum of Months | 502.00 | 26.34 | 496.33 | 24.72 | 394.00 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 409.33 | 20.06 | 409.33 | 20.02 |
February | 454.00 | 20.37 | 385.17 | 20.30 | 385.17 | 20.27 |
March | 513.17 | 21.26 | 173.50 | 21.04 | 173.50 | 20.91 |
April | 410.67 | 22.24 | 49.67 | 22.18 | 32.50 | 22.05 |
May | 187.83 | 23.32 | 135.17 | 23.73 | 0.00 | 23.73 |
June | 28.17 | 24.88 | 426.67 | 24.34 | 20.33 | 24.38 |
July | 60.67 | 25.75 | 496.67 | 24.62 | 60.67 | 24.74 |
August | 32.67 | 25.89 | 467.00 | 24.48 | 32.00 | 24.57 |
September | 103.17 | 23.58 | 290.83 | 24.10 | 11.50 | 24.12 |
October | 280.83 | 22.82 | 130.50 | 23.18 | 4.00 | 23.17 |
November | 485.17 | 21.40 | 160.67 | 21.10 | 160.67 | 20.92 |
December | 497.00 | 20.43 | 421.33 | 20.37 | 421.33 | 20.35 |
Annual Sum or Average | 3555.33 | 21.45 | 3546.50 | 21.97 | 1711.00 | 21.70 |
Minimum of Months | 28.17 | 20.15 | 49.67 | 20.06 | 0.00 | 20.02 |
Maximum of Months | 513.17 | 25.89 | 496.67 | 24.62 | 421.33 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.12 | 330.67 | 19.96 | 330.67 | 19.89 |
February | 385.00 | 20.59 | 272.50 | 20.40 | 272.50 | 20.32 |
March | 417.50 | 21.59 | 113.83 | 21.30 | 112.67 | 21.11 |
April | 294.00 | 22.37 | 69.67 | 22.68 | 12.83 | 22.61 |
May | 139.33 | 23.73 | 186.33 | 24.26 | 18.83 | 24.39 |
June | 36.17 | 25.90 | 385.50 | 24.59 | 32.50 | 24.70 |
July | 88.50 | 26.32 | 422.00 | 24.97 | 88.50 | 25.17 |
August | 48.50 | 26.42 | 410.00 | 24.74 | 48.50 | 24.90 |
September | 81.17 | 24.50 | 288.67 | 24.54 | 31.00 | 24.67 |
October | 199.00 | 23.05 | 154.33 | 23.58 | 5.00 | 23.59 |
November | 389.33 | 21.50 | 127.17 | 21.18 | 123.67 | 20.97 |
December | 422.00 | 20.58 | 291.17 | 20.40 | 291.17 | 20.32 |
Annual Sum or Average | 2927.50 | 21.72 | 3051.83 | 22.30 | 1367.83 | 22.07 |
Minimum of Months | 36.17 | 20.12 | 69.67 | 19.96 | 5.00 | 19.89 |
Maximum of Months | 427.00 | 26.42 | 422.00 | 24.97 | 330.67 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.33 | 20.78 | 286.50 | 20.43 | 286.50 | 20.26 |
February | 420.00 | 21.26 | 233.00 | 20.97 | 226.83 | 20.79 |
March | 421.33 | 21.73 | 122.17 | 21.60 | 98.17 | 21.41 |
April | 330.83 | 22.34 | 90.17 | 22.63 | 18.83 | 22.54 |
May | 170.83 | 23.35 | 191.00 | 23.92 | 5.50 | 23.97 |
June | 40.67 | 25.14 | 436.67 | 24.41 | 28.33 | 24.48 |
July | 80.50 | 26.05 | 497.00 | 24.74 | 80.50 | 24.90 |
August | 48.17 | 26.35 | 482.17 | 24.61 | 48.00 | 24.76 |
September | 82.00 | 24.62 | 366.00 | 24.48 | 33.33 | 24.61 |
October | 161.17 | 23.35 | 278.83 | 24.05 | 11.00 | 24.11 |
November | 385.83 | 21.82 | 130.50 | 21.70 | 92.33 | 21.47 |
December | 452.00 | 21.20 | 253.00 | 20.96 | 243.17 | 20.79 |
Annual Sum or Average | 3078.67 | 22.00 | 3367.00 | 22.64 | 1172.50 | 22.42 |
Minimum of Months | 40.67 | 20.78 | 90.17 | 20.43 | 5.50 | 20.26 |
Maximum of Months | 485.33 | 26.35 | 497.00 | 24.74 | 286.50 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 359.83 | 20.16 | 359.83 | 20.08 |
February | 453.50 | 20.71 | 320.33 | 20.49 | 320.33 | 20.41 |
March | 460.83 | 21.52 | 143.00 | 21.32 | 133.33 | 21.15 |
April | 354.33 | 22.31 | 83.50 | 22.49 | 27.50 | 22.38 |
May | 157.00 | 23.55 | 219.67 | 24.06 | 15.83 | 24.15 |
June | 44.83 | 25.60 | 449.67 | 24.49 | 37.00 | 24.60 |
July | 84.83 | 26.13 | 497.00 | 24.79 | 84.83 | 24.96 |
August | 45.33 | 26.31 | 486.33 | 24.61 | 45.33 | 24.75 |
September | 87.83 | 24.15 | 334.17 | 24.34 | 25.33 | 24.44 |
October | 218.50 | 22.95 | 209.50 | 23.58 | 3.83 | 23.59 |
November | 455.33 | 21.44 | 147.17 | 21.15 | 145.67 | 20.96 |
December | 497.00 | 20.68 | 353.33 | 20.52 | 353.33 | 20.45 |
Annual Sum or Average | 3361.33 | 21.68 | 3603.50 | 22.28 | 1552.17 | 22.04 |
Minimum of Months | 44.83 | 20.35 | 83.50 | 20.16 | 3.83 | 20.08 |
Maximum of Months | 502.00 | 26.31 | 497.00 | 24.79 | 359.83 | 24.96 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.01263 | 24.58061 | -0.3334 | 9.34610 |
February | 454.00000 | 22.64310 | 20.42118 | -0.1974 | 6.40531 |
March | 514.00000 | 23.48660 | 28.22488 | 0.07480 | 5.54082 |
April | 485.00000 | 23.93297 | 33.53354 | 0.24897 | 6.69725 |
May | 508.00000 | 24.23734 | 40.46703 | -0.4767 | 10.11498 |
June | 496.00000 | 24.32448 | 50.09775 | -0.3372 | 7.73929 |
July | 497.00000 | 24.38131 | 53.61717 | -0.2827 | 7.03546 |
August | 514.00000 | 24.35962 | 50.14319 | -0.3073 | 7.43890 |
September | 485.00000 | 24.36093 | 45.69301 | -0.3619 | 8.15992 |
October | 502.00000 | 24.31005 | 39.31760 | 0.42650 | 9.20805 |
November | 489.00000 | 23.73113 | 30.72932 | 0.16652 | 6.60087 |
December | 497.00000 | 23.03235 | 23.53593 | -0.0783 | 5.54170 |
Annual Sum or Average | 5943.00000 | 23.74156 | 36.82175 | -0.1219 | 7.49710 |
Minimum of Months | 454.00000 | 22.01263 | 20.42118 | -0.4767 | 5.54082 |
Maximum of Months | 514.00000 | 24.38131 | 53.61717 | 0.42650 | 10.11498 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.04663 | 25.68882 | -0.5519 | 13.16438 |
February | 454.00000 | 21.46703 | 21.54011 | -0.4650 | 10.15779 |
March | 514.00000 | 22.48700 | 30.00079 | -0.1458 | 6.23165 |
April | 485.00000 | 23.30737 | 35.28100 | 0.10896 | 6.22898 |
May | 508.00000 | 24.01299 | 41.70745 | -0.5525 | 11.89611 |
June | 496.00000 | 24.24856 | 50.58155 | -0.3715 | 8.20093 |
July | 497.00000 | 24.32751 | 54.29358 | -0.3047 | 7.26021 |
August | 514.00000 | 24.30936 | 50.83515 | -0.3324 | 7.72388 |
September | 485.00000 | 24.22186 | 46.35963 | -0.4227 | 9.18132 |
October | 502.00000 | 23.98504 | 40.32872 | 0.33693 | 7.98768 |
November | 489.00000 | 22.66129 | 33.12528 | -0.0827 | 7.02894 |
December | 497.00000 | 21.63629 | 25.22854 | -0.3930 | 8.83479 |
Annual Sum or Average | 5943.00000 | 23.15467 | 38.03836 | -0.2640 | 8.65293 |
Minimum of Months | 454.00000 | 21.04663 | 21.54011 | -0.5525 | 6.22898 |
Maximum of Months | 514.00000 | 24.32751 | 54.29358 | 0.33693 | 13.16438 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56917 | 26.37093 | -0.6882 | 17.13478 |
February | 454.00000 | 20.88180 | 21.31524 | -0.6324 | 14.64884 |
March | 514.00000 | 21.87012 | 30.81478 | -0.3004 | 8.19915 |
April | 485.00000 | 22.86956 | 36.08255 | 0.00219 | 6.71975 |
May | 508.00000 | 23.87572 | 42.11122 | -0.5961 | 13.32951 |
June | 496.00000 | 24.22781 | 50.31557 | -0.3715 | 8.24677 |
July | 497.00000 | 24.35487 | 53.94989 | -0.2835 | 7.04279 |
August | 514.00000 | 24.30214 | 50.61167 | -0.3258 | 7.68045 |
September | 485.00000 | 24.09908 | 46.37758 | -0.4684 | 10.26737 |
October | 502.00000 | 23.55011 | 41.40067 | 0.22763 | 7.37280 |
November | 489.00000 | 21.86375 | 34.43779 | -0.2870 | 9.12334 |
December | 497.00000 | 20.90466 | 25.73747 | -0.5932 | 13.51999 |
Annual Sum or Average | 5943.00000 | 22.79518 | 38.42143 | -0.3583 | 10.24685 |
Minimum of Months | 454.00000 | 20.56917 | 21.31524 | -0.6882 | 6.71975 |
Maximum of Months | 514.00000 | 24.35487 | 53.94989 | 0.22763 | 17.13478 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.94113 | 27.59279 | -0.8801 | 24.02165 |
February | 454.00000 | 20.10915 | 22.14306 | -0.8574 | 22.66925 |
March | 514.00000 | 20.95085 | 32.47013 | -0.5246 | 12.79446 |
April | 485.00000 | 22.16048 | 37.66717 | -0.1572 | 8.52973 |
May | 508.00000 | 23.66284 | 43.14697 | -0.6443 | 15.86958 |
June | 496.00000 | 24.23608 | 52.30144 | -0.3138 | 7.93101 |
July | 497.00000 | 24.49016 | 57.15872 | -0.1618 | 6.71464 |
August | 514.00000 | 24.32823 | 52.66826 | -0.2597 | 7.42472 |
September | 485.00000 | 23.91486 | 48.71419 | -0.5051 | 11.96301 |
October | 502.00000 | 22.86074 | 43.59403 | 0.07535 | 7.92723 |
November | 489.00000 | 20.89494 | 36.14830 | -0.5250 | 13.78601 |
December | 497.00000 | 20.13016 | 27.47491 | -0.8127 | 20.75862 |
Annual Sum or Average | 5943.00000 | 22.32405 | 40.22286 | -0.4613 | 13.30185 |
Minimum of Months | 454.00000 | 19.94113 | 22.14306 | -0.8801 | 6.71464 |
Maximum of Months | 514.00000 | 24.49016 | 57.15872 | 0.07535 | 24.02165 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02789 | 28.39432 | -0.8348 | 22.70889 |
February | 454.00000 | 20.34435 | 22.82424 | -0.7673 | 19.88250 |
March | 514.00000 | 21.47123 | 32.40366 | -0.3776 | 11.16456 |
April | 485.00000 | 22.69762 | 36.55415 | -0.0042 | 8.61965 |
May | 508.00000 | 23.92638 | 42.33808 | -0.4949 | 13.31961 |
June | 496.00000 | 24.33449 | 51.85663 | -0.2251 | 7.47252 |
July | 497.00000 | 24.57689 | 56.46585 | -0.0708 | 6.96809 |
August | 514.00000 | 24.40941 | 51.99462 | -0.1453 | 6.87123 |
September | 485.00000 | 24.14838 | 47.85779 | -0.3703 | 10.26825 |
October | 502.00000 | 23.32178 | 42.29032 | 0.21189 | 8.59142 |
November | 489.00000 | 21.24489 | 36.25547 | -0.4238 | 12.55598 |
December | 497.00000 | 20.28428 | 28.14413 | -0.7514 | 18.92570 |
Annual Sum or Average | 5943.00000 | 22.58289 | 39.90831 | -0.3517 | 12.22484 |
Minimum of Months | 454.00000 | 20.02789 | 22.82424 | -0.8348 | 6.87123 |
Maximum of Months | 514.00000 | 24.57689 | 56.46585 | 0.21189 | 22.70889 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58894 | 26.71117 | -0.6780 | 19.68812 |
February | 454.00000 | 21.10616 | 20.88053 | -0.5649 | 16.45278 |
March | 514.00000 | 21.78575 | 30.39901 | -0.2869 | 10.80771 |
April | 485.00000 | 22.60442 | 36.05454 | -0.0252 | 8.93433 |
May | 508.00000 | 23.73794 | 42.64210 | -0.5881 | 15.28724 |
June | 496.00000 | 24.24754 | 52.11171 | -0.2873 | 7.99742 |
July | 497.00000 | 24.51261 | 56.82197 | -0.1239 | 6.87206 |
August | 514.00000 | 24.38589 | 51.98825 | -0.1666 | 7.05593 |
September | 485.00000 | 24.14831 | 47.35279 | -0.3396 | 10.14040 |
October | 502.00000 | 23.64008 | 40.51165 | 0.33031 | 10.42135 |
November | 489.00000 | 21.77290 | 34.01850 | -0.2772 | 11.17986 |
December | 497.00000 | 21.06742 | 26.05556 | -0.5464 | 15.77360 |
Annual Sum or Average | 5943.00000 | 22.81311 | 38.92983 | -0.2946 | 11.68974 |
Minimum of Months | 454.00000 | 20.58894 | 20.88053 | -0.6780 | 6.87206 |
Maximum of Months | 514.00000 | 24.51261 | 56.82197 | 0.33031 | 19.68812 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11931 | 28.23343 | -0.8219 | 22.44861 |
February | 454.00000 | 20.42476 | 22.60055 | -0.7623 | 20.42994 |
March | 514.00000 | 21.44043 | 31.98112 | -0.3859 | 11.62248 |
April | 485.00000 | 22.45639 | 37.21742 | -0.0584 | 9.13328 |
May | 508.00000 | 23.79426 | 42.98776 | -0.5463 | 14.61793 |
June | 496.00000 | 24.30283 | 52.00564 | -0.2266 | 7.71184 |
July | 497.00000 | 24.55177 | 56.86684 | -0.0814 | 6.99189 |
August | 514.00000 | 24.40371 | 52.25890 | -0.1495 | 7.00108 |
September | 485.00000 | 24.04331 | 48.31923 | -0.4077 | 10.97698 |
October | 502.00000 | 23.20003 | 42.66015 | 0.18788 | 8.95791 |
November | 489.00000 | 21.08768 | 36.43071 | -0.4676 | 13.19377 |
December | 497.00000 | 20.33111 | 28.06266 | -0.7501 | 19.14403 |
Annual Sum or Average | 5943.00000 | 22.52999 | 40.09608 | -0.3698 | 12.62991 |
Minimum of Months | 454.00000 | 20.11931 | 22.60055 | -0.8219 | 6.99189 |
Maximum of Months | 514.00000 | 24.55177 | 56.86684 | 0.18788 | 22.44861 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.21048 | 27.49717 | -0.8043 | 20.48803 |
February | 454.00000 | 20.36533 | 22.31723 | -0.7908 | 19.37875 |
March | 514.00000 | 20.94070 | 32.99639 | -0.5303 | 11.78223 |
April | 485.00000 | 21.97157 | 38.84027 | -0.2136 | 7.62385 |
May | 508.00000 | 23.38870 | 44.56294 | -0.7801 | 19.25952 |
June | 496.00000 | 24.14611 | 53.01004 | -0.3900 | 8.60123 |
July | 497.00000 | 24.38053 | 56.76019 | -0.2452 | 6.78864 |
August | 514.00000 | 24.29967 | 52.29064 | -0.3008 | 7.45699 |
September | 485.00000 | 24.08268 | 48.35984 | -0.4560 | 10.03252 |
October | 502.00000 | 23.47288 | 42.57931 | 0.22166 | 7.25904 |
November | 489.00000 | 21.67321 | 34.94294 | -0.3132 | 9.21081 |
December | 497.00000 | 20.56973 | 27.10649 | -0.6695 | 15.07142 |
Annual Sum or Average | 5943.00000 | 22.47370 | 40.23890 | -0.4376 | 11.87916 |
Minimum of Months | 454.00000 | 20.21048 | 22.31723 | -0.8043 | 6.78864 |
Maximum of Months | 514.00000 | 24.38053 | 56.76019 | 0.22166 | 20.48803 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32960 | 28.31995 | -0.7514 | 18.88711 |
February | 454.00000 | 20.65202 | 23.03557 | -0.6864 | 16.12608 |
March | 514.00000 | 21.55781 | 32.97398 | -0.3555 | 9.30981 |
April | 485.00000 | 22.76138 | 37.18224 | -0.0027 | 7.39310 |
May | 508.00000 | 23.85212 | 43.01412 | -0.5679 | 14.23153 |
June | 496.00000 | 24.31077 | 52.23442 | -0.2760 | 7.47408 |
July | 497.00000 | 24.54850 | 55.83678 | -0.1250 | 6.56865 |
August | 514.00000 | 24.44181 | 51.33118 | -0.1592 | 6.53084 |
September | 485.00000 | 24.34092 | 47.29439 | -0.3070 | 8.37260 |
October | 502.00000 | 23.93211 | 40.97934 | 0.36412 | 8.81333 |
November | 489.00000 | 22.16580 | 34.63795 | -0.1810 | 8.32997 |
December | 497.00000 | 20.86026 | 27.70131 | -0.5787 | 12.97348 |
Annual Sum or Average | 5943.00000 | 22.82788 | 39.67125 | -0.3003 | 10.38833 |
Minimum of Months | 454.00000 | 20.32960 | 23.03557 | -0.7514 | 6.53084 |
Maximum of Months | 514.00000 | 24.54850 | 55.83678 | 0.36412 | 18.88711 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22540 | 24.96889 | -0.7186 | 18.67529 |
February | 454.00000 | 20.70932 | 19.54121 | -0.6063 | 15.44455 |
March | 514.00000 | 21.38218 | 29.74671 | -0.3521 | 9.78496 |
April | 485.00000 | 22.20212 | 36.06213 | -0.1149 | 7.95956 |
May | 508.00000 | 23.20194 | 44.09426 | -0.7894 | 20.83449 |
June | 496.00000 | 24.11969 | 54.86823 | -0.3560 | 8.61229 |
July | 497.00000 | 24.46818 | 59.41909 | -0.1631 | 6.43872 |
August | 514.00000 | 24.42641 | 53.44516 | -0.1630 | 6.58788 |
September | 485.00000 | 24.29164 | 48.20101 | -0.2744 | 8.51627 |
October | 502.00000 | 24.07669 | 39.91952 | 0.46555 | 11.18108 |
November | 489.00000 | 22.11864 | 31.62513 | -0.1416 | 8.47773 |
December | 497.00000 | 21.13754 | 23.96349 | -0.4664 | 12.19415 |
Annual Sum or Average | 5943.00000 | 22.71055 | 38.96926 | -0.3055 | 11.21789 |
Minimum of Months | 454.00000 | 20.22540 | 19.54121 | -0.7894 | 6.43872 |
Maximum of Months | 514.00000 | 24.46818 | 59.41909 | 0.46555 | 20.83449 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36722 | 28.24045 | -0.7486 | 18.88234 |
February | 454.00000 | 20.65991 | 22.97138 | -0.6938 | 16.75055 |
March | 514.00000 | 21.58719 | 32.59856 | -0.3497 | 9.46722 |
April | 485.00000 | 22.59191 | 37.69417 | -0.0431 | 7.55169 |
May | 508.00000 | 23.76851 | 43.57424 | -0.6067 | 14.94429 |
June | 496.00000 | 24.33077 | 52.10825 | -0.2596 | 7.35640 |
July | 497.00000 | 24.53727 | 56.03463 | -0.1292 | 6.55883 |
August | 514.00000 | 24.45020 | 51.50402 | -0.1579 | 6.50583 |
September | 485.00000 | 24.27778 | 47.60433 | -0.3320 | 8.55979 |
October | 502.00000 | 23.93432 | 41.09292 | 0.36610 | 8.95776 |
November | 489.00000 | 21.93620 | 35.07060 | -0.2403 | 8.77559 |
December | 497.00000 | 20.82051 | 27.71299 | -0.5944 | 13.42143 |
Annual Sum or Average | 5943.00000 | 22.78749 | 39.80925 | -0.3136 | 10.61192 |
Minimum of Months | 454.00000 | 20.36722 | 22.97138 | -0.7486 | 6.50583 |
Maximum of Months | 514.00000 | 24.53727 | 56.03463 | 0.36610 | 18.88234 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15269 | 27.44405 | -0.7983 | 20.67986 |
February | 454.00000 | 20.36601 | 21.97969 | -0.7616 | 18.83709 |
March | 514.00000 | 21.26537 | 32.08894 | -0.4263 | 10.24954 |
April | 485.00000 | 22.51719 | 37.10555 | -0.0645 | 7.24796 |
May | 508.00000 | 23.83193 | 42.65217 | -0.5912 | 13.55165 |
June | 496.00000 | 24.26768 | 52.22840 | -0.3113 | 7.61984 |
July | 497.00000 | 24.48663 | 56.99488 | -0.1781 | 6.64218 |
August | 514.00000 | 24.35067 | 52.53111 | -0.2633 | 7.26428 |
September | 485.00000 | 24.05934 | 48.37381 | -0.4554 | 10.28292 |
October | 502.00000 | 23.32070 | 42.44206 | 0.18797 | 7.38665 |
November | 489.00000 | 21.41953 | 35.21948 | -0.3756 | 10.52633 |
December | 497.00000 | 20.43495 | 27.04419 | -0.7000 | 16.41454 |
Annual Sum or Average | 5943.00000 | 22.55589 | 39.80753 | -0.3927 | 11.34381 |
Minimum of Months | 454.00000 | 20.15269 | 21.97969 | -0.7983 | 6.64218 |
Maximum of Months | 514.00000 | 24.48663 | 56.99488 | 0.18797 | 20.67986 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.11781 | 27.85007 | -0.7873 | 20.77413 |
February | 385.00000 | 20.59217 | 22.25614 | -0.6838 | 16.93306 |
March | 433.00000 | 21.68334 | 31.73884 | -0.3101 | 9.41844 |
April | 410.00000 | 22.94469 | 35.96417 | 0.05806 | 7.88571 |
May | 430.00000 | 24.08662 | 41.64276 | -0.4564 | 12.01225 |
June | 418.00000 | 24.43649 | 51.43141 | -0.2186 | 7.37910 |
July | 422.00000 | 24.68802 | 56.15997 | -0.0693 | 7.06925 |
August | 433.00000 | 24.51299 | 51.78032 | -0.1456 | 6.92514 |
September | 410.00000 | 24.31867 | 47.46819 | -0.3279 | 9.32660 |
October | 427.00000 | 23.63502 | 40.97670 | 0.28146 | 8.41419 |
November | 417.00000 | 21.66475 | 35.07116 | -0.3038 | 10.07845 |
December | 422.00000 | 20.58117 | 27.49161 | -0.6486 | 15.41174 |
Annual Sum or Average | 5034.00000 | 22.78525 | 39.26481 | -0.2989 | 10.93681 |
Minimum of Months | 385.00000 | 20.11781 | 22.25614 | -0.7873 | 6.92514 |
Maximum of Months | 433.00000 | 24.68802 | 56.15997 | 0.28146 | 20.77413 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.89032 | 26.34470 | -0.5799 | 16.45833 |
February | 454.00000 | 21.50401 | 20.49953 | -0.4441 | 13.08426 |
March | 514.00000 | 22.15582 | 29.82815 | -0.1803 | 8.72245 |
April | 485.00000 | 22.94813 | 35.41328 | 0.06393 | 7.87799 |
May | 508.00000 | 23.91123 | 42.09061 | -0.5346 | 12.93192 |
June | 496.00000 | 24.29346 | 51.98461 | -0.2811 | 7.59200 |
July | 497.00000 | 24.52258 | 56.57030 | -0.1370 | 6.74438 |
August | 514.00000 | 24.41426 | 51.78234 | -0.1693 | 6.81934 |
September | 485.00000 | 24.28055 | 47.03336 | -0.2946 | 8.78639 |
October | 502.00000 | 23.97410 | 39.62387 | 0.41781 | 10.62515 |
November | 489.00000 | 22.30579 | 32.94296 | -0.1287 | 9.00402 |
December | 497.00000 | 21.51439 | 25.36502 | -0.4088 | 12.25933 |
Annual Sum or Average | 5943.00000 | 23.07118 | 38.42416 | -0.2221 | 10.06053 |
Minimum of Months | 454.00000 | 20.89032 | 20.49953 | -0.5799 | 6.74438 |
Maximum of Months | 514.00000 | 24.52258 | 56.57030 | 0.41781 | 16.45833 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34693 | 28.09553 | -0.7373 | 19.20940 |
February | 454.00000 | 20.70991 | 22.40315 | -0.6621 | 16.78310 |
March | 514.00000 | 21.78586 | 31.50903 | -0.2832 | 9.33771 |
April | 485.00000 | 22.82182 | 36.57402 | 0.03505 | 7.95992 |
May | 508.00000 | 23.97044 | 42.42110 | -0.4921 | 12.27009 |
June | 496.00000 | 24.34745 | 51.87904 | -0.2207 | 7.30044 |
July | 497.00000 | 24.56338 | 56.64085 | -0.0938 | 6.82096 |
August | 514.00000 | 24.43066 | 52.11019 | -0.1522 | 6.76966 |
September | 485.00000 | 24.18458 | 47.96512 | -0.3598 | 9.42036 |
October | 502.00000 | 23.62119 | 41.56706 | 0.29235 | 8.70074 |
November | 489.00000 | 21.61130 | 35.44747 | -0.3196 | 10.13361 |
December | 497.00000 | 20.68481 | 27.59018 | -0.6292 | 14.94797 |
Annual Sum or Average | 5943.00000 | 22.77255 | 39.64361 | -0.2996 | 10.76355 |
Minimum of Months | 454.00000 | 20.34693 | 22.40315 | -0.7373 | 6.76966 |
Maximum of Months | 514.00000 | 24.56338 | 56.64085 | 0.29235 | 19.20940 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.358215E+09 | 90739829.19 | 13.83 | 0.231420E+09 | 0.126795E+09 | 0.00 | 0.65 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 18922.49 | 27-MAR-16:00 | 14554.15 | 27-MAR-16:00 | 6749.44 | 27-MAR-13:00 | 4541.07 | 27-MAR-16:00 | 0.00 |
April | 0.355842E+10 | 0.887558E+09 | 99.39 | 0.314447E+10 | 0.413947E+09 | 0.00 | 1.00 | 07-APR-15:10 | 0.00 | 01-APR-00:10 | 32246.47 | 07-APR-15:30 | 32246.47 | 07-APR-15:30 | 4976.54 | 10-APR-08:20 | 7322.50 | 07-APR-15:30 | 0.00 |
May | 0.138817E+11 | 0.339794E+10 | 282.94 | 0.116081E+11 | 0.227360E+10 | 0.00 | 1.00 | 30-MAY-06:03 | 0.00 | 01-MAY-00:10 | 71616.53 | 30-MAY-14:00 | 71616.53 | 30-MAY-14:00 | 19875.27 | 31-MAY-06:03 | 17914.00 | 30-MAY-14:00 | 0.00 |
June | 0.501625E+11 | 0.116748E+11 | 422.88 | 0.378721E+11 | 0.122904E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 101899.77 | 19-JUN-05:02 | 69079.62 | 19-JUN-05:02 | 48531.00 | 27-JUN-06:03 | 24774.35 | 19-JUN-12:03 | 0.00 |
July | 0.734727E+11 | 0.172115E+11 | 437.43 | 0.527199E+11 | 0.207528E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 108229.54 | 22-JUL-05:03 | 76516.58 | 10-JUL-06:03 | 54418.70 | 22-JUL-05:03 | 23272.11 | 22-JUL-05:03 | 0.00 |
August | 0.753914E+11 | 0.179052E+11 | 449.97 | 0.587986E+11 | 0.165928E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 103343.94 | 17-AUG-05:03 | 76726.37 | 22-AUG-15:40 | 43480.33 | 16-AUG-06:03 | 23306.80 | 05-AUG-06:03 | 0.00 |
September | 0.388404E+11 | 0.897319E+10 | 387.04 | 0.308356E+11 | 0.800481E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 102120.30 | 07-SEP-06:03 | 74014.86 | 05-SEP-05:12 | 42877.32 | 08-SEP-06:03 | 22595.79 | 01-SEP-06:03 | 0.00 |
October | 0.175115E+11 | 0.405444E+10 | 248.36 | 0.125054E+11 | 0.500612E+10 | 0.00 | 1.00 | 02-OCT-13:00 | 0.00 | 01-OCT-00:10 | 57802.60 | 04-OCT-15:10 | 45100.85 | 04-OCT-15:20 | 23942.35 | 24-OCT-09:10 | 12649.89 | 04-OCT-15:10 | 0.00 |
November | 0.398515E+09 | 0.107155E+09 | 28.54 | 0.332649E+09 | 65866043.97 | 0.00 | 0.35 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 9454.67 | 03-NOV-14:00 | 9454.67 | 03-NOV-14:00 | 3444.96 | 10-NOV-10:00 | 2452.10 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.273575E+12 | 0.643026E+11 | 2370.40 | 0.208048E+12 | 0.655271E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.753914E+11 | 0.179052E+11 | 449.97 | 0.587986E+11 | 0.207528E+11 | 0.00 | 1.00 | 0.00 | 108229.54 | 76726.37 | 54418.70 | 24774.35 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.373809E+09 | 93979567.83 | 14.47 | 0.248991E+09 | 0.124818E+09 | 0.00 | 0.68 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 19326.45 | 27-MAR-16:00 | 15267.56 | 27-MAR-16:00 | 6860.45 | 27-MAR-12:55 | 4603.31 | 27-MAR-16:00 | 0.00 |
April | 0.384112E+10 | 0.946595E+09 | 95.94 | 0.342084E+10 | 0.420284E+09 | 0.00 | 1.00 | 07-APR-12:05 | 0.00 | 01-APR-00:10 | 42504.86 | 07-APR-14:05 | 42504.86 | 07-APR-14:05 | 5775.81 | 09-APR-12:00 | 9746.92 | 07-APR-14:05 | 0.00 |
May | 0.147147E+11 | 0.357636E+10 | 292.85 | 0.125376E+11 | 0.217712E+10 | 0.00 | 1.00 | 22-MAY-10:05 | 0.00 | 01-MAY-00:10 | 77484.24 | 30-MAY-14:05 | 77484.24 | 30-MAY-14:05 | 20334.38 | 31-MAY-06:03 | 19272.81 | 30-MAY-14:05 | 0.00 |
June | 0.495330E+11 | 0.115239E+11 | 428.32 | 0.374748E+11 | 0.120582E+11 | 0.00 | 1.00 | 01-JUN-09:40 | 0.00 | 01-JUN-00:10 | 100613.79 | 19-JUN-05:02 | 69791.66 | 26-JUN-06:03 | 47343.83 | 20-JUN-06:03 | 26590.26 | 19-JUN-12:02 | 0.00 |
July | 0.711623E+11 | 0.166552E+11 | 443.35 | 0.507968E+11 | 0.203655E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 106179.27 | 22-JUL-05:03 | 72570.02 | 10-JUL-06:03 | 62311.17 | 24-JUL-05:12 | 22711.65 | 22-JUL-05:03 | 0.00 |
August | 0.707378E+11 | 0.167966E+11 | 452.50 | 0.550798E+11 | 0.156580E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 101643.22 | 17-AUG-05:03 | 76430.31 | 22-AUG-15:10 | 44679.12 | 17-AUG-05:03 | 22743.34 | 05-AUG-06:03 | 0.00 |
September | 0.349818E+11 | 0.812344E+10 | 385.17 | 0.274436E+11 | 0.753821E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 83648.79 | 01-SEP-05:03 | 69711.63 | 05-SEP-05:12 | 31225.62 | 07-SEP-06:03 | 18339.92 | 01-SEP-05:03 | 0.00 |
October | 0.149665E+11 | 0.347532E+10 | 229.75 | 0.103677E+11 | 0.459873E+10 | 0.00 | 1.00 | 02-OCT-13:00 | 0.00 | 01-OCT-00:10 | 56884.97 | 04-OCT-14:05 | 44525.51 | 04-OCT-14:05 | 21408.13 | 24-OCT-09:10 | 12582.31 | 04-OCT-14:05 | 0.00 |
November | 0.340183E+09 | 91509188.59 | 24.67 | 0.283813E+09 | 56370189.99 | 0.00 | 0.33 | 03-NOV-14:05 | 0.00 | 01-NOV-00:10 | 8600.34 | 03-NOV-14:05 | 8600.34 | 03-NOV-14:05 | 2580.25 | 10-NOV-10:00 | 2242.16 | 03-NOV-14:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.260651E+12 | 0.612829E+11 | 2367.02 | 0.197654E+12 | 0.629972E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.711623E+11 | 0.167966E+11 | 452.50 | 0.550798E+11 | 0.203655E+11 | 0.00 | 1.00 | 0.00 | 106179.27 | 77484.24 | 62311.17 | 26590.26 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 337898.54 | 95052.55 | 0.33 | 295924.04 | 41974.50 | 0.00 | 0.01 | 15-JAN-10:10 | 0.00 | 01-JAN-00:02 | 397.15 | 15-JAN-10:10 | 347.68 | 15-JAN-10:10 | 49.47 | 15-JAN-10:10 | 111.66 | 15-JAN-10:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.428828E+09 | 0.109603E+09 | 17.41 | 0.289857E+09 | 0.138971E+09 | 0.00 | 0.64 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 20262.84 | 27-MAR-16:00 | 15330.78 | 27-MAR-16:00 | 7145.71 | 27-MAR-13:00 | 4877.02 | 27-MAR-16:00 | 0.00 |
April | 0.417262E+10 | 0.102866E+10 | 94.08 | 0.371922E+10 | 0.453403E+09 | 0.00 | 1.00 | 07-APR-12:05 | 0.00 | 01-APR-00:10 | 46371.50 | 07-APR-14:30 | 46371.50 | 07-APR-14:30 | 6546.97 | 09-APR-11:53 | 10590.07 | 07-APR-14:30 | 0.00 |
May | 0.155922E+11 | 0.380846E+10 | 292.33 | 0.133192E+11 | 0.227307E+10 | 0.00 | 1.00 | 29-MAY-10:12 | 0.00 | 01-MAY-00:10 | 85212.20 | 30-MAY-14:00 | 85212.20 | 30-MAY-14:00 | 14181.40 | 19-MAY-12:07 | 21308.07 | 30-MAY-14:00 | 0.00 |
June | 0.527624E+11 | 0.123532E+11 | 430.66 | 0.405314E+11 | 0.122310E+11 | 0.00 | 1.00 | 01-JUN-09:50 | 0.00 | 01-JUN-00:10 | 112587.76 | 19-JUN-05:02 | 76736.56 | 19-JUN-13:40 | 44630.82 | 20-JUN-06:03 | 26179.79 | 19-JUN-12:05 | 0.00 |
July | 0.760742E+11 | 0.178727E+11 | 446.63 | 0.554188E+11 | 0.206554E+11 | 0.00 | 1.00 | 01-JUL-09:00 | 0.00 | 01-JUL-00:10 | 119286.87 | 22-JUL-05:03 | 82449.12 | 10-JUL-04:02 | 66516.18 | 22-JUL-05:03 | 25515.35 | 22-JUL-05:03 | 0.00 |
August | 0.750820E+11 | 0.179004E+11 | 452.31 | 0.593827E+11 | 0.156993E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 113103.77 | 05-AUG-05:03 | 88166.36 | 22-AUG-14:40 | 48633.97 | 04-AUG-05:03 | 25476.36 | 05-AUG-05:03 | 0.00 |
September | 0.355855E+11 | 0.834110E+10 | 384.31 | 0.277732E+11 | 0.781229E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 82517.67 | 01-SEP-14:20 | 82517.67 | 01-SEP-14:20 | 28156.63 | 01-SEP-05:03 | 21452.27 | 01-SEP-14:20 | 0.00 |
October | 0.144058E+11 | 0.338677E+10 | 223.97 | 0.991882E+10 | 0.448695E+10 | 0.00 | 1.00 | 03-OCT-11:00 | 0.00 | 01-OCT-00:10 | 57941.53 | 04-OCT-13:50 | 48187.65 | 04-OCT-15:00 | 21438.88 | 24-OCT-10:00 | 12896.29 | 04-OCT-13:30 | 0.00 |
November | 0.298195E+09 | 80926813.86 | 24.17 | 0.234581E+09 | 63614429.75 | 0.00 | 0.26 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 7460.33 | 04-NOV-12:30 | 7233.58 | 03-NOV-14:00 | 2127.43 | 10-NOV-10:00 | 1979.14 | 04-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.274402E+12 | 0.648819E+11 | 2366.20 | 0.210588E+12 | 0.638141E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.760742E+11 | 0.179004E+11 | 452.31 | 0.593827E+11 | 0.206554E+11 | 0.00 | 1.00 | 0.00 | 119286.87 | 88166.36 | 66516.18 | 26179.79 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.71 | 0.00 | 327.71 | 27.30 | 1687.67 | 0.00 | 0.00 | 0.00 |
February | 448.46 | 0.00 | 448.46 | 50.20 | 1754.55 | 0.00 | 0.00 | 0.00 |
March | 621.90 | 0.00 | 621.90 | 243.87 | 1165.03 | 0.00 | 0.00 | 0.00 |
April | 746.98 | 2.12 | 744.86 | 490.54 | 839.55 | 0.00 | 0.00 | 0.00 |
May | 991.01 | 33.02 | 957.99 | 940.42 | 532.91 | 0.00 | 0.00 | 0.00 |
June | 1050.95 | 56.47 | 994.48 | 1307.33 | 291.27 | 0.00 | 0.00 | 0.00 |
July | 1015.65 | 36.73 | 978.92 | 1447.60 | 164.09 | 0.00 | 0.00 | 0.00 |
August | 899.81 | 10.71 | 889.10 | 1269.50 | 220.76 | 0.00 | 0.00 | 0.00 |
September | 678.31 | 0.13 | 678.18 | 732.49 | 442.87 | 0.00 | 0.00 | 0.00 |
October | 587.03 | 0.00 | 587.03 | 446.48 | 801.82 | 0.00 | 0.00 | 0.00 |
November | 411.74 | 0.00 | 411.74 | 131.84 | 1181.49 | 0.00 | 0.00 | 0.00 |
December | 285.85 | 0.00 | 285.85 | 18.38 | 1557.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.41 | 11.66 | 661.75 | 595.81 | 881.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.85 | 0.00 | 285.85 | 18.38 | 164.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1050.95 | 56.47 | 994.48 | 1447.60 | 1754.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.37 | 182.97 | 273.40 | 293.26 | 1047.38 | 0.00 | 0.00 | 0.00 |
February | 707.73 | 330.16 | 377.57 | 513.28 | 1055.66 | 0.00 | 0.00 | 0.00 |
March | 902.84 | 383.99 | 518.86 | 805.57 | 754.00 | 0.00 | 0.00 | 0.00 |
April | 1083.48 | 474.60 | 608.88 | 1113.23 | 548.81 | 0.00 | 0.00 | 0.00 |
May | 1314.03 | 525.17 | 788.86 | 1530.05 | 365.25 | 0.00 | 0.00 | 0.00 |
June | 1217.83 | 440.84 | 776.98 | 1595.18 | 199.72 | 0.00 | 0.00 | 0.00 |
July | 1223.16 | 441.41 | 781.75 | 1734.20 | 111.65 | 0.00 | 0.00 | 0.00 |
August | 1377.31 | 621.03 | 756.28 | 1945.18 | 148.98 | 0.00 | 0.00 | 0.00 |
September | 1027.20 | 460.87 | 566.34 | 1287.38 | 289.38 | 0.00 | 0.00 | 0.00 |
October | 931.23 | 422.07 | 509.17 | 1044.03 | 523.70 | 0.00 | 0.00 | 0.00 |
November | 575.90 | 221.15 | 354.75 | 479.48 | 746.19 | 0.00 | 0.00 | 0.00 |
December | 448.66 | 210.66 | 237.99 | 315.56 | 959.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 940.30 | 393.35 | 546.95 | 1058.45 | 559.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 448.66 | 182.97 | 237.99 | 293.26 | 111.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.31 | 621.03 | 788.86 | 1945.18 | 1055.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1695.32 | 1110.10 | 585.21 | 1699.70 | 1512.19 | 0.00 | 0.00 | 0.00 |
February | 2236.06 | 1480.09 | 755.97 | 2277.35 | 1537.67 | 0.00 | 0.00 | 0.00 |
March | 2017.35 | 1119.66 | 897.69 | 2170.41 | 1141.05 | 0.00 | 0.00 | 0.00 |
April | 1565.39 | 619.00 | 946.39 | 1737.40 | 869.85 | 0.00 | 0.00 | 0.00 |
May | 1371.84 | 286.14 | 1085.69 | 1606.75 | 573.73 | 0.00 | 0.00 | 0.00 |
June | 1287.43 | 196.80 | 1090.63 | 1739.70 | 312.20 | 0.00 | 0.00 | 0.00 |
July | 1349.48 | 234.40 | 1115.08 | 2020.18 | 168.85 | 0.00 | 0.00 | 0.00 |
August | 1802.08 | 668.42 | 1133.66 | 2722.71 | 234.52 | 0.00 | 0.00 | 0.00 |
September | 1955.30 | 1011.36 | 943.94 | 2622.25 | 456.27 | 0.00 | 0.00 | 0.00 |
October | 2678.59 | 1679.67 | 998.92 | 3354.94 | 808.93 | 0.00 | 0.00 | 0.00 |
November | 1857.37 | 1115.44 | 741.93 | 2014.34 | 1118.41 | 0.00 | 0.00 | 0.00 |
December | 1837.47 | 1304.48 | 532.99 | 1918.69 | 1386.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1802.44 | 899.21 | 903.23 | 2157.46 | 839.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1287.43 | 196.80 | 532.99 | 1606.75 | 168.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2678.59 | 1679.67 | 1133.66 | 3354.94 | 1537.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.54 | 184.54 | 266.00 | 289.31 | 1071.08 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 291.80 | 372.58 | 470.76 | 1102.90 | 0.00 | 0.00 | 0.00 |
March | 981.04 | 452.92 | 528.12 | 904.10 | 751.41 | 0.00 | 0.00 | 0.00 |
April | 1072.24 | 458.78 | 613.45 | 1112.90 | 564.63 | 0.00 | 0.00 | 0.00 |
May | 1249.05 | 474.34 | 774.71 | 1459.27 | 377.50 | 0.00 | 0.00 | 0.00 |
June | 1367.04 | 551.37 | 815.68 | 1803.63 | 211.10 | 0.00 | 0.00 | 0.00 |
July | 1280.31 | 482.12 | 798.18 | 1812.51 | 118.92 | 0.00 | 0.00 | 0.00 |
August | 1416.37 | 655.69 | 760.68 | 2009.41 | 160.51 | 0.00 | 0.00 | 0.00 |
September | 1005.51 | 439.41 | 566.10 | 1274.10 | 303.17 | 0.00 | 0.00 | 0.00 |
October | 996.89 | 484.76 | 512.13 | 1138.04 | 539.64 | 0.00 | 0.00 | 0.00 |
November | 468.13 | 135.29 | 332.84 | 333.51 | 765.95 | 0.00 | 0.00 | 0.00 |
December | 416.40 | 180.18 | 236.22 | 275.29 | 987.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.31 | 400.18 | 549.13 | 1077.89 | 576.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.40 | 135.29 | 236.22 | 275.29 | 118.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1416.37 | 655.69 | 815.68 | 2009.41 | 1102.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.23 | 0.00 | 109.23 | 8.91 | 580.60 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 17.17 | 599.63 | 0.00 | 0.00 | 0.00 |
March | 207.29 | 0.00 | 207.29 | 86.44 | 393.32 | 0.00 | 0.00 | 0.00 |
April | 248.98 | 0.71 | 248.27 | 172.58 | 278.65 | 0.00 | 0.00 | 0.00 |
May | 330.32 | 11.01 | 319.31 | 328.96 | 170.35 | 0.00 | 0.00 | 0.00 |
June | 350.30 | 18.82 | 331.48 | 446.44 | 93.26 | 0.00 | 0.00 | 0.00 |
July | 338.53 | 12.24 | 326.29 | 492.35 | 50.85 | 0.00 | 0.00 | 0.00 |
August | 299.92 | 3.57 | 296.35 | 428.37 | 73.10 | 0.00 | 0.00 | 0.00 |
September | 226.09 | 0.04 | 226.05 | 245.13 | 155.17 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 144.25 | 290.77 | 0.00 | 0.00 | 0.00 |
November | 137.24 | 0.00 | 137.24 | 38.46 | 434.71 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.95 | 555.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.46 | 3.89 | 220.57 | 202.41 | 304.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.95 | 50.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.30 | 18.82 | 331.48 | 492.35 | 599.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.24 | 0.00 | 109.24 | 8.91 | 580.64 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 17.17 | 599.67 | 0.00 | 0.00 | 0.00 |
March | 207.30 | 0.00 | 207.30 | 86.44 | 393.35 | 0.00 | 0.00 | 0.00 |
April | 248.99 | 0.71 | 248.28 | 172.59 | 278.67 | 0.00 | 0.00 | 0.00 |
May | 330.33 | 11.01 | 319.33 | 328.97 | 170.36 | 0.00 | 0.00 | 0.00 |
June | 350.32 | 18.82 | 331.49 | 446.45 | 93.27 | 0.00 | 0.00 | 0.00 |
July | 338.55 | 12.24 | 326.30 | 492.37 | 50.85 | 0.00 | 0.00 | 0.00 |
August | 299.94 | 3.57 | 296.37 | 428.39 | 73.10 | 0.00 | 0.00 | 0.00 |
September | 226.10 | 0.04 | 226.06 | 245.14 | 155.18 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 144.26 | 290.78 | 0.00 | 0.00 | 0.00 |
November | 137.25 | 0.00 | 137.25 | 38.46 | 434.74 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.95 | 555.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.47 | 3.89 | 220.58 | 202.42 | 304.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.95 | 50.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.32 | 18.82 | 331.49 | 492.37 | 599.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.24 | 0.00 | 109.24 | 8.91 | 580.64 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 17.17 | 599.67 | 0.00 | 0.00 | 0.00 |
March | 207.30 | 0.00 | 207.30 | 86.44 | 393.35 | 0.00 | 0.00 | 0.00 |
April | 248.99 | 0.71 | 248.28 | 172.59 | 278.67 | 0.00 | 0.00 | 0.00 |
May | 330.33 | 11.01 | 319.33 | 328.97 | 170.36 | 0.00 | 0.00 | 0.00 |
June | 350.32 | 18.82 | 331.49 | 446.45 | 93.27 | 0.00 | 0.00 | 0.00 |
July | 338.55 | 12.24 | 326.30 | 492.37 | 50.85 | 0.00 | 0.00 | 0.00 |
August | 299.94 | 3.57 | 296.37 | 428.39 | 73.10 | 0.00 | 0.00 | 0.00 |
September | 226.10 | 0.04 | 226.06 | 245.14 | 155.18 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 144.26 | 290.78 | 0.00 | 0.00 | 0.00 |
November | 137.25 | 0.00 | 137.25 | 38.46 | 434.74 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.95 | 555.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.47 | 3.89 | 220.58 | 202.42 | 304.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.95 | 50.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.32 | 18.82 | 331.49 | 492.37 | 599.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.00 | 176.00 | 263.00 | 282.90 | 1048.17 | 0.00 | 0.00 | 0.00 |
February | 680.80 | 317.59 | 363.21 | 495.42 | 1055.50 | 0.00 | 0.00 | 0.00 |
March | 868.49 | 369.37 | 499.12 | 786.87 | 748.84 | 0.00 | 0.00 | 0.00 |
April | 1042.25 | 456.54 | 585.71 | 1085.62 | 541.59 | 0.00 | 0.00 | 0.00 |
May | 1264.03 | 505.18 | 758.85 | 1496.88 | 348.44 | 0.00 | 0.00 | 0.00 |
June | 1171.49 | 424.07 | 747.42 | 1553.33 | 191.20 | 0.00 | 0.00 | 0.00 |
July | 1176.62 | 424.61 | 752.01 | 1684.87 | 106.42 | 0.00 | 0.00 | 0.00 |
August | 1324.90 | 597.39 | 727.50 | 1881.49 | 150.82 | 0.00 | 0.00 | 0.00 |
September | 988.12 | 443.33 | 544.79 | 1241.48 | 300.81 | 0.00 | 0.00 | 0.00 |
October | 895.80 | 406.01 | 489.80 | 996.52 | 559.16 | 0.00 | 0.00 | 0.00 |
November | 553.98 | 212.73 | 341.25 | 445.04 | 803.75 | 0.00 | 0.00 | 0.00 |
December | 431.58 | 202.64 | 228.94 | 296.56 | 998.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 904.52 | 378.38 | 526.14 | 1024.23 | 568.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 431.58 | 176.00 | 228.94 | 282.90 | 106.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1324.90 | 597.39 | 758.85 | 1881.49 | 1055.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.96 | 10.40 | 11.19 | 41.44 | 0.00 | 0.00 | 0.00 |
February | 26.92 | 12.56 | 14.36 | 19.59 | 41.73 | 0.00 | 0.00 | 0.00 |
March | 34.34 | 14.60 | 19.73 | 31.11 | 29.61 | 0.00 | 0.00 | 0.00 |
April | 41.21 | 18.05 | 23.16 | 42.92 | 21.41 | 0.00 | 0.00 | 0.00 |
May | 49.98 | 19.97 | 30.00 | 59.19 | 13.78 | 0.00 | 0.00 | 0.00 |
June | 46.32 | 16.77 | 29.55 | 61.42 | 7.56 | 0.00 | 0.00 | 0.00 |
July | 46.52 | 16.79 | 29.73 | 66.62 | 4.21 | 0.00 | 0.00 | 0.00 |
August | 52.39 | 23.62 | 28.76 | 74.39 | 5.96 | 0.00 | 0.00 | 0.00 |
September | 39.07 | 17.53 | 21.54 | 49.09 | 11.89 | 0.00 | 0.00 | 0.00 |
October | 35.42 | 16.05 | 19.37 | 39.40 | 22.11 | 0.00 | 0.00 | 0.00 |
November | 21.90 | 8.41 | 13.49 | 17.60 | 31.78 | 0.00 | 0.00 | 0.00 |
December | 17.06 | 8.01 | 9.05 | 11.73 | 39.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.76 | 14.96 | 20.80 | 40.50 | 22.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.06 | 6.96 | 9.05 | 11.19 | 4.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.39 | 23.62 | 30.00 | 74.39 | 41.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.09 | 370.03 | 195.07 | 576.69 | 526.60 | 0.00 | 0.00 | 0.00 |
February | 745.34 | 493.35 | 251.99 | 770.57 | 539.53 | 0.00 | 0.00 | 0.00 |
March | 672.44 | 373.21 | 299.23 | 737.28 | 395.22 | 0.00 | 0.00 | 0.00 |
April | 521.79 | 206.33 | 315.46 | 592.42 | 293.18 | 0.00 | 0.00 | 0.00 |
May | 457.27 | 95.38 | 361.89 | 554.07 | 183.95 | 0.00 | 0.00 | 0.00 |
June | 429.14 | 65.60 | 363.54 | 591.80 | 101.22 | 0.00 | 0.00 | 0.00 |
July | 449.82 | 78.13 | 371.69 | 682.84 | 54.34 | 0.00 | 0.00 | 0.00 |
August | 600.69 | 222.80 | 377.88 | 913.32 | 82.43 | 0.00 | 0.00 | 0.00 |
September | 651.76 | 337.11 | 314.64 | 877.27 | 166.12 | 0.00 | 0.00 | 0.00 |
October | 892.85 | 559.88 | 332.97 | 1118.98 | 304.83 | 0.00 | 0.00 | 0.00 |
November | 619.11 | 371.81 | 247.31 | 669.60 | 416.95 | 0.00 | 0.00 | 0.00 |
December | 612.48 | 434.82 | 177.66 | 641.65 | 503.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.80 | 299.73 | 301.07 | 727.34 | 295.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.14 | 65.60 | 177.66 | 554.07 | 54.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.85 | 559.88 | 377.88 | 1118.98 | 539.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.09 | 370.03 | 195.07 | 576.69 | 526.60 | 0.00 | 0.00 | 0.00 |
February | 745.34 | 493.35 | 251.99 | 770.57 | 539.53 | 0.00 | 0.00 | 0.00 |
March | 672.44 | 373.21 | 299.23 | 737.28 | 395.22 | 0.00 | 0.00 | 0.00 |
April | 521.79 | 206.33 | 315.46 | 592.42 | 293.18 | 0.00 | 0.00 | 0.00 |
May | 457.27 | 95.38 | 361.89 | 554.07 | 183.95 | 0.00 | 0.00 | 0.00 |
June | 429.14 | 65.60 | 363.54 | 591.80 | 101.22 | 0.00 | 0.00 | 0.00 |
July | 449.82 | 78.13 | 371.69 | 682.84 | 54.34 | 0.00 | 0.00 | 0.00 |
August | 600.69 | 222.80 | 377.88 | 913.32 | 82.43 | 0.00 | 0.00 | 0.00 |
September | 651.76 | 337.11 | 314.64 | 877.27 | 166.12 | 0.00 | 0.00 | 0.00 |
October | 892.85 | 559.88 | 332.97 | 1118.98 | 304.83 | 0.00 | 0.00 | 0.00 |
November | 619.11 | 371.81 | 247.31 | 669.60 | 416.95 | 0.00 | 0.00 | 0.00 |
December | 612.48 | 434.82 | 177.66 | 641.65 | 503.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.80 | 299.73 | 301.07 | 727.34 | 295.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.14 | 65.60 | 177.66 | 554.07 | 54.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.85 | 559.88 | 377.88 | 1118.98 | 539.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.06 | 370.00 | 195.06 | 576.65 | 526.56 | 0.00 | 0.00 | 0.00 |
February | 745.29 | 493.32 | 251.97 | 770.52 | 539.49 | 0.00 | 0.00 | 0.00 |
March | 672.40 | 373.19 | 299.21 | 737.24 | 395.20 | 0.00 | 0.00 | 0.00 |
April | 521.76 | 206.32 | 315.44 | 592.38 | 293.16 | 0.00 | 0.00 | 0.00 |
May | 457.24 | 95.37 | 361.87 | 554.04 | 183.94 | 0.00 | 0.00 | 0.00 |
June | 429.11 | 65.59 | 363.52 | 591.76 | 101.21 | 0.00 | 0.00 | 0.00 |
July | 449.79 | 78.13 | 371.67 | 682.80 | 54.34 | 0.00 | 0.00 | 0.00 |
August | 600.65 | 222.79 | 377.86 | 913.26 | 82.42 | 0.00 | 0.00 | 0.00 |
September | 651.71 | 337.09 | 314.62 | 877.21 | 166.11 | 0.00 | 0.00 | 0.00 |
October | 892.79 | 559.84 | 332.95 | 1118.91 | 304.81 | 0.00 | 0.00 | 0.00 |
November | 619.07 | 371.78 | 247.29 | 669.55 | 416.92 | 0.00 | 0.00 | 0.00 |
December | 612.44 | 434.79 | 177.65 | 641.61 | 503.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.77 | 299.71 | 301.06 | 727.29 | 295.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.11 | 65.59 | 177.65 | 554.04 | 54.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.79 | 559.84 | 377.86 | 1118.91 | 539.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 433.40 | 177.52 | 255.88 | 282.29 | 1070.20 | 0.00 | 0.00 | 0.00 |
February | 639.11 | 280.70 | 358.41 | 461.04 | 1100.95 | 0.00 | 0.00 | 0.00 |
March | 943.72 | 435.69 | 508.03 | 883.69 | 751.05 | 0.00 | 0.00 | 0.00 |
April | 1031.44 | 441.32 | 590.11 | 1087.11 | 559.89 | 0.00 | 0.00 | 0.00 |
May | 1201.52 | 456.29 | 745.23 | 1428.33 | 362.55 | 0.00 | 0.00 | 0.00 |
June | 1315.03 | 530.39 | 784.64 | 1754.52 | 206.11 | 0.00 | 0.00 | 0.00 |
July | 1231.60 | 463.78 | 767.82 | 1761.11 | 115.50 | 0.00 | 0.00 | 0.00 |
August | 1362.48 | 630.74 | 731.74 | 1943.66 | 164.11 | 0.00 | 0.00 | 0.00 |
September | 967.25 | 422.69 | 544.57 | 1228.31 | 315.27 | 0.00 | 0.00 | 0.00 |
October | 958.96 | 466.32 | 492.64 | 1087.35 | 579.35 | 0.00 | 0.00 | 0.00 |
November | 450.32 | 130.15 | 320.18 | 308.96 | 820.28 | 0.00 | 0.00 | 0.00 |
December | 400.55 | 173.32 | 227.23 | 262.64 | 1024.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 913.19 | 384.96 | 528.24 | 1044.92 | 586.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.55 | 130.15 | 227.23 | 262.64 | 115.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1362.48 | 630.74 | 784.64 | 1943.66 | 1100.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.14 | 7.02 | 10.12 | 11.16 | 42.31 | 0.00 | 0.00 | 0.00 |
February | 25.27 | 11.10 | 14.17 | 18.23 | 43.53 | 0.00 | 0.00 | 0.00 |
March | 37.31 | 17.23 | 20.09 | 34.94 | 29.70 | 0.00 | 0.00 | 0.00 |
April | 40.78 | 17.45 | 23.33 | 42.98 | 22.14 | 0.00 | 0.00 | 0.00 |
May | 47.51 | 18.04 | 29.47 | 56.47 | 14.33 | 0.00 | 0.00 | 0.00 |
June | 51.99 | 20.97 | 31.02 | 69.37 | 8.15 | 0.00 | 0.00 | 0.00 |
July | 48.70 | 18.34 | 30.36 | 69.63 | 4.57 | 0.00 | 0.00 | 0.00 |
August | 53.87 | 24.94 | 28.93 | 76.85 | 6.49 | 0.00 | 0.00 | 0.00 |
September | 38.24 | 16.71 | 21.53 | 48.57 | 12.47 | 0.00 | 0.00 | 0.00 |
October | 37.92 | 18.44 | 19.48 | 42.99 | 22.91 | 0.00 | 0.00 | 0.00 |
November | 17.81 | 5.15 | 12.66 | 12.22 | 32.43 | 0.00 | 0.00 | 0.00 |
December | 15.84 | 6.85 | 8.98 | 10.38 | 40.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.11 | 15.22 | 20.89 | 41.32 | 23.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.84 | 5.15 | 8.98 | 10.38 | 4.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.87 | 24.94 | 31.02 | 76.85 | 43.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.71 | 0.00 | 327.71 | 24.50 | 1753.56 | 0.00 | 0.00 | 0.00 |
February | 448.46 | 0.00 | 448.46 | 45.85 | 1831.33 | 0.00 | 0.00 | 0.00 |
March | 621.90 | 0.00 | 621.90 | 234.61 | 1230.73 | 0.00 | 0.00 | 0.00 |
April | 746.98 | 2.12 | 744.86 | 479.38 | 889.75 | 0.00 | 0.00 | 0.00 |
May | 991.01 | 33.02 | 957.99 | 936.25 | 553.40 | 0.00 | 0.00 | 0.00 |
June | 1050.95 | 56.47 | 994.48 | 1311.80 | 299.53 | 0.00 | 0.00 | 0.00 |
July | 1015.65 | 36.73 | 978.92 | 1455.95 | 166.46 | 0.00 | 0.00 | 0.00 |
August | 899.81 | 10.71 | 889.10 | 1274.37 | 227.07 | 0.00 | 0.00 | 0.00 |
September | 678.31 | 0.13 | 678.18 | 730.03 | 464.96 | 0.00 | 0.00 | 0.00 |
October | 587.03 | 0.00 | 587.03 | 431.45 | 857.77 | 0.00 | 0.00 | 0.00 |
November | 411.74 | 0.00 | 411.74 | 116.72 | 1271.36 | 0.00 | 0.00 | 0.00 |
December | 285.85 | 0.00 | 285.85 | 14.52 | 1650.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.41 | 11.66 | 661.75 | 591.62 | 927.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.85 | 0.00 | 285.85 | 14.52 | 166.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1050.95 | 56.47 | 994.48 | 1455.95 | 1831.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.37 | 182.97 | 273.40 | 287.77 | 1088.58 | 0.00 | 0.00 | 0.00 |
February | 707.73 | 330.16 | 377.57 | 502.57 | 1103.96 | 0.00 | 0.00 | 0.00 |
March | 902.84 | 383.99 | 518.86 | 794.39 | 796.98 | 0.00 | 0.00 | 0.00 |
April | 1083.48 | 474.60 | 608.88 | 1102.94 | 579.44 | 0.00 | 0.00 | 0.00 |
May | 1314.03 | 525.17 | 788.86 | 1525.97 | 378.41 | 0.00 | 0.00 | 0.00 |
June | 1217.83 | 440.84 | 776.98 | 1595.43 | 205.38 | 0.00 | 0.00 | 0.00 |
July | 1223.16 | 441.41 | 781.75 | 1736.77 | 113.66 | 0.00 | 0.00 | 0.00 |
August | 1377.31 | 621.03 | 756.28 | 1946.09 | 153.30 | 0.00 | 0.00 | 0.00 |
September | 1027.20 | 460.87 | 566.34 | 1283.47 | 302.81 | 0.00 | 0.00 | 0.00 |
October | 931.23 | 422.07 | 509.17 | 1032.51 | 557.23 | 0.00 | 0.00 | 0.00 |
November | 575.90 | 221.15 | 354.75 | 463.26 | 801.96 | 0.00 | 0.00 | 0.00 |
December | 448.66 | 210.66 | 237.99 | 305.68 | 1018.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 940.30 | 393.35 | 546.95 | 1051.86 | 588.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 448.66 | 182.97 | 237.99 | 287.77 | 113.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.31 | 621.03 | 788.86 | 1946.09 | 1103.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1695.32 | 1110.10 | 585.21 | 1690.52 | 1577.86 | 0.00 | 0.00 | 0.00 |
February | 2236.06 | 1480.09 | 755.97 | 2261.72 | 1611.36 | 0.00 | 0.00 | 0.00 |
March | 2017.35 | 1119.66 | 897.69 | 2160.25 | 1205.46 | 0.00 | 0.00 | 0.00 |
April | 1565.39 | 619.00 | 946.39 | 1728.82 | 919.07 | 0.00 | 0.00 | 0.00 |
May | 1371.84 | 286.14 | 1085.69 | 1605.82 | 596.11 | 0.00 | 0.00 | 0.00 |
June | 1287.43 | 196.80 | 1090.63 | 1745.56 | 321.44 | 0.00 | 0.00 | 0.00 |
July | 1349.48 | 234.40 | 1115.08 | 2029.34 | 171.81 | 0.00 | 0.00 | 0.00 |
August | 1802.08 | 668.42 | 1133.66 | 2730.08 | 241.34 | 0.00 | 0.00 | 0.00 |
September | 1955.30 | 1011.36 | 943.94 | 2622.48 | 476.84 | 0.00 | 0.00 | 0.00 |
October | 2678.59 | 1679.67 | 998.92 | 3346.18 | 857.66 | 0.00 | 0.00 | 0.00 |
November | 1857.37 | 1115.44 | 741.93 | 1992.47 | 1198.84 | 0.00 | 0.00 | 0.00 |
December | 1837.47 | 1304.48 | 532.99 | 1900.52 | 1471.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1802.44 | 899.21 | 903.23 | 2151.65 | 883.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1287.43 | 196.80 | 532.99 | 1605.82 | 171.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2678.59 | 1679.67 | 1133.66 | 3346.18 | 1611.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.54 | 184.54 | 266.00 | 286.39 | 1114.08 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 291.80 | 372.58 | 466.32 | 1152.56 | 0.00 | 0.00 | 0.00 |
March | 981.04 | 452.92 | 528.12 | 897.62 | 794.43 | 0.00 | 0.00 | 0.00 |
April | 1072.24 | 458.78 | 613.45 | 1106.53 | 598.01 | 0.00 | 0.00 | 0.00 |
May | 1249.05 | 474.34 | 774.71 | 1458.53 | 392.58 | 0.00 | 0.00 | 0.00 |
June | 1367.04 | 551.37 | 815.68 | 1808.24 | 217.58 | 0.00 | 0.00 | 0.00 |
July | 1280.31 | 482.12 | 798.18 | 1818.98 | 121.22 | 0.00 | 0.00 | 0.00 |
August | 1416.37 | 655.69 | 760.68 | 2014.23 | 165.15 | 0.00 | 0.00 | 0.00 |
September | 1005.51 | 439.41 | 566.10 | 1273.52 | 317.44 | 0.00 | 0.00 | 0.00 |
October | 996.89 | 484.76 | 512.13 | 1129.65 | 575.33 | 0.00 | 0.00 | 0.00 |
November | 468.13 | 135.29 | 332.84 | 321.72 | 823.34 | 0.00 | 0.00 | 0.00 |
December | 416.40 | 180.18 | 236.22 | 269.66 | 1047.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.31 | 400.18 | 549.13 | 1075.30 | 606.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.40 | 135.29 | 236.22 | 269.66 | 121.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1416.37 | 655.69 | 815.68 | 2014.23 | 1152.56 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.877739E+09 | 0.00 | 0.877739E+09 | 73126662.21 | 0.452026E+10 |
February | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.121433E+09 | 0.424461E+10 |
March | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.653186E+09 | 0.312040E+10 |
April | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.127148E+10 | 0.217612E+10 |
May | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.251882E+10 | 0.142734E+10 |
June | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.338861E+10 | 0.754984E+09 |
July | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.387726E+10 | 0.439499E+09 |
August | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.340023E+10 | 0.591289E+09 |
September | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.189862E+10 | 0.114793E+10 |
October | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.119586E+10 | 0.214758E+10 |
November | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.341721E+09 | 0.306243E+10 |
December | 0.765622E+09 | 0.00 | 0.765622E+09 | 49226267.42 | 0.417203E+10 |
Annual Sum or Average | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.187896E+11 | 0.278045E+11 |
Minimum of Months | 0.765622E+09 | 0.00 | 0.765622E+09 | 49226267.42 | 0.439499E+09 |
Maximum of Months | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.387726E+10 | 0.452026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.785466E+09 | 0.280529E+10 |
February | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.124174E+10 | 0.255386E+10 |
March | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.215763E+10 | 0.201950E+10 |
April | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.288550E+10 | 0.142252E+10 |
May | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.409808E+10 | 0.978279E+09 |
June | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.413471E+10 | 0.517682E+09 |
July | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.464487E+10 | 0.299044E+09 |
August | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.520997E+10 | 0.399018E+09 |
September | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.333689E+10 | 0.750065E+09 |
October | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.279634E+10 | 0.140269E+10 |
November | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.124282E+10 | 0.193413E+10 |
December | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.845208E+09 | 0.256899E+10 |
Annual Sum or Average | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.333792E+11 | 0.176511E+11 |
Minimum of Months | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.785466E+09 | 0.299044E+09 |
Maximum of Months | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.520997E+10 | 0.280529E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.455247E+10 | 0.405025E+10 |
February | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.550936E+10 | 0.371992E+10 |
March | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.581323E+10 | 0.305618E+10 |
April | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.450333E+10 | 0.225466E+10 |
May | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.430352E+10 | 0.153668E+10 |
June | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.450930E+10 | 0.809221E+09 |
July | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.541084E+10 | 0.452249E+09 |
August | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.729252E+10 | 0.628145E+09 |
September | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.679688E+10 | 0.118266E+10 |
October | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.898588E+10 | 0.216664E+10 |
November | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.522116E+10 | 0.289892E+10 |
December | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.513902E+10 | 0.371293E+10 |
Annual Sum or Average | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.680375E+11 | 0.264685E+11 |
Minimum of Months | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.430352E+10 | 0.452249E+09 |
Maximum of Months | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.898588E+10 | 0.405025E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.774894E+09 | 0.286877E+10 |
February | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.113887E+10 | 0.266814E+10 |
March | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.242154E+10 | 0.201258E+10 |
April | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.288465E+10 | 0.146351E+10 |
May | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.390851E+10 | 0.101109E+10 |
June | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.467501E+10 | 0.547180E+09 |
July | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.485463E+10 | 0.318515E+09 |
August | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.538200E+10 | 0.429922E+09 |
September | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.330246E+10 | 0.785818E+09 |
October | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.304812E+10 | 0.144538E+10 |
November | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.864456E+09 | 0.198533E+10 |
December | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.737333E+09 | 0.264516E+10 |
Annual Sum or Average | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.339925E+11 | 0.181814E+11 |
Minimum of Months | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.737333E+09 | 0.318515E+09 |
Maximum of Months | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.538200E+10 | 0.286877E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292566E+09 | 0.00 | 0.292566E+09 | 23856239.90 | 0.155507E+10 |
February | 0.361619E+09 | 0.00 | 0.361619E+09 | 41544318.14 | 0.145063E+10 |
March | 0.555204E+09 | 0.00 | 0.555204E+09 | 0.231528E+09 | 0.105347E+10 |
April | 0.645364E+09 | 1835613.72 | 0.643528E+09 | 0.447340E+09 | 0.722266E+09 |
May | 0.884732E+09 | 29479770.21 | 0.855252E+09 | 0.881084E+09 | 0.456260E+09 |
June | 0.907981E+09 | 48789636.46 | 0.859192E+09 | 0.115716E+10 | 0.241731E+09 |
July | 0.906725E+09 | 32790217.14 | 0.873935E+09 | 0.131871E+10 | 0.136190E+09 |
August | 0.803315E+09 | 9560583.93 | 0.793755E+09 | 0.114734E+10 | 0.195791E+09 |
September | 0.586032E+09 | 109739.98 | 0.585922E+09 | 0.635371E+09 | 0.402203E+09 |
October | 0.524074E+09 | 0.00 | 0.524074E+09 | 0.386364E+09 | 0.778785E+09 |
November | 0.355730E+09 | 0.00 | 0.355730E+09 | 99684869.42 | 0.112677E+10 |
December | 0.255195E+09 | 0.00 | 0.255195E+09 | 13264368.72 | 0.148681E+10 |
Annual Sum or Average | 0.707854E+10 | 0.122566E+09 | 0.695597E+10 | 0.638325E+10 | 0.960598E+10 |
Minimum of Months | 0.255195E+09 | 0.00 | 0.255195E+09 | 13264368.72 | 0.136190E+09 |
Maximum of Months | 0.907981E+09 | 48789636.46 | 0.873935E+09 | 0.131871E+10 | 0.155507E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292577E+09 | 0.00 | 0.292577E+09 | 23854858.93 | 0.155517E+10 |
February | 0.361633E+09 | 0.00 | 0.361633E+09 | 41543402.52 | 0.145072E+10 |
March | 0.555226E+09 | 0.00 | 0.555226E+09 | 0.231531E+09 | 0.105354E+10 |
April | 0.645390E+09 | 1835663.06 | 0.643554E+09 | 0.447353E+09 | 0.722312E+09 |
May | 0.884767E+09 | 29480562.63 | 0.855286E+09 | 0.881112E+09 | 0.456287E+09 |
June | 0.908017E+09 | 48790947.93 | 0.859226E+09 | 0.115721E+10 | 0.241744E+09 |
July | 0.906761E+09 | 32791098.55 | 0.873970E+09 | 0.131876E+10 | 0.136196E+09 |
August | 0.803349E+09 | 9560840.92 | 0.793788E+09 | 0.114739E+10 | 0.195800E+09 |
September | 0.586056E+09 | 109742.93 | 0.585946E+09 | 0.635395E+09 | 0.402226E+09 |
October | 0.524095E+09 | 0.00 | 0.524095E+09 | 0.386375E+09 | 0.778831E+09 |
November | 0.355744E+09 | 0.00 | 0.355744E+09 | 99684436.35 | 0.112684E+10 |
December | 0.255205E+09 | 0.00 | 0.255205E+09 | 13263587.14 | 0.148691E+10 |
Annual Sum or Average | 0.707882E+10 | 0.122569E+09 | 0.695625E+10 | 0.638348E+10 | 0.960658E+10 |
Minimum of Months | 0.255205E+09 | 0.00 | 0.255205E+09 | 13263587.14 | 0.136196E+09 |
Maximum of Months | 0.908017E+09 | 48790947.93 | 0.873970E+09 | 0.131876E+10 | 0.155517E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292577E+09 | 0.00 | 0.292577E+09 | 23854858.93 | 0.155517E+10 |
February | 0.361633E+09 | 0.00 | 0.361633E+09 | 41543402.52 | 0.145072E+10 |
March | 0.555226E+09 | 0.00 | 0.555226E+09 | 0.231531E+09 | 0.105354E+10 |
April | 0.645390E+09 | 1835663.06 | 0.643554E+09 | 0.447353E+09 | 0.722312E+09 |
May | 0.884767E+09 | 29480562.63 | 0.855286E+09 | 0.881112E+09 | 0.456287E+09 |
June | 0.908017E+09 | 48790947.93 | 0.859226E+09 | 0.115721E+10 | 0.241744E+09 |
July | 0.906761E+09 | 32791098.55 | 0.873970E+09 | 0.131876E+10 | 0.136196E+09 |
August | 0.803349E+09 | 9560840.92 | 0.793788E+09 | 0.114739E+10 | 0.195800E+09 |
September | 0.586056E+09 | 109742.93 | 0.585946E+09 | 0.635395E+09 | 0.402226E+09 |
October | 0.524095E+09 | 0.00 | 0.524095E+09 | 0.386375E+09 | 0.778831E+09 |
November | 0.355744E+09 | 0.00 | 0.355744E+09 | 99684436.35 | 0.112684E+10 |
December | 0.255205E+09 | 0.00 | 0.255205E+09 | 13263587.14 | 0.148691E+10 |
Annual Sum or Average | 0.707882E+10 | 0.122569E+09 | 0.695625E+10 | 0.638348E+10 | 0.960658E+10 |
Minimum of Months | 0.255205E+09 | 0.00 | 0.255205E+09 | 13263587.14 | 0.136196E+09 |
Maximum of Months | 0.908017E+09 | 48790947.93 | 0.873970E+09 | 0.131876E+10 | 0.155517E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117583E+10 | 0.471411E+09 | 0.704419E+09 | 0.757718E+09 | 0.280741E+10 |
February | 0.164699E+10 | 0.768321E+09 | 0.878673E+09 | 0.119851E+10 | 0.255346E+10 |
March | 0.232617E+10 | 0.989331E+09 | 0.133684E+10 | 0.210755E+10 | 0.200570E+10 |
April | 0.270151E+10 | 0.118334E+10 | 0.151817E+10 | 0.281393E+10 | 0.140379E+10 |
May | 0.338558E+10 | 0.135308E+10 | 0.203250E+10 | 0.400924E+10 | 0.933267E+09 |
June | 0.303650E+10 | 0.109919E+10 | 0.193731E+10 | 0.402622E+10 | 0.495583E+09 |
July | 0.315145E+10 | 0.113728E+10 | 0.201418E+10 | 0.451275E+10 | 0.285044E+09 |
August | 0.354861E+10 | 0.160006E+10 | 0.194855E+10 | 0.503938E+10 | 0.403946E+09 |
September | 0.256120E+10 | 0.114910E+10 | 0.141209E+10 | 0.321791E+10 | 0.779690E+09 |
October | 0.239931E+10 | 0.108745E+10 | 0.131187E+10 | 0.266909E+10 | 0.149767E+10 |
November | 0.143592E+10 | 0.551408E+09 | 0.884517E+09 | 0.115353E+10 | 0.208333E+10 |
December | 0.115596E+10 | 0.542764E+09 | 0.613192E+09 | 0.794296E+09 | 0.267380E+10 |
Annual Sum or Average | 0.285250E+11 | 0.119327E+11 | 0.165923E+11 | 0.323001E+11 | 0.179227E+11 |
Minimum of Months | 0.115596E+10 | 0.471411E+09 | 0.613192E+09 | 0.757718E+09 | 0.285044E+09 |
Maximum of Months | 0.354861E+10 | 0.160006E+10 | 0.203250E+10 | 0.503938E+10 | 0.280741E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46491248.53 | 18639173.47 | 27852075.06 | 29959482.41 | 0.111002E+09 |
February | 65120688.91 | 30378734.06 | 34741954.85 | 47388066.39 | 0.100962E+09 |
March | 91974516.67 | 39117249.61 | 52857267.06 | 83330439.64 | 79303507.10 |
April | 0.106815E+09 | 46788213.91 | 60027079.77 | 0.111260E+09 | 55504540.66 |
May | 0.133863E+09 | 53499380.13 | 80363332.10 | 0.158522E+09 | 36900553.39 |
June | 0.120060E+09 | 43460819.36 | 76599620.23 | 0.159193E+09 | 19594922.95 |
July | 0.124606E+09 | 44966859.13 | 79638710.84 | 0.178430E+09 | 11270373.18 |
August | 0.140309E+09 | 63265002.36 | 77043847.34 | 0.199253E+09 | 15971653.87 |
September | 0.101267E+09 | 45434569.04 | 55832907.16 | 0.127233E+09 | 30828254.01 |
October | 94866683.40 | 42996643.49 | 51870039.91 | 0.105533E+09 | 59216359.31 |
November | 56775167.18 | 21802171.41 | 34972995.77 | 45609623.72 | 82372985.54 |
December | 45705453.17 | 21460412.81 | 24245040.36 | 31405759.74 | 0.105720E+09 |
Annual Sum or Average | 0.112785E+10 | 0.471809E+09 | 0.656045E+09 | 0.127712E+10 | 0.708647E+09 |
Minimum of Months | 45705453.17 | 18639173.47 | 24245040.36 | 29959482.41 | 11270373.18 |
Maximum of Months | 0.140309E+09 | 63265002.36 | 80363332.10 | 0.199253E+09 | 0.111002E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151355E+10 | 0.991081E+09 | 0.522470E+09 | 0.154461E+10 | 0.141043E+10 |
February | 0.180313E+10 | 0.119352E+10 | 0.609607E+09 | 0.186416E+10 | 0.130523E+10 |
March | 0.180106E+10 | 0.999616E+09 | 0.801445E+09 | 0.197474E+10 | 0.105857E+10 |
April | 0.135248E+10 | 0.534808E+09 | 0.817672E+09 | 0.153555E+10 | 0.759929E+09 |
May | 0.122476E+10 | 0.255463E+09 | 0.969297E+09 | 0.148402E+10 | 0.492702E+09 |
June | 0.111232E+10 | 0.170029E+09 | 0.942296E+09 | 0.153395E+10 | 0.262355E+09 |
July | 0.120480E+10 | 0.209272E+09 | 0.995531E+09 | 0.182893E+10 | 0.145540E+09 |
August | 0.160888E+10 | 0.596755E+09 | 0.101212E+10 | 0.244623E+10 | 0.220768E+09 |
September | 0.168935E+10 | 0.873796E+09 | 0.815553E+09 | 0.227388E+10 | 0.430586E+09 |
October | 0.239140E+10 | 0.149958E+10 | 0.891826E+09 | 0.299708E+10 | 0.816447E+09 |
November | 0.160474E+10 | 0.963721E+09 | 0.641020E+09 | 0.173559E+10 | 0.108073E+10 |
December | 0.164046E+10 | 0.116462E+10 | 0.475845E+09 | 0.171861E+10 | 0.134929E+10 |
Annual Sum or Average | 0.189469E+11 | 0.945226E+10 | 0.949469E+10 | 0.229373E+11 | 0.933257E+10 |
Minimum of Months | 0.111232E+10 | 0.170029E+09 | 0.475845E+09 | 0.148402E+10 | 0.145540E+09 |
Maximum of Months | 0.239140E+10 | 0.149958E+10 | 0.101212E+10 | 0.299708E+10 | 0.141043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151355E+10 | 0.991081E+09 | 0.522470E+09 | 0.154461E+10 | 0.141043E+10 |
February | 0.180313E+10 | 0.119352E+10 | 0.609607E+09 | 0.186416E+10 | 0.130523E+10 |
March | 0.180106E+10 | 0.999616E+09 | 0.801445E+09 | 0.197474E+10 | 0.105857E+10 |
April | 0.135248E+10 | 0.534808E+09 | 0.817672E+09 | 0.153555E+10 | 0.759929E+09 |
May | 0.122476E+10 | 0.255463E+09 | 0.969297E+09 | 0.148402E+10 | 0.492702E+09 |
June | 0.111232E+10 | 0.170029E+09 | 0.942296E+09 | 0.153395E+10 | 0.262355E+09 |
July | 0.120480E+10 | 0.209272E+09 | 0.995531E+09 | 0.182893E+10 | 0.145540E+09 |
August | 0.160888E+10 | 0.596755E+09 | 0.101212E+10 | 0.244623E+10 | 0.220768E+09 |
September | 0.168935E+10 | 0.873796E+09 | 0.815553E+09 | 0.227388E+10 | 0.430586E+09 |
October | 0.239140E+10 | 0.149958E+10 | 0.891826E+09 | 0.299708E+10 | 0.816447E+09 |
November | 0.160474E+10 | 0.963721E+09 | 0.641020E+09 | 0.173559E+10 | 0.108073E+10 |
December | 0.164046E+10 | 0.116462E+10 | 0.475845E+09 | 0.171861E+10 | 0.134929E+10 |
Annual Sum or Average | 0.189469E+11 | 0.945226E+10 | 0.949469E+10 | 0.229373E+11 | 0.933257E+10 |
Minimum of Months | 0.111232E+10 | 0.170029E+09 | 0.475845E+09 | 0.148402E+10 | 0.145540E+09 |
Maximum of Months | 0.239140E+10 | 0.149958E+10 | 0.101212E+10 | 0.299708E+10 | 0.141043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151345E+10 | 0.991018E+09 | 0.522437E+09 | 0.154451E+10 | 0.141034E+10 |
February | 0.180302E+10 | 0.119345E+10 | 0.609569E+09 | 0.186404E+10 | 0.130514E+10 |
March | 0.180095E+10 | 0.999553E+09 | 0.801394E+09 | 0.197461E+10 | 0.105850E+10 |
April | 0.135240E+10 | 0.534774E+09 | 0.817621E+09 | 0.153545E+10 | 0.759881E+09 |
May | 0.122468E+10 | 0.255447E+09 | 0.969236E+09 | 0.148393E+10 | 0.492671E+09 |
June | 0.111225E+10 | 0.170018E+09 | 0.942237E+09 | 0.153385E+10 | 0.262338E+09 |
July | 0.120473E+10 | 0.209259E+09 | 0.995468E+09 | 0.182881E+10 | 0.145531E+09 |
August | 0.160878E+10 | 0.596718E+09 | 0.101206E+10 | 0.244608E+10 | 0.220754E+09 |
September | 0.168924E+10 | 0.873741E+09 | 0.815501E+09 | 0.227373E+10 | 0.430559E+09 |
October | 0.239125E+10 | 0.149948E+10 | 0.891770E+09 | 0.299689E+10 | 0.816396E+09 |
November | 0.160464E+10 | 0.963660E+09 | 0.640979E+09 | 0.173548E+10 | 0.108066E+10 |
December | 0.164036E+10 | 0.116454E+10 | 0.475815E+09 | 0.171850E+10 | 0.134920E+10 |
Annual Sum or Average | 0.189457E+11 | 0.945166E+10 | 0.949409E+10 | 0.229359E+11 | 0.933199E+10 |
Minimum of Months | 0.111225E+10 | 0.170018E+09 | 0.475815E+09 | 0.148393E+10 | 0.145531E+09 |
Maximum of Months | 0.239125E+10 | 0.149948E+10 | 0.101206E+10 | 0.299689E+10 | 0.141034E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116081E+10 | 0.475470E+09 | 0.685340E+09 | 0.756075E+09 | 0.286643E+10 |
February | 0.154612E+10 | 0.679061E+09 | 0.867062E+09 | 0.111535E+10 | 0.266342E+10 |
March | 0.252765E+10 | 0.116694E+10 | 0.136071E+10 | 0.236687E+10 | 0.201160E+10 |
April | 0.267349E+10 | 0.114391E+10 | 0.152958E+10 | 0.281778E+10 | 0.145122E+10 |
May | 0.321816E+10 | 0.122213E+10 | 0.199603E+10 | 0.382564E+10 | 0.971045E+09 |
June | 0.340856E+10 | 0.137476E+10 | 0.203379E+10 | 0.454773E+10 | 0.534232E+09 |
July | 0.329871E+10 | 0.124219E+10 | 0.205652E+10 | 0.471695E+10 | 0.309351E+09 |
August | 0.364927E+10 | 0.168936E+10 | 0.195990E+10 | 0.520591E+10 | 0.439552E+09 |
September | 0.250712E+10 | 0.109560E+10 | 0.141152E+10 | 0.318377E+10 | 0.817192E+09 |
October | 0.256847E+10 | 0.124898E+10 | 0.131949E+10 | 0.291235E+10 | 0.155174E+10 |
November | 0.116724E+10 | 0.337339E+09 | 0.829900E+09 | 0.800825E+09 | 0.212617E+10 |
December | 0.107284E+10 | 0.464221E+09 | 0.608622E+09 | 0.703467E+09 | 0.274494E+10 |
Annual Sum or Average | 0.287984E+11 | 0.121400E+11 | 0.166585E+11 | 0.329527E+11 | 0.184869E+11 |
Minimum of Months | 0.107284E+10 | 0.337339E+09 | 0.608622E+09 | 0.703467E+09 | 0.309351E+09 |
Maximum of Months | 0.364927E+10 | 0.168936E+10 | 0.205652E+10 | 0.520591E+10 | 0.286643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45897219.76 | 18799578.49 | 27097641.27 | 29894402.05 | 0.113336E+09 |
February | 61132159.56 | 26849383.05 | 34282776.51 | 44099674.25 | 0.105309E+09 |
March | 99940809.17 | 46139769.68 | 53801039.48 | 93583667.48 | 79537025.13 |
April | 0.105707E+09 | 45229190.01 | 60477938.52 | 0.111412E+09 | 57380058.95 |
May | 0.127243E+09 | 48321638.08 | 78921059.36 | 0.151262E+09 | 38394245.32 |
June | 0.134771E+09 | 54356766.41 | 80414196.70 | 0.179812E+09 | 21123033.15 |
July | 0.130428E+09 | 49114806.49 | 81312788.21 | 0.186503E+09 | 12231438.00 |
August | 0.144288E+09 | 66795753.60 | 77492599.82 | 0.205837E+09 | 17379454.80 |
September | 99128965.29 | 43318956.13 | 55810009.16 | 0.125883E+09 | 32311011.30 |
October | 0.101555E+09 | 49383479.05 | 52171383.98 | 0.115151E+09 | 61354494.11 |
November | 46151441.29 | 13338037.77 | 32813403.52 | 31663776.16 | 84066664.82 |
December | 42419103.52 | 18354807.59 | 24064295.94 | 27814318.55 | 0.108532E+09 |
Annual Sum or Average | 0.113866E+10 | 0.480002E+09 | 0.658659E+09 | 0.130292E+10 | 0.730955E+09 |
Minimum of Months | 42419103.52 | 13338037.77 | 24064295.94 | 27814318.55 | 12231438.00 |
Maximum of Months | 0.144288E+09 | 66795753.60 | 81312788.21 | 0.205837E+09 | 0.113336E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.877739E+09 | 0.00 | 0.877739E+09 | 65611954.77 | 0.469675E+10 |
February | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.110929E+09 | 0.443035E+10 |
March | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.628383E+09 | 0.329638E+10 |
April | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.124255E+10 | 0.230624E+10 |
May | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.250765E+10 | 0.148222E+10 |
June | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.340020E+10 | 0.776383E+09 |
July | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.389960E+10 | 0.445846E+09 |
August | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.341326E+10 | 0.608192E+09 |
September | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.189225E+10 | 0.120517E+10 |
October | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.115559E+10 | 0.229745E+10 |
November | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.302549E+09 | 0.329538E+10 |
December | 0.765622E+09 | 0.00 | 0.765622E+09 | 38882493.45 | 0.442141E+10 |
Annual Sum or Average | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.186575E+11 | 0.292618E+11 |
Minimum of Months | 0.765622E+09 | 0.00 | 0.765622E+09 | 38882493.45 | 0.445846E+09 |
Maximum of Months | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.389960E+10 | 0.469675E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.770767E+09 | 0.291566E+10 |
February | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.121582E+10 | 0.267070E+10 |
March | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.212770E+10 | 0.213463E+10 |
April | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.285881E+10 | 0.150192E+10 |
May | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.408717E+10 | 0.101353E+10 |
June | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.413535E+10 | 0.532352E+09 |
July | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.465176E+10 | 0.304414E+09 |
August | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.521240E+10 | 0.410587E+09 |
September | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.332675E+10 | 0.784873E+09 |
October | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.276547E+10 | 0.149248E+10 |
November | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.120077E+10 | 0.207867E+10 |
December | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.818737E+09 | 0.272750E+10 |
Annual Sum or Average | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.331715E+11 | 0.185673E+11 |
Minimum of Months | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.770767E+09 | 0.304414E+09 |
Maximum of Months | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.521240E+10 | 0.291566E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.452788E+10 | 0.422614E+10 |
February | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.547156E+10 | 0.389820E+10 |
March | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.578601E+10 | 0.322870E+10 |
April | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.448110E+10 | 0.238222E+10 |
May | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.430103E+10 | 0.159663E+10 |
June | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.452450E+10 | 0.833172E+09 |
July | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.543537E+10 | 0.460178E+09 |
August | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.731225E+10 | 0.646416E+09 |
September | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.679747E+10 | 0.123598E+10 |
October | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.896241E+10 | 0.229715E+10 |
November | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.516449E+10 | 0.310739E+10 |
December | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.509036E+10 | 0.394162E+10 |
Annual Sum or Average | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.678544E+11 | 0.278538E+11 |
Minimum of Months | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.430103E+10 | 0.460178E+09 |
Maximum of Months | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.896241E+10 | 0.422614E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.767058E+09 | 0.298396E+10 |
February | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.112812E+10 | 0.278828E+10 |
March | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.240417E+10 | 0.212779E+10 |
April | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.286812E+10 | 0.155003E+10 |
May | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.390652E+10 | 0.105148E+10 |
June | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.468695E+10 | 0.563959E+09 |
July | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.487194E+10 | 0.324679E+09 |
August | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.539491E+10 | 0.442350E+09 |
September | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.330097E+10 | 0.822793E+09 |
October | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.302566E+10 | 0.154096E+10 |
November | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.833888E+09 | 0.213409E+10 |
December | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.722246E+09 | 0.280657E+10 |
Annual Sum or Average | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.339105E+11 | 0.191369E+11 |
Minimum of Months | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.722246E+09 | 0.324679E+09 |
Maximum of Months | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.539491E+10 | 0.298396E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.30 | 1687.67 | 327.71 | 0.00 | 327.71 | 0.00 | 0.00 |
February | 50.20 | 1754.55 | 448.46 | 0.00 | 448.46 | 0.00 | 0.00 |
March | 243.87 | 1165.03 | 621.90 | 0.00 | 621.90 | 0.00 | 0.00 |
April | 490.54 | 839.55 | 746.98 | 2.12 | 744.86 | 0.00 | 0.00 |
May | 940.42 | 532.91 | 991.01 | 33.02 | 957.99 | 0.00 | 0.00 |
June | 1307.33 | 291.27 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
July | 1447.60 | 164.09 | 1015.65 | 36.73 | 978.92 | 0.00 | 0.00 |
August | 1269.50 | 220.76 | 899.81 | 10.71 | 889.10 | 0.00 | 0.00 |
September | 732.49 | 442.87 | 678.31 | 0.13 | 678.18 | 0.00 | 0.00 |
October | 446.48 | 801.82 | 587.03 | 0.00 | 587.03 | 0.00 | 0.00 |
November | 131.84 | 1181.49 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 18.38 | 1557.66 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Annual Sum or Average | 595.81 | 881.67 | 673.41 | 11.66 | 661.75 | 0.00 | 0.00 |
Minimum of Months | 18.38 | 164.09 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Maximum of Months | 1447.60 | 1754.55 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.26 | 1047.38 | 456.37 | 182.97 | 273.40 | 0.00 | 0.00 |
February | 513.28 | 1055.66 | 707.73 | 330.16 | 377.57 | 0.00 | 0.00 |
March | 805.57 | 754.00 | 902.84 | 383.99 | 518.86 | 0.00 | 0.00 |
April | 1113.23 | 548.81 | 1083.48 | 474.60 | 608.88 | 0.00 | 0.00 |
May | 1530.05 | 365.25 | 1314.03 | 525.17 | 788.86 | 0.00 | 0.00 |
June | 1595.18 | 199.72 | 1217.83 | 440.84 | 776.98 | 0.00 | 0.00 |
July | 1734.20 | 111.65 | 1223.16 | 441.41 | 781.75 | 0.00 | 0.00 |
August | 1945.18 | 148.98 | 1377.31 | 621.03 | 756.28 | 0.00 | 0.00 |
September | 1287.38 | 289.38 | 1027.20 | 460.87 | 566.34 | 0.00 | 0.00 |
October | 1044.03 | 523.70 | 931.23 | 422.07 | 509.17 | 0.00 | 0.00 |
November | 479.48 | 746.19 | 575.90 | 221.15 | 354.75 | 0.00 | 0.00 |
December | 315.56 | 959.15 | 448.66 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1058.45 | 559.71 | 940.30 | 393.35 | 546.95 | 0.00 | 0.00 |
Minimum of Months | 293.26 | 111.65 | 448.66 | 182.97 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1945.18 | 1055.66 | 1377.31 | 621.03 | 788.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1699.70 | 1512.19 | 1695.32 | 1110.10 | 585.21 | 0.00 | 0.00 |
February | 2277.35 | 1537.67 | 2236.06 | 1480.09 | 755.97 | 0.00 | 0.00 |
March | 2170.41 | 1141.05 | 2017.35 | 1119.66 | 897.69 | 0.00 | 0.00 |
April | 1737.40 | 869.85 | 1565.39 | 619.00 | 946.39 | 0.00 | 0.00 |
May | 1606.75 | 573.73 | 1371.84 | 286.14 | 1085.69 | 0.00 | 0.00 |
June | 1739.70 | 312.20 | 1287.43 | 196.80 | 1090.63 | 0.00 | 0.00 |
July | 2020.18 | 168.85 | 1349.48 | 234.40 | 1115.08 | 0.00 | 0.00 |
August | 2722.71 | 234.52 | 1802.08 | 668.42 | 1133.66 | 0.00 | 0.00 |
September | 2622.25 | 456.27 | 1955.30 | 1011.36 | 943.94 | 0.00 | 0.00 |
October | 3354.94 | 808.93 | 2678.59 | 1679.67 | 998.92 | 0.00 | 0.00 |
November | 2014.34 | 1118.41 | 1857.37 | 1115.44 | 741.93 | 0.00 | 0.00 |
December | 1918.69 | 1386.25 | 1837.47 | 1304.48 | 532.99 | 0.00 | 0.00 |
Annual Sum or Average | 2157.46 | 839.31 | 1802.44 | 899.21 | 903.23 | 0.00 | 0.00 |
Minimum of Months | 1606.75 | 168.85 | 1287.43 | 196.80 | 532.99 | 0.00 | 0.00 |
Maximum of Months | 3354.94 | 1537.67 | 2678.59 | 1679.67 | 1133.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 289.31 | 1071.08 | 450.54 | 184.54 | 266.00 | 0.00 | 0.00 |
February | 470.76 | 1102.90 | 664.38 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 904.10 | 751.41 | 981.04 | 452.92 | 528.12 | 0.00 | 0.00 |
April | 1112.90 | 564.63 | 1072.24 | 458.78 | 613.45 | 0.00 | 0.00 |
May | 1459.27 | 377.50 | 1249.05 | 474.34 | 774.71 | 0.00 | 0.00 |
June | 1803.63 | 211.10 | 1367.04 | 551.37 | 815.68 | 0.00 | 0.00 |
July | 1812.51 | 118.92 | 1280.31 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2009.41 | 160.51 | 1416.37 | 655.69 | 760.68 | 0.00 | 0.00 |
September | 1274.10 | 303.17 | 1005.51 | 439.41 | 566.10 | 0.00 | 0.00 |
October | 1138.04 | 539.64 | 996.89 | 484.76 | 512.13 | 0.00 | 0.00 |
November | 333.51 | 765.95 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 275.29 | 987.59 | 416.40 | 180.18 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1077.89 | 576.53 | 949.31 | 400.18 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 275.29 | 118.92 | 416.40 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2009.41 | 1102.90 | 1416.37 | 655.69 | 815.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.72 | 1741.87 | 327.70 | 0.00 | 327.70 | 0.00 | 0.00 |
February | 51.52 | 1798.97 | 448.45 | 0.00 | 448.45 | 0.00 | 0.00 |
March | 259.33 | 1180.01 | 621.88 | 0.00 | 621.88 | 0.00 | 0.00 |
April | 517.76 | 835.99 | 746.97 | 2.12 | 744.84 | 0.00 | 0.00 |
May | 986.90 | 511.06 | 990.99 | 33.02 | 957.97 | 0.00 | 0.00 |
June | 1339.34 | 279.79 | 1050.93 | 56.47 | 994.46 | 0.00 | 0.00 |
July | 1477.09 | 152.55 | 1015.62 | 36.73 | 978.90 | 0.00 | 0.00 |
August | 1285.14 | 219.31 | 899.80 | 10.71 | 889.09 | 0.00 | 0.00 |
September | 735.40 | 465.53 | 678.30 | 0.13 | 678.17 | 0.00 | 0.00 |
October | 432.76 | 872.33 | 587.02 | 0.00 | 587.02 | 0.00 | 0.00 |
November | 115.38 | 1304.19 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 14.86 | 1665.41 | 285.84 | 0.00 | 285.84 | 0.00 | 0.00 |
Annual Sum or Average | 607.25 | 913.85 | 673.39 | 11.66 | 661.73 | 0.00 | 0.00 |
Minimum of Months | 14.86 | 152.55 | 285.84 | 0.00 | 285.84 | 0.00 | 0.00 |
Maximum of Months | 1477.09 | 1798.97 | 1050.93 | 56.47 | 994.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.09 | 1089.61 | 456.36 | 182.96 | 273.40 | 0.00 | 0.00 |
February | 515.00 | 1097.23 | 707.72 | 330.15 | 377.57 | 0.00 | 0.00 |
March | 817.98 | 778.45 | 902.83 | 383.98 | 518.85 | 0.00 | 0.00 |
April | 1128.55 | 563.00 | 1083.46 | 474.59 | 608.87 | 0.00 | 0.00 |
May | 1556.07 | 362.22 | 1314.01 | 525.15 | 788.85 | 0.00 | 0.00 |
June | 1614.74 | 198.76 | 1217.81 | 440.84 | 776.97 | 0.00 | 0.00 |
July | 1751.49 | 110.63 | 1223.14 | 441.40 | 781.74 | 0.00 | 0.00 |
August | 1955.88 | 156.78 | 1377.28 | 621.02 | 756.27 | 0.00 | 0.00 |
September | 1290.56 | 312.70 | 1027.19 | 460.86 | 566.33 | 0.00 | 0.00 |
October | 1035.92 | 581.27 | 931.22 | 422.06 | 509.16 | 0.00 | 0.00 |
November | 462.63 | 835.53 | 575.89 | 221.15 | 354.74 | 0.00 | 0.00 |
December | 308.28 | 1037.75 | 448.65 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1064.73 | 590.80 | 940.29 | 393.35 | 546.94 | 0.00 | 0.00 |
Minimum of Months | 294.09 | 110.63 | 448.65 | 182.96 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1955.88 | 1097.23 | 1377.28 | 621.02 | 788.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1730.03 | 1579.75 | 1695.25 | 1110.06 | 585.19 | 0.00 | 0.00 |
February | 2311.66 | 1618.55 | 2235.98 | 1480.03 | 755.95 | 0.00 | 0.00 |
March | 2211.80 | 1185.64 | 2017.28 | 1119.62 | 897.66 | 0.00 | 0.00 |
April | 1777.21 | 879.53 | 1565.34 | 618.98 | 946.36 | 0.00 | 0.00 |
May | 1662.18 | 551.85 | 1371.79 | 286.13 | 1085.66 | 0.00 | 0.00 |
June | 1775.37 | 303.64 | 1287.39 | 196.79 | 1090.60 | 0.00 | 0.00 |
July | 2048.49 | 163.01 | 1349.44 | 234.39 | 1115.04 | 0.00 | 0.00 |
August | 2739.90 | 247.27 | 1802.02 | 668.39 | 1133.63 | 0.00 | 0.00 |
September | 2631.75 | 498.35 | 1955.22 | 1011.32 | 943.91 | 0.00 | 0.00 |
October | 3356.87 | 914.46 | 2678.49 | 1679.60 | 998.89 | 0.00 | 0.00 |
November | 2008.75 | 1250.82 | 1857.30 | 1115.39 | 741.91 | 0.00 | 0.00 |
December | 1924.92 | 1511.27 | 1837.40 | 1304.43 | 532.97 | 0.00 | 0.00 |
Annual Sum or Average | 2181.97 | 887.78 | 1802.37 | 899.17 | 903.20 | 0.00 | 0.00 |
Minimum of Months | 1662.18 | 163.01 | 1287.39 | 196.79 | 532.97 | 0.00 | 0.00 |
Maximum of Months | 3356.87 | 1618.55 | 2678.49 | 1679.60 | 1133.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.45 | 1112.52 | 450.53 | 184.54 | 265.99 | 0.00 | 0.00 |
February | 479.27 | 1144.48 | 664.37 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 918.63 | 780.74 | 981.03 | 452.91 | 528.12 | 0.00 | 0.00 |
April | 1130.09 | 582.02 | 1072.22 | 458.77 | 613.45 | 0.00 | 0.00 |
May | 1484.81 | 376.88 | 1249.03 | 474.33 | 774.70 | 0.00 | 0.00 |
June | 1823.90 | 214.26 | 1367.03 | 551.36 | 815.67 | 0.00 | 0.00 |
July | 1830.74 | 120.07 | 1280.29 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2020.52 | 170.60 | 1416.35 | 655.68 | 760.68 | 0.00 | 0.00 |
September | 1276.87 | 327.74 | 1005.50 | 439.40 | 566.10 | 0.00 | 0.00 |
October | 1130.34 | 602.26 | 996.87 | 484.75 | 512.12 | 0.00 | 0.00 |
November | 321.18 | 852.71 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 273.03 | 1065.36 | 416.39 | 180.17 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1086.24 | 609.39 | 949.30 | 400.18 | 549.12 | 0.00 | 0.00 |
Minimum of Months | 273.03 | 120.07 | 416.39 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2020.52 | 1144.48 | 1416.35 | 655.68 | 815.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.50 | 1753.56 | 327.71 | 0.00 | 327.71 | 0.00 | 0.00 |
February | 45.85 | 1831.33 | 448.46 | 0.00 | 448.46 | 0.00 | 0.00 |
March | 234.61 | 1230.73 | 621.90 | 0.00 | 621.90 | 0.00 | 0.00 |
April | 479.38 | 889.75 | 746.98 | 2.12 | 744.86 | 0.00 | 0.00 |
May | 936.25 | 553.40 | 991.01 | 33.02 | 957.99 | 0.00 | 0.00 |
June | 1311.80 | 299.53 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
July | 1455.95 | 166.46 | 1015.65 | 36.73 | 978.92 | 0.00 | 0.00 |
August | 1274.37 | 227.07 | 899.81 | 10.71 | 889.10 | 0.00 | 0.00 |
September | 730.03 | 464.96 | 678.31 | 0.13 | 678.18 | 0.00 | 0.00 |
October | 431.45 | 857.77 | 587.03 | 0.00 | 587.03 | 0.00 | 0.00 |
November | 116.72 | 1271.36 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 14.52 | 1650.77 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Annual Sum or Average | 591.62 | 927.88 | 673.41 | 11.66 | 661.75 | 0.00 | 0.00 |
Minimum of Months | 14.52 | 166.46 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Maximum of Months | 1455.95 | 1831.33 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.77 | 1088.58 | 456.37 | 182.97 | 273.40 | 0.00 | 0.00 |
February | 502.57 | 1103.96 | 707.73 | 330.16 | 377.57 | 0.00 | 0.00 |
March | 794.39 | 796.98 | 902.84 | 383.99 | 518.86 | 0.00 | 0.00 |
April | 1102.94 | 579.44 | 1083.48 | 474.60 | 608.88 | 0.00 | 0.00 |
May | 1525.97 | 378.41 | 1314.03 | 525.17 | 788.86 | 0.00 | 0.00 |
June | 1595.43 | 205.38 | 1217.83 | 440.84 | 776.98 | 0.00 | 0.00 |
July | 1736.77 | 113.66 | 1223.16 | 441.41 | 781.75 | 0.00 | 0.00 |
August | 1946.09 | 153.30 | 1377.31 | 621.03 | 756.28 | 0.00 | 0.00 |
September | 1283.47 | 302.81 | 1027.20 | 460.87 | 566.34 | 0.00 | 0.00 |
October | 1032.51 | 557.23 | 931.23 | 422.07 | 509.17 | 0.00 | 0.00 |
November | 463.26 | 801.96 | 575.90 | 221.15 | 354.75 | 0.00 | 0.00 |
December | 305.68 | 1018.33 | 448.66 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1051.86 | 588.77 | 940.30 | 393.35 | 546.95 | 0.00 | 0.00 |
Minimum of Months | 287.77 | 113.66 | 448.66 | 182.97 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1946.09 | 1103.96 | 1377.31 | 621.03 | 788.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1690.52 | 1577.86 | 1695.32 | 1110.10 | 585.21 | 0.00 | 0.00 |
February | 2261.72 | 1611.36 | 2236.06 | 1480.09 | 755.97 | 0.00 | 0.00 |
March | 2160.25 | 1205.46 | 2017.35 | 1119.66 | 897.69 | 0.00 | 0.00 |
April | 1728.82 | 919.07 | 1565.39 | 619.00 | 946.39 | 0.00 | 0.00 |
May | 1605.82 | 596.11 | 1371.84 | 286.14 | 1085.69 | 0.00 | 0.00 |
June | 1745.56 | 321.44 | 1287.43 | 196.80 | 1090.63 | 0.00 | 0.00 |
July | 2029.34 | 171.81 | 1349.48 | 234.40 | 1115.08 | 0.00 | 0.00 |
August | 2730.08 | 241.34 | 1802.08 | 668.42 | 1133.66 | 0.00 | 0.00 |
September | 2622.48 | 476.84 | 1955.30 | 1011.36 | 943.94 | 0.00 | 0.00 |
October | 3346.18 | 857.66 | 2678.59 | 1679.67 | 998.92 | 0.00 | 0.00 |
November | 1992.47 | 1198.84 | 1857.37 | 1115.44 | 741.93 | 0.00 | 0.00 |
December | 1900.52 | 1471.63 | 1837.47 | 1304.48 | 532.99 | 0.00 | 0.00 |
Annual Sum or Average | 2151.65 | 883.24 | 1802.44 | 899.21 | 903.23 | 0.00 | 0.00 |
Minimum of Months | 1605.82 | 171.81 | 1287.43 | 196.80 | 532.99 | 0.00 | 0.00 |
Maximum of Months | 3346.18 | 1611.36 | 2678.59 | 1679.67 | 1133.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.39 | 1114.08 | 450.54 | 184.54 | 266.00 | 0.00 | 0.00 |
February | 466.32 | 1152.56 | 664.38 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 897.62 | 794.43 | 981.04 | 452.92 | 528.12 | 0.00 | 0.00 |
April | 1106.53 | 598.01 | 1072.24 | 458.78 | 613.45 | 0.00 | 0.00 |
May | 1458.53 | 392.58 | 1249.05 | 474.34 | 774.71 | 0.00 | 0.00 |
June | 1808.24 | 217.58 | 1367.04 | 551.37 | 815.68 | 0.00 | 0.00 |
July | 1818.98 | 121.22 | 1280.31 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2014.23 | 165.15 | 1416.37 | 655.69 | 760.68 | 0.00 | 0.00 |
September | 1273.52 | 317.44 | 1005.51 | 439.41 | 566.10 | 0.00 | 0.00 |
October | 1129.65 | 575.33 | 996.89 | 484.76 | 512.13 | 0.00 | 0.00 |
November | 321.72 | 823.34 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 269.66 | 1047.85 | 416.40 | 180.18 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1075.30 | 606.83 | 949.31 | 400.18 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 269.66 | 121.22 | 416.40 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2014.23 | 1152.56 | 1416.37 | 655.69 | 815.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 73126662.21 | 0.452026E+10 | 0.877739E+09 | 0.00 | 0.877739E+09 | 0.00 | 0.00 |
February | 0.121433E+09 | 0.424461E+10 | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.00 | 0.00 |
March | 0.653186E+09 | 0.312040E+10 | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.00 | 0.00 |
April | 0.127148E+10 | 0.217612E+10 | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.00 | 0.00 |
May | 0.251882E+10 | 0.142734E+10 | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.00 | 0.00 |
June | 0.338861E+10 | 0.754984E+09 | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.00 | 0.00 |
July | 0.387726E+10 | 0.439499E+09 | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.00 | 0.00 |
August | 0.340023E+10 | 0.591289E+09 | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.00 | 0.00 |
September | 0.189862E+10 | 0.114793E+10 | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.00 | 0.00 |
October | 0.119586E+10 | 0.214758E+10 | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.00 | 0.00 |
November | 0.341721E+09 | 0.306243E+10 | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.00 | 0.00 |
December | 49226267.42 | 0.417203E+10 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187896E+11 | 0.278045E+11 | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.00 | 0.00 |
Minimum of Months | 49226267.42 | 0.439499E+09 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Maximum of Months | 0.387726E+10 | 0.452026E+10 | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785466E+09 | 0.280529E+10 | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.00 | 0.00 |
February | 0.124174E+10 | 0.255386E+10 | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.00 | 0.00 |
March | 0.215763E+10 | 0.201950E+10 | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.00 | 0.00 |
April | 0.288550E+10 | 0.142252E+10 | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.00 | 0.00 |
May | 0.409808E+10 | 0.978279E+09 | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.00 | 0.00 |
June | 0.413471E+10 | 0.517682E+09 | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.00 | 0.00 |
July | 0.464487E+10 | 0.299044E+09 | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.00 | 0.00 |
August | 0.520997E+10 | 0.399018E+09 | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.00 | 0.00 |
September | 0.333689E+10 | 0.750065E+09 | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.00 | 0.00 |
October | 0.279634E+10 | 0.140269E+10 | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.00 | 0.00 |
November | 0.124282E+10 | 0.193413E+10 | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.00 | 0.00 |
December | 0.845208E+09 | 0.256899E+10 | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333792E+11 | 0.176511E+11 | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.785466E+09 | 0.299044E+09 | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.520997E+10 | 0.280529E+10 | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.455247E+10 | 0.405025E+10 | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.00 | 0.00 |
February | 0.550936E+10 | 0.371992E+10 | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.00 | 0.00 |
March | 0.581323E+10 | 0.305618E+10 | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.00 | 0.00 |
April | 0.450333E+10 | 0.225466E+10 | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.00 | 0.00 |
May | 0.430352E+10 | 0.153668E+10 | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.00 | 0.00 |
June | 0.450930E+10 | 0.809221E+09 | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.00 | 0.00 |
July | 0.541084E+10 | 0.452249E+09 | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.00 | 0.00 |
August | 0.729252E+10 | 0.628145E+09 | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.00 | 0.00 |
September | 0.679688E+10 | 0.118266E+10 | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.00 | 0.00 |
October | 0.898588E+10 | 0.216664E+10 | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.00 | 0.00 |
November | 0.522116E+10 | 0.289892E+10 | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.00 | 0.00 |
December | 0.513902E+10 | 0.371293E+10 | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.680375E+11 | 0.264685E+11 | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430352E+10 | 0.452249E+09 | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898588E+10 | 0.405025E+10 | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.774894E+09 | 0.286877E+10 | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.00 | 0.00 |
February | 0.113887E+10 | 0.266814E+10 | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.00 | 0.00 |
March | 0.242154E+10 | 0.201258E+10 | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.00 | 0.00 |
April | 0.288465E+10 | 0.146351E+10 | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.00 | 0.00 |
May | 0.390851E+10 | 0.101109E+10 | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.00 | 0.00 |
June | 0.467501E+10 | 0.547180E+09 | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.00 | 0.00 |
July | 0.485463E+10 | 0.318515E+09 | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.00 | 0.00 |
August | 0.538200E+10 | 0.429922E+09 | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.00 | 0.00 |
September | 0.330246E+10 | 0.785818E+09 | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.00 | 0.00 |
October | 0.304812E+10 | 0.144538E+10 | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.00 | 0.00 |
November | 0.864456E+09 | 0.198533E+10 | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.00 | 0.00 |
December | 0.737333E+09 | 0.264516E+10 | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339925E+11 | 0.181814E+11 | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.00 | 0.00 |
Minimum of Months | 0.737333E+09 | 0.318515E+09 | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.00 | 0.00 |
Maximum of Months | 0.538200E+10 | 0.286877E+10 | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71565957.75 | 0.466542E+10 | 0.877720E+09 | 0.00 | 0.877720E+09 | 0.00 | 0.00 |
February | 0.124631E+09 | 0.435208E+10 | 0.108489E+10 | 0.00 | 0.108489E+10 | 0.00 | 0.00 |
March | 0.694591E+09 | 0.316054E+10 | 0.166566E+10 | 0.00 | 0.166566E+10 | 0.00 | 0.00 |
April | 0.134205E+10 | 0.216689E+10 | 0.193614E+10 | 5506939.83 | 0.193064E+10 | 0.00 | 0.00 |
May | 0.264331E+10 | 0.136883E+10 | 0.265427E+10 | 88440895.47 | 0.256582E+10 | 0.00 | 0.00 |
June | 0.347158E+10 | 0.725219E+09 | 0.272402E+10 | 0.146372E+09 | 0.257764E+10 | 0.00 | 0.00 |
July | 0.395624E+10 | 0.408582E+09 | 0.272025E+10 | 98372414.25 | 0.262187E+10 | 0.00 | 0.00 |
August | 0.344213E+10 | 0.587391E+09 | 0.241001E+10 | 28682265.77 | 0.238133E+10 | 0.00 | 0.00 |
September | 0.190616E+10 | 0.120665E+10 | 0.175814E+10 | 329225.84 | 0.175781E+10 | 0.00 | 0.00 |
October | 0.115911E+10 | 0.233645E+10 | 0.157226E+10 | 0.00 | 0.157226E+10 | 0.00 | 0.00 |
November | 0.299054E+09 | 0.338046E+10 | 0.106722E+10 | 0.00 | 0.106722E+10 | 0.00 | 0.00 |
December | 39791543.01 | 0.446062E+10 | 0.765605E+09 | 0.00 | 0.765605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191502E+11 | 0.288191E+11 | 0.212362E+11 | 0.367703E+09 | 0.208685E+11 | 0.00 | 0.00 |
Minimum of Months | 39791543.01 | 0.408582E+09 | 0.765605E+09 | 0.00 | 0.765605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.395624E+10 | 0.466542E+10 | 0.272402E+10 | 0.146372E+09 | 0.262187E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.787677E+09 | 0.291841E+10 | 0.122232E+10 | 0.490050E+09 | 0.732271E+09 | 0.00 | 0.00 |
February | 0.124590E+10 | 0.265443E+10 | 0.171212E+10 | 0.798700E+09 | 0.913415E+09 | 0.00 | 0.00 |
March | 0.219088E+10 | 0.208500E+10 | 0.241814E+10 | 0.102845E+10 | 0.138969E+10 | 0.00 | 0.00 |
April | 0.292519E+10 | 0.145929E+10 | 0.280833E+10 | 0.123013E+10 | 0.157820E+10 | 0.00 | 0.00 |
May | 0.416776E+10 | 0.970168E+09 | 0.351944E+10 | 0.140657E+10 | 0.211287E+10 | 0.00 | 0.00 |
June | 0.418542E+10 | 0.515178E+09 | 0.315656E+10 | 0.114265E+10 | 0.201391E+10 | 0.00 | 0.00 |
July | 0.469118E+10 | 0.296314E+09 | 0.327606E+10 | 0.118224E+10 | 0.209381E+10 | 0.00 | 0.00 |
August | 0.523863E+10 | 0.419917E+09 | 0.368892E+10 | 0.166333E+10 | 0.202559E+10 | 0.00 | 0.00 |
September | 0.334514E+10 | 0.810519E+09 | 0.266247E+10 | 0.119454E+10 | 0.146793E+10 | 0.00 | 0.00 |
October | 0.277462E+10 | 0.155688E+10 | 0.249418E+10 | 0.113044E+10 | 0.136374E+10 | 0.00 | 0.00 |
November | 0.119914E+10 | 0.216570E+10 | 0.149270E+10 | 0.573210E+09 | 0.919490E+09 | 0.00 | 0.00 |
December | 0.825702E+09 | 0.277952E+10 | 0.120166E+10 | 0.564225E+09 | 0.637437E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335772E+11 | 0.186313E+11 | 0.296529E+11 | 0.124045E+11 | 0.172484E+11 | 0.00 | 0.00 |
Minimum of Months | 0.787677E+09 | 0.296314E+09 | 0.120166E+10 | 0.490050E+09 | 0.637437E+09 | 0.00 | 0.00 |
Maximum of Months | 0.523863E+10 | 0.291841E+10 | 0.368892E+10 | 0.166333E+10 | 0.211287E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.463372E+10 | 0.423121E+10 | 0.454055E+10 | 0.297318E+10 | 0.156738E+10 | 0.00 | 0.00 |
February | 0.559237E+10 | 0.391560E+10 | 0.540927E+10 | 0.358049E+10 | 0.182878E+10 | 0.00 | 0.00 |
March | 0.592408E+10 | 0.317563E+10 | 0.540307E+10 | 0.299879E+10 | 0.240428E+10 | 0.00 | 0.00 |
April | 0.460654E+10 | 0.227974E+10 | 0.405736E+10 | 0.160439E+10 | 0.245297E+10 | 0.00 | 0.00 |
May | 0.445198E+10 | 0.147807E+10 | 0.367420E+10 | 0.766374E+09 | 0.290783E+10 | 0.00 | 0.00 |
June | 0.460175E+10 | 0.787048E+09 | 0.333690E+10 | 0.510075E+09 | 0.282683E+10 | 0.00 | 0.00 |
July | 0.548667E+10 | 0.436611E+09 | 0.361433E+10 | 0.627803E+09 | 0.298653E+10 | 0.00 | 0.00 |
August | 0.733854E+10 | 0.662290E+09 | 0.482653E+10 | 0.179023E+10 | 0.303630E+10 | 0.00 | 0.00 |
September | 0.682149E+10 | 0.129173E+10 | 0.506794E+10 | 0.262133E+10 | 0.244661E+10 | 0.00 | 0.00 |
October | 0.899104E+10 | 0.244929E+10 | 0.717406E+10 | 0.449864E+10 | 0.267542E+10 | 0.00 | 0.00 |
November | 0.520667E+10 | 0.324213E+10 | 0.481412E+10 | 0.289110E+10 | 0.192302E+10 | 0.00 | 0.00 |
December | 0.515572E+10 | 0.404778E+10 | 0.492128E+10 | 0.349377E+10 | 0.142751E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.688106E+11 | 0.279971E+11 | 0.568396E+11 | 0.283562E+11 | 0.284835E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445198E+10 | 0.436611E+09 | 0.333690E+10 | 0.510075E+09 | 0.142751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.899104E+10 | 0.423121E+10 | 0.717406E+10 | 0.449864E+10 | 0.303630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785970E+09 | 0.297977E+10 | 0.120671E+10 | 0.494269E+09 | 0.712437E+09 | 0.00 | 0.00 |
February | 0.115945E+10 | 0.276873E+10 | 0.160726E+10 | 0.705911E+09 | 0.901345E+09 | 0.00 | 0.00 |
March | 0.246046E+10 | 0.209114E+10 | 0.262759E+10 | 0.121308E+10 | 0.141451E+10 | 0.00 | 0.00 |
April | 0.292920E+10 | 0.150860E+10 | 0.277920E+10 | 0.118914E+10 | 0.159005E+10 | 0.00 | 0.00 |
May | 0.397690E+10 | 0.100944E+10 | 0.334540E+10 | 0.127045E+10 | 0.207495E+10 | 0.00 | 0.00 |
June | 0.472754E+10 | 0.555355E+09 | 0.354333E+10 | 0.142912E+10 | 0.211421E+10 | 0.00 | 0.00 |
July | 0.490345E+10 | 0.321582E+09 | 0.342914E+10 | 0.129130E+10 | 0.213783E+10 | 0.00 | 0.00 |
August | 0.541175E+10 | 0.456931E+09 | 0.379356E+10 | 0.175616E+10 | 0.203739E+10 | 0.00 | 0.00 |
September | 0.330965E+10 | 0.849503E+09 | 0.260625E+10 | 0.113892E+10 | 0.146733E+10 | 0.00 | 0.00 |
October | 0.302750E+10 | 0.161310E+10 | 0.267003E+10 | 0.129837E+10 | 0.137166E+10 | 0.00 | 0.00 |
November | 0.832489E+09 | 0.221023E+10 | 0.121339E+10 | 0.350677E+09 | 0.862713E+09 | 0.00 | 0.00 |
December | 0.731281E+09 | 0.285347E+10 | 0.111526E+10 | 0.482575E+09 | 0.632686E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342556E+11 | 0.192178E+11 | 0.299371E+11 | 0.126200E+11 | 0.173171E+11 | 0.00 | 0.00 |
Minimum of Months | 0.731281E+09 | 0.321582E+09 | 0.111526E+10 | 0.350677E+09 | 0.632686E+09 | 0.00 | 0.00 |
Maximum of Months | 0.541175E+10 | 0.297977E+10 | 0.379356E+10 | 0.175616E+10 | 0.213783E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 65611954.77 | 0.469675E+10 | 0.877739E+09 | 0.00 | 0.877739E+09 | 0.00 | 0.00 |
February | 0.110929E+09 | 0.443035E+10 | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.00 | 0.00 |
March | 0.628383E+09 | 0.329638E+10 | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.00 | 0.00 |
April | 0.124255E+10 | 0.230624E+10 | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.00 | 0.00 |
May | 0.250765E+10 | 0.148222E+10 | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.00 | 0.00 |
June | 0.340020E+10 | 0.776383E+09 | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.00 | 0.00 |
July | 0.389960E+10 | 0.445846E+09 | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.00 | 0.00 |
August | 0.341326E+10 | 0.608192E+09 | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.00 | 0.00 |
September | 0.189225E+10 | 0.120517E+10 | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.00 | 0.00 |
October | 0.115559E+10 | 0.229745E+10 | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.00 | 0.00 |
November | 0.302549E+09 | 0.329538E+10 | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.00 | 0.00 |
December | 38882493.45 | 0.442141E+10 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186575E+11 | 0.292618E+11 | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.00 | 0.00 |
Minimum of Months | 38882493.45 | 0.445846E+09 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Maximum of Months | 0.389960E+10 | 0.469675E+10 | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770767E+09 | 0.291566E+10 | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.00 | 0.00 |
February | 0.121582E+10 | 0.267070E+10 | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.00 | 0.00 |
March | 0.212770E+10 | 0.213463E+10 | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.00 | 0.00 |
April | 0.285881E+10 | 0.150192E+10 | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.00 | 0.00 |
May | 0.408717E+10 | 0.101353E+10 | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.00 | 0.00 |
June | 0.413535E+10 | 0.532352E+09 | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.00 | 0.00 |
July | 0.465176E+10 | 0.304414E+09 | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.00 | 0.00 |
August | 0.521240E+10 | 0.410587E+09 | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.00 | 0.00 |
September | 0.332675E+10 | 0.784873E+09 | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.00 | 0.00 |
October | 0.276547E+10 | 0.149248E+10 | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.00 | 0.00 |
November | 0.120077E+10 | 0.207867E+10 | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.00 | 0.00 |
December | 0.818737E+09 | 0.272750E+10 | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.331715E+11 | 0.185673E+11 | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.770767E+09 | 0.304414E+09 | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521240E+10 | 0.291566E+10 | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452788E+10 | 0.422614E+10 | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.00 | 0.00 |
February | 0.547156E+10 | 0.389820E+10 | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.00 | 0.00 |
March | 0.578601E+10 | 0.322870E+10 | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.00 | 0.00 |
April | 0.448110E+10 | 0.238222E+10 | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.00 | 0.00 |
May | 0.430103E+10 | 0.159663E+10 | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.00 | 0.00 |
June | 0.452450E+10 | 0.833172E+09 | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.00 | 0.00 |
July | 0.543537E+10 | 0.460178E+09 | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.00 | 0.00 |
August | 0.731225E+10 | 0.646416E+09 | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.00 | 0.00 |
September | 0.679747E+10 | 0.123598E+10 | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.00 | 0.00 |
October | 0.896241E+10 | 0.229715E+10 | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.00 | 0.00 |
November | 0.516449E+10 | 0.310739E+10 | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.00 | 0.00 |
December | 0.509036E+10 | 0.394162E+10 | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.678544E+11 | 0.278538E+11 | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430103E+10 | 0.460178E+09 | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.00 | 0.00 |
Maximum of Months | 0.896241E+10 | 0.422614E+10 | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.767058E+09 | 0.298396E+10 | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.00 | 0.00 |
February | 0.112812E+10 | 0.278828E+10 | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.00 | 0.00 |
March | 0.240417E+10 | 0.212779E+10 | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.00 | 0.00 |
April | 0.286812E+10 | 0.155003E+10 | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.00 | 0.00 |
May | 0.390652E+10 | 0.105148E+10 | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.00 | 0.00 |
June | 0.468695E+10 | 0.563959E+09 | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.00 | 0.00 |
July | 0.487194E+10 | 0.324679E+09 | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.00 | 0.00 |
August | 0.539491E+10 | 0.442350E+09 | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.00 | 0.00 |
September | 0.330097E+10 | 0.822793E+09 | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.00 | 0.00 |
October | 0.302566E+10 | 0.154096E+10 | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.00 | 0.00 |
November | 0.833888E+09 | 0.213409E+10 | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.00 | 0.00 |
December | 0.722246E+09 | 0.280657E+10 | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339105E+11 | 0.191369E+11 | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.00 | 0.00 |
Minimum of Months | 0.722246E+09 | 0.324679E+09 | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.00 | 0.00 |
Maximum of Months | 0.539491E+10 | 0.298396E+10 | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.537642E+10 | -0.462439E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -752024467.0 | 58.98 | 0.00 | 0.00 |
February | 0.491036E+10 | -0.424500E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -665358986.0 | 58.98 | 0.00 | 0.00 |
March | 0.562890E+10 | -0.491112E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717784455.1 | 58.98 | 0.00 | 0.00 |
April | 0.487547E+10 | -0.419253E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -682932960.1 | 58.98 | 0.00 | 0.00 |
May | 0.488283E+10 | -0.418700E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695831516.4 | 58.98 | 0.00 | 0.00 |
June | 0.452613E+10 | -0.385677E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669355269.8 | 58.98 | 0.00 | 0.00 |
July | 0.413083E+10 | -0.344124E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689586077.1 | 58.98 | 0.00 | 0.00 |
August | 0.444354E+10 | -0.375350E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690037972.4 | 58.98 | 0.00 | 0.00 |
September | 0.415475E+10 | -0.348641E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668339546.3 | 58.98 | 0.00 | 0.00 |
October | 0.453274E+10 | -0.383933E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693409452.7 | 58.98 | 0.00 | 0.00 |
November | 0.476010E+10 | -0.407193E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -688170970.3 | 58.98 | 0.00 | 0.00 |
December | 0.503406E+10 | -0.430584E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -728216168.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.572561E+11 | -0.489151E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.834105E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.413083E+10 | -0.491112E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -752024467.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.562890E+10 | -0.344124E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -665358986.0 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6502.60 | 36.69 | 196.17 | 241.50 | 3388.99 | 33.30 | 185.67 | 196.67 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9259.17 | 37.54 | 210.00 | 258.33 | 2126.96 | 26.55 | 176.83 | 233.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3276.47 | 21.57 | 57.00 | 318.33 | 1592.25 | 21.71 | 170.17 | 285.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2073.87 | 18.95 | 1.83 | 339.00 | 1227.90 | 21.18 | 149.83 | 299.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1803.96 | 18.85 | 0.00 | 390.67 | 1014.36 | 21.02 | 225.17 | 347.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1718.13 | 18.83 | 0.00 | 382.50 | 978.98 | 21.06 | 208.00 | 340.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1896.16 | 19.09 | 1.00 | 390.33 | 1057.77 | 21.32 | 237.83 | 344.33 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2107.07 | 19.07 | 7.83 | 370.67 | 1223.37 | 21.27 | 238.00 | 340.00 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3805.78 | 21.30 | 36.50 | 323.83 | 1466.81 | 21.48 | 178.50 | 289.50 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10128.99 | 36.12 | 283.50 | 307.00 | 2052.87 | 23.60 | 258.83 | 289.00 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6447.57 | 36.31 | 235.17 | 257.17 | 2274.92 | 29.45 | 223.33 | 236.00 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6063.17 | 36.57 | 198.50 | 243.33 | 5410.95 | 39.04 | 208.00 | 214.67 |
Annual Sum or Average | 3472.67 | 0.50 | 4187.37 | 25.32 | 1227.50 | 3822.67 | 1789.52 | 24.15 | 2460.17 | 3415.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1718.13 | 18.83 | 0.00 | 241.50 | 978.98 | 21.02 | 149.83 | 196.67 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10128.99 | 37.54 | 283.50 | 390.67 | 5410.95 | 39.04 | 258.83 | 347.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1978.73 | 21.31 | 61.00 | 221.17 | 1125.41 | 23.69 | 88.67 | 158.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2816.44 | 24.01 | 80.67 | 245.50 | 1626.39 | 24.64 | 92.17 | 207.17 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2919.56 | 21.40 | 71.50 | 313.50 | 1635.57 | 22.57 | 77.67 | 260.17 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3823.68 | 22.28 | 80.67 | 341.33 | 1557.02 | 22.91 | 53.33 | 302.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3178.29 | 21.15 | 99.17 | 396.67 | 1725.36 | 22.44 | 73.50 | 354.83 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2835.16 | 20.46 | 80.67 | 387.17 | 1588.14 | 22.72 | 69.83 | 353.17 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:49 | 2929.24 | 21.08 | 89.67 | 396.00 | 1588.94 | 22.48 | 69.50 | 358.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3910.50 | 23.17 | 128.17 | 373.17 | 1632.37 | 22.85 | 82.67 | 346.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3397.81 | 22.17 | 82.67 | 320.67 | 1492.55 | 22.75 | 64.17 | 285.83 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3017.01 | 23.06 | 91.17 | 293.50 | 1597.73 | 23.88 | 137.67 | 265.33 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2042.55 | 22.03 | 73.33 | 244.50 | 1050.61 | 22.55 | 114.17 | 200.67 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1895.84 | 23.20 | 81.17 | 221.17 | 1103.75 | 24.08 | 91.33 | 157.33 |
Annual Sum or Average | 3472.67 | 0.51 | 2983.12 | 22.03 | 1019.83 | 3754.33 | 1511.35 | 23.03 | 1014.67 | 3250.33 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1895.84 | 20.46 | 61.00 | 221.17 | 1050.61 | 22.44 | 53.33 | 157.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3910.50 | 24.01 | 128.17 | 396.67 | 1725.36 | 24.64 | 137.67 | 358.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:39 | 634.71 | 15.57 | 0.00 | 207.50 | 385.93 | 17.99 | 0.00 | 118.00 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 688.41 | 16.52 | 0.00 | 230.33 | 443.21 | 19.04 | 0.00 | 162.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 911.03 | 17.40 | 0.00 | 308.00 | 564.74 | 19.64 | 13.33 | 237.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1025.43 | 18.38 | 0.00 | 344.00 | 638.11 | 20.58 | 51.17 | 295.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1322.13 | 19.16 | 7.50 | 403.67 | 759.55 | 21.28 | 168.33 | 363.17 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-04:00 | 1491.61 | 22.44 | 74.50 | 401.83 | 837.60 | 23.66 | 239.00 | 373.33 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1468.07 | 20.28 | 26.83 | 407.50 | 829.27 | 23.22 | 244.50 | 371.50 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1208.24 | 18.79 | 0.00 | 377.83 | 726.71 | 20.97 | 164.67 | 350.00 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 940.22 | 17.95 | 0.00 | 320.17 | 590.55 | 20.22 | 27.50 | 269.67 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 854.25 | 17.60 | 0.00 | 289.17 | 548.00 | 20.01 | 0.00 | 243.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 707.70 | 16.27 | 0.00 | 233.83 | 421.69 | 18.60 | 0.00 | 155.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:39 | 512.50 | 14.57 | 0.00 | 196.00 | 321.08 | 17.16 | 0.00 | 89.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1043.72 | 18.29 | 108.83 | 3719.83 | 622.82 | 20.54 | 908.50 | 3030.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 512.50 | 14.57 | 0.00 | 196.00 | 321.08 | 17.16 | 0.00 | 89.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1491.61 | 22.44 | 74.50 | 407.50 | 837.60 | 23.66 | 244.50 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:39 | 1970.59 | 23.24 | 73.33 | 228.67 | 1113.66 | 23.83 | 78.83 | 162.50 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2197.29 | 21.43 | 57.00 | 244.33 | 1186.09 | 23.37 | 76.00 | 204.50 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3178.88 | 23.68 | 95.83 | 317.00 | 1797.95 | 24.57 | 92.50 | 272.33 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3617.58 | 21.96 | 76.83 | 340.17 | 1503.45 | 21.51 | 40.33 | 299.67 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3412.56 | 19.22 | 69.33 | 395.17 | 1516.69 | 19.00 | 0.00 | 357.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3301.34 | 15.87 | 1.83 | 391.17 | 1787.28 | 19.18 | 2.50 | 351.83 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 3106.44 | 18.53 | 49.00 | 397.17 | 1665.56 | 19.30 | 6.17 | 355.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3988.07 | 20.31 | 86.33 | 373.33 | 1740.05 | 19.43 | 19.50 | 346.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3220.56 | 22.40 | 85.33 | 322.17 | 1683.18 | 23.13 | 68.50 | 284.67 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3451.04 | 24.12 | 109.33 | 303.50 | 1464.97 | 23.44 | 119.17 | 275.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1669.38 | 21.05 | 68.83 | 245.33 | 913.53 | 23.40 | 99.67 | 203.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:39 | 1561.79 | 21.16 | 67.50 | 220.17 | 890.50 | 23.26 | 76.33 | 162.67 |
Annual Sum or Average | 3472.67 | 0.50 | 3026.26 | 20.80 | 840.50 | 3778.17 | 1491.57 | 21.57 | 679.50 | 3277.17 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1561.79 | 15.87 | 1.83 | 220.17 | 890.50 | 19.00 | 0.00 | 162.50 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3988.07 | 24.12 | 109.33 | 397.17 | 1797.95 | 24.57 | 119.17 | 357.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6326.56 | 36.47 | 196.17 | 238.33 | 3258.62 | 32.19 | 144.00 | 194.00 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9075.85 | 37.27 | 210.00 | 256.83 | 2002.17 | 24.94 | 80.00 | 233.67 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3153.97 | 18.16 | 45.83 | 318.33 | 1479.48 | 19.19 | 40.50 | 279.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1969.95 | 15.24 | 0.00 | 338.33 | 1152.51 | 18.82 | 7.67 | 295.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1727.85 | 15.23 | 0.00 | 389.17 | 964.77 | 18.66 | 0.50 | 342.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:49 | 1648.46 | 15.22 | 0.00 | 380.33 | 935.04 | 18.73 | 0.00 | 335.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.89 | 15.42 | 0.00 | 388.67 | 1007.82 | 18.91 | 1.83 | 341.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2007.75 | 15.51 | 0.00 | 368.67 | 1154.27 | 19.00 | 19.33 | 335.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3670.97 | 17.87 | 29.50 | 322.33 | 1365.47 | 18.97 | 20.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 9929.84 | 35.44 | 281.00 | 306.17 | 1907.88 | 20.87 | 46.33 | 287.33 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6268.79 | 35.30 | 228.83 | 255.83 | 2152.12 | 27.59 | 121.17 | 234.00 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5883.17 | 35.73 | 195.50 | 239.17 | 5278.82 | 38.86 | 208.00 | 212.00 |
Annual Sum or Average | 3472.67 | 0.50 | 4061.83 | 22.74 | 1186.83 | 3802.17 | 1699.27 | 22.02 | 689.67 | 3377.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1648.46 | 15.22 | 0.00 | 238.33 | 935.04 | 18.66 | 0.00 | 194.00 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 9929.84 | 37.27 | 281.00 | 389.17 | 5278.82 | 38.86 | 208.00 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1921.04 | 20.83 | 61.00 | 218.83 | 1081.84 | 23.47 | 82.50 | 156.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2748.16 | 23.56 | 80.67 | 243.50 | 1572.21 | 24.44 | 82.67 | 202.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2742.96 | 19.56 | 58.83 | 311.00 | 1573.44 | 22.36 | 67.83 | 252.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3732.76 | 21.83 | 80.67 | 338.83 | 1485.02 | 22.73 | 52.00 | 298.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3083.31 | 20.70 | 99.17 | 395.67 | 1656.52 | 22.27 | 72.83 | 351.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2751.88 | 19.99 | 80.67 | 385.00 | 1526.79 | 22.55 | 69.00 | 351.17 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2838.36 | 20.58 | 89.17 | 394.33 | 1524.45 | 22.31 | 67.00 | 354.67 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3767.85 | 21.40 | 111.67 | 371.00 | 1554.94 | 22.54 | 74.17 | 344.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3312.24 | 21.69 | 82.67 | 319.67 | 1400.88 | 21.70 | 49.00 | 281.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2932.16 | 22.58 | 91.17 | 291.00 | 1532.35 | 23.67 | 119.67 | 261.67 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 1976.18 | 21.37 | 72.00 | 242.17 | 1002.42 | 22.32 | 102.00 | 197.00 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1757.84 | 20.40 | 64.00 | 214.83 | 1064.80 | 23.86 | 86.33 | 152.17 |
Annual Sum or Average | 3472.67 | 0.51 | 2883.09 | 21.15 | 971.67 | 3725.83 | 1447.10 | 22.76 | 925.00 | 3203.17 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1757.84 | 19.56 | 58.83 | 214.83 | 1002.42 | 21.70 | 49.00 | 152.17 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3767.85 | 23.56 | 111.67 | 395.67 | 1656.52 | 24.44 | 119.67 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:50 | 610.06 | 12.00 | 0.00 | 203.17 | 372.57 | 15.62 | 0.00 | 112.33 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 662.22 | 13.10 | 0.00 | 226.67 | 429.60 | 16.87 | 0.00 | 157.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:30 | 878.27 | 14.16 | 0.00 | 306.50 | 547.39 | 17.66 | 0.00 | 229.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 989.39 | 15.16 | 0.00 | 342.50 | 619.11 | 18.71 | 0.00 | 291.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1274.56 | 15.68 | 3.00 | 401.83 | 732.99 | 19.16 | 36.67 | 359.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1434.32 | 18.89 | 62.67 | 398.83 | 807.88 | 21.82 | 76.67 | 371.50 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1411.99 | 15.75 | 0.00 | 405.00 | 799.54 | 21.32 | 63.17 | 368.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1165.38 | 15.59 | 0.00 | 377.50 | 703.61 | 19.10 | 8.17 | 346.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 906.59 | 14.77 | 0.00 | 317.83 | 572.88 | 18.32 | 0.00 | 263.83 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 821.12 | 14.41 | 0.00 | 286.67 | 530.68 | 18.03 | 0.00 | 239.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 680.86 | 12.60 | 0.00 | 230.83 | 406.95 | 16.20 | 0.00 | 146.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:50 | 492.02 | 10.88 | 0.00 | 190.33 | 310.15 | 14.69 | 0.00 | 84.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1004.99 | 14.78 | 65.67 | 3687.67 | 602.17 | 18.51 | 184.67 | 2971.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 492.02 | 10.88 | 0.00 | 190.33 | 310.15 | 14.69 | 0.00 | 84.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1434.32 | 18.89 | 62.67 | 405.00 | 807.88 | 21.82 | 76.67 | 371.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:39 | 1832.28 | 20.59 | 57.17 | 224.50 | 1070.81 | 23.70 | 77.00 | 158.33 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2128.10 | 21.00 | 57.00 | 242.83 | 1100.33 | 22.17 | 66.50 | 199.67 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3094.28 | 23.30 | 95.83 | 316.17 | 1729.71 | 24.39 | 88.83 | 265.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3526.55 | 21.53 | 76.83 | 337.83 | 1431.94 | 21.36 | 38.83 | 297.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:19 | 3325.85 | 18.75 | 69.17 | 393.50 | 1452.61 | 18.82 | 0.00 | 353.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3198.87 | 15.34 | 1.83 | 389.50 | 1714.55 | 19.00 | 1.50 | 347.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:00 | 3008.69 | 18.05 | 49.00 | 395.33 | 1596.86 | 19.13 | 4.50 | 352.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3842.14 | 19.86 | 86.33 | 371.17 | 1664.28 | 19.28 | 14.83 | 344.17 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3136.61 | 21.99 | 85.33 | 320.83 | 1615.36 | 23.01 | 66.50 | 280.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3358.70 | 23.74 | 109.33 | 302.17 | 1395.36 | 23.33 | 115.83 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1619.51 | 20.64 | 68.83 | 243.67 | 874.07 | 23.11 | 94.33 | 197.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:50 | 1513.50 | 20.77 | 67.50 | 218.00 | 820.02 | 21.77 | 65.50 | 155.33 |
Annual Sum or Average | 3472.67 | 0.50 | 2932.74 | 20.23 | 824.17 | 3755.50 | 1424.33 | 21.26 | 634.17 | 3224.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1513.50 | 15.34 | 1.83 | 218.00 | 820.02 | 18.82 | 0.00 | 155.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3842.14 | 23.74 | 109.33 | 395.33 | 1729.71 | 24.39 | 115.83 | 353.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6326.55 | 36.47 | 196.17 | 238.33 | 3258.51 | 32.19 | 144.00 | 193.83 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9075.80 | 37.27 | 210.00 | 256.83 | 2002.06 | 24.94 | 80.00 | 233.67 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3153.85 | 18.16 | 45.83 | 318.33 | 1479.37 | 19.19 | 40.50 | 279.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1969.85 | 15.25 | 0.00 | 338.33 | 1152.43 | 18.82 | 7.67 | 295.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1727.75 | 15.24 | 0.00 | 389.17 | 964.70 | 18.67 | 0.83 | 342.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:49 | 1648.37 | 15.22 | 0.00 | 380.33 | 934.97 | 18.73 | 0.00 | 335.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.78 | 15.42 | 0.00 | 388.67 | 1007.74 | 18.91 | 1.83 | 341.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2007.65 | 15.51 | 0.00 | 368.67 | 1154.19 | 19.00 | 19.50 | 335.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3670.85 | 17.87 | 29.50 | 322.33 | 1365.37 | 18.97 | 20.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 9929.75 | 35.44 | 281.00 | 306.17 | 1907.75 | 20.87 | 46.33 | 287.33 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6268.75 | 35.30 | 228.83 | 255.83 | 2152.00 | 27.59 | 121.17 | 234.00 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5883.19 | 35.73 | 195.50 | 239.17 | 5278.73 | 38.86 | 208.00 | 212.00 |
Annual Sum or Average | 3472.67 | 0.50 | 4061.74 | 22.74 | 1186.83 | 3802.17 | 1699.18 | 22.02 | 690.17 | 3377.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1648.37 | 15.22 | 0.00 | 238.33 | 934.97 | 18.67 | 0.00 | 193.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 9929.75 | 37.27 | 281.00 | 389.17 | 5278.73 | 38.86 | 208.00 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1921.02 | 20.83 | 61.00 | 218.83 | 1081.80 | 23.47 | 82.50 | 156.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2748.14 | 23.56 | 80.67 | 243.50 | 1572.16 | 24.44 | 82.67 | 202.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2742.93 | 19.56 | 58.83 | 311.00 | 1573.37 | 22.36 | 67.83 | 252.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3732.71 | 21.83 | 80.67 | 338.83 | 1484.95 | 22.73 | 52.00 | 298.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3083.25 | 20.70 | 99.17 | 395.67 | 1656.44 | 22.27 | 72.83 | 351.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2751.81 | 19.99 | 80.67 | 385.00 | 1526.72 | 22.56 | 69.00 | 351.00 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2838.80 | 20.62 | 89.67 | 394.33 | 1524.37 | 22.31 | 67.00 | 354.67 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3815.01 | 22.74 | 128.17 | 372.00 | 1554.86 | 22.54 | 74.33 | 344.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3312.20 | 21.70 | 82.67 | 319.67 | 1400.81 | 21.70 | 49.00 | 281.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2932.14 | 22.59 | 91.17 | 291.00 | 1532.29 | 23.67 | 119.67 | 261.67 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 1976.15 | 21.37 | 72.00 | 242.17 | 1002.36 | 22.32 | 102.00 | 197.00 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1757.83 | 20.40 | 64.00 | 214.83 | 1064.76 | 23.86 | 86.33 | 152.17 |
Annual Sum or Average | 3472.67 | 0.51 | 2888.39 | 21.30 | 988.67 | 3726.83 | 1447.03 | 22.76 | 925.17 | 3203.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1757.83 | 19.56 | 58.83 | 214.83 | 1002.36 | 21.70 | 49.00 | 152.17 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3815.01 | 23.56 | 128.17 | 395.67 | 1656.44 | 24.44 | 119.67 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:50 | 610.05 | 12.00 | 0.00 | 203.17 | 372.54 | 15.62 | 0.00 | 112.17 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 662.22 | 13.10 | 0.00 | 226.67 | 429.58 | 16.87 | 0.00 | 157.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:30 | 878.25 | 14.16 | 0.00 | 306.50 | 547.36 | 17.66 | 0.00 | 229.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 989.37 | 15.16 | 0.00 | 342.50 | 619.08 | 18.71 | 0.00 | 291.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1274.51 | 15.68 | 3.00 | 401.83 | 732.94 | 19.17 | 36.67 | 359.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1434.27 | 18.89 | 62.83 | 398.83 | 807.83 | 21.83 | 76.67 | 371.50 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1411.94 | 15.75 | 0.00 | 405.00 | 799.49 | 21.32 | 63.33 | 368.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1165.35 | 15.59 | 0.00 | 377.50 | 703.57 | 19.10 | 8.17 | 346.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 906.57 | 14.77 | 0.00 | 317.83 | 572.84 | 18.32 | 0.00 | 263.83 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 821.11 | 14.41 | 0.00 | 286.67 | 530.65 | 18.03 | 0.00 | 239.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 680.84 | 12.61 | 0.00 | 230.83 | 406.92 | 16.20 | 0.00 | 146.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:50 | 492.02 | 10.88 | 0.00 | 190.33 | 310.14 | 14.69 | 0.00 | 84.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1004.96 | 14.78 | 65.83 | 3687.67 | 602.13 | 18.51 | 184.83 | 2970.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 492.02 | 10.88 | 0.00 | 190.33 | 310.14 | 14.69 | 0.00 | 84.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1434.27 | 18.89 | 62.83 | 405.00 | 807.83 | 21.83 | 76.67 | 371.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:39 | 1832.26 | 20.59 | 57.17 | 224.50 | 1070.77 | 23.70 | 77.17 | 158.33 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2128.09 | 21.01 | 57.00 | 242.83 | 1100.28 | 22.17 | 66.50 | 199.67 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3094.25 | 23.30 | 95.83 | 316.17 | 1729.64 | 24.40 | 88.83 | 265.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3526.51 | 21.53 | 76.83 | 337.83 | 1431.87 | 21.36 | 38.83 | 297.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:19 | 3325.77 | 18.75 | 69.17 | 393.50 | 1452.53 | 18.82 | 0.00 | 353.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3198.79 | 15.34 | 1.83 | 389.50 | 1714.46 | 19.00 | 1.50 | 347.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:00 | 3008.61 | 18.05 | 49.00 | 395.33 | 1596.77 | 19.13 | 4.50 | 352.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3842.09 | 19.86 | 86.33 | 371.17 | 1664.20 | 19.28 | 15.00 | 344.17 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3136.57 | 21.99 | 85.33 | 320.83 | 1615.29 | 23.01 | 66.50 | 280.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3358.68 | 23.74 | 109.33 | 302.17 | 1395.29 | 23.33 | 115.83 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1619.48 | 20.64 | 68.83 | 243.67 | 874.02 | 23.11 | 94.50 | 197.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:50 | 1513.49 | 20.77 | 67.50 | 218.00 | 819.98 | 21.77 | 65.50 | 155.33 |
Annual Sum or Average | 3472.67 | 0.50 | 2932.70 | 20.23 | 824.17 | 3755.50 | 1424.26 | 21.26 | 634.67 | 3223.83 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1513.49 | 15.34 | 1.83 | 218.00 | 819.98 | 18.82 | 0.00 | 155.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3842.09 | 23.74 | 109.33 | 395.33 | 1729.64 | 24.40 | 115.83 | 353.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106918E+10 | 21298.17 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17230810.44 | 21298.17 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106918E+10 | 21298.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.544643E+10 | 11345.93 | 02-JAN-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442315E+10 | 11967.78 | 06-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.294690E+10 | 10900.55 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147126E+10 | 10889.77 | 17-APR-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.409192E+09 | 10865.89 | 15-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1995274.97 | 2002.75 | 02-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14308595.24 | 6104.44 | 20-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262749E+09 | 10860.54 | 19-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191460E+10 | 10919.84 | 14-NOV-17:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350218E+10 | 10875.34 | 04-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.544643E+10 | 11967.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197113E+10 | 9006.75 | 03-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132233E+10 | 9006.75 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323555E+09 | 8968.05 | 09-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68812913.69 | 8941.04 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197741E+09 | 9000.42 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.730492E+09 | 9006.75 | 26-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197113E+10 | 9006.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373822E+10 | 8169.37 | 02-JAN-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308007E+10 | 8618.11 | 06-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106205E+10 | 7824.38 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206948E+09 | 7815.27 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17413.59 | 87.07 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490633E+09 | 7850.53 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160542E+10 | 7831.26 | 30-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373822E+10 | 8618.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212462E+10 | 9080.87 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154589E+10 | 9080.87 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337508E+09 | 9080.87 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73228610.99 | 9080.87 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.259152E+09 | 9080.87 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.838548E+09 | 9080.87 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.517895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212462E+10 | 9080.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.239822E+10 | 21737.87 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100055E+10 | 21737.87 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42837120.37 | 21737.87 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5030247.04 | 17704.68 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222160E+09 | 21737.87 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410649E+09 | 21737.87 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.239822E+10 | 21737.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223268E+10 | 12287.12 | 23-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140133E+10 | 12233.62 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331088E+09 | 12177.42 | 09-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72050431.64 | 12113.94 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370971E+09 | 12264.10 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107607E+10 | 12293.67 | 26-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.223268E+10 | 12293.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183751E+10 | 9726.28 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120706E+10 | 9726.28 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260388E+09 | 9726.28 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36843507.39 | 9726.28 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 306553.91 | 512.12 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341976E+09 | 9726.28 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.909350E+09 | 9726.28 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183751E+10 | 9726.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.350699E+10 | 8731.68 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264184E+10 | 9243.86 | 06-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.649073E+09 | 8680.64 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96301006.42 | 8659.16 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 830409.10 | 1230.49 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.747424E+09 | 8716.89 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187490E+10 | 8703.55 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.951735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350699E+10 | 9243.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207776E+10 | 9801.05 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147264E+10 | 9801.05 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303446E+09 | 9801.05 | 01-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54167098.56 | 9801.05 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 238766.97 | 214.79 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436549E+09 | 9801.05 | 20-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108011E+10 | 9801.05 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207776E+10 | 9801.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558517E+10 | 31019.14 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.388369E+10 | 30977.94 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.750888E+09 | 30908.86 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159091E+09 | 30957.45 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136465E+10 | 31013.86 | 27-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291768E+10 | 31011.87 | 26-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558517E+10 | 31019.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361689E+10 | 13627.01 | 24-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262440E+10 | 13598.90 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.943931E+09 | 13557.19 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286285E+09 | 13518.74 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3810433.95 | 6847.96 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19118385.50 | 11367.47 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.951620E+09 | 13632.58 | 27-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221356E+10 | 13586.44 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.361689E+10 | 13632.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.294574E+10 | 10977.94 | 19-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215776E+10 | 11005.32 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.668376E+09 | 10971.37 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171122E+09 | 10940.35 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19703.62 | 98.52 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17917318.93 | 8093.02 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.811616E+09 | 10966.60 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183634E+10 | 10986.85 | 30-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.860889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.294574E+10 | 11005.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.526019E+10 | 10169.54 | 31-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.432617E+10 | 10572.07 | 06-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149951E+10 | 10030.27 | 06-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346855E+09 | 10018.02 | 25-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2518531.80 | 5339.66 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46345375.09 | 9993.75 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164545E+10 | 10048.98 | 27-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351556E+10 | 10035.17 | 26-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.526019E+10 | 10572.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.317004E+10 | 11888.71 | 13-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250804E+10 | 11924.49 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.791740E+09 | 11887.72 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199056E+09 | 11854.10 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2295706.81 | 4002.49 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25504718.90 | 7509.70 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.978244E+09 | 11882.54 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206556E+10 | 11904.47 | 30-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317004E+10 | 11924.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117118E+11 | 23991.04 | 02-JAN-08:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117444E+11 | 23991.04 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.673771E+10 | 18020.58 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158166E+10 | 9557.25 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15258847.64 | 2797.44 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185921E+09 | 6393.83 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399812E+10 | 18624.26 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.899492E+10 | 18152.97 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117444E+11 | 23991.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117186E+11 | 23867.48 | 02-JAN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117194E+11 | 24525.24 | 06-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.684958E+10 | 19230.50 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188743E+10 | 9192.02 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22374882.22 | 3396.61 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325914E+09 | 6758.19 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.437799E+10 | 17428.21 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925294E+10 | 19679.05 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117194E+11 | 24525.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125539E+11 | 24216.11 | 31-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124254E+11 | 24216.11 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.719771E+10 | 19178.20 | 23-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214942E+10 | 11048.18 | 03-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39485392.32 | 4448.82 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1174386.46 | 580.75 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.478521E+09 | 9107.87 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.474687E+10 | 19176.16 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.982195E+10 | 20026.85 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.494144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125539E+11 | 24216.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.358215E+09 | 0.231420E+09 | 18922.49 | 27-MAR-16:00 | 14554.15 | 0.00 |
April | 0.00 | 0.00 | 0.355842E+10 | 0.314447E+10 | 32246.47 | 07-APR-15:30 | 32246.47 | 0.00 |
May | 0.00 | 0.00 | 0.138817E+11 | 0.116081E+11 | 71616.53 | 30-MAY-14:00 | 71616.53 | 0.00 |
June | 0.00 | 0.00 | 0.501625E+11 | 0.378721E+11 | 101899.77 | 19-JUN-05:02 | 69079.62 | 0.00 |
July | 0.00 | 0.00 | 0.734727E+11 | 0.527199E+11 | 108229.54 | 22-JUL-05:03 | 53810.84 | 0.00 |
August | 0.00 | 0.00 | 0.753914E+11 | 0.587986E+11 | 103343.94 | 17-AUG-05:03 | 62796.93 | 0.00 |
September | 0.00 | 0.00 | 0.388404E+11 | 0.308356E+11 | 102120.30 | 07-SEP-06:03 | 61989.67 | 0.00 |
October | 0.00 | 0.00 | 0.175115E+11 | 0.125054E+11 | 57802.60 | 04-OCT-15:10 | 45096.15 | 0.00 |
November | 0.00 | 0.00 | 0.398515E+09 | 0.332649E+09 | 9454.67 | 03-NOV-14:00 | 9454.67 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.273575E+12 | 0.208048E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.753914E+11 | 0.587986E+11 | 108229.54 | 71616.53 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.373809E+09 | 0.248991E+09 | 19326.45 | 27-MAR-16:00 | 15267.56 | 0.00 |
April | 0.00 | 0.00 | 0.384112E+10 | 0.342084E+10 | 42504.86 | 07-APR-14:05 | 42504.86 | 0.00 |
May | 0.00 | 0.00 | 0.147147E+11 | 0.125376E+11 | 77484.24 | 30-MAY-14:05 | 77484.24 | 0.00 |
June | 0.00 | 0.00 | 0.495330E+11 | 0.374748E+11 | 100613.79 | 19-JUN-05:02 | 64050.31 | 0.00 |
July | 0.00 | 0.00 | 0.711623E+11 | 0.507968E+11 | 106179.27 | 22-JUL-05:03 | 49829.87 | 0.00 |
August | 0.00 | 0.00 | 0.707378E+11 | 0.550798E+11 | 101643.22 | 17-AUG-05:03 | 56964.10 | 0.00 |
September | 0.00 | 0.00 | 0.349818E+11 | 0.274436E+11 | 83648.79 | 01-SEP-05:03 | 52705.15 | 0.00 |
October | 0.00 | 0.00 | 0.149665E+11 | 0.103677E+11 | 56884.97 | 04-OCT-14:05 | 44525.51 | 0.00 |
November | 0.00 | 0.00 | 0.340183E+09 | 0.283813E+09 | 8600.34 | 03-NOV-14:05 | 8600.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.260651E+12 | 0.197654E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.711623E+11 | 0.550798E+11 | 106179.27 | 77484.24 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 337898.54 | 295924.04 | 397.15 | 15-JAN-10:10 | 347.68 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.428828E+09 | 0.289857E+09 | 20262.84 | 27-MAR-16:00 | 15330.78 | 0.00 |
April | 0.00 | 0.00 | 0.417262E+10 | 0.371922E+10 | 46371.50 | 07-APR-14:30 | 46371.50 | 0.00 |
May | 0.00 | 0.00 | 0.155922E+11 | 0.133192E+11 | 85212.20 | 30-MAY-14:00 | 85212.20 | 0.00 |
June | 0.00 | 0.00 | 0.527624E+11 | 0.405314E+11 | 112587.76 | 19-JUN-05:02 | 71499.37 | 0.00 |
July | 0.00 | 0.00 | 0.760742E+11 | 0.554188E+11 | 119286.87 | 22-JUL-05:03 | 52770.70 | 0.00 |
August | 0.00 | 0.00 | 0.750820E+11 | 0.593827E+11 | 113103.77 | 05-AUG-05:03 | 65981.61 | 0.00 |
September | 0.00 | 0.00 | 0.355855E+11 | 0.277732E+11 | 82517.67 | 01-SEP-14:20 | 82517.67 | 0.00 |
October | 0.00 | 0.00 | 0.144058E+11 | 0.991882E+10 | 57941.53 | 04-OCT-13:50 | 47326.83 | 0.00 |
November | 0.00 | 0.00 | 0.298195E+09 | 0.234581E+09 | 7460.33 | 04-NOV-12:30 | 5689.91 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.274402E+12 | 0.210588E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.760742E+11 | 0.593827E+11 | 119286.87 | 85212.20 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 1879.08 | 6593.62 | 31-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1907.50 | 6604.51 | 06-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1989.97 | 6534.03 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1770.55 | 6268.40 | 03-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1718.30 | 5902.44 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1644.33 | 5465.06 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1436.96 | 5112.98 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1558.74 | 5007.28 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1498.02 | 5228.75 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1586.43 | 5640.94 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1725.23 | 6049.40 | 29-NOV-12:06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1758.95 | 6385.20 | 28-DEC-12:08 |
Annual Sum or Average | 0.00 | 1705.03 | ||||
Minimum of Months | 0.00 | 0.00 | 1436.96 | 5007.28 | ||
Maximum of Months | 0.00 | 0.00 | 1989.97 | 6604.51 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109908E+10 | 0.29 | 2175.73 | 02-JAN-06:23 | 0.75 |
February | 0.947694E+09 | 0.28 | 2175.73 | 06-FEB-07:01 | 0.75 |
March | 0.112451E+10 | 0.29 | 1363.51 | 01-MAR-06:11 | 0.60 |
April | 0.134428E+10 | 0.29 | 3488.50 | 10-APR-15:10 | 0.98 |
May | 0.220270E+10 | 0.36 | 7450.39 | 30-MAY-12:10 | 1.55 |
June | 0.381051E+10 | 0.47 | 9314.96 | 19-JUN-05:02 | 1.78 |
July | 0.494625E+10 | 0.52 | 9314.96 | 08-JUL-06:03 | 1.78 |
August | 0.552056E+10 | 0.57 | 9314.96 | 02-AUG-06:03 | 1.78 |
September | 0.351084E+10 | 0.44 | 9314.96 | 05-SEP-06:03 | 1.78 |
October | 0.266762E+10 | 0.38 | 5627.37 | 05-OCT-16:00 | 1.29 |
November | 0.119828E+10 | 0.28 | 2596.34 | 02-NOV-14:10 | 0.82 |
December | 0.983713E+09 | 0.27 | 1363.51 | 02-DEC-06:01 | 0.60 |
Annual Sum or Average | 0.293561E+11 | 0.37 | |||
Minimum of Months | 0.947694E+09 | 0.27 | 1363.51 | 0.60 | |
Maximum of Months | 0.552056E+10 | 0.57 | 9314.96 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108884E+10 | 0.30 | 2292.24 | 02-JAN-05:01 | 0.79 |
February | 0.951569E+09 | 0.29 | 2292.24 | 06-FEB-06:01 | 0.79 |
March | 0.113487E+10 | 0.29 | 2292.24 | 13-MAR-06:01 | 0.79 |
April | 0.138612E+10 | 0.31 | 4806.59 | 10-APR-14:05 | 1.22 |
May | 0.236772E+10 | 0.38 | 8922.18 | 30-MAY-06:03 | 1.78 |
June | 0.387689E+10 | 0.48 | 8922.18 | 19-JUN-05:02 | 1.78 |
July | 0.481974E+10 | 0.53 | 8922.18 | 03-JUL-06:03 | 1.78 |
August | 0.535355E+10 | 0.57 | 8922.18 | 02-AUG-06:03 | 1.78 |
September | 0.301333E+10 | 0.42 | 8922.18 | 05-SEP-06:03 | 1.78 |
October | 0.211460E+10 | 0.35 | 5489.09 | 04-OCT-15:40 | 1.31 |
November | 0.102865E+10 | 0.27 | 2410.04 | 03-NOV-14:05 | 0.81 |
December | 0.972751E+09 | 0.27 | 2292.24 | 07-DEC-07:01 | 0.79 |
Annual Sum or Average | 0.281086E+11 | 0.37 | |||
Minimum of Months | 0.951569E+09 | 0.27 | 2292.24 | 0.79 | |
Maximum of Months | 0.535355E+10 | 0.57 | 8922.18 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138281E+10 | 0.37 | 2286.89 | 01-JAN-01:22 | 0.73 |
February | 0.118258E+10 | 0.35 | 2286.89 | 01-FEB-06:01 | 0.73 |
March | 0.122629E+10 | 0.32 | 2286.89 | 01-MAR-06:11 | 0.72 |
April | 0.140631E+10 | 0.31 | 4217.77 | 07-APR-14:50 | 1.02 |
May | 0.230285E+10 | 0.37 | 9023.54 | 30-MAY-14:10 | 1.63 |
June | 0.374312E+10 | 0.45 | 10375.91 | 19-JUN-05:02 | 1.78 |
July | 0.469814E+10 | 0.49 | 10375.91 | 10-JUL-04:02 | 1.78 |
August | 0.520256E+10 | 0.52 | 9655.36 | 14-AUG-14:40 | 1.70 |
September | 0.274826E+10 | 0.39 | 7920.64 | 05-SEP-06:03 | 1.50 |
October | 0.185705E+10 | 0.33 | 5267.91 | 04-OCT-15:30 | 1.16 |
November | 0.110421E+10 | 0.30 | 2286.89 | 20-NOV-06:01 | 0.73 |
December | 0.113841E+10 | 0.31 | 2286.89 | 02-DEC-06:01 | 0.73 |
Annual Sum or Average | 0.279926E+11 | 0.38 | |||
Minimum of Months | 0.110421E+10 | 0.30 | 2286.89 | 0.72 | |
Maximum of Months | 0.520256E+10 | 0.52 | 10375.91 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 56.82 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.36 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 56.30 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.01 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.35 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 56.05 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.59 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.66 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.29 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.72 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.85 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 55.34 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.34 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.72 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.31 | 56.31 | 1879.08 | 6593.62 | 31-JAN-12:06 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.73 | 56.73 | 1907.50 | 6604.51 | 06-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.10 | 57.10 | 1989.97 | 6534.03 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.70 | 56.70 | 1770.55 | 6268.40 | 03-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.85 | 57.85 | 1718.30 | 5902.44 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.59 | 57.59 | 1644.33 | 5465.06 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.01 | 57.01 | 1436.96 | 5112.98 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.98 | 56.98 | 1558.74 | 5007.28 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.61 | 56.61 | 1498.02 | 5228.75 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.59 | 55.59 | 1586.43 | 5640.94 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.34 | 57.34 | 1725.23 | 6049.40 | 29-NOV-12:06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.03 | 56.03 | 1758.95 | 6385.20 | 28-DEC-12:08 |
Annual Sum or Average | 0.00 | 1705.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.59 | 55.59 | 1436.96 | 5007.28 | ||
Maximum of Months | 0.00 | 0.00 | 57.85 | 57.85 | 1989.97 | 6604.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154487E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.113364E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.588526E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.405209E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.600985E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.154874E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.221578E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.234258E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.124983E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.698481E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.416756E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.766035E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.135114E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.405209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.234258E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131420E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.867500E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.281568E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.259711E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.594408E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.154008E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.214750E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.221501E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.111368E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.559130E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.323924E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.632382E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.118491E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.259711E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.221501E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.219609E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166826E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.599033E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.359737E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.611996E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.160963E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.225709E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.231029E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110894E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.535271E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.693672E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.136871E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.153187E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.359737E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.231029E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109908E+10 | 0.00 | 0.260613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.947694E+09 | 0.00 | 0.221331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112451E+10 | 0.358215E+09 | 0.114077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134428E+10 | 0.355842E+10 | 0.340191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220270E+10 | 0.138817E+11 | 0.424469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.381051E+10 | 0.501625E+11 | 1995274.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.494625E+10 | 0.734727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.552056E+10 | 0.753914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.351084E+10 | 0.388404E+11 | 14308595.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266762E+10 | 0.175115E+11 | 0.448670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119828E+10 | 0.398515E+09 | 0.686024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.983713E+09 | 0.00 | 0.156716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293561E+11 | 0.273575E+12 | 0.864253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.947694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.552056E+10 | 0.753914E+11 | 0.260613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108884E+10 | 0.00 | 0.237717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.951569E+09 | 0.00 | 0.194428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113487E+10 | 0.373809E+09 | 0.843641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138612E+10 | 0.384112E+10 | 0.215182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236772E+10 | 0.147147E+11 | 22374882.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387689E+10 | 0.495330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.481974E+10 | 0.711623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.535355E+10 | 0.707378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301333E+10 | 0.349818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211460E+10 | 0.149665E+11 | 0.327290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102865E+10 | 0.340183E+09 | 0.649707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.972751E+09 | 0.00 | 0.146040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281086E+11 | 0.260651E+12 | 0.752535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.951569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.535355E+10 | 0.711623E+11 | 0.237717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138281E+10 | 337898.54 | 0.331319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118258E+10 | 0.00 | 0.279254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122629E+10 | 0.428828E+09 | 0.118522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140631E+10 | 0.417262E+10 | 0.331183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230285E+10 | 0.155922E+11 | 48129768.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.374312E+10 | 0.527624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.469814E+10 | 0.760742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.520256E+10 | 0.750820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274826E+10 | 0.355855E+11 | 1174386.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185705E+10 | 0.144058E+11 | 0.587407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110421E+10 | 0.298195E+09 | 0.104985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113841E+10 | 0.00 | 0.223707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279926E+11 | 0.274402E+12 | 0.109727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.520256E+10 | 0.760742E+11 | 0.331319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.947694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112451E+10 | 0.00 | 0.00 | 0.00 | 90739829.19 | 0.467001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134428E+10 | 0.00 | 0.00 | 0.00 | 0.887558E+09 | 0.182025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220270E+10 | 0.00 | 0.00 | 0.00 | 0.339794E+10 | 0.409210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.381051E+10 | 0.00 | 0.00 | 0.00 | 0.116748E+11 | 1995274.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.494625E+10 | 0.00 | 0.00 | 0.00 | 0.172115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.552056E+10 | 0.00 | 0.00 | 0.00 | 0.179052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.351084E+10 | 0.00 | 0.00 | 0.00 | 0.897319E+10 | 14308595.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266762E+10 | 0.00 | 0.00 | 0.00 | 0.405444E+10 | 0.262749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119828E+10 | 0.00 | 0.00 | 0.00 | 0.107155E+09 | 0.286212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.983713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293561E+11 | 0.00 | 0.00 | 0.00 | 0.643026E+11 | 0.414556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.947694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.552056E+10 | 0.00 | 0.00 | 0.00 | 0.179052E+11 | 0.143496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.951569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113487E+10 | 0.00 | 0.00 | 0.00 | 93979567.83 | 0.158683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138612E+10 | 0.00 | 0.00 | 0.00 | 0.946595E+09 | 0.264392E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236772E+10 | 0.00 | 0.00 | 0.00 | 0.357636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387689E+10 | 0.00 | 0.00 | 0.00 | 0.115239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.481974E+10 | 0.00 | 0.00 | 0.00 | 0.166552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.535355E+10 | 0.00 | 0.00 | 0.00 | 0.167966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301333E+10 | 0.00 | 0.00 | 0.00 | 0.812344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211460E+10 | 0.00 | 0.00 | 0.00 | 0.347532E+10 | 1375729.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102865E+10 | 0.00 | 0.00 | 0.00 | 91509188.59 | 0.211908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.972751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281086E+11 | 0.00 | 0.00 | 0.00 | 0.612829E+11 | 0.290993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.951569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.535355E+10 | 0.00 | 0.00 | 0.00 | 0.167966E+11 | 0.120532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138281E+10 | 0.00 | 0.00 | 0.00 | 95052.55 | 0.205780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122629E+10 | 0.00 | 0.00 | 0.00 | 0.109603E+09 | 0.465444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140631E+10 | 0.00 | 0.00 | 0.00 | 0.102866E+10 | 0.116241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230285E+10 | 0.00 | 0.00 | 0.00 | 0.380846E+10 | 8644376.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.374312E+10 | 0.00 | 0.00 | 0.00 | 0.123532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.469814E+10 | 0.00 | 0.00 | 0.00 | 0.178727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.520256E+10 | 0.00 | 0.00 | 0.00 | 0.179004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274826E+10 | 0.00 | 0.00 | 0.00 | 0.834110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185705E+10 | 0.00 | 0.00 | 0.00 | 0.338677E+10 | 0.108886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110421E+10 | 0.00 | 0.00 | 0.00 | 80926813.86 | 0.575158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279926E+11 | 0.00 | 0.00 | 0.00 | 0.648819E+11 | 0.603128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.520256E+10 | 0.00 | 0.00 | 0.00 | 0.179004E+11 | 0.205780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128503E+11 | 0.00 | 0.00 | 245932.53 | 0.00 | 0.880775E+09 | 0.607272E+09 | 0.00 | 0.28 |
February | 0.123034E+11 | 0.00 | 0.00 | 1176864.72 | 0.00 | 6271098.86 | 0.190348E+10 | 0.00 | 0.29 |
March | 0.671720E+10 | 0.00 | 0.00 | 11788360.99 | 0.00 | 0.00 | 0.847342E+10 | 0.00 | 0.35 |
April | 0.309077E+10 | 7573337.43 | 0.00 | 19202609.78 | 0.00 | 0.00 | 0.102595E+11 | 0.00 | 0.46 |
May | 0.937509E+09 | 90014381.03 | 0.00 | 29393315.33 | 0.00 | 0.00 | 0.126511E+11 | 0.00 | 0.74 |
June | 0.256165E+09 | 0.291694E+10 | 0.00 | 13305808.56 | 41409329.44 | 0.00 | 0.283543E+10 | 0.00 | 0.56 |
July | 8555214.62 | 0.736621E+10 | 0.00 | 1121449.25 | 0.107948E+09 | 0.00 | 0.114915E+09 | 0.00 | 0.27 |
August | 92615608.52 | 0.583407E+10 | 0.00 | 11120025.70 | 89443502.37 | 0.00 | 0.136859E+10 | 0.00 | 0.47 |
September | 0.630676E+09 | 0.181270E+10 | 0.00 | 21209125.74 | 17547277.45 | 0.00 | 0.648102E+10 | 0.00 | 0.65 |
October | 0.117690E+10 | 0.141419E+09 | 0.00 | 32282716.18 | 0.00 | 0.00 | 0.120803E+11 | 0.00 | 0.69 |
November | 0.455783E+10 | 0.00 | 0.00 | 16538134.67 | 0.00 | 0.00 | 0.102532E+11 | 0.00 | 0.41 |
December | 0.934678E+10 | 0.00 | 0.00 | 4380455.14 | 0.00 | 0.00 | 0.482084E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.519687E+11 | 0.181689E+11 | 0.00 | 0.161765E+09 | 0.256349E+09 | 0.887046E+09 | 0.718491E+11 | 0.00 | 0.46 |
Minimum of Months | 8555214.62 | 0.00 | 0.00 | 245932.53 | 0.00 | 0.00 | 0.114915E+09 | 0.00 | 0.27 |
Maximum of Months | 0.128503E+11 | 0.736621E+10 | 0.00 | 32282716.18 | 0.107948E+09 | 0.880775E+09 | 0.126511E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173106E+10 | 0.00 | 0.00 | 0.28 |
February | 0.130524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676543E+09 | 0.00 | 0.00 | 0.28 |
March | 0.124941E+11 | 0.00 | 0.00 | 865042.38 | 0.00 | 14793045.30 | 0.111649E+10 | 0.00 | 0.32 |
April | 0.605945E+10 | 4117452.65 | 0.00 | 7649960.66 | 0.00 | 776460.75 | 0.507489E+10 | 0.00 | 0.39 |
May | 0.235607E+10 | 83354547.62 | 0.00 | 18024187.71 | 0.00 | 0.00 | 0.831137E+10 | 0.00 | 0.58 |
June | 0.326289E+09 | 0.248357E+10 | 0.00 | 10047512.51 | 39647456.45 | 0.00 | 0.213059E+10 | 0.00 | 0.45 |
July | 8154636.57 | 0.659866E+10 | 0.00 | 936501.48 | 0.106449E+09 | 0.00 | 94255108.99 | 0.00 | 0.24 |
August | 0.143509E+09 | 0.531621E+10 | 0.00 | 8218742.86 | 89202250.44 | 0.00 | 0.100119E+10 | 0.00 | 0.40 |
September | 0.922226E+09 | 0.162588E+10 | 0.00 | 13441736.11 | 18502922.97 | 0.00 | 0.432124E+10 | 0.00 | 0.51 |
October | 0.249804E+10 | 0.138399E+09 | 0.00 | 16397265.64 | 2299065.19 | 0.00 | 0.699990E+10 | 0.00 | 0.50 |
November | 0.921152E+10 | 0.00 | 0.00 | 3307960.41 | 0.00 | 67553789.47 | 0.245928E+10 | 0.00 | 0.32 |
December | 0.132471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100542E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.726552E+11 | 0.162502E+11 | 0.00 | 78888909.76 | 0.256101E+09 | 0.259127E+10 | 0.315092E+11 | 0.00 | 0.38 |
Minimum of Months | 8154636.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.132471E+11 | 0.659866E+10 | 0.00 | 18024187.71 | 0.106449E+09 | 0.173106E+10 | 0.831137E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.920753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407364E+10 | 0.00 | 0.00 | 0.27 |
February | 0.990507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304276E+10 | 0.00 | 0.00 | 0.28 |
March | 0.120397E+11 | 0.00 | 0.00 | 598323.81 | 0.00 | 0.438987E+09 | 0.659590E+09 | 0.00 | 0.32 |
April | 0.669025E+10 | 1786030.73 | 0.00 | 6630774.74 | 333799.76 | 44114712.10 | 0.403933E+10 | 0.00 | 0.39 |
May | 0.302156E+10 | 70461945.12 | 0.00 | 16441192.38 | 0.00 | 0.00 | 0.781927E+10 | 0.00 | 0.59 |
June | 0.433603E+09 | 0.239731E+10 | 0.00 | 9956232.27 | 36184091.01 | 0.00 | 0.217419E+10 | 0.00 | 0.46 |
July | 14974360.04 | 0.644935E+10 | 0.00 | 1083155.74 | 98559232.44 | 0.00 | 88857080.05 | 0.00 | 0.25 |
August | 0.166163E+09 | 0.515778E+10 | 0.00 | 8472907.59 | 83213999.98 | 0.00 | 0.953750E+09 | 0.00 | 0.42 |
September | 0.145007E+10 | 0.159801E+10 | 0.00 | 10680113.29 | 18466020.80 | 0.00 | 0.342877E+10 | 0.00 | 0.49 |
October | 0.370372E+10 | 90356950.32 | 0.00 | 10434907.95 | 1033256.69 | 0.00 | 0.474135E+10 | 0.00 | 0.47 |
November | 0.880898E+10 | 0.00 | 0.00 | 1137235.77 | 0.00 | 0.833095E+09 | 0.117499E+10 | 0.00 | 0.31 |
December | 0.105301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192559E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.659718E+11 | 0.157651E+11 | 0.00 | 65434843.55 | 0.237790E+09 | 0.103582E+11 | 0.250801E+11 | 0.00 | 0.38 |
Minimum of Months | 14974360.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.120397E+11 | 0.644935E+10 | 0.00 | 16441192.38 | 98559232.44 | 0.407364E+10 | 0.781927E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.366878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274331E+10 | 0.00 | 0.00 | 0.30 |
February | 0.460906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254516E+10 | 0.00 | 0.00 | 0.30 |
March | 0.168111E+10 | 0.00 | 0.00 | 36016.55 | 0.00 | 0.108000E+10 | 46465647.64 | 0.00 | 0.32 |
April | 0.149557E+10 | 544500.04 | 0.00 | 1209052.70 | 0.00 | 0.241803E+09 | 0.566087E+09 | 0.00 | 0.41 |
May | 0.786163E+09 | 22871048.29 | 0.00 | 4193265.15 | 0.00 | 536078.98 | 0.177729E+10 | 0.00 | 0.69 |
June | 96659211.65 | 0.780675E+09 | 0.00 | 2876221.85 | 8149130.59 | 0.00 | 0.603888E+09 | 0.00 | 0.64 |
July | 2409581.77 | 0.216543E+10 | 0.00 | 423610.08 | 20625098.83 | 0.00 | 25826124.65 | 0.00 | 0.39 |
August | 40413834.77 | 0.171589E+10 | 0.00 | 2356897.21 | 18362193.82 | 0.00 | 0.251949E+09 | 0.00 | 0.58 |
September | 0.396572E+09 | 0.426343E+09 | 0.00 | 2374998.30 | 6521325.67 | 0.00 | 0.703399E+09 | 0.00 | 0.56 |
October | 0.105068E+10 | 20489017.18 | 0.00 | 1629827.08 | 2238532.12 | 35998774.98 | 0.623163E+09 | 0.00 | 0.47 |
November | 0.127452E+10 | 0.00 | 0.00 | 31042.23 | 0.00 | 0.101575E+10 | 28378520.47 | 0.00 | 0.31 |
December | 0.502853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220904E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.815474E+10 | 0.513224E+10 | 0.00 | 15130931.15 | 55896281.03 | 0.987159E+10 | 0.462645E+10 | 0.00 | 0.44 |
Minimum of Months | 2409581.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.168111E+10 | 0.216543E+10 | 0.00 | 4193265.15 | 20625098.83 | 0.274331E+10 | 0.177729E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.459522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146338E+10 | 0.00 | 0.00 | 0.29 |
February | 0.646265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117380E+10 | 0.00 | 0.00 | 0.29 |
March | 0.109452E+10 | 0.00 | 0.00 | 658215.78 | 0.00 | 0.420725E+09 | 0.387453E+09 | 0.00 | 0.35 |
April | 0.710372E+09 | 1112705.78 | 0.00 | 2531261.76 | 0.00 | 0.119052E+09 | 0.123168E+10 | 0.00 | 0.61 |
May | 0.382621E+09 | 23898340.87 | 0.00 | 5573498.44 | 0.00 | 0.00 | 0.222121E+10 | 0.00 | 1.09 |
June | 38145748.92 | 0.637740E+09 | 0.00 | 3345703.47 | 5163243.47 | 0.00 | 0.725742E+09 | 0.00 | 0.92 |
July | 800853.20 | 0.179810E+10 | 0.00 | 489713.92 | 13067947.02 | 0.00 | 36848533.31 | 0.00 | 0.54 |
August | 17222475.57 | 0.154459E+10 | 0.00 | 2742800.40 | 11134473.71 | 0.00 | 0.322818E+09 | 0.00 | 0.91 |
September | 0.174713E+09 | 0.348669E+09 | 0.00 | 3509675.04 | 4043021.02 | 0.00 | 0.945067E+09 | 0.00 | 0.85 |
October | 0.453963E+09 | 18434485.10 | 0.00 | 2931331.34 | 529103.65 | 10417652.80 | 0.110374E+10 | 0.00 | 0.71 |
November | 0.832672E+09 | 0.00 | 0.00 | 277954.11 | 0.00 | 0.454263E+09 | 0.212133E+09 | 0.00 | 0.32 |
December | 0.651636E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105779E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.546245E+10 | 0.437254E+10 | 0.00 | 22060154.28 | 33937788.87 | 0.469943E+10 | 0.718669E+10 | 0.00 | 0.60 |
Minimum of Months | 800853.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.109452E+10 | 0.179810E+10 | 0.00 | 5573498.44 | 13067947.02 | 0.146338E+10 | 0.222121E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.866678E+09 | 0.00 | 0.00 | 1034428.45 | 0.00 | 0.170201E+10 | 0.727161E+09 | 0.00 | 0.32 |
February | 0.999013E+09 | 0.00 | 0.00 | 1512545.01 | 0.00 | 0.135183E+10 | 0.106975E+10 | 0.00 | 0.35 |
March | 0.145352E+10 | 0.00 | 0.00 | 4096150.58 | 0.00 | 0.552240E+09 | 0.223602E+10 | 0.00 | 0.51 |
April | 0.116977E+10 | 1441504.12 | 0.00 | 4550416.74 | 0.00 | 0.192561E+09 | 0.211954E+10 | 0.00 | 0.66 |
May | 0.735020E+09 | 28746430.58 | 0.00 | 6404137.45 | 0.00 | 2312065.97 | 0.260768E+10 | 0.00 | 0.90 |
June | 0.109326E+09 | 0.881386E+09 | 0.00 | 3491850.17 | 8250310.69 | 0.00 | 0.715832E+09 | 0.00 | 0.73 |
July | 4397754.68 | 0.247943E+10 | 0.00 | 581777.54 | 20920233.73 | 0.00 | 25493577.62 | 0.00 | 0.44 |
August | 37800034.70 | 0.226804E+10 | 0.00 | 3871801.43 | 17990889.77 | 0.00 | 0.384398E+09 | 0.00 | 0.83 |
September | 0.274728E+09 | 0.631606E+09 | 0.00 | 7090947.56 | 6124333.61 | 0.00 | 0.183098E+10 | 0.00 | 1.02 |
October | 0.555596E+09 | 57580024.04 | 0.00 | 9181666.41 | 42458.98 | 12726381.13 | 0.361479E+10 | 0.00 | 1.14 |
November | 0.112968E+10 | 0.00 | 0.00 | 2973444.87 | 0.00 | 0.537025E+09 | 0.166558E+10 | 0.00 | 0.49 |
December | 0.978944E+09 | 0.00 | 0.00 | 1292934.38 | 0.00 | 0.129651E+10 | 0.832037E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.831448E+10 | 0.634823E+10 | 0.00 | 46082100.58 | 53328226.78 | 0.564721E+10 | 0.178293E+11 | 0.00 | 0.64 |
Minimum of Months | 4397754.68 | 0.00 | 0.00 | 581777.54 | 0.00 | 0.00 | 25493577.62 | 0.00 | 0.32 |
Maximum of Months | 0.145352E+10 | 0.247943E+10 | 0.00 | 9181666.41 | 20920233.73 | 0.170201E+10 | 0.361479E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.416150E+09 | 0.00 | 0.00 | 18892.96 | 0.00 | 0.152952E+10 | 27551825.15 | 0.00 | 0.30 |
February | 0.486472E+09 | 0.00 | 0.00 | 94308.48 | 0.00 | 0.134754E+10 | 0.100401E+09 | 0.00 | 0.31 |
March | 0.973600E+09 | 0.00 | 0.00 | 1150051.21 | 0.00 | 0.512066E+09 | 0.696914E+09 | 0.00 | 0.41 |
April | 0.788128E+09 | 416777.22 | 0.00 | 2717103.26 | 0.00 | 0.135594E+09 | 0.126497E+10 | 0.00 | 0.65 |
May | 0.398619E+09 | 22200702.36 | 0.00 | 5285802.97 | 0.00 | 1431723.30 | 0.203491E+10 | 0.00 | 1.05 |
June | 59328283.60 | 0.680857E+09 | 0.00 | 2943914.15 | 3720027.29 | 0.00 | 0.569551E+09 | 0.00 | 0.92 |
July | 2715553.33 | 0.184582E+10 | 0.00 | 543819.02 | 6229646.33 | 0.00 | 17276836.28 | 0.00 | 0.52 |
August | 24460553.23 | 0.161905E+10 | 0.00 | 2365436.77 | 6585498.19 | 0.00 | 0.220766E+09 | 0.00 | 0.88 |
September | 0.211847E+09 | 0.391055E+09 | 0.00 | 3274171.30 | 3138454.49 | 0.00 | 0.811776E+09 | 0.00 | 0.84 |
October | 0.533731E+09 | 29058389.22 | 0.00 | 2791410.98 | 26916.78 | 18001485.78 | 0.110818E+10 | 0.00 | 0.74 |
November | 0.769732E+09 | 0.00 | 0.00 | 323230.07 | 0.00 | 0.568765E+09 | 0.228634E+09 | 0.00 | 0.34 |
December | 0.464666E+09 | 0.00 | 0.00 | 5576.57 | 0.00 | 0.124609E+10 | 13936076.44 | 0.00 | 0.29 |
Annual Sum or Average | 0.512945E+10 | 0.458846E+10 | 0.00 | 21513717.75 | 19700543.09 | 0.535901E+10 | 0.709486E+10 | 0.00 | 0.61 |
Minimum of Months | 2715553.33 | 0.00 | 0.00 | 5576.57 | 0.00 | 0.00 | 13936076.44 | 0.00 | 0.29 |
Maximum of Months | 0.973600E+09 | 0.184582E+10 | 0.00 | 5285802.97 | 6585498.19 | 0.152952E+10 | 0.203491E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.507710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269276E+10 | 0.00 | 0.00 | 0.29 |
February | 0.524172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262799E+10 | 0.00 | 0.00 | 0.30 |
March | 0.193939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100882E+10 | 0.00 | 0.00 | 0.32 |
April | 0.182910E+10 | 448129.97 | 0.00 | 227176.57 | 647262.64 | 0.153318E+09 | 0.142327E+09 | 0.00 | 0.34 |
May | 0.116107E+10 | 18052061.46 | 0.00 | 1795570.65 | 0.00 | 0.00 | 0.747702E+09 | 0.00 | 0.50 |
June | 0.101114E+09 | 0.612550E+09 | 0.00 | 1924773.51 | 9374680.66 | 0.00 | 0.411802E+09 | 0.00 | 0.48 |
July | 2428602.85 | 0.177123E+10 | 0.00 | 222316.99 | 22697205.53 | 0.00 | 21769087.98 | 0.00 | 0.30 |
August | 44334839.64 | 0.147645E+10 | 0.00 | 2003760.99 | 18806370.45 | 0.00 | 0.220324E+09 | 0.00 | 0.48 |
September | 0.337757E+09 | 0.366389E+09 | 0.00 | 2544163.47 | 3689486.56 | 0.00 | 0.772022E+09 | 0.00 | 0.53 |
October | 0.102696E+10 | 25911421.41 | 0.00 | 2054470.36 | 68270.33 | 0.00 | 0.808263E+09 | 0.00 | 0.47 |
November | 0.185412E+10 | 0.00 | 0.00 | 65293.53 | 0.00 | 0.512208E+09 | 0.113247E+09 | 0.00 | 0.31 |
December | 0.124044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168671E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.105686E+11 | 0.427103E+10 | 0.00 | 10837526.07 | 55283276.16 | 0.868180E+10 | 0.323746E+10 | 0.00 | 0.38 |
Minimum of Months | 2428602.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.193939E+10 | 0.177123E+10 | 0.00 | 2544163.47 | 22697205.53 | 0.269276E+10 | 0.808263E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.597329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141424E+10 | 0.00 | 0.00 | 0.29 |
February | 0.746052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119683E+10 | 0.00 | 0.00 | 0.29 |
March | 0.143955E+10 | 0.00 | 0.00 | 217839.46 | 0.00 | 0.308954E+09 | 0.162255E+09 | 0.00 | 0.33 |
April | 0.921239E+09 | 1921327.21 | 0.00 | 1583645.80 | 0.00 | 51077861.06 | 0.748467E+09 | 0.00 | 0.48 |
May | 0.482362E+09 | 21827106.65 | 0.00 | 3655573.77 | 0.00 | 0.00 | 0.145647E+10 | 0.00 | 0.83 |
June | 32012468.80 | 0.541061E+09 | 0.00 | 2595548.14 | 5774153.37 | 0.00 | 0.574117E+09 | 0.00 | 0.75 |
July | 883769.30 | 0.157900E+10 | 0.00 | 287688.97 | 14482408.22 | 0.00 | 31423134.11 | 0.00 | 0.45 |
August | 17297278.67 | 0.142370E+10 | 0.00 | 2476420.61 | 11947787.14 | 0.00 | 0.303572E+09 | 0.00 | 0.81 |
September | 0.115751E+09 | 0.328037E+09 | 0.00 | 3657757.34 | 2343950.43 | 0.00 | 0.105537E+10 | 0.00 | 0.84 |
October | 0.377790E+09 | 25359641.36 | 0.00 | 3909117.15 | 0.00 | 0.00 | 0.145416E+10 | 0.00 | 0.77 |
November | 0.103884E+10 | 0.00 | 0.00 | 751920.07 | 0.00 | 0.231565E+09 | 0.430730E+09 | 0.00 | 0.34 |
December | 0.110101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762081E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.687011E+10 | 0.392090E+10 | 0.00 | 19135511.31 | 34548299.15 | 0.396474E+10 | 0.621657E+10 | 0.00 | 0.54 |
Minimum of Months | 883769.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.143955E+10 | 0.157900E+10 | 0.00 | 3909117.15 | 14482408.22 | 0.141424E+10 | 0.145647E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.822412E+09 | 0.00 | 0.00 | 1995.22 | 0.00 | 0.329622E+10 | 9698594.01 | 0.00 | 0.38 |
February | 0.941523E+09 | 0.00 | 0.00 | 41109.94 | 0.00 | 0.303907E+10 | 58576587.37 | 0.00 | 0.38 |
March | 0.158831E+10 | 0.00 | 0.00 | 499924.89 | 0.00 | 0.185012E+10 | 0.321025E+09 | 0.00 | 0.40 |
April | 0.139810E+10 | 3639723.53 | 0.00 | 1272926.79 | 0.00 | 0.746654E+09 | 0.521484E+09 | 0.00 | 0.46 |
May | 0.120007E+10 | 27687420.46 | 0.00 | 1920860.48 | 163956.99 | 0.176904E+09 | 0.742057E+09 | 0.00 | 0.57 |
June | 0.147472E+09 | 0.760842E+09 | 0.00 | 1908149.30 | 22360007.69 | 522121.36 | 0.377349E+09 | 0.00 | 0.54 |
July | 6994940.87 | 0.235760E+10 | 0.00 | 260111.93 | 26622975.81 | 0.00 | 16021643.29 | 0.00 | 0.39 |
August | 62438177.10 | 0.238680E+10 | 0.00 | 3158386.46 | 22154020.30 | 0.00 | 0.288111E+09 | 0.00 | 0.75 |
September | 0.276284E+09 | 0.614843E+09 | 0.00 | 5954462.61 | 8452402.13 | 9165073.29 | 0.154831E+10 | 0.00 | 0.91 |
October | 0.532971E+09 | 72508777.29 | 0.00 | 8195856.25 | 0.00 | 0.116613E+09 | 0.302559E+10 | 0.00 | 1.02 |
November | 0.149695E+10 | 0.00 | 0.00 | 1605768.21 | 0.00 | 0.103985E+10 | 0.992223E+09 | 0.00 | 0.47 |
December | 0.129596E+10 | 0.00 | 0.00 | 195261.17 | 0.00 | 0.227363E+10 | 0.182348E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.976948E+10 | 0.622392E+10 | 0.00 | 25014813.24 | 79753362.93 | 0.125488E+11 | 0.808279E+10 | 0.00 | 0.55 |
Minimum of Months | 6994940.87 | 0.00 | 0.00 | 1995.22 | 0.00 | 0.00 | 9698594.01 | 0.00 | 0.36 |
Maximum of Months | 0.158831E+10 | 0.238680E+10 | 0.00 | 8195856.25 | 26622975.81 | 0.329622E+10 | 0.302559E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.559297E+09 | 0.00 | 0.00 | 332.82 | 0.00 | 0.147697E+10 | 2358424.07 | 0.00 | 0.30 |
February | 0.630627E+09 | 0.00 | 0.00 | 15012.30 | 0.00 | 0.133346E+10 | 27222203.27 | 0.00 | 0.30 |
March | 0.135786E+10 | 0.00 | 0.00 | 494617.55 | 0.00 | 0.317707E+09 | 0.301220E+09 | 0.00 | 0.35 |
April | 0.954982E+09 | 1069156.28 | 0.00 | 1580465.62 | 0.00 | 62426528.88 | 0.691825E+09 | 0.00 | 0.48 |
May | 0.534224E+09 | 20323396.89 | 0.00 | 3168091.89 | 0.00 | 0.00 | 0.121247E+10 | 0.00 | 0.77 |
June | 47597929.30 | 0.617816E+09 | 0.00 | 2145529.65 | 4483653.56 | 0.00 | 0.440014E+09 | 0.00 | 0.75 |
July | 1064906.29 | 0.165398E+10 | 0.00 | 195546.83 | 9321110.19 | 0.00 | 16190994.24 | 0.00 | 0.44 |
August | 21599458.02 | 0.152406E+10 | 0.00 | 2094930.39 | 8576307.28 | 0.00 | 0.207099E+09 | 0.00 | 0.77 |
September | 0.155145E+09 | 0.365719E+09 | 0.00 | 3191541.51 | 1974497.76 | 0.00 | 0.866411E+09 | 0.00 | 0.81 |
October | 0.388170E+09 | 36044004.57 | 0.00 | 3627894.84 | 0.00 | 0.00 | 0.135629E+10 | 0.00 | 0.77 |
November | 0.110042E+10 | 0.00 | 0.00 | 448733.40 | 0.00 | 0.277689E+09 | 0.298529E+09 | 0.00 | 0.34 |
December | 0.989205E+09 | 0.00 | 0.00 | 3134.56 | 0.00 | 0.860211E+09 | 12647193.22 | 0.00 | 0.28 |
Annual Sum or Average | 0.674019E+10 | 0.421901E+10 | 0.00 | 16965831.34 | 24355568.79 | 0.432846E+10 | 0.543228E+10 | 0.00 | 0.53 |
Minimum of Months | 1064906.29 | 0.00 | 0.00 | 332.82 | 0.00 | 0.00 | 2358424.07 | 0.00 | 0.28 |
Maximum of Months | 0.135786E+10 | 0.165398E+10 | 0.00 | 3627894.84 | 9321110.19 | 0.147697E+10 | 0.135629E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.592115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251706E+10 | 0.00 | 0.00 | 0.29 |
February | 0.781212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222980E+10 | 0.00 | 0.00 | 0.29 |
March | 0.221923E+10 | 0.00 | 0.00 | 36847.08 | 0.00 | 0.625458E+09 | 28284018.46 | 0.00 | 0.32 |
April | 0.169006E+10 | 1233346.70 | 0.00 | 1179057.77 | 0.00 | 57115936.29 | 0.576755E+09 | 0.00 | 0.41 |
May | 0.694168E+09 | 28029714.24 | 0.00 | 4381919.18 | 0.00 | 0.00 | 0.177557E+10 | 0.00 | 0.68 |
June | 72816654.43 | 0.843476E+09 | 0.00 | 2800298.49 | 8342151.61 | 0.00 | 0.570501E+09 | 0.00 | 0.62 |
July | 1629009.61 | 0.228676E+10 | 0.00 | 263474.02 | 22397836.95 | 0.00 | 25020323.88 | 0.00 | 0.38 |
August | 41413348.40 | 0.182308E+10 | 0.00 | 2165090.62 | 18768888.69 | 0.00 | 0.237231E+09 | 0.00 | 0.56 |
September | 0.345745E+09 | 0.445227E+09 | 0.00 | 2639424.01 | 3923182.52 | 0.00 | 0.785622E+09 | 0.00 | 0.57 |
October | 0.104344E+10 | 36157417.38 | 0.00 | 2025827.39 | 147323.00 | 327827.36 | 0.784898E+09 | 0.00 | 0.48 |
November | 0.165022E+10 | 0.00 | 0.00 | 90740.56 | 0.00 | 0.650842E+09 | 0.130975E+09 | 0.00 | 0.31 |
December | 0.110520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172121E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.102373E+11 | 0.546396E+10 | 0.00 | 15582679.11 | 53579382.77 | 0.780181E+10 | 0.491486E+10 | 0.00 | 0.43 |
Minimum of Months | 1629009.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.221923E+10 | 0.228676E+10 | 0.00 | 4381919.18 | 22397836.95 | 0.251706E+10 | 0.177557E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.505900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115766E+10 | 0.00 | 0.00 | 0.24 |
February | 0.643086E+09 | 0.00 | 0.00 | 4813.52 | 0.00 | 0.916486E+09 | 8010707.57 | 0.00 | 0.24 |
March | 0.105444E+10 | 0.00 | 0.00 | 772292.83 | 0.00 | 0.233529E+09 | 0.443707E+09 | 0.00 | 0.31 |
April | 0.716794E+09 | 1557073.76 | 0.00 | 2508630.44 | 0.00 | 19867770.58 | 0.118728E+10 | 0.00 | 0.57 |
May | 0.303487E+09 | 25722063.50 | 0.00 | 5361437.70 | 0.00 | 0.00 | 0.208038E+10 | 0.00 | 1.01 |
June | 29386468.27 | 0.646131E+09 | 0.00 | 3118559.83 | 5326197.22 | 0.00 | 0.667172E+09 | 0.00 | 0.85 |
July | 855730.33 | 0.180046E+10 | 0.00 | 305674.45 | 14289170.21 | 0.00 | 34859492.54 | 0.00 | 0.50 |
August | 19899747.38 | 0.155123E+10 | 0.00 | 2497784.98 | 11917654.49 | 0.00 | 0.307186E+09 | 0.00 | 0.84 |
September | 0.139142E+09 | 0.341314E+09 | 0.00 | 3595795.98 | 2523233.77 | 0.00 | 0.970303E+09 | 0.00 | 0.80 |
October | 0.442738E+09 | 28678207.67 | 0.00 | 3206001.14 | 0.00 | 0.00 | 0.118743E+10 | 0.00 | 0.70 |
November | 0.801482E+09 | 0.00 | 0.00 | 526588.95 | 0.00 | 0.275862E+09 | 0.320873E+09 | 0.00 | 0.29 |
December | 0.684352E+09 | 0.00 | 0.00 | 6159.57 | 0.00 | 0.797493E+09 | 3838688.70 | 0.00 | 0.23 |
Annual Sum or Average | 0.534157E+10 | 0.439510E+10 | 0.00 | 21903739.37 | 34056255.70 | 0.340090E+10 | 0.721104E+10 | 0.00 | 0.55 |
Minimum of Months | 855730.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.105444E+10 | 0.180046E+10 | 0.00 | 5361437.70 | 14289170.21 | 0.115766E+10 | 0.208038E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120060E+10 | 0.00 | 0.00 | 1346607.08 | 0.00 | 0.137769E+10 | 0.915365E+09 | 0.00 | 0.33 |
February | 0.133333E+10 | 0.00 | 0.00 | 1885463.81 | 0.00 | 0.106940E+10 | 0.129722E+10 | 0.00 | 0.36 |
March | 0.175769E+10 | 0.00 | 0.00 | 4571508.68 | 0.00 | 0.286131E+09 | 0.231899E+10 | 0.00 | 0.52 |
April | 0.134818E+10 | 3311388.77 | 0.00 | 4629853.71 | 0.00 | 50909803.25 | 0.204122E+10 | 0.00 | 0.66 |
May | 0.661269E+09 | 36272020.62 | 0.00 | 6264798.21 | 0.00 | 0.00 | 0.249270E+10 | 0.00 | 0.88 |
June | 87691997.47 | 0.971420E+09 | 0.00 | 3244396.46 | 8383696.85 | 0.00 | 0.640767E+09 | 0.00 | 0.71 |
July | 2326135.10 | 0.265752E+10 | 0.00 | 292038.50 | 22589663.02 | 0.00 | 23866524.51 | 0.00 | 0.44 |
August | 41747193.33 | 0.246221E+10 | 0.00 | 3398257.27 | 18862360.74 | 0.00 | 0.330300E+09 | 0.00 | 0.78 |
September | 0.242640E+09 | 0.678413E+09 | 0.00 | 7349659.09 | 3942720.59 | 0.00 | 0.179665E+10 | 0.00 | 1.02 |
October | 0.519576E+09 | 0.100701E+09 | 0.00 | 9938798.42 | 0.00 | 0.00 | 0.379077E+10 | 0.00 | 1.16 |
November | 0.132822E+10 | 0.00 | 0.00 | 3913688.54 | 0.00 | 0.308151E+09 | 0.211650E+10 | 0.00 | 0.54 |
December | 0.139232E+10 | 0.00 | 0.00 | 1868597.12 | 0.00 | 0.925040E+09 | 0.117211E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.991559E+10 | 0.690986E+10 | 0.00 | 48703666.90 | 53778441.21 | 0.401732E+10 | 0.189365E+11 | 0.00 | 0.65 |
Minimum of Months | 2326135.10 | 0.00 | 0.00 | 292038.50 | 0.00 | 0.00 | 23866524.51 | 0.00 | 0.33 |
Maximum of Months | 0.175769E+10 | 0.265752E+10 | 0.00 | 9938798.42 | 22589663.02 | 0.137769E+10 | 0.379077E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.573443E+09 | 0.00 | 0.00 | 29219.50 | 0.00 | 0.138044E+10 | 35124756.96 | 0.00 | 0.30 |
February | 0.681228E+09 | 0.00 | 0.00 | 110815.01 | 0.00 | 0.117336E+10 | 0.112310E+09 | 0.00 | 0.30 |
March | 0.127933E+10 | 0.00 | 0.00 | 1204243.60 | 0.00 | 0.254307E+09 | 0.689219E+09 | 0.00 | 0.41 |
April | 0.893408E+09 | 1088245.75 | 0.00 | 2690173.83 | 0.00 | 35188020.81 | 0.121078E+10 | 0.00 | 0.65 |
May | 0.343052E+09 | 28867315.01 | 0.00 | 5147493.27 | 0.00 | 0.00 | 0.194029E+10 | 0.00 | 1.03 |
June | 47017972.44 | 0.762566E+09 | 0.00 | 2653545.55 | 3917002.90 | 0.00 | 0.508030E+09 | 0.00 | 0.89 |
July | 1035654.28 | 0.200134E+10 | 0.00 | 211668.42 | 6600729.19 | 0.00 | 16358357.98 | 0.00 | 0.52 |
August | 25694797.01 | 0.176612E+10 | 0.00 | 2073272.60 | 7416727.56 | 0.00 | 0.194196E+09 | 0.00 | 0.84 |
September | 0.182047E+09 | 0.416245E+09 | 0.00 | 3221219.32 | 1995297.14 | 0.00 | 0.827013E+09 | 0.00 | 0.84 |
October | 0.513860E+09 | 48736081.12 | 0.00 | 3117316.49 | 0.00 | 0.00 | 0.120321E+10 | 0.00 | 0.77 |
November | 0.996001E+09 | 0.00 | 0.00 | 471305.41 | 0.00 | 0.373954E+09 | 0.300830E+09 | 0.00 | 0.35 |
December | 0.821893E+09 | 0.00 | 0.00 | 28708.24 | 0.00 | 0.946309E+09 | 36401029.70 | 0.00 | 0.28 |
Annual Sum or Average | 0.635801E+10 | 0.502497E+10 | 0.00 | 20958981.25 | 19929756.79 | 0.416356E+10 | 0.707377E+10 | 0.00 | 0.60 |
Minimum of Months | 1035654.28 | 0.00 | 0.00 | 28708.24 | 0.00 | 0.00 | 16358357.98 | 0.00 | 0.28 |
Maximum of Months | 0.127933E+10 | 0.200134E+10 | 0.00 | 5147493.27 | 7416727.56 | 0.138044E+10 | 0.194029E+10 | 0.00 | 1.03 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.125095E+12 | 0.259944E+11 | 0.00 | 0.126775E+12 | 0.685456E+10 |
February | 0.198938E+12 | 0.241371E+11 | 0.00 | 0.132641E+12 | 0.683603E+10 |
March | 0.329227E+12 | 0.206258E+11 | 0.00 | 0.169982E+12 | 0.541422E+10 |
April | 0.349678E+12 | 0.134176E+11 | 0.00 | 0.180642E+12 | 0.155052E+11 |
May | 0.446791E+12 | 0.763054E+10 | 0.00 | 0.186497E+12 | 0.549862E+11 |
June | 0.431692E+12 | -718649270.0 | 0.00 | 0.397802E+11 | 0.188010E+12 |
July | 0.424714E+12 | -0.794747E+10 | 0.00 | -0.418025E+11 | 0.272449E+12 |
August | 0.411862E+12 | -0.476225E+10 | 0.00 | -0.298414E+10 | 0.273813E+12 |
September | 0.291979E+12 | 0.201077E+10 | 0.00 | 0.972496E+11 | 0.134846E+12 |
October | 0.284892E+12 | 0.103095E+11 | 0.00 | 0.192339E+12 | 0.579889E+11 |
November | 0.138833E+12 | 0.195104E+11 | 0.00 | 0.169797E+12 | 0.381610E+10 |
December | 0.100551E+12 | 0.227773E+11 | 0.00 | 0.142931E+12 | 0.534663E+10 |
Annual Sum or Average | 0.353425E+13 | 0.132985E+12 | 0.00 | 0.139385E+13 | 0.102587E+13 |
Minimum of Months | 0.100551E+12 | -0.794747E+10 | 0.00 | -0.418025E+11 | 0.381610E+10 |
Maximum of Months | 0.446791E+12 | 0.259944E+11 | 0.00 | 0.192339E+12 | 0.273813E+12 |