Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:32:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1532.33 | 307.56 | 307.56 |
Net Site Energy | 1352.18 | 271.40 | 271.40 |
Total Source Energy | 4593.54 | 921.99 | 921.99 |
Net Source Energy | 4023.01 | 807.48 | 807.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 8.15 | 7.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 396.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 176.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 132.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1407.82 | 124.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 8.15 | 7.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 396.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 176.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 132.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 117.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 8.15 | 7.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 396.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 176.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 132.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 117.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 108.01 | 24.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 282.57 | 24.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 108.01 | 24.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 282.57 | 24.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 187.918 | 13.35 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.77 | -0.6 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 180.148 | 12.80 |
Electricity Coming From Utility | 1228.477 | 87.26 |
Surplus Electricity Going To Utility | 0.802 | 0.06 |
Net Electricity From Utility | 1227.675 | 87.20 |
Total On-Site and Utility Electric Sources | 1407.823 | 100.00 |
Total Electricity End Uses | 1407.823 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 76.17 |
Time Setpoint Not Met During Occupied Cooling | 532.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 973.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:00 | 06-DEC-07:30 | - | - | - | - | - | - | - | - | - | - | 01-FEB-12:09 |
Heating | 0.00 | 33294.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85522.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14732.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 37678.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 824.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24763.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8775.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 163527.48 | 42069.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 33294.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 85522.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 14732.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 3151.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 38.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 824.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 24763.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8775.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 25.80 | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1256.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 558.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 420.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 127.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4458.58 | 134.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 5.18 | 1.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 252.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 112.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 894.90 | 27.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 5.18 | 1.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 252.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 112.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 894.90 | 27.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.56 | 0.292930 | 0.249000 | 0.637060 | 0.781147 | 0.500000 | 0.001301 |
CORE_MID VAV BOX COMPONENT | 2.17 | 0.345943 | 0.294000 | 0.636925 | 0.922515 | 0.500000 | 0.001101 |
CORE_TOP VAV BOX COMPONENT | 2.42 | 0.309865 | 0.263000 | 0.636105 | 0.826307 | 0.500000 | 0.001230 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.869989 | 0.181602 | 0.154000 | 0.133978 | 0.484272 | 0.500000 | 0.002098 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.774009 | 0.129226 | 0.110000 | 0.085141 | 0.344602 | 0.500000 | 0.002948 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.962222 | 0.164195 | 0.140000 | 0.134711 | 0.437852 | 0.500000 | 0.002320 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.883500 | 0.113203 | 0.096000 | 0.084816 | 0.301876 | 0.500000 | 0.003366 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.704570 | 0.224238 | 0.191000 | 0.134573 | 0.597969 | 0.500000 | 0.001699 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.671718 | 0.148904 | 0.127000 | 0.085308 | 0.397078 | 0.500000 | 0.002559 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.786774 | 0.200810 | 0.171000 | 0.134538 | 0.535492 | 0.500000 | 0.001897 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.713207 | 0.140233 | 0.119000 | 0.084872 | 0.373955 | 0.500000 | 0.002717 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.740322 | 0.213409 | 0.181000 | 0.133998 | 0.569092 | 0.500000 | 0.001785 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.733689 | 0.363539 | 0.500000 | 0.002795 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.832742 | 0.189725 | 0.161000 | 0.134071 | 0.505932 | 0.500000 | 0.002008 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.789906 | 0.126617 | 0.108000 | 0.085310 | 0.337644 | 0.500000 | 0.003009 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19316.31 |
CORE_MID VAV BOX REHEAT COIL | 19312.19 |
CORE_TOP VAV BOX REHEAT COIL | 29786.55 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13108.15 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8604.03 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13153.45 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8566.74 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8529.89 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5691.32 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8589.40 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5651.94 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10081.93 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6690.26 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10127.45 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6651.57 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.72 | 1.08 | 5.43 | 1.36 | 4.97 | 4.97 | 0.300000 | 0.274123 | 4.97 |
PACU_VAV_MID | 2.63 | 1.08 | 5.26 | 1.66 | 4.71 | 4.71 | 0.300000 | 0.351859 | 4.71 |
PACU_VAV_TOP | 2.95 | 1.07 | 5.91 | 2.41 | 5.64 | 5.64 | 0.300000 | 0.428016 | 5.64 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.97 |
PACU_VAV_MID_OA_CONTROLLER | 4.71 |
PACU_VAV_TOP_OA_CONTROLLER | 5.64 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.97 | 96541.24 | 0.788542 | 1.66 | 32177.20 | 0.788542 |
PACU_VAV_MID COOLING COIL | 4.71 | 92406.09 | 0.784009 | 1.57 | 30798.95 | 0.784009 |
PACU_VAV_TOP COOLING COIL | 5.64 | 106410.43 | 0.800677 | 1.88 | 35466.60 | 0.800677 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 8611.15 |
PACU_VAV_MID HEATING COIL | 9694.12 |
PACU_VAV_TOP HEATING COIL | 9068.85 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.97 |
PACU_VAV_MID FAN | 4.71 |
PACU_VAV_TOP FAN | 5.64 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.015 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7516 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7656 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5610 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27848788E-12 | 0.13637022E-14 | -0.81023097E-13 | 0.79216012E-16 |
43 | 6 | 0.25824895E-07 | 0.27625343E-09 | 0.59397345E-08 | -0.11998209E-12 |
44 | 5 | -0.17554640E-03 | 0.24097886E-05 | -0.90470599E-04 | 0.58795774E-08 |
45 | 4 | 0.27494803 | 0.11927753E-02 | 0.93505830E-01 | -0.31160983E-04 |
46 | 3 | -6.9253412 | 0.37505722E-01 | -2.2377579 | 0.27339040E-01 |
47 | 2 | 39.746130 | 0.13507978 | 14.849253 | -0.32081291 |
48 | 1 | -79.683230 | 0.61641880E-01 | -28.768593 | 1.0602386 |
49 | 0 | 46.824344 | 0.12537427E-02 | 16.300359 | |
50 | 7 | -0.27402251E-12 | 0.13062726E-14 | -0.81664977E-13 | 0.79643054E-16 |
51 | 6 | 0.25995733E-07 | 0.27297844E-09 | 0.59774430E-08 | -0.12089174E-12 |
52 | 5 | -0.17642699E-03 | 0.23783059E-05 | -0.90913883E-04 | 0.59164366E-08 |
53 | 4 | 0.27599802 | 0.11759213E-02 | 0.93882490E-01 | -0.31307097E-04 |
54 | 3 | -6.9461820 | 0.36940511E-01 | -2.2439388 | 0.27441040E-01 |
55 | 2 | 39.814917 | 0.13293308 | 14.874721 | -0.32157873 |
56 | 1 | -79.735998 | 0.60618496E-01 | -28.791459 | 1.0613631 |
57 | 0 | 46.824344 | 0.12320537E-02 | 16.299787 | |
58 | 7 | -0.27749376E-12 | 0.16893975E-14 | -0.84125370E-13 | 0.18079425E-15 |
59 | 6 | 0.22886636E-07 | 0.32835403E-09 | 0.52910653E-08 | -0.10444131E-12 |
60 | 5 | -0.16025164E-03 | 0.29299438E-05 | -0.82748939E-04 | 0.52444335E-08 |
61 | 4 | 0.25649379 | 0.14793778E-02 | 0.86896489E-01 | -0.28615133E-04 |
62 | 3 | -6.5585231 | 0.47340314E-01 | -2.1290029 | 0.25545250E-01 |
63 | 2 | 38.534810 | 0.17312159 | 14.399826 | -0.30733026 |
64 | 1 | -78.753333 | 0.80044855E-01 | -28.364722 | 1.0404251 |
65 | 0 | 46.824351 | 0.16491755E-02 | 16.310723 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2186E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2606E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7931E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8285E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3995E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4281E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1048 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8423E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1175 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2927E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7888E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1278E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2195E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2673E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7940E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8359E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4006E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4335E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8657E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7860E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5716E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5619E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7283E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3599E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4170E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4334E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1818E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1937E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0144E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0186E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9463E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9836E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4776E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5074E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1650E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1866E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7416E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5589E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1206E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1920E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9462E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2358E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9461E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9836E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4772E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5064E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1640E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1829E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2175E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4845E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7792E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1926E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1412E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0911E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0026E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0421E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6720E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7134E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6553E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6742E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1052 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9617E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1160 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.4964E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3118E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0034E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7100E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6962E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4338E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4823E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6189E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2944E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1418E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0515E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4781E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6181E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3021E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2145E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0817E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4087E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6660E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1302E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0489E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0375E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1052 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9610E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1160 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.4957E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3113E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0029E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7099E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6960E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4337E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4821E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6186E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2942E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1419E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0514E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4781E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6180E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3020E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2144E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0817E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4086E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6659E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1301E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0487E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0372E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 32245.09857 | 32245.09857 | 2.55848 | 2.55848 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5939.71228 | 5939.71228 | 0.27558 | 0.42469 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27324.69227 | 27324.69227 | 2.16641 | 2.16641 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11808.63482 | 11808.63482 | 0.54967 | 0.54967 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30221.09138 | 30221.09138 | 2.41865 | 2.41865 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 20996.34120 | 20996.34120 | 0.98237 | 0.98237 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10871.26668 | 10871.26668 | 0.86999 | 0.86999 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9210.04052 | 9210.04052 | 0.43231 | 0.43231 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9671.97305 | 9671.97305 | 0.77401 | 0.77401 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6044.68811 | 6044.68811 | 0.28376 | 0.28376 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12023.81174 | 12023.81174 | 0.96222 | 0.96222 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9241.76464 | 9241.76464 | 0.43381 | 0.43381 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11040.15722 | 11040.15722 | 0.88350 | 0.88350 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6018.57444 | 6018.57444 | 0.28253 | 0.28253 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8803.99384 | 8803.99384 | 0.70457 | 0.70457 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6001.83992 | 6001.83992 | 0.28132 | 0.28132 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8393.54146 | 8393.54146 | 0.67172 | 0.67172 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4003.75324 | 4003.75324 | 0.18770 | 0.18770 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9831.17877 | 9831.17877 | 0.78677 | 0.78677 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6043.54053 | 6043.54053 | 0.28328 | 0.28328 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8911.97139 | 8911.97139 | 0.71321 | 0.71321 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 38.71633 | 5.62786E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3976.15424 | 3976.15424 | 0.18640 | 0.18640 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9250.87733 | 9250.87733 | 0.74032 | 0.74032 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7090.20352 | 7090.20352 | 0.33251 | 0.33251 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9168.05858 | 9168.05858 | 0.73369 | 0.73369 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 35.74600 | 5.62327E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4704.11191 | 4704.11191 | 0.22065 | 0.22065 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10405.74548 | 10405.74548 | 0.83274 | 0.83274 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7122.08521 | 7122.08521 | 0.33401 | 0.33401 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9870.52163 | 9870.52163 | 0.78991 | 0.78991 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4677.01657 | 4677.01657 | 0.21937 | 0.21937 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 78674.96 | 4.97367 | 4.97367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 12887.68 | 1.36340 | 1.36340 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 75168.69 | 4.70699 | 4.70699 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 12880.27 | 1.65620 | 1.65620 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 86519.35 | 5.64183 | 5.64183 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 12712.99 | 2.41479 | 2.41479 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55848 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29293 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63706 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78115 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30065E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19316.30833 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.16641 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34594 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63692 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92252 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10134E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19312.19225 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.41865 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30986 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63610 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82631 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22957E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29786.54775 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86999 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18160 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13398 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48427 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09800E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13108.14962 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77401 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12923 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51410E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34460 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94833E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8604.02529 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96222 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16419 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13471 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43785 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32042E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13153.45132 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88350 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11320 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.60000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48160E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30188 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36562E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8566.73785 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70457 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22424 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13457 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59797 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69909E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8529.89050 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67172 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53082E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39708 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55869E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5691.31864 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78677 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20081 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13454 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53549 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89732E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8589.40259 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71321 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14023 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48717E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37395 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71691E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5651.94198 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74032 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21341 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13400 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56909 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78530E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10081.92671 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73369 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36354 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79475E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6690.25503 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83274 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18972 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16100 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13407 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50593 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.00817E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10127.45217 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78991 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12662 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10800 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53098E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33764 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00908E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6651.56705 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.71737 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07635 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.43474 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36340 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.97367 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.97367 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.27412 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.63153 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07541 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.26307 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.65620 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.70699 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.70699 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.35186 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.95419 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07475 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.90837 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.41479 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.64183 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.64183 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.42802 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.97367 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.70699 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.64183 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.97367 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.97367 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 96541.24487 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78854 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65772 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32177.19691 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78854 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 8611.14571 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.97367 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.70699 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.70699 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 92406.08825 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78401 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56884 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30798.94922 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78401 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 9694.12357 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.70699 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.64183 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.64183 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106410.43391 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80068 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.88042 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35466.59762 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80068 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 9068.85358 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.64183 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 95543.80 | 326008.98 | 11.82 | 3.00 | 3.38 | 3.56 | 3.75 | 10.23 | 11.55 | 12.15 | 12.79 | 5.2225 | 4.1770 | 2.8137 | 1.1255 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 91492.85 | 312186.56 | 11.85 | 3.00 | 3.39 | 3.57 | 3.75 | 10.25 | 11.57 | 12.18 | 12.81 | 4.9424 | 3.9513 | 2.6623 | 1.0689 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 105187.52 | 358914.70 | 11.75 | 2.98 | 3.36 | 3.54 | 3.74 | 10.18 | 11.48 | 12.07 | 12.75 | 5.9240 | 4.7440 | 3.1965 | 1.2644 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2016405337E-002 | 8.6087786541E-002 | Pass | Pass | 1.4455999502E-002 | 0.1186423365 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1075946335 | 6.9286956170E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2540494329E-002 | 1.0593190037E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3772712830E-002 | 2.4570991789E-002 | Pass | Pass | 6.0096701025E-002 | 0.3655685226 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.1903640361E-002 | 7.0331772090E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4939882233E-002 | 1.6264025314E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.5000698692E-002 | 2.8431873499E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.7877934792E-002 | 7.6829464513E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1371816079 | 9.8301534379E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1214600031 | 0.1005532103 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.2253604729E-002 | 4.6895967867E-002 | Pass | Pass | 1.4190669685E-002 | 0.1137991548 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.1576312494E-002 | 8.6591776566E-002 | Pass | Pass | 1.4271326127E-002 | 0.1168403673 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1122453622 | 0.1153194185 | Pass | Pass | 2.3566315245E-002 | 0.1719082803 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.6506814928E-002 | 0.1060571464 | Pass | Pass | 1.3889259773E-002 | 0.1132302594 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.7178746723E-002 | 2.1289263062E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.7770089915E-002 | 8.1381308338E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1173450586 | 9.6048465160E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1013452587 | 9.6511461079E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2853.97 | 20.71 | 0.00 | 1053.77 | 1851.41 | 5779.88 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.455_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.455_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.455_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.586 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 39.34 | 0.0000 | Y | 42.16 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 39.34 | 0.0000 | Y | 42.16 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 39.34 | 0.0000 | Y | 42.16 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.73 | 0.0000 | Y | 5.14 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.41 | 0.0000 | Y | 3.20 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.29 | 0.0000 | Y | 5.04 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.60 | 0.0000 | Y | 3.23 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.67 | 0.0000 | Y | 5.12 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.37 | 0.0000 | Y | 3.20 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.26 | 0.0000 | Y | 5.03 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.55 | 0.0000 | Y | 3.23 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.73 | 0.0000 | Y | 5.14 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.41 | 0.0000 | Y | 3.20 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.29 | 0.0000 | Y | 5.04 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.60 | 0.0000 | Y | 3.23 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 176.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 41.79 | 41.79 | 4.26 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.79 | 62.79 | 3.30 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.79 | 47.06 | 26.52 | |
Exterior Lighting Total | 3824.74 | 34.08 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 96541.24 | 76126.85 | 20414.39 | 0.79 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 92406.09 | 72447.24 | 19958.85 | 0.78 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106410.43 | 85200.37 | 21210.06 | 0.80 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 95543.8 | 3.00 | 10.23 | N/A | N/A | 11.82 | |
PACU_VAV_MID COOLING COIL | 91492.8 | 3.00 | 10.25 | N/A | N/A | 11.85 | |
PACU_VAV_TOP COOLING COIL | 105187.5 | 2.98 | 10.18 | N/A | N/A | 11.75 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 19316.31 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 19312.19 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 29786.55 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13108.15 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8604.03 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13153.45 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8566.74 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8529.89 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5691.32 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8589.40 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5651.94 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10081.93 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6690.26 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10127.45 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6651.57 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 8611.15 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 9694.12 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 9068.85 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.97 | 10887.42 | 2189.01 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.71 | 10303.66 | 2189.01 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.64 | 12270.35 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95543.80 | 3.00 | 10.23 | 11.82 | 5.2225 | 3.38 | 11.55 | 4.1770 | 3.56 | 12.15 | 2.8137 | 3.75 | 12.79 | 1.1255 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 91492.85 | 3.00 | 10.25 | 11.85 | 4.9424 | 3.39 | 11.57 | 3.9513 | 3.57 | 12.18 | 2.6623 | 3.75 | 12.81 | 1.0689 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105187.52 | 2.98 | 10.18 | 11.75 | 5.9240 | 3.36 | 11.48 | 4.7440 | 3.54 | 12.07 | 3.1965 | 3.74 | 12.75 | 1.2644 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 32245.10 | 32245.10 | 32.78 | 2.558 | 2.558 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_MID | 27324.69 | 27324.69 | 27.78 | 2.166 | 2.166 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_TOP | 30221.09 | 30221.09 | 30.73 | 2.419 | 2.419 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00890 | 40.27 | 0.00563 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10871.27 | 10871.27 | 52.43 | 0.870 | 0.870 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00862 | 40.53 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9671.97 | 9671.97 | 73.68 | 0.774 | 0.774 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00858 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12023.81 | 12023.81 | 57.99 | 0.962 | 0.962 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00861 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11040.16 | 11040.16 | 84.11 | 0.883 | 0.883 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00857 | 38.94 | 0.00563 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8803.99 | 8803.99 | 42.46 | 0.705 | 0.705 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00871 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8393.54 | 8393.54 | 63.94 | 0.672 | 0.672 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00864 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9831.18 | 9831.18 | 47.42 | 0.787 | 0.787 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00869 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8911.97 | 8911.97 | 67.90 | 0.713 | 0.713 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 38.72 | 0.00563 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9250.88 | 9250.88 | 44.62 | 0.740 | 0.740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00866 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9168.06 | 9168.06 | 69.85 | 0.734 | 0.734 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00860 | 35.75 | 0.00562 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10405.75 | 10405.75 | 50.19 | 0.833 | 0.833 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00864 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9870.52 | 9870.52 | 75.20 | 0.790 | 0.790 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00859 | 38.94 | 0.00563 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5939.71 | 5939.71 | 6.04 | 0.276 | 0.425 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_MID | 11808.63 | 11808.63 | 12.01 | 0.550 | 0.550 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_TOP | 20996.34 | 20996.34 | 21.35 | 0.982 | 0.982 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9210.04 | 9210.04 | 44.42 | 0.432 | 0.432 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6044.69 | 6044.69 | 46.05 | 0.284 | 0.284 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9241.76 | 9241.76 | 44.57 | 0.434 | 0.434 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6018.57 | 6018.57 | 45.85 | 0.283 | 0.283 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6001.84 | 6001.84 | 28.95 | 0.281 | 0.281 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4003.75 | 4003.75 | 30.50 | 0.188 | 0.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6043.54 | 6043.54 | 29.15 | 0.283 | 0.283 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3976.15 | 3976.15 | 30.29 | 0.186 | 0.186 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7090.20 | 7090.20 | 34.20 | 0.333 | 0.333 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4704.11 | 4704.11 | 35.84 | 0.221 | 0.221 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7122.09 | 7122.09 | 34.35 | 0.334 | 0.334 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4677.02 | 4677.02 | 35.63 | 0.219 | 0.219 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.97 | 4.97 | 1.36 | 1.36 | 4.9737 | 1.3634 | 4.9737 | 0.2741 | 0.3000 |
PACU_VAV_MID | 4.71 | 4.71 | 1.66 | 1.66 | 4.7070 | 1.6562 | 4.7070 | 0.3519 | 0.3000 |
PACU_VAV_TOP | 5.64 | 5.64 | 2.41 | 2.41 | 5.6418 | 2.4148 | 5.6418 | 0.4280 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19316.308 | 19316.308 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19316.31 | 12877.06 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 5939.71 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 19312.192 | 19312.192 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19312.19 | 16666.42 | 0.549666 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 11808.63 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 29786.548 | 29786.548 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29786.55 | 29786.55 | 0.982373 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 20996.34 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13108.150 | 13108.150 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13108.15 | 13108.15 | 0.432313 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784548 | 46.0575 | 9210.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8604.025 | 8604.025 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8604.03 | 8604.03 | 0.283765 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784585 | 46.0596 | 6044.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13153.451 | 13153.451 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13153.45 | 13153.45 | 0.433807 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784629 | 46.0622 | 9241.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8566.738 | 8566.738 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8566.74 | 8566.74 | 0.282535 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784490 | 46.0542 | 6018.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8529.890 | 8529.890 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8529.89 | 8529.89 | 0.281320 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777013 | 45.6209 | 6001.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5691.319 | 5691.319 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5691.32 | 5691.32 | 0.187702 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778392 | 45.7009 | 4003.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8589.403 | 8589.403 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8589.40 | 8589.40 | 0.283282 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777356 | 45.6408 | 6043.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5651.942 | 5651.942 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5651.94 | 5651.94 | 0.186404 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778050 | 45.6811 | 3976.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10081.927 | 10081.927 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10081.93 | 10081.93 | 0.332506 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778104 | 45.6843 | 7090.20 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6690.255 | 6690.255 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6690.26 | 6690.26 | 0.220648 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00779020 | 45.7373 | 4704.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10127.452 | 10127.452 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10127.45 | 10127.45 | 0.334008 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778294 | 45.6953 | 7122.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 6651.567 | 6651.567 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6651.57 | 6651.57 | 0.219372 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778792 | 45.7242 | 4677.02 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 96541.245 | 76126.853 | 4.973671 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 88015.33 | 88015.33 | 4.973671 | 27.24 | 16.24 | 0.00818074 | 10.84 | 10.11 | 0.00818074 | 40.80 | 0.00563111 | 18.58 | 19.2232 | 24.00 | 0.00878943 | 42.9370 | 61987.64 | 0.00 | 99546.98 | 73650.02 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 8611.146 | 8611.146 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8611.15 | 8611.15 | 1.492101 | 7.55 | 5.71 | 0.00551001 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 64.0774 | 19.66 | 0.00757296 | 48.3095 | 12378.23 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 92406.088 | 72447.236 | 4.706991 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 84245.36 | 84245.36 | 4.706991 | 27.43 | 16.27 | 0.00814066 | 10.84 | 10.07 | 0.00814066 | 40.80 | 0.00563111 | 18.58 | 20.3123 | 24.00 | 0.00878570 | 42.9187 | 58426.44 | 0.00 | 95283.08 | 70125.72 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 9694.124 | 9694.124 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9694.12 | 9694.12 | 1.412097 | 6.55 | 5.06 | 0.00537278 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 67.7078 | 19.63 | 0.00738292 | 47.2090 | 15053.58 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 106410.434 | 85200.369 | 5.641831 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 97302.26 | 97302.26 | 5.641831 | 26.81 | 16.11 | 0.00820148 | 10.85 | 10.14 | 0.00820148 | 40.53 | 0.00563070 | 18.50 | 16.9466 | 24.00 | 0.00872836 | 42.6423 | 70239.20 | 0.00 | 109723.44 | 82308.83 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 9068.854 | 9068.854 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9068.85 | 9068.85 | 1.692549 | 7.92 | 6.19 | 0.00576639 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 56.4888 | 17.60 | 0.00748107 | 54.3101 | 16141.55 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 19316.308 | 19316.308 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19316.31 | 12877.06 | 1.0000 | 0.46426985 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19316.31 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.65 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 5939.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 19312.192 | 19312.192 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19312.19 | 16666.42 | 1.0000 | 0.60089160 | 0.549666 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19312.19 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 11808.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 29786.548 | 29786.548 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29786.55 | 29786.55 | 1.0000 | 1.07392489 | 0.982373 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29786.55 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 20996.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13108.150 | 13108.150 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13108.15 | 13108.15 | 1.0000 | 0.47260153 | 0.432313 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13108.15 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784548 | 21.00 | 0.00784548 | 46.0575 | 9210.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8604.025 | 8604.025 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8604.03 | 8604.03 | 1.0000 | 0.31020973 | 0.283765 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8604.03 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784585 | 21.00 | 0.00784585 | 46.0596 | 6044.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13153.451 | 13153.451 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13153.45 | 13153.45 | 1.0000 | 0.47423484 | 0.433807 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13153.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784629 | 21.00 | 0.00784629 | 46.0622 | 9241.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8566.738 | 8566.738 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8566.74 | 8566.74 | 1.0000 | 0.30886537 | 0.282535 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8566.74 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00784490 | 21.00 | 0.00784490 | 46.0542 | 6018.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8529.890 | 8529.890 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8529.89 | 8529.89 | 1.0000 | 0.30753687 | 0.281320 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8529.89 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00777013 | 21.00 | 0.00777013 | 45.6209 | 6001.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5691.319 | 5691.319 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5691.32 | 5691.32 | 1.0000 | 0.20519494 | 0.187702 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5691.32 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00778392 | 21.00 | 0.00778392 | 45.7009 | 4003.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8589.403 | 8589.403 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8589.40 | 8589.40 | 1.0000 | 0.30968252 | 0.283282 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8589.40 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00777356 | 21.00 | 0.00777356 | 45.6408 | 6043.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5651.942 | 5651.942 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5651.94 | 5651.94 | 1.0000 | 0.20377525 | 0.186404 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5651.94 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00778050 | 21.00 | 0.00778050 | 45.6811 | 3976.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10081.927 | 10081.927 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10081.93 | 10081.93 | 1.0000 | 0.36349402 | 0.332506 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10081.93 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778104 | 21.00 | 0.00778104 | 45.6843 | 7090.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6690.255 | 6690.255 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6690.26 | 6690.26 | 1.0000 | 0.24121061 | 0.220648 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.26 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00779020 | 21.00 | 0.00779020 | 45.7373 | 4704.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10127.452 | 10127.452 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10127.45 | 10127.45 | 1.0000 | 0.36513540 | 0.334008 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10127.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778294 | 21.00 | 0.00778294 | 45.6953 | 7122.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6651.567 | 6651.567 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6651.57 | 6651.57 | 1.0000 | 0.23981575 | 0.219372 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6651.57 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778792 | 21.00 | 0.00778792 | 45.7242 | 4677.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 96541.245 | 76126.853 | 4.973671 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0476 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.973671 | 5.43718833 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 88015.33 | 88015.33 | 0.9117 | 5.43718833 | 4.973671 | 27.24 | 16.24 | 0.00818074 | 48242.5 | 10.84 | 10.11 | 0.00818074 | 31513.7 | -999.0 | -999.00 | -999.00 | -999.00 | 10887.420 | 77127.91 | 40.80 | 0.00563111 | 18.58 | 0.95610000 | 19.2232 | 24.00 | 0.00878943 | 24.00 | 0.00878943 | 42.9370 | 61987.64 | 0.00 | 99546.98 | 73650.02 | 5.22246050 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.87 | 12.86 | 0.00924044 | 36261.1 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8611.146 | 8611.146 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.973671 | 5.43718833 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8611.15 | 8611.15 | 1.0000 | 1.63115650 | 1.492101 | 7.55 | 5.71 | 0.00551001 | 21440.4 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8611.15 | 0.50 | 0.00431558 | 0.50 | 0.95610000 | 64.0774 | 20.12 | 0.00764059 | 19.66 | 0.00757296 | 48.3095 | 12378.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 92406.088 | 72447.236 | 4.706991 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9731 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.706991 | 5.14565581 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 84245.36 | 84245.36 | 0.9117 | 5.14565581 | 4.706991 | 27.43 | 16.27 | 0.00814066 | 48341.7 | 10.84 | 10.07 | 0.00814066 | 31412.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10303.656 | 73941.71 | 40.80 | 0.00563111 | 18.58 | 0.95610000 | 20.3123 | 24.00 | 0.00878570 | 24.00 | 0.00878570 | 42.9187 | 58426.44 | 0.00 | 95283.08 | 70125.72 | 4.94244130 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.78 | 12.77 | 0.00918896 | 36043.8 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9694.124 | 9694.124 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.706991 | 5.14565581 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9694.12 | 9694.12 | 1.0000 | 1.54369674 | 1.412097 | 6.55 | 5.06 | 0.00537278 | 20084.7 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9694.12 | 0.50 | 0.00431558 | 0.50 | 0.95610000 | 67.7078 | 19.24 | 0.00758942 | 19.63 | 0.00738292 | 47.2090 | 15053.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106410.434 | 85200.369 | 5.641831 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0861 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.641831 | 6.16761675 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 97302.26 | 97302.26 | 0.9144 | 6.16761675 | 5.641831 | 26.81 | 16.11 | 0.00820148 | 47861.5 | 10.85 | 10.14 | 0.00820148 | 31579.0 | -999.0 | -999.00 | -999.00 | -999.00 | 12270.352 | 85031.91 | 40.53 | 0.00563070 | 18.50 | 0.95610000 | 16.9466 | 24.00 | 0.00872836 | 24.00 | 0.00872836 | 42.6423 | 70239.20 | 0.00 | 109723.44 | 82308.83 | 5.92404251 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.08 | 13.07 | 0.00937025 | 36800.7 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9068.854 | 9068.854 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.641831 | 6.16761675 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9068.85 | 9068.85 | 1.0000 | 1.85028503 | 1.692549 | 7.92 | 6.19 | 0.00576639 | 22467.0 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9068.85 | 0.50 | 0.00431558 | 0.50 | 0.95610000 | 56.4888 | 17.56 | 0.00764990 | 17.60 | 0.00748107 | 54.3101 | 16141.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.97 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.71 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.64 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1807.33 | 1601.83 | 5.50 |
CORE_MID | 1622.00 | 2466.17 | 16.00 |
CORE_TOP | 1669.67 | 2781.50 | 105.83 |
PERIMETER_TOP_ZN_3 | 2397.33 | 3059.50 | 606.50 |
PERIMETER_TOP_ZN_2 | 2806.67 | 2505.17 | 524.67 |
PERIMETER_TOP_ZN_1 | 2886.83 | 2089.33 | 443.17 |
PERIMETER_TOP_ZN_4 | 2801.00 | 2657.00 | 636.67 |
PERIMETER_BOT_ZN_3 | 1876.00 | 3050.17 | 172.33 |
PERIMETER_BOT_ZN_2 | 2506.67 | 2227.17 | 214.17 |
PERIMETER_BOT_ZN_1 | 2599.50 | 2004.33 | 295.00 |
PERIMETER_BOT_ZN_4 | 2441.33 | 2367.83 | 200.67 |
PERIMETER_MID_ZN_3 | 2013.67 | 2890.17 | 248.50 |
PERIMETER_MID_ZN_2 | 2184.50 | 2052.00 | 306.83 |
PERIMETER_MID_ZN_1 | 2710.17 | 1825.33 | 239.50 |
PERIMETER_MID_ZN_4 | 2530.67 | 2442.50 | 330.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4083.17 | 3677.67 | 973.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.83 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.17 | 53.17 | 0.17 | 33.00 |
PERIMETER_TOP_ZN_2 | 0.17 | 95.67 | 0.17 | 73.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 87.00 | 0.00 | 65.83 |
PERIMETER_TOP_ZN_4 | 0.17 | 88.67 | 0.17 | 46.67 |
PERIMETER_BOT_ZN_3 | 0.00 | 12.83 | 0.00 | 8.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 72.50 | 0.00 | 62.50 |
PERIMETER_BOT_ZN_1 | 76.00 | 365.17 | 76.00 | 358.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 67.33 | 0.00 | 36.33 |
PERIMETER_MID_ZN_3 | 0.00 | 27.17 | 0.00 | 17.50 |
PERIMETER_MID_ZN_2 | 0.00 | 80.00 | 0.00 | 69.50 |
PERIMETER_MID_ZN_1 | 0.00 | 75.83 | 0.00 | 66.33 |
PERIMETER_MID_ZN_4 | 0.00 | 72.83 | 0.00 | 40.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 76.17 | 608.83 | 76.17 | 532.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.754 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.591 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.560 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.648 | 0.067 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.998 | 0.071 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.176 | 0.068 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.934 | 0.071 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.605 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.970 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.050 | 1.279 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.867 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.663 | 0.056 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.974 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.178 | 0.056 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.943 | 0.059 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 11948455.68 | 0.00 | 11948455.68 | 0.00 | 11948455.68 | 13393058.27 | 6106.80 | 87.65 | 2565.55 | 39.42 |
CORE_MID | 9354322.73 | 0.00 | 9354322.73 | 0.00 | 9354322.73 | 13393058.27 | 6346.91 | 173.34 | 2239.75 | 30.25 |
CORE_TOP | 8902561.89 | 0.00 | 8902561.89 | 0.00 | 8902561.89 | 13393058.27 | 6308.27 | 240.47 | 2211.26 | 38.52 |
PERIMETER_TOP_ZN_3 | 2166265.27 | 0.00 | 2166265.27 | 446659.24 | 2612924.51 | 2823374.22 | 4343.25 | 286.67 | 4130.08 | 38.52 |
PERIMETER_TOP_ZN_2 | 2105422.43 | 0.00 | 2105422.43 | 297771.03 | 2403193.46 | 1787429.43 | 4156.86 | 162.15 | 4440.99 | 38.52 |
PERIMETER_TOP_ZN_1 | 3921417.39 | 0.00 | 3921417.39 | 446659.24 | 4368076.63 | 2823374.22 | 4222.18 | 148.96 | 4388.87 | 38.52 |
PERIMETER_TOP_ZN_4 | 1974851.80 | 0.00 | 1974851.80 | 297771.03 | 2272622.83 | 1787312.18 | 4249.08 | 274.14 | 4236.78 | 38.52 |
PERIMETER_BOT_ZN_3 | 2025607.14 | 0.00 | 2025607.14 | 237487.89 | 2263095.03 | 2823374.22 | 5198.77 | 130.81 | 3430.42 | 39.42 |
PERIMETER_BOT_ZN_2 | 2047679.44 | 0.00 | 2047679.44 | 158324.31 | 2206003.75 | 1787429.43 | 4328.00 | 63.57 | 4368.43 | 39.42 |
PERIMETER_BOT_ZN_1 | 3505353.35 | 0.00 | 3505353.35 | 4361350.24 | 7866703.58 | 2823374.22 | 4310.89 | 79.66 | 4369.45 | 39.42 |
PERIMETER_BOT_ZN_4 | 1832237.35 | 0.00 | 1832237.35 | 158324.31 | 1990561.66 | 1787312.18 | 4498.99 | 117.71 | 4143.30 | 39.42 |
PERIMETER_MID_ZN_3 | 2210937.13 | 0.00 | 2210937.13 | 371810.73 | 2582747.86 | 2823374.22 | 4416.25 | 235.65 | 4108.10 | 30.25 |
PERIMETER_MID_ZN_2 | 2069134.30 | 0.00 | 2069134.30 | 247872.33 | 2317006.62 | 1601953.02 | 4157.65 | 146.23 | 4456.12 | 939.25 |
PERIMETER_MID_ZN_1 | 3923179.81 | 0.00 | 3923179.81 | 371810.73 | 4294990.53 | 2823374.22 | 4207.86 | 208.06 | 4344.08 | 30.25 |
PERIMETER_MID_ZN_4 | 1988974.86 | 0.00 | 1988974.86 | 247872.33 | 2236847.18 | 1787312.18 | 4252.69 | 126.46 | 4380.85 | 30.25 |
Total Facility | 59976400.55 | 0.00 | 59976400.55 | 7643713.41 | 67620113.95 | 67658168.57 | 6732.69 | 543.49 | 4715.37 | 974.99 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5539 | 0.0000 | 0.5539 | 0.0000 | 0.5539 | 0.4247 | 3329.10 | 87.65 | 2526.25 |
CORE_MID | 0.4337 | 0.0000 | 0.4337 | 0.0000 | 0.4337 | 0.4247 | 3560.04 | 173.34 | 2209.62 |
CORE_TOP | 0.4119 | 0.0000 | 0.4119 | 0.0000 | 0.4119 | 0.4247 | 3528.78 | 240.47 | 2173.75 |
PERIMETER_TOP_ZN_3 | 0.1004 | 0.0000 | 0.1004 | 0.0104 | 0.1108 | 0.0895 | 1563.76 | 286.67 | 4092.57 |
PERIMETER_TOP_ZN_2 | 0.0978 | 0.0000 | 0.0978 | 0.0070 | 0.1048 | 0.0567 | 1377.37 | 162.15 | 4403.48 |
PERIMETER_TOP_ZN_1 | 0.1824 | 0.0000 | 0.1824 | 0.0104 | 0.1928 | 0.0895 | 1442.69 | 148.96 | 4351.35 |
PERIMETER_TOP_ZN_4 | 0.0916 | 0.0000 | 0.0916 | 0.0070 | 0.0985 | 0.0567 | 1469.60 | 274.14 | 4199.26 |
PERIMETER_BOT_ZN_3 | 0.0937 | 0.0000 | 0.0937 | 0.0055 | 0.0993 | 0.0895 | 2421.07 | 130.81 | 3391.12 |
PERIMETER_BOT_ZN_2 | 0.0951 | 0.0000 | 0.0951 | 0.0037 | 0.0988 | 0.0567 | 1550.30 | 63.57 | 4329.13 |
PERIMETER_BOT_ZN_1 | 0.1628 | 0.0000 | 0.1628 | 0.1983 | 0.3611 | 0.0895 | 1533.19 | 79.66 | 4330.15 |
PERIMETER_BOT_ZN_4 | 0.0849 | 0.0000 | 0.0849 | 0.0037 | 0.0886 | 0.0567 | 1721.30 | 117.71 | 4104.00 |
PERIMETER_MID_ZN_3 | 0.1026 | 0.0000 | 0.1026 | 0.0087 | 0.1113 | 0.0895 | 1629.38 | 235.65 | 4077.97 |
PERIMETER_MID_ZN_2 | 0.0955 | 0.0000 | 0.0955 | 0.0062 | 0.1017 | 0.0567 | 1370.78 | 146.23 | 3516.99 |
PERIMETER_MID_ZN_1 | 0.1826 | 0.0000 | 0.1826 | 0.0087 | 0.1913 | 0.0895 | 1420.99 | 208.06 | 4313.95 |
PERIMETER_MID_ZN_4 | 0.0924 | 0.0000 | 0.0924 | 0.0058 | 0.0982 | 0.0567 | 1465.82 | 126.46 | 4350.72 |
Total Facility | 2.7813 | 0.0000 | 2.7813 | 0.2754 | 3.0568 | 2.1513 | 3928.11 | 543.49 | 4650.39 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 25525936.38 | 0.00 | 25525936.38 | 22614548.33 | 4051.42 | 5.79 | 4702.79 | 39.42 |
PACU_VAV_MID | 23359531.89 | 0.00 | 23359531.89 | 22429071.92 | 4080.05 | 4.50 | 4675.45 | 30.25 |
PACU_VAV_TOP | 22790634.28 | 0.00 | 22790634.28 | 22614548.33 | 4113.61 | 1.07 | 4645.31 | 38.52 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1837 | 0.0000 | 1.1837 | 0.7171 | 1273.72 | 5.79 | 4663.49 |
PACU_VAV_MID | 1.0846 | 0.0000 | 1.0846 | 0.7084 | 1293.19 | 4.50 | 4645.32 |
PACU_VAV_TOP | 1.0565 | 0.0000 | 1.0565 | 0.7171 | 1334.13 | 1.07 | 4607.80 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 286.79 | 2285.33 | 0.00 | 0.00 | 0.00 | 2194.86 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 135.95 | 2294.39 | 0.00 | 0.00 | 0.00 | 2321.43 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 78.20 | 2284.80 | 0.00 | 0.00 | 0.00 | 2389.36 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.1165 | 2.0707 | 0.0000 | 0.0000 | 0.0000 | 0.9402 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1090 | 1.8151 | 0.0000 | 0.0000 | 0.0000 | 0.9419 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0721 | 1.7594 | 0.0000 | 0.0000 | 0.0000 | 0.9389 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1407.82 | 11286.77 | 04-JUN-17:20 | 163527.48 | 28-JUN-15:00 |
Electricity:Building | 824.01 | 11118.23 | 02-APR-17:10 | 58101.33 | 20-JAN-08:30 |
Electricity:Zone:CORE_BOTTOM | 220.64 | 3059.02 | 01-JAN-00:10 | 16454.92 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 824.01 | 11118.23 | 02-APR-17:10 | 58101.33 | 20-JAN-08:30 |
InteriorLights:Electricity | 176.26 | 818.34 | 01-JAN-09:50 | 18725.62 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 176.26 | 818.34 | 01-JAN-09:50 | 18725.62 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity | 176.26 | 818.34 | 01-JAN-09:50 | 18725.62 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 176.26 | 818.34 | 01-JAN-09:50 | 18725.62 | 28-NOV-16:30 |
Electricity:Zone:CORE_MID | 157.58 | 2036.88 | 01-JAN-00:10 | 10504.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 157.58 | 2036.88 | 01-JAN-00:10 | 10504.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.47 | 406.75 | 02-APR-17:10 | 2214.53 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.14 | 20.65 | 01-JAN-09:50 | 779.28 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.14 | 20.65 | 01-JAN-09:50 | 779.28 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.61 | 257.49 | 02-APR-17:10 | 1401.92 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.20 | 13.07 | 01-JAN-08:00 | 493.35 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.20 | 13.07 | 01-JAN-08:00 | 493.35 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.37 | 406.75 | 12-MAR-17:10 | 2214.52 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.04 | 20.65 | 01-JAN-07:50 | 779.28 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.04 | 20.65 | 01-JAN-07:50 | 779.28 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.64 | 257.49 | 12-MAR-17:10 | 1401.89 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.23 | 13.07 | 01-JAN-09:40 | 493.32 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.23 | 13.07 | 01-JAN-09:40 | 493.32 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.45 | 406.75 | 02-APR-17:10 | 2214.53 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.12 | 20.65 | 01-JAN-09:40 | 779.28 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.12 | 20.65 | 01-JAN-09:40 | 779.28 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.60 | 257.49 | 02-APR-17:10 | 1401.92 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.20 | 13.07 | 01-JAN-07:50 | 493.35 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.20 | 13.07 | 01-JAN-07:50 | 493.35 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.36 | 406.75 | 12-MAR-17:10 | 2214.52 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.03 | 20.65 | 01-JAN-07:50 | 779.28 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.03 | 20.65 | 01-JAN-07:50 | 779.28 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.63 | 257.49 | 12-MAR-17:10 | 1401.89 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.23 | 13.07 | 01-JAN-09:40 | 493.32 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.23 | 13.07 | 01-JAN-09:40 | 493.32 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.47 | 406.75 | 02-APR-17:10 | 2214.53 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.14 | 20.65 | 01-JAN-09:50 | 779.28 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.14 | 20.65 | 01-JAN-09:50 | 779.28 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.61 | 257.49 | 02-APR-17:10 | 1401.92 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.20 | 13.07 | 01-JAN-08:00 | 493.35 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.20 | 13.07 | 01-JAN-08:00 | 493.35 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.37 | 406.75 | 12-MAR-17:10 | 2214.52 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.04 | 20.65 | 01-JAN-07:50 | 779.28 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.04 | 20.65 | 01-JAN-07:50 | 779.28 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.64 | 257.49 | 12-MAR-17:10 | 1401.89 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.23 | 13.07 | 01-JAN-09:40 | 493.32 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.23 | 13.07 | 01-JAN-09:40 | 493.32 | 28-NOV-16:30 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 180.15 | -0.00 | 12-JAN-17:30 | 26510.07 | 12-MAY-12:30 |
ElectricityProduced:Plant | 180.15 | -0.00 | 12-JAN-17:30 | 26510.07 | 12-MAY-12:30 |
Photovoltaic:ElectricityProduced | 187.92 | 0.00 | 01-JAN-00:10 | 27611.30 | 12-MAY-12:30 |
PowerConversion:ElectricityProduced | -7.77 | -1101.23 | 12-MAY-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 549.59 | 168.34 | 01-JAN-00:10 | 111110.10 | 28-JUN-15:00 |
ExteriorEquipment:Electricity | 11.63 | 168.34 | 01-JAN-00:10 | 830.04 | 28-NOV-16:40 |
Transformer:ExteriorEquipment:Electricity | 11.63 | 168.34 | 01-JAN-00:10 | 830.04 | 28-NOV-16:40 |
ElectricityPurchased:Facility | 1228.48 | 0.00 | 01-JAN-11:00 | 143265.48 | 28-JUN-15:00 |
ElectricityPurchased:Plant | 1228.48 | 0.00 | 01-JAN-11:00 | 143265.48 | 28-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1228.48 | 0.00 | 01-JAN-11:00 | 143265.48 | 28-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1228.48 | 0.00 | 01-JAN-11:00 | 143265.48 | 28-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.80 | 0.00 | 01-JAN-00:10 | 11443.08 | 26-MAR-12:40 |
ElectricitySurplusSold:Plant | 0.80 | 0.00 | 01-JAN-00:10 | 11443.08 | 26-MAR-12:40 |
Cogeneration:ElectricitySurplusSold | 0.80 | 0.00 | 01-JAN-00:10 | 11443.08 | 26-MAR-12:40 |
General:Cogeneration:ElectricitySurplusSold | 0.80 | 0.00 | 01-JAN-00:10 | 11443.08 | 26-MAR-12:40 |
ElectricityNet:Facility | 1227.68 | -11443.08 | 26-MAR-12:40 | 143265.48 | 28-JUN-15:00 |
ElectricityNet:Plant | 1227.68 | -11443.08 | 26-MAR-12:40 | 143265.48 | 28-JUN-15:00 |
Cogeneration:ElectricityNet | 1227.68 | -11443.08 | 26-MAR-12:40 | 143265.48 | 28-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1227.68 | -11443.08 | 26-MAR-12:40 | 143265.48 | 28-JUN-15:00 |
Heating:Electricity | 8.15 | 0.00 | 01-JAN-00:10 | 82862.81 | 02-JAN-07:10 |
General:Heating:Electricity | 8.15 | 0.00 | 01-JAN-00:10 | 82862.81 | 02-JAN-07:10 |
Fans:Electricity | 132.93 | 0.00 | 01-JAN-00:10 | 27591.88 | 19-JUN-15:00 |
General:Fans:Electricity | 132.93 | 0.00 | 01-JAN-00:10 | 27591.88 | 19-JUN-15:00 |
ExteriorLights:Electricity | 34.08 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.08 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 396.89 | 0.00 | 01-JAN-00:10 | 85522.40 | 28-JUN-15:00 |
General:Cooling:Electricity | 396.89 | 0.00 | 01-JAN-00:10 | 85522.40 | 28-JUN-15:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 4.95 | 0.00 | 01-JAN-00:10 | 526.19 | 28-NOV-16:40 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 124.50 | 1886.44 | 06-MAY-16:10 | 42069.21 | 06-DEC-07:30 |
NaturalGas:HVAC | 7.28 | 0.00 | 01-JAN-00:10 | 33832.17 | 06-DEC-07:20 |
Heating:NaturalGas | 7.28 | 0.00 | 01-JAN-00:10 | 33832.17 | 06-DEC-07:20 |
General:Heating:NaturalGas | 7.28 | 0.00 | 01-JAN-00:10 | 33832.17 | 06-DEC-07:20 |
NaturalGas:Plant | 117.22 | 1886.44 | 08-FEB-08:10 | 9789.03 | 03-FEB-12:10 |
WaterSystems:NaturalGas | 117.22 | 1886.44 | 08-FEB-08:10 | 9789.03 | 03-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 117.22 | 1886.44 | 08-FEB-08:10 | 9789.03 | 03-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2890.61 | 0.00 | 01-JAN-00:10 | 409911.88 | 05-SEP-07:50 |
EnergyTransfer:Building | 1385.10 | 0.00 | 01-JAN-00:10 | 169014.52 | 14-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 228.20 | 0.00 | 01-JAN-00:10 | 24002.79 | 05-SEP-07:50 |
Heating:EnergyTransfer | 13.48 | 0.00 | 01-JAN-00:10 | 70913.97 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 13.48 | 0.00 | 01-JAN-00:10 | 70913.97 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1371.63 | 0.00 | 01-JAN-00:10 | 169014.52 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 228.20 | 0.00 | 01-JAN-00:10 | 24002.79 | 05-SEP-07:50 |
General:Cooling:EnergyTransfer | 1371.63 | 0.00 | 01-JAN-00:10 | 169014.52 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 228.20 | 0.00 | 01-JAN-00:10 | 24002.79 | 05-SEP-07:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.98 | 0.00 | 01-JAN-00:10 | 13016.96 | 28-JUN-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.46 | 0.00 | 01-JAN-00:10 | 6996.69 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.46 | 0.00 | 01-JAN-00:10 | 6996.69 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.52 | 0.00 | 01-JAN-00:10 | 13016.96 | 28-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.52 | 0.00 | 01-JAN-00:10 | 13016.96 | 28-JUN-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 33.33 | 0.00 | 01-JAN-00:10 | 6192.62 | 19-JUN-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 2.05 | 0.00 | 01-JAN-00:10 | 2622.57 | 02-JAN-13:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 2.05 | 0.00 | 01-JAN-00:10 | 2622.57 | 02-JAN-13:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.27 | 0.00 | 01-JAN-00:10 | 6192.62 | 19-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.27 | 0.00 | 01-JAN-00:10 | 6192.62 | 19-JUN-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 35.47 | 0.00 | 01-JAN-00:10 | 5960.83 | 28-AUG-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.76 | 0.00 | 01-JAN-00:10 | 1721.25 | 02-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.76 | 0.00 | 01-JAN-00:10 | 1721.25 | 02-JAN-13:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.71 | 0.00 | 01-JAN-00:10 | 5960.83 | 28-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.71 | 0.00 | 01-JAN-00:10 | 5960.83 | 28-AUG-07:10 |
EnergyTransfer:Zone:CORE_MID | 177.58 | 0.00 | 01-JAN-00:10 | 19880.54 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2692.84 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2692.84 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 177.58 | 0.00 | 01-JAN-00:10 | 19880.54 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 177.58 | 0.00 | 01-JAN-00:10 | 19880.54 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 178.66 | 0.00 | 01-JAN-00:10 | 21066.20 | 19-JUN-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.12 | 0.00 | 01-JAN-00:10 | 13523.70 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.12 | 0.00 | 01-JAN-00:10 | 13523.70 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 178.54 | 0.00 | 01-JAN-00:10 | 21066.20 | 19-JUN-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 178.54 | 0.00 | 01-JAN-00:10 | 21066.20 | 19-JUN-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.69 | 0.00 | 01-JAN-00:10 | 8164.55 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.78 | 0.00 | 01-JAN-00:10 | 7481.83 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.78 | 0.00 | 01-JAN-00:10 | 7481.83 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.91 | 0.00 | 01-JAN-00:10 | 8164.55 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.91 | 0.00 | 01-JAN-00:10 | 8164.55 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.63 | 0.00 | 01-JAN-00:10 | 8950.51 | 19-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.31 | 0.00 | 01-JAN-00:10 | 4809.09 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.31 | 0.00 | 01-JAN-00:10 | 4809.09 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.32 | 0.00 | 01-JAN-00:10 | 8950.51 | 19-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.32 | 0.00 | 01-JAN-00:10 | 8950.51 | 19-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.49 | 0.00 | 01-JAN-00:10 | 12452.57 | 02-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.38 | 0.00 | 01-JAN-00:10 | 6135.83 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.38 | 0.00 | 01-JAN-00:10 | 6135.83 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.11 | 0.00 | 01-JAN-00:10 | 12452.57 | 02-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.11 | 0.00 | 01-JAN-00:10 | 12452.57 | 02-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.98 | 0.00 | 01-JAN-00:10 | 9675.39 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.45 | 0.00 | 01-JAN-00:10 | 4557.92 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.45 | 0.00 | 01-JAN-00:10 | 4557.92 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.53 | 0.00 | 01-JAN-00:10 | 9675.39 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.53 | 0.00 | 01-JAN-00:10 | 9675.39 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 47.03 | 0.00 | 01-JAN-00:10 | 7041.87 | 17-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.06 | 0.00 | 01-JAN-00:10 | 3348.99 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.06 | 0.00 | 01-JAN-00:10 | 3348.99 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 46.97 | 0.00 | 01-JAN-00:10 | 7041.87 | 17-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 46.97 | 0.00 | 01-JAN-00:10 | 7041.87 | 17-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.62 | 0.00 | 01-JAN-00:10 | 7935.36 | 14-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1592.43 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1592.43 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.61 | 0.00 | 01-JAN-00:10 | 7935.36 | 14-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.61 | 0.00 | 01-JAN-00:10 | 7935.36 | 14-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 82.64 | 0.00 | 01-JAN-00:10 | 13797.89 | 28-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.85 | 0.00 | 01-JAN-00:10 | 8135.48 | 06-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.85 | 0.00 | 01-JAN-00:10 | 8135.48 | 06-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 79.79 | 0.00 | 01-JAN-00:10 | 13797.89 | 28-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 79.79 | 0.00 | 01-JAN-00:10 | 13797.89 | 28-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 44.72 | 0.00 | 01-JAN-00:10 | 7878.07 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1376.56 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1376.56 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 44.70 | 0.00 | 01-JAN-00:10 | 7878.07 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 44.70 | 0.00 | 01-JAN-00:10 | 7878.07 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 49.32 | 0.00 | 01-JAN-00:10 | 7248.70 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.11 | 0.00 | 01-JAN-00:10 | 3897.14 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.11 | 0.00 | 01-JAN-00:10 | 3897.14 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 49.22 | 0.00 | 01-JAN-00:10 | 7248.70 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 49.22 | 0.00 | 01-JAN-00:10 | 7248.70 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 46.16 | 0.00 | 01-JAN-00:10 | 8672.93 | 19-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 2420.74 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 2420.74 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 46.11 | 0.00 | 01-JAN-00:10 | 8672.93 | 19-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 46.11 | 0.00 | 01-JAN-00:10 | 8672.93 | 19-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 75.65 | 0.00 | 01-JAN-00:10 | 11083.51 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 2713.02 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 2713.02 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 75.61 | 0.00 | 01-JAN-00:10 | 11083.51 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 75.61 | 0.00 | 01-JAN-00:10 | 11083.51 | 02-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 45.97 | 0.00 | 01-JAN-00:10 | 8995.51 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2203.65 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 2203.65 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 45.91 | 0.00 | 01-JAN-00:10 | 8995.51 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 45.91 | 0.00 | 01-JAN-00:10 | 8995.51 | 26-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 38.47 | 0.00 | 01-JAN-00:10 | 5188.10 | 24-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5188.10 | 24-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5188.10 | 24-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 38.47 | 0.00 | 01-JAN-00:10 | 5188.10 | 24-JAN-12:10 |
EnergyTransfer:HVAC | 1467.04 | 0.00 | 01-JAN-00:10 | 276566.40 | 05-SEP-07:40 |
HeatingCoils:EnergyTransfer | 13.97 | 0.00 | 01-JAN-00:10 | 96220.29 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 1453.07 | 0.00 | 01-JAN-00:10 | 276566.40 | 05-SEP-07:40 |
EnergyTransfer:Plant | 38.47 | 0.00 | 01-JAN-00:10 | 5188.10 | 24-JAN-12:10 |
WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5188.10 | 24-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 38.47 | 0.00 | 01-JAN-00:10 | 5188.10 | 24-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -228.196 | 0.000 | 0.000 | 32.709 | 42.156 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.153 |
CORE_MID | 0.000 | 0.000 | 0.002 | -177.581 | 0.000 | 0.000 | 32.895 | 42.156 | 115.425 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -12.897 |
CORE_TOP | 0.000 | 0.000 | 0.119 | -178.544 | 0.000 | 0.000 | 33.264 | 42.156 | 115.425 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -12.420 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.776 | -50.911 | 0.000 | 0.000 | 7.151 | 5.135 | 24.333 | 25.178 | 0.000 | 0.971 | 9.175 | 0.000 | -19.631 | 0.000 | -2.177 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.305 | -49.324 | 0.000 | 0.000 | 4.428 | 3.205 | 15.404 | 43.473 | 0.000 | 0.630 | 0.000 | 0.000 | -12.451 | 0.000 | -1.523 | -4.146 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.384 | -77.110 | 0.000 | 0.000 | 6.998 | 5.036 | 24.332 | 71.522 | 0.000 | 0.950 | 0.000 | 0.000 | -19.595 | 0.000 | -2.388 | -10.128 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.446 | -47.533 | 0.000 | 0.000 | 4.501 | 3.232 | 15.403 | 41.775 | 0.000 | 0.622 | 0.000 | 0.000 | -13.563 | 0.000 | -1.530 | -3.353 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.060 | -46.970 | 0.000 | 0.000 | 7.087 | 5.122 | 24.333 | 25.330 | 0.000 | 0.542 | 6.493 | 0.000 | -20.749 | 0.000 | -1.247 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.009 | -47.606 | 0.000 | 0.000 | 4.394 | 3.199 | 15.404 | 43.540 | 0.000 | 0.341 | 0.000 | 0.000 | -13.500 | 0.000 | -0.898 | -4.883 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.845 | -79.790 | 0.000 | 0.000 | 6.968 | 5.029 | 24.332 | 71.704 | 0.000 | 14.832 | 0.003 | 0.000 | -21.298 | 0.000 | -16.034 | -8.589 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.012 | -44.704 | 0.000 | 0.000 | 4.436 | 3.225 | 15.403 | 41.913 | 0.000 | 0.335 | 0.002 | 0.000 | -14.748 | 0.000 | -0.903 | -4.970 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.106 | -49.218 | 0.000 | 0.000 | 7.069 | 5.135 | 24.333 | 25.105 | 0.000 | 0.821 | 9.503 | 0.000 | -20.896 | 0.000 | -1.958 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.043 | -46.114 | 0.000 | 0.000 | 3.244 | 3.205 | 15.404 | 43.300 | 0.000 | 0.527 | 0.002 | 0.000 | -13.173 | 0.000 | -1.364 | -5.071 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.039 | -75.608 | 0.000 | 0.000 | 6.946 | 5.036 | 24.332 | 71.476 | 0.000 | 0.802 | 0.003 | 0.000 | -20.684 | 0.000 | -2.123 | -10.216 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.059 | -45.906 | 0.000 | 0.000 | 4.452 | 3.232 | 15.403 | 41.781 | 0.000 | 0.522 | 0.000 | 0.000 | -14.391 | 0.000 | -1.369 | -3.784 |
TOPFLOOR_PLENUM | 5.457 | -60.520 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.245 | 57.129 | 0.000 | 0.000 | 0.000 | -3.311 | -0.000 |
MIDFLOOR_PLENUM | 2.054 | -31.272 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.276 | 31.439 | 0.000 | 0.000 | 0.000 | -3.497 | -0.000 |
FIRSTFLOOR_PLENUM | 0.761 | -34.714 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.996 | 35.777 | 0.000 | 0.000 | 0.000 | -2.820 | -0.000 |
Total Facility | 8.273 | -126.506 | 5.204 | -1245.115 | 0.000 | 0.000 | 166.541 | 176.258 | 647.750 | 546.098 | 0.000 | 25.415 | 149.529 | 0.000 | -204.679 | 0.000 | -43.144 | -105.610 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 30-MAY-05:12 | 0.00 | 0.00 | 0.00 | -34213.02 | 0.00 | 0.00 | 323.33 | 410.74 | 4048.06 | 0.00 | 0.00 | 0.00 | 29430.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 19-JUN-05:14 | 0.00 | 0.00 | 0.00 | -32303.19 | 0.00 | 0.00 | 315.78 | 410.74 | 3025.92 | 0.00 | 0.00 | 0.00 | 28550.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-AUG-04:02 | 0.00 | 0.00 | 0.00 | -33464.99 | 0.00 | 0.00 | 0.00 | 410.74 | 2442.06 | 0.00 | 0.00 | 0.00 | 30612.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-15:21 | 0.00 | 0.00 | 0.00 | -13758.85 | 0.00 | 0.00 | 25.59 | 20.65 | 478.42 | 3509.21 | 0.00 | 227.97 | 9497.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:21 | 0.00 | 0.00 | 0.00 | -13455.62 | 0.00 | 0.00 | 13.10 | 13.07 | 302.86 | 7791.00 | 0.00 | 35.35 | 5300.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:02 | 0.00 | 0.00 | 0.00 | -16700.38 | 0.00 | 0.00 | 22.26 | 20.65 | 478.41 | 11409.03 | 0.00 | 49.69 | 4720.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-APR-16:31 | 0.00 | 0.00 | 0.00 | -15471.24 | 0.00 | 0.00 | 12.11 | 13.07 | 302.86 | 8754.06 | 0.00 | 139.96 | 6249.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 27-AUG-17:41 | 0.00 | 0.00 | 0.00 | -10901.20 | 0.00 | 0.00 | 0.00 | 20.65 | 386.10 | 2373.07 | 0.00 | 242.69 | 7878.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 27-AUG-11:02 | 0.00 | 0.00 | 0.00 | -11037.53 | 0.00 | 0.00 | 14.99 | 13.07 | 302.86 | 4372.49 | 0.00 | 102.26 | 6231.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 28-JUN-17:00 | 0.00 | 0.00 | 0.00 | -13794.02 | 0.00 | 0.00 | 154.42 | 206.51 | 797.35 | 3218.37 | 0.00 | 14410.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4992.63 |
PERIMETER_BOT_ZN_4 | 27-AUG-17:41 | 0.00 | 0.00 | 0.00 | -12476.27 | 0.00 | 0.00 | 0.00 | 13.07 | 244.42 | 6500.48 | 0.00 | 137.01 | 5581.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-18:21 | 0.00 | 0.00 | 0.00 | -11595.67 | 0.00 | 0.00 | 0.00 | 20.65 | 386.10 | 3585.38 | 0.00 | 317.03 | 7286.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:11 | 0.00 | 0.00 | 0.00 | -12766.03 | 0.00 | 0.00 | 13.73 | 13.07 | 302.86 | 8039.10 | 0.00 | 77.87 | 4319.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 25-DEC-14:32 | 0.00 | 0.00 | 0.00 | -14016.40 | 0.00 | 0.00 | 23.73 | 20.65 | 478.41 | 11439.41 | 0.00 | 0.00 | 2075.95 | 0.00 | -0.00 | 0.00 | -21.75 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-18:21 | 0.00 | 0.00 | 0.00 | -13588.59 | 0.00 | 0.00 | 0.00 | 13.07 | 244.42 | 6284.65 | 0.00 | 176.30 | 6870.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:50 | 0.00 | -13017.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.10 | 12711.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 19-JUN-12:03 | 0.00 | -6615.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.16 | 6389.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 19-JUN-12:08 | 0.00 | -7362.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.95 | 7188.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:02 | 0.00 | 8307.62 | 0.00 | -202952.00 | 0.00 | 0.00 | 0.00 | 2080.62 | 13392.47 | 0.00 | 0.00 | 349.53 | 182206.62 | 0.00 | -3384.86 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:02 | 0.00 | 0.00 | 13463.66 | 0.00 | 0.00 | 0.00 | 900.09 | 1232.21 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18621.89 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 25841.18 | 0.00 | 0.00 | 0.00 | 485.73 | 410.74 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29763.56 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 11132.85 | 0.00 | 0.00 | 0.00 | 110.76 | 86.59 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1882.99 | 0.00 | -46.45 | -10038.65 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 8058.85 | 0.00 | 0.00 | 0.00 | 69.91 | 54.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1279.86 | 0.00 | -31.42 | -7276.10 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 11820.81 | 0.00 | 0.00 | 0.00 | 107.74 | 86.59 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2036.38 | 0.00 | -49.97 | -10566.67 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 7840.02 | 0.00 | 0.00 | 0.00 | 69.41 | 54.81 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1289.27 | 0.00 | -31.96 | -7046.82 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 7220.60 | 0.00 | 0.00 | 0.00 | 102.83 | 86.59 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2185.31 | 0.00 | -28.75 | -5833.85 |
PERIMETER_BOT_ZN_2 | 18-DEC-07:01 | 0.00 | 0.00 | 4272.81 | 0.00 | 0.00 | 0.00 | 120.27 | 164.45 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1781.78 | 0.00 | -39.71 | -3139.86 |
PERIMETER_BOT_ZN_1 | 07-DEC-07:10 | 0.00 | 0.00 | 8339.87 | 0.00 | 0.00 | 0.00 | 193.30 | 259.76 | 637.88 | 0.00 | 0.00 | 0.00 | 11753.27 | 0.00 | -3019.44 | 0.00 | -18164.64 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 4467.15 | 0.00 | 0.00 | 0.00 | 62.58 | 54.81 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1552.84 | 0.00 | -20.53 | -3414.98 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 8759.13 | 0.00 | 0.00 | 0.00 | 104.23 | 86.59 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2142.87 | 0.00 | -44.12 | -7400.84 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5484.20 | 0.00 | 0.00 | 0.00 | 65.78 | 54.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1456.46 | 0.00 | -29.59 | -4522.56 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 8395.69 | 0.00 | 0.00 | 0.00 | 100.88 | 86.59 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2298.84 | 0.00 | -46.87 | -6875.33 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5259.90 | 0.00 | 0.00 | 0.00 | 65.23 | 54.81 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1460.94 | 0.00 | -30.04 | -4292.78 |
TOPFLOOR_PLENUM | 02-JAN-07:02 | 9720.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -88.39 | -9631.73 |
MIDFLOOR_PLENUM | 25-DEC-15:52 | 5235.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.43 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5295.47 |
FIRSTFLOOR_PLENUM | 24-DEC-16:23 | 3411.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -75.56 | -3335.49 |
Total Facility | 02-JAN-07:02 | 6241.29 | 4397.13 | 116710.97 | -4397.13 | 0.00 | 0.00 | 4548.64 | 6241.87 | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21273.17 | 0.00 | -17107.14 | -113708.48 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4347 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9737 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2631 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7070 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.9084 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6418 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7174 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0764 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6315 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0754 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9542 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0748 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5585 | 2.5585 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1664 | 2.1664 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4187 | 2.4187 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8700 | 0.8700 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7740 | 0.7740 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9622 | 0.9622 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8835 | 0.8835 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7046 | 0.7046 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6717 | 0.6717 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7868 | 0.7868 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7132 | 0.7132 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7403 | 0.7403 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7337 | 0.7337 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8327 | 0.8327 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7899 | 0.7899 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4347 | 4.9737 | 5.4347 | 1.0764 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2631 | 4.7070 | 5.2631 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.9084 | 5.6418 | 5.9084 | 1.0748 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2792 | 1.2792 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0832 | 1.0832 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2093 | 1.2093 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4350 | 0.4350 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3870 | 0.3870 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4811 | 0.4811 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4417 | 0.4417 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3523 | 0.3523 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3359 | 0.3359 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3934 | 0.3934 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3566 | 0.3566 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3702 | 0.3702 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3668 | 0.3668 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4164 | 0.4164 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3950 | 0.3950 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7174 | 1.0764 | 1.0764 | 1.0764 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6315 | 1.0754 | 1.0754 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9542 | 1.0748 | 1.0748 | 1.0748 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 76.17 |
Number of hours cooling loads not met | 532.83 |
Number of hours not met | 609.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 8.15 | 82862.81 | 7.28 | 33832.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 396.89 | 85522.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 176.26 | 18725.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.08 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.63 | 830.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 132.93 | 27591.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 117.22 | 9789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1407.82 |
Natural Gas | 0.00 | 124.50 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1532.33 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 187.92 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 35.38 |
Space Heating | 1.64 |
Space Cooling | 79.66 |
Fans (All) | 26.68 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 282.57 |
Subtotal | 282.57 |
Natural Gas [MJ/m2] | |
Space Heating | 1.46 |
Service Water Heating | 23.53 |
Miscellaneous (All) | 24.99 |
Subtotal | 24.99 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.50 |
Space Heating | 1.01 |
Space Cooling | 25.90 |
Fans (All) | 8.67 |
Service Water Heating | 7.65 |
Receptacle Equipment | 42.27 |
Miscellaneous | 2.99 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2115. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 917. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8674.67 | 85.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8599.17 | 160.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8632.67 | 127.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8566.17 | 193.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8738.83 | 21.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8593.17 | 166.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8601.33 | 158.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8577.00 | 183.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8698.17 | 61.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8628.83 | 131.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8654.33 | 105.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8594.83 | 165.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8470.83 | 289.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
Min | 8470.83 | 7.67 | 0.00 | 0.00 | 0.00 |
Max | 8752.33 | 289.17 | 0.00 | 0.00 | 0.00 |
Average | 8653.38 | 106.62 | 0.00 | 0.00 | 0.00 |
Sum | 155760.83 | 1919.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.67 | 4.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24816.67 | 92.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 92.33 | 0.00 | 0.00 | 0.00 |
Average | 34137.74 | 5.59 | 0.00 | 0.00 | 0.00 |
Sum | 614479.33 | 100.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8478.50 | 281.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8523.50 | 236.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8598.83 | 161.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8404.83 | 355.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8355.83 | 404.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8383.17 | 376.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8349.67 | 410.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8405.33 | 354.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8330.67 | 429.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8306.50 | 453.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8334.67 | 425.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8358.67 | 401.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8306.83 | 453.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8332.17 | 427.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8308.33 | 451.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8033.17 | 726.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8454.67 | 305.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8481.00 | 279.00 | 0.00 | 0.00 | 0.00 |
Min | 8033.17 | 161.17 | 0.00 | 0.00 | 0.00 |
Max | 8598.83 | 726.83 | 0.00 | 0.00 | 0.00 |
Average | 8374.80 | 385.20 | 0.00 | 0.00 | 0.00 |
Sum | 150746.33 | 6933.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128161.00 | 143.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128199.17 | 104.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128160.50 | 143.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24857.33 | 51.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13972.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24874.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13983.83 | 32.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24903.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14007.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24699.83 | 209.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24857.17 | 51.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10115.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24876.67 | 32.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13981.00 | 35.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128199.17 | 209.17 | 0.00 | 0.00 | 0.00 |
Average | 34092.53 | 50.81 | 0.00 | 0.00 | 0.00 |
Sum | 613665.50 | 914.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145785E+11 | 16331.86 | 27-JAN-17:00 | 26.00 | 9.22 | 0.198336E+10 | 2606.66 | 23-JAN-14:20 | 26.00 | 9.22 |
February | 0.115433E+11 | 17491.96 | 01-FEB-07:01 | 5.00 | 3.59 | 0.179947E+10 | 2606.68 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.155673E+11 | 22875.63 | 20-MAR-06:03 | 11.52 | 7.81 | 0.215566E+10 | 2606.68 | 17-MAR-09:00 | 11.52 | 7.81 |
April | 0.194121E+11 | 32175.41 | 17-APR-06:02 | 16.17 | 10.40 | 0.191599E+10 | 2606.67 | 03-APR-09:30 | 16.17 | 10.40 |
May | 0.220003E+11 | 34212.85 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207622E+10 | 2606.66 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.240131E+11 | 34155.59 | 20-JUN-05:12 | 21.33 | 9.32 | 0.207043E+10 | 2606.67 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.237238E+11 | 33508.00 | 06-JUL-05:12 | 22.33 | 12.67 | 0.192450E+10 | 2606.71 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.247860E+11 | 33333.20 | 29-AUG-05:03 | 25.83 | 17.61 | 0.216001E+10 | 2606.77 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.225363E+11 | 33419.12 | 12-SEP-05:12 | 22.53 | 18.75 | 0.191926E+10 | 2606.66 | 15-SEP-09:20 | 25.90 | 16.61 |
October | 0.202457E+11 | 34076.78 | 10-OCT-05:12 | 17.33 | 11.48 | 0.199383E+10 | 2606.66 | 10-OCT-09:20 | 27.00 | 15.93 |
November | 0.165539E+11 | 32605.56 | 13-NOV-07:02 | 16.00 | 16.00 | 0.197214E+10 | 2606.74 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.132347E+11 | 15963.22 | 28-DEC-17:00 | 18.60 | 7.88 | 0.191438E+10 | 2606.65 | 13-DEC-10:09 | 18.60 | 7.88 |
Annual Sum or Average | 0.228195E+12 | 0.238852E+11 | ||||||||
Minimum of Months | 0.115433E+11 | 15963.22 | 5.00 | 3.59 | 0.179947E+10 | 2606.65 | 11.52 | 7.81 | ||
Maximum of Months | 0.247860E+11 | 34212.85 | 26.00 | 18.75 | 0.216001E+10 | 2606.77 | 33.33 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167159E+10 | 5650.51 | 31-JAN-16:10 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.833878E+09 | 4138.97 | 23-FEB-14:30 | 18.00 | 10.57 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.57 |
March | 0.201283E+10 | 6773.59 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.590503E+10 | 10780.36 | 14-APR-15:00 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.761170E+10 | 10696.82 | 15-MAY-15:20 | 36.00 | 15.08 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 15.08 |
June | 0.105800E+11 | 13016.96 | 28-JUN-14:50 | 41.83 | 19.32 | 0.00 | 0.00 | 01-JUN-00:10 | 41.83 | 19.32 |
July | 0.924660E+10 | 12218.18 | 20-JUL-14:20 | 39.33 | 20.22 | 0.00 | 0.00 | 01-JUL-00:10 | 39.33 | 20.22 |
August | 0.905990E+10 | 12211.10 | 25-AUG-15:10 | 41.00 | 17.61 | 0.00 | 0.00 | 01-AUG-00:10 | 41.00 | 17.61 |
September | 0.695206E+10 | 11315.23 | 07-SEP-15:00 | 37.20 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.20 | 19.77 |
October | 0.399590E+10 | 10359.41 | 02-OCT-14:10 | 35.00 | 19.69 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.69 |
November | 0.179195E+10 | 6793.69 | 01-NOV-15:40 | 28.33 | 15.88 | 0.00 | 0.00 | 01-NOV-00:10 | 28.33 | 15.88 |
December | 0.859826E+09 | 4339.76 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.605213E+11 | 0.00 | ||||||||
Minimum of Months | 0.833878E+09 | 4138.97 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.105800E+11 | 13016.96 | 41.83 | 20.22 | 0.00 | 0.00 | 41.83 | 20.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476314E+09 | 1859.03 | 27-JAN-16:50 | 26.17 | 9.31 | 0.00 | 0.00 | 01-JAN-00:10 | 26.17 | 9.31 |
February | 0.236427E+09 | 886.41 | 01-FEB-16:30 | 15.50 | 6.82 | 0.00 | 0.00 | 01-FEB-00:10 | 15.50 | 6.82 |
March | 0.660129E+09 | 2275.43 | 17-MAR-16:00 | 26.60 | 14.13 | 0.00 | 0.00 | 01-MAR-00:10 | 26.60 | 14.13 |
April | 0.278554E+10 | 4488.36 | 24-APR-15:50 | 33.83 | 13.43 | 0.00 | 0.00 | 01-APR-00:10 | 33.83 | 13.43 |
May | 0.392739E+10 | 4999.32 | 08-MAY-12:08 | 32.17 | 13.12 | 0.00 | 0.00 | 01-MAY-00:10 | 32.17 | 13.12 |
June | 0.559828E+10 | 6615.63 | 19-JUN-12:03 | 37.17 | 17.20 | 0.00 | 0.00 | 01-JUN-00:10 | 37.17 | 17.20 |
July | 0.518386E+10 | 6019.18 | 17-JUL-12:03 | 35.83 | 21.43 | 0.00 | 0.00 | 01-JUL-00:10 | 35.83 | 21.43 |
August | 0.510835E+10 | 6191.59 | 28-AUG-10:10 | 34.33 | 21.40 | 0.00 | 0.00 | 01-AUG-00:10 | 34.33 | 21.40 |
September | 0.417479E+10 | 6150.39 | 05-SEP-06:10 | 20.78 | 19.22 | 0.00 | 0.00 | 01-SEP-00:10 | 20.78 | 19.22 |
October | 0.221104E+10 | 5366.18 | 02-OCT-14:30 | 35.00 | 19.50 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.50 |
November | 0.713460E+09 | 2722.28 | 01-NOV-16:00 | 28.00 | 15.72 | 0.00 | 0.00 | 01-NOV-00:10 | 28.00 | 15.72 |
December | 0.196070E+09 | 2606.52 | 14-DEC-07:01 | 1.33 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 1.33 | -1.0 |
Annual Sum or Average | 0.312716E+11 | 0.00 | ||||||||
Minimum of Months | 0.196070E+09 | 886.41 | 1.33 | -1.0 | 0.00 | 0.00 | 1.33 | -1.0 | ||
Maximum of Months | 0.559828E+10 | 6615.63 | 37.17 | 21.43 | 0.00 | 0.00 | 37.17 | 21.43 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102161E+10 | 2370.08 | 27-JAN-17:00 | 26.00 | 9.22 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 9.22 |
February | 0.529401E+09 | 2198.54 | 01-FEB-07:09 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.106031E+10 | 2551.05 | 27-MAR-06:01 | 1.97 | -1.0 | 0.00 | 0.00 | 01-MAR-00:10 | 1.97 | -1.0 |
April | 0.301482E+10 | 4540.78 | 24-APR-12:08 | 31.33 | 12.22 | 0.00 | 0.00 | 01-APR-00:10 | 31.33 | 12.22 |
May | 0.398327E+10 | 5136.74 | 08-MAY-12:08 | 32.17 | 13.12 | 0.00 | 0.00 | 01-MAY-00:10 | 32.17 | 13.12 |
June | 0.536875E+10 | 7362.44 | 19-JUN-12:08 | 37.17 | 17.20 | 0.00 | 0.00 | 01-JUN-00:10 | 37.17 | 17.20 |
July | 0.513510E+10 | 7054.54 | 05-JUL-12:07 | 36.17 | 15.62 | 0.00 | 0.00 | 01-JUL-00:10 | 36.17 | 15.62 |
August | 0.519285E+10 | 6251.41 | 08-AUG-12:09 | 36.83 | 20.66 | 0.00 | 0.00 | 01-AUG-00:10 | 36.83 | 20.66 |
September | 0.451178E+10 | 6316.82 | 05-SEP-06:10 | 20.78 | 19.22 | 0.00 | 0.00 | 01-SEP-00:10 | 20.78 | 19.22 |
October | 0.290122E+10 | 5264.39 | 02-OCT-17:08 | 31.33 | 19.60 | 0.00 | 0.00 | 01-OCT-00:10 | 31.33 | 19.60 |
November | 0.143720E+10 | 3135.78 | 02-NOV-16:00 | 26.00 | 15.13 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 15.13 |
December | 0.557169E+09 | 2475.95 | 07-DEC-07:01 | 1.33 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | 1.33 | -4.1 |
Annual Sum or Average | 0.347135E+11 | 0.00 | ||||||||
Minimum of Months | 0.529401E+09 | 2198.54 | 1.33 | -4.1 | 0.00 | 0.00 | 1.33 | -4.1 | ||
Maximum of Months | 0.536875E+10 | 7362.44 | 37.17 | 20.66 | 0.00 | 0.00 | 37.17 | 20.66 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101337E+11 | 12227.89 | 27-JAN-17:00 | 26.00 | 9.22 | 0.194724E+10 | 2606.64 | 09-JAN-10:20 | 26.00 | 9.22 |
February | 0.802442E+10 | 11110.71 | 01-FEB-17:00 | 15.00 | 6.61 | 0.175958E+10 | 2606.65 | 10-FEB-14:09 | 15.83 | 11.90 |
March | 0.110421E+11 | 13017.12 | 20-MAR-16:00 | 28.30 | 14.35 | 0.213459E+10 | 2606.66 | 17-MAR-09:00 | 28.30 | 14.35 |
April | 0.155947E+11 | 27057.16 | 17-APR-06:02 | 16.17 | 10.40 | 0.191280E+10 | 2606.66 | 03-APR-09:30 | 16.17 | 10.40 |
May | 0.182565E+11 | 29808.61 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207489E+10 | 2606.66 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.207585E+11 | 32308.13 | 19-JUN-05:14 | 22.33 | 10.28 | 0.207003E+10 | 2606.67 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.202337E+11 | 32196.30 | 05-JUL-05:14 | 23.00 | 11.31 | 0.192392E+10 | 2606.70 | 21-JUL-09:20 | 31.33 | 20.88 |
August | 0.206002E+11 | 28892.02 | 22-AUG-05:12 | 23.00 | 15.21 | 0.215900E+10 | 2606.70 | 28-AUG-09:39 | 33.00 | 21.02 |
September | 0.181613E+11 | 31841.71 | 25-SEP-05:14 | 23.63 | 17.70 | 0.191798E+10 | 2606.68 | 05-SEP-09:20 | 23.63 | 17.70 |
October | 0.149633E+11 | 29381.20 | 10-OCT-05:12 | 17.33 | 11.48 | 0.198740E+10 | 2606.67 | 03-OCT-13:39 | 17.33 | 11.48 |
November | 0.111236E+11 | 13677.24 | 01-NOV-16:00 | 28.00 | 15.72 | 0.195561E+10 | 2606.71 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.868800E+10 | 11206.99 | 27-DEC-17:00 | 19.00 | 9.46 | 0.185623E+10 | 2606.62 | 04-DEC-10:20 | 19.00 | 9.46 |
Annual Sum or Average | 0.177580E+12 | 0.236993E+11 | ||||||||
Minimum of Months | 0.802442E+10 | 11110.71 | 15.00 | 6.61 | 0.175958E+10 | 2606.62 | 15.83 | 9.22 | ||
Maximum of Months | 0.207585E+11 | 32308.13 | 28.30 | 17.70 | 0.215900E+10 | 2606.71 | 33.33 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.882310E+10 | 12315.34 | 27-JAN-17:00 | 26.00 | 9.22 | 0.188522E+10 | 2606.62 | 23-JAN-14:20 | 26.00 | 9.22 |
February | 0.718532E+10 | 10582.50 | 22-FEB-17:00 | 20.00 | 11.26 | 0.169163E+10 | 2606.64 | 10-FEB-14:30 | 20.00 | 11.26 |
March | 0.101834E+11 | 14282.69 | 17-MAR-16:00 | 26.60 | 14.13 | 0.208244E+10 | 2606.65 | 14-MAR-13:50 | 26.60 | 14.13 |
April | 0.158959E+11 | 24468.89 | 24-APR-06:02 | 16.50 | 5.42 | 0.190708E+10 | 2606.67 | 03-APR-09:20 | 16.50 | 5.42 |
May | 0.192545E+11 | 32688.73 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207376E+10 | 2606.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.229719E+11 | 32650.78 | 12-JUN-05:12 | 20.33 | 10.58 | 0.207071E+10 | 2606.67 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.222263E+11 | 33102.43 | 24-JUL-04:02 | 25.42 | 19.04 | 0.192516E+10 | 2606.72 | 21-JUL-09:09 | 25.42 | 19.04 |
August | 0.221598E+11 | 33455.67 | 21-AUG-04:02 | 25.00 | 16.17 | 0.215941E+10 | 2606.71 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.188723E+11 | 33176.08 | 08-SEP-04:02 | 25.92 | 19.60 | 0.191772E+10 | 2606.67 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.139752E+11 | 32962.88 | 02-OCT-04:02 | 26.00 | 17.05 | 0.196746E+10 | 2606.66 | 05-OCT-09:20 | 27.00 | 16.87 |
November | 0.965939E+10 | 14717.88 | 01-NOV-16:00 | 28.00 | 15.72 | 0.190809E+10 | 2606.68 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.733674E+10 | 10691.43 | 22-DEC-17:00 | 24.00 | 9.52 | 0.174127E+10 | 2606.59 | 26-DEC-14:20 | 23.00 | 10.23 |
Annual Sum or Average | 0.178544E+12 | 0.233299E+11 | ||||||||
Minimum of Months | 0.718532E+10 | 10582.50 | 16.50 | 5.42 | 0.169163E+10 | 2606.59 | 16.50 | 5.42 | ||
Maximum of Months | 0.229719E+11 | 33455.67 | 28.00 | 19.60 | 0.215941E+10 | 2606.72 | 33.33 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152160E+10 | 2846.68 | 31-JAN-16:30 | 29.00 | 10.73 | 0.371940E+09 | 549.49 | 20-JAN-14:20 | 29.00 | 10.73 |
February | 0.117339E+10 | 2075.53 | 22-FEB-16:20 | 20.67 | 11.54 | 0.330494E+09 | 549.48 | 23-FEB-14:20 | 18.00 | 10.64 |
March | 0.203794E+10 | 4096.37 | 16-MAR-16:00 | 28.80 | 13.95 | 0.416887E+09 | 549.50 | 21-MAR-13:20 | 25.17 | 12.74 |
April | 0.431316E+10 | 13167.59 | 30-APR-16:31 | 32.33 | 11.86 | 0.398380E+09 | 549.50 | 12-APR-09:20 | 32.33 | 11.86 |
May | 0.604401E+10 | 11830.47 | 07-MAY-17:32 | 35.33 | 14.08 | 0.437033E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.860343E+10 | 13596.53 | 25-JUN-18:11 | 37.33 | 14.77 | 0.437358E+09 | 549.51 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.787678E+10 | 13758.58 | 16-JUL-15:21 | 37.00 | 20.09 | 0.406785E+09 | 549.52 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.735100E+10 | 13605.78 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455720E+09 | 549.51 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.586089E+10 | 13157.81 | 17-SEP-13:43 | 34.50 | 17.78 | 0.404259E+09 | 549.50 | 22-SEP-09:20 | 24.20 | 17.34 |
October | 0.330861E+10 | 11423.35 | 02-OCT-04:02 | 26.00 | 17.05 | 0.402643E+09 | 549.51 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.174948E+10 | 4050.79 | 01-NOV-15:30 | 28.50 | 15.96 | 0.382863E+09 | 549.50 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.107073E+10 | 1979.07 | 22-DEC-16:40 | 24.33 | 9.71 | 0.335290E+09 | 549.47 | 22-DEC-14:39 | 24.33 | 9.71 |
Annual Sum or Average | 0.509110E+11 | 0.477965E+10 | ||||||||
Minimum of Months | 0.107073E+10 | 1979.07 | 20.67 | 9.71 | 0.330494E+09 | 549.47 | 18.00 | 9.71 | ||
Maximum of Months | 0.860343E+10 | 13758.58 | 38.00 | 20.37 | 0.455720E+09 | 549.52 | 33.33 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153891E+10 | 2995.41 | 27-JAN-10:30 | 21.00 | 7.83 | 0.254293E+09 | 347.88 | 23-JAN-14:20 | 21.00 | 7.83 |
February | 0.111582E+10 | 3242.71 | 23-FEB-10:30 | 15.00 | 11.05 | 0.228017E+09 | 347.88 | 14-FEB-10:20 | 15.00 | 11.05 |
March | 0.213111E+10 | 4538.93 | 23-MAR-10:20 | 22.33 | 10.61 | 0.278300E+09 | 347.89 | 14-MAR-13:50 | 22.33 | 10.61 |
April | 0.489290E+10 | 12953.20 | 30-APR-09:52 | 28.00 | 10.47 | 0.255239E+09 | 347.90 | 03-APR-09:20 | 28.00 | 10.47 |
May | 0.618908E+10 | 12532.70 | 28-MAY-10:32 | 30.33 | 12.86 | 0.277385E+09 | 348.20 | 11-MAY-09:00 | 30.33 | 12.86 |
June | 0.785397E+10 | 12752.44 | 18-JUN-09:02 | 32.33 | 17.55 | 0.277149E+09 | 348.16 | 08-JUN-09:00 | 32.33 | 17.55 |
July | 0.711004E+10 | 13457.75 | 23-JUL-09:21 | 32.50 | 22.15 | 0.257820E+09 | 348.12 | 28-JUL-09:00 | 31.00 | 20.55 |
August | 0.690081E+10 | 12707.85 | 13-AUG-09:32 | 32.67 | 21.08 | 0.288827E+09 | 348.15 | 01-AUG-09:00 | 32.67 | 21.08 |
September | 0.534303E+10 | 11910.54 | 10-SEP-10:22 | 32.45 | 19.22 | 0.256315E+09 | 348.42 | 08-SEP-09:00 | 32.45 | 19.22 |
October | 0.351263E+10 | 8107.18 | 09-OCT-15:02 | 32.17 | 17.27 | 0.262374E+09 | 347.89 | 17-OCT-09:20 | 24.67 | 9.84 |
November | 0.175899E+10 | 3857.11 | 01-NOV-10:05 | 23.33 | 16.05 | 0.255379E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.976211E+09 | 1857.84 | 01-DEC-10:30 | 18.50 | 8.87 | 0.233768E+09 | 347.88 | 13-DEC-10:20 | 11.67 | 10.42 |
Annual Sum or Average | 0.493235E+11 | 0.312487E+10 | ||||||||
Minimum of Months | 0.976211E+09 | 1857.84 | 15.00 | 7.83 | 0.228017E+09 | 347.88 | 11.67 | 7.83 | ||
Maximum of Months | 0.785397E+10 | 13457.75 | 32.67 | 22.15 | 0.288827E+09 | 348.42 | 32.67 | 21.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603785E+10 | 15693.43 | 15-JAN-13:42 | 22.67 | 10.33 | 0.404094E+09 | 549.68 | 24-JAN-14:00 | 26.00 | 10.66 |
February | 0.320333E+10 | 9404.40 | 28-FEB-14:05 | 18.17 | 7.92 | 0.357624E+09 | 549.60 | 23-FEB-14:39 | 18.17 | 7.92 |
March | 0.402799E+10 | 8663.50 | 16-MAR-13:40 | 27.53 | 13.09 | 0.431635E+09 | 549.52 | 14-MAR-13:50 | 27.53 | 13.09 |
April | 0.644644E+10 | 15094.65 | 30-APR-16:31 | 32.33 | 11.86 | 0.399539E+09 | 549.79 | 12-APR-13:00 | 32.33 | 11.86 |
May | 0.667016E+10 | 14702.39 | 07-MAY-13:32 | 34.67 | 14.00 | 0.436689E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.831145E+10 | 14681.33 | 04-JUN-16:41 | 38.00 | 16.06 | 0.437146E+09 | 549.51 | 19-JUN-13:20 | 38.33 | 18.31 |
July | 0.806731E+10 | 15330.97 | 16-JUL-15:21 | 37.00 | 20.09 | 0.406742E+09 | 549.71 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.867982E+10 | 15231.54 | 13-AUG-16:11 | 38.00 | 20.37 | 0.455874E+09 | 550.28 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.828630E+10 | 15451.33 | 10-SEP-13:42 | 34.90 | 19.64 | 0.404846E+09 | 566.40 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.737931E+10 | 16699.83 | 09-OCT-13:02 | 31.17 | 17.33 | 0.412637E+09 | 568.86 | 02-OCT-13:09 | 31.17 | 17.33 |
November | 0.561028E+10 | 15666.31 | 19-NOV-14:12 | 26.33 | 11.25 | 0.404609E+09 | 549.65 | 14-NOV-14:00 | 26.33 | 11.25 |
December | 0.439113E+10 | 15982.89 | 25-DEC-14:32 | 26.00 | 11.71 | 0.381507E+09 | 549.66 | 22-DEC-14:50 | 26.00 | 11.71 |
Annual Sum or Average | 0.771114E+11 | 0.493294E+10 | ||||||||
Minimum of Months | 0.320333E+10 | 8663.50 | 18.17 | 7.92 | 0.357624E+09 | 549.50 | 18.17 | 7.92 | ||
Maximum of Months | 0.867982E+10 | 16699.83 | 38.00 | 20.37 | 0.455874E+09 | 568.86 | 38.33 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187620E+10 | 6034.49 | 24-JAN-16:30 | 24.50 | 10.78 | 0.240069E+09 | 347.85 | 23-JAN-14:20 | 24.50 | 10.78 |
February | 0.120884E+10 | 5960.34 | 22-FEB-16:30 | 20.50 | 11.47 | 0.213335E+09 | 347.84 | 14-FEB-14:20 | 20.50 | 11.47 |
March | 0.213797E+10 | 9166.89 | 18-MAR-17:06 | 26.92 | 12.85 | 0.266004E+09 | 347.85 | 21-MAR-13:20 | 25.17 | 12.74 |
April | 0.477377E+10 | 15471.45 | 30-APR-16:31 | 32.33 | 11.86 | 0.252780E+09 | 347.85 | 03-APR-09:20 | 32.33 | 11.86 |
May | 0.589556E+10 | 14624.92 | 28-MAY-17:11 | 32.67 | 12.64 | 0.276752E+09 | 347.86 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.752129E+10 | 14974.55 | 25-JUN-17:31 | 38.00 | 15.08 | 0.277006E+09 | 347.86 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.634413E+10 | 15085.80 | 16-JUL-17:21 | 36.50 | 21.23 | 0.257653E+09 | 347.86 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.623752E+10 | 15019.81 | 13-AUG-16:51 | 38.00 | 19.94 | 0.288680E+09 | 347.86 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.497600E+10 | 14133.53 | 04-SEP-15:52 | 31.60 | 21.45 | 0.256138E+09 | 347.86 | 22-SEP-09:20 | 24.20 | 17.34 |
October | 0.336286E+10 | 14570.34 | 09-OCT-16:22 | 32.50 | 17.31 | 0.256137E+09 | 347.86 | 03-OCT-13:30 | 32.50 | 17.31 |
November | 0.202342E+10 | 9411.27 | 19-NOV-15:32 | 27.00 | 11.63 | 0.245632E+09 | 347.85 | 16-NOV-14:20 | 27.00 | 11.63 |
December | 0.117712E+10 | 10053.77 | 25-DEC-16:33 | 24.67 | 11.46 | 0.221203E+09 | 347.84 | 22-DEC-14:50 | 24.67 | 11.46 |
Annual Sum or Average | 0.475347E+11 | 0.305139E+10 | ||||||||
Minimum of Months | 0.117712E+10 | 5960.34 | 20.50 | 10.78 | 0.213335E+09 | 347.84 | 20.50 | 10.78 | ||
Maximum of Months | 0.752129E+10 | 15471.45 | 38.00 | 21.45 | 0.288680E+09 | 347.86 | 33.33 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159994E+10 | 2100.31 | 27-JAN-16:30 | 26.50 | 9.48 | 0.380852E+09 | 549.49 | 06-JAN-14:20 | 26.50 | 9.48 |
February | 0.124247E+10 | 1246.84 | 22-FEB-16:40 | 20.33 | 11.40 | 0.331771E+09 | 542.91 | 22-FEB-14:00 | 20.33 | 11.40 |
March | 0.172271E+10 | 2728.74 | 20-MAR-14:30 | 27.70 | 14.31 | 0.415356E+09 | 549.49 | 21-MAR-13:20 | 25.17 | 12.74 |
April | 0.330053E+10 | 4694.65 | 25-APR-15:00 | 33.00 | 15.10 | 0.399610E+09 | 549.50 | 12-APR-09:20 | 33.00 | 15.10 |
May | 0.458936E+10 | 5308.21 | 08-MAY-15:20 | 34.00 | 13.77 | 0.436549E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.693641E+10 | 10746.37 | 25-JUN-18:11 | 37.33 | 14.77 | 0.436889E+09 | 549.51 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.709343E+10 | 10878.41 | 02-JUL-18:21 | 37.00 | 14.49 | 0.406556E+09 | 549.51 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.700009E+10 | 10901.08 | 27-AUG-17:41 | 39.17 | 18.06 | 0.455745E+09 | 549.53 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.618606E+10 | 9832.90 | 17-SEP-13:32 | 34.60 | 17.84 | 0.404918E+09 | 549.50 | 19-SEP-09:20 | 29.23 | 14.41 |
October | 0.370829E+10 | 9469.29 | 01-OCT-13:53 | 37.00 | 19.01 | 0.415278E+09 | 549.50 | 05-OCT-09:20 | 27.00 | 16.87 |
November | 0.211016E+10 | 3781.05 | 02-NOV-14:00 | 27.00 | 15.44 | 0.402083E+09 | 549.50 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.148082E+10 | 1762.33 | 01-DEC-15:30 | 23.30 | 10.04 | 0.358208E+09 | 549.48 | 01-DEC-14:20 | 23.30 | 10.04 |
Annual Sum or Average | 0.469703E+11 | 0.484381E+10 | ||||||||
Minimum of Months | 0.124247E+10 | 1246.84 | 20.33 | 9.48 | 0.331771E+09 | 542.91 | 18.00 | 9.48 | ||
Maximum of Months | 0.709343E+10 | 10901.08 | 39.17 | 19.01 | 0.455745E+09 | 549.53 | 33.33 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165933E+10 | 2871.72 | 27-JAN-10:30 | 21.00 | 7.83 | 0.259234E+09 | 347.88 | 23-JAN-14:20 | 21.00 | 7.83 |
February | 0.112860E+10 | 2577.41 | 23-FEB-10:30 | 15.00 | 11.05 | 0.231309E+09 | 347.87 | 14-FEB-10:20 | 15.00 | 11.05 |
March | 0.180441E+10 | 3565.13 | 23-MAR-10:30 | 22.70 | 10.73 | 0.281006E+09 | 347.88 | 23-MAR-13:20 | 25.17 | 11.90 |
April | 0.422963E+10 | 10827.17 | 30-APR-09:52 | 28.00 | 10.47 | 0.255646E+09 | 347.89 | 03-APR-09:30 | 28.00 | 10.47 |
May | 0.522443E+10 | 10539.25 | 28-MAY-10:32 | 30.33 | 12.86 | 0.277432E+09 | 348.03 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.677904E+10 | 10610.81 | 18-JUN-09:12 | 32.67 | 17.60 | 0.277087E+09 | 348.07 | 02-JUN-09:50 | 32.67 | 17.60 |
July | 0.665989E+10 | 10880.71 | 23-JUL-09:51 | 33.00 | 22.32 | 0.257833E+09 | 348.01 | 05-JUL-09:00 | 33.00 | 22.32 |
August | 0.679427E+10 | 11037.28 | 27-AUG-11:02 | 37.17 | 17.45 | 0.288981E+09 | 348.09 | 11-AUG-09:50 | 37.17 | 17.45 |
September | 0.567489E+10 | 10900.59 | 04-SEP-10:12 | 26.97 | 21.90 | 0.256713E+09 | 349.73 | 05-SEP-07:00 | 24.40 | 20.16 |
October | 0.405620E+10 | 8092.57 | 01-OCT-11:13 | 34.33 | 19.35 | 0.265562E+09 | 347.89 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.224625E+10 | 3981.31 | 02-NOV-08:40 | 21.00 | 14.47 | 0.261007E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.134888E+10 | 2520.41 | 01-DEC-10:30 | 18.50 | 8.87 | 0.247598E+09 | 347.88 | 13-DEC-10:20 | 11.67 | 10.42 |
Annual Sum or Average | 0.476058E+11 | 0.315941E+10 | ||||||||
Minimum of Months | 0.112860E+10 | 2520.41 | 15.00 | 7.83 | 0.231309E+09 | 347.87 | 11.67 | 7.83 | ||
Maximum of Months | 0.679427E+10 | 11037.28 | 37.17 | 22.32 | 0.288981E+09 | 349.73 | 37.17 | 22.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532200E+10 | 12550.08 | 16-JAN-15:53 | 24.00 | 8.91 | 0.406266E+09 | 560.97 | 17-JAN-14:39 | 24.67 | 9.24 |
February | 0.193018E+10 | 7721.54 | 28-FEB-13:07 | 17.17 | 7.91 | 0.344011E+09 | 549.51 | 01-FEB-14:20 | 17.17 | 7.91 |
March | 0.280301E+10 | 9945.09 | 16-MAR-16:10 | 28.72 | 13.89 | 0.418312E+09 | 549.52 | 14-MAR-13:50 | 28.72 | 13.89 |
April | 0.605771E+10 | 11997.89 | 30-APR-16:31 | 32.33 | 11.86 | 0.398651E+09 | 626.59 | 14-APR-12:09 | 32.33 | 11.86 |
May | 0.681717E+10 | 12047.52 | 15-MAY-17:00 | 37.00 | 15.57 | 0.437913E+09 | 626.88 | 18-MAY-12:09 | 34.00 | 13.67 |
June | 0.931490E+10 | 13797.89 | 28-JUN-17:00 | 42.00 | 19.33 | 0.446067E+09 | 738.03 | 28-JUN-12:09 | 42.00 | 19.33 |
July | 0.943745E+10 | 12999.38 | 20-JUL-17:00 | 39.00 | 20.23 | 0.414299E+09 | 724.44 | 12-JUL-12:09 | 39.00 | 20.23 |
August | 0.105909E+11 | 13638.80 | 25-AUG-17:00 | 41.00 | 17.61 | 0.467600E+09 | 773.77 | 25-AUG-12:09 | 41.00 | 17.61 |
September | 0.100042E+11 | 12938.10 | 08-SEP-16:10 | 38.02 | 19.47 | 0.417303E+09 | 723.44 | 07-SEP-12:09 | 38.02 | 19.47 |
October | 0.803160E+10 | 13583.00 | 09-OCT-13:02 | 31.17 | 17.33 | 0.423491E+09 | 704.61 | 02-OCT-12:09 | 31.17 | 17.33 |
November | 0.554113E+10 | 12722.24 | 05-NOV-13:23 | 22.00 | 8.08 | 0.408516E+09 | 584.57 | 20-NOV-14:20 | 27.00 | 11.68 |
December | 0.394137E+10 | 12675.28 | 25-DEC-12:02 | 23.33 | 10.56 | 0.380519E+09 | 556.36 | 26-DEC-14:09 | 23.00 | 10.20 |
Annual Sum or Average | 0.797916E+11 | 0.496295E+10 | ||||||||
Minimum of Months | 0.193018E+10 | 7721.54 | 17.17 | 7.91 | 0.344011E+09 | 549.51 | 17.17 | 7.91 | ||
Maximum of Months | 0.105909E+11 | 13797.89 | 42.00 | 20.23 | 0.467600E+09 | 773.77 | 42.00 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180806E+10 | 5001.33 | 24-JAN-16:40 | 24.33 | 10.79 | 0.252005E+09 | 347.85 | 23-JAN-14:20 | 24.33 | 10.79 |
February | 0.111451E+10 | 4288.70 | 22-FEB-16:30 | 20.50 | 11.47 | 0.219481E+09 | 347.84 | 02-FEB-14:20 | 20.50 | 11.47 |
March | 0.170711E+10 | 5253.65 | 18-MAR-17:06 | 26.92 | 12.85 | 0.271381E+09 | 347.85 | 17-MAR-09:20 | 26.92 | 12.85 |
April | 0.400291E+10 | 11933.47 | 30-APR-16:31 | 32.33 | 11.86 | 0.254904E+09 | 347.85 | 12-APR-09:20 | 32.33 | 11.86 |
May | 0.486315E+10 | 11628.86 | 29-MAY-17:11 | 31.67 | 13.84 | 0.277151E+09 | 347.86 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.643920E+10 | 11731.92 | 25-JUN-17:31 | 38.00 | 15.08 | 0.276985E+09 | 347.86 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.586349E+10 | 12123.71 | 02-JUL-18:21 | 37.00 | 14.49 | 0.257693E+09 | 347.86 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.609320E+10 | 12476.18 | 27-AUG-17:41 | 39.17 | 18.06 | 0.288849E+09 | 347.87 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.527433E+10 | 11917.82 | 04-SEP-17:32 | 31.60 | 21.23 | 0.256664E+09 | 347.86 | 15-SEP-09:20 | 25.90 | 16.61 |
October | 0.372943E+10 | 11802.57 | 15-OCT-16:22 | 30.50 | 12.33 | 0.264655E+09 | 347.86 | 10-OCT-09:20 | 30.50 | 12.33 |
November | 0.236626E+10 | 7994.20 | 19-NOV-15:43 | 27.00 | 11.67 | 0.258898E+09 | 347.86 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.144293E+10 | 8218.34 | 25-DEC-16:42 | 24.33 | 11.32 | 0.237915E+09 | 347.84 | 12-DEC-14:30 | 24.33 | 11.32 |
Annual Sum or Average | 0.447046E+11 | 0.311658E+10 | ||||||||
Minimum of Months | 0.111451E+10 | 4288.70 | 20.50 | 10.79 | 0.219481E+09 | 347.84 | 20.00 | 10.79 | ||
Maximum of Months | 0.643920E+10 | 12476.18 | 39.17 | 21.23 | 0.288849E+09 | 347.87 | 33.33 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174767E+10 | 2774.60 | 31-JAN-16:30 | 29.00 | 10.73 | 0.385924E+09 | 549.49 | 23-JAN-14:20 | 29.00 | 10.73 |
February | 0.135356E+10 | 1984.77 | 22-FEB-16:20 | 20.67 | 11.54 | 0.344097E+09 | 549.48 | 15-FEB-14:00 | 20.67 | 11.54 |
March | 0.216486E+10 | 3875.18 | 20-MAR-14:30 | 27.70 | 14.31 | 0.429766E+09 | 549.50 | 20-MAR-09:20 | 27.70 | 14.31 |
April | 0.412925E+10 | 5600.50 | 25-APR-15:00 | 33.00 | 15.10 | 0.401302E+09 | 549.50 | 10-APR-09:20 | 33.00 | 15.10 |
May | 0.567058E+10 | 9330.78 | 21-MAY-17:41 | 31.17 | 13.16 | 0.437477E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.783099E+10 | 11384.83 | 25-JUN-18:11 | 37.33 | 14.77 | 0.437372E+09 | 550.52 | 19-JUN-13:20 | 37.33 | 14.77 |
July | 0.716769E+10 | 11595.73 | 04-JUL-18:21 | 36.00 | 14.91 | 0.406732E+09 | 549.52 | 25-JUL-09:20 | 33.33 | 21.12 |
August | 0.681996E+10 | 11317.42 | 27-AUG-15:51 | 40.00 | 18.27 | 0.455733E+09 | 549.51 | 18-AUG-09:20 | 40.00 | 18.27 |
September | 0.556939E+10 | 10904.83 | 17-SEP-13:43 | 34.50 | 17.78 | 0.404618E+09 | 549.51 | 05-SEP-09:20 | 34.50 | 17.78 |
October | 0.338177E+10 | 9349.11 | 02-OCT-04:02 | 26.00 | 17.05 | 0.411128E+09 | 549.51 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.198645E+10 | 3784.67 | 02-NOV-14:00 | 27.00 | 15.44 | 0.395573E+09 | 549.50 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.139641E+10 | 1979.96 | 22-DEC-16:40 | 24.33 | 9.71 | 0.351457E+09 | 549.47 | 22-DEC-14:00 | 24.33 | 9.71 |
Annual Sum or Average | 0.492186E+11 | 0.486118E+10 | ||||||||
Minimum of Months | 0.135356E+10 | 1979.96 | 20.67 | 9.71 | 0.344097E+09 | 549.47 | 20.00 | 9.71 | ||
Maximum of Months | 0.783099E+10 | 11595.73 | 40.00 | 18.27 | 0.455733E+09 | 550.52 | 40.00 | 21.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162965E+10 | 4251.70 | 27-JAN-11:05 | 22.33 | 7.96 | 0.190384E+09 | 356.46 | 26-JAN-13:09 | 22.33 | 7.96 |
February | 0.117137E+10 | 5562.73 | 24-FEB-13:01 | 14.17 | 9.26 | 0.171195E+09 | 356.45 | 13-FEB-15:09 | 14.17 | 9.26 |
March | 0.211193E+10 | 5836.81 | 23-MAR-10:05 | 21.97 | 10.49 | 0.207700E+09 | 356.46 | 16-MAR-10:09 | 21.97 | 10.49 |
April | 0.454478E+10 | 11411.42 | 02-APR-09:32 | 25.67 | 10.98 | 0.189780E+09 | 356.47 | 28-APR-10:09 | 25.17 | 10.76 |
May | 0.567633E+10 | 12392.90 | 21-MAY-09:02 | 27.33 | 11.56 | 0.206047E+09 | 356.47 | 22-MAY-10:09 | 25.33 | 9.96 |
June | 0.708821E+10 | 12464.00 | 11-JUN-08:52 | 28.00 | 12.26 | 0.205680E+09 | 356.58 | 19-JUN-10:09 | 34.17 | 14.95 |
July | 0.638265E+10 | 12699.18 | 04-JUL-09:41 | 31.67 | 15.19 | 0.191926E+09 | 356.46 | 03-JUL-14:09 | 31.67 | 15.19 |
August | 0.625898E+10 | 12765.71 | 27-AUG-09:11 | 33.67 | 16.18 | 0.214231E+09 | 356.46 | 14-AUG-10:09 | 33.67 | 16.18 |
September | 0.491030E+10 | 12258.23 | 04-SEP-09:42 | 26.33 | 22.09 | 0.190533E+09 | 356.46 | 22-SEP-10:09 | 25.37 | 17.42 |
October | 0.343067E+10 | 7957.07 | 02-OCT-12:02 | 34.00 | 19.16 | 0.195863E+09 | 356.46 | 03-OCT-14:09 | 33.17 | 20.16 |
November | 0.184142E+10 | 5171.12 | 01-NOV-10:05 | 23.33 | 16.05 | 0.191322E+09 | 356.47 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.106780E+10 | 4700.05 | 13-DEC-13:02 | 15.17 | 9.27 | 0.178525E+09 | 356.45 | 14-DEC-13:09 | 15.17 | 6.41 |
Annual Sum or Average | 0.461141E+11 | 0.233319E+10 | ||||||||
Minimum of Months | 0.106780E+10 | 4251.70 | 14.17 | 7.96 | 0.171195E+09 | 356.45 | 14.17 | 6.41 | ||
Maximum of Months | 0.708821E+10 | 12765.71 | 34.00 | 22.09 | 0.214231E+09 | 356.58 | 34.17 | 20.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639588E+10 | 13426.67 | 22-JAN-14:13 | 19.00 | 11.31 | 0.411546E+09 | 562.74 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.347499E+10 | 9210.20 | 28-FEB-14:05 | 18.17 | 7.92 | 0.366633E+09 | 549.79 | 23-FEB-14:50 | 18.17 | 7.92 |
March | 0.418934E+10 | 8272.00 | 23-MAR-13:50 | 25.42 | 11.73 | 0.441010E+09 | 550.13 | 23-MAR-13:20 | 25.42 | 11.73 |
April | 0.613131E+10 | 13179.85 | 30-APR-13:23 | 34.00 | 12.40 | 0.402273E+09 | 550.63 | 25-APR-13:20 | 34.00 | 12.40 |
May | 0.623127E+10 | 10805.38 | 21-MAY-16:21 | 32.00 | 13.36 | 0.437481E+09 | 549.50 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.754919E+10 | 12429.65 | 04-JUN-16:41 | 38.00 | 16.06 | 0.437170E+09 | 550.06 | 26-JUN-13:20 | 39.33 | 17.81 |
July | 0.733371E+10 | 12863.06 | 16-JUL-13:32 | 37.67 | 20.48 | 0.406720E+09 | 550.38 | 31-JUL-13:20 | 37.00 | 19.00 |
August | 0.806150E+10 | 12975.36 | 27-AUG-15:11 | 40.00 | 18.27 | 0.455963E+09 | 550.84 | 28-AUG-13:20 | 37.67 | 20.48 |
September | 0.786875E+10 | 13609.90 | 24-SEP-12:22 | 31.90 | 18.33 | 0.405411E+09 | 582.56 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.739375E+10 | 13467.01 | 09-OCT-13:12 | 31.33 | 17.32 | 0.418325E+09 | 586.16 | 02-OCT-13:20 | 31.33 | 17.32 |
November | 0.598977E+10 | 13759.90 | 19-NOV-13:32 | 26.00 | 11.06 | 0.410903E+09 | 568.41 | 01-NOV-13:00 | 26.00 | 11.06 |
December | 0.498948E+10 | 14016.25 | 25-DEC-14:32 | 26.00 | 11.71 | 0.390935E+09 | 550.67 | 27-DEC-14:09 | 19.17 | 9.79 |
Annual Sum or Average | 0.756089E+11 | 0.498437E+10 | ||||||||
Minimum of Months | 0.347499E+10 | 8272.00 | 18.17 | 7.92 | 0.366633E+09 | 549.50 | 18.17 | 7.92 | ||
Maximum of Months | 0.806150E+10 | 14016.25 | 40.00 | 20.48 | 0.455963E+09 | 586.16 | 39.33 | 20.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201668E+10 | 5881.24 | 24-JAN-16:30 | 24.50 | 10.78 | 0.248938E+09 | 347.85 | 23-JAN-14:20 | 24.50 | 10.78 |
February | 0.132998E+10 | 5795.13 | 22-FEB-16:30 | 20.50 | 11.47 | 0.221424E+09 | 347.84 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.220458E+10 | 8037.43 | 18-MAR-17:06 | 26.92 | 12.85 | 0.273918E+09 | 347.85 | 20-MAR-09:20 | 21.43 | 12.56 |
April | 0.453752E+10 | 12593.23 | 23-APR-16:22 | 33.15 | 12.72 | 0.254622E+09 | 347.86 | 10-APR-09:20 | 33.15 | 12.72 |
May | 0.554275E+10 | 12990.12 | 21-MAY-17:01 | 31.83 | 13.32 | 0.277200E+09 | 347.86 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.694865E+10 | 13165.27 | 25-JUN-17:31 | 38.00 | 15.08 | 0.277025E+09 | 347.86 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.581698E+10 | 13588.78 | 04-JUL-18:21 | 36.00 | 14.91 | 0.257645E+09 | 347.86 | 25-JUL-09:20 | 33.33 | 21.12 |
August | 0.581603E+10 | 13284.68 | 27-AUG-16:31 | 40.00 | 18.00 | 0.288706E+09 | 347.86 | 18-AUG-09:20 | 40.00 | 18.00 |
September | 0.472692E+10 | 12748.02 | 04-SEP-15:41 | 31.60 | 21.45 | 0.256352E+09 | 347.86 | 05-SEP-09:20 | 26.07 | 20.24 |
October | 0.337266E+10 | 11818.12 | 15-OCT-16:32 | 30.33 | 12.24 | 0.261219E+09 | 347.86 | 03-OCT-13:39 | 30.33 | 12.24 |
November | 0.219111E+10 | 9188.64 | 19-NOV-15:32 | 27.00 | 11.63 | 0.253115E+09 | 347.86 | 16-NOV-14:20 | 27.00 | 11.63 |
December | 0.140283E+10 | 10011.41 | 25-DEC-16:33 | 24.67 | 11.46 | 0.230371E+09 | 347.84 | 20-DEC-14:20 | 24.67 | 11.46 |
Annual Sum or Average | 0.459067E+11 | 0.310054E+10 | ||||||||
Minimum of Months | 0.132998E+10 | 5795.13 | 20.50 | 10.78 | 0.221424E+09 | 347.84 | 20.50 | 10.78 | ||
Maximum of Months | 0.694865E+10 | 13588.78 | 40.00 | 21.45 | 0.288706E+09 | 347.86 | 40.00 | 21.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.879437E+09 | 9720.55 | 02-JAN-07:02 | 6.00 |
February | 0.760110E+09 | 4791.39 | 13-FEB-07:02 | 8.33 |
March | 0.772523E+09 | 7228.28 | 27-MAR-06:01 | 1.97 |
April | 0.340235E+09 | 3438.41 | 30-APR-07:53 | 23.00 |
May | 0.180940E+09 | 4304.71 | 22-MAY-05:12 | 15.33 |
June | 48600343.13 | 3434.88 | 12-JUN-05:12 | 20.33 |
July | 32824712.18 | 4831.96 | 31-JUL-04:02 | 26.00 |
August | 32742976.00 | 4835.62 | 21-AUG-04:02 | 25.00 |
September | 57607803.19 | 4153.77 | 18-SEP-04:02 | 25.42 |
October | 0.469196E+09 | 3789.72 | 02-OCT-04:02 | 26.00 |
November | 0.663761E+09 | 6258.25 | 24-NOV-07:01 | 4.50 |
December | 0.121892E+10 | 9494.14 | 06-DEC-07:02 | -0.5 |
Annual Sum or Average | 0.545690E+10 | |||
Minimum of Months | 32742976.00 | 3434.88 | -0.5 | |
Maximum of Months | 0.121892E+10 | 9720.55 | 26.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355503E+09 | 4165.81 | 22-JAN-16:12 | 20.00 |
February | 0.394103E+09 | 2622.02 | 20-FEB-16:17 | 17.67 |
March | 0.232275E+09 | 2193.11 | 26-MAR-14:07 | 17.20 |
April | 26807171.16 | 3236.58 | 02-APR-14:53 | 31.00 |
May | 22112897.57 | 2617.13 | 21-MAY-17:01 | 31.83 |
June | 19502520.73 | 2687.14 | 11-JUN-16:51 | 34.00 |
July | 24539037.70 | 2762.99 | 02-JUL-15:51 | 38.00 |
August | 18432982.06 | 2591.85 | 27-AUG-15:11 | 40.00 |
September | 16711079.19 | 2554.66 | 24-SEP-14:22 | 33.55 |
October | 56040285.12 | 3384.60 | 15-OCT-15:52 | 31.00 |
November | 0.185613E+09 | 4803.35 | 19-NOV-15:32 | 27.00 |
December | 0.702418E+09 | 5235.11 | 25-DEC-15:52 | 26.00 |
Annual Sum or Average | 0.205406E+10 | |||
Minimum of Months | 16711079.19 | 2193.11 | 17.20 | |
Maximum of Months | 0.702418E+09 | 5235.11 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139206E+09 | 2652.96 | 22-JAN-16:33 | 20.00 |
February | 0.125349E+09 | 1768.39 | 14-FEB-08:09 | 9.33 |
March | 49745622.99 | 1600.00 | 27-MAR-07:17 | 5.67 |
April | 15587331.73 | 2117.17 | 23-APR-15:51 | 33.30 |
May | 11988541.21 | 1580.73 | 07-MAY-16:01 | 36.00 |
June | 13800227.78 | 2067.79 | 30-JUN-04:02 | 27.83 |
July | 24068468.97 | 2716.77 | 12-JUL-04:02 | 27.83 |
August | 20651073.76 | 2687.41 | 16-AUG-04:02 | 28.17 |
September | 23139368.04 | 3047.21 | 07-SEP-04:02 | 26.10 |
October | 29737216.47 | 2870.26 | 15-OCT-14:22 | 31.00 |
November | 47010437.71 | 3218.00 | 19-NOV-15:43 | 27.00 |
December | 0.261058E+09 | 3411.06 | 24-DEC-16:23 | 22.50 |
Annual Sum or Average | 0.761342E+09 | |||
Minimum of Months | 11988541.21 | 1580.73 | 5.67 | |
Maximum of Months | 0.261058E+09 | 3411.06 | 36.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2117989.71 | 13464.20 | 02-JAN-07:02 | 6.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 2117989.71 | |||
Minimum of Months | 0.00 | 0.00 | 6.00 | |
Maximum of Months | 2117989.71 | 13464.20 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56052000.63 | 25844.80 | 02-JAN-06:11 | 4.67 |
February | 7843649.99 | 23249.78 | 13-FEB-07:02 | 8.33 |
March | 1525175.97 | 22877.64 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 1594792.28 | 18605.91 | 24-NOV-07:01 | 4.50 |
December | 51728317.60 | 24558.99 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.118744E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 56052000.63 | 25844.80 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126887E+09 | 11132.59 | 02-JAN-06:11 | 4.67 |
February | 99277388.51 | 9934.89 | 13-FEB-06:12 | 8.00 |
March | 72514841.12 | 10066.71 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 6623256.58 | 9175.45 | 26-OCT-06:02 | 8.17 |
November | 61248915.05 | 10083.04 | 24-NOV-06:12 | 3.33 |
December | 0.409464E+09 | 10714.78 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.776015E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.409464E+09 | 11132.59 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51073902.26 | 8058.59 | 02-JAN-06:11 | 4.67 |
February | 38404108.46 | 6892.71 | 13-FEB-06:12 | 8.00 |
March | 29943594.09 | 7027.46 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 3536560.94 | 6053.19 | 26-OCT-06:02 | 8.17 |
November | 18090091.67 | 7110.38 | 24-NOV-06:12 | 3.33 |
December | 0.164098E+09 | 7720.88 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.305147E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.164098E+09 | 8058.59 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57440279.93 | 11820.52 | 02-JAN-06:11 | 4.67 |
February | 52128954.72 | 10930.40 | 13-FEB-06:12 | 8.00 |
March | 51346768.14 | 10809.63 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 2686907.99 | 6991.06 | 26-OCT-06:02 | 8.17 |
November | 20695822.98 | 10736.45 | 24-NOV-06:12 | 3.33 |
December | 0.199221E+09 | 11493.00 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.383520E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.199221E+09 | 11820.52 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69577771.53 | 7839.74 | 02-JAN-06:11 | 4.67 |
February | 58606709.14 | 6700.48 | 13-FEB-06:12 | 8.00 |
March | 39649050.26 | 6674.29 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 3460827.65 | 5598.44 | 26-OCT-06:02 | 8.17 |
November | 33054733.94 | 6778.34 | 24-NOV-06:12 | 3.33 |
December | 0.241662E+09 | 7571.19 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.446011E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.241662E+09 | 7839.74 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23549625.62 | 7220.60 | 02-JAN-06:11 | 4.67 |
February | 9254990.77 | 6539.55 | 14-FEB-07:02 | 7.33 |
March | 10746146.65 | 6689.70 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 16375236.39 | 6698.91 | 07-DEC-07:01 | 1.33 |
Annual Sum or Average | 59925999.43 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 23549625.62 | 7220.60 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4948223.44 | 4199.65 | 02-JAN-06:11 | 4.67 |
February | 1481930.66 | 4133.32 | 13-FEB-07:02 | 8.33 |
March | 886143.73 | 3959.47 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 1908152.46 | 4272.80 | 18-DEC-07:01 | 3.33 |
Annual Sum or Average | 9224450.30 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 4948223.44 | 4272.80 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496326E+09 | 7643.14 | 02-JAN-07:10 | 6.00 |
February | 0.543271E+09 | 7643.97 | 08-FEB-07:10 | 6.17 |
March | 0.617737E+09 | 8293.86 | 27-MAR-06:10 | 1.97 |
April | 98112314.02 | 6796.72 | 21-APR-06:10 | 9.33 |
May | 3999056.83 | 5175.17 | 01-MAY-06:06 | 13.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.201862E+09 | 7305.63 | 25-OCT-06:10 | 5.00 |
November | 0.274989E+09 | 7378.75 | 24-NOV-07:10 | 4.50 |
December | 0.609025E+09 | 8339.99 | 07-DEC-07:10 | 1.33 |
Annual Sum or Average | 0.284532E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.617737E+09 | 8339.99 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4784387.04 | 4467.16 | 02-JAN-06:11 | 4.67 |
February | 2731979.42 | 4041.22 | 13-FEB-07:02 | 8.33 |
March | 580442.34 | 4170.91 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 3565833.22 | 4126.48 | 08-DEC-07:01 | 2.17 |
Annual Sum or Average | 11662642.02 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 4784387.04 | 4467.16 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26646122.26 | 8759.05 | 02-JAN-06:11 | 4.67 |
February | 8257183.39 | 7935.44 | 13-FEB-07:02 | 8.33 |
March | 6616724.87 | 7989.30 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 2810735.38 | 7921.18 | 24-NOV-07:01 | 4.50 |
December | 61290560.43 | 8334.15 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.105621E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 61290560.43 | 8759.05 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11228882.30 | 5484.13 | 02-JAN-06:11 | 4.67 |
February | 3755418.02 | 4997.75 | 13-FEB-07:02 | 8.33 |
March | 2990317.22 | 5086.34 | 28-MAR-06:01 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 592673.34 | 4686.47 | 24-NOV-07:01 | 4.50 |
December | 24037252.12 | 5456.63 | 06-DEC-06:01 | 0.67 |
Annual Sum or Average | 42604543.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.67 | |
Maximum of Months | 24037252.12 | 5484.13 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10728172.13 | 8395.61 | 02-JAN-06:11 | 4.67 |
February | 3373256.91 | 7733.79 | 13-FEB-07:02 | 8.33 |
March | 3108095.57 | 7853.26 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 387205.98 | 4517.40 | 24-NOV-07:01 | 4.50 |
December | 21343572.20 | 7957.85 | 07-DEC-07:01 | 1.33 |
Annual Sum or Average | 38940302.80 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 21343572.20 | 8395.61 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13680247.13 | 5259.83 | 02-JAN-06:11 | 4.67 |
February | 4656782.36 | 4960.31 | 13-FEB-07:02 | 8.33 |
March | 2622716.84 | 4562.95 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 1012690.02 | 4840.55 | 24-NOV-07:01 | 4.50 |
December | 37163241.30 | 5181.14 | 16-DEC-07:03 | 1.17 |
Annual Sum or Average | 59135677.65 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 37163241.30 | 5259.83 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351743E+10 | 3696.64 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.319060E+10 | 3696.64 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.379103E+10 | 3696.64 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.338654E+10 | 3696.64 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.365423E+10 | 3696.64 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.363649E+10 | 3696.64 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.340429E+10 | 3696.64 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.379103E+10 | 3696.64 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.338654E+10 | 3696.64 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.351743E+10 | 3696.64 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.347603E+10 | 3696.64 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.340429E+10 | 3696.64 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.421559E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.319060E+10 | 3696.64 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.379103E+10 | 3696.64 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351743E+10 | 3696.64 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.319060E+10 | 3696.64 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.379103E+10 | 3696.64 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.338654E+10 | 3696.64 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.365423E+10 | 3696.64 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.363649E+10 | 3696.64 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.340429E+10 | 3696.64 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.379103E+10 | 3696.64 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.338654E+10 | 3696.64 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.351743E+10 | 3696.64 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.347603E+10 | 3696.64 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.340429E+10 | 3696.64 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.421559E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.319060E+10 | 3696.64 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.379103E+10 | 3696.64 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351743E+10 | 3696.64 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.319060E+10 | 3696.64 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.379103E+10 | 3696.64 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.338654E+10 | 3696.64 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.365423E+10 | 3696.64 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.363649E+10 | 3696.64 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.340429E+10 | 3696.64 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.379103E+10 | 3696.64 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.338654E+10 | 3696.64 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.351743E+10 | 3696.64 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.347603E+10 | 3696.64 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.340429E+10 | 3696.64 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.421559E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.319060E+10 | 3696.64 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.379103E+10 | 3696.64 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466895E+09 | 701.41 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.412196E+09 | 660.75 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.456694E+09 | 616.33 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.393956E+09 | 421.29 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.414950E+09 | 405.17 | 26-MAY-08:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.404055E+09 | 371.72 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.384424E+09 | 415.30 | 13-JUL-15:00 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.439643E+09 | 621.88 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.402670E+09 | 548.71 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.443907E+09 | 677.27 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.454577E+09 | 779.28 | 28-NOV-16:30 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.461315E+09 | 779.28 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.513528E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.384424E+09 | 371.72 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.466895E+09 | 779.28 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.284003E+09 | 439.37 | 20-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.254217E+09 | 400.32 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.286023E+09 | 317.51 | 09-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.247862E+09 | 235.33 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.263987E+09 | 249.64 | 25-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.257693E+09 | 235.33 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.245354E+09 | 266.49 | 13-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.277637E+09 | 382.48 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.253472E+09 | 265.33 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.272316E+09 | 333.03 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280136E+09 | 493.35 | 28-NOV-16:30 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281959E+09 | 493.35 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.320466E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.245354E+09 | 235.33 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.286023E+09 | 493.35 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.438884E+09 | 684.49 | 20-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.396341E+09 | 643.94 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.449496E+09 | 592.12 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.395413E+09 | 424.76 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.419933E+09 | 405.18 | 26-MAY-08:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.410338E+09 | 400.28 | 27-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.390510E+09 | 418.45 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.442175E+09 | 625.06 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.400816E+09 | 428.92 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.423208E+09 | 571.25 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.433794E+09 | 779.28 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.434613E+09 | 779.28 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.503552E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.390510E+09 | 400.28 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.449496E+09 | 779.28 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.289334E+09 | 449.30 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.257322E+09 | 418.76 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.287898E+09 | 421.49 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.249890E+09 | 339.64 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265125E+09 | 265.34 | 26-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.258491E+09 | 255.11 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.246118E+09 | 309.67 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.279596E+09 | 400.06 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.255254E+09 | 378.40 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.276397E+09 | 434.17 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281784E+09 | 493.32 | 28-NOV-16:30 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.284740E+09 | 493.32 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.323195E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.246118E+09 | 255.11 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.289334E+09 | 493.32 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.464553E+09 | 698.06 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.410770E+09 | 656.48 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.455273E+09 | 609.62 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.393380E+09 | 419.02 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.414817E+09 | 401.60 | 26-MAY-08:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.403949E+09 | 371.72 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.384079E+09 | 412.21 | 13-JUL-15:00 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.438799E+09 | 615.85 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.401988E+09 | 539.49 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.442180E+09 | 671.77 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.452662E+09 | 779.28 | 28-NOV-16:30 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.459161E+09 | 779.28 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.512161E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.384079E+09 | 371.72 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.464553E+09 | 779.28 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283186E+09 | 437.71 | 20-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.253628E+09 | 397.25 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.285586E+09 | 312.64 | 09-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.247679E+09 | 235.33 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.263790E+09 | 235.33 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.257370E+09 | 235.33 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.245014E+09 | 264.88 | 13-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.277249E+09 | 378.86 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.253156E+09 | 263.98 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.271876E+09 | 329.47 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279389E+09 | 493.35 | 28-NOV-16:30 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.280992E+09 | 493.35 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.319892E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.245014E+09 | 235.33 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.285586E+09 | 493.35 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.438651E+09 | 680.78 | 20-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.395816E+09 | 638.65 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.448902E+09 | 584.44 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.394955E+09 | 422.71 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.419411E+09 | 401.60 | 26-MAY-08:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.409702E+09 | 398.06 | 27-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.389635E+09 | 416.79 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.441346E+09 | 619.18 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.400361E+09 | 426.52 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.422919E+09 | 562.69 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.433461E+09 | 779.28 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.434300E+09 | 779.28 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.502946E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.389635E+09 | 398.06 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.448902E+09 | 779.28 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.288181E+09 | 447.75 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.256743E+09 | 416.55 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.287324E+09 | 419.31 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.249493E+09 | 333.89 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.264779E+09 | 263.77 | 26-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.258189E+09 | 253.95 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.245709E+09 | 304.36 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.279068E+09 | 397.21 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.254782E+09 | 374.90 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.275743E+09 | 431.90 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281225E+09 | 493.32 | 28-NOV-16:30 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.284025E+09 | 493.32 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.322526E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.245709E+09 | 253.95 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.288181E+09 | 493.32 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466894E+09 | 701.40 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.412195E+09 | 660.75 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.456693E+09 | 616.32 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.393956E+09 | 421.29 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.414950E+09 | 405.16 | 26-MAY-08:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.404055E+09 | 371.72 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.384424E+09 | 415.29 | 13-JUL-15:00 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.439643E+09 | 621.87 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.402670E+09 | 548.69 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.443906E+09 | 677.27 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.454576E+09 | 779.28 | 28-NOV-16:30 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.461316E+09 | 779.28 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.513528E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.384424E+09 | 371.72 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.466894E+09 | 779.28 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.284026E+09 | 439.36 | 20-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.254216E+09 | 400.31 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.286023E+09 | 317.51 | 09-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.247862E+09 | 235.33 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.263987E+09 | 249.63 | 25-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.257693E+09 | 235.33 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.245354E+09 | 266.49 | 13-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.277636E+09 | 382.47 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.253472E+09 | 265.33 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.272316E+09 | 333.03 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280136E+09 | 493.35 | 28-NOV-16:30 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281959E+09 | 493.35 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.320468E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.245354E+09 | 235.33 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.286023E+09 | 493.35 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.438884E+09 | 684.48 | 20-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.396340E+09 | 643.93 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.449495E+09 | 592.11 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.395412E+09 | 424.76 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.419933E+09 | 405.17 | 26-MAY-08:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.410338E+09 | 400.28 | 27-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.390510E+09 | 418.45 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.442174E+09 | 625.05 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.400815E+09 | 428.91 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.423208E+09 | 571.24 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.433794E+09 | 779.28 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.434613E+09 | 779.28 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.503552E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.390510E+09 | 400.28 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.449495E+09 | 779.28 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.289334E+09 | 449.30 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.257322E+09 | 418.77 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.287898E+09 | 421.49 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.249890E+09 | 339.64 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265125E+09 | 265.34 | 26-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.258491E+09 | 255.10 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.246118E+09 | 309.68 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.279595E+09 | 400.05 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.255254E+09 | 378.40 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.276389E+09 | 434.16 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281783E+09 | 493.32 | 28-NOV-16:30 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.284740E+09 | 493.32 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.323194E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.246118E+09 | 255.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.289334E+09 | 493.32 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.351743E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.319060E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.379103E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.338654E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.365423E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.363649E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.340429E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.379103E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.338654E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.351743E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.347603E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.340429E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.421559E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.319060E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.379103E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.351743E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.338654E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.365423E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.363649E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.340429E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.338654E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.351743E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.347603E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.340429E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.421559E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.351743E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.338654E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.365423E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.363649E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.340429E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.338654E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.351743E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.347603E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.340429E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.421559E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.466895E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3014956.83 | 0.345442E+09 |
February | 0.901968E+09 | 0.412196E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278203E+09 |
March | 0.107774E+10 | 0.456694E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3664090.19 | 0.371301E+09 |
April | 0.956342E+09 | 0.393956E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65672673.24 | 0.128350E+09 |
May | 0.103597E+10 | 0.414950E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124604E+09 | 82177480.01 |
June | 0.103308E+10 | 0.404055E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227308E+09 | 25307902.99 |
July | 0.959235E+09 | 0.384424E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222788E+09 | 21698513.75 |
August | 0.107774E+10 | 0.439643E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156206E+09 | 29218200.91 |
September | 0.956342E+09 | 0.402670E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116010E+09 | 55745344.89 |
October | 0.994195E+09 | 0.443907E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44266797.41 | 0.190712E+09 |
November | 0.984487E+09 | 0.454577E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5694387.15 | 0.317546E+09 |
December | 0.959235E+09 | 0.461315E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1459755.41 | 0.331522E+09 |
Annual Sum or Average | 0.119305E+11 | 0.513528E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970689E+09 | 0.217722E+10 |
Minimum of Months | 0.901968E+09 | 0.384424E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21698513.75 |
Maximum of Months | 0.107774E+10 | 0.466895E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227308E+09 | 0.371301E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.284003E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 901013.82 | 0.243102E+09 |
February | 0.571020E+09 | 0.254217E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194143E+09 |
March | 0.682301E+09 | 0.286023E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2280007.33 | 0.258576E+09 |
April | 0.605444E+09 | 0.247862E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41370879.18 | 91671253.26 |
May | 0.655854E+09 | 0.263987E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80728295.86 | 57367293.97 |
June | 0.654023E+09 | 0.257693E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150710E+09 | 17480060.40 |
July | 0.607275E+09 | 0.245354E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146996E+09 | 15237339.93 |
August | 0.682301E+09 | 0.277637E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101935E+09 | 20894516.13 |
September | 0.605444E+09 | 0.253472E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75569345.49 | 38709620.30 |
October | 0.629407E+09 | 0.272316E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26839843.33 | 0.134127E+09 |
November | 0.623262E+09 | 0.280136E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2383057.19 | 0.221742E+09 |
December | 0.607275E+09 | 0.281959E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 403915.02 | 0.230310E+09 |
Annual Sum or Average | 0.755301E+10 | 0.320466E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630117E+09 | 0.152336E+10 |
Minimum of Months | 0.571020E+09 | 0.245354E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15237339.93 |
Maximum of Months | 0.682301E+09 | 0.286023E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150710E+09 | 0.258576E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.438884E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1194126.16 | 0.398674E+09 |
February | 0.901968E+09 | 0.396341E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303029E+09 |
March | 0.107774E+10 | 0.449496E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3266013.07 | 0.394762E+09 |
April | 0.956342E+09 | 0.395413E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61526798.41 | 0.133326E+09 |
May | 0.103597E+10 | 0.419933E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123834E+09 | 81998262.08 |
June | 0.103308E+10 | 0.410338E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229174E+09 | 24662053.84 |
July | 0.959235E+09 | 0.390510E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223237E+09 | 21391011.32 |
August | 0.107774E+10 | 0.442175E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154429E+09 | 30182003.55 |
September | 0.956342E+09 | 0.400816E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112390E+09 | 59161728.45 |
October | 0.994195E+09 | 0.423208E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38728685.98 | 0.210754E+09 |
November | 0.984487E+09 | 0.433794E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2156880.58 | 0.356444E+09 |
December | 0.959235E+09 | 0.434613E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106342.14 | 0.373353E+09 |
Annual Sum or Average | 0.119305E+11 | 0.503552E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950043E+09 | 0.238774E+10 |
Minimum of Months | 0.901968E+09 | 0.390510E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21391011.32 |
Maximum of Months | 0.107774E+10 | 0.449496E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229174E+09 | 0.398674E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.289334E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1169560.15 | 0.244509E+09 |
February | 0.570983E+09 | 0.257322E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192927E+09 |
March | 0.682256E+09 | 0.287898E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2177632.93 | 0.258866E+09 |
April | 0.605404E+09 | 0.249890E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40014704.46 | 92420707.09 |
May | 0.655811E+09 | 0.265125E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79738598.61 | 58471817.87 |
June | 0.653980E+09 | 0.258491E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148420E+09 | 18206471.08 |
July | 0.607235E+09 | 0.246118E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144704E+09 | 15682705.40 |
August | 0.682256E+09 | 0.279596E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100899E+09 | 20935829.39 |
September | 0.605404E+09 | 0.255254E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74599213.12 | 39388830.72 |
October | 0.629366E+09 | 0.276397E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27161209.84 | 0.134935E+09 |
November | 0.623221E+09 | 0.281784E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2523590.46 | 0.223316E+09 |
December | 0.607235E+09 | 0.284740E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 290622.86 | 0.230526E+09 |
Annual Sum or Average | 0.755252E+10 | 0.323195E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621697E+09 | 0.153018E+10 |
Minimum of Months | 0.570983E+09 | 0.246118E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15682705.40 |
Maximum of Months | 0.682256E+09 | 0.289334E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148420E+09 | 0.258866E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.464553E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1691029.30 | 0.199907E+09 |
February | 0.901968E+09 | 0.410770E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156086E+09 |
March | 0.107774E+10 | 0.455273E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2176634.52 | 0.199960E+09 |
April | 0.956342E+09 | 0.393380E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40200444.24 | 66893354.89 |
May | 0.103597E+10 | 0.414817E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73104773.43 | 41544529.38 |
June | 0.103308E+10 | 0.403949E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125885E+09 | 12284142.78 |
July | 0.959235E+09 | 0.384079E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122897E+09 | 11239860.17 |
August | 0.107774E+10 | 0.438799E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85641846.07 | 16776190.59 |
September | 0.956342E+09 | 0.401988E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63322240.89 | 32656225.59 |
October | 0.994195E+09 | 0.442180E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24140231.68 | 0.114517E+09 |
November | 0.984487E+09 | 0.452662E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2742787.51 | 0.194654E+09 |
December | 0.959235E+09 | 0.459161E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 581865.55 | 0.200706E+09 |
Annual Sum or Average | 0.119305E+11 | 0.512161E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542383E+09 | 0.124722E+10 |
Minimum of Months | 0.901968E+09 | 0.384079E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11239860.17 |
Maximum of Months | 0.107774E+10 | 0.464553E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125885E+09 | 0.200706E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.283186E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 473355.40 | 0.144536E+09 |
February | 0.571020E+09 | 0.253628E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111413E+09 |
March | 0.682301E+09 | 0.285586E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1265468.34 | 0.144017E+09 |
April | 0.605444E+09 | 0.247679E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23256579.95 | 50367491.43 |
May | 0.655854E+09 | 0.263790E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44550543.43 | 31030398.64 |
June | 0.654023E+09 | 0.257370E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81690823.95 | 9296830.88 |
July | 0.607275E+09 | 0.245014E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79418304.48 | 8683844.26 |
August | 0.682301E+09 | 0.277249E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54592823.73 | 12971129.72 |
September | 0.605444E+09 | 0.253156E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40465232.02 | 24085340.55 |
October | 0.629407E+09 | 0.271876E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14445668.88 | 81871933.99 |
November | 0.623262E+09 | 0.279389E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1158722.79 | 0.137598E+09 |
December | 0.607275E+09 | 0.280992E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 151168.79 | 0.142202E+09 |
Annual Sum or Average | 0.755301E+10 | 0.319892E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341469E+09 | 0.898072E+09 |
Minimum of Months | 0.571020E+09 | 0.245014E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8683844.26 |
Maximum of Months | 0.682301E+09 | 0.285586E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81690823.95 | 0.144536E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.438651E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44638455.96 | 0.237968E+10 |
February | 0.901968E+09 | 0.395816E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287293E+10 |
March | 0.107774E+10 | 0.448902E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150058E+09 | 0.239518E+10 |
April | 0.956342E+09 | 0.394955E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116080E+10 | 0.730392E+09 |
May | 0.103597E+10 | 0.419411E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203142E+10 | 0.327470E+09 |
June | 0.103308E+10 | 0.409702E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324313E+10 | 66988748.31 |
July | 0.959235E+09 | 0.389635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262591E+10 | 27823430.54 |
August | 0.107774E+10 | 0.441346E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279060E+10 | 92169666.67 |
September | 0.956342E+09 | 0.400361E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187552E+10 | 0.223642E+09 |
October | 0.994195E+09 | 0.422919E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813621E+09 | 0.138709E+10 |
November | 0.984487E+09 | 0.433461E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92128128.39 | 0.221263E+10 |
December | 0.959235E+09 | 0.434300E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4607034.68 | 0.331849E+10 |
Annual Sum or Average | 0.119305E+11 | 0.502946E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148324E+11 | 0.160345E+11 |
Minimum of Months | 0.901968E+09 | 0.389635E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27823430.54 |
Maximum of Months | 0.107774E+10 | 0.448902E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324313E+10 | 0.331849E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.288181E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 523239.94 | 0.145906E+09 |
February | 0.570983E+09 | 0.256743E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110376E+09 |
March | 0.682256E+09 | 0.287324E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1186857.03 | 0.143652E+09 |
April | 0.605404E+09 | 0.249493E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22058850.40 | 51473098.86 |
May | 0.655811E+09 | 0.264779E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43738623.36 | 32127566.20 |
June | 0.653980E+09 | 0.258189E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80308741.57 | 9893809.83 |
July | 0.607235E+09 | 0.245709E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78094810.26 | 8905127.44 |
August | 0.682256E+09 | 0.279068E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54047137.24 | 12861457.70 |
September | 0.605404E+09 | 0.254782E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39916008.62 | 24426779.79 |
October | 0.629366E+09 | 0.275743E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14437656.63 | 82722700.71 |
November | 0.623221E+09 | 0.281225E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1098841.51 | 0.138979E+09 |
December | 0.607235E+09 | 0.284025E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85034.85 | 0.141758E+09 |
Annual Sum or Average | 0.755252E+10 | 0.322526E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335496E+09 | 0.903082E+09 |
Minimum of Months | 0.570983E+09 | 0.245709E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8905127.44 |
Maximum of Months | 0.682256E+09 | 0.288181E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80308741.57 | 0.145906E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.466894E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2155837.04 | 0.315262E+09 |
February | 0.901968E+09 | 0.412195E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251028E+09 |
March | 0.107774E+10 | 0.456693E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3107941.14 | 0.329713E+09 |
April | 0.956342E+09 | 0.393956E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57428772.21 | 0.111963E+09 |
May | 0.103597E+10 | 0.414950E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106495E+09 | 71565489.86 |
June | 0.103308E+10 | 0.404055E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191146E+09 | 21738890.48 |
July | 0.959235E+09 | 0.384424E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188148E+09 | 18436407.01 |
August | 0.107774E+10 | 0.439643E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131982E+09 | 25552460.44 |
September | 0.956342E+09 | 0.402670E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98227446.67 | 48532435.78 |
October | 0.994195E+09 | 0.443906E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37346558.64 | 0.171378E+09 |
November | 0.984487E+09 | 0.454576E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4379728.41 | 0.290066E+09 |
December | 0.959235E+09 | 0.461316E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 955418.29 | 0.302928E+09 |
Annual Sum or Average | 0.119305E+11 | 0.513528E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821373E+09 | 0.195816E+10 |
Minimum of Months | 0.901968E+09 | 0.384424E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18436407.01 |
Maximum of Months | 0.107774E+10 | 0.466894E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191146E+09 | 0.329713E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.284026E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 647909.24 | 0.220507E+09 |
February | 0.421807E+09 | 0.254216E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174359E+09 |
March | 0.502994E+09 | 0.286023E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1787235.03 | 0.228650E+09 |
April | 0.447140E+09 | 0.247862E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35010697.66 | 79425203.22 |
May | 0.484071E+09 | 0.263987E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67812388.88 | 49812762.25 |
June | 0.482240E+09 | 0.257693E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125967E+09 | 14985417.36 |
July | 0.448971E+09 | 0.245354E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123341E+09 | 12958642.01 |
August | 0.502994E+09 | 0.277636E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85332763.43 | 18276701.91 |
September | 0.447140E+09 | 0.253472E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63157482.69 | 33744380.01 |
October | 0.465148E+09 | 0.272316E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22288663.04 | 0.119667E+09 |
November | 0.460569E+09 | 0.280136E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1810913.61 | 0.201448E+09 |
December | 0.448971E+09 | 0.281959E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251303.62 | 0.210056E+09 |
Annual Sum or Average | 0.557719E+10 | 0.320468E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527407E+09 | 0.136389E+10 |
Minimum of Months | 0.421807E+09 | 0.245354E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12958642.01 |
Maximum of Months | 0.502994E+09 | 0.286023E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125967E+09 | 0.228650E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.438884E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 990206.20 | 0.357139E+09 |
February | 0.901968E+09 | 0.396340E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270365E+09 |
March | 0.107774E+10 | 0.449495E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2783668.15 | 0.347885E+09 |
April | 0.956342E+09 | 0.395412E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52634875.64 | 0.116121E+09 |
May | 0.103597E+10 | 0.419933E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105262E+09 | 71576404.49 |
June | 0.103308E+10 | 0.410338E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192998E+09 | 21179124.29 |
July | 0.959235E+09 | 0.390510E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188545E+09 | 18165640.45 |
August | 0.107774E+10 | 0.442174E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130170E+09 | 26362236.25 |
September | 0.956342E+09 | 0.400815E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94635716.08 | 51455712.84 |
October | 0.994195E+09 | 0.423208E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32457551.14 | 0.187060E+09 |
November | 0.984487E+09 | 0.433794E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1780406.38 | 0.319931E+09 |
December | 0.959235E+09 | 0.434613E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90709.43 | 0.335878E+09 |
Annual Sum or Average | 0.119305E+11 | 0.503552E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802349E+09 | 0.212312E+10 |
Minimum of Months | 0.901968E+09 | 0.390510E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18165640.45 |
Maximum of Months | 0.107774E+10 | 0.449495E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192998E+09 | 0.357139E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.289334E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 838858.88 | 0.221450E+09 |
February | 0.570983E+09 | 0.257322E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173172E+09 |
March | 0.682256E+09 | 0.287898E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1840564.04 | 0.228895E+09 |
April | 0.605404E+09 | 0.249890E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33801816.58 | 80579507.68 |
May | 0.655811E+09 | 0.265125E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67134954.77 | 50948770.52 |
June | 0.653980E+09 | 0.258491E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124485E+09 | 15624789.81 |
July | 0.607235E+09 | 0.246118E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121555E+09 | 13317436.34 |
August | 0.682256E+09 | 0.279595E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84841288.91 | 18269736.28 |
September | 0.605404E+09 | 0.255254E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62775214.19 | 34252118.33 |
October | 0.629366E+09 | 0.276389E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22728550.00 | 0.120521E+09 |
November | 0.623221E+09 | 0.281783E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1892491.37 | 0.202345E+09 |
December | 0.607235E+09 | 0.284740E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 156842.62 | 0.209437E+09 |
Annual Sum or Average | 0.755252E+10 | 0.323194E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522050E+09 | 0.136881E+10 |
Minimum of Months | 0.570983E+09 | 0.246118E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13317436.34 |
Maximum of Months | 0.682256E+09 | 0.289334E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124485E+09 | 0.228895E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896840.59 | 0.466039E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361721E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3002253.86 | 0.467895E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66070010.85 | 0.156168E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128731E+09 | 95933892.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237848E+09 | 26865732.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236344E+09 | 22672946.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162179E+09 | 33562964.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117507E+09 | 63792550.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40241822.32 | 0.248788E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2833783.55 | 0.427578E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297974.45 | 0.449372E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995953E+09 | 0.282039E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22672946.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237848E+09 | 0.467895E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1585710.81 | 0.570761E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445429E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4109477.13 | 0.587920E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84766637.54 | 0.201250E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162960E+09 | 0.125638E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302676E+09 | 36276150.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300611E+09 | 30505229.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207638E+09 | 42911608.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151986E+09 | 81483566.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53778887.96 | 0.308233E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5246763.24 | 0.521926E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753620.96 | 0.545143E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127611E+10 | 0.349748E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30505229.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302676E+09 | 0.587920E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686301.81 | 0.538579E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438371E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2104969.68 | 0.576687E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68364894.37 | 0.190169E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147815E+09 | 0.108121E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312479E+09 | 29980593.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298027E+09 | 25864213.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213244E+09 | 36416307.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150995E+09 | 73308611.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49308501.87 | 0.292210E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1903887.43 | 0.491198E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90289.18 | 0.510005E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124502E+10 | 0.331091E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25864213.66 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312479E+09 | 0.576687E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3696.64 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3696.64 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3696.64 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3696.64 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3696.64 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3696.64 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3696.64 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3696.64 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3696.64 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3696.64 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3696.64 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3696.64 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3696.64 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3696.64 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3696.64 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3696.64 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3696.64 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3696.64 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3696.64 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3696.64 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3696.64 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3696.64 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3696.64 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3696.64 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3696.64 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3696.64 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3696.64 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3696.64 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3696.64 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3696.64 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3696.64 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3696.64 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3696.64 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3696.64 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3696.64 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3696.64 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3696.64 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3696.64 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 701.41 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.99 | 16-JAN-11:53 | 614.78 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 660.75 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 821.84 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 616.33 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.82 | 18-MAR-17:02 | 705.36 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 421.29 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 493.09 | 30-APR-15:54 | 368.58 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 405.17 | 26-MAY-08:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.59 | 20-MAY-17:02 | 308.65 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 371.72 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.16 | 17-JUN-17:10 | 157.24 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 415.30 | 13-JUL-15:00 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 922.81 | 22-JUL-17:43 | 249.28 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 621.88 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.21 | 13-AUG-16:00 | 384.00 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 548.71 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.81 | 17-SEP-12:00 | 260.32 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 677.27 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.16 | 01-OCT-14:55 | 738.20 | 22-OCT-13:55 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 28-NOV-16:30 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.47 | 19-NOV-13:20 | 684.80 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.61 | 25-DEC-14:00 | 586.20 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.24 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 922.81 | 821.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 439.37 | 20-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 | 29-JAN-16:00 | 419.37 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 400.32 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 559.96 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 317.51 | 09-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 | 18-MAR-17:02 | 472.71 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 235.33 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.10 | 30-APR-15:54 | 368.70 | 16-APR-08:50 |
May | 827.22 | 01-MAY-09:09 | 249.64 | 25-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.74 | 20-MAY-17:47 | 205.20 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 235.33 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.69 | 17-JUN-17:10 | 114.36 | 11-JUN-06:20 |
July | 827.22 | 03-JUL-09:09 | 266.49 | 13-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 617.25 | 22-JUL-17:43 | 166.61 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 382.48 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.47 | 13-AUG-16:00 | 261.27 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 265.33 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.07 | 17-SEP-12:00 | 173.35 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 333.03 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.67 | 01-OCT-14:55 | 541.56 | 22-OCT-13:55 |
November | 827.22 | 01-NOV-09:09 | 493.35 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.72 | 19-NOV-15:00 | 460.61 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 493.35 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.40 | 25-DEC-16:00 | 391.92 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.36 | |||||
Maximum of Months | 827.22 | 493.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 617.25 | 559.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 684.49 | 20-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 | 31-JAN-14:10 | 698.47 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 643.94 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 890.29 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 592.12 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 15-MAR-13:00 | 723.05 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 424.76 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.92 | 30-APR-15:13 | 372.36 | 26-APR-21:10 |
May | 1306.65 | 01-MAY-09:09 | 405.18 | 26-MAY-08:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.08 | 20-MAY-17:47 | 308.68 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 400.28 | 27-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.20 | 17-JUN-17:10 | 156.38 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 418.45 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.69 | 22-JUL-17:43 | 247.95 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 625.06 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.20 | 13-AUG-16:00 | 395.30 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 428.92 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.57 | 17-SEP-12:00 | 264.15 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 571.25 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.04 | 01-OCT-14:55 | 877.42 | 22-OCT-13:55 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.16 | 01-NOV-16:00 | 718.45 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 21-DEC-15:00 | 609.16 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 400.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.38 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 925.69 | 890.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 449.30 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.88 | 16-JAN-11:53 | 433.62 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 418.76 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 574.42 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 421.49 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 | 15-MAR-13:00 | 480.06 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 339.64 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.51 | 30-APR-15:59 | 260.88 | 26-APR-21:10 |
May | 827.17 | 01-MAY-09:09 | 265.34 | 26-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.70 | 20-MAY-18:30 | 210.02 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 255.11 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.79 | 17-JUN-17:10 | 109.27 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 309.67 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 611.99 | 22-JUL-18:00 | 177.78 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 400.06 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.46 | 13-AUG-16:00 | 264.90 | 05-AUG-17:40 |
September | 827.17 | 01-SEP-09:09 | 378.40 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.81 | 17-SEP-12:00 | 173.16 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 434.17 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.70 | 01-OCT-14:55 | 506.84 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 493.32 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.16 | 19-NOV-12:40 | 460.62 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 493.32 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 25-DEC-13:42 | 394.38 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 255.11 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.27 | |||||
Maximum of Months | 827.17 | 493.32 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 611.99 | 574.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 698.06 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.26 | 16-JAN-12:00 | 383.03 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 656.48 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 468.64 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 609.62 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 18-MAR-17:02 | 397.93 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 419.02 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.11 | 30-APR-15:00 | 211.60 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 401.60 | 26-MAY-08:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.76 | 20-MAY-18:10 | 169.39 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 371.72 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.66 | 17-JUN-17:03 | 83.83 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 412.21 | 13-JUL-15:00 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 504.23 | 22-JUL-18:00 | 135.82 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 615.85 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.94 | 13-AUG-16:00 | 206.52 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 539.49 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.88 | 17-SEP-12:00 | 155.35 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 671.77 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.98 | 01-OCT-14:38 | 416.80 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 28-NOV-16:30 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.26 | 19-NOV-14:42 | 419.62 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.12 | 25-DEC-15:52 | 352.03 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 504.23 | 468.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 437.71 | 20-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 29-JAN-16:00 | 272.17 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 397.25 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 331.21 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 312.64 | 09-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.92 | 18-MAR-17:02 | 277.66 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 235.33 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.34 | 30-APR-15:54 | 182.64 | 16-APR-08:30 |
May | 827.22 | 01-MAY-09:09 | 235.33 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.39 | 20-MAY-18:00 | 117.03 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 235.33 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.46 | 17-JUN-17:10 | 61.40 | 11-JUN-06:20 |
July | 827.22 | 03-JUL-09:09 | 264.88 | 13-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.39 | 22-JUL-18:00 | 95.59 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 378.86 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.63 | 13-AUG-16:00 | 142.89 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 263.98 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.50 | 17-SEP-12:15 | 106.98 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 329.47 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.74 | 01-OCT-14:38 | 306.22 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 493.35 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 19-NOV-15:10 | 290.41 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 493.35 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 25-DEC-15:42 | 240.91 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.40 | |||||
Maximum of Months | 827.22 | 493.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 336.39 | 331.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 680.78 | 20-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4682.00 | 31-JAN-17:10 | 18305.63 | 12-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 638.65 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18763.64 | 01-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 584.44 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5353.36 | 20-MAR-17:00 | 21291.32 | 27-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 422.71 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11356.57 | 14-APR-16:02 | 13679.05 | 21-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 401.60 | 26-MAY-08:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13430.18 | 31-MAY-16:02 | 10348.09 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 398.06 | 27-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18521.78 | 28-JUN-16:01 | 4485.02 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 416.79 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15604.89 | 20-JUL-16:01 | 2032.88 | 27-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 619.18 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17312.20 | 25-AUG-16:01 | 4948.76 | 24-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 426.52 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13728.66 | 08-SEP-16:01 | 7094.35 | 22-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 562.69 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10797.75 | 03-OCT-16:02 | 18958.08 | 25-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3343.46 | 01-NOV-16:05 | 19475.25 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.02 | 21-DEC-15:00 | 24536.86 | 05-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 398.06 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2032.88 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18521.78 | 24536.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 447.75 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 16-JAN-12:00 | 280.24 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 416.55 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 336.42 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 419.31 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 15-MAR-13:00 | 281.07 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 333.89 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.13 | 30-APR-15:13 | 147.01 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 263.77 | 26-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.04 | 20-MAY-17:07 | 120.77 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 253.95 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.08 | 17-JUN-17:03 | 62.47 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 304.36 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.89 | 22-JUL-18:00 | 100.97 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 397.21 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.62 | 13-AUG-16:00 | 142.78 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 374.90 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.52 | 17-SEP-12:15 | 105.85 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 431.90 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.99 | 01-OCT-14:35 | 290.51 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 493.32 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 | 19-NOV-12:43 | 290.78 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 493.32 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 25-DEC-13:52 | 240.85 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 253.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.47 | |||||
Maximum of Months | 827.17 | 493.32 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 326.89 | 336.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 701.40 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.35 | 16-JAN-12:10 | 583.77 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 660.75 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 743.41 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 616.32 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.99 | 18-MAR-17:02 | 635.10 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 421.29 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.65 | 30-APR-15:40 | 331.13 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 405.16 | 26-MAY-08:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.30 | 20-MAY-17:02 | 273.01 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 371.72 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 608.15 | 17-JUN-17:10 | 137.26 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 415.29 | 13-JUL-15:00 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 773.88 | 22-JUL-18:00 | 208.70 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 621.87 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.69 | 13-AUG-16:00 | 314.75 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 548.69 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.02 | 17-SEP-12:00 | 224.15 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 677.27 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.98 | 01-OCT-14:46 | 626.28 | 22-OCT-13:55 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 28-NOV-16:30 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.66 | 19-NOV-13:20 | 625.55 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | 25-DEC-16:00 | 531.61 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.26 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 773.88 | 743.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 439.36 | 20-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 31-JAN-14:00 | 396.55 | 01-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 400.31 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 504.25 | 02-FEB-23:00 |
March | 805.43 | 01-MAR-08:09 | 317.51 | 09-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 | 18-MAR-17:02 | 425.12 | 28-MAR-04:00 |
April | 805.43 | 03-APR-07:10 | 235.33 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.43 | 30-APR-15:26 | 318.77 | 16-APR-09:00 |
May | 805.43 | 01-MAY-07:10 | 249.63 | 25-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.57 | 20-MAY-17:02 | 181.63 | 23-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 235.33 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.33 | 17-JUN-17:10 | 99.24 | 11-JUN-06:10 |
July | 805.43 | 03-JUL-07:10 | 266.49 | 13-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 520.19 | 22-JUL-18:00 | 140.00 | 26-JUL-24:00 |
August | 805.43 | 01-AUG-07:10 | 382.47 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.78 | 13-AUG-16:00 | 215.14 | 05-AUG-17:50 |
September | 805.43 | 01-SEP-07:10 | 265.33 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.90 | 17-SEP-12:00 | 149.70 | 03-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 333.03 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.21 | 01-OCT-14:44 | 457.21 | 22-OCT-13:55 |
November | 805.43 | 01-NOV-07:10 | 493.35 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.03 | 19-NOV-15:00 | 419.73 | 29-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 493.35 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.11 | 25-DEC-16:00 | 355.86 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.24 | |||||
Maximum of Months | 805.43 | 493.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 520.19 | 504.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 684.48 | 20-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 31-JAN-14:05 | 651.25 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 643.93 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 795.26 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 592.11 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.63 | 15-MAR-13:00 | 649.14 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 424.76 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.97 | 30-APR-15:24 | 333.43 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 405.17 | 26-MAY-08:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.74 | 20-MAY-17:02 | 273.02 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 400.28 | 27-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 608.79 | 17-JUN-17:10 | 136.52 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 418.45 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.66 | 22-JUL-18:00 | 207.62 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 625.05 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.66 | 13-AUG-16:00 | 323.93 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 428.91 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.57 | 17-SEP-12:00 | 227.32 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 571.24 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.73 | 01-OCT-14:44 | 737.93 | 22-OCT-13:55 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 01-NOV-16:00 | 651.00 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 21-DEC-15:00 | 550.93 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 400.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.52 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 784.66 | 795.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 449.30 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 | 16-JAN-12:10 | 407.75 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 418.77 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 515.71 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 421.49 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 | 15-MAR-13:00 | 431.21 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 339.64 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.41 | 30-APR-15:24 | 223.28 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 265.34 | 26-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.97 | 20-MAY-17:45 | 185.58 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 255.10 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.36 | 17-JUN-17:10 | 95.25 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 309.68 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.61 | 22-JUL-18:00 | 148.61 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 400.05 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.77 | 13-AUG-16:00 | 216.76 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 378.40 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.88 | 17-SEP-12:00 | 149.11 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 434.16 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.59 | 01-OCT-14:44 | 430.04 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 493.32 | 28-NOV-16:30 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 19-NOV-12:40 | 419.92 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 493.32 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 25-DEC-13:42 | 357.25 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 255.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | |||||
Maximum of Months | 827.17 | 493.32 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 510.61 | 515.71 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 | 31-JAN-14:00 | 894.79 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1092.08 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.36 | 18-MAR-17:02 | 914.01 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.50 | 30-APR-15:00 | 469.02 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.43 | 20-MAY-17:02 | 377.09 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.36 | 17-JUN-17:03 | 181.79 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.64 | 22-JUL-18:00 | 273.23 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.68 | 13-AUG-16:00 | 422.49 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.96 | 17-SEP-12:00 | 307.76 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.35 | 01-OCT-14:23 | 849.38 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.78 | 19-NOV-14:52 | 916.83 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 25-DEC-14:00 | 775.62 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1000.64 | 1092.08 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 31-JAN-14:00 | 1057.49 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1362.45 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.15 | 18-MAR-17:02 | 1143.40 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.79 | 30-APR-15:10 | 596.23 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.47 | 20-MAY-17:02 | 486.00 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.67 | 17-JUN-17:03 | 237.42 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.71 | 22-JUL-18:00 | 353.07 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.76 | 13-AUG-16:00 | 540.11 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.83 | 17-SEP-12:00 | 392.73 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.28 | 01-OCT-14:32 | 1045.20 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.34 | 19-NOV-14:50 | 1129.90 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.43 | 25-DEC-15:52 | 958.62 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.71 | 1362.45 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 | 31-JAN-17:00 | 932.21 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1246.96 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 | 15-MAR-13:00 | 1048.25 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.40 | 30-APR-15:40 | 560.41 | 26-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.87 | 20-MAY-17:02 | 435.85 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.76 | 17-JUN-17:03 | 210.29 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.09 | 22-JUL-18:00 | 368.36 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.33 | 13-AUG-16:00 | 639.86 | 05-AUG-17:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.45 | 17-SEP-12:00 | 390.94 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.23 | 01-OCT-14:30 | 1335.50 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.45 | 19-NOV-15:20 | 1017.39 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 25-DEC-14:00 | 869.30 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.09 | 1335.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16331.86 | 27-JAN-17:00 | 6035.01 | 3696.64 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17491.96 | 01-FEB-07:01 | 8893.70 | 8625.49 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22875.63 | 20-MAR-06:03 | 3811.58 | 3696.64 | 18132.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32175.41 | 17-APR-06:02 | 6352.64 | 6161.06 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34212.85 | 30-MAY-05:12 | 2541.06 | 1642.95 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34155.59 | 20-JUN-05:12 | 2541.06 | 1642.95 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33508.00 | 06-JUL-05:12 | 2541.06 | 1642.95 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33333.20 | 29-AUG-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33419.12 | 12-SEP-05:12 | 2541.06 | 1642.95 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34076.78 | 10-OCT-05:12 | 2541.06 | 1642.95 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32605.56 | 13-NOV-07:02 | 7623.17 | 7393.27 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15963.22 | 28-DEC-17:00 | 6035.01 | 3696.64 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15963.22 | 2541.06 | 846.94 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34212.85 | 8893.70 | 8625.49 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5650.51 | 31-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 0.00 |
February | 4138.97 | 23-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.36 |
March | 6773.59 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.64 | 0.00 |
April | 10780.36 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 0.00 |
May | 10696.82 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.43 | 0.00 |
June | 13016.96 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.10 | 0.00 |
July | 12218.18 | 20-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.31 | 0.00 |
August | 12211.10 | 25-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.87 | 0.00 |
September | 11315.23 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.75 | 0.00 |
October | 10359.41 | 02-OCT-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.84 | 0.00 |
November | 6793.69 | 01-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 0.00 |
December | 4339.76 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4138.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13016.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.10 | 69.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1859.03 | 27-JAN-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 0.00 |
February | 886.41 | 01-FEB-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 |
March | 2275.43 | 17-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.35 | 0.00 |
April | 4488.36 | 24-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 | 0.00 |
May | 4999.32 | 08-MAY-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 0.00 |
June | 6615.63 | 19-JUN-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.16 | 0.00 |
July | 6019.18 | 17-JUL-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.39 | 0.00 |
August | 6191.59 | 28-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.65 | 0.00 |
September | 6150.39 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 |
October | 5366.18 | 02-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.63 | 0.00 |
November | 2722.28 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.27 | 0.00 |
December | 2606.52 | 14-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 886.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6615.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.16 | 205.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2370.08 | 27-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 0.00 |
February | 2198.54 | 01-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.43 |
March | 2551.05 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.71 |
April | 4540.78 | 24-APR-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.45 | 0.00 |
May | 5136.74 | 08-MAY-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.80 | 0.00 |
June | 7362.44 | 19-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.95 | 0.00 |
July | 7054.54 | 05-JUL-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 | 0.00 |
August | 6251.41 | 08-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.66 | 0.00 |
September | 6316.82 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 |
October | 5264.39 | 02-OCT-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.47 | 0.00 |
November | 3135.78 | 02-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | 0.00 |
December | 2475.95 | 07-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2198.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7362.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.95 | 178.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12227.89 | 27-JAN-17:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11110.71 | 01-FEB-17:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13017.12 | 20-MAR-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27057.16 | 17-APR-06:02 | 6352.64 | 6161.06 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29808.61 | 30-MAY-05:12 | 2541.06 | 1642.95 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32308.13 | 19-JUN-05:14 | 3176.32 | 2053.69 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32196.30 | 05-JUL-05:14 | 3176.32 | 2053.69 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28892.02 | 22-AUG-05:12 | 2541.06 | 1642.95 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31841.71 | 25-SEP-05:14 | 3176.32 | 2053.69 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29381.20 | 10-OCT-05:12 | 2541.06 | 1642.95 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13677.24 | 01-NOV-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11206.99 | 27-DEC-17:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11110.71 | 2541.06 | 1642.95 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32308.13 | 6352.64 | 6161.06 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12315.34 | 27-JAN-17:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10582.50 | 22-FEB-17:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14282.69 | 17-MAR-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24468.89 | 24-APR-06:02 | 6352.64 | 6161.06 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32688.73 | 30-MAY-05:12 | 2541.06 | 1642.95 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32650.78 | 12-JUN-05:12 | 2541.06 | 1642.95 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33102.43 | 24-JUL-04:02 | 0.00 | 2053.69 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33455.67 | 21-AUG-04:02 | 0.00 | 2053.69 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33176.08 | 08-SEP-04:02 | 0.00 | 2053.69 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32962.88 | 02-OCT-04:02 | 0.00 | 2053.69 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14717.88 | 01-NOV-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10691.43 | 22-DEC-17:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10582.50 | 0.00 | 1642.95 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33455.67 | 6352.64 | 6161.06 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2846.68 | 31-JAN-16:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 0.00 |
February | 2075.53 | 22-FEB-16:20 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 |
March | 4096.37 | 16-MAR-16:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 0.00 |
April | 13167.59 | 30-APR-16:31 | 535.68 | 165.19 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 358.64 | 0.00 |
May | 11830.47 | 07-MAY-17:32 | 0.00 | 123.89 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 352.50 | 0.00 |
June | 13596.53 | 25-JUN-18:11 | 0.00 | 144.54 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 555.47 | 0.00 |
July | 13758.58 | 16-JUL-15:21 | 468.72 | 144.54 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 227.97 | 0.00 |
August | 13605.78 | 13-AUG-16:11 | 468.72 | 144.54 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 747.97 | 0.00 |
September | 13157.81 | 17-SEP-13:43 | 267.84 | 82.59 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 396.64 | 0.00 |
October | 11423.35 | 02-OCT-04:02 | 0.00 | 432.94 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
November | 4050.79 | 01-NOV-15:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 | 0.00 |
December | 1979.07 | 22-DEC-16:40 | 1272.23 | 527.22 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1979.07 | 0.00 | 82.59 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13758.58 | 1272.23 | 527.22 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 747.97 | 36.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2995.41 | 27-JAN-10:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 |
February | 3242.71 | 23-FEB-10:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
March | 4538.93 | 23-MAR-10:20 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 |
April | 12953.20 | 30-APR-09:52 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
May | 12532.70 | 28-MAY-10:32 | 211.95 | 65.36 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 49.34 | 0.00 |
June | 12752.44 | 18-JUN-09:02 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 105.67 | 0.00 |
July | 13457.75 | 23-JUL-09:21 | 296.74 | 91.50 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 | 0.00 |
August | 12707.85 | 13-AUG-09:32 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 46.49 | 0.00 |
September | 11910.54 | 10-SEP-10:22 | 211.95 | 65.36 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 97.77 | 0.00 |
October | 8107.18 | 09-OCT-15:02 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 70.35 | 0.00 |
November | 3857.11 | 01-NOV-10:05 | 1610.86 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
December | 1857.84 | 01-DEC-10:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1857.84 | 211.95 | 65.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13457.75 | 1610.86 | 470.66 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.67 | 30.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15693.43 | 15-JAN-13:42 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.18 |
February | 9404.40 | 28-FEB-14:05 | 2613.31 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 |
March | 8663.50 | 16-MAR-13:40 | 1306.65 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 0.00 |
April | 15094.65 | 30-APR-16:31 | 535.68 | 165.19 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 324.13 | 0.00 |
May | 14702.39 | 07-MAY-13:32 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 220.36 | 0.00 |
June | 14681.33 | 04-JUN-16:41 | 468.72 | 144.54 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 404.19 | 0.00 |
July | 15330.97 | 16-JUL-15:21 | 468.72 | 144.54 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 225.34 | 0.00 |
August | 15231.54 | 13-AUG-16:11 | 468.72 | 144.54 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 736.01 | 0.00 |
September | 15451.33 | 10-SEP-13:42 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 353.99 | 0.00 |
October | 16699.83 | 09-OCT-13:02 | 401.76 | 123.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 49.69 | 0.00 |
November | 15666.31 | 19-NOV-14:12 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.35 |
December | 15982.89 | 25-DEC-14:32 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8663.50 | 267.84 | 82.59 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16699.83 | 2613.31 | 743.44 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 736.01 | 75.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6034.49 | 24-JAN-16:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
February | 5960.34 | 22-FEB-16:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.29 |
March | 9166.89 | 18-MAR-17:06 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 0.00 |
April | 15471.45 | 30-APR-16:31 | 339.11 | 104.57 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 139.96 | 0.00 |
May | 14624.92 | 28-MAY-17:11 | 0.00 | 104.57 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 155.59 | 0.00 |
June | 14974.55 | 25-JUN-17:31 | 0.00 | 91.50 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 307.28 | 0.00 |
July | 15085.80 | 16-JUL-17:21 | 0.00 | 117.64 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 357.32 | 0.00 |
August | 15019.81 | 13-AUG-16:51 | 296.72 | 91.50 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 387.24 | 0.00 |
September | 14133.53 | 04-SEP-15:52 | 254.33 | 78.43 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 55.99 | 0.00 |
October | 14570.34 | 09-OCT-16:22 | 254.33 | 78.43 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 | 0.00 |
November | 9411.27 | 19-NOV-15:32 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 |
December | 10053.77 | 25-DEC-16:33 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5960.34 | 0.00 | 52.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15471.45 | 805.38 | 235.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 387.24 | 41.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2100.31 | 27-JAN-16:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
February | 1246.84 | 22-FEB-16:40 | 1272.23 | 403.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.27 |
March | 2728.74 | 20-MAR-14:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 |
April | 4694.65 | 25-APR-15:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 0.00 |
May | 5308.21 | 08-MAY-15:20 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 0.00 |
June | 10746.37 | 25-JUN-18:11 | 0.00 | 144.54 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 313.31 | 0.00 |
July | 10878.41 | 02-JUL-18:21 | 0.00 | 144.54 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 244.34 | 0.00 |
August | 10901.08 | 27-AUG-17:41 | 0.00 | 165.19 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 242.69 | 0.00 |
September | 9832.90 | 17-SEP-13:32 | 267.84 | 82.59 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 228.88 | 0.00 |
October | 9469.29 | 01-OCT-13:53 | 267.84 | 82.59 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 178.29 | 0.00 |
November | 3781.05 | 02-NOV-14:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
December | 1762.33 | 01-DEC-15:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1246.84 | 0.00 | 82.59 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10901.08 | 1306.65 | 403.56 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 313.31 | 20.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2871.72 | 27-JAN-10:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 |
February | 2577.41 | 23-FEB-10:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
March | 3565.13 | 23-MAR-10:30 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
April | 10827.17 | 30-APR-09:52 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
May | 10539.25 | 28-MAY-10:32 | 211.95 | 65.36 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 | 0.00 |
June | 10610.81 | 18-JUN-09:12 | 211.95 | 65.36 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 | 0.00 |
July | 10880.71 | 23-JUL-09:51 | 339.13 | 104.58 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 49.93 | 0.00 |
August | 11037.28 | 27-AUG-11:02 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 102.26 | 0.00 |
September | 10900.59 | 04-SEP-10:12 | 211.95 | 65.36 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
October | 8092.57 | 01-OCT-11:13 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 | 0.00 |
November | 3981.31 | 02-NOV-08:40 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
December | 2520.41 | 01-DEC-10:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2520.41 | 169.56 | 52.29 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11037.28 | 827.22 | 235.33 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 102.26 | 16.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12550.08 | 16-JAN-15:53 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.03 |
February | 7721.54 | 28-FEB-13:07 | 3816.70 | 1115.15 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1154.67 |
March | 9945.09 | 16-MAR-16:10 | 401.76 | 206.51 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5270.13 | 0.00 |
April | 11997.89 | 30-APR-16:31 | 535.68 | 165.19 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 199.59 | 0.00 |
May | 12047.52 | 15-MAY-17:00 | 401.76 | 206.51 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11250.87 | 0.00 |
June | 13797.89 | 28-JUN-17:00 | 401.76 | 206.51 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.00 | 0.00 |
July | 12999.38 | 20-JUL-17:00 | 401.76 | 206.51 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12423.08 | 0.00 |
August | 13638.80 | 25-AUG-17:00 | 401.76 | 206.51 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13574.69 | 0.00 |
September | 12938.10 | 08-SEP-16:10 | 2812.30 | 1445.57 | 5581.48 | 0.00 | 0.00 | 0.00 | 0.00 | 11430.62 | 0.00 |
October | 13583.00 | 09-OCT-13:02 | 401.76 | 123.89 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 27.51 | 0.00 |
November | 12722.24 | 05-NOV-13:23 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.21 |
December | 12675.28 | 25-DEC-12:02 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7721.54 | 267.84 | 82.59 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13797.89 | 3816.70 | 1445.57 | 5581.48 | 0.00 | 0.00 | 0.00 | 0.00 | 14410.00 | 1154.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5001.33 | 24-JAN-16:40 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
February | 4288.70 | 22-FEB-16:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 |
March | 5253.65 | 18-MAR-17:06 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 0.00 |
April | 11933.47 | 30-APR-16:31 | 339.11 | 104.57 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 100.18 | 0.00 |
May | 11628.86 | 29-MAY-17:11 | 0.00 | 117.64 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 | 0.00 |
June | 11731.92 | 25-JUN-17:31 | 0.00 | 91.50 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 175.84 | 0.00 |
July | 12123.71 | 02-JUL-18:21 | 0.00 | 91.50 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 139.16 | 0.00 |
August | 12476.18 | 27-AUG-17:41 | 0.00 | 104.57 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 137.01 | 0.00 |
September | 11917.82 | 04-SEP-17:32 | 0.00 | 78.43 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 42.04 | 0.00 |
October | 11802.57 | 15-OCT-16:22 | 254.33 | 78.43 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 26.79 | 0.00 |
November | 7994.20 | 19-NOV-15:43 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 | 0.00 |
December | 8218.34 | 25-DEC-16:42 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4288.70 | 0.00 | 52.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12476.18 | 805.38 | 235.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 175.84 | 25.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2774.60 | 31-JAN-16:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 0.00 |
February | 1984.77 | 22-FEB-16:20 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 |
March | 3875.18 | 20-MAR-14:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 |
April | 5600.50 | 25-APR-15:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 93.39 | 0.00 |
May | 9330.78 | 21-MAY-17:41 | 0.00 | 185.83 | 3474.93 | 0.00 | 0.00 | 0.00 | 0.00 | 212.55 | 0.00 |
June | 11384.83 | 25-JUN-18:11 | 0.00 | 144.54 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 473.24 | 0.00 |
July | 11595.73 | 04-JUL-18:21 | 0.00 | 165.19 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 317.03 | 0.00 |
August | 11317.42 | 27-AUG-15:51 | 669.60 | 206.48 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 0.00 |
September | 10904.83 | 17-SEP-13:43 | 267.84 | 82.59 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 334.00 | 0.00 |
October | 9349.11 | 02-OCT-04:02 | 0.00 | 432.94 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
November | 3784.67 | 02-NOV-14:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 0.00 |
December | 1979.96 | 22-DEC-16:40 | 1272.23 | 527.22 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1979.96 | 0.00 | 82.59 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11595.73 | 1306.65 | 527.22 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 480.64 | 29.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4251.70 | 27-JAN-11:05 | 1610.86 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 |
February | 5562.73 | 24-FEB-13:01 | 5638.00 | 1647.30 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.46 |
March | 5836.81 | 23-MAR-10:05 | 1610.86 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 |
April | 11411.42 | 02-APR-09:32 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 |
May | 12392.90 | 21-MAY-09:02 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 |
June | 12464.00 | 11-JUN-08:52 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
July | 12699.18 | 04-JUL-09:41 | 296.74 | 91.50 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.72 | 0.00 |
August | 12765.71 | 27-AUG-09:11 | 296.74 | 91.50 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.87 | 0.00 |
September | 12258.23 | 04-SEP-09:42 | 254.35 | 78.43 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 |
October | 7957.07 | 02-OCT-12:02 | 4027.14 | 1176.64 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 0.00 |
November | 5171.12 | 01-NOV-10:05 | 1610.86 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
December | 4700.05 | 13-DEC-13:02 | 4832.57 | 1411.97 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4251.70 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12765.71 | 5638.00 | 1647.30 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 77.87 | 36.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13426.67 | 22-JAN-14:13 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.60 |
February | 9210.20 | 28-FEB-14:05 | 2613.31 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 |
March | 8272.00 | 23-MAR-13:50 | 1306.65 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 0.00 |
April | 13179.85 | 30-APR-13:23 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 263.66 | 0.00 |
May | 10805.38 | 21-MAY-16:21 | 602.64 | 185.83 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 291.23 | 0.00 |
June | 12429.65 | 04-JUN-16:41 | 468.72 | 144.54 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 344.49 | 0.00 |
July | 12863.06 | 16-JUL-13:32 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 334.27 | 0.00 |
August | 12975.36 | 27-AUG-15:11 | 602.64 | 185.83 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 409.46 | 0.00 |
September | 13609.90 | 24-SEP-12:22 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 116.14 | 0.00 |
October | 13467.01 | 09-OCT-13:12 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 | 0.00 |
November | 13759.90 | 19-NOV-13:32 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.32 |
December | 14016.25 | 25-DEC-14:32 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8272.00 | 267.84 | 82.59 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14016.25 | 2613.31 | 743.44 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 409.46 | 233.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5881.24 | 24-JAN-16:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
February | 5795.13 | 22-FEB-16:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 |
March | 8037.43 | 18-MAR-17:06 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 0.00 |
April | 12593.23 | 23-APR-16:22 | 254.33 | 78.43 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 0.00 |
May | 12990.12 | 21-MAY-17:01 | 0.00 | 117.64 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 146.13 | 0.00 |
June | 13165.27 | 25-JUN-17:31 | 0.00 | 91.50 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 262.84 | 0.00 |
July | 13588.78 | 04-JUL-18:21 | 0.00 | 104.57 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 176.30 | 0.00 |
August | 13284.68 | 27-AUG-16:31 | 423.88 | 130.71 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 215.13 | 0.00 |
September | 12748.02 | 04-SEP-15:41 | 339.11 | 104.57 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 54.68 | 0.00 |
October | 11818.12 | 15-OCT-16:32 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 57.75 | 0.00 |
November | 9188.64 | 19-NOV-15:32 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
December | 10011.41 | 25-DEC-16:33 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5795.13 | 0.00 | 52.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13588.78 | 805.38 | 235.31 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 262.84 | 34.41 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.910342E+11 | 114888.30 | 02-JAN-07:10 | 0.113729E+11 | 30153.07 | 02-JAN-07:30 |
February | 0.745129E+11 | 80648.22 | 13-FEB-07:10 | 0.106727E+11 | 27104.62 | 01-FEB-07:30 |
March | 0.935897E+11 | 99164.95 | 16-MAR-15:30 | 0.117867E+11 | 36508.75 | 27-MAR-06:10 |
April | 0.114119E+12 | 130416.59 | 14-APR-15:20 | 0.968106E+10 | 11484.58 | 21-APR-06:30 |
May | 0.134441E+12 | 136286.29 | 31-MAY-15:39 | 0.975814E+10 | 9488.67 | 01-MAY-11:30 |
June | 0.162735E+12 | 163527.48 | 28-JUN-14:00 | 0.921578E+10 | 9370.78 | 01-JUN-11:20 |
July | 0.153941E+12 | 154244.45 | 31-JUL-15:00 | 0.905110E+10 | 9296.11 | 05-JUL-11:09 |
August | 0.159731E+12 | 156958.58 | 25-AUG-15:20 | 0.943927E+10 | 9324.41 | 30-AUG-11:20 |
September | 0.137476E+12 | 146600.91 | 08-SEP-15:00 | 0.911968E+10 | 9420.52 | 28-SEP-11:20 |
October | 0.111013E+12 | 131917.97 | 02-OCT-15:09 | 0.100249E+11 | 23358.95 | 25-OCT-06:40 |
November | 0.901000E+11 | 100767.46 | 01-NOV-15:00 | 0.103982E+11 | 29549.40 | 24-NOV-07:19 |
December | 0.851320E+11 | 93553.59 | 18-DEC-07:10 | 0.139813E+11 | 42069.21 | 06-DEC-07:30 |
Annual Sum or Average | 0.140782E+13 | 0.124502E+12 | ||||
Minimum of Months | 0.745129E+11 | 80648.22 | 0.905110E+10 | 9296.11 | ||
Maximum of Months | 0.162735E+12 | 163527.48 | 0.139813E+11 | 42069.21 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.106531E+11 | 17803.78 | 30-JAN-12:30 | 0.00 | 0.00 |
February | 0.954416E+10 | 22416.92 | 27-FEB-12:39 | 0.00 | 0.00 |
March | 0.139732E+11 | 25841.17 | 28-MAR-12:30 | 0.00 | 0.00 |
April | 0.198679E+11 | 26073.52 | 19-APR-12:30 | 0.00 | 0.00 |
May | 0.219725E+11 | 26510.07 | 12-MAY-12:30 | 0.00 | 0.00 |
June | 0.219097E+11 | 25742.91 | 10-JUN-12:30 | 0.00 | 0.00 |
July | 0.186002E+11 | 24442.80 | 21-JUL-12:30 | 0.00 | 0.00 |
August | 0.170913E+11 | 23991.08 | 05-AUG-12:30 | 0.00 | 0.00 |
September | 0.138277E+11 | 22925.78 | 09-SEP-12:30 | 0.00 | 0.00 |
October | 0.132359E+11 | 21963.41 | 12-OCT-12:30 | 0.00 | 0.00 |
November | 0.101106E+11 | 18837.91 | 04-NOV-11:00 | 0.00 | 0.00 |
December | 0.936148E+10 | 16484.97 | 14-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.180148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.936148E+10 | 16484.97 | 0.00 | 0.00 | |
Maximum of Months | 0.219725E+11 | 26510.07 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.149851E+11 | 0.359114E+10 | 0.545046E+11 | 0.977371E+09 | 0.533119E+10 | 12379742.02 | 0.147897E+10 | 0.101534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135289E+11 | 0.297607E+10 | 0.493409E+11 | 0.884505E+09 | 0.385424E+10 | 11196021.66 | 0.136583E+10 | 0.255128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158104E+11 | 0.294263E+10 | 0.567112E+11 | 0.102336E+10 | 0.549237E+10 | 12675672.10 | 0.123143E+10 | 0.103657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140194E+11 | 0.251106E+10 | 0.526212E+11 | 0.941236E+09 | 0.113341E+11 | 11960507.72 | 0.134674E+09 | 0.325450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150535E+11 | 0.230166E+10 | 0.556079E+11 | 0.100015E+10 | 0.148177E+11 | 12527707.06 | 6760015.67 | 0.456404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148998E+11 | 0.212272E+10 | 0.546110E+11 | 0.984470E+09 | 0.202260E+11 | 12231776.97 | 0.00 | 0.698786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140101E+11 | 0.224671E+10 | 0.536070E+11 | 0.956727E+09 | 0.184079E+11 | 12256437.81 | 0.00 | 0.646999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156876E+11 | 0.247732E+10 | 0.567112E+11 | 0.102330E+10 | 0.184607E+11 | 12675672.10 | 0.00 | 0.653585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140943E+11 | 0.268061E+10 | 0.525990E+11 | 0.941043E+09 | 0.148148E+11 | 11960507.72 | 0.00 | 0.523337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147966E+11 | 0.313446E+10 | 0.545158E+11 | 0.977361E+09 | 0.963234E+10 | 12379742.02 | 0.316281E+09 | 0.276277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147754E+11 | 0.338994E+10 | 0.533244E+11 | 0.959157E+09 | 0.605284E+10 | 12059151.09 | 0.653482E+09 | 0.109327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145966E+11 | 0.370359E+10 | 0.535958E+11 | 0.957008E+09 | 0.450283E+10 | 12256437.81 | 0.296054E+10 | 0.480330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176258E+12 | 0.340779E+11 | 0.647750E+12 | 0.116257E+11 | 0.132927E+12 | 0.146559E+09 | 0.814796E+10 | 0.396890E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135289E+11 | 0.212272E+10 | 0.493409E+11 | 0.884505E+09 | 0.385424E+10 | 11196021.66 | 0.00 | 0.255128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158104E+11 | 0.370359E+10 | 0.567112E+11 | 0.102336E+10 | 0.202260E+11 | 12675672.10 | 0.296054E+10 | 0.698786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.741730E+09 | 0.00 | 0.106312E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108109E+10 | 0.00 | 0.959161E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.109437E+10 | 0.00 | 0.106923E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 8795788.40 | 0.00 | 0.967226E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.975814E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.921578E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.905110E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.943927E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.911968E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.241863E+09 | 0.00 | 0.978307E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.488909E+09 | 0.00 | 0.990927E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.362179E+10 | 0.00 | 0.103595E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.727855E+10 | 0.00 | 0.117223E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.905110E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.362179E+10 | 0.00 | 0.106923E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17819.32 | 20-JAN-16:00 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 829.77 | 20-JAN-08:39 | 10305.19 | 27-JAN-16:49 | 6.85 | 12-JAN-08:09 | 82862.81 | 02-JAN-07:10 |
February | 17428.52 | 10-FEB-08:09 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 829.46 | 10-FEB-08:20 | 7642.41 | 22-FEB-16:30 | 6.85 | 02-FEB-17:10 | 48958.89 | 13-FEB-07:10 |
March | 16732.45 | 21-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 828.55 | 21-MAR-07:19 | 12532.95 | 16-MAR-15:30 | 6.85 | 14-MAR-07:10 | 44153.65 | 27-MAR-06:10 |
April | 15342.91 | 04-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 826.71 | 04-APR-07:19 | 21723.96 | 24-APR-15:50 | 6.85 | 02-APR-16:30 | 8589.40 | 07-APR-06:19 |
May | 15006.18 | 26-MAY-08:30 | 3824.74 | 01-MAY-05:10 | 40437.79 | 01-MAY-07:10 | 826.21 | 26-MAY-07:19 | 24305.73 | 08-MAY-15:00 | 6.85 | 07-MAY-15:30 | 3658.61 | 01-MAY-06:19 |
June | 14873.83 | 27-JUN-07:10 | 3824.74 | 01-JUN-05:10 | 40437.79 | 01-JUN-07:10 | 826.10 | 27-JUN-07:19 | 27591.88 | 19-JUN-14:00 | 6.85 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 15134.17 | 13-JUL-15:00 | 3824.74 | 01-JUL-05:10 | 40437.79 | 03-JUL-07:10 | 826.38 | 27-JUL-07:19 | 25799.05 | 31-JUL-15:00 | 6.85 | 01-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 17159.92 | 04-AUG-07:10 | 3824.74 | 01-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 829.11 | 04-AUG-07:19 | 26338.89 | 14-AUG-15:20 | 6.85 | 01-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 15846.48 | 29-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 827.38 | 29-SEP-07:19 | 23796.20 | 05-SEP-15:00 | 6.85 | 04-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 16778.17 | 27-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 828.61 | 27-OCT-07:19 | 20278.61 | 02-OCT-15:30 | 6.85 | 25-OCT-07:10 | 17646.79 | 26-OCT-06:10 |
November | 18725.62 | 28-NOV-16:30 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 830.04 | 28-NOV-16:40 | 12688.20 | 02-NOV-15:50 | 6.85 | 01-NOV-05:10 | 33731.72 | 24-NOV-07:10 |
December | 18725.62 | 01-DEC-16:30 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 830.04 | 01-DEC-16:40 | 8682.85 | 22-DEC-16:49 | 6.85 | 04-DEC-07:10 | 61845.35 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14873.83 | 3824.74 | 40437.79 | 826.10 | 7642.41 | 6.85 | 0.00 | |||||||
Maximum of Months | 18725.62 | 3824.74 | 40437.79 | 830.04 | 27591.88 | 6.85 | 82862.81 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 31355.55 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 13817.92 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 32613.76 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 56034.01 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 61062.68 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 85522.40 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 76555.97 | 19-JUL-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 79557.84 | 25-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 70597.14 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 62823.69 | 02-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 36458.33 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23236.67 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13817.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 85522.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 114888.30 | 02-JAN-07:10 | 6241.87 | 18346.02 | 3824.74 | 243.28 | 3362.72 | 6.85 | 82862.81 | 0.00 | 0.00 |
February | 80648.22 | 13-FEB-07:10 | 6241.87 | 18346.02 | 3824.74 | 243.28 | 2994.50 | 6.85 | 48958.89 | 32.06 | 0.00 |
March | 99164.95 | 16-MAR-15:30 | 14732.14 | 38454.47 | 0.00 | 824.78 | 12532.95 | 6.85 | 0.00 | 32613.76 | 0.00 |
April | 130416.59 | 14-APR-15:20 | 14732.14 | 38454.47 | 0.00 | 824.78 | 20364.33 | 6.85 | 0.00 | 56034.01 | 0.00 |
May | 136286.29 | 31-MAY-15:39 | 14732.14 | 38454.47 | 0.00 | 824.78 | 22048.68 | 6.85 | 0.00 | 60219.36 | 0.00 |
June | 163527.48 | 28-JUN-14:00 | 14732.14 | 37678.39 | 0.00 | 824.33 | 24763.37 | 6.85 | 0.00 | 85522.40 | 0.00 |
July | 154244.45 | 31-JUL-15:00 | 14732.14 | 38454.47 | 0.00 | 824.78 | 25799.05 | 6.85 | 0.00 | 74427.16 | 0.00 |
August | 156958.58 | 25-AUG-15:20 | 14732.14 | 38454.47 | 0.00 | 824.78 | 23382.49 | 6.85 | 0.00 | 79557.84 | 0.00 |
September | 146600.91 | 08-SEP-15:00 | 14732.14 | 38454.47 | 0.00 | 824.78 | 21985.53 | 6.85 | 0.00 | 70597.14 | 0.00 |
October | 131917.97 | 02-OCT-15:09 | 14732.14 | 38454.47 | 0.00 | 824.78 | 19274.13 | 6.85 | 0.00 | 58625.59 | 0.00 |
November | 100767.46 | 01-NOV-15:00 | 14832.99 | 38454.47 | 0.00 | 824.78 | 10842.96 | 6.85 | 0.00 | 35805.41 | 0.00 |
December | 93553.59 | 18-DEC-07:10 | 6241.87 | 18346.02 | 3824.74 | 243.28 | 3045.47 | 6.85 | 61845.35 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 80648.22 | 6241.87 | 18346.02 | 0.00 | 243.28 | 2994.50 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 163527.48 | 14832.99 | 38454.47 | 3824.74 | 824.78 | 25799.05 | 6.85 | 82862.81 | 85522.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 21378.36 | 02-JAN-07:30 | 0.00 | 9781.80 | 13-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 18650.30 | 01-FEB-07:00 | 0.00 | 9789.03 | 03-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 29883.24 | 27-MAR-06:19 | 0.00 | 9728.88 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 4127.28 | 21-APR-06:10 | 0.00 | 9610.96 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9488.67 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9370.78 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9296.11 | 05-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9324.41 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9420.52 | 28-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 17512.37 | 25-OCT-06:00 | 0.00 | 9548.76 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 20779.08 | 24-NOV-07:19 | 0.00 | 9677.47 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 33832.17 | 06-DEC-07:19 | 0.00 | 9756.19 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9296.11 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 33832.17 | 0.00 | 9789.03 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.28 | 0.00 | 26.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.22 | 0.00 | 26.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.26 | 0.00 | 26.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 26.25 | 0.00 | 26.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.28 | 0.00 | 26.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.19 | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.36 | 1.17 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.45 | 3.83 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.69 | 7.50 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.64 | 9.67 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.62 | 4.83 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.52 | 4.67 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.47 | 1.33 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.19 | 0.17 | 19.19 | 53.17 | 27.55 | 33.00 | 27.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.19 | 0.17 | 19.19 | 15.83 | 27.69 | 9.67 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.69 | 10.67 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.88 | 12.33 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 28.08 | 11.50 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.98 | 14.67 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.94 | 10.17 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.80 | 8.83 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.53 | 5.17 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.34 | 0.17 | 19.34 | 95.67 | 27.86 | 73.33 | 27.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.34 | 0.17 | 19.34 | 20.83 | 28.08 | 14.67 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.83 | 5.50 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.71 | 6.50 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.58 | 6.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.70 | 7.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.73 | 10.17 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.82 | 6.33 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.97 | 7.50 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.95 | 7.83 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.70 | 3.83 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.80 | 4.50 | 27.80 |
Annual Sum or Average | 0.00 | 0.00 | 87.00 | 27.78 | 65.83 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.97 | 10.17 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.40 | 0.17 | 19.40 | 0.50 | 24.29 | 0.50 | 25.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.61 | 0.17 | 27.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.18 | 5.00 | 28.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28.38 | 5.67 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 28.21 | 7.83 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28.11 | 10.33 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.20 | 6.00 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.97 | 5.83 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.91 | 4.17 | 27.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.50 | 0.67 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.59 | 0.50 | 27.59 |
Annual Sum or Average | 0.17 | 19.40 | 0.17 | 19.40 | 88.67 | 28.11 | 46.67 | 28.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.40 | 0.17 | 19.40 | 21.33 | 28.38 | 10.33 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.38 | 1.00 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.39 | 3.00 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.33 | 2.00 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.32 | 2.17 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.83 | 27.36 | 8.50 | 27.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.39 | 3.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.50 | 5.83 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.59 | 9.00 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.75 | 10.67 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.69 | 13.83 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.69 | 8.83 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.62 | 9.17 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.40 | 5.17 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 72.50 | 27.64 | 62.50 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.75 | 13.83 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 19.63 | 13.67 | 19.63 | 6.00 | 21.08 | 6.00 | 22.09 |
February | 17.50 | 19.14 | 17.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
March | 16.67 | 18.83 | 16.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 1.00 | 20.15 | 1.00 | 20.15 | 19.00 | 24.90 | 19.00 | 25.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 25.33 | 28.33 | 25.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 | 26.38 | 49.33 | 26.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 26.30 | 46.17 | 26.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 26.13 | 59.50 | 26.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 | 25.71 | 77.83 | 25.69 |
October | 4.33 | 19.73 | 4.33 | 19.73 | 55.83 | 24.95 | 54.50 | 25.30 |
November | 4.50 | 19.99 | 4.50 | 19.99 | 11.67 | 23.43 | 11.67 | 24.39 |
December | 18.33 | 18.62 | 18.33 | 18.62 | 5.67 | 19.84 | 5.67 | 20.78 |
Annual Sum or Average | 76.00 | 19.13 | 76.00 | 19.13 | 365.17 | 23.97 | 358.00 | 24.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 0.00 | 18.83 |
Maximum of Months | 18.33 | 20.15 | 18.33 | 20.15 | 79.83 | 26.38 | 77.83 | 26.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.17 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.83 | 3.67 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.01 | 4.33 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.97 | 4.50 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.88 | 8.00 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.85 | 5.17 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.73 | 5.17 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.69 | 3.83 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.50 | 27.50 |
Annual Sum or Average | 0.00 | 0.00 | 67.33 | 27.86 | 36.33 | 27.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 28.01 | 8.00 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.30 | 0.17 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.51 | 5.17 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.48 | 6.00 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.41 | 3.17 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.37 | 2.33 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.17 | 27.46 | 17.50 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.51 | 6.00 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.45 | 0.17 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.72 | 8.33 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.75 | 12.83 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.96 | 11.17 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.84 | 14.83 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.83 | 9.00 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.67 | 9.17 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.56 | 4.00 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 80.00 | 27.80 | 69.50 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.96 | 14.83 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.86 | 6.17 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 1.00 | 27.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.56 | 5.83 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.38 | 5.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.50 | 5.67 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.57 | 8.67 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.69 | 5.33 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.47 | 8.50 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.39 | 9.33 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.70 | 5.17 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.67 | 27.80 |
Annual Sum or Average | 0.00 | 0.00 | 75.83 | 27.57 | 66.33 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.86 | 9.33 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.47 | 0.83 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.71 | 0.17 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.07 | 4.67 | 28.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.28 | 5.17 | 28.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.12 | 5.83 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.04 | 8.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.08 | 5.00 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.88 | 5.17 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.81 | 3.83 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.50 | 0.83 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.65 | 0.50 | 27.65 |
Annual Sum or Average | 0.00 | 0.00 | 72.83 | 28.05 | 40.50 | 28.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.28 | 8.50 | 28.33 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.00 | 23.90 | 22.17 | 23.99 | 0.00 | 23.99 |
February | 175.83 | 23.87 | 35.67 | 24.03 | 0.00 | 24.03 |
March | 173.83 | 24.02 | 53.67 | 24.31 | 0.00 | 24.31 |
April | 133.17 | 24.03 | 33.17 | 24.38 | 0.00 | 24.38 |
May | 89.00 | 24.01 | 34.83 | 24.59 | 0.00 | 24.59 |
June | 4.17 | 24.00 | 103.83 | 25.10 | 0.00 | 25.10 |
July | 10.00 | 24.01 | 402.00 | 24.44 | 0.00 | 24.44 |
August | 2.33 | 24.00 | 449.00 | 24.37 | 0.00 | 24.37 |
September | 0.00 | 0.00 | 393.83 | 24.52 | 0.00 | 24.52 |
October | 111.67 | 24.01 | 162.67 | 24.50 | 0.00 | 24.50 |
November | 193.33 | 24.03 | 116.50 | 24.30 | 5.50 | 24.29 |
December | 413.50 | 23.99 | 0.00 | 23.99 | 0.00 | 23.99 |
Annual Sum or Average | 1601.83 | 23.98 | 1807.33 | 24.33 | 5.50 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 | 23.99 |
Maximum of Months | 413.50 | 24.03 | 449.00 | 25.10 | 5.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 432.33 | 23.57 | 1.33 | 23.57 | 0.00 | 23.57 |
February | 375.00 | 23.42 | 2.83 | 23.43 | 0.00 | 23.43 |
March | 312.67 | 23.69 | 9.67 | 23.72 | 0.00 | 23.72 |
April | 191.00 | 23.99 | 18.00 | 24.14 | 0.00 | 24.14 |
May | 133.17 | 24.03 | 28.33 | 24.35 | 0.00 | 24.35 |
June | 12.33 | 24.00 | 110.17 | 24.99 | 0.00 | 24.99 |
July | 11.17 | 24.02 | 400.83 | 24.42 | 0.00 | 24.42 |
August | 9.00 | 24.00 | 446.33 | 24.33 | 2.50 | 24.33 |
September | 0.00 | 0.00 | 387.00 | 24.47 | 0.00 | 24.47 |
October | 192.00 | 23.94 | 128.17 | 24.20 | 0.00 | 24.20 |
November | 304.33 | 23.77 | 89.33 | 23.94 | 13.50 | 23.94 |
December | 493.17 | 23.43 | 0.00 | 23.43 | 0.00 | 23.43 |
Annual Sum or Average | 2466.17 | 23.65 | 1622.00 | 23.99 | 16.00 | 23.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.43 | 0.00 | 23.43 |
Maximum of Months | 493.17 | 24.03 | 446.33 | 24.99 | 13.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.17 | 23.13 | 16.67 | 23.02 | 16.67 | 22.92 |
February | 414.50 | 22.86 | 2.17 | 22.85 | 2.17 | 22.84 |
March | 385.50 | 23.34 | 9.67 | 23.32 | 5.83 | 23.28 |
April | 200.00 | 23.90 | 18.33 | 24.02 | 0.00 | 24.02 |
May | 143.17 | 24.03 | 34.50 | 24.36 | 0.00 | 24.36 |
June | 8.17 | 24.00 | 140.50 | 24.95 | 0.00 | 24.95 |
July | 17.17 | 24.00 | 406.17 | 24.47 | 6.17 | 24.46 |
August | 14.50 | 24.00 | 451.17 | 24.35 | 7.50 | 24.35 |
September | 8.83 | 23.98 | 381.17 | 24.48 | 7.17 | 24.47 |
October | 244.17 | 23.68 | 109.50 | 23.93 | 1.67 | 23.93 |
November | 365.33 | 23.25 | 57.67 | 23.37 | 16.50 | 23.37 |
December | 497.00 | 22.61 | 42.17 | 22.46 | 42.17 | 22.34 |
Annual Sum or Average | 2781.50 | 23.20 | 1669.67 | 23.64 | 105.83 | 23.60 |
Minimum of Months | 8.17 | 22.61 | 2.17 | 22.46 | 0.00 | 22.34 |
Maximum of Months | 497.00 | 24.03 | 451.17 | 24.95 | 42.17 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 22.27 | 85.00 | 21.96 | 85.00 | 21.72 |
February | 442.83 | 21.94 | 45.00 | 21.78 | 45.00 | 21.65 |
March | 421.17 | 22.57 | 46.83 | 22.43 | 36.67 | 22.27 |
April | 208.33 | 23.55 | 55.83 | 23.90 | 1.00 | 23.89 |
May | 107.83 | 23.87 | 88.17 | 24.61 | 0.33 | 24.61 |
June | 22.00 | 26.40 | 308.83 | 24.89 | 17.00 | 25.00 |
July | 48.83 | 26.01 | 449.50 | 24.79 | 45.17 | 24.90 |
August | 36.00 | 25.42 | 470.50 | 24.53 | 28.00 | 24.60 |
September | 62.83 | 25.31 | 410.17 | 24.65 | 44.17 | 24.77 |
October | 286.83 | 23.08 | 128.83 | 23.43 | 17.33 | 23.37 |
November | 425.00 | 22.46 | 106.67 | 22.38 | 84.83 | 22.27 |
December | 497.00 | 21.57 | 202.00 | 21.26 | 202.00 | 21.09 |
Annual Sum or Average | 3059.50 | 22.58 | 2397.33 | 23.14 | 606.50 | 23.02 |
Minimum of Months | 22.00 | 21.57 | 45.00 | 21.26 | 0.33 | 21.09 |
Maximum of Months | 500.83 | 26.40 | 470.50 | 24.89 | 202.00 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.33 | 22.79 | 60.33 | 22.50 | 55.00 | 22.26 |
February | 350.83 | 22.27 | 43.83 | 22.22 | 27.50 | 22.08 |
March | 302.83 | 22.83 | 67.83 | 22.92 | 20.83 | 22.77 |
April | 105.50 | 23.90 | 187.83 | 24.55 | 9.50 | 24.63 |
May | 63.17 | 24.95 | 241.50 | 24.89 | 19.50 | 25.04 |
June | 41.00 | 27.07 | 408.17 | 24.89 | 39.83 | 25.07 |
July | 65.67 | 26.75 | 469.17 | 24.96 | 65.00 | 25.16 |
August | 49.83 | 26.47 | 491.50 | 24.71 | 47.33 | 24.86 |
September | 60.33 | 26.14 | 439.00 | 24.77 | 50.17 | 24.95 |
October | 200.33 | 23.38 | 188.17 | 23.97 | 17.67 | 23.96 |
November | 348.50 | 22.85 | 94.50 | 22.86 | 57.50 | 22.77 |
December | 494.83 | 22.33 | 114.83 | 21.97 | 114.83 | 21.72 |
Annual Sum or Average | 2505.17 | 23.12 | 2806.67 | 23.72 | 524.67 | 23.70 |
Minimum of Months | 41.00 | 22.27 | 43.83 | 21.97 | 9.50 | 21.72 |
Maximum of Months | 494.83 | 27.07 | 491.50 | 24.96 | 114.83 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 261.00 | 22.64 | 174.17 | 23.11 | 44.00 | 22.95 |
February | 292.33 | 22.10 | 106.33 | 22.45 | 26.17 | 22.31 |
March | 288.67 | 22.64 | 102.17 | 22.88 | 25.83 | 22.72 |
April | 160.33 | 23.62 | 153.33 | 24.21 | 6.17 | 24.26 |
May | 120.33 | 23.90 | 125.67 | 24.54 | 3.17 | 24.58 |
June | 34.33 | 25.68 | 290.67 | 24.87 | 18.67 | 24.99 |
July | 57.50 | 25.93 | 442.33 | 24.80 | 49.83 | 24.93 |
August | 43.17 | 25.74 | 477.50 | 24.59 | 35.17 | 24.69 |
September | 64.00 | 25.82 | 429.50 | 24.76 | 48.50 | 24.91 |
October | 186.67 | 23.63 | 238.33 | 24.18 | 32.00 | 24.28 |
November | 252.00 | 22.84 | 187.50 | 23.31 | 56.50 | 23.20 |
December | 329.00 | 22.33 | 159.33 | 22.39 | 97.17 | 22.14 |
Annual Sum or Average | 2089.33 | 23.08 | 2886.83 | 23.82 | 443.17 | 23.79 |
Minimum of Months | 34.33 | 22.10 | 102.17 | 22.39 | 3.17 | 22.14 |
Maximum of Months | 329.00 | 25.93 | 477.50 | 24.87 | 97.17 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.33 | 22.24 | 98.33 | 22.10 | 70.50 | 21.85 |
February | 376.17 | 21.94 | 60.33 | 21.89 | 40.50 | 21.75 |
March | 341.17 | 22.53 | 91.00 | 22.61 | 35.33 | 22.45 |
April | 172.00 | 23.81 | 160.33 | 24.29 | 15.17 | 24.42 |
May | 120.50 | 24.40 | 200.17 | 24.71 | 20.50 | 24.86 |
June | 37.83 | 26.19 | 338.17 | 24.92 | 26.17 | 25.06 |
July | 68.33 | 26.12 | 453.50 | 24.88 | 63.33 | 25.03 |
August | 47.83 | 25.69 | 481.50 | 24.62 | 40.83 | 24.71 |
September | 73.83 | 25.46 | 424.17 | 24.72 | 57.33 | 24.85 |
October | 242.33 | 23.26 | 185.00 | 23.78 | 26.50 | 23.81 |
November | 344.00 | 22.53 | 136.17 | 22.66 | 76.67 | 22.53 |
December | 447.67 | 21.82 | 172.33 | 21.52 | 163.83 | 21.30 |
Annual Sum or Average | 2657.00 | 22.80 | 2801.00 | 23.47 | 636.67 | 23.40 |
Minimum of Months | 37.83 | 21.82 | 60.33 | 21.52 | 15.17 | 21.30 |
Maximum of Months | 447.67 | 26.19 | 481.50 | 24.92 | 163.83 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.61 | 30.67 | 22.47 | 30.67 | 22.35 |
February | 454.00 | 22.16 | 4.33 | 22.14 | 4.33 | 22.13 |
March | 483.83 | 22.69 | 17.17 | 22.62 | 17.17 | 22.55 |
April | 280.67 | 23.76 | 9.50 | 23.80 | 0.00 | 23.80 |
May | 168.83 | 23.96 | 19.17 | 24.14 | 0.00 | 24.14 |
June | 4.33 | 24.69 | 205.67 | 24.95 | 0.83 | 24.96 |
July | 13.17 | 25.29 | 447.17 | 24.64 | 11.00 | 24.66 |
August | 9.17 | 25.19 | 466.17 | 24.48 | 8.00 | 24.50 |
September | 21.00 | 26.29 | 429.17 | 24.65 | 21.00 | 24.72 |
October | 230.33 | 23.69 | 130.67 | 24.01 | 0.17 | 24.01 |
November | 385.83 | 23.26 | 69.00 | 23.40 | 31.83 | 23.45 |
December | 497.00 | 22.38 | 47.33 | 22.24 | 47.33 | 22.13 |
Annual Sum or Average | 3050.17 | 22.91 | 1876.00 | 23.47 | 172.33 | 23.44 |
Minimum of Months | 4.33 | 22.16 | 4.33 | 22.14 | 0.00 | 22.13 |
Maximum of Months | 502.00 | 26.29 | 466.17 | 24.95 | 47.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 400.83 | 23.25 | 17.83 | 23.25 | 6.50 | 23.20 |
February | 366.17 | 22.76 | 16.50 | 22.83 | 1.17 | 22.82 |
March | 335.00 | 23.16 | 31.17 | 23.27 | 6.17 | 23.23 |
April | 91.83 | 23.90 | 142.50 | 24.61 | 0.83 | 24.63 |
May | 43.33 | 24.25 | 168.83 | 24.96 | 2.83 | 25.00 |
June | 23.17 | 27.17 | 382.33 | 24.83 | 23.17 | 24.96 |
July | 47.50 | 26.74 | 469.67 | 24.90 | 47.50 | 25.06 |
August | 35.33 | 26.78 | 493.67 | 24.71 | 35.33 | 24.84 |
September | 43.33 | 26.76 | 461.17 | 24.81 | 43.33 | 24.96 |
October | 114.17 | 23.89 | 208.50 | 24.50 | 3.00 | 24.53 |
November | 270.67 | 23.66 | 101.33 | 23.88 | 32.00 | 23.91 |
December | 455.83 | 23.17 | 13.17 | 23.11 | 12.33 | 23.05 |
Annual Sum or Average | 2227.17 | 23.51 | 2506.67 | 24.13 | 214.17 | 24.20 |
Minimum of Months | 23.17 | 22.76 | 13.17 | 22.83 | 0.83 | 22.82 |
Maximum of Months | 455.83 | 27.17 | 493.67 | 24.96 | 47.50 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 215.33 | 23.06 | 142.67 | 23.74 | 10.17 | 23.71 |
February | 331.33 | 22.18 | 50.83 | 22.38 | 10.67 | 22.29 |
March | 354.00 | 22.58 | 61.67 | 22.66 | 20.83 | 22.50 |
April | 165.50 | 23.38 | 91.83 | 24.04 | 1.00 | 24.02 |
May | 165.17 | 23.69 | 57.33 | 24.26 | 0.00 | 24.26 |
June | 21.83 | 24.50 | 216.33 | 25.30 | 3.83 | 25.34 |
July | 47.67 | 25.24 | 446.67 | 24.86 | 43.33 | 24.90 |
August | 49.83 | 25.74 | 481.00 | 24.85 | 48.17 | 24.93 |
September | 69.67 | 26.15 | 458.17 | 25.05 | 67.00 | 25.19 |
October | 120.00 | 23.95 | 276.00 | 24.73 | 31.83 | 24.85 |
November | 171.00 | 23.31 | 216.00 | 24.06 | 33.00 | 24.08 |
December | 293.00 | 22.69 | 101.00 | 23.09 | 25.17 | 22.96 |
Annual Sum or Average | 2004.33 | 23.17 | 2599.50 | 24.11 | 295.00 | 24.13 |
Minimum of Months | 21.83 | 22.18 | 50.83 | 22.38 | 0.00 | 22.29 |
Maximum of Months | 354.00 | 26.15 | 481.00 | 25.30 | 67.00 | 25.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 388.50 | 23.06 | 29.83 | 23.07 | 12.67 | 22.98 |
February | 401.50 | 22.51 | 7.00 | 22.55 | 0.33 | 22.55 |
March | 378.50 | 22.97 | 37.67 | 23.07 | 7.33 | 23.03 |
April | 140.17 | 23.91 | 126.50 | 24.38 | 2.83 | 24.42 |
May | 92.67 | 24.26 | 155.33 | 24.73 | 6.33 | 24.80 |
June | 14.33 | 26.69 | 323.33 | 24.87 | 12.00 | 24.95 |
July | 38.50 | 26.43 | 463.50 | 24.83 | 36.83 | 24.95 |
August | 25.50 | 26.50 | 487.00 | 24.64 | 25.50 | 24.73 |
September | 40.17 | 26.65 | 455.00 | 24.80 | 40.17 | 24.94 |
October | 144.50 | 23.95 | 199.50 | 24.41 | 7.67 | 24.47 |
November | 264.17 | 23.58 | 124.50 | 23.89 | 26.33 | 23.93 |
December | 439.33 | 22.85 | 32.17 | 22.82 | 22.67 | 22.73 |
Annual Sum or Average | 2367.83 | 23.30 | 2441.33 | 23.98 | 200.67 | 24.02 |
Minimum of Months | 14.33 | 22.51 | 7.00 | 22.55 | 0.33 | 22.55 |
Maximum of Months | 439.33 | 26.69 | 487.00 | 24.87 | 40.17 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.33 | 22.74 | 27.17 | 22.60 | 27.17 | 22.47 |
February | 435.50 | 22.43 | 5.00 | 22.41 | 5.00 | 22.38 |
March | 402.67 | 22.94 | 20.33 | 22.91 | 12.17 | 22.84 |
April | 198.67 | 23.80 | 40.00 | 24.06 | 0.00 | 24.06 |
May | 99.17 | 24.00 | 63.17 | 24.73 | 0.00 | 24.73 |
June | 7.33 | 27.10 | 262.50 | 24.98 | 7.33 | 25.03 |
July | 28.33 | 25.93 | 449.00 | 24.73 | 27.50 | 24.80 |
August | 20.00 | 25.33 | 464.83 | 24.50 | 15.33 | 24.54 |
September | 34.00 | 25.76 | 412.00 | 24.65 | 30.33 | 24.73 |
October | 264.50 | 23.48 | 118.33 | 23.81 | 1.83 | 23.82 |
November | 405.67 | 22.95 | 67.33 | 23.07 | 37.83 | 23.09 |
December | 497.00 | 22.13 | 84.00 | 21.92 | 84.00 | 21.76 |
Annual Sum or Average | 2890.17 | 22.93 | 2013.67 | 23.52 | 248.50 | 23.49 |
Minimum of Months | 7.33 | 22.13 | 5.00 | 21.92 | 0.00 | 21.76 |
Maximum of Months | 497.33 | 27.10 | 464.83 | 24.98 | 84.00 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 336.00 | 22.98 | 28.00 | 22.98 | 11.83 | 22.89 |
February | 294.17 | 22.59 | 26.83 | 22.73 | 3.17 | 22.71 |
March | 255.00 | 23.06 | 58.67 | 23.32 | 9.00 | 23.26 |
April | 93.50 | 24.12 | 135.17 | 24.79 | 8.00 | 24.87 |
May | 48.33 | 24.97 | 170.83 | 25.18 | 14.17 | 25.31 |
June | 33.67 | 27.16 | 317.50 | 25.08 | 33.67 | 25.26 |
July | 59.00 | 26.68 | 394.67 | 25.08 | 59.00 | 25.27 |
August | 41.33 | 26.58 | 409.83 | 24.82 | 40.33 | 24.97 |
September | 46.33 | 26.59 | 368.50 | 24.92 | 45.17 | 25.09 |
October | 160.33 | 23.64 | 155.17 | 24.30 | 7.17 | 24.36 |
November | 281.00 | 23.19 | 73.83 | 23.40 | 31.00 | 23.41 |
December | 403.33 | 22.66 | 45.50 | 22.46 | 44.33 | 22.29 |
Annual Sum or Average | 2052.00 | 23.38 | 2184.50 | 24.06 | 306.83 | 24.13 |
Minimum of Months | 33.67 | 22.59 | 26.83 | 22.46 | 3.17 | 22.29 |
Maximum of Months | 403.33 | 27.16 | 409.83 | 25.18 | 59.00 | 25.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 240.67 | 23.19 | 162.00 | 23.75 | 17.00 | 23.76 |
February | 272.17 | 22.62 | 91.33 | 23.07 | 3.00 | 23.05 |
March | 261.83 | 23.04 | 89.67 | 23.36 | 8.50 | 23.30 |
April | 138.67 | 23.81 | 131.33 | 24.36 | 1.50 | 24.38 |
May | 101.50 | 23.96 | 91.50 | 24.68 | 0.00 | 24.68 |
June | 16.67 | 25.64 | 251.83 | 24.92 | 8.67 | 24.99 |
July | 45.17 | 25.92 | 442.33 | 24.77 | 41.17 | 24.87 |
August | 31.17 | 25.95 | 475.83 | 24.58 | 26.17 | 24.67 |
September | 47.17 | 26.49 | 435.67 | 24.79 | 45.00 | 24.95 |
October | 152.50 | 24.02 | 243.00 | 24.48 | 21.83 | 24.62 |
November | 215.67 | 23.37 | 188.50 | 23.93 | 32.50 | 23.96 |
December | 302.17 | 22.84 | 107.17 | 23.18 | 34.17 | 23.09 |
Annual Sum or Average | 1825.33 | 23.43 | 2710.17 | 24.15 | 239.50 | 24.20 |
Minimum of Months | 16.67 | 22.62 | 89.67 | 23.07 | 0.00 | 23.05 |
Maximum of Months | 302.17 | 26.49 | 475.83 | 24.92 | 45.00 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.50 | 22.80 | 48.33 | 22.85 | 17.00 | 22.73 |
February | 364.50 | 22.46 | 23.17 | 22.55 | 3.83 | 22.52 |
March | 323.33 | 22.97 | 67.83 | 23.14 | 12.00 | 23.07 |
April | 145.33 | 24.00 | 149.17 | 24.44 | 10.00 | 24.53 |
May | 96.83 | 24.53 | 182.33 | 24.83 | 16.00 | 24.96 |
June | 26.83 | 26.58 | 325.33 | 24.95 | 22.33 | 25.07 |
July | 57.67 | 26.17 | 456.83 | 24.86 | 54.33 | 24.99 |
August | 35.83 | 25.98 | 481.50 | 24.62 | 32.33 | 24.71 |
September | 49.33 | 26.05 | 428.83 | 24.75 | 46.67 | 24.88 |
October | 209.00 | 23.65 | 178.50 | 24.12 | 13.00 | 24.20 |
November | 315.67 | 23.06 | 110.83 | 23.37 | 35.33 | 23.39 |
December | 439.67 | 22.37 | 78.00 | 22.22 | 67.67 | 22.04 |
Annual Sum or Average | 2442.50 | 23.17 | 2530.67 | 23.85 | 330.50 | 23.89 |
Minimum of Months | 26.83 | 22.37 | 23.17 | 22.22 | 3.83 | 22.04 |
Maximum of Months | 439.67 | 26.58 | 481.50 | 24.95 | 67.67 | 25.07 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14013 | 21.81151 | 0.23803 | 6.54451 |
February | 454.00000 | 24.10960 | 34.18170 | 0.30095 | 7.02305 |
March | 514.00000 | 24.23856 | 26.67969 | 0.29829 | 7.07124 |
April | 485.00000 | 24.30363 | 18.91933 | 0.30075 | 7.06120 |
May | 508.00000 | 24.33163 | 18.27348 | -0.5486 | 11.61280 |
June | 496.00000 | 24.32611 | 25.56522 | -0.4767 | 10.09403 |
July | 497.00000 | 24.40201 | 41.82069 | -0.3447 | 7.93694 |
August | 514.00000 | 24.34416 | 44.41218 | -0.3427 | 7.84493 |
September | 485.00000 | 24.42579 | 43.54529 | -0.3263 | 7.83142 |
October | 502.00000 | 24.39119 | 26.44661 | 0.37341 | 8.32607 |
November | 489.00000 | 24.32791 | 26.61202 | 0.33609 | 7.85719 |
December | 497.00000 | 24.12196 | 16.20292 | 0.18607 | 5.87921 |
Annual Sum or Average | 5943.00000 | 24.28954 | 28.67153 | -0.0036 | 7.93506 |
Minimum of Months | 454.00000 | 24.10960 | 16.20292 | -0.5486 | 5.87921 |
Maximum of Months | 514.00000 | 24.42579 | 44.41218 | 0.37341 | 11.61280 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.69675 | 24.19229 | 0.13433 | 5.90678 |
February | 454.00000 | 23.54428 | 36.08699 | 0.16502 | 5.88546 |
March | 514.00000 | 23.90107 | 27.82566 | 0.21292 | 6.28268 |
April | 485.00000 | 24.20942 | 19.60477 | 0.27479 | 6.76253 |
May | 508.00000 | 24.28620 | 18.93814 | -0.5689 | 12.07855 |
June | 496.00000 | 24.31303 | 26.21956 | -0.4823 | 10.24543 |
July | 497.00000 | 24.37941 | 43.41205 | -0.3476 | 7.99053 |
August | 514.00000 | 24.30794 | 46.22484 | -0.3526 | 7.96933 |
September | 485.00000 | 24.38098 | 44.99946 | -0.3452 | 8.08512 |
October | 502.00000 | 24.22349 | 27.33447 | 0.32280 | 7.62383 |
November | 489.00000 | 23.97595 | 27.90017 | 0.23921 | 6.81759 |
December | 497.00000 | 23.43918 | 17.78461 | 0.01765 | 5.50452 |
Annual Sum or Average | 5943.00000 | 24.05815 | 30.00645 | -0.0634 | 7.61391 |
Minimum of Months | 454.00000 | 23.43918 | 17.78461 | -0.5689 | 5.50452 |
Maximum of Months | 514.00000 | 24.38098 | 46.22484 | 0.32280 | 12.07855 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.16729 | 24.95584 | 0.00032 | 6.07435 |
February | 454.00000 | 22.95690 | 37.31365 | 0.02059 | 5.86093 |
March | 514.00000 | 23.53680 | 28.16662 | 0.12033 | 6.12174 |
April | 485.00000 | 24.14975 | 19.65335 | 0.26381 | 6.74696 |
May | 508.00000 | 24.28215 | 18.97526 | -0.5585 | 11.92946 |
June | 496.00000 | 24.35329 | 25.92267 | -0.4471 | 9.73688 |
July | 497.00000 | 24.43368 | 42.79180 | -0.3126 | 7.67304 |
August | 514.00000 | 24.33455 | 45.82025 | -0.3302 | 7.74060 |
September | 485.00000 | 24.38908 | 44.68717 | -0.3362 | 8.01236 |
October | 502.00000 | 24.00521 | 27.41540 | 0.26346 | 7.24199 |
November | 489.00000 | 23.47119 | 28.52975 | 0.11007 | 6.48249 |
December | 497.00000 | 22.60515 | 18.45470 | -0.1878 | 7.00825 |
Annual Sum or Average | 5943.00000 | 23.81298 | 30.17883 | -0.1180 | 7.56947 |
Minimum of Months | 454.00000 | 22.60515 | 18.45470 | -0.5585 | 5.86093 |
Maximum of Months | 514.00000 | 24.43368 | 45.82025 | 0.26381 | 11.92946 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.27757 | 26.16639 | -0.2152 | 8.40448 |
February | 454.00000 | 21.99281 | 40.75227 | -0.2029 | 7.47464 |
March | 514.00000 | 22.84372 | 30.13833 | -0.0384 | 7.19689 |
April | 485.00000 | 24.03173 | 20.00403 | 0.24801 | 7.26101 |
May | 508.00000 | 24.32941 | 18.71404 | -0.5045 | 11.46751 |
June | 496.00000 | 24.52089 | 25.38934 | -0.3085 | 8.25999 |
July | 497.00000 | 24.61379 | 43.00609 | -0.1788 | 7.05394 |
August | 514.00000 | 24.43645 | 46.01903 | -0.2386 | 7.22565 |
September | 485.00000 | 24.45406 | 45.69974 | -0.2673 | 7.87079 |
October | 502.00000 | 23.61291 | 28.83293 | 0.17798 | 7.84469 |
November | 489.00000 | 22.66812 | 31.04026 | -0.0779 | 7.73233 |
December | 497.00000 | 21.56948 | 20.27341 | -0.4413 | 11.19781 |
Annual Sum or Average | 5943.00000 | 23.45598 | 31.27223 | -0.1713 | 8.25801 |
Minimum of Months | 454.00000 | 21.56948 | 18.71404 | -0.5045 | 7.05394 |
Maximum of Months | 514.00000 | 24.61379 | 46.01903 | 0.24801 | 11.46751 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.00013 | 24.67798 | -0.0245 | 7.48108 |
February | 454.00000 | 22.68665 | 39.11163 | -0.0232 | 7.25026 |
March | 514.00000 | 23.39745 | 28.68494 | 0.12060 | 7.34474 |
April | 485.00000 | 24.33060 | 19.12286 | 0.39160 | 9.47785 |
May | 508.00000 | 24.47818 | 18.30590 | -0.3474 | 9.39830 |
June | 496.00000 | 24.57311 | 25.17772 | -0.1856 | 7.49511 |
July | 497.00000 | 24.68313 | 42.72023 | -0.0621 | 6.88738 |
August | 514.00000 | 24.51214 | 45.59012 | -0.1173 | 6.84267 |
September | 485.00000 | 24.52437 | 45.25545 | -0.1673 | 7.33955 |
October | 502.00000 | 24.00088 | 27.65555 | 0.31599 | 9.34228 |
November | 489.00000 | 23.21165 | 29.79711 | 0.07419 | 7.25994 |
December | 497.00000 | 22.34001 | 19.98361 | -0.2437 | 8.95061 |
Annual Sum or Average | 5943.00000 | 23.81939 | 30.44777 | -0.0232 | 7.92516 |
Minimum of Months | 454.00000 | 22.34001 | 18.30590 | -0.3474 | 6.84267 |
Maximum of Months | 514.00000 | 24.68313 | 45.59012 | 0.39160 | 9.47785 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.47492 | 22.17861 | 0.15669 | 9.21545 |
February | 454.00000 | 22.86421 | 37.02355 | 0.04615 | 7.97122 |
March | 514.00000 | 23.34851 | 28.12361 | 0.11969 | 7.84890 |
April | 485.00000 | 24.16038 | 19.41276 | 0.32427 | 8.62595 |
May | 508.00000 | 24.32085 | 18.65014 | -0.4893 | 11.57386 |
June | 496.00000 | 24.48807 | 25.46535 | -0.3289 | 8.60928 |
July | 497.00000 | 24.60558 | 43.00752 | -0.1759 | 7.24488 |
August | 514.00000 | 24.45917 | 45.80304 | -0.1943 | 7.11472 |
September | 485.00000 | 24.52044 | 45.14468 | -0.1725 | 7.50555 |
October | 502.00000 | 24.06887 | 26.91695 | 0.36768 | 10.49624 |
November | 489.00000 | 23.57645 | 27.76985 | 0.21436 | 8.91657 |
December | 497.00000 | 23.05289 | 16.89492 | -0.0214 | 9.68778 |
Annual Sum or Average | 5943.00000 | 23.91838 | 29.65159 | -0.0144 | 8.74217 |
Minimum of Months | 454.00000 | 22.86421 | 16.89492 | -0.4893 | 7.11472 |
Maximum of Months | 514.00000 | 24.60558 | 45.80304 | 0.36768 | 11.57386 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.72874 | 25.20572 | -0.0785 | 8.58487 |
February | 454.00000 | 22.31601 | 40.01796 | -0.1076 | 7.60916 |
March | 514.00000 | 23.09852 | 29.72929 | 0.05105 | 7.77401 |
April | 485.00000 | 24.16001 | 19.81211 | 0.34222 | 9.12598 |
May | 508.00000 | 24.38323 | 18.69478 | -0.4044 | 10.77671 |
June | 496.00000 | 24.56062 | 25.38151 | -0.2179 | 8.02005 |
July | 497.00000 | 24.65257 | 42.99298 | -0.1169 | 7.32201 |
August | 514.00000 | 24.48460 | 45.93099 | -0.1623 | 7.25692 |
September | 485.00000 | 24.50931 | 45.57964 | -0.1935 | 7.64588 |
October | 502.00000 | 23.81187 | 28.39708 | 0.26556 | 9.12631 |
November | 489.00000 | 23.05124 | 30.13100 | 0.04291 | 8.25248 |
December | 497.00000 | 22.07451 | 19.71682 | -0.3038 | 10.49302 |
Annual Sum or Average | 5943.00000 | 23.66168 | 30.90496 | -0.0743 | 8.50544 |
Minimum of Months | 454.00000 | 22.07451 | 18.69478 | -0.4044 | 7.25692 |
Maximum of Months | 514.00000 | 24.65257 | 45.93099 | 0.34222 | 10.77671 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.61246 | 26.26300 | -0.1309 | 6.62083 |
February | 454.00000 | 22.15739 | 40.88434 | -0.1592 | 6.23740 |
March | 514.00000 | 22.77357 | 31.35061 | -0.0611 | 6.34480 |
April | 485.00000 | 23.96991 | 20.30063 | 0.20730 | 6.34709 |
May | 508.00000 | 24.22125 | 18.79826 | -0.5902 | 12.69979 |
June | 496.00000 | 24.43870 | 25.32225 | -0.3887 | 8.88570 |
July | 497.00000 | 24.57458 | 42.00475 | -0.2250 | 6.96118 |
August | 514.00000 | 24.43063 | 44.61467 | -0.2621 | 7.09759 |
September | 485.00000 | 24.50734 | 44.20107 | -0.2503 | 7.31564 |
October | 502.00000 | 24.05617 | 28.09546 | 0.29073 | 7.69236 |
November | 489.00000 | 23.44153 | 29.94877 | 0.11578 | 6.49953 |
December | 497.00000 | 22.37647 | 19.85803 | -0.2271 | 7.14688 |
Annual Sum or Average | 5943.00000 | 23.63875 | 30.90678 | -0.1413 | 7.50489 |
Minimum of Months | 454.00000 | 22.15739 | 18.79826 | -0.5902 | 6.23740 |
Maximum of Months | 514.00000 | 24.57458 | 44.61467 | 0.29073 | 12.69979 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45316 | 24.46162 | 0.08935 | 6.29861 |
February | 454.00000 | 23.02784 | 39.09377 | 0.05994 | 6.22505 |
March | 514.00000 | 23.53982 | 29.56257 | 0.14496 | 6.58727 |
April | 485.00000 | 24.37734 | 18.99620 | 0.37643 | 8.68206 |
May | 508.00000 | 24.47669 | 18.06206 | -0.3964 | 9.52403 |
June | 496.00000 | 24.55490 | 24.92286 | -0.2411 | 7.50854 |
July | 497.00000 | 24.68489 | 41.53453 | -0.0916 | 6.50906 |
August | 514.00000 | 24.54171 | 44.02085 | -0.1241 | 6.47483 |
September | 485.00000 | 24.59770 | 43.68976 | -0.1391 | 6.79430 |
October | 502.00000 | 24.36173 | 26.90106 | 0.41737 | 9.76744 |
November | 489.00000 | 23.91892 | 28.50578 | 0.25847 | 7.24457 |
December | 497.00000 | 23.26591 | 19.08819 | -0.0036 | 6.20899 |
Annual Sum or Average | 5943.00000 | 24.07300 | 29.84406 | 0.02785 | 7.32579 |
Minimum of Months | 454.00000 | 23.02784 | 18.06206 | -0.3964 | 6.20899 |
Maximum of Months | 514.00000 | 24.68489 | 44.02085 | 0.41737 | 9.76744 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.86533 | 21.39879 | 0.27149 | 8.55398 |
February | 454.00000 | 22.75814 | 36.97408 | 0.04956 | 6.92806 |
March | 514.00000 | 23.13140 | 28.17656 | 0.07425 | 7.16132 |
April | 485.00000 | 24.13280 | 18.40857 | 0.28821 | 7.77313 |
May | 508.00000 | 24.26542 | 17.26530 | -0.5688 | 12.89262 |
June | 496.00000 | 24.63928 | 23.94645 | -0.3597 | 8.99518 |
July | 497.00000 | 24.76007 | 41.64211 | -0.1712 | 6.89516 |
August | 514.00000 | 24.71000 | 43.88808 | -0.1457 | 6.72720 |
September | 485.00000 | 24.81797 | 43.06980 | -0.0831 | 6.94178 |
October | 502.00000 | 24.46829 | 25.62510 | 0.47844 | 11.82951 |
November | 489.00000 | 24.04938 | 26.84303 | 0.36356 | 9.30839 |
December | 497.00000 | 23.47384 | 15.85473 | 0.13049 | 8.37153 |
Annual Sum or Average | 5943.00000 | 24.09685 | 28.53792 | 0.02555 | 8.54849 |
Minimum of Months | 454.00000 | 22.75814 | 15.85473 | -0.5688 | 6.72720 |
Maximum of Months | 514.00000 | 24.81797 | 43.88808 | 0.47844 | 12.89262 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.34543 | 24.82624 | 0.06782 | 6.54306 |
February | 454.00000 | 22.69854 | 39.93064 | -0.0179 | 6.07873 |
March | 514.00000 | 23.30607 | 30.43951 | 0.08682 | 6.52764 |
April | 485.00000 | 24.28481 | 19.49540 | 0.34464 | 8.27615 |
May | 508.00000 | 24.41032 | 18.38063 | -0.4417 | 10.31564 |
June | 496.00000 | 24.54447 | 25.10728 | -0.2690 | 7.82743 |
July | 497.00000 | 24.66278 | 41.84075 | -0.1422 | 6.83683 |
August | 514.00000 | 24.51809 | 44.37065 | -0.1671 | 6.73648 |
September | 485.00000 | 24.59656 | 43.94829 | -0.1606 | 6.93164 |
October | 502.00000 | 24.30711 | 27.39605 | 0.39313 | 9.31034 |
November | 489.00000 | 23.89921 | 28.72773 | 0.25687 | 7.54376 |
December | 497.00000 | 23.03470 | 19.05434 | -0.0557 | 6.63638 |
Annual Sum or Average | 5943.00000 | 23.97487 | 30.23221 | -0.0100 | 7.47426 |
Minimum of Months | 454.00000 | 22.69854 | 18.38063 | -0.4417 | 6.07873 |
Maximum of Months | 514.00000 | 24.66278 | 44.37065 | 0.39313 | 10.31564 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.75338 | 25.81878 | -0.0911 | 6.69845 |
February | 454.00000 | 22.49255 | 39.73702 | -0.0753 | 6.09808 |
March | 514.00000 | 23.19401 | 29.85416 | 0.05140 | 6.38314 |
April | 485.00000 | 24.12941 | 19.85296 | 0.26584 | 6.95151 |
May | 508.00000 | 24.35636 | 18.59448 | -0.5094 | 11.11260 |
June | 496.00000 | 24.51517 | 25.48013 | -0.3356 | 8.41550 |
July | 497.00000 | 24.60613 | 43.33101 | -0.2030 | 7.00111 |
August | 514.00000 | 24.43128 | 46.17925 | -0.2568 | 7.18147 |
September | 485.00000 | 24.47213 | 45.62709 | -0.2724 | 7.66529 |
October | 502.00000 | 23.87843 | 28.61375 | 0.24418 | 7.51557 |
November | 489.00000 | 23.14796 | 30.47589 | 0.04559 | 6.68260 |
December | 497.00000 | 22.12809 | 19.91501 | -0.2883 | 8.14735 |
Annual Sum or Average | 5943.00000 | 23.68345 | 31.06594 | -0.1200 | 7.50146 |
Minimum of Months | 454.00000 | 22.12809 | 18.59448 | -0.5094 | 6.09808 |
Maximum of Months | 514.00000 | 24.60613 | 46.17925 | 0.26584 | 11.11260 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.25973 | 24.32062 | 0.04566 | 6.72482 |
February | 385.00000 | 22.97865 | 38.31883 | 0.05527 | 6.59299 |
March | 433.00000 | 23.59138 | 28.28989 | 0.16591 | 7.08677 |
April | 410.00000 | 24.46350 | 18.63247 | 0.39655 | 9.37245 |
May | 430.00000 | 24.59650 | 17.70989 | -0.3511 | 9.41679 |
June | 418.00000 | 24.67746 | 24.70881 | -0.2055 | 7.77648 |
July | 422.00000 | 24.80147 | 42.23612 | -0.0755 | 6.94100 |
August | 433.00000 | 24.61100 | 44.84290 | -0.1349 | 6.95994 |
September | 410.00000 | 24.64146 | 44.64161 | -0.1683 | 7.37414 |
October | 427.00000 | 24.20930 | 27.10520 | 0.35357 | 9.34856 |
November | 417.00000 | 23.54381 | 29.27459 | 0.15784 | 6.96318 |
December | 422.00000 | 22.74438 | 19.17995 | -0.1324 | 7.31522 |
Annual Sum or Average | 5034.00000 | 24.01560 | 29.87467 | 0.00795 | 7.66180 |
Minimum of Months | 385.00000 | 22.74438 | 17.70989 | -0.3511 | 6.59299 |
Maximum of Months | 433.00000 | 24.80147 | 44.84290 | 0.39655 | 9.41679 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.81815 | 21.91958 | 0.25028 | 8.72873 |
February | 454.00000 | 23.28249 | 36.04923 | 0.15474 | 7.38538 |
March | 514.00000 | 23.63880 | 27.80744 | 0.19559 | 7.36395 |
April | 485.00000 | 24.27047 | 19.22294 | 0.34226 | 8.31668 |
May | 508.00000 | 24.37015 | 18.49554 | -0.4889 | 11.01197 |
June | 496.00000 | 24.48323 | 25.55386 | -0.3553 | 8.72710 |
July | 497.00000 | 24.60167 | 43.31109 | -0.1994 | 7.13649 |
August | 514.00000 | 24.46081 | 45.92775 | -0.2120 | 6.99424 |
September | 485.00000 | 24.54519 | 45.01076 | -0.1782 | 7.23060 |
October | 502.00000 | 24.27618 | 26.71157 | 0.41937 | 10.47026 |
November | 489.00000 | 23.92499 | 27.34501 | 0.30857 | 8.85773 |
December | 497.00000 | 23.48345 | 16.48099 | 0.10154 | 8.42108 |
Annual Sum or Average | 5943.00000 | 24.10125 | 29.44493 | 0.02611 | 8.39604 |
Minimum of Months | 454.00000 | 23.28249 | 16.48099 | -0.4889 | 6.99424 |
Maximum of Months | 514.00000 | 24.60167 | 45.92775 | 0.41937 | 11.01197 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.18357 | 24.84160 | 0.03954 | 7.20269 |
February | 454.00000 | 22.79434 | 38.98057 | 0.01452 | 6.45761 |
March | 514.00000 | 23.43686 | 29.37950 | 0.13706 | 7.05527 |
April | 485.00000 | 24.27631 | 19.58166 | 0.36175 | 8.82133 |
May | 508.00000 | 24.43252 | 18.51404 | -0.4044 | 10.13832 |
June | 496.00000 | 24.55760 | 25.43978 | -0.2445 | 7.95018 |
July | 497.00000 | 24.65255 | 43.29439 | -0.1393 | 7.12781 |
August | 514.00000 | 24.48577 | 46.06301 | -0.1798 | 7.07164 |
September | 485.00000 | 24.53131 | 45.48249 | -0.1987 | 7.37108 |
October | 502.00000 | 24.06271 | 28.14608 | 0.32733 | 8.86564 |
November | 489.00000 | 23.49083 | 29.58467 | 0.15690 | 7.51803 |
December | 497.00000 | 22.60406 | 19.27105 | -0.1588 | 7.90588 |
Annual Sum or Average | 5943.00000 | 23.88289 | 30.66057 | -0.0253 | 7.79980 |
Minimum of Months | 454.00000 | 22.60406 | 18.51404 | -0.4044 | 6.45761 |
Maximum of Months | 514.00000 | 24.65255 | 46.06301 | 0.36175 | 10.13832 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.152249E+11 | 0.366443E+10 | 282.32 | 0.150748E+11 | 0.150022E+09 | 0.00 | 1.00 | 17-JAN-14:30 | 0.00 | 01-JAN-00:10 | 43339.09 | 31-JAN-16:30 | 43339.09 | 31-JAN-16:30 | 4683.56 | 08-JAN-15:53 | 10753.88 | 31-JAN-16:30 | 0.00 |
February | 0.377334E+10 | 0.981590E+09 | 162.78 | 0.330979E+10 | 0.463557E+09 | 0.00 | 0.68 | 01-FEB-16:10 | 0.00 | 01-FEB-00:10 | 20650.37 | 01-FEB-16:10 | 20650.37 | 01-FEB-16:10 | 3659.74 | 18-FEB-14:00 | 4917.51 | 01-FEB-16:10 | 0.00 |
March | 0.145292E+11 | 0.357503E+10 | 302.78 | 0.140945E+11 | 0.434651E+09 | 0.00 | 1.00 | 15-MAR-14:40 | 0.00 | 01-MAR-00:10 | 41602.41 | 20-MAR-14:30 | 41602.41 | 20-MAR-14:30 | 2506.56 | 14-MAR-19:20 | 10159.95 | 16-MAR-15:50 | 0.00 |
April | 0.417158E+11 | 0.106797E+11 | 408.94 | 0.416265E+11 | 89345799.74 | 0.00 | 1.00 | 03-APR-09:20 | 0.00 | 01-APR-00:10 | 59886.03 | 14-APR-16:00 | 59886.03 | 14-APR-16:00 | 2310.45 | 16-APR-10:00 | 17704.63 | 14-APR-16:00 | 0.00 |
May | 0.558647E+11 | 0.149484E+11 | 457.34 | 0.558147E+11 | 49979997.48 | 0.00 | 1.00 | 01-MAY-09:40 | 0.00 | 01-MAY-00:10 | 63910.07 | 31-MAY-16:00 | 63910.07 | 31-MAY-16:00 | 2152.41 | 26-MAY-05:10 | 20094.75 | 31-MAY-16:00 | 0.00 |
June | 0.759846E+11 | 0.227627E+11 | 479.72 | 0.757001E+11 | 0.284449E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 80568.03 | 27-JUN-06:03 | 80568.03 | 27-JUN-06:03 | 5103.25 | 17-JUN-17:00 | 27228.12 | 28-JUN-16:00 | 0.00 |
July | 0.783522E+11 | 0.220422E+11 | 497.26 | 0.724430E+11 | 0.590919E+10 | 0.00 | 1.00 | 01-JUL-08:70 | 0.00 | 01-JUL-00:10 | 111942.57 | 14-JUL-05:03 | 82992.71 | 17-JUL-06:03 | 65471.72 | 14-JUL-05:03 | 25745.22 | 19-JUL-13:00 | 0.00 |
August | 0.813959E+11 | 0.227800E+11 | 495.44 | 0.748954E+11 | 0.650047E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 108658.86 | 01-AUG-04:03 | 82393.20 | 14-AUG-06:03 | 51599.94 | 01-AUG-04:03 | 25633.09 | 25-AUG-16:00 | 0.00 |
September | 0.705851E+11 | 0.187615E+11 | 450.32 | 0.641324E+11 | 0.645272E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 108478.77 | 05-SEP-07:20 | 80082.79 | 18-SEP-06:03 | 61788.53 | 05-SEP-06:03 | 23830.88 | 08-SEP-04:02 | 0.00 |
October | 0.397356E+11 | 0.100719E+11 | 389.68 | 0.385116E+11 | 0.122396E+10 | 0.00 | 1.00 | 01-OCT-11:13 | 0.00 | 01-OCT-00:10 | 103787.01 | 03-OCT-06:03 | 77673.12 | 02-OCT-06:03 | 48877.99 | 03-OCT-06:03 | 22684.59 | 03-OCT-06:03 | 0.00 |
November | 0.173770E+11 | 0.413126E+10 | 285.87 | 0.163747E+11 | 0.100226E+10 | 0.00 | 1.00 | 01-NOV-10:05 | 0.00 | 01-NOV-00:10 | 50062.18 | 01-NOV-16:00 | 50062.18 | 01-NOV-16:00 | 23322.69 | 13-NOV-07:02 | 12194.17 | 01-NOV-15:20 | 0.00 |
December | 0.752345E+10 | 0.185360E+10 | 202.42 | 0.747413E+10 | 49322324.68 | 0.00 | 1.00 | 22-DEC-14:00 | 0.00 | 01-DEC-00:10 | 37422.69 | 22-DEC-16:30 | 37422.69 | 22-DEC-16:30 | 1464.82 | 12-DEC-13:00 | 8274.21 | 22-DEC-16:30 | 0.00 |
Annual Sum or Average | 0.502062E+12 | 0.136252E+12 | 4414.88 | 0.479452E+12 | 0.226099E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.377334E+10 | 0.981590E+09 | 162.78 | 0.330979E+10 | 49322324.68 | 0.00 | 0.68 | 0.00 | 20650.37 | 20650.37 | 1464.82 | 4917.51 | 0.00 | ||||||
Maximum of Months | 0.813959E+11 | 0.227800E+11 | 497.26 | 0.757001E+11 | 0.650047E+10 | 0.00 | 1.00 | 0.00 | 111942.57 | 82992.71 | 65471.72 | 27228.12 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.134249E+11 | 0.325843E+10 | 276.92 | 0.132667E+11 | 0.158198E+09 | 0.00 | 1.00 | 17-JAN-15:05 | 0.00 | 01-JAN-00:10 | 39578.00 | 31-JAN-16:30 | 39578.00 | 31-JAN-16:30 | 2872.23 | 08-JAN-12:00 | 9821.58 | 31-JAN-16:30 | 0.00 |
February | 0.297552E+10 | 0.779337E+09 | 151.19 | 0.252540E+10 | 0.450119E+09 | 0.00 | 0.67 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 19368.06 | 22-FEB-16:00 | 19368.06 | 22-FEB-16:00 | 3439.06 | 18-FEB-13:50 | 4626.66 | 22-FEB-16:00 | 0.00 |
March | 0.133715E+11 | 0.329785E+10 | 299.85 | 0.129078E+11 | 0.463686E+09 | 0.00 | 1.00 | 10-MAR-15:05 | 0.00 | 01-MAR-00:10 | 42199.75 | 16-MAR-15:30 | 42199.75 | 16-MAR-15:30 | 2565.27 | 18-MAR-09:05 | 10413.27 | 16-MAR-15:30 | 0.00 |
April | 0.401936E+11 | 0.103015E+11 | 413.59 | 0.401026E+11 | 91023210.99 | 0.00 | 1.00 | 01-APR-14:05 | 0.00 | 01-APR-00:10 | 60103.33 | 24-APR-15:50 | 60103.33 | 24-APR-15:50 | 2147.33 | 16-APR-09:48 | 17726.00 | 14-APR-15:20 | 0.00 |
May | 0.539876E+11 | 0.144414E+11 | 464.01 | 0.539404E+11 | 47227153.02 | 0.00 | 1.00 | 01-MAY-09:40 | 0.00 | 01-MAY-00:10 | 61354.76 | 08-MAY-16:00 | 61354.76 | 08-MAY-16:00 | 2011.19 | 26-MAY-05:10 | 18874.15 | 31-MAY-16:00 | 0.00 |
June | 0.735057E+11 | 0.220247E+11 | 486.68 | 0.732915E+11 | 0.214167E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 75532.34 | 29-JUN-06:03 | 75532.34 | 29-JUN-06:03 | 4639.58 | 17-JUN-17:10 | 27063.77 | 28-JUN-15:00 | 0.00 |
July | 0.713951E+11 | 0.200673E+11 | 492.20 | 0.668281E+11 | 0.456702E+10 | 0.00 | 1.00 | 01-JUL-08:00 | 0.00 | 01-JUL-00:10 | 107147.73 | 14-JUL-05:03 | 76414.03 | 17-JUL-04:02 | 63953.57 | 14-JUL-05:03 | 26443.62 | 19-JUL-12:01 | 0.00 |
August | 0.720601E+11 | 0.201764E+11 | 488.31 | 0.673163E+11 | 0.474378E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 104004.67 | 01-AUG-04:03 | 79539.94 | 28-AUG-06:03 | 50983.04 | 01-AUG-04:03 | 25900.54 | 28-AUG-12:01 | 0.00 |
September | 0.602512E+11 | 0.160844E+11 | 437.46 | 0.553386E+11 | 0.491257E+10 | 0.00 | 1.00 | 01-SEP-05:13 | 0.00 | 01-SEP-00:10 | 103946.17 | 02-SEP-05:03 | 69418.33 | 18-SEP-04:02 | 59189.27 | 05-SEP-06:03 | 23100.92 | 02-SEP-05:03 | 0.00 |
October | 0.333409E+11 | 0.854052E+10 | 375.84 | 0.322710E+11 | 0.106994E+10 | 0.00 | 1.00 | 01-OCT-11:22 | 0.00 | 01-OCT-00:10 | 87216.23 | 03-OCT-06:03 | 73401.64 | 02-OCT-04:02 | 41798.47 | 03-OCT-06:03 | 20389.88 | 02-OCT-14:05 | 0.00 |
November | 0.141372E+11 | 0.341546E+10 | 278.83 | 0.132249E+11 | 0.912264E+09 | 0.00 | 1.00 | 01-NOV-10:30 | 0.00 | 01-NOV-00:10 | 46417.44 | 01-NOV-15:30 | 46417.44 | 01-NOV-15:30 | 17540.07 | 13-NOV-15:05 | 11390.39 | 01-NOV-15:00 | 0.00 |
December | 0.601491E+10 | 0.150671E+10 | 189.28 | 0.595351E+10 | 61409234.94 | 0.00 | 1.00 | 22-DEC-15:05 | 0.00 | 01-DEC-00:10 | 32596.88 | 22-DEC-15:05 | 32596.88 | 22-DEC-15:05 | 1815.22 | 12-DEC-13:00 | 7444.78 | 22-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.454658E+12 | 0.123894E+12 | 4354.16 | 0.436967E+12 | 0.176914E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.297552E+10 | 0.779337E+09 | 151.19 | 0.252540E+10 | 47227153.02 | 0.00 | 0.67 | 0.00 | 19368.06 | 19368.06 | 1815.22 | 4626.66 | 0.00 | ||||||
Maximum of Months | 0.735057E+11 | 0.220247E+11 | 492.20 | 0.732915E+11 | 0.491257E+10 | 0.00 | 1.00 | 0.00 | 107147.73 | 79539.94 | 63953.57 | 27063.77 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.130812E+11 | 0.323057E+10 | 279.14 | 0.128355E+11 | 0.245636E+09 | 0.00 | 1.00 | 24-JAN-15:00 | 0.00 | 01-JAN-00:10 | 43536.99 | 31-JAN-16:10 | 43536.99 | 31-JAN-16:10 | 2177.49 | 07-JAN-17:10 | 10805.01 | 31-JAN-16:10 | 0.00 |
February | 0.298955E+10 | 0.790350E+09 | 161.67 | 0.244829E+10 | 0.541262E+09 | 0.00 | 0.60 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 19693.04 | 22-FEB-16:00 | 19693.04 | 22-FEB-16:00 | 4032.74 | 18-FEB-14:00 | 4790.17 | 22-FEB-16:00 | 0.00 |
March | 0.140358E+11 | 0.349278E+10 | 301.43 | 0.133627E+11 | 0.673098E+09 | 0.00 | 1.00 | 10-MAR-15:20 | 0.00 | 01-MAR-00:10 | 48833.69 | 16-MAR-15:30 | 48833.69 | 16-MAR-15:30 | 3394.55 | 18-MAR-10:00 | 12050.15 | 16-MAR-15:30 | 0.00 |
April | 0.446941E+11 | 0.115638E+11 | 417.87 | 0.445220E+11 | 0.172119E+09 | 0.00 | 1.00 | 01-APR-14:30 | 0.00 | 01-APR-00:10 | 76425.66 | 30-APR-16:31 | 76425.66 | 30-APR-16:31 | 2925.95 | 15-APR-20:20 | 20971.24 | 14-APR-15:30 | 0.00 |
May | 0.601464E+11 | 0.162505E+11 | 465.74 | 0.600467E+11 | 99631801.15 | 0.00 | 1.00 | 01-MAY-10:20 | 0.00 | 01-MAY-00:10 | 72895.10 | 28-MAY-14:32 | 72895.10 | 28-MAY-14:32 | 2634.34 | 29-MAY-22:25 | 22122.61 | 07-MAY-16:12 | 0.00 |
June | 0.830297E+11 | 0.250912E+11 | 493.85 | 0.826622E+11 | 0.367541E+09 | 0.00 | 1.00 | 01-JUN-07:40 | 0.00 | 01-JUN-00:10 | 87098.18 | 28-JUN-14:50 | 87098.18 | 28-JUN-14:50 | 6293.06 | 17-JUN-16:25 | 31985.51 | 28-JUN-15:00 | 0.00 |
July | 0.798374E+11 | 0.225904E+11 | 503.07 | 0.749637E+11 | 0.487370E+10 | 0.00 | 1.00 | 01-JUL-09:05 | 0.00 | 01-JUL-00:10 | 123386.20 | 14-JUL-05:03 | 89724.00 | 16-JUL-15:21 | 74270.17 | 14-JUL-05:03 | 27967.79 | 19-JUL-13:40 | 0.00 |
August | 0.793950E+11 | 0.224022E+11 | 492.01 | 0.744665E+11 | 0.492855E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 119766.80 | 01-AUG-04:03 | 83801.44 | 14-AUG-04:02 | 60880.56 | 01-AUG-04:03 | 29349.65 | 25-AUG-15:20 | 0.00 |
September | 0.649593E+11 | 0.174877E+11 | 440.79 | 0.598970E+11 | 0.506228E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 115935.53 | 05-SEP-06:03 | 79581.11 | 08-SEP-16:00 | 68113.70 | 05-SEP-06:03 | 25439.86 | 08-SEP-16:00 | 0.00 |
October | 0.347370E+11 | 0.901527E+10 | 380.27 | 0.335032E+11 | 0.123379E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 84747.73 | 02-OCT-04:02 | 84747.73 | 02-OCT-04:02 | 29006.74 | 03-OCT-06:03 | 22636.83 | 02-OCT-14:00 | 0.00 |
November | 0.137789E+11 | 0.338602E+10 | 283.25 | 0.128066E+11 | 0.972348E+09 | 0.00 | 1.00 | 01-NOV-12:05 | 0.00 | 01-NOV-00:10 | 52510.24 | 01-NOV-15:30 | 52510.24 | 01-NOV-15:30 | 14371.35 | 13-NOV-15:40 | 12896.33 | 01-NOV-15:00 | 0.00 |
December | 0.566117E+10 | 0.144298E+10 | 191.19 | 0.555387E+10 | 0.107297E+09 | 0.00 | 1.00 | 25-DEC-15:52 | 0.00 | 01-DEC-00:10 | 36158.17 | 25-DEC-15:52 | 36158.17 | 25-DEC-15:52 | 2109.56 | 12-DEC-15:00 | 8299.52 | 25-DEC-15:52 | 0.00 |
Annual Sum or Average | 0.496346E+12 | 0.136744E+12 | 4410.29 | 0.477068E+12 | 0.192772E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.298955E+10 | 0.790350E+09 | 161.67 | 0.244829E+10 | 99631801.15 | 0.00 | 0.60 | 0.00 | 19693.04 | 19693.04 | 2109.56 | 4790.17 | 0.00 | ||||||
Maximum of Months | 0.830297E+11 | 0.250912E+11 | 503.07 | 0.826622E+11 | 0.506228E+10 | 0.00 | 1.00 | 0.00 | 123386.20 | 89724.00 | 74270.17 | 31985.51 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 282.60 | 0.00 | 282.60 | 246.56 | 1060.13 | 0.00 | 0.00 | 0.00 |
February | 322.02 | 0.00 | 322.02 | 177.96 | 1030.05 | 0.00 | 0.00 | 0.00 |
March | 427.96 | 0.00 | 427.96 | 421.26 | 937.21 | 0.00 | 0.00 | 0.00 |
April | 521.41 | 5.41 | 516.00 | 863.55 | 524.78 | 0.00 | 0.00 | 0.00 |
May | 610.37 | 48.87 | 561.49 | 1180.26 | 357.98 | 0.00 | 0.00 | 0.00 |
June | 709.29 | 128.87 | 580.42 | 1818.53 | 155.87 | 0.00 | 0.00 | 0.00 |
July | 604.89 | 63.02 | 541.87 | 1547.67 | 118.56 | 0.00 | 0.00 | 0.00 |
August | 488.25 | 12.13 | 476.12 | 1282.33 | 147.08 | 0.00 | 0.00 | 0.00 |
September | 460.66 | 0.12 | 460.54 | 1071.98 | 221.91 | 0.00 | 0.00 | 0.00 |
October | 356.40 | 0.00 | 356.40 | 530.42 | 681.05 | 0.00 | 0.00 | 0.00 |
November | 296.95 | 0.00 | 296.95 | 245.19 | 979.68 | 0.00 | 0.00 | 0.00 |
December | 263.98 | 0.00 | 263.98 | 160.94 | 1275.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 445.85 | 21.58 | 424.27 | 798.39 | 622.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.98 | 0.00 | 263.98 | 160.94 | 118.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 709.29 | 128.87 | 580.42 | 1818.53 | 1275.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 608.64 | 381.81 | 226.82 | 801.96 | 665.73 | 0.00 | 0.00 | 0.00 |
February | 599.93 | 343.19 | 256.74 | 699.90 | 656.44 | 0.00 | 0.00 | 0.00 |
March | 750.78 | 386.21 | 364.58 | 995.49 | 592.38 | 0.00 | 0.00 | 0.00 |
April | 1071.70 | 638.75 | 432.95 | 1769.03 | 336.77 | 0.00 | 0.00 | 0.00 |
May | 1110.67 | 658.40 | 452.28 | 1954.64 | 239.14 | 0.00 | 0.00 | 0.00 |
June | 1157.68 | 719.37 | 438.31 | 2331.95 | 101.00 | 0.00 | 0.00 | 0.00 |
July | 977.73 | 551.30 | 426.43 | 1987.75 | 76.93 | 0.00 | 0.00 | 0.00 |
August | 927.95 | 529.58 | 398.37 | 1876.06 | 95.35 | 0.00 | 0.00 | 0.00 |
September | 761.45 | 367.03 | 394.42 | 1482.18 | 140.59 | 0.00 | 0.00 | 0.00 |
October | 764.83 | 465.47 | 299.36 | 1205.38 | 428.72 | 0.00 | 0.00 | 0.00 |
November | 588.11 | 353.05 | 235.06 | 765.91 | 621.16 | 0.00 | 0.00 | 0.00 |
December | 536.21 | 323.78 | 212.43 | 633.19 | 796.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.32 | 477.12 | 345.20 | 1378.52 | 394.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.21 | 323.78 | 212.43 | 633.19 | 76.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1157.68 | 719.37 | 452.28 | 2331.95 | 796.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2326.98 | 1858.50 | 468.49 | 3563.43 | 1054.56 | 0.00 | 0.00 | 0.00 |
February | 1471.32 | 992.31 | 479.01 | 2033.96 | 1003.83 | 0.00 | 0.00 | 0.00 |
March | 1224.25 | 630.55 | 593.70 | 1815.95 | 940.03 | 0.00 | 0.00 | 0.00 |
April | 1042.15 | 421.13 | 621.02 | 1962.27 | 551.10 | 0.00 | 0.00 | 0.00 |
May | 698.35 | 115.38 | 582.98 | 1446.52 | 388.74 | 0.00 | 0.00 | 0.00 |
June | 597.99 | 46.10 | 551.89 | 1635.31 | 161.52 | 0.00 | 0.00 | 0.00 |
July | 611.04 | 63.22 | 547.83 | 1594.79 | 119.73 | 0.00 | 0.00 | 0.00 |
August | 743.00 | 205.33 | 537.67 | 1851.00 | 147.80 | 0.00 | 0.00 | 0.00 |
September | 1070.59 | 456.74 | 613.85 | 2244.00 | 224.05 | 0.00 | 0.00 | 0.00 |
October | 1705.87 | 1180.72 | 525.15 | 2860.62 | 673.39 | 0.00 | 0.00 | 0.00 |
November | 1987.99 | 1522.70 | 465.29 | 3005.71 | 967.03 | 0.00 | 0.00 | 0.00 |
December | 2163.40 | 1712.62 | 450.78 | 3171.99 | 1242.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1303.61 | 766.96 | 536.65 | 2267.95 | 621.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 597.99 | 46.10 | 450.78 | 1446.52 | 119.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2326.98 | 1858.50 | 621.02 | 3563.43 | 1242.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.44 | 395.56 | 240.88 | 933.70 | 729.56 | 0.00 | 0.00 | 0.00 |
February | 515.58 | 249.25 | 266.33 | 614.27 | 690.58 | 0.00 | 0.00 | 0.00 |
March | 682.90 | 325.55 | 357.35 | 933.11 | 628.38 | 0.00 | 0.00 | 0.00 |
April | 1048.61 | 598.16 | 450.45 | 1778.53 | 377.62 | 0.00 | 0.00 | 0.00 |
May | 1051.31 | 589.47 | 461.84 | 1897.66 | 274.45 | 0.00 | 0.00 | 0.00 |
June | 1117.64 | 657.35 | 460.29 | 2284.42 | 121.85 | 0.00 | 0.00 | 0.00 |
July | 813.45 | 379.71 | 433.73 | 1716.93 | 89.09 | 0.00 | 0.00 | 0.00 |
August | 775.69 | 389.57 | 386.12 | 1630.66 | 107.85 | 0.00 | 0.00 | 0.00 |
September | 676.14 | 284.09 | 392.06 | 1352.97 | 155.35 | 0.00 | 0.00 | 0.00 |
October | 691.84 | 395.59 | 296.25 | 1129.58 | 466.05 | 0.00 | 0.00 | 0.00 |
November | 637.20 | 384.72 | 252.48 | 908.08 | 670.27 | 0.00 | 0.00 | 0.00 |
December | 513.56 | 292.40 | 221.15 | 680.60 | 862.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.23 | 412.36 | 351.87 | 1324.68 | 430.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.56 | 249.25 | 221.15 | 614.27 | 89.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1117.64 | 657.35 | 461.84 | 2284.42 | 862.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.20 | 0.00 | 94.20 | 80.24 | 374.35 | 0.00 | 0.00 | 0.00 |
February | 107.34 | 0.00 | 107.34 | 61.22 | 357.69 | 0.00 | 0.00 | 0.00 |
March | 142.65 | 0.00 | 142.65 | 147.24 | 313.52 | 0.00 | 0.00 | 0.00 |
April | 173.80 | 1.80 | 171.99 | 296.69 | 172.33 | 0.00 | 0.00 | 0.00 |
May | 203.45 | 16.29 | 187.16 | 403.32 | 114.39 | 0.00 | 0.00 | 0.00 |
June | 236.42 | 42.95 | 193.46 | 615.33 | 48.12 | 0.00 | 0.00 | 0.00 |
July | 201.62 | 21.00 | 180.61 | 521.16 | 38.64 | 0.00 | 0.00 | 0.00 |
August | 162.74 | 4.04 | 158.70 | 429.06 | 50.64 | 0.00 | 0.00 | 0.00 |
September | 153.55 | 0.04 | 153.50 | 355.63 | 79.97 | 0.00 | 0.00 | 0.00 |
October | 118.79 | 0.00 | 118.79 | 171.95 | 251.25 | 0.00 | 0.00 | 0.00 |
November | 98.98 | 0.00 | 98.98 | 74.24 | 366.44 | 0.00 | 0.00 | 0.00 |
December | 87.99 | 0.00 | 87.99 | 45.46 | 470.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 148.61 | 7.19 | 141.42 | 267.73 | 219.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.99 | 0.00 | 87.99 | 45.46 | 38.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.42 | 42.95 | 193.46 | 615.33 | 470.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.20 | 0.00 | 94.20 | 80.24 | 374.37 | 0.00 | 0.00 | 0.00 |
February | 107.34 | 0.00 | 107.34 | 61.23 | 357.71 | 0.00 | 0.00 | 0.00 |
March | 142.65 | 0.00 | 142.65 | 147.25 | 313.54 | 0.00 | 0.00 | 0.00 |
April | 173.80 | 1.80 | 172.00 | 296.70 | 172.33 | 0.00 | 0.00 | 0.00 |
May | 203.46 | 16.29 | 187.16 | 403.34 | 114.40 | 0.00 | 0.00 | 0.00 |
June | 236.43 | 42.96 | 193.47 | 615.37 | 48.12 | 0.00 | 0.00 | 0.00 |
July | 201.63 | 21.01 | 180.62 | 521.19 | 38.64 | 0.00 | 0.00 | 0.00 |
August | 162.75 | 4.04 | 158.71 | 429.08 | 50.64 | 0.00 | 0.00 | 0.00 |
September | 153.55 | 0.04 | 153.51 | 355.65 | 79.98 | 0.00 | 0.00 | 0.00 |
October | 118.80 | 0.00 | 118.80 | 171.96 | 251.26 | 0.00 | 0.00 | 0.00 |
November | 98.98 | 0.00 | 98.98 | 74.24 | 366.46 | 0.00 | 0.00 | 0.00 |
December | 87.99 | 0.00 | 87.99 | 45.46 | 470.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 148.61 | 7.19 | 141.42 | 267.74 | 219.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.99 | 0.00 | 87.99 | 45.46 | 38.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.43 | 42.96 | 193.47 | 615.37 | 470.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.20 | 0.00 | 94.20 | 80.24 | 374.37 | 0.00 | 0.00 | 0.00 |
February | 107.34 | 0.00 | 107.34 | 61.23 | 357.71 | 0.00 | 0.00 | 0.00 |
March | 142.65 | 0.00 | 142.65 | 147.25 | 313.54 | 0.00 | 0.00 | 0.00 |
April | 173.80 | 1.80 | 172.00 | 296.70 | 172.33 | 0.00 | 0.00 | 0.00 |
May | 203.46 | 16.29 | 187.16 | 403.34 | 114.40 | 0.00 | 0.00 | 0.00 |
June | 236.43 | 42.96 | 193.47 | 615.37 | 48.12 | 0.00 | 0.00 | 0.00 |
July | 201.63 | 21.01 | 180.62 | 521.19 | 38.64 | 0.00 | 0.00 | 0.00 |
August | 162.75 | 4.04 | 158.71 | 429.08 | 50.64 | 0.00 | 0.00 | 0.00 |
September | 153.55 | 0.04 | 153.51 | 355.65 | 79.98 | 0.00 | 0.00 | 0.00 |
October | 118.80 | 0.00 | 118.80 | 171.96 | 251.26 | 0.00 | 0.00 | 0.00 |
November | 98.98 | 0.00 | 98.98 | 74.24 | 366.46 | 0.00 | 0.00 | 0.00 |
December | 87.99 | 0.00 | 87.99 | 45.46 | 470.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 148.61 | 7.19 | 141.42 | 267.74 | 219.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.99 | 0.00 | 87.99 | 45.46 | 38.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.43 | 42.96 | 193.47 | 615.37 | 470.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.48 | 367.29 | 218.19 | 764.12 | 693.59 | 0.00 | 0.00 | 0.00 |
February | 577.10 | 330.13 | 246.97 | 675.93 | 673.67 | 0.00 | 0.00 | 0.00 |
March | 722.22 | 371.51 | 350.70 | 968.39 | 588.07 | 0.00 | 0.00 | 0.00 |
April | 1030.93 | 614.44 | 416.48 | 1718.93 | 332.84 | 0.00 | 0.00 | 0.00 |
May | 1068.41 | 633.34 | 435.07 | 1899.43 | 232.80 | 0.00 | 0.00 | 0.00 |
June | 1113.63 | 691.99 | 421.64 | 2261.37 | 97.01 | 0.00 | 0.00 | 0.00 |
July | 940.53 | 530.33 | 410.21 | 1922.10 | 78.27 | 0.00 | 0.00 | 0.00 |
August | 892.65 | 509.43 | 383.22 | 1809.52 | 102.68 | 0.00 | 0.00 | 0.00 |
September | 732.48 | 353.07 | 379.41 | 1424.64 | 153.25 | 0.00 | 0.00 | 0.00 |
October | 735.73 | 447.76 | 287.97 | 1152.23 | 463.45 | 0.00 | 0.00 | 0.00 |
November | 565.73 | 339.62 | 226.12 | 719.96 | 676.64 | 0.00 | 0.00 | 0.00 |
December | 515.80 | 311.46 | 204.35 | 584.18 | 862.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 791.03 | 458.96 | 332.07 | 1328.14 | 411.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.80 | 311.46 | 204.35 | 584.18 | 78.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1113.63 | 691.99 | 435.07 | 2261.37 | 862.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.15 | 14.52 | 8.63 | 30.21 | 27.42 | 0.00 | 0.00 | 0.00 |
February | 22.82 | 13.05 | 9.77 | 26.73 | 26.64 | 0.00 | 0.00 | 0.00 |
March | 28.56 | 14.69 | 13.87 | 38.29 | 23.25 | 0.00 | 0.00 | 0.00 |
April | 40.76 | 24.29 | 16.47 | 67.96 | 13.16 | 0.00 | 0.00 | 0.00 |
May | 42.24 | 25.04 | 17.20 | 75.10 | 9.20 | 0.00 | 0.00 | 0.00 |
June | 44.03 | 27.36 | 16.67 | 89.41 | 3.84 | 0.00 | 0.00 | 0.00 |
July | 37.19 | 20.97 | 16.22 | 76.00 | 3.09 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 20.14 | 15.15 | 71.55 | 4.06 | 0.00 | 0.00 | 0.00 |
September | 28.96 | 13.96 | 15.00 | 56.33 | 6.06 | 0.00 | 0.00 | 0.00 |
October | 29.09 | 17.70 | 11.39 | 45.56 | 18.32 | 0.00 | 0.00 | 0.00 |
November | 22.37 | 13.43 | 8.94 | 28.47 | 26.75 | 0.00 | 0.00 | 0.00 |
December | 20.39 | 12.31 | 8.08 | 23.10 | 34.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.28 | 18.15 | 13.13 | 52.51 | 16.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.39 | 12.31 | 8.08 | 23.10 | 3.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.03 | 27.36 | 17.20 | 89.41 | 34.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 775.65 | 619.49 | 156.16 | 1188.38 | 392.31 | 0.00 | 0.00 | 0.00 |
February | 490.43 | 330.76 | 159.67 | 686.37 | 357.03 | 0.00 | 0.00 | 0.00 |
March | 408.08 | 210.18 | 197.90 | 616.42 | 321.59 | 0.00 | 0.00 | 0.00 |
April | 347.38 | 140.37 | 207.01 | 663.03 | 186.24 | 0.00 | 0.00 | 0.00 |
May | 232.78 | 38.46 | 194.32 | 490.54 | 126.34 | 0.00 | 0.00 | 0.00 |
June | 199.33 | 15.37 | 183.96 | 549.09 | 50.91 | 0.00 | 0.00 | 0.00 |
July | 203.68 | 21.07 | 182.61 | 532.71 | 40.41 | 0.00 | 0.00 | 0.00 |
August | 247.66 | 68.44 | 179.22 | 613.46 | 54.43 | 0.00 | 0.00 | 0.00 |
September | 356.86 | 152.24 | 204.61 | 742.62 | 86.28 | 0.00 | 0.00 | 0.00 |
October | 568.61 | 393.57 | 175.05 | 950.55 | 255.12 | 0.00 | 0.00 | 0.00 |
November | 662.65 | 507.55 | 155.10 | 998.81 | 368.11 | 0.00 | 0.00 | 0.00 |
December | 721.12 | 570.86 | 150.26 | 1053.64 | 468.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 434.53 | 255.65 | 178.88 | 757.92 | 225.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.33 | 15.37 | 150.26 | 490.54 | 40.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.65 | 619.49 | 207.01 | 1188.38 | 468.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 775.65 | 619.49 | 156.16 | 1188.38 | 392.31 | 0.00 | 0.00 | 0.00 |
February | 490.43 | 330.76 | 159.67 | 686.37 | 357.03 | 0.00 | 0.00 | 0.00 |
March | 408.08 | 210.18 | 197.90 | 616.42 | 321.59 | 0.00 | 0.00 | 0.00 |
April | 347.38 | 140.37 | 207.01 | 663.03 | 186.24 | 0.00 | 0.00 | 0.00 |
May | 232.78 | 38.46 | 194.32 | 490.54 | 126.34 | 0.00 | 0.00 | 0.00 |
June | 199.33 | 15.37 | 183.96 | 549.09 | 50.91 | 0.00 | 0.00 | 0.00 |
July | 203.68 | 21.07 | 182.61 | 532.71 | 40.41 | 0.00 | 0.00 | 0.00 |
August | 247.66 | 68.44 | 179.22 | 613.46 | 54.43 | 0.00 | 0.00 | 0.00 |
September | 356.86 | 152.24 | 204.61 | 742.62 | 86.28 | 0.00 | 0.00 | 0.00 |
October | 568.61 | 393.57 | 175.05 | 950.55 | 255.12 | 0.00 | 0.00 | 0.00 |
November | 662.65 | 507.55 | 155.10 | 998.81 | 368.11 | 0.00 | 0.00 | 0.00 |
December | 721.12 | 570.86 | 150.26 | 1053.64 | 468.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 434.53 | 255.65 | 178.88 | 757.92 | 225.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.33 | 15.37 | 150.26 | 490.54 | 40.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.65 | 619.49 | 207.01 | 1188.38 | 468.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 775.60 | 619.45 | 156.15 | 1188.30 | 392.29 | 0.00 | 0.00 | 0.00 |
February | 490.40 | 330.74 | 159.66 | 686.32 | 357.01 | 0.00 | 0.00 | 0.00 |
March | 408.05 | 210.17 | 197.88 | 616.38 | 321.57 | 0.00 | 0.00 | 0.00 |
April | 347.36 | 140.37 | 206.99 | 662.98 | 186.23 | 0.00 | 0.00 | 0.00 |
May | 232.77 | 38.46 | 194.31 | 490.51 | 126.33 | 0.00 | 0.00 | 0.00 |
June | 199.32 | 15.36 | 183.95 | 549.06 | 50.91 | 0.00 | 0.00 | 0.00 |
July | 203.67 | 21.07 | 182.60 | 532.67 | 40.41 | 0.00 | 0.00 | 0.00 |
August | 247.65 | 68.44 | 179.21 | 613.42 | 54.43 | 0.00 | 0.00 | 0.00 |
September | 356.84 | 152.23 | 204.60 | 742.57 | 86.28 | 0.00 | 0.00 | 0.00 |
October | 568.58 | 393.54 | 175.04 | 950.49 | 255.10 | 0.00 | 0.00 | 0.00 |
November | 662.61 | 507.52 | 155.09 | 998.75 | 368.08 | 0.00 | 0.00 | 0.00 |
December | 721.08 | 570.83 | 150.25 | 1053.58 | 468.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 434.50 | 255.63 | 178.87 | 757.87 | 225.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.32 | 15.36 | 150.25 | 490.51 | 40.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 775.60 | 619.45 | 206.99 | 1188.30 | 468.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 612.22 | 380.51 | 231.72 | 895.42 | 765.51 | 0.00 | 0.00 | 0.00 |
February | 495.96 | 239.77 | 256.20 | 596.61 | 707.85 | 0.00 | 0.00 | 0.00 |
March | 656.92 | 313.16 | 343.76 | 911.48 | 625.82 | 0.00 | 0.00 | 0.00 |
April | 1008.72 | 575.40 | 433.32 | 1728.78 | 376.81 | 0.00 | 0.00 | 0.00 |
May | 1011.31 | 567.04 | 444.27 | 1844.28 | 269.95 | 0.00 | 0.00 | 0.00 |
June | 1075.12 | 632.34 | 442.78 | 2214.59 | 118.49 | 0.00 | 0.00 | 0.00 |
July | 782.50 | 365.27 | 417.23 | 1660.49 | 89.72 | 0.00 | 0.00 | 0.00 |
August | 746.18 | 374.75 | 371.44 | 1571.68 | 113.70 | 0.00 | 0.00 | 0.00 |
September | 650.42 | 273.28 | 377.14 | 1300.08 | 167.84 | 0.00 | 0.00 | 0.00 |
October | 665.51 | 380.54 | 284.98 | 1081.08 | 505.73 | 0.00 | 0.00 | 0.00 |
November | 612.95 | 370.08 | 242.87 | 862.90 | 735.30 | 0.00 | 0.00 | 0.00 |
December | 494.02 | 281.28 | 212.74 | 640.66 | 933.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 735.15 | 396.67 | 338.48 | 1278.50 | 449.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.02 | 239.77 | 212.74 | 596.61 | 89.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1075.12 | 632.34 | 444.27 | 2214.59 | 933.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.21 | 15.04 | 9.16 | 35.40 | 30.27 | 0.00 | 0.00 | 0.00 |
February | 19.61 | 9.48 | 10.13 | 23.59 | 27.99 | 0.00 | 0.00 | 0.00 |
March | 25.97 | 12.38 | 13.59 | 36.04 | 24.74 | 0.00 | 0.00 | 0.00 |
April | 39.88 | 22.75 | 17.13 | 68.35 | 14.90 | 0.00 | 0.00 | 0.00 |
May | 39.99 | 22.42 | 17.57 | 72.92 | 10.67 | 0.00 | 0.00 | 0.00 |
June | 42.51 | 25.00 | 17.51 | 87.56 | 4.68 | 0.00 | 0.00 | 0.00 |
July | 30.94 | 14.44 | 16.50 | 65.65 | 3.55 | 0.00 | 0.00 | 0.00 |
August | 29.50 | 14.82 | 14.69 | 62.14 | 4.50 | 0.00 | 0.00 | 0.00 |
September | 25.72 | 10.81 | 14.91 | 51.40 | 6.64 | 0.00 | 0.00 | 0.00 |
October | 26.31 | 15.05 | 11.27 | 42.74 | 20.00 | 0.00 | 0.00 | 0.00 |
November | 24.24 | 14.63 | 9.60 | 34.12 | 29.07 | 0.00 | 0.00 | 0.00 |
December | 19.53 | 11.12 | 8.41 | 25.33 | 36.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.07 | 15.68 | 13.38 | 50.55 | 17.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.53 | 9.48 | 8.41 | 23.59 | 3.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.51 | 25.00 | 17.57 | 87.56 | 36.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 282.60 | 0.00 | 282.60 | 230.09 | 1139.34 | 0.00 | 0.00 | 0.00 |
February | 322.02 | 0.00 | 322.02 | 165.44 | 1113.86 | 0.00 | 0.00 | 0.00 |
March | 427.96 | 0.00 | 427.96 | 408.95 | 992.72 | 0.00 | 0.00 | 0.00 |
April | 521.41 | 5.41 | 516.00 | 867.72 | 545.12 | 0.00 | 0.00 | 0.00 |
May | 610.37 | 48.87 | 561.49 | 1185.82 | 366.57 | 0.00 | 0.00 | 0.00 |
June | 709.29 | 128.87 | 580.42 | 1831.30 | 156.59 | 0.00 | 0.00 | 0.00 |
July | 604.89 | 63.02 | 541.87 | 1562.00 | 118.54 | 0.00 | 0.00 | 0.00 |
August | 488.25 | 12.13 | 476.12 | 1292.88 | 149.74 | 0.00 | 0.00 | 0.00 |
September | 460.66 | 0.12 | 460.54 | 1078.89 | 228.53 | 0.00 | 0.00 | 0.00 |
October | 356.40 | 0.00 | 356.40 | 524.28 | 725.98 | 0.00 | 0.00 | 0.00 |
November | 296.95 | 0.00 | 296.95 | 229.57 | 1058.89 | 0.00 | 0.00 | 0.00 |
December | 263.98 | 0.00 | 263.98 | 141.61 | 1377.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 445.85 | 21.58 | 424.27 | 796.08 | 662.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 263.98 | 0.00 | 263.98 | 141.61 | 118.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 709.29 | 128.87 | 580.42 | 1831.30 | 1377.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 608.64 | 381.81 | 226.82 | 784.83 | 709.29 | 0.00 | 0.00 | 0.00 |
February | 599.93 | 343.19 | 256.74 | 686.85 | 705.32 | 0.00 | 0.00 | 0.00 |
March | 750.78 | 386.21 | 364.58 | 983.05 | 622.73 | 0.00 | 0.00 | 0.00 |
April | 1071.70 | 638.75 | 432.95 | 1769.15 | 347.18 | 0.00 | 0.00 | 0.00 |
May | 1110.67 | 658.40 | 452.28 | 1957.02 | 245.25 | 0.00 | 0.00 | 0.00 |
June | 1157.68 | 719.37 | 438.31 | 2338.64 | 102.00 | 0.00 | 0.00 | 0.00 |
July | 977.73 | 551.30 | 426.43 | 1994.99 | 77.31 | 0.00 | 0.00 | 0.00 |
August | 927.95 | 529.58 | 398.37 | 1880.86 | 97.77 | 0.00 | 0.00 | 0.00 |
September | 761.45 | 367.03 | 394.42 | 1484.18 | 144.90 | 0.00 | 0.00 | 0.00 |
October | 764.83 | 465.47 | 299.36 | 1198.25 | 452.98 | 0.00 | 0.00 | 0.00 |
November | 588.11 | 353.05 | 235.06 | 749.73 | 665.64 | 0.00 | 0.00 | 0.00 |
December | 536.21 | 323.78 | 212.43 | 609.72 | 856.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.32 | 477.12 | 345.20 | 1373.02 | 417.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.21 | 323.78 | 212.43 | 609.72 | 77.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1157.68 | 719.37 | 452.28 | 2338.64 | 856.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2326.98 | 1858.50 | 468.49 | 3548.63 | 1117.76 | 0.00 | 0.00 | 0.00 |
February | 1471.32 | 992.31 | 479.01 | 2019.53 | 1075.39 | 0.00 | 0.00 | 0.00 |
March | 1224.25 | 630.55 | 593.70 | 1806.03 | 990.12 | 0.00 | 0.00 | 0.00 |
April | 1042.15 | 421.13 | 621.02 | 1968.58 | 572.07 | 0.00 | 0.00 | 0.00 |
May | 698.35 | 115.38 | 582.98 | 1453.89 | 401.11 | 0.00 | 0.00 | 0.00 |
June | 597.99 | 46.10 | 551.89 | 1648.45 | 163.90 | 0.00 | 0.00 | 0.00 |
July | 611.04 | 63.22 | 547.83 | 1609.46 | 120.67 | 0.00 | 0.00 | 0.00 |
August | 743.00 | 205.33 | 537.67 | 1862.78 | 151.56 | 0.00 | 0.00 | 0.00 |
September | 1070.59 | 456.74 | 613.85 | 2252.99 | 230.96 | 0.00 | 0.00 | 0.00 |
October | 1705.87 | 1180.72 | 525.15 | 2857.17 | 710.93 | 0.00 | 0.00 | 0.00 |
November | 1987.99 | 1522.70 | 465.29 | 2990.62 | 1030.06 | 0.00 | 0.00 | 0.00 |
December | 2163.40 | 1712.62 | 450.78 | 3149.20 | 1326.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1303.61 | 766.96 | 536.65 | 2266.49 | 655.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 597.99 | 46.10 | 450.78 | 1453.89 | 120.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2326.98 | 1858.50 | 621.02 | 3548.63 | 1326.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.44 | 395.56 | 240.88 | 925.01 | 780.48 | 0.00 | 0.00 | 0.00 |
February | 515.58 | 249.25 | 266.33 | 606.92 | 744.41 | 0.00 | 0.00 | 0.00 |
March | 682.90 | 325.55 | 357.35 | 926.91 | 664.54 | 0.00 | 0.00 | 0.00 |
April | 1048.61 | 598.16 | 450.45 | 1783.29 | 391.80 | 0.00 | 0.00 | 0.00 |
May | 1051.31 | 589.47 | 461.84 | 1904.31 | 282.73 | 0.00 | 0.00 | 0.00 |
June | 1117.64 | 657.35 | 460.29 | 2295.20 | 123.27 | 0.00 | 0.00 | 0.00 |
July | 813.45 | 379.71 | 433.73 | 1727.17 | 89.53 | 0.00 | 0.00 | 0.00 |
August | 775.69 | 389.57 | 386.12 | 1638.75 | 110.05 | 0.00 | 0.00 | 0.00 |
September | 676.14 | 284.09 | 392.06 | 1358.60 | 159.76 | 0.00 | 0.00 | 0.00 |
October | 691.84 | 395.59 | 296.25 | 1127.53 | 494.97 | 0.00 | 0.00 | 0.00 |
November | 637.20 | 384.72 | 252.48 | 899.80 | 720.37 | 0.00 | 0.00 | 0.00 |
December | 513.56 | 292.40 | 221.15 | 668.76 | 928.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.23 | 412.36 | 351.87 | 1324.86 | 456.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.56 | 249.25 | 221.15 | 606.92 | 89.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1117.64 | 657.35 | 461.84 | 2295.20 | 928.02 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.660395E+09 | 0.283946E+10 |
February | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.430525E+09 | 0.249189E+10 |
March | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.112830E+10 | 0.251024E+10 |
April | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.223831E+10 | 0.136023E+10 |
May | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.316121E+10 | 0.958806E+09 |
June | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.471363E+10 | 0.404009E+09 |
July | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.414528E+10 | 0.317561E+09 |
August | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.343459E+10 | 0.393930E+09 |
September | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.277858E+10 | 0.575188E+09 |
October | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.142066E+10 | 0.182413E+10 |
November | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.635539E+09 | 0.253933E+10 |
December | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.431066E+09 | 0.341581E+10 |
Annual Sum or Average | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.251781E+11 | 0.196306E+11 |
Minimum of Months | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.430525E+09 | 0.317561E+09 |
Maximum of Months | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.471363E+10 | 0.341581E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.214796E+10 | 0.178309E+10 |
February | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.169321E+10 | 0.158807E+10 |
March | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.266632E+10 | 0.158664E+10 |
April | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.458533E+10 | 0.872901E+09 |
May | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.523531E+10 | 0.640510E+09 |
June | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.604440E+10 | 0.261797E+09 |
July | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.532399E+10 | 0.206053E+09 |
August | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.502484E+10 | 0.255398E+09 |
September | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.384182E+10 | 0.364419E+09 |
October | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.322850E+10 | 0.114829E+10 |
November | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.198525E+10 | 0.161004E+10 |
December | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.169594E+10 | 0.213373E+10 |
Annual Sum or Average | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.434729E+11 | 0.124509E+11 |
Minimum of Months | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.169321E+10 | 0.206053E+09 |
Maximum of Months | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.604440E+10 | 0.213373E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.954430E+10 | 0.282454E+10 |
February | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.492056E+10 | 0.242846E+10 |
March | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.486384E+10 | 0.251778E+10 |
April | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.508621E+10 | 0.142845E+10 |
May | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.387436E+10 | 0.104119E+10 |
June | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.423872E+10 | 0.418672E+09 |
July | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.427148E+10 | 0.320685E+09 |
August | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.495772E+10 | 0.395872E+09 |
September | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.581645E+10 | 0.580739E+09 |
October | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.766189E+10 | 0.180361E+10 |
November | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.779080E+10 | 0.250654E+10 |
December | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.849584E+10 | 0.332863E+10 |
Annual Sum or Average | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.715222E+11 | 0.195952E+11 |
Minimum of Months | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.387436E+10 | 0.320685E+09 |
Maximum of Months | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.954430E+10 | 0.332863E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.250083E+10 | 0.195405E+10 |
February | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.148603E+10 | 0.167064E+10 |
March | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.249924E+10 | 0.168305E+10 |
April | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.460996E+10 | 0.978780E+09 |
May | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.508270E+10 | 0.735083E+09 |
June | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.592121E+10 | 0.315823E+09 |
July | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.459863E+10 | 0.238613E+09 |
August | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.436755E+10 | 0.288874E+09 |
September | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.350689E+10 | 0.402679E+09 |
October | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.302548E+10 | 0.124827E+10 |
November | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.235374E+10 | 0.173735E+10 |
December | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.182291E+10 | 0.230986E+10 |
Annual Sum or Average | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.417752E+11 | 0.135631E+11 |
Minimum of Months | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.148603E+10 | 0.238613E+09 |
Maximum of Months | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.592121E+10 | 0.230986E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252297E+09 | 0.00 | 0.252297E+09 | 0.214906E+09 | 0.100267E+10 |
February | 0.259665E+09 | 0.00 | 0.259665E+09 | 0.148115E+09 | 0.865321E+09 |
March | 0.382069E+09 | 0.00 | 0.382069E+09 | 0.394367E+09 | 0.839725E+09 |
April | 0.450478E+09 | 4674808.12 | 0.445804E+09 | 0.769011E+09 | 0.446668E+09 |
May | 0.544910E+09 | 43631393.23 | 0.501279E+09 | 0.108024E+10 | 0.306392E+09 |
June | 0.612794E+09 | 0.111338E+09 | 0.501455E+09 | 0.159494E+10 | 0.124716E+09 |
July | 0.540017E+09 | 56259066.12 | 0.483758E+09 | 0.139587E+10 | 0.103486E+09 |
August | 0.435891E+09 | 10828551.39 | 0.425063E+09 | 0.114920E+10 | 0.135633E+09 |
September | 0.397990E+09 | 106244.11 | 0.397884E+09 | 0.921789E+09 | 0.207294E+09 |
October | 0.318180E+09 | 0.00 | 0.318180E+09 | 0.460550E+09 | 0.672943E+09 |
November | 0.256551E+09 | 0.00 | 0.256551E+09 | 0.192422E+09 | 0.949814E+09 |
December | 0.235669E+09 | 0.00 | 0.235669E+09 | 0.121752E+09 | 0.126142E+10 |
Annual Sum or Average | 0.468651E+10 | 0.226838E+09 | 0.445967E+10 | 0.844316E+10 | 0.691608E+10 |
Minimum of Months | 0.235669E+09 | 0.00 | 0.235669E+09 | 0.121752E+09 | 0.103486E+09 |
Maximum of Months | 0.612794E+09 | 0.111338E+09 | 0.501455E+09 | 0.159494E+10 | 0.126142E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252308E+09 | 0.00 | 0.252308E+09 | 0.214917E+09 | 0.100272E+10 |
February | 0.259676E+09 | 0.00 | 0.259676E+09 | 0.148119E+09 | 0.865373E+09 |
March | 0.382085E+09 | 0.00 | 0.382085E+09 | 0.394382E+09 | 0.839773E+09 |
April | 0.450499E+09 | 4674933.78 | 0.445824E+09 | 0.769053E+09 | 0.446691E+09 |
May | 0.544934E+09 | 43632566.05 | 0.501302E+09 | 0.108030E+10 | 0.306405E+09 |
June | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159503E+10 | 0.124721E+09 |
July | 0.540039E+09 | 56260578.38 | 0.483779E+09 | 0.139594E+10 | 0.103490E+09 |
August | 0.435910E+09 | 10828842.47 | 0.425081E+09 | 0.114926E+10 | 0.135638E+09 |
September | 0.398007E+09 | 106246.97 | 0.397901E+09 | 0.921837E+09 | 0.207304E+09 |
October | 0.318194E+09 | 0.00 | 0.318194E+09 | 0.460574E+09 | 0.672979E+09 |
November | 0.256562E+09 | 0.00 | 0.256562E+09 | 0.192430E+09 | 0.949868E+09 |
December | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.121757E+09 | 0.126149E+10 |
Annual Sum or Average | 0.468671E+10 | 0.226845E+09 | 0.445987E+10 | 0.844360E+10 | 0.691645E+10 |
Minimum of Months | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.121757E+09 | 0.103490E+09 |
Maximum of Months | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159503E+10 | 0.126149E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.252308E+09 | 0.00 | 0.252308E+09 | 0.214917E+09 | 0.100272E+10 |
February | 0.259676E+09 | 0.00 | 0.259676E+09 | 0.148119E+09 | 0.865373E+09 |
March | 0.382085E+09 | 0.00 | 0.382085E+09 | 0.394382E+09 | 0.839773E+09 |
April | 0.450499E+09 | 4674933.78 | 0.445824E+09 | 0.769053E+09 | 0.446691E+09 |
May | 0.544934E+09 | 43632566.05 | 0.501302E+09 | 0.108030E+10 | 0.306405E+09 |
June | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159503E+10 | 0.124721E+09 |
July | 0.540039E+09 | 56260578.38 | 0.483779E+09 | 0.139594E+10 | 0.103490E+09 |
August | 0.435910E+09 | 10828842.47 | 0.425081E+09 | 0.114926E+10 | 0.135638E+09 |
September | 0.398007E+09 | 106246.97 | 0.397901E+09 | 0.921837E+09 | 0.207304E+09 |
October | 0.318194E+09 | 0.00 | 0.318194E+09 | 0.460574E+09 | 0.672979E+09 |
November | 0.256562E+09 | 0.00 | 0.256562E+09 | 0.192430E+09 | 0.949868E+09 |
December | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.121757E+09 | 0.126149E+10 |
Annual Sum or Average | 0.468671E+10 | 0.226845E+09 | 0.445987E+10 | 0.844360E+10 | 0.691645E+10 |
Minimum of Months | 0.235679E+09 | 0.00 | 0.235679E+09 | 0.121757E+09 | 0.103490E+09 |
Maximum of Months | 0.612820E+09 | 0.111341E+09 | 0.501478E+09 | 0.159503E+10 | 0.126149E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156814E+10 | 0.983737E+09 | 0.584407E+09 | 0.204663E+10 | 0.185771E+10 |
February | 0.139613E+10 | 0.798645E+09 | 0.597481E+09 | 0.163522E+10 | 0.162975E+10 |
March | 0.193439E+10 | 0.995059E+09 | 0.939327E+09 | 0.259375E+10 | 0.157507E+10 |
April | 0.267216E+10 | 0.159264E+10 | 0.107952E+10 | 0.445546E+10 | 0.862730E+09 |
May | 0.286163E+10 | 0.169634E+10 | 0.116529E+10 | 0.508744E+10 | 0.623522E+09 |
June | 0.288653E+10 | 0.179364E+10 | 0.109289E+10 | 0.586147E+10 | 0.251460E+09 |
July | 0.251912E+10 | 0.142042E+10 | 0.109870E+10 | 0.514814E+10 | 0.209639E+09 |
August | 0.239086E+10 | 0.136446E+10 | 0.102640E+10 | 0.484663E+10 | 0.275030E+09 |
September | 0.189858E+10 | 0.915146E+09 | 0.983434E+09 | 0.369267E+10 | 0.397221E+09 |
October | 0.197058E+10 | 0.119928E+10 | 0.771302E+09 | 0.308613E+10 | 0.124132E+10 |
November | 0.146638E+10 | 0.880287E+09 | 0.586098E+09 | 0.186612E+10 | 0.175386E+10 |
December | 0.138152E+10 | 0.834202E+09 | 0.547323E+09 | 0.156466E+10 | 0.230946E+10 |
Annual Sum or Average | 0.249460E+11 | 0.144739E+11 | 0.104722E+11 | 0.418843E+11 | 0.129868E+11 |
Minimum of Months | 0.138152E+10 | 0.798645E+09 | 0.547323E+09 | 0.156466E+10 | 0.209639E+09 |
Maximum of Months | 0.288653E+10 | 0.179364E+10 | 0.116529E+10 | 0.586147E+10 | 0.230946E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62003001.54 | 38896065.90 | 23106935.64 | 80921985.79 | 73452126.90 |
February | 55201549.19 | 31577700.44 | 23623848.76 | 64655036.03 | 64438890.84 |
March | 76483898.75 | 39343747.54 | 37140151.21 | 0.102554E+09 | 62277015.48 |
April | 0.105655E+09 | 62971384.63 | 42683417.76 | 0.176165E+09 | 34111561.41 |
May | 0.113146E+09 | 67071865.79 | 46074454.33 | 0.201153E+09 | 24653489.96 |
June | 0.114131E+09 | 70918989.07 | 43211812.98 | 0.231757E+09 | 9942492.42 |
July | 99603705.08 | 56162247.99 | 43441457.09 | 0.203553E+09 | 8288922.13 |
August | 94532548.83 | 53949436.95 | 40583111.87 | 0.191631E+09 | 10874450.93 |
September | 75068144.51 | 36184034.32 | 38884110.19 | 0.146005E+09 | 15705774.14 |
October | 77914880.04 | 47418280.87 | 30496599.17 | 0.122023E+09 | 49080506.19 |
November | 57979513.73 | 34805744.57 | 23173769.16 | 73784881.01 | 69346168.14 |
December | 54624237.24 | 32983593.39 | 21640643.85 | 61865245.78 | 91313866.88 |
Annual Sum or Average | 0.986343E+09 | 0.572283E+09 | 0.414060E+09 | 0.165607E+10 | 0.513485E+09 |
Minimum of Months | 54624237.24 | 31577700.44 | 21640643.85 | 61865245.78 | 8288922.13 |
Maximum of Months | 0.114131E+09 | 70918989.07 | 46074454.33 | 0.231757E+09 | 91313866.88 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207749E+10 | 0.165923E+10 | 0.418261E+09 | 0.318296E+10 | 0.105077E+10 |
February | 0.118645E+10 | 0.800182E+09 | 0.386270E+09 | 0.166046E+10 | 0.863733E+09 |
March | 0.109299E+10 | 0.562945E+09 | 0.530046E+09 | 0.165101E+10 | 0.861346E+09 |
April | 0.900411E+09 | 0.363851E+09 | 0.536560E+09 | 0.171856E+10 | 0.482743E+09 |
May | 0.623485E+09 | 0.103005E+09 | 0.520480E+09 | 0.131387E+10 | 0.338390E+09 |
June | 0.516663E+09 | 39827365.51 | 0.476836E+09 | 0.142325E+10 | 0.131969E+09 |
July | 0.545536E+09 | 56439392.14 | 0.489097E+09 | 0.142680E+10 | 0.108229E+09 |
August | 0.663343E+09 | 0.183313E+09 | 0.480029E+09 | 0.164309E+10 | 0.145792E+09 |
September | 0.924977E+09 | 0.394616E+09 | 0.530361E+09 | 0.192487E+10 | 0.223645E+09 |
October | 0.152298E+10 | 0.105412E+10 | 0.468854E+09 | 0.254595E+10 | 0.683302E+09 |
November | 0.171759E+10 | 0.131558E+10 | 0.402008E+09 | 0.258892E+10 | 0.954132E+09 |
December | 0.193145E+10 | 0.152900E+10 | 0.402451E+09 | 0.282208E+10 | 0.125531E+10 |
Annual Sum or Average | 0.137034E+11 | 0.806212E+10 | 0.564125E+10 | 0.239018E+11 | 0.709936E+10 |
Minimum of Months | 0.516663E+09 | 39827365.51 | 0.386270E+09 | 0.131387E+10 | 0.108229E+09 |
Maximum of Months | 0.207749E+10 | 0.165923E+10 | 0.536560E+09 | 0.318296E+10 | 0.125531E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207749E+10 | 0.165923E+10 | 0.418261E+09 | 0.318296E+10 | 0.105077E+10 |
February | 0.118645E+10 | 0.800182E+09 | 0.386270E+09 | 0.166046E+10 | 0.863733E+09 |
March | 0.109299E+10 | 0.562945E+09 | 0.530046E+09 | 0.165101E+10 | 0.861346E+09 |
April | 0.900411E+09 | 0.363851E+09 | 0.536560E+09 | 0.171856E+10 | 0.482743E+09 |
May | 0.623485E+09 | 0.103005E+09 | 0.520480E+09 | 0.131387E+10 | 0.338390E+09 |
June | 0.516663E+09 | 39827365.51 | 0.476836E+09 | 0.142325E+10 | 0.131969E+09 |
July | 0.545536E+09 | 56439392.14 | 0.489097E+09 | 0.142680E+10 | 0.108229E+09 |
August | 0.663343E+09 | 0.183313E+09 | 0.480029E+09 | 0.164309E+10 | 0.145792E+09 |
September | 0.924977E+09 | 0.394616E+09 | 0.530361E+09 | 0.192487E+10 | 0.223645E+09 |
October | 0.152298E+10 | 0.105412E+10 | 0.468854E+09 | 0.254595E+10 | 0.683302E+09 |
November | 0.171759E+10 | 0.131558E+10 | 0.402008E+09 | 0.258892E+10 | 0.954132E+09 |
December | 0.193145E+10 | 0.152900E+10 | 0.402451E+09 | 0.282208E+10 | 0.125531E+10 |
Annual Sum or Average | 0.137034E+11 | 0.806212E+10 | 0.564125E+10 | 0.239018E+11 | 0.709936E+10 |
Minimum of Months | 0.516663E+09 | 39827365.51 | 0.386270E+09 | 0.131387E+10 | 0.108229E+09 |
Maximum of Months | 0.207749E+10 | 0.165923E+10 | 0.536560E+09 | 0.318296E+10 | 0.125531E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207736E+10 | 0.165913E+10 | 0.418235E+09 | 0.318275E+10 | 0.105071E+10 |
February | 0.118638E+10 | 0.800131E+09 | 0.386246E+09 | 0.166035E+10 | 0.863678E+09 |
March | 0.109292E+10 | 0.562909E+09 | 0.530013E+09 | 0.165091E+10 | 0.861292E+09 |
April | 0.900354E+09 | 0.363828E+09 | 0.536527E+09 | 0.171845E+10 | 0.482713E+09 |
May | 0.623446E+09 | 0.102999E+09 | 0.520447E+09 | 0.131378E+10 | 0.338369E+09 |
June | 0.516631E+09 | 39824848.64 | 0.476806E+09 | 0.142316E+10 | 0.131961E+09 |
July | 0.545501E+09 | 56435825.49 | 0.489066E+09 | 0.142671E+10 | 0.108222E+09 |
August | 0.663301E+09 | 0.183302E+09 | 0.479999E+09 | 0.164299E+10 | 0.145783E+09 |
September | 0.924919E+09 | 0.394591E+09 | 0.530328E+09 | 0.192474E+10 | 0.223631E+09 |
October | 0.152288E+10 | 0.105406E+10 | 0.468824E+09 | 0.254579E+10 | 0.683259E+09 |
November | 0.171748E+10 | 0.131550E+10 | 0.401982E+09 | 0.258876E+10 | 0.954072E+09 |
December | 0.193133E+10 | 0.152890E+10 | 0.402425E+09 | 0.282190E+10 | 0.125523E+10 |
Annual Sum or Average | 0.137025E+11 | 0.806161E+10 | 0.564090E+10 | 0.239003E+11 | 0.709891E+10 |
Minimum of Months | 0.516631E+09 | 39824848.64 | 0.386246E+09 | 0.131378E+10 | 0.108222E+09 |
Maximum of Months | 0.207736E+10 | 0.165913E+10 | 0.536527E+09 | 0.318275E+10 | 0.125523E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163978E+10 | 0.101915E+10 | 0.620634E+09 | 0.239830E+10 | 0.205035E+10 |
February | 0.119983E+10 | 0.580043E+09 | 0.619788E+09 | 0.144333E+10 | 0.171242E+10 |
March | 0.175949E+10 | 0.838772E+09 | 0.920714E+09 | 0.244130E+10 | 0.167620E+10 |
April | 0.261459E+10 | 0.149144E+10 | 0.112315E+10 | 0.448100E+10 | 0.976704E+09 |
May | 0.270868E+10 | 0.151876E+10 | 0.118993E+10 | 0.493972E+10 | 0.723037E+09 |
June | 0.278671E+10 | 0.163903E+10 | 0.114768E+10 | 0.574022E+10 | 0.307123E+09 |
July | 0.209584E+10 | 0.978326E+09 | 0.111751E+10 | 0.444747E+10 | 0.240308E+09 |
August | 0.199857E+10 | 0.100372E+10 | 0.994852E+09 | 0.420959E+10 | 0.304547E+09 |
September | 0.168589E+10 | 0.708339E+09 | 0.977548E+09 | 0.336982E+10 | 0.435035E+09 |
October | 0.178251E+10 | 0.101923E+10 | 0.763279E+09 | 0.289557E+10 | 0.135455E+10 |
November | 0.158878E+10 | 0.959256E+09 | 0.629523E+09 | 0.223663E+10 | 0.190591E+10 |
December | 0.132317E+10 | 0.753372E+09 | 0.569801E+09 | 0.171595E+10 | 0.250110E+10 |
Annual Sum or Average | 0.231838E+11 | 0.125094E+11 | 0.106744E+11 | 0.403189E+11 | 0.141873E+11 |
Minimum of Months | 0.119983E+10 | 0.580043E+09 | 0.569801E+09 | 0.144333E+10 | 0.240308E+09 |
Maximum of Months | 0.278671E+10 | 0.163903E+10 | 0.118993E+10 | 0.574022E+10 | 0.250110E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 64835315.84 | 40296040.96 | 24539274.88 | 94826215.70 | 81069091.09 |
February | 47440085.14 | 22934289.60 | 24505795.54 | 57067793.71 | 67707697.86 |
March | 69568302.24 | 33164184.88 | 36404117.36 | 96526696.88 | 66275349.22 |
April | 0.103378E+09 | 58969948.50 | 44408441.88 | 0.177174E+09 | 38617933.80 |
May | 0.107099E+09 | 60050029.77 | 47048541.08 | 0.195312E+09 | 28588208.61 |
June | 0.110184E+09 | 64805458.31 | 45378164.41 | 0.226963E+09 | 12143359.67 |
July | 82867389.00 | 38682005.84 | 44185383.16 | 0.175849E+09 | 9501550.52 |
August | 79021467.22 | 39686009.75 | 39335457.46 | 0.166443E+09 | 12041481.67 |
September | 66658256.67 | 28006975.97 | 38651280.69 | 0.133239E+09 | 17200885.34 |
October | 70478756.76 | 40299438.77 | 30179317.99 | 0.114488E+09 | 53557666.00 |
November | 62818720.93 | 37927983.01 | 24890737.93 | 88434031.55 | 75357922.15 |
December | 52316928.45 | 29787537.45 | 22529391.01 | 67847023.50 | 98891236.36 |
Annual Sum or Average | 0.916666E+09 | 0.494610E+09 | 0.422056E+09 | 0.159417E+10 | 0.560952E+09 |
Minimum of Months | 47440085.14 | 22934289.60 | 22529391.01 | 57067793.71 | 9501550.52 |
Maximum of Months | 0.110184E+09 | 64805458.31 | 47048541.08 | 0.226963E+09 | 98891236.36 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.616262E+09 | 0.305160E+10 |
February | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.400235E+09 | 0.269466E+10 |
March | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.109534E+10 | 0.265889E+10 |
April | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.224913E+10 | 0.141295E+10 |
May | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.317610E+10 | 0.981826E+09 |
June | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.474673E+10 | 0.405879E+09 |
July | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.418365E+10 | 0.317488E+09 |
August | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.346285E+10 | 0.401077E+09 |
September | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.279647E+10 | 0.592343E+09 |
October | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.140422E+10 | 0.194446E+10 |
November | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.595038E+09 | 0.274465E+10 |
December | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.379293E+09 | 0.369062E+10 |
Annual Sum or Average | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.251053E+11 | 0.208965E+11 |
Minimum of Months | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.379293E+09 | 0.317488E+09 |
Maximum of Months | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.474673E+10 | 0.369062E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.210210E+10 | 0.189977E+10 |
February | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.166162E+10 | 0.170631E+10 |
March | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.263299E+10 | 0.166792E+10 |
April | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.458563E+10 | 0.899884E+09 |
May | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.524167E+10 | 0.656880E+09 |
June | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.606176E+10 | 0.264396E+09 |
July | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.534339E+10 | 0.207055E+09 |
August | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.503768E+10 | 0.261859E+09 |
September | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.384700E+10 | 0.375570E+09 |
October | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.320939E+10 | 0.121326E+10 |
November | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.194330E+10 | 0.172534E+10 |
December | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.163306E+10 | 0.229440E+10 |
Annual Sum or Average | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.432996E+11 | 0.131726E+11 |
Minimum of Months | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.163306E+10 | 0.207055E+09 |
Maximum of Months | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.606176E+10 | 0.229440E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.950464E+10 | 0.299382E+10 |
February | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.488565E+10 | 0.260157E+10 |
March | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.483728E+10 | 0.265195E+10 |
April | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.510257E+10 | 0.148280E+10 |
May | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.389409E+10 | 0.107433E+10 |
June | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.427277E+10 | 0.424819E+09 |
July | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.431079E+10 | 0.323199E+09 |
August | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.498928E+10 | 0.405948E+09 |
September | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.583975E+10 | 0.598648E+09 |
October | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.765264E+10 | 0.190416E+10 |
November | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.775169E+10 | 0.266992E+10 |
December | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.843481E+10 | 0.355329E+10 |
Annual Sum or Average | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.714760E+11 | 0.206844E+11 |
Minimum of Months | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.389409E+10 | 0.323199E+09 |
Maximum of Months | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.950464E+10 | 0.355329E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.247755E+10 | 0.209043E+10 |
February | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.146827E+10 | 0.180088E+10 |
March | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.248263E+10 | 0.177991E+10 |
April | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.462229E+10 | 0.101556E+10 |
May | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.510050E+10 | 0.757262E+09 |
June | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.594916E+10 | 0.319507E+09 |
July | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.462606E+10 | 0.239792E+09 |
August | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.438922E+10 | 0.294765E+09 |
September | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.352150E+10 | 0.414105E+09 |
October | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.301999E+10 | 0.132573E+10 |
November | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.233227E+10 | 0.186720E+10 |
December | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.179121E+10 | 0.248561E+10 |
Annual Sum or Average | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.417807E+11 | 0.143907E+11 |
Minimum of Months | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.146827E+10 | 0.239792E+09 |
Maximum of Months | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.594916E+10 | 0.248561E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.56 | 1060.13 | 282.60 | 0.00 | 282.60 | 0.00 | 0.00 |
February | 177.96 | 1030.05 | 322.02 | 0.00 | 322.02 | 0.00 | 0.00 |
March | 421.26 | 937.21 | 427.96 | 0.00 | 427.96 | 0.00 | 0.00 |
April | 863.55 | 524.78 | 521.41 | 5.41 | 516.00 | 0.00 | 0.00 |
May | 1180.26 | 357.98 | 610.37 | 48.87 | 561.49 | 0.00 | 0.00 |
June | 1818.53 | 155.87 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
July | 1547.67 | 118.56 | 604.89 | 63.02 | 541.87 | 0.00 | 0.00 |
August | 1282.33 | 147.08 | 488.25 | 12.13 | 476.12 | 0.00 | 0.00 |
September | 1071.98 | 221.91 | 460.66 | 0.12 | 460.54 | 0.00 | 0.00 |
October | 530.42 | 681.05 | 356.40 | 0.00 | 356.40 | 0.00 | 0.00 |
November | 245.19 | 979.68 | 296.95 | 0.00 | 296.95 | 0.00 | 0.00 |
December | 160.94 | 1275.32 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Annual Sum or Average | 798.39 | 622.48 | 445.85 | 21.58 | 424.27 | 0.00 | 0.00 |
Minimum of Months | 160.94 | 118.56 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Maximum of Months | 1818.53 | 1275.32 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 801.96 | 665.73 | 608.64 | 381.81 | 226.82 | 0.00 | 0.00 |
February | 699.90 | 656.44 | 599.93 | 343.19 | 256.74 | 0.00 | 0.00 |
March | 995.49 | 592.38 | 750.78 | 386.21 | 364.58 | 0.00 | 0.00 |
April | 1769.03 | 336.77 | 1071.70 | 638.75 | 432.95 | 0.00 | 0.00 |
May | 1954.64 | 239.14 | 1110.67 | 658.40 | 452.28 | 0.00 | 0.00 |
June | 2331.95 | 101.00 | 1157.68 | 719.37 | 438.31 | 0.00 | 0.00 |
July | 1987.75 | 76.93 | 977.73 | 551.30 | 426.43 | 0.00 | 0.00 |
August | 1876.06 | 95.35 | 927.95 | 529.58 | 398.37 | 0.00 | 0.00 |
September | 1482.18 | 140.59 | 761.45 | 367.03 | 394.42 | 0.00 | 0.00 |
October | 1205.38 | 428.72 | 764.83 | 465.47 | 299.36 | 0.00 | 0.00 |
November | 765.91 | 621.16 | 588.11 | 353.05 | 235.06 | 0.00 | 0.00 |
December | 633.19 | 796.64 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Annual Sum or Average | 1378.52 | 394.82 | 822.32 | 477.12 | 345.20 | 0.00 | 0.00 |
Minimum of Months | 633.19 | 76.93 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Maximum of Months | 2331.95 | 796.64 | 1157.68 | 719.37 | 452.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3563.43 | 1054.56 | 2326.98 | 1858.50 | 468.49 | 0.00 | 0.00 |
February | 2033.96 | 1003.83 | 1471.32 | 992.31 | 479.01 | 0.00 | 0.00 |
March | 1815.95 | 940.03 | 1224.25 | 630.55 | 593.70 | 0.00 | 0.00 |
April | 1962.27 | 551.10 | 1042.15 | 421.13 | 621.02 | 0.00 | 0.00 |
May | 1446.52 | 388.74 | 698.35 | 115.38 | 582.98 | 0.00 | 0.00 |
June | 1635.31 | 161.52 | 597.99 | 46.10 | 551.89 | 0.00 | 0.00 |
July | 1594.79 | 119.73 | 611.04 | 63.22 | 547.83 | 0.00 | 0.00 |
August | 1851.00 | 147.80 | 743.00 | 205.33 | 537.67 | 0.00 | 0.00 |
September | 2244.00 | 224.05 | 1070.59 | 456.74 | 613.85 | 0.00 | 0.00 |
October | 2860.62 | 673.39 | 1705.87 | 1180.72 | 525.15 | 0.00 | 0.00 |
November | 3005.71 | 967.03 | 1987.99 | 1522.70 | 465.29 | 0.00 | 0.00 |
December | 3171.99 | 1242.77 | 2163.40 | 1712.62 | 450.78 | 0.00 | 0.00 |
Annual Sum or Average | 2267.95 | 621.36 | 1303.61 | 766.96 | 536.65 | 0.00 | 0.00 |
Minimum of Months | 1446.52 | 119.73 | 597.99 | 46.10 | 450.78 | 0.00 | 0.00 |
Maximum of Months | 3563.43 | 1242.77 | 2326.98 | 1858.50 | 621.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 933.70 | 729.56 | 636.44 | 395.56 | 240.88 | 0.00 | 0.00 |
February | 614.27 | 690.58 | 515.58 | 249.25 | 266.33 | 0.00 | 0.00 |
March | 933.11 | 628.38 | 682.90 | 325.55 | 357.35 | 0.00 | 0.00 |
April | 1778.53 | 377.62 | 1048.61 | 598.16 | 450.45 | 0.00 | 0.00 |
May | 1897.66 | 274.45 | 1051.31 | 589.47 | 461.84 | 0.00 | 0.00 |
June | 2284.42 | 121.85 | 1117.64 | 657.35 | 460.29 | 0.00 | 0.00 |
July | 1716.93 | 89.09 | 813.45 | 379.71 | 433.73 | 0.00 | 0.00 |
August | 1630.66 | 107.85 | 775.69 | 389.57 | 386.12 | 0.00 | 0.00 |
September | 1352.97 | 155.35 | 676.14 | 284.09 | 392.06 | 0.00 | 0.00 |
October | 1129.58 | 466.05 | 691.84 | 395.59 | 296.25 | 0.00 | 0.00 |
November | 908.08 | 670.27 | 637.20 | 384.72 | 252.48 | 0.00 | 0.00 |
December | 680.60 | 862.40 | 513.56 | 292.40 | 221.15 | 0.00 | 0.00 |
Annual Sum or Average | 1324.68 | 430.08 | 764.23 | 412.36 | 351.87 | 0.00 | 0.00 |
Minimum of Months | 614.27 | 89.09 | 513.56 | 249.25 | 221.15 | 0.00 | 0.00 |
Maximum of Months | 2284.42 | 862.40 | 1117.64 | 657.35 | 461.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 240.72 | 1123.10 | 282.60 | 0.00 | 282.60 | 0.00 | 0.00 |
February | 183.68 | 1073.11 | 322.01 | 0.00 | 322.01 | 0.00 | 0.00 |
March | 441.73 | 940.59 | 427.96 | 0.00 | 427.96 | 0.00 | 0.00 |
April | 890.09 | 516.99 | 521.40 | 5.41 | 515.99 | 0.00 | 0.00 |
May | 1209.99 | 343.19 | 610.36 | 48.87 | 561.49 | 0.00 | 0.00 |
June | 1846.07 | 144.35 | 709.27 | 128.87 | 580.41 | 0.00 | 0.00 |
July | 1563.53 | 115.91 | 604.87 | 63.02 | 541.86 | 0.00 | 0.00 |
August | 1287.23 | 151.92 | 488.24 | 12.13 | 476.11 | 0.00 | 0.00 |
September | 1066.92 | 239.93 | 460.65 | 0.12 | 460.53 | 0.00 | 0.00 |
October | 515.87 | 753.77 | 356.39 | 0.00 | 356.39 | 0.00 | 0.00 |
November | 222.72 | 1099.36 | 296.94 | 0.00 | 296.94 | 0.00 | 0.00 |
December | 136.37 | 1412.93 | 263.97 | 0.00 | 263.97 | 0.00 | 0.00 |
Annual Sum or Average | 803.22 | 657.95 | 445.84 | 21.58 | 424.26 | 0.00 | 0.00 |
Minimum of Months | 136.37 | 115.91 | 263.97 | 0.00 | 263.97 | 0.00 | 0.00 |
Maximum of Months | 1846.07 | 1412.93 | 709.27 | 128.87 | 580.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 794.34 | 721.01 | 608.63 | 381.81 | 226.82 | 0.00 | 0.00 |
February | 702.66 | 700.31 | 599.92 | 343.18 | 256.74 | 0.00 | 0.00 |
March | 1006.68 | 611.32 | 750.77 | 386.20 | 364.57 | 0.00 | 0.00 |
April | 1786.89 | 346.00 | 1071.69 | 638.74 | 432.95 | 0.00 | 0.00 |
May | 1974.54 | 242.00 | 1110.65 | 658.38 | 452.27 | 0.00 | 0.00 |
June | 2350.78 | 100.85 | 1157.66 | 719.35 | 438.31 | 0.00 | 0.00 |
July | 1998.09 | 81.36 | 977.72 | 551.29 | 426.43 | 0.00 | 0.00 |
August | 1881.07 | 106.74 | 927.94 | 529.57 | 398.37 | 0.00 | 0.00 |
September | 1480.97 | 159.31 | 761.44 | 367.03 | 394.41 | 0.00 | 0.00 |
October | 1197.79 | 481.78 | 764.82 | 465.46 | 299.36 | 0.00 | 0.00 |
November | 748.42 | 703.40 | 588.10 | 353.04 | 235.06 | 0.00 | 0.00 |
December | 607.27 | 896.35 | 536.20 | 323.77 | 212.43 | 0.00 | 0.00 |
Annual Sum or Average | 1380.66 | 428.09 | 822.31 | 477.11 | 345.20 | 0.00 | 0.00 |
Minimum of Months | 607.27 | 81.36 | 536.20 | 323.77 | 212.43 | 0.00 | 0.00 |
Maximum of Months | 2350.78 | 896.35 | 1157.66 | 719.35 | 452.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3565.06 | 1176.92 | 2326.89 | 1858.42 | 468.47 | 0.00 | 0.00 |
February | 2059.05 | 1071.07 | 1471.26 | 992.27 | 479.00 | 0.00 | 0.00 |
March | 1849.22 | 964.75 | 1224.20 | 630.52 | 593.68 | 0.00 | 0.00 |
April | 1989.04 | 558.72 | 1042.12 | 421.11 | 621.01 | 0.00 | 0.00 |
May | 1471.59 | 379.01 | 698.33 | 115.37 | 582.96 | 0.00 | 0.00 |
June | 1647.25 | 152.74 | 597.98 | 46.10 | 551.88 | 0.00 | 0.00 |
July | 1598.09 | 121.22 | 611.03 | 63.21 | 547.81 | 0.00 | 0.00 |
August | 1840.34 | 163.29 | 742.98 | 205.32 | 537.66 | 0.00 | 0.00 |
September | 2227.81 | 258.84 | 1070.55 | 456.72 | 613.83 | 0.00 | 0.00 |
October | 2851.59 | 765.33 | 1705.81 | 1180.67 | 525.14 | 0.00 | 0.00 |
November | 2996.37 | 1104.30 | 1987.91 | 1522.63 | 465.28 | 0.00 | 0.00 |
December | 3160.87 | 1406.01 | 2163.32 | 1712.55 | 450.76 | 0.00 | 0.00 |
Annual Sum or Average | 2273.72 | 675.34 | 1303.57 | 766.93 | 536.64 | 0.00 | 0.00 |
Minimum of Months | 1471.59 | 121.22 | 597.98 | 46.10 | 450.76 | 0.00 | 0.00 |
Maximum of Months | 3565.06 | 1406.01 | 2326.89 | 1858.42 | 621.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 930.83 | 795.78 | 636.43 | 395.55 | 240.88 | 0.00 | 0.00 |
February | 620.20 | 735.84 | 515.57 | 249.25 | 266.33 | 0.00 | 0.00 |
March | 947.52 | 650.57 | 682.89 | 325.54 | 357.35 | 0.00 | 0.00 |
April | 1797.14 | 391.71 | 1048.60 | 598.15 | 450.45 | 0.00 | 0.00 |
May | 1917.20 | 280.62 | 1051.29 | 589.46 | 461.83 | 0.00 | 0.00 |
June | 2302.15 | 123.17 | 1117.63 | 657.34 | 460.28 | 0.00 | 0.00 |
July | 1726.15 | 93.27 | 813.44 | 379.71 | 433.73 | 0.00 | 0.00 |
August | 1633.82 | 118.20 | 775.68 | 389.56 | 386.12 | 0.00 | 0.00 |
September | 1351.49 | 174.47 | 676.14 | 284.08 | 392.05 | 0.00 | 0.00 |
October | 1123.83 | 525.73 | 691.83 | 395.58 | 296.24 | 0.00 | 0.00 |
November | 897.02 | 764.38 | 637.19 | 384.72 | 252.47 | 0.00 | 0.00 |
December | 665.99 | 970.73 | 513.55 | 292.40 | 221.15 | 0.00 | 0.00 |
Annual Sum or Average | 1329.05 | 467.66 | 764.22 | 412.36 | 351.87 | 0.00 | 0.00 |
Minimum of Months | 620.20 | 93.27 | 513.55 | 249.25 | 221.15 | 0.00 | 0.00 |
Maximum of Months | 2302.15 | 970.73 | 1117.63 | 657.34 | 461.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.09 | 1139.34 | 282.60 | 0.00 | 282.60 | 0.00 | 0.00 |
February | 165.44 | 1113.86 | 322.02 | 0.00 | 322.02 | 0.00 | 0.00 |
March | 408.95 | 992.72 | 427.96 | 0.00 | 427.96 | 0.00 | 0.00 |
April | 867.72 | 545.12 | 521.41 | 5.41 | 516.00 | 0.00 | 0.00 |
May | 1185.82 | 366.57 | 610.37 | 48.87 | 561.49 | 0.00 | 0.00 |
June | 1831.30 | 156.59 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
July | 1562.00 | 118.54 | 604.89 | 63.02 | 541.87 | 0.00 | 0.00 |
August | 1292.88 | 149.74 | 488.25 | 12.13 | 476.12 | 0.00 | 0.00 |
September | 1078.89 | 228.53 | 460.66 | 0.12 | 460.54 | 0.00 | 0.00 |
October | 524.28 | 725.98 | 356.40 | 0.00 | 356.40 | 0.00 | 0.00 |
November | 229.57 | 1058.89 | 296.95 | 0.00 | 296.95 | 0.00 | 0.00 |
December | 141.61 | 1377.92 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Annual Sum or Average | 796.08 | 662.62 | 445.85 | 21.58 | 424.27 | 0.00 | 0.00 |
Minimum of Months | 141.61 | 118.54 | 263.98 | 0.00 | 263.98 | 0.00 | 0.00 |
Maximum of Months | 1831.30 | 1377.92 | 709.29 | 128.87 | 580.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 784.83 | 709.29 | 608.64 | 381.81 | 226.82 | 0.00 | 0.00 |
February | 686.85 | 705.32 | 599.93 | 343.19 | 256.74 | 0.00 | 0.00 |
March | 983.05 | 622.73 | 750.78 | 386.21 | 364.58 | 0.00 | 0.00 |
April | 1769.15 | 347.18 | 1071.70 | 638.75 | 432.95 | 0.00 | 0.00 |
May | 1957.02 | 245.25 | 1110.67 | 658.40 | 452.28 | 0.00 | 0.00 |
June | 2338.64 | 102.00 | 1157.68 | 719.37 | 438.31 | 0.00 | 0.00 |
July | 1994.99 | 77.31 | 977.73 | 551.30 | 426.43 | 0.00 | 0.00 |
August | 1880.86 | 97.77 | 927.95 | 529.58 | 398.37 | 0.00 | 0.00 |
September | 1484.18 | 144.90 | 761.45 | 367.03 | 394.42 | 0.00 | 0.00 |
October | 1198.25 | 452.98 | 764.83 | 465.47 | 299.36 | 0.00 | 0.00 |
November | 749.73 | 665.64 | 588.11 | 353.05 | 235.06 | 0.00 | 0.00 |
December | 609.72 | 856.63 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Annual Sum or Average | 1373.02 | 417.70 | 822.32 | 477.12 | 345.20 | 0.00 | 0.00 |
Minimum of Months | 609.72 | 77.31 | 536.21 | 323.78 | 212.43 | 0.00 | 0.00 |
Maximum of Months | 2338.64 | 856.63 | 1157.68 | 719.37 | 452.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3548.63 | 1117.76 | 2326.98 | 1858.50 | 468.49 | 0.00 | 0.00 |
February | 2019.53 | 1075.39 | 1471.32 | 992.31 | 479.01 | 0.00 | 0.00 |
March | 1806.03 | 990.12 | 1224.25 | 630.55 | 593.70 | 0.00 | 0.00 |
April | 1968.58 | 572.07 | 1042.15 | 421.13 | 621.02 | 0.00 | 0.00 |
May | 1453.89 | 401.11 | 698.35 | 115.38 | 582.98 | 0.00 | 0.00 |
June | 1648.45 | 163.90 | 597.99 | 46.10 | 551.89 | 0.00 | 0.00 |
July | 1609.46 | 120.67 | 611.04 | 63.22 | 547.83 | 0.00 | 0.00 |
August | 1862.78 | 151.56 | 743.00 | 205.33 | 537.67 | 0.00 | 0.00 |
September | 2252.99 | 230.96 | 1070.59 | 456.74 | 613.85 | 0.00 | 0.00 |
October | 2857.17 | 710.93 | 1705.87 | 1180.72 | 525.15 | 0.00 | 0.00 |
November | 2990.62 | 1030.06 | 1987.99 | 1522.70 | 465.29 | 0.00 | 0.00 |
December | 3149.20 | 1326.65 | 2163.40 | 1712.62 | 450.78 | 0.00 | 0.00 |
Annual Sum or Average | 2266.49 | 655.90 | 1303.61 | 766.96 | 536.65 | 0.00 | 0.00 |
Minimum of Months | 1453.89 | 120.67 | 597.99 | 46.10 | 450.78 | 0.00 | 0.00 |
Maximum of Months | 3548.63 | 1326.65 | 2326.98 | 1858.50 | 621.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 925.01 | 780.48 | 636.44 | 395.56 | 240.88 | 0.00 | 0.00 |
February | 606.92 | 744.41 | 515.58 | 249.25 | 266.33 | 0.00 | 0.00 |
March | 926.91 | 664.54 | 682.90 | 325.55 | 357.35 | 0.00 | 0.00 |
April | 1783.29 | 391.80 | 1048.61 | 598.16 | 450.45 | 0.00 | 0.00 |
May | 1904.31 | 282.73 | 1051.31 | 589.47 | 461.84 | 0.00 | 0.00 |
June | 2295.20 | 123.27 | 1117.64 | 657.35 | 460.29 | 0.00 | 0.00 |
July | 1727.17 | 89.53 | 813.45 | 379.71 | 433.73 | 0.00 | 0.00 |
August | 1638.75 | 110.05 | 775.69 | 389.57 | 386.12 | 0.00 | 0.00 |
September | 1358.60 | 159.76 | 676.14 | 284.09 | 392.06 | 0.00 | 0.00 |
October | 1127.53 | 494.97 | 691.84 | 395.59 | 296.25 | 0.00 | 0.00 |
November | 899.80 | 720.37 | 637.20 | 384.72 | 252.48 | 0.00 | 0.00 |
December | 668.76 | 928.02 | 513.56 | 292.40 | 221.15 | 0.00 | 0.00 |
Annual Sum or Average | 1324.86 | 456.33 | 764.23 | 412.36 | 351.87 | 0.00 | 0.00 |
Minimum of Months | 606.92 | 89.53 | 513.56 | 249.25 | 221.15 | 0.00 | 0.00 |
Maximum of Months | 2295.20 | 928.02 | 1117.64 | 657.35 | 461.84 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.660395E+09 | 0.283946E+10 | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.00 | 0.00 |
February | 0.430525E+09 | 0.249189E+10 | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.00 | 0.00 |
March | 0.112830E+10 | 0.251024E+10 | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.00 | 0.00 |
April | 0.223831E+10 | 0.136023E+10 | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.00 | 0.00 |
May | 0.316121E+10 | 0.958806E+09 | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.00 | 0.00 |
June | 0.471363E+10 | 0.404009E+09 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
July | 0.414528E+10 | 0.317561E+09 | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.00 | 0.00 |
August | 0.343459E+10 | 0.393930E+09 | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.00 | 0.00 |
September | 0.277858E+10 | 0.575188E+09 | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.00 | 0.00 |
October | 0.142066E+10 | 0.182413E+10 | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.00 | 0.00 |
November | 0.635539E+09 | 0.253933E+10 | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.00 | 0.00 |
December | 0.431066E+09 | 0.341581E+10 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.251781E+11 | 0.196306E+11 | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430525E+09 | 0.317561E+09 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Maximum of Months | 0.471363E+10 | 0.341581E+10 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.214796E+10 | 0.178309E+10 | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.00 | 0.00 |
February | 0.169321E+10 | 0.158807E+10 | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.00 | 0.00 |
March | 0.266632E+10 | 0.158664E+10 | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.00 | 0.00 |
April | 0.458533E+10 | 0.872901E+09 | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.00 | 0.00 |
May | 0.523531E+10 | 0.640510E+09 | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.00 | 0.00 |
June | 0.604440E+10 | 0.261797E+09 | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.00 | 0.00 |
July | 0.532399E+10 | 0.206053E+09 | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.00 | 0.00 |
August | 0.502484E+10 | 0.255398E+09 | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.00 | 0.00 |
September | 0.384182E+10 | 0.364419E+09 | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.00 | 0.00 |
October | 0.322850E+10 | 0.114829E+10 | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.00 | 0.00 |
November | 0.198525E+10 | 0.161004E+10 | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.00 | 0.00 |
December | 0.169594E+10 | 0.213373E+10 | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.434729E+11 | 0.124509E+11 | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169321E+10 | 0.206053E+09 | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.00 | 0.00 |
Maximum of Months | 0.604440E+10 | 0.213373E+10 | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.954430E+10 | 0.282454E+10 | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.00 | 0.00 |
February | 0.492056E+10 | 0.242846E+10 | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.00 | 0.00 |
March | 0.486384E+10 | 0.251778E+10 | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.00 | 0.00 |
April | 0.508621E+10 | 0.142845E+10 | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.00 | 0.00 |
May | 0.387436E+10 | 0.104119E+10 | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.00 | 0.00 |
June | 0.423872E+10 | 0.418672E+09 | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.00 | 0.00 |
July | 0.427148E+10 | 0.320685E+09 | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.00 | 0.00 |
August | 0.495772E+10 | 0.395872E+09 | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.00 | 0.00 |
September | 0.581645E+10 | 0.580739E+09 | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.00 | 0.00 |
October | 0.766189E+10 | 0.180361E+10 | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.00 | 0.00 |
November | 0.779080E+10 | 0.250654E+10 | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.00 | 0.00 |
December | 0.849584E+10 | 0.332863E+10 | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.715222E+11 | 0.195952E+11 | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.00 | 0.00 |
Minimum of Months | 0.387436E+10 | 0.320685E+09 | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.954430E+10 | 0.332863E+10 | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250083E+10 | 0.195405E+10 | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.00 | 0.00 |
February | 0.148603E+10 | 0.167064E+10 | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.00 | 0.00 |
March | 0.249924E+10 | 0.168305E+10 | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.00 | 0.00 |
April | 0.460996E+10 | 0.978780E+09 | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.00 | 0.00 |
May | 0.508270E+10 | 0.735083E+09 | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.00 | 0.00 |
June | 0.592121E+10 | 0.315823E+09 | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.00 | 0.00 |
July | 0.459863E+10 | 0.238613E+09 | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.00 | 0.00 |
August | 0.436755E+10 | 0.288874E+09 | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.00 | 0.00 |
September | 0.350689E+10 | 0.402679E+09 | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.00 | 0.00 |
October | 0.302548E+10 | 0.124827E+10 | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.00 | 0.00 |
November | 0.235374E+10 | 0.173735E+10 | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.00 | 0.00 |
December | 0.182291E+10 | 0.230986E+10 | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.417752E+11 | 0.135631E+11 | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148603E+10 | 0.238613E+09 | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.00 | 0.00 |
Maximum of Months | 0.592121E+10 | 0.230986E+10 | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.644740E+09 | 0.300812E+10 | 0.756913E+09 | 0.00 | 0.756913E+09 | 0.00 | 0.00 |
February | 0.444352E+09 | 0.259607E+10 | 0.779016E+09 | 0.00 | 0.779016E+09 | 0.00 | 0.00 |
March | 0.118313E+10 | 0.251927E+10 | 0.114624E+10 | 0.00 | 0.114624E+10 | 0.00 | 0.00 |
April | 0.230712E+10 | 0.134005E+10 | 0.135148E+10 | 14024675.69 | 0.133745E+10 | 0.00 | 0.00 |
May | 0.324085E+10 | 0.919203E+09 | 0.163478E+10 | 0.130897E+09 | 0.150388E+10 | 0.00 | 0.00 |
June | 0.478500E+10 | 0.374158E+09 | 0.183843E+10 | 0.334021E+09 | 0.150441E+10 | 0.00 | 0.00 |
July | 0.418775E+10 | 0.310466E+09 | 0.162010E+10 | 0.168780E+09 | 0.145132E+10 | 0.00 | 0.00 |
August | 0.344772E+10 | 0.406909E+09 | 0.130771E+10 | 32486236.32 | 0.127523E+10 | 0.00 | 0.00 |
September | 0.276546E+10 | 0.621902E+09 | 0.119400E+10 | 318738.06 | 0.119369E+10 | 0.00 | 0.00 |
October | 0.138170E+10 | 0.201890E+10 | 0.954568E+09 | 0.00 | 0.954568E+09 | 0.00 | 0.00 |
November | 0.577283E+09 | 0.284955E+10 | 0.769674E+09 | 0.00 | 0.769674E+09 | 0.00 | 0.00 |
December | 0.365265E+09 | 0.378439E+10 | 0.707026E+09 | 0.00 | 0.707026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.253304E+11 | 0.207490E+11 | 0.140599E+11 | 0.680527E+09 | 0.133794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365265E+09 | 0.310466E+09 | 0.707026E+09 | 0.00 | 0.707026E+09 | 0.00 | 0.00 |
Maximum of Months | 0.478500E+10 | 0.378439E+10 | 0.183843E+10 | 0.334021E+09 | 0.150441E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212755E+10 | 0.193116E+10 | 0.163015E+10 | 0.102263E+10 | 0.607514E+09 | 0.00 | 0.00 |
February | 0.169987E+10 | 0.169419E+10 | 0.145133E+10 | 0.830223E+09 | 0.621105E+09 | 0.00 | 0.00 |
March | 0.269630E+10 | 0.163735E+10 | 0.201087E+10 | 0.103440E+10 | 0.976467E+09 | 0.00 | 0.00 |
April | 0.463163E+10 | 0.896841E+09 | 0.277781E+10 | 0.165561E+10 | 0.112221E+10 | 0.00 | 0.00 |
May | 0.528859E+10 | 0.648175E+09 | 0.297478E+10 | 0.176341E+10 | 0.121136E+10 | 0.00 | 0.00 |
June | 0.609322E+10 | 0.261402E+09 | 0.300066E+10 | 0.186456E+10 | 0.113610E+10 | 0.00 | 0.00 |
July | 0.535169E+10 | 0.217928E+09 | 0.261872E+10 | 0.147659E+10 | 0.114214E+10 | 0.00 | 0.00 |
August | 0.503826E+10 | 0.285905E+09 | 0.248540E+10 | 0.141841E+10 | 0.106699E+10 | 0.00 | 0.00 |
September | 0.383867E+10 | 0.412927E+09 | 0.197365E+10 | 0.951330E+09 | 0.102232E+10 | 0.00 | 0.00 |
October | 0.320815E+10 | 0.129040E+10 | 0.204849E+10 | 0.124669E+10 | 0.801799E+09 | 0.00 | 0.00 |
November | 0.193991E+10 | 0.182321E+10 | 0.152436E+10 | 0.915092E+09 | 0.609271E+09 | 0.00 | 0.00 |
December | 0.162653E+10 | 0.240077E+10 | 0.143615E+10 | 0.867186E+09 | 0.568963E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.435404E+11 | 0.135003E+11 | 0.259324E+11 | 0.150461E+11 | 0.108862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.162653E+10 | 0.217928E+09 | 0.143615E+10 | 0.830223E+09 | 0.568963E+09 | 0.00 | 0.00 |
Maximum of Months | 0.609322E+10 | 0.240077E+10 | 0.300066E+10 | 0.186456E+10 | 0.121136E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.954867E+10 | 0.315225E+10 | 0.623235E+10 | 0.497759E+10 | 0.125476E+10 | 0.00 | 0.00 |
February | 0.498126E+10 | 0.259114E+10 | 0.355928E+10 | 0.240049E+10 | 0.115879E+10 | 0.00 | 0.00 |
March | 0.495294E+10 | 0.258398E+10 | 0.327890E+10 | 0.168880E+10 | 0.159010E+10 | 0.00 | 0.00 |
April | 0.515558E+10 | 0.144820E+10 | 0.270118E+10 | 0.109153E+10 | 0.160965E+10 | 0.00 | 0.00 |
May | 0.394152E+10 | 0.101515E+10 | 0.187042E+10 | 0.309010E+09 | 0.156141E+10 | 0.00 | 0.00 |
June | 0.426967E+10 | 0.395899E+09 | 0.154996E+10 | 0.119480E+09 | 0.143048E+10 | 0.00 | 0.00 |
July | 0.428032E+10 | 0.324679E+09 | 0.163657E+10 | 0.169315E+09 | 0.146726E+10 | 0.00 | 0.00 |
August | 0.492917E+10 | 0.437368E+09 | 0.198999E+10 | 0.549928E+09 | 0.144006E+10 | 0.00 | 0.00 |
September | 0.577447E+10 | 0.670921E+09 | 0.277487E+10 | 0.118382E+10 | 0.159105E+10 | 0.00 | 0.00 |
October | 0.763770E+10 | 0.204986E+10 | 0.456884E+10 | 0.316231E+10 | 0.140653E+10 | 0.00 | 0.00 |
November | 0.776660E+10 | 0.286234E+10 | 0.515266E+10 | 0.394666E+10 | 0.120600E+10 | 0.00 | 0.00 |
December | 0.846607E+10 | 0.376585E+10 | 0.579423E+10 | 0.458690E+10 | 0.120733E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.717040E+11 | 0.212976E+11 | 0.411092E+11 | 0.241858E+11 | 0.169234E+11 | 0.00 | 0.00 |
Minimum of Months | 0.394152E+10 | 0.324679E+09 | 0.154996E+10 | 0.119480E+09 | 0.115879E+10 | 0.00 | 0.00 |
Maximum of Months | 0.954867E+10 | 0.376585E+10 | 0.623235E+10 | 0.497759E+10 | 0.160965E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249312E+10 | 0.213142E+10 | 0.170462E+10 | 0.105944E+10 | 0.645174E+09 | 0.00 | 0.00 |
February | 0.150040E+10 | 0.178013E+10 | 0.124727E+10 | 0.602977E+09 | 0.644294E+09 | 0.00 | 0.00 |
March | 0.253783E+10 | 0.174247E+10 | 0.182905E+10 | 0.871936E+09 | 0.957118E+09 | 0.00 | 0.00 |
April | 0.465818E+10 | 0.101532E+10 | 0.271797E+10 | 0.155041E+10 | 0.116756E+10 | 0.00 | 0.00 |
May | 0.513503E+10 | 0.751626E+09 | 0.281578E+10 | 0.157881E+10 | 0.123698E+10 | 0.00 | 0.00 |
June | 0.596718E+10 | 0.319267E+09 | 0.289689E+10 | 0.170383E+10 | 0.119306E+10 | 0.00 | 0.00 |
July | 0.462332E+10 | 0.249810E+09 | 0.217871E+10 | 0.101701E+10 | 0.116170E+10 | 0.00 | 0.00 |
August | 0.437603E+10 | 0.316588E+09 | 0.207759E+10 | 0.104340E+10 | 0.103419E+10 | 0.00 | 0.00 |
September | 0.350305E+10 | 0.452236E+09 | 0.175254E+10 | 0.736345E+09 | 0.101620E+10 | 0.00 | 0.00 |
October | 0.301006E+10 | 0.140811E+10 | 0.185299E+10 | 0.105953E+10 | 0.793459E+09 | 0.00 | 0.00 |
November | 0.232506E+10 | 0.198127E+10 | 0.165160E+10 | 0.997184E+09 | 0.654414E+09 | 0.00 | 0.00 |
December | 0.178380E+10 | 0.259999E+10 | 0.137549E+10 | 0.783159E+09 | 0.592331E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.419131E+11 | 0.147482E+11 | 0.241005E+11 | 0.130040E+11 | 0.110965E+11 | 0.00 | 0.00 |
Minimum of Months | 0.150040E+10 | 0.249810E+09 | 0.124727E+10 | 0.602977E+09 | 0.592331E+09 | 0.00 | 0.00 |
Maximum of Months | 0.596718E+10 | 0.259999E+10 | 0.289689E+10 | 0.170383E+10 | 0.123698E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.616262E+09 | 0.305160E+10 | 0.756926E+09 | 0.00 | 0.756926E+09 | 0.00 | 0.00 |
February | 0.400235E+09 | 0.269466E+10 | 0.779031E+09 | 0.00 | 0.779031E+09 | 0.00 | 0.00 |
March | 0.109534E+10 | 0.265889E+10 | 0.114626E+10 | 0.00 | 0.114626E+10 | 0.00 | 0.00 |
April | 0.224913E+10 | 0.141295E+10 | 0.135150E+10 | 14025087.93 | 0.133747E+10 | 0.00 | 0.00 |
May | 0.317610E+10 | 0.981826E+09 | 0.163481E+10 | 0.130900E+09 | 0.150391E+10 | 0.00 | 0.00 |
June | 0.474673E+10 | 0.405879E+09 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
July | 0.418365E+10 | 0.317488E+09 | 0.162013E+10 | 0.168785E+09 | 0.145134E+10 | 0.00 | 0.00 |
August | 0.346285E+10 | 0.401077E+09 | 0.130774E+10 | 32487191.21 | 0.127525E+10 | 0.00 | 0.00 |
September | 0.279647E+10 | 0.592343E+09 | 0.119403E+10 | 318747.42 | 0.119371E+10 | 0.00 | 0.00 |
October | 0.140422E+10 | 0.194446E+10 | 0.954585E+09 | 0.00 | 0.954585E+09 | 0.00 | 0.00 |
November | 0.595038E+09 | 0.274465E+10 | 0.769689E+09 | 0.00 | 0.769689E+09 | 0.00 | 0.00 |
December | 0.379293E+09 | 0.369062E+10 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.251053E+11 | 0.208965E+11 | 0.140602E+11 | 0.680547E+09 | 0.133796E+11 | 0.00 | 0.00 |
Minimum of Months | 0.379293E+09 | 0.317488E+09 | 0.707039E+09 | 0.00 | 0.707039E+09 | 0.00 | 0.00 |
Maximum of Months | 0.474673E+10 | 0.369062E+10 | 0.183847E+10 | 0.334031E+09 | 0.150444E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.210210E+10 | 0.189977E+10 | 0.163017E+10 | 0.102265E+10 | 0.607520E+09 | 0.00 | 0.00 |
February | 0.166162E+10 | 0.170631E+10 | 0.145135E+10 | 0.830239E+09 | 0.621112E+09 | 0.00 | 0.00 |
March | 0.263299E+10 | 0.166792E+10 | 0.201090E+10 | 0.103442E+10 | 0.976479E+09 | 0.00 | 0.00 |
April | 0.458563E+10 | 0.899884E+09 | 0.277786E+10 | 0.165564E+10 | 0.112222E+10 | 0.00 | 0.00 |
May | 0.524167E+10 | 0.656880E+09 | 0.297482E+10 | 0.176345E+10 | 0.121137E+10 | 0.00 | 0.00 |
June | 0.606176E+10 | 0.264396E+09 | 0.300071E+10 | 0.186460E+10 | 0.113611E+10 | 0.00 | 0.00 |
July | 0.534339E+10 | 0.207055E+09 | 0.261876E+10 | 0.147661E+10 | 0.114215E+10 | 0.00 | 0.00 |
August | 0.503768E+10 | 0.261859E+09 | 0.248543E+10 | 0.141844E+10 | 0.106700E+10 | 0.00 | 0.00 |
September | 0.384700E+10 | 0.375570E+09 | 0.197368E+10 | 0.951348E+09 | 0.102233E+10 | 0.00 | 0.00 |
October | 0.320939E+10 | 0.121326E+10 | 0.204853E+10 | 0.124672E+10 | 0.801807E+09 | 0.00 | 0.00 |
November | 0.194330E+10 | 0.172534E+10 | 0.152439E+10 | 0.915110E+09 | 0.609278E+09 | 0.00 | 0.00 |
December | 0.163306E+10 | 0.229440E+10 | 0.143617E+10 | 0.867202E+09 | 0.568969E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.432996E+11 | 0.131726E+11 | 0.259328E+11 | 0.150464E+11 | 0.108863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.163306E+10 | 0.207055E+09 | 0.143617E+10 | 0.830239E+09 | 0.568969E+09 | 0.00 | 0.00 |
Maximum of Months | 0.606176E+10 | 0.229440E+10 | 0.300071E+10 | 0.186460E+10 | 0.121137E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.950464E+10 | 0.299382E+10 | 0.623260E+10 | 0.497780E+10 | 0.125480E+10 | 0.00 | 0.00 |
February | 0.488565E+10 | 0.260157E+10 | 0.355942E+10 | 0.240059E+10 | 0.115882E+10 | 0.00 | 0.00 |
March | 0.483728E+10 | 0.265195E+10 | 0.327902E+10 | 0.168887E+10 | 0.159015E+10 | 0.00 | 0.00 |
April | 0.510257E+10 | 0.148280E+10 | 0.270126E+10 | 0.109157E+10 | 0.160969E+10 | 0.00 | 0.00 |
May | 0.389409E+10 | 0.107433E+10 | 0.187047E+10 | 0.309023E+09 | 0.156144E+10 | 0.00 | 0.00 |
June | 0.427277E+10 | 0.424819E+09 | 0.154999E+10 | 0.119485E+09 | 0.143051E+10 | 0.00 | 0.00 |
July | 0.431079E+10 | 0.323199E+09 | 0.163662E+10 | 0.169322E+09 | 0.146730E+10 | 0.00 | 0.00 |
August | 0.498928E+10 | 0.405948E+09 | 0.199005E+10 | 0.549951E+09 | 0.144010E+10 | 0.00 | 0.00 |
September | 0.583975E+10 | 0.598648E+09 | 0.277497E+10 | 0.118387E+10 | 0.159110E+10 | 0.00 | 0.00 |
October | 0.765264E+10 | 0.190416E+10 | 0.456901E+10 | 0.316244E+10 | 0.140657E+10 | 0.00 | 0.00 |
November | 0.775169E+10 | 0.266992E+10 | 0.515286E+10 | 0.394683E+10 | 0.120603E+10 | 0.00 | 0.00 |
December | 0.843481E+10 | 0.355329E+10 | 0.579446E+10 | 0.458709E+10 | 0.120737E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.714760E+11 | 0.206844E+11 | 0.411107E+11 | 0.241868E+11 | 0.169239E+11 | 0.00 | 0.00 |
Minimum of Months | 0.389409E+10 | 0.323199E+09 | 0.154999E+10 | 0.119485E+09 | 0.115882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.950464E+10 | 0.355329E+10 | 0.623260E+10 | 0.497780E+10 | 0.160969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247755E+10 | 0.209043E+10 | 0.170464E+10 | 0.105946E+10 | 0.645179E+09 | 0.00 | 0.00 |
February | 0.146827E+10 | 0.180088E+10 | 0.124729E+10 | 0.602987E+09 | 0.644300E+09 | 0.00 | 0.00 |
March | 0.248263E+10 | 0.177991E+10 | 0.182908E+10 | 0.871951E+09 | 0.957127E+09 | 0.00 | 0.00 |
April | 0.462229E+10 | 0.101556E+10 | 0.271801E+10 | 0.155043E+10 | 0.116757E+10 | 0.00 | 0.00 |
May | 0.510050E+10 | 0.757262E+09 | 0.281582E+10 | 0.157883E+10 | 0.123698E+10 | 0.00 | 0.00 |
June | 0.594916E+10 | 0.319507E+09 | 0.289693E+10 | 0.170386E+10 | 0.119307E+10 | 0.00 | 0.00 |
July | 0.462606E+10 | 0.239792E+09 | 0.217873E+10 | 0.101702E+10 | 0.116171E+10 | 0.00 | 0.00 |
August | 0.438922E+10 | 0.294765E+09 | 0.207762E+10 | 0.104342E+10 | 0.103420E+10 | 0.00 | 0.00 |
September | 0.352150E+10 | 0.414105E+09 | 0.175257E+10 | 0.736358E+09 | 0.101621E+10 | 0.00 | 0.00 |
October | 0.301999E+10 | 0.132573E+10 | 0.185302E+10 | 0.105955E+10 | 0.793465E+09 | 0.00 | 0.00 |
November | 0.233227E+10 | 0.186720E+10 | 0.165162E+10 | 0.997200E+09 | 0.654420E+09 | 0.00 | 0.00 |
December | 0.179121E+10 | 0.248561E+10 | 0.137551E+10 | 0.783172E+09 | 0.592336E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.417807E+11 | 0.143907E+11 | 0.241008E+11 | 0.130043E+11 | 0.110966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146827E+10 | 0.239792E+09 | 0.124729E+10 | 0.602987E+09 | 0.592336E+09 | 0.00 | 0.00 |
Maximum of Months | 0.594916E+10 | 0.248561E+10 | 0.289693E+10 | 0.170386E+10 | 0.123698E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.450847E+10 | -0.380900E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -699465130.3 | 58.98 | 0.00 | 0.00 |
February | 0.406118E+10 | -0.342746E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -633716810.8 | 58.98 | 0.00 | 0.00 |
March | 0.455532E+10 | -0.385820E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -697125728.5 | 58.98 | 0.00 | 0.00 |
April | 0.386590E+10 | -0.319595E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669955184.6 | 58.98 | 0.00 | 0.00 |
May | 0.380131E+10 | -0.311019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691120516.8 | 58.98 | 0.00 | 0.00 |
June | 0.349334E+10 | -0.282445E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668891601.9 | 58.98 | 0.00 | 0.00 |
July | 0.323035E+10 | -0.254006E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690291468.4 | 58.98 | 0.00 | 0.00 |
August | 0.354281E+10 | -0.285165E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691159475.2 | 58.98 | 0.00 | 0.00 |
September | 0.342020E+10 | -0.275372E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666476287.6 | 58.98 | 0.00 | 0.00 |
October | 0.382151E+10 | -0.313106E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690454883.4 | 58.98 | 0.00 | 0.00 |
November | 0.405303E+10 | -0.338156E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671474875.4 | 58.98 | 0.00 | 0.00 |
December | 0.428653E+10 | -0.358637E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -700160652.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.466400E+11 | -0.384697E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.817029E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.323035E+10 | -0.385820E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -700160652.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.455532E+10 | -0.254006E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -633716810.8 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9182.04 | 38.84 | 306.33 | 291.50 | 2427.03 | 28.40 | 169.50 | 288.00 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8250.77 | 36.26 | 234.17 | 264.83 | 1334.24 | 22.66 | 120.33 | 222.67 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1568.35 | 17.87 | 2.33 | 327.67 | 931.86 | 20.08 | 120.83 | 286.83 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:49 | 1202.35 | 17.59 | 0.00 | 331.50 | 765.58 | 19.76 | 61.67 | 301.67 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:19 | 945.51 | 17.35 | 0.00 | 356.50 | 600.34 | 19.59 | 13.50 | 315.00 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-06:00 | 781.80 | 16.60 | 0.00 | 361.17 | 509.73 | 18.89 | 0.83 | 308.33 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:19 | 910.72 | 17.01 | 0.00 | 360.67 | 554.79 | 19.25 | 18.17 | 291.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 1050.17 | 17.36 | 0.00 | 335.50 | 647.12 | 19.56 | 33.17 | 286.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 1515.99 | 18.31 | 11.00 | 318.17 | 862.89 | 20.06 | 102.83 | 285.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3166.43 | 23.97 | 140.17 | 318.00 | 1150.91 | 20.00 | 86.83 | 300.17 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8686.22 | 37.47 | 282.00 | 285.17 | 1664.03 | 25.01 | 132.33 | 267.33 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8483.73 | 38.32 | 284.17 | 279.67 | 2263.84 | 28.07 | 164.33 | 274.50 |
Annual Sum or Average | 4135.50 | 0.51 | 3358.07 | 23.54 | 1260.17 | 3830.33 | 1072.98 | 21.43 | 1024.33 | 3428.17 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 781.80 | 16.60 | 0.00 | 264.83 | 509.73 | 18.89 | 0.83 | 222.67 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9182.04 | 38.84 | 306.33 | 361.17 | 2427.03 | 28.40 | 169.50 | 315.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.52 | 0.48 | 01-JAN-07:49 | 2068.02 | 20.46 | 87.17 | 266.33 | 1192.61 | 23.02 | 77.17 | 221.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2606.48 | 23.03 | 85.83 | 253.33 | 1457.01 | 23.45 | 63.00 | 183.50 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2130.83 | 19.72 | 86.17 | 312.00 | 1154.39 | 21.89 | 69.67 | 276.83 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3049.97 | 21.29 | 112.33 | 345.33 | 1717.43 | 22.20 | 82.33 | 320.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3410.84 | 21.05 | 118.50 | 377.00 | 1387.99 | 21.67 | 72.33 | 350.83 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3479.78 | 21.75 | 134.33 | 385.67 | 1371.67 | 21.12 | 74.83 | 346.17 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 2994.99 | 20.64 | 115.33 | 379.00 | 1237.24 | 21.11 | 68.33 | 318.33 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2965.63 | 21.55 | 114.50 | 350.17 | 1648.48 | 22.36 | 83.50 | 304.83 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2333.22 | 21.08 | 102.00 | 316.00 | 1259.56 | 22.15 | 75.17 | 274.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2206.61 | 19.42 | 87.83 | 288.33 | 1229.53 | 21.57 | 72.33 | 249.50 |
November | 288.50 | 0.51 | 0.48 | 01-NOV-07:30 | 1837.63 | 20.90 | 80.17 | 267.00 | 974.45 | 21.51 | 52.83 | 201.33 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:30 | 2131.32 | 22.82 | 101.67 | 253.67 | 1191.24 | 23.52 | 77.17 | 199.83 |
Annual Sum or Average | 4135.50 | 0.51 | 2659.18 | 21.09 | 1225.83 | 3793.83 | 1327.91 | 22.04 | 868.67 | 3247.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1837.63 | 19.42 | 80.17 | 253.33 | 974.45 | 21.11 | 52.83 | 183.50 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3479.78 | 23.03 | 134.33 | 385.67 | 1717.43 | 23.52 | 83.50 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-09:39 | 449.38 | 13.83 | 0.00 | 219.67 | 312.15 | 16.57 | 0.00 | 118.00 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:00 | 554.59 | 14.85 | 0.00 | 221.83 | 358.84 | 17.27 | 0.00 | 125.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 636.27 | 16.14 | 0.00 | 298.33 | 399.41 | 18.35 | 0.00 | 224.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 749.09 | 17.41 | 0.00 | 335.17 | 494.78 | 19.58 | 5.33 | 302.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 886.38 | 18.16 | 2.67 | 388.50 | 585.62 | 20.38 | 52.00 | 373.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1032.49 | 21.16 | 81.50 | 399.17 | 635.03 | 23.29 | 124.17 | 395.00 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:49 | 914.17 | 20.47 | 62.50 | 394.00 | 584.08 | 22.58 | 108.33 | 359.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-07:10 | 759.84 | 17.45 | 0.00 | 347.17 | 484.90 | 19.63 | 7.33 | 293.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 723.88 | 16.74 | 0.00 | 313.33 | 445.61 | 18.88 | 1.00 | 253.17 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-07:49 | 519.38 | 14.77 | 0.00 | 255.83 | 348.49 | 17.21 | 0.00 | 172.00 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:20 | 488.72 | 14.54 | 0.00 | 230.00 | 326.82 | 17.18 | 0.00 | 120.00 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-08:00 | 453.34 | 13.99 | 0.00 | 205.17 | 307.22 | 16.74 | 0.00 | 94.00 |
Annual Sum or Average | 4135.50 | 0.52 | 704.42 | 16.92 | 146.67 | 3608.17 | 454.66 | 19.24 | 298.17 | 2830.67 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 449.38 | 13.83 | 0.00 | 205.17 | 307.22 | 16.57 | 0.00 | 94.00 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 1032.49 | 21.16 | 81.50 | 399.17 | 635.03 | 23.29 | 124.17 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:39 | 2321.64 | 21.96 | 105.67 | 243.33 | 1302.70 | 22.36 | 76.33 | 204.83 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-09:00 | 2348.93 | 21.19 | 81.17 | 234.50 | 919.77 | 20.09 | 36.50 | 173.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-08:20 | 1936.79 | 19.04 | 79.00 | 310.00 | 1083.28 | 21.52 | 65.33 | 272.33 |
April | 380.33 | 0.51 | 0.48 | 01-APR-08:09 | 2840.61 | 18.93 | 85.00 | 332.33 | 1585.90 | 20.25 | 55.00 | 304.00 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:30 | 3052.44 | 16.65 | 54.50 | 361.17 | 1688.78 | 17.19 | 0.00 | 330.17 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:10 | 3069.80 | 12.96 | 0.00 | 367.67 | 1255.20 | 16.77 | 0.00 | 338.17 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:30 | 2293.01 | 13.85 | 3.67 | 367.67 | 1041.38 | 17.21 | 0.00 | 318.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2370.25 | 16.48 | 49.17 | 340.33 | 1304.97 | 17.33 | 5.00 | 292.67 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:19 | 1864.32 | 19.16 | 81.83 | 315.67 | 1023.49 | 20.37 | 53.83 | 278.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2296.65 | 21.03 | 109.33 | 282.83 | 1264.01 | 21.98 | 81.17 | 247.50 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:30 | 2094.57 | 20.23 | 80.83 | 248.33 | 1171.74 | 21.96 | 62.50 | 203.50 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-08:00 | 1769.71 | 20.15 | 80.67 | 233.33 | 940.92 | 20.84 | 53.17 | 192.67 |
Annual Sum or Average | 4135.50 | 0.52 | 2391.84 | 18.14 | 810.83 | 3637.17 | 1234.49 | 19.62 | 488.83 | 3156.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1769.71 | 12.96 | 0.00 | 233.33 | 919.77 | 16.77 | 0.00 | 173.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3069.80 | 21.96 | 109.33 | 367.67 | 1688.78 | 22.36 | 81.17 | 338.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9023.50 | 38.63 | 306.33 | 291.00 | 2290.31 | 26.30 | 145.50 | 286.50 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8125.05 | 36.02 | 234.17 | 264.17 | 1234.44 | 20.01 | 40.67 | 219.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1484.99 | 14.04 | 2.33 | 326.17 | 869.00 | 17.65 | 1.83 | 283.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:49 | 1144.95 | 14.15 | 0.00 | 328.67 | 724.90 | 17.75 | 0.00 | 298.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:19 | 909.85 | 13.97 | 0.00 | 354.00 | 578.89 | 17.57 | 0.00 | 311.83 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:10 | 755.53 | 13.23 | 0.00 | 357.33 | 495.44 | 16.88 | 0.00 | 301.83 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:30 | 877.20 | 13.51 | 0.00 | 357.67 | 535.05 | 17.09 | 0.00 | 286.50 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1005.51 | 13.82 | 0.00 | 333.17 | 617.54 | 17.42 | 0.00 | 281.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 1443.60 | 14.67 | 10.83 | 316.17 | 810.64 | 17.67 | 0.00 | 282.33 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3058.18 | 21.29 | 139.83 | 316.33 | 1062.50 | 17.39 | 13.17 | 297.33 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8543.42 | 37.19 | 281.83 | 284.50 | 1544.46 | 22.51 | 89.17 | 266.17 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8312.85 | 37.81 | 282.17 | 279.17 | 2127.04 | 25.85 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.51 | 3276.15 | 20.96 | 1257.50 | 3808.33 | 1010.10 | 19.18 | 421.00 | 3388.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 755.53 | 13.23 | 0.00 | 264.17 | 495.44 | 16.88 | 0.00 | 219.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9023.50 | 38.63 | 306.33 | 357.67 | 2290.31 | 26.30 | 145.50 | 311.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.52 | 0.48 | 01-JAN-07:00 | 2014.93 | 19.97 | 87.17 | 262.83 | 1147.70 | 22.81 | 75.17 | 217.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2544.50 | 22.58 | 85.83 | 251.50 | 1407.54 | 23.26 | 63.00 | 178.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:19 | 2069.98 | 19.23 | 86.17 | 308.83 | 1101.52 | 21.70 | 69.83 | 273.00 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 2971.51 | 20.84 | 112.33 | 344.33 | 1656.42 | 22.03 | 82.33 | 317.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3326.02 | 20.52 | 117.83 | 376.17 | 1324.02 | 21.51 | 72.33 | 347.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3335.28 | 19.69 | 115.00 | 384.33 | 1310.56 | 20.96 | 74.83 | 340.83 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 2924.80 | 20.18 | 115.33 | 376.33 | 1179.42 | 20.96 | 68.33 | 313.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2887.64 | 21.09 | 114.50 | 347.83 | 1590.55 | 22.19 | 83.50 | 300.00 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2273.16 | 20.62 | 102.00 | 314.00 | 1210.00 | 21.97 | 75.17 | 271.00 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2145.25 | 18.93 | 87.83 | 284.83 | 1178.68 | 21.38 | 72.17 | 247.83 |
November | 288.50 | 0.51 | 0.48 | 01-NOV-07:30 | 1756.86 | 19.91 | 76.33 | 261.83 | 932.90 | 21.29 | 52.83 | 197.17 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:40 | 1987.52 | 20.37 | 85.33 | 247.67 | 1150.25 | 23.30 | 74.33 | 196.67 |
Annual Sum or Average | 4135.50 | 0.51 | 2576.83 | 20.28 | 1185.67 | 3760.50 | 1274.33 | 21.86 | 863.83 | 3201.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1756.86 | 18.93 | 76.33 | 247.67 | 932.90 | 20.96 | 52.83 | 178.67 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3335.28 | 22.58 | 117.83 | 384.33 | 1656.42 | 23.30 | 83.50 | 347.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-09:50 | 433.21 | 10.36 | 0.00 | 211.67 | 304.37 | 14.29 | 0.00 | 109.17 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-10:09 | 535.62 | 11.41 | 0.00 | 218.67 | 349.19 | 15.10 | 0.00 | 119.67 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:09 | 614.82 | 12.77 | 0.00 | 295.50 | 388.19 | 16.35 | 0.00 | 217.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 724.20 | 14.28 | 0.00 | 333.67 | 482.43 | 17.91 | 0.00 | 298.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 856.46 | 14.77 | 2.67 | 386.17 | 569.48 | 18.47 | 4.00 | 370.83 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1000.39 | 18.27 | 81.33 | 398.83 | 616.37 | 21.53 | 82.33 | 394.33 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:00 | 881.75 | 17.45 | 62.50 | 393.00 | 565.56 | 20.73 | 62.83 | 355.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 734.42 | 14.05 | 0.00 | 344.17 | 471.74 | 17.72 | 0.00 | 286.17 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 698.83 | 13.39 | 0.00 | 310.17 | 432.23 | 16.89 | 0.00 | 246.83 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-07:49 | 502.21 | 11.39 | 0.00 | 250.33 | 340.10 | 15.16 | 0.00 | 165.50 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:30 | 471.59 | 10.96 | 0.00 | 222.00 | 318.33 | 14.89 | 0.00 | 110.33 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:09 | 436.77 | 10.39 | 0.00 | 199.00 | 299.04 | 14.36 | 0.00 | 85.33 |
Annual Sum or Average | 4135.50 | 0.52 | 680.58 | 13.61 | 146.50 | 3563.17 | 442.04 | 17.24 | 149.17 | 2760.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 433.21 | 10.36 | 0.00 | 199.00 | 299.04 | 14.29 | 0.00 | 85.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 1000.39 | 18.27 | 81.33 | 398.83 | 616.37 | 21.53 | 82.33 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-09:39 | 2144.52 | 19.49 | 86.50 | 238.83 | 1255.14 | 22.25 | 76.00 | 201.33 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-09:00 | 2291.87 | 20.80 | 81.17 | 232.50 | 877.40 | 19.96 | 36.67 | 171.33 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-08:30 | 1880.27 | 18.59 | 79.00 | 308.17 | 1036.31 | 21.39 | 65.33 | 269.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-08:20 | 2761.19 | 18.46 | 85.00 | 329.83 | 1523.46 | 20.08 | 55.00 | 301.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:30 | 2970.65 | 16.15 | 54.50 | 359.50 | 1628.73 | 17.01 | 0.00 | 327.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:19 | 2999.49 | 12.42 | 0.00 | 364.83 | 1195.28 | 16.59 | 0.00 | 335.67 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:30 | 2232.72 | 13.30 | 3.67 | 364.83 | 995.23 | 17.01 | 0.00 | 314.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:49 | 2302.79 | 15.96 | 49.17 | 337.33 | 1257.23 | 17.14 | 5.00 | 289.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1810.84 | 18.72 | 81.83 | 312.83 | 979.88 | 20.23 | 53.83 | 274.83 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-07:00 | 2240.66 | 20.62 | 109.33 | 280.67 | 1218.38 | 21.86 | 81.17 | 245.67 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:30 | 2032.91 | 19.80 | 80.83 | 245.17 | 1122.10 | 21.85 | 62.17 | 201.00 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-08:00 | 1718.29 | 19.75 | 80.67 | 230.83 | 889.14 | 20.50 | 50.50 | 189.50 |
Annual Sum or Average | 4135.50 | 0.52 | 2319.27 | 17.52 | 791.67 | 3605.33 | 1183.62 | 19.45 | 485.67 | 3122.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1718.29 | 12.42 | 0.00 | 230.83 | 877.40 | 16.59 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 2999.49 | 20.80 | 109.33 | 364.83 | 1628.73 | 22.25 | 81.17 | 335.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9023.49 | 38.63 | 306.33 | 291.00 | 2290.25 | 26.30 | 145.50 | 286.50 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8124.99 | 36.02 | 234.17 | 264.17 | 1234.37 | 20.02 | 40.67 | 219.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1484.91 | 14.04 | 2.33 | 326.17 | 868.94 | 17.65 | 1.83 | 283.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:49 | 1144.91 | 14.16 | 0.00 | 328.67 | 724.86 | 17.75 | 0.00 | 298.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:19 | 909.82 | 13.97 | 0.00 | 354.00 | 578.86 | 17.57 | 0.00 | 311.83 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:10 | 755.51 | 13.23 | 0.00 | 357.33 | 495.42 | 16.88 | 0.00 | 301.83 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:30 | 877.16 | 13.51 | 0.00 | 357.67 | 535.02 | 17.09 | 0.00 | 286.50 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1005.47 | 13.82 | 0.00 | 333.17 | 617.51 | 17.42 | 0.00 | 281.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 1443.52 | 14.67 | 10.83 | 316.17 | 810.58 | 17.67 | 0.00 | 282.33 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3058.12 | 21.29 | 139.83 | 316.33 | 1062.45 | 17.39 | 13.17 | 297.33 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8543.39 | 37.19 | 281.83 | 284.50 | 1544.40 | 22.51 | 89.17 | 266.17 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8312.85 | 37.81 | 282.17 | 279.17 | 2126.97 | 25.85 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.51 | 3276.11 | 20.96 | 1257.50 | 3808.33 | 1010.05 | 19.18 | 421.00 | 3388.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 755.51 | 13.23 | 0.00 | 264.17 | 495.42 | 16.88 | 0.00 | 219.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9023.49 | 38.63 | 306.33 | 357.67 | 2290.25 | 26.30 | 145.50 | 311.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.52 | 0.48 | 01-JAN-07:00 | 2014.93 | 19.98 | 87.17 | 262.83 | 1147.68 | 22.81 | 75.17 | 217.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2544.48 | 22.58 | 85.83 | 251.50 | 1407.50 | 23.26 | 63.00 | 178.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:19 | 2069.95 | 19.23 | 86.17 | 308.83 | 1101.48 | 21.70 | 69.83 | 272.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 2971.50 | 20.84 | 112.33 | 344.33 | 1656.37 | 22.03 | 82.33 | 317.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3326.00 | 20.53 | 117.83 | 376.17 | 1323.98 | 21.51 | 72.33 | 347.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3335.27 | 19.70 | 115.00 | 384.33 | 1310.53 | 20.97 | 74.83 | 340.83 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 2924.77 | 20.18 | 115.33 | 376.33 | 1179.38 | 20.96 | 68.33 | 313.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2887.62 | 21.10 | 114.50 | 347.83 | 1590.50 | 22.20 | 83.50 | 300.00 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2273.12 | 20.62 | 102.00 | 314.00 | 1209.95 | 21.97 | 75.17 | 271.00 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2145.23 | 18.93 | 87.83 | 284.83 | 1178.65 | 21.38 | 72.17 | 247.83 |
November | 288.50 | 0.51 | 0.48 | 01-NOV-07:30 | 1756.85 | 19.91 | 76.33 | 261.83 | 932.87 | 21.30 | 52.83 | 197.17 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:40 | 1987.52 | 20.37 | 85.33 | 247.67 | 1150.22 | 23.30 | 74.33 | 196.67 |
Annual Sum or Average | 4135.50 | 0.51 | 2576.81 | 20.28 | 1185.67 | 3760.50 | 1274.29 | 21.86 | 863.83 | 3201.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1756.85 | 18.93 | 76.33 | 247.67 | 932.87 | 20.96 | 52.83 | 178.67 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3335.27 | 22.58 | 117.83 | 384.33 | 1656.37 | 23.30 | 83.50 | 347.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-09:50 | 433.21 | 10.37 | 0.00 | 211.67 | 304.36 | 14.30 | 0.00 | 109.17 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-10:09 | 535.61 | 11.41 | 0.00 | 218.67 | 349.17 | 15.10 | 0.00 | 119.67 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:09 | 614.80 | 12.77 | 0.00 | 295.50 | 388.17 | 16.35 | 0.00 | 217.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 724.19 | 14.28 | 0.00 | 333.67 | 482.40 | 17.91 | 0.00 | 298.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 856.45 | 14.77 | 2.67 | 386.17 | 569.45 | 18.47 | 4.17 | 370.83 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1000.38 | 18.27 | 81.33 | 398.83 | 616.34 | 21.53 | 82.33 | 394.33 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:00 | 881.73 | 17.46 | 62.50 | 393.00 | 565.53 | 20.73 | 62.83 | 355.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 734.41 | 14.05 | 0.00 | 344.17 | 471.72 | 17.72 | 0.00 | 286.17 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 698.81 | 13.39 | 0.00 | 310.17 | 432.20 | 16.89 | 0.00 | 246.83 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-07:49 | 502.21 | 11.39 | 0.00 | 250.33 | 340.09 | 15.16 | 0.00 | 165.50 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:30 | 471.59 | 10.96 | 0.00 | 222.00 | 318.32 | 14.89 | 0.00 | 110.33 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:09 | 436.77 | 10.39 | 0.00 | 199.00 | 299.02 | 14.36 | 0.00 | 85.33 |
Annual Sum or Average | 4135.50 | 0.52 | 680.57 | 13.61 | 146.50 | 3563.17 | 442.02 | 17.24 | 149.33 | 2760.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 433.21 | 10.37 | 0.00 | 199.00 | 299.02 | 14.30 | 0.00 | 85.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 1000.38 | 18.27 | 81.33 | 398.83 | 616.34 | 21.53 | 82.33 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-09:39 | 2144.52 | 19.49 | 86.50 | 238.83 | 1255.11 | 22.25 | 76.00 | 201.33 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-09:00 | 2291.85 | 20.80 | 81.17 | 232.50 | 877.36 | 19.97 | 36.67 | 171.33 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-08:30 | 1880.24 | 18.59 | 79.00 | 308.17 | 1036.27 | 21.39 | 65.33 | 269.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-08:20 | 2761.17 | 18.46 | 85.00 | 329.83 | 1523.41 | 20.08 | 55.00 | 301.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:30 | 2970.63 | 16.15 | 54.50 | 359.50 | 1628.68 | 17.01 | 0.00 | 327.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:19 | 2999.48 | 12.43 | 0.00 | 364.83 | 1195.24 | 16.59 | 0.00 | 335.67 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:30 | 2232.69 | 13.30 | 3.67 | 364.83 | 995.19 | 17.01 | 0.00 | 314.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:49 | 2302.77 | 15.96 | 49.17 | 337.33 | 1257.19 | 17.15 | 5.00 | 289.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1810.80 | 18.72 | 81.83 | 312.83 | 979.83 | 20.23 | 53.83 | 274.83 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-07:00 | 2240.65 | 20.62 | 109.33 | 280.67 | 1218.35 | 21.86 | 81.17 | 245.67 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:30 | 2032.90 | 19.80 | 80.83 | 245.17 | 1122.07 | 21.85 | 62.17 | 201.00 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-08:00 | 1718.28 | 19.75 | 80.67 | 230.83 | 889.11 | 20.50 | 50.50 | 189.50 |
Annual Sum or Average | 4135.50 | 0.52 | 2319.25 | 17.52 | 791.67 | 3605.33 | 1183.58 | 19.46 | 485.67 | 3122.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1718.28 | 12.43 | 0.00 | 230.83 | 877.36 | 16.59 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 2999.48 | 20.80 | 109.33 | 364.83 | 1628.68 | 22.25 | 81.17 | 335.67 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.633501E+09 | 8589.40 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690413E+09 | 8589.40 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.778155E+09 | 8589.40 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134674E+09 | 8589.40 | 07-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6760015.67 | 6673.06 | 01-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262343E+09 | 8589.40 | 12-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.361768E+09 | 8589.40 | 06-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747576E+09 | 8589.40 | 01-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.778155E+09 | 8589.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8871529.16 | 5691.32 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3475731.01 | 5691.32 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2687207.64 | 5691.32 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4709676.42 | 5691.32 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19744144.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8871529.16 | 5691.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 51919650.61 | 8529.89 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33424290.29 | 8529.89 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28555315.90 | 8529.89 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12811.34 | 149.47 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45365254.36 | 8529.89 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51919650.61 | 8529.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10392308.58 | 5651.94 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9679962.96 | 5651.94 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2967377.26 | 5651.94 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12295037.51 | 5651.94 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35334686.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12295037.51 | 5651.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10628253.44 | 19312.19 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10628253.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10628253.44 | 19312.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17885086.03 | 10127.45 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9071189.92 | 10127.45 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9099462.06 | 10127.45 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 497255.22 | 5801.31 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50945357.72 | 10127.45 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87498350.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50945357.72 | 10127.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17808221.29 | 6690.26 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8010175.91 | 6690.26 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6763199.61 | 6690.26 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1026494.48 | 6690.26 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48948849.48 | 6690.26 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 82556940.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48948849.48 | 6690.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 50112122.07 | 10022.21 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27249400.15 | 10070.78 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16918896.18 | 9989.75 | 28-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6663675.91 | 9958.47 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138507E+09 | 10081.93 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138507E+09 | 10081.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 23624982.54 | 6651.57 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14861561.24 | 6651.57 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7582333.75 | 6651.57 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2859878.80 | 6651.57 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78893460.72 | 6651.57 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78893460.72 | 6651.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101204E+09 | 29786.55 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26278218.85 | 29786.55 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8272280.76 | 29786.55 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5892956.99 | 23825.21 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162440E+09 | 29786.55 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162440E+09 | 29786.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 99325535.88 | 13105.14 | 12-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119771E+09 | 13148.67 | 14-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98478476.85 | 13045.59 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10189107.74 | 9029.73 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42024932.32 | 12929.35 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312053E+09 | 13153.45 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.312053E+09 | 13153.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 87727657.05 | 8604.03 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83906544.62 | 8604.03 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51839012.56 | 8604.03 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9111392.25 | 7809.44 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34892779.21 | 8604.03 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266292E+09 | 8604.03 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.266292E+09 | 8604.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237924E+09 | 11889.50 | 11-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215333E+09 | 11888.29 | 14-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139970E+09 | 11880.58 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22813665.91 | 11806.12 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127433E+09 | 11808.02 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.698979E+09 | 12384.06 | 14-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.698979E+09 | 12384.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128047E+09 | 8566.74 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124356E+09 | 8566.74 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80137569.06 | 8566.74 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11823592.50 | 7225.20 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70409368.47 | 8566.74 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393532E+09 | 8566.74 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.808305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393532E+09 | 8566.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100013E+09 | 5178.09 | 02-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170968E+09 | 4456.41 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201285E+09 | 7868.38 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38387.77 | 255.92 | 21-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11957731.92 | 4202.35 | 25-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53661213.43 | 5119.89 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.738689E+09 | 8611.15 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.738689E+09 | 8611.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188611E+09 | 5409.54 | 02-JAN-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275426E+09 | 4796.55 | 01-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279870E+09 | 7839.13 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1663448.98 | 1094.64 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 63174888.02 | 4673.12 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124377E+09 | 5728.67 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943967E+09 | 9694.12 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.943967E+09 | 9694.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304761E+09 | 6864.03 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418478E+09 | 6324.97 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394345E+09 | 9068.85 | 27-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5334793.97 | 2165.44 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118357E+09 | 5960.92 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213089E+09 | 7331.68 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121478E+10 | 9068.85 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121478E+10 | 9068.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152249E+11 | 0.150748E+11 | 43339.09 | 31-JAN-16:30 | 43339.09 | 0.00 |
February | 0.00 | 0.00 | 0.377334E+10 | 0.330979E+10 | 20650.37 | 01-FEB-16:10 | 20650.37 | 0.00 |
March | 0.00 | 0.00 | 0.145292E+11 | 0.140945E+11 | 41602.41 | 20-MAR-14:30 | 41602.41 | 0.00 |
April | 0.00 | 0.00 | 0.417158E+11 | 0.416265E+11 | 59886.03 | 14-APR-16:00 | 59886.03 | 0.00 |
May | 0.00 | 0.00 | 0.558647E+11 | 0.558147E+11 | 63910.07 | 31-MAY-16:00 | 63910.07 | 0.00 |
June | 0.00 | 0.00 | 0.759846E+11 | 0.757001E+11 | 80568.03 | 27-JUN-06:03 | 80568.03 | 0.00 |
July | 0.00 | 0.00 | 0.783522E+11 | 0.724430E+11 | 111942.57 | 14-JUL-05:03 | 46470.85 | 0.00 |
August | 0.00 | 0.00 | 0.813959E+11 | 0.748954E+11 | 108658.86 | 01-AUG-04:03 | 57058.92 | 0.00 |
September | 0.00 | 0.00 | 0.705851E+11 | 0.641324E+11 | 108478.77 | 05-SEP-07:20 | 47140.40 | 0.00 |
October | 0.00 | 0.00 | 0.397356E+11 | 0.385116E+11 | 103787.01 | 03-OCT-06:03 | 54909.02 | 0.00 |
November | 0.00 | 0.00 | 0.173770E+11 | 0.163747E+11 | 50062.18 | 01-NOV-16:00 | 50062.18 | 0.00 |
December | 0.00 | 0.00 | 0.752345E+10 | 0.747413E+10 | 37422.69 | 22-DEC-16:30 | 37422.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.502062E+12 | 0.479452E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.377334E+10 | 0.330979E+10 | 20650.37 | 20650.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.813959E+11 | 0.757001E+11 | 111942.57 | 80568.03 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.134249E+11 | 0.132667E+11 | 39578.00 | 31-JAN-16:30 | 39578.00 | 0.00 |
February | 0.00 | 0.00 | 0.297552E+10 | 0.252540E+10 | 19368.06 | 22-FEB-16:00 | 19368.06 | 0.00 |
March | 0.00 | 0.00 | 0.133715E+11 | 0.129078E+11 | 42199.75 | 16-MAR-15:30 | 42199.75 | 0.00 |
April | 0.00 | 0.00 | 0.401936E+11 | 0.401026E+11 | 60103.33 | 24-APR-15:50 | 60103.33 | 0.00 |
May | 0.00 | 0.00 | 0.539876E+11 | 0.539404E+11 | 61354.76 | 08-MAY-16:00 | 61354.76 | 0.00 |
June | 0.00 | 0.00 | 0.735057E+11 | 0.732915E+11 | 75532.34 | 29-JUN-06:03 | 75532.34 | 0.00 |
July | 0.00 | 0.00 | 0.713951E+11 | 0.668281E+11 | 107147.73 | 14-JUL-05:03 | 43194.16 | 0.00 |
August | 0.00 | 0.00 | 0.720601E+11 | 0.673163E+11 | 104004.67 | 01-AUG-04:03 | 53021.62 | 0.00 |
September | 0.00 | 0.00 | 0.602512E+11 | 0.553386E+11 | 103946.17 | 02-SEP-05:03 | 58432.28 | 0.00 |
October | 0.00 | 0.00 | 0.333409E+11 | 0.322710E+11 | 87216.23 | 03-OCT-06:03 | 45417.75 | 0.00 |
November | 0.00 | 0.00 | 0.141372E+11 | 0.132249E+11 | 46417.44 | 01-NOV-15:30 | 46417.44 | 0.00 |
December | 0.00 | 0.00 | 0.601491E+10 | 0.595351E+10 | 32596.88 | 22-DEC-15:05 | 32596.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.454658E+12 | 0.436967E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.297552E+10 | 0.252540E+10 | 19368.06 | 19368.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.735057E+11 | 0.732915E+11 | 107147.73 | 75532.34 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.130812E+11 | 0.128355E+11 | 43536.99 | 31-JAN-16:10 | 43536.99 | 0.00 |
February | 0.00 | 0.00 | 0.298955E+10 | 0.244829E+10 | 19693.04 | 22-FEB-16:00 | 19693.04 | 0.00 |
March | 0.00 | 0.00 | 0.140358E+11 | 0.133627E+11 | 48833.69 | 16-MAR-15:30 | 48833.69 | 0.00 |
April | 0.00 | 0.00 | 0.446941E+11 | 0.445220E+11 | 76425.66 | 30-APR-16:31 | 76425.66 | 0.00 |
May | 0.00 | 0.00 | 0.601464E+11 | 0.600467E+11 | 72895.10 | 28-MAY-14:32 | 72895.10 | 0.00 |
June | 0.00 | 0.00 | 0.830297E+11 | 0.826622E+11 | 87098.18 | 28-JUN-14:50 | 87098.18 | 0.00 |
July | 0.00 | 0.00 | 0.798374E+11 | 0.749637E+11 | 123386.20 | 14-JUL-05:03 | 49116.03 | 0.00 |
August | 0.00 | 0.00 | 0.793950E+11 | 0.744665E+11 | 119766.80 | 01-AUG-04:03 | 58886.24 | 0.00 |
September | 0.00 | 0.00 | 0.649593E+11 | 0.598970E+11 | 115935.53 | 05-SEP-06:03 | 47821.84 | 0.00 |
October | 0.00 | 0.00 | 0.347370E+11 | 0.335032E+11 | 84747.73 | 02-OCT-04:02 | 84747.73 | 0.00 |
November | 0.00 | 0.00 | 0.137789E+11 | 0.128066E+11 | 52510.24 | 01-NOV-15:30 | 52510.24 | 0.00 |
December | 0.00 | 0.00 | 0.566117E+10 | 0.555387E+10 | 36158.17 | 25-DEC-15:52 | 36158.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.496346E+12 | 0.477068E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.298955E+10 | 0.244829E+10 | 19693.04 | 19693.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.830297E+11 | 0.826622E+11 | 123386.20 | 87098.18 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1575.23 | 5413.42 | 30-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1570.68 | 5427.58 | 03-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1597.61 | 5276.44 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1386.42 | 4879.11 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1317.20 | 4492.41 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1247.54 | 4099.60 | 02-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1101.49 | 3849.14 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1222.82 | 3956.26 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1216.90 | 4276.41 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1322.54 | 4687.72 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1459.21 | 5074.87 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1490.87 | 5335.51 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 1374.64 | ||||
Minimum of Months | 0.00 | 0.00 | 1101.49 | 3849.14 | ||
Maximum of Months | 0.00 | 0.00 | 1597.61 | 5427.58 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.200145E+10 | 0.36 | 3863.71 | 19-JAN-17:00 | 1.04 |
February | 0.135613E+10 | 0.33 | 2568.39 | 28-FEB-16:30 | 0.83 |
March | 0.193583E+10 | 0.36 | 4188.91 | 20-MAR-14:30 | 1.09 |
April | 0.377888E+10 | 0.49 | 6624.84 | 17-APR-16:00 | 1.44 |
May | 0.500213E+10 | 0.56 | 8259.39 | 08-MAY-16:00 | 1.66 |
June | 0.645681E+10 | 0.68 | 10883.07 | 05-JUN-06:03 | 1.97 |
July | 0.613970E+10 | 0.65 | 10883.07 | 05-JUL-05:12 | 1.98 |
August | 0.618531E+10 | 0.65 | 10883.07 | 01-AUG-04:03 | 1.95 |
September | 0.536144E+10 | 0.59 | 10883.07 | 02-SEP-06:03 | 1.96 |
October | 0.376129E+10 | 0.47 | 10883.07 | 02-OCT-04:02 | 1.96 |
November | 0.247624E+10 | 0.39 | 4894.04 | 14-NOV-16:30 | 1.19 |
December | 0.169795E+10 | 0.35 | 3603.37 | 27-DEC-16:40 | 1.00 |
Annual Sum or Average | 0.461532E+11 | 0.49 | |||
Minimum of Months | 0.135613E+10 | 0.33 | 2568.39 | 0.83 | |
Maximum of Months | 0.645681E+10 | 0.68 | 10883.07 | 1.98 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166913E+10 | 0.35 | 3817.22 | 27-JAN-16:50 | 1.07 |
February | 0.122189E+10 | 0.33 | 2748.57 | 22-FEB-16:30 | 0.88 |
March | 0.178374E+10 | 0.37 | 4542.17 | 20-MAR-14:05 | 1.18 |
April | 0.383884E+10 | 0.51 | 7961.74 | 24-APR-15:50 | 1.68 |
May | 0.498997E+10 | 0.58 | 9014.15 | 30-MAY-06:03 | 1.81 |
June | 0.687532E+10 | 0.72 | 10299.53 | 05-JUN-05:12 | 1.97 |
July | 0.619191E+10 | 0.66 | 10299.53 | 05-JUL-05:12 | 1.98 |
August | 0.618527E+10 | 0.66 | 10299.53 | 01-AUG-06:03 | 1.95 |
September | 0.482838E+10 | 0.57 | 10299.53 | 02-SEP-05:03 | 1.95 |
October | 0.304075E+10 | 0.44 | 10299.53 | 02-OCT-04:02 | 1.96 |
November | 0.184106E+10 | 0.36 | 4520.79 | 02-NOV-15:40 | 1.17 |
December | 0.137903E+10 | 0.33 | 3068.53 | 22-DEC-16:50 | 0.94 |
Annual Sum or Average | 0.438453E+11 | 0.49 | |||
Minimum of Months | 0.122189E+10 | 0.33 | 2748.57 | 0.88 | |
Maximum of Months | 0.687532E+10 | 0.72 | 10299.53 | 1.98 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166061E+10 | 0.36 | 3389.00 | 27-JAN-16:30 | 0.90 |
February | 0.127621E+10 | 0.36 | 2427.81 | 22-FEB-16:30 | 0.75 |
March | 0.177280E+10 | 0.39 | 4238.74 | 16-MAR-15:30 | 1.02 |
April | 0.371638E+10 | 0.48 | 8248.52 | 24-APR-15:30 | 1.53 |
May | 0.482560E+10 | 0.53 | 8033.23 | 15-MAY-15:20 | 1.50 |
June | 0.689387E+10 | 0.67 | 11103.49 | 19-JUN-05:12 | 1.84 |
July | 0.607630E+10 | 0.62 | 11624.04 | 10-JUL-04:02 | 1.88 |
August | 0.609015E+10 | 0.61 | 10732.65 | 14-AUG-15:20 | 1.78 |
September | 0.462503E+10 | 0.52 | 11708.44 | 25-SEP-05:12 | 1.89 |
October | 0.283030E+10 | 0.42 | 11299.87 | 02-OCT-04:02 | 1.85 |
November | 0.173554E+10 | 0.37 | 4339.50 | 02-NOV-15:30 | 1.02 |
December | 0.142585E+10 | 0.36 | 2738.72 | 22-DEC-16:30 | 0.80 |
Annual Sum or Average | 0.429286E+11 | 0.48 | |||
Minimum of Months | 0.127621E+10 | 0.36 | 2427.81 | 0.75 | |
Maximum of Months | 0.689387E+10 | 0.67 | 11708.44 | 1.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.76 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.68 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.21 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.45 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.15 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 57.52 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.64 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 56.77 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 56.98 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.82 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.70 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.30 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.45 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.82 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.69 | 57.69 | 1575.23 | 5413.42 | 30-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.08 | 57.08 | 1570.68 | 5427.58 | 03-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.60 | 57.60 | 1597.61 | 5276.44 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.87 | 56.87 | 1386.42 | 4879.11 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.39 | 57.39 | 1317.20 | 4492.41 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.76 | 57.76 | 1247.54 | 4099.60 | 02-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.81 | 56.81 | 1101.49 | 3849.14 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.27 | 57.27 | 1222.82 | 3956.26 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.21 | 57.21 | 1216.90 | 4276.41 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.36 | 57.36 | 1322.54 | 4687.72 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.03 | 57.03 | 1459.21 | 5074.87 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.67 | 57.67 | 1490.87 | 5335.51 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 1374.64 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.81 | 56.81 | 1101.49 | 3849.14 | ||
Maximum of Months | 0.00 | 0.00 | 57.76 | 57.76 | 1597.61 | 5427.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.637057E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.307472E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.632322E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.145933E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.199573E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.292195E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.281819E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.289653E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.241230E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.140956E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.696928E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.436150E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.186235E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.307472E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.292195E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.504762E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.206042E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.512196E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.141404E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.194314E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.289000E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.262592E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.263616E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209128E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115813E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.526757E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.320304E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.168287E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.289000E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.554541E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.263620E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.564428E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152802E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.210761E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.319851E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.286667E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.284923E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.221128E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118995E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.540221E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.470214E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.183443E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.263620E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.319851E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.200145E+10 | 0.152249E+11 | 0.804697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135613E+10 | 0.377334E+10 | 0.907961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193583E+10 | 0.145292E+11 | 0.101365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377888E+10 | 0.417158E+11 | 0.134713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.500213E+10 | 0.558647E+11 | 6760015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.645681E+10 | 0.759846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.613970E+10 | 0.783522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.618531E+10 | 0.813959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.536144E+10 | 0.705851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376129E+10 | 0.397356E+11 | 0.274301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247624E+10 | 0.173770E+11 | 0.415442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169795E+10 | 0.752345E+10 | 0.154864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461532E+11 | 0.502062E+12 | 0.510616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135613E+10 | 0.377334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.645681E+10 | 0.813959E+11 | 0.154864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166913E+10 | 0.134249E+11 | 0.308670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122189E+10 | 0.297552E+10 | 0.334618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178374E+10 | 0.133715E+11 | 0.320234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383884E+10 | 0.401936E+11 | 1663448.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.498997E+10 | 0.539876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687532E+10 | 0.735057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.619191E+10 | 0.713951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.618527E+10 | 0.720601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482838E+10 | 0.602512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304075E+10 | 0.333409E+11 | 63174888.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184106E+10 | 0.141372E+11 | 0.135424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137903E+10 | 0.601491E+10 | 0.126126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438453E+11 | 0.454658E+12 | 0.242504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122189E+10 | 0.297552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.687532E+10 | 0.735057E+11 | 0.126126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166061E+10 | 0.130812E+11 | 0.958989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127621E+10 | 0.298955E+10 | 0.988123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177280E+10 | 0.140358E+11 | 0.773043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.371638E+10 | 0.446941E+11 | 5334793.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482560E+10 | 0.601464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.689387E+10 | 0.830297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.607630E+10 | 0.798374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.609015E+10 | 0.793950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.462503E+10 | 0.649593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283030E+10 | 0.347370E+11 | 0.172295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173554E+10 | 0.137789E+11 | 0.493743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142585E+10 | 0.566117E+10 | 0.304807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429286E+11 | 0.496346E+12 | 0.643960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127621E+10 | 0.298955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.689387E+10 | 0.830297E+11 | 0.304807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.200145E+10 | 0.00 | 0.00 | 0.00 | 0.366443E+10 | 0.704685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135613E+10 | 0.00 | 0.00 | 0.00 | 0.981590E+09 | 0.736993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193583E+10 | 0.00 | 0.00 | 0.00 | 0.357503E+10 | 0.812365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377888E+10 | 0.00 | 0.00 | 0.00 | 0.106797E+11 | 0.134674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.500213E+10 | 0.00 | 0.00 | 0.00 | 0.149484E+11 | 6760015.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.645681E+10 | 0.00 | 0.00 | 0.00 | 0.227627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.613970E+10 | 0.00 | 0.00 | 0.00 | 0.220422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.618531E+10 | 0.00 | 0.00 | 0.00 | 0.227800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.536144E+10 | 0.00 | 0.00 | 0.00 | 0.187615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376129E+10 | 0.00 | 0.00 | 0.00 | 0.100719E+11 | 0.262343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247624E+10 | 0.00 | 0.00 | 0.00 | 0.413126E+10 | 0.361781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169795E+10 | 0.00 | 0.00 | 0.00 | 0.185360E+10 | 0.809946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461532E+11 | 0.00 | 0.00 | 0.00 | 0.136252E+12 | 0.382955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135613E+10 | 0.00 | 0.00 | 0.00 | 0.981590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.645681E+10 | 0.00 | 0.00 | 0.00 | 0.227800E+11 | 0.812365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166913E+10 | 0.00 | 0.00 | 0.00 | 0.325843E+10 | 0.120059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122189E+10 | 0.00 | 0.00 | 0.00 | 0.779337E+09 | 59192327.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178374E+10 | 0.00 | 0.00 | 0.00 | 0.329785E+10 | 40363891.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383884E+10 | 0.00 | 0.00 | 0.00 | 0.103015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.498997E+10 | 0.00 | 0.00 | 0.00 | 0.144414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.687532E+10 | 0.00 | 0.00 | 0.00 | 0.220247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.619191E+10 | 0.00 | 0.00 | 0.00 | 0.200673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.618527E+10 | 0.00 | 0.00 | 0.00 | 0.201764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482838E+10 | 0.00 | 0.00 | 0.00 | 0.160844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304075E+10 | 0.00 | 0.00 | 0.00 | 0.854052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184106E+10 | 0.00 | 0.00 | 0.00 | 0.341546E+10 | 11047304.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137903E+10 | 0.00 | 0.00 | 0.00 | 0.150671E+10 | 0.317294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438453E+11 | 0.00 | 0.00 | 0.00 | 0.123894E+12 | 0.547956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122189E+10 | 0.00 | 0.00 | 0.00 | 0.779337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.687532E+10 | 0.00 | 0.00 | 0.00 | 0.220247E+11 | 0.317294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166061E+10 | 0.00 | 0.00 | 0.00 | 0.323057E+10 | 0.654228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127621E+10 | 0.00 | 0.00 | 0.00 | 0.790350E+09 | 0.569645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177280E+10 | 0.00 | 0.00 | 0.00 | 0.349278E+10 | 0.378698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.371638E+10 | 0.00 | 0.00 | 0.00 | 0.115638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482560E+10 | 0.00 | 0.00 | 0.00 | 0.162505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.689387E+10 | 0.00 | 0.00 | 0.00 | 0.250912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.607630E+10 | 0.00 | 0.00 | 0.00 | 0.225904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.609015E+10 | 0.00 | 0.00 | 0.00 | 0.224022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.462503E+10 | 0.00 | 0.00 | 0.00 | 0.174877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283030E+10 | 0.00 | 0.00 | 0.00 | 0.901527E+10 | 53937758.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173554E+10 | 0.00 | 0.00 | 0.00 | 0.338602E+10 | 0.280653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142585E+10 | 0.00 | 0.00 | 0.00 | 0.144298E+10 | 0.183330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429286E+11 | 0.00 | 0.00 | 0.00 | 0.136744E+12 | 0.377046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127621E+10 | 0.00 | 0.00 | 0.00 | 0.790350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.689387E+10 | 0.00 | 0.00 | 0.00 | 0.250912E+11 | 0.183330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117162E+10 | 935763.42 | 0.00 | 27855724.47 | 8231574.50 | 0.00 | 0.898331E+10 | 0.00 | 0.63 |
February | 0.103946E+10 | 0.00 | 0.00 | 23872280.81 | 1910615.97 | 0.00 | 0.109870E+11 | 0.00 | 0.60 |
March | 0.658226E+09 | 7540941.48 | 0.00 | 30984229.81 | 666552.34 | 0.00 | 0.102217E+11 | 0.00 | 0.67 |
April | 0.402367E+09 | 0.586215E+09 | 0.00 | 21104682.74 | 55848039.88 | 0.00 | 0.402352E+10 | 0.00 | 0.55 |
May | 0.199875E+09 | 0.122936E+10 | 0.00 | 13183804.39 | 49928286.50 | 0.00 | 0.166310E+10 | 0.00 | 0.43 |
June | 86748886.50 | 0.326849E+10 | 0.00 | 3161792.37 | 88952259.42 | 0.00 | 0.374037E+09 | 0.00 | 0.31 |
July | 59495018.18 | 0.422569E+10 | 0.00 | 1070868.46 | 0.183568E+09 | 0.00 | 0.133637E+09 | 0.00 | 0.29 |
August | 39631279.68 | 0.427041E+10 | 0.00 | 1812845.44 | 0.116965E+09 | 0.00 | 0.168154E+09 | 0.00 | 0.35 |
September | 47656383.98 | 0.293637E+10 | 0.00 | 7242418.01 | 0.366128E+09 | 0.00 | 0.601336E+09 | 0.00 | 0.41 |
October | 0.433600E+09 | 0.650051E+09 | 0.00 | 26234573.53 | 47771915.84 | 0.00 | 0.701469E+10 | 0.00 | 0.64 |
November | 0.848286E+09 | 16431642.77 | 0.00 | 34136835.71 | 12530976.52 | 0.00 | 0.108407E+11 | 0.00 | 0.75 |
December | 0.116769E+10 | 572460.99 | 0.00 | 26698559.54 | 0.00 | 0.00 | 0.113694E+11 | 0.00 | 0.58 |
Annual Sum or Average | 0.615466E+10 | 0.171921E+11 | 0.00 | 0.217359E+09 | 0.932501E+09 | 0.00 | 0.663806E+11 | 0.00 | 0.52 |
Minimum of Months | 39631279.68 | 0.00 | 0.00 | 1070868.46 | 0.00 | 0.00 | 0.133637E+09 | 0.00 | 0.29 |
Maximum of Months | 0.117162E+10 | 0.427041E+10 | 0.00 | 34136835.71 | 0.366128E+09 | 0.00 | 0.113694E+11 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279062E+10 | 0.00 | 0.00 | 12257673.55 | 2726380.67 | 2878239.50 | 0.453084E+10 | 0.00 | 0.46 |
February | 0.383635E+10 | 0.00 | 0.00 | 8679441.64 | 2251674.48 | 0.00 | 0.507474E+10 | 0.00 | 0.45 |
March | 0.267094E+10 | 2566814.19 | 0.00 | 15471093.57 | 586907.01 | 0.00 | 0.555632E+10 | 0.00 | 0.50 |
April | 0.583698E+09 | 0.410399E+09 | 0.00 | 16560004.51 | 88840086.63 | 0.00 | 0.294184E+10 | 0.00 | 0.44 |
May | 0.330660E+09 | 0.948741E+09 | 0.00 | 11683214.55 | 51840866.07 | 0.00 | 0.129857E+10 | 0.00 | 0.37 |
June | 0.105486E+09 | 0.287152E+10 | 0.00 | 3111746.87 | 92305612.61 | 0.00 | 0.358135E+09 | 0.00 | 0.29 |
July | 57130838.04 | 0.359093E+10 | 0.00 | 1087884.91 | 0.158853E+09 | 0.00 | 0.121753E+09 | 0.00 | 0.27 |
August | 38591894.04 | 0.357130E+10 | 0.00 | 1305541.76 | 95671256.88 | 0.00 | 0.135990E+09 | 0.00 | 0.32 |
September | 78783099.36 | 0.245664E+10 | 0.00 | 6441240.15 | 0.223375E+09 | 0.00 | 0.423679E+09 | 0.00 | 0.36 |
October | 0.785087E+09 | 0.555176E+09 | 0.00 | 16522196.17 | 30647544.59 | 0.00 | 0.450725E+10 | 0.00 | 0.48 |
November | 0.212093E+10 | 16295125.10 | 0.00 | 17074566.80 | 14426834.64 | 0.00 | 0.580397E+10 | 0.00 | 0.51 |
December | 0.484167E+10 | 2198.10 | 0.00 | 7047199.13 | 1576018.71 | 0.00 | 0.389931E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.182399E+11 | 0.144236E+11 | 0.00 | 0.117242E+09 | 0.763101E+09 | 2878239.50 | 0.346524E+11 | 0.00 | 0.40 |
Minimum of Months | 38591894.04 | 0.00 | 0.00 | 1087884.91 | 586907.01 | 0.00 | 0.121753E+09 | 0.00 | 0.27 |
Maximum of Months | 0.484167E+10 | 0.359093E+10 | 0.00 | 17074566.80 | 0.223375E+09 | 2878239.50 | 0.580397E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.369103E+10 | 0.00 | 0.00 | 7486403.75 | 0.00 | 40849099.55 | 0.276111E+10 | 0.00 | 0.45 |
February | 0.469627E+10 | 0.00 | 0.00 | 4995652.41 | 2496926.42 | 11561444.73 | 0.346458E+10 | 0.00 | 0.42 |
March | 0.345468E+10 | 1057235.51 | 0.00 | 11195402.61 | 223229.01 | 356506.70 | 0.397747E+10 | 0.00 | 0.49 |
April | 0.780356E+09 | 0.287142E+09 | 0.00 | 16417325.31 | 61079431.04 | 0.00 | 0.209886E+10 | 0.00 | 0.42 |
May | 0.372678E+09 | 0.711160E+09 | 0.00 | 13303647.12 | 44983227.49 | 0.00 | 0.774739E+09 | 0.00 | 0.34 |
June | 0.134862E+09 | 0.262436E+10 | 0.00 | 2474385.73 | 84976455.74 | 0.00 | 0.174461E+09 | 0.00 | 0.28 |
July | 51733690.83 | 0.340488E+10 | 0.00 | 915526.45 | 0.210585E+09 | 0.00 | 64126196.35 | 0.00 | 0.26 |
August | 54852295.79 | 0.338030E+10 | 0.00 | 888245.36 | 0.124130E+09 | 0.00 | 45362587.26 | 0.00 | 0.31 |
September | 90667365.64 | 0.226898E+10 | 0.00 | 5800370.86 | 0.291766E+09 | 0.00 | 0.212882E+09 | 0.00 | 0.33 |
October | 0.126160E+10 | 0.491859E+09 | 0.00 | 13023697.62 | 43813654.02 | 0.00 | 0.302023E+10 | 0.00 | 0.44 |
November | 0.314232E+10 | 11906931.16 | 0.00 | 11282049.54 | 31234767.86 | 382650.94 | 0.379098E+10 | 0.00 | 0.48 |
December | 0.589049E+10 | 0.00 | 0.00 | 3128648.45 | 3674423.14 | 87814671.74 | 0.186393E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.236215E+11 | 0.131816E+11 | 0.00 | 90911355.22 | 0.898963E+09 | 0.140964E+09 | 0.222487E+11 | 0.00 | 0.38 |
Minimum of Months | 51733690.83 | 0.00 | 0.00 | 888245.36 | 0.00 | 0.00 | 45362587.26 | 0.00 | 0.26 |
Maximum of Months | 0.589049E+10 | 0.340488E+10 | 0.00 | 16417325.31 | 0.291766E+09 | 87814671.74 | 0.397747E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.960818E+09 | 0.00 | 0.00 | 827620.74 | 0.00 | 0.110650E+09 | 0.243002E+09 | 0.00 | 0.43 |
February | 0.128358E+10 | 0.00 | 0.00 | 321788.32 | 525909.93 | 96476416.84 | 0.249772E+09 | 0.00 | 0.40 |
March | 0.930113E+09 | 218384.34 | 0.00 | 1973317.35 | 107617.28 | 75710689.66 | 0.527666E+09 | 0.00 | 0.49 |
April | 0.239439E+09 | 99344023.85 | 0.00 | 3755589.73 | 11906247.19 | 0.00 | 0.355318E+09 | 0.00 | 0.48 |
May | 99646445.28 | 0.266529E+09 | 0.00 | 3450710.56 | 8609949.98 | 0.00 | 0.153464E+09 | 0.00 | 0.46 |
June | 30125429.28 | 0.108250E+10 | 0.00 | 643926.13 | 12637081.08 | 0.00 | 41824555.19 | 0.00 | 0.48 |
July | 11578128.57 | 0.126061E+10 | 0.00 | 206060.08 | 28596447.10 | 0.00 | 14633880.82 | 0.00 | 0.43 |
August | 13082064.80 | 0.111633E+10 | 0.00 | 197581.27 | 25777115.78 | 0.00 | 7241193.12 | 0.00 | 0.45 |
September | 28342224.05 | 0.721795E+09 | 0.00 | 1472117.62 | 55778107.93 | 0.00 | 44482594.28 | 0.00 | 0.44 |
October | 0.465539E+09 | 0.139821E+09 | 0.00 | 2310937.83 | 9379939.58 | 13322995.49 | 0.357878E+09 | 0.00 | 0.44 |
November | 0.863402E+09 | 1705260.93 | 0.00 | 1553993.28 | 7342172.70 | 64937522.12 | 0.422870E+09 | 0.00 | 0.45 |
December | 0.122300E+10 | 0.00 | 0.00 | 173828.71 | 773917.73 | 0.337964E+09 | 76068284.72 | 0.00 | 0.38 |
Annual Sum or Average | 0.614866E+10 | 0.468885E+10 | 0.00 | 16887471.62 | 0.161435E+09 | 0.699062E+09 | 0.249422E+10 | 0.00 | 0.44 |
Minimum of Months | 11578128.57 | 0.00 | 0.00 | 173828.71 | 0.00 | 0.00 | 7241193.12 | 0.00 | 0.38 |
Maximum of Months | 0.128358E+10 | 0.126061E+10 | 0.00 | 3755589.73 | 55778107.93 | 0.337964E+09 | 0.527666E+09 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.394981E+09 | 0.00 | 0.00 | 2108815.22 | 0.00 | 34232567.29 | 0.706235E+09 | 0.00 | 0.59 |
February | 0.471764E+09 | 0.00 | 0.00 | 1479982.90 | 334207.16 | 35624134.32 | 0.838799E+09 | 0.00 | 0.51 |
March | 0.353409E+09 | 482930.25 | 0.00 | 3451500.22 | 8662.12 | 25777053.08 | 0.112090E+10 | 0.00 | 0.77 |
April | 86920932.06 | 96152808.65 | 0.00 | 6006183.25 | 7153582.73 | 0.00 | 0.782525E+09 | 0.00 | 0.98 |
May | 47228952.50 | 0.213260E+09 | 0.00 | 5044557.51 | 4705682.75 | 0.00 | 0.319841E+09 | 0.00 | 0.84 |
June | 16009049.31 | 0.911162E+09 | 0.00 | 828102.02 | 5403582.69 | 0.00 | 49786079.25 | 0.00 | 0.69 |
July | 4876001.05 | 0.113586E+10 | 0.00 | 259835.03 | 16012254.69 | 0.00 | 20332076.79 | 0.00 | 0.61 |
August | 7281624.29 | 0.106466E+10 | 0.00 | 220398.56 | 14311060.07 | 0.00 | 10357800.12 | 0.00 | 0.67 |
September | 14728395.31 | 0.703907E+09 | 0.00 | 1414529.65 | 25472451.12 | 0.00 | 44252234.87 | 0.00 | 0.66 |
October | 0.174146E+09 | 0.134378E+09 | 0.00 | 3514188.62 | 4710746.90 | 5303481.47 | 0.761078E+09 | 0.00 | 0.77 |
November | 0.393330E+09 | 1445877.83 | 0.00 | 2601991.62 | 4355749.00 | 13441359.89 | 0.799889E+09 | 0.00 | 0.65 |
December | 0.686340E+09 | 0.00 | 0.00 | 713989.46 | 491812.06 | 0.109999E+09 | 0.320909E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.265102E+10 | 0.426131E+10 | 0.00 | 27644074.06 | 82959791.28 | 0.224377E+09 | 0.577490E+10 | 0.00 | 0.68 |
Minimum of Months | 4876001.05 | 0.00 | 0.00 | 220398.56 | 0.00 | 0.00 | 10357800.12 | 0.00 | 0.43 |
Maximum of Months | 0.686340E+09 | 0.113586E+10 | 0.00 | 6006183.25 | 25472451.12 | 0.109999E+09 | 0.112090E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444403E+09 | 0.00 | 0.00 | 11334368.46 | 0.00 | 41047018.82 | 0.325707E+10 | 0.00 | 1.39 |
February | 0.668969E+09 | 0.00 | 0.00 | 6019912.40 | 528786.64 | 59356576.29 | 0.320130E+10 | 0.00 | 0.92 |
March | 0.567597E+09 | 639383.97 | 0.00 | 6722978.37 | 0.00 | 57409158.66 | 0.208721E+10 | 0.00 | 0.90 |
April | 0.224938E+09 | 0.155987E+09 | 0.00 | 6023030.01 | 11208509.11 | 0.00 | 0.582593E+09 | 0.00 | 0.67 |
May | 0.119062E+09 | 0.291466E+09 | 0.00 | 3566820.02 | 8371067.76 | 0.00 | 0.132780E+09 | 0.00 | 0.48 |
June | 34737477.16 | 0.104901E+10 | 0.00 | 499542.36 | 13225143.29 | 0.00 | 27548351.97 | 0.00 | 0.45 |
July | 11645740.25 | 0.126092E+10 | 0.00 | 182509.90 | 31782883.38 | 0.00 | 10849823.59 | 0.00 | 0.43 |
August | 13292321.54 | 0.128494E+10 | 0.00 | 198899.15 | 24457765.24 | 0.00 | 6948427.31 | 0.00 | 0.51 |
September | 27538580.63 | 0.997512E+09 | 0.00 | 2186077.09 | 45492912.59 | 0.00 | 61479570.73 | 0.00 | 0.58 |
October | 0.262017E+09 | 0.240226E+09 | 0.00 | 8421500.85 | 7876577.31 | 5054518.26 | 0.165313E+10 | 0.00 | 0.98 |
November | 0.442535E+09 | 2980704.79 | 0.00 | 10177087.69 | 6720341.58 | 18401830.76 | 0.313918E+10 | 0.00 | 1.25 |
December | 0.646880E+09 | 964246.36 | 0.00 | 8264225.41 | 449143.61 | 0.124840E+09 | 0.324446E+10 | 0.00 | 1.07 |
Annual Sum or Average | 0.346362E+10 | 0.528464E+10 | 0.00 | 63596951.71 | 0.150113E+09 | 0.306109E+09 | 0.174045E+11 | 0.00 | 0.80 |
Minimum of Months | 11645740.25 | 0.00 | 0.00 | 182509.90 | 0.00 | 0.00 | 6948427.31 | 0.00 | 0.43 |
Maximum of Months | 0.668969E+09 | 0.128494E+10 | 0.00 | 11334368.46 | 45492912.59 | 0.124840E+09 | 0.325707E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.501186E+09 | 0.00 | 0.00 | 2515846.55 | 0.00 | 58249005.54 | 0.656334E+09 | 0.00 | 0.72 |
February | 0.654771E+09 | 0.00 | 0.00 | 1489219.12 | 332931.28 | 58473164.91 | 0.803003E+09 | 0.00 | 0.59 |
March | 0.479311E+09 | 229908.06 | 0.00 | 3043701.92 | 59498.88 | 46411304.87 | 0.844624E+09 | 0.00 | 0.77 |
April | 0.144563E+09 | 0.130774E+09 | 0.00 | 4348579.98 | 2130989.25 | 0.00 | 0.382933E+09 | 0.00 | 0.76 |
May | 68810892.31 | 0.301803E+09 | 0.00 | 2609206.75 | 2087746.06 | 0.00 | 93715806.96 | 0.00 | 0.62 |
June | 19748411.71 | 0.989280E+09 | 0.00 | 361223.25 | 5325009.75 | 0.00 | 21912246.32 | 0.00 | 0.62 |
July | 6758161.10 | 0.997156E+09 | 0.00 | 129753.41 | 14064042.00 | 0.00 | 8403943.73 | 0.00 | 0.52 |
August | 7680635.94 | 0.906705E+09 | 0.00 | 158555.61 | 11606448.78 | 0.00 | 5379281.19 | 0.00 | 0.57 |
September | 17195652.55 | 0.595723E+09 | 0.00 | 1293160.93 | 30893895.87 | 0.00 | 37714137.81 | 0.00 | 0.55 |
October | 0.245054E+09 | 0.117640E+09 | 0.00 | 3278462.30 | 4810619.65 | 7697790.12 | 0.537249E+09 | 0.00 | 0.67 |
November | 0.440814E+09 | 1866950.08 | 0.00 | 2955873.28 | 4248266.30 | 37717059.08 | 0.819850E+09 | 0.00 | 0.73 |
December | 0.623425E+09 | 95245.65 | 0.00 | 1256365.33 | 453630.90 | 0.179761E+09 | 0.549914E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.320932E+10 | 0.404127E+10 | 0.00 | 23439948.43 | 76013078.73 | 0.388309E+09 | 0.476103E+10 | 0.00 | 0.64 |
Minimum of Months | 6758161.10 | 0.00 | 0.00 | 129753.41 | 0.00 | 0.00 | 5379281.19 | 0.00 | 0.52 |
Maximum of Months | 0.654771E+09 | 0.997156E+09 | 0.00 | 4348579.98 | 30893895.87 | 0.179761E+09 | 0.844624E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117803E+10 | 26043.03 | 0.00 | 503908.61 | 1887810.03 | 28718889.02 | 0.154941E+09 | 0.00 | 0.39 |
February | 0.156257E+10 | 0.00 | 0.00 | 40425.62 | 403599.44 | 20400379.92 | 70098685.10 | 0.00 | 0.39 |
March | 0.123570E+10 | 1037153.53 | 0.00 | 752034.11 | 240593.89 | 18687501.45 | 0.169442E+09 | 0.00 | 0.40 |
April | 0.290369E+09 | 0.121081E+09 | 0.00 | 2023778.23 | 16122483.34 | 0.00 | 0.266734E+09 | 0.00 | 0.38 |
May | 0.118241E+09 | 0.308297E+09 | 0.00 | 1643940.68 | 10608770.72 | 0.00 | 0.152362E+09 | 0.00 | 0.37 |
June | 38019178.01 | 0.105887E+10 | 0.00 | 523875.80 | 20608614.95 | 0.00 | 53373644.33 | 0.00 | 0.41 |
July | 18542636.72 | 0.132823E+10 | 0.00 | 203011.89 | 36907922.68 | 0.00 | 21793100.35 | 0.00 | 0.40 |
August | 14705439.11 | 0.125736E+10 | 0.00 | 271619.47 | 26455238.55 | 0.00 | 24068688.62 | 0.00 | 0.44 |
September | 27789130.18 | 0.865820E+09 | 0.00 | 1414651.47 | 72865749.55 | 0.00 | 92618331.22 | 0.00 | 0.47 |
October | 0.376140E+09 | 0.171733E+09 | 0.00 | 2692133.17 | 7081662.33 | 0.00 | 0.591651E+09 | 0.00 | 0.48 |
November | 0.901124E+09 | 1226088.44 | 0.00 | 2300784.94 | 3667187.48 | 0.00 | 0.633799E+09 | 0.00 | 0.46 |
December | 0.162860E+10 | 0.00 | 0.00 | 220422.97 | 74082.24 | 36544569.07 | 0.101449E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.738983E+10 | 0.511369E+10 | 0.00 | 12590586.95 | 0.196924E+09 | 0.104351E+09 | 0.233233E+10 | 0.00 | 0.41 |
Minimum of Months | 14705439.11 | 0.00 | 0.00 | 40425.62 | 74082.24 | 0.00 | 21793100.35 | 0.00 | 0.37 |
Maximum of Months | 0.162860E+10 | 0.132823E+10 | 0.00 | 2692133.17 | 72865749.55 | 36544569.07 | 0.633799E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.462187E+09 | 127085.17 | 0.00 | 2344642.31 | 1102283.51 | 5295776.89 | 0.750893E+09 | 0.00 | 0.57 |
February | 0.571862E+09 | 0.00 | 0.00 | 1367077.87 | 255849.04 | 2780976.07 | 0.714535E+09 | 0.00 | 0.47 |
March | 0.446043E+09 | 976004.26 | 0.00 | 2630863.47 | 89257.49 | 2037100.28 | 0.808445E+09 | 0.00 | 0.59 |
April | 90477951.37 | 0.140202E+09 | 0.00 | 4426660.31 | 7560790.99 | 0.00 | 0.753385E+09 | 0.00 | 0.86 |
May | 55624700.58 | 0.290375E+09 | 0.00 | 3210563.65 | 6332336.14 | 0.00 | 0.345103E+09 | 0.00 | 0.75 |
June | 13367971.23 | 0.948480E+09 | 0.00 | 759284.79 | 7893214.37 | 0.00 | 78515769.03 | 0.00 | 0.64 |
July | 4590850.15 | 0.121099E+10 | 0.00 | 295633.59 | 18723083.26 | 0.00 | 35446438.10 | 0.00 | 0.59 |
August | 3813945.83 | 0.119267E+10 | 0.00 | 357832.92 | 11633376.89 | 0.00 | 32039314.23 | 0.00 | 0.66 |
September | 9600389.13 | 0.811332E+09 | 0.00 | 1443740.12 | 31994763.60 | 0.00 | 0.105257E+09 | 0.00 | 0.70 |
October | 0.121586E+09 | 0.159702E+09 | 0.00 | 4293758.02 | 4043231.62 | 0.00 | 0.108179E+10 | 0.00 | 0.89 |
November | 0.316916E+09 | 1512177.82 | 0.00 | 4054833.85 | 1883404.03 | 0.00 | 0.123587E+10 | 0.00 | 0.76 |
December | 0.643169E+09 | 3903.46 | 0.00 | 1620788.63 | 43625.26 | 3602422.56 | 0.684707E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.273924E+10 | 0.475637E+10 | 0.00 | 26805679.55 | 91555216.20 | 13716275.80 | 0.662599E+10 | 0.00 | 0.66 |
Minimum of Months | 3813945.83 | 0.00 | 0.00 | 295633.59 | 43625.26 | 0.00 | 32039314.23 | 0.00 | 0.47 |
Maximum of Months | 0.643169E+09 | 0.121099E+10 | 0.00 | 4426660.31 | 31994763.60 | 5295776.89 | 0.123587E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.442843E+09 | 1338859.07 | 0.00 | 9672795.68 | 1449129.99 | 0.290450E+09 | 0.233688E+10 | 0.00 | 1.09 |
February | 0.102631E+10 | 0.00 | 0.00 | 2147233.86 | 403495.61 | 0.341092E+09 | 0.115354E+10 | 0.00 | 0.59 |
March | 0.861909E+09 | 2583366.80 | 0.00 | 3354918.27 | 140766.61 | 0.372171E+09 | 0.721050E+09 | 0.00 | 0.61 |
April | 0.280622E+09 | 0.270610E+09 | 0.00 | 3523566.04 | 11939738.56 | 60102159.74 | 0.326712E+09 | 0.00 | 0.59 |
May | 0.171215E+09 | 0.472437E+09 | 0.00 | 1686918.55 | 10643606.56 | 4105297.81 | 81829118.71 | 0.00 | 0.47 |
June | 54817702.76 | 0.139449E+10 | 0.00 | 354257.72 | 21233444.84 | 0.00 | 22108141.02 | 0.00 | 0.50 |
July | 17981687.53 | 0.171539E+10 | 0.00 | 173972.89 | 36455098.21 | 0.00 | 17335155.60 | 0.00 | 0.49 |
August | 19796323.21 | 0.184394E+10 | 0.00 | 230865.14 | 28050743.69 | 0.00 | 15275789.52 | 0.00 | 0.59 |
September | 36477432.38 | 0.136029E+10 | 0.00 | 2036136.58 | 57023433.70 | 0.00 | 92027029.76 | 0.00 | 0.66 |
October | 0.261818E+09 | 0.324081E+09 | 0.00 | 7544922.46 | 4753709.04 | 0.120674E+09 | 0.140610E+10 | 0.00 | 0.97 |
November | 0.394273E+09 | 2798478.72 | 0.00 | 10298466.48 | 3336494.52 | 0.165986E+09 | 0.272738E+10 | 0.00 | 1.11 |
December | 0.808479E+09 | 14395.15 | 0.00 | 6853700.53 | 68800.72 | 0.407299E+09 | 0.226834E+10 | 0.00 | 0.91 |
Annual Sum or Average | 0.437655E+10 | 0.738798E+10 | 0.00 | 47877754.20 | 0.175498E+09 | 0.176188E+10 | 0.111686E+11 | 0.00 | 0.72 |
Minimum of Months | 17981687.53 | 0.00 | 0.00 | 173972.89 | 68800.72 | 0.00 | 15275789.52 | 0.00 | 0.47 |
Maximum of Months | 0.102631E+10 | 0.184394E+10 | 0.00 | 10298466.48 | 57023433.70 | 0.407299E+09 | 0.272738E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.565090E+09 | 368491.96 | 0.00 | 2228409.60 | 1096642.79 | 6410611.29 | 0.511287E+09 | 0.00 | 0.57 |
February | 0.793075E+09 | 0.00 | 0.00 | 1027989.54 | 254539.79 | 6282083.17 | 0.494737E+09 | 0.00 | 0.49 |
March | 0.598454E+09 | 1647333.04 | 0.00 | 1900310.51 | 0.00 | 1649319.95 | 0.481636E+09 | 0.00 | 0.56 |
April | 0.134563E+09 | 0.182683E+09 | 0.00 | 2694246.38 | 3032733.81 | 0.00 | 0.365190E+09 | 0.00 | 0.67 |
May | 64882658.05 | 0.383082E+09 | 0.00 | 1433715.71 | 2456082.02 | 0.00 | 0.130861E+09 | 0.00 | 0.57 |
June | 12712652.45 | 0.105269E+10 | 0.00 | 424528.93 | 6189429.52 | 0.00 | 48115059.22 | 0.00 | 0.58 |
July | 7438274.96 | 0.110166E+10 | 0.00 | 173927.39 | 14481935.60 | 0.00 | 21039493.16 | 0.00 | 0.50 |
August | 5390812.43 | 0.109656E+10 | 0.00 | 242841.64 | 9324687.51 | 0.00 | 22982629.77 | 0.00 | 0.57 |
September | 6525674.07 | 0.756749E+09 | 0.00 | 1143146.39 | 35149550.15 | 0.00 | 81674133.27 | 0.00 | 0.61 |
October | 0.153154E+09 | 0.153589E+09 | 0.00 | 3450932.16 | 3519881.52 | 0.00 | 0.735660E+09 | 0.00 | 0.73 |
November | 0.355505E+09 | 2481372.06 | 0.00 | 3889054.45 | 1664117.21 | 0.00 | 0.106879E+10 | 0.00 | 0.75 |
December | 0.791849E+09 | 3319.75 | 0.00 | 1510976.05 | 43402.01 | 12923630.24 | 0.580773E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.348864E+10 | 0.473151E+10 | 0.00 | 20120078.77 | 77213001.91 | 27265644.65 | 0.454275E+10 | 0.00 | 0.59 |
Minimum of Months | 5390812.43 | 0.00 | 0.00 | 173927.39 | 0.00 | 0.00 | 21039493.16 | 0.00 | 0.49 |
Maximum of Months | 0.793075E+09 | 0.110166E+10 | 0.00 | 3889054.45 | 35149550.15 | 12923630.24 | 0.106879E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109149E+10 | 0.00 | 0.00 | 988879.52 | 573584.82 | 27974816.87 | 0.267308E+09 | 0.00 | 0.41 |
February | 0.138313E+10 | 0.00 | 0.00 | 421694.99 | 473714.59 | 13475025.70 | 0.310766E+09 | 0.00 | 0.41 |
March | 0.998426E+09 | 721310.80 | 0.00 | 2167096.38 | 123475.40 | 14416102.81 | 0.579532E+09 | 0.00 | 0.48 |
April | 0.250121E+09 | 0.153144E+09 | 0.00 | 3153573.39 | 12693481.57 | 0.00 | 0.404920E+09 | 0.00 | 0.48 |
May | 0.102590E+09 | 0.367865E+09 | 0.00 | 2708785.38 | 10957690.02 | 0.00 | 0.236771E+09 | 0.00 | 0.49 |
June | 33170148.64 | 0.124467E+10 | 0.00 | 764271.50 | 14473766.25 | 0.00 | 76349828.22 | 0.00 | 0.50 |
July | 13705175.10 | 0.135762E+10 | 0.00 | 225332.08 | 31431401.82 | 0.00 | 26870751.40 | 0.00 | 0.45 |
August | 17260881.53 | 0.122942E+10 | 0.00 | 230041.16 | 20994482.59 | 0.00 | 17614138.49 | 0.00 | 0.47 |
September | 32381739.85 | 0.806848E+09 | 0.00 | 1469127.05 | 45972490.58 | 0.00 | 68915894.34 | 0.00 | 0.46 |
October | 0.481808E+09 | 0.159784E+09 | 0.00 | 2291608.96 | 7253436.14 | 0.00 | 0.436163E+09 | 0.00 | 0.46 |
November | 0.950327E+09 | 1382204.97 | 0.00 | 1935096.07 | 4913964.28 | 5907026.74 | 0.504556E+09 | 0.00 | 0.44 |
December | 0.153767E+10 | 0.00 | 0.00 | 215859.73 | 332030.38 | 0.107784E+09 | 99508038.79 | 0.00 | 0.38 |
Annual Sum or Average | 0.689208E+10 | 0.532146E+10 | 0.00 | 16571366.21 | 0.150194E+09 | 0.169557E+09 | 0.302927E+10 | 0.00 | 0.45 |
Minimum of Months | 13705175.10 | 0.00 | 0.00 | 215859.73 | 123475.40 | 0.00 | 17614138.49 | 0.00 | 0.38 |
Maximum of Months | 0.153767E+10 | 0.135762E+10 | 0.00 | 3153573.39 | 45972490.58 | 0.107784E+09 | 0.579532E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.430709E+09 | 300586.53 | 0.00 | 2354899.26 | 36320.46 | 9177658.65 | 0.771161E+09 | 0.00 | 0.56 |
February | 0.484121E+09 | 0.00 | 0.00 | 1649927.01 | 300876.18 | 4336412.47 | 0.855414E+09 | 0.00 | 0.49 |
March | 0.374720E+09 | 508037.63 | 0.00 | 3506940.30 | 78424.45 | 4952123.03 | 0.112422E+10 | 0.00 | 0.72 |
April | 91226146.96 | 0.135410E+09 | 0.00 | 5248563.09 | 7948831.85 | 0.00 | 0.873588E+09 | 0.00 | 0.96 |
May | 54116534.48 | 0.286166E+09 | 0.00 | 4133574.49 | 6632568.28 | 0.00 | 0.419015E+09 | 0.00 | 0.86 |
June | 16052687.32 | 0.989320E+09 | 0.00 | 931364.77 | 7223199.43 | 0.00 | 87349742.17 | 0.00 | 0.71 |
July | 5359570.14 | 0.116050E+10 | 0.00 | 297069.96 | 16762773.90 | 0.00 | 34187903.70 | 0.00 | 0.61 |
August | 9391834.03 | 0.108762E+10 | 0.00 | 282717.19 | 11082477.10 | 0.00 | 21890462.11 | 0.00 | 0.67 |
September | 18916301.59 | 0.713833E+09 | 0.00 | 1440609.04 | 22266856.90 | 0.00 | 73418438.14 | 0.00 | 0.66 |
October | 0.181836E+09 | 0.138608E+09 | 0.00 | 3482747.29 | 3479767.21 | 0.00 | 0.862416E+09 | 0.00 | 0.77 |
November | 0.389708E+09 | 1055423.04 | 0.00 | 3029577.49 | 3076890.74 | 432581.95 | 0.903764E+09 | 0.00 | 0.63 |
December | 0.630858E+09 | 19565.34 | 0.00 | 1106972.06 | 95151.51 | 32806562.74 | 0.474695E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.268702E+10 | 0.451334E+10 | 0.00 | 27464961.96 | 78984138.00 | 51705338.83 | 0.650112E+10 | 0.00 | 0.67 |
Minimum of Months | 5359570.14 | 0.00 | 0.00 | 282717.19 | 36320.46 | 0.00 | 21890462.11 | 0.00 | 0.40 |
Maximum of Months | 0.630858E+09 | 0.116050E+10 | 0.00 | 5248563.09 | 22266856.90 | 32806562.74 | 0.112422E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478016E+09 | 2991215.57 | 0.00 | 11880231.61 | 56327.87 | 11763643.21 | 0.310836E+10 | 0.00 | 1.28 |
February | 0.729929E+09 | 0.00 | 0.00 | 6605806.78 | 473973.47 | 4297833.87 | 0.322356E+10 | 0.00 | 0.95 |
March | 0.636181E+09 | 1199896.35 | 0.00 | 7081172.15 | 123542.88 | 8146605.15 | 0.204499E+10 | 0.00 | 0.88 |
April | 0.236983E+09 | 0.251019E+09 | 0.00 | 4790175.70 | 12521879.76 | 0.00 | 0.587651E+09 | 0.00 | 0.67 |
May | 0.115207E+09 | 0.412505E+09 | 0.00 | 2623135.09 | 10963678.28 | 0.00 | 0.198970E+09 | 0.00 | 0.51 |
June | 41374517.94 | 0.121305E+10 | 0.00 | 562762.97 | 16229748.45 | 0.00 | 52103450.04 | 0.00 | 0.47 |
July | 16320905.08 | 0.137576E+10 | 0.00 | 190903.87 | 31527371.14 | 0.00 | 18818710.41 | 0.00 | 0.44 |
August | 16917977.13 | 0.144439E+10 | 0.00 | 226939.65 | 18524794.83 | 0.00 | 17125530.78 | 0.00 | 0.53 |
September | 31061332.17 | 0.112944E+10 | 0.00 | 2067394.90 | 40293320.86 | 0.00 | 85863902.54 | 0.00 | 0.61 |
October | 0.274389E+09 | 0.286614E+09 | 0.00 | 7608930.87 | 3900648.85 | 0.00 | 0.167867E+10 | 0.00 | 0.99 |
November | 0.444936E+09 | 2395265.26 | 0.00 | 11331751.23 | 4818750.17 | 191484.21 | 0.316726E+10 | 0.00 | 1.20 |
December | 0.754836E+09 | 121412.46 | 0.00 | 9666519.64 | 269912.65 | 38746239.15 | 0.345519E+10 | 0.00 | 1.11 |
Annual Sum or Average | 0.377615E+10 | 0.611949E+10 | 0.00 | 64635724.46 | 0.139704E+09 | 63145805.60 | 0.176386E+11 | 0.00 | 0.80 |
Minimum of Months | 16320905.08 | 0.00 | 0.00 | 190903.87 | 56327.87 | 0.00 | 17125530.78 | 0.00 | 0.44 |
Maximum of Months | 0.754836E+09 | 0.144439E+10 | 0.00 | 11880231.61 | 40293320.86 | 38746239.15 | 0.345519E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.565524E+09 | 1195194.77 | 0.00 | 2620670.71 | 35841.47 | 14219133.46 | 0.604235E+09 | 0.00 | 0.64 |
February | 0.731062E+09 | 0.00 | 0.00 | 1598840.98 | 301589.75 | 8388059.13 | 0.792659E+09 | 0.00 | 0.60 |
March | 0.530923E+09 | 956658.15 | 0.00 | 3109239.15 | 0.00 | 5562232.67 | 0.808258E+09 | 0.00 | 0.73 |
April | 0.150895E+09 | 0.205189E+09 | 0.00 | 3221819.07 | 2007025.97 | 0.00 | 0.391481E+09 | 0.00 | 0.76 |
May | 69460895.89 | 0.430477E+09 | 0.00 | 1896111.52 | 2260025.69 | 0.00 | 0.137359E+09 | 0.00 | 0.67 |
June | 20352179.50 | 0.119118E+10 | 0.00 | 430479.75 | 5877436.26 | 0.00 | 42984246.11 | 0.00 | 0.67 |
July | 7924200.87 | 0.110923E+10 | 0.00 | 142057.50 | 12762720.24 | 0.00 | 16104525.24 | 0.00 | 0.55 |
August | 9147962.59 | 0.103996E+10 | 0.00 | 156106.99 | 8151022.44 | 0.00 | 13252725.39 | 0.00 | 0.60 |
September | 20047216.69 | 0.686621E+09 | 0.00 | 1185576.01 | 24337433.43 | 0.00 | 50866699.75 | 0.00 | 0.58 |
October | 0.251375E+09 | 0.142681E+09 | 0.00 | 2988058.80 | 2370687.84 | 0.00 | 0.561816E+09 | 0.00 | 0.68 |
November | 0.481942E+09 | 1949095.69 | 0.00 | 3276946.91 | 2883736.91 | 3627326.39 | 0.840180E+09 | 0.00 | 0.69 |
December | 0.791606E+09 | 16360.16 | 0.00 | 1431638.02 | 204127.15 | 62284416.20 | 0.563469E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.363026E+10 | 0.480946E+10 | 0.00 | 22057545.41 | 61191647.14 | 94081167.85 | 0.482266E+10 | 0.00 | 0.64 |
Minimum of Months | 7924200.87 | 0.00 | 0.00 | 142057.50 | 0.00 | 0.00 | 13252725.39 | 0.00 | 0.54 |
Maximum of Months | 0.791606E+09 | 0.119118E+10 | 0.00 | 3276946.91 | 24337433.43 | 62284416.20 | 0.840180E+09 | 0.00 | 0.76 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.193503E+12 | 0.727784E+10 | 0.00 | 0.169376E+12 | 0.520327E+11 |
February | 0.201349E+12 | 0.686922E+10 | 0.00 | 0.173996E+12 | 0.125059E+11 |
March | 0.255019E+12 | 0.744565E+10 | 0.00 | 0.173488E+12 | 0.525210E+11 |
April | 0.301273E+12 | 0.128943E+10 | 0.00 | 0.968746E+11 | 0.159150E+12 |
May | 0.292656E+12 | -858659337.7 | 0.00 | 0.605708E+11 | 0.215639E+12 |
June | 0.298425E+12 | -0.416852E+10 | 0.00 | -0.475563E+10 | 0.302399E+12 |
July | 0.276774E+12 | -0.624411E+10 | 0.00 | -0.359035E+11 | 0.294285E+12 |
August | 0.249246E+12 | -0.516058E+10 | 0.00 | -0.288790E+11 | 0.298210E+12 |
September | 0.215778E+12 | -0.339629E+10 | 0.00 | -0.287097E+11 | 0.248129E+12 |
October | 0.213587E+12 | 0.283753E+10 | 0.00 | 0.126274E+12 | 0.135490E+12 |
November | 0.195362E+12 | 0.665255E+10 | 0.00 | 0.169883E+12 | 0.563236E+11 |
December | 0.160997E+12 | 0.816750E+10 | 0.00 | 0.181519E+12 | 0.247272E+11 |
Annual Sum or Average | 0.285397E+13 | 0.207116E+11 | 0.00 | 0.105373E+13 | 0.185141E+13 |
Minimum of Months | 0.160997E+12 | -0.624411E+10 | 0.00 | -0.359035E+11 | 0.125059E+11 |
Maximum of Months | 0.301273E+12 | 0.816750E+10 | 0.00 | 0.181519E+12 | 0.302399E+12 |