Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2023-10-16 08:32:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1490.59 | 299.18 | 299.18 |
Net Site Energy | 1333.37 | 267.63 | 267.63 |
Total Source Energy | 4380.54 | 879.24 | 879.24 |
Net Source Energy | 3882.60 | 779.30 | 779.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 119.55 | 38.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 286.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 166.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 124.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1327.29 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 119.55 | 38.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 286.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 166.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 60.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 124.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 119.55 | 38.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 286.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 166.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 60.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 124.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 93.67 | 32.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 266.41 | 32.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 93.67 | 32.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 266.41 | 32.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 164.235 | 12.37 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.01 | -0.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 157.229 | 11.85 |
Electricity Coming From Utility | 1171.465 | 88.26 |
Surplus Electricity Going To Utility | 1.407 | 0.11 |
Net Electricity From Utility | 1170.058 | 88.15 |
Total On-Site and Utility Electric Sources | 1327.287 | 100.00 |
Total Electricity End Uses | 1327.287 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 163.83 |
Time Setpoint Not Met During Occupied Cooling | 146.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2016.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 03-FEB-07:30 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:20 |
Heating | 189631.84 | 64896.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5682.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8862.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 223625.88 | 73758.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 189631.84 | 64896.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2981.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 36.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5682.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8862.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 378.62 | 42.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 906.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 528.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 108.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 191.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 135.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4203.52 | 177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 76.00 | 8.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 182.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 843.71 | 35.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 76.00 | 8.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 182.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 843.71 | 35.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.35 | 0.318501 | 0.271000 | 0.637681 | 0.849337 | 0.500000 | 0.001196 |
CORE_MID VAV BOX COMPONENT | 1.97 | 0.381372 | 0.324000 | 0.636710 | 1.00 | 0.500000 | 0.000999 |
CORE_TOP VAV BOX COMPONENT | 2.13 | 0.352034 | 0.299000 | 0.636549 | 0.938758 | 0.500000 | 0.001082 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.691110 | 0.228606 | 0.194000 | 0.134075 | 0.609615 | 0.500000 | 0.001667 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.666969 | 0.149965 | 0.127000 | 0.084705 | 0.399906 | 0.500000 | 0.002541 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.803618 | 0.196601 | 0.167000 | 0.134204 | 0.524268 | 0.500000 | 0.001938 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.741161 | 0.134944 | 0.115000 | 0.085234 | 0.359851 | 0.500000 | 0.002823 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.542506 | 0.291226 | 0.248000 | 0.134541 | 0.776602 | 0.500000 | 0.001308 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.563392 | 0.177535 | 0.151000 | 0.085072 | 0.473427 | 0.500000 | 0.002146 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.640200 | 0.246785 | 0.210000 | 0.134442 | 0.658093 | 0.500000 | 0.001544 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.586397 | 0.170559 | 0.145000 | 0.085028 | 0.454824 | 0.500000 | 0.002234 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.592279 | 0.266752 | 0.227000 | 0.134447 | 0.711339 | 0.500000 | 0.001428 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.638711 | 0.417598 | 0.500000 | 0.002433 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.703770 | 0.224493 | 0.191000 | 0.134420 | 0.598649 | 0.500000 | 0.001697 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.668509 | 0.149609 | 0.127000 | 0.084901 | 0.398958 | 0.500000 | 0.002547 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20533.99 |
CORE_MID VAV BOX REHEAT COIL | 21599.78 |
CORE_TOP VAV BOX REHEAT COIL | 36913.54 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17494.49 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11363.42 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17357.63 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11446.07 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13081.07 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8561.83 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12968.07 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8635.48 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 13841.97 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9032.79 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 13715.09 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9107.38 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.34 | 1.08 | 4.69 | 1.77 | 4.23 | 4.23 | 0.300000 | 0.418102 | 4.23 |
PACU_VAV_MID | 2.28 | 1.08 | 4.57 | 2.09 | 4.01 | 4.01 | 0.300000 | 0.521512 | 4.01 |
PACU_VAV_TOP | 2.52 | 1.07 | 5.03 | 2.94 | 4.74 | 4.74 | 0.300000 | 0.619199 | 4.74 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.23 |
PACU_VAV_MID_OA_CONTROLLER | 4.01 |
PACU_VAV_TOP_OA_CONTROLLER | 4.74 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.23 | 94713.78 | 0.734673 | 1.41 | 31568.10 | 0.734673 |
PACU_VAV_MID COOLING COIL | 4.01 | 91276.81 | 0.729198 | 1.34 | 30422.56 | 0.729198 |
PACU_VAV_TOP COOLING COIL | 4.74 | 103156.18 | 0.744842 | 1.58 | 34381.95 | 0.744842 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 19009.80 |
PACU_VAV_MID HEATING COIL | 18950.08 |
PACU_VAV_TOP HEATING COIL | 18622.89 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.23 |
PACU_VAV_MID FAN | 4.01 |
PACU_VAV_TOP FAN | 4.74 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9876E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0268E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5034E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5358E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3121E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3378E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1007 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5921E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1122 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9771E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6206E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0413E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9904E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0437E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5066E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5545E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3151E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3510E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4493E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0494E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2883E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8840E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1659E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5527E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7894E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8053E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6401E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6517E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2824E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2868E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9303E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9681E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4705E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5013E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1767E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2002E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7223E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5417E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1120E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1824E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9625E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3066E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9294E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9674E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4691E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4983E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1741E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1911E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8870E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3300E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3808E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0040E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7587E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9122E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7839E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8175E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4043E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4384E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4155E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4331E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1088 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6949E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1209 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.1608E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3084E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9068E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2765E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9482E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1295E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7901E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0446E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4791E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1220E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0325E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4696E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6078E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3197E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2232E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7613E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2607E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2800E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9497E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6778E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8660E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1088 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6943E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1209 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.1601E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3079E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9063E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2764E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9479E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1293E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7899E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0443E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4788E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1221E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0324E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4696E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6077E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3196E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2231E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7613E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2606E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2800E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9496E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6775E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8658E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 31504.02445 | 31504.02445 | 2.35307 | 2.35307 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8701.98302 | 8701.98302 | 0.38759 | 0.42469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26333.70968 | 26333.70968 | 1.96516 | 1.96516 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 15271.99738 | 15271.99738 | 0.67078 | 0.67078 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28250.43209 | 28250.43209 | 2.12893 | 2.12893 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 25995.43085 | 25995.43085 | 1.14635 | 1.14635 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9170.27786 | 9170.27786 | 0.69111 | 0.69111 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.11500 | 1.44727E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12284.96156 | 12284.96156 | 0.54329 | 0.54329 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8849.98219 | 8849.98219 | 0.66697 | 0.66697 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7979.15284 | 7979.15284 | 0.35289 | 0.35289 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10663.15346 | 10663.15346 | 0.80362 | 0.80362 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12189.10223 | 12189.10223 | 0.53904 | 0.53904 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9834.45374 | 9834.45374 | 0.74116 | 0.74116 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8037.03709 | 8037.03709 | 0.35546 | 0.35546 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7198.69621 | 7198.69621 | 0.54251 | 0.54251 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9192.50215 | 9192.50215 | 0.40623 | 0.40623 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7475.87990 | 7475.87990 | 0.56339 | 0.56339 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6016.04220 | 6016.04220 | 0.26589 | 0.26589 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8495.05222 | 8495.05222 | 0.64020 | 0.64020 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9113.37098 | 9113.37098 | 0.40272 | 0.40272 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 7781.15773 | 7781.15773 | 0.58640 | 0.58640 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59500 | 1.44700E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6067.61522 | 6067.61522 | 0.26817 | 0.26817 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7858.97789 | 7858.97789 | 0.59228 | 0.59228 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9726.15042 | 9726.15042 | 0.42986 | 0.42986 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8475.13747 | 8475.13747 | 0.63871 | 0.63871 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6346.37874 | 6346.37874 | 0.28051 | 0.28051 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9338.36925 | 9338.36925 | 0.70377 | 0.70377 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9637.28472 | 9637.28472 | 0.42592 | 0.42592 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 8870.54265 | 8870.54265 | 0.66851 | 0.66851 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6398.61773 | 6398.61773 | 0.28283 | 0.28283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 66686.49 | 4.22793 | 4.22793 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 21151.99 | 1.76771 | 1.76771 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 63569.44 | 4.00739 | 4.00739 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 21103.68 | 2.08990 | 2.08990 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73075.67 | 4.74326 | 4.74326 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 21147.44 | 2.93702 | 2.93702 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.35307 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31850 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63768 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84934 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19623E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20533.98914 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96516 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38137 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63671 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.99025E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21599.77853 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12893 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35203 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63655 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93876 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08228E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 36913.54288 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69111 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22861 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19400 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13408 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60962 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66663E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17494.48755 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66697 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14996 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47051E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39991 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54060E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11363.42493 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80362 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19660 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16700 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13420 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52427 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.93794E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17357.62749 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74116 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13494 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52335E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35985 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82339E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11446.06914 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54251 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29123 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13454 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77660 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30826E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13081.06872 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56339 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17754 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15100 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50721E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47343 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.14605E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8561.83062 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64020 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24678 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13444 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65809 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54386E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12968.06627 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58640 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17056 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14500 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50276E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45482 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23383E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8635.47911 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59228 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26675 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13445 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71134 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42829E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13841.97470 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63871 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41760 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43296E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9032.79175 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70377 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22449 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19100 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13442 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59865 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69715E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13715.08824 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66851 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14961 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49007E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39896 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54663E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9107.38238 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.34278 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07676 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.68556 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76771 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.22793 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.22793 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.41810 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.28421 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07543 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.56842 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.08990 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.00739 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.00739 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.52151 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.51589 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07477 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.03178 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.93702 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.74326 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.74326 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.61920 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.22793 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.00739 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.74326 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.22793 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.22793 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 94713.78460 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73467 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.40917 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31568.10441 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73467 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 19009.79500 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.22793 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.00739 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.00739 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 91276.81272 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72920 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.33566 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30422.56168 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72920 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 18950.07947 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.00739 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.74326 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.74326 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103156.17572 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74484 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58093 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34381.95337 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74484 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 18622.89235 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.74326 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 94239.10 | 321557.15 | 12.01 | 3.06 | 3.44 | 3.63 | 3.78 | 10.45 | 11.74 | 12.37 | 12.89 | 4.7147 | 3.7547 | 2.5278 | 1.0544 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 90871.25 | 310065.58 | 12.04 | 3.07 | 3.45 | 3.64 | 3.78 | 10.48 | 11.77 | 12.41 | 12.91 | 4.4687 | 3.5574 | 2.3946 | 1.0041 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 102532.10 | 349854.04 | 11.94 | 3.05 | 3.42 | 3.60 | 3.77 | 10.41 | 11.67 | 12.30 | 12.85 | 5.2893 | 4.2161 | 2.8383 | 1.1724 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.0933046269E-003 | 6.1235122972E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.7948282856E-002 | 4.6650268339E-002 | Pass | Pass | 0.1072777888 | 0.3010524296 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9328528336E-003 | 5.7063329971E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6573713673E-003 | 5.2149182560E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.4517936041E-003 | 6.7914781170E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.8892409643E-002 | 6.0648795470E-002 | Pass | Pass | 0.1079197755 | 0.3071080321 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.4599029545E-002 | 0.1164162759 | Pass | Pass | 0.2710404295 | 0.8753722846 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.6606112322E-002 | 0.1181328354 | Pass | Pass | 0.2622244945 | 0.8473788559 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.0743637925E-002 | 0.1039020444 | Pass | Pass | 0.2480561421 | 0.7973937875 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.9583678614E-002 | 0.1254998973 | Pass | Pass | 0.2656248462 | 0.8586201325 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3932991424E-002 | 2.2859530234E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.4898683322E-002 | 2.4509113912E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.5312703992E-002 | 2.5492142151E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.4917548995E-002 | 2.3314633004E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.9156813614E-002 | 2.6723128651E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.0476777980E-002 | 2.8664054241E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.0861753812E-002 | 3.0079832336E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.0517547226E-002 | 2.7352670937E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2904.72 | 49.00 | 0.00 | 985.53 | 1476.53 | 5415.78 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.68 | 0.0000 | Y | 4.90 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.40 | 0.0000 | Y | 3.06 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.25 | 0.0000 | Y | 4.80 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.53 | 0.0000 | Y | 3.08 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.61 | 0.0000 | Y | 4.88 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.36 | 0.0000 | Y | 3.05 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.22 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 3.07 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.68 | 0.0000 | Y | 4.90 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.40 | 0.0000 | Y | 3.06 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.25 | 0.0000 | Y | 4.80 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.53 | 0.0000 | Y | 3.08 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 166.86 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 41.77 | 41.77 | 4.25 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.77 | 62.77 | 3.30 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.77 | 47.60 | 26.82 | |
Exterior Lighting Total | 3824.74 | 34.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 94713.78 | 69583.66 | 25130.12 | 0.73 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 91276.81 | 66558.87 | 24717.94 | 0.73 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103156.18 | 76835.10 | 26321.07 | 0.74 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 94239.1 | 3.06 | 10.45 | N/A | N/A | 12.01 | |
PACU_VAV_MID COOLING COIL | 90871.3 | 3.07 | 10.48 | N/A | N/A | 12.04 | |
PACU_VAV_TOP COOLING COIL | 102532.1 | 3.05 | 10.41 | N/A | N/A | 11.94 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20533.99 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21599.78 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 36913.54 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17494.49 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11363.42 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17357.63 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11446.07 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13081.07 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8561.83 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12968.07 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8635.48 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13841.97 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9032.79 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13715.09 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9107.38 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 19009.80 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 18950.08 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 18622.89 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.23 | 9254.98 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.01 | 8772.22 | 2189.01 | 1.00 | 1.15 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.74 | 10383.05 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 94239.10 | 3.06 | 10.45 | 12.01 | 4.7147 | 3.44 | 11.74 | 3.7547 | 3.63 | 12.37 | 2.5278 | 3.78 | 12.89 | 1.0544 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 90871.25 | 3.07 | 10.48 | 12.04 | 4.4687 | 3.45 | 11.77 | 3.5574 | 3.64 | 12.41 | 2.3946 | 3.78 | 12.91 | 1.0041 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102532.10 | 3.05 | 10.41 | 11.94 | 5.2893 | 3.42 | 11.67 | 4.2161 | 3.60 | 12.30 | 2.8383 | 3.77 | 12.85 | 1.1724 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 31504.02 | 31504.02 | 32.03 | 2.353 | 2.353 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_MID | 26333.71 | 26333.71 | 26.77 | 1.965 | 1.965 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_TOP | 28250.43 | 28250.43 | 28.72 | 2.129 | 2.129 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00892 | 34.02 | 0.01447 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9170.28 | 9170.28 | 44.23 | 0.691 | 0.691 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00900 | 34.12 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8849.98 | 8849.98 | 67.42 | 0.667 | 0.667 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00884 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10663.15 | 10663.15 | 51.43 | 0.804 | 0.804 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00893 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9834.45 | 9834.45 | 74.93 | 0.741 | 0.741 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00881 | 32.91 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7198.70 | 7198.70 | 34.72 | 0.543 | 0.543 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00900 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7475.88 | 7475.88 | 56.95 | 0.563 | 0.563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00882 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8495.05 | 8495.05 | 40.97 | 0.640 | 0.640 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00893 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7781.16 | 7781.16 | 59.28 | 0.586 | 0.586 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00880 | 32.59 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7858.98 | 7858.98 | 37.90 | 0.592 | 0.592 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00904 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8475.14 | 8475.14 | 64.57 | 0.639 | 0.639 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00883 | 31.03 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9338.37 | 9338.37 | 45.04 | 0.704 | 0.704 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00896 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8870.54 | 8870.54 | 67.58 | 0.669 | 0.669 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00881 | 32.75 | 0.01447 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8701.98 | 8701.98 | 8.85 | 0.388 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_MID | 15272.00 | 15272.00 | 15.53 | 0.671 | 0.671 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_TOP | 25995.43 | 25995.43 | 26.43 | 1.146 | 1.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12284.96 | 12284.96 | 59.25 | 0.543 | 0.543 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7979.15 | 7979.15 | 60.79 | 0.353 | 0.353 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12189.10 | 12189.10 | 58.79 | 0.539 | 0.539 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8037.04 | 8037.04 | 61.23 | 0.355 | 0.355 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9192.50 | 9192.50 | 44.34 | 0.406 | 0.406 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6016.04 | 6016.04 | 45.83 | 0.266 | 0.266 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9113.37 | 9113.37 | 43.95 | 0.403 | 0.403 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6067.62 | 6067.62 | 46.23 | 0.268 | 0.268 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9726.15 | 9726.15 | 46.91 | 0.430 | 0.430 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6346.38 | 6346.38 | 48.35 | 0.281 | 0.281 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9637.28 | 9637.28 | 46.48 | 0.426 | 0.426 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6398.62 | 6398.62 | 48.75 | 0.283 | 0.283 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -6.30 | 0.00230 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.23 | 4.23 | 1.77 | 1.77 | 4.2279 | 1.7677 | 4.2279 | 0.4181 | 0.3000 |
PACU_VAV_MID | 4.01 | 4.01 | 2.09 | 2.09 | 4.0074 | 2.0899 | 4.0074 | 0.5215 | 0.3000 |
PACU_VAV_TOP | 4.74 | 4.74 | 2.94 | 2.94 | 4.7433 | 2.9370 | 4.7433 | 0.6192 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20533.989 | 20533.989 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 20533.99 | 13675.49 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 8701.98 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21599.779 | 21599.779 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21599.78 | 21599.78 | 0.670779 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 15272.00 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 36913.543 | 36913.543 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36913.54 | 36913.54 | 1.146347 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 25995.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17494.488 | 17494.488 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17494.49 | 17494.49 | 0.543290 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755984 | 47.1582 | 12284.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11363.425 | 11363.425 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11363.42 | 11363.42 | 0.352890 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755000 | 47.0978 | 7979.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17357.627 | 17357.627 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17357.63 | 17357.63 | 0.539040 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755639 | 47.1370 | 12189.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11446.069 | 11446.069 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11446.07 | 11446.07 | 0.355457 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00755318 | 47.1174 | 8037.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13081.069 | 13081.069 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13081.07 | 13081.07 | 0.406231 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00762818 | 47.5777 | 9192.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8561.831 | 8561.831 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8561.83 | 8561.83 | 0.265887 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00763217 | 47.6022 | 6016.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12968.066 | 12968.066 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12968.07 | 12968.07 | 0.402722 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00762184 | 47.5387 | 9113.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8635.479 | 8635.479 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8635.48 | 8635.48 | 0.268174 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00763773 | 47.6365 | 6067.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 13841.975 | 13841.975 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13841.97 | 13841.97 | 0.429861 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751621 | 46.8889 | 9726.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9032.792 | 9032.792 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9032.79 | 9032.79 | 0.280513 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751139 | 46.8593 | 6346.38 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 13715.088 | 13715.088 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13715.09 | 13715.09 | 0.425921 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751060 | 46.8544 | 9637.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9107.382 | 9107.382 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9107.38 | 9107.38 | 0.282829 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00751614 | 46.8886 | 6398.62 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 94713.785 | 69583.661 | 4.227930 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 94976.31 | 74489.93 | 4.227930 | 26.36 | 18.19 | 0.01018529 | 10.96 | 10.96 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 22.6139 | 24.00 | 0.00892782 | 46.3082 | 55949.81 | 0.00 | 97662.63 | 69569.84 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 19009.795 | 19009.795 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19009.80 | 19009.80 | 1.268379 | -0.05 | -0.63 | 0.00350501 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 75.3797 | 19.37 | 0.00661244 | 45.6737 | 14220.35 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 91276.813 | 66558.874 | 4.007392 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 91874.28 | 71078.36 | 4.007392 | 26.47 | 18.32 | 0.01030600 | 10.96 | 10.96 | 0.00850000 | 34.30 | 0.01447309 | 23.52 | 23.8584 | 24.00 | 0.00899104 | 46.6319 | 52891.23 | 0.00 | 94118.65 | 66569.96 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 18950.079 | 18950.079 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18950.08 | 18950.08 | 1.202218 | -0.71 | -1.21 | 0.00335991 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 79.5280 | 17.83 | 0.00732560 | 55.6903 | 16239.99 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 103156.176 | 76835.104 | 4.743260 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 103175.22 | 81972.47 | 4.743260 | 26.04 | 17.98 | 0.01005288 | 10.96 | 10.96 | 0.00850000 | 34.12 | 0.01447274 | 23.47 | 20.1570 | 24.00 | 0.00893308 | 46.3357 | 62761.98 | 0.00 | 106367.86 | 76765.18 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 18622.892 | 18622.892 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18622.89 | 18622.89 | 1.422978 | 1.58 | 0.93 | 0.00392502 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 67.1901 | 17.41 | 0.00691316 | 53.9979 | 19095.05 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20533.989 | 20533.989 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 20533.99 | 13675.49 | 1.0000 | 0.49305639 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20533.99 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.03 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 8701.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21599.779 | 21599.779 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21599.78 | 21599.78 | 1.0000 | 0.77875892 | 0.670779 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21599.78 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 15272.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 36913.543 | 36913.543 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36913.54 | 36913.54 | 1.0000 | 1.33088174 | 1.146347 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36913.54 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 25995.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17494.488 | 17494.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17494.49 | 17494.49 | 1.0000 | 0.63074666 | 0.543290 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17494.49 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755984 | 21.00 | 0.00755984 | 47.1582 | 12284.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11363.425 | 11363.425 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11363.42 | 11363.42 | 1.0000 | 0.40969719 | 0.352890 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11363.42 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755000 | 21.00 | 0.00755000 | 47.0978 | 7979.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17357.627 | 17357.627 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17357.63 | 17357.63 | 1.0000 | 0.62581231 | 0.539040 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17357.63 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755639 | 21.00 | 0.00755639 | 47.1370 | 12189.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11446.069 | 11446.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11446.07 | 11446.07 | 1.0000 | 0.41267684 | 0.355457 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11446.07 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755318 | 21.00 | 0.00755318 | 47.1174 | 8037.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13081.069 | 13081.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13081.07 | 13081.07 | 1.0000 | 0.47162516 | 0.406231 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13081.07 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00762818 | 21.00 | 0.00762818 | 47.5777 | 9192.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8561.831 | 8561.831 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8561.83 | 8561.83 | 1.0000 | 0.30868844 | 0.265887 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8561.83 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763217 | 21.00 | 0.00763217 | 47.6022 | 6016.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12968.066 | 12968.066 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12968.07 | 12968.07 | 1.0000 | 0.46755096 | 0.402722 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12968.07 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00762184 | 21.00 | 0.00762184 | 47.5387 | 9113.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8635.479 | 8635.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8635.48 | 8635.48 | 1.0000 | 0.31134377 | 0.268174 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8635.48 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00763773 | 21.00 | 0.00763773 | 47.6365 | 6067.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13841.975 | 13841.975 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13841.97 | 13841.97 | 1.0000 | 0.49905888 | 0.429861 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13841.97 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751621 | 21.00 | 0.00751621 | 46.8889 | 9726.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9032.792 | 9032.792 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9032.79 | 9032.79 | 1.0000 | 0.32566849 | 0.280513 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9032.79 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751139 | 21.00 | 0.00751139 | 46.8593 | 6346.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13715.088 | 13715.088 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13715.09 | 13715.09 | 1.0000 | 0.49448411 | 0.425921 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13715.09 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751060 | 21.00 | 0.00751060 | 46.8544 | 9637.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9107.382 | 9107.382 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9107.38 | 9107.38 | 1.0000 | 0.32835778 | 0.282829 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9107.38 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751614 | 21.00 | 0.00751614 | 46.8886 | 6398.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 94713.785 | 69583.661 | 4.227930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7740 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.227930 | 4.90852700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 94976.31 | 74489.93 | 1.0028 | 4.90852700 | 4.227930 | 26.36 | 18.19 | 0.01018529 | 52456.6 | 10.96 | 10.96 | 0.00850000 | 32442.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9254.984 | 85721.32 | 34.40 | 0.01447326 | 23.54 | 0.95610000 | 22.6139 | 24.00 | 0.00892782 | 24.00 | 0.00892782 | 46.3082 | 55949.81 | 0.00 | 97662.63 | 69569.84 | 4.71467729 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.22 | 12.21 | 0.00884843 | 34607.8 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19009.795 | 19009.795 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.227930 | 4.90852700 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19009.80 | 19009.80 | 1.0000 | 1.47255810 | 1.268379 | -0.05 | -0.63 | 0.00350501 | 8718.3 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19009.80 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 75.3797 | 19.10 | 0.00720114 | 19.37 | 0.00661244 | 45.6737 | 14220.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 91276.813 | 66558.874 | 4.007392 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9983 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.007392 | 4.65248782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 91874.28 | 71078.36 | 1.0065 | 4.65248782 | 4.007392 | 26.47 | 18.32 | 0.01030600 | 52880.5 | 10.96 | 10.96 | 0.00850000 | 32442.9 | -999.0 | -999.00 | -999.00 | -999.00 | 8772.225 | 83102.06 | 34.30 | 0.01447309 | 23.52 | 0.95610000 | 23.8584 | 24.00 | 0.00899104 | 24.00 | 0.00899104 | 46.6319 | 52891.23 | 0.00 | 94118.65 | 66569.96 | 4.46874972 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.08 | 12.07 | 0.00876760 | 34260.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18950.079 | 18950.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.007392 | 4.65248782 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18950.08 | 18950.08 | 1.0000 | 1.39574635 | 1.202218 | -0.71 | -1.21 | 0.00335991 | 7683.7 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18950.08 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 79.5280 | 21.00 | 0.00748593 | 17.83 | 0.00732560 | 55.6903 | 16239.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103156.176 | 76835.104 | 4.743260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5278 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.743260 | 5.50681390 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 103175.22 | 81972.47 | 1.0002 | 5.50681390 | 4.743260 | 26.04 | 17.98 | 0.01005288 | 51797.7 | 10.96 | 10.96 | 0.00850000 | 32442.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10383.049 | 92792.17 | 34.12 | 0.01447274 | 23.47 | 0.95610000 | 20.1570 | 24.00 | 0.00893308 | 24.00 | 0.00893308 | 46.3357 | 62761.98 | 0.00 | 106367.86 | 76765.18 | 5.28933638 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.46 | 12.45 | 0.00899033 | 35212.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18622.892 | 18622.892 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.743260 | 5.50681390 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18622.89 | 18622.89 | 1.0000 | 1.65204417 | 1.422978 | 1.58 | 0.93 | 0.00392502 | 11417.3 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18622.89 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 67.1901 | 17.72 | 0.00725735 | 17.41 | 0.00691316 | 53.9979 | 19095.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.23 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.01 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2547.83 | 2506.67 | 138.83 |
CORE_MID | 2481.17 | 3139.83 | 447.50 |
CORE_TOP | 2807.17 | 3344.83 | 853.17 |
PERIMETER_TOP_ZN_3 | 3509.33 | 3549.33 | 1538.50 |
PERIMETER_TOP_ZN_2 | 3578.17 | 3286.00 | 1390.17 |
PERIMETER_TOP_ZN_1 | 3327.67 | 3057.00 | 1102.50 |
PERIMETER_TOP_ZN_4 | 3566.50 | 3318.50 | 1419.33 |
PERIMETER_BOT_ZN_3 | 3101.00 | 3650.33 | 1223.33 |
PERIMETER_BOT_ZN_2 | 3237.00 | 3216.83 | 1000.17 |
PERIMETER_BOT_ZN_1 | 3023.83 | 3422.17 | 1041.17 |
PERIMETER_BOT_ZN_4 | 3243.83 | 3236.67 | 1029.33 |
PERIMETER_MID_ZN_3 | 3309.17 | 3384.83 | 1222.67 |
PERIMETER_MID_ZN_2 | 2868.83 | 2744.67 | 1008.83 |
PERIMETER_MID_ZN_1 | 3193.17 | 2826.67 | 802.83 |
PERIMETER_MID_ZN_4 | 3419.67 | 3146.67 | 1121.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4442.00 | 4300.83 | 2016.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 2.00 | 0.00 | 2.00 | 0.00 |
CORE_TOP | 3.17 | 0.00 | 2.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 36.00 | 8.17 | 18.33 | 5.17 |
PERIMETER_TOP_ZN_2 | 21.33 | 38.83 | 4.17 | 34.50 |
PERIMETER_TOP_ZN_1 | 17.50 | 27.50 | 5.67 | 24.00 |
PERIMETER_TOP_ZN_4 | 20.17 | 39.50 | 5.67 | 22.33 |
PERIMETER_BOT_ZN_3 | 6.67 | 0.00 | 6.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.83 | 15.50 | 0.33 | 15.50 |
PERIMETER_BOT_ZN_1 | 152.33 | 60.00 | 151.83 | 60.00 |
PERIMETER_BOT_ZN_4 | 0.83 | 21.00 | 0.33 | 11.33 |
PERIMETER_MID_ZN_3 | 9.83 | 1.17 | 6.17 | 0.83 |
PERIMETER_MID_ZN_2 | 4.83 | 28.33 | 1.33 | 27.67 |
PERIMETER_MID_ZN_1 | 2.50 | 17.17 | 1.50 | 16.83 |
PERIMETER_MID_ZN_4 | 4.67 | 31.00 | 1.50 | 18.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 185.17 | 173.00 | 163.83 | 146.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.576 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.513 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.510 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.591 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.737 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.738 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.741 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.534 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.668 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.677 | 0.841 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.653 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.585 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.674 | 0.078 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.741 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.732 | 0.074 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 9085923.28 | 0.00 | 9085923.28 | 0.00 | 9085923.28 | 13393058.27 | 5493.66 | 273.39 | 2992.95 | 13.23 |
CORE_MID | 8121332.90 | 0.00 | 8121332.90 | 0.00 | 8121332.90 | 13393058.27 | 5879.60 | 450.33 | 2430.07 | 38.76 |
CORE_TOP | 8098876.66 | 0.00 | 8098876.66 | 0.00 | 8098876.66 | 13393058.27 | 5925.40 | 455.44 | 2379.15 | 118.35 |
PERIMETER_TOP_ZN_3 | 1978152.39 | 0.00 | 1978152.39 | 563886.35 | 2542038.74 | 2823374.22 | 4451.09 | 436.01 | 3872.90 | 118.35 |
PERIMETER_TOP_ZN_2 | 1557182.97 | 0.00 | 1557182.97 | 375921.98 | 1933104.95 | 1787429.43 | 4376.51 | 481.95 | 3901.54 | 118.35 |
PERIMETER_TOP_ZN_1 | 2463364.49 | 0.00 | 2463364.49 | 563886.35 | 3027250.84 | 2823374.22 | 4442.58 | 413.18 | 3904.24 | 118.35 |
PERIMETER_TOP_ZN_4 | 1566507.00 | 0.00 | 1566507.00 | 375921.98 | 1942428.97 | 1787312.18 | 4386.72 | 276.56 | 4096.73 | 118.35 |
PERIMETER_BOT_ZN_3 | 1781250.06 | 0.00 | 1781250.06 | 299816.06 | 2081066.12 | 2823374.22 | 5255.69 | 312.57 | 3191.74 | 13.23 |
PERIMETER_BOT_ZN_2 | 1405205.17 | 0.00 | 1405205.17 | 199876.17 | 1605081.34 | 1787429.43 | 4519.01 | 271.48 | 3969.51 | 13.23 |
PERIMETER_BOT_ZN_1 | 2253714.63 | 0.00 | 2253714.63 | 2951634.14 | 5205348.78 | 2823374.22 | 4696.65 | 250.01 | 3813.34 | 13.23 |
PERIMETER_BOT_ZN_4 | 1373559.06 | 0.00 | 1373559.06 | 199876.17 | 1573435.23 | 1787312.18 | 4621.14 | 302.04 | 3836.82 | 13.23 |
PERIMETER_MID_ZN_3 | 1951422.65 | 0.00 | 1951422.65 | 469392.62 | 2420815.27 | 2823374.22 | 4462.42 | 353.10 | 3944.48 | 38.76 |
PERIMETER_MID_ZN_2 | 1416109.73 | 0.00 | 1416109.73 | 312926.53 | 1729036.26 | 1601953.02 | 4315.56 | 327.94 | 4116.49 | 947.76 |
PERIMETER_MID_ZN_1 | 2465233.79 | 0.00 | 2465233.79 | 469392.62 | 2934626.41 | 2823374.22 | 4391.10 | 328.73 | 4040.17 | 38.76 |
PERIMETER_MID_ZN_4 | 1541602.85 | 0.00 | 1541602.85 | 312926.53 | 1854529.38 | 1787312.18 | 4397.15 | 412.56 | 3950.29 | 38.76 |
Total Facility | 47059437.61 | 0.00 | 47059437.61 | 7095457.52 | 54154895.13 | 67658168.57 | 6321.60 | 1061.55 | 4466.36 | 1033.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.4242 | 0.0000 | 0.4242 | 0.0000 | 0.4242 | 0.4247 | 2677.49 | 273.39 | 2992.12 |
CORE_MID | 0.3783 | 0.0000 | 0.3783 | 0.0000 | 0.3783 | 0.4247 | 3066.27 | 450.33 | 2426.40 |
CORE_TOP | 0.3763 | 0.0000 | 0.3763 | 0.0000 | 0.3763 | 0.4247 | 3114.24 | 455.44 | 2373.32 |
PERIMETER_TOP_ZN_3 | 0.0919 | 0.0000 | 0.0919 | 0.0131 | 0.1050 | 0.0895 | 1639.92 | 436.01 | 3867.07 |
PERIMETER_TOP_ZN_2 | 0.0725 | 0.0000 | 0.0725 | 0.0087 | 0.0812 | 0.0567 | 1565.56 | 481.95 | 3895.49 |
PERIMETER_TOP_ZN_1 | 0.1146 | 0.0000 | 0.1146 | 0.0131 | 0.1277 | 0.0895 | 1631.42 | 413.18 | 3898.41 |
PERIMETER_TOP_ZN_4 | 0.0729 | 0.0000 | 0.0729 | 0.0087 | 0.0816 | 0.0567 | 1575.83 | 276.53 | 4090.64 |
PERIMETER_BOT_ZN_3 | 0.0831 | 0.0000 | 0.0831 | 0.0069 | 0.0901 | 0.0895 | 2439.65 | 312.55 | 3190.80 |
PERIMETER_BOT_ZN_2 | 0.0656 | 0.0000 | 0.0656 | 0.0046 | 0.0702 | 0.0567 | 1703.22 | 271.48 | 3968.30 |
PERIMETER_BOT_ZN_1 | 0.1052 | 0.0000 | 0.1052 | 0.1309 | 0.2361 | 0.0895 | 1880.53 | 250.01 | 3812.46 |
PERIMETER_BOT_ZN_4 | 0.0641 | 0.0000 | 0.0641 | 0.0046 | 0.0688 | 0.0567 | 1805.28 | 302.04 | 3835.69 |
PERIMETER_MID_ZN_3 | 0.0909 | 0.0000 | 0.0909 | 0.0109 | 0.1018 | 0.0895 | 1649.28 | 353.08 | 3940.64 |
PERIMETER_MID_ZN_2 | 0.0662 | 0.0000 | 0.0662 | 0.0077 | 0.0739 | 0.0567 | 1503.01 | 327.85 | 3203.15 |
PERIMETER_MID_ZN_1 | 0.1149 | 0.0000 | 0.1149 | 0.0109 | 0.1258 | 0.0895 | 1578.08 | 328.69 | 4036.23 |
PERIMETER_MID_ZN_4 | 0.0719 | 0.0000 | 0.0719 | 0.0073 | 0.0791 | 0.0567 | 1584.50 | 412.53 | 3945.97 |
Total Facility | 2.1927 | 0.0000 | 2.1927 | 0.2274 | 2.4200 | 2.1513 | 3504.94 | 1061.34 | 4458.29 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21430576.41 | 0.00 | 21430576.41 | 22614548.33 | 4238.41 | 3.18 | 4518.41 | 13.23 |
PACU_VAV_MID | 20886169.09 | 0.00 | 20886169.09 | 22429071.92 | 4228.09 | 2.79 | 4529.12 | 38.76 |
PACU_VAV_TOP | 21112927.25 | 0.00 | 21112927.25 | 22614548.33 | 4259.52 | 0.73 | 4499.75 | 118.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.0005 | 0.0000 | 1.0005 | 0.7171 | 1422.31 | 3.18 | 4517.51 |
PACU_VAV_MID | 0.9731 | 0.0000 | 0.9731 | 0.7084 | 1414.91 | 2.79 | 4525.30 |
PACU_VAV_TOP | 0.9814 | 0.0000 | 0.9814 | 0.7171 | 1448.35 | 0.73 | 4493.92 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 128.05 | 2061.31 | 0.00 | 0.00 | 0.00 | 2389.03 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 155.23 | 2063.87 | 0.00 | 0.00 | 0.00 | 2397.80 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 92.13 | 2142.51 | 0.00 | 0.00 | 0.00 | 2480.98 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2161 | 1.5972 | 0.0000 | 0.0000 | 0.0000 | 1.0546 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2167 | 1.5236 | 0.0000 | 0.0000 | 0.0000 | 1.0469 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2240 | 1.5346 | 0.0000 | 0.0000 | 0.0000 | 1.0545 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2232 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1327.29 | 11240.73 | 04-JUL-17:20 | 223625.88 | 02-JAN-07:10 |
Electricity:Building | 814.61 | 11072.20 | 23-APR-17:10 | 58092.18 | 30-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 814.61 | 11072.20 | 23-APR-17:10 | 58092.18 | 30-OCT-07:10 |
InteriorLights:Electricity | 166.86 | 772.31 | 01-JAN-11:00 | 17654.39 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 166.86 | 772.31 | 01-JAN-11:00 | 17654.39 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 166.86 | 772.31 | 01-JAN-11:00 | 17654.39 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 166.86 | 772.31 | 01-JAN-11:00 | 17654.39 | 30-OCT-07:10 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.23 | 405.59 | 12-MAR-17:10 | 2168.90 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.90 | 19.49 | 01-JAN-11:00 | 733.65 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.90 | 19.49 | 01-JAN-11:00 | 733.65 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.46 | 256.76 | 23-APR-17:10 | 1373.02 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 464.45 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 464.45 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.13 | 405.59 | 12-MAR-17:10 | 2168.89 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.80 | 19.49 | 01-JAN-09:10 | 733.65 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.80 | 19.49 | 01-JAN-09:10 | 733.65 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.48 | 256.75 | 26-FEB-18:10 | 1372.98 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.08 | 12.34 | 01-JAN-10:50 | 464.42 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.08 | 12.34 | 01-JAN-10:50 | 464.42 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.21 | 405.59 | 12-MAR-17:10 | 2168.83 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.88 | 19.49 | 01-JAN-10:50 | 733.58 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.88 | 19.49 | 01-JAN-10:50 | 733.58 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.46 | 256.76 | 23-APR-17:10 | 1372.99 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.05 | 12.34 | 01-JAN-09:00 | 464.41 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.05 | 12.34 | 01-JAN-09:00 | 464.41 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.12 | 405.59 | 12-MAR-17:10 | 2168.82 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.79 | 19.49 | 01-JAN-09:10 | 733.58 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.79 | 19.49 | 01-JAN-09:10 | 733.58 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.48 | 256.75 | 20-FEB-18:10 | 1372.95 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.07 | 12.34 | 01-JAN-10:40 | 464.38 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.07 | 12.34 | 01-JAN-10:40 | 464.38 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.23 | 405.59 | 12-MAR-17:10 | 2168.90 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.90 | 19.49 | 01-JAN-11:00 | 733.65 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.90 | 19.49 | 01-JAN-11:00 | 733.65 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.46 | 256.76 | 23-APR-17:10 | 1373.02 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 464.45 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 464.45 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.13 | 405.59 | 12-MAR-17:10 | 2168.89 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.80 | 19.49 | 01-JAN-09:10 | 733.65 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.80 | 19.49 | 01-JAN-09:10 | 733.65 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.48 | 256.75 | 26-FEB-18:10 | 1372.98 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.08 | 12.34 | 01-JAN-10:50 | 464.42 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.08 | 12.34 | 01-JAN-10:50 | 464.42 | 30-OCT-07:10 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 157.23 | -0.00 | 01-FEB-08:00 | 26293.87 | 06-APR-12:40 |
ElectricityProduced:Plant | 157.23 | -0.00 | 01-FEB-08:00 | 26293.87 | 06-APR-12:40 |
Photovoltaic:ElectricityProduced | 164.23 | 0.00 | 01-JAN-00:10 | 27383.78 | 06-APR-12:40 |
PowerConversion:ElectricityProduced | -7.01 | -1089.91 | 06-APR-12:40 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 478.15 | 168.34 | 01-JAN-00:10 | 195557.50 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.76 | 30-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.76 | 30-OCT-07:20 |
ElectricityPurchased:Facility | 1171.46 | 0.00 | 15-JAN-11:00 | 223625.88 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1171.46 | 0.00 | 15-JAN-11:00 | 223625.88 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1171.46 | 0.00 | 15-JAN-11:00 | 223625.88 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1171.46 | 0.00 | 15-JAN-11:00 | 223625.88 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 1.41 | 0.00 | 01-JAN-00:10 | 11645.16 | 09-APR-12:30 |
ElectricitySurplusSold:Plant | 1.41 | 0.00 | 01-JAN-00:10 | 11645.16 | 09-APR-12:30 |
Cogeneration:ElectricitySurplusSold | 1.41 | 0.00 | 01-JAN-00:10 | 11645.16 | 09-APR-12:30 |
General:Cogeneration:ElectricitySurplusSold | 1.41 | 0.00 | 01-JAN-00:10 | 11645.16 | 09-APR-12:30 |
ElectricityNet:Facility | 1170.06 | -11645.16 | 09-APR-12:30 | 223625.88 | 02-JAN-07:10 |
ElectricityNet:Plant | 1170.06 | -11645.16 | 09-APR-12:30 | 223625.88 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1170.06 | -11645.16 | 09-APR-12:30 | 223625.88 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1170.06 | -11645.16 | 09-APR-12:30 | 223625.88 | 02-JAN-07:10 |
Heating:Electricity | 119.55 | 0.00 | 01-JAN-00:10 | 189631.84 | 02-JAN-07:10 |
General:Heating:Electricity | 119.55 | 0.00 | 01-JAN-00:10 | 189631.84 | 02-JAN-07:10 |
Fans:Electricity | 60.60 | 0.00 | 01-JAN-00:10 | 13159.34 | 02-AUG-15:40 |
General:Fans:Electricity | 60.60 | 0.00 | 01-JAN-00:10 | 13159.34 | 02-AUG-15:40 |
ExteriorLights:Electricity | 34.38 | 0.00 | 01-JAN-07:50 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.38 | 0.00 | 01-JAN-07:50 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 286.38 | 0.00 | 01-JAN-00:10 | 68964.38 | 07-JUL-16:00 |
General:Cooling:Electricity | 286.38 | 0.00 | 01-JAN-00:10 | 68964.38 | 07-JUL-16:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 4.69 | 0.00 | 01-JAN-00:10 | 496.09 | 30-OCT-07:20 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 163.31 | 1886.44 | 05-JAN-06:10 | 73758.87 | 03-FEB-07:30 |
NaturalGas:HVAC | 38.76 | 0.00 | 01-JAN-00:10 | 64896.15 | 03-FEB-07:30 |
Heating:NaturalGas | 38.76 | 0.00 | 01-JAN-00:10 | 64896.15 | 03-FEB-07:30 |
General:Heating:NaturalGas | 38.76 | 0.00 | 01-JAN-00:10 | 64896.15 | 03-FEB-07:30 |
NaturalGas:Plant | 124.54 | 1886.44 | 02-JAN-08:10 | 10021.07 | 06-FEB-12:10 |
WaterSystems:NaturalGas | 124.54 | 1886.44 | 02-JAN-08:10 | 10021.07 | 06-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 124.54 | 1886.44 | 02-JAN-08:10 | 10021.07 | 06-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2447.73 | 0.00 | 01-JAN-00:10 | 387403.77 | 07-JUL-16:00 |
EnergyTransfer:Building | 1070.56 | 0.00 | 01-JAN-00:10 | 154231.05 | 02-JAN-06:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 189.50 | 0.00 | 01-JAN-00:10 | 21432.22 | 21-AUG-08:00 |
Heating:EnergyTransfer | 79.61 | 0.00 | 01-JAN-00:10 | 153923.25 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.12 | 0.00 | 01-JAN-00:10 | 10428.12 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 79.61 | 0.00 | 01-JAN-00:10 | 153923.25 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.12 | 0.00 | 01-JAN-00:10 | 10428.12 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 990.95 | 0.00 | 01-JAN-00:10 | 146605.99 | 02-AUG-15:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 189.38 | 0.00 | 01-JAN-00:10 | 21432.22 | 21-AUG-08:00 |
General:Cooling:EnergyTransfer | 990.95 | 0.00 | 01-JAN-00:10 | 146605.99 | 02-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 189.38 | 0.00 | 01-JAN-00:10 | 21432.22 | 21-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 44.51 | 0.00 | 01-JAN-00:10 | 13350.27 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.11 | 0.00 | 01-JAN-00:10 | 13350.27 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.11 | 0.00 | 01-JAN-00:10 | 13350.27 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 32.41 | 0.00 | 01-JAN-00:10 | 9963.77 | 01-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 32.41 | 0.00 | 01-JAN-00:10 | 9963.77 | 01-AUG-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.86 | 0.00 | 01-JAN-00:10 | 7168.51 | 09-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.04 | 0.00 | 01-JAN-00:10 | 7168.51 | 09-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.04 | 0.00 | 01-JAN-00:10 | 7168.51 | 09-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.82 | 0.00 | 01-JAN-00:10 | 4187.09 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.82 | 0.00 | 01-JAN-00:10 | 4187.09 | 10-JUL-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.70 | 0.00 | 01-JAN-00:10 | 4726.15 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.26 | 0.00 | 01-JAN-00:10 | 4726.15 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.26 | 0.00 | 01-JAN-00:10 | 4726.15 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.44 | 0.00 | 01-JAN-00:10 | 4113.07 | 10-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.44 | 0.00 | 01-JAN-00:10 | 4113.07 | 10-JUL-15:50 |
EnergyTransfer:Zone:CORE_MID | 155.19 | 0.00 | 01-JAN-00:10 | 17494.36 | 21-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.05 | 0.00 | 01-JAN-00:10 | 15393.45 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.05 | 0.00 | 01-JAN-00:10 | 15393.45 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 154.15 | 0.00 | 01-JAN-00:10 | 17494.36 | 21-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 154.15 | 0.00 | 01-JAN-00:10 | 17494.36 | 21-AUG-07:20 |
EnergyTransfer:Zone:CORE_TOP | 155.61 | 0.00 | 01-JAN-00:10 | 27716.49 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.84 | 0.00 | 01-JAN-00:10 | 27716.49 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.84 | 0.00 | 01-JAN-00:10 | 27716.49 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 150.77 | 0.00 | 01-JAN-00:10 | 19088.03 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 150.77 | 0.00 | 01-JAN-00:10 | 19088.03 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.25 | 0.00 | 01-JAN-00:10 | 9329.41 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.82 | 0.00 | 01-JAN-00:10 | 9329.41 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.82 | 0.00 | 01-JAN-00:10 | 9329.41 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.43 | 0.00 | 01-JAN-00:10 | 7029.85 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.43 | 0.00 | 01-JAN-00:10 | 7029.85 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.74 | 0.00 | 01-JAN-00:10 | 8010.61 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.48 | 0.00 | 01-JAN-00:10 | 8010.61 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.48 | 0.00 | 01-JAN-00:10 | 8010.61 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 32.26 | 0.00 | 01-JAN-00:10 | 7985.18 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 32.26 | 0.00 | 01-JAN-00:10 | 7985.18 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 54.57 | 0.00 | 01-JAN-00:10 | 10712.75 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.45 | 0.00 | 01-JAN-00:10 | 10233.64 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.45 | 0.00 | 01-JAN-00:10 | 10233.64 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 49.12 | 0.00 | 01-JAN-00:10 | 10712.75 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 49.12 | 0.00 | 01-JAN-00:10 | 10712.75 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.79 | 0.00 | 01-JAN-00:10 | 8152.28 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.15 | 0.00 | 01-JAN-00:10 | 8152.28 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.15 | 0.00 | 01-JAN-00:10 | 8152.28 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.64 | 0.00 | 01-JAN-00:10 | 8062.23 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.64 | 0.00 | 01-JAN-00:10 | 8062.23 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 36.61 | 0.00 | 01-JAN-00:10 | 6944.24 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.35 | 0.00 | 01-JAN-00:10 | 6944.24 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.35 | 0.00 | 01-JAN-00:10 | 6944.24 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.26 | 0.00 | 01-JAN-00:10 | 5671.93 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.26 | 0.00 | 01-JAN-00:10 | 5671.93 | 10-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.37 | 0.00 | 01-JAN-00:10 | 6573.45 | 07-AUG-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.98 | 0.00 | 01-JAN-00:10 | 5730.69 | 13-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.98 | 0.00 | 01-JAN-00:10 | 5730.69 | 13-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.39 | 0.00 | 01-JAN-00:10 | 6573.45 | 07-AUG-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.39 | 0.00 | 01-JAN-00:10 | 6573.45 | 07-AUG-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 52.91 | 0.00 | 01-JAN-00:10 | 10022.14 | 03-FEB-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 9.29 | 0.00 | 01-JAN-00:10 | 10022.14 | 03-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 9.29 | 0.00 | 01-JAN-00:10 | 10022.14 | 03-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 43.62 | 0.00 | 01-JAN-00:10 | 9868.80 | 18-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 43.62 | 0.00 | 01-JAN-00:10 | 9868.80 | 18-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 0.00 | 01-JAN-00:10 | 6481.69 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.17 | 0.00 | 01-JAN-00:10 | 5589.16 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.17 | 0.00 | 01-JAN-00:10 | 5589.16 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.15 | 0.00 | 01-JAN-00:10 | 6481.69 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.15 | 0.00 | 01-JAN-00:10 | 6481.69 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.59 | 0.00 | 01-JAN-00:10 | 7558.61 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.40 | 0.00 | 01-JAN-00:10 | 7558.61 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.40 | 0.00 | 01-JAN-00:10 | 7558.61 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 36.19 | 0.00 | 01-JAN-00:10 | 6244.62 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 36.19 | 0.00 | 01-JAN-00:10 | 6244.62 | 10-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.19 | 0.00 | 01-JAN-00:10 | 7766.12 | 07-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.20 | 0.00 | 01-JAN-00:10 | 6250.41 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.20 | 0.00 | 01-JAN-00:10 | 6250.41 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.99 | 0.00 | 01-JAN-00:10 | 7766.12 | 07-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.99 | 0.00 | 01-JAN-00:10 | 7766.12 | 07-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.36 | 0.00 | 01-JAN-00:10 | 9625.99 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.43 | 0.00 | 01-JAN-00:10 | 8576.73 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.43 | 0.00 | 01-JAN-00:10 | 8576.73 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.93 | 0.00 | 01-JAN-00:10 | 9625.99 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.93 | 0.00 | 01-JAN-00:10 | 9625.99 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.49 | 0.00 | 01-JAN-00:10 | 7416.34 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.49 | 0.00 | 01-JAN-00:10 | 6057.77 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.49 | 0.00 | 01-JAN-00:10 | 6057.77 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.01 | 0.00 | 01-JAN-00:10 | 7416.34 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.01 | 0.00 | 01-JAN-00:10 | 7416.34 | 02-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 44.21 | 0.00 | 01-JAN-00:10 | 5830.17 | 30-JAN-13:00 |
PlantLoopHeatingDemand:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5830.17 | 30-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5830.17 | 30-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 44.21 | 0.00 | 01-JAN-00:10 | 5830.17 | 30-JAN-13:00 |
EnergyTransfer:HVAC | 1332.96 | 0.00 | 01-JAN-00:10 | 240318.38 | 07-JUL-16:00 |
HeatingCoils:EnergyTransfer | 150.56 | 0.00 | 01-JAN-00:10 | 209915.24 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 1182.40 | 0.00 | 01-JAN-00:10 | 240318.38 | 07-JUL-16:00 |
EnergyTransfer:Plant | 44.21 | 0.00 | 01-JAN-00:10 | 5830.17 | 30-JAN-13:00 |
WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5830.17 | 30-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 44.21 | 0.00 | 01-JAN-00:10 | 5830.17 | 30-JAN-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.116 | -189.382 | 0.000 | 0.000 | 33.501 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -62.515 |
CORE_MID | 0.000 | 0.000 | 1.046 | -154.149 | 0.000 | 0.000 | 34.480 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -36.598 |
CORE_TOP | 0.000 | 0.000 | 4.845 | -150.767 | 0.000 | 0.000 | 34.969 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -44.268 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.819 | -36.432 | 0.000 | 0.000 | 7.472 | 4.897 | 24.333 | 18.192 | 0.000 | 0.289 | 1.588 | 0.000 | -24.069 | 0.000 | -5.090 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.479 | -32.256 | 0.000 | 0.000 | 4.650 | 3.061 | 15.404 | 29.232 | 0.000 | 0.179 | 0.000 | 0.000 | -14.907 | 0.000 | -3.488 | -6.355 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.446 | -49.123 | 0.000 | 0.000 | 7.273 | 4.801 | 24.332 | 51.506 | 0.000 | 0.270 | 0.000 | 0.000 | -22.633 | 0.000 | -5.430 | -16.443 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.145 | -31.640 | 0.000 | 0.000 | 4.692 | 3.079 | 15.403 | 29.490 | 0.000 | 0.177 | 0.000 | 0.000 | -15.951 | 0.000 | -3.516 | -6.880 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.349 | -32.260 | 0.000 | 0.000 | 7.458 | 4.882 | 24.333 | 18.654 | 0.000 | 0.171 | 0.172 | 0.000 | -24.902 | 0.000 | -2.858 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.981 | -29.388 | 0.000 | 0.000 | 4.621 | 3.055 | 15.404 | 29.469 | 0.000 | 0.101 | 0.001 | 0.000 | -15.723 | 0.000 | -1.991 | -7.528 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 9.288 | -43.617 | 0.000 | 0.000 | 7.362 | 4.792 | 24.332 | 52.178 | 0.000 | 4.002 | 0.003 | 0.000 | -23.874 | 0.000 | -21.721 | -12.742 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.171 | -28.151 | 0.000 | 0.000 | 4.656 | 3.072 | 15.403 | 29.812 | 0.000 | 0.098 | 0.001 | 0.000 | -16.855 | 0.000 | -2.006 | -8.200 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 4.398 | -36.188 | 0.000 | 0.000 | 7.412 | 4.897 | 24.333 | 18.130 | 0.000 | 0.250 | 6.624 | 0.000 | -25.366 | 0.000 | -4.491 | -0.002 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.198 | -29.986 | 0.000 | 0.000 | 3.404 | 3.061 | 15.404 | 29.030 | 0.000 | 0.151 | 0.000 | 0.000 | -15.691 | 0.000 | -3.085 | -4.485 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.435 | -48.925 | 0.000 | 0.000 | 7.206 | 4.801 | 24.332 | 51.368 | 0.000 | 0.233 | 0.000 | 0.000 | -23.820 | 0.000 | -4.788 | -12.842 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.488 | -31.005 | 0.000 | 0.000 | 4.650 | 3.079 | 15.403 | 29.460 | 0.000 | 0.150 | 0.001 | 0.000 | -16.804 | 0.000 | -3.098 | -4.324 |
TOPFLOOR_PLENUM | 12.106 | -32.407 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.273 | 27.771 | 0.000 | 0.000 | 0.000 | -7.743 | -0.000 |
MIDFLOOR_PLENUM | 5.038 | -16.823 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.358 | 19.269 | 0.000 | 0.000 | 0.000 | -7.842 | -0.000 |
FIRSTFLOOR_PLENUM | 3.259 | -18.439 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.278 | 21.268 | 0.000 | 0.000 | 0.000 | -6.366 | -0.000 |
Total Facility | 20.403 | -67.668 | 59.204 | -923.268 | 0.000 | 0.000 | 173.807 | 166.864 | 647.750 | 386.521 | 0.000 | 6.980 | 76.698 | 0.000 | -240.595 | 0.000 | -83.511 | -223.181 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 15-JUL-05:03 | 0.00 | 0.00 | 0.00 | -32927.90 | 0.00 | 0.00 | 311.05 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 28181.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-04:03 | 0.00 | 0.00 | 0.00 | -27716.87 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 24887.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-04:03 | 0.00 | 0.00 | 0.00 | -30858.77 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 28029.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-13:53 | 0.00 | 0.00 | 0.00 | -11296.25 | 0.00 | 0.00 | 26.91 | 19.49 | 478.42 | 3392.07 | 0.00 | 122.19 | 7257.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 09-JUL-09:12 | 0.00 | 0.00 | 0.00 | -11842.21 | 0.00 | 0.00 | 15.02 | 12.34 | 302.86 | 7501.01 | 0.00 | 0.00 | 4058.94 | 0.00 | -0.00 | 0.00 | -47.95 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:43 | 0.00 | 0.00 | 0.00 | -13799.84 | 0.00 | 0.00 | 25.59 | 19.49 | 478.41 | 9257.52 | 0.00 | 0.00 | 4030.86 | 0.00 | -0.00 | 0.00 | -12.02 | 0.00 |
PERIMETER_TOP_ZN_4 | 21-MAY-17:32 | 0.00 | 0.00 | 0.00 | -12919.52 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 6387.43 | 0.00 | 0.00 | 6339.49 | 0.00 | -0.00 | 0.00 | -64.15 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6202.47 | 0.00 | 0.00 | 148.82 | 129.08 | 637.89 | 523.78 | 0.00 | 0.00 | 4767.11 | 0.00 | -0.00 | 0.00 | -4.20 | 0.00 |
PERIMETER_BOT_ZN_2 | 27-AUG-09:52 | 0.00 | 0.00 | 0.00 | -9839.10 | 0.00 | 0.00 | 16.20 | 12.34 | 302.86 | 7133.02 | 0.00 | 0.00 | 2376.36 | 0.00 | -0.00 | 0.00 | -1.67 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-14:02 | 0.00 | 0.00 | 0.00 | -11111.49 | 0.00 | 0.00 | 25.88 | 19.49 | 478.41 | 9156.13 | 0.00 | 0.00 | 1435.22 | 0.00 | -0.00 | 0.00 | -3.65 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-17:02 | 0.00 | 0.00 | 0.00 | -9959.97 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 7310.69 | 0.00 | 42.45 | 2350.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:13 | 0.00 | 0.00 | 0.00 | -9460.08 | 0.00 | 0.00 | 28.41 | 19.49 | 478.42 | 3517.16 | 0.00 | 178.71 | 5237.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-09:42 | 0.00 | 0.00 | 0.00 | -11546.14 | 0.00 | 0.00 | 14.87 | 12.34 | 302.86 | 7099.37 | 0.00 | 0.00 | 4124.84 | 0.00 | -0.00 | 0.00 | -8.13 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:02 | 0.00 | 0.00 | 0.00 | -12145.95 | 0.00 | 0.00 | 25.76 | 19.49 | 478.41 | 9132.13 | 0.00 | 0.00 | 2494.59 | 0.00 | -0.00 | 0.00 | -4.43 | 0.00 |
PERIMETER_MID_ZN_4 | 09-JUL-17:41 | 0.00 | 0.00 | 0.00 | -11944.98 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 6274.55 | 0.00 | 66.47 | 5347.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 01-AUG-14:00 | 0.00 | -9963.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.51 | 9874.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-06:03 | 0.00 | -4365.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4383.91 | 0.00 | -0.00 | 0.00 | -18.79 | 0.00 |
FIRSTFLOOR_PLENUM | 10-JUL-15:50 | 0.00 | -4113.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | 4018.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-06:03 | 0.00 | -10010.12 | 0.00 | -151296.54 | 0.00 | 0.00 | 3551.87 | 5783.34 | 18346.02 | 5290.24 | 0.00 | 0.00 | 131152.88 | 0.00 | -1799.61 | 0.00 | -1018.09 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 10-JAN-06:01 | 0.00 | 0.00 | 14903.77 | 0.00 | 0.00 | 0.00 | 464.84 | 211.73 | 4048.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19628.40 |
CORE_MID | 09-JAN-05:02 | 0.00 | 0.00 | 17112.97 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19942.66 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 30141.47 | 0.00 | 0.00 | 0.00 | 536.27 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34091.30 |
PERIMETER_TOP_ZN_3 | 12-FEB-08:22 | 0.00 | 0.00 | 10496.56 | 0.00 | 0.00 | 0.00 | 59.91 | 28.39 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3026.10 | 0.00 | -1421.76 | -6615.43 |
PERIMETER_TOP_ZN_2 | 12-FEB-05:02 | 0.00 | 0.00 | 9970.67 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2379.02 | 0.00 | -1244.38 | -6617.55 |
PERIMETER_TOP_ZN_1 | 12-FEB-05:02 | 0.00 | 0.00 | 12056.34 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3592.41 | 0.00 | -1860.07 | -7030.82 |
PERIMETER_TOP_ZN_4 | 12-FEB-08:22 | 0.00 | 0.00 | 10753.64 | 0.00 | 0.00 | 0.00 | 37.99 | 18.10 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2016.75 | 0.00 | -964.61 | -8131.24 |
PERIMETER_BOT_ZN_3 | 13-FEB-04:02 | 0.00 | 0.00 | 7779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2954.16 | 0.00 | -975.71 | -4405.18 |
PERIMETER_BOT_ZN_2 | 09-JAN-05:01 | 0.00 | 0.00 | 7553.47 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1608.96 | 0.00 | -350.86 | -5971.28 |
PERIMETER_BOT_ZN_1 | 03-FEB-07:10 | 0.00 | 0.00 | 10160.71 | 0.00 | 0.00 | 0.00 | 193.30 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 12083.17 | 0.00 | -3837.43 | 0.00 | -19482.79 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:01 | 0.00 | 0.00 | 7590.30 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1649.16 | 0.00 | -350.60 | -5968.16 |
PERIMETER_MID_ZN_3 | 13-FEB-04:02 | 0.00 | 0.00 | 8682.01 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2924.36 | 0.00 | -1488.83 | -4824.48 |
PERIMETER_MID_ZN_2 | 13-FEB-04:02 | 0.00 | 0.00 | 8173.83 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1955.18 | 0.00 | -1007.50 | -5562.91 |
PERIMETER_MID_ZN_1 | 12-FEB-05:02 | 0.00 | 0.00 | 10073.48 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3760.71 | 0.00 | -1616.50 | -5123.22 |
PERIMETER_MID_ZN_4 | 12-FEB-05:02 | 0.00 | 0.00 | 8187.43 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2572.10 | 0.00 | -1077.49 | -4808.12 |
TOPFLOOR_PLENUM | 13-FEB-06:06 | 13940.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -567.94 | -13372.42 |
MIDFLOOR_PLENUM | 09-JAN-07:11 | 7531.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -364.22 | -7167.01 |
FIRSTFLOOR_PLENUM | 02-JAN-07:12 | 5391.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -143.13 | -5248.39 |
Total Facility | 02-JAN-06:11 | 6129.50 | 0.00 | 165110.09 | 0.00 | 0.00 | 0.00 | 2644.54 | 1963.59 | 16350.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16371.28 | 0.00 | -2603.35 | -173223.15 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.6856 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2279 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.5684 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.0074 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.0318 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7433 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.3428 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0768 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2842 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0754 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5159 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0748 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3531 | 2.3531 | 0.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9652 | 1.9652 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1289 | 2.1289 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6911 | 0.6911 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6670 | 0.6670 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8036 | 0.8036 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7412 | 0.7412 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5425 | 0.5425 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5634 | 0.5634 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6402 | 0.6402 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5864 | 0.5864 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5923 | 0.5923 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6387 | 0.6387 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7038 | 0.7038 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6685 | 0.6685 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.6856 | 4.2279 | 4.6856 | 1.0768 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.5684 | 4.0074 | 4.5684 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.0318 | 4.7433 | 5.0318 | 1.0748 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1765 | 1.1765 | 0.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9826 | 0.9826 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0645 | 1.0645 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3456 | 0.3456 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3335 | 0.3335 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4018 | 0.4018 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3706 | 0.3706 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2713 | 0.2713 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2817 | 0.2817 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3201 | 0.3201 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2932 | 0.2932 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2961 | 0.2961 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3194 | 0.3194 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3519 | 0.3519 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3343 | 0.3343 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.3428 | 1.0768 | 1.0768 | 1.0768 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2842 | 1.0754 | 1.0754 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5159 | 1.0748 | 1.0748 | 1.0748 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 163.83 |
Number of hours cooling loads not met | 146.50 |
Number of hours not met | 310.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 119.55 | 189631.84 | 38.76 | 64896.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 286.38 | 68964.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 166.86 | 17654.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.38 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 829.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 60.60 | 13159.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 124.54 | 10021.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1327.29 |
Natural Gas | 0.00 | 163.31 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1490.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 164.23 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.49 |
Space Heating | 24.00 |
Space Cooling | 57.48 |
Fans (All) | 12.16 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 266.41 |
Subtotal | 266.41 |
Natural Gas [MJ/m2] | |
Space Heating | 7.78 |
Service Water Heating | 25.00 |
Miscellaneous (All) | 32.78 |
Subtotal | 32.78 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.19 |
Space Heating | 10.62 |
Space Cooling | 19.21 |
Fans (All) | 4.07 |
Service Water Heating | 8.36 |
Receptacle Equipment | 43.46 |
Miscellaneous | 3.10 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1050. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8642.17 | 117.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8685.50 | 74.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8609.00 | 151.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8684.33 | 75.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8729.33 | 30.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8676.83 | 83.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8654.50 | 105.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8698.33 | 61.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8611.50 | 148.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8549.17 | 210.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8549.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 210.83 | 0.00 | 0.00 | 0.00 |
Average | 8697.71 | 62.29 | 0.00 | 0.00 | 0.00 |
Sum | 156558.83 | 1121.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7880.00 | 880.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7812.17 | 947.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7843.33 | 916.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7787.33 | 972.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8123.67 | 636.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7944.00 | 816.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7815.33 | 944.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7910.67 | 849.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7862.50 | 897.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7790.00 | 970.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7823.83 | 936.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7757.50 | 1002.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8133.50 | 626.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8232.17 | 527.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8344.83 | 415.17 | 0.00 | 0.00 | 0.00 |
Min | 7757.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1002.50 | 0.00 | 0.00 | 0.00 |
Average | 8074.02 | 685.98 | 0.00 | 0.00 | 0.00 |
Sum | 145332.33 | 12347.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128295.67 | 8.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24876.83 | 32.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14014.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24876.33 | 32.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14014.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24896.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23607.50 | 1301.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24877.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24876.67 | 32.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.33 | 0.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 1301.50 | 0.00 | 0.00 | 0.00 |
Average | 34062.45 | 80.88 | 0.00 | 0.00 | 0.00 |
Sum | 613124.17 | 1455.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870209E+10 | 8079.66 | 31-JAN-17:00 | 19.40 | 13.37 | 0.164945E+10 | 2454.98 | 31-JAN-14:09 | 19.40 | 13.37 |
February | 0.929512E+10 | 11809.29 | 28-FEB-17:00 | 23.90 | 12.94 | 0.160271E+10 | 2606.62 | 28-FEB-14:20 | 23.90 | 12.94 |
March | 0.136324E+11 | 15616.57 | 31-MAR-07:07 | 17.88 | 16.12 | 0.212175E+10 | 2606.70 | 08-MAR-10:09 | 17.88 | 16.12 |
April | 0.146888E+11 | 16326.09 | 17-APR-16:00 | 28.90 | 16.41 | 0.190435E+10 | 2606.63 | 17-APR-09:20 | 28.90 | 16.41 |
May | 0.183688E+11 | 21601.03 | 22-MAY-06:03 | 16.78 | 16.78 | 0.207321E+10 | 2606.72 | 11-MAY-09:00 | 16.78 | 16.78 |
June | 0.211600E+11 | 32317.03 | 26-JUN-05:12 | 23.30 | 21.67 | 0.206860E+10 | 2606.67 | 09-JUN-09:50 | 23.30 | 21.67 |
July | 0.214929E+11 | 32928.97 | 15-JUL-05:03 | 23.98 | 20.57 | 0.192290E+10 | 2606.60 | 03-JUL-09:20 | 23.98 | 20.57 |
August | 0.234668E+11 | 32504.37 | 21-AUG-05:12 | 21.87 | 21.87 | 0.215863E+10 | 2606.59 | 28-AUG-13:20 | 28.30 | 22.11 |
September | 0.196342E+11 | 30074.34 | 18-SEP-06:02 | 14.50 | 13.76 | 0.191608E+10 | 2606.64 | 15-SEP-09:00 | 14.50 | 13.76 |
October | 0.162278E+11 | 17321.71 | 11-OCT-16:00 | 26.10 | 17.12 | 0.198036E+10 | 2606.63 | 04-OCT-13:20 | 26.10 | 17.12 |
November | 0.124408E+11 | 15371.54 | 07-NOV-08:10 | 6.57 | 3.35 | 0.193772E+10 | 2606.73 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.102718E+11 | 10639.47 | 14-DEC-17:00 | 13.90 | 10.25 | 0.175693E+10 | 2606.63 | 13-DEC-14:30 | 13.90 | 10.25 |
Annual Sum or Average | 0.189382E+12 | 0.230927E+11 | ||||||||
Minimum of Months | 0.870209E+10 | 8079.66 | 6.57 | 3.35 | 0.160271E+10 | 2454.98 | 10.68 | 10.03 | ||
Maximum of Months | 0.234668E+11 | 32928.97 | 28.90 | 21.87 | 0.215863E+10 | 2606.73 | 28.90 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71400039.79 | 1088.72 | 28-JAN-17:25 | 11.40 | 4.15 | 0.00 | 0.00 | 01-JAN-00:10 | 11.40 | 4.15 |
February | 0.359270E+09 | 2928.88 | 26-FEB-15:33 | 24.60 | 12.48 | 0.00 | 0.00 | 01-FEB-00:10 | 24.60 | 12.48 |
March | 0.123132E+10 | 6381.26 | 30-MAR-14:50 | 27.80 | 17.21 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.21 |
April | 0.240047E+10 | 7421.74 | 17-APR-15:00 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.399969E+10 | 8296.87 | 30-MAY-15:00 | 30.60 | 21.44 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 21.44 |
June | 0.582302E+10 | 8901.91 | 12-JUN-15:00 | 33.30 | 22.72 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 22.72 |
July | 0.622964E+10 | 9806.27 | 07-JUL-15:20 | 35.20 | 23.90 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 23.90 |
August | 0.648564E+10 | 9963.77 | 01-AUG-14:00 | 33.90 | 23.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.66 |
September | 0.348634E+10 | 8512.63 | 06-SEP-14:20 | 30.53 | 23.42 | 0.00 | 0.00 | 01-SEP-00:10 | 30.53 | 23.42 |
October | 0.161450E+10 | 6526.56 | 10-OCT-14:40 | 29.07 | 20.78 | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 20.78 |
November | 0.548305E+09 | 2383.54 | 05-NOV-14:53 | 23.90 | 18.46 | 0.00 | 0.00 | 01-NOV-00:10 | 23.90 | 18.46 |
December | 0.157838E+09 | 1529.67 | 12-DEC-14:40 | 22.80 | 16.47 | 0.00 | 0.00 | 01-DEC-00:10 | 22.80 | 16.47 |
Annual Sum or Average | 0.324074E+11 | 0.00 | ||||||||
Minimum of Months | 71400039.79 | 1088.72 | 11.40 | 4.15 | 0.00 | 0.00 | 11.40 | 4.15 | ||
Maximum of Months | 0.648564E+10 | 9963.77 | 35.20 | 23.90 | 0.00 | 0.00 | 35.20 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24826898.40 | 2005.34 | 14-JAN-05:01 | -6.2 | -7.4 | 0.00 | 0.00 | 01-JAN-00:10 | -6.2 | -7.4 |
February | 0.115729E+09 | 1918.31 | 03-FEB-05:01 | -7.9 | -9.5 | 0.00 | 0.00 | 01-FEB-00:10 | -7.9 | -9.5 |
March | 0.498773E+09 | 1956.03 | 06-MAR-07:03 | 2.80 | 0.11 | 0.00 | 0.00 | 01-MAR-00:10 | 2.80 | 0.11 |
April | 0.997998E+09 | 2647.81 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.187590E+10 | 3445.81 | 30-MAY-15:20 | 29.67 | 21.52 | 0.00 | 0.00 | 01-MAY-00:10 | 29.67 | 21.52 |
June | 0.301162E+10 | 4235.52 | 26-JUN-06:03 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.339737E+10 | 4365.40 | 17-JUL-06:03 | 21.70 | 19.38 | 0.00 | 0.00 | 01-JUL-00:10 | 21.70 | 19.38 |
August | 0.366893E+10 | 4171.82 | 07-AUG-06:03 | 22.88 | 22.15 | 0.00 | 0.00 | 01-AUG-00:10 | 22.88 | 22.15 |
September | 0.212177E+10 | 3595.38 | 11-SEP-16:00 | 30.00 | 22.85 | 0.00 | 0.00 | 01-SEP-00:10 | 30.00 | 22.85 |
October | 0.809333E+09 | 2436.90 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.228586E+09 | 1720.00 | 08-NOV-07:03 | 4.40 | 1.76 | 0.00 | 0.00 | 01-NOV-00:10 | 4.40 | 1.76 |
December | 72322933.06 | 1775.02 | 09-DEC-06:11 | 2.20 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | -1.0 |
Annual Sum or Average | 0.168232E+11 | 0.00 | ||||||||
Minimum of Months | 24826898.40 | 1720.00 | -7.9 | -9.5 | 0.00 | 0.00 | -7.9 | -9.5 | ||
Maximum of Months | 0.366893E+10 | 4365.40 | 30.00 | 22.85 | 0.00 | 0.00 | 30.00 | 22.85 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40565076.87 | 1670.77 | 14-JAN-06:01 | -6.7 | -7.8 | 0.00 | 0.00 | 01-JAN-00:10 | -6.7 | -7.8 |
February | 0.157136E+09 | 2030.16 | 23-FEB-07:03 | 5.00 | 3.70 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.70 |
March | 0.654161E+09 | 2300.85 | 03-MAR-07:03 | 6.28 | 4.66 | 0.00 | 0.00 | 01-MAR-00:10 | 6.28 | 4.66 |
April | 0.115418E+10 | 2713.33 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.193204E+10 | 3226.94 | 30-MAY-15:10 | 30.13 | 21.49 | 0.00 | 0.00 | 01-MAY-00:10 | 30.13 | 21.49 |
June | 0.306812E+10 | 3615.80 | 26-JUN-06:03 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.346797E+10 | 4113.07 | 10-JUL-15:50 | 32.70 | 22.31 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 22.31 |
August | 0.387505E+10 | 4088.97 | 07-AUG-12:20 | 31.13 | 23.76 | 0.00 | 0.00 | 01-AUG-00:10 | 31.13 | 23.76 |
September | 0.251082E+10 | 3949.13 | 11-SEP-16:00 | 30.00 | 22.85 | 0.00 | 0.00 | 01-SEP-00:10 | 30.00 | 22.85 |
October | 0.113303E+10 | 2856.65 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.332516E+09 | 1338.10 | 14-NOV-07:03 | 3.03 | 0.85 | 0.00 | 0.00 | 01-NOV-00:10 | 3.03 | 0.85 |
December | 0.113530E+09 | 1935.05 | 15-DEC-07:03 | 3.22 | 0.92 | 0.00 | 0.00 | 01-DEC-00:10 | 3.22 | 0.92 |
Annual Sum or Average | 0.184391E+11 | 0.00 | ||||||||
Minimum of Months | 40565076.87 | 1338.10 | -6.7 | -7.8 | 0.00 | 0.00 | -6.7 | -7.8 | ||
Maximum of Months | 0.387505E+10 | 4113.07 | 32.70 | 23.76 | 0.00 | 0.00 | 32.70 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591587E+10 | 7293.56 | 31-JAN-17:00 | 19.40 | 13.37 | 0.150773E+10 | 2217.05 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.723205E+10 | 8373.91 | 28-FEB-17:00 | 23.90 | 12.94 | 0.145481E+10 | 2546.27 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.115224E+11 | 11872.69 | 31-MAR-16:00 | 17.20 | 13.86 | 0.198393E+10 | 2606.61 | 30-MAR-09:20 | 17.20 | 13.86 |
April | 0.122970E+11 | 13136.31 | 17-APR-16:00 | 28.90 | 16.41 | 0.185936E+10 | 2606.64 | 17-APR-09:20 | 28.90 | 16.41 |
May | 0.154310E+11 | 15254.46 | 30-MAY-15:50 | 28.27 | 21.53 | 0.206015E+10 | 2606.69 | 11-MAY-09:00 | 28.27 | 21.53 |
June | 0.177710E+11 | 26180.85 | 26-JUN-05:12 | 23.30 | 21.67 | 0.206404E+10 | 2606.67 | 09-JUN-09:39 | 23.30 | 21.67 |
July | 0.183201E+11 | 27445.34 | 10-JUL-05:12 | 20.73 | 19.68 | 0.191941E+10 | 2606.60 | 03-JUL-09:20 | 20.73 | 19.68 |
August | 0.195865E+11 | 27711.14 | 14-AUG-04:03 | 24.22 | 20.90 | 0.215656E+10 | 2606.59 | 28-AUG-09:20 | 24.97 | 21.71 |
September | 0.157089E+11 | 23229.73 | 11-SEP-06:03 | 19.50 | 18.37 | 0.190633E+10 | 2606.63 | 21-SEP-09:20 | 21.33 | 17.87 |
October | 0.125007E+11 | 13626.76 | 11-OCT-16:00 | 26.10 | 17.12 | 0.190417E+10 | 2606.63 | 10-OCT-09:20 | 26.10 | 17.12 |
November | 0.995065E+10 | 9493.01 | 06-NOV-17:00 | 18.90 | 9.61 | 0.175548E+10 | 2606.29 | 06-NOV-14:00 | 18.90 | 9.61 |
December | 0.791244E+10 | 8094.35 | 13-DEC-17:00 | 16.70 | 16.70 | 0.154211E+10 | 2462.34 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.154149E+12 | 0.221141E+11 | ||||||||
Minimum of Months | 0.591587E+10 | 7293.56 | 16.70 | 9.61 | 0.145481E+10 | 2217.05 | 16.70 | 9.61 | ||
Maximum of Months | 0.195865E+11 | 27711.14 | 28.90 | 21.67 | 0.215656E+10 | 2606.69 | 28.90 | 21.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442434E+10 | 7323.85 | 20-JAN-17:00 | 16.70 | 11.48 | 0.148108E+10 | 2203.70 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.592716E+10 | 8659.62 | 28-FEB-17:00 | 23.90 | 12.94 | 0.141082E+10 | 2543.72 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.109134E+11 | 14145.34 | 30-MAR-16:00 | 27.80 | 17.47 | 0.190212E+10 | 2606.61 | 29-MAR-13:20 | 27.80 | 17.47 |
April | 0.122695E+11 | 15613.85 | 17-APR-16:00 | 28.90 | 16.41 | 0.181698E+10 | 2606.63 | 11-APR-13:20 | 28.90 | 16.41 |
May | 0.159806E+11 | 17916.57 | 30-MAY-15:20 | 29.67 | 21.52 | 0.204667E+10 | 2606.69 | 24-MAY-09:20 | 29.67 | 21.52 |
June | 0.189786E+11 | 29510.91 | 26-JUN-05:12 | 23.30 | 21.67 | 0.206127E+10 | 2606.66 | 09-JUN-13:09 | 23.30 | 21.67 |
July | 0.197541E+11 | 30287.24 | 10-JUL-05:12 | 20.73 | 19.68 | 0.191903E+10 | 2606.61 | 03-JUL-09:20 | 20.73 | 19.68 |
August | 0.209456E+11 | 30851.09 | 14-AUG-04:03 | 24.22 | 20.90 | 0.215652E+10 | 2606.62 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.155891E+11 | 17608.10 | 11-SEP-15:30 | 29.70 | 22.95 | 0.189254E+10 | 2606.67 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.115395E+11 | 14788.09 | 11-OCT-16:00 | 26.10 | 17.12 | 0.182531E+10 | 2606.61 | 16-OCT-13:20 | 24.60 | 18.97 |
November | 0.859279E+10 | 8741.34 | 06-NOV-17:00 | 18.90 | 9.61 | 0.163703E+10 | 2569.07 | 06-NOV-14:00 | 18.90 | 9.61 |
December | 0.585210E+10 | 7954.82 | 13-DEC-17:00 | 16.70 | 16.70 | 0.147563E+10 | 2423.52 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.150767E+12 | 0.216250E+11 | ||||||||
Minimum of Months | 0.442434E+10 | 7323.85 | 16.70 | 9.61 | 0.141082E+10 | 2203.70 | 16.70 | 9.61 | ||
Maximum of Months | 0.209456E+11 | 30851.09 | 29.70 | 22.95 | 0.215652E+10 | 2606.69 | 29.67 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245566E+09 | 1524.88 | 31-JAN-16:40 | 19.60 | 13.44 | 0.307565E+09 | 467.80 | 31-JAN-14:00 | 19.60 | 13.44 |
February | 0.638596E+09 | 2268.90 | 28-FEB-15:30 | 24.15 | 13.12 | 0.288971E+09 | 549.48 | 28-FEB-14:50 | 24.15 | 13.12 |
March | 0.194434E+10 | 4451.61 | 30-MAR-15:50 | 27.80 | 17.41 | 0.381988E+09 | 549.48 | 30-MAR-13:20 | 27.80 | 17.41 |
April | 0.272890E+10 | 4848.33 | 19-APR-14:30 | 26.15 | 17.54 | 0.370011E+09 | 549.49 | 11-APR-13:20 | 26.15 | 17.54 |
May | 0.427335E+10 | 6364.57 | 30-MAY-15:00 | 30.60 | 21.44 | 0.427192E+09 | 549.50 | 18-MAY-09:20 | 30.60 | 21.44 |
June | 0.597319E+10 | 11068.69 | 25-JUN-16:22 | 33.05 | 22.20 | 0.434423E+09 | 549.50 | 09-JUN-13:20 | 33.05 | 22.20 |
July | 0.626102E+10 | 11296.62 | 16-JUL-13:53 | 33.90 | 23.22 | 0.405084E+09 | 549.49 | 03-JUL-09:20 | 33.90 | 23.22 |
August | 0.648918E+10 | 11015.02 | 06-AUG-14:43 | 31.88 | 23.78 | 0.454885E+09 | 549.49 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.394160E+10 | 6112.86 | 06-SEP-14:30 | 30.25 | 23.24 | 0.394870E+09 | 549.50 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.220653E+10 | 4186.93 | 02-OCT-14:40 | 26.70 | 20.10 | 0.365746E+09 | 549.48 | 19-OCT-13:20 | 22.77 | 19.40 |
November | 0.122034E+10 | 1763.59 | 02-NOV-15:40 | 22.40 | 16.14 | 0.326858E+09 | 536.30 | 03-NOV-13:00 | 21.70 | 17.40 |
December | 0.510230E+09 | 1641.76 | 13-DEC-15:00 | 18.30 | 16.86 | 0.300755E+09 | 504.55 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.364328E+11 | 0.445835E+10 | ||||||||
Minimum of Months | 0.245566E+09 | 1524.88 | 18.30 | 13.12 | 0.288971E+09 | 467.80 | 18.30 | 13.12 | ||
Maximum of Months | 0.648918E+10 | 11296.62 | 33.90 | 23.78 | 0.454885E+09 | 549.50 | 33.90 | 23.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277898E+09 | 999.08 | 31-JAN-15:00 | 21.10 | 12.97 | 0.196220E+09 | 308.72 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.590085E+09 | 2018.13 | 27-FEB-10:40 | 14.27 | 6.32 | 0.191906E+09 | 347.87 | 24-FEB-10:39 | 14.27 | 6.32 |
March | 0.160353E+10 | 3550.40 | 30-MAR-11:00 | 22.20 | 17.83 | 0.260530E+09 | 347.88 | 08-MAR-10:09 | 22.20 | 17.83 |
April | 0.259752E+10 | 7416.69 | 16-APR-10:43 | 25.45 | 15.37 | 0.247555E+09 | 347.88 | 12-APR-13:00 | 25.45 | 15.37 |
May | 0.395725E+10 | 11225.04 | 07-MAY-09:23 | 24.15 | 19.65 | 0.274258E+09 | 347.89 | 11-MAY-09:50 | 16.73 | 12.76 |
June | 0.521834E+10 | 11810.47 | 25-JUN-10:22 | 29.70 | 23.14 | 0.275967E+09 | 347.89 | 09-JUN-09:00 | 29.70 | 23.14 |
July | 0.546392E+10 | 11833.82 | 09-JUL-09:12 | 26.10 | 22.57 | 0.256873E+09 | 347.87 | 17-JUL-09:20 | 26.67 | 21.67 |
August | 0.556090E+10 | 11142.24 | 13-AUG-11:02 | 27.88 | 22.91 | 0.288369E+09 | 347.88 | 25-AUG-09:30 | 26.10 | 18.45 |
September | 0.358878E+10 | 11117.12 | 04-SEP-09:32 | 26.13 | 22.05 | 0.252443E+09 | 347.88 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.192923E+10 | 4388.72 | 11-OCT-10:30 | 24.20 | 19.54 | 0.244378E+09 | 347.87 | 20-OCT-13:20 | 18.13 | 11.22 |
November | 0.970435E+09 | 1765.86 | 06-NOV-10:40 | 16.27 | 12.91 | 0.219067E+09 | 347.87 | 06-NOV-10:20 | 16.27 | 12.91 |
December | 0.498827E+09 | 1064.00 | 12-DEC-15:00 | 22.80 | 16.17 | 0.195010E+09 | 328.03 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.322567E+11 | 0.290258E+10 | ||||||||
Minimum of Months | 0.277898E+09 | 999.08 | 14.27 | 6.32 | 0.191906E+09 | 308.72 | 14.27 | 6.32 | ||
Maximum of Months | 0.556090E+10 | 11833.82 | 29.70 | 23.14 | 0.288369E+09 | 347.89 | 29.70 | 23.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107503E+10 | 4267.07 | 11-JAN-14:30 | 6.70 | 2.05 | 0.340353E+09 | 549.49 | 10-JAN-14:20 | 6.70 | 2.05 |
February | 0.157773E+10 | 10605.35 | 26-FEB-14:33 | 24.80 | 12.68 | 0.317141E+09 | 549.50 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.321467E+10 | 9325.09 | 30-MAR-13:50 | 27.62 | 17.92 | 0.407952E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.92 |
April | 0.382614E+10 | 11358.96 | 16-APR-14:03 | 28.62 | 16.11 | 0.379151E+09 | 549.52 | 12-APR-13:00 | 28.62 | 16.11 |
May | 0.489819E+10 | 9342.27 | 29-MAY-13:43 | 28.40 | 20.38 | 0.427142E+09 | 549.50 | 18-MAY-09:20 | 28.40 | 20.38 |
June | 0.617037E+10 | 11998.25 | 25-JUN-16:22 | 33.05 | 22.20 | 0.433583E+09 | 549.50 | 09-JUN-13:20 | 33.05 | 22.20 |
July | 0.658183E+10 | 13160.01 | 09-JUL-13:53 | 32.80 | 23.63 | 0.405035E+09 | 549.49 | 03-JUL-09:20 | 32.80 | 23.63 |
August | 0.766359E+10 | 13559.81 | 27-AUG-13:23 | 31.70 | 22.52 | 0.455120E+09 | 549.49 | 25-AUG-09:20 | 31.70 | 22.52 |
September | 0.562995E+10 | 13788.18 | 24-SEP-13:13 | 28.70 | 19.86 | 0.397072E+09 | 549.50 | 22-SEP-13:00 | 28.70 | 19.86 |
October | 0.427889E+10 | 13797.04 | 09-OCT-13:43 | 27.02 | 19.32 | 0.387728E+09 | 551.72 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.259680E+10 | 10482.21 | 11-NOV-15:13 | 21.30 | 11.76 | 0.365676E+09 | 549.49 | 14-NOV-14:30 | 19.15 | 8.88 |
December | 0.161157E+10 | 5740.33 | 08-DEC-14:10 | 12.80 | 5.52 | 0.341442E+09 | 549.48 | 12-DEC-14:20 | 22.80 | 16.78 |
Annual Sum or Average | 0.491247E+11 | 0.465739E+10 | ||||||||
Minimum of Months | 0.107503E+10 | 4267.07 | 6.70 | 2.05 | 0.317141E+09 | 549.48 | 6.70 | 2.05 | ||
Maximum of Months | 0.766359E+10 | 13797.04 | 33.05 | 23.63 | 0.455120E+09 | 551.72 | 33.05 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312313E+09 | 1082.76 | 11-JAN-16:40 | 6.47 | 1.83 | 0.198599E+09 | 326.32 | 11-JAN-16:49 | 6.28 | 1.74 |
February | 0.613909E+09 | 4077.31 | 27-FEB-17:00 | 22.20 | 11.44 | 0.187940E+09 | 347.85 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.179770E+10 | 6249.98 | 30-MAR-16:00 | 27.80 | 17.47 | 0.247867E+09 | 347.84 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.267014E+10 | 12265.37 | 09-APR-17:03 | 21.60 | 10.86 | 0.236843E+09 | 347.85 | 12-APR-13:00 | 28.90 | 17.10 |
May | 0.381852E+10 | 12915.31 | 21-MAY-17:32 | 25.97 | 19.50 | 0.270671E+09 | 347.85 | 24-MAY-09:20 | 17.57 | 16.38 |
June | 0.495382E+10 | 12494.51 | 25-JUN-16:22 | 33.05 | 22.20 | 0.274837E+09 | 347.85 | 09-JUN-09:20 | 33.05 | 22.20 |
July | 0.514867E+10 | 12863.31 | 30-JUL-17:42 | 30.60 | 23.73 | 0.256602E+09 | 347.85 | 03-JUL-09:20 | 30.60 | 23.73 |
August | 0.542350E+10 | 12751.53 | 13-AUG-17:02 | 31.10 | 22.35 | 0.288238E+09 | 347.85 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.343813E+10 | 11906.40 | 04-SEP-16:23 | 28.05 | 22.55 | 0.250738E+09 | 347.85 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.197950E+10 | 10863.65 | 09-OCT-16:23 | 27.25 | 19.48 | 0.235794E+09 | 347.84 | 19-OCT-13:20 | 22.77 | 19.40 |
November | 0.101165E+10 | 3765.20 | 06-NOV-16:00 | 20.60 | 10.48 | 0.215191E+09 | 347.84 | 15-NOV-14:30 | 21.40 | 11.46 |
December | 0.473726E+09 | 1484.30 | 11-DEC-16:00 | 21.10 | 15.91 | 0.197531E+09 | 347.82 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.316416E+11 | 0.286085E+10 | ||||||||
Minimum of Months | 0.312313E+09 | 1082.76 | 6.47 | 1.83 | 0.187940E+09 | 326.32 | 6.28 | 1.74 | ||
Maximum of Months | 0.542350E+10 | 12915.31 | 33.05 | 23.73 | 0.288238E+09 | 347.85 | 33.05 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220543E+09 | 1436.56 | 31-JAN-15:00 | 21.10 | 12.97 | 0.307438E+09 | 443.54 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.587440E+09 | 1673.36 | 28-FEB-15:10 | 24.72 | 13.51 | 0.285490E+09 | 514.73 | 28-FEB-14:00 | 24.72 | 13.51 |
March | 0.177559E+10 | 2317.26 | 30-MAR-16:00 | 27.80 | 17.47 | 0.369772E+09 | 549.49 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.209646E+10 | 2752.92 | 19-APR-14:30 | 26.15 | 17.54 | 0.355528E+09 | 549.49 | 17-APR-13:20 | 26.15 | 17.54 |
May | 0.298664E+10 | 4242.21 | 30-MAY-15:00 | 30.60 | 21.44 | 0.422565E+09 | 549.50 | 18-MAY-09:20 | 30.60 | 21.44 |
June | 0.465722E+10 | 5067.66 | 28-JUN-14:30 | 30.85 | 23.20 | 0.434357E+09 | 549.50 | 09-JUN-09:20 | 30.85 | 23.20 |
July | 0.519440E+10 | 6201.10 | 17-JUL-06:03 | 21.70 | 19.38 | 0.404763E+09 | 549.49 | 03-JUL-09:20 | 21.70 | 19.38 |
August | 0.571747E+10 | 5781.39 | 07-AUG-06:03 | 22.88 | 22.15 | 0.454792E+09 | 549.49 | 18-AUG-13:20 | 34.03 | 22.77 |
September | 0.388319E+10 | 5333.32 | 06-SEP-14:30 | 30.25 | 23.24 | 0.400897E+09 | 549.49 | 20-SEP-09:20 | 20.93 | 15.94 |
October | 0.257823E+10 | 3661.28 | 02-OCT-14:30 | 26.70 | 20.05 | 0.385934E+09 | 549.49 | 05-OCT-13:20 | 20.00 | 14.95 |
November | 0.178071E+10 | 1836.98 | 05-NOV-13:13 | 22.57 | 18.26 | 0.346180E+09 | 543.28 | 03-NOV-13:00 | 22.57 | 18.26 |
December | 0.782358E+09 | 1634.86 | 13-DEC-13:30 | 19.45 | 17.14 | 0.304687E+09 | 499.71 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.322602E+11 | 0.447240E+10 | ||||||||
Minimum of Months | 0.220543E+09 | 1436.56 | 19.45 | 12.97 | 0.285490E+09 | 443.54 | 18.30 | 12.97 | ||
Maximum of Months | 0.571747E+10 | 6201.10 | 30.85 | 23.24 | 0.454792E+09 | 549.50 | 34.03 | 23.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297948E+09 | 962.47 | 31-JAN-14:50 | 21.02 | 13.03 | 0.196574E+09 | 296.76 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.572700E+09 | 1640.44 | 27-FEB-10:40 | 14.27 | 6.32 | 0.190799E+09 | 347.87 | 24-FEB-10:00 | 14.27 | 6.32 |
March | 0.143576E+10 | 2397.66 | 14-MAR-11:00 | 20.60 | 15.46 | 0.258184E+09 | 347.88 | 08-MAR-10:20 | 20.60 | 15.46 |
April | 0.192017E+10 | 4126.11 | 17-APR-10:10 | 23.27 | 15.57 | 0.244943E+09 | 347.87 | 17-APR-09:20 | 23.27 | 15.57 |
May | 0.295473E+10 | 5129.85 | 30-MAY-10:00 | 27.80 | 21.16 | 0.273652E+09 | 347.89 | 11-MAY-09:00 | 27.80 | 21.16 |
June | 0.432905E+10 | 8472.83 | 04-JUN-08:23 | 23.30 | 17.57 | 0.276004E+09 | 347.88 | 09-JUN-09:50 | 24.13 | 15.23 |
July | 0.475186E+10 | 9679.95 | 09-JUL-09:12 | 26.10 | 22.57 | 0.256934E+09 | 347.87 | 17-JUL-09:20 | 26.67 | 21.67 |
August | 0.509949E+10 | 9837.26 | 27-AUG-09:52 | 27.20 | 21.81 | 0.288472E+09 | 347.87 | 18-AUG-13:20 | 27.20 | 21.81 |
September | 0.364125E+10 | 8624.65 | 04-SEP-09:23 | 25.85 | 21.92 | 0.254946E+09 | 347.88 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.228679E+10 | 4287.16 | 10-OCT-10:20 | 24.23 | 18.95 | 0.254102E+09 | 347.87 | 04-OCT-13:20 | 24.23 | 18.95 |
November | 0.133648E+10 | 2225.87 | 06-NOV-10:10 | 14.87 | 12.62 | 0.236171E+09 | 347.87 | 15-NOV-10:09 | 13.53 | 8.25 |
December | 0.761825E+09 | 1074.14 | 13-DEC-12:00 | 20.00 | 17.41 | 0.201288E+09 | 327.61 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.293881E+11 | 0.293207E+10 | ||||||||
Minimum of Months | 0.297948E+09 | 962.47 | 14.27 | 6.32 | 0.190799E+09 | 296.76 | 13.53 | 6.32 | ||
Maximum of Months | 0.509949E+10 | 9837.26 | 27.80 | 22.57 | 0.288472E+09 | 347.89 | 27.80 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.618243E+09 | 2226.78 | 28-JAN-14:50 | 11.93 | 4.48 | 0.311318E+09 | 522.30 | 31-JAN-14:50 | 21.02 | 13.03 |
February | 0.103495E+10 | 5457.94 | 21-FEB-14:30 | 22.25 | 10.82 | 0.297627E+09 | 549.50 | 27-FEB-14:20 | 20.77 | 9.86 |
March | 0.225182E+10 | 7309.05 | 30-MAR-16:10 | 27.62 | 17.53 | 0.390938E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.53 |
April | 0.262029E+10 | 7538.62 | 17-APR-16:10 | 28.80 | 16.45 | 0.362918E+09 | 549.50 | 17-APR-13:20 | 28.80 | 16.45 |
May | 0.358734E+10 | 8550.22 | 30-MAY-12:00 | 29.40 | 21.24 | 0.416158E+09 | 549.50 | 10-MAY-13:39 | 29.40 | 21.24 |
June | 0.558483E+10 | 9283.94 | 06-JUN-16:30 | 33.90 | 21.77 | 0.432026E+09 | 574.38 | 06-JUN-12:09 | 33.90 | 21.77 |
July | 0.625747E+10 | 9685.11 | 07-JUL-16:50 | 35.10 | 23.67 | 0.404947E+09 | 598.52 | 14-JUL-12:09 | 33.40 | 24.44 |
August | 0.777480E+10 | 10563.12 | 06-AUG-13:23 | 32.50 | 23.69 | 0.457018E+09 | 624.17 | 18-AUG-12:09 | 33.98 | 23.68 |
September | 0.576235E+10 | 10571.28 | 24-SEP-12:13 | 28.50 | 19.83 | 0.400203E+09 | 601.64 | 07-SEP-12:09 | 28.50 | 19.83 |
October | 0.417008E+10 | 11110.27 | 09-OCT-14:02 | 27.30 | 19.46 | 0.394164E+09 | 589.83 | 10-OCT-13:00 | 29.40 | 21.05 |
November | 0.254043E+10 | 10525.03 | 12-NOV-14:13 | 19.27 | 10.66 | 0.370949E+09 | 549.50 | 09-NOV-14:20 | 19.27 | 10.66 |
December | 0.141551E+10 | 5188.17 | 12-DEC-14:00 | 22.80 | 17.07 | 0.330709E+09 | 549.49 | 19-DEC-14:09 | 13.90 | 5.02 |
Annual Sum or Average | 0.436181E+11 | 0.456898E+10 | ||||||||
Minimum of Months | 0.618243E+09 | 2226.78 | 11.93 | 4.48 | 0.297627E+09 | 522.30 | 13.90 | 5.02 | ||
Maximum of Months | 0.777480E+10 | 11110.27 | 35.10 | 23.69 | 0.457018E+09 | 624.17 | 33.98 | 24.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300045E+09 | 1004.90 | 20-JAN-16:40 | 16.87 | 11.91 | 0.197558E+09 | 302.19 | 27-JAN-16:00 | 4.40 | -1.6 |
February | 0.558006E+09 | 2770.51 | 27-FEB-17:00 | 22.20 | 11.44 | 0.186446E+09 | 347.83 | 28-FEB-14:39 | 25.00 | 13.71 |
March | 0.152278E+10 | 4044.31 | 30-MAR-16:00 | 27.80 | 17.47 | 0.247894E+09 | 347.84 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.189975E+10 | 4678.58 | 17-APR-16:00 | 28.90 | 16.41 | 0.235294E+09 | 347.84 | 12-APR-13:20 | 28.90 | 16.41 |
May | 0.275227E+10 | 9731.22 | 21-MAY-17:22 | 26.15 | 19.60 | 0.270995E+09 | 347.85 | 17-MAY-09:20 | 26.15 | 19.60 |
June | 0.403661E+10 | 9849.29 | 25-JUN-17:23 | 31.70 | 22.62 | 0.275572E+09 | 347.85 | 09-JUN-09:20 | 31.70 | 22.62 |
July | 0.440249E+10 | 9908.38 | 09-JUL-17:12 | 33.13 | 22.68 | 0.256724E+09 | 347.85 | 03-JUL-09:20 | 33.13 | 22.68 |
August | 0.494222E+10 | 9960.05 | 13-AUG-17:02 | 31.10 | 22.35 | 0.288441E+09 | 347.84 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.345572E+10 | 9540.49 | 24-SEP-16:53 | 27.80 | 19.57 | 0.254819E+09 | 347.85 | 20-SEP-09:20 | 27.80 | 19.57 |
October | 0.222324E+10 | 5701.91 | 09-OCT-17:23 | 25.55 | 19.16 | 0.250926E+09 | 347.85 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.137294E+10 | 3616.88 | 06-NOV-16:30 | 19.75 | 10.05 | 0.230790E+09 | 347.84 | 03-NOV-13:20 | 19.75 | 10.05 |
December | 0.685863E+09 | 1261.85 | 11-DEC-16:00 | 21.10 | 15.91 | 0.200839E+09 | 345.61 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.281519E+11 | 0.289630E+10 | ||||||||
Minimum of Months | 0.300045E+09 | 1004.90 | 16.87 | 10.05 | 0.186446E+09 | 302.19 | 4.40 | -1.6 | ||
Maximum of Months | 0.494222E+10 | 9960.05 | 33.13 | 22.68 | 0.288441E+09 | 347.85 | 33.13 | 22.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304440E+09 | 1522.75 | 31-JAN-16:30 | 19.70 | 13.48 | 0.308656E+09 | 468.16 | 31-JAN-14:00 | 19.70 | 13.48 |
February | 0.778540E+09 | 2158.66 | 28-FEB-15:30 | 24.15 | 13.12 | 0.291596E+09 | 549.49 | 28-FEB-14:20 | 24.15 | 13.12 |
March | 0.217309E+10 | 3840.84 | 30-MAR-16:00 | 27.80 | 17.47 | 0.392198E+09 | 549.48 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.272074E+10 | 4341.77 | 18-APR-14:00 | 27.20 | 15.86 | 0.377981E+09 | 549.50 | 17-APR-09:20 | 27.20 | 15.86 |
May | 0.404753E+10 | 5647.06 | 30-MAY-15:00 | 30.60 | 21.44 | 0.431453E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.44 |
June | 0.557428E+10 | 7716.78 | 26-JUN-05:12 | 23.30 | 21.67 | 0.435337E+09 | 549.50 | 09-JUN-09:20 | 23.30 | 21.67 |
July | 0.580666E+10 | 9459.16 | 16-JUL-13:13 | 32.77 | 23.89 | 0.405280E+09 | 549.49 | 03-JUL-09:20 | 32.77 | 23.89 |
August | 0.606714E+10 | 7138.57 | 07-AUG-06:03 | 22.88 | 22.15 | 0.455034E+09 | 549.49 | 18-AUG-13:20 | 34.03 | 22.77 |
September | 0.390104E+10 | 5508.48 | 06-SEP-14:20 | 30.53 | 23.42 | 0.399269E+09 | 549.49 | 20-SEP-09:20 | 20.93 | 15.94 |
October | 0.249384E+10 | 3813.87 | 02-OCT-14:40 | 26.70 | 20.10 | 0.378323E+09 | 549.49 | 11-OCT-09:20 | 21.33 | 18.09 |
November | 0.160160E+10 | 1783.89 | 05-NOV-13:03 | 22.38 | 18.19 | 0.338735E+09 | 545.68 | 03-NOV-13:00 | 22.38 | 18.19 |
December | 0.720000E+09 | 1671.80 | 13-DEC-13:30 | 19.45 | 17.14 | 0.304570E+09 | 511.75 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.361889E+11 | 0.451843E+10 | ||||||||
Minimum of Months | 0.304440E+09 | 1522.75 | 19.45 | 13.12 | 0.291596E+09 | 468.16 | 18.30 | 13.12 | ||
Maximum of Months | 0.606714E+10 | 9459.16 | 32.77 | 23.89 | 0.455034E+09 | 549.50 | 34.03 | 23.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274567E+09 | 1061.74 | 31-JAN-15:10 | 20.92 | 13.08 | 0.146054E+09 | 327.16 | 31-JAN-15:09 | 20.92 | 13.08 |
February | 0.580136E+09 | 3877.57 | 23-FEB-13:02 | 13.40 | 6.52 | 0.143383E+09 | 356.45 | 21-FEB-13:09 | 13.40 | 6.52 |
March | 0.155309E+10 | 5113.74 | 15-MAR-12:02 | 13.48 | 6.47 | 0.195770E+09 | 356.46 | 13-MAR-14:09 | 13.48 | 6.47 |
April | 0.243508E+10 | 7584.30 | 16-APR-10:13 | 23.50 | 14.96 | 0.184497E+09 | 356.46 | 17-APR-10:09 | 23.27 | 15.57 |
May | 0.361278E+10 | 10762.12 | 07-MAY-09:13 | 23.87 | 19.51 | 0.203948E+09 | 356.47 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.471313E+10 | 11181.00 | 25-JUN-10:22 | 29.70 | 23.14 | 0.204685E+09 | 356.47 | 09-JUN-10:09 | 29.70 | 23.14 |
July | 0.492501E+10 | 11542.24 | 09-JUL-09:42 | 27.75 | 23.00 | 0.191176E+09 | 356.45 | 20-JUL-10:09 | 27.98 | 22.07 |
August | 0.503741E+10 | 11466.35 | 27-AUG-09:52 | 27.20 | 21.81 | 0.213822E+09 | 356.45 | 18-AUG-14:09 | 27.20 | 21.81 |
September | 0.337004E+10 | 10648.65 | 04-SEP-09:23 | 25.85 | 21.92 | 0.188331E+09 | 356.47 | 15-SEP-10:09 | 24.18 | 16.24 |
October | 0.196915E+10 | 5770.46 | 11-OCT-10:05 | 23.27 | 19.04 | 0.184519E+09 | 356.45 | 26-OCT-12:09 | 16.20 | 9.82 |
November | 0.100290E+10 | 3360.43 | 06-NOV-11:05 | 17.30 | 12.97 | 0.169249E+09 | 356.45 | 15-NOV-13:09 | 20.18 | 11.08 |
December | 0.513488E+09 | 2177.53 | 13-DEC-13:05 | 20.22 | 17.28 | 0.148254E+09 | 356.45 | 13-DEC-13:09 | 20.22 | 17.28 |
Annual Sum or Average | 0.299868E+11 | 0.217369E+10 | ||||||||
Minimum of Months | 0.274567E+09 | 1061.74 | 13.40 | 6.47 | 0.143383E+09 | 327.16 | 13.40 | 6.47 | ||
Maximum of Months | 0.503741E+10 | 11542.24 | 29.70 | 23.14 | 0.213822E+09 | 356.47 | 29.70 | 23.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121348E+10 | 4253.52 | 11-JAN-14:10 | 6.70 | 2.05 | 0.344838E+09 | 549.49 | 10-JAN-14:20 | 6.70 | 2.05 |
February | 0.175127E+10 | 9819.18 | 26-FEB-14:23 | 24.70 | 12.65 | 0.321646E+09 | 549.50 | 28-FEB-14:09 | 25.00 | 13.72 |
March | 0.340943E+10 | 8620.80 | 30-MAR-13:40 | 27.43 | 17.97 | 0.418503E+09 | 549.50 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.376524E+10 | 9606.89 | 16-APR-13:33 | 28.70 | 16.13 | 0.386448E+09 | 549.49 | 11-APR-13:20 | 28.70 | 16.13 |
May | 0.463668E+10 | 6859.95 | 30-MAY-14:00 | 30.60 | 21.03 | 0.431416E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.03 |
June | 0.573972E+10 | 7744.96 | 26-JUN-05:12 | 23.30 | 21.67 | 0.434885E+09 | 549.50 | 09-JUN-09:20 | 23.30 | 21.67 |
July | 0.608994E+10 | 11246.64 | 16-JUL-13:53 | 33.90 | 23.22 | 0.405392E+09 | 549.49 | 18-JUL-13:20 | 30.00 | 21.94 |
August | 0.716692E+10 | 11770.26 | 06-AUG-13:23 | 32.50 | 23.69 | 0.455353E+09 | 549.49 | 18-AUG-13:20 | 34.03 | 22.77 |
September | 0.552285E+10 | 11654.76 | 24-SEP-12:13 | 28.50 | 19.83 | 0.400687E+09 | 549.50 | 22-SEP-13:50 | 28.50 | 19.83 |
October | 0.460271E+10 | 12144.23 | 09-OCT-14:02 | 27.30 | 19.46 | 0.397242E+09 | 567.04 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.306155E+10 | 11587.98 | 11-NOV-12:43 | 20.82 | 11.71 | 0.378258E+09 | 549.49 | 14-NOV-14:30 | 19.15 | 8.88 |
December | 0.196664E+10 | 6101.36 | 08-DEC-14:00 | 12.80 | 5.54 | 0.349514E+09 | 549.48 | 08-DEC-10:39 | 12.80 | 5.54 |
Annual Sum or Average | 0.489264E+11 | 0.472418E+10 | ||||||||
Minimum of Months | 0.121348E+10 | 4253.52 | 6.70 | 2.05 | 0.321646E+09 | 549.48 | 6.70 | 2.05 | ||
Maximum of Months | 0.716692E+10 | 12144.23 | 33.90 | 23.69 | 0.455353E+09 | 567.04 | 34.03 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358453E+09 | 1074.68 | 11-JAN-16:40 | 6.47 | 1.83 | 0.199925E+09 | 324.76 | 11-JAN-16:49 | 6.28 | 1.74 |
February | 0.693561E+09 | 3864.65 | 27-FEB-17:00 | 22.20 | 11.44 | 0.190096E+09 | 347.84 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.190262E+10 | 5760.54 | 30-MAR-16:00 | 27.80 | 17.47 | 0.254923E+09 | 347.84 | 30-MAR-13:20 | 27.80 | 17.47 |
April | 0.259782E+10 | 7275.38 | 15-APR-17:08 | 26.42 | 15.32 | 0.242168E+09 | 347.85 | 17-APR-09:20 | 20.93 | 14.77 |
May | 0.361107E+10 | 11500.68 | 21-MAY-17:22 | 26.15 | 19.60 | 0.273511E+09 | 347.85 | 17-MAY-09:20 | 26.15 | 19.60 |
June | 0.462103E+10 | 11296.65 | 25-JUN-16:22 | 33.05 | 22.20 | 0.275651E+09 | 347.85 | 09-JUN-09:20 | 33.05 | 22.20 |
July | 0.477647E+10 | 11944.50 | 09-JUL-17:41 | 32.88 | 22.59 | 0.256818E+09 | 347.85 | 17-JUL-09:20 | 26.67 | 21.67 |
August | 0.507635E+10 | 11666.11 | 13-AUG-16:51 | 31.10 | 22.45 | 0.288374E+09 | 347.84 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.336672E+10 | 11085.98 | 04-SEP-16:23 | 28.05 | 22.55 | 0.253429E+09 | 347.85 | 20-SEP-09:20 | 20.93 | 15.94 |
October | 0.214471E+10 | 6314.98 | 08-OCT-17:13 | 25.77 | 18.43 | 0.243627E+09 | 347.85 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.124341E+10 | 3820.71 | 06-NOV-15:50 | 20.60 | 10.48 | 0.222959E+09 | 347.84 | 15-NOV-14:30 | 21.40 | 11.46 |
December | 0.613622E+09 | 1539.60 | 11-DEC-15:30 | 21.10 | 15.20 | 0.200632E+09 | 347.82 | 12-DEC-14:00 | 22.80 | 16.17 |
Annual Sum or Average | 0.310058E+11 | 0.290211E+10 | ||||||||
Minimum of Months | 0.358453E+09 | 1074.68 | 6.47 | 1.83 | 0.190096E+09 | 324.76 | 6.28 | 1.74 | ||
Maximum of Months | 0.507635E+10 | 11944.50 | 33.05 | 22.59 | 0.288374E+09 | 347.85 | 33.05 | 22.59 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102241E+09 | 14903.75 | 10-JAN-06:01 | -4.4 |
February | 12596649.37 | 13674.81 | 15-FEB-07:02 | 4.40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 1424448.10 | 14244.48 | 26-DEC-07:02 | 3.30 |
Annual Sum or Average | 0.116262E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.102241E+09 | 14903.75 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389393E+10 | 12797.86 | 14-JAN-06:12 | -6.7 |
February | 0.245163E+10 | 13940.37 | 13-FEB-06:06 | -5.6 |
March | 0.787728E+09 | 5773.56 | 18-MAR-06:03 | 2.70 |
April | 0.456217E+09 | 5307.51 | 06-APR-05:02 | 0.18 |
May | 0.175129E+09 | 2994.29 | 10-MAY-05:03 | 8.98 |
June | 75892307.36 | 2625.80 | 08-JUN-05:03 | 11.70 |
July | 22121860.72 | 2945.01 | 15-JUL-05:03 | 23.98 |
August | 20491115.22 | 3713.93 | 14-AUG-04:03 | 24.22 |
September | 0.137451E+09 | 2545.78 | 29-SEP-05:03 | 12.30 |
October | 0.633341E+09 | 6178.85 | 26-OCT-06:03 | 2.20 |
November | 0.113427E+10 | 10217.85 | 22-NOV-07:02 | -3.2 |
December | 0.231783E+10 | 12883.46 | 18-DEC-06:13 | -5.0 |
Annual Sum or Average | 0.121060E+11 | |||
Minimum of Months | 20491115.22 | 2545.78 | -6.7 | |
Maximum of Months | 0.389393E+10 | 13940.37 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187152E+10 | 7531.23 | 09-JAN-07:11 | -3.3 |
February | 0.105805E+10 | 7031.52 | 13-FEB-07:11 | -5.6 |
March | 0.259535E+09 | 1941.63 | 26-MAR-16:30 | 20.30 |
April | 67373944.32 | 1802.30 | 09-APR-15:20 | 21.70 |
May | 9690981.26 | 1488.85 | 07-MAY-09:13 | 23.87 |
June | 8323865.23 | 1602.60 | 11-JUN-09:02 | 23.58 |
July | 12054325.10 | 1799.95 | 09-JUL-16:21 | 33.60 |
August | 10301491.91 | 2026.70 | 27-AUG-15:12 | 31.70 |
September | 10789300.87 | 1761.24 | 24-SEP-11:33 | 28.13 |
October | 0.170710E+09 | 2898.32 | 08-OCT-15:13 | 27.20 |
November | 0.493364E+09 | 3349.27 | 11-NOV-12:43 | 20.82 |
December | 0.106574E+10 | 5418.66 | 26-DEC-07:12 | 3.30 |
Annual Sum or Average | 0.503745E+10 | |||
Minimum of Months | 8323865.23 | 1488.85 | -5.6 | |
Maximum of Months | 0.187152E+10 | 7531.23 | 33.60 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129727E+10 | 5391.53 | 02-JAN-07:12 | 3.30 |
February | 0.729198E+09 | 3890.43 | 13-FEB-07:01 | -5.6 |
March | 0.129497E+09 | 972.00 | 23-MAR-08:70 | 6.97 |
April | 18553629.31 | 1137.11 | 09-APR-16:43 | 21.70 |
May | 3885448.10 | 1255.35 | 29-MAY-14:13 | 28.67 |
June | 6121527.25 | 1147.85 | 18-JUN-13:50 | 29.22 |
July | 6921813.86 | 1439.77 | 15-JUL-05:03 | 23.98 |
August | 8697233.44 | 1554.59 | 14-AUG-04:03 | 24.22 |
September | 11556977.01 | 1449.25 | 17-SEP-11:30 | 26.40 |
October | 92709678.52 | 1905.38 | 22-OCT-11:33 | 21.67 |
November | 0.274890E+09 | 2309.49 | 12-NOV-13:33 | 18.53 |
December | 0.679805E+09 | 2360.44 | 26-DEC-08:09 | 3.30 |
Annual Sum or Average | 0.325911E+10 | |||
Minimum of Months | 3885448.10 | 972.00 | -5.6 | |
Maximum of Months | 0.129727E+10 | 5391.53 | 29.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.694266E+09 | 17113.00 | 09-JAN-05:02 | -2.2 |
February | 0.231374E+09 | 16250.54 | 13-FEB-05:01 | -5.1 |
March | 346474.05 | 2309.83 | 23-MAR-06:03 | 6.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 4714469.70 | 13533.53 | 24-NOV-07:03 | 8.30 |
December | 0.115109E+09 | 14809.72 | 07-DEC-07:02 | 2.62 |
Annual Sum or Average | 0.104581E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.694266E+09 | 17113.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252291E+10 | 30141.58 | 02-JAN-06:11 | 3.30 |
February | 0.113034E+10 | 29860.50 | 13-FEB-05:01 | -5.1 |
March | 36279075.52 | 24302.66 | 23-MAR-06:03 | 6.10 |
April | 3591433.04 | 19464.09 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 16927522.82 | 24438.66 | 30-OCT-06:03 | 8.90 |
November | 0.146860E+09 | 26129.03 | 22-NOV-06:01 | -3.3 |
December | 0.987870E+09 | 28790.67 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.484477E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.252291E+10 | 30141.58 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379525E+10 | 10195.18 | 09-JAN-04:53 | -2.2 |
February | 0.214002E+10 | 10496.66 | 12-FEB-08:22 | -11.4 |
March | 0.230272E+09 | 8679.82 | 23-MAR-05:11 | 6.10 |
April | 56089840.88 | 8418.07 | 06-APR-05:02 | 0.18 |
May | 129062.71 | 430.21 | 11-MAY-06:05 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.100592E+09 | 8737.01 | 26-OCT-05:11 | 2.20 |
November | 0.582256E+09 | 9486.32 | 22-NOV-05:02 | -2.9 |
December | 0.191409E+10 | 9945.69 | 04-DEC-05:11 | -2.8 |
Annual Sum or Average | 0.881870E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.4 | |
Maximum of Months | 0.379525E+10 | 10496.66 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202621E+10 | 9650.73 | 09-JAN-04:53 | -2.2 |
February | 0.109507E+10 | 9970.81 | 12-FEB-05:02 | -11.8 |
March | 0.105453E+09 | 8303.20 | 23-MAR-05:11 | 6.10 |
April | 23683725.08 | 7989.06 | 06-APR-05:02 | 0.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 59819931.18 | 8330.82 | 26-OCT-05:11 | 2.20 |
November | 0.259315E+09 | 9020.54 | 22-NOV-05:02 | -2.9 |
December | 0.909718E+09 | 9501.42 | 04-DEC-05:11 | -2.8 |
Annual Sum or Average | 0.447926E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.202621E+10 | 9970.81 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242464E+10 | 11748.57 | 09-JAN-04:53 | -2.2 |
February | 0.136836E+10 | 12056.53 | 12-FEB-05:02 | -11.8 |
March | 0.160399E+09 | 10033.92 | 23-MAR-05:11 | 6.10 |
April | 47832695.82 | 9646.39 | 06-APR-05:02 | 0.18 |
May | 369348.63 | 1231.16 | 11-MAY-06:05 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 75032335.45 | 9923.66 | 26-OCT-05:11 | 2.20 |
November | 0.320723E+09 | 10748.66 | 21-NOV-05:02 | -2.3 |
December | 0.104882E+10 | 11421.52 | 04-DEC-05:11 | -2.8 |
Annual Sum or Average | 0.544618E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.242464E+10 | 12056.53 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221909E+10 | 10341.90 | 09-JAN-04:53 | -2.2 |
February | 0.124178E+10 | 10753.70 | 12-FEB-08:22 | -11.4 |
March | 0.132009E+09 | 8790.75 | 23-MAR-05:11 | 6.10 |
April | 31440441.59 | 8433.47 | 06-APR-05:02 | 0.18 |
May | 76477.44 | 254.92 | 11-MAY-06:05 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 61543511.24 | 8766.15 | 26-OCT-05:11 | 2.20 |
November | 0.344582E+09 | 9659.75 | 22-NOV-05:02 | -2.9 |
December | 0.111453E+10 | 10222.24 | 04-DEC-05:11 | -2.8 |
Annual Sum or Average | 0.514506E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.4 | |
Maximum of Months | 0.221909E+10 | 10753.70 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238278E+10 | 7729.34 | 09-JAN-05:01 | -2.2 |
February | 0.126437E+10 | 7779.44 | 13-FEB-04:02 | -5.0 |
March | 78490737.64 | 6477.57 | 23-MAR-05:11 | 6.10 |
April | 18269569.84 | 6221.62 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 2836728.03 | 6085.62 | 26-OCT-06:03 | 2.20 |
November | 50170374.49 | 6562.26 | 22-NOV-06:01 | -3.3 |
December | 0.552275E+09 | 7070.52 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.434919E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.238278E+10 | 7779.44 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117132E+10 | 7553.63 | 09-JAN-05:01 | -2.2 |
February | 0.561757E+09 | 7433.94 | 13-FEB-05:01 | -5.1 |
March | 27814982.39 | 6232.53 | 23-MAR-05:11 | 6.10 |
April | 4350115.19 | 5971.81 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 1472164.85 | 3424.25 | 31-OCT-06:03 | 8.22 |
November | 10864317.00 | 6239.48 | 22-NOV-06:01 | -3.3 |
December | 0.203347E+09 | 6776.20 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.198092E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.117132E+10 | 7553.63 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338162E+10 | 9918.14 | 09-JAN-08:00 | -3.3 |
February | 0.209979E+10 | 10160.95 | 03-FEB-07:10 | -8.9 |
March | 0.775256E+09 | 8182.67 | 06-MAR-07:50 | 2.80 |
April | 0.434488E+09 | 8557.43 | 06-APR-06:10 | 1.20 |
May | 0.108624E+09 | 7375.18 | 11-MAY-06:10 | 8.17 |
June | 12949151.80 | 6443.33 | 08-JUN-06:07 | 12.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 13193036.35 | 3730.38 | 29-SEP-06:08 | 12.88 |
October | 0.375237E+09 | 8165.57 | 26-OCT-07:00 | 2.20 |
November | 0.752803E+09 | 9040.33 | 22-NOV-07:10 | -3.2 |
December | 0.133381E+10 | 9547.42 | 18-DEC-07:10 | -5.1 |
Annual Sum or Average | 0.928777E+10 | |||
Minimum of Months | 0.00 | 0.00 | -8.9 | |
Maximum of Months | 0.338162E+10 | 10160.95 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124551E+10 | 7590.46 | 09-JAN-05:01 | -2.2 |
February | 0.626819E+09 | 7454.50 | 13-FEB-05:01 | -5.1 |
March | 27686295.24 | 5994.84 | 23-MAR-05:11 | 6.10 |
April | 5003487.70 | 5934.01 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 998300.45 | 3424.85 | 31-OCT-06:03 | 8.22 |
November | 18546865.83 | 6255.19 | 22-NOV-06:01 | -3.3 |
December | 0.246644E+09 | 6782.47 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.217121E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.124551E+10 | 7590.46 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222708E+10 | 8499.09 | 09-JAN-04:53 | -2.2 |
February | 0.113373E+10 | 8682.02 | 13-FEB-04:02 | -5.0 |
March | 46679172.08 | 7019.35 | 22-MAR-05:11 | 5.93 |
April | 7924868.23 | 6768.47 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 12493932.77 | 6743.47 | 31-OCT-06:03 | 8.22 |
November | 0.157884E+09 | 7609.30 | 22-NOV-06:01 | -3.3 |
December | 0.812470E+09 | 8145.55 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.439827E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.222708E+10 | 8682.02 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117325E+10 | 7841.39 | 09-JAN-05:01 | -2.2 |
February | 0.559569E+09 | 8173.84 | 13-FEB-04:02 | -5.0 |
March | 24239422.88 | 6059.94 | 22-MAR-05:11 | 5.93 |
April | 3507489.09 | 6243.49 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 8881316.02 | 5686.33 | 26-OCT-06:03 | 2.20 |
November | 65427095.91 | 7008.05 | 22-NOV-06:01 | -3.3 |
December | 0.363504E+09 | 7579.11 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.219838E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.117325E+10 | 8173.84 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129779E+10 | 9926.50 | 02-JAN-06:11 | 3.30 |
February | 0.632343E+09 | 10073.48 | 12-FEB-05:02 | -11.8 |
March | 30928187.12 | 7938.14 | 22-MAR-06:03 | 5.50 |
April | 6648606.85 | 8000.00 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 10363491.07 | 7957.17 | 31-OCT-06:03 | 8.22 |
November | 70189523.62 | 8808.67 | 22-NOV-06:01 | -3.3 |
December | 0.386234E+09 | 9566.21 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.243450E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.129779E+10 | 10073.48 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126980E+10 | 7860.62 | 09-JAN-05:01 | -2.2 |
February | 0.631056E+09 | 8187.42 | 12-FEB-05:02 | -11.8 |
March | 26602279.15 | 5651.94 | 23-MAR-05:11 | 6.10 |
April | 4581107.07 | 6355.61 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 8474075.11 | 5604.74 | 26-OCT-06:03 | 2.20 |
November | 92338744.46 | 7007.25 | 22-NOV-06:01 | -3.3 |
December | 0.454933E+09 | 7599.67 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.248779E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.126980E+10 | 8187.42 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.448419E+09 | 671.47 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.403993E+09 | 714.87 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.433824E+09 | 677.08 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.373471E+09 | 611.75 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.389789E+09 | 403.50 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.383334E+09 | 397.58 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.364028E+09 | 477.49 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.412252E+09 | 581.83 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.385121E+09 | 639.55 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.431675E+09 | 733.65 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.433778E+09 | 724.46 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.437774E+09 | 673.25 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.489746E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.364028E+09 | 397.58 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.448419E+09 | 733.65 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.275010E+09 | 415.67 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.248604E+09 | 452.42 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271271E+09 | 423.82 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.235863E+09 | 369.94 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.248479E+09 | 239.55 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244631E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.231707E+09 | 255.86 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.261282E+09 | 348.67 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241788E+09 | 392.96 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.264353E+09 | 464.45 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.269114E+09 | 454.72 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.268796E+09 | 416.95 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306090E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.231707E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.275010E+09 | 464.45 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.423316E+09 | 662.03 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.386588E+09 | 714.87 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.428758E+09 | 676.09 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.374805E+09 | 614.22 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.394228E+09 | 411.62 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.387923E+09 | 405.64 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.368178E+09 | 507.27 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.414534E+09 | 588.83 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.382950E+09 | 633.93 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.413890E+09 | 733.65 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.414321E+09 | 720.65 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.411566E+09 | 662.93 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.480106E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.368178E+09 | 405.64 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.428758E+09 | 733.65 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.275595E+09 | 426.47 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.251239E+09 | 452.39 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274808E+09 | 430.79 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.237318E+09 | 397.88 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.249354E+09 | 352.38 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244986E+09 | 260.82 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.232845E+09 | 338.10 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.262703E+09 | 381.56 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.244640E+09 | 409.10 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.270425E+09 | 464.42 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.267326E+09 | 459.32 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.267911E+09 | 427.13 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307915E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.232845E+09 | 260.82 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.275595E+09 | 464.42 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.445763E+09 | 669.01 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.401700E+09 | 714.10 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.432490E+09 | 674.83 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.372731E+09 | 606.90 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.389759E+09 | 401.04 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.383118E+09 | 394.83 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.363747E+09 | 413.17 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.411731E+09 | 575.82 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.384135E+09 | 635.84 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.429735E+09 | 733.58 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.431526E+09 | 724.02 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.435361E+09 | 670.87 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.488180E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.363747E+09 | 394.83 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.445763E+09 | 733.58 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274110E+09 | 413.98 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.247915E+09 | 452.02 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.270754E+09 | 422.43 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.235574E+09 | 366.54 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.248199E+09 | 237.32 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244436E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.231436E+09 | 254.41 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.261034E+09 | 344.69 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241374E+09 | 390.52 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.263690E+09 | 464.41 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.268358E+09 | 454.31 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.267963E+09 | 415.31 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.305484E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.231436E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.274110E+09 | 464.41 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.422523E+09 | 659.09 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.386043E+09 | 714.10 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.428105E+09 | 673.79 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.373978E+09 | 609.49 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.393579E+09 | 409.70 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.387318E+09 | 403.42 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.367611E+09 | 498.44 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.413832E+09 | 583.16 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.382258E+09 | 629.94 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.412941E+09 | 733.58 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.413679E+09 | 720.03 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.410548E+09 | 660.03 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.479242E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.367611E+09 | 403.42 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.428105E+09 | 733.58 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.274698E+09 | 425.26 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.250314E+09 | 451.99 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274111E+09 | 429.72 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.236913E+09 | 395.80 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.248962E+09 | 349.13 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244607E+09 | 259.73 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.232431E+09 | 334.20 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.262161E+09 | 378.99 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.244025E+09 | 407.37 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.269581E+09 | 464.38 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.266630E+09 | 459.12 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.267130E+09 | 425.94 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307156E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.232431E+09 | 259.73 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.274698E+09 | 464.38 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.448416E+09 | 671.46 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.403991E+09 | 714.87 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.433823E+09 | 677.07 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.373471E+09 | 611.73 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.389789E+09 | 403.49 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.383334E+09 | 397.58 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.364027E+09 | 477.47 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.412251E+09 | 581.82 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.385120E+09 | 639.54 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.431673E+09 | 733.65 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.433776E+09 | 724.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.437772E+09 | 673.25 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.489744E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.364027E+09 | 397.58 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.448416E+09 | 733.65 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.275009E+09 | 415.67 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.248603E+09 | 452.42 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271270E+09 | 423.81 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.235863E+09 | 369.93 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.248479E+09 | 239.54 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244631E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.231707E+09 | 255.85 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.261281E+09 | 348.66 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241787E+09 | 392.96 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.264352E+09 | 464.45 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.269113E+09 | 454.72 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.268796E+09 | 416.94 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306089E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.231707E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.275009E+09 | 464.45 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.423315E+09 | 662.02 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.386587E+09 | 714.87 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.428757E+09 | 676.09 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.374804E+09 | 614.21 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.394227E+09 | 411.62 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.387922E+09 | 405.63 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.368177E+09 | 507.26 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.414533E+09 | 588.82 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.382949E+09 | 633.92 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.413889E+09 | 733.65 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.414320E+09 | 720.65 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.411565E+09 | 662.93 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.480105E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.368177E+09 | 405.63 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.428757E+09 | 733.65 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.275594E+09 | 426.47 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.251238E+09 | 452.39 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274807E+09 | 430.79 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.237318E+09 | 397.87 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.249354E+09 | 352.37 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.244986E+09 | 260.81 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.232845E+09 | 338.09 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.262703E+09 | 381.55 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.244640E+09 | 409.10 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.270425E+09 | 464.42 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.267326E+09 | 459.32 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.267910E+09 | 427.12 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307914E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.232845E+09 | 260.81 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.275594E+09 | 464.42 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.448419E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995524E+09 |
February | 0.901968E+09 | 0.403993E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2318984.60 | 0.847219E+09 |
March | 0.107774E+10 | 0.433824E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2792389.17 | 0.543016E+09 |
April | 0.956342E+09 | 0.373471E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6838233.39 | 0.347095E+09 |
May | 0.103597E+10 | 0.389789E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17641849.04 | 0.230749E+09 |
June | 0.103308E+10 | 0.383334E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73022983.14 | 0.115353E+09 |
July | 0.959235E+09 | 0.364028E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78564309.85 | 76910881.99 |
August | 0.107774E+10 | 0.412252E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76468219.68 | 48396138.75 |
September | 0.956342E+09 | 0.385121E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22887381.49 | 0.114551E+09 |
October | 0.994195E+09 | 0.431675E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7152215.79 | 0.367105E+09 |
November | 0.984487E+09 | 0.433778E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 985553.75 | 0.517702E+09 |
December | 0.959235E+09 | 0.437774E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.05 | 0.885990E+09 |
Annual Sum or Average | 0.119305E+11 | 0.489746E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288672E+09 | 0.508961E+10 |
Minimum of Months | 0.901968E+09 | 0.364028E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48396138.75 |
Maximum of Months | 0.107774E+10 | 0.448419E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78564309.85 | 0.995524E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.275010E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671659E+09 |
February | 0.571020E+09 | 0.248604E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 581996.53 | 0.577572E+09 |
March | 0.682301E+09 | 0.271271E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1617495.15 | 0.379789E+09 |
April | 0.605444E+09 | 0.235863E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3469629.95 | 0.242074E+09 |
May | 0.655854E+09 | 0.248479E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10209122.72 | 0.162149E+09 |
June | 0.654023E+09 | 0.244631E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47042516.15 | 79333002.28 |
July | 0.607275E+09 | 0.231707E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50119976.30 | 53527411.62 |
August | 0.682301E+09 | 0.261282E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49152595.69 | 33742872.70 |
September | 0.605444E+09 | 0.241788E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13405483.93 | 78703443.04 |
October | 0.629407E+09 | 0.264353E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3191202.34 | 0.255471E+09 |
November | 0.623262E+09 | 0.269114E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540069.44 | 0.356837E+09 |
December | 0.607275E+09 | 0.268796E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596723E+09 |
Annual Sum or Average | 0.755301E+10 | 0.306090E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179330E+09 | 0.348758E+10 |
Minimum of Months | 0.571020E+09 | 0.231707E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33742872.70 |
Maximum of Months | 0.682301E+09 | 0.275010E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50119976.30 | 0.671659E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.423316E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105422E+10 |
February | 0.901968E+09 | 0.386588E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114308.68 | 0.903644E+09 |
March | 0.107774E+10 | 0.428758E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2024813.61 | 0.596931E+09 |
April | 0.956342E+09 | 0.374805E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4997034.11 | 0.362021E+09 |
May | 0.103597E+10 | 0.394228E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16206328.27 | 0.233167E+09 |
June | 0.103308E+10 | 0.387923E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72614280.27 | 0.114031E+09 |
July | 0.959235E+09 | 0.368178E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77818056.03 | 76643554.94 |
August | 0.107774E+10 | 0.414534E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74219874.54 | 50037082.91 |
September | 0.956342E+09 | 0.382950E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18998718.43 | 0.119571E+09 |
October | 0.994195E+09 | 0.413890E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3053065.43 | 0.402765E+09 |
November | 0.984487E+09 | 0.414321E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574835E+09 |
December | 0.959235E+09 | 0.411566E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941878E+09 |
Annual Sum or Average | 0.119305E+11 | 0.480106E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270046E+09 | 0.542975E+10 |
Minimum of Months | 0.901968E+09 | 0.368178E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50037082.91 |
Maximum of Months | 0.107774E+10 | 0.428758E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77818056.03 | 0.105422E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.275595E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674487E+09 |
February | 0.570983E+09 | 0.251239E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 770940.73 | 0.578777E+09 |
March | 0.682256E+09 | 0.274808E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1363518.22 | 0.389248E+09 |
April | 0.605404E+09 | 0.237318E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3633766.10 | 0.244397E+09 |
May | 0.655811E+09 | 0.249354E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10469090.62 | 0.161541E+09 |
June | 0.653980E+09 | 0.244986E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46723715.18 | 80375804.60 |
July | 0.607235E+09 | 0.232845E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50051868.21 | 53627152.83 |
August | 0.682256E+09 | 0.262703E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47950822.76 | 36010577.57 |
September | 0.605404E+09 | 0.244640E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13489165.78 | 80638768.02 |
October | 0.629366E+09 | 0.270425E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2818137.33 | 0.257719E+09 |
November | 0.623221E+09 | 0.267326E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15657.60 | 0.359466E+09 |
December | 0.607235E+09 | 0.267911E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599546E+09 |
Annual Sum or Average | 0.755252E+10 | 0.307915E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177287E+09 | 0.351583E+10 |
Minimum of Months | 0.570983E+09 | 0.232845E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36010577.57 |
Maximum of Months | 0.682256E+09 | 0.275595E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50051868.21 | 0.674487E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.445763E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561910E+09 |
February | 0.901968E+09 | 0.401700E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1470097.18 | 0.467163E+09 |
March | 0.107774E+10 | 0.432490E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2502229.00 | 0.286217E+09 |
April | 0.956342E+09 | 0.372731E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5692930.17 | 0.171891E+09 |
May | 0.103597E+10 | 0.389759E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11436215.43 | 0.114553E+09 |
June | 0.103308E+10 | 0.383118E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42288629.77 | 57934462.72 |
July | 0.959235E+09 | 0.363747E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46725828.11 | 38878779.40 |
August | 0.107774E+10 | 0.411731E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44145071.60 | 24379500.21 |
September | 0.956342E+09 | 0.384135E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12842228.55 | 67550061.95 |
October | 0.994195E+09 | 0.429735E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3861631.58 | 0.221736E+09 |
November | 0.984487E+09 | 0.431526E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172331.61 | 0.314228E+09 |
December | 0.959235E+09 | 0.435361E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4386.99 | 0.531222E+09 |
Annual Sum or Average | 0.119305E+11 | 0.488180E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171142E+09 | 0.285766E+10 |
Minimum of Months | 0.901968E+09 | 0.363747E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24379500.21 |
Maximum of Months | 0.107774E+10 | 0.445763E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46725828.11 | 0.561910E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.274110E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381256E+09 |
February | 0.571020E+09 | 0.247915E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318904.85 | 0.321543E+09 |
March | 0.682301E+09 | 0.270754E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1215631.94 | 0.205862E+09 |
April | 0.605444E+09 | 0.235574E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2396947.86 | 0.124492E+09 |
May | 0.655854E+09 | 0.248199E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6048724.30 | 84271935.43 |
June | 0.654023E+09 | 0.244436E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26226763.61 | 41642235.70 |
July | 0.607275E+09 | 0.231436E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28173455.67 | 28416869.63 |
August | 0.682301E+09 | 0.261034E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27116204.14 | 18380195.28 |
September | 0.605444E+09 | 0.241374E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7488450.45 | 47340678.92 |
October | 0.629407E+09 | 0.263690E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1685193.81 | 0.156534E+09 |
November | 0.623262E+09 | 0.268358E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38988.65 | 0.220426E+09 |
December | 0.607275E+09 | 0.267963E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360900E+09 |
Annual Sum or Average | 0.755301E+10 | 0.305484E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100709E+09 | 0.199106E+10 |
Minimum of Months | 0.571020E+09 | 0.231436E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18380195.28 |
Maximum of Months | 0.682301E+09 | 0.274110E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28173455.67 | 0.381256E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.422523E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454649E+10 |
February | 0.901968E+09 | 0.386043E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 656328.06 | 0.336210E+10 |
March | 0.107774E+10 | 0.428105E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28005595.31 | 0.240019E+10 |
April | 0.956342E+09 | 0.373978E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142759E+09 | 0.136563E+10 |
May | 0.103597E+10 | 0.393579E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339198E+09 | 0.734802E+09 |
June | 0.103308E+10 | 0.387318E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959380E+09 | 0.282387E+09 |
July | 0.959235E+09 | 0.367611E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993571E+09 | 0.210285E+09 |
August | 0.107774E+10 | 0.413832E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109498E+10 | 0.131059E+09 |
September | 0.956342E+09 | 0.382258E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375571E+09 | 0.493145E+09 |
October | 0.994195E+09 | 0.412941E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68376354.51 | 0.187992E+10 |
November | 0.984487E+09 | 0.413679E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284028E+10 |
December | 0.959235E+09 | 0.410548E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347433E+10 |
Annual Sum or Average | 0.119305E+11 | 0.479242E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400250E+10 | 0.217206E+11 |
Minimum of Months | 0.901968E+09 | 0.367611E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131059E+09 |
Maximum of Months | 0.107774E+10 | 0.428105E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109498E+10 | 0.454649E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.274698E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382394E+09 |
February | 0.570983E+09 | 0.250314E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 396351.21 | 0.321028E+09 |
March | 0.682256E+09 | 0.274111E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 866651.13 | 0.211367E+09 |
April | 0.605404E+09 | 0.236913E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2224860.50 | 0.126845E+09 |
May | 0.655811E+09 | 0.248962E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5831588.72 | 84309057.70 |
June | 0.653980E+09 | 0.244607E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25728323.64 | 42442185.27 |
July | 0.607235E+09 | 0.232431E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27969493.03 | 28397636.53 |
August | 0.682256E+09 | 0.262161E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26261839.63 | 19796398.59 |
September | 0.605404E+09 | 0.244025E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7316282.88 | 48611921.51 |
October | 0.629366E+09 | 0.269581E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410956.66 | 0.158432E+09 |
November | 0.623221E+09 | 0.266630E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221463E+09 |
December | 0.607235E+09 | 0.267130E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361203E+09 |
Annual Sum or Average | 0.755252E+10 | 0.307156E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98006347.40 | 0.200629E+10 |
Minimum of Months | 0.570983E+09 | 0.232431E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19796398.59 |
Maximum of Months | 0.682256E+09 | 0.274698E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27969493.03 | 0.382394E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.448416E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866906E+09 |
February | 0.901968E+09 | 0.403991E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1732917.40 | 0.736659E+09 |
March | 0.107774E+10 | 0.433823E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2446317.58 | 0.480324E+09 |
April | 0.956342E+09 | 0.373471E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6211207.73 | 0.302782E+09 |
May | 0.103597E+10 | 0.389789E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15730948.66 | 0.199231E+09 |
June | 0.103308E+10 | 0.383334E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63168028.09 | 98615148.57 |
July | 0.959235E+09 | 0.364027E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68580848.04 | 65565018.29 |
August | 0.107774E+10 | 0.412251E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66254605.48 | 41205135.53 |
September | 0.956342E+09 | 0.385120E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19723529.73 | 0.102500E+09 |
October | 0.994195E+09 | 0.431673E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5932494.57 | 0.331628E+09 |
November | 0.984487E+09 | 0.433776E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 431257.72 | 0.469157E+09 |
December | 0.959235E+09 | 0.437772E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795972E+09 |
Annual Sum or Average | 0.119305E+11 | 0.489744E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250212E+09 | 0.449054E+10 |
Minimum of Months | 0.901968E+09 | 0.364027E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41205135.53 |
Maximum of Months | 0.107774E+10 | 0.448416E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68580848.04 | 0.866906E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.275009E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586217E+09 |
February | 0.421807E+09 | 0.248603E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430402.29 | 0.504008E+09 |
March | 0.502994E+09 | 0.271270E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1310501.62 | 0.336808E+09 |
April | 0.447140E+09 | 0.235863E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2981853.67 | 0.210977E+09 |
May | 0.484071E+09 | 0.248479E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8683631.20 | 0.139895E+09 |
June | 0.482240E+09 | 0.244631E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39403754.20 | 67856173.38 |
July | 0.448971E+09 | 0.231707E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42489709.29 | 45796596.34 |
August | 0.502994E+09 | 0.261281E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41245176.19 | 28891273.93 |
September | 0.447140E+09 | 0.241787E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11233494.29 | 70687595.41 |
October | 0.465148E+09 | 0.264352E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2653115.58 | 0.230530E+09 |
November | 0.460569E+09 | 0.269113E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 211304.35 | 0.324816E+09 |
December | 0.448971E+09 | 0.268796E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538440E+09 |
Annual Sum or Average | 0.557719E+10 | 0.306089E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150643E+09 | 0.308492E+10 |
Minimum of Months | 0.421807E+09 | 0.231707E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28891273.93 |
Maximum of Months | 0.502994E+09 | 0.275009E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42489709.29 | 0.586217E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.423315E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922657E+09 |
February | 0.901968E+09 | 0.386587E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98651.71 | 0.788287E+09 |
March | 0.107774E+10 | 0.428757E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1740462.29 | 0.524954E+09 |
April | 0.956342E+09 | 0.374804E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4409462.81 | 0.314914E+09 |
May | 0.103597E+10 | 0.394227E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14378003.93 | 0.201197E+09 |
June | 0.103308E+10 | 0.387922E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62626386.36 | 97638435.38 |
July | 0.959235E+09 | 0.368177E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67379927.43 | 65431977.70 |
August | 0.107774E+10 | 0.414533E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63316758.41 | 42658078.65 |
September | 0.956342E+09 | 0.382949E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16183207.25 | 0.106568E+09 |
October | 0.994195E+09 | 0.413889E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2559972.44 | 0.359746E+09 |
November | 0.984487E+09 | 0.414320E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516619E+09 |
December | 0.959235E+09 | 0.411565E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847319E+09 |
Annual Sum or Average | 0.119305E+11 | 0.480105E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232693E+09 | 0.478799E+10 |
Minimum of Months | 0.901968E+09 | 0.368177E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42658078.65 |
Maximum of Months | 0.107774E+10 | 0.428757E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67379927.43 | 0.922657E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.275594E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587668E+09 |
February | 0.570983E+09 | 0.251238E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530381.92 | 0.503458E+09 |
March | 0.682256E+09 | 0.274807E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1154363.28 | 0.342868E+09 |
April | 0.605404E+09 | 0.237318E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3097808.76 | 0.212863E+09 |
May | 0.655811E+09 | 0.249354E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8913269.26 | 0.139418E+09 |
June | 0.653980E+09 | 0.244986E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39549862.21 | 68797917.74 |
July | 0.607235E+09 | 0.232845E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42560989.55 | 45779232.36 |
August | 0.682256E+09 | 0.262703E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40579439.40 | 30697887.16 |
September | 0.605404E+09 | 0.244640E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11413445.03 | 71937524.06 |
October | 0.629366E+09 | 0.270425E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2309906.65 | 0.231567E+09 |
November | 0.623221E+09 | 0.267326E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324696E+09 |
December | 0.607235E+09 | 0.267910E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538163E+09 |
Annual Sum or Average | 0.755252E+10 | 0.307914E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150109E+09 | 0.309791E+10 |
Minimum of Months | 0.570983E+09 | 0.232845E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30697887.16 |
Maximum of Months | 0.682256E+09 | 0.275594E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42560989.55 | 0.587668E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121231E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1055477.41 | 0.103643E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2035740.20 | 0.686428E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5905463.59 | 0.417017E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16336001.30 | 0.269644E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72026367.00 | 0.128497E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81703222.37 | 84090457.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74883031.89 | 51889467.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19276985.46 | 0.145110E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4029782.82 | 0.487267E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425170.62 | 0.692723E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115482E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277677E+09 | 0.636622E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51889467.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81703222.37 | 0.121231E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149512E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2211454.86 | 0.128171E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2896796.62 | 0.854098E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8279883.57 | 0.531639E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21117400.62 | 0.348239E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91749795.30 | 0.167927E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102703E+09 | 0.110032E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94920358.61 | 68517700.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25986026.09 | 0.179314E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6274062.49 | 0.587358E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1798106.35 | 0.826539E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.00 | 0.139128E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357937E+09 | 0.784178E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68517700.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102703E+09 | 0.149512E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148514E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25608.29 | 0.127616E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016744.89 | 0.857609E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2101275.52 | 0.544140E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10517804.00 | 0.358105E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74135150.58 | 0.163027E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83714376.17 | 0.110006E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80946830.18 | 64561363.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17742243.04 | 0.171991E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2239468.99 | 0.574774E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507896.49 | 0.798473E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133908E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272947E+09 | 0.774307E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64561363.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83714376.17 | 0.148514E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 671.47 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1962.71 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 714.87 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 152.47 | 26-FEB-13:00 | 2388.66 | 12-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 677.08 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.38 | 11-MAR-16:00 | 1317.09 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 611.75 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 | 16-APR-11:53 | 763.93 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 403.50 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.90 | 07-MAY-11:43 | 611.05 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 397.58 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.01 | 11-JUN-15:00 | 452.63 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 477.49 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.80 | 08-JUL-18:53 | 325.61 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 581.83 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.64 | 06-AUG-13:52 | 210.42 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 639.55 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.40 | 24-SEP-12:57 | 406.35 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 733.65 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.24 | 08-OCT-13:53 | 785.67 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 724.46 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.00 | 19-NOV-15:00 | 1383.71 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 673.25 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 12-DEC-14:00 | 1938.43 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 397.58 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.42 | |||||
Maximum of Months | 1306.65 | 733.65 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 385.01 | 2388.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 415.67 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1304.24 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 452.42 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 26-FEB-15:30 | 1591.49 | 12-FEB-00:52 |
March | 827.22 | 01-MAR-10:09 | 423.82 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 | 11-MAR-16:00 | 870.53 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 369.94 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 | 08-APR-17:03 | 508.03 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 239.55 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 | 29-MAY-17:50 | 406.13 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.17 | 25-JUN-16:25 | 302.76 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 255.86 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.06 | 08-JUL-19:10 | 218.51 | 01-JUL-20:00 |
August | 827.22 | 01-AUG-09:09 | 348.67 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.75 | 06-AUG-14:08 | 138.99 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 392.96 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.72 | 17-SEP-15:00 | 269.16 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 464.45 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.95 | 09-OCT-15:50 | 523.48 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 454.72 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.29 | 19-NOV-15:00 | 921.42 | 30-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 416.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1286.55 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.99 | |||||
Maximum of Months | 827.22 | 464.45 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 244.75 | 1591.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 662.03 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1985.34 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 714.87 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 28-FEB-15:00 | 2406.31 | 11-FEB-18:05 |
March | 1306.65 | 01-MAR-10:09 | 676.09 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 | 30-MAR-16:00 | 1324.14 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 614.22 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.86 | 16-APR-14:07 | 766.08 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 411.62 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.50 | 07-MAY-11:43 | 614.01 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 405.64 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.73 | 11-JUN-15:00 | 453.48 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 507.27 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.48 | 08-JUL-19:10 | 326.13 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 588.83 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.28 | 06-AUG-14:05 | 211.66 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 633.93 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.85 | 17-SEP-14:50 | 407.77 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 733.65 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.70 | 09-OCT-15:47 | 814.65 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 720.65 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1384.10 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 662.93 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1971.38 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 405.64 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.66 | |||||
Maximum of Months | 1306.65 | 733.65 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 363.28 | 2406.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 426.47 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1316.78 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 452.39 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.64 | 26-FEB-13:00 | 1658.61 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 430.79 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 30-MAR-16:00 | 875.33 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 397.88 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.59 | 16-APR-11:53 | 505.69 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 352.38 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.35 | 07-MAY-11:43 | 413.42 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 260.82 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.80 | 25-JUN-15:58 | 306.50 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 338.10 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.53 | 08-JUL-19:10 | 219.60 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 381.56 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.17 | 06-AUG-14:05 | 142.94 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 409.10 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.30 | 24-SEP-12:53 | 268.95 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 464.42 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.93 | 08-OCT-13:43 | 528.55 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 459.32 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 19-NOV-15:00 | 921.91 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 427.13 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1284.36 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 260.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.94 | |||||
Maximum of Months | 827.17 | 464.42 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 241.17 | 1658.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 669.01 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1087.39 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 714.10 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.08 | 26-FEB-15:50 | 1311.10 | 12-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 674.83 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.99 | 11-MAR-18:05 | 765.76 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 606.90 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.96 | 08-APR-17:03 | 401.90 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 401.04 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.50 | 07-MAY-12:00 | 344.39 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 394.83 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.81 | 11-JUN-15:00 | 244.31 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 413.17 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.93 | 08-JUL-18:53 | 180.66 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 575.82 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.44 | 06-AUG-13:52 | 119.46 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 635.84 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.94 | 17-SEP-15:00 | 253.13 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 733.58 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.44 | 08-OCT-13:53 | 489.72 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 724.02 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 | 19-NOV-15:00 | 744.32 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 670.87 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 12-DEC-14:00 | 1243.16 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 394.83 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.46 | |||||
Maximum of Months | 1306.65 | 733.58 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 244.81 | 1311.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 413.98 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 723.94 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 452.02 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 26-FEB-15:50 | 871.74 | 12-FEB-00:52 |
March | 827.22 | 01-MAR-10:09 | 422.43 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 11-MAR-18:05 | 519.55 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 366.54 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 08-APR-17:03 | 268.66 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 237.32 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 | 29-MAY-18:00 | 235.10 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.71 | 11-JUN-15:00 | 168.79 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 254.41 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.44 | 08-JUL-18:53 | 119.79 | 28-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 344.69 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.17 | 06-AUG-13:52 | 79.72 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 390.52 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 | 17-SEP-15:00 | 168.41 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 464.41 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.22 | 09-OCT-15:50 | 336.10 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 454.31 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 | 19-NOV-15:00 | 500.99 | 07-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 415.31 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 831.62 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.72 | |||||
Maximum of Months | 827.22 | 464.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 136.44 | 871.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 659.09 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 23133.94 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 714.10 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.15 | 28-FEB-15:00 | 25079.18 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 673.79 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.65 | 30-MAR-16:10 | 14293.74 | 06-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 609.49 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3719.95 | 17-APR-16:10 | 15679.73 | 06-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 409.70 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.22 | 19-MAY-16:10 | 10261.86 | 11-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 403.42 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7177.57 | 06-JUN-16:05 | 7323.14 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 498.44 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8368.34 | 07-JUL-16:03 | 3547.10 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 583.16 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8010.95 | 01-AUG-16:03 | 3705.19 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 629.94 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5387.24 | 07-SEP-16:03 | 8045.51 | 14-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 733.58 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3918.80 | 10-OCT-16:05 | 14823.47 | 26-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 720.03 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19696.86 | 22-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 660.03 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21582.93 | 18-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 403.42 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3547.10 | |||||
Maximum of Months | 1306.65 | 733.58 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8368.34 | 25079.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 425.26 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 728.50 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 451.99 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.59 | 26-FEB-13:47 | 899.42 | 11-FEB-18:13 |
March | 827.17 | 01-MAR-10:09 | 429.72 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 30-MAR-16:00 | 522.28 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 395.80 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.69 | 16-APR-11:53 | 268.73 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 349.13 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.68 | 07-MAY-12:00 | 239.38 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 259.73 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.69 | 25-JUN-16:05 | 171.12 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 334.20 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.58 | 08-JUL-18:53 | 121.90 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 378.99 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.12 | 06-AUG-13:52 | 83.46 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 407.37 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 | 24-SEP-13:00 | 168.55 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 464.38 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.74 | 08-OCT-13:53 | 338.57 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 459.12 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 507.31 | 07-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 425.94 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 827.67 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 259.73 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.46 | |||||
Maximum of Months | 827.17 | 464.38 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 138.12 | 899.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 671.46 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1683.20 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 714.87 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.51 | 26-FEB-13:30 | 2004.71 | 12-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 677.07 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.35 | 11-MAR-16:00 | 1208.40 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 611.73 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 16-APR-12:00 | 673.08 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 403.49 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.19 | 07-MAY-12:07 | 548.37 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 397.58 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.59 | 11-JUN-14:53 | 391.15 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 477.47 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.84 | 08-JUL-18:53 | 281.89 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 581.82 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.47 | 06-AUG-13:52 | 187.25 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 639.54 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.98 | 17-SEP-15:00 | 374.38 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 733.65 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.89 | 08-OCT-14:00 | 724.52 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 724.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 19-NOV-15:00 | 1159.18 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 673.25 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1800.20 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 397.58 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.25 | |||||
Maximum of Months | 1306.65 | 733.65 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 348.59 | 2004.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 415.67 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1116.86 | 07-JAN-18:05 |
February | 805.43 | 01-FEB-08:09 | 452.42 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.82 | 26-FEB-16:00 | 1335.46 | 12-FEB-00:52 |
March | 805.43 | 01-MAR-08:09 | 423.81 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 11-MAR-16:00 | 800.04 | 22-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 369.93 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 | 08-APR-17:03 | 447.97 | 05-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 239.54 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.21 | 29-MAY-18:00 | 364.68 | 10-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.91 | 25-JUN-15:52 | 261.87 | 07-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 255.85 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.29 | 08-JUL-18:53 | 186.84 | 28-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 348.66 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.93 | 06-AUG-14:08 | 123.90 | 25-AUG-05:00 |
September | 805.43 | 01-SEP-07:10 | 392.96 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 | 17-SEP-15:00 | 248.24 | 29-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 464.45 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.34 | 09-OCT-15:50 | 483.34 | 28-OCT-04:00 |
November | 805.43 | 01-NOV-07:10 | 454.72 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.82 | 19-NOV-15:00 | 772.04 | 30-NOV-22:03 |
December | 805.43 | 01-DEC-08:09 | 416.94 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1195.63 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.90 | |||||
Maximum of Months | 805.43 | 464.45 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 205.93 | 1335.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 662.02 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1701.12 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 714.87 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 28-FEB-15:00 | 2056.14 | 11-FEB-18:13 |
March | 1306.65 | 01-MAR-10:09 | 676.09 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 30-MAR-16:00 | 1214.62 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 614.21 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.86 | 08-APR-17:20 | 675.10 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 411.62 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.95 | 07-MAY-12:13 | 550.84 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 405.63 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.53 | 11-JUN-14:53 | 391.82 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 507.26 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.84 | 08-JUL-18:53 | 282.35 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 588.82 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.85 | 06-AUG-14:05 | 188.32 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 633.92 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.59 | 17-SEP-14:50 | 375.57 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 733.65 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 09-OCT-15:27 | 747.39 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 720.65 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1159.51 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 662.93 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1829.59 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 405.63 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.32 | |||||
Maximum of Months | 1306.65 | 733.65 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 321.53 | 2056.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 426.47 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1128.37 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 452.39 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 26-FEB-12:50 | 1415.87 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 430.79 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 | 30-MAR-16:00 | 803.37 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 397.87 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.17 | 16-APR-12:00 | 446.00 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 352.37 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 | 07-MAY-12:07 | 370.59 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 260.81 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.72 | 25-JUN-15:54 | 264.75 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 338.09 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.32 | 08-JUL-19:10 | 189.83 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 381.55 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.26 | 06-AUG-13:52 | 127.00 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 409.10 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 | 24-SEP-13:00 | 247.81 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 464.42 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 | 08-OCT-13:43 | 486.52 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 459.32 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 772.38 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 427.12 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1192.83 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 260.81 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.00 | |||||
Maximum of Months | 827.17 | 464.42 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 207.26 | 1415.87 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2350.69 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.94 | 26-FEB-14:33 | 2886.35 | 12-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 | 11-MAR-16:00 | 1778.40 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.16 | 16-APR-11:53 | 934.39 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.97 | 07-MAY-12:00 | 776.82 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.85 | 11-JUN-15:00 | 530.79 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.08 | 08-JUL-18:53 | 378.08 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.06 | 06-AUG-13:52 | 254.30 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.29 | 17-SEP-15:00 | 538.60 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.81 | 08-OCT-13:53 | 1073.88 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.58 | 19-NOV-15:00 | 1599.60 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2714.87 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.30 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.85 | 2886.35 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2967.33 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 | 26-FEB-13:00 | 3610.31 | 12-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.81 | 11-MAR-16:00 | 2190.19 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.48 | 16-APR-12:00 | 1197.92 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.12 | 07-MAY-12:20 | 990.31 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.66 | 11-JUN-14:53 | 684.34 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.85 | 08-JUL-18:53 | 480.14 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.67 | 06-AUG-13:52 | 325.21 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.72 | 17-SEP-15:00 | 670.01 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.70 | 08-OCT-13:53 | 1293.06 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.10 | 19-NOV-15:00 | 1971.21 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 12-DEC-14:00 | 3283.49 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.21 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.66 | 3610.31 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3168.87 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 26-FEB-15:00 | 3750.67 | 11-FEB-18:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.60 | 30-MAR-16:00 | 2001.65 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.61 | 16-APR-11:53 | 1144.52 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.56 | 07-MAY-11:43 | 889.03 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.57 | 11-JUN-15:00 | 672.69 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.55 | 08-JUL-18:50 | 524.28 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.89 | 06-AUG-13:52 | 312.28 | 23-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.47 | 06-SEP-12:00 | 579.19 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.32 | 08-OCT-13:53 | 1191.51 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.68 | 19-NOV-15:00 | 1990.03 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2960.47 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.28 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.55 | 3750.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8079.66 | 31-JAN-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11809.29 | 28-FEB-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15616.57 | 31-MAR-07:07 | 18105.02 | 10466.10 | 38274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16326.09 | 17-APR-16:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21601.03 | 22-MAY-06:03 | 5082.11 | 4651.60 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32317.03 | 26-JUN-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32928.97 | 15-JUL-05:03 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32504.37 | 21-AUG-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30074.34 | 18-SEP-06:02 | 6352.64 | 5814.50 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17321.71 | 11-OCT-16:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15371.54 | 07-NOV-08:10 | 18105.02 | 10466.10 | 38274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10639.47 | 14-DEC-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8079.66 | 2541.06 | 1550.53 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32928.97 | 18105.02 | 10466.10 | 38274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1088.72 | 28-JAN-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.49 |
February | 2928.88 | 26-FEB-15:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 |
March | 6381.26 | 30-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.44 | 0.00 |
April | 7421.74 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 | 0.00 |
May | 8296.87 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.44 | 0.00 |
June | 8901.91 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 0.00 |
July | 9806.27 | 07-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.48 | 0.00 |
August | 9963.77 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.51 | 0.00 |
September | 8512.63 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 0.00 |
October | 6526.56 | 10-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 | 0.00 |
November | 2383.54 | 05-NOV-14:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 |
December | 1529.67 | 12-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1088.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9963.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 146.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2005.34 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1577.85 |
February | 1918.31 | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1732.02 |
March | 1956.03 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.31 |
April | 2647.81 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.26 |
May | 3445.81 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 | 0.00 |
June | 4235.52 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.22 |
July | 4365.40 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 |
August | 4171.82 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 |
September | 3595.38 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.64 | 0.00 |
October | 2436.90 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 0.00 |
November | 1720.00 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.62 |
December | 1775.02 | 09-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1720.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4365.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.64 | 1732.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1670.77 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.47 |
February | 2030.16 | 23-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.40 |
March | 2300.85 | 03-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.47 |
April | 2713.33 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.59 |
May | 3226.94 | 30-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.31 | 0.00 |
June | 3615.80 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 |
July | 4113.07 | 10-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | 0.00 |
August | 4088.97 | 07-AUG-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 | 0.00 |
September | 3949.13 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 0.00 |
October | 2856.65 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 | 0.00 |
November | 1338.10 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 |
December | 1935.05 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1338.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4113.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | 345.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7293.56 | 31-JAN-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8373.91 | 28-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11872.69 | 31-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13136.31 | 17-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15254.46 | 30-MAY-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26180.85 | 26-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27445.34 | 10-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27711.14 | 14-AUG-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23229.73 | 11-SEP-06:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13626.76 | 11-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9493.01 | 06-NOV-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8094.35 | 13-DEC-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7293.56 | 0.00 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27711.14 | 6035.01 | 3488.70 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7323.85 | 20-JAN-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8659.62 | 28-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14145.34 | 30-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15613.85 | 17-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17916.57 | 30-MAY-15:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29510.91 | 26-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30287.24 | 10-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30851.09 | 14-AUG-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17608.10 | 11-SEP-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14788.09 | 11-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8741.34 | 06-NOV-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7954.82 | 13-DEC-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7323.85 | 0.00 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30851.09 | 6035.01 | 3488.70 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1524.88 | 31-JAN-16:40 | 1272.23 | 394.49 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 |
February | 2268.90 | 28-FEB-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
March | 4451.61 | 30-MAR-15:50 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 58.11 | 0.00 |
April | 4848.33 | 19-APR-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 | 0.00 |
May | 6364.57 | 30-MAY-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.98 | 0.00 |
June | 11068.69 | 25-JUN-16:22 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 318.49 | 0.00 |
July | 11296.62 | 16-JUL-13:53 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 122.19 | 0.00 |
August | 11015.02 | 06-AUG-14:43 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 242.14 | 0.00 |
September | 6112.86 | 06-SEP-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.54 | 0.00 |
October | 4186.93 | 02-OCT-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 | 0.00 |
November | 1763.59 | 02-NOV-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
December | 1641.76 | 13-DEC-15:00 | 1306.65 | 398.49 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1524.88 | 267.84 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11296.62 | 1306.65 | 398.49 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 318.49 | 34.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 999.08 | 31-JAN-15:00 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 |
February | 2018.13 | 27-FEB-10:40 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.51 |
March | 3550.40 | 30-MAR-11:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
April | 7416.69 | 16-APR-10:43 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 |
May | 11225.04 | 07-MAY-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.14 |
June | 11810.47 | 25-JUN-10:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 | 0.00 |
July | 11833.82 | 09-JUL-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.95 |
August | 11142.24 | 13-AUG-11:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 0.00 |
September | 11117.12 | 04-SEP-09:32 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 |
October | 4388.72 | 11-OCT-10:30 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 |
November | 1765.86 | 06-NOV-10:40 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.63 |
December | 1064.00 | 12-DEC-15:00 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 999.08 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11833.82 | 827.22 | 222.09 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 | 86.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4267.07 | 11-JAN-14:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 |
February | 10605.35 | 26-FEB-14:33 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 |
March | 9325.09 | 30-MAR-13:50 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.32 | 0.00 |
April | 11358.96 | 16-APR-14:03 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 | 0.00 |
May | 9342.27 | 29-MAY-13:43 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 | 0.00 |
June | 11998.25 | 25-JUN-16:22 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 318.09 | 0.00 |
July | 13160.01 | 09-JUL-13:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 200.17 | 0.00 |
August | 13559.81 | 27-AUG-13:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 183.08 | 0.00 |
September | 13788.18 | 24-SEP-13:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 46.11 | 0.00 |
October | 13797.04 | 09-OCT-13:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 |
November | 10482.21 | 11-NOV-15:13 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.91 |
December | 5740.33 | 08-DEC-14:10 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4267.07 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13797.04 | 1306.65 | 350.81 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 318.09 | 218.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1082.76 | 11-JAN-16:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 |
February | 4077.31 | 27-FEB-17:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
March | 6249.98 | 30-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 0.00 |
April | 12265.37 | 09-APR-17:03 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.38 |
May | 12915.31 | 21-MAY-17:32 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.15 |
June | 12494.51 | 25-JUN-16:22 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 187.69 | 0.00 |
July | 12863.31 | 30-JUL-17:42 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 | 0.00 |
August | 12751.53 | 13-AUG-17:02 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 0.00 |
September | 11906.40 | 04-SEP-16:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 0.00 |
October | 10863.65 | 09-OCT-16:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 | 0.00 |
November | 3765.20 | 06-NOV-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 |
December | 1484.30 | 11-DEC-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1082.76 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12915.31 | 805.38 | 222.08 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 187.69 | 64.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1436.56 | 31-JAN-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
February | 1673.36 | 28-FEB-15:10 | 2544.47 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 0.00 |
March | 2317.26 | 30-MAR-16:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 | 0.00 |
April | 2752.92 | 19-APR-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
May | 4242.21 | 30-MAY-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
June | 5067.66 | 28-JUN-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 | 0.00 |
July | 6201.10 | 17-JUL-06:03 | 803.52 | 387.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 |
August | 5781.39 | 07-AUG-06:03 | 803.52 | 704.25 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 |
September | 5333.32 | 06-SEP-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.63 | 0.00 |
October | 3661.28 | 02-OCT-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.14 | 0.00 |
November | 1836.98 | 05-NOV-13:13 | 200.88 | 58.46 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 |
December | 1634.86 | 13-DEC-13:30 | 1272.23 | 380.64 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1436.56 | 200.88 | 58.46 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6201.10 | 2544.47 | 704.25 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 | 19.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 962.47 | 31-JAN-14:50 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 |
February | 1640.44 | 27-FEB-10:40 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 |
March | 2397.66 | 14-MAR-11:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 |
April | 4126.11 | 17-APR-10:10 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
May | 5129.85 | 30-MAY-10:00 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
June | 8472.83 | 04-JUN-08:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 |
July | 9679.95 | 09-JUL-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 |
August | 9837.26 | 27-AUG-09:52 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 |
September | 8624.65 | 04-SEP-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 |
October | 4287.16 | 10-OCT-10:20 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
November | 2225.87 | 06-NOV-10:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.10 |
December | 1074.14 | 13-DEC-12:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 962.47 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9837.26 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 45.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2226.78 | 28-JAN-14:50 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
February | 5457.94 | 21-FEB-14:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.80 |
March | 7309.05 | 30-MAR-16:10 | 401.76 | 194.89 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.65 | 0.00 |
April | 7538.62 | 17-APR-16:10 | 401.76 | 194.89 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3719.95 | 0.00 |
May | 8550.22 | 30-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4167.21 | 0.00 |
June | 9283.94 | 06-JUN-16:30 | 401.76 | 194.89 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6758.57 | 0.00 |
July | 9685.11 | 07-JUL-16:50 | 401.76 | 194.89 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 7280.46 | 0.00 |
August | 10563.12 | 06-AUG-13:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 127.56 | 0.00 |
September | 10571.28 | 24-SEP-12:13 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 0.00 |
October | 11110.27 | 09-OCT-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
November | 10525.03 | 12-NOV-14:13 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.82 |
December | 5188.17 | 12-DEC-14:00 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2226.78 | 137.54 | 58.46 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11110.27 | 1306.65 | 350.81 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 7280.46 | 190.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1004.90 | 20-JAN-16:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 |
February | 2770.51 | 27-FEB-17:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
March | 4044.31 | 30-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 |
April | 4678.58 | 17-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 | 0.00 |
May | 9731.22 | 21-MAY-17:22 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 |
June | 9849.29 | 25-JUN-17:23 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 | 0.00 |
July | 9908.38 | 09-JUL-17:12 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 | 0.00 |
August | 9960.05 | 13-AUG-17:02 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 0.00 |
September | 9540.49 | 24-SEP-16:53 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 0.00 |
October | 5701.91 | 09-OCT-17:23 | 0.00 | 37.01 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 |
November | 3616.88 | 06-NOV-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.70 |
December | 1261.85 | 11-DEC-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1004.90 | 0.00 | 37.01 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9960.05 | 805.38 | 222.08 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 | 26.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1522.75 | 31-JAN-16:30 | 1272.23 | 386.67 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 |
February | 2158.66 | 28-FEB-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 0.00 |
March | 3840.84 | 30-MAR-16:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 0.00 |
April | 4341.77 | 18-APR-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
May | 5647.06 | 30-MAY-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 | 0.00 |
June | 7716.78 | 26-JUN-05:12 | 535.68 | 326.87 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 |
July | 9459.16 | 16-JUL-13:13 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 178.71 | 0.00 |
August | 7138.57 | 07-AUG-06:03 | 803.52 | 705.67 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
September | 5508.48 | 06-SEP-14:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 | 0.00 |
October | 3813.87 | 02-OCT-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 0.00 |
November | 1783.89 | 05-NOV-13:03 | 200.88 | 58.46 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 |
December | 1671.80 | 13-DEC-13:30 | 1272.23 | 383.68 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1522.75 | 200.88 | 58.46 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9459.16 | 1306.65 | 705.67 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 178.71 | 29.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1061.74 | 31-JAN-15:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 |
February | 3877.57 | 23-FEB-13:02 | 4027.14 | 1110.46 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.41 |
March | 5113.74 | 15-MAR-12:02 | 4027.14 | 1110.46 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.37 |
April | 7584.30 | 16-APR-10:13 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 |
May | 10762.12 | 07-MAY-09:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.76 |
June | 11181.00 | 25-JUN-10:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 | 0.00 |
July | 11542.24 | 09-JUL-09:42 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 |
August | 11466.35 | 27-AUG-09:52 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
September | 10648.65 | 04-SEP-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 |
October | 5770.46 | 11-OCT-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
November | 3360.43 | 06-NOV-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.53 |
December | 2177.53 | 13-DEC-13:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1061.74 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11542.24 | 4027.14 | 1110.46 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 | 138.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4253.52 | 11-JAN-14:10 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.69 |
February | 9819.18 | 26-FEB-14:23 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.47 |
March | 8620.80 | 30-MAR-13:40 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 0.00 |
April | 9606.89 | 16-APR-13:33 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 0.00 |
May | 6859.95 | 30-MAY-14:00 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 | 0.00 |
June | 7744.96 | 26-JUN-05:12 | 535.68 | 326.87 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 |
July | 11246.64 | 16-JUL-13:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 106.10 | 0.00 |
August | 11770.26 | 06-AUG-13:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 189.05 | 0.00 |
September | 11654.76 | 24-SEP-12:13 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 0.00 |
October | 12144.23 | 09-OCT-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
November | 11587.98 | 11-NOV-12:43 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.26 |
December | 6101.36 | 08-DEC-14:00 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4253.52 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12144.23 | 1306.65 | 350.81 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 189.05 | 229.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1074.68 | 11-JAN-16:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 |
February | 3864.65 | 27-FEB-17:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
March | 5760.54 | 30-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 | 0.00 |
April | 7275.38 | 15-APR-17:08 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
May | 11500.68 | 21-MAY-17:22 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.59 |
June | 11296.65 | 25-JUN-16:22 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 162.55 | 0.00 |
July | 11944.50 | 09-JUL-17:41 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 0.00 |
August | 11666.11 | 13-AUG-16:51 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 57.23 | 0.00 |
September | 11085.98 | 04-SEP-16:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | 0.00 |
October | 6314.98 | 08-OCT-17:13 | 0.00 | 37.01 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
November | 3820.71 | 06-NOV-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 |
December | 1539.60 | 11-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1074.68 | 0.00 | 37.01 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11944.50 | 805.38 | 222.08 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 162.55 | 50.25 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.129701E+12 | 223625.88 | 02-JAN-07:10 | 0.305589E+11 | 65269.10 | 27-JAN-07:30 |
February | 0.101181E+12 | 219556.23 | 13-FEB-07:10 | 0.199363E+11 | 73758.87 | 03-FEB-07:30 |
March | 0.923732E+11 | 99614.51 | 23-MAR-06:10 | 0.125795E+11 | 27504.13 | 18-MAR-07:10 |
April | 0.902526E+11 | 95647.16 | 17-APR-15:50 | 0.107225E+11 | 30720.66 | 06-APR-06:19 |
May | 0.108615E+12 | 112449.60 | 30-MAY-15:09 | 0.104904E+11 | 9740.85 | 01-MAY-11:20 |
June | 0.127756E+12 | 122003.70 | 27-JUN-15:39 | 0.990601E+10 | 9597.41 | 01-JUN-11:30 |
July | 0.134904E+12 | 134609.36 | 07-JUL-15:00 | 0.964611E+10 | 9495.25 | 03-JUL-11:39 |
August | 0.147030E+12 | 133123.80 | 01-AUG-15:20 | 0.100317E+11 | 9490.03 | 31-AUG-11:50 |
September | 0.111846E+12 | 126043.40 | 07-SEP-15:00 | 0.961281E+10 | 9578.42 | 28-SEP-11:09 |
October | 0.941742E+11 | 105591.11 | 10-OCT-15:39 | 0.104782E+11 | 27795.24 | 26-OCT-06:19 |
November | 0.878722E+11 | 127071.75 | 22-NOV-07:10 | 0.129425E+11 | 46723.96 | 21-NOV-07:30 |
December | 0.101581E+12 | 180204.23 | 26-DEC-07:10 | 0.164029E+11 | 59698.50 | 18-DEC-07:00 |
Annual Sum or Average | 0.132729E+13 | 0.163308E+12 | ||||
Minimum of Months | 0.878722E+11 | 95647.16 | 0.961281E+10 | 9490.03 | ||
Maximum of Months | 0.147030E+12 | 223625.88 | 0.305589E+11 | 73758.87 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.840517E+10 | 18762.05 | 27-JAN-12:50 | 0.00 | 0.00 |
February | 0.906654E+10 | 21668.49 | 24-FEB-12:50 | 0.00 | 0.00 |
March | 0.138306E+11 | 25602.78 | 18-MAR-12:50 | 0.00 | 0.00 |
April | 0.161800E+11 | 26293.87 | 06-APR-12:39 | 0.00 | 0.00 |
May | 0.181426E+11 | 26270.55 | 10-MAY-12:20 | 0.00 | 0.00 |
June | 0.184868E+11 | 25687.90 | 10-JUN-12:30 | 0.00 | 0.00 |
July | 0.177161E+11 | 24780.10 | 24-JUL-12:30 | 0.00 | 0.00 |
August | 0.163715E+11 | 23787.67 | 02-AUG-12:30 | 0.00 | 0.00 |
September | 0.120747E+11 | 22695.96 | 14-SEP-12:30 | 0.00 | 0.00 |
October | 0.111383E+11 | 21852.15 | 25-OCT-12:30 | 0.00 | 0.00 |
November | 0.834208E+10 | 17796.38 | 07-NOV-12:30 | 0.00 | 0.00 |
December | 0.747425E+10 | 16660.90 | 02-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.157229E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.747425E+10 | 16660.90 | 0.00 | 0.00 | |
Maximum of Months | 0.184868E+11 | 26293.87 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.142232E+11 | 0.365310E+10 | 0.545046E+11 | 0.976613E+09 | 0.336557E+10 | 12379742.02 | 0.517282E+11 | 0.123742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129027E+11 | 0.300361E+10 | 0.493409E+11 | 0.883921E+09 | 0.302863E+10 | 11196021.66 | 0.289710E+11 | 0.303961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149591E+11 | 0.296875E+10 | 0.567112E+11 | 0.102250E+10 | 0.350731E+10 | 12675672.10 | 0.429632E+10 | 0.889538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132528E+11 | 0.253274E+10 | 0.526212E+11 | 0.940464E+09 | 0.384382E+10 | 11960507.72 | 0.125111E+10 | 0.157984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141931E+11 | 0.230669E+10 | 0.556079E+11 | 0.999280E+09 | 0.528108E+10 | 12527707.06 | 0.183000E+09 | 0.300313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140799E+11 | 0.211349E+10 | 0.546110E+11 | 0.983615E+09 | 0.752356E+10 | 12231776.97 | 25506973.59 | 0.484063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132297E+11 | 0.224387E+10 | 0.536070E+11 | 0.955937E+09 | 0.830696E+10 | 12256437.81 | 0.00 | 0.565483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147866E+11 | 0.249202E+10 | 0.567112E+11 | 0.102238E+10 | 0.923681E+10 | 12675672.10 | 0.00 | 0.627688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133515E+11 | 0.271475E+10 | 0.525990E+11 | 0.940293E+09 | 0.616368E+10 | 11960507.72 | 24107930.07 | 0.360409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140980E+11 | 0.315544E+10 | 0.545158E+11 | 0.976683E+09 | 0.413031E+10 | 12379742.02 | 0.201834E+10 | 0.152672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139935E+11 | 0.343584E+10 | 0.533244E+11 | 0.958362E+09 | 0.313002E+10 | 12059151.09 | 0.690815E+10 | 0.610987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137940E+11 | 0.375866E+10 | 0.535958E+11 | 0.956209E+09 | 0.308018E+10 | 12256437.81 | 0.241473E+11 | 0.223642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166864E+12 | 0.343790E+11 | 0.647750E+12 | 0.116163E+11 | 0.605979E+11 | 0.146559E+09 | 0.119553E+12 | 0.286380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129027E+11 | 0.211349E+10 | 0.493409E+11 | 0.883921E+09 | 0.302863E+10 | 11196021.66 | 0.00 | 0.123742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149591E+11 | 0.375866E+10 | 0.567112E+11 | 0.102250E+10 | 0.923681E+10 | 12675672.10 | 0.517282E+11 | 0.627688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.192830E+11 | 0.00 | 0.112759E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.973149E+10 | 0.00 | 0.102048E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.114177E+10 | 0.00 | 0.114377E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.350413E+09 | 0.00 | 0.103721E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.104904E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.990601E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.964611E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.100317E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.961281E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.208586E+09 | 0.00 | 0.102696E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.254344E+10 | 0.00 | 0.103991E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.550414E+10 | 0.00 | 0.108988E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.387629E+11 | 0.00 | 0.124545E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.961281E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.192830E+11 | 0.00 | 0.114377E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 16984.71 | 03-JAN-08:09 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 828.88 | 03-JAN-08:20 | 5682.43 | 02-JAN-07:10 | 6.85 | 02-JAN-07:10 | 189631.84 | 02-JAN-07:10 |
February | 17467.42 | 01-FEB-08:09 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 829.52 | 01-FEB-08:20 | 5688.46 | 13-FEB-07:10 | 6.85 | 01-FEB-06:10 | 185556.15 | 13-FEB-07:10 |
March | 17082.41 | 21-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 829.01 | 21-MAR-07:19 | 6560.85 | 30-MAR-15:00 | 6.85 | 20-MAR-07:10 | 68504.88 | 23-MAR-06:10 |
April | 16432.35 | 03-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 828.15 | 03-APR-07:19 | 7555.06 | 17-APR-15:50 | 6.85 | 26-APR-07:10 | 53733.13 | 07-APR-06:10 |
May | 14614.06 | 24-MAY-07:30 | 3824.74 | 01-MAY-05:10 | 40437.79 | 01-MAY-07:10 | 825.76 | 24-MAY-07:40 | 10067.46 | 30-MAY-15:09 | 6.85 | 01-MAY-05:10 | 12921.43 | 11-MAY-06:10 |
June | 14318.41 | 23-JUN-07:10 | 3824.74 | 01-JUN-05:10 | 40437.79 | 01-JUN-07:10 | 825.37 | 23-JUN-07:19 | 10874.16 | 26-JUN-15:30 | 6.85 | 01-JUN-05:10 | 4380.69 | 08-JUN-06:10 |
July | 15123.71 | 27-JUL-07:10 | 3824.74 | 01-JUL-05:10 | 40437.79 | 03-JUL-07:10 | 826.43 | 27-JUL-07:19 | 12525.19 | 10-JUL-15:30 | 6.85 | 09-JUL-16:30 | 0.00 | 01-JUL-00:10 |
August | 16150.50 | 24-AUG-07:10 | 3824.74 | 01-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 827.78 | 24-AUG-07:19 | 13159.34 | 02-AUG-15:39 | 6.85 | 13-AUG-16:19 | 0.00 | 01-AUG-00:10 |
September | 16680.85 | 29-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 828.48 | 29-SEP-07:19 | 12310.37 | 07-SEP-15:30 | 6.85 | 01-SEP-05:10 | 4299.44 | 29-SEP-06:19 |
October | 17654.39 | 30-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 829.76 | 30-OCT-07:19 | 8721.23 | 11-OCT-15:30 | 6.85 | 01-OCT-05:10 | 60911.16 | 26-OCT-06:10 |
November | 17541.88 | 01-NOV-07:10 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 829.61 | 01-NOV-07:19 | 4050.97 | 06-NOV-15:09 | 6.85 | 13-NOV-12:09 | 95658.06 | 22-NOV-07:10 |
December | 16998.75 | 06-DEC-08:09 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.90 | 06-DEC-08:20 | 4086.83 | 18-DEC-07:10 | 6.85 | 01-DEC-06:10 | 147827.04 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14318.41 | 3824.74 | 40437.79 | 825.37 | 4050.97 | 6.85 | 0.00 | |||||||
Maximum of Months | 17654.39 | 3824.74 | 40437.79 | 829.76 | 13159.34 | 6.85 | 189631.84 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 12507.30 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 16626.33 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 31906.48 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 35848.65 | 17-APR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 49646.48 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 58191.58 | 27-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 68964.38 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 67325.39 | 01-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 60735.33 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 43848.24 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 17897.56 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17399.11 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12507.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 68964.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 223625.88 | 02-JAN-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 5682.43 | 6.85 | 189631.84 | 0.00 | 0.00 |
February | 219556.23 | 13-FEB-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 5688.46 | 6.85 | 185556.15 | 0.00 | 0.00 |
March | 99614.51 | 23-MAR-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 2798.02 | 6.85 | 68504.88 | 0.00 | 0.00 |
April | 95647.16 | 17-APR-15:50 | 13903.46 | 38454.47 | 0.00 | 823.69 | 7555.06 | 6.85 | 0.00 | 34903.63 | 0.00 |
May | 112449.60 | 30-MAY-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 10067.46 | 6.85 | 0.00 | 49193.66 | 0.00 |
June | 122003.70 | 27-JUN-15:39 | 13903.46 | 38454.47 | 0.00 | 823.69 | 10662.29 | 6.85 | 0.00 | 58152.94 | 0.00 |
July | 134609.36 | 07-JUL-15:00 | 13903.46 | 38454.47 | 0.00 | 823.69 | 12456.50 | 6.85 | 0.00 | 68964.38 | 0.00 |
August | 133123.80 | 01-AUG-15:20 | 13903.46 | 38454.47 | 0.00 | 823.69 | 12609.94 | 6.85 | 0.00 | 67325.39 | 0.00 |
September | 126043.40 | 07-SEP-15:00 | 13903.46 | 38454.47 | 0.00 | 823.69 | 12119.60 | 6.85 | 0.00 | 60735.33 | 0.00 |
October | 105591.11 | 10-OCT-15:39 | 13903.46 | 38454.47 | 0.00 | 823.69 | 8598.94 | 6.85 | 0.00 | 43803.70 | 0.00 |
November | 127071.75 | 22-NOV-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3102.09 | 6.85 | 95658.06 | 0.00 | 0.00 |
December | 180204.23 | 26-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 4065.58 | 6.85 | 147827.04 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 95647.16 | 5890.77 | 18346.02 | 0.00 | 243.23 | 2798.02 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 223625.88 | 13903.46 | 38454.47 | 3824.74 | 823.69 | 12609.94 | 6.85 | 189631.84 | 68964.38 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 56432.69 | 14-JAN-07:30 | 0.00 | 10017.34 | 27-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 64896.15 | 03-FEB-07:30 | 0.00 | 10021.07 | 06-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 19033.79 | 18-MAR-06:00 | 0.00 | 9977.65 | 02-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 21907.83 | 06-APR-06:19 | 0.00 | 9861.31 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9740.85 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9597.41 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9495.25 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9490.03 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9578.42 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 19008.47 | 26-OCT-06:19 | 0.00 | 9726.49 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 39329.49 | 22-NOV-07:30 | 0.00 | 9850.47 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 50870.33 | 18-DEC-07:00 | 0.00 | 9965.65 | 27-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9490.03 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 64896.15 | 0.00 | 10021.07 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.60 | 1.67 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 0.33 | 19.80 | 0.33 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 19.64 | 2.00 | 19.64 | 0.00 | 19.64 | 0.00 | 19.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.80 | 1.67 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.04 | 1.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
February | 0.83 | 18.29 | 0.50 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 18.58 | 0.50 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
Annual Sum or Average | 3.17 | 18.75 | 2.50 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.04 | 1.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 16.84 | 9.00 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
February | 12.33 | 16.25 | 6.00 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.43 | 1.17 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.51 | 2.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.37 | 1.33 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
December | 5.67 | 17.90 | 3.33 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
Annual Sum or Average | 36.00 | 16.80 | 18.33 | 17.29 | 8.17 | 18.62 | 5.17 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.67 | 17.90 | 9.00 | 18.46 | 4.67 | 27.51 | 2.67 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 15.54 | 2.33 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
February | 7.33 | 15.05 | 1.33 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.83 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.52 | 3.50 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.66 | 8.00 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.74 | 11.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.71 | 8.83 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.54 | 1.83 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
December | 2.67 | 16.17 | 0.50 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
Annual Sum or Average | 21.33 | 15.47 | 4.17 | 15.61 | 38.83 | 22.89 | 34.50 | 24.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.00 | 16.97 | 2.33 | 16.97 | 13.83 | 27.74 | 11.50 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 16.15 | 3.00 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
February | 6.17 | 15.82 | 2.00 | 16.19 | 0.83 | 17.23 | 0.83 | 18.09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.46 | 1.00 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.38 | 0.83 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.49 | 2.50 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.54 | 5.67 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.67 | 5.33 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.57 | 2.83 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 3.67 | 27.64 |
November | 0.33 | 17.11 | 0.00 | 17.11 | 1.33 | 25.39 | 1.33 | 26.31 |
December | 1.67 | 17.58 | 0.67 | 18.01 | 0.00 | 18.01 | 0.00 | 18.01 |
Annual Sum or Average | 17.50 | 16.19 | 5.67 | 16.54 | 27.50 | 22.53 | 24.00 | 24.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.33 | 17.58 | 3.00 | 18.01 | 7.50 | 27.67 | 5.67 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 15.58 | 2.83 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
February | 7.50 | 15.04 | 2.50 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.58 | 2.00 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.91 | 2.00 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.97 | 4.00 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28.11 | 5.83 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.05 | 4.50 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.64 | 2.83 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.57 | 1.17 | 27.58 |
November | 0.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
December | 1.83 | 16.52 | 0.33 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
Annual Sum or Average | 20.17 | 15.48 | 5.67 | 15.57 | 39.50 | 23.05 | 22.33 | 24.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 16.96 | 2.83 | 16.96 | 11.67 | 28.11 | 5.83 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 19.37 | 3.33 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
February | 2.67 | 19.13 | 2.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.31 | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Annual Sum or Average | 6.67 | 19.27 | 6.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.37 | 3.33 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.87 | 0.17 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
February | 0.50 | 17.39 | 0.17 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.53 | 2.67 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.52 | 6.33 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.53 | 4.83 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.45 | 1.33 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.58 | 0.33 | 18.01 | 15.50 | 26.85 | 15.50 | 27.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.87 | 0.17 | 18.24 | 6.33 | 27.53 | 6.33 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.33 | 18.13 | 55.17 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
February | 34.00 | 18.16 | 33.67 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
March | 14.83 | 19.46 | 14.83 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
April | 5.67 | 18.87 | 5.67 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
May | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.70 | 4.67 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 24.91 | 14.67 | 24.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 25.19 | 23.50 | 25.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.17 | 8.00 | 25.17 |
October | 3.33 | 19.61 | 3.33 | 19.61 | 7.33 | 22.97 | 7.33 | 24.02 |
November | 15.67 | 19.48 | 15.67 | 19.48 | 1.83 | 19.92 | 1.83 | 20.31 |
December | 23.33 | 18.35 | 23.33 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
Annual Sum or Average | 152.33 | 18.50 | 151.83 | 18.50 | 60.00 | 19.62 | 60.00 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 0.00 | 18.13 |
Maximum of Months | 55.33 | 20.44 | 55.17 | 20.44 | 23.50 | 25.19 | 23.50 | 25.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.85 | 0.17 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
February | 0.50 | 17.46 | 0.17 | 17.90 | 0.00 | 17.90 | 0.00 | 17.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.44 | 0.50 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.64 | 2.17 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.77 | 3.33 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.74 | 3.00 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.46 | 1.83 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.50 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.62 | 0.33 | 18.04 | 21.00 | 27.16 | 11.33 | 27.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.85 | 0.17 | 18.21 | 7.00 | 27.77 | 3.33 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.68 | 2.83 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
February | 4.67 | 17.13 | 2.67 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.34 | 0.83 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 18.53 | 0.67 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 9.83 | 17.93 | 6.17 | 18.30 | 1.17 | 18.92 | 0.83 | 19.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 18.68 | 2.83 | 19.04 | 1.17 | 27.34 | 0.83 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 17.40 | 0.50 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
February | 2.50 | 15.60 | 0.67 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.54 | 2.67 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.71 | 5.17 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.64 | 10.00 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.66 | 7.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.56 | 1.83 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.82 | 0.17 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
Annual Sum or Average | 4.83 | 16.51 | 1.33 | 16.73 | 28.33 | 25.69 | 27.67 | 26.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 17.82 | 0.67 | 18.17 | 10.50 | 27.71 | 10.00 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.21 | 0.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
February | 1.17 | 15.87 | 0.67 | 15.87 | 0.83 | 19.47 | 0.83 | 21.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.43 | 2.17 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.50 | 4.67 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.47 | 2.17 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.58 | 4.17 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 2.17 | 27.52 |
December | 0.17 | 19.09 | 0.17 | 19.09 | 0.17 | 21.83 | 0.17 | 23.19 |
Annual Sum or Average | 2.50 | 17.18 | 1.50 | 17.37 | 17.17 | 25.58 | 16.83 | 26.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.09 | 0.67 | 19.09 | 4.83 | 27.58 | 4.67 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 17.23 | 0.33 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
February | 2.50 | 15.62 | 1.00 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.52 | 1.33 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.72 | 1.67 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.85 | 3.17 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.96 | 5.00 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.95 | 3.50 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.59 | 2.67 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.54 | 1.00 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.85 | 0.17 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
Annual Sum or Average | 4.67 | 16.43 | 1.50 | 16.50 | 31.00 | 25.95 | 18.33 | 26.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 17.85 | 1.00 | 18.18 | 9.50 | 27.96 | 5.00 | 27.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.74 | 109.50 | 21.56 | 109.50 | 21.44 |
February | 449.83 | 22.44 | 29.33 | 22.35 | 29.33 | 22.28 |
March | 374.33 | 23.54 | 19.00 | 23.58 | 0.00 | 23.58 |
April | 174.50 | 23.69 | 115.83 | 24.04 | 0.00 | 24.04 |
May | 20.50 | 23.81 | 307.33 | 24.43 | 0.00 | 24.43 |
June | 6.17 | 23.88 | 410.17 | 24.32 | 0.00 | 24.32 |
July | 0.00 | 0.00 | 483.33 | 24.36 | 0.00 | 24.36 |
August | 0.00 | 0.00 | 511.33 | 24.30 | 0.00 | 24.30 |
September | 2.00 | 23.43 | 399.83 | 24.40 | 0.00 | 24.40 |
October | 118.83 | 23.57 | 154.33 | 24.09 | 0.00 | 24.09 |
November | 377.83 | 23.57 | 7.50 | 23.60 | 0.00 | 23.60 |
December | 480.67 | 22.71 | 0.33 | 22.71 | 0.00 | 22.71 |
Annual Sum or Average | 2506.67 | 22.84 | 2547.83 | 23.52 | 138.83 | 23.45 |
Minimum of Months | 0.00 | 0.00 | 0.33 | 21.56 | 0.00 | 21.44 |
Maximum of Months | 502.00 | 23.88 | 511.33 | 24.43 | 109.50 | 24.43 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.93 | 269.50 | 20.79 | 269.50 | 20.73 |
February | 454.00 | 21.56 | 106.50 | 21.37 | 106.50 | 21.24 |
March | 457.00 | 22.80 | 17.67 | 22.85 | 0.00 | 22.85 |
April | 281.50 | 23.26 | 69.00 | 23.48 | 0.00 | 23.48 |
May | 86.17 | 23.41 | 239.00 | 24.06 | 0.00 | 24.06 |
June | 29.00 | 23.61 | 374.67 | 24.22 | 0.00 | 24.22 |
July | 9.00 | 23.22 | 458.00 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 486.00 | 24.26 | 0.00 | 24.26 |
September | 44.67 | 23.23 | 311.17 | 24.20 | 0.00 | 24.20 |
October | 296.50 | 22.99 | 78.17 | 23.23 | 0.00 | 23.23 |
November | 483.00 | 22.59 | 0.67 | 22.59 | 0.67 | 22.58 |
December | 497.00 | 21.50 | 70.83 | 21.42 | 70.83 | 21.35 |
Annual Sum or Average | 3139.83 | 22.17 | 2481.17 | 22.81 | 447.50 | 22.65 |
Minimum of Months | 0.00 | 0.00 | 0.67 | 20.79 | 0.00 | 20.73 |
Maximum of Months | 502.00 | 23.61 | 486.00 | 24.28 | 269.50 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 355.67 | 20.40 | 355.67 | 20.34 |
February | 453.67 | 21.15 | 168.83 | 20.92 | 168.83 | 20.80 |
March | 466.50 | 22.33 | 39.67 | 22.32 | 23.00 | 22.25 |
April | 302.50 | 22.96 | 58.67 | 23.16 | 1.00 | 23.15 |
May | 118.00 | 23.30 | 234.17 | 23.93 | 0.00 | 23.93 |
June | 36.50 | 23.48 | 374.67 | 24.21 | 0.00 | 24.21 |
July | 12.67 | 23.02 | 456.83 | 24.30 | 0.00 | 24.30 |
August | 0.83 | 23.54 | 489.50 | 24.28 | 0.00 | 24.28 |
September | 92.33 | 23.11 | 266.50 | 24.00 | 0.00 | 24.00 |
October | 374.67 | 22.55 | 59.83 | 22.74 | 1.83 | 22.73 |
November | 488.17 | 21.84 | 63.83 | 21.70 | 63.83 | 21.59 |
December | 497.00 | 20.94 | 239.00 | 20.75 | 239.00 | 20.65 |
Annual Sum or Average | 3344.83 | 21.77 | 2807.17 | 22.37 | 853.17 | 22.12 |
Minimum of Months | 0.83 | 20.53 | 39.67 | 20.40 | 0.00 | 20.34 |
Maximum of Months | 502.00 | 23.54 | 489.50 | 24.30 | 355.67 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 424.83 | 19.93 | 424.83 | 19.90 |
February | 451.33 | 20.64 | 270.17 | 20.42 | 270.17 | 20.32 |
March | 463.17 | 21.67 | 119.50 | 21.56 | 93.50 | 21.39 |
April | 311.00 | 22.43 | 112.67 | 22.71 | 30.50 | 22.62 |
May | 131.17 | 22.98 | 275.33 | 23.85 | 6.33 | 23.86 |
June | 54.33 | 24.20 | 410.00 | 24.33 | 23.50 | 24.39 |
July | 56.67 | 25.21 | 476.00 | 24.54 | 48.00 | 24.63 |
August | 48.67 | 25.24 | 501.33 | 24.44 | 45.33 | 24.51 |
September | 148.67 | 23.30 | 287.00 | 23.99 | 24.67 | 24.06 |
October | 401.17 | 21.94 | 100.17 | 22.16 | 39.33 | 22.12 |
November | 484.17 | 21.16 | 175.83 | 20.92 | 175.83 | 20.79 |
December | 497.00 | 20.30 | 356.50 | 20.14 | 356.50 | 20.07 |
Annual Sum or Average | 3549.33 | 21.40 | 3509.33 | 22.02 | 1538.50 | 21.76 |
Minimum of Months | 48.67 | 20.03 | 100.17 | 19.93 | 6.33 | 19.90 |
Maximum of Months | 502.00 | 25.24 | 501.33 | 24.54 | 424.83 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 401.17 | 20.08 | 401.17 | 20.03 |
February | 446.83 | 21.01 | 224.83 | 20.69 | 224.83 | 20.52 |
March | 413.83 | 22.17 | 100.00 | 22.14 | 52.83 | 21.97 |
April | 212.17 | 22.65 | 172.67 | 23.30 | 21.67 | 23.25 |
May | 105.17 | 23.65 | 343.50 | 24.26 | 22.33 | 24.35 |
June | 58.67 | 25.35 | 450.00 | 24.53 | 41.83 | 24.66 |
July | 85.50 | 25.94 | 478.33 | 24.77 | 77.00 | 24.95 |
August | 70.17 | 25.93 | 507.83 | 24.62 | 68.83 | 24.77 |
September | 120.17 | 23.66 | 339.00 | 24.23 | 33.83 | 24.34 |
October | 308.33 | 22.05 | 149.50 | 22.59 | 34.83 | 22.53 |
November | 466.17 | 21.53 | 116.67 | 21.28 | 116.33 | 21.10 |
December | 497.00 | 20.50 | 294.67 | 20.25 | 294.67 | 20.14 |
Annual Sum or Average | 3286.00 | 21.72 | 3578.17 | 22.41 | 1390.17 | 22.20 |
Minimum of Months | 58.67 | 20.20 | 100.00 | 20.08 | 21.67 | 20.03 |
Maximum of Months | 502.00 | 25.94 | 507.83 | 24.77 | 401.17 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.67 | 20.85 | 293.33 | 20.49 | 291.00 | 20.32 |
February | 403.50 | 21.17 | 205.83 | 20.98 | 190.50 | 20.79 |
March | 350.17 | 21.96 | 133.33 | 22.15 | 59.83 | 21.95 |
April | 242.67 | 22.49 | 156.67 | 23.09 | 25.33 | 23.03 |
May | 130.50 | 23.00 | 286.67 | 23.91 | 8.50 | 23.93 |
June | 67.17 | 24.16 | 402.67 | 24.33 | 26.83 | 24.41 |
July | 67.67 | 25.48 | 469.17 | 24.60 | 59.17 | 24.73 |
August | 59.17 | 25.59 | 503.00 | 24.53 | 55.67 | 24.63 |
September | 125.00 | 23.67 | 321.50 | 24.23 | 35.50 | 24.36 |
October | 279.33 | 22.19 | 189.67 | 22.98 | 38.67 | 23.01 |
November | 382.83 | 21.70 | 137.17 | 21.75 | 93.00 | 21.53 |
December | 458.33 | 21.05 | 228.67 | 20.72 | 218.50 | 20.50 |
Annual Sum or Average | 3057.00 | 21.88 | 3327.67 | 22.60 | 1102.50 | 22.39 |
Minimum of Months | 59.17 | 20.85 | 133.33 | 20.49 | 8.50 | 20.32 |
Maximum of Months | 490.67 | 25.59 | 503.00 | 24.60 | 291.00 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 375.50 | 20.08 | 375.50 | 20.00 |
February | 434.17 | 20.82 | 245.00 | 20.60 | 239.33 | 20.46 |
March | 388.00 | 21.74 | 143.17 | 21.87 | 78.00 | 21.67 |
April | 254.33 | 22.54 | 172.83 | 23.14 | 31.33 | 23.12 |
May | 128.00 | 23.29 | 318.50 | 24.06 | 18.17 | 24.13 |
June | 68.83 | 24.62 | 421.17 | 24.43 | 36.33 | 24.54 |
July | 68.67 | 25.55 | 473.33 | 24.64 | 61.00 | 24.77 |
August | 62.33 | 25.68 | 504.33 | 24.56 | 59.50 | 24.68 |
September | 131.33 | 23.68 | 314.83 | 24.21 | 39.50 | 24.34 |
October | 339.17 | 21.98 | 142.67 | 22.52 | 37.00 | 22.51 |
November | 448.00 | 21.36 | 154.33 | 21.16 | 142.83 | 20.98 |
December | 493.67 | 20.56 | 300.83 | 20.29 | 300.83 | 20.17 |
Annual Sum or Average | 3318.50 | 21.61 | 3566.50 | 22.31 | 1419.33 | 22.09 |
Minimum of Months | 62.33 | 20.26 | 142.67 | 20.08 | 18.17 | 20.00 |
Maximum of Months | 502.00 | 25.68 | 504.33 | 24.64 | 375.50 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.29 | 424.33 | 20.22 | 424.33 | 20.20 |
February | 454.00 | 20.70 | 260.83 | 20.54 | 260.83 | 20.47 |
March | 503.33 | 21.58 | 82.83 | 21.45 | 79.83 | 21.34 |
April | 431.00 | 22.32 | 37.17 | 22.32 | 23.83 | 22.28 |
May | 237.00 | 23.14 | 175.50 | 23.60 | 12.00 | 23.64 |
June | 46.33 | 23.97 | 385.50 | 24.22 | 12.17 | 24.26 |
July | 28.83 | 24.71 | 474.50 | 24.38 | 22.50 | 24.41 |
August | 19.50 | 25.31 | 507.33 | 24.34 | 19.50 | 24.38 |
September | 76.67 | 23.83 | 332.67 | 24.23 | 20.17 | 24.29 |
October | 374.00 | 22.64 | 84.17 | 22.91 | 13.00 | 22.94 |
November | 480.67 | 21.87 | 53.00 | 21.75 | 52.00 | 21.64 |
December | 497.00 | 20.77 | 283.17 | 20.64 | 283.17 | 20.57 |
Annual Sum or Average | 3650.33 | 21.64 | 3101.00 | 22.20 | 1223.33 | 21.97 |
Minimum of Months | 19.50 | 20.29 | 37.17 | 20.22 | 12.00 | 20.20 |
Maximum of Months | 503.33 | 25.31 | 507.33 | 24.38 | 424.33 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.49 | 380.50 | 20.39 | 380.50 | 20.35 |
February | 452.00 | 21.17 | 205.83 | 20.90 | 205.83 | 20.77 |
March | 464.33 | 22.28 | 39.17 | 22.21 | 27.67 | 22.12 |
April | 303.67 | 22.79 | 92.33 | 23.11 | 10.00 | 23.11 |
May | 126.83 | 23.40 | 285.50 | 24.15 | 13.83 | 24.21 |
June | 31.17 | 25.11 | 445.33 | 24.43 | 19.17 | 24.50 |
July | 50.17 | 25.91 | 478.17 | 24.67 | 44.17 | 24.80 |
August | 36.67 | 26.27 | 511.50 | 24.56 | 36.67 | 24.67 |
September | 59.33 | 24.38 | 400.00 | 24.43 | 25.33 | 24.52 |
October | 244.83 | 22.77 | 161.83 | 23.40 | 13.83 | 23.43 |
November | 448.83 | 22.42 | 35.33 | 22.39 | 21.67 | 22.31 |
December | 497.00 | 21.08 | 201.50 | 20.88 | 201.50 | 20.76 |
Annual Sum or Average | 3216.83 | 21.98 | 3237.00 | 22.68 | 1000.17 | 22.48 |
Minimum of Months | 31.17 | 20.49 | 35.33 | 20.39 | 10.00 | 20.35 |
Maximum of Months | 502.00 | 26.27 | 511.50 | 24.67 | 380.50 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 20.59 | 291.83 | 20.32 | 289.00 | 20.18 |
February | 417.33 | 20.98 | 187.33 | 20.78 | 176.83 | 20.59 |
March | 422.00 | 21.96 | 75.17 | 22.01 | 38.67 | 21.87 |
April | 354.17 | 22.38 | 81.33 | 22.62 | 19.33 | 22.57 |
May | 234.83 | 22.91 | 207.17 | 23.53 | 27.33 | 23.57 |
June | 117.00 | 23.67 | 390.33 | 24.11 | 67.00 | 24.11 |
July | 99.67 | 24.11 | 473.33 | 24.34 | 91.83 | 24.32 |
August | 112.67 | 24.49 | 509.00 | 24.44 | 111.67 | 24.45 |
September | 102.50 | 23.83 | 393.17 | 24.33 | 51.50 | 24.39 |
October | 236.33 | 22.65 | 213.33 | 23.52 | 40.00 | 23.58 |
November | 362.83 | 22.25 | 75.00 | 22.57 | 15.50 | 22.47 |
December | 466.17 | 21.35 | 126.83 | 21.15 | 112.50 | 20.94 |
Annual Sum or Average | 3422.17 | 22.01 | 3023.83 | 22.68 | 1041.17 | 22.53 |
Minimum of Months | 99.67 | 20.59 | 75.00 | 20.32 | 15.50 | 20.18 |
Maximum of Months | 496.67 | 24.49 | 509.00 | 24.44 | 289.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.51 | 369.00 | 20.37 | 369.00 | 20.32 |
February | 445.83 | 20.99 | 215.33 | 20.77 | 214.67 | 20.65 |
March | 442.17 | 22.06 | 71.17 | 22.07 | 42.00 | 21.96 |
April | 321.17 | 22.70 | 91.67 | 23.03 | 11.00 | 23.04 |
May | 146.33 | 23.36 | 268.17 | 24.02 | 14.33 | 24.07 |
June | 41.67 | 24.59 | 424.83 | 24.39 | 18.50 | 24.45 |
July | 44.67 | 25.61 | 478.50 | 24.57 | 39.17 | 24.67 |
August | 34.50 | 26.18 | 511.67 | 24.54 | 34.50 | 24.64 |
September | 65.17 | 24.38 | 397.00 | 24.44 | 27.33 | 24.52 |
October | 267.33 | 22.82 | 155.67 | 23.39 | 13.50 | 23.43 |
November | 431.33 | 22.24 | 46.17 | 22.22 | 30.67 | 22.13 |
December | 494.50 | 21.08 | 214.67 | 20.86 | 214.67 | 20.75 |
Annual Sum or Average | 3236.67 | 21.90 | 3243.83 | 22.61 | 1029.33 | 22.40 |
Minimum of Months | 34.50 | 20.51 | 46.17 | 20.37 | 11.00 | 20.32 |
Maximum of Months | 502.00 | 26.18 | 511.67 | 24.57 | 369.00 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.24 | 410.17 | 20.14 | 410.17 | 20.11 |
February | 451.67 | 20.83 | 227.17 | 20.61 | 227.17 | 20.49 |
March | 461.67 | 21.98 | 74.33 | 21.94 | 49.17 | 21.82 |
April | 296.67 | 22.71 | 92.17 | 23.02 | 10.67 | 23.01 |
May | 107.83 | 23.27 | 298.17 | 24.01 | 4.83 | 24.02 |
June | 34.00 | 24.32 | 421.67 | 24.32 | 16.50 | 24.36 |
July | 39.33 | 25.02 | 481.17 | 24.48 | 33.50 | 24.53 |
August | 30.67 | 25.16 | 507.00 | 24.39 | 30.67 | 24.43 |
September | 100.50 | 23.64 | 314.50 | 24.16 | 24.50 | 24.23 |
October | 382.17 | 22.34 | 88.67 | 22.61 | 21.33 | 22.62 |
November | 481.33 | 21.60 | 92.17 | 21.41 | 92.17 | 21.28 |
December | 497.00 | 20.62 | 302.00 | 20.45 | 302.00 | 20.37 |
Annual Sum or Average | 3384.83 | 21.60 | 3309.17 | 22.27 | 1222.67 | 22.02 |
Minimum of Months | 30.67 | 20.24 | 74.33 | 20.14 | 4.83 | 20.11 |
Maximum of Months | 502.00 | 25.16 | 507.00 | 24.48 | 410.17 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.34 | 313.17 | 20.18 | 313.17 | 20.12 |
February | 373.33 | 21.11 | 163.83 | 20.80 | 163.83 | 20.64 |
March | 347.50 | 22.38 | 60.50 | 22.44 | 22.00 | 22.33 |
April | 185.00 | 22.90 | 129.00 | 23.53 | 11.50 | 23.55 |
May | 82.17 | 23.95 | 289.33 | 24.43 | 19.50 | 24.53 |
June | 45.33 | 25.59 | 378.17 | 24.62 | 35.00 | 24.75 |
July | 70.17 | 26.10 | 410.83 | 24.87 | 65.33 | 25.04 |
August | 59.00 | 26.10 | 429.50 | 24.72 | 59.00 | 24.87 |
September | 83.67 | 24.20 | 298.83 | 24.45 | 33.50 | 24.57 |
October | 256.67 | 22.41 | 122.33 | 23.00 | 19.67 | 23.01 |
November | 393.67 | 21.95 | 55.67 | 21.81 | 48.67 | 21.66 |
December | 421.17 | 20.77 | 217.67 | 20.53 | 217.67 | 20.40 |
Annual Sum or Average | 2744.67 | 21.95 | 2868.83 | 22.66 | 1008.83 | 22.47 |
Minimum of Months | 45.33 | 20.34 | 55.67 | 20.18 | 11.50 | 20.12 |
Maximum of Months | 427.00 | 26.10 | 429.50 | 24.87 | 313.17 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.67 | 21.11 | 261.50 | 20.78 | 257.50 | 20.59 |
February | 398.50 | 21.42 | 155.17 | 21.26 | 140.67 | 21.07 |
March | 337.17 | 22.32 | 105.33 | 22.62 | 26.17 | 22.50 |
April | 222.50 | 22.82 | 143.67 | 23.41 | 11.17 | 23.42 |
May | 99.83 | 23.21 | 305.83 | 24.06 | 4.83 | 24.07 |
June | 46.00 | 24.26 | 417.50 | 24.32 | 19.00 | 24.37 |
July | 47.50 | 25.35 | 481.17 | 24.54 | 41.83 | 24.62 |
August | 48.67 | 25.82 | 508.00 | 24.52 | 48.67 | 24.63 |
September | 87.17 | 24.07 | 354.17 | 24.36 | 31.50 | 24.47 |
October | 251.67 | 22.61 | 202.33 | 23.40 | 28.33 | 23.47 |
November | 360.33 | 22.15 | 92.83 | 22.37 | 39.67 | 22.23 |
December | 442.67 | 21.40 | 165.67 | 21.14 | 153.50 | 20.92 |
Annual Sum or Average | 2826.67 | 22.11 | 3193.17 | 22.91 | 802.83 | 22.73 |
Minimum of Months | 46.00 | 21.11 | 92.83 | 20.78 | 4.83 | 20.59 |
Maximum of Months | 484.67 | 25.82 | 508.00 | 24.54 | 257.50 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.49 | 350.67 | 20.30 | 350.67 | 20.22 |
February | 434.50 | 21.04 | 195.17 | 20.81 | 190.67 | 20.66 |
March | 383.00 | 22.12 | 107.17 | 22.32 | 39.17 | 22.18 |
April | 228.67 | 22.86 | 167.83 | 23.47 | 16.00 | 23.51 |
May | 96.50 | 23.57 | 345.17 | 24.19 | 14.00 | 24.25 |
June | 53.67 | 24.99 | 435.50 | 24.46 | 32.17 | 24.56 |
July | 59.67 | 25.70 | 483.50 | 24.63 | 54.67 | 24.75 |
August | 50.33 | 25.87 | 509.17 | 24.56 | 50.33 | 24.66 |
September | 94.00 | 24.10 | 353.00 | 24.36 | 36.33 | 24.47 |
October | 314.17 | 22.42 | 142.00 | 22.98 | 22.00 | 23.00 |
November | 437.00 | 21.79 | 86.83 | 21.69 | 71.67 | 21.54 |
December | 493.17 | 20.89 | 243.67 | 20.64 | 243.67 | 20.51 |
Annual Sum or Average | 3146.67 | 21.84 | 3419.67 | 22.59 | 1121.33 | 22.39 |
Minimum of Months | 50.33 | 20.49 | 86.83 | 20.30 | 14.00 | 20.22 |
Maximum of Months | 502.00 | 25.87 | 509.17 | 24.63 | 350.67 | 24.75 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.73573 | 28.15085 | -0.3593 | 8.47146 |
February | 454.00000 | 22.45253 | 29.04996 | -0.1628 | 6.74016 |
March | 514.00000 | 23.73202 | 32.00172 | 0.19598 | 6.26091 |
April | 485.00000 | 24.08260 | 36.57014 | 0.33196 | 7.62009 |
May | 508.00000 | 24.28823 | 42.93776 | -0.4301 | 9.26060 |
June | 496.00000 | 24.28442 | 44.89810 | -0.3823 | 8.41260 |
July | 497.00000 | 24.34584 | 47.00128 | -0.3424 | 7.79013 |
August | 514.00000 | 24.30170 | 47.24814 | -0.3464 | 7.81562 |
September | 485.00000 | 24.32617 | 45.56056 | -0.3723 | 8.28744 |
October | 502.00000 | 24.10443 | 39.14691 | 0.36278 | 8.04153 |
November | 489.00000 | 23.74328 | 30.29738 | 0.18349 | 6.14877 |
December | 497.00000 | 22.74955 | 30.31887 | -0.0793 | 5.83985 |
Annual Sum or Average | 5943.00000 | 23.68722 | 37.83701 | -0.1173 | 7.56485 |
Minimum of Months | 454.00000 | 21.73573 | 28.15085 | -0.4301 | 5.83985 |
Maximum of Months | 514.00000 | 24.34584 | 47.24814 | 0.36278 | 9.26060 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.92830 | 28.94815 | -0.5525 | 12.30008 |
February | 454.00000 | 21.55802 | 30.13763 | -0.3668 | 9.30728 |
March | 514.00000 | 22.94383 | 33.78888 | 0.02537 | 5.97451 |
April | 485.00000 | 23.63880 | 38.04607 | 0.23690 | 6.77468 |
May | 508.00000 | 24.01682 | 44.22220 | -0.5116 | 10.93614 |
June | 496.00000 | 24.16666 | 45.75705 | -0.4220 | 9.13529 |
July | 497.00000 | 24.24781 | 47.87517 | -0.3745 | 8.29012 |
August | 514.00000 | 24.23790 | 48.08090 | -0.3707 | 8.16577 |
September | 485.00000 | 24.10754 | 46.47446 | -0.4530 | 9.79555 |
October | 502.00000 | 23.43828 | 41.26523 | 0.20697 | 6.70143 |
November | 489.00000 | 22.60518 | 32.46301 | -0.0742 | 5.96383 |
December | 497.00000 | 21.49863 | 32.22010 | -0.3644 | 8.64002 |
Annual Sum or Average | 5943.00000 | 23.12719 | 39.17975 | -0.2516 | 8.49507 |
Minimum of Months | 454.00000 | 20.92830 | 28.94815 | -0.5525 | 5.96383 |
Maximum of Months | 514.00000 | 24.24781 | 48.08090 | 0.23690 | 12.30008 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52723 | 27.89596 | -0.6812 | 16.76489 |
February | 454.00000 | 21.15285 | 30.37990 | -0.4832 | 12.08041 |
March | 514.00000 | 22.48722 | 34.00648 | -0.0881 | 6.78169 |
April | 485.00000 | 23.39335 | 37.81286 | 0.17672 | 6.71433 |
May | 508.00000 | 23.94773 | 43.49692 | -0.5319 | 11.63135 |
June | 496.00000 | 24.17328 | 45.20006 | -0.4099 | 9.03036 |
July | 497.00000 | 24.28010 | 47.37997 | -0.3518 | 8.04556 |
August | 514.00000 | 24.26482 | 47.68376 | -0.3502 | 7.87371 |
September | 485.00000 | 23.98214 | 46.05836 | -0.4998 | 11.02557 |
October | 502.00000 | 22.92073 | 42.00298 | 0.07728 | 6.53358 |
November | 489.00000 | 21.84531 | 33.38547 | -0.2653 | 7.73745 |
December | 497.00000 | 20.93587 | 32.46546 | -0.5278 | 12.30187 |
Annual Sum or Average | 5943.00000 | 22.83897 | 39.04971 | -0.3273 | 9.69227 |
Minimum of Months | 454.00000 | 20.52723 | 27.89596 | -0.6812 | 6.53358 |
Maximum of Months | 514.00000 | 24.28010 | 47.68376 | 0.17672 | 16.76489 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02967 | 29.40886 | -0.8507 | 23.20588 |
February | 454.00000 | 20.66154 | 31.52752 | -0.6396 | 16.69300 |
March | 514.00000 | 21.90056 | 36.31537 | -0.2291 | 8.91309 |
April | 485.00000 | 23.03137 | 40.87188 | 0.10767 | 7.64040 |
May | 508.00000 | 23.87539 | 46.42179 | -0.5193 | 12.44073 |
June | 496.00000 | 24.23600 | 47.59299 | -0.3271 | 8.44698 |
July | 497.00000 | 24.41367 | 51.00198 | -0.2340 | 7.37733 |
August | 514.00000 | 24.34566 | 51.50993 | -0.2525 | 7.20782 |
September | 485.00000 | 23.90740 | 50.03434 | -0.4920 | 12.05454 |
October | 502.00000 | 22.34792 | 46.55617 | -0.0460 | 7.57382 |
November | 489.00000 | 21.19083 | 36.71365 | -0.4312 | 11.05577 |
December | 497.00000 | 20.30328 | 33.52671 | -0.7157 | 18.54813 |
Annual Sum or Average | 5943.00000 | 22.53511 | 41.86973 | -0.3842 | 11.72288 |
Minimum of Months | 454.00000 | 20.02967 | 29.40886 | -0.8507 | 7.20782 |
Maximum of Months | 514.00000 | 24.41367 | 51.50993 | 0.10767 | 23.20588 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19934 | 30.11943 | -0.7838 | 20.74602 |
February | 454.00000 | 21.06170 | 31.79150 | -0.5210 | 14.59297 |
March | 514.00000 | 22.53324 | 35.73740 | -0.0644 | 7.92145 |
April | 485.00000 | 23.52089 | 39.66871 | 0.25237 | 8.55889 |
May | 508.00000 | 24.12847 | 45.35153 | -0.3795 | 10.45064 |
June | 496.00000 | 24.35494 | 46.90036 | -0.2243 | 7.63396 |
July | 497.00000 | 24.52042 | 50.18127 | -0.1338 | 7.37066 |
August | 514.00000 | 24.43242 | 50.80998 | -0.1622 | 6.97351 |
September | 485.00000 | 24.07545 | 49.24737 | -0.3844 | 10.67347 |
October | 502.00000 | 22.86638 | 45.37010 | 0.09363 | 8.16071 |
November | 489.00000 | 21.64495 | 36.76861 | -0.3073 | 9.48811 |
December | 497.00000 | 20.49741 | 34.13398 | -0.6434 | 16.56943 |
Annual Sum or Average | 5943.00000 | 22.83378 | 41.41417 | -0.2699 | 10.72747 |
Minimum of Months | 454.00000 | 20.19934 | 30.11943 | -0.7838 | 6.97351 |
Maximum of Months | 514.00000 | 24.52042 | 50.80998 | 0.25237 | 20.74602 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.93348 | 28.26668 | -0.5860 | 17.20826 |
February | 454.00000 | 21.56184 | 30.07430 | -0.3870 | 13.10043 |
March | 514.00000 | 22.70703 | 34.23574 | -0.0156 | 8.66885 |
April | 485.00000 | 23.35693 | 39.59834 | 0.20541 | 8.54699 |
May | 508.00000 | 23.90858 | 46.08281 | -0.4906 | 12.25025 |
June | 496.00000 | 24.21482 | 47.62464 | -0.3290 | 8.77632 |
July | 497.00000 | 24.42104 | 50.91213 | -0.2228 | 7.49563 |
August | 514.00000 | 24.38395 | 51.05650 | -0.2074 | 7.09288 |
September | 485.00000 | 24.05941 | 48.90548 | -0.3918 | 10.93975 |
October | 502.00000 | 23.09673 | 43.64280 | 0.16813 | 9.28707 |
November | 489.00000 | 22.31122 | 33.95421 | -0.1345 | 9.57096 |
December | 497.00000 | 21.30641 | 31.79690 | -0.4324 | 13.74788 |
Annual Sum or Average | 5943.00000 | 23.03328 | 40.59545 | -0.2346 | 10.53597 |
Minimum of Months | 454.00000 | 20.93348 | 28.26668 | -0.5860 | 7.09288 |
Maximum of Months | 514.00000 | 24.42104 | 51.05650 | 0.20541 | 17.20826 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26311 | 29.98561 | -0.7752 | 21.05108 |
February | 454.00000 | 20.98389 | 31.76935 | -0.5459 | 15.24145 |
March | 514.00000 | 22.36260 | 35.74756 | -0.1010 | 8.99373 |
April | 485.00000 | 23.32448 | 40.29068 | 0.20809 | 8.79137 |
May | 508.00000 | 23.97415 | 46.13473 | -0.4383 | 11.61489 |
June | 496.00000 | 24.27682 | 47.55096 | -0.2647 | 8.35225 |
July | 497.00000 | 24.45965 | 50.98139 | -0.1722 | 7.44730 |
August | 514.00000 | 24.41163 | 51.27302 | -0.1775 | 7.08050 |
September | 485.00000 | 24.03194 | 49.70509 | -0.4071 | 11.18483 |
October | 502.00000 | 22.70048 | 45.94390 | 0.05624 | 8.40406 |
November | 489.00000 | 21.60682 | 36.58401 | -0.3208 | 10.40599 |
December | 497.00000 | 20.58251 | 34.00930 | -0.6338 | 16.80057 |
Annual Sum or Average | 5943.00000 | 22.76226 | 41.74122 | -0.2961 | 11.24676 |
Minimum of Months | 454.00000 | 20.26311 | 29.98561 | -0.7752 | 7.08050 |
Maximum of Months | 514.00000 | 24.45965 | 51.27302 | 0.20809 | 21.05108 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29097 | 29.39572 | -0.7761 | 19.41472 |
February | 454.00000 | 20.70232 | 31.95358 | -0.6234 | 15.12717 |
March | 514.00000 | 21.62432 | 37.46371 | -0.2984 | 8.35435 |
April | 485.00000 | 22.50558 | 42.88511 | -0.0341 | 6.65072 |
May | 508.00000 | 23.63985 | 48.11206 | -0.6471 | 15.17662 |
June | 496.00000 | 24.15617 | 47.75067 | -0.4016 | 8.97905 |
July | 497.00000 | 24.32479 | 50.38028 | -0.3065 | 7.52706 |
August | 514.00000 | 24.29949 | 50.39608 | -0.3029 | 7.35547 |
September | 485.00000 | 24.12205 | 49.25659 | -0.4250 | 9.64373 |
October | 502.00000 | 22.98737 | 44.83618 | 0.11570 | 6.67437 |
November | 489.00000 | 21.90610 | 35.51546 | -0.2308 | 7.53246 |
December | 497.00000 | 20.77364 | 33.04303 | -0.5681 | 13.03379 |
Annual Sum or Average | 5943.00000 | 22.62499 | 41.82630 | -0.3739 | 10.43371 |
Minimum of Months | 454.00000 | 20.29097 | 29.39572 | -0.7761 | 6.65072 |
Maximum of Months | 514.00000 | 24.32479 | 50.39608 | 0.11570 | 19.41472 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49199 | 30.15197 | -0.7018 | 16.94018 |
February | 454.00000 | 21.17992 | 32.25664 | -0.4868 | 12.61286 |
March | 514.00000 | 22.44489 | 36.79860 | -0.0900 | 6.96003 |
April | 485.00000 | 23.30131 | 41.26089 | 0.17512 | 7.21637 |
May | 508.00000 | 24.05775 | 46.51705 | -0.4569 | 11.30530 |
June | 496.00000 | 24.33805 | 46.81260 | -0.2778 | 7.57477 |
July | 497.00000 | 24.50623 | 49.44280 | -0.1811 | 7.04914 |
August | 514.00000 | 24.43795 | 49.58103 | -0.1931 | 6.79096 |
September | 485.00000 | 24.29539 | 48.44179 | -0.3114 | 8.35876 |
October | 502.00000 | 23.51441 | 43.47678 | 0.25967 | 7.98369 |
November | 489.00000 | 22.56617 | 35.17606 | -0.0648 | 6.69010 |
December | 497.00000 | 21.08156 | 33.51397 | -0.4703 | 11.07469 |
Annual Sum or Average | 5943.00000 | 23.03114 | 41.18987 | -0.2322 | 9.19387 |
Minimum of Months | 454.00000 | 20.49199 | 30.15197 | -0.7018 | 6.69010 |
Maximum of Months | 514.00000 | 24.50623 | 49.58103 | 0.25967 | 16.94018 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.64884 | 26.99331 | -0.6079 | 15.91429 |
February | 454.00000 | 21.28433 | 29.33473 | -0.4222 | 12.50791 |
March | 514.00000 | 22.38684 | 34.94935 | -0.0773 | 7.59974 |
April | 485.00000 | 22.87016 | 41.08849 | 0.07671 | 7.27964 |
May | 508.00000 | 23.57512 | 49.54567 | -0.6306 | 15.42188 |
June | 496.00000 | 24.09639 | 51.35099 | -0.3904 | 9.27028 |
July | 497.00000 | 24.35005 | 54.88989 | -0.2581 | 7.19100 |
August | 514.00000 | 24.41792 | 55.17002 | -0.1945 | 6.54508 |
September | 485.00000 | 24.22706 | 50.90029 | -0.3123 | 8.82011 |
October | 502.00000 | 23.55237 | 42.85771 | 0.30821 | 9.37815 |
November | 489.00000 | 22.85372 | 32.27595 | 0.04358 | 7.84381 |
December | 497.00000 | 21.54633 | 30.36111 | -0.3166 | 10.00528 |
Annual Sum or Average | 5943.00000 | 22.99610 | 41.74846 | -0.2313 | 9.80460 |
Minimum of Months | 454.00000 | 20.64884 | 26.99331 | -0.6306 | 6.54508 |
Maximum of Months | 514.00000 | 24.41792 | 55.17002 | 0.30821 | 15.91429 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.50627 | 30.13009 | -0.7009 | 17.20922 |
February | 454.00000 | 21.04918 | 32.34021 | -0.5207 | 13.25597 |
March | 514.00000 | 22.36315 | 36.62923 | -0.1077 | 7.42918 |
April | 485.00000 | 23.20255 | 41.52014 | 0.15014 | 7.22460 |
May | 508.00000 | 23.96295 | 47.04033 | -0.4990 | 11.83512 |
June | 496.00000 | 24.28922 | 47.30180 | -0.3084 | 7.97581 |
July | 497.00000 | 24.44409 | 50.05143 | -0.2189 | 7.11481 |
August | 514.00000 | 24.42894 | 49.84800 | -0.2037 | 6.81973 |
September | 485.00000 | 24.29621 | 48.65380 | -0.3204 | 8.45870 |
October | 502.00000 | 23.47454 | 43.80208 | 0.24785 | 7.86719 |
November | 489.00000 | 22.48140 | 35.10901 | -0.0852 | 7.05174 |
December | 497.00000 | 21.08999 | 33.52453 | -0.4746 | 11.37467 |
Annual Sum or Average | 5943.00000 | 22.97951 | 41.40061 | -0.2523 | 9.44687 |
Minimum of Months | 454.00000 | 20.50627 | 30.13009 | -0.7009 | 6.81973 |
Maximum of Months | 514.00000 | 24.44409 | 50.05143 | 0.24785 | 17.20922 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24091 | 29.34452 | -0.7703 | 19.79057 |
February | 454.00000 | 20.85029 | 31.41569 | -0.5678 | 14.44567 |
March | 514.00000 | 22.18676 | 36.16496 | -0.1475 | 7.52832 |
April | 485.00000 | 23.24738 | 40.86293 | 0.16193 | 7.24372 |
May | 508.00000 | 23.98593 | 46.59590 | -0.4898 | 11.07609 |
June | 496.00000 | 24.25697 | 47.65548 | -0.3341 | 8.07018 |
July | 497.00000 | 24.40628 | 50.89163 | -0.2532 | 7.19837 |
August | 514.00000 | 24.33956 | 51.26710 | -0.2711 | 7.18225 |
September | 485.00000 | 24.05025 | 49.90326 | -0.4444 | 10.33293 |
October | 502.00000 | 22.73176 | 45.70943 | 0.05631 | 6.91131 |
November | 489.00000 | 21.63237 | 36.01597 | -0.3017 | 8.58574 |
December | 497.00000 | 20.62194 | 33.04940 | -0.6079 | 14.69329 |
Annual Sum or Average | 5943.00000 | 22.72686 | 41.65233 | -0.3295 | 10.22322 |
Minimum of Months | 454.00000 | 20.24091 | 29.34452 | -0.7703 | 6.91131 |
Maximum of Months | 514.00000 | 24.40628 | 51.26710 | 0.16193 | 19.79057 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.33561 | 29.75718 | -0.7280 | 18.45845 |
February | 385.00000 | 21.20521 | 31.53694 | -0.4670 | 13.03649 |
March | 433.00000 | 22.72396 | 35.18806 | -0.0132 | 7.18320 |
April | 410.00000 | 23.65343 | 39.58988 | 0.27648 | 8.34712 |
May | 430.00000 | 24.25186 | 45.27615 | -0.3660 | 9.94257 |
June | 418.00000 | 24.44857 | 46.83038 | -0.2319 | 7.57571 |
July | 422.00000 | 24.62947 | 50.05824 | -0.1380 | 7.32078 |
August | 433.00000 | 24.52153 | 50.65551 | -0.1723 | 7.09807 |
September | 410.00000 | 24.24651 | 49.15105 | -0.3462 | 9.50528 |
October | 427.00000 | 23.14351 | 44.60551 | 0.16467 | 7.87189 |
November | 417.00000 | 22.07277 | 35.78502 | -0.1894 | 7.85312 |
December | 422.00000 | 20.78030 | 33.57638 | -0.5513 | 13.55073 |
Annual Sum or Average | 5034.00000 | 23.01171 | 41.06250 | -0.2291 | 9.79139 |
Minimum of Months | 385.00000 | 20.33561 | 29.75718 | -0.7280 | 7.09807 |
Maximum of Months | 433.00000 | 24.62947 | 50.65551 | 0.27648 | 18.45845 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.23669 | 28.01904 | -0.4903 | 14.33335 |
February | 454.00000 | 21.81313 | 29.83698 | -0.3057 | 11.13435 |
March | 514.00000 | 23.00289 | 34.00910 | 0.06540 | 7.75520 |
April | 485.00000 | 23.57253 | 39.52042 | 0.25795 | 8.22738 |
May | 508.00000 | 24.02309 | 46.21669 | -0.4609 | 10.82386 |
June | 496.00000 | 24.24667 | 47.66091 | -0.3335 | 8.27192 |
July | 497.00000 | 24.42914 | 50.76772 | -0.2383 | 7.25398 |
August | 514.00000 | 24.39188 | 50.77681 | -0.2234 | 7.01968 |
September | 485.00000 | 24.19673 | 48.79612 | -0.3478 | 9.35222 |
October | 502.00000 | 23.42819 | 42.86079 | 0.25754 | 9.01784 |
November | 489.00000 | 22.76424 | 33.13528 | -0.0070 | 8.22581 |
December | 497.00000 | 21.71138 | 31.11333 | -0.3113 | 10.79505 |
Annual Sum or Average | 5943.00000 | 23.24543 | 40.30911 | -0.1778 | 9.33735 |
Minimum of Months | 454.00000 | 21.23669 | 28.01904 | -0.4903 | 7.01968 |
Maximum of Months | 514.00000 | 24.42914 | 50.77681 | 0.25795 | 14.33335 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48627 | 29.98696 | -0.6928 | 17.82911 |
February | 454.00000 | 21.18648 | 31.68345 | -0.4722 | 13.09989 |
March | 514.00000 | 22.67060 | 35.56511 | -0.0166 | 7.78404 |
April | 485.00000 | 23.56460 | 40.19452 | 0.26556 | 8.46710 |
May | 508.00000 | 24.10151 | 46.22962 | -0.4056 | 10.11826 |
June | 496.00000 | 24.31878 | 47.56198 | -0.2668 | 7.79867 |
July | 497.00000 | 24.47244 | 50.81844 | -0.1867 | 7.15952 |
August | 514.00000 | 24.41956 | 50.99421 | -0.1935 | 6.96315 |
September | 485.00000 | 24.17991 | 49.56526 | -0.3596 | 9.50978 |
October | 502.00000 | 23.08163 | 45.08567 | 0.15663 | 7.89083 |
November | 489.00000 | 22.05820 | 35.85356 | -0.1912 | 8.24860 |
December | 497.00000 | 20.91476 | 33.55546 | -0.5244 | 13.21756 |
Annual Sum or Average | 5943.00000 | 22.96816 | 41.50048 | -0.2393 | 9.81437 |
Minimum of Months | 454.00000 | 20.48627 | 29.98696 | -0.6928 | 6.96315 |
Maximum of Months | 514.00000 | 24.47244 | 50.99421 | 0.26556 | 17.82911 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.160624E+10 | 0.411461E+09 | 52.83 | 0.975016E+09 | 0.631225E+09 | 0.00 | 0.58 | 19-JAN-16:00 | 0.00 | 01-JAN-00:05 | 16734.27 | 19-JAN-16:00 | 11213.27 | 31-JAN-15:00 | 8266.42 | 19-JAN-16:00 | 4096.03 | 19-JAN-16:00 | 0.00 |
February | 0.382490E+10 | 0.981668E+09 | 131.61 | 0.304924E+10 | 0.775663E+09 | 0.00 | 0.76 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 | 23173.08 | 28-FEB-15:00 | 23173.08 | 28-FEB-15:00 | 7203.51 | 18-FEB-16:00 | 5548.83 | 28-FEB-15:00 | 0.00 |
March | 0.117721E+11 | 0.289408E+10 | 267.92 | 0.877968E+10 | 0.299241E+10 | 0.00 | 1.00 | 30-MAR-12:40 | 0.00 | 01-MAR-00:10 | 39137.90 | 30-MAR-15:30 | 39137.90 | 30-MAR-15:30 | 10544.77 | 31-MAR-11:40 | 9389.17 | 30-MAR-15:30 | 0.00 |
April | 0.206191E+11 | 0.498069E+10 | 328.22 | 0.163606E+11 | 0.425849E+10 | 0.00 | 1.00 | 12-APR-14:00 | 0.00 | 01-APR-00:10 | 45038.20 | 17-APR-15:00 | 45038.20 | 17-APR-15:00 | 13030.17 | 04-APR-11:00 | 11143.33 | 17-APR-15:00 | 0.00 |
May | 0.405588E+11 | 0.958307E+10 | 408.36 | 0.296162E+11 | 0.109426E+11 | 0.00 | 1.00 | 02-MAY-15:10 | 0.00 | 01-MAY-00:10 | 60805.94 | 30-MAY-15:10 | 47204.37 | 30-MAY-15:00 | 18067.37 | 31-MAY-09:00 | 15324.70 | 30-MAY-15:00 | 0.00 |
June | 0.653224E+11 | 0.159290E+11 | 433.81 | 0.471917E+11 | 0.181307E+11 | 0.00 | 1.00 | 01-JUN-07:15 | 0.00 | 01-JUN-00:10 | 76042.37 | 28-JUN-12:05 | 54561.51 | 26-JUN-06:03 | 26733.42 | 27-JUN-12:00 | 19341.39 | 28-JUN-12:05 | 0.00 |
July | 0.764168E+11 | 0.187976E+11 | 439.05 | 0.520431E+11 | 0.243738E+11 | 0.00 | 1.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 | 84006.14 | 07-JUL-12:05 | 60624.06 | 17-JUL-06:03 | 32082.68 | 26-JUL-12:00 | 22440.80 | 07-JUL-16:00 | 0.00 |
August | 0.877875E+11 | 0.213381E+11 | 464.04 | 0.583897E+11 | 0.293978E+11 | 0.00 | 1.00 | 01-AUG-06:05 | 0.00 | 01-AUG-00:10 | 93326.13 | 21-AUG-06:03 | 65801.79 | 07-AUG-06:03 | 31740.56 | 24-AUG-06:05 | 21848.48 | 01-AUG-15:20 | 0.00 |
September | 0.538819E+11 | 0.126151E+11 | 410.51 | 0.383492E+11 | 0.155327E+11 | 0.00 | 1.00 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 79589.97 | 06-SEP-12:03 | 57019.77 | 07-SEP-16:00 | 26128.05 | 06-SEP-12:03 | 20414.20 | 07-SEP-16:00 | 0.00 |
October | 0.229889E+11 | 0.539637E+10 | 302.36 | 0.164155E+11 | 0.657335E+10 | 0.00 | 1.00 | 02-OCT-08:40 | 0.00 | 01-OCT-00:10 | 59619.88 | 10-OCT-15:50 | 48331.25 | 10-OCT-16:00 | 23259.01 | 18-OCT-15:20 | 14992.03 | 10-OCT-16:00 | 0.00 |
November | 0.846494E+10 | 0.209758E+10 | 218.19 | 0.619500E+10 | 0.226993E+10 | 0.00 | 0.87 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 | 27530.72 | 02-NOV-13:00 | 21906.46 | 08-NOV-15:30 | 10145.88 | 27-NOV-18:00 | 6258.29 | 02-NOV-13:00 | 0.00 |
December | 0.295990E+10 | 0.742856E+09 | 111.99 | 0.187175E+10 | 0.108815E+10 | 0.00 | 0.81 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 24950.54 | 12-DEC-14:00 | 17123.91 | 12-DEC-14:00 | 10187.39 | 13-DEC-16:10 | 5755.33 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.396204E+12 | 0.957675E+11 | 3568.90 | 0.279237E+12 | 0.116967E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.160624E+10 | 0.411461E+09 | 52.83 | 0.975016E+09 | 0.631225E+09 | 0.00 | 0.58 | 0.00 | 16734.27 | 11213.27 | 7203.51 | 4096.03 | 0.00 | ||||||
Maximum of Months | 0.877875E+11 | 0.213381E+11 | 464.04 | 0.583897E+11 | 0.293978E+11 | 0.00 | 1.00 | 0.00 | 93326.13 | 65801.79 | 32082.68 | 22440.80 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.157909E+10 | 0.403587E+09 | 52.83 | 0.964801E+09 | 0.614294E+09 | 0.00 | 0.62 | 19-JAN-16:00 | 0.00 | 01-JAN-00:05 | 17517.50 | 19-JAN-16:00 | 10976.90 | 31-JAN-15:10 | 8168.28 | 19-JAN-15:50 | 4239.38 | 19-JAN-16:00 | 0.00 |
February | 0.392518E+10 | 0.100280E+10 | 133.13 | 0.319036E+10 | 0.734815E+09 | 0.00 | 0.82 | 28-FEB-15:05 | 0.00 | 01-FEB-00:10 | 24442.04 | 28-FEB-15:05 | 24442.04 | 28-FEB-15:05 | 7108.18 | 18-FEB-16:00 | 5719.92 | 28-FEB-15:05 | 0.00 |
March | 0.118183E+11 | 0.289718E+10 | 271.15 | 0.901257E+10 | 0.280577E+10 | 0.00 | 1.00 | 29-MAR-15:10 | 0.00 | 01-MAR-00:10 | 43704.74 | 30-MAR-15:20 | 43704.74 | 30-MAR-15:20 | 10406.88 | 31-MAR-08:20 | 10483.76 | 30-MAR-15:20 | 0.00 |
April | 0.214021E+11 | 0.515084E+10 | 340.00 | 0.173949E+11 | 0.400723E+10 | 0.00 | 1.00 | 04-APR-13:40 | 0.00 | 01-APR-00:10 | 50173.12 | 17-APR-15:50 | 50173.12 | 17-APR-15:50 | 12919.48 | 21-APR-11:00 | 12409.46 | 17-APR-15:50 | 0.00 |
May | 0.412137E+11 | 0.972707E+10 | 424.39 | 0.307299E+11 | 0.104837E+11 | 0.00 | 1.00 | 01-MAY-14:05 | 0.00 | 01-MAY-00:10 | 63123.34 | 30-MAY-14:05 | 50357.92 | 30-MAY-14:05 | 17473.40 | 31-MAY-13:00 | 16078.01 | 30-MAY-14:05 | 0.00 |
June | 0.637113E+11 | 0.155140E+11 | 441.17 | 0.460630E+11 | 0.176483E+11 | 0.00 | 1.00 | 01-JUN-07:50 | 0.00 | 01-JUN-00:10 | 86131.86 | 26-JUN-06:03 | 66391.82 | 26-JUN-05:12 | 25058.16 | 23-JUN-10:05 | 18837.11 | 26-JUN-06:03 | 0.00 |
July | 0.736730E+11 | 0.180750E+11 | 444.87 | 0.498356E+11 | 0.238374E+11 | 0.00 | 1.00 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 77939.66 | 07-JUL-12:02 | 66844.59 | 17-JUL-05:12 | 27939.17 | 26-JUL-10:40 | 21739.49 | 07-JUL-16:00 | 0.00 |
August | 0.823613E+11 | 0.199556E+11 | 465.24 | 0.539250E+11 | 0.284363E+11 | 0.00 | 1.00 | 01-AUG-06:05 | 0.00 | 01-AUG-00:10 | 95440.43 | 21-AUG-06:03 | 63006.97 | 07-AUG-06:03 | 35419.47 | 21-AUG-06:03 | 21243.00 | 01-AUG-15:20 | 0.00 |
September | 0.485905E+11 | 0.114129E+11 | 412.69 | 0.338448E+11 | 0.147457E+11 | 0.00 | 1.00 | 01-SEP-09:00 | 0.00 | 01-SEP-00:10 | 75806.25 | 06-SEP-14:05 | 53547.75 | 07-SEP-15:30 | 23313.78 | 09-SEP-11:00 | 19200.16 | 06-SEP-14:05 | 0.00 |
October | 0.205585E+11 | 0.485661E+10 | 302.75 | 0.144195E+11 | 0.613894E+10 | 0.00 | 1.00 | 02-OCT-09:50 | 0.00 | 01-OCT-00:10 | 58457.18 | 11-OCT-14:05 | 44246.98 | 10-OCT-15:40 | 23125.70 | 18-OCT-15:00 | 14235.29 | 10-OCT-14:05 | 0.00 |
November | 0.791679E+10 | 0.197089E+10 | 218.50 | 0.572441E+10 | 0.219238E+10 | 0.00 | 0.84 | 02-NOV-14:05 | 0.00 | 01-NOV-00:10 | 25433.81 | 02-NOV-14:05 | 19745.19 | 08-NOV-15:05 | 9817.22 | 27-NOV-18:00 | 5799.18 | 02-NOV-14:05 | 0.00 |
December | 0.292659E+10 | 0.733641E+09 | 112.53 | 0.189095E+10 | 0.103565E+10 | 0.00 | 0.82 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 24394.91 | 12-DEC-14:00 | 17037.49 | 12-DEC-14:00 | 9632.65 | 13-DEC-11:05 | 5603.69 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.379676E+12 | 0.917001E+11 | 3619.26 | 0.266996E+12 | 0.112681E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.157909E+10 | 0.403587E+09 | 52.83 | 0.964801E+09 | 0.614294E+09 | 0.00 | 0.62 | 0.00 | 17517.50 | 10976.90 | 7108.18 | 4239.38 | 0.00 | ||||||
Maximum of Months | 0.823613E+11 | 0.199556E+11 | 465.24 | 0.539250E+11 | 0.284363E+11 | 0.00 | 1.00 | 0.00 | 95440.43 | 66844.59 | 35419.47 | 21739.49 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.163806E+10 | 0.422371E+09 | 53.33 | 0.990016E+09 | 0.648043E+09 | 0.00 | 0.54 | 19-JAN-16:00 | 0.00 | 01-JAN-00:05 | 16877.41 | 19-JAN-16:00 | 11263.27 | 31-JAN-15:00 | 8352.21 | 19-JAN-16:00 | 4171.90 | 19-JAN-16:00 | 0.00 |
February | 0.410192E+10 | 0.105514E+10 | 133.06 | 0.328586E+10 | 0.816066E+09 | 0.00 | 0.72 | 28-FEB-15:30 | 0.00 | 01-FEB-00:10 | 23717.82 | 28-FEB-15:30 | 23717.82 | 28-FEB-15:30 | 7494.86 | 18-FEB-07:03 | 5695.64 | 28-FEB-15:00 | 0.00 |
March | 0.125717E+11 | 0.310412E+10 | 273.03 | 0.948948E+10 | 0.308223E+10 | 0.00 | 1.00 | 29-MAR-15:00 | 0.00 | 01-MAR-00:10 | 50234.16 | 30-MAR-15:20 | 50234.16 | 30-MAR-15:20 | 10386.03 | 31-MAR-11:10 | 12049.57 | 30-MAR-15:20 | 0.00 |
April | 0.234290E+11 | 0.566687E+10 | 342.14 | 0.189883E+11 | 0.444067E+10 | 0.00 | 1.00 | 04-APR-13:50 | 0.00 | 01-APR-00:10 | 56016.20 | 17-APR-14:50 | 56016.20 | 17-APR-14:50 | 13313.53 | 23-APR-13:03 | 13855.16 | 17-APR-14:50 | 0.00 |
May | 0.451072E+11 | 0.107212E+11 | 428.01 | 0.340931E+11 | 0.110142E+11 | 0.00 | 1.00 | 01-MAY-15:00 | 0.00 | 01-MAY-00:10 | 71943.47 | 30-MAY-15:00 | 59091.65 | 16-MAY-16:00 | 17581.84 | 31-MAY-13:00 | 18285.92 | 30-MAY-15:00 | 0.00 |
June | 0.692239E+11 | 0.169633E+11 | 443.87 | 0.510644E+11 | 0.181595E+11 | 0.00 | 1.00 | 01-JUN-09:05 | 0.00 | 01-JUN-00:10 | 87667.92 | 26-JUN-06:03 | 67064.52 | 26-JUN-05:12 | 24862.01 | 23-JUN-10:40 | 21021.29 | 12-JUN-15:00 | 0.00 |
July | 0.795916E+11 | 0.196757E+11 | 449.64 | 0.553404E+11 | 0.242512E+11 | 0.00 | 1.00 | 01-JUL-08:00 | 0.00 | 01-JUL-00:10 | 86418.64 | 07-JUL-16:00 | 70247.20 | 09-JUL-15:52 | 27998.30 | 26-JUL-10:40 | 24784.10 | 07-JUL-16:00 | 0.00 |
August | 0.880313E+11 | 0.214752E+11 | 468.79 | 0.591468E+11 | 0.288845E+11 | 0.00 | 1.00 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 97220.33 | 19-AUG-05:03 | 69735.92 | 06-AUG-14:43 | 37927.57 | 19-AUG-05:03 | 24252.25 | 01-AUG-15:00 | 0.00 |
September | 0.506847E+11 | 0.120128E+11 | 414.72 | 0.353713E+11 | 0.153133E+11 | 0.00 | 1.00 | 01-SEP-10:20 | 0.00 | 01-SEP-00:10 | 82333.20 | 06-SEP-14:00 | 61454.42 | 07-SEP-15:30 | 23959.32 | 16-SEP-13:40 | 21130.50 | 07-SEP-16:00 | 0.00 |
October | 0.210120E+11 | 0.501426E+10 | 300.17 | 0.145163E+11 | 0.649570E+10 | 0.00 | 1.00 | 02-OCT-10:40 | 0.00 | 01-OCT-00:10 | 62024.86 | 11-OCT-14:00 | 49578.58 | 10-OCT-15:30 | 23248.49 | 18-OCT-15:00 | 15244.12 | 10-OCT-14:00 | 0.00 |
November | 0.811863E+10 | 0.204140E+10 | 217.28 | 0.575148E+10 | 0.236715E+10 | 0.00 | 0.82 | 05-NOV-13:53 | 0.00 | 01-NOV-00:10 | 27761.25 | 05-NOV-13:53 | 20102.91 | 05-NOV-13:53 | 10208.32 | 27-NOV-18:00 | 6401.34 | 05-NOV-13:53 | 0.00 |
December | 0.300592E+10 | 0.759927E+09 | 111.17 | 0.191253E+10 | 0.109339E+10 | 0.00 | 0.78 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 25982.97 | 12-DEC-14:00 | 17764.05 | 12-DEC-14:00 | 9644.81 | 13-DEC-11:10 | 6040.09 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.406516E+12 | 0.989123E+11 | 3635.20 | 0.289950E+12 | 0.116566E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.163806E+10 | 0.422371E+09 | 53.33 | 0.990016E+09 | 0.648043E+09 | 0.00 | 0.54 | 0.00 | 16877.41 | 11263.27 | 7494.86 | 4171.90 | 0.00 | ||||||
Maximum of Months | 0.880313E+11 | 0.214752E+11 | 468.79 | 0.591468E+11 | 0.288845E+11 | 0.00 | 1.00 | 0.00 | 97220.33 | 70247.20 | 37927.57 | 24784.10 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 276.89 | 0.00 | 276.89 | 53.15 | 1647.54 | 0.00 | 0.00 | 0.00 |
February | 306.91 | 0.00 | 306.91 | 152.26 | 1347.89 | 0.00 | 0.00 | 0.00 |
March | 430.88 | 0.00 | 430.88 | 333.21 | 849.25 | 0.00 | 0.00 | 0.00 |
April | 521.19 | 2.31 | 518.87 | 599.93 | 691.80 | 0.00 | 0.00 | 0.00 |
May | 623.33 | 19.89 | 603.44 | 888.74 | 455.09 | 0.00 | 0.00 | 0.00 |
June | 686.00 | 45.29 | 640.71 | 1251.79 | 290.10 | 0.00 | 0.00 | 0.00 |
July | 647.25 | 31.46 | 615.78 | 1245.60 | 210.89 | 0.00 | 0.00 | 0.00 |
August | 575.62 | 6.27 | 569.35 | 1136.50 | 174.71 | 0.00 | 0.00 | 0.00 |
September | 435.11 | 0.06 | 435.05 | 663.95 | 383.23 | 0.00 | 0.00 | 0.00 |
October | 330.83 | 0.00 | 330.83 | 318.59 | 782.08 | 0.00 | 0.00 | 0.00 |
November | 296.08 | 0.00 | 296.08 | 189.72 | 1046.58 | 0.00 | 0.00 | 0.00 |
December | 255.96 | 0.00 | 255.96 | 60.84 | 1315.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 449.61 | 8.81 | 440.80 | 576.88 | 763.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.96 | 0.00 | 255.96 | 53.15 | 174.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 686.00 | 45.29 | 640.71 | 1251.79 | 1647.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 405.39 | 182.85 | 222.54 | 308.75 | 983.91 | 0.00 | 0.00 | 0.00 |
February | 511.07 | 274.59 | 236.48 | 521.99 | 812.83 | 0.00 | 0.00 | 0.00 |
March | 642.99 | 292.71 | 350.28 | 757.59 | 529.94 | 0.00 | 0.00 | 0.00 |
April | 777.54 | 354.54 | 423.00 | 1090.16 | 441.99 | 0.00 | 0.00 | 0.00 |
May | 853.79 | 361.06 | 492.74 | 1316.94 | 303.53 | 0.00 | 0.00 | 0.00 |
June | 883.96 | 370.49 | 513.47 | 1545.06 | 195.33 | 0.00 | 0.00 | 0.00 |
July | 861.90 | 362.35 | 499.54 | 1553.03 | 142.64 | 0.00 | 0.00 | 0.00 |
August | 788.35 | 312.77 | 475.59 | 1446.22 | 117.58 | 0.00 | 0.00 | 0.00 |
September | 647.92 | 287.08 | 360.84 | 1039.81 | 250.75 | 0.00 | 0.00 | 0.00 |
October | 552.73 | 287.60 | 265.13 | 729.31 | 492.54 | 0.00 | 0.00 | 0.00 |
November | 441.91 | 200.10 | 241.82 | 471.79 | 635.78 | 0.00 | 0.00 | 0.00 |
December | 382.78 | 174.49 | 208.29 | 317.66 | 786.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.51 | 288.34 | 358.17 | 926.95 | 472.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.78 | 174.49 | 208.29 | 308.75 | 117.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.96 | 370.49 | 513.47 | 1553.03 | 983.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1480.84 | 1032.44 | 448.40 | 1743.97 | 1390.69 | 0.00 | 0.00 | 0.00 |
February | 1382.12 | 926.47 | 455.65 | 1761.29 | 1197.52 | 0.00 | 0.00 | 0.00 |
March | 1242.99 | 647.78 | 595.22 | 1711.27 | 836.90 | 0.00 | 0.00 | 0.00 |
April | 930.92 | 303.03 | 627.89 | 1412.76 | 717.18 | 0.00 | 0.00 | 0.00 |
May | 752.14 | 87.42 | 664.73 | 1197.43 | 483.15 | 0.00 | 0.00 | 0.00 |
June | 695.44 | 38.70 | 656.74 | 1307.59 | 308.63 | 0.00 | 0.00 | 0.00 |
July | 703.07 | 52.43 | 650.65 | 1385.52 | 219.46 | 0.00 | 0.00 | 0.00 |
August | 839.42 | 156.81 | 682.61 | 1686.54 | 182.93 | 0.00 | 0.00 | 0.00 |
September | 923.15 | 343.37 | 579.79 | 1592.11 | 395.23 | 0.00 | 0.00 | 0.00 |
October | 1338.31 | 866.96 | 471.35 | 2008.38 | 769.61 | 0.00 | 0.00 | 0.00 |
November | 1439.78 | 955.42 | 484.37 | 1965.84 | 977.75 | 0.00 | 0.00 | 0.00 |
December | 1459.70 | 1026.91 | 432.79 | 1830.48 | 1164.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.78 | 534.66 | 563.12 | 1633.25 | 717.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.44 | 38.70 | 432.79 | 1197.43 | 182.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1480.84 | 1032.44 | 682.61 | 2008.38 | 1390.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.39 | 193.15 | 223.24 | 351.43 | 1024.61 | 0.00 | 0.00 | 0.00 |
February | 478.02 | 223.50 | 254.51 | 512.46 | 862.15 | 0.00 | 0.00 | 0.00 |
March | 704.57 | 340.46 | 364.10 | 898.55 | 569.84 | 0.00 | 0.00 | 0.00 |
April | 792.63 | 362.70 | 429.92 | 1145.43 | 478.01 | 0.00 | 0.00 | 0.00 |
May | 796.61 | 301.81 | 494.81 | 1252.93 | 328.13 | 0.00 | 0.00 | 0.00 |
June | 837.74 | 322.28 | 515.47 | 1481.36 | 213.73 | 0.00 | 0.00 | 0.00 |
July | 790.18 | 292.97 | 497.21 | 1444.49 | 153.00 | 0.00 | 0.00 | 0.00 |
August | 774.27 | 289.55 | 484.72 | 1431.34 | 129.47 | 0.00 | 0.00 | 0.00 |
September | 630.82 | 262.76 | 368.05 | 1022.40 | 265.99 | 0.00 | 0.00 | 0.00 |
October | 561.98 | 291.73 | 270.25 | 782.41 | 530.70 | 0.00 | 0.00 | 0.00 |
November | 448.50 | 201.31 | 247.19 | 531.71 | 692.09 | 0.00 | 0.00 | 0.00 |
December | 370.01 | 161.84 | 208.17 | 340.24 | 844.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.27 | 270.54 | 363.73 | 935.12 | 505.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.01 | 161.84 | 208.17 | 340.24 | 129.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.74 | 362.70 | 515.47 | 1481.36 | 1024.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.29 | 0.00 | 92.29 | 17.55 | 568.49 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 53.61 | 457.58 | 0.00 | 0.00 | 0.00 |
March | 143.62 | 0.00 | 143.62 | 121.24 | 278.57 | 0.00 | 0.00 | 0.00 |
April | 173.72 | 0.77 | 172.95 | 217.97 | 216.30 | 0.00 | 0.00 | 0.00 |
May | 207.77 | 6.63 | 201.14 | 311.57 | 141.05 | 0.00 | 0.00 | 0.00 |
June | 228.66 | 15.10 | 213.56 | 427.79 | 91.80 | 0.00 | 0.00 | 0.00 |
July | 215.74 | 10.49 | 205.25 | 425.02 | 66.19 | 0.00 | 0.00 | 0.00 |
August | 191.86 | 2.09 | 189.77 | 385.27 | 56.21 | 0.00 | 0.00 | 0.00 |
September | 145.03 | 0.02 | 145.01 | 221.10 | 137.33 | 0.00 | 0.00 | 0.00 |
October | 110.27 | 0.00 | 110.27 | 101.06 | 289.83 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 55.69 | 388.13 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 18.55 | 478.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.86 | 2.94 | 146.93 | 197.17 | 263.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 17.55 | 56.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.66 | 15.10 | 213.56 | 427.79 | 568.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.30 | 0.00 | 92.30 | 17.55 | 568.53 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 53.61 | 457.61 | 0.00 | 0.00 | 0.00 |
March | 143.63 | 0.00 | 143.63 | 121.24 | 278.59 | 0.00 | 0.00 | 0.00 |
April | 173.73 | 0.77 | 172.96 | 217.98 | 216.31 | 0.00 | 0.00 | 0.00 |
May | 207.78 | 6.63 | 201.14 | 311.58 | 141.06 | 0.00 | 0.00 | 0.00 |
June | 228.67 | 15.10 | 213.57 | 427.81 | 91.81 | 0.00 | 0.00 | 0.00 |
July | 215.75 | 10.49 | 205.26 | 425.04 | 66.19 | 0.00 | 0.00 | 0.00 |
August | 191.87 | 2.09 | 189.78 | 385.29 | 56.21 | 0.00 | 0.00 | 0.00 |
September | 145.04 | 0.02 | 145.02 | 221.11 | 137.34 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 0.00 | 110.28 | 101.06 | 289.85 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 55.69 | 388.16 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 18.55 | 478.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.87 | 2.94 | 146.93 | 197.17 | 263.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 17.55 | 56.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.67 | 15.10 | 213.57 | 427.81 | 568.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.30 | 0.00 | 92.30 | 17.55 | 568.53 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 53.61 | 457.61 | 0.00 | 0.00 | 0.00 |
March | 143.63 | 0.00 | 143.63 | 121.24 | 278.59 | 0.00 | 0.00 | 0.00 |
April | 173.73 | 0.77 | 172.96 | 217.98 | 216.31 | 0.00 | 0.00 | 0.00 |
May | 207.78 | 6.63 | 201.14 | 311.58 | 141.06 | 0.00 | 0.00 | 0.00 |
June | 228.67 | 15.10 | 213.57 | 427.81 | 91.81 | 0.00 | 0.00 | 0.00 |
July | 215.75 | 10.49 | 205.26 | 425.04 | 66.19 | 0.00 | 0.00 | 0.00 |
August | 191.87 | 2.09 | 189.78 | 385.29 | 56.21 | 0.00 | 0.00 | 0.00 |
September | 145.04 | 0.02 | 145.02 | 221.11 | 137.34 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 0.00 | 110.28 | 101.06 | 289.85 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 55.69 | 388.16 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 18.55 | 478.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.87 | 2.94 | 146.93 | 197.17 | 263.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 17.55 | 56.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.67 | 15.10 | 213.57 | 427.81 | 568.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.97 | 175.89 | 214.07 | 295.30 | 988.73 | 0.00 | 0.00 | 0.00 |
February | 491.62 | 264.15 | 227.48 | 508.75 | 807.20 | 0.00 | 0.00 | 0.00 |
March | 618.52 | 281.57 | 336.95 | 747.24 | 515.89 | 0.00 | 0.00 | 0.00 |
April | 747.95 | 341.04 | 406.91 | 1077.95 | 413.02 | 0.00 | 0.00 | 0.00 |
May | 821.31 | 347.32 | 473.99 | 1293.99 | 282.18 | 0.00 | 0.00 | 0.00 |
June | 850.33 | 356.39 | 493.94 | 1506.29 | 185.15 | 0.00 | 0.00 | 0.00 |
July | 829.10 | 348.57 | 480.54 | 1512.04 | 135.90 | 0.00 | 0.00 | 0.00 |
August | 758.36 | 300.87 | 457.49 | 1403.93 | 115.63 | 0.00 | 0.00 | 0.00 |
September | 623.27 | 276.15 | 347.11 | 1001.46 | 264.80 | 0.00 | 0.00 | 0.00 |
October | 531.70 | 276.65 | 255.04 | 690.37 | 535.22 | 0.00 | 0.00 | 0.00 |
November | 425.10 | 192.48 | 232.62 | 430.29 | 694.40 | 0.00 | 0.00 | 0.00 |
December | 368.22 | 167.85 | 200.37 | 295.15 | 837.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 621.91 | 277.36 | 344.54 | 898.91 | 479.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 368.22 | 167.85 | 200.37 | 295.15 | 115.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 850.33 | 356.39 | 493.94 | 1512.04 | 988.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.42 | 6.95 | 8.46 | 11.68 | 39.09 | 0.00 | 0.00 | 0.00 |
February | 19.44 | 10.44 | 8.99 | 20.12 | 31.92 | 0.00 | 0.00 | 0.00 |
March | 24.46 | 11.13 | 13.32 | 29.55 | 20.40 | 0.00 | 0.00 | 0.00 |
April | 29.57 | 13.48 | 16.09 | 42.62 | 16.33 | 0.00 | 0.00 | 0.00 |
May | 32.47 | 13.73 | 18.74 | 51.16 | 11.16 | 0.00 | 0.00 | 0.00 |
June | 33.62 | 14.09 | 19.53 | 59.56 | 7.32 | 0.00 | 0.00 | 0.00 |
July | 32.78 | 13.78 | 19.00 | 59.78 | 5.37 | 0.00 | 0.00 | 0.00 |
August | 29.98 | 11.90 | 18.09 | 55.51 | 4.57 | 0.00 | 0.00 | 0.00 |
September | 24.64 | 10.92 | 13.72 | 39.60 | 10.47 | 0.00 | 0.00 | 0.00 |
October | 21.02 | 10.94 | 10.08 | 27.30 | 21.16 | 0.00 | 0.00 | 0.00 |
November | 16.81 | 7.61 | 9.20 | 17.01 | 27.46 | 0.00 | 0.00 | 0.00 |
December | 14.56 | 6.64 | 7.92 | 11.67 | 33.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.59 | 10.97 | 13.62 | 35.54 | 18.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.56 | 6.64 | 7.92 | 11.67 | 4.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.62 | 14.09 | 19.53 | 59.78 | 39.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.60 | 344.14 | 149.47 | 589.05 | 488.81 | 0.00 | 0.00 | 0.00 |
February | 460.70 | 308.82 | 151.88 | 597.16 | 416.25 | 0.00 | 0.00 | 0.00 |
March | 414.32 | 215.92 | 198.40 | 584.57 | 285.11 | 0.00 | 0.00 | 0.00 |
April | 310.30 | 101.01 | 209.29 | 489.30 | 229.32 | 0.00 | 0.00 | 0.00 |
May | 250.71 | 29.14 | 221.57 | 415.29 | 150.56 | 0.00 | 0.00 | 0.00 |
June | 231.81 | 12.90 | 218.91 | 446.78 | 97.72 | 0.00 | 0.00 | 0.00 |
July | 234.36 | 17.47 | 216.88 | 471.20 | 69.45 | 0.00 | 0.00 | 0.00 |
August | 279.80 | 52.27 | 227.54 | 567.62 | 61.25 | 0.00 | 0.00 | 0.00 |
September | 307.71 | 114.45 | 193.26 | 531.89 | 143.71 | 0.00 | 0.00 | 0.00 |
October | 446.10 | 288.98 | 157.12 | 668.15 | 290.66 | 0.00 | 0.00 | 0.00 |
November | 479.92 | 318.47 | 161.45 | 649.38 | 372.11 | 0.00 | 0.00 | 0.00 |
December | 486.56 | 342.30 | 144.26 | 609.48 | 433.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.92 | 178.21 | 187.71 | 551.53 | 252.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.81 | 12.90 | 144.26 | 415.29 | 61.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.60 | 344.14 | 227.54 | 668.15 | 488.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.60 | 344.14 | 149.47 | 589.05 | 488.81 | 0.00 | 0.00 | 0.00 |
February | 460.70 | 308.82 | 151.88 | 597.16 | 416.25 | 0.00 | 0.00 | 0.00 |
March | 414.32 | 215.92 | 198.40 | 584.57 | 285.11 | 0.00 | 0.00 | 0.00 |
April | 310.30 | 101.01 | 209.29 | 489.30 | 229.32 | 0.00 | 0.00 | 0.00 |
May | 250.71 | 29.14 | 221.57 | 415.29 | 150.56 | 0.00 | 0.00 | 0.00 |
June | 231.81 | 12.90 | 218.91 | 446.78 | 97.72 | 0.00 | 0.00 | 0.00 |
July | 234.36 | 17.47 | 216.88 | 471.20 | 69.45 | 0.00 | 0.00 | 0.00 |
August | 279.80 | 52.27 | 227.54 | 567.62 | 61.25 | 0.00 | 0.00 | 0.00 |
September | 307.71 | 114.45 | 193.26 | 531.89 | 143.71 | 0.00 | 0.00 | 0.00 |
October | 446.10 | 288.98 | 157.12 | 668.15 | 290.66 | 0.00 | 0.00 | 0.00 |
November | 479.92 | 318.47 | 161.45 | 649.38 | 372.11 | 0.00 | 0.00 | 0.00 |
December | 486.56 | 342.30 | 144.26 | 609.48 | 433.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.92 | 178.21 | 187.71 | 551.53 | 252.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.81 | 12.90 | 144.26 | 415.29 | 61.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.60 | 344.14 | 227.54 | 668.15 | 488.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.57 | 344.12 | 149.46 | 589.01 | 488.78 | 0.00 | 0.00 | 0.00 |
February | 460.67 | 308.80 | 151.87 | 597.13 | 416.22 | 0.00 | 0.00 | 0.00 |
March | 414.30 | 215.91 | 198.39 | 584.53 | 285.09 | 0.00 | 0.00 | 0.00 |
April | 310.28 | 101.00 | 209.28 | 489.27 | 229.31 | 0.00 | 0.00 | 0.00 |
May | 250.70 | 29.14 | 221.56 | 415.26 | 150.55 | 0.00 | 0.00 | 0.00 |
June | 231.80 | 12.90 | 218.90 | 446.75 | 97.71 | 0.00 | 0.00 | 0.00 |
July | 234.34 | 17.47 | 216.87 | 471.17 | 69.45 | 0.00 | 0.00 | 0.00 |
August | 279.79 | 52.26 | 227.52 | 567.58 | 61.24 | 0.00 | 0.00 | 0.00 |
September | 307.69 | 114.45 | 193.25 | 531.85 | 143.70 | 0.00 | 0.00 | 0.00 |
October | 446.07 | 288.96 | 157.11 | 668.11 | 290.65 | 0.00 | 0.00 | 0.00 |
November | 479.89 | 318.45 | 161.44 | 649.33 | 372.09 | 0.00 | 0.00 | 0.00 |
December | 486.53 | 342.27 | 144.25 | 609.44 | 433.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.90 | 178.20 | 187.69 | 551.49 | 252.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.80 | 12.90 | 144.25 | 415.26 | 61.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.57 | 344.12 | 227.52 | 668.11 | 488.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 400.55 | 185.80 | 214.75 | 342.62 | 1030.70 | 0.00 | 0.00 | 0.00 |
February | 459.83 | 215.00 | 244.83 | 504.35 | 855.40 | 0.00 | 0.00 | 0.00 |
March | 677.76 | 327.51 | 350.25 | 885.86 | 558.92 | 0.00 | 0.00 | 0.00 |
April | 762.47 | 348.90 | 413.57 | 1132.34 | 451.71 | 0.00 | 0.00 | 0.00 |
May | 766.30 | 290.32 | 475.98 | 1230.90 | 307.61 | 0.00 | 0.00 | 0.00 |
June | 805.87 | 310.01 | 495.86 | 1445.62 | 204.18 | 0.00 | 0.00 | 0.00 |
July | 760.12 | 281.83 | 478.29 | 1406.90 | 145.77 | 0.00 | 0.00 | 0.00 |
August | 744.81 | 278.53 | 466.28 | 1388.94 | 127.78 | 0.00 | 0.00 | 0.00 |
September | 606.82 | 252.76 | 354.05 | 984.70 | 281.48 | 0.00 | 0.00 | 0.00 |
October | 540.60 | 280.63 | 259.97 | 745.02 | 579.00 | 0.00 | 0.00 | 0.00 |
November | 431.44 | 193.65 | 237.79 | 496.60 | 753.75 | 0.00 | 0.00 | 0.00 |
December | 355.93 | 155.69 | 200.25 | 323.13 | 894.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 610.14 | 260.24 | 349.90 | 909.38 | 514.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.93 | 155.69 | 200.25 | 323.13 | 127.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 805.87 | 348.90 | 495.86 | 1445.62 | 1030.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.84 | 7.35 | 8.49 | 13.55 | 40.75 | 0.00 | 0.00 | 0.00 |
February | 18.18 | 8.50 | 9.68 | 19.94 | 33.82 | 0.00 | 0.00 | 0.00 |
March | 26.80 | 12.95 | 13.85 | 35.03 | 22.10 | 0.00 | 0.00 | 0.00 |
April | 30.15 | 13.80 | 16.35 | 44.77 | 17.86 | 0.00 | 0.00 | 0.00 |
May | 30.30 | 11.48 | 18.82 | 48.67 | 12.16 | 0.00 | 0.00 | 0.00 |
June | 31.86 | 12.26 | 19.61 | 57.16 | 8.07 | 0.00 | 0.00 | 0.00 |
July | 30.05 | 11.14 | 18.91 | 55.63 | 5.76 | 0.00 | 0.00 | 0.00 |
August | 29.45 | 11.01 | 18.44 | 54.92 | 5.05 | 0.00 | 0.00 | 0.00 |
September | 23.99 | 9.99 | 14.00 | 38.93 | 11.13 | 0.00 | 0.00 | 0.00 |
October | 21.37 | 11.10 | 10.28 | 29.46 | 22.89 | 0.00 | 0.00 | 0.00 |
November | 17.06 | 7.66 | 9.40 | 19.63 | 29.80 | 0.00 | 0.00 | 0.00 |
December | 14.07 | 6.16 | 7.92 | 12.78 | 35.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.12 | 10.29 | 13.83 | 35.96 | 20.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.07 | 6.16 | 7.92 | 12.78 | 5.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.86 | 13.80 | 19.61 | 57.16 | 40.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 276.89 | 0.00 | 276.89 | 49.54 | 1720.14 | 0.00 | 0.00 | 0.00 |
February | 306.91 | 0.00 | 306.91 | 147.71 | 1410.33 | 0.00 | 0.00 | 0.00 |
March | 430.88 | 0.00 | 430.88 | 323.89 | 900.31 | 0.00 | 0.00 | 0.00 |
April | 521.19 | 2.31 | 518.87 | 596.21 | 722.35 | 0.00 | 0.00 | 0.00 |
May | 623.33 | 19.89 | 603.44 | 891.08 | 468.92 | 0.00 | 0.00 | 0.00 |
June | 686.00 | 45.29 | 640.71 | 1260.49 | 294.89 | 0.00 | 0.00 | 0.00 |
July | 647.25 | 31.46 | 615.78 | 1257.47 | 212.54 | 0.00 | 0.00 | 0.00 |
August | 575.62 | 6.27 | 569.35 | 1146.97 | 176.74 | 0.00 | 0.00 | 0.00 |
September | 435.11 | 0.06 | 435.05 | 662.79 | 404.62 | 0.00 | 0.00 | 0.00 |
October | 330.83 | 0.00 | 330.83 | 306.76 | 841.48 | 0.00 | 0.00 | 0.00 |
November | 296.08 | 0.00 | 296.08 | 172.71 | 1128.58 | 0.00 | 0.00 | 0.00 |
December | 255.96 | 0.00 | 255.96 | 54.40 | 1408.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 449.61 | 8.81 | 440.80 | 574.89 | 804.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.96 | 0.00 | 255.96 | 49.54 | 176.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 686.00 | 45.29 | 640.71 | 1260.49 | 1720.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 405.39 | 182.85 | 222.54 | 299.42 | 1027.51 | 0.00 | 0.00 | 0.00 |
February | 511.07 | 274.59 | 236.48 | 512.54 | 851.25 | 0.00 | 0.00 | 0.00 |
March | 642.99 | 292.71 | 350.28 | 745.20 | 560.63 | 0.00 | 0.00 | 0.00 |
April | 777.54 | 354.54 | 423.00 | 1084.25 | 459.16 | 0.00 | 0.00 | 0.00 |
May | 853.79 | 361.06 | 492.74 | 1316.21 | 311.51 | 0.00 | 0.00 | 0.00 |
June | 883.96 | 370.49 | 513.47 | 1547.88 | 198.43 | 0.00 | 0.00 | 0.00 |
July | 861.90 | 362.35 | 499.54 | 1557.79 | 144.20 | 0.00 | 0.00 | 0.00 |
August | 788.35 | 312.77 | 475.59 | 1449.99 | 119.33 | 0.00 | 0.00 | 0.00 |
September | 647.92 | 287.08 | 360.84 | 1036.39 | 263.64 | 0.00 | 0.00 | 0.00 |
October | 552.73 | 287.60 | 265.13 | 716.98 | 526.95 | 0.00 | 0.00 | 0.00 |
November | 441.91 | 200.10 | 241.82 | 450.38 | 685.87 | 0.00 | 0.00 | 0.00 |
December | 382.78 | 174.49 | 208.29 | 303.86 | 844.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.51 | 288.34 | 358.17 | 920.52 | 497.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.78 | 174.49 | 208.29 | 299.42 | 119.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.96 | 370.49 | 513.47 | 1557.79 | 1027.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1480.84 | 1032.44 | 448.40 | 1728.11 | 1457.55 | 0.00 | 0.00 | 0.00 |
February | 1382.12 | 926.47 | 455.65 | 1750.38 | 1256.12 | 0.00 | 0.00 | 0.00 |
March | 1242.99 | 647.78 | 595.22 | 1701.95 | 883.97 | 0.00 | 0.00 | 0.00 |
April | 930.92 | 303.03 | 627.89 | 1410.84 | 747.09 | 0.00 | 0.00 | 0.00 |
May | 752.14 | 87.42 | 664.73 | 1201.82 | 498.23 | 0.00 | 0.00 | 0.00 |
June | 695.44 | 38.70 | 656.74 | 1317.22 | 314.87 | 0.00 | 0.00 | 0.00 |
July | 703.07 | 52.43 | 650.65 | 1397.59 | 221.99 | 0.00 | 0.00 | 0.00 |
August | 839.42 | 156.81 | 682.61 | 1697.77 | 185.48 | 0.00 | 0.00 | 0.00 |
September | 923.15 | 343.37 | 579.79 | 1592.97 | 415.30 | 0.00 | 0.00 | 0.00 |
October | 1338.31 | 866.96 | 471.35 | 1998.54 | 821.34 | 0.00 | 0.00 | 0.00 |
November | 1439.78 | 955.42 | 484.37 | 1943.25 | 1049.00 | 0.00 | 0.00 | 0.00 |
December | 1459.70 | 1026.91 | 432.79 | 1809.66 | 1245.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.78 | 534.66 | 563.12 | 1628.87 | 755.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.44 | 38.70 | 432.79 | 1201.82 | 185.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1480.84 | 1032.44 | 682.61 | 1998.54 | 1457.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.39 | 193.15 | 223.24 | 347.23 | 1071.40 | 0.00 | 0.00 | 0.00 |
February | 478.02 | 223.50 | 254.51 | 509.33 | 903.34 | 0.00 | 0.00 | 0.00 |
March | 704.57 | 340.46 | 364.10 | 893.74 | 603.58 | 0.00 | 0.00 | 0.00 |
April | 792.63 | 362.70 | 429.92 | 1144.34 | 498.97 | 0.00 | 0.00 | 0.00 |
May | 796.61 | 301.81 | 494.81 | 1256.20 | 338.63 | 0.00 | 0.00 | 0.00 |
June | 837.74 | 322.28 | 515.47 | 1488.53 | 218.40 | 0.00 | 0.00 | 0.00 |
July | 790.18 | 292.97 | 497.21 | 1452.50 | 154.98 | 0.00 | 0.00 | 0.00 |
August | 774.27 | 289.55 | 484.72 | 1438.75 | 131.18 | 0.00 | 0.00 | 0.00 |
September | 630.82 | 262.76 | 368.05 | 1022.68 | 279.94 | 0.00 | 0.00 | 0.00 |
October | 561.98 | 291.73 | 270.25 | 776.23 | 569.25 | 0.00 | 0.00 | 0.00 |
November | 448.50 | 201.31 | 247.19 | 520.21 | 744.86 | 0.00 | 0.00 | 0.00 |
December | 370.01 | 161.84 | 208.17 | 333.27 | 903.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.27 | 270.54 | 363.73 | 934.16 | 532.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.01 | 161.84 | 208.17 | 333.27 | 131.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.74 | 362.70 | 515.47 | 1488.53 | 1071.40 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.142365E+09 | 0.441278E+10 |
February | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.368340E+09 | 0.326081E+10 |
March | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.892467E+09 | 0.227463E+10 |
April | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.155502E+10 | 0.179316E+10 |
May | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.238039E+10 | 0.121892E+10 |
June | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.324463E+10 | 0.751939E+09 |
July | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.333623E+10 | 0.564846E+09 |
August | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.304400E+10 | 0.467947E+09 |
September | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.172095E+10 | 0.993344E+09 |
October | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.853310E+09 | 0.209473E+10 |
November | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.491750E+09 | 0.271274E+10 |
December | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.162953E+09 | 0.352269E+10 |
Annual Sum or Average | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.181924E+11 | 0.240685E+11 |
Minimum of Months | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.142365E+09 | 0.467947E+09 |
Maximum of Months | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.333623E+10 | 0.441278E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.826965E+09 | 0.263531E+10 |
February | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.126281E+10 | 0.196639E+10 |
March | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.202914E+10 | 0.141939E+10 |
April | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.282571E+10 | 0.114564E+10 |
May | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.352729E+10 | 0.812987E+09 |
June | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.400478E+10 | 0.506296E+09 |
July | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.415964E+10 | 0.382047E+09 |
August | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.387356E+10 | 0.314921E+09 |
September | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.269520E+10 | 0.649949E+09 |
October | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.195338E+10 | 0.131922E+10 |
November | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.122287E+10 | 0.164794E+10 |
December | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.850815E+09 | 0.210661E+10 |
Annual Sum or Average | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.292322E+11 | 0.149067E+11 |
Minimum of Months | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.826965E+09 | 0.314921E+09 |
Maximum of Months | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.415964E+10 | 0.263531E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.467106E+10 | 0.372483E+10 |
February | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.426090E+10 | 0.289705E+10 |
March | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.458347E+10 | 0.224155E+10 |
April | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.366187E+10 | 0.185892E+10 |
May | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.320720E+10 | 0.129406E+10 |
June | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.338926E+10 | 0.799962E+09 |
July | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.371097E+10 | 0.587802E+09 |
August | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.451723E+10 | 0.489950E+09 |
September | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.412675E+10 | 0.102443E+10 |
October | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.537924E+10 | 0.206131E+10 |
November | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.509547E+10 | 0.253433E+10 |
December | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.490276E+10 | 0.311872E+10 |
Annual Sum or Average | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.515062E+11 | 0.226329E+11 |
Minimum of Months | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.320720E+10 | 0.489950E+09 |
Maximum of Months | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.537924E+10 | 0.372483E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.941262E+09 | 0.274431E+10 |
February | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.123975E+10 | 0.208571E+10 |
March | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.240668E+10 | 0.152625E+10 |
April | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.296896E+10 | 0.123899E+10 |
May | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.335584E+10 | 0.878864E+09 |
June | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.383970E+10 | 0.553988E+09 |
July | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.386891E+10 | 0.409787E+09 |
August | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.383370E+10 | 0.346762E+09 |
September | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.265005E+10 | 0.689437E+09 |
October | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.209561E+10 | 0.142142E+10 |
November | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.137819E+10 | 0.179390E+10 |
December | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.911301E+09 | 0.226134E+10 |
Annual Sum or Average | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.294900E+11 | 0.159507E+11 |
Minimum of Months | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.911301E+09 | 0.346762E+09 |
Maximum of Months | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.386891E+10 | 0.274431E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247195E+09 | 0.00 | 0.247195E+09 | 46997211.49 | 0.152265E+10 |
February | 0.247477E+09 | 0.00 | 0.247477E+09 | 0.129701E+09 | 0.110698E+10 |
March | 0.384670E+09 | 0.00 | 0.384670E+09 | 0.324722E+09 | 0.746121E+09 |
April | 0.450284E+09 | 1997142.59 | 0.448287E+09 | 0.564975E+09 | 0.560649E+09 |
May | 0.556484E+09 | 17759922.67 | 0.538724E+09 | 0.834499E+09 | 0.377786E+09 |
June | 0.592679E+09 | 39130827.43 | 0.553548E+09 | 0.110884E+10 | 0.237948E+09 |
July | 0.577834E+09 | 28088916.80 | 0.549745E+09 | 0.113837E+10 | 0.177284E+09 |
August | 0.513888E+09 | 5598005.79 | 0.508290E+09 | 0.103191E+10 | 0.150548E+09 |
September | 0.375920E+09 | 52919.09 | 0.375867E+09 | 0.573099E+09 | 0.355956E+09 |
October | 0.295352E+09 | 0.00 | 0.295352E+09 | 0.270670E+09 | 0.776276E+09 |
November | 0.255803E+09 | 0.00 | 0.255803E+09 | 0.144340E+09 | 0.100604E+10 |
December | 0.228514E+09 | 0.00 | 0.228514E+09 | 49691595.53 | 0.128206E+10 |
Annual Sum or Average | 0.472610E+10 | 92627734.38 | 0.463347E+10 | 0.621782E+10 | 0.830030E+10 |
Minimum of Months | 0.228514E+09 | 0.00 | 0.228514E+09 | 46997211.49 | 0.150548E+09 |
Maximum of Months | 0.592679E+09 | 39130827.43 | 0.553548E+09 | 0.113837E+10 | 0.152265E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247205E+09 | 0.00 | 0.247205E+09 | 46997821.34 | 0.152275E+10 |
February | 0.247487E+09 | 0.00 | 0.247487E+09 | 0.129705E+09 | 0.110705E+10 |
March | 0.384685E+09 | 0.00 | 0.384685E+09 | 0.324733E+09 | 0.746165E+09 |
April | 0.450302E+09 | 1997196.27 | 0.448305E+09 | 0.564999E+09 | 0.560681E+09 |
May | 0.556506E+09 | 17760400.06 | 0.538746E+09 | 0.834533E+09 | 0.377807E+09 |
June | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.110889E+10 | 0.237960E+09 |
July | 0.577857E+09 | 28089671.84 | 0.549767E+09 | 0.113842E+10 | 0.177292E+09 |
August | 0.513909E+09 | 5598156.26 | 0.508311E+09 | 0.103196E+10 | 0.150555E+09 |
September | 0.375935E+09 | 52920.51 | 0.375882E+09 | 0.573124E+09 | 0.355975E+09 |
October | 0.295364E+09 | 0.00 | 0.295364E+09 | 0.270680E+09 | 0.776322E+09 |
November | 0.255813E+09 | 0.00 | 0.255813E+09 | 0.144344E+09 | 0.100610E+10 |
December | 0.228523E+09 | 0.00 | 0.228523E+09 | 49691650.78 | 0.128214E+10 |
Annual Sum or Average | 0.472629E+10 | 92630224.23 | 0.463366E+10 | 0.621808E+10 | 0.830080E+10 |
Minimum of Months | 0.228523E+09 | 0.00 | 0.228523E+09 | 46997821.34 | 0.150555E+09 |
Maximum of Months | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.113842E+10 | 0.152275E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247205E+09 | 0.00 | 0.247205E+09 | 46997821.34 | 0.152275E+10 |
February | 0.247487E+09 | 0.00 | 0.247487E+09 | 0.129705E+09 | 0.110705E+10 |
March | 0.384685E+09 | 0.00 | 0.384685E+09 | 0.324733E+09 | 0.746165E+09 |
April | 0.450302E+09 | 1997196.27 | 0.448305E+09 | 0.564999E+09 | 0.560681E+09 |
May | 0.556506E+09 | 17760400.06 | 0.538746E+09 | 0.834533E+09 | 0.377807E+09 |
June | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.110889E+10 | 0.237960E+09 |
July | 0.577857E+09 | 28089671.84 | 0.549767E+09 | 0.113842E+10 | 0.177292E+09 |
August | 0.513909E+09 | 5598156.26 | 0.508311E+09 | 0.103196E+10 | 0.150555E+09 |
September | 0.375935E+09 | 52920.51 | 0.375882E+09 | 0.573124E+09 | 0.355975E+09 |
October | 0.295364E+09 | 0.00 | 0.295364E+09 | 0.270680E+09 | 0.776322E+09 |
November | 0.255813E+09 | 0.00 | 0.255813E+09 | 0.144344E+09 | 0.100610E+10 |
December | 0.228523E+09 | 0.00 | 0.228523E+09 | 49691650.78 | 0.128214E+10 |
Annual Sum or Average | 0.472629E+10 | 92630224.23 | 0.463366E+10 | 0.621808E+10 | 0.830080E+10 |
Minimum of Months | 0.228523E+09 | 0.00 | 0.228523E+09 | 46997821.34 | 0.150555E+09 |
Maximum of Months | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.113842E+10 | 0.152275E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104448E+10 | 0.471113E+09 | 0.573371E+09 | 0.790927E+09 | 0.264821E+10 |
February | 0.118934E+10 | 0.639020E+09 | 0.550317E+09 | 0.123076E+10 | 0.195277E+10 |
March | 0.165665E+10 | 0.754150E+09 | 0.902495E+09 | 0.200140E+10 | 0.138175E+10 |
April | 0.193869E+10 | 0.883988E+09 | 0.105470E+10 | 0.279404E+10 | 0.107054E+10 |
May | 0.219979E+10 | 0.930254E+09 | 0.126953E+10 | 0.346581E+10 | 0.755801E+09 |
June | 0.220405E+10 | 0.923768E+09 | 0.128028E+10 | 0.390431E+10 | 0.479900E+09 |
July | 0.222067E+10 | 0.933599E+09 | 0.128707E+10 | 0.404984E+10 | 0.364003E+09 |
August | 0.203118E+10 | 0.805839E+09 | 0.122534E+10 | 0.376028E+10 | 0.309715E+09 |
September | 0.161550E+10 | 0.715785E+09 | 0.899719E+09 | 0.259578E+10 | 0.686364E+09 |
October | 0.142410E+10 | 0.740991E+09 | 0.683110E+09 | 0.184908E+10 | 0.143354E+10 |
November | 0.110185E+10 | 0.498912E+09 | 0.602939E+09 | 0.111532E+10 | 0.179989E+10 |
December | 0.986230E+09 | 0.449560E+09 | 0.536670E+09 | 0.790540E+09 | 0.224276E+10 |
Annual Sum or Average | 0.196125E+11 | 0.874698E+10 | 0.108656E+11 | 0.283481E+11 | 0.151252E+11 |
Minimum of Months | 0.986230E+09 | 0.449560E+09 | 0.536670E+09 | 0.790540E+09 | 0.309715E+09 |
Maximum of Months | 0.222067E+10 | 0.933599E+09 | 0.128707E+10 | 0.404984E+10 | 0.264821E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41297968.64 | 18627401.67 | 22670566.97 | 31272536.46 | 0.104708E+09 |
February | 47025321.95 | 25266263.70 | 21759058.25 | 48663222.95 | 77210773.94 |
March | 65502272.49 | 29818417.68 | 35683854.81 | 79133517.60 | 54633201.07 |
April | 76654026.86 | 34952094.60 | 41701932.26 | 0.110474E+09 | 42328264.86 |
May | 86977579.04 | 36781404.46 | 50196174.57 | 0.137035E+09 | 29883696.68 |
June | 87146182.83 | 36524961.51 | 50621221.33 | 0.154373E+09 | 18974829.47 |
July | 87803420.16 | 36913651.60 | 50889768.56 | 0.160127E+09 | 14392358.71 |
August | 80311103.59 | 31862138.09 | 48448965.50 | 0.148678E+09 | 12245856.29 |
September | 63875563.18 | 28301493.83 | 35574069.35 | 0.102635E+09 | 27138229.48 |
October | 56307668.25 | 29298132.82 | 27009535.43 | 73111131.49 | 56680917.12 |
November | 43566232.40 | 19726548.35 | 23839684.04 | 44098603.73 | 71165980.00 |
December | 38994650.79 | 17775203.84 | 21219446.95 | 31257221.58 | 88676818.98 |
Annual Sum or Average | 0.775462E+09 | 0.345848E+09 | 0.429614E+09 | 0.112086E+10 | 0.598039E+09 |
Minimum of Months | 38994650.79 | 17775203.84 | 21219446.95 | 31257221.58 | 12245856.29 |
Maximum of Months | 87803420.16 | 36913651.60 | 50889768.56 | 0.160127E+09 | 0.104708E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132207E+10 | 0.921741E+09 | 0.400330E+09 | 0.157770E+10 | 0.130924E+10 |
February | 0.111452E+10 | 0.747093E+09 | 0.367430E+09 | 0.144466E+10 | 0.100698E+10 |
March | 0.110973E+10 | 0.578322E+09 | 0.531406E+09 | 0.156571E+10 | 0.763641E+09 |
April | 0.804304E+09 | 0.261816E+09 | 0.542488E+09 | 0.126826E+10 | 0.594396E+09 |
May | 0.671509E+09 | 78046639.51 | 0.593462E+09 | 0.111230E+10 | 0.403256E+09 |
June | 0.600853E+09 | 33434677.84 | 0.567418E+09 | 0.115806E+10 | 0.253286E+09 |
July | 0.627698E+09 | 46804225.75 | 0.580894E+09 | 0.126207E+10 | 0.186023E+09 |
August | 0.749425E+09 | 0.139994E+09 | 0.609431E+09 | 0.152031E+10 | 0.164046E+09 |
September | 0.797594E+09 | 0.296662E+09 | 0.500933E+09 | 0.137865E+10 | 0.372488E+09 |
October | 0.119482E+10 | 0.774006E+09 | 0.420819E+09 | 0.178958E+10 | 0.778516E+09 |
November | 0.124395E+10 | 0.825462E+09 | 0.418487E+09 | 0.168318E+10 | 0.964506E+09 |
December | 0.130320E+10 | 0.916806E+09 | 0.386390E+09 | 0.163242E+10 | 0.116188E+10 |
Annual Sum or Average | 0.115397E+11 | 0.562019E+10 | 0.591949E+10 | 0.173929E+11 | 0.795827E+10 |
Minimum of Months | 0.600853E+09 | 33434677.84 | 0.367430E+09 | 0.111230E+10 | 0.164046E+09 |
Maximum of Months | 0.132207E+10 | 0.921741E+09 | 0.609431E+09 | 0.178958E+10 | 0.130924E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132207E+10 | 0.921741E+09 | 0.400330E+09 | 0.157770E+10 | 0.130924E+10 |
February | 0.111452E+10 | 0.747093E+09 | 0.367430E+09 | 0.144466E+10 | 0.100698E+10 |
March | 0.110973E+10 | 0.578322E+09 | 0.531406E+09 | 0.156571E+10 | 0.763641E+09 |
April | 0.804304E+09 | 0.261816E+09 | 0.542488E+09 | 0.126826E+10 | 0.594396E+09 |
May | 0.671509E+09 | 78046639.51 | 0.593462E+09 | 0.111230E+10 | 0.403256E+09 |
June | 0.600853E+09 | 33434677.84 | 0.567418E+09 | 0.115806E+10 | 0.253286E+09 |
July | 0.627698E+09 | 46804225.75 | 0.580894E+09 | 0.126207E+10 | 0.186023E+09 |
August | 0.749425E+09 | 0.139994E+09 | 0.609431E+09 | 0.152031E+10 | 0.164046E+09 |
September | 0.797594E+09 | 0.296662E+09 | 0.500933E+09 | 0.137865E+10 | 0.372488E+09 |
October | 0.119482E+10 | 0.774006E+09 | 0.420819E+09 | 0.178958E+10 | 0.778516E+09 |
November | 0.124395E+10 | 0.825462E+09 | 0.418487E+09 | 0.168318E+10 | 0.964506E+09 |
December | 0.130320E+10 | 0.916806E+09 | 0.386390E+09 | 0.163242E+10 | 0.116188E+10 |
Annual Sum or Average | 0.115397E+11 | 0.562019E+10 | 0.591949E+10 | 0.173929E+11 | 0.795827E+10 |
Minimum of Months | 0.600853E+09 | 33434677.84 | 0.367430E+09 | 0.111230E+10 | 0.164046E+09 |
Maximum of Months | 0.132207E+10 | 0.921741E+09 | 0.609431E+09 | 0.178958E+10 | 0.130924E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132199E+10 | 0.921683E+09 | 0.400305E+09 | 0.157760E+10 | 0.130916E+10 |
February | 0.111445E+10 | 0.747046E+09 | 0.367407E+09 | 0.144457E+10 | 0.100692E+10 |
March | 0.110966E+10 | 0.578285E+09 | 0.531372E+09 | 0.156561E+10 | 0.763593E+09 |
April | 0.804253E+09 | 0.261800E+09 | 0.542454E+09 | 0.126818E+10 | 0.594359E+09 |
May | 0.671466E+09 | 78041707.40 | 0.593424E+09 | 0.111223E+10 | 0.403230E+09 |
June | 0.600815E+09 | 33432564.96 | 0.567382E+09 | 0.115798E+10 | 0.253270E+09 |
July | 0.627659E+09 | 46801267.99 | 0.580857E+09 | 0.126199E+10 | 0.186012E+09 |
August | 0.749378E+09 | 0.139985E+09 | 0.609393E+09 | 0.152022E+10 | 0.164035E+09 |
September | 0.797544E+09 | 0.296643E+09 | 0.500901E+09 | 0.137857E+10 | 0.372465E+09 |
October | 0.119475E+10 | 0.773957E+09 | 0.420792E+09 | 0.178947E+10 | 0.778467E+09 |
November | 0.124387E+10 | 0.825410E+09 | 0.418461E+09 | 0.168307E+10 | 0.964446E+09 |
December | 0.130311E+10 | 0.916748E+09 | 0.386365E+09 | 0.163232E+10 | 0.116181E+10 |
Annual Sum or Average | 0.115389E+11 | 0.561983E+10 | 0.591911E+10 | 0.173918E+11 | 0.795776E+10 |
Minimum of Months | 0.600815E+09 | 33432564.96 | 0.367407E+09 | 0.111223E+10 | 0.164035E+09 |
Maximum of Months | 0.132199E+10 | 0.921683E+09 | 0.609393E+09 | 0.178947E+10 | 0.130916E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107283E+10 | 0.497654E+09 | 0.575180E+09 | 0.917674E+09 | 0.276064E+10 |
February | 0.111242E+10 | 0.520121E+09 | 0.592297E+09 | 0.122012E+10 | 0.206938E+10 |
March | 0.181531E+10 | 0.877198E+09 | 0.938116E+09 | 0.237269E+10 | 0.149700E+10 |
April | 0.197632E+10 | 0.904353E+09 | 0.107197E+10 | 0.293503E+10 | 0.117083E+10 |
May | 0.205247E+10 | 0.777597E+09 | 0.127487E+10 | 0.329685E+10 | 0.823908E+09 |
June | 0.208881E+10 | 0.803554E+09 | 0.128526E+10 | 0.374704E+10 | 0.529243E+09 |
July | 0.203590E+10 | 0.754841E+09 | 0.128106E+10 | 0.376823E+10 | 0.390423E+09 |
August | 0.199490E+10 | 0.746009E+09 | 0.124889E+10 | 0.372015E+10 | 0.342241E+09 |
September | 0.157286E+10 | 0.655165E+09 | 0.917700E+09 | 0.255234E+10 | 0.729585E+09 |
October | 0.144794E+10 | 0.751639E+09 | 0.696304E+09 | 0.199547E+10 | 0.155079E+10 |
November | 0.111829E+10 | 0.501943E+09 | 0.616344E+09 | 0.128718E+10 | 0.195371E+10 |
December | 0.953332E+09 | 0.416987E+09 | 0.536345E+09 | 0.865482E+09 | 0.239644E+10 |
Annual Sum or Average | 0.192414E+11 | 0.820706E+10 | 0.110343E+11 | 0.286782E+11 | 0.162142E+11 |
Minimum of Months | 0.953332E+09 | 0.416987E+09 | 0.536345E+09 | 0.865482E+09 | 0.342241E+09 |
Maximum of Months | 0.208881E+10 | 0.904353E+09 | 0.128526E+10 | 0.376823E+10 | 0.276064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42418767.26 | 19676731.62 | 22742035.64 | 36283829.51 | 0.109153E+09 |
February | 43983894.94 | 20565053.16 | 23418841.78 | 48242191.07 | 81821600.67 |
March | 71775721.37 | 34683525.60 | 37092195.77 | 93813643.84 | 59190115.01 |
April | 78141703.59 | 35757173.75 | 42384529.84 | 0.116048E+09 | 46293685.40 |
May | 81152613.96 | 30745385.62 | 50407228.33 | 0.130354E+09 | 32576557.31 |
June | 82589595.18 | 31771686.60 | 50817908.58 | 0.148154E+09 | 20925780.86 |
July | 80497582.55 | 29845636.76 | 50651945.78 | 0.148992E+09 | 15436960.91 |
August | 78876146.14 | 29496422.79 | 49379723.36 | 0.147091E+09 | 13531865.14 |
September | 62189492.73 | 25904536.92 | 36284955.81 | 0.100917E+09 | 28847092.00 |
October | 57250228.41 | 29719041.32 | 27531187.09 | 78898797.04 | 61316916.50 |
November | 44215952.03 | 19846317.65 | 24369634.38 | 50893785.54 | 77248056.37 |
December | 37693793.36 | 16487250.69 | 21206542.66 | 34220219.13 | 94753124.14 |
Annual Sum or Average | 0.760785E+09 | 0.324499E+09 | 0.436287E+09 | 0.113391E+10 | 0.641095E+09 |
Minimum of Months | 37693793.36 | 16487250.69 | 21206542.66 | 34220219.13 | 13531865.14 |
Maximum of Months | 82589595.18 | 35757173.75 | 50817908.58 | 0.148992E+09 | 0.109153E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.132679E+09 | 0.460722E+10 |
February | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.357329E+09 | 0.341187E+10 |
March | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.867508E+09 | 0.241139E+10 |
April | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.154537E+10 | 0.187234E+10 |
May | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.238668E+10 | 0.125595E+10 |
June | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.326719E+10 | 0.764359E+09 |
July | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.336801E+10 | 0.569266E+09 |
August | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.307205E+10 | 0.473392E+09 |
September | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.171796E+10 | 0.104877E+10 |
October | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.821629E+09 | 0.225381E+10 |
November | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.447676E+09 | 0.292528E+10 |
December | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.145702E+09 | 0.377221E+10 |
Annual Sum or Average | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.181298E+11 | 0.253658E+11 |
Minimum of Months | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.132679E+09 | 0.473392E+09 |
Maximum of Months | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.336801E+10 | 0.460722E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.801976E+09 | 0.275207E+10 |
February | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.123993E+10 | 0.205933E+10 |
March | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.199593E+10 | 0.150158E+10 |
April | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.281037E+10 | 0.119014E+10 |
May | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.352534E+10 | 0.834358E+09 |
June | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.401210E+10 | 0.514335E+09 |
July | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.417239E+10 | 0.386218E+09 |
August | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.388365E+10 | 0.319627E+09 |
September | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.268632E+10 | 0.683347E+09 |
October | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.192036E+10 | 0.141138E+10 |
November | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.116739E+10 | 0.177779E+10 |
December | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.813851E+09 | 0.226080E+10 |
Annual Sum or Average | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.290296E+11 | 0.156910E+11 |
Minimum of Months | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.801976E+09 | 0.319627E+09 |
Maximum of Months | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.417239E+10 | 0.275207E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.462856E+10 | 0.390389E+10 |
February | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.423451E+10 | 0.303881E+10 |
March | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.455851E+10 | 0.236763E+10 |
April | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.365689E+10 | 0.193646E+10 |
May | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.321895E+10 | 0.133446E+10 |
June | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.341423E+10 | 0.816152E+09 |
July | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.374329E+10 | 0.594569E+09 |
August | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.454731E+10 | 0.496787E+09 |
September | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.412898E+10 | 0.107644E+10 |
October | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.535288E+10 | 0.219987E+10 |
November | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.503689E+10 | 0.271901E+10 |
December | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.484699E+10 | 0.333615E+10 |
Annual Sum or Average | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.513680E+11 | 0.238202E+11 |
Minimum of Months | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.321895E+10 | 0.496787E+09 |
Maximum of Months | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.535288E+10 | 0.390389E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.930012E+09 | 0.286964E+10 |
February | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.123216E+10 | 0.218535E+10 |
March | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.239380E+10 | 0.161663E+10 |
April | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.296612E+10 | 0.129333E+10 |
May | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.336460E+10 | 0.906986E+09 |
June | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.385827E+10 | 0.566081E+09 |
July | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.389038E+10 | 0.415099E+09 |
August | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.385355E+10 | 0.351349E+09 |
September | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.265079E+10 | 0.725615E+09 |
October | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.207905E+10 | 0.152468E+10 |
November | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.134838E+10 | 0.193068E+10 |
December | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.892636E+09 | 0.241891E+10 |
Annual Sum or Average | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.294597E+11 | 0.168044E+11 |
Minimum of Months | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.892636E+09 | 0.351349E+09 |
Maximum of Months | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.389038E+10 | 0.286964E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 53.15 | 1647.54 | 276.89 | 0.00 | 276.89 | 0.00 | 0.00 |
February | 152.26 | 1347.89 | 306.91 | 0.00 | 306.91 | 0.00 | 0.00 |
March | 333.21 | 849.25 | 430.88 | 0.00 | 430.88 | 0.00 | 0.00 |
April | 599.93 | 691.80 | 521.19 | 2.31 | 518.87 | 0.00 | 0.00 |
May | 888.74 | 455.09 | 623.33 | 19.89 | 603.44 | 0.00 | 0.00 |
June | 1251.79 | 290.10 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
July | 1245.60 | 210.89 | 647.25 | 31.46 | 615.78 | 0.00 | 0.00 |
August | 1136.50 | 174.71 | 575.62 | 6.27 | 569.35 | 0.00 | 0.00 |
September | 663.95 | 383.23 | 435.11 | 0.06 | 435.05 | 0.00 | 0.00 |
October | 318.59 | 782.08 | 330.83 | 0.00 | 330.83 | 0.00 | 0.00 |
November | 189.72 | 1046.58 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 60.84 | 1315.22 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 576.88 | 763.21 | 449.61 | 8.81 | 440.80 | 0.00 | 0.00 |
Minimum of Months | 53.15 | 174.71 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1251.79 | 1647.54 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 308.75 | 983.91 | 405.39 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 521.99 | 812.83 | 511.07 | 274.59 | 236.48 | 0.00 | 0.00 |
March | 757.59 | 529.94 | 642.99 | 292.71 | 350.28 | 0.00 | 0.00 |
April | 1090.16 | 441.99 | 777.54 | 354.54 | 423.00 | 0.00 | 0.00 |
May | 1316.94 | 303.53 | 853.79 | 361.06 | 492.74 | 0.00 | 0.00 |
June | 1545.06 | 195.33 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
July | 1553.03 | 142.64 | 861.90 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1446.22 | 117.58 | 788.35 | 312.77 | 475.59 | 0.00 | 0.00 |
September | 1039.81 | 250.75 | 647.92 | 287.08 | 360.84 | 0.00 | 0.00 |
October | 729.31 | 492.54 | 552.73 | 287.60 | 265.13 | 0.00 | 0.00 |
November | 471.79 | 635.78 | 441.91 | 200.10 | 241.82 | 0.00 | 0.00 |
December | 317.66 | 786.52 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 926.95 | 472.69 | 646.51 | 288.34 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 308.75 | 117.58 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1553.03 | 983.91 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1743.97 | 1390.69 | 1480.84 | 1032.44 | 448.40 | 0.00 | 0.00 |
February | 1761.29 | 1197.52 | 1382.12 | 926.47 | 455.65 | 0.00 | 0.00 |
March | 1711.27 | 836.90 | 1242.99 | 647.78 | 595.22 | 0.00 | 0.00 |
April | 1412.76 | 717.18 | 930.92 | 303.03 | 627.89 | 0.00 | 0.00 |
May | 1197.43 | 483.15 | 752.14 | 87.42 | 664.73 | 0.00 | 0.00 |
June | 1307.59 | 308.63 | 695.44 | 38.70 | 656.74 | 0.00 | 0.00 |
July | 1385.52 | 219.46 | 703.07 | 52.43 | 650.65 | 0.00 | 0.00 |
August | 1686.54 | 182.93 | 839.42 | 156.81 | 682.61 | 0.00 | 0.00 |
September | 1592.11 | 395.23 | 923.15 | 343.37 | 579.79 | 0.00 | 0.00 |
October | 2008.38 | 769.61 | 1338.31 | 866.96 | 471.35 | 0.00 | 0.00 |
November | 1965.84 | 977.75 | 1439.78 | 955.42 | 484.37 | 0.00 | 0.00 |
December | 1830.48 | 1164.40 | 1459.70 | 1026.91 | 432.79 | 0.00 | 0.00 |
Annual Sum or Average | 1633.25 | 717.69 | 1097.78 | 534.66 | 563.12 | 0.00 | 0.00 |
Minimum of Months | 1197.43 | 182.93 | 695.44 | 38.70 | 432.79 | 0.00 | 0.00 |
Maximum of Months | 2008.38 | 1390.69 | 1480.84 | 1032.44 | 682.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 351.43 | 1024.61 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 512.46 | 862.15 | 478.02 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 898.55 | 569.84 | 704.57 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1145.43 | 478.01 | 792.63 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1252.93 | 328.13 | 796.61 | 301.81 | 494.81 | 0.00 | 0.00 |
June | 1481.36 | 213.73 | 837.74 | 322.28 | 515.47 | 0.00 | 0.00 |
July | 1444.49 | 153.00 | 790.18 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1431.34 | 129.47 | 774.27 | 289.55 | 484.72 | 0.00 | 0.00 |
September | 1022.40 | 265.99 | 630.82 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 782.41 | 530.70 | 561.98 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 531.71 | 692.09 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 340.24 | 844.29 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 935.12 | 505.79 | 634.27 | 270.54 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 340.24 | 129.47 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1481.36 | 1024.61 | 837.74 | 362.70 | 515.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 52.64 | 1705.55 | 276.88 | 0.00 | 276.88 | 0.00 | 0.00 |
February | 160.84 | 1372.80 | 306.90 | 0.00 | 306.90 | 0.00 | 0.00 |
March | 363.72 | 835.74 | 430.87 | 0.00 | 430.87 | 0.00 | 0.00 |
April | 653.92 | 648.92 | 521.18 | 2.31 | 518.86 | 0.00 | 0.00 |
May | 934.72 | 423.16 | 623.32 | 19.89 | 603.43 | 0.00 | 0.00 |
June | 1283.42 | 275.41 | 685.99 | 45.29 | 640.70 | 0.00 | 0.00 |
July | 1275.10 | 198.58 | 647.23 | 31.46 | 615.77 | 0.00 | 0.00 |
August | 1155.85 | 168.63 | 575.61 | 6.27 | 569.34 | 0.00 | 0.00 |
September | 663.33 | 412.00 | 435.10 | 0.06 | 435.04 | 0.00 | 0.00 |
October | 303.18 | 869.52 | 330.82 | 0.00 | 330.82 | 0.00 | 0.00 |
November | 167.06 | 1164.45 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 55.66 | 1436.06 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 591.51 | 789.63 | 449.60 | 8.81 | 440.79 | 0.00 | 0.00 |
Minimum of Months | 52.64 | 168.63 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1283.42 | 1705.55 | 685.99 | 45.29 | 640.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 306.97 | 1027.82 | 405.38 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 528.86 | 839.11 | 511.06 | 274.59 | 236.47 | 0.00 | 0.00 |
March | 776.78 | 536.28 | 642.98 | 292.70 | 350.28 | 0.00 | 0.00 |
April | 1120.57 | 429.35 | 777.52 | 354.53 | 423.00 | 0.00 | 0.00 |
May | 1345.15 | 293.34 | 853.78 | 361.05 | 492.73 | 0.00 | 0.00 |
June | 1565.85 | 192.47 | 883.95 | 370.48 | 513.47 | 0.00 | 0.00 |
July | 1571.82 | 141.28 | 861.89 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1459.44 | 120.21 | 788.34 | 312.76 | 475.58 | 0.00 | 0.00 |
September | 1041.06 | 275.27 | 647.91 | 287.07 | 360.84 | 0.00 | 0.00 |
October | 717.67 | 556.39 | 552.72 | 287.59 | 265.13 | 0.00 | 0.00 |
November | 447.31 | 721.86 | 441.91 | 200.09 | 241.81 | 0.00 | 0.00 |
December | 306.82 | 870.46 | 382.78 | 174.48 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 934.45 | 498.58 | 646.50 | 288.33 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 306.82 | 120.21 | 382.78 | 174.48 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1571.82 | 1027.82 | 883.95 | 370.48 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1767.10 | 1466.41 | 1480.78 | 1032.39 | 448.39 | 0.00 | 0.00 |
February | 1791.45 | 1248.71 | 1382.07 | 926.44 | 455.63 | 0.00 | 0.00 |
March | 1753.67 | 855.31 | 1242.95 | 647.75 | 595.20 | 0.00 | 0.00 |
April | 1467.87 | 687.94 | 930.89 | 303.02 | 627.87 | 0.00 | 0.00 |
May | 1245.83 | 451.67 | 752.12 | 87.42 | 664.71 | 0.00 | 0.00 |
June | 1340.31 | 293.15 | 695.42 | 38.70 | 656.72 | 0.00 | 0.00 |
July | 1413.58 | 208.36 | 703.05 | 52.42 | 650.63 | 0.00 | 0.00 |
August | 1702.82 | 183.74 | 839.39 | 156.80 | 682.59 | 0.00 | 0.00 |
September | 1595.63 | 431.11 | 923.12 | 343.35 | 579.77 | 0.00 | 0.00 |
October | 2004.42 | 871.98 | 1338.26 | 866.92 | 471.34 | 0.00 | 0.00 |
November | 1948.08 | 1116.30 | 1439.73 | 955.38 | 484.35 | 0.00 | 0.00 |
December | 1828.39 | 1301.36 | 1459.64 | 1026.87 | 432.78 | 0.00 | 0.00 |
Annual Sum or Average | 1654.54 | 757.05 | 1097.74 | 534.63 | 563.11 | 0.00 | 0.00 |
Minimum of Months | 1245.83 | 183.74 | 695.42 | 38.70 | 432.78 | 0.00 | 0.00 |
Maximum of Months | 2004.42 | 1466.41 | 1480.78 | 1032.39 | 682.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 356.17 | 1071.46 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 524.29 | 889.22 | 478.01 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 920.89 | 581.02 | 704.56 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1177.11 | 469.57 | 792.62 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1279.57 | 319.77 | 796.60 | 301.80 | 494.80 | 0.00 | 0.00 |
June | 1502.77 | 212.26 | 837.73 | 322.27 | 515.46 | 0.00 | 0.00 |
July | 1462.52 | 151.53 | 790.17 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1443.86 | 132.83 | 774.26 | 289.54 | 484.72 | 0.00 | 0.00 |
September | 1023.63 | 292.60 | 630.81 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 774.48 | 601.89 | 561.97 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 516.23 | 783.55 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 335.91 | 930.11 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 945.34 | 534.48 | 634.27 | 270.53 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 335.91 | 132.83 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1502.77 | 1071.46 | 837.73 | 362.70 | 515.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.54 | 1720.14 | 276.89 | 0.00 | 276.89 | 0.00 | 0.00 |
February | 147.71 | 1410.33 | 306.91 | 0.00 | 306.91 | 0.00 | 0.00 |
March | 323.89 | 900.31 | 430.88 | 0.00 | 430.88 | 0.00 | 0.00 |
April | 596.21 | 722.35 | 521.19 | 2.31 | 518.87 | 0.00 | 0.00 |
May | 891.08 | 468.92 | 623.33 | 19.89 | 603.44 | 0.00 | 0.00 |
June | 1260.49 | 294.89 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
July | 1257.47 | 212.54 | 647.25 | 31.46 | 615.78 | 0.00 | 0.00 |
August | 1146.97 | 176.74 | 575.62 | 6.27 | 569.35 | 0.00 | 0.00 |
September | 662.79 | 404.62 | 435.11 | 0.06 | 435.05 | 0.00 | 0.00 |
October | 306.76 | 841.48 | 330.83 | 0.00 | 330.83 | 0.00 | 0.00 |
November | 172.71 | 1128.58 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 54.40 | 1408.38 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 574.89 | 804.35 | 449.61 | 8.81 | 440.80 | 0.00 | 0.00 |
Minimum of Months | 49.54 | 176.74 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1260.49 | 1720.14 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 299.42 | 1027.51 | 405.39 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 512.54 | 851.25 | 511.07 | 274.59 | 236.48 | 0.00 | 0.00 |
March | 745.20 | 560.63 | 642.99 | 292.71 | 350.28 | 0.00 | 0.00 |
April | 1084.25 | 459.16 | 777.54 | 354.54 | 423.00 | 0.00 | 0.00 |
May | 1316.21 | 311.51 | 853.79 | 361.06 | 492.74 | 0.00 | 0.00 |
June | 1547.88 | 198.43 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
July | 1557.79 | 144.20 | 861.90 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1449.99 | 119.33 | 788.35 | 312.77 | 475.59 | 0.00 | 0.00 |
September | 1036.39 | 263.64 | 647.92 | 287.08 | 360.84 | 0.00 | 0.00 |
October | 716.98 | 526.95 | 552.73 | 287.60 | 265.13 | 0.00 | 0.00 |
November | 450.38 | 685.87 | 441.91 | 200.10 | 241.82 | 0.00 | 0.00 |
December | 303.86 | 844.09 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 920.52 | 497.56 | 646.51 | 288.34 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 299.42 | 119.33 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1557.79 | 1027.51 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1728.11 | 1457.55 | 1480.84 | 1032.44 | 448.40 | 0.00 | 0.00 |
February | 1750.38 | 1256.12 | 1382.12 | 926.47 | 455.65 | 0.00 | 0.00 |
March | 1701.95 | 883.97 | 1242.99 | 647.78 | 595.22 | 0.00 | 0.00 |
April | 1410.84 | 747.09 | 930.92 | 303.03 | 627.89 | 0.00 | 0.00 |
May | 1201.82 | 498.23 | 752.14 | 87.42 | 664.73 | 0.00 | 0.00 |
June | 1317.22 | 314.87 | 695.44 | 38.70 | 656.74 | 0.00 | 0.00 |
July | 1397.59 | 221.99 | 703.07 | 52.43 | 650.65 | 0.00 | 0.00 |
August | 1697.77 | 185.48 | 839.42 | 156.81 | 682.61 | 0.00 | 0.00 |
September | 1592.97 | 415.30 | 923.15 | 343.37 | 579.79 | 0.00 | 0.00 |
October | 1998.54 | 821.34 | 1338.31 | 866.96 | 471.35 | 0.00 | 0.00 |
November | 1943.25 | 1049.00 | 1439.78 | 955.42 | 484.37 | 0.00 | 0.00 |
December | 1809.66 | 1245.58 | 1459.70 | 1026.91 | 432.79 | 0.00 | 0.00 |
Annual Sum or Average | 1628.87 | 755.33 | 1097.78 | 534.66 | 563.12 | 0.00 | 0.00 |
Minimum of Months | 1201.82 | 185.48 | 695.44 | 38.70 | 432.79 | 0.00 | 0.00 |
Maximum of Months | 1998.54 | 1457.55 | 1480.84 | 1032.44 | 682.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.23 | 1071.40 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 509.33 | 903.34 | 478.02 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 893.74 | 603.58 | 704.57 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1144.34 | 498.97 | 792.63 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1256.20 | 338.63 | 796.61 | 301.81 | 494.81 | 0.00 | 0.00 |
June | 1488.53 | 218.40 | 837.74 | 322.28 | 515.47 | 0.00 | 0.00 |
July | 1452.50 | 154.98 | 790.18 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1438.75 | 131.18 | 774.27 | 289.55 | 484.72 | 0.00 | 0.00 |
September | 1022.68 | 279.94 | 630.82 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 776.23 | 569.25 | 561.98 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 520.21 | 744.86 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 333.27 | 903.12 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 934.16 | 532.86 | 634.27 | 270.54 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 333.27 | 131.18 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1488.53 | 1071.40 | 837.74 | 362.70 | 515.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142365E+09 | 0.441278E+10 | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.00 | 0.00 |
February | 0.368340E+09 | 0.326081E+10 | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.00 | 0.00 |
March | 0.892467E+09 | 0.227463E+10 | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.00 | 0.00 |
April | 0.155502E+10 | 0.179316E+10 | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.00 | 0.00 |
May | 0.238039E+10 | 0.121892E+10 | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.00 | 0.00 |
June | 0.324463E+10 | 0.751939E+09 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
July | 0.333623E+10 | 0.564846E+09 | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.00 | 0.00 |
August | 0.304400E+10 | 0.467947E+09 | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.00 | 0.00 |
September | 0.172095E+10 | 0.993344E+09 | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.00 | 0.00 |
October | 0.853310E+09 | 0.209473E+10 | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.00 | 0.00 |
November | 0.491750E+09 | 0.271274E+10 | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.00 | 0.00 |
December | 0.162953E+09 | 0.352269E+10 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181924E+11 | 0.240685E+11 | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142365E+09 | 0.467947E+09 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.333623E+10 | 0.441278E+10 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.826965E+09 | 0.263531E+10 | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.00 | 0.00 |
February | 0.126281E+10 | 0.196639E+10 | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.00 | 0.00 |
March | 0.202914E+10 | 0.141939E+10 | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.00 | 0.00 |
April | 0.282571E+10 | 0.114564E+10 | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.00 | 0.00 |
May | 0.352729E+10 | 0.812987E+09 | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.00 | 0.00 |
June | 0.400478E+10 | 0.506296E+09 | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.00 | 0.00 |
July | 0.415964E+10 | 0.382047E+09 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
August | 0.387356E+10 | 0.314921E+09 | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.00 | 0.00 |
September | 0.269520E+10 | 0.649949E+09 | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.00 | 0.00 |
October | 0.195338E+10 | 0.131922E+10 | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.00 | 0.00 |
November | 0.122287E+10 | 0.164794E+10 | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.00 | 0.00 |
December | 0.850815E+09 | 0.210661E+10 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292322E+11 | 0.149067E+11 | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.00 | 0.00 |
Minimum of Months | 0.826965E+09 | 0.314921E+09 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.415964E+10 | 0.263531E+10 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.467106E+10 | 0.372483E+10 | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.00 | 0.00 |
February | 0.426090E+10 | 0.289705E+10 | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.00 | 0.00 |
March | 0.458347E+10 | 0.224155E+10 | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.00 | 0.00 |
April | 0.366187E+10 | 0.185892E+10 | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.00 | 0.00 |
May | 0.320720E+10 | 0.129406E+10 | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.00 | 0.00 |
June | 0.338926E+10 | 0.799962E+09 | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.00 | 0.00 |
July | 0.371097E+10 | 0.587802E+09 | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.00 | 0.00 |
August | 0.451723E+10 | 0.489950E+09 | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.00 | 0.00 |
September | 0.412675E+10 | 0.102443E+10 | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.537924E+10 | 0.206131E+10 | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.00 | 0.00 |
November | 0.509547E+10 | 0.253433E+10 | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.00 | 0.00 |
December | 0.490276E+10 | 0.311872E+10 | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.515062E+11 | 0.226329E+11 | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320720E+10 | 0.489950E+09 | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.537924E+10 | 0.372483E+10 | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.941262E+09 | 0.274431E+10 | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.00 | 0.00 |
February | 0.123975E+10 | 0.208571E+10 | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.00 | 0.00 |
March | 0.240668E+10 | 0.152625E+10 | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.00 | 0.00 |
April | 0.296896E+10 | 0.123899E+10 | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.00 | 0.00 |
May | 0.335584E+10 | 0.878864E+09 | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.00 | 0.00 |
June | 0.383970E+10 | 0.553988E+09 | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.00 | 0.00 |
July | 0.386891E+10 | 0.409787E+09 | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.00 | 0.00 |
August | 0.383370E+10 | 0.346762E+09 | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.00 | 0.00 |
September | 0.265005E+10 | 0.689437E+09 | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.00 | 0.00 |
October | 0.209561E+10 | 0.142142E+10 | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.00 | 0.00 |
November | 0.137819E+10 | 0.179390E+10 | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.00 | 0.00 |
December | 0.911301E+09 | 0.226134E+10 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294900E+11 | 0.159507E+11 | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.911301E+09 | 0.346762E+09 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386891E+10 | 0.274431E+10 | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140993E+09 | 0.456815E+10 | 0.741606E+09 | 0.00 | 0.741606E+09 | 0.00 | 0.00 |
February | 0.389110E+09 | 0.332107E+10 | 0.742450E+09 | 0.00 | 0.742450E+09 | 0.00 | 0.00 |
March | 0.974188E+09 | 0.223845E+10 | 0.115404E+10 | 0.00 | 0.115404E+10 | 0.00 | 0.00 |
April | 0.169497E+10 | 0.168201E+10 | 0.135089E+10 | 5991535.14 | 0.134490E+10 | 0.00 | 0.00 |
May | 0.250357E+10 | 0.113340E+10 | 0.166950E+10 | 53280722.79 | 0.161622E+10 | 0.00 | 0.00 |
June | 0.332662E+10 | 0.713869E+09 | 0.177808E+10 | 0.117395E+09 | 0.166069E+10 | 0.00 | 0.00 |
July | 0.341522E+10 | 0.531868E+09 | 0.173355E+10 | 84268260.49 | 0.164928E+10 | 0.00 | 0.00 |
August | 0.309582E+10 | 0.451658E+09 | 0.154171E+10 | 16794318.31 | 0.152491E+10 | 0.00 | 0.00 |
September | 0.171935E+10 | 0.106791E+10 | 0.112779E+10 | 158760.12 | 0.112763E+10 | 0.00 | 0.00 |
October | 0.812030E+09 | 0.232892E+10 | 0.886080E+09 | 0.00 | 0.886080E+09 | 0.00 | 0.00 |
November | 0.433028E+09 | 0.301825E+10 | 0.767428E+09 | 0.00 | 0.767428E+09 | 0.00 | 0.00 |
December | 0.149075E+09 | 0.384635E+10 | 0.685560E+09 | 0.00 | 0.685560E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186540E+11 | 0.249019E+11 | 0.141787E+11 | 0.277888E+09 | 0.139008E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140993E+09 | 0.451658E+09 | 0.685560E+09 | 0.00 | 0.685560E+09 | 0.00 | 0.00 |
Maximum of Months | 0.341522E+10 | 0.456815E+10 | 0.177808E+10 | 0.117395E+09 | 0.166069E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.822199E+09 | 0.275291E+10 | 0.108578E+10 | 0.489741E+09 | 0.596041E+09 | 0.00 | 0.00 |
February | 0.127943E+10 | 0.202998E+10 | 0.123636E+10 | 0.664286E+09 | 0.572077E+09 | 0.00 | 0.00 |
March | 0.208053E+10 | 0.143638E+10 | 0.172215E+10 | 0.783969E+09 | 0.938179E+09 | 0.00 | 0.00 |
April | 0.290451E+10 | 0.111287E+10 | 0.201534E+10 | 0.918940E+09 | 0.109640E+10 | 0.00 | 0.00 |
May | 0.360285E+10 | 0.785685E+09 | 0.228676E+10 | 0.967035E+09 | 0.131973E+10 | 0.00 | 0.00 |
June | 0.405868E+10 | 0.498875E+09 | 0.229120E+10 | 0.960293E+09 | 0.133090E+10 | 0.00 | 0.00 |
July | 0.420997E+10 | 0.378396E+09 | 0.230848E+10 | 0.970512E+09 | 0.133796E+10 | 0.00 | 0.00 |
August | 0.390896E+10 | 0.321961E+09 | 0.211149E+10 | 0.837701E+09 | 0.127379E+10 | 0.00 | 0.00 |
September | 0.269842E+10 | 0.713503E+09 | 0.167938E+10 | 0.744086E+09 | 0.935293E+09 | 0.00 | 0.00 |
October | 0.192220E+10 | 0.149022E+10 | 0.148041E+10 | 0.770290E+09 | 0.710119E+09 | 0.00 | 0.00 |
November | 0.115941E+10 | 0.187105E+10 | 0.114542E+10 | 0.518639E+09 | 0.626779E+09 | 0.00 | 0.00 |
December | 0.821797E+09 | 0.233144E+10 | 0.102522E+10 | 0.467335E+09 | 0.557889E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294690E+11 | 0.157233E+11 | 0.203880E+11 | 0.909283E+10 | 0.112952E+11 | 0.00 | 0.00 |
Minimum of Months | 0.821797E+09 | 0.321961E+09 | 0.102522E+10 | 0.467335E+09 | 0.557889E+09 | 0.00 | 0.00 |
Maximum of Months | 0.420997E+10 | 0.275291E+10 | 0.230848E+10 | 0.970512E+09 | 0.133796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.473300E+10 | 0.392764E+10 | 0.396613E+10 | 0.276517E+10 | 0.120096E+10 | 0.00 | 0.00 |
February | 0.433388E+10 | 0.302089E+10 | 0.334350E+10 | 0.224123E+10 | 0.110227E+10 | 0.00 | 0.00 |
March | 0.469703E+10 | 0.229087E+10 | 0.332911E+10 | 0.173493E+10 | 0.159418E+10 | 0.00 | 0.00 |
April | 0.380471E+10 | 0.178315E+10 | 0.241286E+10 | 0.785432E+09 | 0.162743E+10 | 0.00 | 0.00 |
May | 0.333683E+10 | 0.120974E+10 | 0.201448E+10 | 0.234135E+09 | 0.178035E+10 | 0.00 | 0.00 |
June | 0.347409E+10 | 0.759841E+09 | 0.180252E+10 | 0.100302E+09 | 0.170222E+10 | 0.00 | 0.00 |
July | 0.378614E+10 | 0.558058E+09 | 0.188306E+10 | 0.140410E+09 | 0.174265E+10 | 0.00 | 0.00 |
August | 0.456084E+10 | 0.492126E+09 | 0.224823E+10 | 0.419973E+09 | 0.182826E+10 | 0.00 | 0.00 |
September | 0.413587E+10 | 0.111744E+10 | 0.239273E+10 | 0.889967E+09 | 0.150277E+10 | 0.00 | 0.00 |
October | 0.536863E+10 | 0.233550E+10 | 0.358440E+10 | 0.232197E+10 | 0.126243E+10 | 0.00 | 0.00 |
November | 0.504943E+10 | 0.289346E+10 | 0.373177E+10 | 0.247633E+10 | 0.125544E+10 | 0.00 | 0.00 |
December | 0.489717E+10 | 0.348557E+10 | 0.390951E+10 | 0.275036E+10 | 0.115915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.521776E+11 | 0.238743E+11 | 0.346183E+11 | 0.168602E+11 | 0.177581E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333683E+10 | 0.492126E+09 | 0.180252E+10 | 0.100302E+09 | 0.110227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.536863E+10 | 0.392764E+10 | 0.396613E+10 | 0.276517E+10 | 0.182826E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.953957E+09 | 0.286979E+10 | 0.111525E+10 | 0.517331E+09 | 0.597922E+09 | 0.00 | 0.00 |
February | 0.126836E+10 | 0.215121E+10 | 0.115640E+10 | 0.540686E+09 | 0.615716E+09 | 0.00 | 0.00 |
March | 0.246650E+10 | 0.155619E+10 | 0.188709E+10 | 0.911882E+09 | 0.975209E+09 | 0.00 | 0.00 |
April | 0.305108E+10 | 0.121713E+10 | 0.205446E+10 | 0.940110E+09 | 0.111435E+10 | 0.00 | 0.00 |
May | 0.342720E+10 | 0.856484E+09 | 0.213362E+10 | 0.808342E+09 | 0.132528E+10 | 0.00 | 0.00 |
June | 0.389519E+10 | 0.550169E+09 | 0.217140E+10 | 0.835325E+09 | 0.133608E+10 | 0.00 | 0.00 |
July | 0.391722E+10 | 0.405860E+09 | 0.211640E+10 | 0.784687E+09 | 0.133171E+10 | 0.00 | 0.00 |
August | 0.386724E+10 | 0.355772E+09 | 0.207377E+10 | 0.775505E+09 | 0.129827E+10 | 0.00 | 0.00 |
September | 0.265326E+10 | 0.758432E+09 | 0.163505E+10 | 0.681069E+09 | 0.953985E+09 | 0.00 | 0.00 |
October | 0.207437E+10 | 0.161211E+10 | 0.150519E+10 | 0.781358E+09 | 0.723836E+09 | 0.00 | 0.00 |
November | 0.133807E+10 | 0.203096E+10 | 0.116250E+10 | 0.521790E+09 | 0.640714E+09 | 0.00 | 0.00 |
December | 0.899702E+09 | 0.249119E+10 | 0.991026E+09 | 0.433475E+09 | 0.557551E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298122E+11 | 0.168553E+11 | 0.200022E+11 | 0.853156E+10 | 0.114706E+11 | 0.00 | 0.00 |
Minimum of Months | 0.899702E+09 | 0.355772E+09 | 0.991026E+09 | 0.433475E+09 | 0.557551E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391722E+10 | 0.286979E+10 | 0.217140E+10 | 0.940110E+09 | 0.133608E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132679E+09 | 0.460722E+10 | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.00 | 0.00 |
February | 0.357329E+09 | 0.341187E+10 | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.00 | 0.00 |
March | 0.867508E+09 | 0.241139E+10 | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.00 | 0.00 |
April | 0.154537E+10 | 0.187234E+10 | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.00 | 0.00 |
May | 0.238668E+10 | 0.125595E+10 | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.00 | 0.00 |
June | 0.326719E+10 | 0.764359E+09 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
July | 0.336801E+10 | 0.569266E+09 | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.00 | 0.00 |
August | 0.307205E+10 | 0.473392E+09 | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.00 | 0.00 |
September | 0.171796E+10 | 0.104877E+10 | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.00 | 0.00 |
October | 0.821629E+09 | 0.225381E+10 | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.00 | 0.00 |
November | 0.447676E+09 | 0.292528E+10 | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.00 | 0.00 |
December | 0.145702E+09 | 0.377221E+10 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181298E+11 | 0.253658E+11 | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.132679E+09 | 0.473392E+09 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336801E+10 | 0.460722E+10 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.801976E+09 | 0.275207E+10 | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.00 | 0.00 |
February | 0.123993E+10 | 0.205933E+10 | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.00 | 0.00 |
March | 0.199593E+10 | 0.150158E+10 | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.00 | 0.00 |
April | 0.281037E+10 | 0.119014E+10 | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.00 | 0.00 |
May | 0.352534E+10 | 0.834358E+09 | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.00 | 0.00 |
June | 0.401210E+10 | 0.514335E+09 | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.00 | 0.00 |
July | 0.417239E+10 | 0.386218E+09 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
August | 0.388365E+10 | 0.319627E+09 | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.00 | 0.00 |
September | 0.268632E+10 | 0.683347E+09 | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.00 | 0.00 |
October | 0.192036E+10 | 0.141138E+10 | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.00 | 0.00 |
November | 0.116739E+10 | 0.177779E+10 | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.00 | 0.00 |
December | 0.813851E+09 | 0.226080E+10 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290296E+11 | 0.156910E+11 | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.00 | 0.00 |
Minimum of Months | 0.801976E+09 | 0.319627E+09 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417239E+10 | 0.275207E+10 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462856E+10 | 0.390389E+10 | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.00 | 0.00 |
February | 0.423451E+10 | 0.303881E+10 | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.00 | 0.00 |
March | 0.455851E+10 | 0.236763E+10 | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.00 | 0.00 |
April | 0.365689E+10 | 0.193646E+10 | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.00 | 0.00 |
May | 0.321895E+10 | 0.133446E+10 | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.00 | 0.00 |
June | 0.341423E+10 | 0.816152E+09 | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.00 | 0.00 |
July | 0.374329E+10 | 0.594569E+09 | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.00 | 0.00 |
August | 0.454731E+10 | 0.496787E+09 | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.00 | 0.00 |
September | 0.412898E+10 | 0.107644E+10 | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.535288E+10 | 0.219987E+10 | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.00 | 0.00 |
November | 0.503689E+10 | 0.271901E+10 | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.00 | 0.00 |
December | 0.484699E+10 | 0.333615E+10 | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.513680E+11 | 0.238202E+11 | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321895E+10 | 0.496787E+09 | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.535288E+10 | 0.390389E+10 | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930012E+09 | 0.286964E+10 | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.00 | 0.00 |
February | 0.123216E+10 | 0.218535E+10 | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.00 | 0.00 |
March | 0.239380E+10 | 0.161663E+10 | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.00 | 0.00 |
April | 0.296612E+10 | 0.129333E+10 | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.00 | 0.00 |
May | 0.336460E+10 | 0.906986E+09 | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.00 | 0.00 |
June | 0.385827E+10 | 0.566081E+09 | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.00 | 0.00 |
July | 0.389038E+10 | 0.415099E+09 | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.00 | 0.00 |
August | 0.385355E+10 | 0.351349E+09 | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.00 | 0.00 |
September | 0.265079E+10 | 0.725615E+09 | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.00 | 0.00 |
October | 0.207905E+10 | 0.152468E+10 | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.00 | 0.00 |
November | 0.134838E+10 | 0.193068E+10 | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.00 | 0.00 |
December | 0.892636E+09 | 0.241891E+10 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294597E+11 | 0.168044E+11 | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.892636E+09 | 0.351349E+09 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Maximum of Months | 0.389038E+10 | 0.286964E+10 | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.502788E+10 | -0.427289E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -754987485.3 | 58.98 | 0.00 | 0.00 |
February | 0.455865E+10 | -0.389178E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -666864858.2 | 58.98 | 0.00 | 0.00 |
March | 0.516011E+10 | -0.445089E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -709223482.6 | 58.98 | 0.00 | 0.00 |
April | 0.442694E+10 | -0.374971E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -677229822.6 | 58.98 | 0.00 | 0.00 |
May | 0.439395E+10 | -0.370009E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693856787.4 | 58.98 | 0.00 | 0.00 |
June | 0.405203E+10 | -0.338182E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670215131.0 | 58.98 | 0.00 | 0.00 |
July | 0.371204E+10 | -0.302125E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690789327.4 | 58.98 | 0.00 | 0.00 |
August | 0.402268E+10 | -0.333097E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691709345.6 | 58.98 | 0.00 | 0.00 |
September | 0.381442E+10 | -0.314531E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669104918.0 | 58.98 | 0.00 | 0.00 |
October | 0.421438E+10 | -0.351556E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698821082.5 | 58.98 | 0.00 | 0.00 |
November | 0.445059E+10 | -0.376460E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -685995703.5 | 58.98 | 0.00 | 0.00 |
December | 0.472419E+10 | -0.399239E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -731806886.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.525579E+11 | -0.442173E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.834060E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.371204E+10 | -0.445089E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -754987485.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.516011E+10 | -0.302125E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -666864858.2 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5920.38 | 33.55 | 265.83 | 271.17 | 1650.66 | 25.57 | 177.00 | 250.00 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6934.78 | 33.58 | 230.83 | 246.83 | 1105.41 | 19.24 | 74.17 | 210.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1633.21 | 18.11 | 6.83 | 317.67 | 957.68 | 20.20 | 123.00 | 283.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:20 | 1344.75 | 17.74 | 0.00 | 324.00 | 770.22 | 19.89 | 103.50 | 279.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1215.20 | 17.92 | 0.00 | 357.83 | 681.12 | 20.08 | 88.50 | 310.33 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:00 | 1129.01 | 17.67 | 0.00 | 358.33 | 638.99 | 19.83 | 89.50 | 310.67 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1190.49 | 17.84 | 0.00 | 362.33 | 665.84 | 19.97 | 116.50 | 312.50 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 1455.23 | 18.47 | 0.00 | 349.17 | 798.32 | 20.59 | 173.00 | 311.33 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1557.93 | 18.58 | 6.50 | 307.67 | 877.00 | 20.45 | 120.83 | 268.00 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-08:20 | 2820.72 | 23.84 | 119.17 | 291.83 | 1066.59 | 19.62 | 82.67 | 254.83 |
November | 299.00 | 0.50 | 0.48 | 01-NOV-08:20 | 5827.00 | 34.49 | 285.50 | 272.50 | 1198.31 | 24.23 | 166.50 | 252.67 |
December | 285.17 | 0.49 | 0.48 | 01-DEC-07:00 | 5579.70 | 34.34 | 269.83 | 267.67 | 1592.15 | 26.53 | 179.17 | 245.17 |
Annual Sum or Average | 4071.00 | 0.51 | 2765.65 | 22.91 | 1184.50 | 3727.00 | 959.12 | 21.18 | 1494.33 | 3289.17 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 1129.01 | 17.67 | 0.00 | 246.83 | 638.99 | 19.24 | 74.17 | 210.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6934.78 | 34.49 | 285.50 | 362.33 | 1650.66 | 26.53 | 179.17 | 312.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-08:00 | 1397.54 | 19.11 | 71.83 | 240.67 | 712.40 | 19.97 | 55.00 | 178.00 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1855.92 | 18.92 | 60.17 | 222.50 | 1026.20 | 21.06 | 50.00 | 176.67 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2233.61 | 20.54 | 105.50 | 309.50 | 877.58 | 20.09 | 47.50 | 266.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2150.98 | 19.95 | 93.33 | 324.50 | 1159.31 | 21.17 | 67.17 | 287.17 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2452.55 | 20.31 | 108.50 | 366.17 | 1014.10 | 20.19 | 50.00 | 327.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2476.13 | 20.23 | 110.50 | 368.17 | 1037.98 | 20.90 | 64.00 | 332.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2450.90 | 20.27 | 105.50 | 371.67 | 1038.64 | 20.27 | 51.83 | 330.50 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2246.61 | 20.62 | 102.17 | 350.33 | 1185.56 | 21.91 | 73.50 | 313.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-06:00 | 2074.68 | 19.38 | 67.33 | 302.83 | 1118.49 | 21.63 | 55.33 | 259.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2480.84 | 20.86 | 90.67 | 267.17 | 925.34 | 19.91 | 43.67 | 214.00 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:09 | 1694.77 | 21.16 | 97.00 | 246.83 | 915.18 | 21.99 | 75.50 | 200.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1434.68 | 19.72 | 73.17 | 236.17 | 768.26 | 21.40 | 60.00 | 176.83 |
Annual Sum or Average | 4071.00 | 0.51 | 2122.25 | 20.13 | 1085.67 | 3606.50 | 992.83 | 20.86 | 693.50 | 3061.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1397.54 | 18.92 | 60.17 | 222.50 | 712.40 | 19.91 | 43.67 | 176.67 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2480.84 | 21.16 | 110.50 | 371.67 | 1185.56 | 21.99 | 75.50 | 332.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:50 | 498.44 | 14.33 | 0.00 | 211.17 | 301.36 | 16.73 | 0.00 | 87.17 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 529.36 | 14.53 | 0.00 | 190.00 | 329.03 | 16.88 | 0.00 | 110.67 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 675.39 | 16.35 | 0.00 | 299.33 | 412.09 | 18.56 | 0.00 | 225.83 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 806.72 | 17.26 | 0.00 | 327.83 | 483.64 | 19.37 | 0.67 | 270.50 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 1008.63 | 20.32 | 51.83 | 382.33 | 581.94 | 20.46 | 65.17 | 341.83 |
June | 411.67 | 0.49 | 0.48 | 01-JUN-06:40 | 1097.26 | 21.04 | 66.83 | 385.17 | 645.83 | 23.05 | 176.50 | 363.33 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1105.58 | 20.47 | 53.33 | 384.83 | 615.06 | 21.44 | 145.00 | 348.33 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 986.07 | 18.22 | 0.00 | 359.17 | 575.97 | 20.30 | 52.50 | 324.83 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:30 | 749.92 | 17.07 | 0.00 | 302.50 | 454.78 | 19.17 | 0.00 | 218.83 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 553.98 | 15.06 | 0.00 | 236.33 | 354.52 | 17.45 | 0.00 | 142.67 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 515.74 | 14.64 | 0.00 | 224.00 | 313.81 | 16.98 | 0.00 | 120.33 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 481.59 | 14.41 | 0.00 | 203.00 | 292.19 | 16.85 | 0.00 | 80.83 |
Annual Sum or Average | 4071.00 | 0.52 | 785.86 | 17.33 | 172.00 | 3505.67 | 465.50 | 19.23 | 439.83 | 2635.17 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 481.59 | 14.33 | 0.00 | 190.00 | 292.19 | 16.73 | 0.00 | 80.83 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1105.58 | 21.04 | 66.83 | 385.17 | 645.83 | 23.05 | 176.50 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:39 | 1717.65 | 21.12 | 89.67 | 243.33 | 951.84 | 21.82 | 68.00 | 190.67 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1641.64 | 18.88 | 64.00 | 214.00 | 853.54 | 19.70 | 40.33 | 165.00 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2213.33 | 20.88 | 98.17 | 309.33 | 1177.37 | 21.79 | 72.00 | 265.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2359.32 | 18.66 | 78.67 | 330.50 | 1299.47 | 20.02 | 51.83 | 288.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:00 | 2358.91 | 17.03 | 50.83 | 364.00 | 1004.51 | 18.01 | 0.00 | 325.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2480.11 | 14.70 | 1.67 | 367.50 | 1061.85 | 17.97 | 0.00 | 330.67 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2461.49 | 17.01 | 52.00 | 367.17 | 1039.12 | 18.01 | 0.00 | 327.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-07:30 | 2413.60 | 19.51 | 89.00 | 352.67 | 1053.24 | 18.70 | 7.67 | 318.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:09 | 2166.48 | 21.46 | 90.83 | 305.00 | 1144.91 | 22.22 | 62.67 | 256.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2341.93 | 20.89 | 92.67 | 262.33 | 899.11 | 19.97 | 42.83 | 209.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-09:39 | 1590.18 | 19.46 | 80.83 | 248.00 | 854.44 | 21.74 | 68.33 | 199.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:20 | 1388.01 | 19.35 | 74.17 | 236.50 | 754.13 | 21.33 | 63.33 | 177.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2142.30 | 18.87 | 862.50 | 3600.33 | 1020.79 | 19.92 | 477.00 | 3054.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1388.01 | 14.70 | 1.67 | 214.00 | 754.13 | 17.97 | 0.00 | 165.00 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2480.11 | 21.46 | 98.17 | 367.50 | 1299.47 | 22.22 | 72.00 | 330.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5799.80 | 33.11 | 258.00 | 269.83 | 1555.30 | 23.28 | 103.33 | 248.83 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6826.34 | 33.21 | 229.50 | 245.67 | 1055.84 | 18.03 | 25.83 | 213.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1546.96 | 14.21 | 6.67 | 314.67 | 893.23 | 17.61 | 0.33 | 278.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 1284.74 | 14.00 | 0.00 | 321.00 | 728.96 | 17.50 | 0.00 | 276.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1167.83 | 14.24 | 0.00 | 355.67 | 651.76 | 17.72 | 0.00 | 307.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:10 | 1086.73 | 14.05 | 0.00 | 356.17 | 613.77 | 17.52 | 0.00 | 306.33 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1144.77 | 14.23 | 0.00 | 358.83 | 638.15 | 17.66 | 0.00 | 308.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:19 | 1395.04 | 14.84 | 0.00 | 347.17 | 759.70 | 18.27 | 0.00 | 307.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1484.19 | 14.97 | 6.50 | 304.83 | 825.43 | 18.10 | 0.00 | 265.17 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-10:39 | 2717.02 | 21.23 | 117.33 | 290.17 | 984.16 | 16.84 | 2.00 | 250.83 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:20 | 5713.98 | 34.08 | 281.17 | 271.67 | 1111.17 | 21.75 | 82.17 | 249.33 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5407.84 | 32.28 | 249.33 | 263.67 | 1495.07 | 24.33 | 116.17 | 242.67 |
Annual Sum or Average | 4071.00 | 0.51 | 2684.52 | 20.10 | 1148.50 | 3699.33 | 904.89 | 18.86 | 329.83 | 3254.83 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1086.73 | 14.00 | 0.00 | 245.67 | 613.77 | 16.84 | 0.00 | 213.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6826.34 | 34.08 | 281.17 | 358.83 | 1555.30 | 24.33 | 116.17 | 308.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-09:09 | 1358.32 | 18.61 | 71.33 | 238.67 | 681.94 | 19.72 | 48.67 | 171.33 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1806.26 | 18.42 | 60.17 | 219.17 | 985.15 | 20.85 | 48.50 | 173.33 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2182.55 | 20.07 | 105.33 | 307.50 | 836.12 | 19.88 | 47.33 | 262.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2090.24 | 19.48 | 93.00 | 322.50 | 1111.38 | 20.99 | 67.17 | 283.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-06:00 | 2381.81 | 19.85 | 108.33 | 363.17 | 963.64 | 20.02 | 50.17 | 323.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2412.05 | 19.78 | 110.33 | 365.50 | 988.18 | 20.74 | 64.00 | 329.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2383.04 | 19.82 | 105.33 | 368.83 | 987.46 | 20.10 | 51.83 | 328.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2175.50 | 20.16 | 102.17 | 348.67 | 1136.05 | 21.73 | 73.50 | 309.17 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2015.65 | 18.88 | 67.33 | 301.00 | 1070.50 | 21.43 | 55.33 | 252.67 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2427.12 | 20.38 | 90.50 | 264.50 | 880.94 | 19.70 | 42.67 | 209.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-08:09 | 1652.64 | 20.69 | 97.00 | 243.83 | 881.95 | 21.77 | 72.83 | 195.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1394.67 | 19.20 | 73.00 | 233.33 | 736.12 | 21.16 | 57.50 | 172.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2064.99 | 19.66 | 1083.83 | 3576.67 | 948.66 | 20.66 | 679.50 | 3008.67 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1358.32 | 18.42 | 60.17 | 219.17 | 681.94 | 19.70 | 42.67 | 171.33 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2427.12 | 20.69 | 110.33 | 368.83 | 1136.05 | 21.77 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 481.03 | 10.45 | 0.00 | 205.33 | 291.98 | 14.18 | 0.00 | 78.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 511.45 | 10.76 | 0.00 | 184.33 | 319.62 | 14.45 | 0.00 | 106.00 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:09 | 652.25 | 12.84 | 0.00 | 296.17 | 399.71 | 16.41 | 0.00 | 219.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 779.27 | 13.79 | 0.00 | 325.50 | 468.71 | 17.31 | 0.00 | 265.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 972.34 | 17.27 | 51.83 | 379.83 | 571.59 | 20.44 | 52.50 | 348.00 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:40 | 1057.03 | 18.06 | 65.67 | 384.67 | 622.27 | 21.21 | 68.17 | 361.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1061.59 | 16.15 | 27.33 | 383.00 | 601.99 | 20.57 | 54.00 | 350.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 950.10 | 14.78 | 0.00 | 357.83 | 555.66 | 18.24 | 0.00 | 320.33 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 723.09 | 13.75 | 0.00 | 299.33 | 440.23 | 17.22 | 0.00 | 209.83 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 535.53 | 11.50 | 0.00 | 230.33 | 345.08 | 15.24 | 0.00 | 134.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 497.27 | 10.88 | 0.00 | 218.67 | 303.86 | 14.53 | 0.00 | 108.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 464.14 | 10.49 | 0.00 | 197.67 | 282.77 | 14.27 | 0.00 | 68.50 |
Annual Sum or Average | 4071.00 | 0.52 | 757.50 | 13.77 | 144.83 | 3462.67 | 451.98 | 17.38 | 174.67 | 2570.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 464.14 | 10.45 | 0.00 | 184.33 | 282.77 | 14.18 | 0.00 | 68.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1061.59 | 18.06 | 65.67 | 384.67 | 622.27 | 21.21 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:50 | 1675.90 | 20.73 | 89.17 | 240.67 | 918.99 | 21.71 | 68.00 | 185.17 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1591.15 | 18.45 | 63.83 | 211.33 | 813.80 | 19.57 | 40.00 | 161.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2087.83 | 18.80 | 77.50 | 306.50 | 1129.42 | 21.66 | 72.17 | 263.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2298.56 | 18.19 | 78.50 | 327.67 | 1251.60 | 19.86 | 51.83 | 285.00 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:09 | 2291.09 | 16.52 | 50.83 | 361.67 | 957.87 | 17.82 | 0.00 | 322.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2393.35 | 14.16 | 1.67 | 363.83 | 1014.43 | 17.77 | 0.00 | 327.50 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2376.73 | 16.50 | 52.00 | 364.83 | 991.75 | 17.81 | 0.00 | 323.67 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:40 | 2340.46 | 18.88 | 86.50 | 351.00 | 996.68 | 18.53 | 7.83 | 313.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:20 | 2062.88 | 19.38 | 75.50 | 301.00 | 1097.64 | 22.09 | 62.67 | 252.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2289.71 | 20.47 | 92.50 | 260.00 | 856.37 | 19.84 | 42.83 | 206.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-09:50 | 1545.84 | 19.03 | 80.83 | 245.67 | 820.14 | 21.63 | 68.00 | 196.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:30 | 1349.25 | 18.93 | 73.67 | 233.33 | 723.46 | 21.22 | 63.00 | 173.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2071.25 | 18.13 | 822.50 | 3567.50 | 976.51 | 19.77 | 476.33 | 3009.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1349.25 | 14.16 | 1.67 | 211.33 | 723.46 | 17.77 | 0.00 | 161.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2393.35 | 20.73 | 92.50 | 364.83 | 1251.60 | 22.09 | 72.17 | 327.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5799.76 | 33.11 | 258.00 | 269.83 | 1555.23 | 23.28 | 103.33 | 248.83 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6826.27 | 33.21 | 229.50 | 245.67 | 1055.77 | 18.03 | 25.83 | 213.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1546.87 | 14.21 | 6.67 | 314.67 | 893.17 | 17.61 | 0.50 | 278.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 1284.67 | 14.00 | 0.00 | 321.00 | 728.90 | 17.51 | 0.00 | 276.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1167.76 | 14.24 | 0.00 | 355.67 | 651.71 | 17.72 | 0.00 | 307.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:10 | 1086.67 | 14.05 | 0.00 | 356.17 | 613.72 | 17.52 | 0.00 | 306.33 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1144.71 | 14.23 | 0.00 | 358.83 | 638.10 | 17.66 | 0.00 | 308.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:19 | 1394.95 | 14.84 | 0.00 | 347.17 | 759.64 | 18.27 | 0.00 | 307.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1484.10 | 14.97 | 6.50 | 304.67 | 825.37 | 18.11 | 0.00 | 265.17 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-10:39 | 2716.95 | 21.23 | 117.33 | 290.17 | 984.10 | 16.84 | 2.00 | 250.83 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:20 | 5713.93 | 34.08 | 281.17 | 271.67 | 1111.09 | 21.75 | 82.17 | 249.33 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5407.81 | 32.29 | 249.33 | 263.67 | 1495.00 | 24.33 | 116.17 | 242.67 |
Annual Sum or Average | 4071.00 | 0.51 | 2684.45 | 20.11 | 1148.50 | 3699.17 | 904.83 | 18.86 | 330.00 | 3254.83 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1086.67 | 14.00 | 0.00 | 245.67 | 613.72 | 16.84 | 0.00 | 213.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6826.27 | 34.08 | 281.17 | 358.83 | 1555.23 | 24.33 | 116.17 | 308.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-09:09 | 1358.29 | 18.61 | 71.33 | 238.67 | 681.91 | 19.73 | 48.67 | 171.33 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1806.24 | 18.42 | 60.17 | 219.17 | 985.12 | 20.85 | 48.50 | 173.33 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2182.51 | 20.07 | 105.33 | 307.50 | 836.07 | 19.88 | 47.33 | 262.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2090.19 | 19.48 | 93.00 | 322.50 | 1111.33 | 20.99 | 67.17 | 283.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-06:00 | 2381.75 | 19.85 | 108.33 | 363.17 | 963.58 | 20.02 | 50.17 | 323.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2411.99 | 19.78 | 110.33 | 365.50 | 988.12 | 20.74 | 64.00 | 329.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2382.98 | 19.82 | 105.33 | 368.83 | 987.40 | 20.10 | 51.83 | 328.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2175.44 | 20.16 | 102.17 | 348.67 | 1135.99 | 21.73 | 73.50 | 309.17 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2015.61 | 18.88 | 67.33 | 301.00 | 1070.45 | 21.43 | 55.33 | 252.67 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2427.10 | 20.38 | 90.50 | 264.50 | 880.91 | 19.70 | 42.67 | 209.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-08:09 | 1652.61 | 20.69 | 97.00 | 244.00 | 881.91 | 21.77 | 72.83 | 195.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1394.64 | 19.20 | 73.00 | 233.33 | 736.09 | 21.16 | 57.50 | 172.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2064.95 | 19.66 | 1083.83 | 3576.83 | 948.62 | 20.66 | 679.50 | 3008.67 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1358.29 | 18.42 | 60.17 | 219.17 | 681.91 | 19.70 | 42.67 | 171.33 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2427.10 | 20.69 | 110.33 | 368.83 | 1135.99 | 21.77 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 481.02 | 10.45 | 0.00 | 205.33 | 291.96 | 14.18 | 0.00 | 78.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 511.43 | 10.76 | 0.00 | 184.33 | 319.60 | 14.45 | 0.00 | 106.00 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:09 | 652.23 | 12.84 | 0.00 | 296.17 | 399.69 | 16.41 | 0.00 | 219.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 779.24 | 13.79 | 0.00 | 325.50 | 468.68 | 17.31 | 0.00 | 265.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 972.30 | 17.27 | 51.83 | 379.83 | 571.55 | 20.44 | 52.50 | 348.00 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:40 | 1056.99 | 18.07 | 65.67 | 384.67 | 622.23 | 21.22 | 68.17 | 361.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1061.55 | 16.15 | 27.33 | 383.00 | 601.95 | 20.57 | 54.00 | 350.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 950.06 | 14.78 | 0.00 | 357.83 | 555.62 | 18.25 | 0.00 | 320.33 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 723.07 | 13.76 | 0.00 | 299.33 | 440.20 | 17.22 | 0.00 | 209.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 535.52 | 11.50 | 0.00 | 230.17 | 345.06 | 15.24 | 0.00 | 134.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 497.25 | 10.88 | 0.00 | 218.67 | 303.84 | 14.54 | 0.00 | 108.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 464.12 | 10.49 | 0.00 | 197.67 | 282.75 | 14.27 | 0.00 | 68.50 |
Annual Sum or Average | 4071.00 | 0.52 | 757.47 | 13.78 | 144.83 | 3462.50 | 451.95 | 17.38 | 174.67 | 2570.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 464.12 | 10.45 | 0.00 | 184.33 | 282.75 | 14.18 | 0.00 | 68.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1061.55 | 18.07 | 65.67 | 384.67 | 622.23 | 21.22 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:50 | 1675.87 | 20.73 | 89.17 | 240.67 | 918.95 | 21.72 | 68.00 | 185.17 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1591.12 | 18.46 | 63.83 | 211.33 | 813.76 | 19.57 | 40.00 | 161.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2087.79 | 18.80 | 77.50 | 306.50 | 1129.37 | 21.66 | 72.17 | 263.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2298.51 | 18.19 | 78.50 | 327.67 | 1251.55 | 19.86 | 51.83 | 285.00 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:09 | 2291.03 | 16.52 | 50.83 | 361.67 | 957.81 | 17.82 | 0.00 | 322.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2393.29 | 14.16 | 1.67 | 363.83 | 1014.37 | 17.77 | 0.00 | 327.50 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2376.67 | 16.51 | 52.00 | 364.83 | 991.69 | 17.81 | 0.00 | 323.67 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:40 | 2340.39 | 18.88 | 86.50 | 351.00 | 996.61 | 18.53 | 7.83 | 313.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:20 | 2062.83 | 19.38 | 75.50 | 301.00 | 1097.58 | 22.09 | 62.67 | 252.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2289.69 | 20.47 | 92.50 | 260.00 | 856.33 | 19.84 | 42.83 | 206.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-09:50 | 1545.81 | 19.04 | 80.83 | 245.67 | 820.10 | 21.63 | 68.00 | 196.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:30 | 1349.22 | 18.93 | 73.67 | 233.33 | 723.43 | 21.22 | 63.00 | 173.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2071.20 | 18.13 | 822.50 | 3567.50 | 976.46 | 19.77 | 476.33 | 3009.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1349.22 | 14.16 | 1.67 | 211.33 | 723.43 | 17.77 | 0.00 | 161.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2393.29 | 20.73 | 92.50 | 364.83 | 1251.55 | 22.09 | 72.17 | 327.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.844609E+09 | 20533.99 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152823E+09 | 20533.99 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5453481.18 | 20290.39 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.844609E+09 | 20533.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.492399E+10 | 10351.35 | 19-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322025E+10 | 10331.20 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121255E+10 | 10311.92 | 24-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.657855E+09 | 10290.68 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176631E+09 | 10247.15 | 11-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25506973.59 | 9223.00 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24106911.01 | 5336.71 | 29-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.565262E+09 | 10307.55 | 24-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110646E+10 | 10302.83 | 06-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212899E+10 | 10306.59 | 07-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.492399E+10 | 10351.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208428E+10 | 8561.83 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113828E+10 | 8561.83 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109259E+09 | 8561.83 | 23-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14501303.39 | 8561.83 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9762975.74 | 4888.20 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65061850.73 | 8561.83 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.624749E+09 | 8561.83 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208428E+10 | 8561.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.406360E+10 | 8761.43 | 18-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241962E+10 | 8743.43 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418323E+09 | 8722.81 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83720618.06 | 8713.16 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18985915.95 | 8676.87 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256542E+09 | 8696.41 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158412E+10 | 8714.46 | 07-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406360E+10 | 8761.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216519E+10 | 8635.48 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123311E+10 | 8635.48 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131724E+09 | 8124.49 | 23-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19130778.77 | 8635.48 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7981757.89 | 4889.05 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93797080.00 | 8635.48 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.746996E+09 | 8635.48 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216519E+10 | 8635.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.374432E+10 | 21599.78 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173215E+10 | 21599.78 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4641964.76 | 8396.22 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1717251.00 | 3805.89 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65845242.12 | 21599.78 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121946E+10 | 21599.78 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.676813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.374432E+10 | 21599.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232129E+10 | 11363.08 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130608E+10 | 11328.41 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129237E+09 | 11251.85 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24083089.73 | 11198.95 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56879736.12 | 11293.11 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214994E+09 | 11288.59 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.930637E+09 | 11312.86 | 26-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232129E+10 | 11363.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196118E+10 | 9032.79 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103023E+10 | 9032.79 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82459878.45 | 8210.60 | 22-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10467196.19 | 9032.79 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46085216.90 | 8091.06 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194703E+09 | 9032.79 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.832218E+09 | 9032.79 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196118E+10 | 9032.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.386383E+10 | 9562.74 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215583E+10 | 9559.15 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218935E+09 | 9517.04 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31035113.86 | 9424.80 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85187030.05 | 9504.06 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504007E+09 | 9516.25 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193594E+10 | 9537.62 | 28-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.386383E+10 | 9562.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217437E+10 | 9107.38 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119804E+10 | 9107.38 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114093E+09 | 7943.41 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15793793.43 | 9107.38 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45200236.50 | 7975.48 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270297E+09 | 9107.38 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105213E+10 | 9107.38 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.217437E+10 | 9107.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.748951E+10 | 34402.99 | 18-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392708E+10 | 34278.66 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273625E+09 | 33986.16 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20843162.66 | 27720.93 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161424E+09 | 34105.22 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.905388E+09 | 34096.20 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417806E+10 | 34227.54 | 26-DEC-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.748951E+10 | 34402.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376940E+10 | 12958.73 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226825E+10 | 13112.01 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403653E+09 | 12913.19 | 22-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114270E+09 | 12857.65 | 27-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3647737.75 | 2536.00 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251771E+09 | 12895.39 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.692254E+09 | 12966.48 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191930E+10 | 12953.88 | 23-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.942254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.376940E+10 | 13112.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316396E+10 | 10728.58 | 19-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178386E+10 | 10754.94 | 08-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252604E+09 | 10664.81 | 22-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46899236.93 | 10615.73 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190800E+09 | 10702.47 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.556078E+09 | 10676.76 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166939E+10 | 10751.40 | 23-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316396E+10 | 10754.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.579116E+10 | 11168.37 | 18-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342549E+10 | 11276.34 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.608505E+09 | 11122.59 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136217E+09 | 11117.11 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1288137.91 | 1734.18 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.369835E+09 | 11166.40 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126804E+10 | 11151.10 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337711E+10 | 11141.79 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579116E+10 | 11276.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.336748E+10 | 11446.07 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197992E+10 | 11446.07 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.336713E+09 | 11446.07 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76292438.65 | 11446.07 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1433470.86 | 1083.95 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1019.06 | 6.79 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207452E+09 | 11446.07 | 26-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714693E+09 | 11446.07 | 13-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194271E+10 | 11446.07 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336748E+10 | 11446.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505212E+10 | 15005.94 | 27-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249669E+10 | 17523.74 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233027E+09 | 4501.30 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69219007.26 | 5171.47 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30171675.05 | 4272.66 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.529664E+09 | 9899.98 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130174E+10 | 13330.67 | 18-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.971264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505212E+10 | 17523.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.504793E+10 | 15418.33 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254973E+10 | 17648.55 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284565E+09 | 4849.05 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85293629.27 | 5556.23 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45155007.50 | 4916.66 | 26-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659973E+09 | 10366.27 | 22-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144219E+10 | 13727.94 | 18-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504793E+10 | 17648.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.532636E+10 | 17457.82 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273877E+10 | 18622.89 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395825E+09 | 5876.68 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125818E+09 | 7150.03 | 06-APR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91542303.23 | 6263.72 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.845117E+09 | 12643.86 | 21-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165938E+10 | 14403.91 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.532636E+10 | 18622.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.160624E+10 | 0.975016E+09 | 16734.27 | 19-JAN-16:00 | 8467.85 | 0.00 |
February | 0.00 | 0.00 | 0.382490E+10 | 0.304924E+10 | 23173.08 | 28-FEB-15:00 | 23173.08 | 0.00 |
March | 0.00 | 0.00 | 0.117721E+11 | 0.877968E+10 | 39137.90 | 30-MAR-15:30 | 39137.90 | 0.00 |
April | 0.00 | 0.00 | 0.206191E+11 | 0.163606E+11 | 45038.20 | 17-APR-15:00 | 45038.20 | 0.00 |
May | 0.00 | 0.00 | 0.405588E+11 | 0.296162E+11 | 60805.94 | 30-MAY-15:10 | 47190.84 | 0.00 |
June | 0.00 | 0.00 | 0.653224E+11 | 0.471917E+11 | 76042.37 | 28-JUN-12:05 | 50807.95 | 0.00 |
July | 0.00 | 0.00 | 0.764168E+11 | 0.520431E+11 | 84006.14 | 07-JUL-12:05 | 55900.17 | 0.00 |
August | 0.00 | 0.00 | 0.877875E+11 | 0.583897E+11 | 93326.13 | 21-AUG-06:03 | 62742.36 | 0.00 |
September | 0.00 | 0.00 | 0.538819E+11 | 0.383492E+11 | 79589.97 | 06-SEP-12:03 | 53461.91 | 0.00 |
October | 0.00 | 0.00 | 0.229889E+11 | 0.164155E+11 | 59619.88 | 10-OCT-15:50 | 48062.70 | 0.00 |
November | 0.00 | 0.00 | 0.846494E+10 | 0.619500E+10 | 27530.72 | 02-NOV-13:00 | 19146.64 | 0.00 |
December | 0.00 | 0.00 | 0.295990E+10 | 0.187175E+10 | 24950.54 | 12-DEC-14:00 | 17123.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.396204E+12 | 0.279237E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.160624E+10 | 0.975016E+09 | 16734.27 | 8467.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.877875E+11 | 0.583897E+11 | 93326.13 | 62742.36 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.157909E+10 | 0.964801E+09 | 17517.50 | 19-JAN-16:00 | 9422.44 | 0.00 |
February | 0.00 | 0.00 | 0.392518E+10 | 0.319036E+10 | 24442.04 | 28-FEB-15:05 | 24442.04 | 0.00 |
March | 0.00 | 0.00 | 0.118183E+11 | 0.901257E+10 | 43704.74 | 30-MAR-15:20 | 43704.74 | 0.00 |
April | 0.00 | 0.00 | 0.214021E+11 | 0.173949E+11 | 50173.12 | 17-APR-15:50 | 50173.12 | 0.00 |
May | 0.00 | 0.00 | 0.412137E+11 | 0.307299E+11 | 63123.34 | 30-MAY-14:05 | 50357.92 | 0.00 |
June | 0.00 | 0.00 | 0.637113E+11 | 0.460630E+11 | 86131.86 | 26-JUN-06:03 | 63351.49 | 0.00 |
July | 0.00 | 0.00 | 0.736730E+11 | 0.498356E+11 | 77939.66 | 07-JUL-12:02 | 53776.29 | 0.00 |
August | 0.00 | 0.00 | 0.823613E+11 | 0.539250E+11 | 95440.43 | 21-AUG-06:03 | 60020.95 | 0.00 |
September | 0.00 | 0.00 | 0.485905E+11 | 0.338448E+11 | 75806.25 | 06-SEP-14:05 | 53308.00 | 0.00 |
October | 0.00 | 0.00 | 0.205585E+11 | 0.144195E+11 | 58457.18 | 11-OCT-14:05 | 42895.71 | 0.00 |
November | 0.00 | 0.00 | 0.791679E+10 | 0.572441E+10 | 25433.81 | 02-NOV-14:05 | 18679.16 | 0.00 |
December | 0.00 | 0.00 | 0.292659E+10 | 0.189095E+10 | 24394.91 | 12-DEC-14:00 | 17037.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.379676E+12 | 0.266996E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.157909E+10 | 0.964801E+09 | 17517.50 | 9422.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.823613E+11 | 0.539250E+11 | 95440.43 | 63351.49 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.163806E+10 | 0.990016E+09 | 16877.41 | 19-JAN-16:00 | 8525.20 | 0.00 |
February | 0.00 | 0.00 | 0.410192E+10 | 0.328586E+10 | 23717.82 | 28-FEB-15:30 | 23717.82 | 0.00 |
March | 0.00 | 0.00 | 0.125717E+11 | 0.948948E+10 | 50234.16 | 30-MAR-15:20 | 50234.16 | 0.00 |
April | 0.00 | 0.00 | 0.234290E+11 | 0.189883E+11 | 56016.20 | 17-APR-14:50 | 56016.20 | 0.00 |
May | 0.00 | 0.00 | 0.451072E+11 | 0.340931E+11 | 71943.47 | 30-MAY-15:00 | 58530.80 | 0.00 |
June | 0.00 | 0.00 | 0.692239E+11 | 0.510644E+11 | 87667.92 | 26-JUN-06:03 | 64996.93 | 0.00 |
July | 0.00 | 0.00 | 0.795916E+11 | 0.553404E+11 | 86418.64 | 07-JUL-16:00 | 68197.38 | 0.00 |
August | 0.00 | 0.00 | 0.880313E+11 | 0.591468E+11 | 97220.33 | 19-AUG-05:03 | 59292.76 | 0.00 |
September | 0.00 | 0.00 | 0.506847E+11 | 0.353713E+11 | 82333.20 | 06-SEP-14:00 | 60014.10 | 0.00 |
October | 0.00 | 0.00 | 0.210120E+11 | 0.145163E+11 | 62024.86 | 11-OCT-14:00 | 46352.26 | 0.00 |
November | 0.00 | 0.00 | 0.811863E+10 | 0.575148E+10 | 27761.25 | 05-NOV-13:53 | 20102.91 | 0.00 |
December | 0.00 | 0.00 | 0.300592E+10 | 0.191253E+10 | 25982.97 | 12-DEC-14:00 | 17764.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.406516E+12 | 0.289950E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.163806E+10 | 0.990016E+09 | 16877.41 | 8525.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.880313E+11 | 0.591468E+11 | 97220.33 | 68197.38 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1748.71 | 6087.40 | 30-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1762.32 | 6098.06 | 01-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1818.18 | 5984.21 | 02-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1599.50 | 5656.74 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1536.87 | 5271.20 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1461.88 | 4839.10 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1280.73 | 4529.43 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1401.45 | 4500.63 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1366.92 | 4793.76 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1466.33 | 5234.67 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1606.56 | 5638.28 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1642.20 | 5936.97 | 27-DEC-12:08 |
Annual Sum or Average | 0.00 | 1556.49 | ||||
Minimum of Months | 0.00 | 0.00 | 1280.73 | 4500.63 | ||
Maximum of Months | 0.00 | 0.00 | 1818.18 | 6098.06 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.101844E+10 | 0.28 | 2107.75 | 02-JAN-06:11 | 0.76 |
February | 0.937589E+09 | 0.29 | 2107.75 | 06-FEB-07:01 | 0.77 |
March | 0.114062E+10 | 0.30 | 1744.05 | 30-MAR-16:00 | 0.69 |
April | 0.122946E+10 | 0.30 | 2098.59 | 17-APR-15:50 | 0.76 |
May | 0.168648E+10 | 0.33 | 2999.05 | 30-MAY-15:10 | 0.92 |
June | 0.256245E+10 | 0.41 | 5879.40 | 26-JUN-06:03 | 1.38 |
July | 0.290218E+10 | 0.42 | 8006.35 | 17-JUL-06:03 | 1.68 |
August | 0.336673E+10 | 0.46 | 9251.28 | 07-AUG-06:03 | 1.84 |
September | 0.236101E+10 | 0.38 | 6921.95 | 05-SEP-06:03 | 1.53 |
October | 0.152734E+10 | 0.32 | 3206.76 | 11-OCT-16:00 | 0.96 |
November | 0.106266E+10 | 0.29 | 1588.76 | 06-NOV-16:10 | 0.66 |
December | 0.966121E+09 | 0.28 | 1280.67 | 01-DEC-06:01 | 0.60 |
Annual Sum or Average | 0.207611E+11 | 0.34 | |||
Minimum of Months | 0.937589E+09 | 0.28 | 1280.67 | 0.60 | |
Maximum of Months | 0.336673E+10 | 0.46 | 9251.28 | 1.84 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102720E+10 | 0.29 | 2123.24 | 02-JAN-06:11 | 0.79 |
February | 0.956417E+09 | 0.30 | 2123.24 | 02-FEB-07:01 | 0.79 |
March | 0.113766E+10 | 0.31 | 2289.09 | 30-MAR-16:00 | 0.82 |
April | 0.127090E+10 | 0.31 | 2602.81 | 17-APR-15:50 | 0.88 |
May | 0.175845E+10 | 0.35 | 3567.71 | 30-MAY-14:05 | 1.05 |
June | 0.244745E+10 | 0.41 | 8768.72 | 26-JUN-06:03 | 1.84 |
July | 0.266684E+10 | 0.42 | 8768.72 | 17-JUL-06:03 | 1.85 |
August | 0.292317E+10 | 0.45 | 8768.72 | 07-AUG-06:03 | 1.84 |
September | 0.193275E+10 | 0.36 | 4072.68 | 06-SEP-14:05 | 1.14 |
October | 0.130262E+10 | 0.31 | 2884.70 | 11-OCT-14:05 | 0.93 |
November | 0.989600E+09 | 0.29 | 2123.24 | 22-NOV-07:01 | 0.79 |
December | 0.960318E+09 | 0.28 | 2123.24 | 01-DEC-07:01 | 0.79 |
Annual Sum or Average | 0.193734E+11 | 0.34 | |||
Minimum of Months | 0.956417E+09 | 0.28 | 2123.24 | 0.79 | |
Maximum of Months | 0.292317E+10 | 0.45 | 8768.72 | 1.85 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131992E+10 | 0.36 | 2157.51 | 02-JAN-06:11 | 0.73 |
February | 0.113463E+10 | 0.35 | 2157.51 | 01-FEB-07:01 | 0.73 |
March | 0.122903E+10 | 0.33 | 2527.71 | 30-MAR-16:00 | 0.79 |
April | 0.134346E+10 | 0.32 | 2855.39 | 17-APR-15:40 | 0.84 |
May | 0.183614E+10 | 0.35 | 3683.28 | 30-MAY-15:00 | 0.97 |
June | 0.251366E+10 | 0.40 | 7569.54 | 26-JUN-06:03 | 1.51 |
July | 0.273794E+10 | 0.41 | 7318.33 | 17-JUL-06:03 | 1.48 |
August | 0.294690E+10 | 0.43 | 6796.36 | 07-AUG-06:03 | 1.41 |
September | 0.186991E+10 | 0.36 | 3991.69 | 07-SEP-15:30 | 1.02 |
October | 0.130035E+10 | 0.31 | 2699.28 | 11-OCT-15:20 | 0.81 |
November | 0.107776E+10 | 0.31 | 2157.51 | 21-NOV-06:01 | 0.73 |
December | 0.115374E+10 | 0.32 | 2157.51 | 01-DEC-06:01 | 0.73 |
Annual Sum or Average | 0.204635E+11 | 0.35 | |||
Minimum of Months | 0.107776E+10 | 0.31 | 2157.51 | 0.73 | |
Maximum of Months | 0.294690E+10 | 0.43 | 7569.54 | 1.51 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.74 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.93 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.51 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.14 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.65 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.76 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.71 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.26 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.01 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.11 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.09 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.13 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.93 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.74 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.95 | 56.95 | 1748.71 | 6087.40 | 30-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.39 | 56.39 | 1762.32 | 6098.06 | 01-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.05 | 57.05 | 1818.18 | 5984.21 | 02-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.67 | 56.67 | 1599.50 | 5656.74 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.06 | 58.06 | 1536.87 | 5271.20 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.79 | 57.79 | 1461.88 | 4839.10 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.65 | 57.65 | 1280.73 | 4529.43 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.53 | 57.53 | 1401.45 | 4500.63 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.31 | 57.31 | 1366.92 | 4793.76 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.30 | 56.30 | 1466.33 | 5234.67 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.97 | 56.97 | 1606.56 | 5638.28 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.47 | 57.47 | 1642.20 | 5936.97 | 27-DEC-12:08 |
Annual Sum or Average | 0.00 | 1556.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.30 | 56.30 | 1280.73 | 4500.63 | ||
Maximum of Months | 0.00 | 0.00 | 58.06 | 58.06 | 1818.18 | 6098.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.155116E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.100833E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.590655E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.698536E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114462E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.185169E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216998E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.247048E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150002E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.752570E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.468210E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.679928E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.148862E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.468210E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.247048E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154958E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.938154E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.458421E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.650312E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.114855E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.179614E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.207419E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.228787E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133457E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.639431E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.421034E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.766434E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140647E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.421034E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.228787E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.253238E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.155744E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.620826E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.740485E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.125637E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.194770E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.224136E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.244221E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.138828E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.749589E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.725561E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.150002E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.177022E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.620826E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.253238E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.101844E+10 | 0.160624E+10 | 0.191338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.937589E+09 | 0.382490E+10 | 0.106608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114062E+10 | 0.117721E+11 | 0.210488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122946E+10 | 0.206191E+11 | 0.844427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168648E+10 | 0.405588E+11 | 0.176631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256245E+10 | 0.653224E+11 | 25506973.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.290218E+10 | 0.764168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.336673E+10 | 0.877875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236101E+10 | 0.538819E+11 | 24106911.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152734E+10 | 0.229889E+11 | 0.632165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106266E+10 | 0.846494E+10 | 0.205152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966121E+09 | 0.295990E+10 | 0.639205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207611E+11 | 0.396204E+12 | 0.420459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.937589E+09 | 0.160624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336673E+10 | 0.877875E+11 | 0.191338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.102720E+10 | 0.157909E+10 | 0.191129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.956417E+09 | 0.392518E+10 | 0.997205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113766E+10 | 0.118183E+11 | 0.833932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127090E+10 | 0.214021E+11 | 0.166673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175845E+10 | 0.412137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.244745E+10 | 0.637113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.266684E+10 | 0.736730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292317E+10 | 0.823613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193275E+10 | 0.485905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130262E+10 | 0.205585E+11 | 0.280224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.989600E+09 | 0.791679E+10 | 0.190982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.960318E+09 | 0.292659E+10 | 0.741257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193734E+11 | 0.379676E+12 | 0.396882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.956417E+09 | 0.157909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.292317E+10 | 0.823613E+11 | 0.191129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131992E+10 | 0.163806E+10 | 0.289079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113463E+10 | 0.410192E+10 | 0.161234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122903E+10 | 0.125717E+11 | 0.227093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134346E+10 | 0.234290E+11 | 0.520340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183614E+10 | 0.451072E+11 | 6369346.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.251366E+10 | 0.692239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.273794E+10 | 0.795916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.294690E+10 | 0.880313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186991E+10 | 0.506847E+11 | 1019.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130035E+10 | 0.210120E+11 | 0.127282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107776E+10 | 0.811863E+10 | 0.498157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115374E+10 | 0.300592E+10 | 0.147459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204635E+11 | 0.406516E+12 | 0.688292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107776E+10 | 0.163806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.294690E+10 | 0.880313E+11 | 0.289079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.101844E+10 | 0.00 | 0.00 | 0.00 | 0.411461E+09 | 0.140817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.937589E+09 | 0.00 | 0.00 | 0.00 | 0.981668E+09 | 0.816409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114062E+10 | 0.00 | 0.00 | 0.00 | 0.289408E+10 | 0.187186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122946E+10 | 0.00 | 0.00 | 0.00 | 0.498069E+10 | 0.775208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168648E+10 | 0.00 | 0.00 | 0.00 | 0.958307E+10 | 0.176631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256245E+10 | 0.00 | 0.00 | 0.00 | 0.159290E+11 | 25506973.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.290218E+10 | 0.00 | 0.00 | 0.00 | 0.187976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.336673E+10 | 0.00 | 0.00 | 0.00 | 0.213381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236101E+10 | 0.00 | 0.00 | 0.00 | 0.126151E+11 | 24106911.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152734E+10 | 0.00 | 0.00 | 0.00 | 0.539637E+10 | 0.601993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106266E+10 | 0.00 | 0.00 | 0.00 | 0.209758E+10 | 0.152186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966121E+09 | 0.00 | 0.00 | 0.00 | 0.742856E+09 | 0.509031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207611E+11 | 0.00 | 0.00 | 0.00 | 0.957675E+11 | 0.323332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.937589E+09 | 0.00 | 0.00 | 0.00 | 0.411461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336673E+10 | 0.00 | 0.00 | 0.00 | 0.213381E+11 | 0.140817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.102720E+10 | 0.00 | 0.00 | 0.00 | 0.403587E+09 | 0.140650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.956417E+09 | 0.00 | 0.00 | 0.00 | 0.100280E+10 | 0.742232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113766E+10 | 0.00 | 0.00 | 0.00 | 0.289718E+10 | 0.549367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127090E+10 | 0.00 | 0.00 | 0.00 | 0.515084E+10 | 81379193.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175845E+10 | 0.00 | 0.00 | 0.00 | 0.972707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.244745E+10 | 0.00 | 0.00 | 0.00 | 0.155140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.266684E+10 | 0.00 | 0.00 | 0.00 | 0.180750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292317E+10 | 0.00 | 0.00 | 0.00 | 0.199556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193275E+10 | 0.00 | 0.00 | 0.00 | 0.114129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130262E+10 | 0.00 | 0.00 | 0.00 | 0.485661E+10 | 0.235069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.989600E+09 | 0.00 | 0.00 | 0.00 | 0.197089E+10 | 0.124985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.960318E+09 | 0.00 | 0.00 | 0.00 | 0.733641E+09 | 0.597039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193734E+11 | 0.00 | 0.00 | 0.00 | 0.917001E+11 | 0.295734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.956417E+09 | 0.00 | 0.00 | 0.00 | 0.403587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.292317E+10 | 0.00 | 0.00 | 0.00 | 0.199556E+11 | 0.140650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.131992E+10 | 0.00 | 0.00 | 0.00 | 0.422371E+09 | 0.235815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113463E+10 | 0.00 | 0.00 | 0.00 | 0.105514E+10 | 0.133846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122903E+10 | 0.00 | 0.00 | 0.00 | 0.310412E+10 | 0.187510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134346E+10 | 0.00 | 0.00 | 0.00 | 0.566687E+10 | 0.394522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.183614E+10 | 0.00 | 0.00 | 0.00 | 0.107212E+11 | 6369346.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.251366E+10 | 0.00 | 0.00 | 0.00 | 0.169633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.273794E+10 | 0.00 | 0.00 | 0.00 | 0.196757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.294690E+10 | 0.00 | 0.00 | 0.00 | 0.214752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186991E+10 | 0.00 | 0.00 | 0.00 | 0.120128E+11 | 1019.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130035E+10 | 0.00 | 0.00 | 0.00 | 0.501426E+10 | 0.118128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107776E+10 | 0.00 | 0.00 | 0.00 | 0.204140E+10 | 0.413645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115374E+10 | 0.00 | 0.00 | 0.00 | 0.759927E+09 | 0.130866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204635E+11 | 0.00 | 0.00 | 0.00 | 0.989123E+11 | 0.576464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107776E+10 | 0.00 | 0.00 | 0.00 | 0.422371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.294690E+10 | 0.00 | 0.00 | 0.00 | 0.214752E+11 | 0.235815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122400E+11 | 0.00 | 0.00 | 11072.89 | 11281160.85 | 0.251140E+09 | 17161816.10 | 0.00 | 0.32 |
February | 0.874686E+10 | 0.00 | 0.00 | 2573563.23 | 1691363.63 | 21893883.87 | 0.124371E+10 | 0.00 | 0.37 |
March | 0.350639E+10 | 0.156656E+09 | 0.00 | 14334600.35 | 0.132142E+09 | 0.00 | 0.631548E+10 | 0.00 | 0.47 |
April | 0.129422E+10 | 0.395247E+09 | 0.00 | 17450397.56 | 0.100785E+09 | 0.00 | 0.501414E+10 | 0.00 | 0.50 |
May | 0.329969E+09 | 0.244560E+10 | 0.00 | 9906279.29 | 52556384.66 | 0.00 | 0.192094E+10 | 0.00 | 0.44 |
June | 0.161035E+09 | 0.741251E+10 | 0.00 | 4964753.96 | 74336646.66 | 0.00 | 0.895493E+09 | 0.00 | 0.36 |
July | 29719.54 | 0.972098E+10 | 0.00 | 0.00 | 0.194367E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 3014429.23 | 0.116937E+11 | 0.00 | 187289.94 | 0.146168E+09 | 0.00 | 8159594.94 | 0.00 | 0.28 |
September | 0.173096E+09 | 0.463588E+10 | 0.00 | 10774960.22 | 0.100645E+09 | 0.00 | 0.143513E+10 | 0.00 | 0.42 |
October | 0.149543E+10 | 0.133529E+10 | 0.00 | 18560008.92 | 10471927.87 | 0.00 | 0.741534E+10 | 0.00 | 0.49 |
November | 0.353768E+10 | 78105594.01 | 0.00 | 14570404.22 | 0.108072E+09 | 0.00 | 0.688448E+10 | 0.00 | 0.44 |
December | 0.893219E+10 | 19087124.59 | 0.00 | 2538364.81 | 2303435.39 | 1465944.66 | 0.185971E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.404199E+11 | 0.378930E+11 | 0.00 | 95871695.39 | 0.934821E+09 | 0.274500E+09 | 0.330097E+11 | 0.00 | 0.39 |
Minimum of Months | 29719.54 | 0.00 | 0.00 | 0.00 | 1691363.63 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.122400E+11 | 0.116937E+11 | 0.00 | 18560008.92 | 0.194367E+09 | 0.251140E+09 | 0.741534E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106046E+11 | 0.00 | 0.00 | 0.00 | 17023190.59 | 0.173753E+10 | 0.00 | 0.00 | 0.32 |
February | 0.919179E+10 | 15213.45 | 0.00 | 136815.53 | 2698497.76 | 0.492090E+09 | 43219544.21 | 0.00 | 0.37 |
March | 0.717996E+10 | 65055307.53 | 0.00 | 2391005.28 | 0.175068E+09 | 969577.11 | 0.160908E+10 | 0.00 | 0.43 |
April | 0.302960E+10 | 0.194466E+09 | 0.00 | 7369879.52 | 0.221857E+09 | 0.00 | 0.236615E+10 | 0.00 | 0.43 |
May | 0.738761E+09 | 0.171791E+10 | 0.00 | 5776091.97 | 0.306379E+09 | 0.00 | 0.117555E+10 | 0.00 | 0.36 |
June | 0.253120E+09 | 0.665928E+10 | 0.00 | 3065824.94 | 88877187.36 | 0.00 | 0.636369E+09 | 0.00 | 0.31 |
July | 1398720.65 | 0.876122E+10 | 0.00 | 14832.75 | 0.352833E+09 | 0.00 | 433843.56 | 0.00 | 0.24 |
August | 8768572.37 | 0.110237E+11 | 0.00 | 159211.51 | 0.145315E+09 | 0.00 | 6875246.77 | 0.00 | 0.26 |
September | 0.354682E+09 | 0.403466E+10 | 0.00 | 6024905.34 | 0.444626E+09 | 0.00 | 0.838237E+09 | 0.00 | 0.35 |
October | 0.434580E+10 | 0.110417E+10 | 0.00 | 5644579.91 | 0.145145E+09 | 0.00 | 0.257416E+10 | 0.00 | 0.40 |
November | 0.816660E+10 | 14302833.48 | 0.00 | 762014.63 | 0.227840E+09 | 3559591.30 | 0.620439E+09 | 0.00 | 0.39 |
December | 0.979807E+10 | 145055.06 | 0.00 | 5781.87 | 44865482.54 | 0.207369E+09 | 1503458.46 | 0.00 | 0.34 |
Annual Sum or Average | 0.536731E+11 | 0.335750E+11 | 0.00 | 31350943.25 | 0.217253E+10 | 0.244152E+10 | 0.987202E+10 | 0.00 | 0.35 |
Minimum of Months | 1398720.65 | 0.00 | 0.00 | 0.00 | 2698497.76 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.106046E+11 | 0.110237E+11 | 0.00 | 7369879.52 | 0.444626E+09 | 0.173753E+10 | 0.257416E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.798239E+10 | 0.00 | 0.00 | 0.00 | 15390436.13 | 0.378617E+10 | 0.00 | 0.00 | 0.32 |
February | 0.738556E+10 | 0.00 | 0.00 | 148593.59 | 5821469.00 | 0.169656E+10 | 53628111.32 | 0.00 | 0.36 |
March | 0.748772E+10 | 81352476.40 | 0.00 | 1797750.41 | 0.157266E+09 | 44793657.65 | 0.733442E+09 | 0.00 | 0.43 |
April | 0.318550E+10 | 0.153507E+09 | 0.00 | 7477574.64 | 0.214682E+09 | 1347321.40 | 0.182325E+10 | 0.00 | 0.44 |
May | 0.712322E+09 | 0.166122E+10 | 0.00 | 4712946.88 | 0.250741E+09 | 0.00 | 0.961650E+09 | 0.00 | 0.36 |
June | 0.308902E+09 | 0.644797E+10 | 0.00 | 2747412.99 | 95496005.44 | 0.00 | 0.492728E+09 | 0.00 | 0.31 |
July | 0.00 | 0.854949E+10 | 0.00 | 0.00 | 0.376748E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 7367055.52 | 0.107895E+11 | 0.00 | 12236.59 | 0.134904E+09 | 0.00 | 2551064.08 | 0.00 | 0.26 |
September | 0.405856E+09 | 0.382928E+10 | 0.00 | 4716725.49 | 0.690188E+09 | 0.00 | 0.544945E+09 | 0.00 | 0.35 |
October | 0.487971E+10 | 0.102796E+10 | 0.00 | 2602514.79 | 0.210029E+09 | 24106802.65 | 0.123942E+10 | 0.00 | 0.39 |
November | 0.760430E+10 | 7799679.35 | 4733398.02 | 238573.20 | 0.249445E+09 | 0.207643E+09 | 0.198829E+09 | 39948.25 | 0.38 |
December | 0.811962E+10 | 0.00 | 0.00 | 0.00 | 47420824.31 | 0.135023E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.480793E+11 | 0.325480E+11 | 4733398.02 | 24454328.59 | 0.244813E+10 | 0.711085E+10 | 0.605045E+10 | 39948.25 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5821469.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.811962E+10 | 0.107895E+11 | 4733398.02 | 7477574.64 | 0.690188E+09 | 0.378617E+10 | 0.182325E+10 | 39948.25 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.367088E+09 | 0.00 | 0.00 | 0.00 | 3241663.78 | 0.250299E+10 | 0.00 | 0.00 | 0.36 |
February | 0.636772E+09 | 0.00 | 361344.61 | 62570.19 | 861675.16 | 0.145037E+10 | 15194931.65 | 3147.25 | 0.38 |
March | 0.136529E+10 | 21694865.64 | 0.00 | 368301.97 | 31295510.85 | 0.273282E+09 | 0.112761E+09 | 0.00 | 0.43 |
April | 0.763468E+09 | 64016086.28 | 0.00 | 1722181.50 | 23192248.70 | 56424130.31 | 0.264351E+09 | 0.00 | 0.48 |
May | 0.188940E+09 | 0.515100E+09 | 0.00 | 1087335.18 | 36273281.02 | 348893.68 | 0.184477E+09 | 0.00 | 0.44 |
June | 67961060.09 | 0.218582E+10 | 0.00 | 774767.04 | 22452246.20 | 0.00 | 0.120156E+09 | 0.00 | 0.46 |
July | 0.00 | 0.294745E+10 | 0.00 | 0.00 | 54541850.79 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 2091615.58 | 0.348626E+10 | 0.00 | 0.00 | 32051048.51 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.106744E+09 | 0.108992E+10 | 0.00 | 1047755.13 | 0.112706E+09 | 0.00 | 0.108140E+09 | 0.00 | 0.40 |
October | 0.100806E+10 | 0.266294E+09 | 0.00 | 311292.83 | 38599575.45 | 0.151731E+09 | 0.130540E+09 | 0.00 | 0.39 |
November | 0.115456E+10 | 2221649.96 | 3107277.28 | 16880.00 | 49924297.70 | 0.553938E+09 | 12576343.35 | 14265.09 | 0.38 |
December | 0.693334E+09 | 0.00 | 60692.31 | 0.00 | 9927004.25 | 0.145413E+10 | 0.00 | 478.38 | 0.36 |
Annual Sum or Average | 0.635431E+10 | 0.105788E+11 | 3529314.20 | 5391083.83 | 0.415066E+09 | 0.644322E+10 | 0.948196E+09 | 17890.71 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 861675.16 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.136529E+10 | 0.348626E+10 | 3107277.28 | 1722181.50 | 0.112706E+09 | 0.250299E+10 | 0.264351E+09 | 14265.09 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.479613E+09 | 0.00 | 0.00 | 0.00 | 2047992.44 | 0.129027E+10 | 0.00 | 0.00 | 0.35 |
February | 0.502670E+09 | 0.00 | 227947.61 | 279601.62 | 544382.25 | 0.711595E+09 | 93412708.42 | 2328.15 | 0.39 |
March | 0.690609E+09 | 24235650.74 | 0.00 | 1115995.32 | 12696458.07 | 0.110807E+09 | 0.386038E+09 | 0.00 | 0.48 |
April | 0.296093E+09 | 56973838.55 | 0.00 | 2954625.26 | 7430230.11 | 18938013.96 | 0.588548E+09 | 0.00 | 0.68 |
May | 80389103.40 | 0.503105E+09 | 0.00 | 1574904.83 | 17180301.72 | 0.00 | 0.283674E+09 | 0.00 | 0.64 |
June | 29622813.99 | 0.185521E+10 | 0.00 | 1037890.38 | 10219173.26 | 0.00 | 0.181280E+09 | 0.00 | 0.65 |
July | 0.00 | 0.259673E+10 | 0.00 | 0.00 | 32742410.96 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 1321424.18 | 0.296593E+10 | 0.00 | 0.00 | 17479906.29 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 58086438.53 | 0.104660E+10 | 0.00 | 1326898.00 | 46067504.45 | 0.00 | 0.139294E+09 | 0.00 | 0.58 |
October | 0.496238E+09 | 0.237162E+09 | 0.00 | 1067514.14 | 12076125.61 | 79967847.42 | 0.405164E+09 | 0.00 | 0.49 |
November | 0.773047E+09 | 2427808.46 | 1973512.79 | 172170.60 | 30691556.86 | 0.231429E+09 | 83074369.63 | 8131.30 | 0.39 |
December | 0.667171E+09 | 0.00 | 38495.38 | 5.32 | 6271603.42 | 0.664903E+09 | 9156.36 | 150.55 | 0.35 |
Annual Sum or Average | 0.407486E+10 | 0.928837E+10 | 2239955.77 | 9529605.46 | 0.195448E+09 | 0.310791E+10 | 0.216049E+10 | 10610.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 544382.25 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.773047E+09 | 0.296593E+10 | 1973512.79 | 2954625.26 | 46067504.45 | 0.129027E+10 | 0.588548E+09 | 8131.30 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.844037E+09 | 0.00 | 0.00 | 803235.27 | 3244778.24 | 0.150559E+10 | 0.516439E+09 | 0.00 | 0.36 |
February | 0.794674E+09 | 0.00 | 362610.29 | 1814023.09 | 862503.02 | 0.872842E+09 | 0.643644E+09 | 2231.76 | 0.46 |
March | 0.100262E+10 | 59167526.75 | 0.00 | 3351985.71 | 14867146.08 | 0.184037E+09 | 0.101553E+10 | 0.00 | 0.59 |
April | 0.569326E+09 | 86833289.92 | 0.00 | 3881243.67 | 15266133.48 | 50174699.92 | 0.725603E+09 | 0.00 | 0.64 |
May | 0.180606E+09 | 0.589260E+09 | 0.00 | 1475211.27 | 37712456.84 | 349228.88 | 0.246974E+09 | 0.00 | 0.50 |
June | 75741695.38 | 0.223182E+10 | 0.00 | 796944.35 | 29214883.66 | 0.00 | 0.119689E+09 | 0.00 | 0.47 |
July | 0.00 | 0.307741E+10 | 0.00 | 0.00 | 59185344.22 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 2093625.12 | 0.406173E+10 | 0.00 | 0.00 | 28540473.89 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 96441714.53 | 0.154286E+10 | 0.00 | 2088731.64 | 78959750.09 | 0.00 | 0.210401E+09 | 0.00 | 0.57 |
October | 0.676060E+09 | 0.456122E+09 | 0.00 | 3808449.64 | 16029734.67 | 0.101754E+09 | 0.123546E+10 | 0.00 | 0.66 |
November | 0.936759E+09 | 5620245.40 | 3121776.96 | 3195822.52 | 48235630.81 | 0.290043E+09 | 0.103696E+10 | 9914.03 | 0.54 |
December | 0.918037E+09 | 4989406.50 | 0.00 | 1693221.14 | 7024793.52 | 0.731088E+09 | 0.738608E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.609639E+10 | 0.121158E+11 | 3484387.25 | 22908868.30 | 0.339144E+09 | 0.373588E+10 | 0.648931E+10 | 12145.79 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 862503.02 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.100262E+10 | 0.406173E+10 | 3121776.96 | 3881243.67 | 78959750.09 | 0.150559E+10 | 0.123546E+10 | 9914.03 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.432871E+09 | 0.00 | 0.00 | 1593.52 | 2060769.50 | 0.138510E+10 | 6022664.31 | 0.00 | 0.36 |
February | 0.487960E+09 | 0.00 | 230340.21 | 341760.37 | 547778.55 | 0.787950E+09 | 0.106212E+09 | 1372.20 | 0.41 |
March | 0.735447E+09 | 34641764.30 | 0.00 | 1323356.89 | 11053467.53 | 0.159041E+09 | 0.407082E+09 | 0.00 | 0.55 |
April | 0.377641E+09 | 54332718.25 | 0.00 | 2902705.17 | 11790731.30 | 32470353.97 | 0.519228E+09 | 0.00 | 0.71 |
May | 0.108816E+09 | 0.441181E+09 | 0.00 | 1304500.74 | 16945248.70 | 221796.43 | 0.236644E+09 | 0.00 | 0.62 |
June | 48006047.05 | 0.175965E+10 | 0.00 | 753002.76 | 10996868.51 | 0.00 | 0.109561E+09 | 0.00 | 0.60 |
July | 0.00 | 0.238624E+10 | 0.00 | 0.00 | 28665172.84 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 1329668.31 | 0.292965E+10 | 0.00 | 0.00 | 8461400.35 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 64170386.53 | 0.965783E+09 | 0.00 | 1160747.48 | 48721469.27 | 0.00 | 0.112126E+09 | 0.00 | 0.55 |
October | 0.549109E+09 | 0.225380E+09 | 0.00 | 1105492.61 | 15483426.84 | 87494143.51 | 0.365712E+09 | 0.00 | 0.51 |
November | 0.676713E+09 | 1865576.59 | 1984807.03 | 494599.51 | 31318375.35 | 0.306957E+09 | 0.184085E+09 | 8109.10 | 0.42 |
December | 0.540262E+09 | 324369.05 | 38867.50 | 49626.04 | 6016042.08 | 0.805710E+09 | 26497446.18 | 19.54 | 0.36 |
Annual Sum or Average | 0.402232E+10 | 0.879906E+10 | 2254014.74 | 9437385.10 | 0.192061E+09 | 0.356495E+10 | 0.207317E+10 | 9500.83 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 547778.55 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.735447E+09 | 0.292965E+10 | 1984807.03 | 2902705.17 | 48721469.27 | 0.138510E+10 | 0.519228E+09 | 8109.10 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365122E+09 | 0.00 | 0.00 | 0.00 | 2380160.78 | 0.244614E+10 | 0.00 | 0.00 | 0.33 |
February | 0.792048E+09 | 0.00 | 0.00 | 0.00 | 356853.11 | 0.140894E+10 | 0.00 | 0.00 | 0.37 |
March | 0.167285E+10 | 6868122.72 | 0.00 | 27532.29 | 48381108.00 | 0.197692E+09 | 25351332.09 | 0.00 | 0.42 |
April | 0.100113E+10 | 18927609.50 | 0.00 | 300334.04 | 71066619.89 | 37877433.28 | 48096242.23 | 0.00 | 0.40 |
May | 0.288153E+09 | 0.362912E+09 | 0.00 | 312888.85 | 88264444.22 | 0.00 | 69592797.42 | 0.00 | 0.34 |
June | 82651851.69 | 0.174395E+10 | 0.00 | 568562.17 | 22500699.32 | 0.00 | 91553712.67 | 0.00 | 0.36 |
July | 6270.39 | 0.247489E+10 | 0.00 | 0.00 | 53933630.95 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 1497038.46 | 0.297227E+10 | 0.00 | 5999.63 | 30839370.88 | 0.00 | 497727.67 | 0.00 | 0.33 |
September | 0.125249E+09 | 0.100800E+10 | 0.00 | 1183932.99 | 29746490.50 | 0.00 | 0.138418E+09 | 0.00 | 0.37 |
October | 0.128385E+10 | 0.242782E+09 | 0.00 | 470084.57 | 11123292.84 | 8487232.26 | 0.210613E+09 | 0.00 | 0.39 |
November | 0.180914E+10 | 1943926.43 | 140350.08 | 29886.55 | 36240900.92 | 0.158731E+09 | 29826722.28 | 3038.84 | 0.39 |
December | 0.130590E+10 | 0.00 | 0.00 | 0.00 | 4358799.94 | 0.984712E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.872760E+10 | 0.883254E+10 | 140350.08 | 2899221.08 | 0.399192E+09 | 0.524258E+10 | 0.613950E+09 | 3038.84 | 0.36 |
Minimum of Months | 6270.39 | 0.00 | 0.00 | 0.00 | 356853.11 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.180914E+10 | 0.297227E+10 | 140350.08 | 1183932.99 | 88264444.22 | 0.244614E+10 | 0.210613E+09 | 3038.84 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.600959E+09 | 0.00 | 0.00 | 0.00 | 1505003.42 | 0.117048E+10 | 0.00 | 0.00 | 0.33 |
February | 0.630536E+09 | 0.00 | 0.00 | 170507.82 | 225642.39 | 0.670369E+09 | 74536401.33 | 0.00 | 0.37 |
March | 0.962602E+09 | 11233520.56 | 0.00 | 529856.77 | 25589072.11 | 50222008.86 | 0.212246E+09 | 0.00 | 0.44 |
April | 0.459882E+09 | 30996777.00 | 0.00 | 1578514.75 | 32697929.55 | 6335363.16 | 0.331903E+09 | 0.00 | 0.51 |
May | 0.110512E+09 | 0.420200E+09 | 0.00 | 1116022.47 | 30769274.90 | 0.00 | 0.214336E+09 | 0.00 | 0.52 |
June | 32793554.43 | 0.157815E+10 | 0.00 | 944548.85 | 10415727.14 | 0.00 | 0.167788E+09 | 0.00 | 0.55 |
July | 3964.84 | 0.230275E+10 | 0.00 | 0.00 | 32787190.56 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 900141.39 | 0.264251E+10 | 0.00 | 8487.55 | 19500093.94 | 0.00 | 368926.19 | 0.00 | 0.46 |
September | 64507910.57 | 0.947187E+09 | 0.00 | 1510873.65 | 15072833.22 | 0.00 | 0.181891E+09 | 0.00 | 0.56 |
October | 0.575174E+09 | 0.215567E+09 | 0.00 | 1726536.04 | 1397044.82 | 2932085.07 | 0.635799E+09 | 0.00 | 0.52 |
November | 0.107304E+10 | 1972406.80 | 0.00 | 491268.37 | 22561487.63 | 24692425.39 | 0.201047E+09 | 0.00 | 0.40 |
December | 0.110700E+10 | 0.00 | 0.00 | 0.00 | 2756120.05 | 0.340460E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.561791E+10 | 0.815056E+10 | 0.00 | 8076616.26 | 0.195277E+09 | 0.226549E+10 | 0.201991E+10 | 0.00 | 0.45 |
Minimum of Months | 3964.84 | 0.00 | 0.00 | 0.00 | 225642.39 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.110700E+10 | 0.264251E+10 | 0.00 | 1726536.04 | 32787190.56 | 0.117048E+10 | 0.635799E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.882229E+09 | 0.00 | 0.00 | 45951.44 | 2378402.29 | 0.254077E+10 | 30580320.02 | 0.00 | 0.40 |
February | 0.809527E+09 | 0.00 | 0.00 | 737004.55 | 356589.47 | 0.165383E+10 | 0.196836E+09 | 0.00 | 0.46 |
March | 0.134644E+10 | 50712358.49 | 0.00 | 839674.37 | 21649072.64 | 0.578619E+09 | 0.238709E+09 | 0.00 | 0.49 |
April | 0.814521E+09 | 47583278.91 | 0.00 | 1323870.23 | 58348633.50 | 0.294841E+09 | 0.120124E+09 | 0.00 | 0.48 |
May | 0.261562E+09 | 0.491266E+09 | 0.00 | 404398.65 | 85773469.77 | 64244928.76 | 67591476.69 | 0.00 | 0.40 |
June | 95829056.67 | 0.208494E+10 | 0.00 | 453336.20 | 72028131.47 | 15845100.25 | 60255335.16 | 0.00 | 0.41 |
July | 6265.76 | 0.294150E+10 | 0.00 | 0.00 | 0.102962E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 1995931.48 | 0.400995E+10 | 0.00 | 0.00 | 45707204.12 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.132175E+09 | 0.150623E+10 | 0.00 | 1921057.56 | 45143505.71 | 12564766.12 | 0.183789E+09 | 0.00 | 0.54 |
October | 0.835216E+09 | 0.421533E+09 | 0.00 | 3078513.04 | 7352429.51 | 0.264024E+09 | 0.971306E+09 | 0.00 | 0.61 |
November | 0.127887E+10 | 9837598.10 | 0.00 | 2423704.67 | 29994959.83 | 0.505077E+09 | 0.794997E+09 | 0.00 | 0.53 |
December | 0.132927E+10 | 3221560.15 | 14634.29 | 581304.03 | 2250329.77 | 0.105655E+10 | 0.291592E+09 | 787.61 | 0.41 |
Annual Sum or Average | 0.778764E+10 | 0.115668E+11 | 14634.29 | 11808814.74 | 0.473945E+09 | 0.698636E+10 | 0.295578E+10 | 787.61 | 0.46 |
Minimum of Months | 6265.76 | 0.00 | 0.00 | 0.00 | 356589.47 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.134644E+10 | 0.400995E+10 | 14634.29 | 3078513.04 | 0.102962E+09 | 0.254077E+10 | 0.971306E+09 | 787.61 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.468859E+09 | 0.00 | 0.00 | 0.00 | 1504215.57 | 0.130639E+10 | 0.00 | 0.00 | 0.33 |
February | 0.593518E+09 | 0.00 | 0.00 | 168842.24 | 225524.26 | 0.757441E+09 | 45947757.11 | 0.00 | 0.38 |
March | 0.989463E+09 | 28326475.78 | 0.00 | 592123.73 | 16367105.13 | 68484885.94 | 0.196164E+09 | 0.00 | 0.46 |
April | 0.525439E+09 | 32453496.16 | 0.00 | 1306439.10 | 32720448.70 | 9494090.16 | 0.227000E+09 | 0.00 | 0.50 |
May | 0.141720E+09 | 0.379290E+09 | 0.00 | 689045.19 | 29260426.99 | 0.00 | 0.143304E+09 | 0.00 | 0.48 |
June | 51043279.68 | 0.152351E+10 | 0.00 | 621210.07 | 8918186.96 | 0.00 | 85711441.87 | 0.00 | 0.50 |
July | 3962.77 | 0.215031E+10 | 0.00 | 0.00 | 24090299.20 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 747144.07 | 0.264996E+10 | 0.00 | 10909.33 | 11784184.79 | 0.00 | 511916.94 | 0.00 | 0.46 |
September | 70355543.61 | 0.920818E+09 | 0.00 | 1282647.05 | 14025733.30 | 0.00 | 0.130462E+09 | 0.00 | 0.52 |
October | 0.638538E+09 | 0.215463E+09 | 0.00 | 1372373.48 | 2032361.06 | 1384292.18 | 0.474682E+09 | 0.00 | 0.50 |
November | 0.107201E+10 | 1823420.41 | 0.00 | 595770.98 | 22555820.12 | 45904449.53 | 0.212406E+09 | 0.00 | 0.43 |
December | 0.983427E+09 | 257508.09 | 0.00 | 26180.66 | 2507453.13 | 0.445661E+09 | 18615247.53 | 0.00 | 0.35 |
Annual Sum or Average | 0.553512E+10 | 0.790221E+10 | 0.00 | 6665541.84 | 0.165992E+09 | 0.263476E+10 | 0.153480E+10 | 0.00 | 0.44 |
Minimum of Months | 3962.77 | 0.00 | 0.00 | 0.00 | 225524.26 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.107201E+10 | 0.264996E+10 | 0.00 | 1372373.48 | 32720448.70 | 0.130639E+10 | 0.474682E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.487378E+09 | 0.00 | 0.00 | 0.00 | 3594606.70 | 0.227699E+10 | 0.00 | 0.00 | 0.33 |
February | 0.842142E+09 | 3283.70 | 0.00 | 54628.03 | 569813.16 | 0.128229E+10 | 8887841.79 | 0.00 | 0.37 |
March | 0.165614E+10 | 22705588.37 | 0.00 | 308521.92 | 31782327.57 | 0.107753E+09 | 98037024.76 | 0.00 | 0.43 |
April | 0.870742E+09 | 76793425.77 | 0.00 | 1358774.28 | 22388053.82 | 16562433.97 | 0.254644E+09 | 0.00 | 0.45 |
May | 0.221541E+09 | 0.572432E+09 | 0.00 | 1099549.67 | 23589292.36 | 0.00 | 0.185355E+09 | 0.00 | 0.43 |
June | 73985623.17 | 0.232036E+10 | 0.00 | 777051.67 | 15840871.71 | 0.00 | 0.123774E+09 | 0.00 | 0.46 |
July | 390095.23 | 0.311164E+10 | 0.00 | 0.00 | 49190592.79 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 2487951.56 | 0.364911E+10 | 0.00 | 10175.84 | 30684692.43 | 0.00 | 770974.17 | 0.00 | 0.40 |
September | 0.137400E+09 | 0.117172E+10 | 0.00 | 1056549.23 | 41410411.72 | 0.00 | 0.110798E+09 | 0.00 | 0.40 |
October | 0.123548E+10 | 0.290292E+09 | 0.00 | 404320.23 | 18861205.63 | 24258695.13 | 0.168248E+09 | 0.00 | 0.40 |
November | 0.152980E+10 | 3610826.14 | 303651.92 | 19193.55 | 47378721.56 | 0.313450E+09 | 19961758.32 | 7138.01 | 0.39 |
December | 0.107360E+10 | 0.00 | 0.00 | 0.00 | 9504398.07 | 0.109339E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.813109E+10 | 0.112187E+11 | 303651.92 | 5088764.43 | 0.294795E+09 | 0.511469E+10 | 0.970477E+09 | 7138.01 | 0.40 |
Minimum of Months | 390095.23 | 0.00 | 0.00 | 0.00 | 569813.16 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.165614E+10 | 0.364911E+10 | 303651.92 | 1358774.28 | 49190592.79 | 0.227699E+10 | 0.254644E+09 | 7138.01 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.446656E+09 | 0.00 | 0.00 | 0.00 | 2271200.13 | 0.105171E+10 | 0.00 | 0.00 | 0.28 |
February | 0.482754E+09 | 3392.41 | 0.00 | 319016.86 | 360028.19 | 0.558995E+09 | 0.117345E+09 | 0.00 | 0.33 |
March | 0.678596E+09 | 23445265.98 | 0.00 | 1172456.54 | 11005564.63 | 40608985.64 | 0.416396E+09 | 0.00 | 0.43 |
April | 0.329043E+09 | 62500435.93 | 0.00 | 2606227.97 | 7364339.66 | 4868954.24 | 0.590480E+09 | 0.00 | 0.61 |
May | 97050026.98 | 0.497351E+09 | 0.00 | 1596632.42 | 13281632.09 | 0.00 | 0.292667E+09 | 0.00 | 0.60 |
June | 33253736.53 | 0.184334E+10 | 0.00 | 1044600.77 | 9714542.72 | 0.00 | 0.187635E+09 | 0.00 | 0.62 |
July | 246476.02 | 0.258555E+10 | 0.00 | 0.00 | 30015255.68 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 1553087.50 | 0.293767E+10 | 0.00 | 13891.52 | 19395536.30 | 0.00 | 538194.44 | 0.00 | 0.51 |
September | 72486994.11 | 0.992099E+09 | 0.00 | 1274026.81 | 21383529.99 | 0.00 | 0.145116E+09 | 0.00 | 0.54 |
October | 0.509598E+09 | 0.220399E+09 | 0.00 | 1321288.25 | 6738955.05 | 17727344.81 | 0.494046E+09 | 0.00 | 0.46 |
November | 0.758396E+09 | 2944323.57 | 161083.29 | 345743.47 | 25517133.89 | 0.122445E+09 | 0.136159E+09 | 3664.75 | 0.34 |
December | 0.679483E+09 | 1338289.62 | 0.00 | 2333.71 | 2900757.96 | 0.445200E+09 | 759074.14 | 0.00 | 0.28 |
Annual Sum or Average | 0.408912E+10 | 0.916664E+10 | 161083.29 | 9696218.31 | 0.149948E+09 | 0.224155E+10 | 0.238114E+10 | 3664.75 | 0.46 |
Minimum of Months | 246476.02 | 0.00 | 0.00 | 0.00 | 360028.19 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.758396E+09 | 0.293767E+10 | 161083.29 | 2606227.97 | 30015255.68 | 0.105171E+10 | 0.590480E+09 | 3664.75 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.982212E+09 | 0.00 | 0.00 | 1035928.26 | 3593875.23 | 0.132285E+10 | 0.598657E+09 | 0.00 | 0.35 |
February | 0.952257E+09 | 10505.21 | 0.00 | 2019873.04 | 568646.10 | 0.760774E+09 | 0.680783E+09 | 0.00 | 0.47 |
March | 0.120957E+10 | 74385385.80 | 0.00 | 3299608.90 | 10749308.00 | 67954993.27 | 0.101682E+10 | 0.00 | 0.59 |
April | 0.669876E+09 | 0.109663E+09 | 0.00 | 3281199.33 | 14331146.96 | 14863740.07 | 0.674310E+09 | 0.00 | 0.60 |
May | 0.221786E+09 | 0.667529E+09 | 0.00 | 1386033.39 | 23687690.13 | 0.00 | 0.225033E+09 | 0.00 | 0.49 |
June | 86509583.69 | 0.238561E+10 | 0.00 | 746406.59 | 16371942.25 | 0.00 | 0.111438E+09 | 0.00 | 0.47 |
July | 390015.85 | 0.327724E+10 | 0.00 | 0.00 | 48533221.39 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 2487445.29 | 0.428981E+10 | 0.00 | 9670.39 | 30678448.42 | 0.00 | 769251.69 | 0.00 | 0.46 |
September | 0.128175E+09 | 0.163056E+10 | 0.00 | 1990996.74 | 34345783.49 | 0.00 | 0.193258E+09 | 0.00 | 0.56 |
October | 0.822690E+09 | 0.474957E+09 | 0.00 | 4286056.59 | 8776112.42 | 17484106.08 | 0.135142E+10 | 0.00 | 0.68 |
November | 0.117127E+10 | 11807249.47 | 138761.38 | 3942872.51 | 42245819.17 | 0.117384E+09 | 0.121914E+10 | 2308.53 | 0.58 |
December | 0.118890E+10 | 10811404.68 | 0.00 | 2109339.17 | 3213796.53 | 0.455909E+09 | 0.876643E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.743612E+10 | 0.129324E+11 | 138761.38 | 24107984.93 | 0.237096E+09 | 0.275722E+10 | 0.694827E+10 | 2308.53 | 0.50 |
Minimum of Months | 390015.85 | 0.00 | 0.00 | 0.00 | 568646.10 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.120957E+10 | 0.428981E+10 | 138761.38 | 4286056.59 | 48533221.39 | 0.132285E+10 | 0.135142E+10 | 2308.53 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.497429E+09 | 0.00 | 0.00 | 671.02 | 2269918.51 | 0.125677E+10 | 4653853.65 | 0.00 | 0.33 |
February | 0.598192E+09 | 2975.57 | 0.00 | 335149.19 | 359825.03 | 0.703496E+09 | 87827901.91 | 0.00 | 0.40 |
March | 0.905712E+09 | 44453188.14 | 0.00 | 1208370.87 | 8296818.07 | 60075173.63 | 0.369442E+09 | 0.00 | 0.54 |
April | 0.437119E+09 | 71878744.51 | 0.00 | 2357822.34 | 9986704.05 | 9501239.85 | 0.465559E+09 | 0.00 | 0.65 |
May | 0.128077E+09 | 0.511476E+09 | 0.00 | 1193073.12 | 8255555.16 | 0.00 | 0.214019E+09 | 0.00 | 0.60 |
June | 53612262.97 | 0.192589E+10 | 0.00 | 698378.44 | 5832797.70 | 0.00 | 96789651.61 | 0.00 | 0.61 |
July | 246336.93 | 0.259724E+10 | 0.00 | 0.00 | 21016255.47 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 1571089.07 | 0.314017E+10 | 0.00 | 7580.45 | 8217973.37 | 0.00 | 488847.91 | 0.00 | 0.53 |
September | 81964282.86 | 0.103228E+10 | 0.00 | 1118340.68 | 21525314.76 | 0.00 | 99773110.92 | 0.00 | 0.54 |
October | 0.679257E+09 | 0.243640E+09 | 0.00 | 1201882.00 | 6290262.86 | 13727797.39 | 0.376187E+09 | 0.00 | 0.51 |
November | 0.890299E+09 | 2908315.21 | 162301.89 | 589048.07 | 29532212.37 | 0.168934E+09 | 0.192854E+09 | 3693.43 | 0.43 |
December | 0.773883E+09 | 1070653.09 | 0.00 | 53955.26 | 5052705.08 | 0.571373E+09 | 30300960.75 | 0.00 | 0.35 |
Annual Sum or Average | 0.504736E+10 | 0.957101E+10 | 162301.89 | 8764271.44 | 0.126636E+09 | 0.278388E+10 | 0.193790E+10 | 3693.43 | 0.50 |
Minimum of Months | 246336.93 | 0.00 | 0.00 | 0.00 | 359825.03 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.905712E+09 | 0.314017E+10 | 162301.89 | 2357822.34 | 29532212.37 | 0.125677E+10 | 0.465559E+09 | 3693.43 | 0.65 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.185250E+12 | 0.175191E+11 | 0.00 | 0.164662E+12 | 0.991741E+10 |
February | 0.183657E+12 | 0.146990E+11 | 0.00 | 0.159442E+12 | 0.168379E+11 |
March | 0.265452E+12 | 0.948458E+10 | 0.00 | 0.177538E+12 | 0.452859E+11 |
April | 0.295350E+12 | 0.460944E+10 | 0.00 | 0.121143E+12 | 0.813187E+11 |
May | 0.324396E+12 | 0.135685E+09 | 0.00 | 0.417445E+11 | 0.156911E+12 |
June | 0.314724E+12 | -0.566779E+10 | 0.00 | -0.187850E+11 | 0.246664E+12 |
July | 0.305164E+12 | -0.851318E+10 | 0.00 | -0.604449E+11 | 0.286230E+12 |
August | 0.284704E+12 | -0.103845E+11 | 0.00 | -0.738008E+11 | 0.320949E+12 |
September | 0.223051E+12 | -0.268557E+10 | 0.00 | -0.194087E+10 | 0.189198E+12 |
October | 0.214452E+12 | 0.482574E+10 | 0.00 | 0.132038E+12 | 0.798683E+11 |
November | 0.157596E+12 | 0.940867E+10 | 0.00 | 0.162820E+12 | 0.311189E+11 |
December | 0.150926E+12 | 0.155701E+11 | 0.00 | 0.181092E+12 | 0.122297E+11 |
Annual Sum or Average | 0.290472E+13 | 0.490013E+11 | 0.00 | 0.985508E+12 | 0.147653E+13 |
Minimum of Months | 0.150926E+12 | -0.103845E+11 | 0.00 | -0.738008E+11 | 0.991741E+10 |
Maximum of Months | 0.324396E+12 | 0.175191E+11 | 0.00 | 0.181092E+12 | 0.320949E+12 |