Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:32:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1521.94 | 305.48 | 305.48 |
Net Site Energy | 1366.26 | 274.23 | 274.23 |
Total Source Energy | 4190.67 | 841.13 | 841.13 |
Net Source Energy | 3697.64 | 742.17 | 742.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 101.14 | 168.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 154.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 166.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 104.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 133.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1219.82 | 302.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 101.14 | 168.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 154.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 166.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 104.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 133.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 101.14 | 168.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 154.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 166.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 104.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 133.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 72.21 | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 244.84 | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 72.21 | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 244.84 | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 162.613 | 13.33 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -6.94 | -0.6 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 155.676 | 12.76 |
Electricity Coming From Utility | 1065.164 | 87.32 |
Surplus Electricity Going To Utility | 1.019 | 0.08 |
Net Electricity From Utility | 1064.145 | 87.24 |
Total On-Site and Utility Electric Sources | 1219.821 | 100.00 |
Total Electricity End Uses | 1219.821 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 203.17 |
Time Setpoint Not Met During Occupied Cooling | 192.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2231.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-FEB-07:10 | 21-DEC-09:20 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 158129.76 | 89794.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5760.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9466.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 188377.46 | 99260.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 158129.76 | 89794.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2981.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 36.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5760.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9466.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 320.30 | 182.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 488.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 527.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 330.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 145.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3863.17 | 327.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 64.29 | 36.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 775.40 | 65.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 64.29 | 36.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 775.40 | 65.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.87 | 0.261369 | 0.222000 | 0.636567 | 0.696985 | 0.500000 | 0.001458 |
CORE_MID VAV BOX COMPONENT | 2.40 | 0.312117 | 0.265000 | 0.636318 | 0.832311 | 0.500000 | 0.001221 |
CORE_TOP VAV BOX COMPONENT | 2.56 | 0.292831 | 0.249000 | 0.637276 | 0.780883 | 0.500000 | 0.001301 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.817320 | 0.193304 | 0.164000 | 0.134041 | 0.515479 | 0.500000 | 0.001971 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.936514 | 0.106802 | 0.091000 | 0.085223 | 0.300000 | 0.500000 | 0.003567 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.11 | 0.142160 | 0.121000 | 0.134475 | 0.379093 | 0.500000 | 0.002680 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.08 | 0.092786 | 0.079000 | 0.085155 | 0.300000 | 0.500000 | 0.004106 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.620014 | 0.254820 | 0.217000 | 0.134543 | 0.679519 | 0.500000 | 0.001495 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.756440 | 0.132227 | 0.112000 | 0.084721 | 0.352605 | 0.500000 | 0.002881 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.867437 | 0.182136 | 0.155000 | 0.134453 | 0.485697 | 0.500000 | 0.002092 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.830394 | 0.120443 | 0.102000 | 0.084700 | 0.321182 | 0.500000 | 0.003163 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.706091 | 0.223755 | 0.190000 | 0.134157 | 0.596681 | 0.500000 | 0.001703 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.930495 | 0.300000 | 0.500000 | 0.003544 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.00 | 0.157209 | 0.134000 | 0.134667 | 0.419224 | 0.500000 | 0.002424 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.997103 | 0.100306 | 0.085000 | 0.084754 | 0.300000 | 0.500000 | 0.003798 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17257.56 |
CORE_MID VAV BOX REHEAT COIL | 21218.68 |
CORE_TOP VAV BOX REHEAT COIL | 38425.09 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17469.89 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11502.72 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17576.49 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11502.53 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13146.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8740.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13255.81 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8740.44 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 13657.59 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9066.39 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 13752.71 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9066.31 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.97 | 1.07 | 5.94 | 2.06 | 5.22 | 5.22 | 0.300000 | 0.394639 | 5.22 |
PACU_VAV_MID | 3.02 | 1.07 | 6.04 | 2.46 | 5.06 | 5.06 | 0.300000 | 0.487122 | 5.06 |
PACU_VAV_TOP | 3.25 | 1.08 | 6.50 | 3.56 | 5.90 | 5.90 | 0.300000 | 0.602859 | 5.90 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.22 |
PACU_VAV_MID_OA_CONTROLLER | 5.06 |
PACU_VAV_TOP_OA_CONTROLLER | 5.90 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.22 | 86431.37 | 0.800655 | 1.74 | 28807.58 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.06 | 83684.56 | 0.800655 | 1.68 | 27892.06 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.90 | 97715.38 | 0.800655 | 1.97 | 32568.54 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 25134.16 |
PACU_VAV_MID HEATING COIL | 25620.90 |
PACU_VAV_TOP HEATING COIL | 24672.34 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.22 |
PACU_VAV_MID FAN | 5.06 |
PACU_VAV_TOP FAN | 5.90 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5358 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5301 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.6467 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.632 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.652 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.312 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.34415616E-12 | 0.73563561E-15 | -0.10764161E-12 | 0.10685741E-15 |
43 | 6 | 0.31504638E-07 | 0.15474724E-09 | 0.71933787E-08 | -0.15048178E-12 |
44 | 5 | -0.20438857E-03 | 0.13016735E-05 | -0.10492214E-03 | 0.71015789E-08 |
45 | 4 | 0.30870407 | 0.62380386E-03 | 0.10564545 | -0.35923044E-04 |
46 | 3 | -7.5938769 | 0.19061556E-01 | -2.4361333 | 0.30615224E-01 |
47 | 2 | 41.951003 | 0.66938758E-01 | 15.662994 | -0.34536947 |
48 | 1 | -81.372858 | 0.29881068E-01 | -29.498176 | 1.0962451 |
49 | 0 | 46.824334 | 0.59474289E-03 | 16.282875 | |
50 | 7 | -0.34405391E-12 | 0.74902691E-15 | -0.11167434E-12 | 0.10710038E-15 |
51 | 6 | 0.31570920E-07 | 0.15318783E-09 | 0.72080048E-08 | -0.15084089E-12 |
52 | 5 | -0.20472033E-03 | 0.12880691E-05 | -0.10508761E-03 | 0.71158009E-08 |
53 | 4 | 0.30908525 | 0.61707511E-03 | 0.10578288 | -0.35977555E-04 |
54 | 3 | -7.6014096 | 0.18850271E-01 | -2.4383697 | 0.30652185E-01 |
55 | 2 | 41.975828 | 0.66179041E-01 | 15.672127 | -0.34564605 |
56 | 1 | -81.391862 | 0.29534967E-01 | -29.506353 | 1.0966501 |
57 | 0 | 46.824333 | 0.58771801E-03 | 16.282688 | |
58 | 7 | -0.33303739E-12 | 0.11430073E-14 | -0.10564856E-12 | 0.99270328E-16 |
59 | 6 | 0.30206507E-07 | 0.18467178E-09 | 0.69068382E-08 | -0.14346196E-12 |
60 | 5 | -0.19787007E-03 | 0.15652367E-05 | -0.10166770E-03 | 0.68228702E-08 |
61 | 4 | 0.30118360 | 0.75522621E-03 | 0.10293566 | -0.34850853E-04 |
62 | 3 | -7.4451882 | 0.23217066E-01 | -2.3919942 | 0.29885849E-01 |
63 | 2 | 41.460907 | 0.81970212E-01 | 15.482559 | -0.33990950 |
64 | 1 | -80.997597 | 0.36763750E-01 | -29.336578 | 1.0882477 |
65 | 0 | 46.824336 | 0.73512635E-03 | 16.286622 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2115E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2185E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3381E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3442E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2296E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2785E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3510E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3752E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1673 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9797E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1898 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1018 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1171 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9932E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2114E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2182E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3379E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3439E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2287E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2767E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3507E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3749E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9676E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1014E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4146E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7166E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8760E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4795E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6444E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6601E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4127E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4391E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9814E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0004E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8688E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8752E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0780E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0864E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6216E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6789E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8576E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9030E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3633E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3952E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3507E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3749E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4064E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5257E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3885E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9215E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1342E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3231E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6219E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6792E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8579E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9035E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3638E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3963E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3510E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3752E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.1305E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1788E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6184E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8137E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0092E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5415E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6444E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6601E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5398E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6232E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1423E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2355E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9599E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9915E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0782E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0865E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1655 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1068 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1844 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1201 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1252 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3046E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4807E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5582E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7376E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9712E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2148E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6039E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7160E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.3853E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5395E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5971E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0217E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.2920E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9352E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5798E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6825E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9276E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4807E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5582E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8959E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0471E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4126E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6992E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8457E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4455E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5395E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5971E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1655 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1068 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1844 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1200 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1252 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3038E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4802E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5579E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7376E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9709E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2147E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6037E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7156E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.3849E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5390E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5968E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0219E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.2919E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9353E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5797E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6823E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9274E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4802E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5579E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8959E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0468E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4125E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6989E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8453E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4451E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5390E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5968E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 32301.79093 | 32301.79093 | 2.86742 | 2.86742 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8647.76021 | 8647.76021 | 0.45675 | 0.45675 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27069.85783 | 27069.85783 | 2.40120 | 2.40120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14985.22256 | 14985.22256 | 0.78268 | 0.78268 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28592.58520 | 28592.58520 | 2.55934 | 2.55934 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 27035.07891 | 27035.07891 | 1.41736 | 1.41736 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9131.50789 | 9131.50789 | 0.81732 | 0.81732 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12262.55204 | 12262.55204 | 0.64440 | 0.64440 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10463.29724 | 10463.29724 | 0.93651 | 0.93651 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.17933 | 5.46350E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8073.43563 | 8073.43563 | 0.42429 | 0.42429 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12416.75198 | 12416.75198 | 1.11136 | 1.11136 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12337.21785 | 12337.21785 | 0.64833 | 0.64833 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12043.12118 | 12043.12118 | 1.07792 | 1.07792 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8073.29722 | 8073.29722 | 0.42429 | 0.42429 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6926.94516 | 6926.94516 | 0.62001 | 0.62001 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9232.78956 | 9232.78956 | 0.48491 | 0.48491 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8451.21903 | 8451.21903 | 0.75644 | 0.75644 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6137.88269 | 6137.88269 | 0.32241 | 0.32241 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9691.25359 | 9691.25359 | 0.86744 | 0.86744 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9309.64753 | 9309.64753 | 0.48896 | 0.48896 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9277.46321 | 9277.46321 | 0.83039 | 0.83039 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.08800 | 5.47095E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6137.82315 | 6137.82315 | 0.32240 | 0.32240 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7888.73422 | 7888.73422 | 0.70609 | 0.70609 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9591.79428 | 9591.79428 | 0.50378 | 0.50378 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10395.98556 | 10395.98556 | 0.93050 | 0.93050 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.29133 | 5.46218E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6366.60404 | 6366.60404 | 0.33443 | 0.33443 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11228.05706 | 11228.05706 | 1.00498 | 1.00498 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 33.28333 | 5.47432E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9658.41419 | 9658.41419 | 0.50729 | 0.50729 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11140.14859 | 11140.14859 | 0.99710 | 0.99710 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6366.54281 | 6366.54281 | 0.33442 | 0.33442 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 66714.68 | 5.22132 | 5.22132 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 28554.74 | 2.06053 | 2.06053 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64815.84 | 5.05538 | 5.05538 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 28718.58 | 2.46259 | 2.46259 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 74063.85 | 5.90299 | 5.90299 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 28823.39 | 3.55867 | 3.55867 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.86742 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26137 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63657 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69698 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45771E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17257.55639 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.40120 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31212 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26500 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63632 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83231 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22070E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21218.67971 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55934 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29283 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63728 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78088 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30109E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 38425.09114 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81732 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19330 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16400 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13404 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51548 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97098E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17469.88535 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93651 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10680 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.10000E-002 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52228E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.56734E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11502.72478 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11136 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14216 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13448 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37909 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68008E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17576.48568 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07792 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.27857E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 7.90000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51554E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.10624E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11502.52866 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62001 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25482 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13454 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67952 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49518E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13146.06239 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75644 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13223 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47212E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35261 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88141E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8740.52131 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86744 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18214 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13445 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48570 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09184E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13255.80513 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83039 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12044 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47002E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32118 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16332E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8740.43779 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70609 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22376 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13416 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59668 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70275E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13657.59351 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93050 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54441E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9066.39138 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00498 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15721 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13400 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13467 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41922 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42352E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13752.71388 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99710 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10031 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.50000E-002 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47538E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79838E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9066.30547 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.97085 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07498 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.94170 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.06053 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.22132 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.22132 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.39464 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.01993 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07457 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.03987 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.46259 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.05538 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.05538 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.48712 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.25123 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07617 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.50246 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.55867 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.90299 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.90299 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.60286 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.22132 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.05538 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.90299 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.22132 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.22132 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86431.36922 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.74027 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28807.57536 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 25134.15565 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.22132 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.05538 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.05538 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 83684.55610 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68496 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27892.06255 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 25620.90281 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.05538 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.90299 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.90299 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97715.38170 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.96747 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32568.53672 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 24672.33690 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.90299 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 84944.10 | 289841.30 | 11.70 | 2.92 | 3.35 | 3.53 | 3.69 | 9.95 | 11.44 | 12.06 | 12.59 | 4.9020 | 3.8755 | 2.5980 | 1.1002 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 82244.55 | 280630.06 | 11.70 | 2.92 | 3.35 | 3.53 | 3.69 | 9.95 | 11.44 | 12.06 | 12.59 | 4.7462 | 3.7523 | 2.5155 | 1.0653 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 96033.94 | 327681.42 | 11.70 | 2.92 | 3.35 | 3.53 | 3.69 | 9.95 | 11.44 | 12.06 | 12.59 | 5.5419 | 4.3815 | 2.9372 | 1.2439 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.6607961433E-002 | 8.6491228010E-002 | Pass | Pass | 2.9289188122E-002 | 0.1669927117 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.9267443602E-002 | 7.9723815472E-002 | Pass | Pass | 4.3348436714E-002 | 0.2003804636 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.9289845946E-002 | 3.6092278571E-002 | Pass | Pass | 5.3634998678E-002 | 0.2185392544 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2336365035E-002 | 2.5931738031E-002 | Pass | Pass | 7.4245999608E-002 | 0.3770230571 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.1813239905E-002 | 5.7995948158E-002 | Pass | Pass | 4.8777540634E-002 | 0.2144207040 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.2610404927E-002 | 2.7821268796E-002 | Pass | Pass | 4.7341042695E-002 | 0.2213902749 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.9379658799E-002 | 9.3133252640E-002 | Pass | Pass | 0.6980610617 | 7.6348756733 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.0109997694E-002 | 0.1306841668 | Pass | Pass | 0.7037599249 | 7.9820754581 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1532706728 | 0.1496221018 | Pass | Pass | 6.7382684908E-002 | 0.3795088860 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1109856392 | 0.1100208497 | Pass | Pass | 0.6179080534 | 6.7232103518 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0188636767E-002 | 3.3541523467E-002 | Pass | Pass | 3.0442710172E-002 | 0.1739489498 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.6192696355E-002 | 0.1144357496 | Pass | Pass | 2.9389779948E-002 | 0.1680320610 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1246257988 | 0.1410960093 | Pass | Pass | 3.6101052063E-002 | 0.2059160963 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.0249020411E-002 | 0.1011731238 | Pass | Pass | 2.7875210221E-002 | 0.1585582206 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.3492226929E-002 | 3.5029090750E-002 | Pass | Pass | 4.8972600404E-002 | 0.2133379888 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.4595463851E-002 | 0.1372790509 | Pass | Pass | 4.9420799431E-002 | 0.2179448792 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1645478073 | 0.1724891528 | Pass | Pass | 5.1550284484E-002 | 0.2140136689 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.9080609145E-002 | 0.1119696234 | Pass | Pass | 4.6465949810E-002 | 0.1994712074 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4101.66 | 127.85 | 0.00 | 1865.85 | 803.30 | 6898.66 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.51 | 0.0000 | Y | 4.86 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 3.07 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 4.79 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 3.04 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 4.85 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.45 | 0.0000 | Y | 3.07 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.20 | 0.0000 | Y | 4.79 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.20 | 0.0000 | Y | 3.03 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.51 | 0.0000 | Y | 4.86 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 3.07 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 4.79 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.23 | 0.0000 | Y | 3.04 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 166.65 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.26 | 42.26 | 4.30 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.67 | 62.97 | 3.31 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.67 | 46.88 | 26.42 | |
Exterior Lighting Total | 3824.74 | 34.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86431.37 | 69201.73 | 17229.64 | 0.80 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 83684.56 | 67002.48 | 16682.08 | 0.80 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97715.38 | 78236.33 | 19479.05 | 0.80 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 84944.1 | 2.92 | 9.95 | N/A | N/A | 11.70 | |
PACU_VAV_MID COOLING COIL | 82244.6 | 2.92 | 9.95 | N/A | N/A | 11.70 | |
PACU_VAV_TOP COOLING COIL | 96033.9 | 2.92 | 9.95 | N/A | N/A | 11.70 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 17257.56 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21218.68 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 38425.09 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17469.89 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11502.72 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17576.49 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11502.53 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13146.06 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8740.52 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13255.81 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8740.44 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13657.59 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9066.39 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13752.71 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9066.31 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 25134.16 | 0.84 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 25620.90 | 0.84 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 24672.34 | 0.84 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.22 | 11355.79 | 2174.89 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.06 | 10994.90 | 2174.89 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.90 | 12838.34 | 2174.89 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 84944.10 | 2.92 | 9.95 | 11.70 | 4.9020 | 3.35 | 11.44 | 3.8755 | 3.53 | 12.06 | 2.5980 | 3.69 | 12.59 | 1.1002 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 82244.55 | 2.92 | 9.95 | 11.70 | 4.7462 | 3.35 | 11.44 | 3.7523 | 3.53 | 12.06 | 2.5155 | 3.69 | 12.59 | 1.0653 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96033.94 | 2.92 | 9.95 | 11.70 | 5.5419 | 3.35 | 11.44 | 4.3815 | 3.53 | 12.06 | 2.9372 | 3.69 | 12.59 | 1.2439 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 32301.79 | 32301.79 | 32.84 | 2.867 | 2.867 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_MID | 27069.86 | 27069.86 | 27.52 | 2.401 | 2.401 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_TOP | 28592.59 | 28592.59 | 29.07 | 2.559 | 2.559 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00892 | 33.75 | 0.00548 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9131.51 | 9131.51 | 44.04 | 0.817 | 0.817 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00867 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10463.30 | 10463.30 | 79.71 | 0.937 | 0.937 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00859 | 26.18 | 0.00546 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12416.75 | 12416.75 | 59.89 | 1.111 | 1.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00863 | 33.53 | 0.00547 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12043.12 | 12043.12 | 91.75 | 1.078 | 1.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00858 | 32.03 | 0.00547 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6926.95 | 6926.95 | 33.41 | 0.620 | 0.620 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00879 | 33.90 | 0.00548 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8451.22 | 8451.22 | 64.38 | 0.756 | 0.756 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00865 | 26.60 | 0.00546 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9691.25 | 9691.25 | 46.74 | 0.867 | 0.867 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00871 | 33.53 | 0.00547 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9277.46 | 9277.46 | 70.68 | 0.830 | 0.830 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00864 | 31.09 | 0.00547 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7888.73 | 7888.73 | 38.05 | 0.706 | 0.706 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00872 | 33.90 | 0.00548 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10395.99 | 10395.99 | 79.20 | 0.930 | 0.930 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00860 | 25.29 | 0.00546 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11228.06 | 11228.06 | 54.15 | 1.005 | 1.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00866 | 33.28 | 0.00547 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11140.15 | 11140.15 | 84.88 | 0.997 | 0.997 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00860 | 31.83 | 0.00547 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8647.76 | 8647.76 | 8.79 | 0.457 | 0.457 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_MID | 14985.22 | 14985.22 | 15.24 | 0.783 | 0.783 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_TOP | 27035.08 | 27035.08 | 27.49 | 1.417 | 1.417 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12262.55 | 12262.55 | 59.14 | 0.644 | 0.644 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8073.44 | 8073.44 | 61.51 | 0.424 | 0.424 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12337.22 | 12337.22 | 59.50 | 0.648 | 0.648 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8073.30 | 8073.30 | 61.51 | 0.424 | 0.424 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9232.79 | 9232.79 | 44.53 | 0.485 | 0.485 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6137.88 | 6137.88 | 46.76 | 0.322 | 0.322 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9309.65 | 9309.65 | 44.90 | 0.489 | 0.489 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6137.82 | 6137.82 | 46.76 | 0.322 | 0.322 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9591.79 | 9591.79 | 46.26 | 0.504 | 0.504 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6366.60 | 6366.60 | 48.50 | 0.334 | 0.334 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9658.41 | 9658.41 | 46.58 | 0.507 | 0.507 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6366.54 | 6366.54 | 48.51 | 0.334 | 0.334 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -17.90 | 0.00096 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.22 | 5.22 | 2.06 | 2.06 | 5.2213 | 2.0605 | 5.2213 | 0.3946 | 0.3000 |
PACU_VAV_MID | 5.06 | 5.06 | 2.46 | 2.46 | 5.0554 | 2.4626 | 5.0554 | 0.4871 | 0.3000 |
PACU_VAV_TOP | 5.90 | 5.90 | 3.56 | 3.56 | 5.9030 | 3.5587 | 5.9030 | 0.6029 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17257.556 | 17257.556 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 17257.56 | 12382.77 | 0.456754 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 8647.76 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21218.680 | 21218.680 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21218.68 | 21218.68 | 0.782678 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 14985.22 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 38425.091 | 38425.091 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 38425.09 | 38425.09 | 1.417358 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 27035.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17469.885 | 17469.885 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17469.89 | 17469.89 | 0.644399 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776508 | 40.7652 | 12262.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11502.725 | 11502.725 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11502.72 | 11502.72 | 0.424293 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776235 | 40.7512 | 8073.44 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17576.486 | 17576.486 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17576.49 | 17576.49 | 0.648331 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776648 | 40.7725 | 12337.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11502.529 | 11502.529 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11502.53 | 11502.53 | 0.424285 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00776234 | 40.7511 | 8073.30 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13146.062 | 13146.062 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13146.06 | 13146.06 | 0.484909 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00782245 | 41.0615 | 9232.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8740.521 | 8740.521 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8740.52 | 8740.52 | 0.322405 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00782554 | 41.0775 | 6137.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13255.805 | 13255.805 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13255.81 | 13255.81 | 0.488957 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00782464 | 41.0729 | 9309.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8740.438 | 8740.438 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8740.44 | 8740.44 | 0.322402 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00782554 | 41.0776 | 6137.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 13657.594 | 13657.594 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13657.59 | 13657.59 | 0.503778 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00774518 | 40.6618 | 9591.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9066.391 | 9066.391 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9066.39 | 9066.39 | 0.334425 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00774604 | 40.6663 | 6366.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 13752.714 | 13752.714 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13752.71 | 13752.71 | 0.507286 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00774724 | 40.6724 | 9658.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9066.305 | 9066.305 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9066.31 | 9066.31 | 0.334422 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00774604 | 40.6663 | 6366.54 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 86431.369 | 69201.730 | 5.221319 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 84155.23 | 84155.23 | 5.221319 | 25.81 | 14.61 | 0.00820595 | 10.62 | 9.07 | 0.00820595 | 33.90 | 0.00547527 | 15.07 | 18.3115 | 24.00 | 0.00881824 | 38.5148 | 58318.57 | 0.00 | 89122.34 | 63483.16 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 25134.156 | 25134.156 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25134.16 | 25134.16 | 1.566396 | -3.54 | -3.54 | 0.00349998 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 61.0382 | 18.31 | 0.00748009 | 46.4247 | 13054.38 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 83684.556 | 67002.480 | 5.055384 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 81480.75 | 81480.75 | 5.055384 | 25.87 | 14.61 | 0.00818070 | 10.62 | 9.04 | 0.00818070 | 33.90 | 0.00547527 | 15.07 | 18.9125 | 24.00 | 0.00881294 | 38.4917 | 56390.02 | 0.00 | 86290.01 | 61465.65 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 25620.903 | 25620.903 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25620.90 | 25620.90 | 1.516615 | -4.40 | -4.40 | 0.00335217 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 63.0417 | 17.79 | 0.00747710 | 47.9636 | 12653.17 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 97715.382 | 78236.334 | 5.902986 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 95142.08 | 95142.08 | 5.902986 | 25.61 | 14.56 | 0.00822743 | 10.62 | 9.09 | 0.00822743 | 33.90 | 0.00547527 | 15.07 | 16.1969 | 24.00 | 0.00876095 | 38.2677 | 65783.33 | 0.00 | 100757.67 | 71771.18 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 24672.337 | 24672.337 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24672.34 | 24672.34 | 1.770896 | -1.38 | -1.64 | 0.00396848 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 53.9896 | 15.85 | 0.00761864 | 55.2674 | 12953.43 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 17257.556 | 17257.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 17257.56 | 12382.77 | 1.0000 | 0.44644860 | 0.456754 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17257.56 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 8647.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21218.680 | 21218.680 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21218.68 | 21218.68 | 1.0000 | 0.76501877 | 0.782678 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21218.68 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 14985.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 38425.091 | 38425.091 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 38425.09 | 38425.09 | 1.0000 | 1.38537913 | 1.417358 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38425.09 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 27035.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17469.885 | 17469.885 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17469.89 | 17469.89 | 1.0000 | 0.62985966 | 0.644399 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17469.89 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00776508 | 21.00 | 0.00776508 | 40.7652 | 12262.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11502.725 | 11502.725 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11502.72 | 11502.72 | 1.0000 | 0.41471951 | 0.424293 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11502.72 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00776235 | 21.00 | 0.00776235 | 40.7512 | 8073.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17576.486 | 17576.486 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17576.49 | 17576.49 | 1.0000 | 0.63370303 | 0.648331 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17576.49 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00776648 | 21.00 | 0.00776648 | 40.7725 | 12337.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11502.529 | 11502.529 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11502.53 | 11502.53 | 1.0000 | 0.41471244 | 0.424285 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11502.53 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00776234 | 21.00 | 0.00776234 | 40.7511 | 8073.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13146.062 | 13146.062 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13146.06 | 13146.06 | 1.0000 | 0.47396844 | 0.484909 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13146.06 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782245 | 21.00 | 0.00782245 | 41.0615 | 9232.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8740.521 | 8740.521 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8740.52 | 8740.52 | 1.0000 | 0.31513096 | 0.322405 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8740.52 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782554 | 21.00 | 0.00782554 | 41.0775 | 6137.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13255.805 | 13255.805 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13255.81 | 13255.81 | 1.0000 | 0.47792511 | 0.488957 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13255.81 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782464 | 21.00 | 0.00782464 | 41.0729 | 9309.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8740.438 | 8740.438 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8740.44 | 8740.44 | 1.0000 | 0.31512795 | 0.322402 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8740.44 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00782554 | 21.00 | 0.00782554 | 41.0776 | 6137.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13657.594 | 13657.594 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13657.59 | 13657.59 | 1.0000 | 0.49241120 | 0.503778 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13657.59 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774518 | 21.00 | 0.00774518 | 40.6618 | 9591.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9066.391 | 9066.391 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9066.39 | 9066.39 | 1.0000 | 0.32687989 | 0.334425 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9066.39 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774604 | 21.00 | 0.00774604 | 40.6663 | 6366.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13752.714 | 13752.714 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13752.71 | 13752.71 | 1.0000 | 0.49584067 | 0.507286 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13752.71 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774724 | 21.00 | 0.00774724 | 40.6724 | 9658.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9066.305 | 9066.305 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9066.31 | 9066.31 | 1.0000 | 0.32687679 | 0.334422 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9066.31 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774604 | 21.00 | 0.00774604 | 40.6663 | 6366.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86431.369 | 69201.730 | 5.221319 | -999.0 | -999.000 | -999.0000 | 1.09409 | 1.00000 | 1020.0944 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.221319 | 5.10351359 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 84155.23 | 84155.23 | 0.9737 | 5.10351359 | 5.221319 | 25.81 | 14.61 | 0.00820595 | 46853.6 | 10.62 | 9.07 | 0.00820595 | 31354.7 | -999.0 | -999.00 | -999.00 | -999.00 | 11355.786 | 72799.44 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 18.3115 | 24.00 | 0.00881824 | 24.00 | 0.00881824 | 38.5148 | 58318.57 | 0.00 | 89122.34 | 63483.16 | 4.90196338 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25134.156 | 25134.156 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.221319 | 5.10351359 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25134.16 | 25134.16 | 1.0000 | 1.53105408 | 1.566396 | -3.54 | -3.54 | 0.00349998 | 5176.2 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25134.16 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 61.0382 | 18.96 | 0.00748662 | 18.31 | 0.00748009 | 46.4247 | 13054.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 83684.556 | 67002.480 | 5.055384 | -999.0 | -999.000 | -999.0000 | 1.08986 | 1.00000 | 1020.0475 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.055384 | 4.94132250 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 81480.75 | 81480.75 | 0.9737 | 4.94132250 | 5.055384 | 25.87 | 14.61 | 0.00818070 | 46852.6 | 10.62 | 9.04 | 0.00818070 | 31291.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10994.896 | 70485.85 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 18.9125 | 24.00 | 0.00881294 | 24.00 | 0.00881294 | 38.4917 | 56390.02 | 0.00 | 86290.01 | 61465.65 | 4.74617761 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25620.903 | 25620.903 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.055384 | 4.94132250 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25620.90 | 25620.90 | 1.0000 | 1.48239675 | 1.516615 | -4.40 | -4.40 | 0.00335217 | 3935.0 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25620.90 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 63.0417 | 18.63 | 0.00744075 | 17.79 | 0.00747710 | 47.9636 | 12653.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97715.382 | 78236.334 | 5.902986 | -999.0 | -999.000 | -999.0000 | 1.10838 | 1.00000 | 1020.1344 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.902986 | 5.76980075 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 95142.08 | 95142.08 | 0.9737 | 5.76980075 | 5.902986 | 25.61 | 14.56 | 0.00822743 | 46698.6 | 10.62 | 9.09 | 0.00822743 | 31408.9 | -999.0 | -999.00 | -999.00 | -999.00 | 12838.336 | 82303.74 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 16.1969 | 24.00 | 0.00876095 | 24.00 | 0.00876095 | 38.2677 | 65783.33 | 0.00 | 100757.67 | 71771.18 | 5.54193723 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24672.337 | 24672.337 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.902986 | 5.76980075 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 04:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24672.34 | 24672.34 | 1.0000 | 1.73094022 | 1.770896 | -1.38 | -1.64 | 0.00396848 | 8523.2 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24672.34 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 53.9896 | 17.99 | 0.00750429 | 15.85 | 0.00761864 | 55.2674 | 12953.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.22 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.06 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1206.33 | 3154.00 | 51.50 |
CORE_MID | 1264.33 | 3648.50 | 318.33 |
CORE_TOP | 1821.50 | 3880.17 | 907.67 |
PERIMETER_TOP_ZN_3 | 2963.17 | 4018.17 | 1873.50 |
PERIMETER_TOP_ZN_2 | 2994.50 | 3560.83 | 1477.50 |
PERIMETER_TOP_ZN_1 | 2935.83 | 3089.33 | 1237.83 |
PERIMETER_TOP_ZN_4 | 3045.67 | 3646.50 | 1641.17 |
PERIMETER_BOT_ZN_3 | 2491.33 | 4122.50 | 1627.83 |
PERIMETER_BOT_ZN_2 | 2652.33 | 3456.00 | 1070.17 |
PERIMETER_BOT_ZN_1 | 2359.00 | 3142.00 | 850.00 |
PERIMETER_BOT_ZN_4 | 2553.33 | 3573.67 | 1138.83 |
PERIMETER_MID_ZN_3 | 2462.50 | 3896.17 | 1315.17 |
PERIMETER_MID_ZN_2 | 2334.83 | 2961.67 | 1025.00 |
PERIMETER_MID_ZN_1 | 2713.00 | 2832.00 | 872.50 |
PERIMETER_MID_ZN_4 | 2652.00 | 3457.83 | 1158.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4532.67 | 4492.33 | 2231.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.83 | 0.00 | 0.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 46.50 | 10.67 | 17.17 | 8.50 |
PERIMETER_TOP_ZN_2 | 35.67 | 44.00 | 4.83 | 41.33 |
PERIMETER_TOP_ZN_1 | 23.17 | 53.67 | 4.17 | 51.33 |
PERIMETER_TOP_ZN_4 | 35.17 | 42.50 | 6.00 | 30.50 |
PERIMETER_BOT_ZN_3 | 4.00 | 0.17 | 3.00 | 0.17 |
PERIMETER_BOT_ZN_2 | 1.17 | 30.67 | 0.00 | 30.50 |
PERIMETER_BOT_ZN_1 | 190.67 | 66.67 | 189.83 | 65.17 |
PERIMETER_BOT_ZN_4 | 1.00 | 26.67 | 0.00 | 18.67 |
PERIMETER_MID_ZN_3 | 5.00 | 4.33 | 2.17 | 3.67 |
PERIMETER_MID_ZN_2 | 4.33 | 41.00 | 0.50 | 40.17 |
PERIMETER_MID_ZN_1 | 1.83 | 68.00 | 0.33 | 67.00 |
PERIMETER_MID_ZN_4 | 4.00 | 37.67 | 0.67 | 27.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 241.17 | 213.50 | 203.17 | 192.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.820 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.654 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.646 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.750 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.276 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 1.381 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.125 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.618 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 1.089 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 1.065 | 0.858 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.919 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.732 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.194 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 1.363 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.092 | 0.073 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13062848.15 | 0.00 | 13062848.15 | 0.00 | 13062848.15 | 13393058.27 | 5238.74 | 548.25 | 2973.01 | 46.83 |
CORE_MID | 10450739.29 | 0.00 | 10450739.29 | 0.00 | 10450739.29 | 13393058.27 | 5606.04 | 900.10 | 2253.85 | 73.01 |
CORE_TOP | 10371236.53 | 0.00 | 10371236.53 | 0.00 | 10371236.53 | 13393058.27 | 5642.91 | 862.41 | 2254.68 | 113.66 |
PERIMETER_TOP_ZN_3 | 2537865.67 | 0.00 | 2537865.67 | 579019.07 | 3116884.74 | 2823374.22 | 4773.12 | 914.85 | 3072.03 | 113.66 |
PERIMETER_TOP_ZN_2 | 2717964.87 | 0.00 | 2717964.87 | 386010.39 | 3103975.26 | 1787429.43 | 4579.05 | 730.41 | 3450.54 | 113.63 |
PERIMETER_TOP_ZN_1 | 4643398.26 | 0.00 | 4643398.26 | 579019.07 | 5222417.33 | 2823374.22 | 4313.43 | 791.95 | 3654.62 | 113.66 |
PERIMETER_TOP_ZN_4 | 2412603.98 | 0.00 | 2412603.98 | 386010.39 | 2798614.38 | 1787312.18 | 4574.84 | 775.55 | 3409.62 | 113.63 |
PERIMETER_BOT_ZN_3 | 2085958.28 | 0.00 | 2085958.28 | 307860.96 | 2393819.24 | 2823374.22 | 5841.86 | 520.60 | 2397.55 | 46.83 |
PERIMETER_BOT_ZN_2 | 2314398.67 | 0.00 | 2314398.67 | 205239.41 | 2519638.08 | 1787429.43 | 5129.84 | 627.44 | 3002.73 | 46.83 |
PERIMETER_BOT_ZN_1 | 3582288.03 | 0.00 | 3582288.03 | 3038318.74 | 6620606.77 | 2823374.22 | 4716.46 | 484.77 | 3558.77 | 46.83 |
PERIMETER_BOT_ZN_4 | 1961147.90 | 0.00 | 1961147.90 | 205239.41 | 2166387.31 | 1787312.18 | 5282.24 | 644.07 | 2833.69 | 46.83 |
PERIMETER_MID_ZN_3 | 2468003.38 | 0.00 | 2468003.38 | 481988.59 | 2949991.98 | 2823374.22 | 4929.99 | 886.21 | 2943.80 | 73.01 |
PERIMETER_MID_ZN_2 | 2541789.16 | 0.00 | 2541789.16 | 321323.80 | 2863112.95 | 1601953.02 | 4469.17 | 857.65 | 3433.19 | 982.01 |
PERIMETER_MID_ZN_1 | 4575340.08 | 0.00 | 4575340.08 | 481988.59 | 5057328.67 | 2823374.22 | 4292.74 | 677.03 | 3790.23 | 73.01 |
PERIMETER_MID_ZN_4 | 2331792.20 | 0.00 | 2331792.20 | 321323.80 | 2653116.00 | 1787312.18 | 4723.21 | 940.15 | 3096.64 | 73.01 |
Total Facility | 68057374.43 | 0.00 | 68057374.43 | 7293342.22 | 75350716.65 | 67658168.57 | 6532.41 | 1403.45 | 4479.54 | 1067.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6067 | 0.0000 | 0.6067 | 0.0000 | 0.6067 | 0.4247 | 2455.74 | 548.25 | 2939.01 |
CORE_MID | 0.4840 | 0.0000 | 0.4840 | 0.0000 | 0.4840 | 0.4247 | 2827.73 | 900.02 | 2215.25 |
CORE_TOP | 0.4788 | 0.0000 | 0.4788 | 0.0000 | 0.4788 | 0.4247 | 2879.22 | 862.41 | 2201.36 |
PERIMETER_TOP_ZN_3 | 0.1173 | 0.0000 | 0.1173 | 0.0131 | 0.1304 | 0.0895 | 2009.44 | 914.85 | 3018.71 |
PERIMETER_TOP_ZN_2 | 0.1262 | 0.0000 | 0.1262 | 0.0087 | 0.1349 | 0.0567 | 1815.37 | 730.41 | 3397.22 |
PERIMETER_TOP_ZN_1 | 0.2157 | 0.0000 | 0.2157 | 0.0131 | 0.2288 | 0.0895 | 1549.74 | 791.95 | 3601.30 |
PERIMETER_TOP_ZN_4 | 0.1112 | 0.0000 | 0.1112 | 0.0087 | 0.1199 | 0.0567 | 1811.16 | 775.55 | 3356.30 |
PERIMETER_BOT_ZN_3 | 0.0967 | 0.0000 | 0.0967 | 0.0070 | 0.1036 | 0.0895 | 3058.86 | 520.60 | 2363.55 |
PERIMETER_BOT_ZN_2 | 0.1077 | 0.0000 | 0.1077 | 0.0046 | 0.1123 | 0.0567 | 2346.92 | 627.27 | 2968.80 |
PERIMETER_BOT_ZN_1 | 0.1666 | 0.0000 | 0.1666 | 0.1346 | 0.3011 | 0.0895 | 1933.48 | 484.77 | 3524.75 |
PERIMETER_BOT_ZN_4 | 0.0909 | 0.0000 | 0.0909 | 0.0046 | 0.0955 | 0.0567 | 2499.33 | 644.07 | 2799.60 |
PERIMETER_MID_ZN_3 | 0.1144 | 0.0000 | 0.1144 | 0.0109 | 0.1253 | 0.0895 | 2151.68 | 886.13 | 2905.19 |
PERIMETER_MID_ZN_2 | 0.1181 | 0.0000 | 0.1181 | 0.0078 | 0.1258 | 0.0567 | 1690.92 | 857.63 | 2485.46 |
PERIMETER_MID_ZN_1 | 0.2129 | 0.0000 | 0.2129 | 0.0109 | 0.2238 | 0.0895 | 1514.51 | 676.86 | 3751.63 |
PERIMETER_MID_ZN_4 | 0.1080 | 0.0000 | 0.1080 | 0.0073 | 0.1152 | 0.0567 | 1944.99 | 940.13 | 3057.89 |
Total Facility | 3.1552 | 0.0000 | 3.1552 | 0.2312 | 3.3864 | 2.1513 | 3735.53 | 1403.07 | 4410.92 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21980136.25 | 0.00 | 21980136.25 | 22614548.33 | 4953.13 | 288.47 | 3518.41 | 46.83 |
PACU_VAV_MID | 21369659.68 | 0.00 | 21369659.68 | 22429071.92 | 5259.20 | 67.02 | 3433.78 | 73.01 |
PACU_VAV_TOP | 21670958.54 | 0.00 | 21670958.54 | 22614548.33 | 5247.58 | 88.59 | 3423.83 | 111.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.0209 | 0.0000 | 1.0209 | 0.7171 | 2170.13 | 288.47 | 3484.41 |
PACU_VAV_MID | 0.9912 | 0.0000 | 0.9912 | 0.7084 | 2480.64 | 66.96 | 3395.40 |
PACU_VAV_TOP | 1.0024 | 0.0000 | 1.0024 | 0.7171 | 2483.90 | 88.42 | 3370.68 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 478.66 | 2208.49 | 0.00 | 0.00 | 0.00 | 2155.89 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 391.91 | 2242.22 | 0.00 | 0.00 | 0.00 | 2273.88 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 300.48 | 2319.42 | 0.00 | 0.00 | 0.00 | 2327.41 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.9001 | 1.8629 | 0.0000 | 0.0000 | 0.0000 | 0.7472 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.8978 | 1.7884 | 0.0000 | 0.0000 | 0.0000 | 0.7294 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.8945 | 1.8038 | 0.0000 | 0.0000 | 0.0000 | 0.7337 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1219.82 | 11240.73 | 14-MAY-17:10 | 188377.46 | 06-FEB-07:10 |
Electricity:Building | 814.40 | 11072.20 | 14-MAY-17:10 | 57051.52 | 21-DEC-08:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 814.40 | 11072.20 | 14-MAY-17:10 | 57051.52 | 21-DEC-08:10 |
InteriorLights:Electricity | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 166.65 | 772.31 | 01-JAN-09:00 | 17672.30 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.19 | 405.59 | 09-APR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.48 | 256.76 | 14-MAY-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.13 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.44 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.18 | 405.59 | 09-APR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.85 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.85 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.47 | 256.76 | 14-MAY-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.12 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.43 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.03 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.03 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.19 | 405.59 | 09-APR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.86 | 19.49 | 01-JAN-09:00 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.48 | 256.76 | 14-MAY-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.07 | 12.34 | 01-JAN-07:50 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.13 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.79 | 19.49 | 01-JAN-07:50 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.44 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.04 | 12.34 | 01-JAN-09:00 | 465.57 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 155.68 | -0.00 | 13-FEB-17:20 | 26811.28 | 26-APR-12:30 |
ElectricityProduced:Plant | 155.68 | -0.00 | 13-FEB-17:20 | 26811.28 | 26-APR-12:30 |
Photovoltaic:ElectricityProduced | 162.61 | 0.00 | 01-JAN-00:10 | 27928.39 | 26-APR-12:30 |
PowerConversion:ElectricityProduced | -6.94 | -1117.11 | 26-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 371.24 | 168.34 | 01-JAN-00:10 | 164133.82 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.65 | 02-JAN-17:00 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.65 | 02-JAN-17:00 |
ElectricityPurchased:Facility | 1065.16 | 0.00 | 15-JAN-11:20 | 188377.46 | 06-FEB-07:10 |
ElectricityPurchased:Plant | 1065.16 | 0.00 | 15-JAN-11:20 | 188377.46 | 06-FEB-07:10 |
Cogeneration:ElectricityPurchased | 1065.16 | 0.00 | 15-JAN-11:20 | 188377.46 | 06-FEB-07:10 |
General:Cogeneration:ElectricityPurchased | 1065.16 | 0.00 | 15-JAN-11:20 | 188377.46 | 06-FEB-07:10 |
ElectricitySurplusSold:Facility | 1.02 | 0.00 | 01-JAN-00:10 | 11051.80 | 09-APR-11:30 |
ElectricitySurplusSold:Plant | 1.02 | 0.00 | 01-JAN-00:10 | 11051.80 | 09-APR-11:30 |
Cogeneration:ElectricitySurplusSold | 1.02 | 0.00 | 01-JAN-00:10 | 11051.80 | 09-APR-11:30 |
General:Cogeneration:ElectricitySurplusSold | 1.02 | 0.00 | 01-JAN-00:10 | 11051.80 | 09-APR-11:30 |
ElectricityNet:Facility | 1064.14 | -11051.80 | 09-APR-11:30 | 188377.46 | 06-FEB-07:10 |
ElectricityNet:Plant | 1064.14 | -11051.80 | 09-APR-11:30 | 188377.46 | 06-FEB-07:10 |
Cogeneration:ElectricityNet | 1064.14 | -11051.80 | 09-APR-11:30 | 188377.46 | 06-FEB-07:10 |
General:Cogeneration:ElectricityNet | 1064.14 | -11051.80 | 09-APR-11:30 | 188377.46 | 06-FEB-07:10 |
Heating:Electricity | 101.14 | 0.00 | 01-JAN-00:10 | 158129.76 | 06-FEB-07:10 |
General:Heating:Electricity | 101.14 | 0.00 | 01-JAN-00:10 | 158129.76 | 06-FEB-07:10 |
Fans:Electricity | 104.24 | 0.00 | 01-JAN-00:10 | 32342.68 | 24-JUL-15:20 |
General:Fans:Electricity | 104.24 | 0.00 | 01-JAN-00:10 | 32342.68 | 24-JUL-15:20 |
ExteriorLights:Electricity | 34.03 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.03 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 154.25 | 0.00 | 01-JAN-00:10 | 75231.58 | 26-JUN-15:10 |
General:Cooling:Electricity | 154.25 | 0.00 | 01-JAN-00:10 | 75231.58 | 26-JUN-15:10 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 4.68 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 302.12 | 1886.44 | 18-JAN-06:20 | 99260.88 | 21-DEC-09:20 |
NaturalGas:HVAC | 168.29 | 0.00 | 01-JAN-00:10 | 89794.52 | 21-DEC-08:10 |
Heating:NaturalGas | 168.29 | 0.00 | 01-JAN-00:10 | 89794.52 | 21-DEC-08:10 |
General:Heating:NaturalGas | 168.29 | 0.00 | 01-JAN-00:10 | 89794.52 | 21-DEC-08:10 |
NaturalGas:Plant | 133.83 | 1886.44 | 10-JAN-17:10 | 10526.48 | 06-FEB-12:30 |
WaterSystems:NaturalGas | 133.83 | 1886.44 | 10-JAN-17:10 | 10526.48 | 06-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 133.83 | 1886.44 | 10-JAN-17:10 | 10526.48 | 06-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1933.90 | 0.00 | 01-JAN-00:10 | 386844.35 | 26-JUN-15:10 |
EnergyTransfer:Building | 1017.51 | 0.00 | 01-JAN-00:10 | 159843.16 | 26-JUN-15:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 173.19 | 0.00 | 01-JAN-00:10 | 22825.58 | 05-SEP-08:00 |
Heating:EnergyTransfer | 99.26 | 0.00 | 01-JAN-00:10 | 147372.71 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 3317.59 | 26-DEC-07:10 |
General:Heating:EnergyTransfer | 99.26 | 0.00 | 01-JAN-00:10 | 147372.71 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 3317.59 | 26-DEC-07:10 |
Cooling:EnergyTransfer | 918.25 | 0.00 | 01-JAN-00:10 | 159843.16 | 26-JUN-15:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 173.18 | 0.00 | 01-JAN-00:10 | 22825.58 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 918.25 | 0.00 | 01-JAN-00:10 | 159843.16 | 26-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 173.18 | 0.00 | 01-JAN-00:10 | 22825.58 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.89 | 0.00 | 01-JAN-00:10 | 12992.43 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.07 | 0.00 | 01-JAN-00:10 | 12992.43 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 16.07 | 0.00 | 01-JAN-00:10 | 12992.43 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.83 | 0.00 | 01-JAN-00:10 | 11456.35 | 26-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.83 | 0.00 | 01-JAN-00:10 | 11456.35 | 26-JUN-13:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.15 | 0.00 | 01-JAN-00:10 | 6194.39 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.54 | 0.00 | 01-JAN-00:10 | 6194.39 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.54 | 0.00 | 01-JAN-00:10 | 6194.39 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.61 | 0.00 | 01-JAN-00:10 | 5286.32 | 17-JUL-10:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.61 | 0.00 | 01-JAN-00:10 | 5286.32 | 17-JUL-10:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 22.31 | 0.00 | 01-JAN-00:10 | 5165.96 | 17-JUL-12:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.59 | 0.00 | 01-JAN-00:10 | 3352.86 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.59 | 0.00 | 01-JAN-00:10 | 3352.86 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.72 | 0.00 | 01-JAN-00:10 | 5165.96 | 17-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.72 | 0.00 | 01-JAN-00:10 | 5165.96 | 17-JUL-12:20 |
EnergyTransfer:Zone:CORE_MID | 130.79 | 0.00 | 01-JAN-00:10 | 18653.92 | 17-JUL-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.45 | 0.00 | 01-JAN-00:10 | 14852.82 | 26-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.45 | 0.00 | 01-JAN-00:10 | 14852.82 | 26-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 130.34 | 0.00 | 01-JAN-00:10 | 18653.92 | 17-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 130.34 | 0.00 | 01-JAN-00:10 | 18653.92 | 17-JUL-07:20 |
EnergyTransfer:Zone:CORE_TOP | 126.47 | 0.00 | 01-JAN-00:10 | 26407.04 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.72 | 0.00 | 01-JAN-00:10 | 26407.04 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.72 | 0.00 | 01-JAN-00:10 | 26407.04 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 121.75 | 0.00 | 01-JAN-00:10 | 19747.01 | 26-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 121.75 | 0.00 | 01-JAN-00:10 | 19747.01 | 26-JUN-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.53 | 0.00 | 01-JAN-00:10 | 9107.77 | 23-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 10.91 | 0.00 | 01-JAN-00:10 | 9107.77 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 10.91 | 0.00 | 01-JAN-00:10 | 9107.77 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.62 | 0.00 | 01-JAN-00:10 | 7648.28 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.62 | 0.00 | 01-JAN-00:10 | 7648.28 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.24 | 0.00 | 01-JAN-00:10 | 9757.93 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.78 | 0.00 | 01-JAN-00:10 | 8332.30 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.78 | 0.00 | 01-JAN-00:10 | 8332.30 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 32.46 | 0.00 | 01-JAN-00:10 | 9757.93 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 32.46 | 0.00 | 01-JAN-00:10 | 9757.93 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 65.58 | 0.00 | 01-JAN-00:10 | 13365.55 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.07 | 0.00 | 01-JAN-00:10 | 11486.69 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.07 | 0.00 | 01-JAN-00:10 | 11486.69 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.51 | 0.00 | 01-JAN-00:10 | 13365.55 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.51 | 0.00 | 01-JAN-00:10 | 13365.55 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.69 | 0.00 | 01-JAN-00:10 | 10441.56 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.30 | 0.00 | 01-JAN-00:10 | 8380.35 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.30 | 0.00 | 01-JAN-00:10 | 8380.35 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.39 | 0.00 | 01-JAN-00:10 | 10441.56 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.39 | 0.00 | 01-JAN-00:10 | 10441.56 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.15 | 0.00 | 01-JAN-00:10 | 6413.67 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.25 | 0.00 | 01-JAN-00:10 | 6413.67 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.25 | 0.00 | 01-JAN-00:10 | 6413.67 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.90 | 0.00 | 01-JAN-00:10 | 6128.93 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.90 | 0.00 | 01-JAN-00:10 | 6128.93 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.84 | 0.00 | 01-JAN-00:10 | 7851.18 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.21 | 0.00 | 01-JAN-00:10 | 5538.91 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.21 | 0.00 | 01-JAN-00:10 | 5538.91 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.63 | 0.00 | 01-JAN-00:10 | 7851.18 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.63 | 0.00 | 01-JAN-00:10 | 7851.18 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.94 | 0.00 | 01-JAN-00:10 | 12445.19 | 21-DEC-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 13.06 | 0.00 | 01-JAN-00:10 | 12445.19 | 21-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 13.06 | 0.00 | 01-JAN-00:10 | 12445.19 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 45.89 | 0.00 | 01-JAN-00:10 | 11081.05 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 45.89 | 0.00 | 01-JAN-00:10 | 11081.05 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.60 | 0.00 | 01-JAN-00:10 | 8083.91 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.30 | 0.00 | 01-JAN-00:10 | 5524.55 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.30 | 0.00 | 01-JAN-00:10 | 5524.55 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.30 | 0.00 | 01-JAN-00:10 | 8083.91 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.30 | 0.00 | 01-JAN-00:10 | 8083.91 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 34.20 | 0.00 | 01-JAN-00:10 | 7296.51 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.47 | 0.00 | 01-JAN-00:10 | 7296.51 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.47 | 0.00 | 01-JAN-00:10 | 7296.51 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.73 | 0.00 | 01-JAN-00:10 | 7115.56 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.73 | 0.00 | 01-JAN-00:10 | 7115.56 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.42 | 0.00 | 01-JAN-00:10 | 9662.80 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.38 | 0.00 | 01-JAN-00:10 | 5658.01 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.38 | 0.00 | 01-JAN-00:10 | 5658.01 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.03 | 0.00 | 01-JAN-00:10 | 9662.80 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.03 | 0.00 | 01-JAN-00:10 | 9662.80 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.91 | 0.00 | 01-JAN-00:10 | 12407.25 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.65 | 0.00 | 01-JAN-00:10 | 8490.43 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.65 | 0.00 | 01-JAN-00:10 | 8490.43 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 61.26 | 0.00 | 01-JAN-00:10 | 12407.25 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 61.26 | 0.00 | 01-JAN-00:10 | 12407.25 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.61 | 0.00 | 01-JAN-00:10 | 9914.16 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.51 | 0.00 | 01-JAN-00:10 | 5699.09 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.51 | 0.00 | 01-JAN-00:10 | 5699.09 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.10 | 0.00 | 01-JAN-00:10 | 9914.16 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.10 | 0.00 | 01-JAN-00:10 | 9914.16 | 16-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 51.77 | 0.00 | 01-JAN-00:10 | 6543.35 | 14-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 51.77 | 0.00 | 01-JAN-00:10 | 6543.35 | 14-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 51.77 | 0.00 | 01-JAN-00:10 | 6543.35 | 14-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 51.77 | 0.00 | 01-JAN-00:10 | 6543.35 | 14-FEB-12:10 |
EnergyTransfer:HVAC | 864.63 | 0.00 | 01-JAN-00:10 | 222830.91 | 26-JUN-15:10 |
HeatingCoils:EnergyTransfer | 242.50 | 0.00 | 01-JAN-00:10 | 213732.56 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 622.13 | 0.00 | 01-JAN-00:10 | 222830.91 | 26-JUN-15:10 |
EnergyTransfer:Plant | 51.77 | 0.00 | 01-JAN-00:10 | 6543.35 | 14-FEB-12:10 |
WaterSystems:EnergyTransfer | 51.77 | 0.00 | 01-JAN-00:10 | 6543.35 | 14-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 51.77 | 0.00 | 01-JAN-00:10 | 6543.35 | 14-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.005 | -173.184 | 0.000 | 0.000 | 32.968 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -78.068 |
CORE_MID | 0.000 | 0.000 | 0.448 | -130.338 | 0.000 | 0.000 | 33.834 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -59.165 |
CORE_TOP | 0.000 | 0.000 | 4.717 | -121.753 | 0.000 | 0.000 | 34.522 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -72.706 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 10.906 | -28.619 | 0.000 | 0.000 | 7.477 | 4.860 | 24.333 | 20.604 | 0.000 | 0.156 | 3.632 | 0.000 | -35.986 | 0.000 | -7.363 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.783 | -32.460 | 0.000 | 0.000 | 4.601 | 3.072 | 15.404 | 46.289 | 0.000 | 0.101 | 0.000 | 0.000 | -23.244 | 0.000 | -5.037 | -14.507 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 7.067 | -58.513 | 0.000 | 0.000 | 7.184 | 4.795 | 24.332 | 95.937 | 0.000 | 0.152 | 0.000 | 0.000 | -35.111 | 0.000 | -7.744 | -38.100 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 6.303 | -30.391 | 0.000 | 0.000 | 4.665 | 3.036 | 15.403 | 42.509 | 0.000 | 0.100 | 0.001 | 0.000 | -23.865 | 0.000 | -5.050 | -12.710 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 5.247 | -23.901 | 0.000 | 0.000 | 7.484 | 4.851 | 24.333 | 21.050 | 0.000 | 0.091 | 1.760 | 0.000 | -36.866 | 0.000 | -4.051 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.211 | -29.625 | 0.000 | 0.000 | 4.577 | 3.067 | 15.404 | 46.515 | 0.000 | 0.055 | 0.001 | 0.000 | -24.374 | 0.000 | -2.839 | -14.991 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 13.055 | -45.887 | 0.000 | 0.000 | 7.290 | 4.789 | 24.332 | 96.651 | 0.000 | 2.340 | 0.004 | 0.000 | -37.219 | 0.000 | -34.175 | -31.175 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.300 | -26.301 | 0.000 | 0.000 | 4.627 | 3.031 | 15.403 | 42.791 | 0.000 | 0.055 | 0.000 | 0.000 | -25.056 | 0.000 | -2.845 | -14.006 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 4.472 | -29.730 | 0.000 | 0.000 | 7.398 | 4.860 | 24.333 | 20.418 | 0.000 | 0.133 | 12.310 | 0.000 | -37.761 | 0.000 | -6.432 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.384 | -32.032 | 0.000 | 0.000 | 3.365 | 3.072 | 15.404 | 46.047 | 0.000 | 0.083 | 0.001 | 0.000 | -24.343 | 0.000 | -4.398 | -9.582 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.653 | -61.255 | 0.000 | 0.000 | 7.114 | 4.795 | 24.332 | 95.715 | 0.000 | 0.128 | 0.002 | 0.000 | -36.776 | 0.000 | -6.755 | -29.950 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.507 | -31.100 | 0.000 | 0.000 | 4.614 | 3.036 | 15.403 | 42.392 | 0.000 | 0.085 | 0.001 | 0.000 | -25.041 | 0.000 | -4.408 | -7.487 |
TOPFLOOR_PLENUM | 16.068 | -30.825 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.161 | 25.967 | 0.000 | 0.000 | 0.000 | -11.370 | -0.000 |
MIDFLOOR_PLENUM | 8.542 | -14.609 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.198 | 17.093 | 0.000 | 0.000 | 0.000 | -11.223 | -0.002 |
FIRSTFLOOR_PLENUM | 4.594 | -17.718 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.155 | 21.945 | 0.000 | 0.000 | 0.000 | -8.976 | -0.000 |
Total Facility | 29.203 | -63.151 | 70.057 | -855.091 | 0.000 | 0.000 | 171.719 | 166.649 | 647.750 | 616.919 | 0.000 | 3.994 | 82.716 | 0.000 | -365.644 | 0.000 | -122.667 | -382.449 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -34433.54 | 0.00 | 0.00 | 312.88 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 29684.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -30167.77 | 0.00 | 0.00 | 316.20 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 26438.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-05:12 | 0.00 | 0.00 | 0.00 | -31036.59 | 0.00 | 0.00 | 322.58 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 27300.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-14:32 | 0.00 | 0.00 | 0.00 | -11162.47 | 0.00 | 0.00 | 24.76 | 19.49 | 478.42 | 5418.08 | 0.00 | 399.94 | 4821.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:12 | 0.00 | 0.00 | 0.00 | -13542.62 | 0.00 | 0.00 | 13.05 | 12.34 | 302.86 | 10614.07 | 0.00 | 0.00 | 2623.68 | 0.00 | -0.00 | 0.00 | -23.37 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:21 | 0.00 | 0.00 | 0.00 | -17994.25 | 0.00 | 0.00 | 20.15 | 19.49 | 478.41 | 16770.08 | 0.00 | 0.00 | 804.87 | 0.00 | -0.00 | 0.00 | -98.75 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-OCT-16:01 | 0.00 | 0.00 | 0.00 | -15999.10 | 0.00 | 0.00 | 13.78 | 12.34 | 302.86 | 11017.13 | 0.00 | 0.00 | 4734.71 | 0.00 | -0.00 | 0.00 | -81.70 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6953.56 | 0.00 | 0.00 | 144.48 | 116.94 | 637.89 | 2814.48 | 0.00 | 0.00 | 3247.10 | 0.00 | -0.00 | 0.00 | -7.31 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-09:01 | 0.00 | 0.00 | 0.00 | -11470.92 | 0.00 | 0.00 | 15.14 | 12.34 | 302.86 | 11140.62 | 0.00 | 0.00 | 17.27 | 0.00 | -0.00 | 0.00 | -17.31 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-13:21 | 0.00 | 0.00 | 0.00 | -13955.80 | 0.00 | 0.00 | 21.23 | 19.49 | 478.41 | 16833.12 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -51.35 | -3345.11 |
PERIMETER_BOT_ZN_4 | 13-AUG-17:41 | 0.00 | 0.00 | 0.00 | -12897.80 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 9591.14 | 0.00 | 0.00 | 3075.48 | 0.00 | -0.00 | 0.00 | -25.58 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:42 | 0.00 | 0.00 | 0.00 | -9590.14 | 0.00 | 0.00 | 26.81 | 19.49 | 478.42 | 5515.03 | 0.00 | 294.82 | 3255.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:01 | 0.00 | 0.00 | 0.00 | -14801.18 | 0.00 | 0.00 | 12.93 | 12.34 | 302.86 | 11044.24 | 0.00 | 0.00 | 3463.96 | 0.00 | -0.00 | 0.00 | -35.15 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:41 | 0.00 | 0.00 | 0.00 | -15727.63 | 0.00 | 0.00 | 21.73 | 19.49 | 478.41 | 14644.92 | 0.00 | 0.00 | 585.88 | 0.00 | -0.00 | 0.00 | -22.79 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-16:21 | 0.00 | 0.00 | 0.00 | -15946.95 | 0.00 | 0.00 | 11.04 | 12.34 | 302.86 | 12253.48 | 0.00 | 53.14 | 3314.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:20 | 0.00 | -11455.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 11388.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-10:10 | 0.00 | -5463.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 | 5372.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:08 | 0.00 | -5655.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 | 5594.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-06:03 | 0.00 | -7488.24 | 0.00 | -171654.43 | 0.00 | 0.00 | 3474.35 | 4634.49 | 18346.02 | 35410.74 | 0.00 | 0.00 | 118513.32 | 0.00 | 0.00 | 0.00 | -1236.25 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 06-FEB-07:01 | 0.00 | 0.00 | 11774.74 | 0.00 | 0.00 | 0.00 | 883.47 | 1162.90 | 6044.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19865.13 |
CORE_MID | 26-DEC-06:11 | 0.00 | 0.00 | 18203.12 | 0.00 | 0.00 | 0.00 | 494.12 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22110.79 |
CORE_TOP | 06-FEB-05:11 | 0.00 | 0.00 | 30021.67 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32675.46 |
PERIMETER_TOP_ZN_3 | 24-DEC-07:12 | 0.00 | 0.00 | 10559.23 | 0.00 | 0.00 | 0.00 | 60.37 | 40.85 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3754.31 | 0.00 | -1452.00 | -5932.56 |
PERIMETER_TOP_ZN_2 | 24-DEC-07:12 | 0.00 | 0.00 | 11850.27 | 0.00 | 0.00 | 0.00 | 38.32 | 25.86 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2572.16 | 0.00 | -984.13 | -8661.03 |
PERIMETER_TOP_ZN_1 | 24-DEC-07:12 | 0.00 | 0.00 | 14142.99 | 0.00 | 0.00 | 0.00 | 60.26 | 40.85 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3886.63 | 0.00 | -1469.60 | -9366.28 |
PERIMETER_TOP_ZN_4 | 24-DEC-07:12 | 0.00 | 0.00 | 12197.79 | 0.00 | 0.00 | 0.00 | 38.27 | 25.86 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2502.61 | 0.00 | -987.20 | -9074.98 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 7385.85 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2950.39 | 0.00 | -386.50 | -4645.48 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 8570.91 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1959.02 | 0.00 | -260.27 | -6729.24 |
PERIMETER_BOT_ZN_1 | 21-DEC-08:00 | 0.00 | 0.00 | 12444.65 | 0.00 | 0.00 | 0.00 | 251.00 | 216.53 | 637.88 | 0.00 | 0.00 | 0.00 | 14944.67 | 0.00 | -4646.50 | 0.00 | -23848.24 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 8550.95 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2001.88 | 0.00 | -260.34 | -6666.35 |
PERIMETER_MID_ZN_3 | 24-DEC-07:02 | 0.00 | 0.00 | 8553.94 | 0.00 | 0.00 | 0.00 | 58.82 | 40.85 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3979.23 | 0.00 | -1425.91 | -3726.88 |
PERIMETER_MID_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 8915.70 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1945.09 | 0.00 | -406.75 | -6941.48 |
PERIMETER_MID_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 11920.02 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2996.75 | 0.00 | -608.17 | -8911.61 |
PERIMETER_MID_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 8914.08 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1990.37 | 0.00 | -406.46 | -6894.87 |
TOPFLOOR_PLENUM | 23-DEC-06:13 | 15402.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -645.09 | -14757.28 |
MIDFLOOR_PLENUM | 06-FEB-07:11 | 7456.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -308.97 | -7147.24 |
FIRSTFLOOR_PLENUM | 17-DEC-12:42 | 4037.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -280.72 | -3756.74 |
Total Facility | 06-FEB-07:01 | 21113.45 | 0.00 | 149983.90 | 0.00 | 0.00 | 0.00 | 4615.18 | 5890.77 | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32555.73 | 0.00 | -24074.91 | -143318.67 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.9417 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2213 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.0399 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0554 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.5025 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9030 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9709 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0750 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.0199 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0746 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.2512 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0762 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8674 | 2.8674 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4012 | 2.4012 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5593 | 2.5593 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8173 | 0.8173 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9365 | 0.9365 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1114 | 1.1114 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0779 | 1.0779 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6200 | 0.6200 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7564 | 0.7564 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8674 | 0.8674 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8304 | 0.8304 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7061 | 0.7061 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9305 | 0.9305 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0050 | 1.0050 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9971 | 0.9971 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.9417 | 5.2213 | 5.9417 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.0399 | 5.0554 | 6.0399 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.5025 | 5.9030 | 6.5025 | 1.0762 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4337 | 1.4337 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2006 | 1.2006 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2797 | 1.2797 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4087 | 0.4087 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4683 | 0.4683 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5557 | 0.5557 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5390 | 0.5390 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3100 | 0.3100 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3782 | 0.3782 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4337 | 0.4337 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4152 | 0.4152 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3530 | 0.3530 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4652 | 0.4652 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5025 | 0.5025 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4986 | 0.4986 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9709 | 1.0750 | 1.0750 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.0199 | 1.0746 | 1.0746 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.2512 | 1.0762 | 1.0762 | 1.0762 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 203.17 |
Number of hours cooling loads not met | 192.83 |
Number of hours not met | 396.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 101.14 | 158129.76 | 168.29 | 89794.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 154.25 | 75231.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 166.65 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.03 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 828.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 104.24 | 32342.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 133.83 | 10526.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1219.82 |
Natural Gas | 0.00 | 302.12 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1521.94 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 162.61 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.45 |
Space Heating | 20.30 |
Space Cooling | 30.96 |
Fans (All) | 20.92 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 244.84 |
Subtotal | 244.84 |
Natural Gas [MJ/m2] | |
Space Heating | 33.78 |
Service Water Heating | 26.86 |
Miscellaneous (All) | 60.64 |
Subtotal | 60.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.95 |
Space Heating | 17.70 |
Space Cooling | 10.13 |
Fans (All) | 6.85 |
Service Water Heating | 8.79 |
Receptacle Equipment | 42.56 |
Miscellaneous | 3.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 721. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8729.83 | 30.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8663.33 | 96.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8663.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 96.67 | 0.00 | 0.00 | 0.00 |
Average | 8743.44 | 16.56 | 0.00 | 0.00 | 0.00 |
Sum | 157381.83 | 298.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8723.67 | 36.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8726.67 | 33.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8739.83 | 20.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8722.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 37.50 | 0.00 | 0.00 | 0.00 |
Average | 8742.62 | 17.38 | 0.00 | 0.00 | 0.00 |
Sum | 157367.17 | 312.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128291.33 | 12.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128298.67 | 5.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128303.67 | 12.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.31 | 1.02 | 0.00 | 0.00 | 0.00 |
Sum | 614561.67 | 18.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908515E+10 | 13775.61 | 26-JAN-16:40 | 6.67 | 2.08 | 0.193848E+10 | 2606.62 | 10-JAN-10:00 | 6.67 | 2.08 |
February | 0.811603E+10 | 13175.52 | 22-FEB-08:06 | 0.50 | 0.30 | 0.173758E+10 | 2606.64 | 23-FEB-10:20 | 4.67 | 3.22 |
March | 0.116717E+11 | 25452.13 | 15-MAR-06:02 | 10.00 | 2.57 | 0.212137E+10 | 2606.64 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.102948E+11 | 14584.92 | 13-APR-13:00 | 18.00 | 9.26 | 0.189577E+10 | 2606.75 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.161478E+11 | 24733.60 | 22-MAY-06:03 | 11.17 | 10.50 | 0.207412E+10 | 2606.69 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.210473E+11 | 33139.32 | 26-JUN-05:12 | 17.53 | 11.60 | 0.206980E+10 | 2606.68 | 08-JUN-13:09 | 17.53 | 11.60 |
July | 0.206232E+11 | 34076.99 | 24-JUL-05:12 | 18.00 | 14.77 | 0.192383E+10 | 2606.67 | 14-JUL-09:30 | 18.00 | 14.77 |
August | 0.220637E+11 | 34173.63 | 28-AUG-05:12 | 15.00 | 14.37 | 0.215994E+10 | 2606.68 | 10-AUG-09:39 | 15.00 | 14.37 |
September | 0.195413E+11 | 34436.16 | 05-SEP-05:12 | 14.20 | 8.43 | 0.191757E+10 | 2606.87 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.149848E+11 | 32338.96 | 10-OCT-06:01 | 8.33 | 4.27 | 0.198552E+10 | 2606.64 | 03-OCT-13:20 | 8.33 | 4.27 |
November | 0.111200E+11 | 20908.51 | 09-NOV-07:01 | 10.17 | 5.62 | 0.195533E+10 | 2606.64 | 29-NOV-10:30 | -9.0 | -9.0 |
December | 0.848842E+10 | 12904.65 | 05-DEC-08:06 | -0.8 | -3.2 | 0.184718E+10 | 2606.63 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.173184E+12 | 0.236265E+11 | ||||||||
Minimum of Months | 0.811603E+10 | 12904.65 | -0.8 | -3.2 | 0.173758E+10 | 2606.62 | -9.0 | -9.0 | ||
Maximum of Months | 0.220637E+11 | 34436.16 | 18.00 | 14.77 | 0.215994E+10 | 2606.87 | 18.00 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208511E+09 | 2765.16 | 20-JAN-15:05 | 19.67 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 19.67 | 6.93 |
February | 0.289175E+09 | 2865.49 | 18-FEB-14:30 | 19.50 | 7.87 | 0.00 | 0.00 | 01-FEB-00:10 | 19.50 | 7.87 |
March | 0.113529E+10 | 6714.08 | 14-MAR-14:05 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.115334E+10 | 5992.03 | 21-APR-13:30 | 15.50 | 6.04 | 0.00 | 0.00 | 01-APR-00:10 | 15.50 | 6.04 |
May | 0.291214E+10 | 8367.02 | 31-MAY-14:30 | 28.00 | 14.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.75 |
June | 0.672390E+10 | 11456.35 | 26-JUN-13:20 | 36.97 | 15.36 | 0.00 | 0.00 | 01-JUN-00:10 | 36.97 | 15.36 |
July | 0.616064E+10 | 9947.79 | 17-JUL-14:00 | 35.00 | 14.93 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 14.93 |
August | 0.626023E+10 | 11154.35 | 16-AUG-15:00 | 36.00 | 16.15 | 0.00 | 0.00 | 01-AUG-00:10 | 36.00 | 16.15 |
September | 0.400851E+10 | 8422.25 | 12-SEP-14:20 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.140145E+10 | 6503.93 | 11-OCT-15:00 | 26.00 | 9.46 | 0.00 | 0.00 | 01-OCT-00:10 | 26.00 | 9.46 |
November | 0.456713E+09 | 3934.54 | 09-NOV-13:05 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.115730E+09 | 1650.86 | 01-DEC-14:30 | 21.50 | 7.65 | 0.00 | 0.00 | 01-DEC-00:10 | 21.50 | 7.65 |
Annual Sum or Average | 0.308256E+11 | 0.00 | ||||||||
Minimum of Months | 0.115730E+09 | 1650.86 | 15.50 | 6.04 | 0.00 | 0.00 | 15.50 | 6.04 | ||
Maximum of Months | 0.672390E+10 | 11456.35 | 36.97 | 16.15 | 0.00 | 0.00 | 36.97 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58997743.50 | 2913.88 | 05-JAN-05:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 48847974.37 | 2422.70 | 10-FEB-06:01 | -8.2 | -9.1 | 0.00 | 0.00 | 01-FEB-00:10 | -8.2 | -9.1 |
March | 0.318612E+09 | 2490.09 | 15-MAR-16:00 | 19.00 | 5.38 | 0.00 | 0.00 | 01-MAR-00:10 | 19.00 | 5.38 |
April | 0.210081E+09 | 2693.51 | 15-APR-05:01 | -5.0 | -5.1 | 0.00 | 0.00 | 01-APR-00:10 | -5.0 | -5.1 |
May | 0.109214E+10 | 2533.82 | 18-MAY-14:20 | 23.67 | 11.39 | 0.00 | 0.00 | 01-MAY-00:10 | 23.67 | 11.39 |
June | 0.338573E+10 | 5101.02 | 26-JUN-10:10 | 31.05 | 15.98 | 0.00 | 0.00 | 01-JUN-00:10 | 31.05 | 15.98 |
July | 0.335176E+10 | 5463.39 | 17-JUL-10:10 | 34.17 | 14.38 | 0.00 | 0.00 | 01-JUL-00:10 | 34.17 | 14.38 |
August | 0.330646E+10 | 4626.65 | 21-AUG-14:20 | 28.00 | 14.54 | 0.00 | 0.00 | 01-AUG-00:10 | 28.00 | 14.54 |
September | 0.221104E+10 | 4569.88 | 05-SEP-15:40 | 24.60 | 13.98 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 13.98 |
October | 0.485667E+09 | 3014.81 | 10-OCT-16:00 | 25.00 | 8.21 | 0.00 | 0.00 | 01-OCT-00:10 | 25.00 | 8.21 |
November | 0.111902E+09 | 1874.61 | 02-NOV-05:01 | -9.0 | -9.0 | 0.00 | 0.00 | 01-NOV-00:10 | -9.0 | -9.0 |
December | 27407749.76 | 3449.50 | 21-DEC-05:01 | -18.2 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -18.2 | -18.4 |
Annual Sum or Average | 0.146086E+11 | 0.00 | ||||||||
Minimum of Months | 27407749.76 | 1874.61 | -18.2 | -18.4 | 0.00 | 0.00 | -18.2 | -18.4 | ||
Maximum of Months | 0.338573E+10 | 5463.39 | 34.17 | 15.98 | 0.00 | 0.00 | 34.17 | 15.98 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206051E+09 | 2378.38 | 14-JAN-06:01 | -14.0 | -14.0 | 0.00 | 0.00 | 01-JAN-00:10 | -14.0 | -14.0 |
February | 0.164430E+09 | 2565.00 | 02-FEB-06:01 | -9.2 | -9.2 | 0.00 | 0.00 | 01-FEB-00:10 | -9.2 | -9.2 |
March | 0.554290E+09 | 2547.44 | 25-MAR-05:01 | -0.2 | -0.2 | 0.00 | 0.00 | 01-MAR-00:10 | -0.2 | -0.2 |
April | 0.372782E+09 | 2383.07 | 03-APR-05:01 | -8.0 | -8.0 | 0.00 | 0.00 | 01-APR-00:10 | -8.0 | -8.0 |
May | 0.138826E+10 | 2484.93 | 18-MAY-15:10 | 22.33 | 11.65 | 0.00 | 0.00 | 01-MAY-00:10 | 22.33 | 11.65 |
June | 0.352516E+10 | 5615.34 | 26-JUN-12:08 | 36.18 | 15.20 | 0.00 | 0.00 | 01-JUN-00:10 | 36.18 | 15.20 |
July | 0.347937E+10 | 5655.53 | 17-JUL-12:08 | 36.00 | 14.76 | 0.00 | 0.00 | 01-JUL-00:10 | 36.00 | 14.76 |
August | 0.366232E+10 | 4441.74 | 21-AUG-15:00 | 26.00 | 14.34 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 14.34 |
September | 0.282910E+10 | 4998.12 | 05-SEP-06:15 | 14.00 | 7.55 | 0.00 | 0.00 | 01-SEP-00:10 | 14.00 | 7.55 |
October | 0.105030E+10 | 3268.83 | 11-OCT-16:20 | 23.33 | 8.54 | 0.00 | 0.00 | 01-OCT-00:10 | 23.33 | 8.54 |
November | 0.355398E+09 | 2066.09 | 30-NOV-06:01 | -12.0 | -12.8 | 0.00 | 0.00 | 01-NOV-00:10 | -12.0 | -12.8 |
December | 0.130469E+09 | 3019.79 | 21-DEC-05:01 | -18.2 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -18.2 | -18.4 |
Annual Sum or Average | 0.177179E+11 | 0.00 | ||||||||
Minimum of Months | 0.130469E+09 | 2066.09 | -18.2 | -18.4 | 0.00 | 0.00 | -18.2 | -18.4 | ||
Maximum of Months | 0.366232E+10 | 5655.53 | 36.18 | 15.20 | 0.00 | 0.00 | 36.18 | 15.20 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.663377E+10 | 9276.97 | 25-JAN-16:20 | 13.67 | 4.08 | 0.179115E+10 | 2606.61 | 24-JAN-10:20 | 13.67 | 4.08 |
February | 0.579942E+10 | 8878.20 | 27-FEB-16:30 | 13.00 | 4.47 | 0.160943E+10 | 2608.00 | 22-FEB-14:00 | 13.00 | 4.47 |
March | 0.854304E+10 | 13144.27 | 15-MAR-16:00 | 19.00 | 5.38 | 0.201062E+10 | 2606.65 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.754971E+10 | 11580.57 | 21-APR-14:00 | 15.00 | 5.55 | 0.179588E+10 | 2606.71 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.121137E+11 | 13557.19 | 18-MAY-15:40 | 20.33 | 11.59 | 0.205689E+10 | 2606.66 | 18-MAY-09:09 | 20.33 | 11.59 |
June | 0.171471E+11 | 28408.70 | 26-JUN-05:12 | 17.53 | 11.60 | 0.206820E+10 | 2606.67 | 08-JUN-13:09 | 17.53 | 11.60 |
July | 0.169401E+11 | 28905.94 | 24-JUL-05:12 | 18.00 | 14.77 | 0.192225E+10 | 2606.65 | 11-JUL-09:30 | 18.00 | 14.77 |
August | 0.175056E+11 | 29040.22 | 07-AUG-05:12 | 16.33 | 11.48 | 0.215802E+10 | 2606.65 | 10-AUG-09:39 | 24.67 | 13.62 |
September | 0.147949E+11 | 30169.15 | 05-SEP-05:12 | 14.20 | 8.43 | 0.191340E+10 | 2606.85 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.996319E+10 | 26112.81 | 10-OCT-06:01 | 8.33 | 4.27 | 0.191768E+10 | 2606.63 | 03-OCT-09:20 | 8.33 | 4.27 |
November | 0.747208E+10 | 11420.65 | 08-NOV-16:20 | 16.33 | 7.18 | 0.183863E+10 | 2606.60 | 15-NOV-10:20 | 7.67 | 3.50 |
December | 0.587563E+10 | 7205.68 | 15-DEC-16:00 | 6.00 | 2.22 | 0.167834E+10 | 2606.54 | 05-DEC-10:50 | 6.00 | 2.22 |
Annual Sum or Average | 0.130338E+12 | 0.227605E+11 | ||||||||
Minimum of Months | 0.579942E+10 | 7205.68 | 6.00 | 2.22 | 0.160943E+10 | 2606.54 | 6.00 | 2.22 | ||
Maximum of Months | 0.175056E+11 | 30169.15 | 20.33 | 14.77 | 0.215802E+10 | 2608.00 | 24.67 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514741E+10 | 8313.61 | 20-JAN-16:30 | 15.00 | 6.47 | 0.167689E+10 | 2606.58 | 26-JAN-14:20 | 9.00 | 2.97 |
February | 0.464098E+10 | 8014.01 | 27-FEB-16:20 | 13.00 | 4.42 | 0.152777E+10 | 2606.56 | 27-FEB-14:20 | 13.00 | 4.42 |
March | 0.754295E+10 | 14231.41 | 15-MAR-15:20 | 19.67 | 5.62 | 0.193231E+10 | 2606.65 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.688859E+10 | 13209.65 | 21-APR-14:00 | 15.00 | 5.55 | 0.173990E+10 | 2606.72 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.117633E+11 | 15240.71 | 31-MAY-15:40 | 28.00 | 14.79 | 0.203229E+10 | 2606.65 | 18-MAY-09:09 | 28.00 | 14.79 |
June | 0.179476E+11 | 30391.96 | 26-JUN-05:12 | 17.53 | 11.60 | 0.206667E+10 | 2606.68 | 08-JUN-13:09 | 17.53 | 11.60 |
July | 0.175958E+11 | 31034.90 | 24-JUL-05:12 | 18.00 | 14.77 | 0.192145E+10 | 2606.65 | 11-JUL-09:30 | 18.00 | 14.77 |
August | 0.178668E+11 | 30684.53 | 21-AUG-05:12 | 19.83 | 12.23 | 0.215587E+10 | 2606.66 | 10-AUG-09:50 | 19.83 | 12.23 |
September | 0.140016E+11 | 30858.22 | 05-SEP-05:12 | 14.20 | 8.43 | 0.190251E+10 | 2606.85 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.811182E+10 | 14982.26 | 11-OCT-15:30 | 25.00 | 9.04 | 0.183384E+10 | 2606.63 | 03-OCT-13:20 | 25.00 | 9.04 |
November | 0.590000E+10 | 10722.36 | 08-NOV-16:00 | 18.00 | 7.82 | 0.172093E+10 | 2606.59 | 08-NOV-14:20 | 18.00 | 7.82 |
December | 0.434690E+10 | 6029.29 | 15-DEC-16:00 | 6.00 | 2.22 | 0.156186E+10 | 2591.02 | 15-DEC-14:00 | 6.00 | 2.22 |
Annual Sum or Average | 0.121754E+12 | 0.220723E+11 | ||||||||
Minimum of Months | 0.434690E+10 | 6029.29 | 6.00 | 2.22 | 0.152777E+10 | 2591.02 | 6.00 | 2.22 | ||
Maximum of Months | 0.179476E+11 | 31034.90 | 28.00 | 14.79 | 0.215587E+10 | 2606.85 | 28.00 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508115E+09 | 1420.71 | 20-JAN-14:30 | 20.50 | 6.87 | 0.322780E+09 | 533.54 | 20-JAN-16:10 | 17.00 | 7.18 |
February | 0.447331E+09 | 1226.80 | 27-FEB-13:20 | 14.00 | 4.75 | 0.292662E+09 | 534.32 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.107778E+10 | 3582.39 | 14-MAR-14:30 | 23.00 | 7.59 | 0.379856E+09 | 549.49 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.119616E+10 | 3571.82 | 20-APR-13:30 | 21.50 | 8.83 | 0.348532E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.295280E+10 | 5496.62 | 17-MAY-13:30 | 29.00 | 11.78 | 0.421366E+09 | 549.50 | 17-MAY-09:20 | 29.00 | 11.78 |
June | 0.579054E+10 | 11052.06 | 25-JUN-17:52 | 31.60 | 13.99 | 0.435743E+09 | 549.99 | 12-JUN-13:09 | 31.60 | 13.99 |
July | 0.564298E+10 | 11162.41 | 16-JUL-14:32 | 35.67 | 14.60 | 0.405282E+09 | 549.94 | 18-JUL-13:09 | 34.33 | 14.01 |
August | 0.516002E+10 | 6682.44 | 20-AUG-15:42 | 28.00 | 14.08 | 0.453467E+09 | 549.50 | 21-AUG-09:20 | 25.67 | 14.10 |
September | 0.351579E+10 | 6557.74 | 10-SEP-14:42 | 31.78 | 12.50 | 0.395929E+09 | 549.54 | 05-SEP-09:09 | 31.78 | 12.50 |
October | 0.131402E+10 | 3968.33 | 11-OCT-14:30 | 26.50 | 9.60 | 0.362351E+09 | 549.50 | 03-OCT-13:20 | 26.50 | 9.60 |
November | 0.683594E+09 | 2348.94 | 09-NOV-13:40 | 20.00 | 8.72 | 0.332142E+09 | 549.48 | 08-NOV-14:20 | 20.00 | 8.72 |
December | 0.329857E+09 | 1124.10 | 01-DEC-13:40 | 21.67 | 7.88 | 0.303031E+09 | 513.20 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.286190E+11 | 0.445314E+10 | ||||||||
Minimum of Months | 0.329857E+09 | 1124.10 | 14.00 | 4.75 | 0.292662E+09 | 513.20 | 14.00 | 4.75 | ||
Maximum of Months | 0.579054E+10 | 11162.41 | 35.67 | 14.60 | 0.453467E+09 | 549.99 | 34.33 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581432E+09 | 2659.43 | 20-JAN-09:40 | 12.67 | 4.18 | 0.224024E+09 | 347.88 | 10-JAN-10:20 | 12.67 | 4.18 |
February | 0.679093E+09 | 3833.77 | 27-FEB-09:10 | 9.17 | 2.67 | 0.208029E+09 | 347.88 | 23-FEB-10:20 | 9.17 | 2.67 |
March | 0.163243E+10 | 8219.26 | 12-MAR-09:23 | 14.50 | 5.32 | 0.261429E+09 | 347.88 | 27-MAR-09:39 | 0.67 | -0.6 |
April | 0.170707E+10 | 7110.62 | 21-APR-08:40 | 11.67 | 5.95 | 0.236108E+09 | 347.89 | 13-APR-13:00 | 11.67 | 5.95 |
May | 0.331541E+10 | 7771.22 | 16-MAY-08:30 | 21.50 | 11.33 | 0.273116E+09 | 347.90 | 17-MAY-09:09 | 25.33 | 11.72 |
June | 0.608558E+10 | 10718.49 | 11-JUN-09:02 | 20.37 | 10.85 | 0.276479E+09 | 348.56 | 06-JUN-09:00 | 20.37 | 10.85 |
July | 0.571405E+10 | 13485.89 | 16-JUL-09:12 | 33.33 | 14.70 | 0.257294E+09 | 348.81 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.588632E+10 | 13542.24 | 06-AUG-09:12 | 25.67 | 15.47 | 0.287949E+09 | 348.62 | 14-AUG-09:00 | 28.00 | 11.89 |
September | 0.405148E+10 | 11176.17 | 04-SEP-09:12 | 24.97 | 13.41 | 0.254006E+09 | 347.93 | 18-SEP-09:09 | 23.08 | 10.77 |
October | 0.163336E+10 | 7921.96 | 01-OCT-09:13 | 13.33 | 7.78 | 0.240978E+09 | 347.88 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.793600E+09 | 3733.55 | 07-NOV-09:10 | 14.00 | 4.09 | 0.226722E+09 | 347.88 | 14-NOV-10:20 | 3.33 | 2.24 |
December | 0.380267E+09 | 1050.21 | 01-DEC-09:25 | 11.00 | 3.52 | 0.206012E+09 | 347.88 | 15-DEC-10:20 | 6.00 | 0.55 |
Annual Sum or Average | 0.324601E+11 | 0.295214E+10 | ||||||||
Minimum of Months | 0.380267E+09 | 1050.21 | 9.17 | 2.67 | 0.206012E+09 | 347.88 | 0.67 | -0.6 | ||
Maximum of Months | 0.608558E+10 | 13542.24 | 33.33 | 15.47 | 0.287949E+09 | 348.81 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374315E+10 | 12903.41 | 22-JAN-14:32 | 8.00 | 4.11 | 0.381889E+09 | 561.75 | 20-JAN-14:09 | 8.00 | 4.11 |
February | 0.348006E+10 | 15545.44 | 26-FEB-13:22 | 17.50 | 4.55 | 0.346655E+09 | 549.71 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.402793E+10 | 16725.00 | 12-MAR-12:42 | 18.83 | 6.01 | 0.411932E+09 | 560.32 | 15-MAR-13:20 | 20.33 | 5.93 |
April | 0.263979E+10 | 9137.98 | 21-APR-13:10 | 15.83 | 6.37 | 0.364987E+09 | 549.53 | 13-APR-13:00 | 15.83 | 6.37 |
May | 0.403295E+10 | 8047.76 | 16-MAY-13:10 | 27.17 | 12.14 | 0.423619E+09 | 549.51 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.660657E+10 | 14451.08 | 25-JUN-14:32 | 33.43 | 13.43 | 0.435235E+09 | 549.96 | 26-JUN-13:30 | 37.15 | 15.33 |
July | 0.668935E+10 | 15322.41 | 30-JUL-13:13 | 28.33 | 19.61 | 0.405207E+09 | 549.51 | 11-JUL-09:30 | 28.33 | 19.61 |
August | 0.785594E+10 | 15149.22 | 06-AUG-12:32 | 31.33 | 15.82 | 0.454067E+09 | 560.32 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.717892E+10 | 16313.17 | 04-SEP-13:12 | 29.40 | 13.45 | 0.400240E+09 | 599.14 | 28-SEP-13:09 | 30.50 | 11.31 |
October | 0.530562E+10 | 17990.59 | 09-OCT-13:21 | 22.00 | 8.88 | 0.382793E+09 | 586.40 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.412392E+10 | 17499.84 | 05-NOV-13:11 | 21.00 | 6.50 | 0.381714E+09 | 568.02 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.283011E+10 | 14921.20 | 03-DEC-13:22 | 17.60 | 6.45 | 0.358411E+09 | 549.53 | 15-DEC-14:39 | 10.00 | 3.25 |
Annual Sum or Average | 0.585143E+11 | 0.474675E+10 | ||||||||
Minimum of Months | 0.263979E+10 | 8047.76 | 8.00 | 4.11 | 0.346655E+09 | 549.51 | 8.00 | 3.25 | ||
Maximum of Months | 0.785594E+10 | 17990.59 | 33.43 | 19.61 | 0.454067E+09 | 599.14 | 37.15 | 19.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.739903E+09 | 4818.14 | 20-JAN-15:40 | 18.67 | 7.30 | 0.218978E+09 | 347.83 | 27-JAN-14:00 | 10.00 | 5.47 |
February | 0.799362E+09 | 5188.38 | 17-FEB-16:30 | 13.50 | 6.66 | 0.199275E+09 | 347.84 | 22-FEB-14:20 | 8.00 | 3.90 |
March | 0.167426E+10 | 15324.73 | 12-MAR-16:02 | 18.00 | 5.74 | 0.247453E+09 | 347.84 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.157575E+10 | 9871.07 | 08-APR-17:06 | 15.67 | 5.07 | 0.224593E+09 | 347.86 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.303071E+10 | 9570.76 | 28-MAY-15:02 | 20.00 | 10.02 | 0.267406E+09 | 347.85 | 17-MAY-09:20 | 20.00 | 10.02 |
June | 0.557287E+10 | 15968.75 | 11-JUN-16:21 | 28.35 | 12.62 | 0.275793E+09 | 347.86 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.492780E+10 | 15868.45 | 02-JUL-16:51 | 28.00 | 12.40 | 0.256610E+09 | 347.86 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.507638E+10 | 15531.54 | 13-AUG-16:32 | 22.33 | 9.94 | 0.287347E+09 | 347.86 | 21-AUG-09:20 | 25.67 | 14.10 |
September | 0.367457E+10 | 15748.01 | 10-SEP-16:01 | 31.92 | 12.68 | 0.251465E+09 | 347.88 | 05-SEP-09:09 | 31.92 | 12.68 |
October | 0.190493E+10 | 15998.11 | 09-OCT-16:01 | 21.83 | 8.61 | 0.233251E+09 | 347.85 | 11-OCT-13:20 | 26.33 | 9.54 |
November | 0.949721E+09 | 7273.83 | 05-NOV-15:12 | 20.33 | 6.40 | 0.221497E+09 | 347.85 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.465592E+09 | 3580.80 | 01-DEC-15:30 | 19.50 | 7.14 | 0.204227E+09 | 347.84 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.303918E+11 | 0.288789E+10 | ||||||||
Minimum of Months | 0.465592E+09 | 3580.80 | 13.50 | 5.07 | 0.199275E+09 | 347.83 | 8.00 | 3.00 | ||
Maximum of Months | 0.557287E+10 | 15998.11 | 31.92 | 12.68 | 0.287347E+09 | 347.88 | 31.92 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491956E+09 | 1278.61 | 20-JAN-14:10 | 20.83 | 6.93 | 0.318620E+09 | 481.11 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.365421E+09 | 1182.70 | 24-FEB-13:05 | 8.17 | 2.18 | 0.286858E+09 | 483.91 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.801888E+09 | 1578.85 | 14-MAR-15:00 | 23.00 | 7.59 | 0.366037E+09 | 549.48 | 16-MAR-13:20 | 16.00 | 5.23 |
April | 0.935572E+09 | 1364.53 | 20-APR-13:30 | 21.50 | 8.83 | 0.337155E+09 | 549.48 | 20-APR-13:20 | 21.50 | 8.83 |
May | 0.197235E+10 | 3659.56 | 17-MAY-13:30 | 29.00 | 11.78 | 0.418553E+09 | 549.50 | 18-MAY-09:20 | 20.67 | 11.73 |
June | 0.437653E+10 | 6434.58 | 26-JUN-06:03 | 19.77 | 12.60 | 0.435291E+09 | 549.58 | 13-JUN-13:09 | 19.77 | 12.60 |
July | 0.437053E+10 | 6953.39 | 17-JUL-06:03 | 22.50 | 11.12 | 0.404749E+09 | 549.63 | 25-JUL-13:20 | 28.67 | 16.33 |
August | 0.430319E+10 | 5155.03 | 21-AUG-13:50 | 29.00 | 14.47 | 0.453893E+09 | 549.50 | 21-AUG-09:20 | 29.00 | 14.47 |
September | 0.342903E+10 | 6129.56 | 05-SEP-06:02 | 13.90 | 7.58 | 0.400460E+09 | 549.54 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.150276E+10 | 3250.48 | 11-OCT-14:00 | 27.00 | 9.73 | 0.378227E+09 | 549.49 | 03-OCT-13:20 | 27.00 | 9.73 |
November | 0.901260E+09 | 1920.17 | 09-NOV-13:30 | 20.00 | 8.78 | 0.340209E+09 | 549.49 | 09-NOV-10:20 | 20.00 | 8.78 |
December | 0.450666E+09 | 1178.92 | 03-DEC-15:23 | 17.00 | 6.47 | 0.306105E+09 | 498.41 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.239012E+11 | 0.444616E+10 | ||||||||
Minimum of Months | 0.365421E+09 | 1178.92 | 8.17 | 2.18 | 0.286858E+09 | 481.11 | 14.00 | 4.48 | ||
Maximum of Months | 0.437653E+10 | 6953.39 | 29.00 | 14.47 | 0.453893E+09 | 549.63 | 29.00 | 16.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588991E+09 | 1780.74 | 25-JAN-08:40 | 5.67 | 0.52 | 0.224192E+09 | 347.87 | 24-JAN-10:20 | 5.67 | 0.52 |
February | 0.614536E+09 | 3086.02 | 27-FEB-08:35 | 7.67 | 2.12 | 0.205921E+09 | 347.88 | 23-FEB-10:20 | 7.67 | 2.12 |
March | 0.129402E+10 | 4549.44 | 15-MAR-08:50 | 13.17 | 3.86 | 0.260808E+09 | 347.88 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.135112E+10 | 4742.42 | 21-APR-08:50 | 11.83 | 5.97 | 0.236208E+09 | 347.89 | 13-APR-13:00 | 11.83 | 5.97 |
May | 0.253520E+10 | 6085.98 | 11-MAY-06:03 | 8.33 | 4.35 | 0.273425E+09 | 347.90 | 31-MAY-09:00 | 25.00 | 13.24 |
June | 0.522933E+10 | 10670.25 | 18-JUN-10:02 | 24.87 | 18.10 | 0.276571E+09 | 348.41 | 27-JUN-09:00 | 26.60 | 12.07 |
July | 0.491085E+10 | 10578.13 | 16-JUL-09:12 | 33.33 | 14.70 | 0.257357E+09 | 348.36 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.547997E+10 | 11470.14 | 06-AUG-09:01 | 25.33 | 15.45 | 0.288366E+09 | 348.31 | 31-AUG-09:50 | 26.67 | 13.56 |
September | 0.424122E+10 | 10851.32 | 04-SEP-10:22 | 26.65 | 13.27 | 0.255524E+09 | 348.43 | 08-SEP-09:50 | 25.82 | 12.10 |
October | 0.191036E+10 | 6269.08 | 01-OCT-09:13 | 13.33 | 7.78 | 0.249530E+09 | 347.88 | 03-OCT-09:20 | 9.00 | 7.34 |
November | 0.989670E+09 | 3423.50 | 07-NOV-08:25 | 12.00 | 3.43 | 0.235655E+09 | 347.87 | 14-NOV-10:20 | 3.33 | 2.24 |
December | 0.480354E+09 | 1393.70 | 18-DEC-08:33 | -1.0 | -3.0 | 0.212091E+09 | 347.88 | 18-DEC-10:20 | 3.33 | -0.7 |
Annual Sum or Average | 0.296256E+11 | 0.297565E+10 | ||||||||
Minimum of Months | 0.480354E+09 | 1393.70 | -1.0 | -3.0 | 0.205921E+09 | 347.87 | 1.33 | -0.7 | ||
Maximum of Months | 0.547997E+10 | 11470.14 | 33.33 | 18.10 | 0.288366E+09 | 348.43 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238368E+10 | 9627.45 | 24-JAN-14:05 | 17.83 | 6.61 | 0.369462E+09 | 551.04 | 24-JAN-14:09 | 17.83 | 6.61 |
February | 0.187561E+10 | 12456.95 | 26-FEB-13:52 | 17.00 | 4.27 | 0.327490E+09 | 549.64 | 17-FEB-14:50 | 17.00 | 4.27 |
March | 0.229771E+10 | 11509.48 | 12-MAR-12:32 | 18.67 | 6.04 | 0.395437E+09 | 552.61 | 13-MAR-13:00 | 23.00 | 7.20 |
April | 0.136425E+10 | 5504.93 | 21-APR-12:08 | 14.33 | 6.08 | 0.346019E+09 | 549.52 | 13-APR-13:00 | 14.33 | 6.08 |
May | 0.226646E+10 | 6558.31 | 16-MAY-12:00 | 27.00 | 11.84 | 0.408523E+09 | 549.52 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.557677E+10 | 10930.12 | 26-JUN-12:00 | 36.10 | 15.16 | 0.433485E+09 | 610.82 | 26-JUN-12:09 | 36.18 | 15.20 |
July | 0.566016E+10 | 10888.69 | 17-JUL-12:00 | 36.00 | 14.76 | 0.403672E+09 | 610.22 | 17-JUL-12:09 | 36.00 | 14.76 |
August | 0.728463E+10 | 12243.88 | 06-AUG-11:42 | 31.67 | 16.22 | 0.453782E+09 | 623.17 | 16-AUG-12:09 | 35.17 | 12.78 |
September | 0.714213E+10 | 13222.48 | 04-SEP-12:21 | 28.85 | 13.46 | 0.401540E+09 | 617.20 | 28-SEP-12:09 | 30.08 | 11.35 |
October | 0.466737E+10 | 13952.97 | 09-OCT-13:21 | 22.00 | 8.88 | 0.384429E+09 | 618.36 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.329718E+10 | 12503.28 | 05-NOV-13:22 | 21.00 | 6.47 | 0.373709E+09 | 586.01 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.207175E+10 | 12357.46 | 17-DEC-15:23 | 16.75 | 5.34 | 0.343330E+09 | 549.71 | 15-DEC-14:00 | 16.75 | 5.34 |
Annual Sum or Average | 0.458877E+11 | 0.464088E+10 | ||||||||
Minimum of Months | 0.136425E+10 | 5504.93 | 14.33 | 4.27 | 0.327490E+09 | 549.52 | 12.83 | 4.27 | ||
Maximum of Months | 0.728463E+10 | 13952.97 | 36.10 | 16.22 | 0.453782E+09 | 623.17 | 36.18 | 15.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655785E+09 | 3573.87 | 23-JAN-16:10 | 18.17 | 6.14 | 0.220049E+09 | 347.83 | 24-JAN-14:20 | 17.67 | 6.59 |
February | 0.615791E+09 | 3772.28 | 17-FEB-16:30 | 13.50 | 6.66 | 0.199339E+09 | 347.84 | 23-FEB-14:20 | 9.00 | 4.54 |
March | 0.119392E+10 | 6899.21 | 12-MAR-16:32 | 18.00 | 5.65 | 0.247916E+09 | 347.85 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.112956E+10 | 6305.75 | 08-APR-17:06 | 15.67 | 5.07 | 0.225724E+09 | 347.86 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.215276E+10 | 5875.77 | 31-MAY-16:00 | 28.00 | 14.86 | 0.269211E+09 | 347.85 | 10-MAY-13:50 | 28.00 | 14.86 |
June | 0.462433E+10 | 12286.97 | 04-JUN-16:51 | 29.40 | 12.14 | 0.276192E+09 | 347.86 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.404088E+10 | 12171.44 | 02-JUL-17:21 | 28.00 | 12.39 | 0.256758E+09 | 347.85 | 14-JUL-09:30 | 25.00 | 12.08 |
August | 0.455877E+10 | 12899.08 | 13-AUG-17:41 | 22.83 | 10.50 | 0.288123E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.372552E+10 | 12343.36 | 10-SEP-17:51 | 29.40 | 11.87 | 0.254966E+09 | 347.88 | 05-SEP-09:09 | 29.40 | 11.87 |
October | 0.200830E+10 | 12366.81 | 09-OCT-16:01 | 21.83 | 8.61 | 0.246936E+09 | 347.85 | 19-OCT-09:20 | 9.67 | 2.68 |
November | 0.105708E+10 | 5204.27 | 07-NOV-15:40 | 21.33 | 7.24 | 0.231515E+09 | 347.84 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.538940E+09 | 2888.54 | 04-DEC-15:30 | 18.00 | 5.80 | 0.208604E+09 | 347.83 | 18-DEC-14:00 | 5.00 | 0.54 |
Annual Sum or Average | 0.263017E+11 | 0.292533E+10 | ||||||||
Minimum of Months | 0.538940E+09 | 2888.54 | 13.50 | 5.07 | 0.199339E+09 | 347.83 | 5.00 | 0.54 | ||
Maximum of Months | 0.462433E+10 | 12899.08 | 29.40 | 14.86 | 0.288123E+09 | 347.88 | 29.40 | 14.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.721645E+09 | 1424.72 | 20-JAN-15:00 | 20.00 | 6.78 | 0.331727E+09 | 531.18 | 20-JAN-16:19 | 16.00 | 6.84 |
February | 0.631766E+09 | 1413.01 | 27-FEB-13:30 | 14.00 | 4.75 | 0.299376E+09 | 535.55 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.125157E+10 | 3397.32 | 14-MAR-14:30 | 23.00 | 7.59 | 0.389578E+09 | 549.49 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.134586E+10 | 3167.27 | 20-APR-13:30 | 21.50 | 8.83 | 0.357733E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.301986E+10 | 5169.49 | 17-MAY-13:30 | 29.00 | 11.78 | 0.427519E+09 | 549.50 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.557390E+10 | 9546.67 | 25-JUN-16:21 | 32.70 | 13.84 | 0.436204E+09 | 550.59 | 14-JUN-13:20 | 32.70 | 13.84 |
July | 0.544831E+10 | 9590.12 | 16-JUL-13:42 | 35.33 | 14.36 | 0.405623E+09 | 550.51 | 24-JUL-13:20 | 32.00 | 16.99 |
August | 0.503531E+10 | 6961.22 | 21-AUG-06:03 | 19.75 | 12.40 | 0.454344E+09 | 550.22 | 18-AUG-13:20 | 19.75 | 12.40 |
September | 0.362595E+10 | 6828.42 | 11-SEP-06:03 | 19.00 | 9.04 | 0.399937E+09 | 549.54 | 05-SEP-09:09 | 19.00 | 9.04 |
October | 0.157809E+10 | 3848.50 | 10-OCT-15:20 | 25.00 | 8.38 | 0.376995E+09 | 549.49 | 11-OCT-13:20 | 26.33 | 9.54 |
November | 0.963399E+09 | 2514.64 | 09-NOV-13:30 | 20.00 | 8.78 | 0.343282E+09 | 549.49 | 17-NOV-14:20 | 13.33 | 5.89 |
December | 0.535046E+09 | 1282.87 | 14-DEC-13:50 | 16.25 | 4.38 | 0.309795E+09 | 529.58 | 04-DEC-14:00 | 16.25 | 4.38 |
Annual Sum or Average | 0.297307E+11 | 0.453211E+10 | ||||||||
Minimum of Months | 0.535046E+09 | 1282.87 | 14.00 | 4.38 | 0.299376E+09 | 529.58 | 11.67 | 3.37 | ||
Maximum of Months | 0.557390E+10 | 9590.12 | 35.33 | 14.36 | 0.454344E+09 | 550.59 | 32.70 | 16.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.642228E+09 | 4304.61 | 26-JAN-13:02 | 9.00 | 2.97 | 0.169922E+09 | 356.45 | 13-JAN-11:09 | 9.00 | 2.97 |
February | 0.770028E+09 | 4970.23 | 27-FEB-09:10 | 9.17 | 2.67 | 0.156345E+09 | 356.45 | 14-FEB-11:09 | 9.17 | 2.67 |
March | 0.171854E+10 | 9900.26 | 12-MAR-09:32 | 14.67 | 5.41 | 0.195039E+09 | 356.46 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.173783E+10 | 7457.71 | 21-APR-08:70 | 11.17 | 5.89 | 0.176642E+09 | 356.47 | 13-APR-10:09 | 11.17 | 5.89 |
May | 0.324551E+10 | 9447.60 | 28-MAY-09:02 | 12.33 | 8.71 | 0.203520E+09 | 356.52 | 03-MAY-10:09 | 12.33 | 8.71 |
June | 0.577124E+10 | 13842.20 | 11-JUN-08:52 | 20.00 | 10.75 | 0.205168E+09 | 356.47 | 05-JUN-10:09 | 20.00 | 10.75 |
July | 0.540719E+10 | 14352.33 | 16-JUL-08:21 | 31.50 | 14.54 | 0.191556E+09 | 356.46 | 18-JUL-14:09 | 31.00 | 15.46 |
August | 0.560711E+10 | 14800.79 | 06-AUG-09:01 | 25.33 | 15.45 | 0.213602E+09 | 356.49 | 30-AUG-10:09 | 25.17 | 12.29 |
September | 0.402074E+10 | 13782.39 | 04-SEP-08:22 | 22.75 | 12.87 | 0.189030E+09 | 356.48 | 18-SEP-10:09 | 25.18 | 11.04 |
October | 0.180095E+10 | 9757.87 | 01-OCT-09:23 | 13.50 | 7.83 | 0.181856E+09 | 356.46 | 10-OCT-14:09 | 25.00 | 8.67 |
November | 0.897326E+09 | 4759.12 | 07-NOV-08:50 | 13.33 | 3.89 | 0.172331E+09 | 356.45 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.413565E+09 | 2048.70 | 01-DEC-11:05 | 19.17 | 6.79 | 0.156838E+09 | 356.46 | 18-DEC-11:09 | 4.00 | -0.6 |
Annual Sum or Average | 0.320323E+11 | 0.221185E+10 | ||||||||
Minimum of Months | 0.413565E+09 | 2048.70 | 9.00 | 2.67 | 0.156345E+09 | 356.45 | 0.33 | -0.6 | ||
Maximum of Months | 0.577124E+10 | 14800.79 | 31.50 | 15.45 | 0.213602E+09 | 356.52 | 31.00 | 15.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438404E+10 | 14104.75 | 22-JAN-14:43 | 8.00 | 4.11 | 0.390357E+09 | 583.25 | 20-JAN-14:09 | 8.00 | 4.11 |
February | 0.394722E+10 | 14401.06 | 26-FEB-13:02 | 17.83 | 4.74 | 0.353004E+09 | 551.35 | 17-FEB-14:09 | 17.83 | 4.74 |
March | 0.433168E+10 | 14244.04 | 12-MAR-12:12 | 18.33 | 6.09 | 0.419438E+09 | 576.62 | 15-MAR-13:20 | 20.33 | 5.93 |
April | 0.279397E+10 | 8697.72 | 21-APR-13:05 | 15.83 | 6.37 | 0.373710E+09 | 550.30 | 21-APR-13:20 | 15.67 | 6.21 |
May | 0.409363E+10 | 7543.22 | 16-MAY-13:10 | 27.17 | 12.14 | 0.429391E+09 | 549.52 | 10-MAY-13:39 | 27.17 | 12.14 |
June | 0.635832E+10 | 13551.62 | 25-JUN-16:21 | 32.70 | 13.84 | 0.435988E+09 | 550.94 | 30-JUN-13:20 | 34.97 | 13.87 |
July | 0.645197E+10 | 13920.14 | 23-JUL-11:22 | 31.00 | 16.01 | 0.405702E+09 | 550.77 | 31-JUL-13:20 | 26.67 | 17.30 |
August | 0.768052E+10 | 14564.28 | 06-AUG-11:42 | 31.67 | 16.22 | 0.455152E+09 | 570.71 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.731799E+10 | 15727.61 | 04-SEP-11:41 | 28.12 | 13.34 | 0.403160E+09 | 617.38 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.574085E+10 | 15061.20 | 09-OCT-12:52 | 22.00 | 9.18 | 0.393300E+09 | 609.81 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.477608E+10 | 14854.84 | 05-NOV-12:42 | 20.83 | 6.41 | 0.391104E+09 | 592.54 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.338001E+10 | 14257.85 | 17-DEC-12:42 | 17.67 | 5.69 | 0.366691E+09 | 550.23 | 18-DEC-14:20 | 4.33 | 0.17 |
Annual Sum or Average | 0.612563E+11 | 0.481700E+10 | ||||||||
Minimum of Months | 0.279397E+10 | 7543.22 | 8.00 | 4.11 | 0.353004E+09 | 549.52 | 4.33 | 0.17 | ||
Maximum of Months | 0.768052E+10 | 15727.61 | 32.70 | 16.22 | 0.455152E+09 | 617.38 | 34.97 | 17.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929686E+09 | 4765.29 | 20-JAN-15:40 | 18.67 | 7.30 | 0.224607E+09 | 347.84 | 26-JAN-14:20 | 9.00 | 2.97 |
February | 0.938457E+09 | 5203.21 | 17-FEB-16:30 | 13.50 | 6.66 | 0.203732E+09 | 348.04 | 22-FEB-14:00 | 8.00 | 4.48 |
March | 0.178586E+10 | 9905.50 | 12-MAR-16:12 | 18.00 | 5.71 | 0.253637E+09 | 347.85 | 16-MAR-09:20 | 11.67 | 3.37 |
April | 0.164554E+10 | 9571.83 | 08-APR-17:06 | 15.67 | 5.07 | 0.230784E+09 | 347.86 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.306013E+10 | 8825.68 | 28-MAY-15:32 | 20.00 | 9.85 | 0.271306E+09 | 347.86 | 10-MAY-13:39 | 20.00 | 9.85 |
June | 0.540538E+10 | 15946.90 | 25-JUN-16:21 | 32.70 | 13.84 | 0.276231E+09 | 347.86 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.475739E+10 | 14675.34 | 02-JUL-16:31 | 28.00 | 12.40 | 0.256909E+09 | 347.86 | 14-JUL-09:30 | 25.00 | 12.08 |
August | 0.496100E+10 | 15640.10 | 13-AUG-17:41 | 22.83 | 10.50 | 0.287955E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.374181E+10 | 15335.76 | 17-SEP-16:11 | 26.43 | 10.71 | 0.253831E+09 | 347.88 | 05-SEP-09:09 | 26.43 | 10.71 |
October | 0.209512E+10 | 11652.49 | 09-OCT-15:32 | 22.00 | 8.78 | 0.242081E+09 | 347.85 | 06-OCT-09:20 | 22.00 | 8.78 |
November | 0.116099E+10 | 6023.03 | 07-NOV-15:30 | 21.50 | 7.27 | 0.228601E+09 | 347.85 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.619522E+09 | 3564.54 | 01-DEC-15:30 | 19.50 | 7.14 | 0.208994E+09 | 347.84 | 18-DEC-14:00 | 5.00 | 0.54 |
Annual Sum or Average | 0.311009E+11 | 0.293867E+10 | ||||||||
Minimum of Months | 0.619522E+09 | 3564.54 | 13.50 | 5.07 | 0.203732E+09 | 347.84 | 5.00 | 0.54 | ||
Maximum of Months | 0.540538E+10 | 15946.90 | 32.70 | 13.84 | 0.287955E+09 | 348.04 | 26.43 | 13.66 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 968836.41 | 11774.78 | 06-FEB-07:01 | -9.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 3562974.19 | 11216.10 | 26-DEC-07:03 | 6.83 |
Annual Sum or Average | 4531810.61 | |||
Minimum of Months | 0.00 | 0.00 | -9.7 | |
Maximum of Months | 3562974.19 | 11774.78 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231469E+10 | 12348.96 | 05-JAN-07:02 | -17.0 |
February | 0.255753E+10 | 13844.38 | 06-FEB-06:13 | -10.0 |
March | 0.178712E+10 | 10217.99 | 20-MAR-05:13 | 0.00 |
April | 0.118576E+10 | 13323.40 | 17-APR-05:12 | -8.0 |
May | 0.407389E+09 | 4510.43 | 01-MAY-06:03 | 6.33 |
June | 0.117321E+09 | 4089.62 | 26-JUN-05:12 | 17.53 |
July | 92446030.18 | 4209.07 | 04-JUL-07:12 | 16.33 |
August | 0.121548E+09 | 3268.32 | 06-AUG-07:52 | 22.00 |
September | 0.312113E+09 | 4442.20 | 17-SEP-08:23 | 16.35 |
October | 0.153309E+10 | 12790.36 | 30-OCT-05:12 | -10.0 |
November | 0.189103E+10 | 12399.36 | 30-NOV-06:13 | -12.0 |
December | 0.374745E+10 | 15402.33 | 23-DEC-06:13 | -22.1 |
Annual Sum or Average | 0.160675E+11 | |||
Minimum of Months | 92446030.18 | 3268.32 | -22.1 | |
Maximum of Months | 0.374745E+10 | 15402.33 | 22.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143482E+10 | 6849.75 | 16-JAN-13:33 | -0.3 |
February | 0.146735E+10 | 7456.22 | 06-FEB-07:11 | -9.3 |
March | 0.974290E+09 | 5201.21 | 20-MAR-06:01 | 0.00 |
April | 0.780221E+09 | 4007.20 | 17-APR-06:02 | -7.7 |
May | 0.166521E+09 | 3066.61 | 28-MAY-09:02 | 12.33 |
June | 26307026.84 | 4392.59 | 11-JUN-15:31 | 28.87 |
July | 36318800.38 | 3899.23 | 04-JUL-14:13 | 27.67 |
August | 22884130.50 | 4096.07 | 06-AUG-10:22 | 28.50 |
September | 63725174.51 | 5133.44 | 24-SEP-14:43 | 22.20 |
October | 0.600631E+09 | 5815.83 | 15-OCT-15:13 | 15.00 |
November | 0.117695E+10 | 5879.91 | 12-NOV-11:23 | 5.00 |
December | 0.179146E+10 | 6961.30 | 26-DEC-06:22 | 7.00 |
Annual Sum or Average | 0.854147E+10 | |||
Minimum of Months | 22884130.50 | 3066.61 | -9.3 | |
Maximum of Months | 0.179146E+10 | 7456.22 | 28.87 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748340E+09 | 2571.55 | 22-JAN-15:03 | 8.17 |
February | 0.789192E+09 | 3403.78 | 06-FEB-08:30 | -6.5 |
March | 0.547821E+09 | 2576.61 | 20-MAR-07:10 | 0.17 |
April | 0.434940E+09 | 2153.79 | 26-APR-07:10 | 5.67 |
May | 77561516.76 | 1740.41 | 02-MAY-07:07 | 1.33 |
June | 14119560.35 | 1953.69 | 11-JUN-15:41 | 28.88 |
July | 19314896.92 | 2282.74 | 09-JUL-13:43 | 34.67 |
August | 16143517.44 | 2599.29 | 13-AUG-15:01 | 23.00 |
September | 27334335.73 | 3096.40 | 17-SEP-15:21 | 26.60 |
October | 0.303451E+09 | 4001.58 | 15-OCT-16:23 | 14.50 |
November | 0.561319E+09 | 3757.62 | 05-NOV-11:22 | 19.00 |
December | 0.105424E+10 | 4037.57 | 17-DEC-12:42 | 17.67 |
Annual Sum or Average | 0.459377E+10 | |||
Minimum of Months | 14119560.35 | 1740.41 | -6.5 | |
Maximum of Months | 0.105424E+10 | 4037.57 | 34.67 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29369684.20 | 16030.49 | 06-JAN-07:01 | -7.0 |
February | 0.165367E+09 | 18016.97 | 06-FEB-06:01 | -10.0 |
March | 44978992.87 | 17266.06 | 20-MAR-05:01 | 0.00 |
April | 19832344.76 | 16168.43 | 17-APR-06:01 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 6199979.78 | 15953.41 | 31-OCT-06:01 | -9.0 |
November | 8474134.44 | 15984.00 | 01-NOV-06:01 | -2.8 |
December | 0.173911E+09 | 18203.01 | 26-DEC-06:11 | 7.00 |
Annual Sum or Average | 0.448133E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.173911E+09 | 18203.01 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.674571E+09 | 27526.70 | 02-JAN-06:01 | -2.8 |
February | 0.106091E+10 | 30021.77 | 06-FEB-05:11 | -10.0 |
March | 0.441992E+09 | 28777.11 | 20-MAR-04:01 | 0.83 |
April | 0.378427E+09 | 27761.05 | 17-APR-05:01 | -8.0 |
May | 8090147.58 | 24554.29 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.307210E+09 | 27619.99 | 30-OCT-05:01 | -10.0 |
November | 0.375584E+09 | 27038.63 | 30-NOV-06:01 | -12.0 |
December | 0.146983E+10 | 29754.99 | 26-DEC-06:11 | 7.00 |
Annual Sum or Average | 0.471661E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.146983E+10 | 30021.77 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174285E+10 | 9817.52 | 17-JAN-05:01 | -0.8 |
February | 0.210201E+10 | 10125.44 | 12-FEB-05:23 | -19.5 |
March | 0.109335E+10 | 10353.58 | 19-MAR-07:52 | -12.9 |
April | 0.590786E+09 | 9854.65 | 03-APR-04:01 | -8.0 |
May | 31454317.93 | 8586.08 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 8364063.54 | 7719.32 | 22-SEP-06:03 | -1.4 |
October | 0.779929E+09 | 9733.56 | 31-OCT-04:01 | -8.0 |
November | 0.125990E+10 | 9800.75 | 30-NOV-05:11 | -12.7 |
December | 0.329753E+10 | 10559.28 | 24-DEC-07:12 | -18.7 |
Annual Sum or Average | 0.109062E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.5 | |
Maximum of Months | 0.329753E+10 | 10559.28 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839473E+09 | 10958.92 | 17-JAN-05:01 | -0.8 |
February | 0.108879E+10 | 11405.95 | 06-FEB-05:11 | -10.0 |
March | 0.584799E+09 | 11575.60 | 19-MAR-07:52 | -12.9 |
April | 0.309432E+09 | 11116.86 | 03-APR-04:01 | -8.0 |
May | 10277460.68 | 9625.15 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 3692888.90 | 4766.64 | 22-SEP-06:03 | -1.4 |
October | 0.496334E+09 | 11021.59 | 31-OCT-04:01 | -8.0 |
November | 0.660851E+09 | 11064.00 | 30-NOV-05:11 | -12.7 |
December | 0.178903E+10 | 11850.30 | 24-DEC-07:12 | -18.7 |
Annual Sum or Average | 0.578268E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.178903E+10 | 11850.30 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.877621E+09 | 13079.95 | 05-JAN-05:01 | -17.0 |
February | 0.135658E+10 | 13636.58 | 06-FEB-05:11 | -10.0 |
March | 0.869802E+09 | 13883.21 | 19-MAR-07:52 | -12.9 |
April | 0.535209E+09 | 13290.87 | 03-APR-04:01 | -8.0 |
May | 35386509.31 | 11566.84 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 7344842.81 | 7936.23 | 22-SEP-06:03 | -1.4 |
October | 0.704632E+09 | 13110.35 | 31-OCT-04:01 | -8.0 |
November | 0.746537E+09 | 13149.44 | 30-NOV-05:11 | -12.7 |
December | 0.193406E+10 | 14143.05 | 24-DEC-07:12 | -18.7 |
Annual Sum or Average | 0.706717E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.193406E+10 | 14143.05 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.934639E+09 | 11168.73 | 05-JAN-05:01 | -17.0 |
February | 0.118918E+10 | 11740.48 | 06-FEB-05:11 | -10.0 |
March | 0.663157E+09 | 11889.17 | 19-MAR-07:52 | -12.9 |
April | 0.377345E+09 | 11363.62 | 03-APR-04:01 | -8.0 |
May | 23003356.05 | 9611.93 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 6182165.04 | 5108.34 | 22-SEP-06:03 | -1.4 |
October | 0.502034E+09 | 11224.10 | 31-OCT-04:01 | -8.0 |
November | 0.717481E+09 | 11292.90 | 30-NOV-05:11 | -12.7 |
December | 0.188987E+10 | 12197.82 | 24-DEC-07:12 | -18.7 |
Annual Sum or Average | 0.630289E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.188987E+10 | 12197.82 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110297E+10 | 6971.81 | 02-JAN-05:01 | -2.2 |
February | 0.137217E+10 | 7385.89 | 06-FEB-05:01 | -10.0 |
March | 0.608840E+09 | 6891.01 | 20-MAR-04:01 | 0.83 |
April | 0.257809E+09 | 6845.24 | 03-APR-04:01 | -8.0 |
May | 6194298.59 | 5916.25 | 02-MAY-06:02 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.173702E+09 | 6510.78 | 30-OCT-05:01 | -10.0 |
November | 0.316863E+09 | 6716.32 | 30-NOV-06:01 | -12.0 |
December | 0.140851E+10 | 7188.96 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.524706E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.140851E+10 | 7385.89 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378756E+09 | 7909.47 | 06-JAN-05:01 | -7.8 |
February | 0.591334E+09 | 8571.02 | 06-FEB-05:01 | -10.0 |
March | 0.257162E+09 | 7621.60 | 20-MAR-05:01 | 0.00 |
April | 0.112375E+09 | 7828.49 | 03-APR-05:01 | -8.0 |
May | 842691.73 | 3403.53 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.106713E+09 | 7455.72 | 31-OCT-05:01 | -8.2 |
November | 0.143310E+09 | 7754.46 | 30-NOV-06:01 | -12.0 |
December | 0.620603E+09 | 8331.90 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.221110E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.620603E+09 | 8571.02 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183118E+10 | 11866.08 | 05-JAN-07:10 | -17.0 |
February | 0.219911E+10 | 11379.75 | 06-FEB-07:50 | -8.3 |
March | 0.186620E+10 | 10434.36 | 29-MAR-06:10 | -7.7 |
April | 0.135925E+10 | 10726.26 | 17-APR-06:10 | -7.7 |
May | 0.456839E+09 | 9446.70 | 02-MAY-06:10 | 0.17 |
June | 8326209.59 | 6073.62 | 09-JUN-06:06 | 9.37 |
July | 1604779.68 | 2979.32 | 03-JUL-06:07 | 11.00 |
August | 531865.63 | 2701.19 | 23-AUG-06:08 | 12.50 |
September | 77173022.79 | 8991.88 | 22-SEP-06:10 | -1.4 |
October | 0.131795E+10 | 10998.69 | 30-OCT-06:10 | -10.0 |
November | 0.143386E+10 | 11190.59 | 30-NOV-07:10 | -11.3 |
December | 0.250387E+10 | 12445.19 | 21-DEC-08:00 | -20.0 |
Annual Sum or Average | 0.130559E+11 | |||
Minimum of Months | 531865.63 | 2701.19 | -20.0 | |
Maximum of Months | 0.250387E+10 | 12445.19 | 12.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401195E+09 | 7556.83 | 03-JAN-06:01 | -7.0 |
February | 0.589527E+09 | 8551.07 | 06-FEB-05:01 | -10.0 |
March | 0.272882E+09 | 7555.38 | 20-MAR-04:01 | 0.83 |
April | 0.136593E+09 | 7715.39 | 03-APR-05:01 | -8.0 |
May | 3369565.49 | 4908.63 | 02-MAY-06:02 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.109601E+09 | 7338.06 | 31-OCT-05:01 | -8.2 |
November | 0.133329E+09 | 7586.06 | 30-NOV-06:01 | -12.0 |
December | 0.653257E+09 | 8236.09 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.229975E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.653257E+09 | 8551.07 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.713317E+09 | 7924.44 | 06-JAN-05:01 | -7.8 |
February | 0.938987E+09 | 8451.83 | 06-FEB-05:01 | -10.0 |
March | 0.336754E+09 | 7984.95 | 20-MAR-04:01 | 0.83 |
April | 0.204215E+09 | 7987.04 | 17-APR-04:01 | -8.0 |
May | 3547029.94 | 6676.10 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 18278.12 | 121.85 | 22-SEP-06:03 | -1.4 |
October | 0.295921E+09 | 7853.72 | 30-OCT-04:01 | -10.0 |
November | 0.431672E+09 | 7900.10 | 01-NOV-04:01 | -3.0 |
December | 0.154794E+10 | 8553.93 | 24-DEC-07:02 | -19.3 |
Annual Sum or Average | 0.447237E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.154794E+10 | 8553.93 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335542E+09 | 8279.36 | 06-JAN-05:01 | -7.8 |
February | 0.488443E+09 | 8915.61 | 06-FEB-05:01 | -10.0 |
March | 0.186264E+09 | 8286.22 | 20-MAR-04:01 | 0.83 |
April | 0.110287E+09 | 8305.25 | 03-APR-04:01 | -8.0 |
May | 836270.83 | 3603.17 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.204367E+09 | 8234.50 | 30-OCT-04:01 | -10.0 |
November | 0.241723E+09 | 8233.64 | 01-NOV-04:01 | -3.0 |
December | 0.816697E+09 | 8893.46 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.238416E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.816697E+09 | 8915.61 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302677E+09 | 11047.26 | 05-JAN-05:01 | -17.0 |
February | 0.594171E+09 | 11919.95 | 06-FEB-05:01 | -10.0 |
March | 0.259732E+09 | 11239.65 | 20-MAR-04:01 | 0.83 |
April | 0.188507E+09 | 11247.16 | 17-APR-04:01 | -8.0 |
May | 4593098.47 | 7966.31 | 02-MAY-06:02 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.274763E+09 | 10730.59 | 30-OCT-05:01 | -10.0 |
November | 0.238302E+09 | 11098.93 | 01-NOV-04:01 | -3.0 |
December | 0.789860E+09 | 11775.64 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.265261E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.789860E+09 | 11919.95 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363130E+09 | 8209.58 | 06-JAN-05:01 | -7.8 |
February | 0.515106E+09 | 8913.98 | 06-FEB-05:01 | -10.0 |
March | 0.200106E+09 | 8233.74 | 20-MAR-04:01 | 0.83 |
April | 0.134661E+09 | 8329.80 | 17-APR-04:01 | -8.0 |
May | 2987690.98 | 4630.06 | 02-MAY-06:02 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 120974.12 | 806.49 | 22-SEP-06:03 | -1.4 |
October | 0.197924E+09 | 8236.28 | 30-OCT-04:01 | -10.0 |
November | 0.241870E+09 | 8230.79 | 01-NOV-04:01 | -3.0 |
December | 0.851253E+09 | 8862.30 | 21-DEC-05:01 | -18.2 |
Annual Sum or Average | 0.250716E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.2 | |
Maximum of Months | 0.851253E+09 | 8913.98 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456004E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.387341E+09 | 688.55 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.428798E+09 | 549.73 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370263E+09 | 479.82 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.387702E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380730E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359596E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407726E+09 | 386.61 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.374987E+09 | 390.43 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.414109E+09 | 627.00 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.445704E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.447060E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.486002E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359596E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.456004E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285036E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243682E+09 | 435.99 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271106E+09 | 333.12 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234971E+09 | 258.84 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247059E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242835E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229292E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.259487E+09 | 247.43 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237598E+09 | 250.26 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.260268E+09 | 390.31 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280142E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.280219E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307170E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.229292E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.285036E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433663E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377588E+09 | 687.48 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.425971E+09 | 543.64 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.371125E+09 | 475.87 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389570E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383397E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.362049E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.409382E+09 | 384.05 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.374235E+09 | 383.76 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.408013E+09 | 621.20 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.429276E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.430492E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.479476E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.362049E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.433663E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277749E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.239825E+09 | 434.19 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269243E+09 | 352.29 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233729E+09 | 314.25 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245237E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241087E+09 | 238.44 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227784E+09 | 236.19 | 28-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256999E+09 | 244.03 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.236548E+09 | 253.02 | 22-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259324E+09 | 397.50 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.273694E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.274452E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303567E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227784E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.277749E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.454448E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.386020E+09 | 686.78 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.428156E+09 | 542.64 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.369949E+09 | 414.04 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.387444E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380509E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359326E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407831E+09 | 383.47 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.374533E+09 | 387.48 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.412998E+09 | 622.89 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.444405E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.445824E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.485144E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359326E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.454448E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.284377E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243146E+09 | 435.08 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.270658E+09 | 328.85 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234800E+09 | 257.55 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246891E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242687E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229159E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.259270E+09 | 245.73 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237345E+09 | 248.70 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259856E+09 | 387.90 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279381E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.279470E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306704E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.229159E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.284377E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433297E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377082E+09 | 685.65 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.425664E+09 | 536.26 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370781E+09 | 413.44 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389264E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383086E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.361775E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.409034E+09 | 380.76 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.373926E+09 | 380.42 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.407521E+09 | 616.79 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.428504E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.428961E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.478889E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.361775E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.433297E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277276E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.239419E+09 | 433.21 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.268958E+09 | 348.83 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233563E+09 | 309.64 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245097E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240981E+09 | 236.39 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227649E+09 | 222.08 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256855E+09 | 242.51 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.236330E+09 | 251.71 | 22-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.258846E+09 | 395.42 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.272403E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.274070E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303145E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227649E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.277276E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.456003E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.387340E+09 | 688.55 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.428797E+09 | 549.71 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370263E+09 | 479.80 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.387701E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380730E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359596E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.407726E+09 | 386.60 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.374987E+09 | 390.42 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.414108E+09 | 626.99 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.445702E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.447060E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.486001E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359596E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.456003E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285036E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243682E+09 | 435.98 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271106E+09 | 333.11 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234971E+09 | 258.83 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247059E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242835E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.229292E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.259487E+09 | 247.42 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237598E+09 | 250.26 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.260267E+09 | 390.30 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280141E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.280218E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307169E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.229292E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.285036E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.433663E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377588E+09 | 687.48 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.425971E+09 | 543.62 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.371125E+09 | 475.85 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389569E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383397E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.362048E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.409381E+09 | 384.04 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.374235E+09 | 383.75 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.408012E+09 | 621.19 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.429275E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.430492E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.479476E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.362048E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.433663E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.277748E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.239824E+09 | 434.19 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269243E+09 | 352.28 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233729E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245236E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241087E+09 | 238.43 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227784E+09 | 236.19 | 28-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256999E+09 | 244.03 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.236548E+09 | 253.02 | 22-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259323E+09 | 397.49 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.273693E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.274452E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303567E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227784E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.277748E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.456004E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536166E+09 |
February | 0.901968E+09 | 0.387341E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860023E+09 |
March | 0.107774E+10 | 0.428798E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929855E+09 |
April | 0.956342E+09 | 0.370263E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987765E+09 |
May | 0.103597E+10 | 0.387702E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2205962.72 | 0.534702E+09 |
June | 0.103308E+10 | 0.380730E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46300711.79 | 0.232887E+09 |
July | 0.959235E+09 | 0.359596E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58258228.60 | 0.232061E+09 |
August | 0.107774E+10 | 0.407726E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31605604.12 | 0.228134E+09 |
September | 0.956342E+09 | 0.374987E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17056356.18 | 0.336725E+09 |
October | 0.994195E+09 | 0.414109E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 309097.53 | 0.716931E+09 |
November | 0.984487E+09 | 0.445704E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616467E+09 |
December | 0.959235E+09 | 0.447060E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115157E+10 |
Annual Sum or Average | 0.119305E+11 | 0.486002E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155736E+09 | 0.736328E+10 |
Minimum of Months | 0.901968E+09 | 0.359596E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228134E+09 |
Maximum of Months | 0.107774E+10 | 0.456004E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58258228.60 | 0.115157E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.285036E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367805E+09 |
February | 0.571020E+09 | 0.243682E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587816E+09 |
March | 0.682301E+09 | 0.271106E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637957E+09 |
April | 0.605444E+09 | 0.234971E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674983E+09 |
May | 0.655854E+09 | 0.247059E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1469777.02 | 0.364219E+09 |
June | 0.654023E+09 | 0.242835E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30266983.85 | 0.158586E+09 |
July | 0.607275E+09 | 0.229292E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37931630.15 | 0.160890E+09 |
August | 0.682301E+09 | 0.259487E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20458539.11 | 0.157316E+09 |
September | 0.605444E+09 | 0.237598E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10505225.26 | 0.233976E+09 |
October | 0.629407E+09 | 0.260268E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206062.50 | 0.493886E+09 |
November | 0.623262E+09 | 0.280142E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419833E+09 |
December | 0.607275E+09 | 0.280219E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779411E+09 |
Annual Sum or Average | 0.755301E+10 | 0.307170E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100838E+09 | 0.503668E+10 |
Minimum of Months | 0.571020E+09 | 0.229292E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157316E+09 |
Maximum of Months | 0.682301E+09 | 0.285036E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37931630.15 | 0.779411E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.433663E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589204E+09 |
February | 0.901968E+09 | 0.377588E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914455E+09 |
March | 0.107774E+10 | 0.425971E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977828E+09 |
April | 0.956342E+09 | 0.371125E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101185E+10 |
May | 0.103597E+10 | 0.389570E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2204393.18 | 0.542556E+09 |
June | 0.103308E+10 | 0.383397E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45907803.96 | 0.232302E+09 |
July | 0.959235E+09 | 0.362049E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57701590.64 | 0.233330E+09 |
August | 0.107774E+10 | 0.409382E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30637602.84 | 0.236809E+09 |
September | 0.956342E+09 | 0.374235E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15167863.23 | 0.356772E+09 |
October | 0.994195E+09 | 0.408013E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259184.71 | 0.760766E+09 |
November | 0.984487E+09 | 0.429276E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663174E+09 |
December | 0.959235E+09 | 0.430492E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122445E+10 |
Annual Sum or Average | 0.119305E+11 | 0.479476E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151878E+09 | 0.774350E+10 |
Minimum of Months | 0.901968E+09 | 0.362049E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232302E+09 |
Maximum of Months | 0.107774E+10 | 0.433663E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57701590.64 | 0.122445E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.277749E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369020E+09 |
February | 0.570983E+09 | 0.239825E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588908E+09 |
March | 0.682256E+09 | 0.269243E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638122E+09 |
April | 0.605404E+09 | 0.233729E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671158E+09 |
May | 0.655811E+09 | 0.245237E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1469144.67 | 0.368460E+09 |
June | 0.653980E+09 | 0.241087E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30126666.53 | 0.162154E+09 |
July | 0.607235E+09 | 0.227784E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37622489.99 | 0.160242E+09 |
August | 0.682256E+09 | 0.256999E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20679444.51 | 0.160965E+09 |
September | 0.605404E+09 | 0.236548E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10395481.60 | 0.236031E+09 |
October | 0.629366E+09 | 0.259324E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206085.11 | 0.491386E+09 |
November | 0.623221E+09 | 0.273694E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422016E+09 |
December | 0.607235E+09 | 0.274452E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781464E+09 |
Annual Sum or Average | 0.755252E+10 | 0.303567E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100499E+09 | 0.504993E+10 |
Minimum of Months | 0.570983E+09 | 0.227784E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160242E+09 |
Maximum of Months | 0.682256E+09 | 0.277749E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37622489.99 | 0.781464E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.454448E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297583E+09 |
February | 0.901968E+09 | 0.386020E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467925E+09 |
March | 0.107774E+10 | 0.428156E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.51 | 0.505249E+09 |
April | 0.956342E+09 | 0.369949E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542159E+09 |
May | 0.103597E+10 | 0.387444E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1224121.48 | 0.280944E+09 |
June | 0.103308E+10 | 0.380509E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26881863.68 | 0.120206E+09 |
July | 0.959235E+09 | 0.359326E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35044011.53 | 0.119219E+09 |
August | 0.107774E+10 | 0.407831E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18129124.24 | 0.121415E+09 |
September | 0.956342E+09 | 0.374533E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9907203.56 | 0.188767E+09 |
October | 0.994195E+09 | 0.412998E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170748.39 | 0.412284E+09 |
November | 0.984487E+09 | 0.444405E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350504E+09 |
December | 0.959235E+09 | 0.445824E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1814.94 | 0.644371E+09 |
Annual Sum or Average | 0.119305E+11 | 0.485144E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91359169.32 | 0.405063E+10 |
Minimum of Months | 0.901968E+09 | 0.359326E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119219E+09 |
Maximum of Months | 0.107774E+10 | 0.454448E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35044011.53 | 0.644371E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.284377E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207483E+09 |
February | 0.571020E+09 | 0.243146E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325974E+09 |
March | 0.682301E+09 | 0.270658E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.354542E+09 |
April | 0.605444E+09 | 0.234800E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380908E+09 |
May | 0.655854E+09 | 0.246891E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 803304.65 | 0.197869E+09 |
June | 0.654023E+09 | 0.242687E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16632107.80 | 86263259.51 |
July | 0.607275E+09 | 0.229159E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20943686.54 | 87548036.13 |
August | 0.682301E+09 | 0.259270E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11061084.03 | 88623615.40 |
September | 0.605444E+09 | 0.237345E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5716513.46 | 0.135837E+09 |
October | 0.629407E+09 | 0.259856E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113826.98 | 0.288694E+09 |
November | 0.623262E+09 | 0.279381E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242473E+09 |
December | 0.607275E+09 | 0.279470E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442566E+09 |
Annual Sum or Average | 0.755301E+10 | 0.306704E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55270525.92 | 0.283878E+10 |
Minimum of Months | 0.571020E+09 | 0.229159E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86263259.51 |
Maximum of Months | 0.682301E+09 | 0.284377E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20943686.54 | 0.442566E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.433297E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451685E+10 |
February | 0.901968E+09 | 0.377082E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456733E+10 |
March | 0.107774E+10 | 0.425664E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402859E+10 |
April | 0.956342E+09 | 0.370781E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314710E+10 |
May | 0.103597E+10 | 0.389264E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54192485.96 | 0.195264E+10 |
June | 0.103308E+10 | 0.383086E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744811E+09 | 0.514759E+09 |
July | 0.959235E+09 | 0.361775E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608483E+09 | 0.490864E+09 |
August | 0.107774E+10 | 0.409034E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650812E+09 | 0.692725E+09 |
September | 0.956342E+09 | 0.373926E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277219E+09 | 0.109129E+10 |
October | 0.994195E+09 | 0.407521E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4063395.73 | 0.359322E+10 |
November | 0.984487E+09 | 0.428504E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433628E+10 |
December | 0.959235E+09 | 0.428961E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524325E+10 |
Annual Sum or Average | 0.119305E+11 | 0.478889E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233958E+10 | 0.341749E+11 |
Minimum of Months | 0.901968E+09 | 0.361775E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490864E+09 |
Maximum of Months | 0.107774E+10 | 0.433297E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744811E+09 | 0.524325E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.277276E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208283E+09 |
February | 0.570983E+09 | 0.239419E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326520E+09 |
March | 0.682256E+09 | 0.268958E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 0.353600E+09 |
April | 0.605404E+09 | 0.233563E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378152E+09 |
May | 0.655811E+09 | 0.245097E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 800396.96 | 0.199375E+09 |
June | 0.653980E+09 | 0.240981E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16606526.53 | 88854149.37 |
July | 0.607235E+09 | 0.227649E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20871816.44 | 86649904.79 |
August | 0.682256E+09 | 0.256855E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11311588.76 | 90733357.53 |
September | 0.605404E+09 | 0.236330E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5651431.73 | 0.137390E+09 |
October | 0.629366E+09 | 0.258846E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113836.78 | 0.288522E+09 |
November | 0.623221E+09 | 0.272403E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243806E+09 |
December | 0.607235E+09 | 0.274070E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443457E+09 |
Annual Sum or Average | 0.755252E+10 | 0.303145E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55355600.34 | 0.284534E+10 |
Minimum of Months | 0.570983E+09 | 0.227649E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86649904.79 |
Maximum of Months | 0.682256E+09 | 0.277276E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20871816.44 | 0.443457E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.456003E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474998E+09 |
February | 0.901968E+09 | 0.387340E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746562E+09 |
March | 0.107774E+10 | 0.428797E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811072E+09 |
April | 0.956342E+09 | 0.370263E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871363E+09 |
May | 0.103597E+10 | 0.387701E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1860684.10 | 0.462189E+09 |
June | 0.103308E+10 | 0.380730E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39282713.06 | 0.199168E+09 |
July | 0.959235E+09 | 0.359596E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50100495.60 | 0.198026E+09 |
August | 0.107774E+10 | 0.407726E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26897171.66 | 0.196199E+09 |
September | 0.956342E+09 | 0.374987E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14564662.21 | 0.294587E+09 |
October | 0.994195E+09 | 0.414108E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262266.57 | 0.634788E+09 |
November | 0.984487E+09 | 0.445702E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543550E+09 |
December | 0.959235E+09 | 0.447060E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999984E+09 |
Annual Sum or Average | 0.119305E+11 | 0.486001E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132968E+09 | 0.643249E+10 |
Minimum of Months | 0.901968E+09 | 0.359596E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196199E+09 |
Maximum of Months | 0.107774E+10 | 0.456003E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50100495.60 | 0.999984E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.285036E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326038E+09 |
February | 0.421807E+09 | 0.243682E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510648E+09 |
March | 0.502994E+09 | 0.271106E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555426E+09 |
April | 0.447140E+09 | 0.234971E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594616E+09 |
May | 0.484071E+09 | 0.247059E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1161463.31 | 0.314735E+09 |
June | 0.482240E+09 | 0.242835E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25042933.51 | 0.135741E+09 |
July | 0.448971E+09 | 0.229292E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31703701.33 | 0.137315E+09 |
August | 0.502994E+09 | 0.259487E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16752489.15 | 0.135375E+09 |
September | 0.447140E+09 | 0.237598E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8633025.35 | 0.203818E+09 |
October | 0.465148E+09 | 0.260267E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152637.11 | 0.435415E+09 |
November | 0.460569E+09 | 0.280141E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370350E+09 |
December | 0.448971E+09 | 0.280218E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678704E+09 |
Annual Sum or Average | 0.557719E+10 | 0.307169E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83446249.76 | 0.439818E+10 |
Minimum of Months | 0.421807E+09 | 0.229292E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135375E+09 |
Maximum of Months | 0.502994E+09 | 0.285036E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31703701.33 | 0.678704E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.433663E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518652E+09 |
February | 0.901968E+09 | 0.377588E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794336E+09 |
March | 0.107774E+10 | 0.425971E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850902E+09 |
April | 0.956342E+09 | 0.371125E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891739E+09 |
May | 0.103597E+10 | 0.389569E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1857417.23 | 0.468594E+09 |
June | 0.103308E+10 | 0.383397E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38661396.10 | 0.198955E+09 |
July | 0.959235E+09 | 0.362048E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49144253.39 | 0.199479E+09 |
August | 0.107774E+10 | 0.409381E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25693195.03 | 0.203835E+09 |
September | 0.956342E+09 | 0.374235E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12727189.82 | 0.310711E+09 |
October | 0.994195E+09 | 0.408012E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173577.17 | 0.669227E+09 |
November | 0.984487E+09 | 0.429275E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581428E+09 |
December | 0.959235E+09 | 0.430492E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106746E+10 |
Annual Sum or Average | 0.119305E+11 | 0.479476E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128257E+09 | 0.675532E+10 |
Minimum of Months | 0.901968E+09 | 0.362048E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198955E+09 |
Maximum of Months | 0.107774E+10 | 0.433663E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49144253.39 | 0.106746E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.277748E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326303E+09 |
February | 0.570983E+09 | 0.239824E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511239E+09 |
March | 0.682256E+09 | 0.269243E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555494E+09 |
April | 0.605404E+09 | 0.233729E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591647E+09 |
May | 0.655811E+09 | 0.245236E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1237434.22 | 0.318201E+09 |
June | 0.653980E+09 | 0.241087E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25354971.69 | 0.138986E+09 |
July | 0.607235E+09 | 0.227784E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31766287.87 | 0.137113E+09 |
August | 0.682256E+09 | 0.256999E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17363861.58 | 0.138532E+09 |
September | 0.605404E+09 | 0.236548E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8719118.61 | 0.206050E+09 |
October | 0.629366E+09 | 0.259323E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174851.19 | 0.433746E+09 |
November | 0.623221E+09 | 0.273693E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371417E+09 |
December | 0.607235E+09 | 0.274452E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679276E+09 |
Annual Sum or Average | 0.755252E+10 | 0.303567E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84616525.16 | 0.440800E+10 |
Minimum of Months | 0.570983E+09 | 0.227784E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137113E+09 |
Maximum of Months | 0.682256E+09 | 0.277748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31766287.87 | 0.679276E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670461E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104616E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114030E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121574E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1776739.19 | 0.623065E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46298461.38 | 0.264525E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62112720.83 | 0.262291E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29594844.82 | 0.266198E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15445822.90 | 0.410936E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130145.73 | 0.898332E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767535E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141062E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155359E+09 | 0.897616E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262291E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62112720.83 | 0.141062E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830466E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130581E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142542E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151845E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2298385.43 | 0.794733E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58632072.88 | 0.342913E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78203421.08 | 0.340941E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38028172.96 | 0.341442E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20379196.98 | 0.518806E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194240.79 | 0.111495E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948719E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174070E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197735E+09 | 0.112233E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340941E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78203421.08 | 0.174070E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832499E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132616E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144824E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153712E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1476691.29 | 0.833298E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50284675.67 | 0.349659E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62848191.17 | 0.350841E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31997268.72 | 0.349739E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14678805.72 | 0.520421E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58203.36 | 0.111837E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953364E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175079E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161344E+09 | 0.113705E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349659E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62848191.17 | 0.175079E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1013.22 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 688.55 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1293.05 | 05-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 549.73 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2881.77 | 19-MAR-07:00 |
April | 1306.65 | 03-APR-09:09 | 479.82 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1857.41 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 17-MAY-14:50 | 1049.17 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.18 | 25-JUN-17:55 | 655.93 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.24 | 16-JUL-11:55 | 653.45 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 386.61 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.41 | 02-AUG-16:00 | 821.47 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 390.43 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.11 | 10-SEP-15:00 | 712.85 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 627.00 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 11-OCT-14:00 | 1521.81 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1599.35 | 01-NOV-04:07 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2394.68 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.45 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 495.24 | 2881.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 676.64 | 13-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 435.99 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 872.99 | 23-FEB-24:00 |
March | 827.22 | 01-MAR-10:09 | 333.12 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1921.17 | 19-MAR-07:00 |
April | 827.22 | 03-APR-09:09 | 258.84 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1238.26 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 17-MAY-14:50 | 700.95 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.11 | 25-JUN-17:55 | 437.87 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.97 | 16-JUL-11:55 | 463.96 | 02-JUL-08:50 |
August | 827.22 | 01-AUG-09:09 | 247.43 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.28 | 02-AUG-16:00 | 561.95 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 250.26 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.45 | 10-SEP-14:45 | 475.82 | 21-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 390.31 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-OCT-14:00 | 1019.16 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1067.22 | 01-NOV-04:04 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1596.17 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.87 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 330.97 | 1921.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1053.47 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 687.48 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1363.89 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 543.64 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2881.77 | 19-MAR-07:00 |
April | 1306.65 | 03-APR-09:09 | 475.87 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1857.42 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 17-MAY-14:50 | 1062.36 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.42 | 25-JUN-17:55 | 654.09 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.15 | 16-JUL-11:55 | 655.00 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 384.05 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.41 | 02-AUG-16:00 | 886.02 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 383.76 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.37 | 10-SEP-15:00 | 718.89 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 621.20 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 11-OCT-14:10 | 1557.98 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1613.06 | 01-NOV-04:04 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2398.62 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.09 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 494.15 | 2881.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 681.69 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 434.19 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 884.61 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 352.29 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1921.17 | 19-MAR-07:00 |
April | 827.17 | 03-APR-09:09 | 314.25 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1238.26 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 17-MAY-14:50 | 714.02 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 238.44 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.72 | 25-JUN-18:00 | 461.14 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 236.19 | 28-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.10 | 16-JUL-11:55 | 450.01 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 244.03 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.27 | 02-AUG-16:00 | 595.59 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 253.02 | 22-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.91 | 10-SEP-15:00 | 472.95 | 21-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 397.50 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 11-OCT-14:00 | 1012.30 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1066.52 | 01-NOV-04:04 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1596.47 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.01 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 330.10 | 1921.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 590.76 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 686.78 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 706.52 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 542.64 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 14-MAR-13:00 | 1569.41 | 19-MAR-06:55 |
April | 1306.65 | 03-APR-09:09 | 414.04 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1047.20 | 15-APR-04:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 17-MAY-14:50 | 589.53 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.32 | 25-JUN-18:00 | 354.96 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.81 | 16-JUL-12:00 | 345.06 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 383.47 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.95 | 06-AUG-12:00 | 411.97 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 387.48 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.97 | 10-SEP-15:00 | 418.42 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 622.89 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 11-OCT-14:00 | 931.67 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 887.27 | 01-NOV-03:53 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 02-DEC-15:00 | 1330.13 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.06 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 265.81 | 1569.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 405.24 | 13-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 435.08 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 498.21 | 23-FEB-24:00 |
March | 827.22 | 01-MAR-10:09 | 328.85 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1044.76 | 19-MAR-06:55 |
April | 827.22 | 03-APR-09:09 | 257.55 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 711.97 | 15-APR-04:55 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 17-MAY-14:50 | 403.64 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.63 | 25-JUN-18:00 | 248.58 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.55 | 16-JUL-11:55 | 245.69 | 03-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 245.73 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.21 | 02-AUG-16:00 | 298.89 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 248.70 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.72 | 10-SEP-14:35 | 282.17 | 22-SEP-02:00 |
October | 827.22 | 02-OCT-09:09 | 387.90 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 11-OCT-14:00 | 637.94 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 588.63 | 01-NOV-03:53 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.66 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.69 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 177.55 | 1044.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 27334.40 | 05-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 685.65 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 21556.62 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 536.26 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 20731.40 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 413.44 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20127.31 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2552.47 | 31-MAY-16:10 | 13909.88 | 02-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8953.47 | 26-JUN-16:03 | 8637.02 | 09-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6933.44 | 17-JUL-11:03 | 8249.48 | 03-JUL-06:01 |
August | 1306.65 | 01-AUG-09:09 | 380.76 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7872.24 | 16-AUG-16:03 | 7460.39 | 17-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 380.42 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4252.20 | 12-SEP-16:05 | 15964.67 | 21-SEP-16:01 |
October | 1306.65 | 02-OCT-09:09 | 616.79 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 664.66 | 10-OCT-16:50 | 21914.08 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23592.38 | 29-NOV-17:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32643.39 | 21-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7460.39 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8953.47 | 32643.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 407.65 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 433.21 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 499.15 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 348.83 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 1042.33 | 19-MAR-06:55 |
April | 827.17 | 03-APR-09:09 | 309.64 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 700.60 | 15-APR-04:55 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 17-MAY-14:50 | 413.06 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 236.39 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.37 | 25-JUN-17:53 | 260.29 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 222.08 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.61 | 16-JUL-11:55 | 254.25 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 242.51 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.21 | 02-AUG-16:00 | 325.41 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 251.71 | 22-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.97 | 10-SEP-15:00 | 279.71 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 395.42 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 11-OCT-14:00 | 629.94 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 587.76 | 01-NOV-03:53 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 889.32 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.25 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 176.61 | 1042.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 931.22 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 688.55 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1141.08 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 549.71 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2380.60 | 19-MAR-06:55 |
April | 1306.65 | 03-APR-09:09 | 479.80 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1620.10 | 15-APR-04:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 17-MAY-14:50 | 941.75 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.24 | 25-JUN-17:43 | 563.61 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.90 | 16-JUL-11:53 | 558.41 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 386.60 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.22 | 02-AUG-16:00 | 677.23 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 390.42 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 | 10-SEP-15:00 | 633.06 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 626.99 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 11-OCT-14:00 | 1395.81 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1330.42 | 01-NOV-04:04 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2044.17 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.41 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 404.90 | 2380.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 622.53 | 13-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 435.98 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 771.72 | 23-FEB-24:00 |
March | 805.43 | 01-MAR-08:09 | 333.11 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1583.44 | 19-MAR-06:55 |
April | 805.43 | 03-APR-07:10 | 258.83 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1077.16 | 15-APR-04:55 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 17-MAY-14:50 | 628.86 | 03-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.30 | 25-JUN-17:43 | 376.85 | 08-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.02 | 16-JUL-11:53 | 379.98 | 02-JUL-08:30 |
August | 805.43 | 01-AUG-07:10 | 247.42 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.48 | 02-AUG-16:00 | 465.18 | 27-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 250.26 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 | 10-SEP-14:34 | 421.61 | 22-SEP-02:00 |
October | 805.43 | 02-OCT-07:10 | 390.30 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 11-OCT-14:10 | 934.39 | 29-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 894.13 | 01-NOV-04:03 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1354.87 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.85 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 270.02 | 1583.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 965.02 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 687.48 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1201.78 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 543.62 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2383.10 | 19-MAR-06:55 |
April | 1306.65 | 03-APR-09:09 | 475.85 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1627.86 | 15-APR-04:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 17-MAY-14:50 | 951.99 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.11 | 25-JUN-17:43 | 562.31 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.94 | 16-JUL-11:53 | 560.15 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 384.04 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.22 | 02-AUG-16:00 | 735.22 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 383.75 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.78 | 10-SEP-15:00 | 635.92 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 621.19 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 | 11-OCT-14:10 | 1424.92 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1341.39 | 01-NOV-04:03 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2074.69 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.15 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 404.94 | 2383.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 625.90 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 434.19 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 781.46 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 352.28 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1582.22 | 19-MAR-06:55 |
April | 827.17 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1073.85 | 15-APR-04:55 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 17-MAY-14:50 | 639.42 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 238.43 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.16 | 25-JUN-17:43 | 395.34 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 236.19 | 28-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.96 | 16-JUL-11:53 | 385.03 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 244.03 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.48 | 02-AUG-16:00 | 494.16 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 253.02 | 22-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.18 | 10-SEP-15:00 | 419.21 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 397.49 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 11-OCT-14:00 | 928.34 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 893.56 | 01-NOV-04:03 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1363.62 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.03 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 269.96 | 1582.22 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1359.29 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1624.89 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3460.22 | 19-MAR-06:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2334.80 | 15-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | 17-MAY-14:40 | 1336.49 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.65 | 25-JUN-18:00 | 756.18 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.07 | 16-JUL-12:00 | 748.51 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.16 | 06-AUG-12:00 | 883.04 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.51 | 10-SEP-15:00 | 889.21 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 11-OCT-14:00 | 2015.27 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1931.38 | 01-NOV-03:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2839.84 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.07 | 3460.22 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1686.88 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2047.39 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4259.91 | 19-MAR-06:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2921.76 | 15-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.09 | 17-MAY-14:40 | 1679.56 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.04 | 25-JUN-18:00 | 970.17 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.67 | 16-JUL-12:00 | 974.03 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.11 | 06-AUG-12:00 | 1135.20 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.24 | 10-SEP-15:00 | 1123.42 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 | 11-OCT-14:00 | 2461.62 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2338.39 | 01-NOV-03:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3562.48 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 970.17 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.67 | 4259.91 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1555.86 | 31-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2065.82 | 19-FEB-17:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4276.72 | 19-MAR-06:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2825.69 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 | 17-MAY-13:00 | 1570.80 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.22 | 25-JUN-17:40 | 969.03 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.40 | 16-JUL-12:00 | 972.25 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.99 | 02-AUG-16:00 | 1330.23 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.93 | 10-SEP-14:30 | 1082.67 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 | 11-OCT-14:00 | 2361.11 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2259.90 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3659.38 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.03 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.40 | 4276.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13775.61 | 26-JAN-16:40 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13175.52 | 22-FEB-08:06 | 30175.04 | 17443.51 | 63791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25452.13 | 15-MAR-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14584.92 | 13-APR-13:00 | 6035.01 | 3488.70 | 10947.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24733.60 | 22-MAY-06:03 | 5082.11 | 4651.60 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33139.32 | 26-JUN-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34076.99 | 24-JUL-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34173.63 | 28-AUG-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34436.16 | 05-SEP-05:12 | 3176.32 | 1938.17 | 20240.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32338.96 | 10-OCT-06:01 | 10164.22 | 9303.20 | 48352.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20908.51 | 09-NOV-07:01 | 8893.70 | 8140.30 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12904.65 | 05-DEC-08:06 | 30175.04 | 17443.51 | 63791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12904.65 | 2541.06 | 1550.53 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34436.16 | 30175.04 | 17443.51 | 63791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2765.16 | 20-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 |
February | 2865.49 | 18-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.12 |
March | 6714.08 | 14-MAR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.36 |
April | 5992.03 | 21-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.93 |
May | 8367.02 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.99 | 0.00 |
June | 11456.35 | 26-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 | 0.00 |
July | 9947.79 | 17-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.11 | 0.00 |
August | 11154.35 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 0.00 |
September | 8422.25 | 12-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.26 | 0.00 |
October | 6503.93 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 0.00 |
November | 3934.54 | 09-NOV-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 |
December | 1650.86 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1650.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11456.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.11 | 146.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2913.88 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.24 |
February | 2422.70 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.51 |
March | 2490.09 | 15-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.66 |
April | 2693.51 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.01 |
May | 2533.82 | 18-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
June | 5101.02 | 26-JUN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.13 | 0.00 |
July | 5463.39 | 17-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 | 0.00 |
August | 4626.65 | 21-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 | 0.00 |
September | 4569.88 | 05-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
October | 3014.81 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 0.00 |
November | 1874.61 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.43 |
December | 3449.50 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1536.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1874.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5463.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 | 1536.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2378.38 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 |
February | 2565.00 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.58 |
March | 2547.44 | 25-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.40 |
April | 2383.07 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.09 |
May | 2484.93 | 18-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 |
June | 5615.34 | 26-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.18 | 0.00 |
July | 5655.53 | 17-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 | 0.00 |
August | 4441.74 | 21-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
September | 4998.12 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.12 |
October | 3268.83 | 11-OCT-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
November | 2066.09 | 30-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.52 |
December | 3019.79 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2066.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5655.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 | 1237.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9276.97 | 25-JAN-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8878.20 | 27-FEB-16:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13144.27 | 15-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11580.57 | 21-APR-14:00 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13557.19 | 18-MAY-15:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28408.70 | 26-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28905.94 | 24-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29040.22 | 07-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30169.15 | 05-SEP-05:12 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26112.81 | 10-OCT-06:01 | 10164.22 | 9303.20 | 24207.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11420.65 | 08-NOV-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7205.68 | 15-DEC-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7205.68 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30169.15 | 10164.22 | 9303.20 | 24207.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8313.61 | 20-JAN-16:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8014.01 | 27-FEB-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14231.41 | 15-MAR-15:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13209.65 | 21-APR-14:00 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15240.71 | 31-MAY-15:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30391.96 | 26-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31034.90 | 24-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30684.53 | 21-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30858.22 | 05-SEP-05:12 | 3176.32 | 1938.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14982.26 | 11-OCT-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10722.36 | 08-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6029.29 | 15-DEC-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6029.29 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31034.90 | 6198.29 | 3488.70 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1420.71 | 20-JAN-14:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 |
February | 1226.80 | 27-FEB-13:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.20 |
March | 3582.39 | 14-MAR-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
April | 3571.82 | 20-APR-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
May | 5496.62 | 17-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 0.00 |
June | 11052.06 | 25-JUN-17:52 | 0.00 | 116.92 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 283.34 | 0.00 |
July | 11162.41 | 16-JUL-14:32 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 399.94 | 0.00 |
August | 6682.44 | 20-AUG-15:42 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 0.00 |
September | 6557.74 | 10-SEP-14:42 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 178.07 | 0.00 |
October | 3968.33 | 11-OCT-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 0.00 |
November | 2348.94 | 09-NOV-13:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 |
December | 1124.10 | 01-DEC-13:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1124.10 | 0.00 | 97.43 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11162.41 | 1306.65 | 350.81 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 399.94 | 213.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2659.43 | 20-JAN-09:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.12 |
February | 3833.77 | 27-FEB-09:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.51 |
March | 8219.26 | 12-MAR-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.84 |
April | 7110.62 | 21-APR-08:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.42 |
May | 7771.22 | 16-MAY-08:30 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 |
June | 10718.49 | 11-JUN-09:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.62 |
July | 13485.89 | 16-JUL-09:12 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 | 0.00 |
August | 13542.24 | 06-AUG-09:12 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 |
September | 11176.17 | 04-SEP-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 |
October | 7921.96 | 01-OCT-09:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.67 |
November | 3733.55 | 07-NOV-09:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 |
December | 1050.21 | 01-DEC-09:25 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1050.21 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13542.24 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 | 433.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12903.41 | 22-JAN-14:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.12 |
February | 15545.44 | 26-FEB-13:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.20 |
March | 16725.00 | 12-MAR-12:42 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.14 |
April | 9137.98 | 21-APR-13:10 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
May | 8047.76 | 16-MAY-13:10 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 | 0.00 |
June | 14451.08 | 25-JUN-14:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 79.89 | 0.00 |
July | 15322.41 | 30-JUL-13:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 0.00 |
August | 15149.22 | 06-AUG-12:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 94.98 | 0.00 |
September | 16313.17 | 04-SEP-13:12 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 46.49 | 0.00 |
October | 17990.59 | 09-OCT-13:21 | 535.68 | 155.89 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 |
November | 17499.84 | 05-NOV-13:11 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 |
December | 14921.20 | 03-DEC-13:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8047.76 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17990.59 | 2613.31 | 701.62 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 94.98 | 688.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4818.14 | 20-JAN-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
February | 5188.38 | 17-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.59 |
March | 15324.73 | 12-MAR-16:02 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.14 |
April | 9871.07 | 08-APR-17:06 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.97 |
May | 9570.76 | 28-MAY-15:02 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.92 |
June | 15968.75 | 11-JUN-16:21 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 0.00 |
July | 15868.45 | 02-JUL-16:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 |
August | 15531.54 | 13-AUG-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.76 |
September | 15748.01 | 10-SEP-16:01 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 41.95 | 0.00 |
October | 15998.11 | 09-OCT-16:01 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.70 |
November | 7273.83 | 05-NOV-15:12 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.25 |
December | 3580.80 | 01-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3580.80 | 169.55 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15998.11 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 41.95 | 272.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1278.61 | 20-JAN-14:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
February | 1182.70 | 24-FEB-13:05 | 7633.40 | 2104.85 | 8611.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.44 |
March | 1578.85 | 14-MAR-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 |
April | 1364.53 | 20-APR-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 |
May | 3659.56 | 17-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 0.00 |
June | 6434.58 | 26-JUN-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 |
July | 6953.39 | 17-JUL-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
August | 5155.03 | 21-AUG-13:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 0.00 |
September | 6129.56 | 05-SEP-06:02 | 1607.03 | 1136.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.36 |
October | 3250.48 | 11-OCT-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
November | 1920.17 | 09-NOV-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
December | 1178.92 | 03-DEC-15:23 | 267.84 | 101.77 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1178.92 | 267.84 | 101.77 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6953.39 | 7633.40 | 2104.85 | 8611.48 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 194.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1780.74 | 25-JAN-08:40 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.26 |
February | 3086.02 | 27-FEB-08:35 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 |
March | 4549.44 | 15-MAR-08:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 |
April | 4742.42 | 21-APR-08:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 |
May | 6085.98 | 11-MAY-06:03 | 678.26 | 296.12 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 |
June | 10670.25 | 18-JUN-10:02 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 |
July | 10578.13 | 16-JUL-09:12 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 0.00 |
August | 11470.14 | 06-AUG-09:01 | 339.13 | 98.69 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 |
September | 10851.32 | 04-SEP-10:22 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 |
October | 6269.08 | 01-OCT-09:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.04 |
November | 3423.50 | 07-NOV-08:25 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 |
December | 1393.70 | 18-DEC-08:33 | 2416.29 | 666.27 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1393.70 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11470.14 | 2416.29 | 666.27 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 229.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9627.45 | 24-JAN-14:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.50 |
February | 12456.95 | 26-FEB-13:52 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.34 |
March | 11509.48 | 12-MAR-12:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.32 |
April | 5504.93 | 21-APR-12:08 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.20 |
May | 6558.31 | 16-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1993.01 | 0.00 |
June | 10930.12 | 26-JUN-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6851.70 | 0.00 |
July | 10888.69 | 17-JUL-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6826.43 | 0.00 |
August | 12243.88 | 06-AUG-11:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 | 0.00 |
September | 13222.48 | 04-SEP-12:21 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 0.00 |
October | 13952.97 | 09-OCT-13:21 | 535.68 | 155.89 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.35 |
November | 12503.28 | 05-NOV-13:22 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 |
December | 12357.46 | 17-DEC-15:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5504.93 | 267.84 | 77.95 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13952.97 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 6851.70 | 873.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3573.87 | 23-JAN-16:10 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
February | 3772.28 | 17-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
March | 6899.21 | 12-MAR-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.58 |
April | 6305.75 | 08-APR-17:06 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.45 |
May | 5875.77 | 31-MAY-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 0.00 |
June | 12286.97 | 04-JUN-16:51 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 | 0.00 |
July | 12171.44 | 02-JUL-17:21 | 0.00 | 111.02 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 0.00 |
August | 12899.08 | 13-AUG-17:41 | 0.00 | 98.69 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 |
September | 12343.36 | 10-SEP-17:51 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 |
October | 12366.81 | 09-OCT-16:01 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 |
November | 5204.27 | 07-NOV-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
December | 2888.54 | 04-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2888.54 | 0.00 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12899.08 | 805.38 | 222.08 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 | 143.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1424.72 | 20-JAN-15:00 | 1306.65 | 373.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 |
February | 1413.01 | 27-FEB-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.56 |
March | 3397.32 | 14-MAR-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 |
April | 3167.27 | 20-APR-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
May | 5169.49 | 17-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 | 0.00 |
June | 9546.67 | 25-JUN-16:21 | 669.60 | 194.87 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 149.59 | 0.00 |
July | 9590.12 | 16-JUL-13:42 | 334.80 | 97.43 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 294.82 | 0.00 |
August | 6961.22 | 21-AUG-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 |
September | 6828.42 | 11-SEP-06:03 | 1071.35 | 660.21 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 |
October | 3848.50 | 10-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 0.00 |
November | 2514.64 | 09-NOV-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 |
December | 1282.87 | 14-DEC-13:50 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1282.87 | 334.80 | 97.43 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9590.12 | 1306.65 | 660.21 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 294.82 | 182.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4304.61 | 26-JAN-13:02 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 |
February | 4970.23 | 27-FEB-09:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.92 |
March | 9900.26 | 12-MAR-09:32 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.31 |
April | 7457.71 | 21-APR-08:70 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.81 |
May | 9447.60 | 28-MAY-09:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.53 |
June | 13842.20 | 11-JUN-08:52 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.21 |
July | 14352.33 | 16-JUL-08:21 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.99 | 0.00 |
August | 14800.79 | 06-AUG-09:01 | 339.13 | 98.69 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 |
September | 13782.39 | 04-SEP-08:22 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.26 |
October | 9757.87 | 01-OCT-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.03 |
November | 4759.12 | 07-NOV-08:50 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 |
December | 2048.70 | 01-DEC-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2048.70 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14800.79 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 64.99 | 374.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14104.75 | 22-JAN-14:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.58 |
February | 14401.06 | 26-FEB-13:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.81 |
March | 14244.04 | 12-MAR-12:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.73 |
April | 8697.72 | 21-APR-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.86 |
May | 7543.22 | 16-MAY-13:10 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 24.07 | 0.00 |
June | 13551.62 | 25-JUN-16:21 | 669.60 | 194.87 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 150.61 | 0.00 |
July | 13920.14 | 23-JUL-11:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 37.03 | 0.00 |
August | 14564.28 | 06-AUG-11:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 82.23 | 0.00 |
September | 15727.61 | 04-SEP-11:41 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 |
October | 15061.20 | 09-OCT-12:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.36 |
November | 14854.84 | 05-NOV-12:42 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.85 |
December | 14257.85 | 17-DEC-12:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7543.22 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15727.61 | 2613.31 | 701.62 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 150.61 | 577.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4765.29 | 20-JAN-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 |
February | 5203.21 | 17-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 |
March | 9905.50 | 12-MAR-16:12 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.61 |
April | 9571.83 | 08-APR-17:06 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.56 |
May | 8825.68 | 28-MAY-15:32 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.08 |
June | 15946.90 | 25-JUN-16:21 | 423.88 | 123.36 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | 0.00 |
July | 14675.34 | 02-JUL-16:31 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 0.00 |
August | 15640.10 | 13-AUG-17:41 | 0.00 | 98.69 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 |
September | 15335.76 | 17-SEP-16:11 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 |
October | 11652.49 | 09-OCT-15:32 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.51 |
November | 6023.03 | 07-NOV-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
December | 3564.54 | 01-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3564.54 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15946.90 | 805.38 | 222.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | 226.56 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.945350E+11 | 148111.89 | 05-JAN-07:10 | 0.413515E+11 | 97996.29 | 05-JAN-07:30 |
February | 0.908386E+11 | 188377.46 | 06-FEB-07:10 | 0.398693E+11 | 72338.35 | 02-FEB-07:30 |
March | 0.950508E+11 | 157348.72 | 20-MAR-06:10 | 0.318808E+11 | 64515.27 | 04-MAR-07:30 |
April | 0.827373E+11 | 145901.61 | 03-APR-06:10 | 0.232177E+11 | 66955.55 | 17-APR-06:30 |
May | 0.906041E+11 | 104628.32 | 31-MAY-15:20 | 0.127472E+11 | 39015.39 | 02-MAY-06:19 |
June | 0.125420E+12 | 159361.83 | 26-JUN-15:09 | 0.109036E+11 | 10256.37 | 09-JUN-06:10 |
July | 0.122575E+12 | 143745.88 | 17-JUL-10:50 | 0.105686E+11 | 9831.56 | 03-JUL-11:00 |
August | 0.126643E+12 | 141700.22 | 16-AUG-14:00 | 0.109806E+11 | 9784.84 | 01-AUG-11:09 |
September | 0.104599E+12 | 124246.86 | 12-SEP-15:39 | 0.112071E+11 | 38938.10 | 22-SEP-06:10 |
October | 0.923631E+11 | 141015.71 | 30-OCT-06:10 | 0.245903E+11 | 77182.36 | 30-OCT-06:30 |
November | 0.890212E+11 | 133472.35 | 30-NOV-07:10 | 0.339278E+11 | 81087.42 | 29-NOV-20:00 |
December | 0.105433E+12 | 184055.90 | 26-DEC-07:10 | 0.508714E+11 | 99260.88 | 21-DEC-09:20 |
Annual Sum or Average | 0.121982E+13 | 0.302116E+12 | ||||
Minimum of Months | 0.827373E+11 | 104628.32 | 0.105686E+11 | 9784.84 | ||
Maximum of Months | 0.126643E+12 | 188377.46 | 0.508714E+11 | 99260.88 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.760930E+10 | 17000.11 | 31-JAN-12:30 | 0.00 | 0.00 |
February | 0.961065E+10 | 20259.14 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.129606E+11 | 25643.75 | 28-MAR-12:09 | 0.00 | 0.00 |
April | 0.136047E+11 | 26811.28 | 26-APR-12:30 | 0.00 | 0.00 |
May | 0.172350E+11 | 24641.49 | 27-MAY-11:30 | 0.00 | 0.00 |
June | 0.197774E+11 | 25870.85 | 16-JUN-11:00 | 0.00 | 0.00 |
July | 0.179169E+11 | 26223.18 | 01-JUL-11:50 | 0.00 | 0.00 |
August | 0.176447E+11 | 24029.60 | 04-AUG-11:50 | 0.00 | 0.00 |
September | 0.139015E+11 | 22118.82 | 05-SEP-11:00 | 0.00 | 0.00 |
October | 0.108111E+11 | 21224.89 | 01-OCT-11:30 | 0.00 | 0.00 |
November | 0.805312E+10 | 18174.43 | 01-NOV-11:30 | 0.00 | 0.00 |
December | 0.655144E+10 | 14083.28 | 22-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.155676E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.655144E+10 | 14083.28 | 0.00 | 0.00 | |
Maximum of Months | 0.197774E+11 | 26811.28 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.143157E+11 | 0.387111E+10 | 0.545046E+11 | 0.976693E+09 | 0.430944E+10 | 12379742.02 | 0.155793E+11 | 0.965750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127784E+11 | 0.311835E+10 | 0.493409E+11 | 0.883753E+09 | 0.411946E+10 | 11196021.66 | 0.199303E+11 | 0.656325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149200E+11 | 0.292505E+10 | 0.567112E+11 | 0.102244E+10 | 0.559254E+10 | 12675672.10 | 0.116160E+11 | 0.225087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132200E+11 | 0.235678E+10 | 0.526212E+11 | 0.940430E+09 | 0.460713E+10 | 11960507.72 | 0.699583E+10 | 0.198396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141567E+11 | 0.210763E+10 | 0.556079E+11 | 0.999257E+09 | 0.782271E+10 | 12527707.06 | 0.838278E+09 | 0.905913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140420E+11 | 0.190756E+10 | 0.546110E+11 | 0.983595E+09 | 0.171591E+11 | 12231776.97 | 11411829.26 | 0.366932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131763E+11 | 0.202103E+10 | 0.536070E+11 | 0.955904E+09 | 0.162179E+11 | 12256437.81 | 3615660.07 | 0.365815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147365E+11 | 0.227746E+10 | 0.567112E+11 | 0.102234E+10 | 0.166261E+11 | 12675672.10 | 1173257.99 | 0.352560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132596E+11 | 0.260525E+10 | 0.525990E+11 | 0.940212E+09 | 0.123132E+11 | 11960507.72 | 0.149702E+09 | 0.227198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139841E+11 | 0.323314E+10 | 0.545158E+11 | 0.976507E+09 | 0.643449E+10 | 12379742.02 | 0.778915E+10 | 0.541765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141265E+11 | 0.360566E+10 | 0.533244E+11 | 0.958520E+09 | 0.467922E+10 | 12059151.09 | 0.104056E+11 | 0.190926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139337E+11 | 0.400421E+10 | 0.535958E+11 | 0.956364E+09 | 0.436220E+10 | 12256437.81 | 0.278161E+11 | 0.752618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166649E+12 | 0.340332E+11 | 0.647750E+12 | 0.116160E+11 | 0.104243E+12 | 0.146559E+09 | 0.101137E+12 | 0.154246E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127784E+11 | 0.190756E+10 | 0.493409E+11 | 0.883753E+09 | 0.411946E+10 | 11196021.66 | 1173257.99 | 0.656325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149200E+11 | 0.400421E+10 | 0.567112E+11 | 0.102244E+10 | 0.171591E+11 | 12675672.10 | 0.278161E+11 | 0.366932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.295108E+11 | 0.00 | 0.118407E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.290730E+11 | 0.00 | 0.107963E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.196192E+11 | 0.00 | 0.122616E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.120067E+11 | 0.00 | 0.112110E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.128549E+10 | 0.00 | 0.114617E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1314318.66 | 0.00 | 0.109023E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.105686E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.109806E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.835018E+09 | 0.00 | 0.103721E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136261E+11 | 0.00 | 0.109642E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.229247E+11 | 0.00 | 0.110031E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.394048E+11 | 0.00 | 0.114666E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168287E+12 | 0.00 | 0.133829E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.103721E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.394048E+11 | 0.00 | 0.122616E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-16:49 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 828.65 | 02-JAN-16:00 | 7351.53 | 24-JAN-16:10 | 6.85 | 03-JAN-06:10 | 115642.38 | 05-JAN-07:10 |
February | 17199.23 | 06-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 827.81 | 06-FEB-16:00 | 7523.30 | 27-FEB-15:30 | 6.85 | 02-FEB-12:09 | 158129.76 | 06-FEB-07:10 |
March | 15780.20 | 21-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 827.29 | 21-MAR-07:19 | 17805.98 | 15-MAR-15:00 | 6.85 | 01-MAR-08:09 | 128413.38 | 20-MAR-06:10 |
April | 14918.27 | 03-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 826.16 | 03-APR-07:19 | 10909.81 | 21-APR-13:30 | 6.85 | 04-APR-06:10 | 117522.30 | 03-APR-06:10 |
May | 13903.46 | 01-MAY-07:10 | 2323.70 | 01-MAY-18:49 | 40437.79 | 01-MAY-07:10 | 824.82 | 01-MAY-07:19 | 17394.74 | 18-MAY-14:30 | 6.85 | 11-MAY-16:10 | 48893.08 | 01-MAY-06:10 |
June | 13950.50 | 16-JUN-07:10 | 2323.70 | 01-JUN-19:19 | 40437.79 | 01-JUN-07:10 | 824.88 | 16-JUN-07:19 | 30941.78 | 26-JUN-15:09 | 6.85 | 04-JUN-14:00 | 4800.63 | 09-JUN-06:19 |
July | 13931.69 | 28-JUL-07:10 | 2323.70 | 01-JUL-19:30 | 40437.79 | 03-JUL-07:10 | 824.86 | 28-JUL-07:19 | 32342.68 | 24-JUL-15:20 | 6.85 | 02-JUL-15:50 | 1392.54 | 03-JUL-06:00 |
August | 14178.45 | 28-AUG-15:00 | 3824.74 | 10-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 824.91 | 21-AUG-07:19 | 27727.90 | 11-AUG-14:00 | 6.85 | 05-AUG-16:10 | 925.59 | 23-AUG-06:10 |
September | 14197.81 | 21-SEP-15:00 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 825.05 | 22-SEP-07:19 | 26246.49 | 05-SEP-15:39 | 6.85 | 04-SEP-13:09 | 22630.17 | 22-SEP-06:10 |
October | 16561.09 | 30-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 828.32 | 30-OCT-07:19 | 17744.92 | 11-OCT-15:00 | 6.85 | 07-OCT-16:10 | 108700.24 | 30-OCT-06:10 |
November | 17672.30 | 06-NOV-16:49 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 828.65 | 06-NOV-16:00 | 9795.16 | 07-NOV-15:00 | 6.85 | 01-NOV-06:10 | 105107.71 | 30-NOV-07:10 |
December | 17672.30 | 01-DEC-16:30 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.65 | 01-DEC-16:40 | 5353.62 | 15-DEC-15:09 | 6.85 | 11-DEC-07:10 | 150404.51 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 13903.46 | 2323.70 | 40437.79 | 824.82 | 5353.62 | 6.85 | 925.59 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 40437.79 | 828.65 | 32342.68 | 6.85 | 158129.76 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 13705.17 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 10100.86 | 18-FEB-13:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 23301.46 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 15597.94 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34094.97 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 75231.58 | 26-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 62091.06 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 62820.36 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 47184.83 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 34553.51 | 11-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 18364.48 | 07-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13104.32 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10100.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 75231.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 148111.89 | 05-JAN-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 4157.90 | 6.85 | 115642.38 | 0.00 | 0.00 |
February | 188377.46 | 06-FEB-07:10 | 5890.77 | 18346.02 | 0.00 | 243.23 | 5760.83 | 6.85 | 158129.76 | 0.00 | 0.00 |
March | 157348.72 | 20-MAR-06:10 | 5890.77 | 18346.02 | 0.00 | 243.23 | 4448.47 | 6.85 | 128413.38 | 0.00 | 0.00 |
April | 145901.61 | 03-APR-06:10 | 5585.81 | 18346.02 | 0.00 | 243.20 | 4197.44 | 6.85 | 117522.30 | 0.00 | 0.00 |
May | 104628.32 | 31-MAY-15:20 | 13903.46 | 38454.47 | 0.00 | 823.69 | 17344.87 | 6.85 | 0.00 | 34094.97 | 0.00 |
June | 159361.83 | 26-JUN-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 30941.78 | 6.85 | 0.00 | 75231.58 | 0.00 |
July | 143745.88 | 17-JUL-10:50 | 13903.46 | 38195.78 | 0.00 | 823.54 | 30637.07 | 6.85 | 0.00 | 60179.19 | 0.00 |
August | 141700.22 | 16-AUG-14:00 | 13903.46 | 37678.39 | 0.00 | 823.25 | 27045.35 | 6.85 | 0.00 | 62242.92 | 0.00 |
September | 124246.86 | 12-SEP-15:39 | 13903.46 | 38454.47 | 0.00 | 823.69 | 24104.81 | 6.85 | 0.00 | 46953.58 | 0.00 |
October | 141015.71 | 30-OCT-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 4003.87 | 6.85 | 108700.24 | 0.00 | 0.00 |
November | 133472.35 | 30-NOV-07:10 | 5890.77 | 18346.02 | 0.00 | 243.23 | 3877.78 | 6.85 | 105107.71 | 0.00 | 0.00 |
December | 184055.90 | 26-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 5339.78 | 6.85 | 150404.51 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 104628.32 | 5585.81 | 18346.02 | 0.00 | 243.20 | 3877.78 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 188377.46 | 13903.46 | 38454.47 | 3824.74 | 823.69 | 30941.78 | 6.85 | 158129.76 | 75231.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 89090.69 | 05-JAN-07:30 | 0.00 | 10266.51 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 63540.98 | 06-FEB-08:09 | 0.00 | 10526.48 | 06-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 56491.27 | 04-MAR-07:10 | 0.00 | 10389.01 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 58074.34 | 17-APR-06:30 | 0.00 | 10190.57 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 30157.84 | 02-MAY-06:19 | 0.00 | 10071.92 | 03-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 1459.07 | 09-JUN-06:10 | 0.00 | 9940.40 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9831.56 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9784.84 | 01-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 32533.09 | 22-SEP-06:30 | 0.00 | 9840.00 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 68466.48 | 30-OCT-06:40 | 0.00 | 9965.81 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 72292.54 | 29-NOV-20:00 | 0.00 | 10082.88 | 28-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 89794.52 | 21-DEC-08:09 | 0.00 | 10193.70 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9784.84 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 89794.52 | 0.00 | 10526.48 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 17.38 | 0.17 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 18.91 | 0.33 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Annual Sum or Average | 0.83 | 17.99 | 0.50 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.91 | 0.33 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 16.88 | 0.83 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
February | 12.00 | 16.02 | 4.33 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
March | 3.00 | 15.11 | 1.67 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
April | 2.17 | 16.87 | 0.50 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.58 | 1.67 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.54 | 5.50 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.28 | 1.00 | 27.28 |
October | 1.00 | 17.96 | 0.50 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
November | 1.33 | 16.81 | 0.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
December | 24.17 | 16.31 | 9.17 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
Annual Sum or Average | 46.50 | 16.27 | 17.17 | 16.75 | 10.67 | 18.29 | 8.50 | 19.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.17 | 17.96 | 9.17 | 18.50 | 6.83 | 27.58 | 5.50 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 16.23 | 0.17 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
February | 9.50 | 14.98 | 1.67 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
March | 4.17 | 14.95 | 1.50 | 14.82 | 0.67 | 16.16 | 0.67 | 17.24 |
April | 2.50 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.55 | 0.83 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.78 | 10.33 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 28.02 | 15.17 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.03 | 6.67 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.73 | 6.17 | 27.74 |
October | 0.83 | 15.78 | 0.00 | 15.78 | 1.50 | 23.31 | 1.50 | 24.94 |
November | 1.33 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
December | 15.33 | 14.94 | 1.50 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Annual Sum or Average | 35.67 | 15.15 | 4.83 | 15.13 | 44.00 | 21.77 | 41.33 | 23.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 | 0.00 | 14.96 |
Maximum of Months | 15.33 | 16.24 | 1.67 | 16.24 | 16.67 | 28.03 | 15.17 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 16.92 | 0.00 | 16.92 | 1.00 | 22.80 | 1.00 | 24.53 |
February | 6.33 | 15.26 | 1.17 | 15.30 | 1.67 | 17.59 | 1.67 | 19.17 |
March | 2.83 | 14.90 | 1.50 | 14.77 | 1.83 | 18.71 | 1.83 | 20.84 |
April | 1.50 | 16.32 | 0.17 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.66 | 5.83 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.78 | 9.67 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.86 | 6.17 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.33 | 10.33 | 27.32 |
October | 0.67 | 17.13 | 0.17 | 17.57 | 8.50 | 26.57 | 8.50 | 26.99 |
November | 1.17 | 16.58 | 0.00 | 16.58 | 3.83 | 25.31 | 3.83 | 26.46 |
December | 9.83 | 15.11 | 1.17 | 15.18 | 2.33 | 17.41 | 2.33 | 18.98 |
Annual Sum or Average | 23.17 | 15.40 | 4.17 | 15.42 | 53.67 | 23.53 | 51.33 | 25.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 0.00 | 16.61 |
Maximum of Months | 9.83 | 17.13 | 1.50 | 17.57 | 11.00 | 27.86 | 10.33 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 9.50 | 15.01 | 2.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
March | 4.33 | 14.95 | 1.50 | 14.82 | 1.33 | 17.26 | 1.00 | 18.58 |
April | 2.50 | 15.48 | 0.00 | 15.48 | 0.17 | 16.27 | 0.17 | 16.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.58 | 3.00 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.45 | 5.67 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.11 | 8.33 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.18 | 4.00 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.19 | 5.50 | 28.22 |
October | 1.00 | 15.64 | 0.00 | 15.64 | 2.83 | 24.82 | 2.50 | 26.12 |
November | 1.33 | 16.27 | 0.00 | 16.27 | 0.33 | 18.51 | 0.33 | 20.00 |
December | 15.33 | 14.94 | 2.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
Annual Sum or Average | 35.17 | 15.13 | 6.00 | 15.10 | 42.50 | 21.73 | 30.50 | 23.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.98 | 0.00 | 14.98 |
Maximum of Months | 15.33 | 16.82 | 2.33 | 16.82 | 11.83 | 28.45 | 8.33 | 28.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 19.32 | 2.17 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 18.40 | 0.67 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Annual Sum or Average | 4.00 | 19.06 | 3.00 | 19.37 | 0.17 | 19.55 | 0.17 | 19.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.40 | 2.17 | 19.57 | 0.17 | 27.30 | 0.17 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.53 | 4.83 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.66 | 12.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.72 | 5.83 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.54 | 5.50 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.39 | 1.83 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
Annual Sum or Average | 1.17 | 16.93 | 0.00 | 16.93 | 30.67 | 27.22 | 30.50 | 27.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 16.97 | 0.00 | 16.97 | 12.67 | 27.72 | 12.50 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 18.12 | 30.17 | 18.12 | 1.33 | 18.33 | 1.33 | 18.52 |
February | 33.83 | 18.08 | 33.50 | 18.09 | 1.33 | 18.28 | 1.33 | 18.46 |
March | 25.67 | 18.63 | 25.67 | 18.63 | 1.33 | 18.86 | 1.33 | 19.08 |
April | 17.17 | 18.65 | 17.17 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
May | 2.83 | 19.16 | 2.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 25.16 | 5.50 | 25.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.35 | 4.00 | 26.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 25.84 | 12.33 | 25.84 |
September | 1.00 | 19.37 | 1.00 | 19.37 | 15.83 | 25.65 | 15.00 | 25.98 |
October | 15.83 | 17.82 | 15.83 | 17.82 | 15.83 | 20.70 | 15.17 | 22.09 |
November | 24.83 | 18.33 | 24.83 | 18.33 | 6.50 | 19.30 | 6.50 | 20.07 |
December | 39.33 | 17.44 | 38.83 | 17.44 | 2.67 | 17.79 | 2.67 | 18.11 |
Annual Sum or Average | 190.67 | 18.11 | 189.83 | 18.12 | 66.67 | 19.35 | 65.17 | 20.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | 0.00 | 18.11 |
Maximum of Months | 39.33 | 19.37 | 38.83 | 19.37 | 15.83 | 26.35 | 15.17 | 26.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.33 | 27.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.67 | 0.17 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.05 | 3.50 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.85 | 4.67 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.96 | 2.67 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.83 | 5.17 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.91 | 2.00 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
Annual Sum or Average | 1.00 | 16.93 | 0.00 | 16.93 | 26.67 | 27.51 | 18.67 | 27.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 16.95 | 0.00 | 16.95 | 6.83 | 28.05 | 5.17 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.33 | 18.59 | 0.83 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
March | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
April | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.00 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.48 | 2.67 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
December | 3.17 | 16.56 | 1.33 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
Annual Sum or Average | 5.00 | 17.16 | 2.17 | 17.56 | 4.33 | 21.29 | 3.67 | 22.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 18.59 | 1.33 | 19.02 | 2.83 | 27.48 | 2.67 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 0.67 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
March | 0.17 | 17.16 | 0.00 | 17.16 | 0.83 | 26.00 | 0.83 | 26.81 |
April | 0.17 | 17.16 | 0.00 | 17.16 | 0.50 | 24.86 | 0.50 | 25.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.78 | 0.83 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.72 | 9.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.97 | 14.33 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.03 | 6.17 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.75 | 6.17 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.33 | 27.70 |
November | 0.33 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
December | 2.67 | 15.66 | 0.50 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
Annual Sum or Average | 4.33 | 16.18 | 0.50 | 16.19 | 41.00 | 26.63 | 40.17 | 27.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 0.00 | 15.76 |
Maximum of Months | 2.67 | 17.21 | 0.50 | 17.21 | 14.83 | 28.03 | 14.33 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.31 | 5.83 | 26.31 |
February | 0.50 | 16.85 | 0.00 | 16.85 | 2.50 | 26.06 | 2.50 | 26.89 |
March | 0.17 | 17.22 | 0.00 | 17.22 | 2.00 | 27.14 | 2.00 | 27.54 |
April | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.50 | 4.50 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.58 | 9.17 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.79 | 5.33 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.06 | 11.83 | 27.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.78 | 13.00 | 26.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.61 | 10.00 | 26.61 |
December | 1.00 | 16.81 | 0.33 | 16.88 | 2.83 | 24.51 | 2.83 | 25.97 |
Annual Sum or Average | 1.83 | 16.89 | 0.33 | 16.92 | 68.00 | 26.82 | 67.00 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 17.22 | 0.33 | 17.22 | 13.00 | 27.79 | 13.00 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 0.67 | 16.82 | 0.00 | 16.82 | 0.17 | 18.91 | 0.17 | 20.31 |
March | 0.17 | 17.16 | 0.00 | 17.16 | 1.33 | 26.75 | 1.00 | 27.25 |
April | 0.17 | 17.08 | 0.00 | 17.08 | 0.17 | 22.55 | 0.17 | 24.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.56 | 2.33 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.33 | 4.83 | 28.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.01 | 7.17 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.15 | 3.33 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.10 | 5.17 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.08 | 2.67 | 28.10 |
November | 0.33 | 17.13 | 0.00 | 17.13 | 0.33 | 22.33 | 0.33 | 24.06 |
December | 2.50 | 15.75 | 0.67 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
Annual Sum or Average | 4.00 | 16.22 | 0.67 | 16.17 | 37.67 | 26.77 | 27.17 | 27.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 0.00 | 15.78 |
Maximum of Months | 2.50 | 17.21 | 0.67 | 17.21 | 10.00 | 28.33 | 7.17 | 28.40 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.50 | 23.48 | 0.00 | 23.48 | 0.00 | 23.48 |
February | 430.33 | 23.39 | 4.00 | 23.37 | 4.00 | 23.35 |
March | 477.83 | 23.67 | 1.50 | 23.68 | 0.00 | 23.68 |
April | 388.33 | 23.79 | 4.33 | 23.81 | 0.00 | 23.81 |
May | 146.67 | 23.96 | 105.67 | 24.43 | 0.00 | 24.43 |
June | 5.83 | 24.00 | 269.33 | 24.49 | 0.33 | 24.49 |
July | 30.67 | 24.35 | 321.83 | 24.49 | 22.67 | 24.49 |
August | 2.00 | 24.13 | 307.67 | 24.53 | 0.17 | 24.53 |
September | 52.33 | 24.01 | 140.17 | 24.70 | 0.00 | 24.70 |
October | 258.50 | 23.92 | 24.50 | 24.05 | 0.00 | 24.05 |
November | 379.00 | 23.82 | 3.00 | 23.83 | 0.00 | 23.83 |
December | 497.00 | 23.30 | 24.33 | 23.20 | 24.33 | 23.10 |
Annual Sum or Average | 3154.00 | 23.62 | 1206.33 | 23.88 | 51.50 | 23.87 |
Minimum of Months | 2.00 | 23.30 | 0.00 | 23.20 | 0.00 | 23.10 |
Maximum of Months | 497.00 | 24.35 | 321.83 | 24.70 | 24.33 | 24.70 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.33 | 22.51 | 61.17 | 22.32 | 61.17 | 22.18 |
February | 452.67 | 22.50 | 72.00 | 22.26 | 72.00 | 22.08 |
March | 491.67 | 22.91 | 24.33 | 22.80 | 24.33 | 22.71 |
April | 448.50 | 23.06 | 9.83 | 23.02 | 8.50 | 22.98 |
May | 207.33 | 23.74 | 41.67 | 23.90 | 0.00 | 23.90 |
June | 15.00 | 24.01 | 258.17 | 24.40 | 0.00 | 24.40 |
July | 39.50 | 24.22 | 295.67 | 24.43 | 27.50 | 24.42 |
August | 8.00 | 24.03 | 267.67 | 24.46 | 0.17 | 24.46 |
September | 130.67 | 23.93 | 105.67 | 24.36 | 0.00 | 24.36 |
October | 389.17 | 23.41 | 14.33 | 23.36 | 10.83 | 23.30 |
November | 469.67 | 22.99 | 8.50 | 22.96 | 8.50 | 22.92 |
December | 497.00 | 22.13 | 105.33 | 21.84 | 105.33 | 21.64 |
Annual Sum or Average | 3648.50 | 22.88 | 1264.33 | 23.08 | 318.33 | 22.95 |
Minimum of Months | 8.00 | 22.13 | 8.50 | 21.84 | 0.00 | 21.64 |
Maximum of Months | 499.33 | 24.22 | 295.67 | 24.46 | 105.33 | 24.46 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.66 | 155.83 | 21.33 | 155.83 | 21.13 |
February | 454.00 | 21.77 | 160.17 | 21.41 | 160.17 | 21.20 |
March | 506.83 | 22.36 | 91.17 | 22.03 | 91.17 | 21.79 |
April | 459.00 | 22.49 | 79.50 | 22.18 | 79.50 | 21.95 |
May | 267.33 | 23.54 | 32.83 | 23.59 | 3.00 | 23.56 |
June | 21.67 | 23.91 | 258.33 | 24.37 | 0.00 | 24.37 |
July | 34.00 | 24.18 | 303.67 | 24.41 | 27.00 | 24.40 |
August | 22.50 | 23.94 | 263.33 | 24.37 | 0.17 | 24.37 |
September | 169.17 | 23.69 | 85.83 | 24.04 | 0.00 | 24.04 |
October | 458.33 | 22.87 | 58.17 | 22.63 | 58.17 | 22.43 |
November | 488.33 | 22.18 | 78.83 | 21.99 | 78.83 | 21.84 |
December | 497.00 | 21.25 | 253.83 | 20.94 | 253.83 | 20.78 |
Annual Sum or Average | 3880.17 | 22.28 | 1821.50 | 22.35 | 907.67 | 22.09 |
Minimum of Months | 21.67 | 21.25 | 32.83 | 20.94 | 0.00 | 20.78 |
Maximum of Months | 506.83 | 24.18 | 303.67 | 24.41 | 253.83 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.57 | 322.67 | 20.32 | 322.67 | 20.21 |
February | 454.00 | 20.69 | 302.67 | 20.46 | 302.67 | 20.36 |
March | 514.00 | 21.48 | 212.83 | 21.06 | 212.83 | 20.83 |
April | 457.67 | 21.53 | 157.00 | 21.07 | 154.83 | 20.79 |
May | 272.33 | 22.99 | 86.00 | 23.19 | 14.67 | 23.09 |
June | 30.33 | 24.23 | 324.17 | 24.38 | 8.83 | 24.41 |
July | 60.00 | 24.49 | 364.00 | 24.50 | 45.33 | 24.52 |
August | 60.50 | 23.64 | 292.67 | 24.22 | 7.00 | 24.23 |
September | 205.17 | 23.21 | 103.17 | 23.64 | 6.67 | 23.58 |
October | 477.83 | 21.93 | 136.00 | 21.54 | 136.00 | 21.30 |
November | 487.33 | 21.10 | 259.00 | 20.82 | 259.00 | 20.69 |
December | 497.00 | 20.27 | 403.00 | 20.13 | 403.00 | 20.07 |
Annual Sum or Average | 4018.17 | 21.43 | 2963.17 | 21.57 | 1873.50 | 21.28 |
Minimum of Months | 30.33 | 20.27 | 86.00 | 20.13 | 6.67 | 20.07 |
Maximum of Months | 514.00 | 24.49 | 403.00 | 24.50 | 403.00 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 21.23 | 234.83 | 20.84 | 234.83 | 20.64 |
February | 431.33 | 21.34 | 201.17 | 20.90 | 200.33 | 20.66 |
March | 426.83 | 21.73 | 168.33 | 21.35 | 153.50 | 21.06 |
April | 371.00 | 21.61 | 157.17 | 21.27 | 125.50 | 20.93 |
May | 177.83 | 23.15 | 171.83 | 23.74 | 10.67 | 23.68 |
June | 41.67 | 26.24 | 406.83 | 24.64 | 36.00 | 24.79 |
July | 91.33 | 25.78 | 435.33 | 24.82 | 87.67 | 24.97 |
August | 52.00 | 25.23 | 392.33 | 24.51 | 28.50 | 24.64 |
September | 131.50 | 23.70 | 202.83 | 24.25 | 18.17 | 24.32 |
October | 374.50 | 22.01 | 150.17 | 21.90 | 109.67 | 21.61 |
November | 465.33 | 21.61 | 168.50 | 21.27 | 167.50 | 21.06 |
December | 497.00 | 20.79 | 305.17 | 20.43 | 305.17 | 20.27 |
Annual Sum or Average | 3560.83 | 21.83 | 2994.50 | 22.16 | 1477.50 | 21.89 |
Minimum of Months | 41.67 | 20.79 | 150.17 | 20.43 | 10.67 | 20.27 |
Maximum of Months | 500.50 | 26.24 | 435.33 | 24.82 | 305.17 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.33 | 21.48 | 231.17 | 21.51 | 160.50 | 21.24 |
February | 320.50 | 21.30 | 222.17 | 21.29 | 160.33 | 21.00 |
March | 375.00 | 21.64 | 199.00 | 21.47 | 154.67 | 21.20 |
April | 370.00 | 21.43 | 161.83 | 21.13 | 131.50 | 20.81 |
May | 235.83 | 22.91 | 131.83 | 23.36 | 14.17 | 23.26 |
June | 62.33 | 24.38 | 324.83 | 24.40 | 18.67 | 24.49 |
July | 90.67 | 24.79 | 369.50 | 24.58 | 61.17 | 24.68 |
August | 70.67 | 24.50 | 357.67 | 24.42 | 24.83 | 24.53 |
September | 149.83 | 23.84 | 229.17 | 24.28 | 29.50 | 24.43 |
October | 329.67 | 22.15 | 228.33 | 22.37 | 125.67 | 22.17 |
November | 329.50 | 21.81 | 215.67 | 22.00 | 129.00 | 21.75 |
December | 400.00 | 21.20 | 264.67 | 21.01 | 227.83 | 20.77 |
Annual Sum or Average | 3089.33 | 21.99 | 2935.83 | 22.44 | 1237.83 | 22.17 |
Minimum of Months | 62.33 | 21.20 | 131.83 | 21.01 | 14.17 | 20.77 |
Maximum of Months | 400.00 | 24.79 | 369.50 | 24.58 | 227.83 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.50 | 20.99 | 257.83 | 20.64 | 257.33 | 20.47 |
February | 410.17 | 21.02 | 246.00 | 20.74 | 236.50 | 20.56 |
March | 435.00 | 21.50 | 202.67 | 21.22 | 178.33 | 20.97 |
April | 385.50 | 21.40 | 168.00 | 21.11 | 136.83 | 20.81 |
May | 226.67 | 22.99 | 154.33 | 23.52 | 18.17 | 23.48 |
June | 64.50 | 24.90 | 360.50 | 24.52 | 28.50 | 24.65 |
July | 93.17 | 24.94 | 390.83 | 24.61 | 67.50 | 24.71 |
August | 71.17 | 24.39 | 361.00 | 24.41 | 25.50 | 24.50 |
September | 175.00 | 23.59 | 181.33 | 24.10 | 25.17 | 24.22 |
October | 400.00 | 21.91 | 179.17 | 21.83 | 132.00 | 21.59 |
November | 434.17 | 21.36 | 204.17 | 21.08 | 196.00 | 20.90 |
December | 482.67 | 20.66 | 339.83 | 20.36 | 339.33 | 20.24 |
Annual Sum or Average | 3646.50 | 21.68 | 3045.67 | 21.98 | 1641.17 | 21.71 |
Minimum of Months | 64.50 | 20.66 | 154.33 | 20.36 | 18.17 | 20.24 |
Maximum of Months | 482.67 | 24.94 | 390.83 | 24.61 | 339.33 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.70 | 314.50 | 20.53 | 314.50 | 20.46 |
February | 454.00 | 20.69 | 316.50 | 20.55 | 316.50 | 20.50 |
March | 514.00 | 21.28 | 240.00 | 21.00 | 240.00 | 20.85 |
April | 482.83 | 21.56 | 141.33 | 21.28 | 141.33 | 21.10 |
May | 379.33 | 23.14 | 29.00 | 23.11 | 12.67 | 23.04 |
June | 36.83 | 23.94 | 245.00 | 24.25 | 5.50 | 24.25 |
July | 50.33 | 24.02 | 304.67 | 24.34 | 37.83 | 24.31 |
August | 42.17 | 23.87 | 246.83 | 24.23 | 4.00 | 24.23 |
September | 185.33 | 23.62 | 98.00 | 24.00 | 0.00 | 24.00 |
October | 489.67 | 22.59 | 60.83 | 22.37 | 60.83 | 22.19 |
November | 489.00 | 21.56 | 141.50 | 21.37 | 141.50 | 21.24 |
December | 497.00 | 20.62 | 353.17 | 20.47 | 353.17 | 20.41 |
Annual Sum or Average | 4122.50 | 21.65 | 2491.33 | 21.71 | 1627.83 | 21.47 |
Minimum of Months | 36.83 | 20.62 | 29.00 | 20.47 | 0.00 | 20.41 |
Maximum of Months | 514.00 | 24.02 | 353.17 | 24.34 | 353.17 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.54 | 183.50 | 21.23 | 183.50 | 21.06 |
February | 437.83 | 21.57 | 186.17 | 21.17 | 186.17 | 20.95 |
March | 466.67 | 22.08 | 129.83 | 21.71 | 125.33 | 21.45 |
April | 408.83 | 22.17 | 98.50 | 21.90 | 86.67 | 21.66 |
May | 194.83 | 23.34 | 119.83 | 23.77 | 5.17 | 23.72 |
June | 13.83 | 26.14 | 410.00 | 24.54 | 13.67 | 24.59 |
July | 63.83 | 25.37 | 441.50 | 24.71 | 63.83 | 24.79 |
August | 25.17 | 26.18 | 418.50 | 24.57 | 21.83 | 24.66 |
September | 65.67 | 24.05 | 238.50 | 24.59 | 7.33 | 24.65 |
October | 328.67 | 22.70 | 96.00 | 22.80 | 49.83 | 22.59 |
November | 451.67 | 22.27 | 77.33 | 22.06 | 74.17 | 21.88 |
December | 497.00 | 21.32 | 252.67 | 20.98 | 252.67 | 20.81 |
Annual Sum or Average | 3456.00 | 22.14 | 2652.33 | 22.54 | 1070.17 | 22.29 |
Minimum of Months | 13.83 | 21.32 | 77.33 | 20.98 | 5.17 | 20.81 |
Maximum of Months | 502.00 | 26.18 | 441.50 | 24.71 | 252.67 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.83 | 21.73 | 146.00 | 21.74 | 93.83 | 21.45 |
February | 341.33 | 21.31 | 170.17 | 21.18 | 130.33 | 20.86 |
March | 408.50 | 21.58 | 147.17 | 21.29 | 134.33 | 21.02 |
April | 433.17 | 21.63 | 108.33 | 21.34 | 104.00 | 21.12 |
May | 342.83 | 22.75 | 48.00 | 22.87 | 13.67 | 22.78 |
June | 67.33 | 23.27 | 252.33 | 24.16 | 7.50 | 24.16 |
July | 79.00 | 23.71 | 328.50 | 24.33 | 44.17 | 24.31 |
August | 49.50 | 23.71 | 368.83 | 24.38 | 15.83 | 24.43 |
September | 88.00 | 23.76 | 264.33 | 24.51 | 20.33 | 24.64 |
October | 270.83 | 22.34 | 185.17 | 22.84 | 72.50 | 22.69 |
November | 299.00 | 21.94 | 157.00 | 22.39 | 58.33 | 22.15 |
December | 395.67 | 21.33 | 183.17 | 21.13 | 155.17 | 20.84 |
Annual Sum or Average | 3142.00 | 21.95 | 2359.00 | 22.47 | 850.00 | 22.22 |
Minimum of Months | 49.50 | 21.31 | 48.00 | 21.13 | 7.50 | 20.84 |
Maximum of Months | 433.17 | 23.76 | 368.83 | 24.51 | 155.17 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.50 | 21.42 | 198.50 | 21.12 | 198.50 | 20.95 |
February | 433.83 | 21.40 | 200.00 | 21.06 | 199.33 | 20.88 |
March | 467.00 | 21.82 | 153.67 | 21.47 | 149.00 | 21.23 |
April | 432.83 | 22.01 | 102.33 | 21.73 | 94.50 | 21.50 |
May | 255.17 | 23.26 | 96.50 | 23.61 | 5.00 | 23.57 |
June | 34.17 | 25.26 | 363.00 | 24.54 | 20.00 | 24.62 |
July | 51.00 | 24.67 | 394.17 | 24.54 | 49.17 | 24.55 |
August | 23.00 | 25.20 | 394.17 | 24.50 | 15.00 | 24.55 |
September | 96.83 | 24.14 | 208.83 | 24.57 | 14.17 | 24.69 |
October | 361.83 | 22.80 | 101.17 | 22.79 | 57.00 | 22.60 |
November | 439.00 | 22.18 | 78.17 | 21.99 | 74.33 | 21.83 |
December | 492.50 | 21.22 | 262.83 | 20.90 | 262.83 | 20.74 |
Annual Sum or Average | 3573.67 | 22.06 | 2553.33 | 22.39 | 1138.83 | 22.14 |
Minimum of Months | 23.00 | 21.22 | 78.17 | 20.90 | 5.00 | 20.74 |
Maximum of Months | 492.50 | 25.26 | 394.17 | 24.57 | 262.83 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.03 | 239.00 | 20.76 | 239.00 | 20.62 |
February | 454.00 | 21.03 | 236.83 | 20.76 | 236.83 | 20.62 |
March | 511.17 | 21.80 | 142.33 | 21.41 | 142.33 | 21.17 |
April | 463.67 | 22.03 | 98.33 | 21.70 | 96.83 | 21.46 |
May | 253.50 | 23.34 | 73.33 | 23.55 | 5.17 | 23.50 |
June | 11.50 | 24.19 | 343.83 | 24.41 | 4.83 | 24.41 |
July | 38.67 | 24.45 | 373.33 | 24.51 | 38.33 | 24.50 |
August | 27.33 | 23.89 | 302.00 | 24.33 | 4.67 | 24.33 |
September | 177.33 | 23.52 | 106.33 | 24.00 | 0.00 | 24.00 |
October | 473.50 | 22.46 | 69.83 | 22.19 | 69.83 | 21.98 |
November | 486.50 | 21.58 | 153.50 | 21.35 | 153.50 | 21.20 |
December | 497.00 | 20.64 | 323.83 | 20.42 | 323.83 | 20.33 |
Annual Sum or Average | 3896.17 | 21.77 | 2462.50 | 21.97 | 1315.17 | 21.69 |
Minimum of Months | 11.50 | 20.64 | 69.83 | 20.42 | 0.00 | 20.33 |
Maximum of Months | 511.17 | 24.45 | 373.33 | 24.51 | 323.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 415.83 | 21.53 | 156.00 | 21.20 | 154.83 | 21.01 |
February | 356.33 | 21.48 | 155.50 | 21.09 | 150.50 | 20.84 |
March | 360.17 | 21.92 | 112.50 | 21.62 | 97.50 | 21.33 |
April | 319.33 | 21.99 | 101.33 | 21.80 | 73.17 | 21.53 |
May | 138.67 | 23.42 | 149.50 | 24.06 | 5.00 | 24.06 |
June | 30.00 | 26.50 | 343.83 | 24.76 | 29.17 | 24.89 |
July | 79.50 | 25.87 | 369.33 | 24.96 | 79.50 | 25.09 |
August | 36.83 | 25.79 | 327.67 | 24.68 | 26.83 | 24.80 |
September | 102.67 | 23.98 | 175.83 | 24.54 | 12.00 | 24.65 |
October | 319.50 | 22.44 | 106.33 | 22.48 | 64.50 | 22.26 |
November | 382.67 | 21.94 | 101.17 | 21.69 | 96.17 | 21.50 |
December | 420.17 | 21.06 | 235.83 | 20.70 | 235.83 | 20.52 |
Annual Sum or Average | 2961.67 | 22.10 | 2334.83 | 22.50 | 1025.00 | 22.27 |
Minimum of Months | 30.00 | 21.06 | 101.17 | 20.70 | 5.00 | 20.52 |
Maximum of Months | 420.17 | 26.50 | 369.33 | 24.96 | 235.83 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 333.67 | 21.96 | 183.17 | 22.16 | 98.17 | 21.93 |
February | 304.33 | 21.68 | 198.33 | 21.75 | 126.50 | 21.45 |
March | 360.17 | 21.96 | 144.83 | 21.86 | 99.67 | 21.59 |
April | 369.83 | 22.02 | 106.17 | 21.82 | 79.83 | 21.55 |
May | 207.50 | 23.26 | 126.83 | 23.72 | 4.50 | 23.67 |
June | 28.67 | 24.83 | 341.50 | 24.46 | 13.00 | 24.51 |
July | 60.50 | 25.01 | 379.67 | 24.61 | 52.67 | 24.67 |
August | 38.50 | 25.25 | 379.50 | 24.50 | 21.50 | 24.59 |
September | 122.00 | 24.24 | 241.50 | 24.53 | 24.17 | 24.70 |
October | 306.50 | 22.67 | 198.67 | 22.96 | 86.33 | 22.84 |
November | 312.00 | 22.35 | 184.33 | 22.71 | 82.33 | 22.55 |
December | 388.33 | 21.68 | 228.50 | 21.55 | 183.83 | 21.31 |
Annual Sum or Average | 2832.00 | 22.35 | 2713.00 | 22.90 | 872.50 | 22.69 |
Minimum of Months | 28.67 | 21.68 | 106.17 | 21.55 | 4.50 | 21.31 |
Maximum of Months | 388.33 | 25.25 | 379.67 | 24.61 | 183.83 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.33 | 21.46 | 180.00 | 21.14 | 176.17 | 20.95 |
February | 401.83 | 21.36 | 193.50 | 21.07 | 181.17 | 20.86 |
March | 432.33 | 21.88 | 140.00 | 21.62 | 117.00 | 21.36 |
April | 386.50 | 21.99 | 111.50 | 21.80 | 82.17 | 21.54 |
May | 201.17 | 23.36 | 148.83 | 23.85 | 9.00 | 23.85 |
June | 40.00 | 25.62 | 376.17 | 24.58 | 26.50 | 24.70 |
July | 64.00 | 25.28 | 404.67 | 24.65 | 60.50 | 24.73 |
August | 37.17 | 25.09 | 377.67 | 24.50 | 21.83 | 24.58 |
September | 143.83 | 23.96 | 190.17 | 24.40 | 19.00 | 24.55 |
October | 386.33 | 22.48 | 123.67 | 22.48 | 73.83 | 22.28 |
November | 425.00 | 21.86 | 129.83 | 21.67 | 117.00 | 21.48 |
December | 478.33 | 21.03 | 276.00 | 20.71 | 273.83 | 20.55 |
Annual Sum or Average | 3457.83 | 22.04 | 2652.00 | 22.40 | 1158.00 | 22.17 |
Minimum of Months | 37.17 | 21.03 | 111.50 | 20.71 | 9.00 | 20.55 |
Maximum of Months | 478.33 | 25.62 | 404.67 | 24.65 | 273.83 | 24.73 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.51864 | 20.19219 | 0.02517 | 5.70052 |
February | 454.00000 | 23.45307 | 18.49860 | -0.0026 | 5.93351 |
March | 514.00000 | 23.74751 | 18.35378 | 0.08572 | 5.55315 |
April | 485.00000 | 23.91408 | 22.39490 | 0.15137 | 5.81648 |
May | 508.00000 | 24.31372 | 24.98166 | -0.5720 | 12.39118 |
June | 496.00000 | 24.31226 | 32.96519 | -0.4561 | 9.70915 |
July | 497.00000 | 24.36725 | 34.87013 | -0.4243 | 9.12142 |
August | 514.00000 | 24.34006 | 33.45468 | -0.4410 | 9.46363 |
September | 485.00000 | 24.36308 | 24.85529 | -0.5058 | 10.87579 |
October | 502.00000 | 24.20053 | 19.77618 | 0.23948 | 6.53257 |
November | 489.00000 | 23.95801 | 20.89135 | 0.15753 | 5.84265 |
December | 497.00000 | 23.29505 | 15.15219 | -0.0645 | 6.02983 |
Annual Sum or Average | 5943.00000 | 23.98587 | 23.91499 | -0.1524 | 7.76491 |
Minimum of Months | 454.00000 | 23.29505 | 15.15219 | -0.5720 | 5.55315 |
Maximum of Months | 514.00000 | 24.36725 | 34.87013 | 0.23948 | 12.39118 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.51479 | 21.86518 | -0.2002 | 7.24035 |
February | 454.00000 | 22.50012 | 20.01044 | -0.2190 | 7.75161 |
March | 514.00000 | 22.98106 | 19.58424 | -0.0911 | 6.60467 |
April | 485.00000 | 23.14811 | 23.73247 | -0.0239 | 6.24208 |
May | 508.00000 | 24.07309 | 25.91921 | -0.6577 | 14.77040 |
June | 496.00000 | 24.25884 | 33.60209 | -0.4811 | 10.14479 |
July | 497.00000 | 24.31405 | 35.47678 | -0.4489 | 9.53500 |
August | 514.00000 | 24.27863 | 34.08937 | -0.4730 | 10.00549 |
September | 485.00000 | 24.24478 | 25.40997 | -0.5631 | 12.20595 |
October | 502.00000 | 23.62660 | 20.92410 | 0.09222 | 6.23735 |
November | 489.00000 | 23.04490 | 22.67330 | -0.0581 | 6.05254 |
December | 497.00000 | 22.12512 | 16.39191 | -0.3349 | 9.12954 |
Annual Sum or Average | 5943.00000 | 23.43359 | 25.01882 | -0.2892 | 8.84084 |
Minimum of Months | 454.00000 | 22.12512 | 16.39191 | -0.6577 | 6.05254 |
Maximum of Months | 514.00000 | 24.31405 | 35.47678 | 0.09222 | 14.77040 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.65620 | 22.54694 | -0.4195 | 10.95353 |
February | 454.00000 | 21.76752 | 20.43429 | -0.4090 | 11.11567 |
March | 514.00000 | 22.38230 | 20.01709 | -0.2423 | 8.94436 |
April | 485.00000 | 22.57519 | 24.38782 | -0.1650 | 8.05489 |
May | 508.00000 | 23.85340 | 26.02285 | -0.7332 | 17.50204 |
June | 496.00000 | 24.23857 | 33.35010 | -0.4789 | 10.13905 |
July | 497.00000 | 24.31143 | 35.23848 | -0.4425 | 9.49488 |
August | 514.00000 | 24.23925 | 33.99054 | -0.4815 | 10.17859 |
September | 485.00000 | 24.09430 | 25.33598 | -0.6212 | 14.03328 |
October | 502.00000 | 22.98259 | 21.70643 | -0.0750 | 7.11458 |
November | 489.00000 | 22.18450 | 23.93104 | -0.2742 | 8.26860 |
December | 497.00000 | 21.24973 | 16.98305 | -0.5615 | 14.05844 |
Annual Sum or Average | 5943.00000 | 22.97178 | 25.37203 | -0.4089 | 10.82417 |
Minimum of Months | 454.00000 | 21.24973 | 16.98305 | -0.7332 | 7.11458 |
Maximum of Months | 514.00000 | 24.31143 | 35.23848 | -0.0750 | 17.50204 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56686 | 24.59999 | -0.7034 | 18.20603 |
February | 454.00000 | 20.68799 | 22.13274 | -0.6907 | 17.84024 |
March | 514.00000 | 21.48220 | 21.50377 | -0.4659 | 13.34678 |
April | 485.00000 | 21.67157 | 25.56503 | -0.3712 | 12.31361 |
May | 508.00000 | 23.54917 | 27.13765 | -0.8092 | 21.30052 |
June | 496.00000 | 24.27708 | 33.35372 | -0.4135 | 9.42528 |
July | 497.00000 | 24.38455 | 35.42149 | -0.3672 | 8.95500 |
August | 514.00000 | 24.17389 | 34.88012 | -0.4671 | 10.41513 |
September | 485.00000 | 23.84140 | 26.32489 | -0.6890 | 17.59462 |
October | 502.00000 | 22.03303 | 23.88087 | -0.3040 | 10.28621 |
November | 489.00000 | 21.10500 | 25.86189 | -0.5500 | 13.59068 |
December | 497.00000 | 20.27140 | 17.96573 | -0.8346 | 22.37832 |
Annual Sum or Average | 5943.00000 | 22.35189 | 26.59311 | -0.5545 | 14.61144 |
Minimum of Months | 454.00000 | 20.27140 | 17.96573 | -0.8346 | 8.95500 |
Maximum of Months | 514.00000 | 24.38455 | 35.42149 | -0.3040 | 22.37832 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.23925 | 24.51691 | -0.5206 | 14.24742 |
February | 454.00000 | 21.48630 | 21.79538 | -0.4699 | 14.75093 |
March | 514.00000 | 22.16319 | 20.59599 | -0.2650 | 11.84073 |
April | 485.00000 | 22.20503 | 24.55623 | -0.2050 | 11.68404 |
May | 508.00000 | 23.89087 | 26.11467 | -0.6237 | 15.99167 |
June | 496.00000 | 24.40466 | 32.74152 | -0.2589 | 7.97070 |
July | 497.00000 | 24.55228 | 34.89392 | -0.2098 | 8.11886 |
August | 514.00000 | 24.31962 | 34.03640 | -0.3000 | 8.65097 |
September | 485.00000 | 24.14665 | 25.41437 | -0.4950 | 13.23674 |
October | 502.00000 | 22.63615 | 22.74591 | -0.1329 | 10.42515 |
November | 489.00000 | 21.73704 | 25.41933 | -0.3781 | 11.30813 |
December | 497.00000 | 20.78720 | 18.40398 | -0.6883 | 18.90472 |
Annual Sum or Average | 5943.00000 | 22.80959 | 25.97392 | -0.3782 | 12.23952 |
Minimum of Months | 454.00000 | 20.78720 | 18.40398 | -0.6883 | 7.97070 |
Maximum of Months | 514.00000 | 24.55228 | 34.89392 | -0.1329 | 18.90472 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.31229 | 20.96145 | -0.2049 | 12.23590 |
February | 454.00000 | 22.18691 | 19.05260 | -0.2482 | 13.87910 |
March | 514.00000 | 22.33080 | 19.28728 | -0.2008 | 12.14375 |
April | 485.00000 | 22.06716 | 24.13166 | -0.2433 | 12.07494 |
May | 508.00000 | 23.64976 | 26.51668 | -0.7415 | 19.88346 |
June | 496.00000 | 24.25063 | 33.28850 | -0.3974 | 9.69912 |
July | 497.00000 | 24.39316 | 35.25797 | -0.3317 | 9.09082 |
August | 514.00000 | 24.25754 | 34.27353 | -0.3601 | 9.39191 |
September | 485.00000 | 24.12077 | 25.07878 | -0.4795 | 13.83922 |
October | 502.00000 | 22.87529 | 21.20059 | -0.0229 | 11.68164 |
November | 489.00000 | 22.65974 | 22.16801 | -0.0985 | 11.26816 |
December | 497.00000 | 21.81849 | 15.68329 | -0.3848 | 15.42186 |
Annual Sum or Average | 5943.00000 | 23.08510 | 24.79422 | -0.3103 | 12.54415 |
Minimum of Months | 454.00000 | 21.81849 | 15.68329 | -0.7415 | 9.09082 |
Maximum of Months | 514.00000 | 24.39316 | 35.25797 | -0.0229 | 19.88346 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.19254 | 24.02127 | -0.5316 | 15.43385 |
February | 454.00000 | 21.33356 | 21.50195 | -0.5091 | 15.72362 |
March | 514.00000 | 21.91525 | 21.06359 | -0.3268 | 12.76610 |
April | 485.00000 | 21.95541 | 25.24083 | -0.2713 | 12.37251 |
May | 508.00000 | 23.70432 | 26.90958 | -0.7004 | 19.27293 |
June | 496.00000 | 24.31258 | 33.31913 | -0.3200 | 9.26586 |
July | 497.00000 | 24.41665 | 35.40366 | -0.2975 | 8.83858 |
August | 514.00000 | 24.25959 | 34.69389 | -0.3605 | 9.50574 |
September | 485.00000 | 24.00866 | 25.99843 | -0.5622 | 15.64801 |
October | 502.00000 | 22.40757 | 23.26924 | -0.1781 | 10.94178 |
November | 489.00000 | 21.67932 | 25.20408 | -0.3900 | 12.10201 |
December | 497.00000 | 20.76378 | 18.01240 | -0.6966 | 19.75063 |
Annual Sum or Average | 5943.00000 | 22.67471 | 26.26300 | -0.4281 | 13.44944 |
Minimum of Months | 454.00000 | 20.76378 | 18.01240 | -0.7004 | 8.83858 |
Maximum of Months | 514.00000 | 24.41665 | 35.40366 | -0.1781 | 19.75063 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.70151 | 24.74419 | -0.6654 | 15.75202 |
February | 454.00000 | 20.69296 | 22.33981 | -0.6914 | 16.57829 |
March | 514.00000 | 21.28310 | 22.17770 | -0.5203 | 12.58425 |
April | 485.00000 | 21.57165 | 26.71291 | -0.4023 | 10.27784 |
May | 508.00000 | 23.39151 | 28.48422 | -0.9052 | 24.02046 |
June | 496.00000 | 24.18604 | 33.88211 | -0.4954 | 10.42525 |
July | 497.00000 | 24.27986 | 35.76844 | -0.4491 | 9.64087 |
August | 514.00000 | 24.17065 | 34.94684 | -0.4997 | 10.55047 |
September | 485.00000 | 24.03636 | 26.39773 | -0.6276 | 14.49247 |
October | 502.00000 | 22.62712 | 23.75190 | -0.1447 | 7.30440 |
November | 489.00000 | 21.56267 | 25.61435 | -0.4135 | 9.88454 |
December | 497.00000 | 20.62171 | 18.14220 | -0.7202 | 17.59647 |
Annual Sum or Average | 5943.00000 | 22.44121 | 26.95650 | -0.5440 | 13.25080 |
Minimum of Months | 454.00000 | 20.62171 | 18.14220 | -0.9052 | 7.30440 |
Maximum of Months | 514.00000 | 24.27986 | 35.76844 | -0.1447 | 24.02046 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.53590 | 24.69657 | -0.4393 | 11.19484 |
February | 454.00000 | 21.66494 | 21.99543 | -0.4261 | 12.56096 |
March | 514.00000 | 22.28671 | 21.07669 | -0.2436 | 9.91564 |
April | 485.00000 | 22.49408 | 25.17976 | -0.1493 | 8.74096 |
May | 508.00000 | 23.93521 | 26.80178 | -0.6515 | 15.84654 |
June | 496.00000 | 24.41761 | 32.84718 | -0.2984 | 7.82762 |
July | 497.00000 | 24.55986 | 34.87093 | -0.2493 | 7.72721 |
August | 514.00000 | 24.39898 | 33.73644 | -0.2951 | 7.93861 |
September | 485.00000 | 24.36386 | 25.24812 | -0.4140 | 10.26823 |
October | 502.00000 | 23.31522 | 22.31983 | 0.05073 | 8.04240 |
November | 489.00000 | 22.42030 | 24.81986 | -0.1903 | 8.04641 |
December | 497.00000 | 21.32041 | 18.52124 | -0.5318 | 13.63403 |
Annual Sum or Average | 5943.00000 | 23.07083 | 26.04744 | -0.3195 | 10.13631 |
Minimum of Months | 454.00000 | 21.32041 | 18.52124 | -0.6515 | 7.72721 |
Maximum of Months | 514.00000 | 24.55986 | 34.87093 | 0.05073 | 15.84654 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.48280 | 19.71384 | -0.1206 | 10.03641 |
February | 454.00000 | 22.09500 | 17.99099 | -0.2341 | 12.46287 |
March | 514.00000 | 22.14846 | 18.54046 | -0.2298 | 10.75501 |
April | 485.00000 | 21.90763 | 23.89529 | -0.2748 | 9.64752 |
May | 508.00000 | 23.25520 | 27.11901 | -0.8970 | 24.64242 |
June | 496.00000 | 24.14212 | 33.20656 | -0.4855 | 10.88592 |
July | 497.00000 | 24.29646 | 35.30728 | -0.4098 | 9.64994 |
August | 514.00000 | 24.27164 | 33.63130 | -0.3796 | 9.29649 |
September | 485.00000 | 24.29665 | 24.54422 | -0.4052 | 11.19454 |
October | 502.00000 | 23.30033 | 20.04941 | 0.12090 | 10.47459 |
November | 489.00000 | 22.96014 | 20.63811 | 0.02998 | 9.85136 |
December | 497.00000 | 21.98203 | 14.21865 | -0.2837 | 12.73862 |
Annual Sum or Average | 5943.00000 | 23.10270 | 24.12785 | -0.2988 | 11.81756 |
Minimum of Months | 454.00000 | 21.90763 | 14.21865 | -0.8970 | 9.29649 |
Maximum of Months | 514.00000 | 24.29665 | 35.30728 | 0.12090 | 24.64242 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.49820 | 24.35202 | -0.4476 | 11.76687 |
February | 454.00000 | 21.52656 | 21.86654 | -0.4602 | 12.88520 |
March | 514.00000 | 22.04427 | 21.50791 | -0.3065 | 10.53779 |
April | 485.00000 | 22.24255 | 25.92515 | -0.2185 | 9.06072 |
May | 508.00000 | 23.79453 | 27.57321 | -0.7196 | 18.28189 |
June | 496.00000 | 24.35677 | 33.36862 | -0.3504 | 8.69530 |
July | 497.00000 | 24.42889 | 35.42603 | -0.3383 | 8.43201 |
August | 514.00000 | 24.36258 | 34.33701 | -0.3517 | 8.57156 |
September | 485.00000 | 24.32056 | 25.61848 | -0.4558 | 11.31267 |
October | 502.00000 | 23.23635 | 22.60148 | 0.03466 | 8.00408 |
November | 489.00000 | 22.38921 | 24.68030 | -0.1962 | 8.14055 |
December | 497.00000 | 21.25194 | 18.25729 | -0.5475 | 14.31750 |
Annual Sum or Average | 5943.00000 | 22.96589 | 26.33490 | -0.3630 | 10.83047 |
Minimum of Months | 454.00000 | 21.25194 | 18.25729 | -0.7196 | 8.00408 |
Maximum of Months | 514.00000 | 24.42889 | 35.42603 | 0.03466 | 18.28189 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.03181 | 24.30574 | -0.5614 | 13.68082 |
February | 454.00000 | 21.03139 | 21.86506 | -0.5776 | 14.48020 |
March | 514.00000 | 21.80748 | 21.23906 | -0.3665 | 10.78201 |
April | 485.00000 | 22.11424 | 25.11114 | -0.2553 | 9.18214 |
May | 508.00000 | 23.77606 | 26.89383 | -0.7312 | 17.90475 |
June | 496.00000 | 24.31666 | 33.45846 | -0.4094 | 9.07948 |
July | 497.00000 | 24.41504 | 35.46267 | -0.3656 | 8.58241 |
August | 514.00000 | 24.23628 | 34.78902 | -0.4520 | 9.78325 |
September | 485.00000 | 24.02776 | 26.23886 | -0.6223 | 14.75929 |
October | 502.00000 | 22.55561 | 23.36172 | -0.1612 | 7.91480 |
November | 489.00000 | 21.59236 | 25.23755 | -0.4051 | 10.12535 |
December | 497.00000 | 20.63598 | 17.92612 | -0.7080 | 17.82095 |
Annual Sum or Average | 5943.00000 | 22.64224 | 26.36578 | -0.4674 | 11.99225 |
Minimum of Months | 454.00000 | 20.63598 | 17.92612 | -0.7312 | 7.91480 |
Maximum of Months | 514.00000 | 24.41504 | 35.46267 | -0.1612 | 17.90475 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.60380 | 23.93175 | -0.4092 | 11.29526 |
February | 385.00000 | 21.69914 | 21.33707 | -0.3930 | 12.96753 |
March | 433.00000 | 22.32913 | 20.17078 | -0.2092 | 10.49943 |
April | 410.00000 | 22.47878 | 24.18552 | -0.1326 | 9.42794 |
May | 430.00000 | 24.06987 | 26.05036 | -0.5734 | 14.30305 |
June | 418.00000 | 24.51652 | 32.59385 | -0.2526 | 7.97471 |
July | 422.00000 | 24.68346 | 34.57553 | -0.1983 | 8.08260 |
August | 433.00000 | 24.44128 | 33.91542 | -0.2919 | 8.53037 |
September | 410.00000 | 24.31383 | 25.29790 | -0.4545 | 12.02513 |
October | 427.00000 | 22.98252 | 22.17054 | -0.0351 | 9.08533 |
November | 417.00000 | 22.13986 | 24.60903 | -0.2595 | 9.19944 |
December | 422.00000 | 21.08134 | 17.98583 | -0.5868 | 15.73082 |
Annual Sum or Average | 5034.00000 | 23.03776 | 25.60126 | -0.3159 | 10.74689 |
Minimum of Months | 385.00000 | 21.08134 | 17.98583 | -0.5868 | 7.97471 |
Maximum of Months | 433.00000 | 24.68346 | 34.57553 | -0.0351 | 15.73082 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.77048 | 20.55253 | -0.0665 | 10.15083 |
February | 454.00000 | 22.56085 | 18.61144 | -0.1320 | 11.87436 |
March | 514.00000 | 22.64443 | 18.90129 | -0.1058 | 10.31824 |
April | 485.00000 | 22.52038 | 23.56913 | -0.1266 | 9.08521 |
May | 508.00000 | 23.86893 | 26.27423 | -0.6663 | 16.57146 |
June | 496.00000 | 24.31073 | 33.34170 | -0.3881 | 9.13136 |
July | 497.00000 | 24.43943 | 35.25192 | -0.3263 | 8.55495 |
August | 514.00000 | 24.33136 | 34.14091 | -0.3429 | 8.70141 |
September | 485.00000 | 24.27923 | 25.05453 | -0.4218 | 11.61876 |
October | 502.00000 | 23.30111 | 20.78489 | 0.09957 | 10.25021 |
November | 489.00000 | 23.10839 | 21.46212 | 0.03598 | 9.88365 |
December | 497.00000 | 22.26679 | 15.30799 | -0.2458 | 12.42327 |
Annual Sum or Average | 5943.00000 | 23.37379 | 24.49187 | -0.2251 | 10.71118 |
Minimum of Months | 454.00000 | 22.26679 | 15.30799 | -0.6663 | 8.55495 |
Maximum of Months | 514.00000 | 24.43943 | 35.25192 | 0.09957 | 16.57146 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.66928 | 23.66347 | -0.3888 | 11.60985 |
February | 454.00000 | 21.69811 | 21.19203 | -0.3933 | 12.85667 |
March | 514.00000 | 22.25119 | 20.74579 | -0.2267 | 10.52710 |
April | 485.00000 | 22.42051 | 24.71978 | -0.1521 | 9.30785 |
May | 508.00000 | 23.93070 | 26.62092 | -0.6233 | 15.89553 |
June | 496.00000 | 24.37053 | 33.37177 | -0.3109 | 8.65678 |
July | 497.00000 | 24.46318 | 35.40973 | -0.2917 | 8.28447 |
August | 514.00000 | 24.33278 | 34.57122 | -0.3430 | 8.79858 |
September | 485.00000 | 24.18891 | 25.89963 | -0.4980 | 12.99814 |
October | 502.00000 | 22.90691 | 22.76517 | -0.0409 | 8.87497 |
November | 489.00000 | 22.17585 | 24.52678 | -0.2452 | 9.24880 |
December | 497.00000 | 21.15741 | 17.89684 | -0.5661 | 15.62677 |
Annual Sum or Average | 5943.00000 | 22.97492 | 25.99268 | -0.3398 | 11.04616 |
Minimum of Months | 454.00000 | 21.15741 | 17.89684 | -0.6233 | 8.28447 |
Maximum of Months | 514.00000 | 24.46318 | 35.40973 | -0.0409 | 15.89553 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.126428E+10 | 0.315033E+09 | 38.48 | 0.126312E+10 | 1162486.15 | 0.00 | 0.78 | 24-JAN-14:00 | 0.00 | 01-JAN-00:10 | 21645.17 | 24-JAN-14:00 | 21645.17 | 24-JAN-14:00 | 199.50 | 19-JAN-12:40 | 5020.79 | 24-JAN-14:00 | 0.00 |
February | 0.488840E+09 | 0.128197E+09 | 29.70 | 0.484675E+09 | 4165025.77 | 0.00 | 0.60 | 27-FEB-12:00 | 0.00 | 01-FEB-00:10 | 16053.41 | 27-FEB-12:00 | 16053.41 | 27-FEB-12:00 | 728.48 | 23-FEB-12:02 | 3902.91 | 27-FEB-12:00 | 0.00 |
March | 0.278180E+10 | 0.669604E+09 | 83.67 | 0.277942E+10 | 2387394.27 | 0.00 | 1.00 | 13-MAR-13:50 | 0.00 | 01-MAR-00:10 | 34152.51 | 14-MAR-13:00 | 34152.51 | 14-MAR-13:00 | 554.50 | 17-MAR-16:02 | 7463.83 | 14-MAR-13:00 | 0.00 |
April | 0.288474E+10 | 0.732789E+09 | 111.48 | 0.281892E+10 | 65811112.87 | 0.00 | 0.88 | 12-APR-13:50 | 0.00 | 01-APR-00:10 | 25377.38 | 12-APR-13:50 | 25377.38 | 12-APR-13:50 | 2564.46 | 28-APR-14:00 | 5711.49 | 12-APR-13:50 | 0.00 |
May | 0.117534E+11 | 0.282006E+10 | 222.47 | 0.114410E+11 | 0.312392E+09 | 0.00 | 1.00 | 10-MAY-12:30 | 0.00 | 01-MAY-00:10 | 42565.73 | 17-MAY-13:00 | 42565.73 | 17-MAY-13:00 | 2949.52 | 30-MAY-17:10 | 10559.81 | 17-MAY-13:00 | 0.00 |
June | 0.470936E+11 | 0.118994E+11 | 432.65 | 0.448618E+11 | 0.223177E+10 | 0.00 | 1.00 | 01-JUN-10:20 | 0.00 | 01-JUN-00:10 | 70210.27 | 26-JUN-15:20 | 70210.27 | 26-JUN-15:20 | 14903.69 | 22-JUN-13:20 | 23667.05 | 26-JUN-15:10 | 0.00 |
July | 0.478116E+11 | 0.118927E+11 | 435.27 | 0.441216E+11 | 0.368999E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 65724.59 | 17-JUL-12:20 | 65724.59 | 17-JUL-12:20 | 28279.10 | 31-JUL-15:40 | 20024.11 | 17-JUL-12:20 | 0.00 |
August | 0.476239E+11 | 0.117889E+11 | 430.66 | 0.452224E+11 | 0.240147E+10 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 65080.07 | 16-AUG-16:00 | 65080.07 | 16-AUG-16:00 | 21764.93 | 04-AUG-06:03 | 20453.28 | 16-AUG-16:00 | 0.00 |
September | 0.334002E+11 | 0.799765E+10 | 364.50 | 0.329082E+11 | 0.492001E+09 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 58734.23 | 12-SEP-16:00 | 58734.23 | 12-SEP-16:00 | 8834.63 | 01-SEP-14:00 | 15449.81 | 12-SEP-16:00 | 0.00 |
October | 0.946419E+10 | 0.223116E+10 | 176.55 | 0.939124E+10 | 72947195.87 | 0.00 | 1.00 | 10-OCT-10:00 | 0.00 | 01-OCT-00:10 | 49446.65 | 10-OCT-15:30 | 49446.65 | 10-OCT-15:30 | 1632.61 | 03-OCT-11:10 | 11256.58 | 11-OCT-14:00 | 0.00 |
November | 0.300463E+10 | 0.736106E+09 | 83.60 | 0.298090E+10 | 23729953.76 | 0.00 | 0.95 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 | 27936.81 | 07-NOV-15:00 | 27936.81 | 07-NOV-15:00 | 1198.10 | 14-NOV-13:05 | 6161.88 | 07-NOV-15:00 | 0.00 |
December | 0.840314E+09 | 0.216360E+09 | 41.36 | 0.838620E+09 | 1694319.91 | 0.00 | 0.66 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 17795.81 | 01-DEC-14:00 | 17795.81 | 01-DEC-14:00 | 227.95 | 03-DEC-15:28 | 4262.61 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.208411E+12 | 0.514279E+11 | 2450.38 | 0.199112E+12 | 0.929953E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.488840E+09 | 0.128197E+09 | 29.70 | 0.484675E+09 | 1162486.15 | 0.00 | 0.60 | 0.00 | 16053.41 | 16053.41 | 199.50 | 3902.91 | 0.00 | ||||||
Maximum of Months | 0.478116E+11 | 0.118994E+11 | 435.27 | 0.452224E+11 | 0.368999E+10 | 0.00 | 1.00 | 0.00 | 70210.27 | 70210.27 | 28279.10 | 23667.05 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167414E+10 | 0.417689E+09 | 50.73 | 0.166197E+10 | 12170839.70 | 0.00 | 0.79 | 24-JAN-15:05 | 0.00 | 01-JAN-00:10 | 21347.33 | 24-JAN-15:05 | 21347.33 | 24-JAN-15:05 | 1320.69 | 27-JAN-13:25 | 4935.38 | 24-JAN-15:05 | 0.00 |
February | 0.113149E+10 | 0.292803E+09 | 54.37 | 0.111026E+10 | 21235136.45 | 0.00 | 0.66 | 27-FEB-15:05 | 0.00 | 01-FEB-00:10 | 17312.24 | 27-FEB-15:05 | 17312.24 | 27-FEB-15:05 | 1001.50 | 23-FEB-12:00 | 4143.81 | 27-FEB-15:05 | 0.00 |
March | 0.319362E+10 | 0.763486E+09 | 86.92 | 0.319301E+10 | 604265.85 | 0.00 | 1.00 | 13-MAR-13:30 | 0.00 | 01-MAR-00:10 | 36128.77 | 13-MAR-15:50 | 36128.77 | 13-MAR-15:50 | 156.74 | 31-MAR-17:50 | 7854.55 | 13-MAR-15:50 | 0.00 |
April | 0.243721E+10 | 0.614996E+09 | 89.98 | 0.239957E+10 | 37636873.71 | 0.00 | 0.83 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 22708.36 | 20-APR-13:00 | 22708.36 | 20-APR-13:00 | 2583.28 | 28-APR-14:00 | 5190.33 | 20-APR-13:00 | 0.00 |
May | 0.125281E+11 | 0.298707E+10 | 235.19 | 0.121914E+11 | 0.336699E+09 | 0.00 | 1.00 | 04-MAY-14:05 | 0.00 | 01-MAY-00:10 | 45989.18 | 16-MAY-14:05 | 45989.18 | 16-MAY-14:05 | 2768.72 | 31-MAY-07:35 | 11050.17 | 16-MAY-14:05 | 0.00 |
June | 0.465937E+11 | 0.117589E+11 | 435.58 | 0.444553E+11 | 0.213843E+10 | 0.00 | 1.00 | 01-JUN-10:05 | 0.00 | 01-JUN-00:10 | 70693.80 | 26-JUN-15:00 | 70693.80 | 26-JUN-15:00 | 15111.27 | 22-JUN-13:20 | 23941.14 | 26-JUN-15:00 | 0.00 |
July | 0.473134E+11 | 0.117732E+11 | 441.17 | 0.437402E+11 | 0.357326E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 67514.41 | 17-JUL-12:02 | 67514.41 | 17-JUL-12:02 | 29643.15 | 31-JUL-15:40 | 20564.67 | 17-JUL-12:02 | 0.00 |
August | 0.450388E+11 | 0.111798E+11 | 431.29 | 0.427845E+11 | 0.225435E+10 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 65276.34 | 16-AUG-15:00 | 65276.34 | 16-AUG-15:00 | 18156.31 | 28-AUG-06:02 | 20018.55 | 16-AUG-14:05 | 0.00 |
September | 0.298831E+11 | 0.719160E+10 | 356.10 | 0.294152E+11 | 0.467906E+09 | 0.00 | 1.00 | 01-SEP-10:05 | 0.00 | 01-SEP-00:10 | 58428.88 | 11-SEP-14:05 | 58428.88 | 11-SEP-14:05 | 7825.12 | 01-SEP-14:00 | 15097.53 | 12-SEP-15:40 | 0.00 |
October | 0.712705E+10 | 0.169580E+10 | 143.26 | 0.708761E+10 | 39440468.91 | 0.00 | 1.00 | 10-OCT-10:05 | 0.00 | 01-OCT-00:10 | 48500.32 | 11-OCT-14:05 | 48500.32 | 11-OCT-14:05 | 2085.65 | 03-OCT-11:05 | 11349.65 | 11-OCT-14:05 | 0.00 |
November | 0.230651E+10 | 0.568858E+09 | 70.34 | 0.228035E+10 | 26156744.63 | 0.00 | 1.00 | 07-NOV-15:05 | 0.00 | 01-NOV-00:10 | 28665.02 | 07-NOV-15:05 | 28665.02 | 07-NOV-15:05 | 983.67 | 14-NOV-13:03 | 6241.17 | 07-NOV-15:05 | 0.00 |
December | 0.110494E+10 | 0.283925E+09 | 51.14 | 0.110175E+10 | 3191368.01 | 0.00 | 0.72 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 19010.73 | 01-DEC-14:00 | 19010.73 | 01-DEC-14:00 | 207.64 | 03-DEC-15:30 | 4483.72 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.200332E+12 | 0.495281E+11 | 2446.10 | 0.191421E+12 | 0.891107E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.110494E+10 | 0.283925E+09 | 50.73 | 0.110175E+10 | 604265.85 | 0.00 | 0.66 | 0.00 | 17312.24 | 17312.24 | 156.74 | 4143.81 | 0.00 | ||||||
Maximum of Months | 0.473134E+11 | 0.117732E+11 | 441.17 | 0.444553E+11 | 0.357326E+10 | 0.00 | 1.00 | 0.00 | 70693.80 | 70693.80 | 29643.15 | 23941.14 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.905837E+09 | 0.233028E+09 | 36.33 | 0.892459E+09 | 13378335.31 | 0.00 | 0.65 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 19677.38 | 20-JAN-14:00 | 19677.38 | 20-JAN-14:00 | 1050.49 | 27-JAN-13:50 | 4728.97 | 20-JAN-14:00 | 0.00 |
February | 0.883934E+09 | 0.235325E+09 | 54.78 | 0.860671E+09 | 23262887.94 | 0.00 | 0.47 | 18-FEB-13:25 | 0.00 | 01-FEB-00:10 | 13692.97 | 18-FEB-13:25 | 13692.97 | 18-FEB-13:25 | 911.25 | 23-FEB-13:15 | 3445.93 | 18-FEB-13:25 | 0.00 |
March | 0.337174E+10 | 0.817783E+09 | 90.43 | 0.336868E+10 | 3062067.96 | 0.00 | 1.00 | 13-MAR-13:50 | 0.00 | 01-MAR-00:10 | 37873.67 | 13-MAR-15:50 | 37873.67 | 13-MAR-15:50 | 422.82 | 30-MAR-16:13 | 8235.57 | 13-MAR-15:50 | 0.00 |
April | 0.251221E+10 | 0.636178E+09 | 85.73 | 0.246242E+10 | 49794147.92 | 0.00 | 0.80 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 25257.75 | 20-APR-13:00 | 25257.75 | 20-APR-13:00 | 2932.73 | 28-APR-14:00 | 5825.47 | 20-APR-13:00 | 0.00 |
May | 0.135320E+11 | 0.325201E+10 | 236.78 | 0.130707E+11 | 0.461341E+09 | 0.00 | 1.00 | 04-MAY-14:05 | 0.00 | 01-MAY-00:10 | 54296.96 | 31-MAY-15:20 | 54296.96 | 31-MAY-15:20 | 3313.60 | 30-MAY-17:10 | 13104.32 | 31-MAY-15:20 | 0.00 |
June | 0.512358E+11 | 0.130349E+11 | 436.74 | 0.488806E+11 | 0.235520E+10 | 0.00 | 1.00 | 01-JUN-10:30 | 0.00 | 01-JUN-00:10 | 82312.24 | 26-JUN-15:00 | 82312.24 | 26-JUN-15:00 | 16478.85 | 22-JUN-13:20 | 27876.18 | 26-JUN-15:00 | 0.00 |
July | 0.514263E+11 | 0.129156E+11 | 444.32 | 0.475918E+11 | 0.383443E+10 | 0.00 | 1.00 | 01-JUL-08:50 | 0.00 | 01-JUL-00:10 | 75056.46 | 17-JUL-14:00 | 75056.46 | 17-JUL-14:00 | 30873.32 | 31-JUL-15:40 | 22453.61 | 17-JUL-13:10 | 0.00 |
August | 0.490383E+11 | 0.122873E+11 | 431.83 | 0.466183E+11 | 0.242000E+10 | 0.00 | 1.00 | 02-AUG-09:50 | 0.00 | 01-AUG-00:10 | 77310.39 | 16-AUG-15:00 | 77310.39 | 16-AUG-15:00 | 16060.14 | 05-AUG-14:50 | 23550.32 | 16-AUG-15:00 | 0.00 |
September | 0.309429E+11 | 0.753054E+10 | 357.89 | 0.303048E+11 | 0.638062E+09 | 0.00 | 1.00 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 | 65357.81 | 12-SEP-15:40 | 65357.81 | 12-SEP-15:40 | 7572.57 | 01-SEP-14:00 | 16914.75 | 12-SEP-15:40 | 0.00 |
October | 0.617284E+10 | 0.149068E+10 | 125.34 | 0.613473E+10 | 38106153.09 | 0.00 | 1.00 | 10-OCT-12:05 | 0.00 | 01-OCT-00:10 | 52999.90 | 11-OCT-14:50 | 52999.90 | 11-OCT-14:50 | 1200.47 | 01-OCT-11:52 | 12245.46 | 11-OCT-14:30 | 0.00 |
November | 0.239795E+10 | 0.604299E+09 | 73.52 | 0.235893E+10 | 39026461.75 | 0.00 | 0.86 | 07-NOV-14:40 | 0.00 | 01-NOV-00:10 | 27967.96 | 07-NOV-14:40 | 27967.96 | 07-NOV-14:40 | 845.45 | 14-NOV-15:00 | 6326.74 | 07-NOV-14:40 | 0.00 |
December | 0.965266E+09 | 0.252333E+09 | 45.38 | 0.958753E+09 | 6513537.23 | 0.00 | 0.60 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 17889.84 | 01-DEC-14:00 | 17889.84 | 01-DEC-14:00 | 386.63 | 29-DEC-16:10 | 4357.99 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.213385E+12 | 0.532900E+11 | 2419.06 | 0.203503E+12 | 0.988218E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.883934E+09 | 0.233028E+09 | 36.33 | 0.860671E+09 | 3062067.96 | 0.00 | 0.47 | 0.00 | 13692.97 | 13692.97 | 386.63 | 3445.93 | 0.00 | ||||||
Maximum of Months | 0.514263E+11 | 0.130349E+11 | 444.32 | 0.488806E+11 | 0.383443E+10 | 0.00 | 1.00 | 0.00 | 82312.24 | 82312.24 | 30873.32 | 27876.18 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.46 | 0.00 | 384.46 | 81.82 | 1784.84 | 0.00 | 0.00 | 0.00 |
February | 483.22 | 0.00 | 483.22 | 99.85 | 1813.12 | 0.00 | 0.00 | 0.00 |
March | 657.51 | 0.00 | 657.51 | 311.29 | 1374.17 | 0.00 | 0.00 | 0.00 |
April | 825.73 | 4.58 | 821.15 | 469.00 | 1170.25 | 0.00 | 0.00 | 0.00 |
May | 1128.00 | 37.29 | 1090.72 | 1027.58 | 717.27 | 0.00 | 0.00 | 0.00 |
June | 1236.93 | 137.13 | 1099.80 | 1643.67 | 401.65 | 0.00 | 0.00 | 0.00 |
July | 1169.80 | 75.72 | 1094.08 | 1572.05 | 381.16 | 0.00 | 0.00 | 0.00 |
August | 931.07 | 22.03 | 909.05 | 1196.18 | 434.85 | 0.00 | 0.00 | 0.00 |
September | 782.10 | 0.18 | 781.92 | 887.05 | 669.23 | 0.00 | 0.00 | 0.00 |
October | 560.17 | 0.00 | 560.17 | 315.31 | 1364.95 | 0.00 | 0.00 | 0.00 |
November | 425.24 | 0.00 | 425.24 | 129.02 | 1621.06 | 0.00 | 0.00 | 0.00 |
December | 359.71 | 0.00 | 359.71 | 70.46 | 2003.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 746.69 | 23.13 | 723.56 | 653.35 | 1141.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 359.71 | 0.00 | 359.71 | 70.46 | 381.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1236.93 | 137.13 | 1099.80 | 1643.67 | 2003.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 802.58 | 491.85 | 310.74 | 727.06 | 1119.75 | 0.00 | 0.00 | 0.00 |
February | 1066.14 | 673.05 | 393.09 | 1012.45 | 1160.53 | 0.00 | 0.00 | 0.00 |
March | 1286.81 | 750.58 | 536.22 | 1313.57 | 884.98 | 0.00 | 0.00 | 0.00 |
April | 1319.69 | 642.84 | 676.85 | 1319.02 | 763.96 | 0.00 | 0.00 | 0.00 |
May | 1542.70 | 644.39 | 898.31 | 1750.48 | 485.49 | 0.00 | 0.00 | 0.00 |
June | 1882.25 | 988.13 | 894.12 | 2524.42 | 270.22 | 0.00 | 0.00 | 0.00 |
July | 1711.11 | 814.79 | 896.32 | 2314.06 | 256.40 | 0.00 | 0.00 | 0.00 |
August | 1725.89 | 950.56 | 775.33 | 2321.00 | 291.91 | 0.00 | 0.00 | 0.00 |
September | 1436.03 | 780.09 | 655.94 | 1832.14 | 431.12 | 0.00 | 0.00 | 0.00 |
October | 1039.97 | 569.84 | 470.13 | 1096.15 | 893.64 | 0.00 | 0.00 | 0.00 |
November | 809.48 | 457.04 | 352.44 | 769.86 | 1046.17 | 0.00 | 0.00 | 0.00 |
December | 700.80 | 403.71 | 297.09 | 607.85 | 1267.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1277.76 | 680.24 | 597.52 | 1467.80 | 737.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 700.80 | 403.71 | 297.09 | 607.85 | 256.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1882.25 | 988.13 | 898.31 | 2524.42 | 1267.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3684.63 | 3031.01 | 653.63 | 4238.77 | 1630.07 | 0.00 | 0.00 | 0.00 |
February | 3534.25 | 2817.72 | 716.52 | 4023.59 | 1698.47 | 0.00 | 0.00 | 0.00 |
March | 2605.72 | 1714.42 | 891.30 | 3005.54 | 1351.46 | 0.00 | 0.00 | 0.00 |
April | 1687.66 | 678.61 | 1009.04 | 1778.05 | 1207.08 | 0.00 | 0.00 | 0.00 |
May | 1546.55 | 283.47 | 1263.08 | 1768.48 | 786.32 | 0.00 | 0.00 | 0.00 |
June | 1425.87 | 260.61 | 1165.26 | 2052.54 | 439.41 | 0.00 | 0.00 | 0.00 |
July | 1484.30 | 265.80 | 1218.50 | 2141.21 | 408.22 | 0.00 | 0.00 | 0.00 |
August | 1889.81 | 790.01 | 1099.80 | 2743.52 | 458.96 | 0.00 | 0.00 | 0.00 |
September | 2431.43 | 1356.72 | 1074.70 | 3312.00 | 687.86 | 0.00 | 0.00 | 0.00 |
October | 2907.28 | 2062.78 | 844.50 | 3532.58 | 1357.46 | 0.00 | 0.00 | 0.00 |
November | 3542.11 | 2823.58 | 718.53 | 4158.58 | 1556.20 | 0.00 | 0.00 | 0.00 |
December | 3387.18 | 2741.54 | 645.64 | 3817.96 | 1817.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2504.77 | 1561.76 | 943.01 | 3042.15 | 1113.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1425.87 | 260.61 | 645.64 | 1768.48 | 408.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3684.63 | 3031.01 | 1263.08 | 4238.77 | 1817.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 853.77 | 540.99 | 312.77 | 825.05 | 1146.50 | 0.00 | 0.00 | 0.00 |
February | 1029.52 | 638.00 | 391.52 | 981.90 | 1174.19 | 0.00 | 0.00 | 0.00 |
March | 1205.51 | 665.11 | 540.40 | 1221.05 | 901.65 | 0.00 | 0.00 | 0.00 |
April | 1135.04 | 480.56 | 654.48 | 1099.84 | 782.92 | 0.00 | 0.00 | 0.00 |
May | 1387.31 | 489.08 | 898.23 | 1576.08 | 514.07 | 0.00 | 0.00 | 0.00 |
June | 1696.77 | 816.38 | 880.39 | 2306.09 | 302.49 | 0.00 | 0.00 | 0.00 |
July | 1382.46 | 506.37 | 876.09 | 1883.52 | 277.59 | 0.00 | 0.00 | 0.00 |
August | 1442.90 | 712.81 | 730.09 | 1939.92 | 308.90 | 0.00 | 0.00 | 0.00 |
September | 1279.42 | 613.57 | 665.85 | 1644.96 | 460.13 | 0.00 | 0.00 | 0.00 |
October | 1076.33 | 615.20 | 461.13 | 1171.81 | 908.96 | 0.00 | 0.00 | 0.00 |
November | 883.19 | 536.20 | 346.98 | 874.63 | 1058.51 | 0.00 | 0.00 | 0.00 |
December | 713.37 | 421.41 | 291.96 | 632.32 | 1271.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1174.16 | 585.60 | 588.56 | 1347.95 | 756.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.37 | 421.41 | 291.96 | 632.32 | 277.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1696.77 | 816.38 | 898.23 | 2306.09 | 1271.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.15 | 0.00 | 128.15 | 27.99 | 607.75 | 0.00 | 0.00 | 0.00 |
February | 161.07 | 0.00 | 161.07 | 36.42 | 610.37 | 0.00 | 0.00 | 0.00 |
March | 219.16 | 0.00 | 219.16 | 112.33 | 459.44 | 0.00 | 0.00 | 0.00 |
April | 275.23 | 1.53 | 273.70 | 165.76 | 396.67 | 0.00 | 0.00 | 0.00 |
May | 375.98 | 12.43 | 363.55 | 355.29 | 234.53 | 0.00 | 0.00 | 0.00 |
June | 412.29 | 45.71 | 366.58 | 558.61 | 130.58 | 0.00 | 0.00 | 0.00 |
July | 389.92 | 25.24 | 364.68 | 534.29 | 123.18 | 0.00 | 0.00 | 0.00 |
August | 310.34 | 7.34 | 303.00 | 404.34 | 145.33 | 0.00 | 0.00 | 0.00 |
September | 260.69 | 0.06 | 260.63 | 296.40 | 233.26 | 0.00 | 0.00 | 0.00 |
October | 186.72 | 0.00 | 186.72 | 102.66 | 484.24 | 0.00 | 0.00 | 0.00 |
November | 141.74 | 0.00 | 141.74 | 40.70 | 570.15 | 0.00 | 0.00 | 0.00 |
December | 119.90 | 0.00 | 119.90 | 22.66 | 694.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.89 | 7.71 | 241.18 | 222.49 | 389.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.90 | 0.00 | 119.90 | 22.66 | 123.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.29 | 45.71 | 366.58 | 558.61 | 694.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.15 | 0.00 | 128.15 | 27.99 | 607.79 | 0.00 | 0.00 | 0.00 |
February | 161.07 | 0.00 | 161.07 | 36.43 | 610.41 | 0.00 | 0.00 | 0.00 |
March | 219.17 | 0.00 | 219.17 | 112.34 | 459.47 | 0.00 | 0.00 | 0.00 |
April | 275.24 | 1.53 | 273.72 | 165.76 | 396.70 | 0.00 | 0.00 | 0.00 |
May | 376.00 | 12.43 | 363.57 | 355.30 | 234.55 | 0.00 | 0.00 | 0.00 |
June | 412.31 | 45.71 | 366.60 | 558.64 | 130.59 | 0.00 | 0.00 | 0.00 |
July | 389.93 | 25.24 | 364.69 | 534.31 | 123.18 | 0.00 | 0.00 | 0.00 |
August | 310.36 | 7.34 | 303.01 | 404.36 | 145.33 | 0.00 | 0.00 | 0.00 |
September | 260.70 | 0.06 | 260.64 | 296.41 | 233.28 | 0.00 | 0.00 | 0.00 |
October | 186.72 | 0.00 | 186.72 | 102.66 | 484.27 | 0.00 | 0.00 | 0.00 |
November | 141.75 | 0.00 | 141.75 | 40.70 | 570.19 | 0.00 | 0.00 | 0.00 |
December | 119.90 | 0.00 | 119.90 | 22.66 | 694.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.90 | 7.71 | 241.19 | 222.50 | 389.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.90 | 0.00 | 119.90 | 22.66 | 123.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.31 | 45.71 | 366.60 | 558.64 | 694.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.15 | 0.00 | 128.15 | 27.99 | 607.79 | 0.00 | 0.00 | 0.00 |
February | 161.07 | 0.00 | 161.07 | 36.43 | 610.41 | 0.00 | 0.00 | 0.00 |
March | 219.17 | 0.00 | 219.17 | 112.34 | 459.47 | 0.00 | 0.00 | 0.00 |
April | 275.24 | 1.53 | 273.72 | 165.76 | 396.70 | 0.00 | 0.00 | 0.00 |
May | 376.00 | 12.43 | 363.57 | 355.30 | 234.55 | 0.00 | 0.00 | 0.00 |
June | 412.31 | 45.71 | 366.60 | 558.64 | 130.59 | 0.00 | 0.00 | 0.00 |
July | 389.93 | 25.24 | 364.69 | 534.31 | 123.18 | 0.00 | 0.00 | 0.00 |
August | 310.36 | 7.34 | 303.01 | 404.36 | 145.33 | 0.00 | 0.00 | 0.00 |
September | 260.70 | 0.06 | 260.64 | 296.41 | 233.28 | 0.00 | 0.00 | 0.00 |
October | 186.72 | 0.00 | 186.72 | 102.66 | 484.27 | 0.00 | 0.00 | 0.00 |
November | 141.75 | 0.00 | 141.75 | 40.70 | 570.19 | 0.00 | 0.00 | 0.00 |
December | 119.90 | 0.00 | 119.90 | 22.66 | 694.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 248.90 | 7.71 | 241.19 | 222.50 | 389.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.90 | 0.00 | 119.90 | 22.66 | 123.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.31 | 45.71 | 366.60 | 558.64 | 694.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 772.04 | 473.13 | 298.91 | 699.02 | 1119.34 | 0.00 | 0.00 | 0.00 |
February | 1025.58 | 647.44 | 378.14 | 981.68 | 1148.29 | 0.00 | 0.00 | 0.00 |
March | 1237.84 | 722.02 | 515.82 | 1277.84 | 878.47 | 0.00 | 0.00 | 0.00 |
April | 1269.47 | 618.38 | 651.09 | 1282.34 | 772.36 | 0.00 | 0.00 | 0.00 |
May | 1484.00 | 619.87 | 864.13 | 1702.87 | 472.84 | 0.00 | 0.00 | 0.00 |
June | 1810.63 | 950.53 | 860.10 | 2445.68 | 265.02 | 0.00 | 0.00 | 0.00 |
July | 1646.00 | 783.78 | 862.22 | 2242.40 | 251.01 | 0.00 | 0.00 | 0.00 |
August | 1660.22 | 914.39 | 745.83 | 2242.29 | 295.81 | 0.00 | 0.00 | 0.00 |
September | 1381.39 | 750.41 | 630.98 | 1763.87 | 446.84 | 0.00 | 0.00 | 0.00 |
October | 1000.40 | 548.16 | 452.24 | 1050.96 | 933.46 | 0.00 | 0.00 | 0.00 |
November | 778.68 | 439.65 | 339.03 | 732.81 | 1080.33 | 0.00 | 0.00 | 0.00 |
December | 674.13 | 388.35 | 285.78 | 580.25 | 1284.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1229.14 | 654.35 | 574.79 | 1418.88 | 743.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 674.13 | 388.35 | 285.78 | 580.25 | 251.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1810.63 | 950.53 | 864.13 | 2445.68 | 1284.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.53 | 18.71 | 11.82 | 27.64 | 44.26 | 0.00 | 0.00 | 0.00 |
February | 40.55 | 25.60 | 14.95 | 38.81 | 45.40 | 0.00 | 0.00 | 0.00 |
March | 48.94 | 28.55 | 20.40 | 50.52 | 34.73 | 0.00 | 0.00 | 0.00 |
April | 50.19 | 24.45 | 25.74 | 50.70 | 30.54 | 0.00 | 0.00 | 0.00 |
May | 58.68 | 24.51 | 34.17 | 67.33 | 18.70 | 0.00 | 0.00 | 0.00 |
June | 71.59 | 37.58 | 34.01 | 96.70 | 10.48 | 0.00 | 0.00 | 0.00 |
July | 65.08 | 30.99 | 34.09 | 88.66 | 9.92 | 0.00 | 0.00 | 0.00 |
August | 65.64 | 36.15 | 29.49 | 88.66 | 11.70 | 0.00 | 0.00 | 0.00 |
September | 54.62 | 29.67 | 24.95 | 69.74 | 17.67 | 0.00 | 0.00 | 0.00 |
October | 39.55 | 21.67 | 17.88 | 41.55 | 36.91 | 0.00 | 0.00 | 0.00 |
November | 30.79 | 17.38 | 13.41 | 28.97 | 42.72 | 0.00 | 0.00 | 0.00 |
December | 26.65 | 15.35 | 11.30 | 22.94 | 50.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.60 | 25.87 | 22.73 | 56.10 | 29.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.65 | 15.35 | 11.30 | 22.94 | 9.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 71.59 | 37.58 | 34.17 | 96.70 | 50.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1228.19 | 1010.32 | 217.87 | 1416.27 | 585.51 | 0.00 | 0.00 | 0.00 |
February | 1178.06 | 939.22 | 238.84 | 1352.07 | 598.90 | 0.00 | 0.00 | 0.00 |
March | 868.56 | 571.46 | 297.10 | 1013.68 | 469.03 | 0.00 | 0.00 | 0.00 |
April | 562.54 | 226.20 | 336.34 | 604.13 | 418.38 | 0.00 | 0.00 | 0.00 |
May | 515.51 | 94.49 | 421.02 | 604.56 | 258.28 | 0.00 | 0.00 | 0.00 |
June | 475.29 | 86.87 | 388.42 | 695.03 | 144.34 | 0.00 | 0.00 | 0.00 |
July | 494.76 | 88.60 | 406.16 | 723.95 | 134.14 | 0.00 | 0.00 | 0.00 |
August | 629.93 | 263.33 | 366.60 | 920.99 | 159.24 | 0.00 | 0.00 | 0.00 |
September | 810.46 | 452.23 | 358.23 | 1106.87 | 249.33 | 0.00 | 0.00 | 0.00 |
October | 969.08 | 687.58 | 281.50 | 1178.64 | 496.75 | 0.00 | 0.00 | 0.00 |
November | 1180.68 | 941.17 | 239.51 | 1388.88 | 567.77 | 0.00 | 0.00 | 0.00 |
December | 1129.04 | 913.83 | 215.21 | 1276.84 | 652.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 834.91 | 520.58 | 314.33 | 1021.61 | 393.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.29 | 86.87 | 215.21 | 604.13 | 134.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1228.19 | 1010.32 | 421.02 | 1416.27 | 652.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1228.19 | 1010.32 | 217.87 | 1416.27 | 585.51 | 0.00 | 0.00 | 0.00 |
February | 1178.06 | 939.22 | 238.84 | 1352.07 | 598.90 | 0.00 | 0.00 | 0.00 |
March | 868.56 | 571.46 | 297.10 | 1013.68 | 469.03 | 0.00 | 0.00 | 0.00 |
April | 562.54 | 226.20 | 336.34 | 604.13 | 418.38 | 0.00 | 0.00 | 0.00 |
May | 515.51 | 94.49 | 421.02 | 604.56 | 258.28 | 0.00 | 0.00 | 0.00 |
June | 475.29 | 86.87 | 388.42 | 695.03 | 144.34 | 0.00 | 0.00 | 0.00 |
July | 494.76 | 88.60 | 406.16 | 723.95 | 134.14 | 0.00 | 0.00 | 0.00 |
August | 629.93 | 263.33 | 366.60 | 920.99 | 159.24 | 0.00 | 0.00 | 0.00 |
September | 810.46 | 452.23 | 358.23 | 1106.87 | 249.33 | 0.00 | 0.00 | 0.00 |
October | 969.08 | 687.58 | 281.50 | 1178.64 | 496.75 | 0.00 | 0.00 | 0.00 |
November | 1180.68 | 941.17 | 239.51 | 1388.88 | 567.77 | 0.00 | 0.00 | 0.00 |
December | 1129.04 | 913.83 | 215.21 | 1276.84 | 652.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 834.91 | 520.58 | 314.33 | 1021.61 | 393.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.29 | 86.87 | 215.21 | 604.13 | 134.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1228.19 | 1010.32 | 421.02 | 1416.27 | 652.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1228.11 | 1010.25 | 217.86 | 1416.18 | 585.47 | 0.00 | 0.00 | 0.00 |
February | 1177.99 | 939.16 | 238.82 | 1351.98 | 598.86 | 0.00 | 0.00 | 0.00 |
March | 868.50 | 571.42 | 297.08 | 1013.61 | 469.00 | 0.00 | 0.00 | 0.00 |
April | 562.51 | 226.19 | 336.32 | 604.09 | 418.36 | 0.00 | 0.00 | 0.00 |
May | 515.48 | 94.48 | 421.00 | 604.52 | 258.26 | 0.00 | 0.00 | 0.00 |
June | 475.26 | 86.86 | 388.39 | 694.99 | 144.33 | 0.00 | 0.00 | 0.00 |
July | 494.73 | 88.59 | 406.14 | 723.90 | 134.13 | 0.00 | 0.00 | 0.00 |
August | 629.89 | 263.32 | 366.57 | 920.94 | 159.23 | 0.00 | 0.00 | 0.00 |
September | 810.41 | 452.20 | 358.21 | 1106.80 | 249.31 | 0.00 | 0.00 | 0.00 |
October | 969.01 | 687.54 | 281.48 | 1178.57 | 496.71 | 0.00 | 0.00 | 0.00 |
November | 1180.61 | 941.11 | 239.49 | 1388.79 | 567.74 | 0.00 | 0.00 | 0.00 |
December | 1128.97 | 913.77 | 215.20 | 1276.76 | 652.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 834.86 | 520.54 | 314.31 | 1021.55 | 393.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.26 | 86.86 | 215.20 | 604.09 | 134.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1228.11 | 1010.25 | 421.00 | 1416.18 | 652.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 821.28 | 520.41 | 300.88 | 798.67 | 1150.47 | 0.00 | 0.00 | 0.00 |
February | 990.35 | 613.72 | 376.63 | 955.85 | 1166.63 | 0.00 | 0.00 | 0.00 |
March | 1159.64 | 639.80 | 519.84 | 1191.42 | 894.22 | 0.00 | 0.00 | 0.00 |
April | 1091.86 | 462.27 | 629.58 | 1072.41 | 788.73 | 0.00 | 0.00 | 0.00 |
May | 1334.53 | 470.47 | 864.06 | 1537.04 | 501.01 | 0.00 | 0.00 | 0.00 |
June | 1632.21 | 785.32 | 846.89 | 2235.33 | 298.25 | 0.00 | 0.00 | 0.00 |
July | 1329.86 | 487.10 | 842.76 | 1828.93 | 269.45 | 0.00 | 0.00 | 0.00 |
August | 1388.00 | 685.69 | 702.31 | 1876.10 | 310.96 | 0.00 | 0.00 | 0.00 |
September | 1230.74 | 590.22 | 640.52 | 1583.63 | 477.24 | 0.00 | 0.00 | 0.00 |
October | 1035.38 | 591.79 | 443.58 | 1121.87 | 952.50 | 0.00 | 0.00 | 0.00 |
November | 849.58 | 515.80 | 333.78 | 836.71 | 1096.46 | 0.00 | 0.00 | 0.00 |
December | 686.23 | 405.37 | 280.86 | 608.10 | 1291.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1129.49 | 563.32 | 566.17 | 1305.29 | 764.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.23 | 405.37 | 280.86 | 608.10 | 269.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1632.21 | 785.32 | 864.06 | 2235.33 | 1291.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.47 | 20.58 | 11.90 | 31.58 | 45.49 | 0.00 | 0.00 | 0.00 |
February | 39.16 | 24.27 | 14.89 | 37.79 | 46.13 | 0.00 | 0.00 | 0.00 |
March | 45.85 | 25.30 | 20.55 | 47.11 | 35.36 | 0.00 | 0.00 | 0.00 |
April | 43.17 | 18.28 | 24.89 | 42.40 | 31.19 | 0.00 | 0.00 | 0.00 |
May | 52.77 | 18.60 | 34.16 | 60.77 | 19.81 | 0.00 | 0.00 | 0.00 |
June | 64.54 | 31.05 | 33.49 | 88.38 | 11.79 | 0.00 | 0.00 | 0.00 |
July | 52.58 | 19.26 | 33.32 | 72.31 | 10.65 | 0.00 | 0.00 | 0.00 |
August | 54.88 | 27.11 | 27.77 | 74.18 | 12.30 | 0.00 | 0.00 | 0.00 |
September | 48.66 | 23.34 | 25.33 | 62.62 | 18.87 | 0.00 | 0.00 | 0.00 |
October | 40.94 | 23.40 | 17.54 | 44.36 | 37.66 | 0.00 | 0.00 | 0.00 |
November | 33.59 | 20.39 | 13.20 | 33.08 | 43.35 | 0.00 | 0.00 | 0.00 |
December | 27.13 | 16.03 | 11.10 | 24.04 | 51.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.66 | 22.27 | 22.39 | 51.61 | 30.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.13 | 16.03 | 11.10 | 24.04 | 10.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.54 | 31.05 | 34.16 | 88.38 | 51.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 384.46 | 0.00 | 384.46 | 72.65 | 1883.37 | 0.00 | 0.00 | 0.00 |
February | 483.22 | 0.00 | 483.22 | 92.08 | 1895.10 | 0.00 | 0.00 | 0.00 |
March | 657.51 | 0.00 | 657.51 | 302.35 | 1443.52 | 0.00 | 0.00 | 0.00 |
April | 825.73 | 4.58 | 821.15 | 459.02 | 1244.98 | 0.00 | 0.00 | 0.00 |
May | 1128.00 | 37.29 | 1090.72 | 1018.06 | 744.67 | 0.00 | 0.00 | 0.00 |
June | 1236.93 | 137.13 | 1099.80 | 1646.92 | 410.58 | 0.00 | 0.00 | 0.00 |
July | 1169.80 | 75.72 | 1094.08 | 1576.36 | 388.80 | 0.00 | 0.00 | 0.00 |
August | 931.07 | 22.03 | 909.05 | 1198.12 | 448.01 | 0.00 | 0.00 | 0.00 |
September | 782.10 | 0.18 | 781.92 | 883.12 | 698.77 | 0.00 | 0.00 | 0.00 |
October | 560.17 | 0.00 | 560.17 | 302.45 | 1445.99 | 0.00 | 0.00 | 0.00 |
November | 425.24 | 0.00 | 425.24 | 117.15 | 1715.67 | 0.00 | 0.00 | 0.00 |
December | 359.71 | 0.00 | 359.71 | 64.10 | 2093.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 746.69 | 23.13 | 723.56 | 647.46 | 1197.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 359.71 | 0.00 | 359.71 | 64.10 | 388.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1236.93 | 137.13 | 1099.80 | 1646.92 | 2093.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 802.58 | 491.85 | 310.74 | 711.62 | 1179.89 | 0.00 | 0.00 | 0.00 |
February | 1066.14 | 673.05 | 393.09 | 1001.39 | 1211.40 | 0.00 | 0.00 | 0.00 |
March | 1286.81 | 750.58 | 536.22 | 1304.52 | 927.06 | 0.00 | 0.00 | 0.00 |
April | 1319.69 | 642.84 | 676.85 | 1309.91 | 810.84 | 0.00 | 0.00 | 0.00 |
May | 1542.70 | 644.39 | 898.31 | 1743.24 | 502.42 | 0.00 | 0.00 | 0.00 |
June | 1882.25 | 988.13 | 894.12 | 2524.70 | 276.35 | 0.00 | 0.00 | 0.00 |
July | 1711.11 | 814.79 | 896.32 | 2314.89 | 261.86 | 0.00 | 0.00 | 0.00 |
August | 1725.89 | 950.56 | 775.33 | 2320.35 | 300.64 | 0.00 | 0.00 | 0.00 |
September | 1436.03 | 780.09 | 655.94 | 1827.72 | 448.20 | 0.00 | 0.00 | 0.00 |
October | 1039.97 | 569.84 | 470.13 | 1086.58 | 942.77 | 0.00 | 0.00 | 0.00 |
November | 809.48 | 457.04 | 352.44 | 755.47 | 1104.98 | 0.00 | 0.00 | 0.00 |
December | 700.80 | 403.71 | 297.09 | 595.61 | 1324.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1277.76 | 680.24 | 597.52 | 1460.15 | 771.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 700.80 | 403.71 | 297.09 | 595.61 | 261.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1882.25 | 988.13 | 898.31 | 2524.70 | 1324.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3684.63 | 3031.01 | 653.63 | 4218.00 | 1713.01 | 0.00 | 0.00 | 0.00 |
February | 3534.25 | 2817.72 | 716.52 | 4010.93 | 1774.49 | 0.00 | 0.00 | 0.00 |
March | 2605.72 | 1714.42 | 891.30 | 2997.22 | 1417.34 | 0.00 | 0.00 | 0.00 |
April | 1687.66 | 678.61 | 1009.04 | 1769.38 | 1282.01 | 0.00 | 0.00 | 0.00 |
May | 1546.55 | 283.47 | 1263.08 | 1763.70 | 817.42 | 0.00 | 0.00 | 0.00 |
June | 1425.87 | 260.61 | 1165.26 | 2057.74 | 451.31 | 0.00 | 0.00 | 0.00 |
July | 1484.30 | 265.80 | 1218.50 | 2147.04 | 418.13 | 0.00 | 0.00 | 0.00 |
August | 1889.81 | 790.01 | 1099.80 | 2747.68 | 473.44 | 0.00 | 0.00 | 0.00 |
September | 2431.43 | 1356.72 | 1074.70 | 3311.39 | 716.08 | 0.00 | 0.00 | 0.00 |
October | 2907.28 | 2062.78 | 844.50 | 3522.38 | 1430.84 | 0.00 | 0.00 | 0.00 |
November | 3542.11 | 2823.58 | 718.53 | 4142.10 | 1638.52 | 0.00 | 0.00 | 0.00 |
December | 3387.18 | 2741.54 | 645.64 | 3800.40 | 1901.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2504.77 | 1561.76 | 943.01 | 3035.11 | 1166.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1425.87 | 260.61 | 645.64 | 1763.70 | 418.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3684.63 | 3031.01 | 1263.08 | 4218.00 | 1901.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 853.77 | 540.99 | 312.77 | 816.18 | 1209.05 | 0.00 | 0.00 | 0.00 |
February | 1029.52 | 638.00 | 391.52 | 975.80 | 1228.28 | 0.00 | 0.00 | 0.00 |
March | 1205.51 | 665.11 | 540.40 | 1215.80 | 947.42 | 0.00 | 0.00 | 0.00 |
April | 1135.04 | 480.56 | 654.48 | 1093.44 | 832.61 | 0.00 | 0.00 | 0.00 |
May | 1387.31 | 489.08 | 898.23 | 1572.91 | 534.77 | 0.00 | 0.00 | 0.00 |
June | 1696.77 | 816.38 | 880.39 | 2310.15 | 310.76 | 0.00 | 0.00 | 0.00 |
July | 1382.46 | 506.37 | 876.09 | 1887.62 | 284.39 | 0.00 | 0.00 | 0.00 |
August | 1442.90 | 712.81 | 730.09 | 1942.48 | 318.64 | 0.00 | 0.00 | 0.00 |
September | 1279.42 | 613.57 | 665.85 | 1643.51 | 479.86 | 0.00 | 0.00 | 0.00 |
October | 1076.33 | 615.20 | 461.13 | 1163.99 | 961.16 | 0.00 | 0.00 | 0.00 |
November | 883.19 | 536.20 | 346.98 | 865.24 | 1119.02 | 0.00 | 0.00 | 0.00 |
December | 713.37 | 421.41 | 291.96 | 625.41 | 1330.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1174.16 | 585.60 | 588.56 | 1344.24 | 794.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 713.37 | 421.41 | 291.96 | 625.41 | 284.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1696.77 | 816.38 | 898.23 | 2310.15 | 1330.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.219136E+09 | 0.478052E+10 |
February | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.241565E+09 | 0.438629E+10 |
March | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.833762E+09 | 0.368059E+10 |
April | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.121564E+10 | 0.303328E+10 |
May | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.275227E+10 | 0.192113E+10 |
June | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.426039E+10 | 0.104107E+10 |
July | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.421057E+10 | 0.102091E+10 |
August | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.320384E+10 | 0.116469E+10 |
September | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.229925E+10 | 0.173463E+10 |
October | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.844518E+09 | 0.365589E+10 |
November | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.334417E+09 | 0.420178E+10 |
December | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.188721E+09 | 0.536527E+10 |
Annual Sum or Average | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.206041E+11 | 0.359861E+11 |
Minimum of Months | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.188721E+09 | 0.102091E+10 |
Maximum of Months | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.426039E+10 | 0.536527E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.194734E+10 | 0.299914E+10 |
February | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.244932E+10 | 0.280757E+10 |
March | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.351826E+10 | 0.237034E+10 |
April | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.341890E+10 | 0.198020E+10 |
May | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.468849E+10 | 0.130033E+10 |
June | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.654329E+10 | 0.700406E+09 |
July | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.619797E+10 | 0.686752E+09 |
August | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.621657E+10 | 0.781839E+09 |
September | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.474890E+10 | 0.111746E+10 |
October | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.293593E+10 | 0.239352E+10 |
November | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.199547E+10 | 0.271168E+10 |
December | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.162807E+10 | 0.339515E+10 |
Annual Sum or Average | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.462885E+11 | 0.232444E+11 |
Minimum of Months | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.162807E+10 | 0.686752E+09 |
Maximum of Months | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.654329E+10 | 0.339515E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.113531E+11 | 0.436599E+10 |
February | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.973386E+10 | 0.410893E+10 |
March | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.805003E+10 | 0.361975E+10 |
April | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.460870E+10 | 0.312876E+10 |
May | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.473669E+10 | 0.210608E+10 |
June | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.532018E+10 | 0.113896E+10 |
July | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.573502E+10 | 0.109337E+10 |
August | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.734826E+10 | 0.122929E+10 |
September | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.858472E+10 | 0.178294E+10 |
October | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.946165E+10 | 0.363583E+10 |
November | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.107790E+11 | 0.403366E+10 |
December | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.102260E+11 | 0.486731E+10 |
Annual Sum or Average | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.959373E+11 | 0.351109E+11 |
Minimum of Months | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.460870E+10 | 0.109337E+10 |
Maximum of Months | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.113531E+11 | 0.486731E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.220980E+10 | 0.307078E+10 |
February | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.237541E+10 | 0.284059E+10 |
March | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.327046E+10 | 0.241498E+10 |
April | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.285079E+10 | 0.202934E+10 |
May | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.422136E+10 | 0.137688E+10 |
June | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.597739E+10 | 0.784051E+09 |
July | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.504483E+10 | 0.743488E+09 |
August | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.519589E+10 | 0.827345E+09 |
September | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.426374E+10 | 0.119266E+10 |
October | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.313857E+10 | 0.243456E+10 |
November | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.226705E+10 | 0.274366E+10 |
December | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.169361E+10 | 0.340676E+10 |
Annual Sum or Average | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.425089E+11 | 0.238651E+11 |
Minimum of Months | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.169361E+10 | 0.743488E+09 |
Maximum of Months | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.597739E+10 | 0.340676E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343232E+09 | 0.00 | 0.343232E+09 | 74979747.40 | 0.162781E+10 |
February | 0.389652E+09 | 0.00 | 0.389652E+09 | 88118539.13 | 0.147661E+10 |
March | 0.586995E+09 | 0.00 | 0.586995E+09 | 0.300876E+09 | 0.123055E+10 |
April | 0.713401E+09 | 3957640.90 | 0.709443E+09 | 0.429647E+09 | 0.102817E+10 |
May | 0.100703E+10 | 33288481.68 | 0.973745E+09 | 0.951611E+09 | 0.628171E+09 |
June | 0.106866E+10 | 0.118478E+09 | 0.950182E+09 | 0.144792E+10 | 0.338469E+09 |
July | 0.104435E+10 | 67602645.39 | 0.976748E+09 | 0.143104E+10 | 0.329915E+09 |
August | 0.831224E+09 | 19663953.70 | 0.811560E+09 | 0.108299E+10 | 0.389242E+09 |
September | 0.675704E+09 | 158711.02 | 0.675546E+09 | 0.768257E+09 | 0.604618E+09 |
October | 0.500100E+09 | 0.00 | 0.500100E+09 | 0.274953E+09 | 0.129700E+10 |
November | 0.367392E+09 | 0.00 | 0.367392E+09 | 0.105501E+09 | 0.147784E+10 |
December | 0.321136E+09 | 0.00 | 0.321136E+09 | 60687460.38 | 0.185968E+10 |
Annual Sum or Average | 0.784888E+10 | 0.243150E+09 | 0.760573E+10 | 0.701658E+10 | 0.122881E+11 |
Minimum of Months | 0.321136E+09 | 0.00 | 0.321136E+09 | 60687460.38 | 0.329915E+09 |
Maximum of Months | 0.106866E+10 | 0.118478E+09 | 0.976748E+09 | 0.144792E+10 | 0.185968E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343246E+09 | 0.00 | 0.343246E+09 | 74980720.20 | 0.162791E+10 |
February | 0.389669E+09 | 0.00 | 0.389669E+09 | 88120300.18 | 0.147670E+10 |
March | 0.587020E+09 | 0.00 | 0.587020E+09 | 0.300885E+09 | 0.123063E+10 |
April | 0.713429E+09 | 3957747.28 | 0.709472E+09 | 0.429659E+09 | 0.102824E+10 |
May | 0.100707E+10 | 33289376.48 | 0.973784E+09 | 0.951642E+09 | 0.628209E+09 |
June | 0.106870E+10 | 0.118481E+09 | 0.950222E+09 | 0.144798E+10 | 0.338487E+09 |
July | 0.104439E+10 | 67604462.56 | 0.976787E+09 | 0.143110E+10 | 0.329933E+09 |
August | 0.831259E+09 | 19664482.27 | 0.811595E+09 | 0.108304E+10 | 0.389264E+09 |
September | 0.675733E+09 | 158715.28 | 0.675574E+09 | 0.768290E+09 | 0.604653E+09 |
October | 0.500121E+09 | 0.00 | 0.500121E+09 | 0.274963E+09 | 0.129708E+10 |
November | 0.367408E+09 | 0.00 | 0.367408E+09 | 0.105503E+09 | 0.147793E+10 |
December | 0.321149E+09 | 0.00 | 0.321149E+09 | 60688803.02 | 0.185980E+10 |
Annual Sum or Average | 0.784920E+10 | 0.243156E+09 | 0.760605E+10 | 0.701685E+10 | 0.122888E+11 |
Minimum of Months | 0.321149E+09 | 0.00 | 0.321149E+09 | 60688803.02 | 0.329933E+09 |
Maximum of Months | 0.106870E+10 | 0.118481E+09 | 0.976787E+09 | 0.144798E+10 | 0.185980E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343246E+09 | 0.00 | 0.343246E+09 | 74980720.20 | 0.162791E+10 |
February | 0.389669E+09 | 0.00 | 0.389669E+09 | 88120300.18 | 0.147670E+10 |
March | 0.587020E+09 | 0.00 | 0.587020E+09 | 0.300885E+09 | 0.123063E+10 |
April | 0.713429E+09 | 3957747.28 | 0.709472E+09 | 0.429659E+09 | 0.102824E+10 |
May | 0.100707E+10 | 33289376.48 | 0.973784E+09 | 0.951642E+09 | 0.628209E+09 |
June | 0.106870E+10 | 0.118481E+09 | 0.950222E+09 | 0.144798E+10 | 0.338487E+09 |
July | 0.104439E+10 | 67604462.56 | 0.976787E+09 | 0.143110E+10 | 0.329933E+09 |
August | 0.831259E+09 | 19664482.27 | 0.811595E+09 | 0.108304E+10 | 0.389264E+09 |
September | 0.675733E+09 | 158715.28 | 0.675574E+09 | 0.768290E+09 | 0.604653E+09 |
October | 0.500121E+09 | 0.00 | 0.500121E+09 | 0.274963E+09 | 0.129708E+10 |
November | 0.367408E+09 | 0.00 | 0.367408E+09 | 0.105503E+09 | 0.147793E+10 |
December | 0.321149E+09 | 0.00 | 0.321149E+09 | 60688803.02 | 0.185980E+10 |
Annual Sum or Average | 0.784920E+10 | 0.243156E+09 | 0.760605E+10 | 0.701685E+10 | 0.122888E+11 |
Minimum of Months | 0.321149E+09 | 0.00 | 0.321149E+09 | 60688803.02 | 0.329933E+09 |
Maximum of Months | 0.106870E+10 | 0.118481E+09 | 0.976787E+09 | 0.144798E+10 | 0.185980E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206784E+10 | 0.126723E+10 | 0.800611E+09 | 0.187227E+10 | 0.299803E+10 |
February | 0.248107E+10 | 0.156629E+10 | 0.914786E+09 | 0.237489E+10 | 0.277795E+10 |
March | 0.331543E+10 | 0.193386E+10 | 0.138158E+10 | 0.342257E+10 | 0.235288E+10 |
April | 0.329048E+10 | 0.160284E+10 | 0.168763E+10 | 0.332382E+10 | 0.200197E+10 |
May | 0.397473E+10 | 0.166025E+10 | 0.231448E+10 | 0.456097E+10 | 0.126644E+10 |
June | 0.469314E+10 | 0.246377E+10 | 0.222938E+10 | 0.633920E+10 | 0.686927E+09 |
July | 0.440866E+10 | 0.209929E+10 | 0.230937E+10 | 0.600604E+10 | 0.672303E+09 |
August | 0.444673E+10 | 0.244909E+10 | 0.199764E+10 | 0.600575E+10 | 0.792310E+09 |
September | 0.358056E+10 | 0.194505E+10 | 0.163550E+10 | 0.457194E+10 | 0.115822E+10 |
October | 0.267947E+10 | 0.146819E+10 | 0.121128E+10 | 0.281489E+10 | 0.250019E+10 |
November | 0.201835E+10 | 0.113957E+10 | 0.878772E+09 | 0.189944E+10 | 0.280022E+10 |
December | 0.180559E+10 | 0.104015E+10 | 0.765447E+09 | 0.155414E+10 | 0.343995E+10 |
Annual Sum or Average | 0.387621E+11 | 0.206356E+11 | 0.181265E+11 | 0.447459E+11 | 0.234474E+11 |
Minimum of Months | 0.180559E+10 | 0.104015E+10 | 0.765447E+09 | 0.155414E+10 | 0.672303E+09 |
Maximum of Months | 0.469314E+10 | 0.246377E+10 | 0.231448E+10 | 0.633920E+10 | 0.343995E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 81760686.43 | 50105254.26 | 31655432.17 | 74027693.78 | 0.118540E+09 |
February | 98099357.20 | 61929538.73 | 36169818.47 | 93901083.75 | 0.109838E+09 |
March | 0.131089E+09 | 76462961.31 | 54626324.10 | 0.135325E+09 | 93030862.07 |
April | 0.130102E+09 | 63374965.96 | 66727507.05 | 0.131421E+09 | 79156072.38 |
May | 0.157157E+09 | 65644977.66 | 91512381.12 | 0.180337E+09 | 50074035.26 |
June | 0.185563E+09 | 97415121.80 | 88147574.49 | 0.250646E+09 | 27160494.20 |
July | 0.174314E+09 | 83003846.61 | 91310418.94 | 0.237473E+09 | 26582240.25 |
August | 0.175820E+09 | 96834891.99 | 78984946.19 | 0.237462E+09 | 31327216.94 |
September | 0.141572E+09 | 76905604.65 | 64666355.52 | 0.180770E+09 | 45794969.68 |
October | 0.105944E+09 | 58050904.71 | 47892977.97 | 0.111298E+09 | 98855279.07 |
November | 79803621.74 | 45057757.81 | 34745863.93 | 75101990.98 | 0.110718E+09 |
December | 71391537.52 | 41126470.69 | 30265066.83 | 61449198.34 | 0.136012E+09 |
Annual Sum or Average | 0.153262E+10 | 0.815912E+09 | 0.716705E+09 | 0.176921E+10 | 0.927089E+09 |
Minimum of Months | 71391537.52 | 41126470.69 | 30265066.83 | 61449198.34 | 26582240.25 |
Maximum of Months | 0.185563E+09 | 97415121.80 | 91512381.12 | 0.250646E+09 | 0.136012E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328958E+10 | 0.270603E+10 | 0.583550E+09 | 0.379334E+10 | 0.156823E+10 |
February | 0.284996E+10 | 0.227217E+10 | 0.577798E+09 | 0.327092E+10 | 0.144885E+10 |
March | 0.232635E+10 | 0.153060E+10 | 0.795748E+09 | 0.271504E+10 | 0.125626E+10 |
April | 0.145812E+10 | 0.586310E+09 | 0.871805E+09 | 0.156589E+10 | 0.108445E+10 |
May | 0.138075E+10 | 0.253078E+09 | 0.112767E+10 | 0.161925E+10 | 0.691775E+09 |
June | 0.123194E+10 | 0.225161E+09 | 0.100678E+10 | 0.180153E+10 | 0.374118E+09 |
July | 0.132517E+10 | 0.237298E+09 | 0.108787E+10 | 0.193902E+10 | 0.359285E+09 |
August | 0.168720E+10 | 0.705309E+09 | 0.981894E+09 | 0.246679E+10 | 0.426507E+09 |
September | 0.210072E+10 | 0.117218E+10 | 0.928536E+09 | 0.286900E+10 | 0.646257E+09 |
October | 0.259557E+10 | 0.184161E+10 | 0.753960E+09 | 0.315687E+10 | 0.133048E+10 |
November | 0.306033E+10 | 0.243952E+10 | 0.620807E+09 | 0.359998E+10 | 0.147167E+10 |
December | 0.302402E+10 | 0.244760E+10 | 0.576423E+09 | 0.341990E+10 | 0.174875E+10 |
Annual Sum or Average | 0.263297E+11 | 0.164169E+11 | 0.991283E+10 | 0.322175E+11 | 0.124066E+11 |
Minimum of Months | 0.123194E+10 | 0.225161E+09 | 0.576423E+09 | 0.156589E+10 | 0.359285E+09 |
Maximum of Months | 0.328958E+10 | 0.270603E+10 | 0.112767E+10 | 0.379334E+10 | 0.174875E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328958E+10 | 0.270603E+10 | 0.583550E+09 | 0.379334E+10 | 0.156823E+10 |
February | 0.284996E+10 | 0.227217E+10 | 0.577798E+09 | 0.327092E+10 | 0.144885E+10 |
March | 0.232635E+10 | 0.153060E+10 | 0.795748E+09 | 0.271504E+10 | 0.125626E+10 |
April | 0.145812E+10 | 0.586310E+09 | 0.871805E+09 | 0.156589E+10 | 0.108445E+10 |
May | 0.138075E+10 | 0.253078E+09 | 0.112767E+10 | 0.161925E+10 | 0.691775E+09 |
June | 0.123194E+10 | 0.225161E+09 | 0.100678E+10 | 0.180153E+10 | 0.374118E+09 |
July | 0.132517E+10 | 0.237298E+09 | 0.108787E+10 | 0.193902E+10 | 0.359285E+09 |
August | 0.168720E+10 | 0.705309E+09 | 0.981894E+09 | 0.246679E+10 | 0.426507E+09 |
September | 0.210072E+10 | 0.117218E+10 | 0.928536E+09 | 0.286900E+10 | 0.646257E+09 |
October | 0.259557E+10 | 0.184161E+10 | 0.753960E+09 | 0.315687E+10 | 0.133048E+10 |
November | 0.306033E+10 | 0.243952E+10 | 0.620807E+09 | 0.359998E+10 | 0.147167E+10 |
December | 0.302402E+10 | 0.244760E+10 | 0.576423E+09 | 0.341990E+10 | 0.174875E+10 |
Annual Sum or Average | 0.263297E+11 | 0.164169E+11 | 0.991283E+10 | 0.322175E+11 | 0.124066E+11 |
Minimum of Months | 0.123194E+10 | 0.225161E+09 | 0.576423E+09 | 0.156589E+10 | 0.359285E+09 |
Maximum of Months | 0.328958E+10 | 0.270603E+10 | 0.112767E+10 | 0.379334E+10 | 0.174875E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.328937E+10 | 0.270586E+10 | 0.583513E+09 | 0.379310E+10 | 0.156813E+10 |
February | 0.284978E+10 | 0.227202E+10 | 0.577762E+09 | 0.327072E+10 | 0.144876E+10 |
March | 0.232620E+10 | 0.153050E+10 | 0.795698E+09 | 0.271487E+10 | 0.125618E+10 |
April | 0.145802E+10 | 0.586273E+09 | 0.871750E+09 | 0.156579E+10 | 0.108439E+10 |
May | 0.138066E+10 | 0.253062E+09 | 0.112760E+10 | 0.161915E+10 | 0.691731E+09 |
June | 0.123186E+10 | 0.225147E+09 | 0.100672E+10 | 0.180141E+10 | 0.374095E+09 |
July | 0.132508E+10 | 0.237283E+09 | 0.108780E+10 | 0.193889E+10 | 0.359262E+09 |
August | 0.168710E+10 | 0.705264E+09 | 0.981832E+09 | 0.246663E+10 | 0.426480E+09 |
September | 0.210059E+10 | 0.117211E+10 | 0.928477E+09 | 0.286882E+10 | 0.646216E+09 |
October | 0.259541E+10 | 0.184149E+10 | 0.753912E+09 | 0.315667E+10 | 0.133040E+10 |
November | 0.306013E+10 | 0.243937E+10 | 0.620768E+09 | 0.359976E+10 | 0.147158E+10 |
December | 0.302383E+10 | 0.244744E+10 | 0.576387E+09 | 0.341969E+10 | 0.174864E+10 |
Annual Sum or Average | 0.263280E+11 | 0.164158E+11 | 0.991221E+10 | 0.322155E+11 | 0.124059E+11 |
Minimum of Months | 0.123186E+10 | 0.225147E+09 | 0.576387E+09 | 0.156579E+10 | 0.359262E+09 |
Maximum of Months | 0.328937E+10 | 0.270586E+10 | 0.112760E+10 | 0.379310E+10 | 0.174864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219973E+10 | 0.139386E+10 | 0.805865E+09 | 0.213917E+10 | 0.308143E+10 |
February | 0.239586E+10 | 0.148472E+10 | 0.911142E+09 | 0.231239E+10 | 0.282231E+10 |
March | 0.310598E+10 | 0.171363E+10 | 0.139235E+10 | 0.319110E+10 | 0.239509E+10 |
April | 0.283009E+10 | 0.119821E+10 | 0.163188E+10 | 0.277969E+10 | 0.204438E+10 |
May | 0.357440E+10 | 0.126010E+10 | 0.231429E+10 | 0.411681E+10 | 0.134191E+10 |
June | 0.423068E+10 | 0.203554E+10 | 0.219515E+10 | 0.579397E+10 | 0.773062E+09 |
July | 0.356191E+10 | 0.130466E+10 | 0.225725E+10 | 0.489861E+10 | 0.721683E+09 |
August | 0.371762E+10 | 0.183655E+10 | 0.188107E+10 | 0.502495E+10 | 0.832886E+09 |
September | 0.319008E+10 | 0.152985E+10 | 0.166023E+10 | 0.410477E+10 | 0.123700E+10 |
October | 0.277316E+10 | 0.158506E+10 | 0.118810E+10 | 0.300482E+10 | 0.255118E+10 |
November | 0.220212E+10 | 0.133695E+10 | 0.865163E+09 | 0.216875E+10 | 0.284201E+10 |
December | 0.183800E+10 | 0.108575E+10 | 0.752247E+09 | 0.162873E+10 | 0.346024E+10 |
Annual Sum or Average | 0.356196E+11 | 0.177649E+11 | 0.178547E+11 | 0.411638E+11 | 0.241032E+11 |
Minimum of Months | 0.183800E+10 | 0.108575E+10 | 0.752247E+09 | 0.162873E+10 | 0.721683E+09 |
Maximum of Months | 0.423068E+10 | 0.203554E+10 | 0.231429E+10 | 0.579397E+10 | 0.346024E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86975063.61 | 55111960.46 | 31863103.15 | 84580459.19 | 0.121837E+09 |
February | 94730006.39 | 58704353.86 | 36025652.54 | 91429630.85 | 0.111592E+09 |
March | 0.122807E+09 | 67755274.10 | 55052016.37 | 0.126173E+09 | 94699695.65 |
April | 0.111899E+09 | 47375869.14 | 64522999.00 | 0.109906E+09 | 80833107.44 |
May | 0.141328E+09 | 49823187.03 | 91504875.63 | 0.162775E+09 | 53057964.63 |
June | 0.167277E+09 | 80483061.54 | 86793885.65 | 0.229088E+09 | 30566167.09 |
July | 0.140834E+09 | 51584726.00 | 89249486.79 | 0.193686E+09 | 28534687.12 |
August | 0.146991E+09 | 72615278.85 | 74375646.53 | 0.198682E+09 | 32931553.82 |
September | 0.126132E+09 | 60488701.33 | 65643764.97 | 0.162298E+09 | 48909815.28 |
October | 0.109648E+09 | 62671682.37 | 46976140.24 | 0.118808E+09 | 0.100871E+09 |
November | 87069489.53 | 52861796.30 | 34207693.24 | 85750091.65 | 0.112371E+09 |
December | 72672600.43 | 42929506.76 | 29743093.67 | 64398091.22 | 0.136815E+09 |
Annual Sum or Average | 0.140836E+10 | 0.702405E+09 | 0.705958E+09 | 0.162757E+10 | 0.953018E+09 |
Minimum of Months | 72672600.43 | 42929506.76 | 29743093.67 | 64398091.22 | 28534687.12 |
Maximum of Months | 0.167277E+09 | 80483061.54 | 91504875.63 | 0.229088E+09 | 0.136815E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.194598E+09 | 0.504442E+10 |
February | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.222751E+09 | 0.458463E+10 |
March | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.809815E+09 | 0.386631E+10 |
April | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.118979E+10 | 0.322699E+10 |
May | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.272677E+10 | 0.199453E+10 |
June | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.426883E+10 | 0.106424E+10 |
July | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.422213E+10 | 0.104136E+10 |
August | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.320904E+10 | 0.119996E+10 |
September | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.228904E+10 | 0.181122E+10 |
October | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.810086E+09 | 0.387293E+10 |
November | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.303645E+09 | 0.444703E+10 |
December | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.171699E+09 | 0.560783E+10 |
Annual Sum or Average | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.204182E+11 | 0.377614E+11 |
Minimum of Months | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.171699E+09 | 0.104136E+10 |
Maximum of Months | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.426883E+10 | 0.560783E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.190600E+10 | 0.316022E+10 |
February | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.242256E+10 | 0.293061E+10 |
March | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.349404E+10 | 0.248304E+10 |
April | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.339529E+10 | 0.210170E+10 |
May | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.466909E+10 | 0.134569E+10 |
June | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.654402E+10 | 0.716310E+09 |
July | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.620021E+10 | 0.701361E+09 |
August | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.621482E+10 | 0.805234E+09 |
September | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.473745E+10 | 0.116174E+10 |
October | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.291029E+10 | 0.252511E+10 |
November | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.195817E+10 | 0.286411E+10 |
December | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.159528E+10 | 0.354825E+10 |
Annual Sum or Average | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.460472E+11 | 0.243434E+11 |
Minimum of Months | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.159528E+10 | 0.701361E+09 |
Maximum of Months | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.654402E+10 | 0.354825E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.112975E+11 | 0.458812E+10 |
February | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.970324E+10 | 0.429284E+10 |
March | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.802775E+10 | 0.379620E+10 |
April | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.458622E+10 | 0.332296E+10 |
May | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.472389E+10 | 0.218937E+10 |
June | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.533367E+10 | 0.116980E+10 |
July | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.575063E+10 | 0.111993E+10 |
August | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.735939E+10 | 0.126806E+10 |
September | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.858313E+10 | 0.185609E+10 |
October | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.943435E+10 | 0.383237E+10 |
November | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.107363E+11 | 0.424704E+10 |
December | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.101790E+11 | 0.509333E+10 |
Annual Sum or Average | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.957151E+11 | 0.367761E+11 |
Minimum of Months | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.458622E+10 | 0.111993E+10 |
Maximum of Months | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.112975E+11 | 0.509333E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.218605E+10 | 0.323833E+10 |
February | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.236064E+10 | 0.297145E+10 |
March | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.325640E+10 | 0.253757E+10 |
April | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.283421E+10 | 0.215813E+10 |
May | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.421287E+10 | 0.143232E+10 |
June | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.598790E+10 | 0.805502E+09 |
July | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.505580E+10 | 0.761711E+09 |
August | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.520275E+10 | 0.853442E+09 |
September | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.425997E+10 | 0.124380E+10 |
October | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.311764E+10 | 0.257436E+10 |
November | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.224270E+10 | 0.290050E+10 |
December | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.167510E+10 | 0.356403E+10 |
Annual Sum or Average | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.423920E+11 | 0.250411E+11 |
Minimum of Months | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.167510E+10 | 0.761711E+09 |
Maximum of Months | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.598790E+10 | 0.356403E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.82 | 1784.84 | 384.46 | 0.00 | 384.46 | 0.00 | 0.00 |
February | 99.85 | 1813.12 | 483.22 | 0.00 | 483.22 | 0.00 | 0.00 |
March | 311.29 | 1374.17 | 657.51 | 0.00 | 657.51 | 0.00 | 0.00 |
April | 469.00 | 1170.25 | 825.73 | 4.58 | 821.15 | 0.00 | 0.00 |
May | 1027.58 | 717.27 | 1128.00 | 37.29 | 1090.72 | 0.00 | 0.00 |
June | 1643.67 | 401.65 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
July | 1572.05 | 381.16 | 1169.80 | 75.72 | 1094.08 | 0.00 | 0.00 |
August | 1196.18 | 434.85 | 931.07 | 22.03 | 909.05 | 0.00 | 0.00 |
September | 887.05 | 669.23 | 782.10 | 0.18 | 781.92 | 0.00 | 0.00 |
October | 315.31 | 1364.95 | 560.17 | 0.00 | 560.17 | 0.00 | 0.00 |
November | 129.02 | 1621.06 | 425.24 | 0.00 | 425.24 | 0.00 | 0.00 |
December | 70.46 | 2003.16 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Annual Sum or Average | 653.35 | 1141.11 | 746.69 | 23.13 | 723.56 | 0.00 | 0.00 |
Minimum of Months | 70.46 | 381.16 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Maximum of Months | 1643.67 | 2003.16 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 727.06 | 1119.75 | 802.58 | 491.85 | 310.74 | 0.00 | 0.00 |
February | 1012.45 | 1160.53 | 1066.14 | 673.05 | 393.09 | 0.00 | 0.00 |
March | 1313.57 | 884.98 | 1286.81 | 750.58 | 536.22 | 0.00 | 0.00 |
April | 1319.02 | 763.96 | 1319.69 | 642.84 | 676.85 | 0.00 | 0.00 |
May | 1750.48 | 485.49 | 1542.70 | 644.39 | 898.31 | 0.00 | 0.00 |
June | 2524.42 | 270.22 | 1882.25 | 988.13 | 894.12 | 0.00 | 0.00 |
July | 2314.06 | 256.40 | 1711.11 | 814.79 | 896.32 | 0.00 | 0.00 |
August | 2321.00 | 291.91 | 1725.89 | 950.56 | 775.33 | 0.00 | 0.00 |
September | 1832.14 | 431.12 | 1436.03 | 780.09 | 655.94 | 0.00 | 0.00 |
October | 1096.15 | 893.64 | 1039.97 | 569.84 | 470.13 | 0.00 | 0.00 |
November | 769.86 | 1046.17 | 809.48 | 457.04 | 352.44 | 0.00 | 0.00 |
December | 607.85 | 1267.60 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Annual Sum or Average | 1467.80 | 737.07 | 1277.76 | 680.24 | 597.52 | 0.00 | 0.00 |
Minimum of Months | 607.85 | 256.40 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Maximum of Months | 2524.42 | 1267.60 | 1882.25 | 988.13 | 898.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4238.77 | 1630.07 | 3684.63 | 3031.01 | 653.63 | 0.00 | 0.00 |
February | 4023.59 | 1698.47 | 3534.25 | 2817.72 | 716.52 | 0.00 | 0.00 |
March | 3005.54 | 1351.46 | 2605.72 | 1714.42 | 891.30 | 0.00 | 0.00 |
April | 1778.05 | 1207.08 | 1687.66 | 678.61 | 1009.04 | 0.00 | 0.00 |
May | 1768.48 | 786.32 | 1546.55 | 283.47 | 1263.08 | 0.00 | 0.00 |
June | 2052.54 | 439.41 | 1425.87 | 260.61 | 1165.26 | 0.00 | 0.00 |
July | 2141.21 | 408.22 | 1484.30 | 265.80 | 1218.50 | 0.00 | 0.00 |
August | 2743.52 | 458.96 | 1889.81 | 790.01 | 1099.80 | 0.00 | 0.00 |
September | 3312.00 | 687.86 | 2431.43 | 1356.72 | 1074.70 | 0.00 | 0.00 |
October | 3532.58 | 1357.46 | 2907.28 | 2062.78 | 844.50 | 0.00 | 0.00 |
November | 4158.58 | 1556.20 | 3542.11 | 2823.58 | 718.53 | 0.00 | 0.00 |
December | 3817.96 | 1817.25 | 3387.18 | 2741.54 | 645.64 | 0.00 | 0.00 |
Annual Sum or Average | 3042.15 | 1113.36 | 2504.77 | 1561.76 | 943.01 | 0.00 | 0.00 |
Minimum of Months | 1768.48 | 408.22 | 1425.87 | 260.61 | 645.64 | 0.00 | 0.00 |
Maximum of Months | 4238.77 | 1817.25 | 3684.63 | 3031.01 | 1263.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 825.05 | 1146.50 | 853.77 | 540.99 | 312.77 | 0.00 | 0.00 |
February | 981.90 | 1174.19 | 1029.52 | 638.00 | 391.52 | 0.00 | 0.00 |
March | 1221.05 | 901.65 | 1205.51 | 665.11 | 540.40 | 0.00 | 0.00 |
April | 1099.84 | 782.92 | 1135.04 | 480.56 | 654.48 | 0.00 | 0.00 |
May | 1576.08 | 514.07 | 1387.31 | 489.08 | 898.23 | 0.00 | 0.00 |
June | 2306.09 | 302.49 | 1696.77 | 816.38 | 880.39 | 0.00 | 0.00 |
July | 1883.52 | 277.59 | 1382.46 | 506.37 | 876.09 | 0.00 | 0.00 |
August | 1939.92 | 308.90 | 1442.90 | 712.81 | 730.09 | 0.00 | 0.00 |
September | 1644.96 | 460.13 | 1279.42 | 613.57 | 665.85 | 0.00 | 0.00 |
October | 1171.81 | 908.96 | 1076.33 | 615.20 | 461.13 | 0.00 | 0.00 |
November | 874.63 | 1058.51 | 883.19 | 536.20 | 346.98 | 0.00 | 0.00 |
December | 632.32 | 1271.94 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Annual Sum or Average | 1347.95 | 756.76 | 1174.16 | 585.60 | 588.56 | 0.00 | 0.00 |
Minimum of Months | 632.32 | 277.59 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Maximum of Months | 2306.09 | 1271.94 | 1696.77 | 816.38 | 898.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.98 | 1823.33 | 384.45 | 0.00 | 384.45 | 0.00 | 0.00 |
February | 109.28 | 1831.19 | 483.21 | 0.00 | 483.21 | 0.00 | 0.00 |
March | 337.01 | 1378.37 | 657.49 | 0.00 | 657.49 | 0.00 | 0.00 |
April | 497.29 | 1190.06 | 825.72 | 4.58 | 821.14 | 0.00 | 0.00 |
May | 1065.90 | 703.62 | 1127.98 | 37.29 | 1090.69 | 0.00 | 0.00 |
June | 1675.88 | 391.76 | 1236.91 | 137.13 | 1099.78 | 0.00 | 0.00 |
July | 1602.91 | 369.54 | 1169.78 | 75.72 | 1094.06 | 0.00 | 0.00 |
August | 1213.06 | 436.00 | 931.06 | 22.03 | 909.03 | 0.00 | 0.00 |
September | 889.21 | 699.82 | 782.09 | 0.18 | 781.90 | 0.00 | 0.00 |
October | 307.97 | 1452.79 | 560.16 | 0.00 | 560.16 | 0.00 | 0.00 |
November | 122.11 | 1710.54 | 425.23 | 0.00 | 425.23 | 0.00 | 0.00 |
December | 67.98 | 2083.06 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Annual Sum or Average | 667.50 | 1169.01 | 746.68 | 23.13 | 723.55 | 0.00 | 0.00 |
Minimum of Months | 67.98 | 369.54 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Maximum of Months | 1675.88 | 2083.06 | 1236.91 | 137.13 | 1099.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 726.66 | 1163.60 | 802.57 | 491.84 | 310.73 | 0.00 | 0.00 |
February | 1020.50 | 1193.69 | 1066.13 | 673.04 | 393.09 | 0.00 | 0.00 |
March | 1328.36 | 913.20 | 1286.78 | 750.57 | 536.22 | 0.00 | 0.00 |
April | 1333.04 | 802.90 | 1319.67 | 642.83 | 676.84 | 0.00 | 0.00 |
May | 1770.20 | 491.53 | 1542.67 | 644.38 | 898.29 | 0.00 | 0.00 |
June | 2542.38 | 275.50 | 1882.22 | 988.11 | 894.11 | 0.00 | 0.00 |
July | 2331.06 | 260.93 | 1711.08 | 814.77 | 896.31 | 0.00 | 0.00 |
August | 2330.95 | 307.51 | 1725.86 | 950.54 | 775.32 | 0.00 | 0.00 |
September | 1833.61 | 464.51 | 1436.01 | 780.08 | 655.93 | 0.00 | 0.00 |
October | 1092.51 | 970.37 | 1039.95 | 569.83 | 470.12 | 0.00 | 0.00 |
November | 761.78 | 1123.05 | 809.47 | 457.03 | 352.44 | 0.00 | 0.00 |
December | 603.19 | 1335.11 | 700.79 | 403.70 | 297.08 | 0.00 | 0.00 |
Annual Sum or Average | 1474.99 | 772.91 | 1277.74 | 680.22 | 597.51 | 0.00 | 0.00 |
Minimum of Months | 603.19 | 260.93 | 700.79 | 403.70 | 297.08 | 0.00 | 0.00 |
Maximum of Months | 2542.38 | 1335.11 | 1882.22 | 988.11 | 898.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4248.72 | 1756.49 | 3684.49 | 3030.88 | 653.60 | 0.00 | 0.00 |
February | 4056.12 | 1796.65 | 3534.11 | 2817.61 | 716.50 | 0.00 | 0.00 |
March | 3040.97 | 1407.07 | 2605.62 | 1714.34 | 891.28 | 0.00 | 0.00 |
April | 1812.34 | 1255.13 | 1687.60 | 678.59 | 1009.01 | 0.00 | 0.00 |
May | 1813.64 | 774.82 | 1546.50 | 283.46 | 1263.04 | 0.00 | 0.00 |
June | 2085.06 | 433.00 | 1425.83 | 260.60 | 1165.23 | 0.00 | 0.00 |
July | 2171.79 | 402.42 | 1484.25 | 265.79 | 1218.46 | 0.00 | 0.00 |
August | 2762.92 | 477.71 | 1889.75 | 789.98 | 1099.77 | 0.00 | 0.00 |
September | 3320.53 | 747.97 | 2431.34 | 1356.67 | 1074.67 | 0.00 | 0.00 |
October | 3535.85 | 1490.21 | 2907.16 | 2062.69 | 844.47 | 0.00 | 0.00 |
November | 4166.56 | 1703.29 | 3541.97 | 2823.46 | 718.51 | 0.00 | 0.00 |
December | 3830.45 | 1958.69 | 3387.05 | 2741.43 | 645.62 | 0.00 | 0.00 |
Annual Sum or Average | 3064.77 | 1180.21 | 2504.67 | 1561.69 | 942.98 | 0.00 | 0.00 |
Minimum of Months | 1812.34 | 402.42 | 1425.83 | 260.60 | 645.62 | 0.00 | 0.00 |
Maximum of Months | 4248.72 | 1958.69 | 3684.49 | 3030.88 | 1263.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 830.25 | 1195.96 | 853.76 | 540.99 | 312.77 | 0.00 | 0.00 |
February | 993.64 | 1212.76 | 1029.51 | 637.99 | 391.52 | 0.00 | 0.00 |
March | 1238.53 | 929.58 | 1205.49 | 665.09 | 540.40 | 0.00 | 0.00 |
April | 1114.81 | 819.91 | 1135.03 | 480.55 | 654.48 | 0.00 | 0.00 |
May | 1597.81 | 520.82 | 1387.29 | 489.07 | 898.22 | 0.00 | 0.00 |
June | 2323.71 | 310.04 | 1696.74 | 816.37 | 880.38 | 0.00 | 0.00 |
July | 1901.25 | 280.10 | 1382.45 | 506.36 | 876.08 | 0.00 | 0.00 |
August | 1950.28 | 323.26 | 1442.88 | 712.80 | 730.08 | 0.00 | 0.00 |
September | 1646.25 | 496.11 | 1279.40 | 613.56 | 665.85 | 0.00 | 0.00 |
October | 1166.23 | 990.16 | 1076.32 | 615.19 | 461.12 | 0.00 | 0.00 |
November | 869.79 | 1139.81 | 883.17 | 536.19 | 346.98 | 0.00 | 0.00 |
December | 632.14 | 1342.99 | 713.36 | 421.40 | 291.96 | 0.00 | 0.00 |
Annual Sum or Average | 1356.90 | 794.53 | 1174.15 | 585.59 | 588.56 | 0.00 | 0.00 |
Minimum of Months | 632.14 | 280.10 | 713.36 | 421.40 | 291.96 | 0.00 | 0.00 |
Maximum of Months | 2323.71 | 1342.99 | 1696.74 | 816.37 | 898.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 72.65 | 1883.37 | 384.46 | 0.00 | 384.46 | 0.00 | 0.00 |
February | 92.08 | 1895.10 | 483.22 | 0.00 | 483.22 | 0.00 | 0.00 |
March | 302.35 | 1443.52 | 657.51 | 0.00 | 657.51 | 0.00 | 0.00 |
April | 459.02 | 1244.98 | 825.73 | 4.58 | 821.15 | 0.00 | 0.00 |
May | 1018.06 | 744.67 | 1128.00 | 37.29 | 1090.72 | 0.00 | 0.00 |
June | 1646.92 | 410.58 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
July | 1576.36 | 388.80 | 1169.80 | 75.72 | 1094.08 | 0.00 | 0.00 |
August | 1198.12 | 448.01 | 931.07 | 22.03 | 909.05 | 0.00 | 0.00 |
September | 883.12 | 698.77 | 782.10 | 0.18 | 781.92 | 0.00 | 0.00 |
October | 302.45 | 1445.99 | 560.17 | 0.00 | 560.17 | 0.00 | 0.00 |
November | 117.15 | 1715.67 | 425.24 | 0.00 | 425.24 | 0.00 | 0.00 |
December | 64.10 | 2093.73 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Annual Sum or Average | 647.46 | 1197.41 | 746.69 | 23.13 | 723.56 | 0.00 | 0.00 |
Minimum of Months | 64.10 | 388.80 | 359.71 | 0.00 | 359.71 | 0.00 | 0.00 |
Maximum of Months | 1646.92 | 2093.73 | 1236.93 | 137.13 | 1099.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 711.62 | 1179.89 | 802.58 | 491.85 | 310.74 | 0.00 | 0.00 |
February | 1001.39 | 1211.40 | 1066.14 | 673.05 | 393.09 | 0.00 | 0.00 |
March | 1304.52 | 927.06 | 1286.81 | 750.58 | 536.22 | 0.00 | 0.00 |
April | 1309.91 | 810.84 | 1319.69 | 642.84 | 676.85 | 0.00 | 0.00 |
May | 1743.24 | 502.42 | 1542.70 | 644.39 | 898.31 | 0.00 | 0.00 |
June | 2524.70 | 276.35 | 1882.25 | 988.13 | 894.12 | 0.00 | 0.00 |
July | 2314.89 | 261.86 | 1711.11 | 814.79 | 896.32 | 0.00 | 0.00 |
August | 2320.35 | 300.64 | 1725.89 | 950.56 | 775.33 | 0.00 | 0.00 |
September | 1827.72 | 448.20 | 1436.03 | 780.09 | 655.94 | 0.00 | 0.00 |
October | 1086.58 | 942.77 | 1039.97 | 569.84 | 470.13 | 0.00 | 0.00 |
November | 755.47 | 1104.98 | 809.48 | 457.04 | 352.44 | 0.00 | 0.00 |
December | 595.61 | 1324.77 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Annual Sum or Average | 1460.15 | 771.92 | 1277.76 | 680.24 | 597.52 | 0.00 | 0.00 |
Minimum of Months | 595.61 | 261.86 | 700.80 | 403.71 | 297.09 | 0.00 | 0.00 |
Maximum of Months | 2524.70 | 1324.77 | 1882.25 | 988.13 | 898.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4218.00 | 1713.01 | 3684.63 | 3031.01 | 653.63 | 0.00 | 0.00 |
February | 4010.93 | 1774.49 | 3534.25 | 2817.72 | 716.52 | 0.00 | 0.00 |
March | 2997.22 | 1417.34 | 2605.72 | 1714.42 | 891.30 | 0.00 | 0.00 |
April | 1769.38 | 1282.01 | 1687.66 | 678.61 | 1009.04 | 0.00 | 0.00 |
May | 1763.70 | 817.42 | 1546.55 | 283.47 | 1263.08 | 0.00 | 0.00 |
June | 2057.74 | 451.31 | 1425.87 | 260.61 | 1165.26 | 0.00 | 0.00 |
July | 2147.04 | 418.13 | 1484.30 | 265.80 | 1218.50 | 0.00 | 0.00 |
August | 2747.68 | 473.44 | 1889.81 | 790.01 | 1099.80 | 0.00 | 0.00 |
September | 3311.39 | 716.08 | 2431.43 | 1356.72 | 1074.70 | 0.00 | 0.00 |
October | 3522.38 | 1430.84 | 2907.28 | 2062.78 | 844.50 | 0.00 | 0.00 |
November | 4142.10 | 1638.52 | 3542.11 | 2823.58 | 718.53 | 0.00 | 0.00 |
December | 3800.40 | 1901.63 | 3387.18 | 2741.54 | 645.64 | 0.00 | 0.00 |
Annual Sum or Average | 3035.11 | 1166.16 | 2504.77 | 1561.76 | 943.01 | 0.00 | 0.00 |
Minimum of Months | 1763.70 | 418.13 | 1425.87 | 260.61 | 645.64 | 0.00 | 0.00 |
Maximum of Months | 4218.00 | 1901.63 | 3684.63 | 3031.01 | 1263.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 816.18 | 1209.05 | 853.77 | 540.99 | 312.77 | 0.00 | 0.00 |
February | 975.80 | 1228.28 | 1029.52 | 638.00 | 391.52 | 0.00 | 0.00 |
March | 1215.80 | 947.42 | 1205.51 | 665.11 | 540.40 | 0.00 | 0.00 |
April | 1093.44 | 832.61 | 1135.04 | 480.56 | 654.48 | 0.00 | 0.00 |
May | 1572.91 | 534.77 | 1387.31 | 489.08 | 898.23 | 0.00 | 0.00 |
June | 2310.15 | 310.76 | 1696.77 | 816.38 | 880.39 | 0.00 | 0.00 |
July | 1887.62 | 284.39 | 1382.46 | 506.37 | 876.09 | 0.00 | 0.00 |
August | 1942.48 | 318.64 | 1442.90 | 712.81 | 730.09 | 0.00 | 0.00 |
September | 1643.51 | 479.86 | 1279.42 | 613.57 | 665.85 | 0.00 | 0.00 |
October | 1163.99 | 961.16 | 1076.33 | 615.20 | 461.13 | 0.00 | 0.00 |
November | 865.24 | 1119.02 | 883.19 | 536.20 | 346.98 | 0.00 | 0.00 |
December | 625.41 | 1330.66 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Annual Sum or Average | 1344.24 | 794.05 | 1174.16 | 585.60 | 588.56 | 0.00 | 0.00 |
Minimum of Months | 625.41 | 284.39 | 713.37 | 421.41 | 291.96 | 0.00 | 0.00 |
Maximum of Months | 2310.15 | 1330.66 | 1696.77 | 816.38 | 898.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219136E+09 | 0.478052E+10 | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.00 | 0.00 |
February | 0.241565E+09 | 0.438629E+10 | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.00 | 0.00 |
March | 0.833762E+09 | 0.368059E+10 | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.00 | 0.00 |
April | 0.121564E+10 | 0.303328E+10 | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.00 | 0.00 |
May | 0.275227E+10 | 0.192113E+10 | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.00 | 0.00 |
June | 0.426039E+10 | 0.104107E+10 | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.00 | 0.00 |
July | 0.421057E+10 | 0.102091E+10 | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.00 | 0.00 |
August | 0.320384E+10 | 0.116469E+10 | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.00 | 0.00 |
September | 0.229925E+10 | 0.173463E+10 | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.00 | 0.00 |
October | 0.844518E+09 | 0.365589E+10 | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.00 | 0.00 |
November | 0.334417E+09 | 0.420178E+10 | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.00 | 0.00 |
December | 0.188721E+09 | 0.536527E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206041E+11 | 0.359861E+11 | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.00 | 0.00 |
Minimum of Months | 0.188721E+09 | 0.102091E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.426039E+10 | 0.536527E+10 | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194734E+10 | 0.299914E+10 | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.00 | 0.00 |
February | 0.244932E+10 | 0.280757E+10 | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.00 | 0.00 |
March | 0.351826E+10 | 0.237034E+10 | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.00 | 0.00 |
April | 0.341890E+10 | 0.198020E+10 | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.00 | 0.00 |
May | 0.468849E+10 | 0.130033E+10 | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.00 | 0.00 |
June | 0.654329E+10 | 0.700406E+09 | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.00 | 0.00 |
July | 0.619797E+10 | 0.686752E+09 | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.00 | 0.00 |
August | 0.621657E+10 | 0.781839E+09 | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.00 | 0.00 |
September | 0.474890E+10 | 0.111746E+10 | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.00 | 0.00 |
October | 0.293593E+10 | 0.239352E+10 | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.00 | 0.00 |
November | 0.199547E+10 | 0.271168E+10 | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.00 | 0.00 |
December | 0.162807E+10 | 0.339515E+10 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.462885E+11 | 0.232444E+11 | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.162807E+10 | 0.686752E+09 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654329E+10 | 0.339515E+10 | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113531E+11 | 0.436599E+10 | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.00 | 0.00 |
February | 0.973386E+10 | 0.410893E+10 | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.00 | 0.00 |
March | 0.805003E+10 | 0.361975E+10 | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.00 | 0.00 |
April | 0.460870E+10 | 0.312876E+10 | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.00 | 0.00 |
May | 0.473669E+10 | 0.210608E+10 | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.00 | 0.00 |
June | 0.532018E+10 | 0.113896E+10 | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.00 | 0.00 |
July | 0.573502E+10 | 0.109337E+10 | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.00 | 0.00 |
August | 0.734826E+10 | 0.122929E+10 | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.00 | 0.00 |
September | 0.858472E+10 | 0.178294E+10 | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.00 | 0.00 |
October | 0.946165E+10 | 0.363583E+10 | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.00 | 0.00 |
November | 0.107790E+11 | 0.403366E+10 | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.00 | 0.00 |
December | 0.102260E+11 | 0.486731E+10 | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.959373E+11 | 0.351109E+11 | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.00 | 0.00 |
Minimum of Months | 0.460870E+10 | 0.109337E+10 | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113531E+11 | 0.486731E+10 | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220980E+10 | 0.307078E+10 | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.00 | 0.00 |
February | 0.237541E+10 | 0.284059E+10 | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.00 | 0.00 |
March | 0.327046E+10 | 0.241498E+10 | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.00 | 0.00 |
April | 0.285079E+10 | 0.202934E+10 | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.00 | 0.00 |
May | 0.422136E+10 | 0.137688E+10 | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.00 | 0.00 |
June | 0.597739E+10 | 0.784051E+09 | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.00 | 0.00 |
July | 0.504483E+10 | 0.743488E+09 | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.00 | 0.00 |
August | 0.519589E+10 | 0.827345E+09 | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.00 | 0.00 |
September | 0.426374E+10 | 0.119266E+10 | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.00 | 0.00 |
October | 0.313857E+10 | 0.243456E+10 | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.00 | 0.00 |
November | 0.226705E+10 | 0.274366E+10 | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.00 | 0.00 |
December | 0.169361E+10 | 0.340676E+10 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.425089E+11 | 0.238651E+11 | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169361E+10 | 0.743488E+09 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Maximum of Months | 0.597739E+10 | 0.340676E+10 | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.224941E+09 | 0.488362E+10 | 0.102972E+10 | 0.00 | 0.102972E+10 | 0.00 | 0.00 |
February | 0.264359E+09 | 0.443002E+10 | 0.116899E+10 | 0.00 | 0.116899E+10 | 0.00 | 0.00 |
March | 0.902645E+09 | 0.369182E+10 | 0.176103E+10 | 0.00 | 0.176103E+10 | 0.00 | 0.00 |
April | 0.128897E+10 | 0.308464E+10 | 0.214026E+10 | 11873135.46 | 0.212839E+10 | 0.00 | 0.00 |
May | 0.285489E+10 | 0.188459E+10 | 0.302118E+10 | 99867234.64 | 0.292131E+10 | 0.00 | 0.00 |
June | 0.434389E+10 | 0.101544E+10 | 0.320607E+10 | 0.355441E+09 | 0.285063E+10 | 0.00 | 0.00 |
July | 0.429324E+10 | 0.989780E+09 | 0.313313E+10 | 0.202812E+09 | 0.293032E+10 | 0.00 | 0.00 |
August | 0.324906E+10 | 0.116777E+10 | 0.249374E+10 | 58992918.24 | 0.243475E+10 | 0.00 | 0.00 |
September | 0.230484E+10 | 0.181392E+10 | 0.202717E+10 | 476141.58 | 0.202669E+10 | 0.00 | 0.00 |
October | 0.824879E+09 | 0.389116E+10 | 0.150034E+10 | 0.00 | 0.150034E+10 | 0.00 | 0.00 |
November | 0.316507E+09 | 0.443371E+10 | 0.110221E+10 | 0.00 | 0.110221E+10 | 0.00 | 0.00 |
December | 0.182065E+09 | 0.557928E+10 | 0.963435E+09 | 0.00 | 0.963435E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.210503E+11 | 0.368657E+11 | 0.235473E+11 | 0.729462E+09 | 0.228178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.182065E+09 | 0.989780E+09 | 0.963435E+09 | 0.00 | 0.963435E+09 | 0.00 | 0.00 |
Maximum of Months | 0.434389E+10 | 0.557928E+10 | 0.320607E+10 | 0.355441E+09 | 0.293032E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194629E+10 | 0.311657E+10 | 0.214960E+10 | 0.131734E+10 | 0.832266E+09 | 0.00 | 0.00 |
February | 0.246879E+10 | 0.288779E+10 | 0.257917E+10 | 0.162822E+10 | 0.950956E+09 | 0.00 | 0.00 |
March | 0.355789E+10 | 0.244591E+10 | 0.344652E+10 | 0.201032E+10 | 0.143620E+10 | 0.00 | 0.00 |
April | 0.345524E+10 | 0.208113E+10 | 0.342058E+10 | 0.166622E+10 | 0.175436E+10 | 0.00 | 0.00 |
May | 0.474131E+10 | 0.131652E+10 | 0.413189E+10 | 0.172590E+10 | 0.240599E+10 | 0.00 | 0.00 |
June | 0.658985E+10 | 0.714088E+09 | 0.487871E+10 | 0.256118E+10 | 0.231752E+10 | 0.00 | 0.00 |
July | 0.624351E+10 | 0.698885E+09 | 0.458297E+10 | 0.218229E+10 | 0.240068E+10 | 0.00 | 0.00 |
August | 0.624321E+10 | 0.823637E+09 | 0.462255E+10 | 0.254593E+10 | 0.207663E+10 | 0.00 | 0.00 |
September | 0.475271E+10 | 0.120401E+10 | 0.372213E+10 | 0.202196E+10 | 0.170017E+10 | 0.00 | 0.00 |
October | 0.292619E+10 | 0.259905E+10 | 0.278542E+10 | 0.152624E+10 | 0.125917E+10 | 0.00 | 0.00 |
November | 0.197454E+10 | 0.291094E+10 | 0.209815E+10 | 0.118463E+10 | 0.913518E+09 | 0.00 | 0.00 |
December | 0.161559E+10 | 0.357596E+10 | 0.187698E+10 | 0.108127E+10 | 0.795712E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.465151E+11 | 0.243745E+11 | 0.402947E+11 | 0.214515E+11 | 0.188432E+11 | 0.00 | 0.00 |
Minimum of Months | 0.161559E+10 | 0.698885E+09 | 0.187698E+10 | 0.108127E+10 | 0.795712E+09 | 0.00 | 0.00 |
Maximum of Months | 0.658985E+10 | 0.357596E+10 | 0.487871E+10 | 0.256118E+10 | 0.240599E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113798E+11 | 0.470459E+10 | 0.986853E+10 | 0.811791E+10 | 0.175061E+10 | 0.00 | 0.00 |
February | 0.981256E+10 | 0.434646E+10 | 0.854971E+10 | 0.681636E+10 | 0.173336E+10 | 0.00 | 0.00 |
March | 0.814494E+10 | 0.376869E+10 | 0.697889E+10 | 0.459170E+10 | 0.238719E+10 | 0.00 | 0.00 |
April | 0.469758E+10 | 0.325329E+10 | 0.437425E+10 | 0.175889E+10 | 0.261536E+10 | 0.00 | 0.00 |
May | 0.485766E+10 | 0.207528E+10 | 0.414215E+10 | 0.759219E+09 | 0.338293E+10 | 0.00 | 0.00 |
June | 0.540446E+10 | 0.112233E+10 | 0.369574E+10 | 0.675470E+09 | 0.302027E+10 | 0.00 | 0.00 |
July | 0.581692E+10 | 0.107783E+10 | 0.397541E+10 | 0.711879E+09 | 0.326354E+10 | 0.00 | 0.00 |
August | 0.740021E+10 | 0.127949E+10 | 0.506150E+10 | 0.211588E+10 | 0.294562E+10 | 0.00 | 0.00 |
September | 0.860682E+10 | 0.193873E+10 | 0.630203E+10 | 0.351648E+10 | 0.278555E+10 | 0.00 | 0.00 |
October | 0.947041E+10 | 0.399137E+10 | 0.778655E+10 | 0.552472E+10 | 0.226183E+10 | 0.00 | 0.00 |
November | 0.107997E+11 | 0.441493E+10 | 0.918079E+10 | 0.731841E+10 | 0.186238E+10 | 0.00 | 0.00 |
December | 0.102595E+11 | 0.524615E+10 | 0.907187E+10 | 0.734263E+10 | 0.172923E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.966506E+11 | 0.372192E+11 | 0.789874E+11 | 0.492495E+11 | 0.297379E+11 | 0.00 | 0.00 |
Minimum of Months | 0.469758E+10 | 0.107783E+10 | 0.369574E+10 | 0.675470E+09 | 0.172923E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113798E+11 | 0.524615E+10 | 0.986853E+10 | 0.811791E+10 | 0.338293E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.222375E+10 | 0.320326E+10 | 0.228670E+10 | 0.144898E+10 | 0.837728E+09 | 0.00 | 0.00 |
February | 0.240382E+10 | 0.293390E+10 | 0.249059E+10 | 0.154343E+10 | 0.947167E+09 | 0.00 | 0.00 |
March | 0.331728E+10 | 0.248979E+10 | 0.322879E+10 | 0.178139E+10 | 0.144740E+10 | 0.00 | 0.00 |
April | 0.288960E+10 | 0.212522E+10 | 0.294199E+10 | 0.124558E+10 | 0.169640E+10 | 0.00 | 0.00 |
May | 0.427959E+10 | 0.139497E+10 | 0.371573E+10 | 0.130993E+10 | 0.240580E+10 | 0.00 | 0.00 |
June | 0.602306E+10 | 0.803628E+09 | 0.439796E+10 | 0.211602E+10 | 0.228194E+10 | 0.00 | 0.00 |
July | 0.509229E+10 | 0.750218E+09 | 0.370274E+10 | 0.135624E+10 | 0.234650E+10 | 0.00 | 0.00 |
August | 0.522364E+10 | 0.865818E+09 | 0.386461E+10 | 0.190916E+10 | 0.195545E+10 | 0.00 | 0.00 |
September | 0.426707E+10 | 0.128591E+10 | 0.331621E+10 | 0.159034E+10 | 0.172587E+10 | 0.00 | 0.00 |
October | 0.312363E+10 | 0.265205E+10 | 0.288280E+10 | 0.164773E+10 | 0.123507E+10 | 0.00 | 0.00 |
November | 0.225450E+10 | 0.295438E+10 | 0.228919E+10 | 0.138982E+10 | 0.899371E+09 | 0.00 | 0.00 |
December | 0.169312E+10 | 0.359706E+10 | 0.191067E+10 | 0.112868E+10 | 0.781990E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427913E+11 | 0.250562E+11 | 0.370280E+11 | 0.184673E+11 | 0.185607E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169312E+10 | 0.750218E+09 | 0.191067E+10 | 0.112868E+10 | 0.781990E+09 | 0.00 | 0.00 |
Maximum of Months | 0.602306E+10 | 0.359706E+10 | 0.439796E+10 | 0.211602E+10 | 0.240580E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194598E+09 | 0.504442E+10 | 0.102974E+10 | 0.00 | 0.102974E+10 | 0.00 | 0.00 |
February | 0.222751E+09 | 0.458463E+10 | 0.116901E+10 | 0.00 | 0.116901E+10 | 0.00 | 0.00 |
March | 0.809815E+09 | 0.386631E+10 | 0.176107E+10 | 0.00 | 0.176107E+10 | 0.00 | 0.00 |
April | 0.118979E+10 | 0.322699E+10 | 0.214030E+10 | 11873484.46 | 0.212843E+10 | 0.00 | 0.00 |
May | 0.272677E+10 | 0.199453E+10 | 0.302124E+10 | 99870170.09 | 0.292137E+10 | 0.00 | 0.00 |
June | 0.426883E+10 | 0.106424E+10 | 0.320613E+10 | 0.355452E+09 | 0.285068E+10 | 0.00 | 0.00 |
July | 0.422213E+10 | 0.104136E+10 | 0.313320E+10 | 0.202818E+09 | 0.293038E+10 | 0.00 | 0.00 |
August | 0.320904E+10 | 0.119996E+10 | 0.249379E+10 | 58994652.25 | 0.243479E+10 | 0.00 | 0.00 |
September | 0.228904E+10 | 0.181122E+10 | 0.202721E+10 | 476155.58 | 0.202673E+10 | 0.00 | 0.00 |
October | 0.810086E+09 | 0.387293E+10 | 0.150037E+10 | 0.00 | 0.150037E+10 | 0.00 | 0.00 |
November | 0.303645E+09 | 0.444703E+10 | 0.110223E+10 | 0.00 | 0.110223E+10 | 0.00 | 0.00 |
December | 0.171699E+09 | 0.560783E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.204182E+11 | 0.377614E+11 | 0.235478E+11 | 0.729484E+09 | 0.228183E+11 | 0.00 | 0.00 |
Minimum of Months | 0.171699E+09 | 0.104136E+10 | 0.963454E+09 | 0.00 | 0.963454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.426883E+10 | 0.560783E+10 | 0.320613E+10 | 0.355452E+09 | 0.293038E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.190600E+10 | 0.316022E+10 | 0.214964E+10 | 0.131736E+10 | 0.832275E+09 | 0.00 | 0.00 |
February | 0.242256E+10 | 0.293061E+10 | 0.257921E+10 | 0.162825E+10 | 0.950966E+09 | 0.00 | 0.00 |
March | 0.349404E+10 | 0.248304E+10 | 0.344658E+10 | 0.201036E+10 | 0.143622E+10 | 0.00 | 0.00 |
April | 0.339529E+10 | 0.210170E+10 | 0.342063E+10 | 0.166625E+10 | 0.175438E+10 | 0.00 | 0.00 |
May | 0.466909E+10 | 0.134569E+10 | 0.413195E+10 | 0.172593E+10 | 0.240602E+10 | 0.00 | 0.00 |
June | 0.654402E+10 | 0.716310E+09 | 0.487878E+10 | 0.256123E+10 | 0.231755E+10 | 0.00 | 0.00 |
July | 0.620021E+10 | 0.701361E+09 | 0.458304E+10 | 0.218233E+10 | 0.240071E+10 | 0.00 | 0.00 |
August | 0.621482E+10 | 0.805234E+09 | 0.462263E+10 | 0.254598E+10 | 0.207665E+10 | 0.00 | 0.00 |
September | 0.473745E+10 | 0.116174E+10 | 0.372219E+10 | 0.202200E+10 | 0.170019E+10 | 0.00 | 0.00 |
October | 0.291029E+10 | 0.252511E+10 | 0.278546E+10 | 0.152627E+10 | 0.125919E+10 | 0.00 | 0.00 |
November | 0.195817E+10 | 0.286411E+10 | 0.209818E+10 | 0.118466E+10 | 0.913528E+09 | 0.00 | 0.00 |
December | 0.159528E+10 | 0.354825E+10 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.460472E+11 | 0.243434E+11 | 0.402953E+11 | 0.214519E+11 | 0.188434E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159528E+10 | 0.701361E+09 | 0.187702E+10 | 0.108129E+10 | 0.795721E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654402E+10 | 0.354825E+10 | 0.487878E+10 | 0.256123E+10 | 0.240602E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112975E+11 | 0.458812E+10 | 0.986892E+10 | 0.811825E+10 | 0.175067E+10 | 0.00 | 0.00 |
February | 0.970324E+10 | 0.429284E+10 | 0.855005E+10 | 0.681664E+10 | 0.173341E+10 | 0.00 | 0.00 |
March | 0.802775E+10 | 0.379620E+10 | 0.697916E+10 | 0.459189E+10 | 0.238727E+10 | 0.00 | 0.00 |
April | 0.458622E+10 | 0.332296E+10 | 0.437441E+10 | 0.175897E+10 | 0.261544E+10 | 0.00 | 0.00 |
May | 0.472389E+10 | 0.218937E+10 | 0.414228E+10 | 0.759251E+09 | 0.338303E+10 | 0.00 | 0.00 |
June | 0.533367E+10 | 0.116980E+10 | 0.369585E+10 | 0.675498E+09 | 0.302035E+10 | 0.00 | 0.00 |
July | 0.575063E+10 | 0.111993E+10 | 0.397554E+10 | 0.711908E+09 | 0.326363E+10 | 0.00 | 0.00 |
August | 0.735939E+10 | 0.126806E+10 | 0.506167E+10 | 0.211597E+10 | 0.294570E+10 | 0.00 | 0.00 |
September | 0.858313E+10 | 0.185609E+10 | 0.630226E+10 | 0.351663E+10 | 0.278563E+10 | 0.00 | 0.00 |
October | 0.943435E+10 | 0.383237E+10 | 0.778685E+10 | 0.552495E+10 | 0.226190E+10 | 0.00 | 0.00 |
November | 0.107363E+11 | 0.424704E+10 | 0.918115E+10 | 0.731871E+10 | 0.186244E+10 | 0.00 | 0.00 |
December | 0.101790E+11 | 0.509333E+10 | 0.907223E+10 | 0.734294E+10 | 0.172929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.957151E+11 | 0.367761E+11 | 0.789904E+11 | 0.492516E+11 | 0.297388E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458622E+10 | 0.111993E+10 | 0.369585E+10 | 0.675498E+09 | 0.172929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112975E+11 | 0.509333E+10 | 0.986892E+10 | 0.811825E+10 | 0.338303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218605E+10 | 0.323833E+10 | 0.228674E+10 | 0.144900E+10 | 0.837735E+09 | 0.00 | 0.00 |
February | 0.236064E+10 | 0.297145E+10 | 0.249063E+10 | 0.154345E+10 | 0.947175E+09 | 0.00 | 0.00 |
March | 0.325640E+10 | 0.253757E+10 | 0.322883E+10 | 0.178142E+10 | 0.144741E+10 | 0.00 | 0.00 |
April | 0.283421E+10 | 0.215813E+10 | 0.294203E+10 | 0.124560E+10 | 0.169642E+10 | 0.00 | 0.00 |
May | 0.421287E+10 | 0.143232E+10 | 0.371577E+10 | 0.130995E+10 | 0.240582E+10 | 0.00 | 0.00 |
June | 0.598790E+10 | 0.805502E+09 | 0.439802E+10 | 0.211606E+10 | 0.228196E+10 | 0.00 | 0.00 |
July | 0.505580E+10 | 0.761711E+09 | 0.370279E+10 | 0.135626E+10 | 0.234652E+10 | 0.00 | 0.00 |
August | 0.520275E+10 | 0.853442E+09 | 0.386466E+10 | 0.190920E+10 | 0.195546E+10 | 0.00 | 0.00 |
September | 0.425997E+10 | 0.124380E+10 | 0.331625E+10 | 0.159036E+10 | 0.172589E+10 | 0.00 | 0.00 |
October | 0.311764E+10 | 0.257436E+10 | 0.288284E+10 | 0.164776E+10 | 0.123508E+10 | 0.00 | 0.00 |
November | 0.224270E+10 | 0.290050E+10 | 0.228922E+10 | 0.138984E+10 | 0.899379E+09 | 0.00 | 0.00 |
December | 0.167510E+10 | 0.356403E+10 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423920E+11 | 0.250411E+11 | 0.370285E+11 | 0.184676E+11 | 0.185609E+11 | 0.00 | 0.00 |
Minimum of Months | 0.167510E+10 | 0.761711E+09 | 0.191070E+10 | 0.112870E+10 | 0.781997E+09 | 0.00 | 0.00 |
Maximum of Months | 0.598790E+10 | 0.356403E+10 | 0.439802E+10 | 0.211606E+10 | 0.240582E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.548448E+10 | -0.476676E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717724773.7 | 58.98 | 0.00 | 0.00 |
February | 0.503490E+10 | -0.438575E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -649149803.7 | 58.99 | 0.00 | 0.00 |
March | 0.582658E+10 | -0.511525E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -711330285.7 | 58.98 | 0.00 | 0.00 |
April | 0.510678E+10 | -0.442205E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -684725597.8 | 58.98 | 0.00 | 0.00 |
May | 0.517664E+10 | -0.448184E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694803234.1 | 58.98 | 0.00 | 0.00 |
June | 0.485806E+10 | -0.418822E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669840252.4 | 58.98 | 0.00 | 0.00 |
July | 0.445604E+10 | -0.376618E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689856852.9 | 58.98 | 0.00 | 0.00 |
August | 0.478950E+10 | -0.409860E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690901888.6 | 58.98 | 0.00 | 0.00 |
September | 0.443006E+10 | -0.376169E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668368241.9 | 58.98 | 0.00 | 0.00 |
October | 0.477365E+10 | -0.407613E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -697521612.1 | 58.98 | 0.00 | 0.00 |
November | 0.494169E+10 | -0.425853E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -683164110.4 | 58.99 | 0.00 | 0.00 |
December | 0.517954E+10 | -0.445680E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -722735572.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.600579E+11 | -0.517778E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.828012E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.443006E+10 | -0.511525E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -722735572.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.582658E+10 | -0.376169E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -649149803.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10608.03 | 39.55 | 274.17 | 267.83 | 5719.64 | 35.01 | 235.50 | 259.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 14167.50 | 39.31 | 241.00 | 264.33 | 2392.44 | 24.90 | 117.50 | 243.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2839.00 | 19.18 | 18.33 | 327.33 | 1624.12 | 21.08 | 131.00 | 293.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2130.57 | 18.95 | 8.33 | 340.67 | 1246.71 | 21.17 | 163.00 | 303.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1901.51 | 19.05 | 0.83 | 393.00 | 1053.77 | 21.25 | 261.67 | 357.17 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 1543.19 | 18.56 | 0.00 | 392.33 | 927.84 | 20.84 | 187.17 | 352.50 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:10 | 1732.54 | 18.69 | 2.83 | 396.00 | 985.19 | 20.91 | 236.67 | 357.50 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1864.30 | 18.43 | 4.67 | 371.33 | 1143.72 | 20.67 | 171.83 | 337.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 3030.28 | 20.24 | 39.50 | 333.00 | 1425.63 | 21.08 | 169.33 | 305.00 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13789.60 | 36.66 | 239.83 | 300.50 | 2004.95 | 21.67 | 123.83 | 277.33 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 12101.16 | 39.11 | 250.50 | 264.67 | 3682.56 | 29.94 | 180.00 | 243.17 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9938.22 | 39.96 | 250.67 | 258.50 | 8039.11 | 40.64 | 248.33 | 248.00 |
Annual Sum or Average | 3902.00 | 0.50 | 5411.17 | 25.59 | 1330.67 | 3909.50 | 2235.50 | 24.13 | 2225.83 | 3577.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1543.19 | 18.43 | 0.00 | 258.50 | 927.84 | 20.67 | 117.50 | 243.17 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 14167.50 | 39.96 | 274.17 | 396.00 | 8039.11 | 40.64 | 261.67 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2470.79 | 21.00 | 82.67 | 235.00 | 1495.14 | 23.48 | 97.00 | 205.83 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3941.77 | 23.33 | 84.33 | 250.83 | 2348.44 | 23.86 | 73.00 | 206.17 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3771.68 | 22.39 | 83.50 | 319.83 | 2112.10 | 23.24 | 77.33 | 281.17 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 4103.61 | 21.88 | 84.83 | 341.83 | 1828.33 | 22.74 | 58.67 | 303.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3292.41 | 21.79 | 111.67 | 400.67 | 1795.85 | 23.03 | 88.00 | 367.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3919.40 | 21.43 | 109.00 | 404.67 | 2258.66 | 23.52 | 92.17 | 376.17 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3526.81 | 21.64 | 116.33 | 406.67 | 1909.60 | 22.72 | 87.83 | 374.83 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:40 | 4852.18 | 22.98 | 131.00 | 373.50 | 1938.65 | 22.15 | 70.00 | 340.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 3960.04 | 22.54 | 108.33 | 332.33 | 1557.02 | 21.78 | 67.17 | 308.83 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3651.12 | 22.94 | 79.83 | 290.33 | 2053.80 | 23.69 | 68.00 | 250.00 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2486.69 | 21.33 | 70.50 | 242.83 | 1298.53 | 21.79 | 81.00 | 201.67 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:40 | 2621.82 | 23.62 | 91.83 | 233.00 | 1547.91 | 24.16 | 97.17 | 195.17 |
Annual Sum or Average | 3902.00 | 0.50 | 3612.72 | 22.18 | 1153.83 | 3831.50 | 1859.65 | 22.96 | 957.33 | 3410.67 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2470.79 | 21.00 | 70.50 | 233.00 | 1298.53 | 21.78 | 58.67 | 195.17 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 4852.18 | 23.62 | 131.00 | 406.67 | 2348.44 | 24.16 | 97.17 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.55 | 0.48 | 01-JAN-08:00 | 561.88 | 14.46 | 0.00 | 219.17 | 375.14 | 17.24 | 0.00 | 156.50 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 669.75 | 16.01 | 0.00 | 241.33 | 462.42 | 18.71 | 1.50 | 176.17 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:19 | 869.31 | 17.35 | 0.00 | 315.67 | 564.64 | 19.73 | 10.83 | 261.33 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1160.94 | 18.58 | 0.00 | 345.67 | 690.29 | 20.73 | 78.33 | 302.17 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1410.42 | 19.27 | 4.50 | 408.67 | 785.99 | 21.47 | 204.00 | 381.00 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1542.23 | 21.90 | 76.17 | 418.17 | 863.67 | 24.04 | 255.17 | 404.83 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1453.34 | 20.28 | 35.67 | 420.00 | 805.96 | 22.46 | 236.83 | 393.50 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1130.92 | 18.46 | 2.83 | 380.00 | 701.28 | 20.64 | 113.83 | 347.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 952.33 | 17.85 | 0.00 | 330.83 | 602.78 | 20.13 | 42.83 | 290.33 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 812.11 | 17.11 | 0.00 | 281.33 | 547.99 | 19.64 | 1.33 | 218.67 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:50 | 630.78 | 15.48 | 0.00 | 229.50 | 429.70 | 18.22 | 0.33 | 168.67 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-08:30 | 580.44 | 15.08 | 0.00 | 217.83 | 385.47 | 17.88 | 0.00 | 151.17 |
Annual Sum or Average | 3902.00 | 0.51 | 1047.62 | 18.05 | 119.17 | 3808.17 | 632.52 | 20.42 | 945.00 | 3251.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 561.88 | 14.46 | 0.00 | 217.83 | 375.14 | 17.24 | 0.00 | 151.17 | |
Maximum of Months | 430.33 | 0.55 | 0.48 | 1542.23 | 21.90 | 76.17 | 420.00 | 863.67 | 24.04 | 255.17 | 404.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.51 | 0.48 | 01-JAN-08:00 | 2956.45 | 24.16 | 108.67 | 252.17 | 1770.26 | 24.45 | 104.33 | 219.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 3024.31 | 21.70 | 68.50 | 255.83 | 1733.33 | 23.94 | 73.67 | 214.17 |
March | 296.17 | 0.49 | 0.48 | 01-MAR-07:30 | 3562.68 | 22.98 | 99.33 | 328.50 | 2025.92 | 23.79 | 91.17 | 294.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3330.95 | 21.52 | 85.33 | 347.50 | 1513.87 | 21.47 | 39.33 | 312.50 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2880.74 | 18.33 | 53.17 | 398.50 | 1519.72 | 19.14 | 6.50 | 367.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:49 | 3421.95 | 15.28 | 1.83 | 403.33 | 1934.97 | 18.78 | 1.00 | 378.33 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 2885.83 | 17.92 | 54.83 | 405.33 | 1579.80 | 18.93 | 7.50 | 376.17 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 2994.80 | 17.88 | 53.67 | 380.67 | 1706.67 | 18.89 | 8.33 | 357.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:40 | 3332.56 | 22.34 | 109.83 | 334.50 | 1810.81 | 23.37 | 98.67 | 310.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4290.26 | 23.95 | 93.83 | 295.83 | 1695.50 | 23.65 | 66.50 | 260.00 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 2991.04 | 24.46 | 96.50 | 252.67 | 1714.95 | 25.00 | 99.83 | 214.50 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2355.03 | 22.36 | 80.67 | 240.67 | 1422.42 | 24.74 | 93.83 | 212.83 |
Annual Sum or Average | 3902.00 | 0.50 | 3161.00 | 20.54 | 906.17 | 3895.50 | 1704.14 | 21.70 | 690.67 | 3517.00 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2355.03 | 15.28 | 1.83 | 240.67 | 1422.42 | 18.78 | 1.00 | 212.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 4290.26 | 24.46 | 109.83 | 405.33 | 2025.92 | 25.00 | 104.33 | 378.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10373.60 | 39.34 | 274.17 | 267.83 | 5523.90 | 33.85 | 205.33 | 259.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 13943.54 | 39.05 | 241.00 | 263.00 | 2197.93 | 22.23 | 69.67 | 240.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2723.10 | 15.35 | 10.33 | 327.83 | 1497.05 | 18.54 | 19.00 | 289.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 2026.45 | 15.27 | 0.00 | 339.00 | 1171.96 | 18.80 | 16.83 | 298.67 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1823.21 | 15.36 | 0.00 | 391.50 | 1003.21 | 18.85 | 3.50 | 354.17 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:49 | 1481.48 | 15.08 | 0.00 | 390.00 | 889.14 | 18.67 | 0.00 | 348.83 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:10 | 1662.14 | 15.06 | 0.00 | 394.17 | 940.20 | 18.57 | 4.33 | 354.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1773.32 | 14.85 | 0.00 | 369.00 | 1078.52 | 18.41 | 20.00 | 333.83 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 2900.87 | 16.73 | 29.50 | 331.50 | 1326.52 | 18.58 | 15.33 | 302.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13588.53 | 36.18 | 239.67 | 300.00 | 1839.24 | 18.86 | 21.67 | 273.67 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 11850.67 | 38.57 | 248.50 | 262.83 | 3481.37 | 27.91 | 131.83 | 240.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9577.86 | 37.58 | 233.50 | 254.33 | 7837.92 | 40.39 | 247.17 | 246.33 |
Annual Sum or Average | 3902.00 | 0.50 | 5266.78 | 22.92 | 1276.67 | 3891.00 | 2126.57 | 21.96 | 754.67 | 3542.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1481.48 | 14.85 | 0.00 | 254.33 | 889.14 | 18.41 | 0.00 | 240.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 13943.54 | 39.34 | 274.17 | 394.17 | 7837.92 | 40.39 | 247.17 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2406.25 | 20.52 | 82.67 | 233.67 | 1442.05 | 23.27 | 94.00 | 203.33 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3857.75 | 22.86 | 84.33 | 249.50 | 2277.68 | 23.66 | 70.67 | 204.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3506.00 | 20.27 | 68.83 | 315.67 | 2031.95 | 23.04 | 72.00 | 279.17 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3997.26 | 21.42 | 84.83 | 340.83 | 1745.70 | 22.55 | 54.50 | 298.17 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3194.45 | 21.34 | 111.67 | 399.33 | 1723.71 | 22.84 | 86.17 | 364.67 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3811.40 | 20.96 | 109.00 | 402.50 | 2149.97 | 22.57 | 79.83 | 373.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3417.29 | 21.06 | 114.50 | 404.50 | 1832.86 | 22.56 | 86.67 | 372.17 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:40 | 4657.50 | 21.37 | 116.50 | 368.83 | 1849.40 | 21.98 | 69.83 | 337.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 3866.36 | 22.08 | 108.33 | 330.33 | 1479.41 | 21.59 | 61.00 | 307.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3556.48 | 22.47 | 79.83 | 289.00 | 1974.79 | 23.48 | 63.50 | 244.50 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2392.56 | 20.69 | 69.50 | 239.67 | 1238.95 | 21.57 | 76.83 | 200.33 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:49 | 2406.15 | 21.34 | 78.00 | 228.33 | 1495.91 | 23.95 | 93.50 | 192.17 |
Annual Sum or Average | 3902.00 | 0.51 | 3485.78 | 21.33 | 1108.00 | 3802.17 | 1782.53 | 22.69 | 908.50 | 3377.00 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2392.56 | 20.27 | 68.83 | 228.33 | 1238.95 | 21.57 | 54.50 | 192.17 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 4657.50 | 22.86 | 116.50 | 404.50 | 2277.68 | 23.95 | 94.00 | 373.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.55 | 0.48 | 01-JAN-08:00 | 541.66 | 10.86 | 0.00 | 214.67 | 365.10 | 14.80 | 0.00 | 150.67 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 647.35 | 12.57 | 0.00 | 239.00 | 451.84 | 16.51 | 0.00 | 172.00 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:30 | 840.34 | 14.11 | 0.00 | 313.67 | 550.13 | 17.76 | 0.00 | 253.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1121.65 | 15.32 | 0.00 | 344.17 | 669.16 | 18.82 | 9.50 | 295.67 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1361.02 | 15.67 | 0.00 | 406.67 | 758.51 | 19.31 | 20.50 | 377.00 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1460.28 | 15.87 | 0.00 | 416.33 | 834.75 | 22.29 | 110.17 | 402.67 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1396.28 | 15.58 | 0.00 | 416.50 | 777.93 | 20.45 | 61.67 | 391.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1118.37 | 15.17 | 0.00 | 380.83 | 681.46 | 18.77 | 22.17 | 344.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 919.91 | 14.63 | 0.00 | 327.67 | 586.01 | 18.22 | 0.00 | 286.67 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 783.29 | 13.87 | 0.00 | 278.50 | 533.83 | 17.63 | 0.00 | 212.67 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:50 | 607.60 | 11.97 | 0.00 | 225.83 | 418.32 | 15.90 | 0.00 | 164.83 |
December | 251.17 | 0.54 | 0.48 | 01-DEC-08:30 | 557.96 | 11.47 | 0.00 | 215.00 | 374.08 | 15.43 | 0.00 | 144.67 |
Annual Sum or Average | 3902.00 | 0.51 | 1010.06 | 14.22 | 0.00 | 3778.83 | 613.33 | 18.37 | 224.00 | 3195.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 541.66 | 10.86 | 0.00 | 214.67 | 365.10 | 14.80 | 0.00 | 144.67 | |
Maximum of Months | 430.33 | 0.55 | 0.48 | 1460.28 | 15.87 | 0.00 | 416.50 | 834.75 | 22.29 | 110.17 | 402.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-08:00 | 2891.23 | 23.80 | 108.67 | 250.00 | 1715.82 | 24.36 | 104.00 | 215.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 2937.24 | 21.28 | 68.50 | 254.17 | 1661.33 | 23.84 | 72.83 | 210.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:30 | 3476.67 | 22.57 | 99.33 | 326.67 | 1955.01 | 23.67 | 88.33 | 289.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3244.53 | 21.08 | 85.33 | 344.83 | 1447.07 | 21.31 | 38.83 | 308.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2792.87 | 17.83 | 53.17 | 397.00 | 1454.50 | 18.96 | 4.67 | 364.33 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:00 | 3322.49 | 14.75 | 1.83 | 401.17 | 1841.17 | 18.60 | 1.00 | 374.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 2800.80 | 17.42 | 54.83 | 403.83 | 1517.12 | 18.74 | 5.50 | 374.67 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 2908.59 | 17.39 | 53.67 | 379.67 | 1637.99 | 18.72 | 7.83 | 354.33 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:40 | 3251.92 | 21.91 | 109.83 | 332.17 | 1739.44 | 23.04 | 94.50 | 306.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4193.72 | 23.45 | 92.83 | 294.00 | 1554.14 | 22.47 | 57.00 | 252.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 2755.46 | 21.58 | 77.17 | 248.83 | 1654.72 | 24.91 | 99.17 | 212.50 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2289.34 | 21.97 | 80.67 | 239.67 | 1368.88 | 24.66 | 92.50 | 208.83 |
Annual Sum or Average | 3902.00 | 0.50 | 3066.01 | 19.92 | 885.83 | 3872.00 | 1630.95 | 21.47 | 666.17 | 3472.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2289.34 | 14.75 | 1.83 | 239.67 | 1368.88 | 18.60 | 1.00 | 208.83 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4193.72 | 23.80 | 109.83 | 403.83 | 1955.01 | 24.91 | 104.00 | 374.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:49 | 10373.60 | 39.34 | 274.17 | 267.83 | 5523.82 | 33.85 | 205.33 | 259.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 13943.51 | 39.05 | 241.00 | 263.00 | 2197.85 | 22.23 | 69.67 | 240.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2723.01 | 15.35 | 10.33 | 327.83 | 1496.97 | 18.54 | 19.00 | 289.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 2026.34 | 15.28 | 0.00 | 339.00 | 1171.87 | 18.80 | 16.83 | 298.67 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1823.10 | 15.36 | 0.00 | 391.50 | 1003.13 | 18.85 | 3.50 | 354.17 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:49 | 1481.42 | 15.08 | 0.00 | 390.00 | 889.08 | 18.67 | 0.17 | 348.67 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:10 | 1662.05 | 15.06 | 0.00 | 394.17 | 940.13 | 18.57 | 4.33 | 354.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:10 | 1773.24 | 14.85 | 0.00 | 369.00 | 1078.45 | 18.41 | 20.00 | 333.67 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:19 | 2900.76 | 16.73 | 29.50 | 331.50 | 1326.43 | 18.58 | 15.33 | 302.33 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 13588.46 | 36.18 | 239.67 | 300.00 | 1839.15 | 18.86 | 21.67 | 273.67 |
November | 257.67 | 0.49 | 0.48 | 01-NOV-08:39 | 11850.67 | 38.57 | 248.50 | 262.83 | 3481.27 | 27.91 | 131.83 | 240.83 |
December | 251.17 | 0.49 | 0.48 | 01-DEC-07:40 | 9577.89 | 37.58 | 233.50 | 254.33 | 7837.83 | 40.39 | 247.17 | 246.33 |
Annual Sum or Average | 3902.00 | 0.50 | 5266.71 | 22.92 | 1276.67 | 3891.00 | 2126.49 | 21.96 | 754.83 | 3542.50 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1481.42 | 14.85 | 0.00 | 254.33 | 889.08 | 18.41 | 0.17 | 240.83 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 13943.51 | 39.34 | 274.17 | 394.17 | 7837.83 | 40.39 | 247.17 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2406.24 | 20.52 | 82.67 | 233.67 | 1442.02 | 23.27 | 94.00 | 203.33 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 3857.75 | 22.86 | 84.33 | 249.50 | 2277.64 | 23.66 | 70.83 | 204.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-06:49 | 3505.98 | 20.27 | 68.83 | 315.67 | 2031.89 | 23.04 | 72.00 | 279.17 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3997.21 | 21.42 | 84.83 | 340.83 | 1745.63 | 22.56 | 54.50 | 298.17 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:40 | 3194.38 | 21.34 | 111.67 | 399.33 | 1723.62 | 22.84 | 86.33 | 364.67 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3811.36 | 20.96 | 109.00 | 402.50 | 2149.89 | 22.57 | 79.83 | 373.50 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:10 | 3417.23 | 21.06 | 114.50 | 404.50 | 1832.78 | 22.56 | 86.67 | 372.17 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:40 | 4657.46 | 21.37 | 116.50 | 368.83 | 1849.33 | 21.98 | 69.83 | 337.50 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-05:49 | 3866.32 | 22.08 | 108.33 | 330.33 | 1479.35 | 21.59 | 61.00 | 307.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:19 | 3556.47 | 22.47 | 79.83 | 289.00 | 1974.74 | 23.48 | 63.50 | 244.50 |
November | 257.67 | 0.52 | 0.48 | 01-NOV-08:39 | 2392.56 | 20.70 | 69.50 | 239.67 | 1238.91 | 21.57 | 76.83 | 200.33 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-07:49 | 2406.14 | 21.35 | 78.00 | 228.33 | 1495.88 | 23.95 | 93.50 | 192.17 |
Annual Sum or Average | 3902.00 | 0.51 | 3485.75 | 21.34 | 1108.00 | 3802.17 | 1782.47 | 22.69 | 908.83 | 3377.00 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2392.56 | 20.27 | 68.83 | 228.33 | 1238.91 | 21.57 | 54.50 | 192.17 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 4657.46 | 22.86 | 116.50 | 404.50 | 2277.64 | 23.95 | 94.00 | 373.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.55 | 0.48 | 01-JAN-08:00 | 541.66 | 10.86 | 0.00 | 214.67 | 365.08 | 14.80 | 0.00 | 150.67 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 647.35 | 12.58 | 0.00 | 239.00 | 451.82 | 16.51 | 0.00 | 172.00 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:30 | 840.33 | 14.11 | 0.00 | 313.67 | 550.10 | 17.76 | 0.00 | 253.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 1121.62 | 15.32 | 0.00 | 344.17 | 669.12 | 18.82 | 9.50 | 295.67 |
May | 415.33 | 0.49 | 0.48 | 01-MAY-05:00 | 1360.97 | 15.67 | 0.00 | 406.67 | 758.46 | 19.31 | 20.50 | 377.00 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-04:00 | 1460.24 | 15.87 | 0.00 | 416.33 | 834.70 | 22.29 | 110.17 | 402.67 |
July | 430.33 | 0.49 | 0.48 | 01-JUL-05:30 | 1396.23 | 15.58 | 0.00 | 416.50 | 777.88 | 20.45 | 61.67 | 391.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 1118.35 | 15.18 | 0.00 | 380.83 | 681.42 | 18.77 | 22.17 | 344.00 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:30 | 919.89 | 14.64 | 0.00 | 327.67 | 585.98 | 18.22 | 0.00 | 286.67 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:00 | 783.29 | 13.87 | 0.00 | 278.50 | 533.80 | 17.63 | 0.00 | 212.67 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:50 | 607.60 | 11.97 | 0.00 | 225.83 | 418.30 | 15.90 | 0.00 | 164.83 |
December | 251.17 | 0.54 | 0.48 | 01-DEC-08:30 | 557.96 | 11.47 | 0.00 | 215.00 | 374.06 | 15.43 | 0.00 | 144.67 |
Annual Sum or Average | 3902.00 | 0.51 | 1010.04 | 14.22 | 0.00 | 3778.83 | 613.30 | 18.37 | 224.00 | 3195.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 541.66 | 10.86 | 0.00 | 214.67 | 365.08 | 14.80 | 0.00 | 144.67 | |
Maximum of Months | 430.33 | 0.55 | 0.48 | 1460.24 | 15.87 | 0.00 | 416.50 | 834.70 | 22.29 | 110.17 | 402.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-08:00 | 2891.22 | 23.80 | 108.67 | 250.00 | 1715.78 | 24.36 | 104.00 | 215.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 2937.24 | 21.28 | 68.50 | 254.17 | 1661.29 | 23.84 | 72.83 | 210.50 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:30 | 3476.65 | 22.57 | 99.33 | 326.67 | 1954.95 | 23.67 | 88.50 | 289.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 3244.47 | 21.08 | 85.33 | 344.83 | 1447.00 | 21.31 | 38.83 | 308.33 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:30 | 2792.78 | 17.84 | 53.17 | 397.00 | 1454.41 | 18.96 | 4.67 | 364.33 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-05:00 | 3322.44 | 14.75 | 1.83 | 401.17 | 1841.10 | 18.60 | 1.00 | 374.83 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-06:10 | 2800.73 | 17.43 | 54.83 | 403.83 | 1517.04 | 18.74 | 5.67 | 374.67 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:19 | 2908.56 | 17.40 | 53.67 | 379.67 | 1637.93 | 18.72 | 7.83 | 354.33 |
September | 354.00 | 0.50 | 0.48 | 01-SEP-06:40 | 3251.88 | 21.92 | 109.83 | 332.17 | 1739.37 | 23.04 | 94.50 | 306.00 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:00 | 4193.72 | 23.46 | 92.83 | 294.00 | 1554.09 | 22.47 | 57.00 | 252.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:50 | 2755.46 | 21.58 | 77.17 | 248.83 | 1654.68 | 24.91 | 99.17 | 212.50 |
December | 251.17 | 0.51 | 0.48 | 01-DEC-08:30 | 2289.33 | 21.97 | 80.67 | 239.67 | 1368.84 | 24.66 | 92.50 | 208.83 |
Annual Sum or Average | 3902.00 | 0.50 | 3065.97 | 19.92 | 885.83 | 3872.00 | 1630.89 | 21.47 | 666.50 | 3472.33 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 2289.33 | 14.75 | 1.83 | 239.67 | 1368.84 | 18.60 | 1.00 | 208.83 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 4193.72 | 23.80 | 109.83 | 403.83 | 1954.95 | 24.91 | 104.00 | 374.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1370983.48 | 15123.96 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12354612.98 | 17257.56 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13725596.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12354612.98 | 17257.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223367E+10 | 11079.59 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268667E+10 | 10538.46 | 21-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.237514E+10 | 10557.81 | 21-MAR-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173954E+10 | 10583.44 | 28-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.596300E+09 | 10806.36 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11411829.26 | 7842.30 | 09-JUN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3615660.07 | 3806.15 | 03-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1173257.99 | 3471.14 | 23-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101390E+09 | 10577.16 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162533E+10 | 10666.65 | 12-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175658E+10 | 10554.50 | 10-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303042E+10 | 12483.52 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1173257.99 | 3471.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.303042E+10 | 12483.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.593915E+09 | 8740.52 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.830362E+09 | 8740.52 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.421301E+09 | 8740.52 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182429E+09 | 8740.52 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1859259.08 | 4361.70 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173953E+09 | 8740.52 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250028E+09 | 8740.52 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.921611E+09 | 8740.52 | 07-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.921611E+09 | 8740.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169974E+10 | 7920.79 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201875E+10 | 7533.58 | 22-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105364E+10 | 7545.41 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.479546E+09 | 7531.45 | 26-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19476263.14 | 7502.20 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294808E+09 | 7489.00 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.602869E+09 | 7530.47 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208804E+10 | 8922.71 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208804E+10 | 8922.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.641771E+09 | 8740.44 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.848527E+09 | 8740.44 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467453E+09 | 8740.44 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219356E+09 | 8740.44 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7508827.92 | 6298.72 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176992E+09 | 8740.44 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239689E+09 | 8740.44 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.966176E+09 | 8740.44 | 07-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.966176E+09 | 8740.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114677E+09 | 21218.68 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451092E+09 | 21218.68 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155829E+09 | 21218.68 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69285888.48 | 21218.68 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49429009.95 | 21218.68 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37160690.60 | 21218.68 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.592731E+09 | 21218.68 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592731E+09 | 21218.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.474406E+09 | 12140.57 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.828758E+09 | 12213.88 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.463112E+09 | 12153.26 | 24-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286329E+09 | 12168.28 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10689538.97 | 10271.93 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57482.33 | 383.22 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.408256E+09 | 12162.66 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.381931E+09 | 12212.42 | 30-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111608E+10 | 12797.60 | 19-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111608E+10 | 12797.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.515258E+09 | 9066.39 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.681052E+09 | 9066.39 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.306471E+09 | 9066.39 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165328E+09 | 9066.39 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1211546.29 | 4640.60 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.287976E+09 | 9066.39 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371148E+09 | 9066.39 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112274E+10 | 9066.39 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112274E+10 | 9066.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115495E+10 | 8738.17 | 05-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139016E+10 | 8623.67 | 14-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628383E+09 | 8654.23 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332393E+09 | 8633.31 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8786200.71 | 8580.05 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 139586.33 | 837.93 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.440238E+09 | 8596.20 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729897E+09 | 8619.65 | 02-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218722E+10 | 9751.92 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.687216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218722E+10 | 9751.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.568465E+09 | 9066.31 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.742941E+09 | 9066.31 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352879E+09 | 9066.31 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202783E+09 | 9066.31 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6959291.74 | 5971.48 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 482300.89 | 1258.02 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288518E+09 | 9066.31 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392545E+09 | 9066.31 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119492E+10 | 9066.31 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.375049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119492E+10 | 9066.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150129E+10 | 31239.92 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203038E+10 | 31110.18 | 14-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.955262E+09 | 31208.14 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.707112E+09 | 31104.11 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24407741.81 | 30966.68 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.686289E+09 | 31084.68 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.889376E+09 | 31030.58 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297569E+10 | 31502.84 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.976981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.297569E+10 | 31502.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121709E+10 | 13556.67 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172559E+10 | 13542.59 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119253E+10 | 13562.69 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.756505E+09 | 13507.34 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55913853.26 | 13465.59 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13768162.05 | 10236.25 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.943916E+09 | 13574.73 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103708E+10 | 13561.11 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251985E+10 | 13915.62 | 20-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.946225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251985E+10 | 13915.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114471E+10 | 11386.73 | 18-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138630E+10 | 11323.31 | 24-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.793127E+09 | 11348.88 | 25-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448601E+09 | 11333.48 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16726205.73 | 11300.69 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6715277.23 | 6148.56 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.666508E+09 | 11292.58 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.910248E+09 | 11344.04 | 15-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230838E+10 | 11502.72 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.768132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230838E+10 | 11502.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242295E+10 | 10533.82 | 05-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276639E+10 | 9959.58 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154071E+10 | 9989.05 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.873471E+09 | 9965.72 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52915975.70 | 9952.46 | 03-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15990131.98 | 9940.63 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107076E+10 | 9983.11 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180156E+10 | 9973.54 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431185E+10 | 11225.66 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.431185E+10 | 11225.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129642E+10 | 11502.53 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154190E+10 | 11502.53 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.910202E+09 | 11502.53 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.533159E+09 | 11502.53 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35523787.62 | 11502.53 | 01-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11158729.12 | 6587.92 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.676179E+09 | 11502.53 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100548E+10 | 11502.53 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246807E+10 | 11502.53 | 01-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246807E+10 | 11502.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.815422E+10 | 25134.16 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.807372E+10 | 21629.20 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529279E+10 | 17519.38 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309940E+10 | 18971.40 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272298E+09 | 8634.38 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156637E+09 | 9516.23 | 22-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.330244E+10 | 20736.15 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.605345E+10 | 22018.28 | 30-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107657E+11 | 25134.16 | 19-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107657E+11 | 25134.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.801394E+10 | 25620.90 | 05-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790346E+10 | 21418.25 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.539649E+10 | 18536.94 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337806E+10 | 17601.48 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360045E+09 | 9055.18 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51338.92 | 295.90 | 09-JUN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243824E+09 | 8984.45 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377831E+10 | 20674.15 | 30-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.632666E+10 | 21430.31 | 30-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107170E+11 | 25620.90 | 19-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.461179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107170E+11 | 25620.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.862094E+10 | 24672.34 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844415E+10 | 22657.09 | 02-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.579087E+10 | 22106.20 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360819E+10 | 17254.24 | 15-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.447472E+09 | 9261.57 | 02-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1052688.75 | 1299.42 | 09-JUN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.300955E+09 | 12952.82 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.436513E+10 | 21094.98 | 30-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687664E+10 | 22922.05 | 30-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116173E+11 | 24672.34 | 19-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116173E+11 | 24672.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.126428E+10 | 0.126312E+10 | 21645.17 | 24-JAN-14:00 | 21645.17 | 0.00 |
February | 0.00 | 0.00 | 0.488840E+09 | 0.484675E+09 | 16053.41 | 27-FEB-12:00 | 16053.41 | 0.00 |
March | 0.00 | 0.00 | 0.278180E+10 | 0.277942E+10 | 34152.51 | 14-MAR-13:00 | 34152.51 | 0.00 |
April | 0.00 | 0.00 | 0.288474E+10 | 0.281892E+10 | 25377.38 | 12-APR-13:50 | 25377.38 | 0.00 |
May | 0.00 | 0.00 | 0.117534E+11 | 0.114410E+11 | 42565.73 | 17-MAY-13:00 | 42565.73 | 0.00 |
June | 0.00 | 0.00 | 0.470936E+11 | 0.448618E+11 | 70210.27 | 26-JUN-15:20 | 70210.27 | 0.00 |
July | 0.00 | 0.00 | 0.478116E+11 | 0.441216E+11 | 65724.59 | 17-JUL-12:20 | 65724.59 | 0.00 |
August | 0.00 | 0.00 | 0.476239E+11 | 0.452224E+11 | 65080.07 | 16-AUG-16:00 | 65080.07 | 0.00 |
September | 0.00 | 0.00 | 0.334002E+11 | 0.329082E+11 | 58734.23 | 12-SEP-16:00 | 58734.23 | 0.00 |
October | 0.00 | 0.00 | 0.946419E+10 | 0.939124E+10 | 49446.65 | 10-OCT-15:30 | 49446.65 | 0.00 |
November | 0.00 | 0.00 | 0.300463E+10 | 0.298090E+10 | 27936.81 | 07-NOV-15:00 | 27936.81 | 0.00 |
December | 0.00 | 0.00 | 0.840314E+09 | 0.838620E+09 | 17795.81 | 01-DEC-14:00 | 17795.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208411E+12 | 0.199112E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.488840E+09 | 0.484675E+09 | 16053.41 | 16053.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.478116E+11 | 0.452224E+11 | 70210.27 | 70210.27 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167414E+10 | 0.166197E+10 | 21347.33 | 24-JAN-15:05 | 21347.33 | 0.00 |
February | 0.00 | 0.00 | 0.113149E+10 | 0.111026E+10 | 17312.24 | 27-FEB-15:05 | 17312.24 | 0.00 |
March | 0.00 | 0.00 | 0.319362E+10 | 0.319301E+10 | 36128.77 | 13-MAR-15:50 | 36128.77 | 0.00 |
April | 0.00 | 0.00 | 0.243721E+10 | 0.239957E+10 | 22708.36 | 20-APR-13:00 | 22708.36 | 0.00 |
May | 0.00 | 0.00 | 0.125281E+11 | 0.121914E+11 | 45989.18 | 16-MAY-14:05 | 45989.18 | 0.00 |
June | 0.00 | 0.00 | 0.465937E+11 | 0.444553E+11 | 70693.80 | 26-JUN-15:00 | 70693.80 | 0.00 |
July | 0.00 | 0.00 | 0.473134E+11 | 0.437402E+11 | 67514.41 | 17-JUL-12:02 | 67514.41 | 0.00 |
August | 0.00 | 0.00 | 0.450388E+11 | 0.427845E+11 | 65276.34 | 16-AUG-15:00 | 65276.34 | 0.00 |
September | 0.00 | 0.00 | 0.298831E+11 | 0.294152E+11 | 58428.88 | 11-SEP-14:05 | 58428.88 | 0.00 |
October | 0.00 | 0.00 | 0.712705E+10 | 0.708761E+10 | 48500.32 | 11-OCT-14:05 | 48500.32 | 0.00 |
November | 0.00 | 0.00 | 0.230651E+10 | 0.228035E+10 | 28665.02 | 07-NOV-15:05 | 28665.02 | 0.00 |
December | 0.00 | 0.00 | 0.110494E+10 | 0.110175E+10 | 19010.73 | 01-DEC-14:00 | 19010.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200332E+12 | 0.191421E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.110494E+10 | 0.110175E+10 | 17312.24 | 17312.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.473134E+11 | 0.444553E+11 | 70693.80 | 70693.80 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.905837E+09 | 0.892459E+09 | 19677.38 | 20-JAN-14:00 | 19677.38 | 0.00 |
February | 0.00 | 0.00 | 0.883934E+09 | 0.860671E+09 | 13692.97 | 18-FEB-13:25 | 13692.97 | 0.00 |
March | 0.00 | 0.00 | 0.337174E+10 | 0.336868E+10 | 37873.67 | 13-MAR-15:50 | 37873.67 | 0.00 |
April | 0.00 | 0.00 | 0.251221E+10 | 0.246242E+10 | 25257.75 | 20-APR-13:00 | 25257.75 | 0.00 |
May | 0.00 | 0.00 | 0.135320E+11 | 0.130707E+11 | 54296.96 | 31-MAY-15:20 | 54296.96 | 0.00 |
June | 0.00 | 0.00 | 0.512358E+11 | 0.488806E+11 | 82312.24 | 26-JUN-15:00 | 82312.24 | 0.00 |
July | 0.00 | 0.00 | 0.514263E+11 | 0.475918E+11 | 75056.46 | 17-JUL-14:00 | 75056.46 | 0.00 |
August | 0.00 | 0.00 | 0.490383E+11 | 0.466183E+11 | 77310.39 | 16-AUG-15:00 | 77310.39 | 0.00 |
September | 0.00 | 0.00 | 0.309429E+11 | 0.303048E+11 | 65357.81 | 12-SEP-15:40 | 65357.81 | 0.00 |
October | 0.00 | 0.00 | 0.617284E+10 | 0.613473E+10 | 52999.90 | 11-OCT-14:50 | 52999.90 | 0.00 |
November | 0.00 | 0.00 | 0.239795E+10 | 0.235893E+10 | 27967.96 | 07-NOV-14:40 | 27967.96 | 0.00 |
December | 0.00 | 0.00 | 0.965266E+09 | 0.958753E+09 | 17889.84 | 01-DEC-14:00 | 17889.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.213385E+12 | 0.203503E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.883934E+09 | 0.860671E+09 | 13692.97 | 13692.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.514263E+11 | 0.488806E+11 | 82312.24 | 82312.24 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1932.54 | 6776.77 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1966.04 | 6807.06 | 10-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2065.81 | 6782.68 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1858.75 | 6572.36 | 03-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1828.03 | 6262.14 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1772.19 | 5875.70 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1557.81 | 5570.88 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1687.00 | 5407.03 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1604.55 | 5581.37 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1675.17 | 5946.72 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1796.98 | 6308.95 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1815.13 | 6584.15 | 29-DEC-12:06 |
Annual Sum or Average | 0.00 | 1795.70 | ||||
Minimum of Months | 0.00 | 0.00 | 1557.81 | 5407.03 | ||
Maximum of Months | 0.00 | 0.00 | 2065.81 | 6807.06 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141095E+10 | 0.38 | 2946.30 | 24-JAN-16:20 | 0.97 |
February | 0.128707E+10 | 0.38 | 2679.31 | 27-FEB-15:30 | 0.92 |
March | 0.180732E+10 | 0.42 | 5331.22 | 15-MAR-16:00 | 1.38 |
April | 0.146489E+10 | 0.38 | 2842.53 | 21-APR-13:30 | 0.95 |
May | 0.252470E+10 | 0.42 | 5481.77 | 11-MAY-06:03 | 1.39 |
June | 0.572750E+10 | 0.67 | 11351.24 | 26-JUN-12:08 | 2.18 |
July | 0.545208E+10 | 0.63 | 10630.65 | 24-JUL-15:30 | 2.09 |
August | 0.575602E+10 | 0.65 | 9383.40 | 17-AUG-16:00 | 1.94 |
September | 0.460627E+10 | 0.58 | 11351.24 | 05-SEP-06:02 | 2.19 |
October | 0.243950E+10 | 0.43 | 5875.76 | 10-OCT-08:50 | 1.45 |
November | 0.166281E+10 | 0.39 | 3925.89 | 08-NOV-15:50 | 1.14 |
December | 0.134524E+10 | 0.38 | 2410.28 | 26-DEC-07:03 | 0.87 |
Annual Sum or Average | 0.354843E+11 | 0.48 | |||
Minimum of Months | 0.128707E+10 | 0.38 | 2410.28 | 0.87 | |
Maximum of Months | 0.575602E+10 | 0.67 | 11351.24 | 2.19 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137950E+10 | 0.39 | 2952.40 | 03-JAN-07:01 | 0.99 |
February | 0.130555E+10 | 0.39 | 2952.40 | 06-FEB-06:01 | 0.99 |
March | 0.182971E+10 | 0.43 | 6710.03 | 15-MAR-16:00 | 1.62 |
April | 0.150350E+10 | 0.39 | 4093.73 | 21-APR-12:02 | 1.19 |
May | 0.271013E+10 | 0.46 | 6508.44 | 18-MAY-14:05 | 1.58 |
June | 0.580520E+10 | 0.68 | 10990.50 | 26-JUN-10:10 | 2.18 |
July | 0.551355E+10 | 0.64 | 10990.50 | 17-JUL-05:12 | 2.19 |
August | 0.557125E+10 | 0.65 | 10721.74 | 07-AUG-10:10 | 2.14 |
September | 0.406406E+10 | 0.56 | 10850.49 | 05-SEP-15:40 | 2.16 |
October | 0.203711E+10 | 0.43 | 7100.03 | 10-OCT-16:00 | 1.67 |
November | 0.147960E+10 | 0.40 | 4053.18 | 07-NOV-16:00 | 1.19 |
December | 0.133938E+10 | 0.40 | 2952.40 | 11-DEC-07:01 | 0.99 |
Annual Sum or Average | 0.345385E+11 | 0.48 | |||
Minimum of Months | 0.130555E+10 | 0.39 | 2952.40 | 0.99 | |
Maximum of Months | 0.580520E+10 | 0.68 | 10990.50 | 2.19 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151900E+10 | 0.43 | 2886.42 | 02-JAN-06:01 | 0.90 |
February | 0.152684E+10 | 0.47 | 2886.42 | 01-FEB-06:01 | 0.90 |
March | 0.195550E+10 | 0.49 | 6245.39 | 15-MAR-15:50 | 1.41 |
April | 0.163875E+10 | 0.44 | 4380.57 | 21-APR-13:30 | 1.13 |
May | 0.258788E+10 | 0.46 | 6358.06 | 31-MAY-15:20 | 1.40 |
June | 0.562642E+10 | 0.63 | 11466.71 | 26-JUN-14:00 | 2.03 |
July | 0.525227E+10 | 0.60 | 11363.46 | 17-JUL-10:40 | 2.02 |
August | 0.529883E+10 | 0.60 | 11002.42 | 16-AUG-15:00 | 1.98 |
September | 0.364284E+10 | 0.52 | 9354.60 | 12-SEP-15:40 | 1.79 |
October | 0.195788E+10 | 0.45 | 6549.43 | 11-OCT-16:00 | 1.45 |
November | 0.153681E+10 | 0.43 | 3402.78 | 07-NOV-15:40 | 0.98 |
December | 0.167758E+10 | 0.49 | 2886.42 | 07-DEC-07:01 | 0.90 |
Annual Sum or Average | 0.342206E+11 | 0.50 | |||
Minimum of Months | 0.151900E+10 | 0.43 | 2886.42 | 0.90 | |
Maximum of Months | 0.562642E+10 | 0.63 | 11466.71 | 2.03 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.79 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.20 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:02 | 2.06 | 2.06 | 55.32 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.07 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 56.32 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 55.55 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.02 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 55.89 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.36 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.47 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 56.13 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 55.38 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.32 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.47 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.79 | 56.79 | 1932.54 | 6776.77 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.95 | 56.95 | 1966.04 | 6807.06 | 10-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.82 | 55.82 | 2065.81 | 6782.68 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.76 | 56.76 | 1858.75 | 6572.36 | 03-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.15 | 57.15 | 1828.03 | 6262.14 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.02 | 56.02 | 1772.19 | 5875.70 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.54 | 57.54 | 1557.81 | 5570.88 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.77 | 56.77 | 1687.00 | 5407.03 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.62 | 57.62 | 1604.55 | 5581.37 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.42 | 55.42 | 1675.17 | 5946.72 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.54 | 56.54 | 1796.98 | 6308.95 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.10 | 56.10 | 1815.13 | 6584.15 | 29-DEC-12:06 |
Annual Sum or Average | 0.00 | 1795.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.42 | 55.42 | 1557.81 | 5407.03 | ||
Maximum of Months | 0.00 | 0.00 | 57.62 | 57.62 | 2065.81 | 6807.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.689508E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.780095E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.679447E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.481855E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.596990E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176383E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.173484E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.175461E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.127053E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.694174E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.524808E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.858020E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.118287E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.481855E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.176383E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.462494E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.569236E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.449987E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.317461E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.572484E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.175641E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.172867E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.167511E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.112563E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.520733E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.396114E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.783699E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.103580E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.317461E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.175641E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.933449E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.112127E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.816512E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.559377E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.602538E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.186613E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.181679E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.175862E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.112210E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.749221E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.778486E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.165138E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.137759E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.559377E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.186613E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141095E+10 | 0.126428E+10 | 0.133233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128707E+10 | 0.488840E+09 | 0.144594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180732E+10 | 0.278180E+10 | 0.961033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146489E+10 | 0.288474E+10 | 0.572027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252470E+10 | 0.117534E+11 | 0.897442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.572750E+10 | 0.470936E+11 | 11411829.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.545208E+10 | 0.478116E+11 | 3615660.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.575602E+10 | 0.476239E+11 | 1173257.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.460627E+10 | 0.334002E+11 | 0.258027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243950E+10 | 0.946419E+10 | 0.557352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166281E+10 | 0.300463E+10 | 0.890261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134524E+10 | 0.840314E+09 | 0.177843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354843E+11 | 0.208411E+12 | 0.765454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128707E+10 | 0.488840E+09 | 1173257.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.575602E+10 | 0.478116E+11 | 0.177843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137950E+10 | 0.167414E+10 | 0.108417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130555E+10 | 0.113149E+10 | 0.119975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182971E+10 | 0.319362E+10 | 0.730316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150350E+10 | 0.243721E+10 | 0.443418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271013E+10 | 0.125281E+11 | 0.387692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580520E+10 | 0.465937E+11 | 51338.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.551355E+10 | 0.473134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.557125E+10 | 0.450388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.406406E+10 | 0.298831E+11 | 0.244503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203711E+10 | 0.712705E+10 | 0.525273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147960E+10 | 0.230651E+10 | 0.823935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133938E+10 | 0.110494E+10 | 0.169307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345385E+11 | 0.200332E+12 | 0.656315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130555E+10 | 0.110494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.580520E+10 | 0.473134E+11 | 0.169307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151900E+10 | 0.905837E+09 | 0.162034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152684E+10 | 0.883934E+09 | 0.178947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195550E+10 | 0.337174E+10 | 0.111827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163875E+10 | 0.251221E+10 | 0.692703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.258788E+10 | 0.135320E+11 | 0.632959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.562642E+10 | 0.512358E+11 | 1052688.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.525227E+10 | 0.514263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.529883E+10 | 0.490383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364284E+10 | 0.309429E+11 | 0.348587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195788E+10 | 0.617284E+10 | 0.840878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153681E+10 | 0.239795E+10 | 0.125204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167758E+10 | 0.965266E+09 | 0.262012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342206E+11 | 0.213385E+12 | 0.100321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151900E+10 | 0.883934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.562642E+10 | 0.514263E+11 | 0.262012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141095E+10 | 0.00 | 0.00 | 0.00 | 0.315033E+09 | 0.516909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128707E+10 | 0.00 | 0.00 | 0.00 | 0.128197E+09 | 0.638568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180732E+10 | 0.00 | 0.00 | 0.00 | 0.669604E+09 | 0.431754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146489E+10 | 0.00 | 0.00 | 0.00 | 0.732789E+09 | 0.262087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252470E+10 | 0.00 | 0.00 | 0.00 | 0.282006E+10 | 0.625144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.572750E+10 | 0.00 | 0.00 | 0.00 | 0.118994E+11 | 11411829.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.545208E+10 | 0.00 | 0.00 | 0.00 | 0.118927E+11 | 3615660.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.575602E+10 | 0.00 | 0.00 | 0.00 | 0.117889E+11 | 1173257.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.460627E+10 | 0.00 | 0.00 | 0.00 | 0.799765E+10 | 0.101390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243950E+10 | 0.00 | 0.00 | 0.00 | 0.223116E+10 | 0.227108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166281E+10 | 0.00 | 0.00 | 0.00 | 0.736106E+09 | 0.284916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134524E+10 | 0.00 | 0.00 | 0.00 | 0.216360E+09 | 0.701860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354843E+11 | 0.00 | 0.00 | 0.00 | 0.514279E+11 | 0.313748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128707E+10 | 0.00 | 0.00 | 0.00 | 0.128197E+09 | 1173257.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.575602E+10 | 0.00 | 0.00 | 0.00 | 0.118994E+11 | 0.701860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137950E+10 | 0.00 | 0.00 | 0.00 | 0.417689E+09 | 0.282775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130555E+10 | 0.00 | 0.00 | 0.00 | 0.292803E+09 | 0.409400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182971E+10 | 0.00 | 0.00 | 0.00 | 0.763486E+09 | 0.190667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150350E+10 | 0.00 | 0.00 | 0.00 | 0.614996E+09 | 0.105612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271013E+10 | 0.00 | 0.00 | 0.00 | 0.298707E+10 | 27646577.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580520E+10 | 0.00 | 0.00 | 0.00 | 0.117589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.551355E+10 | 0.00 | 0.00 | 0.00 | 0.117732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.557125E+10 | 0.00 | 0.00 | 0.00 | 0.111798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.406406E+10 | 0.00 | 0.00 | 0.00 | 0.719160E+10 | 679369.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203711E+10 | 0.00 | 0.00 | 0.00 | 0.169580E+10 | 0.147442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147960E+10 | 0.00 | 0.00 | 0.00 | 0.568858E+09 | 0.191268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133938E+10 | 0.00 | 0.00 | 0.00 | 0.283925E+09 | 0.621369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345385E+11 | 0.00 | 0.00 | 0.00 | 0.495281E+11 | 0.195137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130555E+10 | 0.00 | 0.00 | 0.00 | 0.283925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.580520E+10 | 0.00 | 0.00 | 0.00 | 0.117732E+11 | 0.621369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151900E+10 | 0.00 | 0.00 | 0.00 | 0.233028E+09 | 0.758247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152684E+10 | 0.00 | 0.00 | 0.00 | 0.235325E+09 | 0.945057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195550E+10 | 0.00 | 0.00 | 0.00 | 0.817783E+09 | 0.539184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163875E+10 | 0.00 | 0.00 | 0.00 | 0.636178E+09 | 0.331885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.258788E+10 | 0.00 | 0.00 | 0.00 | 0.325201E+10 | 0.185488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.562642E+10 | 0.00 | 0.00 | 0.00 | 0.130349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.525227E+10 | 0.00 | 0.00 | 0.00 | 0.129156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.529883E+10 | 0.00 | 0.00 | 0.00 | 0.122873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364284E+10 | 0.00 | 0.00 | 0.00 | 0.753054E+10 | 47632300.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195788E+10 | 0.00 | 0.00 | 0.00 | 0.149068E+10 | 0.404365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153681E+10 | 0.00 | 0.00 | 0.00 | 0.604299E+09 | 0.564375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167758E+10 | 0.00 | 0.00 | 0.00 | 0.252333E+09 | 0.145838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342206E+11 | 0.00 | 0.00 | 0.00 | 0.532900E+11 | 0.502481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151900E+10 | 0.00 | 0.00 | 0.00 | 0.233028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.562642E+10 | 0.00 | 0.00 | 0.00 | 0.130349E+11 | 0.145838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.626125E+10 | 0.00 | 0.00 | 13696883.10 | 0.00 | 0.00 | 0.854121E+10 | 0.00 | 0.36 |
February | 0.622208E+10 | 0.00 | 0.00 | 11833162.19 | 0.00 | 1066345.60 | 0.756995E+10 | 0.00 | 0.35 |
March | 0.406341E+10 | 0.00 | 0.00 | 20000468.52 | 0.00 | 0.00 | 0.118601E+11 | 0.00 | 0.53 |
April | 0.234705E+10 | 0.00 | 0.00 | 17664401.40 | 0.00 | 0.00 | 0.102309E+11 | 0.00 | 0.46 |
May | 0.789877E+09 | 2838816.86 | 0.00 | 32022096.39 | 2253860.10 | 0.00 | 0.134623E+11 | 0.00 | 0.79 |
June | 0.324192E+09 | 0.449010E+09 | 0.00 | 24859176.88 | 65416198.46 | 0.00 | 0.452437E+10 | 0.00 | 0.69 |
July | 0.266775E+09 | 0.557685E+09 | 0.00 | 21918129.78 | 0.104831E+09 | 0.00 | 0.327211E+10 | 0.00 | 0.64 |
August | 0.370088E+09 | 0.421453E+09 | 0.00 | 31784911.70 | 27290646.26 | 0.00 | 0.615212E+10 | 0.00 | 0.73 |
September | 0.443893E+09 | 61710685.51 | 0.00 | 34838310.10 | 16834695.96 | 0.00 | 0.894967E+10 | 0.00 | 0.80 |
October | 0.203108E+10 | 0.00 | 0.00 | 29581700.14 | 0.00 | 0.00 | 0.137405E+11 | 0.00 | 0.56 |
November | 0.329869E+10 | 0.00 | 0.00 | 21498798.57 | 0.00 | 0.00 | 0.121950E+11 | 0.00 | 0.44 |
December | 0.747626E+10 | 0.00 | 0.00 | 11057929.64 | 0.00 | 3077554.52 | 0.789065E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.338946E+11 | 0.149270E+10 | 0.00 | 0.270756E+09 | 0.216626E+09 | 4143900.12 | 0.108389E+12 | 0.00 | 0.56 |
Minimum of Months | 0.266775E+09 | 0.00 | 0.00 | 11057929.64 | 0.00 | 0.00 | 0.327211E+10 | 0.00 | 0.35 |
Maximum of Months | 0.747626E+10 | 0.557685E+09 | 0.00 | 34838310.10 | 0.104831E+09 | 3077554.52 | 0.137405E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105038E+11 | 0.00 | 0.00 | 2888860.59 | 0.00 | 81368132.69 | 0.170809E+10 | 0.00 | 0.29 |
February | 0.924387E+10 | 0.00 | 0.00 | 2353007.41 | 0.00 | 0.488217E+09 | 0.160960E+10 | 0.00 | 0.29 |
March | 0.767000E+10 | 0.00 | 0.00 | 8243167.73 | 0.00 | 68078599.49 | 0.500643E+10 | 0.00 | 0.42 |
April | 0.621652E+10 | 0.00 | 0.00 | 7125859.10 | 0.00 | 83047133.67 | 0.432198E+10 | 0.00 | 0.39 |
May | 0.166199E+10 | 1527146.32 | 0.00 | 20835151.81 | 1604109.12 | 0.00 | 0.907347E+10 | 0.00 | 0.60 |
June | 0.506291E+09 | 0.337539E+09 | 0.00 | 20248442.74 | 54580615.23 | 0.00 | 0.345536E+10 | 0.00 | 0.57 |
July | 0.424523E+09 | 0.427268E+09 | 0.00 | 17999613.50 | 0.108236E+09 | 0.00 | 0.254352E+10 | 0.00 | 0.53 |
August | 0.568420E+09 | 0.326645E+09 | 0.00 | 25377750.24 | 24947726.87 | 0.00 | 0.463718E+10 | 0.00 | 0.59 |
September | 0.805708E+09 | 49996905.46 | 0.00 | 24757382.62 | 16146768.98 | 0.00 | 0.634183E+10 | 0.00 | 0.61 |
October | 0.508373E+10 | 0.00 | 0.00 | 13441820.87 | 0.00 | 17676532.52 | 0.702800E+10 | 0.00 | 0.43 |
November | 0.835632E+10 | 0.00 | 0.00 | 5511724.11 | 0.00 | 23032429.94 | 0.370224E+10 | 0.00 | 0.34 |
December | 0.114007E+11 | 0.00 | 0.00 | 1133996.46 | 0.00 | 0.435427E+09 | 0.126926E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.624419E+11 | 0.114298E+10 | 0.00 | 0.149917E+09 | 0.205516E+09 | 0.119685E+10 | 0.506970E+11 | 0.00 | 0.45 |
Minimum of Months | 0.424523E+09 | 0.00 | 0.00 | 1133996.46 | 0.00 | 0.00 | 0.126926E+10 | 0.00 | 0.29 |
Maximum of Months | 0.114007E+11 | 0.427268E+09 | 0.00 | 25377750.24 | 0.108236E+09 | 0.488217E+09 | 0.907347E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.931762E+10 | 0.00 | 0.00 | 1116762.09 | 0.00 | 0.129509E+10 | 0.979573E+09 | 0.00 | 0.29 |
February | 0.800271E+10 | 0.00 | 0.00 | 1108095.57 | 0.00 | 0.164460E+10 | 0.103676E+10 | 0.00 | 0.28 |
March | 0.755178E+10 | 0.00 | 0.00 | 6027981.83 | 0.00 | 0.622310E+09 | 0.392612E+10 | 0.00 | 0.40 |
April | 0.596616E+10 | 0.00 | 0.00 | 6005871.86 | 0.00 | 0.476673E+09 | 0.393493E+10 | 0.00 | 0.39 |
May | 0.236867E+10 | 228546.01 | 0.00 | 18588038.04 | 601819.98 | 18433537.45 | 0.815019E+10 | 0.00 | 0.60 |
June | 0.628305E+09 | 0.267338E+09 | 0.00 | 21846307.82 | 49680261.14 | 0.00 | 0.320879E+10 | 0.00 | 0.60 |
July | 0.472036E+09 | 0.340116E+09 | 0.00 | 19290538.10 | 0.103624E+09 | 0.00 | 0.227476E+10 | 0.00 | 0.55 |
August | 0.676922E+09 | 0.268608E+09 | 0.00 | 25266078.61 | 22525009.36 | 0.00 | 0.407443E+10 | 0.00 | 0.59 |
September | 0.131330E+10 | 36530499.15 | 0.00 | 21405207.44 | 13437964.48 | 0.00 | 0.499536E+10 | 0.00 | 0.59 |
October | 0.570505E+10 | 0.00 | 0.00 | 7885762.25 | 0.00 | 0.752638E+09 | 0.443964E+10 | 0.00 | 0.41 |
November | 0.842494E+10 | 0.00 | 0.00 | 2761926.69 | 0.00 | 0.666542E+09 | 0.183690E+10 | 0.00 | 0.32 |
December | 0.888783E+10 | 0.00 | 0.00 | 285801.17 | 0.00 | 0.271539E+10 | 0.366193E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.593153E+11 | 0.912820E+09 | 0.00 | 0.131588E+09 | 0.189869E+09 | 0.819167E+10 | 0.392236E+11 | 0.00 | 0.44 |
Minimum of Months | 0.472036E+09 | 0.00 | 0.00 | 285801.17 | 0.00 | 0.00 | 0.366193E+09 | 0.00 | 0.28 |
Maximum of Months | 0.931762E+10 | 0.340116E+09 | 0.00 | 25266078.61 | 0.103624E+09 | 0.271539E+10 | 0.815019E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101011E+10 | 0.00 | 0.00 | 10186.91 | 0.00 | 0.164804E+10 | 11929870.64 | 0.00 | 0.31 |
February | 0.933730E+09 | 0.00 | 0.00 | 7791.62 | 0.00 | 0.151662E+10 | 16006289.97 | 0.00 | 0.30 |
March | 0.121778E+10 | 0.00 | 0.00 | 752827.52 | 0.00 | 0.916705E+09 | 0.405581E+09 | 0.00 | 0.40 |
April | 0.115649E+10 | 0.00 | 0.00 | 1076337.64 | 0.00 | 0.486380E+09 | 0.612512E+09 | 0.00 | 0.41 |
May | 0.659720E+09 | 79833.28 | 0.00 | 4709986.76 | 126582.94 | 23777817.08 | 0.177019E+10 | 0.00 | 0.73 |
June | 0.129037E+09 | 0.103416E+09 | 0.00 | 6865234.84 | 9134574.14 | 0.00 | 0.885132E+09 | 0.00 | 0.84 |
July | 0.106983E+09 | 0.130578E+09 | 0.00 | 5849271.39 | 18295039.43 | 0.00 | 0.590957E+09 | 0.00 | 0.76 |
August | 0.186955E+09 | 93504325.64 | 0.00 | 6815364.93 | 4199587.18 | 0.00 | 0.934194E+09 | 0.00 | 0.72 |
September | 0.403420E+09 | 14312609.21 | 0.00 | 5058177.33 | 2729081.33 | 10120651.55 | 0.939143E+09 | 0.00 | 0.64 |
October | 0.116317E+10 | 0.00 | 0.00 | 950814.51 | 0.00 | 0.703798E+09 | 0.431152E+09 | 0.00 | 0.40 |
November | 0.103209E+10 | 0.00 | 0.00 | 231338.28 | 0.00 | 0.125053E+10 | 0.126784E+09 | 0.00 | 0.32 |
December | 0.723931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253176E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.872342E+10 | 0.341891E+09 | 0.00 | 32327331.74 | 34484865.02 | 0.908772E+10 | 0.672358E+10 | 0.00 | 0.51 |
Minimum of Months | 0.106983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.121778E+10 | 0.130578E+09 | 0.00 | 6865234.84 | 18295039.43 | 0.253176E+10 | 0.177019E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.728292E+09 | 0.00 | 0.00 | 444019.78 | 0.00 | 0.756112E+09 | 0.253925E+09 | 0.00 | 0.33 |
February | 0.664436E+09 | 0.00 | 0.00 | 814550.55 | 0.00 | 0.645400E+09 | 0.460138E+09 | 0.00 | 0.36 |
March | 0.612383E+09 | 0.00 | 0.00 | 2823574.05 | 0.00 | 0.420736E+09 | 0.148521E+10 | 0.00 | 0.68 |
April | 0.548895E+09 | 0.00 | 0.00 | 2988267.33 | 0.00 | 0.226373E+09 | 0.164066E+10 | 0.00 | 0.74 |
May | 0.265372E+09 | 69590.74 | 0.00 | 6363527.56 | 80481.28 | 7400437.24 | 0.250195E+10 | 0.00 | 1.27 |
June | 35904666.99 | 83264451.72 | 0.00 | 8958881.86 | 4361981.05 | 0.00 | 0.142908E+10 | 0.00 | 1.60 |
July | 37169045.30 | 0.121574E+09 | 0.00 | 7791134.63 | 5260911.54 | 0.00 | 0.771348E+09 | 0.00 | 1.28 |
August | 69503586.69 | 79402149.61 | 0.00 | 9743754.72 | 2533381.42 | 0.00 | 0.169307E+10 | 0.00 | 1.50 |
September | 0.152241E+09 | 12943142.64 | 0.00 | 7465246.61 | 1754124.26 | 5539845.88 | 0.155708E+10 | 0.00 | 1.28 |
October | 0.523829E+09 | 0.00 | 0.00 | 2668925.40 | 0.00 | 0.428801E+09 | 0.122037E+10 | 0.00 | 0.65 |
November | 0.676231E+09 | 0.00 | 0.00 | 895259.06 | 0.00 | 0.616258E+09 | 0.424361E+09 | 0.00 | 0.39 |
December | 0.622247E+09 | 0.00 | 0.00 | 73219.77 | 0.00 | 0.129054E+10 | 58455665.19 | 0.00 | 0.33 |
Annual Sum or Average | 0.493650E+10 | 0.297253E+09 | 0.00 | 51030361.30 | 13990879.55 | 0.439716E+10 | 0.134956E+11 | 0.00 | 0.87 |
Minimum of Months | 35904666.99 | 0.00 | 0.00 | 73219.77 | 0.00 | 0.00 | 58455665.19 | 0.00 | 0.33 |
Maximum of Months | 0.728292E+09 | 0.121574E+09 | 0.00 | 9743754.72 | 5260911.54 | 0.129054E+10 | 0.250195E+10 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.856293E+09 | 0.00 | 0.00 | 7975363.47 | 0.00 | 0.783485E+09 | 0.413285E+10 | 0.00 | 0.83 |
February | 0.748956E+09 | 0.00 | 0.00 | 8127311.06 | 0.00 | 0.769081E+09 | 0.398240E+10 | 0.00 | 0.76 |
March | 0.820681E+09 | 0.00 | 0.00 | 8243566.60 | 0.00 | 0.643696E+09 | 0.408140E+10 | 0.00 | 1.01 |
April | 0.935290E+09 | 0.00 | 0.00 | 4603385.01 | 0.00 | 0.361108E+09 | 0.252829E+10 | 0.00 | 0.77 |
May | 0.554071E+09 | 95986.93 | 0.00 | 7161740.94 | 126993.39 | 25365865.64 | 0.275834E+10 | 0.00 | 0.99 |
June | 0.162388E+09 | 0.116504E+09 | 0.00 | 7879020.32 | 8202754.67 | 0.00 | 0.940475E+09 | 0.00 | 0.93 |
July | 0.115202E+09 | 0.181111E+09 | 0.00 | 6952337.68 | 10290398.29 | 0.00 | 0.650894E+09 | 0.00 | 0.86 |
August | 0.167915E+09 | 0.135853E+09 | 0.00 | 11257113.88 | 3991398.43 | 0.00 | 0.144748E+10 | 0.00 | 1.03 |
September | 0.279641E+09 | 27577035.05 | 0.00 | 13025634.45 | 2725270.39 | 9716302.70 | 0.228736E+10 | 0.00 | 1.28 |
October | 0.634554E+09 | 0.00 | 0.00 | 12468105.62 | 0.00 | 0.630845E+09 | 0.456400E+10 | 0.00 | 1.23 |
November | 0.792923E+09 | 0.00 | 0.00 | 9157321.80 | 0.00 | 0.646836E+09 | 0.398669E+10 | 0.00 | 0.89 |
December | 0.860626E+09 | 0.00 | 0.00 | 5833758.39 | 0.00 | 0.131962E+10 | 0.275435E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.692854E+10 | 0.461142E+09 | 0.00 | 0.102685E+09 | 25336815.17 | 0.518976E+10 | 0.341145E+11 | 0.00 | 0.94 |
Minimum of Months | 0.115202E+09 | 0.00 | 0.00 | 4603385.01 | 0.00 | 0.00 | 0.650894E+09 | 0.00 | 0.70 |
Maximum of Months | 0.935290E+09 | 0.181111E+09 | 0.00 | 13025634.45 | 10290398.29 | 0.131962E+10 | 0.456400E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.618656E+09 | 0.00 | 0.00 | 809107.07 | 0.00 | 0.848356E+09 | 0.541904E+09 | 0.00 | 0.41 |
February | 0.574725E+09 | 0.00 | 0.00 | 1107055.21 | 0.00 | 0.773199E+09 | 0.670372E+09 | 0.00 | 0.41 |
March | 0.659939E+09 | 0.00 | 0.00 | 2842992.89 | 0.00 | 0.500699E+09 | 0.137983E+10 | 0.00 | 0.75 |
April | 0.631922E+09 | 0.00 | 0.00 | 2610210.60 | 0.00 | 0.266625E+09 | 0.138032E+10 | 0.00 | 0.73 |
May | 0.318295E+09 | 98927.69 | 0.00 | 5541975.61 | 80417.65 | 16299449.38 | 0.204155E+10 | 0.00 | 1.16 |
June | 91651294.71 | 0.122962E+09 | 0.00 | 6680314.32 | 2600797.33 | 0.00 | 0.676758E+09 | 0.00 | 1.14 |
July | 69236995.50 | 0.134398E+09 | 0.00 | 4958048.70 | 7291277.16 | 0.00 | 0.473695E+09 | 0.00 | 1.00 |
August | 0.105604E+09 | 0.105002E+09 | 0.00 | 7140202.32 | 1548215.45 | 0.00 | 0.787718E+09 | 0.00 | 1.01 |
September | 0.207792E+09 | 17559988.07 | 0.00 | 6261935.62 | 873185.37 | 7047012.79 | 0.107343E+10 | 0.00 | 1.04 |
October | 0.580680E+09 | 0.00 | 0.00 | 3438538.63 | 0.00 | 0.429871E+09 | 0.133991E+10 | 0.00 | 0.77 |
November | 0.610217E+09 | 0.00 | 0.00 | 1195773.21 | 0.00 | 0.667860E+09 | 0.621808E+09 | 0.00 | 0.45 |
December | 0.509593E+09 | 0.00 | 0.00 | 395010.29 | 0.00 | 0.138941E+10 | 0.243495E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.497831E+10 | 0.380021E+09 | 0.00 | 42981164.48 | 12393892.94 | 0.489937E+10 | 0.112308E+11 | 0.00 | 0.77 |
Minimum of Months | 69236995.50 | 0.00 | 0.00 | 395010.29 | 0.00 | 0.00 | 0.243495E+09 | 0.00 | 0.38 |
Maximum of Months | 0.659939E+09 | 0.134398E+09 | 0.00 | 7140202.32 | 7291277.16 | 0.138941E+10 | 0.204155E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161955E+10 | 0.00 | 0.00 | 0.30 |
February | 0.887116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170301E+10 | 0.00 | 0.00 | 0.30 |
March | 0.134543E+10 | 0.00 | 0.00 | 125291.11 | 0.00 | 0.103726E+10 | 77057735.03 | 0.00 | 0.35 |
April | 0.150289E+10 | 0.00 | 0.00 | 124662.27 | 0.00 | 0.387718E+09 | 86771163.68 | 0.00 | 0.32 |
May | 0.847634E+09 | 530793.32 | 0.00 | 2397560.96 | 477264.81 | 12467926.79 | 0.882409E+09 | 0.00 | 0.48 |
June | 0.144335E+09 | 0.115039E+09 | 0.00 | 4200603.31 | 13826182.60 | 0.00 | 0.622676E+09 | 0.00 | 0.60 |
July | 0.115223E+09 | 0.140750E+09 | 0.00 | 3708007.34 | 22156697.25 | 0.00 | 0.451250E+09 | 0.00 | 0.57 |
August | 0.169422E+09 | 0.103242E+09 | 0.00 | 5144821.64 | 5768073.77 | 0.00 | 0.811721E+09 | 0.00 | 0.60 |
September | 0.357762E+09 | 17168830.69 | 0.00 | 4814403.41 | 3558133.70 | 0.00 | 0.978619E+09 | 0.00 | 0.61 |
October | 0.129001E+10 | 0.00 | 0.00 | 978565.75 | 0.00 | 0.393605E+09 | 0.393617E+09 | 0.00 | 0.34 |
November | 0.155552E+10 | 0.00 | 0.00 | 145219.12 | 0.00 | 0.725087E+09 | 84650868.34 | 0.00 | 0.30 |
December | 0.100711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203857E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.103374E+11 | 0.376731E+09 | 0.00 | 21639134.92 | 45786352.14 | 0.791728E+10 | 0.438877E+10 | 0.00 | 0.42 |
Minimum of Months | 0.115223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.155552E+10 | 0.140750E+09 | 0.00 | 5144821.64 | 22156697.25 | 0.203857E+10 | 0.978619E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.916831E+09 | 0.00 | 0.00 | 301347.23 | 0.00 | 0.656880E+09 | 0.165606E+09 | 0.00 | 0.30 |
February | 0.760012E+09 | 0.00 | 0.00 | 619686.63 | 0.00 | 0.662484E+09 | 0.342022E+09 | 0.00 | 0.33 |
March | 0.749551E+09 | 0.00 | 0.00 | 2004659.01 | 0.00 | 0.360733E+09 | 0.104553E+10 | 0.00 | 0.55 |
April | 0.700112E+09 | 0.00 | 0.00 | 2076517.47 | 0.00 | 0.141153E+09 | 0.100006E+10 | 0.00 | 0.53 |
May | 0.290670E+09 | 617545.62 | 0.00 | 4692646.70 | 299968.25 | 541753.04 | 0.178815E+10 | 0.00 | 0.93 |
June | 31542541.87 | 0.108018E+09 | 0.00 | 6541141.97 | 7219750.94 | 0.00 | 0.116663E+10 | 0.00 | 1.28 |
July | 29958708.32 | 0.141364E+09 | 0.00 | 5614947.97 | 9677095.08 | 0.00 | 0.694319E+09 | 0.00 | 1.06 |
August | 64867249.63 | 0.108459E+09 | 0.00 | 8203886.31 | 3313930.72 | 0.00 | 0.153207E+10 | 0.00 | 1.35 |
September | 0.128794E+09 | 17866455.23 | 0.00 | 7513437.95 | 2113740.91 | 0.00 | 0.169479E+10 | 0.00 | 1.27 |
October | 0.572253E+09 | 0.00 | 0.00 | 3322379.18 | 0.00 | 0.215608E+09 | 0.122014E+10 | 0.00 | 0.59 |
November | 0.975587E+09 | 0.00 | 0.00 | 1172588.40 | 0.00 | 0.259852E+09 | 0.488681E+09 | 0.00 | 0.38 |
December | 0.831666E+09 | 0.00 | 0.00 | 107283.30 | 0.00 | 0.964357E+09 | 85422062.20 | 0.00 | 0.30 |
Annual Sum or Average | 0.605184E+10 | 0.376324E+09 | 0.00 | 42170522.14 | 22624485.91 | 0.326161E+10 | 0.112234E+11 | 0.00 | 0.74 |
Minimum of Months | 29958708.32 | 0.00 | 0.00 | 107283.30 | 0.00 | 0.00 | 85422062.20 | 0.00 | 0.30 |
Maximum of Months | 0.975587E+09 | 0.141364E+09 | 0.00 | 8203886.31 | 9677095.08 | 0.964357E+09 | 0.178815E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108534E+10 | 0.00 | 0.00 | 3900460.00 | 0.00 | 0.165673E+10 | 0.209437E+10 | 0.00 | 0.62 |
February | 0.964737E+09 | 0.00 | 0.00 | 3247309.59 | 0.00 | 0.180250E+10 | 0.176268E+10 | 0.00 | 0.60 |
March | 0.992053E+09 | 0.00 | 0.00 | 3629250.59 | 0.00 | 0.147336E+10 | 0.174335E+10 | 0.00 | 0.74 |
April | 0.114019E+10 | 0.00 | 0.00 | 1287147.74 | 0.00 | 0.100378E+10 | 0.603877E+09 | 0.00 | 0.48 |
May | 0.880255E+09 | 948342.27 | 0.00 | 2807402.77 | 476944.74 | 0.262977E+09 | 0.817842E+09 | 0.00 | 0.57 |
June | 0.228931E+09 | 0.159001E+09 | 0.00 | 4577318.38 | 13612108.90 | 7660447.31 | 0.492495E+09 | 0.00 | 0.66 |
July | 0.170450E+09 | 0.200961E+09 | 0.00 | 4051966.22 | 21151846.04 | 2907419.30 | 0.378284E+09 | 0.00 | 0.64 |
August | 0.243612E+09 | 0.189000E+09 | 0.00 | 8689312.52 | 3339082.50 | 729750.65 | 0.102419E+10 | 0.00 | 0.87 |
September | 0.326005E+09 | 37918694.50 | 0.00 | 11205952.18 | 2968324.34 | 56965922.84 | 0.191069E+10 | 0.00 | 1.18 |
October | 0.589936E+09 | 0.00 | 0.00 | 11011988.13 | 0.00 | 0.108271E+10 | 0.311135E+10 | 0.00 | 0.95 |
November | 0.950400E+09 | 0.00 | 0.00 | 6349246.81 | 0.00 | 0.127351E+10 | 0.268159E+10 | 0.00 | 0.77 |
December | 0.110311E+10 | 0.00 | 0.00 | 3624785.64 | 0.00 | 0.240001E+10 | 0.166665E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.867502E+10 | 0.587829E+09 | 0.00 | 64382140.58 | 41548306.52 | 0.110238E+11 | 0.182874E+11 | 0.00 | 0.73 |
Minimum of Months | 0.170450E+09 | 0.00 | 0.00 | 1287147.74 | 0.00 | 729750.65 | 0.378284E+09 | 0.00 | 0.48 |
Maximum of Months | 0.114019E+10 | 0.200961E+09 | 0.00 | 11205952.18 | 21151846.04 | 0.240001E+10 | 0.311135E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.899871E+09 | 0.00 | 0.00 | 439658.04 | 0.00 | 0.661016E+09 | 0.265950E+09 | 0.00 | 0.34 |
February | 0.750338E+09 | 0.00 | 0.00 | 555067.28 | 0.00 | 0.704248E+09 | 0.376575E+09 | 0.00 | 0.35 |
March | 0.784351E+09 | 0.00 | 0.00 | 1629709.80 | 0.00 | 0.458889E+09 | 0.784391E+09 | 0.00 | 0.56 |
April | 0.800940E+09 | 0.00 | 0.00 | 1381700.98 | 0.00 | 0.180280E+09 | 0.614559E+09 | 0.00 | 0.47 |
May | 0.353570E+09 | 898372.37 | 0.00 | 3598033.60 | 299893.64 | 6735525.21 | 0.127491E+10 | 0.00 | 0.79 |
June | 73398708.94 | 0.149309E+09 | 0.00 | 4372959.44 | 3901634.91 | 0.00 | 0.577814E+09 | 0.00 | 0.91 |
July | 64752454.87 | 0.151861E+09 | 0.00 | 3280998.32 | 9628134.12 | 0.00 | 0.425770E+09 | 0.00 | 0.80 |
August | 81602986.80 | 0.128339E+09 | 0.00 | 5608619.85 | 2607187.43 | 0.00 | 0.781342E+09 | 0.00 | 0.92 |
September | 0.157329E+09 | 21125682.27 | 0.00 | 5807935.92 | 846128.52 | 0.00 | 0.117024E+10 | 0.00 | 1.02 |
October | 0.558993E+09 | 0.00 | 0.00 | 3521220.28 | 0.00 | 0.215125E+09 | 0.121185E+10 | 0.00 | 0.62 |
November | 0.974479E+09 | 0.00 | 0.00 | 1096045.55 | 0.00 | 0.259019E+09 | 0.536395E+09 | 0.00 | 0.40 |
December | 0.842689E+09 | 0.00 | 0.00 | 287644.19 | 0.00 | 0.943533E+09 | 0.177613E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.634231E+10 | 0.451533E+09 | 0.00 | 31579593.24 | 17282978.61 | 0.342885E+10 | 0.819742E+10 | 0.00 | 0.63 |
Minimum of Months | 64752454.87 | 0.00 | 0.00 | 287644.19 | 0.00 | 0.00 | 0.177613E+09 | 0.00 | 0.33 |
Maximum of Months | 0.974479E+09 | 0.151861E+09 | 0.00 | 5807935.92 | 9628134.12 | 0.943533E+09 | 0.127491E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136466E+10 | 0.00 | 0.00 | 19208.83 | 0.00 | 0.122798E+10 | 23369934.47 | 0.00 | 0.29 |
February | 0.124932E+10 | 0.00 | 0.00 | 12919.74 | 0.00 | 0.119083E+10 | 9442157.90 | 0.00 | 0.29 |
March | 0.149161E+10 | 0.00 | 0.00 | 843059.01 | 0.00 | 0.639102E+09 | 0.435633E+09 | 0.00 | 0.40 |
April | 0.139262E+10 | 0.00 | 0.00 | 1072611.19 | 0.00 | 0.264055E+09 | 0.546352E+09 | 0.00 | 0.40 |
May | 0.608430E+09 | 660634.66 | 0.00 | 4951287.39 | 338200.21 | 9933805.48 | 0.180978E+10 | 0.00 | 0.71 |
June | 0.100617E+09 | 0.134595E+09 | 0.00 | 6097380.47 | 11177726.34 | 0.00 | 0.913335E+09 | 0.00 | 0.79 |
July | 94239716.40 | 0.170802E+09 | 0.00 | 5157372.22 | 22234367.25 | 0.00 | 0.634789E+09 | 0.00 | 0.73 |
August | 0.158770E+09 | 0.121045E+09 | 0.00 | 6617026.33 | 5259820.73 | 0.00 | 0.101153E+10 | 0.00 | 0.72 |
September | 0.362375E+09 | 20798230.97 | 0.00 | 5217344.72 | 3184492.36 | 365975.28 | 0.106276E+10 | 0.00 | 0.65 |
October | 0.128515E+10 | 0.00 | 0.00 | 1257516.77 | 0.00 | 0.458270E+09 | 0.553687E+09 | 0.00 | 0.39 |
November | 0.147990E+10 | 0.00 | 0.00 | 329581.01 | 0.00 | 0.803245E+09 | 0.177466E+09 | 0.00 | 0.32 |
December | 0.108512E+10 | 0.00 | 0.00 | 174.34 | 0.00 | 0.197803E+10 | 3544995.73 | 0.00 | 0.31 |
Annual Sum or Average | 0.106728E+11 | 0.447901E+09 | 0.00 | 31575482.01 | 42194606.89 | 0.657181E+10 | 0.718169E+10 | 0.00 | 0.50 |
Minimum of Months | 94239716.40 | 0.00 | 0.00 | 174.34 | 0.00 | 0.00 | 3544995.73 | 0.00 | 0.29 |
Maximum of Months | 0.149161E+10 | 0.170802E+09 | 0.00 | 6617026.33 | 22234367.25 | 0.197803E+10 | 0.180978E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.737711E+09 | 0.00 | 0.00 | 678335.80 | 0.00 | 0.532437E+09 | 0.313211E+09 | 0.00 | 0.28 |
February | 0.594298E+09 | 0.00 | 0.00 | 1251549.78 | 0.00 | 0.525627E+09 | 0.605260E+09 | 0.00 | 0.34 |
March | 0.631381E+09 | 0.00 | 0.00 | 3223744.27 | 0.00 | 0.252269E+09 | 0.159430E+10 | 0.00 | 0.66 |
April | 0.537720E+09 | 0.00 | 0.00 | 3132538.65 | 0.00 | 0.118051E+09 | 0.155879E+10 | 0.00 | 0.68 |
May | 0.218119E+09 | 526200.39 | 0.00 | 6335858.85 | 213459.35 | 456841.67 | 0.244584E+10 | 0.00 | 1.19 |
June | 29372444.11 | 0.103425E+09 | 0.00 | 7981262.52 | 5621194.37 | 0.00 | 0.142195E+10 | 0.00 | 1.47 |
July | 28579735.19 | 0.145848E+09 | 0.00 | 6865574.16 | 8298707.31 | 0.00 | 0.814517E+09 | 0.00 | 1.20 |
August | 67468474.75 | 0.101355E+09 | 0.00 | 9061754.63 | 2698620.02 | 0.00 | 0.170776E+10 | 0.00 | 1.44 |
September | 0.144976E+09 | 18147877.16 | 0.00 | 7289857.86 | 1950324.51 | 0.00 | 0.164572E+10 | 0.00 | 1.24 |
October | 0.536865E+09 | 0.00 | 0.00 | 3217429.55 | 0.00 | 0.273534E+09 | 0.125877E+10 | 0.00 | 0.60 |
November | 0.730353E+09 | 0.00 | 0.00 | 1236016.94 | 0.00 | 0.369487E+09 | 0.544579E+09 | 0.00 | 0.37 |
December | 0.636272E+09 | 0.00 | 0.00 | 235319.40 | 0.00 | 0.978835E+09 | 0.127281E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.489312E+10 | 0.369302E+09 | 0.00 | 50509242.41 | 18782305.56 | 0.305070E+10 | 0.140380E+11 | 0.00 | 0.82 |
Minimum of Months | 28579735.19 | 0.00 | 0.00 | 235319.40 | 0.00 | 0.00 | 0.127281E+09 | 0.00 | 0.28 |
Maximum of Months | 0.737711E+09 | 0.145848E+09 | 0.00 | 9061754.63 | 8298707.31 | 0.978835E+09 | 0.244584E+10 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114201E+10 | 0.00 | 0.00 | 9662354.06 | 0.00 | 0.471300E+09 | 0.423135E+10 | 0.00 | 0.81 |
February | 0.896765E+09 | 0.00 | 0.00 | 9316418.23 | 0.00 | 0.598700E+09 | 0.418232E+10 | 0.00 | 0.78 |
March | 0.104399E+10 | 0.00 | 0.00 | 8866976.55 | 0.00 | 0.423936E+09 | 0.408481E+10 | 0.00 | 1.03 |
April | 0.108074E+10 | 0.00 | 0.00 | 4743314.24 | 0.00 | 0.209986E+09 | 0.230398E+10 | 0.00 | 0.75 |
May | 0.526232E+09 | 952059.53 | 0.00 | 7318188.02 | 339485.33 | 9966945.92 | 0.267350E+10 | 0.00 | 0.96 |
June | 0.145224E+09 | 0.152929E+09 | 0.00 | 6716352.00 | 11272699.34 | 0.00 | 0.884577E+09 | 0.00 | 0.86 |
July | 0.113032E+09 | 0.232902E+09 | 0.00 | 5783306.72 | 14058064.36 | 0.00 | 0.643414E+09 | 0.00 | 0.81 |
August | 0.146326E+09 | 0.190519E+09 | 0.00 | 10398014.84 | 2978049.82 | 0.00 | 0.144350E+10 | 0.00 | 1.01 |
September | 0.274028E+09 | 42465884.22 | 0.00 | 12057972.81 | 2945521.06 | 0.00 | 0.224583E+10 | 0.00 | 1.26 |
October | 0.732396E+09 | 0.00 | 0.00 | 13454822.85 | 0.00 | 0.430575E+09 | 0.435253E+10 | 0.00 | 1.16 |
November | 0.104355E+10 | 0.00 | 0.00 | 10904476.34 | 0.00 | 0.365699E+09 | 0.451183E+10 | 0.00 | 0.97 |
December | 0.109688E+10 | 0.00 | 0.00 | 7280238.07 | 0.00 | 0.951922E+09 | 0.321212E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.824119E+10 | 0.619768E+09 | 0.00 | 0.106502E+09 | 31593819.92 | 0.346209E+10 | 0.347698E+11 | 0.00 | 0.93 |
Minimum of Months | 0.113032E+09 | 0.00 | 0.00 | 4743314.24 | 0.00 | 0.00 | 0.643414E+09 | 0.00 | 0.74 |
Maximum of Months | 0.114201E+10 | 0.232902E+09 | 0.00 | 13454822.85 | 14058064.36 | 0.951922E+09 | 0.451183E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.877110E+09 | 0.00 | 0.00 | 966316.49 | 0.00 | 0.558181E+09 | 0.524579E+09 | 0.00 | 0.38 |
February | 0.741850E+09 | 0.00 | 0.00 | 1243453.87 | 0.00 | 0.584021E+09 | 0.685749E+09 | 0.00 | 0.40 |
March | 0.800472E+09 | 0.00 | 0.00 | 2942207.06 | 0.00 | 0.343445E+09 | 0.134109E+10 | 0.00 | 0.74 |
April | 0.741304E+09 | 0.00 | 0.00 | 2600498.97 | 0.00 | 0.151510E+09 | 0.123006E+10 | 0.00 | 0.71 |
May | 0.301107E+09 | 917687.41 | 0.00 | 5618290.73 | 212909.51 | 5847188.33 | 0.196355E+10 | 0.00 | 1.12 |
June | 80740172.10 | 0.167529E+09 | 0.00 | 5419024.45 | 2663793.89 | 0.00 | 0.641036E+09 | 0.00 | 1.05 |
July | 67469266.41 | 0.184331E+09 | 0.00 | 3947476.91 | 7740709.02 | 0.00 | 0.468247E+09 | 0.00 | 0.93 |
August | 93285127.20 | 0.143248E+09 | 0.00 | 6493347.17 | 1881110.69 | 0.00 | 0.803147E+09 | 0.00 | 1.00 |
September | 0.195918E+09 | 26053218.36 | 0.00 | 5760600.05 | 603280.82 | 231204.63 | 0.108768E+10 | 0.00 | 1.02 |
October | 0.624911E+09 | 0.00 | 0.00 | 3769357.60 | 0.00 | 0.287872E+09 | 0.139664E+10 | 0.00 | 0.75 |
November | 0.855075E+09 | 0.00 | 0.00 | 1414255.92 | 0.00 | 0.410942E+09 | 0.694227E+09 | 0.00 | 0.47 |
December | 0.757735E+09 | 0.00 | 0.00 | 483985.27 | 0.00 | 0.104495E+10 | 0.268810E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.613698E+10 | 0.522079E+09 | 0.00 | 40658814.49 | 13101803.93 | 0.338700E+10 | 0.111048E+11 | 0.00 | 0.75 |
Minimum of Months | 67469266.41 | 0.00 | 0.00 | 483985.27 | 0.00 | 0.00 | 0.268810E+09 | 0.00 | 0.37 |
Maximum of Months | 0.877110E+09 | 0.184331E+09 | 0.00 | 6493347.17 | 7740709.02 | 0.104495E+10 | 0.196355E+10 | 0.00 | 1.12 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.239919E+12 | 0.119676E+11 | 0.00 | 0.167063E+12 | 0.953175E+10 |
February | 0.296879E+12 | 0.160264E+11 | 0.00 | 0.152260E+12 | 0.781227E+10 |
March | 0.361652E+12 | 0.164204E+11 | 0.00 | 0.174808E+12 | 0.147371E+11 |
April | 0.374729E+12 | 0.162298E+11 | 0.00 | 0.172179E+12 | 0.117392E+11 |
May | 0.441199E+12 | 0.872916E+10 | 0.00 | 0.197391E+12 | 0.470784E+11 |
June | 0.462350E+12 | 0.262602E+10 | 0.00 | 0.117953E+12 | 0.181616E+12 |
July | 0.432007E+12 | 0.196518E+10 | 0.00 | 0.946173E+11 | 0.183133E+12 |
August | 0.429869E+12 | 0.246642E+10 | 0.00 | 0.101455E+12 | 0.176957E+12 |
September | 0.325961E+12 | 0.522574E+10 | 0.00 | 0.153692E+12 | 0.117080E+12 |
October | 0.285685E+12 | 0.130970E+11 | 0.00 | 0.198145E+12 | 0.303619E+11 |
November | 0.253075E+12 | 0.128201E+11 | 0.00 | 0.180634E+12 | 0.132863E+11 |
December | 0.198330E+12 | 0.202748E+11 | 0.00 | 0.155625E+12 | 0.996791E+10 |
Annual Sum or Average | 0.410166E+13 | 0.127849E+12 | 0.00 | 0.186582E+13 | 0.803301E+12 |
Minimum of Months | 0.198330E+12 | 0.196518E+10 | 0.00 | 0.946173E+11 | 0.781227E+10 |
Maximum of Months | 0.462350E+12 | 0.202748E+11 | 0.00 | 0.198145E+12 | 0.183133E+12 |