Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:32:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1219.14 | 244.70 | 244.70 |
Net Site Energy | 1039.45 | 208.63 | 208.63 |
Total Source Energy | 3589.38 | 720.44 | 720.44 |
Net Source Energy | 3020.30 | 606.22 | 606.22 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 5.81 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 139.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 176.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 73.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 125.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1088.73 | 130.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 5.81 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 139.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 176.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 33.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 73.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 125.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 5.81 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 139.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 176.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 33.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 73.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 125.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.96 | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 218.53 | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.96 | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 218.53 | 26.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 187.490 | 17.22 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.80 | -0.7 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 179.692 | 16.50 |
Electricity Coming From Utility | 912.009 | 83.77 |
Surplus Electricity Going To Utility | 2.966 | 0.27 |
Net Electricity From Utility | 909.042 | 83.50 |
Total On-Site and Utility Electric Sources | 1088.734 | 100.00 |
Total Electricity End Uses | 1088.734 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 19.00 |
Time Setpoint Not Met During Occupied Cooling | 138.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 563.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-10:00 | 03-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 25360.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 54929.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14732.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38195.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 824.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11525.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8815.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 120214.46 | 34176.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 25360.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 54929.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 14732.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 3662.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 45.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 824.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11525.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8815.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 18.41 | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 442.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 559.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 231.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 135.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3448.02 | 141.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 3.69 | 1.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 112.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 46.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 692.07 | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 3.69 | 1.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 112.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 46.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 692.07 | 28.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.33 | 0.320974 | 0.273000 | 0.637438 | 0.855931 | 0.500000 | 0.001187 |
CORE_MID VAV BOX COMPONENT | 1.94 | 0.387264 | 0.329000 | 0.636699 | 1.00 | 0.500000 | 0.000984 |
CORE_TOP VAV BOX COMPONENT | 2.01 | 0.372072 | 0.316000 | 0.636510 | 0.992193 | 0.500000 | 0.001024 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.597038 | 0.264626 | 0.225000 | 0.134334 | 0.705669 | 0.500000 | 0.001440 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.645400 | 0.154976 | 0.132000 | 0.085193 | 0.413270 | 0.500000 | 0.002458 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.814335 | 0.194013 | 0.165000 | 0.134365 | 0.517368 | 0.500000 | 0.001964 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.729664 | 0.137070 | 0.117000 | 0.085371 | 0.365521 | 0.500000 | 0.002780 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.462283 | 0.341764 | 0.291000 | 0.134524 | 0.911371 | 0.500000 | 0.001115 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.541016 | 0.184878 | 0.157000 | 0.084940 | 0.493007 | 0.500000 | 0.002061 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.652536 | 0.242119 | 0.206000 | 0.134423 | 0.645651 | 0.500000 | 0.001574 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.582428 | 0.171721 | 0.146000 | 0.085035 | 0.457923 | 0.500000 | 0.002219 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.518286 | 0.304835 | 0.259000 | 0.134236 | 0.812893 | 0.500000 | 0.001250 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.634872 | 0.420124 | 0.500000 | 0.002418 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.731441 | 0.216001 | 0.184000 | 0.134585 | 0.576002 | 0.500000 | 0.001764 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.668419 | 0.149630 | 0.127000 | 0.084889 | 0.399012 | 0.500000 | 0.002546 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20893.94 |
CORE_MID VAV BOX REHEAT COIL | 20869.70 |
CORE_TOP VAV BOX REHEAT COIL | 27246.98 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11545.55 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7545.03 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11559.62 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7531.46 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8217.01 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5487.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8252.94 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5463.42 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 9045.48 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6003.99 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 9067.95 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5981.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.29 | 1.08 | 4.57 | 1.26 | 4.05 | 4.05 | 0.300000 | 0.311221 | 4.05 |
PACU_VAV_MID | 2.24 | 1.08 | 4.49 | 1.36 | 3.84 | 3.84 | 0.300000 | 0.355156 | 3.84 |
PACU_VAV_TOP | 2.40 | 1.08 | 4.80 | 2.06 | 4.45 | 4.45 | 0.300000 | 0.463470 | 4.45 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.05 |
PACU_VAV_MID_OA_CONTROLLER | 3.84 |
PACU_VAV_TOP_OA_CONTROLLER | 4.45 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.05 | 72518.18 | 0.800105 | 1.35 | 24170.31 | 0.800105 |
PACU_VAV_MID COOLING COIL | 3.84 | 69096.75 | 0.800076 | 1.28 | 23029.95 | 0.800076 |
PACU_VAV_TOP COOLING COIL | 4.45 | 78687.03 | 0.800808 | 1.48 | 26226.39 | 0.800808 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 7919.13 |
PACU_VAV_MID HEATING COIL | 8576.93 |
PACU_VAV_TOP HEATING COIL | 6543.21 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.05 |
PACU_VAV_MID FAN | 3.84 |
PACU_VAV_TOP FAN | 4.45 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2596E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3063E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8441E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8848E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4129E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4452E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1049 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8915E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1175 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3547E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7984E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1427E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2582E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3009E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8425E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8788E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4116E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4409E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3040E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5262E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8840E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2434E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2347E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1353E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0505E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0673E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7300E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7421E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7081E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7122E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9488E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9862E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4780E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5072E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1646E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1839E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7451E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5619E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1216E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1934E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9474E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2401E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9492E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9865E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4785E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5082E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1655E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1867E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7498E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7326E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4291E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4963E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6380E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3195E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3516E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3965E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1014E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1495E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9640E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9841E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1048 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.0090E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1154 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5558E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3127E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0189E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1653E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4479E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7672E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1779E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1395E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0793E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1454E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0548E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4790E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6195E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3034E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2150E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5978E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6462E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2958E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4208E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5314E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2563E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1048 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.0084E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1154 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5550E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3122E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0184E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1653E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4477E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7671E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1777E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1392E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0791E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1455E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0547E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4791E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6194E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3033E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2149E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5977E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6460E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2957E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4206E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5311E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2560E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 31823.85502 | 31823.85502 | 2.33494 | 2.33494 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5689.27033 | 5689.27033 | 0.24374 | 0.42469 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26401.09427 | 26401.09427 | 1.93525 | 1.93525 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10366.47075 | 10366.47075 | 0.44495 | 0.44495 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27207.93646 | 27207.93646 | 2.01427 | 2.01427 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 19232.83724 | 19232.83724 | 0.83126 | 0.83126 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8064.71417 | 8064.71417 | 0.59704 | 0.59704 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8815.64676 | 8815.64676 | 0.35223 | 0.35223 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8718.03648 | 8718.03648 | 0.64540 | 0.64540 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5755.89468 | 5755.89468 | 0.23019 | 0.23019 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10999.96146 | 10999.96146 | 0.81433 | 0.81433 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8826.07927 | 8826.07927 | 0.35266 | 0.35266 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9856.27100 | 9856.27100 | 0.72966 | 0.72966 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5745.85473 | 5745.85473 | 0.22977 | 0.22977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6244.41022 | 6244.41022 | 0.46228 | 0.46228 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5785.13245 | 5785.13245 | 0.25069 | 0.25069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7307.97949 | 7307.97949 | 0.54102 | 0.54102 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 26.90933 | 8.22654E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3862.09962 | 3862.09962 | 0.16740 | 0.16740 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8814.34309 | 8814.34309 | 0.65254 | 0.65254 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5810.29797 | 5810.29797 | 0.25178 | 0.25178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 7867.36751 | 7867.36751 | 0.58243 | 0.58243 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.23151E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3845.58074 | 3845.58074 | 0.16668 | 0.16668 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7000.92814 | 7000.92814 | 0.51829 | 0.51829 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6366.39649 | 6366.39649 | 0.27596 | 0.27596 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8575.80775 | 8575.80775 | 0.63487 | 0.63487 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12317 | 8.22530E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4224.98878 | 4224.98878 | 0.18317 | 0.18317 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9880.21250 | 9880.21250 | 0.73144 | 0.73144 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6382.14694 | 6382.14694 | 0.27665 | 0.27665 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9028.95445 | 9028.95445 | 0.66842 | 0.66842 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4208.89156 | 4208.89156 | 0.18247 | 0.18247 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 62183.74 | 4.05255 | 4.05255 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 10012.15 | 1.26124 | 1.26124 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 59323.84 | 3.83831 | 3.83831 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 10137.23 | 1.36320 | 1.36320 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 67376.28 | 4.44516 | 4.44516 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 10164.41 | 2.06020 | 2.06020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33494 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32097 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63744 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85593 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18701E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20893.94151 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.93525 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38726 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63670 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.83824E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20869.70434 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.01427 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37207 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63651 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99219 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02399E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27246.97828 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59704 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26463 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13433 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70567 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43977E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11545.54795 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64540 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15498 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51928E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41327 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45844E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7545.02609 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81433 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19401 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16500 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13437 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51737 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96378E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11559.61522 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72966 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13707 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11700 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53707E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36552 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77960E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7531.46056 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.46228 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34176 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13452 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91137 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11480E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8217.01127 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54102 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18488 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49395E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49301 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06082E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5486.99704 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65254 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24212 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13442 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64565 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57360E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8252.94252 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58243 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17172 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14600 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50345E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45792 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21871E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5463.41863 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.51829 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30483 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13424 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81289 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24986E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9045.47527 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63487 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42012 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41833E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6003.98657 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73144 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21600 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18400 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13459 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57600 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76388E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9067.95268 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66842 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14963 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48892E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39901 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54629E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5981.02440 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.28660 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07636 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.57320 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26124 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.05255 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.05255 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.31122 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.24414 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07548 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.48827 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36320 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.83831 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 3.83831 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.35516 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.40035 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07577 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.80071 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.06020 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.44516 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.44516 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.46347 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.05255 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 3.83831 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.44516 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.05255 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.05255 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 72518.17733 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80011 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.35071 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 24170.30850 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80011 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 7919.12591 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.05255 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.83831 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 3.83831 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 69096.75271 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80008 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.27931 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 23029.94768 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80008 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 8576.93134 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 3.83831 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.44516 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.44516 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 78687.03103 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80081 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.48157 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26226.38744 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80081 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 6543.20985 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.44516 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 71524.18 | 244050.62 | 11.46 | 2.96 | 3.28 | 3.45 | 3.65 | 10.09 | 11.18 | 11.77 | 12.44 | 4.6001 | 3.6533 | 2.4531 | 0.9929 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 68167.47 | 232597.05 | 12.39 | 3.21 | 3.54 | 3.72 | 3.95 | 10.95 | 12.09 | 12.71 | 13.48 | 4.3569 | 3.4615 | 2.3250 | 0.9386 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 77571.45 | 264684.78 | 11.43 | 2.95 | 3.27 | 3.44 | 3.64 | 10.07 | 11.16 | 11.74 | 12.41 | 5.0457 | 4.0045 | 2.6875 | 1.0915 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0985852665E-003 | 5.2495114236E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.6768496924E-002 | 4.4416180531E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0645079014E-002 | 7.1750797074E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.0320537746E-003 | 6.5940229606E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.8607002847E-003 | 5.5479136221E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.8002980542E-002 | 1.0970700287E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0298285117E-002 | 2.0969327701E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.6454179558E-002 | 8.8492549368E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.1142295805E-002 | 7.4071872211E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.4888291831E-002 | 3.4219163518E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.0967891894E-002 | 1.6971686567E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.4792560745E-002 | 7.6326621611E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.4823922520E-002 | 5.9591916984E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.1831329380E-002 | 2.9987173214E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.4115466969E-002 | 1.8943650123E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.5669473003E-002 | 9.1027827809E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.8773890529E-002 | 7.5108044779E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7595945977E-002 | 3.3840628283E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3514.76 | 56.38 | 0.00 | 1924.93 | 757.84 | 6253.93 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 39.34 | 0.0000 | Y | 42.16 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 39.34 | 0.0000 | Y | 42.16 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 39.34 | 0.0000 | Y | 42.16 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.87 | 0.0000 | Y | 5.17 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.75 | 0.0000 | Y | 3.25 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.56 | 0.0000 | Y | 5.10 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.66 | 0.0000 | Y | 3.24 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.82 | 0.0000 | Y | 5.15 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.72 | 0.0000 | Y | 3.25 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.54 | 0.0000 | Y | 5.09 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.62 | 0.0000 | Y | 3.23 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.87 | 0.0000 | Y | 5.17 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.75 | 0.0000 | Y | 3.25 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.56 | 0.0000 | Y | 5.10 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 40.56 | 168.00 | 22.66 | 0.0000 | Y | 3.24 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 176.71 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.14 | 42.14 | 4.29 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.75 | 62.95 | 3.31 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.75 | 46.20 | 26.04 | |
Exterior Lighting Total | 3824.74 | 33.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 72518.18 | 58022.16 | 14496.02 | 0.80 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 69096.75 | 55282.63 | 13814.13 | 0.80 | 3.92 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 78687.03 | 63013.20 | 15673.83 | 0.80 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 71524.2 | 2.96 | 10.09 | N/A | N/A | 11.46 | |
PACU_VAV_MID COOLING COIL | 68167.5 | 3.21 | 10.95 | N/A | N/A | 12.39 | |
PACU_VAV_TOP COOLING COIL | 77571.5 | 2.95 | 10.07 | N/A | N/A | 11.43 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20893.94 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 20869.70 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 27246.98 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11545.55 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7545.03 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11559.62 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7531.46 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8217.01 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5487.00 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8252.94 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5463.42 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9045.48 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6003.99 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9067.95 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5981.02 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 7919.13 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 8576.93 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 6543.21 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.05 | 8871.07 | 2189.01 | 1.00 | 1.15 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 3.84 | 8402.09 | 2189.01 | 1.00 | 1.15 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.45 | 9730.50 | 2189.01 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 71524.18 | 2.96 | 10.09 | 11.46 | 4.6001 | 3.28 | 11.18 | 3.6533 | 3.45 | 11.77 | 2.4531 | 3.65 | 12.44 | 0.9929 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 68167.47 | 3.21 | 10.95 | 12.39 | 4.3569 | 3.54 | 12.09 | 3.4615 | 3.72 | 12.71 | 2.3250 | 3.95 | 13.48 | 0.9386 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 77571.45 | 2.95 | 10.07 | 11.43 | 5.0457 | 3.27 | 11.16 | 4.0045 | 3.44 | 11.74 | 2.6875 | 3.64 | 12.41 | 1.0915 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 31823.86 | 31823.86 | 32.36 | 2.335 | 2.335 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_MID | 26401.09 | 26401.09 | 26.84 | 1.935 | 1.935 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_TOP | 27207.94 | 27207.94 | 27.66 | 2.014 | 2.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00894 | 31.30 | 0.00823 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8064.71 | 8064.71 | 38.90 | 0.597 | 0.597 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00879 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8718.04 | 8718.04 | 66.42 | 0.645 | 0.645 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00867 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10999.96 | 10999.96 | 53.05 | 0.814 | 0.814 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00871 | 31.08 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9856.27 | 9856.27 | 75.09 | 0.730 | 0.730 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6244.41 | 6244.41 | 30.12 | 0.462 | 0.462 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00888 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7307.98 | 7307.98 | 55.67 | 0.541 | 0.541 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00871 | 26.91 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8814.34 | 8814.34 | 42.51 | 0.653 | 0.653 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00877 | 31.00 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7867.37 | 7867.37 | 59.94 | 0.582 | 0.582 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00869 | 30.05 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7000.93 | 7000.93 | 33.77 | 0.518 | 0.518 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00883 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8575.81 | 8575.81 | 65.33 | 0.635 | 0.635 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00867 | 26.12 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9880.21 | 9880.21 | 47.65 | 0.731 | 0.731 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00874 | 30.93 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9028.95 | 9028.95 | 68.79 | 0.668 | 0.668 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00867 | 30.41 | 0.00823 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5689.27 | 5689.27 | 5.78 | 0.244 | 0.425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_MID | 10366.47 | 10366.47 | 10.54 | 0.445 | 0.445 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_TOP | 19232.84 | 19232.84 | 19.55 | 0.831 | 0.831 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8815.65 | 8815.65 | 42.52 | 0.352 | 0.352 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00747 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5755.89 | 5755.89 | 43.85 | 0.230 | 0.230 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00750 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8826.08 | 8826.08 | 42.57 | 0.353 | 0.353 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00748 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5745.85 | 5745.85 | 43.78 | 0.230 | 0.230 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.69 | 0.00750 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5785.13 | 5785.13 | 27.90 | 0.251 | 0.251 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3862.10 | 3862.10 | 29.42 | 0.167 | 0.167 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00760 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5810.30 | 5810.30 | 28.02 | 0.252 | 0.252 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3845.58 | 3845.58 | 29.30 | 0.167 | 0.167 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00759 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6366.40 | 6366.40 | 30.71 | 0.276 | 0.276 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00752 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4224.99 | 4224.99 | 32.19 | 0.183 | 0.183 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00754 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6382.15 | 6382.15 | 30.78 | 0.277 | 0.277 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4208.89 | 4208.89 | 32.07 | 0.182 | 0.182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00754 | 3.80 | 0.00506 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.05 | 4.05 | 1.26 | 1.26 | 4.0525 | 1.2612 | 4.0525 | 0.3112 | 0.3000 |
PACU_VAV_MID | 3.84 | 3.84 | 1.36 | 1.36 | 3.8383 | 1.3632 | 3.8383 | 0.3552 | 0.3000 |
PACU_VAV_TOP | 4.45 | 4.45 | 2.06 | 2.06 | 4.4452 | 2.0602 | 4.4452 | 0.4635 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20893.942 | 20893.942 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20893.94 | 13920.52 | 0.424691 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 5689.27 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 20869.704 | 20869.704 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20869.70 | 14584.48 | 0.444947 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 10366.47 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27246.978 | 27246.978 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27246.98 | 27246.98 | 0.831258 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 19232.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11545.548 | 11545.548 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11545.55 | 11545.55 | 0.352235 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00747489 | 48.3641 | 8815.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7545.026 | 7545.026 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7545.03 | 7545.03 | 0.230186 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00750450 | 48.5542 | 5755.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11559.615 | 11559.615 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11559.62 | 11559.62 | 0.352664 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00747718 | 48.3788 | 8826.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7531.461 | 7531.461 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7531.46 | 7531.46 | 0.229772 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.69 | 0.00750111 | 48.5324 | 5745.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8217.011 | 8217.011 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8217.01 | 8217.01 | 0.250687 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00758075 | 48.1316 | 5785.13 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5486.997 | 5486.997 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5487.00 | 5487.00 | 0.167399 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00759527 | 48.2228 | 3862.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8252.943 | 8252.943 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8252.94 | 8252.94 | 0.251783 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00758327 | 48.1474 | 5810.30 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5463.419 | 5463.419 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5463.42 | 5463.42 | 0.166679 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00759282 | 48.2074 | 3845.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 9045.475 | 9045.475 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9045.48 | 9045.48 | 0.275962 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00752471 | 47.7808 | 6366.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6003.987 | 6003.987 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6003.99 | 6003.99 | 0.183171 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00754048 | 47.8798 | 4224.99 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 9067.953 | 9067.953 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9067.95 | 9067.95 | 0.276648 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00752634 | 47.7911 | 6382.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5981.024 | 5981.024 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5981.02 | 5981.02 | 0.182471 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00753803 | 47.8644 | 4208.89 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 72518.177 | 58022.156 | 4.052546 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 72491.81 | 69901.33 | 4.052546 | 25.72 | 16.98 | 0.00871379 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 23.5926 | 24.00 | 0.00886210 | 46.7949 | 54740.52 | 0.00 | 74775.98 | 58267.73 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 7919.126 | 7919.126 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7919.13 | 7919.13 | 1.215764 | 7.31 | 6.26 | 0.00557954 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 78.6419 | 19.69 | 0.00738512 | 50.8603 | 12938.69 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 69096.753 | 55282.625 | 3.838305 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 69116.99 | 66618.36 | 3.838305 | 25.82 | 17.01 | 0.00871781 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 24.9094 | 24.00 | 0.00887851 | 46.8803 | 51835.74 | 0.00 | 71248.03 | 55511.32 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 8576.931 | 8576.931 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8576.93 | 8576.93 | 1.151492 | 6.53 | 5.69 | 0.00543975 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 83.0314 | 19.60 | 0.00701683 | 48.6262 | 17359.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 78687.031 | 63013.201 | 4.445157 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 78567.57 | 75928.19 | 4.445157 | 25.57 | 16.91 | 0.00869845 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 21.5088 | 24.00 | 0.00882594 | 46.6066 | 60014.68 | 0.00 | 81136.89 | 63285.89 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 6543.210 | 6543.210 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6543.21 | 6543.21 | 1.333547 | 8.67 | 7.22 | 0.00583546 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 71.6960 | 18.94 | 0.00777508 | 56.0476 | 19001.78 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20893.942 | 20893.942 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20893.94 | 13920.52 | 1.0000 | 0.50189087 | 0.424691 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20893.94 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.65 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 5689.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 20869.704 | 20869.704 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20869.70 | 14584.48 | 1.0000 | 0.52582933 | 0.444947 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20869.70 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 10366.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 27246.978 | 27246.978 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 27246.98 | 27246.98 | 1.0000 | 0.98236319 | 0.831258 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27246.98 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 19232.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11545.548 | 11545.548 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11545.55 | 11545.55 | 1.0000 | 0.41626346 | 0.352235 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11545.55 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00747489 | 20.69 | 0.00747489 | 48.3641 | 8815.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7545.026 | 7545.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7545.03 | 7545.03 | 1.0000 | 0.27202855 | 0.230186 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7545.03 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00750450 | 20.69 | 0.00750450 | 48.5542 | 5755.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11559.615 | 11559.615 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11559.62 | 11559.62 | 1.0000 | 0.41677064 | 0.352664 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11559.62 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00747718 | 20.69 | 0.00747718 | 48.3788 | 8826.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7531.461 | 7531.461 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7531.46 | 7531.46 | 1.0000 | 0.27153946 | 0.229772 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7531.46 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00750111 | 20.69 | 0.00750111 | 48.5324 | 5745.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8217.011 | 8217.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8217.01 | 8217.01 | 1.0000 | 0.29625632 | 0.250687 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8217.01 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00758075 | 21.00 | 0.00758075 | 48.1316 | 5785.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5486.997 | 5486.997 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5487.00 | 5487.00 | 1.0000 | 0.19782832 | 0.167399 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5487.00 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00759527 | 21.00 | 0.00759527 | 48.2228 | 3862.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8252.943 | 8252.943 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8252.94 | 8252.94 | 1.0000 | 0.29755178 | 0.251783 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8252.94 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00758327 | 21.00 | 0.00758327 | 48.1474 | 5810.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5463.419 | 5463.419 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5463.42 | 5463.42 | 1.0000 | 0.19697822 | 0.166679 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5463.42 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00759282 | 21.00 | 0.00759282 | 48.2074 | 3845.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9045.475 | 9045.475 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9045.48 | 9045.48 | 1.0000 | 0.32612578 | 0.275962 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9045.48 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00752471 | 21.00 | 0.00752471 | 47.7808 | 6366.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6003.987 | 6003.987 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6003.99 | 6003.99 | 1.0000 | 0.21646787 | 0.183171 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6003.99 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00754048 | 21.00 | 0.00754048 | 47.8798 | 4224.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9067.953 | 9067.953 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9067.95 | 9067.95 | 1.0000 | 0.32693618 | 0.276648 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9067.95 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00752634 | 21.00 | 0.00752634 | 47.7911 | 6382.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5981.024 | 5981.024 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5981.02 | 5981.02 | 1.0000 | 0.21563999 | 0.182471 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5981.02 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00753803 | 21.00 | 0.00753803 | 47.8644 | 4208.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 72518.177 | 58022.156 | 4.052546 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0385 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.052546 | 4.78921238 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 72491.81 | 69901.33 | 0.9996 | 4.78921238 | 4.052546 | 25.72 | 16.98 | 0.00871379 | 48055.2 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 8871.068 | 63620.74 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 23.5926 | 24.00 | 0.00886210 | 24.00 | 0.00886210 | 46.7949 | 54740.52 | 0.00 | 74775.98 | 58267.73 | 4.60007470 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.28 | 13.93 | 0.00977762 | 39067.0 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7919.126 | 7919.126 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.052546 | 4.78921238 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7919.13 | 7919.13 | 1.0000 | 1.43676372 | 1.215764 | 7.31 | 6.26 | 0.00557954 | 21380.2 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7919.13 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 78.6419 | 20.26 | 0.00749830 | 19.69 | 0.00738512 | 50.8603 | 12938.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 69096.753 | 55282.625 | 3.838305 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0460 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.838305 | 4.53602717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 69116.99 | 66618.36 | 1.0003 | 4.53602717 | 3.838305 | 25.82 | 17.01 | 0.00871781 | 48164.0 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 8402.092 | 60714.90 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 24.9094 | 24.00 | 0.00887851 | 24.00 | 0.00887851 | 46.8803 | 51835.74 | 0.00 | 71248.03 | 55511.32 | 4.35688839 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.21 | 13.89 | 0.00976851 | 38969.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8576.931 | 8576.931 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.838305 | 4.53602717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8576.93 | 8576.93 | 1.0000 | 1.36080815 | 1.151492 | 6.53 | 5.69 | 0.00543975 | 20229.7 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8576.93 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 83.0314 | 19.87 | 0.00730562 | 19.60 | 0.00701683 | 48.6262 | 17359.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 78687.031 | 63013.201 | 4.445157 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0100 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.445157 | 5.25319210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 78567.57 | 75928.19 | 0.9985 | 5.25319210 | 4.445157 | 25.57 | 16.91 | 0.00869845 | 47861.6 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 9730.498 | 68837.07 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 21.5088 | 24.00 | 0.00882594 | 24.00 | 0.00882594 | 46.6066 | 60014.68 | 0.00 | 81136.89 | 63285.89 | 5.04573072 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.41 | 14.00 | 0.00979755 | 39242.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6543.210 | 6543.210 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.445157 | 5.25319210 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6543.21 | 6543.21 | 1.0000 | 1.57595763 | 1.333547 | 8.67 | 7.22 | 0.00583546 | 23398.3 | 12.80 | 11.43 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6543.21 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 71.6960 | 21.00 | 0.00780373 | 18.94 | 0.00777508 | 56.0476 | 19001.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.05 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 3.84 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.45 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 3030.83 | 770.00 | 12.33 |
CORE_MID | 2125.50 | 2081.00 | 8.33 |
CORE_TOP | 1753.50 | 2834.67 | 7.00 |
PERIMETER_TOP_ZN_3 | 1725.83 | 3568.50 | 229.50 |
PERIMETER_TOP_ZN_2 | 2288.50 | 2796.00 | 178.83 |
PERIMETER_TOP_ZN_1 | 2588.83 | 2498.83 | 182.83 |
PERIMETER_TOP_ZN_4 | 2469.33 | 2967.33 | 317.17 |
PERIMETER_BOT_ZN_3 | 1179.17 | 3801.00 | 34.83 |
PERIMETER_BOT_ZN_2 | 2175.50 | 2532.67 | 30.67 |
PERIMETER_BOT_ZN_1 | 2223.17 | 2685.50 | 111.17 |
PERIMETER_BOT_ZN_4 | 2398.33 | 2547.17 | 56.33 |
PERIMETER_MID_ZN_3 | 1705.83 | 3145.33 | 37.67 |
PERIMETER_MID_ZN_2 | 1951.33 | 2172.33 | 80.67 |
PERIMETER_MID_ZN_1 | 2786.33 | 2000.33 | 74.17 |
PERIMETER_MID_ZN_4 | 2558.83 | 2487.83 | 128.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4337.67 | 4387.17 | 563.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 15.00 | 0.00 | 15.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 22.50 | 0.00 | 22.50 |
PERIMETER_TOP_ZN_4 | 0.00 | 31.33 | 0.00 | 25.17 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 5.33 | 0.00 | 5.33 |
PERIMETER_BOT_ZN_1 | 19.00 | 31.83 | 19.00 | 31.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 13.50 | 0.00 | 11.33 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 15.83 | 0.00 | 15.83 |
PERIMETER_MID_ZN_1 | 0.00 | 30.50 | 0.00 | 30.50 |
PERIMETER_MID_ZN_4 | 0.00 | 26.67 | 0.00 | 22.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 19.00 | 149.00 | 19.00 | 138.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 1.103 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.831 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.819 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.861 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 1.279 | 0.061 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 1.434 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 1.379 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.737 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 1.120 | 0.032 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 1.095 | 0.829 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 1.175 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.850 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 1.158 | 0.052 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 1.426 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 1.352 | 0.051 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.81 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 17315561.26 | 0.00 | 17315561.26 | 0.00 | 17315561.26 | 13393058.27 | 4117.15 | 122.19 | 4520.66 | 25.58 |
CORE_MID | 13084433.54 | 0.00 | 13084433.54 | 0.00 | 13084433.54 | 13393058.27 | 4145.56 | 208.49 | 4405.95 | 33.92 |
CORE_TOP | 12914848.27 | 0.00 | 12914848.27 | 0.00 | 12914848.27 | 13393058.27 | 4129.77 | 281.10 | 4349.12 | 37.75 |
PERIMETER_TOP_ZN_3 | 2860710.54 | 0.00 | 2860710.54 | 331330.52 | 3192041.06 | 2823374.22 | 4036.15 | 273.77 | 4450.08 | 37.75 |
PERIMETER_TOP_ZN_2 | 2682342.89 | 0.00 | 2682342.89 | 220885.69 | 2903228.57 | 1787429.43 | 3974.85 | 244.76 | 4540.39 | 37.75 |
PERIMETER_TOP_ZN_1 | 4754876.01 | 0.00 | 4754876.01 | 331330.52 | 5086206.53 | 2823374.22 | 3964.44 | 266.43 | 4529.13 | 37.75 |
PERIMETER_TOP_ZN_4 | 2897793.45 | 0.00 | 2897793.45 | 220885.69 | 3118679.14 | 1787312.18 | 3995.20 | 186.72 | 4578.09 | 37.75 |
PERIMETER_BOT_ZN_3 | 2447264.57 | 0.00 | 2447264.57 | 176167.23 | 2623431.80 | 2823374.22 | 4272.08 | 121.67 | 4366.25 | 25.58 |
PERIMETER_BOT_ZN_2 | 2346937.07 | 0.00 | 2346937.07 | 117444.12 | 2464381.19 | 1787429.43 | 4101.30 | 131.35 | 4527.35 | 25.58 |
PERIMETER_BOT_ZN_1 | 3631750.38 | 0.00 | 3631750.38 | 2823248.61 | 6454999.00 | 2823374.22 | 4012.74 | 116.75 | 4630.51 | 25.58 |
PERIMETER_BOT_ZN_4 | 2462055.15 | 0.00 | 2462055.15 | 117444.12 | 2579499.26 | 1787312.18 | 4106.79 | 131.82 | 4521.39 | 25.58 |
PERIMETER_MID_ZN_3 | 2822401.83 | 0.00 | 2822401.83 | 275807.65 | 3098209.48 | 2823374.22 | 4027.03 | 211.03 | 4521.95 | 33.92 |
PERIMETER_MID_ZN_2 | 2484659.72 | 0.00 | 2484659.72 | 183870.66 | 2668530.38 | 1601953.02 | 3935.36 | 189.16 | 4635.48 | 942.92 |
PERIMETER_MID_ZN_1 | 4726194.22 | 0.00 | 4726194.22 | 275807.65 | 5002001.87 | 2823374.22 | 3927.98 | 177.69 | 4654.32 | 33.92 |
PERIMETER_MID_ZN_4 | 2837300.13 | 0.00 | 2837300.13 | 183870.66 | 3021170.79 | 1787312.18 | 3971.57 | 217.64 | 4570.79 | 33.92 |
Total Facility | 80269129.02 | 0.00 | 80269129.02 | 5258093.13 | 85527222.15 | 67658168.57 | 4452.29 | 350.16 | 4863.26 | 956.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.8066 | 0.0000 | 0.8066 | 0.0000 | 0.8066 | 0.4247 | 1325.73 | 122.19 | 4495.08 |
CORE_MID | 0.6079 | 0.0000 | 0.6079 | 0.0000 | 0.6079 | 0.4247 | 1362.48 | 208.49 | 4372.03 |
CORE_TOP | 0.5996 | 0.0000 | 0.5996 | 0.0000 | 0.5996 | 0.4247 | 1350.53 | 281.10 | 4311.37 |
PERIMETER_TOP_ZN_3 | 0.1329 | 0.0000 | 0.1329 | 0.0089 | 0.1418 | 0.0895 | 1256.90 | 273.77 | 4412.33 |
PERIMETER_TOP_ZN_2 | 0.1248 | 0.0000 | 0.1248 | 0.0059 | 0.1308 | 0.0567 | 1195.60 | 244.76 | 4502.64 |
PERIMETER_TOP_ZN_1 | 0.2214 | 0.0000 | 0.2214 | 0.0089 | 0.2303 | 0.0895 | 1185.19 | 266.43 | 4491.38 |
PERIMETER_TOP_ZN_4 | 0.1346 | 0.0000 | 0.1346 | 0.0059 | 0.1406 | 0.0567 | 1215.95 | 186.72 | 4540.34 |
PERIMETER_BOT_ZN_3 | 0.1138 | 0.0000 | 0.1138 | 0.0047 | 0.1185 | 0.0895 | 1480.66 | 121.67 | 4340.67 |
PERIMETER_BOT_ZN_2 | 0.1093 | 0.0000 | 0.1093 | 0.0032 | 0.1125 | 0.0567 | 1309.88 | 131.35 | 4501.77 |
PERIMETER_BOT_ZN_1 | 0.1692 | 0.0000 | 0.1692 | 0.1285 | 0.2976 | 0.0895 | 1221.32 | 116.75 | 4604.93 |
PERIMETER_BOT_ZN_4 | 0.1146 | 0.0000 | 0.1146 | 0.0032 | 0.1178 | 0.0567 | 1315.37 | 131.82 | 4495.81 |
PERIMETER_MID_ZN_3 | 0.1312 | 0.0000 | 0.1312 | 0.0074 | 0.1386 | 0.0895 | 1243.94 | 211.03 | 4488.03 |
PERIMETER_MID_ZN_2 | 0.1131 | 0.0000 | 0.1131 | 0.0051 | 0.1182 | 0.0567 | 1152.28 | 189.16 | 3692.56 |
PERIMETER_MID_ZN_1 | 0.2201 | 0.0000 | 0.2201 | 0.0074 | 0.2276 | 0.0895 | 1144.90 | 177.69 | 4620.41 |
PERIMETER_MID_ZN_4 | 0.1319 | 0.0000 | 0.1319 | 0.0049 | 0.1369 | 0.0567 | 1188.49 | 217.64 | 4536.87 |
Total Facility | 3.7311 | 0.0000 | 3.7311 | 0.1942 | 3.9252 | 2.1513 | 1648.96 | 350.16 | 4815.68 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 39389130.81 | 0.00 | 39389130.81 | 22614548.33 | 3912.25 | 3.56 | 4844.19 | 25.58 |
PACU_VAV_MID | 36248771.06 | 0.00 | 36248771.06 | 22429071.92 | 3859.96 | 3.81 | 4896.23 | 33.92 |
PACU_VAV_TOP | 36466039.07 | 0.00 | 36466039.07 | 22614548.33 | 3897.48 | 2.85 | 4859.67 | 37.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.8345 | 0.0000 | 1.8345 | 0.7171 | 1120.84 | 3.56 | 4818.61 |
PACU_VAV_MID | 1.6855 | 0.0000 | 1.6855 | 0.7084 | 1076.87 | 3.81 | 4862.32 |
PACU_VAV_TOP | 1.6945 | 0.0000 | 1.6945 | 0.7171 | 1118.23 | 2.85 | 4821.92 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 95.00 | 4460.24 | 0.00 | 0.00 | 0.00 | 303.73 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 57.82 | 4484.12 | 0.00 | 0.00 | 0.00 | 377.88 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 59.66 | 4453.44 | 0.00 | 0.00 | 0.00 | 405.18 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3203 | 2.3553 | 0.0000 | 0.0000 | 0.0000 | 1.0997 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3293 | 2.1434 | 0.0000 | 0.0000 | 0.0000 | 1.0684 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.3246 | 2.1670 | 0.0000 | 0.0000 | 0.0000 | 1.0493 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1088.73 | 11286.77 | 14-MAY-17:10 | 120214.46 | 16-OCT-11:00 |
Electricity:Building | 824.46 | 11118.23 | 14-MAY-17:10 | 57180.09 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 220.64 | 3059.02 | 01-JAN-00:10 | 16454.92 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 824.46 | 11118.23 | 14-MAY-17:10 | 57180.09 | 02-JAN-16:50 |
InteriorLights:Electricity | 176.71 | 818.34 | 01-JAN-08:50 | 18725.62 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 176.71 | 818.34 | 01-JAN-08:50 | 18725.62 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 176.71 | 818.34 | 01-JAN-08:50 | 18725.62 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 176.71 | 818.34 | 01-JAN-08:50 | 18725.62 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 157.58 | 2036.88 | 01-JAN-00:10 | 10504.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 157.58 | 2036.88 | 01-JAN-00:10 | 10504.96 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 42.16 | 205.34 | 01-JAN-00:10 | 3696.64 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.50 | 406.75 | 16-APR-17:10 | 2214.53 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.17 | 20.65 | 01-JAN-08:50 | 779.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.17 | 20.65 | 01-JAN-08:50 | 779.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.66 | 257.49 | 14-MAY-17:10 | 1401.92 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.25 | 13.07 | 01-JAN-07:20 | 493.35 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.25 | 13.07 | 01-JAN-07:20 | 493.35 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.43 | 406.75 | 16-APR-17:10 | 2214.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.10 | 20.65 | 01-JAN-07:20 | 779.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.10 | 20.65 | 01-JAN-07:20 | 779.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.64 | 257.49 | 12-MAR-17:10 | 1401.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.24 | 13.07 | 01-JAN-08:50 | 493.32 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.24 | 13.07 | 01-JAN-08:50 | 493.32 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.49 | 406.75 | 16-APR-17:10 | 2214.53 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.15 | 20.65 | 01-JAN-08:40 | 779.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.15 | 20.65 | 01-JAN-08:40 | 779.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.65 | 257.49 | 30-APR-17:10 | 1401.92 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.25 | 13.07 | 01-JAN-07:20 | 493.35 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.25 | 13.07 | 01-JAN-07:20 | 493.35 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.42 | 406.75 | 16-APR-17:10 | 2214.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.09 | 20.65 | 01-JAN-07:20 | 779.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.09 | 20.65 | 01-JAN-07:20 | 779.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.64 | 257.49 | 12-MAR-17:10 | 1401.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.23 | 13.07 | 01-JAN-08:40 | 493.32 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.23 | 13.07 | 01-JAN-08:40 | 493.32 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.50 | 406.75 | 16-APR-17:10 | 2214.53 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.17 | 20.65 | 01-JAN-08:50 | 779.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.17 | 20.65 | 01-JAN-08:50 | 779.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.66 | 257.49 | 14-MAY-17:10 | 1401.92 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.25 | 13.07 | 01-JAN-07:20 | 493.35 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.25 | 13.07 | 01-JAN-07:20 | 493.35 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.43 | 406.75 | 16-APR-17:10 | 2214.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.10 | 20.65 | 01-JAN-07:20 | 779.28 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.10 | 20.65 | 01-JAN-07:20 | 779.28 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.64 | 257.49 | 12-MAR-17:10 | 1401.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.24 | 13.07 | 01-JAN-08:50 | 493.32 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.24 | 13.07 | 01-JAN-08:50 | 493.32 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 179.69 | -0.00 | 11-FEB-06:40 | 26813.75 | 27-MAY-11:40 |
ElectricityProduced:Plant | 179.69 | -0.00 | 11-FEB-06:40 | 26813.75 | 27-MAY-11:40 |
Photovoltaic:ElectricityProduced | 187.49 | 0.00 | 01-JAN-00:10 | 28118.69 | 27-MAY-11:50 |
PowerConversion:ElectricityProduced | -7.80 | -1304.94 | 27-MAY-11:50 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 230.49 | 168.34 | 01-JAN-00:10 | 67279.69 | 16-OCT-11:00 |
ExteriorEquipment:Electricity | 11.63 | 168.34 | 01-JAN-00:10 | 830.04 | 02-JAN-17:00 |
Transformer:ExteriorEquipment:Electricity | 11.63 | 168.34 | 01-JAN-00:10 | 830.04 | 02-JAN-17:00 |
ElectricityPurchased:Facility | 912.01 | 0.00 | 08-JAN-10:30 | 107708.51 | 16-OCT-16:00 |
ElectricityPurchased:Plant | 912.01 | 0.00 | 08-JAN-10:30 | 107708.51 | 16-OCT-16:00 |
Cogeneration:ElectricityPurchased | 912.01 | 0.00 | 08-JAN-10:30 | 107708.51 | 16-OCT-16:00 |
General:Cogeneration:ElectricityPurchased | 912.01 | 0.00 | 08-JAN-10:30 | 107708.51 | 16-OCT-16:00 |
ElectricitySurplusSold:Facility | 2.97 | 0.00 | 01-JAN-00:10 | 13108.71 | 21-MAY-12:00 |
ElectricitySurplusSold:Plant | 2.97 | 0.00 | 01-JAN-00:10 | 13108.71 | 21-MAY-12:00 |
Cogeneration:ElectricitySurplusSold | 2.97 | 0.00 | 01-JAN-00:10 | 13108.71 | 21-MAY-12:00 |
General:Cogeneration:ElectricitySurplusSold | 2.97 | 0.00 | 01-JAN-00:10 | 13108.71 | 21-MAY-12:00 |
ElectricityNet:Facility | 909.04 | -13108.71 | 21-MAY-12:00 | 107708.51 | 16-OCT-16:00 |
ElectricityNet:Plant | 909.04 | -13108.71 | 21-MAY-12:00 | 107708.51 | 16-OCT-16:00 |
Cogeneration:ElectricityNet | 909.04 | -13108.71 | 21-MAY-12:00 | 107708.51 | 16-OCT-16:00 |
General:Cogeneration:ElectricityNet | 909.04 | -13108.71 | 21-MAY-12:00 | 107708.51 | 16-OCT-16:00 |
Heating:Electricity | 5.81 | 0.00 | 01-JAN-00:10 | 56601.18 | 02-JAN-07:10 |
General:Heating:Electricity | 5.81 | 0.00 | 01-JAN-00:10 | 56601.18 | 02-JAN-07:10 |
Fans:Electricity | 73.19 | 0.00 | 01-JAN-00:10 | 18063.41 | 16-OCT-16:00 |
General:Fans:Electricity | 73.19 | 0.00 | 01-JAN-00:10 | 18063.41 | 16-OCT-16:00 |
ExteriorLights:Electricity | 33.64 | 0.00 | 01-JAN-07:00 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 33.64 | 0.00 | 01-JAN-07:00 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 139.86 | 0.00 | 01-JAN-00:10 | 54929.39 | 16-OCT-11:00 |
General:Cooling:Electricity | 139.86 | 0.00 | 01-JAN-00:10 | 54929.39 | 16-OCT-11:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-17:10 |
WIRED_LTG_ELECTRICITY | 4.97 | 0.00 | 01-JAN-00:10 | 526.19 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 130.41 | 1886.44 | 01-JAN-00:10 | 34176.09 | 03-JAN-07:20 |
NaturalGas:HVAC | 5.16 | 0.00 | 01-JAN-00:10 | 25360.92 | 03-JAN-07:20 |
Heating:NaturalGas | 5.16 | 0.00 | 01-JAN-00:10 | 25360.92 | 03-JAN-07:20 |
General:Heating:NaturalGas | 5.16 | 0.00 | 01-JAN-00:10 | 25360.92 | 03-JAN-07:20 |
NaturalGas:Plant | 125.24 | 1886.44 | 01-JAN-00:10 | 9845.43 | 10-FEB-12:10 |
WaterSystems:NaturalGas | 125.24 | 1886.44 | 01-JAN-00:10 | 9845.43 | 10-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 125.24 | 1886.44 | 01-JAN-00:10 | 9845.43 | 10-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1613.10 | 0.00 | 01-JAN-00:10 | 328138.44 | 16-OCT-13:00 |
EnergyTransfer:Building | 941.30 | 0.00 | 01-JAN-00:10 | 145009.75 | 16-OCT-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 192.52 | 0.00 | 01-JAN-00:10 | 20234.99 | 02-OCT-08:00 |
Heating:EnergyTransfer | 11.49 | 0.00 | 01-JAN-00:10 | 45869.30 | 03-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 11.49 | 0.00 | 01-JAN-00:10 | 45869.30 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 929.82 | 0.00 | 01-JAN-00:10 | 145009.75 | 16-OCT-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 192.52 | 0.00 | 01-JAN-00:10 | 20234.99 | 02-OCT-08:00 |
General:Cooling:EnergyTransfer | 929.82 | 0.00 | 01-JAN-00:10 | 145009.75 | 16-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 192.52 | 0.00 | 01-JAN-00:10 | 20234.99 | 02-OCT-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.78 | 0.00 | 01-JAN-00:10 | 8908.84 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.42 | 0.00 | 01-JAN-00:10 | 4808.75 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.42 | 0.00 | 01-JAN-00:10 | 4808.75 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.35 | 0.00 | 01-JAN-00:10 | 8908.84 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.35 | 0.00 | 01-JAN-00:10 | 8908.84 | 16-OCT-13:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.20 | 0.00 | 01-JAN-00:10 | 4214.23 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.97 | 0.00 | 01-JAN-00:10 | 2270.99 | 02-JAN-11:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.97 | 0.00 | 01-JAN-00:10 | 2270.99 | 02-JAN-11:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.23 | 0.00 | 01-JAN-00:10 | 4214.23 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.23 | 0.00 | 01-JAN-00:10 | 4214.23 | 16-OCT-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.43 | 0.00 | 01-JAN-00:10 | 3878.06 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.59 | 0.00 | 01-JAN-00:10 | 1479.91 | 02-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.59 | 0.00 | 01-JAN-00:10 | 1479.91 | 02-JAN-11:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.84 | 0.00 | 01-JAN-00:10 | 3878.06 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.84 | 0.00 | 01-JAN-00:10 | 3878.06 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_MID | 143.10 | 0.00 | 01-JAN-00:10 | 16026.84 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2084.49 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2084.49 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 143.10 | 0.00 | 01-JAN-00:10 | 16026.84 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 143.10 | 0.00 | 01-JAN-00:10 | 16026.84 | 16-OCT-14:00 |
EnergyTransfer:Zone:CORE_TOP | 136.80 | 0.00 | 01-JAN-00:10 | 18032.04 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.04 | 0.00 | 01-JAN-00:10 | 8441.44 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.04 | 0.00 | 01-JAN-00:10 | 8441.44 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 136.76 | 0.00 | 01-JAN-00:10 | 18032.04 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 136.76 | 0.00 | 01-JAN-00:10 | 18032.04 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.36 | 0.00 | 01-JAN-00:10 | 5719.32 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.41 | 0.00 | 01-JAN-00:10 | 4830.66 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.41 | 0.00 | 01-JAN-00:10 | 4830.66 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.95 | 0.00 | 01-JAN-00:10 | 5719.32 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.95 | 0.00 | 01-JAN-00:10 | 5719.32 | 16-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.77 | 0.00 | 01-JAN-00:10 | 6444.74 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.12 | 0.00 | 01-JAN-00:10 | 3310.64 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.12 | 0.00 | 01-JAN-00:10 | 3310.64 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.65 | 0.00 | 01-JAN-00:10 | 6444.74 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.65 | 0.00 | 01-JAN-00:10 | 6444.74 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.97 | 0.00 | 01-JAN-00:10 | 11653.21 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.18 | 0.00 | 01-JAN-00:10 | 4219.63 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.18 | 0.00 | 01-JAN-00:10 | 4219.63 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.79 | 0.00 | 01-JAN-00:10 | 11653.21 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.79 | 0.00 | 01-JAN-00:10 | 11653.21 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.90 | 0.00 | 01-JAN-00:10 | 7655.97 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.23 | 0.00 | 01-JAN-00:10 | 3064.72 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.23 | 0.00 | 01-JAN-00:10 | 3064.72 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.66 | 0.00 | 01-JAN-00:10 | 7655.97 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.66 | 0.00 | 01-JAN-00:10 | 7655.97 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 25.21 | 0.00 | 01-JAN-00:10 | 4281.78 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2156.28 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2156.28 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 25.17 | 0.00 | 01-JAN-00:10 | 4281.78 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 25.17 | 0.00 | 01-JAN-00:10 | 4281.78 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.66 | 0.00 | 01-JAN-00:10 | 5570.44 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1058.38 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1058.38 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.66 | 0.00 | 01-JAN-00:10 | 5570.44 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.66 | 0.00 | 01-JAN-00:10 | 5570.44 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 41.88 | 0.00 | 01-JAN-00:10 | 11418.92 | 16-OCT-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.39 | 0.00 | 01-JAN-00:10 | 7070.84 | 30-MAR-06:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.39 | 0.00 | 01-JAN-00:10 | 7070.84 | 30-MAR-06:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.49 | 0.00 | 01-JAN-00:10 | 11418.92 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.49 | 0.00 | 01-JAN-00:10 | 11418.92 | 16-OCT-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.89 | 0.00 | 01-JAN-00:10 | 6175.64 | 16-OCT-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1277.17 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1277.17 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.88 | 0.00 | 01-JAN-00:10 | 6175.64 | 16-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.88 | 0.00 | 01-JAN-00:10 | 6175.64 | 16-OCT-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.99 | 0.00 | 01-JAN-00:10 | 5174.94 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2355.94 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2355.94 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.95 | 0.00 | 01-JAN-00:10 | 5174.94 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.95 | 0.00 | 01-JAN-00:10 | 5174.94 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.56 | 0.00 | 01-JAN-00:10 | 6409.70 | 16-OCT-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1336.66 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1336.66 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.55 | 0.00 | 01-JAN-00:10 | 6409.70 | 16-OCT-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.55 | 0.00 | 01-JAN-00:10 | 6409.70 | 16-OCT-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.25 | 0.00 | 01-JAN-00:10 | 10634.83 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 2085.09 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 2085.09 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.24 | 0.00 | 01-JAN-00:10 | 10634.83 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.24 | 0.00 | 01-JAN-00:10 | 10634.83 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.03 | 0.00 | 01-JAN-00:10 | 7181.41 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1497.37 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1497.37 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.01 | 0.00 | 01-JAN-00:10 | 7181.41 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.01 | 0.00 | 01-JAN-00:10 | 7181.41 | 29-SEP-15:30 |
PlantLoopHeatingDemand:Facility | 44.91 | 0.00 | 01-JAN-00:10 | 5341.86 | 06-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 44.91 | 0.00 | 01-JAN-00:10 | 5341.86 | 06-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 44.91 | 0.00 | 01-JAN-00:10 | 5341.86 | 06-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 44.91 | 0.00 | 01-JAN-00:10 | 5341.86 | 06-FEB-12:10 |
EnergyTransfer:HVAC | 626.88 | 0.00 | 01-JAN-00:10 | 206894.31 | 31-JUL-16:00 |
HeatingCoils:EnergyTransfer | 9.94 | 0.00 | 01-JAN-00:10 | 75338.19 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 616.94 | 0.00 | 01-JAN-00:10 | 206894.31 | 31-JUL-16:00 |
EnergyTransfer:Plant | 44.91 | 0.00 | 01-JAN-00:10 | 5341.86 | 06-FEB-12:10 |
WaterSystems:EnergyTransfer | 44.91 | 0.00 | 01-JAN-00:10 | 5341.86 | 06-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 44.91 | 0.00 | 01-JAN-00:10 | 5341.86 | 06-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -192.523 | 0.000 | 0.000 | 32.736 | 42.156 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -60.852 |
CORE_MID | 0.000 | 0.000 | 0.001 | -143.102 | 0.000 | 0.000 | 33.004 | 42.156 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.484 |
CORE_TOP | 0.000 | 0.000 | 0.041 | -136.763 | 0.000 | 0.000 | 33.439 | 42.156 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.298 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.412 | -28.953 | 0.000 | 0.000 | 7.204 | 5.165 | 24.333 | 13.696 | 0.000 | 0.029 | 4.745 | 0.000 | -23.796 | 0.000 | -2.835 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.116 | -28.655 | 0.000 | 0.000 | 4.453 | 3.254 | 15.404 | 29.367 | 0.000 | 0.016 | 0.002 | 0.000 | -15.598 | 0.000 | -1.991 | -6.366 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.176 | -51.791 | 0.000 | 0.000 | 7.043 | 5.096 | 24.332 | 57.588 | 0.000 | 0.023 | 0.000 | 0.000 | -24.249 | 0.000 | -3.084 | -15.134 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.234 | -30.663 | 0.000 | 0.000 | 4.524 | 3.240 | 15.403 | 33.397 | 0.000 | 0.018 | 0.000 | 0.000 | -16.273 | 0.000 | -2.011 | -7.869 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.038 | -25.169 | 0.000 | 0.000 | 7.173 | 5.154 | 24.333 | 14.073 | 0.000 | 0.017 | 0.453 | 0.000 | -24.502 | 0.000 | -1.570 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.003 | -25.661 | 0.000 | 0.000 | 4.425 | 3.250 | 15.404 | 29.538 | 0.000 | 0.009 | 0.000 | 0.000 | -16.430 | 0.000 | -1.127 | -9.409 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.390 | -39.494 | 0.000 | 0.000 | 7.102 | 5.092 | 24.332 | 58.225 | 0.000 | 0.346 | 0.003 | 0.000 | -25.517 | 0.000 | -18.470 | -14.005 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.008 | -26.879 | 0.000 | 0.000 | 4.462 | 3.235 | 15.403 | 33.715 | 0.000 | 0.010 | 0.000 | 0.000 | -17.288 | 0.000 | -1.146 | -11.520 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.041 | -29.946 | 0.000 | 0.000 | 7.099 | 5.165 | 24.333 | 13.410 | 0.000 | 0.024 | 7.731 | 0.000 | -25.334 | 0.000 | -2.524 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.011 | -27.551 | 0.000 | 0.000 | 3.261 | 3.254 | 15.404 | 29.065 | 0.000 | 0.013 | 0.000 | 0.000 | -16.508 | 0.000 | -1.770 | -5.179 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.014 | -53.241 | 0.000 | 0.000 | 6.977 | 5.096 | 24.332 | 57.373 | 0.000 | 0.019 | 0.001 | 0.000 | -25.630 | 0.000 | -2.719 | -12.221 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.022 | -31.009 | 0.000 | 0.000 | 4.461 | 3.240 | 15.403 | 33.288 | 0.000 | 0.015 | 0.000 | 0.000 | -17.280 | 0.000 | -1.783 | -6.357 |
TOPFLOOR_PLENUM | 5.423 | -29.353 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.025 | 28.513 | 0.000 | 0.000 | 0.000 | -4.608 | -0.000 |
MIDFLOOR_PLENUM | 1.968 | -12.228 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.032 | 14.712 | 0.000 | 0.000 | 0.000 | -4.485 | -0.000 |
FIRSTFLOOR_PLENUM | 0.589 | -16.838 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.023 | 19.835 | 0.000 | 0.000 | 0.000 | -3.611 | -0.000 |
Total Facility | 7.981 | -58.418 | 3.508 | -871.401 | 0.000 | 0.000 | 167.362 | 176.710 | 647.750 | 402.737 | 0.000 | 0.617 | 75.997 | 0.000 | -248.405 | 0.000 | -53.734 | -250.697 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-OCT-06:03 | 0.00 | 0.00 | 0.00 | -31670.71 | 0.00 | 0.00 | 690.87 | 1232.21 | 6044.02 | 0.00 | 0.00 | 0.00 | 23703.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-06:03 | 0.00 | 0.00 | 0.00 | -26104.75 | 0.00 | 0.00 | 699.57 | 1232.21 | 3025.92 | 0.00 | 0.00 | 0.00 | 21147.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-OCT-06:03 | 0.00 | 0.00 | 0.00 | -19007.79 | 0.00 | 0.00 | 717.85 | 1232.21 | 3025.92 | 0.00 | 0.00 | 0.00 | 14031.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | -5720.10 | 0.00 | 0.00 | 757.17 | 371.72 | 1435.25 | 2522.10 | 0.00 | 105.83 | 528.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-08:32 | 0.00 | 0.00 | 0.00 | -11109.34 | 0.00 | 0.00 | 16.07 | 13.07 | 302.86 | 7302.08 | 0.00 | 0.00 | 3509.68 | 0.00 | -0.00 | 0.00 | -34.43 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:42 | 0.00 | 0.00 | 0.00 | -14419.53 | 0.00 | 0.00 | 21.53 | 20.65 | 478.41 | 11306.40 | 0.00 | 212.87 | 2379.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-15:52 | 0.00 | 0.00 | 0.00 | -12939.75 | 0.00 | 0.00 | 15.12 | 13.07 | 302.86 | 7290.79 | 0.00 | 0.00 | 5394.94 | 0.00 | -0.00 | 0.00 | -77.02 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -4282.03 | 0.00 | 0.00 | 737.21 | 371.72 | 1435.25 | 2845.15 | 0.00 | 68.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1176.02 |
PERIMETER_BOT_ZN_2 | 15-OCT-08:32 | 0.00 | 0.00 | 0.00 | -9041.38 | 0.00 | 0.00 | 17.15 | 13.07 | 302.86 | 7754.11 | 0.00 | 64.69 | 889.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 19-NOV-13:13 | 0.00 | 0.00 | 0.00 | -11604.14 | 0.00 | 0.00 | 25.56 | 20.65 | 478.41 | 11545.53 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.83 | -442.18 |
PERIMETER_BOT_ZN_4 | 15-OCT-15:11 | 0.00 | 0.00 | 0.00 | -9810.76 | 0.00 | 0.00 | 16.18 | 13.07 | 302.86 | 8209.63 | 0.00 | 43.50 | 1225.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -5175.24 | 0.00 | 0.00 | 737.21 | 371.72 | 1435.25 | 2823.60 | 0.00 | 107.35 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -299.89 |
PERIMETER_MID_ZN_2 | 23-JUL-08:23 | 0.00 | 0.00 | 0.00 | -10919.55 | 0.00 | 0.00 | 16.10 | 13.07 | 302.86 | 7505.46 | 0.00 | 0.00 | 3106.10 | 0.00 | -0.00 | 0.00 | -24.03 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:52 | 0.00 | 0.00 | 0.00 | -13194.34 | 0.00 | 0.00 | 25.13 | 20.65 | 478.41 | 10207.46 | 0.00 | 0.00 | 2558.08 | 0.00 | -0.00 | 0.00 | -95.39 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-16:22 | 0.00 | 0.00 | 0.00 | -11675.96 | 0.00 | 0.00 | 15.86 | 13.07 | 302.86 | 7467.51 | 0.00 | 0.00 | 3991.79 | 0.00 | -0.00 | 0.00 | -115.13 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-13:05 | 0.00 | -8918.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.34 | 8792.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -4214.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 4183.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -3878.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 3854.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-14:05 | 0.00 | -16072.95 | 0.00 | -129916.56 | 0.00 | 0.00 | 17583.94 | 14732.14 | 37678.39 | 58118.34 | 0.00 | 1465.46 | 16411.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:03 | 0.00 | 0.00 | 8338.12 | 0.00 | 0.00 | 0.00 | 887.89 | 1232.21 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13484.14 |
CORE_TOP | 02-JAN-07:03 | 0.00 | 0.00 | 21576.62 | 0.00 | 0.00 | 0.00 | 916.92 | 1232.21 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26751.67 |
PERIMETER_TOP_ZN_3 | 03-JAN-06:11 | 0.00 | 0.00 | 7787.82 | 0.00 | 0.00 | 0.00 | 105.81 | 86.59 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2029.70 | 0.00 | -47.43 | -6540.97 |
PERIMETER_TOP_ZN_2 | 03-JAN-06:11 | 0.00 | 0.00 | 6513.86 | 0.00 | 0.00 | 0.00 | 67.05 | 54.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1352.19 | 0.00 | -31.90 | -5655.45 |
PERIMETER_TOP_ZN_1 | 03-JAN-06:11 | 0.00 | 0.00 | 10036.13 | 0.00 | 0.00 | 0.00 | 104.21 | 86.59 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2067.40 | 0.00 | -49.39 | -8748.01 |
PERIMETER_TOP_ZN_4 | 03-JAN-06:11 | 0.00 | 0.00 | 6306.32 | 0.00 | 0.00 | 0.00 | 66.69 | 54.81 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1351.79 | 0.00 | -32.20 | -5447.64 |
PERIMETER_BOT_ZN_3 | 03-JAN-06:11 | 0.00 | 0.00 | 5562.24 | 0.00 | 0.00 | 0.00 | 98.81 | 86.59 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2260.45 | 0.00 | -28.22 | -4096.86 |
PERIMETER_BOT_ZN_2 | 02-JAN-07:03 | 0.00 | 0.00 | 4233.60 | 0.00 | 0.00 | 0.00 | 121.68 | 126.07 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -271.99 | 0.00 | -28.52 | -4584.66 |
PERIMETER_BOT_ZN_1 | 03-JAN-07:10 | 0.00 | 0.00 | 7212.46 | 0.00 | 0.00 | 0.00 | 193.30 | 185.17 | 637.88 | 49.98 | 0.00 | 0.00 | 4344.85 | 0.00 | -0.00 | 0.00 | -12623.64 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-MAR-06:03 | 0.00 | 0.00 | 4260.22 | 0.00 | 0.00 | 0.00 | 121.37 | 159.68 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1251.16 | 0.00 | -53.63 | -3640.30 |
PERIMETER_MID_ZN_3 | 03-JAN-06:11 | 0.00 | 0.00 | 6319.06 | 0.00 | 0.00 | 0.00 | 100.06 | 86.59 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2233.37 | 0.00 | -43.46 | -4866.77 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 4796.67 | 0.00 | 0.00 | 0.00 | 62.69 | 54.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -860.10 | 0.00 | -42.49 | -4415.39 |
PERIMETER_MID_ZN_1 | 03-JAN-07:03 | 0.00 | 0.00 | 6840.53 | 0.00 | 0.00 | 0.00 | 193.30 | 188.98 | 637.88 | 110.31 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12.17 | -7958.83 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 4821.91 | 0.00 | 0.00 | 0.00 | 62.85 | 54.81 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -865.33 | 0.00 | -42.19 | -4435.85 |
TOPFLOOR_PLENUM | 03-JAN-07:03 | 6551.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18.90 | -6533.02 |
MIDFLOOR_PLENUM | 25-DEC-13:02 | 4068.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.09 | -4045.12 |
FIRSTFLOOR_PLENUM | 25-DEC-13:02 | 2623.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -32.45 | -2590.67 |
Total Facility | 02-JAN-07:03 | -1254.69 | 5021.67 | 99510.38 | -5021.67 | 0.00 | 0.00 | 4523.72 | 5832.01 | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8678.27 | 0.00 | -8495.29 | -109783.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.5732 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.0525 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.4883 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.8383 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.8007 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4452 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.2866 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0764 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2441 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0755 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4004 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0758 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3349 | 2.3349 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9353 | 1.9353 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0143 | 2.0143 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5970 | 0.5970 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6454 | 0.6454 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8143 | 0.8143 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7297 | 0.7297 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4623 | 0.4623 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5410 | 0.5410 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6525 | 0.6525 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5824 | 0.5824 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5183 | 0.5183 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6349 | 0.6349 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7314 | 0.7314 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6684 | 0.6684 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.5732 | 4.0525 | 4.5732 | 1.0764 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.4883 | 3.8383 | 4.4883 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.8007 | 4.4452 | 4.8007 | 1.0758 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1675 | 1.1675 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9676 | 0.9676 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0071 | 1.0071 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2985 | 0.2985 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3227 | 0.3227 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4072 | 0.4072 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3648 | 0.3648 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2311 | 0.2311 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2705 | 0.2705 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3263 | 0.3263 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2912 | 0.2912 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2591 | 0.2591 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3174 | 0.3174 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3657 | 0.3657 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3342 | 0.3342 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.2866 | 1.0764 | 1.0764 | 1.0764 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2441 | 1.0755 | 1.0755 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4004 | 1.0758 | 1.0758 | 1.0758 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 19.00 |
Number of hours cooling loads not met | 138.67 |
Number of hours not met | 157.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 5.81 | 56601.18 | 5.16 | 25360.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 139.86 | 54929.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 176.71 | 18725.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 33.64 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.63 | 830.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 73.19 | 18063.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 125.24 | 9845.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1088.73 |
Natural Gas | 0.00 | 130.41 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1219.14 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 187.49 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 35.47 |
Space Heating | 1.17 |
Space Cooling | 28.07 |
Fans (All) | 14.69 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 218.53 |
Subtotal | 218.53 |
Natural Gas [MJ/m2] | |
Space Heating | 1.04 |
Service Water Heating | 25.14 |
Miscellaneous (All) | 26.17 |
Subtotal | 26.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.49 |
Space Heating | 0.90 |
Space Cooling | 11.47 |
Fans (All) | 6.00 |
Service Water Heating | 10.27 |
Receptacle Equipment | 53.13 |
Miscellaneous | 3.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2115. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1058. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8699.67 | 60.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8673.00 | 87.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8700.17 | 59.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8687.50 | 72.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8673.83 | 86.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8661.67 | 98.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8661.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 98.33 | 0.00 | 0.00 | 0.00 |
Average | 8723.86 | 36.14 | 0.00 | 0.00 | 0.00 |
Sum | 157029.50 | 650.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8172.50 | 587.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8387.33 | 372.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8678.17 | 81.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8695.17 | 64.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8583.83 | 176.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8610.50 | 149.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8523.00 | 237.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8553.33 | 206.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8573.17 | 186.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8392.17 | 367.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8668.33 | 91.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8497.83 | 262.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8545.17 | 214.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8387.50 | 372.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8176.83 | 583.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8676.83 | 83.17 | 0.00 | 0.00 | 0.00 |
Min | 8172.50 | 33.00 | 0.00 | 0.00 | 0.00 |
Max | 8727.00 | 587.50 | 0.00 | 0.00 | 0.00 |
Average | 8529.96 | 230.04 | 0.00 | 0.00 | 0.00 |
Sum | 153539.33 | 4140.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127989.00 | 315.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128160.33 | 143.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128255.67 | 48.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14008.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24626.00 | 283.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24907.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128255.67 | 315.00 | 0.00 | 0.00 | 0.00 |
Average | 34098.89 | 44.44 | 0.00 | 0.00 | 0.00 |
Sum | 613780.00 | 800.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132734E+11 | 15654.54 | 20-JAN-16:20 | 16.67 | 14.61 | 0.198038E+10 | 2606.75 | 10-JAN-14:09 | 16.67 | 14.61 |
February | 0.123075E+11 | 15320.12 | 03-FEB-17:00 | 18.00 | 9.93 | 0.179959E+10 | 2606.82 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.142316E+11 | 15685.61 | 24-MAR-16:00 | 18.00 | 14.96 | 0.215009E+10 | 2606.72 | 01-MAR-14:09 | 18.00 | 14.96 |
April | 0.149687E+11 | 19661.81 | 28-APR-06:02 | 14.17 | 12.31 | 0.191261E+10 | 2606.77 | 13-APR-09:00 | 14.17 | 12.31 |
May | 0.165216E+11 | 19472.88 | 05-MAY-06:03 | 16.17 | 14.82 | 0.207361E+10 | 2606.81 | 03-MAY-13:00 | 16.17 | 14.82 |
June | 0.177295E+11 | 22276.39 | 28-JUN-06:03 | 16.03 | 15.93 | 0.206824E+10 | 2606.65 | 23-JUN-09:20 | 16.03 | 15.93 |
July | 0.185529E+11 | 29984.77 | 17-JUL-06:02 | 15.12 | 14.45 | 0.192228E+10 | 2606.65 | 13-JUL-09:20 | 15.12 | 14.45 |
August | 0.201449E+11 | 29908.95 | 21-AUG-06:03 | 16.58 | 15.13 | 0.215789E+10 | 2606.63 | 23-AUG-09:20 | 21.67 | 16.23 |
September | 0.175081E+11 | 27578.57 | 05-SEP-06:03 | 16.00 | 14.76 | 0.191601E+10 | 2606.67 | 21-SEP-09:39 | 20.33 | 18.35 |
October | 0.182373E+11 | 31678.14 | 02-OCT-06:03 | 19.17 | 17.72 | 0.199179E+10 | 2606.75 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.150644E+11 | 22255.45 | 01-NOV-06:02 | 11.83 | 10.47 | 0.197034E+10 | 2606.86 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.139817E+11 | 15572.52 | 07-DEC-16:20 | 17.33 | 14.71 | 0.191576E+10 | 2607.00 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.192522E+12 | 0.238586E+11 | ||||||||
Minimum of Months | 0.123075E+11 | 15320.12 | 11.83 | 9.93 | 0.179959E+10 | 2606.63 | 14.17 | 9.93 | ||
Maximum of Months | 0.201449E+11 | 31678.14 | 19.17 | 17.72 | 0.215789E+10 | 2607.00 | 22.00 | 18.35 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.986207E+09 | 4658.62 | 18-JAN-15:05 | 22.83 | 14.90 | 0.00 | 0.00 | 01-JAN-00:10 | 22.83 | 14.90 |
February | 0.902042E+09 | 4308.76 | 01-FEB-14:05 | 19.00 | 15.70 | 0.00 | 0.00 | 01-FEB-00:10 | 19.00 | 15.70 |
March | 0.131655E+10 | 5888.14 | 23-MAR-14:20 | 22.67 | 17.32 | 0.00 | 0.00 | 01-MAR-00:10 | 22.67 | 17.32 |
April | 0.262953E+10 | 7508.18 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.257683E+10 | 6669.83 | 03-MAY-13:30 | 23.50 | 15.91 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 15.91 |
June | 0.352810E+10 | 6586.55 | 30-JUN-13:05 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.450989E+10 | 8057.49 | 31-JUL-13:30 | 27.50 | 21.02 | 0.00 | 0.00 | 01-JUL-00:10 | 27.50 | 21.02 |
August | 0.471802E+10 | 7778.47 | 14-AUG-13:05 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.323653E+10 | 8772.19 | 29-SEP-14:05 | 33.83 | 17.79 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 17.79 |
October | 0.275906E+10 | 8917.99 | 16-OCT-13:05 | 33.75 | 16.65 | 0.00 | 0.00 | 01-OCT-00:10 | 33.75 | 16.65 |
November | 0.119060E+10 | 4142.62 | 10-NOV-14:05 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.999240E+09 | 4161.49 | 19-DEC-14:05 | 22.83 | 9.79 | 0.00 | 0.00 | 01-DEC-00:10 | 22.83 | 9.79 |
Annual Sum or Average | 0.293526E+11 | 0.00 | ||||||||
Minimum of Months | 0.902042E+09 | 4142.62 | 19.00 | 9.79 | 0.00 | 0.00 | 19.00 | 9.79 | ||
Maximum of Months | 0.471802E+10 | 8917.99 | 33.83 | 21.02 | 0.00 | 0.00 | 33.83 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325522E+09 | 1190.26 | 19-JAN-15:30 | 19.50 | 14.95 | 0.00 | 0.00 | 01-JAN-00:10 | 19.50 | 14.95 |
February | 0.318943E+09 | 1066.32 | 03-FEB-16:10 | 20.50 | 10.05 | 0.00 | 0.00 | 01-FEB-00:10 | 20.50 | 10.05 |
March | 0.386673E+09 | 1595.44 | 23-MAR-16:00 | 21.00 | 17.19 | 0.00 | 0.00 | 01-MAR-00:10 | 21.00 | 17.19 |
April | 0.833690E+09 | 2078.29 | 26-APR-15:50 | 22.17 | 16.38 | 0.00 | 0.00 | 01-APR-00:10 | 22.17 | 16.38 |
May | 0.916749E+09 | 1981.95 | 03-MAY-15:50 | 21.17 | 15.06 | 0.00 | 0.00 | 01-MAY-00:10 | 21.17 | 15.06 |
June | 0.145846E+10 | 2336.00 | 26-JUN-16:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.00 | 17.40 |
July | 0.201159E+10 | 3042.30 | 31-JUL-15:20 | 25.33 | 20.29 | 0.00 | 0.00 | 01-JUL-00:10 | 25.33 | 20.29 |
August | 0.217954E+10 | 2889.78 | 14-AUG-15:50 | 25.17 | 18.63 | 0.00 | 0.00 | 01-AUG-00:10 | 25.17 | 18.63 |
September | 0.153565E+10 | 3406.41 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.147131E+10 | 4214.23 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.454152E+09 | 1112.90 | 10-NOV-15:20 | 18.67 | 15.74 | 0.00 | 0.00 | 01-NOV-00:10 | 18.67 | 15.74 |
December | 0.335826E+09 | 1223.17 | 07-DEC-15:40 | 18.33 | 15.07 | 0.00 | 0.00 | 01-DEC-00:10 | 18.33 | 15.07 |
Annual Sum or Average | 0.122281E+11 | 0.00 | ||||||||
Minimum of Months | 0.318943E+09 | 1066.32 | 18.33 | 10.05 | 0.00 | 0.00 | 18.33 | 10.05 | ||
Maximum of Months | 0.217954E+10 | 4214.23 | 32.00 | 20.29 | 0.00 | 0.00 | 32.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.668959E+09 | 1776.21 | 18-JAN-15:30 | 22.50 | 15.11 | 0.00 | 0.00 | 01-JAN-00:10 | 22.50 | 15.11 |
February | 0.633861E+09 | 1554.88 | 03-FEB-16:10 | 20.50 | 10.05 | 0.00 | 0.00 | 01-FEB-00:10 | 20.50 | 10.05 |
March | 0.676225E+09 | 1892.59 | 23-MAR-16:00 | 21.00 | 17.19 | 0.00 | 0.00 | 01-MAR-00:10 | 21.00 | 17.19 |
April | 0.118156E+10 | 2244.33 | 26-APR-15:40 | 22.33 | 16.35 | 0.00 | 0.00 | 01-APR-00:10 | 22.33 | 16.35 |
May | 0.130484E+10 | 2089.06 | 04-MAY-15:10 | 22.00 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 22.00 | 16.32 |
June | 0.177551E+10 | 2357.97 | 26-JUN-16:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.00 | 17.40 |
July | 0.231628E+10 | 3108.14 | 31-JUL-15:10 | 25.67 | 20.38 | 0.00 | 0.00 | 01-JUL-00:10 | 25.67 | 20.38 |
August | 0.256562E+10 | 3014.38 | 14-AUG-15:50 | 25.17 | 18.63 | 0.00 | 0.00 | 01-AUG-00:10 | 25.17 | 18.63 |
September | 0.196786E+10 | 3350.72 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.199705E+10 | 3878.06 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.988805E+09 | 1615.65 | 01-NOV-06:07 | 11.83 | 10.47 | 0.00 | 0.00 | 01-NOV-00:10 | 11.83 | 10.47 |
December | 0.760918E+09 | 1744.74 | 19-DEC-16:00 | 21.00 | 8.28 | 0.00 | 0.00 | 01-DEC-00:10 | 21.00 | 8.28 |
Annual Sum or Average | 0.168375E+11 | 0.00 | ||||||||
Minimum of Months | 0.633861E+09 | 1554.88 | 11.83 | 8.28 | 0.00 | 0.00 | 11.83 | 8.28 | ||
Maximum of Months | 0.256562E+10 | 3878.06 | 32.00 | 20.38 | 0.00 | 0.00 | 32.00 | 20.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.944309E+10 | 11497.78 | 20-JAN-16:20 | 16.67 | 14.61 | 0.192118E+10 | 2606.65 | 27-JAN-14:20 | 16.67 | 12.79 |
February | 0.883672E+10 | 11215.56 | 03-FEB-17:00 | 18.00 | 9.93 | 0.175888E+10 | 2606.84 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.101779E+11 | 11867.81 | 24-MAR-16:00 | 18.00 | 14.96 | 0.210281E+10 | 2606.66 | 15-MAR-09:20 | 18.00 | 14.96 |
April | 0.113701E+11 | 12847.23 | 27-APR-16:00 | 18.00 | 14.37 | 0.189556E+10 | 2606.72 | 13-APR-09:00 | 18.00 | 14.37 |
May | 0.123981E+11 | 12907.27 | 04-MAY-16:00 | 22.00 | 15.83 | 0.205931E+10 | 2606.77 | 03-MAY-13:00 | 22.00 | 15.83 |
June | 0.135831E+11 | 13429.98 | 26-JUN-16:00 | 22.00 | 17.40 | 0.206082E+10 | 2606.64 | 23-JUN-09:20 | 22.00 | 17.40 |
July | 0.145533E+11 | 18008.96 | 31-JUL-06:03 | 17.17 | 16.43 | 0.191805E+10 | 2606.65 | 13-JUL-09:20 | 17.17 | 16.43 |
August | 0.155552E+11 | 15227.47 | 21-AUG-06:03 | 16.58 | 15.13 | 0.215386E+10 | 2606.63 | 02-AUG-09:20 | 16.58 | 15.13 |
September | 0.131857E+11 | 14168.95 | 29-SEP-16:00 | 32.00 | 16.86 | 0.190881E+10 | 2606.66 | 21-SEP-09:20 | 32.00 | 16.86 |
October | 0.136320E+11 | 26109.96 | 02-OCT-06:03 | 19.17 | 17.72 | 0.198285E+10 | 2606.70 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.105035E+11 | 11927.26 | 01-NOV-16:00 | 16.80 | 12.58 | 0.194824E+10 | 2606.80 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.986329E+10 | 11447.02 | 07-DEC-16:20 | 17.33 | 14.71 | 0.187994E+10 | 2606.92 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.143102E+12 | 0.235903E+11 | ||||||||
Minimum of Months | 0.883672E+10 | 11215.56 | 16.58 | 9.93 | 0.175888E+10 | 2606.63 | 16.58 | 9.93 | ||
Maximum of Months | 0.155552E+11 | 26109.96 | 32.00 | 17.72 | 0.215386E+10 | 2606.92 | 32.00 | 17.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.835315E+10 | 11144.54 | 19-JAN-15:50 | 19.17 | 14.83 | 0.184603E+10 | 2606.66 | 27-JAN-14:20 | 16.67 | 12.79 |
February | 0.797314E+10 | 11063.34 | 02-FEB-16:20 | 17.67 | 13.13 | 0.169706E+10 | 2606.85 | 01-FEB-14:09 | 17.67 | 13.13 |
March | 0.940153E+10 | 12571.95 | 24-MAR-15:30 | 18.00 | 15.20 | 0.202678E+10 | 2606.65 | 09-MAR-14:20 | 18.00 | 15.20 |
April | 0.110540E+11 | 14223.61 | 27-APR-15:20 | 18.80 | 14.83 | 0.187091E+10 | 2606.70 | 13-APR-13:00 | 18.80 | 14.83 |
May | 0.120689E+11 | 14429.36 | 03-MAY-15:20 | 21.67 | 15.26 | 0.203903E+10 | 2606.78 | 03-MAY-13:00 | 21.67 | 15.26 |
June | 0.137232E+11 | 15166.80 | 26-JUN-14:00 | 22.00 | 17.40 | 0.205113E+10 | 2606.65 | 27-JUN-09:20 | 23.00 | 18.04 |
July | 0.150054E+11 | 16264.76 | 31-JUL-14:00 | 27.00 | 20.84 | 0.191251E+10 | 2606.64 | 13-JUL-09:20 | 27.00 | 20.84 |
August | 0.158338E+11 | 15838.79 | 14-AUG-14:00 | 25.00 | 20.20 | 0.214692E+10 | 2606.64 | 18-AUG-13:20 | 25.33 | 20.30 |
September | 0.127841E+11 | 15923.79 | 29-SEP-14:40 | 33.33 | 17.61 | 0.189672E+10 | 2606.66 | 13-SEP-09:20 | 33.33 | 17.61 |
October | 0.127318E+11 | 19007.13 | 02-OCT-06:03 | 19.17 | 17.72 | 0.196348E+10 | 2606.70 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.919584E+10 | 11352.88 | 01-NOV-16:00 | 16.80 | 12.58 | 0.189715E+10 | 2606.79 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.863835E+10 | 11172.05 | 07-DEC-16:00 | 18.00 | 14.97 | 0.180781E+10 | 2606.90 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.136763E+12 | 0.231555E+11 | ||||||||
Minimum of Months | 0.797314E+10 | 11063.34 | 16.80 | 12.58 | 0.169706E+10 | 2606.64 | 16.67 | 10.62 | ||
Maximum of Months | 0.158338E+11 | 19007.13 | 33.33 | 20.84 | 0.214692E+10 | 2606.90 | 33.33 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140299E+10 | 2470.73 | 18-JAN-14:50 | 23.27 | 14.80 | 0.364161E+09 | 549.50 | 20-JAN-14:20 | 17.00 | 14.51 |
February | 0.137483E+10 | 2165.11 | 03-FEB-15:00 | 23.00 | 8.84 | 0.337729E+09 | 549.54 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.169362E+10 | 2811.29 | 23-MAR-15:20 | 21.67 | 17.34 | 0.402996E+09 | 549.50 | 09-MAR-14:20 | 21.67 | 17.34 |
April | 0.224684E+10 | 3961.80 | 26-APR-14:00 | 26.00 | 16.74 | 0.383650E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.264544E+10 | 4262.13 | 04-MAY-13:50 | 23.00 | 16.67 | 0.422367E+09 | 549.53 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.335576E+10 | 4132.10 | 26-JUN-16:00 | 22.00 | 17.40 | 0.429537E+09 | 549.50 | 27-JUN-09:20 | 23.00 | 18.04 |
July | 0.380854E+10 | 4791.50 | 31-JUL-14:00 | 27.00 | 20.84 | 0.401885E+09 | 549.50 | 13-JUL-09:20 | 27.00 | 20.84 |
August | 0.378913E+10 | 4558.64 | 18-AUG-15:00 | 27.00 | 20.85 | 0.449819E+09 | 549.50 | 18-AUG-13:20 | 27.00 | 20.85 |
September | 0.282586E+10 | 5481.53 | 29-SEP-13:50 | 34.33 | 17.92 | 0.394021E+09 | 549.50 | 13-SEP-09:20 | 34.33 | 17.92 |
October | 0.273069E+10 | 5719.82 | 16-OCT-13:10 | 33.75 | 16.65 | 0.405113E+09 | 549.50 | 31-OCT-13:20 | 26.67 | 16.70 |
November | 0.161044E+10 | 2247.83 | 10-NOV-14:10 | 19.83 | 15.69 | 0.380289E+09 | 549.52 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.146846E+10 | 2475.56 | 05-DEC-15:00 | 25.00 | 13.22 | 0.355278E+09 | 549.50 | 04-DEC-14:20 | 25.00 | 13.22 |
Annual Sum or Average | 0.289526E+11 | 0.472684E+10 | ||||||||
Minimum of Months | 0.137483E+10 | 2165.11 | 19.83 | 8.84 | 0.337729E+09 | 549.50 | 17.00 | 8.84 | ||
Maximum of Months | 0.380854E+10 | 5719.82 | 34.33 | 20.85 | 0.449819E+09 | 549.54 | 34.33 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123561E+10 | 3045.84 | 20-JAN-10:00 | 19.00 | 14.77 | 0.250779E+09 | 347.88 | 27-JAN-14:20 | 16.67 | 12.79 |
February | 0.124134E+10 | 2848.18 | 02-FEB-10:10 | 17.17 | 12.19 | 0.226544E+09 | 347.90 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.160702E+10 | 4661.32 | 23-MAR-09:30 | 20.50 | 15.62 | 0.271180E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.257570E+10 | 7296.51 | 30-APR-09:43 | 24.50 | 16.21 | 0.250734E+09 | 347.91 | 13-APR-09:00 | 24.50 | 16.21 |
May | 0.260048E+10 | 4991.64 | 04-MAY-09:30 | 21.00 | 15.49 | 0.272158E+09 | 347.90 | 03-MAY-13:00 | 21.00 | 15.49 |
June | 0.322018E+10 | 7447.58 | 18-JUN-08:23 | 20.50 | 16.09 | 0.273434E+09 | 347.88 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.394665E+10 | 11112.49 | 23-JUL-08:32 | 24.33 | 19.42 | 0.255767E+09 | 347.88 | 13-JUL-09:39 | 24.33 | 19.42 |
August | 0.414619E+10 | 7586.00 | 20-AUG-09:13 | 22.00 | 18.63 | 0.286738E+09 | 347.88 | 31-AUG-09:09 | 23.00 | 18.43 |
September | 0.282030E+10 | 7798.20 | 10-SEP-08:43 | 21.50 | 17.28 | 0.252148E+09 | 347.89 | 13-SEP-09:09 | 22.17 | 18.15 |
October | 0.256071E+10 | 10970.27 | 15-OCT-08:43 | 32.33 | 15.60 | 0.262159E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.142860E+10 | 2615.55 | 01-NOV-09:30 | 15.00 | 12.66 | 0.254521E+09 | 347.90 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.127215E+10 | 3001.42 | 05-DEC-09:50 | 25.67 | 12.88 | 0.243692E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.286549E+11 | 0.309985E+10 | ||||||||
Minimum of Months | 0.123561E+10 | 2615.55 | 15.00 | 12.19 | 0.226544E+09 | 347.88 | 16.67 | 10.63 | ||
Maximum of Months | 0.414619E+10 | 11112.49 | 32.33 | 19.42 | 0.286738E+09 | 347.91 | 24.50 | 19.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456623E+10 | 14137.21 | 22-JAN-13:53 | 18.00 | 12.36 | 0.403289E+09 | 549.75 | 18-JAN-14:00 | 18.00 | 12.36 |
February | 0.337662E+10 | 11401.77 | 20-FEB-13:43 | 17.00 | 10.89 | 0.360278E+09 | 549.76 | 03-FEB-14:50 | 17.00 | 10.89 |
March | 0.333109E+10 | 9338.03 | 19-MAR-13:13 | 19.67 | 15.00 | 0.423805E+09 | 549.72 | 23-MAR-13:00 | 23.00 | 17.27 |
April | 0.372890E+10 | 7488.87 | 26-APR-13:10 | 26.83 | 17.07 | 0.389031E+09 | 549.52 | 13-APR-13:50 | 26.83 | 17.07 |
May | 0.309179E+10 | 5677.85 | 04-MAY-12:40 | 23.33 | 16.64 | 0.422061E+09 | 549.54 | 03-MAY-13:00 | 23.33 | 16.64 |
June | 0.350621E+10 | 5106.80 | 30-JUN-13:10 | 23.00 | 17.85 | 0.428170E+09 | 549.50 | 27-JUN-09:20 | 23.00 | 17.85 |
July | 0.421504E+10 | 7163.09 | 31-JUL-12:50 | 28.00 | 21.19 | 0.401436E+09 | 549.50 | 13-JUL-09:20 | 28.00 | 21.19 |
August | 0.529148E+10 | 8110.87 | 30-AUG-13:00 | 24.00 | 18.12 | 0.450689E+09 | 549.50 | 18-AUG-13:20 | 24.00 | 18.12 |
September | 0.519984E+10 | 11333.97 | 29-SEP-13:10 | 35.67 | 18.16 | 0.397806E+09 | 568.53 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.586762E+10 | 14419.61 | 15-OCT-12:42 | 32.00 | 16.02 | 0.414197E+09 | 586.39 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.475091E+10 | 14066.83 | 19-NOV-11:02 | 26.00 | 15.13 | 0.404681E+09 | 549.82 | 10-NOV-14:50 | 26.00 | 15.13 |
December | 0.486506E+10 | 13793.91 | 03-DEC-13:53 | 17.00 | 12.88 | 0.391596E+09 | 549.78 | 20-DEC-14:50 | 19.20 | 11.87 |
Annual Sum or Average | 0.517908E+11 | 0.488704E+10 | ||||||||
Minimum of Months | 0.309179E+10 | 5106.80 | 17.00 | 10.89 | 0.360278E+09 | 549.50 | 17.00 | 10.89 | ||
Maximum of Months | 0.586762E+10 | 14419.61 | 35.67 | 21.19 | 0.450689E+09 | 586.39 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137259E+10 | 4532.00 | 18-JAN-15:00 | 23.00 | 14.79 | 0.238447E+09 | 347.86 | 10-JAN-14:09 | 23.00 | 14.79 |
February | 0.138854E+10 | 4869.47 | 22-FEB-15:40 | 16.60 | 12.17 | 0.218422E+09 | 347.88 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.177998E+10 | 7129.23 | 19-MAR-15:53 | 18.00 | 14.97 | 0.260065E+09 | 347.85 | 10-MAR-14:00 | 18.00 | 14.97 |
April | 0.268364E+10 | 12354.83 | 30-APR-16:23 | 22.00 | 15.83 | 0.244961E+09 | 347.86 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.280077E+10 | 11567.37 | 28-MAY-16:03 | 19.83 | 14.53 | 0.268265E+09 | 347.89 | 03-MAY-13:00 | 19.83 | 14.53 |
June | 0.352996E+10 | 11577.04 | 18-JUN-15:43 | 22.17 | 17.48 | 0.272130E+09 | 347.85 | 26-JUN-09:20 | 22.67 | 17.27 |
July | 0.404794E+10 | 12943.65 | 23-JUL-15:52 | 24.00 | 19.32 | 0.255014E+09 | 347.85 | 13-JUL-09:20 | 24.00 | 19.32 |
August | 0.416807E+10 | 10861.00 | 06-AUG-17:42 | 21.33 | 19.00 | 0.285711E+09 | 347.85 | 18-AUG-13:20 | 25.33 | 20.30 |
September | 0.309604E+10 | 11981.70 | 10-SEP-15:23 | 22.00 | 17.12 | 0.251159E+09 | 347.86 | 13-SEP-09:20 | 22.33 | 18.21 |
October | 0.266875E+10 | 12330.40 | 15-OCT-15:22 | 30.50 | 15.19 | 0.258007E+09 | 347.86 | 25-OCT-13:00 | 24.00 | 11.58 |
November | 0.169596E+10 | 4644.12 | 10-NOV-14:50 | 19.17 | 15.85 | 0.244755E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.143135E+10 | 4548.01 | 19-DEC-15:30 | 21.50 | 8.94 | 0.231882E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.306636E+11 | 0.302882E+10 | ||||||||
Minimum of Months | 0.137259E+10 | 4532.00 | 16.60 | 8.94 | 0.218422E+09 | 347.85 | 16.60 | 11.58 | ||
Maximum of Months | 0.416807E+10 | 12943.65 | 30.50 | 19.32 | 0.285711E+09 | 347.91 | 25.33 | 20.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152029E+10 | 1875.69 | 18-JAN-13:30 | 25.30 | 14.77 | 0.370114E+09 | 549.49 | 18-JAN-14:20 | 24.07 | 14.82 |
February | 0.141290E+10 | 1553.78 | 01-FEB-12:05 | 25.67 | 14.54 | 0.337430E+09 | 548.69 | 01-FEB-14:30 | 19.00 | 15.33 |
March | 0.164363E+10 | 1634.26 | 23-MAR-15:20 | 21.67 | 17.34 | 0.402522E+09 | 549.49 | 23-MAR-13:20 | 21.67 | 17.34 |
April | 0.179716E+10 | 2466.45 | 26-APR-14:00 | 26.00 | 16.74 | 0.382885E+09 | 549.50 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.211532E+10 | 2892.42 | 04-MAY-14:10 | 22.83 | 16.63 | 0.424113E+09 | 549.52 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.252638E+10 | 2839.49 | 27-JUN-16:00 | 22.00 | 18.09 | 0.429905E+09 | 549.50 | 23-JUN-09:20 | 22.00 | 18.09 |
July | 0.296607E+10 | 3423.00 | 31-JUL-13:10 | 27.83 | 21.13 | 0.402185E+09 | 549.50 | 13-JUL-09:20 | 27.83 | 21.13 |
August | 0.297446E+10 | 3352.54 | 18-AUG-15:00 | 27.00 | 20.85 | 0.450547E+09 | 549.49 | 02-AUG-09:20 | 27.00 | 20.85 |
September | 0.239125E+10 | 3972.48 | 29-SEP-13:10 | 35.67 | 18.16 | 0.396865E+09 | 549.50 | 13-SEP-09:20 | 35.67 | 18.16 |
October | 0.251411E+10 | 4281.78 | 16-OCT-12:30 | 35.05 | 17.21 | 0.410473E+09 | 549.50 | 31-OCT-13:20 | 26.67 | 16.70 |
November | 0.168713E+10 | 1763.48 | 19-NOV-13:13 | 26.33 | 15.04 | 0.388798E+09 | 549.50 | 09-NOV-14:00 | 26.33 | 15.04 |
December | 0.162070E+10 | 1747.10 | 19-DEC-14:30 | 22.50 | 9.72 | 0.361596E+09 | 546.70 | 05-DEC-14:00 | 22.50 | 9.72 |
Annual Sum or Average | 0.251694E+11 | 0.475743E+10 | ||||||||
Minimum of Months | 0.141290E+10 | 1553.78 | 21.67 | 9.72 | 0.337430E+09 | 546.70 | 19.00 | 9.72 | ||
Maximum of Months | 0.297446E+10 | 4281.78 | 35.67 | 21.13 | 0.450547E+09 | 549.52 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132573E+10 | 2733.45 | 20-JAN-09:50 | 18.67 | 14.64 | 0.255570E+09 | 347.88 | 27-JAN-14:20 | 16.67 | 12.79 |
February | 0.120720E+10 | 2438.81 | 21-FEB-10:00 | 17.00 | 11.03 | 0.229447E+09 | 347.89 | 01-FEB-14:09 | 17.00 | 11.03 |
March | 0.146842E+10 | 3647.75 | 23-MAR-09:30 | 20.50 | 15.62 | 0.274663E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.212788E+10 | 5358.94 | 30-APR-09:43 | 24.50 | 16.21 | 0.252117E+09 | 347.91 | 13-APR-09:00 | 24.50 | 16.21 |
May | 0.218872E+10 | 3987.82 | 04-MAY-09:30 | 21.00 | 15.49 | 0.273575E+09 | 347.90 | 03-MAY-13:00 | 21.00 | 15.49 |
June | 0.258129E+10 | 4791.80 | 25-JUN-09:53 | 23.00 | 17.26 | 0.273922E+09 | 347.88 | 22-JUN-09:39 | 23.00 | 17.26 |
July | 0.333896E+10 | 8033.83 | 04-JUL-09:02 | 22.00 | 15.93 | 0.256202E+09 | 347.88 | 17-JUL-09:20 | 21.67 | 16.98 |
August | 0.356865E+10 | 5269.77 | 14-AUG-09:10 | 25.32 | 20.33 | 0.287392E+09 | 347.88 | 23-AUG-09:20 | 21.67 | 16.23 |
September | 0.250477E+10 | 5526.60 | 10-SEP-08:43 | 21.50 | 17.28 | 0.253778E+09 | 347.88 | 12-SEP-09:20 | 21.67 | 16.41 |
October | 0.246041E+10 | 9041.60 | 15-OCT-08:32 | 31.67 | 15.30 | 0.264080E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.152354E+10 | 2576.87 | 01-NOV-09:30 | 15.00 | 12.66 | 0.258748E+09 | 347.89 | 06-NOV-10:00 | 19.00 | 13.20 |
December | 0.136569E+10 | 2679.79 | 05-DEC-09:50 | 25.67 | 12.88 | 0.248731E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.256613E+11 | 0.312823E+10 | ||||||||
Minimum of Months | 0.120720E+10 | 2438.81 | 15.00 | 11.03 | 0.229447E+09 | 347.88 | 16.67 | 11.03 | ||
Maximum of Months | 0.356865E+10 | 9041.60 | 31.67 | 20.33 | 0.287392E+09 | 347.91 | 24.50 | 17.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369670E+10 | 10978.07 | 22-JAN-12:13 | 17.00 | 12.07 | 0.403176E+09 | 549.73 | 18-JAN-14:00 | 17.00 | 12.07 |
February | 0.247323E+10 | 9258.74 | 20-FEB-13:33 | 17.00 | 10.76 | 0.354449E+09 | 549.68 | 03-FEB-14:00 | 17.00 | 10.76 |
March | 0.218177E+10 | 6287.80 | 23-MAR-14:00 | 23.00 | 17.27 | 0.410061E+09 | 549.52 | 01-MAR-14:09 | 23.00 | 17.27 |
April | 0.237905E+10 | 6177.27 | 26-APR-12:00 | 26.00 | 17.28 | 0.382237E+09 | 549.52 | 13-APR-09:00 | 26.00 | 17.28 |
May | 0.198707E+10 | 3904.20 | 01-MAY-12:10 | 21.00 | 13.98 | 0.408627E+09 | 549.54 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.221867E+10 | 3327.83 | 27-JUN-13:00 | 24.00 | 18.72 | 0.416220E+09 | 549.50 | 12-JUN-13:20 | 24.00 | 18.72 |
July | 0.303358E+10 | 7977.45 | 31-JUL-12:00 | 28.00 | 21.19 | 0.396453E+09 | 549.50 | 13-JUL-09:20 | 28.00 | 21.19 |
August | 0.400546E+10 | 7912.12 | 18-AUG-12:00 | 28.00 | 21.20 | 0.447200E+09 | 549.50 | 29-AUG-13:20 | 25.33 | 17.78 |
September | 0.412326E+10 | 11084.70 | 29-SEP-12:00 | 36.00 | 18.21 | 0.396800E+09 | 691.63 | 29-SEP-12:09 | 36.00 | 18.21 |
October | 0.526439E+10 | 11502.55 | 01-OCT-12:52 | 25.00 | 20.20 | 0.416951E+09 | 716.91 | 16-OCT-12:09 | 35.68 | 17.48 |
November | 0.392183E+10 | 11604.27 | 19-NOV-13:13 | 26.33 | 15.04 | 0.404391E+09 | 549.86 | 28-NOV-14:00 | 23.00 | 10.79 |
December | 0.420851E+10 | 11311.38 | 25-DEC-13:02 | 22.00 | 9.19 | 0.391707E+09 | 561.23 | 19-DEC-13:09 | 22.00 | 9.19 |
Annual Sum or Average | 0.394935E+11 | 0.482827E+10 | ||||||||
Minimum of Months | 0.198707E+10 | 3327.83 | 17.00 | 9.19 | 0.354449E+09 | 549.50 | 17.00 | 9.19 | ||
Maximum of Months | 0.526439E+10 | 11604.27 | 36.00 | 21.20 | 0.447200E+09 | 716.91 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134992E+10 | 3360.41 | 18-JAN-15:30 | 22.50 | 15.11 | 0.246602E+09 | 347.86 | 10-JAN-14:09 | 22.50 | 15.11 |
February | 0.127501E+10 | 3815.47 | 22-FEB-16:30 | 15.00 | 12.17 | 0.224587E+09 | 347.87 | 01-FEB-14:09 | 15.00 | 12.17 |
March | 0.154284E+10 | 4620.41 | 23-MAR-16:00 | 21.00 | 17.19 | 0.266774E+09 | 347.85 | 01-MAR-14:20 | 21.00 | 17.19 |
April | 0.215150E+10 | 5201.59 | 26-APR-16:00 | 22.00 | 16.41 | 0.249705E+09 | 347.86 | 13-APR-13:00 | 22.00 | 16.41 |
May | 0.231717E+10 | 7133.39 | 28-MAY-16:42 | 19.17 | 14.31 | 0.272541E+09 | 347.88 | 03-MAY-13:00 | 19.17 | 14.31 |
June | 0.284481E+10 | 6824.03 | 18-JUN-17:03 | 20.67 | 17.09 | 0.273960E+09 | 347.85 | 23-JUN-09:20 | 21.33 | 15.56 |
July | 0.344079E+10 | 8422.39 | 23-JUL-16:22 | 24.00 | 19.02 | 0.256240E+09 | 347.85 | 13-JUL-09:20 | 24.00 | 19.02 |
August | 0.358824E+10 | 7341.43 | 06-AUG-16:43 | 23.17 | 19.14 | 0.287322E+09 | 347.85 | 02-AUG-09:20 | 23.17 | 19.14 |
September | 0.277183E+10 | 7825.80 | 10-SEP-15:43 | 22.00 | 16.93 | 0.254429E+09 | 347.85 | 21-SEP-09:20 | 19.67 | 17.71 |
October | 0.250196E+10 | 9810.82 | 15-OCT-15:11 | 30.67 | 15.29 | 0.263082E+09 | 347.85 | 10-OCT-09:20 | 30.67 | 15.29 |
November | 0.166193E+10 | 3808.76 | 07-NOV-15:40 | 19.00 | 14.59 | 0.254637E+09 | 347.89 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.143283E+10 | 3649.45 | 19-DEC-15:30 | 21.50 | 8.94 | 0.241108E+09 | 347.90 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.268788E+11 | 0.309099E+10 | ||||||||
Minimum of Months | 0.127501E+10 | 3360.41 | 15.00 | 8.94 | 0.224587E+09 | 347.85 | 15.00 | 12.17 | ||
Maximum of Months | 0.358824E+10 | 9810.82 | 30.67 | 19.14 | 0.287322E+09 | 347.90 | 30.67 | 19.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164529E+10 | 2407.02 | 24-JAN-15:00 | 25.00 | 15.45 | 0.377709E+09 | 549.50 | 24-JAN-14:20 | 25.00 | 15.45 |
February | 0.156572E+10 | 2198.04 | 03-FEB-15:00 | 23.00 | 8.84 | 0.351044E+09 | 549.53 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.187348E+10 | 2608.41 | 23-MAR-15:20 | 21.67 | 17.34 | 0.418032E+09 | 549.50 | 09-MAR-14:20 | 21.67 | 17.34 |
April | 0.228317E+10 | 3531.73 | 26-APR-14:00 | 26.00 | 16.74 | 0.391451E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.267595E+10 | 3861.51 | 04-MAY-14:10 | 22.83 | 16.63 | 0.429137E+09 | 549.53 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.328863E+10 | 3757.45 | 26-JUN-16:00 | 22.00 | 17.40 | 0.432638E+09 | 549.50 | 23-JUN-09:20 | 22.00 | 17.40 |
July | 0.367010E+10 | 4285.76 | 31-JUL-13:10 | 27.83 | 21.13 | 0.403409E+09 | 549.50 | 13-JUL-09:20 | 27.83 | 21.13 |
August | 0.368553E+10 | 4112.97 | 18-AUG-15:00 | 27.00 | 20.85 | 0.452137E+09 | 549.50 | 02-AUG-09:20 | 27.00 | 20.85 |
September | 0.286395E+10 | 4899.53 | 29-SEP-13:10 | 35.67 | 18.16 | 0.398835E+09 | 549.50 | 21-SEP-09:20 | 35.67 | 18.16 |
October | 0.285299E+10 | 5174.94 | 16-OCT-12:30 | 35.05 | 17.21 | 0.412063E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.181837E+10 | 2280.57 | 01-NOV-14:00 | 17.00 | 13.47 | 0.394527E+09 | 549.52 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.172232E+10 | 2423.91 | 05-DEC-15:00 | 25.00 | 13.22 | 0.370454E+09 | 549.50 | 04-DEC-14:20 | 25.00 | 13.22 |
Annual Sum or Average | 0.299455E+11 | 0.483143E+10 | ||||||||
Minimum of Months | 0.156572E+10 | 2198.04 | 17.00 | 8.84 | 0.351044E+09 | 549.50 | 18.00 | 8.84 | ||
Maximum of Months | 0.368553E+10 | 5174.94 | 35.67 | 21.13 | 0.452137E+09 | 549.53 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128733E+10 | 3984.76 | 20-JAN-11:05 | 21.17 | 15.50 | 0.188365E+09 | 356.46 | 05-JAN-11:09 | 21.17 | 15.50 |
February | 0.127166E+10 | 4484.42 | 09-FEB-13:02 | 15.13 | 10.41 | 0.170583E+09 | 356.47 | 02-FEB-13:09 | 15.13 | 10.41 |
March | 0.160836E+10 | 5729.62 | 23-MAR-10:05 | 22.00 | 16.49 | 0.203799E+09 | 356.47 | 23-MAR-10:09 | 22.00 | 16.49 |
April | 0.244922E+10 | 7405.20 | 30-APR-09:53 | 25.00 | 16.34 | 0.186788E+09 | 356.49 | 13-APR-10:09 | 25.00 | 16.34 |
May | 0.246670E+10 | 6702.81 | 28-MAY-08:23 | 18.50 | 14.07 | 0.202823E+09 | 356.48 | 03-MAY-14:09 | 18.50 | 14.07 |
June | 0.297493E+10 | 7400.13 | 25-JUN-08:63 | 19.50 | 15.48 | 0.203134E+09 | 356.46 | 02-JUN-10:09 | 19.50 | 15.48 |
July | 0.363360E+10 | 10924.05 | 23-JUL-08:23 | 24.00 | 19.32 | 0.190394E+09 | 356.46 | 12-JUL-10:09 | 24.00 | 19.32 |
August | 0.384719E+10 | 7247.66 | 06-AUG-10:03 | 23.33 | 19.67 | 0.212720E+09 | 356.46 | 23-AUG-10:09 | 23.17 | 16.83 |
September | 0.266999E+10 | 7390.13 | 29-SEP-12:02 | 36.00 | 18.21 | 0.187962E+09 | 356.46 | 12-SEP-10:09 | 36.00 | 18.21 |
October | 0.250599E+10 | 10807.49 | 15-OCT-08:23 | 31.00 | 15.00 | 0.195559E+09 | 356.49 | 30-OCT-12:09 | 24.33 | 16.19 |
November | 0.149941E+10 | 4160.39 | 01-NOV-12:02 | 18.00 | 13.26 | 0.190651E+09 | 356.47 | 30-NOV-15:09 | 20.50 | 12.92 |
December | 0.133616E+10 | 4530.36 | 01-DEC-13:02 | 15.17 | 11.65 | 0.183576E+09 | 356.48 | 20-DEC-15:09 | 18.67 | 12.31 |
Annual Sum or Average | 0.275506E+11 | 0.231635E+10 | ||||||||
Minimum of Months | 0.127166E+10 | 3984.76 | 15.13 | 10.41 | 0.170583E+09 | 356.46 | 15.13 | 10.41 | ||
Maximum of Months | 0.384719E+10 | 10924.05 | 36.00 | 19.67 | 0.212720E+09 | 356.49 | 36.00 | 19.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497736E+10 | 12854.73 | 22-JAN-12:43 | 17.00 | 12.32 | 0.409970E+09 | 557.68 | 18-JAN-14:09 | 17.00 | 12.32 |
February | 0.367281E+10 | 12063.06 | 20-FEB-13:13 | 17.00 | 10.50 | 0.367984E+09 | 549.85 | 01-FEB-14:20 | 17.00 | 10.50 |
March | 0.354523E+10 | 8670.53 | 19-MAR-13:13 | 19.67 | 15.00 | 0.435404E+09 | 550.12 | 23-MAR-13:20 | 22.33 | 16.99 |
April | 0.372567E+10 | 6899.42 | 26-APR-13:00 | 27.00 | 17.13 | 0.395220E+09 | 549.53 | 13-APR-13:39 | 27.00 | 17.13 |
May | 0.311165E+10 | 5215.49 | 04-MAY-12:30 | 23.50 | 16.62 | 0.428758E+09 | 549.54 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.341721E+10 | 4599.65 | 30-JUN-13:10 | 23.00 | 17.85 | 0.431775E+09 | 549.50 | 27-JUN-09:20 | 23.00 | 17.85 |
July | 0.403687E+10 | 6577.44 | 31-JUL-12:40 | 28.00 | 21.19 | 0.403213E+09 | 549.50 | 13-JUL-09:20 | 28.00 | 21.19 |
August | 0.511444E+10 | 7583.17 | 30-AUG-12:50 | 23.83 | 17.97 | 0.452822E+09 | 550.49 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.517064E+10 | 10359.31 | 29-SEP-12:04 | 36.00 | 18.21 | 0.401439E+09 | 575.38 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.598342E+10 | 13199.70 | 01-OCT-12:52 | 25.00 | 20.20 | 0.418630E+09 | 595.31 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.513423E+10 | 12850.46 | 19-NOV-11:02 | 26.00 | 15.13 | 0.410404E+09 | 550.00 | 13-NOV-10:20 | 26.00 | 15.13 |
December | 0.535119E+10 | 12755.65 | 25-DEC-13:02 | 22.00 | 9.19 | 0.398129E+09 | 559.16 | 19-DEC-14:09 | 22.00 | 9.19 |
Annual Sum or Average | 0.532407E+11 | 0.495375E+10 | ||||||||
Minimum of Months | 0.311165E+10 | 4599.65 | 17.00 | 9.19 | 0.367984E+09 | 549.50 | 17.00 | 9.19 | ||
Maximum of Months | 0.598342E+10 | 13199.70 | 36.00 | 21.19 | 0.452822E+09 | 595.31 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153414E+10 | 4406.50 | 18-JAN-15:00 | 23.00 | 14.79 | 0.246319E+09 | 347.85 | 10-JAN-14:09 | 23.00 | 14.79 |
February | 0.151961E+10 | 4832.93 | 22-FEB-15:40 | 16.60 | 12.17 | 0.226148E+09 | 347.88 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.187927E+10 | 6600.98 | 19-MAR-15:53 | 18.00 | 14.97 | 0.269307E+09 | 347.85 | 10-MAR-14:00 | 18.00 | 14.97 |
April | 0.265954E+10 | 7025.97 | 23-APR-16:23 | 16.50 | 13.77 | 0.249817E+09 | 347.86 | 13-APR-13:00 | 16.50 | 13.77 |
May | 0.278297E+10 | 10699.91 | 28-MAY-16:03 | 19.83 | 14.53 | 0.272567E+09 | 347.89 | 03-MAY-13:00 | 19.83 | 14.53 |
June | 0.343604E+10 | 11676.95 | 25-JUN-16:22 | 21.00 | 16.52 | 0.274257E+09 | 347.85 | 23-JUN-09:20 | 21.00 | 16.52 |
July | 0.387928E+10 | 11413.85 | 09-JUL-15:32 | 21.33 | 16.12 | 0.256047E+09 | 347.85 | 13-JUL-09:20 | 22.00 | 17.64 |
August | 0.403753E+10 | 11674.91 | 27-AUG-16:02 | 21.67 | 17.87 | 0.287038E+09 | 347.85 | 02-AUG-09:20 | 21.67 | 17.87 |
September | 0.308773E+10 | 11372.99 | 04-SEP-16:03 | 19.67 | 15.96 | 0.253852E+09 | 347.85 | 21-SEP-09:20 | 19.67 | 17.71 |
October | 0.273306E+10 | 11194.82 | 15-OCT-15:42 | 30.17 | 14.99 | 0.262176E+09 | 347.86 | 03-OCT-13:00 | 30.17 | 14.99 |
November | 0.184831E+10 | 4554.56 | 07-NOV-15:30 | 19.00 | 14.51 | 0.252983E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.161136E+10 | 4449.29 | 19-DEC-15:30 | 21.50 | 8.94 | 0.240519E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.310088E+11 | 0.309103E+10 | ||||||||
Minimum of Months | 0.151961E+10 | 4406.50 | 16.50 | 8.94 | 0.226148E+09 | 347.85 | 16.50 | 12.17 | ||
Maximum of Months | 0.403753E+10 | 11676.95 | 30.17 | 17.87 | 0.287038E+09 | 347.91 | 30.17 | 17.87 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.851503E+09 | 6551.98 | 03-JAN-07:03 | 3.67 |
February | 0.643796E+09 | 3153.75 | 09-FEB-06:03 | 6.45 |
March | 0.752218E+09 | 4925.22 | 30-MAR-06:03 | 5.58 |
April | 0.400358E+09 | 2850.53 | 20-APR-05:03 | 9.17 |
May | 0.344185E+09 | 2962.85 | 19-MAY-05:03 | 8.67 |
June | 0.185512E+09 | 2725.01 | 05-JUN-05:03 | 12.17 |
July | 0.106504E+09 | 2371.73 | 06-JUL-05:05 | 14.33 |
August | 0.133912E+09 | 2411.25 | 06-AUG-07:10 | 19.50 |
September | 0.234937E+09 | 2722.52 | 20-SEP-05:03 | 12.00 |
October | 0.358136E+09 | 3096.80 | 15-OCT-07:27 | 26.50 |
November | 0.610582E+09 | 3201.32 | 24-NOV-06:03 | 8.92 |
December | 0.801727E+09 | 3268.81 | 20-DEC-06:03 | 8.67 |
Annual Sum or Average | 0.542337E+10 | |||
Minimum of Months | 0.106504E+09 | 2371.73 | 3.67 | |
Maximum of Months | 0.851503E+09 | 6551.98 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498030E+09 | 3861.63 | 08-JAN-13:23 | 17.00 |
February | 0.302513E+09 | 3166.04 | 20-FEB-11:53 | 17.00 |
March | 0.420892E+09 | 2224.31 | 19-MAR-13:13 | 19.67 |
April | 69580357.48 | 2112.57 | 02-APR-15:43 | 19.33 |
May | 42505212.45 | 2169.06 | 28-MAY-16:42 | 19.17 |
June | 14656714.55 | 1677.95 | 18-JUN-15:43 | 22.17 |
July | 20668885.90 | 1682.92 | 23-JUL-09:02 | 25.00 |
August | 16297377.29 | 1663.68 | 06-AUG-13:50 | 25.17 |
September | 18889761.38 | 2027.96 | 10-SEP-14:23 | 22.50 |
October | 42671575.54 | 3251.77 | 15-OCT-09:43 | 31.33 |
November | 0.177963E+09 | 3423.13 | 26-NOV-12:03 | 16.02 |
December | 0.343723E+09 | 4067.62 | 25-DEC-13:02 | 22.00 |
Annual Sum or Average | 0.196839E+10 | |||
Minimum of Months | 14656714.55 | 1663.68 | 16.02 | |
Maximum of Months | 0.498030E+09 | 4067.62 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178805E+09 | 2022.38 | 22-JAN-11:33 | 16.67 |
February | 95507155.31 | 1989.44 | 20-FEB-12:53 | 17.00 |
March | 0.128703E+09 | 2118.86 | 30-MAR-07:09 | 7.33 |
April | 11478446.99 | 1514.47 | 02-APR-15:47 | 19.33 |
May | 11780410.02 | 1425.61 | 14-MAY-15:50 | 17.17 |
June | 8032178.33 | 1323.09 | 18-JUN-07:40 | 18.67 |
July | 13212962.73 | 1269.11 | 09-JUL-14:00 | 21.00 |
August | 11537110.13 | 1225.26 | 27-AUG-14:00 | 23.00 |
September | 14524745.56 | 1685.82 | 17-SEP-14:20 | 20.67 |
October | 20606288.57 | 2113.61 | 15-OCT-09:53 | 31.00 |
November | 23610025.60 | 2167.26 | 26-NOV-13:23 | 16.05 |
December | 71407791.56 | 2622.69 | 25-DEC-13:02 | 22.00 |
Annual Sum or Average | 0.589205E+09 | |||
Minimum of Months | 8032178.33 | 1225.26 | 7.33 | |
Maximum of Months | 0.178805E+09 | 2622.69 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1250693.29 | 8337.96 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 1250693.29 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 1250693.29 | 8337.96 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35056819.50 | 21577.20 | 02-JAN-07:03 | 11.00 |
February | 1679643.62 | 5118.75 | 27-FEB-07:03 | 10.67 |
March | 4224781.66 | 20124.45 | 30-MAR-06:03 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 521145.48 | 3474.30 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 41482390.26 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 35056819.50 | 21577.20 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177820E+09 | 7787.77 | 03-JAN-06:11 | 4.33 |
February | 42271899.84 | 6927.79 | 13-FEB-07:03 | 14.17 |
March | 84372048.30 | 7550.85 | 30-MAR-05:12 | 5.03 |
April | 7374950.04 | 6915.81 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 1107738.75 | 6270.85 | 30-OCT-06:02 | 10.50 |
November | 21411764.02 | 6904.68 | 18-NOV-07:03 | 9.67 |
December | 77152930.02 | 7248.66 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.411511E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 0.177820E+09 | 7787.77 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57715869.64 | 6513.79 | 03-JAN-06:11 | 4.33 |
February | 13743181.44 | 5633.94 | 10-FEB-07:03 | 7.57 |
March | 22786706.76 | 6289.89 | 30-MAR-05:12 | 5.03 |
April | 1416749.29 | 4782.40 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 432192.71 | 3001.45 | 30-OCT-06:02 | 10.50 |
November | 2859279.81 | 3701.12 | 24-NOV-07:03 | 8.75 |
December | 17352081.60 | 6190.50 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.116306E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 57715869.64 | 6513.79 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72049063.49 | 10036.03 | 03-JAN-06:11 | 4.33 |
February | 19750123.67 | 8542.02 | 11-FEB-07:03 | 8.08 |
March | 54051361.17 | 9862.94 | 30-MAR-05:12 | 5.03 |
April | 6082703.53 | 9028.76 | 01-APR-06:03 | 7.67 |
May | 877104.23 | 1982.71 | 15-MAY-06:05 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 3433057.42 | 5395.63 | 24-NOV-07:03 | 8.75 |
December | 19974245.81 | 8631.83 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 0.176218E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 72049063.49 | 10036.03 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101176E+09 | 6306.24 | 03-JAN-06:11 | 4.33 |
February | 23422066.70 | 5731.87 | 06-FEB-07:03 | 9.50 |
March | 48801746.05 | 6013.74 | 30-MAR-05:12 | 5.03 |
April | 4980741.26 | 5858.75 | 01-APR-06:03 | 7.67 |
May | 243203.72 | 547.14 | 13-MAY-06:05 | 12.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 301026.06 | 1875.52 | 30-OCT-06:02 | 10.50 |
November | 10432806.15 | 5564.10 | 24-NOV-07:03 | 8.75 |
December | 44940474.54 | 5890.95 | 15-DEC-07:03 | 6.50 |
Annual Sum or Average | 0.234298E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 0.101176E+09 | 6306.24 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22665521.71 | 5562.27 | 03-JAN-06:11 | 4.33 |
February | 2615171.82 | 3140.65 | 28-FEB-07:03 | 11.33 |
March | 9410536.33 | 5372.40 | 30-MAR-06:03 | 5.58 |
April | 914028.31 | 5196.31 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 2307800.42 | 4342.68 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 37913058.59 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 22665521.71 | 5562.27 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2193351.51 | 4233.52 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 1250357.14 | 4203.99 | 30-MAR-06:03 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 3443708.65 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 2193351.51 | 4233.52 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352678E+09 | 7213.49 | 03-JAN-07:10 | 3.67 |
February | 0.344487E+09 | 6522.80 | 10-FEB-07:10 | 7.57 |
March | 0.656275E+09 | 7206.16 | 30-MAR-06:10 | 5.58 |
April | 0.255849E+09 | 6395.86 | 03-APR-06:30 | 10.50 |
May | 0.208692E+09 | 6340.79 | 15-MAY-06:10 | 11.33 |
June | 62569500.74 | 5083.77 | 01-JUN-06:10 | 13.17 |
July | 469876.71 | 1242.85 | 27-JUL-06:10 | 15.17 |
August | 2227055.06 | 3142.74 | 28-AUG-06:08 | 14.00 |
September | 16871847.57 | 4517.42 | 20-SEP-06:08 | 12.17 |
October | 57724595.35 | 6258.90 | 25-OCT-06:07 | 11.33 |
November | 0.144234E+09 | 6366.30 | 30-NOV-07:20 | 9.33 |
December | 0.287796E+09 | 6649.26 | 13-DEC-07:10 | 7.17 |
Annual Sum or Average | 0.238987E+10 | |||
Minimum of Months | 469876.71 | 1242.85 | 3.67 | |
Maximum of Months | 0.656275E+09 | 7213.49 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5680346.78 | 4019.14 | 02-JAN-07:03 | 11.00 |
February | 114871.30 | 423.89 | 28-FEB-07:03 | 11.33 |
March | 2203100.65 | 4260.29 | 30-MAR-06:03 | 5.58 |
April | 300795.22 | 2005.30 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 81745.46 | 544.97 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 8380859.39 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 5680346.78 | 4260.29 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27867322.92 | 6319.07 | 03-JAN-06:11 | 4.33 |
February | 1354515.54 | 2999.09 | 27-FEB-07:03 | 10.67 |
March | 8282209.79 | 6006.23 | 30-MAR-06:03 | 5.58 |
April | 603610.00 | 3991.33 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 3099026.97 | 5490.90 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 41206685.22 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 27867322.92 | 6319.07 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8378202.40 | 4796.69 | 02-JAN-06:11 | 11.00 |
February | 70803.47 | 416.34 | 27-FEB-07:03 | 10.67 |
March | 1890544.92 | 4697.81 | 30-MAR-06:03 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 236866.44 | 1078.71 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 10576417.23 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 8378202.40 | 4796.69 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8252338.69 | 6840.72 | 03-JAN-07:03 | 3.67 |
February | 122438.93 | 443.37 | 13-FEB-07:03 | 14.17 |
March | 4614863.62 | 6840.63 | 30-MAR-06:03 | 5.58 |
April | 475678.01 | 3171.19 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 298714.61 | 1991.43 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 13764033.86 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 8252338.69 | 6840.72 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14710860.11 | 4821.92 | 02-JAN-06:11 | 11.00 |
February | 482823.73 | 1458.12 | 28-FEB-07:03 | 11.33 |
March | 4412301.03 | 4515.88 | 30-MAR-06:03 | 5.58 |
April | 444035.16 | 2783.62 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1457596.21 | 3561.04 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 21507616.24 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 14710860.11 | 4821.92 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351743E+10 | 3696.64 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.319060E+10 | 3696.64 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.379103E+10 | 3696.64 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.338654E+10 | 3696.64 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.365423E+10 | 3696.64 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.363649E+10 | 3696.64 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.340429E+10 | 3696.64 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.379103E+10 | 3696.64 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.338654E+10 | 3696.64 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.351743E+10 | 3696.64 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.347603E+10 | 3696.64 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.340429E+10 | 3696.64 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.421559E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.319060E+10 | 3696.64 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.379103E+10 | 3696.64 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351743E+10 | 3696.64 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.319060E+10 | 3696.64 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.379103E+10 | 3696.64 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.338654E+10 | 3696.64 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.365423E+10 | 3696.64 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.363649E+10 | 3696.64 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.340429E+10 | 3696.64 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.379103E+10 | 3696.64 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.338654E+10 | 3696.64 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.351743E+10 | 3696.64 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.347603E+10 | 3696.64 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.340429E+10 | 3696.64 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.421559E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.319060E+10 | 3696.64 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.379103E+10 | 3696.64 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351743E+10 | 3696.64 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.319060E+10 | 3696.64 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.379103E+10 | 3696.64 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.338654E+10 | 3696.64 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.365423E+10 | 3696.64 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.363649E+10 | 3696.64 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.340429E+10 | 3696.64 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.379103E+10 | 3696.64 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.338654E+10 | 3696.64 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.351743E+10 | 3696.64 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.347603E+10 | 3696.64 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.340429E+10 | 3696.64 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.421559E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.319060E+10 | 3696.64 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.379103E+10 | 3696.64 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.472676E+09 | 779.28 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.401637E+09 | 689.92 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.460472E+09 | 520.87 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.396717E+09 | 434.57 | 21-APR-15:00 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.418067E+09 | 423.95 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.412868E+09 | 414.52 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.388954E+09 | 402.42 | 12-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.436572E+09 | 424.96 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.406562E+09 | 554.05 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.443145E+09 | 569.00 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.462593E+09 | 779.28 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.465034E+09 | 779.28 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.516530E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.388954E+09 | 402.42 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.472676E+09 | 779.28 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294205E+09 | 493.35 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.252775E+09 | 438.86 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.289763E+09 | 330.63 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251459E+09 | 277.75 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265933E+09 | 256.84 | 09-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.262986E+09 | 252.13 | 16-JUN-14:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.247647E+09 | 235.33 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.277240E+09 | 255.51 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.256082E+09 | 316.78 | 21-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.276805E+09 | 376.54 | 20-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.290415E+09 | 493.35 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.288830E+09 | 493.35 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.325414E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.247647E+09 | 235.33 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.294205E+09 | 493.35 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.454762E+09 | 779.28 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.393616E+09 | 684.17 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.456625E+09 | 437.49 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.397263E+09 | 432.83 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.420571E+09 | 426.23 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.416664E+09 | 419.94 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.392179E+09 | 409.64 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.438539E+09 | 426.13 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.405087E+09 | 542.75 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.428995E+09 | 529.24 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.447774E+09 | 779.28 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.444149E+09 | 779.28 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.509622E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.392179E+09 | 409.64 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.456625E+09 | 779.28 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.292186E+09 | 493.32 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.251370E+09 | 428.07 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.289781E+09 | 352.80 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251526E+09 | 276.44 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265522E+09 | 274.44 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.261991E+09 | 270.81 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.246566E+09 | 267.03 | 12-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.277002E+09 | 275.64 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.257138E+09 | 368.31 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.275079E+09 | 371.34 | 24-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.285414E+09 | 493.32 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.286434E+09 | 493.32 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.324001E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.246566E+09 | 267.03 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.292186E+09 | 493.32 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470930E+09 | 779.28 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.400678E+09 | 686.50 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.459681E+09 | 510.77 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.396306E+09 | 432.40 | 21-APR-15:00 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.417761E+09 | 421.26 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.412496E+09 | 411.35 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.388727E+09 | 398.66 | 12-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.436270E+09 | 422.32 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.405926E+09 | 545.39 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.441261E+09 | 560.08 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.461092E+09 | 779.28 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.463341E+09 | 779.28 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.515447E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.388727E+09 | 398.66 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.470930E+09 | 779.28 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.293711E+09 | 493.35 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.252353E+09 | 437.18 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.289413E+09 | 323.81 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251201E+09 | 276.62 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265704E+09 | 254.67 | 09-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.262784E+09 | 249.93 | 16-JUN-14:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.247460E+09 | 235.33 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.276964E+09 | 253.24 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.255796E+09 | 276.80 | 21-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.276085E+09 | 372.99 | 20-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.289848E+09 | 493.35 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.288188E+09 | 493.35 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.324951E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.247460E+09 | 235.33 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.293711E+09 | 493.35 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.454308E+09 | 779.28 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.393784E+09 | 680.45 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.456243E+09 | 435.42 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.396849E+09 | 430.56 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.420160E+09 | 423.66 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.416220E+09 | 417.10 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.391899E+09 | 406.32 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.438150E+09 | 423.55 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.404560E+09 | 533.57 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.428581E+09 | 519.26 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.447472E+09 | 779.28 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.443785E+09 | 779.28 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.509201E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.391899E+09 | 406.32 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.456243E+09 | 779.28 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.291576E+09 | 493.32 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.250959E+09 | 425.93 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.289422E+09 | 348.50 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251236E+09 | 275.29 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265262E+09 | 273.19 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.261754E+09 | 269.41 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.246339E+09 | 265.50 | 12-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.276757E+09 | 274.45 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.256729E+09 | 364.56 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.274359E+09 | 367.60 | 24-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.285000E+09 | 493.32 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.285469E+09 | 493.32 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.323486E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.246339E+09 | 265.50 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.291576E+09 | 493.32 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.472676E+09 | 779.28 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.401636E+09 | 689.91 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.460452E+09 | 520.85 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.396716E+09 | 434.57 | 21-APR-15:00 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.418066E+09 | 423.95 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.412868E+09 | 414.51 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.388953E+09 | 402.41 | 12-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.436572E+09 | 424.96 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.406561E+09 | 554.03 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.443144E+09 | 569.00 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.462592E+09 | 779.28 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.465033E+09 | 779.28 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.516527E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.388953E+09 | 402.41 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.472676E+09 | 779.28 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294205E+09 | 493.35 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.252775E+09 | 438.85 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.289763E+09 | 330.64 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251459E+09 | 277.75 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265928E+09 | 256.84 | 09-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.262986E+09 | 252.12 | 16-JUN-14:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.247647E+09 | 235.33 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.277239E+09 | 255.51 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.256081E+09 | 316.76 | 21-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.276804E+09 | 376.53 | 20-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.290414E+09 | 493.35 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.288830E+09 | 493.35 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.325413E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.247647E+09 | 235.33 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.294205E+09 | 493.35 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.454761E+09 | 779.28 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.393616E+09 | 684.16 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.456625E+09 | 437.49 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.397263E+09 | 432.83 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.420571E+09 | 426.22 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.416664E+09 | 419.94 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.392179E+09 | 409.64 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.438539E+09 | 426.13 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.405086E+09 | 542.73 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.428994E+09 | 529.22 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.447774E+09 | 779.28 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.444149E+09 | 779.28 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.509622E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.392179E+09 | 409.64 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.456625E+09 | 779.28 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.292185E+09 | 493.32 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.251370E+09 | 428.06 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.289781E+09 | 352.79 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.251523E+09 | 276.44 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.265522E+09 | 274.44 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.261991E+09 | 270.81 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.246565E+09 | 267.03 | 12-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.277002E+09 | 275.64 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.257137E+09 | 368.30 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.275079E+09 | 371.33 | 24-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.285414E+09 | 493.32 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.286434E+09 | 493.32 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.324000E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.246565E+09 | 267.03 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.292185E+09 | 493.32 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.351743E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.319060E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.379103E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.338654E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.365423E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.363649E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.340429E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.379103E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.338654E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.351743E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.347603E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.340429E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.421559E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.319060E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.379103E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.351743E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.338654E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.365423E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.363649E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.340429E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.338654E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.351743E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.347603E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.340429E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.421559E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.351743E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.338654E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.365423E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.363649E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.340429E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.338654E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.351743E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.347603E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.340429E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.421559E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.319060E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.379103E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.472676E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 811505.12 | 0.290570E+09 |
February | 0.901968E+09 | 0.401637E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64350.78 | 0.343568E+09 |
March | 0.107774E+10 | 0.460472E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99926.28 | 0.378732E+09 |
April | 0.956342E+09 | 0.396717E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 864342.59 | 0.230351E+09 |
May | 0.103597E+10 | 0.418067E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282459E+09 |
June | 0.103308E+10 | 0.412868E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32589.94 | 0.154595E+09 |
July | 0.959235E+09 | 0.388954E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2517358.11 | 0.111918E+09 |
August | 0.107774E+10 | 0.436572E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2685970.64 | 0.134977E+09 |
September | 0.956342E+09 | 0.406562E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4071974.23 | 0.130483E+09 |
October | 0.994195E+09 | 0.443145E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15000805.29 | 0.197649E+09 |
November | 0.984487E+09 | 0.462593E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1726259.99 | 0.283557E+09 |
December | 0.959235E+09 | 0.465034E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189035.93 | 0.296475E+09 |
Annual Sum or Average | 0.119305E+11 | 0.516530E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29064118.91 | 0.283533E+10 |
Minimum of Months | 0.901968E+09 | 0.388954E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111918E+09 |
Maximum of Months | 0.107774E+10 | 0.472676E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15000805.29 | 0.378732E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.294205E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 278450.02 | 0.202527E+09 |
February | 0.571020E+09 | 0.252775E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36917.76 | 0.239076E+09 |
March | 0.682301E+09 | 0.289763E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262908E+09 |
April | 0.605444E+09 | 0.251459E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173576.77 | 0.164373E+09 |
May | 0.655854E+09 | 0.265933E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197949E+09 |
June | 0.654023E+09 | 0.262986E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21722.68 | 0.107327E+09 |
July | 0.607275E+09 | 0.247647E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1570852.86 | 81432615.65 |
August | 0.682301E+09 | 0.277240E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1633865.56 | 97021908.08 |
September | 0.605444E+09 | 0.256082E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2712532.49 | 93402572.61 |
October | 0.629407E+09 | 0.276805E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8847774.26 | 0.139596E+09 |
November | 0.623262E+09 | 0.290415E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 329283.72 | 0.197849E+09 |
December | 0.607275E+09 | 0.288830E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 188217.48 | 0.207481E+09 |
Annual Sum or Average | 0.755301E+10 | 0.325414E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15793193.59 | 0.199094E+10 |
Minimum of Months | 0.571020E+09 | 0.247647E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81432615.65 |
Maximum of Months | 0.682301E+09 | 0.294205E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8847774.26 | 0.262908E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.454762E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 338140.05 | 0.326919E+09 |
February | 0.901968E+09 | 0.393616E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55345.40 | 0.379853E+09 |
March | 0.107774E+10 | 0.456625E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401769E+09 |
April | 0.956342E+09 | 0.397263E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295131.80 | 0.247303E+09 |
May | 0.103597E+10 | 0.420571E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287190E+09 |
June | 0.103308E+10 | 0.416664E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32591.66 | 0.153790E+09 |
July | 0.959235E+09 | 0.392179E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2479154.32 | 0.114302E+09 |
August | 0.107774E+10 | 0.438539E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2451275.35 | 0.142845E+09 |
September | 0.956342E+09 | 0.405087E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4036868.26 | 0.147228E+09 |
October | 0.994195E+09 | 0.428995E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12987109.01 | 0.223752E+09 |
November | 0.984487E+09 | 0.447774E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114823.09 | 0.318805E+09 |
December | 0.959235E+09 | 0.444149E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221251.77 | 0.340023E+09 |
Annual Sum or Average | 0.119305E+11 | 0.509622E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23011690.70 | 0.308378E+10 |
Minimum of Months | 0.901968E+09 | 0.392179E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114302E+09 |
Maximum of Months | 0.107774E+10 | 0.456625E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12987109.01 | 0.401769E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.292186E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399682.28 | 0.201948E+09 |
February | 0.570983E+09 | 0.251370E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40973.73 | 0.240126E+09 |
March | 0.682256E+09 | 0.289781E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33746.78 | 0.261826E+09 |
April | 0.605404E+09 | 0.251526E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 527750.12 | 0.167619E+09 |
May | 0.655811E+09 | 0.265522E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201853E+09 |
June | 0.653980E+09 | 0.261991E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21730.56 | 0.109408E+09 |
July | 0.607235E+09 | 0.246566E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1698956.45 | 82994250.93 |
August | 0.682256E+09 | 0.277002E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1738627.16 | 99031374.64 |
September | 0.605404E+09 | 0.257138E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2705228.32 | 97344270.73 |
October | 0.629366E+09 | 0.275079E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9467980.22 | 0.142381E+09 |
November | 0.623221E+09 | 0.285414E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 844626.11 | 0.199273E+09 |
December | 0.607235E+09 | 0.286434E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 461893.15 | 0.207549E+09 |
Annual Sum or Average | 0.755252E+10 | 0.324001E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17941194.89 | 0.201135E+10 |
Minimum of Months | 0.570983E+09 | 0.246566E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82994250.93 |
Maximum of Months | 0.682256E+09 | 0.292186E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9467980.22 | 0.261826E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.470930E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 447663.73 | 0.167585E+09 |
February | 0.901968E+09 | 0.400678E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42383.11 | 0.193957E+09 |
March | 0.107774E+10 | 0.459681E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88574.37 | 0.209576E+09 |
April | 0.956342E+09 | 0.396306E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 623590.25 | 0.122772E+09 |
May | 0.103597E+10 | 0.417761E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 0.151397E+09 |
June | 0.103308E+10 | 0.412496E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19270.92 | 80353995.34 |
July | 0.959235E+09 | 0.388727E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1558163.86 | 57043777.83 |
August | 0.107774E+10 | 0.436270E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1554762.61 | 70924742.74 |
September | 0.956342E+09 | 0.405926E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2186834.88 | 69807370.85 |
October | 0.994195E+09 | 0.441261E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8613797.59 | 0.111134E+09 |
November | 0.984487E+09 | 0.461092E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982636.10 | 0.163666E+09 |
December | 0.959235E+09 | 0.463341E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617718.12 | 0.171308E+09 |
Annual Sum or Average | 0.119305E+11 | 0.515447E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16735439.03 | 0.156952E+10 |
Minimum of Months | 0.901968E+09 | 0.388727E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 57043777.83 |
Maximum of Months | 0.107774E+10 | 0.470930E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8613797.59 | 0.209576E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.293711E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132290.32 | 0.119552E+09 |
February | 0.571020E+09 | 0.252353E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20614.89 | 0.137532E+09 |
March | 0.682301E+09 | 0.289413E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 0.148565E+09 |
April | 0.605444E+09 | 0.251201E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95215.85 | 90150479.46 |
May | 0.655854E+09 | 0.265704E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 | 0.108036E+09 |
June | 0.654023E+09 | 0.262784E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12840.75 | 56932833.61 |
July | 0.607275E+09 | 0.247460E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 857578.42 | 43142338.33 |
August | 0.682301E+09 | 0.276964E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 897147.55 | 53238379.82 |
September | 0.605444E+09 | 0.255796E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1455518.31 | 51155497.77 |
October | 0.629407E+09 | 0.276085E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4910743.12 | 80008647.71 |
November | 0.623262E+09 | 0.289848E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229447.56 | 0.116186E+09 |
December | 0.607275E+09 | 0.288188E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103042.41 | 0.122785E+09 |
Annual Sum or Average | 0.755301E+10 | 0.324951E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8714505.31 | 0.112728E+10 |
Minimum of Months | 0.571020E+09 | 0.247460E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 | 43142338.33 |
Maximum of Months | 0.682301E+09 | 0.293711E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4910743.12 | 0.148565E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.454308E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5053615.68 | 0.221893E+10 |
February | 0.901968E+09 | 0.393784E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2720835.97 | 0.204647E+10 |
March | 0.107774E+10 | 0.456243E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 | 0.258000E+10 |
April | 0.956342E+09 | 0.396849E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8384804.28 | 0.156365E+10 |
May | 0.103597E+10 | 0.420160E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.23 | 0.152267E+10 |
June | 0.103308E+10 | 0.416220E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1450809.58 | 0.104798E+10 |
July | 0.959235E+09 | 0.391899E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53241252.75 | 0.644548E+09 |
August | 0.107774E+10 | 0.438150E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54361158.35 | 0.760489E+09 |
September | 0.956342E+09 | 0.404560E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79409573.00 | 0.103121E+10 |
October | 0.994195E+09 | 0.428581E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133858E+09 | 0.104281E+10 |
November | 0.984487E+09 | 0.447472E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352480.34 | 0.199846E+10 |
December | 0.959235E+09 | 0.443785E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6707976.15 | 0.201316E+10 |
Annual Sum or Average | 0.119305E+11 | 0.509201E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345542E+09 | 0.184704E+11 |
Minimum of Months | 0.901968E+09 | 0.391899E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 | 0.644548E+09 |
Maximum of Months | 0.107774E+10 | 0.456243E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133858E+09 | 0.258000E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.291576E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 157034.82 | 0.118677E+09 |
February | 0.570983E+09 | 0.250959E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20776.35 | 0.138506E+09 |
March | 0.682256E+09 | 0.289422E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18965.66 | 0.148478E+09 |
April | 0.605404E+09 | 0.251236E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260913.34 | 92884379.01 |
May | 0.655811E+09 | 0.265262E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 0.111754E+09 |
June | 0.653980E+09 | 0.261754E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12853.85 | 59185871.10 |
July | 0.607235E+09 | 0.246339E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 973098.49 | 45021848.38 |
August | 0.682256E+09 | 0.276757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 940948.27 | 55013589.58 |
September | 0.605404E+09 | 0.256729E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1451632.07 | 54197809.44 |
October | 0.629366E+09 | 0.274359E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5158666.94 | 82274767.58 |
November | 0.623221E+09 | 0.285000E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 417112.83 | 0.117443E+09 |
December | 0.607235E+09 | 0.285469E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155814.23 | 0.122795E+09 |
Annual Sum or Average | 0.755252E+10 | 0.323486E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9567848.15 | 0.114623E+10 |
Minimum of Months | 0.570983E+09 | 0.246339E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 45021848.38 |
Maximum of Months | 0.682256E+09 | 0.291576E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5158666.94 | 0.148478E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.472676E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497246.81 | 0.264903E+09 |
February | 0.901968E+09 | 0.401636E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47638.77 | 0.312639E+09 |
March | 0.107774E+10 | 0.460452E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72722.59 | 0.337779E+09 |
April | 0.956342E+09 | 0.396716E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 683869.33 | 0.200801E+09 |
May | 0.103597E+10 | 0.418066E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245216E+09 |
June | 0.103308E+10 | 0.412868E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28517.54 | 0.131731E+09 |
July | 0.959235E+09 | 0.388953E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2176678.46 | 93992284.74 |
August | 0.107774E+10 | 0.436572E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2291644.84 | 0.116455E+09 |
September | 0.956342E+09 | 0.406561E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3405499.11 | 0.113119E+09 |
October | 0.994195E+09 | 0.443144E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12766797.23 | 0.177095E+09 |
November | 0.984487E+09 | 0.462592E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1334118.75 | 0.258015E+09 |
December | 0.959235E+09 | 0.465033E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 611815.67 | 0.272385E+09 |
Annual Sum or Average | 0.119305E+11 | 0.516527E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23916549.09 | 0.252413E+10 |
Minimum of Months | 0.901968E+09 | 0.388953E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93992284.74 |
Maximum of Months | 0.107774E+10 | 0.472676E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12766797.23 | 0.337779E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.294205E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139681.47 | 0.184165E+09 |
February | 0.421807E+09 | 0.252775E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22454.24 | 0.216844E+09 |
March | 0.502994E+09 | 0.289763E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.67 | 0.234260E+09 |
April | 0.447140E+09 | 0.251459E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127309.70 | 0.143112E+09 |
May | 0.484071E+09 | 0.265928E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171697E+09 |
June | 0.482240E+09 | 0.262986E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11606.19 | 92061552.27 |
July | 0.448971E+09 | 0.247647E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1191237.97 | 69026786.35 |
August | 0.502994E+09 | 0.277239E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1209136.70 | 83846221.12 |
September | 0.447140E+09 | 0.256081E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2198154.58 | 81009338.34 |
October | 0.465148E+09 | 0.276804E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7283810.23 | 0.124531E+09 |
November | 0.460569E+09 | 0.290414E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 254940.86 | 0.179111E+09 |
December | 0.448971E+09 | 0.288830E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107264.68 | 0.190012E+09 |
Annual Sum or Average | 0.557719E+10 | 0.325413E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12545742.29 | 0.176967E+10 |
Minimum of Months | 0.421807E+09 | 0.247647E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69026786.35 |
Maximum of Months | 0.502994E+09 | 0.294205E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7283810.23 | 0.234260E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.454761E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 236118.59 | 0.293167E+09 |
February | 0.901968E+09 | 0.393616E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47204.97 | 0.340756E+09 |
March | 0.107774E+10 | 0.456625E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356180E+09 |
April | 0.956342E+09 | 0.397263E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 231637.97 | 0.214438E+09 |
May | 0.103597E+10 | 0.420571E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248903E+09 |
June | 0.103308E+10 | 0.416664E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28518.94 | 0.131051E+09 |
July | 0.959235E+09 | 0.392179E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2110599.24 | 95939271.46 |
August | 0.107774E+10 | 0.438539E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2072962.71 | 0.122851E+09 |
September | 0.956342E+09 | 0.405086E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3362881.70 | 0.126902E+09 |
October | 0.994195E+09 | 0.428994E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10769309.99 | 0.197839E+09 |
November | 0.984487E+09 | 0.447774E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98314.89 | 0.284770E+09 |
December | 0.959235E+09 | 0.444149E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 181358.63 | 0.305856E+09 |
Annual Sum or Average | 0.119305E+11 | 0.509622E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19138907.63 | 0.271865E+10 |
Minimum of Months | 0.901968E+09 | 0.392179E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95939271.46 |
Maximum of Months | 0.107774E+10 | 0.456625E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10769309.99 | 0.356180E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.292185E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234619.55 | 0.183094E+09 |
February | 0.570983E+09 | 0.251370E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31570.63 | 0.217165E+09 |
March | 0.682256E+09 | 0.289781E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19810.76 | 0.232785E+09 |
April | 0.605404E+09 | 0.251523E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 408882.23 | 0.145668E+09 |
May | 0.655811E+09 | 0.265522E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175021E+09 |
June | 0.653980E+09 | 0.261991E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19014.81 | 93440748.81 |
July | 0.607235E+09 | 0.246565E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1458596.64 | 70408042.87 |
August | 0.682256E+09 | 0.277002E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1450417.58 | 85565447.85 |
September | 0.605404E+09 | 0.257137E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2262136.27 | 84120503.74 |
October | 0.629366E+09 | 0.275079E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7915320.49 | 0.126674E+09 |
November | 0.623221E+09 | 0.285414E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 634349.84 | 0.179929E+09 |
December | 0.607235E+09 | 0.286434E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 215465.41 | 0.189407E+09 |
Annual Sum or Average | 0.755252E+10 | 0.324000E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14650184.21 | 0.178328E+10 |
Minimum of Months | 0.570983E+09 | 0.246565E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70408042.87 |
Maximum of Months | 0.682256E+09 | 0.292185E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7915320.49 | 0.232785E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360925.96 | 0.385664E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44047.07 | 0.451658E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 | 0.477504E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463361.77 | 0.282599E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336789E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7247.16 | 0.179738E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1853209.68 | 0.132045E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719035.65 | 0.166207E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3766865.77 | 0.163147E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14196866.24 | 0.257893E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 852951.86 | 0.375383E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195239.77 | 0.401985E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23459765.79 | 0.361061E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132045E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14196866.24 | 0.477504E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831874.20 | 0.470270E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76052.36 | 0.553006E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35372.99 | 0.592619E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 939688.47 | 0.354911E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424438E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9849.09 | 0.229578E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2402628.61 | 0.169367E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2319570.96 | 0.212240E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4940246.39 | 0.204718E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18739180.29 | 0.321066E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1533416.66 | 0.461854E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545255.16 | 0.490945E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32373135.18 | 0.448501E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169367E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18739180.29 | 0.592619E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768945.47 | 0.454675E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12249.87 | 0.541956E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597140E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64026.71 | 0.388184E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464516E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265378E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1055855.03 | 0.207479E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773753.42 | 0.232477E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4709656.31 | 0.229805E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16526970.10 | 0.317794E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696424.40 | 0.446158E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240652.92 | 0.462636E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24848534.23 | 0.460820E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207479E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16526970.10 | 0.597140E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3696.64 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3696.64 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3696.64 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3696.64 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3696.64 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3696.64 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3696.64 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3696.64 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3696.64 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3696.64 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3696.64 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3696.64 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3696.64 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3696.64 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3696.64 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3696.64 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3696.64 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3696.64 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3696.64 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3696.64 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3696.64 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3696.64 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3696.64 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3696.64 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3696.64 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3696.64 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3696.64 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3696.64 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3696.64 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3696.64 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3696.64 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3696.64 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3696.64 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3696.64 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3696.64 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3696.64 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3696.64 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3696.64 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 779.28 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 | 15-JAN-10:00 | 634.57 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 689.92 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 01-FEB-12:00 | 651.32 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 520.87 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 | 11-MAR-13:05 | 752.39 | 28-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 434.57 | 21-APR-15:00 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.22 | 30-APR-10:50 | 453.79 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 423.95 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 474.93 | 20-MAY-17:53 |
June | 1306.65 | 01-JUN-09:09 | 414.52 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 29-JUN-11:00 | 314.86 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 402.42 | 12-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.26 | 23-JUL-10:53 | 272.99 | 09-JUL-17:20 |
August | 1306.65 | 01-AUG-09:09 | 424.96 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 | 06-AUG-12:45 | 224.11 | 27-AUG-18:10 |
September | 1306.65 | 01-SEP-09:09 | 554.05 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.88 | 29-SEP-14:00 | 276.59 | 04-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 569.00 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.41 | 15-OCT-09:00 | 473.21 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 | 19-NOV-12:52 | 595.15 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.41 | 25-DEC-12:00 | 592.86 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 402.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.11 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 343.41 | 752.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 493.35 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 15-JAN-10:00 | 422.78 | 27-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 438.86 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 01-FEB-12:00 | 431.76 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 330.63 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 500.95 | 28-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 277.75 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 26-APR-13:00 | 303.34 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 256.84 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 312.73 | 29-MAY-13:00 |
June | 827.22 | 01-JUN-09:09 | 252.13 | 16-JUN-14:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 29-JUN-11:00 | 220.51 | 04-JUN-14:10 |
July | 827.22 | 03-JUL-09:09 | 235.33 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.74 | 31-JUL-13:00 | 188.75 | 04-JUL-13:45 |
August | 827.22 | 01-AUG-09:09 | 255.51 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 17-AUG-14:00 | 156.93 | 27-AUG-18:10 |
September | 827.22 | 01-SEP-09:09 | 316.78 | 21-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 29-SEP-14:00 | 196.84 | 03-SEP-17:45 |
October | 827.22 | 02-OCT-09:09 | 376.54 | 20-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.67 | 15-OCT-12:46 | 320.11 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 493.35 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.20 | 19-NOV-12:52 | 398.91 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 493.35 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 17-DEC-13:00 | 396.51 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.93 | |||||
Maximum of Months | 827.22 | 493.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 181.67 | 500.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 779.28 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 15-JAN-10:00 | 653.80 | 06-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 684.17 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 01-FEB-12:00 | 711.96 | 20-FEB-15:00 |
March | 1306.65 | 01-MAR-10:09 | 437.49 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 754.85 | 28-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 432.83 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 26-APR-13:00 | 475.59 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 426.23 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 462.45 | 29-MAY-13:00 |
June | 1306.65 | 01-JUN-09:09 | 419.94 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 29-JUN-11:00 | 313.59 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 409.64 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 | 31-JUL-13:00 | 270.98 | 09-JUL-17:20 |
August | 1306.65 | 01-AUG-09:09 | 426.13 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 17-AUG-14:00 | 238.83 | 27-AUG-18:10 |
September | 1306.65 | 01-SEP-09:09 | 542.75 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.44 | 29-SEP-14:00 | 333.49 | 24-SEP-15:00 |
October | 1306.65 | 02-OCT-09:09 | 529.24 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.81 | 15-OCT-12:57 | 505.68 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 18-NOV-13:05 | 624.07 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 | 05-DEC-10:00 | 613.57 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 409.64 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.83 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 261.81 | 754.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 493.32 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 | 15-JAN-10:00 | 425.21 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 428.07 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 01-FEB-12:00 | 434.35 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 352.80 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 11-MAR-11:05 | 503.19 | 28-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 276.44 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.62 | 30-APR-10:50 | 389.51 | 16-APR-17:40 |
May | 827.17 | 01-MAY-09:09 | 274.44 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 406.76 | 20-MAY-17:53 |
June | 827.17 | 01-JUN-09:09 | 270.81 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 29-JUN-11:00 | 287.47 | 03-JUN-17:07 |
July | 827.17 | 03-JUL-09:09 | 267.03 | 12-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | 23-JUL-10:53 | 259.20 | 09-JUL-17:20 |
August | 827.17 | 01-AUG-09:09 | 275.64 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 17-AUG-14:00 | 203.22 | 27-AUG-18:10 |
September | 827.17 | 01-SEP-09:09 | 368.31 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 29-SEP-14:00 | 273.97 | 03-SEP-16:50 |
October | 827.17 | 02-OCT-09:09 | 371.34 | 24-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.92 | 15-OCT-09:00 | 325.20 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 493.32 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.55 | 19-NOV-12:12 | 402.84 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 493.32 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.61 | 25-DEC-11:55 | 399.52 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 267.03 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.22 | |||||
Maximum of Months | 827.17 | 493.32 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 225.92 | 503.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 779.28 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 15-JAN-10:00 | 370.80 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 686.50 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 01-FEB-12:10 | 373.74 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 510.77 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 11-MAR-14:00 | 410.21 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 432.40 | 21-APR-15:00 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.01 | 30-APR-11:30 | 248.09 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 421.26 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 242.67 | 20-MAY-17:53 |
June | 1306.65 | 01-JUN-09:09 | 411.35 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 29-JUN-11:00 | 167.97 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 398.66 | 12-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.52 | 23-JUL-11:00 | 132.86 | 02-JUL-18:55 |
August | 1306.65 | 01-AUG-09:09 | 422.32 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 06-AUG-11:25 | 120.60 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 545.39 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 | 29-SEP-14:00 | 138.07 | 04-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 560.08 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.46 | 15-OCT-13:00 | 273.71 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.72 | 19-NOV-12:52 | 365.52 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 | 25-DEC-12:00 | 341.10 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 398.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 120.60 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 190.46 | 410.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 493.35 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 15-JAN-10:00 | 250.89 | 27-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 437.18 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 01-FEB-12:00 | 253.83 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 323.81 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 274.69 | 28-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 276.62 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 26-APR-13:00 | 171.83 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 254.67 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 162.23 | 27-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 249.93 | 16-JUN-14:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 29-JUN-11:00 | 113.93 | 06-JUN-21:20 |
July | 827.22 | 03-JUL-09:09 | 235.33 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 31-JUL-13:00 | 97.63 | 02-JUL-18:55 |
August | 827.22 | 01-AUG-09:09 | 253.24 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | 17-AUG-14:00 | 83.43 | 21-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 276.80 | 21-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 29-SEP-14:00 | 113.34 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 372.99 | 20-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.54 | 15-OCT-13:00 | 192.27 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 493.35 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 19-NOV-12:54 | 251.51 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 493.35 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 17-DEC-12:53 | 233.56 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 83.43 | |||||
Maximum of Months | 827.22 | 493.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 101.54 | 274.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 779.28 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1522.47 | 18-JAN-13:00 | 14271.86 | 09-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 680.45 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.91 | 01-FEB-12:10 | 11603.03 | 09-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 435.42 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 11956.15 | 30-MAR-06:03 |
April | 1306.65 | 03-APR-09:09 | 430.56 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.27 | 26-APR-11:05 | 9144.42 | 03-APR-06:05 |
May | 1306.65 | 01-MAY-09:09 | 423.66 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 03-MAY-12:00 | 8054.71 | 15-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 417.10 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 668.94 | 29-JUN-11:10 | 6514.17 | 01-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 406.32 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3174.42 | 19-JUL-12:00 | 5814.23 | 17-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 423.55 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.94 | 18-AUG-12:00 | 6735.55 | 28-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 533.57 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8526.64 | 29-SEP-11:02 | 7664.66 | 20-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 519.26 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8643.06 | 16-OCT-11:02 | 9726.78 | 30-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.59 | 28-NOV-14:00 | 10596.13 | 24-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1182.18 | 19-DEC-13:00 | 13163.11 | 22-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 406.32 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 5814.23 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8643.06 | 14271.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 493.32 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 | 15-JAN-10:00 | 251.58 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 425.93 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 01-FEB-12:00 | 254.74 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 348.50 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 11-MAR-12:20 | 277.51 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 275.29 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 30-APR-10:50 | 201.18 | 16-APR-17:55 |
May | 827.17 | 01-MAY-09:09 | 273.19 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 214.57 | 20-MAY-17:53 |
June | 827.17 | 01-JUN-09:09 | 269.41 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 29-JUN-11:00 | 147.10 | 03-JUN-17:10 |
July | 827.17 | 03-JUL-09:09 | 265.50 | 12-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 23-JUL-11:00 | 131.07 | 09-JUL-17:10 |
August | 827.17 | 01-AUG-09:09 | 274.45 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 06-AUG-11:25 | 101.67 | 27-AUG-17:55 |
September | 827.17 | 01-SEP-09:09 | 364.56 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 29-SEP-14:00 | 139.80 | 03-SEP-16:40 |
October | 827.17 | 02-OCT-09:09 | 367.60 | 24-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.88 | 15-OCT-08:52 | 194.45 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 493.32 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 19-NOV-12:52 | 255.93 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 493.32 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 25-DEC-12:00 | 234.98 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 265.50 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 101.67 | |||||
Maximum of Months | 827.17 | 493.32 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 120.88 | 277.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 779.28 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.51 | 15-JAN-10:00 | 573.03 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 689.91 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 01-FEB-12:00 | 595.62 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 520.85 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 11-MAR-13:05 | 641.52 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 434.57 | 21-APR-15:00 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 30-APR-10:53 | 401.06 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 423.95 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 402.65 | 20-MAY-17:53 |
June | 1306.65 | 01-JUN-09:09 | 414.51 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 29-JUN-11:00 | 271.12 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 402.41 | 12-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 23-JUL-10:50 | 218.03 | 02-JUL-18:55 |
August | 1306.65 | 01-AUG-09:09 | 424.96 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.57 | 06-AUG-13:10 | 194.47 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 554.03 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.70 | 29-SEP-14:00 | 231.76 | 04-SEP-17:55 |
October | 1306.65 | 02-OCT-09:09 | 569.00 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.08 | 15-OCT-08:52 | 430.66 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.05 | 19-NOV-12:52 | 562.88 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.69 | 25-DEC-12:00 | 533.52 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 402.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.47 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 281.08 | 641.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 493.35 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 | 15-JAN-10:00 | 381.57 | 27-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 438.85 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 01-FEB-12:00 | 394.84 | 25-FEB-03:00 |
March | 805.43 | 01-MAR-08:09 | 330.64 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 11-MAR-13:10 | 426.24 | 28-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 277.75 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 | 26-APR-13:00 | 268.27 | 21-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 256.84 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 259.12 | 20-MAY-17:53 |
June | 805.43 | 01-JUN-07:10 | 252.12 | 16-JUN-14:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 29-JUN-11:00 | 184.47 | 04-JUN-13:45 |
July | 805.43 | 03-JUL-07:10 | 235.33 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 31-JUL-13:00 | 152.64 | 04-JUL-13:45 |
August | 805.43 | 01-AUG-07:10 | 255.51 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 | 17-AUG-14:10 | 129.81 | 21-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 316.76 | 21-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.14 | 29-SEP-14:10 | 181.94 | 03-SEP-07:00 |
October | 805.43 | 02-OCT-07:10 | 376.53 | 20-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.39 | 15-OCT-12:42 | 290.67 | 30-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 493.35 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 19-NOV-12:52 | 376.22 | 23-NOV-04:00 |
December | 805.43 | 01-DEC-08:09 | 493.35 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 | 17-DEC-12:53 | 356.39 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.81 | |||||
Maximum of Months | 805.43 | 493.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 146.39 | 426.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 779.28 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 14-JAN-11:00 | 585.43 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 684.16 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 01-FEB-12:00 | 600.63 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 437.49 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 649.38 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 432.83 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 26-APR-13:00 | 401.69 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 426.22 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 389.00 | 20-MAY-17:53 |
June | 1306.65 | 01-JUN-09:09 | 419.94 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 29-JUN-11:00 | 270.19 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 409.64 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.37 | 31-JUL-13:00 | 218.66 | 02-JUL-18:55 |
August | 1306.65 | 01-AUG-09:09 | 426.13 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 17-AUG-14:00 | 196.51 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 542.73 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.67 | 29-SEP-14:00 | 283.96 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 529.22 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.21 | 15-OCT-12:46 | 456.84 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 779.28 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 18-NOV-13:10 | 584.71 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 779.28 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 05-DEC-10:00 | 549.17 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 409.64 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.51 | |||||
Maximum of Months | 1306.65 | 779.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 215.21 | 649.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 493.32 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.57 | 15-JAN-10:00 | 383.54 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 428.06 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 01-FEB-12:00 | 396.81 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 352.79 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 11-MAR-11:05 | 432.49 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 276.44 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.36 | 30-APR-10:53 | 322.41 | 16-APR-17:40 |
May | 827.17 | 01-MAY-09:09 | 274.44 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 344.94 | 20-MAY-17:53 |
June | 827.17 | 01-JUN-09:09 | 270.81 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 29-JUN-11:00 | 236.36 | 03-JUN-17:07 |
July | 827.17 | 03-JUL-09:09 | 267.03 | 12-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.36 | 23-JUL-10:50 | 202.79 | 09-JUL-17:30 |
August | 827.17 | 01-AUG-09:09 | 275.64 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.07 | 17-AUG-14:00 | 170.46 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 368.30 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 | 29-SEP-14:00 | 225.90 | 03-SEP-16:40 |
October | 827.17 | 02-OCT-09:09 | 371.33 | 24-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.82 | 15-OCT-08:52 | 294.90 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 493.32 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.20 | 19-NOV-12:33 | 379.57 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 493.32 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 | 25-DEC-12:00 | 358.72 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 267.03 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.46 | |||||
Maximum of Months | 827.17 | 493.32 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 184.82 | 432.49 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.42 | 15-JAN-10:00 | 818.12 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.52 | 01-FEB-12:00 | 868.59 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 11-MAR-11:00 | 924.15 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.12 | 30-APR-10:53 | 561.73 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 534.79 | 20-MAY-17:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 29-JUN-11:00 | 370.22 | 06-JUN-21:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 23-JUL-11:00 | 289.99 | 02-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 | 06-AUG-12:53 | 266.60 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.83 | 29-SEP-13:40 | 328.31 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.03 | 15-OCT-08:52 | 620.82 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 19-NOV-13:00 | 844.56 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 04-DEC-10:00 | 767.57 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.60 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.03 | 924.15 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 15-JAN-10:00 | 1027.35 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 01-FEB-12:00 | 1079.00 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 11-MAR-13:00 | 1152.56 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 30-APR-11:00 | 702.83 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 675.05 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 29-JUN-11:00 | 476.65 | 06-JUN-21:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.96 | 23-JUL-10:53 | 372.73 | 02-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.42 | 06-AUG-12:53 | 340.72 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 | 29-SEP-13:40 | 417.12 | 04-SEP-17:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.67 | 15-OCT-08:52 | 771.26 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.66 | 19-NOV-13:00 | 1042.00 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 | 04-DEC-10:00 | 959.39 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.72 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.67 | 1152.56 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.23 | 15-JAN-10:00 | 950.66 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 01-FEB-12:00 | 990.11 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1159.22 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 26-APR-13:00 | 799.31 | 16-APR-17:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 826.41 | 07-MAY-14:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 614.67 | 04-JUN-14:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 | 31-JUL-13:00 | 524.98 | 09-JUL-16:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 | 17-AUG-14:00 | 413.67 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.76 | 29-SEP-13:30 | 521.64 | 03-SEP-16:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.21 | 15-OCT-08:52 | 703.57 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 | 19-NOV-09:55 | 854.80 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.61 | 04-DEC-10:00 | 904.69 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.21 | 1159.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15654.54 | 20-JAN-16:20 | 6035.01 | 3696.64 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15320.12 | 03-FEB-17:00 | 6035.01 | 3696.64 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15685.61 | 24-MAR-16:00 | 6035.01 | 3696.64 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19661.81 | 28-APR-06:02 | 6352.64 | 6161.06 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19472.88 | 05-MAY-06:03 | 5082.11 | 4928.85 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22276.39 | 28-JUN-06:03 | 5082.11 | 4928.85 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29984.77 | 17-JUL-06:02 | 6352.64 | 6161.06 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29908.95 | 21-AUG-06:03 | 5082.11 | 4928.85 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27578.57 | 05-SEP-06:03 | 5082.11 | 4928.85 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31678.14 | 02-OCT-06:03 | 3811.58 | 3696.64 | 18132.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22255.45 | 01-NOV-06:02 | 7623.17 | 7393.27 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15572.52 | 07-DEC-16:20 | 6035.01 | 3696.64 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15320.12 | 3811.58 | 3696.64 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31678.14 | 7623.17 | 7393.27 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4658.62 | 18-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.80 |
February | 4308.76 | 01-FEB-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.00 |
March | 5888.14 | 23-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.19 |
April | 7508.18 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 0.00 |
May | 6669.83 | 03-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 |
June | 6586.55 | 30-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.74 |
July | 8057.49 | 31-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
August | 7778.47 | 14-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 |
September | 8772.19 | 29-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.43 | 0.00 |
October | 8917.99 | 16-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.34 | 0.00 |
November | 4142.62 | 10-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.48 |
December | 4161.49 | 19-DEC-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4142.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8917.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.43 | 102.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1190.26 | 19-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 |
February | 1066.32 | 03-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 |
March | 1595.44 | 23-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 |
April | 2078.29 | 26-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.86 |
May | 1981.95 | 03-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 |
June | 2336.00 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 |
July | 3042.30 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 0.00 |
August | 2889.78 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
September | 3406.41 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.63 | 0.00 |
October | 4214.23 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.21 | 0.00 |
November | 1112.90 | 10-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.82 |
December | 1223.17 | 07-DEC-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1066.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4214.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.63 | 91.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1776.21 | 18-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 |
February | 1554.88 | 03-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 |
March | 1892.59 | 23-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 |
April | 2244.33 | 26-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 |
May | 2089.06 | 04-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 |
June | 2357.97 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.47 |
July | 3108.14 | 31-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 |
August | 3014.38 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
September | 3350.72 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.27 | 0.00 |
October | 3878.06 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 0.00 |
November | 1615.65 | 01-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.96 |
December | 1744.74 | 19-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1554.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3878.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.27 | 53.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11497.78 | 20-JAN-16:20 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11215.56 | 03-FEB-17:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11867.81 | 24-MAR-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12847.23 | 27-APR-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12907.27 | 04-MAY-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13429.98 | 26-JUN-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18008.96 | 31-JUL-06:03 | 5082.11 | 4928.85 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15227.47 | 21-AUG-06:03 | 5082.11 | 4928.85 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14168.95 | 29-SEP-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26109.96 | 02-OCT-06:03 | 3811.58 | 3696.64 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11927.26 | 01-NOV-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11447.02 | 07-DEC-16:20 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11215.56 | 3811.58 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26109.96 | 6035.01 | 4928.85 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11144.54 | 19-JAN-15:50 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11063.34 | 02-FEB-16:20 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12571.95 | 24-MAR-15:30 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14223.61 | 27-APR-15:20 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14429.36 | 03-MAY-15:20 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15166.80 | 26-JUN-14:00 | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16264.76 | 31-JUL-14:00 | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15838.79 | 14-AUG-14:00 | 6198.29 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15923.79 | 29-SEP-14:40 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19007.13 | 02-OCT-06:03 | 3811.58 | 3696.64 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11352.88 | 01-NOV-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11172.05 | 07-DEC-16:00 | 6035.01 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11063.34 | 3811.58 | 3696.64 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19007.13 | 6198.29 | 3696.64 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2470.73 | 18-JAN-14:50 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
February | 2165.11 | 03-FEB-15:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
March | 2811.29 | 23-MAR-15:20 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 |
April | 3961.80 | 26-APR-14:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 0.00 |
May | 4262.13 | 04-MAY-13:50 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
June | 4132.10 | 26-JUN-16:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 |
July | 4791.50 | 31-JUL-14:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 0.00 |
August | 4558.64 | 18-AUG-15:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 | 0.00 |
September | 5481.53 | 29-SEP-13:50 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 109.75 | 0.00 |
October | 5719.82 | 16-OCT-13:10 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 105.83 | 0.00 |
November | 2247.83 | 10-NOV-14:10 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.10 |
December | 2475.56 | 05-DEC-15:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2165.11 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5719.82 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 109.75 | 49.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3045.84 | 20-JAN-10:00 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 |
February | 2848.18 | 02-FEB-10:10 | 1654.44 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 |
March | 4661.32 | 23-MAR-09:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
April | 7296.51 | 30-APR-09:43 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.43 |
May | 4991.64 | 04-MAY-09:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 |
June | 7447.58 | 18-JUN-08:23 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.61 |
July | 11112.49 | 23-JUL-08:32 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.43 |
August | 7586.00 | 20-AUG-09:13 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.52 |
September | 7798.20 | 10-SEP-08:43 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 |
October | 10970.27 | 15-OCT-08:43 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 135.34 | 0.00 |
November | 2615.55 | 01-NOV-09:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.96 |
December | 3001.42 | 05-DEC-09:50 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2615.55 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11112.49 | 1654.44 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 135.34 | 76.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14137.21 | 22-JAN-13:53 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.78 |
February | 11401.77 | 20-FEB-13:43 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.37 |
March | 9338.03 | 19-MAR-13:13 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.35 |
April | 7488.87 | 26-APR-13:10 | 2613.31 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 | 0.00 |
May | 5677.85 | 04-MAY-12:40 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
June | 5106.80 | 30-JUN-13:10 | 2613.31 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
July | 7163.09 | 31-JUL-12:50 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 42.42 | 0.00 |
August | 8110.87 | 30-AUG-13:00 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 11333.97 | 29-SEP-13:10 | 2613.31 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 103.43 | 0.00 |
October | 14419.61 | 15-OCT-12:42 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 212.87 | 0.00 |
November | 14066.83 | 19-NOV-11:02 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 |
December | 13793.91 | 03-DEC-13:53 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5106.80 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14419.61 | 2613.31 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 212.87 | 516.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4532.00 | 18-JAN-15:00 | 827.17 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 |
February | 4869.47 | 22-FEB-15:40 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.85 |
March | 7129.23 | 19-MAR-15:53 | 127.16 | 39.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.02 |
April | 12354.83 | 30-APR-16:23 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.37 |
May | 11567.37 | 28-MAY-16:03 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.49 |
June | 11577.04 | 18-JUN-15:43 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.20 |
July | 12943.65 | 23-JUL-15:52 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.02 |
August | 10861.00 | 06-AUG-17:42 | 0.00 | 52.28 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.44 |
September | 11981.70 | 10-SEP-15:23 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.98 |
October | 12330.40 | 15-OCT-15:22 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 | 0.00 |
November | 4644.12 | 10-NOV-14:50 | 827.17 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 |
December | 4548.01 | 19-DEC-15:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4532.00 | 0.00 | 39.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12943.65 | 827.17 | 235.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 | 234.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1875.69 | 18-JAN-13:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 0.00 |
February | 1553.78 | 01-FEB-12:05 | 1375.43 | 743.44 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 0.00 |
March | 1634.26 | 23-MAR-15:20 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 |
April | 2466.45 | 26-APR-14:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 0.00 |
May | 2892.42 | 04-MAY-14:10 | 2544.47 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
June | 2839.49 | 27-JUN-16:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
July | 3423.00 | 31-JUL-13:10 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
August | 3352.54 | 18-AUG-15:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 |
September | 3972.48 | 29-SEP-13:10 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 | 0.00 |
October | 4281.78 | 16-OCT-12:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.73 | 0.00 |
November | 1763.48 | 19-NOV-13:13 | 267.84 | 82.59 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 | 0.00 |
December | 1747.10 | 19-DEC-14:30 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1553.78 | 267.84 | 82.59 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4281.78 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.73 | 10.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2733.45 | 20-JAN-09:50 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
February | 2438.81 | 21-FEB-10:00 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3647.75 | 23-MAR-09:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 |
April | 5358.94 | 30-APR-09:43 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 |
May | 3987.82 | 04-MAY-09:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
June | 4791.80 | 25-JUN-09:53 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.12 |
July | 8033.83 | 04-JUL-09:02 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 |
August | 5269.77 | 14-AUG-09:10 | 1654.44 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
September | 5526.60 | 10-SEP-08:43 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 |
October | 9041.60 | 15-OCT-08:32 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 64.69 | 0.00 |
November | 2576.87 | 01-NOV-09:30 | 827.22 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 |
December | 2679.79 | 05-DEC-09:50 | 805.43 | 235.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2438.81 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9041.60 | 1654.44 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 64.69 | 43.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10978.07 | 22-JAN-12:13 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.44 |
February | 9258.74 | 20-FEB-13:33 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.01 |
March | 6287.80 | 23-MAR-14:00 | 1306.65 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.71 |
April | 6177.27 | 26-APR-12:00 | 687.71 | 371.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.28 | 0.00 |
May | 3904.20 | 01-MAY-12:10 | 2544.47 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.70 |
June | 3327.83 | 27-JUN-13:00 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
July | 7977.45 | 31-JUL-12:00 | 687.71 | 371.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3164.28 | 0.00 |
August | 7912.12 | 18-AUG-12:00 | 687.71 | 371.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.94 | 0.00 |
September | 11084.70 | 29-SEP-12:00 | 687.71 | 371.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6967.66 | 0.00 |
October | 11502.55 | 01-OCT-12:52 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 |
November | 11604.27 | 19-NOV-13:13 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 |
December | 11311.38 | 25-DEC-13:02 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3327.83 | 200.88 | 61.94 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11604.27 | 2544.47 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 6967.66 | 328.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3360.41 | 18-JAN-15:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
February | 3815.47 | 22-FEB-16:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 |
March | 4620.41 | 23-MAR-16:00 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
April | 5201.59 | 26-APR-16:00 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
May | 7133.39 | 28-MAY-16:42 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.78 |
June | 6824.03 | 18-JUN-17:03 | 0.00 | 52.28 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.77 |
July | 8422.39 | 23-JUL-16:22 | 254.33 | 78.43 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
August | 7341.43 | 06-AUG-16:43 | 127.16 | 39.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.77 |
September | 7825.80 | 10-SEP-15:43 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.39 |
October | 9810.82 | 15-OCT-15:11 | 296.72 | 91.50 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 0.00 |
November | 3808.76 | 07-NOV-15:40 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 |
December | 3649.45 | 19-DEC-15:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3360.41 | 0.00 | 39.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9810.82 | 805.38 | 235.31 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 107.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2407.02 | 24-JAN-15:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 0.00 |
February | 2198.04 | 03-FEB-15:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
March | 2608.41 | 23-MAR-15:20 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 |
April | 3531.73 | 26-APR-14:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
May | 3861.51 | 04-MAY-14:10 | 2544.47 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
June | 3757.45 | 26-JUN-16:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 |
July | 4285.76 | 31-JUL-13:10 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 0.00 |
August | 4112.97 | 18-AUG-15:00 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
September | 4899.53 | 29-SEP-13:10 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 0.00 |
October | 5174.94 | 16-OCT-12:30 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 0.00 |
November | 2280.57 | 01-NOV-14:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.01 |
December | 2423.91 | 05-DEC-15:00 | 1306.65 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2198.04 | 1272.23 | 371.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5174.94 | 2613.31 | 743.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 35.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3984.76 | 20-JAN-11:05 | 1610.86 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 |
February | 4484.42 | 09-FEB-13:02 | 4027.14 | 1176.64 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 |
March | 5729.62 | 23-MAR-10:05 | 1610.86 | 470.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
April | 7405.20 | 30-APR-09:53 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.05 |
May | 6702.81 | 28-MAY-08:23 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.79 |
June | 7400.13 | 25-JUN-08:63 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.16 |
July | 10924.05 | 23-JUL-08:23 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 |
August | 7247.66 | 06-AUG-10:03 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.09 |
September | 7390.13 | 29-SEP-12:02 | 4027.14 | 1176.64 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 | 0.00 |
October | 10807.49 | 15-OCT-08:23 | 169.56 | 52.29 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 77.93 | 0.00 |
November | 4160.39 | 01-NOV-12:02 | 3221.71 | 941.31 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
December | 4530.36 | 01-DEC-13:02 | 4027.14 | 1176.64 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3984.76 | 127.17 | 39.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10924.05 | 4027.14 | 1176.64 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 77.93 | 120.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12854.73 | 22-JAN-12:43 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.60 |
February | 12063.06 | 20-FEB-13:13 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.45 |
March | 8670.53 | 19-MAR-13:13 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.82 |
April | 6899.42 | 26-APR-13:00 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 |
May | 5215.49 | 04-MAY-12:30 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
June | 4599.65 | 30-JUN-13:10 | 2613.31 | 743.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
July | 6577.44 | 31-JUL-12:40 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 0.00 |
August | 7583.17 | 30-AUG-12:50 | 1272.23 | 371.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
September | 10359.31 | 29-SEP-12:04 | 6361.16 | 1858.59 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 | 0.00 |
October | 13199.70 | 01-OCT-12:52 | 334.80 | 103.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.39 |
November | 12850.46 | 19-NOV-11:02 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.21 |
December | 12755.65 | 25-DEC-13:02 | 267.84 | 82.59 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4599.65 | 200.88 | 61.94 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13199.70 | 6361.16 | 1858.59 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 | 428.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4406.50 | 18-JAN-15:00 | 827.17 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
February | 4832.93 | 22-FEB-15:40 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 |
March | 6600.98 | 19-MAR-15:53 | 127.16 | 39.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.20 |
April | 7025.97 | 23-APR-16:23 | 127.16 | 39.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.65 |
May | 10699.91 | 28-MAY-16:03 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.78 |
June | 11676.95 | 25-JUN-16:22 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.13 |
July | 11413.85 | 09-JUL-15:32 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11674.91 | 27-AUG-16:02 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.66 |
September | 11372.99 | 04-SEP-16:03 | 169.55 | 52.28 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.93 |
October | 11194.82 | 15-OCT-15:42 | 211.94 | 65.36 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 0.00 |
November | 4554.56 | 07-NOV-15:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 |
December | 4449.29 | 19-DEC-15:30 | 805.38 | 235.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4406.50 | 127.16 | 39.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11676.95 | 827.17 | 235.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 203.65 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.846311E+11 | 83757.91 | 02-JAN-07:10 | 0.125438E+11 | 34176.09 | 03-JAN-07:19 |
February | 0.740257E+11 | 78407.20 | 03-FEB-14:00 | 0.103056E+11 | 22533.97 | 09-FEB-07:19 |
March | 0.856032E+11 | 86458.96 | 23-MAR-15:09 | 0.126414E+11 | 27661.40 | 30-MAR-06:40 |
April | 0.835188E+11 | 93109.92 | 26-APR-12:00 | 0.103385E+11 | 18261.81 | 01-APR-06:30 |
May | 0.878462E+11 | 84056.22 | 03-MAY-12:00 | 0.106827E+11 | 9753.48 | 01-MAY-11:00 |
June | 0.943189E+11 | 94848.57 | 29-JUN-12:00 | 0.103514E+11 | 9712.49 | 02-JUN-11:09 |
July | 0.103745E+12 | 113150.18 | 31-JUL-15:00 | 0.102042E+11 | 9680.53 | 03-JUL-11:09 |
August | 0.113427E+12 | 108416.16 | 15-AUG-15:30 | 0.106514E+11 | 9675.58 | 24-AUG-11:09 |
September | 0.953092E+11 | 115709.40 | 29-SEP-12:00 | 0.100425E+11 | 9703.70 | 29-SEP-11:20 |
October | 0.998843E+11 | 120214.46 | 16-OCT-10:00 | 0.104884E+11 | 11681.65 | 12-OCT-06:19 |
November | 0.829008E+11 | 80152.65 | 28-NOV-13:00 | 0.104586E+11 | 17529.25 | 24-NOV-07:10 |
December | 0.835241E+11 | 81694.72 | 05-DEC-15:09 | 0.116972E+11 | 28317.07 | 22-DEC-07:10 |
Annual Sum or Average | 0.108873E+13 | 0.130406E+12 | ||||
Minimum of Months | 0.740257E+11 | 78407.20 | 0.100425E+11 | 9675.58 | ||
Maximum of Months | 0.113427E+12 | 120214.46 | 0.126414E+11 | 34176.09 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.955566E+10 | 17692.61 | 29-JAN-12:09 | 0.00 | 0.00 |
February | 0.992946E+10 | 20775.75 | 22-FEB-11:00 | 0.00 | 0.00 |
March | 0.135773E+11 | 23529.50 | 21-MAR-12:30 | 0.00 | 0.00 |
April | 0.189815E+11 | 26646.08 | 29-APR-11:39 | 0.00 | 0.00 |
May | 0.194379E+11 | 26813.75 | 27-MAY-11:39 | 0.00 | 0.00 |
June | 0.196698E+11 | 26653.96 | 13-JUN-11:50 | 0.00 | 0.00 |
July | 0.219325E+11 | 25765.90 | 02-JUL-11:00 | 0.00 | 0.00 |
August | 0.203182E+11 | 24654.76 | 01-AUG-12:09 | 0.00 | 0.00 |
September | 0.155703E+11 | 24501.51 | 02-SEP-11:00 | 0.00 | 0.00 |
October | 0.118673E+11 | 21362.26 | 03-OCT-11:39 | 0.00 | 0.00 |
November | 0.982229E+10 | 18473.54 | 02-NOV-11:30 | 0.00 | 0.00 |
December | 0.902936E+10 | 16416.91 | 02-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.179692E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.902936E+10 | 16416.91 | 0.00 | 0.00 | |
Maximum of Months | 0.219325E+11 | 26813.75 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.150905E+11 | 0.362556E+10 | 0.545046E+11 | 0.977492E+09 | 0.430716E+10 | 12379742.02 | 0.160282E+10 | 0.451061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134684E+11 | 0.298755E+10 | 0.493409E+11 | 0.884444E+09 | 0.385804E+10 | 11196021.66 | 0.777674E+09 | 0.269753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158611E+11 | 0.289121E+10 | 0.567112E+11 | 0.102337E+10 | 0.437046E+10 | 12675672.10 | 0.142779E+10 | 0.330536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140492E+11 | 0.241100E+10 | 0.526212E+11 | 0.941247E+09 | 0.551806E+10 | 11960507.72 | 0.399153E+09 | 0.756704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150717E+11 | 0.223378E+10 | 0.556079E+11 | 0.100016E+10 | 0.568456E+10 | 12527707.06 | 0.288691E+09 | 0.794682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149717E+11 | 0.206398E+10 | 0.546110E+11 | 0.984503E+09 | 0.697306E+10 | 12231776.97 | 0.102528E+09 | 0.145998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140380E+11 | 0.216719E+10 | 0.536070E+11 | 0.956732E+09 | 0.862252E+10 | 12256437.81 | 3185207.72 | 0.243383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156599E+11 | 0.237087E+10 | 0.567112E+11 | 0.102327E+10 | 0.980873E+10 | 12675672.10 | 5270271.96 | 0.278348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141324E+11 | 0.262436E+10 | 0.525990E+11 | 0.941060E+09 | 0.753036E+10 | 11960507.72 | 28338924.71 | 0.174418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148206E+11 | 0.313446E+10 | 0.545158E+11 | 0.977363E+09 | 0.723400E+10 | 12379742.02 | 91975541.36 | 0.190977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148839E+11 | 0.340371E+10 | 0.533244E+11 | 0.959290E+09 | 0.484028E+10 | 12059151.09 | 0.301151E+09 | 0.517604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146625E+11 | 0.372653E+10 | 0.535958E+11 | 0.957111E+09 | 0.443885E+10 | 12256437.81 | 0.783772E+09 | 0.534716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176710E+12 | 0.336402E+11 | 0.647750E+12 | 0.116260E+11 | 0.731861E+11 | 0.146559E+09 | 0.581235E+10 | 0.139863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134684E+11 | 0.206398E+10 | 0.493409E+11 | 0.884444E+09 | 0.385804E+10 | 11196021.66 | 3185207.72 | 0.269753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158611E+11 | 0.372653E+10 | 0.567112E+11 | 0.102337E+10 | 0.980873E+10 | 12675672.10 | 0.160282E+10 | 0.278348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.176642E+10 | 0.00 | 0.107774E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.539037E+09 | 0.00 | 0.976652E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.154599E+10 | 0.00 | 0.110954E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 51573277.30 | 0.00 | 0.102870E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3807761.65 | 0.00 | 0.106789E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.103514E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.102042E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.106514E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.100425E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 14762118.87 | 0.00 | 0.104736E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.126853E+09 | 0.00 | 0.103318E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.111533E+10 | 0.00 | 0.105819E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.516377E+10 | 0.00 | 0.125242E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.976652E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.176642E+10 | 0.00 | 0.110954E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 18725.62 | 02-JAN-16:49 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 830.04 | 02-JAN-16:00 | 8951.32 | 18-JAN-15:30 | 6.85 | 02-JAN-17:10 | 56601.18 | 02-JAN-07:10 |
February | 17801.98 | 27-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 828.44 | 27-FEB-16:00 | 8753.72 | 03-FEB-15:09 | 6.85 | 01-FEB-06:10 | 23538.08 | 27-FEB-07:10 |
March | 15812.47 | 16-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 827.33 | 16-MAR-07:19 | 10766.66 | 23-MAR-15:20 | 6.85 | 02-MAR-17:10 | 45344.97 | 30-MAR-06:10 |
April | 15318.48 | 21-APR-15:00 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 826.56 | 05-APR-07:19 | 12475.23 | 26-APR-14:30 | 6.85 | 01-APR-05:10 | 18638.18 | 01-APR-06:10 |
May | 15225.60 | 09-MAY-07:10 | 2323.70 | 01-MAY-18:30 | 40437.79 | 01-MAY-07:10 | 826.56 | 09-MAY-07:19 | 10975.92 | 03-MAY-15:20 | 6.85 | 01-MAY-05:10 | 10467.79 | 15-MAY-06:10 |
June | 15132.16 | 09-JUN-07:10 | 2323.70 | 01-JUN-18:49 | 40437.79 | 01-JUN-07:10 | 826.44 | 09-JUN-07:19 | 11983.66 | 30-JUN-15:00 | 6.85 | 01-JUN-05:10 | 5102.92 | 01-JUN-06:19 |
July | 15024.53 | 12-JUL-07:10 | 2323.70 | 01-JUL-18:00 | 40437.79 | 03-JUL-07:10 | 826.30 | 12-JUL-07:19 | 16325.60 | 31-JUL-14:30 | 6.85 | 01-JUL-05:10 | 754.77 | 17-JUL-06:40 |
August | 15227.94 | 21-AUG-07:10 | 3824.74 | 08-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 826.56 | 21-AUG-07:19 | 15712.59 | 14-AUG-15:09 | 6.85 | 01-AUG-05:10 | 1615.33 | 28-AUG-06:00 |
September | 16338.13 | 21-SEP-07:30 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 828.03 | 21-SEP-07:40 | 16542.67 | 29-SEP-15:00 | 6.85 | 01-SEP-05:10 | 5090.91 | 20-SEP-06:19 |
October | 16291.60 | 24-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 827.96 | 24-OCT-07:19 | 18063.41 | 16-OCT-15:00 | 6.85 | 01-OCT-05:10 | 7427.00 | 12-OCT-06:10 |
November | 18725.62 | 06-NOV-16:00 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 830.04 | 07-NOV-16:00 | 8521.99 | 10-NOV-14:00 | 6.85 | 01-NOV-05:10 | 14533.20 | 24-NOV-07:10 |
December | 18725.62 | 01-DEC-16:40 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 830.04 | 01-DEC-16:49 | 8598.71 | 07-DEC-15:30 | 6.85 | 13-DEC-17:10 | 26534.19 | 13-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15024.53 | 2323.70 | 40437.79 | 826.30 | 8521.99 | 6.85 | 754.77 | |||||||
Maximum of Months | 18725.62 | 3824.74 | 40437.79 | 830.04 | 18063.41 | 6.85 | 56601.18 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 21140.43 | 18-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 18620.15 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 21807.94 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27709.30 | 26-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 20050.98 | 03-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 31154.80 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 43909.70 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 40184.26 | 15-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 51100.40 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 54929.39 | 16-OCT-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 20196.39 | 28-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 21080.82 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 18620.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 54929.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 83757.91 | 02-JAN-07:10 | 5832.01 | 18346.02 | 0.00 | 243.24 | 2728.61 | 6.85 | 56601.18 | 0.00 | 0.00 |
February | 78407.20 | 03-FEB-14:00 | 14732.14 | 37678.39 | 0.00 | 824.33 | 8465.89 | 6.85 | 0.00 | 16699.60 | 0.00 |
March | 86458.96 | 23-MAR-15:09 | 14732.14 | 38454.47 | 0.00 | 824.78 | 10726.81 | 6.85 | 0.00 | 21713.90 | 0.00 |
April | 93109.92 | 26-APR-12:00 | 14732.14 | 38626.93 | 0.00 | 824.88 | 11209.82 | 6.85 | 0.00 | 27709.30 | 0.00 |
May | 84056.22 | 03-MAY-12:00 | 14732.14 | 38626.93 | 0.00 | 824.88 | 9814.43 | 6.85 | 0.00 | 20050.98 | 0.00 |
June | 94848.57 | 29-JUN-12:00 | 14732.14 | 38626.93 | 0.00 | 824.88 | 9502.97 | 6.85 | 0.00 | 31154.80 | 0.00 |
July | 113150.18 | 31-JUL-15:00 | 14732.14 | 38454.47 | 0.00 | 824.78 | 15222.23 | 6.85 | 0.00 | 43909.70 | 0.00 |
August | 108416.16 | 15-AUG-15:30 | 14732.14 | 38454.47 | 0.00 | 824.78 | 14213.66 | 6.85 | 0.00 | 40184.26 | 0.00 |
September | 115709.40 | 29-SEP-12:00 | 14732.14 | 38626.93 | 0.00 | 824.88 | 10418.20 | 6.85 | 0.00 | 51100.40 | 0.00 |
October | 120214.46 | 16-OCT-10:00 | 14732.14 | 38195.78 | 0.00 | 824.63 | 11525.67 | 6.85 | 0.00 | 54929.39 | 0.00 |
November | 80152.65 | 28-NOV-13:00 | 14732.14 | 38626.93 | 0.00 | 824.88 | 5765.45 | 6.85 | 0.00 | 20196.39 | 0.00 |
December | 81694.72 | 05-DEC-15:09 | 14732.14 | 37678.39 | 0.00 | 824.33 | 7679.41 | 6.85 | 0.00 | 20773.60 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 78407.20 | 5832.01 | 18346.02 | 0.00 | 243.24 | 2728.61 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120214.46 | 14732.14 | 38626.93 | 0.00 | 824.88 | 15222.23 | 6.85 | 56601.18 | 54929.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 25360.92 | 03-JAN-07:19 | 0.00 | 9842.17 | 25-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 14549.25 | 09-FEB-07:10 | 0.00 | 9845.43 | 10-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 20931.80 | 30-MAR-06:19 | 0.00 | 9833.14 | 03-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 13345.68 | 01-APR-06:10 | 0.00 | 9799.64 | 06-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 1310.83 | 15-MAY-06:10 | 0.00 | 9753.48 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9712.49 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9680.53 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9675.58 | 24-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9703.70 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 4437.75 | 12-OCT-06:10 | 0.00 | 9745.95 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 9082.29 | 24-NOV-07:10 | 0.00 | 9785.58 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 19509.10 | 22-DEC-07:10 | 0.00 | 9817.64 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9675.58 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 25360.92 | 0.00 | 9845.43 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.47 | 0.83 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.54 | 1.83 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 5.17 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.56 | 3.33 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.49 | 1.17 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.83 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.00 | 27.55 | 15.00 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 5.17 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.54 | 1.83 | 27.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.44 | 1.67 | 27.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.37 | 0.67 | 27.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.39 | 2.17 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.22 | 9.00 | 27.22 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.67 | 3.33 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.52 | 3.50 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 22.50 | 27.40 | 22.50 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.67 | 9.00 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.33 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.60 | 3.67 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.52 | 3.67 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.67 | 2.83 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.82 | 5.83 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.85 | 3.67 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 2.67 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.88 | 2.50 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 31.33 | 27.73 | 25.17 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.88 | 5.83 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.41 | 2.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 1.33 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.33 | 27.40 | 5.33 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.51 | 2.00 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 19.90 | 6.67 | 19.90 | 1.67 | 20.74 | 1.67 | 21.41 |
February | 2.17 | 20.25 | 2.17 | 20.25 | 0.83 | 21.39 | 0.83 | 22.22 |
March | 8.00 | 19.64 | 8.00 | 19.64 | 0.17 | 19.72 | 0.17 | 19.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.26 | 4.33 | 25.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 25.85 | 17.00 | 25.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.49 | 3.50 | 27.49 |
December | 2.17 | 20.13 | 2.17 | 20.13 | 4.33 | 23.79 | 4.33 | 25.01 |
Annual Sum or Average | 19.00 | 19.86 | 19.00 | 19.86 | 31.83 | 22.79 | 31.83 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.00 | 20.25 | 8.00 | 20.25 | 17.00 | 27.49 | 17.00 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.67 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.67 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 0.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.51 | 3.50 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.53 | 2.33 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.42 | 1.83 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.61 | 1.50 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.50 | 27.49 | 11.33 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.61 | 3.50 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.37 | 0.17 | 27.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.47 | 1.33 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.41 | 1.17 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.55 | 2.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.61 | 5.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.58 | 3.50 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.54 | 1.50 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.71 | 1.17 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 27.57 | 15.83 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.71 | 5.00 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.55 | 2.83 | 27.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.44 | 2.83 | 27.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.35 | 1.67 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.60 | 12.50 | 26.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.63 | 4.67 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.56 | 5.33 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 30.50 | 27.15 | 30.50 | 27.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.63 | 12.50 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.33 | 27.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.53 | 3.17 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.53 | 2.17 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 2.50 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.71 | 5.50 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.76 | 3.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.64 | 2.83 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.71 | 2.83 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.67 | 27.65 | 22.50 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.76 | 5.50 | 27.79 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 184.33 | 23.73 | 89.33 | 23.96 | 12.33 | 23.93 |
February | 111.17 | 23.78 | 50.67 | 24.11 | 0.00 | 24.11 |
March | 111.33 | 23.76 | 114.17 | 24.15 | 0.00 | 24.15 |
April | 24.00 | 23.84 | 225.17 | 24.44 | 0.00 | 24.44 |
May | 8.33 | 23.81 | 242.33 | 24.52 | 0.00 | 24.52 |
June | 0.00 | 0.00 | 394.67 | 24.35 | 0.00 | 24.35 |
July | 0.00 | 0.00 | 491.17 | 24.33 | 0.00 | 24.33 |
August | 0.00 | 0.00 | 514.00 | 24.28 | 0.00 | 24.28 |
September | 0.00 | 0.00 | 424.67 | 24.37 | 0.00 | 24.37 |
October | 25.67 | 24.00 | 276.83 | 24.49 | 0.00 | 24.49 |
November | 93.83 | 23.99 | 147.67 | 24.40 | 0.00 | 24.40 |
December | 211.33 | 23.91 | 60.17 | 24.09 | 0.00 | 24.09 |
Annual Sum or Average | 770.00 | 23.83 | 3030.83 | 24.30 | 12.33 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 50.67 | 23.96 | 0.00 | 23.93 |
Maximum of Months | 211.33 | 24.00 | 514.00 | 24.52 | 12.33 | 24.52 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.17 | 23.24 | 24.50 | 23.25 | 8.33 | 23.22 |
February | 319.17 | 23.33 | 6.83 | 23.35 | 0.00 | 23.35 |
March | 337.33 | 23.36 | 32.17 | 23.44 | 0.00 | 23.44 |
April | 144.17 | 23.38 | 109.50 | 23.78 | 0.00 | 23.78 |
May | 123.17 | 23.49 | 119.67 | 23.93 | 0.00 | 23.93 |
June | 26.17 | 23.52 | 292.33 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 446.67 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 498.00 | 24.17 | 0.00 | 24.17 |
September | 11.17 | 23.52 | 338.00 | 24.22 | 0.00 | 24.22 |
October | 113.67 | 23.72 | 189.67 | 24.12 | 0.00 | 24.12 |
November | 258.17 | 23.59 | 58.00 | 23.76 | 0.00 | 23.76 |
December | 392.83 | 23.47 | 10.17 | 23.49 | 0.00 | 23.49 |
Annual Sum or Average | 2081.00 | 23.41 | 2125.50 | 23.83 | 8.33 | 23.83 |
Minimum of Months | 0.00 | 0.00 | 6.83 | 23.25 | 0.00 | 23.22 |
Maximum of Months | 392.83 | 23.72 | 498.00 | 24.22 | 8.33 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.50 | 22.67 | 12.33 | 22.67 | 4.83 | 22.64 |
February | 379.33 | 22.81 | 2.00 | 22.82 | 0.00 | 22.82 |
March | 403.00 | 22.87 | 26.83 | 22.94 | 0.50 | 22.93 |
April | 214.50 | 23.10 | 91.00 | 23.39 | 0.00 | 23.39 |
May | 201.50 | 23.24 | 97.00 | 23.55 | 0.00 | 23.55 |
June | 76.17 | 23.36 | 258.83 | 24.00 | 0.00 | 24.00 |
July | 16.67 | 23.37 | 403.50 | 24.17 | 0.00 | 24.17 |
August | 15.33 | 23.32 | 425.00 | 24.11 | 0.00 | 24.11 |
September | 82.33 | 23.34 | 254.00 | 23.96 | 0.00 | 23.96 |
October | 202.17 | 23.46 | 154.17 | 23.79 | 0.00 | 23.79 |
November | 362.50 | 23.11 | 22.83 | 23.18 | 0.00 | 23.18 |
December | 454.67 | 22.87 | 6.00 | 22.88 | 1.67 | 22.87 |
Annual Sum or Average | 2834.67 | 22.98 | 1753.50 | 23.43 | 7.00 | 23.42 |
Minimum of Months | 15.33 | 22.67 | 2.00 | 22.67 | 0.00 | 22.64 |
Maximum of Months | 454.67 | 23.46 | 425.00 | 24.17 | 4.83 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.83 | 21.85 | 75.83 | 21.63 | 75.17 | 21.45 |
February | 421.83 | 22.01 | 31.50 | 21.89 | 31.00 | 21.79 |
March | 448.83 | 22.09 | 53.17 | 22.04 | 33.00 | 21.93 |
April | 299.33 | 22.59 | 81.17 | 22.86 | 4.83 | 22.83 |
May | 262.17 | 22.81 | 104.00 | 23.19 | 0.00 | 23.19 |
June | 134.83 | 23.14 | 246.50 | 23.77 | 0.00 | 23.77 |
July | 58.00 | 23.20 | 366.33 | 24.06 | 0.00 | 24.06 |
August | 101.00 | 23.20 | 341.33 | 23.89 | 0.50 | 23.89 |
September | 188.17 | 23.01 | 208.83 | 23.58 | 0.00 | 23.58 |
October | 265.33 | 22.90 | 126.67 | 23.33 | 0.00 | 23.33 |
November | 431.83 | 22.34 | 31.50 | 22.25 | 26.00 | 22.15 |
December | 488.33 | 21.99 | 59.00 | 21.81 | 59.00 | 21.65 |
Annual Sum or Average | 3568.50 | 22.36 | 1725.83 | 22.77 | 229.50 | 22.66 |
Minimum of Months | 58.00 | 21.85 | 31.50 | 21.63 | 0.00 | 21.45 |
Maximum of Months | 488.33 | 23.20 | 366.33 | 24.06 | 75.17 | 24.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.67 | 22.36 | 60.67 | 22.25 | 38.67 | 22.09 |
February | 346.33 | 22.24 | 42.50 | 22.29 | 15.83 | 22.20 |
March | 328.67 | 22.19 | 90.50 | 22.47 | 17.67 | 22.37 |
April | 195.67 | 22.72 | 218.17 | 23.57 | 3.83 | 23.57 |
May | 182.67 | 22.90 | 204.50 | 23.71 | 0.50 | 23.72 |
June | 112.67 | 23.40 | 304.67 | 24.04 | 8.00 | 24.10 |
July | 68.17 | 24.75 | 408.83 | 24.47 | 28.83 | 24.61 |
August | 76.50 | 24.21 | 405.67 | 24.27 | 20.83 | 24.37 |
September | 134.00 | 23.15 | 284.00 | 23.91 | 4.83 | 23.94 |
October | 163.33 | 23.01 | 197.00 | 23.79 | 2.00 | 23.81 |
November | 334.67 | 22.66 | 40.50 | 22.74 | 9.83 | 22.67 |
December | 449.67 | 22.59 | 31.50 | 22.45 | 28.00 | 22.32 |
Annual Sum or Average | 2796.00 | 22.69 | 2288.50 | 23.34 | 178.83 | 23.31 |
Minimum of Months | 68.17 | 22.19 | 31.50 | 22.25 | 0.50 | 22.09 |
Maximum of Months | 449.67 | 24.75 | 408.83 | 24.47 | 38.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 274.33 | 22.29 | 165.00 | 22.83 | 33.83 | 22.70 |
February | 272.83 | 22.14 | 118.17 | 22.70 | 18.67 | 22.63 |
March | 329.50 | 22.23 | 136.17 | 22.63 | 27.83 | 22.54 |
April | 227.33 | 22.60 | 186.50 | 23.36 | 4.83 | 23.34 |
May | 248.67 | 22.72 | 138.67 | 23.28 | 0.50 | 23.28 |
June | 159.67 | 23.08 | 236.00 | 23.71 | 0.00 | 23.71 |
July | 81.17 | 23.35 | 346.00 | 24.09 | 3.50 | 24.11 |
August | 87.50 | 23.47 | 366.33 | 24.07 | 8.50 | 24.11 |
September | 134.00 | 23.40 | 288.50 | 24.05 | 13.67 | 24.14 |
October | 173.50 | 23.61 | 265.50 | 24.18 | 27.67 | 24.35 |
November | 242.33 | 22.67 | 176.00 | 23.39 | 13.83 | 23.38 |
December | 268.00 | 22.46 | 166.00 | 23.03 | 30.00 | 22.90 |
Annual Sum or Average | 2498.83 | 22.67 | 2588.83 | 23.45 | 182.83 | 23.43 |
Minimum of Months | 81.17 | 22.14 | 118.17 | 22.63 | 0.00 | 22.54 |
Maximum of Months | 329.50 | 23.61 | 366.33 | 24.18 | 33.83 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 395.83 | 21.96 | 105.83 | 21.92 | 63.50 | 21.73 |
February | 343.17 | 22.00 | 79.17 | 22.21 | 24.50 | 22.10 |
March | 376.50 | 22.15 | 118.00 | 22.41 | 32.00 | 22.30 |
April | 239.00 | 22.82 | 181.00 | 23.47 | 17.67 | 23.54 |
May | 227.33 | 23.01 | 194.50 | 23.66 | 12.00 | 23.75 |
June | 123.33 | 23.50 | 312.00 | 24.03 | 14.50 | 24.13 |
July | 80.67 | 24.60 | 403.67 | 24.40 | 30.67 | 24.55 |
August | 82.00 | 24.00 | 404.83 | 24.19 | 19.83 | 24.29 |
September | 139.83 | 23.39 | 283.00 | 24.01 | 15.33 | 24.09 |
October | 215.00 | 23.14 | 210.00 | 23.78 | 12.67 | 23.88 |
November | 344.00 | 22.37 | 100.33 | 22.61 | 23.00 | 22.50 |
December | 400.67 | 22.11 | 77.00 | 22.03 | 51.50 | 21.86 |
Annual Sum or Average | 2967.33 | 22.55 | 2469.33 | 23.21 | 317.17 | 23.18 |
Minimum of Months | 80.67 | 21.96 | 77.00 | 21.92 | 12.00 | 21.73 |
Maximum of Months | 400.67 | 24.60 | 404.83 | 24.40 | 63.50 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.50 | 22.20 | 21.33 | 22.13 | 21.33 | 22.06 |
February | 451.67 | 22.28 | 2.67 | 22.27 | 2.67 | 22.26 |
March | 494.50 | 22.30 | 9.50 | 22.29 | 5.83 | 22.27 |
April | 383.50 | 22.84 | 18.50 | 22.89 | 0.67 | 22.89 |
May | 320.83 | 23.10 | 26.17 | 23.18 | 0.00 | 23.18 |
June | 164.67 | 23.29 | 156.33 | 23.67 | 0.00 | 23.67 |
July | 42.67 | 23.35 | 345.50 | 24.05 | 0.00 | 24.05 |
August | 77.33 | 23.27 | 321.17 | 23.91 | 0.00 | 23.91 |
September | 183.17 | 23.25 | 166.67 | 23.64 | 0.00 | 23.64 |
October | 266.17 | 23.28 | 104.67 | 23.52 | 0.00 | 23.52 |
November | 447.00 | 22.80 | 3.00 | 22.81 | 0.67 | 22.81 |
December | 493.00 | 22.35 | 3.67 | 22.34 | 3.67 | 22.33 |
Annual Sum or Average | 3801.00 | 22.66 | 1179.17 | 22.98 | 34.83 | 22.96 |
Minimum of Months | 42.67 | 22.20 | 2.67 | 22.13 | 0.00 | 22.06 |
Maximum of Months | 494.50 | 23.35 | 345.50 | 24.05 | 21.33 | 24.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.33 | 22.87 | 29.50 | 22.91 | 5.33 | 22.88 |
February | 356.67 | 22.68 | 9.33 | 22.74 | 0.00 | 22.74 |
March | 356.00 | 22.67 | 55.33 | 22.89 | 2.33 | 22.88 |
April | 192.33 | 23.06 | 175.33 | 23.70 | 0.33 | 23.70 |
May | 177.17 | 23.20 | 179.83 | 23.84 | 0.00 | 23.84 |
June | 95.83 | 23.30 | 269.67 | 24.03 | 0.67 | 24.04 |
July | 22.67 | 24.94 | 438.50 | 24.42 | 9.83 | 24.48 |
August | 19.83 | 25.27 | 450.00 | 24.32 | 10.50 | 24.38 |
September | 74.83 | 23.35 | 307.67 | 24.09 | 1.33 | 24.10 |
October | 117.67 | 23.44 | 215.83 | 24.08 | 0.33 | 24.09 |
November | 300.83 | 23.21 | 42.17 | 23.35 | 0.00 | 23.35 |
December | 433.50 | 23.10 | 2.33 | 23.10 | 0.00 | 23.10 |
Annual Sum or Average | 2532.67 | 23.03 | 2175.50 | 23.63 | 30.67 | 23.64 |
Minimum of Months | 19.83 | 22.67 | 2.33 | 22.74 | 0.00 | 22.74 |
Maximum of Months | 433.50 | 25.27 | 450.00 | 24.42 | 10.50 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.33 | 22.65 | 152.17 | 23.33 | 7.67 | 23.32 |
February | 302.00 | 22.41 | 84.00 | 22.92 | 0.00 | 22.92 |
March | 371.50 | 22.19 | 76.67 | 22.48 | 9.83 | 22.42 |
April | 284.67 | 22.67 | 122.00 | 23.20 | 0.00 | 23.20 |
May | 353.00 | 22.66 | 53.00 | 22.89 | 0.00 | 22.89 |
June | 273.83 | 22.87 | 111.50 | 23.23 | 0.83 | 23.23 |
July | 105.67 | 22.94 | 305.00 | 23.84 | 18.67 | 23.83 |
August | 84.33 | 22.89 | 385.33 | 23.91 | 28.33 | 23.88 |
September | 92.17 | 22.95 | 325.50 | 24.05 | 11.17 | 24.06 |
October | 126.83 | 23.59 | 298.50 | 24.32 | 30.50 | 24.40 |
November | 203.00 | 22.94 | 168.17 | 23.75 | 3.33 | 23.78 |
December | 238.17 | 22.84 | 141.33 | 23.59 | 0.83 | 23.60 |
Annual Sum or Average | 2685.50 | 22.70 | 2223.17 | 23.46 | 111.17 | 23.47 |
Minimum of Months | 84.33 | 22.19 | 53.00 | 22.48 | 0.00 | 22.42 |
Maximum of Months | 371.50 | 23.59 | 385.33 | 24.32 | 30.50 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 401.50 | 22.62 | 36.17 | 22.67 | 7.83 | 22.63 |
February | 358.50 | 22.60 | 35.50 | 22.77 | 0.00 | 22.77 |
March | 390.17 | 22.63 | 62.67 | 22.84 | 1.67 | 22.83 |
April | 200.83 | 23.11 | 163.50 | 23.70 | 0.67 | 23.71 |
May | 174.50 | 23.25 | 181.83 | 23.86 | 1.00 | 23.87 |
June | 70.17 | 23.47 | 315.17 | 24.12 | 3.00 | 24.15 |
July | 18.33 | 26.80 | 458.50 | 24.47 | 17.83 | 24.56 |
August | 19.33 | 25.87 | 471.67 | 24.32 | 13.67 | 24.39 |
September | 41.67 | 23.92 | 348.17 | 24.28 | 6.17 | 24.33 |
October | 149.33 | 23.59 | 233.17 | 24.10 | 4.50 | 24.13 |
November | 316.50 | 23.12 | 75.17 | 23.36 | 0.00 | 23.36 |
December | 406.33 | 22.82 | 16.83 | 22.88 | 0.00 | 22.88 |
Annual Sum or Average | 2547.17 | 22.95 | 2398.33 | 23.62 | 56.33 | 23.64 |
Minimum of Months | 18.33 | 22.60 | 16.83 | 22.67 | 0.00 | 22.63 |
Maximum of Months | 406.33 | 26.80 | 471.67 | 24.47 | 17.83 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.17 | 22.33 | 28.50 | 22.24 | 25.00 | 22.15 |
February | 407.67 | 22.50 | 2.17 | 22.50 | 1.67 | 22.49 |
March | 433.33 | 22.53 | 25.17 | 22.57 | 5.00 | 22.54 |
April | 279.50 | 22.98 | 70.00 | 23.19 | 0.00 | 23.19 |
May | 225.67 | 23.19 | 102.50 | 23.48 | 0.00 | 23.48 |
June | 77.83 | 23.36 | 272.17 | 23.96 | 0.00 | 23.96 |
July | 16.17 | 23.37 | 416.33 | 24.15 | 0.00 | 24.15 |
August | 31.00 | 23.33 | 397.33 | 24.04 | 0.17 | 24.04 |
September | 115.83 | 23.26 | 232.50 | 23.82 | 0.00 | 23.82 |
October | 225.50 | 23.28 | 141.33 | 23.65 | 0.00 | 23.65 |
November | 395.50 | 22.81 | 13.67 | 22.85 | 1.67 | 22.84 |
December | 483.17 | 22.54 | 4.17 | 22.53 | 4.17 | 22.51 |
Annual Sum or Average | 3145.33 | 22.74 | 1705.83 | 23.20 | 37.67 | 23.18 |
Minimum of Months | 16.17 | 22.33 | 2.17 | 22.24 | 0.00 | 22.15 |
Maximum of Months | 483.17 | 23.37 | 416.33 | 24.15 | 25.00 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 329.67 | 22.66 | 35.00 | 22.69 | 11.83 | 22.61 |
February | 290.50 | 22.63 | 27.33 | 22.79 | 0.50 | 22.79 |
March | 278.17 | 22.58 | 68.17 | 22.91 | 2.83 | 22.89 |
April | 165.33 | 23.12 | 164.33 | 23.82 | 2.83 | 23.84 |
May | 149.00 | 23.28 | 171.33 | 23.98 | 1.83 | 23.99 |
June | 70.83 | 23.74 | 261.33 | 24.24 | 7.83 | 24.30 |
July | 36.33 | 25.65 | 366.33 | 24.60 | 23.33 | 24.73 |
August | 30.83 | 25.42 | 368.50 | 24.42 | 18.33 | 24.52 |
September | 77.50 | 23.56 | 250.17 | 24.15 | 6.50 | 24.21 |
October | 119.33 | 23.36 | 183.17 | 24.08 | 2.17 | 24.11 |
November | 273.67 | 23.03 | 46.67 | 23.24 | 0.50 | 23.24 |
December | 351.17 | 22.90 | 9.00 | 22.91 | 2.17 | 22.90 |
Annual Sum or Average | 2172.33 | 23.00 | 1951.33 | 23.67 | 80.67 | 23.70 |
Minimum of Months | 30.83 | 22.58 | 9.00 | 22.69 | 0.50 | 22.61 |
Maximum of Months | 351.17 | 25.65 | 368.50 | 24.60 | 23.33 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 238.50 | 22.77 | 161.83 | 23.40 | 13.83 | 23.39 |
February | 250.00 | 22.68 | 117.00 | 23.29 | 3.83 | 23.33 |
March | 289.50 | 22.63 | 123.67 | 23.11 | 3.67 | 23.11 |
April | 195.50 | 23.00 | 187.17 | 23.67 | 0.00 | 23.67 |
May | 217.67 | 23.12 | 144.67 | 23.58 | 0.00 | 23.58 |
June | 110.00 | 23.32 | 254.00 | 23.89 | 0.00 | 23.89 |
July | 24.83 | 23.52 | 392.67 | 24.20 | 1.00 | 24.20 |
August | 22.50 | 23.59 | 420.50 | 24.17 | 1.83 | 24.18 |
September | 78.17 | 23.77 | 339.50 | 24.24 | 10.17 | 24.30 |
October | 129.67 | 24.12 | 296.33 | 24.43 | 27.67 | 24.59 |
November | 207.17 | 23.23 | 188.00 | 23.89 | 6.50 | 23.95 |
December | 236.83 | 23.02 | 161.00 | 23.71 | 5.67 | 23.76 |
Annual Sum or Average | 2000.33 | 23.05 | 2786.33 | 23.81 | 74.17 | 23.85 |
Minimum of Months | 22.50 | 22.63 | 117.00 | 23.11 | 0.00 | 23.11 |
Maximum of Months | 289.50 | 24.12 | 420.50 | 24.43 | 27.67 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 375.50 | 22.47 | 70.33 | 22.57 | 20.50 | 22.47 |
February | 327.00 | 22.56 | 59.17 | 22.84 | 0.33 | 22.84 |
March | 345.00 | 22.60 | 97.00 | 22.93 | 5.50 | 22.92 |
April | 191.50 | 23.17 | 186.33 | 23.79 | 9.33 | 23.86 |
May | 172.67 | 23.35 | 207.67 | 23.93 | 9.17 | 24.00 |
June | 70.83 | 23.89 | 338.50 | 24.20 | 12.00 | 24.28 |
July | 38.83 | 25.90 | 447.50 | 24.49 | 27.67 | 24.62 |
August | 31.67 | 25.34 | 455.00 | 24.32 | 17.83 | 24.41 |
September | 74.50 | 23.83 | 332.17 | 24.23 | 11.33 | 24.30 |
October | 168.83 | 23.56 | 236.50 | 24.07 | 10.83 | 24.15 |
November | 312.33 | 22.93 | 89.67 | 23.25 | 0.33 | 23.26 |
December | 379.17 | 22.67 | 39.00 | 22.81 | 3.33 | 22.79 |
Annual Sum or Average | 2487.83 | 22.95 | 2558.83 | 23.63 | 128.17 | 23.67 |
Minimum of Months | 31.67 | 22.47 | 39.00 | 22.57 | 0.33 | 22.47 |
Maximum of Months | 379.17 | 25.90 | 455.00 | 24.49 | 27.67 | 24.62 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.07534 | 37.69192 | 0.32114 | 7.47949 |
February | 454.00000 | 24.11142 | 39.45970 | 0.34597 | 7.65755 |
March | 514.00000 | 24.11072 | 42.16345 | 0.36517 | 7.96363 |
April | 485.00000 | 24.23167 | 44.48498 | 0.42701 | 9.00083 |
May | 508.00000 | 24.27625 | 43.60464 | -0.4486 | 9.47893 |
June | 496.00000 | 24.28311 | 48.50186 | -0.3942 | 8.51172 |
July | 497.00000 | 24.32831 | 52.34404 | -0.3389 | 7.67723 |
August | 514.00000 | 24.28164 | 53.69050 | -0.3382 | 7.63596 |
September | 485.00000 | 24.32272 | 49.60938 | -0.3674 | 8.12784 |
October | 502.00000 | 24.32070 | 41.05277 | 0.44746 | 9.47647 |
November | 489.00000 | 24.27288 | 37.34595 | 0.38632 | 8.46845 |
December | 497.00000 | 24.14099 | 32.83207 | 0.31408 | 7.31108 |
Annual Sum or Average | 5943.00000 | 24.23008 | 43.60626 | 0.05701 | 8.23513 |
Minimum of Months | 454.00000 | 24.07534 | 32.83207 | -0.4486 | 7.31108 |
Maximum of Months | 514.00000 | 24.32831 | 53.69050 | 0.44746 | 9.47893 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.47679 | 39.58420 | 0.17811 | 6.33810 |
February | 454.00000 | 23.55466 | 41.56364 | 0.21394 | 6.31953 |
March | 514.00000 | 23.59943 | 44.42113 | 0.24435 | 6.63449 |
April | 485.00000 | 23.87335 | 45.96990 | 0.34259 | 7.78630 |
May | 508.00000 | 23.97153 | 44.96658 | -0.5554 | 11.81752 |
June | 496.00000 | 24.10024 | 49.63612 | -0.4621 | 9.70765 |
July | 497.00000 | 24.18683 | 53.25237 | -0.3935 | 8.42221 |
August | 514.00000 | 24.15708 | 54.61283 | -0.3904 | 8.33993 |
September | 485.00000 | 24.12289 | 50.72609 | -0.4446 | 9.36749 |
October | 502.00000 | 24.10047 | 42.18000 | 0.38812 | 8.45387 |
November | 489.00000 | 23.84925 | 39.01235 | 0.27939 | 7.03971 |
December | 497.00000 | 23.59798 | 34.55969 | 0.18126 | 6.07404 |
Annual Sum or Average | 5943.00000 | 23.88444 | 45.07802 | -0.0376 | 8.03911 |
Minimum of Months | 454.00000 | 23.47679 | 34.55969 | -0.5554 | 6.07404 |
Maximum of Months | 514.00000 | 24.18683 | 54.61283 | 0.38812 | 11.81752 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.86704 | 40.94322 | 0.02717 | 6.31253 |
February | 454.00000 | 23.00013 | 43.02930 | 0.07823 | 5.99956 |
March | 514.00000 | 23.10918 | 45.60908 | 0.12428 | 6.23663 |
April | 485.00000 | 23.61455 | 46.59315 | 0.28124 | 7.26863 |
May | 508.00000 | 23.74821 | 45.43552 | -0.6314 | 14.17643 |
June | 496.00000 | 23.97716 | 49.70616 | -0.5006 | 10.62691 |
July | 497.00000 | 24.11393 | 53.20630 | -0.4111 | 8.76500 |
August | 514.00000 | 24.05893 | 54.72491 | -0.4182 | 8.85605 |
September | 485.00000 | 23.94598 | 51.07243 | -0.5064 | 10.76849 |
October | 502.00000 | 23.85773 | 42.76566 | 0.32615 | 7.73981 |
November | 489.00000 | 23.34816 | 40.39815 | 0.15410 | 6.30312 |
December | 497.00000 | 22.96689 | 36.14518 | 0.02647 | 5.88832 |
Annual Sum or Average | 5943.00000 | 23.55415 | 45.83451 | -0.1232 | 8.26539 |
Minimum of Months | 454.00000 | 22.86704 | 36.14518 | -0.6314 | 5.88832 |
Maximum of Months | 514.00000 | 24.11393 | 54.72491 | 0.32615 | 14.17643 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.99167 | 42.31886 | -0.1903 | 8.00606 |
February | 454.00000 | 22.14715 | 45.38026 | -0.1236 | 6.98397 |
March | 514.00000 | 22.32272 | 48.15203 | -0.0596 | 6.99504 |
April | 485.00000 | 23.12988 | 48.70165 | 0.16895 | 6.91831 |
May | 508.00000 | 23.41233 | 47.07795 | -0.7354 | 18.19070 |
June | 496.00000 | 23.81256 | 50.91867 | -0.5407 | 12.05314 |
July | 497.00000 | 24.02663 | 54.36030 | -0.4232 | 9.44490 |
August | 514.00000 | 23.87578 | 56.50611 | -0.4685 | 10.30073 |
September | 485.00000 | 23.63402 | 53.20545 | -0.6064 | 13.92017 |
October | 502.00000 | 23.46447 | 44.54734 | 0.23457 | 7.48392 |
November | 489.00000 | 22.52743 | 42.62629 | -0.0431 | 6.72847 |
December | 497.00000 | 22.02630 | 37.80755 | -0.2035 | 7.52849 |
Annual Sum or Average | 5943.00000 | 23.03702 | 47.66139 | -0.2510 | 9.57237 |
Minimum of Months | 454.00000 | 21.99167 | 37.80755 | -0.7354 | 6.72847 |
Maximum of Months | 514.00000 | 24.02663 | 56.50611 | 0.23457 | 18.19070 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.68185 | 41.20843 | -0.0117 | 7.30798 |
February | 454.00000 | 22.66901 | 44.27532 | 0.01597 | 6.94092 |
March | 514.00000 | 22.88202 | 46.76264 | 0.09328 | 7.52158 |
April | 485.00000 | 23.63451 | 46.69123 | 0.32574 | 8.79141 |
May | 508.00000 | 23.77153 | 45.80657 | -0.5730 | 14.27573 |
June | 496.00000 | 23.97646 | 50.20570 | -0.4347 | 10.71805 |
July | 497.00000 | 24.26944 | 53.18670 | -0.2721 | 8.48273 |
August | 514.00000 | 24.11722 | 55.08311 | -0.3097 | 8.66334 |
September | 485.00000 | 23.87504 | 52.10385 | -0.4751 | 11.59848 |
October | 502.00000 | 23.82596 | 43.49883 | 0.34760 | 8.75786 |
November | 489.00000 | 23.10835 | 41.33021 | 0.10966 | 6.78512 |
December | 497.00000 | 22.72640 | 36.81371 | -0.0235 | 6.71867 |
Annual Sum or Average | 5943.00000 | 23.46686 | 46.44133 | -0.1023 | 8.89544 |
Minimum of Months | 454.00000 | 22.66901 | 36.81371 | -0.5730 | 6.71867 |
Maximum of Months | 514.00000 | 24.26944 | 55.08311 | 0.34760 | 14.27573 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.18859 | 38.16649 | 0.15752 | 8.89225 |
February | 454.00000 | 23.00142 | 42.21183 | 0.12263 | 8.34344 |
March | 514.00000 | 22.91497 | 45.58365 | 0.11237 | 8.18018 |
April | 485.00000 | 23.47874 | 46.88872 | 0.28076 | 8.57895 |
May | 508.00000 | 23.44929 | 46.68465 | -0.7099 | 18.07167 |
June | 496.00000 | 23.75598 | 51.03782 | -0.5555 | 12.74218 |
July | 497.00000 | 24.03595 | 54.22384 | -0.4089 | 9.69047 |
August | 514.00000 | 23.99045 | 55.59467 | -0.3872 | 9.49698 |
September | 485.00000 | 23.95146 | 51.31763 | -0.4283 | 11.31059 |
October | 502.00000 | 23.99415 | 42.31428 | 0.42314 | 10.80816 |
November | 489.00000 | 23.51533 | 38.71237 | 0.25352 | 8.90343 |
December | 497.00000 | 23.34850 | 33.74383 | 0.17767 | 8.81495 |
Annual Sum or Average | 5943.00000 | 23.55472 | 45.58003 | -0.0829 | 10.34183 |
Minimum of Months | 454.00000 | 22.91497 | 33.74383 | -0.7099 | 8.18018 |
Maximum of Months | 514.00000 | 24.03595 | 55.59467 | 0.42314 | 18.07167 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.41241 | 41.46138 | -0.0720 | 8.10584 |
February | 454.00000 | 22.53778 | 44.44880 | -0.0102 | 7.59020 |
March | 514.00000 | 22.66706 | 47.19232 | 0.04647 | 7.76520 |
April | 485.00000 | 23.49575 | 47.55737 | 0.29785 | 9.17939 |
May | 508.00000 | 23.64676 | 46.42049 | -0.6042 | 16.24095 |
June | 496.00000 | 23.93999 | 50.53593 | -0.4326 | 11.04444 |
July | 497.00000 | 24.19994 | 53.71947 | -0.2911 | 8.85151 |
August | 514.00000 | 24.05910 | 55.68070 | -0.3293 | 9.05968 |
September | 485.00000 | 23.91864 | 52.16125 | -0.4483 | 11.61756 |
October | 502.00000 | 23.73651 | 43.88238 | 0.33060 | 9.24995 |
November | 489.00000 | 22.90979 | 41.53806 | 0.07147 | 7.49068 |
December | 497.00000 | 22.50288 | 36.89988 | -0.0727 | 7.67280 |
Annual Sum or Average | 5943.00000 | 23.34059 | 46.82146 | -0.1280 | 9.50648 |
Minimum of Months | 454.00000 | 22.41241 | 36.89988 | -0.6042 | 7.49068 |
Maximum of Months | 514.00000 | 24.19994 | 55.68070 | 0.33060 | 16.24095 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.29320 | 42.15769 | -0.1111 | 6.61095 |
February | 454.00000 | 22.28420 | 45.40568 | -0.0917 | 5.89049 |
March | 514.00000 | 22.36556 | 48.43168 | -0.0523 | 6.06908 |
April | 485.00000 | 23.08097 | 49.78042 | 0.14284 | 6.16416 |
May | 508.00000 | 23.43546 | 47.96668 | -0.7525 | 17.80648 |
June | 496.00000 | 23.77325 | 51.92515 | -0.5880 | 12.73943 |
July | 497.00000 | 23.99554 | 54.92987 | -0.4675 | 9.84637 |
August | 514.00000 | 23.87385 | 56.95760 | -0.5012 | 10.58755 |
September | 485.00000 | 23.71578 | 53.49540 | -0.5976 | 13.02139 |
October | 502.00000 | 23.64344 | 44.51940 | 0.27110 | 7.16045 |
November | 489.00000 | 22.90439 | 42.28604 | 0.04829 | 5.88076 |
December | 497.00000 | 22.36519 | 37.62311 | -0.1159 | 6.07217 |
Annual Sum or Average | 5943.00000 | 23.14975 | 47.98647 | -0.2367 | 9.01997 |
Minimum of Months | 454.00000 | 22.28420 | 37.62311 | -0.7525 | 5.88076 |
Maximum of Months | 514.00000 | 23.99554 | 56.95760 | 0.27110 | 17.80648 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13924 | 40.63109 | 0.10242 | 6.42341 |
February | 454.00000 | 22.98700 | 44.01041 | 0.08777 | 6.16935 |
March | 514.00000 | 23.12753 | 46.68950 | 0.14365 | 6.80433 |
April | 485.00000 | 23.76986 | 46.98066 | 0.33985 | 8.26103 |
May | 508.00000 | 23.88145 | 46.21298 | -0.5606 | 12.94483 |
June | 496.00000 | 24.00396 | 50.79337 | -0.4612 | 10.61033 |
July | 497.00000 | 24.31873 | 53.28673 | -0.2909 | 7.91448 |
August | 514.00000 | 24.20762 | 54.93905 | -0.3114 | 7.98956 |
September | 485.00000 | 24.03236 | 51.98434 | -0.4414 | 10.01093 |
October | 502.00000 | 24.04516 | 43.18895 | 0.39499 | 8.84313 |
November | 489.00000 | 23.55994 | 40.66657 | 0.22004 | 6.66057 |
December | 497.00000 | 23.22077 | 36.26735 | 0.09814 | 5.94907 |
Annual Sum or Average | 5943.00000 | 23.69556 | 46.33308 | -0.0585 | 8.23095 |
Minimum of Months | 454.00000 | 22.98700 | 36.26735 | -0.5606 | 5.94907 |
Maximum of Months | 514.00000 | 24.31873 | 54.93905 | 0.39499 | 12.94483 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.50470 | 37.16355 | 0.25369 | 8.26950 |
February | 454.00000 | 23.07857 | 41.47410 | 0.15547 | 7.37737 |
March | 514.00000 | 22.75159 | 45.20375 | 0.08676 | 7.21497 |
April | 485.00000 | 23.31485 | 47.51081 | 0.23710 | 7.39585 |
May | 508.00000 | 23.10859 | 47.62243 | -0.8245 | 21.00038 |
June | 496.00000 | 23.37484 | 52.87982 | -0.6964 | 16.38231 |
July | 497.00000 | 23.84136 | 56.31308 | -0.4909 | 10.96967 |
August | 514.00000 | 23.90679 | 57.42201 | -0.4281 | 9.85845 |
September | 485.00000 | 24.00387 | 51.87739 | -0.4137 | 10.29154 |
October | 502.00000 | 24.18984 | 42.10717 | 0.47441 | 11.10257 |
November | 489.00000 | 23.77917 | 37.96447 | 0.33722 | 8.84866 |
December | 497.00000 | 23.68856 | 32.74681 | 0.27922 | 8.36473 |
Annual Sum or Average | 5943.00000 | 23.54632 | 45.90679 | -0.0891 | 10.62733 |
Minimum of Months | 454.00000 | 22.75159 | 32.74681 | -0.8245 | 7.21497 |
Maximum of Months | 514.00000 | 24.18984 | 57.42201 | 0.47441 | 21.00038 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90973 | 41.00682 | 0.04938 | 6.58445 |
February | 454.00000 | 22.93137 | 44.03221 | 0.07709 | 6.31825 |
March | 514.00000 | 22.98884 | 46.83926 | 0.11281 | 6.65100 |
April | 485.00000 | 23.76858 | 47.26035 | 0.33990 | 8.53469 |
May | 508.00000 | 23.89998 | 46.23510 | -0.5487 | 12.94811 |
June | 496.00000 | 24.06880 | 50.59086 | -0.4269 | 9.86745 |
July | 497.00000 | 24.33102 | 53.38483 | -0.2820 | 7.70922 |
August | 514.00000 | 24.20834 | 55.14294 | -0.3108 | 7.87017 |
September | 485.00000 | 24.16851 | 51.48725 | -0.3846 | 9.06835 |
October | 502.00000 | 24.05559 | 43.30334 | 0.39894 | 9.16385 |
November | 489.00000 | 23.48825 | 40.74078 | 0.20782 | 6.85937 |
December | 497.00000 | 23.05595 | 36.45263 | 0.06133 | 6.14854 |
Annual Sum or Average | 5943.00000 | 23.66022 | 46.40379 | -0.0609 | 8.15900 |
Minimum of Months | 454.00000 | 22.90973 | 36.45263 | -0.5487 | 6.14854 |
Maximum of Months | 514.00000 | 24.33102 | 55.14294 | 0.39894 | 12.94811 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.48406 | 41.30335 | -0.0618 | 6.67411 |
February | 454.00000 | 22.65084 | 44.20045 | 0.00283 | 5.99232 |
March | 514.00000 | 22.75159 | 47.14189 | 0.04911 | 6.28604 |
April | 485.00000 | 23.40818 | 48.09101 | 0.23527 | 6.86479 |
May | 508.00000 | 23.66152 | 46.54318 | -0.6524 | 14.80013 |
June | 496.00000 | 23.95350 | 50.70713 | -0.4971 | 10.56408 |
July | 497.00000 | 24.11344 | 54.22999 | -0.4011 | 8.64408 |
August | 514.00000 | 23.99041 | 56.17812 | -0.4356 | 9.23882 |
September | 485.00000 | 23.83620 | 52.66670 | -0.5382 | 11.58196 |
October | 502.00000 | 23.73480 | 43.95901 | 0.30150 | 7.60600 |
November | 489.00000 | 23.03979 | 41.49775 | 0.08482 | 6.14566 |
December | 497.00000 | 22.58323 | 36.69784 | -0.0618 | 6.07239 |
Annual Sum or Average | 5943.00000 | 23.35520 | 46.96633 | -0.1667 | 8.39528 |
Minimum of Months | 454.00000 | 22.48406 | 36.69784 | -0.6524 | 5.99232 |
Maximum of Months | 514.00000 | 24.11344 | 56.17812 | 0.30150 | 14.80013 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.98853 | 40.42952 | 0.07166 | 6.71327 |
February | 385.00000 | 23.00789 | 43.32052 | 0.10280 | 6.46856 |
March | 433.00000 | 23.14723 | 45.72253 | 0.15959 | 7.14195 |
April | 410.00000 | 23.82289 | 46.36396 | 0.36211 | 8.85123 |
May | 430.00000 | 23.95591 | 45.44942 | -0.5214 | 12.46505 |
June | 418.00000 | 24.11039 | 50.00694 | -0.4095 | 9.91091 |
July | 422.00000 | 24.39806 | 52.92685 | -0.2577 | 8.09557 |
August | 433.00000 | 24.23823 | 54.83410 | -0.2957 | 8.21673 |
September | 410.00000 | 24.04513 | 51.68252 | -0.4333 | 10.23082 |
October | 427.00000 | 24.03720 | 43.28340 | 0.39396 | 9.14059 |
November | 417.00000 | 23.42943 | 40.54428 | 0.19299 | 6.72501 |
December | 422.00000 | 23.09653 | 35.70598 | 0.07263 | 6.14820 |
Annual Sum or Average | 5034.00000 | 23.69364 | 45.87208 | -0.0482 | 8.35357 |
Minimum of Months | 385.00000 | 22.98853 | 35.70598 | -0.5214 | 6.14820 |
Maximum of Months | 433.00000 | 24.39806 | 54.83410 | 0.39396 | 12.46505 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.56132 | 37.30602 | 0.25826 | 8.62960 |
February | 454.00000 | 23.40551 | 41.11398 | 0.22685 | 8.02444 |
March | 514.00000 | 23.29406 | 44.58406 | 0.20896 | 7.78538 |
April | 485.00000 | 23.73132 | 46.28814 | 0.34001 | 8.52550 |
May | 508.00000 | 23.69336 | 46.14523 | -0.6290 | 14.62111 |
June | 496.00000 | 23.90214 | 50.81069 | -0.5107 | 11.07161 |
July | 497.00000 | 24.12699 | 54.06578 | -0.3865 | 8.72952 |
August | 514.00000 | 24.09994 | 55.25870 | -0.3580 | 8.41643 |
September | 485.00000 | 24.13004 | 50.85185 | -0.3698 | 9.34959 |
October | 502.00000 | 24.20937 | 41.81055 | 0.47651 | 11.13554 |
November | 489.00000 | 23.87330 | 37.83414 | 0.34788 | 9.13338 |
December | 497.00000 | 23.74188 | 32.81298 | 0.28302 | 8.68739 |
Annual Sum or Average | 5943.00000 | 23.81572 | 44.95000 | -0.0123 | 9.52445 |
Minimum of Months | 454.00000 | 23.29406 | 32.81298 | -0.6290 | 7.78538 |
Maximum of Months | 514.00000 | 24.20937 | 55.25870 | 0.47651 | 14.62111 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.88457 | 40.48664 | 0.05095 | 7.06189 |
February | 454.00000 | 23.01474 | 43.28508 | 0.10964 | 6.84579 |
March | 514.00000 | 23.08921 | 46.14651 | 0.15228 | 7.23078 |
April | 485.00000 | 23.77513 | 46.86225 | 0.36235 | 9.18928 |
May | 508.00000 | 23.89686 | 45.80956 | -0.5227 | 12.89234 |
June | 496.00000 | 24.08691 | 50.24036 | -0.3891 | 9.48298 |
July | 497.00000 | 24.30265 | 53.49302 | -0.2668 | 7.94528 |
August | 514.00000 | 24.17279 | 55.29369 | -0.2989 | 8.04688 |
September | 485.00000 | 24.10915 | 51.59150 | -0.3858 | 9.55192 |
October | 502.00000 | 23.99375 | 43.30533 | 0.39365 | 9.43118 |
November | 489.00000 | 23.38459 | 40.49188 | 0.19067 | 7.15504 |
December | 497.00000 | 23.02242 | 35.83187 | 0.06004 | 6.62060 |
Annual Sum or Average | 5943.00000 | 23.64807 | 46.10311 | -0.0474 | 8.46721 |
Minimum of Months | 454.00000 | 22.88457 | 35.83187 | -0.5227 | 6.62060 |
Maximum of Months | 514.00000 | 24.30265 | 55.29369 | 0.39365 | 12.89234 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.680433E+10 | 0.164188E+10 | 200.81 | 0.618957E+10 | 0.614759E+09 | 0.00 | 1.00 | 13-JAN-13:05 | 0.00 | 01-JAN-00:10 | 33286.84 | 18-JAN-13:05 | 33286.84 | 18-JAN-13:05 | 6116.08 | 20-JAN-13:20 | 7586.03 | 18-JAN-13:05 | 0.00 |
February | 0.399707E+10 | 0.987589E+09 | 151.78 | 0.344555E+10 | 0.551518E+09 | 0.00 | 1.00 | 01-FEB-11:20 | 0.00 | 01-FEB-00:10 | 29856.96 | 01-FEB-12:00 | 29856.96 | 01-FEB-12:00 | 4682.31 | 11-FEB-14:00 | 6845.58 | 01-FEB-12:00 | 0.00 |
March | 0.464825E+10 | 0.112922E+10 | 144.69 | 0.361090E+10 | 0.103735E+10 | 0.00 | 1.00 | 22-MAR-12:20 | 0.00 | 01-MAR-00:10 | 32675.51 | 23-MAR-15:10 | 27318.29 | 23-MAR-14:00 | 8960.04 | 23-MAR-16:00 | 7142.35 | 23-MAR-15:10 | 0.00 |
April | 0.106717E+11 | 0.254547E+10 | 247.06 | 0.878287E+10 | 0.188882E+10 | 0.00 | 1.00 | 04-APR-12:50 | 0.00 | 01-APR-00:10 | 38162.88 | 26-APR-13:00 | 37203.30 | 26-APR-13:00 | 6046.49 | 13-APR-16:00 | 8963.96 | 26-APR-13:00 | 0.00 |
May | 0.114241E+11 | 0.275388E+10 | 297.92 | 0.953033E+10 | 0.189373E+10 | 0.00 | 1.00 | 02-MAY-12:50 | 0.00 | 01-MAY-00:10 | 30726.56 | 03-MAY-13:00 | 30726.56 | 03-MAY-13:00 | 9075.53 | 05-MAY-15:00 | 6714.23 | 03-MAY-13:00 | 0.00 |
June | 0.215368E+11 | 0.498619E+10 | 383.31 | 0.160851E+11 | 0.545169E+10 | 0.00 | 1.00 | 14-JUN-09:50 | 0.00 | 01-JUN-00:10 | 47824.05 | 29-JUN-13:00 | 31761.07 | 29-JUN-11:00 | 17196.55 | 29-JUN-13:00 | 10495.21 | 29-JUN-13:00 | 0.00 |
July | 0.370024E+11 | 0.838498E+10 | 422.44 | 0.246466E+11 | 0.123558E+11 | 0.00 | 1.00 | 03-JUL-09:05 | 0.00 | 01-JUL-00:10 | 67409.62 | 31-JUL-16:00 | 44611.74 | 31-JUL-13:00 | 29172.41 | 31-JUL-16:00 | 14730.17 | 31-JUL-16:00 | 0.00 |
August | 0.428230E+11 | 0.964874E+10 | 439.37 | 0.278094E+11 | 0.150136E+11 | 0.00 | 1.00 | 01-AUG-09:40 | 0.00 | 01-AUG-00:10 | 63267.90 | 07-AUG-10:30 | 43205.21 | 17-AUG-14:00 | 27265.93 | 15-AUG-16:00 | 13920.07 | 07-AUG-10:30 | 0.00 |
September | 0.262995E+11 | 0.615296E+10 | 371.81 | 0.189768E+11 | 0.732265E+10 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 54787.90 | 29-SEP-13:00 | 54787.90 | 29-SEP-13:00 | 27893.98 | 22-SEP-10:00 | 16692.95 | 29-SEP-13:00 | 0.00 |
October | 0.293654E+11 | 0.691963E+10 | 381.00 | 0.233521E+11 | 0.601331E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 64507.72 | 03-OCT-13:40 | 58569.93 | 16-OCT-12:04 | 30854.60 | 02-OCT-06:03 | 18268.24 | 16-OCT-11:00 | 0.00 |
November | 0.801093E+10 | 0.193298E+10 | 228.33 | 0.708226E+10 | 0.928669E+09 | 0.00 | 1.00 | 08-NOV-10:50 | 0.00 | 01-NOV-00:10 | 32720.17 | 28-NOV-14:00 | 32720.17 | 28-NOV-14:00 | 7967.61 | 20-NOV-13:05 | 7318.78 | 28-NOV-14:00 | 0.00 |
December | 0.853664E+10 | 0.201453E+10 | 208.22 | 0.827432E+10 | 0.262318E+09 | 0.00 | 1.00 | 04-DEC-09:50 | 0.00 | 01-DEC-00:10 | 32859.39 | 19-DEC-13:05 | 32859.39 | 19-DEC-13:05 | 5019.00 | 07-DEC-15:00 | 7439.67 | 19-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.211120E+12 | 0.490980E+11 | 3476.73 | 0.157786E+12 | 0.533342E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.399707E+10 | 0.987589E+09 | 144.69 | 0.344555E+10 | 0.262318E+09 | 0.00 | 1.00 | 0.00 | 29856.96 | 27318.29 | 4682.31 | 6714.23 | 0.00 | ||||||
Maximum of Months | 0.428230E+11 | 0.964874E+10 | 439.37 | 0.278094E+11 | 0.150136E+11 | 0.00 | 1.00 | 0.00 | 67409.62 | 58569.93 | 30854.60 | 18268.24 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.630143E+10 | 0.139369E+10 | 200.47 | 0.563058E+10 | 0.670858E+09 | 0.00 | 1.00 | 13-JAN-13:05 | 0.00 | 01-JAN-00:10 | 30828.79 | 18-JAN-14:00 | 30828.79 | 18-JAN-14:00 | 6885.43 | 20-JAN-13:05 | 6308.15 | 18-JAN-13:05 | 0.00 |
February | 0.365174E+10 | 0.827553E+09 | 154.08 | 0.308512E+10 | 0.566618E+09 | 0.00 | 1.00 | 01-FEB-11:30 | 0.00 | 01-FEB-00:10 | 26734.47 | 03-FEB-15:05 | 26734.47 | 03-FEB-15:05 | 6458.00 | 01-FEB-14:00 | 5574.40 | 01-FEB-12:00 | 0.00 |
March | 0.465639E+10 | 0.102707E+10 | 150.11 | 0.361153E+10 | 0.104486E+10 | 0.00 | 1.00 | 22-MAR-12:05 | 0.00 | 01-MAR-00:10 | 35576.91 | 23-MAR-14:05 | 28931.81 | 23-MAR-14:05 | 9079.08 | 23-MAR-15:50 | 7077.98 | 23-MAR-14:05 | 0.00 |
April | 0.106168E+11 | 0.230416E+10 | 258.28 | 0.879088E+10 | 0.182588E+10 | 0.00 | 1.00 | 04-APR-12:40 | 0.00 | 01-APR-00:10 | 41043.13 | 26-APR-14:05 | 38961.97 | 26-APR-14:05 | 5967.99 | 13-APR-16:00 | 8478.15 | 26-APR-14:05 | 0.00 |
May | 0.109099E+11 | 0.239783E+10 | 307.32 | 0.909753E+10 | 0.181236E+10 | 0.00 | 1.00 | 02-MAY-12:50 | 0.00 | 01-MAY-00:10 | 30675.59 | 04-MAY-12:05 | 30675.59 | 04-MAY-12:05 | 9006.41 | 05-MAY-15:00 | 6082.25 | 04-MAY-12:05 | 0.00 |
June | 0.208557E+11 | 0.439539E+10 | 391.25 | 0.156798E+11 | 0.517581E+10 | 0.00 | 1.00 | 13-JUN-14:05 | 0.00 | 01-JUN-00:10 | 46459.66 | 29-JUN-12:05 | 31775.16 | 26-JUN-10:05 | 16731.43 | 28-JUN-12:05 | 9285.70 | 29-JUN-12:05 | 0.00 |
July | 0.352204E+11 | 0.727455E+10 | 430.72 | 0.235984E+11 | 0.116220E+11 | 0.00 | 1.00 | 02-JUL-15:32 | 0.00 | 01-JUL-00:10 | 66613.89 | 31-JUL-16:00 | 45257.92 | 31-JUL-14:05 | 28973.60 | 31-JUL-16:00 | 13255.75 | 31-JUL-16:00 | 0.00 |
August | 0.405243E+11 | 0.832368E+10 | 446.25 | 0.265020E+11 | 0.140223E+11 | 0.00 | 1.00 | 01-AUG-09:50 | 0.00 | 01-AUG-00:10 | 61722.78 | 07-AUG-10:05 | 44208.11 | 17-AUG-14:05 | 26640.77 | 15-AUG-16:00 | 12411.36 | 17-AUG-14:05 | 0.00 |
September | 0.246840E+11 | 0.527213E+10 | 377.23 | 0.179146E+11 | 0.676946E+10 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 56983.71 | 29-SEP-12:02 | 56983.71 | 29-SEP-12:02 | 26206.68 | 22-SEP-10:05 | 15807.87 | 29-SEP-12:02 | 0.00 |
October | 0.265955E+11 | 0.574468E+10 | 383.33 | 0.212238E+11 | 0.537173E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 61978.79 | 16-OCT-12:02 | 61978.79 | 16-OCT-12:02 | 29620.03 | 02-OCT-06:03 | 17019.54 | 16-OCT-12:02 | 0.00 |
November | 0.718624E+10 | 0.158825E+10 | 228.00 | 0.627575E+10 | 0.910493E+09 | 0.00 | 1.00 | 10-NOV-13:05 | 0.00 | 01-NOV-00:10 | 29353.87 | 28-NOV-14:00 | 29353.87 | 28-NOV-14:00 | 7596.51 | 20-NOV-13:05 | 5980.81 | 28-NOV-14:00 | 0.00 |
December | 0.746204E+10 | 0.162174E+10 | 205.67 | 0.718397E+10 | 0.278068E+09 | 0.00 | 1.00 | 05-DEC-09:40 | 0.00 | 01-DEC-00:10 | 32585.24 | 05-DEC-15:05 | 32585.24 | 05-DEC-15:05 | 6045.37 | 07-DEC-13:00 | 6585.20 | 05-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.198664E+12 | 0.421707E+11 | 3532.72 | 0.148594E+12 | 0.500705E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.365174E+10 | 0.827553E+09 | 150.11 | 0.308512E+10 | 0.278068E+09 | 0.00 | 1.00 | 0.00 | 26734.47 | 26734.47 | 5967.99 | 5574.40 | 0.00 | ||||||
Maximum of Months | 0.405243E+11 | 0.832368E+10 | 446.25 | 0.265020E+11 | 0.140223E+11 | 0.00 | 1.00 | 0.00 | 66613.89 | 61978.79 | 29620.03 | 17019.54 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.596611E+10 | 0.147503E+10 | 198.31 | 0.519756E+10 | 0.768547E+09 | 0.00 | 1.00 | 13-JAN-14:00 | 0.00 | 01-JAN-00:10 | 33311.11 | 18-JAN-13:40 | 33311.11 | 18-JAN-13:40 | 6720.69 | 20-JAN-13:05 | 7463.88 | 18-JAN-13:40 | 0.00 |
February | 0.348728E+10 | 0.882391E+09 | 151.14 | 0.286809E+10 | 0.619190E+09 | 0.00 | 1.00 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 27033.46 | 01-FEB-12:00 | 27033.46 | 01-FEB-12:00 | 6450.63 | 01-FEB-14:00 | 6200.17 | 01-FEB-12:00 | 0.00 |
March | 0.470396E+10 | 0.114908E+10 | 148.42 | 0.356554E+10 | 0.113842E+10 | 0.00 | 1.00 | 22-MAR-12:40 | 0.00 | 01-MAR-00:10 | 36299.13 | 23-MAR-15:00 | 29588.01 | 23-MAR-14:00 | 9877.72 | 23-MAR-15:50 | 7935.25 | 23-MAR-15:00 | 0.00 |
April | 0.113405E+11 | 0.271740E+10 | 258.67 | 0.914433E+10 | 0.219620E+10 | 0.00 | 1.00 | 04-APR-12:50 | 0.00 | 01-APR-00:10 | 47578.65 | 26-APR-14:00 | 45705.67 | 26-APR-14:00 | 6646.27 | 13-APR-16:00 | 10918.95 | 26-APR-13:50 | 0.00 |
May | 0.115292E+11 | 0.279511E+10 | 309.14 | 0.938057E+10 | 0.214858E+10 | 0.00 | 1.00 | 02-MAY-13:05 | 0.00 | 01-MAY-00:10 | 33734.33 | 03-MAY-14:00 | 33641.77 | 03-MAY-13:00 | 8819.45 | 05-MAY-15:00 | 7351.12 | 03-MAY-13:00 | 0.00 |
June | 0.224726E+11 | 0.521822E+10 | 393.83 | 0.165315E+11 | 0.594109E+10 | 0.00 | 1.00 | 14-JUN-12:05 | 0.00 | 01-JUN-00:10 | 51883.44 | 29-JUN-13:00 | 33979.35 | 27-JUN-13:00 | 18800.31 | 29-JUN-13:00 | 11386.06 | 29-JUN-13:00 | 0.00 |
July | 0.381234E+11 | 0.867874E+10 | 434.31 | 0.252509E+11 | 0.128725E+11 | 0.00 | 1.00 | 02-JUL-16:02 | 0.00 | 01-JUL-00:10 | 79000.06 | 31-JUL-15:30 | 51748.82 | 31-JUL-14:00 | 32503.62 | 31-JUL-15:30 | 17487.78 | 31-JUL-15:30 | 0.00 |
August | 0.435855E+11 | 0.986241E+10 | 447.94 | 0.280529E+11 | 0.155326E+11 | 0.00 | 1.00 | 01-AUG-10:05 | 0.00 | 01-AUG-00:10 | 77495.69 | 14-AUG-13:20 | 49985.00 | 17-AUG-14:00 | 31315.66 | 14-AUG-14:00 | 17310.66 | 14-AUG-13:20 | 0.00 |
September | 0.254226E+11 | 0.601670E+10 | 377.97 | 0.182468E+11 | 0.717579E+10 | 0.00 | 1.00 | 01-SEP-12:40 | 0.00 | 01-SEP-00:10 | 63710.70 | 29-SEP-13:40 | 63710.70 | 29-SEP-13:40 | 24049.05 | 22-SEP-11:40 | 19255.42 | 29-SEP-13:00 | 0.00 |
October | 0.268120E+11 | 0.643343E+10 | 381.50 | 0.211839E+11 | 0.562804E+10 | 0.00 | 1.00 | 01-OCT-11:43 | 0.00 | 01-OCT-00:10 | 68780.26 | 03-OCT-13:10 | 65780.12 | 16-OCT-13:05 | 27377.34 | 03-OCT-13:30 | 20007.32 | 16-OCT-11:00 | 0.00 |
November | 0.667392E+10 | 0.165482E+10 | 224.33 | 0.569153E+10 | 0.982385E+09 | 0.00 | 1.00 | 19-NOV-11:02 | 0.00 | 01-NOV-00:10 | 30825.22 | 28-NOV-14:00 | 30825.22 | 28-NOV-14:00 | 7066.43 | 20-NOV-13:05 | 6940.15 | 19-NOV-13:02 | 0.00 |
December | 0.703864E+10 | 0.171089E+10 | 202.82 | 0.671892E+10 | 0.319715E+09 | 0.00 | 1.00 | 05-DEC-13:50 | 0.00 | 01-DEC-00:10 | 33816.55 | 05-DEC-15:00 | 33816.55 | 05-DEC-15:00 | 6363.92 | 07-DEC-13:00 | 7564.76 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.207156E+12 | 0.485942E+11 | 3528.38 | 0.151833E+12 | 0.553230E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.348728E+10 | 0.882391E+09 | 148.42 | 0.286809E+10 | 0.319715E+09 | 0.00 | 1.00 | 0.00 | 27033.46 | 27033.46 | 6363.92 | 6200.17 | 0.00 | ||||||
Maximum of Months | 0.435855E+11 | 0.986241E+10 | 447.94 | 0.280529E+11 | 0.155326E+11 | 0.00 | 1.00 | 0.00 | 79000.06 | 65780.12 | 32503.62 | 20007.32 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 291.61 | 0.00 | 291.61 | 202.16 | 1012.36 | 0.00 | 0.00 | 0.00 |
February | 366.04 | 0.00 | 366.04 | 238.85 | 918.82 | 0.00 | 0.00 | 0.00 |
March | 448.56 | 0.00 | 448.56 | 338.90 | 948.06 | 0.00 | 0.00 | 0.00 |
April | 516.79 | 1.99 | 514.80 | 453.24 | 765.03 | 0.00 | 0.00 | 0.00 |
May | 621.02 | 28.92 | 592.10 | 578.28 | 673.14 | 0.00 | 0.00 | 0.00 |
June | 661.73 | 64.70 | 597.03 | 725.95 | 532.66 | 0.00 | 0.00 | 0.00 |
July | 626.55 | 52.52 | 574.04 | 755.63 | 479.72 | 0.00 | 0.00 | 0.00 |
August | 520.33 | 10.42 | 509.91 | 607.51 | 501.74 | 0.00 | 0.00 | 0.00 |
September | 440.41 | 0.07 | 440.34 | 474.90 | 600.46 | 0.00 | 0.00 | 0.00 |
October | 349.34 | 0.00 | 349.34 | 413.48 | 668.94 | 0.00 | 0.00 | 0.00 |
November | 316.31 | 0.00 | 316.31 | 226.47 | 938.57 | 0.00 | 0.00 | 0.00 |
December | 271.46 | 0.00 | 271.46 | 182.09 | 1025.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.88 | 13.29 | 439.59 | 434.31 | 754.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 271.46 | 0.00 | 271.46 | 182.09 | 479.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.73 | 64.70 | 597.03 | 755.63 | 1025.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 524.39 | 280.46 | 243.94 | 645.55 | 644.45 | 0.00 | 0.00 | 0.00 |
February | 553.18 | 253.42 | 299.76 | 637.06 | 589.59 | 0.00 | 0.00 | 0.00 |
March | 671.95 | 299.39 | 372.57 | 804.02 | 607.40 | 0.00 | 0.00 | 0.00 |
April | 859.08 | 430.85 | 428.24 | 1154.90 | 504.20 | 0.00 | 0.00 | 0.00 |
May | 810.73 | 338.34 | 472.39 | 1047.14 | 462.83 | 0.00 | 0.00 | 0.00 |
June | 805.68 | 349.57 | 456.11 | 1110.52 | 372.12 | 0.00 | 0.00 | 0.00 |
July | 912.90 | 453.64 | 459.25 | 1350.95 | 336.49 | 0.00 | 0.00 | 0.00 |
August | 901.56 | 478.88 | 422.68 | 1352.84 | 341.97 | 0.00 | 0.00 | 0.00 |
September | 656.41 | 300.79 | 355.62 | 933.11 | 394.95 | 0.00 | 0.00 | 0.00 |
October | 581.04 | 298.64 | 282.40 | 845.10 | 433.96 | 0.00 | 0.00 | 0.00 |
November | 529.69 | 269.10 | 260.58 | 647.57 | 601.86 | 0.00 | 0.00 | 0.00 |
December | 505.31 | 280.76 | 224.56 | 621.50 | 651.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 693.59 | 336.82 | 356.77 | 931.24 | 494.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.31 | 253.42 | 224.56 | 621.50 | 336.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 912.90 | 478.88 | 472.39 | 1352.84 | 651.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1924.40 | 1411.64 | 512.77 | 2828.94 | 991.98 | 0.00 | 0.00 | 0.00 |
February | 1512.48 | 931.61 | 580.87 | 2095.51 | 905.42 | 0.00 | 0.00 | 0.00 |
March | 1205.80 | 582.46 | 623.34 | 1648.10 | 952.41 | 0.00 | 0.00 | 0.00 |
April | 1007.47 | 384.16 | 623.31 | 1463.24 | 805.30 | 0.00 | 0.00 | 0.00 |
May | 717.40 | 88.29 | 629.11 | 846.19 | 733.46 | 0.00 | 0.00 | 0.00 |
June | 629.35 | 38.00 | 591.35 | 741.25 | 577.61 | 0.00 | 0.00 | 0.00 |
July | 666.65 | 75.05 | 591.61 | 912.57 | 515.11 | 0.00 | 0.00 | 0.00 |
August | 856.45 | 270.15 | 586.30 | 1355.02 | 535.63 | 0.00 | 0.00 | 0.00 |
September | 1191.75 | 603.90 | 587.85 | 1891.24 | 622.31 | 0.00 | 0.00 | 0.00 |
October | 1515.63 | 1013.24 | 502.39 | 2411.59 | 674.62 | 0.00 | 0.00 | 0.00 |
November | 1842.09 | 1300.49 | 541.60 | 2694.50 | 921.36 | 0.00 | 0.00 | 0.00 |
December | 2055.88 | 1564.79 | 491.09 | 3034.44 | 1000.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1259.39 | 687.82 | 571.57 | 1826.09 | 768.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.35 | 38.00 | 491.09 | 741.25 | 515.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.88 | 1564.79 | 629.11 | 3034.44 | 1000.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.13 | 251.74 | 247.39 | 639.17 | 676.53 | 0.00 | 0.00 | 0.00 |
February | 595.46 | 274.89 | 320.57 | 724.93 | 614.52 | 0.00 | 0.00 | 0.00 |
March | 682.56 | 301.98 | 380.59 | 840.58 | 630.67 | 0.00 | 0.00 | 0.00 |
April | 940.95 | 489.95 | 451.00 | 1295.21 | 530.68 | 0.00 | 0.00 | 0.00 |
May | 924.31 | 426.94 | 497.37 | 1233.14 | 483.24 | 0.00 | 0.00 | 0.00 |
June | 979.20 | 489.58 | 489.62 | 1378.43 | 382.61 | 0.00 | 0.00 | 0.00 |
July | 1036.56 | 554.66 | 481.91 | 1537.68 | 345.94 | 0.00 | 0.00 | 0.00 |
August | 972.50 | 527.05 | 445.45 | 1463.52 | 358.31 | 0.00 | 0.00 | 0.00 |
September | 832.64 | 445.53 | 387.11 | 1213.56 | 410.18 | 0.00 | 0.00 | 0.00 |
October | 636.51 | 347.51 | 289.00 | 951.95 | 455.73 | 0.00 | 0.00 | 0.00 |
November | 574.96 | 300.75 | 274.22 | 749.18 | 625.12 | 0.00 | 0.00 | 0.00 |
December | 507.79 | 272.36 | 235.44 | 661.47 | 684.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 765.88 | 390.74 | 375.14 | 1059.02 | 516.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 499.13 | 251.74 | 235.44 | 639.17 | 345.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1036.56 | 554.66 | 497.37 | 1537.68 | 684.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.20 | 0.00 | 97.20 | 65.45 | 356.42 | 0.00 | 0.00 | 0.00 |
February | 122.01 | 0.00 | 122.01 | 81.06 | 317.30 | 0.00 | 0.00 | 0.00 |
March | 149.51 | 0.00 | 149.51 | 117.24 | 323.15 | 0.00 | 0.00 | 0.00 |
April | 172.26 | 0.66 | 171.59 | 159.33 | 255.61 | 0.00 | 0.00 | 0.00 |
May | 207.00 | 9.64 | 197.36 | 200.38 | 226.39 | 0.00 | 0.00 | 0.00 |
June | 220.57 | 21.56 | 199.00 | 252.67 | 176.17 | 0.00 | 0.00 | 0.00 |
July | 208.84 | 17.50 | 191.34 | 261.22 | 159.44 | 0.00 | 0.00 | 0.00 |
August | 173.44 | 3.47 | 169.96 | 209.73 | 167.12 | 0.00 | 0.00 | 0.00 |
September | 146.80 | 0.02 | 146.77 | 162.58 | 203.96 | 0.00 | 0.00 | 0.00 |
October | 116.44 | 0.00 | 116.44 | 138.98 | 231.77 | 0.00 | 0.00 | 0.00 |
November | 105.43 | 0.00 | 105.43 | 73.25 | 331.90 | 0.00 | 0.00 | 0.00 |
December | 90.48 | 0.00 | 90.48 | 58.28 | 361.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.95 | 4.43 | 146.52 | 148.75 | 258.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.48 | 0.00 | 90.48 | 58.28 | 159.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.57 | 21.56 | 199.00 | 261.22 | 361.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.20 | 0.00 | 97.20 | 65.45 | 356.44 | 0.00 | 0.00 | 0.00 |
February | 122.01 | 0.00 | 122.01 | 81.06 | 317.32 | 0.00 | 0.00 | 0.00 |
March | 149.52 | 0.00 | 149.52 | 117.25 | 323.17 | 0.00 | 0.00 | 0.00 |
April | 172.26 | 0.66 | 171.60 | 159.34 | 255.63 | 0.00 | 0.00 | 0.00 |
May | 207.01 | 9.64 | 197.37 | 200.38 | 226.40 | 0.00 | 0.00 | 0.00 |
June | 220.57 | 21.56 | 199.01 | 252.68 | 176.18 | 0.00 | 0.00 | 0.00 |
July | 208.85 | 17.50 | 191.35 | 261.23 | 159.45 | 0.00 | 0.00 | 0.00 |
August | 173.44 | 3.47 | 169.97 | 209.74 | 167.13 | 0.00 | 0.00 | 0.00 |
September | 146.80 | 0.02 | 146.78 | 162.59 | 203.97 | 0.00 | 0.00 | 0.00 |
October | 116.45 | 0.00 | 116.45 | 138.99 | 231.79 | 0.00 | 0.00 | 0.00 |
November | 105.43 | 0.00 | 105.43 | 73.25 | 331.92 | 0.00 | 0.00 | 0.00 |
December | 90.49 | 0.00 | 90.49 | 58.29 | 361.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.96 | 4.43 | 146.53 | 148.76 | 258.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.49 | 0.00 | 90.49 | 58.29 | 159.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.57 | 21.56 | 199.01 | 261.23 | 361.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.20 | 0.00 | 97.20 | 65.45 | 356.44 | 0.00 | 0.00 | 0.00 |
February | 122.01 | 0.00 | 122.01 | 81.06 | 317.32 | 0.00 | 0.00 | 0.00 |
March | 149.52 | 0.00 | 149.52 | 117.25 | 323.17 | 0.00 | 0.00 | 0.00 |
April | 172.26 | 0.66 | 171.60 | 159.34 | 255.63 | 0.00 | 0.00 | 0.00 |
May | 207.01 | 9.64 | 197.37 | 200.38 | 226.40 | 0.00 | 0.00 | 0.00 |
June | 220.57 | 21.56 | 199.01 | 252.68 | 176.18 | 0.00 | 0.00 | 0.00 |
July | 208.85 | 17.50 | 191.35 | 261.23 | 159.45 | 0.00 | 0.00 | 0.00 |
August | 173.44 | 3.47 | 169.97 | 209.74 | 167.13 | 0.00 | 0.00 | 0.00 |
September | 146.80 | 0.02 | 146.78 | 162.59 | 203.97 | 0.00 | 0.00 | 0.00 |
October | 116.45 | 0.00 | 116.45 | 138.99 | 231.79 | 0.00 | 0.00 | 0.00 |
November | 105.43 | 0.00 | 105.43 | 73.25 | 331.92 | 0.00 | 0.00 | 0.00 |
December | 90.49 | 0.00 | 90.49 | 58.29 | 361.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.96 | 4.43 | 146.53 | 148.76 | 258.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.49 | 0.00 | 90.49 | 58.29 | 159.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.57 | 21.56 | 199.01 | 261.23 | 361.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 504.44 | 269.79 | 234.65 | 612.65 | 668.96 | 0.00 | 0.00 | 0.00 |
February | 532.13 | 243.77 | 288.36 | 613.04 | 600.43 | 0.00 | 0.00 | 0.00 |
March | 646.38 | 287.99 | 358.39 | 778.03 | 610.93 | 0.00 | 0.00 | 0.00 |
April | 826.40 | 414.45 | 411.94 | 1123.71 | 502.55 | 0.00 | 0.00 | 0.00 |
May | 779.88 | 325.46 | 454.42 | 1019.85 | 459.45 | 0.00 | 0.00 | 0.00 |
June | 775.03 | 336.27 | 438.76 | 1085.51 | 362.46 | 0.00 | 0.00 | 0.00 |
July | 878.16 | 436.38 | 441.78 | 1315.15 | 332.98 | 0.00 | 0.00 | 0.00 |
August | 867.26 | 460.66 | 406.60 | 1314.80 | 341.08 | 0.00 | 0.00 | 0.00 |
September | 631.43 | 289.34 | 342.09 | 905.54 | 397.50 | 0.00 | 0.00 | 0.00 |
October | 558.93 | 287.28 | 271.66 | 815.70 | 442.83 | 0.00 | 0.00 | 0.00 |
November | 509.53 | 258.86 | 250.67 | 615.87 | 624.54 | 0.00 | 0.00 | 0.00 |
December | 486.08 | 270.07 | 216.01 | 588.54 | 676.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 667.20 | 324.00 | 343.20 | 901.02 | 501.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 486.08 | 243.77 | 216.01 | 588.54 | 332.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 878.16 | 460.66 | 454.42 | 1315.15 | 676.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.95 | 10.67 | 9.28 | 24.22 | 26.45 | 0.00 | 0.00 | 0.00 |
February | 21.04 | 9.64 | 11.40 | 24.24 | 23.74 | 0.00 | 0.00 | 0.00 |
March | 25.56 | 11.39 | 14.17 | 30.76 | 24.16 | 0.00 | 0.00 | 0.00 |
April | 32.67 | 16.39 | 16.29 | 44.43 | 19.87 | 0.00 | 0.00 | 0.00 |
May | 30.84 | 12.87 | 17.97 | 40.32 | 18.17 | 0.00 | 0.00 | 0.00 |
June | 30.64 | 13.30 | 17.35 | 42.92 | 14.33 | 0.00 | 0.00 | 0.00 |
July | 34.72 | 17.25 | 17.47 | 52.00 | 13.17 | 0.00 | 0.00 | 0.00 |
August | 34.29 | 18.21 | 16.08 | 51.99 | 13.49 | 0.00 | 0.00 | 0.00 |
September | 24.97 | 11.44 | 13.53 | 35.80 | 15.72 | 0.00 | 0.00 | 0.00 |
October | 22.10 | 11.36 | 10.74 | 32.25 | 17.51 | 0.00 | 0.00 | 0.00 |
November | 20.15 | 10.24 | 9.91 | 24.35 | 24.69 | 0.00 | 0.00 | 0.00 |
December | 19.22 | 10.68 | 8.54 | 23.27 | 26.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.38 | 12.81 | 13.57 | 35.63 | 19.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.22 | 9.64 | 8.54 | 23.27 | 13.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.72 | 18.21 | 17.97 | 52.00 | 26.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 641.46 | 470.54 | 170.92 | 942.56 | 364.73 | 0.00 | 0.00 | 0.00 |
February | 504.15 | 310.53 | 193.62 | 703.90 | 323.82 | 0.00 | 0.00 | 0.00 |
March | 401.93 | 194.15 | 207.78 | 557.79 | 330.12 | 0.00 | 0.00 | 0.00 |
April | 335.82 | 128.05 | 207.77 | 497.98 | 272.82 | 0.00 | 0.00 | 0.00 |
May | 239.13 | 29.43 | 209.70 | 294.56 | 243.60 | 0.00 | 0.00 | 0.00 |
June | 209.78 | 12.67 | 197.12 | 260.91 | 186.92 | 0.00 | 0.00 | 0.00 |
July | 222.22 | 25.01 | 197.20 | 314.91 | 169.74 | 0.00 | 0.00 | 0.00 |
August | 285.48 | 90.05 | 195.43 | 460.85 | 180.79 | 0.00 | 0.00 | 0.00 |
September | 397.24 | 201.30 | 195.95 | 636.98 | 217.96 | 0.00 | 0.00 | 0.00 |
October | 505.20 | 337.74 | 167.46 | 807.25 | 243.35 | 0.00 | 0.00 | 0.00 |
November | 614.02 | 433.49 | 180.53 | 899.61 | 337.47 | 0.00 | 0.00 | 0.00 |
December | 685.28 | 521.59 | 163.69 | 1011.30 | 368.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.79 | 229.27 | 190.52 | 615.45 | 269.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.78 | 12.67 | 163.69 | 260.91 | 169.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.28 | 521.59 | 209.70 | 1011.30 | 368.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 641.46 | 470.54 | 170.92 | 942.56 | 364.73 | 0.00 | 0.00 | 0.00 |
February | 504.15 | 310.53 | 193.62 | 703.90 | 323.82 | 0.00 | 0.00 | 0.00 |
March | 401.93 | 194.15 | 207.78 | 557.79 | 330.12 | 0.00 | 0.00 | 0.00 |
April | 335.82 | 128.05 | 207.77 | 497.98 | 272.82 | 0.00 | 0.00 | 0.00 |
May | 239.13 | 29.43 | 209.70 | 294.56 | 243.60 | 0.00 | 0.00 | 0.00 |
June | 209.78 | 12.67 | 197.12 | 260.91 | 186.92 | 0.00 | 0.00 | 0.00 |
July | 222.22 | 25.01 | 197.20 | 314.91 | 169.74 | 0.00 | 0.00 | 0.00 |
August | 285.48 | 90.05 | 195.43 | 460.85 | 180.79 | 0.00 | 0.00 | 0.00 |
September | 397.24 | 201.30 | 195.95 | 636.98 | 217.96 | 0.00 | 0.00 | 0.00 |
October | 505.20 | 337.74 | 167.46 | 807.25 | 243.35 | 0.00 | 0.00 | 0.00 |
November | 614.02 | 433.49 | 180.53 | 899.61 | 337.47 | 0.00 | 0.00 | 0.00 |
December | 685.28 | 521.59 | 163.69 | 1011.30 | 368.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.79 | 229.27 | 190.52 | 615.45 | 269.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.78 | 12.67 | 163.69 | 260.91 | 169.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.28 | 521.59 | 209.70 | 1011.30 | 368.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 641.42 | 470.51 | 170.91 | 942.50 | 364.71 | 0.00 | 0.00 | 0.00 |
February | 504.12 | 310.51 | 193.61 | 703.85 | 323.80 | 0.00 | 0.00 | 0.00 |
March | 401.90 | 194.14 | 207.76 | 557.75 | 330.10 | 0.00 | 0.00 | 0.00 |
April | 335.80 | 128.04 | 207.76 | 497.95 | 272.80 | 0.00 | 0.00 | 0.00 |
May | 239.12 | 29.43 | 209.69 | 294.54 | 243.58 | 0.00 | 0.00 | 0.00 |
June | 209.77 | 12.66 | 197.10 | 260.90 | 186.91 | 0.00 | 0.00 | 0.00 |
July | 222.20 | 25.01 | 197.19 | 314.89 | 169.73 | 0.00 | 0.00 | 0.00 |
August | 285.46 | 90.04 | 195.42 | 460.82 | 180.78 | 0.00 | 0.00 | 0.00 |
September | 397.22 | 201.28 | 195.94 | 636.94 | 217.95 | 0.00 | 0.00 | 0.00 |
October | 505.17 | 337.72 | 167.45 | 807.20 | 243.33 | 0.00 | 0.00 | 0.00 |
November | 613.98 | 433.46 | 180.52 | 899.55 | 337.45 | 0.00 | 0.00 | 0.00 |
December | 685.24 | 521.55 | 163.68 | 1011.24 | 368.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.76 | 229.26 | 190.51 | 615.41 | 269.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.77 | 12.66 | 163.68 | 260.90 | 169.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.24 | 521.55 | 209.69 | 1011.24 | 368.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.14 | 242.16 | 237.98 | 613.51 | 703.00 | 0.00 | 0.00 | 0.00 |
February | 572.81 | 264.43 | 308.37 | 702.18 | 629.93 | 0.00 | 0.00 | 0.00 |
March | 656.59 | 290.49 | 366.11 | 818.35 | 638.89 | 0.00 | 0.00 | 0.00 |
April | 905.15 | 471.31 | 433.84 | 1262.62 | 533.99 | 0.00 | 0.00 | 0.00 |
May | 889.14 | 410.69 | 478.45 | 1202.70 | 486.57 | 0.00 | 0.00 | 0.00 |
June | 941.95 | 470.95 | 470.99 | 1347.78 | 379.00 | 0.00 | 0.00 | 0.00 |
July | 997.13 | 533.55 | 463.57 | 1498.07 | 346.25 | 0.00 | 0.00 | 0.00 |
August | 935.50 | 507.00 | 428.50 | 1424.87 | 360.23 | 0.00 | 0.00 | 0.00 |
September | 800.96 | 428.58 | 372.38 | 1179.01 | 418.71 | 0.00 | 0.00 | 0.00 |
October | 612.30 | 334.29 | 278.01 | 920.94 | 468.83 | 0.00 | 0.00 | 0.00 |
November | 553.09 | 289.30 | 263.78 | 718.70 | 654.80 | 0.00 | 0.00 | 0.00 |
December | 488.47 | 261.99 | 226.48 | 633.68 | 713.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.74 | 375.87 | 360.87 | 1028.44 | 527.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.14 | 242.16 | 226.48 | 613.51 | 346.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 997.13 | 533.55 | 478.45 | 1498.07 | 713.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.98 | 9.57 | 9.41 | 24.26 | 27.80 | 0.00 | 0.00 | 0.00 |
February | 22.65 | 10.46 | 12.19 | 27.76 | 24.91 | 0.00 | 0.00 | 0.00 |
March | 25.96 | 11.49 | 14.48 | 32.36 | 25.26 | 0.00 | 0.00 | 0.00 |
April | 35.79 | 18.64 | 17.15 | 49.92 | 21.11 | 0.00 | 0.00 | 0.00 |
May | 35.16 | 16.24 | 18.92 | 47.55 | 19.24 | 0.00 | 0.00 | 0.00 |
June | 37.24 | 18.62 | 18.62 | 53.29 | 14.99 | 0.00 | 0.00 | 0.00 |
July | 39.43 | 21.10 | 18.33 | 59.23 | 13.69 | 0.00 | 0.00 | 0.00 |
August | 36.99 | 20.05 | 16.94 | 56.34 | 14.24 | 0.00 | 0.00 | 0.00 |
September | 31.67 | 16.95 | 14.72 | 46.62 | 16.56 | 0.00 | 0.00 | 0.00 |
October | 24.21 | 13.22 | 10.99 | 36.41 | 18.54 | 0.00 | 0.00 | 0.00 |
November | 21.87 | 11.44 | 10.43 | 28.42 | 25.89 | 0.00 | 0.00 | 0.00 |
December | 19.31 | 10.36 | 8.95 | 25.06 | 28.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.13 | 14.86 | 14.27 | 40.66 | 20.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.98 | 9.57 | 8.95 | 24.26 | 13.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.43 | 21.10 | 18.92 | 59.23 | 28.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 291.61 | 0.00 | 291.61 | 184.96 | 1090.72 | 0.00 | 0.00 | 0.00 |
February | 366.04 | 0.00 | 366.04 | 221.26 | 992.04 | 0.00 | 0.00 | 0.00 |
March | 448.56 | 0.00 | 448.56 | 323.39 | 1011.32 | 0.00 | 0.00 | 0.00 |
April | 516.79 | 1.99 | 514.80 | 446.70 | 807.23 | 0.00 | 0.00 | 0.00 |
May | 621.02 | 28.92 | 592.10 | 568.79 | 707.15 | 0.00 | 0.00 | 0.00 |
June | 661.73 | 64.70 | 597.03 | 725.00 | 555.35 | 0.00 | 0.00 | 0.00 |
July | 626.55 | 52.52 | 574.04 | 759.18 | 498.07 | 0.00 | 0.00 | 0.00 |
August | 520.33 | 10.42 | 509.91 | 608.62 | 523.71 | 0.00 | 0.00 | 0.00 |
September | 440.41 | 0.07 | 440.34 | 471.37 | 633.60 | 0.00 | 0.00 | 0.00 |
October | 349.34 | 0.00 | 349.34 | 405.82 | 710.63 | 0.00 | 0.00 | 0.00 |
November | 316.31 | 0.00 | 316.31 | 209.05 | 1012.04 | 0.00 | 0.00 | 0.00 |
December | 271.46 | 0.00 | 271.46 | 163.77 | 1109.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.88 | 13.29 | 439.59 | 425.23 | 803.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 271.46 | 0.00 | 271.46 | 163.77 | 498.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.73 | 64.70 | 597.03 | 759.18 | 1109.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 524.39 | 280.46 | 243.94 | 627.84 | 690.47 | 0.00 | 0.00 | 0.00 |
February | 553.18 | 253.42 | 299.76 | 620.66 | 632.91 | 0.00 | 0.00 | 0.00 |
March | 671.95 | 299.39 | 372.57 | 789.35 | 644.79 | 0.00 | 0.00 | 0.00 |
April | 859.08 | 430.85 | 428.24 | 1147.87 | 528.56 | 0.00 | 0.00 | 0.00 |
May | 810.73 | 338.34 | 472.39 | 1039.53 | 484.09 | 0.00 | 0.00 | 0.00 |
June | 805.68 | 349.57 | 456.11 | 1107.21 | 386.72 | 0.00 | 0.00 | 0.00 |
July | 912.90 | 453.64 | 459.25 | 1350.97 | 348.21 | 0.00 | 0.00 | 0.00 |
August | 901.56 | 478.88 | 422.68 | 1351.72 | 355.56 | 0.00 | 0.00 | 0.00 |
September | 656.41 | 300.79 | 355.62 | 928.52 | 415.33 | 0.00 | 0.00 | 0.00 |
October | 581.04 | 298.64 | 282.40 | 837.27 | 458.17 | 0.00 | 0.00 | 0.00 |
November | 529.69 | 269.10 | 260.58 | 631.40 | 643.51 | 0.00 | 0.00 | 0.00 |
December | 505.31 | 280.76 | 224.56 | 602.45 | 699.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 693.59 | 336.82 | 356.77 | 921.65 | 523.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.31 | 253.42 | 224.56 | 602.45 | 348.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 912.90 | 478.88 | 472.39 | 1351.72 | 699.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1924.40 | 1411.64 | 512.77 | 2812.16 | 1057.29 | 0.00 | 0.00 | 0.00 |
February | 1512.48 | 931.61 | 580.87 | 2080.27 | 969.55 | 0.00 | 0.00 | 0.00 |
March | 1205.80 | 582.46 | 623.34 | 1634.85 | 1011.79 | 0.00 | 0.00 | 0.00 |
April | 1007.47 | 384.16 | 623.31 | 1459.90 | 846.27 | 0.00 | 0.00 | 0.00 |
May | 717.40 | 88.29 | 629.11 | 841.32 | 770.92 | 0.00 | 0.00 | 0.00 |
June | 629.35 | 38.00 | 591.35 | 741.22 | 602.11 | 0.00 | 0.00 | 0.00 |
July | 666.65 | 75.05 | 591.61 | 916.64 | 534.13 | 0.00 | 0.00 | 0.00 |
August | 856.45 | 270.15 | 586.30 | 1358.97 | 557.91 | 0.00 | 0.00 | 0.00 |
September | 1191.75 | 603.90 | 587.85 | 1891.45 | 653.62 | 0.00 | 0.00 | 0.00 |
October | 1515.63 | 1013.24 | 502.39 | 2407.16 | 710.70 | 0.00 | 0.00 | 0.00 |
November | 1842.09 | 1300.49 | 541.60 | 2679.94 | 980.93 | 0.00 | 0.00 | 0.00 |
December | 2055.88 | 1564.79 | 491.09 | 3016.57 | 1067.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1259.39 | 687.82 | 571.57 | 1819.29 | 812.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.35 | 38.00 | 491.09 | 741.22 | 534.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.88 | 1564.79 | 629.11 | 3016.57 | 1067.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.13 | 251.74 | 247.39 | 629.12 | 726.92 | 0.00 | 0.00 | 0.00 |
February | 595.46 | 274.89 | 320.57 | 714.87 | 661.40 | 0.00 | 0.00 | 0.00 |
March | 682.56 | 301.98 | 380.59 | 832.27 | 672.21 | 0.00 | 0.00 | 0.00 |
April | 940.95 | 489.95 | 451.00 | 1293.70 | 558.39 | 0.00 | 0.00 | 0.00 |
May | 924.31 | 426.94 | 497.37 | 1231.64 | 507.99 | 0.00 | 0.00 | 0.00 |
June | 979.20 | 489.58 | 489.62 | 1381.28 | 399.07 | 0.00 | 0.00 | 0.00 |
July | 1036.56 | 554.66 | 481.91 | 1542.78 | 359.26 | 0.00 | 0.00 | 0.00 |
August | 972.50 | 527.05 | 445.45 | 1467.68 | 373.48 | 0.00 | 0.00 | 0.00 |
September | 832.64 | 445.53 | 387.11 | 1214.16 | 431.68 | 0.00 | 0.00 | 0.00 |
October | 636.51 | 347.51 | 289.00 | 949.01 | 482.40 | 0.00 | 0.00 | 0.00 |
November | 574.96 | 300.75 | 274.22 | 739.61 | 671.65 | 0.00 | 0.00 | 0.00 |
December | 507.79 | 272.36 | 235.44 | 650.56 | 737.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 765.88 | 390.74 | 375.14 | 1055.54 | 547.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 499.13 | 251.74 | 235.44 | 629.12 | 359.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1036.56 | 554.66 | 497.37 | 1542.78 | 737.67 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.541465E+09 | 0.271150E+10 |
February | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.577833E+09 | 0.222281E+10 |
March | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.907715E+09 | 0.253928E+10 |
April | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.117479E+10 | 0.198296E+10 |
May | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.154887E+10 | 0.180293E+10 |
June | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.188166E+10 | 0.138065E+10 |
July | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.202388E+10 | 0.128488E+10 |
August | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.162714E+10 | 0.134385E+10 |
September | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.123094E+10 | 0.155640E+10 |
October | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.110745E+10 | 0.179169E+10 |
November | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.587005E+09 | 0.243278E+10 |
December | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.487712E+09 | 0.274599E+10 |
Annual Sum or Average | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.136965E+11 | 0.237957E+11 |
Minimum of Months | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.487712E+09 | 0.128488E+10 |
Maximum of Months | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.202388E+10 | 0.274599E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.172905E+10 | 0.172609E+10 |
February | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.154118E+10 | 0.142633E+10 |
March | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.215350E+10 | 0.162685E+10 |
April | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.299351E+10 | 0.130688E+10 |
May | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.280465E+10 | 0.123966E+10 |
June | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.287848E+10 | 0.964543E+09 |
July | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.361839E+10 | 0.901253E+09 |
August | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.362344E+10 | 0.915923E+09 |
September | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.241862E+10 | 0.102371E+10 |
October | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.226351E+10 | 0.116232E+10 |
November | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.167851E+10 | 0.156001E+10 |
December | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.166463E+10 | 0.174436E+10 |
Annual Sum or Average | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.293675E+11 | 0.155979E+11 |
Minimum of Months | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.154118E+10 | 0.901253E+09 |
Maximum of Months | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.362344E+10 | 0.174436E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.757703E+10 | 0.265692E+10 |
February | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.506947E+10 | 0.219039E+10 |
March | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.441428E+10 | 0.255094E+10 |
April | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.379272E+10 | 0.208735E+10 |
May | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.226644E+10 | 0.196449E+10 |
June | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.192131E+10 | 0.149717E+10 |
July | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.244424E+10 | 0.137968E+10 |
August | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.362930E+10 | 0.143463E+10 |
September | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.490210E+10 | 0.161303E+10 |
October | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.645920E+10 | 0.180692E+10 |
November | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.698414E+10 | 0.238816E+10 |
December | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.812744E+10 | 0.267964E+10 |
Annual Sum or Average | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.575877E+11 | 0.242493E+11 |
Minimum of Months | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.192131E+10 | 0.137968E+10 |
Maximum of Months | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.812744E+10 | 0.267964E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.171195E+10 | 0.181201E+10 |
February | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.175374E+10 | 0.148664E+10 |
March | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.225140E+10 | 0.168920E+10 |
April | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.335719E+10 | 0.137551E+10 |
May | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.330284E+10 | 0.129431E+10 |
June | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.357288E+10 | 0.991714E+09 |
July | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.411852E+10 | 0.926560E+09 |
August | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.391989E+10 | 0.959693E+09 |
September | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.314555E+10 | 0.106319E+10 |
October | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.254971E+10 | 0.122063E+10 |
November | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.194188E+10 | 0.162032E+10 |
December | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.177168E+10 | 0.183321E+10 |
Annual Sum or Average | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.333972E+11 | 0.162730E+11 |
Minimum of Months | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.171195E+10 | 0.926560E+09 |
Maximum of Months | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.411852E+10 | 0.183321E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260334E+09 | 0.00 | 0.260334E+09 | 0.175301E+09 | 0.954622E+09 |
February | 0.295164E+09 | 0.00 | 0.295164E+09 | 0.196096E+09 | 0.767606E+09 |
March | 0.400455E+09 | 0.00 | 0.400455E+09 | 0.314024E+09 | 0.865521E+09 |
April | 0.446488E+09 | 1718463.26 | 0.444769E+09 | 0.412991E+09 | 0.662544E+09 |
May | 0.554420E+09 | 25816832.63 | 0.528603E+09 | 0.536692E+09 | 0.606365E+09 |
June | 0.571706E+09 | 55893851.50 | 0.515812E+09 | 0.654914E+09 | 0.456622E+09 |
July | 0.559359E+09 | 46883561.74 | 0.512476E+09 | 0.699642E+09 | 0.427052E+09 |
August | 0.464529E+09 | 9301741.30 | 0.455227E+09 | 0.561741E+09 | 0.447627E+09 |
September | 0.380493E+09 | 59638.15 | 0.380434E+09 | 0.421406E+09 | 0.528658E+09 |
October | 0.311880E+09 | 0.00 | 0.311880E+09 | 0.372242E+09 | 0.620784E+09 |
November | 0.273276E+09 | 0.00 | 0.273276E+09 | 0.189857E+09 | 0.860276E+09 |
December | 0.242349E+09 | 0.00 | 0.242349E+09 | 0.156107E+09 | 0.969381E+09 |
Annual Sum or Average | 0.476046E+10 | 0.139674E+09 | 0.462078E+10 | 0.469101E+10 | 0.816706E+10 |
Minimum of Months | 0.242349E+09 | 0.00 | 0.242349E+09 | 0.156107E+09 | 0.427052E+09 |
Maximum of Months | 0.571706E+09 | 55893851.50 | 0.528603E+09 | 0.699642E+09 | 0.969381E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260345E+09 | 0.00 | 0.260345E+09 | 0.175307E+09 | 0.954678E+09 |
February | 0.295176E+09 | 0.00 | 0.295176E+09 | 0.196100E+09 | 0.767651E+09 |
March | 0.400471E+09 | 0.00 | 0.400471E+09 | 0.314033E+09 | 0.865573E+09 |
April | 0.446507E+09 | 1718509.46 | 0.444789E+09 | 0.413008E+09 | 0.662584E+09 |
May | 0.554443E+09 | 25817526.59 | 0.528625E+09 | 0.536708E+09 | 0.606401E+09 |
June | 0.571730E+09 | 55895353.94 | 0.515834E+09 | 0.654936E+09 | 0.456649E+09 |
July | 0.559383E+09 | 46884821.98 | 0.512499E+09 | 0.699671E+09 | 0.427076E+09 |
August | 0.464550E+09 | 9301991.33 | 0.455248E+09 | 0.561766E+09 | 0.447652E+09 |
September | 0.380510E+09 | 59639.75 | 0.380450E+09 | 0.421424E+09 | 0.528688E+09 |
October | 0.311894E+09 | 0.00 | 0.311894E+09 | 0.372258E+09 | 0.620819E+09 |
November | 0.273287E+09 | 0.00 | 0.273287E+09 | 0.189863E+09 | 0.860326E+09 |
December | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.156113E+09 | 0.969437E+09 |
Annual Sum or Average | 0.476066E+10 | 0.139678E+09 | 0.462098E+10 | 0.469119E+10 | 0.816753E+10 |
Minimum of Months | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.156113E+09 | 0.427076E+09 |
Maximum of Months | 0.571730E+09 | 55895353.94 | 0.528625E+09 | 0.699671E+09 | 0.969437E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260345E+09 | 0.00 | 0.260345E+09 | 0.175307E+09 | 0.954678E+09 |
February | 0.295176E+09 | 0.00 | 0.295176E+09 | 0.196100E+09 | 0.767651E+09 |
March | 0.400471E+09 | 0.00 | 0.400471E+09 | 0.314033E+09 | 0.865573E+09 |
April | 0.446507E+09 | 1718509.46 | 0.444789E+09 | 0.413008E+09 | 0.662584E+09 |
May | 0.554443E+09 | 25817526.59 | 0.528625E+09 | 0.536708E+09 | 0.606401E+09 |
June | 0.571730E+09 | 55895353.94 | 0.515834E+09 | 0.654936E+09 | 0.456649E+09 |
July | 0.559383E+09 | 46884821.98 | 0.512499E+09 | 0.699671E+09 | 0.427076E+09 |
August | 0.464550E+09 | 9301991.33 | 0.455248E+09 | 0.561766E+09 | 0.447652E+09 |
September | 0.380510E+09 | 59639.75 | 0.380450E+09 | 0.421424E+09 | 0.528688E+09 |
October | 0.311894E+09 | 0.00 | 0.311894E+09 | 0.372258E+09 | 0.620819E+09 |
November | 0.273287E+09 | 0.00 | 0.273287E+09 | 0.189863E+09 | 0.860326E+09 |
December | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.156113E+09 | 0.969437E+09 |
Annual Sum or Average | 0.476066E+10 | 0.139678E+09 | 0.462098E+10 | 0.469119E+10 | 0.816753E+10 |
Minimum of Months | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.156113E+09 | 0.427076E+09 |
Maximum of Months | 0.571730E+09 | 55895353.94 | 0.528625E+09 | 0.699671E+09 | 0.969437E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135109E+10 | 0.722593E+09 | 0.628499E+09 | 0.164093E+10 | 0.179174E+10 |
February | 0.128733E+10 | 0.589736E+09 | 0.697598E+09 | 0.148307E+10 | 0.145256E+10 |
March | 0.173128E+10 | 0.771360E+09 | 0.959917E+09 | 0.208388E+10 | 0.163632E+10 |
April | 0.214202E+10 | 0.107426E+10 | 0.106776E+10 | 0.291267E+10 | 0.130261E+10 |
May | 0.208884E+10 | 0.871716E+09 | 0.121712E+10 | 0.273157E+10 | 0.123059E+10 |
June | 0.200887E+10 | 0.871607E+09 | 0.113726E+10 | 0.281364E+10 | 0.939507E+09 |
July | 0.235207E+10 | 0.116880E+10 | 0.118327E+10 | 0.352250E+10 | 0.891845E+09 |
August | 0.232286E+10 | 0.123382E+10 | 0.108904E+10 | 0.352156E+10 | 0.913541E+09 |
September | 0.163667E+10 | 0.749981E+09 | 0.886691E+09 | 0.234715E+10 | 0.103033E+10 |
October | 0.149704E+10 | 0.769439E+09 | 0.727605E+09 | 0.218478E+10 | 0.118609E+10 |
November | 0.132071E+10 | 0.670972E+09 | 0.649736E+09 | 0.159634E+10 | 0.161880E+10 |
December | 0.130193E+10 | 0.723362E+09 | 0.578566E+09 | 0.157635E+10 | 0.181103E+10 |
Annual Sum or Average | 0.210407E+11 | 0.102176E+11 | 0.108231E+11 | 0.284144E+11 | 0.158050E+11 |
Minimum of Months | 0.128733E+10 | 0.589736E+09 | 0.578566E+09 | 0.148307E+10 | 0.891845E+09 |
Maximum of Months | 0.235207E+10 | 0.123382E+10 | 0.121712E+10 | 0.352250E+10 | 0.181103E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53420946.35 | 28570678.17 | 24850268.18 | 64881004.09 | 70843714.64 |
February | 50900029.87 | 23317617.75 | 27582412.12 | 58639106.31 | 57433076.10 |
March | 68453131.60 | 30498874.53 | 37954257.08 | 82394825.58 | 64698475.12 |
April | 84693429.20 | 42475266.96 | 42218162.25 | 0.115164E+09 | 51504166.90 |
May | 82590686.80 | 34466861.00 | 48123825.80 | 0.108004E+09 | 48656374.78 |
June | 79428758.87 | 34462562.24 | 44966196.63 | 0.111249E+09 | 37147262.02 |
July | 92998785.53 | 46213353.89 | 46785431.64 | 0.139276E+09 | 35262763.60 |
August | 91843830.39 | 48784140.54 | 43059689.84 | 0.139239E+09 | 36120601.78 |
September | 64712538.24 | 29653592.71 | 35058945.53 | 92804302.23 | 40738173.70 |
October | 59191794.02 | 30422932.67 | 28768861.35 | 86384306.38 | 46896897.39 |
November | 52219614.40 | 26529622.89 | 25689991.51 | 63117877.58 | 64005766.04 |
December | 51477071.96 | 28601093.78 | 22875978.19 | 62327584.22 | 71606335.55 |
Annual Sum or Average | 0.831931E+09 | 0.403997E+09 | 0.427934E+09 | 0.112348E+10 | 0.624914E+09 |
Minimum of Months | 50900029.87 | 23317617.75 | 22875978.19 | 58639106.31 | 35262763.60 |
Maximum of Months | 92998785.53 | 48784140.54 | 48123825.80 | 0.139276E+09 | 71606335.55 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171808E+10 | 0.126029E+10 | 0.457791E+09 | 0.252454E+10 | 0.976902E+09 |
February | 0.121964E+10 | 0.751233E+09 | 0.468409E+09 | 0.170287E+10 | 0.783396E+09 |
March | 0.107652E+10 | 0.520007E+09 | 0.556513E+09 | 0.149398E+10 | 0.884197E+09 |
April | 0.870447E+09 | 0.331907E+09 | 0.538540E+09 | 0.129077E+10 | 0.707151E+09 |
May | 0.640488E+09 | 78819929.33 | 0.561669E+09 | 0.788937E+09 | 0.652455E+09 |
June | 0.543755E+09 | 32829474.14 | 0.510925E+09 | 0.676285E+09 | 0.484490E+09 |
July | 0.595185E+09 | 66999882.23 | 0.528186E+09 | 0.843464E+09 | 0.454641E+09 |
August | 0.764632E+09 | 0.241186E+09 | 0.523445E+09 | 0.123434E+10 | 0.484240E+09 |
September | 0.102966E+10 | 0.521760E+09 | 0.507898E+09 | 0.165105E+10 | 0.564950E+09 |
October | 0.135313E+10 | 0.904602E+09 | 0.448528E+09 | 0.216215E+10 | 0.651776E+09 |
November | 0.159154E+10 | 0.112360E+10 | 0.467940E+09 | 0.233179E+10 | 0.874713E+09 |
December | 0.183546E+10 | 0.139702E+10 | 0.438437E+09 | 0.270866E+10 | 0.987054E+09 |
Annual Sum or Average | 0.132385E+11 | 0.723025E+10 | 0.600828E+10 | 0.194088E+11 | 0.850597E+10 |
Minimum of Months | 0.543755E+09 | 32829474.14 | 0.438437E+09 | 0.676285E+09 | 0.454641E+09 |
Maximum of Months | 0.183546E+10 | 0.139702E+10 | 0.561669E+09 | 0.270866E+10 | 0.987054E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171808E+10 | 0.126029E+10 | 0.457791E+09 | 0.252454E+10 | 0.976902E+09 |
February | 0.121964E+10 | 0.751233E+09 | 0.468409E+09 | 0.170287E+10 | 0.783396E+09 |
March | 0.107652E+10 | 0.520007E+09 | 0.556513E+09 | 0.149398E+10 | 0.884197E+09 |
April | 0.870447E+09 | 0.331907E+09 | 0.538540E+09 | 0.129077E+10 | 0.707151E+09 |
May | 0.640488E+09 | 78819929.33 | 0.561669E+09 | 0.788937E+09 | 0.652455E+09 |
June | 0.543755E+09 | 32829474.14 | 0.510925E+09 | 0.676285E+09 | 0.484490E+09 |
July | 0.595185E+09 | 66999882.23 | 0.528186E+09 | 0.843464E+09 | 0.454641E+09 |
August | 0.764632E+09 | 0.241186E+09 | 0.523445E+09 | 0.123434E+10 | 0.484240E+09 |
September | 0.102966E+10 | 0.521760E+09 | 0.507898E+09 | 0.165105E+10 | 0.564950E+09 |
October | 0.135313E+10 | 0.904602E+09 | 0.448528E+09 | 0.216215E+10 | 0.651776E+09 |
November | 0.159154E+10 | 0.112360E+10 | 0.467940E+09 | 0.233179E+10 | 0.874713E+09 |
December | 0.183546E+10 | 0.139702E+10 | 0.438437E+09 | 0.270866E+10 | 0.987054E+09 |
Annual Sum or Average | 0.132385E+11 | 0.723025E+10 | 0.600828E+10 | 0.194088E+11 | 0.850597E+10 |
Minimum of Months | 0.543755E+09 | 32829474.14 | 0.438437E+09 | 0.676285E+09 | 0.454641E+09 |
Maximum of Months | 0.183546E+10 | 0.139702E+10 | 0.561669E+09 | 0.270866E+10 | 0.987054E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171797E+10 | 0.126021E+10 | 0.457763E+09 | 0.252438E+10 | 0.976840E+09 |
February | 0.121956E+10 | 0.751185E+09 | 0.468379E+09 | 0.170277E+10 | 0.783347E+09 |
March | 0.107645E+10 | 0.519974E+09 | 0.556477E+09 | 0.149389E+10 | 0.884141E+09 |
April | 0.870392E+09 | 0.331886E+09 | 0.538506E+09 | 0.129069E+10 | 0.707106E+09 |
May | 0.640448E+09 | 78814948.36 | 0.561633E+09 | 0.788887E+09 | 0.652413E+09 |
June | 0.543720E+09 | 32827399.51 | 0.510893E+09 | 0.676243E+09 | 0.484460E+09 |
July | 0.595148E+09 | 66995648.21 | 0.528152E+09 | 0.843410E+09 | 0.454612E+09 |
August | 0.764583E+09 | 0.241171E+09 | 0.523412E+09 | 0.123426E+10 | 0.484210E+09 |
September | 0.102959E+10 | 0.521727E+09 | 0.507866E+09 | 0.165095E+10 | 0.564915E+09 |
October | 0.135305E+10 | 0.904545E+09 | 0.448500E+09 | 0.216201E+10 | 0.651734E+09 |
November | 0.159144E+10 | 0.112353E+10 | 0.467910E+09 | 0.233164E+10 | 0.874658E+09 |
December | 0.183534E+10 | 0.139693E+10 | 0.438410E+09 | 0.270849E+10 | 0.986992E+09 |
Annual Sum or Average | 0.132377E+11 | 0.722979E+10 | 0.600790E+10 | 0.194076E+11 | 0.850543E+10 |
Minimum of Months | 0.543720E+09 | 32827399.51 | 0.438410E+09 | 0.676243E+09 | 0.454612E+09 |
Maximum of Months | 0.183534E+10 | 0.139693E+10 | 0.561633E+09 | 0.270849E+10 | 0.986992E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128601E+10 | 0.648601E+09 | 0.637405E+09 | 0.164321E+10 | 0.188293E+10 |
February | 0.138574E+10 | 0.639720E+09 | 0.746019E+09 | 0.169872E+10 | 0.152392E+10 |
March | 0.175862E+10 | 0.778037E+09 | 0.980579E+09 | 0.219186E+10 | 0.171120E+10 |
April | 0.234615E+10 | 0.122163E+10 | 0.112452E+10 | 0.327271E+10 | 0.138409E+10 |
May | 0.238147E+10 | 0.109999E+10 | 0.128148E+10 | 0.322132E+10 | 0.130322E+10 |
June | 0.244152E+10 | 0.122071E+10 | 0.122081E+10 | 0.349345E+10 | 0.982369E+09 |
July | 0.267070E+10 | 0.142906E+10 | 0.124164E+10 | 0.401244E+10 | 0.927398E+09 |
August | 0.250564E+10 | 0.135795E+10 | 0.114769E+10 | 0.381638E+10 | 0.964847E+09 |
September | 0.207609E+10 | 0.111088E+10 | 0.965207E+09 | 0.305600E+10 | 0.108530E+10 |
October | 0.163997E+10 | 0.895354E+09 | 0.744621E+09 | 0.246666E+10 | 0.125571E+10 |
November | 0.143360E+10 | 0.749872E+09 | 0.683729E+09 | 0.186286E+10 | 0.169724E+10 |
December | 0.130832E+10 | 0.701720E+09 | 0.606601E+09 | 0.169726E+10 | 0.191235E+10 |
Annual Sum or Average | 0.232338E+11 | 0.118535E+11 | 0.113803E+11 | 0.324329E+11 | 0.166306E+11 |
Minimum of Months | 0.128601E+10 | 0.639720E+09 | 0.606601E+09 | 0.164321E+10 | 0.927398E+09 |
Maximum of Months | 0.267070E+10 | 0.142906E+10 | 0.128148E+10 | 0.401244E+10 | 0.191235E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50847388.40 | 25645034.41 | 25202353.99 | 64970913.15 | 74449125.10 |
February | 54790705.92 | 25293858.53 | 29496847.39 | 67165696.92 | 60254431.12 |
March | 69533916.73 | 30762785.10 | 38771131.64 | 86664024.38 | 67659182.80 |
April | 92764216.28 | 48301985.15 | 44462231.13 | 0.129400E+09 | 54725663.20 |
May | 94161049.55 | 43492648.38 | 50668401.16 | 0.127368E+09 | 51528145.60 |
June | 96535428.04 | 48265674.06 | 48269753.98 | 0.138127E+09 | 38841986.88 |
July | 0.105597E+09 | 56503714.35 | 49093129.74 | 0.158648E+09 | 36668455.78 |
August | 99070456.15 | 53691856.15 | 45378600.00 | 0.150896E+09 | 38149162.96 |
September | 82086361.34 | 43923044.09 | 38163317.25 | 0.120831E+09 | 42911700.73 |
October | 64842956.12 | 35401356.91 | 29441599.21 | 97529189.51 | 49649501.89 |
November | 56683134.85 | 29649156.44 | 27033978.40 | 73655580.16 | 67107292.44 |
December | 51729684.55 | 27745281.96 | 23984402.59 | 67107978.44 | 75612380.52 |
Annual Sum or Average | 0.918642E+09 | 0.468676E+09 | 0.449966E+09 | 0.128236E+10 | 0.657557E+09 |
Minimum of Months | 50847388.40 | 25293858.53 | 23984402.59 | 64970913.15 | 36668455.78 |
Maximum of Months | 0.105597E+09 | 56503714.35 | 50668401.16 | 0.158648E+09 | 75612380.52 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.495385E+09 | 0.292138E+10 |
February | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.535284E+09 | 0.239994E+10 |
March | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.866165E+09 | 0.270871E+10 |
April | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.115784E+10 | 0.209234E+10 |
May | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.152346E+10 | 0.189403E+10 |
June | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.187920E+10 | 0.143947E+10 |
July | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.203340E+10 | 0.133402E+10 |
August | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.163014E+10 | 0.140272E+10 |
September | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.122180E+10 | 0.164230E+10 |
October | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.108694E+10 | 0.190335E+10 |
November | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.541863E+09 | 0.262322E+10 |
December | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.438646E+09 | 0.297209E+10 |
Annual Sum or Average | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.134101E+11 | 0.253336E+11 |
Minimum of Months | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.438646E+09 | 0.133402E+10 |
Maximum of Months | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.203340E+10 | 0.297209E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.168161E+10 | 0.184935E+10 |
February | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.150149E+10 | 0.153114E+10 |
March | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.211418E+10 | 0.172700E+10 |
April | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.297527E+10 | 0.137002E+10 |
May | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.278427E+10 | 0.129658E+10 |
June | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.286990E+10 | 0.100237E+10 |
July | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.361843E+10 | 0.932648E+09 |
August | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.362046E+10 | 0.952319E+09 |
September | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.240672E+10 | 0.107654E+10 |
October | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.224255E+10 | 0.122717E+10 |
November | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.163659E+10 | 0.166797E+10 |
December | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.161360E+10 | 0.187440E+10 |
Annual Sum or Average | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.290651E+11 | 0.165075E+11 |
Minimum of Months | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.150149E+10 | 0.932648E+09 |
Maximum of Months | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.362046E+10 | 0.187440E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.753209E+10 | 0.283184E+10 |
February | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.503258E+10 | 0.234553E+10 |
March | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.437879E+10 | 0.270999E+10 |
April | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.378406E+10 | 0.219354E+10 |
May | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.225340E+10 | 0.206482E+10 |
June | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.192125E+10 | 0.156068E+10 |
July | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.245513E+10 | 0.143062E+10 |
August | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.363986E+10 | 0.149431E+10 |
September | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.490263E+10 | 0.169417E+10 |
October | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.644735E+10 | 0.190355E+10 |
November | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.694640E+10 | 0.254257E+10 |
December | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.807959E+10 | 0.285845E+10 |
Annual Sum or Average | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.573731E+11 | 0.256301E+11 |
Minimum of Months | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.192125E+10 | 0.143062E+10 |
Maximum of Months | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.807959E+10 | 0.285845E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.168504E+10 | 0.194699E+10 |
February | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.172941E+10 | 0.160007E+10 |
March | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.222915E+10 | 0.180044E+10 |
April | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.335328E+10 | 0.144736E+10 |
May | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.329882E+10 | 0.136060E+10 |
June | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.358028E+10 | 0.103438E+10 |
July | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.413219E+10 | 0.962254E+09 |
August | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.393103E+10 | 0.100032E+10 |
September | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.314710E+10 | 0.111891E+10 |
October | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.254184E+10 | 0.129207E+10 |
November | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.191707E+10 | 0.174091E+10 |
December | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.174245E+10 | 0.197578E+10 |
Annual Sum or Average | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.332876E+11 | 0.172801E+11 |
Minimum of Months | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.168504E+10 | 0.962254E+09 |
Maximum of Months | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.413219E+10 | 0.197578E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 202.16 | 1012.36 | 291.61 | 0.00 | 291.61 | 0.00 | 0.00 |
February | 238.85 | 918.82 | 366.04 | 0.00 | 366.04 | 0.00 | 0.00 |
March | 338.90 | 948.06 | 448.56 | 0.00 | 448.56 | 0.00 | 0.00 |
April | 453.24 | 765.03 | 516.79 | 1.99 | 514.80 | 0.00 | 0.00 |
May | 578.28 | 673.14 | 621.02 | 28.92 | 592.10 | 0.00 | 0.00 |
June | 725.95 | 532.66 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
July | 755.63 | 479.72 | 626.55 | 52.52 | 574.04 | 0.00 | 0.00 |
August | 607.51 | 501.74 | 520.33 | 10.42 | 509.91 | 0.00 | 0.00 |
September | 474.90 | 600.46 | 440.41 | 0.07 | 440.34 | 0.00 | 0.00 |
October | 413.48 | 668.94 | 349.34 | 0.00 | 349.34 | 0.00 | 0.00 |
November | 226.47 | 938.57 | 316.31 | 0.00 | 316.31 | 0.00 | 0.00 |
December | 182.09 | 1025.23 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Annual Sum or Average | 434.31 | 754.56 | 452.88 | 13.29 | 439.59 | 0.00 | 0.00 |
Minimum of Months | 182.09 | 479.72 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Maximum of Months | 755.63 | 1025.23 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 645.55 | 644.45 | 524.39 | 280.46 | 243.94 | 0.00 | 0.00 |
February | 637.06 | 589.59 | 553.18 | 253.42 | 299.76 | 0.00 | 0.00 |
March | 804.02 | 607.40 | 671.95 | 299.39 | 372.57 | 0.00 | 0.00 |
April | 1154.90 | 504.20 | 859.08 | 430.85 | 428.24 | 0.00 | 0.00 |
May | 1047.14 | 462.83 | 810.73 | 338.34 | 472.39 | 0.00 | 0.00 |
June | 1110.52 | 372.12 | 805.68 | 349.57 | 456.11 | 0.00 | 0.00 |
July | 1350.95 | 336.49 | 912.90 | 453.64 | 459.25 | 0.00 | 0.00 |
August | 1352.84 | 341.97 | 901.56 | 478.88 | 422.68 | 0.00 | 0.00 |
September | 933.11 | 394.95 | 656.41 | 300.79 | 355.62 | 0.00 | 0.00 |
October | 845.10 | 433.96 | 581.04 | 298.64 | 282.40 | 0.00 | 0.00 |
November | 647.57 | 601.86 | 529.69 | 269.10 | 260.58 | 0.00 | 0.00 |
December | 621.50 | 651.27 | 505.31 | 280.76 | 224.56 | 0.00 | 0.00 |
Annual Sum or Average | 931.24 | 494.61 | 693.59 | 336.82 | 356.77 | 0.00 | 0.00 |
Minimum of Months | 621.50 | 336.49 | 505.31 | 253.42 | 224.56 | 0.00 | 0.00 |
Maximum of Months | 1352.84 | 651.27 | 912.90 | 478.88 | 472.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2828.94 | 991.98 | 1924.40 | 1411.64 | 512.77 | 0.00 | 0.00 |
February | 2095.51 | 905.42 | 1512.48 | 931.61 | 580.87 | 0.00 | 0.00 |
March | 1648.10 | 952.41 | 1205.80 | 582.46 | 623.34 | 0.00 | 0.00 |
April | 1463.24 | 805.30 | 1007.47 | 384.16 | 623.31 | 0.00 | 0.00 |
May | 846.19 | 733.46 | 717.40 | 88.29 | 629.11 | 0.00 | 0.00 |
June | 741.25 | 577.61 | 629.35 | 38.00 | 591.35 | 0.00 | 0.00 |
July | 912.57 | 515.11 | 666.65 | 75.05 | 591.61 | 0.00 | 0.00 |
August | 1355.02 | 535.63 | 856.45 | 270.15 | 586.30 | 0.00 | 0.00 |
September | 1891.24 | 622.31 | 1191.75 | 603.90 | 587.85 | 0.00 | 0.00 |
October | 2411.59 | 674.62 | 1515.63 | 1013.24 | 502.39 | 0.00 | 0.00 |
November | 2694.50 | 921.36 | 1842.09 | 1300.49 | 541.60 | 0.00 | 0.00 |
December | 3034.44 | 1000.46 | 2055.88 | 1564.79 | 491.09 | 0.00 | 0.00 |
Annual Sum or Average | 1826.09 | 768.94 | 1259.39 | 687.82 | 571.57 | 0.00 | 0.00 |
Minimum of Months | 741.25 | 515.11 | 629.35 | 38.00 | 491.09 | 0.00 | 0.00 |
Maximum of Months | 3034.44 | 1000.46 | 2055.88 | 1564.79 | 629.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 639.17 | 676.53 | 499.13 | 251.74 | 247.39 | 0.00 | 0.00 |
February | 724.93 | 614.52 | 595.46 | 274.89 | 320.57 | 0.00 | 0.00 |
March | 840.58 | 630.67 | 682.56 | 301.98 | 380.59 | 0.00 | 0.00 |
April | 1295.21 | 530.68 | 940.95 | 489.95 | 451.00 | 0.00 | 0.00 |
May | 1233.14 | 483.24 | 924.31 | 426.94 | 497.37 | 0.00 | 0.00 |
June | 1378.43 | 382.61 | 979.20 | 489.58 | 489.62 | 0.00 | 0.00 |
July | 1537.68 | 345.94 | 1036.56 | 554.66 | 481.91 | 0.00 | 0.00 |
August | 1463.52 | 358.31 | 972.50 | 527.05 | 445.45 | 0.00 | 0.00 |
September | 1213.56 | 410.18 | 832.64 | 445.53 | 387.11 | 0.00 | 0.00 |
October | 951.95 | 455.73 | 636.51 | 347.51 | 289.00 | 0.00 | 0.00 |
November | 749.18 | 625.12 | 574.96 | 300.75 | 274.22 | 0.00 | 0.00 |
December | 661.47 | 684.44 | 507.79 | 272.36 | 235.44 | 0.00 | 0.00 |
Annual Sum or Average | 1059.02 | 516.01 | 765.88 | 390.74 | 375.14 | 0.00 | 0.00 |
Minimum of Months | 639.17 | 345.94 | 499.13 | 251.74 | 235.44 | 0.00 | 0.00 |
Maximum of Months | 1537.68 | 684.44 | 1036.56 | 554.66 | 497.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.35 | 1069.29 | 291.60 | 0.00 | 291.60 | 0.00 | 0.00 |
February | 243.18 | 951.93 | 366.04 | 0.00 | 366.04 | 0.00 | 0.00 |
March | 351.74 | 969.48 | 448.55 | 0.00 | 448.55 | 0.00 | 0.00 |
April | 478.01 | 766.86 | 516.78 | 1.99 | 514.79 | 0.00 | 0.00 |
May | 601.15 | 679.20 | 621.01 | 28.92 | 592.09 | 0.00 | 0.00 |
June | 758.02 | 528.52 | 661.72 | 64.69 | 597.02 | 0.00 | 0.00 |
July | 783.67 | 478.35 | 626.54 | 52.51 | 574.03 | 0.00 | 0.00 |
August | 629.21 | 501.39 | 520.32 | 10.42 | 509.90 | 0.00 | 0.00 |
September | 487.75 | 611.90 | 440.40 | 0.07 | 440.33 | 0.00 | 0.00 |
October | 416.95 | 695.35 | 349.34 | 0.00 | 349.34 | 0.00 | 0.00 |
November | 219.75 | 995.73 | 316.30 | 0.00 | 316.30 | 0.00 | 0.00 |
December | 174.86 | 1085.82 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Annual Sum or Average | 446.26 | 776.96 | 452.87 | 13.29 | 439.58 | 0.00 | 0.00 |
Minimum of Months | 174.86 | 478.35 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Maximum of Months | 783.67 | 1085.82 | 661.72 | 64.69 | 597.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 636.88 | 695.41 | 524.38 | 280.45 | 243.93 | 0.00 | 0.00 |
February | 637.28 | 624.17 | 553.17 | 253.41 | 299.76 | 0.00 | 0.00 |
March | 808.80 | 635.09 | 671.94 | 299.38 | 372.56 | 0.00 | 0.00 |
April | 1168.15 | 522.42 | 859.07 | 430.84 | 428.23 | 0.00 | 0.00 |
May | 1060.18 | 477.62 | 810.72 | 338.33 | 472.39 | 0.00 | 0.00 |
June | 1128.43 | 376.80 | 805.67 | 349.56 | 456.11 | 0.00 | 0.00 |
July | 1367.15 | 346.14 | 912.88 | 453.63 | 459.25 | 0.00 | 0.00 |
August | 1366.78 | 354.56 | 901.55 | 478.87 | 422.68 | 0.00 | 0.00 |
September | 941.34 | 413.22 | 656.40 | 300.79 | 355.61 | 0.00 | 0.00 |
October | 847.96 | 460.34 | 581.03 | 298.63 | 282.40 | 0.00 | 0.00 |
November | 640.22 | 649.23 | 529.68 | 269.10 | 260.58 | 0.00 | 0.00 |
December | 611.81 | 702.89 | 505.30 | 280.75 | 224.55 | 0.00 | 0.00 |
Annual Sum or Average | 936.64 | 520.99 | 693.58 | 336.81 | 356.77 | 0.00 | 0.00 |
Minimum of Months | 611.81 | 346.14 | 505.30 | 253.41 | 224.55 | 0.00 | 0.00 |
Maximum of Months | 1367.15 | 702.89 | 912.88 | 478.87 | 472.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2827.61 | 1094.18 | 1924.33 | 1411.58 | 512.75 | 0.00 | 0.00 |
February | 2111.65 | 971.45 | 1512.42 | 931.57 | 580.85 | 0.00 | 0.00 |
March | 1673.33 | 990.34 | 1205.75 | 582.43 | 623.32 | 0.00 | 0.00 |
April | 1493.92 | 818.44 | 1007.44 | 384.14 | 623.30 | 0.00 | 0.00 |
May | 883.65 | 730.78 | 717.38 | 88.28 | 629.10 | 0.00 | 0.00 |
June | 782.72 | 560.74 | 629.33 | 38.00 | 591.34 | 0.00 | 0.00 |
July | 944.72 | 509.22 | 666.64 | 75.04 | 591.59 | 0.00 | 0.00 |
August | 1382.52 | 542.37 | 856.42 | 270.14 | 586.28 | 0.00 | 0.00 |
September | 1910.90 | 653.86 | 1191.71 | 603.88 | 587.83 | 0.00 | 0.00 |
October | 2421.71 | 730.02 | 1515.57 | 1013.20 | 502.37 | 0.00 | 0.00 |
November | 2698.77 | 1012.38 | 1842.02 | 1300.44 | 541.59 | 0.00 | 0.00 |
December | 3033.83 | 1105.55 | 2055.80 | 1564.73 | 491.07 | 0.00 | 0.00 |
Annual Sum or Average | 1846.31 | 809.15 | 1259.35 | 687.79 | 571.55 | 0.00 | 0.00 |
Minimum of Months | 782.72 | 509.22 | 629.33 | 38.00 | 491.07 | 0.00 | 0.00 |
Maximum of Months | 3033.83 | 1105.55 | 2055.80 | 1564.73 | 629.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 637.76 | 730.80 | 499.12 | 251.73 | 247.39 | 0.00 | 0.00 |
February | 729.95 | 654.83 | 595.46 | 274.89 | 320.57 | 0.00 | 0.00 |
March | 850.70 | 664.15 | 682.55 | 301.97 | 380.58 | 0.00 | 0.00 |
April | 1312.54 | 555.10 | 940.94 | 489.94 | 450.99 | 0.00 | 0.00 |
May | 1250.26 | 505.81 | 924.30 | 426.93 | 497.37 | 0.00 | 0.00 |
June | 1401.07 | 393.99 | 979.19 | 489.57 | 489.62 | 0.00 | 0.00 |
July | 1557.31 | 359.94 | 1036.55 | 554.65 | 481.90 | 0.00 | 0.00 |
August | 1481.21 | 374.48 | 972.49 | 527.05 | 445.44 | 0.00 | 0.00 |
September | 1225.63 | 435.27 | 832.63 | 445.53 | 387.10 | 0.00 | 0.00 |
October | 957.36 | 487.36 | 636.51 | 347.50 | 289.00 | 0.00 | 0.00 |
November | 747.11 | 680.69 | 574.96 | 300.74 | 274.21 | 0.00 | 0.00 |
December | 658.74 | 742.22 | 507.78 | 272.35 | 235.43 | 0.00 | 0.00 |
Annual Sum or Average | 1069.10 | 548.20 | 765.87 | 390.73 | 375.14 | 0.00 | 0.00 |
Minimum of Months | 637.76 | 359.94 | 499.12 | 251.73 | 235.43 | 0.00 | 0.00 |
Maximum of Months | 1557.31 | 742.22 | 1036.55 | 554.65 | 497.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.96 | 1090.72 | 291.61 | 0.00 | 291.61 | 0.00 | 0.00 |
February | 221.26 | 992.04 | 366.04 | 0.00 | 366.04 | 0.00 | 0.00 |
March | 323.39 | 1011.32 | 448.56 | 0.00 | 448.56 | 0.00 | 0.00 |
April | 446.70 | 807.23 | 516.79 | 1.99 | 514.80 | 0.00 | 0.00 |
May | 568.79 | 707.15 | 621.02 | 28.92 | 592.10 | 0.00 | 0.00 |
June | 725.00 | 555.35 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
July | 759.18 | 498.07 | 626.55 | 52.52 | 574.04 | 0.00 | 0.00 |
August | 608.62 | 523.71 | 520.33 | 10.42 | 509.91 | 0.00 | 0.00 |
September | 471.37 | 633.60 | 440.41 | 0.07 | 440.34 | 0.00 | 0.00 |
October | 405.82 | 710.63 | 349.34 | 0.00 | 349.34 | 0.00 | 0.00 |
November | 209.05 | 1012.04 | 316.31 | 0.00 | 316.31 | 0.00 | 0.00 |
December | 163.77 | 1109.65 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Annual Sum or Average | 425.23 | 803.32 | 452.88 | 13.29 | 439.59 | 0.00 | 0.00 |
Minimum of Months | 163.77 | 498.07 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Maximum of Months | 759.18 | 1109.65 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 627.84 | 690.47 | 524.39 | 280.46 | 243.94 | 0.00 | 0.00 |
February | 620.66 | 632.91 | 553.18 | 253.42 | 299.76 | 0.00 | 0.00 |
March | 789.35 | 644.79 | 671.95 | 299.39 | 372.57 | 0.00 | 0.00 |
April | 1147.87 | 528.56 | 859.08 | 430.85 | 428.24 | 0.00 | 0.00 |
May | 1039.53 | 484.09 | 810.73 | 338.34 | 472.39 | 0.00 | 0.00 |
June | 1107.21 | 386.72 | 805.68 | 349.57 | 456.11 | 0.00 | 0.00 |
July | 1350.97 | 348.21 | 912.90 | 453.64 | 459.25 | 0.00 | 0.00 |
August | 1351.72 | 355.56 | 901.56 | 478.88 | 422.68 | 0.00 | 0.00 |
September | 928.52 | 415.33 | 656.41 | 300.79 | 355.62 | 0.00 | 0.00 |
October | 837.27 | 458.17 | 581.04 | 298.64 | 282.40 | 0.00 | 0.00 |
November | 631.40 | 643.51 | 529.69 | 269.10 | 260.58 | 0.00 | 0.00 |
December | 602.45 | 699.82 | 505.31 | 280.76 | 224.56 | 0.00 | 0.00 |
Annual Sum or Average | 921.65 | 523.45 | 693.59 | 336.82 | 356.77 | 0.00 | 0.00 |
Minimum of Months | 602.45 | 348.21 | 505.31 | 253.42 | 224.56 | 0.00 | 0.00 |
Maximum of Months | 1351.72 | 699.82 | 912.90 | 478.88 | 472.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2812.16 | 1057.29 | 1924.40 | 1411.64 | 512.77 | 0.00 | 0.00 |
February | 2080.27 | 969.55 | 1512.48 | 931.61 | 580.87 | 0.00 | 0.00 |
March | 1634.85 | 1011.79 | 1205.80 | 582.46 | 623.34 | 0.00 | 0.00 |
April | 1459.90 | 846.27 | 1007.47 | 384.16 | 623.31 | 0.00 | 0.00 |
May | 841.32 | 770.92 | 717.40 | 88.29 | 629.11 | 0.00 | 0.00 |
June | 741.22 | 602.11 | 629.35 | 38.00 | 591.35 | 0.00 | 0.00 |
July | 916.64 | 534.13 | 666.65 | 75.05 | 591.61 | 0.00 | 0.00 |
August | 1358.97 | 557.91 | 856.45 | 270.15 | 586.30 | 0.00 | 0.00 |
September | 1891.45 | 653.62 | 1191.75 | 603.90 | 587.85 | 0.00 | 0.00 |
October | 2407.16 | 710.70 | 1515.63 | 1013.24 | 502.39 | 0.00 | 0.00 |
November | 2679.94 | 980.93 | 1842.09 | 1300.49 | 541.60 | 0.00 | 0.00 |
December | 3016.57 | 1067.22 | 2055.88 | 1564.79 | 491.09 | 0.00 | 0.00 |
Annual Sum or Average | 1819.29 | 812.72 | 1259.39 | 687.82 | 571.57 | 0.00 | 0.00 |
Minimum of Months | 741.22 | 534.13 | 629.35 | 38.00 | 491.09 | 0.00 | 0.00 |
Maximum of Months | 3016.57 | 1067.22 | 2055.88 | 1564.79 | 629.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 629.12 | 726.92 | 499.13 | 251.74 | 247.39 | 0.00 | 0.00 |
February | 714.87 | 661.40 | 595.46 | 274.89 | 320.57 | 0.00 | 0.00 |
March | 832.27 | 672.21 | 682.56 | 301.98 | 380.59 | 0.00 | 0.00 |
April | 1293.70 | 558.39 | 940.95 | 489.95 | 451.00 | 0.00 | 0.00 |
May | 1231.64 | 507.99 | 924.31 | 426.94 | 497.37 | 0.00 | 0.00 |
June | 1381.28 | 399.07 | 979.20 | 489.58 | 489.62 | 0.00 | 0.00 |
July | 1542.78 | 359.26 | 1036.56 | 554.66 | 481.91 | 0.00 | 0.00 |
August | 1467.68 | 373.48 | 972.50 | 527.05 | 445.45 | 0.00 | 0.00 |
September | 1214.16 | 431.68 | 832.64 | 445.53 | 387.11 | 0.00 | 0.00 |
October | 949.01 | 482.40 | 636.51 | 347.51 | 289.00 | 0.00 | 0.00 |
November | 739.61 | 671.65 | 574.96 | 300.75 | 274.22 | 0.00 | 0.00 |
December | 650.56 | 737.67 | 507.79 | 272.36 | 235.44 | 0.00 | 0.00 |
Annual Sum or Average | 1055.54 | 547.95 | 765.88 | 390.74 | 375.14 | 0.00 | 0.00 |
Minimum of Months | 629.12 | 359.26 | 499.13 | 251.74 | 235.44 | 0.00 | 0.00 |
Maximum of Months | 1542.78 | 737.67 | 1036.56 | 554.66 | 497.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.541465E+09 | 0.271150E+10 | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.00 | 0.00 |
February | 0.577833E+09 | 0.222281E+10 | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.00 | 0.00 |
March | 0.907715E+09 | 0.253928E+10 | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.00 | 0.00 |
April | 0.117479E+10 | 0.198296E+10 | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.00 | 0.00 |
May | 0.154887E+10 | 0.180293E+10 | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.00 | 0.00 |
June | 0.188166E+10 | 0.138065E+10 | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.00 | 0.00 |
July | 0.202388E+10 | 0.128488E+10 | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.00 | 0.00 |
August | 0.162714E+10 | 0.134385E+10 | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.00 | 0.00 |
September | 0.123094E+10 | 0.155640E+10 | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.00 | 0.00 |
October | 0.110745E+10 | 0.179169E+10 | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.00 | 0.00 |
November | 0.587005E+09 | 0.243278E+10 | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.00 | 0.00 |
December | 0.487712E+09 | 0.274599E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136965E+11 | 0.237957E+11 | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.487712E+09 | 0.128488E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Maximum of Months | 0.202388E+10 | 0.274599E+10 | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172905E+10 | 0.172609E+10 | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.00 | 0.00 |
February | 0.154118E+10 | 0.142633E+10 | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.00 | 0.00 |
March | 0.215350E+10 | 0.162685E+10 | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.00 | 0.00 |
April | 0.299351E+10 | 0.130688E+10 | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.00 | 0.00 |
May | 0.280465E+10 | 0.123966E+10 | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.00 | 0.00 |
June | 0.287848E+10 | 0.964543E+09 | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.00 | 0.00 |
July | 0.361839E+10 | 0.901253E+09 | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.00 | 0.00 |
August | 0.362344E+10 | 0.915923E+09 | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.00 | 0.00 |
September | 0.241862E+10 | 0.102371E+10 | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.00 | 0.00 |
October | 0.226351E+10 | 0.116232E+10 | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.00 | 0.00 |
November | 0.167851E+10 | 0.156001E+10 | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.00 | 0.00 |
December | 0.166463E+10 | 0.174436E+10 | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293675E+11 | 0.155979E+11 | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154118E+10 | 0.901253E+09 | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.00 | 0.00 |
Maximum of Months | 0.362344E+10 | 0.174436E+10 | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.757703E+10 | 0.265692E+10 | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.00 | 0.00 |
February | 0.506947E+10 | 0.219039E+10 | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.00 | 0.00 |
March | 0.441428E+10 | 0.255094E+10 | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.00 | 0.00 |
April | 0.379272E+10 | 0.208735E+10 | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.00 | 0.00 |
May | 0.226644E+10 | 0.196449E+10 | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.00 | 0.00 |
June | 0.192131E+10 | 0.149717E+10 | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.00 | 0.00 |
July | 0.244424E+10 | 0.137968E+10 | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.00 | 0.00 |
August | 0.362930E+10 | 0.143463E+10 | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.00 | 0.00 |
September | 0.490210E+10 | 0.161303E+10 | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.00 | 0.00 |
October | 0.645920E+10 | 0.180692E+10 | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.00 | 0.00 |
November | 0.698414E+10 | 0.238816E+10 | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.00 | 0.00 |
December | 0.812744E+10 | 0.267964E+10 | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.575877E+11 | 0.242493E+11 | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192131E+10 | 0.137968E+10 | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.00 | 0.00 |
Maximum of Months | 0.812744E+10 | 0.267964E+10 | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171195E+10 | 0.181201E+10 | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.00 | 0.00 |
February | 0.175374E+10 | 0.148664E+10 | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.00 | 0.00 |
March | 0.225140E+10 | 0.168920E+10 | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.00 | 0.00 |
April | 0.335719E+10 | 0.137551E+10 | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.00 | 0.00 |
May | 0.330284E+10 | 0.129431E+10 | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.00 | 0.00 |
June | 0.357288E+10 | 0.991714E+09 | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.00 | 0.00 |
July | 0.411852E+10 | 0.926560E+09 | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.00 | 0.00 |
August | 0.391989E+10 | 0.959693E+09 | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.00 | 0.00 |
September | 0.314555E+10 | 0.106319E+10 | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.00 | 0.00 |
October | 0.254971E+10 | 0.122063E+10 | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.00 | 0.00 |
November | 0.194188E+10 | 0.162032E+10 | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.00 | 0.00 |
December | 0.177168E+10 | 0.183321E+10 | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333972E+11 | 0.162730E+11 | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.171195E+10 | 0.926560E+09 | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.411852E+10 | 0.183321E+10 | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525915E+09 | 0.286398E+10 | 0.781025E+09 | 0.00 | 0.781025E+09 | 0.00 | 0.00 |
February | 0.588296E+09 | 0.230291E+10 | 0.885517E+09 | 0.00 | 0.885517E+09 | 0.00 | 0.00 |
March | 0.942090E+09 | 0.259667E+10 | 0.120140E+10 | 0.00 | 0.120140E+10 | 0.00 | 0.00 |
April | 0.123901E+10 | 0.198771E+10 | 0.133950E+10 | 5155482.18 | 0.133435E+10 | 0.00 | 0.00 |
May | 0.161011E+10 | 0.181917E+10 | 0.166331E+10 | 77451885.80 | 0.158585E+10 | 0.00 | 0.00 |
June | 0.196479E+10 | 0.136992E+10 | 0.171517E+10 | 0.167685E+09 | 0.154748E+10 | 0.00 | 0.00 |
July | 0.209898E+10 | 0.128120E+10 | 0.167813E+10 | 0.140653E+09 | 0.153747E+10 | 0.00 | 0.00 |
August | 0.168527E+10 | 0.134293E+10 | 0.139363E+10 | 27905723.97 | 0.136572E+10 | 0.00 | 0.00 |
September | 0.126425E+10 | 0.158603E+10 | 0.114151E+10 | 178917.66 | 0.114133E+10 | 0.00 | 0.00 |
October | 0.111676E+10 | 0.186242E+10 | 0.935668E+09 | 0.00 | 0.935668E+09 | 0.00 | 0.00 |
November | 0.569584E+09 | 0.258093E+10 | 0.819851E+09 | 0.00 | 0.819851E+09 | 0.00 | 0.00 |
December | 0.468332E+09 | 0.290826E+10 | 0.727067E+09 | 0.00 | 0.727067E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140734E+11 | 0.245021E+11 | 0.142818E+11 | 0.419030E+09 | 0.138627E+11 | 0.00 | 0.00 |
Minimum of Months | 0.468332E+09 | 0.128120E+10 | 0.727067E+09 | 0.00 | 0.727067E+09 | 0.00 | 0.00 |
Maximum of Months | 0.209898E+10 | 0.290826E+10 | 0.171517E+10 | 0.167685E+09 | 0.158585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170581E+10 | 0.186258E+10 | 0.140451E+10 | 0.751164E+09 | 0.653349E+09 | 0.00 | 0.00 |
February | 0.154171E+10 | 0.151000E+10 | 0.133823E+10 | 0.613053E+09 | 0.725181E+09 | 0.00 | 0.00 |
March | 0.216628E+10 | 0.170101E+10 | 0.179973E+10 | 0.801859E+09 | 0.997871E+09 | 0.00 | 0.00 |
April | 0.302783E+10 | 0.135412E+10 | 0.222671E+10 | 0.111674E+10 | 0.110998E+10 | 0.00 | 0.00 |
May | 0.283958E+10 | 0.127925E+10 | 0.217143E+10 | 0.906183E+09 | 0.126524E+10 | 0.00 | 0.00 |
June | 0.292489E+10 | 0.976654E+09 | 0.208829E+10 | 0.906070E+09 | 0.118223E+10 | 0.00 | 0.00 |
July | 0.366177E+10 | 0.927108E+09 | 0.244507E+10 | 0.121501E+10 | 0.123006E+10 | 0.00 | 0.00 |
August | 0.366079E+10 | 0.949662E+09 | 0.241470E+10 | 0.128260E+10 | 0.113210E+10 | 0.00 | 0.00 |
September | 0.243996E+10 | 0.107106E+10 | 0.170138E+10 | 0.779635E+09 | 0.921749E+09 | 0.00 | 0.00 |
October | 0.227117E+10 | 0.123299E+10 | 0.155624E+10 | 0.799862E+09 | 0.756374E+09 | 0.00 | 0.00 |
November | 0.165946E+10 | 0.168280E+10 | 0.137293E+10 | 0.697501E+09 | 0.675426E+09 | 0.00 | 0.00 |
December | 0.163868E+10 | 0.188263E+10 | 0.135341E+10 | 0.751963E+09 | 0.601442E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.295379E+11 | 0.164299E+11 | 0.218726E+11 | 0.106216E+11 | 0.112510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154171E+10 | 0.927108E+09 | 0.133823E+10 | 0.613053E+09 | 0.601442E+09 | 0.00 | 0.00 |
Maximum of Months | 0.366177E+10 | 0.188263E+10 | 0.244507E+10 | 0.128260E+10 | 0.126524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.757347E+10 | 0.293064E+10 | 0.515412E+10 | 0.378078E+10 | 0.137335E+10 | 0.00 | 0.00 |
February | 0.510851E+10 | 0.235014E+10 | 0.365885E+10 | 0.225365E+10 | 0.140520E+10 | 0.00 | 0.00 |
March | 0.448185E+10 | 0.265254E+10 | 0.322949E+10 | 0.155999E+10 | 0.166950E+10 | 0.00 | 0.00 |
April | 0.387223E+10 | 0.212141E+10 | 0.261129E+10 | 0.995700E+09 | 0.161559E+10 | 0.00 | 0.00 |
May | 0.236676E+10 | 0.195732E+10 | 0.192142E+10 | 0.236455E+09 | 0.168497E+10 | 0.00 | 0.00 |
June | 0.202881E+10 | 0.145344E+10 | 0.163123E+10 | 98486347.79 | 0.153274E+10 | 0.00 | 0.00 |
July | 0.253034E+10 | 0.136389E+10 | 0.178552E+10 | 0.200995E+09 | 0.158452E+10 | 0.00 | 0.00 |
August | 0.370294E+10 | 0.145269E+10 | 0.229385E+10 | 0.723543E+09 | 0.157030E+10 | 0.00 | 0.00 |
September | 0.495305E+10 | 0.169482E+10 | 0.308891E+10 | 0.156525E+10 | 0.152366E+10 | 0.00 | 0.00 |
October | 0.648631E+10 | 0.195529E+10 | 0.405931E+10 | 0.271375E+10 | 0.134556E+10 | 0.00 | 0.00 |
November | 0.699522E+10 | 0.262408E+10 | 0.477452E+10 | 0.337073E+10 | 0.140379E+10 | 0.00 | 0.00 |
December | 0.812582E+10 | 0.296110E+10 | 0.550625E+10 | 0.419097E+10 | 0.131528E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.582253E+11 | 0.255174E+11 | 0.397148E+11 | 0.216903E+11 | 0.180245E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202881E+10 | 0.136389E+10 | 0.163123E+10 | 98486347.79 | 0.131528E+10 | 0.00 | 0.00 |
Maximum of Months | 0.812582E+10 | 0.296110E+10 | 0.550625E+10 | 0.419097E+10 | 0.168497E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170818E+10 | 0.195737E+10 | 0.133685E+10 | 0.674246E+09 | 0.662607E+09 | 0.00 | 0.00 |
February | 0.176589E+10 | 0.158418E+10 | 0.144053E+10 | 0.665014E+09 | 0.775516E+09 | 0.00 | 0.00 |
March | 0.227853E+10 | 0.177886E+10 | 0.182815E+10 | 0.808800E+09 | 0.101935E+10 | 0.00 | 0.00 |
April | 0.340211E+10 | 0.143882E+10 | 0.243891E+10 | 0.126993E+10 | 0.116898E+10 | 0.00 | 0.00 |
May | 0.334869E+10 | 0.135475E+10 | 0.247563E+10 | 0.114349E+10 | 0.133215E+10 | 0.00 | 0.00 |
June | 0.363157E+10 | 0.102121E+10 | 0.253806E+10 | 0.126898E+10 | 0.126908E+10 | 0.00 | 0.00 |
July | 0.417109E+10 | 0.964066E+09 | 0.277630E+10 | 0.148557E+10 | 0.129073E+10 | 0.00 | 0.00 |
August | 0.396727E+10 | 0.100300E+10 | 0.260471E+10 | 0.141164E+10 | 0.119307E+10 | 0.00 | 0.00 |
September | 0.317683E+10 | 0.112821E+10 | 0.215817E+10 | 0.115480E+10 | 0.100337E+10 | 0.00 | 0.00 |
October | 0.256419E+10 | 0.130536E+10 | 0.170482E+10 | 0.930755E+09 | 0.774063E+09 | 0.00 | 0.00 |
November | 0.193652E+10 | 0.176435E+10 | 0.149028E+10 | 0.779521E+09 | 0.710763E+09 | 0.00 | 0.00 |
December | 0.176437E+10 | 0.198796E+10 | 0.136005E+10 | 0.729465E+09 | 0.630585E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.337152E+11 | 0.172881E+11 | 0.241525E+11 | 0.123222E+11 | 0.118303E+11 | 0.00 | 0.00 |
Minimum of Months | 0.170818E+10 | 0.964066E+09 | 0.133685E+10 | 0.665014E+09 | 0.630585E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417109E+10 | 0.198796E+10 | 0.277630E+10 | 0.148557E+10 | 0.133215E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.495385E+09 | 0.292138E+10 | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.00 | 0.00 |
February | 0.535284E+09 | 0.239994E+10 | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.00 | 0.00 |
March | 0.866165E+09 | 0.270871E+10 | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.00 | 0.00 |
April | 0.115784E+10 | 0.209234E+10 | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.00 | 0.00 |
May | 0.152346E+10 | 0.189403E+10 | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.00 | 0.00 |
June | 0.187920E+10 | 0.143947E+10 | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.00 | 0.00 |
July | 0.203340E+10 | 0.133402E+10 | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.00 | 0.00 |
August | 0.163014E+10 | 0.140272E+10 | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.00 | 0.00 |
September | 0.122180E+10 | 0.164230E+10 | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.00 | 0.00 |
October | 0.108694E+10 | 0.190335E+10 | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.00 | 0.00 |
November | 0.541863E+09 | 0.262322E+10 | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.00 | 0.00 |
December | 0.438646E+09 | 0.297209E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134101E+11 | 0.253336E+11 | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.438646E+09 | 0.133402E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Maximum of Months | 0.203340E+10 | 0.297209E+10 | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168161E+10 | 0.184935E+10 | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.00 | 0.00 |
February | 0.150149E+10 | 0.153114E+10 | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.00 | 0.00 |
March | 0.211418E+10 | 0.172700E+10 | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.00 | 0.00 |
April | 0.297527E+10 | 0.137002E+10 | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.00 | 0.00 |
May | 0.278427E+10 | 0.129658E+10 | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.00 | 0.00 |
June | 0.286990E+10 | 0.100237E+10 | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.00 | 0.00 |
July | 0.361843E+10 | 0.932648E+09 | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.00 | 0.00 |
August | 0.362046E+10 | 0.952319E+09 | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.00 | 0.00 |
September | 0.240672E+10 | 0.107654E+10 | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.00 | 0.00 |
October | 0.224255E+10 | 0.122717E+10 | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.00 | 0.00 |
November | 0.163659E+10 | 0.166797E+10 | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.00 | 0.00 |
December | 0.161360E+10 | 0.187440E+10 | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290651E+11 | 0.165075E+11 | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.150149E+10 | 0.932648E+09 | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.00 | 0.00 |
Maximum of Months | 0.362046E+10 | 0.187440E+10 | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.753209E+10 | 0.283184E+10 | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.00 | 0.00 |
February | 0.503258E+10 | 0.234553E+10 | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.00 | 0.00 |
March | 0.437879E+10 | 0.270999E+10 | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.00 | 0.00 |
April | 0.378406E+10 | 0.219354E+10 | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.00 | 0.00 |
May | 0.225340E+10 | 0.206482E+10 | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.00 | 0.00 |
June | 0.192125E+10 | 0.156068E+10 | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.00 | 0.00 |
July | 0.245513E+10 | 0.143062E+10 | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.00 | 0.00 |
August | 0.363986E+10 | 0.149431E+10 | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.00 | 0.00 |
September | 0.490263E+10 | 0.169417E+10 | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.00 | 0.00 |
October | 0.644735E+10 | 0.190355E+10 | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.00 | 0.00 |
November | 0.694640E+10 | 0.254257E+10 | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.00 | 0.00 |
December | 0.807959E+10 | 0.285845E+10 | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.573731E+11 | 0.256301E+11 | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192125E+10 | 0.143062E+10 | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.00 | 0.00 |
Maximum of Months | 0.807959E+10 | 0.285845E+10 | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168504E+10 | 0.194699E+10 | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.00 | 0.00 |
February | 0.172941E+10 | 0.160007E+10 | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.00 | 0.00 |
March | 0.222915E+10 | 0.180044E+10 | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.00 | 0.00 |
April | 0.335328E+10 | 0.144736E+10 | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.00 | 0.00 |
May | 0.329882E+10 | 0.136060E+10 | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.00 | 0.00 |
June | 0.358028E+10 | 0.103438E+10 | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.00 | 0.00 |
July | 0.413219E+10 | 0.962254E+09 | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.00 | 0.00 |
August | 0.393103E+10 | 0.100032E+10 | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.00 | 0.00 |
September | 0.314710E+10 | 0.111891E+10 | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.00 | 0.00 |
October | 0.254184E+10 | 0.129207E+10 | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.00 | 0.00 |
November | 0.191707E+10 | 0.174091E+10 | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.00 | 0.00 |
December | 0.174245E+10 | 0.197578E+10 | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.332876E+11 | 0.172801E+11 | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168504E+10 | 0.962254E+09 | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.413219E+10 | 0.197578E+10 | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.462660E+10 | -0.392472E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -701878838.3 | 58.98 | 0.00 | 0.00 |
February | 0.420408E+10 | -0.357110E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -632984826.0 | 58.98 | 0.00 | 0.00 |
March | 0.488221E+10 | -0.418133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -700886596.4 | 58.98 | 0.00 | 0.00 |
April | 0.435858E+10 | -0.368408E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -674500256.9 | 58.98 | 0.00 | 0.00 |
May | 0.454654E+10 | -0.385090E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695635418.2 | 58.98 | 0.00 | 0.00 |
June | 0.441048E+10 | -0.373840E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -672078031.3 | 58.98 | 0.00 | 0.00 |
July | 0.416195E+10 | -0.346942E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692537212.9 | 58.98 | 0.00 | 0.00 |
August | 0.452470E+10 | -0.383124E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693464137.7 | 58.98 | 0.00 | 0.00 |
September | 0.416175E+10 | -0.349143E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670322281.4 | 58.98 | 0.00 | 0.00 |
October | 0.438047E+10 | -0.368781E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692661139.3 | 58.98 | 0.00 | 0.00 |
November | 0.439603E+10 | -0.372250E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -673531600.4 | 58.98 | 0.00 | 0.00 |
December | 0.446614E+10 | -0.376659E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -699553687.4 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.531196E+11 | -0.449195E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.820003E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.416175E+10 | -0.418133E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -701878838.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.488221E+10 | -0.346942E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -632984826.0 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7832.42 | 37.26 | 285.00 | 280.00 | 1727.28 | 25.87 | 168.33 | 265.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6938.87 | 35.51 | 275.33 | 274.67 | 1228.26 | 21.05 | 138.17 | 244.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:00 | 2038.98 | 18.81 | 11.17 | 315.00 | 998.96 | 20.30 | 148.17 | 286.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1322.42 | 18.00 | 0.00 | 332.50 | 812.61 | 20.19 | 92.50 | 296.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1129.36 | 17.83 | 0.00 | 364.00 | 654.31 | 19.99 | 59.67 | 320.50 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 998.22 | 17.49 | 0.00 | 355.17 | 595.83 | 19.68 | 20.50 | 308.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 1005.78 | 17.53 | 0.00 | 364.50 | 620.46 | 19.75 | 24.17 | 328.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1133.72 | 17.65 | 0.00 | 353.67 | 710.58 | 19.84 | 48.00 | 315.67 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1617.09 | 18.45 | 11.00 | 308.67 | 947.17 | 20.19 | 87.67 | 277.50 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3495.50 | 24.53 | 115.83 | 303.00 | 1184.76 | 20.85 | 83.17 | 276.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7573.72 | 36.89 | 292.67 | 279.17 | 1551.51 | 25.54 | 179.17 | 270.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:10 | 7695.12 | 37.38 | 286.17 | 281.00 | 2197.90 | 28.82 | 181.17 | 271.50 |
Annual Sum or Average | 4065.67 | 0.51 | 3247.95 | 23.84 | 1277.17 | 3811.33 | 1051.64 | 21.60 | 1230.67 | 3460.50 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 998.22 | 17.49 | 0.00 | 274.67 | 595.83 | 19.68 | 20.50 | 244.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7832.42 | 37.38 | 292.67 | 364.50 | 2197.90 | 28.82 | 181.17 | 328.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-07:19 | 1711.29 | 21.62 | 85.00 | 264.67 | 876.70 | 22.17 | 61.17 | 222.50 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1838.67 | 20.32 | 70.83 | 266.83 | 986.49 | 22.44 | 55.83 | 220.50 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2279.31 | 21.60 | 106.50 | 315.83 | 1255.39 | 22.50 | 77.67 | 274.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2266.40 | 19.28 | 77.33 | 336.50 | 1230.04 | 21.78 | 65.17 | 305.00 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2224.65 | 20.06 | 99.50 | 376.33 | 1216.95 | 21.33 | 69.33 | 328.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2214.66 | 19.23 | 88.83 | 367.00 | 947.49 | 19.38 | 36.33 | 321.67 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:19 | 2443.17 | 19.72 | 99.67 | 375.83 | 1295.37 | 20.90 | 68.67 | 337.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:49 | 2459.74 | 20.45 | 102.17 | 362.17 | 1261.43 | 21.46 | 69.67 | 324.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2556.09 | 20.46 | 92.83 | 311.00 | 977.13 | 20.47 | 43.83 | 272.17 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2330.35 | 20.93 | 88.83 | 281.83 | 963.48 | 20.41 | 42.67 | 233.67 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1948.07 | 21.87 | 95.17 | 262.50 | 1058.65 | 22.48 | 68.50 | 228.33 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1689.01 | 21.24 | 86.17 | 263.83 | 874.95 | 21.70 | 63.33 | 220.00 |
Annual Sum or Average | 4065.67 | 0.51 | 2187.88 | 20.49 | 1092.83 | 3784.33 | 1093.28 | 21.37 | 722.17 | 3288.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1689.01 | 19.23 | 70.83 | 262.50 | 874.95 | 19.38 | 36.33 | 220.00 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2556.09 | 21.87 | 106.50 | 376.33 | 1295.37 | 22.50 | 77.67 | 337.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 524.21 | 15.16 | 0.00 | 232.67 | 341.95 | 17.77 | 0.00 | 151.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 628.73 | 16.00 | 0.00 | 246.67 | 387.82 | 18.32 | 0.00 | 171.83 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-07:00 | 737.31 | 16.41 | 0.00 | 305.50 | 442.33 | 18.54 | 0.00 | 248.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 816.63 | 17.64 | 0.00 | 335.83 | 521.05 | 19.83 | 6.00 | 295.83 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:30 | 1025.83 | 18.30 | 0.00 | 381.17 | 599.53 | 20.48 | 72.00 | 352.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1084.76 | 20.13 | 42.50 | 374.17 | 648.57 | 22.22 | 125.50 | 341.00 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1015.34 | 20.05 | 45.17 | 384.33 | 599.68 | 20.58 | 100.83 | 361.00 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 838.05 | 17.74 | 0.00 | 364.67 | 537.53 | 19.92 | 29.67 | 337.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 729.23 | 16.91 | 0.00 | 303.67 | 468.48 | 19.17 | 0.00 | 257.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 556.60 | 15.40 | 0.00 | 258.00 | 365.40 | 17.84 | 0.00 | 170.67 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:40 | 532.80 | 14.81 | 0.00 | 236.67 | 344.35 | 17.28 | 0.00 | 159.83 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:20 | 476.51 | 14.42 | 0.00 | 225.67 | 316.69 | 17.10 | 0.00 | 130.17 |
Annual Sum or Average | 4065.67 | 0.52 | 771.63 | 17.13 | 87.67 | 3649.00 | 477.90 | 19.25 | 334.00 | 2975.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 476.51 | 14.42 | 0.00 | 225.67 | 316.69 | 17.10 | 0.00 | 130.17 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 1084.76 | 20.13 | 45.17 | 384.33 | 648.57 | 22.22 | 125.50 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:39 | 2224.16 | 22.52 | 105.17 | 251.33 | 841.22 | 21.22 | 50.50 | 209.33 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:39 | 1998.84 | 20.27 | 73.50 | 252.83 | 1100.46 | 22.51 | 60.00 | 213.67 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-08:09 | 2273.72 | 21.00 | 100.17 | 309.17 | 1235.50 | 21.93 | 71.67 | 266.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 3145.38 | 19.47 | 82.33 | 330.33 | 1189.84 | 17.70 | 0.00 | 297.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2922.63 | 17.04 | 52.50 | 365.17 | 1199.28 | 17.85 | 0.00 | 328.17 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2493.51 | 14.27 | 0.00 | 360.67 | 1359.22 | 17.81 | 0.00 | 323.17 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:30 | 2631.09 | 14.38 | 5.67 | 369.83 | 1403.31 | 17.72 | 0.00 | 341.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 3238.01 | 19.13 | 88.17 | 352.83 | 1327.46 | 17.90 | 7.00 | 323.67 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:19 | 2798.59 | 21.85 | 101.83 | 303.83 | 1499.81 | 22.47 | 71.83 | 269.33 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2078.48 | 20.51 | 81.83 | 284.17 | 1093.65 | 21.08 | 52.50 | 237.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-07:49 | 2171.83 | 22.40 | 104.33 | 253.50 | 1194.15 | 22.95 | 75.17 | 213.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:20 | 1973.67 | 22.38 | 104.67 | 245.50 | 1096.13 | 22.96 | 80.17 | 197.17 |
Annual Sum or Average | 4065.67 | 0.51 | 2538.89 | 19.30 | 900.17 | 3679.17 | 1225.34 | 20.09 | 468.83 | 3220.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1973.67 | 14.27 | 0.00 | 245.50 | 841.22 | 17.70 | 0.00 | 197.17 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3238.01 | 22.52 | 105.17 | 369.83 | 1499.81 | 22.96 | 80.17 | 341.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7679.41 | 36.96 | 284.83 | 279.00 | 1605.83 | 23.48 | 97.33 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 6821.35 | 35.28 | 275.33 | 274.00 | 1176.54 | 21.68 | 61.00 | 251.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 1950.24 | 15.05 | 11.17 | 314.00 | 937.43 | 17.95 | 5.33 | 282.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1260.39 | 14.39 | 0.00 | 331.50 | 769.02 | 17.96 | 0.00 | 293.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1085.92 | 14.28 | 0.00 | 361.33 | 627.65 | 17.76 | 0.00 | 315.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 962.08 | 14.02 | 0.00 | 353.50 | 574.94 | 17.53 | 0.00 | 303.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 967.85 | 14.17 | 0.00 | 362.50 | 598.20 | 17.71 | 0.00 | 323.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1083.49 | 14.22 | 0.00 | 351.33 | 676.93 | 17.76 | 0.00 | 311.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1536.74 | 14.77 | 11.00 | 307.00 | 886.05 | 17.80 | 2.00 | 274.67 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3387.63 | 21.86 | 115.67 | 302.50 | 1093.29 | 18.18 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7433.59 | 36.65 | 292.67 | 278.50 | 1440.58 | 23.10 | 92.67 | 269.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7537.30 | 37.03 | 285.67 | 279.33 | 2069.65 | 26.75 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.51 | 3163.52 | 21.30 | 1276.33 | 3794.50 | 991.19 | 19.53 | 415.33 | 3432.17 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 962.08 | 14.02 | 0.00 | 274.00 | 574.94 | 17.53 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7679.41 | 37.03 | 292.67 | 362.50 | 2069.65 | 26.75 | 143.00 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-07:19 | 1660.04 | 21.12 | 85.00 | 263.50 | 836.82 | 21.95 | 56.83 | 218.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-06:00 | 1784.26 | 19.82 | 70.83 | 264.83 | 943.46 | 22.23 | 54.83 | 216.33 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:49 | 2223.24 | 21.15 | 106.50 | 313.33 | 1210.03 | 22.31 | 77.67 | 269.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2196.50 | 18.79 | 77.33 | 334.67 | 1174.99 | 21.60 | 65.17 | 301.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2159.87 | 19.59 | 99.33 | 375.33 | 1170.45 | 21.15 | 69.33 | 323.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2157.25 | 18.76 | 88.83 | 363.83 | 902.00 | 19.20 | 36.33 | 316.33 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:19 | 2374.83 | 19.24 | 99.17 | 372.83 | 1243.39 | 20.73 | 68.67 | 334.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2342.57 | 18.65 | 85.67 | 357.67 | 1207.00 | 21.29 | 69.67 | 322.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2502.44 | 19.99 | 92.83 | 309.50 | 932.73 | 20.27 | 43.83 | 268.33 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2248.50 | 20.00 | 85.00 | 278.50 | 921.03 | 20.19 | 42.67 | 229.83 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1831.29 | 19.64 | 79.50 | 258.33 | 1018.21 | 22.27 | 66.33 | 223.83 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-07:10 | 1640.23 | 20.74 | 86.17 | 261.67 | 835.00 | 21.47 | 58.83 | 215.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2117.35 | 19.72 | 1056.17 | 3754.00 | 1047.01 | 21.17 | 710.17 | 3239.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1640.23 | 18.65 | 70.83 | 258.33 | 835.00 | 19.20 | 36.33 | 215.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2502.44 | 21.15 | 106.50 | 375.33 | 1243.39 | 22.31 | 77.67 | 334.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-08:50 | 504.49 | 11.55 | 0.00 | 228.50 | 331.81 | 15.46 | 0.00 | 140.33 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 606.04 | 12.52 | 0.00 | 244.00 | 375.70 | 16.14 | 0.00 | 163.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:09 | 711.77 | 13.06 | 0.00 | 303.17 | 428.44 | 16.49 | 0.00 | 240.83 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 788.81 | 14.36 | 0.00 | 334.83 | 506.71 | 17.95 | 0.00 | 292.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:30 | 990.55 | 14.75 | 0.00 | 380.17 | 579.71 | 18.35 | 0.00 | 348.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1047.42 | 16.94 | 42.50 | 373.67 | 627.25 | 20.21 | 41.17 | 338.67 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 980.48 | 16.99 | 45.17 | 382.67 | 580.49 | 18.56 | 0.00 | 358.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 809.59 | 14.48 | 0.00 | 364.00 | 522.83 | 18.11 | 0.00 | 333.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 704.16 | 13.61 | 0.00 | 301.50 | 455.61 | 17.20 | 0.00 | 252.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 537.86 | 11.96 | 0.00 | 253.50 | 356.01 | 15.72 | 0.00 | 161.50 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-07:49 | 513.14 | 11.39 | 0.00 | 232.33 | 334.19 | 15.08 | 0.00 | 149.50 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:20 | 458.19 | 10.88 | 0.00 | 219.00 | 307.38 | 14.77 | 0.00 | 118.67 |
Annual Sum or Average | 4065.67 | 0.52 | 744.74 | 13.77 | 87.67 | 3617.33 | 463.50 | 17.18 | 41.17 | 2898.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 458.19 | 10.88 | 0.00 | 219.00 | 307.38 | 14.77 | 0.00 | 118.67 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 1047.42 | 16.99 | 45.17 | 382.67 | 627.25 | 20.21 | 41.17 | 358.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2172.20 | 22.13 | 105.17 | 248.50 | 801.37 | 21.11 | 49.33 | 207.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 1938.76 | 19.84 | 73.50 | 251.00 | 1053.72 | 22.40 | 60.00 | 210.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-08:09 | 2215.63 | 20.59 | 100.17 | 307.17 | 1188.40 | 21.81 | 71.67 | 263.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 3069.55 | 19.00 | 82.33 | 329.00 | 1130.42 | 17.54 | 0.00 | 294.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2844.04 | 16.54 | 52.50 | 363.17 | 1144.46 | 17.67 | 0.00 | 323.67 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2420.05 | 13.73 | 0.00 | 359.50 | 1300.74 | 17.62 | 0.00 | 320.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:30 | 2550.16 | 13.86 | 5.67 | 368.00 | 1343.45 | 17.54 | 0.00 | 339.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:40 | 3154.91 | 18.67 | 88.17 | 350.00 | 1267.83 | 17.74 | 7.00 | 321.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:19 | 2728.90 | 21.43 | 101.83 | 302.33 | 1440.28 | 22.35 | 71.83 | 266.83 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2018.18 | 20.08 | 81.83 | 280.67 | 1044.04 | 20.96 | 52.50 | 234.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-07:49 | 2107.96 | 21.74 | 101.83 | 251.83 | 1150.51 | 22.85 | 75.00 | 209.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:30 | 1856.15 | 20.22 | 88.17 | 239.83 | 1056.57 | 22.86 | 79.17 | 193.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2465.55 | 18.70 | 881.17 | 3651.00 | 1173.02 | 19.94 | 466.50 | 3184.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1856.15 | 13.73 | 0.00 | 239.83 | 801.37 | 17.54 | 0.00 | 193.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3154.91 | 22.13 | 105.17 | 368.00 | 1440.28 | 22.86 | 79.17 | 339.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7679.38 | 36.96 | 284.83 | 279.00 | 1605.75 | 23.48 | 97.33 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 6821.27 | 35.28 | 275.33 | 274.00 | 1176.46 | 21.68 | 61.00 | 251.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 1950.15 | 15.05 | 11.17 | 314.00 | 937.36 | 17.95 | 5.33 | 282.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1260.33 | 14.39 | 0.00 | 331.50 | 768.97 | 17.96 | 0.00 | 293.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1085.87 | 14.28 | 0.00 | 361.33 | 627.60 | 17.76 | 0.00 | 315.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 962.04 | 14.02 | 0.00 | 353.50 | 574.90 | 17.53 | 0.00 | 303.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 967.82 | 14.18 | 0.00 | 362.50 | 598.16 | 17.71 | 0.00 | 323.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1083.45 | 14.22 | 0.00 | 351.33 | 676.89 | 17.76 | 0.00 | 311.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1536.68 | 14.78 | 11.00 | 307.00 | 885.99 | 17.80 | 2.00 | 274.67 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3387.56 | 21.86 | 115.67 | 302.50 | 1093.23 | 18.18 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7433.54 | 36.65 | 292.67 | 278.50 | 1440.50 | 23.10 | 92.67 | 269.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7537.29 | 37.03 | 285.67 | 279.33 | 2069.58 | 26.75 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.51 | 3163.47 | 21.30 | 1276.33 | 3794.50 | 991.13 | 19.53 | 415.33 | 3432.17 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 962.04 | 14.02 | 0.00 | 274.00 | 574.90 | 17.53 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7679.38 | 37.03 | 292.67 | 362.50 | 2069.58 | 26.75 | 143.00 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-07:19 | 1660.03 | 21.13 | 85.00 | 263.50 | 836.78 | 21.95 | 56.83 | 218.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-06:00 | 1784.24 | 19.82 | 70.83 | 264.83 | 943.42 | 22.23 | 54.83 | 216.33 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:49 | 2223.19 | 21.15 | 106.50 | 313.33 | 1209.97 | 22.31 | 77.67 | 269.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2196.47 | 18.80 | 77.33 | 334.67 | 1174.94 | 21.60 | 65.17 | 301.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2159.82 | 19.59 | 99.33 | 375.33 | 1170.40 | 21.15 | 69.33 | 323.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2157.21 | 18.76 | 88.83 | 363.83 | 901.95 | 19.20 | 36.33 | 316.33 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:19 | 2374.80 | 19.24 | 99.17 | 372.83 | 1243.34 | 20.73 | 68.67 | 334.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2342.55 | 18.65 | 85.67 | 357.67 | 1206.95 | 21.29 | 69.67 | 322.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2502.41 | 19.99 | 92.83 | 309.50 | 932.68 | 20.27 | 43.83 | 268.33 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2248.49 | 20.00 | 85.00 | 278.50 | 920.99 | 20.19 | 42.67 | 229.83 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1831.28 | 19.64 | 79.50 | 258.33 | 1018.17 | 22.27 | 66.33 | 223.83 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-07:10 | 1640.22 | 20.74 | 86.17 | 261.67 | 834.97 | 21.47 | 58.83 | 215.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2117.32 | 19.72 | 1056.17 | 3754.00 | 1046.96 | 21.17 | 710.17 | 3239.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1640.22 | 18.65 | 70.83 | 258.33 | 834.97 | 19.20 | 36.33 | 215.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2502.41 | 21.15 | 106.50 | 375.33 | 1243.34 | 22.31 | 77.67 | 334.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-08:50 | 504.48 | 11.55 | 0.00 | 228.50 | 331.79 | 15.46 | 0.00 | 140.33 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 606.03 | 12.53 | 0.00 | 244.00 | 375.68 | 16.14 | 0.00 | 163.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:09 | 711.75 | 13.06 | 0.00 | 303.17 | 428.41 | 16.49 | 0.00 | 240.83 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 788.80 | 14.36 | 0.00 | 334.83 | 506.68 | 17.95 | 0.00 | 292.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:30 | 990.52 | 14.75 | 0.00 | 380.17 | 579.67 | 18.35 | 0.00 | 348.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1047.39 | 16.94 | 42.50 | 373.67 | 627.22 | 20.21 | 41.17 | 338.67 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 980.46 | 17.00 | 45.17 | 382.67 | 580.46 | 18.56 | 0.00 | 358.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 809.58 | 14.48 | 0.00 | 364.00 | 522.81 | 18.11 | 0.00 | 333.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 704.14 | 13.62 | 0.00 | 301.50 | 455.59 | 17.20 | 0.00 | 252.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 537.85 | 11.96 | 0.00 | 253.50 | 355.99 | 15.72 | 0.00 | 161.50 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-07:49 | 513.13 | 11.40 | 0.00 | 232.33 | 334.17 | 15.09 | 0.00 | 149.50 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:20 | 458.19 | 10.88 | 0.00 | 219.00 | 307.37 | 14.77 | 0.00 | 118.67 |
Annual Sum or Average | 4065.67 | 0.52 | 744.72 | 13.77 | 87.67 | 3617.33 | 463.47 | 17.18 | 41.17 | 2897.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 458.19 | 10.88 | 0.00 | 219.00 | 307.37 | 14.77 | 0.00 | 118.67 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 1047.39 | 17.00 | 45.17 | 382.67 | 627.22 | 20.21 | 41.17 | 358.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2172.19 | 22.13 | 105.17 | 248.50 | 801.33 | 21.11 | 49.33 | 207.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 1938.74 | 19.84 | 73.50 | 251.00 | 1053.67 | 22.40 | 60.00 | 210.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-08:09 | 2215.59 | 20.60 | 100.17 | 307.17 | 1188.34 | 21.81 | 71.67 | 263.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 3069.53 | 19.00 | 82.33 | 329.00 | 1130.37 | 17.54 | 0.00 | 294.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2843.99 | 16.54 | 52.50 | 363.17 | 1144.40 | 17.67 | 0.00 | 323.67 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2420.01 | 13.73 | 0.00 | 359.50 | 1300.68 | 17.62 | 0.00 | 320.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:30 | 2550.13 | 13.86 | 5.67 | 368.00 | 1343.39 | 17.54 | 0.00 | 339.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:40 | 3154.89 | 18.67 | 88.17 | 350.00 | 1267.78 | 17.74 | 7.00 | 321.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:19 | 2728.87 | 21.43 | 101.83 | 302.33 | 1440.23 | 22.35 | 71.83 | 266.83 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2018.16 | 20.08 | 81.83 | 280.67 | 1044.00 | 20.96 | 52.50 | 234.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-07:49 | 2107.95 | 21.75 | 101.83 | 251.83 | 1150.47 | 22.85 | 75.00 | 209.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:30 | 1856.15 | 20.22 | 88.17 | 239.83 | 1056.53 | 22.86 | 79.17 | 193.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2465.52 | 18.70 | 881.17 | 3651.00 | 1172.97 | 19.94 | 466.50 | 3184.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1856.15 | 13.73 | 0.00 | 239.83 | 801.33 | 17.54 | 0.00 | 193.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3154.89 | 22.13 | 105.17 | 368.00 | 1440.23 | 22.86 | 79.17 | 339.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.469924E+09 | 8252.94 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464520E+09 | 8252.94 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.877338E+09 | 8252.94 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.342539E+09 | 8252.94 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.284792E+09 | 8252.94 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102528E+09 | 6530.94 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3185207.72 | 2098.58 | 27-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5270271.96 | 4034.16 | 28-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28338924.71 | 5799.94 | 20-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84205105.28 | 8252.94 | 12-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203642E+09 | 8252.94 | 03-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387815E+09 | 8252.94 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.325410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3185207.72 | 2098.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.877338E+09 | 8252.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9639867.61 | 5487.00 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 537974.23 | 197.90 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3994326.52 | 5487.00 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14172168.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9639867.61 | 5487.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 78344463.03 | 6770.35 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12239367.84 | 4029.77 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34062532.93 | 6770.77 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3662378.09 | 6654.57 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9289989.55 | 5567.67 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78344463.03 | 6770.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18558665.14 | 5463.42 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 755831.84 | 975.35 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6917876.43 | 5463.42 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1353886.37 | 2569.24 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 443050.96 | 1095.39 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28029310.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18558665.14 | 5463.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3983856.78 | 12359.23 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3983856.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3983856.78 | 12359.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18369414.27 | 9067.95 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 844662.61 | 1322.22 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11831778.79 | 9067.95 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1854182.22 | 4063.78 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 429179.90 | 2861.20 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33329217.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18369414.27 | 9067.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 21391627.09 | 6003.99 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 856449.57 | 968.31 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4371235.63 | 6003.99 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32217.77 | 214.79 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 418352.85 | 1628.55 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27069882.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21391627.09 | 6003.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 77664679.77 | 7588.45 | 11-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5306589.56 | 3869.45 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24983859.37 | 7590.42 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2417325.01 | 5113.81 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 121711.22 | 414.27 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11631960.57 | 7039.73 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 77664679.77 | 7590.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37361781.67 | 5981.02 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2065143.25 | 2007.96 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12761703.20 | 5981.02 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1773648.97 | 3565.99 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5402410.17 | 4565.05 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59364687.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37361781.67 | 5981.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108369E+09 | 27246.98 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6970455.39 | 9227.58 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17561322.09 | 25669.23 | 30-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3494751.40 | 7536.26 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108369E+09 | 27246.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128788E+09 | 11559.62 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52600370.33 | 10925.78 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110103E+09 | 11559.62 | 29-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14105645.63 | 11559.62 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2765677.40 | 2853.44 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 236685.71 | 619.43 | 12-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5148406.37 | 6924.67 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42105127.69 | 11034.27 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128788E+09 | 11559.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106065E+09 | 7545.03 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41974925.26 | 7203.12 | 10-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48732952.84 | 7545.03 | 30-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2612371.16 | 6112.85 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 758883.25 | 3850.88 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5192377.77 | 4748.76 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38618596.81 | 7545.03 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106065E+09 | 7545.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342395E+09 | 9196.76 | 28-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123844E+09 | 8805.79 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180300E+09 | 8772.62 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17967636.50 | 8727.06 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 227644.06 | 758.81 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5051608.51 | 8043.48 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 57559474.64 | 8776.45 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183860E+09 | 8824.72 | 22-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342395E+09 | 9196.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181963E+09 | 7531.46 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65157890.76 | 7333.76 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94832189.98 | 7531.46 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10834222.22 | 7484.47 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 905525.25 | 1101.63 | 13-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1723258.62 | 2428.39 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29486520.66 | 7130.79 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100263E+09 | 7531.46 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181963E+09 | 7531.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.355940E+09 | 7463.51 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78733415.86 | 3246.01 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281377E+09 | 5204.29 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6446523.37 | 3172.37 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41941.51 | 209.71 | 12-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7782109.83 | 1971.65 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202673E+09 | 4697.21 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.355940E+09 | 7463.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.441592E+09 | 8143.13 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119910E+09 | 3749.24 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394118E+09 | 5542.12 | 30-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10126854.90 | 3447.84 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1380478.80 | 1180.50 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17909396.34 | 2374.04 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264483E+09 | 5100.11 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.441592E+09 | 8143.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.615604E+09 | 6543.21 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232586E+09 | 5267.46 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.561294E+09 | 6543.21 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24685243.58 | 4729.61 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3046209.32 | 1064.63 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10387274.79 | 2306.77 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75791183.60 | 3665.58 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425108E+09 | 6543.21 | 22-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.615604E+09 | 6543.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.680433E+10 | 0.618957E+10 | 33286.84 | 18-JAN-13:05 | 33286.84 | 0.00 |
February | 0.00 | 0.00 | 0.399707E+10 | 0.344555E+10 | 29856.96 | 01-FEB-12:00 | 29856.96 | 0.00 |
March | 0.00 | 0.00 | 0.464825E+10 | 0.361090E+10 | 32675.51 | 23-MAR-15:10 | 24387.77 | 0.00 |
April | 0.00 | 0.00 | 0.106717E+11 | 0.878287E+10 | 38162.88 | 26-APR-13:00 | 37203.30 | 0.00 |
May | 0.00 | 0.00 | 0.114241E+11 | 0.953033E+10 | 30726.56 | 03-MAY-13:00 | 30726.56 | 0.00 |
June | 0.00 | 0.00 | 0.215368E+11 | 0.160851E+11 | 47824.05 | 29-JUN-13:00 | 30627.50 | 0.00 |
July | 0.00 | 0.00 | 0.370024E+11 | 0.246466E+11 | 67409.62 | 31-JUL-16:00 | 38237.21 | 0.00 |
August | 0.00 | 0.00 | 0.428230E+11 | 0.278094E+11 | 63267.90 | 07-AUG-10:30 | 36890.87 | 0.00 |
September | 0.00 | 0.00 | 0.262995E+11 | 0.189768E+11 | 54787.90 | 29-SEP-13:00 | 54787.90 | 0.00 |
October | 0.00 | 0.00 | 0.293654E+11 | 0.233521E+11 | 64507.72 | 03-OCT-13:40 | 38855.38 | 0.00 |
November | 0.00 | 0.00 | 0.801093E+10 | 0.708226E+10 | 32720.17 | 28-NOV-14:00 | 32720.17 | 0.00 |
December | 0.00 | 0.00 | 0.853664E+10 | 0.827432E+10 | 32859.39 | 19-DEC-13:05 | 32859.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211120E+12 | 0.157786E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.399707E+10 | 0.344555E+10 | 29856.96 | 24387.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.428230E+11 | 0.278094E+11 | 67409.62 | 54787.90 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.630143E+10 | 0.563058E+10 | 30828.79 | 18-JAN-14:00 | 30828.79 | 0.00 |
February | 0.00 | 0.00 | 0.365174E+10 | 0.308512E+10 | 26734.47 | 03-FEB-15:05 | 26734.47 | 0.00 |
March | 0.00 | 0.00 | 0.465639E+10 | 0.361153E+10 | 35576.91 | 23-MAR-14:05 | 28931.81 | 0.00 |
April | 0.00 | 0.00 | 0.106168E+11 | 0.879088E+10 | 41043.13 | 26-APR-14:05 | 38961.97 | 0.00 |
May | 0.00 | 0.00 | 0.109099E+11 | 0.909753E+10 | 30675.59 | 04-MAY-12:05 | 30675.59 | 0.00 |
June | 0.00 | 0.00 | 0.208557E+11 | 0.156798E+11 | 46459.66 | 29-JUN-12:05 | 29802.56 | 0.00 |
July | 0.00 | 0.00 | 0.352204E+11 | 0.235984E+11 | 66613.89 | 31-JUL-16:00 | 37640.29 | 0.00 |
August | 0.00 | 0.00 | 0.405243E+11 | 0.265020E+11 | 61722.78 | 07-AUG-10:05 | 35396.03 | 0.00 |
September | 0.00 | 0.00 | 0.246840E+11 | 0.179146E+11 | 56983.71 | 29-SEP-12:02 | 56983.71 | 0.00 |
October | 0.00 | 0.00 | 0.265955E+11 | 0.212238E+11 | 61978.79 | 16-OCT-12:02 | 61978.79 | 0.00 |
November | 0.00 | 0.00 | 0.718624E+10 | 0.627575E+10 | 29353.87 | 28-NOV-14:00 | 29353.87 | 0.00 |
December | 0.00 | 0.00 | 0.746204E+10 | 0.718397E+10 | 32585.24 | 05-DEC-15:05 | 32585.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198664E+12 | 0.148594E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.365174E+10 | 0.308512E+10 | 26734.47 | 26734.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.405243E+11 | 0.265020E+11 | 66613.89 | 61978.79 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.596611E+10 | 0.519756E+10 | 33311.11 | 18-JAN-13:40 | 33311.11 | 0.00 |
February | 0.00 | 0.00 | 0.348728E+10 | 0.286809E+10 | 27033.46 | 01-FEB-12:00 | 27033.46 | 0.00 |
March | 0.00 | 0.00 | 0.470396E+10 | 0.356554E+10 | 36299.13 | 23-MAR-15:00 | 27102.70 | 0.00 |
April | 0.00 | 0.00 | 0.113405E+11 | 0.914433E+10 | 47578.65 | 26-APR-14:00 | 45705.67 | 0.00 |
May | 0.00 | 0.00 | 0.115292E+11 | 0.938057E+10 | 33734.33 | 03-MAY-14:00 | 31630.59 | 0.00 |
June | 0.00 | 0.00 | 0.224726E+11 | 0.165315E+11 | 51883.44 | 29-JUN-13:00 | 33083.13 | 0.00 |
July | 0.00 | 0.00 | 0.381234E+11 | 0.252509E+11 | 79000.06 | 31-JUL-15:30 | 46496.44 | 0.00 |
August | 0.00 | 0.00 | 0.435855E+11 | 0.280529E+11 | 77495.69 | 14-AUG-13:20 | 47122.65 | 0.00 |
September | 0.00 | 0.00 | 0.254226E+11 | 0.182468E+11 | 63710.70 | 29-SEP-13:40 | 63710.70 | 0.00 |
October | 0.00 | 0.00 | 0.268120E+11 | 0.211839E+11 | 68780.26 | 03-OCT-13:10 | 41713.21 | 0.00 |
November | 0.00 | 0.00 | 0.667392E+10 | 0.569153E+10 | 30825.22 | 28-NOV-14:00 | 30825.22 | 0.00 |
December | 0.00 | 0.00 | 0.703864E+10 | 0.671892E+10 | 33816.55 | 05-DEC-15:00 | 33816.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207156E+12 | 0.151833E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.348728E+10 | 0.286809E+10 | 27033.46 | 27033.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.435855E+11 | 0.280529E+11 | 79000.06 | 63710.70 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1618.28 | 5588.81 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1628.90 | 5589.14 | 14-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1718.02 | 5564.39 | 03-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1574.71 | 5450.39 | 05-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1592.79 | 5326.54 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1598.68 | 5199.92 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1447.32 | 5095.09 | 05-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1587.95 | 5088.29 | 30-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1499.96 | 5185.25 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1530.31 | 5291.10 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1590.17 | 5419.64 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1558.18 | 5523.17 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 1578.50 | ||||
Minimum of Months | 0.00 | 0.00 | 1447.32 | 5088.29 | ||
Maximum of Months | 0.00 | 0.00 | 1718.02 | 5589.14 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163378E+10 | 0.32 | 3178.87 | 18-JAN-15:30 | 0.96 |
February | 0.143249E+10 | 0.31 | 3086.02 | 03-FEB-15:00 | 0.96 |
March | 0.158155E+10 | 0.32 | 3361.12 | 23-MAR-15:20 | 0.99 |
April | 0.190127E+10 | 0.34 | 3730.39 | 26-APR-15:10 | 1.06 |
May | 0.202449E+10 | 0.35 | 3355.04 | 03-MAY-15:10 | 0.99 |
June | 0.239739E+10 | 0.39 | 3717.50 | 30-JUN-16:00 | 1.05 |
July | 0.300868E+10 | 0.42 | 5244.87 | 31-JUL-15:10 | 1.30 |
August | 0.345249E+10 | 0.46 | 5153.21 | 14-AUG-15:10 | 1.29 |
September | 0.273422E+10 | 0.40 | 4693.60 | 11-SEP-15:10 | 1.21 |
October | 0.274254E+10 | 0.40 | 6142.57 | 16-OCT-08:00 | 1.45 |
November | 0.192114E+10 | 0.34 | 3284.96 | 13-NOV-14:00 | 0.98 |
December | 0.171014E+10 | 0.32 | 3157.99 | 07-DEC-15:30 | 0.96 |
Annual Sum or Average | 0.265402E+11 | 0.36 | |||
Minimum of Months | 0.143249E+10 | 0.31 | 3086.02 | 0.96 | |
Maximum of Months | 0.345249E+10 | 0.46 | 6142.57 | 1.45 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138006E+10 | 0.30 | 3311.76 | 19-JAN-15:05 | 1.02 |
February | 0.124988E+10 | 0.31 | 3431.48 | 03-FEB-15:05 | 1.05 |
March | 0.141450E+10 | 0.32 | 3790.29 | 23-MAR-15:20 | 1.10 |
April | 0.184061E+10 | 0.35 | 4670.75 | 26-APR-14:05 | 1.25 |
May | 0.186268E+10 | 0.35 | 3943.34 | 03-MAY-14:05 | 1.13 |
June | 0.231300E+10 | 0.39 | 4099.67 | 30-JUN-14:05 | 1.15 |
July | 0.283678E+10 | 0.42 | 5896.99 | 31-JUL-14:05 | 1.45 |
August | 0.324069E+10 | 0.46 | 5508.35 | 14-AUG-14:05 | 1.39 |
September | 0.249755E+10 | 0.40 | 6176.49 | 29-SEP-16:00 | 1.50 |
October | 0.236331E+10 | 0.38 | 6772.87 | 16-OCT-16:00 | 1.59 |
November | 0.154821E+10 | 0.32 | 3305.18 | 10-NOV-15:05 | 1.02 |
December | 0.141497E+10 | 0.31 | 3068.14 | 05-DEC-15:40 | 0.98 |
Annual Sum or Average | 0.239622E+11 | 0.36 | |||
Minimum of Months | 0.124988E+10 | 0.30 | 3068.14 | 0.98 | |
Maximum of Months | 0.324069E+10 | 0.46 | 6772.87 | 1.59 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129332E+10 | 0.29 | 2869.49 | 18-JAN-15:30 | 0.86 |
February | 0.117566E+10 | 0.30 | 2715.22 | 03-FEB-14:50 | 0.84 |
March | 0.137441E+10 | 0.32 | 3615.24 | 23-MAR-15:20 | 0.98 |
April | 0.177617E+10 | 0.34 | 4486.46 | 26-APR-14:20 | 1.12 |
May | 0.179739E+10 | 0.34 | 3912.66 | 03-MAY-15:00 | 1.03 |
June | 0.226267E+10 | 0.38 | 4187.97 | 30-JUN-16:00 | 1.07 |
July | 0.277706E+10 | 0.40 | 5709.76 | 31-JUL-14:40 | 1.29 |
August | 0.311555E+10 | 0.43 | 5361.82 | 14-AUG-15:00 | 1.24 |
September | 0.229859E+10 | 0.37 | 6614.00 | 29-SEP-16:00 | 1.42 |
October | 0.212815E+10 | 0.35 | 7243.20 | 16-OCT-16:00 | 1.51 |
November | 0.137093E+10 | 0.30 | 2814.66 | 10-NOV-14:40 | 0.85 |
December | 0.131375E+10 | 0.30 | 2847.14 | 05-DEC-15:20 | 0.86 |
Annual Sum or Average | 0.226837E+11 | 0.34 | |||
Minimum of Months | 0.117566E+10 | 0.29 | 2715.22 | 0.84 | |
Maximum of Months | 0.311555E+10 | 0.43 | 7243.20 | 1.51 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.58 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.54 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.05 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.34 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.49 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.90 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.18 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.16 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.10 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 56.84 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.05 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.76 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.05 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.10 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.79 | 56.79 | 1618.28 | 5588.81 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.01 | 57.01 | 1628.90 | 5589.14 | 14-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.54 | 56.54 | 1718.02 | 5564.39 | 03-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.89 | 56.89 | 1574.71 | 5450.39 | 05-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.85 | 57.85 | 1592.79 | 5326.54 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.31 | 57.31 | 1598.68 | 5199.92 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.60 | 56.60 | 1447.32 | 5095.09 | 05-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.52 | 56.52 | 1587.95 | 5088.29 | 30-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.48 | 57.48 | 1499.96 | 5185.25 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.22 | 56.22 | 1530.31 | 5291.10 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.47 | 57.47 | 1590.17 | 5419.64 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.21 | 57.21 | 1558.18 | 5523.17 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 1578.50 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.22 | 56.22 | 1447.32 | 5088.29 | ||
Maximum of Months | 0.00 | 0.00 | 57.85 | 57.85 | 1718.02 | 5589.14 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.385213E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.289813E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.363308E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.479430E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.506316E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.748611E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.113969E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.131065E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.891552E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.974637E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.405776E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.412222E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.790721E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.289813E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.131065E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.293252E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.208651E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.249551E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.415085E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.426051E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.670839E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.101113E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.115644E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.776968E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.810799E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.313658E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.305459E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.663788E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.208651E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.115644E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.363593E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.234860E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.297502E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.453909E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.459640E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.748089E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.114558E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.129780E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.831529E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.856936E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.312313E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.339297E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.734105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.234860E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.129780E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163378E+10 | 0.680433E+10 | 0.932407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143249E+10 | 0.399707E+10 | 0.556787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158155E+10 | 0.464825E+10 | 0.120369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190127E+10 | 0.106717E+11 | 0.354002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202449E+10 | 0.114241E+11 | 0.284792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239739E+10 | 0.215368E+11 | 0.102528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300868E+10 | 0.370024E+11 | 3185207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345249E+10 | 0.428230E+11 | 5270271.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.273422E+10 | 0.262995E+11 | 28338924.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274254E+10 | 0.293654E+11 | 84247046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192114E+10 | 0.801093E+10 | 0.211424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171014E+10 | 0.853664E+10 | 0.600221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265402E+11 | 0.211120E+12 | 0.436689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143249E+10 | 0.399707E+10 | 3185207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345249E+10 | 0.428230E+11 | 0.120369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138006E+10 | 0.630143E+10 | 0.600363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124988E+10 | 0.365174E+10 | 0.128983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141450E+10 | 0.465639E+10 | 0.448067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184061E+10 | 0.106168E+11 | 16204228.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186268E+10 | 0.109099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231300E+10 | 0.208557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283678E+10 | 0.352204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.324069E+10 | 0.405243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249755E+10 | 0.246840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236331E+10 | 0.265955E+11 | 1380478.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154821E+10 | 0.718624E+10 | 18031107.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141497E+10 | 0.746204E+10 | 0.282365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239622E+11 | 0.198664E+12 | 0.149539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124988E+10 | 0.365174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324069E+10 | 0.405243E+11 | 0.600363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129332E+10 | 0.596611E+10 | 0.148318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117566E+10 | 0.348728E+10 | 0.523134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137441E+10 | 0.470396E+10 | 0.101282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177617E+10 | 0.113405E+11 | 70205119.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179739E+10 | 0.115292E+11 | 6945056.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.226267E+10 | 0.224726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.277706E+10 | 0.381234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311555E+10 | 0.435855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229859E+10 | 0.254226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212815E+10 | 0.268120E+11 | 18157710.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137093E+10 | 0.667392E+10 | 0.173178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131375E+10 | 0.703864E+10 | 0.793450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226837E+11 | 0.207156E+12 | 0.408108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117566E+10 | 0.348728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.311555E+10 | 0.435855E+11 | 0.148318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163378E+10 | 0.00 | 0.00 | 0.00 | 0.164188E+10 | 0.576467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143249E+10 | 0.00 | 0.00 | 0.00 | 0.987589E+09 | 0.478053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158155E+10 | 0.00 | 0.00 | 0.00 | 0.112922E+10 | 0.922313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190127E+10 | 0.00 | 0.00 | 0.00 | 0.254547E+10 | 0.347556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202449E+10 | 0.00 | 0.00 | 0.00 | 0.275388E+10 | 0.284792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239739E+10 | 0.00 | 0.00 | 0.00 | 0.498619E+10 | 0.102528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300868E+10 | 0.00 | 0.00 | 0.00 | 0.838498E+10 | 3185207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.345249E+10 | 0.00 | 0.00 | 0.00 | 0.964874E+10 | 5270271.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.273422E+10 | 0.00 | 0.00 | 0.00 | 0.615296E+10 | 28338924.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274254E+10 | 0.00 | 0.00 | 0.00 | 0.691963E+10 | 84205105.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192114E+10 | 0.00 | 0.00 | 0.00 | 0.193298E+10 | 0.203642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171014E+10 | 0.00 | 0.00 | 0.00 | 0.201453E+10 | 0.397548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265402E+11 | 0.00 | 0.00 | 0.00 | 0.490980E+11 | 0.343390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143249E+10 | 0.00 | 0.00 | 0.00 | 0.987589E+09 | 3185207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.345249E+10 | 0.00 | 0.00 | 0.00 | 0.964874E+10 | 0.922313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138006E+10 | 0.00 | 0.00 | 0.00 | 0.139369E+10 | 0.158771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124988E+10 | 0.00 | 0.00 | 0.00 | 0.827553E+09 | 9072844.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141450E+10 | 0.00 | 0.00 | 0.00 | 0.102707E+10 | 53948577.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184061E+10 | 0.00 | 0.00 | 0.00 | 0.230416E+10 | 6077373.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186268E+10 | 0.00 | 0.00 | 0.00 | 0.239783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231300E+10 | 0.00 | 0.00 | 0.00 | 0.439539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.283678E+10 | 0.00 | 0.00 | 0.00 | 0.727455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.324069E+10 | 0.00 | 0.00 | 0.00 | 0.832368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249755E+10 | 0.00 | 0.00 | 0.00 | 0.527213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236331E+10 | 0.00 | 0.00 | 0.00 | 0.574468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154821E+10 | 0.00 | 0.00 | 0.00 | 0.158825E+10 | 121711.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141497E+10 | 0.00 | 0.00 | 0.00 | 0.162174E+10 | 17881903.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239622E+11 | 0.00 | 0.00 | 0.00 | 0.421707E+11 | 0.245874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124988E+10 | 0.00 | 0.00 | 0.00 | 0.827553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324069E+10 | 0.00 | 0.00 | 0.00 | 0.832368E+10 | 0.158771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129332E+10 | 0.00 | 0.00 | 0.00 | 0.147503E+10 | 0.867579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117566E+10 | 0.00 | 0.00 | 0.00 | 0.882391E+09 | 0.290548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137441E+10 | 0.00 | 0.00 | 0.00 | 0.114908E+10 | 0.451530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177617E+10 | 0.00 | 0.00 | 0.00 | 0.271740E+10 | 45519875.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179739E+10 | 0.00 | 0.00 | 0.00 | 0.279511E+10 | 3898846.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.226267E+10 | 0.00 | 0.00 | 0.00 | 0.521822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.277706E+10 | 0.00 | 0.00 | 0.00 | 0.867874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311555E+10 | 0.00 | 0.00 | 0.00 | 0.986241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229859E+10 | 0.00 | 0.00 | 0.00 | 0.601670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212815E+10 | 0.00 | 0.00 | 0.00 | 0.643343E+10 | 7770436.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137093E+10 | 0.00 | 0.00 | 0.00 | 0.165482E+10 | 97386779.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131375E+10 | 0.00 | 0.00 | 0.00 | 0.171089E+10 | 0.368342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226837E+11 | 0.00 | 0.00 | 0.00 | 0.485942E+11 | 0.213257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117566E+10 | 0.00 | 0.00 | 0.00 | 0.882391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.311555E+10 | 0.00 | 0.00 | 0.00 | 0.986241E+10 | 0.867579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206498E+10 | 19203924.68 | 0.00 | 23917849.93 | 3115122.62 | 0.00 | 0.105871E+11 | 0.00 | 0.59 |
February | 0.154915E+10 | 5207010.58 | 0.00 | 23118505.97 | 0.00 | 0.00 | 0.112331E+11 | 0.00 | 0.61 |
March | 0.143683E+10 | 0.00 | 0.00 | 25977845.76 | 14063623.20 | 0.00 | 0.134833E+11 | 0.00 | 0.63 |
April | 0.103422E+10 | 8874450.99 | 0.00 | 28204151.36 | 9944393.65 | 0.00 | 0.115123E+11 | 0.00 | 0.73 |
May | 0.979082E+09 | 16293953.07 | 0.00 | 31785817.99 | 0.00 | 0.00 | 0.127914E+11 | 0.00 | 0.81 |
June | 0.718810E+09 | 0.197593E+09 | 0.00 | 31151148.88 | 14075101.40 | 0.00 | 0.913783E+10 | 0.00 | 0.91 |
July | 0.655521E+09 | 0.162685E+10 | 0.00 | 20217326.17 | 0.138425E+09 | 0.00 | 0.394757E+10 | 0.00 | 0.86 |
August | 0.438854E+09 | 0.197941E+10 | 0.00 | 20287664.45 | 0.169084E+09 | 0.00 | 0.379794E+10 | 0.00 | 0.93 |
September | 0.716787E+09 | 0.521114E+09 | 0.00 | 27374024.86 | 28566370.71 | 0.00 | 0.753245E+10 | 0.00 | 0.86 |
October | 0.711933E+09 | 0.105984E+10 | 0.00 | 24281848.35 | 0.125722E+09 | 0.00 | 0.728874E+10 | 0.00 | 0.77 |
November | 0.100094E+10 | 1698799.02 | 0.00 | 30986676.01 | 8155351.12 | 0.00 | 0.133329E+11 | 0.00 | 0.72 |
December | 0.138557E+10 | 1806808.84 | 0.00 | 26382667.35 | 0.00 | 0.00 | 0.110754E+11 | 0.00 | 0.59 |
Annual Sum or Average | 0.126927E+11 | 0.543789E+10 | 0.00 | 0.313686E+09 | 0.511151E+09 | 0.00 | 0.115720E+12 | 0.00 | 0.75 |
Minimum of Months | 0.438854E+09 | 0.00 | 0.00 | 20217326.17 | 0.00 | 0.00 | 0.379794E+10 | 0.00 | 0.59 |
Maximum of Months | 0.206498E+10 | 0.197941E+10 | 0.00 | 31785817.99 | 0.169084E+09 | 0.00 | 0.134833E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.541980E+10 | 3378632.70 | 0.00 | 8144020.86 | 20595135.39 | 1006227.31 | 0.394540E+10 | 0.00 | 0.43 |
February | 0.471550E+10 | 5164641.87 | 0.00 | 8776853.20 | 0.00 | 0.00 | 0.482742E+10 | 0.00 | 0.46 |
March | 0.537493E+10 | 0.00 | 0.00 | 9584476.80 | 18826580.41 | 0.00 | 0.573340E+10 | 0.00 | 0.46 |
April | 0.273688E+10 | 2119313.25 | 0.00 | 15493948.98 | 39346323.59 | 0.00 | 0.694587E+10 | 0.00 | 0.56 |
May | 0.239016E+10 | 12205620.68 | 0.00 | 18065936.36 | 0.00 | 0.00 | 0.818844E+10 | 0.00 | 0.61 |
June | 0.106622E+10 | 0.149539E+09 | 0.00 | 20101504.73 | 26118328.55 | 0.00 | 0.658493E+10 | 0.00 | 0.71 |
July | 0.709261E+09 | 0.127363E+10 | 0.00 | 14311318.78 | 0.149717E+09 | 0.00 | 0.292517E+10 | 0.00 | 0.68 |
August | 0.469237E+09 | 0.155279E+10 | 0.00 | 14108943.20 | 0.196345E+09 | 0.00 | 0.276462E+10 | 0.00 | 0.72 |
September | 0.875429E+09 | 0.413434E+09 | 0.00 | 16938640.09 | 40745367.52 | 0.00 | 0.526454E+10 | 0.00 | 0.65 |
October | 0.127254E+10 | 0.811050E+09 | 0.00 | 13937104.72 | 0.129227E+09 | 0.00 | 0.467641E+10 | 0.00 | 0.58 |
November | 0.363878E+10 | 960979.42 | 0.00 | 13416283.03 | 12035490.65 | 0.00 | 0.651907E+10 | 0.00 | 0.50 |
December | 0.484428E+10 | 1658934.29 | 0.00 | 9638895.28 | 1472445.73 | 0.00 | 0.436781E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.335130E+11 | 0.422593E+10 | 0.00 | 0.162518E+09 | 0.634428E+09 | 1006227.31 | 0.627431E+11 | 0.00 | 0.57 |
Minimum of Months | 0.469237E+09 | 0.00 | 0.00 | 8144020.86 | 0.00 | 0.00 | 0.276462E+10 | 0.00 | 0.43 |
Maximum of Months | 0.541980E+10 | 0.155279E+10 | 0.00 | 20101504.73 | 0.196345E+09 | 1006227.31 | 0.818844E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.603233E+10 | 1063712.71 | 0.00 | 4901959.55 | 12311075.36 | 58205304.06 | 0.252003E+10 | 0.00 | 0.41 |
February | 0.531031E+10 | 566263.05 | 0.00 | 5609638.24 | 92201.80 | 1609409.99 | 0.347945E+10 | 0.00 | 0.43 |
March | 0.645933E+10 | 0.00 | 0.00 | 6237047.48 | 10484961.01 | 6964505.61 | 0.408386E+10 | 0.00 | 0.45 |
April | 0.322475E+10 | 292801.60 | 0.00 | 13871455.20 | 14277144.39 | 0.00 | 0.637652E+10 | 0.00 | 0.56 |
May | 0.313496E+10 | 4285309.30 | 0.00 | 16367105.37 | 0.00 | 0.00 | 0.738337E+10 | 0.00 | 0.60 |
June | 0.156974E+10 | 75431537.65 | 0.00 | 19484101.84 | 1967889.23 | 0.00 | 0.625768E+10 | 0.00 | 0.72 |
July | 0.100952E+10 | 0.105114E+10 | 0.00 | 13849805.25 | 0.120096E+09 | 0.00 | 0.267611E+10 | 0.00 | 0.71 |
August | 0.694714E+09 | 0.138144E+10 | 0.00 | 13804107.89 | 0.162704E+09 | 0.00 | 0.238427E+10 | 0.00 | 0.76 |
September | 0.158018E+10 | 0.291200E+09 | 0.00 | 15063840.19 | 38964240.37 | 0.00 | 0.435324E+10 | 0.00 | 0.63 |
October | 0.221546E+10 | 0.705486E+09 | 0.00 | 10421346.67 | 0.124107E+09 | 0.00 | 0.304722E+10 | 0.00 | 0.56 |
November | 0.445362E+10 | 0.00 | 0.00 | 8519074.26 | 4137138.60 | 0.00 | 0.459667E+10 | 0.00 | 0.46 |
December | 0.553366E+10 | 129004.64 | 0.00 | 5467494.70 | 500634.14 | 1673418.87 | 0.268715E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.412186E+11 | 0.351104E+10 | 0.00 | 0.133597E+09 | 0.489642E+09 | 68452638.54 | 0.498456E+11 | 0.00 | 0.56 |
Minimum of Months | 0.694714E+09 | 0.00 | 0.00 | 4901959.55 | 0.00 | 0.00 | 0.238427E+10 | 0.00 | 0.41 |
Maximum of Months | 0.645933E+10 | 0.138144E+10 | 0.00 | 19484101.84 | 0.162704E+09 | 58205304.06 | 0.738337E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138214E+10 | 206001.33 | 0.00 | 438170.38 | 2616605.82 | 0.189674E+09 | 0.200113E+09 | 0.00 | 0.40 |
February | 0.134488E+10 | 121790.25 | 0.00 | 512401.02 | 19458.91 | 62846256.92 | 0.359669E+09 | 0.00 | 0.41 |
March | 0.166447E+10 | 0.00 | 0.00 | 748847.08 | 2212818.61 | 83338316.31 | 0.436000E+09 | 0.00 | 0.44 |
April | 0.973760E+09 | 74325.29 | 0.00 | 2482996.83 | 3013147.19 | 10820314.52 | 0.102207E+10 | 0.00 | 0.56 |
May | 0.872850E+09 | 1091706.49 | 0.00 | 3451801.72 | 0.00 | 0.00 | 0.144069E+10 | 0.00 | 0.64 |
June | 0.450088E+09 | 20820861.02 | 0.00 | 4850393.88 | 415316.94 | 0.00 | 0.140881E+10 | 0.00 | 0.84 |
July | 0.267114E+09 | 0.311830E+09 | 0.00 | 3181522.27 | 25219906.62 | 0.00 | 0.587240E+09 | 0.00 | 0.85 |
August | 0.250196E+09 | 0.375205E+09 | 0.00 | 2734321.76 | 36372559.58 | 0.00 | 0.409050E+09 | 0.00 | 0.86 |
September | 0.537177E+09 | 83285375.05 | 0.00 | 2831297.35 | 9173089.65 | 0.00 | 0.703214E+09 | 0.00 | 0.66 |
October | 0.660684E+09 | 0.187366E+09 | 0.00 | 1674720.70 | 26797741.15 | 1435064.17 | 0.416807E+09 | 0.00 | 0.57 |
November | 0.127426E+10 | 0.00 | 0.00 | 790232.05 | 873130.31 | 30228693.71 | 0.459759E+09 | 0.00 | 0.43 |
December | 0.139133E+10 | 0.00 | 0.00 | 399077.96 | 132883.32 | 0.110822E+09 | 0.179183E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.110689E+11 | 0.980002E+09 | 0.00 | 24095783.00 | 0.106847E+09 | 0.489164E+09 | 0.762261E+10 | 0.00 | 0.59 |
Minimum of Months | 0.250196E+09 | 0.00 | 0.00 | 399077.96 | 0.00 | 0.00 | 0.179183E+09 | 0.00 | 0.39 |
Maximum of Months | 0.166447E+10 | 0.375205E+09 | 0.00 | 4850393.88 | 36372559.58 | 0.189674E+09 | 0.144069E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.654373E+09 | 1893133.01 | 0.00 | 1223443.69 | 0.00 | 53747589.47 | 0.547199E+09 | 0.00 | 0.47 |
February | 0.657857E+09 | 118108.52 | 0.00 | 1434546.44 | 12340.62 | 16316597.77 | 0.705923E+09 | 0.00 | 0.52 |
March | 0.753900E+09 | 203502.00 | 0.00 | 2069578.61 | 1339379.86 | 22650301.25 | 0.927581E+09 | 0.00 | 0.59 |
April | 0.444431E+09 | 918996.49 | 0.00 | 4254382.49 | 1550953.02 | 1108301.54 | 0.164934E+10 | 0.00 | 0.97 |
May | 0.442105E+09 | 1463818.44 | 0.00 | 4346364.85 | 0.00 | 0.00 | 0.170324E+10 | 0.00 | 0.98 |
June | 0.251603E+09 | 20827329.18 | 0.00 | 5384543.14 | 118839.04 | 0.00 | 0.138258E+10 | 0.00 | 1.26 |
July | 0.130779E+09 | 0.320696E+09 | 0.00 | 4494583.93 | 5185824.10 | 0.00 | 0.719914E+09 | 0.00 | 1.38 |
August | 0.117896E+09 | 0.469389E+09 | 0.00 | 3751240.75 | 7707087.68 | 0.00 | 0.553449E+09 | 0.00 | 1.46 |
September | 0.277709E+09 | 78976780.25 | 0.00 | 3764257.12 | 4994800.48 | 0.00 | 0.873141E+09 | 0.00 | 1.01 |
October | 0.299255E+09 | 0.174367E+09 | 0.00 | 2385351.36 | 14684968.20 | 509937.09 | 0.642863E+09 | 0.00 | 0.78 |
November | 0.583678E+09 | 0.00 | 0.00 | 1801313.51 | 553729.52 | 2367668.84 | 0.792644E+09 | 0.00 | 0.54 |
December | 0.704250E+09 | 127220.73 | 0.00 | 1246435.87 | 0.00 | 15343839.27 | 0.430351E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.531784E+10 | 0.106898E+10 | 0.00 | 36156041.78 | 36147922.51 | 0.112044E+09 | 0.109282E+11 | 0.00 | 0.87 |
Minimum of Months | 0.117896E+09 | 0.00 | 0.00 | 1223443.69 | 0.00 | 0.00 | 0.430351E+09 | 0.00 | 0.46 |
Maximum of Months | 0.753900E+09 | 0.469389E+09 | 0.00 | 5384543.14 | 14684968.20 | 53747589.47 | 0.170324E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.743623E+09 | 15543439.40 | 0.00 | 7689684.47 | 0.00 | 63534366.94 | 0.323004E+10 | 0.00 | 1.02 |
February | 0.843604E+09 | 501943.44 | 0.00 | 5656598.29 | 19463.50 | 22387825.82 | 0.254169E+10 | 0.00 | 0.87 |
March | 0.110783E+10 | 2143803.47 | 0.00 | 5066765.40 | 549940.20 | 53260532.07 | 0.226870E+10 | 0.00 | 0.79 |
April | 0.779194E+09 | 1653672.87 | 0.00 | 5883750.10 | 2247254.87 | 9665180.27 | 0.223408E+10 | 0.00 | 0.90 |
May | 0.877819E+09 | 1468192.75 | 0.00 | 4415894.87 | 0.00 | 840172.10 | 0.175131E+10 | 0.00 | 0.75 |
June | 0.513026E+09 | 24493903.43 | 0.00 | 4952254.56 | 415415.00 | 0.00 | 0.138093E+10 | 0.00 | 0.88 |
July | 0.291307E+09 | 0.367971E+09 | 0.00 | 3348039.75 | 23474725.25 | 0.00 | 0.597760E+09 | 0.00 | 0.93 |
August | 0.219941E+09 | 0.569124E+09 | 0.00 | 4175380.58 | 29529070.91 | 0.00 | 0.594781E+09 | 0.00 | 1.18 |
September | 0.385867E+09 | 0.150688E+09 | 0.00 | 7099010.72 | 8277556.65 | 0.00 | 0.160024E+10 | 0.00 | 1.17 |
October | 0.422739E+09 | 0.429269E+09 | 0.00 | 6250752.88 | 7327312.99 | 0.00 | 0.140526E+10 | 0.00 | 1.09 |
November | 0.703912E+09 | 1293450.64 | 0.00 | 8234601.33 | 137234.92 | 1921431.67 | 0.333200E+10 | 0.00 | 1.10 |
December | 0.753609E+09 | 730061.52 | 0.00 | 8587270.74 | 0.00 | 15565720.24 | 0.283889E+10 | 0.00 | 1.03 |
Annual Sum or Average | 0.764247E+10 | 0.156488E+10 | 0.00 | 71360003.69 | 71977974.30 | 0.167175E+09 | 0.237757E+11 | 0.00 | 0.98 |
Minimum of Months | 0.219941E+09 | 501943.44 | 0.00 | 3348039.75 | 0.00 | 0.00 | 0.594781E+09 | 0.00 | 0.75 |
Maximum of Months | 0.110783E+10 | 0.569124E+09 | 0.00 | 8587270.74 | 29529070.91 | 63534366.94 | 0.333200E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.709298E+09 | 3194500.00 | 0.00 | 1404233.31 | 515055.22 | 0.101943E+09 | 0.667233E+09 | 0.00 | 0.54 |
February | 0.712189E+09 | 161146.81 | 0.00 | 1688596.01 | 12366.39 | 32664179.42 | 0.833101E+09 | 0.00 | 0.60 |
March | 0.827819E+09 | 0.00 | 0.00 | 2353186.24 | 1406274.81 | 43954136.48 | 0.114843E+10 | 0.00 | 0.67 |
April | 0.446265E+09 | 872706.36 | 0.00 | 4731836.60 | 1418490.87 | 6867498.23 | 0.179062E+10 | 0.00 | 1.02 |
May | 0.412948E+09 | 697135.74 | 0.00 | 4966189.79 | 0.00 | 364527.21 | 0.194791E+10 | 0.00 | 1.05 |
June | 0.209800E+09 | 16744706.66 | 0.00 | 6135357.64 | 218898.55 | 0.00 | 0.169274E+10 | 0.00 | 1.37 |
July | 0.120482E+09 | 0.354972E+09 | 0.00 | 4657129.77 | 12396759.72 | 0.00 | 0.769455E+09 | 0.00 | 1.41 |
August | 0.105428E+09 | 0.398269E+09 | 0.00 | 4087785.49 | 17467519.95 | 0.00 | 0.569883E+09 | 0.00 | 1.48 |
September | 0.220031E+09 | 75614568.00 | 0.00 | 4491634.17 | 4569292.64 | 0.00 | 0.111480E+10 | 0.00 | 1.12 |
October | 0.335655E+09 | 0.168571E+09 | 0.00 | 2528864.94 | 13089927.25 | 543103.31 | 0.603833E+09 | 0.00 | 0.82 |
November | 0.676709E+09 | 51708.01 | 0.00 | 2102412.71 | 503177.58 | 15144917.13 | 0.954100E+09 | 0.00 | 0.66 |
December | 0.718748E+09 | 11198.97 | 0.00 | 1478924.26 | 73250.09 | 61796832.44 | 0.579350E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.549537E+10 | 0.101916E+10 | 0.00 | 40626150.92 | 51671013.07 | 0.263278E+09 | 0.126715E+11 | 0.00 | 0.94 |
Minimum of Months | 0.105428E+09 | 0.00 | 0.00 | 1404233.31 | 0.00 | 0.00 | 0.569883E+09 | 0.00 | 0.54 |
Maximum of Months | 0.827819E+09 | 0.398269E+09 | 0.00 | 6135357.64 | 17467519.95 | 0.101943E+09 | 0.194791E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173396E+10 | 0.00 | 0.00 | 315501.68 | 4286245.89 | 66035992.60 | 0.130448E+09 | 0.00 | 0.39 |
February | 0.178829E+10 | 508248.38 | 0.00 | 78214.49 | 0.00 | 2691467.29 | 75278630.24 | 0.00 | 0.40 |
March | 0.204514E+10 | 0.00 | 0.00 | 191439.50 | 2967972.11 | 16995859.89 | 0.128431E+09 | 0.00 | 0.42 |
April | 0.123691E+10 | 337301.70 | 0.00 | 1082829.05 | 3324781.86 | 1787804.66 | 0.476842E+09 | 0.00 | 0.46 |
May | 0.107390E+10 | 2228521.20 | 0.00 | 2020240.77 | 0.00 | 0.00 | 0.825060E+09 | 0.00 | 0.52 |
June | 0.572141E+09 | 30938535.55 | 0.00 | 2953610.76 | 3042362.65 | 0.00 | 0.834982E+09 | 0.00 | 0.64 |
July | 0.300809E+09 | 0.292044E+09 | 0.00 | 1958032.97 | 29213129.27 | 0.00 | 0.390256E+09 | 0.00 | 0.66 |
August | 0.339104E+09 | 0.318838E+09 | 0.00 | 1434876.49 | 36676756.62 | 0.00 | 0.248221E+09 | 0.00 | 0.65 |
September | 0.633441E+09 | 85304537.86 | 0.00 | 1888731.73 | 9183954.13 | 0.00 | 0.479147E+09 | 0.00 | 0.56 |
October | 0.732898E+09 | 0.179805E+09 | 0.00 | 1359376.95 | 29503182.71 | 0.00 | 0.363099E+09 | 0.00 | 0.51 |
November | 0.147344E+10 | 109953.39 | 0.00 | 556415.52 | 1858965.44 | 0.00 | 0.409424E+09 | 0.00 | 0.42 |
December | 0.176446E+10 | 141257.60 | 0.00 | 132564.23 | 69641.61 | 3542515.37 | 79771764.14 | 0.00 | 0.39 |
Annual Sum or Average | 0.136945E+11 | 0.910255E+09 | 0.00 | 13971834.14 | 0.120127E+09 | 91053639.81 | 0.444096E+10 | 0.00 | 0.50 |
Minimum of Months | 0.300809E+09 | 0.00 | 0.00 | 78214.49 | 0.00 | 0.00 | 75278630.24 | 0.00 | 0.39 |
Maximum of Months | 0.204514E+10 | 0.318838E+09 | 0.00 | 2953610.76 | 36676756.62 | 66035992.60 | 0.834982E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.750588E+09 | 1528936.77 | 0.00 | 1403939.18 | 1332643.04 | 2933734.53 | 0.631940E+09 | 0.00 | 0.47 |
February | 0.764762E+09 | 603157.33 | 0.00 | 1268499.35 | 0.00 | 0.00 | 0.608306E+09 | 0.00 | 0.49 |
March | 0.865282E+09 | 0.00 | 0.00 | 1646670.63 | 1873997.80 | 746418.31 | 0.742919E+09 | 0.00 | 0.53 |
April | 0.494467E+09 | 1995972.35 | 0.00 | 3340497.81 | 1309089.78 | 0.00 | 0.123483E+10 | 0.00 | 0.80 |
May | 0.468196E+09 | 3165646.07 | 0.00 | 3499591.71 | 0.00 | 0.00 | 0.129906E+10 | 0.00 | 0.82 |
June | 0.280770E+09 | 35199896.76 | 0.00 | 3943511.90 | 1423672.58 | 0.00 | 0.987021E+09 | 0.00 | 1.01 |
July | 0.108391E+09 | 0.337904E+09 | 0.00 | 3337802.58 | 12293995.39 | 0.00 | 0.602301E+09 | 0.00 | 1.15 |
August | 95137943.66 | 0.446476E+09 | 0.00 | 2865563.46 | 12750778.32 | 0.00 | 0.506185E+09 | 0.00 | 1.21 |
September | 0.259771E+09 | 87961631.97 | 0.00 | 3154444.44 | 5392843.01 | 0.00 | 0.770306E+09 | 0.00 | 0.90 |
October | 0.283026E+09 | 0.175498E+09 | 0.00 | 2415364.19 | 16797743.80 | 0.00 | 0.691788E+09 | 0.00 | 0.73 |
November | 0.618618E+09 | 191245.84 | 0.00 | 2124008.35 | 1086712.14 | 0.00 | 0.892081E+09 | 0.00 | 0.56 |
December | 0.767915E+09 | 215995.09 | 0.00 | 1477947.11 | 0.00 | 0.00 | 0.516165E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.575692E+10 | 0.109074E+10 | 0.00 | 30477840.72 | 54261475.85 | 3680152.84 | 0.948290E+10 | 0.00 | 0.76 |
Minimum of Months | 95137943.66 | 0.00 | 0.00 | 1268499.35 | 0.00 | 0.00 | 0.506185E+09 | 0.00 | 0.46 |
Maximum of Months | 0.865282E+09 | 0.446476E+09 | 0.00 | 3943511.90 | 16797743.80 | 2933734.53 | 0.129906E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.932425E+09 | 20351701.81 | 0.00 | 5535643.68 | 0.00 | 0.260168E+09 | 0.226222E+10 | 0.00 | 0.83 |
February | 0.114227E+10 | 2374778.03 | 0.00 | 3067631.31 | 0.00 | 0.224580E+09 | 0.131327E+10 | 0.00 | 0.67 |
March | 0.149381E+10 | 1684244.83 | 0.00 | 2085132.78 | 1858916.21 | 0.408556E+09 | 0.789428E+09 | 0.00 | 0.58 |
April | 0.110638E+10 | 3245675.80 | 0.00 | 2562407.50 | 2036191.21 | 0.144338E+09 | 0.812245E+09 | 0.00 | 0.61 |
May | 0.129898E+10 | 2047900.00 | 0.00 | 1427054.74 | 375501.36 | 0.123906E+09 | 0.494601E+09 | 0.00 | 0.53 |
June | 0.889295E+09 | 34223390.84 | 0.00 | 1572128.35 | 3010181.51 | 56883069.72 | 0.358107E+09 | 0.00 | 0.59 |
July | 0.419402E+09 | 0.349210E+09 | 0.00 | 1190290.43 | 29853266.97 | 737911.56 | 0.232248E+09 | 0.00 | 0.66 |
August | 0.299535E+09 | 0.510541E+09 | 0.00 | 1797073.07 | 35957076.84 | 4469788.65 | 0.323826E+09 | 0.00 | 0.85 |
September | 0.472545E+09 | 0.178078E+09 | 0.00 | 4311999.44 | 8817593.25 | 16760876.24 | 0.987105E+09 | 0.00 | 0.92 |
October | 0.413684E+09 | 0.438492E+09 | 0.00 | 4980181.13 | 9537492.91 | 55507787.24 | 0.116252E+10 | 0.00 | 0.93 |
November | 0.835175E+09 | 3184909.57 | 0.00 | 6143466.33 | 57636.42 | 0.106474E+09 | 0.242306E+10 | 0.00 | 0.91 |
December | 0.860678E+09 | 1022373.83 | 0.00 | 7023866.81 | 0.00 | 0.202681E+09 | 0.211884E+10 | 0.00 | 0.86 |
Annual Sum or Average | 0.101642E+11 | 0.154446E+10 | 0.00 | 41696875.58 | 91503856.68 | 0.160506E+10 | 0.132775E+11 | 0.00 | 0.75 |
Minimum of Months | 0.299535E+09 | 1022373.83 | 0.00 | 1190290.43 | 0.00 | 737911.56 | 0.232248E+09 | 0.00 | 0.53 |
Maximum of Months | 0.149381E+10 | 0.510541E+09 | 0.00 | 7023866.81 | 35957076.84 | 0.408556E+09 | 0.242306E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.906025E+09 | 3665206.83 | 0.00 | 1154247.39 | 649789.27 | 11867598.68 | 0.521913E+09 | 0.00 | 0.49 |
February | 0.858359E+09 | 666526.59 | 0.00 | 1219238.81 | 0.00 | 209793.58 | 0.572245E+09 | 0.00 | 0.52 |
March | 0.983043E+09 | 0.00 | 0.00 | 1608491.87 | 1876093.38 | 5315141.93 | 0.736411E+09 | 0.00 | 0.56 |
April | 0.455429E+09 | 1315743.36 | 0.00 | 3492324.44 | 1381854.76 | 210798.93 | 0.128825E+10 | 0.00 | 0.81 |
May | 0.402726E+09 | 2018391.08 | 0.00 | 3896234.38 | 0.00 | 0.00 | 0.146201E+10 | 0.00 | 0.87 |
June | 0.207792E+09 | 31689792.59 | 0.00 | 4550008.55 | 1256950.89 | 0.00 | 0.123263E+10 | 0.00 | 1.11 |
July | 92727100.55 | 0.369130E+09 | 0.00 | 3502191.72 | 11678586.06 | 0.00 | 0.641402E+09 | 0.00 | 1.18 |
August | 82724647.12 | 0.388305E+09 | 0.00 | 2995275.25 | 14815734.16 | 0.00 | 0.516889E+09 | 0.00 | 1.22 |
September | 0.178129E+09 | 90547155.43 | 0.00 | 3869771.91 | 3826018.28 | 0.00 | 0.991285E+09 | 0.00 | 1.00 |
October | 0.301955E+09 | 0.179729E+09 | 0.00 | 2305835.27 | 13271138.64 | 0.00 | 0.598877E+09 | 0.00 | 0.74 |
November | 0.687905E+09 | 291000.48 | 0.00 | 2049700.28 | 1087927.34 | 0.00 | 0.905868E+09 | 0.00 | 0.62 |
December | 0.883515E+09 | 227307.97 | 0.00 | 1279481.94 | 33739.86 | 168279.06 | 0.464065E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.604033E+10 | 0.106759E+10 | 0.00 | 31922801.83 | 49877832.65 | 17771612.18 | 0.993184E+10 | 0.00 | 0.80 |
Minimum of Months | 82724647.12 | 0.00 | 0.00 | 1154247.39 | 0.00 | 0.00 | 0.464065E+09 | 0.00 | 0.48 |
Maximum of Months | 0.983043E+09 | 0.388305E+09 | 0.00 | 4550008.55 | 14815734.16 | 11867598.68 | 0.146201E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154714E+10 | 616644.68 | 0.00 | 624391.06 | 4434438.48 | 66762828.12 | 0.266836E+09 | 0.00 | 0.40 |
February | 0.143997E+10 | 1112199.46 | 0.00 | 712601.04 | 0.00 | 1131597.27 | 0.430708E+09 | 0.00 | 0.42 |
March | 0.174004E+10 | 0.00 | 0.00 | 944872.87 | 3969237.27 | 12873330.26 | 0.501414E+09 | 0.00 | 0.44 |
April | 0.981704E+09 | 777417.06 | 0.00 | 2567094.66 | 8026845.62 | 1012477.49 | 0.982600E+09 | 0.00 | 0.55 |
May | 0.827436E+09 | 3198560.10 | 0.00 | 3652412.11 | 0.00 | 0.00 | 0.142711E+10 | 0.00 | 0.64 |
June | 0.412568E+09 | 41854786.53 | 0.00 | 4744415.36 | 5271199.79 | 0.00 | 0.134764E+10 | 0.00 | 0.81 |
July | 0.216441E+09 | 0.375587E+09 | 0.00 | 2930821.34 | 31565093.00 | 0.00 | 0.598234E+09 | 0.00 | 0.80 |
August | 0.247546E+09 | 0.421490E+09 | 0.00 | 2235905.87 | 41395629.83 | 0.00 | 0.415383E+09 | 0.00 | 0.79 |
September | 0.525237E+09 | 0.114663E+09 | 0.00 | 2686717.20 | 11375027.27 | 0.00 | 0.705602E+09 | 0.00 | 0.66 |
October | 0.668081E+09 | 0.218064E+09 | 0.00 | 1875616.91 | 25010670.91 | 0.00 | 0.489754E+09 | 0.00 | 0.57 |
November | 0.127885E+10 | 167451.85 | 0.00 | 1207210.25 | 2541243.98 | 0.00 | 0.616174E+09 | 0.00 | 0.44 |
December | 0.155166E+10 | 275358.13 | 0.00 | 564304.90 | 310438.03 | 5626957.45 | 0.253917E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.114367E+11 | 0.117781E+10 | 0.00 | 24746363.54 | 0.133900E+09 | 87407190.59 | 0.803536E+10 | 0.00 | 0.58 |
Minimum of Months | 0.216441E+09 | 0.00 | 0.00 | 564304.90 | 0.00 | 0.00 | 0.253917E+09 | 0.00 | 0.40 |
Maximum of Months | 0.174004E+10 | 0.421490E+09 | 0.00 | 4744415.36 | 41395629.83 | 66762828.12 | 0.142711E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.651134E+09 | 2523153.21 | 0.00 | 1545415.14 | 205612.18 | 17978262.54 | 0.633128E+09 | 0.00 | 0.45 |
February | 0.655902E+09 | 1104145.20 | 0.00 | 1616816.96 | 351.13 | 505492.75 | 0.731600E+09 | 0.00 | 0.50 |
March | 0.737875E+09 | 162624.77 | 0.00 | 2204955.31 | 2408161.72 | 1510296.20 | 0.906984E+09 | 0.00 | 0.56 |
April | 0.427981E+09 | 2475925.64 | 0.00 | 4112176.20 | 4171993.65 | 0.00 | 0.152852E+10 | 0.00 | 0.90 |
May | 0.395731E+09 | 3496690.24 | 0.00 | 4253701.19 | 0.00 | 0.00 | 0.158207E+10 | 0.00 | 0.91 |
June | 0.228152E+09 | 38163535.50 | 0.00 | 4858825.12 | 2276277.15 | 0.00 | 0.124532E+10 | 0.00 | 1.14 |
July | 0.105735E+09 | 0.345031E+09 | 0.00 | 3953878.66 | 12874682.55 | 0.00 | 0.699283E+09 | 0.00 | 1.24 |
August | 0.102864E+09 | 0.466536E+09 | 0.00 | 3264388.20 | 15111710.70 | 0.00 | 0.570693E+09 | 0.00 | 1.30 |
September | 0.251302E+09 | 92335107.63 | 0.00 | 3433169.23 | 6616251.99 | 0.00 | 0.840376E+09 | 0.00 | 0.95 |
October | 0.294996E+09 | 0.176454E+09 | 0.00 | 2501252.87 | 15345395.52 | 0.00 | 0.719619E+09 | 0.00 | 0.74 |
November | 0.584704E+09 | 307738.35 | 0.00 | 2137036.40 | 1415409.09 | 0.00 | 0.878634E+09 | 0.00 | 0.54 |
December | 0.671756E+09 | 428700.71 | 0.00 | 1605660.24 | 5629.25 | 330862.91 | 0.546306E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.510813E+10 | 0.112902E+10 | 0.00 | 35487275.51 | 60431474.94 | 20324914.40 | 0.108825E+11 | 0.00 | 0.81 |
Minimum of Months | 0.102864E+09 | 162624.77 | 0.00 | 1545415.14 | 0.00 | 0.00 | 0.546306E+09 | 0.00 | 0.45 |
Maximum of Months | 0.737875E+09 | 0.466536E+09 | 0.00 | 4858825.12 | 15345395.52 | 17978262.54 | 0.158207E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.820576E+09 | 26501610.86 | 0.00 | 8630511.75 | 0.00 | 12540680.99 | 0.330031E+10 | 0.00 | 1.05 |
February | 0.913345E+09 | 4505515.47 | 0.00 | 6272890.03 | 0.00 | 300776.39 | 0.259314E+10 | 0.00 | 0.91 |
March | 0.115785E+10 | 3733923.41 | 0.00 | 5529410.87 | 1040761.24 | 7777299.61 | 0.223586E+10 | 0.00 | 0.80 |
April | 0.786032E+09 | 6337680.73 | 0.00 | 5833499.49 | 5760228.11 | 321674.98 | 0.203419E+10 | 0.00 | 0.89 |
May | 0.831490E+09 | 4367502.83 | 0.00 | 4554876.75 | 0.00 | 0.00 | 0.168071E+10 | 0.00 | 0.74 |
June | 0.492434E+09 | 49403408.69 | 0.00 | 4702954.43 | 5284902.81 | 0.00 | 0.126991E+10 | 0.00 | 0.85 |
July | 0.255858E+09 | 0.449145E+09 | 0.00 | 2866867.29 | 30165238.68 | 0.00 | 0.569841E+09 | 0.00 | 0.87 |
August | 0.201086E+09 | 0.646555E+09 | 0.00 | 3203429.49 | 38723026.45 | 0.00 | 0.571436E+09 | 0.00 | 1.08 |
September | 0.354982E+09 | 0.221669E+09 | 0.00 | 6241457.89 | 7274079.24 | 0.00 | 0.148782E+10 | 0.00 | 1.16 |
October | 0.392610E+09 | 0.501399E+09 | 0.00 | 6192002.75 | 5154893.27 | 0.00 | 0.144938E+10 | 0.00 | 1.06 |
November | 0.720015E+09 | 5195639.74 | 0.00 | 9142033.42 | 690514.18 | 0.00 | 0.342053E+10 | 0.00 | 1.14 |
December | 0.799932E+09 | 3104421.91 | 0.00 | 9704225.64 | 0.00 | 254339.52 | 0.302203E+10 | 0.00 | 1.08 |
Annual Sum or Average | 0.772621E+10 | 0.192192E+10 | 0.00 | 72874159.82 | 94093643.97 | 21194771.49 | 0.236351E+11 | 0.00 | 0.97 |
Minimum of Months | 0.201086E+09 | 3104421.91 | 0.00 | 2866867.29 | 0.00 | 0.00 | 0.569841E+09 | 0.00 | 0.74 |
Maximum of Months | 0.115785E+10 | 0.646555E+09 | 0.00 | 9704225.64 | 38723026.45 | 12540680.99 | 0.342053E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.823414E+09 | 5634650.12 | 0.00 | 1593849.97 | 836753.05 | 26484341.20 | 0.671534E+09 | 0.00 | 0.54 |
February | 0.756716E+09 | 1368091.67 | 0.00 | 1892335.24 | 0.00 | 323306.17 | 0.861896E+09 | 0.00 | 0.61 |
March | 0.846782E+09 | 0.00 | 0.00 | 2544914.85 | 2510094.39 | 6946434.49 | 0.113963E+10 | 0.00 | 0.68 |
April | 0.424902E+09 | 4935276.95 | 0.00 | 4659658.80 | 2428462.62 | 1032846.26 | 0.165098E+10 | 0.00 | 1.00 |
May | 0.373876E+09 | 2389093.70 | 0.00 | 5003597.14 | 0.00 | 0.00 | 0.183187E+10 | 0.00 | 1.04 |
June | 0.197260E+09 | 38352892.55 | 0.00 | 5767519.49 | 2268433.13 | 0.00 | 0.153066E+10 | 0.00 | 1.33 |
July | 0.104669E+09 | 0.432718E+09 | 0.00 | 3983207.68 | 12091156.75 | 0.00 | 0.691451E+09 | 0.00 | 1.32 |
August | 0.102620E+09 | 0.466830E+09 | 0.00 | 3177893.63 | 15652584.11 | 0.00 | 0.525329E+09 | 0.00 | 1.36 |
September | 0.200285E+09 | 0.110786E+09 | 0.00 | 4206782.22 | 3836784.38 | 0.00 | 0.104748E+10 | 0.00 | 1.11 |
October | 0.319492E+09 | 0.205048E+09 | 0.00 | 2530842.90 | 10851325.08 | 0.00 | 0.629588E+09 | 0.00 | 0.81 |
November | 0.673336E+09 | 714744.58 | 0.00 | 2431345.77 | 1348465.93 | 0.00 | 0.101725E+10 | 0.00 | 0.68 |
December | 0.809626E+09 | 490179.54 | 0.00 | 1696675.67 | 164891.29 | 2415919.03 | 0.623768E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.563298E+10 | 0.126927E+10 | 0.00 | 39488623.37 | 51988950.74 | 37202847.15 | 0.122214E+11 | 0.00 | 0.92 |
Minimum of Months | 0.102620E+09 | 0.00 | 0.00 | 1593849.97 | 0.00 | 0.00 | 0.525329E+09 | 0.00 | 0.54 |
Maximum of Months | 0.846782E+09 | 0.466830E+09 | 0.00 | 5767519.49 | 15652584.11 | 26484341.20 | 0.183187E+10 | 0.00 | 1.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.188164E+12 | 0.671179E+10 | 0.00 | 0.181143E+12 | 0.239358E+11 |
February | 0.219163E+12 | 0.740398E+10 | 0.00 | 0.182148E+12 | 0.139414E+11 |
March | 0.294730E+12 | 0.811073E+10 | 0.00 | 0.188875E+12 | 0.176231E+11 |
April | 0.370992E+12 | 0.477368E+10 | 0.00 | 0.184761E+12 | 0.402063E+11 |
May | 0.384799E+12 | 0.540971E+10 | 0.00 | 0.193963E+12 | 0.418107E+11 |
June | 0.377395E+12 | 0.282603E+10 | 0.00 | 0.153354E+12 | 0.794648E+11 |
July | 0.403226E+12 | 0.963818E+09 | 0.00 | 0.929482E+11 | 0.134685E+12 |
August | 0.376659E+12 | 0.103946E+10 | 0.00 | 0.722745E+11 | 0.154768E+12 |
September | 0.303420E+12 | 0.219374E+10 | 0.00 | 0.132733E+12 | 0.938479E+11 |
October | 0.220639E+12 | 0.338744E+10 | 0.00 | 0.137908E+12 | 0.101874E+12 |
November | 0.201910E+12 | 0.650810E+10 | 0.00 | 0.203733E+12 | 0.270725E+11 |
December | 0.173662E+12 | 0.705604E+10 | 0.00 | 0.201058E+12 | 0.286075E+11 |
Annual Sum or Average | 0.351476E+13 | 0.563845E+11 | 0.00 | 0.192490E+13 | 0.757836E+12 |
Minimum of Months | 0.173662E+12 | 0.963818E+09 | 0.00 | 0.722745E+11 | 0.139414E+11 |
Maximum of Months | 0.403226E+12 | 0.811073E+10 | 0.00 | 0.203733E+12 | 0.154768E+12 |