Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:32:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1674.23 | 336.04 | 336.04 |
Net Site Energy | 1546.68 | 310.44 | 310.44 |
Total Source Energy | 4774.26 | 958.27 | 958.27 |
Net Source Energy | 4370.32 | 877.19 | 877.19 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 360.24 | 110.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 80.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 21.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 143.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1420.74 | 253.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 360.24 | 110.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 167.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 80.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 21.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 143.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 360.24 | 110.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 97.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 167.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 80.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 21.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 143.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 108.00 | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 136.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 285.16 | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 108.00 | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 136.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 285.16 | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 133.675 | 9.41 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -6.13 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 127.546 | 8.98 |
Electricity Coming From Utility | 1294.392 | 91.11 |
Surplus Electricity Going To Utility | 1.202 | 0.08 |
Net Electricity From Utility | 1293.190 | 91.02 |
Total On-Site and Utility Electric Sources | 1420.736 | 100.00 |
Total Electricity End Uses | 1420.736 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 13.09 | 3.35 |
Air to Air Heat Recovery for Heating | 377.27 | 96.65 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 390.36 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 597.83 |
Time Setpoint Not Met During Occupied Cooling | 87.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3196.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 06-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 181546.28 | 170950.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 40437.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 814.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6280.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9574.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 252791.27 | 180524.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 181546.28 | 170950.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 814.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6280.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9574.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1140.88 | 119.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 307.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 529.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 109.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 255.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 68.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 155.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4499.47 | 274.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 228.99 | 23.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 31.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 903.11 | 55.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 228.99 | 23.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 31.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 903.11 | 55.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.44 | 0.306867 | 0.261000 | 0.637434 | 0.818313 | 0.500000 | 0.001242 |
CORE_MID VAV BOX COMPONENT | 2.05 | 0.366480 | 0.312000 | 0.638042 | 0.977281 | 0.500000 | 0.001040 |
CORE_TOP VAV BOX COMPONENT | 2.07 | 0.361230 | 0.307000 | 0.636943 | 0.963279 | 0.500000 | 0.001055 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.653034 | 0.241935 | 0.211000 | 0.137790 | 0.645160 | 0.500000 | 0.001575 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.818801 | 0.122156 | 0.104000 | 0.085155 | 0.325751 | 0.500000 | 0.003119 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.06 | 0.149026 | 0.127000 | 0.134640 | 0.397404 | 0.500000 | 0.002557 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.891875 | 0.112140 | 0.095000 | 0.084728 | 0.300000 | 0.500000 | 0.003398 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.506889 | 0.311689 | 0.273000 | 0.138381 | 0.831171 | 0.500000 | 0.001222 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.655875 | 0.152501 | 0.130000 | 0.085264 | 0.406670 | 0.500000 | 0.002498 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.837698 | 0.188602 | 0.160000 | 0.134032 | 0.502939 | 0.500000 | 0.002020 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.701648 | 0.142543 | 0.121000 | 0.084899 | 0.380115 | 0.500000 | 0.002673 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.566017 | 0.279129 | 0.237000 | 0.134146 | 0.744344 | 0.500000 | 0.001365 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.817259 | 0.326365 | 0.500000 | 0.003113 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.989094 | 0.159734 | 0.136000 | 0.134517 | 0.425957 | 0.500000 | 0.002385 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.840239 | 0.119032 | 0.101000 | 0.084864 | 0.317418 | 0.500000 | 0.003201 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20401.35 |
CORE_MID VAV BOX REHEAT COIL | 24762.37 |
CORE_TOP VAV BOX REHEAT COIL | 44750.66 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20900.64 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13671.48 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21028.30 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13766.08 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16223.20 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10697.06 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16351.33 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10782.04 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16300.04 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10733.39 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16411.96 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10820.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.57 | 1.08 | 5.14 | 2.14 | 4.45 | 4.45 | 0.300000 | 0.481149 | 4.45 |
PACU_VAV_MID | 2.63 | 1.08 | 5.26 | 2.47 | 4.31 | 4.31 | 0.300000 | 0.572302 | 4.31 |
PACU_VAV_TOP | 2.75 | 1.08 | 5.50 | 3.57 | 4.86 | 4.86 | 0.300000 | 0.733079 | 4.86 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.45 |
PACU_VAV_MID_OA_CONTROLLER | 4.31 |
PACU_VAV_TOP_OA_CONTROLLER | 4.86 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 0.956100 |
PACU_VAV_MID OA HEAT RECOVERY | 0.956100 |
PACU_VAV_TOP OA HEAT RECOVERY | 0.956100 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.45 | 87866.10 | 0.781558 | 1.48 | 29285.77 | 0.781558 |
PACU_VAV_MID COOLING COIL | 4.31 | 85917.12 | 0.777622 | 1.44 | 28636.18 | 0.777622 |
PACU_VAV_TOP COOLING COIL | 4.86 | 94632.85 | 0.786800 | 1.62 | 31541.13 | 0.786800 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 47904.80 |
PACU_VAV_MID HEATING COIL | 48284.07 |
PACU_VAV_TOP HEATING COIL | 47412.77 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.45 |
PACU_VAV_MID FAN | 4.31 |
PACU_VAV_TOP FAN | 4.86 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.4963 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.4907 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.6059 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.781 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.804 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.416 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.34899309E-12 | 0.71341365E-15 | -0.12063995E-12 | 0.11056198E-15 |
43 | 6 | 0.31964619E-07 | 0.14386379E-09 | 0.72949101E-08 | -0.15297586E-12 |
44 | 5 | -0.20668886E-03 | 0.12069764E-05 | -0.10606906E-03 | 0.72002597E-08 |
45 | 4 | 0.31134388 | 0.57707282E-03 | 0.10659731 | -0.36300877E-04 |
46 | 3 | -7.6460366 | 0.17597044E-01 | -2.4516196 | 0.30871179E-01 |
47 | 2 | 42.122891 | 0.61681621E-01 | 15.726221 | -0.34728460 |
48 | 1 | -81.504432 | 0.27489519E-01 | -29.554779 | 1.0990493 |
49 | 0 | 46.824333 | 0.54626793E-03 | 16.281579 | |
50 | 7 | -0.35248218E-12 | 0.86833836E-15 | -0.12082203E-12 | 0.11089560E-15 |
51 | 6 | 0.32029947E-07 | 0.14230652E-09 | 0.73093307E-08 | -0.15333007E-12 |
52 | 5 | -0.20701518E-03 | 0.11934730E-05 | -0.10623169E-03 | 0.72142720E-08 |
53 | 4 | 0.31171778 | 0.57042913E-03 | 0.10673215 | -0.36354454E-04 |
54 | 3 | -7.6534230 | 0.17389373E-01 | -2.4538128 | 0.30907429E-01 |
55 | 2 | 42.147231 | 0.60937802E-01 | 15.735171 | -0.34755580 |
56 | 1 | -81.523061 | 0.27151788E-01 | -29.562791 | 1.0994463 |
57 | 0 | 46.824333 | 0.53943493E-03 | 16.281396 | |
58 | 7 | -0.34003326E-12 | 0.10587728E-14 | -0.10362110E-12 | 0.10156885E-15 |
59 | 6 | 0.30685099E-07 | 0.17377759E-09 | 0.70124784E-08 | -0.14604764E-12 |
60 | 5 | -0.20027796E-03 | 0.14687154E-05 | -0.10287063E-03 | 0.69256609E-08 |
61 | 4 | 0.30396857 | 0.70685606E-03 | 0.10393882 | -0.35247175E-04 |
62 | 3 | -7.5002666 | 0.21681124E-01 | -2.4083433 | 0.30155984E-01 |
63 | 2 | 41.642471 | 0.76394252E-01 | 15.549432 | -0.34193213 |
64 | 1 | -81.136638 | 0.34202797E-01 | -29.396480 | 1.0912109 |
65 | 0 | 46.824335 | 0.68273867E-03 | 16.285225 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.292_SHGC_EAST_0.399 | 35 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
2 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 36 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
3 | WINDOW_U_0.292_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
4 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 38 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3672E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3743E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5390E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5452E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5484E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5975E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5854E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6108E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1817 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1063 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2089 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1235 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1196 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2513E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0713E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9024E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3674E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3757E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5392E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5468E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5501E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6066E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5851E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6105E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.5228E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9848E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2276E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7321E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.9908E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0429E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9534E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8051E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5518E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.5813E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2868E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.3083E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6456E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6530E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3517E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3604E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1268E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1900E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2770E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3286E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6759E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7140E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5851E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6105E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0086E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8703E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8702E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1954E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5223E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4798E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0713E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9024E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1265E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1909E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2762E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3272E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6742E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7075E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5854E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6108E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.2148E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3233E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5493E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8792E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0395E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5859E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9535E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8051E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7247E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.8175E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2212E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3269E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0670E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0995E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3519E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3606E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1824 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1271 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2064 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1468 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1289 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.6338E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7810E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.6977E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2342E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8194E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.9604E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5787E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.7982E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9284E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8428E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7387E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6803E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7145E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4658E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9195E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1166E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1369E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7810E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6977E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9709E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.1881E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3398E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7650E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8761E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4910E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8429E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7387E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1824 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1271 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2064 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1468 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1289 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.6330E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7804E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.6974E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2342E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8191E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.9603E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5784E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.7978E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9280E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8423E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7384E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6805E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7143E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4659E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9194E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1164E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1367E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7804E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6974E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9709E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.1879E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3398E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7647E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8757E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4906E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8423E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7384E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 32497.51870 | 32497.51870 | 2.44228 | 2.44228 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10447.38908 | 10447.38908 | 0.46730 | 0.46730 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27234.69471 | 27234.69471 | 2.04501 | 2.04501 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 17490.30482 | 17490.30482 | 0.77369 | 0.77369 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27364.04579 | 27364.04579 | 2.07473 | 2.07473 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 31487.52439 | 31487.52439 | 1.39822 | 1.39822 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8403.68559 | 8403.68559 | 0.63720 | 0.63720 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 14670.47580 | 14670.47580 | 0.65303 | 0.65303 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10798.84659 | 10798.84659 | 0.81880 | 0.81880 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9595.62928 | 9595.62928 | 0.42716 | 0.42716 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13982.01466 | 13982.01466 | 1.06016 | 1.06016 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 14759.89640 | 14759.89640 | 0.65702 | 0.65702 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11762.62445 | 11762.62445 | 0.89188 | 0.89188 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9661.89532 | 9661.89532 | 0.43012 | 0.43012 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6488.58680 | 6488.58680 | 0.49198 | 0.49198 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11392.79154 | 11392.79154 | 0.50689 | 0.50689 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8650.32253 | 8650.32253 | 0.65588 | 0.65588 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 23.98267 | 1.27152E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7511.28209 | 7511.28209 | 0.33423 | 0.33423 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11048.34435 | 11048.34435 | 0.83770 | 0.83770 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27257E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11482.53374 | 11482.53374 | 0.51089 | 0.51089 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9254.03373 | 9254.03373 | 0.70165 | 0.70165 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 26.50400 | 1.27196E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7570.80085 | 7570.80085 | 0.33688 | 0.33688 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7464.98031 | 7464.98031 | 0.56602 | 0.56602 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11447.46282 | 11447.46282 | 0.50929 | 0.50929 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10778.64172 | 10778.64172 | 0.81726 | 0.81726 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 22.88733 | 1.27133E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7537.28723 | 7537.28723 | 0.33536 | 0.33536 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13044.87663 | 13044.87663 | 0.98909 | 0.98909 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27251E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11525.84952 | 11525.84952 | 0.51279 | 0.51279 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11081.70959 | 11081.70959 | 0.84024 | 0.84024 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7598.22697 | 7598.22697 | 0.33808 | 0.33808 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 64605.11 | 4.45478 | 4.45478 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 50044.51 | 2.14341 | 2.14341 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 62760.98 | 4.31452 | 4.31452 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 50160.85 | 2.46921 | 2.46921 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 69813.86 | 4.86381 | 4.86381 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 50435.43 | 3.56555 | 3.56555 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.44228 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30687 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63743 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81831 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24158E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20401.35489 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.04501 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36648 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63804 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97728 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03962E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24762.37280 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07473 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36123 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63694 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96328 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05473E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 44750.65888 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65303 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24193 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13779 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64516 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57480E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20900.63567 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81880 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12216 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51553E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32575 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11895E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13671.47817 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06016 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14903 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13464 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39740 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55659E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21028.29758 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89188 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11214 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.50000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47282E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.39753E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13766.08313 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50689 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31169 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13838 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83117 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22237E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16223.20131 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65588 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15250 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52638E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40667 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49834E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10697.05848 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83770 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18860 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13403 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50294 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02012E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16351.33457 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70165 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14254 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48994E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38012 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67287E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10782.04067 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56602 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27913 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13415 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74434 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36496E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16300.03827 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81726 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32636 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11308E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10733.39194 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98909 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15973 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13600 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13452 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42596 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38522E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16411.95544 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84024 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11903 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10100 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48641E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31742 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20082E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10820.39882 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.57219 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08001 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.14439 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.14341 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.45478 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.45478 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.48115 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.62881 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07656 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.25762 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.46921 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.31452 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.31452 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.57230 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.74930 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07926 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.49860 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.56555 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.86381 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.86381 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.73308 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.45478 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.31452 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.86381 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.45478 |
146 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.45478 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 87866.09564 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78156 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.48478 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29285.76968 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78156 |
153 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 47904.79757 |
154 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.45478 |
155 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.31452 |
156 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.31452 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85917.11752 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77762 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.43803 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28636.17527 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77762 |
163 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 48284.06856 |
164 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.31452 |
165 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.86381 |
166 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.86381 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 94632.85246 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78680 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.62111 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31541.12972 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78680 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 47412.77055 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.86381 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 87013.93 | 296903.84 | 11.74 | 3.01 | 3.36 | 3.54 | 3.73 | 10.26 | 11.47 | 12.06 | 12.71 | 4.9375 | 3.9457 | 2.6576 | 1.0637 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 85115.90 | 290427.51 | 11.76 | 3.01 | 3.37 | 3.54 | 3.73 | 10.27 | 11.49 | 12.09 | 12.73 | 4.7820 | 3.8200 | 2.5727 | 1.0333 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 93664.05 | 319595.01 | 11.71 | 3.00 | 3.35 | 3.52 | 3.72 | 10.23 | 11.43 | 12.03 | 12.69 | 5.3908 | 4.3092 | 2.9025 | 1.1566 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_NORTH_0.399 | N/A | 1.658 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_EAST_0.399 | N/A | 1.658 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_SOUTH_0.399 | N/A | 1.658 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.292_SHGC_WEST_0.399 | N/A | 1.658 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.2515275491E-002 | 1.5451084341E-002 | Pass | Pass | 0.4995670516 | 0.5017032154 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2379764389 | 0.1811060576 | Pass | Pass | 0.5275366402 | 0.5071609066 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1046078457 | 6.8132627257E-002 | Pass | Pass | 0.5203074508 | 0.4984145522 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8660913954E-002 | 5.4908850587E-002 | Pass | Pass | 0.4989716391 | 0.4965693084 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.2004081310E-002 | 3.8923466721E-002 | Pass | Pass | 1.2724221693 | 6.0561497255 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1925133931 | 0.2055323049 | Pass | Pass | 0.6381381720 | 0.6277156426 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.9308081544 | 0.7522561887 | Pass | Pass | 0.5885226819 | 0.5398650794 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8436940397 | 0.8411522901 | Pass | Pass | 0.6108304646 | 0.5597695198 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5987536244 | 0.7051551187 | Pass | Pass | 2.6171719206 | 22.3553546976 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8667044904 | 0.8714178906 | Pass | Pass | 0.6099115685 | 0.5672776285 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6986298096 | 0.5803833503 | Pass | Pass | 0.6035995687 | 0.5487555480 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5908970573 | 0.6041048637 | Pass | Pass | 0.6288220739 | 0.6151445103 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3137104209 | 0.3845327944 | Pass | Pass | 1.8749028891 | 15.2310825496 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6134511504 | 0.6296784498 | Pass | Pass | 0.6462794895 | 0.6897684939 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7216476918 | 0.6062699314 | Pass | Pass | 0.6322001529 | 0.5536225755 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6369299895 | 0.6615011652 | Pass | Pass | 0.6337283824 | 0.5786541151 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4456575088 | 0.5203014417 | Pass | Pass | 0.6642414228 | 0.7373777074 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6585117264 | 0.6788996465 | Pass | Pass | 0.6360952116 | 0.5903747496 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3249.44 | 210.27 | 0.00 | 2035.93 | 528.78 | 6024.43 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.292_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.292_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.292_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.658 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.292_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.292_SHGC_EAST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.292_SHGC_EAST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.292_SHGC_WEST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.292_SHGC_WEST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.658 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.292_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.292_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.292_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.292_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.658 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 195.79 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.658 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.76 | 0.0000 | Y | 4.91 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.60 | 0.0000 | Y | 3.09 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.42 | 0.0000 | Y | 4.84 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.55 | 0.0000 | Y | 3.08 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.70 | 0.0000 | Y | 4.90 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.56 | 0.0000 | Y | 3.08 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.39 | 0.0000 | Y | 4.83 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.51 | 0.0000 | Y | 3.08 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.76 | 0.0000 | Y | 4.91 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.60 | 0.0000 | Y | 3.09 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.42 | 0.0000 | Y | 4.84 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.55 | 0.0000 | Y | 3.08 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 167.12 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.55 | 42.55 | 4.33 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.52 | 63.04 | 3.32 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.52 | 47.99 | 27.04 | |
Exterior Lighting Total | 3824.74 | 34.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 87866.10 | 68672.45 | 19193.64 | 0.78 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 85917.12 | 66811.06 | 19106.06 | 0.78 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 94632.85 | 74457.10 | 20175.75 | 0.79 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 87013.9 | 3.01 | 10.26 | N/A | N/A | 11.74 | |
PACU_VAV_MID COOLING COIL | 85115.9 | 3.01 | 10.27 | N/A | N/A | 11.76 | |
PACU_VAV_TOP COOLING COIL | 93664.1 | 3.00 | 10.23 | N/A | N/A | 11.71 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20401.35 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24762.37 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 44750.66 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20900.64 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13671.48 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21028.30 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13766.08 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16223.20 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10697.06 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16351.33 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10782.04 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16300.04 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10733.39 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16411.96 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10820.40 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 47904.80 | 0.84 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 48284.07 | 0.84 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 47412.77 | 0.84 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.45 | 10305.63 | 2313.39 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.31 | 9981.16 | 2313.39 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.86 | 11179.27 | 2298.46 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 87013.93 | 3.01 | 10.26 | 11.74 | 4.9375 | 3.36 | 11.47 | 3.9457 | 3.54 | 12.06 | 2.6576 | 3.73 | 12.71 | 1.0637 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85115.90 | 3.01 | 10.27 | 11.76 | 4.7820 | 3.37 | 11.49 | 3.8200 | 3.54 | 12.09 | 2.5727 | 3.73 | 12.73 | 1.0333 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93664.05 | 3.00 | 10.23 | 11.71 | 5.3908 | 3.35 | 11.43 | 4.3092 | 3.52 | 12.03 | 2.9025 | 3.72 | 12.69 | 1.1566 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 32497.52 | 32497.52 | 33.04 | 2.442 | 2.442 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_MID | 27234.69 | 27234.69 | 27.69 | 2.045 | 2.045 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_TOP | 27364.05 | 27364.05 | 27.82 | 2.075 | 2.075 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00894 | 29.85 | 0.01273 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8403.69 | 8403.69 | 40.53 | 0.637 | 0.637 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00900 | 29.98 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10798.85 | 10798.85 | 82.27 | 0.819 | 0.819 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00876 | 23.28 | 0.01271 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13982.01 | 13982.01 | 67.44 | 1.060 | 1.060 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00881 | 29.79 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11762.62 | 11762.62 | 89.62 | 0.892 | 0.892 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00874 | 27.95 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6488.59 | 6488.59 | 31.29 | 0.492 | 0.492 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00903 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8650.32 | 8650.32 | 65.90 | 0.656 | 0.656 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00876 | 23.98 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11048.34 | 11048.34 | 53.29 | 0.838 | 0.838 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00881 | 30.00 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9254.03 | 9254.03 | 70.50 | 0.702 | 0.702 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00874 | 26.50 | 0.01272 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7464.98 | 7464.98 | 36.00 | 0.566 | 0.566 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00902 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10778.64 | 10778.64 | 82.12 | 0.817 | 0.817 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00874 | 22.89 | 0.01271 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13044.88 | 13044.88 | 62.92 | 0.989 | 0.989 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00881 | 29.69 | 0.01273 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11081.71 | 11081.71 | 84.43 | 0.840 | 0.840 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00873 | 27.95 | 0.01272 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10447.39 | 10447.39 | 10.62 | 0.467 | 0.467 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_MID | 17490.30 | 17490.30 | 17.78 | 0.774 | 0.774 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_TOP | 31487.52 | 31487.52 | 32.01 | 1.398 | 1.398 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 14670.48 | 14670.48 | 70.76 | 0.653 | 0.653 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9595.63 | 9595.63 | 73.10 | 0.427 | 0.427 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14759.90 | 14759.90 | 71.19 | 0.657 | 0.657 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9661.90 | 9661.90 | 73.61 | 0.430 | 0.430 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11392.79 | 11392.79 | 54.95 | 0.507 | 0.507 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7511.28 | 7511.28 | 57.22 | 0.334 | 0.334 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11482.53 | 11482.53 | 55.38 | 0.511 | 0.511 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7570.80 | 7570.80 | 57.68 | 0.337 | 0.337 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11447.46 | 11447.46 | 55.21 | 0.509 | 0.509 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7537.29 | 7537.29 | 57.42 | 0.335 | 0.335 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11525.85 | 11525.85 | 55.59 | 0.513 | 0.513 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7598.23 | 7598.23 | 57.89 | 0.338 | 0.338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -32.70 | 0.00018 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.45 | 4.45 | 2.14 | 2.14 | 4.4548 | 2.1434 | 4.4548 | 0.4811 | 0.3000 |
PACU_VAV_MID | 4.31 | 4.31 | 2.47 | 2.47 | 4.3145 | 2.4692 | 4.3145 | 0.5723 | 0.3000 |
PACU_VAV_TOP | 4.86 | 4.86 | 3.57 | 3.57 | 4.8638 | 3.5656 | 4.8638 | 0.7331 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20401.355 | 20401.355 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 20401.35 | 14956.26 | 0.467304 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 10447.39 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24762.373 | 24762.373 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24762.37 | 24762.37 | 0.773693 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 17490.30 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 44750.659 | 44750.659 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 44750.66 | 44750.66 | 1.398220 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 31487.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20900.636 | 20900.636 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20900.64 | 20900.64 | 0.653034 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773717 | 47.9558 | 14670.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13671.478 | 13671.478 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13671.48 | 13671.48 | 0.427161 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773244 | 47.9270 | 9595.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21028.298 | 21028.298 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21028.30 | 21028.30 | 0.657023 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773875 | 47.9654 | 14759.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13766.083 | 13766.083 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13766.08 | 13766.08 | 0.430117 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773425 | 47.9381 | 9661.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16223.201 | 16223.201 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16223.20 | 16223.20 | 0.506889 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00781189 | 48.4114 | 11392.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10697.058 | 10697.058 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10697.06 | 10697.06 | 0.334226 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00781156 | 48.4094 | 7511.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16351.335 | 16351.335 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16351.33 | 16351.33 | 0.510892 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00781371 | 48.4225 | 11482.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10782.041 | 10782.041 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10782.04 | 10782.04 | 0.336882 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00781331 | 48.4202 | 7570.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16300.038 | 16300.038 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16300.04 | 16300.04 | 0.509290 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00771470 | 47.8178 | 11447.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10733.392 | 10733.392 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10733.39 | 10733.39 | 0.335361 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00771276 | 47.8061 | 7537.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16411.955 | 16411.955 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16411.96 | 16411.96 | 0.512786 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00771686 | 47.8310 | 11525.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10820.399 | 10820.399 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10820.40 | 10820.40 | 0.338080 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00771526 | 47.8213 | 7598.23 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 87866.096 | 68672.454 | 4.454780 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 89205.11 | 73607.32 | 4.454780 | 25.31 | 17.41 | 0.00971826 | 10.84 | 10.84 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 21.4623 | 24.00 | 0.00889627 | 45.8664 | 58749.35 | 0.00 | 90601.74 | 68212.61 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 47904.798 | 47904.798 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47904.80 | 47904.80 | 1.336434 | -18.11 | -18.11 | 0.00230074 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 71.5411 | 18.20 | 0.00762495 | 56.2571 | 16039.92 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 85917.118 | 66811.059 | 4.314522 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 87330.60 | 71479.84 | 4.314522 | 25.35 | 17.47 | 0.00977865 | 10.84 | 10.84 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 22.1600 | 24.00 | 0.00893909 | 46.0844 | 56876.10 | 0.00 | 88592.08 | 66386.19 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 48284.069 | 48284.069 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48284.07 | 48284.07 | 1.294357 | -19.37 | -19.37 | 0.00209314 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 73.8668 | 17.61 | 0.00752569 | 57.6398 | 14706.20 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 94632.852 | 74457.105 | 4.863808 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 95921.94 | 79743.85 | 4.863808 | 25.20 | 17.32 | 0.00965763 | 10.85 | 10.85 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 19.6574 | 24.00 | 0.00890535 | 45.9130 | 64039.70 | 0.00 | 97579.17 | 73939.53 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 47412.771 | 47412.771 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47412.77 | 47412.77 | 1.459142 | -15.22 | -15.22 | 0.00268981 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 65.5248 | 16.02 | 0.00758013 | 64.1850 | 15292.71 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20401.355 | 20401.355 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 20401.35 | 14956.26 | 1.0000 | 0.53923343 | 0.467304 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20401.35 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 10447.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24762.373 | 24762.373 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24762.37 | 24762.37 | 1.0000 | 0.89278317 | 0.773693 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24762.37 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 17490.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 44750.659 | 44750.659 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 44750.66 | 44750.66 | 1.0000 | 1.61344130 | 1.398220 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44750.66 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 31487.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20900.636 | 20900.636 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20900.64 | 20900.64 | 1.0000 | 0.75355201 | 0.653034 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20900.64 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00773717 | 21.00 | 0.00773717 | 47.9558 | 14670.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13671.478 | 13671.478 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13671.48 | 13671.48 | 1.0000 | 0.49291179 | 0.427161 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13671.48 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00773244 | 21.00 | 0.00773244 | 47.9270 | 9595.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 21028.298 | 21028.298 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21028.30 | 21028.30 | 1.0000 | 0.75815473 | 0.657023 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21028.30 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00773875 | 21.00 | 0.00773875 | 47.9654 | 14759.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13766.083 | 13766.083 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13766.08 | 13766.08 | 1.0000 | 0.49632268 | 0.430117 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13766.08 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00773425 | 21.00 | 0.00773425 | 47.9381 | 9661.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16223.201 | 16223.201 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16223.20 | 16223.20 | 1.0000 | 0.58491168 | 0.506889 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16223.20 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00781189 | 21.00 | 0.00781189 | 48.4114 | 11392.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10697.058 | 10697.058 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10697.06 | 10697.06 | 1.0000 | 0.38567200 | 0.334226 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10697.06 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00781156 | 21.00 | 0.00781156 | 48.4094 | 7511.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16351.335 | 16351.335 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16351.33 | 16351.33 | 1.0000 | 0.58953140 | 0.510892 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16351.33 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00781371 | 21.00 | 0.00781371 | 48.4225 | 11482.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10782.041 | 10782.041 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10782.04 | 10782.04 | 1.0000 | 0.38873595 | 0.336882 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10782.04 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00781331 | 21.00 | 0.00781331 | 48.4202 | 7570.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16300.038 | 16300.038 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16300.04 | 16300.04 | 1.0000 | 0.58768196 | 0.509290 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16300.04 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00771470 | 21.00 | 0.00771470 | 47.8178 | 11447.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10733.392 | 10733.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10733.39 | 10733.39 | 1.0000 | 0.38698196 | 0.335361 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10733.39 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00771276 | 21.00 | 0.00771276 | 47.8061 | 7537.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16411.955 | 16411.955 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16411.96 | 16411.96 | 1.0000 | 0.59171703 | 0.512786 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16411.96 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00771686 | 21.00 | 0.00771686 | 47.8310 | 11525.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10820.399 | 10820.399 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10820.40 | 10820.40 | 1.0000 | 0.39011891 | 0.338080 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10820.40 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00771526 | 21.00 | 0.00771526 | 47.8213 | 7598.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 87866.096 | 68672.454 | 4.454780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9058 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.454780 | 5.14048132 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 89205.11 | 73607.32 | 1.0152 | 5.14048132 | 4.454780 | 25.31 | 17.41 | 0.00971826 | 50192.7 | 10.84 | 10.84 | 0.00850000 | 32321.8 | -999.0 | -999.00 | -999.00 | -999.00 | 10305.628 | 78899.48 | 30.10 | 0.01272586 | 21.13 | 0.95610000 | 21.4623 | 24.00 | 0.00889627 | 24.00 | 0.00889627 | 45.8664 | 58749.35 | 0.00 | 90601.74 | 68212.61 | 4.93747116 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.15 | 13.13 | 0.00940677 | 36972.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47904.798 | 47904.798 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.454780 | 5.14048132 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47904.80 | 47904.80 | 1.0000 | 1.54214440 | 1.336434 | -18.11 | -18.11 | 0.00230074 | -12524.7 | 12.80 | 11.22 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47904.80 | -32.70 | 0.00018338 | -32.70 | 0.95610000 | 71.5411 | 18.55 | 0.00762348 | 18.20 | 0.00762495 | 56.2571 | 16039.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85917.118 | 66811.059 | 4.314522 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0180 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.314522 | 4.97863385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 87330.60 | 71479.84 | 1.0165 | 4.97863385 | 4.314522 | 25.35 | 17.47 | 0.00977865 | 50390.5 | 10.84 | 10.84 | 0.00850000 | 32322.1 | -999.0 | -999.00 | -999.00 | -999.00 | 9981.157 | 77349.44 | 30.10 | 0.01272586 | 21.13 | 0.95610000 | 22.1600 | 24.00 | 0.00893909 | 24.00 | 0.00893909 | 46.0844 | 56876.10 | 0.00 | 88592.08 | 66386.19 | 4.78201544 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.09 | 13.07 | 0.00936400 | 36796.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48284.069 | 48284.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.314522 | 4.97863385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48284.07 | 48284.07 | 1.0000 | 1.49359015 | 1.294357 | -19.37 | -19.37 | 0.00209314 | -14305.5 | 12.80 | 11.22 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48284.07 | -32.70 | 0.00018338 | -32.70 | 0.95610000 | 73.8668 | 18.30 | 0.00749119 | 17.61 | 0.00752569 | 57.6398 | 14706.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 94632.852 | 74457.105 | 4.863808 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.7931 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.863808 | 5.61246841 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 95921.94 | 79743.85 | 1.0136 | 5.61246841 | 4.863808 | 25.20 | 17.32 | 0.00965763 | 49927.4 | 10.85 | 10.85 | 0.00850000 | 32334.5 | -999.0 | -999.00 | -999.00 | -999.00 | 11179.275 | 84742.66 | 30.10 | 0.01272586 | 21.13 | 0.95610000 | 19.6574 | 24.00 | 0.00890535 | 24.00 | 0.00890535 | 45.9130 | 64039.70 | 0.00 | 97579.17 | 73939.53 | 5.39081833 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.25 | 13.23 | 0.00946533 | 37221.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47412.771 | 47412.771 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.863808 | 5.61246841 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:50:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47412.77 | 47412.77 | 1.0000 | 1.68374052 | 1.459142 | -15.22 | -15.22 | 0.00268981 | -8645.8 | 12.80 | 11.22 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47412.77 | -32.70 | 0.00018338 | -32.70 | 0.95610000 | 65.5248 | 17.99 | 0.00745363 | 16.02 | 0.00758013 | 64.1850 | 15292.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.45 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.31 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.86 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2324.83 | 3442.33 | 753.33 |
CORE_MID | 2882.00 | 3802.17 | 1492.17 |
CORE_TOP | 3363.50 | 4053.83 | 2112.00 |
PERIMETER_TOP_ZN_3 | 3906.67 | 4262.50 | 2731.17 |
PERIMETER_TOP_ZN_2 | 4011.67 | 3946.33 | 2541.00 |
PERIMETER_TOP_ZN_1 | 3621.50 | 3886.33 | 2182.50 |
PERIMETER_TOP_ZN_4 | 3950.83 | 4069.33 | 2569.50 |
PERIMETER_BOT_ZN_3 | 3783.50 | 4411.17 | 2770.00 |
PERIMETER_BOT_ZN_2 | 3933.17 | 3928.17 | 2454.17 |
PERIMETER_BOT_ZN_1 | 3657.50 | 4263.67 | 2440.33 |
PERIMETER_BOT_ZN_4 | 3907.00 | 3988.50 | 2482.83 |
PERIMETER_MID_ZN_3 | 3785.67 | 4057.67 | 2489.83 |
PERIMETER_MID_ZN_2 | 3334.50 | 3260.33 | 2000.83 |
PERIMETER_MID_ZN_1 | 3453.67 | 3646.17 | 1877.50 |
PERIMETER_MID_ZN_4 | 3810.33 | 3849.67 | 2294.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5047.83 | 4796.83 | 3196.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.50 | 1.00 | 2.33 | 1.00 |
CORE_MID | 5.50 | 0.50 | 4.83 | 0.50 |
CORE_TOP | 22.00 | 0.33 | 17.33 | 0.33 |
PERIMETER_TOP_ZN_3 | 287.00 | 2.33 | 145.33 | 2.17 |
PERIMETER_TOP_ZN_2 | 159.17 | 17.33 | 33.00 | 16.83 |
PERIMETER_TOP_ZN_1 | 127.50 | 22.83 | 24.50 | 22.33 |
PERIMETER_TOP_ZN_4 | 155.50 | 25.00 | 34.17 | 14.50 |
PERIMETER_BOT_ZN_3 | 189.00 | 0.67 | 148.33 | 0.67 |
PERIMETER_BOT_ZN_2 | 40.83 | 9.33 | 8.17 | 9.33 |
PERIMETER_BOT_ZN_1 | 520.83 | 13.00 | 498.33 | 13.00 |
PERIMETER_BOT_ZN_4 | 41.17 | 17.33 | 9.33 | 8.67 |
PERIMETER_MID_ZN_3 | 122.33 | 3.00 | 70.33 | 3.00 |
PERIMETER_MID_ZN_2 | 61.83 | 17.67 | 13.83 | 17.50 |
PERIMETER_MID_ZN_1 | 40.67 | 26.00 | 5.67 | 25.83 |
PERIMETER_MID_ZN_4 | 61.17 | 24.50 | 14.50 | 14.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 781.67 | 107.67 | 597.83 | 87.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.741 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.630 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.616 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.762 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.084 | 0.091 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 1.062 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.043 | 0.091 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.636 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.918 | 0.048 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.902 | 0.876 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.872 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.738 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.990 | 0.080 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 1.060 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.022 | 0.076 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.67 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 11747369.58 | 0.00 | 11747369.58 | 0.00 | 11747369.58 | 13393058.27 | 5535.08 | 793.71 | 2431.20 | 226.70 |
CORE_MID | 10037105.87 | 0.00 | 10037105.87 | 0.00 | 10037105.87 | 13393058.27 | 5303.68 | 1209.71 | 2246.61 | 277.83 |
CORE_TOP | 9802829.50 | 0.00 | 9802829.50 | 0.00 | 9802829.50 | 13393058.27 | 5572.34 | 1139.14 | 2048.52 | 87.48 |
PERIMETER_TOP_ZN_3 | 2552702.21 | 0.00 | 2552702.21 | 554487.21 | 3107189.42 | 2823374.22 | 4396.43 | 110.58 | 4252.99 | 87.48 |
PERIMETER_TOP_ZN_2 | 2288111.52 | 0.00 | 2288111.52 | 369655.91 | 2657767.44 | 1787429.43 | 4551.46 | 1029.34 | 3179.20 | 87.48 |
PERIMETER_TOP_ZN_1 | 3541394.16 | 0.00 | 3541394.16 | 554487.21 | 4095881.36 | 2823374.22 | 4585.22 | 1028.18 | 3146.60 | 87.48 |
PERIMETER_TOP_ZN_4 | 2219220.06 | 0.00 | 2219220.06 | 369655.91 | 2588875.97 | 1787312.18 | 4670.12 | 1117.26 | 2972.61 | 87.48 |
PERIMETER_BOT_ZN_3 | 2140068.58 | 0.00 | 2140068.58 | 294816.05 | 2434884.63 | 2823374.22 | 5078.36 | 171.21 | 3510.43 | 226.70 |
PERIMETER_BOT_ZN_2 | 1941415.00 | 0.00 | 1941415.00 | 196542.85 | 2137957.85 | 1787429.43 | 5094.00 | 735.40 | 2930.61 | 226.70 |
PERIMETER_BOT_ZN_1 | 3030237.99 | 0.00 | 3030237.99 | 3086506.81 | 6116744.80 | 2823374.22 | 4653.89 | 784.25 | 3321.85 | 226.70 |
PERIMETER_BOT_ZN_4 | 1850469.87 | 0.00 | 1850469.87 | 196542.85 | 2047012.73 | 1787312.18 | 5135.19 | 824.43 | 2800.38 | 226.70 |
PERIMETER_MID_ZN_3 | 2474575.24 | 0.00 | 2474575.24 | 461566.56 | 2936141.80 | 2823374.22 | 4733.68 | 1232.70 | 2793.62 | 277.80 |
PERIMETER_MID_ZN_2 | 2111544.36 | 0.00 | 2111544.36 | 307709.19 | 2419253.55 | 1601953.02 | 4449.87 | 1000.38 | 3309.75 | 1186.80 |
PERIMETER_MID_ZN_1 | 3537866.84 | 0.00 | 3537866.84 | 461566.56 | 3999433.41 | 2823374.22 | 4568.64 | 1198.07 | 2993.29 | 277.80 |
PERIMETER_MID_ZN_4 | 2172969.88 | 0.00 | 2172969.88 | 307709.19 | 2480679.07 | 1787312.18 | 4681.40 | 1243.69 | 2834.91 | 277.80 |
Total Facility | 61447880.65 | 0.00 | 61447880.65 | 7161246.32 | 68609126.97 | 67658168.57 | 6525.94 | 1986.50 | 4682.49 | 1285.30 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5439 | 0.0000 | 0.5439 | 0.0000 | 0.5439 | 0.4247 | 2751.08 | 793.71 | 2398.20 |
CORE_MID | 0.4632 | 0.0000 | 0.4632 | 0.0000 | 0.4632 | 0.4247 | 2529.34 | 1209.71 | 2203.94 |
CORE_TOP | 0.4529 | 0.0000 | 0.4529 | 0.0000 | 0.4529 | 0.4247 | 2804.38 | 1139.14 | 1999.48 |
PERIMETER_TOP_ZN_3 | 0.1182 | 0.0000 | 0.1182 | 0.0135 | 0.1316 | 0.0895 | 1628.47 | 110.58 | 4203.95 |
PERIMETER_TOP_ZN_2 | 0.1062 | 0.0000 | 0.1062 | 0.0090 | 0.1152 | 0.0567 | 1783.50 | 1029.34 | 3130.16 |
PERIMETER_TOP_ZN_1 | 0.1644 | 0.0000 | 0.1644 | 0.0135 | 0.1778 | 0.0895 | 1817.26 | 1028.18 | 3097.56 |
PERIMETER_TOP_ZN_4 | 0.1022 | 0.0000 | 0.1022 | 0.0090 | 0.1112 | 0.0567 | 1902.17 | 1117.26 | 2923.57 |
PERIMETER_BOT_ZN_3 | 0.0989 | 0.0000 | 0.0989 | 0.0072 | 0.1060 | 0.0895 | 2294.36 | 171.21 | 3477.43 |
PERIMETER_BOT_ZN_2 | 0.0900 | 0.0000 | 0.0900 | 0.0048 | 0.0948 | 0.0567 | 2310.07 | 735.37 | 2897.56 |
PERIMETER_BOT_ZN_1 | 0.1405 | 0.0000 | 0.1405 | 0.1376 | 0.2781 | 0.0895 | 1869.89 | 784.25 | 3288.85 |
PERIMETER_BOT_ZN_4 | 0.0855 | 0.0000 | 0.0855 | 0.0048 | 0.0903 | 0.0567 | 2351.22 | 824.43 | 2767.36 |
PERIMETER_MID_ZN_3 | 0.1144 | 0.0000 | 0.1144 | 0.0112 | 0.1256 | 0.0895 | 1959.35 | 1232.70 | 2750.95 |
PERIMETER_MID_ZN_2 | 0.0970 | 0.0000 | 0.0970 | 0.0079 | 0.1049 | 0.0567 | 1675.61 | 1000.36 | 2358.04 |
PERIMETER_MID_ZN_1 | 0.1641 | 0.0000 | 0.1641 | 0.0112 | 0.1753 | 0.0895 | 1794.31 | 1198.07 | 2950.62 |
PERIMETER_MID_ZN_4 | 0.1001 | 0.0000 | 0.1001 | 0.0075 | 0.1076 | 0.0567 | 1907.18 | 1243.69 | 2792.12 |
Total Facility | 2.8412 | 0.0000 | 2.8412 | 0.2370 | 3.0782 | 2.1513 | 3730.61 | 1986.45 | 4622.30 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 27575648.38 | 0.00 | 27575648.38 | 22614548.33 | 4160.21 | 2.94 | 4596.86 | 226.68 |
PACU_VAV_MID | 27075629.19 | 0.00 | 27075629.19 | 22429071.92 | 4117.92 | 4.28 | 4637.80 | 277.51 |
PACU_VAV_TOP | 27169066.07 | 0.00 | 27169066.07 | 22614548.33 | 4131.46 | 1.69 | 4626.84 | 87.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2766 | 0.0000 | 1.2766 | 0.7171 | 1376.21 | 2.94 | 4563.86 |
PACU_VAV_MID | 1.2511 | 0.0000 | 1.2511 | 0.7084 | 1344.42 | 4.28 | 4594.30 |
PACU_VAV_TOP | 1.2568 | 0.0000 | 1.2568 | 0.7171 | 1363.50 | 1.69 | 4577.80 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 241.74 | 2268.61 | 0.00 | 0.00 | 0.00 | 2511.10 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 106.18 | 2377.05 | 0.00 | 0.00 | 0.00 | 2637.55 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 95.09 | 2102.39 | 0.00 | 0.00 | 0.00 | 2665.69 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2611 | 2.2749 | 0.0000 | 0.0000 | 0.0000 | 1.0504 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2587 | 2.2278 | 0.0000 | 0.0000 | 0.0000 | 0.9961 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2942 | 2.3040 | 0.0000 | 0.0000 | 0.0000 | 1.0150 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 954 |
Defaulted Fields | 550 |
Fields with Defaults | 2304 |
Autosized Fields | 153 |
Autosizable Fields | 205 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1420.74 | 11240.73 | 16-APR-17:30 | 252791.27 | 02-JAN-08:10 |
Electricity:Building | 814.88 | 11072.20 | 16-APR-17:10 | 58110.10 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 814.88 | 11072.20 | 16-APR-17:10 | 58110.10 | 02-JAN-08:10 |
InteriorLights:Electricity | 167.13 | 772.31 | 01-JAN-10:20 | 17672.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 167.13 | 772.31 | 01-JAN-10:20 | 17672.30 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 167.13 | 772.31 | 01-JAN-10:20 | 17672.30 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 167.13 | 772.31 | 01-JAN-10:20 | 17672.30 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.25 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.91 | 19.49 | 01-JAN-10:20 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.91 | 19.49 | 01-JAN-10:20 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.49 | 256.76 | 16-APR-17:10 | 1374.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.09 | 12.34 | 01-JAN-08:40 | 465.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.09 | 12.34 | 01-JAN-08:40 | 465.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.17 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.84 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.84 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.48 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.08 | 12.34 | 01-JAN-10:10 | 465.57 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.08 | 12.34 | 01-JAN-10:10 | 465.57 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.24 | 405.59 | 26-MAR-17:10 | 2170.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.90 | 19.49 | 01-JAN-10:10 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.90 | 19.49 | 01-JAN-10:10 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.49 | 256.76 | 26-MAR-17:10 | 1374.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.08 | 12.34 | 01-JAN-08:40 | 465.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.08 | 12.34 | 01-JAN-08:40 | 465.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.16 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.83 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.83 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.48 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.08 | 12.34 | 01-JAN-10:10 | 465.57 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.08 | 12.34 | 01-JAN-10:10 | 465.57 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.25 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.91 | 19.49 | 01-JAN-10:20 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.91 | 19.49 | 01-JAN-10:20 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.49 | 256.76 | 16-APR-17:10 | 1374.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.09 | 12.34 | 01-JAN-08:40 | 465.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.09 | 12.34 | 01-JAN-08:40 | 465.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.17 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.84 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.84 | 19.49 | 01-JAN-08:40 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.48 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.08 | 12.34 | 01-JAN-10:10 | 465.57 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.08 | 12.34 | 01-JAN-10:10 | 465.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 127.55 | -0.00 | 21-JAN-16:40 | 25605.48 | 19-APR-12:20 |
ElectricityProduced:Plant | 127.55 | -0.00 | 21-JAN-16:40 | 25605.48 | 19-APR-12:20 |
Photovoltaic:ElectricityProduced | 133.68 | 0.00 | 01-JAN-00:10 | 26647.85 | 19-APR-12:20 |
PowerConversion:ElectricityProduced | -6.13 | -1042.38 | 19-APR-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 571.02 | 168.53 | 19-MAR-17:10 | 213537.62 | 26-DEC-07:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.79 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.79 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1294.39 | 0.00 | 19-FEB-11:10 | 252791.27 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 1294.39 | 0.00 | 19-FEB-11:10 | 252791.27 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1294.39 | 0.00 | 19-FEB-11:10 | 252791.27 | 02-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1294.39 | 0.00 | 19-FEB-11:10 | 252791.27 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 1.20 | 0.00 | 01-JAN-00:10 | 10944.87 | 14-MAY-11:50 |
ElectricitySurplusSold:Plant | 1.20 | 0.00 | 01-JAN-00:10 | 10944.87 | 14-MAY-11:50 |
Cogeneration:ElectricitySurplusSold | 1.20 | 0.00 | 01-JAN-00:10 | 10944.87 | 14-MAY-11:50 |
General:Cogeneration:ElectricitySurplusSold | 1.20 | 0.00 | 01-JAN-00:10 | 10944.87 | 14-MAY-11:50 |
ElectricityNet:Facility | 1293.19 | -10944.87 | 14-MAY-11:50 | 252791.27 | 02-JAN-08:10 |
ElectricityNet:Plant | 1293.19 | -10944.87 | 14-MAY-11:50 | 252791.27 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 1293.19 | -10944.87 | 14-MAY-11:50 | 252791.27 | 02-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1293.19 | -10944.87 | 14-MAY-11:50 | 252791.27 | 02-JAN-08:10 |
Heating:Electricity | 360.24 | 0.00 | 01-JAN-00:40 | 203268.66 | 26-DEC-07:10 |
General:Heating:Electricity | 360.24 | 0.00 | 01-JAN-00:40 | 203268.66 | 26-DEC-07:10 |
Fans:Electricity | 80.66 | 0.00 | 01-JAN-00:40 | 31453.47 | 05-JUL-10:30 |
General:Fans:Electricity | 80.66 | 0.00 | 01-JAN-00:40 | 31453.47 | 05-JUL-10:30 |
ExteriorLights:Electricity | 34.69 | 0.00 | 01-JAN-08:20 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.69 | 0.00 | 01-JAN-08:20 | 3824.74 | 01-JAN-06:10 |
HeatRecovery:Electricity | 21.50 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:50 |
General:HeatRecovery:Electricity | 21.50 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:50 |
Cooling:Electricity | 97.01 | 0.00 | 01-JAN-00:10 | 67628.11 | 05-JUL-11:50 |
General:Cooling:Electricity | 97.01 | 0.00 | 01-JAN-00:10 | 67628.11 | 05-JUL-11:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 4.70 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 253.49 | 1886.44 | 04-JAN-05:30 | 180524.58 | 06-JAN-08:10 |
NaturalGas:HVAC | 110.05 | 0.00 | 01-JAN-00:40 | 170954.33 | 05-JAN-07:40 |
Heating:NaturalGas | 110.05 | 0.00 | 01-JAN-00:40 | 170954.33 | 05-JAN-07:40 |
General:Heating:NaturalGas | 110.05 | 0.00 | 01-JAN-00:40 | 170954.33 | 05-JAN-07:40 |
NaturalGas:Plant | 143.45 | 1886.44 | 03-JAN-05:20 | 13904.76 | 02-MAR-12:30 |
WaterSystems:NaturalGas | 143.45 | 1886.44 | 03-JAN-05:20 | 13904.76 | 02-MAR-12:30 |
Water Heater:WaterSystems:NaturalGas | 143.45 | 1886.44 | 03-JAN-05:20 | 13904.76 | 02-MAR-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2345.27 | 0.00 | 01-JAN-00:40 | 520065.76 | 09-JAN-07:10 |
EnergyTransfer:Building | 1028.75 | 0.00 | 01-JAN-00:40 | 205093.89 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 150.52 | 0.00 | 01-JAN-00:40 | 21260.08 | 05-JUL-08:00 |
Heating:EnergyTransfer | 330.36 | 0.00 | 01-JAN-00:40 | 205093.89 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.14 | 0.00 | 01-JAN-00:10 | 16461.67 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 330.36 | 0.00 | 01-JAN-00:40 | 205093.89 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.14 | 0.00 | 01-JAN-00:10 | 16461.67 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 698.38 | 0.00 | 01-JAN-00:40 | 153321.09 | 24-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 149.38 | 0.00 | 01-JAN-00:40 | 21260.08 | 05-JUL-08:00 |
General:Cooling:EnergyTransfer | 698.38 | 0.00 | 01-JAN-00:40 | 153321.09 | 24-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 149.38 | 0.00 | 01-JAN-00:40 | 21260.08 | 05-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.58 | 0.00 | 01-JAN-00:40 | 16616.67 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.63 | 0.00 | 01-JAN-00:40 | 16616.67 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.63 | 0.00 | 01-JAN-00:40 | 16616.67 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.95 | 0.00 | 01-JAN-00:10 | 9549.41 | 30-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.95 | 0.00 | 01-JAN-00:10 | 9549.41 | 30-JUN-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.84 | 0.00 | 01-JAN-00:40 | 10181.93 | 26-DEC-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.11 | 0.00 | 01-JAN-00:40 | 10181.93 | 26-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.11 | 0.00 | 01-JAN-00:40 | 10181.93 | 26-DEC-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.73 | 0.00 | 01-JAN-00:10 | 5089.22 | 24-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.73 | 0.00 | 01-JAN-00:10 | 5089.22 | 24-JUL-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.13 | 0.00 | 01-JAN-00:40 | 8369.38 | 02-JAN-08:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.79 | 0.00 | 01-JAN-00:40 | 8369.38 | 02-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.79 | 0.00 | 01-JAN-00:40 | 8369.38 | 02-JAN-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.34 | 0.00 | 01-JAN-00:10 | 4814.77 | 24-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.34 | 0.00 | 01-JAN-00:10 | 4814.77 | 24-JUL-15:40 |
EnergyTransfer:Zone:CORE_MID | 117.47 | 0.00 | 01-JAN-00:40 | 21558.55 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.42 | 0.00 | 01-JAN-00:40 | 21558.55 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.42 | 0.00 | 01-JAN-00:40 | 21558.55 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 112.04 | 0.00 | 01-JAN-00:20 | 17865.91 | 24-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 112.04 | 0.00 | 01-JAN-00:20 | 17865.91 | 24-JUL-07:20 |
EnergyTransfer:Zone:CORE_TOP | 120.60 | 0.00 | 01-JAN-00:40 | 26384.27 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 21.57 | 0.00 | 01-JAN-00:40 | 26384.27 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 21.57 | 0.00 | 01-JAN-00:40 | 26384.27 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 99.03 | 0.00 | 01-JAN-00:20 | 18938.31 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 99.03 | 0.00 | 01-JAN-00:20 | 18938.31 | 24-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.75 | 0.00 | 01-JAN-00:40 | 9345.35 | 23-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.01 | 0.00 | 01-JAN-00:40 | 9345.35 | 23-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.01 | 0.00 | 01-JAN-00:40 | 9345.35 | 23-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.74 | 0.00 | 01-JAN-00:10 | 6506.79 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.74 | 0.00 | 01-JAN-00:10 | 6506.79 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 41.24 | 0.00 | 01-JAN-00:40 | 9864.38 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 18.51 | 0.00 | 01-JAN-00:40 | 9864.38 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 18.51 | 0.00 | 01-JAN-00:40 | 9864.38 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.72 | 0.00 | 01-JAN-00:10 | 9486.62 | 24-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.72 | 0.00 | 01-JAN-00:10 | 9486.62 | 24-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.56 | 0.00 | 01-JAN-00:40 | 14137.47 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.08 | 0.00 | 01-JAN-00:40 | 14137.47 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.08 | 0.00 | 01-JAN-00:40 | 14137.47 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.48 | 0.00 | 01-JAN-00:10 | 14005.24 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.48 | 0.00 | 01-JAN-00:10 | 14005.24 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.23 | 0.00 | 01-JAN-00:40 | 10353.30 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 19.47 | 0.00 | 01-JAN-00:40 | 10353.30 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 19.47 | 0.00 | 01-JAN-00:40 | 10353.30 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.76 | 0.00 | 01-JAN-00:10 | 9713.21 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.76 | 0.00 | 01-JAN-00:10 | 9713.21 | 30-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.44 | 0.00 | 01-JAN-00:40 | 7038.09 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.29 | 0.00 | 01-JAN-00:40 | 7038.09 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.29 | 0.00 | 01-JAN-00:40 | 7038.09 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 17.14 | 0.00 | 01-JAN-00:10 | 4660.17 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 17.14 | 0.00 | 01-JAN-00:10 | 4660.17 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.86 | 0.00 | 01-JAN-00:40 | 7965.50 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 12.63 | 0.00 | 01-JAN-00:40 | 7965.50 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 12.63 | 0.00 | 01-JAN-00:40 | 7965.50 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.24 | 0.00 | 01-JAN-00:10 | 7328.56 | 24-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.24 | 0.00 | 01-JAN-00:10 | 7328.56 | 24-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 67.54 | 0.00 | 01-JAN-00:40 | 17165.21 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 42.34 | 0.00 | 01-JAN-00:40 | 17165.21 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 42.34 | 0.00 | 01-JAN-00:40 | 17165.21 | 09-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.20 | 0.00 | 01-JAN-00:20 | 12042.47 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.20 | 0.00 | 01-JAN-00:20 | 12042.47 | 29-JUN-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.81 | 0.00 | 01-JAN-00:40 | 8425.83 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.19 | 0.00 | 01-JAN-00:40 | 8425.83 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.19 | 0.00 | 01-JAN-00:40 | 8425.83 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 18.63 | 0.00 | 01-JAN-00:20 | 7303.70 | 24-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 18.63 | 0.00 | 01-JAN-00:20 | 7303.70 | 24-JUL-17:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.57 | 0.00 | 01-JAN-00:40 | 7849.39 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 19.60 | 0.00 | 01-JAN-00:40 | 7849.39 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 19.60 | 0.00 | 01-JAN-00:40 | 7849.39 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.97 | 0.00 | 01-JAN-00:10 | 6028.74 | 29-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.97 | 0.00 | 01-JAN-00:10 | 6028.74 | 29-JUN-14:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.57 | 0.00 | 01-JAN-00:40 | 9458.42 | 24-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.99 | 0.00 | 01-JAN-00:40 | 8589.29 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.99 | 0.00 | 01-JAN-00:40 | 8589.29 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.58 | 0.00 | 01-JAN-00:20 | 9458.42 | 24-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.58 | 0.00 | 01-JAN-00:20 | 9458.42 | 24-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.79 | 0.00 | 01-JAN-00:40 | 13243.47 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 11.99 | 0.00 | 01-JAN-00:40 | 11868.19 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 11.99 | 0.00 | 01-JAN-00:40 | 11868.19 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.80 | 0.00 | 01-JAN-00:20 | 13243.47 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.80 | 0.00 | 01-JAN-00:20 | 13243.47 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 35.25 | 0.00 | 01-JAN-00:40 | 9302.54 | 24-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.61 | 0.00 | 01-JAN-00:40 | 8626.65 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.61 | 0.00 | 01-JAN-00:40 | 8626.65 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.65 | 0.00 | 01-JAN-00:20 | 9302.54 | 24-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.65 | 0.00 | 01-JAN-00:20 | 9302.54 | 24-JUL-17:00 |
PlantLoopHeatingDemand:Facility | 59.32 | 0.00 | 01-JAN-00:10 | 7496.42 | 22-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 59.32 | 0.00 | 01-JAN-00:10 | 7496.42 | 22-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 59.32 | 0.00 | 01-JAN-00:10 | 7496.42 | 22-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 59.32 | 0.00 | 01-JAN-00:10 | 7496.42 | 22-FEB-12:20 |
EnergyTransfer:HVAC | 1257.20 | 0.00 | 01-JAN-00:40 | 326812.06 | 09-JAN-07:20 |
HeatingCoils:EnergyTransfer | 452.68 | 0.00 | 01-JAN-00:40 | 326812.06 | 09-JAN-07:20 |
HeatRecoveryForHeating:EnergyTransfer | 377.27 | 0.00 | 01-JAN-00:10 | 101925.81 | 21-JAN-07:30 |
HeatRecoveryForCooling:EnergyTransfer | 13.09 | 0.00 | 01-JAN-00:10 | 57052.90 | 15-JUL-14:00 |
CoolingCoils:EnergyTransfer | 414.16 | 0.00 | 01-JAN-00:10 | 315467.03 | 05-JUL-10:30 |
EnergyTransfer:Plant | 59.32 | 0.00 | 01-JAN-00:10 | 7496.42 | 22-FEB-12:20 |
WaterSystems:EnergyTransfer | 59.32 | 0.00 | 01-JAN-00:10 | 7496.42 | 22-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 59.32 | 0.00 | 01-JAN-00:10 | 7496.42 | 22-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 1.141 | -149.381 | 0.000 | 0.000 | 34.177 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -104.217 |
CORE_MID | 0.000 | 0.000 | 5.422 | -112.045 | 0.000 | 0.000 | 35.194 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -83.792 |
CORE_TOP | 0.000 | 0.000 | 21.567 | -99.034 | 0.000 | 0.000 | 35.728 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -113.482 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 32.008 | -21.744 | 0.000 | 0.000 | 7.664 | 4.915 | 24.333 | 16.694 | 0.000 | 0.040 | 0.000 | 0.000 | -41.392 | 0.000 | -11.899 | -10.618 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 18.514 | -22.725 | 0.000 | 0.000 | 4.783 | 3.089 | 15.404 | 32.936 | 0.000 | 0.026 | 0.001 | 0.000 | -25.708 | 0.000 | -8.034 | -18.284 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 22.076 | -38.479 | 0.000 | 0.000 | 7.460 | 4.838 | 24.332 | 70.239 | 0.000 | 0.037 | 0.000 | 0.000 | -37.177 | 0.000 | -12.235 | -41.091 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 19.469 | -22.756 | 0.000 | 0.000 | 4.811 | 3.081 | 15.403 | 33.499 | 0.000 | 0.024 | 0.001 | 0.000 | -26.584 | 0.000 | -8.056 | -18.892 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 23.294 | -17.144 | 0.000 | 0.000 | 7.678 | 4.903 | 24.333 | 17.141 | 0.000 | 0.027 | 0.000 | 0.000 | -41.692 | 0.000 | -6.432 | -12.109 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 12.626 | -19.239 | 0.000 | 0.000 | 4.773 | 3.084 | 15.404 | 33.188 | 0.000 | 0.015 | 0.001 | 0.000 | -26.190 | 0.000 | -4.382 | -19.279 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 42.343 | -25.197 | 0.000 | 0.000 | 7.772 | 4.831 | 24.332 | 71.239 | 0.000 | 0.696 | 0.005 | 0.000 | -37.622 | 0.000 | -59.548 | -28.846 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 13.186 | -18.628 | 0.000 | 0.000 | 4.797 | 3.076 | 15.403 | 33.795 | 0.000 | 0.014 | 0.001 | 0.000 | -27.103 | 0.000 | -4.398 | -20.142 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 19.600 | -22.966 | 0.000 | 0.000 | 7.597 | 4.915 | 24.333 | 16.496 | 0.000 | 0.034 | 2.878 | 0.000 | -42.698 | 0.000 | -10.189 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 10.989 | -22.578 | 0.000 | 0.000 | 3.506 | 3.089 | 15.404 | 32.721 | 0.000 | 0.021 | 0.000 | 0.000 | -26.496 | 0.000 | -6.877 | -9.779 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 11.989 | -40.796 | 0.000 | 0.000 | 7.383 | 4.838 | 24.332 | 69.966 | 0.000 | 0.032 | 0.003 | 0.000 | -38.435 | 0.000 | -10.503 | -28.805 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 11.606 | -23.649 | 0.000 | 0.000 | 4.770 | 3.081 | 15.403 | 33.371 | 0.000 | 0.021 | 0.001 | 0.000 | -27.423 | 0.000 | -6.895 | -10.286 |
TOPFLOOR_PLENUM | 37.627 | -17.954 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.035 | 0.000 | 0.000 | 0.000 | 0.000 | -18.109 | -1.599 |
MIDFLOOR_PLENUM | 16.113 | -10.729 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.046 | 11.867 | 0.000 | 0.000 | 0.000 | -17.297 | -0.000 |
FIRSTFLOOR_PLENUM | 10.792 | -13.337 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.037 | 16.251 | 0.000 | 0.000 | 0.000 | -13.743 | -0.001 |
Total Facility | 64.533 | -42.021 | 265.830 | -656.360 | 0.000 | 0.000 | 178.093 | 167.125 | 647.750 | 461.285 | 0.000 | 1.106 | 31.010 | 0.000 | -398.520 | 0.000 | -198.597 | -521.221 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-05:12 | 0.00 | 0.00 | 0.00 | -34898.75 | 0.00 | 0.00 | 322.34 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 30140.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 31-JUL-05:12 | 0.00 | 0.00 | 0.00 | -29463.63 | 0.00 | 0.00 | 328.09 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 25721.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-JUL-05:12 | 0.00 | 0.00 | 0.00 | -29754.86 | 0.00 | 0.00 | 331.44 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 26009.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-15:32 | 0.00 | 0.00 | 0.00 | -9968.57 | 0.00 | 0.00 | 27.45 | 19.49 | 478.42 | 3116.20 | 0.00 | 170.45 | 6156.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:22 | 0.00 | 0.00 | 0.00 | -13799.59 | 0.00 | 0.00 | 13.29 | 12.34 | 302.86 | 11435.47 | 0.00 | 0.00 | 2112.30 | 0.00 | -0.00 | 0.00 | -76.67 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-13:22 | 0.00 | 0.00 | 0.00 | -17781.97 | 0.00 | 0.00 | 22.49 | 19.49 | 478.41 | 17932.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -285.78 | -385.36 |
PERIMETER_TOP_ZN_4 | 21-MAY-16:42 | 0.00 | 0.00 | 0.00 | -15542.13 | 0.00 | 0.00 | 14.35 | 12.34 | 302.86 | 10175.42 | 0.00 | 0.00 | 5175.26 | 0.00 | -0.00 | 0.00 | -138.10 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6346.30 | 0.00 | 0.00 | 147.62 | 116.94 | 637.89 | 2614.89 | 0.00 | 0.00 | 2855.02 | 0.00 | -0.00 | 0.00 | -26.06 | 0.00 |
PERIMETER_BOT_ZN_2 | 25-JUN-08:51 | 0.00 | 0.00 | 0.00 | -11242.33 | 0.00 | 0.00 | 16.57 | 12.34 | 302.86 | 9832.92 | 0.00 | 0.00 | 1110.67 | 0.00 | -0.00 | 0.00 | -33.03 | 0.00 |
PERIMETER_BOT_ZN_1 | 22-OCT-14:53 | 0.00 | 0.00 | 0.00 | -14214.30 | 0.00 | 0.00 | 25.33 | 19.49 | 478.41 | 10200.66 | 0.00 | 0.00 | 3703.69 | 0.00 | -0.00 | 0.00 | -213.28 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-SEP-17:12 | 0.00 | 0.00 | 0.00 | -12372.17 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 10240.28 | 0.00 | 0.00 | 1985.77 | 0.00 | -0.00 | 0.00 | -110.63 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-16:41 | 0.00 | 0.00 | 0.00 | -8845.06 | 0.00 | 0.00 | 29.10 | 19.49 | 478.42 | 2202.51 | 0.00 | 54.01 | 6061.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-08:11 | 0.00 | 0.00 | 0.00 | -15157.72 | 0.00 | 0.00 | 13.47 | 12.34 | 302.86 | 11676.99 | 0.00 | 0.00 | 3256.20 | 0.00 | -0.00 | 0.00 | -104.14 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-12:42 | 0.00 | 0.00 | 0.00 | -17307.43 | 0.00 | 0.00 | 23.37 | 19.49 | 478.41 | 12372.01 | 0.00 | 39.40 | 4374.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 23-APR-16:41 | 0.00 | 0.00 | 0.00 | -15280.23 | 0.00 | 0.00 | 13.38 | 12.34 | 302.86 | 13161.26 | 0.00 | 0.00 | 1887.38 | 0.00 | -0.00 | 0.00 | -96.98 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:40 | 0.00 | -9549.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.03 | 9392.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:15 | 0.00 | -6322.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6401.37 | 0.00 | -0.00 | 0.00 | -79.17 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-06:15 | 0.00 | -5281.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5341.91 | 0.00 | -0.00 | 0.00 | -60.13 | 0.00 |
Total Facility | 24-JUL-06:03 | 0.00 | -6496.96 | 0.00 | -169644.63 | 0.00 | 0.00 | 3480.01 | 4634.49 | 18346.02 | 33274.01 | 0.00 | 0.00 | 121259.47 | 0.00 | 0.00 | 0.00 | -4852.41 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 19281.67 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 3464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23133.49 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 24512.38 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27342.07 |
CORE_TOP | 01-JAN-23:22 | 0.00 | 0.00 | 29796.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.79 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31822.24 |
PERIMETER_TOP_ZN_3 | 24-DEC-12:02 | 0.00 | 0.00 | 10178.13 | 0.00 | 0.00 | 0.00 | 60.80 | 19.49 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2568.25 | 0.00 | -2705.54 | -5463.04 |
PERIMETER_TOP_ZN_2 | 23-JAN-05:11 | 0.00 | 0.00 | 12510.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2359.86 | 0.00 | -860.94 | -9643.68 |
PERIMETER_TOP_ZN_1 | 23-JAN-05:11 | 0.00 | 0.00 | 16205.04 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3470.68 | 0.00 | -1291.01 | -12002.78 |
PERIMETER_TOP_ZN_4 | 23-JAN-05:11 | 0.00 | 0.00 | 13570.98 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2308.63 | 0.00 | -863.48 | -10753.02 |
PERIMETER_BOT_ZN_3 | 01-JAN-22:02 | 0.00 | 0.00 | 7722.85 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3461.66 | 0.00 | -736.46 | -3951.69 |
PERIMETER_BOT_ZN_2 | 01-JAN-22:02 | 0.00 | 0.00 | 9735.16 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2321.27 | 0.00 | -500.00 | -7184.17 |
PERIMETER_BOT_ZN_1 | 06-JAN-07:10 | 0.00 | 0.00 | 17313.06 | 0.00 | 0.00 | 0.00 | 209.50 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 25284.82 | 0.00 | -4762.95 | 0.00 | -38927.46 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-22:02 | 0.00 | 0.00 | 10378.43 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2368.84 | 0.00 | -501.18 | -7778.69 |
PERIMETER_MID_ZN_3 | 01-JAN-22:02 | 0.00 | 0.00 | 8623.87 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3493.28 | 0.00 | -1153.65 | -4403.90 |
PERIMETER_MID_ZN_2 | 01-JAN-22:02 | 0.00 | 0.00 | 11372.49 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2332.87 | 0.00 | -783.10 | -8526.80 |
PERIMETER_MID_ZN_1 | 26-DEC-04:42 | 0.00 | 0.00 | 14612.82 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3782.12 | 0.00 | -919.81 | -10466.54 |
PERIMETER_MID_ZN_4 | 01-JAN-22:02 | 0.00 | 0.00 | 11459.56 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2388.33 | 0.00 | -783.87 | -8557.64 |
TOPFLOOR_PLENUM | 06-JAN-06:13 | 17120.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17120.59 |
MIDFLOOR_PLENUM | 02-JAN-07:04 | 10607.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -253.24 | -10354.44 |
FIRSTFLOOR_PLENUM | 02-JAN-08:30 | 8506.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -104.78 | -8402.14 |
Total Facility | 02-JAN-05:01 | 20699.93 | 0.00 | 200355.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31011.53 | 0.00 | -13898.24 | -191501.79 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1444 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4548 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2576 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3145 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.4986 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8638 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5722 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0800 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6288 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0766 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7493 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0793 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4423 | 2.4423 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0450 | 2.0450 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0747 | 2.0747 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6530 | 0.6530 | 0.1378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8188 | 0.8188 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0602 | 1.0602 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8919 | 0.8919 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5069 | 0.5069 | 0.1384 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6559 | 0.6559 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8377 | 0.8377 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7016 | 0.7016 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5660 | 0.5660 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8173 | 0.8173 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9891 | 0.9891 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8402 | 0.8402 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1444 | 4.4548 | 5.1444 | 1.0800 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2576 | 4.3145 | 5.2576 | 1.0766 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.4986 | 4.8638 | 5.4986 | 1.0793 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2211 | 1.2211 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0225 | 1.0225 | 0.6380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0374 | 1.0374 | 0.6369 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3265 | 0.3265 | 0.1378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4094 | 0.4094 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5301 | 0.5301 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4459 | 0.4459 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2534 | 0.2534 | 0.1384 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3279 | 0.3279 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4188 | 0.4188 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3508 | 0.3508 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2830 | 0.2830 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4086 | 0.4086 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4945 | 0.4945 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4201 | 0.4201 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5722 | 1.0800 | 1.0800 | 1.0800 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6288 | 1.0766 | 1.0766 | 1.0766 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7493 | 1.0793 | 1.0793 | 1.0793 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 597.83 |
Number of hours cooling loads not met | 87.67 |
Number of hours not met | 685.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 360.24 | 203268.66 | 110.05 | 170954.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 97.01 | 67628.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 167.13 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.69 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 829.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 80.66 | 31453.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 21.50 | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 143.45 | 13904.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1420.74 |
Natural Gas | 0.00 | 253.49 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1674.23 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 133.68 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.54 |
Space Heating | 72.31 |
Space Cooling | 19.47 |
Fans (All) | 16.19 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 285.16 |
Subtotal | 285.16 |
Natural Gas [MJ/m2] | |
Space Heating | 22.09 |
Service Water Heating | 28.79 |
Miscellaneous (All) | 50.88 |
Subtotal | 50.88 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.98 |
Space Heating | 28.09 |
Space Cooling | 5.79 |
Fans (All) | 4.82 |
Service Water Heating | 8.57 |
Receptacle Equipment | 38.69 |
Miscellaneous | 4.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 823. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8703.00 | 57.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8710.67 | 49.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8684.00 | 76.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8723.50 | 36.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8714.00 | 46.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8708.17 | 51.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8715.83 | 44.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8690.33 | 69.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8684.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 76.00 | 0.00 | 0.00 | 0.00 |
Average | 8730.51 | 29.49 | 0.00 | 0.00 | 0.00 |
Sum | 157149.17 | 530.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8356.83 | 403.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8449.00 | 311.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8537.83 | 222.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8491.50 | 268.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8459.50 | 300.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8447.17 | 312.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8409.50 | 350.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8573.83 | 186.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8460.33 | 299.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8415.00 | 345.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8409.83 | 350.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8460.67 | 299.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8415.50 | 344.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8410.17 | 349.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8374.50 | 385.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8286.33 | 473.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8448.33 | 311.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8453.67 | 306.33 | 0.00 | 0.00 | 0.00 |
Min | 8286.33 | 186.17 | 0.00 | 0.00 | 0.00 |
Max | 8573.83 | 473.67 | 0.00 | 0.00 | 0.00 |
Average | 8436.64 | 323.36 | 0.00 | 0.00 | 0.00 |
Sum | 151859.50 | 5820.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128023.33 | 280.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128053.67 | 250.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128093.83 | 210.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24857.33 | 51.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13986.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24857.33 | 51.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13987.00 | 29.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24862.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 13992.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24555.00 | 354.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 13996.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24868.83 | 40.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10121.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24876.67 | 32.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13990.00 | 26.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128093.83 | 354.00 | 0.00 | 0.00 | 0.00 |
Average | 34062.30 | 81.04 | 0.00 | 0.00 | 0.00 |
Sum | 613121.33 | 1458.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.561546E+10 | 6298.48 | 06-JAN-08:57 | -35.6 | -35.7 | 0.157624E+10 | 2357.98 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.634266E+10 | 5960.54 | 10-FEB-17:00 | -12.8 | -14.1 | 0.152354E+10 | 2462.27 | 09-FEB-14:09 | -12.8 | -14.1 |
March | 0.818089E+10 | 9259.79 | 31-MAR-16:00 | 8.90 | 3.77 | 0.194896E+10 | 2608.22 | 30-MAR-13:20 | 8.90 | 3.77 |
April | 0.101656E+11 | 15203.00 | 20-APR-07:03 | -0.4 | -4.2 | 0.186669E+10 | 2608.31 | 28-APR-13:20 | 4.07 | -0.4 |
May | 0.163523E+11 | 31949.44 | 30-MAY-06:03 | 10.63 | 8.28 | 0.207323E+10 | 2608.19 | 09-MAY-09:00 | 10.63 | 8.28 |
June | 0.190988E+11 | 31939.18 | 26-JUN-06:03 | 17.30 | 15.84 | 0.206856E+10 | 2606.67 | 06-JUN-09:20 | 17.30 | 15.84 |
July | 0.201662E+11 | 34904.42 | 05-JUL-05:12 | 19.80 | 19.00 | 0.192538E+10 | 2711.97 | 05-JUL-10:00 | 24.40 | 23.25 |
August | 0.211133E+11 | 32539.98 | 28-AUG-06:02 | 14.08 | 13.35 | 0.215825E+10 | 2606.67 | 03-AUG-13:00 | 14.08 | 13.35 |
September | 0.167311E+11 | 34605.23 | 06-SEP-05:03 | 1.28 | 1.24 | 0.191544E+10 | 2606.66 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.117396E+11 | 15064.69 | 05-OCT-07:03 | 2.30 | 0.26 | 0.197207E+10 | 2608.36 | 06-OCT-13:20 | 5.97 | 5.15 |
November | 0.742335E+10 | 8980.41 | 02-NOV-07:40 | 3.90 | 2.94 | 0.182343E+10 | 2608.21 | 03-NOV-13:20 | 1.50 | -1.6 |
December | 0.645114E+10 | 5816.20 | 01-DEC-17:00 | -19.7 | -20.2 | 0.156541E+10 | 2440.35 | 01-DEC-14:09 | -19.7 | -20.2 |
Annual Sum or Average | 0.149380E+12 | 0.224172E+11 | ||||||||
Minimum of Months | 0.561546E+10 | 5816.20 | -35.6 | -35.7 | 0.152354E+10 | 2357.98 | -19.7 | -20.2 | ||
Maximum of Months | 0.211133E+11 | 34904.42 | 19.80 | 19.00 | 0.215825E+10 | 2711.97 | 24.40 | 23.25 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 158733.96 | 193.94 | 04-FEB-17:25 | 6.10 | 1.54 | 0.00 | 0.00 | 01-FEB-00:10 | 6.10 | 1.54 |
March | 44141242.57 | 1073.88 | 31-MAR-16:10 | 8.90 | 3.69 | 0.00 | 0.00 | 01-MAR-00:10 | 8.90 | 3.69 |
April | 0.706822E+09 | 4178.25 | 13-APR-14:50 | 19.82 | 7.99 | 0.00 | 0.00 | 01-APR-00:10 | 19.82 | 7.99 |
May | 0.281861E+10 | 8356.86 | 18-MAY-14:05 | 28.57 | 16.73 | 0.00 | 0.00 | 01-MAY-00:10 | 28.57 | 16.73 |
June | 0.424600E+10 | 9549.41 | 30-JUN-14:40 | 31.83 | 24.26 | 0.00 | 0.00 | 01-JUN-00:10 | 31.83 | 24.26 |
July | 0.496813E+10 | 9194.24 | 24-JUL-14:30 | 29.40 | 19.57 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.57 |
August | 0.352129E+10 | 8260.44 | 08-AUG-15:00 | 30.60 | 23.36 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.36 |
September | 0.140521E+10 | 6979.27 | 01-SEP-15:40 | 26.10 | 17.70 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.70 |
October | 0.240546E+09 | 2959.45 | 20-OCT-14:05 | 18.90 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 18.90 | 10.07 |
November | 3726343.04 | 537.01 | 01-NOV-17:00 | 16.70 | 12.79 | 0.00 | 0.00 | 01-NOV-00:10 | 16.70 | 12.79 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.179546E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.00 | 0.00 | -21.9 | -22.1 | ||
Maximum of Months | 0.496813E+10 | 9549.41 | 31.83 | 24.26 | 0.00 | 0.00 | 31.83 | 24.26 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11134064.20 | 3620.76 | 13-JAN-05:01 | -30.2 | -30.3 | 0.00 | 0.00 | 01-JAN-00:10 | -30.2 | -30.3 |
February | 6869347.12 | 3651.12 | 25-FEB-05:01 | -29.0 | -29.1 | 0.00 | 0.00 | 01-FEB-00:10 | -29.0 | -29.1 |
March | 27060544.92 | 2879.45 | 16-MAR-04:01 | -26.3 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.5 |
April | 0.212039E+09 | 1906.55 | 05-APR-05:01 | -13.4 | -13.9 | 0.00 | 0.00 | 01-APR-00:10 | -13.4 | -13.9 |
May | 0.143828E+10 | 3460.90 | 18-MAY-15:40 | 28.63 | 16.41 | 0.00 | 0.00 | 01-MAY-00:10 | 28.63 | 16.41 |
June | 0.249695E+10 | 4311.35 | 30-JUN-14:20 | 31.47 | 24.01 | 0.00 | 0.00 | 01-JUN-00:10 | 31.47 | 24.01 |
July | 0.310139E+10 | 6322.96 | 24-JUL-06:15 | 19.07 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 19.07 | 17.12 |
August | 0.236690E+10 | 3671.13 | 08-AUG-15:50 | 30.60 | 23.05 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.05 |
September | 0.916557E+09 | 3509.41 | 01-SEP-15:40 | 26.10 | 17.70 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.70 |
October | 0.133615E+09 | 2321.86 | 06-OCT-06:01 | -3.6 | -4.0 | 0.00 | 0.00 | 01-OCT-00:10 | -3.6 | -4.0 |
November | 7508429.20 | 2691.35 | 29-NOV-05:01 | -19.6 | -19.9 | 0.00 | 0.00 | 01-NOV-00:10 | -19.6 | -19.9 |
December | 10865219.91 | 3330.53 | 02-DEC-05:01 | -27.3 | -27.5 | 0.00 | 0.00 | 01-DEC-00:10 | -27.3 | -27.5 |
Annual Sum or Average | 0.107292E+11 | 0.00 | ||||||||
Minimum of Months | 6869347.12 | 1906.55 | -30.2 | -30.3 | 0.00 | 0.00 | -30.2 | -30.3 | ||
Maximum of Months | 0.310139E+10 | 6322.96 | 31.47 | 24.01 | 0.00 | 0.00 | 31.47 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139875E+09 | 3370.70 | 13-JAN-05:01 | -30.2 | -30.3 | 0.00 | 0.00 | 01-JAN-00:10 | -30.2 | -30.3 |
February | 0.135510E+09 | 3575.30 | 25-FEB-05:01 | -29.0 | -29.1 | 0.00 | 0.00 | 01-FEB-00:10 | -29.0 | -29.1 |
March | 0.185471E+09 | 3461.53 | 16-MAR-04:01 | -26.3 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.5 |
April | 0.475201E+09 | 3111.08 | 05-APR-05:01 | -13.4 | -13.9 | 0.00 | 0.00 | 01-APR-00:10 | -13.4 | -13.9 |
May | 0.163691E+10 | 3223.48 | 18-MAY-16:00 | 28.50 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 28.50 | 16.32 |
June | 0.255017E+10 | 4151.59 | 30-JUN-12:10 | 31.70 | 24.14 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.14 |
July | 0.329072E+10 | 5282.18 | 24-JUL-06:15 | 19.07 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 19.07 | 17.12 |
August | 0.285053E+10 | 3833.71 | 08-AUG-16:00 | 30.60 | 22.99 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 22.99 |
September | 0.149804E+10 | 3488.90 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.386616E+09 | 2310.77 | 25-OCT-06:08 | -4.2 | -4.4 | 0.00 | 0.00 | 01-OCT-00:10 | -4.2 | -4.4 |
November | 67642090.51 | 1958.98 | 29-NOV-05:01 | -19.6 | -19.9 | 0.00 | 0.00 | 01-NOV-00:10 | -19.6 | -19.9 |
December | 0.120692E+09 | 2880.56 | 01-DEC-17:10 | -19.9 | -20.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.9 | -20.4 |
Annual Sum or Average | 0.133374E+11 | 0.00 | ||||||||
Minimum of Months | 67642090.51 | 1958.98 | -30.2 | -30.3 | 0.00 | 0.00 | -30.2 | -30.3 | ||
Maximum of Months | 0.329072E+10 | 5282.18 | 31.70 | 24.14 | 0.00 | 0.00 | 31.70 | 24.14 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308821E+10 | 4975.60 | 27-JAN-16:33 | -15.9 | -16.8 | 0.148192E+10 | 2162.23 | 27-JAN-14:00 | -15.9 | -16.8 |
February | 0.390615E+10 | 5385.27 | 08-FEB-16:50 | 3.48 | -1.2 | 0.138475E+10 | 2244.47 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.627004E+10 | 6178.77 | 29-MAR-16:00 | 5.00 | 1.34 | 0.177166E+10 | 2531.52 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.806379E+10 | 10460.72 | 24-APR-16:00 | 8.90 | 4.89 | 0.176644E+10 | 2607.86 | 20-APR-09:39 | 8.90 | 4.89 |
May | 0.132155E+11 | 24677.95 | 30-MAY-06:03 | 10.63 | 8.28 | 0.205792E+10 | 2606.71 | 24-MAY-09:09 | 10.63 | 8.28 |
June | 0.155156E+11 | 26196.69 | 26-JUN-06:03 | 17.30 | 15.84 | 0.206451E+10 | 2606.66 | 06-JUN-09:20 | 17.30 | 15.84 |
July | 0.164636E+11 | 29468.96 | 31-JUL-05:12 | 14.97 | 13.44 | 0.192293E+10 | 2700.65 | 05-JUL-10:00 | 14.97 | 13.44 |
August | 0.163928E+11 | 27197.83 | 28-AUG-06:02 | 14.08 | 13.35 | 0.215460E+10 | 2606.66 | 25-AUG-09:20 | 14.08 | 13.35 |
September | 0.120848E+11 | 26910.95 | 05-SEP-06:01 | 6.05 | 5.72 | 0.190239E+10 | 2606.66 | 14-SEP-09:20 | 13.73 | 10.59 |
October | 0.831245E+10 | 10533.33 | 20-OCT-16:00 | 18.30 | 9.93 | 0.184902E+10 | 2608.05 | 03-OCT-13:50 | 18.30 | 9.93 |
November | 0.522908E+10 | 5959.27 | 17-NOV-15:50 | 10.10 | 3.24 | 0.160358E+10 | 2462.75 | 17-NOV-14:00 | 10.10 | 3.24 |
December | 0.350227E+10 | 4961.42 | 01-DEC-16:30 | -19.2 | -19.8 | 0.144072E+10 | 2193.86 | 01-DEC-14:00 | -19.2 | -19.8 |
Annual Sum or Average | 0.112044E+12 | 0.214004E+11 | ||||||||
Minimum of Months | 0.308821E+10 | 4961.42 | -19.2 | -19.8 | 0.138475E+10 | 2162.23 | -19.2 | -19.8 | ||
Maximum of Months | 0.164636E+11 | 29468.96 | 18.30 | 15.84 | 0.215460E+10 | 2700.65 | 18.30 | 15.84 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163944E+10 | 4603.87 | 27-JAN-16:30 | -15.6 | -16.5 | 0.145664E+10 | 2055.47 | 27-JAN-14:00 | -15.6 | -16.5 |
February | 0.240656E+10 | 5261.20 | 08-FEB-16:30 | 3.85 | -1.1 | 0.134205E+10 | 2226.86 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.447487E+10 | 6068.63 | 29-MAR-16:00 | 5.00 | 1.34 | 0.168566E+10 | 2483.82 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.714890E+10 | 10422.96 | 14-APR-16:00 | 15.00 | 6.77 | 0.169495E+10 | 2606.61 | 20-APR-13:20 | 9.60 | 2.32 |
May | 0.128399E+11 | 16155.59 | 18-MAY-15:30 | 28.70 | 16.46 | 0.204007E+10 | 2606.72 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.156248E+11 | 26484.79 | 26-JUN-06:03 | 17.30 | 15.84 | 0.205872E+10 | 2606.67 | 06-JUN-09:20 | 17.30 | 15.84 |
July | 0.165045E+11 | 29758.95 | 05-JUL-05:12 | 19.80 | 19.00 | 0.191916E+10 | 2668.55 | 05-JUL-10:00 | 24.40 | 23.25 |
August | 0.156766E+11 | 19560.38 | 28-AUG-06:02 | 14.08 | 13.35 | 0.214850E+10 | 2606.64 | 25-AUG-09:20 | 14.08 | 13.35 |
September | 0.106239E+11 | 15779.92 | 01-SEP-15:40 | 26.10 | 17.70 | 0.187086E+10 | 2606.65 | 14-SEP-09:20 | 13.73 | 10.59 |
October | 0.671573E+10 | 10124.71 | 20-OCT-16:00 | 18.30 | 9.93 | 0.172754E+10 | 2606.61 | 02-OCT-13:20 | 18.30 | 9.93 |
November | 0.364280E+10 | 5614.02 | 17-NOV-16:40 | 7.80 | 1.96 | 0.151718E+10 | 2360.89 | 17-NOV-14:00 | 7.80 | 1.96 |
December | 0.173564E+10 | 4476.85 | 28-DEC-16:10 | -2.2 | -3.9 | 0.140479E+10 | 2046.10 | 28-DEC-14:00 | -2.2 | -3.9 |
Annual Sum or Average | 0.990337E+11 | 0.208661E+11 | ||||||||
Minimum of Months | 0.163944E+10 | 4476.85 | -15.6 | -16.5 | 0.134205E+10 | 2046.10 | -15.6 | -16.5 | ||
Maximum of Months | 0.165045E+11 | 29758.95 | 28.70 | 19.00 | 0.214850E+10 | 2668.55 | 24.40 | 23.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6177144.80 | 798.05 | 28-JAN-17:02 | -7.8 | -9.1 | 0.301240E+09 | 406.70 | 05-JAN-14:50 | -7.8 | -9.1 |
February | 35707988.00 | 902.79 | 08-FEB-16:30 | 3.85 | -1.1 | 0.275672E+09 | 413.40 | 08-FEB-14:00 | 3.85 | -1.1 |
March | 0.266794E+09 | 1156.98 | 31-MAR-16:00 | 8.90 | 3.77 | 0.336681E+09 | 475.24 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.108489E+10 | 2508.16 | 18-APR-14:00 | 17.80 | 10.49 | 0.332350E+09 | 549.49 | 14-APR-13:20 | 17.80 | 10.49 |
May | 0.330295E+10 | 5319.77 | 18-MAY-14:50 | 28.83 | 16.63 | 0.422684E+09 | 549.51 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.465649E+10 | 7997.79 | 28-JUN-06:03 | 19.55 | 18.20 | 0.433550E+09 | 549.51 | 26-JUN-13:09 | 19.55 | 18.20 |
July | 0.499336E+10 | 9970.83 | 23-JUL-15:32 | 30.00 | 22.71 | 0.404623E+09 | 568.08 | 05-JUL-10:00 | 30.00 | 22.71 |
August | 0.407045E+10 | 5530.81 | 08-AUG-15:20 | 30.60 | 23.24 | 0.450579E+09 | 549.50 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.219531E+10 | 4619.95 | 01-SEP-15:40 | 26.10 | 17.70 | 0.379292E+09 | 549.50 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.952935E+09 | 1805.37 | 20-OCT-15:20 | 18.70 | 10.02 | 0.334482E+09 | 549.46 | 20-OCT-13:00 | 18.70 | 10.02 |
November | 0.171531E+09 | 1135.07 | 01-NOV-15:50 | 17.88 | 13.29 | 0.304018E+09 | 472.42 | 01-NOV-13:00 | 17.88 | 13.29 |
December | 7861521.18 | 804.63 | 16-DEC-17:02 | -5.9 | -6.6 | 0.291505E+09 | 406.69 | 19-DEC-10:00 | -24.2 | -24.7 |
Annual Sum or Average | 0.217445E+11 | 0.426667E+10 | ||||||||
Minimum of Months | 6177144.80 | 798.05 | -7.8 | -9.1 | 0.275672E+09 | 406.69 | -24.2 | -24.7 | ||
Maximum of Months | 0.499336E+10 | 9970.83 | 30.60 | 23.24 | 0.450579E+09 | 568.08 | 30.00 | 22.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5287527.10 | 492.15 | 28-JAN-17:02 | -7.8 | -9.1 | 0.192771E+09 | 257.49 | 05-JAN-14:39 | -7.8 | -9.1 |
February | 91236810.60 | 720.64 | 28-FEB-10:30 | -4.4 | -6.4 | 0.177046E+09 | 310.91 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.409538E+09 | 2360.10 | 31-MAR-09:50 | 1.42 | -1.1 | 0.227316E+09 | 347.88 | 27-MAR-09:20 | 1.42 | -1.1 |
April | 0.154417E+10 | 6107.20 | 18-APR-09:20 | 17.97 | 10.84 | 0.232459E+09 | 347.88 | 21-APR-09:09 | 6.47 | 0.20 |
May | 0.340008E+10 | 10164.44 | 21-MAY-10:02 | 14.40 | 8.55 | 0.274016E+09 | 347.90 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.481479E+10 | 13805.62 | 25-JUN-08:22 | 24.45 | 20.92 | 0.275533E+09 | 348.33 | 27-JUN-09:39 | 25.73 | 19.17 |
July | 0.524340E+10 | 13712.16 | 23-JUL-09:32 | 26.13 | 22.79 | 0.256657E+09 | 348.54 | 31-JUL-09:00 | 19.40 | 13.46 |
August | 0.398400E+10 | 10315.70 | 20-AUG-10:53 | 23.90 | 15.75 | 0.286826E+09 | 347.89 | 04-AUG-09:50 | 23.90 | 15.75 |
September | 0.225625E+10 | 7770.97 | 01-SEP-09:00 | 20.00 | 17.77 | 0.245916E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.781216E+09 | 3549.58 | 19-OCT-09:20 | 12.03 | 8.67 | 0.220208E+09 | 347.87 | 19-OCT-13:20 | 20.97 | 13.65 |
November | 0.184368E+09 | 743.49 | 16-NOV-10:10 | 2.15 | -0.3 | 0.195549E+09 | 316.62 | 16-NOV-10:20 | 2.60 | 0.02 |
December | 10320237.14 | 496.81 | 16-DEC-17:02 | -5.9 | -6.6 | 0.185923E+09 | 257.48 | 21-DEC-10:00 | -23.4 | -23.8 |
Annual Sum or Average | 0.227247E+11 | 0.277022E+10 | ||||||||
Minimum of Months | 5287527.10 | 492.15 | -7.8 | -9.1 | 0.177046E+09 | 257.48 | -23.4 | -23.8 | ||
Maximum of Months | 0.524340E+10 | 13805.62 | 26.13 | 22.79 | 0.286826E+09 | 348.54 | 25.73 | 19.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526456E+09 | 5524.57 | 27-JAN-13:40 | -14.8 | -15.9 | 0.325743E+09 | 549.50 | 06-JAN-14:20 | -14.8 | -15.9 |
February | 0.100142E+10 | 7931.05 | 28-FEB-13:35 | 3.33 | -0.5 | 0.309182E+09 | 549.50 | 27-FEB-14:00 | 3.33 | -0.5 |
March | 0.144613E+10 | 8919.93 | 31-MAR-14:00 | 8.30 | 3.10 | 0.376880E+09 | 550.11 | 24-MAR-13:20 | 8.30 | 3.10 |
April | 0.294620E+10 | 17547.25 | 23-APR-12:53 | 22.80 | 15.30 | 0.360908E+09 | 549.50 | 21-APR-13:20 | 22.80 | 15.30 |
May | 0.505186E+10 | 14516.23 | 21-MAY-13:23 | 20.30 | 10.93 | 0.426631E+09 | 550.23 | 17-MAY-13:50 | 20.30 | 10.93 |
June | 0.596624E+10 | 13339.78 | 25-JUN-11:02 | 27.62 | 22.13 | 0.432967E+09 | 550.00 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.684368E+10 | 17609.21 | 23-JUL-12:52 | 30.00 | 22.84 | 0.404471E+09 | 575.03 | 05-JUL-13:09 | 30.00 | 22.84 |
August | 0.651716E+10 | 17468.45 | 27-AUG-13:53 | 22.20 | 17.84 | 0.451890E+09 | 549.93 | 25-AUG-13:00 | 22.20 | 17.84 |
September | 0.459422E+10 | 17600.74 | 03-SEP-13:23 | 20.55 | 15.69 | 0.387683E+09 | 550.24 | 07-SEP-13:50 | 23.90 | 14.43 |
October | 0.238920E+10 | 17783.71 | 22-OCT-13:22 | 18.85 | 12.94 | 0.357329E+09 | 549.74 | 20-OCT-13:00 | 18.85 | 12.94 |
November | 0.918392E+09 | 7318.25 | 17-NOV-13:03 | 10.10 | 3.25 | 0.331189E+09 | 549.94 | 07-NOV-14:09 | 10.10 | 3.25 |
December | 0.278923E+09 | 3026.52 | 02-DEC-13:30 | -18.6 | -19.3 | 0.305674E+09 | 549.50 | 26-DEC-14:20 | -19.3 | -20.0 |
Annual Sum or Average | 0.384799E+11 | 0.447055E+10 | ||||||||
Minimum of Months | 0.278923E+09 | 3026.52 | -18.6 | -19.3 | 0.305674E+09 | 549.50 | -19.3 | -20.0 | ||
Maximum of Months | 0.684368E+10 | 17783.71 | 30.00 | 22.84 | 0.451890E+09 | 575.03 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45021903.77 | 740.04 | 27-JAN-16:00 | -14.4 | -15.6 | 0.194058E+09 | 310.38 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.160365E+09 | 2005.88 | 08-FEB-16:30 | 3.85 | -1.1 | 0.180439E+09 | 342.20 | 28-FEB-14:00 | 6.10 | 1.55 |
March | 0.491453E+09 | 4448.39 | 31-MAR-16:00 | 8.90 | 3.77 | 0.221983E+09 | 347.71 | 31-MAR-13:00 | 8.90 | 3.77 |
April | 0.157161E+10 | 14721.28 | 23-APR-16:12 | 26.50 | 16.86 | 0.217071E+09 | 347.84 | 20-APR-13:20 | 26.50 | 16.86 |
May | 0.367644E+10 | 15541.63 | 21-MAY-16:42 | 22.15 | 11.20 | 0.268874E+09 | 347.86 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.445170E+10 | 14783.39 | 04-JUN-15:42 | 21.10 | 11.66 | 0.274284E+09 | 347.86 | 26-JUN-13:09 | 25.78 | 17.07 |
July | 0.496222E+10 | 15232.25 | 16-JUL-16:22 | 21.95 | 16.03 | 0.256193E+09 | 348.10 | 05-JUL-13:00 | 21.95 | 16.03 |
August | 0.406284E+10 | 14297.41 | 05-AUG-17:04 | 22.70 | 14.24 | 0.285872E+09 | 347.86 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.223409E+10 | 12626.83 | 03-SEP-16:02 | 21.70 | 15.87 | 0.242192E+09 | 347.85 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.899854E+09 | 5042.94 | 19-OCT-16:00 | 21.70 | 13.55 | 0.217768E+09 | 347.85 | 02-OCT-13:20 | 21.70 | 13.55 |
November | 0.181199E+09 | 1249.62 | 17-NOV-15:40 | 10.20 | 3.28 | 0.196908E+09 | 340.35 | 17-NOV-14:00 | 10.20 | 3.28 |
December | 19868294.08 | 570.86 | 20-DEC-15:40 | -19.8 | -20.5 | 0.185959E+09 | 262.06 | 28-DEC-14:00 | -1.7 | -3.7 |
Annual Sum or Average | 0.227567E+11 | 0.274160E+10 | ||||||||
Minimum of Months | 19868294.08 | 570.86 | -19.8 | -20.5 | 0.180439E+09 | 262.06 | -14.8 | -15.9 | ||
Maximum of Months | 0.496222E+10 | 15541.63 | 26.50 | 16.86 | 0.285872E+09 | 348.10 | 26.50 | 17.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6816304.59 | 804.84 | 28-JAN-17:02 | -7.8 | -9.1 | 0.298173E+09 | 406.70 | 05-JAN-14:09 | -7.8 | -9.1 |
February | 8922070.27 | 806.80 | 11-FEB-17:03 | -7.1 | -8.6 | 0.275845E+09 | 406.68 | 02-FEB-10:09 | -7.1 | -8.6 |
March | 98793147.23 | 948.53 | 31-MAR-16:00 | 8.90 | 3.77 | 0.332207E+09 | 421.05 | 31-MAR-13:00 | 8.90 | 3.77 |
April | 0.690107E+09 | 1413.78 | 23-APR-17:11 | 25.93 | 16.61 | 0.308986E+09 | 490.25 | 14-APR-13:09 | 25.93 | 16.61 |
May | 0.202389E+10 | 3188.49 | 26-MAY-13:30 | 22.50 | 17.44 | 0.407079E+09 | 549.51 | 24-MAY-09:09 | 22.50 | 17.44 |
June | 0.304776E+10 | 4558.62 | 29-JUN-15:00 | 34.40 | 24.01 | 0.430939E+09 | 549.50 | 06-JUN-09:20 | 34.40 | 24.01 |
July | 0.380358E+10 | 6347.93 | 24-JUL-06:03 | 18.68 | 16.82 | 0.404160E+09 | 565.87 | 05-JUL-10:00 | 18.68 | 16.82 |
August | 0.356727E+10 | 4425.04 | 09-AUG-15:30 | 27.25 | 21.19 | 0.452000E+09 | 549.50 | 25-AUG-09:20 | 21.33 | 17.19 |
September | 0.221118E+10 | 3716.49 | 01-SEP-15:40 | 26.10 | 17.70 | 0.391000E+09 | 549.50 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.134012E+10 | 1679.40 | 22-OCT-14:53 | 19.40 | 12.77 | 0.352366E+09 | 549.49 | 02-OCT-13:20 | 19.40 | 12.77 |
November | 0.336003E+09 | 1149.28 | 01-NOV-15:30 | 18.05 | 13.35 | 0.307995E+09 | 481.69 | 01-NOV-13:00 | 18.05 | 13.35 |
December | 9495330.06 | 819.47 | 16-DEC-17:02 | -5.9 | -6.6 | 0.291373E+09 | 406.69 | 18-DEC-14:30 | -22.8 | -23.5 |
Annual Sum or Average | 0.171439E+11 | 0.425212E+10 | ||||||||
Minimum of Months | 6816304.59 | 804.84 | -7.8 | -9.1 | 0.275845E+09 | 406.68 | -22.8 | -23.5 | ||
Maximum of Months | 0.380358E+10 | 6347.93 | 34.40 | 24.01 | 0.452000E+09 | 565.87 | 34.40 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5131781.30 | 544.29 | 20-JAN-07:03 | -7.3 | -7.9 | 0.193003E+09 | 257.49 | 05-JAN-14:09 | -7.3 | -7.9 |
February | 53322712.76 | 612.32 | 28-FEB-10:25 | -4.4 | -6.4 | 0.175982E+09 | 278.86 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.250614E+09 | 829.80 | 31-MAR-10:05 | 2.07 | -0.7 | 0.219899E+09 | 344.75 | 31-MAR-09:00 | 2.07 | -0.7 |
April | 0.102349E+10 | 3341.08 | 18-APR-09:30 | 18.05 | 10.95 | 0.225343E+09 | 347.88 | 18-APR-09:20 | 18.05 | 10.95 |
May | 0.230319E+10 | 6870.16 | 17-MAY-06:02 | 11.65 | 8.33 | 0.272568E+09 | 347.89 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.365408E+10 | 11245.09 | 25-JUN-08:51 | 25.00 | 21.06 | 0.275372E+09 | 347.88 | 06-JUN-09:09 | 25.00 | 21.06 |
July | 0.446392E+10 | 8417.70 | 18-JUL-06:02 | 11.23 | 10.70 | 0.256831E+09 | 350.12 | 05-JUL-13:09 | 11.23 | 10.70 |
August | 0.376346E+10 | 8371.41 | 21-AUG-06:02 | 12.77 | 12.43 | 0.287706E+09 | 347.88 | 04-AUG-09:00 | 12.77 | 12.43 |
September | 0.236595E+10 | 5848.92 | 05-SEP-08:30 | 11.65 | 8.65 | 0.251762E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.102788E+10 | 2750.36 | 19-OCT-08:40 | 10.37 | 7.57 | 0.235201E+09 | 347.88 | 25-OCT-09:50 | 2.75 | 2.54 |
November | 0.314294E+09 | 756.16 | 17-NOV-10:10 | 3.87 | 0.38 | 0.199848E+09 | 321.96 | 17-NOV-10:30 | 5.00 | 1.00 |
December | 13279046.59 | 549.56 | 01-DEC-09:45 | -21.0 | -21.2 | 0.186342E+09 | 260.54 | 01-DEC-10:09 | -20.6 | -20.9 |
Annual Sum or Average | 0.192386E+11 | 0.277986E+10 | ||||||||
Minimum of Months | 5131781.30 | 544.29 | -21.0 | -21.2 | 0.175982E+09 | 257.49 | -20.6 | -20.9 | ||
Maximum of Months | 0.446392E+10 | 11245.09 | 25.00 | 21.06 | 0.287706E+09 | 350.12 | 25.00 | 21.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42109428.90 | 999.70 | 21-JAN-12:00 | -10.0 | -10.7 | 0.270606E+09 | 428.41 | 27-JAN-14:50 | -14.4 | -15.6 |
February | 0.195530E+09 | 1293.96 | 28-FEB-15:10 | 6.10 | 1.55 | 0.262081E+09 | 541.09 | 28-FEB-14:00 | 6.10 | 1.55 |
March | 0.293295E+09 | 2159.79 | 31-MAR-14:30 | 8.30 | 2.87 | 0.326076E+09 | 549.51 | 31-MAR-13:50 | 8.30 | 2.87 |
April | 0.113774E+10 | 6191.31 | 23-APR-14:32 | 25.20 | 16.35 | 0.324974E+09 | 549.51 | 19-APR-13:20 | 25.20 | 16.35 |
May | 0.280613E+10 | 9506.80 | 18-MAY-12:00 | 27.80 | 16.87 | 0.402495E+09 | 549.52 | 16-MAY-13:20 | 27.80 | 16.87 |
June | 0.392907E+10 | 12042.47 | 29-JUN-16:10 | 34.90 | 24.48 | 0.422106E+09 | 563.96 | 30-JUN-12:09 | 31.70 | 24.14 |
July | 0.533745E+10 | 11243.36 | 24-JUL-12:00 | 28.30 | 19.76 | 0.401379E+09 | 567.05 | 05-JUL-13:09 | 28.30 | 19.76 |
August | 0.545889E+10 | 13254.48 | 27-AUG-14:32 | 22.93 | 18.30 | 0.445923E+09 | 549.94 | 22-AUG-13:50 | 22.93 | 18.30 |
September | 0.374539E+10 | 14041.27 | 03-SEP-13:52 | 21.10 | 15.89 | 0.378498E+09 | 549.90 | 07-SEP-13:00 | 23.90 | 14.48 |
October | 0.179657E+10 | 14213.91 | 22-OCT-14:53 | 19.40 | 12.77 | 0.349573E+09 | 549.58 | 20-OCT-13:00 | 19.40 | 12.77 |
November | 0.368495E+09 | 4211.26 | 17-NOV-13:30 | 10.30 | 3.32 | 0.308644E+09 | 549.50 | 17-NOV-14:09 | 10.60 | 3.43 |
December | 86077008.98 | 1737.97 | 02-DEC-13:40 | -18.4 | -19.2 | 0.266563E+09 | 406.65 | 19-DEC-10:00 | -24.2 | -24.7 |
Annual Sum or Average | 0.251967E+11 | 0.415892E+10 | ||||||||
Minimum of Months | 42109428.90 | 999.70 | -18.4 | -19.2 | 0.262081E+09 | 406.65 | -24.2 | -24.7 | ||
Maximum of Months | 0.545889E+10 | 14213.91 | 34.90 | 24.48 | 0.445923E+09 | 567.05 | 31.70 | 24.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30745839.31 | 661.09 | 27-JAN-16:00 | -14.4 | -15.6 | 0.193565E+09 | 286.17 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 87089401.59 | 813.74 | 08-FEB-16:40 | 3.67 | -1.2 | 0.177968E+09 | 332.55 | 08-FEB-16:49 | 3.48 | -1.2 |
March | 0.267087E+09 | 2282.65 | 28-MAR-17:20 | 7.20 | 3.26 | 0.216584E+09 | 338.67 | 31-MAR-15:39 | 8.70 | 3.39 |
April | 0.951026E+09 | 10674.00 | 23-APR-17:11 | 25.93 | 16.61 | 0.211839E+09 | 347.83 | 24-APR-13:00 | 8.30 | 4.56 |
May | 0.244654E+10 | 11461.30 | 21-MAY-16:42 | 22.15 | 11.20 | 0.267411E+09 | 347.86 | 24-MAY-09:20 | 22.57 | 16.40 |
June | 0.321009E+10 | 9496.52 | 17-JUN-18:22 | 23.05 | 13.03 | 0.273895E+09 | 347.86 | 06-JUN-09:20 | 23.05 | 13.03 |
July | 0.415911E+10 | 11542.28 | 16-JUL-16:41 | 21.38 | 15.74 | 0.256790E+09 | 350.47 | 05-JUL-13:39 | 21.38 | 15.74 |
August | 0.378884E+10 | 10593.73 | 05-AUG-17:04 | 22.70 | 14.24 | 0.287399E+09 | 347.86 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.226688E+10 | 12371.74 | 03-SEP-17:12 | 21.33 | 15.90 | 0.250980E+09 | 347.85 | 14-SEP-09:20 | 13.73 | 10.59 |
October | 0.110818E+10 | 4149.15 | 19-OCT-16:00 | 21.70 | 13.55 | 0.233160E+09 | 347.85 | 02-OCT-13:20 | 21.70 | 13.55 |
November | 0.296238E+09 | 1019.68 | 17-NOV-15:40 | 10.20 | 3.28 | 0.199285E+09 | 338.66 | 17-NOV-15:50 | 10.10 | 3.24 |
December | 16958101.47 | 557.00 | 08-DEC-15:30 | -10.9 | -12.0 | 0.186358E+09 | 258.05 | 08-DEC-14:00 | -10.9 | -12.0 |
Annual Sum or Average | 0.186288E+11 | 0.275523E+10 | ||||||||
Minimum of Months | 16958101.47 | 557.00 | -14.4 | -15.6 | 0.177968E+09 | 258.05 | -14.8 | -15.9 | ||
Maximum of Months | 0.415911E+10 | 12371.74 | 25.93 | 16.61 | 0.287399E+09 | 350.47 | 23.05 | 16.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7449432.86 | 790.05 | 28-JAN-17:02 | -7.8 | -9.1 | 0.302984E+09 | 406.70 | 05-JAN-14:00 | -7.8 | -9.1 |
February | 53435458.45 | 905.06 | 08-FEB-15:10 | 4.90 | -0.6 | 0.277075E+09 | 420.18 | 08-FEB-14:00 | 4.90 | -0.6 |
March | 0.409608E+09 | 1155.82 | 29-MAR-15:40 | 4.80 | 1.35 | 0.340751E+09 | 487.16 | 29-MAR-13:00 | 4.80 | 1.35 |
April | 0.128108E+10 | 2420.57 | 14-APR-15:30 | 15.00 | 6.90 | 0.343282E+09 | 549.49 | 14-APR-13:20 | 15.00 | 6.90 |
May | 0.336310E+10 | 4922.36 | 26-MAY-13:30 | 22.50 | 17.44 | 0.428632E+09 | 549.51 | 24-MAY-09:09 | 22.50 | 17.44 |
June | 0.463041E+10 | 7504.68 | 28-JUN-06:03 | 19.55 | 18.20 | 0.435024E+09 | 550.47 | 28-JUN-13:20 | 30.00 | 21.52 |
July | 0.496013E+10 | 8845.50 | 23-JUL-16:41 | 28.58 | 21.92 | 0.405715E+09 | 587.23 | 05-JUL-13:09 | 28.58 | 21.92 |
August | 0.419896E+10 | 5099.93 | 08-AUG-15:30 | 30.60 | 23.17 | 0.452975E+09 | 549.50 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.242496E+10 | 4303.28 | 01-SEP-15:40 | 26.10 | 17.70 | 0.391878E+09 | 549.50 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.128830E+10 | 1973.32 | 02-OCT-13:10 | 10.92 | 9.77 | 0.353981E+09 | 549.49 | 02-OCT-13:20 | 10.73 | 9.70 |
November | 0.339500E+09 | 1152.48 | 01-NOV-15:40 | 17.97 | 13.32 | 0.308204E+09 | 491.26 | 01-NOV-13:00 | 17.97 | 13.32 |
December | 9351300.54 | 794.50 | 16-DEC-17:02 | -5.9 | -6.6 | 0.292927E+09 | 406.68 | 19-DEC-10:00 | -24.2 | -24.7 |
Annual Sum or Average | 0.229663E+11 | 0.433343E+10 | ||||||||
Minimum of Months | 7449432.86 | 790.05 | -7.8 | -9.1 | 0.277075E+09 | 406.68 | -24.2 | -24.7 | ||
Maximum of Months | 0.496013E+10 | 8845.50 | 30.60 | 23.17 | 0.452975E+09 | 587.23 | 30.00 | 21.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18119064.96 | 569.19 | 19-JAN-13:03 | -2.8 | -3.4 | 0.141326E+09 | 256.27 | 25-JAN-09:00 | -23.3 | -23.6 |
February | 0.103765E+09 | 777.01 | 28-FEB-10:00 | -6.1 | -7.7 | 0.131036E+09 | 326.95 | 28-FEB-11:09 | -2.4 | -4.8 |
March | 0.455294E+09 | 4174.15 | 31-MAR-10:05 | 2.07 | -0.7 | 0.170108E+09 | 356.60 | 23-MAR-10:09 | 2.07 | -0.7 |
April | 0.161129E+10 | 6789.58 | 18-APR-10:05 | 18.12 | 11.26 | 0.175248E+09 | 356.46 | 18-APR-10:09 | 18.12 | 11.26 |
May | 0.333242E+10 | 11206.84 | 14-MAY-08:43 | 10.07 | 3.57 | 0.204120E+09 | 356.47 | 25-MAY-10:09 | 21.83 | 16.93 |
June | 0.463680E+10 | 15163.94 | 25-JUN-08:11 | 24.27 | 20.87 | 0.204605E+09 | 356.47 | 13-JUN-10:09 | 24.27 | 20.87 |
July | 0.503650E+10 | 14684.83 | 23-JUL-10:01 | 26.97 | 23.13 | 0.191175E+09 | 357.66 | 05-JUL-12:09 | 26.97 | 23.13 |
August | 0.390899E+10 | 12118.59 | 06-AUG-08:42 | 17.93 | 13.93 | 0.213021E+09 | 356.47 | 04-AUG-10:09 | 17.93 | 13.93 |
September | 0.233610E+10 | 7960.08 | 01-SEP-10:05 | 21.97 | 17.75 | 0.185389E+09 | 356.46 | 06-SEP-10:09 | 14.78 | 10.33 |
October | 0.884813E+09 | 5542.27 | 25-OCT-12:01 | 10.10 | 6.54 | 0.170925E+09 | 356.46 | 19-OCT-10:09 | 10.10 | 6.54 |
November | 0.232755E+09 | 820.52 | 16-NOV-09:45 | 1.32 | -0.7 | 0.147378E+09 | 339.62 | 17-NOV-11:09 | 7.07 | 2.03 |
December | 21057497.97 | 582.78 | 01-DEC-10:00 | -20.8 | -21.1 | 0.136446E+09 | 262.10 | 01-DEC-09:00 | -20.8 | -21.1 |
Annual Sum or Average | 0.225779E+11 | 0.207078E+10 | ||||||||
Minimum of Months | 18119064.96 | 569.19 | -20.8 | -21.1 | 0.131036E+09 | 256.27 | -23.3 | -23.6 | ||
Maximum of Months | 0.503650E+10 | 15163.94 | 26.97 | 23.13 | 0.213021E+09 | 357.66 | 26.97 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670357E+09 | 6304.43 | 27-JAN-13:40 | -14.8 | -15.9 | 0.330484E+09 | 549.50 | 06-JAN-14:20 | -14.8 | -15.9 |
February | 0.119160E+10 | 8217.52 | 28-FEB-13:35 | 3.33 | -0.5 | 0.315006E+09 | 550.02 | 28-FEB-10:50 | 3.33 | -0.5 |
March | 0.176254E+10 | 9248.92 | 31-MAR-13:40 | 7.77 | 2.77 | 0.384613E+09 | 549.50 | 20-MAR-13:00 | 7.77 | 2.77 |
April | 0.323419E+10 | 17048.02 | 23-APR-13:22 | 23.60 | 15.70 | 0.370238E+09 | 550.12 | 13-APR-13:20 | 23.60 | 15.70 |
May | 0.513870E+10 | 11245.80 | 21-MAY-12:13 | 18.37 | 10.32 | 0.431507E+09 | 550.84 | 25-MAY-13:20 | 27.07 | 19.13 |
June | 0.590737E+10 | 16574.01 | 25-JUN-11:32 | 27.07 | 21.57 | 0.434717E+09 | 551.02 | 26-JUN-13:20 | 25.97 | 17.06 |
July | 0.676408E+10 | 17311.35 | 23-JUL-12:42 | 29.72 | 22.78 | 0.405703E+09 | 590.52 | 05-JUL-13:09 | 29.72 | 22.78 |
August | 0.665287E+10 | 16350.90 | 27-AUG-13:43 | 22.02 | 17.72 | 0.453911E+09 | 550.78 | 22-AUG-13:20 | 22.02 | 17.72 |
September | 0.498471E+10 | 17101.72 | 03-SEP-13:52 | 21.10 | 15.89 | 0.396340E+09 | 557.88 | 01-SEP-13:20 | 21.10 | 15.89 |
October | 0.288755E+10 | 16829.43 | 22-OCT-13:22 | 18.85 | 12.94 | 0.374859E+09 | 550.44 | 26-OCT-13:39 | 14.23 | 8.58 |
November | 0.121722E+10 | 8125.35 | 17-NOV-13:03 | 10.10 | 3.25 | 0.340478E+09 | 550.04 | 10-NOV-10:39 | 10.10 | 3.25 |
December | 0.385494E+09 | 3963.26 | 02-DEC-13:30 | -18.6 | -19.3 | 0.309974E+09 | 549.50 | 20-DEC-14:20 | -19.8 | -20.5 |
Annual Sum or Average | 0.407967E+11 | 0.454783E+10 | ||||||||
Minimum of Months | 0.385494E+09 | 3963.26 | -18.6 | -19.3 | 0.309974E+09 | 549.50 | -19.8 | -20.5 | ||
Maximum of Months | 0.676408E+10 | 17311.35 | 29.72 | 22.78 | 0.453911E+09 | 590.52 | 29.72 | 22.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59453581.65 | 777.79 | 27-JAN-16:00 | -14.4 | -15.6 | 0.194912E+09 | 321.26 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.189614E+09 | 2060.44 | 08-FEB-16:30 | 3.85 | -1.1 | 0.181817E+09 | 345.11 | 28-FEB-14:00 | 6.10 | 1.55 |
March | 0.605601E+09 | 4554.05 | 31-MAR-16:00 | 8.90 | 3.77 | 0.225276E+09 | 347.83 | 31-MAR-13:00 | 8.90 | 3.77 |
April | 0.171201E+10 | 15279.68 | 23-APR-16:41 | 26.20 | 16.72 | 0.223839E+09 | 347.85 | 18-APR-09:00 | 26.20 | 16.72 |
May | 0.370906E+10 | 15138.96 | 14-MAY-17:11 | 20.00 | 8.46 | 0.272354E+09 | 347.86 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.440423E+10 | 13518.76 | 17-JUN-17:04 | 23.90 | 13.28 | 0.275319E+09 | 347.86 | 06-JUN-13:20 | 23.90 | 13.28 |
July | 0.490855E+10 | 15133.65 | 23-JUL-16:41 | 28.58 | 21.92 | 0.256870E+09 | 351.93 | 05-JUL-13:09 | 28.58 | 21.92 |
August | 0.414249E+10 | 14207.74 | 27-AUG-17:42 | 22.80 | 19.07 | 0.287181E+09 | 347.86 | 10-AUG-13:00 | 22.80 | 19.07 |
September | 0.243585E+10 | 14875.83 | 03-SEP-17:12 | 21.33 | 15.90 | 0.249205E+09 | 347.86 | 14-SEP-09:20 | 13.73 | 10.59 |
October | 0.115114E+10 | 6204.11 | 22-OCT-15:23 | 19.15 | 12.57 | 0.229063E+09 | 348.00 | 03-OCT-13:50 | 19.15 | 12.57 |
November | 0.299467E+09 | 1513.43 | 17-NOV-15:40 | 10.20 | 3.28 | 0.200475E+09 | 347.83 | 17-NOV-14:00 | 10.20 | 3.28 |
December | 31478847.88 | 617.49 | 20-DEC-15:40 | -19.8 | -20.5 | 0.186442E+09 | 274.10 | 20-DEC-15:50 | -20.0 | -20.7 |
Annual Sum or Average | 0.236489E+11 | 0.278275E+10 | ||||||||
Minimum of Months | 31478847.88 | 617.49 | -19.8 | -20.5 | 0.181817E+09 | 274.10 | -20.0 | -20.7 | ||
Maximum of Months | 0.490855E+10 | 15279.68 | 28.58 | 21.92 | 0.287181E+09 | 351.93 | 28.58 | 21.92 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853578E+09 | 19281.67 | 02-JAN-05:01 | -18.2 |
February | 39951267.07 | 16371.30 | 27-FEB-06:01 | -18.5 |
March | 12562923.13 | 15078.24 | 06-MAR-06:01 | -19.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 9964234.75 | 15697.97 | 27-NOV-07:11 | -6.7 |
December | 0.225222E+09 | 16766.44 | 26-DEC-06:01 | -26.7 |
Annual Sum or Average | 0.114128E+10 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.853578E+09 | 19281.67 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.993506E+10 | 17120.58 | 06-JAN-06:13 | -34.6 |
February | 0.635742E+10 | 16629.44 | 14-FEB-06:13 | -32.2 |
March | 0.410470E+10 | 15068.97 | 06-MAR-06:13 | -19.1 |
April | 0.137040E+10 | 10447.46 | 05-APR-06:01 | -13.5 |
May | 0.384784E+09 | 5135.70 | 01-MAY-06:01 | -3.5 |
June | 0.149403E+09 | 3363.73 | 04-JUN-08:22 | 14.20 |
July | 0.113955E+09 | 3357.15 | 02-JUL-06:30 | 12.25 |
August | 0.168291E+09 | 3298.11 | 06-AUG-08:23 | 17.20 |
September | 0.489369E+09 | 3592.57 | 10-SEP-08:13 | 11.10 |
October | 0.144520E+10 | 11337.90 | 30-OCT-05:13 | -9.8 |
November | 0.404525E+10 | 13764.89 | 25-NOV-06:13 | -19.4 |
December | 0.906348E+10 | 16750.00 | 20-DEC-06:13 | -29.0 |
Annual Sum or Average | 0.376273E+11 | |||
Minimum of Months | 0.113955E+09 | 3298.11 | -34.6 | |
Maximum of Months | 0.993506E+10 | 17120.58 | 17.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.409587E+10 | 10607.65 | 02-JAN-07:04 | -18.1 |
February | 0.260806E+10 | 7802.78 | 13-FEB-06:05 | -24.0 |
March | 0.190996E+10 | 7310.11 | 06-MAR-07:02 | -19.3 |
April | 0.787386E+09 | 6339.24 | 23-APR-16:01 | 26.60 |
May | 0.124517E+09 | 4502.66 | 14-MAY-15:13 | 20.00 |
June | 22897458.64 | 3846.30 | 04-JUN-15:13 | 21.10 |
July | 28128594.73 | 3930.80 | 23-JUL-16:01 | 29.72 |
August | 31195353.51 | 3812.43 | 27-AUG-15:02 | 23.40 |
September | 0.122674E+09 | 4945.71 | 03-SEP-15:52 | 21.70 |
October | 0.797407E+09 | 6170.27 | 09-OCT-13:13 | 5.77 |
November | 0.194030E+10 | 8045.25 | 27-NOV-07:11 | -6.7 |
December | 0.364391E+10 | 10606.25 | 26-DEC-07:05 | -26.5 |
Annual Sum or Average | 0.161123E+11 | |||
Minimum of Months | 22897458.64 | 3812.43 | -26.5 | |
Maximum of Months | 0.409587E+10 | 10607.65 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301640E+10 | 8506.66 | 02-JAN-08:30 | -19.7 |
February | 0.174561E+10 | 4170.81 | 27-FEB-07:01 | -19.2 |
March | 0.125980E+10 | 4097.37 | 06-MAR-07:01 | -19.3 |
April | 0.402113E+09 | 2136.87 | 10-APR-07:10 | -0.2 |
May | 38040468.10 | 1764.61 | 21-MAY-16:02 | 22.35 |
June | 8296149.50 | 1749.84 | 25-JUN-11:32 | 27.07 |
July | 14469405.60 | 1663.79 | 09-JUL-14:43 | 17.93 |
August | 18303290.16 | 2049.27 | 27-AUG-14:32 | 22.93 |
September | 23023719.35 | 3008.14 | 03-SEP-15:52 | 21.70 |
October | 0.385103E+09 | 2951.69 | 22-OCT-12:13 | 17.23 |
November | 0.128042E+10 | 4491.78 | 27-NOV-07:02 | -6.7 |
December | 0.260053E+10 | 7173.99 | 26-DEC-06:07 | -26.7 |
Annual Sum or Average | 0.107921E+11 | |||
Minimum of Months | 8296149.50 | 1663.79 | -26.7 | |
Maximum of Months | 0.301640E+10 | 8506.66 | 27.07 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244501E+10 | 24512.39 | 02-JAN-05:01 | -18.2 |
February | 0.632795E+09 | 21878.82 | 27-FEB-06:01 | -18.5 |
March | 0.226437E+09 | 21951.58 | 06-MAR-06:01 | -19.0 |
April | 15239189.51 | 19600.59 | 10-APR-06:01 | -1.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 5122744.13 | 19135.07 | 30-OCT-06:01 | -9.4 |
November | 0.439966E+09 | 21967.88 | 27-NOV-06:01 | -7.1 |
December | 0.165749E+10 | 24102.50 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.542206E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.244501E+10 | 24512.39 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740355E+10 | 29796.86 | 01-JAN-23:22 | -21.4 |
February | 0.364604E+10 | 28951.70 | 13-FEB-05:01 | -23.4 |
March | 0.165383E+10 | 28843.85 | 06-MAR-05:11 | -18.5 |
April | 0.272769E+09 | 26223.56 | 03-APR-05:01 | -4.3 |
May | 2554161.12 | 23352.58 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.193347E+09 | 26511.58 | 30-OCT-05:01 | -9.9 |
November | 0.215568E+10 | 28828.65 | 27-NOV-05:11 | -7.2 |
December | 0.623969E+10 | 29693.44 | 26-DEC-04:42 | -25.6 |
Annual Sum or Average | 0.215675E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.740355E+10 | 29796.86 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.953689E+10 | 10162.07 | 01-JAN-22:02 | -23.0 |
February | 0.590879E+10 | 10153.67 | 13-FEB-03:42 | -22.7 |
March | 0.340923E+10 | 9836.47 | 06-MAR-04:32 | -17.9 |
April | 0.615567E+09 | 9150.90 | 03-APR-04:11 | -5.2 |
May | 11477261.93 | 7839.20 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 1738630.50 | 3616.22 | 23-SEP-06:03 | 4.32 |
October | 0.510452E+09 | 9256.25 | 30-OCT-04:01 | -10.0 |
November | 0.322358E+10 | 9424.38 | 26-NOV-21:53 | -6.1 |
December | 0.879044E+10 | 10178.19 | 24-DEC-12:02 | -26.9 |
Annual Sum or Average | 0.320082E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.9 | |
Maximum of Months | 0.953689E+10 | 10178.19 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.575849E+10 | 12510.63 | 23-JAN-05:11 | -22.8 |
February | 0.317921E+10 | 12449.28 | 13-FEB-03:42 | -22.7 |
March | 0.169820E+10 | 11977.91 | 06-MAR-04:32 | -17.9 |
April | 0.254256E+09 | 11237.71 | 03-APR-04:11 | -5.2 |
May | 1156978.30 | 7223.80 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 1012118.41 | 2053.65 | 23-SEP-06:03 | 4.32 |
October | 0.286454E+09 | 11461.04 | 30-OCT-04:01 | -10.0 |
November | 0.191215E+10 | 11614.20 | 27-NOV-05:11 | -7.2 |
December | 0.542287E+10 | 12425.49 | 24-DEC-20:42 | -26.5 |
Annual Sum or Average | 0.185138E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.5 | |
Maximum of Months | 0.575849E+10 | 12510.63 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.659309E+10 | 16205.38 | 23-JAN-05:11 | -22.8 |
February | 0.365223E+10 | 16158.45 | 13-FEB-03:42 | -22.7 |
March | 0.221469E+10 | 15567.39 | 06-MAR-04:32 | -17.9 |
April | 0.460981E+09 | 14483.00 | 03-APR-04:11 | -5.2 |
May | 12320079.19 | 11959.53 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 1131190.32 | 2562.49 | 23-SEP-06:03 | 4.32 |
October | 0.383334E+09 | 14804.41 | 30-OCT-04:01 | -10.0 |
November | 0.232941E+10 | 15098.18 | 27-NOV-05:11 | -7.2 |
December | 0.642887E+10 | 16105.69 | 26-DEC-04:42 | -25.6 |
Annual Sum or Average | 0.220761E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.659309E+10 | 16205.38 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.592193E+10 | 13571.31 | 23-JAN-05:11 | -22.8 |
February | 0.344825E+10 | 13503.35 | 13-FEB-03:42 | -22.7 |
March | 0.191285E+10 | 12993.56 | 06-MAR-04:32 | -17.9 |
April | 0.351100E+09 | 12140.14 | 03-APR-04:11 | -5.2 |
May | 8785675.49 | 9955.71 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 892461.00 | 1591.62 | 23-SEP-06:03 | 4.32 |
October | 0.321019E+09 | 12426.35 | 30-OCT-04:01 | -10.0 |
November | 0.198465E+10 | 12602.16 | 27-NOV-05:11 | -7.2 |
December | 0.551979E+10 | 13477.56 | 25-DEC-10:02 | -23.6 |
Annual Sum or Average | 0.194693E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.6 | |
Maximum of Months | 0.592193E+10 | 13571.31 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.729433E+10 | 7722.86 | 01-JAN-22:02 | -23.0 |
February | 0.457508E+10 | 7456.07 | 13-FEB-03:42 | -22.7 |
March | 0.351708E+10 | 7379.76 | 06-MAR-04:32 | -17.9 |
April | 0.681320E+09 | 6636.42 | 10-APR-04:01 | -2.8 |
May | 13656931.05 | 6100.91 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 49599251.57 | 6081.10 | 30-OCT-05:01 | -9.9 |
November | 0.140265E+10 | 7018.89 | 27-NOV-05:01 | -7.2 |
December | 0.576037E+10 | 7417.61 | 26-DEC-05:11 | -26.1 |
Annual Sum or Average | 0.232941E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.1 | |
Maximum of Months | 0.729433E+10 | 7722.86 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435695E+10 | 9735.17 | 01-JAN-22:02 | -23.0 |
February | 0.228023E+10 | 9447.48 | 13-FEB-03:42 | -22.7 |
March | 0.150644E+10 | 9325.51 | 06-MAR-05:11 | -18.5 |
April | 0.183945E+09 | 8217.67 | 10-APR-05:01 | -2.7 |
May | 363741.40 | 3031.18 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 25711203.01 | 7761.02 | 30-OCT-05:01 | -9.9 |
November | 0.795125E+09 | 8950.62 | 27-NOV-05:01 | -7.2 |
December | 0.347709E+10 | 9473.39 | 26-DEC-05:11 | -26.1 |
Annual Sum or Average | 0.126258E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.1 | |
Maximum of Months | 0.435695E+10 | 9735.17 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106602E+11 | 17313.46 | 06-JAN-07:10 | -35.0 |
February | 0.668256E+10 | 16788.05 | 14-FEB-07:10 | -33.0 |
March | 0.612305E+10 | 14979.03 | 15-MAR-07:00 | -23.9 |
April | 0.229734E+10 | 13292.51 | 05-APR-06:10 | -13.5 |
May | 0.661264E+09 | 11634.08 | 01-MAY-06:10 | -3.5 |
June | 0.112917E+09 | 8552.79 | 02-JUN-06:07 | 9.08 |
July | 11499314.56 | 6709.24 | 10-JUL-06:06 | 11.75 |
August | 46137668.85 | 7743.52 | 18-AUG-06:07 | 11.10 |
September | 0.550750E+09 | 9587.42 | 21-SEP-06:20 | 5.20 |
October | 0.174387E+10 | 12699.66 | 30-OCT-06:10 | -9.4 |
November | 0.397877E+10 | 13979.45 | 29-NOV-07:10 | -18.4 |
December | 0.947504E+10 | 16280.27 | 20-DEC-08:00 | -29.2 |
Annual Sum or Average | 0.423434E+11 | |||
Minimum of Months | 11499314.56 | 6709.24 | -35.0 | |
Maximum of Months | 0.106602E+11 | 17313.46 | 11.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448268E+10 | 10378.44 | 01-JAN-22:02 | -23.0 |
February | 0.240604E+10 | 10018.73 | 13-FEB-03:42 | -22.7 |
March | 0.163538E+10 | 9981.02 | 06-MAR-05:11 | -18.5 |
April | 0.255417E+09 | 8767.99 | 10-APR-05:01 | -2.7 |
May | 6307138.90 | 7901.89 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 30044095.04 | 8259.22 | 30-OCT-05:01 | -9.9 |
November | 0.805258E+09 | 9524.97 | 27-NOV-05:01 | -7.2 |
December | 0.356445E+10 | 10125.33 | 26-DEC-05:11 | -26.1 |
Annual Sum or Average | 0.131856E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.1 | |
Maximum of Months | 0.448268E+10 | 10378.44 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.659248E+10 | 8623.89 | 01-JAN-22:02 | -23.0 |
February | 0.355483E+10 | 8399.57 | 13-FEB-04:42 | -23.2 |
March | 0.180975E+10 | 8245.17 | 06-MAR-04:32 | -17.9 |
April | 0.205436E+09 | 7303.76 | 03-APR-05:01 | -4.3 |
May | 621072.16 | 6325.50 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.110598E+09 | 7189.45 | 30-OCT-05:01 | -9.9 |
November | 0.155838E+10 | 8017.49 | 27-NOV-05:11 | -7.2 |
December | 0.576813E+10 | 8532.68 | 26-DEC-04:42 | -25.6 |
Annual Sum or Average | 0.196002E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.659248E+10 | 8623.89 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382626E+10 | 11372.51 | 01-JAN-22:02 | -23.0 |
February | 0.178079E+10 | 10978.96 | 13-FEB-04:42 | -23.2 |
March | 0.854771E+09 | 10802.65 | 06-MAR-05:11 | -18.5 |
April | 77957837.04 | 9542.79 | 03-APR-05:01 | -4.3 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 64930286.90 | 9445.40 | 30-OCT-05:01 | -9.9 |
November | 0.927257E+09 | 10586.39 | 27-NOV-05:11 | -7.2 |
December | 0.345674E+10 | 11268.43 | 26-DEC-04:42 | -25.6 |
Annual Sum or Average | 0.109887E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.382626E+10 | 11372.51 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405267E+10 | 14599.96 | 02-JAN-04:02 | -18.8 |
February | 0.187072E+10 | 14314.58 | 13-FEB-04:42 | -23.2 |
March | 0.101488E+10 | 14052.94 | 06-MAR-05:11 | -18.5 |
April | 0.136372E+09 | 12480.77 | 04-APR-05:01 | -9.0 |
May | 1195170.31 | 11037.05 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 80968447.52 | 12353.65 | 30-OCT-05:01 | -9.9 |
November | 0.105746E+10 | 13819.29 | 27-NOV-05:11 | -7.2 |
December | 0.377505E+10 | 14612.84 | 26-DEC-04:42 | -25.6 |
Annual Sum or Average | 0.119893E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.405267E+10 | 14612.84 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398264E+10 | 11459.58 | 01-JAN-22:02 | -23.0 |
February | 0.197901E+10 | 11070.93 | 13-FEB-04:42 | -23.2 |
March | 0.957985E+09 | 10898.22 | 06-MAR-05:11 | -18.5 |
April | 0.109695E+09 | 9575.26 | 04-APR-05:01 | -9.0 |
May | 1143315.94 | 8286.50 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 74846178.36 | 9477.06 | 30-OCT-05:01 | -9.9 |
November | 0.949361E+09 | 10659.91 | 27-NOV-05:11 | -7.2 |
December | 0.355094E+10 | 11381.37 | 26-DEC-04:42 | -25.6 |
Annual Sum or Average | 0.116056E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.398264E+10 | 11459.58 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.475851E+09 | 735.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.388236E+09 | 636.29 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.432976E+09 | 579.40 | 03-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.367865E+09 | 401.07 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.381834E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.376210E+09 | 396.82 | 30-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.355062E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.406151E+09 | 509.98 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.376450E+09 | 522.45 | 19-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.419904E+09 | 725.99 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.460436E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.473788E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.491476E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.355062E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.475851E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.293467E+09 | 465.60 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243344E+09 | 411.21 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272205E+09 | 372.74 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.232994E+09 | 240.25 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.243447E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240045E+09 | 244.04 | 30-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.226408E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257535E+09 | 300.37 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237806E+09 | 297.69 | 19-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.262182E+09 | 457.67 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.286461E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.292806E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308870E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.226408E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.293467E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.452752E+09 | 735.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.378137E+09 | 605.44 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.428576E+09 | 566.48 | 03-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.368502E+09 | 399.02 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.384413E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.379041E+09 | 398.22 | 30-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.357513E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.407338E+09 | 502.91 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.375463E+09 | 512.43 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.410544E+09 | 723.74 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.443083E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.452761E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.483812E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.357513E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.452761E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.293462E+09 | 465.57 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241807E+09 | 369.87 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272401E+09 | 375.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.232653E+09 | 259.59 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.241944E+09 | 236.93 | 12-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.238210E+09 | 254.69 | 30-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.224672E+09 | 238.98 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257248E+09 | 330.50 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238175E+09 | 342.36 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.263643E+09 | 459.78 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.284661E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.292360E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308124E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.224672E+09 | 236.93 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.293462E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.473818E+09 | 735.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.387105E+09 | 632.32 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.431825E+09 | 573.41 | 03-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.367483E+09 | 398.59 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.381657E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.375966E+09 | 394.13 | 30-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.354868E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.405670E+09 | 501.35 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.375822E+09 | 514.24 | 19-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.418353E+09 | 725.63 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.458543E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.471683E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.490279E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.354868E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.473818E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.292794E+09 | 465.60 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242876E+09 | 409.50 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271698E+09 | 369.91 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.232811E+09 | 238.04 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.243280E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.239837E+09 | 242.13 | 30-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.226259E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257220E+09 | 261.25 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237500E+09 | 260.31 | 19-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.261600E+09 | 457.39 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.285685E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.292027E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308359E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.226259E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.292794E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.451596E+09 | 735.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377722E+09 | 599.90 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.427974E+09 | 559.87 | 03-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.368132E+09 | 396.42 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.384106E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.378611E+09 | 395.62 | 30-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.357207E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.406747E+09 | 493.95 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.374991E+09 | 503.73 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.409873E+09 | 723.26 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.442078E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.451915E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.483095E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.357207E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.451915E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.292779E+09 | 465.57 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241289E+09 | 366.86 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.271818E+09 | 372.24 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.232291E+09 | 258.44 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.241820E+09 | 235.22 | 12-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.238054E+09 | 253.30 | 30-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.224527E+09 | 236.98 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256929E+09 | 326.38 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237780E+09 | 338.60 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.263096E+09 | 459.60 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.283924E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.291691E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307600E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.224527E+09 | 235.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.292779E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.475838E+09 | 735.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.388235E+09 | 636.28 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.432975E+09 | 579.38 | 03-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.367865E+09 | 401.07 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.381834E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.376210E+09 | 396.81 | 30-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.355062E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.406150E+09 | 509.95 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.376449E+09 | 522.43 | 19-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.419902E+09 | 725.99 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.460434E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.473752E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.491471E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.355062E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.475838E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.293466E+09 | 465.60 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243344E+09 | 411.21 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272202E+09 | 372.74 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.232994E+09 | 240.24 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.243447E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240045E+09 | 244.04 | 30-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.226407E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257535E+09 | 300.36 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237805E+09 | 297.68 | 19-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.262181E+09 | 457.67 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.286460E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.292805E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308869E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.226407E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.293466E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.452752E+09 | 735.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.378137E+09 | 605.43 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.428576E+09 | 566.47 | 03-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.368501E+09 | 399.01 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.384413E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.379040E+09 | 398.22 | 30-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.357512E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.407337E+09 | 502.89 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.375458E+09 | 512.41 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.410543E+09 | 723.74 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.443082E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.452761E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.483811E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.357512E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.452761E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.293462E+09 | 465.57 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241807E+09 | 369.86 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272401E+09 | 375.01 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.232653E+09 | 259.59 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.241944E+09 | 236.93 | 12-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.238210E+09 | 254.69 | 30-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.224672E+09 | 238.98 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.257247E+09 | 330.49 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238172E+09 | 342.35 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.263642E+09 | 459.78 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.284660E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.292359E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.308123E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.224672E+09 | 236.93 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.293462E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.475851E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197883E+10 |
February | 0.901968E+09 | 0.388236E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168856E+10 |
March | 0.107774E+10 | 0.432976E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115743E+10 |
April | 0.956342E+09 | 0.367865E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1696307.58 | 0.106252E+10 |
May | 0.103597E+10 | 0.381834E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3495165.08 | 0.545563E+09 |
June | 0.103308E+10 | 0.376210E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13234402.97 | 0.298208E+09 |
July | 0.959235E+09 | 0.355062E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15955268.95 | 0.218638E+09 |
August | 0.107774E+10 | 0.406151E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5392187.69 | 0.299914E+09 |
September | 0.956342E+09 | 0.376450E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172804.08 | 0.507783E+09 |
October | 0.994195E+09 | 0.419904E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733236E+09 |
November | 0.984487E+09 | 0.460436E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130715E+10 |
December | 0.959235E+09 | 0.473788E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210082E+10 |
Annual Sum or Average | 0.119305E+11 | 0.491476E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39946136.36 | 0.118987E+11 |
Minimum of Months | 0.901968E+09 | 0.355062E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218638E+09 |
Maximum of Months | 0.107774E+10 | 0.475851E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15955268.95 | 0.210082E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.293467E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132192E+10 |
February | 0.571020E+09 | 0.243344E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113026E+10 |
March | 0.682301E+09 | 0.272205E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782532E+09 |
April | 0.605444E+09 | 0.232994E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 653587.77 | 0.730944E+09 |
May | 0.655854E+09 | 0.243447E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2330127.39 | 0.377160E+09 |
June | 0.654023E+09 | 0.240045E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8685607.97 | 0.205082E+09 |
July | 0.607275E+09 | 0.226408E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10402847.74 | 0.149160E+09 |
August | 0.682301E+09 | 0.257535E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3570506.33 | 0.211621E+09 |
September | 0.605444E+09 | 0.237806E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115203.10 | 0.350263E+09 |
October | 0.629407E+09 | 0.262182E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497925E+09 |
November | 0.623262E+09 | 0.286461E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874533E+09 |
December | 0.607275E+09 | 0.292806E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140261E+10 |
Annual Sum or Average | 0.755301E+10 | 0.308870E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25757880.30 | 0.803401E+10 |
Minimum of Months | 0.571020E+09 | 0.226408E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149160E+09 |
Maximum of Months | 0.682301E+09 | 0.293467E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10402847.74 | 0.140261E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.452752E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199704E+10 |
February | 0.901968E+09 | 0.378137E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173813E+10 |
March | 0.107774E+10 | 0.428576E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120581E+10 |
April | 0.956342E+09 | 0.368502E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7680.85 | 0.111791E+10 |
May | 0.103597E+10 | 0.384413E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3494496.11 | 0.560131E+09 |
June | 0.103308E+10 | 0.379041E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12892425.33 | 0.301870E+09 |
July | 0.959235E+09 | 0.357513E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15326050.64 | 0.222914E+09 |
August | 0.107774E+10 | 0.407338E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5327632.83 | 0.317548E+09 |
September | 0.956342E+09 | 0.375463E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171988.01 | 0.539868E+09 |
October | 0.994195E+09 | 0.410544E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772290E+09 |
November | 0.984487E+09 | 0.443083E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134070E+10 |
December | 0.959235E+09 | 0.452761E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212098E+10 |
Annual Sum or Average | 0.119305E+11 | 0.483812E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37220273.77 | 0.122352E+11 |
Minimum of Months | 0.901968E+09 | 0.357513E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222914E+09 |
Maximum of Months | 0.107774E+10 | 0.452761E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15326050.64 | 0.212098E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.293462E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132251E+10 |
February | 0.570983E+09 | 0.241807E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113617E+10 |
March | 0.682256E+09 | 0.272401E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787998E+09 |
April | 0.605404E+09 | 0.232653E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731602E+09 |
May | 0.655811E+09 | 0.241944E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2330169.92 | 0.378515E+09 |
June | 0.653980E+09 | 0.238210E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8335937.86 | 0.204950E+09 |
July | 0.607235E+09 | 0.224672E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10113037.07 | 0.153788E+09 |
August | 0.682256E+09 | 0.257248E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3541405.34 | 0.211306E+09 |
September | 0.605404E+09 | 0.238175E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115206.60 | 0.351975E+09 |
October | 0.629366E+09 | 0.263643E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499293E+09 |
November | 0.623221E+09 | 0.284661E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875436E+09 |
December | 0.607235E+09 | 0.292360E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140282E+10 |
Annual Sum or Average | 0.755252E+10 | 0.308124E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24435756.79 | 0.805636E+10 |
Minimum of Months | 0.570983E+09 | 0.224672E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153788E+09 |
Maximum of Months | 0.682256E+09 | 0.293462E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10113037.07 | 0.140282E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.473818E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106181E+10 |
February | 0.901968E+09 | 0.387105E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911161E+09 |
March | 0.107774E+10 | 0.431825E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618725E+09 |
April | 0.956342E+09 | 0.367483E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2980333.01 | 0.559189E+09 |
May | 0.103597E+10 | 0.381657E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1958986.26 | 0.273812E+09 |
June | 0.103308E+10 | 0.375966E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9052490.35 | 0.149270E+09 |
July | 0.959235E+09 | 0.354868E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9869750.38 | 0.111423E+09 |
August | 0.107774E+10 | 0.405670E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3238792.12 | 0.160007E+09 |
September | 0.956342E+09 | 0.375822E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95979.99 | 0.284601E+09 |
October | 0.994195E+09 | 0.418353E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424110E+09 |
November | 0.984487E+09 | 0.458543E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739803E+09 |
December | 0.959235E+09 | 0.471683E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113789E+10 |
Annual Sum or Average | 0.119305E+11 | 0.490279E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27196332.10 | 0.643180E+10 |
Minimum of Months | 0.901968E+09 | 0.354868E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111423E+09 |
Maximum of Months | 0.107774E+10 | 0.473818E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9869750.38 | 0.113789E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.292794E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710070E+09 |
February | 0.571020E+09 | 0.242876E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612956E+09 |
March | 0.682301E+09 | 0.271698E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419828E+09 |
April | 0.605444E+09 | 0.232811E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1047322.15 | 0.393331E+09 |
May | 0.655854E+09 | 0.243280E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1273397.88 | 0.196629E+09 |
June | 0.654023E+09 | 0.239837E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5104863.99 | 0.107613E+09 |
July | 0.607275E+09 | 0.226259E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5857470.51 | 78840873.32 |
August | 0.682301E+09 | 0.257220E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1944353.59 | 0.116441E+09 |
September | 0.605444E+09 | 0.237500E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63985.88 | 0.198914E+09 |
October | 0.629407E+09 | 0.261600E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291278E+09 |
November | 0.623262E+09 | 0.285685E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496824E+09 |
December | 0.607275E+09 | 0.292027E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759498E+09 |
Annual Sum or Average | 0.755301E+10 | 0.308359E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15291393.99 | 0.438222E+10 |
Minimum of Months | 0.571020E+09 | 0.226259E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78840873.32 |
Maximum of Months | 0.682301E+09 | 0.292794E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5857470.51 | 0.759498E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.451596E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107137E+11 |
February | 0.901968E+09 | 0.377722E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829575E+10 |
March | 0.107774E+10 | 0.427974E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778385E+10 |
April | 0.956342E+09 | 0.368132E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139192.46 | 0.458159E+10 |
May | 0.103597E+10 | 0.384106E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104590E+09 | 0.228467E+10 |
June | 0.103308E+10 | 0.378611E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239872E+09 | 0.112770E+10 |
July | 0.959235E+09 | 0.357207E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223804E+09 | 0.791894E+09 |
August | 0.107774E+10 | 0.406747E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122260E+09 | 0.138492E+10 |
September | 0.956342E+09 | 0.374991E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5137380.22 | 0.267574E+10 |
October | 0.994195E+09 | 0.409873E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447492E+10 |
November | 0.984487E+09 | 0.442078E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598134E+10 |
December | 0.959235E+09 | 0.451915E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945174E+10 |
Annual Sum or Average | 0.119305E+11 | 0.483095E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695803E+09 | 0.595478E+11 |
Minimum of Months | 0.901968E+09 | 0.357207E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791894E+09 |
Maximum of Months | 0.107774E+10 | 0.451915E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239872E+09 | 0.107137E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.292779E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710477E+09 |
February | 0.570983E+09 | 0.241289E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614851E+09 |
March | 0.682256E+09 | 0.271818E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422258E+09 |
April | 0.605404E+09 | 0.232291E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.47 | 0.393127E+09 |
May | 0.655811E+09 | 0.241820E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270591.32 | 0.199488E+09 |
June | 0.653980E+09 | 0.238054E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4853271.14 | 0.106777E+09 |
July | 0.607235E+09 | 0.224527E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5723125.60 | 83354229.40 |
August | 0.682256E+09 | 0.256929E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1927829.44 | 0.117785E+09 |
September | 0.605404E+09 | 0.237780E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63988.37 | 0.201041E+09 |
October | 0.629366E+09 | 0.263096E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292103E+09 |
November | 0.623221E+09 | 0.283924E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496710E+09 |
December | 0.607235E+09 | 0.291691E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760151E+09 |
Annual Sum or Average | 0.755252E+10 | 0.307600E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13840489.33 | 0.439812E+10 |
Minimum of Months | 0.570983E+09 | 0.224527E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83354229.40 |
Maximum of Months | 0.682256E+09 | 0.292779E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5723125.60 | 0.760151E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.475838E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166331E+10 |
February | 0.901968E+09 | 0.388235E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142952E+10 |
March | 0.107774E+10 | 0.432975E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990860E+09 |
April | 0.956342E+09 | 0.367865E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1511627.67 | 0.930889E+09 |
May | 0.103597E+10 | 0.381834E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2946519.01 | 0.469259E+09 |
June | 0.103308E+10 | 0.376210E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11371834.84 | 0.255261E+09 |
July | 0.959235E+09 | 0.355062E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13740628.43 | 0.186523E+09 |
August | 0.107774E+10 | 0.406150E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4625443.59 | 0.257886E+09 |
September | 0.956342E+09 | 0.376449E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147049.50 | 0.445915E+09 |
October | 0.994195E+09 | 0.419902E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653235E+09 |
November | 0.984487E+09 | 0.460434E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113415E+10 |
December | 0.959235E+09 | 0.473752E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177257E+10 |
Annual Sum or Average | 0.119305E+11 | 0.491471E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34343103.04 | 0.101894E+11 |
Minimum of Months | 0.901968E+09 | 0.355062E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186523E+09 |
Maximum of Months | 0.107774E+10 | 0.475838E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13740628.43 | 0.177257E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.293466E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110849E+10 |
February | 0.421807E+09 | 0.243344E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958268E+09 |
March | 0.502994E+09 | 0.272202E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670840E+09 |
April | 0.447140E+09 | 0.232994E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 611399.86 | 0.640497E+09 |
May | 0.484071E+09 | 0.243447E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1849311.54 | 0.323589E+09 |
June | 0.482240E+09 | 0.240045E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7186807.34 | 0.176009E+09 |
July | 0.448971E+09 | 0.226407E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8542932.53 | 0.127623E+09 |
August | 0.502994E+09 | 0.257535E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2854264.65 | 0.181652E+09 |
September | 0.447140E+09 | 0.237805E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89031.44 | 0.306515E+09 |
October | 0.465148E+09 | 0.262181E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443829E+09 |
November | 0.460569E+09 | 0.286460E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759196E+09 |
December | 0.448971E+09 | 0.292805E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118075E+10 |
Annual Sum or Average | 0.557719E+10 | 0.308869E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21133747.36 | 0.687725E+10 |
Minimum of Months | 0.421807E+09 | 0.226407E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127623E+09 |
Maximum of Months | 0.502994E+09 | 0.293466E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8542932.53 | 0.118075E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.452752E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168515E+10 |
February | 0.901968E+09 | 0.378137E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148517E+10 |
March | 0.107774E+10 | 0.428576E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103389E+10 |
April | 0.956342E+09 | 0.368501E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11223.77 | 0.976622E+09 |
May | 0.103597E+10 | 0.384413E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2945456.76 | 0.480801E+09 |
June | 0.103308E+10 | 0.379040E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10951978.93 | 0.258553E+09 |
July | 0.959235E+09 | 0.357512E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13065674.40 | 0.190515E+09 |
August | 0.107774E+10 | 0.407337E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4489153.59 | 0.272420E+09 |
September | 0.956342E+09 | 0.375458E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142651.26 | 0.469787E+09 |
October | 0.994195E+09 | 0.410543E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684846E+09 |
November | 0.984487E+09 | 0.443082E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116815E+10 |
December | 0.959235E+09 | 0.452761E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179724E+10 |
Annual Sum or Average | 0.119305E+11 | 0.483811E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31606138.71 | 0.105031E+11 |
Minimum of Months | 0.901968E+09 | 0.357512E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190515E+09 |
Maximum of Months | 0.107774E+10 | 0.452761E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13065674.40 | 0.179724E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.293462E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111024E+10 |
February | 0.570983E+09 | 0.241807E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963147E+09 |
March | 0.682256E+09 | 0.272401E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674860E+09 |
April | 0.605404E+09 | 0.232653E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.92 | 0.639957E+09 |
May | 0.655811E+09 | 0.241944E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1964392.20 | 0.325013E+09 |
June | 0.653980E+09 | 0.238210E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7059750.50 | 0.175495E+09 |
July | 0.607235E+09 | 0.224672E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8605033.06 | 0.131417E+09 |
August | 0.682256E+09 | 0.257247E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2981754.08 | 0.181495E+09 |
September | 0.605404E+09 | 0.238172E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98035.61 | 0.307574E+09 |
October | 0.629366E+09 | 0.263642E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443773E+09 |
November | 0.623221E+09 | 0.284660E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759470E+09 |
December | 0.607235E+09 | 0.292359E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118242E+10 |
Annual Sum or Average | 0.755252E+10 | 0.308123E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20709178.37 | 0.689486E+10 |
Minimum of Months | 0.570983E+09 | 0.224672E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131417E+09 |
Maximum of Months | 0.682256E+09 | 0.293462E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8605033.06 | 0.118242E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219070E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193047E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133237E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1698971.27 | 0.127312E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2668664.35 | 0.623242E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13638414.62 | 0.337468E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15242173.11 | 0.246000E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4058664.99 | 0.351346E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88847.37 | 0.614419E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913630E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156839E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236204E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37395735.70 | 0.137432E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246000E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15242173.11 | 0.236204E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277515E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242439E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168705E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1841122.28 | 0.160750E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3395790.16 | 0.804353E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16724282.68 | 0.436707E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19000848.51 | 0.317740E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5247926.99 | 0.448327E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114026.94 | 0.771339E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111788E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193214E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297405E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46323997.56 | 0.172966E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317740E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19000848.51 | 0.297405E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293614E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254107E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177059E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8172.10 | 0.166979E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2394115.18 | 0.858291E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15316942.29 | 0.470394E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13241062.80 | 0.344213E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4044312.22 | 0.481387E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42040.45 | 0.806677E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113733E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197485E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311790E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35046645.03 | 0.181086E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344213E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15316942.29 | 0.311790E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3524.68 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 636.29 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4227.35 | 12-FEB-22:51 |
March | 1306.65 | 01-MAR-10:09 | 579.40 | 03-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2175.82 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 401.07 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.85 | 23-APR-16:00 | 1681.26 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 24-MAY-15:00 | 912.13 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 396.82 | 30-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.07 | 29-JUN-21:03 | 613.74 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.88 | 23-JUL-14:56 | 607.24 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 509.98 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 08-AUG-16:00 | 809.89 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 522.45 | 19-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 01-SEP-15:00 | 1053.20 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 725.99 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1452.73 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2265.90 | 21-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3493.28 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.24 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 256.88 | 4227.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2398.80 | 04-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 411.21 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2817.40 | 12-FEB-22:51 |
March | 827.22 | 01-MAR-10:09 | 372.74 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1450.53 | 15-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 240.25 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.65 | 23-APR-16:00 | 1119.95 | 01-APR-19:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 24-MAY-15:00 | 648.18 | 14-MAY-07:50 |
June | 827.22 | 01-JUN-09:09 | 244.04 | 30-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 29-JUN-21:03 | 406.21 | 20-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.07 | 23-JUL-14:54 | 401.72 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 300.37 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 08-AUG-16:00 | 546.39 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 297.69 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 01-SEP-15:00 | 699.56 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 457.67 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 967.99 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1509.09 | 21-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2328.85 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.72 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 168.07 | 2817.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3598.22 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 605.44 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4232.04 | 12-FEB-22:51 |
March | 1306.65 | 01-MAR-10:09 | 566.48 | 03-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2175.82 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 399.02 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.16 | 23-APR-16:16 | 1854.51 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 24-MAY-15:00 | 923.51 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 398.22 | 30-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.45 | 29-JUN-21:03 | 613.78 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.93 | 23-JUL-14:54 | 612.53 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 502.91 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 08-AUG-16:00 | 825.10 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 512.43 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 01-SEP-15:00 | 1057.67 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 723.74 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1453.65 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2266.11 | 21-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3493.29 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.53 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 249.93 | 4232.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2398.80 | 04-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 369.87 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2817.83 | 12-FEB-22:51 |
March | 827.17 | 01-MAR-10:09 | 375.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1450.53 | 15-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 259.59 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1127.31 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 236.93 | 12-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 24-MAY-15:00 | 618.96 | 29-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 254.69 | 30-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.15 | 29-JUN-16:00 | 408.82 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 238.98 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 23-JUL-14:54 | 446.41 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 330.50 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 08-AUG-16:00 | 551.58 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 342.36 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 01-SEP-15:00 | 698.91 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 459.78 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 967.81 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1508.82 | 21-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2328.84 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 236.93 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.82 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 2817.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1888.96 | 04-JAN-05:52 |
February | 1306.65 | 01-FEB-10:09 | 632.32 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2264.05 | 12-FEB-22:51 |
March | 1306.65 | 01-MAR-10:09 | 573.41 | 03-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1155.37 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 398.59 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.90 | 23-APR-16:00 | 909.92 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 | 24-MAY-15:00 | 477.56 | 20-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 394.13 | 30-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 | 24-JUN-17:02 | 319.48 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.41 | 23-JUL-14:52 | 324.30 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 501.35 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 | 08-AUG-16:00 | 448.76 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 514.24 | 19-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 01-SEP-15:00 | 609.70 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 725.63 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 777.48 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1332.27 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1854.51 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.48 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 221.90 | 2264.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1262.17 | 04-JAN-05:52 |
February | 827.22 | 01-FEB-10:09 | 409.50 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1509.26 | 12-FEB-22:51 |
March | 827.22 | 01-MAR-10:09 | 369.91 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 770.24 | 15-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 238.04 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.03 | 23-APR-16:00 | 615.67 | 01-APR-19:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 24-MAY-15:00 | 328.13 | 08-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 242.13 | 30-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.26 | 24-JUN-17:02 | 219.44 | 20-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.71 | 23-JUL-15:10 | 222.39 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 261.25 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 08-AUG-16:00 | 314.73 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 260.31 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 01-SEP-15:00 | 406.01 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 457.39 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 518.39 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 884.53 | 22-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1236.33 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.44 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 102.03 | 1509.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 50512.25 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 599.90 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 48559.83 | 14-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 559.87 | 03-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 38689.51 | 16-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 396.42 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 | 23-APR-17:40 | 29124.96 | 05-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.43 | 25-MAY-17:00 | 19848.05 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 395.62 | 30-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8031.26 | 29-JUN-16:10 | 9845.01 | 02-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4075.33 | 28-JUL-16:10 | 8938.85 | 18-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 493.95 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4967.15 | 08-AUG-16:10 | 10910.53 | 25-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 503.73 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.41 | 01-SEP-16:10 | 15940.49 | 06-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 723.26 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 25518.21 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 34051.95 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 44786.38 | 20-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8938.85 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8031.26 | 50512.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1262.04 | 04-JAN-05:52 |
February | 827.17 | 01-FEB-10:09 | 366.86 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1510.05 | 12-FEB-22:51 |
March | 827.17 | 01-MAR-10:09 | 372.24 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 770.24 | 15-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 258.44 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | 23-APR-15:53 | 621.67 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 235.22 | 12-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 24-MAY-15:00 | 325.56 | 08-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 253.30 | 30-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.11 | 29-JUN-21:03 | 218.31 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 236.98 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.41 | 23-JUL-15:07 | 253.52 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 326.38 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 08-AUG-16:00 | 321.51 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 338.60 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 01-SEP-15:00 | 407.82 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 459.60 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 518.08 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 884.38 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1236.33 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 235.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 79.41 | 1510.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2993.55 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 636.28 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3562.76 | 12-FEB-22:53 |
March | 1306.65 | 01-MAR-10:09 | 579.38 | 03-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1810.02 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 401.07 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.02 | 23-APR-15:51 | 1477.32 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 24-MAY-15:00 | 787.12 | 08-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 396.81 | 30-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.16 | 24-JUN-17:02 | 534.13 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.86 | 23-JUL-14:47 | 519.78 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 509.95 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.17 | 08-AUG-16:00 | 708.04 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 522.43 | 19-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 | 01-SEP-15:00 | 928.62 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 725.99 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1214.69 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1994.38 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2905.62 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.78 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 202.86 | 3562.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1995.69 | 04-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 411.21 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2375.19 | 12-FEB-22:51 |
March | 805.43 | 01-MAR-08:09 | 372.74 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1206.67 | 15-MAR-05:00 |
April | 805.43 | 03-APR-07:10 | 240.24 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.75 | 23-APR-15:51 | 987.50 | 01-APR-19:00 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 24-MAY-15:00 | 557.36 | 14-MAY-08:00 |
June | 805.43 | 01-JUN-07:10 | 244.04 | 30-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.57 | 24-JUN-17:02 | 354.04 | 20-JUN-04:00 |
July | 805.43 | 03-JUL-07:10 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.74 | 23-JUL-14:45 | 344.94 | 06-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 300.36 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 08-AUG-16:00 | 477.82 | 27-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 297.68 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 01-SEP-15:00 | 617.26 | 20-SEP-01:00 |
October | 805.43 | 02-OCT-07:10 | 457.67 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 809.48 | 31-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1320.10 | 22-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1925.47 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.94 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 134.74 | 2375.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2993.55 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 605.43 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3562.84 | 12-FEB-22:51 |
March | 1306.65 | 01-MAR-10:09 | 566.47 | 03-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1810.02 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 399.01 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 23-APR-16:04 | 1651.14 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 24-MAY-15:00 | 790.42 | 08-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 398.22 | 30-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.61 | 29-JUN-21:03 | 534.22 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.62 | 23-JUL-14:43 | 524.61 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 502.89 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.16 | 08-AUG-16:00 | 720.49 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 512.41 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 | 01-SEP-15:00 | 931.89 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 723.74 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1215.65 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1996.14 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2905.62 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.61 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 195.62 | 3562.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1995.69 | 04-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 369.86 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2375.22 | 12-FEB-22:51 |
March | 827.17 | 01-MAR-10:09 | 375.01 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1206.68 | 15-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 259.59 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 23-APR-16:04 | 992.02 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 236.93 | 12-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 24-MAY-15:00 | 524.37 | 08-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 254.69 | 30-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.06 | 29-JUN-16:00 | 355.86 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 238.98 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.12 | 23-JUL-14:43 | 380.60 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 330.49 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 08-AUG-16:00 | 481.83 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 342.35 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 01-SEP-15:00 | 616.17 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 459.78 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 809.32 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1318.69 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1937.06 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 236.93 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.86 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 135.12 | 2375.22 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3759.78 | 04-JAN-05:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4827.16 | 12-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2376.80 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.72 | 23-APR-15:51 | 2069.26 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.44 | 24-MAY-15:00 | 1070.95 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.97 | 24-JUN-17:02 | 718.26 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.62 | 23-JUL-14:52 | 689.89 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.49 | 08-AUG-16:00 | 970.85 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 01-SEP-15:00 | 1286.65 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1606.89 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2866.95 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3777.79 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.62 | 4827.16 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4814.74 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5959.49 | 12-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3015.52 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.88 | 23-APR-16:00 | 2599.29 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 | 24-MAY-15:00 | 1370.86 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.71 | 24-JUN-17:02 | 926.67 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.59 | 23-JUL-15:00 | 884.12 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.33 | 08-AUG-16:00 | 1236.49 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 01-SEP-15:00 | 1625.38 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1992.19 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3537.53 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4752.14 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.12 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.59 | 5959.49 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5098.05 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6123.95 | 12-FEB-22:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3112.12 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 23-APR-16:00 | 2638.45 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.15 | 24-MAY-15:00 | 1450.81 | 29-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.60 | 29-JUN-16:00 | 920.19 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.95 | 15-JUL-17:05 | 873.74 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.10 | 08-AUG-16:00 | 1241.45 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | 01-SEP-15:50 | 1612.06 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2128.13 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3416.45 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4890.24 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.74 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.95 | 6123.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6298.48 | 06-JAN-08:57 | 18105.02 | 10466.10 | 38274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5960.54 | 10-FEB-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9259.79 | 31-MAR-16:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15203.00 | 20-APR-07:03 | 54315.07 | 31398.31 | 114824.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31949.44 | 30-MAY-06:03 | 3811.58 | 3488.70 | 18132.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31939.18 | 26-JUN-06:03 | 5082.11 | 4651.60 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34904.42 | 05-JUL-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32539.98 | 28-AUG-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34605.23 | 06-SEP-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15064.69 | 05-OCT-07:03 | 36210.05 | 20932.21 | 76549.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8980.41 | 02-NOV-07:40 | 6035.01 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5816.20 | 01-DEC-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5816.20 | 2541.06 | 846.94 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34904.42 | 54315.07 | 31398.31 | 114824.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1747.79 |
February | 193.94 | 04-FEB-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.28 |
March | 1073.88 | 31-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.49 |
April | 4178.25 | 13-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.75 |
May | 8356.86 | 18-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 0.00 |
June | 9549.41 | 30-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.03 | 0.00 |
July | 9194.24 | 24-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 | 0.00 |
August | 8260.44 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.55 | 0.00 |
September | 6979.27 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 0.00 |
October | 2959.45 | 20-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.14 |
November | 537.01 | 01-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1856.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9549.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.03 | 1856.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3620.76 | 13-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3651.12 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2879.45 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1495.11 |
April | 1906.55 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3460.90 | 18-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.31 | 0.00 |
June | 4311.35 | 30-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.71 | 0.00 |
July | 6322.96 | 24-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 |
August | 3671.13 | 08-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.00 | 0.00 |
September | 3509.41 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 0.00 |
October | 2321.86 | 06-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.57 |
November | 2691.35 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.99 |
December | 3330.53 | 02-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1575.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1906.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6322.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.71 | 1575.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3370.70 | 13-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3575.30 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3461.53 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172.78 |
April | 3111.08 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3223.48 | 18-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 | 0.00 |
June | 4151.59 | 30-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.73 | 0.00 |
July | 5282.18 | 24-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 |
August | 3833.71 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.49 | 0.00 |
September | 3488.90 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 0.00 |
October | 2310.77 | 25-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1958.98 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.74 |
December | 2880.56 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1958.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5282.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.49 | 1172.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4975.60 | 27-JAN-16:33 | 18105.02 | 10466.10 | 20424.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5385.27 | 08-FEB-16:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6178.77 | 29-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10460.72 | 24-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24677.95 | 30-MAY-06:03 | 3811.58 | 3488.70 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26196.69 | 26-JUN-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29468.96 | 31-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27197.83 | 28-AUG-06:02 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26910.95 | 05-SEP-06:01 | 11434.75 | 10466.10 | 27233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10533.33 | 20-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5959.27 | 17-NOV-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4961.42 | 01-DEC-16:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4961.42 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29468.96 | 18105.02 | 10466.10 | 27233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4603.87 | 27-JAN-16:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5261.20 | 08-FEB-16:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6068.63 | 29-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10422.96 | 14-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16155.59 | 18-MAY-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26484.79 | 26-JUN-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29758.95 | 05-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19560.38 | 28-AUG-06:02 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15779.92 | 01-SEP-15:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10124.71 | 20-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5614.02 | 17-NOV-16:40 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4476.85 | 28-DEC-16:10 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4476.85 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29758.95 | 12070.02 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 798.05 | 28-JAN-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.11 |
February | 902.79 | 08-FEB-16:30 | 1272.23 | 483.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.55 |
March | 1156.98 | 31-MAR-16:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.35 |
April | 2508.16 | 18-APR-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.52 |
May | 5319.77 | 18-MAY-14:50 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 0.00 |
June | 7997.79 | 28-JUN-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9970.83 | 23-JUL-15:32 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 170.45 | 0.00 |
August | 5530.81 | 08-AUG-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.20 | 0.00 |
September | 4619.95 | 01-SEP-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 |
October | 1805.37 | 20-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 |
November | 1135.07 | 01-NOV-15:50 | 1272.23 | 395.33 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 |
December | 804.63 | 16-DEC-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 798.05 | 334.80 | 116.92 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9970.83 | 1306.65 | 483.66 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 170.45 | 421.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 492.15 | 28-JAN-17:02 | 211.95 | 129.32 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.63 |
February | 720.64 | 28-FEB-10:30 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.83 |
March | 2360.10 | 31-MAR-09:50 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.64 |
April | 6107.20 | 18-APR-09:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 |
May | 10164.44 | 21-MAY-10:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.33 |
June | 13805.62 | 25-JUN-08:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.67 |
July | 13712.16 | 23-JUL-09:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 |
August | 10315.70 | 20-AUG-10:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.41 |
September | 7770.97 | 01-SEP-09:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 |
October | 3549.58 | 19-OCT-09:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.57 |
November | 743.49 | 16-NOV-10:10 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.48 |
December | 496.81 | 16-DEC-17:02 | 211.95 | 129.32 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 492.15 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | |
Maximum of Months | 13805.62 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5524.57 | 27-JAN-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7931.05 | 28-FEB-13:35 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.22 |
March | 8919.93 | 31-MAR-14:00 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.79 |
April | 17547.25 | 23-APR-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.03 |
May | 14516.23 | 21-MAY-13:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.86 |
June | 13339.78 | 25-JUN-11:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 | 0.00 |
July | 17609.21 | 23-JUL-12:52 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 88.48 | 0.00 |
August | 17468.45 | 27-AUG-13:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.05 |
September | 17600.74 | 03-SEP-13:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.60 |
October | 17783.71 | 22-OCT-13:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.78 |
November | 7318.25 | 17-NOV-13:03 | 8905.63 | 2455.66 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.98 |
December | 3026.52 | 02-DEC-13:30 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3026.52 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17783.71 | 8905.63 | 2455.66 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 88.48 | 385.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 740.04 | 27-JAN-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2005.88 | 08-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.09 |
March | 4448.39 | 31-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 |
April | 14721.28 | 23-APR-16:12 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.08 |
May | 15541.63 | 21-MAY-16:42 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.10 |
June | 14783.39 | 04-JUN-15:42 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.61 |
July | 15232.25 | 16-JUL-16:22 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.69 |
August | 14297.41 | 05-AUG-17:04 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.28 |
September | 12626.83 | 03-SEP-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.05 |
October | 5042.94 | 19-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 |
November | 1249.62 | 17-NOV-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.05 |
December | 570.86 | 20-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 570.86 | 211.94 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15541.63 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 804.84 | 28-JAN-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.66 |
February | 806.80 | 11-FEB-17:03 | 267.84 | 146.27 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.43 |
March | 948.53 | 31-MAR-16:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.29 |
April | 1413.78 | 23-APR-17:11 | 0.00 | 136.41 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 139.95 | 0.00 |
May | 3188.49 | 26-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 |
June | 4558.62 | 29-JUN-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 78.36 | 0.00 |
July | 6347.93 | 24-JUL-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 |
August | 4425.04 | 09-AUG-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 0.00 |
September | 3716.49 | 01-SEP-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
October | 1679.40 | 22-OCT-14:53 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.96 |
November | 1149.28 | 01-NOV-15:30 | 1272.23 | 377.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 |
December | 819.47 | 16-DEC-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 804.84 | 0.00 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6347.93 | 1306.65 | 377.28 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 139.95 | 223.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 544.29 | 20-JAN-07:03 | 1695.64 | 1552.00 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.56 |
February | 612.32 | 28-FEB-10:25 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.38 |
March | 829.80 | 31-MAR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.95 |
April | 3341.08 | 18-APR-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.46 |
May | 6870.16 | 17-MAY-06:02 | 847.82 | 370.15 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
June | 11245.09 | 25-JUN-08:51 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 |
July | 8417.70 | 18-JUL-06:02 | 1017.38 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
August | 8371.41 | 21-AUG-06:02 | 1017.38 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 |
September | 5848.92 | 05-SEP-08:30 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 |
October | 2750.36 | 19-OCT-08:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
November | 756.16 | 17-NOV-10:10 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.25 |
December | 549.56 | 01-DEC-09:45 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 544.29 | 296.74 | 86.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | |
Maximum of Months | 11245.09 | 1695.64 | 1552.00 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 999.70 | 21-JAN-12:00 | 401.76 | 116.94 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.38 |
February | 1293.96 | 28-FEB-15:10 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2081.62 |
March | 2159.79 | 31-MAR-14:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.33 |
April | 6191.31 | 23-APR-14:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.79 |
May | 9506.80 | 18-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2951.90 | 0.00 |
June | 12042.47 | 29-JUN-16:10 | 401.76 | 194.89 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8031.26 | 0.00 |
July | 11243.36 | 24-JUL-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3197.68 | 0.00 |
August | 13254.48 | 27-AUG-14:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.80 |
September | 14041.27 | 03-SEP-13:52 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.94 |
October | 14213.91 | 22-OCT-14:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.28 |
November | 4211.26 | 17-NOV-13:30 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1589.87 |
December | 1737.97 | 02-DEC-13:40 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 999.70 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14213.91 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8031.26 | 2081.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 661.09 | 27-JAN-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 813.74 | 08-FEB-16:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 |
March | 2282.65 | 28-MAR-17:20 | 84.78 | 74.03 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 |
April | 10674.00 | 23-APR-17:11 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 |
May | 11461.30 | 21-MAY-16:42 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 |
June | 9496.52 | 17-JUN-18:22 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 |
July | 11542.28 | 16-JUL-16:41 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.85 |
August | 10593.73 | 05-AUG-17:04 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 |
September | 12371.74 | 03-SEP-17:12 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.63 |
October | 4149.15 | 19-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
November | 1019.68 | 17-NOV-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 |
December | 557.00 | 08-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 557.00 | 0.00 | 61.68 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12371.74 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 790.05 | 28-JAN-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 |
February | 905.06 | 08-FEB-15:10 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.76 |
March | 1155.82 | 29-MAR-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.62 |
April | 2420.57 | 14-APR-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.86 |
May | 4922.36 | 26-MAY-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
June | 7504.68 | 28-JUN-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8845.50 | 23-JUL-16:41 | 535.68 | 155.89 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 54.01 | 0.00 |
August | 5099.93 | 08-AUG-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 | 0.00 |
September | 4303.28 | 01-SEP-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
October | 1973.32 | 02-OCT-13:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 |
November | 1152.48 | 01-NOV-15:40 | 1272.23 | 387.86 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 |
December | 794.50 | 16-DEC-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 790.05 | 334.80 | 155.89 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8845.50 | 2613.31 | 701.62 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 | 351.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 569.19 | 19-JAN-13:03 | 8054.28 | 2220.91 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.64 |
February | 777.01 | 28-FEB-10:00 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.86 |
March | 4174.15 | 31-MAR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.00 |
April | 6789.58 | 18-APR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.73 |
May | 11206.84 | 14-MAY-08:43 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.86 |
June | 15163.94 | 25-JUN-08:11 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.14 |
July | 14684.83 | 23-JUL-10:01 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.66 |
August | 12118.59 | 06-AUG-08:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.36 |
September | 7960.08 | 01-SEP-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 |
October | 5542.27 | 25-OCT-12:01 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.41 |
November | 820.52 | 16-NOV-09:45 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.32 |
December | 582.78 | 01-DEC-10:00 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 569.19 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 | |
Maximum of Months | 15163.94 | 8054.28 | 2220.91 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6304.43 | 27-JAN-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8217.52 | 28-FEB-13:35 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.84 |
March | 9248.92 | 31-MAR-13:40 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.78 |
April | 17048.02 | 23-APR-13:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.42 |
May | 11245.80 | 21-MAY-12:13 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.50 |
June | 16574.01 | 25-JUN-11:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
July | 17311.35 | 23-JUL-12:42 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 | 0.00 |
August | 16350.90 | 27-AUG-13:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.26 |
September | 17101.72 | 03-SEP-13:52 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.34 |
October | 16829.43 | 22-OCT-13:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.94 |
November | 8125.35 | 17-NOV-13:03 | 8905.63 | 2455.66 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.41 |
December | 3963.26 | 02-DEC-13:30 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3963.26 | 133.92 | 58.46 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17311.35 | 8905.63 | 2455.66 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 | 349.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 777.79 | 27-JAN-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2060.44 | 08-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.84 |
March | 4554.05 | 31-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 |
April | 15279.68 | 23-APR-16:41 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.98 |
May | 15138.96 | 14-MAY-17:11 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.90 |
June | 13518.76 | 17-JUN-17:04 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.43 |
July | 15133.65 | 23-JUL-16:41 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 |
August | 14207.74 | 27-AUG-17:42 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.58 |
September | 14875.83 | 03-SEP-17:12 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.97 |
October | 6204.11 | 22-OCT-15:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.83 |
November | 1513.43 | 17-NOV-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.10 |
December | 617.49 | 20-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 617.49 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15279.68 | 805.38 | 222.08 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.90 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.190609E+12 | 252791.27 | 02-JAN-08:09 | 0.641857E+11 | 180524.58 | 06-JAN-08:09 |
February | 0.134783E+12 | 214367.63 | 13-FEB-07:10 | 0.314627E+11 | 179341.75 | 14-FEB-07:19 |
March | 0.123914E+12 | 199712.48 | 06-MAR-07:10 | 0.175060E+11 | 135793.31 | 15-MAR-06:00 |
April | 0.856645E+11 | 135176.51 | 03-APR-06:10 | 0.123660E+11 | 18325.09 | 05-APR-06:19 |
May | 0.927553E+11 | 115510.60 | 25-MAY-15:20 | 0.124984E+11 | 22141.47 | 13-MAY-06:10 |
June | 0.106860E+12 | 139609.23 | 29-JUN-15:30 | 0.118046E+11 | 10823.36 | 02-JUN-11:30 |
July | 0.115733E+12 | 151851.09 | 05-JUL-12:20 | 0.113330E+11 | 10147.80 | 03-JUL-11:30 |
August | 0.110352E+12 | 129981.43 | 08-AUG-15:39 | 0.117389E+11 | 10063.86 | 03-AUG-11:09 |
September | 0.830847E+11 | 114915.82 | 01-SEP-15:39 | 0.110893E+11 | 20263.90 | 21-SEP-06:10 |
October | 0.866592E+11 | 135536.10 | 30-OCT-06:10 | 0.117219E+11 | 15596.53 | 30-OCT-06:30 |
November | 0.114059E+12 | 202197.45 | 27-NOV-07:10 | 0.138327E+11 | 27441.82 | 25-NOV-07:40 |
December | 0.176263E+12 | 241606.00 | 26-DEC-07:10 | 0.439540E+11 | 172470.77 | 20-DEC-07:00 |
Annual Sum or Average | 0.142074E+13 | 0.253493E+12 | ||||
Minimum of Months | 0.830847E+11 | 114915.82 | 0.110893E+11 | 10063.86 | ||
Maximum of Months | 0.190609E+12 | 252791.27 | 0.641857E+11 | 180524.58 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.461449E+10 | 12276.04 | 25-JAN-12:30 | 0.00 | 0.00 |
February | 0.725661E+10 | 18937.32 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.106248E+11 | 22445.28 | 31-MAR-12:30 | 0.00 | 0.00 |
April | 0.140742E+11 | 25605.48 | 19-APR-12:20 | 0.00 | 0.00 |
May | 0.169985E+11 | 25562.37 | 06-MAY-12:20 | 0.00 | 0.00 |
June | 0.170046E+11 | 25222.26 | 16-JUN-12:30 | 0.00 | 0.00 |
July | 0.178219E+11 | 24978.30 | 07-JUL-12:30 | 0.00 | 0.00 |
August | 0.143300E+11 | 23196.76 | 05-AUG-12:30 | 0.00 | 0.00 |
September | 0.105891E+11 | 20834.95 | 04-SEP-11:00 | 0.00 | 0.00 |
October | 0.660091E+10 | 15365.26 | 09-OCT-11:30 | 0.00 | 0.00 |
November | 0.404865E+10 | 11959.71 | 07-NOV-12:20 | 0.00 | 0.00 |
December | 0.358257E+10 | 9704.13 | 02-DEC-12:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127546E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.358257E+10 | 9704.13 | 0.00 | 0.00 | |
Maximum of Months | 0.178219E+11 | 25605.48 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.145035E+11 | 0.427959E+10 | 0.545046E+11 | 0.976910E+09 | 0.515041E+10 | 12379742.02 | 0.108326E+12 | 1655217.74 | 0.00 | 0.00 | 0.285363E+10 | 0.00 | 0.00 |
February | 0.127879E+11 | 0.332719E+10 | 0.493409E+11 | 0.883738E+09 | 0.395634E+10 | 11196021.66 | 0.618555E+11 | 4761499.34 | 0.00 | 0.00 | 0.261516E+10 | 0.00 | 0.00 |
March | 0.149519E+11 | 0.298289E+10 | 0.567112E+11 | 0.102247E+10 | 0.400950E+10 | 12675672.10 | 0.411284E+11 | 21382028.63 | 0.00 | 0.00 | 0.307310E+10 | 0.00 | 0.00 |
April | 0.131955E+11 | 0.226729E+10 | 0.526212E+11 | 0.940419E+09 | 0.407780E+10 | 11960507.72 | 0.943380E+10 | 0.111613E+10 | 0.00 | 0.00 | 0.200040E+10 | 0.00 | 0.00 |
May | 0.141030E+11 | 0.190365E+10 | 0.556079E+11 | 0.999234E+09 | 0.786746E+10 | 12527707.06 | 0.981814E+09 | 0.104609E+11 | 0.00 | 0.00 | 0.818844E+09 | 0.00 | 0.00 |
June | 0.139981E+11 | 0.165264E+10 | 0.546110E+11 | 0.983579E+09 | 0.113410E+11 | 12231776.97 | 0.160097E+09 | 0.236031E+11 | 0.00 | 0.00 | 0.498244E+09 | 0.00 | 0.00 |
July | 0.131311E+11 | 0.178710E+10 | 0.536070E+11 | 0.955885E+09 | 0.139719E+11 | 12256437.81 | 20445940.95 | 0.313881E+11 | 0.00 | 0.00 | 0.859135E+09 | 0.00 | 0.00 |
August | 0.147194E+11 | 0.212245E+10 | 0.567112E+11 | 0.102234E+10 | 0.113460E+11 | 12675672.10 | 69211110.18 | 0.238869E+11 | 0.00 | 0.00 | 0.461631E+09 | 0.00 | 0.00 |
September | 0.132726E+11 | 0.258850E+10 | 0.525990E+11 | 0.940226E+09 | 0.663054E+10 | 11960507.72 | 0.743762E+09 | 0.560935E+10 | 0.00 | 0.00 | 0.688800E+09 | 0.00 | 0.00 |
October | 0.140269E+11 | 0.338231E+10 | 0.545158E+11 | 0.976560E+09 | 0.394150E+10 | 12379742.02 | 0.677919E+10 | 0.807303E+09 | 0.00 | 0.00 | 0.221735E+10 | 0.00 | 0.00 |
November | 0.142637E+11 | 0.394070E+10 | 0.533244E+11 | 0.958658E+09 | 0.354439E+10 | 12059151.09 | 0.353161E+11 | 0.106308E+09 | 0.00 | 0.00 | 0.259299E+10 | 0.00 | 0.00 |
December | 0.141717E+11 | 0.445629E+10 | 0.535958E+11 | 0.956646E+09 | 0.481926E+10 | 12256437.81 | 0.954266E+11 | 3020047.09 | 0.00 | 0.00 | 0.282183E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.167125E+12 | 0.346906E+11 | 0.647750E+12 | 0.116167E+11 | 0.806561E+11 | 0.146559E+09 | 0.360241E+12 | 0.970089E+11 | 0.00 | 0.00 | 0.215011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.127879E+11 | 0.165264E+10 | 0.493409E+11 | 0.883738E+09 | 0.354439E+10 | 11196021.66 | 20445940.95 | 1655217.74 | 0.00 | 0.00 | 0.461631E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149519E+11 | 0.445629E+10 | 0.567112E+11 | 0.102247E+10 | 0.139719E+11 | 12675672.10 | 0.108326E+12 | 0.313881E+11 | 0.00 | 0.00 | 0.307310E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.515031E+11 | 0.00 | 0.126826E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.198452E+11 | 0.00 | 0.116175E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.421919E+10 | 0.00 | 0.132868E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.233081E+09 | 0.00 | 0.121329E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 76893198.45 | 0.00 | 0.124215E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4378987.42 | 0.00 | 0.118002E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.113330E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2022781.06 | 0.00 | 0.117368E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 91226279.61 | 0.00 | 0.109981E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136373E+09 | 0.00 | 0.115855E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.216953E+10 | 0.00 | 0.116631E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.317659E+11 | 0.00 | 0.121881E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110047E+12 | 0.00 | 0.143446E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.109981E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.515031E+11 | 0.00 | 0.132868E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-08:09 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 829.79 | 02-JAN-08:20 | 7773.68 | 02-JAN-06:19 | 6.85 | 03-JAN-06:10 | 202545.12 | 02-JAN-06:19 |
February | 16514.15 | 02-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 827.32 | 15-FEB-08:20 | 6148.08 | 13-FEB-07:10 | 6.85 | 01-FEB-17:19 | 177699.93 | 13-FEB-07:10 |
March | 16035.82 | 03-MAR-16:00 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 827.52 | 13-MAR-07:19 | 5869.90 | 06-MAR-06:10 | 6.85 | 01-MAR-12:09 | 169123.26 | 06-MAR-06:10 |
April | 14357.44 | 03-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 825.42 | 03-APR-07:19 | 8164.95 | 21-APR-15:39 | 6.85 | 03-APR-05:10 | 104950.83 | 03-APR-06:10 |
May | 13946.31 | 12-MAY-07:10 | 2323.70 | 01-MAY-19:30 | 40437.79 | 01-MAY-07:10 | 824.88 | 12-MAY-07:19 | 21472.88 | 18-MAY-15:09 | 6.85 | 01-MAY-06:10 | 39381.97 | 01-MAY-06:10 |
June | 14338.81 | 30-JUN-07:10 | 2323.70 | 01-JUN-19:00 | 40437.79 | 01-JUN-07:10 | 825.39 | 30-JUN-07:19 | 26832.45 | 30-JUN-15:09 | 6.85 | 24-JUN-16:10 | 8756.86 | 02-JUN-06:19 |
July | 13952.17 | 03-JUL-07:10 | 2323.70 | 01-JUL-20:19 | 40437.79 | 03-JUL-07:10 | 824.89 | 03-JUL-07:19 | 31453.47 | 05-JUL-10:30 | 6.85 | 16-JUL-16:19 | 4008.69 | 10-JUL-06:19 |
August | 15336.49 | 31-AUG-07:10 | 3824.74 | 15-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 826.71 | 31-AUG-07:19 | 24743.75 | 08-AUG-15:00 | 6.85 | 05-AUG-16:10 | 6626.23 | 18-AUG-06:19 |
September | 15432.79 | 19-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 826.83 | 19-SEP-07:19 | 21690.34 | 01-SEP-15:39 | 6.85 | 01-SEP-05:10 | 15652.19 | 28-SEP-06:10 |
October | 17566.35 | 31-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 829.65 | 31-OCT-07:19 | 9002.08 | 20-OCT-14:39 | 6.85 | 02-OCT-11:09 | 101210.61 | 30-OCT-06:10 |
November | 17672.30 | 06-NOV-16:49 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 829.61 | 01-NOV-07:19 | 5421.58 | 27-NOV-07:10 | 6.85 | 03-NOV-05:10 | 166111.28 | 27-NOV-07:10 |
December | 17672.30 | 01-DEC-16:19 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 829.79 | 26-DEC-08:20 | 7817.72 | 26-DEC-07:10 | 6.85 | 01-DEC-17:19 | 203268.66 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 13946.31 | 2323.70 | 40437.79 | 824.88 | 5421.58 | 6.85 | 4008.69 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 40437.79 | 829.79 | 31453.47 | 6.85 | 203268.66 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 411.95 | 19-JAN-07:10 | 0.00 | 0.00 | 2208.01 | 02-JAN-08:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 394.68 | 21-FEB-07:10 | 0.00 | 0.00 | 2208.01 | 01-FEB-17:40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1114.00 | 31-MAR-15:09 | 0.00 | 0.00 | 2208.01 | 01-MAR-17:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 14163.30 | 23-APR-16:19 | 0.00 | 0.00 | 2208.01 | 03-APR-06:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 40816.72 | 25-MAY-15:00 | 0.00 | 0.00 | 2208.01 | 01-MAY-06:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 60322.93 | 29-JUN-15:00 | 0.00 | 0.00 | 2208.01 | 30-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 67628.11 | 05-JUL-11:50 | 0.00 | 0.00 | 2208.01 | 15-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 52066.24 | 31-AUG-12:50 | 0.00 | 0.00 | 2208.01 | 08-AUG-10:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 39372.60 | 01-SEP-13:20 | 0.00 | 0.00 | 2208.01 | 23-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 15435.26 | 19-OCT-14:00 | 0.00 | 0.00 | 2208.01 | 02-OCT-17:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5301.67 | 01-NOV-14:00 | 0.00 | 0.00 | 2208.01 | 02-NOV-12:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 460.18 | 30-DEC-07:10 | 0.00 | 0.00 | 2208.01 | 01-DEC-17:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 394.68 | 0.00 | 0.00 | 2208.01 | 0.00 | 0.00 | |||
Maximum of Months | 67628.11 | 0.00 | 0.00 | 2208.01 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 252791.27 | 02-JAN-08:09 | 17672.30 | 40437.79 | 3824.74 | 814.34 | 6280.95 | 6.85 | 181546.28 | 0.00 | 0.00 |
February | 214367.63 | 13-FEB-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6148.08 | 6.85 | 177699.93 | 0.00 | 0.00 |
March | 199712.48 | 06-MAR-07:10 | 5048.46 | 18346.02 | 0.00 | 243.14 | 5546.75 | 6.85 | 168313.25 | 0.00 | 0.00 |
April | 135176.51 | 03-APR-06:10 | 5579.02 | 18346.02 | 0.00 | 243.20 | 3589.38 | 6.85 | 104950.83 | 253.21 | 0.00 |
May | 115510.60 | 25-MAY-15:20 | 13903.46 | 38454.47 | 0.00 | 823.69 | 19476.01 | 6.85 | 0.00 | 40638.12 | 0.00 |
June | 139609.23 | 29-JUN-15:30 | 13903.46 | 38454.47 | 0.00 | 823.69 | 25028.92 | 6.85 | 0.00 | 59183.84 | 0.00 |
July | 151851.09 | 05-JUL-12:20 | 13903.46 | 38626.93 | 0.00 | 823.79 | 31453.47 | 6.85 | 0.00 | 67036.59 | 0.00 |
August | 129981.43 | 08-AUG-15:39 | 13903.46 | 38454.47 | 0.00 | 823.69 | 24393.18 | 6.85 | 0.00 | 50191.77 | 0.00 |
September | 114915.82 | 01-SEP-15:39 | 13903.46 | 38454.47 | 0.00 | 823.69 | 21690.34 | 6.85 | 0.00 | 37829.01 | 0.00 |
October | 135536.10 | 30-OCT-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3587.83 | 6.85 | 101210.61 | 218.05 | 0.00 |
November | 202197.45 | 27-NOV-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 5421.58 | 6.85 | 166111.28 | 144.96 | 0.00 |
December | 241606.00 | 26-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 7817.72 | 6.85 | 203268.66 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 114915.82 | 5048.46 | 18346.02 | 0.00 | 243.14 | 3587.83 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 252791.27 | 17672.30 | 40437.79 | 3824.74 | 823.79 | 31453.47 | 6.85 | 203268.66 | 67036.59 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 170954.33 | 05-JAN-07:40 | 0.00 | 13667.92 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 170529.02 | 14-FEB-07:30 | 0.00 | 13879.65 | 24-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 133906.87 | 15-MAR-06:00 | 0.00 | 13904.76 | 02-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 9612.62 | 05-APR-06:10 | 0.00 | 13335.99 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 20255.03 | 13-MAY-06:10 | 0.00 | 12363.17 | 02-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 3122.43 | 03-JUN-06:30 | 0.00 | 10823.36 | 02-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 10147.80 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 798.84 | 18-AUG-20:40 | 0.00 | 10063.86 | 03-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 18377.46 | 21-SEP-06:10 | 0.00 | 10083.31 | 27-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 6690.29 | 30-OCT-06:30 | 0.00 | 10199.91 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 19338.36 | 25-NOV-07:30 | 0.00 | 11326.60 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 163529.97 | 20-DEC-07:00 | 0.00 | 12673.27 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10063.86 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 170954.33 | 0.00 | 13904.76 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.21 | 2.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.71 | 1.00 | 24.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 2.50 | 19.22 | 2.33 | 19.29 | 1.00 | 20.22 | 1.00 | 20.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.35 | 2.17 | 19.35 | 1.00 | 24.71 | 1.00 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.09 | 2.67 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
March | 0.17 | 19.37 | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.73 | 0.50 | 24.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
December | 1.83 | 19.34 | 1.67 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Annual Sum or Average | 5.50 | 19.20 | 4.83 | 19.34 | 0.50 | 19.59 | 0.50 | 19.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.37 | 2.67 | 19.46 | 0.50 | 24.73 | 0.50 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 18.85 | 7.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
February | 3.00 | 19.14 | 2.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 1.33 | 18.45 | 0.83 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.33 | 24.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.57 | 1.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 6.83 | 18.85 | 5.33 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 22.00 | 18.85 | 17.33 | 19.10 | 0.33 | 19.14 | 0.33 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.50 | 19.14 | 7.50 | 19.26 | 0.33 | 24.67 | 0.33 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 105.83 | 16.68 | 57.50 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
February | 57.50 | 16.73 | 27.00 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
March | 18.33 | 17.13 | 9.00 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
April | 1.17 | 17.09 | 0.17 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.25 | 2.17 | 26.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 18.68 | 0.50 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
November | 19.83 | 16.59 | 8.33 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
December | 83.67 | 16.25 | 42.83 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
Annual Sum or Average | 287.00 | 16.60 | 145.33 | 17.11 | 2.33 | 17.16 | 2.17 | 17.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 105.83 | 18.68 | 57.50 | 18.96 | 2.33 | 26.25 | 2.17 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.00 | 14.71 | 13.50 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
February | 29.50 | 14.88 | 2.33 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
March | 8.50 | 15.20 | 0.67 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
April | 0.83 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.62 | 1.33 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.98 | 5.50 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.79 | 5.33 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.88 | 3.83 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.83 | 27.37 |
October | 0.17 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
November | 13.17 | 15.15 | 2.33 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
December | 52.00 | 14.60 | 14.17 | 14.59 | 0.00 | 14.59 | 0.00 | 14.59 |
Annual Sum or Average | 159.17 | 14.78 | 33.00 | 14.78 | 17.33 | 15.86 | 16.83 | 16.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 0.00 | 14.59 |
Maximum of Months | 55.00 | 16.67 | 14.17 | 16.67 | 5.83 | 27.98 | 5.50 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.00 | 15.10 | 10.50 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
February | 20.67 | 15.15 | 2.33 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
March | 6.67 | 15.45 | 0.67 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
April | 0.67 | 16.67 | 0.00 | 16.67 | 1.17 | 23.80 | 1.17 | 25.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.49 | 1.83 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.68 | 2.83 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.81 | 5.17 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.86 | 5.67 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.84 | 3.67 | 27.84 |
October | 0.17 | 16.77 | 0.00 | 16.77 | 2.00 | 27.05 | 2.00 | 27.46 |
November | 10.67 | 15.21 | 1.50 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
December | 42.67 | 14.84 | 9.50 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
Annual Sum or Average | 127.50 | 15.06 | 24.50 | 15.18 | 22.83 | 16.82 | 22.33 | 18.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 0.00 | 14.92 |
Maximum of Months | 46.00 | 16.77 | 10.50 | 16.77 | 5.67 | 27.86 | 5.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.83 | 14.66 | 13.33 | 14.67 | 0.00 | 14.67 | 0.00 | 14.67 |
February | 29.67 | 14.88 | 4.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
March | 8.17 | 15.17 | 1.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
April | 0.83 | 16.70 | 0.00 | 16.70 | 1.33 | 23.91 | 0.83 | 25.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.11 | 1.83 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.92 | 1.67 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.14 | 5.00 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.98 | 4.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.13 | 1.00 | 28.13 |
October | 0.17 | 16.69 | 0.00 | 16.69 | 0.17 | 21.98 | 0.17 | 23.74 |
November | 12.83 | 15.10 | 2.33 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
December | 51.00 | 14.56 | 13.17 | 14.53 | 0.00 | 14.53 | 0.00 | 14.53 |
Annual Sum or Average | 155.50 | 14.74 | 34.17 | 14.73 | 25.00 | 16.28 | 14.50 | 17.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 0.00 | 14.53 |
Maximum of Months | 52.83 | 16.70 | 13.33 | 16.70 | 8.67 | 28.14 | 5.00 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 94.67 | 18.47 | 75.83 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
February | 26.33 | 18.96 | 21.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 15.33 | 18.89 | 12.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.67 | 0.67 | 24.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 19.21 | 1.67 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
December | 50.50 | 17.96 | 37.33 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
Annual Sum or Average | 189.00 | 18.44 | 148.33 | 18.79 | 0.67 | 18.80 | 0.67 | 18.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.67 | 19.44 | 75.83 | 19.44 | 0.67 | 24.67 | 0.67 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.17 | 15.37 | 5.17 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
February | 4.33 | 16.25 | 0.17 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
March | 2.33 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.62 | 2.50 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.48 | 3.33 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.59 | 3.17 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
December | 14.50 | 15.18 | 2.83 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
Annual Sum or Average | 40.83 | 15.45 | 8.17 | 15.49 | 9.33 | 17.42 | 9.33 | 18.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.17 | 17.08 | 5.17 | 17.08 | 3.33 | 27.62 | 3.33 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 134.50 | 15.36 | 122.00 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
February | 84.00 | 15.99 | 81.83 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
March | 77.33 | 16.84 | 76.17 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
April | 32.17 | 18.00 | 32.17 | 18.00 | 0.33 | 18.05 | 0.33 | 18.09 |
May | 5.33 | 19.35 | 5.33 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.39 | 0.50 | 26.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.55 | 2.17 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.54 | 4.17 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.59 | 4.00 | 27.59 |
October | 23.17 | 19.02 | 23.17 | 19.02 | 1.83 | 19.35 | 1.83 | 19.66 |
November | 54.17 | 17.77 | 53.83 | 17.77 | 0.00 | 17.77 | 0.00 | 17.77 |
December | 110.17 | 15.65 | 103.83 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
Annual Sum or Average | 520.83 | 16.36 | 498.33 | 16.37 | 13.00 | 16.51 | 13.00 | 16.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | 0.00 | 15.35 |
Maximum of Months | 134.50 | 19.35 | 122.00 | 19.35 | 4.17 | 27.59 | 4.17 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.17 | 15.17 | 5.33 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
February | 3.83 | 16.36 | 0.17 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
March | 2.50 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.68 | 0.33 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.56 | 1.00 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 0.17 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.68 | 3.50 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.64 | 3.00 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.84 | 0.67 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
December | 15.33 | 15.12 | 3.83 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
Annual Sum or Average | 41.17 | 15.32 | 9.33 | 15.30 | 17.33 | 18.46 | 8.67 | 19.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.17 | 17.01 | 5.33 | 17.01 | 6.33 | 27.84 | 3.50 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.67 | 17.09 | 30.67 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
February | 17.67 | 17.66 | 9.83 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
March | 5.33 | 17.79 | 2.83 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
April | 0.33 | 19.41 | 0.33 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.83 | 3.00 | 24.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.00 | 18.36 | 1.67 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
December | 44.33 | 16.58 | 25.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
Annual Sum or Average | 122.33 | 17.06 | 70.33 | 17.51 | 3.00 | 17.62 | 3.00 | 17.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.67 | 19.41 | 30.67 | 19.41 | 3.00 | 24.83 | 3.00 | 24.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.50 | 15.02 | 6.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
February | 8.67 | 15.54 | 0.67 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
March | 2.17 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.69 | 2.33 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.99 | 5.33 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.80 | 4.67 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.01 | 3.83 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.60 | 1.33 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
December | 25.33 | 14.97 | 7.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
Annual Sum or Average | 61.83 | 15.14 | 13.83 | 15.14 | 17.67 | 17.55 | 17.50 | 19.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.33 | 16.59 | 7.17 | 16.59 | 5.33 | 28.01 | 5.33 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 15.31 | 2.33 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
February | 4.67 | 15.96 | 0.17 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
March | 1.17 | 16.40 | 0.00 | 16.40 | 0.17 | 17.76 | 0.17 | 18.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.89 | 1.17 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.48 | 2.00 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.61 | 2.50 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.97 | 6.67 | 26.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.81 | 5.50 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.81 | 4.67 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.82 | 3.17 | 27.82 |
November | 1.00 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
December | 17.33 | 15.23 | 3.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
Annual Sum or Average | 40.67 | 15.41 | 5.67 | 15.48 | 26.00 | 19.82 | 25.83 | 21.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 | 15.29 |
Maximum of Months | 17.33 | 16.64 | 3.17 | 16.64 | 6.83 | 27.89 | 6.67 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.67 | 15.00 | 5.67 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
February | 8.17 | 15.60 | 1.00 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
March | 2.33 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.24 | 1.00 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.11 | 1.67 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.83 | 1.50 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.07 | 4.67 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.93 | 3.67 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.98 | 1.17 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
November | 1.17 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
December | 25.83 | 14.94 | 7.83 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
Annual Sum or Average | 61.17 | 15.12 | 14.50 | 15.11 | 24.50 | 18.26 | 14.00 | 19.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 | 14.93 |
Maximum of Months | 25.83 | 16.64 | 7.83 | 16.64 | 8.17 | 28.24 | 4.67 | 28.19 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.15 | 330.83 | 20.98 | 330.83 | 20.90 |
February | 454.00 | 21.79 | 116.33 | 21.61 | 116.33 | 21.49 |
March | 514.00 | 22.53 | 35.50 | 22.43 | 35.50 | 22.35 |
April | 456.00 | 23.54 | 0.00 | 23.54 | 0.00 | 23.54 |
May | 141.83 | 23.94 | 142.33 | 24.31 | 0.00 | 24.31 |
June | 16.33 | 24.00 | 325.17 | 24.36 | 0.00 | 24.36 |
July | 1.50 | 24.59 | 481.50 | 24.42 | 1.50 | 24.42 |
August | 0.00 | 0.00 | 457.00 | 24.31 | 0.00 | 24.31 |
September | 26.83 | 23.93 | 158.17 | 24.66 | 0.00 | 24.66 |
October | 343.83 | 23.72 | 8.83 | 23.76 | 0.00 | 23.76 |
November | 489.00 | 22.82 | 32.67 | 22.70 | 32.67 | 22.60 |
December | 497.00 | 21.44 | 236.50 | 21.24 | 236.50 | 21.14 |
Annual Sum or Average | 3442.33 | 22.44 | 2324.83 | 22.78 | 753.33 | 22.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20.98 | 0.00 | 20.90 |
Maximum of Months | 514.00 | 24.59 | 481.50 | 24.66 | 330.83 | 24.66 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.55 | 443.83 | 20.49 | 443.83 | 20.47 |
February | 454.00 | 20.94 | 308.00 | 20.81 | 308.00 | 20.75 |
March | 514.00 | 21.61 | 172.00 | 21.41 | 172.00 | 21.28 |
April | 474.17 | 22.87 | 10.00 | 22.82 | 10.00 | 22.78 |
May | 204.67 | 23.67 | 129.17 | 24.02 | 0.00 | 24.02 |
June | 37.33 | 23.75 | 286.17 | 24.24 | 0.00 | 24.24 |
July | 2.83 | 24.39 | 457.33 | 24.35 | 2.83 | 24.35 |
August | 15.67 | 23.52 | 422.00 | 24.22 | 0.00 | 24.22 |
September | 141.67 | 23.57 | 101.67 | 23.98 | 3.67 | 23.98 |
October | 469.83 | 22.88 | 1.17 | 22.88 | 1.17 | 22.87 |
November | 489.00 | 21.51 | 153.17 | 21.31 | 153.17 | 21.19 |
December | 497.00 | 20.65 | 397.50 | 20.57 | 397.50 | 20.53 |
Annual Sum or Average | 3802.17 | 21.78 | 2882.00 | 22.04 | 1492.17 | 21.77 |
Minimum of Months | 2.83 | 20.55 | 1.17 | 20.49 | 0.00 | 20.47 |
Maximum of Months | 514.00 | 24.39 | 457.33 | 24.35 | 443.83 | 24.35 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.16 | 485.83 | 20.14 | 485.83 | 20.14 |
February | 454.00 | 20.47 | 399.50 | 20.40 | 399.50 | 20.37 |
March | 514.00 | 21.08 | 299.17 | 20.87 | 299.17 | 20.78 |
April | 477.50 | 22.31 | 86.50 | 22.04 | 86.50 | 21.84 |
May | 233.83 | 23.45 | 123.17 | 23.79 | 2.00 | 23.78 |
June | 71.50 | 23.45 | 266.67 | 24.09 | 0.00 | 24.09 |
July | 20.00 | 23.53 | 425.83 | 24.29 | 2.83 | 24.29 |
August | 39.17 | 23.38 | 384.00 | 24.11 | 0.00 | 24.11 |
September | 260.83 | 23.30 | 63.00 | 23.49 | 6.33 | 23.50 |
October | 495.00 | 22.10 | 67.33 | 21.89 | 67.33 | 21.73 |
November | 489.00 | 20.76 | 292.50 | 20.56 | 292.50 | 20.46 |
December | 497.00 | 20.20 | 470.00 | 20.17 | 470.00 | 20.16 |
Annual Sum or Average | 4053.83 | 21.38 | 3363.50 | 21.55 | 2112.00 | 21.27 |
Minimum of Months | 20.00 | 20.16 | 63.00 | 20.14 | 0.00 | 20.14 |
Maximum of Months | 514.00 | 23.53 | 485.83 | 24.29 | 485.83 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.59 | 502.00 | 19.59 | 502.00 | 19.59 |
February | 454.00 | 19.82 | 450.83 | 19.82 | 450.83 | 19.82 |
March | 514.00 | 20.36 | 431.00 | 20.26 | 431.00 | 20.23 |
April | 476.83 | 21.40 | 193.00 | 21.04 | 190.67 | 20.84 |
May | 248.17 | 22.96 | 132.83 | 23.39 | 6.50 | 23.35 |
June | 92.83 | 23.58 | 281.33 | 24.10 | 9.83 | 24.14 |
July | 71.17 | 24.73 | 432.33 | 24.42 | 43.33 | 24.53 |
August | 88.00 | 23.17 | 344.67 | 23.97 | 6.00 | 23.97 |
September | 331.50 | 22.70 | 59.33 | 22.89 | 11.67 | 22.89 |
October | 498.00 | 21.15 | 167.83 | 20.84 | 167.83 | 20.65 |
November | 489.00 | 19.98 | 414.50 | 19.89 | 414.50 | 19.85 |
December | 497.00 | 19.63 | 497.00 | 19.63 | 497.00 | 19.63 |
Annual Sum or Average | 4262.50 | 20.83 | 3906.67 | 21.02 | 2731.17 | 20.76 |
Minimum of Months | 71.17 | 19.59 | 59.33 | 19.59 | 6.00 | 19.59 |
Maximum of Months | 514.00 | 24.73 | 502.00 | 24.42 | 502.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 502.00 | 19.73 | 502.00 | 19.73 |
February | 454.00 | 19.97 | 417.67 | 19.91 | 417.67 | 19.89 |
March | 511.67 | 20.82 | 351.83 | 20.58 | 351.83 | 20.47 |
April | 416.83 | 21.90 | 130.33 | 21.52 | 118.83 | 21.22 |
May | 156.00 | 23.22 | 208.00 | 23.99 | 3.33 | 23.98 |
June | 72.00 | 24.69 | 372.50 | 24.44 | 29.33 | 24.58 |
July | 76.17 | 25.60 | 452.00 | 24.64 | 57.67 | 24.81 |
August | 68.50 | 24.21 | 411.83 | 24.32 | 26.50 | 24.41 |
September | 246.00 | 22.78 | 135.83 | 23.35 | 15.00 | 23.37 |
October | 457.17 | 21.29 | 151.50 | 21.04 | 140.67 | 20.83 |
November | 489.00 | 20.10 | 381.17 | 19.95 | 381.17 | 19.88 |
December | 497.00 | 19.73 | 497.00 | 19.73 | 497.00 | 19.73 |
Annual Sum or Average | 3946.33 | 20.96 | 4011.67 | 21.32 | 2541.00 | 21.04 |
Minimum of Months | 68.50 | 19.73 | 130.33 | 19.73 | 3.33 | 19.73 |
Maximum of Months | 511.67 | 25.60 | 502.00 | 24.64 | 502.00 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.67 | 20.06 | 421.33 | 19.85 | 421.33 | 19.78 |
February | 431.17 | 20.59 | 313.33 | 20.27 | 313.33 | 20.13 |
March | 461.33 | 21.05 | 297.33 | 20.80 | 285.83 | 20.64 |
April | 389.83 | 21.80 | 161.67 | 21.54 | 138.33 | 21.30 |
May | 181.67 | 22.88 | 190.00 | 23.63 | 8.67 | 23.58 |
June | 111.17 | 23.69 | 315.17 | 24.17 | 19.00 | 24.25 |
July | 97.33 | 24.88 | 422.50 | 24.53 | 56.50 | 24.69 |
August | 92.33 | 24.09 | 388.33 | 24.28 | 27.83 | 24.40 |
September | 244.50 | 22.96 | 170.67 | 23.64 | 21.00 | 23.75 |
October | 420.33 | 21.46 | 181.83 | 21.48 | 131.33 | 21.27 |
November | 464.00 | 20.41 | 313.33 | 20.14 | 313.33 | 20.02 |
December | 497.00 | 20.04 | 446.00 | 19.89 | 446.00 | 19.84 |
Annual Sum or Average | 3886.33 | 21.24 | 3621.50 | 21.53 | 2182.50 | 21.24 |
Minimum of Months | 92.33 | 20.04 | 161.67 | 19.85 | 8.67 | 19.78 |
Maximum of Months | 497.00 | 24.88 | 446.00 | 24.53 | 446.00 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 486.33 | 19.73 | 486.33 | 19.72 |
February | 454.00 | 20.12 | 397.50 | 19.99 | 397.50 | 19.94 |
March | 491.83 | 20.66 | 358.00 | 20.46 | 354.83 | 20.37 |
April | 412.33 | 21.51 | 185.83 | 21.26 | 162.67 | 21.03 |
May | 196.17 | 23.05 | 196.17 | 23.70 | 16.50 | 23.71 |
June | 104.83 | 23.76 | 331.33 | 24.20 | 20.50 | 24.29 |
July | 95.67 | 25.13 | 439.17 | 24.60 | 61.33 | 24.76 |
August | 97.00 | 23.97 | 390.67 | 24.24 | 28.83 | 24.34 |
September | 273.83 | 22.78 | 125.17 | 23.32 | 15.50 | 23.38 |
October | 455.67 | 21.22 | 165.00 | 20.99 | 149.83 | 20.78 |
November | 489.00 | 20.14 | 382.17 | 19.97 | 382.17 | 19.90 |
December | 497.00 | 19.73 | 493.50 | 19.73 | 493.50 | 19.73 |
Annual Sum or Average | 4069.33 | 20.98 | 3950.83 | 21.29 | 2569.50 | 21.02 |
Minimum of Months | 95.67 | 19.73 | 125.17 | 19.73 | 15.50 | 19.72 |
Maximum of Months | 502.00 | 25.13 | 493.50 | 24.60 | 493.50 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 502.00 | 19.63 | 502.00 | 19.63 |
February | 454.00 | 19.97 | 454.00 | 19.97 | 454.00 | 19.97 |
March | 514.00 | 20.32 | 487.50 | 20.30 | 487.50 | 20.30 |
April | 485.00 | 20.91 | 299.00 | 20.75 | 299.00 | 20.68 |
May | 377.17 | 22.71 | 81.50 | 22.85 | 17.00 | 22.78 |
June | 179.67 | 23.42 | 186.67 | 23.79 | 12.67 | 23.81 |
July | 49.67 | 24.46 | 405.17 | 24.29 | 29.83 | 24.34 |
August | 63.17 | 23.40 | 347.67 | 24.01 | 2.83 | 24.01 |
September | 302.33 | 23.19 | 62.50 | 23.37 | 7.67 | 23.38 |
October | 498.17 | 21.84 | 71.17 | 21.68 | 71.17 | 21.56 |
November | 489.00 | 20.47 | 389.33 | 20.38 | 389.33 | 20.34 |
December | 497.00 | 19.83 | 497.00 | 19.83 | 497.00 | 19.83 |
Annual Sum or Average | 4411.17 | 21.02 | 3783.50 | 21.12 | 2770.00 | 20.87 |
Minimum of Months | 49.67 | 19.63 | 62.50 | 19.63 | 2.83 | 19.63 |
Maximum of Months | 514.00 | 24.46 | 502.00 | 24.29 | 502.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 502.00 | 19.85 | 502.00 | 19.85 |
February | 454.00 | 20.15 | 448.67 | 20.14 | 448.67 | 20.14 |
March | 514.00 | 20.72 | 401.33 | 20.57 | 401.33 | 20.52 |
April | 459.33 | 21.89 | 140.50 | 21.51 | 140.50 | 21.28 |
May | 230.33 | 23.22 | 148.50 | 23.74 | 1.50 | 23.72 |
June | 71.67 | 23.91 | 327.67 | 24.30 | 15.17 | 24.36 |
July | 46.83 | 25.98 | 466.00 | 24.60 | 43.50 | 24.72 |
August | 36.50 | 24.62 | 447.83 | 24.37 | 15.50 | 24.43 |
September | 180.50 | 23.28 | 160.17 | 23.88 | 9.00 | 23.88 |
October | 447.00 | 22.15 | 61.00 | 22.09 | 47.50 | 21.96 |
November | 489.00 | 20.65 | 332.50 | 20.48 | 332.50 | 20.41 |
December | 497.00 | 19.93 | 497.00 | 19.93 | 497.00 | 19.93 |
Annual Sum or Average | 3928.17 | 21.15 | 3933.17 | 21.49 | 2454.17 | 21.21 |
Minimum of Months | 36.50 | 19.85 | 61.00 | 19.85 | 1.50 | 19.85 |
Maximum of Months | 514.00 | 25.98 | 502.00 | 24.60 | 502.00 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.66 | 484.50 | 18.62 | 484.50 | 18.60 |
February | 454.00 | 19.67 | 376.83 | 19.47 | 376.83 | 19.40 |
March | 506.83 | 20.23 | 372.67 | 19.98 | 372.67 | 19.89 |
April | 443.00 | 21.22 | 186.83 | 20.91 | 180.83 | 20.70 |
May | 307.33 | 22.46 | 120.00 | 22.90 | 12.67 | 22.82 |
June | 221.00 | 23.02 | 228.50 | 23.64 | 51.50 | 23.67 |
July | 106.17 | 24.19 | 414.33 | 24.36 | 72.17 | 24.43 |
August | 109.17 | 23.37 | 402.17 | 24.14 | 40.83 | 24.20 |
September | 218.50 | 22.66 | 191.83 | 23.61 | 20.33 | 23.70 |
October | 413.33 | 21.70 | 116.83 | 21.88 | 65.00 | 21.75 |
November | 485.33 | 20.52 | 284.00 | 20.24 | 284.00 | 20.11 |
December | 497.00 | 19.06 | 479.00 | 19.01 | 479.00 | 18.99 |
Annual Sum or Average | 4263.67 | 20.74 | 3657.50 | 20.97 | 2440.33 | 20.67 |
Minimum of Months | 106.17 | 18.66 | 116.83 | 18.62 | 12.67 | 18.60 |
Maximum of Months | 506.83 | 24.19 | 484.50 | 24.36 | 484.50 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 494.67 | 19.85 | 494.67 | 19.85 |
February | 454.00 | 20.21 | 427.67 | 20.16 | 427.67 | 20.14 |
March | 511.33 | 20.69 | 403.17 | 20.54 | 403.17 | 20.48 |
April | 454.67 | 21.58 | 186.67 | 21.28 | 181.83 | 21.08 |
May | 247.50 | 23.12 | 143.67 | 23.54 | 7.33 | 23.50 |
June | 111.33 | 23.41 | 288.67 | 24.06 | 8.83 | 24.08 |
July | 45.83 | 26.12 | 469.67 | 24.61 | 45.50 | 24.74 |
August | 40.33 | 24.46 | 439.33 | 24.35 | 13.67 | 24.42 |
September | 188.83 | 23.37 | 152.83 | 23.91 | 11.67 | 23.95 |
October | 446.67 | 22.16 | 66.50 | 22.06 | 54.33 | 21.91 |
November | 489.00 | 20.63 | 337.67 | 20.48 | 337.67 | 20.41 |
December | 497.00 | 19.94 | 496.50 | 19.94 | 496.50 | 19.94 |
Annual Sum or Average | 3988.50 | 21.15 | 3907.00 | 21.46 | 2482.83 | 21.18 |
Minimum of Months | 40.33 | 19.87 | 66.50 | 19.85 | 7.33 | 19.85 |
Maximum of Months | 511.33 | 26.12 | 496.50 | 24.61 | 496.50 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.75 | 502.00 | 19.75 | 502.00 | 19.75 |
February | 454.00 | 20.05 | 446.67 | 20.04 | 446.67 | 20.04 |
March | 514.00 | 20.60 | 389.33 | 20.47 | 389.33 | 20.42 |
April | 475.67 | 21.82 | 133.83 | 21.51 | 132.50 | 21.30 |
May | 224.83 | 23.29 | 134.50 | 23.68 | 3.17 | 23.66 |
June | 56.67 | 23.97 | 292.00 | 24.23 | 8.00 | 24.26 |
July | 44.00 | 25.61 | 460.00 | 24.50 | 40.67 | 24.60 |
August | 35.17 | 23.34 | 393.33 | 24.11 | 0.33 | 24.11 |
September | 270.33 | 23.13 | 73.67 | 23.37 | 6.83 | 23.38 |
October | 495.00 | 21.79 | 95.17 | 21.54 | 95.17 | 21.37 |
November | 489.00 | 20.34 | 368.17 | 20.20 | 368.17 | 20.15 |
December | 497.00 | 19.82 | 497.00 | 19.82 | 497.00 | 19.82 |
Annual Sum or Average | 4057.67 | 21.04 | 3785.67 | 21.28 | 2489.83 | 21.00 |
Minimum of Months | 35.17 | 19.75 | 73.67 | 19.75 | 0.33 | 19.75 |
Maximum of Months | 514.00 | 25.61 | 502.00 | 24.50 | 502.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.62 | 427.00 | 19.62 | 427.00 | 19.62 |
February | 385.00 | 20.07 | 349.50 | 20.00 | 349.50 | 19.97 |
March | 427.83 | 20.97 | 260.50 | 20.71 | 260.50 | 20.59 |
April | 349.50 | 22.17 | 98.33 | 21.95 | 77.83 | 21.68 |
May | 128.83 | 23.53 | 183.50 | 24.26 | 3.67 | 24.28 |
June | 47.67 | 25.40 | 320.67 | 24.62 | 27.33 | 24.77 |
July | 52.83 | 26.29 | 397.83 | 24.80 | 49.67 | 24.97 |
August | 38.83 | 24.87 | 373.67 | 24.46 | 17.00 | 24.56 |
September | 183.17 | 23.20 | 127.83 | 23.80 | 8.67 | 23.84 |
October | 380.67 | 21.80 | 88.00 | 21.68 | 72.00 | 21.48 |
November | 417.00 | 20.35 | 289.17 | 20.14 | 289.17 | 20.06 |
December | 422.00 | 19.67 | 418.50 | 19.67 | 418.50 | 19.66 |
Annual Sum or Average | 3260.33 | 21.09 | 3334.50 | 21.49 | 2000.83 | 21.20 |
Minimum of Months | 38.83 | 19.62 | 88.00 | 19.62 | 3.67 | 19.62 |
Maximum of Months | 427.83 | 26.29 | 427.00 | 24.80 | 427.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.50 | 20.27 | 405.83 | 20.04 | 405.83 | 19.95 |
February | 428.17 | 20.94 | 279.83 | 20.59 | 279.83 | 20.43 |
March | 451.83 | 21.32 | 253.50 | 21.11 | 236.17 | 20.92 |
April | 376.83 | 22.22 | 108.50 | 22.06 | 84.83 | 21.84 |
May | 157.17 | 23.24 | 190.50 | 23.94 | 3.17 | 23.93 |
June | 78.50 | 24.09 | 328.33 | 24.29 | 16.50 | 24.36 |
July | 61.00 | 25.85 | 446.67 | 24.63 | 53.33 | 24.78 |
August | 54.33 | 24.83 | 433.33 | 24.39 | 22.50 | 24.50 |
September | 189.83 | 23.44 | 196.50 | 24.04 | 23.50 | 24.16 |
October | 400.50 | 22.09 | 130.33 | 22.23 | 71.50 | 22.08 |
November | 459.50 | 20.87 | 255.00 | 20.56 | 255.00 | 20.41 |
December | 497.00 | 20.31 | 425.33 | 20.13 | 425.33 | 20.06 |
Annual Sum or Average | 3646.17 | 21.50 | 3453.67 | 21.85 | 1877.50 | 21.55 |
Minimum of Months | 54.33 | 20.27 | 108.50 | 20.04 | 3.17 | 19.95 |
Maximum of Months | 497.00 | 25.85 | 446.67 | 24.63 | 425.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 480.00 | 19.83 | 480.00 | 19.82 |
February | 454.00 | 20.35 | 379.67 | 20.20 | 379.67 | 20.14 |
March | 491.00 | 20.93 | 313.33 | 20.70 | 309.33 | 20.59 |
April | 408.33 | 21.98 | 129.17 | 21.78 | 107.17 | 21.56 |
May | 170.50 | 23.44 | 200.00 | 24.01 | 10.83 | 24.06 |
June | 70.33 | 24.13 | 347.33 | 24.32 | 16.50 | 24.39 |
July | 61.67 | 26.09 | 467.50 | 24.67 | 58.50 | 24.83 |
August | 52.17 | 24.69 | 429.67 | 24.36 | 22.00 | 24.46 |
September | 210.83 | 23.20 | 148.50 | 23.75 | 13.50 | 23.80 |
October | 442.83 | 21.84 | 102.83 | 21.70 | 84.50 | 21.51 |
November | 489.00 | 20.51 | 326.50 | 20.30 | 326.50 | 20.21 |
December | 497.00 | 19.89 | 485.83 | 19.87 | 485.83 | 19.87 |
Annual Sum or Average | 3849.67 | 21.18 | 3810.33 | 21.54 | 2294.33 | 21.26 |
Minimum of Months | 52.17 | 19.88 | 102.83 | 19.83 | 10.83 | 19.82 |
Maximum of Months | 502.00 | 26.09 | 485.83 | 24.67 | 485.83 | 24.83 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.14777 | 14.87573 | -0.6149 | 14.16441 |
February | 454.00000 | 21.78923 | 17.43196 | -0.4291 | 9.54120 |
March | 514.00000 | 22.53103 | 21.31146 | -0.2205 | 6.96815 |
April | 485.00000 | 23.60474 | 20.61488 | 0.06302 | 5.60271 |
May | 508.00000 | 24.29982 | 32.28782 | -0.5245 | 11.57368 |
June | 496.00000 | 24.28422 | 44.23226 | -0.4078 | 8.88378 |
July | 497.00000 | 24.40922 | 50.54065 | -0.3078 | 7.44454 |
August | 514.00000 | 24.28304 | 49.96808 | -0.3539 | 7.91879 |
September | 485.00000 | 24.30555 | 37.62671 | -0.4669 | 10.01414 |
October | 502.00000 | 23.90514 | 30.98423 | 0.21793 | 6.34064 |
November | 489.00000 | 22.81604 | 24.39637 | -0.1319 | 6.39951 |
December | 497.00000 | 21.43910 | 17.08962 | -0.5183 | 11.52372 |
Annual Sum or Average | 5943.00000 | 23.24428 | 30.23795 | -0.3078 | 8.86651 |
Minimum of Months | 454.00000 | 21.14777 | 14.87573 | -0.6149 | 5.60271 |
Maximum of Months | 514.00000 | 24.40922 | 50.54065 | 0.21793 | 14.16441 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.55060 | 16.28423 | -0.7574 | 18.53061 |
February | 454.00000 | 20.93518 | 18.83136 | -0.6281 | 14.25534 |
March | 514.00000 | 21.61214 | 23.20832 | -0.4187 | 9.75651 |
April | 485.00000 | 22.89694 | 22.35122 | -0.0888 | 6.36293 |
May | 508.00000 | 24.06643 | 32.93795 | -0.5980 | 13.60803 |
June | 496.00000 | 24.16428 | 45.12955 | -0.4497 | 9.65855 |
July | 497.00000 | 24.31870 | 51.15340 | -0.3441 | 7.85960 |
August | 514.00000 | 24.18672 | 50.72577 | -0.3999 | 8.64443 |
September | 485.00000 | 24.02123 | 39.02146 | -0.5754 | 12.50658 |
October | 502.00000 | 22.96204 | 33.85400 | 0.00242 | 6.09071 |
November | 489.00000 | 21.51406 | 27.00138 | -0.4262 | 9.94495 |
December | 497.00000 | 20.65413 | 18.53974 | -0.7101 | 16.91661 |
Annual Sum or Average | 5943.00000 | 22.66985 | 31.70867 | -0.4486 | 11.15968 |
Minimum of Months | 454.00000 | 20.55060 | 16.28423 | -0.7574 | 6.09071 |
Maximum of Months | 514.00000 | 24.31870 | 51.15340 | 0.00242 | 18.53061 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16437 | 16.42465 | -0.8841 | 23.57856 |
February | 454.00000 | 20.46677 | 18.85119 | -0.7735 | 19.34059 |
March | 514.00000 | 21.07673 | 23.52414 | -0.5703 | 13.44560 |
April | 485.00000 | 22.34062 | 23.09563 | -0.2267 | 8.09062 |
May | 508.00000 | 23.89669 | 32.96954 | -0.6587 | 15.76136 |
June | 496.00000 | 24.07380 | 45.37436 | -0.4763 | 10.41173 |
July | 497.00000 | 24.25769 | 51.21304 | -0.3629 | 8.25378 |
August | 514.00000 | 24.08997 | 51.01495 | -0.4376 | 9.39115 |
September | 485.00000 | 23.68185 | 40.05677 | -0.7020 | 16.40801 |
October | 502.00000 | 22.12247 | 35.89566 | -0.2062 | 7.64742 |
November | 489.00000 | 20.76455 | 27.26890 | -0.6306 | 15.33760 |
December | 497.00000 | 20.19799 | 18.67878 | -0.8560 | 22.54505 |
Annual Sum or Average | 5943.00000 | 22.27578 | 32.15382 | -0.5640 | 14.14338 |
Minimum of Months | 454.00000 | 20.16437 | 16.42465 | -0.8841 | 7.64742 |
Maximum of Months | 514.00000 | 24.25769 | 51.21304 | -0.2062 | 23.57856 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.59148 | 16.32601 | -1.1111 | 33.12925 |
February | 454.00000 | 19.82181 | 19.26550 | -0.9906 | 28.09725 |
March | 514.00000 | 20.35590 | 24.20371 | -0.7865 | 20.25344 |
April | 485.00000 | 21.44911 | 23.87461 | -0.4371 | 12.21334 |
May | 508.00000 | 23.60507 | 33.51002 | -0.7288 | 19.23368 |
June | 496.00000 | 24.05715 | 45.61726 | -0.4418 | 10.32081 |
July | 497.00000 | 24.28014 | 52.02565 | -0.3080 | 8.17571 |
August | 514.00000 | 23.95702 | 51.97974 | -0.4603 | 10.41041 |
September | 485.00000 | 23.13141 | 41.97357 | -0.8738 | 23.50298 |
October | 502.00000 | 21.16883 | 36.10354 | -0.4427 | 11.65170 |
November | 489.00000 | 19.98249 | 27.61799 | -0.8555 | 23.37742 |
December | 497.00000 | 19.63233 | 18.66574 | -1.0765 | 31.72039 |
Annual Sum or Average | 5943.00000 | 21.76995 | 32.71898 | -0.7071 | 19.26124 |
Minimum of Months | 454.00000 | 19.59148 | 16.32601 | -1.1111 | 8.17571 |
Maximum of Months | 514.00000 | 24.28014 | 52.02565 | -0.3080 | 33.12925 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72649 | 17.28825 | -1.0575 | 30.92085 |
February | 454.00000 | 19.97053 | 20.19276 | -0.9184 | 25.47823 |
March | 514.00000 | 20.83870 | 24.60913 | -0.6385 | 16.74581 |
April | 485.00000 | 22.21452 | 22.95824 | -0.2171 | 10.37346 |
May | 508.00000 | 24.02071 | 32.76104 | -0.5282 | 13.76796 |
June | 496.00000 | 24.24621 | 44.93998 | -0.2919 | 8.78439 |
July | 497.00000 | 24.41201 | 51.26782 | -0.1700 | 7.54563 |
August | 514.00000 | 24.18229 | 51.23804 | -0.3203 | 9.02386 |
September | 485.00000 | 23.49978 | 41.13940 | -0.7071 | 18.86203 |
October | 502.00000 | 21.56180 | 36.06548 | -0.3385 | 10.98244 |
November | 489.00000 | 20.10435 | 28.40236 | -0.8103 | 22.01614 |
December | 497.00000 | 19.73074 | 19.51012 | -1.0379 | 30.13520 |
Annual Sum or Average | 5943.00000 | 22.06027 | 32.64717 | -0.5836 | 16.97322 |
Minimum of Months | 454.00000 | 19.72649 | 17.28825 | -1.0575 | 7.54563 |
Maximum of Months | 514.00000 | 24.41201 | 51.26782 | -0.1700 | 30.92085 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11395 | 16.48860 | -0.9065 | 26.99632 |
February | 454.00000 | 20.76107 | 18.40435 | -0.6862 | 20.47798 |
March | 514.00000 | 21.40350 | 22.70254 | -0.4869 | 15.24726 |
April | 485.00000 | 22.26028 | 21.94785 | -0.2026 | 10.94124 |
May | 508.00000 | 23.79826 | 32.69158 | -0.6122 | 16.64306 |
June | 496.00000 | 24.06288 | 45.37257 | -0.4015 | 10.52378 |
July | 497.00000 | 24.31597 | 51.58322 | -0.2422 | 8.29898 |
August | 514.00000 | 24.11805 | 51.05011 | -0.3351 | 9.60612 |
September | 485.00000 | 23.60539 | 40.08106 | -0.6424 | 18.48407 |
October | 502.00000 | 21.94719 | 34.02995 | -0.2274 | 11.23031 |
November | 489.00000 | 20.59366 | 26.66968 | -0.6698 | 19.22210 |
December | 497.00000 | 20.04174 | 18.81338 | -0.9205 | 26.59292 |
Annual Sum or Average | 5943.00000 | 22.26551 | 31.77679 | -0.5265 | 16.14471 |
Minimum of Months | 454.00000 | 20.04174 | 16.48860 | -0.9205 | 8.29898 |
Maximum of Months | 514.00000 | 24.31597 | 51.58322 | -0.2026 | 26.99632 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76371 | 17.08989 | -1.0527 | 30.86804 |
February | 454.00000 | 20.11777 | 19.80082 | -0.8933 | 25.13682 |
March | 514.00000 | 20.81907 | 24.35118 | -0.6503 | 17.92919 |
April | 485.00000 | 21.90453 | 23.43669 | -0.2953 | 11.86446 |
May | 508.00000 | 23.79408 | 33.14494 | -0.5955 | 16.82549 |
June | 496.00000 | 24.09254 | 45.63259 | -0.3642 | 10.11212 |
July | 497.00000 | 24.36527 | 51.76162 | -0.2023 | 8.20948 |
August | 514.00000 | 24.09200 | 51.62879 | -0.3498 | 9.78509 |
September | 485.00000 | 23.40406 | 41.55332 | -0.7404 | 20.51895 |
October | 502.00000 | 21.50106 | 35.93751 | -0.3503 | 11.39924 |
November | 489.00000 | 20.13964 | 28.35598 | -0.8055 | 22.02247 |
December | 497.00000 | 19.73405 | 19.40163 | -1.0398 | 30.22051 |
Annual Sum or Average | 5943.00000 | 21.99399 | 32.79300 | -0.6092 | 17.83830 |
Minimum of Months | 454.00000 | 19.73405 | 17.08989 | -1.0527 | 8.20948 |
Maximum of Months | 514.00000 | 24.36527 | 51.76162 | -0.2023 | 30.86804 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.63192 | 15.64430 | -1.0979 | 32.16448 |
February | 454.00000 | 19.97475 | 18.90217 | -0.9661 | 26.40954 |
March | 514.00000 | 20.32403 | 23.76736 | -0.8310 | 21.01470 |
April | 485.00000 | 20.91485 | 24.43637 | -0.5967 | 13.59464 |
May | 508.00000 | 23.07161 | 35.78935 | -0.9630 | 27.20749 |
June | 496.00000 | 23.83840 | 46.94692 | -0.5791 | 12.97716 |
July | 497.00000 | 24.18934 | 52.65715 | -0.3822 | 8.54167 |
August | 514.00000 | 23.99373 | 52.04158 | -0.4669 | 9.98751 |
September | 485.00000 | 23.52468 | 41.12097 | -0.7487 | 18.00322 |
October | 502.00000 | 21.85917 | 34.56960 | -0.2623 | 7.68610 |
November | 489.00000 | 20.47159 | 26.80867 | -0.7106 | 17.16423 |
December | 497.00000 | 19.82780 | 18.19646 | -1.0102 | 28.45183 |
Annual Sum or Average | 5943.00000 | 21.81742 | 32.70073 | -0.7163 | 18.55833 |
Minimum of Months | 454.00000 | 19.63192 | 15.64430 | -1.0979 | 7.68610 |
Maximum of Months | 514.00000 | 24.18934 | 52.65715 | -0.2623 | 32.16448 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84719 | 16.59673 | -1.0304 | 29.29937 |
February | 454.00000 | 20.15208 | 19.93683 | -0.8895 | 23.29634 |
March | 514.00000 | 20.71783 | 24.54222 | -0.6947 | 16.96102 |
April | 485.00000 | 21.99996 | 23.68913 | -0.2990 | 9.80707 |
May | 508.00000 | 23.84178 | 34.32984 | -0.6489 | 16.19781 |
June | 496.00000 | 24.19541 | 45.34524 | -0.3709 | 9.31517 |
July | 497.00000 | 24.42187 | 51.38005 | -0.2060 | 6.99968 |
August | 514.00000 | 24.27551 | 50.88365 | -0.3015 | 8.02750 |
September | 485.00000 | 23.92131 | 40.02066 | -0.5665 | 13.50347 |
October | 502.00000 | 22.39959 | 34.28878 | -0.1255 | 7.45015 |
November | 489.00000 | 20.64662 | 27.66436 | -0.6537 | 15.73083 |
December | 497.00000 | 19.93322 | 19.12915 | -0.9709 | 26.82071 |
Annual Sum or Average | 5943.00000 | 22.21244 | 32.43576 | -0.5610 | 15.23211 |
Minimum of Months | 454.00000 | 19.84719 | 16.59673 | -1.0304 | 6.99968 |
Maximum of Months | 514.00000 | 24.42187 | 51.38005 | -0.1255 | 29.29937 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.66131 | 13.22313 | -1.1916 | 36.29976 |
February | 454.00000 | 19.66777 | 15.53850 | -0.9030 | 25.28317 |
March | 514.00000 | 20.29121 | 19.90569 | -0.7303 | 19.67419 |
April | 485.00000 | 21.49227 | 20.81802 | -0.3895 | 11.73294 |
May | 508.00000 | 23.18758 | 33.85471 | -0.8514 | 23.93871 |
June | 496.00000 | 23.68702 | 47.26169 | -0.5714 | 14.20497 |
July | 497.00000 | 24.21411 | 52.78888 | -0.3054 | 8.48238 |
August | 514.00000 | 24.03890 | 51.93478 | -0.3539 | 9.70073 |
September | 485.00000 | 23.61707 | 39.14985 | -0.6064 | 17.06277 |
October | 502.00000 | 22.20858 | 30.85021 | -0.1237 | 9.05843 |
November | 489.00000 | 20.54994 | 23.30877 | -0.6305 | 16.22403 |
December | 497.00000 | 19.06080 | 15.58818 | -1.0940 | 32.32142 |
Annual Sum or Average | 5943.00000 | 21.73888 | 30.49152 | -0.6445 | 18.63244 |
Minimum of Months | 454.00000 | 18.66131 | 13.22313 | -1.1916 | 8.48238 |
Maximum of Months | 514.00000 | 24.21411 | 52.78888 | -0.1237 | 36.29976 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86744 | 16.45961 | -1.0288 | 29.29524 |
February | 454.00000 | 20.21415 | 19.75634 | -0.8782 | 23.24258 |
March | 514.00000 | 20.70455 | 24.41230 | -0.7023 | 17.66971 |
April | 485.00000 | 21.75414 | 23.99484 | -0.3646 | 10.94880 |
May | 508.00000 | 23.71521 | 34.41567 | -0.6875 | 17.94827 |
June | 496.00000 | 24.03663 | 46.21348 | -0.4468 | 10.76440 |
July | 497.00000 | 24.43638 | 51.61449 | -0.2167 | 7.25862 |
August | 514.00000 | 24.25054 | 51.03651 | -0.3103 | 8.22103 |
September | 485.00000 | 23.92253 | 40.14930 | -0.5719 | 13.76116 |
October | 502.00000 | 22.38712 | 34.05562 | -0.1264 | 7.50379 |
November | 489.00000 | 20.63458 | 27.68986 | -0.6579 | 15.86395 |
December | 497.00000 | 19.94325 | 19.04390 | -0.9717 | 26.84146 |
Annual Sum or Average | 5943.00000 | 22.17156 | 32.52250 | -0.5782 | 15.72934 |
Minimum of Months | 454.00000 | 19.86744 | 16.45961 | -1.0288 | 7.25862 |
Maximum of Months | 514.00000 | 24.43638 | 51.61449 | -0.1264 | 29.29524 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.75156 | 16.78457 | -1.0308 | 29.57479 |
February | 454.00000 | 20.04985 | 19.66254 | -0.8978 | 23.97796 |
March | 514.00000 | 20.59537 | 24.16079 | -0.6950 | 16.91461 |
April | 485.00000 | 21.86925 | 23.44825 | -0.3234 | 9.52653 |
May | 508.00000 | 23.82076 | 33.40646 | -0.6548 | 16.11000 |
June | 496.00000 | 24.15827 | 45.30792 | -0.4111 | 9.25856 |
July | 497.00000 | 24.35899 | 51.80640 | -0.2843 | 7.50180 |
August | 514.00000 | 24.08620 | 51.47680 | -0.4144 | 9.07674 |
September | 485.00000 | 23.56097 | 40.79920 | -0.7247 | 17.49534 |
October | 502.00000 | 21.81775 | 34.92572 | -0.2687 | 8.41775 |
November | 489.00000 | 20.33601 | 27.32545 | -0.7325 | 18.49370 |
December | 497.00000 | 19.81966 | 19.08861 | -0.9873 | 27.83515 |
Annual Sum or Average | 5943.00000 | 22.03516 | 32.46900 | -0.6167 | 16.12072 |
Minimum of Months | 454.00000 | 19.75156 | 16.78457 | -1.0308 | 7.50180 |
Maximum of Months | 514.00000 | 24.35899 | 51.80640 | -0.2687 | 29.57479 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.62204 | 17.23688 | -1.0402 | 30.19254 |
February | 385.00000 | 20.06820 | 20.17099 | -0.8642 | 22.92339 |
March | 433.00000 | 21.00301 | 24.07995 | -0.5745 | 14.61333 |
April | 410.00000 | 22.50177 | 22.18956 | -0.1427 | 8.90316 |
May | 430.00000 | 24.19115 | 32.23267 | -0.4821 | 12.43220 |
June | 418.00000 | 24.38196 | 44.44110 | -0.2656 | 8.32692 |
July | 422.00000 | 24.56166 | 50.81463 | -0.1439 | 7.21232 |
August | 433.00000 | 24.32203 | 50.42669 | -0.2871 | 8.41395 |
September | 410.00000 | 23.81231 | 39.91049 | -0.6040 | 15.21380 |
October | 427.00000 | 22.10293 | 34.35927 | -0.1949 | 8.67012 |
November | 417.00000 | 20.34999 | 27.48518 | -0.7186 | 18.53188 |
December | 422.00000 | 19.67286 | 19.44571 | -1.0058 | 28.75975 |
Annual Sum or Average | 5034.00000 | 22.22966 | 31.99591 | -0.5249 | 15.29860 |
Minimum of Months | 385.00000 | 19.62204 | 17.23688 | -1.0402 | 7.21232 |
Maximum of Months | 433.00000 | 24.56166 | 50.81463 | -0.1427 | 30.19254 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34536 | 16.61381 | -0.8140 | 23.46703 |
February | 454.00000 | 21.11502 | 18.45216 | -0.5704 | 16.65067 |
March | 514.00000 | 21.71206 | 22.39185 | -0.3833 | 12.67124 |
April | 485.00000 | 22.66446 | 21.33830 | -0.0939 | 8.95752 |
May | 508.00000 | 23.98822 | 32.57993 | -0.5458 | 13.88241 |
June | 496.00000 | 24.17329 | 44.98881 | -0.3689 | 9.23965 |
July | 497.00000 | 24.40622 | 51.29162 | -0.2162 | 7.47829 |
August | 514.00000 | 24.23356 | 50.58310 | -0.2938 | 8.40193 |
September | 485.00000 | 23.93459 | 39.08910 | -0.5213 | 14.01536 |
October | 502.00000 | 22.55991 | 32.75254 | -0.0626 | 8.95518 |
November | 489.00000 | 21.06069 | 26.09593 | -0.5267 | 14.83263 |
December | 497.00000 | 20.31310 | 18.99670 | -0.8160 | 22.56306 |
Annual Sum or Average | 5943.00000 | 22.55450 | 31.38732 | -0.4335 | 13.39856 |
Minimum of Months | 454.00000 | 20.31310 | 16.61381 | -0.8160 | 7.47829 |
Maximum of Months | 514.00000 | 24.40622 | 51.29162 | -0.0626 | 23.46703 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87728 | 17.60430 | -0.9813 | 27.87450 |
February | 454.00000 | 20.34601 | 20.18095 | -0.8010 | 21.32987 |
March | 514.00000 | 21.07850 | 24.19207 | -0.5559 | 14.90174 |
April | 485.00000 | 22.32560 | 22.87487 | -0.1826 | 9.42892 |
May | 508.00000 | 23.99583 | 32.97771 | -0.5260 | 13.86798 |
June | 496.00000 | 24.19969 | 45.25900 | -0.3322 | 8.87050 |
July | 497.00000 | 24.44984 | 51.48089 | -0.1774 | 7.43529 |
August | 514.00000 | 24.21144 | 51.11886 | -0.3072 | 8.53897 |
September | 485.00000 | 23.78344 | 40.39787 | -0.6055 | 15.28155 |
October | 502.00000 | 22.12392 | 34.62779 | -0.1831 | 8.53548 |
November | 489.00000 | 20.50634 | 28.01429 | -0.6808 | 17.38151 |
December | 497.00000 | 19.88720 | 19.89381 | -0.9569 | 26.67505 |
Annual Sum or Average | 5943.00000 | 22.24796 | 32.50094 | -0.5221 | 14.95739 |
Minimum of Months | 454.00000 | 19.87728 | 17.60430 | -0.9813 | 7.43529 |
Maximum of Months | 514.00000 | 24.44984 | 51.48089 | -0.1774 | 27.87450 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3744183.92 | 1025733.10 | 1.13 | 3661567.74 | 82616.18 | 0.00 | 0.27 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 6618.59 | 20-JAN-07:01 | 6618.59 | 20-JAN-07:01 | 68.29 | 19-JAN-13:13 | 1753.08 | 20-JAN-07:01 | 0.00 |
February | 5850109.38 | 1620844.05 | 2.50 | 5646416.24 | 203693.14 | 0.00 | 0.25 | 22-FEB-07:01 | 0.00 | 01-FEB-00:05 | 6258.22 | 22-FEB-07:01 | 6258.22 | 22-FEB-07:01 | 88.42 | 21-FEB-12:10 | 1663.16 | 22-FEB-07:01 | 0.00 |
March | 14136669.31 | 3954409.90 | 8.30 | 13293431.21 | 843238.09 | 0.00 | 0.19 | 13-MAR-06:01 | 0.00 | 01-MAR-00:10 | 4597.43 | 13-MAR-06:01 | 4597.43 | 13-MAR-06:01 | 154.94 | 28-MAR-16:04 | 1240.86 | 13-MAR-06:01 | 0.00 |
April | 0.925297E+09 | 0.244714E+09 | 66.63 | 0.883459E+09 | 41837611.28 | 0.00 | 0.81 | 23-APR-17:11 | 0.00 | 01-APR-00:10 | 22858.70 | 23-APR-17:11 | 22858.70 | 23-APR-17:11 | 3837.09 | 23-APR-13:32 | 5534.68 | 23-APR-17:11 | 0.00 |
May | 0.133504E+11 | 0.319686E+10 | 226.38 | 0.123583E+11 | 0.992016E+09 | 0.00 | 1.00 | 16-MAY-12:05 | 0.00 | 01-MAY-00:10 | 48855.48 | 25-MAY-15:40 | 45871.21 | 18-MAY-15:10 | 15225.95 | 26-MAY-11:00 | 11995.74 | 25-MAY-15:50 | 0.00 |
June | 0.312794E+11 | 0.741204E+10 | 342.58 | 0.241902E+11 | 0.708919E+10 | 0.00 | 1.00 | 06-JUN-10:00 | 0.00 | 01-JUN-00:10 | 93058.66 | 29-JUN-06:03 | 54555.77 | 30-JUN-15:10 | 47379.64 | 29-JUN-06:03 | 20251.16 | 29-JUN-06:03 | 0.00 |
July | 0.441895E+11 | 0.102001E+11 | 389.65 | 0.329476E+11 | 0.112419E+11 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 01-JUL-00:10 | 103268.25 | 05-JUL-10:20 | 59146.79 | 24-JUL-15:40 | 67485.82 | 05-JUL-11:00 | 22138.09 | 05-JUL-11:50 | 0.00 |
August | 0.354525E+11 | 0.818510E+10 | 385.44 | 0.253001E+11 | 0.101524E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 83520.06 | 31-AUG-12:50 | 54919.43 | 08-AUG-16:00 | 45615.93 | 31-AUG-12:50 | 18049.20 | 31-AUG-12:50 | 0.00 |
September | 0.850607E+10 | 0.205284E+10 | 207.84 | 0.717520E+10 | 0.133088E+10 | 0.00 | 1.00 | 01-SEP-08:40 | 0.00 | 01-SEP-00:10 | 57123.05 | 01-SEP-13:10 | 50562.41 | 01-SEP-16:00 | 15910.01 | 01-SEP-09:00 | 12707.67 | 01-SEP-13:10 | 0.00 |
October | 0.123219E+10 | 0.314096E+09 | 67.79 | 0.116152E+10 | 70667910.71 | 0.00 | 0.80 | 19-OCT-15:10 | 0.00 | 01-OCT-00:10 | 22860.15 | 19-OCT-15:10 | 22860.15 | 19-OCT-15:10 | 2797.40 | 22-OCT-12:53 | 5266.22 | 19-OCT-15:10 | 0.00 |
November | 0.139580E+09 | 37527773.70 | 15.31 | 95883258.67 | 43696717.51 | 0.00 | 0.29 | 01-NOV-15:10 | 0.00 | 01-NOV-00:10 | 7135.39 | 01-NOV-15:10 | 5604.32 | 28-NOV-07:01 | 2320.09 | 01-NOV-15:00 | 1881.00 | 01-NOV-15:10 | 0.00 |
December | 5002238.48 | 1376796.14 | 1.94 | 4815562.92 | 186675.56 | 0.00 | 0.25 | 05-DEC-07:01 | 0.00 | 01-DEC-00:10 | 6152.12 | 05-DEC-07:01 | 6152.12 | 05-DEC-07:01 | 130.14 | 05-DEC-18:12 | 1636.57 | 05-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.135104E+12 | 0.316513E+11 | 1715.50 | 0.104140E+12 | 0.309639E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 3744183.92 | 1025733.10 | 1.13 | 3661567.74 | 82616.18 | 0.00 | 0.19 | 0.00 | 4597.43 | 4597.43 | 68.29 | 1240.86 | 0.00 | ||||||
Maximum of Months | 0.441895E+11 | 0.102001E+11 | 389.65 | 0.329476E+11 | 0.112419E+11 | 0.00 | 1.00 | 0.00 | 103268.25 | 59146.79 | 67485.82 | 22138.09 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1932583.20 | 529213.25 | 0.34 | 1922370.11 | 10213.09 | 0.00 | 0.24 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 5898.95 | 19-JAN-07:01 | 5898.95 | 19-JAN-07:01 | 82.49 | 19-JAN-13:01 | 1570.96 | 19-JAN-07:01 | 0.00 |
February | 6616604.09 | 1810188.00 | 3.19 | 6545198.74 | 71405.35 | 0.00 | 0.31 | 09-FEB-07:01 | 0.00 | 01-FEB-00:05 | 7736.73 | 09-FEB-07:01 | 7736.73 | 09-FEB-07:01 | 46.75 | 09-FEB-13:01 | 2025.08 | 09-FEB-07:01 | 0.00 |
March | 16756157.06 | 4609979.47 | 8.73 | 16255292.28 | 500864.77 | 0.00 | 0.33 | 27-MAR-06:01 | 0.00 | 01-MAR-00:10 | 8261.65 | 27-MAR-06:01 | 8261.65 | 27-MAR-06:01 | 107.76 | 21-MAR-06:03 | 2151.95 | 27-MAR-06:01 | 0.00 |
April | 0.158032E+10 | 0.407286E+09 | 83.25 | 0.153684E+10 | 43479075.40 | 0.00 | 1.00 | 23-APR-14:02 | 0.00 | 01-APR-00:10 | 39640.52 | 23-APR-16:01 | 39640.52 | 23-APR-16:01 | 3611.62 | 23-APR-13:26 | 9225.89 | 23-APR-16:01 | 0.00 |
May | 0.147477E+11 | 0.349226E+10 | 225.42 | 0.138144E+11 | 0.933251E+09 | 0.00 | 1.00 | 10-MAY-15:10 | 0.00 | 01-MAY-00:10 | 56903.46 | 25-MAY-14:05 | 52427.32 | 18-MAY-14:05 | 17645.43 | 26-MAY-11:00 | 13628.51 | 25-MAY-14:05 | 0.00 |
June | 0.334172E+11 | 0.785736E+10 | 353.37 | 0.262515E+11 | 0.716571E+10 | 0.00 | 1.00 | 01-JUN-12:05 | 0.00 | 01-JUN-00:10 | 95141.12 | 29-JUN-06:03 | 61000.94 | 30-JUN-06:03 | 47005.47 | 29-JUN-06:03 | 21388.41 | 30-JUN-06:03 | 0.00 |
July | 0.446761E+11 | 0.103003E+11 | 397.31 | 0.333407E+11 | 0.113354E+11 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 01-JUL-00:10 | 100977.63 | 05-JUL-10:30 | 65462.45 | 23-JUL-16:41 | 66015.01 | 05-JUL-11:00 | 21647.04 | 05-JUL-11:50 | 0.00 |
August | 0.333733E+11 | 0.772334E+10 | 385.28 | 0.240636E+11 | 0.930977E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 82336.75 | 08-AUG-10:05 | 54638.33 | 08-AUG-15:10 | 44510.53 | 31-AUG-12:50 | 18028.03 | 08-AUG-10:05 | 0.00 |
September | 0.752252E+10 | 0.180789E+10 | 171.84 | 0.627652E+10 | 0.124600E+10 | 0.00 | 1.00 | 01-SEP-08:30 | 0.00 | 01-SEP-00:10 | 59546.81 | 01-SEP-12:05 | 52615.37 | 01-SEP-15:40 | 18017.70 | 01-SEP-12:05 | 13091.89 | 01-SEP-13:20 | 0.00 |
October | 0.999830E+09 | 0.252994E+09 | 47.46 | 0.938060E+09 | 61770416.98 | 0.00 | 0.80 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 22169.00 | 19-OCT-15:00 | 22169.00 | 19-OCT-15:00 | 3471.73 | 22-OCT-12:02 | 5114.72 | 19-OCT-15:00 | 0.00 |
November | 0.124708E+09 | 33591105.86 | 13.54 | 84580346.98 | 40127452.18 | 0.00 | 0.31 | 22-NOV-07:01 | 0.00 | 01-NOV-00:10 | 7619.02 | 22-NOV-07:01 | 7619.02 | 22-NOV-07:01 | 2180.33 | 01-NOV-15:00 | 1996.46 | 22-NOV-07:01 | 0.00 |
December | 5240510.60 | 1427068.15 | 0.63 | 5202969.82 | 37540.78 | 0.00 | 0.27 | 06-DEC-07:01 | 0.00 | 01-DEC-00:10 | 6449.38 | 06-DEC-07:01 | 6449.38 | 06-DEC-07:01 | 123.10 | 06-DEC-07:12 | 1708.62 | 06-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.136472E+12 | 0.318834E+11 | 1690.37 | 0.106336E+12 | 0.301361E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1932583.20 | 529213.25 | 0.34 | 1922370.11 | 10213.09 | 0.00 | 0.24 | 0.00 | 5898.95 | 5898.95 | 46.75 | 1570.96 | 0.00 | ||||||
Maximum of Months | 0.446761E+11 | 0.103003E+11 | 397.31 | 0.333407E+11 | 0.113354E+11 | 0.00 | 1.00 | 0.00 | 100977.63 | 65462.45 | 66015.01 | 21647.04 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 357983.24 | 100271.39 | 0.19 | 357983.24 | -0.0 | 0.00 | 0.06 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 1574.71 | 19-JAN-07:01 | 1574.71 | 19-JAN-07:01 | 0.00 | 30-JAN-07:11 | 437.92 | 19-JAN-07:01 | 0.00 |
February | 4729583.22 | 1330467.30 | 5.35 | 4430885.91 | 298697.31 | 0.00 | 0.07 | 09-FEB-07:01 | 0.00 | 01-FEB-00:05 | 1831.35 | 09-FEB-07:01 | 1831.35 | 09-FEB-07:01 | 36.46 | 08-FEB-11:00 | 508.12 | 09-FEB-07:01 | 0.00 |
March | 46434034.30 | 12817639.26 | 17.35 | 45536706.02 | 897328.28 | 0.00 | 0.19 | 29-MAR-06:01 | 0.00 | 01-MAR-00:10 | 4885.94 | 29-MAR-06:01 | 4885.94 | 29-MAR-06:01 | 104.32 | 30-MAR-06:03 | 1319.48 | 29-MAR-06:01 | 0.00 |
April | 0.180037E+10 | 0.464133E+09 | 89.34 | 0.173003E+10 | 70339604.19 | 0.00 | 1.00 | 23-APR-15:32 | 0.00 | 01-APR-00:10 | 38086.33 | 23-APR-16:12 | 38086.33 | 23-APR-16:12 | 4331.70 | 23-APR-15:34 | 8848.46 | 23-APR-16:12 | 0.00 |
May | 0.158851E+11 | 0.377174E+10 | 228.12 | 0.148501E+11 | 0.103505E+10 | 0.00 | 1.00 | 10-MAY-15:10 | 0.00 | 01-MAY-00:10 | 62459.04 | 25-MAY-15:00 | 59386.06 | 18-MAY-14:40 | 17028.50 | 26-MAY-11:00 | 15260.37 | 25-MAY-15:20 | 0.00 |
June | 0.352754E+11 | 0.833367E+10 | 352.96 | 0.277933E+11 | 0.748217E+10 | 0.00 | 1.00 | 01-JUN-12:05 | 0.00 | 01-JUN-00:10 | 93325.58 | 29-JUN-06:03 | 68314.49 | 30-JUN-14:40 | 48705.02 | 19-JUN-16:00 | 22155.06 | 29-JUN-16:00 | 0.00 |
July | 0.470106E+11 | 0.108877E+11 | 396.84 | 0.352359E+11 | 0.117747E+11 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 01-JUL-00:10 | 111221.16 | 05-JUL-10:30 | 74021.02 | 23-JUL-15:32 | 72642.93 | 05-JUL-11:00 | 24755.54 | 23-JUL-16:52 | 0.00 |
August | 0.342867E+11 | 0.797850E+10 | 384.07 | 0.246382E+11 | 0.964847E+10 | 0.00 | 1.00 | 04-AUG-12:30 | 0.00 | 01-AUG-00:10 | 88892.85 | 29-AUG-15:50 | 62464.18 | 08-AUG-15:00 | 41221.09 | 31-AUG-12:50 | 19768.87 | 29-AUG-13:50 | 0.00 |
September | 0.720917E+10 | 0.174862E+10 | 168.11 | 0.591937E+10 | 0.128979E+10 | 0.00 | 1.00 | 01-SEP-09:00 | 0.00 | 01-SEP-00:10 | 65190.65 | 01-SEP-14:00 | 58789.16 | 01-SEP-15:40 | 16425.06 | 01-SEP-12:40 | 14803.45 | 01-SEP-14:00 | 0.00 |
October | 0.938360E+09 | 0.240213E+09 | 42.21 | 0.866208E+09 | 72152501.36 | 0.00 | 0.72 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 21627.03 | 19-OCT-15:00 | 21627.03 | 19-OCT-15:00 | 3882.66 | 22-OCT-12:02 | 5095.76 | 19-OCT-15:00 | 0.00 |
November | 0.130180E+09 | 35189421.80 | 16.43 | 86394747.75 | 43785655.47 | 0.00 | 0.25 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 6576.64 | 01-NOV-15:00 | 4241.08 | 01-NOV-15:00 | 2335.56 | 01-NOV-15:00 | 1750.24 | 01-NOV-15:00 | 0.00 |
December | 778819.97 | 216182.79 | 0.15 | 774745.30 | 4074.67 | 0.00 | 0.11 | 06-DEC-07:01 | 0.00 | 01-DEC-00:10 | 2731.05 | 06-DEC-07:01 | 2731.05 | 06-DEC-07:01 | 33.96 | 06-DEC-07:12 | 751.68 | 06-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.142588E+12 | 0.334742E+11 | 1701.14 | 0.111171E+12 | 0.314177E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 357983.24 | 100271.39 | 0.15 | 357983.24 | -0.0 | 0.00 | 0.06 | 0.00 | 1574.71 | 1574.71 | 0.00 | 437.92 | 0.00 | ||||||
Maximum of Months | 0.470106E+11 | 0.108877E+11 | 396.84 | 0.352359E+11 | 0.117747E+11 | 0.00 | 1.00 | 0.00 | 111221.16 | 74021.02 | 72642.93 | 24755.54 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 330.24 | 0.00 | 330.24 | 5.37 | 2857.46 | 0.00 | 0.00 | 0.00 |
February | 507.28 | 0.00 | 507.28 | 51.74 | 2244.86 | 0.00 | 0.00 | 0.00 |
March | 624.12 | 0.00 | 624.12 | 118.55 | 1739.13 | 0.00 | 0.00 | 0.00 |
April | 818.09 | 6.29 | 811.80 | 418.04 | 1041.51 | 0.00 | 0.00 | 0.00 |
May | 1150.28 | 61.50 | 1088.78 | 1053.85 | 572.20 | 0.00 | 0.00 | 0.00 |
June | 1283.53 | 140.46 | 1143.08 | 1433.92 | 397.51 | 0.00 | 0.00 | 0.00 |
July | 1226.04 | 104.65 | 1121.39 | 1435.00 | 374.48 | 0.00 | 0.00 | 0.00 |
August | 931.51 | 15.82 | 915.69 | 986.29 | 440.52 | 0.00 | 0.00 | 0.00 |
September | 726.03 | 0.17 | 725.86 | 569.89 | 714.12 | 0.00 | 0.00 | 0.00 |
October | 504.12 | 0.00 | 504.12 | 209.14 | 1060.71 | 0.00 | 0.00 | 0.00 |
November | 333.79 | 0.00 | 333.79 | 34.36 | 1622.22 | 0.00 | 0.00 | 0.00 |
December | 279.81 | 0.00 | 279.81 | 0.84 | 2728.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 727.34 | 27.53 | 699.80 | 529.36 | 1312.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.81 | 0.00 | 279.81 | 0.84 | 374.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1283.53 | 140.46 | 1143.08 | 1435.00 | 2857.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.53 | 201.33 | 281.20 | 194.43 | 1717.01 | 0.00 | 0.00 | 0.00 |
February | 758.40 | 323.44 | 434.96 | 470.54 | 1343.75 | 0.00 | 0.00 | 0.00 |
March | 1033.67 | 518.58 | 515.09 | 809.80 | 1064.77 | 0.00 | 0.00 | 0.00 |
April | 1433.05 | 773.09 | 659.96 | 1415.16 | 662.95 | 0.00 | 0.00 | 0.00 |
May | 1550.95 | 681.98 | 868.97 | 1734.22 | 390.19 | 0.00 | 0.00 | 0.00 |
June | 1755.91 | 840.19 | 915.72 | 2143.91 | 274.28 | 0.00 | 0.00 | 0.00 |
July | 1720.12 | 807.88 | 912.24 | 2155.86 | 255.43 | 0.00 | 0.00 | 0.00 |
August | 1326.13 | 579.74 | 746.38 | 1596.23 | 296.92 | 0.00 | 0.00 | 0.00 |
September | 1061.98 | 475.43 | 586.55 | 1134.24 | 461.46 | 0.00 | 0.00 | 0.00 |
October | 642.97 | 243.82 | 399.14 | 516.81 | 674.74 | 0.00 | 0.00 | 0.00 |
November | 409.21 | 136.74 | 272.47 | 208.70 | 1001.86 | 0.00 | 0.00 | 0.00 |
December | 373.36 | 137.92 | 235.44 | 120.50 | 1662.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1046.74 | 477.06 | 569.68 | 1044.38 | 815.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 373.36 | 136.74 | 235.44 | 120.50 | 255.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1755.91 | 840.19 | 915.72 | 2155.86 | 1717.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2275.90 | 1583.85 | 692.05 | 1974.12 | 2284.45 | 0.00 | 0.00 | 0.00 |
February | 2881.70 | 1947.10 | 934.60 | 2818.04 | 1906.72 | 0.00 | 0.00 | 0.00 |
March | 2537.90 | 1606.39 | 931.51 | 2536.95 | 1591.31 | 0.00 | 0.00 | 0.00 |
April | 2297.23 | 1246.23 | 1051.00 | 2503.94 | 1067.88 | 0.00 | 0.00 | 0.00 |
May | 1930.32 | 658.46 | 1271.86 | 2270.13 | 635.27 | 0.00 | 0.00 | 0.00 |
June | 1731.81 | 459.96 | 1271.84 | 2174.02 | 436.75 | 0.00 | 0.00 | 0.00 |
July | 1893.36 | 598.10 | 1295.27 | 2482.76 | 404.77 | 0.00 | 0.00 | 0.00 |
August | 2022.96 | 845.19 | 1177.77 | 2575.13 | 468.66 | 0.00 | 0.00 | 0.00 |
September | 2168.55 | 1154.82 | 1013.72 | 2554.40 | 728.72 | 0.00 | 0.00 | 0.00 |
October | 1852.93 | 1090.21 | 762.72 | 1942.76 | 1024.23 | 0.00 | 0.00 | 0.00 |
November | 1650.88 | 1036.54 | 614.34 | 1540.10 | 1429.51 | 0.00 | 0.00 | 0.00 |
December | 1757.17 | 1152.65 | 604.52 | 1407.45 | 2204.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2078.16 | 1109.66 | 968.50 | 2227.25 | 1178.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1650.88 | 459.96 | 604.52 | 1407.45 | 404.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2881.70 | 1947.10 | 1295.27 | 2818.04 | 2284.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 487.74 | 204.17 | 283.57 | 215.53 | 1755.20 | 0.00 | 0.00 | 0.00 |
February | 794.83 | 363.01 | 431.82 | 544.73 | 1396.21 | 0.00 | 0.00 | 0.00 |
March | 1046.15 | 535.39 | 510.76 | 858.45 | 1106.89 | 0.00 | 0.00 | 0.00 |
April | 1336.44 | 677.01 | 659.42 | 1318.65 | 698.95 | 0.00 | 0.00 | 0.00 |
May | 1642.14 | 783.51 | 858.62 | 1888.39 | 417.27 | 0.00 | 0.00 | 0.00 |
June | 1584.64 | 685.41 | 899.23 | 1932.45 | 288.95 | 0.00 | 0.00 | 0.00 |
July | 1691.68 | 786.64 | 905.04 | 2129.97 | 273.02 | 0.00 | 0.00 | 0.00 |
August | 1392.06 | 632.66 | 759.41 | 1700.53 | 312.71 | 0.00 | 0.00 | 0.00 |
September | 1087.96 | 488.90 | 599.06 | 1181.45 | 481.28 | 0.00 | 0.00 | 0.00 |
October | 687.19 | 275.88 | 411.31 | 591.46 | 695.67 | 0.00 | 0.00 | 0.00 |
November | 417.26 | 140.62 | 276.64 | 227.06 | 1025.44 | 0.00 | 0.00 | 0.00 |
December | 371.92 | 130.09 | 241.83 | 121.47 | 1689.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1046.38 | 475.95 | 570.43 | 1062.25 | 842.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 371.92 | 130.09 | 241.83 | 121.47 | 273.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1691.68 | 786.64 | 905.04 | 2129.97 | 1755.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 0.00 | 110.08 | 1.60 | 952.31 | 0.00 | 0.00 | 0.00 |
February | 169.09 | 0.00 | 169.09 | 17.55 | 749.78 | 0.00 | 0.00 | 0.00 |
March | 208.03 | 0.00 | 208.03 | 43.43 | 572.43 | 0.00 | 0.00 | 0.00 |
April | 272.68 | 2.10 | 270.59 | 153.49 | 335.96 | 0.00 | 0.00 | 0.00 |
May | 383.41 | 20.50 | 362.91 | 370.27 | 179.21 | 0.00 | 0.00 | 0.00 |
June | 427.82 | 46.82 | 381.01 | 491.82 | 125.82 | 0.00 | 0.00 | 0.00 |
July | 408.66 | 34.88 | 373.78 | 486.86 | 121.66 | 0.00 | 0.00 | 0.00 |
August | 310.49 | 5.27 | 305.21 | 332.41 | 148.16 | 0.00 | 0.00 | 0.00 |
September | 242.00 | 0.06 | 241.94 | 189.05 | 249.08 | 0.00 | 0.00 | 0.00 |
October | 168.03 | 0.00 | 168.03 | 65.20 | 380.02 | 0.00 | 0.00 | 0.00 |
November | 111.26 | 0.00 | 111.26 | 10.42 | 568.86 | 0.00 | 0.00 | 0.00 |
December | 93.27 | 0.00 | 93.27 | 0.07 | 919.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.43 | 9.18 | 233.26 | 181.18 | 440.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.27 | 0.00 | 93.27 | 0.07 | 121.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.82 | 46.82 | 381.01 | 491.82 | 952.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 0.00 | 110.08 | 1.59 | 952.37 | 0.00 | 0.00 | 0.00 |
February | 169.09 | 0.00 | 169.09 | 17.55 | 749.83 | 0.00 | 0.00 | 0.00 |
March | 208.04 | 0.00 | 208.04 | 43.43 | 572.47 | 0.00 | 0.00 | 0.00 |
April | 272.69 | 2.10 | 270.60 | 153.49 | 335.98 | 0.00 | 0.00 | 0.00 |
May | 383.42 | 20.50 | 362.92 | 370.28 | 179.22 | 0.00 | 0.00 | 0.00 |
June | 427.84 | 46.82 | 381.02 | 491.84 | 125.83 | 0.00 | 0.00 | 0.00 |
July | 408.68 | 34.88 | 373.79 | 486.88 | 121.67 | 0.00 | 0.00 | 0.00 |
August | 310.50 | 5.27 | 305.23 | 332.42 | 148.17 | 0.00 | 0.00 | 0.00 |
September | 242.01 | 0.06 | 241.95 | 189.06 | 249.10 | 0.00 | 0.00 | 0.00 |
October | 168.04 | 0.00 | 168.04 | 65.20 | 380.05 | 0.00 | 0.00 | 0.00 |
November | 111.26 | 0.00 | 111.26 | 10.42 | 568.90 | 0.00 | 0.00 | 0.00 |
December | 93.27 | 0.00 | 93.27 | 0.07 | 919.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.44 | 9.18 | 233.27 | 181.19 | 440.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.27 | 0.00 | 93.27 | 0.07 | 121.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.84 | 46.82 | 381.02 | 491.84 | 952.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.08 | 0.00 | 110.08 | 1.59 | 952.37 | 0.00 | 0.00 | 0.00 |
February | 169.09 | 0.00 | 169.09 | 17.55 | 749.83 | 0.00 | 0.00 | 0.00 |
March | 208.04 | 0.00 | 208.04 | 43.43 | 572.47 | 0.00 | 0.00 | 0.00 |
April | 272.69 | 2.10 | 270.60 | 153.49 | 335.98 | 0.00 | 0.00 | 0.00 |
May | 383.42 | 20.50 | 362.92 | 370.28 | 179.22 | 0.00 | 0.00 | 0.00 |
June | 427.84 | 46.82 | 381.02 | 491.84 | 125.83 | 0.00 | 0.00 | 0.00 |
July | 408.68 | 34.88 | 373.79 | 486.88 | 121.67 | 0.00 | 0.00 | 0.00 |
August | 310.50 | 5.27 | 305.23 | 332.42 | 148.17 | 0.00 | 0.00 | 0.00 |
September | 242.01 | 0.06 | 241.95 | 189.06 | 249.10 | 0.00 | 0.00 | 0.00 |
October | 168.04 | 0.00 | 168.04 | 65.20 | 380.05 | 0.00 | 0.00 | 0.00 |
November | 111.26 | 0.00 | 111.26 | 10.42 | 568.90 | 0.00 | 0.00 | 0.00 |
December | 93.27 | 0.00 | 93.27 | 0.07 | 919.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.44 | 9.18 | 233.27 | 181.19 | 440.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.27 | 0.00 | 93.27 | 0.07 | 121.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.84 | 46.82 | 381.02 | 491.84 | 952.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 464.17 | 193.67 | 270.50 | 189.09 | 1658.56 | 0.00 | 0.00 | 0.00 |
February | 729.54 | 311.13 | 418.41 | 457.18 | 1303.22 | 0.00 | 0.00 | 0.00 |
March | 994.34 | 498.85 | 495.49 | 794.06 | 1020.70 | 0.00 | 0.00 | 0.00 |
April | 1378.52 | 743.67 | 634.85 | 1384.45 | 635.76 | 0.00 | 0.00 | 0.00 |
May | 1491.93 | 656.02 | 835.91 | 1694.93 | 366.14 | 0.00 | 0.00 | 0.00 |
June | 1689.10 | 808.22 | 880.88 | 2083.30 | 260.40 | 0.00 | 0.00 | 0.00 |
July | 1654.67 | 777.14 | 877.53 | 2086.91 | 247.74 | 0.00 | 0.00 | 0.00 |
August | 1275.67 | 557.68 | 717.99 | 1542.06 | 297.26 | 0.00 | 0.00 | 0.00 |
September | 1021.57 | 457.34 | 564.24 | 1088.67 | 472.38 | 0.00 | 0.00 | 0.00 |
October | 618.50 | 234.54 | 383.96 | 484.37 | 706.58 | 0.00 | 0.00 | 0.00 |
November | 393.64 | 131.54 | 262.10 | 196.60 | 1020.44 | 0.00 | 0.00 | 0.00 |
December | 359.15 | 132.67 | 226.48 | 115.74 | 1620.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1006.91 | 458.91 | 548.00 | 1012.37 | 798.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 359.15 | 131.54 | 226.48 | 115.74 | 247.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1689.10 | 808.22 | 880.88 | 2086.91 | 1658.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.35 | 7.66 | 10.70 | 7.48 | 65.58 | 0.00 | 0.00 | 0.00 |
February | 28.85 | 12.30 | 16.54 | 18.08 | 51.53 | 0.00 | 0.00 | 0.00 |
March | 39.32 | 19.72 | 19.59 | 31.40 | 40.36 | 0.00 | 0.00 | 0.00 |
April | 54.51 | 29.40 | 25.10 | 54.74 | 25.14 | 0.00 | 0.00 | 0.00 |
May | 58.99 | 25.94 | 33.05 | 67.02 | 14.48 | 0.00 | 0.00 | 0.00 |
June | 66.79 | 31.96 | 34.83 | 82.37 | 10.30 | 0.00 | 0.00 | 0.00 |
July | 65.42 | 30.73 | 34.70 | 82.51 | 9.80 | 0.00 | 0.00 | 0.00 |
August | 50.44 | 22.05 | 28.39 | 60.97 | 11.75 | 0.00 | 0.00 | 0.00 |
September | 40.39 | 18.08 | 22.31 | 43.04 | 18.68 | 0.00 | 0.00 | 0.00 |
October | 24.46 | 9.27 | 15.18 | 19.15 | 27.94 | 0.00 | 0.00 | 0.00 |
November | 15.56 | 5.20 | 10.36 | 7.77 | 40.35 | 0.00 | 0.00 | 0.00 |
December | 14.20 | 5.25 | 8.95 | 4.58 | 64.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.81 | 18.14 | 21.67 | 40.03 | 31.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.20 | 5.20 | 8.95 | 4.58 | 9.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.79 | 31.96 | 34.83 | 82.51 | 65.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 758.62 | 527.94 | 230.68 | 673.59 | 753.11 | 0.00 | 0.00 | 0.00 |
February | 960.55 | 649.02 | 311.53 | 956.82 | 640.27 | 0.00 | 0.00 | 0.00 |
March | 845.95 | 535.45 | 310.50 | 864.26 | 529.04 | 0.00 | 0.00 | 0.00 |
April | 765.73 | 415.40 | 350.33 | 851.60 | 354.31 | 0.00 | 0.00 | 0.00 |
May | 643.43 | 219.48 | 423.95 | 774.20 | 204.01 | 0.00 | 0.00 | 0.00 |
June | 577.26 | 153.32 | 423.94 | 739.44 | 139.37 | 0.00 | 0.00 | 0.00 |
July | 631.11 | 199.36 | 431.75 | 836.22 | 134.95 | 0.00 | 0.00 | 0.00 |
August | 674.31 | 281.72 | 392.59 | 864.33 | 162.29 | 0.00 | 0.00 | 0.00 |
September | 722.84 | 384.93 | 337.90 | 855.29 | 258.06 | 0.00 | 0.00 | 0.00 |
October | 617.63 | 363.40 | 254.24 | 646.15 | 371.31 | 0.00 | 0.00 | 0.00 |
November | 550.28 | 345.51 | 204.78 | 515.00 | 503.64 | 0.00 | 0.00 | 0.00 |
December | 585.71 | 384.21 | 201.50 | 477.27 | 734.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 692.71 | 369.88 | 322.83 | 753.01 | 397.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 550.28 | 153.32 | 201.50 | 477.27 | 134.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 960.55 | 649.02 | 431.75 | 956.82 | 753.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 758.62 | 527.94 | 230.68 | 673.59 | 753.11 | 0.00 | 0.00 | 0.00 |
February | 960.55 | 649.02 | 311.53 | 956.82 | 640.27 | 0.00 | 0.00 | 0.00 |
March | 845.95 | 535.45 | 310.50 | 864.26 | 529.04 | 0.00 | 0.00 | 0.00 |
April | 765.73 | 415.40 | 350.33 | 851.60 | 354.31 | 0.00 | 0.00 | 0.00 |
May | 643.43 | 219.48 | 423.95 | 774.20 | 204.01 | 0.00 | 0.00 | 0.00 |
June | 577.26 | 153.32 | 423.94 | 739.44 | 139.37 | 0.00 | 0.00 | 0.00 |
July | 631.11 | 199.36 | 431.75 | 836.22 | 134.95 | 0.00 | 0.00 | 0.00 |
August | 674.31 | 281.72 | 392.59 | 864.33 | 162.29 | 0.00 | 0.00 | 0.00 |
September | 722.84 | 384.93 | 337.90 | 855.29 | 258.06 | 0.00 | 0.00 | 0.00 |
October | 617.63 | 363.40 | 254.24 | 646.15 | 371.31 | 0.00 | 0.00 | 0.00 |
November | 550.28 | 345.51 | 204.78 | 515.00 | 503.64 | 0.00 | 0.00 | 0.00 |
December | 585.71 | 384.21 | 201.50 | 477.27 | 734.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 692.71 | 369.88 | 322.83 | 753.01 | 397.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 550.28 | 153.32 | 201.50 | 477.27 | 134.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 960.55 | 649.02 | 431.75 | 956.82 | 753.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 758.57 | 527.90 | 230.67 | 673.54 | 753.07 | 0.00 | 0.00 | 0.00 |
February | 960.49 | 648.98 | 311.51 | 956.76 | 640.23 | 0.00 | 0.00 | 0.00 |
March | 845.90 | 535.42 | 310.48 | 864.20 | 529.01 | 0.00 | 0.00 | 0.00 |
April | 765.68 | 415.38 | 350.31 | 851.54 | 354.29 | 0.00 | 0.00 | 0.00 |
May | 643.39 | 219.47 | 423.92 | 774.15 | 204.00 | 0.00 | 0.00 | 0.00 |
June | 577.23 | 153.31 | 423.92 | 739.40 | 139.36 | 0.00 | 0.00 | 0.00 |
July | 631.07 | 199.35 | 431.72 | 836.17 | 134.94 | 0.00 | 0.00 | 0.00 |
August | 674.27 | 281.71 | 392.56 | 864.27 | 162.28 | 0.00 | 0.00 | 0.00 |
September | 722.79 | 384.91 | 337.88 | 855.24 | 258.04 | 0.00 | 0.00 | 0.00 |
October | 617.59 | 363.37 | 254.22 | 646.10 | 371.29 | 0.00 | 0.00 | 0.00 |
November | 550.25 | 345.48 | 204.76 | 514.96 | 503.61 | 0.00 | 0.00 | 0.00 |
December | 585.67 | 384.18 | 201.49 | 477.24 | 734.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 692.67 | 369.86 | 322.81 | 752.96 | 397.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 550.25 | 153.31 | 201.49 | 477.24 | 134.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 960.49 | 648.98 | 431.72 | 956.76 | 753.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.18 | 196.40 | 272.78 | 211.52 | 1693.84 | 0.00 | 0.00 | 0.00 |
February | 764.59 | 349.19 | 415.40 | 533.60 | 1354.15 | 0.00 | 0.00 | 0.00 |
March | 1006.35 | 515.02 | 491.33 | 843.47 | 1063.05 | 0.00 | 0.00 | 0.00 |
April | 1285.59 | 651.25 | 634.33 | 1293.36 | 671.36 | 0.00 | 0.00 | 0.00 |
May | 1579.66 | 753.70 | 825.96 | 1841.58 | 396.09 | 0.00 | 0.00 | 0.00 |
June | 1524.35 | 659.33 | 865.02 | 1881.23 | 273.90 | 0.00 | 0.00 | 0.00 |
July | 1627.32 | 756.71 | 870.61 | 2061.60 | 268.10 | 0.00 | 0.00 | 0.00 |
August | 1339.10 | 608.58 | 730.51 | 1642.29 | 314.93 | 0.00 | 0.00 | 0.00 |
September | 1046.57 | 470.30 | 576.27 | 1135.04 | 494.65 | 0.00 | 0.00 | 0.00 |
October | 661.04 | 265.38 | 395.66 | 558.19 | 729.89 | 0.00 | 0.00 | 0.00 |
November | 401.38 | 135.27 | 266.11 | 215.73 | 1041.10 | 0.00 | 0.00 | 0.00 |
December | 357.77 | 125.14 | 232.63 | 117.63 | 1644.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1006.57 | 457.84 | 548.73 | 1030.87 | 826.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 357.77 | 125.14 | 232.63 | 117.63 | 268.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1627.32 | 756.71 | 870.61 | 2061.60 | 1693.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.55 | 7.77 | 10.79 | 8.36 | 66.97 | 0.00 | 0.00 | 0.00 |
February | 30.23 | 13.81 | 16.42 | 21.10 | 53.54 | 0.00 | 0.00 | 0.00 |
March | 39.79 | 20.36 | 19.43 | 33.35 | 42.03 | 0.00 | 0.00 | 0.00 |
April | 50.83 | 25.75 | 25.08 | 51.14 | 26.54 | 0.00 | 0.00 | 0.00 |
May | 62.46 | 29.80 | 32.66 | 72.81 | 15.66 | 0.00 | 0.00 | 0.00 |
June | 60.27 | 26.07 | 34.20 | 74.38 | 10.83 | 0.00 | 0.00 | 0.00 |
July | 64.34 | 29.92 | 34.42 | 81.51 | 10.60 | 0.00 | 0.00 | 0.00 |
August | 52.95 | 24.06 | 28.88 | 64.93 | 12.45 | 0.00 | 0.00 | 0.00 |
September | 41.38 | 18.60 | 22.79 | 44.88 | 19.56 | 0.00 | 0.00 | 0.00 |
October | 26.14 | 10.49 | 15.64 | 22.07 | 28.86 | 0.00 | 0.00 | 0.00 |
November | 15.87 | 5.35 | 10.52 | 8.53 | 41.16 | 0.00 | 0.00 | 0.00 |
December | 14.15 | 4.95 | 9.20 | 4.65 | 65.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.80 | 18.10 | 21.70 | 40.76 | 32.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.15 | 4.95 | 9.20 | 4.65 | 10.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.34 | 29.92 | 34.42 | 81.51 | 66.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 330.24 | 0.00 | 330.24 | 4.41 | 2903.56 | 0.00 | 0.00 | 0.00 |
February | 507.28 | 0.00 | 507.28 | 47.94 | 2297.24 | 0.00 | 0.00 | 0.00 |
March | 624.12 | 0.00 | 624.12 | 112.49 | 1793.74 | 0.00 | 0.00 | 0.00 |
April | 818.09 | 6.29 | 811.80 | 404.72 | 1093.00 | 0.00 | 0.00 | 0.00 |
May | 1150.28 | 61.50 | 1088.78 | 1045.82 | 591.22 | 0.00 | 0.00 | 0.00 |
June | 1283.53 | 140.46 | 1143.08 | 1430.73 | 408.57 | 0.00 | 0.00 | 0.00 |
July | 1226.04 | 104.65 | 1121.39 | 1433.29 | 383.47 | 0.00 | 0.00 | 0.00 |
August | 931.51 | 15.82 | 915.69 | 982.82 | 455.80 | 0.00 | 0.00 | 0.00 |
September | 726.03 | 0.17 | 725.86 | 557.38 | 752.59 | 0.00 | 0.00 | 0.00 |
October | 504.12 | 0.00 | 504.12 | 191.54 | 1134.14 | 0.00 | 0.00 | 0.00 |
November | 333.79 | 0.00 | 333.79 | 30.31 | 1697.19 | 0.00 | 0.00 | 0.00 |
December | 279.81 | 0.00 | 279.81 | 0.27 | 2780.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 727.34 | 27.53 | 699.80 | 523.09 | 1353.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.81 | 0.00 | 279.81 | 0.27 | 383.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1283.53 | 140.46 | 1143.08 | 1433.29 | 2903.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.53 | 201.33 | 281.20 | 192.32 | 1741.74 | 0.00 | 0.00 | 0.00 |
February | 758.40 | 323.44 | 434.96 | 464.08 | 1374.86 | 0.00 | 0.00 | 0.00 |
March | 1033.67 | 518.58 | 515.09 | 800.16 | 1099.00 | 0.00 | 0.00 | 0.00 |
April | 1433.05 | 773.09 | 659.96 | 1402.39 | 694.29 | 0.00 | 0.00 | 0.00 |
May | 1550.95 | 681.98 | 868.97 | 1728.35 | 401.78 | 0.00 | 0.00 | 0.00 |
June | 1755.91 | 840.19 | 915.72 | 2140.90 | 281.87 | 0.00 | 0.00 | 0.00 |
July | 1720.12 | 807.88 | 912.24 | 2153.25 | 261.61 | 0.00 | 0.00 | 0.00 |
August | 1326.13 | 579.74 | 746.38 | 1592.90 | 306.77 | 0.00 | 0.00 | 0.00 |
September | 1061.98 | 475.43 | 586.55 | 1124.15 | 483.80 | 0.00 | 0.00 | 0.00 |
October | 642.97 | 243.82 | 399.14 | 500.09 | 720.02 | 0.00 | 0.00 | 0.00 |
November | 409.21 | 136.74 | 272.47 | 201.65 | 1048.80 | 0.00 | 0.00 | 0.00 |
December | 373.36 | 137.92 | 235.44 | 118.47 | 1691.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1046.74 | 477.06 | 569.68 | 1037.58 | 840.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 373.36 | 136.74 | 235.44 | 118.47 | 261.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1755.91 | 840.19 | 915.72 | 2153.25 | 1741.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2275.90 | 1583.85 | 692.05 | 1965.31 | 2327.74 | 0.00 | 0.00 | 0.00 |
February | 2881.70 | 1947.10 | 934.60 | 2805.42 | 1960.24 | 0.00 | 0.00 | 0.00 |
March | 2537.90 | 1606.39 | 931.51 | 2525.14 | 1644.59 | 0.00 | 0.00 | 0.00 |
April | 2297.23 | 1246.23 | 1051.00 | 2491.99 | 1117.71 | 0.00 | 0.00 | 0.00 |
May | 1930.32 | 658.46 | 1271.86 | 2266.93 | 656.69 | 0.00 | 0.00 | 0.00 |
June | 1731.81 | 459.96 | 1271.84 | 2173.54 | 450.21 | 0.00 | 0.00 | 0.00 |
July | 1893.36 | 598.10 | 1295.27 | 2483.39 | 415.70 | 0.00 | 0.00 | 0.00 |
August | 2022.96 | 845.19 | 1177.77 | 2575.04 | 484.64 | 0.00 | 0.00 | 0.00 |
September | 2168.55 | 1154.82 | 1013.72 | 2546.18 | 763.72 | 0.00 | 0.00 | 0.00 |
October | 1852.93 | 1090.21 | 762.72 | 1921.62 | 1090.10 | 0.00 | 0.00 | 0.00 |
November | 1650.88 | 1036.54 | 614.34 | 1523.92 | 1498.84 | 0.00 | 0.00 | 0.00 |
December | 1757.17 | 1152.65 | 604.52 | 1397.20 | 2253.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2078.16 | 1109.66 | 968.50 | 2218.61 | 1218.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1650.88 | 459.96 | 604.52 | 1397.20 | 415.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2881.70 | 1947.10 | 1295.27 | 2805.42 | 2327.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 487.74 | 204.17 | 283.57 | 214.05 | 1782.43 | 0.00 | 0.00 | 0.00 |
February | 794.83 | 363.01 | 431.82 | 540.88 | 1429.65 | 0.00 | 0.00 | 0.00 |
March | 1046.15 | 535.39 | 510.76 | 853.30 | 1142.72 | 0.00 | 0.00 | 0.00 |
April | 1336.44 | 677.01 | 659.42 | 1310.32 | 732.55 | 0.00 | 0.00 | 0.00 |
May | 1642.14 | 783.51 | 858.62 | 1885.87 | 431.50 | 0.00 | 0.00 | 0.00 |
June | 1584.64 | 685.41 | 899.23 | 1932.24 | 297.80 | 0.00 | 0.00 | 0.00 |
July | 1691.68 | 786.64 | 905.04 | 2130.72 | 280.37 | 0.00 | 0.00 | 0.00 |
August | 1392.06 | 632.66 | 759.41 | 1700.02 | 323.35 | 0.00 | 0.00 | 0.00 |
September | 1087.96 | 488.90 | 599.06 | 1174.63 | 505.59 | 0.00 | 0.00 | 0.00 |
October | 687.19 | 275.88 | 411.31 | 578.70 | 741.98 | 0.00 | 0.00 | 0.00 |
November | 417.26 | 140.62 | 276.64 | 221.08 | 1072.22 | 0.00 | 0.00 | 0.00 |
December | 371.92 | 130.09 | 241.83 | 119.54 | 1720.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1046.38 | 475.95 | 570.43 | 1058.19 | 869.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 371.92 | 130.09 | 241.83 | 119.54 | 280.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1691.68 | 786.64 | 905.04 | 2130.72 | 1782.43 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.884528E+09 | 0.00 | 0.884528E+09 | 14380272.95 | 0.765342E+10 |
February | 0.122722E+10 | 0.00 | 0.122722E+10 | 0.125173E+09 | 0.543076E+10 |
March | 0.167165E+10 | 0.00 | 0.167165E+10 | 0.317524E+09 | 0.465808E+10 |
April | 0.212049E+10 | 16304275.49 | 0.210418E+10 | 0.108357E+10 | 0.269960E+10 |
May | 0.308091E+10 | 0.164719E+09 | 0.291619E+10 | 0.282263E+10 | 0.153257E+10 |
June | 0.332692E+10 | 0.364063E+09 | 0.296286E+10 | 0.371672E+10 | 0.103036E+10 |
July | 0.328384E+10 | 0.280304E+09 | 0.300353E+10 | 0.384350E+10 | 0.100302E+10 |
August | 0.249496E+10 | 42384900.95 | 0.245258E+10 | 0.264167E+10 | 0.117988E+10 |
September | 0.188188E+10 | 448890.36 | 0.188143E+10 | 0.147714E+10 | 0.185101E+10 |
October | 0.135024E+10 | 0.00 | 0.135024E+10 | 0.560168E+09 | 0.284101E+10 |
November | 0.865193E+09 | 0.00 | 0.865193E+09 | 89048577.30 | 0.420479E+10 |
December | 0.749443E+09 | 0.00 | 0.749443E+09 | 2243863.03 | 0.730760E+10 |
Annual Sum or Average | 0.229373E+11 | 0.868223E+09 | 0.220690E+11 | 0.166938E+11 | 0.413921E+11 |
Minimum of Months | 0.749443E+09 | 0.00 | 0.749443E+09 | 2243863.03 | 0.100302E+10 |
Maximum of Months | 0.332692E+10 | 0.364063E+09 | 0.300353E+10 | 0.384350E+10 | 0.765342E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129240E+10 | 0.539233E+09 | 0.753172E+09 | 0.520775E+09 | 0.459885E+10 |
February | 0.183472E+10 | 0.782458E+09 | 0.105226E+10 | 0.113832E+10 | 0.325079E+10 |
March | 0.276858E+10 | 0.138896E+10 | 0.137962E+10 | 0.216896E+10 | 0.285189E+10 |
April | 0.371446E+10 | 0.200386E+10 | 0.171060E+10 | 0.366809E+10 | 0.171837E+10 |
May | 0.415406E+10 | 0.182660E+10 | 0.232746E+10 | 0.464494E+10 | 0.104508E+10 |
June | 0.455133E+10 | 0.217777E+10 | 0.237356E+10 | 0.555701E+10 | 0.710926E+09 |
July | 0.460717E+10 | 0.216383E+10 | 0.244334E+10 | 0.577425E+10 | 0.684134E+09 |
August | 0.355190E+10 | 0.155278E+10 | 0.199912E+10 | 0.427535E+10 | 0.795267E+09 |
September | 0.275266E+10 | 0.123231E+10 | 0.152035E+10 | 0.293995E+10 | 0.119611E+10 |
October | 0.172212E+10 | 0.653057E+09 | 0.106907E+10 | 0.138422E+10 | 0.180722E+10 |
November | 0.106067E+10 | 0.354439E+09 | 0.706232E+09 | 0.540957E+09 | 0.259683E+10 |
December | 0.100000E+10 | 0.369395E+09 | 0.630606E+09 | 0.322758E+09 | 0.445253E+10 |
Annual Sum or Average | 0.330101E+11 | 0.150447E+11 | 0.179654E+11 | 0.329356E+11 | 0.257080E+11 |
Minimum of Months | 0.100000E+10 | 0.354439E+09 | 0.630606E+09 | 0.322758E+09 | 0.684134E+09 |
Maximum of Months | 0.460717E+10 | 0.217777E+10 | 0.244334E+10 | 0.577425E+10 | 0.459885E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.609577E+10 | 0.424217E+10 | 0.185360E+10 | 0.528749E+10 | 0.611866E+10 |
February | 0.697141E+10 | 0.471043E+10 | 0.226098E+10 | 0.681740E+10 | 0.461274E+10 |
March | 0.679752E+10 | 0.430256E+10 | 0.249496E+10 | 0.679497E+10 | 0.426216E+10 |
April | 0.595443E+10 | 0.323023E+10 | 0.272420E+10 | 0.649020E+10 | 0.276795E+10 |
May | 0.517017E+10 | 0.176362E+10 | 0.340655E+10 | 0.608033E+10 | 0.170150E+10 |
June | 0.448884E+10 | 0.119222E+10 | 0.329662E+10 | 0.563506E+10 | 0.113206E+10 |
July | 0.507119E+10 | 0.160194E+10 | 0.346924E+10 | 0.664983E+10 | 0.108414E+10 |
August | 0.541830E+10 | 0.226376E+10 | 0.315454E+10 | 0.689722E+10 | 0.125526E+10 |
September | 0.562087E+10 | 0.299330E+10 | 0.262757E+10 | 0.662101E+10 | 0.188884E+10 |
October | 0.496290E+10 | 0.292002E+10 | 0.204288E+10 | 0.520348E+10 | 0.274330E+10 |
November | 0.427907E+10 | 0.268671E+10 | 0.159236E+10 | 0.399194E+10 | 0.370530E+10 |
December | 0.470640E+10 | 0.308724E+10 | 0.161916E+10 | 0.376971E+10 | 0.590465E+10 |
Annual Sum or Average | 0.655369E+11 | 0.349942E+11 | 0.305427E+11 | 0.702386E+11 | 0.371766E+11 |
Minimum of Months | 0.427907E+10 | 0.119222E+10 | 0.159236E+10 | 0.376971E+10 | 0.108414E+10 |
Maximum of Months | 0.697141E+10 | 0.471043E+10 | 0.346924E+10 | 0.689722E+10 | 0.611866E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130637E+10 | 0.546844E+09 | 0.759522E+09 | 0.577280E+09 | 0.470113E+10 |
February | 0.192286E+10 | 0.878187E+09 | 0.104467E+10 | 0.131782E+10 | 0.337770E+10 |
March | 0.280201E+10 | 0.143399E+10 | 0.136802E+10 | 0.229927E+10 | 0.296469E+10 |
April | 0.346404E+10 | 0.175482E+10 | 0.170922E+10 | 0.341795E+10 | 0.181169E+10 |
May | 0.439830E+10 | 0.209856E+10 | 0.229974E+10 | 0.505786E+10 | 0.111761E+10 |
June | 0.410740E+10 | 0.177659E+10 | 0.233081E+10 | 0.500890E+10 | 0.748958E+09 |
July | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.570492E+10 | 0.731262E+09 |
August | 0.372850E+10 | 0.169451E+10 | 0.203399E+10 | 0.455470E+10 | 0.837566E+09 |
September | 0.282000E+10 | 0.126723E+10 | 0.155277E+10 | 0.306233E+10 | 0.124748E+10 |
October | 0.184056E+10 | 0.738915E+09 | 0.110164E+10 | 0.158417E+10 | 0.186328E+10 |
November | 0.108154E+10 | 0.364498E+09 | 0.717039E+09 | 0.588542E+09 | 0.265793E+10 |
December | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.325337E+09 | 0.452496E+10 |
Annual Sum or Average | 0.329987E+11 | 0.150095E+11 | 0.179892E+11 | 0.334991E+11 | 0.265843E+11 |
Minimum of Months | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.325337E+09 | 0.731262E+09 |
Maximum of Months | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.570492E+10 | 0.470113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294829E+09 | 0.00 | 0.294829E+09 | 4272530.22 | 0.255066E+10 |
February | 0.409052E+09 | 0.00 | 0.409052E+09 | 42467313.05 | 0.181388E+10 |
March | 0.557189E+09 | 0.00 | 0.557189E+09 | 0.116330E+09 | 0.153321E+10 |
April | 0.706795E+09 | 5434501.37 | 0.701361E+09 | 0.397844E+09 | 0.870802E+09 |
May | 0.102692E+10 | 54903652.56 | 0.972017E+09 | 0.991737E+09 | 0.480000E+09 |
June | 0.110892E+10 | 0.121349E+09 | 0.987572E+09 | 0.127481E+10 | 0.326138E+09 |
July | 0.109456E+10 | 93430121.84 | 0.100113E+10 | 0.130401E+10 | 0.325855E+09 |
August | 0.831615E+09 | 14127631.88 | 0.817487E+09 | 0.890328E+09 | 0.396841E+09 |
September | 0.627262E+09 | 149623.04 | 0.627113E+09 | 0.490023E+09 | 0.645627E+09 |
October | 0.450060E+09 | 0.00 | 0.450060E+09 | 0.174637E+09 | 0.101786E+10 |
November | 0.288384E+09 | 0.00 | 0.288384E+09 | 27019483.73 | 0.147449E+10 |
December | 0.249802E+09 | 0.00 | 0.249802E+09 | 195328.01 | 0.246144E+10 |
Annual Sum or Average | 0.764539E+10 | 0.289394E+09 | 0.735600E+10 | 0.571367E+10 | 0.138968E+11 |
Minimum of Months | 0.249802E+09 | 0.00 | 0.249802E+09 | 195328.01 | 0.325855E+09 |
Maximum of Months | 0.110892E+10 | 0.121349E+09 | 0.100113E+10 | 0.130401E+10 | 0.255066E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294840E+09 | 0.00 | 0.294840E+09 | 4272003.69 | 0.255082E+10 |
February | 0.409068E+09 | 0.00 | 0.409068E+09 | 42466290.71 | 0.181400E+10 |
March | 0.557212E+09 | 0.00 | 0.557212E+09 | 0.116329E+09 | 0.153331E+10 |
April | 0.706824E+09 | 5434647.45 | 0.701390E+09 | 0.397854E+09 | 0.870858E+09 |
May | 0.102696E+10 | 54905128.38 | 0.972055E+09 | 0.991768E+09 | 0.480028E+09 |
June | 0.110896E+10 | 0.121352E+09 | 0.987611E+09 | 0.127485E+10 | 0.326157E+09 |
July | 0.109460E+10 | 93432633.27 | 0.100117E+10 | 0.130406E+10 | 0.325873E+09 |
August | 0.831648E+09 | 14128011.63 | 0.817520E+09 | 0.890360E+09 | 0.396864E+09 |
September | 0.627287E+09 | 149627.06 | 0.627137E+09 | 0.490037E+09 | 0.645667E+09 |
October | 0.450077E+09 | 0.00 | 0.450077E+09 | 0.174638E+09 | 0.101792E+10 |
November | 0.288395E+09 | 0.00 | 0.288395E+09 | 27018668.32 | 0.147458E+10 |
December | 0.249812E+09 | 0.00 | 0.249812E+09 | 195215.54 | 0.246160E+10 |
Annual Sum or Average | 0.764569E+10 | 0.289402E+09 | 0.735629E+10 | 0.571385E+10 | 0.138977E+11 |
Minimum of Months | 0.249812E+09 | 0.00 | 0.249812E+09 | 195215.54 | 0.325873E+09 |
Maximum of Months | 0.110896E+10 | 0.121352E+09 | 0.100117E+10 | 0.130406E+10 | 0.255082E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294840E+09 | 0.00 | 0.294840E+09 | 4272003.69 | 0.255082E+10 |
February | 0.409068E+09 | 0.00 | 0.409068E+09 | 42466290.71 | 0.181400E+10 |
March | 0.557212E+09 | 0.00 | 0.557212E+09 | 0.116329E+09 | 0.153331E+10 |
April | 0.706824E+09 | 5434647.45 | 0.701390E+09 | 0.397854E+09 | 0.870858E+09 |
May | 0.102696E+10 | 54905128.38 | 0.972055E+09 | 0.991768E+09 | 0.480028E+09 |
June | 0.110896E+10 | 0.121352E+09 | 0.987611E+09 | 0.127485E+10 | 0.326157E+09 |
July | 0.109460E+10 | 93432633.27 | 0.100117E+10 | 0.130406E+10 | 0.325873E+09 |
August | 0.831648E+09 | 14128011.63 | 0.817520E+09 | 0.890360E+09 | 0.396864E+09 |
September | 0.627287E+09 | 149627.06 | 0.627137E+09 | 0.490037E+09 | 0.645667E+09 |
October | 0.450077E+09 | 0.00 | 0.450077E+09 | 0.174638E+09 | 0.101792E+10 |
November | 0.288395E+09 | 0.00 | 0.288395E+09 | 27018668.32 | 0.147458E+10 |
December | 0.249812E+09 | 0.00 | 0.249812E+09 | 195215.54 | 0.246160E+10 |
Annual Sum or Average | 0.764569E+10 | 0.289402E+09 | 0.735629E+10 | 0.571385E+10 | 0.138977E+11 |
Minimum of Months | 0.249812E+09 | 0.00 | 0.249812E+09 | 195215.54 | 0.325873E+09 |
Maximum of Months | 0.110896E+10 | 0.121352E+09 | 0.100117E+10 | 0.130406E+10 | 0.255082E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124323E+10 | 0.518713E+09 | 0.724514E+09 | 0.506463E+09 | 0.444229E+10 |
February | 0.176491E+10 | 0.752682E+09 | 0.101223E+10 | 0.110602E+10 | 0.315275E+10 |
March | 0.266323E+10 | 0.133611E+10 | 0.132713E+10 | 0.212680E+10 | 0.273384E+10 |
April | 0.357313E+10 | 0.192760E+10 | 0.164552E+10 | 0.358849E+10 | 0.164790E+10 |
May | 0.399600E+10 | 0.175709E+10 | 0.223890E+10 | 0.453970E+10 | 0.980656E+09 |
June | 0.437815E+10 | 0.209490E+10 | 0.228325E+10 | 0.539990E+10 | 0.674951E+09 |
July | 0.443186E+10 | 0.208149E+10 | 0.235038E+10 | 0.558958E+10 | 0.663548E+09 |
August | 0.341675E+10 | 0.149369E+10 | 0.192306E+10 | 0.413025E+10 | 0.796179E+09 |
September | 0.264792E+10 | 0.118542E+10 | 0.146250E+10 | 0.282182E+10 | 0.122440E+10 |
October | 0.165660E+10 | 0.628205E+09 | 0.102839E+10 | 0.129732E+10 | 0.189249E+10 |
November | 0.102031E+10 | 0.340952E+09 | 0.679361E+09 | 0.509595E+09 | 0.264497E+10 |
December | 0.961950E+09 | 0.355338E+09 | 0.606612E+09 | 0.310008E+09 | 0.433976E+10 |
Annual Sum or Average | 0.317540E+11 | 0.144722E+11 | 0.172818E+11 | 0.319259E+11 | 0.251937E+11 |
Minimum of Months | 0.961950E+09 | 0.340952E+09 | 0.606612E+09 | 0.310008E+09 | 0.663548E+09 |
Maximum of Months | 0.443186E+10 | 0.209490E+10 | 0.235038E+10 | 0.558958E+10 | 0.444229E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49156080.18 | 20509430.45 | 28646649.72 | 20025109.47 | 0.175644E+09 |
February | 69782885.10 | 29760364.49 | 40022520.61 | 43730901.22 | 0.124657E+09 |
March | 0.105302E+09 | 52828549.32 | 52473344.38 | 84091701.63 | 0.108094E+09 |
April | 0.141278E+09 | 76215721.32 | 65062453.55 | 0.141886E+09 | 65156420.77 |
May | 0.157998E+09 | 69473874.82 | 88524257.42 | 0.179496E+09 | 38774268.01 |
June | 0.173108E+09 | 82830298.59 | 90277623.76 | 0.213507E+09 | 26686965.09 |
July | 0.175232E+09 | 82300115.43 | 92931737.26 | 0.221007E+09 | 26236074.83 |
August | 0.135095E+09 | 59059323.93 | 76035873.42 | 0.163306E+09 | 31480190.04 |
September | 0.104696E+09 | 46870307.83 | 57825981.96 | 0.111572E+09 | 48411712.86 |
October | 65500344.76 | 24838662.95 | 40661681.81 | 51295008.92 | 74827412.67 |
November | 40342223.93 | 13480915.43 | 26861308.50 | 20148946.46 | 0.104580E+09 |
December | 38034641.72 | 14049750.95 | 23984890.77 | 12257433.63 | 0.171590E+09 |
Annual Sum or Average | 0.125553E+10 | 0.572217E+09 | 0.683308E+09 | 0.126232E+10 | 0.996137E+09 |
Minimum of Months | 38034641.72 | 13480915.43 | 23984890.77 | 12257433.63 | 26236074.83 |
Maximum of Months | 0.175232E+09 | 82830298.59 | 92931737.26 | 0.221007E+09 | 0.175644E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203189E+10 | 0.141403E+10 | 0.617857E+09 | 0.180414E+10 | 0.201714E+10 |
February | 0.232376E+10 | 0.157011E+10 | 0.753649E+09 | 0.231475E+10 | 0.154894E+10 |
March | 0.226580E+10 | 0.143416E+10 | 0.831645E+09 | 0.231483E+10 | 0.141698E+10 |
April | 0.198478E+10 | 0.107672E+10 | 0.908058E+09 | 0.220734E+10 | 0.918383E+09 |
May | 0.172337E+10 | 0.587862E+09 | 0.113551E+10 | 0.207362E+10 | 0.546431E+09 |
June | 0.149626E+10 | 0.397400E+09 | 0.109886E+10 | 0.191663E+10 | 0.361243E+09 |
July | 0.169037E+10 | 0.533970E+09 | 0.115640E+10 | 0.223973E+10 | 0.361438E+09 |
August | 0.180608E+10 | 0.754571E+09 | 0.105150E+10 | 0.231501E+10 | 0.434690E+09 |
September | 0.187359E+10 | 0.997748E+09 | 0.875845E+09 | 0.221692E+10 | 0.668889E+09 |
October | 0.165427E+10 | 0.973319E+09 | 0.680951E+09 | 0.173064E+10 | 0.994513E+09 |
November | 0.142633E+10 | 0.895552E+09 | 0.530780E+09 | 0.133487E+10 | 0.130543E+10 |
December | 0.156877E+10 | 0.102906E+10 | 0.539710E+09 | 0.127833E+10 | 0.196701E+10 |
Annual Sum or Average | 0.218453E+11 | 0.116645E+11 | 0.101808E+11 | 0.237468E+11 | 0.125411E+11 |
Minimum of Months | 0.142633E+10 | 0.397400E+09 | 0.530780E+09 | 0.127833E+10 | 0.361243E+09 |
Maximum of Months | 0.232376E+10 | 0.157011E+10 | 0.115640E+10 | 0.231501E+10 | 0.201714E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203189E+10 | 0.141403E+10 | 0.617857E+09 | 0.180414E+10 | 0.201714E+10 |
February | 0.232376E+10 | 0.157011E+10 | 0.753649E+09 | 0.231475E+10 | 0.154894E+10 |
March | 0.226580E+10 | 0.143416E+10 | 0.831645E+09 | 0.231483E+10 | 0.141698E+10 |
April | 0.198478E+10 | 0.107672E+10 | 0.908058E+09 | 0.220734E+10 | 0.918383E+09 |
May | 0.172337E+10 | 0.587862E+09 | 0.113551E+10 | 0.207362E+10 | 0.546431E+09 |
June | 0.149626E+10 | 0.397400E+09 | 0.109886E+10 | 0.191663E+10 | 0.361243E+09 |
July | 0.169037E+10 | 0.533970E+09 | 0.115640E+10 | 0.223973E+10 | 0.361438E+09 |
August | 0.180608E+10 | 0.754571E+09 | 0.105150E+10 | 0.231501E+10 | 0.434690E+09 |
September | 0.187359E+10 | 0.997748E+09 | 0.875845E+09 | 0.221692E+10 | 0.668889E+09 |
October | 0.165427E+10 | 0.973319E+09 | 0.680951E+09 | 0.173064E+10 | 0.994513E+09 |
November | 0.142633E+10 | 0.895552E+09 | 0.530780E+09 | 0.133487E+10 | 0.130543E+10 |
December | 0.156877E+10 | 0.102906E+10 | 0.539710E+09 | 0.127833E+10 | 0.196701E+10 |
Annual Sum or Average | 0.218453E+11 | 0.116645E+11 | 0.101808E+11 | 0.237468E+11 | 0.125411E+11 |
Minimum of Months | 0.142633E+10 | 0.397400E+09 | 0.530780E+09 | 0.127833E+10 | 0.361243E+09 |
Maximum of Months | 0.232376E+10 | 0.157011E+10 | 0.115640E+10 | 0.231501E+10 | 0.201714E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203176E+10 | 0.141394E+10 | 0.617818E+09 | 0.180402E+10 | 0.201701E+10 |
February | 0.232361E+10 | 0.157001E+10 | 0.753601E+09 | 0.231460E+10 | 0.154884E+10 |
March | 0.226566E+10 | 0.143407E+10 | 0.831592E+09 | 0.231468E+10 | 0.141689E+10 |
April | 0.198465E+10 | 0.107665E+10 | 0.908001E+09 | 0.220720E+10 | 0.918325E+09 |
May | 0.172326E+10 | 0.587825E+09 | 0.113543E+10 | 0.207349E+10 | 0.546397E+09 |
June | 0.149617E+10 | 0.397375E+09 | 0.109879E+10 | 0.191651E+10 | 0.361220E+09 |
July | 0.169027E+10 | 0.533936E+09 | 0.115633E+10 | 0.223959E+10 | 0.361415E+09 |
August | 0.180596E+10 | 0.754524E+09 | 0.105144E+10 | 0.231486E+10 | 0.434663E+09 |
September | 0.187347E+10 | 0.997685E+09 | 0.875790E+09 | 0.221678E+10 | 0.668847E+09 |
October | 0.165417E+10 | 0.973258E+09 | 0.680908E+09 | 0.173053E+10 | 0.994450E+09 |
November | 0.142624E+10 | 0.895495E+09 | 0.530746E+09 | 0.133478E+10 | 0.130535E+10 |
December | 0.156867E+10 | 0.102900E+10 | 0.539676E+09 | 0.127825E+10 | 0.196689E+10 |
Annual Sum or Average | 0.218439E+11 | 0.116638E+11 | 0.101801E+11 | 0.237453E+11 | 0.125403E+11 |
Minimum of Months | 0.142624E+10 | 0.397375E+09 | 0.530746E+09 | 0.127825E+10 | 0.361220E+09 |
Maximum of Months | 0.232361E+10 | 0.157001E+10 | 0.115633E+10 | 0.231486E+10 | 0.201701E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125666E+10 | 0.526036E+09 | 0.730625E+09 | 0.566531E+09 | 0.453679E+10 |
February | 0.184970E+10 | 0.844771E+09 | 0.100493E+10 | 0.129088E+10 | 0.327595E+10 |
March | 0.269540E+10 | 0.137942E+10 | 0.131598E+10 | 0.225916E+10 | 0.284728E+10 |
April | 0.333224E+10 | 0.168805E+10 | 0.164419E+10 | 0.335240E+10 | 0.174016E+10 |
May | 0.423096E+10 | 0.201871E+10 | 0.221225E+10 | 0.493248E+10 | 0.106090E+10 |
June | 0.395112E+10 | 0.170899E+10 | 0.224213E+10 | 0.487614E+10 | 0.709943E+09 |
July | 0.435860E+10 | 0.202677E+10 | 0.233184E+10 | 0.552178E+10 | 0.718090E+09 |
August | 0.358664E+10 | 0.163003E+10 | 0.195661E+10 | 0.439871E+10 | 0.843499E+09 |
September | 0.271270E+10 | 0.121901E+10 | 0.149369E+10 | 0.294202E+10 | 0.128213E+10 |
October | 0.177053E+10 | 0.710799E+09 | 0.105973E+10 | 0.149506E+10 | 0.195495E+10 |
November | 0.104039E+10 | 0.350628E+09 | 0.689758E+09 | 0.559165E+09 | 0.269854E+10 |
December | 0.958241E+09 | 0.335178E+09 | 0.623063E+09 | 0.315069E+09 | 0.440368E+10 |
Annual Sum or Average | 0.317432E+11 | 0.144384E+11 | 0.173048E+11 | 0.325094E+11 | 0.260719E+11 |
Minimum of Months | 0.958241E+09 | 0.335178E+09 | 0.623063E+09 | 0.315069E+09 | 0.709943E+09 |
Maximum of Months | 0.435860E+10 | 0.202677E+10 | 0.233184E+10 | 0.552178E+10 | 0.453679E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49687100.39 | 20798924.44 | 28888175.94 | 22399993.90 | 0.179381E+09 |
February | 73135131.13 | 33401384.62 | 39733746.51 | 51040160.96 | 0.129528E+09 |
March | 0.106573E+09 | 54540925.66 | 52032370.62 | 89324687.32 | 0.112579E+09 |
April | 0.131754E+09 | 66743720.37 | 65009794.56 | 0.132550E+09 | 68804397.84 |
May | 0.167288E+09 | 79817822.59 | 87469997.30 | 0.195025E+09 | 41946869.08 |
June | 0.156223E+09 | 67571647.86 | 88651610.84 | 0.192798E+09 | 28070489.61 |
July | 0.172335E+09 | 80136263.64 | 92198488.48 | 0.218326E+09 | 28392618.68 |
August | 0.141812E+09 | 64449686.32 | 77362333.32 | 0.173921E+09 | 33351194.69 |
September | 0.107257E+09 | 48198386.90 | 59059099.19 | 0.116324E+09 | 50694398.27 |
October | 70004893.37 | 28104246.62 | 41900646.75 | 59113106.31 | 77296864.81 |
November | 41135808.43 | 13863476.17 | 27272332.26 | 22108767.37 | 0.106698E+09 |
December | 37887896.16 | 13252589.52 | 24635306.64 | 12457460.19 | 0.174118E+09 |
Annual Sum or Average | 0.125509E+10 | 0.570879E+09 | 0.684214E+09 | 0.128539E+10 | 0.103086E+10 |
Minimum of Months | 37887896.16 | 13252589.52 | 24635306.64 | 12457460.19 | 28070489.61 |
Maximum of Months | 0.172335E+09 | 80136263.64 | 92198488.48 | 0.218326E+09 | 0.179381E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.884528E+09 | 0.00 | 0.884528E+09 | 11811011.52 | 0.777690E+10 |
February | 0.122722E+10 | 0.00 | 0.122722E+10 | 0.115982E+09 | 0.555748E+10 |
March | 0.167165E+10 | 0.00 | 0.167165E+10 | 0.301297E+09 | 0.480434E+10 |
April | 0.212049E+10 | 16304275.49 | 0.210418E+10 | 0.104903E+10 | 0.283305E+10 |
May | 0.308091E+10 | 0.164719E+09 | 0.291619E+10 | 0.280111E+10 | 0.158353E+10 |
June | 0.332692E+10 | 0.364063E+09 | 0.296286E+10 | 0.370844E+10 | 0.105902E+10 |
July | 0.328384E+10 | 0.280304E+09 | 0.300353E+10 | 0.383891E+10 | 0.102709E+10 |
August | 0.249496E+10 | 42384900.95 | 0.245258E+10 | 0.263239E+10 | 0.122081E+10 |
September | 0.188188E+10 | 448890.36 | 0.188143E+10 | 0.144474E+10 | 0.195072E+10 |
October | 0.135024E+10 | 0.00 | 0.135024E+10 | 0.513015E+09 | 0.303769E+10 |
November | 0.865193E+09 | 0.00 | 0.865193E+09 | 78570235.73 | 0.439912E+10 |
December | 0.749443E+09 | 0.00 | 0.749443E+09 | 723697.39 | 0.744816E+10 |
Annual Sum or Average | 0.229373E+11 | 0.868223E+09 | 0.220690E+11 | 0.164960E+11 | 0.426979E+11 |
Minimum of Months | 0.749443E+09 | 0.00 | 0.749443E+09 | 723697.39 | 0.102709E+10 |
Maximum of Months | 0.332692E+10 | 0.364063E+09 | 0.300353E+10 | 0.383891E+10 | 0.777690E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129240E+10 | 0.539233E+09 | 0.753172E+09 | 0.515118E+09 | 0.466506E+10 |
February | 0.183472E+10 | 0.782458E+09 | 0.105226E+10 | 0.112270E+10 | 0.332606E+10 |
March | 0.276858E+10 | 0.138896E+10 | 0.137962E+10 | 0.214314E+10 | 0.294357E+10 |
April | 0.371446E+10 | 0.200386E+10 | 0.171060E+10 | 0.363500E+10 | 0.179960E+10 |
May | 0.415406E+10 | 0.182660E+10 | 0.232746E+10 | 0.462921E+10 | 0.107613E+10 |
June | 0.455133E+10 | 0.217777E+10 | 0.237356E+10 | 0.554920E+10 | 0.730605E+09 |
July | 0.460717E+10 | 0.216383E+10 | 0.244334E+10 | 0.576725E+10 | 0.700692E+09 |
August | 0.355190E+10 | 0.155278E+10 | 0.199912E+10 | 0.426642E+10 | 0.821653E+09 |
September | 0.275266E+10 | 0.123231E+10 | 0.152035E+10 | 0.291381E+10 | 0.125402E+10 |
October | 0.172212E+10 | 0.653057E+09 | 0.106907E+10 | 0.133944E+10 | 0.192849E+10 |
November | 0.106067E+10 | 0.354439E+09 | 0.706232E+09 | 0.522672E+09 | 0.271849E+10 |
December | 0.100000E+10 | 0.369395E+09 | 0.630606E+09 | 0.317306E+09 | 0.453148E+10 |
Annual Sum or Average | 0.330101E+11 | 0.150447E+11 | 0.179654E+11 | 0.327213E+11 | 0.264958E+11 |
Minimum of Months | 0.100000E+10 | 0.354439E+09 | 0.630606E+09 | 0.317306E+09 | 0.700692E+09 |
Maximum of Months | 0.460717E+10 | 0.217777E+10 | 0.244334E+10 | 0.576725E+10 | 0.466506E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.609577E+10 | 0.424217E+10 | 0.185360E+10 | 0.526387E+10 | 0.623462E+10 |
February | 0.697141E+10 | 0.471043E+10 | 0.226098E+10 | 0.678687E+10 | 0.474222E+10 |
March | 0.679752E+10 | 0.430256E+10 | 0.249496E+10 | 0.676333E+10 | 0.440486E+10 |
April | 0.595443E+10 | 0.323023E+10 | 0.272420E+10 | 0.645925E+10 | 0.289709E+10 |
May | 0.517017E+10 | 0.176362E+10 | 0.340655E+10 | 0.607175E+10 | 0.175888E+10 |
June | 0.448884E+10 | 0.119222E+10 | 0.329662E+10 | 0.563382E+10 | 0.116696E+10 |
July | 0.507119E+10 | 0.160194E+10 | 0.346924E+10 | 0.665150E+10 | 0.111341E+10 |
August | 0.541830E+10 | 0.226376E+10 | 0.315454E+10 | 0.689700E+10 | 0.129805E+10 |
September | 0.562087E+10 | 0.299330E+10 | 0.262757E+10 | 0.659970E+10 | 0.197957E+10 |
October | 0.496290E+10 | 0.292002E+10 | 0.204288E+10 | 0.514687E+10 | 0.291972E+10 |
November | 0.427907E+10 | 0.268671E+10 | 0.159236E+10 | 0.394999E+10 | 0.388498E+10 |
December | 0.470640E+10 | 0.308724E+10 | 0.161916E+10 | 0.374226E+10 | 0.603495E+10 |
Annual Sum or Average | 0.655369E+11 | 0.349942E+11 | 0.305427E+11 | 0.699662E+11 | 0.384353E+11 |
Minimum of Months | 0.427907E+10 | 0.119222E+10 | 0.159236E+10 | 0.374226E+10 | 0.111341E+10 |
Maximum of Months | 0.697141E+10 | 0.471043E+10 | 0.346924E+10 | 0.689700E+10 | 0.623462E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130637E+10 | 0.546844E+09 | 0.759522E+09 | 0.573309E+09 | 0.477406E+10 |
February | 0.192286E+10 | 0.878187E+09 | 0.104467E+10 | 0.130851E+10 | 0.345860E+10 |
March | 0.280201E+10 | 0.143399E+10 | 0.136802E+10 | 0.228549E+10 | 0.306066E+10 |
April | 0.346404E+10 | 0.175482E+10 | 0.170922E+10 | 0.339635E+10 | 0.189876E+10 |
May | 0.439830E+10 | 0.209856E+10 | 0.229974E+10 | 0.505111E+10 | 0.115573E+10 |
June | 0.410740E+10 | 0.177659E+10 | 0.233081E+10 | 0.500837E+10 | 0.771907E+09 |
July | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.570693E+10 | 0.750946E+09 |
August | 0.372850E+10 | 0.169451E+10 | 0.203399E+10 | 0.455333E+10 | 0.866072E+09 |
September | 0.282000E+10 | 0.126723E+10 | 0.155277E+10 | 0.304464E+10 | 0.131050E+10 |
October | 0.184056E+10 | 0.738915E+09 | 0.110164E+10 | 0.154998E+10 | 0.198732E+10 |
November | 0.108154E+10 | 0.364498E+09 | 0.717039E+09 | 0.573028E+09 | 0.277919E+10 |
December | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.320166E+09 | 0.460926E+10 |
Annual Sum or Average | 0.329987E+11 | 0.150095E+11 | 0.179892E+11 | 0.333712E+11 | 0.274230E+11 |
Minimum of Months | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.320166E+09 | 0.750946E+09 |
Maximum of Months | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.570693E+10 | 0.477406E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.37 | 2857.46 | 330.24 | 0.00 | 330.24 | 0.00 | 0.00 |
February | 51.74 | 2244.86 | 507.28 | 0.00 | 507.28 | 0.00 | 0.00 |
March | 118.55 | 1739.13 | 624.12 | 0.00 | 624.12 | 0.00 | 0.00 |
April | 418.04 | 1041.51 | 818.09 | 6.29 | 811.80 | 0.00 | 0.00 |
May | 1053.85 | 572.20 | 1150.28 | 61.50 | 1088.78 | 0.00 | 0.00 |
June | 1433.92 | 397.51 | 1283.53 | 140.46 | 1143.08 | 0.00 | 0.00 |
July | 1435.00 | 374.48 | 1226.04 | 104.65 | 1121.39 | 0.00 | 0.00 |
August | 986.29 | 440.52 | 931.51 | 15.82 | 915.69 | 0.00 | 0.00 |
September | 569.89 | 714.12 | 726.03 | 0.17 | 725.86 | 0.00 | 0.00 |
October | 209.14 | 1060.71 | 504.12 | 0.00 | 504.12 | 0.00 | 0.00 |
November | 34.36 | 1622.22 | 333.79 | 0.00 | 333.79 | 0.00 | 0.00 |
December | 0.84 | 2728.35 | 279.81 | 0.00 | 279.81 | 0.00 | 0.00 |
Annual Sum or Average | 529.36 | 1312.53 | 727.34 | 27.53 | 699.80 | 0.00 | 0.00 |
Minimum of Months | 0.84 | 374.48 | 279.81 | 0.00 | 279.81 | 0.00 | 0.00 |
Maximum of Months | 1435.00 | 2857.46 | 1283.53 | 140.46 | 1143.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 194.43 | 1717.01 | 482.53 | 201.33 | 281.20 | 0.00 | 0.00 |
February | 470.54 | 1343.75 | 758.40 | 323.44 | 434.96 | 0.00 | 0.00 |
March | 809.80 | 1064.77 | 1033.67 | 518.58 | 515.09 | 0.00 | 0.00 |
April | 1415.16 | 662.95 | 1433.05 | 773.09 | 659.96 | 0.00 | 0.00 |
May | 1734.22 | 390.19 | 1550.95 | 681.98 | 868.97 | 0.00 | 0.00 |
June | 2143.91 | 274.28 | 1755.91 | 840.19 | 915.72 | 0.00 | 0.00 |
July | 2155.86 | 255.43 | 1720.12 | 807.88 | 912.24 | 0.00 | 0.00 |
August | 1596.23 | 296.92 | 1326.13 | 579.74 | 746.38 | 0.00 | 0.00 |
September | 1134.24 | 461.46 | 1061.98 | 475.43 | 586.55 | 0.00 | 0.00 |
October | 516.81 | 674.74 | 642.97 | 243.82 | 399.14 | 0.00 | 0.00 |
November | 208.70 | 1001.86 | 409.21 | 136.74 | 272.47 | 0.00 | 0.00 |
December | 120.50 | 1662.39 | 373.36 | 137.92 | 235.44 | 0.00 | 0.00 |
Annual Sum or Average | 1044.38 | 815.20 | 1046.74 | 477.06 | 569.68 | 0.00 | 0.00 |
Minimum of Months | 120.50 | 255.43 | 373.36 | 136.74 | 235.44 | 0.00 | 0.00 |
Maximum of Months | 2155.86 | 1717.01 | 1755.91 | 840.19 | 915.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1974.12 | 2284.45 | 2275.90 | 1583.85 | 692.05 | 0.00 | 0.00 |
February | 2818.04 | 1906.72 | 2881.70 | 1947.10 | 934.60 | 0.00 | 0.00 |
March | 2536.95 | 1591.31 | 2537.90 | 1606.39 | 931.51 | 0.00 | 0.00 |
April | 2503.94 | 1067.88 | 2297.23 | 1246.23 | 1051.00 | 0.00 | 0.00 |
May | 2270.13 | 635.27 | 1930.32 | 658.46 | 1271.86 | 0.00 | 0.00 |
June | 2174.02 | 436.75 | 1731.81 | 459.96 | 1271.84 | 0.00 | 0.00 |
July | 2482.76 | 404.77 | 1893.36 | 598.10 | 1295.27 | 0.00 | 0.00 |
August | 2575.13 | 468.66 | 2022.96 | 845.19 | 1177.77 | 0.00 | 0.00 |
September | 2554.40 | 728.72 | 2168.55 | 1154.82 | 1013.72 | 0.00 | 0.00 |
October | 1942.76 | 1024.23 | 1852.93 | 1090.21 | 762.72 | 0.00 | 0.00 |
November | 1540.10 | 1429.51 | 1650.88 | 1036.54 | 614.34 | 0.00 | 0.00 |
December | 1407.45 | 2204.54 | 1757.17 | 1152.65 | 604.52 | 0.00 | 0.00 |
Annual Sum or Average | 2227.25 | 1178.86 | 2078.16 | 1109.66 | 968.50 | 0.00 | 0.00 |
Minimum of Months | 1407.45 | 404.77 | 1650.88 | 459.96 | 604.52 | 0.00 | 0.00 |
Maximum of Months | 2818.04 | 2284.45 | 2881.70 | 1947.10 | 1295.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.53 | 1755.20 | 487.74 | 204.17 | 283.57 | 0.00 | 0.00 |
February | 544.73 | 1396.21 | 794.83 | 363.01 | 431.82 | 0.00 | 0.00 |
March | 858.45 | 1106.89 | 1046.15 | 535.39 | 510.76 | 0.00 | 0.00 |
April | 1318.65 | 698.95 | 1336.44 | 677.01 | 659.42 | 0.00 | 0.00 |
May | 1888.39 | 417.27 | 1642.14 | 783.51 | 858.62 | 0.00 | 0.00 |
June | 1932.45 | 288.95 | 1584.64 | 685.41 | 899.23 | 0.00 | 0.00 |
July | 2129.97 | 273.02 | 1691.68 | 786.64 | 905.04 | 0.00 | 0.00 |
August | 1700.53 | 312.71 | 1392.06 | 632.66 | 759.41 | 0.00 | 0.00 |
September | 1181.45 | 481.28 | 1087.96 | 488.90 | 599.06 | 0.00 | 0.00 |
October | 591.46 | 695.67 | 687.19 | 275.88 | 411.31 | 0.00 | 0.00 |
November | 227.06 | 1025.44 | 417.26 | 140.62 | 276.64 | 0.00 | 0.00 |
December | 121.47 | 1689.43 | 371.92 | 130.09 | 241.83 | 0.00 | 0.00 |
Annual Sum or Average | 1062.25 | 842.98 | 1046.38 | 475.95 | 570.43 | 0.00 | 0.00 |
Minimum of Months | 121.47 | 273.02 | 371.92 | 130.09 | 241.83 | 0.00 | 0.00 |
Maximum of Months | 2129.97 | 1755.20 | 1691.68 | 786.64 | 905.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.79 | 2857.04 | 330.24 | 0.00 | 330.24 | 0.00 | 0.00 |
February | 52.66 | 2249.45 | 507.27 | 0.00 | 507.27 | 0.00 | 0.00 |
March | 130.30 | 1717.38 | 624.11 | 0.00 | 624.11 | 0.00 | 0.00 |
April | 460.47 | 1007.92 | 818.07 | 6.29 | 811.78 | 0.00 | 0.00 |
May | 1110.84 | 537.66 | 1150.25 | 61.50 | 1088.76 | 0.00 | 0.00 |
June | 1475.51 | 377.49 | 1283.51 | 140.45 | 1143.05 | 0.00 | 0.00 |
July | 1460.62 | 364.99 | 1226.02 | 104.65 | 1121.37 | 0.00 | 0.00 |
August | 997.25 | 444.51 | 931.49 | 15.82 | 915.67 | 0.00 | 0.00 |
September | 567.17 | 747.28 | 726.02 | 0.17 | 725.84 | 0.00 | 0.00 |
October | 195.61 | 1140.12 | 504.11 | 0.00 | 504.11 | 0.00 | 0.00 |
November | 31.27 | 1706.66 | 333.79 | 0.00 | 333.79 | 0.00 | 0.00 |
December | 0.22 | 2757.11 | 279.80 | 0.00 | 279.80 | 0.00 | 0.00 |
Annual Sum or Average | 543.55 | 1322.05 | 727.32 | 27.53 | 699.79 | 0.00 | 0.00 |
Minimum of Months | 0.22 | 364.99 | 279.80 | 0.00 | 279.80 | 0.00 | 0.00 |
Maximum of Months | 1475.51 | 2857.04 | 1283.51 | 140.45 | 1143.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.57 | 1724.14 | 482.52 | 201.32 | 281.20 | 0.00 | 0.00 |
February | 475.26 | 1354.75 | 758.39 | 323.43 | 434.96 | 0.00 | 0.00 |
March | 825.45 | 1061.06 | 1033.65 | 518.57 | 515.08 | 0.00 | 0.00 |
April | 1439.19 | 660.90 | 1433.03 | 773.08 | 659.95 | 0.00 | 0.00 |
May | 1761.95 | 380.61 | 1550.92 | 681.96 | 868.96 | 0.00 | 0.00 |
June | 2165.67 | 270.69 | 1755.88 | 840.17 | 915.71 | 0.00 | 0.00 |
July | 2169.42 | 257.54 | 1720.09 | 807.87 | 912.23 | 0.00 | 0.00 |
August | 1603.03 | 309.01 | 1326.11 | 579.73 | 746.38 | 0.00 | 0.00 |
September | 1131.71 | 491.05 | 1061.97 | 475.42 | 586.55 | 0.00 | 0.00 |
October | 503.52 | 734.51 | 642.96 | 243.82 | 399.14 | 0.00 | 0.00 |
November | 204.38 | 1060.78 | 409.20 | 136.74 | 272.46 | 0.00 | 0.00 |
December | 120.32 | 1684.34 | 373.35 | 137.91 | 235.44 | 0.00 | 0.00 |
Annual Sum or Average | 1052.39 | 830.48 | 1046.73 | 477.05 | 569.67 | 0.00 | 0.00 |
Minimum of Months | 120.32 | 257.54 | 373.35 | 136.74 | 235.44 | 0.00 | 0.00 |
Maximum of Months | 2169.42 | 1724.14 | 1755.88 | 840.17 | 915.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2020.72 | 2259.29 | 2275.81 | 1583.78 | 692.03 | 0.00 | 0.00 |
February | 2870.41 | 1920.76 | 2881.59 | 1947.02 | 934.56 | 0.00 | 0.00 |
March | 2592.72 | 1587.08 | 2537.81 | 1606.32 | 931.48 | 0.00 | 0.00 |
April | 2554.73 | 1062.92 | 2297.15 | 1246.18 | 1050.97 | 0.00 | 0.00 |
May | 2322.56 | 612.03 | 1930.25 | 658.43 | 1271.82 | 0.00 | 0.00 |
June | 2218.28 | 418.10 | 1731.75 | 459.94 | 1271.81 | 0.00 | 0.00 |
July | 2508.61 | 404.83 | 1893.30 | 598.07 | 1295.23 | 0.00 | 0.00 |
August | 2592.92 | 486.87 | 2022.89 | 845.16 | 1177.73 | 0.00 | 0.00 |
September | 2565.82 | 774.16 | 2168.46 | 1154.78 | 1013.69 | 0.00 | 0.00 |
October | 1938.40 | 1113.90 | 1852.86 | 1090.16 | 762.70 | 0.00 | 0.00 |
November | 1544.96 | 1510.89 | 1650.81 | 1036.50 | 614.32 | 0.00 | 0.00 |
December | 1431.79 | 2203.15 | 1757.10 | 1152.60 | 604.50 | 0.00 | 0.00 |
Annual Sum or Average | 2258.97 | 1193.00 | 2078.08 | 1109.61 | 968.47 | 0.00 | 0.00 |
Minimum of Months | 1431.79 | 404.83 | 1650.81 | 459.94 | 604.50 | 0.00 | 0.00 |
Maximum of Months | 2870.41 | 2259.29 | 2881.59 | 1947.02 | 1295.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.88 | 1760.82 | 487.73 | 204.16 | 283.57 | 0.00 | 0.00 |
February | 554.70 | 1407.69 | 794.82 | 363.00 | 431.82 | 0.00 | 0.00 |
March | 876.82 | 1105.09 | 1046.14 | 535.38 | 510.76 | 0.00 | 0.00 |
April | 1344.50 | 697.90 | 1336.42 | 677.00 | 659.41 | 0.00 | 0.00 |
May | 1914.39 | 411.75 | 1642.12 | 783.50 | 858.62 | 0.00 | 0.00 |
June | 1955.61 | 284.73 | 1584.62 | 685.40 | 899.22 | 0.00 | 0.00 |
July | 2143.11 | 278.70 | 1691.66 | 786.63 | 905.03 | 0.00 | 0.00 |
August | 1707.23 | 327.38 | 1392.04 | 632.65 | 759.40 | 0.00 | 0.00 |
September | 1179.92 | 514.21 | 1087.95 | 488.89 | 599.06 | 0.00 | 0.00 |
October | 580.26 | 758.75 | 687.18 | 275.87 | 411.30 | 0.00 | 0.00 |
November | 224.26 | 1082.27 | 417.25 | 140.62 | 276.63 | 0.00 | 0.00 |
December | 122.28 | 1709.15 | 371.91 | 130.09 | 241.82 | 0.00 | 0.00 |
Annual Sum or Average | 1071.63 | 859.42 | 1046.37 | 475.94 | 570.43 | 0.00 | 0.00 |
Minimum of Months | 122.28 | 278.70 | 371.91 | 130.09 | 241.82 | 0.00 | 0.00 |
Maximum of Months | 2143.11 | 1760.82 | 1691.66 | 786.63 | 905.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.41 | 2903.56 | 330.24 | 0.00 | 330.24 | 0.00 | 0.00 |
February | 47.94 | 2297.24 | 507.28 | 0.00 | 507.28 | 0.00 | 0.00 |
March | 112.49 | 1793.74 | 624.12 | 0.00 | 624.12 | 0.00 | 0.00 |
April | 404.72 | 1093.00 | 818.09 | 6.29 | 811.80 | 0.00 | 0.00 |
May | 1045.82 | 591.22 | 1150.28 | 61.50 | 1088.78 | 0.00 | 0.00 |
June | 1430.73 | 408.57 | 1283.53 | 140.46 | 1143.08 | 0.00 | 0.00 |
July | 1433.29 | 383.47 | 1226.04 | 104.65 | 1121.39 | 0.00 | 0.00 |
August | 982.82 | 455.80 | 931.51 | 15.82 | 915.69 | 0.00 | 0.00 |
September | 557.38 | 752.59 | 726.03 | 0.17 | 725.86 | 0.00 | 0.00 |
October | 191.54 | 1134.14 | 504.12 | 0.00 | 504.12 | 0.00 | 0.00 |
November | 30.31 | 1697.19 | 333.79 | 0.00 | 333.79 | 0.00 | 0.00 |
December | 0.27 | 2780.83 | 279.81 | 0.00 | 279.81 | 0.00 | 0.00 |
Annual Sum or Average | 523.09 | 1353.94 | 727.34 | 27.53 | 699.80 | 0.00 | 0.00 |
Minimum of Months | 0.27 | 383.47 | 279.81 | 0.00 | 279.81 | 0.00 | 0.00 |
Maximum of Months | 1433.29 | 2903.56 | 1283.53 | 140.46 | 1143.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 192.32 | 1741.74 | 482.53 | 201.33 | 281.20 | 0.00 | 0.00 |
February | 464.08 | 1374.86 | 758.40 | 323.44 | 434.96 | 0.00 | 0.00 |
March | 800.16 | 1099.00 | 1033.67 | 518.58 | 515.09 | 0.00 | 0.00 |
April | 1402.39 | 694.29 | 1433.05 | 773.09 | 659.96 | 0.00 | 0.00 |
May | 1728.35 | 401.78 | 1550.95 | 681.98 | 868.97 | 0.00 | 0.00 |
June | 2140.90 | 281.87 | 1755.91 | 840.19 | 915.72 | 0.00 | 0.00 |
July | 2153.25 | 261.61 | 1720.12 | 807.88 | 912.24 | 0.00 | 0.00 |
August | 1592.90 | 306.77 | 1326.13 | 579.74 | 746.38 | 0.00 | 0.00 |
September | 1124.15 | 483.80 | 1061.98 | 475.43 | 586.55 | 0.00 | 0.00 |
October | 500.09 | 720.02 | 642.97 | 243.82 | 399.14 | 0.00 | 0.00 |
November | 201.65 | 1048.80 | 409.21 | 136.74 | 272.47 | 0.00 | 0.00 |
December | 118.47 | 1691.86 | 373.36 | 137.92 | 235.44 | 0.00 | 0.00 |
Annual Sum or Average | 1037.58 | 840.18 | 1046.74 | 477.06 | 569.68 | 0.00 | 0.00 |
Minimum of Months | 118.47 | 261.61 | 373.36 | 136.74 | 235.44 | 0.00 | 0.00 |
Maximum of Months | 2153.25 | 1741.74 | 1755.91 | 840.19 | 915.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1965.31 | 2327.74 | 2275.90 | 1583.85 | 692.05 | 0.00 | 0.00 |
February | 2805.42 | 1960.24 | 2881.70 | 1947.10 | 934.60 | 0.00 | 0.00 |
March | 2525.14 | 1644.59 | 2537.90 | 1606.39 | 931.51 | 0.00 | 0.00 |
April | 2491.99 | 1117.71 | 2297.23 | 1246.23 | 1051.00 | 0.00 | 0.00 |
May | 2266.93 | 656.69 | 1930.32 | 658.46 | 1271.86 | 0.00 | 0.00 |
June | 2173.54 | 450.21 | 1731.81 | 459.96 | 1271.84 | 0.00 | 0.00 |
July | 2483.39 | 415.70 | 1893.36 | 598.10 | 1295.27 | 0.00 | 0.00 |
August | 2575.04 | 484.64 | 2022.96 | 845.19 | 1177.77 | 0.00 | 0.00 |
September | 2546.18 | 763.72 | 2168.55 | 1154.82 | 1013.72 | 0.00 | 0.00 |
October | 1921.62 | 1090.10 | 1852.93 | 1090.21 | 762.72 | 0.00 | 0.00 |
November | 1523.92 | 1498.84 | 1650.88 | 1036.54 | 614.34 | 0.00 | 0.00 |
December | 1397.20 | 2253.19 | 1757.17 | 1152.65 | 604.52 | 0.00 | 0.00 |
Annual Sum or Average | 2218.61 | 1218.78 | 2078.16 | 1109.66 | 968.50 | 0.00 | 0.00 |
Minimum of Months | 1397.20 | 415.70 | 1650.88 | 459.96 | 604.52 | 0.00 | 0.00 |
Maximum of Months | 2805.42 | 2327.74 | 2881.70 | 1947.10 | 1295.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.05 | 1782.43 | 487.74 | 204.17 | 283.57 | 0.00 | 0.00 |
February | 540.88 | 1429.65 | 794.83 | 363.01 | 431.82 | 0.00 | 0.00 |
March | 853.30 | 1142.72 | 1046.15 | 535.39 | 510.76 | 0.00 | 0.00 |
April | 1310.32 | 732.55 | 1336.44 | 677.01 | 659.42 | 0.00 | 0.00 |
May | 1885.87 | 431.50 | 1642.14 | 783.51 | 858.62 | 0.00 | 0.00 |
June | 1932.24 | 297.80 | 1584.64 | 685.41 | 899.23 | 0.00 | 0.00 |
July | 2130.72 | 280.37 | 1691.68 | 786.64 | 905.04 | 0.00 | 0.00 |
August | 1700.02 | 323.35 | 1392.06 | 632.66 | 759.41 | 0.00 | 0.00 |
September | 1174.63 | 505.59 | 1087.96 | 488.90 | 599.06 | 0.00 | 0.00 |
October | 578.70 | 741.98 | 687.19 | 275.88 | 411.31 | 0.00 | 0.00 |
November | 221.08 | 1072.22 | 417.26 | 140.62 | 276.64 | 0.00 | 0.00 |
December | 119.54 | 1720.90 | 371.92 | 130.09 | 241.83 | 0.00 | 0.00 |
Annual Sum or Average | 1058.19 | 869.58 | 1046.38 | 475.95 | 570.43 | 0.00 | 0.00 |
Minimum of Months | 119.54 | 280.37 | 371.92 | 130.09 | 241.83 | 0.00 | 0.00 |
Maximum of Months | 2130.72 | 1782.43 | 1691.68 | 786.64 | 905.04 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14380272.95 | 0.765342E+10 | 0.884528E+09 | 0.00 | 0.884528E+09 | 0.00 | 0.00 |
February | 0.125173E+09 | 0.543076E+10 | 0.122722E+10 | 0.00 | 0.122722E+10 | 0.00 | 0.00 |
March | 0.317524E+09 | 0.465808E+10 | 0.167165E+10 | 0.00 | 0.167165E+10 | 0.00 | 0.00 |
April | 0.108357E+10 | 0.269960E+10 | 0.212049E+10 | 16304275.49 | 0.210418E+10 | 0.00 | 0.00 |
May | 0.282263E+10 | 0.153257E+10 | 0.308091E+10 | 0.164719E+09 | 0.291619E+10 | 0.00 | 0.00 |
June | 0.371672E+10 | 0.103036E+10 | 0.332692E+10 | 0.364063E+09 | 0.296286E+10 | 0.00 | 0.00 |
July | 0.384350E+10 | 0.100302E+10 | 0.328384E+10 | 0.280304E+09 | 0.300353E+10 | 0.00 | 0.00 |
August | 0.264167E+10 | 0.117988E+10 | 0.249496E+10 | 42384900.95 | 0.245258E+10 | 0.00 | 0.00 |
September | 0.147714E+10 | 0.185101E+10 | 0.188188E+10 | 448890.36 | 0.188143E+10 | 0.00 | 0.00 |
October | 0.560168E+09 | 0.284101E+10 | 0.135024E+10 | 0.00 | 0.135024E+10 | 0.00 | 0.00 |
November | 89048577.30 | 0.420479E+10 | 0.865193E+09 | 0.00 | 0.865193E+09 | 0.00 | 0.00 |
December | 2243863.03 | 0.730760E+10 | 0.749443E+09 | 0.00 | 0.749443E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166938E+11 | 0.413921E+11 | 0.229373E+11 | 0.868223E+09 | 0.220690E+11 | 0.00 | 0.00 |
Minimum of Months | 2243863.03 | 0.100302E+10 | 0.749443E+09 | 0.00 | 0.749443E+09 | 0.00 | 0.00 |
Maximum of Months | 0.384350E+10 | 0.765342E+10 | 0.332692E+10 | 0.364063E+09 | 0.300353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.520775E+09 | 0.459885E+10 | 0.129240E+10 | 0.539233E+09 | 0.753172E+09 | 0.00 | 0.00 |
February | 0.113832E+10 | 0.325079E+10 | 0.183472E+10 | 0.782458E+09 | 0.105226E+10 | 0.00 | 0.00 |
March | 0.216896E+10 | 0.285189E+10 | 0.276858E+10 | 0.138896E+10 | 0.137962E+10 | 0.00 | 0.00 |
April | 0.366809E+10 | 0.171837E+10 | 0.371446E+10 | 0.200386E+10 | 0.171060E+10 | 0.00 | 0.00 |
May | 0.464494E+10 | 0.104508E+10 | 0.415406E+10 | 0.182660E+10 | 0.232746E+10 | 0.00 | 0.00 |
June | 0.555701E+10 | 0.710926E+09 | 0.455133E+10 | 0.217777E+10 | 0.237356E+10 | 0.00 | 0.00 |
July | 0.577425E+10 | 0.684134E+09 | 0.460717E+10 | 0.216383E+10 | 0.244334E+10 | 0.00 | 0.00 |
August | 0.427535E+10 | 0.795267E+09 | 0.355190E+10 | 0.155278E+10 | 0.199912E+10 | 0.00 | 0.00 |
September | 0.293995E+10 | 0.119611E+10 | 0.275266E+10 | 0.123231E+10 | 0.152035E+10 | 0.00 | 0.00 |
October | 0.138422E+10 | 0.180722E+10 | 0.172212E+10 | 0.653057E+09 | 0.106907E+10 | 0.00 | 0.00 |
November | 0.540957E+09 | 0.259683E+10 | 0.106067E+10 | 0.354439E+09 | 0.706232E+09 | 0.00 | 0.00 |
December | 0.322758E+09 | 0.445253E+10 | 0.100000E+10 | 0.369395E+09 | 0.630606E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.329356E+11 | 0.257080E+11 | 0.330101E+11 | 0.150447E+11 | 0.179654E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322758E+09 | 0.684134E+09 | 0.100000E+10 | 0.354439E+09 | 0.630606E+09 | 0.00 | 0.00 |
Maximum of Months | 0.577425E+10 | 0.459885E+10 | 0.460717E+10 | 0.217777E+10 | 0.244334E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.528749E+10 | 0.611866E+10 | 0.609577E+10 | 0.424217E+10 | 0.185360E+10 | 0.00 | 0.00 |
February | 0.681740E+10 | 0.461274E+10 | 0.697141E+10 | 0.471043E+10 | 0.226098E+10 | 0.00 | 0.00 |
March | 0.679497E+10 | 0.426216E+10 | 0.679752E+10 | 0.430256E+10 | 0.249496E+10 | 0.00 | 0.00 |
April | 0.649020E+10 | 0.276795E+10 | 0.595443E+10 | 0.323023E+10 | 0.272420E+10 | 0.00 | 0.00 |
May | 0.608033E+10 | 0.170150E+10 | 0.517017E+10 | 0.176362E+10 | 0.340655E+10 | 0.00 | 0.00 |
June | 0.563506E+10 | 0.113206E+10 | 0.448884E+10 | 0.119222E+10 | 0.329662E+10 | 0.00 | 0.00 |
July | 0.664983E+10 | 0.108414E+10 | 0.507119E+10 | 0.160194E+10 | 0.346924E+10 | 0.00 | 0.00 |
August | 0.689722E+10 | 0.125526E+10 | 0.541830E+10 | 0.226376E+10 | 0.315454E+10 | 0.00 | 0.00 |
September | 0.662101E+10 | 0.188884E+10 | 0.562087E+10 | 0.299330E+10 | 0.262757E+10 | 0.00 | 0.00 |
October | 0.520348E+10 | 0.274330E+10 | 0.496290E+10 | 0.292002E+10 | 0.204288E+10 | 0.00 | 0.00 |
November | 0.399194E+10 | 0.370530E+10 | 0.427907E+10 | 0.268671E+10 | 0.159236E+10 | 0.00 | 0.00 |
December | 0.376971E+10 | 0.590465E+10 | 0.470640E+10 | 0.308724E+10 | 0.161916E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.702386E+11 | 0.371766E+11 | 0.655369E+11 | 0.349942E+11 | 0.305427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.376971E+10 | 0.108414E+10 | 0.427907E+10 | 0.119222E+10 | 0.159236E+10 | 0.00 | 0.00 |
Maximum of Months | 0.689722E+10 | 0.611866E+10 | 0.697141E+10 | 0.471043E+10 | 0.346924E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.577280E+09 | 0.470113E+10 | 0.130637E+10 | 0.546844E+09 | 0.759522E+09 | 0.00 | 0.00 |
February | 0.131782E+10 | 0.337770E+10 | 0.192286E+10 | 0.878187E+09 | 0.104467E+10 | 0.00 | 0.00 |
March | 0.229927E+10 | 0.296469E+10 | 0.280201E+10 | 0.143399E+10 | 0.136802E+10 | 0.00 | 0.00 |
April | 0.341795E+10 | 0.181169E+10 | 0.346404E+10 | 0.175482E+10 | 0.170922E+10 | 0.00 | 0.00 |
May | 0.505786E+10 | 0.111761E+10 | 0.439830E+10 | 0.209856E+10 | 0.229974E+10 | 0.00 | 0.00 |
June | 0.500890E+10 | 0.748958E+09 | 0.410740E+10 | 0.177659E+10 | 0.233081E+10 | 0.00 | 0.00 |
July | 0.570492E+10 | 0.731262E+09 | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.00 | 0.00 |
August | 0.455470E+10 | 0.837566E+09 | 0.372850E+10 | 0.169451E+10 | 0.203399E+10 | 0.00 | 0.00 |
September | 0.306233E+10 | 0.124748E+10 | 0.282000E+10 | 0.126723E+10 | 0.155277E+10 | 0.00 | 0.00 |
October | 0.158417E+10 | 0.186328E+10 | 0.184056E+10 | 0.738915E+09 | 0.110164E+10 | 0.00 | 0.00 |
November | 0.588542E+09 | 0.265793E+10 | 0.108154E+10 | 0.364498E+09 | 0.717039E+09 | 0.00 | 0.00 |
December | 0.325337E+09 | 0.452496E+10 | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.334991E+11 | 0.265843E+11 | 0.329987E+11 | 0.150095E+11 | 0.179892E+11 | 0.00 | 0.00 |
Minimum of Months | 0.325337E+09 | 0.731262E+09 | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.00 | 0.00 |
Maximum of Months | 0.570492E+10 | 0.470113E+10 | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12816537.59 | 0.765230E+10 | 0.884508E+09 | 0.00 | 0.884508E+09 | 0.00 | 0.00 |
February | 0.127400E+09 | 0.544187E+10 | 0.122719E+10 | 0.00 | 0.122719E+10 | 0.00 | 0.00 |
March | 0.348988E+09 | 0.459983E+10 | 0.167161E+10 | 0.00 | 0.167161E+10 | 0.00 | 0.00 |
April | 0.119355E+10 | 0.261252E+10 | 0.212044E+10 | 16303796.26 | 0.210414E+10 | 0.00 | 0.00 |
May | 0.297527E+10 | 0.144006E+10 | 0.308084E+10 | 0.164714E+09 | 0.291613E+10 | 0.00 | 0.00 |
June | 0.382451E+10 | 0.978451E+09 | 0.332685E+10 | 0.364052E+09 | 0.296279E+10 | 0.00 | 0.00 |
July | 0.391214E+10 | 0.977601E+09 | 0.328377E+10 | 0.280295E+09 | 0.300347E+10 | 0.00 | 0.00 |
August | 0.267105E+10 | 0.119057E+10 | 0.249491E+10 | 42383655.14 | 0.245253E+10 | 0.00 | 0.00 |
September | 0.147010E+10 | 0.193696E+10 | 0.188184E+10 | 448877.17 | 0.188139E+10 | 0.00 | 0.00 |
October | 0.523913E+09 | 0.305370E+10 | 0.135021E+10 | 0.00 | 0.135021E+10 | 0.00 | 0.00 |
November | 81056820.37 | 0.442365E+10 | 0.865173E+09 | 0.00 | 0.865173E+09 | 0.00 | 0.00 |
December | 585759.09 | 0.738464E+10 | 0.749426E+09 | 0.00 | 0.749426E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171414E+11 | 0.416921E+11 | 0.229368E+11 | 0.868198E+09 | 0.220686E+11 | 0.00 | 0.00 |
Minimum of Months | 585759.09 | 0.977601E+09 | 0.749426E+09 | 0.00 | 0.749426E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391214E+10 | 0.765230E+10 | 0.332685E+10 | 0.364052E+09 | 0.300347E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.526489E+09 | 0.461793E+10 | 0.129238E+10 | 0.539222E+09 | 0.753161E+09 | 0.00 | 0.00 |
February | 0.114975E+10 | 0.327740E+10 | 0.183469E+10 | 0.782442E+09 | 0.105225E+10 | 0.00 | 0.00 |
March | 0.221089E+10 | 0.284194E+10 | 0.276854E+10 | 0.138894E+10 | 0.137960E+10 | 0.00 | 0.00 |
April | 0.373038E+10 | 0.171305E+10 | 0.371440E+10 | 0.200382E+10 | 0.171058E+10 | 0.00 | 0.00 |
May | 0.471920E+10 | 0.101943E+10 | 0.415400E+10 | 0.182657E+10 | 0.232743E+10 | 0.00 | 0.00 |
June | 0.561341E+10 | 0.701638E+09 | 0.455125E+10 | 0.217773E+10 | 0.237353E+10 | 0.00 | 0.00 |
July | 0.581058E+10 | 0.689784E+09 | 0.460709E+10 | 0.216379E+10 | 0.244331E+10 | 0.00 | 0.00 |
August | 0.429356E+10 | 0.827659E+09 | 0.355184E+10 | 0.155275E+10 | 0.199909E+10 | 0.00 | 0.00 |
September | 0.293339E+10 | 0.127281E+10 | 0.275261E+10 | 0.123229E+10 | 0.152033E+10 | 0.00 | 0.00 |
October | 0.134862E+10 | 0.196732E+10 | 0.172210E+10 | 0.653044E+09 | 0.106905E+10 | 0.00 | 0.00 |
November | 0.529744E+09 | 0.274955E+10 | 0.106065E+10 | 0.354432E+09 | 0.706222E+09 | 0.00 | 0.00 |
December | 0.322265E+09 | 0.451135E+10 | 0.999985E+09 | 0.369388E+09 | 0.630597E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.331883E+11 | 0.261899E+11 | 0.330096E+11 | 0.150444E+11 | 0.179651E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322265E+09 | 0.689784E+09 | 0.999985E+09 | 0.354432E+09 | 0.630597E+09 | 0.00 | 0.00 |
Maximum of Months | 0.581058E+10 | 0.461793E+10 | 0.460709E+10 | 0.217773E+10 | 0.244331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.541229E+10 | 0.605129E+10 | 0.609553E+10 | 0.424200E+10 | 0.185353E+10 | 0.00 | 0.00 |
February | 0.694410E+10 | 0.464671E+10 | 0.697114E+10 | 0.471024E+10 | 0.226090E+10 | 0.00 | 0.00 |
March | 0.694434E+10 | 0.425084E+10 | 0.679726E+10 | 0.430238E+10 | 0.249488E+10 | 0.00 | 0.00 |
April | 0.662187E+10 | 0.275509E+10 | 0.595421E+10 | 0.323009E+10 | 0.272412E+10 | 0.00 | 0.00 |
May | 0.622074E+10 | 0.163926E+10 | 0.516999E+10 | 0.176355E+10 | 0.340644E+10 | 0.00 | 0.00 |
June | 0.574978E+10 | 0.108371E+10 | 0.448869E+10 | 0.119217E+10 | 0.329652E+10 | 0.00 | 0.00 |
July | 0.671905E+10 | 0.108429E+10 | 0.507102E+10 | 0.160188E+10 | 0.346914E+10 | 0.00 | 0.00 |
August | 0.694488E+10 | 0.130404E+10 | 0.541811E+10 | 0.226367E+10 | 0.315445E+10 | 0.00 | 0.00 |
September | 0.665062E+10 | 0.200662E+10 | 0.562066E+10 | 0.299318E+10 | 0.262748E+10 | 0.00 | 0.00 |
October | 0.519180E+10 | 0.298348E+10 | 0.496271E+10 | 0.291990E+10 | 0.204281E+10 | 0.00 | 0.00 |
November | 0.400452E+10 | 0.391622E+10 | 0.427890E+10 | 0.268660E+10 | 0.159231E+10 | 0.00 | 0.00 |
December | 0.383490E+10 | 0.590091E+10 | 0.470621E+10 | 0.308712E+10 | 0.161910E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.712389E+11 | 0.376225E+11 | 0.655344E+11 | 0.349928E+11 | 0.305417E+11 | 0.00 | 0.00 |
Minimum of Months | 0.383490E+10 | 0.108371E+10 | 0.427890E+10 | 0.119217E+10 | 0.159231E+10 | 0.00 | 0.00 |
Maximum of Months | 0.694488E+10 | 0.605129E+10 | 0.697114E+10 | 0.471024E+10 | 0.346914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.588931E+09 | 0.471617E+10 | 0.130635E+10 | 0.546835E+09 | 0.759513E+09 | 0.00 | 0.00 |
February | 0.134192E+10 | 0.340548E+10 | 0.192283E+10 | 0.878173E+09 | 0.104466E+10 | 0.00 | 0.00 |
March | 0.234848E+10 | 0.295986E+10 | 0.280197E+10 | 0.143396E+10 | 0.136801E+10 | 0.00 | 0.00 |
April | 0.348495E+10 | 0.180897E+10 | 0.346400E+10 | 0.175479E+10 | 0.170920E+10 | 0.00 | 0.00 |
May | 0.512750E+10 | 0.110284E+10 | 0.439825E+10 | 0.209853E+10 | 0.229972E+10 | 0.00 | 0.00 |
June | 0.506894E+10 | 0.738013E+09 | 0.410734E+10 | 0.177656E+10 | 0.233078E+10 | 0.00 | 0.00 |
July | 0.574011E+10 | 0.746483E+09 | 0.453094E+10 | 0.210690E+10 | 0.242403E+10 | 0.00 | 0.00 |
August | 0.457263E+10 | 0.876851E+09 | 0.372845E+10 | 0.169448E+10 | 0.203397E+10 | 0.00 | 0.00 |
September | 0.305834E+10 | 0.133283E+10 | 0.281996E+10 | 0.126721E+10 | 0.155275E+10 | 0.00 | 0.00 |
October | 0.155417E+10 | 0.203224E+10 | 0.184053E+10 | 0.738903E+09 | 0.110163E+10 | 0.00 | 0.00 |
November | 0.581274E+09 | 0.280524E+10 | 0.108152E+10 | 0.364492E+09 | 0.717030E+09 | 0.00 | 0.00 |
December | 0.327526E+09 | 0.457780E+10 | 0.996129E+09 | 0.348430E+09 | 0.647699E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.337948E+11 | 0.271028E+11 | 0.329983E+11 | 0.150093E+11 | 0.179890E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327526E+09 | 0.738013E+09 | 0.996129E+09 | 0.348430E+09 | 0.647699E+09 | 0.00 | 0.00 |
Maximum of Months | 0.574011E+10 | 0.471617E+10 | 0.453094E+10 | 0.210690E+10 | 0.242403E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11811011.52 | 0.777690E+10 | 0.884528E+09 | 0.00 | 0.884528E+09 | 0.00 | 0.00 |
February | 0.115982E+09 | 0.555748E+10 | 0.122722E+10 | 0.00 | 0.122722E+10 | 0.00 | 0.00 |
March | 0.301297E+09 | 0.480434E+10 | 0.167165E+10 | 0.00 | 0.167165E+10 | 0.00 | 0.00 |
April | 0.104903E+10 | 0.283305E+10 | 0.212049E+10 | 16304275.49 | 0.210418E+10 | 0.00 | 0.00 |
May | 0.280111E+10 | 0.158353E+10 | 0.308091E+10 | 0.164719E+09 | 0.291619E+10 | 0.00 | 0.00 |
June | 0.370844E+10 | 0.105902E+10 | 0.332692E+10 | 0.364063E+09 | 0.296286E+10 | 0.00 | 0.00 |
July | 0.383891E+10 | 0.102709E+10 | 0.328384E+10 | 0.280304E+09 | 0.300353E+10 | 0.00 | 0.00 |
August | 0.263239E+10 | 0.122081E+10 | 0.249496E+10 | 42384900.95 | 0.245258E+10 | 0.00 | 0.00 |
September | 0.144474E+10 | 0.195072E+10 | 0.188188E+10 | 448890.36 | 0.188143E+10 | 0.00 | 0.00 |
October | 0.513015E+09 | 0.303769E+10 | 0.135024E+10 | 0.00 | 0.135024E+10 | 0.00 | 0.00 |
November | 78570235.73 | 0.439912E+10 | 0.865193E+09 | 0.00 | 0.865193E+09 | 0.00 | 0.00 |
December | 723697.39 | 0.744816E+10 | 0.749443E+09 | 0.00 | 0.749443E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164960E+11 | 0.426979E+11 | 0.229373E+11 | 0.868223E+09 | 0.220690E+11 | 0.00 | 0.00 |
Minimum of Months | 723697.39 | 0.102709E+10 | 0.749443E+09 | 0.00 | 0.749443E+09 | 0.00 | 0.00 |
Maximum of Months | 0.383891E+10 | 0.777690E+10 | 0.332692E+10 | 0.364063E+09 | 0.300353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.515118E+09 | 0.466506E+10 | 0.129240E+10 | 0.539233E+09 | 0.753172E+09 | 0.00 | 0.00 |
February | 0.112270E+10 | 0.332606E+10 | 0.183472E+10 | 0.782458E+09 | 0.105226E+10 | 0.00 | 0.00 |
March | 0.214314E+10 | 0.294357E+10 | 0.276858E+10 | 0.138896E+10 | 0.137962E+10 | 0.00 | 0.00 |
April | 0.363500E+10 | 0.179960E+10 | 0.371446E+10 | 0.200386E+10 | 0.171060E+10 | 0.00 | 0.00 |
May | 0.462921E+10 | 0.107613E+10 | 0.415406E+10 | 0.182660E+10 | 0.232746E+10 | 0.00 | 0.00 |
June | 0.554920E+10 | 0.730605E+09 | 0.455133E+10 | 0.217777E+10 | 0.237356E+10 | 0.00 | 0.00 |
July | 0.576725E+10 | 0.700692E+09 | 0.460717E+10 | 0.216383E+10 | 0.244334E+10 | 0.00 | 0.00 |
August | 0.426642E+10 | 0.821653E+09 | 0.355190E+10 | 0.155278E+10 | 0.199912E+10 | 0.00 | 0.00 |
September | 0.291381E+10 | 0.125402E+10 | 0.275266E+10 | 0.123231E+10 | 0.152035E+10 | 0.00 | 0.00 |
October | 0.133944E+10 | 0.192849E+10 | 0.172212E+10 | 0.653057E+09 | 0.106907E+10 | 0.00 | 0.00 |
November | 0.522672E+09 | 0.271849E+10 | 0.106067E+10 | 0.354439E+09 | 0.706232E+09 | 0.00 | 0.00 |
December | 0.317306E+09 | 0.453148E+10 | 0.100000E+10 | 0.369395E+09 | 0.630606E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327213E+11 | 0.264958E+11 | 0.330101E+11 | 0.150447E+11 | 0.179654E+11 | 0.00 | 0.00 |
Minimum of Months | 0.317306E+09 | 0.700692E+09 | 0.100000E+10 | 0.354439E+09 | 0.630606E+09 | 0.00 | 0.00 |
Maximum of Months | 0.576725E+10 | 0.466506E+10 | 0.460717E+10 | 0.217777E+10 | 0.244334E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.526387E+10 | 0.623462E+10 | 0.609577E+10 | 0.424217E+10 | 0.185360E+10 | 0.00 | 0.00 |
February | 0.678687E+10 | 0.474222E+10 | 0.697141E+10 | 0.471043E+10 | 0.226098E+10 | 0.00 | 0.00 |
March | 0.676333E+10 | 0.440486E+10 | 0.679752E+10 | 0.430256E+10 | 0.249496E+10 | 0.00 | 0.00 |
April | 0.645925E+10 | 0.289709E+10 | 0.595443E+10 | 0.323023E+10 | 0.272420E+10 | 0.00 | 0.00 |
May | 0.607175E+10 | 0.175888E+10 | 0.517017E+10 | 0.176362E+10 | 0.340655E+10 | 0.00 | 0.00 |
June | 0.563382E+10 | 0.116696E+10 | 0.448884E+10 | 0.119222E+10 | 0.329662E+10 | 0.00 | 0.00 |
July | 0.665150E+10 | 0.111341E+10 | 0.507119E+10 | 0.160194E+10 | 0.346924E+10 | 0.00 | 0.00 |
August | 0.689700E+10 | 0.129805E+10 | 0.541830E+10 | 0.226376E+10 | 0.315454E+10 | 0.00 | 0.00 |
September | 0.659970E+10 | 0.197957E+10 | 0.562087E+10 | 0.299330E+10 | 0.262757E+10 | 0.00 | 0.00 |
October | 0.514687E+10 | 0.291972E+10 | 0.496290E+10 | 0.292002E+10 | 0.204288E+10 | 0.00 | 0.00 |
November | 0.394999E+10 | 0.388498E+10 | 0.427907E+10 | 0.268671E+10 | 0.159236E+10 | 0.00 | 0.00 |
December | 0.374226E+10 | 0.603495E+10 | 0.470640E+10 | 0.308724E+10 | 0.161916E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.699662E+11 | 0.384353E+11 | 0.655369E+11 | 0.349942E+11 | 0.305427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.374226E+10 | 0.111341E+10 | 0.427907E+10 | 0.119222E+10 | 0.159236E+10 | 0.00 | 0.00 |
Maximum of Months | 0.689700E+10 | 0.623462E+10 | 0.697141E+10 | 0.471043E+10 | 0.346924E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.573309E+09 | 0.477406E+10 | 0.130637E+10 | 0.546844E+09 | 0.759522E+09 | 0.00 | 0.00 |
February | 0.130851E+10 | 0.345860E+10 | 0.192286E+10 | 0.878187E+09 | 0.104467E+10 | 0.00 | 0.00 |
March | 0.228549E+10 | 0.306066E+10 | 0.280201E+10 | 0.143399E+10 | 0.136802E+10 | 0.00 | 0.00 |
April | 0.339635E+10 | 0.189876E+10 | 0.346404E+10 | 0.175482E+10 | 0.170922E+10 | 0.00 | 0.00 |
May | 0.505111E+10 | 0.115573E+10 | 0.439830E+10 | 0.209856E+10 | 0.229974E+10 | 0.00 | 0.00 |
June | 0.500837E+10 | 0.771907E+09 | 0.410740E+10 | 0.177659E+10 | 0.233081E+10 | 0.00 | 0.00 |
July | 0.570693E+10 | 0.750946E+09 | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.00 | 0.00 |
August | 0.455333E+10 | 0.866072E+09 | 0.372850E+10 | 0.169451E+10 | 0.203399E+10 | 0.00 | 0.00 |
September | 0.304464E+10 | 0.131050E+10 | 0.282000E+10 | 0.126723E+10 | 0.155277E+10 | 0.00 | 0.00 |
October | 0.154998E+10 | 0.198732E+10 | 0.184056E+10 | 0.738915E+09 | 0.110164E+10 | 0.00 | 0.00 |
November | 0.573028E+09 | 0.277919E+10 | 0.108154E+10 | 0.364498E+09 | 0.717039E+09 | 0.00 | 0.00 |
December | 0.320166E+09 | 0.460926E+10 | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333712E+11 | 0.274230E+11 | 0.329987E+11 | 0.150095E+11 | 0.179892E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320166E+09 | 0.750946E+09 | 0.996143E+09 | 0.348436E+09 | 0.647707E+09 | 0.00 | 0.00 |
Maximum of Months | 0.570693E+10 | 0.477406E+10 | 0.453100E+10 | 0.210694E+10 | 0.242406E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.616662E+10 | -0.539380E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -772816952.0 | 58.99 | 0.00 | 0.00 |
February | 0.569749E+10 | -0.501409E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -683397386.7 | 58.98 | 0.00 | 0.00 |
March | 0.665279E+10 | -0.591287E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -739920495.4 | 58.99 | 0.00 | 0.00 |
April | 0.585167E+10 | -0.516035E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -691320248.0 | 58.98 | 0.00 | 0.00 |
May | 0.595413E+10 | -0.525882E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695303916.1 | 58.99 | 0.00 | 0.00 |
June | 0.558351E+10 | -0.491214E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671369684.0 | 58.98 | 0.00 | 0.00 |
July | 0.507342E+10 | -0.438350E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689911738.7 | 58.99 | 0.00 | 0.00 |
August | 0.540197E+10 | -0.470917E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692798006.2 | 58.98 | 0.00 | 0.00 |
September | 0.493246E+10 | -0.426128E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671180261.8 | 58.98 | 0.00 | 0.00 |
October | 0.527944E+10 | -0.457294E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -706500926.9 | 58.98 | 0.00 | 0.00 |
November | 0.547241E+10 | -0.476258E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -709826632.9 | 58.98 | 0.00 | 0.00 |
December | 0.576488E+10 | -0.500037E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -764516512.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.678308E+11 | -0.593419E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.848886E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.493246E+10 | -0.591287E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -772816952.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.665279E+10 | -0.426128E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -671180261.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5062.08 | 35.38 | 234.50 | 236.00 | 4242.82 | 36.49 | 241.50 | 224.17 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 7823.97 | 35.91 | 258.83 | 255.50 | 3425.84 | 31.36 | 236.50 | 241.67 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 11013.23 | 34.93 | 215.50 | 318.17 | 1832.44 | 21.55 | 168.00 | 283.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:49 | 2303.33 | 18.31 | 12.17 | 345.50 | 1429.92 | 20.60 | 156.50 | 311.50 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 2008.91 | 18.86 | 0.83 | 406.50 | 1130.21 | 21.09 | 228.67 | 362.33 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-05:19 | 1909.05 | 18.95 | 0.83 | 406.33 | 1086.87 | 21.19 | 226.67 | 364.17 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2070.69 | 19.23 | 4.67 | 414.33 | 1188.85 | 21.48 | 238.67 | 373.33 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2603.42 | 19.79 | 29.83 | 373.67 | 1387.98 | 21.70 | 217.17 | 335.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 4387.94 | 22.89 | 104.33 | 327.83 | 1429.16 | 21.57 | 207.33 | 294.50 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 5518.58 | 31.60 | 269.50 | 295.00 | 1458.81 | 23.78 | 199.67 | 268.83 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-07:00 | 3997.15 | 33.94 | 244.00 | 238.33 | 3311.82 | 35.29 | 246.83 | 216.17 |
December | 226.33 | 0.49 | 0.48 | 01-DEC-08:20 | 3761.53 | 33.42 | 209.17 | 220.67 | 3132.02 | 34.85 | 216.33 | 201.83 |
Annual Sum or Average | 3785.50 | 0.50 | 4024.36 | 25.55 | 1584.17 | 3837.83 | 1907.64 | 24.94 | 2583.83 | 3477.17 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1909.05 | 18.31 | 0.83 | 220.67 | 1086.87 | 20.60 | 156.50 | 201.83 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 11013.23 | 35.91 | 269.50 | 414.33 | 4242.82 | 36.49 | 246.83 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-08:39 | 1662.88 | 22.83 | 98.83 | 217.00 | 980.44 | 23.58 | 97.17 | 182.33 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2149.30 | 21.27 | 73.83 | 242.50 | 1189.82 | 23.48 | 118.83 | 215.17 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3684.22 | 22.94 | 80.83 | 311.67 | 2283.81 | 25.29 | 106.83 | 271.17 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 3962.19 | 21.89 | 84.33 | 351.83 | 2367.84 | 24.11 | 91.33 | 317.50 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 3618.41 | 21.92 | 135.17 | 416.50 | 1619.42 | 22.23 | 93.33 | 379.33 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 4382.30 | 22.39 | 120.00 | 413.50 | 2071.72 | 23.52 | 88.50 | 379.50 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:40 | 4198.75 | 22.79 | 126.00 | 420.33 | 1956.62 | 23.52 | 100.83 | 388.83 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 3526.29 | 22.46 | 99.67 | 377.83 | 1582.33 | 22.60 | 91.17 | 339.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:10 | 2754.61 | 21.26 | 96.67 | 326.50 | 1476.17 | 22.41 | 100.67 | 289.33 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2034.97 | 21.02 | 96.00 | 281.33 | 914.72 | 21.87 | 73.83 | 238.00 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1337.49 | 20.02 | 76.83 | 220.33 | 751.36 | 22.38 | 79.00 | 177.67 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-08:20 | 1206.88 | 20.81 | 66.33 | 200.17 | 809.03 | 23.14 | 80.50 | 163.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3054.56 | 21.87 | 1154.50 | 3779.50 | 1556.70 | 23.12 | 1122.00 | 3341.17 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1206.88 | 20.02 | 66.33 | 200.17 | 751.36 | 21.87 | 73.83 | 163.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4382.30 | 22.94 | 135.17 | 420.33 | 2367.84 | 25.29 | 118.83 | 388.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.53 | 0.48 | 01-JAN-10:09 | 607.70 | 15.35 | 0.00 | 198.50 | 352.57 | 17.83 | 0.00 | 126.17 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:30 | 769.11 | 16.66 | 0.00 | 232.83 | 461.25 | 19.09 | 0.50 | 184.33 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 833.85 | 17.34 | 0.00 | 303.33 | 532.30 | 19.73 | 9.00 | 240.00 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 948.05 | 17.79 | 0.00 | 350.33 | 601.12 | 20.02 | 35.83 | 309.67 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1291.81 | 20.12 | 30.50 | 428.50 | 752.60 | 23.09 | 195.00 | 406.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1537.84 | 22.35 | 102.67 | 434.67 | 889.87 | 24.42 | 259.33 | 405.83 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1470.01 | 21.90 | 91.67 | 436.00 | 870.75 | 23.99 | 264.67 | 412.33 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1228.65 | 19.07 | 0.33 | 382.83 | 731.71 | 21.25 | 147.83 | 343.83 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 931.37 | 17.81 | 0.00 | 324.00 | 549.23 | 20.01 | 6.17 | 272.17 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 763.68 | 16.60 | 0.00 | 270.17 | 430.30 | 18.83 | 0.00 | 200.33 |
November | 255.50 | 0.54 | 0.48 | 01-NOV-08:50 | 590.56 | 15.15 | 0.00 | 203.83 | 330.71 | 17.41 | 0.00 | 114.00 |
December | 226.33 | 0.53 | 0.48 | 01-DEC-09:20 | 563.52 | 15.06 | 0.00 | 182.83 | 316.30 | 17.42 | 0.00 | 83.17 |
Annual Sum or Average | 3785.50 | 0.50 | 1027.67 | 18.41 | 225.17 | 3747.83 | 606.70 | 20.73 | 918.33 | 3097.83 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 563.52 | 15.06 | 0.00 | 182.83 | 316.30 | 17.41 | 0.00 | 83.17 | |
Maximum of Months | 437.50 | 0.54 | 0.48 | 1537.84 | 22.35 | 102.67 | 436.00 | 889.87 | 24.42 | 264.67 | 412.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-10:09 | 1554.24 | 20.94 | 76.00 | 218.33 | 927.14 | 23.24 | 88.50 | 184.67 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:30 | 2170.53 | 21.49 | 75.17 | 244.83 | 1205.94 | 23.55 | 108.50 | 216.83 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3431.21 | 22.92 | 78.83 | 312.50 | 2004.82 | 23.80 | 86.50 | 270.33 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 4091.75 | 21.42 | 84.50 | 348.83 | 1791.98 | 21.07 | 53.83 | 314.67 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-06:30 | 3294.64 | 19.26 | 81.17 | 416.67 | 1926.46 | 20.97 | 61.33 | 384.17 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 3564.04 | 18.16 | 46.83 | 426.83 | 1579.29 | 19.37 | 5.67 | 389.50 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 3842.08 | 18.63 | 53.67 | 429.33 | 1720.66 | 19.59 | 12.50 | 391.83 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3469.15 | 20.73 | 79.17 | 378.67 | 1970.67 | 22.02 | 75.67 | 339.33 |
September | 344.17 | 0.49 | 0.48 | 01-SEP-06:00 | 2925.59 | 21.54 | 99.83 | 327.00 | 1703.74 | 22.83 | 99.83 | 293.33 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2199.03 | 21.56 | 100.33 | 282.50 | 957.04 | 22.13 | 77.33 | 241.17 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1323.91 | 19.89 | 75.33 | 222.33 | 715.10 | 21.90 | 75.00 | 181.00 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-09:20 | 1231.34 | 20.26 | 64.50 | 205.50 | 649.82 | 21.10 | 57.00 | 160.83 |
Annual Sum or Average | 3785.50 | 0.50 | 2903.11 | 20.38 | 915.33 | 3813.33 | 1496.57 | 21.60 | 801.67 | 3367.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1231.34 | 18.16 | 46.83 | 205.50 | 649.82 | 19.37 | 5.67 | 160.83 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4091.75 | 22.92 | 100.33 | 429.33 | 2004.82 | 23.80 | 108.50 | 391.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 4835.77 | 33.53 | 217.83 | 234.00 | 4114.93 | 36.16 | 233.00 | 222.00 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 7628.86 | 35.62 | 255.83 | 254.50 | 3271.56 | 29.91 | 172.67 | 240.67 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 10824.21 | 34.30 | 215.00 | 317.33 | 1686.98 | 18.80 | 15.00 | 279.83 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:49 | 2170.90 | 14.54 | 0.00 | 343.17 | 1328.28 | 18.19 | 16.67 | 308.33 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 1917.67 | 15.11 | 0.00 | 403.67 | 1067.42 | 18.63 | 7.17 | 359.50 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:30 | 1825.66 | 15.35 | 0.00 | 405.17 | 1031.38 | 18.87 | 10.50 | 360.17 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 1976.92 | 15.64 | 0.00 | 411.67 | 1125.17 | 19.18 | 23.17 | 369.67 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2483.80 | 16.14 | 8.00 | 371.67 | 1303.49 | 19.23 | 30.17 | 332.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 4255.68 | 20.03 | 90.33 | 326.50 | 1331.51 | 18.85 | 19.00 | 291.67 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 5390.73 | 30.92 | 261.17 | 293.00 | 1364.64 | 21.30 | 69.83 | 266.33 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-08:09 | 3853.19 | 32.50 | 232.17 | 235.50 | 3219.27 | 35.03 | 245.33 | 214.83 |
December | 226.33 | 0.49 | 0.48 | 01-DEC-08:20 | 3620.50 | 32.69 | 204.33 | 219.50 | 3029.79 | 34.45 | 211.00 | 200.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3892.12 | 23.08 | 1484.67 | 3815.67 | 1814.30 | 22.95 | 1053.50 | 3445.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1825.66 | 14.54 | 0.00 | 219.50 | 1031.38 | 18.19 | 7.17 | 200.00 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 10824.21 | 35.62 | 261.17 | 411.67 | 4114.93 | 36.16 | 245.33 | 369.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-08:39 | 1616.85 | 22.39 | 98.17 | 214.50 | 945.53 | 23.36 | 89.33 | 178.83 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2083.03 | 20.78 | 73.67 | 240.83 | 1137.49 | 23.26 | 108.67 | 212.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3591.78 | 22.46 | 80.83 | 310.17 | 2209.24 | 25.09 | 99.33 | 268.00 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 3856.75 | 21.43 | 84.33 | 351.17 | 2281.92 | 23.93 | 81.50 | 314.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 3530.64 | 21.48 | 134.50 | 412.83 | 1550.26 | 22.05 | 84.33 | 377.50 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 4277.26 | 21.93 | 120.00 | 412.33 | 1990.67 | 23.35 | 84.83 | 376.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:49 | 4088.41 | 22.26 | 125.00 | 417.83 | 1863.29 | 22.74 | 76.67 | 386.33 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3385.99 | 21.05 | 88.67 | 375.17 | 1510.03 | 22.40 | 80.67 | 335.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2679.52 | 20.79 | 96.50 | 324.67 | 1417.38 | 22.18 | 83.33 | 285.50 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 1981.27 | 20.55 | 95.50 | 278.67 | 855.13 | 21.03 | 59.67 | 233.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1297.20 | 19.52 | 76.50 | 217.67 | 721.34 | 22.15 | 73.50 | 173.00 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-08:20 | 1164.21 | 20.02 | 63.33 | 197.83 | 780.52 | 22.90 | 78.17 | 159.67 |
Annual Sum or Average | 3785.50 | 0.50 | 2969.86 | 21.29 | 1137.00 | 3753.67 | 1491.85 | 22.80 | 1000.00 | 3301.17 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1164.21 | 19.52 | 63.33 | 197.83 | 721.34 | 21.03 | 59.67 | 159.67 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4277.26 | 22.46 | 134.50 | 417.83 | 2281.92 | 25.09 | 108.67 | 386.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.53 | 0.48 | 01-JAN-10:20 | 584.52 | 11.49 | 0.00 | 195.00 | 339.62 | 15.25 | 0.00 | 115.00 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 740.30 | 13.04 | 0.00 | 229.67 | 445.54 | 16.72 | 0.00 | 179.50 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 804.00 | 14.05 | 0.00 | 300.83 | 516.87 | 17.72 | 0.00 | 232.33 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 916.16 | 14.61 | 0.00 | 349.17 | 584.80 | 18.21 | 0.83 | 302.33 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1246.99 | 16.88 | 30.00 | 427.17 | 727.07 | 21.18 | 70.00 | 404.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1484.52 | 19.55 | 76.83 | 433.00 | 859.12 | 22.66 | 123.67 | 402.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1407.79 | 17.80 | 38.33 | 433.67 | 841.50 | 22.25 | 118.67 | 409.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1185.00 | 15.71 | 0.00 | 381.17 | 707.78 | 19.25 | 26.00 | 337.50 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 898.52 | 14.34 | 0.00 | 321.83 | 531.26 | 17.84 | 0.00 | 267.33 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 736.50 | 12.80 | 0.00 | 266.17 | 414.95 | 16.35 | 0.00 | 191.67 |
November | 255.50 | 0.54 | 0.48 | 01-NOV-08:50 | 568.79 | 11.16 | 0.00 | 199.50 | 318.31 | 14.74 | 0.00 | 103.67 |
December | 226.33 | 0.54 | 0.48 | 01-DEC-09:30 | 542.30 | 11.04 | 0.00 | 180.17 | 304.21 | 14.73 | 0.00 | 70.33 |
Annual Sum or Average | 3785.50 | 0.51 | 990.16 | 14.88 | 145.17 | 3717.33 | 586.44 | 18.61 | 339.17 | 3015.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 542.30 | 11.04 | 0.00 | 180.17 | 304.21 | 14.73 | 0.00 | 70.33 | |
Maximum of Months | 437.50 | 0.54 | 0.48 | 1484.52 | 19.55 | 76.83 | 433.67 | 859.12 | 22.66 | 123.67 | 409.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-10:09 | 1507.07 | 20.55 | 75.67 | 216.67 | 889.55 | 23.12 | 86.00 | 182.00 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:30 | 2102.52 | 21.09 | 75.00 | 243.67 | 1106.15 | 22.23 | 95.00 | 213.50 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3344.60 | 22.51 | 78.83 | 311.17 | 1934.42 | 23.68 | 84.33 | 265.83 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 3872.76 | 20.98 | 84.50 | 346.17 | 1716.99 | 20.92 | 51.50 | 311.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3203.23 | 18.79 | 80.67 | 414.00 | 1853.97 | 20.82 | 57.00 | 381.17 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 3469.16 | 17.66 | 46.67 | 425.17 | 1507.09 | 19.18 | 2.50 | 385.83 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 3739.69 | 18.13 | 53.67 | 426.67 | 1641.34 | 19.42 | 7.67 | 388.17 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3368.27 | 20.28 | 79.17 | 377.33 | 1872.98 | 21.88 | 70.00 | 334.83 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-07:10 | 2847.16 | 21.12 | 99.33 | 325.33 | 1600.11 | 22.59 | 93.00 | 290.17 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:30 | 2141.34 | 21.16 | 99.83 | 279.33 | 892.36 | 21.20 | 65.83 | 236.00 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1283.29 | 19.48 | 75.33 | 219.83 | 685.05 | 21.78 | 74.17 | 176.83 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-09:20 | 1193.69 | 19.87 | 64.00 | 204.00 | 622.00 | 20.99 | 56.83 | 155.83 |
Annual Sum or Average | 3785.50 | 0.50 | 2814.57 | 19.94 | 912.67 | 3789.33 | 1424.62 | 21.31 | 743.83 | 3322.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1193.69 | 17.66 | 46.67 | 204.00 | 622.00 | 19.18 | 2.50 | 155.83 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 3872.76 | 22.51 | 99.83 | 426.67 | 1934.42 | 23.68 | 95.00 | 388.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 4835.76 | 33.53 | 217.83 | 234.00 | 4114.84 | 36.16 | 233.00 | 222.00 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 7628.82 | 35.62 | 255.83 | 254.50 | 3271.44 | 29.91 | 172.67 | 240.67 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 10824.13 | 34.30 | 215.00 | 317.33 | 1686.87 | 18.80 | 15.00 | 279.83 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:49 | 2170.80 | 14.54 | 0.00 | 343.17 | 1328.20 | 18.19 | 16.67 | 308.33 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 1917.55 | 15.11 | 0.00 | 403.67 | 1067.34 | 18.63 | 7.17 | 359.50 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:30 | 1825.56 | 15.36 | 0.00 | 405.17 | 1031.30 | 18.87 | 10.50 | 360.17 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 1976.81 | 15.64 | 0.00 | 411.67 | 1125.09 | 19.18 | 23.33 | 369.67 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2483.66 | 16.14 | 8.00 | 371.67 | 1303.38 | 19.23 | 30.17 | 332.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 4255.55 | 20.04 | 90.33 | 326.50 | 1331.40 | 18.85 | 19.00 | 291.67 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 5390.66 | 30.92 | 261.17 | 293.00 | 1364.54 | 21.30 | 69.83 | 266.33 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-08:09 | 3853.17 | 32.50 | 232.17 | 235.50 | 3219.19 | 35.03 | 245.33 | 214.83 |
December | 226.33 | 0.49 | 0.48 | 01-DEC-08:20 | 3620.49 | 32.69 | 204.33 | 219.50 | 3029.72 | 34.45 | 211.00 | 200.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3892.04 | 23.08 | 1484.67 | 3815.67 | 1814.21 | 22.95 | 1053.67 | 3445.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1825.56 | 14.54 | 0.00 | 219.50 | 1031.30 | 18.19 | 7.17 | 200.00 | |
Maximum of Months | 437.50 | 0.51 | 0.48 | 10824.13 | 35.62 | 261.17 | 411.67 | 4114.84 | 36.16 | 245.33 | 369.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-08:39 | 1616.82 | 22.39 | 98.17 | 214.50 | 945.49 | 23.36 | 89.33 | 178.83 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 2083.00 | 20.78 | 73.67 | 240.83 | 1137.43 | 23.26 | 108.67 | 212.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3591.75 | 22.46 | 80.83 | 310.17 | 2209.18 | 25.10 | 99.33 | 268.00 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 3856.72 | 21.43 | 84.33 | 351.17 | 2281.86 | 23.93 | 81.50 | 314.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 3530.57 | 21.48 | 134.50 | 412.83 | 1550.18 | 22.05 | 84.33 | 377.50 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 4277.20 | 21.94 | 120.00 | 412.33 | 1990.59 | 23.35 | 84.83 | 376.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:49 | 4088.35 | 22.27 | 125.00 | 417.83 | 1863.20 | 22.74 | 76.67 | 386.33 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3385.93 | 21.05 | 88.67 | 375.17 | 1509.94 | 22.41 | 80.67 | 335.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 2679.47 | 20.79 | 96.50 | 324.67 | 1417.31 | 22.18 | 83.33 | 285.50 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 1981.22 | 20.55 | 95.50 | 278.67 | 855.07 | 21.03 | 59.67 | 233.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1297.16 | 19.52 | 76.50 | 217.67 | 721.29 | 22.15 | 73.50 | 173.00 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-08:20 | 1164.18 | 20.02 | 63.33 | 197.83 | 780.48 | 22.90 | 78.17 | 159.67 |
Annual Sum or Average | 3785.50 | 0.50 | 2969.81 | 21.29 | 1137.00 | 3753.67 | 1491.79 | 22.80 | 1000.00 | 3301.17 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1164.18 | 19.52 | 63.33 | 197.83 | 721.29 | 21.03 | 59.67 | 159.67 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4277.20 | 22.46 | 134.50 | 417.83 | 2281.86 | 25.10 | 108.67 | 386.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.53 | 0.48 | 01-JAN-10:20 | 584.50 | 11.49 | 0.00 | 195.00 | 339.59 | 15.25 | 0.00 | 115.00 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 740.28 | 13.04 | 0.00 | 229.67 | 445.51 | 16.72 | 0.00 | 179.50 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 803.99 | 14.05 | 0.00 | 300.83 | 516.84 | 17.72 | 0.00 | 232.33 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 916.15 | 14.62 | 0.00 | 349.17 | 584.77 | 18.21 | 0.83 | 302.33 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1246.95 | 16.88 | 30.00 | 427.17 | 727.02 | 21.18 | 70.00 | 404.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1484.47 | 19.56 | 76.83 | 433.00 | 859.07 | 22.66 | 123.67 | 402.00 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1407.75 | 17.80 | 38.33 | 433.67 | 841.45 | 22.25 | 118.67 | 409.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1184.96 | 15.71 | 0.00 | 381.17 | 707.73 | 19.26 | 26.00 | 337.50 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 898.48 | 14.34 | 0.00 | 321.83 | 531.22 | 17.84 | 0.00 | 267.33 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 736.47 | 12.81 | 0.00 | 266.00 | 414.92 | 16.35 | 0.00 | 191.67 |
November | 255.50 | 0.54 | 0.48 | 01-NOV-08:50 | 568.76 | 11.16 | 0.00 | 199.50 | 318.29 | 14.74 | 0.00 | 103.67 |
December | 226.33 | 0.54 | 0.48 | 01-DEC-09:30 | 542.28 | 11.04 | 0.00 | 180.17 | 304.19 | 14.73 | 0.00 | 70.33 |
Annual Sum or Average | 3785.50 | 0.51 | 990.12 | 14.88 | 145.17 | 3717.17 | 586.40 | 18.61 | 339.17 | 3015.33 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 542.28 | 11.04 | 0.00 | 180.17 | 304.19 | 14.73 | 0.00 | 70.33 | |
Maximum of Months | 437.50 | 0.54 | 0.48 | 1484.47 | 19.56 | 76.83 | 433.67 | 859.07 | 22.66 | 123.67 | 409.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.51 | 0.48 | 01-JAN-10:09 | 1507.05 | 20.55 | 75.67 | 216.67 | 889.50 | 23.12 | 86.00 | 182.00 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:30 | 2102.49 | 21.09 | 75.00 | 243.67 | 1106.10 | 22.23 | 95.00 | 213.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3344.58 | 22.51 | 78.83 | 311.17 | 1934.37 | 23.68 | 84.33 | 265.83 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 3872.72 | 20.98 | 84.50 | 346.17 | 1716.92 | 20.92 | 51.50 | 311.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3203.16 | 18.80 | 80.67 | 414.00 | 1853.89 | 20.82 | 57.00 | 381.17 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 3469.09 | 17.66 | 46.67 | 425.17 | 1507.00 | 19.18 | 2.67 | 385.83 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 3739.62 | 18.13 | 53.67 | 426.67 | 1641.26 | 19.42 | 7.67 | 388.17 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3368.21 | 20.28 | 79.17 | 377.33 | 1872.89 | 21.88 | 70.00 | 334.83 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-07:10 | 2847.11 | 21.12 | 99.33 | 325.33 | 1600.04 | 22.59 | 93.00 | 290.17 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:30 | 2141.29 | 21.16 | 99.83 | 279.33 | 892.30 | 21.21 | 65.83 | 235.83 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1283.26 | 19.48 | 75.33 | 219.83 | 685.01 | 21.79 | 74.17 | 176.83 |
December | 226.33 | 0.51 | 0.48 | 01-DEC-09:20 | 1193.66 | 19.87 | 64.17 | 204.00 | 621.96 | 20.99 | 56.83 | 155.83 |
Annual Sum or Average | 3785.50 | 0.50 | 2814.52 | 19.94 | 912.83 | 3789.33 | 1424.55 | 21.31 | 744.00 | 3321.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1193.66 | 17.66 | 46.67 | 204.00 | 621.96 | 19.18 | 2.67 | 155.83 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 3872.72 | 22.51 | 99.83 | 426.67 | 1934.37 | 23.68 | 95.00 | 388.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213033E+10 | 20401.35 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193449E+09 | 20401.35 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65730036.32 | 20401.35 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62490037.01 | 20401.35 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.856275E+09 | 20401.35 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213033E+10 | 20401.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120136E+11 | 13215.74 | 06-JAN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772774E+10 | 12708.72 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.733057E+10 | 11998.26 | 07-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.291603E+10 | 11996.14 | 24-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.846555E+09 | 12002.03 | 12-MAY-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160097E+09 | 11096.29 | 02-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20445940.95 | 8626.81 | 10-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69211110.18 | 9969.43 | 18-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.714603E+09 | 12171.21 | 06-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229328E+10 | 12012.77 | 03-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.500908E+10 | 12040.77 | 21-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108575E+11 | 12053.08 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20445940.95 | 8626.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120136E+11 | 13215.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.547041E+10 | 9768.97 | 09-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304020E+10 | 9672.34 | 25-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215550E+10 | 9370.94 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350049E+09 | 9337.05 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 442989.85 | 3691.58 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79789960.22 | 9301.83 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125210E+10 | 9387.49 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.442497E+10 | 9400.74 | 29-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.547041E+10 | 9768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.896425E+10 | 7999.36 | 06-JAN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.589932E+10 | 7692.94 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.485139E+10 | 7262.59 | 07-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126469E+10 | 7243.32 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37069189.28 | 7220.20 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180775E+09 | 7237.47 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227679E+10 | 7286.50 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723419E+10 | 7293.30 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.896425E+10 | 7999.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561743E+10 | 10379.40 | 09-JAN-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317061E+10 | 10347.33 | 25-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230110E+10 | 10048.81 | 08-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466494E+09 | 9988.67 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13130245.64 | 9964.23 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90439929.62 | 9950.99 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127658E+10 | 10002.72 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453739E+10 | 10035.72 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561743E+10 | 10379.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.568718E+10 | 24762.37 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246794E+10 | 24762.37 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.992193E+09 | 24762.37 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72300102.83 | 24762.37 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21425032.29 | 24762.37 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136064E+10 | 24762.37 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457977E+10 | 24762.37 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.568718E+10 | 24762.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.513728E+10 | 14138.72 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253333E+10 | 14200.89 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157866E+10 | 14155.90 | 08-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.259910E+09 | 14072.55 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3875772.65 | 14020.84 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191745E+09 | 14059.88 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162293E+10 | 14191.99 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489429E+10 | 14164.88 | 26-DEC-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.513728E+10 | 14200.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.472819E+10 | 10733.39 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234999E+10 | 10733.39 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125428E+10 | 10733.39 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144287E+09 | 10733.39 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153906E+09 | 10733.39 | 06-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135717E+10 | 10733.39 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427997E+10 | 10733.39 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.472819E+10 | 10733.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.813359E+10 | 9190.82 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.471956E+10 | 8750.25 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275420E+10 | 8173.00 | 27-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.410740E+09 | 8154.71 | 10-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2931593.24 | 8023.47 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.286255E+09 | 8147.46 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241334E+10 | 8166.55 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718166E+10 | 8175.18 | 06-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.813359E+10 | 9190.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.495616E+10 | 10820.40 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262506E+10 | 10820.40 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144790E+10 | 10820.40 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211362E+09 | 10820.40 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3047447.53 | 10820.40 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174206E+09 | 10820.40 | 06-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143821E+10 | 10820.40 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446256E+10 | 10820.40 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495616E+10 | 10820.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120768E+11 | 29855.83 | 19-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.702329E+10 | 29838.92 | 22-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391971E+10 | 29873.21 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.647431E+09 | 29861.55 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10770919.52 | 29389.84 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.636362E+09 | 29793.30 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454318E+10 | 29888.92 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106681E+11 | 29884.26 | 06-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120768E+11 | 29888.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.796426E+10 | 15170.05 | 21-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.455359E+10 | 15211.07 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300764E+10 | 15196.76 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.721521E+09 | 15185.64 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22869892.80 | 15012.46 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7230137.45 | 3406.30 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.672117E+09 | 15190.77 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313125E+10 | 15231.26 | 09-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.780914E+10 | 15190.02 | 06-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.796426E+10 | 15231.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694603E+10 | 11693.18 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398259E+10 | 11671.78 | 21-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229459E+10 | 11737.03 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.401672E+09 | 11656.35 | 27-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1817074.72 | 8787.41 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4250174.41 | 2630.67 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506738E+09 | 11709.89 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256409E+10 | 11716.69 | 06-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.651348E+10 | 11701.64 | 05-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.694603E+10 | 11737.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113689E+11 | 10496.78 | 06-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729957E+10 | 9761.78 | 25-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.461704E+10 | 9398.48 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101164E+10 | 9388.99 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23349315.28 | 9306.54 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11108557.43 | 4632.37 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.938319E+09 | 9409.80 | 16-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.435822E+10 | 9421.05 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104816E+11 | 9402.75 | 06-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.401097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113689E+11 | 10496.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.713208E+10 | 12736.73 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426924E+10 | 12712.93 | 14-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255794E+10 | 12711.76 | 13-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555668E+09 | 12693.98 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15954449.44 | 12629.72 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6570866.66 | 2122.61 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.553830E+09 | 12754.97 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265003E+10 | 12717.78 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.664576E+10 | 12724.97 | 13-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.713208E+10 | 12754.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137110E+11 | 47904.80 | 05-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.487049E+10 | 47904.80 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.721152E+09 | 39125.58 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34760193.07 | 5883.00 | 20-APR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21278005.01 | 5295.54 | 13-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1506973.07 | 1862.28 | 03-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1182535.64 | 671.03 | 18-AUG-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36968542.28 | 5229.52 | 14-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34965215.87 | 2757.18 | 05-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279423E+09 | 4227.00 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.777282E+10 | 47904.80 | 20-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137110E+11 | 47904.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129752E+11 | 48284.07 | 05-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.487326E+10 | 48284.07 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928481E+09 | 34489.13 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32798421.47 | 5589.00 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21484070.36 | 5383.50 | 13-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1742889.93 | 1208.86 | 02-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 266757.34 | 968.11 | 25-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17771598.58 | 5118.77 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25471849.22 | 4633.45 | 06-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482544E+09 | 5398.83 | 25-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.775810E+10 | 45809.25 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129752E+11 | 48284.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165764E+11 | 47412.77 | 04-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.692625E+10 | 47412.77 | 14-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189449E+10 | 38867.06 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128229E+09 | 6261.35 | 05-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21828211.33 | 6335.19 | 13-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 428486.43 | 568.56 | 17-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 249843.12 | 416.41 | 19-AUG-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21889934.01 | 5938.96 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54116457.18 | 4461.90 | 30-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106044E+10 | 8661.79 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111525E+11 | 47412.77 | 02-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165764E+11 | 47412.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3744183.92 | 3661567.74 | 6618.59 | 20-JAN-07:01 | 6618.59 | 0.00 |
February | 0.00 | 0.00 | 5850109.38 | 5646416.24 | 6258.22 | 22-FEB-07:01 | 6258.22 | 0.00 |
March | 0.00 | 0.00 | 14136669.31 | 13293431.21 | 4597.43 | 13-MAR-06:01 | 4597.43 | 0.00 |
April | 0.00 | 0.00 | 0.925297E+09 | 0.883459E+09 | 22858.70 | 23-APR-17:11 | 22858.70 | 0.00 |
May | 0.00 | 0.00 | 0.133504E+11 | 0.123583E+11 | 48855.48 | 25-MAY-15:40 | 43323.60 | 0.00 |
June | 0.00 | 0.00 | 0.312794E+11 | 0.241902E+11 | 93058.66 | 29-JUN-06:03 | 45679.01 | 0.00 |
July | 0.00 | 0.00 | 0.441895E+11 | 0.329476E+11 | 103268.25 | 05-JUL-10:20 | 37499.30 | 0.00 |
August | 0.00 | 0.00 | 0.354525E+11 | 0.253001E+11 | 83520.06 | 31-AUG-12:50 | 37904.14 | 0.00 |
September | 0.00 | 0.00 | 0.850607E+10 | 0.717520E+10 | 57123.05 | 01-SEP-13:10 | 43562.24 | 0.00 |
October | 0.00 | 0.00 | 0.123219E+10 | 0.116152E+10 | 22860.15 | 19-OCT-15:10 | 22860.15 | 0.00 |
November | 0.00 | 0.00 | 0.139580E+09 | 95883258.67 | 7135.39 | 01-NOV-15:10 | 4833.13 | 0.00 |
December | 0.00 | 0.00 | 5002238.48 | 4815562.92 | 6152.12 | 05-DEC-07:01 | 6152.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135104E+12 | 0.104140E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 3744183.92 | 3661567.74 | 4597.43 | 4597.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.441895E+11 | 0.329476E+11 | 103268.25 | 45679.01 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1932583.20 | 1922370.11 | 5898.95 | 19-JAN-07:01 | 5898.95 | 0.00 |
February | 0.00 | 0.00 | 6616604.09 | 6545198.74 | 7736.73 | 09-FEB-07:01 | 7736.73 | 0.00 |
March | 0.00 | 0.00 | 16756157.06 | 16255292.28 | 8261.65 | 27-MAR-06:01 | 8261.65 | 0.00 |
April | 0.00 | 0.00 | 0.158032E+10 | 0.153684E+10 | 39640.52 | 23-APR-16:01 | 39640.52 | 0.00 |
May | 0.00 | 0.00 | 0.147477E+11 | 0.138144E+11 | 56903.46 | 25-MAY-14:05 | 49854.85 | 0.00 |
June | 0.00 | 0.00 | 0.334172E+11 | 0.262515E+11 | 95141.12 | 29-JUN-06:03 | 48135.65 | 0.00 |
July | 0.00 | 0.00 | 0.446761E+11 | 0.333407E+11 | 100977.63 | 05-JUL-10:30 | 36195.36 | 0.00 |
August | 0.00 | 0.00 | 0.333733E+11 | 0.240636E+11 | 82336.75 | 08-AUG-10:05 | 44822.65 | 0.00 |
September | 0.00 | 0.00 | 0.752252E+10 | 0.627652E+10 | 59546.81 | 01-SEP-12:05 | 41529.10 | 0.00 |
October | 0.00 | 0.00 | 0.999830E+09 | 0.938060E+09 | 22169.00 | 19-OCT-15:00 | 22169.00 | 0.00 |
November | 0.00 | 0.00 | 0.124708E+09 | 84580346.98 | 7619.02 | 22-NOV-07:01 | 7619.02 | 0.00 |
December | 0.00 | 0.00 | 5240510.60 | 5202969.82 | 6449.38 | 06-DEC-07:01 | 6449.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136472E+12 | 0.106336E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1932583.20 | 1922370.11 | 5898.95 | 5898.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.446761E+11 | 0.333407E+11 | 100977.63 | 49854.85 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 357983.24 | 357983.24 | 1574.71 | 19-JAN-07:01 | 1574.71 | 0.00 |
February | 0.00 | 0.00 | 4729583.22 | 4430885.91 | 1831.35 | 09-FEB-07:01 | 1831.35 | 0.00 |
March | 0.00 | 0.00 | 46434034.30 | 45536706.02 | 4885.94 | 29-MAR-06:01 | 4885.94 | 0.00 |
April | 0.00 | 0.00 | 0.180037E+10 | 0.173003E+10 | 38086.33 | 23-APR-16:12 | 38086.33 | 0.00 |
May | 0.00 | 0.00 | 0.158851E+11 | 0.148501E+11 | 62459.04 | 25-MAY-15:00 | 56660.13 | 0.00 |
June | 0.00 | 0.00 | 0.352754E+11 | 0.277933E+11 | 93325.58 | 29-JUN-06:03 | 45591.90 | 0.00 |
July | 0.00 | 0.00 | 0.470106E+11 | 0.352359E+11 | 111221.16 | 05-JUL-10:30 | 39935.24 | 0.00 |
August | 0.00 | 0.00 | 0.342867E+11 | 0.246382E+11 | 88892.85 | 29-AUG-15:50 | 52147.23 | 0.00 |
September | 0.00 | 0.00 | 0.720917E+10 | 0.591937E+10 | 65190.65 | 01-SEP-14:00 | 53363.49 | 0.00 |
October | 0.00 | 0.00 | 0.938360E+09 | 0.866208E+09 | 21627.03 | 19-OCT-15:00 | 21627.03 | 0.00 |
November | 0.00 | 0.00 | 0.130180E+09 | 86394747.75 | 6576.64 | 01-NOV-15:00 | 4241.08 | 0.00 |
December | 0.00 | 0.00 | 778819.97 | 774745.30 | 2731.05 | 06-DEC-07:01 | 2731.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142588E+12 | 0.111171E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 357983.24 | 357983.24 | 1574.71 | 1574.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.470106E+11 | 0.352359E+11 | 111221.16 | 56660.13 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2165.78 | 7682.01 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 2224.61 | 7754.43 | 27-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2363.07 | 7749.90 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2142.90 | 7589.46 | 03-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2117.77 | 7284.11 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2050.50 | 6883.17 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1788.35 | 6455.04 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1914.53 | 6227.73 | 03-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1796.74 | 6277.00 | 27-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1860.15 | 6597.28 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1990.77 | 6992.74 | 28-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2017.64 | 7388.88 | 29-DEC-12:09 |
Annual Sum or Average | 0.00 | 2034.97 | ||||
Minimum of Months | 0.00 | 0.00 | 1788.35 | 6227.73 | ||
Maximum of Months | 0.00 | 0.00 | 2363.07 | 7754.43 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162035E+10 | 0.38 | 2565.79 | 02-JAN-05:01 | 0.86 |
February | 0.121404E+10 | 0.35 | 2565.79 | 01-FEB-07:01 | 0.86 |
March | 0.129702E+10 | 0.35 | 2565.79 | 06-MAR-07:01 | 0.86 |
April | 0.128212E+10 | 0.32 | 2162.31 | 21-APR-07:02 | 0.78 |
May | 0.234431E+10 | 0.38 | 5901.06 | 18-MAY-15:10 | 1.38 |
June | 0.344326E+10 | 0.47 | 8252.36 | 30-JUN-15:10 | 1.70 |
July | 0.466119E+10 | 0.52 | 10301.51 | 05-JUL-10:20 | 1.95 |
August | 0.413154E+10 | 0.51 | 8379.48 | 08-AUG-16:00 | 1.72 |
September | 0.255601E+10 | 0.40 | 7704.89 | 05-SEP-15:50 | 1.64 |
October | 0.142605E+10 | 0.32 | 3221.46 | 20-OCT-15:10 | 0.97 |
November | 0.108525E+10 | 0.31 | 2565.79 | 27-NOV-07:01 | 0.86 |
December | 0.147915E+10 | 0.37 | 2565.79 | 04-DEC-07:01 | 0.86 |
Annual Sum or Average | 0.265403E+11 | 0.39 | |||
Minimum of Months | 0.108525E+10 | 0.31 | 2162.31 | 0.78 | |
Maximum of Months | 0.466119E+10 | 0.52 | 10301.51 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152768E+10 | 0.40 | 2802.84 | 02-JAN-05:01 | 0.92 |
February | 0.116958E+10 | 0.36 | 2802.84 | 01-FEB-06:01 | 0.92 |
March | 0.124195E+10 | 0.34 | 2802.84 | 01-MAR-07:01 | 0.91 |
April | 0.138903E+10 | 0.33 | 3291.96 | 21-APR-15:30 | 1.00 |
May | 0.283938E+10 | 0.43 | 7935.87 | 18-MAY-14:20 | 1.69 |
June | 0.404652E+10 | 0.52 | 9977.16 | 29-JUN-06:03 | 1.96 |
July | 0.483250E+10 | 0.55 | 9977.16 | 05-JUL-06:03 | 1.96 |
August | 0.380929E+10 | 0.50 | 8738.58 | 08-AUG-15:00 | 1.80 |
September | 0.217276E+10 | 0.39 | 7987.28 | 01-SEP-15:40 | 1.70 |
October | 0.124370E+10 | 0.32 | 3323.42 | 20-OCT-14:40 | 1.01 |
November | 0.106941E+10 | 0.31 | 2802.84 | 06-NOV-06:01 | 0.91 |
December | 0.146476E+10 | 0.40 | 2802.84 | 01-DEC-07:01 | 0.92 |
Annual Sum or Average | 0.268066E+11 | 0.40 | |||
Minimum of Months | 0.106941E+10 | 0.31 | 2802.84 | 0.91 | |
Maximum of Months | 0.483250E+10 | 0.55 | 9977.16 | 1.96 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.200238E+10 | 0.49 | 2657.20 | 05-JAN-07:02 | 0.83 |
February | 0.157272E+10 | 0.45 | 2657.20 | 13-FEB-07:01 | 0.83 |
March | 0.147054E+10 | 0.40 | 2657.20 | 03-MAR-07:01 | 0.83 |
April | 0.140664E+10 | 0.34 | 3020.10 | 13-APR-15:20 | 0.89 |
May | 0.268377E+10 | 0.41 | 7901.47 | 18-MAY-14:50 | 1.56 |
June | 0.385123E+10 | 0.49 | 10399.32 | 30-JUN-14:40 | 1.86 |
July | 0.447817E+10 | 0.50 | 11174.80 | 05-JUL-10:30 | 1.94 |
August | 0.340520E+10 | 0.46 | 8815.58 | 08-AUG-15:00 | 1.67 |
September | 0.190177E+10 | 0.37 | 8187.93 | 01-SEP-15:40 | 1.60 |
October | 0.127176E+10 | 0.34 | 2677.06 | 20-OCT-14:30 | 0.83 |
November | 0.138974E+10 | 0.39 | 2657.20 | 09-NOV-06:01 | 0.83 |
December | 0.187536E+10 | 0.47 | 2657.20 | 01-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.273093E+11 | 0.42 | |||
Minimum of Months | 0.127176E+10 | 0.34 | 2657.20 | 0.83 | |
Maximum of Months | 0.447817E+10 | 0.50 | 11174.80 | 1.94 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 57.28 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.24 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.06 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 54.79 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:02 | 2.06 | 2.06 | 56.11 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 55.39 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.49 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 55.91 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 55.96 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 56.67 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 56.22 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 55.76 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 54.79 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.28 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.24 | 57.24 | 2165.78 | 7682.01 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 55.82 | 55.82 | 2224.61 | 7754.43 | 27-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.60 | 56.60 | 2363.07 | 7749.90 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.85 | 55.85 | 2142.90 | 7589.46 | 03-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.41 | 57.41 | 2117.77 | 7284.11 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.02 | 57.02 | 2050.50 | 6883.17 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.09 | 57.09 | 1788.35 | 6455.04 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.11 | 57.11 | 1914.53 | 6227.73 | 03-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.46 | 56.46 | 1796.74 | 6277.00 | 27-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.95 | 55.95 | 1860.15 | 6597.28 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.01 | 57.01 | 1990.77 | 6992.74 | 28-NOV-12:08 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.27 | 56.27 | 2017.64 | 7388.88 | 29-DEC-12:09 |
Annual Sum or Average | 0.00 | 2034.97 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.82 | 55.82 | 1788.35 | 6227.73 | ||
Maximum of Months | 0.00 | 0.00 | 57.41 | 57.41 | 2363.07 | 7754.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.358174E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.212470E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180053E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.652411E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.643837E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.110154E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.148818E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.123858E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.532345E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.438443E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.109998E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.293908E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176414E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.438443E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.358174E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.301706E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158673E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.927378E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.289492E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.634150E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.119039E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.151328E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.115326E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.398065E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.232423E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.929529E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.268644E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.145582E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.232423E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.301706E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.474905E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.287023E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.178803E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.520870E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.653027E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.121849E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.153658E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.113837E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.367955E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.481934E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.186717E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.439936E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215911E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.367955E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.474905E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162035E+10 | 3744183.92 | 0.479070E+11 | 0.261828E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121404E+10 | 5850109.38 | 0.249018E+11 | 0.229017E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129702E+10 | 14136669.31 | 0.174254E+11 | 0.226612E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128212E+10 | 0.925297E+09 | 0.503203E+10 | 0.742810E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234431E+10 | 0.133504E+11 | 0.918475E+09 | 0.789599E+09 | 69542344.31 | 0.00 | 0.00 | 0.00 |
June | 0.344326E+10 | 0.312794E+11 | 0.161604E+09 | 23340079.57 | 0.154680E+10 | 0.00 | 0.00 | 0.00 |
July | 0.466119E+10 | 0.441895E+11 | 20445940.95 | 37553147.33 | 0.183095E+10 | 0.00 | 0.00 | 0.00 |
August | 0.413154E+10 | 0.354525E+11 | 70393645.82 | 15967241.14 | 0.895121E+09 | 0.00 | 0.00 | 0.00 |
September | 0.255601E+10 | 0.850607E+10 | 0.751571E+09 | 0.324610E+09 | 11203517.64 | 0.00 | 0.00 | 0.00 |
October | 0.142605E+10 | 0.123219E+10 | 0.267925E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108525E+10 | 0.139580E+09 | 0.101565E+11 | 0.150299E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147915E+10 | 5002238.48 | 0.356831E+11 | 0.268455E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265403E+11 | 0.135104E+12 | 0.145708E+12 | 0.127974E+12 | 0.435361E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108525E+10 | 3744183.92 | 20445940.95 | 15967241.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.466119E+10 | 0.441895E+11 | 0.479070E+11 | 0.268455E+11 | 0.183095E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152768E+10 | 1932583.20 | 0.416176E+11 | 0.241665E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116958E+10 | 6616604.09 | 0.195691E+11 | 0.215453E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124195E+10 | 16756157.06 | 0.895571E+10 | 0.217909E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138903E+10 | 0.158032E+10 | 0.113140E+10 | 0.753515E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283938E+10 | 0.147477E+11 | 31338883.78 | 0.888262E+09 | 79121696.16 | 0.00 | 0.00 | 0.00 |
June | 0.404652E+10 | 0.334172E+11 | 1742889.93 | 22574108.46 | 0.165343E+10 | 0.00 | 0.00 | 0.00 |
July | 0.483250E+10 | 0.446761E+11 | 0.00 | 38562631.50 | 0.200335E+10 | 0.00 | 0.00 | 0.00 |
August | 0.380929E+10 | 0.333733E+11 | 266757.34 | 17926177.86 | 0.951433E+09 | 0.00 | 0.00 | 0.00 |
September | 0.217276E+10 | 0.752252E+10 | 17771598.58 | 0.746075E+09 | 11839840.35 | 0.00 | 0.00 | 0.00 |
October | 0.124370E+10 | 0.999830E+09 | 0.853008E+09 | 0.663613E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106941E+10 | 0.124708E+09 | 0.867484E+10 | 0.149937E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146476E+10 | 5240510.60 | 0.331564E+11 | 0.247513E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268066E+11 | 0.136472E+12 | 0.114009E+12 | 0.123132E+12 | 0.469917E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106941E+10 | 1932583.20 | 0.00 | 17926177.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.483250E+10 | 0.446761E+11 | 0.416176E+11 | 0.247513E+11 | 0.200335E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.200238E+10 | 357983.24 | 0.620645E+11 | 0.245156E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157272E+10 | 4729583.22 | 0.340545E+11 | 0.215837E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147054E+10 | 46434034.30 | 0.182914E+11 | 0.219943E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140664E+10 | 0.180037E+10 | 0.346616E+10 | 0.796840E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268377E+10 | 0.158851E+11 | 96589863.10 | 0.108069E+10 | 56373817.60 | 0.00 | 0.00 | 0.00 |
June | 0.385123E+10 | 0.352754E+11 | 428486.43 | 27756363.29 | 0.150688E+10 | 0.00 | 0.00 | 0.00 |
July | 0.447817E+10 | 0.470106E+11 | 0.00 | 30243238.96 | 0.173138E+10 | 0.00 | 0.00 | 0.00 |
August | 0.340520E+10 | 0.342867E+11 | 249843.12 | 32829230.14 | 0.740787E+09 | 0.00 | 0.00 | 0.00 |
September | 0.190177E+10 | 0.720917E+10 | 51049669.96 | 0.108425E+10 | 2765347.11 | 0.00 | 0.00 | 0.00 |
October | 0.127176E+10 | 0.938360E+09 | 0.336148E+10 | 0.738563E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138974E+10 | 0.130180E+09 | 0.183072E+11 | 0.154111E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187536E+10 | 778819.97 | 0.532705E+11 | 0.250450E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273093E+11 | 0.142588E+12 | 0.192964E+12 | 0.126160E+12 | 0.403819E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127176E+10 | 357983.24 | 0.00 | 27756363.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.447817E+10 | 0.470106E+11 | 0.620645E+11 | 0.250450E+11 | 0.173138E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162035E+10 | 0.00 | 0.00 | 0.00 | 1025733.10 | 0.341960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121404E+10 | 0.00 | 0.00 | 0.00 | 1620844.05 | 0.200313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129702E+10 | 0.00 | 0.00 | 0.00 | 3954409.90 | 0.167043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128212E+10 | 0.00 | 0.00 | 0.00 | 0.244714E+09 | 0.499727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234431E+10 | 0.00 | 0.00 | 0.00 | 0.319686E+10 | 0.897197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.344326E+10 | 0.00 | 0.00 | 0.00 | 0.741204E+10 | 0.160097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.466119E+10 | 0.00 | 0.00 | 0.00 | 0.102001E+11 | 20445940.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413154E+10 | 0.00 | 0.00 | 0.00 | 0.818510E+10 | 69211110.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255601E+10 | 0.00 | 0.00 | 0.00 | 0.205284E+10 | 0.714603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142605E+10 | 0.00 | 0.00 | 0.00 | 0.314096E+09 | 0.264429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108525E+10 | 0.00 | 0.00 | 0.00 | 37527773.70 | 0.987703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147915E+10 | 0.00 | 0.00 | 0.00 | 1376796.14 | 0.279103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265403E+11 | 0.00 | 0.00 | 0.00 | 0.316513E+11 | 0.118222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108525E+10 | 0.00 | 0.00 | 0.00 | 1025733.10 | 20445940.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.466119E+10 | 0.00 | 0.00 | 0.00 | 0.102001E+11 | 0.341960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152768E+10 | 0.00 | 0.00 | 0.00 | 529213.25 | 0.286424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116958E+10 | 0.00 | 0.00 | 0.00 | 1810188.00 | 0.146959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124195E+10 | 0.00 | 0.00 | 0.00 | 4609979.47 | 0.802723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138903E+10 | 0.00 | 0.00 | 0.00 | 0.407286E+09 | 0.109860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283938E+10 | 0.00 | 0.00 | 0.00 | 0.349226E+10 | 9854813.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.404652E+10 | 0.00 | 0.00 | 0.00 | 0.785736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.483250E+10 | 0.00 | 0.00 | 0.00 | 0.103003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.380929E+10 | 0.00 | 0.00 | 0.00 | 0.772334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217276E+10 | 0.00 | 0.00 | 0.00 | 0.180789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124370E+10 | 0.00 | 0.00 | 0.00 | 0.252994E+09 | 0.827536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106941E+10 | 0.00 | 0.00 | 0.00 | 33591105.86 | 0.819229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146476E+10 | 0.00 | 0.00 | 0.00 | 1427068.15 | 0.253983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268066E+11 | 0.00 | 0.00 | 0.00 | 0.318834E+11 | 0.868921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.106941E+10 | 0.00 | 0.00 | 0.00 | 529213.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.483250E+10 | 0.00 | 0.00 | 0.00 | 0.103003E+11 | 0.286424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.200238E+10 | 0.00 | 0.00 | 0.00 | 100271.39 | 0.454880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157272E+10 | 0.00 | 0.00 | 0.00 | 1330467.30 | 0.271283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147054E+10 | 0.00 | 0.00 | 0.00 | 12817639.26 | 0.163969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140664E+10 | 0.00 | 0.00 | 0.00 | 0.464133E+09 | 0.333793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268377E+10 | 0.00 | 0.00 | 0.00 | 0.377174E+10 | 74761651.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.385123E+10 | 0.00 | 0.00 | 0.00 | 0.833367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.447817E+10 | 0.00 | 0.00 | 0.00 | 0.108877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340520E+10 | 0.00 | 0.00 | 0.00 | 0.797850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.190177E+10 | 0.00 | 0.00 | 0.00 | 0.174862E+10 | 29159735.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127176E+10 | 0.00 | 0.00 | 0.00 | 0.240213E+09 | 0.330737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138974E+10 | 0.00 | 0.00 | 0.00 | 35189421.80 | 0.172468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187536E+10 | 0.00 | 0.00 | 0.00 | 216182.79 | 0.421181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273093E+11 | 0.00 | 0.00 | 0.00 | 0.334742E+11 | 0.155127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127176E+10 | 0.00 | 0.00 | 0.00 | 100271.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.447817E+10 | 0.00 | 0.00 | 0.00 | 0.108877E+11 | 0.454880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102309E+10 | 0.00 | 0.00 | 0.26 |
February | 0.861589E+10 | 0.00 | 0.00 | 1274.01 | 0.00 | 47572421.02 | 15888951.61 | 0.00 | 0.28 |
March | 0.743554E+10 | 0.00 | 0.00 | 2563108.04 | 0.00 | 18733417.49 | 0.173413E+10 | 0.00 | 0.31 |
April | 0.366168E+10 | 0.00 | 0.00 | 13804523.53 | 24514683.41 | 0.00 | 0.778737E+10 | 0.00 | 0.38 |
May | 0.115591E+10 | 30608125.18 | 0.00 | 30157581.07 | 0.00 | 0.00 | 0.120357E+11 | 0.00 | 0.64 |
June | 0.599107E+09 | 0.135887E+10 | 0.00 | 27499443.73 | 0.157221E+09 | 0.00 | 0.879693E+10 | 0.00 | 0.84 |
July | 0.552759E+09 | 0.223683E+10 | 0.00 | 22091377.35 | 0.244542E+09 | 0.00 | 0.597326E+10 | 0.00 | 0.78 |
August | 0.772363E+09 | 0.117511E+10 | 0.00 | 30295405.80 | 44768571.61 | 0.00 | 0.947836E+10 | 0.00 | 0.92 |
September | 0.115855E+10 | 5434793.50 | 0.00 | 33011733.79 | 0.00 | 0.00 | 0.155277E+11 | 0.00 | 0.71 |
October | 0.250134E+10 | 0.00 | 0.00 | 19859855.49 | 0.00 | 0.00 | 0.108021E+11 | 0.00 | 0.40 |
November | 0.554972E+10 | 0.00 | 0.00 | 3518684.11 | 0.00 | 11690446.92 | 0.255161E+10 | 0.00 | 0.29 |
December | 0.950240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477704E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.526954E+11 | 0.480685E+10 | 0.00 | 0.182803E+09 | 0.471046E+09 | 0.157879E+10 | 0.747030E+11 | 0.00 | 0.51 |
Minimum of Months | 0.552759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.111901E+11 | 0.223683E+10 | 0.00 | 33011733.79 | 0.244542E+09 | 0.102309E+10 | 0.155277E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.851409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428748E+10 | 0.00 | 0.00 | 0.27 |
February | 0.734322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142951E+10 | 0.00 | 0.00 | 0.28 |
March | 0.832345E+10 | 0.00 | 0.00 | 93957.15 | 0.00 | 0.347267E+09 | 0.215335E+09 | 0.00 | 0.30 |
April | 0.598547E+10 | 0.00 | 0.00 | 5394646.15 | 26179106.03 | 14060316.90 | 0.348924E+10 | 0.00 | 0.33 |
May | 0.240637E+10 | 28941938.68 | 0.00 | 20110853.50 | 0.00 | 0.00 | 0.858286E+10 | 0.00 | 0.53 |
June | 0.869096E+09 | 0.114228E+10 | 0.00 | 20290793.49 | 0.190971E+09 | 0.00 | 0.663770E+10 | 0.00 | 0.68 |
July | 0.718939E+09 | 0.190009E+10 | 0.00 | 16774011.26 | 0.320470E+09 | 0.00 | 0.452118E+10 | 0.00 | 0.64 |
August | 0.100635E+10 | 0.967696E+09 | 0.00 | 21344550.54 | 40774885.39 | 0.00 | 0.687741E+10 | 0.00 | 0.72 |
September | 0.274049E+10 | 16855567.30 | 0.00 | 18441101.88 | 436644.22 | 0.00 | 0.959221E+10 | 0.00 | 0.54 |
October | 0.632993E+10 | 0.00 | 0.00 | 5477299.67 | 0.00 | 2301959.04 | 0.363853E+10 | 0.00 | 0.33 |
November | 0.669741E+10 | 0.00 | 0.00 | 563.09 | 0.00 | 0.610287E+09 | 17964772.16 | 0.00 | 0.29 |
December | 0.680645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340121E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.577413E+11 | 0.405587E+10 | 0.00 | 0.107928E+09 | 0.578831E+09 | 0.100921E+11 | 0.435724E+11 | 0.00 | 0.43 |
Minimum of Months | 0.718939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.851409E+10 | 0.190009E+10 | 0.00 | 21344550.54 | 0.320470E+09 | 0.428748E+10 | 0.959221E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829288E+10 | 0.00 | 0.00 | 0.26 |
February | 0.351261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427909E+10 | 0.00 | 0.00 | 0.27 |
March | 0.636532E+10 | 0.00 | 0.00 | 23481.71 | 0.00 | 0.148524E+10 | 75298848.00 | 0.00 | 0.29 |
April | 0.588294E+10 | 0.00 | 0.00 | 3876470.14 | 37654766.84 | 0.146703E+09 | 0.262046E+10 | 0.00 | 0.33 |
May | 0.303210E+10 | 28935699.54 | 0.00 | 18243878.20 | 0.00 | 1375797.62 | 0.735629E+10 | 0.00 | 0.53 |
June | 0.124962E+10 | 0.115660E+10 | 0.00 | 18462799.25 | 0.246163E+09 | 0.00 | 0.617121E+10 | 0.00 | 0.69 |
July | 0.101812E+10 | 0.193374E+10 | 0.00 | 14772446.32 | 0.351528E+09 | 0.00 | 0.395939E+10 | 0.00 | 0.65 |
August | 0.148235E+10 | 0.104032E+10 | 0.00 | 17595268.39 | 26764248.29 | 0.00 | 0.559580E+10 | 0.00 | 0.70 |
September | 0.379569E+10 | 8273318.86 | 0.00 | 12070241.55 | 0.00 | 0.00 | 0.693288E+10 | 0.00 | 0.49 |
October | 0.673919E+10 | 0.00 | 0.00 | 1629103.90 | 0.00 | 0.152740E+09 | 0.151394E+10 | 0.00 | 0.31 |
November | 0.493737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146938E+10 | 0.00 | 0.00 | 0.28 |
December | 0.242640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636024E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.433888E+11 | 0.416787E+10 | 0.00 | 86673689.49 | 0.662110E+09 | 0.221876E+11 | 0.342253E+11 | 0.00 | 0.42 |
Minimum of Months | 0.101812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.673919E+10 | 0.193374E+10 | 0.00 | 18462799.25 | 0.351528E+09 | 0.829288E+10 | 0.735629E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14625395.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414425E+10 | 0.00 | 0.00 | 0.40 |
February | 0.112780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224235E+10 | 0.00 | 0.00 | 0.35 |
March | 0.546340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132903E+10 | 0.00 | 0.00 | 0.33 |
April | 0.127768E+10 | 0.00 | 0.00 | 377410.71 | 8145871.87 | 0.311579E+09 | 0.265503E+09 | 0.00 | 0.33 |
May | 0.814673E+09 | 9774999.95 | 0.00 | 4703105.42 | 0.00 | 8403661.77 | 0.162840E+10 | 0.00 | 0.65 |
June | 0.262407E+09 | 0.403838E+09 | 0.00 | 5357612.25 | 48104497.26 | 0.00 | 0.171943E+10 | 0.00 | 0.95 |
July | 0.223245E+09 | 0.629333E+09 | 0.00 | 4291308.68 | 71815553.64 | 0.00 | 0.111487E+10 | 0.00 | 0.89 |
August | 0.424928E+09 | 0.313302E+09 | 0.00 | 3903950.20 | 6019012.47 | 0.00 | 0.118630E+10 | 0.00 | 0.84 |
September | 0.118788E+10 | 2322347.60 | 0.00 | 2021040.22 | 0.00 | 4219379.09 | 0.106433E+10 | 0.00 | 0.51 |
October | 0.139027E+10 | 0.00 | 0.00 | 85657.74 | 0.00 | 0.345567E+09 | 70889069.64 | 0.00 | 0.32 |
November | 0.381526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111935E+10 | 0.00 | 0.00 | 0.31 |
December | 20703558.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299467E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.665707E+10 | 0.135857E+10 | 0.00 | 20740085.21 | 0.134085E+09 | 0.124994E+11 | 0.704972E+10 | 0.00 | 0.52 |
Minimum of Months | 14625395.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.139027E+10 | 0.629333E+09 | 0.00 | 5357612.25 | 71815553.64 | 0.414425E+10 | 0.171943E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13031188.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235133E+10 | 0.00 | 0.00 | 0.37 |
February | 0.163539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117024E+10 | 0.00 | 0.00 | 0.32 |
March | 0.449871E+09 | 0.00 | 0.00 | 244120.34 | 0.00 | 0.600203E+09 | 0.106977E+09 | 0.00 | 0.32 |
April | 0.584828E+09 | 0.00 | 0.00 | 2539205.51 | 5034204.67 | 0.105371E+09 | 0.116665E+10 | 0.00 | 0.53 |
May | 0.297573E+09 | 7571775.97 | 0.00 | 6224728.67 | 0.00 | 514171.19 | 0.221311E+10 | 0.00 | 1.05 |
June | 95233130.98 | 0.376085E+09 | 0.00 | 7082575.10 | 13351655.33 | 0.00 | 0.232056E+10 | 0.00 | 1.58 |
July | 95117517.72 | 0.643808E+09 | 0.00 | 6088377.50 | 25181820.15 | 0.00 | 0.153736E+10 | 0.00 | 1.56 |
August | 0.175732E+09 | 0.268453E+09 | 0.00 | 5902909.44 | 3669398.56 | 0.00 | 0.146921E+10 | 0.00 | 1.33 |
September | 0.551347E+09 | 1985920.53 | 0.00 | 3420641.70 | 0.00 | 1229950.04 | 0.164021E+10 | 0.00 | 0.80 |
October | 0.779635E+09 | 0.00 | 0.00 | 478919.25 | 0.00 | 0.170076E+09 | 0.269735E+09 | 0.00 | 0.34 |
November | 0.324370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605391E+09 | 0.00 | 0.00 | 0.30 |
December | 26852761.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174615E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.355713E+10 | 0.129790E+10 | 0.00 | 31981477.51 | 47237078.71 | 0.675050E+10 | 0.107238E+11 | 0.00 | 0.74 |
Minimum of Months | 13031188.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.779635E+09 | 0.643808E+09 | 0.00 | 7082575.10 | 25181820.15 | 0.235133E+10 | 0.232056E+10 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539913E+09 | 0.00 | 0.00 | 997644.54 | 0.00 | 0.243480E+10 | 0.334220E+09 | 0.00 | 0.35 |
February | 0.441425E+09 | 0.00 | 0.00 | 1779532.32 | 0.00 | 0.132169E+10 | 0.637023E+09 | 0.00 | 0.37 |
March | 0.589362E+09 | 0.00 | 0.00 | 2527837.95 | 0.00 | 0.775857E+09 | 0.113862E+10 | 0.00 | 0.40 |
April | 0.762243E+09 | 16393179.80 | 0.00 | 5419580.46 | 1442283.53 | 0.187014E+09 | 0.267676E+10 | 0.00 | 0.64 |
May | 0.591114E+09 | 12504286.76 | 0.00 | 8682489.14 | 0.00 | 7644337.60 | 0.304600E+10 | 0.00 | 0.98 |
June | 0.286710E+09 | 0.492835E+09 | 0.00 | 7048530.68 | 34762462.33 | 0.00 | 0.218397E+10 | 0.00 | 1.19 |
July | 0.230241E+09 | 0.822862E+09 | 0.00 | 6330863.50 | 62663879.70 | 0.00 | 0.150783E+10 | 0.00 | 1.17 |
August | 0.353174E+09 | 0.499415E+09 | 0.00 | 8243279.50 | 3513523.43 | 0.00 | 0.193757E+10 | 0.00 | 1.31 |
September | 0.797575E+09 | 7236242.63 | 0.00 | 8025420.58 | 0.00 | 1372232.63 | 0.347807E+10 | 0.00 | 1.04 |
October | 0.103999E+10 | 0.00 | 0.00 | 3764781.22 | 0.00 | 0.225135E+09 | 0.174795E+10 | 0.00 | 0.56 |
November | 0.538275E+09 | 0.00 | 0.00 | 1417745.09 | 0.00 | 0.703828E+09 | 0.561483E+09 | 0.00 | 0.35 |
December | 0.300154E+09 | 0.00 | 0.00 | 277276.34 | 0.00 | 0.211234E+10 | 90274134.36 | 0.00 | 0.32 |
Annual Sum or Average | 0.647017E+10 | 0.185125E+10 | 0.00 | 54514981.32 | 0.102382E+09 | 0.776968E+10 | 0.193398E+11 | 0.00 | 0.73 |
Minimum of Months | 0.230241E+09 | 0.00 | 0.00 | 277276.34 | 0.00 | 0.00 | 90274134.36 | 0.00 | 0.32 |
Maximum of Months | 0.103999E+10 | 0.822862E+09 | 0.00 | 8682489.14 | 62663879.70 | 0.243480E+10 | 0.347807E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 77533247.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249795E+10 | 0.00 | 0.00 | 0.39 |
February | 0.177364E+09 | 0.00 | 0.00 | 69803.87 | 0.00 | 0.127659E+10 | 47759980.19 | 0.00 | 0.34 |
March | 0.371782E+09 | 0.00 | 0.00 | 640852.62 | 0.00 | 0.665638E+09 | 0.308798E+09 | 0.00 | 0.35 |
April | 0.596698E+09 | 8685572.19 | 0.00 | 2588971.46 | 2745810.54 | 0.151108E+09 | 0.125331E+10 | 0.00 | 0.57 |
May | 0.361001E+09 | 8886432.82 | 0.00 | 6722241.69 | 0.00 | 4954728.92 | 0.213203E+10 | 0.00 | 1.08 |
June | 0.169148E+09 | 0.365745E+09 | 0.00 | 5470830.43 | 18531555.38 | 0.00 | 0.157500E+10 | 0.00 | 1.40 |
July | 0.125956E+09 | 0.602178E+09 | 0.00 | 4932252.35 | 34033559.63 | 0.00 | 0.106760E+10 | 0.00 | 1.33 |
August | 0.226505E+09 | 0.311652E+09 | 0.00 | 4863144.35 | 1000495.48 | 0.00 | 0.117044E+10 | 0.00 | 1.26 |
September | 0.601560E+09 | 2579822.81 | 0.00 | 3389911.67 | 0.00 | 2367277.54 | 0.148775E+10 | 0.00 | 0.80 |
October | 0.737856E+09 | 0.00 | 0.00 | 782809.46 | 0.00 | 0.189039E+09 | 0.440153E+09 | 0.00 | 0.39 |
November | 0.305642E+09 | 0.00 | 0.00 | 14687.32 | 0.00 | 0.612616E+09 | 15807394.82 | 0.00 | 0.31 |
December | 41443000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188619E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.379249E+10 | 0.129973E+10 | 0.00 | 29475505.21 | 56311421.02 | 0.728645E+10 | 0.949864E+10 | 0.00 | 0.72 |
Minimum of Months | 41443000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.737856E+09 | 0.602178E+09 | 0.00 | 6722241.69 | 34033559.63 | 0.249795E+10 | 0.213203E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24710417.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407434E+10 | 0.00 | 0.00 | 0.39 |
February | 40300416.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241253E+10 | 0.00 | 0.00 | 0.34 |
March | 0.273479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189493E+10 | 0.00 | 0.00 | 0.34 |
April | 0.133641E+10 | 0.00 | 0.00 | 0.00 | 5321897.22 | 0.671115E+09 | 0.00 | 0.00 | 0.32 |
May | 0.135309E+10 | 5141608.81 | 0.00 | 1431799.96 | 0.00 | 23486335.83 | 0.431078E+09 | 0.00 | 0.41 |
June | 0.466201E+09 | 0.245922E+09 | 0.00 | 2855335.26 | 36975337.71 | 0.00 | 0.864415E+09 | 0.00 | 0.61 |
July | 0.237395E+09 | 0.444453E+09 | 0.00 | 3216032.02 | 54894619.96 | 0.00 | 0.846412E+09 | 0.00 | 0.66 |
August | 0.398163E+09 | 0.226837E+09 | 0.00 | 3504901.11 | 10344725.49 | 0.00 | 0.110953E+10 | 0.00 | 0.72 |
September | 0.116177E+10 | 1088687.66 | 0.00 | 2114459.80 | 0.00 | 0.00 | 0.110824E+10 | 0.00 | 0.48 |
October | 0.194491E+10 | 0.00 | 0.00 | 59659.11 | 0.00 | 0.100961E+09 | 73492610.60 | 0.00 | 0.31 |
November | 0.723099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103633E+10 | 0.00 | 0.00 | 0.30 |
December | 29259738.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293125E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.798879E+10 | 0.923442E+09 | 0.00 | 13182187.26 | 0.107537E+09 | 0.131449E+11 | 0.443317E+10 | 0.00 | 0.44 |
Minimum of Months | 24710417.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.194491E+10 | 0.444453E+09 | 0.00 | 3504901.11 | 54894619.96 | 0.407434E+10 | 0.110953E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17496796.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246796E+10 | 0.00 | 0.00 | 0.37 |
February | 0.112738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132617E+10 | 0.00 | 0.00 | 0.32 |
March | 0.414463E+09 | 0.00 | 0.00 | 6211.55 | 0.00 | 0.869170E+09 | 8488777.71 | 0.00 | 0.32 |
April | 0.745599E+09 | 0.00 | 0.00 | 1208653.09 | 3279107.46 | 0.183646E+09 | 0.601638E+09 | 0.00 | 0.39 |
May | 0.473254E+09 | 4672240.80 | 0.00 | 3637723.89 | 0.00 | 143745.32 | 0.121488E+10 | 0.00 | 0.69 |
June | 0.115583E+09 | 0.256471E+09 | 0.00 | 5241431.60 | 11091299.28 | 0.00 | 0.167859E+10 | 0.00 | 1.18 |
July | 78697995.06 | 0.492805E+09 | 0.00 | 5040779.21 | 19792002.49 | 0.00 | 0.132032E+10 | 0.00 | 1.28 |
August | 0.157200E+09 | 0.222323E+09 | 0.00 | 5323833.46 | 6254557.32 | 0.00 | 0.143585E+10 | 0.00 | 1.21 |
September | 0.473595E+09 | 1045647.06 | 0.00 | 3904639.08 | 0.00 | 0.00 | 0.180804E+10 | 0.00 | 0.79 |
October | 0.100434E+10 | 0.00 | 0.00 | 666672.06 | 0.00 | 45477765.55 | 0.363693E+09 | 0.00 | 0.33 |
November | 0.546943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544076E+09 | 0.00 | 0.00 | 0.29 |
December | 39121062.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179160E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.417903E+10 | 0.977317E+09 | 0.00 | 25029943.93 | 40416966.54 | 0.722824E+10 | 0.843150E+10 | 0.00 | 0.63 |
Minimum of Months | 17496796.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.100434E+10 | 0.492805E+09 | 0.00 | 5323833.46 | 19792002.49 | 0.246796E+10 | 0.180804E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 80195631.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565909E+10 | 0.00 | 0.00 | 0.54 |
February | 0.289642E+09 | 0.00 | 0.00 | 5184.07 | 0.00 | 0.309970E+10 | 6113206.85 | 0.00 | 0.47 |
March | 0.430197E+09 | 0.00 | 0.00 | 68558.35 | 0.00 | 0.246376E+10 | 42755816.79 | 0.00 | 0.46 |
April | 0.999703E+09 | 2456663.71 | 0.00 | 920734.51 | 3224959.39 | 0.113685E+10 | 0.551549E+09 | 0.00 | 0.44 |
May | 0.109850E+10 | 9026082.81 | 0.00 | 3129679.77 | 0.00 | 0.341049E+09 | 0.722645E+09 | 0.00 | 0.56 |
June | 0.574766E+09 | 0.333562E+09 | 0.00 | 3224793.48 | 38607407.79 | 78333278.50 | 0.803692E+09 | 0.00 | 0.74 |
July | 0.287267E+09 | 0.622920E+09 | 0.00 | 3853028.11 | 58685165.49 | 11648202.78 | 0.933570E+09 | 0.00 | 0.85 |
August | 0.519816E+09 | 0.392543E+09 | 0.00 | 5197211.78 | 7012488.67 | 42141685.80 | 0.121653E+10 | 0.00 | 1.03 |
September | 0.965464E+09 | 3114679.07 | 0.00 | 5745873.82 | 0.00 | 0.296041E+09 | 0.237638E+10 | 0.00 | 0.87 |
October | 0.115946E+10 | 0.00 | 0.00 | 2272548.79 | 0.00 | 0.973095E+09 | 0.100636E+10 | 0.00 | 0.51 |
November | 0.535489E+09 | 0.00 | 0.00 | 85982.47 | 0.00 | 0.177283E+10 | 65591243.05 | 0.00 | 0.40 |
December | 0.123663E+09 | 0.00 | 0.00 | 28159.48 | 0.00 | 0.424455E+10 | 17547509.07 | 0.00 | 0.52 |
Annual Sum or Average | 0.706416E+10 | 0.136362E+10 | 0.00 | 24531754.62 | 0.107530E+09 | 0.201191E+11 | 0.774274E+10 | 0.00 | 0.62 |
Minimum of Months | 80195631.76 | 0.00 | 0.00 | 0.00 | 0.00 | 11648202.78 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.115946E+10 | 0.622920E+09 | 0.00 | 5745873.82 | 58685165.49 | 0.565909E+10 | 0.237638E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 64684647.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258856E+10 | 0.00 | 0.00 | 0.39 |
February | 0.154816E+09 | 0.00 | 0.00 | 1153.79 | 0.00 | 0.138466E+10 | 2297064.38 | 0.00 | 0.33 |
March | 0.382363E+09 | 0.00 | 0.00 | 136008.76 | 0.00 | 0.876259E+09 | 74967734.10 | 0.00 | 0.33 |
April | 0.758671E+09 | 463139.55 | 0.00 | 997632.83 | 2996546.31 | 0.241124E+09 | 0.531834E+09 | 0.00 | 0.39 |
May | 0.486157E+09 | 6340115.21 | 0.00 | 3803307.03 | 0.00 | 6839455.87 | 0.112471E+10 | 0.00 | 0.70 |
June | 0.225959E+09 | 0.251507E+09 | 0.00 | 3671365.84 | 17489827.81 | 0.00 | 0.984994E+09 | 0.00 | 0.99 |
July | 89863445.47 | 0.492693E+09 | 0.00 | 4071927.29 | 25141147.63 | 0.00 | 0.974236E+09 | 0.00 | 1.11 |
August | 0.173533E+09 | 0.243631E+09 | 0.00 | 4633472.03 | 1866763.06 | 0.00 | 0.122127E+10 | 0.00 | 1.15 |
September | 0.495649E+09 | 1681669.80 | 0.00 | 3587292.39 | 0.00 | 0.00 | 0.160055E+10 | 0.00 | 0.77 |
October | 0.982335E+09 | 0.00 | 0.00 | 831580.39 | 0.00 | 54885972.09 | 0.459442E+09 | 0.00 | 0.36 |
November | 0.529705E+09 | 0.00 | 0.00 | 6204.25 | 0.00 | 0.550508E+09 | 7872824.88 | 0.00 | 0.29 |
December | 47501768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189835E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.439124E+10 | 0.996316E+09 | 0.00 | 21739944.60 | 47494284.81 | 0.760118E+10 | 0.698218E+10 | 0.00 | 0.60 |
Minimum of Months | 47501768.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.982335E+09 | 0.492693E+09 | 0.00 | 4633472.03 | 25141147.63 | 0.258856E+10 | 0.160055E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27300883.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382781E+10 | 0.00 | 0.00 | 0.35 |
February | 0.157052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209597E+10 | 0.00 | 0.00 | 0.31 |
March | 0.770591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117558E+10 | 0.00 | 0.00 | 0.31 |
April | 0.143163E+10 | 0.00 | 0.00 | 432013.83 | 5504058.69 | 0.189752E+09 | 0.309860E+09 | 0.00 | 0.32 |
May | 0.700774E+09 | 9898971.83 | 0.00 | 5093233.54 | 0.00 | 731611.26 | 0.181678E+10 | 0.00 | 0.63 |
June | 0.189361E+09 | 0.398359E+09 | 0.00 | 5831383.95 | 39153797.55 | 0.00 | 0.178714E+10 | 0.00 | 0.93 |
July | 0.162179E+09 | 0.603781E+09 | 0.00 | 4658515.43 | 66483860.33 | 0.00 | 0.121869E+10 | 0.00 | 0.87 |
August | 0.328031E+09 | 0.289722E+09 | 0.00 | 4602045.52 | 8850419.36 | 0.00 | 0.139798E+10 | 0.00 | 0.85 |
September | 0.102850E+10 | 4754433.09 | 0.00 | 2814531.03 | 91802.81 | 0.00 | 0.142434E+10 | 0.00 | 0.53 |
October | 0.166353E+10 | 0.00 | 0.00 | 211526.11 | 0.00 | 0.142197E+09 | 0.189856E+09 | 0.00 | 0.32 |
November | 0.655671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941362E+09 | 0.00 | 0.00 | 0.29 |
December | 28225836.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284779E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.714285E+10 | 0.130652E+10 | 0.00 | 23643249.40 | 0.120084E+09 | 0.112212E+11 | 0.814463E+10 | 0.00 | 0.51 |
Minimum of Months | 27300883.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.166353E+10 | 0.603781E+09 | 0.00 | 5831383.95 | 66483860.33 | 0.382781E+10 | 0.181678E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 77780595.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208364E+10 | 0.00 | 0.00 | 0.31 |
February | 0.203219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998757E+09 | 0.00 | 0.00 | 0.26 |
March | 0.465319E+09 | 0.00 | 0.00 | 376474.37 | 0.00 | 0.493766E+09 | 0.148382E+09 | 0.00 | 0.28 |
April | 0.550469E+09 | 0.00 | 0.00 | 2791782.90 | 3487373.17 | 61596250.22 | 0.125353E+10 | 0.00 | 0.50 |
May | 0.267324E+09 | 7143362.81 | 0.00 | 6265993.50 | 0.00 | 0.00 | 0.222913E+10 | 0.00 | 0.98 |
June | 71668191.34 | 0.351717E+09 | 0.00 | 7096691.22 | 11019777.99 | 0.00 | 0.226964E+10 | 0.00 | 1.48 |
July | 67069553.74 | 0.588629E+09 | 0.00 | 6076365.78 | 26083696.22 | 0.00 | 0.155578E+10 | 0.00 | 1.46 |
August | 0.158712E+09 | 0.237522E+09 | 0.00 | 5955741.74 | 5353479.46 | 0.00 | 0.151763E+10 | 0.00 | 1.26 |
September | 0.468704E+09 | 4192394.98 | 0.00 | 3859788.67 | 58166.28 | 0.00 | 0.177876E+10 | 0.00 | 0.78 |
October | 0.787261E+09 | 0.00 | 0.00 | 712907.30 | 0.00 | 74596326.19 | 0.361729E+09 | 0.00 | 0.31 |
November | 0.365487E+09 | 0.00 | 0.00 | 3008.34 | 0.00 | 0.490401E+09 | 3604285.86 | 0.00 | 0.25 |
December | 57593228.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159548E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.354061E+10 | 0.118920E+10 | 0.00 | 33138753.82 | 46002493.13 | 0.579824E+10 | 0.111182E+11 | 0.00 | 0.68 |
Minimum of Months | 57593228.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.787261E+09 | 0.588629E+09 | 0.00 | 7096691.22 | 26083696.22 | 0.208364E+10 | 0.226964E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.655010E+09 | 0.00 | 0.00 | 1419838.21 | 0.00 | 0.228491E+10 | 0.506376E+09 | 0.00 | 0.34 |
February | 0.556920E+09 | 0.00 | 0.00 | 2228207.22 | 0.00 | 0.122053E+10 | 0.728423E+09 | 0.00 | 0.38 |
March | 0.805070E+09 | 0.00 | 0.00 | 3163263.08 | 0.00 | 0.672900E+09 | 0.126034E+10 | 0.00 | 0.42 |
April | 0.907800E+09 | 13270396.24 | 0.00 | 5872011.31 | 409151.30 | 99044840.79 | 0.274131E+10 | 0.00 | 0.65 |
May | 0.550644E+09 | 13341144.31 | 0.00 | 9019569.98 | 0.00 | 1859834.96 | 0.308411E+10 | 0.00 | 0.95 |
June | 0.258660E+09 | 0.475820E+09 | 0.00 | 7294783.62 | 31977360.86 | 0.00 | 0.210157E+10 | 0.00 | 1.17 |
July | 0.185991E+09 | 0.804733E+09 | 0.00 | 6257023.41 | 61409034.21 | 0.00 | 0.151195E+10 | 0.00 | 1.13 |
August | 0.301235E+09 | 0.462469E+09 | 0.00 | 8357491.45 | 4754961.25 | 0.00 | 0.202888E+10 | 0.00 | 1.28 |
September | 0.719462E+09 | 15685386.73 | 0.00 | 9066955.40 | 92056.49 | 0.00 | 0.380106E+10 | 0.00 | 1.09 |
October | 0.122607E+10 | 0.00 | 0.00 | 4693767.37 | 0.00 | 91103800.20 | 0.207540E+10 | 0.00 | 0.59 |
November | 0.764780E+09 | 0.00 | 0.00 | 1786450.22 | 0.00 | 0.605334E+09 | 0.697777E+09 | 0.00 | 0.36 |
December | 0.396951E+09 | 0.00 | 0.00 | 491214.90 | 0.00 | 0.202906E+10 | 0.172988E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.732859E+10 | 0.178532E+10 | 0.00 | 59650576.17 | 98642564.10 | 0.700474E+10 | 0.207102E+11 | 0.00 | 0.72 |
Minimum of Months | 0.185991E+09 | 0.00 | 0.00 | 491214.90 | 0.00 | 0.00 | 0.172988E+09 | 0.00 | 0.31 |
Maximum of Months | 0.122607E+10 | 0.804733E+09 | 0.00 | 9066955.40 | 61409034.21 | 0.228491E+10 | 0.380106E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231196E+10 | 0.00 | 0.00 | 0.35 |
February | 0.229048E+09 | 0.00 | 0.00 | 77507.37 | 0.00 | 0.118396E+10 | 46028229.17 | 0.00 | 0.32 |
March | 0.505942E+09 | 0.00 | 0.00 | 727586.27 | 0.00 | 0.603342E+09 | 0.321504E+09 | 0.00 | 0.35 |
April | 0.689800E+09 | 660718.73 | 0.00 | 2656348.87 | 3294698.49 | 90228227.05 | 0.127014E+10 | 0.00 | 0.56 |
May | 0.323725E+09 | 10042771.51 | 0.00 | 6931795.23 | 0.00 | 2636781.88 | 0.214224E+10 | 0.00 | 1.05 |
June | 0.145903E+09 | 0.357559E+09 | 0.00 | 5625866.08 | 17890878.04 | 0.00 | 0.152625E+10 | 0.00 | 1.37 |
July | 97571157.31 | 0.591968E+09 | 0.00 | 4971451.19 | 31439127.00 | 0.00 | 0.107931E+10 | 0.00 | 1.29 |
August | 0.188815E+09 | 0.284821E+09 | 0.00 | 5081004.25 | 1229420.73 | 0.00 | 0.125431E+10 | 0.00 | 1.24 |
September | 0.522285E+09 | 4170211.70 | 0.00 | 3943614.44 | 28614.47 | 0.00 | 0.171290E+10 | 0.00 | 0.84 |
October | 0.915462E+09 | 0.00 | 0.00 | 1044539.18 | 0.00 | 87576111.46 | 0.548748E+09 | 0.00 | 0.41 |
November | 0.450366E+09 | 0.00 | 0.00 | 37682.48 | 0.00 | 0.539218E+09 | 31345029.11 | 0.00 | 0.30 |
December | 78859780.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178477E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.426688E+10 | 0.124922E+10 | 0.00 | 31097395.36 | 53882738.72 | 0.660369E+10 | 0.993278E+10 | 0.00 | 0.70 |
Minimum of Months | 78859780.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.915462E+09 | 0.591968E+09 | 0.00 | 6931795.23 | 31439127.00 | 0.231196E+10 | 0.214224E+10 | 0.00 | 1.37 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148166E+12 | 0.353336E+11 | 0.00 | 0.176752E+12 | 0.824819E+10 |
February | 0.210771E+12 | 0.300502E+11 | 0.00 | 0.153310E+12 | 0.319720E+10 |
March | 0.293018E+12 | 0.237694E+11 | 0.00 | 0.181604E+12 | 0.773780E+09 |
April | 0.358935E+12 | 0.187863E+11 | 0.00 | 0.181953E+12 | 0.545942E+10 |
May | 0.412960E+12 | 0.947078E+10 | 0.00 | 0.216604E+12 | 0.544563E+11 |
June | 0.420506E+12 | 0.320326E+10 | 0.00 | 0.140739E+12 | 0.123576E+12 |
July | 0.428817E+12 | 0.141011E+10 | 0.00 | 0.102534E+12 | 0.167264E+12 |
August | 0.360325E+12 | 0.399727E+10 | 0.00 | 0.150975E+12 | 0.127000E+12 |
September | 0.269132E+12 | 0.946503E+10 | 0.00 | 0.214199E+12 | 0.288617E+11 |
October | 0.158004E+12 | 0.150918E+11 | 0.00 | 0.200966E+12 | 0.399950E+10 |
November | 0.843551E+11 | 0.237488E+11 | 0.00 | 0.149324E+12 | 0.847901E+09 |
December | 0.104453E+12 | 0.359480E+11 | 0.00 | 0.166967E+12 | 0.509659E+10 |
Annual Sum or Average | 0.324944E+13 | 0.210275E+12 | 0.00 | 0.203593E+13 | 0.528781E+12 |
Minimum of Months | 0.843551E+11 | 0.141011E+10 | 0.00 | 0.102534E+12 | 0.773780E+09 |
Maximum of Months | 0.428817E+12 | 0.359480E+11 | 0.00 | 0.216604E+12 | 0.167264E+12 |