Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:32:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1683.09 | 337.82 | 337.82 |
Net Site Energy | 1552.12 | 311.53 | 311.53 |
Total Source Energy | 4487.43 | 900.70 | 900.70 |
Net Source Energy | 4072.64 | 817.44 | 817.44 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 227.06 | 269.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 166.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 135.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1278.42 | 404.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 227.06 | 269.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 166.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 78.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 135.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 227.06 | 269.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 166.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 78.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 135.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 83.90 | 81.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.60 | 81.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 83.90 | 81.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.60 | 81.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 137.143 | 10.73 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -6.17 | -0.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 130.974 | 10.24 |
Electricity Coming From Utility | 1148.554 | 89.84 |
Surplus Electricity Going To Utility | 1.104 | 0.09 |
Net Electricity From Utility | 1147.450 | 89.76 |
Total On-Site and Utility Electric Sources | 1278.424 | 100.00 |
Total Electricity End Uses | 1278.424 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 386.33 |
Time Setpoint Not Met During Occupied Cooling | 79.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2709.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 06-FEB-08:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 187169.61 | 107246.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6730.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9476.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 222211.27 | 116722.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 187169.61 | 107246.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2981.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 36.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6730.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9476.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 719.10 | 291.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 355.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 527.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 108.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 146.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4048.77 | 438.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 144.33 | 58.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 812.65 | 88.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 144.33 | 58.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 812.65 | 88.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.39 | 0.313307 | 0.266000 | 0.636293 | 0.835485 | 0.500000 | 0.001216 |
CORE_MID VAV BOX COMPONENT | 2.00 | 0.374379 | 0.318000 | 0.636592 | 0.998345 | 0.500000 | 0.001018 |
CORE_TOP VAV BOX COMPONENT | 2.08 | 0.359831 | 0.306000 | 0.637336 | 0.959550 | 0.500000 | 0.001059 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.652254 | 0.242224 | 0.206000 | 0.134364 | 0.645931 | 0.500000 | 0.001573 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.772828 | 0.129423 | 0.110000 | 0.085011 | 0.345128 | 0.500000 | 0.002944 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.948694 | 0.166536 | 0.142000 | 0.134714 | 0.444096 | 0.500000 | 0.002288 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.842280 | 0.118743 | 0.101000 | 0.085070 | 0.316649 | 0.500000 | 0.003209 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.503291 | 0.313917 | 0.267000 | 0.134379 | 0.837112 | 0.500000 | 0.001214 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.627436 | 0.159413 | 0.136000 | 0.085331 | 0.425102 | 0.500000 | 0.002390 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.751050 | 0.210361 | 0.179000 | 0.134438 | 0.560963 | 0.500000 | 0.001811 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.654722 | 0.152760 | 0.130000 | 0.085114 | 0.407359 | 0.500000 | 0.002494 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.569300 | 0.277519 | 0.236000 | 0.134355 | 0.740051 | 0.500000 | 0.001373 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.762351 | 0.349871 | 0.500000 | 0.002904 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.867916 | 0.182036 | 0.155000 | 0.134527 | 0.485428 | 0.500000 | 0.002093 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.784571 | 0.127478 | 0.108000 | 0.084734 | 0.339940 | 0.500000 | 0.002989 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20717.81 |
CORE_MID VAV BOX REHEAT COIL | 22406.60 |
CORE_TOP VAV BOX REHEAT COIL | 39367.01 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19280.94 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12530.04 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19268.72 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12624.27 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14641.21 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9571.41 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14641.19 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9657.47 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15242.36 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9951.33 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 15227.09 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10040.43 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.46 | 1.08 | 4.93 | 1.91 | 4.31 | 4.31 | 0.300000 | 0.443807 | 4.31 |
PACU_VAV_MID | 2.49 | 1.08 | 4.99 | 2.24 | 4.15 | 4.15 | 0.300000 | 0.539880 | 4.15 |
PACU_VAV_TOP | 2.65 | 1.08 | 5.30 | 3.17 | 4.78 | 4.78 | 0.300000 | 0.662845 | 4.78 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.31 |
PACU_VAV_MID_OA_CONTROLLER | 4.15 |
PACU_VAV_TOP_OA_CONTROLLER | 4.78 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.31 | 88592.87 | 0.766357 | 1.44 | 29528.00 | 0.766357 |
PACU_VAV_MID COOLING COIL | 4.15 | 86246.78 | 0.760510 | 1.38 | 28746.05 | 0.760510 |
PACU_VAV_TOP COOLING COIL | 4.78 | 96476.03 | 0.772266 | 1.59 | 32155.46 | 0.772266 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 30354.97 |
PACU_VAV_MID HEATING COIL | 30847.10 |
PACU_VAV_TOP HEATING COIL | 29903.91 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.31 |
PACU_VAV_MID FAN | 4.15 |
PACU_VAV_TOP FAN | 4.78 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5358 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5301 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.6467 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.632 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.652 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.312 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.34415616E-12 | 0.73563561E-15 | -0.10764161E-12 | 0.10685741E-15 |
43 | 6 | 0.31504638E-07 | 0.15474724E-09 | 0.71933787E-08 | -0.15048178E-12 |
44 | 5 | -0.20438857E-03 | 0.13016735E-05 | -0.10492214E-03 | 0.71015789E-08 |
45 | 4 | 0.30870407 | 0.62380386E-03 | 0.10564545 | -0.35923044E-04 |
46 | 3 | -7.5938769 | 0.19061556E-01 | -2.4361333 | 0.30615224E-01 |
47 | 2 | 41.951003 | 0.66938758E-01 | 15.662994 | -0.34536947 |
48 | 1 | -81.372858 | 0.29881068E-01 | -29.498176 | 1.0962451 |
49 | 0 | 46.824334 | 0.59474289E-03 | 16.282875 | |
50 | 7 | -0.34405391E-12 | 0.74902691E-15 | -0.11167434E-12 | 0.10710038E-15 |
51 | 6 | 0.31570920E-07 | 0.15318783E-09 | 0.72080048E-08 | -0.15084089E-12 |
52 | 5 | -0.20472033E-03 | 0.12880691E-05 | -0.10508761E-03 | 0.71158009E-08 |
53 | 4 | 0.30908525 | 0.61707511E-03 | 0.10578288 | -0.35977555E-04 |
54 | 3 | -7.6014096 | 0.18850271E-01 | -2.4383697 | 0.30652185E-01 |
55 | 2 | 41.975828 | 0.66179041E-01 | 15.672127 | -0.34564605 |
56 | 1 | -81.391862 | 0.29534967E-01 | -29.506353 | 1.0966501 |
57 | 0 | 46.824333 | 0.58771801E-03 | 16.282688 | |
58 | 7 | -0.33303739E-12 | 0.11430073E-14 | -0.10564856E-12 | 0.99270328E-16 |
59 | 6 | 0.30206507E-07 | 0.18467178E-09 | 0.69068382E-08 | -0.14346196E-12 |
60 | 5 | -0.19787007E-03 | 0.15652367E-05 | -0.10166770E-03 | 0.68228702E-08 |
61 | 4 | 0.30118360 | 0.75522621E-03 | 0.10293566 | -0.34850853E-04 |
62 | 3 | -7.4451882 | 0.23217066E-01 | -2.3919942 | 0.29885849E-01 |
63 | 2 | 41.460907 | 0.81970212E-01 | 15.482559 | -0.33990950 |
64 | 1 | -80.997597 | 0.36763750E-01 | -29.336578 | 1.0882477 |
65 | 0 | 46.824336 | 0.73512635E-03 | 16.286622 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.378 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.379 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.29167 | 0.50232 | 0.50232 | 0.41580 | 0.13603 | 0.17565 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2215E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2280E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3534E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3589E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2168E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2616E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3510E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3752E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1695 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9604E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1930 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1017 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1169 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9702E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2217E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2294E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3536E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3604E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2188E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2713E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3507E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3749E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8402E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5311E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5065E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2535E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4943E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7697E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6444E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6601E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9839E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0101E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6980E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7170E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2495E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2562E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0780E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0864E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6493E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7071E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8871E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9338E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3774E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4123E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3507E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3749E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4452E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5454E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4292E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9423E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1553E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3320E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6489E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7075E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8863E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9322E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3756E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4054E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3510E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3752E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5523E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9055E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8905E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4652E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4595E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2827E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6444E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6601E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1638E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2366E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6637E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7435E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6191E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6491E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0782E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0865E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1702 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1085 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1909 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1226 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1254 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3015E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4807E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5582E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.5817E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3824E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2709E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1176E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.3162E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6635E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5395E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5971E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0636E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3159E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9790E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6051E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7051E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9384E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4807E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5582E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3353E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7852E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7076E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3654E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3123E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1973E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5395E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5971E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1702 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1085 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1909 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1226 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1254 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3007E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4802E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5579E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.5816E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3821E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2708E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1172E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.3158E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6631E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5390E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5968E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0637E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3158E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9791E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6050E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7048E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9382E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4802E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5579E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3353E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7849E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7076E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3652E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3119E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1970E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5390E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5968E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 32383.42578 | 32383.42578 | 2.39208 | 2.39208 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9134.83598 | 9134.83598 | 0.40230 | 0.42469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27124.40921 | 27124.40921 | 2.00186 | 2.00186 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 15839.34575 | 15839.34575 | 0.68816 | 0.68816 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27946.56412 | 27946.56412 | 2.08280 | 2.08280 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 27715.90062 | 27715.90062 | 1.20905 | 1.20905 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8751.13186 | 8751.13186 | 0.65225 | 0.65225 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 13537.04231 | 13537.04231 | 0.59216 | 0.59216 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10368.89623 | 10368.89623 | 0.77283 | 0.77283 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8796.81022 | 8796.81022 | 0.38483 | 0.38483 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12728.44889 | 12728.44889 | 0.94869 | 0.94869 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 13528.48217 | 13528.48217 | 0.59179 | 0.59179 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11300.76322 | 11300.76322 | 0.84228 | 0.84228 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8862.81471 | 8862.81471 | 0.38772 | 0.38772 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6752.78281 | 6752.78281 | 0.50329 | 0.50329 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10285.66938 | 10285.66938 | 0.44967 | 0.44967 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8418.54644 | 8418.54644 | 0.62744 | 0.62744 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6723.45128 | 6723.45128 | 0.29396 | 0.29396 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10077.07740 | 10077.07740 | 0.75105 | 0.75105 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10285.65353 | 10285.65353 | 0.44967 | 0.44967 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8784.66210 | 8784.66210 | 0.65472 | 0.65472 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 28.37800 | 1.33635E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6783.71754 | 6783.71754 | 0.29660 | 0.29660 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7638.25331 | 7638.25331 | 0.56930 | 0.56930 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 10707.61092 | 10707.61092 | 0.46813 | 0.46813 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10228.49702 | 10228.49702 | 0.76235 | 0.76235 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.44850 | 1.33584E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6990.14335 | 6990.14335 | 0.30563 | 0.30563 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11644.81994 | 11644.81994 | 0.86792 | 0.86792 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10696.91793 | 10696.91793 | 0.46766 | 0.46766 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10526.62490 | 10526.62490 | 0.78457 | 0.78457 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7052.54973 | 7052.54973 | 0.30837 | 0.30837 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 64092.96 | 4.31401 | 4.31401 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 32567.73 | 1.91459 | 1.91459 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 61810.18 | 4.14526 | 4.14526 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 32654.47 | 2.23794 | 2.23794 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 70070.83 | 4.77571 | 4.77571 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 32797.53 | 3.16555 | 3.16555 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39208 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31331 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63629 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83549 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21606E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20717.81197 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00186 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37438 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63659 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99834 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01768E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22406.60112 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.08280 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35983 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63734 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95955 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05883E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 39367.00699 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65225 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24222 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20600 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13436 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64593 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57292E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19280.93681 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77283 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12942 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50110E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34513 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94383E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12530.03726 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94869 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16654 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13471 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44410 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28779E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19268.71733 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84228 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11874 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10100 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50703E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31665 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20860E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12624.26903 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50329 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31392 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13438 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83711 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21370E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14641.21457 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62744 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15941 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13600 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53314E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42510 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39001E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9571.41326 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75105 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21036 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13444 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56096 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81117E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14641.19193 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65472 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15276 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51139E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40736 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49411E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9657.46709 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56930 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27752 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13435 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37288E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15242.35632 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76235 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34987 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90393E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9951.33251 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86792 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18204 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13453 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48543 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09300E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15227.09063 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78457 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12748 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10800 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47337E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33994 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98876E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10040.43432 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.46429 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07555 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.92858 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.91459 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.31401 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.31401 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.44381 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.49300 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07559 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.98600 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.23794 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.14526 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.14526 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.53988 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64943 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07650 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.29885 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.16555 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.77571 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.77571 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.66284 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.31401 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.14526 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.77571 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.31401 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.31401 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 88592.86846 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76636 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.43786 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29528.00306 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76636 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 30354.97270 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.31401 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.14526 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.14526 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86246.78461 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76051 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.38162 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28746.05331 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76051 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 30847.09731 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.14526 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.77571 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.77571 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 96476.03072 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77227 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59174 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32155.46104 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77227 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 29903.90736 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.77571 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 87871.00 | 299828.30 | 12.27 | 3.15 | 3.51 | 3.69 | 3.89 | 10.75 | 11.98 | 12.60 | 13.27 | 4.8643 | 3.8860 | 2.6173 | 1.0578 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 85586.18 | 292032.18 | 12.30 | 3.16 | 3.52 | 3.71 | 3.89 | 10.78 | 12.02 | 12.64 | 13.29 | 4.6740 | 3.7278 | 2.5098 | 1.0226 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 95629.75 | 326302.23 | 12.23 | 3.14 | 3.50 | 3.68 | 3.88 | 10.73 | 11.94 | 12.56 | 13.24 | 5.3849 | 4.3028 | 2.8979 | 1.1659 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.647 | 0.590 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.536 | 0.496 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.378 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.530 | 0.491 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.378 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.5514882806E-002 | 1.9689216801E-002 | Pass | Pass | 0.5243899040 | 0.5194269457 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1062953581 | 6.9401356415E-002 | Pass | Pass | 0.4946974666 | 0.4732046488 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.9388778264E-002 | 3.0508094771E-002 | Pass | Pass | 0.4981882530 | 0.4620497031 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.9124464942E-002 | 2.8640360022E-002 | Pass | Pass | 0.4949177050 | 0.4550967551 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.0177545056E-002 | 7.9612570323E-003 | Pass | Pass | 0.5609731637 | 0.5549769760 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.8796175427E-002 | 7.2541474686E-002 | Pass | Pass | 61.2570249477 | 420.6840009233 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3515119422 | 0.3421448351 | Pass | Pass | 47.5125633453 | 195.8496756598 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3762308116 | 0.3614238800 | Pass | Pass | 58.2855928407 | 197.8363676863 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3460387950 | 0.3411669788 | Pass | Pass | 57.4163292361 | 164.4301508214 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3777346222 | 0.3647909527 | Pass | Pass | 50.0749267781 | 141.3115530594 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2627071236 | 0.2417123966 | Pass | Pass | 26.0857624794 | 58.7119729284 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2716540962 | 0.2505450835 | Pass | Pass | 24.6609318648 | 51.7837575345 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2347351493 | 0.2254214201 | Pass | Pass | 30.8663228413 | 84.6518090301 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2725619645 | 0.2527356691 | Pass | Pass | 25.3351549267 | 53.2495877029 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2659185106 | 0.2517991222 | Pass | Pass | 39.6751644047 | 133.9470957425 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2731428912 | 0.2599566168 | Pass | Pass | 35.4478398391 | 115.3029161265 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2425238816 | 0.2406734851 | Pass | Pass | 36.6422662264 | 106.0701712476 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2744064930 | 0.2628917296 | Pass | Pass | 41.6762728665 | 152.5304884311 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3465.96 | 186.76 | 0.00 | 1643.77 | 660.78 | 5957.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.590 | 0.647 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.496 | 0.536 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.491 | 0.530 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.378 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.378 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.379 | 0.417 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.378 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.378 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.379 | 0.417 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.379 | 0.417 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.379 | 0.417 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.52 | 0.0000 | Y | 4.86 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.40 | 0.0000 | Y | 3.06 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.27 | 0.0000 | Y | 4.81 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.38 | 0.0000 | Y | 3.06 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 4.85 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.37 | 0.0000 | Y | 3.06 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.24 | 0.0000 | Y | 4.80 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.34 | 0.0000 | Y | 3.05 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.52 | 0.0000 | Y | 4.86 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.40 | 0.0000 | Y | 3.06 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.27 | 0.0000 | Y | 4.81 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.38 | 0.0000 | Y | 3.06 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 166.72 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.04 | 42.04 | 4.28 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.67 | 62.85 | 3.31 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.67 | 47.45 | 26.74 | |
Exterior Lighting Total | 3824.74 | 34.33 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 88592.87 | 67893.72 | 20699.15 | 0.77 | 3.74 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86246.78 | 65591.56 | 20655.22 | 0.76 | 3.74 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 96476.03 | 74505.18 | 21970.85 | 0.77 | 3.74 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 87871.0 | 3.15 | 10.75 | N/A | N/A | 12.27 | |
PACU_VAV_MID COOLING COIL | 85586.2 | 3.16 | 10.78 | N/A | N/A | 12.30 | |
PACU_VAV_TOP COOLING COIL | 95629.7 | 3.14 | 10.73 | N/A | N/A | 12.23 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20717.81 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 22406.60 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 39367.01 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19280.94 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12530.04 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19268.72 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12624.27 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14641.21 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9571.41 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14641.19 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9657.47 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15242.36 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9951.33 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15227.09 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10040.43 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 30354.97 | 0.84 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 30847.10 | 0.84 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 29903.91 | 0.84 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.31 | 9979.98 | 2313.39 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.15 | 9589.60 | 2313.39 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.78 | 10976.78 | 2298.46 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 87871.00 | 3.15 | 10.75 | 12.27 | 4.8643 | 3.51 | 11.98 | 3.8860 | 3.69 | 12.60 | 2.6173 | 3.89 | 13.27 | 1.0578 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85586.18 | 3.16 | 10.78 | 12.30 | 4.6740 | 3.52 | 12.02 | 3.7278 | 3.71 | 12.64 | 2.5098 | 3.89 | 13.29 | 1.0226 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95629.75 | 3.14 | 10.73 | 12.23 | 5.3849 | 3.50 | 11.94 | 4.3028 | 3.68 | 12.56 | 2.8979 | 3.88 | 13.24 | 1.1659 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 32383.43 | 32383.43 | 32.93 | 2.392 | 2.392 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 27124.41 | 27124.41 | 27.58 | 2.002 | 2.002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 27946.56 | 27946.56 | 28.41 | 2.083 | 2.083 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00893 | 30.21 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8751.13 | 8751.13 | 42.21 | 0.652 | 0.652 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00906 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10368.90 | 10368.90 | 78.99 | 0.773 | 0.773 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00882 | 25.71 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12728.45 | 12728.45 | 61.39 | 0.949 | 0.949 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00889 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11300.76 | 11300.76 | 86.10 | 0.842 | 0.842 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00879 | 28.84 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6752.78 | 6752.78 | 32.57 | 0.503 | 0.503 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00906 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8418.55 | 8418.55 | 64.14 | 0.627 | 0.627 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00880 | 26.24 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10077.08 | 10077.08 | 48.60 | 0.751 | 0.751 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00888 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8784.66 | 8784.66 | 66.93 | 0.655 | 0.655 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00878 | 28.38 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7638.25 | 7638.25 | 36.84 | 0.569 | 0.569 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00909 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10228.50 | 10228.50 | 77.92 | 0.762 | 0.762 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00880 | 25.45 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11644.82 | 11644.82 | 56.16 | 0.868 | 0.868 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00889 | 29.99 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10526.62 | 10526.62 | 80.20 | 0.785 | 0.785 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00879 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9134.84 | 9134.84 | 9.29 | 0.402 | 0.425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 15839.35 | 15839.35 | 16.10 | 0.688 | 0.688 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 27715.90 | 27715.90 | 28.18 | 1.209 | 1.209 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13537.04 | 13537.04 | 65.29 | 0.592 | 0.592 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8796.81 | 8796.81 | 67.02 | 0.385 | 0.385 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13528.48 | 13528.48 | 65.25 | 0.592 | 0.592 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8862.81 | 8862.81 | 67.52 | 0.388 | 0.388 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10285.67 | 10285.67 | 49.61 | 0.450 | 0.450 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6723.45 | 6723.45 | 51.22 | 0.294 | 0.294 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10285.65 | 10285.65 | 49.61 | 0.450 | 0.450 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6783.72 | 6783.72 | 51.68 | 0.297 | 0.297 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10707.61 | 10707.61 | 51.64 | 0.468 | 0.468 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6990.14 | 6990.14 | 53.25 | 0.306 | 0.306 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10696.92 | 10696.92 | 51.59 | 0.468 | 0.468 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7052.55 | 7052.55 | 53.73 | 0.308 | 0.308 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.31 | 4.31 | 1.91 | 1.91 | 4.3140 | 1.9146 | 4.3140 | 0.4438 | 0.3000 |
PACU_VAV_MID | 4.15 | 4.15 | 2.24 | 2.24 | 4.1453 | 2.2379 | 4.1453 | 0.5399 | 0.3000 |
PACU_VAV_TOP | 4.78 | 4.78 | 3.17 | 3.17 | 4.7757 | 3.1656 | 4.7757 | 0.6628 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20717.812 | 20717.812 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 20717.81 | 13828.02 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 9134.84 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 22406.601 | 22406.601 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22406.60 | 22406.60 | 0.688160 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 15839.35 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 39367.007 | 39367.007 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39367.01 | 39367.01 | 1.209054 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 27715.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19280.937 | 19280.937 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19280.94 | 19280.94 | 0.592163 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00749736 | 47.2963 | 13537.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12530.037 | 12530.037 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12530.04 | 12530.04 | 0.384827 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00748582 | 47.2246 | 8796.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19268.717 | 19268.717 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19268.72 | 19268.72 | 0.591788 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00749706 | 47.2944 | 13528.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12624.269 | 12624.269 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12624.27 | 12624.27 | 0.387721 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00748951 | 47.2476 | 8862.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14641.215 | 14641.215 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14641.21 | 14641.21 | 0.449666 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00761484 | 48.0257 | 10285.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9571.413 | 9571.413 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9571.41 | 9571.41 | 0.293961 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00761279 | 48.0130 | 6723.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14641.192 | 14641.192 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14641.19 | 14641.19 | 0.449666 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00761484 | 48.0257 | 10285.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9657.467 | 9657.467 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9657.47 | 9657.47 | 0.296604 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00761740 | 48.0417 | 6783.72 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 15242.356 | 15242.356 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15242.36 | 15242.36 | 0.468129 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00745821 | 47.0516 | 10707.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9951.333 | 9951.333 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9951.33 | 9951.33 | 0.305629 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00745081 | 47.0056 | 6990.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 15227.091 | 15227.091 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15227.09 | 15227.09 | 0.467660 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00745761 | 47.0478 | 10696.92 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10040.434 | 10040.434 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10040.43 | 10040.43 | 0.308365 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00745608 | 47.0385 | 7052.55 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 88592.868 | 67893.722 | 4.314011 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 90478.90 | 72495.25 | 4.314011 | 25.40 | 17.77 | 0.00990900 | 10.87 | 10.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.1627 | 24.00 | 0.00892435 | 46.8068 | 57880.88 | 0.00 | 91351.14 | 68071.72 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 30354.973 | 30354.973 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30354.97 | 30354.97 | 1.294203 | -7.08 | -7.08 | 0.00256089 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 73.8756 | 18.25 | 0.00715381 | 53.5586 | 15391.97 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 86246.785 | 65591.564 | 4.145263 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 88242.86 | 69899.61 | 4.145263 | 25.45 | 17.86 | 0.00999658 | 10.87 | 10.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 23.0649 | 24.00 | 0.00898483 | 47.1200 | 55562.01 | 0.00 | 88932.01 | 65770.55 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 30847.097 | 30847.097 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30847.10 | 30847.10 | 1.243579 | -8.23 | -8.23 | 0.00235372 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 76.8829 | 17.72 | 0.00712873 | 55.1886 | 15367.03 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 96476.031 | 74505.178 | 4.775709 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 98318.60 | 79518.99 | 4.775709 | 25.26 | 17.66 | 0.00983038 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 20.0201 | 24.00 | 0.00894297 | 46.9038 | 63952.32 | 0.00 | 99479.74 | 74690.63 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 29903.907 | 29903.907 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29903.91 | 29903.91 | 1.432713 | -4.89 | -4.89 | 0.00298486 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 66.7335 | 15.86 | 0.00727604 | 63.3685 | 15632.57 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20717.812 | 20717.812 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 20717.81 | 13828.02 | 1.0000 | 0.49855562 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20717.81 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.02 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 9134.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 22406.601 | 22406.601 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22406.60 | 22406.60 | 1.0000 | 0.80784812 | 0.688160 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22406.60 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 15839.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 39367.007 | 39367.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39367.01 | 39367.01 | 1.0000 | 1.41933899 | 1.209054 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39367.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 27715.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19280.937 | 19280.937 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19280.94 | 19280.94 | 1.0000 | 0.69515535 | 0.592163 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19280.94 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00749736 | 21.00 | 0.00749736 | 47.2963 | 13537.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12530.037 | 12530.037 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12530.04 | 12530.04 | 1.0000 | 0.45175826 | 0.384827 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12530.04 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00748582 | 21.00 | 0.00748582 | 47.2246 | 8796.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19268.717 | 19268.717 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19268.72 | 19268.72 | 1.0000 | 0.69471479 | 0.591788 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19268.72 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00749706 | 21.00 | 0.00749706 | 47.2944 | 13528.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12624.269 | 12624.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12624.27 | 12624.27 | 1.0000 | 0.45515569 | 0.387721 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12624.27 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00748951 | 21.00 | 0.00748951 | 47.2476 | 8862.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14641.215 | 14641.215 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14641.21 | 14641.21 | 1.0000 | 0.52787469 | 0.449666 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14641.21 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00761484 | 21.00 | 0.00761484 | 48.0257 | 10285.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9571.413 | 9571.413 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9571.41 | 9571.41 | 1.0000 | 0.34508796 | 0.293961 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9571.41 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00761279 | 21.00 | 0.00761279 | 48.0130 | 6723.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14641.192 | 14641.192 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14641.19 | 14641.19 | 1.0000 | 0.52787388 | 0.449666 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14641.19 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00761484 | 21.00 | 0.00761484 | 48.0257 | 10285.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9657.467 | 9657.467 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9657.47 | 9657.47 | 1.0000 | 0.34819054 | 0.296604 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9657.47 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00761740 | 21.00 | 0.00761740 | 48.0417 | 6783.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15242.356 | 15242.356 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15242.36 | 15242.36 | 1.0000 | 0.54954827 | 0.468129 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15242.36 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00745821 | 21.00 | 0.00745821 | 47.0516 | 10707.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9951.333 | 9951.333 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9951.33 | 9951.33 | 1.0000 | 0.35878558 | 0.305629 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9951.33 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00745081 | 21.00 | 0.00745081 | 47.0056 | 6990.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15227.091 | 15227.091 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15227.09 | 15227.09 | 1.0000 | 0.54899788 | 0.467660 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15227.09 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00745761 | 21.00 | 0.00745761 | 47.0478 | 10696.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10040.434 | 10040.434 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10040.43 | 10040.43 | 1.0000 | 0.36199805 | 0.308365 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10040.43 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00745608 | 21.00 | 0.00745608 | 47.0385 | 7052.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 88592.868 | 67893.722 | 4.314011 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2603 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.314011 | 5.06432720 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 90478.90 | 72495.25 | 1.0213 | 5.06432720 | 4.314011 | 25.40 | 17.77 | 0.00990900 | 50767.6 | 10.87 | 10.87 | 0.00850000 | 32356.6 | -999.0 | -999.00 | -999.00 | -999.00 | 9979.976 | 80498.93 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 22.1627 | 24.00 | 0.00892435 | 24.00 | 0.00892435 | 46.8068 | 57880.88 | 0.00 | 91351.14 | 68071.72 | 4.86432456 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.98 | 12.97 | 0.00930828 | 36542.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30354.973 | 30354.973 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.314011 | 5.06432720 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30354.97 | 30354.97 | 1.0000 | 1.51929816 | 1.294203 | -7.08 | -7.08 | 0.00256089 | -746.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30354.97 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 73.8756 | 18.98 | 0.00718949 | 18.25 | 0.00715381 | 53.5586 | 15391.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86246.785 | 65591.564 | 4.145263 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4231 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.145263 | 4.86622876 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 88242.86 | 69899.61 | 1.0231 | 4.86622876 | 4.145263 | 25.45 | 17.86 | 0.00999658 | 51050.3 | 10.87 | 10.87 | 0.00850000 | 32356.9 | -999.0 | -999.00 | -999.00 | -999.00 | 9589.595 | 78653.26 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 23.0649 | 24.00 | 0.00898483 | 24.00 | 0.00898483 | 47.1200 | 55562.01 | 0.00 | 88932.01 | 65770.55 | 4.67404951 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.90 | 12.87 | 0.00924179 | 36295.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30847.097 | 30847.097 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.145263 | 4.86622876 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30847.10 | 30847.10 | 1.0000 | 1.45986863 | 1.243579 | -8.23 | -8.23 | 0.00235372 | -2417.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30847.10 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 76.8829 | 18.62 | 0.00710838 | 17.72 | 0.00712873 | 55.1886 | 15367.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 96476.031 | 74505.178 | 4.775709 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1142 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.775709 | 5.60632614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 98318.60 | 79518.99 | 1.0191 | 5.60632614 | 4.775709 | 25.26 | 17.66 | 0.00983038 | 50431.4 | 10.89 | 10.89 | 0.00850000 | 32369.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10976.784 | 87341.81 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 20.0201 | 24.00 | 0.00894297 | 24.00 | 0.00894297 | 46.9038 | 63952.32 | 0.00 | 99479.74 | 74690.63 | 5.38491864 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.10 | 13.09 | 0.00937976 | 36848.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29903.907 | 29903.907 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.775709 | 5.60632614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29903.91 | 29903.91 | 1.0000 | 1.68189784 | 1.432713 | -4.89 | -4.89 | 0.00298486 | 2520.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29903.91 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 66.7335 | 17.99 | 0.00711884 | 15.86 | 0.00727604 | 63.3685 | 15632.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.31 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.15 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.78 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2001.83 | 3179.17 | 308.83 |
CORE_MID | 2476.67 | 3580.83 | 1051.17 |
CORE_TOP | 2987.33 | 3839.83 | 1668.33 |
PERIMETER_TOP_ZN_3 | 3598.33 | 4109.33 | 2359.67 |
PERIMETER_TOP_ZN_2 | 3786.33 | 3808.83 | 2230.67 |
PERIMETER_TOP_ZN_1 | 3487.50 | 3779.33 | 1973.00 |
PERIMETER_TOP_ZN_4 | 3759.50 | 3946.33 | 2268.17 |
PERIMETER_BOT_ZN_3 | 3287.50 | 4212.17 | 2141.67 |
PERIMETER_BOT_ZN_2 | 3545.50 | 3753.00 | 1933.67 |
PERIMETER_BOT_ZN_1 | 3319.33 | 4099.50 | 1980.33 |
PERIMETER_BOT_ZN_4 | 3525.00 | 3826.00 | 1973.83 |
PERIMETER_MID_ZN_3 | 3368.17 | 3929.33 | 2038.67 |
PERIMETER_MID_ZN_2 | 3040.50 | 3174.33 | 1711.00 |
PERIMETER_MID_ZN_1 | 3249.50 | 3534.00 | 1611.67 |
PERIMETER_MID_ZN_4 | 3557.83 | 3743.17 | 1956.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4710.00 | 4660.67 | 2709.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.67 | 0.00 | 1.50 | 0.00 |
CORE_MID | 3.33 | 0.00 | 2.83 | 0.00 |
CORE_TOP | 8.17 | 0.00 | 5.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 123.67 | 2.50 | 55.33 | 2.17 |
PERIMETER_TOP_ZN_2 | 77.17 | 22.83 | 12.33 | 22.33 |
PERIMETER_TOP_ZN_1 | 62.83 | 21.83 | 9.33 | 21.17 |
PERIMETER_TOP_ZN_4 | 79.83 | 28.67 | 14.67 | 18.33 |
PERIMETER_BOT_ZN_3 | 42.50 | 0.00 | 31.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 10.33 | 7.33 | 0.67 | 7.33 |
PERIMETER_BOT_ZN_1 | 360.17 | 7.17 | 354.67 | 7.17 |
PERIMETER_BOT_ZN_4 | 11.00 | 17.00 | 0.67 | 10.00 |
PERIMETER_MID_ZN_3 | 47.50 | 0.00 | 21.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25.50 | 21.00 | 0.50 | 21.00 |
PERIMETER_MID_ZN_1 | 18.33 | 18.67 | 1.00 | 18.67 |
PERIMETER_MID_ZN_4 | 26.50 | 25.50 | 0.50 | 16.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 479.00 | 97.67 | 386.33 | 79.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.775 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.646 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.645 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.755 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.073 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 1.023 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.030 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.637 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.922 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.851 | 0.877 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.874 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.734 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.961 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 1.006 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.996 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.75 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12274125.97 | 0.00 | 12274125.97 | 0.00 | 12274125.97 | 13393058.27 | 5137.14 | 901.88 | 2720.99 | 116.41 |
CORE_MID | 10289222.75 | 0.00 | 10289222.75 | 0.00 | 10289222.75 | 13393058.27 | 4975.49 | 1323.21 | 2461.31 | 164.38 |
CORE_TOP | 10285174.01 | 0.00 | 10285174.01 | 0.00 | 10285174.01 | 13393058.27 | 5079.09 | 1274.34 | 2406.57 | 97.42 |
PERIMETER_TOP_ZN_3 | 2532391.24 | 0.00 | 2532391.24 | 750436.27 | 3282827.51 | 2823374.22 | 4405.11 | 1223.66 | 3131.23 | 97.42 |
PERIMETER_TOP_ZN_2 | 2268567.81 | 0.00 | 2268567.81 | 500287.84 | 2768855.65 | 1787429.43 | 4421.78 | 1259.13 | 3079.09 | 97.42 |
PERIMETER_TOP_ZN_1 | 3420250.21 | 0.00 | 3420250.21 | 750436.27 | 4170686.48 | 2823374.22 | 4341.56 | 1159.49 | 3258.95 | 97.42 |
PERIMETER_TOP_ZN_4 | 2195261.87 | 0.00 | 2195261.87 | 500287.84 | 2695549.71 | 1787312.18 | 4373.67 | 1221.31 | 3165.01 | 97.42 |
PERIMETER_BOT_ZN_3 | 2136527.50 | 0.00 | 2136527.50 | 399002.08 | 2535529.58 | 2823374.22 | 5165.66 | 849.29 | 2745.05 | 116.41 |
PERIMETER_BOT_ZN_2 | 1948969.36 | 0.00 | 1948969.36 | 265999.79 | 2214969.15 | 1787429.43 | 4885.19 | 663.82 | 3210.99 | 116.41 |
PERIMETER_BOT_ZN_1 | 2852940.93 | 0.00 | 2852940.93 | 3134132.70 | 5987073.63 | 2823374.22 | 4512.45 | 729.74 | 3517.81 | 116.41 |
PERIMETER_BOT_ZN_4 | 1853461.34 | 0.00 | 1853461.34 | 265999.79 | 2119461.12 | 1787312.18 | 4926.46 | 812.88 | 3020.65 | 116.41 |
PERIMETER_MID_ZN_3 | 2462052.46 | 0.00 | 2462052.46 | 624679.86 | 3086732.32 | 2823374.22 | 4482.81 | 1256.24 | 3020.95 | 164.38 |
PERIMETER_MID_ZN_2 | 2059296.58 | 0.00 | 2059296.58 | 416450.74 | 2475747.31 | 1601953.02 | 4282.22 | 723.67 | 3754.11 | 1073.38 |
PERIMETER_MID_ZN_1 | 3363343.25 | 0.00 | 3363343.25 | 624679.86 | 3988023.11 | 2823374.22 | 4331.87 | 1160.80 | 3267.33 | 164.38 |
PERIMETER_MID_ZN_4 | 2117968.17 | 0.00 | 2117968.17 | 416450.74 | 2534418.91 | 1787312.18 | 4516.79 | 1341.19 | 2902.02 | 164.38 |
Total Facility | 62059553.45 | 0.00 | 62059553.45 | 8648843.76 | 70708397.21 | 67658168.57 | 5915.72 | 1791.56 | 4368.94 | 1152.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5692 | 0.0000 | 0.5692 | 0.0000 | 0.5692 | 0.4247 | 2353.99 | 901.88 | 2687.14 |
CORE_MID | 0.4752 | 0.0000 | 0.4752 | 0.0000 | 0.4752 | 0.4247 | 2203.32 | 1323.04 | 2416.64 |
CORE_TOP | 0.4747 | 0.0000 | 0.4747 | 0.0000 | 0.4747 | 0.4247 | 2317.25 | 1274.09 | 2351.65 |
PERIMETER_TOP_ZN_3 | 0.1171 | 0.0000 | 0.1171 | 0.0178 | 0.1349 | 0.0895 | 1643.28 | 1223.41 | 3076.31 |
PERIMETER_TOP_ZN_2 | 0.1052 | 0.0000 | 0.1052 | 0.0119 | 0.1171 | 0.0567 | 1659.95 | 1258.88 | 3024.17 |
PERIMETER_TOP_ZN_1 | 0.1586 | 0.0000 | 0.1586 | 0.0178 | 0.1764 | 0.0895 | 1579.72 | 1159.41 | 3203.87 |
PERIMETER_TOP_ZN_4 | 0.1010 | 0.0000 | 0.1010 | 0.0119 | 0.1129 | 0.0567 | 1611.84 | 1221.06 | 3110.09 |
PERIMETER_BOT_ZN_3 | 0.0989 | 0.0000 | 0.0989 | 0.0095 | 0.1084 | 0.0895 | 2382.50 | 849.29 | 2711.20 |
PERIMETER_BOT_ZN_2 | 0.0905 | 0.0000 | 0.0905 | 0.0063 | 0.0968 | 0.0567 | 2102.04 | 663.82 | 3177.14 |
PERIMETER_BOT_ZN_1 | 0.1324 | 0.0000 | 0.1324 | 0.1373 | 0.2697 | 0.0895 | 1729.30 | 729.74 | 3483.97 |
PERIMETER_BOT_ZN_4 | 0.0857 | 0.0000 | 0.0857 | 0.0063 | 0.0921 | 0.0567 | 2143.31 | 812.88 | 2986.81 |
PERIMETER_MID_ZN_3 | 0.1138 | 0.0000 | 0.1138 | 0.0148 | 0.1287 | 0.0895 | 1710.64 | 1256.08 | 2976.28 |
PERIMETER_MID_ZN_2 | 0.0943 | 0.0000 | 0.0943 | 0.0105 | 0.1048 | 0.0567 | 1510.18 | 723.48 | 2800.34 |
PERIMETER_MID_ZN_1 | 0.1560 | 0.0000 | 0.1560 | 0.0148 | 0.1708 | 0.0895 | 1559.70 | 1160.64 | 3222.66 |
PERIMETER_MID_ZN_4 | 0.0977 | 0.0000 | 0.0977 | 0.0099 | 0.1075 | 0.0567 | 1744.75 | 1340.86 | 2857.39 |
Total Facility | 2.8702 | 0.0000 | 2.8702 | 0.2687 | 3.1389 | 2.1513 | 3120.74 | 1791.12 | 4300.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29031059.28 | 0.00 | 29031059.28 | 22614548.33 | 4139.05 | 1.67 | 4619.28 | 116.41 |
PACU_VAV_MID | 27964258.21 | 0.00 | 27964258.21 | 22429071.92 | 4092.43 | 0.79 | 4666.78 | 164.38 |
PACU_VAV_TOP | 28528852.29 | 0.00 | 28528852.29 | 22614548.33 | 4092.99 | 1.90 | 4665.11 | 96.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3460 | 0.0000 | 1.3460 | 0.7171 | 1355.90 | 1.67 | 4585.43 |
PACU_VAV_MID | 1.2927 | 0.0000 | 1.2927 | 0.7084 | 1320.26 | 0.79 | 4621.95 |
PACU_VAV_TOP | 1.3183 | 0.0000 | 1.3183 | 0.7171 | 1331.24 | 1.90 | 4609.86 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 87.92 | 2436.82 | 0.00 | 0.00 | 0.00 | 2328.13 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 69.39 | 2468.28 | 0.00 | 0.00 | 0.00 | 2409.80 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 51.26 | 2425.34 | 0.00 | 0.00 | 0.00 | 2416.08 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2963 | 2.3370 | 0.0000 | 0.0000 | 0.0000 | 1.0587 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3082 | 2.2323 | 0.0000 | 0.0000 | 0.0000 | 1.0173 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2136 | 2.2692 | 0.0000 | 0.0000 | 0.0000 | 1.0297 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1278.42 | 11240.73 | 26-MAR-17:10 | 222211.27 | 02-JAN-07:10 |
Electricity:Building | 814.47 | 11072.20 | 26-MAR-17:10 | 57855.99 | 02-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 814.47 | 11072.20 | 26-MAR-17:10 | 57855.99 | 02-NOV-07:10 |
InteriorLights:Electricity | 166.72 | 772.31 | 01-JAN-10:30 | 17672.30 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 166.72 | 772.31 | 01-JAN-10:30 | 17672.30 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 166.72 | 772.31 | 01-JAN-10:30 | 17672.30 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 166.72 | 772.31 | 01-JAN-10:30 | 17672.30 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.19 | 405.59 | 12-MAR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.86 | 19.49 | 01-JAN-10:30 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.86 | 19.49 | 01-JAN-10:30 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.46 | 256.76 | 26-MAR-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.14 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.81 | 19.49 | 01-JAN-09:10 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.81 | 19.49 | 01-JAN-09:10 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.46 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.06 | 12.34 | 01-JAN-10:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.06 | 12.34 | 01-JAN-10:00 | 465.57 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.18 | 405.59 | 12-MAR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.85 | 19.49 | 01-JAN-10:20 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.85 | 19.49 | 01-JAN-10:20 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.46 | 256.76 | 26-MAR-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.13 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.80 | 19.49 | 01-JAN-09:10 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.80 | 19.49 | 01-JAN-09:10 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.46 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.05 | 12.34 | 01-JAN-10:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.05 | 12.34 | 01-JAN-10:00 | 465.57 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.19 | 405.59 | 12-MAR-17:10 | 2170.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.86 | 19.49 | 01-JAN-10:30 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.86 | 19.49 | 01-JAN-10:30 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.46 | 256.76 | 26-MAR-17:10 | 1374.17 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 465.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.06 | 12.34 | 01-JAN-09:10 | 465.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.14 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.81 | 19.49 | 01-JAN-09:10 | 735.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.81 | 19.49 | 01-JAN-09:10 | 735.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.46 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.06 | 12.34 | 01-JAN-10:00 | 465.57 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.06 | 12.34 | 01-JAN-10:00 | 465.57 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 130.97 | 0.00 | 01-JAN-00:10 | 26813.75 | 14-JUN-12:00 |
ElectricityProduced:Plant | 130.97 | 0.00 | 01-JAN-00:10 | 26813.75 | 14-JUN-12:00 |
Photovoltaic:ElectricityProduced | 137.14 | 0.00 | 01-JAN-00:10 | 28141.87 | 14-JUN-12:20 |
PowerConversion:ElectricityProduced | -6.17 | -1328.12 | 14-JUN-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:20 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 429.49 | 168.53 | 26-MAR-17:10 | 194142.90 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.45 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.45 | 02-NOV-07:20 |
ElectricityPurchased:Facility | 1148.55 | 0.00 | 05-MAR-10:10 | 222211.27 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1148.55 | 0.00 | 05-MAR-10:10 | 222211.27 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1148.55 | 0.00 | 05-MAR-10:10 | 222211.27 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1148.55 | 0.00 | 05-MAR-10:10 | 222211.27 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 1.10 | 0.00 | 01-JAN-00:10 | 10841.53 | 21-MAY-12:00 |
ElectricitySurplusSold:Plant | 1.10 | 0.00 | 01-JAN-00:10 | 10841.53 | 21-MAY-12:00 |
Cogeneration:ElectricitySurplusSold | 1.10 | 0.00 | 01-JAN-00:10 | 10841.53 | 21-MAY-12:00 |
General:Cogeneration:ElectricitySurplusSold | 1.10 | 0.00 | 01-JAN-00:10 | 10841.53 | 21-MAY-12:00 |
ElectricityNet:Facility | 1147.45 | -10841.53 | 21-MAY-12:00 | 222211.27 | 02-JAN-07:10 |
ElectricityNet:Plant | 1147.45 | -10841.53 | 21-MAY-12:00 | 222211.27 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1147.45 | -10841.53 | 21-MAY-12:00 | 222211.27 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1147.45 | -10841.53 | 21-MAY-12:00 | 222211.27 | 02-JAN-07:10 |
Heating:Electricity | 227.06 | 0.00 | 01-JAN-00:40 | 187169.61 | 02-JAN-07:10 |
General:Heating:Electricity | 227.06 | 0.00 | 01-JAN-00:40 | 187169.61 | 02-JAN-07:10 |
Fans:Electricity | 78.50 | 0.00 | 01-JAN-00:40 | 25608.98 | 17-JUL-10:50 |
General:Fans:Electricity | 78.50 | 0.00 | 01-JAN-00:40 | 25608.98 | 17-JUL-10:50 |
ExteriorLights:Electricity | 34.33 | 0.00 | 01-JAN-08:00 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.33 | 0.00 | 01-JAN-08:00 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 112.31 | 0.00 | 01-JAN-00:10 | 61233.50 | 14-AUG-11:00 |
General:Cooling:Electricity | 112.31 | 0.00 | 01-JAN-00:10 | 61233.50 | 14-AUG-11:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:20 |
WIRED_LTG_ELECTRICITY | 4.68 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 404.67 | 1886.44 | 06-FEB-06:00 | 116722.72 | 06-FEB-08:20 |
NaturalGas:HVAC | 269.30 | 0.00 | 01-JAN-00:40 | 108459.50 | 07-FEB-07:20 |
Heating:NaturalGas | 269.30 | 0.00 | 01-JAN-00:40 | 108459.50 | 07-FEB-07:20 |
General:Heating:NaturalGas | 269.30 | 0.00 | 01-JAN-00:40 | 108459.50 | 07-FEB-07:20 |
NaturalGas:Plant | 135.38 | 1886.44 | 02-JAN-18:10 | 11209.95 | 08-FEB-12:30 |
WaterSystems:NaturalGas | 135.38 | 1886.44 | 02-JAN-18:10 | 11209.95 | 08-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 135.38 | 1886.44 | 02-JAN-18:10 | 11209.95 | 08-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1950.67 | 0.00 | 01-JAN-00:40 | 426708.40 | 17-JUL-07:50 |
EnergyTransfer:Building | 939.14 | 0.00 | 01-JAN-00:40 | 182599.10 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 157.59 | 0.00 | 01-JAN-00:40 | 21189.97 | 17-JUL-08:00 |
Heating:EnergyTransfer | 199.82 | 0.00 | 01-JAN-00:40 | 182599.10 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.61 | 0.00 | 01-JAN-00:10 | 16544.54 | 02-JAN-07:00 |
General:Heating:EnergyTransfer | 199.82 | 0.00 | 01-JAN-00:40 | 182599.10 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.61 | 0.00 | 01-JAN-00:10 | 16544.54 | 02-JAN-07:00 |
Cooling:EnergyTransfer | 739.32 | 0.00 | 01-JAN-00:40 | 143897.76 | 17-JUL-13:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 156.98 | 0.00 | 01-JAN-00:40 | 21189.97 | 17-JUL-08:00 |
General:Cooling:EnergyTransfer | 739.32 | 0.00 | 01-JAN-00:40 | 143897.76 | 17-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 156.98 | 0.00 | 01-JAN-00:40 | 21189.97 | 17-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.38 | 0.00 | 01-JAN-00:40 | 14594.79 | 06-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.80 | 0.00 | 01-JAN-00:40 | 14594.79 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.80 | 0.00 | 01-JAN-00:40 | 14594.79 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.58 | 0.00 | 01-JAN-00:10 | 9342.37 | 12-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.58 | 0.00 | 01-JAN-00:10 | 9342.37 | 12-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.22 | 0.00 | 01-JAN-00:40 | 8641.72 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.62 | 0.00 | 01-JAN-00:40 | 8641.72 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.62 | 0.00 | 01-JAN-00:40 | 8641.72 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.60 | 0.00 | 01-JAN-00:10 | 5159.73 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.60 | 0.00 | 01-JAN-00:10 | 5159.73 | 17-JUL-07:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.65 | 0.00 | 01-JAN-00:40 | 7296.87 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.74 | 0.00 | 01-JAN-00:40 | 7296.87 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.74 | 0.00 | 01-JAN-00:40 | 7296.87 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.90 | 0.00 | 01-JAN-00:10 | 4737.46 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.90 | 0.00 | 01-JAN-00:10 | 4737.46 | 17-JUL-07:10 |
EnergyTransfer:Zone:CORE_MID | 121.59 | 0.00 | 01-JAN-00:40 | 19130.73 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.75 | 0.00 | 01-JAN-00:20 | 19130.73 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.75 | 0.00 | 01-JAN-00:20 | 19130.73 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 118.84 | 0.00 | 01-JAN-00:10 | 17844.29 | 17-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 118.84 | 0.00 | 01-JAN-00:10 | 17844.29 | 17-JUL-08:00 |
EnergyTransfer:Zone:CORE_TOP | 120.68 | 0.00 | 01-JAN-00:40 | 26565.44 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 11.67 | 0.00 | 01-JAN-00:40 | 26565.44 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 11.67 | 0.00 | 01-JAN-00:40 | 26565.44 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 109.01 | 0.00 | 01-JAN-00:10 | 19094.91 | 17-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 109.01 | 0.00 | 01-JAN-00:10 | 19094.91 | 17-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.16 | 0.00 | 01-JAN-00:40 | 9413.99 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.47 | 0.00 | 01-JAN-00:40 | 9413.99 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.47 | 0.00 | 01-JAN-00:40 | 9413.99 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.68 | 0.00 | 01-JAN-00:10 | 6594.21 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.68 | 0.00 | 01-JAN-00:10 | 6594.21 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 34.87 | 0.00 | 01-JAN-00:40 | 9428.70 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.20 | 0.00 | 01-JAN-00:40 | 9428.70 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.20 | 0.00 | 01-JAN-00:40 | 9428.70 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.67 | 0.00 | 01-JAN-00:10 | 8649.57 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.67 | 0.00 | 01-JAN-00:10 | 8649.57 | 17-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.64 | 0.00 | 01-JAN-00:40 | 12542.08 | 26-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 14.19 | 0.00 | 01-JAN-00:40 | 12542.08 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 14.19 | 0.00 | 01-JAN-00:40 | 12542.08 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 37.45 | 0.00 | 01-JAN-00:10 | 11903.55 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 37.45 | 0.00 | 01-JAN-00:10 | 11903.55 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.44 | 0.00 | 01-JAN-00:40 | 9634.52 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.05 | 0.00 | 01-JAN-00:40 | 9634.52 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.05 | 0.00 | 01-JAN-00:40 | 9634.52 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.39 | 0.00 | 01-JAN-00:10 | 8761.05 | 18-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.39 | 0.00 | 01-JAN-00:10 | 8761.05 | 18-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.23 | 0.00 | 01-JAN-00:40 | 6761.60 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.23 | 0.00 | 01-JAN-00:40 | 6761.60 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 12.23 | 0.00 | 01-JAN-00:40 | 6761.60 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.00 | 0.00 | 01-JAN-00:10 | 5173.34 | 14-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.00 | 0.00 | 01-JAN-00:10 | 5173.34 | 14-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.51 | 0.00 | 01-JAN-00:40 | 7041.60 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.50 | 0.00 | 01-JAN-00:40 | 7041.60 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.50 | 0.00 | 01-JAN-00:40 | 7041.60 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.01 | 0.00 | 01-JAN-00:10 | 6773.97 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.01 | 0.00 | 01-JAN-00:10 | 6773.97 | 17-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.02 | 0.00 | 01-JAN-00:40 | 13198.99 | 07-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.15 | 0.00 | 01-JAN-00:40 | 13198.99 | 07-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.15 | 0.00 | 01-JAN-00:40 | 13198.99 | 07-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.87 | 0.00 | 01-JAN-00:10 | 10563.25 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.87 | 0.00 | 01-JAN-00:10 | 10563.25 | 10-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.38 | 0.00 | 01-JAN-00:40 | 7133.47 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.04 | 0.00 | 01-JAN-00:40 | 7133.47 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.04 | 0.00 | 01-JAN-00:40 | 7133.47 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.34 | 0.00 | 01-JAN-00:10 | 6939.44 | 04-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.34 | 0.00 | 01-JAN-00:10 | 6939.44 | 04-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.93 | 0.00 | 01-JAN-00:40 | 8010.82 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 11.19 | 0.00 | 01-JAN-00:40 | 8010.82 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 11.19 | 0.00 | 01-JAN-00:40 | 8010.82 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.74 | 0.00 | 01-JAN-00:10 | 5975.85 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.74 | 0.00 | 01-JAN-00:10 | 5975.85 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.41 | 0.00 | 01-JAN-00:40 | 8609.93 | 03-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 6.31 | 0.00 | 01-JAN-00:40 | 7378.61 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 6.31 | 0.00 | 01-JAN-00:40 | 7378.61 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.10 | 0.00 | 01-JAN-00:10 | 8609.93 | 03-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.10 | 0.00 | 01-JAN-00:10 | 8609.93 | 03-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 46.63 | 0.00 | 01-JAN-00:40 | 11661.64 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.47 | 0.00 | 01-JAN-00:40 | 10411.00 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.47 | 0.00 | 01-JAN-00:40 | 10411.00 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 39.16 | 0.00 | 01-JAN-00:10 | 11661.64 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 39.16 | 0.00 | 01-JAN-00:10 | 11661.64 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.82 | 0.00 | 01-JAN-00:40 | 8391.28 | 03-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.83 | 0.00 | 01-JAN-00:40 | 7331.76 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.83 | 0.00 | 01-JAN-00:40 | 7331.76 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.99 | 0.00 | 01-JAN-00:10 | 8391.28 | 03-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.99 | 0.00 | 01-JAN-00:10 | 8391.28 | 03-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 52.88 | 0.00 | 01-JAN-00:10 | 6712.83 | 16-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6712.83 | 16-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6712.83 | 16-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6712.83 | 16-FEB-12:30 |
EnergyTransfer:HVAC | 958.65 | 0.00 | 01-JAN-00:40 | 298952.43 | 14-AUG-10:10 |
HeatingCoils:EnergyTransfer | 453.27 | 0.00 | 01-JAN-00:40 | 256394.33 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 505.38 | 0.00 | 01-JAN-00:10 | 298952.43 | 14-AUG-10:10 |
EnergyTransfer:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6712.83 | 16-FEB-12:30 |
WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6712.83 | 16-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6712.83 | 16-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.609 | -156.984 | 0.000 | 0.000 | 33.749 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -95.654 |
CORE_MID | 0.000 | 0.000 | 2.748 | -118.837 | 0.000 | 0.000 | 34.817 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -73.949 |
CORE_TOP | 0.000 | 0.000 | 11.667 | -109.014 | 0.000 | 0.000 | 35.380 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -93.254 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 19.473 | -23.682 | 0.000 | 0.000 | 7.600 | 4.862 | 24.333 | 16.801 | 0.000 | 0.061 | 0.001 | 0.000 | -34.006 | 0.000 | -11.749 | -3.692 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 11.195 | -23.672 | 0.000 | 0.000 | 4.746 | 3.061 | 15.404 | 30.919 | 0.000 | 0.039 | 0.001 | 0.000 | -21.468 | 0.000 | -7.938 | -12.286 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 14.189 | -37.453 | 0.000 | 0.000 | 7.442 | 4.805 | 24.332 | 57.558 | 0.000 | 0.058 | 0.001 | 0.000 | -32.215 | 0.000 | -12.123 | -26.595 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 12.048 | -23.393 | 0.000 | 0.000 | 4.780 | 3.057 | 15.403 | 31.050 | 0.000 | 0.039 | 0.001 | 0.000 | -22.274 | 0.000 | -7.977 | -12.733 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 12.227 | -20.005 | 0.000 | 0.000 | 7.595 | 4.852 | 24.333 | 17.243 | 0.000 | 0.040 | 0.001 | 0.000 | -34.786 | 0.000 | -6.486 | -5.012 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.501 | -21.006 | 0.000 | 0.000 | 4.726 | 3.057 | 15.404 | 31.157 | 0.000 | 0.022 | 0.000 | 0.000 | -22.276 | 0.000 | -4.434 | -13.151 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 27.147 | -26.869 | 0.000 | 0.000 | 7.657 | 4.799 | 24.332 | 58.505 | 0.000 | 0.790 | 0.000 | 0.000 | -33.169 | 0.000 | -44.771 | -18.420 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 7.042 | -20.340 | 0.000 | 0.000 | 4.756 | 3.052 | 15.403 | 31.378 | 0.000 | 0.022 | 0.000 | 0.000 | -23.119 | 0.000 | -4.453 | -13.741 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 11.190 | -24.735 | 0.000 | 0.000 | 7.534 | 4.862 | 24.333 | 16.620 | 0.000 | 0.053 | 5.831 | 0.000 | -35.502 | 0.000 | -10.187 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 6.314 | -23.095 | 0.000 | 0.000 | 3.478 | 3.061 | 15.404 | 30.694 | 0.000 | 0.032 | 0.000 | 0.000 | -22.387 | 0.000 | -6.885 | -6.615 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 7.472 | -39.156 | 0.000 | 0.000 | 7.368 | 4.805 | 24.332 | 57.325 | 0.000 | 0.050 | 0.001 | 0.000 | -33.666 | 0.000 | -10.530 | -18.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 6.827 | -23.993 | 0.000 | 0.000 | 4.737 | 3.057 | 15.403 | 30.944 | 0.000 | 0.033 | 0.000 | 0.000 | -23.258 | 0.000 | -6.914 | -6.837 |
TOPFLOOR_PLENUM | 23.803 | -21.582 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.049 | 15.724 | 0.000 | 0.000 | 0.000 | -17.994 | -0.001 |
MIDFLOOR_PLENUM | 11.623 | -11.596 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.074 | 17.384 | 0.000 | 0.000 | 0.000 | -17.484 | -0.002 |
FIRSTFLOOR_PLENUM | 7.745 | -13.903 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.059 | 20.150 | 0.000 | 0.000 | 0.000 | -14.051 | -0.001 |
Total Facility | 43.171 | -47.081 | 156.651 | -692.233 | 0.000 | 0.000 | 176.366 | 166.716 | 647.750 | 410.193 | 0.000 | 1.422 | 59.094 | 0.000 | -338.126 | 0.000 | -183.977 | -399.945 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-SEP-05:12 | 0.00 | 0.00 | 0.00 | -34634.83 | 0.00 | 0.00 | 324.96 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 29874.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-SEP-05:12 | 0.00 | 0.00 | 0.00 | -29043.51 | 0.00 | 0.00 | 331.15 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 25298.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-JUL-05:12 | 0.00 | 0.00 | 0.00 | -30214.02 | 0.00 | 0.00 | 331.14 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 26469.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-13:32 | 0.00 | 0.00 | 0.00 | -10317.01 | 0.00 | 0.00 | 27.71 | 19.49 | 478.42 | 4165.88 | 0.00 | 53.24 | 5572.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:02 | 0.00 | 0.00 | 0.00 | -13177.35 | 0.00 | 0.00 | 13.78 | 12.34 | 302.86 | 10876.73 | 0.00 | 0.00 | 2132.55 | 0.00 | -0.00 | 0.00 | -160.90 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:32 | 0.00 | 0.00 | 0.00 | -16901.24 | 0.00 | 0.00 | 23.99 | 19.49 | 478.41 | 13675.35 | 0.00 | 0.00 | 3155.29 | 0.00 | -0.00 | 0.00 | -451.29 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:12 | 0.00 | 0.00 | 0.00 | -15014.85 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 11815.61 | 0.00 | 0.00 | 3045.76 | 0.00 | -0.00 | 0.00 | -103.27 | 0.00 |
PERIMETER_BOT_ZN_3 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -5578.42 | 0.00 | 0.00 | 149.01 | 127.81 | 637.89 | 337.69 | 0.00 | 0.00 | 4341.61 | 0.00 | -0.00 | 0.00 | -15.59 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-10:12 | 0.00 | 0.00 | 0.00 | -10731.62 | 0.00 | 0.00 | 16.45 | 12.34 | 302.86 | 6530.30 | 0.00 | 0.00 | 3938.04 | 0.00 | -0.00 | 0.00 | -68.36 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:43 | 0.00 | 0.00 | 0.00 | -12756.29 | 0.00 | 0.00 | 26.47 | 19.49 | 478.41 | 9681.43 | 0.00 | 0.00 | 2767.51 | 0.00 | -0.00 | 0.00 | -217.02 | 0.00 |
PERIMETER_BOT_ZN_4 | 16-JUL-16:41 | 0.00 | 0.00 | 0.00 | -11128.47 | 0.00 | 0.00 | 15.69 | 12.34 | 302.86 | 9927.07 | 0.00 | 13.81 | 856.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-16:31 | 0.00 | 0.00 | 0.00 | -8731.15 | 0.00 | 0.00 | 29.70 | 19.49 | 478.42 | 2165.26 | 0.00 | 52.44 | 5985.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 11-JUN-09:32 | 0.00 | 0.00 | 0.00 | -13286.83 | 0.00 | 0.00 | 15.24 | 12.34 | 302.86 | 8936.88 | 0.00 | 0.00 | 4171.76 | 0.00 | -0.00 | 0.00 | -152.24 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-11:43 | 0.00 | 0.00 | 0.00 | -14905.31 | 0.00 | 0.00 | 25.52 | 19.49 | 478.41 | 14941.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -337.80 | -221.93 |
PERIMETER_MID_ZN_4 | 11-JUN-16:11 | 0.00 | 0.00 | 0.00 | -14477.12 | 0.00 | 0.00 | 13.92 | 12.34 | 302.86 | 11052.40 | 0.00 | 0.00 | 3208.59 | 0.00 | -0.00 | 0.00 | -112.98 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:30 | 0.00 | -9342.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 9199.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-06:15 | 0.00 | -5956.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5989.69 | 0.00 | -0.00 | 0.00 | -32.91 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-06:15 | 0.00 | -5690.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5714.23 | 0.00 | -0.00 | 0.00 | -23.81 | 0.00 |
Total Facility | 07-AUG-06:03 | 0.00 | -7694.53 | 0.00 | -158552.12 | 0.00 | 0.00 | 3480.52 | 4748.28 | 18346.02 | 2996.03 | 0.00 | 0.00 | 139784.33 | 0.00 | 0.00 | 0.00 | -3108.54 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 19140.95 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 3464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22992.78 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 21995.47 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24825.16 |
CORE_TOP | 26-DEC-05:01 | 0.00 | 0.00 | 29851.04 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32680.73 |
PERIMETER_TOP_ZN_3 | 06-FEB-03:22 | 0.00 | 0.00 | 10288.22 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3421.65 | 0.00 | -2370.15 | -5052.07 |
PERIMETER_TOP_ZN_2 | 26-DEC-04:22 | 0.00 | 0.00 | 11944.76 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2044.14 | 0.00 | -1656.61 | -8595.77 |
PERIMETER_TOP_ZN_1 | 26-DEC-04:22 | 0.00 | 0.00 | 14762.41 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3166.23 | 0.00 | -2467.90 | -9683.93 |
PERIMETER_TOP_ZN_4 | 06-FEB-03:22 | 0.00 | 0.00 | 12976.93 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2279.49 | 0.00 | -1615.33 | -9433.86 |
PERIMETER_BOT_ZN_3 | 06-FEB-04:42 | 0.00 | 0.00 | 7502.37 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3612.05 | 0.00 | -1248.60 | -3197.37 |
PERIMETER_BOT_ZN_2 | 06-FEB-03:22 | 0.00 | 0.00 | 9174.81 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2316.46 | 0.00 | -897.66 | -6312.45 |
PERIMETER_BOT_ZN_1 | 07-FEB-08:00 | 0.00 | 0.00 | 13198.62 | 0.00 | 0.00 | 0.00 | 253.72 | 116.94 | 637.88 | 0.00 | 0.00 | 0.00 | 10564.41 | 0.00 | -563.55 | 0.00 | -24208.02 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-04:42 | 0.00 | 0.00 | 9568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2410.93 | 0.00 | -846.23 | -6662.80 |
PERIMETER_MID_ZN_3 | 06-FEB-03:02 | 0.00 | 0.00 | 8603.98 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3508.89 | 0.00 | -2193.20 | -3457.56 |
PERIMETER_MID_ZN_2 | 06-FEB-03:02 | 0.00 | 0.00 | 10234.66 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2270.26 | 0.00 | -1498.08 | -6818.09 |
PERIMETER_MID_ZN_1 | 06-FEB-03:02 | 0.00 | 0.00 | 12846.49 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3532.21 | 0.00 | -2233.74 | -7636.18 |
PERIMETER_MID_ZN_4 | 06-FEB-03:02 | 0.00 | 0.00 | 10351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2337.23 | 0.00 | -1495.95 | -6869.90 |
TOPFLOOR_PLENUM | 11-DEC-06:06 | 15119.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -285.50 | -14833.87 |
MIDFLOOR_PLENUM | 02-JAN-07:03 | 9246.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -271.37 | -8975.39 |
FIRSTFLOOR_PLENUM | 02-JAN-08:10 | 7992.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -192.08 | -7800.32 |
Total Facility | 02-JAN-05:01 | 11809.59 | 0.00 | 191582.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18469.01 | 0.00 | -8517.92 | -191761.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.9286 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3140 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.9860 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.1453 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2989 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4643 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4930 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6494 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0765 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3921 | 2.3921 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0019 | 2.0019 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0828 | 2.0828 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6523 | 0.6523 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7728 | 0.7728 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9487 | 0.9487 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8423 | 0.8423 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5033 | 0.5033 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6274 | 0.6274 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7510 | 0.7510 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6547 | 0.6547 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5693 | 0.5693 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7624 | 0.7624 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8679 | 0.8679 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7846 | 0.7846 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.9286 | 4.3140 | 4.9286 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.9860 | 4.1453 | 4.9860 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2989 | 4.7757 | 5.2989 | 1.0765 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1960 | 1.1960 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0009 | 1.0009 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0414 | 1.0414 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3261 | 0.3261 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3864 | 0.3864 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4743 | 0.4743 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4211 | 0.4211 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2516 | 0.2516 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3137 | 0.3137 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3755 | 0.3755 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3274 | 0.3274 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2847 | 0.2847 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3812 | 0.3812 | 0.0854 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4340 | 0.4340 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3923 | 0.3923 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4643 | 1.0756 | 1.0756 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4930 | 1.0756 | 1.0756 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6494 | 1.0765 | 1.0765 | 1.0765 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 386.33 |
Number of hours cooling loads not met | 79.50 |
Number of hours not met | 465.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 227.06 | 187169.61 | 269.30 | 108459.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 112.31 | 61233.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 166.72 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.33 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 829.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 78.50 | 25608.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 135.38 | 11209.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1278.42 |
Natural Gas | 0.00 | 404.67 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1683.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 137.14 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.46 |
Space Heating | 45.57 |
Space Cooling | 22.54 |
Fans (All) | 15.76 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 256.60 |
Subtotal | 256.60 |
Natural Gas [MJ/m2] | |
Space Heating | 54.05 |
Service Water Heating | 27.17 |
Miscellaneous (All) | 81.22 |
Subtotal | 81.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.91 |
Space Heating | 29.49 |
Space Cooling | 6.67 |
Fans (All) | 4.66 |
Service Water Heating | 8.04 |
Receptacle Equipment | 38.49 |
Miscellaneous | 2.74 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 886. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8671.83 | 88.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8682.83 | 77.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8638.33 | 121.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8714.17 | 45.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8724.50 | 35.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8679.83 | 80.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8681.17 | 78.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8692.67 | 67.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8646.50 | 113.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8652.83 | 107.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8638.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 121.67 | 0.00 | 0.00 | 0.00 |
Average | 8711.21 | 48.79 | 0.00 | 0.00 | 0.00 |
Sum | 156801.83 | 878.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8316.83 | 443.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8395.33 | 364.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8464.17 | 295.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8300.50 | 459.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8246.33 | 513.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8263.33 | 496.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8227.67 | 532.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8378.17 | 381.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8276.00 | 484.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8211.33 | 548.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8230.00 | 530.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8286.67 | 473.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8231.67 | 528.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8257.17 | 502.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8213.17 | 546.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8000.17 | 759.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8257.00 | 503.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8253.33 | 506.67 | 0.00 | 0.00 | 0.00 |
Min | 8000.17 | 295.83 | 0.00 | 0.00 | 0.00 |
Max | 8464.17 | 759.83 | 0.00 | 0.00 | 0.00 |
Average | 8267.16 | 492.84 | 0.00 | 0.00 | 0.00 |
Sum | 148808.83 | 8871.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128066.50 | 237.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128136.67 | 167.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128167.50 | 136.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24881.33 | 27.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14009.50 | 6.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24879.33 | 29.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14003.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24869.67 | 39.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14010.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24370.33 | 538.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14007.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24887.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24888.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128167.50 | 538.67 | 0.00 | 0.00 | 0.00 |
Average | 34073.66 | 69.68 | 0.00 | 0.00 | 0.00 |
Sum | 613325.83 | 1254.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.629585E+10 | 5889.72 | 20-JAN-17:00 | -1.1 | -3.7 | 0.165543E+10 | 2423.88 | 20-JAN-14:09 | -1.1 | -3.7 |
February | 0.624167E+10 | 5993.81 | 17-FEB-17:00 | 1.10 | 0.20 | 0.152567E+10 | 2457.32 | 17-FEB-14:09 | 1.10 | 0.20 |
March | 0.921555E+10 | 13654.18 | 17-MAR-07:10 | 9.40 | 9.07 | 0.204914E+10 | 2606.63 | 16-MAR-09:20 | 9.40 | 9.07 |
April | 0.105288E+11 | 14451.04 | 26-APR-07:04 | 5.47 | 3.33 | 0.188726E+10 | 2606.66 | 19-APR-09:20 | 5.47 | 3.33 |
May | 0.155577E+11 | 21665.64 | 30-MAY-06:03 | 12.20 | 11.93 | 0.207290E+10 | 2606.66 | 05-MAY-13:09 | 12.20 | 11.93 |
June | 0.197541E+11 | 31902.02 | 19-JUN-06:03 | 16.70 | 15.97 | 0.206891E+10 | 2606.81 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.205877E+11 | 34140.72 | 05-JUL-05:12 | 19.23 | 16.66 | 0.192404E+10 | 2606.67 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.217750E+11 | 33513.30 | 07-AUG-05:12 | 20.20 | 18.58 | 0.216007E+10 | 2639.51 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.180369E+11 | 34644.34 | 18-SEP-05:12 | 9.60 | 8.73 | 0.191641E+10 | 2606.81 | 12-SEP-13:09 | 9.60 | 8.73 |
October | 0.129662E+11 | 16329.46 | 13-OCT-06:02 | 10.00 | 9.62 | 0.198289E+10 | 2606.65 | 10-OCT-09:20 | 10.00 | 9.62 |
November | 0.905536E+10 | 13983.43 | 02-NOV-07:08 | 4.40 | 3.64 | 0.192480E+10 | 2606.69 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.696902E+10 | 7644.78 | 01-DEC-13:20 | 12.03 | 10.45 | 0.167724E+10 | 2606.43 | 01-DEC-14:50 | 7.38 | 5.84 |
Annual Sum or Average | 0.156984E+12 | 0.228448E+11 | ||||||||
Minimum of Months | 0.624167E+10 | 5889.72 | -1.1 | -3.7 | 0.152567E+10 | 2423.88 | -1.1 | -3.7 | ||
Maximum of Months | 0.217750E+11 | 34644.34 | 20.20 | 18.58 | 0.216007E+10 | 2639.51 | 23.90 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 27726.55 | 64.86 | 22-FEB-17:30 | 12.25 | 5.87 | 0.00 | 0.00 | 01-FEB-00:10 | 12.25 | 5.87 |
March | 0.232349E+09 | 4671.73 | 15-MAR-14:00 | 26.10 | 16.06 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 16.06 |
April | 0.763338E+09 | 4178.73 | 21-APR-14:50 | 14.90 | 8.32 | 0.00 | 0.00 | 01-APR-00:10 | 14.90 | 8.32 |
May | 0.235939E+10 | 6545.43 | 31-MAY-14:20 | 21.70 | 14.12 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.12 |
June | 0.461646E+10 | 9342.37 | 12-JUN-13:30 | 30.00 | 19.98 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 19.98 |
July | 0.568697E+10 | 9249.84 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.496749E+10 | 9152.95 | 09-AUG-14:40 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
September | 0.248975E+10 | 7183.56 | 21-SEP-15:20 | 26.10 | 16.82 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 16.82 |
October | 0.442919E+09 | 3859.12 | 11-OCT-15:00 | 22.20 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 14.61 |
November | 23195699.75 | 648.93 | 04-NOV-15:20 | 18.30 | 13.65 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.215819E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.568697E+10 | 9342.37 | 31.15 | 21.91 | 0.00 | 0.00 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4586346.91 | 2602.75 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 4730138.20 | 2455.08 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 92052218.60 | 2582.45 | 04-MAR-06:01 | -10.6 | -11.5 | 0.00 | 0.00 | 01-MAR-00:10 | -10.6 | -11.5 |
April | 0.192230E+09 | 1593.40 | 06-APR-06:02 | 1.20 | 0.69 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | 0.69 |
May | 0.894059E+09 | 2061.67 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.243538E+10 | 4106.31 | 12-JUN-15:20 | 29.43 | 20.07 | 0.00 | 0.00 | 01-JUN-00:10 | 29.43 | 20.07 |
July | 0.325393E+10 | 5957.56 | 17-JUL-06:15 | 22.97 | 21.14 | 0.00 | 0.00 | 01-JUL-00:10 | 22.97 | 21.14 |
August | 0.297323E+10 | 4162.50 | 14-AUG-14:20 | 28.13 | 22.32 | 0.00 | 0.00 | 01-AUG-00:10 | 28.13 | 22.32 |
September | 0.147698E+10 | 3051.88 | 18-SEP-12:40 | 18.70 | 12.39 | 0.00 | 0.00 | 01-SEP-00:10 | 18.70 | 12.39 |
October | 0.231507E+09 | 1224.04 | 17-OCT-06:01 | -2.8 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | -2.8 | -3.4 |
November | 33339274.20 | 1420.91 | 18-NOV-06:01 | 1.02 | -0.8 | 0.00 | 0.00 | 01-NOV-00:10 | 1.02 | -0.8 |
December | 4150652.21 | 2397.85 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.115962E+11 | 0.00 | ||||||||
Minimum of Months | 4150652.21 | 1224.04 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.325393E+10 | 5957.56 | 29.43 | 22.32 | 0.00 | 0.00 | 29.43 | 22.32 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33589788.89 | 2270.84 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 34517132.59 | 2066.83 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.191922E+09 | 2714.98 | 04-MAR-06:01 | -10.6 | -11.5 | 0.00 | 0.00 | 01-MAR-00:10 | -10.6 | -11.5 |
April | 0.407269E+09 | 2295.26 | 11-APR-06:03 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.120243E+10 | 2089.58 | 24-MAY-16:06 | 11.70 | 11.07 | 0.00 | 0.00 | 01-MAY-00:10 | 11.70 | 11.07 |
June | 0.261305E+10 | 3811.28 | 12-JUN-15:10 | 29.72 | 20.02 | 0.00 | 0.00 | 01-JUN-00:10 | 29.72 | 20.02 |
July | 0.338959E+10 | 5690.81 | 17-JUL-06:15 | 22.97 | 21.14 | 0.00 | 0.00 | 01-JUL-00:10 | 22.97 | 21.14 |
August | 0.336052E+10 | 4223.39 | 07-AUG-07:10 | 21.20 | 18.87 | 0.00 | 0.00 | 01-AUG-00:10 | 21.20 | 18.87 |
September | 0.203696E+10 | 3443.29 | 18-SEP-12:05 | 18.40 | 12.35 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 12.35 |
October | 0.495635E+09 | 2274.81 | 17-OCT-06:01 | -2.8 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | -2.8 | -3.4 |
November | 0.113092E+09 | 1709.66 | 03-NOV-06:03 | 1.70 | 0.39 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 0.39 |
December | 24796239.78 | 1658.83 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.139034E+11 | 0.00 | ||||||||
Minimum of Months | 24796239.78 | 1658.83 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.338959E+10 | 5690.81 | 29.72 | 21.14 | 0.00 | 0.00 | 29.72 | 21.14 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382991E+10 | 5065.50 | 12-JAN-16:50 | -6.6 | -8.3 | 0.150942E+10 | 2162.18 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.383204E+10 | 5206.26 | 17-FEB-17:00 | 1.10 | 0.20 | 0.138474E+10 | 2219.30 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.745502E+10 | 10052.46 | 16-MAR-16:00 | 15.60 | 13.95 | 0.186172E+10 | 2606.63 | 16-MAR-09:20 | 15.60 | 13.95 |
April | 0.816437E+10 | 9567.21 | 21-APR-16:00 | 13.30 | 8.77 | 0.179577E+10 | 2606.62 | 20-APR-13:20 | 13.30 | 8.77 |
May | 0.121303E+11 | 12813.23 | 31-MAY-16:00 | 22.20 | 14.47 | 0.205767E+10 | 2606.65 | 10-MAY-13:20 | 22.20 | 14.47 |
June | 0.158290E+11 | 26491.12 | 19-JUN-06:03 | 16.70 | 15.97 | 0.206563E+10 | 2606.78 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.169306E+11 | 28950.58 | 17-JUL-05:15 | 22.80 | 21.19 | 0.192188E+10 | 2606.66 | 25-JUL-09:20 | 22.77 | 17.50 |
August | 0.172204E+11 | 28482.15 | 07-AUG-05:12 | 20.20 | 18.58 | 0.215726E+10 | 2606.79 | 04-AUG-09:09 | 20.20 | 18.58 |
September | 0.133789E+11 | 29049.38 | 18-SEP-05:12 | 9.60 | 8.73 | 0.190936E+10 | 2606.77 | 12-SEP-13:09 | 9.60 | 8.73 |
October | 0.895257E+10 | 11265.84 | 12-OCT-16:00 | 18.30 | 14.87 | 0.190842E+10 | 2606.64 | 03-OCT-09:20 | 18.30 | 14.87 |
November | 0.668317E+10 | 7196.41 | 01-NOV-16:00 | 9.40 | 6.91 | 0.172353E+10 | 2606.57 | 01-NOV-13:50 | 9.40 | 6.91 |
December | 0.443075E+10 | 5506.81 | 01-DEC-17:00 | 7.20 | 4.89 | 0.148119E+10 | 2312.23 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.118837E+12 | 0.217766E+11 | ||||||||
Minimum of Months | 0.382991E+10 | 5065.50 | -6.6 | -8.3 | 0.138474E+10 | 2162.18 | 0.60 | -3.3 | ||
Maximum of Months | 0.172204E+11 | 29049.38 | 22.80 | 21.19 | 0.215726E+10 | 2606.79 | 22.77 | 18.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224944E+10 | 4700.32 | 06-JAN-16:20 | -2.6 | -5.0 | 0.146843E+10 | 2072.29 | 06-JAN-14:00 | -2.6 | -5.0 |
February | 0.253446E+10 | 4934.94 | 28-FEB-17:00 | -0.6 | -3.0 | 0.134680E+10 | 2132.96 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.617744E+10 | 10584.70 | 16-MAR-16:00 | 15.60 | 13.95 | 0.178167E+10 | 2606.63 | 16-MAR-09:20 | 15.60 | 13.95 |
April | 0.745308E+10 | 10613.94 | 21-APR-16:00 | 13.30 | 8.77 | 0.172328E+10 | 2606.62 | 20-APR-13:20 | 13.30 | 8.77 |
May | 0.117188E+11 | 14463.11 | 31-MAY-16:00 | 22.20 | 14.47 | 0.203427E+10 | 2606.65 | 17-MAY-09:50 | 22.20 | 14.47 |
June | 0.161076E+11 | 27668.53 | 19-JUN-06:03 | 16.70 | 15.97 | 0.206068E+10 | 2606.79 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.176229E+11 | 30210.55 | 05-JUL-05:12 | 19.23 | 16.66 | 0.192089E+10 | 2606.66 | 25-JUL-09:39 | 23.33 | 17.69 |
August | 0.172307E+11 | 30186.73 | 07-AUG-05:12 | 20.20 | 18.58 | 0.215361E+10 | 2606.79 | 02-AUG-13:09 | 20.20 | 18.58 |
September | 0.124394E+11 | 15732.78 | 18-SEP-13:10 | 18.72 | 12.47 | 0.189408E+10 | 2606.77 | 12-SEP-13:09 | 18.72 | 12.47 |
October | 0.777831E+10 | 11101.91 | 12-OCT-16:00 | 18.30 | 14.87 | 0.181027E+10 | 2608.06 | 13-OCT-09:50 | 10.60 | 9.99 |
November | 0.514151E+10 | 6218.79 | 01-NOV-16:00 | 9.40 | 6.91 | 0.159775E+10 | 2532.53 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.256037E+10 | 5067.69 | 01-DEC-15:00 | 7.20 | 5.63 | 0.142258E+10 | 2194.30 | 01-DEC-14:00 | 7.20 | 5.63 |
Annual Sum or Average | 0.109014E+12 | 0.212143E+11 | ||||||||
Minimum of Months | 0.224944E+10 | 4700.32 | -2.6 | -5.0 | 0.134680E+10 | 2072.29 | -2.6 | -5.0 | ||
Maximum of Months | 0.176229E+11 | 30210.55 | 22.20 | 18.58 | 0.215361E+10 | 2608.06 | 23.33 | 18.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11478623.95 | 802.79 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304465E+09 | 406.69 | 23-JAN-14:09 | -7.3 | -8.9 |
February | 20857355.96 | 811.28 | 18-FEB-17:03 | 0.82 | -0.6 | 0.276003E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.666592E+09 | 3389.29 | 15-MAR-14:40 | 25.77 | 16.18 | 0.353688E+09 | 549.50 | 15-MAR-13:30 | 25.77 | 16.18 |
April | 0.121494E+10 | 2416.87 | 21-APR-15:20 | 14.43 | 8.49 | 0.337962E+09 | 549.50 | 20-APR-13:20 | 14.43 | 8.49 |
May | 0.259732E+10 | 4573.17 | 23-MAY-14:40 | 23.90 | 13.32 | 0.418448E+09 | 549.50 | 17-MAY-09:20 | 23.90 | 13.32 |
June | 0.452182E+10 | 6929.74 | 12-JUN-06:03 | 22.98 | 18.45 | 0.433165E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.531277E+10 | 10320.99 | 16-JUL-13:32 | 27.93 | 21.28 | 0.405120E+09 | 549.55 | 21-JUL-13:39 | 31.33 | 21.85 |
August | 0.482860E+10 | 8003.83 | 06-AUG-14:02 | 26.97 | 18.51 | 0.452457E+09 | 549.54 | 02-AUG-13:09 | 26.97 | 18.51 |
September | 0.281896E+10 | 4501.60 | 15-SEP-14:00 | 25.60 | 21.03 | 0.390950E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.126824E+10 | 2416.15 | 12-OCT-15:20 | 18.30 | 15.11 | 0.354278E+09 | 549.49 | 12-OCT-13:20 | 18.30 | 15.11 |
November | 0.387734E+09 | 1163.70 | 16-NOV-16:40 | 17.93 | 13.54 | 0.310246E+09 | 489.03 | 01-NOV-13:50 | 17.93 | 13.54 |
December | 33131541.38 | 906.39 | 01-DEC-13:30 | 11.10 | 9.57 | 0.293523E+09 | 407.65 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.236824E+11 | 0.433031E+10 | ||||||||
Minimum of Months | 11478623.95 | 802.79 | 0.82 | -0.6 | 0.276003E+09 | 406.69 | -7.3 | -8.9 | ||
Maximum of Months | 0.531277E+10 | 10320.99 | 27.93 | 21.28 | 0.452457E+09 | 549.55 | 31.33 | 21.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11529264.25 | 507.73 | 14-JAN-17:03 | 3.22 | 2.72 | 0.193055E+09 | 257.48 | 23-JAN-14:09 | -7.3 | -8.9 |
February | 88661692.72 | 750.44 | 28-FEB-10:05 | -3.6 | -5.3 | 0.176665E+09 | 317.41 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.693626E+09 | 2710.14 | 15-MAR-09:30 | 20.25 | 14.29 | 0.236350E+09 | 347.88 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.139741E+10 | 5306.68 | 24-APR-09:10 | 6.28 | 2.92 | 0.231494E+09 | 347.88 | 21-APR-13:00 | 6.28 | 2.92 |
May | 0.289948E+10 | 7352.27 | 31-MAY-08:40 | 17.60 | 13.16 | 0.271066E+09 | 347.88 | 26-MAY-09:00 | 17.60 | 13.16 |
June | 0.446470E+10 | 11674.24 | 11-JUN-08:23 | 22.50 | 15.33 | 0.275514E+09 | 348.38 | 12-JUN-09:00 | 27.80 | 19.41 |
July | 0.510798E+10 | 13180.00 | 04-JUL-09:02 | 21.28 | 17.22 | 0.257060E+09 | 348.37 | 03-JUL-09:00 | 21.28 | 17.22 |
August | 0.466806E+10 | 8145.46 | 06-AUG-14:02 | 26.97 | 18.51 | 0.287463E+09 | 348.29 | 17-AUG-09:50 | 24.63 | 15.64 |
September | 0.290651E+10 | 9692.94 | 04-SEP-09:53 | 17.80 | 13.22 | 0.251173E+09 | 347.89 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.108569E+10 | 4124.17 | 11-OCT-09:30 | 15.85 | 11.81 | 0.239303E+09 | 347.88 | 06-OCT-09:20 | 15.85 | 11.81 |
November | 0.321301E+09 | 928.19 | 03-NOV-09:30 | 4.75 | 2.42 | 0.201714E+09 | 347.87 | 03-NOV-09:50 | 5.32 | 2.80 |
December | 27044163.14 | 580.00 | 01-DEC-13:30 | 11.10 | 9.57 | 0.186241E+09 | 259.66 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.236720E+11 | 0.280710E+10 | ||||||||
Minimum of Months | 11529264.25 | 507.73 | -3.6 | -5.3 | 0.176665E+09 | 257.48 | -7.3 | -8.9 | ||
Maximum of Months | 0.510798E+10 | 13180.00 | 26.97 | 18.51 | 0.287463E+09 | 348.38 | 27.80 | 19.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328756E+09 | 3439.52 | 12-JAN-13:40 | -6.5 | -9.0 | 0.319141E+09 | 549.50 | 12-JAN-14:20 | -5.9 | -8.5 |
February | 0.457938E+09 | 5814.97 | 28-FEB-13:40 | 0.00 | -2.9 | 0.293775E+09 | 549.49 | 08-FEB-14:50 | 0.00 | -2.9 |
March | 0.177107E+10 | 9610.68 | 15-MAR-13:30 | 25.55 | 15.84 | 0.390389E+09 | 549.77 | 15-MAR-13:39 | 25.73 | 15.91 |
April | 0.233112E+10 | 7898.27 | 24-APR-13:10 | 11.38 | 6.04 | 0.358508E+09 | 549.52 | 21-APR-13:00 | 11.38 | 6.04 |
May | 0.391082E+10 | 10499.43 | 14-MAY-14:53 | 26.10 | 17.84 | 0.420932E+09 | 549.51 | 10-MAY-13:50 | 26.10 | 17.84 |
June | 0.556192E+10 | 12330.39 | 11-JUN-14:23 | 25.85 | 18.28 | 0.432439E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.663110E+10 | 15901.80 | 30-JUL-13:53 | 25.60 | 19.95 | 0.405050E+09 | 550.11 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.690414E+10 | 15965.43 | 13-AUG-12:32 | 29.63 | 22.57 | 0.453003E+09 | 550.08 | 03-AUG-13:00 | 29.63 | 22.57 |
September | 0.540303E+10 | 16900.83 | 10-SEP-13:32 | 17.20 | 10.63 | 0.395480E+09 | 550.22 | 22-SEP-13:50 | 23.72 | 15.13 |
October | 0.286889E+10 | 11716.75 | 11-OCT-12:30 | 21.95 | 13.79 | 0.383246E+09 | 549.77 | 11-OCT-13:09 | 22.20 | 14.14 |
November | 0.102631E+10 | 7332.13 | 03-NOV-12:25 | 8.35 | 4.56 | 0.335388E+09 | 549.64 | 03-NOV-13:09 | 8.98 | 4.94 |
December | 0.258553E+09 | 3592.97 | 16-DEC-13:30 | 5.60 | 3.03 | 0.301081E+09 | 549.48 | 04-DEC-14:09 | 5.60 | 3.03 |
Annual Sum or Average | 0.374537E+11 | 0.448843E+10 | ||||||||
Minimum of Months | 0.258553E+09 | 3439.52 | -6.5 | -9.0 | 0.293775E+09 | 549.48 | -5.9 | -8.5 | ||
Maximum of Months | 0.690414E+10 | 16900.83 | 29.63 | 22.57 | 0.453003E+09 | 550.22 | 29.63 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36359666.89 | 667.08 | 06-JAN-15:40 | -2.2 | -4.8 | 0.193468E+09 | 284.86 | 06-JAN-15:50 | -2.2 | -4.8 |
February | 83282556.15 | 1712.68 | 28-FEB-16:30 | 0.00 | -2.6 | 0.177340E+09 | 338.68 | 28-FEB-16:00 | -0.6 | -3.0 |
March | 0.680598E+09 | 3576.49 | 15-MAR-14:20 | 25.93 | 16.12 | 0.232770E+09 | 347.85 | 15-MAR-13:30 | 25.93 | 16.12 |
April | 0.134665E+10 | 6316.54 | 24-APR-16:00 | 13.30 | 7.63 | 0.219459E+09 | 347.85 | 20-APR-13:20 | 13.30 | 7.63 |
May | 0.285579E+10 | 11826.30 | 27-MAY-17:06 | 20.32 | 11.21 | 0.265701E+09 | 347.86 | 10-MAY-13:00 | 20.32 | 11.21 |
June | 0.458887E+10 | 14634.12 | 11-JUN-17:02 | 25.50 | 17.77 | 0.274094E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.495475E+10 | 15014.24 | 02-JUL-17:12 | 24.63 | 16.88 | 0.256583E+09 | 347.86 | 25-JUL-09:20 | 22.77 | 17.50 |
August | 0.460737E+10 | 13694.04 | 12-AUG-17:05 | 24.72 | 16.93 | 0.286753E+09 | 347.88 | 02-AUG-13:09 | 24.72 | 16.93 |
September | 0.274853E+10 | 14876.14 | 04-SEP-16:32 | 18.30 | 12.97 | 0.248664E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.111865E+10 | 5905.28 | 11-OCT-16:00 | 21.70 | 14.52 | 0.229741E+09 | 347.85 | 04-OCT-13:20 | 21.70 | 14.52 |
November | 0.330735E+09 | 1635.16 | 03-NOV-15:00 | 10.00 | 5.48 | 0.201317E+09 | 347.83 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 41897640.74 | 676.49 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186450E+09 | 286.96 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.233935E+11 | 0.277234E+10 | ||||||||
Minimum of Months | 36359666.89 | 667.08 | -2.2 | -4.8 | 0.177340E+09 | 284.86 | -2.2 | -4.8 | ||
Maximum of Months | 0.495475E+10 | 15014.24 | 25.93 | 17.77 | 0.286753E+09 | 347.88 | 25.93 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10930809.94 | 807.49 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304876E+09 | 406.70 | 03-JAN-14:39 | 3.22 | 2.72 |
February | 13010617.66 | 809.42 | 18-FEB-17:03 | 0.82 | -0.6 | 0.276763E+09 | 406.70 | 06-FEB-14:39 | 0.82 | -0.6 |
March | 0.491809E+09 | 1311.65 | 15-MAR-15:30 | 25.30 | 16.10 | 0.345529E+09 | 531.92 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.101337E+10 | 1230.31 | 27-APR-13:50 | 13.30 | 8.09 | 0.323006E+09 | 512.90 | 27-APR-13:00 | 13.30 | 8.09 |
May | 0.180123E+10 | 2623.55 | 23-MAY-14:40 | 23.90 | 13.32 | 0.406126E+09 | 549.50 | 10-MAY-13:20 | 23.90 | 13.32 |
June | 0.326189E+10 | 4474.68 | 26-JUN-15:40 | 28.13 | 20.69 | 0.432762E+09 | 549.52 | 22-JUN-13:09 | 28.13 | 20.69 |
July | 0.415182E+10 | 5073.12 | 21-JUL-13:30 | 31.15 | 21.91 | 0.404599E+09 | 549.50 | 25-JUL-09:20 | 22.77 | 17.50 |
August | 0.413587E+10 | 5579.87 | 07-AUG-06:03 | 20.68 | 18.73 | 0.453539E+09 | 561.07 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.266526E+10 | 3820.63 | 18-SEP-13:10 | 18.72 | 12.47 | 0.397472E+09 | 549.53 | 12-SEP-13:09 | 18.72 | 12.47 |
October | 0.156043E+10 | 2135.91 | 05-OCT-14:40 | 18.90 | 12.59 | 0.373623E+09 | 549.49 | 12-OCT-13:20 | 17.57 | 14.20 |
November | 0.834020E+09 | 1185.68 | 01-NOV-13:30 | 11.15 | 6.93 | 0.321905E+09 | 499.16 | 01-NOV-13:39 | 10.97 | 6.90 |
December | 65067994.98 | 991.46 | 01-DEC-13:30 | 11.10 | 9.57 | 0.295472E+09 | 433.03 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.200047E+11 | 0.433567E+10 | ||||||||
Minimum of Months | 10930809.94 | 807.49 | 0.82 | -0.6 | 0.276763E+09 | 406.70 | 0.82 | -0.6 | ||
Maximum of Months | 0.415182E+10 | 5579.87 | 31.15 | 21.91 | 0.453539E+09 | 561.07 | 28.13 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11508025.01 | 562.73 | 14-JAN-07:05 | 3.30 | 2.57 | 0.193618E+09 | 257.49 | 03-JAN-14:39 | 3.30 | 2.57 |
February | 60635471.44 | 651.80 | 28-FEB-10:00 | -3.9 | -5.5 | 0.176483E+09 | 287.21 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.564713E+09 | 1280.63 | 15-MAR-09:30 | 20.25 | 14.29 | 0.230853E+09 | 347.87 | 15-MAR-13:20 | 25.37 | 15.76 |
April | 0.108421E+10 | 3662.30 | 24-APR-09:10 | 6.28 | 2.92 | 0.229649E+09 | 347.88 | 19-APR-09:20 | 6.28 | 2.92 |
May | 0.204726E+10 | 5870.67 | 31-MAY-06:03 | 14.68 | 12.32 | 0.270060E+09 | 347.88 | 26-MAY-09:00 | 14.68 | 12.32 |
June | 0.361326E+10 | 8157.17 | 23-JUN-06:02 | 13.90 | 11.85 | 0.275683E+09 | 348.10 | 12-JUN-09:00 | 13.90 | 11.85 |
July | 0.438717E+10 | 10731.83 | 04-JUL-10:12 | 22.77 | 17.60 | 0.257026E+09 | 348.26 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.431076E+10 | 8171.02 | 02-AUG-06:02 | 11.85 | 10.72 | 0.287967E+09 | 349.66 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.291544E+10 | 7474.10 | 04-SEP-10:02 | 17.98 | 13.30 | 0.254090E+09 | 347.89 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.132538E+10 | 3619.96 | 11-OCT-09:30 | 15.85 | 11.81 | 0.251976E+09 | 347.88 | 31-OCT-13:30 | 15.00 | 10.33 |
November | 0.636793E+09 | 1434.06 | 03-NOV-08:35 | 3.53 | 1.63 | 0.211680E+09 | 347.88 | 03-NOV-09:39 | 5.03 | 2.61 |
December | 49180317.32 | 635.29 | 01-DEC-13:30 | 11.10 | 9.57 | 0.187465E+09 | 275.50 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.210063E+11 | 0.282655E+10 | ||||||||
Minimum of Months | 11508025.01 | 562.73 | -3.9 | -5.5 | 0.176483E+09 | 257.49 | -3.6 | -5.3 | ||
Maximum of Months | 0.438717E+10 | 10731.83 | 22.77 | 17.60 | 0.287967E+09 | 349.66 | 25.37 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59620244.41 | 1019.91 | 21-JAN-12:30 | -0.6 | -3.1 | 0.287865E+09 | 422.67 | 12-JAN-14:00 | -0.6 | -3.1 |
February | 81587413.41 | 1199.67 | 18-FEB-14:40 | 2.80 | 0.63 | 0.261990E+09 | 461.26 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.715461E+09 | 5601.65 | 15-MAR-13:30 | 25.55 | 15.84 | 0.348176E+09 | 549.50 | 15-MAR-13:20 | 25.55 | 15.84 |
April | 0.107515E+10 | 3524.39 | 22-APR-13:40 | 15.20 | 6.94 | 0.327498E+09 | 549.51 | 21-APR-13:00 | 15.20 | 6.94 |
May | 0.198474E+10 | 5103.33 | 16-MAY-12:10 | 19.18 | 11.50 | 0.394534E+09 | 549.51 | 08-MAY-13:09 | 19.18 | 11.50 |
June | 0.372446E+10 | 10214.52 | 12-JUN-12:00 | 29.40 | 20.11 | 0.423793E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.550209E+10 | 10477.76 | 21-JUL-12:00 | 30.00 | 21.57 | 0.402759E+09 | 554.73 | 21-JUL-12:09 | 30.10 | 21.65 |
August | 0.606679E+10 | 12010.40 | 06-AUG-14:02 | 26.97 | 18.51 | 0.449869E+09 | 559.05 | 10-AUG-12:09 | 29.82 | 22.08 |
September | 0.456135E+10 | 12756.26 | 04-SEP-14:43 | 18.72 | 13.10 | 0.393849E+09 | 549.83 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.222587E+10 | 9727.38 | 11-OCT-12:30 | 21.95 | 13.79 | 0.376581E+09 | 549.72 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.771864E+09 | 4863.57 | 01-NOV-12:08 | 11.20 | 6.39 | 0.325549E+09 | 549.50 | 03-NOV-13:09 | 8.98 | 4.94 |
December | 0.100769E+09 | 1658.54 | 16-DEC-13:30 | 5.60 | 3.03 | 0.281421E+09 | 451.76 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.268698E+11 | 0.427389E+10 | ||||||||
Minimum of Months | 59620244.41 | 1019.91 | -0.6 | -3.1 | 0.261990E+09 | 422.67 | -0.6 | -3.1 | ||
Maximum of Months | 0.606679E+10 | 12756.26 | 30.00 | 21.57 | 0.449869E+09 | 559.05 | 30.10 | 22.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27734985.16 | 643.19 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193741E+09 | 277.74 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 55897099.39 | 802.97 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176720E+09 | 324.22 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.525130E+09 | 1576.02 | 15-MAR-14:20 | 25.93 | 16.12 | 0.226846E+09 | 347.84 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.999171E+09 | 3703.05 | 24-APR-17:30 | 11.70 | 7.64 | 0.218506E+09 | 347.84 | 21-APR-13:20 | 11.70 | 7.64 |
May | 0.194561E+10 | 5681.02 | 27-MAY-17:06 | 20.32 | 11.21 | 0.265390E+09 | 347.85 | 24-MAY-09:20 | 20.32 | 11.21 |
June | 0.372249E+10 | 10312.84 | 11-JUN-17:02 | 25.50 | 17.77 | 0.275297E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.418669E+10 | 11128.82 | 16-JUL-16:41 | 27.77 | 20.68 | 0.256888E+09 | 347.86 | 03-JUL-13:39 | 27.77 | 20.68 |
August | 0.422930E+10 | 9492.74 | 12-AUG-17:05 | 24.72 | 16.93 | 0.287935E+09 | 349.72 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.269012E+10 | 8032.84 | 04-SEP-15:23 | 18.60 | 13.14 | 0.253611E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.128159E+10 | 4939.93 | 11-OCT-16:00 | 21.70 | 14.52 | 0.244348E+09 | 347.85 | 06-OCT-13:20 | 21.70 | 14.52 |
November | 0.616968E+09 | 1441.72 | 03-NOV-15:40 | 9.27 | 5.12 | 0.209893E+09 | 347.68 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 60050299.19 | 669.66 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187519E+09 | 284.86 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.203408E+11 | 0.279669E+10 | ||||||||
Minimum of Months | 27734985.16 | 643.19 | -6.2 | -8.3 | 0.176720E+09 | 277.74 | -6.3 | -8.3 | ||
Maximum of Months | 0.422930E+10 | 11128.82 | 27.77 | 20.68 | 0.287935E+09 | 349.72 | 27.77 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23082823.79 | 814.92 | 14-JAN-17:03 | 3.22 | 2.72 | 0.305216E+09 | 406.69 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 50607635.10 | 858.40 | 17-FEB-15:00 | 3.30 | 1.08 | 0.277058E+09 | 406.69 | 06-FEB-14:39 | 3.30 | 1.08 |
March | 0.853672E+09 | 2883.90 | 15-MAR-14:40 | 25.77 | 16.18 | 0.359461E+09 | 549.50 | 15-MAR-13:20 | 25.77 | 16.18 |
April | 0.141236E+10 | 2211.29 | 21-APR-15:20 | 14.43 | 8.49 | 0.349695E+09 | 549.50 | 20-APR-13:20 | 14.43 | 8.49 |
May | 0.266089E+10 | 4308.10 | 23-MAY-14:40 | 23.90 | 13.32 | 0.426401E+09 | 549.50 | 10-MAY-13:20 | 23.90 | 13.32 |
June | 0.445571E+10 | 7366.54 | 12-JUN-06:03 | 22.98 | 18.45 | 0.434832E+09 | 549.98 | 12-JUN-13:20 | 29.80 | 19.89 |
July | 0.513592E+10 | 7535.62 | 16-JUL-13:32 | 27.93 | 21.28 | 0.405398E+09 | 550.49 | 20-JUL-13:20 | 30.00 | 23.48 |
August | 0.479362E+10 | 8731.29 | 06-AUG-16:31 | 27.80 | 18.98 | 0.453970E+09 | 550.78 | 14-AUG-10:00 | 24.40 | 21.66 |
September | 0.297498E+10 | 4302.75 | 13-SEP-13:30 | 22.20 | 19.01 | 0.397508E+09 | 549.52 | 12-SEP-13:09 | 22.20 | 19.01 |
October | 0.156552E+10 | 2517.24 | 05-OCT-14:40 | 18.90 | 12.59 | 0.371458E+09 | 549.49 | 12-OCT-13:20 | 17.57 | 14.20 |
November | 0.732597E+09 | 1224.46 | 01-NOV-13:40 | 10.97 | 6.90 | 0.320047E+09 | 511.18 | 01-NOV-13:50 | 10.78 | 6.88 |
December | 76167944.83 | 985.49 | 01-DEC-13:30 | 11.10 | 9.57 | 0.294996E+09 | 429.57 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.247351E+11 | 0.439604E+10 | ||||||||
Minimum of Months | 23082823.79 | 814.92 | 3.22 | 1.08 | 0.277058E+09 | 406.69 | -7.0 | -8.8 | ||
Maximum of Months | 0.513592E+10 | 8731.29 | 27.93 | 21.28 | 0.453970E+09 | 550.78 | 30.00 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39507321.17 | 611.44 | 06-JAN-11:10 | -5.3 | -7.0 | 0.141899E+09 | 271.46 | 06-JAN-11:09 | -5.3 | -7.0 |
February | 96466895.18 | 818.81 | 28-FEB-10:00 | -3.9 | -5.5 | 0.130669E+09 | 328.43 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.686081E+09 | 4108.77 | 16-MAR-12:02 | 13.98 | 12.06 | 0.178429E+09 | 356.46 | 29-MAR-12:09 | 9.50 | 3.37 |
April | 0.142871E+10 | 6268.12 | 24-APR-10:05 | 7.67 | 4.25 | 0.175055E+09 | 356.49 | 19-APR-10:09 | 7.67 | 4.25 |
May | 0.282967E+10 | 7717.66 | 31-MAY-06:03 | 14.68 | 12.32 | 0.202268E+09 | 356.47 | 26-MAY-10:09 | 14.68 | 12.32 |
June | 0.423689E+10 | 13287.53 | 11-JUN-09:32 | 24.03 | 16.62 | 0.204469E+09 | 356.47 | 22-JUN-12:09 | 19.18 | 13.72 |
July | 0.478660E+10 | 13181.01 | 09-JUL-08:12 | 20.77 | 17.49 | 0.191400E+09 | 363.07 | 17-JUL-07:49 | 23.80 | 20.82 |
August | 0.446095E+10 | 13173.59 | 06-AUG-09:12 | 24.47 | 17.45 | 0.213270E+09 | 356.48 | 17-AUG-10:09 | 25.28 | 15.57 |
September | 0.288411E+10 | 11124.83 | 04-SEP-10:02 | 17.98 | 13.30 | 0.187739E+09 | 356.47 | 12-SEP-12:09 | 20.68 | 15.09 |
October | 0.116363E+10 | 5514.43 | 11-OCT-10:05 | 17.15 | 12.50 | 0.182906E+09 | 356.46 | 03-OCT-10:09 | 17.15 | 12.50 |
November | 0.429722E+09 | 4782.38 | 01-NOV-12:02 | 11.20 | 6.39 | 0.154106E+09 | 356.46 | 01-NOV-12:09 | 11.20 | 6.39 |
December | 53013939.23 | 659.42 | 01-DEC-13:10 | 12.97 | 11.34 | 0.137272E+09 | 280.92 | 01-DEC-13:09 | 12.97 | 11.34 |
Annual Sum or Average | 0.230954E+11 | 0.209948E+10 | ||||||||
Minimum of Months | 39507321.17 | 611.44 | -5.3 | -7.0 | 0.130669E+09 | 271.46 | -5.3 | -7.0 | ||
Maximum of Months | 0.478660E+10 | 13287.53 | 24.47 | 17.49 | 0.213270E+09 | 363.07 | 25.28 | 20.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445679E+09 | 4342.22 | 12-JAN-13:30 | -6.7 | -9.2 | 0.323374E+09 | 549.50 | 05-JAN-14:20 | -6.7 | -9.2 |
February | 0.597263E+09 | 6062.19 | 28-FEB-13:40 | 0.00 | -2.9 | 0.297869E+09 | 549.50 | 08-FEB-14:00 | 0.00 | -2.9 |
March | 0.207565E+10 | 9071.88 | 15-MAR-13:30 | 25.55 | 15.84 | 0.399737E+09 | 549.81 | 15-MAR-13:50 | 25.92 | 15.99 |
April | 0.256391E+10 | 7915.50 | 24-APR-12:50 | 11.02 | 5.88 | 0.369848E+09 | 549.70 | 19-APR-09:00 | 11.02 | 5.88 |
May | 0.398433E+10 | 8353.14 | 14-MAY-13:33 | 24.63 | 17.99 | 0.427998E+09 | 549.51 | 05-MAY-13:09 | 24.63 | 17.99 |
June | 0.545474E+10 | 9380.74 | 25-JUN-13:13 | 26.10 | 17.35 | 0.434460E+09 | 550.86 | 12-JUN-13:20 | 26.10 | 17.35 |
July | 0.639530E+10 | 14439.49 | 30-JUL-13:53 | 25.60 | 19.95 | 0.405610E+09 | 550.93 | 17-JUL-13:20 | 25.60 | 19.95 |
August | 0.684278E+10 | 14708.54 | 13-AUG-14:22 | 30.00 | 23.06 | 0.454432E+09 | 550.63 | 10-AUG-13:20 | 30.00 | 23.06 |
September | 0.560792E+10 | 14903.31 | 10-SEP-11:43 | 16.60 | 10.77 | 0.400186E+09 | 550.51 | 08-SEP-13:20 | 16.60 | 10.77 |
October | 0.333653E+10 | 11661.64 | 11-OCT-12:30 | 21.95 | 13.79 | 0.396648E+09 | 550.24 | 30-OCT-13:50 | 14.72 | 8.63 |
November | 0.146533E+10 | 8297.56 | 03-NOV-12:25 | 8.35 | 4.56 | 0.347728E+09 | 549.51 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.386740E+09 | 4114.97 | 16-DEC-13:20 | 5.60 | 3.10 | 0.304828E+09 | 549.50 | 11-DEC-14:20 | 5.60 | 3.10 |
Annual Sum or Average | 0.391562E+11 | 0.456272E+10 | ||||||||
Minimum of Months | 0.386740E+09 | 4114.97 | -6.7 | -9.2 | 0.297869E+09 | 549.50 | -6.7 | -9.2 | ||
Maximum of Months | 0.684278E+10 | 14903.31 | 30.00 | 23.06 | 0.454432E+09 | 550.93 | 30.00 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58870724.05 | 706.76 | 12-JAN-16:10 | -6.2 | -8.3 | 0.194193E+09 | 297.00 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 0.116883E+09 | 1741.21 | 28-FEB-16:30 | 0.00 | -2.6 | 0.178102E+09 | 338.67 | 28-FEB-16:00 | -0.6 | -3.0 |
March | 0.811448E+09 | 3248.09 | 21-MAR-16:00 | 4.40 | 1.34 | 0.237210E+09 | 347.85 | 15-MAR-13:20 | 4.40 | 1.34 |
April | 0.146553E+10 | 6259.87 | 24-APR-16:00 | 13.30 | 7.63 | 0.227107E+09 | 347.85 | 20-APR-13:20 | 13.30 | 7.63 |
May | 0.288482E+10 | 13499.11 | 07-MAY-16:22 | 15.00 | 5.94 | 0.270740E+09 | 347.85 | 17-MAY-09:20 | 19.23 | 14.37 |
June | 0.451254E+10 | 14480.42 | 11-JUN-16:11 | 25.60 | 17.82 | 0.275359E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.478766E+10 | 13947.28 | 02-JUL-17:12 | 24.63 | 16.88 | 0.256918E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.455963E+10 | 14097.89 | 06-AUG-16:31 | 27.80 | 18.98 | 0.287685E+09 | 347.88 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.285195E+10 | 12164.70 | 04-SEP-15:23 | 18.60 | 13.14 | 0.252488E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.132317E+10 | 5889.50 | 11-OCT-16:00 | 21.70 | 14.52 | 0.240139E+09 | 347.85 | 04-OCT-13:20 | 21.70 | 14.52 |
November | 0.542674E+09 | 2053.02 | 03-NOV-15:00 | 10.00 | 5.48 | 0.208108E+09 | 347.83 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 78028271.10 | 711.78 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187360E+09 | 297.99 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.239932E+11 | 0.281541E+10 | ||||||||
Minimum of Months | 58870724.05 | 706.76 | -6.2 | -8.3 | 0.178102E+09 | 297.00 | -6.3 | -8.3 | ||
Maximum of Months | 0.478766E+10 | 14480.42 | 27.80 | 18.98 | 0.287685E+09 | 347.88 | 27.80 | 18.98 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556941E+09 | 19140.98 | 02-JAN-05:01 | -0.7 |
February | 33429816.36 | 15842.47 | 13-FEB-07:11 | -9.4 |
March | 911396.94 | 15189.95 | 06-MAR-07:01 | -10.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 18150001.38 | 15650.62 | 29-DEC-07:01 | -7.1 |
Annual Sum or Average | 0.609432E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.8 | |
Maximum of Months | 0.556941E+09 | 19140.98 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.592361E+10 | 13939.14 | 24-JAN-06:13 | -12.0 |
February | 0.515146E+10 | 15050.56 | 06-FEB-06:12 | -13.9 |
March | 0.241047E+10 | 13669.95 | 06-MAR-06:13 | -11.1 |
April | 0.967134E+09 | 10538.81 | 17-APR-05:13 | -4.1 |
May | 0.400388E+09 | 3046.81 | 08-MAY-05:03 | 3.40 |
June | 0.150644E+09 | 2847.31 | 14-JUN-05:03 | 6.78 |
July | 79507698.10 | 3188.58 | 20-JUL-05:03 | 23.90 |
August | 0.126104E+09 | 2329.07 | 03-AUG-05:03 | 11.10 |
September | 0.323429E+09 | 4487.23 | 04-SEP-07:57 | 12.80 |
October | 0.933163E+09 | 8287.72 | 30-OCT-06:02 | -0.4 |
November | 0.195673E+10 | 10655.08 | 24-NOV-06:13 | -3.7 |
December | 0.537990E+10 | 15119.36 | 11-DEC-06:06 | -18.5 |
Annual Sum or Average | 0.238025E+11 | |||
Minimum of Months | 79507698.10 | 2329.07 | -18.5 | |
Maximum of Months | 0.592361E+10 | 15119.36 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284302E+10 | 9246.75 | 02-JAN-07:03 | -1.1 |
February | 0.246603E+10 | 8061.89 | 06-FEB-06:12 | -13.9 |
March | 0.133312E+10 | 5721.28 | 06-MAR-07:11 | -10.5 |
April | 0.646840E+09 | 3182.06 | 17-APR-10:05 | 2.30 |
May | 97521933.31 | 3438.44 | 07-MAY-16:22 | 15.00 |
June | 22461096.62 | 2990.96 | 11-JUN-14:52 | 26.10 |
July | 26735912.61 | 2571.83 | 02-JUL-15:52 | 25.00 |
August | 18303227.61 | 4113.28 | 13-AUG-14:22 | 30.00 |
September | 40616123.34 | 4289.89 | 04-SEP-15:23 | 18.60 |
October | 0.603520E+09 | 3489.83 | 30-OCT-10:05 | 9.18 |
November | 0.108978E+10 | 3474.72 | 24-NOV-07:02 | -3.2 |
December | 0.243490E+10 | 8328.11 | 26-DEC-07:03 | -12.3 |
Annual Sum or Average | 0.116229E+11 | |||
Minimum of Months | 18303227.61 | 2571.83 | -13.9 | |
Maximum of Months | 0.284302E+10 | 9246.75 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215327E+10 | 7992.35 | 02-JAN-08:10 | -1.1 |
February | 0.174236E+10 | 4470.64 | 06-FEB-07:01 | -14.1 |
March | 0.831916E+09 | 3244.05 | 06-MAR-08:17 | -9.0 |
April | 0.304221E+09 | 2043.95 | 17-APR-07:19 | -2.6 |
May | 16872832.19 | 1604.17 | 07-MAY-15:32 | 15.00 |
June | 12320243.17 | 1446.42 | 04-JUN-14:30 | 20.00 |
July | 15777123.50 | 1615.05 | 08-JUL-17:42 | 25.00 |
August | 13801669.17 | 1764.46 | 13-AUG-15:23 | 29.70 |
September | 17338606.20 | 2343.80 | 04-SEP-15:23 | 18.60 |
October | 0.227701E+09 | 2096.05 | 22-OCT-12:03 | 21.70 |
November | 0.705423E+09 | 2061.40 | 24-NOV-08:09 | -2.6 |
December | 0.170393E+10 | 4540.36 | 26-DEC-07:01 | -12.3 |
Annual Sum or Average | 0.774493E+10 | |||
Minimum of Months | 12320243.17 | 1446.42 | -14.1 | |
Maximum of Months | 0.215327E+10 | 7992.35 | 29.70 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123020E+10 | 21995.50 | 02-JAN-05:01 | -0.7 |
February | 0.811311E+09 | 19610.43 | 06-FEB-06:01 | -13.9 |
March | 76070288.27 | 18649.96 | 06-MAR-06:01 | -11.1 |
April | 6057658.11 | 17351.13 | 17-APR-06:01 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 21256435.96 | 17318.14 | 24-NOV-07:01 | -3.2 |
December | 0.603191E+09 | 20210.61 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.274808E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.123020E+10 | 21995.50 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396136E+10 | 29703.31 | 02-JAN-05:01 | -0.7 |
February | 0.320522E+10 | 29701.88 | 06-FEB-05:01 | -14.8 |
March | 0.828718E+09 | 28352.40 | 06-MAR-05:01 | -11.1 |
April | 0.123576E+09 | 27046.30 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 65783368.48 | 25814.14 | 30-OCT-05:01 | -0.1 |
November | 0.416527E+09 | 26979.98 | 24-NOV-06:01 | -3.8 |
December | 0.306585E+10 | 29851.26 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.116670E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.396136E+10 | 29851.26 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581275E+10 | 9856.20 | 29-JAN-22:23 | -9.2 |
February | 0.497304E+10 | 10288.37 | 06-FEB-03:22 | -14.4 |
March | 0.189754E+10 | 9561.76 | 06-MAR-03:33 | -10.9 |
April | 0.316006E+09 | 9309.65 | 17-APR-04:01 | -3.4 |
May | 1199477.87 | 4993.53 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1823169.67 | 5120.56 | 30-SEP-06:03 | 7.30 |
October | 0.226910E+09 | 8790.76 | 30-OCT-04:02 | -0.5 |
November | 0.112710E+10 | 9428.75 | 24-NOV-05:01 | -3.0 |
December | 0.511693E+10 | 10277.17 | 26-DEC-04:22 | -11.9 |
Annual Sum or Average | 0.194733E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.4 | |
Maximum of Months | 0.581275E+10 | 10288.37 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338707E+10 | 11383.92 | 30-JAN-05:01 | -9.5 |
February | 0.289181E+10 | 11938.03 | 06-FEB-03:22 | -14.4 |
March | 0.850304E+09 | 11030.22 | 20-MAR-04:01 | -2.8 |
April | 0.122100E+09 | 10842.60 | 17-APR-04:01 | -3.4 |
May | 228310.47 | 761.03 | 02-MAY-06:05 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1025650.98 | 3511.37 | 30-SEP-06:03 | 7.30 |
October | 0.113395E+09 | 9933.44 | 17-OCT-05:01 | -2.8 |
November | 0.643559E+09 | 11042.99 | 24-NOV-05:01 | -3.0 |
December | 0.318589E+10 | 11945.12 | 26-DEC-04:22 | -11.9 |
Annual Sum or Average | 0.111954E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.4 | |
Maximum of Months | 0.338707E+10 | 11945.12 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422312E+10 | 14029.31 | 29-JAN-22:23 | -9.2 |
February | 0.373263E+10 | 14741.40 | 13-FEB-04:12 | -8.9 |
March | 0.110014E+10 | 13557.35 | 20-MAR-04:01 | -2.8 |
April | 0.259286E+09 | 13211.64 | 17-APR-04:01 | -3.4 |
May | 2546330.44 | 7853.58 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1094353.67 | 4102.06 | 30-SEP-06:03 | 7.30 |
October | 0.148599E+09 | 12113.55 | 30-OCT-05:01 | -0.1 |
November | 0.823734E+09 | 13556.89 | 24-NOV-05:01 | -3.0 |
December | 0.389827E+10 | 14762.88 | 26-DEC-04:22 | -11.9 |
Annual Sum or Average | 0.141894E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.9 | |
Maximum of Months | 0.422312E+10 | 14762.88 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365755E+10 | 12384.96 | 30-JAN-05:01 | -9.5 |
February | 0.310776E+10 | 12977.14 | 06-FEB-03:22 | -14.4 |
March | 0.100735E+10 | 11984.09 | 20-MAR-04:01 | -2.8 |
April | 0.186022E+09 | 11560.29 | 17-APR-04:01 | -3.4 |
May | 1010211.54 | 3875.40 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1051252.30 | 2863.38 | 30-SEP-06:03 | 7.30 |
October | 0.135734E+09 | 10809.63 | 16-OCT-05:01 | 1.20 |
November | 0.708551E+09 | 11962.14 | 24-NOV-05:01 | -3.0 |
December | 0.324269E+10 | 12974.96 | 26-DEC-04:22 | -11.9 |
Annual Sum or Average | 0.120477E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.4 | |
Maximum of Months | 0.365755E+10 | 12977.14 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414834E+10 | 7400.13 | 02-JAN-02:62 | -1.7 |
February | 0.345308E+10 | 7502.42 | 06-FEB-04:42 | -15.0 |
March | 0.145130E+10 | 7273.88 | 06-MAR-05:01 | -11.1 |
April | 0.187479E+09 | 6551.47 | 17-APR-05:01 | -4.0 |
May | 849056.52 | 3432.39 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 11951906.42 | 5859.18 | 17-OCT-06:01 | -2.8 |
November | 0.216628E+09 | 6374.07 | 24-NOV-06:01 | -3.8 |
December | 0.275726E+10 | 7262.82 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.122269E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.414834E+10 | 7502.42 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234660E+10 | 8957.92 | 30-JAN-05:01 | -9.5 |
February | 0.185813E+10 | 9174.84 | 06-FEB-03:22 | -14.4 |
March | 0.471795E+09 | 8665.26 | 06-MAR-05:01 | -11.1 |
April | 41555086.42 | 8002.28 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 4895384.94 | 7152.02 | 30-OCT-06:02 | -0.4 |
November | 0.115985E+09 | 7862.61 | 24-NOV-06:01 | -3.8 |
December | 0.166210E+10 | 8911.96 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.650106E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.234660E+10 | 9174.84 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.690622E+10 | 12738.03 | 04-JAN-08:00 | -13.3 |
February | 0.595664E+10 | 13198.99 | 07-FEB-08:00 | -15.6 |
March | 0.308763E+10 | 12266.46 | 07-MAR-07:10 | -12.9 |
April | 0.160653E+10 | 11013.07 | 17-APR-06:10 | -4.2 |
May | 0.569893E+09 | 9625.63 | 01-MAY-06:10 | 2.35 |
June | 0.115105E+09 | 8576.59 | 06-JUN-06:07 | 7.67 |
July | 2857145.10 | 3225.03 | 07-JUL-06:08 | 13.17 |
August | 17650066.99 | 4964.88 | 31-AUG-06:08 | 11.78 |
September | 0.140395E+09 | 8518.59 | 05-SEP-06:04 | 6.38 |
October | 0.844437E+09 | 10242.58 | 17-OCT-06:10 | -2.8 |
November | 0.213092E+10 | 10859.60 | 24-NOV-07:10 | -3.2 |
December | 0.576962E+10 | 12920.64 | 11-DEC-08:00 | -15.0 |
Annual Sum or Average | 0.271479E+11 | |||
Minimum of Months | 2857145.10 | 3225.03 | -15.6 | |
Maximum of Months | 0.690622E+10 | 13198.99 | 13.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257481E+10 | 9369.68 | 30-JAN-05:01 | -9.5 |
February | 0.204631E+10 | 9568.23 | 06-FEB-04:42 | -15.0 |
March | 0.528138E+09 | 9056.68 | 06-MAR-05:01 | -11.1 |
April | 62923211.05 | 8161.19 | 17-APR-05:01 | -4.0 |
May | 135255.28 | 901.70 | 01-MAY-06:03 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 5190600.63 | 7444.91 | 30-OCT-06:02 | -0.4 |
November | 0.122163E+09 | 8125.09 | 24-NOV-06:01 | -3.8 |
December | 0.170236E+10 | 9283.47 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.704203E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.257481E+10 | 9568.23 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372628E+10 | 8392.69 | 02-JAN-02:62 | -1.7 |
February | 0.307322E+10 | 8604.15 | 06-FEB-03:02 | -14.1 |
March | 0.892809E+09 | 8075.84 | 06-MAR-05:01 | -11.1 |
April | 85762777.23 | 7407.63 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 37404337.16 | 7099.48 | 30-OCT-05:01 | -0.1 |
November | 0.359817E+09 | 7553.67 | 24-NOV-05:01 | -3.0 |
December | 0.301515E+10 | 8415.43 | 11-DEC-03:52 | -17.2 |
Annual Sum or Average | 0.111904E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.372628E+10 | 8604.15 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211796E+10 | 9955.49 | 09-JAN-05:11 | -9.4 |
February | 0.173387E+10 | 10234.76 | 06-FEB-03:02 | -14.1 |
March | 0.354205E+09 | 9630.71 | 06-MAR-05:01 | -11.1 |
April | 28304453.39 | 8780.14 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 21693954.27 | 8388.10 | 30-OCT-05:01 | -0.1 |
November | 0.215479E+09 | 8728.98 | 25-NOV-06:01 | -1.7 |
December | 0.184240E+10 | 10059.02 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.631392E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.1 | |
Maximum of Months | 0.211796E+10 | 10234.76 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251835E+10 | 12486.78 | 09-JAN-05:11 | -9.4 |
February | 0.211710E+10 | 12846.64 | 06-FEB-03:02 | -14.1 |
March | 0.409994E+09 | 12089.09 | 06-MAR-05:01 | -11.1 |
April | 67386406.94 | 11014.17 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 23393746.93 | 10599.23 | 30-OCT-05:01 | -0.1 |
November | 0.248506E+09 | 11075.18 | 24-NOV-06:01 | -3.8 |
December | 0.208752E+10 | 12648.23 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.747225E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.1 | |
Maximum of Months | 0.251835E+10 | 12846.64 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232471E+10 | 10057.17 | 09-JAN-05:11 | -9.4 |
February | 0.188218E+10 | 10351.43 | 06-FEB-03:02 | -14.1 |
March | 0.427940E+09 | 9701.71 | 06-MAR-05:01 | -11.1 |
April | 47609397.82 | 8645.37 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 23215539.87 | 8347.55 | 30-OCT-05:01 | -0.1 |
November | 0.231387E+09 | 8691.80 | 24-NOV-06:01 | -3.8 |
December | 0.188977E+10 | 10153.61 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.682680E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.1 | |
Maximum of Months | 0.232471E+10 | 10351.43 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.452429E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.384976E+09 | 643.48 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.427716E+09 | 525.84 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.368695E+09 | 410.55 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.386881E+09 | 388.89 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379536E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.358298E+09 | 383.21 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.403485E+09 | 388.42 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.377601E+09 | 505.20 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.414698E+09 | 710.10 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.453421E+09 | 735.45 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.454233E+09 | 735.45 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.486197E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.358298E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.454233E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281465E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242144E+09 | 410.90 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269753E+09 | 260.17 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233694E+09 | 251.23 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246208E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241668E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227953E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256463E+09 | 243.23 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238524E+09 | 258.21 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259456E+09 | 376.26 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281951E+09 | 465.60 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281770E+09 | 465.60 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306105E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227953E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.281951E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.436225E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.378324E+09 | 629.12 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.424606E+09 | 510.19 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.369440E+09 | 409.92 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389304E+09 | 390.83 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381877E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360567E+09 | 385.43 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405048E+09 | 389.76 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.376658E+09 | 493.39 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.407190E+09 | 625.30 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.438267E+09 | 735.45 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.437836E+09 | 735.45 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.480534E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360567E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.438267E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280334E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241296E+09 | 405.33 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269717E+09 | 350.75 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233582E+09 | 304.09 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245345E+09 | 252.45 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240518E+09 | 241.75 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227271E+09 | 249.69 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255581E+09 | 254.01 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.239065E+09 | 337.76 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.261141E+09 | 449.50 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281398E+09 | 465.57 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281829E+09 | 465.57 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.305708E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227271E+09 | 241.75 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.281829E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.450557E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.384022E+09 | 639.92 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.426958E+09 | 517.57 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.368403E+09 | 408.52 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.386479E+09 | 385.83 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379365E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.358059E+09 | 379.88 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.403059E+09 | 385.33 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.376942E+09 | 496.23 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.413632E+09 | 708.74 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.451766E+09 | 735.45 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.452318E+09 | 735.45 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.485156E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.358059E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.452318E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280643E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241666E+09 | 409.22 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269423E+09 | 258.92 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233499E+09 | 249.60 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245970E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241524E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227786E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256264E+09 | 241.40 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238195E+09 | 256.87 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259068E+09 | 373.18 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281365E+09 | 465.60 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281108E+09 | 465.60 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.305651E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227786E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.281365E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435259E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377877E+09 | 624.84 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.424110E+09 | 501.15 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.369062E+09 | 407.86 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.388777E+09 | 387.87 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381560E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360226E+09 | 382.24 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.404650E+09 | 386.74 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.376117E+09 | 483.86 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.406638E+09 | 620.01 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.437558E+09 | 735.45 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.436760E+09 | 735.45 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.479859E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360226E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.437558E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.279582E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.240863E+09 | 403.48 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269405E+09 | 347.23 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233239E+09 | 299.18 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245085E+09 | 250.99 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240341E+09 | 240.30 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227081E+09 | 248.15 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255341E+09 | 252.63 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238691E+09 | 333.87 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.260576E+09 | 448.76 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280722E+09 | 465.57 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.280952E+09 | 465.57 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.305188E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227081E+09 | 240.30 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.280952E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.452427E+09 | 735.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.384975E+09 | 643.47 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.427716E+09 | 525.83 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.368694E+09 | 410.55 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.386881E+09 | 388.89 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379536E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.358298E+09 | 383.20 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.403484E+09 | 388.41 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.377601E+09 | 505.18 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.414697E+09 | 710.10 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.453419E+09 | 735.45 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.454230E+09 | 735.45 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.486196E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.358298E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.454230E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.281464E+09 | 465.60 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242144E+09 | 410.90 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269753E+09 | 260.17 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233693E+09 | 251.23 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246207E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241668E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227953E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256463E+09 | 243.23 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238524E+09 | 258.20 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259455E+09 | 376.25 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281950E+09 | 465.60 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281769E+09 | 465.60 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306104E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227953E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.281950E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.436224E+09 | 735.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.378323E+09 | 629.11 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.424606E+09 | 510.17 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.369440E+09 | 409.92 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.389303E+09 | 390.82 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381877E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360566E+09 | 385.43 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405047E+09 | 389.75 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.376657E+09 | 493.37 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.407189E+09 | 625.30 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.438266E+09 | 735.45 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.437835E+09 | 735.45 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.480533E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360566E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.438266E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.280333E+09 | 465.57 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241295E+09 | 405.33 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269717E+09 | 350.74 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.233582E+09 | 304.07 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245345E+09 | 252.45 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240517E+09 | 241.74 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227271E+09 | 249.68 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255580E+09 | 254.01 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.239065E+09 | 337.75 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.261140E+09 | 449.50 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281397E+09 | 465.57 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.281827E+09 | 465.57 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.305707E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227271E+09 | 241.74 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.281827E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.452429E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188754E+10 |
February | 0.901968E+09 | 0.384976E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200983E+10 |
March | 0.107774E+10 | 0.427716E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 454267.47 | 0.123837E+10 |
April | 0.956342E+09 | 0.368695E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100931E+10 |
May | 0.103597E+10 | 0.386881E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 252837.48 | 0.627039E+09 |
June | 0.103308E+10 | 0.379536E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10720594.01 | 0.365794E+09 |
July | 0.959235E+09 | 0.358298E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26828188.86 | 0.216531E+09 |
August | 0.107774E+10 | 0.403485E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21223835.74 | 0.247712E+09 |
September | 0.956342E+09 | 0.377601E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1540260.57 | 0.364991E+09 |
October | 0.994195E+09 | 0.414698E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772393E+09 |
November | 0.984487E+09 | 0.453421E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101837E+10 |
December | 0.959235E+09 | 0.454233E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199143E+10 |
Annual Sum or Average | 0.119305E+11 | 0.486197E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61019984.13 | 0.117493E+11 |
Minimum of Months | 0.901968E+09 | 0.358298E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216531E+09 |
Maximum of Months | 0.107774E+10 | 0.454233E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26828188.86 | 0.200983E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.281465E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126047E+10 |
February | 0.571020E+09 | 0.242144E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134313E+10 |
March | 0.682301E+09 | 0.269753E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 291704.88 | 0.836744E+09 |
April | 0.605444E+09 | 0.233694E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689561E+09 |
May | 0.655854E+09 | 0.246208E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134816.39 | 0.435379E+09 |
June | 0.654023E+09 | 0.241668E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7048925.31 | 0.251897E+09 |
July | 0.607275E+09 | 0.227953E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17371688.36 | 0.149830E+09 |
August | 0.682301E+09 | 0.256463E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13382016.46 | 0.171744E+09 |
September | 0.605444E+09 | 0.238524E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 996521.35 | 0.252567E+09 |
October | 0.629407E+09 | 0.259456E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531953E+09 |
November | 0.623262E+09 | 0.281951E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685371E+09 |
December | 0.607275E+09 | 0.281770E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132952E+10 |
Annual Sum or Average | 0.755301E+10 | 0.306105E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39225672.75 | 0.793817E+10 |
Minimum of Months | 0.571020E+09 | 0.227953E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149830E+09 |
Maximum of Months | 0.682301E+09 | 0.281951E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17371688.36 | 0.134313E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.436225E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192476E+10 |
February | 0.901968E+09 | 0.378324E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203720E+10 |
March | 0.107774E+10 | 0.424606E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 437443.88 | 0.130283E+10 |
April | 0.956342E+09 | 0.369440E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104822E+10 |
May | 0.103597E+10 | 0.389304E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 202455.13 | 0.648097E+09 |
June | 0.103308E+10 | 0.381877E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10597913.58 | 0.370836E+09 |
July | 0.959235E+09 | 0.360567E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26095233.38 | 0.222210E+09 |
August | 0.107774E+10 | 0.405048E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19716541.54 | 0.259270E+09 |
September | 0.956342E+09 | 0.376658E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1391525.72 | 0.388130E+09 |
October | 0.994195E+09 | 0.407190E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830361E+09 |
November | 0.984487E+09 | 0.438267E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106122E+10 |
December | 0.959235E+09 | 0.437836E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202960E+10 |
Annual Sum or Average | 0.119305E+11 | 0.480534E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58441113.24 | 0.121227E+11 |
Minimum of Months | 0.901968E+09 | 0.360567E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222210E+09 |
Maximum of Months | 0.107774E+10 | 0.438267E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26095233.38 | 0.203720E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.280334E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126079E+10 |
February | 0.570983E+09 | 0.241296E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134547E+10 |
March | 0.682256E+09 | 0.269717E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297956.44 | 0.850462E+09 |
April | 0.605404E+09 | 0.233582E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697340E+09 |
May | 0.655811E+09 | 0.245345E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134606.76 | 0.439762E+09 |
June | 0.653980E+09 | 0.240518E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6804562.09 | 0.256963E+09 |
July | 0.607235E+09 | 0.227271E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17361704.28 | 0.155239E+09 |
August | 0.682256E+09 | 0.255581E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13393783.21 | 0.177076E+09 |
September | 0.605404E+09 | 0.239065E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 904892.18 | 0.254759E+09 |
October | 0.629366E+09 | 0.261141E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527705E+09 |
November | 0.623221E+09 | 0.281398E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682551E+09 |
December | 0.607235E+09 | 0.281829E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132890E+10 |
Annual Sum or Average | 0.755252E+10 | 0.305708E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38897504.96 | 0.797702E+10 |
Minimum of Months | 0.570983E+09 | 0.227271E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155239E+09 |
Maximum of Months | 0.682256E+09 | 0.281829E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17361704.28 | 0.134547E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.450557E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104326E+10 |
February | 0.901968E+09 | 0.384022E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110454E+10 |
March | 0.107774E+10 | 0.426958E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 545301.80 | 0.676551E+09 |
April | 0.956342E+09 | 0.368403E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539691E+09 |
May | 0.103597E+10 | 0.386479E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519294.65 | 0.316238E+09 |
June | 0.103308E+10 | 0.379365E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8230698.46 | 0.186784E+09 |
July | 0.959235E+09 | 0.358059E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16568797.55 | 0.106861E+09 |
August | 0.107774E+10 | 0.403059E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13712788.05 | 0.130512E+09 |
September | 0.956342E+09 | 0.376942E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 919326.76 | 0.203094E+09 |
October | 0.994195E+09 | 0.413632E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455679E+09 |
November | 0.984487E+09 | 0.451766E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598441E+09 |
December | 0.959235E+09 | 0.452318E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112451E+10 |
Annual Sum or Average | 0.119305E+11 | 0.485156E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40496207.28 | 0.648616E+10 |
Minimum of Months | 0.901968E+09 | 0.358059E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106861E+09 |
Maximum of Months | 0.107774E+10 | 0.452318E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16568797.55 | 0.112451E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.280643E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698971E+09 |
February | 0.571020E+09 | 0.241666E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739311E+09 |
March | 0.682301E+09 | 0.269423E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198807.12 | 0.460734E+09 |
April | 0.605444E+09 | 0.233499E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378987E+09 |
May | 0.655854E+09 | 0.245970E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 184227.19 | 0.229826E+09 |
June | 0.654023E+09 | 0.241524E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4028809.36 | 0.134031E+09 |
July | 0.607275E+09 | 0.227786E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9787077.85 | 78724388.05 |
August | 0.682301E+09 | 0.256264E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7572432.21 | 94163464.07 |
September | 0.605444E+09 | 0.238195E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570507.95 | 0.143287E+09 |
October | 0.629407E+09 | 0.259068E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317977E+09 |
November | 0.623262E+09 | 0.281365E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406288E+09 |
December | 0.607275E+09 | 0.281108E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751342E+09 |
Annual Sum or Average | 0.755301E+10 | 0.305651E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22341861.69 | 0.443364E+10 |
Minimum of Months | 0.571020E+09 | 0.227786E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78724388.05 |
Maximum of Months | 0.682301E+09 | 0.281365E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9787077.85 | 0.751342E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.435259E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720678E+10 |
February | 0.901968E+09 | 0.377877E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669858E+10 |
March | 0.107774E+10 | 0.424110E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7794841.82 | 0.556792E+10 |
April | 0.956342E+09 | 0.369062E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382020E+10 |
May | 0.103597E+10 | 0.388777E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2386137.54 | 0.243347E+10 |
June | 0.103308E+10 | 0.381560E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129164E+09 | 0.130092E+10 |
July | 0.959235E+09 | 0.360226E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358911E+09 | 0.543676E+09 |
August | 0.107774E+10 | 0.404650E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277761E+09 | 0.923946E+09 |
September | 0.956342E+09 | 0.376117E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13766232.49 | 0.158907E+10 |
October | 0.994195E+09 | 0.406638E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348806E+10 |
November | 0.984487E+09 | 0.437558E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451616E+10 |
December | 0.959235E+09 | 0.436760E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668203E+10 |
Annual Sum or Average | 0.119305E+11 | 0.479859E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789784E+09 | 0.447708E+11 |
Minimum of Months | 0.901968E+09 | 0.360226E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543676E+09 |
Maximum of Months | 0.107774E+10 | 0.437558E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358911E+09 | 0.720678E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.279582E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696918E+09 |
February | 0.570983E+09 | 0.240863E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739967E+09 |
March | 0.682256E+09 | 0.269405E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257622.34 | 0.467365E+09 |
April | 0.605404E+09 | 0.233239E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379876E+09 |
May | 0.655811E+09 | 0.245085E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74648.47 | 0.233974E+09 |
June | 0.653980E+09 | 0.240341E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3905264.17 | 0.138864E+09 |
July | 0.607235E+09 | 0.227081E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9879691.14 | 83307310.93 |
August | 0.682256E+09 | 0.255341E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7546172.86 | 98265205.43 |
September | 0.605404E+09 | 0.238691E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 501210.33 | 0.145035E+09 |
October | 0.629366E+09 | 0.260576E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314710E+09 |
November | 0.623221E+09 | 0.280722E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404348E+09 |
December | 0.607235E+09 | 0.280952E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750782E+09 |
Annual Sum or Average | 0.755252E+10 | 0.305188E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22164609.31 | 0.445341E+10 |
Minimum of Months | 0.570983E+09 | 0.227081E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83307310.93 |
Maximum of Months | 0.682256E+09 | 0.280952E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9879691.14 | 0.750782E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.452427E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161552E+10 |
February | 0.901968E+09 | 0.384975E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171692E+10 |
March | 0.107774E+10 | 0.427716E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 397989.43 | 0.107850E+10 |
April | 0.956342E+09 | 0.368694E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884645E+09 |
May | 0.103597E+10 | 0.386881E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351814.71 | 0.539990E+09 |
June | 0.103308E+10 | 0.379536E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9618045.91 | 0.310671E+09 |
July | 0.959235E+09 | 0.358298E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23213536.52 | 0.181866E+09 |
August | 0.107774E+10 | 0.403484E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18490627.53 | 0.211260E+09 |
September | 0.956342E+09 | 0.377601E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1344306.72 | 0.319470E+09 |
October | 0.994195E+09 | 0.414697E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695770E+09 |
November | 0.984487E+09 | 0.453419E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912075E+09 |
December | 0.959235E+09 | 0.454230E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172072E+10 |
Annual Sum or Average | 0.119305E+11 | 0.486196E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53416320.82 | 0.101874E+11 |
Minimum of Months | 0.901968E+09 | 0.358298E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181866E+09 |
Maximum of Months | 0.107774E+10 | 0.454230E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23213536.52 | 0.172072E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.281464E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107818E+10 |
February | 0.421807E+09 | 0.242144E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114585E+10 |
March | 0.502994E+09 | 0.269753E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201903.54 | 0.731749E+09 |
April | 0.447140E+09 | 0.233693E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605046E+09 |
May | 0.484071E+09 | 0.246207E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134864.49 | 0.374576E+09 |
June | 0.482240E+09 | 0.241668E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5700258.10 | 0.215096E+09 |
July | 0.448971E+09 | 0.227953E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14230479.95 | 0.126899E+09 |
August | 0.502994E+09 | 0.256463E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11036620.06 | 0.146863E+09 |
September | 0.447140E+09 | 0.238524E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 784218.17 | 0.220800E+09 |
October | 0.465148E+09 | 0.259455E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478602E+09 |
November | 0.460569E+09 | 0.281950E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614881E+09 |
December | 0.448971E+09 | 0.281769E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114644E+10 |
Annual Sum or Average | 0.557719E+10 | 0.306104E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32088344.32 | 0.688499E+10 |
Minimum of Months | 0.421807E+09 | 0.227953E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126899E+09 |
Maximum of Months | 0.502994E+09 | 0.281950E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14230479.95 | 0.114644E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.436224E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165706E+10 |
February | 0.901968E+09 | 0.378323E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174603E+10 |
March | 0.107774E+10 | 0.424606E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374476.93 | 0.113698E+10 |
April | 0.956342E+09 | 0.369440E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917074E+09 |
May | 0.103597E+10 | 0.389303E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171785.02 | 0.557553E+09 |
June | 0.103308E+10 | 0.381877E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9062850.93 | 0.316180E+09 |
July | 0.959235E+09 | 0.360566E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22265437.36 | 0.188069E+09 |
August | 0.107774E+10 | 0.405047E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16766279.71 | 0.221404E+09 |
September | 0.956342E+09 | 0.376657E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1190612.58 | 0.337437E+09 |
October | 0.994195E+09 | 0.407189E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741714E+09 |
November | 0.984487E+09 | 0.438266E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949343E+09 |
December | 0.959235E+09 | 0.437835E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176154E+10 |
Annual Sum or Average | 0.119305E+11 | 0.480533E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49831442.53 | 0.105304E+11 |
Minimum of Months | 0.901968E+09 | 0.360566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188069E+09 |
Maximum of Months | 0.107774E+10 | 0.438266E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22265437.36 | 0.176154E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.280333E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107797E+10 |
February | 0.570983E+09 | 0.241295E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114807E+10 |
March | 0.682256E+09 | 0.269717E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257216.88 | 0.741038E+09 |
April | 0.605404E+09 | 0.233582E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610310E+09 |
May | 0.655811E+09 | 0.245345E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114455.68 | 0.378506E+09 |
June | 0.653980E+09 | 0.240517E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5752378.36 | 0.219236E+09 |
July | 0.607235E+09 | 0.227271E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14804301.31 | 0.131826E+09 |
August | 0.682256E+09 | 0.255580E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11385243.88 | 0.151387E+09 |
September | 0.605404E+09 | 0.239065E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 765710.24 | 0.222229E+09 |
October | 0.629366E+09 | 0.261140E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474126E+09 |
November | 0.623221E+09 | 0.281397E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611235E+09 |
December | 0.607235E+09 | 0.281827E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114768E+10 |
Annual Sum or Average | 0.755252E+10 | 0.305707E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33079306.34 | 0.691361E+10 |
Minimum of Months | 0.570983E+09 | 0.227271E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131826E+09 |
Maximum of Months | 0.682256E+09 | 0.281827E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14804301.31 | 0.114807E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220813E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233669E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714564.90 | 0.149654E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122435E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556804.03 | 0.726425E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10295163.98 | 0.416717E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25484675.28 | 0.239192E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21081507.61 | 0.286986E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102504.96 | 0.444864E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990092E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129933E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238144E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59235220.76 | 0.140508E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239192E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25484675.28 | 0.238144E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274943E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290797E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919304.58 | 0.186941E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153871E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650871.91 | 0.931756E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12494144.64 | 0.538840E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31612370.84 | 0.311593E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26671091.59 | 0.368393E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1444765.74 | 0.559667E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120498E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156882E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293487E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73792549.30 | 0.174844E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311593E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31612370.84 | 0.293487E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281715E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299957E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47338.45 | 0.191605E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158847E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34059.25 | 0.100455E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7717157.62 | 0.589938E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23801551.65 | 0.349343E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16263673.68 | 0.394298E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752383.70 | 0.584984E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121103E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155628E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298200E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48616164.36 | 0.179937E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349343E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23801551.65 | 0.299957E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.48 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 643.48 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3648.40 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 525.84 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2005.04 | 01-MAR-22:03 |
April | 1306.65 | 03-APR-09:09 | 410.55 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1814.78 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 388.89 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 | 14-MAY-15:00 | 1190.87 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.14 | 17-JUN-17:03 | 1041.80 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 383.21 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 748.06 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 388.42 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.86 | 13-AUG-12:53 | 491.99 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 505.20 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 16-SEP-13:00 | 843.85 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 710.10 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1031.69 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1796.41 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3405.70 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.99 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 340.86 | 3648.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.97 | 12-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 410.90 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 260.17 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1337.77 | 01-MAR-22:03 |
April | 827.22 | 03-APR-09:09 | 251.23 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1213.79 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 10-MAY-14:00 | 864.20 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.15 | 17-JUN-17:03 | 696.73 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 15-JUL-15:00 | 497.00 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 243.23 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.73 | 13-AUG-12:38 | 327.50 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 258.21 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 16-SEP-13:00 | 558.61 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 376.26 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 720.11 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1192.37 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2264.80 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.50 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 220.73 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.49 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 629.12 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3754.71 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 510.19 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2168.71 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 409.92 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1818.37 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 390.83 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 10-MAY-14:00 | 1296.55 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.69 | 17-JUN-17:03 | 1049.54 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 385.43 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 751.24 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 389.76 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.22 | 13-AUG-13:15 | 494.84 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 493.39 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 16-SEP-13:00 | 848.61 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 625.30 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1082.29 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1825.25 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3430.83 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.84 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 324.22 | 3754.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.97 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 405.33 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 350.75 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1509.99 | 25-MAR-17:05 |
April | 827.17 | 03-APR-09:09 | 304.09 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1208.32 | 04-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 252.45 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 10-MAY-14:00 | 910.68 | 29-MAY-15:10 |
June | 827.17 | 01-JUN-09:09 | 241.75 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.15 | 12-JUN-13:00 | 700.89 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 249.69 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 15-JUL-15:00 | 505.84 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 254.01 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.26 | 13-AUG-13:15 | 386.30 | 27-AUG-16:40 |
September | 827.17 | 01-SEP-09:09 | 337.76 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 16-SEP-13:00 | 557.24 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 449.50 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 689.46 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1190.20 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2268.43 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 241.75 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.30 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 215.26 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1904.58 | 12-JAN-05:53 |
February | 1306.65 | 01-FEB-10:09 | 639.92 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1992.56 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 517.57 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 14-MAR-14:00 | 1110.89 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 408.52 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1077.47 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 385.83 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.61 | 14-MAY-14:53 | 567.26 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.24 | 17-JUN-17:03 | 568.46 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 379.88 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.12 | 21-JUL-03:00 | 413.30 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 385.33 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.50 | 13-AUG-13:00 | 270.51 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 496.23 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 16-SEP-17:03 | 511.22 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 708.74 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 650.97 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1080.80 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1888.22 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.51 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 227.50 | 1992.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1271.65 | 12-JAN-05:43 |
February | 827.22 | 01-FEB-10:09 | 409.22 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.36 | 13-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 258.92 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 15-MAR-14:00 | 763.59 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 249.60 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 723.94 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.35 | 14-MAY-14:53 | 425.59 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.63 | 17-JUN-17:03 | 395.25 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 | 21-JUL-03:00 | 284.58 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 241.40 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.02 | 13-AUG-12:58 | 181.38 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 256.87 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 | 16-SEP-13:00 | 340.91 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 373.18 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 451.51 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 729.50 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1257.55 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.38 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 120.02 | 1328.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 29040.25 | 31-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 624.84 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32140.06 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 501.15 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 800.54 | 15-MAR-12:00 | 29834.89 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 407.86 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20954.95 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 387.87 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.91 | 10-MAY-16:10 | 14741.35 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4653.43 | 27-JUN-12:00 | 11362.90 | 14-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 382.24 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4505.79 | 19-JUL-16:10 | 8149.51 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 386.74 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4334.38 | 10-AUG-12:00 | 9094.41 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 483.86 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.94 | 15-SEP-12:00 | 13589.97 | 05-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 620.01 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19715.38 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19938.24 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32469.28 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8149.51 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4653.43 | 32469.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1272.03 | 12-JAN-05:43 |
February | 827.17 | 01-FEB-10:09 | 403.48 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.36 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 347.23 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 15-MAR-14:00 | 777.56 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 299.18 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 716.09 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 250.99 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 10-MAY-14:00 | 451.12 | 06-MAY-17:10 |
June | 827.17 | 01-JUN-09:09 | 240.30 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.47 | 12-JUN-13:00 | 399.68 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 248.15 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 21-JUL-03:00 | 291.49 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 252.63 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.22 | 13-AUG-12:53 | 181.55 | 30-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 333.87 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.11 | 16-SEP-13:00 | 340.55 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 448.76 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 440.20 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 730.61 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1258.38 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 240.30 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.55 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 118.22 | 1328.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.89 | 12-JAN-05:53 |
February | 1306.65 | 01-FEB-10:09 | 643.47 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3074.67 | 13-FEB-05:50 |
March | 1306.65 | 01-MAR-10:09 | 525.83 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1756.65 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 410.55 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1659.61 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 388.89 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.87 | 14-MAY-15:00 | 996.12 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.06 | 17-JUN-17:03 | 900.75 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 383.20 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.56 | 21-JUL-03:00 | 653.65 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 388.41 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.45 | 13-AUG-12:53 | 421.45 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 505.18 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 16-SEP-17:03 | 769.61 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 710.10 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 966.52 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1628.16 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2915.39 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.45 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 293.45 | 3074.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.91 | 12-JAN-05:53 |
February | 805.43 | 01-FEB-08:09 | 410.90 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2049.78 | 13-FEB-05:50 |
March | 805.43 | 01-MAR-08:09 | 260.17 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 15-MAR-14:10 | 1183.31 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 251.23 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1112.80 | 16-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 | 14-MAY-15:00 | 722.52 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 | 17-JUN-17:03 | 602.97 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.40 | 21-JUL-03:00 | 434.96 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 243.23 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.49 | 13-AUG-13:06 | 280.99 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 258.20 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 16-SEP-13:00 | 509.85 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 376.25 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 671.81 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1082.34 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1936.61 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.99 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 193.49 | 2049.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.89 | 12-JAN-05:53 |
February | 1306.65 | 01-FEB-10:09 | 629.11 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3074.68 | 13-FEB-05:50 |
March | 1306.65 | 01-MAR-10:09 | 510.17 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1920.44 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 409.92 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1665.24 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 390.82 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 10-MAY-14:00 | 1086.01 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.49 | 17-JUN-17:03 | 907.36 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 385.43 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.08 | 21-JUL-03:00 | 656.42 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 389.75 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.56 | 13-AUG-13:04 | 423.71 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 493.37 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.51 | 16-SEP-13:00 | 772.78 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 625.30 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1008.06 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1653.87 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2938.64 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.71 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 285.56 | 3074.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.91 | 12-JAN-05:53 |
February | 827.17 | 01-FEB-10:09 | 405.33 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2049.78 | 13-FEB-05:50 |
March | 827.17 | 01-MAR-10:09 | 350.74 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 15-MAR-14:00 | 1279.96 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 304.07 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1097.35 | 16-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 252.45 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 | 10-MAY-14:00 | 762.66 | 29-MAY-15:10 |
June | 827.17 | 01-JUN-09:09 | 241.74 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 | 12-JUN-13:00 | 606.14 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 249.68 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.86 | 21-JUL-03:00 | 441.83 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 254.01 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.11 | 13-AUG-13:06 | 310.79 | 27-AUG-16:40 |
September | 827.17 | 01-SEP-09:09 | 337.75 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 16-SEP-13:00 | 508.42 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 449.50 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 645.41 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1079.50 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1942.50 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 241.74 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.79 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 186.11 | 2049.78 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3964.45 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3909.00 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 | 15-MAR-14:00 | 2566.76 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2427.97 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.51 | 14-MAY-14:53 | 1199.33 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.80 | 17-JUN-17:03 | 1236.60 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.72 | 21-JUL-03:00 | 897.84 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.88 | 13-AUG-13:00 | 576.59 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 | 16-SEP-13:00 | 1102.59 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1381.02 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2384.05 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4034.57 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.88 | 4034.57 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4958.97 | 12-JAN-01:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4772.96 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 14-MAR-14:00 | 3225.40 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2981.26 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.87 | 14-MAY-14:53 | 1527.61 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.67 | 17-JUN-17:03 | 1591.56 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.63 | 21-JUL-03:00 | 1147.80 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.48 | 13-AUG-12:53 | 740.88 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.61 | 16-SEP-13:00 | 1364.90 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1663.80 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2925.99 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5070.07 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.48 | 5070.07 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4969.28 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5028.82 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 15-MAR-14:00 | 3034.88 | 25-MAR-17:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2809.56 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.22 | 10-MAY-15:00 | 2033.06 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.57 | 17-JUN-17:03 | 1605.30 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.61 | 21-JUL-02:00 | 1134.66 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.04 | 13-AUG-13:00 | 771.21 | 30-AUG-21:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 16-SEP-13:00 | 1294.44 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1572.04 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2776.65 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5464.20 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.21 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.61 | 5464.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5889.72 | 20-JAN-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5993.81 | 17-FEB-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13654.18 | 17-MAR-07:10 | 12070.02 | 6977.40 | 25516.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14451.04 | 26-APR-07:04 | 30175.04 | 17443.51 | 63791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21665.64 | 30-MAY-06:03 | 3811.58 | 3488.70 | 18132.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31902.02 | 19-JUN-06:03 | 5082.11 | 4651.60 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34140.72 | 05-JUL-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33513.30 | 07-AUG-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34644.34 | 18-SEP-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16329.46 | 13-OCT-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13983.43 | 02-NOV-07:08 | 24140.03 | 13954.80 | 51033.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7644.78 | 01-DEC-13:20 | 6035.01 | 3488.70 | 10947.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5889.72 | 2541.06 | 1550.53 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34644.34 | 30175.04 | 17443.51 | 63791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 964.99 |
February | 64.86 | 22-FEB-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.48 |
March | 4671.73 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
April | 4178.73 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.73 |
May | 6545.43 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.93 |
June | 9342.37 | 12-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 0.00 |
July | 9249.84 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.70 | 0.00 |
August | 9152.95 | 09-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.59 | 0.00 |
September | 7183.56 | 21-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 0.00 |
October | 3859.12 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 |
November | 648.93 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.43 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9342.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 1166.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2602.75 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.42 |
February | 2455.08 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1489.19 |
March | 2582.45 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.20 |
April | 1593.40 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.68 |
May | 2061.67 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 |
June | 4106.31 | 12-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.64 | 0.00 |
July | 5957.56 | 17-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 |
August | 4162.50 | 14-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 | 0.00 |
September | 3051.88 | 18-SEP-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 |
October | 1224.04 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.93 |
November | 1420.91 | 18-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.80 |
December | 2397.85 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1877.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5957.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.64 | 1877.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2270.84 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 838.50 |
February | 2066.83 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.21 |
March | 2714.98 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.19 |
April | 2295.26 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.10 |
May | 2089.58 | 24-MAY-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 |
June | 3811.28 | 12-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.76 | 0.00 |
July | 5690.81 | 17-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 |
August | 4223.39 | 07-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.59 |
September | 3443.29 | 18-SEP-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.84 |
October | 2274.81 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.22 |
November | 1709.66 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.45 |
December | 1658.83 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1493.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1658.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5690.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.76 | 1493.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5065.50 | 12-JAN-16:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5206.26 | 17-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10052.46 | 16-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9567.21 | 21-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12813.23 | 31-MAY-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26491.12 | 19-JUN-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28950.58 | 17-JUL-05:15 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28482.15 | 07-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29049.38 | 18-SEP-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11265.84 | 12-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7196.41 | 01-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5506.81 | 01-DEC-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5065.50 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29049.38 | 6035.01 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4700.32 | 06-JAN-16:20 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4934.94 | 28-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10584.70 | 16-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10613.94 | 21-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14463.11 | 31-MAY-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27668.53 | 19-JUN-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30210.55 | 05-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30186.73 | 07-AUG-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15732.78 | 18-SEP-13:10 | 12396.58 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11101.91 | 12-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6218.79 | 01-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5067.69 | 01-DEC-15:00 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4700.32 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30210.55 | 12396.58 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 802.79 | 14-JAN-17:03 | 200.88 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 |
February | 811.28 | 18-FEB-17:03 | 200.88 | 86.40 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.94 |
March | 3389.29 | 15-MAR-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 | 0.00 |
April | 2416.87 | 21-APR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 |
May | 4573.17 | 23-MAY-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
June | 6929.74 | 12-JUN-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 |
July | 10320.99 | 16-JUL-13:32 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 | 0.00 |
August | 8003.83 | 06-AUG-14:02 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 0.00 |
September | 4501.60 | 15-SEP-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
October | 2416.15 | 12-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.00 |
November | 1163.70 | 16-NOV-16:40 | 1272.23 | 697.90 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.55 |
December | 906.39 | 01-DEC-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 802.79 | 200.88 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10320.99 | 1306.65 | 697.90 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 | 312.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 507.73 | 14-JAN-17:03 | 127.17 | 77.59 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 |
February | 750.44 | 28-FEB-10:05 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.94 |
March | 2710.14 | 15-MAR-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 |
April | 5306.68 | 24-APR-09:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 |
May | 7352.27 | 31-MAY-08:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 |
June | 11674.24 | 11-JUN-08:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.45 |
July | 13180.00 | 04-JUL-09:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.90 |
August | 8145.46 | 06-AUG-14:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 | 0.00 |
September | 9692.94 | 04-SEP-09:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.62 |
October | 4124.17 | 11-OCT-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 |
November | 928.19 | 03-NOV-09:30 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.66 |
December | 580.00 | 01-DEC-13:30 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 507.73 | 127.17 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13180.00 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 | 225.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3439.52 | 12-JAN-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.37 |
February | 5814.97 | 28-FEB-13:40 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.32 |
March | 9610.68 | 15-MAR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 | 0.00 |
April | 7898.27 | 24-APR-13:10 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.64 |
May | 10499.43 | 14-MAY-14:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.12 |
June | 12330.39 | 11-JUN-14:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.44 |
July | 15901.80 | 30-JUL-13:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.26 |
August | 15965.43 | 13-AUG-12:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 234.92 | 0.00 |
September | 16900.83 | 10-SEP-13:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.29 |
October | 11716.75 | 11-OCT-12:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 |
November | 7332.13 | 03-NOV-12:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.33 |
December | 3592.97 | 16-DEC-13:30 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3439.52 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16900.83 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 234.92 | 906.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 667.08 | 06-JAN-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.85 |
February | 1712.68 | 28-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.47 |
March | 3576.49 | 15-MAR-14:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
April | 6316.54 | 24-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
May | 11826.30 | 27-MAY-17:06 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.74 |
June | 14634.12 | 11-JUN-17:02 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.38 |
July | 15014.24 | 02-JUL-17:12 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.27 |
August | 13694.04 | 12-AUG-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.04 |
September | 14876.14 | 04-SEP-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.52 |
October | 5905.28 | 11-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
November | 1635.16 | 03-NOV-15:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 |
December | 676.49 | 04-DEC-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 667.08 | 0.00 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15014.24 | 805.38 | 222.08 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 280.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 807.49 | 14-JAN-17:03 | 200.88 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 |
February | 809.42 | 18-FEB-17:03 | 200.88 | 84.63 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.85 |
March | 1311.65 | 15-MAR-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
April | 1230.31 | 27-APR-13:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.43 |
May | 2623.55 | 23-MAY-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
June | 4474.68 | 26-JUN-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 0.00 |
July | 5073.12 | 21-JUL-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.35 | 0.00 |
August | 5579.87 | 07-AUG-06:03 | 803.52 | 383.43 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 |
September | 3820.63 | 18-SEP-13:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 |
October | 2135.91 | 05-OCT-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
November | 1185.68 | 01-NOV-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.72 |
December | 991.46 | 01-DEC-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 807.49 | 200.88 | 84.63 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5579.87 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 47.35 | 166.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 562.73 | 14-JAN-07:05 | 339.13 | 206.93 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.30 |
February | 651.80 | 28-FEB-10:00 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 |
March | 1280.63 | 15-MAR-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
April | 3662.30 | 24-APR-09:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 |
May | 5870.67 | 31-MAY-06:03 | 678.26 | 296.12 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 |
June | 8157.17 | 23-JUN-06:02 | 847.82 | 370.15 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.73 |
July | 10731.83 | 04-JUL-10:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.36 |
August | 8171.02 | 02-AUG-06:02 | 1017.38 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7474.10 | 04-SEP-10:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.64 |
October | 3619.96 | 11-OCT-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 |
November | 1434.06 | 03-NOV-08:35 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.19 |
December | 635.29 | 01-DEC-13:30 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 562.73 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10731.83 | 1654.44 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1019.91 | 21-JAN-12:30 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.86 |
February | 1199.67 | 18-FEB-14:40 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.03 |
March | 5601.65 | 15-MAR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 173.52 | 0.00 |
April | 3524.39 | 22-APR-13:40 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 |
May | 5103.33 | 16-MAY-12:10 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.38 |
June | 10214.52 | 12-JUN-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4172.21 | 0.00 |
July | 10477.76 | 21-JUL-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.29 | 0.00 |
August | 12010.40 | 06-AUG-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 0.00 |
September | 12756.26 | 04-SEP-14:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.02 |
October | 9727.38 | 11-OCT-12:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.05 |
November | 4863.57 | 01-NOV-12:08 | 7633.40 | 2104.85 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.83 |
December | 1658.54 | 16-DEC-13:30 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1019.91 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12756.26 | 7633.40 | 2104.85 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.29 | 1462.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 643.19 | 12-JAN-16:10 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.65 |
February | 802.97 | 28-FEB-16:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.82 |
March | 1576.02 | 15-MAR-14:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 0.00 |
April | 3703.05 | 24-APR-17:30 | 84.78 | 74.03 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
May | 5681.02 | 27-MAY-17:06 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.52 |
June | 10312.84 | 11-JUN-17:02 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 |
July | 11128.82 | 16-JUL-16:41 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 0.00 |
August | 9492.74 | 12-AUG-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 |
September | 8032.84 | 04-SEP-15:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.72 |
October | 4939.93 | 11-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
November | 1441.72 | 03-NOV-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 |
December | 669.66 | 04-DEC-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 643.19 | 0.00 | 49.34 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11128.82 | 805.38 | 222.08 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 266.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 814.92 | 14-JAN-17:03 | 200.88 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.19 |
February | 858.40 | 17-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.18 |
March | 2883.90 | 15-MAR-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 | 0.00 |
April | 2211.29 | 21-APR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 |
May | 4308.10 | 23-MAY-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
June | 7366.54 | 12-JUN-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 |
July | 7535.62 | 16-JUL-13:32 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 53.75 | 0.00 |
August | 8731.29 | 06-AUG-16:31 | 468.72 | 136.41 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 | 0.00 |
September | 4302.75 | 13-SEP-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 |
October | 2517.24 | 05-OCT-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 |
November | 1224.46 | 01-NOV-13:40 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.09 |
December | 985.49 | 01-DEC-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 814.92 | 200.88 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8731.29 | 1306.65 | 350.81 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 53.75 | 259.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 611.44 | 06-JAN-11:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 |
February | 818.81 | 28-FEB-10:00 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 |
March | 4108.77 | 16-MAR-12:02 | 3221.71 | 888.36 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
April | 6268.12 | 24-APR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.94 |
May | 7717.66 | 31-MAY-06:03 | 678.26 | 296.12 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 |
June | 13287.53 | 11-JUN-09:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.24 |
July | 13181.01 | 09-JUL-08:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 |
August | 13173.59 | 06-AUG-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.59 |
September | 11124.83 | 04-SEP-10:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.57 |
October | 5514.43 | 11-OCT-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
November | 4782.38 | 01-NOV-12:02 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.71 |
December | 659.42 | 01-DEC-13:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 611.44 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | |
Maximum of Months | 13287.53 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4342.22 | 12-JAN-13:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.87 |
February | 6062.19 | 28-FEB-13:40 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.91 |
March | 9071.88 | 15-MAR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
April | 7915.50 | 24-APR-12:50 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.81 |
May | 8353.14 | 14-MAY-13:33 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.86 |
June | 9380.74 | 25-JUN-13:13 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 |
July | 14439.49 | 30-JUL-13:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.45 |
August | 14708.54 | 13-AUG-14:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 173.42 | 0.00 |
September | 14903.31 | 10-SEP-11:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.80 |
October | 11661.64 | 11-OCT-12:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 |
November | 8297.56 | 03-NOV-12:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 |
December | 4114.97 | 16-DEC-13:20 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4114.97 | 133.92 | 58.46 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14903.31 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 173.42 | 775.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 706.76 | 12-JAN-16:10 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.67 |
February | 1741.21 | 28-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.47 |
March | 3248.09 | 21-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.59 |
April | 6259.87 | 24-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
May | 13499.11 | 07-MAY-16:22 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.34 |
June | 14480.42 | 11-JUN-16:11 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.98 |
July | 13947.28 | 02-JUL-17:12 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 |
August | 14097.89 | 06-AUG-16:31 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 |
September | 12164.70 | 04-SEP-15:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.28 |
October | 5889.50 | 11-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
November | 2053.02 | 03-NOV-15:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.53 |
December | 711.78 | 04-DEC-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 706.76 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | |
Maximum of Months | 14480.42 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.67 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.146944E+12 | 222211.27 | 02-JAN-07:10 | 0.787318E+11 | 108181.92 | 04-JAN-07:19 |
February | 0.127095E+12 | 214021.50 | 06-FEB-07:10 | 0.728745E+11 | 116722.72 | 06-FEB-08:20 |
March | 0.101503E+12 | 167609.28 | 06-MAR-07:10 | 0.505464E+11 | 101384.17 | 07-MAR-07:30 |
April | 0.784972E+11 | 128421.68 | 17-APR-06:10 | 0.244458E+11 | 64747.10 | 17-APR-06:30 |
May | 0.844326E+11 | 87820.49 | 23-MAY-14:30 | 0.124518E+11 | 35946.21 | 01-MAY-06:19 |
June | 0.104343E+12 | 128092.45 | 27-JUN-12:00 | 0.110782E+11 | 14963.05 | 06-JUN-06:19 |
July | 0.121288E+12 | 140641.83 | 17-JUL-07:10 | 0.106589E+11 | 9869.95 | 03-JUL-11:09 |
August | 0.119368E+12 | 138665.49 | 14-AUG-10:00 | 0.110627E+11 | 9817.51 | 31-AUG-11:20 |
September | 0.910739E+11 | 110347.12 | 15-SEP-10:00 | 0.106447E+11 | 21249.68 | 30-SEP-06:19 |
October | 0.810978E+11 | 105802.86 | 30-OCT-06:10 | 0.187920E+11 | 57818.01 | 17-OCT-06:40 |
November | 0.892085E+11 | 143580.54 | 24-NOV-07:10 | 0.332954E+11 | 64200.79 | 24-NOV-07:30 |
December | 0.133573E+12 | 212877.36 | 11-DEC-07:10 | 0.700885E+11 | 115180.99 | 11-DEC-08:20 |
Annual Sum or Average | 0.127842E+13 | 0.404671E+12 | ||||
Minimum of Months | 0.784972E+11 | 87820.49 | 0.106447E+11 | 9817.51 | ||
Maximum of Months | 0.146944E+12 | 222211.27 | 0.787318E+11 | 116722.72 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.472183E+10 | 15051.31 | 30-JAN-12:30 | 0.00 | 0.00 |
February | 0.672531E+10 | 19384.91 | 28-FEB-12:30 | 0.00 | 0.00 |
March | 0.108149E+11 | 23364.19 | 25-MAR-12:30 | 0.00 | 0.00 |
April | 0.133539E+11 | 25462.86 | 17-APR-12:20 | 0.00 | 0.00 |
May | 0.167532E+11 | 25745.16 | 31-MAY-12:20 | 0.00 | 0.00 |
June | 0.185120E+11 | 26813.75 | 14-JUN-11:00 | 0.00 | 0.00 |
July | 0.175097E+11 | 25225.38 | 01-JUL-12:30 | 0.00 | 0.00 |
August | 0.150673E+11 | 22907.02 | 08-AUG-12:20 | 0.00 | 0.00 |
September | 0.112653E+11 | 21357.36 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.769344E+10 | 17332.51 | 11-OCT-11:00 | 0.00 | 0.00 |
November | 0.440972E+10 | 13707.26 | 03-NOV-11:30 | 0.00 | 0.00 |
December | 0.414778E+10 | 12718.57 | 10-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.130974E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.414778E+10 | 12718.57 | 0.00 | 0.00 | |
Maximum of Months | 0.185120E+11 | 26813.75 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.143084E+11 | 0.400880E+10 | 0.545046E+11 | 0.976676E+09 | 0.408164E+10 | 12379742.02 | 0.690519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127737E+11 | 0.318720E+10 | 0.493409E+11 | 0.883732E+09 | 0.365883E+10 | 11196021.66 | 0.572390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149098E+11 | 0.296265E+10 | 0.567112E+11 | 0.102243E+10 | 0.375625E+10 | 12675672.10 | 0.209950E+11 | 0.113353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132057E+11 | 0.235623E+10 | 0.526212E+11 | 0.940425E+09 | 0.367397E+10 | 11960507.72 | 0.524010E+10 | 0.447535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141506E+11 | 0.203235E+10 | 0.556079E+11 | 0.999257E+09 | 0.595284E+10 | 12527707.06 | 0.769781E+09 | 0.490725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140286E+11 | 0.182138E+10 | 0.546110E+11 | 0.983590E+09 | 0.109125E+11 | 12231776.97 | 0.160262E+09 | 0.218134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131623E+11 | 0.193099E+10 | 0.536070E+11 | 0.955900E+09 | 0.139351E+11 | 12256437.81 | 9588266.99 | 0.376746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146968E+11 | 0.225469E+10 | 0.567112E+11 | 0.102232E+10 | 0.134372E+11 | 12675672.10 | 31308479.03 | 0.312016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132844E+11 | 0.262301E+10 | 0.525990E+11 | 0.940233E+09 | 0.808468E+10 | 11960507.72 | 0.213997E+09 | 0.133167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139863E+11 | 0.328133E+10 | 0.545158E+11 | 0.976520E+09 | 0.406265E+10 | 12379742.02 | 0.269104E+10 | 0.157178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142057E+11 | 0.371351E+10 | 0.533244E+11 | 0.958590E+09 | 0.318003E+10 | 12059151.09 | 0.135707E+11 | 0.243456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140034E+11 | 0.415338E+10 | 0.535958E+11 | 0.956443E+09 | 0.376373E+10 | 12256437.81 | 0.570880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166716E+12 | 0.343255E+11 | 0.647750E+12 | 0.116161E+11 | 0.784996E+11 | 0.146559E+09 | 0.227061E+12 | 0.112310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127737E+11 | 0.182138E+10 | 0.493409E+11 | 0.883732E+09 | 0.318003E+10 | 11196021.66 | 9588266.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149098E+11 | 0.415338E+10 | 0.567112E+11 | 0.102243E+10 | 0.139351E+11 | 12675672.10 | 0.690519E+11 | 0.376746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.667014E+11 | 0.00 | 0.120304E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.618970E+11 | 0.00 | 0.109775E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.380940E+11 | 0.00 | 0.124523E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.130861E+11 | 0.00 | 0.113598E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.846317E+09 | 0.00 | 0.116055E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 60943947.80 | 0.00 | 0.110172E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.106589E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.110627E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.203045E+09 | 0.00 | 0.104416E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.774610E+10 | 0.00 | 0.110459E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.221816E+11 | 0.00 | 0.111138E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.584790E+11 | 0.00 | 0.116096E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.269295E+12 | 0.00 | 0.135375E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.104416E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.667014E+11 | 0.00 | 0.124523E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-16:49 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 828.65 | 02-JAN-16:00 | 6730.06 | 02-JAN-07:10 | 6.85 | 02-JAN-08:20 | 187169.61 | 02-JAN-07:10 |
February | 16675.99 | 01-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 828.41 | 01-FEB-08:20 | 6323.24 | 06-FEB-07:10 | 6.85 | 02-FEB-06:10 | 179386.64 | 06-FEB-07:10 |
March | 15384.83 | 17-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 826.77 | 17-MAR-07:19 | 6530.96 | 15-MAR-13:50 | 6.85 | 02-MAR-06:10 | 139522.44 | 06-MAR-07:10 |
April | 14582.83 | 12-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 825.71 | 12-APR-07:19 | 6822.52 | 21-APR-15:20 | 6.85 | 03-APR-05:10 | 101617.13 | 17-APR-06:10 |
May | 14221.39 | 11-MAY-07:10 | 3824.74 | 01-MAY-05:10 | 40437.79 | 01-MAY-07:10 | 825.24 | 11-MAY-07:19 | 13045.42 | 23-MAY-14:30 | 6.85 | 01-MAY-05:10 | 18019.33 | 01-MAY-06:10 |
June | 13961.01 | 21-JUN-08:09 | 2323.70 | 01-JUN-19:49 | 40437.79 | 01-JUN-07:10 | 824.88 | 19-JUN-07:19 | 24143.09 | 12-JUN-15:20 | 6.85 | 10-JUN-16:10 | 10509.34 | 14-JUN-06:19 |
July | 14176.51 | 11-JUL-07:30 | 2323.70 | 01-JUL-19:00 | 40437.79 | 03-JUL-07:10 | 825.18 | 11-JUL-07:40 | 25608.98 | 17-JUL-10:50 | 6.85 | 02-JUL-15:50 | 1383.38 | 13-JUL-06:10 |
August | 14221.43 | 24-AUG-07:10 | 3824.74 | 02-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 825.24 | 24-AUG-07:19 | 25203.94 | 14-AUG-15:30 | 6.85 | 12-AUG-16:10 | 4050.67 | 31-AUG-06:19 |
September | 15225.98 | 26-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 826.56 | 26-SEP-07:19 | 18130.55 | 21-SEP-15:39 | 6.85 | 01-SEP-05:10 | 9262.75 | 29-SEP-06:10 |
October | 16923.27 | 30-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 828.80 | 30-OCT-07:19 | 9645.87 | 11-OCT-15:00 | 6.85 | 13-OCT-16:10 | 74326.30 | 30-OCT-06:10 |
November | 17672.30 | 06-NOV-16:00 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 829.45 | 02-NOV-07:19 | 3796.18 | 03-NOV-14:30 | 6.85 | 03-NOV-05:10 | 111568.99 | 24-NOV-07:10 |
December | 17672.30 | 01-DEC-16:40 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.79 | 18-DEC-08:20 | 6251.68 | 26-DEC-07:10 | 6.85 | 04-DEC-06:10 | 178348.52 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 13961.01 | 2323.70 | 40437.79 | 824.88 | 3796.18 | 6.85 | 1383.38 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 40437.79 | 829.45 | 25608.98 | 6.85 | 187169.61 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 19314.71 | 15-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8428.09 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23938.72 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 53726.20 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 60272.88 | 17-JUL-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 61233.50 | 14-AUG-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 43182.32 | 15-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 16700.30 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5555.01 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 61233.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 222211.27 | 02-JAN-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6730.06 | 6.85 | 187169.61 | 0.00 | 0.00 |
February | 214021.50 | 06-FEB-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6323.24 | 6.85 | 179386.64 | 0.00 | 0.00 |
March | 167609.28 | 06-MAR-07:10 | 4998.91 | 18346.02 | 0.00 | 243.13 | 4491.93 | 6.85 | 139522.44 | 0.00 | 0.00 |
April | 128421.68 | 17-APR-06:10 | 4734.18 | 18346.02 | 0.00 | 243.07 | 3474.42 | 6.85 | 101617.13 | 0.00 | 0.00 |
May | 87820.49 | 23-MAY-14:30 | 13903.46 | 37678.39 | 0.00 | 823.25 | 13045.42 | 6.85 | 0.00 | 22363.13 | 0.00 |
June | 128092.45 | 27-JUN-12:00 | 13903.46 | 38626.93 | 0.00 | 823.79 | 21005.22 | 6.85 | 0.00 | 53726.20 | 0.00 |
July | 140641.83 | 17-JUL-07:10 | 13903.46 | 40437.79 | 0.00 | 812.71 | 25469.97 | 6.85 | 0.00 | 60011.04 | 0.00 |
August | 138665.49 | 14-AUG-10:00 | 13903.46 | 38195.78 | 0.00 | 823.54 | 24502.36 | 6.85 | 0.00 | 61233.50 | 0.00 |
September | 110347.12 | 15-SEP-10:00 | 13903.46 | 38195.78 | 0.00 | 823.54 | 14235.17 | 6.85 | 0.00 | 43182.32 | 0.00 |
October | 105802.86 | 30-OCT-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3164.94 | 6.85 | 74326.30 | 0.00 | 0.00 |
November | 143580.54 | 24-NOV-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3699.95 | 6.85 | 111568.99 | 0.00 | 0.00 |
December | 212877.36 | 11-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6217.23 | 6.85 | 178348.52 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 87820.49 | 4734.18 | 18346.02 | 0.00 | 243.07 | 3164.94 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 222211.27 | 13903.46 | 40437.79 | 3824.74 | 823.79 | 25469.97 | 6.85 | 187169.61 | 61233.50 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 99243.93 | 04-JAN-07:19 | 0.00 | 11058.86 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 108459.50 | 07-FEB-07:19 | 0.00 | 11209.95 | 08-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 92454.89 | 07-MAR-07:30 | 0.00 | 10911.73 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 56864.40 | 17-APR-06:30 | 0.00 | 10239.76 | 06-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 29443.15 | 01-MAY-06:10 | 0.00 | 10130.45 | 03-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 7309.14 | 06-JUN-06:10 | 0.00 | 9987.61 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9869.95 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9817.51 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 12970.27 | 30-SEP-06:10 | 0.00 | 9868.42 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 49689.31 | 17-OCT-06:30 | 0.00 | 9994.39 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 55337.67 | 24-NOV-07:30 | 0.00 | 10124.30 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 105782.09 | 11-DEC-08:20 | 0.00 | 10254.75 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9817.51 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 108459.50 | 0.00 | 11209.95 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.39 | 1.50 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 19.39 | 1.50 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.39 | 1.50 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.95 | 2.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 0.50 | 19.32 | 0.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.23 | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 3.33 | 19.03 | 2.83 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.32 | 2.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.55 | 2.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
February | 2.17 | 18.39 | 1.33 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
March | 0.17 | 19.27 | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 18.52 | 1.67 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 8.17 | 18.51 | 5.50 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.27 | 2.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.33 | 16.49 | 18.83 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
February | 40.33 | 16.53 | 17.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
March | 7.67 | 17.16 | 3.00 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
April | 0.33 | 18.10 | 0.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.39 | 1.17 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.32 | 1.00 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
November | 1.00 | 18.47 | 0.67 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
December | 32.83 | 16.39 | 15.50 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
Annual Sum or Average | 123.67 | 16.54 | 55.33 | 17.05 | 2.50 | 17.19 | 2.17 | 17.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.33 | 18.47 | 18.83 | 18.77 | 1.50 | 27.39 | 1.17 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.50 | 15.13 | 5.17 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
February | 23.33 | 14.85 | 2.33 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
March | 4.00 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
April | 0.17 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.53 | 6.50 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.74 | 9.33 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.59 | 4.33 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.52 | 1.50 | 27.52 |
October | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
November | 0.67 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
December | 22.33 | 15.03 | 4.83 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
Annual Sum or Average | 77.17 | 15.07 | 12.33 | 15.10 | 22.83 | 17.64 | 22.33 | 19.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 0.00 | 14.87 |
Maximum of Months | 26.50 | 17.16 | 5.17 | 17.16 | 9.67 | 27.74 | 9.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 15.39 | 4.00 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
February | 19.83 | 15.25 | 2.67 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
March | 2.50 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
April | 0.17 | 17.04 | 0.00 | 17.04 | 0.33 | 23.87 | 0.33 | 25.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.46 | 0.67 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.52 | 3.67 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.62 | 7.83 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.72 | 4.83 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.76 | 3.83 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
December | 16.17 | 15.44 | 2.67 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
Annual Sum or Average | 62.83 | 15.40 | 9.33 | 15.58 | 21.83 | 18.38 | 21.17 | 20.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.00 | 17.04 | 4.00 | 17.04 | 8.17 | 27.76 | 7.83 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.00 | 15.07 | 6.67 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
February | 24.33 | 14.86 | 3.50 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
March | 3.50 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
April | 0.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.70 | 2.17 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.16 | 4.00 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.07 | 6.17 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.95 | 3.50 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.80 | 2.50 | 27.80 |
October | 0.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
November | 0.50 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
December | 22.17 | 14.99 | 4.50 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 79.83 | 15.03 | 14.67 | 15.05 | 28.67 | 18.06 | 18.33 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 | 14.89 |
Maximum of Months | 29.00 | 17.23 | 6.67 | 17.23 | 10.00 | 28.16 | 6.17 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.83 | 18.62 | 11.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
February | 15.83 | 18.46 | 11.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
March | 3.50 | 19.24 | 3.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
April | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.17 | 18.97 | 5.83 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 42.50 | 18.67 | 31.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.83 | 19.42 | 11.50 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 15.95 | 0.17 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
February | 3.83 | 16.11 | 0.33 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
March | 0.33 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.42 | 1.17 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.57 | 3.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.47 | 1.17 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.37 | 1.50 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 17.03 | 0.17 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
Annual Sum or Average | 10.33 | 16.17 | 0.67 | 16.36 | 7.33 | 20.81 | 7.33 | 22.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 17.09 | 0.33 | 17.31 | 3.50 | 27.57 | 3.50 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.83 | 16.83 | 83.83 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
February | 79.33 | 16.95 | 77.67 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
March | 47.50 | 18.11 | 47.50 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
April | 22.67 | 18.94 | 22.67 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
May | 4.33 | 19.73 | 4.33 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 1.00 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.45 | 3.00 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.58 | 3.00 | 27.58 |
October | 9.33 | 19.19 | 9.33 | 19.19 | 0.17 | 19.27 | 0.17 | 19.34 |
November | 36.50 | 19.14 | 36.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
December | 73.67 | 17.10 | 72.83 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
Annual Sum or Average | 360.17 | 17.54 | 354.67 | 17.55 | 7.17 | 17.65 | 7.17 | 17.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.83 | 19.73 | 83.83 | 19.73 | 3.00 | 27.58 | 3.00 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 15.86 | 0.17 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
February | 4.33 | 16.05 | 0.33 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 |
March | 0.17 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.33 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.67 | 2.50 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.80 | 3.00 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.64 | 2.67 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 1.50 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 16.84 | 0.17 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
Annual Sum or Average | 11.00 | 16.08 | 0.67 | 16.27 | 17.00 | 23.04 | 10.00 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 16.94 | 0.33 | 17.08 | 5.50 | 27.80 | 3.00 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.67 | 17.33 | 6.83 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
February | 18.17 | 17.18 | 7.83 | 17.83 | 0.00 | 17.83 | 0.00 | 17.83 |
March | 1.17 | 18.76 | 0.83 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.50 | 17.22 | 5.50 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
Annual Sum or Average | 47.50 | 17.28 | 21.00 | 17.94 | 0.00 | 17.94 | 0.00 | 17.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.17 | 18.76 | 7.83 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 15.52 | 0.17 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
February | 10.00 | 15.36 | 0.33 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
March | 0.33 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.47 | 1.00 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.62 | 4.17 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.34 | 9.17 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.51 | 4.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.67 | 2.17 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
Annual Sum or Average | 25.50 | 15.43 | 0.50 | 15.50 | 21.00 | 20.85 | 21.00 | 22.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.00 | 16.89 | 0.33 | 16.89 | 9.17 | 27.67 | 9.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 15.77 | 0.17 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 |
February | 7.50 | 15.60 | 0.50 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
March | 0.17 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.67 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.40 | 2.50 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.51 | 6.17 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.64 | 4.50 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.78 | 4.00 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.83 | 15.85 | 0.33 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
Annual Sum or Average | 18.33 | 15.73 | 1.00 | 15.91 | 18.67 | 21.64 | 18.67 | 23.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.50 | 16.89 | 0.50 | 16.89 | 6.17 | 27.78 | 6.17 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.33 | 15.45 | 0.17 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
February | 9.83 | 15.43 | 0.33 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
March | 0.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.65 | 2.17 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.05 | 3.50 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.02 | 4.83 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.90 | 3.00 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.78 | 2.50 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
Annual Sum or Average | 26.50 | 15.44 | 0.50 | 15.51 | 25.50 | 21.54 | 16.00 | 23.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.33 | 16.96 | 0.33 | 16.96 | 8.33 | 28.05 | 4.83 | 28.04 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.65 | 153.17 | 21.43 | 153.17 | 21.29 |
February | 454.00 | 21.88 | 98.83 | 21.74 | 98.83 | 21.65 |
March | 476.67 | 23.07 | 7.83 | 23.06 | 5.17 | 23.04 |
April | 401.17 | 23.66 | 2.00 | 23.67 | 0.00 | 23.67 |
May | 142.50 | 23.94 | 116.83 | 24.36 | 0.00 | 24.36 |
June | 3.00 | 24.01 | 311.17 | 24.42 | 0.00 | 24.42 |
July | 0.00 | 0.00 | 477.00 | 24.40 | 0.00 | 24.40 |
August | 0.00 | 0.00 | 451.00 | 24.38 | 0.00 | 24.38 |
September | 9.83 | 23.89 | 286.50 | 24.49 | 0.00 | 24.49 |
October | 224.50 | 23.85 | 45.83 | 24.02 | 0.00 | 24.02 |
November | 468.50 | 23.49 | 0.00 | 23.49 | 0.00 | 23.49 |
December | 497.00 | 22.18 | 51.67 | 22.08 | 51.67 | 22.00 |
Annual Sum or Average | 3179.17 | 22.77 | 2001.83 | 23.21 | 308.83 | 23.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.43 | 0.00 | 21.29 |
Maximum of Months | 502.00 | 24.01 | 477.00 | 24.49 | 153.17 | 24.49 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.81 | 377.17 | 20.71 | 377.17 | 20.67 |
February | 454.00 | 20.99 | 300.67 | 20.87 | 300.67 | 20.82 |
March | 485.83 | 22.03 | 70.33 | 21.89 | 68.50 | 21.77 |
April | 461.83 | 23.02 | 3.17 | 23.01 | 3.17 | 22.99 |
May | 232.17 | 23.70 | 64.83 | 23.88 | 0.00 | 23.88 |
June | 38.50 | 23.91 | 267.33 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 465.83 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 406.17 | 24.33 | 0.00 | 24.33 |
September | 38.00 | 23.46 | 212.67 | 24.27 | 0.00 | 24.27 |
October | 382.50 | 23.16 | 6.83 | 23.18 | 0.00 | 23.18 |
November | 489.00 | 22.25 | 13.17 | 22.22 | 13.17 | 22.18 |
December | 497.00 | 21.02 | 288.50 | 20.89 | 288.50 | 20.83 |
Annual Sum or Average | 3580.83 | 22.01 | 2476.67 | 22.32 | 1051.17 | 22.08 |
Minimum of Months | 0.00 | 0.00 | 3.17 | 20.71 | 0.00 | 20.67 |
Maximum of Months | 502.00 | 23.91 | 465.83 | 24.33 | 377.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 460.00 | 20.35 | 460.00 | 20.33 |
February | 454.00 | 20.53 | 382.50 | 20.44 | 382.50 | 20.41 |
March | 486.50 | 21.46 | 195.83 | 21.22 | 193.33 | 21.08 |
April | 472.00 | 22.52 | 35.83 | 22.37 | 35.83 | 22.24 |
May | 279.83 | 23.50 | 51.67 | 23.63 | 0.00 | 23.63 |
June | 61.17 | 23.68 | 257.67 | 24.16 | 0.00 | 24.16 |
July | 3.50 | 23.65 | 452.50 | 24.33 | 0.00 | 24.33 |
August | 15.67 | 23.54 | 392.17 | 24.26 | 0.00 | 24.26 |
September | 134.00 | 23.36 | 158.50 | 23.88 | 0.00 | 23.88 |
October | 445.17 | 22.47 | 26.83 | 22.40 | 22.83 | 22.31 |
November | 489.00 | 21.41 | 149.00 | 21.19 | 149.00 | 21.06 |
December | 497.00 | 20.49 | 424.83 | 20.42 | 424.83 | 20.40 |
Annual Sum or Average | 3839.83 | 21.59 | 2987.33 | 21.82 | 1668.33 | 21.53 |
Minimum of Months | 3.50 | 20.39 | 26.83 | 20.35 | 0.00 | 20.33 |
Maximum of Months | 502.00 | 23.68 | 460.00 | 24.33 | 460.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 494.33 | 19.81 | 494.33 | 19.80 |
February | 454.00 | 19.86 | 452.17 | 19.86 | 452.17 | 19.86 |
March | 493.83 | 20.69 | 324.17 | 20.50 | 314.50 | 20.40 |
April | 474.00 | 21.66 | 115.00 | 21.34 | 115.00 | 21.13 |
May | 309.00 | 22.95 | 58.17 | 23.12 | 4.50 | 23.09 |
June | 92.50 | 23.75 | 274.33 | 24.17 | 17.00 | 24.23 |
July | 49.83 | 25.17 | 452.17 | 24.48 | 41.67 | 24.56 |
August | 61.50 | 23.74 | 377.17 | 24.20 | 13.83 | 24.24 |
September | 217.17 | 23.01 | 154.33 | 23.51 | 13.33 | 23.57 |
October | 469.50 | 21.55 | 109.67 | 21.29 | 106.50 | 21.09 |
November | 489.00 | 20.53 | 307.00 | 20.36 | 307.00 | 20.28 |
December | 497.00 | 19.82 | 479.83 | 19.80 | 479.83 | 19.79 |
Annual Sum or Average | 4109.33 | 21.04 | 3598.33 | 21.27 | 2359.67 | 21.00 |
Minimum of Months | 49.83 | 19.81 | 58.17 | 19.80 | 4.50 | 19.79 |
Maximum of Months | 502.00 | 25.17 | 494.33 | 24.48 | 494.33 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 494.17 | 19.87 | 494.17 | 19.86 |
February | 454.00 | 19.96 | 422.67 | 19.91 | 422.67 | 19.89 |
March | 481.17 | 20.98 | 263.33 | 20.74 | 244.17 | 20.57 |
April | 383.83 | 21.82 | 93.50 | 21.61 | 75.33 | 21.36 |
May | 207.50 | 23.06 | 153.50 | 23.65 | 6.67 | 23.67 |
June | 80.50 | 24.65 | 356.33 | 24.46 | 34.17 | 24.60 |
July | 79.33 | 26.23 | 477.67 | 24.76 | 78.00 | 24.95 |
August | 59.17 | 24.79 | 421.50 | 24.41 | 31.33 | 24.52 |
September | 159.17 | 23.24 | 260.17 | 23.95 | 17.83 | 24.02 |
October | 416.17 | 21.83 | 91.00 | 21.63 | 73.83 | 21.42 |
November | 489.00 | 20.72 | 275.83 | 20.49 | 275.83 | 20.38 |
December | 497.00 | 19.88 | 476.67 | 19.86 | 476.67 | 19.85 |
Annual Sum or Average | 3808.83 | 21.17 | 3786.33 | 21.56 | 2230.67 | 21.29 |
Minimum of Months | 59.17 | 19.87 | 91.00 | 19.86 | 6.67 | 19.85 |
Maximum of Months | 502.00 | 26.23 | 494.17 | 24.76 | 494.17 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.23 | 431.00 | 20.06 | 431.00 | 20.00 |
February | 449.83 | 20.26 | 367.83 | 20.05 | 367.83 | 19.97 |
March | 453.83 | 21.32 | 221.17 | 21.03 | 203.17 | 20.83 |
April | 375.33 | 21.73 | 121.00 | 21.62 | 91.50 | 21.38 |
May | 249.33 | 22.88 | 127.33 | 23.36 | 10.17 | 23.35 |
June | 107.83 | 23.89 | 310.17 | 24.23 | 27.00 | 24.34 |
July | 82.67 | 25.51 | 451.33 | 24.63 | 66.33 | 24.79 |
August | 73.67 | 24.39 | 403.33 | 24.36 | 28.33 | 24.47 |
September | 161.67 | 23.41 | 264.17 | 24.04 | 26.17 | 24.17 |
October | 363.67 | 21.88 | 131.67 | 21.98 | 66.00 | 21.75 |
November | 464.50 | 21.05 | 224.67 | 20.75 | 221.67 | 20.59 |
December | 495.00 | 20.16 | 433.83 | 20.04 | 433.83 | 20.00 |
Annual Sum or Average | 3779.33 | 21.38 | 3487.50 | 21.71 | 1973.00 | 21.43 |
Minimum of Months | 73.67 | 20.16 | 121.00 | 20.04 | 10.17 | 19.97 |
Maximum of Months | 502.00 | 25.51 | 451.33 | 24.63 | 433.83 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 488.33 | 19.86 | 488.33 | 19.86 |
February | 454.00 | 20.00 | 420.17 | 19.93 | 420.17 | 19.90 |
March | 480.50 | 21.03 | 273.67 | 20.77 | 259.33 | 20.60 |
April | 397.83 | 21.64 | 135.83 | 21.55 | 100.83 | 21.31 |
May | 258.17 | 23.03 | 139.33 | 23.52 | 13.00 | 23.59 |
June | 100.00 | 24.20 | 336.17 | 24.34 | 33.50 | 24.48 |
July | 79.83 | 25.56 | 460.67 | 24.65 | 65.67 | 24.80 |
August | 69.00 | 24.39 | 416.17 | 24.37 | 26.83 | 24.46 |
September | 188.67 | 23.26 | 227.00 | 23.87 | 26.00 | 23.99 |
October | 431.50 | 21.67 | 118.33 | 21.52 | 90.67 | 21.30 |
November | 487.83 | 20.69 | 274.00 | 20.45 | 274.00 | 20.34 |
December | 497.00 | 19.87 | 469.83 | 19.84 | 469.83 | 19.83 |
Annual Sum or Average | 3946.33 | 21.18 | 3759.50 | 21.53 | 2268.17 | 21.26 |
Minimum of Months | 69.00 | 19.87 | 118.33 | 19.84 | 13.00 | 19.83 |
Maximum of Months | 502.00 | 25.56 | 488.33 | 24.65 | 488.33 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 495.17 | 20.04 | 495.17 | 20.04 |
February | 454.00 | 20.13 | 454.00 | 20.13 | 454.00 | 20.13 |
March | 514.00 | 20.79 | 347.67 | 20.63 | 347.67 | 20.56 |
April | 485.00 | 21.40 | 122.33 | 21.19 | 122.33 | 21.06 |
May | 443.83 | 22.82 | 10.67 | 22.84 | 3.33 | 22.84 |
June | 129.50 | 23.65 | 220.33 | 23.98 | 9.83 | 24.00 |
July | 28.50 | 24.82 | 446.83 | 24.32 | 26.17 | 24.36 |
August | 36.33 | 23.81 | 376.33 | 24.20 | 9.83 | 24.21 |
September | 175.33 | 23.43 | 149.83 | 23.80 | 10.67 | 23.86 |
October | 457.67 | 22.31 | 12.17 | 22.28 | 10.50 | 22.24 |
November | 489.00 | 21.10 | 180.33 | 20.94 | 180.33 | 20.84 |
December | 497.00 | 20.23 | 471.83 | 20.21 | 471.83 | 20.20 |
Annual Sum or Average | 4212.17 | 21.30 | 3287.50 | 21.47 | 2141.67 | 21.22 |
Minimum of Months | 28.50 | 20.05 | 10.67 | 20.04 | 3.33 | 20.04 |
Maximum of Months | 514.00 | 24.82 | 495.17 | 24.32 | 495.17 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 494.33 | 20.14 | 494.33 | 20.13 |
February | 454.00 | 20.24 | 440.50 | 20.22 | 440.50 | 20.22 |
March | 501.17 | 21.09 | 252.67 | 20.86 | 252.67 | 20.74 |
April | 439.83 | 22.11 | 59.33 | 21.93 | 54.83 | 21.76 |
May | 277.67 | 23.14 | 92.17 | 23.51 | 0.00 | 23.51 |
June | 53.83 | 24.16 | 335.17 | 24.38 | 12.67 | 24.42 |
July | 45.00 | 26.12 | 485.17 | 24.63 | 45.00 | 24.75 |
August | 28.50 | 25.00 | 448.33 | 24.42 | 17.17 | 24.47 |
September | 81.33 | 23.72 | 301.50 | 24.26 | 12.50 | 24.32 |
October | 383.67 | 22.74 | 36.67 | 22.84 | 4.33 | 22.82 |
November | 489.00 | 21.40 | 132.83 | 21.20 | 132.83 | 21.07 |
December | 497.00 | 20.29 | 466.83 | 20.26 | 466.83 | 20.25 |
Annual Sum or Average | 3753.00 | 21.43 | 3545.50 | 21.83 | 1933.67 | 21.55 |
Minimum of Months | 28.50 | 20.14 | 36.67 | 20.14 | 0.00 | 20.13 |
Maximum of Months | 502.00 | 26.12 | 494.33 | 24.63 | 494.33 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.66 | 466.83 | 19.59 | 466.83 | 19.57 |
February | 454.00 | 19.69 | 419.83 | 19.63 | 419.83 | 19.60 |
March | 500.00 | 20.88 | 226.17 | 20.63 | 219.67 | 20.47 |
April | 449.33 | 21.46 | 95.33 | 21.30 | 85.33 | 21.12 |
May | 384.33 | 22.46 | 48.33 | 22.65 | 8.83 | 22.59 |
June | 172.33 | 23.13 | 235.17 | 23.80 | 35.00 | 23.82 |
July | 98.50 | 24.23 | 446.33 | 24.38 | 78.00 | 24.42 |
August | 97.67 | 23.66 | 413.17 | 24.24 | 52.50 | 24.28 |
September | 122.33 | 23.29 | 308.00 | 24.13 | 31.00 | 24.23 |
October | 353.00 | 22.23 | 88.33 | 22.57 | 11.50 | 22.49 |
November | 469.00 | 21.32 | 130.17 | 21.07 | 130.17 | 20.90 |
December | 497.00 | 19.95 | 441.67 | 19.85 | 441.67 | 19.82 |
Annual Sum or Average | 4099.50 | 21.18 | 3319.33 | 21.50 | 1980.33 | 21.22 |
Minimum of Months | 97.67 | 19.66 | 48.33 | 19.59 | 8.83 | 19.57 |
Maximum of Months | 502.00 | 24.23 | 466.83 | 24.38 | 466.83 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.12 | 490.17 | 20.10 | 490.17 | 20.10 |
February | 454.00 | 20.24 | 437.50 | 20.21 | 437.50 | 20.20 |
March | 507.83 | 21.15 | 260.33 | 20.91 | 260.33 | 20.79 |
April | 442.50 | 21.91 | 78.17 | 21.73 | 71.17 | 21.56 |
May | 292.50 | 23.05 | 88.17 | 23.42 | 0.17 | 23.42 |
June | 64.67 | 24.24 | 327.83 | 24.37 | 19.50 | 24.44 |
July | 46.67 | 25.84 | 474.17 | 24.61 | 45.50 | 24.71 |
August | 32.17 | 25.28 | 455.33 | 24.45 | 22.33 | 24.52 |
September | 94.17 | 23.78 | 271.67 | 24.24 | 14.67 | 24.32 |
October | 403.50 | 22.58 | 35.50 | 22.66 | 6.33 | 22.63 |
November | 489.00 | 21.34 | 143.83 | 21.14 | 143.83 | 21.02 |
December | 497.00 | 20.28 | 462.33 | 20.25 | 462.33 | 20.23 |
Annual Sum or Average | 3826.00 | 21.41 | 3525.00 | 21.79 | 1973.83 | 21.52 |
Minimum of Months | 32.17 | 20.12 | 35.50 | 20.10 | 0.17 | 20.10 |
Maximum of Months | 507.83 | 25.84 | 490.17 | 24.61 | 490.17 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.00 | 491.83 | 19.99 | 491.83 | 19.98 |
February | 454.00 | 20.09 | 440.17 | 20.08 | 440.17 | 20.07 |
March | 492.33 | 20.97 | 278.33 | 20.78 | 271.33 | 20.66 |
April | 475.67 | 22.07 | 60.67 | 21.84 | 60.67 | 21.67 |
May | 287.67 | 23.28 | 61.17 | 23.46 | 0.00 | 23.46 |
June | 63.00 | 23.96 | 280.33 | 24.24 | 9.00 | 24.27 |
July | 33.17 | 25.40 | 466.33 | 24.47 | 32.50 | 24.53 |
August | 28.00 | 23.84 | 401.67 | 24.26 | 7.50 | 24.27 |
September | 157.67 | 23.38 | 168.17 | 23.83 | 12.00 | 23.90 |
October | 449.83 | 22.11 | 43.67 | 22.01 | 37.83 | 21.91 |
November | 489.00 | 20.97 | 210.83 | 20.77 | 210.83 | 20.66 |
December | 497.00 | 20.09 | 465.00 | 20.05 | 465.00 | 20.04 |
Annual Sum or Average | 3929.33 | 21.27 | 3368.17 | 21.53 | 2038.67 | 21.26 |
Minimum of Months | 28.00 | 20.00 | 43.67 | 19.99 | 0.00 | 19.98 |
Maximum of Months | 502.00 | 25.40 | 491.83 | 24.47 | 491.83 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.90 | 418.00 | 19.89 | 418.00 | 19.89 |
February | 385.00 | 20.06 | 351.00 | 19.99 | 351.00 | 19.97 |
March | 409.00 | 21.23 | 191.83 | 20.99 | 179.17 | 20.82 |
April | 325.83 | 22.13 | 62.33 | 22.07 | 39.50 | 21.87 |
May | 178.83 | 23.36 | 123.17 | 23.91 | 4.83 | 23.95 |
June | 54.00 | 24.90 | 298.33 | 24.59 | 24.00 | 24.70 |
July | 63.50 | 26.31 | 407.17 | 24.86 | 63.50 | 25.03 |
August | 40.67 | 25.31 | 363.17 | 24.55 | 26.67 | 24.66 |
September | 109.00 | 23.72 | 219.50 | 24.27 | 19.33 | 24.38 |
October | 342.83 | 22.29 | 46.00 | 22.29 | 25.00 | 22.18 |
November | 416.67 | 21.10 | 166.00 | 20.86 | 166.00 | 20.72 |
December | 422.00 | 19.98 | 394.00 | 19.94 | 394.00 | 19.93 |
Annual Sum or Average | 3174.33 | 21.35 | 3040.50 | 21.76 | 1711.00 | 21.49 |
Minimum of Months | 40.67 | 19.90 | 46.00 | 19.89 | 4.83 | 19.89 |
Maximum of Months | 427.00 | 26.31 | 418.00 | 24.86 | 418.00 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.33 | 20.48 | 403.83 | 20.29 | 402.83 | 20.22 |
February | 448.17 | 20.56 | 341.17 | 20.33 | 341.17 | 20.24 |
March | 440.83 | 21.65 | 165.83 | 21.41 | 147.00 | 21.21 |
April | 362.83 | 22.17 | 71.67 | 22.17 | 42.83 | 21.99 |
May | 220.67 | 23.21 | 126.67 | 23.69 | 2.67 | 23.72 |
June | 75.83 | 24.09 | 318.83 | 24.30 | 17.33 | 24.38 |
July | 63.67 | 25.85 | 463.50 | 24.64 | 57.67 | 24.78 |
August | 47.17 | 25.02 | 428.33 | 24.44 | 25.33 | 24.53 |
September | 115.33 | 23.90 | 291.50 | 24.29 | 24.67 | 24.42 |
October | 323.33 | 22.41 | 103.83 | 22.72 | 20.67 | 22.62 |
November | 446.17 | 21.47 | 141.00 | 21.23 | 136.17 | 21.06 |
December | 492.67 | 20.47 | 393.33 | 20.32 | 393.33 | 20.27 |
Annual Sum or Average | 3534.00 | 21.63 | 3249.50 | 22.03 | 1611.67 | 21.76 |
Minimum of Months | 47.17 | 20.47 | 71.67 | 20.29 | 2.67 | 20.22 |
Maximum of Months | 497.33 | 25.85 | 463.50 | 24.64 | 402.83 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 476.83 | 20.03 | 476.83 | 20.01 |
February | 454.00 | 20.22 | 405.83 | 20.14 | 405.83 | 20.11 |
March | 475.67 | 21.33 | 223.00 | 21.08 | 210.33 | 20.91 |
April | 390.17 | 22.10 | 84.50 | 22.09 | 49.83 | 21.90 |
May | 222.67 | 23.36 | 146.67 | 23.83 | 7.67 | 23.89 |
June | 72.67 | 24.61 | 350.50 | 24.44 | 29.67 | 24.55 |
July | 63.83 | 25.92 | 472.50 | 24.67 | 59.33 | 24.82 |
August | 43.17 | 25.01 | 442.33 | 24.44 | 23.33 | 24.52 |
September | 135.67 | 23.73 | 251.50 | 24.16 | 23.17 | 24.29 |
October | 401.00 | 22.22 | 66.83 | 22.24 | 33.00 | 22.12 |
November | 485.33 | 21.13 | 186.83 | 20.90 | 186.83 | 20.76 |
December | 497.00 | 20.13 | 450.50 | 20.08 | 450.50 | 20.06 |
Annual Sum or Average | 3743.17 | 21.41 | 3557.83 | 21.80 | 1956.33 | 21.54 |
Minimum of Months | 43.17 | 20.06 | 66.83 | 20.03 | 7.67 | 20.01 |
Maximum of Months | 502.00 | 25.92 | 476.83 | 24.67 | 476.83 | 24.82 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.65302 | 19.51617 | -0.4575 | 10.58295 |
February | 454.00000 | 21.88018 | 18.92429 | -0.3986 | 8.86448 |
March | 514.00000 | 23.14988 | 25.80163 | -0.0307 | 5.99666 |
April | 485.00000 | 23.79157 | 29.29622 | 0.17189 | 6.01421 |
May | 508.00000 | 24.27677 | 32.94846 | -0.5350 | 11.43916 |
June | 496.00000 | 24.29290 | 43.73582 | -0.4021 | 8.75708 |
July | 497.00000 | 24.38386 | 51.87143 | -0.3025 | 7.29195 |
August | 514.00000 | 24.33575 | 48.48708 | -0.3407 | 7.78883 |
September | 485.00000 | 24.33155 | 44.05555 | -0.3972 | 8.75338 |
October | 502.00000 | 24.11747 | 34.28838 | 0.30525 | 7.18390 |
November | 489.00000 | 23.52512 | 29.21509 | 0.08827 | 5.64742 |
December | 497.00000 | 22.18087 | 22.49513 | -0.2999 | 7.64215 |
Annual Sum or Average | 5943.00000 | 23.50430 | 33.49128 | -0.2162 | 7.99763 |
Minimum of Months | 454.00000 | 21.65302 | 18.92429 | -0.5350 | 5.64742 |
Maximum of Months | 514.00000 | 24.38386 | 51.87143 | 0.30525 | 11.43916 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.81432 | 20.15134 | -0.6567 | 15.09142 |
February | 454.00000 | 20.98901 | 19.63958 | -0.6124 | 13.53081 |
March | 514.00000 | 22.14089 | 27.17937 | -0.2517 | 7.94686 |
April | 485.00000 | 23.07795 | 31.03908 | 0.01446 | 5.95728 |
May | 508.00000 | 23.99794 | 34.19823 | -0.6251 | 13.76596 |
June | 496.00000 | 24.18704 | 44.38076 | -0.4442 | 9.49425 |
July | 497.00000 | 24.30458 | 52.29460 | -0.3357 | 7.66618 |
August | 514.00000 | 24.25836 | 49.04785 | -0.3791 | 8.29329 |
September | 485.00000 | 24.15403 | 44.90088 | -0.4730 | 10.20259 |
October | 502.00000 | 23.38059 | 36.53407 | 0.12957 | 6.05810 |
November | 489.00000 | 22.25414 | 31.56395 | -0.2007 | 6.72075 |
December | 497.00000 | 21.02052 | 23.57610 | -0.5750 | 12.71318 |
Annual Sum or Average | 5943.00000 | 22.89553 | 34.64785 | -0.3665 | 9.76986 |
Minimum of Months | 454.00000 | 20.81432 | 19.63958 | -0.6567 | 5.95728 |
Maximum of Months | 514.00000 | 24.30458 | 52.29460 | 0.12957 | 15.09142 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38905 | 20.04530 | -0.7889 | 19.72060 |
February | 454.00000 | 20.52669 | 19.92967 | -0.7495 | 18.30928 |
March | 514.00000 | 21.59347 | 27.67295 | -0.3969 | 10.78300 |
April | 485.00000 | 22.56399 | 31.83150 | -0.1117 | 6.88473 |
May | 508.00000 | 23.80591 | 34.54089 | -0.6914 | 16.00845 |
June | 496.00000 | 24.12954 | 44.53047 | -0.4580 | 9.93855 |
July | 497.00000 | 24.30440 | 52.15758 | -0.3281 | 7.63260 |
August | 514.00000 | 24.20529 | 49.02968 | -0.3957 | 8.60293 |
September | 485.00000 | 23.93967 | 45.41011 | -0.5530 | 12.33548 |
October | 502.00000 | 22.64553 | 38.02489 | -0.0516 | 6.63437 |
November | 489.00000 | 21.40850 | 32.78941 | -0.4170 | 9.83439 |
December | 497.00000 | 20.48823 | 24.06403 | -0.7334 | 17.76071 |
Annual Sum or Average | 5943.00000 | 22.51551 | 35.10629 | -0.4714 | 12.00069 |
Minimum of Months | 454.00000 | 20.38905 | 19.92967 | -0.7889 | 6.63437 |
Maximum of Months | 514.00000 | 24.30440 | 52.15758 | -0.0516 | 19.72060 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81489 | 20.75093 | -0.9832 | 27.69345 |
February | 454.00000 | 19.86341 | 20.91269 | -0.9524 | 26.52782 |
March | 514.00000 | 20.81654 | 29.33791 | -0.5977 | 16.33189 |
April | 485.00000 | 21.71032 | 33.28564 | -0.3054 | 9.78770 |
May | 508.00000 | 23.40160 | 36.59258 | -0.8016 | 20.77630 |
June | 496.00000 | 24.08157 | 45.63827 | -0.4360 | 10.36890 |
July | 497.00000 | 24.36430 | 53.73297 | -0.2556 | 7.38377 |
August | 514.00000 | 24.13560 | 50.24614 | -0.3843 | 9.13098 |
September | 485.00000 | 23.58368 | 47.48245 | -0.6570 | 16.40545 |
October | 502.00000 | 21.70894 | 40.06320 | -0.2664 | 9.22321 |
November | 489.00000 | 20.53239 | 33.96725 | -0.6427 | 15.51647 |
December | 497.00000 | 19.82277 | 24.83660 | -0.9419 | 26.25909 |
Annual Sum or Average | 5943.00000 | 22.00399 | 36.51127 | -0.5997 | 16.21618 |
Minimum of Months | 454.00000 | 19.81489 | 20.75093 | -0.9832 | 7.38377 |
Maximum of Months | 514.00000 | 24.36430 | 53.73297 | -0.2556 | 27.69345 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87445 | 21.57927 | -0.9493 | 26.36485 |
February | 454.00000 | 19.96338 | 21.73471 | -0.9032 | 24.82533 |
March | 514.00000 | 21.16817 | 29.68344 | -0.4835 | 14.01024 |
April | 485.00000 | 22.32035 | 32.36453 | -0.1323 | 9.14025 |
May | 508.00000 | 23.75279 | 35.44312 | -0.6242 | 16.12758 |
June | 496.00000 | 24.24999 | 44.85834 | -0.3054 | 8.94269 |
July | 497.00000 | 24.49879 | 52.95646 | -0.1312 | 7.18921 |
August | 514.00000 | 24.25809 | 49.60641 | -0.2706 | 8.09699 |
September | 485.00000 | 23.88895 | 46.35288 | -0.4994 | 13.03863 |
October | 502.00000 | 22.20788 | 39.50435 | -0.1343 | 8.53096 |
November | 489.00000 | 20.72266 | 34.50911 | -0.5855 | 14.37564 |
December | 497.00000 | 19.88127 | 25.60452 | -0.9171 | 25.22721 |
Annual Sum or Average | 5943.00000 | 22.25038 | 36.28455 | -0.4920 | 14.58477 |
Minimum of Months | 454.00000 | 19.87445 | 21.57927 | -0.9493 | 7.18921 |
Maximum of Months | 514.00000 | 24.49879 | 52.95646 | -0.1312 | 26.36485 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.23310 | 20.46418 | -0.8373 | 23.35520 |
February | 454.00000 | 20.29607 | 20.51791 | -0.8009 | 22.62171 |
March | 514.00000 | 21.63414 | 27.94242 | -0.3611 | 12.45855 |
April | 485.00000 | 22.30614 | 31.54288 | -0.1397 | 9.45661 |
May | 508.00000 | 23.55931 | 35.61083 | -0.7089 | 18.95935 |
June | 496.00000 | 24.08564 | 45.36615 | -0.4025 | 10.57398 |
July | 497.00000 | 24.39938 | 53.35127 | -0.2043 | 7.64607 |
August | 514.00000 | 24.21238 | 49.56729 | -0.2984 | 8.63345 |
September | 485.00000 | 23.91312 | 45.74914 | -0.4676 | 13.09012 |
October | 502.00000 | 22.52091 | 37.51650 | -0.0412 | 8.88845 |
November | 489.00000 | 21.19539 | 32.59323 | -0.4620 | 12.84651 |
December | 497.00000 | 20.17471 | 24.53050 | -0.8239 | 22.35660 |
Annual Sum or Average | 5943.00000 | 22.39456 | 35.50148 | -0.4602 | 14.18515 |
Minimum of Months | 454.00000 | 20.17471 | 20.46418 | -0.8373 | 7.64607 |
Maximum of Months | 514.00000 | 24.39938 | 53.35127 | -0.0412 | 23.35520 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88255 | 21.45510 | -0.9562 | 26.70666 |
February | 454.00000 | 19.99668 | 21.57100 | -0.9047 | 25.10672 |
March | 514.00000 | 21.22179 | 29.49846 | -0.4798 | 14.30289 |
April | 485.00000 | 22.12403 | 32.71920 | -0.1841 | 9.83786 |
May | 508.00000 | 23.59590 | 36.22498 | -0.6792 | 18.56411 |
June | 496.00000 | 24.15882 | 45.39859 | -0.3329 | 9.93705 |
July | 497.00000 | 24.43733 | 53.45446 | -0.1635 | 7.53774 |
August | 514.00000 | 24.22597 | 49.95896 | -0.2870 | 8.62318 |
September | 485.00000 | 23.77540 | 47.03559 | -0.5456 | 14.61833 |
October | 502.00000 | 21.99888 | 39.79046 | -0.1839 | 9.10486 |
November | 489.00000 | 20.69527 | 34.51437 | -0.5942 | 14.75114 |
December | 497.00000 | 19.87466 | 25.55897 | -0.9195 | 25.41832 |
Annual Sum or Average | 5943.00000 | 22.18356 | 36.53506 | -0.5166 | 15.30757 |
Minimum of Months | 454.00000 | 19.87466 | 21.45510 | -0.9562 | 7.53774 |
Maximum of Months | 514.00000 | 24.43733 | 53.45446 | -0.1635 | 26.70666 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05042 | 20.79170 | -0.9193 | 24.43434 |
February | 454.00000 | 20.13189 | 20.96320 | -0.8887 | 23.11276 |
March | 514.00000 | 20.78612 | 29.93306 | -0.6194 | 15.15032 |
April | 485.00000 | 21.39521 | 34.36336 | -0.3939 | 9.45969 |
May | 508.00000 | 22.97003 | 38.50922 | -0.9864 | 27.09328 |
June | 496.00000 | 23.98523 | 46.46000 | -0.5185 | 11.33931 |
July | 497.00000 | 24.25927 | 54.23082 | -0.3344 | 7.73393 |
August | 514.00000 | 24.15234 | 50.41642 | -0.4042 | 8.85213 |
September | 485.00000 | 23.82095 | 47.24995 | -0.5856 | 13.27929 |
October | 502.00000 | 22.45741 | 38.88533 | -0.0801 | 6.49467 |
November | 489.00000 | 21.10202 | 33.47088 | -0.4716 | 10.53799 |
December | 497.00000 | 20.22968 | 24.79427 | -0.8178 | 20.53555 |
Annual Sum or Average | 5943.00000 | 22.12727 | 36.78392 | -0.5835 | 14.80328 |
Minimum of Months | 454.00000 | 20.05042 | 20.79170 | -0.9864 | 6.49467 |
Maximum of Months | 514.00000 | 24.25927 | 54.23082 | -0.0801 | 27.09328 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14230 | 21.63801 | -0.8801 | 22.86464 |
February | 454.00000 | 20.24048 | 21.84786 | -0.8390 | 21.25747 |
March | 514.00000 | 21.16268 | 30.37881 | -0.4934 | 12.41843 |
April | 485.00000 | 22.33085 | 33.26634 | -0.1470 | 7.84562 |
May | 508.00000 | 23.66321 | 36.56195 | -0.7057 | 17.64417 |
June | 496.00000 | 24.25883 | 45.05603 | -0.3501 | 8.77605 |
July | 497.00000 | 24.48251 | 53.00826 | -0.1768 | 6.79835 |
August | 514.00000 | 24.32428 | 49.47155 | -0.2680 | 7.46663 |
September | 485.00000 | 24.15677 | 45.85279 | -0.4118 | 9.96140 |
October | 502.00000 | 23.06680 | 37.95256 | 0.07742 | 6.60153 |
November | 489.00000 | 21.39552 | 33.87093 | -0.3916 | 9.55852 |
December | 497.00000 | 20.29023 | 25.64151 | -0.7935 | 19.59798 |
Annual Sum or Average | 5943.00000 | 22.47597 | 36.31539 | -0.4463 | 12.52053 |
Minimum of Months | 454.00000 | 20.14230 | 21.63801 | -0.8801 | 6.60153 |
Maximum of Months | 514.00000 | 24.48251 | 53.00826 | 0.07742 | 22.86464 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65602 | 18.58989 | -0.9319 | 25.70408 |
February | 454.00000 | 19.69493 | 18.94318 | -0.9073 | 24.51303 |
March | 514.00000 | 20.96027 | 27.08965 | -0.4899 | 12.74784 |
April | 485.00000 | 21.69254 | 31.64850 | -0.2750 | 9.01165 |
May | 508.00000 | 22.91408 | 36.63850 | -0.9444 | 26.69904 |
June | 496.00000 | 23.82180 | 46.72774 | -0.5232 | 12.65498 |
July | 497.00000 | 24.29445 | 54.82907 | -0.2700 | 7.84155 |
August | 514.00000 | 24.16629 | 50.27165 | -0.3206 | 8.71746 |
September | 485.00000 | 24.01537 | 45.72155 | -0.4168 | 11.22569 |
October | 502.00000 | 22.84832 | 35.65618 | 0.07097 | 7.38823 |
November | 489.00000 | 21.44138 | 30.30915 | -0.3484 | 9.67607 |
December | 497.00000 | 19.95374 | 22.76326 | -0.8247 | 21.50771 |
Annual Sum or Average | 5943.00000 | 22.13936 | 35.04859 | -0.5132 | 14.76488 |
Minimum of Months | 454.00000 | 19.65602 | 18.58989 | -0.9444 | 7.38823 |
Maximum of Months | 514.00000 | 24.29445 | 54.82907 | 0.07097 | 26.69904 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11622 | 21.58718 | -0.8935 | 23.49722 |
February | 454.00000 | 20.23934 | 21.77297 | -0.8471 | 21.68824 |
March | 514.00000 | 21.18344 | 30.35199 | -0.4933 | 12.45763 |
April | 485.00000 | 22.11701 | 33.57772 | -0.2021 | 8.19771 |
May | 508.00000 | 23.58605 | 37.07634 | -0.7374 | 18.89037 |
June | 496.00000 | 24.23913 | 45.28710 | -0.3521 | 8.89061 |
July | 497.00000 | 24.46498 | 53.31721 | -0.1935 | 6.91163 |
August | 514.00000 | 24.33867 | 49.61669 | -0.2682 | 7.54896 |
September | 485.00000 | 24.11802 | 46.23390 | -0.4363 | 10.45950 |
October | 502.00000 | 22.87573 | 38.31431 | 0.03095 | 6.60364 |
November | 489.00000 | 21.33677 | 33.96363 | -0.4067 | 9.70600 |
December | 497.00000 | 20.27750 | 25.64046 | -0.7971 | 19.77809 |
Annual Sum or Average | 5943.00000 | 22.42436 | 36.49931 | -0.4643 | 12.83969 |
Minimum of Months | 454.00000 | 20.11622 | 21.58718 | -0.8935 | 6.60364 |
Maximum of Months | 514.00000 | 24.46498 | 53.31721 | 0.03095 | 23.49722 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.99828 | 20.75553 | -0.9047 | 24.22734 |
February | 454.00000 | 20.09302 | 20.85234 | -0.8657 | 22.63145 |
March | 514.00000 | 21.09811 | 29.08934 | -0.5053 | 13.37477 |
April | 485.00000 | 22.10540 | 32.74665 | -0.2008 | 7.91432 |
May | 508.00000 | 23.64467 | 36.08314 | -0.7215 | 17.34050 |
June | 496.00000 | 24.15646 | 45.30220 | -0.4166 | 9.41570 |
July | 497.00000 | 24.37966 | 53.57243 | -0.2591 | 7.11118 |
August | 514.00000 | 24.20943 | 50.01496 | -0.3625 | 8.38541 |
September | 485.00000 | 23.84027 | 46.77316 | -0.5669 | 13.07928 |
October | 502.00000 | 22.30710 | 38.88186 | -0.1122 | 7.12233 |
November | 489.00000 | 20.97021 | 33.37736 | -0.5051 | 11.58424 |
December | 497.00000 | 20.08503 | 24.69146 | -0.8423 | 21.91115 |
Annual Sum or Average | 5943.00000 | 22.25774 | 36.11820 | -0.5198 | 13.62053 |
Minimum of Months | 454.00000 | 19.99828 | 20.75553 | -0.9047 | 7.11118 |
Maximum of Months | 514.00000 | 24.37966 | 53.57243 | -0.1122 | 24.22734 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.90477 | 21.21245 | -0.9113 | 24.54024 |
February | 385.00000 | 20.05855 | 21.41256 | -0.8539 | 22.43858 |
March | 433.00000 | 21.38212 | 29.18855 | -0.4155 | 11.77704 |
April | 410.00000 | 22.57585 | 31.71403 | -0.0659 | 7.96695 |
May | 430.00000 | 23.91990 | 34.85892 | -0.5812 | 14.50569 |
June | 418.00000 | 24.36745 | 44.35908 | -0.2905 | 8.57627 |
July | 422.00000 | 24.61302 | 52.53932 | -0.1243 | 7.17532 |
August | 433.00000 | 24.37419 | 49.10487 | -0.2567 | 7.80114 |
September | 410.00000 | 24.10572 | 45.75978 | -0.4369 | 11.19674 |
October | 427.00000 | 22.65908 | 38.11199 | -0.0188 | 7.19890 |
November | 417.00000 | 21.09923 | 33.47442 | -0.4683 | 11.28040 |
December | 422.00000 | 19.97840 | 25.09196 | -0.8586 | 22.53027 |
Annual Sum or Average | 5034.00000 | 22.43471 | 35.65581 | -0.4379 | 13.02899 |
Minimum of Months | 385.00000 | 19.90477 | 21.21245 | -0.9113 | 7.17532 |
Maximum of Months | 433.00000 | 24.61302 | 52.53932 | -0.0188 | 24.54024 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.51752 | 20.27161 | -0.7402 | 19.76238 |
February | 454.00000 | 20.60459 | 20.28277 | -0.6996 | 18.57621 |
March | 514.00000 | 21.99410 | 27.47734 | -0.2551 | 10.04911 |
April | 485.00000 | 22.70225 | 30.92172 | -0.0360 | 7.93605 |
May | 508.00000 | 23.78995 | 35.08157 | -0.6328 | 15.66843 |
June | 496.00000 | 24.17978 | 44.96076 | -0.3785 | 9.41062 |
July | 497.00000 | 24.43801 | 53.10695 | -0.2021 | 7.21720 |
August | 514.00000 | 24.29012 | 49.30441 | -0.2764 | 7.86173 |
September | 485.00000 | 24.12164 | 45.19508 | -0.3914 | 10.51891 |
October | 502.00000 | 23.06505 | 36.35782 | 0.10098 | 7.79251 |
November | 489.00000 | 21.69751 | 31.82654 | -0.3139 | 9.74633 |
December | 497.00000 | 20.50671 | 24.24189 | -0.7113 | 18.10766 |
Annual Sum or Average | 5943.00000 | 22.67519 | 35.02378 | -0.3762 | 11.84631 |
Minimum of Months | 454.00000 | 20.50671 | 20.27161 | -0.7402 | 7.21720 |
Maximum of Months | 514.00000 | 24.43801 | 53.10695 | 0.10098 | 19.76238 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05900 | 21.54177 | -0.8788 | 23.40357 |
February | 454.00000 | 20.21689 | 21.57423 | -0.8199 | 21.42175 |
March | 514.00000 | 21.53314 | 29.19911 | -0.3822 | 11.63920 |
April | 485.00000 | 22.53292 | 32.12442 | -0.0776 | 8.17844 |
May | 508.00000 | 23.84261 | 35.64886 | -0.5988 | 15.13173 |
June | 496.00000 | 24.25141 | 44.98823 | -0.3091 | 8.79869 |
July | 497.00000 | 24.47614 | 53.21560 | -0.1610 | 7.11701 |
August | 514.00000 | 24.30465 | 49.69145 | -0.2644 | 7.84902 |
September | 485.00000 | 24.01582 | 46.33848 | -0.4606 | 11.58666 |
October | 502.00000 | 22.58892 | 38.57487 | -0.0322 | 7.28300 |
November | 489.00000 | 21.15627 | 33.89759 | -0.4531 | 10.99791 |
December | 497.00000 | 20.13334 | 25.48288 | -0.8207 | 21.17283 |
Annual Sum or Average | 5943.00000 | 22.44347 | 36.12491 | -0.4358 | 12.82555 |
Minimum of Months | 454.00000 | 20.05900 | 21.54177 | -0.8788 | 7.11701 |
Maximum of Months | 514.00000 | 24.47614 | 53.21560 | -0.0322 | 23.40357 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.146241E+10 | 0.346524E+09 | 33.50 | 0.113478E+10 | 0.327631E+09 | 0.00 | 0.80 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 22692.99 | 15-MAR-14:00 | 22692.99 | 15-MAR-14:00 | 6877.25 | 14-MAR-11:00 | 5281.05 | 15-MAR-14:00 | 0.00 |
April | 0.576657E+09 | 0.146775E+09 | 40.11 | 0.507277E+09 | 69379336.83 | 0.00 | 0.40 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 10390.83 | 08-APR-13:30 | 9912.29 | 07-APR-14:00 | 2478.48 | 08-APR-14:00 | 2540.75 | 08-APR-13:30 | 0.00 |
May | 0.644437E+10 | 0.152828E+10 | 196.99 | 0.579930E+10 | 0.645065E+09 | 0.00 | 1.00 | 23-MAY-13:50 | 0.00 | 01-MAY-00:10 | 32744.86 | 23-MAY-14:30 | 32744.86 | 23-MAY-14:30 | 6080.93 | 10-MAY-17:10 | 6816.13 | 23-MAY-14:30 | 0.00 |
June | 0.314347E+11 | 0.699327E+10 | 371.00 | 0.237306E+11 | 0.770406E+10 | 0.00 | 1.00 | 01-JUN-14:20 | 0.00 | 01-JUN-00:10 | 84094.75 | 27-JUN-07:40 | 54286.21 | 12-JUN-15:10 | 47743.63 | 27-JUN-07:40 | 17834.02 | 27-JUN-11:50 | 0.00 |
July | 0.563868E+11 | 0.123744E+11 | 422.83 | 0.398506E+11 | 0.165363E+11 | 0.00 | 1.00 | 03-JUL-10:00 | 0.00 | 01-JUL-00:10 | 103826.73 | 20-JUL-06:03 | 58847.77 | 21-JUL-06:03 | 62575.67 | 20-JUL-05:03 | 21134.54 | 21-JUL-05:03 | 0.00 |
August | 0.480253E+11 | 0.105854E+11 | 413.33 | 0.372856E+11 | 0.107397E+11 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 103856.48 | 14-AUG-08:00 | 57616.66 | 09-AUG-15:50 | 63777.11 | 14-AUG-05:12 | 21204.08 | 15-AUG-08:20 | 0.00 |
September | 0.210612E+11 | 0.465616E+10 | 301.93 | 0.159993E+11 | 0.506194E+10 | 0.00 | 1.00 | 08-SEP-12:05 | 0.00 | 01-SEP-00:10 | 69422.36 | 15-SEP-11:00 | 48289.80 | 21-SEP-16:00 | 30812.77 | 15-SEP-11:00 | 14447.99 | 15-SEP-11:00 | 0.00 |
October | 0.233696E+10 | 0.565096E+09 | 88.91 | 0.198182E+10 | 0.355138E+09 | 0.00 | 0.92 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 27250.62 | 11-OCT-15:10 | 27250.62 | 11-OCT-15:10 | 4833.12 | 12-OCT-15:00 | 5798.49 | 11-OCT-15:10 | 0.00 |
November | 0.326649E+09 | 83396186.58 | 19.04 | 0.220847E+09 | 0.105801E+09 | 0.00 | 0.31 | 16-NOV-17:00 | 0.00 | 01-NOV-00:10 | 7789.05 | 16-NOV-17:00 | 5763.01 | 16-NOV-13:07 | 2339.34 | 04-NOV-15:00 | 1949.43 | 16-NOV-17:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.168055E+12 | 0.372792E+11 | 1887.64 | 0.126510E+12 | 0.415450E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.563868E+11 | 0.123744E+11 | 422.83 | 0.398506E+11 | 0.165363E+11 | 0.00 | 1.00 | 0.00 | 103856.48 | 58847.77 | 63777.11 | 21204.08 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.160273E+10 | 0.372020E+09 | 33.50 | 0.130143E+10 | 0.301304E+09 | 0.00 | 1.00 | 15-MAR-14:05 | 0.00 | 01-MAR-00:10 | 29950.62 | 15-MAR-14:05 | 29950.62 | 15-MAR-14:05 | 7236.03 | 14-MAR-10:40 | 6559.62 | 15-MAR-14:05 | 0.00 |
April | 0.581458E+09 | 0.146847E+09 | 38.58 | 0.518038E+09 | 63420622.50 | 0.00 | 0.46 | 08-APR-14:05 | 0.00 | 01-APR-00:10 | 11877.85 | 08-APR-14:05 | 11491.04 | 07-APR-14:05 | 2062.36 | 08-APR-14:00 | 2858.58 | 08-APR-14:05 | 0.00 |
May | 0.702621E+10 | 0.164669E+10 | 198.06 | 0.633591E+10 | 0.690297E+09 | 0.00 | 1.00 | 10-MAY-12:50 | 0.00 | 01-MAY-00:10 | 36710.04 | 23-MAY-14:05 | 36710.04 | 23-MAY-14:05 | 6380.38 | 14-MAY-13:50 | 8017.34 | 10-MAY-14:05 | 0.00 |
June | 0.323870E+11 | 0.718481E+10 | 378.79 | 0.244479E+11 | 0.793904E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 91870.30 | 12-JUN-06:03 | 59102.02 | 12-JUN-14:05 | 46874.77 | 27-JUN-07:40 | 19168.45 | 12-JUN-06:03 | 0.00 |
July | 0.556341E+11 | 0.122047E+11 | 430.53 | 0.391355E+11 | 0.164986E+11 | 0.00 | 1.00 | 02-JUL-15:12 | 0.00 | 01-JUL-00:10 | 101077.23 | 20-JUL-06:03 | 57441.43 | 19-JUL-14:05 | 60411.87 | 20-JUL-05:03 | 20891.09 | 21-JUL-05:03 | 0.00 |
August | 0.454032E+11 | 0.100285E+11 | 416.78 | 0.351742E+11 | 0.102290E+11 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 100816.63 | 14-AUG-10:10 | 58189.60 | 06-AUG-16:31 | 62126.76 | 14-AUG-05:12 | 20526.86 | 14-AUG-11:00 | 0.00 |
September | 0.193602E+11 | 0.430393E+10 | 301.25 | 0.145710E+11 | 0.478922E+10 | 0.00 | 1.00 | 08-SEP-12:05 | 0.00 | 01-SEP-00:10 | 69410.34 | 15-SEP-11:00 | 48062.85 | 21-SEP-15:40 | 31677.12 | 15-SEP-11:00 | 14444.18 | 15-SEP-11:00 | 0.00 |
October | 0.211252E+10 | 0.513207E+09 | 85.44 | 0.174681E+10 | 0.365712E+09 | 0.00 | 0.89 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 25418.40 | 11-OCT-15:00 | 25418.40 | 11-OCT-15:00 | 5041.97 | 12-OCT-15:00 | 5456.54 | 11-OCT-15:00 | 0.00 |
November | 0.304870E+09 | 78005266.48 | 19.33 | 0.203914E+09 | 0.100956E+09 | 0.00 | 0.29 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 7215.65 | 16-NOV-18:00 | 5213.03 | 16-NOV-12:40 | 2305.51 | 04-NOV-15:00 | 1812.11 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.164412E+12 | 0.364787E+11 | 1902.26 | 0.123435E+12 | 0.409776E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.556341E+11 | 0.122047E+11 | 430.53 | 0.391355E+11 | 0.164986E+11 | 0.00 | 1.00 | 0.00 | 101077.23 | 59102.02 | 62126.76 | 20891.09 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.179456E+10 | 0.414990E+09 | 33.67 | 0.147454E+10 | 0.320023E+09 | 0.00 | 1.00 | 15-MAR-13:20 | 0.00 | 01-MAR-00:10 | 35882.83 | 15-MAR-13:50 | 35882.83 | 15-MAR-13:50 | 7914.34 | 14-MAR-11:00 | 7864.71 | 15-MAR-14:00 | 0.00 |
April | 0.607451E+09 | 0.153913E+09 | 38.14 | 0.531068E+09 | 76382666.43 | 0.00 | 0.44 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 12662.86 | 08-APR-13:30 | 11968.53 | 07-APR-14:00 | 2412.37 | 08-APR-14:00 | 3062.78 | 08-APR-13:30 | 0.00 |
May | 0.736236E+10 | 0.173229E+10 | 198.32 | 0.659392E+10 | 0.768435E+09 | 0.00 | 1.00 | 10-MAY-12:50 | 0.00 | 01-MAY-00:10 | 42154.53 | 10-MAY-14:30 | 42154.53 | 10-MAY-14:30 | 7144.74 | 14-MAY-14:00 | 9243.32 | 10-MAY-14:30 | 0.00 |
June | 0.342709E+11 | 0.763537E+10 | 378.31 | 0.259854E+11 | 0.828551E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 81621.61 | 27-JUN-13:05 | 66523.29 | 12-JUN-14:00 | 42591.50 | 27-JUN-07:40 | 19373.39 | 27-JUN-13:00 | 0.00 |
July | 0.594625E+11 | 0.130956E+11 | 433.05 | 0.421031E+11 | 0.173594E+11 | 0.00 | 1.00 | 02-JUL-15:12 | 0.00 | 01-JUL-00:10 | 113065.43 | 20-JUL-06:03 | 66958.62 | 21-JUL-13:30 | 67420.15 | 20-JUL-05:03 | 23880.15 | 16-JUL-13:32 | 0.00 |
August | 0.476860E+11 | 0.105877E+11 | 416.22 | 0.369715E+11 | 0.107144E+11 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 111688.50 | 14-AUG-06:03 | 65590.35 | 09-AUG-15:00 | 69409.55 | 14-AUG-05:12 | 22802.75 | 14-AUG-06:03 | 0.00 |
September | 0.194053E+11 | 0.435662E+10 | 301.17 | 0.144182E+11 | 0.498716E+10 | 0.00 | 1.00 | 08-SEP-12:40 | 0.00 | 01-SEP-00:10 | 74260.61 | 15-SEP-13:10 | 53620.16 | 21-SEP-15:30 | 33376.15 | 15-SEP-13:00 | 15648.62 | 15-SEP-11:40 | 0.00 |
October | 0.200516E+10 | 0.493480E+09 | 85.77 | 0.161117E+10 | 0.393990E+09 | 0.00 | 0.79 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 24872.07 | 11-OCT-15:00 | 24872.07 | 11-OCT-15:00 | 5286.22 | 12-OCT-15:00 | 5478.39 | 11-OCT-15:00 | 0.00 |
November | 0.319646E+09 | 82054615.56 | 18.83 | 0.209878E+09 | 0.109768E+09 | 0.00 | 0.34 | 27-NOV-07:03 | 0.00 | 01-NOV-00:10 | 9333.93 | 27-NOV-07:03 | 8060.60 | 27-NOV-07:03 | 2466.48 | 04-NOV-15:00 | 2319.65 | 27-NOV-07:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.172914E+12 | 0.385520E+11 | 1903.48 | 0.129899E+12 | 0.430151E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.594625E+11 | 0.130956E+11 | 433.05 | 0.421031E+11 | 0.173594E+11 | 0.00 | 1.00 | 0.00 | 113065.43 | 66958.62 | 69409.55 | 23880.15 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.55 | 0.00 | 360.55 | 6.88 | 2064.76 | 0.00 | 0.00 | 0.00 |
February | 549.34 | 0.00 | 549.34 | 43.06 | 1928.50 | 0.00 | 0.00 | 0.00 |
March | 666.20 | 0.00 | 666.20 | 230.59 | 1389.11 | 0.00 | 0.00 | 0.00 |
April | 848.87 | 3.39 | 845.48 | 478.02 | 991.32 | 0.00 | 0.00 | 0.00 |
May | 986.34 | 41.83 | 944.52 | 782.02 | 654.56 | 0.00 | 0.00 | 0.00 |
June | 1186.36 | 100.99 | 1085.38 | 1282.42 | 428.18 | 0.00 | 0.00 | 0.00 |
July | 1100.51 | 71.04 | 1029.47 | 1371.70 | 300.95 | 0.00 | 0.00 | 0.00 |
August | 952.25 | 14.49 | 937.76 | 1123.54 | 396.82 | 0.00 | 0.00 | 0.00 |
September | 724.68 | 0.15 | 724.53 | 660.70 | 643.00 | 0.00 | 0.00 | 0.00 |
October | 541.73 | 0.00 | 541.73 | 280.62 | 984.83 | 0.00 | 0.00 | 0.00 |
November | 364.03 | 0.00 | 364.03 | 90.42 | 1252.49 | 0.00 | 0.00 | 0.00 |
December | 337.46 | 0.00 | 337.46 | 7.84 | 1955.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 718.89 | 19.41 | 699.49 | 532.74 | 1078.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.46 | 0.00 | 337.46 | 6.88 | 300.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1186.36 | 100.99 | 1085.38 | 1371.70 | 2064.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.87 | 141.84 | 298.03 | 179.41 | 1250.83 | 0.00 | 0.00 | 0.00 |
February | 645.43 | 193.68 | 451.75 | 321.21 | 1183.86 | 0.00 | 0.00 | 0.00 |
March | 926.17 | 387.87 | 538.29 | 740.93 | 855.94 | 0.00 | 0.00 | 0.00 |
April | 1225.84 | 541.64 | 684.20 | 1167.18 | 633.30 | 0.00 | 0.00 | 0.00 |
May | 1373.38 | 607.52 | 765.86 | 1494.53 | 447.23 | 0.00 | 0.00 | 0.00 |
June | 1533.84 | 677.88 | 855.96 | 1863.80 | 292.67 | 0.00 | 0.00 | 0.00 |
July | 1472.88 | 648.49 | 824.39 | 1920.94 | 203.70 | 0.00 | 0.00 | 0.00 |
August | 1330.18 | 558.34 | 771.84 | 1699.04 | 265.11 | 0.00 | 0.00 | 0.00 |
September | 1106.94 | 491.00 | 615.94 | 1279.69 | 415.18 | 0.00 | 0.00 | 0.00 |
October | 751.15 | 310.70 | 440.45 | 683.97 | 626.74 | 0.00 | 0.00 | 0.00 |
November | 426.07 | 136.68 | 289.39 | 276.82 | 799.67 | 0.00 | 0.00 | 0.00 |
December | 343.00 | 70.87 | 272.13 | 95.31 | 1224.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.99 | 398.17 | 567.82 | 980.43 | 680.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.00 | 70.87 | 272.13 | 95.31 | 203.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1533.84 | 677.88 | 855.96 | 1920.94 | 1250.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1550.36 | 904.99 | 645.37 | 1280.57 | 1764.90 | 0.00 | 0.00 | 0.00 |
February | 1770.13 | 853.54 | 916.59 | 1443.64 | 1734.08 | 0.00 | 0.00 | 0.00 |
March | 2160.56 | 1214.00 | 946.55 | 2150.08 | 1291.55 | 0.00 | 0.00 | 0.00 |
April | 1789.28 | 715.00 | 1074.28 | 1852.59 | 1030.96 | 0.00 | 0.00 | 0.00 |
May | 1565.78 | 454.77 | 1111.01 | 1747.18 | 722.79 | 0.00 | 0.00 | 0.00 |
June | 1521.43 | 322.40 | 1199.03 | 1891.52 | 471.55 | 0.00 | 0.00 | 0.00 |
July | 1553.14 | 376.84 | 1176.30 | 2134.22 | 327.41 | 0.00 | 0.00 | 0.00 |
August | 1743.65 | 565.34 | 1178.32 | 2360.55 | 421.22 | 0.00 | 0.00 | 0.00 |
September | 2027.35 | 987.47 | 1039.88 | 2536.35 | 660.12 | 0.00 | 0.00 | 0.00 |
October | 1939.87 | 1108.09 | 831.78 | 2117.78 | 960.76 | 0.00 | 0.00 | 0.00 |
November | 1389.30 | 784.30 | 604.99 | 1343.38 | 1190.94 | 0.00 | 0.00 | 0.00 |
December | 1296.41 | 670.95 | 625.46 | 1017.43 | 1727.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1691.75 | 746.08 | 945.67 | 1825.15 | 1021.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1296.41 | 322.40 | 604.99 | 1017.43 | 327.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2160.56 | 1214.00 | 1199.03 | 2536.35 | 1764.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.40 | 88.60 | 288.80 | 111.34 | 1299.07 | 0.00 | 0.00 | 0.00 |
February | 611.66 | 157.20 | 454.46 | 277.27 | 1222.82 | 0.00 | 0.00 | 0.00 |
March | 958.67 | 410.48 | 548.19 | 782.60 | 879.70 | 0.00 | 0.00 | 0.00 |
April | 1173.77 | 481.29 | 692.48 | 1117.11 | 661.37 | 0.00 | 0.00 | 0.00 |
May | 1384.65 | 625.77 | 758.88 | 1519.23 | 472.91 | 0.00 | 0.00 | 0.00 |
June | 1670.62 | 785.79 | 884.83 | 2055.34 | 317.74 | 0.00 | 0.00 | 0.00 |
July | 1493.59 | 654.84 | 838.75 | 1957.11 | 224.93 | 0.00 | 0.00 | 0.00 |
August | 1350.87 | 574.40 | 776.47 | 1743.45 | 283.88 | 0.00 | 0.00 | 0.00 |
September | 1060.85 | 458.14 | 602.72 | 1229.10 | 436.74 | 0.00 | 0.00 | 0.00 |
October | 687.69 | 242.25 | 445.45 | 613.93 | 648.18 | 0.00 | 0.00 | 0.00 |
November | 407.53 | 117.44 | 290.09 | 255.42 | 815.23 | 0.00 | 0.00 | 0.00 |
December | 353.29 | 76.98 | 276.31 | 107.80 | 1244.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.47 | 390.56 | 571.91 | 984.58 | 706.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.29 | 76.98 | 276.31 | 107.80 | 224.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1670.62 | 785.79 | 884.83 | 2055.34 | 1299.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.18 | 0.00 | 120.18 | 1.55 | 699.26 | 0.00 | 0.00 | 0.00 |
February | 183.10 | 0.00 | 183.10 | 13.95 | 652.79 | 0.00 | 0.00 | 0.00 |
March | 222.05 | 0.00 | 222.05 | 82.79 | 464.53 | 0.00 | 0.00 | 0.00 |
April | 282.94 | 1.13 | 281.81 | 171.24 | 325.49 | 0.00 | 0.00 | 0.00 |
May | 328.77 | 13.94 | 314.82 | 278.65 | 207.61 | 0.00 | 0.00 | 0.00 |
June | 395.44 | 33.66 | 361.77 | 440.09 | 138.18 | 0.00 | 0.00 | 0.00 |
July | 366.82 | 23.68 | 343.14 | 468.14 | 96.30 | 0.00 | 0.00 | 0.00 |
August | 317.40 | 4.83 | 312.57 | 380.19 | 132.41 | 0.00 | 0.00 | 0.00 |
September | 241.55 | 0.05 | 241.50 | 221.62 | 223.66 | 0.00 | 0.00 | 0.00 |
October | 180.57 | 0.00 | 180.57 | 88.05 | 358.61 | 0.00 | 0.00 | 0.00 |
November | 121.34 | 0.00 | 121.34 | 26.69 | 452.09 | 0.00 | 0.00 | 0.00 |
December | 112.48 | 0.00 | 112.48 | 1.95 | 678.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.62 | 6.47 | 233.15 | 182.25 | 367.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.48 | 0.00 | 112.48 | 1.55 | 96.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.44 | 33.66 | 361.77 | 468.14 | 699.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.18 | 0.00 | 120.18 | 1.55 | 699.31 | 0.00 | 0.00 | 0.00 |
February | 183.11 | 0.00 | 183.11 | 13.95 | 652.83 | 0.00 | 0.00 | 0.00 |
March | 222.06 | 0.00 | 222.06 | 82.79 | 464.56 | 0.00 | 0.00 | 0.00 |
April | 282.95 | 1.13 | 281.83 | 171.24 | 325.51 | 0.00 | 0.00 | 0.00 |
May | 328.78 | 13.94 | 314.84 | 278.66 | 207.62 | 0.00 | 0.00 | 0.00 |
June | 395.45 | 33.66 | 361.79 | 440.11 | 138.19 | 0.00 | 0.00 | 0.00 |
July | 366.83 | 23.68 | 343.15 | 468.16 | 96.30 | 0.00 | 0.00 | 0.00 |
August | 317.41 | 4.83 | 312.58 | 380.20 | 132.42 | 0.00 | 0.00 | 0.00 |
September | 241.56 | 0.05 | 241.51 | 221.63 | 223.67 | 0.00 | 0.00 | 0.00 |
October | 180.57 | 0.00 | 180.57 | 88.05 | 358.63 | 0.00 | 0.00 | 0.00 |
November | 121.34 | 0.00 | 121.34 | 26.69 | 452.12 | 0.00 | 0.00 | 0.00 |
December | 112.49 | 0.00 | 112.49 | 1.95 | 678.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.63 | 6.47 | 233.16 | 182.25 | 367.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.49 | 0.00 | 112.49 | 1.55 | 96.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.45 | 33.66 | 361.79 | 468.16 | 699.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.18 | 0.00 | 120.18 | 1.55 | 699.31 | 0.00 | 0.00 | 0.00 |
February | 183.11 | 0.00 | 183.11 | 13.95 | 652.83 | 0.00 | 0.00 | 0.00 |
March | 222.06 | 0.00 | 222.06 | 82.79 | 464.56 | 0.00 | 0.00 | 0.00 |
April | 282.95 | 1.13 | 281.83 | 171.24 | 325.51 | 0.00 | 0.00 | 0.00 |
May | 328.78 | 13.94 | 314.84 | 278.66 | 207.62 | 0.00 | 0.00 | 0.00 |
June | 395.45 | 33.66 | 361.79 | 440.11 | 138.19 | 0.00 | 0.00 | 0.00 |
July | 366.83 | 23.68 | 343.15 | 468.16 | 96.30 | 0.00 | 0.00 | 0.00 |
August | 317.41 | 4.83 | 312.58 | 380.20 | 132.42 | 0.00 | 0.00 | 0.00 |
September | 241.56 | 0.05 | 241.51 | 221.63 | 223.67 | 0.00 | 0.00 | 0.00 |
October | 180.57 | 0.00 | 180.57 | 88.05 | 358.63 | 0.00 | 0.00 | 0.00 |
November | 121.34 | 0.00 | 121.34 | 26.69 | 452.12 | 0.00 | 0.00 | 0.00 |
December | 112.49 | 0.00 | 112.49 | 1.95 | 678.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 239.63 | 6.47 | 233.16 | 182.25 | 367.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.49 | 0.00 | 112.49 | 1.55 | 96.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.45 | 33.66 | 361.79 | 468.16 | 699.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 423.13 | 136.44 | 286.69 | 172.60 | 1230.00 | 0.00 | 0.00 | 0.00 |
February | 620.87 | 186.31 | 434.56 | 311.07 | 1162.46 | 0.00 | 0.00 | 0.00 |
March | 890.93 | 373.11 | 517.81 | 728.00 | 837.38 | 0.00 | 0.00 | 0.00 |
April | 1179.20 | 521.03 | 658.17 | 1140.96 | 618.78 | 0.00 | 0.00 | 0.00 |
May | 1321.12 | 584.40 | 736.72 | 1462.84 | 425.59 | 0.00 | 0.00 | 0.00 |
June | 1475.47 | 652.08 | 823.39 | 1813.29 | 282.74 | 0.00 | 0.00 | 0.00 |
July | 1416.84 | 623.81 | 793.03 | 1865.84 | 196.69 | 0.00 | 0.00 | 0.00 |
August | 1279.56 | 537.09 | 742.47 | 1645.31 | 264.03 | 0.00 | 0.00 | 0.00 |
September | 1064.82 | 472.31 | 592.51 | 1233.50 | 426.39 | 0.00 | 0.00 | 0.00 |
October | 722.57 | 298.87 | 423.70 | 644.46 | 670.08 | 0.00 | 0.00 | 0.00 |
November | 409.85 | 131.48 | 278.38 | 256.36 | 841.28 | 0.00 | 0.00 | 0.00 |
December | 329.95 | 68.18 | 261.78 | 89.37 | 1227.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 929.24 | 383.02 | 546.22 | 950.39 | 679.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.95 | 68.18 | 261.78 | 89.37 | 196.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1475.47 | 652.08 | 823.39 | 1865.84 | 1230.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.73 | 5.39 | 11.34 | 6.82 | 48.63 | 0.00 | 0.00 | 0.00 |
February | 24.55 | 7.37 | 17.18 | 12.30 | 45.96 | 0.00 | 0.00 | 0.00 |
March | 35.23 | 14.75 | 20.47 | 28.78 | 33.11 | 0.00 | 0.00 | 0.00 |
April | 46.62 | 20.60 | 26.02 | 45.11 | 24.47 | 0.00 | 0.00 | 0.00 |
May | 52.24 | 23.11 | 29.13 | 57.84 | 16.83 | 0.00 | 0.00 | 0.00 |
June | 58.34 | 25.78 | 32.56 | 71.70 | 11.18 | 0.00 | 0.00 | 0.00 |
July | 56.02 | 24.66 | 31.36 | 73.77 | 7.78 | 0.00 | 0.00 | 0.00 |
August | 50.59 | 21.24 | 29.36 | 65.05 | 10.44 | 0.00 | 0.00 | 0.00 |
September | 42.10 | 18.67 | 23.43 | 48.77 | 16.86 | 0.00 | 0.00 | 0.00 |
October | 28.57 | 11.82 | 16.75 | 25.48 | 26.49 | 0.00 | 0.00 | 0.00 |
November | 16.21 | 5.20 | 11.01 | 10.14 | 33.26 | 0.00 | 0.00 | 0.00 |
December | 13.05 | 2.70 | 10.35 | 3.53 | 48.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.74 | 15.14 | 21.60 | 37.58 | 26.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.05 | 2.70 | 10.35 | 3.53 | 7.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.34 | 25.78 | 32.56 | 73.77 | 48.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.78 | 301.66 | 215.12 | 436.17 | 596.89 | 0.00 | 0.00 | 0.00 |
February | 590.03 | 284.51 | 305.52 | 494.03 | 584.35 | 0.00 | 0.00 | 0.00 |
March | 720.17 | 404.66 | 315.51 | 735.11 | 440.37 | 0.00 | 0.00 | 0.00 |
April | 596.42 | 238.33 | 358.09 | 634.93 | 343.87 | 0.00 | 0.00 | 0.00 |
May | 521.92 | 151.59 | 370.33 | 602.40 | 231.55 | 0.00 | 0.00 | 0.00 |
June | 507.14 | 107.46 | 399.68 | 646.04 | 153.39 | 0.00 | 0.00 | 0.00 |
July | 517.71 | 125.61 | 392.10 | 723.13 | 107.48 | 0.00 | 0.00 | 0.00 |
August | 581.21 | 188.44 | 392.77 | 794.46 | 144.67 | 0.00 | 0.00 | 0.00 |
September | 675.77 | 329.15 | 346.62 | 849.90 | 235.45 | 0.00 | 0.00 | 0.00 |
October | 646.61 | 369.36 | 277.26 | 706.33 | 354.15 | 0.00 | 0.00 | 0.00 |
November | 463.09 | 261.43 | 201.66 | 446.69 | 434.63 | 0.00 | 0.00 | 0.00 |
December | 432.13 | 223.65 | 208.48 | 342.98 | 595.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.91 | 248.69 | 315.22 | 618.40 | 350.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.13 | 107.46 | 201.66 | 342.98 | 107.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.17 | 404.66 | 399.68 | 849.90 | 596.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.78 | 301.66 | 215.12 | 436.17 | 596.89 | 0.00 | 0.00 | 0.00 |
February | 590.03 | 284.51 | 305.52 | 494.03 | 584.35 | 0.00 | 0.00 | 0.00 |
March | 720.17 | 404.66 | 315.51 | 735.11 | 440.37 | 0.00 | 0.00 | 0.00 |
April | 596.42 | 238.33 | 358.09 | 634.93 | 343.87 | 0.00 | 0.00 | 0.00 |
May | 521.92 | 151.59 | 370.33 | 602.40 | 231.55 | 0.00 | 0.00 | 0.00 |
June | 507.14 | 107.46 | 399.68 | 646.04 | 153.39 | 0.00 | 0.00 | 0.00 |
July | 517.71 | 125.61 | 392.10 | 723.13 | 107.48 | 0.00 | 0.00 | 0.00 |
August | 581.21 | 188.44 | 392.77 | 794.46 | 144.67 | 0.00 | 0.00 | 0.00 |
September | 675.77 | 329.15 | 346.62 | 849.90 | 235.45 | 0.00 | 0.00 | 0.00 |
October | 646.61 | 369.36 | 277.26 | 706.33 | 354.15 | 0.00 | 0.00 | 0.00 |
November | 463.09 | 261.43 | 201.66 | 446.69 | 434.63 | 0.00 | 0.00 | 0.00 |
December | 432.13 | 223.65 | 208.48 | 342.98 | 595.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.91 | 248.69 | 315.22 | 618.40 | 350.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.13 | 107.46 | 201.66 | 342.98 | 107.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.17 | 404.66 | 399.68 | 849.90 | 596.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.75 | 301.64 | 215.11 | 436.14 | 596.85 | 0.00 | 0.00 | 0.00 |
February | 589.99 | 284.49 | 305.51 | 493.99 | 584.31 | 0.00 | 0.00 | 0.00 |
March | 720.13 | 404.63 | 315.49 | 735.07 | 440.34 | 0.00 | 0.00 | 0.00 |
April | 596.38 | 238.31 | 358.07 | 634.89 | 343.85 | 0.00 | 0.00 | 0.00 |
May | 521.89 | 151.58 | 370.31 | 602.36 | 231.53 | 0.00 | 0.00 | 0.00 |
June | 507.11 | 107.46 | 399.65 | 646.00 | 153.38 | 0.00 | 0.00 | 0.00 |
July | 517.67 | 125.60 | 392.07 | 723.08 | 107.47 | 0.00 | 0.00 | 0.00 |
August | 581.17 | 188.43 | 392.74 | 794.41 | 144.66 | 0.00 | 0.00 | 0.00 |
September | 675.73 | 329.13 | 346.60 | 849.84 | 235.43 | 0.00 | 0.00 | 0.00 |
October | 646.57 | 369.33 | 277.24 | 706.29 | 354.13 | 0.00 | 0.00 | 0.00 |
November | 463.06 | 261.41 | 201.65 | 446.66 | 434.61 | 0.00 | 0.00 | 0.00 |
December | 432.10 | 223.63 | 208.47 | 342.96 | 595.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.87 | 248.67 | 315.20 | 618.36 | 350.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.10 | 107.46 | 201.65 | 342.96 | 107.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 720.13 | 404.63 | 399.65 | 849.84 | 596.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.04 | 85.23 | 277.81 | 108.42 | 1272.22 | 0.00 | 0.00 | 0.00 |
February | 588.39 | 151.22 | 437.17 | 273.06 | 1198.09 | 0.00 | 0.00 | 0.00 |
March | 922.20 | 394.86 | 527.34 | 773.79 | 862.82 | 0.00 | 0.00 | 0.00 |
April | 1129.11 | 462.98 | 666.13 | 1098.53 | 645.56 | 0.00 | 0.00 | 0.00 |
May | 1331.96 | 601.96 | 730.00 | 1488.98 | 453.87 | 0.00 | 0.00 | 0.00 |
June | 1607.05 | 755.89 | 851.16 | 2000.37 | 312.13 | 0.00 | 0.00 | 0.00 |
July | 1436.77 | 629.93 | 806.84 | 1902.67 | 220.19 | 0.00 | 0.00 | 0.00 |
August | 1299.47 | 552.55 | 746.93 | 1688.57 | 285.55 | 0.00 | 0.00 | 0.00 |
September | 1020.49 | 440.70 | 579.79 | 1186.14 | 449.92 | 0.00 | 0.00 | 0.00 |
October | 661.53 | 233.03 | 428.50 | 580.19 | 691.06 | 0.00 | 0.00 | 0.00 |
November | 392.02 | 112.97 | 279.06 | 238.23 | 855.61 | 0.00 | 0.00 | 0.00 |
December | 339.85 | 74.05 | 265.80 | 103.07 | 1245.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 925.85 | 375.70 | 550.15 | 957.15 | 705.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 339.85 | 74.05 | 265.80 | 103.07 | 220.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1607.05 | 755.89 | 851.16 | 2000.37 | 1272.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 3.37 | 10.98 | 4.29 | 50.30 | 0.00 | 0.00 | 0.00 |
February | 23.26 | 5.98 | 17.29 | 10.80 | 47.37 | 0.00 | 0.00 | 0.00 |
March | 36.46 | 15.61 | 20.85 | 30.59 | 34.12 | 0.00 | 0.00 | 0.00 |
April | 44.64 | 18.31 | 26.34 | 43.43 | 25.52 | 0.00 | 0.00 | 0.00 |
May | 52.66 | 23.80 | 28.86 | 58.87 | 17.95 | 0.00 | 0.00 | 0.00 |
June | 63.54 | 29.89 | 33.65 | 79.09 | 12.34 | 0.00 | 0.00 | 0.00 |
July | 56.81 | 24.91 | 31.90 | 75.23 | 8.71 | 0.00 | 0.00 | 0.00 |
August | 51.38 | 21.85 | 29.53 | 66.76 | 11.29 | 0.00 | 0.00 | 0.00 |
September | 40.35 | 17.42 | 22.92 | 46.90 | 17.79 | 0.00 | 0.00 | 0.00 |
October | 26.16 | 9.21 | 16.94 | 22.94 | 27.32 | 0.00 | 0.00 | 0.00 |
November | 15.50 | 4.47 | 11.03 | 9.42 | 33.83 | 0.00 | 0.00 | 0.00 |
December | 13.44 | 2.93 | 10.51 | 4.08 | 49.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.61 | 14.85 | 21.75 | 37.84 | 27.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.44 | 2.93 | 10.51 | 4.08 | 8.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.54 | 29.89 | 33.65 | 79.09 | 50.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.55 | 0.00 | 360.55 | 4.42 | 2125.64 | 0.00 | 0.00 | 0.00 |
February | 549.34 | 0.00 | 549.34 | 37.37 | 1989.49 | 0.00 | 0.00 | 0.00 |
March | 666.20 | 0.00 | 666.20 | 222.36 | 1453.13 | 0.00 | 0.00 | 0.00 |
April | 848.87 | 3.39 | 845.48 | 463.98 | 1045.30 | 0.00 | 0.00 | 0.00 |
May | 986.34 | 41.83 | 944.52 | 774.25 | 681.74 | 0.00 | 0.00 | 0.00 |
June | 1186.36 | 100.99 | 1085.38 | 1283.74 | 439.87 | 0.00 | 0.00 | 0.00 |
July | 1100.51 | 71.04 | 1029.47 | 1377.49 | 306.87 | 0.00 | 0.00 | 0.00 |
August | 952.25 | 14.49 | 937.76 | 1124.79 | 408.83 | 0.00 | 0.00 | 0.00 |
September | 724.68 | 0.15 | 724.53 | 654.15 | 676.67 | 0.00 | 0.00 | 0.00 |
October | 541.73 | 0.00 | 541.73 | 261.55 | 1061.31 | 0.00 | 0.00 | 0.00 |
November | 364.03 | 0.00 | 364.03 | 79.19 | 1340.89 | 0.00 | 0.00 | 0.00 |
December | 337.46 | 0.00 | 337.46 | 5.71 | 2030.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 718.89 | 19.41 | 699.49 | 527.03 | 1125.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.46 | 0.00 | 337.46 | 4.42 | 306.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1186.36 | 100.99 | 1085.38 | 1377.49 | 2125.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.87 | 141.84 | 298.03 | 175.30 | 1286.96 | 0.00 | 0.00 | 0.00 |
February | 645.43 | 193.68 | 451.75 | 313.76 | 1219.89 | 0.00 | 0.00 | 0.00 |
March | 926.17 | 387.87 | 538.29 | 728.56 | 897.11 | 0.00 | 0.00 | 0.00 |
April | 1225.84 | 541.64 | 684.20 | 1153.06 | 665.83 | 0.00 | 0.00 | 0.00 |
May | 1373.38 | 607.52 | 765.86 | 1488.67 | 464.07 | 0.00 | 0.00 | 0.00 |
June | 1533.84 | 677.88 | 855.96 | 1862.64 | 300.39 | 0.00 | 0.00 | 0.00 |
July | 1472.88 | 648.49 | 824.39 | 1922.10 | 207.78 | 0.00 | 0.00 | 0.00 |
August | 1330.18 | 558.34 | 771.84 | 1697.80 | 272.95 | 0.00 | 0.00 | 0.00 |
September | 1106.94 | 491.00 | 615.94 | 1272.91 | 434.82 | 0.00 | 0.00 | 0.00 |
October | 751.15 | 310.70 | 440.45 | 666.24 | 673.76 | 0.00 | 0.00 | 0.00 |
November | 426.07 | 136.68 | 289.39 | 264.48 | 856.71 | 0.00 | 0.00 | 0.00 |
December | 343.00 | 70.87 | 272.13 | 91.62 | 1269.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.99 | 398.17 | 567.82 | 973.30 | 709.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.00 | 70.87 | 272.13 | 91.62 | 207.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1533.84 | 677.88 | 855.96 | 1922.10 | 1286.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1550.36 | 904.99 | 645.37 | 1269.93 | 1824.89 | 0.00 | 0.00 | 0.00 |
February | 1770.13 | 853.54 | 916.59 | 1431.49 | 1792.70 | 0.00 | 0.00 | 0.00 |
March | 2160.56 | 1214.00 | 946.55 | 2136.61 | 1354.21 | 0.00 | 0.00 | 0.00 |
April | 1789.28 | 715.00 | 1074.28 | 1840.19 | 1084.01 | 0.00 | 0.00 | 0.00 |
May | 1565.78 | 454.77 | 1111.01 | 1744.53 | 752.48 | 0.00 | 0.00 | 0.00 |
June | 1521.43 | 322.40 | 1199.03 | 1895.89 | 486.18 | 0.00 | 0.00 | 0.00 |
July | 1553.14 | 376.84 | 1176.30 | 2141.91 | 335.14 | 0.00 | 0.00 | 0.00 |
August | 1743.65 | 565.34 | 1178.32 | 2364.75 | 434.44 | 0.00 | 0.00 | 0.00 |
September | 2027.35 | 987.47 | 1039.88 | 2533.24 | 691.30 | 0.00 | 0.00 | 0.00 |
October | 1939.87 | 1108.09 | 831.78 | 2097.96 | 1030.05 | 0.00 | 0.00 | 0.00 |
November | 1389.30 | 784.30 | 604.99 | 1324.33 | 1274.07 | 0.00 | 0.00 | 0.00 |
December | 1296.41 | 670.95 | 625.46 | 1005.34 | 1797.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1691.75 | 746.08 | 945.67 | 1817.76 | 1067.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1296.41 | 322.40 | 604.99 | 1005.34 | 335.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2160.56 | 1214.00 | 1199.03 | 2533.24 | 1824.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.40 | 88.60 | 288.80 | 108.64 | 1337.52 | 0.00 | 0.00 | 0.00 |
February | 611.66 | 157.20 | 454.46 | 272.83 | 1260.96 | 0.00 | 0.00 | 0.00 |
March | 958.67 | 410.48 | 548.19 | 776.13 | 921.97 | 0.00 | 0.00 | 0.00 |
April | 1173.77 | 481.29 | 692.48 | 1108.56 | 697.14 | 0.00 | 0.00 | 0.00 |
May | 1384.65 | 625.77 | 758.88 | 1517.27 | 492.89 | 0.00 | 0.00 | 0.00 |
June | 1670.62 | 785.79 | 884.83 | 2059.34 | 327.74 | 0.00 | 0.00 | 0.00 |
July | 1493.59 | 654.84 | 838.75 | 1962.77 | 230.52 | 0.00 | 0.00 | 0.00 |
August | 1350.87 | 574.40 | 776.47 | 1746.22 | 292.74 | 0.00 | 0.00 | 0.00 |
September | 1060.85 | 458.14 | 602.72 | 1226.16 | 458.57 | 0.00 | 0.00 | 0.00 |
October | 687.69 | 242.25 | 445.45 | 600.84 | 697.73 | 0.00 | 0.00 | 0.00 |
November | 407.53 | 117.44 | 290.09 | 245.82 | 872.47 | 0.00 | 0.00 | 0.00 |
December | 353.29 | 76.98 | 276.31 | 104.61 | 1291.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 962.47 | 390.56 | 571.91 | 981.22 | 737.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.29 | 76.98 | 276.31 | 104.61 | 230.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1670.62 | 785.79 | 884.83 | 2059.34 | 1337.52 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.965694E+09 | 0.00 | 0.965694E+09 | 18427357.83 | 0.553026E+10 |
February | 0.132897E+10 | 0.00 | 0.132897E+10 | 0.104164E+09 | 0.466543E+10 |
March | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.617608E+09 | 0.372060E+10 |
April | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.123904E+10 | 0.256949E+10 |
May | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.209456E+10 | 0.175317E+10 |
June | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.332404E+10 | 0.110985E+10 |
July | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.367396E+10 | 0.806052E+09 |
August | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.300930E+10 | 0.106283E+10 |
September | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.171253E+10 | 0.166666E+10 |
October | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.751612E+09 | 0.263778E+10 |
November | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.234375E+09 | 0.324647E+10 |
December | 0.903860E+09 | 0.00 | 0.903860E+09 | 20993682.49 | 0.523759E+10 |
Annual Sum or Average | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.168006E+11 | 0.340062E+11 |
Minimum of Months | 0.903860E+09 | 0.00 | 0.903860E+09 | 18427357.83 | 0.806052E+09 |
Maximum of Months | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.367396E+10 | 0.553026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.480519E+09 | 0.335021E+10 |
February | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.777068E+09 | 0.286401E+10 |
March | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.198451E+10 | 0.229256E+10 |
April | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.302533E+10 | 0.164151E+10 |
May | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.400294E+10 | 0.119787E+10 |
June | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.483097E+10 | 0.758595E+09 |
July | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.514504E+10 | 0.545592E+09 |
August | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.455072E+10 | 0.710082E+09 |
September | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.331696E+10 | 0.107615E+10 |
October | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.183195E+10 | 0.167867E+10 |
November | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.717529E+09 | 0.207275E+10 |
December | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.255276E+09 | 0.327981E+10 |
Annual Sum or Average | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.309188E+11 | 0.214678E+11 |
Minimum of Months | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.255276E+09 | 0.545592E+09 |
Maximum of Months | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.514504E+10 | 0.335021E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.342989E+10 | 0.472711E+10 |
February | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.349246E+10 | 0.419510E+10 |
March | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.575877E+10 | 0.345929E+10 |
April | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.480192E+10 | 0.267224E+10 |
May | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.467966E+10 | 0.193592E+10 |
June | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.490281E+10 | 0.122225E+10 |
July | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.571629E+10 | 0.876940E+09 |
August | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.632249E+10 | 0.112821E+10 |
September | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.657422E+10 | 0.171103E+10 |
October | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.567227E+10 | 0.257329E+10 |
November | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.348205E+10 | 0.308693E+10 |
December | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.272509E+10 | 0.462649E+10 |
Annual Sum or Average | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.575579E+11 | 0.322148E+11 |
Minimum of Months | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.272509E+10 | 0.876940E+09 |
Maximum of Months | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.657422E+10 | 0.472711E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.298222E+09 | 0.347942E+10 |
February | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.670770E+09 | 0.295825E+10 |
March | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.209610E+10 | 0.235618E+10 |
April | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.289554E+10 | 0.171427E+10 |
May | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.406911E+10 | 0.126663E+10 |
June | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.532743E+10 | 0.823577E+09 |
July | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.524192E+10 | 0.602456E+09 |
August | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.466967E+10 | 0.760347E+09 |
September | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.318583E+10 | 0.113203E+10 |
October | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.164435E+10 | 0.173609E+10 |
November | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.662050E+09 | 0.211307E+10 |
December | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.288743E+09 | 0.333209E+10 |
Annual Sum or Average | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.310497E+11 | 0.222744E+11 |
Minimum of Months | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.288743E+09 | 0.602456E+09 |
Maximum of Months | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.532743E+10 | 0.347942E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321883E+09 | 0.00 | 0.321883E+09 | 4154659.77 | 0.187290E+10 |
February | 0.442968E+09 | 0.00 | 0.442968E+09 | 33755579.45 | 0.157923E+10 |
March | 0.594751E+09 | 0.00 | 0.594751E+09 | 0.221748E+09 | 0.124419E+10 |
April | 0.733388E+09 | 2926510.60 | 0.730462E+09 | 0.443854E+09 | 0.843678E+09 |
May | 0.880567E+09 | 37341032.44 | 0.843226E+09 | 0.746332E+09 | 0.556055E+09 |
June | 0.102497E+10 | 87250714.54 | 0.937720E+09 | 0.114072E+10 | 0.358166E+09 |
July | 0.982490E+09 | 63421910.74 | 0.919068E+09 | 0.125387E+10 | 0.257919E+09 |
August | 0.850126E+09 | 12932829.72 | 0.837194E+09 | 0.101829E+10 | 0.354647E+09 |
September | 0.626095E+09 | 130075.38 | 0.625965E+09 | 0.574445E+09 | 0.579718E+09 |
October | 0.483634E+09 | 0.00 | 0.483634E+09 | 0.235839E+09 | 0.960489E+09 |
November | 0.314506E+09 | 0.00 | 0.314506E+09 | 69185202.57 | 0.117182E+10 |
December | 0.301273E+09 | 0.00 | 0.301273E+09 | 5215621.17 | 0.181618E+10 |
Annual Sum or Average | 0.755665E+10 | 0.204003E+09 | 0.735265E+10 | 0.574741E+10 | 0.115950E+11 |
Minimum of Months | 0.301273E+09 | 0.00 | 0.301273E+09 | 4154659.77 | 0.257919E+09 |
Maximum of Months | 0.102497E+10 | 87250714.54 | 0.937720E+09 | 0.125387E+10 | 0.187290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321894E+09 | 0.00 | 0.321894E+09 | 4153782.96 | 0.187302E+10 |
February | 0.442984E+09 | 0.00 | 0.442984E+09 | 33752146.80 | 0.157933E+10 |
March | 0.594774E+09 | 0.00 | 0.594774E+09 | 0.221750E+09 | 0.124427E+10 |
April | 0.733417E+09 | 2926589.26 | 0.730491E+09 | 0.443864E+09 | 0.843732E+09 |
May | 0.880602E+09 | 37342036.17 | 0.843260E+09 | 0.746356E+09 | 0.556089E+09 |
June | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.114076E+10 | 0.358187E+09 |
July | 0.982529E+09 | 63423615.54 | 0.919105E+09 | 0.125392E+10 | 0.257933E+09 |
August | 0.850160E+09 | 12933177.36 | 0.837227E+09 | 0.101833E+10 | 0.354667E+09 |
September | 0.626120E+09 | 130078.88 | 0.625990E+09 | 0.574465E+09 | 0.579752E+09 |
October | 0.483652E+09 | 0.00 | 0.483652E+09 | 0.235842E+09 | 0.960549E+09 |
November | 0.314518E+09 | 0.00 | 0.314518E+09 | 69184583.79 | 0.117190E+10 |
December | 0.301283E+09 | 0.00 | 0.301283E+09 | 5214952.43 | 0.181630E+10 |
Annual Sum or Average | 0.755695E+10 | 0.204009E+09 | 0.735294E+10 | 0.574759E+10 | 0.115957E+11 |
Minimum of Months | 0.301283E+09 | 0.00 | 0.301283E+09 | 4153782.96 | 0.257933E+09 |
Maximum of Months | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.125392E+10 | 0.187302E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321894E+09 | 0.00 | 0.321894E+09 | 4153782.96 | 0.187302E+10 |
February | 0.442984E+09 | 0.00 | 0.442984E+09 | 33752146.80 | 0.157933E+10 |
March | 0.594774E+09 | 0.00 | 0.594774E+09 | 0.221750E+09 | 0.124427E+10 |
April | 0.733417E+09 | 2926589.26 | 0.730491E+09 | 0.443864E+09 | 0.843732E+09 |
May | 0.880602E+09 | 37342036.17 | 0.843260E+09 | 0.746356E+09 | 0.556089E+09 |
June | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.114076E+10 | 0.358187E+09 |
July | 0.982529E+09 | 63423615.54 | 0.919105E+09 | 0.125392E+10 | 0.257933E+09 |
August | 0.850160E+09 | 12933177.36 | 0.837227E+09 | 0.101833E+10 | 0.354667E+09 |
September | 0.626120E+09 | 130078.88 | 0.625990E+09 | 0.574465E+09 | 0.579752E+09 |
October | 0.483652E+09 | 0.00 | 0.483652E+09 | 0.235842E+09 | 0.960549E+09 |
November | 0.314518E+09 | 0.00 | 0.314518E+09 | 69184583.79 | 0.117190E+10 |
December | 0.301283E+09 | 0.00 | 0.301283E+09 | 5214952.43 | 0.181630E+10 |
Annual Sum or Average | 0.755695E+10 | 0.204009E+09 | 0.735294E+10 | 0.574759E+10 | 0.115957E+11 |
Minimum of Months | 0.301283E+09 | 0.00 | 0.301283E+09 | 4153782.96 | 0.257933E+09 |
Maximum of Months | 0.102501E+10 | 87253059.87 | 0.937758E+09 | 0.125392E+10 | 0.187302E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113332E+10 | 0.365445E+09 | 0.767877E+09 | 0.462289E+09 | 0.329444E+10 |
February | 0.150200E+10 | 0.450711E+09 | 0.105129E+10 | 0.752552E+09 | 0.281221E+10 |
March | 0.238626E+10 | 0.999346E+09 | 0.138691E+10 | 0.194986E+10 | 0.224283E+10 |
April | 0.305648E+10 | 0.135051E+10 | 0.170597E+10 | 0.295737E+10 | 0.160389E+10 |
May | 0.353850E+10 | 0.156526E+10 | 0.197324E+10 | 0.391807E+10 | 0.113991E+10 |
June | 0.382443E+10 | 0.169020E+10 | 0.213423E+10 | 0.470006E+10 | 0.732861E+09 |
July | 0.379487E+10 | 0.167082E+10 | 0.212405E+10 | 0.499747E+10 | 0.526812E+09 |
August | 0.342718E+10 | 0.143854E+10 | 0.198864E+10 | 0.440679E+10 | 0.707181E+09 |
September | 0.276001E+10 | 0.122423E+10 | 0.153578E+10 | 0.319723E+10 | 0.110519E+10 |
October | 0.193532E+10 | 0.800499E+09 | 0.113482E+10 | 0.172611E+10 | 0.179473E+10 |
November | 0.106234E+10 | 0.340785E+09 | 0.721554E+09 | 0.664474E+09 | 0.218060E+10 |
December | 0.883745E+09 | 0.182600E+09 | 0.701145E+09 | 0.239356E+09 | 0.328773E+10 |
Annual Sum or Average | 0.293044E+11 | 0.120789E+11 | 0.172255E+11 | 0.299716E+11 | 0.214284E+11 |
Minimum of Months | 0.883745E+09 | 0.182600E+09 | 0.701145E+09 | 0.239356E+09 | 0.526812E+09 |
Maximum of Months | 0.382443E+10 | 0.169020E+10 | 0.213423E+10 | 0.499747E+10 | 0.329444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44810523.56 | 14449365.94 | 30361157.62 | 18278492.34 | 0.130259E+09 |
February | 59387722.53 | 17820726.31 | 41566996.22 | 29755246.76 | 0.111192E+09 |
March | 94350443.65 | 39513227.60 | 54837216.06 | 77095843.13 | 88679640.36 |
April | 0.120850E+09 | 53398009.34 | 67452396.70 | 0.116932E+09 | 63416276.13 |
May | 0.139909E+09 | 61888992.73 | 78020017.97 | 0.154917E+09 | 45070835.17 |
June | 0.151214E+09 | 66829025.98 | 84385336.57 | 0.185836E+09 | 28976651.06 |
July | 0.150046E+09 | 66062729.07 | 83982888.72 | 0.197596E+09 | 20829684.86 |
August | 0.135508E+09 | 56878487.95 | 78629175.06 | 0.174240E+09 | 27961306.32 |
September | 0.109128E+09 | 48404925.38 | 60723331.69 | 0.126416E+09 | 43698253.17 |
October | 76520973.79 | 31651024.14 | 44869949.65 | 68248995.08 | 70962125.24 |
November | 42003934.70 | 13474328.15 | 28529606.55 | 26272722.11 | 86218867.83 |
December | 34942489.26 | 7219842.68 | 27722646.58 | 9463936.22 | 0.129994E+09 |
Annual Sum or Average | 0.115867E+10 | 0.477591E+09 | 0.681081E+09 | 0.118505E+10 | 0.847259E+09 |
Minimum of Months | 34942489.26 | 7219842.68 | 27722646.58 | 9463936.22 | 20829684.86 |
Maximum of Months | 0.151214E+09 | 66829025.98 | 84385336.57 | 0.197596E+09 | 0.130259E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138414E+10 | 0.807962E+09 | 0.576178E+09 | 0.116824E+10 | 0.159870E+10 |
February | 0.142741E+10 | 0.688280E+09 | 0.739125E+09 | 0.119515E+10 | 0.141365E+10 |
March | 0.192891E+10 | 0.108384E+10 | 0.845073E+09 | 0.196892E+10 | 0.117949E+10 |
April | 0.154592E+10 | 0.617749E+09 | 0.928168E+09 | 0.164573E+10 | 0.891315E+09 |
May | 0.139791E+10 | 0.406009E+09 | 0.991903E+09 | 0.161347E+10 | 0.620181E+09 |
June | 0.131451E+10 | 0.278547E+09 | 0.103596E+10 | 0.167453E+10 | 0.397584E+09 |
July | 0.138663E+10 | 0.336438E+09 | 0.105019E+10 | 0.193682E+10 | 0.287869E+09 |
August | 0.155671E+10 | 0.504722E+09 | 0.105199E+10 | 0.212789E+10 | 0.387481E+09 |
September | 0.175160E+10 | 0.853156E+09 | 0.898445E+09 | 0.220293E+10 | 0.610274E+09 |
October | 0.173189E+10 | 0.989285E+09 | 0.742603E+09 | 0.189185E+10 | 0.948552E+09 |
November | 0.120033E+10 | 0.677625E+09 | 0.522706E+09 | 0.115781E+10 | 0.112657E+10 |
December | 0.115742E+10 | 0.599014E+09 | 0.558402E+09 | 0.918647E+09 | 0.159493E+10 |
Annual Sum or Average | 0.177834E+11 | 0.784263E+10 | 0.994074E+10 | 0.195020E+11 | 0.110566E+11 |
Minimum of Months | 0.115742E+10 | 0.278547E+09 | 0.522706E+09 | 0.918647E+09 | 0.287869E+09 |
Maximum of Months | 0.192891E+10 | 0.108384E+10 | 0.105199E+10 | 0.220293E+10 | 0.159870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138414E+10 | 0.807962E+09 | 0.576178E+09 | 0.116824E+10 | 0.159870E+10 |
February | 0.142741E+10 | 0.688280E+09 | 0.739125E+09 | 0.119515E+10 | 0.141365E+10 |
March | 0.192891E+10 | 0.108384E+10 | 0.845073E+09 | 0.196892E+10 | 0.117949E+10 |
April | 0.154592E+10 | 0.617749E+09 | 0.928168E+09 | 0.164573E+10 | 0.891315E+09 |
May | 0.139791E+10 | 0.406009E+09 | 0.991903E+09 | 0.161347E+10 | 0.620181E+09 |
June | 0.131451E+10 | 0.278547E+09 | 0.103596E+10 | 0.167453E+10 | 0.397584E+09 |
July | 0.138663E+10 | 0.336438E+09 | 0.105019E+10 | 0.193682E+10 | 0.287869E+09 |
August | 0.155671E+10 | 0.504722E+09 | 0.105199E+10 | 0.212789E+10 | 0.387481E+09 |
September | 0.175160E+10 | 0.853156E+09 | 0.898445E+09 | 0.220293E+10 | 0.610274E+09 |
October | 0.173189E+10 | 0.989285E+09 | 0.742603E+09 | 0.189185E+10 | 0.948552E+09 |
November | 0.120033E+10 | 0.677625E+09 | 0.522706E+09 | 0.115781E+10 | 0.112657E+10 |
December | 0.115742E+10 | 0.599014E+09 | 0.558402E+09 | 0.918647E+09 | 0.159493E+10 |
Annual Sum or Average | 0.177834E+11 | 0.784263E+10 | 0.994074E+10 | 0.195020E+11 | 0.110566E+11 |
Minimum of Months | 0.115742E+10 | 0.278547E+09 | 0.522706E+09 | 0.918647E+09 | 0.287869E+09 |
Maximum of Months | 0.192891E+10 | 0.108384E+10 | 0.105199E+10 | 0.220293E+10 | 0.159870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138405E+10 | 0.807911E+09 | 0.576142E+09 | 0.116817E+10 | 0.159860E+10 |
February | 0.142732E+10 | 0.688237E+09 | 0.739078E+09 | 0.119507E+10 | 0.141356E+10 |
March | 0.192879E+10 | 0.108377E+10 | 0.845020E+09 | 0.196880E+10 | 0.117941E+10 |
April | 0.154582E+10 | 0.617710E+09 | 0.928109E+09 | 0.164562E+10 | 0.891259E+09 |
May | 0.139782E+10 | 0.405983E+09 | 0.991840E+09 | 0.161337E+10 | 0.620142E+09 |
June | 0.131442E+10 | 0.278530E+09 | 0.103589E+10 | 0.167442E+10 | 0.397559E+09 |
July | 0.138654E+10 | 0.336416E+09 | 0.105012E+10 | 0.193670E+10 | 0.287851E+09 |
August | 0.155661E+10 | 0.504690E+09 | 0.105192E+10 | 0.212776E+10 | 0.387456E+09 |
September | 0.175149E+10 | 0.853102E+09 | 0.898389E+09 | 0.220279E+10 | 0.610236E+09 |
October | 0.173178E+10 | 0.989222E+09 | 0.742556E+09 | 0.189173E+10 | 0.948492E+09 |
November | 0.120026E+10 | 0.677582E+09 | 0.522673E+09 | 0.115774E+10 | 0.112650E+10 |
December | 0.115734E+10 | 0.598976E+09 | 0.558367E+09 | 0.918589E+09 | 0.159483E+10 |
Annual Sum or Average | 0.177822E+11 | 0.784213E+10 | 0.994011E+10 | 0.195007E+11 | 0.110559E+11 |
Minimum of Months | 0.115734E+10 | 0.278530E+09 | 0.522673E+09 | 0.918589E+09 | 0.287851E+09 |
Maximum of Months | 0.192879E+10 | 0.108377E+10 | 0.105192E+10 | 0.220279E+10 | 0.159860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972373E+09 | 0.228274E+09 | 0.744099E+09 | 0.290400E+09 | 0.340752E+10 |
February | 0.142344E+10 | 0.365833E+09 | 0.105761E+10 | 0.660578E+09 | 0.289841E+10 |
March | 0.247002E+10 | 0.105760E+10 | 0.141242E+10 | 0.207253E+10 | 0.231098E+10 |
April | 0.292665E+10 | 0.120004E+10 | 0.172661E+10 | 0.284738E+10 | 0.167328E+10 |
May | 0.356753E+10 | 0.161229E+10 | 0.195524E+10 | 0.398809E+10 | 0.121564E+10 |
June | 0.416548E+10 | 0.195927E+10 | 0.220622E+10 | 0.518497E+10 | 0.809029E+09 |
July | 0.384824E+10 | 0.168719E+10 | 0.216104E+10 | 0.509612E+10 | 0.589759E+09 |
August | 0.348050E+10 | 0.147994E+10 | 0.200056E+10 | 0.452267E+10 | 0.764815E+09 |
September | 0.264510E+10 | 0.114230E+10 | 0.150280E+10 | 0.307446E+10 | 0.116620E+10 |
October | 0.177184E+10 | 0.624141E+09 | 0.114770E+10 | 0.155398E+10 | 0.185093E+10 |
November | 0.101613E+10 | 0.292811E+09 | 0.723317E+09 | 0.617482E+09 | 0.221773E+10 |
December | 0.910255E+09 | 0.198334E+09 | 0.711921E+09 | 0.276062E+09 | 0.333490E+10 |
Annual Sum or Average | 0.291976E+11 | 0.118480E+11 | 0.173495E+11 | 0.301847E+11 | 0.222392E+11 |
Minimum of Months | 0.910255E+09 | 0.198334E+09 | 0.711921E+09 | 0.276062E+09 | 0.589759E+09 |
Maximum of Months | 0.416548E+10 | 0.195927E+10 | 0.220622E+10 | 0.518497E+10 | 0.340752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38446651.13 | 9025729.77 | 29420921.35 | 11482089.57 | 0.134730E+09 |
February | 56281302.24 | 14464650.00 | 41816652.25 | 26118495.84 | 0.114601E+09 |
March | 97662032.30 | 41816448.29 | 55845584.00 | 81945573.29 | 91374089.19 |
April | 0.115717E+09 | 47448342.57 | 68268400.37 | 0.112583E+09 | 66160157.71 |
May | 0.141057E+09 | 63748207.56 | 77308383.85 | 0.157685E+09 | 48065109.75 |
June | 0.164699E+09 | 77467326.20 | 87231744.49 | 0.205009E+09 | 31988264.47 |
July | 0.152155E+09 | 66709906.98 | 85445559.96 | 0.201496E+09 | 23318521.84 |
August | 0.137616E+09 | 58515243.79 | 79100356.54 | 0.178822E+09 | 30240083.99 |
September | 0.104585E+09 | 45165419.01 | 59419335.49 | 0.121561E+09 | 46110493.51 |
October | 70056742.45 | 24677899.62 | 45378842.83 | 61442829.27 | 73184035.55 |
November | 40176668.18 | 11577437.89 | 28599230.29 | 24414560.19 | 87687006.65 |
December | 35990571.65 | 7841913.52 | 28148658.13 | 10915179.34 | 0.131859E+09 |
Annual Sum or Average | 0.115444E+10 | 0.468459E+09 | 0.685984E+09 | 0.119347E+10 | 0.879317E+09 |
Minimum of Months | 35990571.65 | 7841913.52 | 28148658.13 | 10915179.34 | 23318521.84 |
Maximum of Months | 0.164699E+09 | 77467326.20 | 87231744.49 | 0.205009E+09 | 0.134730E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.965694E+09 | 0.00 | 0.965694E+09 | 11851230.74 | 0.569333E+10 |
February | 0.132897E+10 | 0.00 | 0.132897E+10 | 90404940.25 | 0.481297E+10 |
March | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.595567E+09 | 0.389207E+10 |
April | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.120263E+10 | 0.270942E+10 |
May | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.207376E+10 | 0.182598E+10 |
June | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.332746E+10 | 0.114014E+10 |
July | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.368948E+10 | 0.821908E+09 |
August | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.301263E+10 | 0.109500E+10 |
September | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.169555E+10 | 0.175392E+10 |
October | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.700540E+09 | 0.284262E+10 |
November | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.205268E+09 | 0.347560E+10 |
December | 0.903860E+09 | 0.00 | 0.903860E+09 | 15282293.26 | 0.543949E+10 |
Annual Sum or Average | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.166204E+11 | 0.355024E+11 |
Minimum of Months | 0.903860E+09 | 0.00 | 0.903860E+09 | 11851230.74 | 0.821908E+09 |
Maximum of Months | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.368948E+10 | 0.569333E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.469513E+09 | 0.344699E+10 |
February | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.759037E+09 | 0.295115E+10 |
March | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.195136E+10 | 0.240282E+10 |
April | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.298872E+10 | 0.172583E+10 |
May | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.398726E+10 | 0.124298E+10 |
June | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.482795E+10 | 0.778617E+09 |
July | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.514815E+10 | 0.556526E+09 |
August | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.454739E+10 | 0.731078E+09 |
September | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.329937E+10 | 0.112707E+10 |
October | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.178446E+10 | 0.180461E+10 |
November | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.685527E+09 | 0.222059E+10 |
December | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.245388E+09 | 0.339901E+10 |
Annual Sum or Average | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.306941E+11 | 0.223873E+11 |
Minimum of Months | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.245388E+09 | 0.556526E+09 |
Maximum of Months | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.514815E+10 | 0.344699E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.340137E+10 | 0.488779E+10 |
February | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.346306E+10 | 0.433690E+10 |
March | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.572268E+10 | 0.362712E+10 |
April | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.476976E+10 | 0.280975E+10 |
May | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.467256E+10 | 0.201543E+10 |
June | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.491416E+10 | 0.126019E+10 |
July | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.573689E+10 | 0.897630E+09 |
August | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.633373E+10 | 0.116359E+10 |
September | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.656616E+10 | 0.179185E+10 |
October | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.561917E+10 | 0.275888E+10 |
November | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.343266E+10 | 0.330240E+10 |
December | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.269269E+10 | 0.481425E+10 |
Annual Sum or Average | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.573249E+11 | 0.336658E+11 |
Minimum of Months | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.269269E+10 | 0.897630E+09 |
Maximum of Months | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.656616E+10 | 0.488779E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.290981E+09 | 0.358241E+10 |
February | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.660022E+09 | 0.305051E+10 |
March | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.207878E+10 | 0.246942E+10 |
April | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.287338E+10 | 0.180698E+10 |
May | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.406387E+10 | 0.132015E+10 |
June | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.533780E+10 | 0.849490E+09 |
July | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.525708E+10 | 0.617412E+09 |
August | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.467707E+10 | 0.784086E+09 |
September | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.317821E+10 | 0.118862E+10 |
October | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.160930E+10 | 0.186879E+10 |
November | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.637161E+09 | 0.226145E+10 |
December | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.280185E+09 | 0.345835E+10 |
Annual Sum or Average | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.309438E+11 | 0.232577E+11 |
Minimum of Months | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.280185E+09 | 0.617412E+09 |
Maximum of Months | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.533780E+10 | 0.358241E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.88 | 2064.76 | 360.55 | 0.00 | 360.55 | 0.00 | 0.00 |
February | 43.06 | 1928.50 | 549.34 | 0.00 | 549.34 | 0.00 | 0.00 |
March | 230.59 | 1389.11 | 666.20 | 0.00 | 666.20 | 0.00 | 0.00 |
April | 478.02 | 991.32 | 848.87 | 3.39 | 845.48 | 0.00 | 0.00 |
May | 782.02 | 654.56 | 986.34 | 41.83 | 944.52 | 0.00 | 0.00 |
June | 1282.42 | 428.18 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
July | 1371.70 | 300.95 | 1100.51 | 71.04 | 1029.47 | 0.00 | 0.00 |
August | 1123.54 | 396.82 | 952.25 | 14.49 | 937.76 | 0.00 | 0.00 |
September | 660.70 | 643.00 | 724.68 | 0.15 | 724.53 | 0.00 | 0.00 |
October | 280.62 | 984.83 | 541.73 | 0.00 | 541.73 | 0.00 | 0.00 |
November | 90.42 | 1252.49 | 364.03 | 0.00 | 364.03 | 0.00 | 0.00 |
December | 7.84 | 1955.49 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Annual Sum or Average | 532.74 | 1078.33 | 718.89 | 19.41 | 699.49 | 0.00 | 0.00 |
Minimum of Months | 6.88 | 300.95 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Maximum of Months | 1371.70 | 2064.76 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.41 | 1250.83 | 439.87 | 141.84 | 298.03 | 0.00 | 0.00 |
February | 321.21 | 1183.86 | 645.43 | 193.68 | 451.75 | 0.00 | 0.00 |
March | 740.93 | 855.94 | 926.17 | 387.87 | 538.29 | 0.00 | 0.00 |
April | 1167.18 | 633.30 | 1225.84 | 541.64 | 684.20 | 0.00 | 0.00 |
May | 1494.53 | 447.23 | 1373.38 | 607.52 | 765.86 | 0.00 | 0.00 |
June | 1863.80 | 292.67 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
July | 1920.94 | 203.70 | 1472.88 | 648.49 | 824.39 | 0.00 | 0.00 |
August | 1699.04 | 265.11 | 1330.18 | 558.34 | 771.84 | 0.00 | 0.00 |
September | 1279.69 | 415.18 | 1106.94 | 491.00 | 615.94 | 0.00 | 0.00 |
October | 683.97 | 626.74 | 751.15 | 310.70 | 440.45 | 0.00 | 0.00 |
November | 276.82 | 799.67 | 426.07 | 136.68 | 289.39 | 0.00 | 0.00 |
December | 95.31 | 1224.54 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Annual Sum or Average | 980.43 | 680.74 | 965.99 | 398.17 | 567.82 | 0.00 | 0.00 |
Minimum of Months | 95.31 | 203.70 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Maximum of Months | 1920.94 | 1250.83 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1280.57 | 1764.90 | 1550.36 | 904.99 | 645.37 | 0.00 | 0.00 |
February | 1443.64 | 1734.08 | 1770.13 | 853.54 | 916.59 | 0.00 | 0.00 |
March | 2150.08 | 1291.55 | 2160.56 | 1214.00 | 946.55 | 0.00 | 0.00 |
April | 1852.59 | 1030.96 | 1789.28 | 715.00 | 1074.28 | 0.00 | 0.00 |
May | 1747.18 | 722.79 | 1565.78 | 454.77 | 1111.01 | 0.00 | 0.00 |
June | 1891.52 | 471.55 | 1521.43 | 322.40 | 1199.03 | 0.00 | 0.00 |
July | 2134.22 | 327.41 | 1553.14 | 376.84 | 1176.30 | 0.00 | 0.00 |
August | 2360.55 | 421.22 | 1743.65 | 565.34 | 1178.32 | 0.00 | 0.00 |
September | 2536.35 | 660.12 | 2027.35 | 987.47 | 1039.88 | 0.00 | 0.00 |
October | 2117.78 | 960.76 | 1939.87 | 1108.09 | 831.78 | 0.00 | 0.00 |
November | 1343.38 | 1190.94 | 1389.30 | 784.30 | 604.99 | 0.00 | 0.00 |
December | 1017.43 | 1727.33 | 1296.41 | 670.95 | 625.46 | 0.00 | 0.00 |
Annual Sum or Average | 1825.15 | 1021.52 | 1691.75 | 746.08 | 945.67 | 0.00 | 0.00 |
Minimum of Months | 1017.43 | 327.41 | 1296.41 | 322.40 | 604.99 | 0.00 | 0.00 |
Maximum of Months | 2536.35 | 1764.90 | 2160.56 | 1214.00 | 1199.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 111.34 | 1299.07 | 377.40 | 88.60 | 288.80 | 0.00 | 0.00 |
February | 277.27 | 1222.82 | 611.66 | 157.20 | 454.46 | 0.00 | 0.00 |
March | 782.60 | 879.70 | 958.67 | 410.48 | 548.19 | 0.00 | 0.00 |
April | 1117.11 | 661.37 | 1173.77 | 481.29 | 692.48 | 0.00 | 0.00 |
May | 1519.23 | 472.91 | 1384.65 | 625.77 | 758.88 | 0.00 | 0.00 |
June | 2055.34 | 317.74 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
July | 1957.11 | 224.93 | 1493.59 | 654.84 | 838.75 | 0.00 | 0.00 |
August | 1743.45 | 283.88 | 1350.87 | 574.40 | 776.47 | 0.00 | 0.00 |
September | 1229.10 | 436.74 | 1060.85 | 458.14 | 602.72 | 0.00 | 0.00 |
October | 613.93 | 648.18 | 687.69 | 242.25 | 445.45 | 0.00 | 0.00 |
November | 255.42 | 815.23 | 407.53 | 117.44 | 290.09 | 0.00 | 0.00 |
December | 107.80 | 1244.06 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Annual Sum or Average | 984.58 | 706.32 | 962.47 | 390.56 | 571.91 | 0.00 | 0.00 |
Minimum of Months | 107.80 | 224.93 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Maximum of Months | 2055.34 | 1299.07 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.65 | 2097.87 | 360.54 | 0.00 | 360.54 | 0.00 | 0.00 |
February | 41.86 | 1958.46 | 549.33 | 0.00 | 549.33 | 0.00 | 0.00 |
March | 248.38 | 1393.64 | 666.18 | 0.00 | 666.18 | 0.00 | 0.00 |
April | 513.73 | 976.52 | 848.85 | 3.39 | 845.46 | 0.00 | 0.00 |
May | 835.96 | 622.85 | 986.32 | 41.83 | 944.50 | 0.00 | 0.00 |
June | 1320.31 | 414.56 | 1186.34 | 100.99 | 1085.35 | 0.00 | 0.00 |
July | 1404.46 | 288.90 | 1100.49 | 71.04 | 1029.45 | 0.00 | 0.00 |
August | 1140.59 | 397.24 | 952.23 | 14.49 | 937.74 | 0.00 | 0.00 |
September | 664.88 | 671.00 | 724.67 | 0.15 | 724.52 | 0.00 | 0.00 |
October | 264.16 | 1075.86 | 541.72 | 0.00 | 541.72 | 0.00 | 0.00 |
November | 80.07 | 1356.33 | 364.02 | 0.00 | 364.02 | 0.00 | 0.00 |
December | 5.84 | 2034.35 | 337.45 | 0.00 | 337.45 | 0.00 | 0.00 |
Annual Sum or Average | 546.76 | 1103.07 | 718.88 | 19.41 | 699.47 | 0.00 | 0.00 |
Minimum of Months | 4.65 | 288.90 | 337.45 | 0.00 | 337.45 | 0.00 | 0.00 |
Maximum of Months | 1404.46 | 2097.87 | 1186.34 | 100.99 | 1085.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.42 | 1278.64 | 439.86 | 141.84 | 298.03 | 0.00 | 0.00 |
February | 323.37 | 1208.42 | 645.41 | 193.67 | 451.74 | 0.00 | 0.00 |
March | 756.78 | 870.49 | 926.15 | 387.87 | 538.29 | 0.00 | 0.00 |
April | 1186.07 | 643.25 | 1225.82 | 541.63 | 684.19 | 0.00 | 0.00 |
May | 1520.68 | 442.42 | 1373.36 | 607.51 | 765.85 | 0.00 | 0.00 |
June | 1884.99 | 293.92 | 1533.81 | 677.87 | 855.95 | 0.00 | 0.00 |
July | 1939.62 | 204.47 | 1472.86 | 648.48 | 824.38 | 0.00 | 0.00 |
August | 1710.36 | 274.47 | 1330.16 | 558.32 | 771.83 | 0.00 | 0.00 |
September | 1282.27 | 443.24 | 1106.92 | 490.99 | 615.93 | 0.00 | 0.00 |
October | 669.94 | 696.57 | 751.14 | 310.69 | 440.45 | 0.00 | 0.00 |
November | 266.49 | 874.54 | 426.06 | 136.67 | 289.38 | 0.00 | 0.00 |
December | 92.90 | 1276.03 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Annual Sum or Average | 987.97 | 706.36 | 965.98 | 398.17 | 567.81 | 0.00 | 0.00 |
Minimum of Months | 92.90 | 204.47 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Maximum of Months | 1939.62 | 1278.64 | 1533.81 | 677.87 | 855.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1308.49 | 1790.63 | 1550.30 | 904.96 | 645.35 | 0.00 | 0.00 |
February | 1482.04 | 1753.00 | 1770.06 | 853.50 | 916.55 | 0.00 | 0.00 |
March | 2205.29 | 1321.08 | 2160.48 | 1213.95 | 946.52 | 0.00 | 0.00 |
April | 1904.74 | 1031.59 | 1789.22 | 714.97 | 1074.25 | 0.00 | 0.00 |
May | 1807.17 | 694.63 | 1565.73 | 454.75 | 1110.98 | 0.00 | 0.00 |
June | 1938.07 | 460.16 | 1521.39 | 322.39 | 1199.00 | 0.00 | 0.00 |
July | 2169.34 | 322.43 | 1553.09 | 376.83 | 1176.26 | 0.00 | 0.00 |
August | 2383.34 | 434.00 | 1743.59 | 565.31 | 1178.28 | 0.00 | 0.00 |
September | 2549.63 | 706.32 | 2027.27 | 987.43 | 1039.85 | 0.00 | 0.00 |
October | 2118.96 | 1062.42 | 1939.80 | 1108.05 | 831.75 | 0.00 | 0.00 |
November | 1340.03 | 1303.87 | 1389.24 | 784.27 | 604.97 | 0.00 | 0.00 |
December | 1028.93 | 1786.40 | 1296.36 | 670.92 | 625.44 | 0.00 | 0.00 |
Annual Sum or Average | 1855.17 | 1051.78 | 1691.68 | 746.05 | 945.64 | 0.00 | 0.00 |
Minimum of Months | 1028.93 | 322.43 | 1296.36 | 322.39 | 604.97 | 0.00 | 0.00 |
Maximum of Months | 2549.63 | 1790.63 | 2160.48 | 1213.95 | 1199.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 112.71 | 1322.52 | 377.40 | 88.60 | 288.80 | 0.00 | 0.00 |
February | 283.85 | 1245.46 | 611.66 | 157.20 | 454.46 | 0.00 | 0.00 |
March | 804.39 | 896.94 | 958.66 | 410.48 | 548.19 | 0.00 | 0.00 |
April | 1141.96 | 671.08 | 1173.75 | 481.28 | 692.47 | 0.00 | 0.00 |
May | 1547.86 | 471.81 | 1384.63 | 625.76 | 758.87 | 0.00 | 0.00 |
June | 2079.47 | 324.47 | 1670.60 | 785.78 | 884.82 | 0.00 | 0.00 |
July | 1977.90 | 228.90 | 1493.58 | 654.83 | 838.74 | 0.00 | 0.00 |
August | 1755.34 | 296.84 | 1350.85 | 574.39 | 776.46 | 0.00 | 0.00 |
September | 1233.03 | 467.71 | 1060.84 | 458.13 | 602.71 | 0.00 | 0.00 |
October | 603.13 | 718.38 | 687.69 | 242.24 | 445.44 | 0.00 | 0.00 |
November | 247.65 | 889.44 | 407.52 | 117.43 | 290.09 | 0.00 | 0.00 |
December | 107.15 | 1294.34 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Annual Sum or Average | 995.00 | 733.08 | 962.46 | 390.55 | 571.90 | 0.00 | 0.00 |
Minimum of Months | 107.15 | 228.90 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Maximum of Months | 2079.47 | 1322.52 | 1670.60 | 785.78 | 884.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.42 | 2125.64 | 360.55 | 0.00 | 360.55 | 0.00 | 0.00 |
February | 37.37 | 1989.49 | 549.34 | 0.00 | 549.34 | 0.00 | 0.00 |
March | 222.36 | 1453.13 | 666.20 | 0.00 | 666.20 | 0.00 | 0.00 |
April | 463.98 | 1045.30 | 848.87 | 3.39 | 845.48 | 0.00 | 0.00 |
May | 774.25 | 681.74 | 986.34 | 41.83 | 944.52 | 0.00 | 0.00 |
June | 1283.74 | 439.87 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
July | 1377.49 | 306.87 | 1100.51 | 71.04 | 1029.47 | 0.00 | 0.00 |
August | 1124.79 | 408.83 | 952.25 | 14.49 | 937.76 | 0.00 | 0.00 |
September | 654.15 | 676.67 | 724.68 | 0.15 | 724.53 | 0.00 | 0.00 |
October | 261.55 | 1061.31 | 541.73 | 0.00 | 541.73 | 0.00 | 0.00 |
November | 79.19 | 1340.89 | 364.03 | 0.00 | 364.03 | 0.00 | 0.00 |
December | 5.71 | 2030.87 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Annual Sum or Average | 527.03 | 1125.77 | 718.89 | 19.41 | 699.49 | 0.00 | 0.00 |
Minimum of Months | 4.42 | 306.87 | 337.46 | 0.00 | 337.46 | 0.00 | 0.00 |
Maximum of Months | 1377.49 | 2125.64 | 1186.36 | 100.99 | 1085.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.30 | 1286.96 | 439.87 | 141.84 | 298.03 | 0.00 | 0.00 |
February | 313.76 | 1219.89 | 645.43 | 193.68 | 451.75 | 0.00 | 0.00 |
March | 728.56 | 897.11 | 926.17 | 387.87 | 538.29 | 0.00 | 0.00 |
April | 1153.06 | 665.83 | 1225.84 | 541.64 | 684.20 | 0.00 | 0.00 |
May | 1488.67 | 464.07 | 1373.38 | 607.52 | 765.86 | 0.00 | 0.00 |
June | 1862.64 | 300.39 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
July | 1922.10 | 207.78 | 1472.88 | 648.49 | 824.39 | 0.00 | 0.00 |
August | 1697.80 | 272.95 | 1330.18 | 558.34 | 771.84 | 0.00 | 0.00 |
September | 1272.91 | 434.82 | 1106.94 | 491.00 | 615.94 | 0.00 | 0.00 |
October | 666.24 | 673.76 | 751.15 | 310.70 | 440.45 | 0.00 | 0.00 |
November | 264.48 | 856.71 | 426.07 | 136.68 | 289.39 | 0.00 | 0.00 |
December | 91.62 | 1269.05 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Annual Sum or Average | 973.30 | 709.90 | 965.99 | 398.17 | 567.82 | 0.00 | 0.00 |
Minimum of Months | 91.62 | 207.78 | 343.00 | 70.87 | 272.13 | 0.00 | 0.00 |
Maximum of Months | 1922.10 | 1286.96 | 1533.84 | 677.88 | 855.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1269.93 | 1824.89 | 1550.36 | 904.99 | 645.37 | 0.00 | 0.00 |
February | 1431.49 | 1792.70 | 1770.13 | 853.54 | 916.59 | 0.00 | 0.00 |
March | 2136.61 | 1354.21 | 2160.56 | 1214.00 | 946.55 | 0.00 | 0.00 |
April | 1840.19 | 1084.01 | 1789.28 | 715.00 | 1074.28 | 0.00 | 0.00 |
May | 1744.53 | 752.48 | 1565.78 | 454.77 | 1111.01 | 0.00 | 0.00 |
June | 1895.89 | 486.18 | 1521.43 | 322.40 | 1199.03 | 0.00 | 0.00 |
July | 2141.91 | 335.14 | 1553.14 | 376.84 | 1176.30 | 0.00 | 0.00 |
August | 2364.75 | 434.44 | 1743.65 | 565.34 | 1178.32 | 0.00 | 0.00 |
September | 2533.24 | 691.30 | 2027.35 | 987.47 | 1039.88 | 0.00 | 0.00 |
October | 2097.96 | 1030.05 | 1939.87 | 1108.09 | 831.78 | 0.00 | 0.00 |
November | 1324.33 | 1274.07 | 1389.30 | 784.30 | 604.99 | 0.00 | 0.00 |
December | 1005.34 | 1797.43 | 1296.41 | 670.95 | 625.46 | 0.00 | 0.00 |
Annual Sum or Average | 1817.76 | 1067.53 | 1691.75 | 746.08 | 945.67 | 0.00 | 0.00 |
Minimum of Months | 1005.34 | 335.14 | 1296.41 | 322.40 | 604.99 | 0.00 | 0.00 |
Maximum of Months | 2533.24 | 1824.89 | 2160.56 | 1214.00 | 1199.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 108.64 | 1337.52 | 377.40 | 88.60 | 288.80 | 0.00 | 0.00 |
February | 272.83 | 1260.96 | 611.66 | 157.20 | 454.46 | 0.00 | 0.00 |
March | 776.13 | 921.97 | 958.67 | 410.48 | 548.19 | 0.00 | 0.00 |
April | 1108.56 | 697.14 | 1173.77 | 481.29 | 692.48 | 0.00 | 0.00 |
May | 1517.27 | 492.89 | 1384.65 | 625.77 | 758.88 | 0.00 | 0.00 |
June | 2059.34 | 327.74 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
July | 1962.77 | 230.52 | 1493.59 | 654.84 | 838.75 | 0.00 | 0.00 |
August | 1746.22 | 292.74 | 1350.87 | 574.40 | 776.47 | 0.00 | 0.00 |
September | 1226.16 | 458.57 | 1060.85 | 458.14 | 602.72 | 0.00 | 0.00 |
October | 600.84 | 697.73 | 687.69 | 242.25 | 445.45 | 0.00 | 0.00 |
November | 245.82 | 872.47 | 407.53 | 117.44 | 290.09 | 0.00 | 0.00 |
December | 104.61 | 1291.20 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Annual Sum or Average | 981.22 | 737.50 | 962.47 | 390.56 | 571.91 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 230.52 | 353.29 | 76.98 | 276.31 | 0.00 | 0.00 |
Maximum of Months | 2059.34 | 1337.52 | 1670.62 | 785.79 | 884.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18427357.83 | 0.553026E+10 | 0.965694E+09 | 0.00 | 0.965694E+09 | 0.00 | 0.00 |
February | 0.104164E+09 | 0.466543E+10 | 0.132897E+10 | 0.00 | 0.132897E+10 | 0.00 | 0.00 |
March | 0.617608E+09 | 0.372060E+10 | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.00 | 0.00 |
April | 0.123904E+10 | 0.256949E+10 | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.00 | 0.00 |
May | 0.209456E+10 | 0.175317E+10 | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.00 | 0.00 |
June | 0.332404E+10 | 0.110985E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
July | 0.367396E+10 | 0.806052E+09 | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.00 | 0.00 |
August | 0.300930E+10 | 0.106283E+10 | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.00 | 0.00 |
September | 0.171253E+10 | 0.166666E+10 | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.00 | 0.00 |
October | 0.751612E+09 | 0.263778E+10 | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.00 | 0.00 |
November | 0.234375E+09 | 0.324647E+10 | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.00 | 0.00 |
December | 20993682.49 | 0.523759E+10 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168006E+11 | 0.340062E+11 | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.00 | 0.00 |
Minimum of Months | 18427357.83 | 0.806052E+09 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367396E+10 | 0.553026E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480519E+09 | 0.335021E+10 | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.00 | 0.00 |
February | 0.777068E+09 | 0.286401E+10 | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.00 | 0.00 |
March | 0.198451E+10 | 0.229256E+10 | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.00 | 0.00 |
April | 0.302533E+10 | 0.164151E+10 | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.00 | 0.00 |
May | 0.400294E+10 | 0.119787E+10 | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.00 | 0.00 |
June | 0.483097E+10 | 0.758595E+09 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
July | 0.514504E+10 | 0.545592E+09 | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.00 | 0.00 |
August | 0.455072E+10 | 0.710082E+09 | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.00 | 0.00 |
September | 0.331696E+10 | 0.107615E+10 | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.00 | 0.00 |
October | 0.183195E+10 | 0.167867E+10 | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.00 | 0.00 |
November | 0.717529E+09 | 0.207275E+10 | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.00 | 0.00 |
December | 0.255276E+09 | 0.327981E+10 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309188E+11 | 0.214678E+11 | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.00 | 0.00 |
Minimum of Months | 0.255276E+09 | 0.545592E+09 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514504E+10 | 0.335021E+10 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.342989E+10 | 0.472711E+10 | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.00 | 0.00 |
February | 0.349246E+10 | 0.419510E+10 | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.00 | 0.00 |
March | 0.575877E+10 | 0.345929E+10 | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.00 | 0.00 |
April | 0.480192E+10 | 0.267224E+10 | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.00 | 0.00 |
May | 0.467966E+10 | 0.193592E+10 | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.00 | 0.00 |
June | 0.490281E+10 | 0.122225E+10 | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.00 | 0.00 |
July | 0.571629E+10 | 0.876940E+09 | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.00 | 0.00 |
August | 0.632249E+10 | 0.112821E+10 | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.00 | 0.00 |
September | 0.657422E+10 | 0.171103E+10 | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.00 | 0.00 |
October | 0.567227E+10 | 0.257329E+10 | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.00 | 0.00 |
November | 0.348205E+10 | 0.308693E+10 | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.00 | 0.00 |
December | 0.272509E+10 | 0.462649E+10 | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.575579E+11 | 0.322148E+11 | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.00 | 0.00 |
Minimum of Months | 0.272509E+10 | 0.876940E+09 | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657422E+10 | 0.472711E+10 | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298222E+09 | 0.347942E+10 | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.00 | 0.00 |
February | 0.670770E+09 | 0.295825E+10 | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.00 | 0.00 |
March | 0.209610E+10 | 0.235618E+10 | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.00 | 0.00 |
April | 0.289554E+10 | 0.171427E+10 | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.00 | 0.00 |
May | 0.406911E+10 | 0.126663E+10 | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.00 | 0.00 |
June | 0.532743E+10 | 0.823577E+09 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
July | 0.524192E+10 | 0.602456E+09 | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.00 | 0.00 |
August | 0.466967E+10 | 0.760347E+09 | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.00 | 0.00 |
September | 0.318583E+10 | 0.113203E+10 | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.00 | 0.00 |
October | 0.164435E+10 | 0.173609E+10 | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.00 | 0.00 |
November | 0.662050E+09 | 0.211307E+10 | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.00 | 0.00 |
December | 0.288743E+09 | 0.333209E+10 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.310497E+11 | 0.222744E+11 | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288743E+09 | 0.602456E+09 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.532743E+10 | 0.347942E+10 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12462225.70 | 0.561895E+10 | 0.965672E+09 | 0.00 | 0.965672E+09 | 0.00 | 0.00 |
February | 0.101260E+09 | 0.473790E+10 | 0.132894E+10 | 0.00 | 0.132894E+10 | 0.00 | 0.00 |
March | 0.665248E+09 | 0.373272E+10 | 0.178430E+10 | 0.00 | 0.178430E+10 | 0.00 | 0.00 |
April | 0.133158E+10 | 0.253114E+10 | 0.220022E+10 | 8779689.12 | 0.219144E+10 | 0.00 | 0.00 |
May | 0.223904E+10 | 0.166823E+10 | 0.264177E+10 | 0.112025E+09 | 0.252975E+10 | 0.00 | 0.00 |
June | 0.342224E+10 | 0.107454E+10 | 0.307499E+10 | 0.261757E+09 | 0.281324E+10 | 0.00 | 0.00 |
July | 0.376170E+10 | 0.773786E+09 | 0.294755E+10 | 0.190269E+09 | 0.275728E+10 | 0.00 | 0.00 |
August | 0.305496E+10 | 0.106398E+10 | 0.255045E+10 | 38799184.43 | 0.251165E+10 | 0.00 | 0.00 |
September | 0.172337E+10 | 0.173922E+10 | 0.187833E+10 | 390233.14 | 0.187794E+10 | 0.00 | 0.00 |
October | 0.707522E+09 | 0.288159E+10 | 0.145094E+10 | 0.00 | 0.145094E+10 | 0.00 | 0.00 |
November | 0.207554E+09 | 0.351561E+10 | 0.943542E+09 | 0.00 | 0.943542E+09 | 0.00 | 0.00 |
December | 15645526.03 | 0.544879E+10 | 0.903839E+09 | 0.00 | 0.903839E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172426E+11 | 0.347865E+11 | 0.226705E+11 | 0.612020E+09 | 0.220585E+11 | 0.00 | 0.00 |
Minimum of Months | 12462225.70 | 0.773786E+09 | 0.903839E+09 | 0.00 | 0.903839E+09 | 0.00 | 0.00 |
Maximum of Months | 0.376170E+10 | 0.561895E+10 | 0.307499E+10 | 0.261757E+09 | 0.281324E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480568E+09 | 0.342470E+10 | 0.117813E+10 | 0.379894E+09 | 0.798238E+09 | 0.00 | 0.00 |
February | 0.782308E+09 | 0.292341E+10 | 0.156139E+10 | 0.468532E+09 | 0.109286E+10 | 0.00 | 0.00 |
March | 0.202696E+10 | 0.233151E+10 | 0.248061E+10 | 0.103886E+10 | 0.144175E+10 | 0.00 | 0.00 |
April | 0.307430E+10 | 0.166730E+10 | 0.317733E+10 | 0.140391E+10 | 0.177342E+10 | 0.00 | 0.00 |
May | 0.407299E+10 | 0.118498E+10 | 0.367841E+10 | 0.162715E+10 | 0.205126E+10 | 0.00 | 0.00 |
June | 0.488590E+10 | 0.761837E+09 | 0.397564E+10 | 0.175703E+10 | 0.221861E+10 | 0.00 | 0.00 |
July | 0.519507E+10 | 0.547642E+09 | 0.394491E+10 | 0.173688E+10 | 0.220803E+10 | 0.00 | 0.00 |
August | 0.458103E+10 | 0.735142E+09 | 0.356269E+10 | 0.149542E+10 | 0.206727E+10 | 0.00 | 0.00 |
September | 0.332365E+10 | 0.114889E+10 | 0.286914E+10 | 0.127263E+10 | 0.159650E+10 | 0.00 | 0.00 |
October | 0.179436E+10 | 0.186570E+10 | 0.201185E+10 | 0.832150E+09 | 0.117969E+10 | 0.00 | 0.00 |
November | 0.690747E+09 | 0.226682E+10 | 0.110434E+10 | 0.354259E+09 | 0.750084E+09 | 0.00 | 0.00 |
December | 0.248820E+09 | 0.341772E+10 | 0.918688E+09 | 0.189820E+09 | 0.728868E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311567E+11 | 0.222756E+11 | 0.304631E+11 | 0.125565E+11 | 0.179066E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248820E+09 | 0.547642E+09 | 0.918688E+09 | 0.189820E+09 | 0.728868E+09 | 0.00 | 0.00 |
Maximum of Months | 0.519507E+10 | 0.342470E+10 | 0.397564E+10 | 0.175703E+10 | 0.221861E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350465E+10 | 0.479601E+10 | 0.415233E+10 | 0.242383E+10 | 0.172850E+10 | 0.00 | 0.00 |
February | 0.358536E+10 | 0.424086E+10 | 0.428213E+10 | 0.206480E+10 | 0.221733E+10 | 0.00 | 0.00 |
March | 0.590665E+10 | 0.353839E+10 | 0.578662E+10 | 0.325145E+10 | 0.253517E+10 | 0.00 | 0.00 |
April | 0.493708E+10 | 0.267389E+10 | 0.463765E+10 | 0.185321E+10 | 0.278444E+10 | 0.00 | 0.00 |
May | 0.484032E+10 | 0.186050E+10 | 0.419365E+10 | 0.121800E+10 | 0.297565E+10 | 0.00 | 0.00 |
June | 0.502348E+10 | 0.119273E+10 | 0.394343E+10 | 0.835625E+09 | 0.310781E+10 | 0.00 | 0.00 |
July | 0.581035E+10 | 0.863589E+09 | 0.415979E+10 | 0.100929E+10 | 0.315050E+10 | 0.00 | 0.00 |
August | 0.638354E+10 | 0.116242E+10 | 0.467004E+10 | 0.151413E+10 | 0.315590E+10 | 0.00 | 0.00 |
September | 0.660864E+10 | 0.183078E+10 | 0.525469E+10 | 0.255941E+10 | 0.269528E+10 | 0.00 | 0.00 |
October | 0.567542E+10 | 0.284560E+10 | 0.519555E+10 | 0.296779E+10 | 0.222776E+10 | 0.00 | 0.00 |
November | 0.347335E+10 | 0.337964E+10 | 0.360092E+10 | 0.203283E+10 | 0.156808E+10 | 0.00 | 0.00 |
December | 0.275588E+10 | 0.478468E+10 | 0.347217E+10 | 0.179700E+10 | 0.167517E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.585047E+11 | 0.331691E+11 | 0.533490E+11 | 0.235274E+11 | 0.298216E+11 | 0.00 | 0.00 |
Minimum of Months | 0.275588E+10 | 0.863589E+09 | 0.347217E+10 | 0.835625E+09 | 0.156808E+10 | 0.00 | 0.00 |
Maximum of Months | 0.660864E+10 | 0.479601E+10 | 0.578662E+10 | 0.325145E+10 | 0.315590E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.301882E+09 | 0.354225E+10 | 0.101082E+10 | 0.237300E+09 | 0.773520E+09 | 0.00 | 0.00 |
February | 0.686696E+09 | 0.301301E+10 | 0.147972E+10 | 0.380297E+09 | 0.109942E+10 | 0.00 | 0.00 |
March | 0.215447E+10 | 0.240235E+10 | 0.256768E+10 | 0.109942E+10 | 0.146826E+10 | 0.00 | 0.00 |
April | 0.295996E+10 | 0.173944E+10 | 0.304237E+10 | 0.124749E+10 | 0.179488E+10 | 0.00 | 0.00 |
May | 0.414578E+10 | 0.126370E+10 | 0.370859E+10 | 0.167604E+10 | 0.203255E+10 | 0.00 | 0.00 |
June | 0.538998E+10 | 0.841017E+09 | 0.433018E+10 | 0.203673E+10 | 0.229345E+10 | 0.00 | 0.00 |
July | 0.529762E+10 | 0.613077E+09 | 0.400039E+10 | 0.175390E+10 | 0.224649E+10 | 0.00 | 0.00 |
August | 0.470149E+10 | 0.795055E+09 | 0.361812E+10 | 0.153845E+10 | 0.207967E+10 | 0.00 | 0.00 |
September | 0.319602E+10 | 0.121231E+10 | 0.274969E+10 | 0.118747E+10 | 0.156222E+10 | 0.00 | 0.00 |
October | 0.161543E+10 | 0.192411E+10 | 0.184190E+10 | 0.648819E+09 | 0.119308E+10 | 0.00 | 0.00 |
November | 0.641896E+09 | 0.230542E+10 | 0.105630E+10 | 0.304388E+09 | 0.751916E+09 | 0.00 | 0.00 |
December | 0.286977E+09 | 0.346676E+10 | 0.946246E+09 | 0.206176E+09 | 0.740070E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.313782E+11 | 0.231185E+11 | 0.303520E+11 | 0.123165E+11 | 0.180355E+11 | 0.00 | 0.00 |
Minimum of Months | 0.286977E+09 | 0.613077E+09 | 0.946246E+09 | 0.206176E+09 | 0.740070E+09 | 0.00 | 0.00 |
Maximum of Months | 0.538998E+10 | 0.354225E+10 | 0.433018E+10 | 0.203673E+10 | 0.229345E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11851230.74 | 0.569333E+10 | 0.965694E+09 | 0.00 | 0.965694E+09 | 0.00 | 0.00 |
February | 90404940.25 | 0.481297E+10 | 0.132897E+10 | 0.00 | 0.132897E+10 | 0.00 | 0.00 |
March | 0.595567E+09 | 0.389207E+10 | 0.178434E+10 | 0.00 | 0.178434E+10 | 0.00 | 0.00 |
April | 0.120263E+10 | 0.270942E+10 | 0.220027E+10 | 8779947.19 | 0.219149E+10 | 0.00 | 0.00 |
May | 0.207376E+10 | 0.182598E+10 | 0.264182E+10 | 0.112028E+09 | 0.252980E+10 | 0.00 | 0.00 |
June | 0.332746E+10 | 0.114014E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
July | 0.368948E+10 | 0.821908E+09 | 0.294761E+10 | 0.190275E+09 | 0.275733E+10 | 0.00 | 0.00 |
August | 0.301263E+10 | 0.109500E+10 | 0.255050E+10 | 38800324.88 | 0.251170E+10 | 0.00 | 0.00 |
September | 0.169555E+10 | 0.175392E+10 | 0.187837E+10 | 390244.61 | 0.187798E+10 | 0.00 | 0.00 |
October | 0.700540E+09 | 0.284262E+10 | 0.145097E+10 | 0.00 | 0.145097E+10 | 0.00 | 0.00 |
November | 0.205268E+09 | 0.347560E+10 | 0.943564E+09 | 0.00 | 0.943564E+09 | 0.00 | 0.00 |
December | 15282293.26 | 0.543949E+10 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166204E+11 | 0.355024E+11 | 0.226710E+11 | 0.612038E+09 | 0.220590E+11 | 0.00 | 0.00 |
Minimum of Months | 11851230.74 | 0.821908E+09 | 0.903860E+09 | 0.00 | 0.903860E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368948E+10 | 0.569333E+10 | 0.307506E+10 | 0.261765E+09 | 0.281329E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.469513E+09 | 0.344699E+10 | 0.117815E+10 | 0.379902E+09 | 0.798249E+09 | 0.00 | 0.00 |
February | 0.759037E+09 | 0.295115E+10 | 0.156141E+10 | 0.468541E+09 | 0.109287E+10 | 0.00 | 0.00 |
March | 0.195136E+10 | 0.240282E+10 | 0.248065E+10 | 0.103888E+10 | 0.144177E+10 | 0.00 | 0.00 |
April | 0.298872E+10 | 0.172583E+10 | 0.317738E+10 | 0.140394E+10 | 0.177344E+10 | 0.00 | 0.00 |
May | 0.398726E+10 | 0.124298E+10 | 0.367846E+10 | 0.162718E+10 | 0.205128E+10 | 0.00 | 0.00 |
June | 0.482795E+10 | 0.778617E+09 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
July | 0.514815E+10 | 0.556526E+09 | 0.394497E+10 | 0.173692E+10 | 0.220806E+10 | 0.00 | 0.00 |
August | 0.454739E+10 | 0.731078E+09 | 0.356274E+10 | 0.149545E+10 | 0.206730E+10 | 0.00 | 0.00 |
September | 0.329937E+10 | 0.112707E+10 | 0.286918E+10 | 0.127266E+10 | 0.159652E+10 | 0.00 | 0.00 |
October | 0.178446E+10 | 0.180461E+10 | 0.201188E+10 | 0.832167E+09 | 0.117971E+10 | 0.00 | 0.00 |
November | 0.685527E+09 | 0.222059E+10 | 0.110436E+10 | 0.354266E+09 | 0.750094E+09 | 0.00 | 0.00 |
December | 0.245388E+09 | 0.339901E+10 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.306941E+11 | 0.223873E+11 | 0.304636E+11 | 0.125568E+11 | 0.179068E+11 | 0.00 | 0.00 |
Minimum of Months | 0.245388E+09 | 0.556526E+09 | 0.918702E+09 | 0.189824E+09 | 0.728878E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514815E+10 | 0.344699E+10 | 0.397570E+10 | 0.175706E+10 | 0.221864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.340137E+10 | 0.488779E+10 | 0.415250E+10 | 0.242393E+10 | 0.172856E+10 | 0.00 | 0.00 |
February | 0.346306E+10 | 0.433690E+10 | 0.428229E+10 | 0.206488E+10 | 0.221741E+10 | 0.00 | 0.00 |
March | 0.572268E+10 | 0.362712E+10 | 0.578684E+10 | 0.325159E+10 | 0.253525E+10 | 0.00 | 0.00 |
April | 0.476976E+10 | 0.280975E+10 | 0.463782E+10 | 0.185329E+10 | 0.278453E+10 | 0.00 | 0.00 |
May | 0.467256E+10 | 0.201543E+10 | 0.419379E+10 | 0.121805E+10 | 0.297573E+10 | 0.00 | 0.00 |
June | 0.491416E+10 | 0.126019E+10 | 0.394356E+10 | 0.835659E+09 | 0.310790E+10 | 0.00 | 0.00 |
July | 0.573689E+10 | 0.897630E+09 | 0.415992E+10 | 0.100933E+10 | 0.315059E+10 | 0.00 | 0.00 |
August | 0.633373E+10 | 0.116359E+10 | 0.467020E+10 | 0.151420E+10 | 0.315600E+10 | 0.00 | 0.00 |
September | 0.656616E+10 | 0.179185E+10 | 0.525489E+10 | 0.255952E+10 | 0.269537E+10 | 0.00 | 0.00 |
October | 0.561917E+10 | 0.275888E+10 | 0.519575E+10 | 0.296792E+10 | 0.222784E+10 | 0.00 | 0.00 |
November | 0.343266E+10 | 0.330240E+10 | 0.360106E+10 | 0.203292E+10 | 0.156814E+10 | 0.00 | 0.00 |
December | 0.269269E+10 | 0.481425E+10 | 0.347231E+10 | 0.179708E+10 | 0.167523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.573249E+11 | 0.336658E+11 | 0.533509E+11 | 0.235284E+11 | 0.298226E+11 | 0.00 | 0.00 |
Minimum of Months | 0.269269E+10 | 0.897630E+09 | 0.347231E+10 | 0.835659E+09 | 0.156814E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656616E+10 | 0.488779E+10 | 0.578684E+10 | 0.325159E+10 | 0.315600E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290981E+09 | 0.358241E+10 | 0.101083E+10 | 0.237304E+09 | 0.773529E+09 | 0.00 | 0.00 |
February | 0.660022E+09 | 0.305051E+10 | 0.147974E+10 | 0.380304E+09 | 0.109943E+10 | 0.00 | 0.00 |
March | 0.207878E+10 | 0.246942E+10 | 0.256771E+10 | 0.109944E+10 | 0.146828E+10 | 0.00 | 0.00 |
April | 0.287338E+10 | 0.180698E+10 | 0.304240E+10 | 0.124751E+10 | 0.179490E+10 | 0.00 | 0.00 |
May | 0.406387E+10 | 0.132015E+10 | 0.370864E+10 | 0.167606E+10 | 0.203257E+10 | 0.00 | 0.00 |
June | 0.533780E+10 | 0.849490E+09 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
July | 0.525708E+10 | 0.617412E+09 | 0.400044E+10 | 0.175393E+10 | 0.224651E+10 | 0.00 | 0.00 |
August | 0.467707E+10 | 0.784086E+09 | 0.361817E+10 | 0.153848E+10 | 0.207969E+10 | 0.00 | 0.00 |
September | 0.317821E+10 | 0.118862E+10 | 0.274972E+10 | 0.118749E+10 | 0.156224E+10 | 0.00 | 0.00 |
October | 0.160930E+10 | 0.186879E+10 | 0.184192E+10 | 0.648830E+09 | 0.119309E+10 | 0.00 | 0.00 |
November | 0.637161E+09 | 0.226145E+10 | 0.105632E+10 | 0.304393E+09 | 0.751925E+09 | 0.00 | 0.00 |
December | 0.280185E+09 | 0.345835E+10 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309438E+11 | 0.232577E+11 | 0.303524E+11 | 0.123167E+11 | 0.180357E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280185E+09 | 0.617412E+09 | 0.946258E+09 | 0.206179E+09 | 0.740079E+09 | 0.00 | 0.00 |
Maximum of Months | 0.533780E+10 | 0.358241E+10 | 0.433024E+10 | 0.203677E+10 | 0.229347E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.564001E+10 | -0.488012E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -759889209.0 | 58.99 | 0.00 | 0.00 |
February | 0.518056E+10 | -0.449948E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -681080521.5 | 58.98 | 0.00 | 0.00 |
March | 0.597927E+10 | -0.525361E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -725656514.4 | 58.98 | 0.00 | 0.00 |
April | 0.522779E+10 | -0.454106E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -686727782.3 | 58.98 | 0.00 | 0.00 |
May | 0.529158E+10 | -0.459557E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696011572.8 | 58.98 | 0.00 | 0.00 |
June | 0.495281E+10 | -0.428195E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670858587.1 | 58.98 | 0.00 | 0.00 |
July | 0.452731E+10 | -0.383726E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690052813.8 | 58.98 | 0.00 | 0.00 |
August | 0.485527E+10 | -0.416402E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691252817.6 | 58.98 | 0.00 | 0.00 |
September | 0.448707E+10 | -0.381719E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669879979.1 | 58.98 | 0.00 | 0.00 |
October | 0.484070E+10 | -0.413958E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -701120840.6 | 58.98 | 0.00 | 0.00 |
November | 0.502852E+10 | -0.433466E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -693857447.7 | 58.98 | 0.00 | 0.00 |
December | 0.529647E+10 | -0.454947E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -747006026.9 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.613074E+11 | -0.528940E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.841339E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.448707E+10 | -0.525361E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -759889209.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.597927E+10 | -0.381719E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -669879979.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4409.99 | 32.57 | 236.00 | 250.83 | 3547.55 | 33.71 | 243.00 | 223.67 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:39 | 5535.09 | 32.76 | 245.83 | 256.00 | 1857.02 | 26.99 | 240.67 | 237.50 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7905.28 | 29.81 | 254.83 | 326.67 | 1499.97 | 21.81 | 189.33 | 294.00 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:00 | 2070.52 | 18.76 | 3.00 | 345.50 | 1163.89 | 20.95 | 200.33 | 311.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1876.12 | 18.83 | 0.17 | 384.00 | 1106.58 | 21.09 | 184.00 | 337.17 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1690.38 | 18.63 | 0.00 | 393.17 | 973.96 | 20.85 | 222.83 | 353.17 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1773.28 | 18.66 | 1.00 | 399.67 | 1007.74 | 20.88 | 219.83 | 354.83 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2103.04 | 19.14 | 4.50 | 377.17 | 1170.06 | 21.35 | 252.33 | 337.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3000.87 | 20.64 | 32.00 | 324.00 | 1543.80 | 21.98 | 220.00 | 292.17 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6397.20 | 32.22 | 277.50 | 298.17 | 1578.78 | 22.39 | 196.33 | 276.67 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4149.34 | 32.38 | 240.17 | 240.50 | 1687.51 | 27.88 | 219.00 | 217.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3716.76 | 31.19 | 209.00 | 238.67 | 2910.88 | 33.07 | 223.33 | 208.00 |
Annual Sum or Average | 3928.50 | 0.50 | 3518.03 | 24.41 | 1504.00 | 3834.33 | 1549.75 | 23.65 | 2611.00 | 3443.33 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1690.38 | 18.63 | 0.00 | 238.67 | 973.96 | 20.85 | 184.00 | 208.00 | |
Maximum of Months | 439.00 | 0.50 | 0.48 | 7905.28 | 32.76 | 277.50 | 399.67 | 3547.55 | 33.71 | 252.33 | 354.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1514.74 | 20.81 | 70.67 | 236.00 | 758.64 | 21.56 | 83.83 | 188.17 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:39 | 2093.95 | 21.96 | 83.33 | 248.17 | 1088.09 | 22.83 | 111.67 | 217.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:19 | 2821.96 | 21.66 | 104.33 | 319.67 | 1243.29 | 22.41 | 90.00 | 284.83 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 3064.73 | 21.09 | 104.33 | 350.33 | 1719.67 | 22.35 | 87.33 | 314.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 4094.18 | 22.57 | 103.50 | 391.67 | 1740.29 | 22.33 | 58.83 | 347.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3723.57 | 21.82 | 133.17 | 402.67 | 1640.42 | 22.07 | 78.83 | 372.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3520.87 | 21.96 | 135.17 | 409.33 | 1553.38 | 22.08 | 80.17 | 371.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3243.51 | 21.35 | 110.33 | 378.33 | 1449.14 | 22.31 | 76.83 | 345.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3305.47 | 22.80 | 85.83 | 323.50 | 1822.47 | 23.77 | 101.17 | 288.33 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-06:00 | 2095.18 | 20.80 | 81.50 | 288.00 | 1134.61 | 22.64 | 94.33 | 254.00 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:40 | 1525.66 | 21.13 | 87.00 | 229.83 | 837.79 | 21.96 | 91.00 | 178.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-07:00 | 1305.58 | 20.08 | 60.33 | 225.83 | 656.02 | 21.04 | 68.83 | 173.33 |
Annual Sum or Average | 3928.50 | 0.50 | 2842.58 | 21.55 | 1159.50 | 3803.33 | 1360.72 | 22.29 | 1022.83 | 3335.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1305.58 | 20.08 | 60.33 | 225.83 | 656.02 | 21.04 | 58.83 | 173.33 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 4094.18 | 22.80 | 135.17 | 409.33 | 1822.47 | 23.77 | 111.67 | 372.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:20 | 652.27 | 15.89 | 0.00 | 220.17 | 366.45 | 18.14 | 0.00 | 135.67 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:20 | 857.00 | 16.98 | 0.00 | 241.83 | 478.49 | 19.13 | 0.50 | 191.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 906.58 | 17.54 | 0.00 | 313.50 | 532.80 | 19.77 | 2.33 | 265.50 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1045.75 | 18.10 | 0.00 | 349.83 | 617.56 | 20.21 | 57.00 | 315.50 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1256.64 | 20.30 | 26.50 | 401.50 | 763.84 | 22.42 | 161.33 | 362.67 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1406.69 | 21.74 | 80.83 | 412.83 | 826.47 | 22.67 | 234.50 | 389.00 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1338.40 | 21.41 | 75.17 | 419.00 | 784.55 | 22.41 | 232.83 | 389.17 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1184.65 | 18.82 | 0.00 | 387.00 | 705.91 | 20.97 | 138.50 | 353.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 989.84 | 18.34 | 0.00 | 320.50 | 614.69 | 20.56 | 40.50 | 272.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:40 | 795.65 | 16.74 | 0.00 | 280.83 | 459.56 | 18.97 | 0.33 | 221.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 632.64 | 15.37 | 0.00 | 217.33 | 353.64 | 17.52 | 0.00 | 126.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 656.75 | 15.82 | 0.00 | 207.33 | 360.77 | 17.99 | 0.00 | 117.17 |
Annual Sum or Average | 3928.50 | 0.50 | 1025.88 | 18.46 | 182.50 | 3771.67 | 602.41 | 20.37 | 867.83 | 3140.33 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 632.64 | 15.37 | 0.00 | 207.33 | 353.64 | 17.52 | 0.00 | 117.17 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1406.69 | 21.74 | 80.83 | 419.00 | 826.47 | 22.67 | 234.50 | 389.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:00 | 1419.14 | 21.25 | 85.83 | 234.83 | 774.14 | 22.20 | 86.50 | 188.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:09 | 1916.63 | 20.38 | 68.17 | 247.50 | 1037.53 | 22.70 | 96.33 | 217.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 2770.71 | 21.50 | 101.67 | 321.83 | 1568.08 | 22.73 | 98.33 | 286.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:19 | 3279.77 | 20.84 | 104.67 | 346.17 | 1392.37 | 20.87 | 55.33 | 312.17 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3511.46 | 18.14 | 43.00 | 390.33 | 1945.35 | 18.88 | 0.00 | 352.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:30 | 3713.55 | 17.90 | 52.83 | 400.83 | 1601.45 | 18.85 | 0.17 | 369.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3312.96 | 17.96 | 54.83 | 407.00 | 1508.05 | 19.03 | 5.83 | 370.83 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:30 | 3101.20 | 19.90 | 85.50 | 382.67 | 1685.23 | 21.27 | 62.67 | 346.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3388.78 | 22.38 | 83.50 | 321.67 | 1498.52 | 22.17 | 68.50 | 290.00 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:00 | 1965.70 | 20.48 | 79.67 | 287.50 | 1055.88 | 22.41 | 91.50 | 254.00 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1458.06 | 20.75 | 86.83 | 228.00 | 778.04 | 21.53 | 82.00 | 181.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-11:39 | 1348.99 | 19.72 | 56.33 | 221.17 | 725.20 | 21.69 | 72.00 | 173.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2745.98 | 19.94 | 902.83 | 3789.50 | 1357.87 | 21.00 | 719.17 | 3341.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1348.99 | 17.90 | 43.00 | 221.17 | 725.20 | 18.85 | 0.00 | 173.00 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3713.55 | 22.38 | 104.67 | 407.00 | 1945.35 | 22.73 | 98.33 | 370.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4276.44 | 32.11 | 233.33 | 248.33 | 3450.68 | 33.23 | 233.00 | 221.17 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:50 | 5389.36 | 32.39 | 241.83 | 254.50 | 1755.52 | 24.97 | 107.00 | 235.67 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7766.52 | 28.70 | 234.67 | 325.67 | 1398.15 | 19.03 | 19.00 | 291.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:00 | 1971.60 | 14.92 | 0.00 | 343.50 | 1093.86 | 18.40 | 10.83 | 308.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1791.55 | 15.19 | 0.00 | 380.67 | 1048.88 | 18.76 | 3.83 | 333.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:10 | 1620.29 | 15.03 | 0.00 | 390.33 | 928.82 | 18.53 | 0.17 | 350.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1698.13 | 14.99 | 0.00 | 397.17 | 958.47 | 18.48 | 6.83 | 351.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2007.98 | 15.41 | 0.00 | 374.17 | 1105.40 | 18.89 | 17.67 | 334.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2860.03 | 17.08 | 17.00 | 321.83 | 1441.02 | 19.51 | 28.17 | 289.00 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6263.65 | 31.62 | 270.67 | 297.50 | 1478.04 | 19.50 | 25.17 | 274.67 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4030.02 | 32.04 | 237.50 | 239.50 | 1604.13 | 26.20 | 135.33 | 215.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3573.39 | 29.71 | 195.33 | 236.33 | 2823.84 | 32.68 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.50 | 3407.92 | 21.98 | 1430.33 | 3809.50 | 1473.03 | 21.48 | 803.83 | 3410.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1620.29 | 14.92 | 0.00 | 236.33 | 928.82 | 18.40 | 0.17 | 206.50 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 7766.52 | 32.39 | 270.67 | 397.17 | 3450.68 | 33.23 | 233.00 | 351.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1469.47 | 20.29 | 70.00 | 234.67 | 724.47 | 21.30 | 77.50 | 183.83 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:50 | 1994.70 | 20.22 | 69.33 | 246.17 | 1042.95 | 22.61 | 98.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 2740.95 | 21.10 | 103.17 | 317.17 | 1187.98 | 22.20 | 79.50 | 281.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 2981.93 | 20.63 | 104.00 | 348.67 | 1655.21 | 22.16 | 81.83 | 311.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 3997.94 | 22.12 | 103.50 | 389.17 | 1666.27 | 22.15 | 58.00 | 344.17 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3634.38 | 21.38 | 132.83 | 400.33 | 1573.95 | 21.90 | 76.83 | 369.33 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3432.47 | 21.52 | 135.17 | 406.83 | 1487.26 | 21.91 | 77.50 | 369.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3156.72 | 20.89 | 110.17 | 376.83 | 1382.38 | 22.14 | 69.33 | 342.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3212.71 | 22.34 | 85.83 | 322.33 | 1749.37 | 23.58 | 87.17 | 284.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-06:00 | 2033.20 | 20.32 | 81.17 | 286.00 | 1086.18 | 22.42 | 83.50 | 249.50 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:40 | 1482.13 | 20.68 | 86.83 | 227.83 | 805.93 | 21.73 | 84.67 | 173.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 1265.44 | 19.58 | 59.67 | 224.33 | 626.96 | 20.78 | 63.67 | 169.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2764.42 | 21.00 | 1141.67 | 3780.33 | 1303.73 | 22.09 | 937.50 | 3292.00 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1265.44 | 19.58 | 59.67 | 224.33 | 626.96 | 20.78 | 58.00 | 169.00 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3997.94 | 22.34 | 135.17 | 406.83 | 1749.37 | 23.58 | 98.00 | 369.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:30 | 628.20 | 11.90 | 0.00 | 216.67 | 352.78 | 15.49 | 0.00 | 125.83 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:30 | 826.59 | 13.26 | 0.00 | 240.00 | 461.15 | 16.68 | 0.00 | 186.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 874.73 | 14.02 | 0.00 | 311.17 | 515.32 | 17.53 | 0.00 | 259.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1014.56 | 14.65 | 0.00 | 349.17 | 597.48 | 18.09 | 0.17 | 310.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1213.03 | 17.20 | 26.17 | 399.67 | 740.05 | 20.54 | 40.00 | 359.17 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1357.26 | 18.94 | 74.50 | 411.83 | 798.28 | 20.67 | 69.50 | 386.67 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1291.34 | 18.55 | 71.00 | 418.00 | 757.88 | 20.40 | 61.83 | 386.00 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1142.53 | 15.40 | 0.00 | 385.33 | 682.64 | 18.90 | 11.33 | 349.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 953.81 | 15.22 | 0.00 | 319.00 | 595.57 | 18.72 | 0.00 | 267.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:49 | 767.15 | 13.06 | 0.00 | 277.83 | 443.69 | 16.56 | 0.00 | 214.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 609.53 | 11.43 | 0.00 | 214.17 | 340.49 | 14.88 | 0.00 | 118.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 632.78 | 11.79 | 0.00 | 204.67 | 346.96 | 15.31 | 0.00 | 108.50 |
Annual Sum or Average | 3928.50 | 0.50 | 990.01 | 15.06 | 171.67 | 3747.50 | 582.12 | 18.16 | 182.83 | 3073.00 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 609.53 | 11.43 | 0.00 | 204.67 | 340.49 | 14.88 | 0.00 | 108.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1357.26 | 18.94 | 74.50 | 418.00 | 798.28 | 20.67 | 69.50 | 386.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 1379.95 | 20.88 | 85.00 | 233.33 | 745.46 | 22.10 | 85.00 | 182.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:20 | 1858.71 | 19.97 | 68.17 | 246.83 | 994.48 | 22.60 | 95.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 2698.14 | 21.09 | 101.50 | 320.50 | 1509.44 | 22.60 | 94.83 | 284.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:19 | 3142.96 | 20.41 | 104.33 | 343.83 | 1332.74 | 20.72 | 53.50 | 309.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3405.90 | 17.65 | 43.00 | 388.83 | 1853.04 | 18.71 | 0.00 | 348.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:30 | 3567.43 | 17.41 | 52.67 | 399.17 | 1525.89 | 18.67 | 0.00 | 366.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3186.66 | 17.47 | 54.67 | 404.00 | 1439.77 | 18.86 | 3.67 | 369.00 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:30 | 3015.25 | 19.45 | 85.50 | 379.83 | 1618.30 | 21.12 | 59.50 | 341.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3302.57 | 21.95 | 83.50 | 320.17 | 1428.94 | 22.04 | 65.17 | 287.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:00 | 1907.40 | 20.06 | 78.67 | 286.17 | 1011.40 | 22.30 | 89.33 | 250.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1417.04 | 20.38 | 86.50 | 226.00 | 748.18 | 21.42 | 81.17 | 175.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 1306.76 | 19.14 | 53.67 | 219.33 | 695.59 | 21.58 | 71.17 | 167.17 |
Annual Sum or Average | 3928.50 | 0.50 | 2656.24 | 19.49 | 897.17 | 3768.00 | 1299.41 | 20.86 | 698.33 | 3297.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1306.76 | 17.41 | 43.00 | 219.33 | 695.59 | 18.67 | 0.00 | 167.17 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3567.43 | 21.95 | 104.33 | 404.00 | 1853.04 | 22.60 | 95.00 | 369.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.49 | 0.48 | 01-JAN-09:09 | 4276.41 | 32.11 | 233.33 | 248.33 | 3450.58 | 33.23 | 233.00 | 221.17 |
February | 262.50 | 0.49 | 0.48 | 01-FEB-09:50 | 5389.27 | 32.39 | 241.83 | 254.50 | 1755.39 | 24.97 | 107.00 | 235.67 |
March | 339.33 | 0.49 | 0.48 | 01-MAR-07:30 | 7766.41 | 28.70 | 234.67 | 325.67 | 1398.05 | 19.03 | 19.00 | 291.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:00 | 1971.48 | 14.92 | 0.00 | 343.50 | 1093.77 | 18.40 | 10.83 | 308.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:30 | 1791.46 | 15.20 | 0.00 | 380.67 | 1048.81 | 18.77 | 3.83 | 333.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:10 | 1620.20 | 15.03 | 0.00 | 390.33 | 928.75 | 18.53 | 0.17 | 350.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1698.03 | 14.99 | 0.00 | 397.17 | 958.40 | 18.48 | 6.83 | 351.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:19 | 2007.86 | 15.41 | 0.00 | 374.17 | 1105.31 | 18.89 | 17.67 | 334.17 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2859.89 | 17.08 | 17.00 | 321.83 | 1440.91 | 19.51 | 28.17 | 289.00 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6263.56 | 31.62 | 270.67 | 297.50 | 1477.93 | 19.50 | 25.17 | 274.67 |
November | 258.33 | 0.50 | 0.48 | 01-NOV-07:40 | 4029.97 | 32.04 | 237.50 | 239.50 | 1604.03 | 26.20 | 135.33 | 215.00 |
December | 230.67 | 0.49 | 0.48 | 01-DEC-08:09 | 3573.35 | 29.71 | 195.33 | 236.33 | 2823.74 | 32.68 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.50 | 3407.83 | 21.98 | 1430.33 | 3809.50 | 1472.94 | 21.48 | 803.83 | 3410.67 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 1620.20 | 14.92 | 0.00 | 236.33 | 928.75 | 18.40 | 0.17 | 206.50 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 7766.41 | 32.39 | 270.67 | 397.17 | 3450.58 | 33.23 | 233.00 | 351.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:09 | 1469.43 | 20.30 | 70.00 | 234.67 | 724.42 | 21.30 | 77.50 | 183.83 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:50 | 1994.64 | 20.22 | 69.33 | 246.17 | 1042.88 | 22.61 | 98.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 2740.90 | 21.10 | 103.17 | 317.17 | 1187.91 | 22.20 | 79.50 | 281.17 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:30 | 2981.86 | 20.63 | 104.00 | 348.67 | 1655.14 | 22.16 | 82.17 | 311.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 3997.88 | 22.13 | 103.50 | 389.17 | 1666.19 | 22.15 | 58.17 | 344.17 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3634.32 | 21.38 | 132.83 | 400.33 | 1573.87 | 21.90 | 76.83 | 369.33 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-04:00 | 3432.40 | 21.52 | 135.17 | 406.83 | 1487.18 | 21.91 | 77.50 | 369.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3156.66 | 20.89 | 110.17 | 376.83 | 1382.30 | 22.14 | 69.33 | 342.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3212.67 | 22.34 | 85.83 | 322.33 | 1749.29 | 23.58 | 87.17 | 284.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-06:00 | 2033.15 | 20.32 | 81.17 | 286.00 | 1086.12 | 22.42 | 83.67 | 249.50 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:40 | 1482.09 | 20.68 | 86.83 | 227.83 | 805.88 | 21.73 | 84.67 | 173.00 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 1265.40 | 19.58 | 59.67 | 224.33 | 626.91 | 20.78 | 63.83 | 169.00 |
Annual Sum or Average | 3928.50 | 0.50 | 2764.36 | 21.00 | 1141.67 | 3780.33 | 1303.66 | 22.09 | 938.33 | 3291.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1265.40 | 19.58 | 59.67 | 224.33 | 626.91 | 20.78 | 58.17 | 169.00 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3997.88 | 22.34 | 135.17 | 406.83 | 1749.29 | 23.58 | 98.00 | 369.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:30 | 628.17 | 11.90 | 0.00 | 216.67 | 352.76 | 15.49 | 0.00 | 125.83 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:30 | 826.55 | 13.26 | 0.00 | 240.00 | 461.11 | 16.69 | 0.00 | 186.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 874.69 | 14.02 | 0.00 | 311.17 | 515.28 | 17.53 | 0.00 | 259.67 |
April | 371.17 | 0.50 | 0.48 | 01-APR-06:49 | 1014.52 | 14.65 | 0.00 | 349.17 | 597.44 | 18.09 | 0.17 | 310.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-05:00 | 1213.01 | 17.20 | 26.17 | 399.67 | 740.01 | 20.54 | 40.00 | 359.17 |
June | 430.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1357.21 | 18.94 | 74.50 | 411.83 | 798.23 | 20.67 | 69.67 | 386.67 |
July | 439.00 | 0.49 | 0.48 | 01-JUL-05:19 | 1291.29 | 18.56 | 71.00 | 418.00 | 757.83 | 20.40 | 61.83 | 386.00 |
August | 406.00 | 0.49 | 0.48 | 01-AUG-05:00 | 1142.48 | 15.40 | 0.00 | 385.33 | 682.59 | 18.91 | 11.33 | 349.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 953.79 | 15.22 | 0.00 | 319.00 | 595.53 | 18.72 | 0.00 | 267.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:49 | 767.12 | 13.06 | 0.00 | 277.83 | 443.65 | 16.57 | 0.00 | 214.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:20 | 609.50 | 11.43 | 0.00 | 214.17 | 340.46 | 14.88 | 0.00 | 118.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 632.74 | 11.79 | 0.00 | 204.67 | 346.93 | 15.31 | 0.00 | 108.50 |
Annual Sum or Average | 3928.50 | 0.50 | 989.98 | 15.06 | 171.67 | 3747.50 | 582.08 | 18.16 | 183.00 | 3072.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 609.50 | 11.43 | 0.00 | 204.67 | 340.46 | 14.88 | 0.00 | 108.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 1357.21 | 18.94 | 74.50 | 418.00 | 798.23 | 20.67 | 69.67 | 386.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:00 | 1379.90 | 20.88 | 85.00 | 233.33 | 745.41 | 22.10 | 85.00 | 182.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-10:20 | 1858.65 | 19.97 | 68.17 | 246.83 | 994.42 | 22.60 | 95.00 | 214.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:09 | 2698.09 | 21.09 | 101.50 | 320.50 | 1509.37 | 22.61 | 94.83 | 284.33 |
April | 371.17 | 0.50 | 0.48 | 01-APR-07:19 | 3142.89 | 20.41 | 104.33 | 343.83 | 1332.66 | 20.72 | 53.67 | 309.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3405.85 | 17.65 | 43.00 | 388.83 | 1852.97 | 18.71 | 0.00 | 348.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:30 | 3567.36 | 17.41 | 52.67 | 399.17 | 1525.81 | 18.67 | 0.00 | 366.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3186.59 | 17.47 | 54.67 | 404.00 | 1439.69 | 18.86 | 3.67 | 369.00 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:30 | 3015.17 | 19.45 | 85.50 | 379.83 | 1618.22 | 21.12 | 59.50 | 341.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3302.53 | 21.96 | 83.50 | 320.17 | 1428.87 | 22.04 | 65.33 | 287.67 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:00 | 1907.35 | 20.06 | 78.67 | 286.17 | 1011.34 | 22.30 | 89.50 | 250.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-08:20 | 1416.99 | 20.38 | 86.50 | 226.00 | 748.13 | 21.42 | 81.33 | 175.33 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 1306.72 | 19.14 | 53.67 | 219.33 | 695.54 | 21.58 | 71.17 | 167.17 |
Annual Sum or Average | 3928.50 | 0.50 | 2656.18 | 19.49 | 897.17 | 3768.00 | 1299.34 | 20.86 | 699.00 | 3297.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1306.72 | 17.41 | 43.00 | 219.33 | 695.54 | 18.67 | 0.00 | 167.17 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 3567.36 | 21.96 | 104.33 | 404.00 | 1852.97 | 22.61 | 95.00 | 369.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110598E+10 | 20717.81 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220101E+09 | 20717.81 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1243068.72 | 20717.81 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115014E+09 | 20717.81 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110598E+10 | 20717.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.825983E+10 | 10997.33 | 11-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.713197E+10 | 11402.02 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400155E+10 | 11006.48 | 14-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.214195E+10 | 10957.51 | 25-APR-11:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746971E+09 | 10952.94 | 12-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160262E+09 | 11128.92 | 14-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9588266.99 | 4122.63 | 07-JUL-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31308479.03 | 6375.10 | 31-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196829E+09 | 10963.09 | 05-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107561E+10 | 10963.24 | 26-OCT-16:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287179E+10 | 10955.27 | 27-NOV-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.698805E+10 | 11622.25 | 11-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9588266.99 | 4122.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.825983E+10 | 11622.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.320300E+10 | 9123.64 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258405E+10 | 9127.39 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.827241E+09 | 9087.56 | 10-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107716E+09 | 9087.49 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10362246.58 | 9065.78 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296245E+09 | 9083.83 | 20-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241563E+10 | 9121.13 | 28-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.944424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.320300E+10 | 9127.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.549035E+10 | 7364.67 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466593E+10 | 7641.81 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233412E+10 | 7348.03 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.473406E+09 | 7323.03 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3203899.22 | 4391.83 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37237180.54 | 7287.81 | 18-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601917E+09 | 7314.06 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394534E+10 | 7791.33 | 11-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.549035E+10 | 7791.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.343617E+10 | 9520.46 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279823E+10 | 9524.34 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.923237E+09 | 9482.77 | 10-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152743E+09 | 9462.88 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 472157.46 | 1445.99 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12670657.56 | 9460.04 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314812E+09 | 9471.07 | 21-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245059E+10 | 9517.80 | 28-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.343617E+10 | 9524.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354180E+10 | 22406.60 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269996E+10 | 22406.60 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311225E+09 | 22406.60 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21950340.94 | 22406.60 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138099E+09 | 22406.60 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235463E+10 | 22406.60 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354180E+10 | 22406.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.350429E+10 | 12681.22 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292653E+10 | 12658.82 | 27-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.701688E+09 | 12611.69 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140176E+09 | 12636.58 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49314834.02 | 12490.06 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.542750E+09 | 12621.06 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.305453E+10 | 12668.29 | 12-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350429E+10 | 12681.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.281659E+10 | 9951.33 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.231262E+10 | 9951.33 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.589333E+09 | 9951.33 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63224950.30 | 9951.33 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42911908.29 | 9951.33 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452201E+09 | 9951.33 | 13-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249709E+10 | 9951.33 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.877396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281659E+10 | 9951.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.501830E+10 | 8356.13 | 18-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422763E+10 | 8359.73 | 07-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151228E+10 | 8331.43 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201139E+09 | 8315.18 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94332492.31 | 8311.03 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.843551E+09 | 8335.74 | 22-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.420536E+10 | 8370.59 | 11-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.501830E+10 | 8370.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.312382E+10 | 10040.43 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256829E+10 | 10040.43 | 01-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.716054E+09 | 10040.43 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104131E+09 | 10040.43 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50901023.20 | 10040.43 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.499474E+09 | 10040.43 | 13-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263376E+10 | 10040.43 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.969644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.312382E+10 | 10040.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.791715E+10 | 30492.04 | 18-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.645414E+10 | 30387.55 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202123E+10 | 30381.85 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286624E+09 | 30446.57 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152809E+09 | 30476.15 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140553E+10 | 30418.34 | 22-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.663486E+10 | 30464.41 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.791715E+10 | 30492.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542336E+10 | 13895.08 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.476235E+10 | 13831.10 | 23-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160715E+10 | 13830.12 | 10-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441438E+09 | 13805.43 | 17-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8900522.59 | 10064.25 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3908083.14 | 5276.87 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264951E+09 | 13773.65 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138625E+10 | 13835.88 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508732E+10 | 13860.36 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542336E+10 | 13895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.432190E+10 | 11250.67 | 14-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366848E+10 | 11267.10 | 23-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123611E+10 | 11194.71 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211763E+09 | 11243.44 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1062581.48 | 1304.90 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2472667.02 | 4513.55 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206311E+09 | 11220.43 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110531E+10 | 11271.03 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407366E+10 | 11291.15 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.432190E+10 | 11291.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.728573E+10 | 9553.16 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628755E+10 | 9746.12 | 07-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275963E+10 | 9557.19 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.572052E+09 | 9529.82 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4827632.00 | 6406.34 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6669187.79 | 6583.83 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.443795E+09 | 9539.80 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193901E+10 | 9556.17 | 21-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.649615E+10 | 9555.58 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.728573E+10 | 9746.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460367E+10 | 12220.72 | 18-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393114E+10 | 12274.50 | 15-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145286E+10 | 12188.56 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321786E+09 | 12210.78 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4342534.51 | 4969.80 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4117908.80 | 3682.59 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249838E+09 | 12216.61 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117380E+10 | 12283.96 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413598E+10 | 12288.65 | 15-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.460367E+10 | 12288.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187686E+11 | 28606.25 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173960E+11 | 30354.97 | 06-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104991E+11 | 30001.92 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340869E+10 | 17913.48 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149988E+09 | 7956.50 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3269860.28 | 1639.93 | 10-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22741969.99 | 3065.86 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177410E+10 | 14599.10 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580116E+10 | 16625.50 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162150E+11 | 30354.97 | 11-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.740386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187686E+11 | 30354.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179383E+11 | 28276.15 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166879E+11 | 30847.10 | 07-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105149E+11 | 26732.74 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365256E+10 | 16101.09 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217271E+09 | 7851.79 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11637935.08 | 2404.50 | 06-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49990909.39 | 3808.06 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218998E+10 | 15971.39 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618457E+10 | 15572.87 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158058E+11 | 30847.10 | 11-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.732529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179383E+11 | 30847.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193224E+11 | 29608.05 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179095E+11 | 29903.91 | 06-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109850E+11 | 28940.44 | 07-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393106E+10 | 18227.08 | 17-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.343647E+09 | 9904.94 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36285120.79 | 3678.37 | 14-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97824563.39 | 4828.15 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254265E+10 | 15853.87 | 17-OCT-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.664678E+10 | 17561.85 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171015E+11 | 29903.91 | 11-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.789167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193224E+11 | 29903.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.146241E+10 | 0.113478E+10 | 22692.99 | 15-MAR-14:00 | 22692.99 | 0.00 |
April | 0.00 | 0.00 | 0.576657E+09 | 0.507277E+09 | 10390.83 | 08-APR-13:30 | 8124.49 | 0.00 |
May | 0.00 | 0.00 | 0.644437E+10 | 0.579930E+10 | 32744.86 | 23-MAY-14:30 | 32744.86 | 0.00 |
June | 0.00 | 0.00 | 0.314347E+11 | 0.237306E+11 | 84094.75 | 27-JUN-07:40 | 36351.12 | 0.00 |
July | 0.00 | 0.00 | 0.563868E+11 | 0.398506E+11 | 103826.73 | 20-JUL-06:03 | 42867.61 | 0.00 |
August | 0.00 | 0.00 | 0.480253E+11 | 0.372856E+11 | 103856.48 | 14-AUG-08:00 | 44352.20 | 0.00 |
September | 0.00 | 0.00 | 0.210612E+11 | 0.159993E+11 | 69422.36 | 15-SEP-11:00 | 38609.59 | 0.00 |
October | 0.00 | 0.00 | 0.233696E+10 | 0.198182E+10 | 27250.62 | 11-OCT-15:10 | 27250.62 | 0.00 |
November | 0.00 | 0.00 | 0.326649E+09 | 0.220847E+09 | 7789.05 | 16-NOV-17:00 | 5454.08 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168055E+12 | 0.126510E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.563868E+11 | 0.398506E+11 | 103856.48 | 44352.20 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160273E+10 | 0.130143E+10 | 29950.62 | 15-MAR-14:05 | 29950.62 | 0.00 |
April | 0.00 | 0.00 | 0.581458E+09 | 0.518038E+09 | 11877.85 | 08-APR-14:05 | 10151.16 | 0.00 |
May | 0.00 | 0.00 | 0.702621E+10 | 0.633591E+10 | 36710.04 | 23-MAY-14:05 | 36710.04 | 0.00 |
June | 0.00 | 0.00 | 0.323870E+11 | 0.244479E+11 | 91870.30 | 12-JUN-06:03 | 55059.35 | 0.00 |
July | 0.00 | 0.00 | 0.556341E+11 | 0.391355E+11 | 101077.23 | 20-JUL-06:03 | 41623.89 | 0.00 |
August | 0.00 | 0.00 | 0.454032E+11 | 0.351742E+11 | 100816.63 | 14-AUG-10:10 | 41668.97 | 0.00 |
September | 0.00 | 0.00 | 0.193602E+11 | 0.145710E+11 | 69410.34 | 15-SEP-11:00 | 37733.22 | 0.00 |
October | 0.00 | 0.00 | 0.211252E+10 | 0.174681E+10 | 25418.40 | 11-OCT-15:00 | 25418.40 | 0.00 |
November | 0.00 | 0.00 | 0.304870E+09 | 0.203914E+09 | 7215.65 | 16-NOV-18:00 | 4962.52 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164412E+12 | 0.123435E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.556341E+11 | 0.391355E+11 | 101077.23 | 55059.35 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.179456E+10 | 0.147454E+10 | 35882.83 | 15-MAR-13:50 | 35882.83 | 0.00 |
April | 0.00 | 0.00 | 0.607451E+09 | 0.531068E+09 | 12662.86 | 08-APR-13:30 | 10577.13 | 0.00 |
May | 0.00 | 0.00 | 0.736236E+10 | 0.659392E+10 | 42154.53 | 10-MAY-14:30 | 42154.53 | 0.00 |
June | 0.00 | 0.00 | 0.342709E+11 | 0.259854E+11 | 81621.61 | 27-JUN-13:05 | 61561.62 | 0.00 |
July | 0.00 | 0.00 | 0.594625E+11 | 0.421031E+11 | 113065.43 | 20-JUL-06:03 | 46799.38 | 0.00 |
August | 0.00 | 0.00 | 0.476860E+11 | 0.369715E+11 | 111688.50 | 14-AUG-06:03 | 42597.04 | 0.00 |
September | 0.00 | 0.00 | 0.194053E+11 | 0.144182E+11 | 74260.61 | 15-SEP-13:10 | 40901.12 | 0.00 |
October | 0.00 | 0.00 | 0.200516E+10 | 0.161117E+10 | 24872.07 | 11-OCT-15:00 | 24872.07 | 0.00 |
November | 0.00 | 0.00 | 0.319646E+09 | 0.209878E+09 | 9333.93 | 27-NOV-07:03 | 8060.60 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172914E+12 | 0.129899E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.594625E+11 | 0.421031E+11 | 113065.43 | 61561.62 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1974.57 | 6954.49 | 31-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2012.42 | 6979.95 | 14-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2117.52 | 6947.60 | 01-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1904.46 | 6711.66 | 06-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1870.50 | 6420.88 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1807.95 | 6005.72 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1584.27 | 5666.04 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1711.82 | 5499.70 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1625.85 | 5685.00 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1698.92 | 6025.73 | 30-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1826.46 | 6407.37 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1849.97 | 6741.96 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1831.03 | ||||
Minimum of Months | 0.00 | 0.00 | 1584.27 | 5499.70 | ||
Maximum of Months | 0.00 | 0.00 | 2117.52 | 6979.95 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126277E+10 | 0.33 | 2426.94 | 02-JAN-05:01 | 0.83 |
February | 0.111278E+10 | 0.32 | 2426.94 | 06-FEB-07:01 | 0.83 |
March | 0.119752E+10 | 0.32 | 1854.16 | 06-MAR-07:01 | 0.72 |
April | 0.121737E+10 | 0.30 | 1887.02 | 24-APR-16:00 | 0.73 |
May | 0.189355E+10 | 0.35 | 4771.14 | 31-MAY-06:03 | 1.22 |
June | 0.355953E+10 | 0.48 | 7309.20 | 12-JUN-15:10 | 1.58 |
July | 0.474075E+10 | 0.53 | 9975.98 | 17-JUL-05:12 | 1.92 |
August | 0.485755E+10 | 0.55 | 9975.98 | 14-AUG-05:12 | 1.92 |
September | 0.309446E+10 | 0.43 | 6583.46 | 18-SEP-12:20 | 1.49 |
October | 0.152425E+10 | 0.31 | 3861.26 | 11-OCT-16:00 | 1.07 |
November | 0.107985E+10 | 0.29 | 1530.15 | 01-NOV-12:08 | 0.66 |
December | 0.112247E+10 | 0.30 | 2426.94 | 11-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.266629E+11 | 0.38 | |||
Minimum of Months | 0.107985E+10 | 0.29 | 1530.15 | 0.66 | |
Maximum of Months | 0.485755E+10 | 0.55 | 9975.98 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122950E+10 | 0.34 | 2614.46 | 02-JAN-05:01 | 0.88 |
February | 0.110120E+10 | 0.34 | 2614.46 | 02-FEB-07:01 | 0.88 |
March | 0.119106E+10 | 0.32 | 2614.46 | 01-MAR-07:01 | 0.89 |
April | 0.120750E+10 | 0.31 | 2670.38 | 26-APR-14:05 | 0.89 |
May | 0.207815E+10 | 0.37 | 4897.90 | 23-MAY-14:30 | 1.27 |
June | 0.378683E+10 | 0.51 | 8877.44 | 12-JUN-06:03 | 1.84 |
July | 0.472520E+10 | 0.55 | 9585.76 | 05-JUL-16:00 | 1.92 |
August | 0.447848E+10 | 0.54 | 9585.76 | 07-AUG-06:03 | 1.93 |
September | 0.265847E+10 | 0.42 | 6955.21 | 21-SEP-15:40 | 1.57 |
October | 0.127960E+10 | 0.31 | 3409.05 | 11-OCT-15:30 | 1.02 |
November | 0.995374E+09 | 0.29 | 2614.46 | 24-NOV-07:01 | 0.88 |
December | 0.114926E+10 | 0.32 | 2614.46 | 04-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.258806E+11 | 0.39 | |||
Minimum of Months | 0.995374E+09 | 0.29 | 2614.46 | 0.88 | |
Maximum of Months | 0.472520E+10 | 0.55 | 9585.76 | 1.93 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158936E+10 | 0.42 | 2506.14 | 02-JAN-05:01 | 0.80 |
February | 0.144484E+10 | 0.42 | 2506.14 | 01-FEB-06:11 | 0.80 |
March | 0.136767E+10 | 0.37 | 2789.17 | 15-MAR-13:40 | 0.84 |
April | 0.124910E+10 | 0.33 | 2576.03 | 21-APR-14:50 | 0.81 |
May | 0.198114E+10 | 0.36 | 4550.53 | 31-MAY-16:00 | 1.11 |
June | 0.356617E+10 | 0.47 | 8639.14 | 12-JUN-06:03 | 1.64 |
July | 0.446919E+10 | 0.50 | 10972.39 | 17-JUL-05:12 | 1.91 |
August | 0.410121E+10 | 0.49 | 10972.39 | 14-AUG-05:12 | 1.91 |
September | 0.233174E+10 | 0.39 | 6438.85 | 21-SEP-15:30 | 1.37 |
October | 0.125880E+10 | 0.32 | 2841.27 | 11-OCT-15:20 | 0.85 |
November | 0.110481E+10 | 0.32 | 2506.14 | 13-NOV-06:11 | 0.80 |
December | 0.149200E+10 | 0.40 | 2506.14 | 02-DEC-06:11 | 0.80 |
Annual Sum or Average | 0.259560E+11 | 0.40 | |||
Minimum of Months | 0.110481E+10 | 0.32 | 2506.14 | 0.80 | |
Maximum of Months | 0.446919E+10 | 0.50 | 10972.39 | 1.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.49 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 55.01 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.21 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:02 | 2.06 | 2.06 | 56.23 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 55.85 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 55.75 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.39 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 55.85 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 55.89 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.44 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 55.55 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.33 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.01 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.49 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.49 | 57.49 | 1974.57 | 6954.49 | 31-JAN-12:09 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.96 | 55.96 | 2012.42 | 6979.95 | 14-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.73 | 56.73 | 2117.52 | 6947.60 | 01-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.78 | 56.78 | 1904.46 | 6711.66 | 06-APR-11:07 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.55 | 56.55 | 1870.50 | 6420.88 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.29 | 56.29 | 1807.95 | 6005.72 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.89 | 56.89 | 1584.27 | 5666.04 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.25 | 56.25 | 1711.82 | 5499.70 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.37 | 56.37 | 1625.85 | 5685.00 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.38 | 55.38 | 1698.92 | 6025.73 | 30-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.29 | 56.29 | 1826.46 | 6407.37 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.10 | 57.10 | 1849.97 | 6741.96 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1831.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.38 | 55.38 | 1584.27 | 5499.70 | ||
Maximum of Months | 0.00 | 0.00 | 57.49 | 57.49 | 2117.52 | 6979.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.227581E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.185131E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.963144E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.423996E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.417248E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.107131E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.171247E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.154742E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.794745E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.322523E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.524800E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.170371E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.136085E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.322523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227581E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.192343E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158362E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.539366E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.188497E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.372484E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.109716E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.169299E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.145070E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.696240E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.203026E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.354945E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158946E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.116919E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.188497E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.192343E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.311412E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.265485E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.108596E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.323667E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.373256E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.112015E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.175648E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.146889E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.670553E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.306999E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.819676E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.279200E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164866E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.306999E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.311412E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126277E+10 | 0.00 | 0.402639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111278E+10 | 0.00 | 0.347963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119752E+10 | 0.146241E+10 | 0.185865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121737E+10 | 0.576657E+09 | 0.628451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189355E+10 | 0.644437E+10 | 0.900635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355953E+10 | 0.314347E+11 | 0.163532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.474075E+10 | 0.563868E+11 | 9588266.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.485755E+10 | 0.480253E+11 | 31308479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.309446E+10 | 0.210612E+11 | 0.219571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152425E+10 | 0.233696E+10 | 0.290998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107985E+10 | 0.326649E+09 | 0.988592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112247E+10 | 0.00 | 0.321296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266629E+11 | 0.168055E+12 | 0.146181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107985E+10 | 0.00 | 9588266.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485755E+10 | 0.563868E+11 | 0.402639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122950E+10 | 0.00 | 0.359430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110120E+10 | 0.00 | 0.314230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119106E+10 | 0.160273E+10 | 0.143455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120750E+10 | 0.581458E+09 | 0.418318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207815E+10 | 0.702621E+10 | 0.217271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.378683E+10 | 0.323870E+11 | 11637935.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.472520E+10 | 0.556341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.447848E+10 | 0.454032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265847E+10 | 0.193602E+11 | 49990909.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127960E+10 | 0.211252E+10 | 0.242744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.995374E+09 | 0.304870E+09 | 0.866065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114926E+10 | 0.00 | 0.305512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258806E+11 | 0.164412E+12 | 0.127813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.995374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.472520E+10 | 0.556341E+11 | 0.359430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158936E+10 | 0.00 | 0.488742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144484E+10 | 0.00 | 0.430132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136767E+10 | 0.179456E+10 | 0.200620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124910E+10 | 0.607451E+09 | 0.576472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198114E+10 | 0.736236E+10 | 0.362781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356617E+10 | 0.342709E+11 | 36285120.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.446919E+10 | 0.594625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410121E+10 | 0.476860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.233174E+10 | 0.194053E+11 | 0.114992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125880E+10 | 0.200516E+10 | 0.386035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110481E+10 | 0.319646E+09 | 0.136567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149200E+10 | 0.00 | 0.435295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259560E+11 | 0.172914E+12 | 0.179275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.446919E+10 | 0.594625E+11 | 0.488742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119752E+10 | 0.00 | 0.00 | 0.00 | 0.346524E+09 | 0.808740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121737E+10 | 0.00 | 0.00 | 0.00 | 0.146775E+09 | 0.287582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189355E+10 | 0.00 | 0.00 | 0.00 | 0.152828E+10 | 0.750648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.355953E+10 | 0.00 | 0.00 | 0.00 | 0.699327E+10 | 0.160262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.474075E+10 | 0.00 | 0.00 | 0.00 | 0.123744E+11 | 9588266.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.485755E+10 | 0.00 | 0.00 | 0.00 | 0.105854E+11 | 31308479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.309446E+10 | 0.00 | 0.00 | 0.00 | 0.465616E+10 | 0.196829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152425E+10 | 0.00 | 0.00 | 0.00 | 0.565096E+09 | 0.113588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107985E+10 | 0.00 | 0.00 | 0.00 | 83396186.58 | 0.408476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266629E+11 | 0.00 | 0.00 | 0.00 | 0.372792E+11 | 0.721427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9588266.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485755E+10 | 0.00 | 0.00 | 0.00 | 0.123744E+11 | 0.214953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119106E+10 | 0.00 | 0.00 | 0.00 | 0.372020E+09 | 0.383058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120750E+10 | 0.00 | 0.00 | 0.00 | 0.146847E+09 | 0.530622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207815E+10 | 0.00 | 0.00 | 0.00 | 0.164669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.378683E+10 | 0.00 | 0.00 | 0.00 | 0.718481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.472520E+10 | 0.00 | 0.00 | 0.00 | 0.122047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.447848E+10 | 0.00 | 0.00 | 0.00 | 0.100285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265847E+10 | 0.00 | 0.00 | 0.00 | 0.430393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127960E+10 | 0.00 | 0.00 | 0.00 | 0.513207E+09 | 0.237460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.995374E+09 | 0.00 | 0.00 | 0.00 | 78005266.48 | 0.247608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258806E+11 | 0.00 | 0.00 | 0.00 | 0.364787E+11 | 0.545599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.995374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.472520E+10 | 0.00 | 0.00 | 0.00 | 0.122047E+11 | 0.180048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136767E+10 | 0.00 | 0.00 | 0.00 | 0.414990E+09 | 0.907698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124910E+10 | 0.00 | 0.00 | 0.00 | 0.153913E+09 | 0.183366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198114E+10 | 0.00 | 0.00 | 0.00 | 0.173229E+10 | 19133270.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356617E+10 | 0.00 | 0.00 | 0.00 | 0.763537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.446919E+10 | 0.00 | 0.00 | 0.00 | 0.130956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.410121E+10 | 0.00 | 0.00 | 0.00 | 0.105877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.233174E+10 | 0.00 | 0.00 | 0.00 | 0.435662E+10 | 17167846.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125880E+10 | 0.00 | 0.00 | 0.00 | 0.493480E+09 | 0.131770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110481E+10 | 0.00 | 0.00 | 0.00 | 82054615.56 | 0.700989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259560E+11 | 0.00 | 0.00 | 0.00 | 0.385520E+11 | 0.100358E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.446919E+10 | 0.00 | 0.00 | 0.00 | 0.130956E+11 | 0.295518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912617E+09 | 0.00 | 0.00 | 0.28 |
February | 0.158061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92978983.38 | 0.00 | 0.00 | 0.28 |
March | 0.100677E+11 | 5373135.60 | 0.00 | 6246190.03 | 0.00 | 771882.89 | 0.557174E+10 | 0.00 | 0.34 |
April | 0.416365E+10 | 0.00 | 0.00 | 15046013.81 | 0.00 | 0.00 | 0.995646E+10 | 0.00 | 0.40 |
May | 0.934673E+09 | 1114581.61 | 0.00 | 30268792.29 | 5506137.79 | 0.00 | 0.148948E+11 | 0.00 | 0.68 |
June | 0.535779E+09 | 0.136542E+10 | 0.00 | 28184854.42 | 0.142729E+09 | 0.00 | 0.970690E+10 | 0.00 | 0.87 |
July | 0.214004E+09 | 0.473400E+10 | 0.00 | 15415862.25 | 0.343366E+09 | 0.00 | 0.301243E+10 | 0.00 | 0.70 |
August | 0.420733E+09 | 0.260050E+10 | 0.00 | 28077804.58 | 0.107982E+09 | 0.00 | 0.645490E+10 | 0.00 | 0.83 |
September | 0.106692E+10 | 0.847003E+09 | 0.00 | 29735682.72 | 17330669.21 | 0.00 | 0.115588E+11 | 0.00 | 0.86 |
October | 0.186311E+10 | 0.00 | 0.00 | 24689329.97 | 465101.56 | 0.00 | 0.137760E+11 | 0.00 | 0.50 |
November | 0.536888E+10 | 0.00 | 0.00 | 10182500.07 | 3908354.18 | 0.00 | 0.817413E+10 | 0.00 | 0.33 |
December | 0.157703E+11 | 0.00 | 0.00 | 344026.57 | 0.00 | 95274107.66 | 0.334777E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.723187E+11 | 0.955341E+10 | 0.00 | 0.188191E+09 | 0.621287E+09 | 0.110164E+10 | 0.834409E+11 | 0.00 | 0.53 |
Minimum of Months | 0.214004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.161069E+11 | 0.473400E+10 | 0.00 | 30268792.29 | 0.343366E+09 | 0.912617E+09 | 0.148948E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311530E+10 | 0.00 | 0.00 | 0.28 |
February | 0.130626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276908E+10 | 0.00 | 0.00 | 0.28 |
March | 0.138443E+11 | 331584.38 | 0.00 | 1592410.53 | 5944263.75 | 0.152929E+09 | 0.902231E+09 | 0.00 | 0.32 |
April | 0.816258E+10 | 0.00 | 0.00 | 4641685.14 | 0.00 | 22155505.41 | 0.385936E+10 | 0.00 | 0.34 |
May | 0.292777E+10 | 64244.98 | 0.00 | 17914279.08 | 19276301.98 | 0.00 | 0.975498E+10 | 0.00 | 0.55 |
June | 0.721450E+09 | 0.117980E+10 | 0.00 | 20324468.64 | 0.159691E+09 | 0.00 | 0.722032E+10 | 0.00 | 0.69 |
July | 0.296463E+09 | 0.401490E+10 | 0.00 | 11770886.47 | 0.369529E+09 | 0.00 | 0.227684E+10 | 0.00 | 0.59 |
August | 0.545355E+09 | 0.215791E+10 | 0.00 | 20594961.66 | 0.136363E+09 | 0.00 | 0.472743E+10 | 0.00 | 0.66 |
September | 0.163083E+10 | 0.670359E+09 | 0.00 | 18721399.98 | 20034128.07 | 0.00 | 0.762550E+10 | 0.00 | 0.64 |
October | 0.646857E+10 | 0.00 | 0.00 | 7396060.29 | 1872554.68 | 0.00 | 0.518073E+10 | 0.00 | 0.37 |
November | 0.110535E+11 | 0.00 | 0.00 | 471881.74 | 6622805.01 | 47377663.64 | 0.753971E+09 | 0.00 | 0.30 |
December | 0.139315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208799E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.866397E+11 | 0.802337E+10 | 0.00 | 0.103428E+09 | 0.719334E+09 | 0.819484E+10 | 0.423014E+11 | 0.00 | 0.44 |
Minimum of Months | 0.296463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.139949E+11 | 0.401490E+10 | 0.00 | 20594961.66 | 0.369529E+09 | 0.311530E+10 | 0.975498E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.761330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826758E+10 | 0.00 | 0.00 | 0.27 |
February | 0.815552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666880E+10 | 0.00 | 0.00 | 0.27 |
March | 0.118570E+11 | 129465.79 | 0.00 | 1515127.47 | 112395.80 | 0.148582E+10 | 0.811557E+09 | 0.00 | 0.32 |
April | 0.872278E+10 | 0.00 | 0.00 | 2869498.73 | 0.00 | 0.167355E+09 | 0.273295E+10 | 0.00 | 0.34 |
May | 0.363867E+10 | 682653.16 | 0.00 | 15913147.16 | 16567440.74 | 0.00 | 0.886791E+10 | 0.00 | 0.54 |
June | 0.103706E+10 | 0.114122E+10 | 0.00 | 19503731.54 | 0.168271E+09 | 0.00 | 0.707078E+10 | 0.00 | 0.73 |
July | 0.427361E+09 | 0.408050E+10 | 0.00 | 11458993.81 | 0.358032E+09 | 0.00 | 0.214950E+10 | 0.00 | 0.63 |
August | 0.764941E+09 | 0.215724E+10 | 0.00 | 18755838.01 | 0.191167E+09 | 0.00 | 0.418885E+10 | 0.00 | 0.68 |
September | 0.247855E+10 | 0.634854E+09 | 0.00 | 13964802.21 | 35373904.90 | 0.00 | 0.588249E+10 | 0.00 | 0.61 |
October | 0.750043E+10 | 0.00 | 0.00 | 3953151.58 | 0.00 | 0.107194E+09 | 0.298495E+10 | 0.00 | 0.35 |
November | 0.102282E+11 | 0.00 | 403408.86 | 47805.86 | 10193629.03 | 0.669816E+09 | 0.104243E+09 | 29539.32 | 0.30 |
December | 0.813668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662578E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.705605E+11 | 0.801462E+10 | 403408.86 | 87982096.37 | 0.779719E+09 | 0.239923E+11 | 0.347932E+11 | 29539.32 | 0.44 |
Minimum of Months | 0.427361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.118570E+11 | 0.408050E+10 | 403408.86 | 19503731.54 | 0.358032E+09 | 0.826758E+10 | 0.886791E+10 | 29539.32 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 47803831.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403386E+10 | 0.00 | 0.00 | 0.32 |
February | 0.136456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363854E+10 | 0.00 | 0.00 | 0.32 |
March | 0.117546E+10 | 55203.08 | 0.00 | 296258.07 | 0.00 | 0.188046E+10 | 96901120.50 | 0.00 | 0.34 |
April | 0.180908E+10 | 0.00 | 0.00 | 359731.03 | 0.00 | 0.383916E+09 | 0.268138E+09 | 0.00 | 0.34 |
May | 0.103461E+10 | 0.00 | 0.00 | 3376298.48 | 3636699.91 | 1000921.74 | 0.171008E+10 | 0.00 | 0.59 |
June | 0.290828E+09 | 0.392882E+09 | 0.00 | 5200323.56 | 31239915.21 | 0.00 | 0.171122E+10 | 0.00 | 0.94 |
July | 99303970.02 | 0.132850E+10 | 0.00 | 3272998.44 | 65275551.47 | 0.00 | 0.574815E+09 | 0.00 | 0.85 |
August | 0.246915E+09 | 0.661517E+09 | 0.00 | 4835990.51 | 35771139.35 | 0.00 | 0.960496E+09 | 0.00 | 0.87 |
September | 0.742883E+09 | 0.168526E+09 | 0.00 | 2730725.33 | 10662354.01 | 4276004.57 | 0.104186E+10 | 0.00 | 0.67 |
October | 0.169415E+10 | 0.00 | 0.00 | 401087.54 | 0.00 | 0.261498E+09 | 0.262362E+09 | 0.00 | 0.35 |
November | 0.961200E+09 | 0.00 | 566475.31 | 0.00 | 1706966.82 | 0.139920E+10 | 0.00 | 11182.77 | 0.30 |
December | 0.142258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357204E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.838095E+10 | 0.255148E+10 | 566475.31 | 20473412.96 | 0.148293E+09 | 0.151748E+11 | 0.662587E+10 | 11182.77 | 0.52 |
Minimum of Months | 47803831.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.180908E+10 | 0.132850E+10 | 566475.31 | 5200323.56 | 65275551.47 | 0.403386E+10 | 0.171122E+10 | 11182.77 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 55691103.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244169E+10 | 0.00 | 0.00 | 0.31 |
February | 0.358074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194309E+10 | 0.00 | 0.00 | 0.31 |
March | 0.106117E+10 | 68186.02 | 0.00 | 490876.66 | 0.00 | 0.729148E+09 | 0.183957E+09 | 0.00 | 0.35 |
April | 0.921021E+09 | 0.00 | 0.00 | 1939181.84 | 0.00 | 0.109433E+09 | 0.110218E+10 | 0.00 | 0.48 |
May | 0.441604E+09 | 23366.62 | 0.00 | 5185833.92 | 2277537.83 | 261015.37 | 0.259093E+10 | 0.00 | 1.01 |
June | 0.121838E+09 | 0.364291E+09 | 0.00 | 6152522.54 | 8160696.36 | 0.00 | 0.224576E+10 | 0.00 | 1.48 |
July | 40065475.94 | 0.113076E+10 | 0.00 | 5036262.65 | 34785585.92 | 0.00 | 0.881552E+09 | 0.00 | 1.38 |
August | 0.105087E+09 | 0.532032E+09 | 0.00 | 5746196.01 | 15974723.86 | 0.00 | 0.120204E+10 | 0.00 | 1.36 |
September | 0.350915E+09 | 0.146605E+09 | 0.00 | 4070100.96 | 4286344.24 | 1105548.48 | 0.158108E+10 | 0.00 | 1.07 |
October | 0.944043E+09 | 0.00 | 0.00 | 965307.29 | 0.00 | 0.100242E+09 | 0.526533E+09 | 0.00 | 0.41 |
November | 0.741580E+09 | 0.00 | 366194.37 | 11756.50 | 1079981.20 | 0.738265E+09 | 12385152.89 | 6340.29 | 0.30 |
December | 0.110893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220234E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.525199E+10 | 0.217378E+10 | 366194.37 | 29598038.36 | 66564869.41 | 0.826558E+10 | 0.103264E+11 | 6340.29 | 0.73 |
Minimum of Months | 40065475.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.106117E+10 | 0.113076E+10 | 366194.37 | 6152522.54 | 34785585.92 | 0.244169E+10 | 0.259093E+10 | 6340.29 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.760285E+09 | 0.00 | 0.00 | 272030.82 | 0.00 | 0.288558E+10 | 0.212521E+09 | 0.00 | 0.31 |
February | 0.884517E+09 | 0.00 | 0.00 | 505985.33 | 0.00 | 0.243860E+10 | 0.401081E+09 | 0.00 | 0.32 |
March | 0.144493E+10 | 297767.02 | 0.00 | 2546803.60 | 0.00 | 0.938997E+09 | 0.137775E+10 | 0.00 | 0.43 |
April | 0.138597E+10 | 0.00 | 0.00 | 3554664.69 | 0.00 | 0.266002E+09 | 0.203672E+10 | 0.00 | 0.53 |
May | 0.869119E+09 | 3528408.65 | 0.00 | 6606559.51 | 1464366.92 | 6550513.82 | 0.320829E+10 | 0.00 | 0.89 |
June | 0.320184E+09 | 0.457166E+09 | 0.00 | 6747310.72 | 21009271.81 | 0.00 | 0.224936E+10 | 0.00 | 1.15 |
July | 0.116868E+09 | 0.160115E+10 | 0.00 | 4541195.29 | 59235552.06 | 0.00 | 0.712085E+09 | 0.00 | 1.03 |
August | 0.229352E+09 | 0.835909E+09 | 0.00 | 7598399.43 | 23085523.02 | 0.00 | 0.142146E+10 | 0.00 | 1.18 |
September | 0.508336E+09 | 0.253919E+09 | 0.00 | 8214149.83 | 9627289.90 | 1230416.49 | 0.287984E+10 | 0.00 | 1.25 |
October | 0.127227E+10 | 0.00 | 0.00 | 4334688.51 | 0.00 | 0.130868E+09 | 0.219102E+10 | 0.00 | 0.64 |
November | 0.116090E+10 | 0.00 | 373585.00 | 1192640.37 | 1911899.86 | 0.899736E+09 | 0.628969E+09 | 8410.47 | 0.34 |
December | 0.610749E+09 | 0.00 | 0.00 | 143058.87 | 0.00 | 0.276966E+10 | 0.128064E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.956348E+10 | 0.315197E+10 | 373585.00 | 46257486.97 | 0.116334E+09 | 0.103372E+11 | 0.174472E+11 | 8410.47 | 0.70 |
Minimum of Months | 0.116868E+09 | 0.00 | 0.00 | 143058.87 | 0.00 | 0.00 | 0.128064E+09 | 0.00 | 0.30 |
Maximum of Months | 0.144493E+10 | 0.160115E+10 | 373585.00 | 8214149.83 | 59235552.06 | 0.288558E+10 | 0.320829E+10 | 8410.47 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245760E+10 | 0.00 | 0.00 | 0.33 |
February | 0.269302E+09 | 0.00 | 0.00 | 16301.73 | 0.00 | 0.211862E+10 | 18311454.44 | 0.00 | 0.33 |
March | 0.877943E+09 | 43444.24 | 0.00 | 561112.01 | 0.00 | 0.904684E+09 | 0.320552E+09 | 0.00 | 0.36 |
April | 0.932001E+09 | 0.00 | 0.00 | 1813721.60 | 0.00 | 0.204546E+09 | 0.108616E+10 | 0.00 | 0.50 |
May | 0.511656E+09 | 1562724.00 | 0.00 | 5167274.90 | 1486862.79 | 2441107.05 | 0.242147E+10 | 0.00 | 1.02 |
June | 0.166940E+09 | 0.360750E+09 | 0.00 | 6199400.57 | 12254900.70 | 0.00 | 0.189058E+10 | 0.00 | 1.49 |
July | 70125489.97 | 0.116983E+10 | 0.00 | 3514998.98 | 22067913.11 | 0.00 | 0.492390E+09 | 0.00 | 1.19 |
August | 0.144194E+09 | 0.575380E+09 | 0.00 | 4971314.97 | 8714221.52 | 0.00 | 0.851945E+09 | 0.00 | 1.22 |
September | 0.373797E+09 | 0.135041E+09 | 0.00 | 3861436.69 | 4730744.07 | 2673765.24 | 0.129903E+10 | 0.00 | 1.00 |
October | 0.962770E+09 | 0.00 | 0.00 | 1003487.57 | 0.00 | 0.132352E+09 | 0.551134E+09 | 0.00 | 0.44 |
November | 0.676907E+09 | 0.00 | 365922.95 | 47070.06 | 1080734.18 | 0.796586E+09 | 35870868.41 | 6692.56 | 0.30 |
December | 0.154454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221306E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.528941E+10 | 0.224261E+10 | 365922.95 | 27156119.08 | 50335376.38 | 0.883257E+10 | 0.896744E+10 | 6692.56 | 0.71 |
Minimum of Months | 70125489.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.962770E+09 | 0.116983E+10 | 365922.95 | 6199400.57 | 22067913.11 | 0.245760E+10 | 0.242147E+10 | 6692.56 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53360498.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407181E+10 | 0.00 | 0.00 | 0.31 |
February | 81020382.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376263E+10 | 0.00 | 0.00 | 0.32 |
March | 0.112138E+10 | 0.00 | 0.00 | 6507.55 | 1000771.22 | 0.216620E+10 | 1285538.10 | 0.00 | 0.33 |
April | 0.198735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422370E+09 | 0.00 | 0.00 | 0.32 |
May | 0.160475E+10 | 8464.16 | 0.00 | 843569.75 | 1349887.41 | 927654.92 | 0.469758E+09 | 0.00 | 0.42 |
June | 0.330501E+09 | 0.270648E+09 | 0.00 | 3374161.63 | 36602232.73 | 0.00 | 0.110277E+10 | 0.00 | 0.65 |
July | 91592504.33 | 0.992487E+09 | 0.00 | 2410594.65 | 80929044.37 | 0.00 | 0.436161E+09 | 0.00 | 0.63 |
August | 0.221978E+09 | 0.552556E+09 | 0.00 | 4124127.63 | 24218484.46 | 0.00 | 0.854068E+09 | 0.00 | 0.71 |
September | 0.707841E+09 | 0.152337E+09 | 0.00 | 2667374.62 | 4755229.27 | 0.00 | 0.104314E+10 | 0.00 | 0.62 |
October | 0.193999E+10 | 0.00 | 0.00 | 496867.63 | 98224.80 | 32068385.14 | 0.325687E+09 | 0.00 | 0.34 |
November | 0.196156E+10 | 0.00 | 18472.53 | 0.00 | 807107.34 | 0.596152E+09 | 0.00 | 3811.44 | 0.29 |
December | 0.293483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342163E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.103948E+11 | 0.196804E+10 | 18472.53 | 13923203.47 | 0.149761E+09 | 0.144738E+11 | 0.423287E+10 | 3811.44 | 0.44 |
Minimum of Months | 53360498.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.198735E+10 | 0.992487E+09 | 18472.53 | 4124127.63 | 80929044.37 | 0.407181E+10 | 0.110277E+10 | 3811.44 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 78014620.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250351E+10 | 0.00 | 0.00 | 0.31 |
February | 0.295381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210077E+10 | 0.00 | 0.00 | 0.31 |
March | 0.122397E+10 | 544924.58 | 0.00 | 91811.88 | 94418.47 | 0.784123E+09 | 28133565.38 | 0.00 | 0.32 |
April | 0.106921E+10 | 0.00 | 0.00 | 1052431.07 | 0.00 | 93444061.43 | 0.599109E+09 | 0.00 | 0.37 |
May | 0.569798E+09 | 50091.45 | 0.00 | 3239575.37 | 816533.57 | 0.00 | 0.153191E+10 | 0.00 | 0.71 |
June | 0.120152E+09 | 0.283062E+09 | 0.00 | 4861378.63 | 15364662.19 | 0.00 | 0.172870E+10 | 0.00 | 1.16 |
July | 34870024.60 | 0.934984E+09 | 0.00 | 3907018.33 | 44792975.84 | 0.00 | 0.744870E+09 | 0.00 | 1.11 |
August | 0.103003E+09 | 0.480585E+09 | 0.00 | 5324589.36 | 14105441.04 | 0.00 | 0.112988E+10 | 0.00 | 1.18 |
September | 0.265000E+09 | 0.138408E+09 | 0.00 | 4374682.25 | 2829639.64 | 0.00 | 0.169650E+10 | 0.00 | 1.05 |
October | 0.922848E+09 | 0.00 | 0.00 | 1419703.75 | 62373.38 | 10443281.32 | 0.771487E+09 | 0.00 | 0.42 |
November | 0.128785E+10 | 0.00 | 10786.33 | 65863.94 | 512518.36 | 0.291037E+09 | 53391007.69 | 833.02 | 0.30 |
December | 0.201671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214337E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.617177E+10 | 0.183763E+10 | 10786.33 | 24337054.59 | 78578562.48 | 0.792670E+10 | 0.828398E+10 | 833.02 | 0.63 |
Minimum of Months | 34870024.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.128785E+10 | 0.934984E+09 | 10786.33 | 5324589.36 | 44792975.84 | 0.250351E+10 | 0.172870E+10 | 833.02 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564526E+10 | 0.00 | 0.00 | 0.44 |
February | 0.248198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510937E+10 | 0.00 | 0.00 | 0.44 |
March | 0.134450E+10 | 2717699.11 | 0.00 | 210493.29 | 0.00 | 0.280249E+10 | 28216509.38 | 0.00 | 0.41 |
April | 0.150488E+10 | 0.00 | 0.00 | 534538.48 | 0.00 | 0.120535E+10 | 0.336412E+09 | 0.00 | 0.40 |
May | 0.142042E+10 | 86504.33 | 0.00 | 1647643.90 | 1286433.11 | 0.339541E+09 | 0.688684E+09 | 0.00 | 0.52 |
June | 0.578374E+09 | 0.336631E+09 | 0.00 | 3085250.70 | 41295043.15 | 77196634.74 | 0.861694E+09 | 0.00 | 0.73 |
July | 0.149397E+09 | 0.129952E+10 | 0.00 | 2703802.54 | 79372974.13 | 6846063.14 | 0.404827E+09 | 0.00 | 0.74 |
August | 0.335551E+09 | 0.775401E+09 | 0.00 | 5680783.33 | 22009106.30 | 19411325.76 | 0.908140E+09 | 0.00 | 0.94 |
September | 0.537739E+09 | 0.232368E+09 | 0.00 | 6398546.30 | 6639202.35 | 0.103997E+09 | 0.209445E+10 | 0.00 | 1.04 |
October | 0.144285E+10 | 44386.52 | 0.00 | 2325154.99 | 76692.91 | 0.557956E+09 | 0.121394E+10 | 0.00 | 0.54 |
November | 0.126145E+10 | 0.00 | 63972.98 | 268382.23 | 759233.17 | 0.184719E+10 | 0.210138E+09 | 2562.86 | 0.37 |
December | 0.231288E+09 | 0.00 | 0.00 | 16580.29 | 0.00 | 0.492149E+10 | 18528312.38 | 0.00 | 0.41 |
Annual Sum or Average | 0.930590E+10 | 0.264677E+10 | 63972.98 | 22871176.07 | 0.151439E+09 | 0.226361E+11 | 0.676503E+10 | 2562.86 | 0.58 |
Minimum of Months | 0.149397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6846063.14 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.150488E+10 | 0.129952E+10 | 63972.98 | 6398546.30 | 79372974.13 | 0.564526E+10 | 0.209445E+10 | 2562.86 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250740E+10 | 0.00 | 0.00 | 0.32 |
February | 0.222708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223636E+10 | 0.00 | 0.00 | 0.32 |
March | 0.111157E+10 | 114009.16 | 0.00 | 85091.78 | 519867.70 | 0.888156E+09 | 52758468.26 | 0.00 | 0.32 |
April | 0.114542E+10 | 0.00 | 0.00 | 773984.01 | 0.00 | 0.144085E+09 | 0.444789E+09 | 0.00 | 0.37 |
May | 0.664036E+09 | 152291.47 | 0.00 | 2849579.23 | 814452.96 | 260959.21 | 0.127500E+10 | 0.00 | 0.68 |
June | 0.137344E+09 | 0.295485E+09 | 0.00 | 4680645.43 | 15149995.10 | 0.00 | 0.146788E+10 | 0.00 | 1.17 |
July | 46716405.18 | 0.967513E+09 | 0.00 | 2840015.09 | 28250061.25 | 0.00 | 0.433161E+09 | 0.00 | 0.95 |
August | 0.104649E+09 | 0.534791E+09 | 0.00 | 4494614.27 | 8336289.53 | 0.00 | 0.830206E+09 | 0.00 | 1.07 |
September | 0.296951E+09 | 0.124558E+09 | 0.00 | 3918969.54 | 2187530.37 | 0.00 | 0.136196E+10 | 0.00 | 0.96 |
October | 0.101424E+10 | 0.00 | 0.00 | 1179771.02 | 62214.45 | 16133560.08 | 0.629907E+09 | 0.00 | 0.42 |
November | 0.126848E+10 | 0.00 | 10839.38 | 41384.85 | 511212.41 | 0.320460E+09 | 38741307.77 | 750.36 | 0.30 |
December | 0.254653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210908E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.641196E+10 | 0.192261E+10 | 10839.38 | 20864055.23 | 55831623.76 | 0.822194E+10 | 0.653440E+10 | 750.36 | 0.60 |
Minimum of Months | 46716405.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.126848E+10 | 0.967513E+09 | 10839.38 | 4680645.43 | 28250061.25 | 0.250740E+10 | 0.146788E+10 | 750.36 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381825E+10 | 0.00 | 0.00 | 0.30 |
February | 0.383737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331977E+10 | 0.00 | 0.00 | 0.31 |
March | 0.164762E+10 | 829784.66 | 0.00 | 286248.42 | 513227.38 | 0.143054E+10 | 0.109129E+09 | 0.00 | 0.33 |
April | 0.201141E+10 | 0.00 | 0.00 | 388260.16 | 0.00 | 0.178299E+09 | 0.315476E+09 | 0.00 | 0.34 |
May | 0.945765E+09 | 13745.72 | 0.00 | 3695499.19 | 4072741.05 | 0.00 | 0.176824E+10 | 0.00 | 0.59 |
June | 0.219643E+09 | 0.407715E+09 | 0.00 | 5207259.97 | 34292893.28 | 0.00 | 0.171169E+10 | 0.00 | 0.90 |
July | 83140939.16 | 0.131704E+10 | 0.00 | 3168063.44 | 75956005.46 | 0.00 | 0.570481E+09 | 0.00 | 0.79 |
August | 0.208974E+09 | 0.660856E+09 | 0.00 | 4946765.97 | 28605634.31 | 0.00 | 0.100683E+10 | 0.00 | 0.83 |
September | 0.664598E+09 | 0.183628E+09 | 0.00 | 3176630.96 | 4809006.00 | 0.00 | 0.121542E+10 | 0.00 | 0.69 |
October | 0.188757E+10 | 0.00 | 0.00 | 662645.43 | 395209.06 | 75469335.90 | 0.396755E+09 | 0.00 | 0.36 |
November | 0.175175E+10 | 0.00 | 43396.99 | 0.00 | 1362655.83 | 0.758995E+09 | 0.00 | 4258.07 | 0.30 |
December | 0.329224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332402E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.102744E+11 | 0.257008E+10 | 43396.99 | 21531373.54 | 0.150007E+09 | 0.129053E+11 | 0.709402E+10 | 4258.07 | 0.50 |
Minimum of Months | 83140939.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.201141E+10 | 0.131704E+10 | 43396.99 | 5207259.97 | 75956005.46 | 0.381825E+10 | 0.176824E+10 | 4258.07 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198867E+10 | 0.00 | 0.00 | 0.26 |
February | 0.391806E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161238E+10 | 0.00 | 0.00 | 0.26 |
March | 0.995469E+09 | 1339548.60 | 0.00 | 480596.98 | 2407.57 | 0.527771E+09 | 0.211085E+09 | 0.00 | 0.30 |
April | 0.840536E+09 | 0.00 | 0.00 | 2085138.20 | 0.00 | 52631560.52 | 0.114960E+10 | 0.00 | 0.45 |
May | 0.399797E+09 | 30658.22 | 0.00 | 5170462.12 | 2568020.27 | 0.00 | 0.245116E+10 | 0.00 | 0.96 |
June | 98302877.88 | 0.357554E+09 | 0.00 | 5860819.20 | 10255052.51 | 0.00 | 0.209775E+10 | 0.00 | 1.35 |
July | 31126007.91 | 0.105227E+10 | 0.00 | 4663685.97 | 41388294.64 | 0.00 | 0.849090E+09 | 0.00 | 1.23 |
August | 0.103896E+09 | 0.494410E+09 | 0.00 | 5591311.17 | 16762414.75 | 0.00 | 0.117467E+10 | 0.00 | 1.23 |
September | 0.285755E+09 | 0.145033E+09 | 0.00 | 4306391.61 | 2752381.57 | 0.00 | 0.163716E+10 | 0.00 | 1.03 |
October | 0.844661E+09 | 0.00 | 0.00 | 1292339.21 | 251157.91 | 30867653.90 | 0.653354E+09 | 0.00 | 0.39 |
November | 0.885966E+09 | 0.00 | 23795.34 | 64291.47 | 865976.58 | 0.408094E+09 | 41530462.17 | 2326.50 | 0.25 |
December | 0.184323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183312E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.525559E+10 | 0.205063E+10 | 23795.34 | 29515035.93 | 74845705.79 | 0.645353E+10 | 0.102654E+11 | 2326.50 | 0.67 |
Minimum of Months | 31126007.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.995469E+09 | 0.105227E+10 | 23795.34 | 5860819.20 | 41388294.64 | 0.198867E+10 | 0.245116E+10 | 2326.50 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104539E+10 | 0.00 | 0.00 | 444802.31 | 0.00 | 0.260523E+10 | 0.323880E+09 | 0.00 | 0.31 |
February | 0.118683E+10 | 0.00 | 0.00 | 647703.67 | 0.00 | 0.215930E+10 | 0.471403E+09 | 0.00 | 0.32 |
March | 0.180683E+10 | 6765008.88 | 0.00 | 2844646.15 | 0.00 | 0.581208E+09 | 0.161133E+10 | 0.00 | 0.43 |
April | 0.154712E+10 | 0.00 | 0.00 | 3848542.92 | 0.00 | 0.120471E+09 | 0.202708E+10 | 0.00 | 0.54 |
May | 0.808327E+09 | 4110146.27 | 0.00 | 6872288.40 | 986441.49 | 0.00 | 0.311361E+10 | 0.00 | 0.88 |
June | 0.265705E+09 | 0.471216E+09 | 0.00 | 6591565.24 | 27377469.96 | 0.00 | 0.212144E+10 | 0.00 | 1.09 |
July | 0.100397E+09 | 0.159054E+10 | 0.00 | 3920159.41 | 62631762.76 | 0.00 | 0.643920E+09 | 0.00 | 0.93 |
August | 0.206717E+09 | 0.836775E+09 | 0.00 | 7422147.66 | 24054326.60 | 0.00 | 0.136774E+10 | 0.00 | 1.11 |
September | 0.477320E+09 | 0.278866E+09 | 0.00 | 8634715.24 | 4356941.97 | 0.00 | 0.290658E+10 | 0.00 | 1.26 |
October | 0.125912E+10 | 378163.30 | 0.00 | 5422591.88 | 113928.11 | 38027202.65 | 0.259332E+10 | 0.00 | 0.69 |
November | 0.163242E+10 | 0.00 | 33915.69 | 1645525.98 | 1364401.72 | 0.523904E+09 | 0.846612E+09 | 1239.06 | 0.37 |
December | 0.995283E+09 | 0.00 | 0.00 | 212371.95 | 0.00 | 0.244413E+10 | 0.173580E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.113315E+11 | 0.318865E+10 | 33915.69 | 48507060.80 | 0.120885E+09 | 0.847227E+10 | 0.182005E+11 | 1239.06 | 0.69 |
Minimum of Months | 0.100397E+09 | 0.00 | 0.00 | 212371.95 | 0.00 | 0.00 | 0.173580E+09 | 0.00 | 0.30 |
Maximum of Months | 0.180683E+10 | 0.159054E+10 | 33915.69 | 8634715.24 | 62631762.76 | 0.260523E+10 | 0.311361E+10 | 1239.06 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.258391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227488E+10 | 0.00 | 0.00 | 0.31 |
February | 0.444024E+09 | 0.00 | 0.00 | 18392.78 | 0.00 | 0.190838E+10 | 19471959.57 | 0.00 | 0.31 |
March | 0.114916E+10 | 743804.55 | 0.00 | 601989.71 | 323677.55 | 0.634704E+09 | 0.357891E+09 | 0.00 | 0.35 |
April | 0.104804E+10 | 0.00 | 0.00 | 1883846.54 | 0.00 | 96284582.15 | 0.105052E+10 | 0.00 | 0.50 |
May | 0.460783E+09 | 590075.38 | 0.00 | 5332174.44 | 1994471.04 | 0.00 | 0.234030E+10 | 0.00 | 1.01 |
June | 0.140145E+09 | 0.385329E+09 | 0.00 | 5858183.73 | 12780376.65 | 0.00 | 0.177206E+10 | 0.00 | 1.41 |
July | 56189497.47 | 0.117823E+10 | 0.00 | 3217809.82 | 24010809.50 | 0.00 | 0.452128E+09 | 0.00 | 1.09 |
August | 0.121652E+09 | 0.567913E+09 | 0.00 | 4808116.39 | 9067878.46 | 0.00 | 0.840332E+09 | 0.00 | 1.14 |
September | 0.340414E+09 | 0.148907E+09 | 0.00 | 4128178.49 | 1503112.61 | 0.00 | 0.134825E+10 | 0.00 | 1.02 |
October | 0.102648E+10 | 0.00 | 0.00 | 1324216.56 | 249246.83 | 39804381.60 | 0.679766E+09 | 0.00 | 0.46 |
November | 0.110152E+10 | 0.00 | 23642.68 | 83059.38 | 859387.32 | 0.434082E+09 | 67986773.61 | 2311.18 | 0.30 |
December | 0.304814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202277E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.645161E+10 | 0.228172E+10 | 23642.68 | 27255967.84 | 50788959.96 | 0.741091E+10 | 0.892870E+10 | 2311.18 | 0.68 |
Minimum of Months | 56189497.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.114916E+10 | 0.117823E+10 | 23642.68 | 5858183.73 | 24010809.50 | 0.227488E+10 | 0.234030E+10 | 2311.18 | 1.41 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.127344E+12 | 0.308260E+11 | 0.00 | 0.132047E+12 | 0.106722E+11 |
February | 0.201925E+12 | 0.315859E+11 | 0.00 | 0.123129E+12 | 0.990352E+10 |
March | 0.304878E+12 | 0.217630E+11 | 0.00 | 0.155139E+12 | 0.120883E+11 |
April | 0.363951E+12 | 0.172786E+11 | 0.00 | 0.184276E+12 | 0.430687E+10 |
May | 0.445741E+12 | 0.103541E+11 | 0.00 | 0.202784E+12 | 0.258756E+11 |
June | 0.481185E+12 | 0.401071E+10 | 0.00 | 0.114829E+12 | 0.119916E+12 |
July | 0.448345E+12 | -920516083.7 | 0.00 | 0.129372E+11 | 0.209158E+12 |
August | 0.383812E+12 | 0.148695E+10 | 0.00 | 0.794316E+11 | 0.172316E+12 |
September | 0.294151E+12 | 0.582737E+10 | 0.00 | 0.162737E+12 | 0.731759E+11 |
October | 0.199268E+12 | 0.141829E+11 | 0.00 | 0.191867E+12 | 0.926580E+10 |
November | 0.102149E+12 | 0.185514E+11 | 0.00 | 0.150746E+12 | 0.474367E+10 |
December | 0.113208E+12 | 0.318093E+11 | 0.00 | 0.133849E+12 | 0.935664E+10 |
Annual Sum or Average | 0.346596E+13 | 0.186756E+12 | 0.00 | 0.164377E+13 | 0.660779E+12 |
Minimum of Months | 0.102149E+12 | -920516083.7 | 0.00 | 0.129372E+11 | 0.430687E+10 |
Maximum of Months | 0.481185E+12 | 0.318093E+11 | 0.00 | 0.202784E+12 | 0.209158E+12 |