Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:32:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1917.74 | 384.92 | 384.92 |
Net Site Energy | 1813.96 | 364.09 | 364.09 |
Total Source Energy | 5274.36 | 1058.64 | 1058.64 |
Net Source Energy | 4945.67 | 992.67 | 992.67 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 517.47 | 234.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 172.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 149.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1534.10 | 383.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 517.47 | 234.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 172.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 78.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 149.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 517.47 | 234.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 46.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 172.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 78.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 149.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 128.95 | 77.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 136.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 307.92 | 77.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 128.95 | 77.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 136.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 307.92 | 77.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 109.323 | 7.13 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.54 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 103.787 | 6.77 |
Electricity Coming From Utility | 1430.826 | 93.27 |
Surplus Electricity Going To Utility | 0.514 | 0.03 |
Net Electricity From Utility | 1430.312 | 93.23 |
Total On-Site and Utility Electric Sources | 1534.099 | 100.00 |
Total Electricity End Uses | 1534.099 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.19 | 0.04 |
Air to Air Heat Recovery for Heating | 473.35 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 473.54 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 748.17 |
Time Setpoint Not Met During Occupied Cooling | 60.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3360.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 12-JAN-07:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 179233.33 | 202340.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 40437.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 814.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6026.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9002.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 250223.45 | 211342.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 179233.33 | 202340.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 814.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6026.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 9002.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1638.81 | 253.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 147.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 547.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 118.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 69.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 161.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4858.49 | 415.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 328.93 | 50.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 109.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 32.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 975.17 | 83.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 328.93 | 50.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 109.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 49.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 32.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 975.17 | 83.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.43 | 0.307958 | 0.262000 | 0.637610 | 0.821222 | 0.500000 | 0.001237 |
CORE_MID VAV BOX COMPONENT | 2.06 | 0.364366 | 0.310000 | 0.637630 | 0.971644 | 0.500000 | 0.001046 |
CORE_TOP VAV BOX COMPONENT | 2.00 | 0.373947 | 0.318000 | 0.637327 | 0.997192 | 0.500000 | 0.001019 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.601993 | 0.262448 | 0.230000 | 0.138458 | 0.699861 | 0.500000 | 0.001452 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.806652 | 0.123996 | 0.105000 | 0.084698 | 0.330656 | 0.500000 | 0.003073 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.26 | 0.125285 | 0.106000 | 0.133672 | 0.334094 | 0.500000 | 0.003041 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.831718 | 0.120251 | 0.102000 | 0.084835 | 0.320670 | 0.500000 | 0.003168 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.497382 | 0.317646 | 0.270000 | 0.134293 | 0.847057 | 0.500000 | 0.001199 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.655357 | 0.152622 | 0.130000 | 0.085196 | 0.406991 | 0.500000 | 0.002496 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.02 | 0.154829 | 0.132000 | 0.134696 | 0.412878 | 0.500000 | 0.002461 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.685029 | 0.146001 | 0.124000 | 0.084944 | 0.389337 | 0.500000 | 0.002610 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.564066 | 0.280094 | 0.238000 | 0.134248 | 0.746919 | 0.500000 | 0.001360 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.807264 | 0.330406 | 0.500000 | 0.003075 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.20 | 0.131146 | 0.111000 | 0.133721 | 0.349724 | 0.500000 | 0.002905 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.794329 | 0.125912 | 0.107000 | 0.084993 | 0.335764 | 0.500000 | 0.003026 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20964.30 |
CORE_MID VAV BOX REHEAT COIL | 23415.13 |
CORE_TOP VAV BOX REHEAT COIL | 45426.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19793.24 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12930.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19712.83 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12884.72 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15950.48 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10515.33 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15891.37 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10476.59 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15001.78 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9877.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 14922.27 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9836.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.65 | 1.08 | 5.29 | 2.03 | 4.51 | 4.51 | 0.300000 | 0.450317 | 4.51 |
PACU_VAV_MID | 2.71 | 1.08 | 5.43 | 2.22 | 4.36 | 4.36 | 0.300000 | 0.509997 | 4.36 |
PACU_VAV_TOP | 2.75 | 1.08 | 5.51 | 3.37 | 4.76 | 4.76 | 0.300000 | 0.708339 | 4.76 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.51 |
PACU_VAV_MID_OA_CONTROLLER | 4.36 |
PACU_VAV_TOP_OA_CONTROLLER | 4.76 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 0.956100 |
PACU_VAV_MID OA HEAT RECOVERY | 0.956100 |
PACU_VAV_TOP OA HEAT RECOVERY | 0.956100 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.51 | 74680.51 | 0.800655 | 1.50 | 24891.01 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.36 | 72117.15 | 0.800655 | 1.45 | 24036.64 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 4.76 | 78714.93 | 0.800655 | 1.58 | 26235.69 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 59534.25 |
PACU_VAV_MID HEATING COIL | 58870.84 |
PACU_VAV_TOP HEATING COIL | 59387.86 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.51 |
PACU_VAV_MID FAN | 4.36 |
PACU_VAV_TOP FAN | 4.76 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.4185 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.4130 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.155 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.187 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.668 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.37057002E-12 | 0.61824839E-15 | -0.12867225E-12 | 0.13278609E-15 |
43 | 6 | 0.32864829E-07 | 0.12215435E-09 | 0.74936321E-08 | -0.15793558E-12 |
44 | 5 | -0.21117705E-03 | 0.10197527E-05 | -0.10830458E-03 | 0.73932783E-08 |
45 | 4 | 0.31647400 | 0.48538563E-03 | 0.10844808 | -0.37037309E-04 |
46 | 3 | -7.7473548 | 0.14742501E-01 | -2.4817050 | 0.31368497E-01 |
47 | 2 | 42.456724 | 0.51492847E-01 | 15.848935 | -0.35100438 |
48 | 1 | -81.759911 | 0.22877031E-01 | -29.664605 | 1.1044942 |
49 | 0 | 46.824331 | 0.45321442E-03 | 16.279087 | |
50 | 7 | -0.37453704E-12 | 0.57793338E-15 | -0.12861619E-12 | 0.13048347E-15 |
51 | 6 | 0.32928281E-07 | 0.12060375E-09 | 0.75076420E-08 | -0.15827917E-12 |
52 | 5 | -0.21149279E-03 | 0.10064611E-05 | -0.10846173E-03 | 0.74068807E-08 |
53 | 4 | 0.31683391 | 0.47891067E-03 | 0.10857797 | -0.37089080E-04 |
54 | 3 | -7.7544604 | 0.14541829E-01 | -2.4838152 | 0.31403381E-01 |
55 | 2 | 42.480133 | 0.50779419E-01 | 15.857537 | -0.35126524 |
56 | 1 | -81.777823 | 0.22555161E-01 | -29.672301 | 1.1048759 |
57 | 0 | 46.824331 | 0.44674234E-03 | 16.278913 | |
58 | 7 | -0.34510616E-12 | 0.74655565E-15 | -0.11565958E-12 | 0.10848325E-15 |
59 | 6 | 0.31621801E-07 | 0.15198870E-09 | 0.72192319E-08 | -0.15111686E-12 |
60 | 5 | -0.20497495E-03 | 0.12776160E-05 | -0.10521458E-03 | 0.71267181E-08 |
61 | 4 | 0.30937768 | 0.61190855E-03 | 0.10588831 | -0.36019385E-04 |
62 | 3 | -7.6071883 | 0.18688135E-01 | -2.4400853 | 0.30680540E-01 |
63 | 2 | 41.994872 | 0.65596338E-01 | 15.679133 | -0.34585823 |
64 | 1 | -81.406440 | 0.29269621E-01 | -29.512625 | 1.0969608 |
65 | 0 | 46.824333 | 0.58233445E-03 | 16.282544 | |
66 | 7 | -0.22718025E-08 | -0.85076432E-15 | 0.54602610E-14 | -0.81699313E-16 |
67 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
68 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
69 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
70 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
71 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
72 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
73 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
74 | 7 | -0.21518248E-08 | -0.72352508E-15 | 0.47198691E-14 | -0.69590188E-16 |
75 | 6 | 0.55239907E-05 | 0.37570600E-08 | 0.31901221E-02 | -0.26761418E-04 |
76 | 5 | -0.39518120E-03 | 0.22239456E-05 | -0.22373891 | 0.19562768E-02 |
77 | 4 | 0.90771213E-02 | 0.10121852E-03 | 4.8297846 | -0.45267278E-01 |
78 | 3 | -0.79671013E-01 | 0.80474906E-03 | -38.022767 | 0.39866868 |
79 | 2 | 0.28284274 | 0.13386367E-02 | 116.48658 | -1.4179745 |
80 | 1 | -0.40820825 | 0.40769430E-03 | -143.90886 | 2.0490654 |
81 | 0 | 0.19901349 | 0.99021926E-05 | 60.838472 | |
82 | 7 | -0.22718025E-08 | -0.85076409E-15 | 0.54602611E-14 | -0.81699316E-16 |
83 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
84 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
85 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
86 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
87 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
88 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
89 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
90 | 7 | -0.21516764E-08 | -0.72282083E-15 | 0.50090186E-14 | -0.71315031E-16 |
91 | 6 | 0.55243484E-05 | 0.37573175E-08 | 0.31901211E-02 | -0.26761409E-04 |
92 | 5 | -0.39520780E-03 | 0.22240973E-05 | -0.22373885 | 0.19562763E-02 |
93 | 4 | 0.90777390E-02 | 0.10122544E-03 | 4.8297836 | -0.45267268E-01 |
94 | 3 | -0.79676455E-01 | 0.80480411E-03 | -38.022761 | 0.39866862 |
95 | 2 | 0.28286209 | 0.13387285E-02 | 116.48657 | -1.4179743 |
96 | 1 | -0.40823619 | 0.40772215E-03 | -143.90885 | 2.0490653 |
97 | 0 | 0.19902711 | 0.99029315E-05 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 35 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 36 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
3 | WINDOW_U_0.262_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
4 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 38 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4670E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4746E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7334E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7402E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3365E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3814E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5636E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5883E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1611 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1088 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1884 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1319 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5051E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2487E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0604E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8980E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4676E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4790E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7342E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7455E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3400E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3980E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5633E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5880E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1057 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5105E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1101 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7858E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2097E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1934E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9382E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7963E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.1439E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.1778E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.4403E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.4664E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8209E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8298E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3268E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3352E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9917E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0654E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0720E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1371E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0531E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0959E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5633E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.5880E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 6.2847E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5557E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0236E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8218E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1357E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7054E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0604E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8980E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9909E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0691E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0695E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1335E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0499E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0831E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5636E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.5883E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.6340E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.6960E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8841E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2247E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6703E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4090E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9383E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7963E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0787E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.1765E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5284E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6452E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8541E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8803E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3270E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3354E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1756 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1303 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2049 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1568 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1048 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4448E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7665E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.6893E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1016 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.2782E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1059 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.5428E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0043E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0716E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8278E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7301E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 7.0388E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.5246E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6949E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.6608E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7749E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4190E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7665E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6893E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3585E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5436E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6445E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0946E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5160E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3198E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8279E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7302E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1756 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1303 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2050 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1568 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1047 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4443E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7660E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.6889E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1016 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.2778E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1059 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.5423E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0039E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0711E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8273E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7298E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 7.0390E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.5244E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6950E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.6606E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7746E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4188E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7660E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6889E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3587E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5434E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6446E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0944E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5156E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3195E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8273E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7299E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 33267.45128 | 33267.45128 | 2.43362 | 2.43362 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9855.16372 | 9855.16372 | 0.42950 | 0.42950 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28140.34470 | 28140.34470 | 2.05687 | 2.05687 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16548.15364 | 16548.15364 | 0.71215 | 0.71215 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27421.47949 | 27421.47949 | 2.00417 | 2.00417 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 31964.23424 | 31964.23424 | 1.38160 | 1.38160 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 7917.52214 | 7917.52214 | 0.58432 | 0.58432 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 21.53500 | 6.99833E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 13894.84861 | 13894.84861 | 0.60199 | 0.60199 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10930.14758 | 10930.14758 | 0.80665 | 0.80665 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9076.37497 | 9076.37497 | 0.39326 | 0.39326 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 17087.25804 | 17087.25804 | 1.26105 | 1.26105 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 13838.52228 | 13838.52228 | 0.59955 | 0.59955 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11269.78918 | 11269.78918 | 0.83172 | 0.83172 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9044.52975 | 9044.52975 | 0.39188 | 0.39188 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6739.38452 | 6739.38452 | 0.49738 | 0.49738 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11202.21055 | 11202.21055 | 0.48512 | 0.48512 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8943.92799 | 8943.92799 | 0.65536 | 0.65536 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7384.25648 | 7384.25648 | 0.31981 | 0.31981 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 13826.58755 | 13826.58755 | 1.02042 | 1.02042 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11160.81261 | 11160.81261 | 0.48332 | 0.48332 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9282.04707 | 9282.04707 | 0.68503 | 0.68503 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 23.04800 | 7.00058E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7357.12087 | 7357.12087 | 0.31864 | 0.31864 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7642.98859 | 7642.98859 | 0.56407 | 0.56407 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 10538.41633 | 10538.41633 | 0.45626 | 0.45626 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10938.40515 | 10938.40515 | 0.80726 | 0.80726 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79000 | 6.99871E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6937.91196 | 6937.91196 | 0.30041 | 0.30041 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 16323.57358 | 16323.57358 | 1.20470 | 1.20470 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10482.72918 | 10482.72918 | 0.45385 | 0.45385 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10763.12808 | 10763.12808 | 0.79433 | 0.79433 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6909.47354 | 6909.47354 | 0.29918 | 0.29918 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 63995.48 | 4.51145 | 4.51145 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 62203.22 | 2.03158 | 2.03158 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 61912.05 | 4.35660 | 4.35660 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 62114.54 | 2.22185 | 2.22185 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 67058.19 | 4.75517 | 4.75517 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 62285.12 | 3.36827 | 3.36827 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.43362 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30796 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63761 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82122 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23718E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20964.30050 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05687 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36437 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63763 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97164 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04565E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23415.12975 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00417 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37395 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63733 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99719 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01886E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 45426.24250 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60199 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26245 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13846 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69986 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45172E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19793.24403 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80665 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12400 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10500 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46985E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33066 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07268E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12930.17941 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26105 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12529 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13367 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33409 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04106E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19712.82652 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83172 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12025 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48353E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32067 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16836E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12884.71528 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.49738 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31765 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13429 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84706 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19945E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15950.48388 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65536 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15262 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51965E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40699 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49637E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10515.32928 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02042 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15483 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13470 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41288 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46077E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15891.37435 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68503 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14600 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49436E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38934 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60956E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10476.58699 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56407 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28009 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13425 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74692 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36026E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15001.77575 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80726 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33041 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07501E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9877.43945 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20470 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13115 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11100 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13372 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34972 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90515E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14922.26663 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79433 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12591 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49933E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33576 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02593E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9836.83711 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64591 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07674 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.29182 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.03158 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.51145 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.51145 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.45032 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.71361 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07536 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.42723 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.22185 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.35660 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.35660 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.51000 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.75280 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07899 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.50559 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.36827 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.75517 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.75517 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.70834 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.51145 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.35660 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.75517 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.51145 |
146 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.51145 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 74680.50904 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.50367 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 24891.01366 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
153 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 59534.25120 |
154 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.51145 |
155 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.35660 |
156 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.35660 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 72117.14571 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.45205 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 24036.64466 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
163 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 58870.83577 |
164 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.35660 |
165 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.75517 |
166 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.75517 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 78714.93356 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58490 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26235.68736 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 59387.86259 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.75517 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 73395.44 | 250435.65 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.1368 | 4.0631 | 2.7228 | 1.1347 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 70876.19 | 241839.60 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 4.9605 | 3.9236 | 2.6294 | 1.0958 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 77360.45 | 263964.80 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.4143 | 4.2826 | 2.8699 | 1.1960 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.526 | 0.487 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.196 | 0.187 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.418 | 0.394 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.196 | 0.187 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.413 | 0.389 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.1359849327E-002 | 6.4976405114E-003 | Pass | Pass | 0.5348678520 | 0.5171197356 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1966235699 | 0.1231476466 | Pass | Pass | 0.5274815127 | 0.5151144387 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.0169763276E-002 | 5.5768760480E-002 | Pass | Pass | 0.4956022260 | 0.4864430390 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.5656492871E-002 | 4.5212729481E-002 | Pass | Pass | 0.4961388476 | 0.4889844919 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.4939342386E-002 | 5.8742109314E-002 | Pass | Pass | 0.9794695570 | 1.0528821670 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1966665968 | 0.1900857620 | Pass | Pass | 0.7986162551 | 0.7643222204 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6730152842 | 0.5563543200 | Pass | Pass | 0.6597788121 | 0.5785860550 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7106917118 | 0.6669539049 | Pass | Pass | 0.6799516068 | 0.6902964521 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6750710356 | 0.6361648844 | Pass | Pass | 0.6833814304 | 0.6797626739 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7093913146 | 0.6678275063 | Pass | Pass | 0.6777277123 | 0.6783240014 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5596951073 | 0.4650695992 | Pass | Pass | 0.6660562634 | 0.6297897926 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5926198135 | 0.5570085972 | Pass | Pass | 0.6928037932 | 0.6709638966 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5593188772 | 0.5270803381 | Pass | Pass | 0.7132418377 | 0.7097142771 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5970593291 | 0.5598673831 | Pass | Pass | 0.7057992897 | 0.7032233412 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5135415227 | 0.4459888540 | Pass | Pass | 0.6802305190 | 0.5782148915 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5526431063 | 0.5200796213 | Pass | Pass | 1.0486956634 | 3.5808281946 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5183413853 | 0.4892832878 | Pass | Pass | 0.8932231679 | 1.6247922365 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5509624219 | 0.5180388874 | Pass | Pass | 1.0714246594 | 3.7899211350 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2258.39 | 188.35 | 0.00 | 2482.41 | 273.97 | 5203.13 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.487 | 0.526 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.394 | 0.418 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.389 | 0.413 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.262_SHGC_EAST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.262_SHGC_WEST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.262_SHGC_WEST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 195.79 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.488 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.62 | 0.0000 | Y | 5.56 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.29 | 0.0000 | Y | 3.47 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 23.80 | 0.0000 | Y | 5.38 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.20 | 0.0000 | Y | 3.46 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.55 | 0.0000 | Y | 5.55 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.24 | 0.0000 | Y | 3.47 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 23.75 | 0.0000 | Y | 5.36 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.14 | 0.0000 | Y | 3.45 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.62 | 0.0000 | Y | 5.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.29 | 0.0000 | Y | 3.47 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 23.80 | 0.0000 | Y | 5.38 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 24.20 | 0.0000 | Y | 3.46 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 172.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 44.84 | 44.84 | 4.57 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.06 | 63.95 | 3.36 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.06 | 52.41 | 29.53 | |
Exterior Lighting Total | 3824.74 | 37.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 74680.51 | 59793.34 | 14887.17 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 72117.15 | 57740.97 | 14376.17 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 78714.93 | 63023.53 | 15691.41 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 73395.4 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_MID COOLING COIL | 70876.2 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_TOP COOLING COIL | 77360.4 | 2.80 | 9.54 | N/A | N/A | 10.81 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20964.30 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 23415.13 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 45426.24 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19793.24 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12930.18 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19712.83 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12884.72 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15950.48 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10515.33 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15891.37 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10476.59 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15001.78 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9877.44 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14922.27 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9836.84 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 59534.25 | 0.84 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 58870.84 | 0.84 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 59387.86 | 0.84 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.51 | 10436.73 | 2313.39 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.36 | 10078.49 | 2313.39 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.76 | 11000.54 | 2313.39 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 73395.44 | 2.80 | 9.54 | 10.81 | 5.1368 | 3.09 | 10.55 | 4.0631 | 3.26 | 11.11 | 2.7228 | 3.43 | 11.69 | 1.1347 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 70876.19 | 2.80 | 9.54 | 10.81 | 4.9605 | 3.09 | 10.55 | 3.9236 | 3.26 | 11.11 | 2.6294 | 3.43 | 11.69 | 1.0958 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 77360.45 | 2.80 | 9.54 | 10.81 | 5.4143 | 3.09 | 10.55 | 4.2826 | 3.26 | 11.11 | 2.8699 | 3.43 | 11.69 | 1.1960 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 33267.45 | 33267.45 | 33.82 | 2.434 | 2.434 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 28140.34 | 28140.34 | 28.61 | 2.057 | 2.057 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 27421.48 | 27421.48 | 27.88 | 2.004 | 2.004 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 19.85 | 0.00700 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7917.52 | 7917.52 | 38.19 | 0.584 | 0.584 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00875 | 21.54 | 0.00700 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10930.15 | 10930.15 | 83.27 | 0.807 | 0.807 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17087.26 | 17087.26 | 82.41 | 1.261 | 1.261 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00862 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11269.79 | 11269.79 | 85.86 | 0.832 | 0.832 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00861 | 24.70 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6739.38 | 6739.38 | 32.50 | 0.497 | 0.497 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00883 | 21.08 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8943.93 | 8943.93 | 68.14 | 0.655 | 0.655 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00866 | 19.85 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13826.59 | 13826.59 | 66.69 | 1.020 | 1.020 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00866 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9282.05 | 9282.05 | 70.72 | 0.685 | 0.685 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00865 | 23.05 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7642.99 | 7642.99 | 36.86 | 0.564 | 0.564 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00877 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10938.41 | 10938.41 | 83.33 | 0.807 | 0.807 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00862 | 21.79 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 16323.57 | 16323.57 | 78.73 | 1.205 | 1.205 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00863 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10763.13 | 10763.13 | 82.00 | 0.794 | 0.794 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00862 | 24.70 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9855.16 | 9855.16 | 10.02 | 0.429 | 0.429 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 16548.15 | 16548.15 | 16.83 | 0.712 | 0.712 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 31964.23 | 31964.23 | 32.50 | 1.382 | 1.382 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13894.85 | 13894.85 | 67.02 | 0.602 | 0.602 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9076.37 | 9076.37 | 69.15 | 0.393 | 0.393 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13838.52 | 13838.52 | 66.74 | 0.600 | 0.600 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9044.53 | 9044.53 | 68.91 | 0.392 | 0.392 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11202.21 | 11202.21 | 54.03 | 0.485 | 0.485 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7384.26 | 7384.26 | 56.26 | 0.320 | 0.320 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11160.81 | 11160.81 | 53.83 | 0.483 | 0.483 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7357.12 | 7357.12 | 56.05 | 0.319 | 0.319 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10538.42 | 10538.42 | 50.83 | 0.456 | 0.456 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6937.91 | 6937.91 | 52.86 | 0.300 | 0.300 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10482.73 | 10482.73 | 50.56 | 0.454 | 0.454 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6909.47 | 6909.47 | 52.64 | 0.299 | 0.299 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.51 | 4.51 | 2.03 | 2.03 | 4.5114 | 2.0316 | 4.5114 | 0.4503 | 0.3000 |
PACU_VAV_MID | 4.36 | 4.36 | 2.22 | 2.22 | 4.3566 | 2.2219 | 4.3566 | 0.5100 | 0.3000 |
PACU_VAV_TOP | 4.76 | 4.76 | 3.37 | 3.37 | 4.7552 | 3.3683 | 4.7552 | 0.7083 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20964.301 | 20964.301 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 20964.30 | 14121.68 | 0.429498 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 9855.16 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 23415.130 | 23415.130 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23415.13 | 23415.13 | 0.712149 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 16548.15 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 45426.242 | 45426.242 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45426.24 | 45426.24 | 1.381597 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 31964.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19793.244 | 19793.244 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19793.24 | 19793.24 | 0.601993 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796111 | 50.6693 | 13894.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12930.179 | 12930.179 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12930.18 | 12930.18 | 0.393259 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796037 | 50.6647 | 9076.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19712.827 | 19712.827 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19712.83 | 19712.83 | 0.599547 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796095 | 50.6683 | 13838.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12884.715 | 12884.715 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12884.72 | 12884.72 | 0.391877 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796022 | 50.6638 | 9044.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15950.484 | 15950.484 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15950.48 | 15950.48 | 0.485119 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797298 | 50.7436 | 11202.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10515.329 | 10515.329 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10515.33 | 10515.33 | 0.319814 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797303 | 50.7440 | 7384.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15891.374 | 15891.374 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15891.37 | 15891.37 | 0.483321 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797284 | 50.7428 | 11160.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10476.587 | 10476.587 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10476.59 | 10476.59 | 0.318636 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797290 | 50.7432 | 7357.12 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 15001.776 | 15001.776 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15001.78 | 15001.78 | 0.456265 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795510 | 50.6315 | 10538.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9877.439 | 9877.439 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9877.44 | 9877.44 | 0.300413 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795509 | 50.6314 | 6937.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 14922.267 | 14922.267 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14922.27 | 14922.27 | 0.453847 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795477 | 50.6295 | 10482.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9836.837 | 9836.837 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9836.84 | 9836.84 | 0.299178 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00795484 | 50.6299 | 6909.47 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 74680.509 | 59793.342 | 4.511450 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 75858.96 | 75858.96 | 4.511450 | 24.72 | 16.42 | 0.00843212 | 10.89 | 10.89 | 0.00843212 | 27.40 | 0.00700714 | 16.15 | 21.1927 | 24.00 | 0.00881582 | 46.6980 | 61066.21 | 0.00 | 77005.63 | 60128.01 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 59534.251 | 59534.251 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59534.25 | 59534.25 | 1.353435 | -24.13 | -24.13 | 0.00237638 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 70.6425 | 18.24 | 0.00793824 | 59.9672 | 15200.36 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 72117.146 | 57740.972 | 4.356597 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 73255.15 | 73255.15 | 4.356597 | 24.75 | 16.42 | 0.00842036 | 10.89 | 10.89 | 0.00842036 | 27.40 | 0.00700714 | 16.15 | 21.9460 | 24.00 | 0.00881840 | 46.7113 | 58950.13 | 0.00 | 74362.46 | 58064.15 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 58870.836 | 58870.836 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 58870.84 | 58870.84 | 1.306979 | -25.01 | -25.01 | 0.00218227 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 73.1534 | 18.04 | 0.00793973 | 60.7547 | 17491.95 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 78714.934 | 63023.526 | 4.755169 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 79999.16 | 79999.16 | 4.755169 | 24.66 | 16.40 | 0.00842909 | 10.89 | 10.89 | 0.00842909 | 27.30 | 0.00700699 | 16.11 | 20.1065 | 24.00 | 0.00878793 | 46.5521 | 64295.12 | 0.00 | 81165.66 | 63376.27 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 59387.863 | 59387.863 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59387.86 | 59387.86 | 1.426551 | -22.15 | -22.15 | 0.00265378 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 67.0218 | 15.63 | 0.00793331 | 70.7111 | 15736.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20964.301 | 20964.301 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 20964.30 | 14121.68 | 1.0000 | 0.50914332 | 0.429498 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20964.30 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 9855.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 23415.130 | 23415.130 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23415.13 | 23415.13 | 1.0000 | 0.84420964 | 0.712149 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23415.13 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 16548.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 45426.242 | 45426.242 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 45426.24 | 45426.24 | 1.0000 | 1.63779881 | 1.381597 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45426.24 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 31964.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19793.244 | 19793.244 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19793.24 | 19793.24 | 1.0000 | 0.71362608 | 0.601993 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19793.24 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796111 | 21.00 | 0.00796111 | 50.6693 | 13894.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12930.179 | 12930.179 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12930.18 | 12930.18 | 1.0000 | 0.46618499 | 0.393259 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12930.18 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796037 | 21.00 | 0.00796037 | 50.6647 | 9076.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 19712.827 | 19712.827 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19712.83 | 19712.83 | 1.0000 | 0.71072671 | 0.599547 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19712.83 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796095 | 21.00 | 0.00796095 | 50.6683 | 13838.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12884.715 | 12884.715 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12884.72 | 12884.72 | 1.0000 | 0.46454583 | 0.391877 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12884.72 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796022 | 21.00 | 0.00796022 | 50.6638 | 9044.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15950.484 | 15950.484 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15950.48 | 15950.48 | 1.0000 | 0.57507912 | 0.485119 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15950.48 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797298 | 21.00 | 0.00797298 | 50.7436 | 11202.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10515.329 | 10515.329 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10515.33 | 10515.33 | 1.0000 | 0.37911993 | 0.319814 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10515.33 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797303 | 21.00 | 0.00797303 | 50.7440 | 7384.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15891.374 | 15891.374 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15891.37 | 15891.37 | 1.0000 | 0.57294798 | 0.483321 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15891.37 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797284 | 21.00 | 0.00797284 | 50.7428 | 11160.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10476.587 | 10476.587 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10476.59 | 10476.59 | 1.0000 | 0.37772311 | 0.318636 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10476.59 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797290 | 21.00 | 0.00797290 | 50.7432 | 7357.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15001.776 | 15001.776 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15001.78 | 15001.78 | 1.0000 | 0.54087437 | 0.456265 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15001.78 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795510 | 21.00 | 0.00795510 | 50.6315 | 10538.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9877.439 | 9877.439 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9877.44 | 9877.44 | 1.0000 | 0.35612143 | 0.300413 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9877.44 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795509 | 21.00 | 0.00795509 | 50.6314 | 6937.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14922.267 | 14922.267 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14922.27 | 14922.27 | 1.0000 | 0.53800775 | 0.453847 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14922.27 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795477 | 21.00 | 0.00795477 | 50.6295 | 10482.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9836.837 | 9836.837 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9836.84 | 9836.84 | 1.0000 | 0.35465756 | 0.299178 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9836.84 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00795484 | 21.00 | 0.00795484 | 50.6299 | 6909.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 74680.509 | 59793.342 | 4.511450 | -999.0 | -999.000 | -999.0000 | 1.03057 | 1.00000 | 1020.5149 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.511450 | 5.34804957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 75858.96 | 75858.96 | 1.0158 | 5.34804957 | 4.511450 | 24.72 | 16.42 | 0.00843212 | 46315.8 | 10.89 | 10.89 | 0.00843212 | 32199.3 | -999.0 | -999.00 | -999.00 | -999.00 | 10436.727 | 65422.23 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 21.1927 | 24.00 | 0.00881582 | 24.00 | 0.00881582 | 46.6980 | 61066.21 | 0.00 | 77005.63 | 60128.01 | 5.13684204 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59534.251 | 59534.251 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.511450 | 5.34804957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59534.25 | 59534.25 | 1.0000 | 1.60441487 | 1.353435 | -24.13 | -24.13 | 0.00237638 | -18407.3 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59534.25 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 70.6425 | 18.64 | 0.00793941 | 18.24 | 0.00793824 | 59.9672 | 15200.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 72117.146 | 57740.972 | 4.356597 | -999.0 | -999.000 | -999.0000 | 1.02872 | 1.00000 | 1020.4930 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.356597 | 5.16448100 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 73255.15 | 73255.15 | 1.0158 | 5.16448100 | 4.356597 | 24.75 | 16.42 | 0.00842036 | 46312.3 | 10.89 | 10.89 | 0.00842036 | 32169.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10078.493 | 63176.65 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 21.9460 | 24.00 | 0.00881840 | 24.00 | 0.00881840 | 46.7113 | 58950.13 | 0.00 | 74362.46 | 58064.15 | 4.96052304 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58870.836 | 58870.836 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.356597 | 5.16448100 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 58870.84 | 58870.84 | 1.0000 | 1.54934430 | 1.306979 | -25.01 | -25.01 | 0.00218227 | -19778.3 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58870.84 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 73.1534 | 21.00 | 0.00795292 | 18.04 | 0.00793973 | 60.7547 | 17491.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 78714.934 | 63023.526 | 4.755169 | -999.0 | -999.000 | -999.0000 | 1.03517 | 1.00000 | 1020.5092 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.755169 | 5.63696434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 79999.16 | 79999.16 | 1.0163 | 5.63696434 | 4.755169 | 24.66 | 16.40 | 0.00842909 | 46250.2 | 10.89 | 10.89 | 0.00842909 | 32191.7 | -999.0 | -999.00 | -999.00 | -999.00 | 11000.545 | 68998.62 | 27.30 | 0.00700699 | 16.11 | 0.95610000 | 20.1065 | 24.00 | 0.00878793 | 24.00 | 0.00878793 | 46.5521 | 64295.12 | 0.00 | 81165.66 | 63376.27 | 5.41434686 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59387.863 | 59387.863 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.755169 | 5.63696434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59387.86 | 59387.86 | 1.0000 | 1.69108930 | 1.426551 | -22.15 | -22.15 | 0.00265378 | -15727.8 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59387.86 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 67.0218 | 17.99 | 0.00791598 | 15.63 | 0.00793331 | 70.7111 | 15736.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.51 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.36 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.76 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2000.17 | 3843.50 | 1260.67 |
CORE_MID | 2620.17 | 4207.17 | 2084.17 |
CORE_TOP | 3143.17 | 4459.00 | 2705.00 |
PERIMETER_TOP_ZN_3 | 3759.17 | 4523.83 | 3168.00 |
PERIMETER_TOP_ZN_2 | 3980.17 | 4088.17 | 2910.50 |
PERIMETER_TOP_ZN_1 | 3792.67 | 4061.67 | 2727.67 |
PERIMETER_TOP_ZN_4 | 3876.00 | 4306.00 | 3047.33 |
PERIMETER_BOT_ZN_3 | 3482.83 | 4708.17 | 3095.67 |
PERIMETER_BOT_ZN_2 | 3849.50 | 4037.83 | 2807.17 |
PERIMETER_BOT_ZN_1 | 3651.17 | 4279.83 | 2766.00 |
PERIMETER_BOT_ZN_4 | 3657.67 | 4348.33 | 2924.17 |
PERIMETER_MID_ZN_3 | 3582.17 | 4363.50 | 2915.33 |
PERIMETER_MID_ZN_2 | 3265.33 | 3385.33 | 2310.33 |
PERIMETER_MID_ZN_1 | 3614.00 | 3841.83 | 2441.83 |
PERIMETER_MID_ZN_4 | 3710.50 | 4123.50 | 2803.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5059.50 | 4959.50 | 3360.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 3.00 | 0.00 | 2.67 | 0.00 |
CORE_MID | 7.83 | 0.00 | 7.17 | 0.00 |
CORE_TOP | 31.00 | 0.00 | 25.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 344.33 | 0.00 | 201.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 183.83 | 11.00 | 47.17 | 10.83 |
PERIMETER_TOP_ZN_1 | 146.83 | 18.17 | 36.17 | 17.67 |
PERIMETER_TOP_ZN_4 | 183.50 | 17.33 | 49.67 | 6.33 |
PERIMETER_BOT_ZN_3 | 229.83 | 0.00 | 188.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 46.33 | 8.33 | 10.00 | 7.83 |
PERIMETER_BOT_ZN_1 | 639.33 | 8.83 | 611.50 | 8.50 |
PERIMETER_BOT_ZN_4 | 48.67 | 5.00 | 12.00 | 1.00 |
PERIMETER_MID_ZN_3 | 99.67 | 0.33 | 57.67 | 0.00 |
PERIMETER_MID_ZN_2 | 53.00 | 14.67 | 12.00 | 13.00 |
PERIMETER_MID_ZN_1 | 36.33 | 19.50 | 7.83 | 19.17 |
PERIMETER_MID_ZN_4 | 55.00 | 16.83 | 13.67 | 5.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 930.67 | 84.00 | 748.17 | 60.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.723 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.630 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.601 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.768 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.143 | 0.057 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 1.171 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.967 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.641 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.011 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 1.058 | 0.874 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.818 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.752 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.040 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 1.190 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.958 | 0.047 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.11 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 11456821.42 | 0.00 | 11456821.42 | 0.00 | 11456821.42 | 13393058.27 | 5995.55 | 571.78 | 2192.67 | 317.40 |
CORE_MID | 10034466.70 | 0.00 | 10034466.70 | 0.00 | 10034466.70 | 13393058.27 | 5654.84 | 1059.76 | 2045.40 | 310.52 |
CORE_TOP | 9553347.16 | 0.00 | 9553347.16 | 0.00 | 9553347.16 | 13393058.27 | 6138.67 | 833.18 | 1788.15 | 86.73 |
PERIMETER_TOP_ZN_3 | 2566963.16 | 0.00 | 2566963.16 | 370406.43 | 2937369.59 | 2823374.22 | 4536.79 | 123.43 | 4099.78 | 86.73 |
PERIMETER_TOP_ZN_2 | 2408835.86 | 0.00 | 2408835.86 | 246936.13 | 2655771.99 | 1787429.43 | 4855.98 | 762.35 | 3141.67 | 86.73 |
PERIMETER_TOP_ZN_1 | 3898464.23 | 0.00 | 3898464.23 | 370406.43 | 4268870.65 | 2823374.22 | 5057.37 | 752.26 | 2950.37 | 86.73 |
PERIMETER_TOP_ZN_4 | 2054198.80 | 0.00 | 2054198.80 | 246936.13 | 2301134.93 | 1787312.18 | 4899.46 | 768.99 | 3091.55 | 86.73 |
PERIMETER_BOT_ZN_3 | 2153838.52 | 0.00 | 2153838.52 | 196941.88 | 2350780.40 | 2823374.22 | 5403.26 | 564.89 | 2791.85 | 317.40 |
PERIMETER_BOT_ZN_2 | 2136325.71 | 0.00 | 2136325.71 | 131293.80 | 2267619.51 | 1787429.43 | 5065.08 | 604.99 | 3089.94 | 317.40 |
PERIMETER_BOT_ZN_1 | 3547602.23 | 0.00 | 3547602.23 | 3034889.02 | 6582491.25 | 2823374.22 | 4687.03 | 523.46 | 3549.51 | 317.40 |
PERIMETER_BOT_ZN_4 | 1736096.11 | 0.00 | 1736096.11 | 131293.80 | 1867389.91 | 1787312.18 | 5268.92 | 594.86 | 2896.22 | 317.40 |
PERIMETER_MID_ZN_3 | 2521256.80 | 0.00 | 2521256.80 | 308333.93 | 2829590.73 | 2823374.22 | 5016.38 | 1030.27 | 2713.35 | 310.48 |
PERIMETER_MID_ZN_2 | 2276202.07 | 0.00 | 2276202.07 | 205554.72 | 2481756.79 | 1601953.02 | 4632.26 | 825.17 | 3302.57 | 1219.48 |
PERIMETER_MID_ZN_1 | 3967694.91 | 0.00 | 3967694.91 | 308333.93 | 4276028.84 | 2823374.22 | 5051.21 | 987.72 | 2721.08 | 310.48 |
PERIMETER_MID_ZN_4 | 2040452.48 | 0.00 | 2040452.48 | 205554.72 | 2246007.20 | 1787312.18 | 4917.29 | 997.59 | 2845.12 | 310.48 |
Total Facility | 62352566.18 | 0.00 | 62352566.18 | 5756880.91 | 68109447.09 | 67658168.57 | 6959.37 | 1745.02 | 4617.97 | 1337.15 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5292 | 0.0000 | 0.5292 | 0.0000 | 0.5292 | 0.4247 | 3215.27 | 571.67 | 2156.06 |
CORE_MID | 0.4618 | 0.0000 | 0.4618 | 0.0000 | 0.4618 | 0.4247 | 2890.42 | 1059.26 | 1993.32 |
CORE_TOP | 0.4410 | 0.0000 | 0.4410 | 0.0000 | 0.4410 | 0.4247 | 3372.29 | 833.18 | 1737.54 |
PERIMETER_TOP_ZN_3 | 0.1188 | 0.0000 | 0.1188 | 0.0083 | 0.1271 | 0.0895 | 1770.48 | 123.43 | 4049.09 |
PERIMETER_TOP_ZN_2 | 0.1118 | 0.0000 | 0.1118 | 0.0056 | 0.1174 | 0.0567 | 2089.98 | 762.35 | 3090.67 |
PERIMETER_TOP_ZN_1 | 0.1810 | 0.0000 | 0.1810 | 0.0083 | 0.1894 | 0.0895 | 2290.98 | 752.26 | 2899.76 |
PERIMETER_TOP_ZN_4 | 0.0947 | 0.0000 | 0.0947 | 0.0056 | 0.1002 | 0.0567 | 2133.21 | 768.93 | 3040.86 |
PERIMETER_BOT_ZN_3 | 0.0993 | 0.0000 | 0.0993 | 0.0044 | 0.1037 | 0.0895 | 2622.98 | 564.73 | 2755.29 |
PERIMETER_BOT_ZN_2 | 0.0990 | 0.0000 | 0.0990 | 0.0030 | 0.1019 | 0.0567 | 2285.15 | 604.91 | 3052.94 |
PERIMETER_BOT_ZN_1 | 0.1644 | 0.0000 | 0.1644 | 0.1371 | 0.3015 | 0.0895 | 1906.77 | 523.35 | 3512.88 |
PERIMETER_BOT_ZN_4 | 0.0801 | 0.0000 | 0.0801 | 0.0030 | 0.0831 | 0.0567 | 2488.71 | 594.69 | 2859.60 |
PERIMETER_MID_ZN_3 | 0.1163 | 0.0000 | 0.1163 | 0.0069 | 0.1232 | 0.0895 | 2252.63 | 1029.82 | 2660.54 |
PERIMETER_MID_ZN_2 | 0.1017 | 0.0000 | 0.1017 | 0.0050 | 0.1067 | 0.0567 | 1868.67 | 824.73 | 2340.60 |
PERIMETER_MID_ZN_1 | 0.1839 | 0.0000 | 0.1839 | 0.0069 | 0.1908 | 0.0895 | 2286.71 | 987.30 | 2668.99 |
PERIMETER_MID_ZN_4 | 0.0937 | 0.0000 | 0.0937 | 0.0046 | 0.0983 | 0.0567 | 2153.21 | 997.09 | 2792.70 |
Total Facility | 2.8767 | 0.0000 | 2.8767 | 0.1986 | 3.0753 | 2.1513 | 4162.10 | 1744.19 | 4546.96 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29553683.35 | 0.00 | 29553683.35 | 22614548.33 | 4188.29 | 2.79 | 4568.91 | 317.37 |
PACU_VAV_MID | 29285866.21 | 0.00 | 29285866.21 | 22429071.92 | 4139.79 | 2.19 | 4618.02 | 309.81 |
PACU_VAV_TOP | 28782353.94 | 0.00 | 28782353.94 | 22614548.33 | 4177.05 | 1.94 | 4581.01 | 86.27 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3659 | 0.0000 | 1.3659 | 0.7171 | 1408.57 | 2.79 | 4531.64 |
PACU_VAV_MID | 1.3506 | 0.0000 | 1.3506 | 0.7084 | 1380.79 | 2.19 | 4560.02 |
PACU_VAV_TOP | 1.3312 | 0.0000 | 1.3312 | 0.7171 | 1412.05 | 1.69 | 4529.26 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 443.09 | 2276.49 | 0.00 | 0.00 | 0.00 | 2400.64 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 94.63 | 2401.87 | 0.00 | 0.00 | 0.00 | 2674.13 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 105.96 | 1964.01 | 0.00 | 0.00 | 0.00 | 2741.59 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3299 | 2.4510 | 0.0000 | 0.0000 | 0.0000 | 1.1363 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3209 | 2.4417 | 0.0000 | 0.0000 | 0.0000 | 1.0450 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.3145 | 2.5655 | 0.0000 | 0.0000 | 0.0000 | 1.0792 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 954 |
Defaulted Fields | 550 |
Fields with Defaults | 2304 |
Autosized Fields | 153 |
Autosizable Fields | 205 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1534.10 | 11240.73 | 02-APR-17:10 | 250223.45 | 02-JAN-08:10 |
Electricity:Building | 820.71 | 11072.20 | 02-APR-17:10 | 58110.10 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 820.71 | 11072.20 | 02-APR-17:10 | 58110.10 | 02-JAN-08:10 |
InteriorLights:Electricity | 172.96 | 772.31 | 12-FEB-11:30 | 17672.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 172.96 | 772.31 | 12-FEB-11:30 | 17672.30 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 172.96 | 772.31 | 12-FEB-11:30 | 17672.30 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 172.96 | 772.31 | 12-FEB-11:30 | 17672.30 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.89 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.56 | 19.49 | 12-FEB-11:30 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.56 | 19.49 | 12-FEB-11:30 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.88 | 256.76 | 02-APR-17:10 | 1374.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.47 | 12.34 | 16-JAN-12:10 | 465.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.47 | 12.34 | 16-JAN-12:10 | 465.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.71 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.38 | 19.49 | 15-JAN-12:00 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.38 | 19.49 | 15-JAN-12:00 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.86 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.46 | 12.34 | 05-FEB-12:10 | 465.57 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.46 | 12.34 | 05-FEB-12:10 | 465.57 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.88 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.55 | 19.49 | 12-FEB-11:10 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.55 | 19.49 | 12-FEB-11:10 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.87 | 256.76 | 02-APR-17:10 | 1374.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.47 | 12.34 | 16-JAN-12:00 | 465.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.47 | 12.34 | 16-JAN-12:00 | 465.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.70 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.36 | 19.49 | 15-JAN-11:50 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.36 | 19.49 | 15-JAN-11:50 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.86 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.45 | 12.34 | 05-FEB-11:50 | 465.57 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.45 | 12.34 | 05-FEB-11:50 | 465.57 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.89 | 405.59 | 02-APR-17:10 | 2170.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.56 | 19.49 | 12-FEB-11:30 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.56 | 19.49 | 12-FEB-11:30 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.88 | 256.76 | 02-APR-17:10 | 1374.17 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.47 | 12.34 | 16-JAN-12:10 | 465.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.47 | 12.34 | 16-JAN-12:10 | 465.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.71 | 405.59 | 12-MAR-17:10 | 2170.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.38 | 19.49 | 15-JAN-12:00 | 735.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.38 | 19.49 | 15-JAN-12:00 | 735.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.86 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.46 | 12.34 | 05-FEB-12:10 | 465.57 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.46 | 12.34 | 05-FEB-12:10 | 465.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 103.79 | -0.00 | 05-JAN-13:40 | 22915.57 | 01-JUN-12:30 |
ElectricityProduced:Plant | 103.79 | -0.00 | 05-JAN-13:40 | 22915.57 | 01-JUN-12:30 |
Photovoltaic:ElectricityProduced | 109.32 | 0.00 | 01-JAN-00:10 | 23816.33 | 01-JUN-12:30 |
PowerConversion:ElectricityProduced | -5.54 | -900.77 | 01-JUN-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 06-JAN-17:20 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 675.78 | 168.53 | 02-APR-17:10 | 212914.09 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.79 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.79 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1430.83 | 0.00 | 26-MAR-11:30 | 250223.45 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 1430.83 | 0.00 | 26-MAR-11:30 | 250223.45 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1430.83 | 0.00 | 26-MAR-11:30 | 250223.45 | 02-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1430.83 | 0.00 | 26-MAR-11:30 | 250223.45 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.51 | 0.00 | 01-JAN-00:10 | 7481.18 | 21-MAY-12:40 |
ElectricitySurplusSold:Plant | 0.51 | 0.00 | 01-JAN-00:10 | 7481.18 | 21-MAY-12:40 |
Cogeneration:ElectricitySurplusSold | 0.51 | 0.00 | 01-JAN-00:10 | 7481.18 | 21-MAY-12:40 |
General:Cogeneration:ElectricitySurplusSold | 0.51 | 0.00 | 01-JAN-00:10 | 7481.18 | 21-MAY-12:40 |
ElectricityNet:Facility | 1430.31 | -7481.18 | 21-MAY-12:40 | 250223.45 | 02-JAN-08:10 |
ElectricityNet:Plant | 1430.31 | -7481.18 | 21-MAY-12:40 | 250223.45 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 1430.31 | -7481.18 | 21-MAY-12:40 | 250223.45 | 02-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1430.31 | -7481.18 | 21-MAY-12:40 | 250223.45 | 02-JAN-08:10 |
Heating:Electricity | 517.47 | 0.00 | 01-JAN-00:40 | 203187.01 | 02-JAN-06:20 |
General:Heating:Electricity | 517.47 | 0.00 | 01-JAN-00:40 | 203187.01 | 02-JAN-06:20 |
Fans:Electricity | 78.43 | 0.00 | 01-JAN-00:40 | 24354.03 | 12-JUL-15:20 |
General:Fans:Electricity | 78.43 | 0.00 | 01-JAN-00:40 | 24354.03 | 12-JUL-15:20 |
ExteriorLights:Electricity | 37.46 | 0.00 | 01-JAN-11:20 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 37.46 | 0.00 | 01-JAN-11:20 | 3824.74 | 01-JAN-06:10 |
HeatRecovery:Electricity | 21.83 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:30 |
General:HeatRecovery:Electricity | 21.83 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:30 |
Cooling:Electricity | 46.43 | 0.00 | 01-JAN-00:10 | 42928.32 | 30-JUN-14:30 |
General:Cooling:Electricity | 46.43 | 0.00 | 01-JAN-00:10 | 42928.32 | 30-JUN-14:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 06-JAN-17:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 06-JAN-17:20 |
WIRED_LTG_ELECTRICITY | 4.86 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 383.64 | 1886.44 | 30-JAN-05:30 | 211342.65 | 12-JAN-07:50 |
NaturalGas:HVAC | 234.28 | 0.00 | 01-JAN-00:40 | 203018.77 | 12-JAN-08:00 |
Heating:NaturalGas | 234.28 | 0.00 | 01-JAN-00:40 | 203018.77 | 12-JAN-08:00 |
General:Heating:NaturalGas | 234.28 | 0.00 | 01-JAN-00:40 | 203018.77 | 12-JAN-08:00 |
NaturalGas:Plant | 149.36 | 1886.44 | 04-JAN-05:10 | 14118.46 | 02-JAN-12:40 |
WaterSystems:NaturalGas | 149.36 | 1886.44 | 04-JAN-05:10 | 14118.46 | 02-JAN-12:40 |
Water Heater:WaterSystems:NaturalGas | 149.36 | 1886.44 | 04-JAN-05:10 | 14118.46 | 02-JAN-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2557.27 | 0.00 | 01-JAN-00:40 | 532017.40 | 27-FEB-07:10 |
EnergyTransfer:Building | 1115.39 | 0.00 | 01-JAN-00:40 | 203789.06 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 145.34 | 0.00 | 01-JAN-00:40 | 21049.79 | 24-JUL-08:00 |
Heating:EnergyTransfer | 470.31 | 0.00 | 01-JAN-00:40 | 203789.06 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.81 | 0.00 | 01-JAN-00:20 | 17202.01 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 470.31 | 0.00 | 01-JAN-00:40 | 203789.06 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.81 | 0.00 | 01-JAN-00:20 | 17202.01 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 645.08 | 0.00 | 01-JAN-00:40 | 140124.85 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 143.53 | 0.00 | 01-JAN-00:40 | 21049.79 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 645.08 | 0.00 | 01-JAN-00:40 | 140124.85 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 143.53 | 0.00 | 01-JAN-00:40 | 21049.79 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.27 | 0.00 | 01-JAN-00:40 | 17153.33 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.61 | 0.00 | 01-JAN-00:40 | 17153.33 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.61 | 0.00 | 01-JAN-00:40 | 17153.33 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 13.65 | 0.00 | 01-JAN-00:10 | 7196.47 | 21-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 13.65 | 0.00 | 01-JAN-00:10 | 7196.47 | 21-JUL-14:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.59 | 0.00 | 01-JAN-00:40 | 10424.90 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 19.38 | 0.00 | 01-JAN-00:40 | 10424.90 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 19.38 | 0.00 | 01-JAN-00:40 | 10424.90 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.20 | 0.00 | 01-JAN-00:10 | 4514.63 | 24-JUL-06:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.20 | 0.00 | 01-JAN-00:10 | 4514.63 | 24-JUL-06:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.54 | 0.00 | 01-JAN-00:40 | 9058.41 | 02-JAN-08:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.92 | 0.00 | 01-JAN-00:40 | 9058.41 | 02-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.92 | 0.00 | 01-JAN-00:40 | 9058.41 | 02-JAN-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.62 | 0.00 | 01-JAN-00:10 | 4225.05 | 24-JUL-06:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.62 | 0.00 | 01-JAN-00:10 | 4225.05 | 24-JUL-06:20 |
EnergyTransfer:Zone:CORE_MID | 113.39 | 0.00 | 01-JAN-00:40 | 20290.93 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 8.62 | 0.00 | 01-JAN-00:40 | 20290.93 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 8.62 | 0.00 | 01-JAN-00:40 | 20290.93 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 104.77 | 0.00 | 01-JAN-00:20 | 17605.51 | 24-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 104.77 | 0.00 | 01-JAN-00:20 | 17605.51 | 24-JUL-07:20 |
EnergyTransfer:Zone:CORE_TOP | 120.37 | 0.00 | 01-JAN-00:40 | 26130.83 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 33.66 | 0.00 | 01-JAN-00:40 | 26130.83 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 33.66 | 0.00 | 01-JAN-00:40 | 26130.83 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 86.72 | 0.00 | 01-JAN-00:20 | 17073.13 | 24-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 86.72 | 0.00 | 01-JAN-00:20 | 17073.13 | 24-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 59.64 | 0.00 | 01-JAN-00:40 | 8724.17 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.83 | 0.00 | 01-JAN-00:40 | 8724.17 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.83 | 0.00 | 01-JAN-00:40 | 8724.17 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.81 | 0.00 | 01-JAN-00:10 | 6189.20 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.81 | 0.00 | 01-JAN-00:10 | 6189.20 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.47 | 0.00 | 01-JAN-00:40 | 10113.43 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.08 | 0.00 | 01-JAN-00:40 | 9744.74 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.08 | 0.00 | 01-JAN-00:40 | 9744.74 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.39 | 0.00 | 01-JAN-00:20 | 10113.43 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.39 | 0.00 | 01-JAN-00:20 | 10113.43 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 71.53 | 0.00 | 01-JAN-00:40 | 14659.92 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.40 | 0.00 | 01-JAN-00:40 | 14659.92 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.40 | 0.00 | 01-JAN-00:40 | 14659.92 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.13 | 0.00 | 01-JAN-00:20 | 14414.10 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.13 | 0.00 | 01-JAN-00:20 | 14414.10 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.84 | 0.00 | 01-JAN-00:40 | 9791.22 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.51 | 0.00 | 01-JAN-00:40 | 9791.22 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.51 | 0.00 | 01-JAN-00:40 | 9791.22 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.33 | 0.00 | 01-JAN-00:20 | 8080.49 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.33 | 0.00 | 01-JAN-00:20 | 8080.49 | 11-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 46.61 | 0.00 | 01-JAN-00:40 | 6980.12 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 31.54 | 0.00 | 01-JAN-00:40 | 6980.12 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 31.54 | 0.00 | 01-JAN-00:40 | 6980.12 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.07 | 0.00 | 01-JAN-00:10 | 5015.20 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.07 | 0.00 | 01-JAN-00:10 | 5015.20 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 38.93 | 0.00 | 01-JAN-00:40 | 8080.91 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.17 | 0.00 | 01-JAN-00:40 | 8080.91 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.17 | 0.00 | 01-JAN-00:40 | 8080.91 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.76 | 0.00 | 01-JAN-00:20 | 7714.14 | 07-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.76 | 0.00 | 01-JAN-00:20 | 7714.14 | 07-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 92.27 | 0.00 | 01-JAN-00:40 | 21716.95 | 12-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 68.72 | 0.00 | 01-JAN-00:40 | 21716.95 | 12-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 68.72 | 0.00 | 01-JAN-00:40 | 21716.95 | 12-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 23.56 | 0.00 | 01-JAN-00:20 | 11159.88 | 11-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 23.56 | 0.00 | 01-JAN-00:20 | 11159.88 | 11-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.85 | 0.00 | 01-JAN-00:40 | 8379.17 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.58 | 0.00 | 01-JAN-00:40 | 8379.17 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.58 | 0.00 | 01-JAN-00:40 | 8379.17 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.27 | 0.00 | 01-JAN-00:20 | 6378.33 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.27 | 0.00 | 01-JAN-00:20 | 6378.33 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 45.41 | 0.00 | 01-JAN-00:40 | 7888.32 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.82 | 0.00 | 01-JAN-00:40 | 7888.32 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.82 | 0.00 | 01-JAN-00:40 | 7888.32 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.59 | 0.00 | 01-JAN-00:10 | 6591.58 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.59 | 0.00 | 01-JAN-00:10 | 6591.58 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.14 | 0.00 | 01-JAN-00:40 | 10130.43 | 07-JUL-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.24 | 0.00 | 01-JAN-00:40 | 7804.05 | 27-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.24 | 0.00 | 01-JAN-00:40 | 7804.05 | 27-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.90 | 0.00 | 01-JAN-00:20 | 10130.43 | 07-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.90 | 0.00 | 01-JAN-00:20 | 10130.43 | 07-JUL-08:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 60.50 | 0.00 | 01-JAN-00:40 | 14198.98 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 19.35 | 0.00 | 01-JAN-00:40 | 11831.81 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 19.35 | 0.00 | 01-JAN-00:40 | 11831.81 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.14 | 0.00 | 01-JAN-00:20 | 14198.98 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.14 | 0.00 | 01-JAN-00:20 | 14198.98 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.70 | 0.00 | 01-JAN-00:40 | 7849.52 | 11-JUL-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 16.06 | 0.00 | 01-JAN-00:40 | 7752.11 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 16.06 | 0.00 | 01-JAN-00:40 | 7752.11 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.64 | 0.00 | 01-JAN-00:20 | 7849.52 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.64 | 0.00 | 01-JAN-00:20 | 7849.52 | 11-JUL-17:40 |
PlantLoopHeatingDemand:Facility | 64.03 | 0.00 | 01-JAN-00:10 | 7551.96 | 28-APR-11:20 |
PlantLoopHeatingDemand:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.96 | 28-APR-11:20 |
WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.96 | 28-APR-11:20 |
General:WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.96 | 28-APR-11:20 |
EnergyTransfer:HVAC | 1377.86 | 0.00 | 01-JAN-00:40 | 336577.98 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 714.26 | 0.00 | 01-JAN-00:40 | 336577.98 | 27-FEB-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 473.35 | 0.00 | 01-JAN-00:10 | 106328.84 | 07-NOV-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 0.19 | 0.00 | 01-JAN-00:10 | 13620.22 | 29-JUL-16:00 |
CoolingCoils:EnergyTransfer | 190.05 | 0.00 | 01-JAN-00:10 | 177639.09 | 30-JUN-12:30 |
EnergyTransfer:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.96 | 28-APR-11:20 |
WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.96 | 28-APR-11:20 |
WaterUse:WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.96 | 28-APR-11:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 1.812 | -143.528 | 0.000 | 0.000 | 34.682 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -111.246 |
CORE_MID | 0.000 | 0.000 | 8.620 | -104.771 | 0.000 | 0.000 | 35.659 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.729 |
CORE_TOP | 0.000 | 0.000 | 33.657 | -86.717 | 0.000 | 0.000 | 36.182 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -138.343 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 40.831 | -18.809 | 0.000 | 0.000 | 7.731 | 5.562 | 24.333 | 14.682 | 0.000 | 0.005 | 0.001 | 0.000 | -48.800 | 0.000 | -8.496 | -17.038 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 25.083 | -22.391 | 0.000 | 0.000 | 4.820 | 3.474 | 15.404 | 33.596 | 0.000 | 0.003 | 0.000 | 0.000 | -31.117 | 0.000 | -5.742 | -23.130 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 33.402 | -38.131 | 0.000 | 0.000 | 7.578 | 5.377 | 24.332 | 66.098 | 0.000 | 0.004 | 0.001 | 0.000 | -44.660 | 0.000 | -8.735 | -45.265 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 26.507 | -17.330 | 0.000 | 0.000 | 4.872 | 3.461 | 15.403 | 23.378 | 0.000 | 0.003 | 0.000 | 0.000 | -31.941 | 0.000 | -5.764 | -18.590 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 31.537 | -15.072 | 0.000 | 0.000 | 7.740 | 5.545 | 24.333 | 15.042 | 0.000 | 0.003 | 0.000 | 0.000 | -49.230 | 0.000 | -4.573 | -15.324 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 19.172 | -19.755 | 0.000 | 0.000 | 4.811 | 3.466 | 15.404 | 33.756 | 0.000 | 0.002 | 0.000 | 0.000 | -31.615 | 0.000 | -3.134 | -22.106 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 68.715 | -23.558 | 0.000 | 0.000 | 7.876 | 5.364 | 24.332 | 66.734 | 0.000 | 0.082 | 0.001 | 0.000 | -44.902 | 0.000 | -75.159 | -29.484 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 20.579 | -14.270 | 0.000 | 0.000 | 4.856 | 3.452 | 15.403 | 23.590 | 0.000 | 0.002 | 0.000 | 0.000 | -32.414 | 0.000 | -3.130 | -18.068 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 24.820 | -20.592 | 0.000 | 0.000 | 7.667 | 5.562 | 24.333 | 14.485 | 0.000 | 0.004 | 1.183 | 0.000 | -50.169 | 0.000 | -7.292 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 15.236 | -22.899 | 0.000 | 0.000 | 3.539 | 3.474 | 15.404 | 33.388 | 0.000 | 0.002 | 0.001 | 0.000 | -31.925 | 0.000 | -4.927 | -11.291 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 19.354 | -41.143 | 0.000 | 0.000 | 7.513 | 5.377 | 24.332 | 65.839 | 0.000 | 0.004 | 0.000 | 0.000 | -45.968 | 0.000 | -7.500 | -27.807 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 16.058 | -18.642 | 0.000 | 0.000 | 4.835 | 3.461 | 15.403 | 23.266 | 0.000 | 0.002 | 0.000 | 0.000 | -32.830 | 0.000 | -4.942 | -6.613 |
TOPFLOOR_PLENUM | 51.614 | -13.651 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -12.953 | -25.012 |
MIDFLOOR_PLENUM | 19.385 | -10.202 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.004 | 3.198 | 0.000 | 0.000 | 0.000 | -12.384 | -0.001 |
FIRSTFLOOR_PLENUM | 13.924 | -13.617 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 9.476 | 0.000 | 0.000 | 0.000 | -9.785 | -0.001 |
Total Facility | 84.922 | -37.471 | 385.383 | -607.610 | 0.000 | 0.000 | 180.361 | 172.963 | 647.750 | 413.854 | 0.000 | 0.125 | 13.863 | 0.000 | -475.571 | 0.000 | -174.516 | -604.049 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUN-05:12 | 0.00 | 0.00 | 0.00 | -34651.97 | 0.00 | 0.00 | 328.94 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 29887.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -30461.97 | 0.00 | 0.00 | 685.35 | 1162.90 | 3025.92 | 0.00 | 0.00 | 0.00 | 25587.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -29724.90 | 0.00 | 0.00 | 694.12 | 1162.90 | 3025.92 | 0.00 | 0.00 | 0.00 | 24841.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -9438.48 | 0.00 | 0.00 | 63.31 | 38.98 | 637.89 | 7870.63 | 0.00 | 0.00 | 891.15 | 0.00 | -0.00 | 0.00 | -63.47 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:31 | 0.00 | 0.00 | 0.00 | -15039.02 | 0.00 | 0.00 | 13.83 | 12.34 | 302.86 | 11123.18 | 0.00 | 0.00 | 3853.58 | 0.00 | -0.00 | 0.00 | -266.77 | 0.00 |
PERIMETER_TOP_ZN_1 | 21-MAY-13:22 | 0.00 | 0.00 | 0.00 | -22676.32 | 0.00 | 0.00 | 22.97 | 19.49 | 478.41 | 17947.43 | 0.00 | 0.00 | 4831.38 | 0.00 | -0.00 | 0.00 | -623.35 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-18:12 | 0.00 | 0.00 | 0.00 | -14391.21 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 10376.78 | 0.00 | 0.00 | 4189.50 | 0.00 | -0.00 | 0.00 | -431.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-05:14 | 0.00 | 0.00 | 0.00 | -7802.08 | 0.00 | 0.00 | 65.10 | 38.98 | 637.89 | 7933.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -31.33 | -842.09 |
PERIMETER_BOT_ZN_2 | 23-JUL-10:01 | 0.00 | 0.00 | 0.00 | -11224.72 | 0.00 | 0.00 | 15.53 | 12.34 | 302.86 | 10288.28 | 0.00 | 0.00 | 637.28 | 0.00 | -0.00 | 0.00 | -31.56 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-JUL-14:01 | 0.00 | 0.00 | 0.00 | -17624.04 | 0.00 | 0.00 | 23.89 | 19.49 | 478.41 | 15577.87 | 0.00 | 0.00 | 1546.79 | 0.00 | -0.00 | 0.00 | -22.41 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-17:22 | 0.00 | 0.00 | 0.00 | -9826.48 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 8332.48 | 0.00 | 0.00 | 1434.97 | 0.00 | -0.00 | 0.00 | -197.72 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -9016.95 | 0.00 | 0.00 | 62.58 | 38.98 | 637.89 | 7853.88 | 0.00 | 0.00 | 477.64 | 0.00 | -0.00 | 0.00 | -54.01 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-07:02 | 0.00 | 0.00 | 0.00 | -14148.21 | 0.00 | 0.00 | 15.07 | 12.34 | 302.86 | 10075.98 | 0.00 | 0.00 | 3920.07 | 0.00 | -0.00 | 0.00 | -178.11 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-13:12 | 0.00 | 0.00 | 0.00 | -20955.99 | 0.00 | 0.00 | 20.24 | 19.49 | 478.41 | 17506.61 | 0.00 | 0.00 | 2968.20 | 0.00 | -0.00 | 0.00 | -36.96 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUN-15:22 | 0.00 | 0.00 | 0.00 | -12981.55 | 0.00 | 0.00 | 16.40 | 12.34 | 302.86 | 8503.43 | 0.00 | 0.00 | 4351.12 | 0.00 | -0.00 | 0.00 | -204.59 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:20 | 0.00 | -7197.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 7188.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -5887.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5947.58 | 0.00 | -0.00 | 0.00 | -60.27 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -5788.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5835.17 | 0.00 | -0.00 | 0.00 | -46.21 | 0.00 |
Total Facility | 24-JUL-06:02 | 0.00 | -6992.76 | 0.00 | -179820.13 | 0.00 | 0.00 | 3494.72 | 4634.49 | 18346.02 | 28510.96 | 0.00 | 0.00 | 140587.24 | 0.00 | 0.00 | 0.00 | -8760.54 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 20316.68 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 3464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24168.51 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 23268.08 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26097.77 |
CORE_TOP | 01-JAN-22:42 | 0.00 | 0.00 | 29419.49 | 0.00 | 0.00 | 0.00 | 0.00 | 193.79 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31444.82 |
PERIMETER_TOP_ZN_3 | 29-JAN-02:12 | 0.00 | 0.00 | 9571.37 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3599.62 | 0.00 | -2456.67 | -3942.03 |
PERIMETER_TOP_ZN_2 | 29-JAN-02:12 | 0.00 | 0.00 | 12557.75 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2395.42 | 0.00 | -1660.94 | -8771.67 |
PERIMETER_TOP_ZN_1 | 30-JAN-02:52 | 0.00 | 0.00 | 19455.45 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3356.78 | 0.00 | -1495.98 | -15158.35 |
PERIMETER_TOP_ZN_4 | 29-JAN-02:12 | 0.00 | 0.00 | 12909.40 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2343.54 | 0.00 | -1664.18 | -9171.96 |
PERIMETER_BOT_ZN_3 | 01-JAN-18:42 | 0.00 | 0.00 | 7676.60 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2465.78 | 0.00 | -739.35 | -4898.42 |
PERIMETER_BOT_ZN_2 | 01-JAN-18:42 | 0.00 | 0.00 | 9870.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1642.07 | 0.00 | -503.70 | -7994.77 |
PERIMETER_BOT_ZN_1 | 12-JAN-08:00 | 0.00 | 0.00 | 21716.93 | 0.00 | 0.00 | 0.00 | 267.84 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 24299.08 | 0.00 | -3918.33 | 0.00 | -43248.55 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-18:42 | 0.00 | 0.00 | 10287.44 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1610.56 | 0.00 | -504.95 | -8442.21 |
PERIMETER_MID_ZN_3 | 01-JAN-18:42 | 0.00 | 0.00 | 8665.39 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2505.13 | 0.00 | -1163.08 | -5424.14 |
PERIMETER_MID_ZN_2 | 30-JAN-02:52 | 0.00 | 0.00 | 10387.22 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2286.67 | 0.00 | -842.70 | -7609.60 |
PERIMETER_MID_ZN_1 | 30-JAN-04:52 | 0.00 | 0.00 | 15628.70 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3475.12 | 0.00 | -1108.55 | -11600.69 |
PERIMETER_MID_ZN_4 | 30-JAN-02:52 | 0.00 | 0.00 | 10349.93 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2330.18 | 0.00 | -842.19 | -7529.32 |
TOPFLOOR_PLENUM | 12-JAN-06:12 | 18069.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18069.03 |
MIDFLOOR_PLENUM | 02-JAN-07:05 | 11000.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -278.61 | -10721.45 |
FIRSTFLOOR_PLENUM | 02-JAN-08:14 | 9209.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -248.68 | -8961.03 |
Total Facility | 02-JAN-05:01 | 17009.27 | 0.00 | 204357.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25730.48 | 0.00 | -4667.75 | -206324.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.2918 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5114 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4272 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3566 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.5056 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7552 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6459 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0767 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7136 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0754 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7528 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0790 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4336 | 2.4336 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0569 | 2.0569 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0042 | 2.0042 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6020 | 0.6020 | 0.1385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8067 | 0.8067 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2611 | 1.2611 | 0.1337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8317 | 0.8317 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4974 | 0.4974 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6554 | 0.6554 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0204 | 1.0204 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6850 | 0.6850 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5641 | 0.5641 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8073 | 0.8073 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2047 | 1.2047 | 0.1337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7943 | 0.7943 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.2918 | 4.5114 | 5.2918 | 1.0767 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4272 | 4.3566 | 5.4272 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.5056 | 4.7552 | 5.5056 | 1.0790 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2168 | 1.2168 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0284 | 1.0284 | 0.6376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0021 | 1.0021 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3010 | 0.3010 | 0.1385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4033 | 0.4033 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6305 | 0.6305 | 0.1337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4159 | 0.4159 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2487 | 0.2487 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3277 | 0.3277 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5102 | 0.5102 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3425 | 0.3425 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2820 | 0.2820 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4036 | 0.4036 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6023 | 0.6023 | 0.1337 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3972 | 0.3972 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6459 | 1.0767 | 1.0767 | 1.0767 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7136 | 1.0754 | 1.0754 | 1.0754 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7528 | 1.0790 | 1.0790 | 1.0790 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 748.17 |
Number of hours cooling loads not met | 60.00 |
Number of hours not met | 808.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 517.47 | 203187.01 | 234.28 | 203018.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 46.43 | 42928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 172.96 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 37.46 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 829.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 78.43 | 24354.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 21.83 | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 149.36 | 14118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1534.10 |
Natural Gas | 0.00 | 383.64 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1917.74 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 109.32 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 34.72 |
Space Heating | 103.86 |
Space Cooling | 9.32 |
Fans (All) | 15.74 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 307.92 |
Subtotal | 307.92 |
Natural Gas [MJ/m2] | |
Space Heating | 47.02 |
Service Water Heating | 29.98 |
Miscellaneous (All) | 77.00 |
Subtotal | 77.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.02 |
Space Heating | 39.20 |
Space Cooling | 2.42 |
Fans (All) | 4.09 |
Service Water Heating | 7.79 |
Receptacle Equipment | 33.78 |
Miscellaneous | 3.71 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 831. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8746.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8740.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 20.00 | 0.00 | 0.00 | 0.00 |
Average | 8753.07 | 6.93 | 0.00 | 0.00 | 0.00 |
Sum | 157555.33 | 124.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8734.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 25.67 | 0.00 | 0.00 | 0.00 |
Average | 8753.09 | 6.91 | 0.00 | 0.00 | 0.00 |
Sum | 157555.67 | 124.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128288.67 | 15.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 15.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.26 | 1.07 | 0.00 | 0.00 | 0.00 |
Sum | 614560.67 | 19.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.558633E+10 | 5483.31 | 27-JAN-17:00 | -12.2 | -12.5 | 0.155114E+10 | 2279.79 | 27-JAN-14:09 | -12.2 | -12.5 |
February | 0.621114E+10 | 5916.53 | 17-FEB-16:40 | -10.4 | -12.1 | 0.147110E+10 | 2412.49 | 17-FEB-14:09 | -10.4 | -12.1 |
March | 0.795104E+10 | 6749.30 | 23-MAR-15:30 | -1.7 | -4.0 | 0.190334E+10 | 2590.55 | 23-MAR-13:09 | -1.7 | -4.0 |
April | 0.106395E+11 | 14925.89 | 25-APR-07:02 | -2.9 | -5.2 | 0.186153E+10 | 2608.04 | 18-APR-13:20 | -2.9 | -5.2 |
May | 0.178566E+11 | 31725.14 | 15-MAY-06:02 | 8.07 | 2.53 | 0.207362E+10 | 2606.67 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.205465E+11 | 34648.80 | 05-JUN-05:12 | 10.77 | 8.82 | 0.207045E+10 | 2606.68 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.202344E+11 | 34463.43 | 24-JUL-05:12 | 13.17 | 12.61 | 0.192478E+10 | 2606.98 | 19-JUL-09:09 | 13.17 | 12.61 |
August | 0.205092E+11 | 34438.41 | 01-AUG-06:02 | 10.10 | 9.72 | 0.215946E+10 | 2606.66 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.139900E+11 | 23513.04 | 11-SEP-06:02 | 5.50 | 4.95 | 0.190952E+10 | 2608.29 | 29-SEP-13:20 | 0.97 | -0.9 |
October | 0.844247E+10 | 12259.07 | 04-OCT-07:15 | 7.80 | 2.92 | 0.186949E+10 | 2606.63 | 13-OCT-09:30 | -7.8 | -8.6 |
November | 0.600867E+10 | 5800.18 | 03-NOV-16:00 | -11.1 | -11.5 | 0.161212E+10 | 2374.14 | 03-NOV-13:09 | -11.1 | -11.5 |
December | 0.555173E+10 | 5310.98 | 22-DEC-17:00 | -21.7 | -22.0 | 0.150549E+10 | 2229.89 | 22-DEC-14:09 | -21.7 | -22.0 |
Annual Sum or Average | 0.143527E+12 | 0.219121E+11 | ||||||||
Minimum of Months | 0.555173E+10 | 5310.98 | -21.7 | -22.0 | 0.147110E+10 | 2229.89 | -21.7 | -22.0 | ||
Maximum of Months | 0.205465E+11 | 34648.80 | 13.17 | 12.61 | 0.215946E+10 | 2608.29 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 3388456.20 | 531.34 | 22-MAR-17:15 | 4.67 | 1.29 | 0.00 | 0.00 | 01-MAR-00:10 | 4.67 | 1.29 |
April | 0.571240E+09 | 3604.18 | 21-APR-15:20 | 14.07 | 5.57 | 0.00 | 0.00 | 01-APR-00:10 | 14.07 | 5.57 |
May | 0.226823E+10 | 6267.80 | 31-MAY-14:30 | 20.55 | 10.45 | 0.00 | 0.00 | 01-MAY-00:10 | 20.55 | 10.45 |
June | 0.405723E+10 | 7136.48 | 29-JUN-14:40 | 25.93 | 16.13 | 0.00 | 0.00 | 01-JUN-00:10 | 25.93 | 16.13 |
July | 0.395431E+10 | 7196.47 | 21-JUL-14:20 | 26.67 | 14.48 | 0.00 | 0.00 | 01-JUL-00:10 | 26.67 | 14.48 |
August | 0.248179E+10 | 6085.92 | 10-AUG-15:20 | 22.40 | 12.08 | 0.00 | 0.00 | 01-AUG-00:10 | 22.40 | 12.08 |
September | 0.313764E+09 | 2545.32 | 07-SEP-15:20 | 16.47 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.47 | 8.91 |
October | 1533087.49 | 335.05 | 03-OCT-16:40 | 11.30 | 5.55 | 0.00 | 0.00 | 01-OCT-00:10 | 11.30 | 5.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.136515E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.405723E+10 | 7196.47 | 26.67 | 16.13 | 0.00 | 0.00 | 26.67 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9308659.54 | 3584.01 | 12-JAN-05:11 | -38.0 | -38.0 | 0.00 | 0.00 | 01-JAN-00:10 | -38.0 | -38.0 |
February | 6154325.53 | 3250.21 | 25-FEB-05:01 | -24.4 | -24.9 | 0.00 | 0.00 | 01-FEB-00:10 | -24.4 | -24.9 |
March | 10854575.79 | 3434.16 | 01-MAR-05:01 | -28.3 | -28.7 | 0.00 | 0.00 | 01-MAR-00:10 | -28.3 | -28.7 |
April | 0.234587E+09 | 2062.26 | 01-APR-05:01 | -10.5 | -12.1 | 0.00 | 0.00 | 01-APR-00:10 | -10.5 | -12.1 |
May | 0.152868E+10 | 3047.35 | 31-MAY-15:30 | 21.65 | 10.77 | 0.00 | 0.00 | 01-MAY-00:10 | 21.65 | 10.77 |
June | 0.306229E+10 | 4021.27 | 05-JUN-06:15 | 11.30 | 8.88 | 0.00 | 0.00 | 01-JUN-00:10 | 11.30 | 8.88 |
July | 0.296884E+10 | 5887.23 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.205478E+10 | 3354.34 | 11-AUG-15:50 | 25.40 | 14.66 | 0.00 | 0.00 | 01-AUG-00:10 | 25.40 | 14.66 |
September | 0.291708E+09 | 1267.74 | 29-SEP-06:02 | -4.6 | -5.0 | 0.00 | 0.00 | 01-SEP-00:10 | -4.6 | -5.0 |
October | 23608087.87 | 2297.68 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 4705343.51 | 3276.16 | 29-NOV-05:01 | -28.9 | -29.1 | 0.00 | 0.00 | 01-NOV-00:10 | -28.9 | -29.1 |
December | 6860465.88 | 3788.53 | 15-DEC-05:01 | -33.2 | -33.3 | 0.00 | 0.00 | 01-DEC-00:10 | -33.2 | -33.3 |
Annual Sum or Average | 0.102024E+11 | 0.00 | ||||||||
Minimum of Months | 4705343.51 | 1267.74 | -38.0 | -38.0 | 0.00 | 0.00 | -38.0 | -38.0 | ||
Maximum of Months | 0.306229E+10 | 5887.23 | 25.40 | 14.66 | 0.00 | 0.00 | 25.40 | 14.66 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241944E+09 | 4024.64 | 12-JAN-17:10 | -35.8 | -35.9 | 0.00 | 0.00 | 01-JAN-00:10 | -35.8 | -35.9 |
February | 0.174346E+09 | 4181.49 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 0.238846E+09 | 4460.66 | 31-MAR-06:10 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.550568E+09 | 3202.95 | 01-APR-05:01 | -10.5 | -12.1 | 0.00 | 0.00 | 01-APR-00:10 | -10.5 | -12.1 |
May | 0.190604E+10 | 3053.41 | 15-MAY-06:05 | 8.07 | 2.53 | 0.00 | 0.00 | 01-MAY-00:10 | 8.07 | 2.53 |
June | 0.313702E+10 | 4361.45 | 22-JUN-06:13 | 15.57 | 11.82 | 0.00 | 0.00 | 01-JUN-00:10 | 15.57 | 11.82 |
July | 0.321895E+10 | 5788.85 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.263164E+10 | 4317.59 | 28-AUG-06:05 | 5.87 | 5.03 | 0.00 | 0.00 | 01-AUG-00:10 | 5.87 | 5.03 |
September | 0.799083E+09 | 2617.98 | 01-SEP-06:05 | 6.70 | 5.86 | 0.00 | 0.00 | 01-SEP-00:10 | 6.70 | 5.86 |
October | 0.168776E+09 | 2643.35 | 27-OCT-06:10 | -18.4 | -18.8 | 0.00 | 0.00 | 01-OCT-00:10 | -18.4 | -18.8 |
November | 0.265243E+09 | 3352.04 | 29-NOV-05:01 | -28.9 | -29.1 | 0.00 | 0.00 | 01-NOV-00:10 | -28.9 | -29.1 |
December | 0.285045E+09 | 3823.04 | 15-DEC-05:01 | -33.2 | -33.3 | 0.00 | 0.00 | 01-DEC-00:10 | -33.2 | -33.3 |
Annual Sum or Average | 0.136175E+11 | 0.00 | ||||||||
Minimum of Months | 0.168776E+09 | 2617.98 | -35.8 | -35.9 | 0.00 | 0.00 | -35.8 | -35.9 | ||
Maximum of Months | 0.321895E+10 | 5788.85 | 15.57 | 13.19 | 0.00 | 0.00 | 15.57 | 13.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264368E+10 | 4666.71 | 20-JAN-17:00 | -11.1 | -11.2 | 0.146728E+10 | 2051.77 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.346289E+10 | 5277.82 | 09-FEB-15:10 | 0.10 | -1.0 | 0.136854E+10 | 2224.99 | 09-FEB-14:00 | 0.10 | -1.0 |
March | 0.583284E+10 | 5859.74 | 22-MAR-15:40 | 5.60 | 2.48 | 0.172721E+10 | 2389.42 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.837915E+10 | 11430.69 | 28-APR-16:00 | 12.20 | 5.13 | 0.176367E+10 | 2606.64 | 25-APR-09:20 | 12.20 | 5.13 |
May | 0.142118E+11 | 25998.21 | 15-MAY-06:02 | 8.07 | 2.53 | 0.206578E+10 | 2606.66 | 16-MAY-09:20 | 6.33 | 4.90 |
June | 0.168967E+11 | 30193.98 | 05-JUN-06:03 | 11.20 | 8.82 | 0.206777E+10 | 2606.64 | 29-JUN-09:20 | 19.63 | 14.92 |
July | 0.164823E+11 | 30463.37 | 24-JUL-06:03 | 14.18 | 13.06 | 0.192212E+10 | 2606.89 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.155996E+11 | 27694.80 | 07-AUG-06:01 | 10.68 | 10.30 | 0.215472E+10 | 2606.65 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.976985E+10 | 11757.35 | 01-SEP-16:00 | 15.60 | 10.82 | 0.185652E+10 | 2608.18 | 05-SEP-09:39 | 7.07 | 6.33 |
October | 0.594724E+10 | 6434.33 | 05-OCT-15:10 | 10.68 | 5.71 | 0.165491E+10 | 2573.05 | 05-OCT-13:00 | 10.68 | 5.71 |
November | 0.309957E+10 | 4851.40 | 02-NOV-16:00 | -8.9 | -9.4 | 0.147357E+10 | 2113.56 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.244535E+10 | 4515.12 | 21-DEC-17:00 | -16.7 | -17.3 | 0.141258E+10 | 2010.39 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.104771E+12 | 0.209347E+11 | ||||||||
Minimum of Months | 0.244535E+10 | 4515.12 | -16.7 | -17.3 | 0.136854E+10 | 2010.39 | -16.7 | -17.3 | ||
Maximum of Months | 0.168967E+11 | 30463.37 | 15.60 | 13.06 | 0.215472E+10 | 2608.18 | 19.63 | 14.92 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787643E+09 | 3998.38 | 28-JAN-17:01 | -21.8 | -22.5 | 0.144983E+10 | 1929.05 | 30-JAN-10:39 | -25.2 | -25.6 |
February | 0.166801E+10 | 4915.74 | 09-FEB-15:20 | 0.20 | -0.9 | 0.132693E+10 | 2133.38 | 09-FEB-14:00 | 0.20 | -0.9 |
March | 0.380672E+10 | 5769.27 | 22-MAR-15:50 | 5.60 | 2.55 | 0.163917E+10 | 2317.21 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.706862E+10 | 11372.46 | 21-APR-16:00 | 14.40 | 5.45 | 0.167752E+10 | 2606.62 | 26-APR-13:20 | 10.93 | 4.19 |
May | 0.131034E+11 | 15202.80 | 31-MAY-15:50 | 22.02 | 10.78 | 0.204981E+10 | 2606.66 | 16-MAY-09:20 | 22.02 | 10.78 |
June | 0.164744E+11 | 25747.55 | 12-JUN-06:01 | 10.18 | 7.56 | 0.206497E+10 | 2606.64 | 27-JUN-09:20 | 13.90 | 13.13 |
July | 0.159685E+11 | 29725.96 | 24-JUL-06:03 | 14.18 | 13.06 | 0.191917E+10 | 2606.85 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.142094E+11 | 15332.15 | 01-AUG-14:00 | 19.40 | 14.22 | 0.214291E+10 | 2606.64 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.796249E+10 | 10882.85 | 01-SEP-16:00 | 15.60 | 10.82 | 0.176600E+10 | 2606.65 | 01-SEP-09:50 | 15.60 | 10.82 |
October | 0.390697E+10 | 6010.46 | 04-OCT-16:00 | 10.00 | 4.57 | 0.153958E+10 | 2445.75 | 04-OCT-13:00 | 10.00 | 4.57 |
November | 0.106838E+10 | 4245.52 | 08-NOV-15:50 | -15.7 | -16.1 | 0.143760E+10 | 1951.44 | 08-NOV-14:00 | -15.7 | -16.1 |
December | 0.692834E+09 | 3981.87 | 30-DEC-17:02 | -10.0 | -10.4 | 0.139885E+10 | 1928.98 | 04-DEC-10:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.867173E+11 | 0.204123E+11 | ||||||||
Minimum of Months | 0.692834E+09 | 3981.87 | -21.8 | -22.5 | 0.132693E+10 | 1928.98 | -25.2 | -25.6 | ||
Maximum of Months | 0.164744E+11 | 29725.96 | 22.02 | 14.22 | 0.214291E+10 | 2606.85 | 22.02 | 13.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6438483.31 | 829.95 | 07-JAN-17:02 | -9.0 | -9.0 | 0.302130E+09 | 406.72 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 7631663.13 | 840.50 | 11-FEB-17:03 | -1.2 | -2.7 | 0.274974E+09 | 406.70 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.111232E+09 | 1120.33 | 22-MAR-15:40 | 5.60 | 2.48 | 0.332191E+09 | 454.42 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.107268E+10 | 2325.83 | 28-APR-15:20 | 12.20 | 4.90 | 0.329715E+09 | 549.49 | 21-APR-13:20 | 12.20 | 4.90 |
May | 0.302560E+10 | 8817.83 | 31-MAY-05:12 | 12.43 | 7.84 | 0.428131E+09 | 549.50 | 19-MAY-13:20 | 12.43 | 7.84 |
June | 0.502816E+10 | 9329.07 | 08-JUN-05:12 | 8.67 | 6.37 | 0.435525E+09 | 549.51 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.469430E+10 | 9439.23 | 11-JUL-05:12 | 15.37 | 12.05 | 0.404834E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.333484E+10 | 5601.38 | 02-AUG-06:01 | 11.28 | 10.30 | 0.446098E+09 | 549.50 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.130190E+10 | 2303.58 | 01-SEP-15:50 | 15.50 | 10.82 | 0.344490E+09 | 549.49 | 01-SEP-13:20 | 15.50 | 10.82 |
October | 0.213311E+09 | 1143.38 | 04-OCT-15:50 | 10.18 | 4.62 | 0.309601E+09 | 465.48 | 04-OCT-13:00 | 10.18 | 4.62 |
November | 5613603.67 | 828.21 | 18-NOV-17:02 | -13.0 | -13.3 | 0.300236E+09 | 406.71 | 17-NOV-10:09 | -13.0 | -13.3 |
December | 7933233.37 | 827.16 | 30-DEC-17:02 | -10.0 | -10.4 | 0.291775E+09 | 406.78 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.188096E+11 | 0.419970E+10 | ||||||||
Minimum of Months | 5613603.67 | 827.16 | -13.0 | -13.3 | 0.274974E+09 | 406.70 | -28.5 | -28.7 | ||
Maximum of Months | 0.502816E+10 | 9439.23 | 15.50 | 12.05 | 0.446098E+09 | 549.54 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5800854.42 | 506.77 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192856E+09 | 257.50 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 22418864.37 | 594.88 | 09-FEB-11:45 | -2.0 | -2.3 | 0.175315E+09 | 267.73 | 15-FEB-10:00 | -15.6 | -15.8 |
March | 0.374093E+09 | 1891.19 | 31-MAR-09:25 | -17.0 | -18.1 | 0.224263E+09 | 347.88 | 27-MAR-09:39 | -17.0 | -18.1 |
April | 0.147145E+10 | 5800.56 | 22-APR-09:20 | 8.87 | 3.75 | 0.232049E+09 | 347.90 | 28-APR-09:09 | 6.70 | 3.13 |
May | 0.448654E+10 | 15039.56 | 14-MAY-09:31 | 15.73 | 8.25 | 0.275374E+09 | 348.34 | 12-MAY-09:00 | 15.73 | 8.25 |
June | 0.529115E+10 | 12108.32 | 13-JUN-05:12 | 12.40 | 9.24 | 0.276149E+09 | 348.43 | 07-JUN-09:50 | 12.40 | 9.24 |
July | 0.520609E+10 | 13900.18 | 23-JUL-09:32 | 20.17 | 14.57 | 0.256917E+09 | 348.60 | 07-JUL-09:39 | 20.17 | 14.57 |
August | 0.394804E+10 | 11088.31 | 10-AUG-06:01 | 10.78 | 7.96 | 0.286809E+09 | 348.33 | 10-AUG-09:00 | 17.80 | 11.30 |
September | 0.130467E+10 | 5228.31 | 10-SEP-10:23 | 13.60 | 7.47 | 0.233590E+09 | 347.88 | 08-SEP-13:20 | 13.60 | 7.47 |
October | 0.269307E+09 | 1783.75 | 03-OCT-09:50 | 3.43 | 2.35 | 0.202363E+09 | 347.87 | 03-OCT-09:20 | 3.43 | 2.35 |
November | 5045086.04 | 506.53 | 18-NOV-17:02 | -13.0 | -13.3 | 0.191093E+09 | 257.49 | 29-NOV-14:39 | -25.2 | -25.5 |
December | 6405521.52 | 505.13 | 30-DEC-17:02 | -10.0 | -10.4 | 0.185928E+09 | 257.54 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.223910E+11 | 0.273271E+10 | ||||||||
Minimum of Months | 5045086.04 | 505.13 | -17.0 | -18.1 | 0.175315E+09 | 257.49 | -25.2 | -25.5 | ||
Maximum of Months | 0.529115E+10 | 15039.56 | 20.17 | 14.57 | 0.286809E+09 | 348.60 | 20.17 | 14.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39240502.39 | 1021.89 | 25-JAN-13:40 | -19.5 | -19.7 | 0.305064E+09 | 446.76 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.329562E+09 | 3960.32 | 15-FEB-13:40 | -8.7 | -9.6 | 0.289532E+09 | 549.49 | 09-FEB-14:00 | -8.7 | -9.6 |
March | 0.148464E+10 | 7869.55 | 31-MAR-13:30 | -11.4 | -13.3 | 0.375897E+09 | 549.49 | 01-MAR-14:20 | -11.4 | -13.3 |
April | 0.411586E+10 | 13019.21 | 20-APR-14:00 | 14.40 | 6.23 | 0.365889E+09 | 549.65 | 20-APR-13:50 | 14.40 | 6.23 |
May | 0.632746E+10 | 22675.95 | 21-MAY-13:22 | 15.00 | 7.02 | 0.428893E+09 | 549.81 | 12-MAY-13:50 | 15.00 | 7.02 |
June | 0.743547E+10 | 17902.76 | 04-JUN-12:53 | 19.40 | 12.41 | 0.434962E+09 | 549.54 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.734743E+10 | 22406.06 | 23-JUL-13:32 | 25.00 | 15.26 | 0.404644E+09 | 550.02 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.684907E+10 | 21508.92 | 27-AUG-13:12 | 18.33 | 13.81 | 0.449734E+09 | 549.86 | 25-AUG-13:00 | 18.33 | 13.81 |
September | 0.318047E+10 | 15480.15 | 10-SEP-11:43 | 15.40 | 8.26 | 0.367716E+09 | 549.51 | 08-SEP-13:09 | 15.40 | 8.26 |
October | 0.916319E+09 | 8734.82 | 03-OCT-13:30 | 10.85 | 6.24 | 0.331995E+09 | 549.50 | 30-OCT-13:20 | -11.8 | -12.9 |
November | 95481222.08 | 1843.36 | 08-NOV-13:16 | -13.7 | -14.5 | 0.304537E+09 | 549.50 | 08-NOV-14:20 | -13.5 | -14.2 |
December | 10357104.54 | 799.30 | 30-DEC-17:02 | -10.0 | -10.4 | 0.293727E+09 | 406.77 | 22-DEC-10:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.381314E+11 | 0.435259E+10 | ||||||||
Minimum of Months | 10357104.54 | 799.30 | -19.5 | -19.7 | 0.289532E+09 | 406.77 | -18.9 | -19.2 | ||
Maximum of Months | 0.743547E+10 | 22675.95 | 25.00 | 15.26 | 0.449734E+09 | 550.02 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5988799.22 | 507.26 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192839E+09 | 257.49 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 19710694.75 | 584.24 | 09-FEB-15:20 | 0.20 | -0.9 | 0.175237E+09 | 262.92 | 09-FEB-14:00 | 0.20 | -0.9 |
March | 0.192238E+09 | 946.42 | 31-MAR-17:00 | -9.4 | -11.7 | 0.214282E+09 | 338.68 | 22-MAR-15:00 | -9.4 | -11.7 |
April | 0.155831E+10 | 7162.52 | 22-APR-17:08 | 14.13 | 6.18 | 0.216955E+09 | 347.85 | 26-APR-13:20 | 10.93 | 4.19 |
May | 0.293884E+10 | 14390.95 | 14-MAY-18:12 | 16.70 | 9.23 | 0.269942E+09 | 347.85 | 19-MAY-13:20 | 14.43 | 8.20 |
June | 0.434540E+10 | 13308.70 | 10-JUN-17:05 | 21.20 | 10.81 | 0.275407E+09 | 347.86 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.388202E+10 | 10748.42 | 09-JUL-19:53 | 19.40 | 13.11 | 0.256033E+09 | 347.88 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.307677E+10 | 9432.75 | 27-AUG-17:12 | 20.93 | 12.63 | 0.282741E+09 | 347.85 | 07-AUG-09:20 | 20.93 | 12.63 |
September | 0.111730E+10 | 5879.39 | 02-SEP-17:43 | 16.70 | 10.38 | 0.222163E+09 | 347.85 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.181199E+09 | 961.22 | 03-OCT-15:00 | 12.80 | 6.92 | 0.197978E+09 | 338.67 | 03-OCT-15:39 | 12.07 | 6.56 |
November | 6338458.22 | 508.65 | 18-NOV-17:02 | -13.0 | -13.3 | 0.191084E+09 | 257.48 | 29-NOV-14:00 | -25.6 | -25.8 |
December | 6492047.05 | 506.01 | 30-DEC-17:02 | -10.0 | -10.4 | 0.185915E+09 | 257.52 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.173306E+11 | 0.268058E+10 | ||||||||
Minimum of Months | 5988799.22 | 506.01 | -13.0 | -13.3 | 0.175237E+09 | 257.48 | -25.6 | -25.8 | ||
Maximum of Months | 0.434540E+10 | 14390.95 | 21.20 | 13.11 | 0.282741E+09 | 347.88 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8142079.15 | 806.45 | 07-JAN-17:02 | -9.0 | -9.0 | 0.298133E+09 | 406.71 | 11-JAN-14:39 | -34.0 | -34.1 |
February | 7166251.33 | 808.96 | 11-FEB-17:03 | -1.2 | -2.7 | 0.271726E+09 | 406.69 | 24-FEB-10:00 | -24.4 | -24.9 |
March | 28726645.00 | 865.99 | 22-MAR-14:00 | 5.60 | 1.90 | 0.331232E+09 | 406.69 | 03-MAR-14:09 | 5.60 | 1.90 |
April | 0.771195E+09 | 1238.12 | 28-APR-15:40 | 12.20 | 5.02 | 0.312715E+09 | 509.96 | 28-APR-13:00 | 12.20 | 5.02 |
May | 0.202663E+10 | 2521.89 | 31-MAY-14:30 | 20.55 | 10.45 | 0.417619E+09 | 549.50 | 12-MAY-09:20 | 20.55 | 10.45 |
June | 0.351282E+10 | 7405.00 | 13-JUN-05:12 | 12.40 | 9.24 | 0.434656E+09 | 549.50 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.372364E+10 | 7803.08 | 11-JUL-05:14 | 15.37 | 12.05 | 0.404492E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.298793E+10 | 6422.01 | 02-AUG-06:01 | 11.28 | 10.30 | 0.449614E+09 | 549.50 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.153128E+10 | 1845.48 | 01-SEP-13:50 | 14.82 | 10.69 | 0.362356E+09 | 549.49 | 13-SEP-13:20 | 11.87 | 8.91 |
October | 0.458469E+09 | 1148.94 | 06-OCT-15:00 | 10.60 | 4.90 | 0.315238E+09 | 484.84 | 06-OCT-13:00 | 10.60 | 4.90 |
November | 6455853.74 | 812.26 | 18-NOV-17:02 | -13.0 | -13.3 | 0.301176E+09 | 406.70 | 27-NOV-14:39 | -23.9 | -24.2 |
December | 9388991.59 | 807.26 | 30-DEC-17:02 | -10.0 | -10.4 | 0.291736E+09 | 406.76 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.150718E+11 | 0.419069E+10 | ||||||||
Minimum of Months | 6455853.74 | 806.45 | -13.0 | -13.3 | 0.271726E+09 | 406.69 | -34.0 | -34.1 | ||
Maximum of Months | 0.372364E+10 | 7803.08 | 20.55 | 12.05 | 0.449614E+09 | 549.54 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6217655.19 | 558.09 | 20-JAN-07:03 | -6.7 | -7.0 | 0.193006E+09 | 257.50 | 30-JAN-14:09 | -23.8 | -24.3 |
February | 12229202.42 | 560.87 | 15-FEB-10:40 | -16.3 | -16.5 | 0.175368E+09 | 259.94 | 15-FEB-10:50 | -16.0 | -16.2 |
March | 0.258443E+09 | 1331.18 | 31-MAR-09:00 | -17.8 | -18.9 | 0.218524E+09 | 347.88 | 31-MAR-09:00 | -16.1 | -17.3 |
April | 0.110294E+10 | 3821.45 | 22-APR-08:30 | 6.65 | 2.48 | 0.227879E+09 | 347.88 | 28-APR-09:20 | 6.70 | 3.17 |
May | 0.353122E+10 | 8753.68 | 21-MAY-07:52 | 9.40 | 4.83 | 0.275618E+09 | 347.88 | 19-MAY-09:09 | 9.40 | 4.83 |
June | 0.431083E+10 | 10023.50 | 13-JUN-05:12 | 12.40 | 9.24 | 0.276028E+09 | 348.31 | 07-JUN-09:20 | 12.40 | 9.24 |
July | 0.461532E+10 | 11225.42 | 23-JUL-10:01 | 21.38 | 14.90 | 0.257038E+09 | 348.38 | 07-JUL-09:50 | 21.38 | 14.90 |
August | 0.386745E+10 | 8817.00 | 25-AUG-06:01 | 7.98 | 7.08 | 0.287665E+09 | 348.20 | 11-AUG-09:09 | 7.98 | 7.08 |
September | 0.158946E+10 | 8427.64 | 10-SEP-09:13 | 11.67 | 6.57 | 0.243730E+09 | 347.88 | 08-SEP-13:20 | 11.67 | 6.57 |
October | 0.449324E+09 | 2171.63 | 03-OCT-09:25 | 2.50 | 1.67 | 0.209721E+09 | 347.88 | 13-OCT-09:00 | -6.7 | -7.8 |
November | 5239173.73 | 557.80 | 03-NOV-06:03 | -15.3 | -15.6 | 0.191470E+09 | 257.49 | 29-NOV-14:39 | -25.2 | -25.5 |
December | 6644431.79 | 510.62 | 30-DEC-17:02 | -10.0 | -10.4 | 0.186183E+09 | 257.53 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.197553E+11 | 0.274223E+10 | ||||||||
Minimum of Months | 5239173.73 | 510.62 | -17.8 | -18.9 | 0.175368E+09 | 257.49 | -25.2 | -25.5 | ||
Maximum of Months | 0.461532E+10 | 11225.42 | 21.38 | 14.90 | 0.287665E+09 | 348.38 | 21.38 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9988973.26 | 811.77 | 28-JAN-17:01 | -21.8 | -22.5 | 0.265980E+09 | 406.67 | 30-JAN-14:09 | -23.8 | -24.3 |
February | 68072546.27 | 1075.04 | 18-FEB-13:30 | -14.4 | -15.8 | 0.254173E+09 | 438.97 | 09-FEB-14:09 | -14.4 | -15.8 |
March | 0.223350E+09 | 1270.73 | 11-MAR-13:40 | -3.7 | -5.7 | 0.321211E+09 | 499.97 | 22-MAR-14:50 | 5.60 | 2.17 |
April | 0.176110E+10 | 10012.28 | 23-APR-13:43 | 10.00 | 3.85 | 0.339354E+09 | 549.51 | 13-APR-13:09 | 10.00 | 3.85 |
May | 0.331755E+10 | 10512.82 | 21-MAY-13:52 | 15.60 | 7.38 | 0.411841E+09 | 549.51 | 05-MAY-13:20 | 15.60 | 7.38 |
June | 0.468928E+10 | 9140.37 | 04-JUN-14:32 | 19.23 | 11.76 | 0.426283E+09 | 549.54 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.550396E+10 | 17624.39 | 23-JUL-14:01 | 25.10 | 15.30 | 0.398885E+09 | 549.54 | 19-JUL-09:09 | 25.10 | 15.30 |
August | 0.516586E+10 | 14975.49 | 27-AUG-13:12 | 18.33 | 13.81 | 0.441504E+09 | 549.55 | 25-AUG-13:00 | 18.33 | 13.81 |
September | 0.227804E+10 | 12915.20 | 10-SEP-11:53 | 15.60 | 8.34 | 0.355035E+09 | 549.51 | 08-SEP-13:09 | 15.60 | 8.34 |
October | 0.515183E+09 | 5508.25 | 03-OCT-13:40 | 11.13 | 6.36 | 0.311649E+09 | 549.51 | 13-OCT-13:09 | 0.18 | -2.9 |
November | 16411261.53 | 919.96 | 08-NOV-13:14 | -13.7 | -14.5 | 0.272528E+09 | 406.66 | 29-NOV-14:00 | -25.6 | -25.8 |
December | 9781573.72 | 805.16 | 30-DEC-17:02 | -10.0 | -10.4 | 0.255809E+09 | 406.74 | 22-DEC-10:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.235586E+11 | 0.405425E+10 | ||||||||
Minimum of Months | 9781573.72 | 805.16 | -21.8 | -22.5 | 0.254173E+09 | 406.66 | -25.6 | -25.8 | ||
Maximum of Months | 0.550396E+10 | 17624.39 | 25.10 | 15.30 | 0.441504E+09 | 549.55 | 25.10 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6462060.93 | 508.29 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192992E+09 | 257.48 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 6346905.34 | 510.66 | 11-FEB-17:03 | -1.2 | -2.7 | 0.175261E+09 | 257.47 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 91422320.34 | 736.06 | 31-MAR-17:00 | -9.4 | -11.7 | 0.211386E+09 | 288.43 | 29-MAR-15:00 | -9.4 | -11.7 |
April | 0.109786E+10 | 5038.10 | 21-APR-18:20 | 14.03 | 5.87 | 0.214821E+09 | 347.83 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.201939E+10 | 5190.87 | 14-MAY-19:22 | 16.15 | 8.31 | 0.269009E+09 | 347.86 | 16-MAY-09:20 | 6.33 | 4.90 |
June | 0.330953E+10 | 9826.13 | 11-JUN-17:22 | 18.60 | 10.93 | 0.275319E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.322528E+10 | 7971.92 | 09-JUL-19:42 | 19.50 | 13.10 | 0.256222E+09 | 347.88 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.290516E+10 | 6348.60 | 01-AUG-06:01 | 10.10 | 9.72 | 0.286104E+09 | 347.85 | 07-AUG-09:20 | 11.87 | 11.33 |
September | 0.126514E+10 | 3542.73 | 08-SEP-16:00 | 14.40 | 9.03 | 0.235406E+09 | 347.86 | 01-SEP-09:20 | 14.40 | 9.03 |
October | 0.329485E+09 | 854.38 | 03-OCT-15:20 | 12.43 | 6.74 | 0.202050E+09 | 336.86 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 7093032.76 | 553.75 | 02-NOV-06:03 | -10.7 | -11.1 | 0.191458E+09 | 257.47 | 29-NOV-14:00 | -25.6 | -25.8 |
December | 6751151.77 | 509.19 | 30-DEC-17:02 | -10.0 | -10.4 | 0.186169E+09 | 257.51 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.142699E+11 | 0.269620E+10 | ||||||||
Minimum of Months | 6346905.34 | 508.29 | -10.7 | -11.7 | 0.175261E+09 | 257.47 | -28.5 | -28.7 | ||
Maximum of Months | 0.330953E+10 | 9826.13 | 19.50 | 13.10 | 0.286104E+09 | 347.88 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8409464.16 | 817.46 | 07-JAN-17:02 | -9.0 | -9.0 | 0.304059E+09 | 406.72 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 19409813.51 | 872.20 | 09-FEB-07:05 | -0.3 | -0.7 | 0.276553E+09 | 406.70 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.222805E+09 | 1111.87 | 22-MAR-15:40 | 5.60 | 2.48 | 0.335023E+09 | 466.65 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.130328E+10 | 2511.66 | 28-APR-14:00 | 11.70 | 4.88 | 0.343682E+09 | 549.49 | 24-APR-13:20 | 11.70 | 4.88 |
May | 0.329647E+10 | 8557.27 | 31-MAY-05:12 | 12.43 | 7.84 | 0.433517E+09 | 549.50 | 16-MAY-09:20 | 12.43 | 7.84 |
June | 0.517871E+10 | 8916.87 | 19-JUN-05:12 | 8.73 | 7.50 | 0.436072E+09 | 549.51 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.484186E+10 | 9017.58 | 11-JUL-05:12 | 15.37 | 12.05 | 0.405495E+09 | 549.55 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.361344E+10 | 7506.36 | 02-AUG-06:01 | 11.28 | 10.30 | 0.451347E+09 | 549.50 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.163918E+10 | 2678.01 | 01-SEP-13:40 | 14.63 | 10.60 | 0.366349E+09 | 549.50 | 01-SEP-09:20 | 14.63 | 10.60 |
October | 0.451751E+09 | 1199.36 | 04-OCT-16:00 | 10.00 | 4.57 | 0.315948E+09 | 496.26 | 06-OCT-13:00 | 10.60 | 4.48 |
November | 7210655.95 | 816.89 | 18-NOV-17:02 | -13.0 | -13.3 | 0.301988E+09 | 406.70 | 17-NOV-10:09 | -13.0 | -13.3 |
December | 9934121.68 | 815.68 | 30-DEC-17:02 | -10.0 | -10.4 | 0.293758E+09 | 406.77 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.205925E+11 | 0.426379E+10 | ||||||||
Minimum of Months | 7210655.95 | 815.68 | -13.0 | -13.3 | 0.276553E+09 | 406.70 | -28.5 | -28.7 | ||
Maximum of Months | 0.517871E+10 | 9017.58 | 15.37 | 12.05 | 0.451347E+09 | 549.55 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7676205.08 | 572.34 | 27-JAN-07:03 | -13.2 | -13.6 | 0.141392E+09 | 250.73 | 10-JAN-16:00 | -13.2 | -13.6 |
February | 51081779.08 | 692.00 | 15-FEB-11:10 | -14.9 | -15.2 | 0.129086E+09 | 292.27 | 15-FEB-11:09 | -14.9 | -15.2 |
March | 0.425080E+09 | 7441.30 | 31-MAR-12:01 | -12.6 | -14.4 | 0.169571E+09 | 356.46 | 31-MAR-12:09 | -12.6 | -14.4 |
April | 0.164151E+10 | 7677.08 | 28-APR-12:01 | 9.27 | 4.21 | 0.174670E+09 | 356.46 | 28-APR-10:09 | 9.27 | 4.21 |
May | 0.457066E+10 | 13640.48 | 21-MAY-08:12 | 10.33 | 5.17 | 0.204915E+09 | 356.46 | 19-MAY-14:09 | 10.33 | 5.17 |
June | 0.519096E+10 | 13975.26 | 04-JUN-09:22 | 16.70 | 11.16 | 0.204869E+09 | 356.46 | 13-JUN-12:09 | 22.98 | 13.18 |
July | 0.512587E+10 | 14149.29 | 09-JUL-07:02 | 15.18 | 12.43 | 0.191306E+09 | 356.47 | 20-JUL-12:09 | 25.10 | 14.82 |
August | 0.401912E+10 | 10756.54 | 24-AUG-06:01 | 8.17 | 7.58 | 0.212929E+09 | 356.47 | 24-AUG-12:09 | 20.28 | 14.31 |
September | 0.150714E+10 | 11287.75 | 10-SEP-09:13 | 11.67 | 6.57 | 0.179557E+09 | 356.46 | 01-SEP-10:09 | 11.67 | 6.57 |
October | 0.345332E+09 | 5520.81 | 03-OCT-12:01 | 8.17 | 5.20 | 0.153573E+09 | 356.45 | 03-OCT-12:09 | 8.17 | 5.20 |
November | 7519445.11 | 572.87 | 02-NOV-12:02 | -9.3 | -9.8 | 0.140176E+09 | 251.99 | 08-NOV-11:20 | -17.1 | -17.5 |
December | 7351619.98 | 557.13 | 21-DEC-13:02 | -14.2 | -14.5 | 0.136354E+09 | 250.73 | 27-DEC-13:00 | -23.9 | -24.1 |
Annual Sum or Average | 0.228993E+11 | 0.203840E+10 | ||||||||
Minimum of Months | 7351619.98 | 557.13 | -14.9 | -15.2 | 0.129086E+09 | 250.73 | -23.9 | -24.1 | ||
Maximum of Months | 0.519096E+10 | 14149.29 | 16.70 | 12.43 | 0.212929E+09 | 356.47 | 25.10 | 14.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73162110.24 | 1161.39 | 25-JAN-13:40 | -19.5 | -19.7 | 0.306483E+09 | 486.80 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.478736E+09 | 4754.92 | 15-FEB-13:40 | -8.7 | -9.6 | 0.295027E+09 | 549.50 | 13-FEB-14:20 | -8.7 | -9.6 |
March | 0.190524E+10 | 8893.41 | 31-MAR-13:30 | -11.4 | -13.3 | 0.384371E+09 | 550.08 | 06-MAR-14:09 | -11.4 | -13.3 |
April | 0.464464E+10 | 16203.06 | 23-APR-13:43 | 10.00 | 3.85 | 0.375052E+09 | 550.45 | 11-APR-13:30 | 10.00 | 3.85 |
May | 0.660984E+10 | 19660.13 | 14-MAY-12:22 | 18.35 | 9.42 | 0.433796E+09 | 550.70 | 12-MAY-13:20 | 18.35 | 9.42 |
June | 0.752900E+10 | 20677.18 | 04-JUN-14:02 | 18.98 | 11.85 | 0.435857E+09 | 549.54 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.746149E+10 | 20957.96 | 23-JUL-13:12 | 25.00 | 15.26 | 0.405551E+09 | 550.97 | 20-JUL-13:20 | 25.00 | 15.26 |
August | 0.718541E+10 | 20611.79 | 27-AUG-13:32 | 18.87 | 14.02 | 0.453120E+09 | 550.88 | 24-AUG-13:20 | 18.87 | 14.02 |
September | 0.381206E+10 | 16521.23 | 10-SEP-11:53 | 15.60 | 8.34 | 0.383296E+09 | 549.64 | 15-SEP-09:30 | 4.15 | 2.95 |
October | 0.127510E+10 | 9549.91 | 03-OCT-13:30 | 10.85 | 6.24 | 0.343638E+09 | 549.85 | 05-OCT-13:00 | 10.60 | 5.47 |
November | 0.157514E+09 | 2921.46 | 08-NOV-13:30 | -13.6 | -14.4 | 0.307302E+09 | 549.49 | 08-NOV-14:20 | -13.5 | -14.2 |
December | 11437022.96 | 902.53 | 21-DEC-07:03 | -13.8 | -14.1 | 0.294183E+09 | 406.75 | 22-DEC-10:50 | -24.1 | -24.4 |
Annual Sum or Average | 0.411436E+11 | 0.441768E+10 | ||||||||
Minimum of Months | 11437022.96 | 902.53 | -19.5 | -19.7 | 0.294183E+09 | 406.75 | -24.1 | -24.4 | ||
Maximum of Months | 0.752900E+10 | 20957.96 | 25.00 | 15.26 | 0.453120E+09 | 550.97 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6654136.85 | 573.87 | 27-JAN-07:03 | -13.2 | -13.6 | 0.193089E+09 | 257.48 | 03-JAN-14:00 | -13.2 | -13.6 |
February | 36929144.18 | 625.97 | 15-FEB-15:50 | -7.2 | -8.6 | 0.175756E+09 | 272.31 | 09-FEB-14:00 | -7.2 | -8.6 |
March | 0.286334E+09 | 1392.99 | 31-MAR-16:00 | -9.4 | -11.8 | 0.216779E+09 | 338.68 | 22-MAR-15:00 | -9.4 | -11.8 |
April | 0.178653E+10 | 7709.15 | 22-APR-17:08 | 14.13 | 6.18 | 0.224962E+09 | 347.85 | 24-APR-13:20 | 4.40 | -1.0 |
May | 0.312680E+10 | 12260.38 | 28-MAY-17:03 | 16.70 | 8.41 | 0.273916E+09 | 347.86 | 16-MAY-09:20 | 16.70 | 8.41 |
June | 0.441657E+10 | 12980.73 | 04-JUN-15:22 | 19.70 | 11.70 | 0.275952E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.396667E+10 | 10646.65 | 09-JUL-19:42 | 19.50 | 13.10 | 0.256601E+09 | 347.89 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.327424E+10 | 10526.17 | 27-AUG-18:53 | 19.40 | 11.72 | 0.285839E+09 | 347.85 | 07-AUG-09:20 | 19.40 | 11.72 |
September | 0.139779E+10 | 6438.80 | 02-SEP-17:43 | 16.70 | 10.38 | 0.234568E+09 | 347.86 | 01-SEP-09:20 | 16.70 | 10.38 |
October | 0.327717E+09 | 1312.48 | 03-OCT-15:00 | 12.80 | 6.92 | 0.202430E+09 | 338.68 | 03-OCT-15:00 | 11.70 | 6.37 |
November | 8908856.50 | 594.85 | 08-NOV-15:40 | -15.4 | -15.8 | 0.191414E+09 | 262.37 | 08-NOV-15:50 | -15.7 | -16.1 |
December | 7097247.47 | 515.44 | 30-DEC-17:02 | -10.0 | -10.4 | 0.186183E+09 | 257.51 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.186422E+11 | 0.271749E+10 | ||||||||
Minimum of Months | 6654136.85 | 515.44 | -15.4 | -15.8 | 0.175756E+09 | 257.48 | -15.7 | -16.1 | ||
Maximum of Months | 0.441657E+10 | 12980.73 | 19.70 | 13.10 | 0.285839E+09 | 347.89 | 25.00 | 15.96 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116489E+10 | 20316.69 | 02-JAN-05:01 | -15.6 |
February | 0.227980E+09 | 16555.28 | 27-FEB-06:01 | -35.9 |
March | 23807057.53 | 16584.94 | 01-MAR-06:01 | -28.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 3387856.44 | 14184.08 | 30-OCT-06:01 | -15.1 |
November | 0.116268E+09 | 16704.75 | 28-NOV-06:01 | -27.4 |
December | 0.276049E+09 | 16993.68 | 27-DEC-06:01 | -20.8 |
Annual Sum or Average | 0.181238E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.9 | |
Maximum of Months | 0.116489E+10 | 20316.69 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104460E+11 | 18069.02 | 12-JAN-06:12 | -38.3 |
February | 0.767883E+10 | 18028.12 | 27-FEB-06:06 | -35.9 |
March | 0.540405E+10 | 16567.83 | 01-MAR-06:12 | -28.5 |
April | 0.181003E+10 | 14178.86 | 03-APR-05:13 | -21.3 |
May | 0.388193E+09 | 5399.17 | 21-MAY-07:22 | 8.05 |
June | 85536455.24 | 5676.49 | 07-JUN-05:12 | 7.40 |
July | 91462831.06 | 5516.82 | 06-JUL-05:12 | 9.23 |
August | 0.305123E+09 | 3408.56 | 31-AUG-07:35 | 1.27 |
September | 0.112300E+10 | 6114.78 | 28-SEP-06:02 | -2.8 |
October | 0.412303E+10 | 14759.62 | 30-OCT-05:12 | -14.6 |
November | 0.921096E+10 | 16865.25 | 27-NOV-06:05 | -26.7 |
December | 0.109475E+11 | 17127.23 | 15-DEC-06:12 | -33.0 |
Annual Sum or Average | 0.516137E+11 | |||
Minimum of Months | 85536455.24 | 3408.56 | -38.3 | |
Maximum of Months | 0.109475E+11 | 18069.02 | 9.23 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408767E+10 | 11000.04 | 02-JAN-07:05 | -14.4 |
February | 0.283499E+10 | 9818.70 | 27-FEB-07:05 | -34.9 |
March | 0.223380E+10 | 6994.38 | 06-MAR-07:02 | -20.9 |
April | 0.883770E+09 | 5075.75 | 03-APR-06:02 | -21.5 |
May | 65144767.32 | 4976.78 | 28-MAY-15:43 | 15.92 |
June | 31339416.29 | 4202.64 | 04-JUN-15:22 | 19.70 |
July | 33439042.66 | 4582.04 | 23-JUL-11:12 | 23.17 |
August | 28727825.42 | 4219.04 | 27-AUG-11:32 | 15.77 |
September | 0.391687E+09 | 5078.29 | 10-SEP-11:53 | 15.60 |
October | 0.172338E+10 | 7718.85 | 30-OCT-06:11 | -15.2 |
November | 0.321107E+10 | 10030.01 | 13-NOV-07:03 | -17.1 |
December | 0.385930E+10 | 9855.59 | 04-DEC-07:03 | -19.4 |
Annual Sum or Average | 0.193843E+11 | |||
Minimum of Months | 28727825.42 | 4202.64 | -34.9 | |
Maximum of Months | 0.408767E+10 | 11000.04 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330638E+10 | 9209.65 | 02-JAN-08:14 | -14.8 |
February | 0.219736E+10 | 5939.26 | 21-FEB-07:01 | -23.2 |
March | 0.143832E+10 | 3770.35 | 06-MAR-08:30 | -17.8 |
April | 0.408248E+09 | 3086.20 | 03-APR-07:17 | -19.7 |
May | 13541720.09 | 2025.35 | 21-MAY-07:52 | 9.40 |
June | 14053287.20 | 2229.05 | 16-JUN-05:12 | 9.60 |
July | 19940109.70 | 2872.93 | 06-JUL-05:12 | 9.23 |
August | 17267536.40 | 3235.18 | 31-AUG-05:03 | -1.2 |
September | 0.137513E+09 | 2862.33 | 10-SEP-11:53 | 15.60 |
October | 0.108524E+10 | 3990.75 | 30-OCT-07:40 | -16.3 |
November | 0.231264E+10 | 5861.92 | 13-NOV-07:01 | -17.1 |
December | 0.297267E+10 | 6143.31 | 04-DEC-07:01 | -19.4 |
Annual Sum or Average | 0.139232E+11 | |||
Minimum of Months | 13541720.09 | 2025.35 | -23.2 | |
Maximum of Months | 0.330638E+10 | 9209.65 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284432E+10 | 23268.09 | 02-JAN-05:01 | -15.6 |
February | 0.135651E+10 | 21946.60 | 21-FEB-05:01 | -22.9 |
March | 0.287149E+09 | 20129.23 | 06-MAR-06:01 | -21.1 |
April | 29854677.18 | 18952.00 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.220769E+09 | 20281.40 | 30-OCT-05:01 | -14.5 |
November | 0.154099E+10 | 21871.65 | 13-NOV-05:01 | -20.2 |
December | 0.234091E+10 | 21908.89 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.862050E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.9 | |
Maximum of Months | 0.284432E+10 | 23268.09 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.861843E+10 | 29419.41 | 01-JAN-22:42 | -15.0 |
February | 0.517396E+10 | 29195.15 | 27-FEB-05:01 | -36.1 |
March | 0.245068E+10 | 28336.72 | 06-MAR-05:01 | -20.2 |
April | 0.423345E+09 | 27111.63 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 34803455.54 | 23485.12 | 28-SEP-06:02 | -2.8 |
October | 0.181494E+10 | 28404.94 | 30-OCT-04:01 | -14.4 |
November | 0.668852E+10 | 29227.24 | 13-NOV-05:01 | -20.2 |
December | 0.845296E+10 | 29075.55 | 11-DEC-05:01 | -19.2 |
Annual Sum or Average | 0.336576E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.861843E+10 | 29419.41 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908847E+10 | 9571.51 | 29-JAN-02:12 | -26.0 |
February | 0.659398E+10 | 9414.61 | 26-FEB-04:22 | -25.6 |
March | 0.424112E+10 | 9014.97 | 06-MAR-05:01 | -20.2 |
April | 0.929501E+09 | 8923.15 | 03-APR-02:33 | -20.4 |
May | 325514.65 | 1627.57 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1617702.27 | 6358.34 | 31-AUG-06:03 | -1.5 |
September | 0.194461E+09 | 7787.71 | 30-SEP-05:01 | -4.5 |
October | 0.306860E+10 | 9107.51 | 30-OCT-03:13 | -13.7 |
November | 0.764007E+10 | 9228.96 | 13-NOV-03:42 | -19.9 |
December | 0.907291E+10 | 9340.25 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.408310E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.908847E+10 | 9571.51 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603253E+10 | 12557.95 | 29-JAN-02:12 | -26.0 |
February | 0.387950E+10 | 12255.72 | 26-FEB-04:22 | -25.6 |
March | 0.185835E+10 | 11883.55 | 06-MAR-05:01 | -20.2 |
April | 0.398728E+09 | 11389.67 | 04-APR-04:01 | -10.3 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 850032.57 | 3140.19 | 31-AUG-06:03 | -1.5 |
September | 89079651.34 | 10200.47 | 30-SEP-05:01 | -4.5 |
October | 0.168467E+10 | 11545.57 | 28-OCT-04:01 | -10.5 |
November | 0.501849E+10 | 12058.74 | 13-NOV-05:01 | -20.2 |
December | 0.612113E+10 | 12147.74 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.250833E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.612113E+10 | 12557.95 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.829951E+10 | 19455.48 | 30-JAN-02:52 | -25.0 |
February | 0.465945E+10 | 19076.88 | 26-FEB-04:22 | -25.6 |
March | 0.239030E+10 | 18516.80 | 06-MAR-05:01 | -20.2 |
April | 0.547978E+09 | 17662.05 | 03-APR-04:01 | -21.1 |
May | 609021.98 | 2975.75 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 617523.62 | 2067.90 | 30-AUG-06:03 | 0.10 |
September | 0.117295E+09 | 15735.25 | 30-SEP-05:01 | -4.5 |
October | 0.210546E+10 | 17721.95 | 28-OCT-04:01 | -10.5 |
November | 0.637706E+10 | 18793.26 | 13-NOV-05:01 | -20.2 |
December | 0.890394E+10 | 18927.35 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.334022E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.890394E+10 | 19455.48 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.611301E+10 | 12909.60 | 29-JAN-02:12 | -26.0 |
February | 0.422702E+10 | 12623.26 | 26-FEB-04:22 | -25.6 |
March | 0.247429E+10 | 12247.55 | 06-MAR-05:01 | -20.2 |
April | 0.478469E+09 | 11700.58 | 04-APR-04:01 | -10.3 |
May | 641215.18 | 2565.78 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 699000.30 | 2075.17 | 31-AUG-06:03 | -1.5 |
September | 0.116098E+09 | 10524.68 | 30-SEP-05:01 | -4.5 |
October | 0.194741E+10 | 11913.82 | 28-OCT-04:01 | -10.5 |
November | 0.501442E+10 | 12414.29 | 13-NOV-05:01 | -20.2 |
December | 0.613461E+10 | 12494.15 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.265067E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.613461E+10 | 12909.60 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.745978E+10 | 7676.59 | 01-JAN-18:42 | -14.4 |
February | 0.593887E+10 | 7542.01 | 21-FEB-02:12 | -23.7 |
March | 0.432042E+10 | 7302.17 | 06-MAR-05:01 | -20.2 |
April | 0.810355E+09 | 7222.55 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 14242110.70 | 5803.35 | 28-SEP-06:02 | -2.8 |
October | 0.131759E+10 | 7029.88 | 30-OCT-04:01 | -14.4 |
November | 0.499292E+10 | 7311.41 | 13-NOV-05:11 | -19.8 |
December | 0.668250E+10 | 7389.61 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.315367E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.7 | |
Maximum of Months | 0.745978E+10 | 7676.59 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515446E+10 | 9870.23 | 01-JAN-18:42 | -14.4 |
February | 0.358196E+10 | 9649.92 | 21-FEB-04:52 | -22.8 |
March | 0.160482E+10 | 9469.85 | 06-MAR-05:01 | -20.2 |
April | 0.225902E+09 | 9039.54 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 4933312.32 | 5752.51 | 28-SEP-06:02 | -2.8 |
October | 0.651672E+09 | 9106.26 | 30-OCT-04:01 | -14.4 |
November | 0.331652E+10 | 9501.65 | 13-NOV-05:11 | -19.8 |
December | 0.463152E+10 | 9511.60 | 11-DEC-05:01 | -19.2 |
Annual Sum or Average | 0.191718E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.515446E+10 | 9870.23 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148260E+11 | 21716.95 | 12-JAN-08:00 | -38.3 |
February | 0.100956E+11 | 21125.96 | 27-FEB-08:00 | -34.4 |
March | 0.749669E+10 | 19808.39 | 01-MAR-08:00 | -28.3 |
April | 0.226728E+10 | 17712.45 | 03-APR-06:10 | -21.5 |
May | 0.641487E+09 | 11809.67 | 04-MAY-06:10 | 4.18 |
June | 0.128411E+09 | 11218.53 | 01-JUN-06:05 | 7.57 |
July | 90212972.91 | 10465.50 | 05-JUL-06:05 | 8.30 |
August | 0.287176E+09 | 12266.33 | 31-AUG-06:10 | -1.5 |
September | 0.132323E+10 | 13651.90 | 29-SEP-07:00 | -5.6 |
October | 0.484319E+10 | 17456.40 | 31-OCT-07:00 | -19.4 |
November | 0.118652E+11 | 19621.35 | 29-NOV-08:00 | -28.9 |
December | 0.148505E+11 | 20660.46 | 15-DEC-08:00 | -33.9 |
Annual Sum or Average | 0.687150E+11 | |||
Minimum of Months | 90212972.91 | 10465.50 | -38.3 | |
Maximum of Months | 0.148505E+11 | 21716.95 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523921E+10 | 10287.41 | 01-JAN-18:42 | -14.4 |
February | 0.393866E+10 | 10097.03 | 21-FEB-04:52 | -22.8 |
March | 0.235908E+10 | 9912.13 | 06-MAR-05:01 | -20.2 |
April | 0.252966E+09 | 9123.94 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 7861214.75 | 6553.08 | 28-SEP-06:02 | -2.8 |
October | 0.820094E+09 | 9544.30 | 30-OCT-04:01 | -14.4 |
November | 0.331530E+10 | 9914.55 | 13-NOV-05:11 | -19.8 |
December | 0.464587E+10 | 9927.11 | 11-DEC-05:01 | -19.2 |
Annual Sum or Average | 0.205790E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.523921E+10 | 10287.41 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.616891E+10 | 8665.39 | 01-JAN-18:42 | -14.4 |
February | 0.403832E+10 | 8511.25 | 26-FEB-10:02 | -27.2 |
March | 0.227239E+10 | 8224.73 | 06-MAR-05:01 | -20.2 |
April | 0.330952E+09 | 8149.90 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 21175799.37 | 6568.90 | 28-SEP-06:02 | -2.8 |
October | 0.139828E+10 | 8168.52 | 23-OCT-04:01 | -11.1 |
November | 0.464493E+10 | 8377.24 | 13-NOV-05:01 | -20.2 |
December | 0.594465E+10 | 8467.07 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.248196E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.616891E+10 | 8665.39 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408092E+10 | 10387.22 | 30-JAN-02:52 | -25.0 |
February | 0.229200E+10 | 10052.12 | 21-FEB-02:12 | -23.7 |
March | 0.917006E+09 | 9817.07 | 06-MAR-05:01 | -20.2 |
April | 0.134556E+09 | 9573.40 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 12941706.25 | 6781.47 | 28-SEP-06:02 | -2.8 |
October | 0.763288E+09 | 9646.40 | 23-OCT-04:01 | -11.1 |
November | 0.302900E+10 | 10081.78 | 13-NOV-05:01 | -20.2 |
December | 0.400627E+10 | 10053.28 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.152360E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.408092E+10 | 10387.22 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.539516E+10 | 15628.72 | 30-JAN-04:52 | -25.6 |
February | 0.257063E+10 | 14747.57 | 27-FEB-05:01 | -36.1 |
March | 0.107399E+10 | 14748.09 | 06-MAR-05:01 | -20.2 |
April | 0.165073E+09 | 13756.42 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 14120875.01 | 10581.92 | 28-SEP-06:02 | -2.8 |
October | 0.860509E+09 | 14440.41 | 30-OCT-04:01 | -14.4 |
November | 0.359189E+10 | 15186.69 | 13-NOV-05:01 | -20.2 |
December | 0.568247E+10 | 15153.19 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.193538E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.568247E+10 | 15628.72 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415213E+10 | 10349.94 | 30-JAN-02:52 | -25.0 |
February | 0.254335E+10 | 10017.96 | 26-FEB-10:02 | -27.2 |
March | 0.125951E+10 | 9798.16 | 06-MAR-05:01 | -20.2 |
April | 0.159320E+09 | 9251.84 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 14889063.56 | 6795.95 | 28-SEP-06:02 | -2.8 |
October | 0.887543E+09 | 9630.46 | 23-OCT-04:01 | -11.1 |
November | 0.301993E+10 | 10033.43 | 13-NOV-05:01 | -20.2 |
December | 0.402151E+10 | 10005.98 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.160582E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.415213E+10 | 10349.94 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.652758E+09 | 735.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.489040E+09 | 735.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.456173E+09 | 735.45 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.355828E+09 | 408.45 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.370912E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.360505E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.343228E+09 | 371.68 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.395187E+09 | 383.84 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.387280E+09 | 697.91 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.482824E+09 | 735.45 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.606114E+09 | 735.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.662327E+09 | 735.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.556218E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.343228E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.662327E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.399857E+09 | 465.60 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.298717E+09 | 465.60 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.284664E+09 | 465.60 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.225718E+09 | 222.09 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.238474E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.231352E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.220173E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.252354E+09 | 243.68 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.243505E+09 | 393.65 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.297390E+09 | 465.60 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366701E+09 | 465.60 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.414969E+09 | 465.60 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.347387E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.220173E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.414969E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.609344E+09 | 735.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.452472E+09 | 735.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.442594E+09 | 735.45 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.357589E+09 | 408.30 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.376074E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.365847E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.347691E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.397045E+09 | 350.81 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.381151E+09 | 667.90 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.457768E+09 | 735.45 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.550930E+09 | 735.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.638535E+09 | 735.45 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.537704E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.347691E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.638535E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403187E+09 | 465.57 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.294977E+09 | 465.57 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.283655E+09 | 465.57 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.226601E+09 | 325.92 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.234742E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.228857E+09 | 222.08 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.217595E+09 | 241.97 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.249201E+09 | 242.06 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242908E+09 | 442.98 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.295587E+09 | 465.57 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366979E+09 | 465.57 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.416762E+09 | 465.57 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.346105E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.217595E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416762E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.650277E+09 | 735.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.486439E+09 | 735.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.454685E+09 | 735.45 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.355392E+09 | 406.31 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.370658E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.360272E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.342910E+09 | 350.81 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.394883E+09 | 380.65 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.386049E+09 | 695.86 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.479516E+09 | 735.45 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.602836E+09 | 735.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.661569E+09 | 735.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.554549E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.342910E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.661569E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.398693E+09 | 465.60 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.297683E+09 | 465.60 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.284048E+09 | 465.60 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.225480E+09 | 222.09 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.238224E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.231113E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.219928E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.252075E+09 | 241.84 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.243083E+09 | 389.07 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.296651E+09 | 465.60 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.365028E+09 | 465.60 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.414347E+09 | 465.60 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.346635E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.219928E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.414347E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.607257E+09 | 735.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.450594E+09 | 735.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.442026E+09 | 735.45 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.357140E+09 | 406.15 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.375700E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.365438E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.347319E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.396629E+09 | 350.81 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.380493E+09 | 663.94 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.456501E+09 | 735.45 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.549008E+09 | 735.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.635796E+09 | 735.45 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.536390E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.347319E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.635796E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.401926E+09 | 465.57 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.293196E+09 | 465.57 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.282986E+09 | 465.57 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.226273E+09 | 321.67 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.234586E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.228702E+09 | 222.08 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.217341E+09 | 240.14 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.248934E+09 | 240.22 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242241E+09 | 441.90 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.294629E+09 | 465.57 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.365184E+09 | 465.57 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.416256E+09 | 465.57 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.345225E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.217341E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416256E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.652757E+09 | 735.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.489038E+09 | 735.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.456171E+09 | 735.45 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.355827E+09 | 408.45 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.370912E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.360505E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.343228E+09 | 371.67 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.395186E+09 | 383.83 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.387279E+09 | 697.91 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.482821E+09 | 735.45 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.606112E+09 | 735.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.662327E+09 | 735.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.556216E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.343228E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.662327E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.399857E+09 | 465.60 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.298708E+09 | 465.60 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.284664E+09 | 465.60 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.225718E+09 | 222.09 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.238474E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.231352E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.220173E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.252353E+09 | 243.68 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.243505E+09 | 393.65 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.297389E+09 | 465.60 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366700E+09 | 465.60 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.414968E+09 | 465.60 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.347386E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.220173E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.414968E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.609344E+09 | 735.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.452471E+09 | 735.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.442594E+09 | 735.45 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.357588E+09 | 408.30 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.376073E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.365846E+09 | 350.81 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.347690E+09 | 350.81 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.397045E+09 | 350.81 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.381151E+09 | 667.90 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.457767E+09 | 735.45 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.550929E+09 | 735.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.638535E+09 | 735.45 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.537703E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.347690E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.638535E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403186E+09 | 465.57 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.294977E+09 | 465.57 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.283655E+09 | 465.57 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.226600E+09 | 325.90 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.234742E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.228857E+09 | 222.08 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.217593E+09 | 241.97 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.249201E+09 | 242.06 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242907E+09 | 442.98 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.295586E+09 | 465.57 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366978E+09 | 465.57 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.416762E+09 | 465.57 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.346104E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.217593E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416762E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.652758E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943409E+09 |
February | 0.901968E+09 | 0.489040E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758160E+09 |
March | 0.107774E+10 | 0.456173E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111388E+10 |
April | 0.956342E+09 | 0.355828E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124573E+10 |
May | 0.103597E+10 | 0.370912E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773011E+09 |
June | 0.103308E+10 | 0.360505E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007876.52 | 0.463002E+09 |
July | 0.959235E+09 | 0.343228E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3116759.70 | 0.345061E+09 |
August | 0.107774E+10 | 0.395187E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 459034.04 | 0.401345E+09 |
September | 0.956342E+09 | 0.387280E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462337E+09 |
October | 0.994195E+09 | 0.482824E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958378E+09 |
November | 0.984487E+09 | 0.606114E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346963E+09 |
December | 0.959235E+09 | 0.662327E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684618E+09 |
Annual Sum or Average | 0.119305E+11 | 0.556218E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4583670.26 | 0.849589E+10 |
Minimum of Months | 0.901968E+09 | 0.343228E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345061E+09 |
Maximum of Months | 0.107774E+10 | 0.662327E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3116759.70 | 0.124573E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.399857E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629834E+09 |
February | 0.571020E+09 | 0.298717E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506085E+09 |
March | 0.682301E+09 | 0.284664E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750239E+09 |
April | 0.605444E+09 | 0.225718E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854183E+09 |
May | 0.655854E+09 | 0.238474E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530582E+09 |
June | 0.654023E+09 | 0.231352E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671929.97 | 0.312505E+09 |
July | 0.607275E+09 | 0.220173E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1958289.92 | 0.234697E+09 |
August | 0.682301E+09 | 0.252354E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306030.69 | 0.273376E+09 |
September | 0.605444E+09 | 0.243505E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318967E+09 |
October | 0.629407E+09 | 0.297390E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643667E+09 |
November | 0.623262E+09 | 0.366701E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231272E+09 |
December | 0.607275E+09 | 0.414969E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456567E+09 |
Annual Sum or Average | 0.755301E+10 | 0.347387E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2936250.58 | 0.574197E+10 |
Minimum of Months | 0.571020E+09 | 0.220173E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231272E+09 |
Maximum of Months | 0.682301E+09 | 0.414969E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1958289.92 | 0.854183E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.609344E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946329E+09 |
February | 0.901968E+09 | 0.452472E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765212E+09 |
March | 0.107774E+10 | 0.442594E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115025E+10 |
April | 0.956342E+09 | 0.357589E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132731E+10 |
May | 0.103597E+10 | 0.376074E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800907E+09 |
June | 0.103308E+10 | 0.365847E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007841.93 | 0.468465E+09 |
July | 0.959235E+09 | 0.347691E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2702201.61 | 0.353577E+09 |
August | 0.107774E+10 | 0.397045E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 458434.79 | 0.418046E+09 |
September | 0.956342E+09 | 0.381151E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487810E+09 |
October | 0.994195E+09 | 0.457768E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983320E+09 |
November | 0.984487E+09 | 0.550930E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348042E+09 |
December | 0.959235E+09 | 0.638535E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685820E+09 |
Annual Sum or Average | 0.119305E+11 | 0.537704E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4168478.34 | 0.873509E+10 |
Minimum of Months | 0.901968E+09 | 0.347691E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348042E+09 |
Maximum of Months | 0.107774E+10 | 0.638535E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2702201.61 | 0.132731E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.403187E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629831E+09 |
February | 0.570983E+09 | 0.294977E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505975E+09 |
March | 0.682256E+09 | 0.283655E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748177E+09 |
April | 0.605404E+09 | 0.226601E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871557E+09 |
May | 0.655811E+09 | 0.234742E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535381E+09 |
June | 0.653980E+09 | 0.228857E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671936.79 | 0.314845E+09 |
July | 0.607235E+09 | 0.217595E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1700255.93 | 0.237438E+09 |
August | 0.682256E+09 | 0.249201E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306035.27 | 0.276046E+09 |
September | 0.605404E+09 | 0.242908E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315595E+09 |
October | 0.629366E+09 | 0.295587E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640837E+09 |
November | 0.623221E+09 | 0.366979E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231337E+09 |
December | 0.607235E+09 | 0.416762E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456568E+09 |
Annual Sum or Average | 0.755252E+10 | 0.346105E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2678227.99 | 0.576359E+10 |
Minimum of Months | 0.570983E+09 | 0.217595E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231337E+09 |
Maximum of Months | 0.682256E+09 | 0.416762E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1700255.93 | 0.871557E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.650277E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505388E+09 |
February | 0.901968E+09 | 0.486439E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405067E+09 |
March | 0.107774E+10 | 0.454685E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600017E+09 |
April | 0.956342E+09 | 0.355392E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662849E+09 |
May | 0.103597E+10 | 0.370658E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399939E+09 |
June | 0.103308E+10 | 0.360272E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 555314.41 | 0.240486E+09 |
July | 0.959235E+09 | 0.342910E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945344.35 | 0.179976E+09 |
August | 0.107774E+10 | 0.394883E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259908.33 | 0.218027E+09 |
September | 0.956342E+09 | 0.386049E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260070E+09 |
October | 0.994195E+09 | 0.479516E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541175E+09 |
November | 0.984487E+09 | 0.602836E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189636E+09 |
December | 0.959235E+09 | 0.661569E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369987E+09 |
Annual Sum or Average | 0.119305E+11 | 0.554549E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2760567.09 | 0.457262E+10 |
Minimum of Months | 0.901968E+09 | 0.342910E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179976E+09 |
Maximum of Months | 0.107774E+10 | 0.661569E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945344.35 | 0.662849E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.398693E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337280E+09 |
February | 0.571020E+09 | 0.297683E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270668E+09 |
March | 0.682301E+09 | 0.284048E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406069E+09 |
April | 0.605444E+09 | 0.225480E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465846E+09 |
May | 0.655854E+09 | 0.238224E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287228E+09 |
June | 0.654023E+09 | 0.231113E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370211.34 | 0.167010E+09 |
July | 0.607275E+09 | 0.219928E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1097786.36 | 0.126758E+09 |
August | 0.682301E+09 | 0.252075E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173255.15 | 0.151593E+09 |
September | 0.605444E+09 | 0.243083E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182380E+09 |
October | 0.629407E+09 | 0.296651E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366885E+09 |
November | 0.623262E+09 | 0.365028E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126168E+09 |
December | 0.607275E+09 | 0.414347E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246199E+09 |
Annual Sum or Average | 0.755301E+10 | 0.346635E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1641252.85 | 0.313408E+10 |
Minimum of Months | 0.571020E+09 | 0.219928E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126168E+09 |
Maximum of Months | 0.682301E+09 | 0.414347E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1097786.36 | 0.465846E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.607257E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106483E+11 |
February | 0.901968E+09 | 0.450594E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838160E+10 |
March | 0.107774E+10 | 0.442026E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935404E+10 |
April | 0.956342E+09 | 0.357140E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551515E+10 |
May | 0.103597E+10 | 0.375700E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331225E+10 |
June | 0.103308E+10 | 0.365438E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29067210.94 | 0.192378E+10 |
July | 0.959235E+09 | 0.347319E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43212521.58 | 0.146573E+10 |
August | 0.107774E+10 | 0.396629E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10101460.18 | 0.263457E+10 |
September | 0.956342E+09 | 0.380493E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403906E+10 |
October | 0.994195E+09 | 0.456501E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684224E+10 |
November | 0.984487E+09 | 0.549008E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102771E+11 |
December | 0.959235E+09 | 0.635796E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107655E+11 |
Annual Sum or Average | 0.119305E+11 | 0.536390E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82381192.70 | 0.751593E+11 |
Minimum of Months | 0.901968E+09 | 0.347319E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146573E+10 |
Maximum of Months | 0.107774E+10 | 0.635796E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43212521.58 | 0.107655E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.401926E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337249E+09 |
February | 0.570983E+09 | 0.293196E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270323E+09 |
March | 0.682256E+09 | 0.282986E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403135E+09 |
April | 0.605404E+09 | 0.226273E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474608E+09 |
May | 0.655811E+09 | 0.234586E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284534E+09 |
June | 0.653980E+09 | 0.228702E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370220.29 | 0.167602E+09 |
July | 0.607235E+09 | 0.217341E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 961882.35 | 0.126101E+09 |
August | 0.682256E+09 | 0.248934E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173260.36 | 0.152026E+09 |
September | 0.605404E+09 | 0.242241E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179664E+09 |
October | 0.629366E+09 | 0.294629E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362787E+09 |
November | 0.623221E+09 | 0.365184E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126237E+09 |
December | 0.607235E+09 | 0.416256E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246194E+09 |
Annual Sum or Average | 0.755252E+10 | 0.345225E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1505363.00 | 0.313046E+10 |
Minimum of Months | 0.570983E+09 | 0.217341E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126101E+09 |
Maximum of Months | 0.682256E+09 | 0.416256E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 961882.35 | 0.474608E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.652757E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794215E+09 |
February | 0.901968E+09 | 0.489038E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640262E+09 |
March | 0.107774E+10 | 0.456171E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954895E+09 |
April | 0.956342E+09 | 0.355827E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108328E+10 |
May | 0.103597E+10 | 0.370912E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667496E+09 |
June | 0.103308E+10 | 0.360505E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854160.26 | 0.395273E+09 |
July | 0.959235E+09 | 0.343228E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2737776.18 | 0.293106E+09 |
August | 0.107774E+10 | 0.395186E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394407.00 | 0.346419E+09 |
September | 0.956342E+09 | 0.387279E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408565E+09 |
October | 0.994195E+09 | 0.482821E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835291E+09 |
November | 0.984487E+09 | 0.606112E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294266E+09 |
December | 0.959235E+09 | 0.662327E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578623E+09 |
Annual Sum or Average | 0.119305E+11 | 0.556216E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3986343.45 | 0.729169E+10 |
Minimum of Months | 0.901968E+09 | 0.343228E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293106E+09 |
Maximum of Months | 0.107774E+10 | 0.662327E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2737776.18 | 0.108328E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.399857E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528764E+09 |
February | 0.421807E+09 | 0.298708E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426751E+09 |
March | 0.502994E+09 | 0.284664E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645093E+09 |
April | 0.447140E+09 | 0.225718E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743303E+09 |
May | 0.484071E+09 | 0.238474E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457324E+09 |
June | 0.482240E+09 | 0.231352E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546657.61 | 0.267311E+09 |
July | 0.448971E+09 | 0.220173E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1667255.45 | 0.199790E+09 |
August | 0.502994E+09 | 0.252353E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262932.49 | 0.235723E+09 |
September | 0.447140E+09 | 0.243505E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280734E+09 |
October | 0.465148E+09 | 0.297389E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562451E+09 |
November | 0.460569E+09 | 0.366700E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195548E+09 |
December | 0.448971E+09 | 0.414968E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384613E+09 |
Annual Sum or Average | 0.557719E+10 | 0.347386E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2476845.55 | 0.492741E+10 |
Minimum of Months | 0.421807E+09 | 0.220173E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195548E+09 |
Maximum of Months | 0.502994E+09 | 0.414968E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1667255.45 | 0.743303E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.609344E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795934E+09 |
February | 0.901968E+09 | 0.452471E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648797E+09 |
March | 0.107774E+10 | 0.442594E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990144E+09 |
April | 0.956342E+09 | 0.357588E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115262E+10 |
May | 0.103597E+10 | 0.376073E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689449E+09 |
June | 0.103308E+10 | 0.365846E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854127.58 | 0.400016E+09 |
July | 0.959235E+09 | 0.347690E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2363659.74 | 0.300208E+09 |
August | 0.107774E+10 | 0.397045E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 393371.67 | 0.359233E+09 |
September | 0.956342E+09 | 0.381151E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427632E+09 |
October | 0.994195E+09 | 0.457767E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861061E+09 |
November | 0.984487E+09 | 0.550929E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296010E+09 |
December | 0.959235E+09 | 0.638535E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579220E+09 |
Annual Sum or Average | 0.119305E+11 | 0.537703E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3611158.98 | 0.750032E+10 |
Minimum of Months | 0.901968E+09 | 0.347690E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296010E+09 |
Maximum of Months | 0.107774E+10 | 0.638535E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2363659.74 | 0.115262E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.403186E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529240E+09 |
February | 0.570983E+09 | 0.294977E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426711E+09 |
March | 0.682256E+09 | 0.283655E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642073E+09 |
April | 0.605404E+09 | 0.226600E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757127E+09 |
May | 0.655811E+09 | 0.234742E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460897E+09 |
June | 0.653980E+09 | 0.228857E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 569456.53 | 0.268840E+09 |
July | 0.607235E+09 | 0.217593E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1442838.96 | 0.201574E+09 |
August | 0.682256E+09 | 0.249201E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262948.38 | 0.237627E+09 |
September | 0.605404E+09 | 0.242907E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277835E+09 |
October | 0.629366E+09 | 0.295586E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558799E+09 |
November | 0.623221E+09 | 0.366978E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195922E+09 |
December | 0.607235E+09 | 0.416762E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385088E+09 |
Annual Sum or Average | 0.755252E+10 | 0.346104E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2275243.87 | 0.494174E+10 |
Minimum of Months | 0.570983E+09 | 0.217593E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195922E+09 |
Maximum of Months | 0.682256E+09 | 0.416762E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1442838.96 | 0.757127E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103805E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845776E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128604E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148623E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892340E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587052.08 | 0.517756E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2349960.81 | 0.383960E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140353.73 | 0.467695E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561816E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114835E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394120E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762908E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3077366.62 | 0.978505E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383960E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2349960.81 | 0.148623E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131827E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107585E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163133E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187765E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114328E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739982.97 | 0.666815E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3015826.41 | 0.494469E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183835.23 | 0.595749E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700140E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141825E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496187E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966234E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3939644.60 | 0.123842E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494469E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3015826.41 | 0.187765E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138724E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112803E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169429E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194995E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121138E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514042.66 | 0.720279E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2092363.37 | 0.540767E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58096.51 | 0.630140E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716681E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144770E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514204E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101226E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2664502.55 | 0.129529E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514204E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2092363.37 | 0.194995E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4251.78 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 735.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2520.28 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 735.45 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1885.67 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 408.45 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2597.05 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1253.76 | 26-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1197.73 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 371.68 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 913.40 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 383.84 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 982.95 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 697.91 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 762.55 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 735.45 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1563.13 | 21-OCT-04:06 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1344.17 | 09-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1449.41 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.55 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4251.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2834.50 | 28-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 465.60 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1689.12 | 25-FEB-00:57 |
March | 827.22 | 01-MAR-10:09 | 465.60 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1257.64 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 222.09 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1730.12 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 840.16 | 26-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 797.01 | 24-JUN-21:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 612.93 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 243.68 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 654.81 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 393.65 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 514.98 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 465.60 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1058.41 | 21-OCT-04:04 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.78 | 09-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 972.60 | 28-DEC-02:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.98 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2834.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4251.78 | 28-JAN-23:57 |
February | 1306.65 | 01-FEB-10:09 | 735.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2531.89 | 25-FEB-00:57 |
March | 1306.65 | 01-MAR-10:09 | 735.45 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1962.78 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 408.30 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2833.16 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1269.87 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1200.05 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 931.88 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 350.81 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 989.64 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 667.90 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 778.63 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 735.45 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1583.21 | 21-OCT-04:04 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1345.33 | 09-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1457.82 | 28-DEC-02:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.63 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4251.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2834.50 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 465.57 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1689.38 | 25-FEB-00:57 |
March | 827.17 | 01-MAR-10:09 | 465.57 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1257.76 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 325.92 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2089.40 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 839.74 | 26-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 222.08 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 796.03 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 241.97 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 621.62 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 242.06 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 654.90 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 442.98 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 507.39 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 465.57 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1059.23 | 21-OCT-04:04 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.94 | 09-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 972.49 | 28-DEC-02:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.39 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2834.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2241.56 | 28-JAN-23:53 |
February | 1306.65 | 01-FEB-10:09 | 735.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1338.34 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 735.45 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1002.14 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 406.31 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1404.97 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 681.47 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 30-JUN-15:00 | 665.41 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 | 21-JUL-16:00 | 481.17 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 380.65 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 11-AUG-16:00 | 557.84 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 695.86 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 437.60 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 735.45 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 862.51 | 21-OCT-04:02 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 737.10 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 771.72 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.60 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 | 2241.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1492.79 | 28-JAN-23:53 |
February | 827.22 | 01-FEB-10:09 | 465.60 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 892.22 | 25-FEB-00:57 |
March | 827.22 | 01-MAR-10:09 | 465.60 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 669.18 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 222.09 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 951.02 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 473.41 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 448.92 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 21-JUL-16:00 | 330.76 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 241.84 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 378.04 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 389.07 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 305.11 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 465.60 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 577.07 | 21-OCT-04:02 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 490.03 | 10-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 512.44 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.11 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 1492.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 55658.30 | 12-JAN-12:01 |
February | 1306.65 | 01-FEB-10:09 | 735.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 50586.09 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 735.45 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 45573.80 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 406.15 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 38035.68 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15195.22 | 16-MAY-07:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.33 | 21-JUN-17:00 | 12202.28 | 01-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.08 | 21-JUL-16:10 | 11777.30 | 17-JUL-06:01 |
August | 1306.65 | 01-AUG-09:09 | 350.81 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.73 | 11-AUG-16:10 | 19976.98 | 31-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 663.94 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20883.77 | 29-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 735.45 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 34944.78 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45511.08 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 51403.03 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11777.30 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.08 | 55658.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1493.13 | 28-JAN-23:53 |
February | 827.17 | 01-FEB-10:09 | 465.57 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 892.22 | 25-FEB-00:57 |
March | 827.17 | 01-MAR-10:09 | 465.57 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 668.79 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 321.67 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1111.45 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 459.05 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 222.08 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 444.96 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 240.14 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 21-JUL-16:00 | 333.14 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 240.22 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 377.16 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 441.90 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 298.77 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 465.57 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 573.74 | 21-OCT-04:02 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 490.83 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 512.78 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.77 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 1493.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.00 | 28-JAN-23:57 |
February | 1306.65 | 01-FEB-10:09 | 735.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2096.25 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 735.45 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1573.82 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 408.45 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2242.73 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1102.01 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1064.55 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 371.67 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 21-JUL-16:00 | 784.51 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 383.83 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 864.14 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 697.91 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 686.87 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 735.45 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1311.92 | 21-OCT-04:02 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1137.51 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1200.59 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.87 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 3537.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.98 | 28-JAN-23:53 |
February | 805.43 | 01-FEB-08:09 | 465.60 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1397.43 | 25-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 465.60 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1049.87 | 14-MAR-21:02 |
April | 805.43 | 03-APR-07:10 | 222.09 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1496.63 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 738.01 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 709.98 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 21-JUL-16:00 | 526.68 | 04-JUL-17:00 |
August | 805.43 | 01-AUG-07:10 | 243.68 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 575.65 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 393.65 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 463.36 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 465.60 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 873.57 | 21-OCT-04:02 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 755.04 | 10-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 796.68 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.36 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 2357.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.00 | 28-JAN-23:53 |
February | 1306.65 | 01-FEB-10:09 | 735.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2096.52 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 735.45 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1718.98 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 408.30 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2440.09 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1115.78 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1055.90 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 350.81 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 21-JUL-16:00 | 800.28 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 350.81 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 868.96 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 667.90 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 700.30 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 735.45 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1346.00 | 22-OCT-17:53 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1147.53 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1203.39 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 700.30 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 3537.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.99 | 28-JAN-23:53 |
February | 827.17 | 01-FEB-10:09 | 465.57 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1397.37 | 25-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 465.57 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1049.80 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 325.90 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1796.47 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 737.44 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 222.08 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 699.29 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 241.97 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 21-JUL-16:00 | 534.12 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 242.06 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 575.35 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 442.98 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 457.18 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 465.57 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 871.73 | 21-OCT-04:02 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 756.69 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 797.71 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.18 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 2357.99 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4722.39 | 28-JAN-23:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2848.82 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2004.40 | 25-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3138.84 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1508.46 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.44 | 30-JUN-15:00 | 1448.08 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.89 | 29-JUL-17:03 | 986.95 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 11-AUG-16:00 | 1186.25 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 913.89 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1858.19 | 21-OCT-04:02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1565.71 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1633.45 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 913.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.89 | 4722.39 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5962.97 | 28-JAN-23:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3634.19 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2560.58 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3953.56 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1927.41 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.68 | 30-JUN-15:00 | 1820.37 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.75 | 21-JUL-16:00 | 1254.28 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 11-AUG-16:00 | 1506.18 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1114.08 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2301.28 | 21-OCT-04:02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1981.34 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2087.18 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1114.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.75 | 5962.97 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6151.54 | 28-JAN-23:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3790.37 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2770.12 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4285.78 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1931.61 | 26-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.27 | 30-JUN-15:00 | 1850.26 | 24-JUN-21:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.72 | 21-JUL-16:00 | 1442.69 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 | 11-AUG-16:00 | 1482.65 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1204.84 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2299.49 | 21-OCT-04:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2024.70 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2159.28 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1204.84 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.72 | 6151.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5483.31 | 27-JAN-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5916.53 | 17-FEB-16:40 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6749.30 | 23-MAR-15:30 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14925.89 | 25-APR-07:02 | 48280.06 | 27909.61 | 102066.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31725.14 | 15-MAY-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34648.80 | 05-JUN-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34463.43 | 24-JUL-05:12 | 3176.32 | 1938.17 | 20240.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34438.41 | 01-AUG-06:02 | 10164.22 | 9303.20 | 48352.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23513.04 | 11-SEP-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12259.07 | 04-OCT-07:15 | 12070.02 | 6977.40 | 25516.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5800.18 | 03-NOV-16:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5310.98 | 22-DEC-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5310.98 | 2541.06 | 1550.53 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34648.80 | 48280.06 | 27909.61 | 102066.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.14 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.62 |
March | 531.34 | 22-MAR-17:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.77 |
April | 3604.18 | 21-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.24 |
May | 6267.80 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 |
June | 7136.48 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 0.00 |
July | 7196.47 | 21-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 0.00 |
August | 6085.92 | 10-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 |
September | 2545.32 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.96 |
October | 335.05 | 03-OCT-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.51 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1137.74 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7196.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 1227.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3584.01 | 12-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3250.21 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2575.06 |
March | 3434.16 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2062.26 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.55 |
May | 3047.35 | 31-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 |
June | 4021.27 | 05-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.55 |
July | 5887.23 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 |
August | 3354.34 | 11-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
September | 1267.74 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.78 |
October | 2297.68 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2094.58 |
November | 3276.16 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3788.53 | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1267.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5887.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 2575.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4024.64 | 12-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4181.49 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.07 |
March | 4460.66 | 31-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3202.95 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.06 |
May | 3053.41 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.77 |
June | 4361.45 | 22-JUN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
July | 5788.85 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.21 |
August | 4317.59 | 28-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.48 |
September | 2617.98 | 01-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 |
October | 2643.35 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.46 |
November | 3352.04 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3823.04 | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2617.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5788.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4666.71 | 20-JAN-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5277.82 | 09-FEB-15:10 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5859.74 | 22-MAR-15:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11430.69 | 28-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25998.21 | 15-MAY-06:02 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30193.98 | 05-JUN-06:03 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30463.37 | 24-JUL-06:03 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27694.80 | 07-AUG-06:01 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11757.35 | 01-SEP-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6434.33 | 05-OCT-15:10 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4851.40 | 02-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4515.12 | 21-DEC-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4515.12 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30463.37 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 3998.38 | 28-JAN-17:01 | 2223.42 | 1356.53 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4915.74 | 09-FEB-15:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5769.27 | 22-MAR-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11372.46 | 21-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15202.80 | 31-MAY-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25747.55 | 12-JUN-06:01 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29725.96 | 24-JUL-06:03 | 7623.17 | 6977.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15332.15 | 01-AUG-14:00 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10882.85 | 01-SEP-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6010.46 | 04-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4245.52 | 08-NOV-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3981.87 | 30-DEC-17:02 | 1588.16 | 968.95 | 11347.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 3981.87 | 1588.16 | 968.95 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29725.96 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 829.95 | 07-JAN-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.13 |
February | 840.50 | 11-FEB-17:03 | 267.84 | 163.41 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.23 |
March | 1120.33 | 22-MAR-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2325.83 | 28-APR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.11 |
May | 8817.83 | 31-MAY-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 |
June | 9329.07 | 08-JUN-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.64 |
July | 9439.23 | 11-JUL-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.47 |
August | 5601.38 | 02-AUG-06:01 | 1874.87 | 818.55 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
September | 2303.58 | 01-SEP-15:50 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.41 |
October | 1143.38 | 04-OCT-15:50 | 1272.23 | 397.59 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.07 |
November | 828.21 | 18-NOV-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 827.16 | 30-DEC-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 827.16 | 267.84 | 163.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9439.23 | 1874.87 | 818.55 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 506.77 | 07-JAN-17:02 | 211.95 | 129.32 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.37 |
February | 594.88 | 09-FEB-11:45 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.06 |
March | 1891.19 | 31-MAR-09:25 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.95 |
April | 5800.56 | 22-APR-09:20 | 261.23 | 74.03 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.13 |
May | 15039.56 | 14-MAY-09:31 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.77 |
June | 12108.32 | 13-JUN-05:12 | 423.91 | 123.38 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.42 |
July | 13900.18 | 23-JUL-09:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.36 |
August | 11088.31 | 10-AUG-06:01 | 1186.95 | 518.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.57 |
September | 5228.31 | 10-SEP-10:23 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.25 |
October | 1783.75 | 03-OCT-09:50 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.61 |
November | 506.53 | 18-NOV-17:02 | 211.95 | 129.32 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 505.13 | 30-DEC-17:02 | 211.95 | 129.32 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 505.13 | 127.17 | 37.01 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15039.56 | 1654.44 | 518.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1021.89 | 25-JAN-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.90 |
February | 3960.32 | 15-FEB-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7869.55 | 31-MAR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.53 |
April | 13019.21 | 20-APR-14:00 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 |
May | 22675.95 | 21-MAY-13:22 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.35 |
June | 17902.76 | 04-JUN-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.21 |
July | 22406.06 | 23-JUL-13:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.95 |
August | 21508.92 | 27-AUG-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.40 |
September | 15480.15 | 10-SEP-11:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.06 |
October | 8734.82 | 03-OCT-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.47 |
November | 1843.36 | 08-NOV-13:16 | 6361.16 | 1754.05 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.63 |
December | 799.30 | 30-DEC-17:02 | 334.80 | 204.26 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 799.30 | 267.84 | 77.95 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22675.95 | 6361.16 | 1754.05 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 507.26 | 07-JAN-17:02 | 211.94 | 129.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.35 |
February | 584.24 | 09-FEB-15:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 |
March | 946.42 | 31-MAR-17:00 | 254.33 | 123.38 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.13 |
April | 7162.52 | 22-APR-17:08 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.28 |
May | 14390.95 | 14-MAY-18:12 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.83 |
June | 13308.70 | 10-JUN-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.96 |
July | 10748.42 | 09-JUL-19:53 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.49 |
August | 9432.75 | 27-AUG-17:12 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.29 |
September | 5879.39 | 02-SEP-17:43 | 127.16 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.81 |
October | 961.22 | 03-OCT-15:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.10 |
November | 508.65 | 18-NOV-17:02 | 211.94 | 129.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 506.01 | 30-DEC-17:02 | 211.94 | 129.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 506.01 | 0.00 | 37.01 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14390.95 | 805.38 | 222.08 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 806.45 | 07-JAN-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
February | 808.96 | 11-FEB-17:03 | 267.84 | 163.41 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.19 |
March | 865.99 | 22-MAR-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1238.12 | 28-APR-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.45 |
May | 2521.89 | 31-MAY-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
June | 7405.00 | 13-JUN-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 |
July | 7803.08 | 11-JUL-05:14 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 |
August | 6422.01 | 02-AUG-06:01 | 1874.87 | 818.55 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
September | 1845.48 | 01-SEP-13:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 |
October | 1148.94 | 06-OCT-15:00 | 1272.23 | 386.27 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.66 |
November | 812.26 | 18-NOV-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 807.26 | 30-DEC-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 806.45 | 267.84 | 163.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7803.08 | 1874.87 | 818.55 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 558.09 | 20-JAN-07:03 | 1695.64 | 1552.00 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 |
February | 560.87 | 15-FEB-10:40 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.15 |
March | 1331.18 | 31-MAR-09:00 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3821.45 | 22-APR-08:30 | 254.35 | 74.03 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
May | 8753.68 | 21-MAY-07:52 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.63 |
June | 10023.50 | 13-JUN-05:12 | 423.91 | 123.38 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 |
July | 11225.42 | 23-JUL-10:01 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 |
August | 8817.00 | 25-AUG-06:01 | 1356.51 | 592.24 | 3230.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8427.64 | 10-SEP-09:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.06 |
October | 2171.63 | 03-OCT-09:25 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 |
November | 557.80 | 03-NOV-06:03 | 1695.64 | 1552.00 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.93 |
December | 510.62 | 30-DEC-17:02 | 211.95 | 129.32 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 510.62 | 169.56 | 49.35 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11225.42 | 1695.64 | 1552.00 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 811.77 | 28-JAN-17:01 | 468.72 | 285.97 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.79 |
February | 1075.04 | 18-FEB-13:30 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.67 |
March | 1270.73 | 11-MAR-13:40 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.68 |
April | 10012.28 | 23-APR-13:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.10 |
May | 10512.82 | 21-MAY-13:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.56 |
June | 9140.37 | 04-JUN-14:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.89 |
July | 17624.39 | 23-JUL-14:01 | 535.68 | 155.89 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.41 |
August | 14975.49 | 27-AUG-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.05 |
September | 12915.20 | 10-SEP-11:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.31 |
October | 5508.25 | 03-OCT-13:40 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1485.11 |
November | 919.96 | 08-NOV-13:14 | 6361.16 | 1754.05 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4235.90 |
December | 805.16 | 30-DEC-17:02 | 334.80 | 204.26 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 805.16 | 133.92 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | |
Maximum of Months | 17624.39 | 6361.16 | 1754.05 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4235.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 508.29 | 07-JAN-17:02 | 211.94 | 129.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 |
February | 510.66 | 11-FEB-17:03 | 169.55 | 103.45 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 |
March | 736.06 | 31-MAR-17:00 | 254.33 | 123.38 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.57 |
April | 5038.10 | 21-APR-18:20 | 84.78 | 74.03 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
May | 5190.87 | 14-MAY-19:22 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.67 |
June | 9826.13 | 11-JUN-17:22 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.72 |
July | 7971.92 | 09-JUL-19:42 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.68 |
August | 6348.60 | 01-AUG-06:01 | 1356.42 | 592.20 | 3230.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3542.73 | 08-SEP-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
October | 854.38 | 03-OCT-15:20 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 |
November | 553.75 | 02-NOV-06:03 | 1695.53 | 1551.90 | 4038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 509.19 | 30-DEC-17:02 | 211.94 | 129.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 508.29 | 0.00 | 49.34 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9826.13 | 1695.53 | 1551.90 | 4038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 817.46 | 07-JAN-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.91 |
February | 872.20 | 09-FEB-07:05 | 1607.03 | 1470.90 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.51 |
March | 1111.87 | 22-MAR-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2511.66 | 28-APR-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8557.27 | 31-MAY-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 |
June | 8916.87 | 19-JUN-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.01 |
July | 9017.58 | 11-JUL-05:12 | 669.60 | 194.89 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.01 |
August | 7506.36 | 02-AUG-06:01 | 1874.87 | 818.55 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 |
September | 2678.01 | 01-SEP-13:40 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.74 |
October | 1199.36 | 04-OCT-16:00 | 1272.23 | 406.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.60 |
November | 816.89 | 18-NOV-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 815.68 | 30-DEC-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 815.68 | 334.80 | 194.89 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9017.58 | 1874.87 | 1470.90 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 572.34 | 27-JAN-07:03 | 1695.64 | 1552.00 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.49 |
February | 692.00 | 15-FEB-11:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 |
March | 7441.30 | 31-MAR-12:01 | 8054.28 | 2220.91 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 |
April | 7677.08 | 28-APR-12:01 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 |
May | 13640.48 | 21-MAY-08:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.85 |
June | 13975.26 | 04-JUN-09:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.22 |
July | 14149.29 | 09-JUL-07:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.11 |
August | 10756.54 | 24-AUG-06:01 | 1186.95 | 518.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.71 |
September | 11287.75 | 10-SEP-09:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.85 |
October | 5520.81 | 03-OCT-12:01 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 |
November | 572.87 | 02-NOV-12:02 | 8054.28 | 2453.18 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 557.13 | 21-DEC-13:02 | 8054.28 | 4463.20 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 557.13 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14149.29 | 8054.28 | 4463.20 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1161.39 | 25-JAN-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.45 |
February | 4754.92 | 15-FEB-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8893.41 | 31-MAR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.91 |
April | 16203.06 | 23-APR-13:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.14 |
May | 19660.13 | 14-MAY-12:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.36 |
June | 20677.18 | 04-JUN-14:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.91 |
July | 20957.96 | 23-JUL-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.96 |
August | 20611.79 | 27-AUG-13:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.89 |
September | 16521.23 | 10-SEP-11:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.19 |
October | 9549.91 | 03-OCT-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.96 |
November | 2921.46 | 08-NOV-13:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.69 |
December | 902.53 | 21-DEC-07:03 | 2678.38 | 2451.50 | 6378.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 902.53 | 267.84 | 77.95 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20957.96 | 2678.38 | 2451.50 | 6378.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 573.87 | 27-JAN-07:03 | 1695.53 | 1551.90 | 4038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.49 |
February | 625.97 | 15-FEB-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 |
March | 1392.99 | 31-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.86 |
April | 7709.15 | 22-APR-17:08 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.07 |
May | 12260.38 | 28-MAY-17:03 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.98 |
June | 12980.73 | 04-JUN-15:22 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.59 |
July | 10646.65 | 09-JUL-19:42 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.10 |
August | 10526.17 | 27-AUG-18:53 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.55 |
September | 6438.80 | 02-SEP-17:43 | 127.16 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.98 |
October | 1312.48 | 03-OCT-15:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 |
November | 594.85 | 08-NOV-15:40 | 805.38 | 410.97 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 |
December | 515.44 | 30-DEC-17:02 | 211.94 | 129.31 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 515.44 | 0.00 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 | |
Maximum of Months | 12980.73 | 1695.53 | 1551.90 | 4038.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.208255E+12 | 250223.45 | 02-JAN-08:09 | 0.700173E+11 | 211342.65 | 12-JAN-07:49 |
February | 0.156421E+12 | 240092.81 | 27-FEB-07:10 | 0.458400E+11 | 187762.34 | 27-FEB-08:00 |
March | 0.133360E+12 | 208080.84 | 06-MAR-07:10 | 0.260868E+11 | 170317.47 | 01-MAR-07:49 |
April | 0.863669E+11 | 173390.53 | 03-APR-06:10 | 0.132306E+11 | 37777.41 | 29-APR-06:10 |
May | 0.844605E+11 | 93204.52 | 31-MAY-15:30 | 0.131177E+11 | 30243.12 | 05-MAY-06:10 |
June | 0.965408E+11 | 120026.00 | 30-JUN-12:30 | 0.125277E+11 | 13439.43 | 01-JUN-11:30 |
July | 0.995799E+11 | 119787.45 | 11-JUL-15:50 | 0.120781E+11 | 12307.21 | 05-JUL-11:00 |
August | 0.947082E+11 | 114238.77 | 11-AUG-15:50 | 0.126053E+11 | 11947.22 | 30-AUG-06:10 |
September | 0.796091E+11 | 95520.45 | 28-SEP-06:10 | 0.118244E+11 | 16377.58 | 21-SEP-06:10 |
October | 0.114101E+12 | 199947.43 | 30-OCT-06:10 | 0.156989E+11 | 29936.83 | 31-OCT-07:10 |
November | 0.175552E+12 | 230093.85 | 27-NOV-07:10 | 0.625382E+11 | 172546.35 | 29-NOV-07:00 |
December | 0.205145E+12 | 228696.57 | 04-DEC-07:10 | 0.880789E+11 | 191045.11 | 15-DEC-08:09 |
Annual Sum or Average | 0.153410E+13 | 0.383644E+12 | ||||
Minimum of Months | 0.796091E+11 | 93204.52 | 0.118244E+11 | 11947.22 | ||
Maximum of Months | 0.208255E+12 | 250223.45 | 0.880789E+11 | 211342.65 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.391855E+09 | 3468.62 | 31-JAN-11:30 | 0.00 | 0.00 |
February | 0.220926E+10 | 8200.08 | 26-FEB-13:09 | 0.00 | 0.00 |
March | 0.792112E+10 | 18484.64 | 30-MAR-12:30 | 0.00 | 0.00 |
April | 0.146157E+11 | 21421.58 | 30-APR-13:30 | 0.00 | 0.00 |
May | 0.181856E+11 | 22835.26 | 21-MAY-12:00 | 0.00 | 0.00 |
June | 0.186771E+11 | 22915.57 | 01-JUN-12:30 | 0.00 | 0.00 |
July | 0.172062E+11 | 22711.06 | 06-JUL-12:50 | 0.00 | 0.00 |
August | 0.132451E+11 | 19992.05 | 10-AUG-12:30 | 0.00 | 0.00 |
September | 0.724677E+10 | 14797.34 | 09-SEP-12:30 | 0.00 | 0.00 |
October | 0.325622E+10 | 9791.56 | 03-OCT-12:30 | 0.00 | 0.00 |
November | 0.757056E+09 | 4166.51 | 06-NOV-13:30 | 0.00 | 0.00 |
December | 75247725.88 | 1105.20 | 02-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.103787E+12 | 0.00 | 0.00 | ||
Minimum of Months | 75247725.88 | 1105.20 | 0.00 | 0.00 | |
Maximum of Months | 0.186771E+11 | 22915.57 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.161499E+11 | 0.592958E+10 | 0.545046E+11 | 0.978974E+09 | 0.523346E+10 | 12379742.02 | 0.122590E+12 | 2289683.75 | 0.00 | 0.00 | 0.285363E+10 | 0.00 | 0.00 |
February | 0.136341E+11 | 0.407989E+10 | 0.493409E+11 | 0.884755E+09 | 0.428782E+10 | 11196021.66 | 0.815638E+11 | 3567656.24 | 0.00 | 0.00 | 0.261516E+10 | 0.00 | 0.00 |
March | 0.151342E+11 | 0.317157E+10 | 0.567112E+11 | 0.102264E+10 | 0.408689E+10 | 12675672.10 | 0.501214E+11 | 7220623.71 | 0.00 | 0.00 | 0.309209E+10 | 0.00 | 0.00 |
April | 0.130865E+11 | 0.193266E+10 | 0.526212E+11 | 0.940377E+09 | 0.442861E+10 | 11960507.72 | 0.109393E+11 | 0.254569E+09 | 0.00 | 0.00 | 0.215173E+10 | 0.00 | 0.00 |
May | 0.140084E+11 | 0.114978E+10 | 0.556079E+11 | 0.999196E+09 | 0.825006E+10 | 12527707.06 | 0.842517E+09 | 0.312816E+10 | 0.00 | 0.00 | 0.461959E+09 | 0.00 | 0.00 |
June | 0.138573E+11 | 0.594081E+09 | 0.546110E+11 | 0.983520E+09 | 0.125572E+11 | 12231776.97 | 0.179247E+09 | 0.135811E+11 | 0.00 | 0.00 | 0.165090E+09 | 0.00 | 0.00 |
July | 0.130258E+11 | 0.851526E+09 | 0.536070E+11 | 0.955844E+09 | 0.124373E+11 | 12256437.81 | 0.127100E+09 | 0.183120E+11 | 0.00 | 0.00 | 0.251122E+09 | 0.00 | 0.00 |
August | 0.146164E+11 | 0.159100E+10 | 0.567112E+11 | 0.102229E+10 | 0.994814E+10 | 12675672.10 | 0.391553E+09 | 0.101553E+11 | 0.00 | 0.00 | 0.259745E+09 | 0.00 | 0.00 |
September | 0.133523E+11 | 0.255107E+10 | 0.525990E+11 | 0.940283E+09 | 0.434461E+10 | 11960507.72 | 0.320167E+10 | 0.959208E+09 | 0.00 | 0.00 | 0.164907E+10 | 0.00 | 0.00 |
October | 0.145558E+11 | 0.389586E+10 | 0.545158E+11 | 0.977135E+09 | 0.357097E+10 | 12379742.02 | 0.338112E+11 | 23673333.98 | 0.00 | 0.00 | 0.273815E+10 | 0.00 | 0.00 |
November | 0.155077E+11 | 0.520287E+10 | 0.533244E+11 | 0.960211E+09 | 0.431685E+10 | 12059151.09 | 0.934599E+11 | 1689997.18 | 0.00 | 0.00 | 0.276619E+10 | 0.00 | 0.00 |
December | 0.160341E+11 | 0.651247E+10 | 0.535958E+11 | 0.958942E+09 | 0.497047E+10 | 12256437.81 | 0.120238E+12 | 1436224.32 | 0.00 | 0.00 | 0.282183E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.172963E+12 | 0.374624E+11 | 0.647750E+12 | 0.116242E+11 | 0.784323E+11 | 0.146559E+09 | 0.517465E+12 | 0.464303E+11 | 0.00 | 0.00 | 0.218258E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130258E+11 | 0.594081E+09 | 0.493409E+11 | 0.884755E+09 | 0.357097E+10 | 11196021.66 | 0.127100E+09 | 1436224.32 | 0.00 | 0.00 | 0.165090E+09 | 0.00 | 0.00 |
Maximum of Months | 0.161499E+11 | 0.651247E+10 | 0.567112E+11 | 0.102264E+10 | 0.125572E+11 | 12675672.10 | 0.122590E+12 | 0.183120E+11 | 0.00 | 0.00 | 0.309209E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.571059E+11 | 0.00 | 0.129114E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.341548E+11 | 0.00 | 0.116852E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.126902E+11 | 0.00 | 0.133966E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.808311E+09 | 0.00 | 0.124223E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 90907936.33 | 0.00 | 0.130268E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6175126.85 | 0.00 | 0.125215E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1958419.70 | 0.00 | 0.120762E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 39935016.47 | 0.00 | 0.125653E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.128349E+09 | 0.00 | 0.116960E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.345613E+10 | 0.00 | 0.122428E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.503296E+11 | 0.00 | 0.122087E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.754671E+11 | 0.00 | 0.126117E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234279E+12 | 0.00 | 0.149365E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1958419.70 | 0.00 | 0.116852E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.754671E+11 | 0.00 | 0.133966E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-08:09 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 829.79 | 02-JAN-08:20 | 7802.26 | 02-JAN-07:10 | 6.85 | 06-JAN-17:19 | 203187.01 | 02-JAN-06:19 |
February | 17672.30 | 01-FEB-08:09 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 829.79 | 01-FEB-08:20 | 7548.19 | 27-FEB-07:10 | 6.85 | 02-FEB-06:10 | 202025.00 | 27-FEB-07:10 |
March | 17672.30 | 01-MAR-08:09 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 829.79 | 01-MAR-08:20 | 5707.46 | 06-MAR-07:10 | 6.85 | 01-MAR-17:19 | 171821.60 | 06-MAR-07:10 |
April | 14551.83 | 04-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 825.67 | 04-APR-07:19 | 11363.33 | 21-APR-15:39 | 6.85 | 01-APR-05:10 | 138303.35 | 03-APR-06:10 |
May | 13903.46 | 01-MAY-07:10 | 2323.70 | 01-MAY-21:10 | 40437.79 | 01-MAY-07:10 | 824.82 | 01-MAY-07:19 | 18021.16 | 31-MAY-15:09 | 6.85 | 02-MAY-16:10 | 14938.67 | 03-MAY-06:10 |
June | 13903.46 | 01-JUN-07:10 | 2323.70 | 01-JUN-22:49 | 40437.79 | 01-JUN-07:10 | 824.82 | 01-JUN-07:30 | 22353.48 | 20-JUN-15:30 | 6.85 | 01-JUN-05:10 | 9654.66 | 02-JUN-06:19 |
July | 13961.31 | 25-JUL-07:10 | 2323.70 | 11-JUL-22:00 | 40437.79 | 03-JUL-07:10 | 824.90 | 25-JUL-07:19 | 24354.03 | 12-JUL-15:20 | 6.85 | 05-JUL-11:09 | 7970.94 | 05-JUL-06:19 |
August | 14062.28 | 18-AUG-15:00 | 3824.74 | 24-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 824.90 | 07-AUG-07:19 | 22159.45 | 10-AUG-15:39 | 6.85 | 01-AUG-06:10 | 19481.15 | 31-AUG-06:10 |
September | 17061.54 | 28-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 828.98 | 28-SEP-07:19 | 9354.13 | 08-SEP-15:30 | 6.85 | 05-SEP-16:10 | 61378.03 | 28-SEP-06:10 |
October | 17672.30 | 03-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 829.79 | 26-OCT-07:19 | 5401.83 | 30-OCT-06:10 | 6.85 | 03-OCT-16:10 | 163939.39 | 30-OCT-06:10 |
November | 17672.30 | 01-NOV-07:10 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 829.79 | 03-NOV-07:19 | 6857.86 | 27-NOV-07:10 | 6.85 | 01-NOV-05:10 | 192716.38 | 27-NOV-07:10 |
December | 17672.30 | 01-DEC-08:09 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 829.79 | 01-DEC-08:20 | 6724.69 | 04-DEC-07:10 | 6.85 | 01-DEC-06:10 | 191452.26 | 04-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 13903.46 | 2323.70 | 40437.79 | 824.82 | 5401.83 | 6.85 | 7970.94 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 40437.79 | 829.79 | 24354.03 | 6.85 | 203187.01 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 521.73 | 07-JAN-07:10 | 0.00 | 0.00 | 2208.01 | 02-JAN-08:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 650.43 | 09-FEB-07:10 | 0.00 | 0.00 | 2208.01 | 01-FEB-12:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 543.20 | 23-MAR-06:10 | 0.00 | 0.00 | 2208.01 | 01-MAR-08:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 5554.53 | 21-APR-12:09 | 0.00 | 0.00 | 2208.01 | 01-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23219.96 | 31-MAY-15:00 | 0.00 | 0.00 | 2208.01 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 42928.32 | 30-JUN-14:30 | 0.00 | 0.00 | 2208.01 | 01-JUN-06:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 40926.03 | 11-JUL-15:00 | 0.00 | 0.00 | 2208.01 | 11-JUL-12:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 36930.69 | 11-AUG-15:50 | 0.00 | 0.00 | 2208.01 | 30-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 10574.72 | 08-SEP-12:00 | 0.00 | 0.00 | 2208.01 | 01-SEP-06:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 1942.30 | 03-OCT-13:30 | 0.00 | 0.00 | 2208.01 | 02-OCT-16:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 513.76 | 04-NOV-06:10 | 0.00 | 0.00 | 2208.01 | 01-NOV-17:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 528.70 | 23-DEC-07:10 | 0.00 | 0.00 | 2208.01 | 02-DEC-17:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 513.76 | 0.00 | 0.00 | 2208.01 | 0.00 | 0.00 | |||
Maximum of Months | 42928.32 | 0.00 | 0.00 | 2208.01 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 250223.45 | 02-JAN-08:09 | 17672.30 | 40437.79 | 3824.74 | 814.34 | 6026.08 | 6.85 | 179233.33 | 0.00 | 0.00 |
February | 240092.81 | 27-FEB-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 7548.19 | 6.85 | 202025.00 | 0.00 | 0.00 |
March | 208080.84 | 06-MAR-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 5707.46 | 6.85 | 171821.60 | 32.16 | 0.00 |
April | 173390.53 | 03-APR-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 4567.56 | 6.85 | 138303.35 | 0.00 | 0.00 |
May | 93204.52 | 31-MAY-15:30 | 13903.46 | 38454.47 | 0.00 | 823.69 | 17750.57 | 6.85 | 0.00 | 22265.48 | 0.00 |
June | 120026.00 | 30-JUN-12:30 | 13903.46 | 38626.93 | 0.00 | 823.79 | 21558.32 | 6.85 | 0.00 | 42898.65 | 0.00 |
July | 119787.45 | 11-JUL-15:50 | 13903.46 | 38454.47 | 0.00 | 823.69 | 23551.28 | 6.85 | 0.00 | 40839.69 | 0.00 |
August | 114238.77 | 11-AUG-15:50 | 13903.46 | 38454.47 | 0.00 | 823.69 | 21911.60 | 6.85 | 0.00 | 36930.69 | 0.00 |
September | 95520.45 | 28-SEP-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3088.33 | 6.85 | 61378.03 | 534.47 | 0.00 |
October | 199947.43 | 30-OCT-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 5401.83 | 6.85 | 163939.39 | 86.60 | 0.00 |
November | 230093.85 | 27-NOV-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6857.86 | 6.85 | 192716.38 | 0.00 | 0.00 |
December | 228696.57 | 04-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6724.69 | 6.85 | 191452.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 93204.52 | 5890.77 | 18346.02 | 0.00 | 243.23 | 3088.33 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 250223.45 | 17672.30 | 40437.79 | 3824.74 | 823.79 | 23551.28 | 6.85 | 202025.00 | 42898.65 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 203018.77 | 12-JAN-07:00 | 0.00 | 14118.46 | 02-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 178280.66 | 27-FEB-08:50 | 0.00 | 14111.58 | 27-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 162287.28 | 01-MAR-07:40 | 0.00 | 14095.89 | 06-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 35890.97 | 29-APR-06:10 | 0.00 | 14071.87 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 21306.08 | 04-MAY-06:10 | 0.00 | 14042.14 | 03-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 2829.97 | 02-JUN-06:19 | 0.00 | 13439.43 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 1014.50 | 05-JUL-06:19 | 0.00 | 12307.21 | 05-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 3653.56 | 19-AUG-06:10 | 0.00 | 11455.33 | 09-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 14491.14 | 21-SEP-06:10 | 0.00 | 11406.14 | 27-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 21051.79 | 31-OCT-06:00 | 0.00 | 12221.24 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 163752.91 | 29-NOV-07:49 | 0.00 | 13195.99 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 184655.57 | 15-DEC-07:00 | 0.00 | 14088.58 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 1014.50 | 0.00 | 11406.14 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 203018.77 | 0.00 | 14118.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.02 | 2.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 19.02 | 2.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.02 | 2.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 19.04 | 4.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
February | 0.83 | 19.60 | 0.83 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
November | 1.17 | 19.58 | 1.17 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
December | 1.00 | 19.52 | 1.00 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
Annual Sum or Average | 7.83 | 19.25 | 7.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 19.60 | 4.00 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 18.94 | 7.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 5.33 | 19.01 | 4.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 1.17 | 19.27 | 1.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
April | 0.17 | 19.32 | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 18.67 | 0.50 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
November | 7.00 | 18.89 | 5.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 7.83 | 18.91 | 6.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 31.00 | 18.94 | 25.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 19.32 | 7.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.00 | 16.74 | 51.67 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
February | 64.33 | 16.72 | 36.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
March | 31.33 | 17.83 | 18.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
April | 5.83 | 17.13 | 2.67 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15.50 | 17.05 | 7.67 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
November | 61.17 | 17.08 | 35.67 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
December | 80.17 | 17.18 | 49.33 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
Annual Sum or Average | 344.33 | 17.02 | 201.00 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 86.00 | 17.83 | 51.67 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.00 | 14.73 | 15.83 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
February | 32.67 | 14.89 | 7.17 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
March | 11.17 | 15.60 | 0.67 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
April | 2.33 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.07 | 3.00 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.33 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.84 | 5.33 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.49 | 0.67 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
October | 8.67 | 15.25 | 1.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
November | 33.83 | 15.01 | 8.33 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
December | 46.17 | 14.98 | 14.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 183.83 | 14.96 | 47.17 | 14.95 | 11.00 | 15.53 | 10.83 | 16.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 0.00 | 14.71 |
Maximum of Months | 49.00 | 15.60 | 15.83 | 15.76 | 5.33 | 28.07 | 5.33 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.00 | 14.80 | 14.83 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
February | 24.67 | 14.96 | 3.50 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
March | 6.67 | 16.12 | 0.33 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
April | 0.83 | 16.06 | 0.00 | 16.06 | 1.17 | 22.76 | 1.17 | 24.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.82 | 5.00 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.78 | 3.17 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.92 | 5.33 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.91 | 2.67 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
October | 6.33 | 15.40 | 0.83 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
November | 25.67 | 15.13 | 5.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
December | 37.67 | 15.02 | 11.67 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
Annual Sum or Average | 146.83 | 15.03 | 36.17 | 15.01 | 18.17 | 16.17 | 17.67 | 17.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 | 14.79 |
Maximum of Months | 45.00 | 16.12 | 14.83 | 16.27 | 5.50 | 27.92 | 5.33 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.33 | 14.72 | 15.83 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
February | 34.00 | 14.84 | 8.83 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
March | 11.33 | 15.64 | 1.00 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
April | 1.00 | 15.74 | 0.00 | 15.74 | 0.50 | 19.70 | 0.17 | 20.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.81 | 1.67 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.90 | 1.50 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.66 | 2.00 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.75 | 0.83 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
October | 8.83 | 15.20 | 1.17 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
November | 33.83 | 15.00 | 8.83 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
December | 46.17 | 14.97 | 14.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Annual Sum or Average | 183.50 | 14.94 | 49.67 | 14.91 | 17.33 | 15.80 | 6.33 | 16.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 | 0.00 | 14.70 |
Maximum of Months | 48.33 | 15.74 | 15.83 | 15.77 | 5.17 | 27.90 | 2.00 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.67 | 18.43 | 67.67 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
February | 67.33 | 18.60 | 55.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
March | 20.83 | 19.16 | 17.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
April | 2.33 | 19.22 | 2.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.17 | 18.97 | 0.83 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
November | 19.33 | 19.27 | 16.67 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
December | 35.17 | 19.13 | 29.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Annual Sum or Average | 229.83 | 18.73 | 188.83 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.67 | 19.27 | 67.67 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.50 | 15.25 | 7.33 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
February | 11.67 | 15.40 | 2.17 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
March | 2.00 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
April | 0.17 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.60 | 2.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.33 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.56 | 4.17 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.51 | 0.50 | 27.51 |
October | 0.33 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
November | 2.83 | 16.79 | 0.17 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
December | 6.83 | 16.09 | 0.33 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
Annual Sum or Average | 46.33 | 15.59 | 10.00 | 15.58 | 8.33 | 17.12 | 7.83 | 18.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 | 15.27 |
Maximum of Months | 22.50 | 17.10 | 7.33 | 17.10 | 4.50 | 27.60 | 4.17 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 151.50 | 15.69 | 137.67 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
February | 90.83 | 15.76 | 86.50 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
March | 79.50 | 16.52 | 78.33 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
April | 26.17 | 18.08 | 26.17 | 18.08 | 0.83 | 18.22 | 0.83 | 18.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.45 | 1.67 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.37 | 1.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.71 | 2.83 | 27.71 |
August | 2.00 | 20.12 | 2.00 | 20.12 | 1.83 | 22.55 | 1.50 | 23.66 |
September | 8.17 | 19.17 | 8.17 | 19.17 | 0.33 | 19.33 | 0.33 | 19.49 |
October | 52.67 | 17.46 | 52.50 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
November | 98.83 | 15.07 | 96.33 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
December | 129.67 | 15.35 | 123.83 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
Annual Sum or Average | 639.33 | 15.94 | 611.50 | 15.94 | 8.83 | 16.03 | 8.50 | 16.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 0.00 | 15.05 |
Maximum of Months | 151.50 | 20.12 | 137.67 | 20.12 | 2.83 | 27.71 | 2.83 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.83 | 15.18 | 7.83 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
February | 14.00 | 15.32 | 3.50 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
March | 2.17 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.00 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.47 | 0.50 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 0.00 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.64 | 0.17 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
October | 0.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
November | 2.67 | 16.77 | 0.17 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
December | 6.67 | 16.06 | 0.50 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
Annual Sum or Average | 48.67 | 15.51 | 12.00 | 15.45 | 5.00 | 16.37 | 1.00 | 16.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 0.00 | 15.16 |
Maximum of Months | 22.83 | 17.07 | 7.83 | 17.07 | 2.00 | 27.64 | 0.50 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.50 | 16.85 | 22.17 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
February | 20.50 | 17.08 | 11.83 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
March | 4.67 | 18.49 | 2.67 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.67 | 18.17 | 0.33 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 18.52 | 1.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
November | 13.83 | 17.99 | 8.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
December | 19.83 | 17.87 | 11.67 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
Annual Sum or Average | 99.67 | 17.37 | 57.67 | 17.83 | 0.33 | 17.85 | 0.00 | 17.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.50 | 18.52 | 22.17 | 18.92 | 0.33 | 27.29 | 0.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.83 | 15.05 | 7.83 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
February | 9.17 | 15.31 | 1.83 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
March | 1.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
April | 0.17 | 16.84 | 0.00 | 16.84 | 0.50 | 24.72 | 0.50 | 25.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.13 | 3.33 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.58 | 1.67 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.74 | 5.50 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.56 | 1.17 | 27.56 |
October | 0.67 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
November | 5.67 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
December | 11.00 | 15.61 | 2.33 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
Annual Sum or Average | 53.00 | 15.35 | 12.00 | 15.30 | 14.67 | 17.60 | 13.00 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 0.00 | 15.03 |
Maximum of Months | 24.83 | 16.92 | 7.83 | 16.92 | 6.50 | 28.13 | 5.50 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.67 | 15.09 | 5.50 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
February | 5.50 | 15.65 | 1.67 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
March | 0.83 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
April | 0.17 | 17.21 | 0.00 | 17.21 | 1.83 | 26.73 | 1.83 | 27.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.81 | 5.50 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.75 | 3.33 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.91 | 4.83 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.86 | 3.17 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.71 | 0.50 | 27.71 |
October | 0.50 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
November | 3.33 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
December | 7.33 | 15.90 | 0.67 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
Annual Sum or Average | 36.33 | 15.51 | 7.83 | 15.44 | 19.50 | 19.23 | 19.17 | 21.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 | 0.00 | 15.06 |
Maximum of Months | 18.67 | 17.21 | 5.50 | 17.21 | 5.50 | 27.91 | 5.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.33 | 15.07 | 8.50 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
February | 10.67 | 15.26 | 3.17 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
March | 1.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
April | 0.17 | 17.07 | 0.00 | 17.07 | 0.50 | 25.06 | 0.17 | 25.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.83 | 1.50 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.85 | 1.33 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.63 | 1.83 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.73 | 0.83 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.49 | 0.17 | 27.49 |
October | 0.67 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
November | 5.67 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
December | 11.00 | 15.65 | 2.00 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
Annual Sum or Average | 55.00 | 15.36 | 13.67 | 15.29 | 16.83 | 17.75 | 5.83 | 18.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 | 15.04 |
Maximum of Months | 25.33 | 17.07 | 8.50 | 17.07 | 4.67 | 27.85 | 1.83 | 27.88 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.98 | 366.67 | 20.83 | 366.67 | 20.77 |
February | 454.00 | 21.46 | 204.33 | 21.25 | 204.33 | 21.14 |
March | 514.00 | 22.28 | 65.67 | 22.14 | 65.67 | 22.03 |
April | 451.33 | 23.51 | 2.00 | 23.50 | 2.00 | 23.49 |
May | 202.33 | 24.02 | 10.00 | 24.10 | 0.00 | 24.10 |
June | 8.00 | 24.00 | 165.00 | 24.91 | 0.00 | 24.91 |
July | 0.00 | 0.00 | 323.00 | 24.64 | 0.00 | 24.64 |
August | 24.00 | 24.01 | 202.33 | 24.71 | 0.00 | 24.71 |
September | 199.83 | 23.88 | 39.17 | 24.17 | 0.00 | 24.17 |
October | 502.00 | 23.06 | 9.00 | 23.02 | 9.00 | 22.99 |
November | 489.00 | 21.55 | 229.33 | 21.37 | 229.33 | 21.28 |
December | 497.00 | 21.16 | 383.67 | 21.06 | 383.67 | 21.01 |
Annual Sum or Average | 3843.50 | 22.21 | 2000.17 | 22.24 | 1260.67 | 21.99 |
Minimum of Months | 0.00 | 0.00 | 2.00 | 20.83 | 0.00 | 20.77 |
Maximum of Months | 514.00 | 24.02 | 383.67 | 24.91 | 383.67 | 24.91 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 467.17 | 20.43 | 467.17 | 20.42 |
February | 454.00 | 20.79 | 327.50 | 20.68 | 327.50 | 20.63 |
March | 514.00 | 21.39 | 222.50 | 21.22 | 222.50 | 21.13 |
April | 478.33 | 22.90 | 45.83 | 22.73 | 45.83 | 22.58 |
May | 335.67 | 23.90 | 2.67 | 23.91 | 0.00 | 23.91 |
June | 21.67 | 24.00 | 130.67 | 24.68 | 0.00 | 24.68 |
July | 0.00 | 0.00 | 273.67 | 24.58 | 0.00 | 24.58 |
August | 60.83 | 23.81 | 128.67 | 24.46 | 0.00 | 24.46 |
September | 352.67 | 23.34 | 0.33 | 23.35 | 0.00 | 23.35 |
October | 502.00 | 21.78 | 113.17 | 21.58 | 113.17 | 21.45 |
November | 489.00 | 20.72 | 420.00 | 20.66 | 420.00 | 20.64 |
December | 497.00 | 20.55 | 488.00 | 20.54 | 488.00 | 20.54 |
Annual Sum or Average | 4207.17 | 21.67 | 2620.17 | 21.57 | 2084.17 | 21.33 |
Minimum of Months | 0.00 | 0.00 | 0.33 | 20.43 | 0.00 | 20.42 |
Maximum of Months | 514.00 | 24.00 | 488.00 | 24.68 | 488.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 502.00 | 20.10 | 502.00 | 20.10 |
February | 454.00 | 20.28 | 419.17 | 20.24 | 419.17 | 20.22 |
March | 514.00 | 20.83 | 377.17 | 20.70 | 377.17 | 20.66 |
April | 485.00 | 22.29 | 116.67 | 21.94 | 116.67 | 21.71 |
May | 389.33 | 23.71 | 0.50 | 23.71 | 0.00 | 23.71 |
June | 45.67 | 23.90 | 102.00 | 24.43 | 0.00 | 24.43 |
July | 4.33 | 23.66 | 242.33 | 24.51 | 0.00 | 24.51 |
August | 120.33 | 23.55 | 93.33 | 24.02 | 0.00 | 24.02 |
September | 456.33 | 22.85 | 13.83 | 22.79 | 13.83 | 22.73 |
October | 502.00 | 20.95 | 290.83 | 20.75 | 290.83 | 20.66 |
November | 489.00 | 20.17 | 488.33 | 20.17 | 488.33 | 20.17 |
December | 497.00 | 20.12 | 497.00 | 20.12 | 497.00 | 20.12 |
Annual Sum or Average | 4459.00 | 21.28 | 3143.17 | 21.10 | 2705.00 | 20.88 |
Minimum of Months | 4.33 | 20.10 | 0.50 | 20.10 | 0.00 | 20.10 |
Maximum of Months | 514.00 | 23.90 | 502.00 | 24.51 | 502.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.67 | 502.00 | 19.67 | 502.00 | 19.67 |
February | 454.00 | 19.79 | 454.00 | 19.79 | 454.00 | 19.79 |
March | 514.00 | 20.17 | 488.67 | 20.15 | 488.67 | 20.14 |
April | 485.00 | 21.40 | 216.50 | 21.00 | 216.50 | 20.79 |
May | 373.50 | 23.43 | 6.33 | 23.41 | 4.17 | 23.38 |
June | 40.67 | 23.56 | 168.17 | 24.34 | 0.00 | 24.34 |
July | 16.33 | 23.61 | 320.17 | 24.42 | 0.00 | 24.42 |
August | 173.67 | 23.18 | 104.00 | 23.58 | 3.33 | 23.54 |
September | 476.67 | 22.02 | 85.83 | 21.80 | 85.83 | 21.64 |
October | 502.00 | 20.25 | 427.50 | 20.16 | 427.50 | 20.13 |
November | 489.00 | 19.72 | 489.00 | 19.72 | 489.00 | 19.72 |
December | 497.00 | 19.65 | 497.00 | 19.65 | 497.00 | 19.65 |
Annual Sum or Average | 4523.83 | 20.73 | 3759.17 | 20.67 | 3168.00 | 20.45 |
Minimum of Months | 16.33 | 19.65 | 6.33 | 19.65 | 0.00 | 19.65 |
Maximum of Months | 514.00 | 23.61 | 502.00 | 24.42 | 502.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 502.00 | 19.77 | 502.00 | 19.77 |
February | 454.00 | 19.90 | 445.83 | 19.89 | 445.83 | 19.89 |
March | 513.00 | 20.65 | 386.00 | 20.44 | 386.00 | 20.35 |
April | 413.00 | 21.97 | 154.50 | 21.58 | 143.83 | 21.31 |
May | 183.83 | 23.62 | 125.17 | 24.05 | 8.83 | 24.13 |
June | 34.83 | 24.06 | 296.67 | 24.41 | 5.33 | 24.45 |
July | 31.33 | 25.96 | 405.17 | 24.64 | 21.67 | 24.75 |
August | 94.17 | 23.44 | 250.33 | 24.07 | 4.17 | 24.06 |
September | 375.00 | 22.26 | 69.83 | 22.23 | 48.17 | 22.06 |
October | 501.00 | 20.49 | 358.67 | 20.29 | 358.67 | 20.21 |
November | 489.00 | 19.80 | 489.00 | 19.80 | 489.00 | 19.80 |
December | 497.00 | 19.73 | 497.00 | 19.73 | 497.00 | 19.73 |
Annual Sum or Average | 4088.17 | 20.77 | 3980.17 | 20.98 | 2910.50 | 20.72 |
Minimum of Months | 31.33 | 19.73 | 69.83 | 19.73 | 4.17 | 19.73 |
Maximum of Months | 513.00 | 25.96 | 502.00 | 24.64 | 502.00 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.80 | 498.17 | 19.80 | 498.17 | 19.79 |
February | 453.50 | 20.27 | 399.00 | 20.13 | 399.00 | 20.07 |
March | 472.50 | 20.97 | 322.33 | 20.65 | 322.33 | 20.51 |
April | 336.17 | 21.89 | 178.17 | 21.85 | 115.33 | 21.55 |
May | 243.67 | 23.35 | 123.00 | 23.77 | 14.50 | 23.82 |
June | 70.67 | 24.12 | 258.17 | 24.36 | 12.50 | 24.46 |
July | 51.33 | 24.95 | 360.50 | 24.56 | 20.67 | 24.68 |
August | 128.17 | 23.45 | 245.83 | 24.07 | 12.17 | 24.12 |
September | 334.67 | 22.19 | 113.67 | 22.43 | 42.83 | 22.26 |
October | 483.00 | 20.73 | 320.67 | 20.49 | 317.00 | 20.38 |
November | 489.00 | 19.89 | 476.17 | 19.86 | 476.17 | 19.85 |
December | 497.00 | 19.75 | 497.00 | 19.75 | 497.00 | 19.75 |
Annual Sum or Average | 4061.67 | 20.94 | 3792.67 | 21.11 | 2727.67 | 20.84 |
Minimum of Months | 51.33 | 19.75 | 113.67 | 19.75 | 12.17 | 19.75 |
Maximum of Months | 502.00 | 24.95 | 498.17 | 24.56 | 498.17 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 502.00 | 19.77 | 502.00 | 19.77 |
February | 454.00 | 19.88 | 448.50 | 19.87 | 448.50 | 19.87 |
March | 514.00 | 20.40 | 437.50 | 20.28 | 437.50 | 20.24 |
April | 407.83 | 21.63 | 188.50 | 21.31 | 166.67 | 21.05 |
May | 277.83 | 23.25 | 57.17 | 23.47 | 7.33 | 23.45 |
June | 57.50 | 23.84 | 226.33 | 24.40 | 6.33 | 24.45 |
July | 37.33 | 24.37 | 350.83 | 24.46 | 9.33 | 24.52 |
August | 146.67 | 23.21 | 190.00 | 23.83 | 6.83 | 23.84 |
September | 420.83 | 22.07 | 83.50 | 21.93 | 71.17 | 21.77 |
October | 502.00 | 20.34 | 405.67 | 20.21 | 405.67 | 20.16 |
November | 489.00 | 19.80 | 489.00 | 19.80 | 489.00 | 19.80 |
December | 497.00 | 19.73 | 497.00 | 19.73 | 497.00 | 19.73 |
Annual Sum or Average | 4306.00 | 20.76 | 3876.00 | 20.84 | 3047.33 | 20.60 |
Minimum of Months | 37.33 | 19.73 | 57.17 | 19.73 | 6.33 | 19.73 |
Maximum of Months | 514.00 | 24.37 | 502.00 | 24.46 | 502.00 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.67 | 502.00 | 19.67 | 502.00 | 19.67 |
February | 454.00 | 19.75 | 454.00 | 19.75 | 454.00 | 19.75 |
March | 514.00 | 20.25 | 510.33 | 20.25 | 510.33 | 20.25 |
April | 485.00 | 21.03 | 275.67 | 20.80 | 275.67 | 20.70 |
May | 507.67 | 23.21 | 0.00 | 23.21 | 0.00 | 23.21 |
June | 109.17 | 23.78 | 74.50 | 24.05 | 0.00 | 24.05 |
July | 11.83 | 23.68 | 246.00 | 24.42 | 0.00 | 24.42 |
August | 155.50 | 23.46 | 66.67 | 23.78 | 0.00 | 23.78 |
September | 481.00 | 22.60 | 27.17 | 22.50 | 27.17 | 22.41 |
October | 502.00 | 20.74 | 340.50 | 20.61 | 340.50 | 20.55 |
November | 489.00 | 19.95 | 489.00 | 19.95 | 489.00 | 19.95 |
December | 497.00 | 19.80 | 497.00 | 19.80 | 497.00 | 19.80 |
Annual Sum or Average | 4708.17 | 20.95 | 3482.83 | 20.76 | 3095.67 | 20.55 |
Minimum of Months | 11.83 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Maximum of Months | 514.00 | 23.78 | 510.33 | 24.42 | 510.33 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 502.00 | 19.84 | 502.00 | 19.84 |
February | 454.00 | 19.97 | 454.00 | 19.97 | 454.00 | 19.97 |
March | 514.00 | 20.63 | 431.83 | 20.52 | 431.83 | 20.47 |
April | 456.00 | 22.10 | 147.83 | 21.75 | 143.67 | 21.50 |
May | 209.00 | 23.68 | 80.83 | 24.03 | 1.83 | 24.05 |
June | 34.50 | 23.74 | 249.33 | 24.39 | 0.33 | 24.39 |
July | 18.00 | 25.86 | 411.67 | 24.61 | 11.67 | 24.67 |
August | 45.67 | 23.72 | 279.17 | 24.33 | 0.33 | 24.33 |
September | 317.67 | 22.86 | 41.17 | 23.06 | 9.83 | 23.00 |
October | 501.00 | 21.13 | 265.67 | 20.89 | 265.67 | 20.77 |
November | 489.00 | 19.99 | 489.00 | 19.99 | 489.00 | 19.99 |
December | 497.00 | 19.85 | 497.00 | 19.85 | 497.00 | 19.85 |
Annual Sum or Average | 4037.83 | 20.93 | 3849.50 | 21.11 | 2807.17 | 20.85 |
Minimum of Months | 18.00 | 19.84 | 41.17 | 19.84 | 0.33 | 19.84 |
Maximum of Months | 514.00 | 25.86 | 502.00 | 24.61 | 502.00 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.45 | 502.00 | 18.45 | 502.00 | 18.45 |
February | 454.00 | 19.21 | 438.83 | 19.17 | 438.83 | 19.16 |
March | 514.00 | 20.06 | 417.33 | 19.88 | 417.33 | 19.81 |
April | 403.17 | 21.69 | 134.67 | 21.44 | 118.17 | 21.18 |
May | 307.17 | 22.83 | 45.50 | 23.18 | 1.00 | 23.19 |
June | 108.17 | 22.93 | 176.00 | 23.93 | 1.00 | 23.94 |
July | 60.00 | 22.99 | 351.67 | 24.31 | 7.83 | 24.36 |
August | 126.50 | 22.84 | 247.33 | 23.98 | 6.33 | 24.03 |
September | 327.67 | 22.16 | 81.17 | 22.52 | 17.67 | 22.41 |
October | 491.17 | 20.74 | 272.67 | 20.43 | 271.83 | 20.29 |
November | 489.00 | 18.88 | 487.00 | 18.88 | 487.00 | 18.88 |
December | 497.00 | 18.38 | 497.00 | 18.38 | 497.00 | 18.38 |
Annual Sum or Average | 4279.83 | 20.24 | 3651.17 | 20.32 | 2766.00 | 20.00 |
Minimum of Months | 60.00 | 18.38 | 45.50 | 18.38 | 1.00 | 18.38 |
Maximum of Months | 514.00 | 22.99 | 502.00 | 24.31 | 502.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 502.00 | 19.84 | 502.00 | 19.84 |
February | 454.00 | 19.92 | 454.00 | 19.92 | 454.00 | 19.92 |
March | 514.00 | 20.39 | 486.00 | 20.35 | 486.00 | 20.34 |
April | 443.33 | 21.85 | 165.83 | 21.50 | 163.17 | 21.28 |
May | 375.67 | 23.42 | 11.67 | 23.49 | 0.00 | 23.49 |
June | 66.50 | 23.71 | 178.50 | 24.34 | 0.17 | 24.34 |
July | 12.67 | 23.60 | 339.17 | 24.44 | 0.17 | 24.44 |
August | 93.00 | 23.57 | 193.83 | 24.18 | 0.83 | 24.18 |
September | 399.17 | 22.79 | 22.33 | 22.77 | 13.50 | 22.71 |
October | 502.00 | 20.85 | 318.33 | 20.68 | 318.33 | 20.61 |
November | 489.00 | 19.99 | 489.00 | 19.99 | 489.00 | 19.99 |
December | 497.00 | 19.85 | 497.00 | 19.85 | 497.00 | 19.85 |
Annual Sum or Average | 4348.33 | 20.98 | 3657.67 | 20.97 | 2924.17 | 20.73 |
Minimum of Months | 12.67 | 19.84 | 11.67 | 19.84 | 0.00 | 19.84 |
Maximum of Months | 514.00 | 23.71 | 502.00 | 24.44 | 502.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.86 | 502.00 | 19.86 | 502.00 | 19.86 |
February | 454.00 | 19.98 | 450.50 | 19.97 | 450.50 | 19.97 |
March | 514.00 | 20.45 | 464.33 | 20.41 | 464.33 | 20.39 |
April | 485.00 | 21.90 | 153.83 | 21.51 | 153.83 | 21.27 |
May | 340.67 | 23.74 | 1.17 | 23.74 | 0.00 | 23.74 |
June | 12.67 | 23.70 | 188.83 | 24.53 | 0.00 | 24.53 |
July | 2.50 | 23.82 | 350.33 | 24.50 | 0.00 | 24.50 |
August | 106.83 | 23.48 | 126.50 | 23.98 | 0.00 | 23.98 |
September | 457.83 | 22.63 | 22.33 | 22.54 | 22.33 | 22.46 |
October | 502.00 | 20.66 | 336.33 | 20.50 | 336.33 | 20.43 |
November | 489.00 | 19.93 | 489.00 | 19.93 | 489.00 | 19.93 |
December | 497.00 | 19.85 | 497.00 | 19.85 | 497.00 | 19.85 |
Annual Sum or Average | 4363.50 | 20.96 | 3582.17 | 20.92 | 2915.33 | 20.69 |
Minimum of Months | 2.50 | 19.85 | 1.17 | 19.85 | 0.00 | 19.85 |
Maximum of Months | 514.00 | 23.82 | 502.00 | 24.53 | 502.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.69 | 427.00 | 19.69 | 427.00 | 19.69 |
February | 385.00 | 19.92 | 373.67 | 19.90 | 373.67 | 19.89 |
March | 431.50 | 20.87 | 284.33 | 20.63 | 284.33 | 20.53 |
April | 341.50 | 22.26 | 94.50 | 22.00 | 80.33 | 21.73 |
May | 150.17 | 23.96 | 121.00 | 24.39 | 9.33 | 24.48 |
June | 16.00 | 25.02 | 243.67 | 24.62 | 6.50 | 24.68 |
July | 23.33 | 26.76 | 356.00 | 24.81 | 21.67 | 24.93 |
August | 48.67 | 23.73 | 227.33 | 24.36 | 2.83 | 24.39 |
September | 297.50 | 22.74 | 47.83 | 22.94 | 14.67 | 22.87 |
October | 425.67 | 20.85 | 251.00 | 20.61 | 251.00 | 20.50 |
November | 417.00 | 19.76 | 417.00 | 19.76 | 417.00 | 19.76 |
December | 422.00 | 19.65 | 422.00 | 19.65 | 422.00 | 19.65 |
Annual Sum or Average | 3385.33 | 20.86 | 3265.33 | 21.10 | 2310.33 | 20.82 |
Minimum of Months | 16.00 | 19.65 | 47.83 | 19.65 | 2.83 | 19.65 |
Maximum of Months | 431.50 | 26.76 | 427.00 | 24.81 | 427.00 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.95 | 491.17 | 19.93 | 491.17 | 19.92 |
February | 449.83 | 20.58 | 363.67 | 20.40 | 363.67 | 20.33 |
March | 456.00 | 21.24 | 260.33 | 20.95 | 256.33 | 20.80 |
April | 316.33 | 22.36 | 145.00 | 22.42 | 74.67 | 22.15 |
May | 210.17 | 23.74 | 122.33 | 24.12 | 9.83 | 24.21 |
June | 35.83 | 24.79 | 278.00 | 24.50 | 11.83 | 24.59 |
July | 24.50 | 26.39 | 391.33 | 24.64 | 20.00 | 24.75 |
August | 82.50 | 23.94 | 268.67 | 24.35 | 10.00 | 24.42 |
September | 303.17 | 22.81 | 99.00 | 23.14 | 14.00 | 23.07 |
October | 475.50 | 21.24 | 233.83 | 20.96 | 229.67 | 20.80 |
November | 489.00 | 20.14 | 463.67 | 20.09 | 463.67 | 20.07 |
December | 497.00 | 19.88 | 497.00 | 19.88 | 497.00 | 19.88 |
Annual Sum or Average | 3841.83 | 21.16 | 3614.00 | 21.37 | 2441.83 | 21.09 |
Minimum of Months | 24.50 | 19.88 | 99.00 | 19.88 | 9.83 | 19.88 |
Maximum of Months | 502.00 | 26.39 | 497.00 | 24.64 | 497.00 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 502.00 | 19.89 | 502.00 | 19.89 |
February | 454.00 | 20.03 | 442.17 | 20.01 | 442.17 | 20.00 |
March | 514.00 | 20.68 | 406.83 | 20.54 | 406.83 | 20.48 |
April | 396.83 | 22.11 | 136.00 | 21.84 | 112.33 | 21.58 |
May | 242.67 | 23.64 | 52.67 | 23.88 | 2.50 | 23.91 |
June | 29.67 | 24.33 | 240.83 | 24.55 | 5.83 | 24.60 |
July | 12.33 | 25.85 | 383.00 | 24.54 | 8.33 | 24.59 |
August | 96.83 | 23.58 | 211.33 | 24.16 | 3.17 | 24.19 |
September | 387.17 | 22.65 | 33.83 | 22.64 | 18.33 | 22.57 |
October | 502.00 | 20.76 | 316.83 | 20.56 | 316.83 | 20.48 |
November | 489.00 | 19.95 | 488.00 | 19.95 | 488.00 | 19.95 |
December | 497.00 | 19.86 | 497.00 | 19.86 | 497.00 | 19.86 |
Annual Sum or Average | 4123.50 | 20.94 | 3710.50 | 21.05 | 2803.33 | 20.79 |
Minimum of Months | 12.33 | 19.86 | 33.83 | 19.86 | 2.50 | 19.86 |
Maximum of Months | 514.00 | 25.85 | 502.00 | 24.55 | 502.00 | 24.60 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97719 | 15.32423 | -0.6559 | 15.33555 |
February | 454.00000 | 21.46031 | 17.28437 | -0.5132 | 11.53987 |
March | 514.00000 | 22.28047 | 18.61928 | -0.3001 | 7.67822 |
April | 485.00000 | 23.62562 | 17.66309 | 0.05273 | 5.90503 |
May | 508.00000 | 24.26377 | 21.65433 | -0.5921 | 12.57862 |
June | 496.00000 | 24.35061 | 33.22086 | -0.4496 | 9.64590 |
July | 497.00000 | 24.41702 | 41.43070 | -0.3694 | 8.34555 |
August | 514.00000 | 24.33836 | 36.75842 | -0.4368 | 9.43096 |
September | 485.00000 | 24.18172 | 28.22852 | -0.6089 | 13.38893 |
October | 502.00000 | 23.05992 | 23.71364 | -0.0683 | 6.09689 |
November | 489.00000 | 21.55168 | 16.07901 | -0.5015 | 10.82020 |
December | 497.00000 | 21.16018 | 13.13042 | -0.6180 | 13.41472 |
Annual Sum or Average | 5943.00000 | 22.98381 | 23.66198 | -0.4215 | 10.33655 |
Minimum of Months | 454.00000 | 20.97719 | 13.13042 | -0.6559 | 5.90503 |
Maximum of Months | 514.00000 | 24.41702 | 41.43070 | 0.05273 | 15.33555 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46436 | 17.35008 | -0.7771 | 19.21658 |
February | 454.00000 | 20.79361 | 19.68648 | -0.6666 | 15.56368 |
March | 514.00000 | 21.39396 | 20.59025 | -0.4924 | 10.82165 |
April | 485.00000 | 22.92513 | 18.64474 | -0.1021 | 6.83626 |
May | 508.00000 | 24.06584 | 22.11881 | -0.6631 | 14.56873 |
June | 496.00000 | 24.25937 | 33.82348 | -0.4853 | 10.22151 |
July | 497.00000 | 24.32153 | 41.99732 | -0.4085 | 8.84401 |
August | 514.00000 | 24.20798 | 37.53446 | -0.4943 | 10.50032 |
September | 485.00000 | 23.61161 | 30.21907 | -0.8059 | 19.94337 |
October | 502.00000 | 21.78066 | 26.56798 | -0.3566 | 8.89353 |
November | 489.00000 | 20.72015 | 18.60670 | -0.6975 | 16.00865 |
December | 497.00000 | 20.55219 | 14.49590 | -0.7723 | 18.35204 |
Annual Sum or Average | 5943.00000 | 22.43808 | 25.19741 | -0.5594 | 13.28289 |
Minimum of Months | 454.00000 | 20.46436 | 14.49590 | -0.8059 | 6.83626 |
Maximum of Months | 514.00000 | 24.32153 | 41.99732 | -0.1021 | 19.94337 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10498 | 17.52763 | -0.9047 | 24.33671 |
February | 454.00000 | 20.28146 | 20.08044 | -0.8241 | 21.42139 |
March | 514.00000 | 20.82662 | 20.70009 | -0.6590 | 15.40046 |
April | 485.00000 | 22.28958 | 19.28693 | -0.2633 | 9.02937 |
May | 508.00000 | 23.83993 | 22.61646 | -0.7471 | 17.50199 |
June | 496.00000 | 24.19793 | 33.77895 | -0.5092 | 10.68547 |
July | 497.00000 | 24.25596 | 42.03016 | -0.4343 | 9.23251 |
August | 514.00000 | 24.04300 | 37.94694 | -0.5617 | 12.23664 |
September | 485.00000 | 22.91846 | 32.06636 | -1.0534 | 30.26575 |
October | 502.00000 | 20.94659 | 27.46416 | -0.5814 | 13.76130 |
November | 489.00000 | 20.17310 | 18.78940 | -0.8710 | 22.83334 |
December | 497.00000 | 20.12279 | 14.68611 | -0.9190 | 24.55666 |
Annual Sum or Average | 5943.00000 | 22.01553 | 25.63905 | -0.6927 | 17.54397 |
Minimum of Months | 454.00000 | 20.10498 | 14.68611 | -1.0534 | 9.02937 |
Maximum of Months | 514.00000 | 24.25596 | 42.03016 | -0.2633 | 30.26575 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.66972 | 17.53695 | -1.1037 | 32.60919 |
February | 454.00000 | 19.78812 | 20.51114 | -1.0264 | 29.58628 |
March | 514.00000 | 20.17444 | 21.27576 | -0.8717 | 23.11155 |
April | 485.00000 | 21.40026 | 19.93360 | -0.4775 | 13.58426 |
May | 508.00000 | 23.61004 | 22.97579 | -0.8072 | 20.08384 |
June | 496.00000 | 24.18492 | 33.91087 | -0.4630 | 10.01601 |
July | 497.00000 | 24.29247 | 41.89584 | -0.3841 | 8.62759 |
August | 514.00000 | 23.81065 | 38.96823 | -0.6260 | 14.66568 |
September | 485.00000 | 22.05342 | 34.18251 | -1.3434 | 43.79402 |
October | 502.00000 | 20.25277 | 27.98531 | -0.7929 | 20.48461 |
November | 489.00000 | 19.72396 | 19.16498 | -1.0723 | 31.27054 |
December | 497.00000 | 19.64611 | 14.51644 | -1.1319 | 33.69618 |
Annual Sum or Average | 5943.00000 | 21.56830 | 26.12755 | -0.8394 | 23.35991 |
Minimum of Months | 454.00000 | 19.64611 | 14.51644 | -1.3434 | 8.62759 |
Maximum of Months | 514.00000 | 24.29247 | 41.89584 | -0.3841 | 43.79402 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76699 | 18.19427 | -1.0815 | 31.62410 |
February | 454.00000 | 19.90026 | 21.48695 | -0.9776 | 27.62036 |
March | 514.00000 | 20.65622 | 21.95319 | -0.7064 | 18.46142 |
April | 485.00000 | 22.30646 | 19.06753 | -0.2252 | 10.83669 |
May | 508.00000 | 24.01959 | 21.64970 | -0.5510 | 13.87352 |
June | 496.00000 | 24.27387 | 33.43277 | -0.3378 | 8.65681 |
July | 497.00000 | 24.43468 | 41.21286 | -0.2347 | 7.75746 |
August | 514.00000 | 24.07544 | 37.84027 | -0.4521 | 10.83968 |
September | 485.00000 | 22.74317 | 33.32777 | -1.0838 | 33.45997 |
October | 502.00000 | 20.49732 | 28.65220 | -0.7121 | 18.46296 |
November | 489.00000 | 19.79562 | 19.89471 | -1.0529 | 30.44891 |
December | 497.00000 | 19.73309 | 15.00575 | -1.1162 | 32.97257 |
Annual Sum or Average | 5943.00000 | 21.86804 | 26.02514 | -0.7081 | 20.30992 |
Minimum of Months | 454.00000 | 19.73309 | 15.00575 | -1.1162 | 7.75746 |
Maximum of Months | 514.00000 | 24.43468 | 41.21286 | -0.2252 | 33.45997 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.80253 | 17.74117 | -1.0549 | 30.60330 |
February | 454.00000 | 20.27597 | 20.38309 | -0.8567 | 23.88345 |
March | 514.00000 | 21.21423 | 19.96099 | -0.5526 | 16.41578 |
April | 485.00000 | 22.62980 | 17.34627 | -0.1166 | 11.09558 |
May | 508.00000 | 23.81613 | 21.67781 | -0.6402 | 17.35676 |
June | 496.00000 | 24.20266 | 33.40151 | -0.3876 | 9.65288 |
July | 497.00000 | 24.34037 | 41.36552 | -0.2902 | 8.47679 |
August | 514.00000 | 24.03588 | 37.53794 | -0.4507 | 11.93686 |
September | 485.00000 | 22.85708 | 31.79514 | -1.0145 | 31.50663 |
October | 502.00000 | 20.85641 | 27.11270 | -0.6115 | 16.61091 |
November | 489.00000 | 19.88760 | 19.40674 | -1.0018 | 28.62339 |
December | 497.00000 | 19.74927 | 14.64528 | -1.1048 | 32.49633 |
Annual Sum or Average | 5943.00000 | 21.98830 | 25.25077 | -0.6714 | 19.81247 |
Minimum of Months | 454.00000 | 19.74927 | 14.64528 | -1.1048 | 8.47679 |
Maximum of Months | 514.00000 | 24.34037 | 41.36552 | -0.1166 | 32.49633 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76507 | 18.12274 | -1.0850 | 31.75631 |
February | 454.00000 | 19.87874 | 21.32851 | -0.9972 | 28.38712 |
March | 514.00000 | 20.40229 | 22.08904 | -0.7973 | 21.07296 |
April | 485.00000 | 22.03538 | 19.42294 | -0.2908 | 12.34522 |
May | 508.00000 | 23.69944 | 22.92944 | -0.7297 | 18.99649 |
June | 496.00000 | 24.20981 | 34.02749 | -0.4047 | 9.73394 |
July | 497.00000 | 24.30902 | 42.07683 | -0.3383 | 8.52946 |
August | 514.00000 | 23.90782 | 38.87738 | -0.5487 | 13.30878 |
September | 485.00000 | 22.35486 | 34.09893 | -1.2244 | 39.22442 |
October | 502.00000 | 20.33931 | 28.84166 | -0.7632 | 19.77295 |
November | 489.00000 | 19.79755 | 19.84263 | -1.0526 | 30.43770 |
December | 497.00000 | 19.73330 | 14.99386 | -1.1167 | 32.99152 |
Annual Sum or Average | 5943.00000 | 21.71957 | 26.44238 | -0.7768 | 22.11629 |
Minimum of Months | 454.00000 | 19.73330 | 14.99386 | -1.2244 | 8.52946 |
Maximum of Months | 514.00000 | 24.30902 | 42.07683 | -0.2908 | 39.22442 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.66674 | 16.03745 | -1.1053 | 32.39419 |
February | 454.00000 | 19.75045 | 18.71331 | -1.0558 | 30.44085 |
March | 514.00000 | 20.25317 | 20.46635 | -0.8877 | 23.02812 |
April | 485.00000 | 21.02693 | 20.80194 | -0.5889 | 14.08132 |
May | 508.00000 | 23.21241 | 24.88282 | -0.9854 | 26.44340 |
June | 496.00000 | 24.08928 | 34.88220 | -0.5527 | 11.71752 |
July | 497.00000 | 24.22572 | 42.69473 | -0.4418 | 9.36839 |
August | 514.00000 | 23.92779 | 39.16722 | -0.6011 | 13.34939 |
September | 485.00000 | 22.60934 | 32.78460 | -1.1474 | 34.23034 |
October | 502.00000 | 20.73720 | 26.70281 | -0.6455 | 15.12193 |
November | 489.00000 | 19.95066 | 17.63474 | -0.9896 | 27.24301 |
December | 497.00000 | 19.79607 | 13.72690 | -1.0760 | 30.86579 |
Annual Sum or Average | 5943.00000 | 21.62157 | 25.77815 | -0.8377 | 22.27255 |
Minimum of Months | 454.00000 | 19.66674 | 13.72690 | -1.1474 | 9.36839 |
Maximum of Months | 514.00000 | 24.22572 | 42.69473 | -0.4418 | 34.23034 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84049 | 16.55929 | -1.0721 | 30.90624 |
February | 454.00000 | 19.97202 | 19.57973 | -0.9897 | 27.55989 |
March | 514.00000 | 20.63462 | 21.37043 | -0.7380 | 18.15493 |
April | 485.00000 | 22.24460 | 19.89256 | -0.2605 | 9.83727 |
May | 508.00000 | 24.04788 | 22.22352 | -0.5895 | 13.93232 |
June | 496.00000 | 24.26404 | 33.86926 | -0.3911 | 9.03637 |
July | 497.00000 | 24.45877 | 41.54052 | -0.2555 | 7.52496 |
August | 514.00000 | 24.22623 | 37.64966 | -0.4071 | 9.34782 |
September | 485.00000 | 23.38554 | 31.39660 | -0.8546 | 23.43455 |
October | 502.00000 | 21.13610 | 27.13525 | -0.5314 | 12.96638 |
November | 489.00000 | 19.98729 | 18.58502 | -0.9788 | 26.81559 |
December | 497.00000 | 19.84896 | 14.33711 | -1.0700 | 30.63135 |
Annual Sum or Average | 5943.00000 | 22.02131 | 25.40525 | -0.6755 | 18.24763 |
Minimum of Months | 454.00000 | 19.84049 | 14.33711 | -1.0721 | 7.52496 |
Maximum of Months | 514.00000 | 24.45877 | 41.54052 | -0.2555 | 30.90624 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.45125 | 13.75625 | -1.3279 | 42.10926 |
February | 454.00000 | 19.20639 | 15.78045 | -1.0979 | 32.23555 |
March | 514.00000 | 20.06321 | 16.44103 | -0.8048 | 21.35193 |
April | 485.00000 | 22.16666 | 16.52860 | -0.2134 | 10.16701 |
May | 508.00000 | 23.45235 | 22.21124 | -0.7828 | 21.02125 |
June | 496.00000 | 23.97887 | 34.14882 | -0.4992 | 11.83731 |
July | 497.00000 | 24.19832 | 41.94506 | -0.3571 | 9.48819 |
August | 514.00000 | 23.95079 | 37.56468 | -0.4623 | 11.95167 |
September | 485.00000 | 22.92266 | 29.34453 | -0.9367 | 27.93295 |
October | 502.00000 | 20.80746 | 22.77611 | -0.5714 | 14.97924 |
November | 489.00000 | 18.88446 | 14.35734 | -1.1757 | 35.50268 |
December | 497.00000 | 18.38318 | 11.60770 | -1.3547 | 43.14685 |
Annual Sum or Average | 5943.00000 | 21.39053 | 23.11435 | -0.7962 | 23.38220 |
Minimum of Months | 454.00000 | 18.38318 | 11.60770 | -1.3547 | 9.48819 |
Maximum of Months | 514.00000 | 24.19832 | 41.94506 | -0.2134 | 43.14685 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83795 | 16.49595 | -1.0758 | 31.05491 |
February | 454.00000 | 19.91811 | 19.44977 | -1.0158 | 28.68890 |
March | 514.00000 | 20.38934 | 21.42340 | -0.8308 | 21.07061 |
April | 485.00000 | 22.05231 | 20.15275 | -0.3066 | 10.45398 |
May | 508.00000 | 23.64343 | 24.03772 | -0.7985 | 20.05852 |
June | 496.00000 | 24.19637 | 34.55130 | -0.4612 | 10.24763 |
July | 497.00000 | 24.31364 | 42.55982 | -0.3696 | 8.50399 |
August | 514.00000 | 24.11310 | 38.59885 | -0.4895 | 10.89698 |
September | 485.00000 | 23.04148 | 32.36427 | -0.9852 | 28.05440 |
October | 502.00000 | 20.85037 | 27.53500 | -0.6105 | 14.44256 |
November | 489.00000 | 19.98783 | 18.58354 | -0.9786 | 26.81113 |
December | 497.00000 | 19.84834 | 14.32562 | -1.0707 | 30.65901 |
Annual Sum or Average | 5943.00000 | 21.86571 | 25.90677 | -0.7474 | 19.99320 |
Minimum of Months | 454.00000 | 19.83795 | 14.32562 | -1.0758 | 8.50399 |
Maximum of Months | 514.00000 | 24.31364 | 42.55982 | -0.3066 | 31.05491 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.85663 | 17.99672 | -1.0130 | 28.66718 |
February | 454.00000 | 19.97844 | 20.62725 | -0.9347 | 25.66666 |
March | 514.00000 | 20.45427 | 21.29036 | -0.7664 | 18.78718 |
April | 485.00000 | 21.89865 | 19.53191 | -0.3417 | 10.53712 |
May | 508.00000 | 23.87701 | 22.46135 | -0.7112 | 16.30563 |
June | 496.00000 | 24.24877 | 33.84863 | -0.4386 | 9.44374 |
July | 497.00000 | 24.36361 | 41.82536 | -0.3566 | 8.16977 |
August | 514.00000 | 24.02434 | 38.43456 | -0.5461 | 12.02311 |
September | 485.00000 | 22.70896 | 32.65200 | -1.1050 | 32.70018 |
October | 502.00000 | 20.66133 | 27.44962 | -0.6536 | 15.83000 |
November | 489.00000 | 19.93014 | 19.64133 | -0.9684 | 26.73571 |
December | 497.00000 | 19.84951 | 15.16231 | -1.0317 | 29.21473 |
Annual Sum or Average | 5943.00000 | 21.83806 | 25.96557 | -0.7369 | 19.42084 |
Minimum of Months | 454.00000 | 19.84951 | 15.16231 | -1.1050 | 8.16977 |
Maximum of Months | 514.00000 | 24.36361 | 41.82536 | -0.3417 | 32.70018 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.68966 | 18.16508 | -1.0491 | 30.32435 |
February | 385.00000 | 19.92159 | 21.18177 | -0.9301 | 25.55316 |
March | 433.00000 | 20.87773 | 21.50084 | -0.6279 | 15.63984 |
April | 410.00000 | 22.62605 | 18.09623 | -0.1407 | 9.17952 |
May | 430.00000 | 24.22827 | 21.11348 | -0.4909 | 12.16110 |
June | 418.00000 | 24.38855 | 33.19382 | -0.3172 | 8.36436 |
July | 422.00000 | 24.57872 | 40.96628 | -0.2051 | 7.57306 |
August | 433.00000 | 24.24313 | 37.18772 | -0.4042 | 9.71695 |
September | 410.00000 | 23.21659 | 31.43429 | -0.9099 | 26.08436 |
October | 427.00000 | 20.86307 | 27.63932 | -0.5923 | 14.86036 |
November | 417.00000 | 19.76126 | 20.15064 | -1.0017 | 28.24648 |
December | 422.00000 | 19.64995 | 15.31578 | -1.0760 | 31.26141 |
Annual Sum or Average | 5034.00000 | 22.01751 | 25.53452 | -0.6433 | 18.16886 |
Minimum of Months | 385.00000 | 19.64995 | 15.31578 | -1.0760 | 7.57306 |
Maximum of Months | 433.00000 | 24.57872 | 40.96628 | -0.1407 | 31.26141 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.94955 | 18.11074 | -0.9715 | 27.11388 |
February | 454.00000 | 20.61401 | 20.12476 | -0.7392 | 19.64176 |
March | 514.00000 | 21.58133 | 19.61166 | -0.4312 | 13.17939 |
April | 485.00000 | 23.04650 | 16.82625 | 0.00127 | 9.32923 |
May | 508.00000 | 24.05794 | 21.26716 | -0.5523 | 13.85742 |
June | 496.00000 | 24.28492 | 33.29994 | -0.3585 | 8.82506 |
July | 497.00000 | 24.42365 | 41.25119 | -0.2601 | 7.80353 |
August | 514.00000 | 24.20107 | 37.12881 | -0.3851 | 9.92848 |
September | 485.00000 | 23.37957 | 30.35163 | -0.8150 | 22.85963 |
October | 502.00000 | 21.38905 | 26.21482 | -0.4505 | 12.54827 |
November | 489.00000 | 20.14450 | 19.55326 | -0.8898 | 23.94587 |
December | 497.00000 | 19.88446 | 15.27004 | -1.0174 | 28.63888 |
Annual Sum or Average | 5943.00000 | 22.26116 | 24.97174 | -0.5708 | 16.41511 |
Minimum of Months | 454.00000 | 19.88446 | 15.27004 | -1.0174 | 7.80353 |
Maximum of Months | 514.00000 | 24.42365 | 41.25119 | 0.00127 | 28.63888 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88603 | 18.74274 | -1.0066 | 28.40522 |
February | 454.00000 | 20.02506 | 21.53061 | -0.9140 | 24.91194 |
March | 514.00000 | 20.68099 | 22.01566 | -0.6928 | 17.18063 |
April | 485.00000 | 22.49819 | 18.88157 | -0.1631 | 9.77620 |
May | 508.00000 | 23.96114 | 22.38475 | -0.6356 | 15.14464 |
June | 496.00000 | 24.29023 | 33.89431 | -0.3759 | 8.93601 |
July | 497.00000 | 24.39199 | 41.94072 | -0.3078 | 7.88506 |
August | 514.00000 | 24.10118 | 38.31831 | -0.4749 | 10.90743 |
September | 485.00000 | 22.95743 | 32.49270 | -1.0020 | 29.06415 |
October | 502.00000 | 20.76084 | 28.23228 | -0.6227 | 15.27064 |
November | 489.00000 | 19.94760 | 20.57875 | -0.9588 | 26.39449 |
December | 497.00000 | 19.85683 | 15.87884 | -1.0314 | 29.23360 |
Annual Sum or Average | 5943.00000 | 21.96304 | 26.29428 | -0.6801 | 18.50761 |
Minimum of Months | 454.00000 | 19.85683 | 15.87884 | -1.0314 | 7.88506 |
Maximum of Months | 514.00000 | 24.39199 | 41.94072 | -0.1631 | 29.23360 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4226504.06 | 1206662.00 | 0.87 | 4225113.22 | 1390.84 | 0.00 | 0.32 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 6799.50 | 20-JAN-07:01 | 6799.50 | 20-JAN-07:01 | 2.04 | 06-JAN-18:40 | 1867.26 | 20-JAN-07:01 | 0.00 |
February | 6740761.87 | 1943585.82 | 2.74 | 6602952.19 | 137809.68 | 0.00 | 0.33 | 08-FEB-07:01 | 0.00 | 01-FEB-00:10 | 6980.33 | 08-FEB-07:01 | 6980.33 | 08-FEB-07:01 | 90.45 | 09-FEB-18:12 | 1913.21 | 08-FEB-07:01 | 0.00 |
March | 11015751.40 | 3216822.74 | 4.14 | 10851137.58 | 164613.83 | 0.00 | 0.32 | 07-MAR-07:01 | 0.00 | 01-MAR-00:10 | 6900.42 | 07-MAR-07:01 | 6900.42 | 07-MAR-07:01 | 145.86 | 22-MAR-16:04 | 1892.93 | 07-MAR-07:01 | 0.00 |
April | 0.287867E+09 | 77933782.85 | 33.73 | 0.287728E+09 | 138164.24 | 0.00 | 0.64 | 28-APR-15:20 | 0.00 | 01-APR-00:10 | 14914.86 | 28-APR-15:20 | 14914.86 | 28-APR-15:20 | 53.61 | 18-APR-16:05 | 3768.23 | 28-APR-15:20 | 0.00 |
May | 0.433342E+10 | 0.114070E+10 | 186.77 | 0.431629E+10 | 17125279.77 | 0.00 | 1.00 | 31-MAY-15:00 | 0.00 | 01-MAY-00:10 | 30692.92 | 31-MAY-16:00 | 30692.92 | 31-MAY-16:00 | 582.01 | 16-MAY-17:02 | 7007.08 | 31-MAY-16:00 | 0.00 |
June | 0.173779E+11 | 0.426656E+10 | 312.39 | 0.166127E+11 | 0.765246E+09 | 0.00 | 1.00 | 12-JUN-13:00 | 0.00 | 01-JUN-00:10 | 54429.70 | 30-JUN-12:20 | 48449.74 | 20-JUN-15:50 | 13592.35 | 30-JUN-06:02 | 13150.48 | 30-JUN-14:30 | 0.00 |
July | 0.249860E+11 | 0.598924E+10 | 332.14 | 0.229914E+11 | 0.199461E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 56040.61 | 11-JUL-15:50 | 53620.99 | 12-JUL-16:00 | 27764.23 | 03-JUL-15:00 | 13504.44 | 11-JUL-16:00 | 0.00 |
August | 0.142107E+11 | 0.347055E+10 | 267.04 | 0.132008E+11 | 0.100997E+10 | 0.00 | 1.00 | 01-AUG-14:20 | 0.00 | 01-AUG-00:10 | 52118.68 | 11-AUG-15:50 | 52118.68 | 11-AUG-15:50 | 6801.24 | 03-AUG-06:02 | 12345.83 | 11-AUG-15:50 | 0.00 |
September | 0.231676E+10 | 0.618879E+09 | 119.79 | 0.218700E+10 | 0.129760E+09 | 0.00 | 0.89 | 08-SEP-16:00 | 0.00 | 01-SEP-00:10 | 22251.60 | 08-SEP-16:00 | 22251.60 | 08-SEP-16:00 | 1570.04 | 05-SEP-16:04 | 5242.71 | 08-SEP-16:00 | 0.00 |
October | 15829279.10 | 4629643.39 | 6.98 | 14928111.38 | 901167.72 | 0.00 | 0.19 | 31-OCT-06:01 | 0.00 | 01-OCT-00:10 | 3864.87 | 31-OCT-06:01 | 3864.87 | 31-OCT-06:01 | 338.23 | 02-OCT-16:07 | 1095.81 | 31-OCT-06:01 | 0.00 |
November | 3087713.49 | 891741.31 | 0.84 | 3083737.81 | 3975.68 | 0.00 | 0.24 | 16-NOV-07:01 | 0.00 | 01-NOV-00:10 | 4991.94 | 16-NOV-07:01 | 4991.94 | 16-NOV-07:01 | 5.96 | 02-NOV-17:18 | 1397.95 | 16-NOV-07:01 | 0.00 |
December | 2633150.16 | 758016.25 | 0.58 | 2633150.16 | -0.0 | 0.00 | 0.25 | 21-DEC-07:01 | 0.00 | 01-DEC-00:10 | 5277.07 | 21-DEC-07:01 | 5277.07 | 21-DEC-07:01 | 0.00 | 23-DEC-07:15 | 1473.20 | 21-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.635563E+11 | 0.155765E+11 | 1268.01 | 0.596382E+11 | 0.391806E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2633150.16 | 758016.25 | 0.58 | 2633150.16 | -0.0 | 0.00 | 0.19 | 0.00 | 3864.87 | 3864.87 | 0.00 | 1095.81 | 0.00 | ||||||
Maximum of Months | 0.249860E+11 | 0.598924E+10 | 332.14 | 0.229914E+11 | 0.199461E+10 | 0.00 | 1.00 | 0.00 | 56040.61 | 53620.99 | 27764.23 | 13504.44 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3698763.05 | 1047298.63 | 0.41 | 3698763.05 | -0.0 | 0.00 | 0.29 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 6039.65 | 20-JAN-07:01 | 6039.65 | 20-JAN-07:01 | 0.00 | 20-JAN-07:01 | 1668.34 | 20-JAN-07:01 | 0.00 |
February | 5255390.69 | 1470897.79 | 0.72 | 5222723.75 | 32666.93 | 0.00 | 0.37 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 | 7825.63 | 09-FEB-07:02 | 7825.63 | 09-FEB-07:02 | 43.49 | 08-FEB-13:01 | 2119.43 | 09-FEB-07:02 | 0.00 |
March | 10460031.97 | 2969005.54 | 4.15 | 10332968.11 | 127063.86 | 0.00 | 0.43 | 21-MAR-06:01 | 0.00 | 01-MAR-00:10 | 9061.45 | 21-MAR-06:01 | 9061.45 | 21-MAR-06:01 | 77.58 | 22-MAR-06:03 | 2421.39 | 21-MAR-06:01 | 0.00 |
April | 98119711.25 | 28482402.53 | 40.09 | 97965727.88 | 153983.37 | 0.00 | 0.30 | 05-APR-06:01 | 0.00 | 01-APR-00:10 | 6246.40 | 05-APR-06:01 | 6246.40 | 05-APR-06:01 | 50.39 | 29-APR-09:10 | 1721.47 | 05-APR-06:01 | 0.00 |
May | 0.387394E+10 | 0.999477E+09 | 156.91 | 0.386398E+10 | 9962017.77 | 0.00 | 1.00 | 12-MAY-12:50 | 0.00 | 01-MAY-00:10 | 34614.16 | 31-MAY-16:00 | 34614.16 | 31-MAY-16:00 | 345.07 | 31-MAY-20:30 | 7899.77 | 31-MAY-16:00 | 0.00 |
June | 0.188420E+11 | 0.458649E+10 | 323.06 | 0.180545E+11 | 0.787434E+09 | 0.00 | 1.00 | 04-JUN-15:22 | 0.00 | 01-JUN-00:10 | 61278.38 | 30-JUN-12:05 | 53284.02 | 29-JUN-14:05 | 15818.14 | 30-JUN-06:02 | 14669.40 | 30-JUN-12:05 | 0.00 |
July | 0.254273E+11 | 0.608594E+10 | 344.60 | 0.233951E+11 | 0.203214E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 56746.66 | 11-JUL-15:30 | 53875.32 | 21-JUL-14:05 | 29670.00 | 03-JUL-15:00 | 13567.86 | 11-JUL-16:00 | 0.00 |
August | 0.137084E+11 | 0.334681E+10 | 268.23 | 0.126956E+11 | 0.101280E+10 | 0.00 | 1.00 | 01-AUG-12:50 | 0.00 | 01-AUG-00:10 | 51151.94 | 11-AUG-15:20 | 51151.94 | 11-AUG-15:20 | 6745.71 | 04-AUG-10:40 | 11986.07 | 11-AUG-15:30 | 0.00 |
September | 0.442595E+09 | 0.122647E+09 | 57.74 | 0.423093E+09 | 19502130.28 | 0.00 | 0.67 | 08-SEP-13:00 | 0.00 | 01-SEP-00:10 | 15086.74 | 08-SEP-13:00 | 15086.74 | 08-SEP-13:00 | 502.97 | 02-SEP-17:55 | 3785.24 | 08-SEP-13:00 | 0.00 |
October | 21235529.73 | 6076593.11 | 5.38 | 20342177.20 | 893352.53 | 0.00 | 0.38 | 11-OCT-06:01 | 0.00 | 01-OCT-00:10 | 7973.93 | 11-OCT-06:01 | 7973.93 | 11-OCT-06:01 | 159.82 | 03-OCT-13:10 | 2156.10 | 11-OCT-06:01 | 0.00 |
November | 2821430.24 | 798255.87 | 0.25 | 2821430.24 | 0.00 | 0.00 | 0.28 | 02-NOV-06:01 | 0.00 | 01-NOV-00:10 | 5626.79 | 02-NOV-06:01 | 5626.79 | 02-NOV-06:01 | 0.00 | 04-NOV-06:03 | 1561.49 | 02-NOV-06:01 | 0.00 |
December | 2274431.32 | 652845.16 | 0.77 | 2271725.16 | 2706.16 | 0.00 | 0.24 | 23-DEC-07:03 | 0.00 | 01-DEC-00:10 | 4944.24 | 23-DEC-07:03 | 4944.24 | 23-DEC-07:03 | 5.41 | 23-DEC-14:10 | 1382.65 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.624381E+11 | 0.151829E+11 | 1202.31 | 0.585751E+11 | 0.386305E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2274431.32 | 652845.16 | 0.25 | 2271725.16 | -0.0 | 0.00 | 0.24 | 0.00 | 4944.24 | 4944.24 | 0.00 | 1382.65 | 0.00 | ||||||
Maximum of Months | 0.254273E+11 | 0.608594E+10 | 344.60 | 0.233951E+11 | 0.203214E+10 | 0.00 | 1.00 | 0.00 | 61278.38 | 53875.32 | 29670.00 | 14669.40 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 121751.61 | 35723.12 | 0.05 | 121751.61 | -0.0 | 0.00 | 0.05 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 1094.31 | 19-JAN-07:01 | 1094.31 | 19-JAN-07:01 | 0.00 | 19-JAN-07:12 | 320.29 | 19-JAN-07:01 | 0.00 |
February | 534750.54 | 153172.63 | 0.08 | 534750.54 | -0.0 | 0.00 | 0.18 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 | 3925.27 | 09-FEB-07:02 | 3925.27 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 | 1114.68 | 09-FEB-07:02 | 0.00 |
March | 3533399.78 | 1034795.44 | 3.30 | 3376598.82 | 156800.96 | 0.00 | 0.19 | 23-MAR-06:01 | 0.00 | 01-MAR-00:10 | 4252.04 | 23-MAR-06:01 | 4252.04 | 23-MAR-06:01 | 47.97 | 22-MAR-10:30 | 1203.34 | 23-MAR-06:01 | 0.00 |
April | 0.554432E+09 | 0.148153E+09 | 61.15 | 0.553863E+09 | 569310.47 | 0.00 | 0.86 | 21-APR-13:50 | 0.00 | 01-APR-00:10 | 22246.41 | 21-APR-13:50 | 22246.41 | 21-APR-13:50 | 39.40 | 18-APR-11:50 | 5297.26 | 21-APR-13:50 | 0.00 |
May | 0.380794E+10 | 0.987979E+09 | 160.07 | 0.379110E+10 | 16840971.60 | 0.00 | 1.00 | 12-MAY-13:05 | 0.00 | 01-MAY-00:10 | 36422.34 | 31-MAY-16:00 | 36422.34 | 31-MAY-16:00 | 506.04 | 31-MAY-06:02 | 8313.10 | 31-MAY-16:00 | 0.00 |
June | 0.193262E+11 | 0.472808E+10 | 320.48 | 0.185012E+11 | 0.824999E+09 | 0.00 | 1.00 | 12-JUN-12:50 | 0.00 | 01-JUN-00:10 | 63846.77 | 30-JUN-12:30 | 57753.77 | 29-JUN-14:30 | 13525.15 | 30-JUN-06:02 | 15469.67 | 30-JUN-14:30 | 0.00 |
July | 0.259352E+11 | 0.623687E+10 | 342.22 | 0.238779E+11 | 0.205733E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 58435.22 | 21-JUL-14:30 | 58435.22 | 21-JUL-14:30 | 29672.43 | 03-JUL-15:00 | 14419.74 | 21-JUL-14:40 | 0.00 |
August | 0.135733E+11 | 0.333791E+10 | 266.83 | 0.124818E+11 | 0.109148E+10 | 0.00 | 1.00 | 02-AUG-12:05 | 0.00 | 01-AUG-00:10 | 53725.28 | 11-AUG-15:40 | 53725.28 | 11-AUG-15:40 | 6615.84 | 04-AUG-10:50 | 12665.49 | 11-AUG-15:40 | 0.00 |
September | 0.812628E+09 | 0.217681E+09 | 55.57 | 0.788145E+09 | 24483437.33 | 0.00 | 0.78 | 08-SEP-15:40 | 0.00 | 01-SEP-00:10 | 19723.50 | 08-SEP-15:40 | 19723.50 | 08-SEP-15:40 | 764.24 | 09-SEP-16:06 | 4803.32 | 08-SEP-15:40 | 0.00 |
October | 45491512.08 | 12967097.48 | 6.95 | 42862014.66 | 2629497.41 | 0.00 | 0.22 | 03-OCT-14:40 | 0.00 | 01-OCT-00:10 | 4774.99 | 03-OCT-14:40 | 4573.28 | 03-OCT-14:40 | 259.82 | 03-OCT-15:10 | 1343.97 | 03-OCT-14:40 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 86168.39 | 25362.91 | 0.04 | 86168.39 | -0.0 | 0.00 | 0.03 | 23-DEC-07:03 | 0.00 | 01-DEC-00:10 | 574.46 | 23-DEC-07:03 | 574.46 | 23-DEC-07:03 | 0.00 | 01-DEC-00:10 | 169.09 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.640594E+11 | 0.156709E+11 | 1216.72 | 0.600410E+11 | 0.401848E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.259352E+11 | 0.623687E+10 | 342.22 | 0.238779E+11 | 0.205733E+10 | 0.00 | 1.00 | 0.00 | 63846.77 | 58435.22 | 29672.43 | 15469.67 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.96 | 0.00 | 39.96 | 0.00 | 2975.53 | 0.00 | 0.00 | 0.00 |
February | 176.66 | 0.00 | 176.66 | 0.00 | 2657.74 | 0.00 | 0.00 | 0.00 |
March | 472.48 | 0.00 | 472.48 | 42.93 | 1955.30 | 0.00 | 0.00 | 0.00 |
April | 853.72 | 17.68 | 836.04 | 355.99 | 1039.11 | 0.00 | 0.00 | 0.00 |
May | 1306.08 | 204.17 | 1101.90 | 1023.24 | 473.83 | 0.00 | 0.00 | 0.00 |
June | 1706.65 | 377.36 | 1329.29 | 1700.68 | 220.12 | 0.00 | 0.00 | 0.00 |
July | 1431.90 | 230.38 | 1201.52 | 1457.64 | 269.67 | 0.00 | 0.00 | 0.00 |
August | 914.28 | 49.35 | 864.93 | 756.70 | 449.01 | 0.00 | 0.00 | 0.00 |
September | 511.03 | 0.45 | 510.58 | 196.59 | 898.39 | 0.00 | 0.00 | 0.00 |
October | 248.69 | 0.00 | 248.69 | 20.57 | 1653.48 | 0.00 | 0.00 | 0.00 |
November | 77.18 | 0.00 | 77.18 | 0.00 | 2912.44 | 0.00 | 0.00 | 0.00 |
December | 12.12 | 0.00 | 12.12 | 0.00 | 3135.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 648.20 | 73.60 | 574.60 | 465.57 | 1547.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.12 | 0.00 | 12.12 | 0.00 | 220.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1706.65 | 377.36 | 1329.29 | 1700.68 | 3135.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.53 | 21.43 | 48.10 | 6.20 | 1925.51 | 0.00 | 0.00 | 0.00 |
February | 386.82 | 184.08 | 202.74 | 209.92 | 1602.44 | 0.00 | 0.00 | 0.00 |
March | 1107.49 | 561.55 | 545.95 | 958.58 | 1170.62 | 0.00 | 0.00 | 0.00 |
April | 1523.07 | 771.86 | 751.22 | 1438.31 | 644.38 | 0.00 | 0.00 | 0.00 |
May | 2215.71 | 1250.43 | 965.29 | 2469.54 | 344.93 | 0.00 | 0.00 | 0.00 |
June | 2036.67 | 951.32 | 1085.34 | 2345.95 | 169.84 | 0.00 | 0.00 | 0.00 |
July | 1935.00 | 939.55 | 995.45 | 2283.85 | 195.17 | 0.00 | 0.00 | 0.00 |
August | 1532.21 | 746.91 | 785.31 | 1729.76 | 304.80 | 0.00 | 0.00 | 0.00 |
September | 947.02 | 415.27 | 531.75 | 895.79 | 567.93 | 0.00 | 0.00 | 0.00 |
October | 499.30 | 200.20 | 299.10 | 368.21 | 1003.42 | 0.00 | 0.00 | 0.00 |
November | 105.42 | 36.29 | 69.13 | 8.77 | 1869.56 | 0.00 | 0.00 | 0.00 |
December | 14.99 | 3.44 | 11.55 | 0.00 | 2078.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1035.06 | 509.11 | 525.95 | 1065.32 | 986.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.99 | 3.44 | 11.55 | 0.00 | 169.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2215.71 | 1250.43 | 1085.34 | 2469.54 | 2078.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.83 | 319.27 | 163.57 | 290.02 | 2673.05 | 0.00 | 0.00 | 0.00 |
February | 1660.68 | 1158.50 | 502.19 | 1445.10 | 2143.03 | 0.00 | 0.00 | 0.00 |
March | 2844.95 | 1932.19 | 912.76 | 2852.88 | 1637.32 | 0.00 | 0.00 | 0.00 |
April | 3462.47 | 2156.39 | 1306.08 | 3862.73 | 1076.28 | 0.00 | 0.00 | 0.00 |
May | 2844.60 | 1471.39 | 1373.21 | 3255.24 | 599.39 | 0.00 | 0.00 | 0.00 |
June | 2594.00 | 1058.45 | 1535.55 | 3050.91 | 322.33 | 0.00 | 0.00 | 0.00 |
July | 2501.55 | 1086.34 | 1415.21 | 3013.67 | 343.71 | 0.00 | 0.00 | 0.00 |
August | 2598.35 | 1432.92 | 1165.43 | 3085.58 | 504.26 | 0.00 | 0.00 | 0.00 |
September | 2104.55 | 1269.97 | 834.58 | 2270.77 | 869.94 | 0.00 | 0.00 | 0.00 |
October | 1518.69 | 966.47 | 552.22 | 1422.89 | 1394.64 | 0.00 | 0.00 | 0.00 |
November | 815.96 | 571.54 | 244.41 | 556.11 | 2489.54 | 0.00 | 0.00 | 0.00 |
December | 144.90 | 102.47 | 42.44 | 26.22 | 2981.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1963.89 | 1125.40 | 838.49 | 2095.94 | 1416.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.90 | 102.47 | 42.44 | 26.22 | 322.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3462.47 | 2156.39 | 1535.55 | 3862.73 | 2981.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.63 | 6.30 | 30.33 | 0.00 | 1963.43 | 0.00 | 0.00 | 0.00 |
February | 216.80 | 74.65 | 142.16 | 45.76 | 1665.97 | 0.00 | 0.00 | 0.00 |
March | 653.44 | 280.50 | 372.94 | 385.19 | 1197.03 | 0.00 | 0.00 | 0.00 |
April | 1555.07 | 807.21 | 747.86 | 1523.05 | 690.72 | 0.00 | 0.00 | 0.00 |
May | 1512.25 | 690.28 | 821.96 | 1561.58 | 365.60 | 0.00 | 0.00 | 0.00 |
June | 1657.01 | 708.17 | 948.85 | 1861.32 | 198.34 | 0.00 | 0.00 | 0.00 |
July | 1385.83 | 525.34 | 860.48 | 1568.88 | 215.39 | 0.00 | 0.00 | 0.00 |
August | 1138.81 | 482.97 | 655.83 | 1222.96 | 320.59 | 0.00 | 0.00 | 0.00 |
September | 688.77 | 288.64 | 400.14 | 575.20 | 580.51 | 0.00 | 0.00 | 0.00 |
October | 268.77 | 80.21 | 188.55 | 105.13 | 1045.91 | 0.00 | 0.00 | 0.00 |
November | 107.07 | 38.39 | 68.68 | 11.91 | 1864.92 | 0.00 | 0.00 | 0.00 |
December | 9.62 | 0.95 | 8.67 | 0.00 | 2085.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.16 | 332.67 | 438.49 | 741.32 | 1012.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.62 | 0.95 | 8.67 | 0.00 | 198.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.01 | 807.21 | 948.85 | 1861.32 | 2085.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 993.36 | 0.00 | 0.00 | 0.00 |
February | 58.88 | 0.00 | 58.88 | 0.00 | 882.28 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.45 | 648.59 | 0.00 | 0.00 | 0.00 |
April | 284.56 | 5.89 | 278.67 | 129.20 | 340.88 | 0.00 | 0.00 | 0.00 |
May | 435.34 | 68.05 | 367.28 | 356.84 | 152.10 | 0.00 | 0.00 | 0.00 |
June | 568.86 | 125.78 | 443.08 | 579.22 | 70.56 | 0.00 | 0.00 | 0.00 |
July | 477.28 | 76.79 | 400.49 | 493.69 | 88.33 | 0.00 | 0.00 | 0.00 |
August | 304.74 | 16.45 | 288.30 | 253.97 | 152.27 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 62.82 | 316.55 | 0.00 | 0.00 | 0.00 |
October | 82.89 | 0.00 | 82.89 | 5.63 | 576.90 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 989.67 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1055.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.06 | 24.53 | 191.52 | 158.99 | 520.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 70.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.86 | 125.78 | 443.08 | 579.22 | 1055.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 993.42 | 0.00 | 0.00 | 0.00 |
February | 58.89 | 0.00 | 58.89 | 0.00 | 882.33 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.45 | 648.63 | 0.00 | 0.00 | 0.00 |
April | 284.57 | 5.89 | 278.68 | 129.20 | 340.90 | 0.00 | 0.00 | 0.00 |
May | 435.35 | 68.06 | 367.30 | 356.85 | 152.11 | 0.00 | 0.00 | 0.00 |
June | 568.88 | 125.78 | 443.09 | 579.24 | 70.56 | 0.00 | 0.00 | 0.00 |
July | 477.29 | 76.79 | 400.50 | 493.71 | 88.33 | 0.00 | 0.00 | 0.00 |
August | 304.76 | 16.45 | 288.31 | 253.98 | 152.28 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 62.82 | 316.57 | 0.00 | 0.00 | 0.00 |
October | 82.90 | 0.00 | 82.90 | 5.63 | 576.93 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 989.73 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1055.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.07 | 24.53 | 191.53 | 158.99 | 520.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 70.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.88 | 125.78 | 443.09 | 579.24 | 1055.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 993.42 | 0.00 | 0.00 | 0.00 |
February | 58.89 | 0.00 | 58.89 | 0.00 | 882.33 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.45 | 648.63 | 0.00 | 0.00 | 0.00 |
April | 284.57 | 5.89 | 278.68 | 129.20 | 340.90 | 0.00 | 0.00 | 0.00 |
May | 435.35 | 68.06 | 367.30 | 356.85 | 152.11 | 0.00 | 0.00 | 0.00 |
June | 568.88 | 125.78 | 443.09 | 579.24 | 70.56 | 0.00 | 0.00 | 0.00 |
July | 477.29 | 76.79 | 400.50 | 493.71 | 88.33 | 0.00 | 0.00 | 0.00 |
August | 304.76 | 16.45 | 288.31 | 253.98 | 152.28 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 62.82 | 316.57 | 0.00 | 0.00 | 0.00 |
October | 82.90 | 0.00 | 82.90 | 5.63 | 576.93 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 989.73 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1055.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.07 | 24.53 | 191.53 | 158.99 | 520.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 70.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.88 | 125.78 | 443.09 | 579.24 | 1055.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.88 | 20.62 | 46.27 | 6.17 | 1857.37 | 0.00 | 0.00 | 0.00 |
February | 372.10 | 177.07 | 195.03 | 203.47 | 1539.93 | 0.00 | 0.00 | 0.00 |
March | 1065.35 | 540.18 | 525.17 | 932.14 | 1129.53 | 0.00 | 0.00 | 0.00 |
April | 1465.12 | 742.49 | 722.63 | 1399.00 | 627.14 | 0.00 | 0.00 | 0.00 |
May | 2131.40 | 1202.84 | 928.56 | 2392.04 | 335.64 | 0.00 | 0.00 | 0.00 |
June | 1959.17 | 915.12 | 1044.05 | 2273.71 | 162.73 | 0.00 | 0.00 | 0.00 |
July | 1861.37 | 903.79 | 957.57 | 2207.48 | 191.18 | 0.00 | 0.00 | 0.00 |
August | 1473.91 | 718.49 | 755.43 | 1666.91 | 305.80 | 0.00 | 0.00 | 0.00 |
September | 910.99 | 399.47 | 511.52 | 852.88 | 586.81 | 0.00 | 0.00 | 0.00 |
October | 480.30 | 192.58 | 287.72 | 347.68 | 1020.25 | 0.00 | 0.00 | 0.00 |
November | 101.41 | 34.91 | 66.50 | 8.23 | 1832.86 | 0.00 | 0.00 | 0.00 |
December | 14.42 | 3.31 | 11.11 | 0.00 | 2018.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 995.68 | 489.74 | 505.94 | 1029.69 | 964.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.42 | 3.31 | 11.11 | 0.00 | 162.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2131.40 | 1202.84 | 1044.05 | 2392.04 | 2018.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.64 | 0.82 | 1.83 | 0.24 | 73.44 | 0.00 | 0.00 | 0.00 |
February | 14.71 | 7.00 | 7.71 | 8.04 | 60.89 | 0.00 | 0.00 | 0.00 |
March | 42.12 | 21.36 | 20.76 | 36.86 | 44.66 | 0.00 | 0.00 | 0.00 |
April | 57.93 | 29.36 | 28.57 | 55.32 | 24.80 | 0.00 | 0.00 | 0.00 |
May | 84.27 | 47.56 | 36.71 | 94.58 | 13.27 | 0.00 | 0.00 | 0.00 |
June | 77.46 | 36.18 | 41.28 | 89.90 | 6.43 | 0.00 | 0.00 | 0.00 |
July | 73.60 | 35.74 | 37.86 | 87.28 | 7.56 | 0.00 | 0.00 | 0.00 |
August | 58.28 | 28.41 | 29.87 | 65.91 | 12.09 | 0.00 | 0.00 | 0.00 |
September | 36.02 | 15.79 | 20.22 | 33.72 | 23.20 | 0.00 | 0.00 | 0.00 |
October | 18.99 | 7.61 | 11.38 | 13.75 | 40.34 | 0.00 | 0.00 | 0.00 |
November | 4.01 | 1.38 | 2.63 | 0.33 | 72.47 | 0.00 | 0.00 | 0.00 |
December | 0.57 | 0.13 | 0.44 | 0.00 | 79.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.37 | 19.36 | 20.00 | 40.71 | 38.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.57 | 0.13 | 0.44 | 0.00 | 6.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.27 | 47.56 | 41.28 | 94.58 | 79.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.94 | 106.42 | 54.52 | 99.38 | 874.38 | 0.00 | 0.00 | 0.00 |
February | 553.55 | 386.16 | 167.39 | 489.50 | 705.47 | 0.00 | 0.00 | 0.00 |
March | 948.30 | 644.05 | 304.25 | 967.46 | 545.57 | 0.00 | 0.00 | 0.00 |
April | 1154.14 | 718.78 | 435.36 | 1300.27 | 369.95 | 0.00 | 0.00 | 0.00 |
May | 948.19 | 490.45 | 457.73 | 1098.08 | 201.51 | 0.00 | 0.00 | 0.00 |
June | 864.65 | 352.81 | 511.84 | 1028.68 | 107.01 | 0.00 | 0.00 | 0.00 |
July | 833.84 | 362.11 | 471.73 | 1012.68 | 116.65 | 0.00 | 0.00 | 0.00 |
August | 866.10 | 477.63 | 388.47 | 1033.68 | 176.67 | 0.00 | 0.00 | 0.00 |
September | 701.50 | 423.31 | 278.19 | 757.53 | 310.40 | 0.00 | 0.00 | 0.00 |
October | 506.22 | 322.15 | 184.07 | 473.34 | 488.71 | 0.00 | 0.00 | 0.00 |
November | 271.98 | 190.51 | 81.47 | 187.84 | 832.51 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.16 | 14.15 | 9.94 | 979.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.62 | 375.13 | 279.49 | 705.39 | 474.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.16 | 14.15 | 9.94 | 107.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.14 | 718.78 | 511.84 | 1300.27 | 979.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.94 | 106.42 | 54.52 | 99.38 | 874.38 | 0.00 | 0.00 | 0.00 |
February | 553.55 | 386.16 | 167.39 | 489.50 | 705.47 | 0.00 | 0.00 | 0.00 |
March | 948.30 | 644.05 | 304.25 | 967.46 | 545.57 | 0.00 | 0.00 | 0.00 |
April | 1154.14 | 718.78 | 435.36 | 1300.27 | 369.95 | 0.00 | 0.00 | 0.00 |
May | 948.19 | 490.45 | 457.73 | 1098.08 | 201.51 | 0.00 | 0.00 | 0.00 |
June | 864.65 | 352.81 | 511.84 | 1028.68 | 107.01 | 0.00 | 0.00 | 0.00 |
July | 833.84 | 362.11 | 471.73 | 1012.68 | 116.65 | 0.00 | 0.00 | 0.00 |
August | 866.10 | 477.63 | 388.47 | 1033.68 | 176.67 | 0.00 | 0.00 | 0.00 |
September | 701.50 | 423.31 | 278.19 | 757.53 | 310.40 | 0.00 | 0.00 | 0.00 |
October | 506.22 | 322.15 | 184.07 | 473.34 | 488.71 | 0.00 | 0.00 | 0.00 |
November | 271.98 | 190.51 | 81.47 | 187.84 | 832.51 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.16 | 14.15 | 9.94 | 979.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.62 | 375.13 | 279.49 | 705.39 | 474.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.16 | 14.15 | 9.94 | 107.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.14 | 718.78 | 511.84 | 1300.27 | 979.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.93 | 106.41 | 54.52 | 99.38 | 874.32 | 0.00 | 0.00 | 0.00 |
February | 553.52 | 386.13 | 167.38 | 489.47 | 705.43 | 0.00 | 0.00 | 0.00 |
March | 948.24 | 644.01 | 304.23 | 967.40 | 545.53 | 0.00 | 0.00 | 0.00 |
April | 1154.06 | 718.74 | 435.33 | 1300.19 | 369.93 | 0.00 | 0.00 | 0.00 |
May | 948.13 | 490.42 | 457.70 | 1098.01 | 201.50 | 0.00 | 0.00 | 0.00 |
June | 864.60 | 352.79 | 511.81 | 1028.61 | 107.00 | 0.00 | 0.00 | 0.00 |
July | 833.78 | 362.08 | 471.70 | 1012.61 | 116.64 | 0.00 | 0.00 | 0.00 |
August | 866.05 | 477.60 | 388.45 | 1033.62 | 176.66 | 0.00 | 0.00 | 0.00 |
September | 701.46 | 423.29 | 278.17 | 757.48 | 310.38 | 0.00 | 0.00 | 0.00 |
October | 506.19 | 322.13 | 184.06 | 473.31 | 488.68 | 0.00 | 0.00 | 0.00 |
November | 271.96 | 190.50 | 81.46 | 187.82 | 832.46 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.15 | 14.14 | 9.94 | 979.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.58 | 375.10 | 279.48 | 705.34 | 474.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.15 | 14.14 | 9.94 | 107.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.06 | 718.74 | 511.81 | 1300.19 | 979.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.24 | 6.06 | 29.18 | 0.00 | 1894.15 | 0.00 | 0.00 | 0.00 |
February | 208.55 | 71.81 | 136.75 | 45.19 | 1600.00 | 0.00 | 0.00 | 0.00 |
March | 628.57 | 269.82 | 358.75 | 380.23 | 1151.27 | 0.00 | 0.00 | 0.00 |
April | 1495.90 | 776.49 | 719.41 | 1484.35 | 676.71 | 0.00 | 0.00 | 0.00 |
May | 1454.71 | 664.02 | 790.69 | 1523.98 | 351.70 | 0.00 | 0.00 | 0.00 |
June | 1593.97 | 681.22 | 912.75 | 1809.18 | 189.43 | 0.00 | 0.00 | 0.00 |
July | 1333.10 | 505.35 | 827.74 | 1522.67 | 208.47 | 0.00 | 0.00 | 0.00 |
August | 1095.48 | 464.60 | 630.88 | 1180.56 | 321.50 | 0.00 | 0.00 | 0.00 |
September | 662.57 | 277.65 | 384.91 | 546.43 | 598.69 | 0.00 | 0.00 | 0.00 |
October | 258.54 | 77.16 | 181.38 | 97.37 | 1056.91 | 0.00 | 0.00 | 0.00 |
November | 103.00 | 36.93 | 66.06 | 11.12 | 1829.21 | 0.00 | 0.00 | 0.00 |
December | 9.25 | 0.91 | 8.34 | 0.00 | 2024.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.82 | 320.01 | 421.80 | 719.58 | 988.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.25 | 0.91 | 8.34 | 0.00 | 189.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1593.97 | 776.49 | 912.75 | 1809.18 | 2024.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.39 | 0.24 | 1.15 | 0.00 | 74.89 | 0.00 | 0.00 | 0.00 |
February | 8.25 | 2.84 | 5.41 | 1.79 | 63.26 | 0.00 | 0.00 | 0.00 |
March | 24.85 | 10.67 | 14.18 | 15.03 | 45.52 | 0.00 | 0.00 | 0.00 |
April | 59.15 | 30.70 | 28.44 | 58.69 | 26.76 | 0.00 | 0.00 | 0.00 |
May | 57.52 | 26.25 | 31.26 | 60.26 | 13.91 | 0.00 | 0.00 | 0.00 |
June | 63.02 | 26.93 | 36.09 | 71.53 | 7.49 | 0.00 | 0.00 | 0.00 |
July | 52.71 | 19.98 | 32.73 | 60.20 | 8.24 | 0.00 | 0.00 | 0.00 |
August | 43.31 | 18.37 | 24.94 | 46.68 | 12.71 | 0.00 | 0.00 | 0.00 |
September | 26.20 | 10.98 | 15.22 | 21.61 | 23.67 | 0.00 | 0.00 | 0.00 |
October | 10.22 | 3.05 | 7.17 | 3.85 | 41.79 | 0.00 | 0.00 | 0.00 |
November | 4.07 | 1.46 | 2.61 | 0.44 | 72.33 | 0.00 | 0.00 | 0.00 |
December | 0.37 | 0.04 | 0.33 | 0.00 | 80.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.33 | 12.65 | 16.68 | 28.45 | 39.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.37 | 0.04 | 0.33 | 0.00 | 7.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.02 | 30.70 | 36.09 | 71.53 | 80.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.96 | 0.00 | 39.96 | 0.00 | 3026.19 | 0.00 | 0.00 | 0.00 |
February | 176.66 | 0.00 | 176.66 | 0.00 | 2712.68 | 0.00 | 0.00 | 0.00 |
March | 472.48 | 0.00 | 472.48 | 39.69 | 2015.32 | 0.00 | 0.00 | 0.00 |
April | 853.72 | 17.68 | 836.04 | 340.35 | 1091.86 | 0.00 | 0.00 | 0.00 |
May | 1306.08 | 204.17 | 1101.90 | 1006.21 | 491.66 | 0.00 | 0.00 | 0.00 |
June | 1706.65 | 377.36 | 1329.29 | 1695.91 | 226.53 | 0.00 | 0.00 | 0.00 |
July | 1431.90 | 230.38 | 1201.52 | 1453.33 | 277.18 | 0.00 | 0.00 | 0.00 |
August | 914.28 | 49.35 | 864.93 | 747.00 | 467.36 | 0.00 | 0.00 | 0.00 |
September | 511.03 | 0.45 | 510.58 | 181.09 | 958.87 | 0.00 | 0.00 | 0.00 |
October | 248.69 | 0.00 | 248.69 | 15.90 | 1728.07 | 0.00 | 0.00 | 0.00 |
November | 77.18 | 0.00 | 77.18 | 0.00 | 2974.92 | 0.00 | 0.00 | 0.00 |
December | 12.12 | 0.00 | 12.12 | 0.00 | 3192.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 648.20 | 73.60 | 574.60 | 459.31 | 1590.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.12 | 0.00 | 12.12 | 0.00 | 226.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1706.65 | 377.36 | 1329.29 | 1695.91 | 3192.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.53 | 21.43 | 48.10 | 6.15 | 1954.42 | 0.00 | 0.00 | 0.00 |
February | 386.82 | 184.08 | 202.74 | 206.66 | 1634.24 | 0.00 | 0.00 | 0.00 |
March | 1107.49 | 561.55 | 545.95 | 947.82 | 1207.92 | 0.00 | 0.00 | 0.00 |
April | 1523.07 | 771.86 | 751.22 | 1422.78 | 673.74 | 0.00 | 0.00 | 0.00 |
May | 2215.71 | 1250.43 | 965.29 | 2460.15 | 356.38 | 0.00 | 0.00 | 0.00 |
June | 2036.67 | 951.32 | 1085.34 | 2341.32 | 174.36 | 0.00 | 0.00 | 0.00 |
July | 1935.00 | 939.55 | 995.45 | 2279.75 | 200.25 | 0.00 | 0.00 | 0.00 |
August | 1532.21 | 746.91 | 785.31 | 1723.00 | 315.64 | 0.00 | 0.00 | 0.00 |
September | 947.02 | 415.27 | 531.75 | 881.11 | 601.87 | 0.00 | 0.00 | 0.00 |
October | 499.30 | 200.20 | 299.10 | 358.76 | 1050.18 | 0.00 | 0.00 | 0.00 |
November | 105.42 | 36.29 | 69.13 | 8.45 | 1906.32 | 0.00 | 0.00 | 0.00 |
December | 14.99 | 3.44 | 11.55 | 0.00 | 2110.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1035.06 | 509.11 | 525.95 | 1058.74 | 1012.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.99 | 3.44 | 11.55 | 0.00 | 174.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2215.71 | 1250.43 | 1085.34 | 2460.15 | 2110.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.83 | 319.27 | 163.57 | 286.54 | 2719.78 | 0.00 | 0.00 | 0.00 |
February | 1660.68 | 1158.50 | 502.19 | 1432.62 | 2195.26 | 0.00 | 0.00 | 0.00 |
March | 2844.95 | 1932.19 | 912.76 | 2837.56 | 1692.67 | 0.00 | 0.00 | 0.00 |
April | 3462.47 | 2156.39 | 1306.08 | 3848.76 | 1124.45 | 0.00 | 0.00 | 0.00 |
May | 2844.60 | 1471.39 | 1373.21 | 3249.63 | 624.59 | 0.00 | 0.00 | 0.00 |
June | 2594.00 | 1058.45 | 1535.55 | 3050.66 | 332.76 | 0.00 | 0.00 | 0.00 |
July | 2501.55 | 1086.34 | 1415.21 | 3013.45 | 354.41 | 0.00 | 0.00 | 0.00 |
August | 2598.35 | 1432.92 | 1165.43 | 3082.08 | 524.00 | 0.00 | 0.00 | 0.00 |
September | 2104.55 | 1269.97 | 834.58 | 2253.74 | 920.04 | 0.00 | 0.00 | 0.00 |
October | 1518.69 | 966.47 | 552.22 | 1403.75 | 1461.61 | 0.00 | 0.00 | 0.00 |
November | 815.96 | 571.54 | 244.41 | 548.35 | 2549.04 | 0.00 | 0.00 | 0.00 |
December | 144.90 | 102.47 | 42.44 | 25.79 | 3035.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1963.89 | 1125.40 | 838.49 | 2087.73 | 1457.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.90 | 102.47 | 42.44 | 25.79 | 332.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3462.47 | 2156.39 | 1535.55 | 3848.76 | 3035.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.63 | 6.30 | 30.33 | 0.00 | 1994.83 | 0.00 | 0.00 | 0.00 |
February | 216.80 | 74.65 | 142.16 | 44.74 | 1700.17 | 0.00 | 0.00 | 0.00 |
March | 653.44 | 280.50 | 372.94 | 380.71 | 1235.02 | 0.00 | 0.00 | 0.00 |
April | 1555.07 | 807.21 | 747.86 | 1513.10 | 724.24 | 0.00 | 0.00 | 0.00 |
May | 1512.25 | 690.28 | 821.96 | 1556.03 | 381.99 | 0.00 | 0.00 | 0.00 |
June | 1657.01 | 708.17 | 948.85 | 1860.69 | 205.10 | 0.00 | 0.00 | 0.00 |
July | 1385.83 | 525.34 | 860.48 | 1568.25 | 222.41 | 0.00 | 0.00 | 0.00 |
August | 1138.81 | 482.97 | 655.83 | 1219.36 | 334.09 | 0.00 | 0.00 | 0.00 |
September | 688.77 | 288.64 | 400.14 | 564.25 | 617.75 | 0.00 | 0.00 | 0.00 |
October | 268.77 | 80.21 | 188.55 | 99.84 | 1093.61 | 0.00 | 0.00 | 0.00 |
November | 107.07 | 38.39 | 68.68 | 11.38 | 1904.02 | 0.00 | 0.00 | 0.00 |
December | 9.62 | 0.95 | 8.67 | 0.00 | 2119.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.16 | 332.67 | 438.49 | 737.77 | 1041.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.62 | 0.95 | 8.67 | 0.00 | 205.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.01 | 807.21 | 948.85 | 1860.69 | 2119.93 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.796966E+10 |
February | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.642962E+10 |
March | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.114988E+09 | 0.523707E+10 |
April | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.922736E+09 | 0.269337E+10 |
May | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.274065E+10 | 0.126910E+10 |
June | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.440816E+10 | 0.570554E+09 |
July | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.390415E+10 | 0.722277E+09 |
August | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.202674E+10 | 0.120264E+10 |
September | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.509566E+09 | 0.232862E+10 |
October | 0.666103E+09 | 0.00 | 0.666103E+09 | 55085622.62 | 0.442868E+10 |
November | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.754906E+10 |
December | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.839944E+10 |
Annual Sum or Average | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.146821E+11 | 0.488001E+11 |
Minimum of Months | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.570554E+09 |
Maximum of Months | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.440816E+10 | 0.839944E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 16605936.38 | 0.515730E+10 |
February | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.507835E+09 | 0.387663E+10 |
March | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.256745E+10 | 0.313539E+10 |
April | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.372811E+10 | 0.167023E+10 |
May | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.661442E+10 | 0.923865E+09 |
June | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.608071E+10 | 0.440232E+09 |
July | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.611706E+10 | 0.522731E+09 |
August | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.463299E+10 | 0.816381E+09 |
September | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.232189E+10 | 0.147208E+10 |
October | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.986216E+09 | 0.268755E+10 |
November | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 22728300.93 | 0.484589E+10 |
December | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.556832E+10 |
Annual Sum or Average | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.335960E+11 | 0.311166E+11 |
Minimum of Months | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.440232E+09 |
Maximum of Months | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.661442E+10 | 0.556832E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.776790E+09 | 0.715950E+10 |
February | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.349599E+10 | 0.518441E+10 |
March | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.764114E+10 | 0.438541E+10 |
April | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.100122E+11 | 0.278972E+10 |
May | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.871883E+10 | 0.160540E+10 |
June | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.790796E+10 | 0.835469E+09 |
July | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.807180E+10 | 0.920602E+09 |
August | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.826441E+10 | 0.135060E+10 |
September | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.588583E+10 | 0.225489E+10 |
October | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.381107E+10 | 0.373542E+10 |
November | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.144145E+10 | 0.645288E+10 |
December | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 70222207.28 | 0.798596E+10 |
Annual Sum or Average | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.660977E+11 | 0.446603E+11 |
Minimum of Months | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 70222207.28 | 0.835469E+09 |
Maximum of Months | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.100122E+11 | 0.798596E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.525886E+10 |
February | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.110692E+09 | 0.403030E+10 |
March | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.103169E+10 | 0.320612E+10 |
April | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.394774E+10 | 0.179035E+10 |
May | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.418255E+10 | 0.979230E+09 |
June | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.482454E+10 | 0.514098E+09 |
July | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.420209E+10 | 0.576903E+09 |
August | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.327557E+10 | 0.858681E+09 |
September | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.149091E+10 | 0.150469E+10 |
October | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.281576E+09 | 0.280137E+10 |
November | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 30883669.08 | 0.483388E+10 |
December | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.558625E+10 |
Annual Sum or Average | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.233782E+11 | 0.319407E+11 |
Minimum of Months | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.514098E+09 |
Maximum of Months | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.482454E+10 | 0.558625E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35677821.11 | 0.00 | 35677821.11 | 0.00 | 0.266062E+10 |
February | 0.142450E+09 | 0.00 | 0.142450E+09 | 0.00 | 0.213440E+10 |
March | 0.421814E+09 | 0.00 | 0.421814E+09 | 41373856.74 | 0.173717E+10 |
April | 0.737577E+09 | 15275674.84 | 0.722302E+09 | 0.334888E+09 | 0.883557E+09 |
May | 0.116601E+10 | 0.182278E+09 | 0.983730E+09 | 0.955756E+09 | 0.407380E+09 |
June | 0.147447E+10 | 0.326021E+09 | 0.114845E+10 | 0.150135E+10 | 0.182886E+09 |
July | 0.127834E+10 | 0.205670E+09 | 0.107267E+10 | 0.132231E+10 | 0.236575E+09 |
August | 0.816226E+09 | 44054132.18 | 0.772172E+09 | 0.680235E+09 | 0.407841E+09 |
September | 0.441512E+09 | 389190.75 | 0.441123E+09 | 0.162828E+09 | 0.820486E+09 |
October | 0.222024E+09 | 0.00 | 0.222024E+09 | 15068868.94 | 0.154516E+10 |
November | 66679304.90 | 0.00 | 66679304.90 | 0.00 | 0.256521E+10 |
December | 10822788.22 | 0.00 | 10822788.22 | 0.00 | 0.282814E+10 |
Annual Sum or Average | 0.681360E+10 | 0.773689E+09 | 0.603991E+10 | 0.501381E+10 | 0.164094E+11 |
Minimum of Months | 10822788.22 | 0.00 | 10822788.22 | 0.00 | 0.182886E+09 |
Maximum of Months | 0.147447E+10 | 0.326021E+09 | 0.114845E+10 | 0.150135E+10 | 0.282814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35679076.65 | 0.00 | 35679076.65 | 0.00 | 0.266078E+10 |
February | 0.142456E+09 | 0.00 | 0.142456E+09 | 0.00 | 0.213454E+10 |
March | 0.421831E+09 | 0.00 | 0.421831E+09 | 41372110.68 | 0.173729E+10 |
April | 0.737606E+09 | 15276085.46 | 0.722330E+09 | 0.334893E+09 | 0.883615E+09 |
May | 0.116605E+10 | 0.182283E+09 | 0.983768E+09 | 0.955778E+09 | 0.407405E+09 |
June | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150139E+10 | 0.182897E+09 |
July | 0.127838E+10 | 0.205676E+09 | 0.107271E+10 | 0.132235E+10 | 0.236590E+09 |
August | 0.816257E+09 | 44055316.37 | 0.772202E+09 | 0.680253E+09 | 0.407866E+09 |
September | 0.441529E+09 | 389201.21 | 0.441139E+09 | 0.162829E+09 | 0.820539E+09 |
October | 0.222032E+09 | 0.00 | 0.222032E+09 | 15068233.66 | 0.154526E+10 |
November | 66681651.46 | 0.00 | 66681651.46 | 0.00 | 0.256537E+10 |
December | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.282831E+10 |
Annual Sum or Average | 0.681385E+10 | 0.773710E+09 | 0.604014E+10 | 0.501393E+10 | 0.164105E+11 |
Minimum of Months | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.182897E+09 |
Maximum of Months | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150139E+10 | 0.282831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35679076.65 | 0.00 | 35679076.65 | 0.00 | 0.266078E+10 |
February | 0.142456E+09 | 0.00 | 0.142456E+09 | 0.00 | 0.213454E+10 |
March | 0.421831E+09 | 0.00 | 0.421831E+09 | 41372110.68 | 0.173729E+10 |
April | 0.737606E+09 | 15276085.46 | 0.722330E+09 | 0.334893E+09 | 0.883615E+09 |
May | 0.116605E+10 | 0.182283E+09 | 0.983768E+09 | 0.955778E+09 | 0.407405E+09 |
June | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150139E+10 | 0.182897E+09 |
July | 0.127838E+10 | 0.205676E+09 | 0.107271E+10 | 0.132235E+10 | 0.236590E+09 |
August | 0.816257E+09 | 44055316.37 | 0.772202E+09 | 0.680253E+09 | 0.407866E+09 |
September | 0.441529E+09 | 389201.21 | 0.441139E+09 | 0.162829E+09 | 0.820539E+09 |
October | 0.222032E+09 | 0.00 | 0.222032E+09 | 15068233.66 | 0.154526E+10 |
November | 66681651.46 | 0.00 | 66681651.46 | 0.00 | 0.256537E+10 |
December | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.282831E+10 |
Annual Sum or Average | 0.681385E+10 | 0.773710E+09 | 0.604014E+10 | 0.501393E+10 | 0.164105E+11 |
Minimum of Months | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.182897E+09 |
Maximum of Months | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.150139E+10 | 0.282831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179138E+09 | 55218116.69 | 0.123919E+09 | 16534935.84 | 0.497479E+10 |
February | 0.900183E+09 | 0.428378E+09 | 0.471805E+09 | 0.492227E+09 | 0.372540E+10 |
March | 0.285343E+10 | 0.144681E+10 | 0.140662E+10 | 0.249664E+10 | 0.302532E+10 |
April | 0.379759E+10 | 0.192452E+10 | 0.187306E+10 | 0.362621E+10 | 0.162555E+10 |
May | 0.570875E+10 | 0.322170E+10 | 0.248705E+10 | 0.640684E+10 | 0.898972E+09 |
June | 0.507816E+10 | 0.237199E+10 | 0.270617E+10 | 0.589345E+10 | 0.421801E+09 |
July | 0.498549E+10 | 0.242072E+10 | 0.256477E+10 | 0.591250E+10 | 0.512045E+09 |
August | 0.394773E+10 | 0.192439E+10 | 0.202333E+10 | 0.446465E+10 | 0.819050E+09 |
September | 0.236128E+10 | 0.103542E+10 | 0.132586E+10 | 0.221067E+10 | 0.152102E+10 |
October | 0.128644E+10 | 0.515813E+09 | 0.770629E+09 | 0.931239E+09 | 0.273264E+10 |
November | 0.262854E+09 | 90488299.20 | 0.172366E+09 | 21331946.87 | 0.475078E+10 |
December | 38623368.56 | 8872006.07 | 29751362.49 | 0.00 | 0.540512E+10 |
Annual Sum or Average | 0.313997E+11 | 0.154443E+11 | 0.159553E+11 | 0.324723E+11 | 0.304125E+11 |
Minimum of Months | 38623368.56 | 8872006.07 | 29751362.49 | 0.00 | 0.421801E+09 |
Maximum of Months | 0.570875E+10 | 0.322170E+10 | 0.270617E+10 | 0.640684E+10 | 0.540512E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7082936.28 | 2183274.62 | 4899661.66 | 653776.48 | 0.196699E+09 |
February | 35592418.46 | 16937678.99 | 18654739.47 | 19462214.11 | 0.147299E+09 |
March | 0.112822E+09 | 57205554.86 | 55616515.73 | 98715050.10 | 0.119619E+09 |
April | 0.150153E+09 | 76093951.76 | 74059270.83 | 0.143377E+09 | 64272903.66 |
May | 0.225719E+09 | 0.127383E+09 | 98335906.32 | 0.253321E+09 | 35544534.37 |
June | 0.200786E+09 | 93786470.86 | 0.107000E+09 | 0.233022E+09 | 16677642.62 |
July | 0.197122E+09 | 95713028.32 | 0.101409E+09 | 0.233775E+09 | 20245811.72 |
August | 0.156090E+09 | 76088825.43 | 80000707.63 | 0.176528E+09 | 32384483.83 |
September | 93362824.18 | 40939699.31 | 52423124.87 | 87407868.88 | 60139700.65 |
October | 50864781.68 | 20394799.44 | 30469982.24 | 36820335.98 | 0.108046E+09 |
November | 10393016.29 | 3577825.88 | 6815190.41 | 843445.97 | 0.187842E+09 |
December | 1527133.22 | 350791.13 | 1176342.09 | 0.00 | 0.213714E+09 |
Annual Sum or Average | 0.124151E+10 | 0.610655E+09 | 0.630860E+09 | 0.128393E+10 | 0.120248E+10 |
Minimum of Months | 1527133.22 | 350791.13 | 1176342.09 | 0.00 | 16677642.62 |
Maximum of Months | 0.225719E+09 | 0.127383E+09 | 0.107000E+09 | 0.253321E+09 | 0.213714E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431067E+09 | 0.285037E+09 | 0.146030E+09 | 0.266186E+09 | 0.234194E+10 |
February | 0.133915E+10 | 0.934194E+09 | 0.404956E+09 | 0.118421E+10 | 0.170668E+10 |
March | 0.253992E+10 | 0.172502E+10 | 0.814901E+09 | 0.259125E+10 | 0.146124E+10 |
April | 0.299152E+10 | 0.186308E+10 | 0.112844E+10 | 0.337030E+10 | 0.958917E+09 |
May | 0.253962E+10 | 0.131363E+10 | 0.122599E+10 | 0.294109E+10 | 0.539735E+09 |
June | 0.224119E+10 | 0.914485E+09 | 0.132670E+10 | 0.266633E+10 | 0.277374E+09 |
July | 0.223335E+10 | 0.969863E+09 | 0.126349E+10 | 0.271235E+10 | 0.312426E+09 |
August | 0.231977E+10 | 0.127929E+10 | 0.104048E+10 | 0.276862E+10 | 0.473194E+09 |
September | 0.181830E+10 | 0.109723E+10 | 0.721067E+09 | 0.196351E+10 | 0.804569E+09 |
October | 0.135586E+10 | 0.862846E+09 | 0.493016E+09 | 0.126778E+10 | 0.130897E+10 |
November | 0.704973E+09 | 0.493802E+09 | 0.211171E+09 | 0.486868E+09 | 0.215787E+10 |
December | 0.129368E+09 | 91482228.09 | 37886262.73 | 26627609.04 | 0.262463E+10 |
Annual Sum or Average | 0.206441E+11 | 0.118300E+11 | 0.881412E+10 | 0.222451E+11 | 0.149676E+11 |
Minimum of Months | 0.129368E+09 | 91482228.09 | 37886262.73 | 26627609.04 | 0.277374E+09 |
Maximum of Months | 0.299152E+10 | 0.186308E+10 | 0.132670E+10 | 0.337030E+10 | 0.262463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431067E+09 | 0.285037E+09 | 0.146030E+09 | 0.266186E+09 | 0.234194E+10 |
February | 0.133915E+10 | 0.934194E+09 | 0.404956E+09 | 0.118421E+10 | 0.170668E+10 |
March | 0.253992E+10 | 0.172502E+10 | 0.814901E+09 | 0.259125E+10 | 0.146124E+10 |
April | 0.299152E+10 | 0.186308E+10 | 0.112844E+10 | 0.337030E+10 | 0.958917E+09 |
May | 0.253962E+10 | 0.131363E+10 | 0.122599E+10 | 0.294109E+10 | 0.539735E+09 |
June | 0.224119E+10 | 0.914485E+09 | 0.132670E+10 | 0.266633E+10 | 0.277374E+09 |
July | 0.223335E+10 | 0.969863E+09 | 0.126349E+10 | 0.271235E+10 | 0.312426E+09 |
August | 0.231977E+10 | 0.127929E+10 | 0.104048E+10 | 0.276862E+10 | 0.473194E+09 |
September | 0.181830E+10 | 0.109723E+10 | 0.721067E+09 | 0.196351E+10 | 0.804569E+09 |
October | 0.135586E+10 | 0.862846E+09 | 0.493016E+09 | 0.126778E+10 | 0.130897E+10 |
November | 0.704973E+09 | 0.493802E+09 | 0.211171E+09 | 0.486868E+09 | 0.215787E+10 |
December | 0.129368E+09 | 91482228.09 | 37886262.73 | 26627609.04 | 0.262463E+10 |
Annual Sum or Average | 0.206441E+11 | 0.118300E+11 | 0.881412E+10 | 0.222451E+11 | 0.149676E+11 |
Minimum of Months | 0.129368E+09 | 91482228.09 | 37886262.73 | 26627609.04 | 0.277374E+09 |
Maximum of Months | 0.299152E+10 | 0.186308E+10 | 0.132670E+10 | 0.337030E+10 | 0.262463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431039E+09 | 0.285019E+09 | 0.146020E+09 | 0.266169E+09 | 0.234179E+10 |
February | 0.133907E+10 | 0.934135E+09 | 0.404930E+09 | 0.118413E+10 | 0.170658E+10 |
March | 0.253976E+10 | 0.172491E+10 | 0.814849E+09 | 0.259109E+10 | 0.146115E+10 |
April | 0.299133E+10 | 0.186296E+10 | 0.112837E+10 | 0.337009E+10 | 0.958857E+09 |
May | 0.253946E+10 | 0.131355E+10 | 0.122591E+10 | 0.294090E+10 | 0.539700E+09 |
June | 0.224104E+10 | 0.914427E+09 | 0.132662E+10 | 0.266616E+10 | 0.277356E+09 |
July | 0.223321E+10 | 0.969802E+09 | 0.126341E+10 | 0.271218E+10 | 0.312407E+09 |
August | 0.231962E+10 | 0.127921E+10 | 0.104042E+10 | 0.276845E+10 | 0.473165E+09 |
September | 0.181818E+10 | 0.109716E+10 | 0.721022E+09 | 0.196338E+10 | 0.804518E+09 |
October | 0.135578E+10 | 0.862792E+09 | 0.492985E+09 | 0.126770E+10 | 0.130889E+10 |
November | 0.704928E+09 | 0.493771E+09 | 0.211157E+09 | 0.486838E+09 | 0.215773E+10 |
December | 0.129360E+09 | 91476446.93 | 37883868.53 | 26625926.32 | 0.262447E+10 |
Annual Sum or Average | 0.206428E+11 | 0.118292E+11 | 0.881357E+10 | 0.222437E+11 | 0.149666E+11 |
Minimum of Months | 0.129360E+09 | 91476446.93 | 37883868.53 | 26625926.32 | 0.277356E+09 |
Maximum of Months | 0.299133E+10 | 0.186296E+10 | 0.132662E+10 | 0.337009E+10 | 0.262447E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94379988.23 | 16233130.55 | 78146857.69 | 0.00 | 0.507329E+10 |
February | 0.504535E+09 | 0.173715E+09 | 0.330821E+09 | 0.109329E+09 | 0.387071E+10 |
March | 0.168357E+10 | 0.722693E+09 | 0.960879E+09 | 0.101840E+10 | 0.308356E+10 |
April | 0.387737E+10 | 0.201267E+10 | 0.186470E+10 | 0.384743E+10 | 0.175402E+10 |
May | 0.389630E+10 | 0.177851E+10 | 0.211779E+10 | 0.408183E+10 | 0.941984E+09 |
June | 0.413156E+10 | 0.176572E+10 | 0.236584E+10 | 0.468940E+10 | 0.490997E+09 |
July | 0.357057E+10 | 0.135354E+10 | 0.221703E+10 | 0.407831E+10 | 0.558363E+09 |
August | 0.293413E+10 | 0.124438E+10 | 0.168975E+10 | 0.316202E+10 | 0.861110E+09 |
September | 0.171738E+10 | 0.719680E+09 | 0.997697E+09 | 0.141634E+10 | 0.155182E+10 |
October | 0.692479E+09 | 0.206670E+09 | 0.485809E+09 | 0.260806E+09 | 0.283084E+10 |
November | 0.266966E+09 | 95726814.84 | 0.171239E+09 | 28814603.25 | 0.474131E+10 |
December | 24777092.81 | 2448507.06 | 22328585.75 | 0.00 | 0.542320E+10 |
Annual Sum or Average | 0.233940E+11 | 0.100920E+11 | 0.133020E+11 | 0.226927E+11 | 0.311812E+11 |
Minimum of Months | 24777092.81 | 2448507.06 | 22328585.75 | 0.00 | 0.490997E+09 |
Maximum of Months | 0.413156E+10 | 0.201267E+10 | 0.236584E+10 | 0.468940E+10 | 0.542320E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 3731689.67 | 641841.29 | 3089848.39 | 0.00 | 0.200593E+09 |
February | 19948822.89 | 6868508.39 | 13080314.50 | 4322734.27 | 0.153044E+09 |
March | 66566767.86 | 28574556.87 | 37992210.99 | 40266437.47 | 0.121921E+09 |
April | 0.153307E+09 | 79579087.00 | 73728338.57 | 0.152123E+09 | 69352444.77 |
May | 0.154056E+09 | 70320337.58 | 83735270.13 | 0.161391E+09 | 37245219.71 |
June | 0.163358E+09 | 69814733.93 | 93543143.14 | 0.185414E+09 | 19413573.84 |
July | 0.141177E+09 | 53517485.69 | 87659226.27 | 0.161252E+09 | 22077178.89 |
August | 0.116012E+09 | 49201345.84 | 66811020.47 | 0.125023E+09 | 34047512.84 |
September | 67903320.69 | 28455387.71 | 39447932.98 | 56000642.14 | 61357429.65 |
October | 27379904.01 | 8171502.04 | 19208401.96 | 10311965.01 | 0.111929E+09 |
November | 10555562.71 | 3784939.80 | 6770622.91 | 1139290.83 | 0.187467E+09 |
December | 979661.29 | 96811.45 | 882849.84 | 0.00 | 0.214428E+09 |
Annual Sum or Average | 0.924976E+09 | 0.399027E+09 | 0.525949E+09 | 0.897245E+09 | 0.123288E+10 |
Minimum of Months | 979661.29 | 96811.45 | 882849.84 | 0.00 | 19413573.84 |
Maximum of Months | 0.163358E+09 | 79579087.00 | 93543143.14 | 0.185414E+09 | 0.214428E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.810535E+10 |
February | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.656252E+10 |
March | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.106312E+09 | 0.539783E+10 |
April | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.882184E+09 | 0.283011E+10 |
May | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.269502E+10 | 0.131686E+10 |
June | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.439580E+10 | 0.587158E+09 |
July | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.389259E+10 | 0.742404E+09 |
August | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.200077E+10 | 0.125177E+10 |
September | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.469397E+09 | 0.248540E+10 |
October | 0.666103E+09 | 0.00 | 0.666103E+09 | 42577465.30 | 0.462845E+10 |
November | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.771098E+10 |
December | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.855009E+10 |
Annual Sum or Average | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.144846E+11 | 0.501689E+11 |
Minimum of Months | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.587158E+09 |
Maximum of Months | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.439580E+10 | 0.855009E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 16478669.22 | 0.523472E+10 |
February | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.499949E+09 | 0.395355E+10 |
March | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.253865E+10 | 0.323529E+10 |
April | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.368784E+10 | 0.174635E+10 |
May | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.658928E+10 | 0.954529E+09 |
June | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.606870E+10 | 0.451934E+09 |
July | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.610609E+10 | 0.536350E+09 |
August | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.461489E+10 | 0.845403E+09 |
September | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.228383E+10 | 0.156005E+10 |
October | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.960899E+09 | 0.281279E+10 |
November | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 21896446.83 | 0.494119E+10 |
December | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.565316E+10 |
Annual Sum or Average | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.333885E+11 | 0.319253E+11 |
Minimum of Months | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.451934E+09 |
Maximum of Months | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.658928E+10 | 0.565316E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.767471E+09 | 0.728467E+10 |
February | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.346579E+10 | 0.531078E+10 |
March | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.760013E+10 | 0.453366E+10 |
April | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.997599E+10 | 0.291458E+10 |
May | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.870381E+10 | 0.167291E+10 |
June | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.790730E+10 | 0.862503E+09 |
July | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.807123E+10 | 0.949252E+09 |
August | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.825505E+10 | 0.140348E+10 |
September | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.584171E+10 | 0.238473E+10 |
October | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.375980E+10 | 0.391478E+10 |
November | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.142131E+10 | 0.660710E+10 |
December | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 69065089.77 | 0.812948E+10 |
Annual Sum or Average | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.658387E+11 | 0.459679E+11 |
Minimum of Months | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 69065089.77 | 0.862503E+09 |
Maximum of Months | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.997599E+10 | 0.812948E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.534295E+10 |
February | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.108238E+09 | 0.411305E+10 |
March | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.101970E+10 | 0.330788E+10 |
April | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.392195E+10 | 0.187723E+10 |
May | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.416766E+10 | 0.102313E+10 |
June | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.482290E+10 | 0.531630E+09 |
July | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.420039E+10 | 0.595710E+09 |
August | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.326593E+10 | 0.894816E+09 |
September | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.146253E+10 | 0.160121E+10 |
October | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.267408E+09 | 0.292913E+10 |
November | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 29495852.41 | 0.493522E+10 |
December | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.567801E+10 |
Annual Sum or Average | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.232662E+11 | 0.328300E+11 |
Minimum of Months | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.531630E+09 |
Maximum of Months | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.482290E+10 | 0.567801E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2975.53 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2657.74 | 176.66 | 0.00 | 176.66 | 0.00 | 0.00 |
March | 42.93 | 1955.30 | 472.48 | 0.00 | 472.48 | 0.00 | 0.00 |
April | 355.99 | 1039.11 | 853.72 | 17.68 | 836.04 | 0.00 | 0.00 |
May | 1023.24 | 473.83 | 1306.08 | 204.17 | 1101.90 | 0.00 | 0.00 |
June | 1700.68 | 220.12 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
July | 1457.64 | 269.67 | 1431.90 | 230.38 | 1201.52 | 0.00 | 0.00 |
August | 756.70 | 449.01 | 914.28 | 49.35 | 864.93 | 0.00 | 0.00 |
September | 196.59 | 898.39 | 511.03 | 0.45 | 510.58 | 0.00 | 0.00 |
October | 20.57 | 1653.48 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2912.44 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3135.99 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 465.57 | 1547.44 | 648.20 | 73.60 | 574.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 220.12 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1700.68 | 3135.99 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.20 | 1925.51 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 209.92 | 1602.44 | 386.82 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 958.58 | 1170.62 | 1107.49 | 561.55 | 545.95 | 0.00 | 0.00 |
April | 1438.31 | 644.38 | 1523.07 | 771.86 | 751.22 | 0.00 | 0.00 |
May | 2469.54 | 344.93 | 2215.71 | 1250.43 | 965.29 | 0.00 | 0.00 |
June | 2345.95 | 169.84 | 2036.67 | 951.32 | 1085.34 | 0.00 | 0.00 |
July | 2283.85 | 195.17 | 1935.00 | 939.55 | 995.45 | 0.00 | 0.00 |
August | 1729.76 | 304.80 | 1532.21 | 746.91 | 785.31 | 0.00 | 0.00 |
September | 895.79 | 567.93 | 947.02 | 415.27 | 531.75 | 0.00 | 0.00 |
October | 368.21 | 1003.42 | 499.30 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.77 | 1869.56 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2078.97 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1065.32 | 986.70 | 1035.06 | 509.11 | 525.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 169.84 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2469.54 | 2078.97 | 2215.71 | 1250.43 | 1085.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 290.02 | 2673.05 | 482.83 | 319.27 | 163.57 | 0.00 | 0.00 |
February | 1445.10 | 2143.03 | 1660.68 | 1158.50 | 502.19 | 0.00 | 0.00 |
March | 2852.88 | 1637.32 | 2844.95 | 1932.19 | 912.76 | 0.00 | 0.00 |
April | 3862.73 | 1076.28 | 3462.47 | 2156.39 | 1306.08 | 0.00 | 0.00 |
May | 3255.24 | 599.39 | 2844.60 | 1471.39 | 1373.21 | 0.00 | 0.00 |
June | 3050.91 | 322.33 | 2594.00 | 1058.45 | 1535.55 | 0.00 | 0.00 |
July | 3013.67 | 343.71 | 2501.55 | 1086.34 | 1415.21 | 0.00 | 0.00 |
August | 3085.58 | 504.26 | 2598.35 | 1432.92 | 1165.43 | 0.00 | 0.00 |
September | 2270.77 | 869.94 | 2104.55 | 1269.97 | 834.58 | 0.00 | 0.00 |
October | 1422.89 | 1394.64 | 1518.69 | 966.47 | 552.22 | 0.00 | 0.00 |
November | 556.11 | 2489.54 | 815.96 | 571.54 | 244.41 | 0.00 | 0.00 |
December | 26.22 | 2981.61 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Annual Sum or Average | 2095.94 | 1416.17 | 1963.89 | 1125.40 | 838.49 | 0.00 | 0.00 |
Minimum of Months | 26.22 | 322.33 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Maximum of Months | 3862.73 | 2981.61 | 3462.47 | 2156.39 | 1535.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1963.43 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 45.76 | 1665.97 | 216.80 | 74.65 | 142.16 | 0.00 | 0.00 |
March | 385.19 | 1197.03 | 653.44 | 280.50 | 372.94 | 0.00 | 0.00 |
April | 1523.05 | 690.72 | 1555.07 | 807.21 | 747.86 | 0.00 | 0.00 |
May | 1561.58 | 365.60 | 1512.25 | 690.28 | 821.96 | 0.00 | 0.00 |
June | 1861.32 | 198.34 | 1657.01 | 708.17 | 948.85 | 0.00 | 0.00 |
July | 1568.88 | 215.39 | 1385.83 | 525.34 | 860.48 | 0.00 | 0.00 |
August | 1222.96 | 320.59 | 1138.81 | 482.97 | 655.83 | 0.00 | 0.00 |
September | 575.20 | 580.51 | 688.77 | 288.64 | 400.14 | 0.00 | 0.00 |
October | 105.13 | 1045.91 | 268.77 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 11.91 | 1864.92 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2085.67 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 741.32 | 1012.83 | 771.16 | 332.67 | 438.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 198.34 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1861.32 | 2085.67 | 1657.01 | 807.21 | 948.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2980.20 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2646.94 | 176.65 | 0.00 | 176.65 | 0.00 | 0.00 |
March | 46.34 | 1945.84 | 472.47 | 0.00 | 472.47 | 0.00 | 0.00 |
April | 387.61 | 1022.68 | 853.70 | 17.68 | 836.02 | 0.00 | 0.00 |
May | 1070.53 | 456.31 | 1306.05 | 204.17 | 1101.88 | 0.00 | 0.00 |
June | 1737.70 | 211.68 | 1706.61 | 377.35 | 1329.26 | 0.00 | 0.00 |
July | 1481.11 | 264.99 | 1431.86 | 230.37 | 1201.49 | 0.00 | 0.00 |
August | 761.93 | 456.83 | 914.25 | 49.34 | 864.91 | 0.00 | 0.00 |
September | 188.46 | 949.68 | 511.02 | 0.45 | 510.57 | 0.00 | 0.00 |
October | 16.88 | 1730.76 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2969.12 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3167.85 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 476.97 | 1561.08 | 648.19 | 73.60 | 574.59 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 211.68 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1737.70 | 3167.85 | 1706.61 | 377.35 | 1329.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.42 | 1930.81 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 211.51 | 1600.82 | 386.81 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 969.00 | 1174.19 | 1107.47 | 561.53 | 545.94 | 0.00 | 0.00 |
April | 1454.32 | 651.94 | 1523.05 | 771.84 | 751.21 | 0.00 | 0.00 |
May | 2486.62 | 348.91 | 2215.68 | 1250.40 | 965.27 | 0.00 | 0.00 |
June | 2363.61 | 169.17 | 2036.63 | 951.30 | 1085.33 | 0.00 | 0.00 |
July | 2294.76 | 198.73 | 1934.96 | 939.53 | 995.44 | 0.00 | 0.00 |
August | 1732.82 | 317.89 | 1532.19 | 746.89 | 785.29 | 0.00 | 0.00 |
September | 886.60 | 610.01 | 947.01 | 415.26 | 531.74 | 0.00 | 0.00 |
October | 361.43 | 1060.59 | 499.29 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.56 | 1905.33 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2097.83 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1070.40 | 1002.50 | 1035.05 | 509.10 | 525.94 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 169.17 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2486.62 | 2097.83 | 2215.68 | 1250.40 | 1085.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.14 | 2623.08 | 482.82 | 319.25 | 163.56 | 0.00 | 0.00 |
February | 1468.48 | 2116.38 | 1660.62 | 1158.45 | 502.17 | 0.00 | 0.00 |
March | 2902.33 | 1636.66 | 2844.83 | 1932.11 | 912.73 | 0.00 | 0.00 |
April | 3900.73 | 1109.83 | 3462.34 | 2156.30 | 1306.04 | 0.00 | 0.00 |
May | 3294.16 | 604.53 | 2844.50 | 1471.33 | 1373.17 | 0.00 | 0.00 |
June | 3085.96 | 321.03 | 2593.91 | 1058.41 | 1535.50 | 0.00 | 0.00 |
July | 3037.96 | 349.93 | 2501.46 | 1086.29 | 1415.16 | 0.00 | 0.00 |
August | 3100.99 | 530.00 | 2598.26 | 1432.87 | 1165.39 | 0.00 | 0.00 |
September | 2272.53 | 931.19 | 2104.47 | 1269.92 | 834.55 | 0.00 | 0.00 |
October | 1419.98 | 1466.11 | 1518.63 | 966.43 | 552.20 | 0.00 | 0.00 |
November | 563.49 | 2497.48 | 815.92 | 571.52 | 244.41 | 0.00 | 0.00 |
December | 29.82 | 2939.72 | 144.90 | 102.46 | 42.43 | 0.00 | 0.00 |
Annual Sum or Average | 2116.12 | 1423.82 | 1963.82 | 1125.35 | 838.46 | 0.00 | 0.00 |
Minimum of Months | 29.82 | 321.03 | 144.90 | 102.46 | 42.43 | 0.00 | 0.00 |
Maximum of Months | 3900.73 | 2939.72 | 3462.34 | 2156.30 | 1535.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1969.04 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 46.98 | 1663.26 | 216.80 | 74.65 | 142.15 | 0.00 | 0.00 |
March | 395.26 | 1196.79 | 653.43 | 280.49 | 372.94 | 0.00 | 0.00 |
April | 1543.04 | 703.46 | 1555.05 | 807.20 | 747.85 | 0.00 | 0.00 |
May | 1584.24 | 365.60 | 1512.23 | 690.27 | 821.95 | 0.00 | 0.00 |
June | 1880.71 | 196.92 | 1656.99 | 708.15 | 948.84 | 0.00 | 0.00 |
July | 1582.87 | 216.71 | 1385.81 | 525.33 | 860.47 | 0.00 | 0.00 |
August | 1227.24 | 334.21 | 1138.79 | 482.97 | 655.82 | 0.00 | 0.00 |
September | 568.03 | 622.37 | 688.77 | 288.63 | 400.13 | 0.00 | 0.00 |
October | 101.22 | 1098.70 | 268.76 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 11.56 | 1901.54 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2104.85 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 748.03 | 1027.84 | 771.15 | 332.67 | 438.48 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 196.92 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1880.71 | 2104.85 | 1656.99 | 807.20 | 948.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3026.19 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2712.68 | 176.66 | 0.00 | 176.66 | 0.00 | 0.00 |
March | 39.69 | 2015.32 | 472.48 | 0.00 | 472.48 | 0.00 | 0.00 |
April | 340.35 | 1091.86 | 853.72 | 17.68 | 836.04 | 0.00 | 0.00 |
May | 1006.21 | 491.66 | 1306.08 | 204.17 | 1101.90 | 0.00 | 0.00 |
June | 1695.91 | 226.53 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
July | 1453.33 | 277.18 | 1431.90 | 230.38 | 1201.52 | 0.00 | 0.00 |
August | 747.00 | 467.36 | 914.28 | 49.35 | 864.93 | 0.00 | 0.00 |
September | 181.09 | 958.87 | 511.03 | 0.45 | 510.58 | 0.00 | 0.00 |
October | 15.90 | 1728.07 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2974.92 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3192.24 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 459.31 | 1590.85 | 648.20 | 73.60 | 574.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 226.53 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1695.91 | 3192.24 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.15 | 1954.42 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 206.66 | 1634.24 | 386.82 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 947.82 | 1207.92 | 1107.49 | 561.55 | 545.95 | 0.00 | 0.00 |
April | 1422.78 | 673.74 | 1523.07 | 771.86 | 751.22 | 0.00 | 0.00 |
May | 2460.15 | 356.38 | 2215.71 | 1250.43 | 965.29 | 0.00 | 0.00 |
June | 2341.32 | 174.36 | 2036.67 | 951.32 | 1085.34 | 0.00 | 0.00 |
July | 2279.75 | 200.25 | 1935.00 | 939.55 | 995.45 | 0.00 | 0.00 |
August | 1723.00 | 315.64 | 1532.21 | 746.91 | 785.31 | 0.00 | 0.00 |
September | 881.11 | 601.87 | 947.02 | 415.27 | 531.75 | 0.00 | 0.00 |
October | 358.76 | 1050.18 | 499.30 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.45 | 1906.32 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2110.65 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1058.74 | 1012.35 | 1035.06 | 509.11 | 525.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 174.36 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2460.15 | 2110.65 | 2215.71 | 1250.43 | 1085.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.54 | 2719.78 | 482.83 | 319.27 | 163.57 | 0.00 | 0.00 |
February | 1432.62 | 2195.26 | 1660.68 | 1158.50 | 502.19 | 0.00 | 0.00 |
March | 2837.56 | 1692.67 | 2844.95 | 1932.19 | 912.76 | 0.00 | 0.00 |
April | 3848.76 | 1124.45 | 3462.47 | 2156.39 | 1306.08 | 0.00 | 0.00 |
May | 3249.63 | 624.59 | 2844.60 | 1471.39 | 1373.21 | 0.00 | 0.00 |
June | 3050.66 | 332.76 | 2594.00 | 1058.45 | 1535.55 | 0.00 | 0.00 |
July | 3013.45 | 354.41 | 2501.55 | 1086.34 | 1415.21 | 0.00 | 0.00 |
August | 3082.08 | 524.00 | 2598.35 | 1432.92 | 1165.43 | 0.00 | 0.00 |
September | 2253.74 | 920.04 | 2104.55 | 1269.97 | 834.58 | 0.00 | 0.00 |
October | 1403.75 | 1461.61 | 1518.69 | 966.47 | 552.22 | 0.00 | 0.00 |
November | 548.35 | 2549.04 | 815.96 | 571.54 | 244.41 | 0.00 | 0.00 |
December | 25.79 | 3035.20 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Annual Sum or Average | 2087.73 | 1457.63 | 1963.89 | 1125.40 | 838.49 | 0.00 | 0.00 |
Minimum of Months | 25.79 | 332.76 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Maximum of Months | 3848.76 | 3035.20 | 3462.47 | 2156.39 | 1535.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1994.83 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 44.74 | 1700.17 | 216.80 | 74.65 | 142.16 | 0.00 | 0.00 |
March | 380.71 | 1235.02 | 653.44 | 280.50 | 372.94 | 0.00 | 0.00 |
April | 1513.10 | 724.24 | 1555.07 | 807.21 | 747.86 | 0.00 | 0.00 |
May | 1556.03 | 381.99 | 1512.25 | 690.28 | 821.96 | 0.00 | 0.00 |
June | 1860.69 | 205.10 | 1657.01 | 708.17 | 948.85 | 0.00 | 0.00 |
July | 1568.25 | 222.41 | 1385.83 | 525.34 | 860.48 | 0.00 | 0.00 |
August | 1219.36 | 334.09 | 1138.81 | 482.97 | 655.83 | 0.00 | 0.00 |
September | 564.25 | 617.75 | 688.77 | 288.64 | 400.14 | 0.00 | 0.00 |
October | 99.84 | 1093.61 | 268.77 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 11.38 | 1904.02 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2119.93 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 737.77 | 1041.03 | 771.16 | 332.67 | 438.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 205.10 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1860.69 | 2119.93 | 1657.01 | 807.21 | 948.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.796966E+10 | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.00 |
February | 0.00 | 0.642962E+10 | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.00 |
March | 0.114988E+09 | 0.523707E+10 | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.00 | 0.00 |
April | 0.922736E+09 | 0.269337E+10 | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.00 | 0.00 |
May | 0.274065E+10 | 0.126910E+10 | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.00 | 0.00 |
June | 0.440816E+10 | 0.570554E+09 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
July | 0.390415E+10 | 0.722277E+09 | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.00 | 0.00 |
August | 0.202674E+10 | 0.120264E+10 | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.00 | 0.00 |
September | 0.509566E+09 | 0.232862E+10 | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.00 | 0.00 |
October | 55085622.62 | 0.442868E+10 | 0.666103E+09 | 0.00 | 0.666103E+09 | 0.00 | 0.00 |
November | 0.00 | 0.754906E+10 | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.00 |
December | 0.00 | 0.839944E+10 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.146821E+11 | 0.488001E+11 | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.570554E+09 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Maximum of Months | 0.440816E+10 | 0.839944E+10 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16605936.38 | 0.515730E+10 | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 0.00 | 0.00 |
February | 0.507835E+09 | 0.387663E+10 | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.00 | 0.00 |
March | 0.256745E+10 | 0.313539E+10 | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.00 | 0.00 |
April | 0.372811E+10 | 0.167023E+10 | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.00 | 0.00 |
May | 0.661442E+10 | 0.923865E+09 | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.00 | 0.00 |
June | 0.608071E+10 | 0.440232E+09 | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.00 | 0.00 |
July | 0.611706E+10 | 0.522731E+09 | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.00 | 0.00 |
August | 0.463299E+10 | 0.816381E+09 | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.00 | 0.00 |
September | 0.232189E+10 | 0.147208E+10 | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.00 | 0.00 |
October | 0.986216E+09 | 0.268755E+10 | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.00 | 0.00 |
November | 22728300.93 | 0.484589E+10 | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 0.00 | 0.00 |
December | 0.00 | 0.556832E+10 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Annual Sum or Average | 0.335960E+11 | 0.311166E+11 | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.440232E+09 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Maximum of Months | 0.661442E+10 | 0.556832E+10 | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.776790E+09 | 0.715950E+10 | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.00 | 0.00 |
February | 0.349599E+10 | 0.518441E+10 | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.00 | 0.00 |
March | 0.764114E+10 | 0.438541E+10 | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.00 | 0.00 |
April | 0.100122E+11 | 0.278972E+10 | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.00 | 0.00 |
May | 0.871883E+10 | 0.160540E+10 | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.00 | 0.00 |
June | 0.790796E+10 | 0.835469E+09 | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.00 | 0.00 |
July | 0.807180E+10 | 0.920602E+09 | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.00 | 0.00 |
August | 0.826441E+10 | 0.135060E+10 | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.00 | 0.00 |
September | 0.588583E+10 | 0.225489E+10 | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.00 | 0.00 |
October | 0.381107E+10 | 0.373542E+10 | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.00 | 0.00 |
November | 0.144145E+10 | 0.645288E+10 | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.00 | 0.00 |
December | 70222207.28 | 0.798596E+10 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.660977E+11 | 0.446603E+11 | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.00 | 0.00 |
Minimum of Months | 70222207.28 | 0.835469E+09 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100122E+11 | 0.798596E+10 | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.525886E+10 | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.00 |
February | 0.110692E+09 | 0.403030E+10 | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.00 | 0.00 |
March | 0.103169E+10 | 0.320612E+10 | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.00 | 0.00 |
April | 0.394774E+10 | 0.179035E+10 | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.00 | 0.00 |
May | 0.418255E+10 | 0.979230E+09 | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.00 | 0.00 |
June | 0.482454E+10 | 0.514098E+09 | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.00 | 0.00 |
July | 0.420209E+10 | 0.576903E+09 | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.00 | 0.00 |
August | 0.327557E+10 | 0.858681E+09 | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.00 | 0.00 |
September | 0.149091E+10 | 0.150469E+10 | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.00 | 0.00 |
October | 0.281576E+09 | 0.280137E+10 | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.00 | 0.00 |
November | 30883669.08 | 0.483388E+10 | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 0.00 | 0.00 |
December | 0.00 | 0.558625E+10 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.233782E+11 | 0.319407E+11 | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.514098E+09 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Maximum of Months | 0.482454E+10 | 0.558625E+10 | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.798218E+10 | 0.107036E+09 | 0.00 | 0.107036E+09 | 0.00 | 0.00 |
February | 0.00 | 0.640347E+10 | 0.427362E+09 | 0.00 | 0.427362E+09 | 0.00 | 0.00 |
March | 0.124118E+09 | 0.521174E+10 | 0.126548E+10 | 0.00 | 0.126548E+10 | 0.00 | 0.00 |
April | 0.100467E+10 | 0.265079E+10 | 0.221279E+10 | 45827845.76 | 0.216696E+10 | 0.00 | 0.00 |
May | 0.286731E+10 | 0.122219E+10 | 0.349811E+10 | 0.546845E+09 | 0.295127E+10 | 0.00 | 0.00 |
June | 0.450412E+10 | 0.548680E+09 | 0.442353E+10 | 0.978081E+09 | 0.344545E+10 | 0.00 | 0.00 |
July | 0.396700E+10 | 0.709755E+09 | 0.383510E+10 | 0.617022E+09 | 0.321808E+10 | 0.00 | 0.00 |
August | 0.204074E+10 | 0.122357E+10 | 0.244874E+10 | 0.132165E+09 | 0.231658E+10 | 0.00 | 0.00 |
September | 0.488486E+09 | 0.246156E+10 | 0.132457E+10 | 1167593.16 | 0.132340E+10 | 0.00 | 0.00 |
October | 45205336.25 | 0.463567E+10 | 0.666088E+09 | 0.00 | 0.666088E+09 | 0.00 | 0.00 |
November | 0.00 | 0.769596E+10 | 0.200043E+09 | 0.00 | 0.200043E+09 | 0.00 | 0.00 |
December | 0.00 | 0.848476E+10 | 32469099.83 | 0.00 | 32469099.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.150417E+11 | 0.492303E+11 | 0.204413E+11 | 0.232111E+10 | 0.181202E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.548680E+09 | 32469099.83 | 0.00 | 32469099.83 | 0.00 | 0.00 |
Maximum of Months | 0.450412E+10 | 0.848476E+10 | 0.442353E+10 | 0.978081E+09 | 0.344545E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17188712.31 | 0.517149E+10 | 0.186220E+09 | 57401391.31 | 0.128819E+09 | 0.00 | 0.00 |
February | 0.511689E+09 | 0.387270E+10 | 0.935775E+09 | 0.445316E+09 | 0.490460E+09 | 0.00 | 0.00 |
March | 0.259536E+10 | 0.314494E+10 | 0.296625E+10 | 0.150402E+10 | 0.146224E+10 | 0.00 | 0.00 |
April | 0.376959E+10 | 0.168983E+10 | 0.394774E+10 | 0.200062E+10 | 0.194712E+10 | 0.00 | 0.00 |
May | 0.666017E+10 | 0.934516E+09 | 0.593447E+10 | 0.334908E+10 | 0.258539E+10 | 0.00 | 0.00 |
June | 0.612647E+10 | 0.438479E+09 | 0.527895E+10 | 0.246578E+10 | 0.281317E+10 | 0.00 | 0.00 |
July | 0.614628E+10 | 0.532291E+09 | 0.518261E+10 | 0.251643E+10 | 0.266618E+10 | 0.00 | 0.00 |
August | 0.464118E+10 | 0.851434E+09 | 0.410382E+10 | 0.200048E+10 | 0.210333E+10 | 0.00 | 0.00 |
September | 0.229808E+10 | 0.158116E+10 | 0.245464E+10 | 0.107636E+10 | 0.137828E+10 | 0.00 | 0.00 |
October | 0.968059E+09 | 0.284069E+10 | 0.133731E+10 | 0.536208E+09 | 0.801099E+09 | 0.00 | 0.00 |
November | 22175392.84 | 0.493863E+10 | 0.273247E+09 | 94066125.08 | 0.179181E+09 | 0.00 | 0.00 |
December | 0.00 | 0.561883E+10 | 40150501.78 | 9222797.20 | 30927704.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.337562E+11 | 0.316150E+11 | 0.326412E+11 | 0.160550E+11 | 0.165862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.438479E+09 | 40150501.78 | 9222797.20 | 30927704.58 | 0.00 | 0.00 |
Maximum of Months | 0.666017E+10 | 0.561883E+10 | 0.593447E+10 | 0.334908E+10 | 0.281317E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.798542E+09 | 0.702566E+10 | 0.129317E+10 | 0.855092E+09 | 0.438080E+09 | 0.00 | 0.00 |
February | 0.355254E+10 | 0.511994E+10 | 0.401737E+10 | 0.280252E+10 | 0.121484E+10 | 0.00 | 0.00 |
March | 0.777360E+10 | 0.438364E+10 | 0.761960E+10 | 0.517495E+10 | 0.244465E+10 | 0.00 | 0.00 |
April | 0.101107E+11 | 0.287669E+10 | 0.897437E+10 | 0.558912E+10 | 0.338525E+10 | 0.00 | 0.00 |
May | 0.882307E+10 | 0.161917E+10 | 0.761871E+10 | 0.394082E+10 | 0.367789E+10 | 0.00 | 0.00 |
June | 0.799881E+10 | 0.832104E+09 | 0.672341E+10 | 0.274340E+10 | 0.398002E+10 | 0.00 | 0.00 |
July | 0.813688E+10 | 0.937259E+09 | 0.669991E+10 | 0.290953E+10 | 0.379038E+10 | 0.00 | 0.00 |
August | 0.830569E+10 | 0.141955E+10 | 0.695917E+10 | 0.383779E+10 | 0.312138E+10 | 0.00 | 0.00 |
September | 0.589040E+10 | 0.241365E+10 | 0.545478E+10 | 0.329163E+10 | 0.216316E+10 | 0.00 | 0.00 |
October | 0.380327E+10 | 0.392683E+10 | 0.406750E+10 | 0.258848E+10 | 0.147902E+10 | 0.00 | 0.00 |
November | 0.146057E+10 | 0.647346E+10 | 0.211487E+10 | 0.148137E+10 | 0.633498E+09 | 0.00 | 0.00 |
December | 79881144.39 | 0.787373E+10 | 0.388097E+09 | 0.274441E+09 | 0.113656E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.667340E+11 | 0.449017E+11 | 0.619310E+11 | 0.354891E+11 | 0.264418E+11 | 0.00 | 0.00 |
Minimum of Months | 79881144.39 | 0.832104E+09 | 0.388097E+09 | 0.274441E+09 | 0.113656E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101107E+11 | 0.787373E+10 | 0.897437E+10 | 0.558912E+10 | 0.398002E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.527388E+10 | 98111677.91 | 16874971.83 | 81236706.08 | 0.00 | 0.00 |
February | 0.113652E+09 | 0.402376E+10 | 0.524484E+09 | 0.180583E+09 | 0.343901E+09 | 0.00 | 0.00 |
March | 0.105867E+10 | 0.320548E+10 | 0.175014E+10 | 0.751268E+09 | 0.998871E+09 | 0.00 | 0.00 |
April | 0.399956E+10 | 0.182337E+10 | 0.403068E+10 | 0.209225E+10 | 0.193843E+10 | 0.00 | 0.00 |
May | 0.424322E+10 | 0.979230E+09 | 0.405035E+10 | 0.184883E+10 | 0.220152E+10 | 0.00 | 0.00 |
June | 0.487481E+10 | 0.510410E+09 | 0.429492E+10 | 0.183553E+10 | 0.245939E+10 | 0.00 | 0.00 |
July | 0.423957E+10 | 0.580440E+09 | 0.371175E+10 | 0.140706E+10 | 0.230469E+10 | 0.00 | 0.00 |
August | 0.328704E+10 | 0.895158E+09 | 0.305014E+10 | 0.129358E+10 | 0.175656E+10 | 0.00 | 0.00 |
September | 0.147234E+10 | 0.161317E+10 | 0.178528E+10 | 0.748135E+09 | 0.103714E+10 | 0.00 | 0.00 |
October | 0.271118E+09 | 0.294277E+10 | 0.719858E+09 | 0.214841E+09 | 0.505017E+09 | 0.00 | 0.00 |
November | 29953894.09 | 0.492878E+10 | 0.277522E+09 | 99511754.63 | 0.178010E+09 | 0.00 | 0.00 |
December | 0.00 | 0.563762E+10 | 25756754.09 | 2545318.51 | 23211435.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.235899E+11 | 0.324141E+11 | 0.243190E+11 | 0.104910E+11 | 0.138280E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.510410E+09 | 25756754.09 | 2545318.51 | 23211435.58 | 0.00 | 0.00 |
Maximum of Months | 0.487481E+10 | 0.563762E+10 | 0.429492E+10 | 0.209225E+10 | 0.245939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.810535E+10 | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.00 |
February | 0.00 | 0.656252E+10 | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.00 |
March | 0.106312E+09 | 0.539783E+10 | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.00 | 0.00 |
April | 0.882184E+09 | 0.283011E+10 | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.00 | 0.00 |
May | 0.269502E+10 | 0.131686E+10 | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.00 | 0.00 |
June | 0.439580E+10 | 0.587158E+09 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
July | 0.389259E+10 | 0.742404E+09 | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.00 | 0.00 |
August | 0.200077E+10 | 0.125177E+10 | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.00 | 0.00 |
September | 0.469397E+09 | 0.248540E+10 | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.00 | 0.00 |
October | 42577465.30 | 0.462845E+10 | 0.666103E+09 | 0.00 | 0.666103E+09 | 0.00 | 0.00 |
November | 0.00 | 0.771098E+10 | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.00 |
December | 0.00 | 0.855009E+10 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.144846E+11 | 0.501689E+11 | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.587158E+09 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Maximum of Months | 0.439580E+10 | 0.855009E+10 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16478669.22 | 0.523472E+10 | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 0.00 | 0.00 |
February | 0.499949E+09 | 0.395355E+10 | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.00 | 0.00 |
March | 0.253865E+10 | 0.323529E+10 | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.00 | 0.00 |
April | 0.368784E+10 | 0.174635E+10 | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.00 | 0.00 |
May | 0.658928E+10 | 0.954529E+09 | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.00 | 0.00 |
June | 0.606870E+10 | 0.451934E+09 | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.00 | 0.00 |
July | 0.610609E+10 | 0.536350E+09 | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.00 | 0.00 |
August | 0.461489E+10 | 0.845403E+09 | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.00 | 0.00 |
September | 0.228383E+10 | 0.156005E+10 | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.00 | 0.00 |
October | 0.960899E+09 | 0.281279E+10 | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.00 | 0.00 |
November | 21896446.83 | 0.494119E+10 | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 0.00 | 0.00 |
December | 0.00 | 0.565316E+10 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Annual Sum or Average | 0.333885E+11 | 0.319253E+11 | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.451934E+09 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Maximum of Months | 0.658928E+10 | 0.565316E+10 | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.767471E+09 | 0.728467E+10 | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.00 | 0.00 |
February | 0.346579E+10 | 0.531078E+10 | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.00 | 0.00 |
March | 0.760013E+10 | 0.453366E+10 | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.00 | 0.00 |
April | 0.997599E+10 | 0.291458E+10 | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.00 | 0.00 |
May | 0.870381E+10 | 0.167291E+10 | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.00 | 0.00 |
June | 0.790730E+10 | 0.862503E+09 | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.00 | 0.00 |
July | 0.807123E+10 | 0.949252E+09 | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.00 | 0.00 |
August | 0.825505E+10 | 0.140348E+10 | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.00 | 0.00 |
September | 0.584171E+10 | 0.238473E+10 | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.00 | 0.00 |
October | 0.375980E+10 | 0.391478E+10 | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.00 | 0.00 |
November | 0.142131E+10 | 0.660710E+10 | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.00 | 0.00 |
December | 69065089.77 | 0.812948E+10 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.658387E+11 | 0.459679E+11 | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.00 | 0.00 |
Minimum of Months | 69065089.77 | 0.862503E+09 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.997599E+10 | 0.812948E+10 | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.534295E+10 | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.00 |
February | 0.108238E+09 | 0.411305E+10 | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.00 | 0.00 |
March | 0.101970E+10 | 0.330788E+10 | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.00 | 0.00 |
April | 0.392195E+10 | 0.187723E+10 | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.00 | 0.00 |
May | 0.416766E+10 | 0.102313E+10 | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.00 | 0.00 |
June | 0.482290E+10 | 0.531630E+09 | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.00 | 0.00 |
July | 0.420039E+10 | 0.595710E+09 | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.00 | 0.00 |
August | 0.326593E+10 | 0.894816E+09 | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.00 | 0.00 |
September | 0.146253E+10 | 0.160121E+10 | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.00 | 0.00 |
October | 0.267408E+09 | 0.292913E+10 | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.00 | 0.00 |
November | 29495852.41 | 0.493522E+10 | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 0.00 | 0.00 |
December | 0.00 | 0.567801E+10 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.232662E+11 | 0.328300E+11 | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.531630E+09 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Maximum of Months | 0.482290E+10 | 0.567801E+10 | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.634938E+10 | -0.557266E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -776713101.6 | 58.99 | 0.00 | 0.00 |
February | 0.575527E+10 | -0.506458E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -690693144.1 | 58.98 | 0.00 | 0.00 |
March | 0.674231E+10 | -0.599669E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -745617765.4 | 58.99 | 0.00 | 0.00 |
April | 0.608569E+10 | -0.539548E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -690211214.7 | 58.98 | 0.00 | 0.00 |
May | 0.644015E+10 | -0.574472E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695426532.8 | 58.98 | 0.00 | 0.00 |
June | 0.616774E+10 | -0.549819E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669549128.3 | 58.99 | 0.00 | 0.00 |
July | 0.567338E+10 | -0.498391E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689465573.9 | 58.98 | 0.00 | 0.00 |
August | 0.607056E+10 | -0.537854E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692023941.3 | 58.98 | 0.00 | 0.00 |
September | 0.549985E+10 | -0.482436E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -675489384.2 | 58.98 | 0.00 | 0.00 |
October | 0.580844E+10 | -0.508128E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -727161456.2 | 58.98 | 0.00 | 0.00 |
November | 0.591418E+10 | -0.517718E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -736997378.2 | 58.98 | 0.00 | 0.00 |
December | 0.610475E+10 | -0.533404E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -770716126.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.726117E+11 | -0.640516E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.856006E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.549985E+10 | -0.599669E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -776713101.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.674231E+10 | -0.482436E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -669549128.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.61 | 0.48 | 10-JAN-10:00 | 628.12 | 11.79 | 5.83 | 65.33 | 539.44 | 22.88 | 45.50 | 42.33 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2627.31 | 32.59 | 169.33 | 172.00 | 2310.45 | 35.94 | 191.17 | 156.33 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5962.17 | 32.46 | 277.33 | 298.33 | 5205.57 | 33.91 | 286.67 | 281.17 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:30 | 8380.75 | 30.96 | 285.50 | 381.17 | 1682.82 | 21.17 | 255.50 | 337.83 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 4087.88 | 21.29 | 123.33 | 451.50 | 1214.76 | 19.90 | 272.83 | 393.33 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:10 | 1983.04 | 17.35 | 8.17 | 474.33 | 1105.06 | 19.65 | 286.00 | 409.17 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2362.03 | 17.96 | 23.00 | 471.33 | 1130.43 | 19.69 | 274.17 | 398.67 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:49 | 5983.27 | 26.49 | 248.17 | 404.83 | 1288.14 | 20.29 | 240.00 | 353.33 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4860.00 | 30.47 | 274.67 | 316.50 | 1697.09 | 21.83 | 198.67 | 278.83 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2695.35 | 31.14 | 222.50 | 234.33 | 2251.68 | 33.46 | 238.00 | 209.67 |
November | 135.83 | 0.55 | 0.48 | 01-NOV-09:00 | 931.72 | 21.39 | 55.83 | 116.67 | 847.59 | 31.80 | 105.17 | 90.67 |
December | 71.17 | 0.77 | 0.48 | 05-DEC-11:20 | 179.75 | 6.06 | 0.00 | 7.00 | 123.19 | 10.09 | 0.00 | 0.33 |
Annual Sum or Average | 4053.17 | 0.54 | 3998.16 | 24.28 | 1693.67 | 3393.33 | 1685.25 | 23.33 | 2393.67 | 2951.67 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 179.75 | 6.06 | 0.00 | 7.00 | 123.19 | 10.09 | 0.00 | 0.33 | |
Maximum of Months | 583.50 | 0.77 | 0.48 | 8380.75 | 32.59 | 285.50 | 474.33 | 5205.57 | 35.94 | 286.67 | 409.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.70 | 0.48 | 16-JAN-11:00 | 285.98 | 10.33 | 1.67 | 29.83 | 174.87 | 13.23 | 4.67 | 12.00 |
February | 205.83 | 0.59 | 0.48 | 01-FEB-12:20 | 938.97 | 16.95 | 45.67 | 140.00 | 637.64 | 21.56 | 79.83 | 96.83 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:20 | 2386.78 | 21.20 | 113.00 | 277.17 | 1552.97 | 23.76 | 154.17 | 238.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3087.86 | 22.83 | 135.50 | 385.17 | 1899.56 | 24.11 | 183.00 | 344.50 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4047.70 | 22.19 | 181.33 | 460.00 | 2129.07 | 23.33 | 195.50 | 417.33 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:39 | 3496.86 | 21.68 | 195.83 | 493.83 | 1563.95 | 22.22 | 203.33 | 434.83 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:49 | 3484.70 | 21.74 | 198.83 | 478.67 | 1823.58 | 22.84 | 215.17 | 424.67 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2868.91 | 21.06 | 146.67 | 406.50 | 1480.53 | 22.36 | 170.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2228.83 | 21.05 | 131.17 | 298.00 | 1172.91 | 22.16 | 141.33 | 252.17 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1176.10 | 19.69 | 95.50 | 209.50 | 690.70 | 20.70 | 83.00 | 151.67 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-09:00 | 388.22 | 15.83 | 33.83 | 67.00 | 228.87 | 18.34 | 35.83 | 19.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 97.58 | 6.08 | 0.00 | 0.00 | 56.81 | 8.43 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2720.71 | 20.57 | 1279.00 | 3245.67 | 1453.34 | 22.04 | 1466.00 | 2749.50 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 97.58 | 6.08 | 0.00 | 0.00 | 56.81 | 8.43 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 4047.70 | 22.83 | 198.83 | 493.83 | 2129.07 | 24.11 | 215.17 | 434.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.79 | 0.52 | 31-JAN-11:30 | 167.46 | 7.85 | 0.00 | 4.33 | 97.38 | 10.35 | 0.00 | 0.00 |
February | 205.83 | 0.62 | 0.48 | 11-FEB-12:20 | 368.20 | 12.17 | 0.00 | 106.50 | 216.92 | 14.68 | 0.00 | 23.17 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 677.10 | 15.55 | 0.00 | 268.83 | 401.64 | 17.91 | 7.00 | 196.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:40 | 891.96 | 17.88 | 0.00 | 394.33 | 553.01 | 20.22 | 56.50 | 337.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1100.12 | 21.51 | 130.33 | 498.50 | 657.34 | 23.68 | 215.17 | 467.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1305.26 | 21.93 | 153.33 | 535.00 | 760.31 | 24.31 | 297.17 | 499.33 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1185.97 | 21.59 | 140.67 | 516.17 | 673.50 | 22.89 | 231.00 | 463.67 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 919.26 | 19.42 | 64.17 | 422.17 | 525.60 | 19.68 | 71.17 | 360.50 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 661.48 | 15.64 | 0.00 | 293.33 | 382.37 | 17.86 | 5.17 | 198.33 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-08:09 | 461.32 | 13.61 | 0.00 | 186.00 | 256.46 | 15.89 | 0.00 | 29.67 |
November | 135.83 | 0.73 | 0.48 | 01-NOV-13:30 | 223.61 | 9.68 | 0.00 | 23.33 | 128.30 | 12.40 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.77 | 04-DEC-11:30 | 66.17 | 3.36 | 0.00 | 0.00 | 38.84 | 5.50 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 874.56 | 17.89 | 488.50 | 3248.50 | 511.18 | 19.84 | 883.17 | 2575.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 66.17 | 3.36 | 0.00 | 0.00 | 38.84 | 5.50 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.77 | 1305.26 | 21.93 | 153.33 | 535.00 | 760.31 | 24.31 | 297.17 | 499.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.72 | 0.48 | 23-JAN-13:20 | 241.30 | 9.89 | 1.67 | 20.67 | 144.92 | 12.74 | 1.83 | 4.17 |
February | 205.83 | 0.56 | 0.48 | 02-FEB-11:09 | 802.73 | 19.52 | 61.50 | 151.17 | 497.05 | 21.80 | 69.83 | 82.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1800.71 | 20.96 | 97.83 | 288.17 | 1090.89 | 23.20 | 118.33 | 252.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3478.80 | 22.73 | 139.50 | 384.67 | 1768.81 | 22.76 | 148.50 | 343.33 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2761.43 | 19.46 | 117.83 | 479.17 | 1380.71 | 20.19 | 78.33 | 433.33 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2919.10 | 18.89 | 111.33 | 506.17 | 1480.15 | 19.90 | 79.17 | 451.50 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2527.98 | 18.82 | 114.50 | 498.17 | 1311.24 | 19.78 | 90.00 | 437.83 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2292.88 | 20.07 | 117.50 | 419.83 | 1387.76 | 21.65 | 121.00 | 371.83 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:00 | 1830.48 | 21.90 | 120.17 | 312.83 | 1112.14 | 22.95 | 114.17 | 256.83 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 920.17 | 19.46 | 82.67 | 214.83 | 531.89 | 20.85 | 65.50 | 137.50 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-10:30 | 374.94 | 15.40 | 33.83 | 64.50 | 250.34 | 20.06 | 45.17 | 24.33 |
December | 71.17 | 0.90 | 0.71 | 04-DEC-11:30 | 84.88 | 5.41 | 0.00 | 0.00 | 48.96 | 7.76 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2197.80 | 19.40 | 998.33 | 3340.17 | 1184.54 | 20.72 | 931.83 | 2795.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 84.88 | 5.41 | 0.00 | 0.00 | 48.96 | 7.76 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.71 | 3478.80 | 22.73 | 139.50 | 506.17 | 1768.81 | 23.20 | 148.50 | 451.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.62 | 0.48 | 10-JAN-10:00 | 571.03 | 7.16 | 5.50 | 61.33 | 434.82 | 11.81 | 6.00 | 38.17 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2456.01 | 29.41 | 153.17 | 168.50 | 2214.90 | 35.68 | 190.50 | 154.50 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5783.24 | 31.76 | 272.33 | 297.00 | 5074.25 | 33.50 | 281.00 | 279.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 8215.56 | 29.76 | 283.67 | 378.33 | 1557.11 | 18.46 | 33.00 | 332.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 3977.66 | 18.43 | 114.67 | 447.00 | 1133.74 | 17.35 | 12.67 | 389.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:19 | 1886.72 | 13.48 | 0.00 | 470.67 | 1037.98 | 17.01 | 9.83 | 403.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2262.85 | 14.19 | 15.67 | 467.33 | 1060.15 | 17.01 | 11.83 | 394.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 5863.49 | 24.67 | 238.50 | 402.00 | 1198.87 | 17.50 | 12.33 | 349.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4728.88 | 29.45 | 267.17 | 314.83 | 1602.68 | 19.12 | 39.50 | 274.33 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2544.99 | 28.57 | 204.50 | 231.50 | 2174.45 | 32.70 | 232.00 | 208.50 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 693.64 | 7.78 | 0.00 | 112.00 | 783.61 | 28.40 | 94.17 | 84.83 |
December | 71.17 | 0.79 | 0.48 | 05-DEC-11:30 | 164.36 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 3870.30 | 21.36 | 1555.17 | 3354.83 | 1597.60 | 20.81 | 922.83 | 2908.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 164.36 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.79 | 0.48 | 8215.56 | 31.76 | 283.67 | 470.67 | 5074.25 | 35.68 | 281.00 | 403.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 16-JAN-12:09 | 274.91 | 9.69 | 1.67 | 26.67 | 167.26 | 12.88 | 2.17 | 10.50 |
February | 205.83 | 0.59 | 0.48 | 02-FEB-10:09 | 904.49 | 16.44 | 45.67 | 137.83 | 611.40 | 21.34 | 76.83 | 92.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 2308.03 | 20.76 | 112.67 | 275.17 | 1427.40 | 22.14 | 127.83 | 234.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:00 | 2908.42 | 20.71 | 109.67 | 382.00 | 1827.71 | 23.91 | 172.33 | 340.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 3949.61 | 21.76 | 181.33 | 457.50 | 2050.65 | 23.15 | 184.00 | 413.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:49 | 3409.86 | 21.22 | 194.83 | 491.00 | 1497.87 | 22.01 | 183.00 | 431.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:00 | 3362.23 | 20.41 | 173.00 | 476.33 | 1749.34 | 22.08 | 184.17 | 419.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2788.24 | 20.61 | 146.17 | 404.50 | 1417.89 | 22.17 | 151.00 | 354.17 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2138.16 | 20.38 | 128.00 | 294.50 | 1122.92 | 21.95 | 134.83 | 247.83 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1078.20 | 17.57 | 73.17 | 207.00 | 663.02 | 20.47 | 81.00 | 147.67 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-09:00 | 374.43 | 15.30 | 33.83 | 63.50 | 219.25 | 18.08 | 35.17 | 16.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2626.65 | 19.68 | 1200.00 | 3216.00 | 1389.96 | 21.64 | 1332.33 | 2708.00 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 3949.61 | 21.76 | 194.83 | 491.00 | 2050.65 | 23.91 | 184.17 | 431.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.80 | 0.52 | 31-JAN-11:30 | 159.74 | 4.04 | 0.00 | 2.67 | 93.01 | 7.46 | 0.00 | 0.00 |
February | 205.83 | 0.63 | 0.48 | 12-FEB-11:30 | 352.51 | 8.25 | 0.00 | 98.83 | 208.16 | 11.95 | 0.00 | 18.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 650.76 | 11.93 | 0.00 | 264.83 | 387.13 | 15.55 | 0.00 | 186.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 857.77 | 14.48 | 0.00 | 392.67 | 534.62 | 18.22 | 1.83 | 331.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1059.99 | 18.88 | 128.67 | 496.83 | 634.19 | 21.97 | 133.67 | 464.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1257.46 | 19.27 | 150.00 | 532.50 | 730.92 | 22.48 | 152.50 | 495.17 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:00 | 1142.89 | 18.94 | 137.00 | 514.50 | 646.95 | 20.45 | 105.50 | 458.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 885.48 | 16.33 | 62.33 | 419.83 | 527.69 | 19.56 | 68.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 636.51 | 11.96 | 0.00 | 290.00 | 368.43 | 15.50 | 0.00 | 185.67 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 443.75 | 9.55 | 0.00 | 179.00 | 246.38 | 13.15 | 0.00 | 23.67 |
November | 135.83 | 0.74 | 0.48 | 06-NOV-13:09 | 213.77 | 5.54 | 0.00 | 18.83 | 122.71 | 9.37 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 62.92 | 0.81 | 0.00 | 0.00 | 37.00 | 3.10 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 841.97 | 14.71 | 478.00 | 3210.50 | 494.62 | 17.85 | 461.67 | 2521.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 62.92 | 0.81 | 0.00 | 0.00 | 37.00 | 3.10 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 1257.46 | 19.27 | 150.00 | 532.50 | 730.92 | 22.48 | 152.50 | 495.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 23-JAN-13:20 | 232.25 | 9.37 | 1.33 | 18.83 | 138.78 | 12.72 | 1.83 | 3.50 |
February | 205.83 | 0.57 | 0.48 | 02-FEB-11:20 | 735.63 | 16.69 | 44.67 | 146.50 | 477.88 | 21.72 | 70.00 | 77.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1742.06 | 20.48 | 96.17 | 286.33 | 1024.83 | 21.95 | 103.67 | 246.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3391.46 | 22.31 | 139.50 | 383.00 | 1701.11 | 22.62 | 145.00 | 339.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2690.88 | 18.99 | 117.83 | 475.67 | 1324.73 | 20.02 | 75.33 | 428.83 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2847.77 | 18.40 | 111.33 | 502.67 | 1424.23 | 19.71 | 70.00 | 446.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2453.06 | 18.35 | 114.50 | 492.33 | 1261.54 | 19.60 | 83.83 | 432.00 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:19 | 2219.41 | 19.43 | 114.50 | 416.83 | 1339.98 | 21.49 | 117.17 | 366.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 1748.20 | 20.01 | 103.67 | 310.33 | 1073.49 | 22.82 | 112.33 | 253.17 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 893.19 | 19.08 | 82.50 | 211.67 | 511.77 | 20.74 | 65.17 | 127.33 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-10:39 | 360.23 | 15.03 | 33.83 | 61.00 | 239.82 | 20.02 | 45.33 | 22.83 |
December | 71.17 | 0.90 | 0.72 | 04-DEC-11:30 | 81.49 | 5.13 | 0.00 | 0.00 | 46.73 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2132.11 | 18.68 | 959.83 | 3305.17 | 1137.89 | 20.48 | 889.67 | 2742.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 81.49 | 5.13 | 0.00 | 0.00 | 46.73 | 7.83 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.72 | 3391.46 | 22.31 | 139.50 | 502.67 | 1701.11 | 22.82 | 145.00 | 446.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.62 | 0.48 | 10-JAN-10:00 | 571.05 | 7.16 | 5.50 | 61.33 | 434.81 | 11.81 | 6.00 | 38.17 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2456.05 | 29.41 | 153.17 | 168.50 | 2214.86 | 35.68 | 190.50 | 154.50 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5783.23 | 31.76 | 272.33 | 297.00 | 5074.15 | 33.50 | 281.00 | 279.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 8215.50 | 29.76 | 283.67 | 378.33 | 1557.00 | 18.46 | 33.00 | 332.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 3977.57 | 18.43 | 114.67 | 447.00 | 1133.65 | 17.35 | 12.83 | 389.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:19 | 1886.61 | 13.48 | 0.00 | 470.67 | 1037.90 | 17.01 | 9.83 | 403.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2262.74 | 14.19 | 15.67 | 467.33 | 1060.06 | 17.01 | 11.83 | 394.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 5863.40 | 24.67 | 238.50 | 402.00 | 1198.77 | 17.50 | 12.33 | 349.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4728.84 | 29.45 | 267.17 | 314.83 | 1602.59 | 19.12 | 39.50 | 274.33 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2544.97 | 28.57 | 204.50 | 231.50 | 2174.40 | 32.71 | 232.00 | 208.50 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 693.67 | 7.78 | 0.00 | 112.00 | 783.59 | 28.40 | 94.17 | 84.83 |
December | 71.17 | 0.79 | 0.48 | 05-DEC-11:30 | 164.37 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 3870.24 | 21.36 | 1555.17 | 3354.83 | 1597.52 | 20.81 | 923.00 | 2908.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 164.37 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.79 | 0.48 | 8215.50 | 31.76 | 283.67 | 470.67 | 5074.15 | 35.68 | 281.00 | 403.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 16-JAN-12:09 | 274.91 | 9.69 | 1.67 | 26.67 | 167.25 | 12.88 | 2.17 | 10.50 |
February | 205.83 | 0.59 | 0.48 | 02-FEB-10:09 | 904.48 | 16.44 | 45.67 | 137.83 | 611.37 | 21.34 | 76.83 | 92.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 2308.02 | 20.76 | 112.67 | 275.17 | 1427.35 | 22.14 | 127.83 | 234.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:00 | 2908.41 | 20.72 | 109.67 | 382.00 | 1827.65 | 23.91 | 172.33 | 340.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 3949.58 | 21.76 | 181.33 | 457.50 | 2050.57 | 23.16 | 184.00 | 413.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:49 | 3410.55 | 21.26 | 195.83 | 491.00 | 1497.79 | 22.01 | 183.00 | 431.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:00 | 3396.93 | 21.33 | 198.17 | 476.33 | 1749.26 | 22.08 | 184.17 | 419.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2788.20 | 20.61 | 146.17 | 404.50 | 1417.82 | 22.17 | 151.17 | 354.17 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2138.13 | 20.38 | 128.00 | 294.50 | 1122.87 | 21.95 | 134.83 | 247.83 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1078.18 | 17.57 | 73.17 | 207.00 | 662.98 | 20.47 | 81.00 | 147.50 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-09:00 | 374.43 | 15.31 | 33.83 | 63.50 | 219.24 | 18.08 | 35.17 | 16.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2631.55 | 19.82 | 1226.17 | 3216.00 | 1389.90 | 21.64 | 1332.50 | 2707.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 3949.58 | 21.76 | 198.17 | 491.00 | 2050.57 | 23.91 | 184.17 | 431.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.80 | 0.52 | 31-JAN-11:30 | 159.74 | 4.04 | 0.00 | 2.67 | 93.00 | 7.47 | 0.00 | 0.00 |
February | 205.83 | 0.63 | 0.48 | 12-FEB-11:30 | 352.51 | 8.25 | 0.00 | 98.83 | 208.14 | 11.95 | 0.00 | 18.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 650.74 | 11.93 | 0.00 | 264.83 | 387.10 | 15.55 | 0.00 | 186.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 857.76 | 14.49 | 0.00 | 392.67 | 534.59 | 18.22 | 1.83 | 331.33 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1059.97 | 18.88 | 128.67 | 496.83 | 634.15 | 21.97 | 133.67 | 464.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1257.43 | 19.27 | 150.00 | 532.50 | 730.88 | 22.48 | 152.50 | 495.17 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:00 | 1142.86 | 18.94 | 137.00 | 514.50 | 646.90 | 20.45 | 105.50 | 458.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 885.45 | 16.34 | 62.33 | 419.83 | 527.66 | 19.57 | 68.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 636.49 | 11.96 | 0.00 | 290.00 | 368.40 | 15.50 | 0.00 | 185.67 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 443.73 | 9.55 | 0.00 | 179.00 | 246.36 | 13.15 | 0.00 | 23.67 |
November | 135.83 | 0.74 | 0.48 | 06-NOV-13:09 | 213.76 | 5.55 | 0.00 | 18.83 | 122.70 | 9.37 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 62.92 | 0.81 | 0.00 | 0.00 | 36.99 | 3.10 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 841.95 | 14.71 | 478.00 | 3210.50 | 494.59 | 17.85 | 461.67 | 2521.17 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 62.92 | 0.81 | 0.00 | 0.00 | 36.99 | 3.10 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 1257.43 | 19.27 | 150.00 | 532.50 | 730.88 | 22.48 | 152.50 | 495.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 23-JAN-13:20 | 232.25 | 9.38 | 1.33 | 18.83 | 138.77 | 12.72 | 1.83 | 3.50 |
February | 205.83 | 0.57 | 0.48 | 02-FEB-11:20 | 735.62 | 16.70 | 44.67 | 146.50 | 477.86 | 21.72 | 70.00 | 77.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1742.04 | 20.49 | 96.17 | 286.33 | 1024.79 | 21.95 | 103.67 | 246.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3391.45 | 22.31 | 139.50 | 383.00 | 1701.04 | 22.62 | 145.17 | 339.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2690.85 | 18.99 | 117.83 | 475.67 | 1324.67 | 20.02 | 75.33 | 428.83 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2847.72 | 18.40 | 111.33 | 502.67 | 1424.16 | 19.71 | 70.00 | 446.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2453.01 | 18.35 | 114.50 | 492.33 | 1261.48 | 19.60 | 83.83 | 432.00 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:19 | 2219.37 | 19.43 | 114.50 | 416.83 | 1339.92 | 21.49 | 117.50 | 365.83 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 1748.17 | 20.01 | 103.67 | 310.33 | 1073.44 | 22.82 | 112.33 | 253.17 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 893.17 | 19.08 | 82.50 | 211.67 | 511.74 | 20.74 | 65.17 | 127.33 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-10:39 | 360.22 | 15.03 | 33.83 | 61.00 | 239.81 | 20.02 | 45.33 | 22.83 |
December | 71.17 | 0.90 | 0.72 | 04-DEC-11:30 | 81.48 | 5.13 | 0.00 | 0.00 | 46.72 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2132.08 | 18.68 | 959.83 | 3305.17 | 1137.84 | 20.48 | 890.17 | 2742.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 81.48 | 5.13 | 0.00 | 0.00 | 46.72 | 7.83 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.72 | 3391.45 | 22.31 | 139.50 | 502.67 | 1701.04 | 22.82 | 145.17 | 446.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.282649E+10 | 20964.30 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.969601E+09 | 20964.30 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129357E+09 | 20964.30 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14467360.21 | 20964.30 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.701723E+09 | 20964.30 | 06-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151696E+10 | 20964.30 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.615860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282649E+10 | 20964.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167559E+11 | 15053.51 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116176E+11 | 15051.45 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.884028E+10 | 14995.88 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281482E+10 | 14978.36 | 28-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.833266E+09 | 15221.12 | 19-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179247E+09 | 14489.07 | 02-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127100E+09 | 13602.02 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.379330E+09 | 15230.90 | 21-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172193E+10 | 15105.25 | 05-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592743E+10 | 15033.44 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135555E+11 | 15059.12 | 21-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168916E+11 | 15064.56 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.796439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.127100E+09 | 13602.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168916E+11 | 15230.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.640788E+10 | 9631.38 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.456248E+10 | 9654.76 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228960E+10 | 9621.94 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389910E+09 | 9568.12 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15142560.39 | 7347.65 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105671E+10 | 9629.73 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.427676E+10 | 9634.82 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584600E+10 | 9629.24 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.640788E+10 | 9654.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.916059E+10 | 7339.82 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.738320E+10 | 7337.57 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.578399E+10 | 7315.89 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134327E+10 | 7300.87 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77268369.65 | 7285.02 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211193E+10 | 7329.37 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.641732E+10 | 7344.19 | 21-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.839926E+10 | 7346.63 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.916059E+10 | 7346.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.651295E+10 | 10067.43 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497187E+10 | 10085.99 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323008E+10 | 10057.56 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435574E+09 | 10001.33 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29307863.90 | 8365.97 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130213E+10 | 10065.71 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.427456E+10 | 10071.05 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.586411E+10 | 10065.19 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.651295E+10 | 10085.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.652413E+10 | 23415.13 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378284E+10 | 23415.13 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136499E+10 | 23415.13 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135644E+09 | 23415.13 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.955400E+09 | 23415.13 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444462E+10 | 23415.13 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608778E+10 | 23415.13 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.652413E+10 | 23415.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.682400E+10 | 14922.27 | 01-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349945E+10 | 14922.27 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164735E+10 | 14922.27 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282824E+09 | 14922.27 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37664852.67 | 13508.00 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140762E+10 | 14922.27 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480719E+10 | 14922.27 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.720533E+10 | 14922.27 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.720533E+10 | 14922.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.504474E+10 | 9877.44 | 01-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297602E+10 | 9877.44 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134298E+10 | 9877.44 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220612E+09 | 9877.44 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32165820.82 | 8655.78 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114292E+10 | 9877.44 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386384E+10 | 9877.44 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.501045E+10 | 9877.44 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504474E+10 | 9877.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.767724E+10 | 8361.76 | 24-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.529113E+10 | 8344.98 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342857E+10 | 8365.48 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.588631E+09 | 8341.17 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84671795.79 | 8257.26 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221444E+10 | 8373.59 | 11-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.600024E+10 | 8361.97 | 14-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747821E+10 | 8342.56 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.767724E+10 | 8373.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.516969E+10 | 9836.84 | 01-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334417E+10 | 9836.84 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189062E+10 | 9836.84 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.275362E+09 | 9836.84 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45360194.41 | 8674.20 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138439E+10 | 9836.84 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390891E+10 | 9836.84 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.505613E+10 | 9836.84 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516969E+10 | 9836.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139850E+11 | 29634.50 | 21-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.920816E+10 | 29733.01 | 17-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.544459E+10 | 29693.95 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103354E+10 | 29630.23 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129350E+09 | 29218.00 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.421918E+10 | 29704.25 | 10-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116504E+11 | 29652.27 | 10-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139910E+11 | 29626.40 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.596613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139910E+11 | 29733.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100901E+11 | 18485.66 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585722E+10 | 18546.75 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325484E+10 | 18446.13 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.787010E+09 | 18410.56 | 08-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3011604.21 | 3835.30 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2595530.59 | 2932.34 | 30-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.221892E+09 | 18345.31 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291183E+10 | 18551.66 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.792654E+10 | 18498.52 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108936E+11 | 18497.52 | 27-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108936E+11 | 18551.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.729382E+10 | 11824.62 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.482061E+10 | 11863.87 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251120E+10 | 11877.73 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.565763E+09 | 11809.99 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1147996.59 | 4039.82 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156937E+09 | 11735.01 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230363E+10 | 11866.89 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.615257E+10 | 11833.22 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747956E+10 | 11832.21 | 27-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.312852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.747956E+10 | 11877.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109227E+11 | 8899.11 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.806994E+10 | 8928.81 | 17-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566642E+10 | 8915.62 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137018E+10 | 8897.46 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3024277.09 | 2518.18 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5450648.53 | 8176.38 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.420321E+09 | 8873.85 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.421842E+10 | 8919.54 | 20-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.932235E+10 | 8904.35 | 10-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110206E+11 | 8895.01 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110206E+11 | 8928.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.739475E+10 | 12192.06 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520954E+10 | 12232.54 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329652E+10 | 12146.17 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.696147E+09 | 12142.78 | 08-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3215010.32 | 3288.32 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3028989.15 | 2670.93 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229658E+09 | 12099.67 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264075E+10 | 12235.65 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.615737E+10 | 12200.94 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749697E+10 | 12199.89 | 27-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.749697E+10 | 12235.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153887E+11 | 57959.78 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.900671E+10 | 54087.18 | 27-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296266E+10 | 47573.25 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97738698.41 | 9535.07 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30784346.16 | 5388.52 | 16-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1968741.57 | 1260.55 | 17-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15141586.66 | 7809.78 | 31-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36612498.29 | 4154.98 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.461949E+09 | 5425.99 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134067E+11 | 49189.86 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210788E+11 | 55261.00 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.210788E+11 | 57959.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140577E+11 | 56353.92 | 12-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.833994E+10 | 51294.90 | 27-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300474E+10 | 46115.08 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154115E+09 | 9703.52 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24720763.57 | 5979.05 | 05-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1190318.77 | 2894.70 | 01-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 820477.94 | 852.18 | 05-JUL-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10430250.88 | 3003.78 | 28-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20410814.11 | 4235.93 | 28-SEP-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.743199E+09 | 5561.87 | 11-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124745E+11 | 46454.32 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187598E+11 | 53657.97 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 820477.94 | 852.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187598E+11 | 56353.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185225E+11 | 58469.79 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113434E+11 | 48546.86 | 27-FEB-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469234E+10 | 47171.52 | 01-MAR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.427127E+09 | 10909.82 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20857556.79 | 6807.10 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2028046.22 | 4392.53 | 07-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 824594.61 | 1895.56 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7973576.30 | 3550.67 | 28-AUG-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50789531.56 | 4930.51 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169800E+10 | 8427.34 | 31-OCT-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163956E+11 | 47372.08 | 29-NOV-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235538E+11 | 53521.55 | 15-DEC-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 824594.61 | 1895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.235538E+11 | 58469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4226504.06 | 4225113.22 | 6799.50 | 20-JAN-07:01 | 6799.50 | 0.00 |
February | 0.00 | 0.00 | 6740761.87 | 6602952.19 | 6980.33 | 08-FEB-07:01 | 6980.33 | 0.00 |
March | 0.00 | 0.00 | 11015751.40 | 10851137.58 | 6900.42 | 07-MAR-07:01 | 6900.42 | 0.00 |
April | 0.00 | 0.00 | 0.287867E+09 | 0.287728E+09 | 14914.86 | 28-APR-15:20 | 14914.86 | 0.00 |
May | 0.00 | 0.00 | 0.433342E+10 | 0.431629E+10 | 30692.92 | 31-MAY-16:00 | 30692.92 | 0.00 |
June | 0.00 | 0.00 | 0.173779E+11 | 0.166127E+11 | 54429.70 | 30-JUN-12:20 | 47269.99 | 0.00 |
July | 0.00 | 0.00 | 0.249860E+11 | 0.229914E+11 | 56040.61 | 11-JUL-15:50 | 52640.52 | 0.00 |
August | 0.00 | 0.00 | 0.142107E+11 | 0.132008E+11 | 52118.68 | 11-AUG-15:50 | 52118.68 | 0.00 |
September | 0.00 | 0.00 | 0.231676E+10 | 0.218700E+10 | 22251.60 | 08-SEP-16:00 | 22251.60 | 0.00 |
October | 0.00 | 0.00 | 15829279.10 | 14928111.38 | 3864.87 | 31-OCT-06:01 | 3864.87 | 0.00 |
November | 0.00 | 0.00 | 3087713.49 | 3083737.81 | 4991.94 | 16-NOV-07:01 | 4991.94 | 0.00 |
December | 0.00 | 0.00 | 2633150.16 | 2633150.16 | 5277.07 | 21-DEC-07:01 | 5277.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.635563E+11 | 0.596382E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2633150.16 | 2633150.16 | 3864.87 | 3864.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.249860E+11 | 0.229914E+11 | 56040.61 | 52640.52 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3698763.05 | 3698763.05 | 6039.65 | 20-JAN-07:01 | 6039.65 | 0.00 |
February | 0.00 | 0.00 | 5255390.69 | 5222723.75 | 7825.63 | 09-FEB-07:02 | 7825.63 | 0.00 |
March | 0.00 | 0.00 | 10460031.97 | 10332968.11 | 9061.45 | 21-MAR-06:01 | 9061.45 | 0.00 |
April | 0.00 | 0.00 | 98119711.25 | 97965727.88 | 6246.40 | 05-APR-06:01 | 6246.40 | 0.00 |
May | 0.00 | 0.00 | 0.387394E+10 | 0.386398E+10 | 34614.16 | 31-MAY-16:00 | 34614.16 | 0.00 |
June | 0.00 | 0.00 | 0.188420E+11 | 0.180545E+11 | 61278.38 | 30-JUN-12:05 | 52651.36 | 0.00 |
July | 0.00 | 0.00 | 0.254273E+11 | 0.233951E+11 | 56746.66 | 11-JUL-15:30 | 53189.73 | 0.00 |
August | 0.00 | 0.00 | 0.137084E+11 | 0.126956E+11 | 51151.94 | 11-AUG-15:20 | 51151.94 | 0.00 |
September | 0.00 | 0.00 | 0.442595E+09 | 0.423093E+09 | 15086.74 | 08-SEP-13:00 | 15086.74 | 0.00 |
October | 0.00 | 0.00 | 21235529.73 | 20342177.20 | 7973.93 | 11-OCT-06:01 | 7973.93 | 0.00 |
November | 0.00 | 0.00 | 2821430.24 | 2821430.24 | 5626.79 | 02-NOV-06:01 | 5626.79 | 0.00 |
December | 0.00 | 0.00 | 2274431.32 | 2271725.16 | 4944.24 | 23-DEC-07:03 | 4944.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.624381E+11 | 0.585751E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2274431.32 | 2271725.16 | 4944.24 | 4944.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254273E+11 | 0.233951E+11 | 61278.38 | 53189.73 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 121751.61 | 121751.61 | 1094.31 | 19-JAN-07:01 | 1094.31 | 0.00 |
February | 0.00 | 0.00 | 534750.54 | 534750.54 | 3925.27 | 09-FEB-07:02 | 3925.27 | 0.00 |
March | 0.00 | 0.00 | 3533399.78 | 3376598.82 | 4252.04 | 23-MAR-06:01 | 4252.04 | 0.00 |
April | 0.00 | 0.00 | 0.554432E+09 | 0.553863E+09 | 22246.41 | 21-APR-13:50 | 22246.41 | 0.00 |
May | 0.00 | 0.00 | 0.380794E+10 | 0.379110E+10 | 36422.34 | 31-MAY-16:00 | 36422.34 | 0.00 |
June | 0.00 | 0.00 | 0.193262E+11 | 0.185012E+11 | 63846.77 | 30-JUN-12:30 | 56578.20 | 0.00 |
July | 0.00 | 0.00 | 0.259352E+11 | 0.238779E+11 | 58435.22 | 21-JUL-14:30 | 58435.22 | 0.00 |
August | 0.00 | 0.00 | 0.135733E+11 | 0.124818E+11 | 53725.28 | 11-AUG-15:40 | 53725.28 | 0.00 |
September | 0.00 | 0.00 | 0.812628E+09 | 0.788145E+09 | 19723.50 | 08-SEP-15:40 | 19723.50 | 0.00 |
October | 0.00 | 0.00 | 45491512.08 | 42862014.66 | 4774.99 | 03-OCT-14:40 | 4573.28 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 86168.39 | 86168.39 | 574.46 | 23-DEC-07:03 | 574.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.640594E+11 | 0.600410E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.259352E+11 | 0.238779E+11 | 63846.77 | 58435.22 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2232.57 | 7808.32 | 02-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2245.43 | 7808.42 | 21-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2394.32 | 7807.76 | 15-MAR-11:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2233.37 | 7806.14 | 19-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2298.16 | 7799.96 | 05-MAY-11:09 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2276.83 | 7587.47 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2011.53 | 7261.74 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2164.00 | 7049.96 | 03-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2013.53 | 7031.94 | 28-SEP-11:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2049.19 | 7250.22 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2150.37 | 7531.89 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2142.12 | 7807.57 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 2183.95 | ||||
Minimum of Months | 0.00 | 0.00 | 2011.53 | 7031.94 | ||
Maximum of Months | 0.00 | 0.00 | 2394.32 | 7808.42 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185140E+10 | 0.40 | 2689.66 | 02-JAN-06:20 | 0.85 |
February | 0.149114E+10 | 0.39 | 2689.66 | 07-FEB-07:01 | 0.85 |
March | 0.134414E+10 | 0.34 | 2689.66 | 01-MAR-07:03 | 0.85 |
April | 0.135999E+10 | 0.32 | 2830.10 | 21-APR-16:00 | 0.87 |
May | 0.249858E+10 | 0.39 | 5061.13 | 11-MAY-06:02 | 1.23 |
June | 0.385101E+10 | 0.48 | 9249.11 | 12-JUN-06:01 | 1.78 |
July | 0.415035E+10 | 0.48 | 8972.12 | 10-JUL-06:02 | 1.74 |
August | 0.358764E+10 | 0.45 | 8091.79 | 05-AUG-06:03 | 1.63 |
September | 0.163692E+10 | 0.33 | 3521.39 | 08-SEP-12:06 | 0.99 |
October | 0.115933E+10 | 0.30 | 2689.66 | 30-OCT-06:01 | 0.85 |
November | 0.135706E+10 | 0.32 | 2689.66 | 13-NOV-07:02 | 0.85 |
December | 0.165300E+10 | 0.35 | 2689.66 | 06-DEC-07:01 | 0.85 |
Annual Sum or Average | 0.259405E+11 | 0.38 | |||
Minimum of Months | 0.115933E+10 | 0.30 | 2689.66 | 0.85 | |
Maximum of Months | 0.415035E+10 | 0.48 | 9249.11 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150504E+10 | 0.39 | 2977.01 | 02-JAN-05:01 | 0.92 |
February | 0.122319E+10 | 0.37 | 2977.01 | 01-FEB-06:01 | 0.92 |
March | 0.122931E+10 | 0.33 | 2977.01 | 01-MAR-06:01 | 0.92 |
April | 0.155487E+10 | 0.33 | 4587.20 | 21-APR-15:30 | 1.18 |
May | 0.307165E+10 | 0.44 | 7085.12 | 31-MAY-14:05 | 1.54 |
June | 0.455355E+10 | 0.54 | 10074.46 | 05-JUN-06:01 | 1.92 |
July | 0.434400E+10 | 0.50 | 10074.46 | 12-JUL-06:02 | 1.92 |
August | 0.342252E+10 | 0.45 | 9260.12 | 01-AUG-06:01 | 1.81 |
September | 0.142172E+10 | 0.32 | 4166.89 | 08-SEP-12:01 | 1.11 |
October | 0.108558E+10 | 0.30 | 2977.01 | 11-OCT-06:01 | 0.91 |
November | 0.123486E+10 | 0.34 | 2977.01 | 01-NOV-05:01 | 0.92 |
December | 0.139850E+10 | 0.36 | 2977.01 | 01-DEC-06:01 | 0.92 |
Annual Sum or Average | 0.260448E+11 | 0.39 | |||
Minimum of Months | 0.108558E+10 | 0.30 | 2977.01 | 0.91 | |
Maximum of Months | 0.455355E+10 | 0.54 | 10074.46 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187702E+10 | 0.44 | 2754.53 | 02-JAN-07:02 | 0.84 |
February | 0.157350E+10 | 0.44 | 2754.53 | 06-FEB-07:02 | 0.84 |
March | 0.151344E+10 | 0.40 | 2754.53 | 02-MAR-07:01 | 0.84 |
April | 0.151375E+10 | 0.34 | 3978.31 | 21-APR-15:40 | 1.03 |
May | 0.267982E+10 | 0.41 | 6721.53 | 31-MAY-14:50 | 1.41 |
June | 0.415264E+10 | 0.49 | 9248.59 | 22-JUN-06:02 | 1.72 |
July | 0.394291E+10 | 0.47 | 10996.14 | 24-JUL-06:02 | 1.91 |
August | 0.293798E+10 | 0.42 | 7362.07 | 10-AUG-15:20 | 1.49 |
September | 0.128597E+10 | 0.32 | 2606.22 | 08-SEP-15:30 | 0.81 |
October | 0.132606E+10 | 0.36 | 2754.53 | 17-OCT-05:01 | 0.83 |
November | 0.172494E+10 | 0.44 | 2754.53 | 17-NOV-07:01 | 0.84 |
December | 0.191897E+10 | 0.45 | 2754.53 | 01-DEC-07:01 | 0.84 |
Annual Sum or Average | 0.264470E+11 | 0.41 | |||
Minimum of Months | 0.128597E+10 | 0.32 | 2606.22 | 0.81 | |
Maximum of Months | 0.415264E+10 | 0.49 | 10996.14 | 1.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 56.69 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.38 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 55.70 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 55.63 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 55.35 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 55.13 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.06 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 55.03 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 55.76 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 56.72 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 56.31 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 54.99 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 54.99 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 56.72 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.42 | 56.42 | 2232.57 | 7808.32 | 02-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.64 | 55.64 | 2245.43 | 7808.42 | 21-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.17 | 56.17 | 2394.32 | 7807.76 | 15-MAR-11:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.14 | 56.14 | 2233.37 | 7806.14 | 19-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.25 | 56.25 | 2298.16 | 7799.96 | 05-MAY-11:09 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.81 | 55.81 | 2276.83 | 7587.47 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.76 | 56.76 | 2011.53 | 7261.74 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.63 | 55.63 | 2164.00 | 7049.96 | 03-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.95 | 56.95 | 2013.53 | 7031.94 | 28-SEP-11:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.61 | 54.61 | 2049.19 | 7250.22 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.79 | 56.79 | 2150.37 | 7531.89 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 55.51 | 55.51 | 2142.12 | 7807.57 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 2183.95 | ||||||
Minimum of Months | 0.00 | 0.00 | 54.61 | 54.61 | 2011.53 | 7031.94 | ||
Maximum of Months | 0.00 | 0.00 | 56.95 | 56.95 | 2394.32 | 7808.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.435164E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.309978E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.216207E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.642149E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.447255E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.829682E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.102667E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.743752E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.409944E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.115766E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.305838E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.401716E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219461E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.409944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.435164E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.327459E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.201183E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.109068E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.308643E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.407113E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.914004E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.104299E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.676933E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.819643E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.242605E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.322371E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163706E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.174423E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.327459E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.515634E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.347391E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.216880E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.611455E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.367705E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.888072E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.101798E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.628811E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.266181E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.176328E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.429342E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.528008E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.259160E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.266181E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.528008E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.185140E+10 | 4226504.06 | 0.570525E+11 | 0.281654E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149114E+10 | 6740761.87 | 0.385114E+11 | 0.239115E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134414E+10 | 11015751.40 | 0.232360E+11 | 0.272351E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135999E+10 | 0.287867E+09 | 0.508131E+10 | 0.962275E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249858E+10 | 0.433342E+10 | 0.864051E+09 | 0.546486E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.385101E+10 | 0.173779E+11 | 0.181216E+09 | 63851035.00 | 4846283.96 | 0.00 | 0.00 | 0.00 |
July | 0.415035E+10 | 0.249860E+11 | 0.127100E+09 | 0.138112E+09 | 62161536.09 | 0.00 | 0.00 | 0.00 |
August | 0.358764E+10 | 0.142107E+11 | 0.394471E+09 | 0.159049E+09 | 28831.58 | 0.00 | 0.00 | 0.00 |
September | 0.163692E+10 | 0.231676E+10 | 0.188026E+10 | 0.429960E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115933E+10 | 15829279.10 | 0.108746E+11 | 0.185025E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135706E+10 | 3087713.49 | 0.426325E+11 | 0.265213E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165300E+10 | 2633150.16 | 0.595967E+11 | 0.249363E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259405E+11 | 0.635563E+11 | 0.240432E+12 | 0.164102E+12 | 67036651.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115933E+10 | 2633150.16 | 0.127100E+09 | 63851035.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.415035E+10 | 0.249860E+11 | 0.595967E+11 | 0.281654E+11 | 62161536.09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150504E+10 | 3698763.05 | 0.452975E+11 | 0.247022E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122319E+10 | 5255390.69 | 0.272335E+11 | 0.216914E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122931E+10 | 10460031.97 | 0.126793E+11 | 0.265387E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155487E+10 | 98119711.25 | 0.165719E+10 | 0.929410E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307165E+10 | 0.387394E+10 | 24720763.57 | 0.701885E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.455355E+10 | 0.188420E+11 | 1190318.77 | 74614489.78 | 6459132.15 | 0.00 | 0.00 | 0.00 |
July | 0.434400E+10 | 0.254273E+11 | 820477.94 | 0.159227E+09 | 64142854.06 | 0.00 | 0.00 | 0.00 |
August | 0.342252E+10 | 0.137084E+11 | 10430250.88 | 0.319245E+09 | 53194.74 | 0.00 | 0.00 | 0.00 |
September | 0.142172E+10 | 0.442595E+09 | 0.220273E+09 | 0.519799E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108558E+10 | 21235529.73 | 0.784797E+10 | 0.183332E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123486E+10 | 2821430.24 | 0.354993E+11 | 0.240880E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139850E+10 | 2274431.32 | 0.495977E+11 | 0.217869E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260448E+11 | 0.624381E+11 | 0.180070E+12 | 0.152887E+12 | 70655180.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108558E+10 | 2274431.32 | 820477.94 | 74614489.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.455355E+10 | 0.254273E+11 | 0.495977E+11 | 0.265387E+11 | 64142854.06 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.187702E+10 | 121751.61 | 0.682089E+11 | 0.250578E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157350E+10 | 534750.54 | 0.445089E+11 | 0.218700E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151344E+10 | 3533399.78 | 0.248659E+11 | 0.264190E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151375E+10 | 0.554432E+09 | 0.487977E+10 | 0.981757E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.267982E+10 | 0.380794E+10 | 30108448.40 | 0.101744E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415264E+10 | 0.193262E+11 | 2028046.22 | 54498793.67 | 6141920.04 | 0.00 | 0.00 | 0.00 |
July | 0.394291E+10 | 0.259352E+11 | 824594.61 | 0.139916E+09 | 49359941.39 | 0.00 | 0.00 | 0.00 |
August | 0.293798E+10 | 0.135733E+11 | 20196741.16 | 0.556426E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128597E+10 | 0.812628E+09 | 0.120895E+10 | 0.603189E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132606E+10 | 45491512.08 | 0.179918E+11 | 0.187550E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172494E+10 | 0.00 | 0.576049E+11 | 0.242647E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191897E+10 | 86168.39 | 0.744356E+11 | 0.223781E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264470E+11 | 0.640594E+11 | 0.293758E+12 | 0.156362E+12 | 55501861.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128597E+10 | 0.00 | 824594.61 | 54498793.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.415264E+10 | 0.259352E+11 | 0.744356E+11 | 0.264190E+11 | 49359941.39 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.185140E+10 | 0.00 | 0.00 | 0.00 | 1206662.00 | 0.416638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149114E+10 | 0.00 | 0.00 | 0.00 | 1943585.82 | 0.295047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134414E+10 | 0.00 | 0.00 | 0.00 | 3216822.74 | 0.202733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135999E+10 | 0.00 | 0.00 | 0.00 | 77933782.85 | 0.498357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.249858E+10 | 0.00 | 0.00 | 0.00 | 0.114070E+10 | 0.833266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.385101E+10 | 0.00 | 0.00 | 0.00 | 0.426656E+10 | 0.179247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.415035E+10 | 0.00 | 0.00 | 0.00 | 0.598924E+10 | 0.127100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.358764E+10 | 0.00 | 0.00 | 0.00 | 0.347055E+10 | 0.379330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163692E+10 | 0.00 | 0.00 | 0.00 | 0.618879E+09 | 0.184364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115933E+10 | 0.00 | 0.00 | 0.00 | 4629643.39 | 0.104127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135706E+10 | 0.00 | 0.00 | 0.00 | 891741.31 | 0.292258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165300E+10 | 0.00 | 0.00 | 0.00 | 758016.25 | 0.385179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259405E+11 | 0.00 | 0.00 | 0.00 | 0.155765E+11 | 0.177944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115933E+10 | 0.00 | 0.00 | 0.00 | 758016.25 | 0.127100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.415035E+10 | 0.00 | 0.00 | 0.00 | 0.598924E+10 | 0.416638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150504E+10 | 0.00 | 0.00 | 0.00 | 1047298.63 | 0.312398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122319E+10 | 0.00 | 0.00 | 0.00 | 1470897.79 | 0.188936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122931E+10 | 0.00 | 0.00 | 0.00 | 2969005.54 | 0.967451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155487E+10 | 0.00 | 0.00 | 0.00 | 28482402.53 | 0.150307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.307165E+10 | 0.00 | 0.00 | 0.00 | 0.999477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.455355E+10 | 0.00 | 0.00 | 0.00 | 0.458649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.434400E+10 | 0.00 | 0.00 | 0.00 | 0.608594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.342252E+10 | 0.00 | 0.00 | 0.00 | 0.334681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142172E+10 | 0.00 | 0.00 | 0.00 | 0.122647E+09 | 0.199863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108558E+10 | 0.00 | 0.00 | 0.00 | 6076593.11 | 0.710477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123486E+10 | 0.00 | 0.00 | 0.00 | 798255.87 | 0.230248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139850E+10 | 0.00 | 0.00 | 0.00 | 652845.16 | 0.308379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260448E+11 | 0.00 | 0.00 | 0.00 | 0.151829E+11 | 0.122478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108558E+10 | 0.00 | 0.00 | 0.00 | 652845.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.455355E+10 | 0.00 | 0.00 | 0.00 | 0.608594E+10 | 0.312398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.187702E+10 | 0.00 | 0.00 | 0.00 | 35723.12 | 0.496864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157350E+10 | 0.00 | 0.00 | 0.00 | 153172.63 | 0.331655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151344E+10 | 0.00 | 0.00 | 0.00 | 1034795.44 | 0.201736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151375E+10 | 0.00 | 0.00 | 0.00 | 0.148153E+09 | 0.445265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.267982E+10 | 0.00 | 0.00 | 0.00 | 0.987979E+09 | 9250891.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.415264E+10 | 0.00 | 0.00 | 0.00 | 0.472808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.394291E+10 | 0.00 | 0.00 | 0.00 | 0.623687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.293798E+10 | 0.00 | 0.00 | 0.00 | 0.333791E+10 | 12223164.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128597E+10 | 0.00 | 0.00 | 0.00 | 0.217681E+09 | 0.115816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132606E+10 | 0.00 | 0.00 | 0.00 | 12967097.48 | 0.162938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191897E+10 | 0.00 | 0.00 | 0.00 | 25362.91 | 0.508818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264470E+11 | 0.00 | 0.00 | 0.00 | 0.156709E+11 | 0.217043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.415264E+10 | 0.00 | 0.00 | 0.00 | 0.623687E+10 | 0.508818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165139E+10 | 0.00 | 0.00 | 0.26 |
February | 0.948815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812790E+09 | 0.00 | 0.00 | 0.27 |
March | 0.891033E+10 | 0.00 | 0.00 | 575971.27 | 0.00 | 83132467.15 | 0.735847E+09 | 0.00 | 0.30 |
April | 0.364226E+10 | 0.00 | 0.00 | 16902076.84 | 0.00 | 0.00 | 0.874215E+10 | 0.00 | 0.36 |
May | 0.140855E+10 | 0.00 | 0.00 | 35793157.70 | 0.00 | 0.00 | 0.186562E+11 | 0.00 | 0.72 |
June | 0.939638E+09 | 4537346.28 | 0.00 | 41493545.37 | 0.00 | 0.00 | 0.167137E+11 | 0.00 | 0.97 |
July | 0.109507E+10 | 50272794.84 | 0.00 | 39038755.97 | 5506803.54 | 0.00 | 0.128176E+11 | 0.00 | 0.91 |
August | 0.978643E+09 | 182683.01 | 0.00 | 43533220.97 | 0.00 | 0.00 | 0.182285E+11 | 0.00 | 0.88 |
September | 0.197272E+10 | 0.00 | 0.00 | 27980439.02 | 0.00 | 0.00 | 0.136334E+11 | 0.00 | 0.45 |
October | 0.545991E+10 | 0.00 | 0.00 | 6126541.00 | 0.00 | 1880414.56 | 0.395990E+10 | 0.00 | 0.30 |
November | 0.116303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510380E+09 | 0.00 | 0.00 | 0.26 |
December | 0.135793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117924E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.699171E+11 | 54992824.13 | 0.00 | 0.211444E+09 | 5506803.54 | 0.423882E+10 | 0.934873E+11 | 0.00 | 0.50 |
Minimum of Months | 0.939638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.135793E+11 | 50272794.84 | 0.00 | 43533220.97 | 5506803.54 | 0.165139E+10 | 0.186562E+11 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.758715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586084E+10 | 0.00 | 0.00 | 0.27 |
February | 0.647660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418457E+10 | 0.00 | 0.00 | 0.28 |
March | 0.898260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731258E+09 | 0.00 | 0.00 | 0.30 |
April | 0.620565E+10 | 0.00 | 0.00 | 6290418.80 | 0.00 | 31955691.72 | 0.416823E+10 | 0.00 | 0.32 |
May | 0.234041E+10 | 0.00 | 0.00 | 24853151.16 | 0.00 | 0.00 | 0.142126E+11 | 0.00 | 0.60 |
June | 0.145950E+10 | 4651177.72 | 0.00 | 32069350.36 | 0.00 | 0.00 | 0.130095E+11 | 0.00 | 0.80 |
July | 0.154145E+10 | 38709072.63 | 0.00 | 29867805.88 | 8217438.37 | 0.00 | 0.973718E+10 | 0.00 | 0.74 |
August | 0.144083E+10 | 208817.42 | 0.00 | 30362819.06 | 0.00 | 0.00 | 0.131267E+11 | 0.00 | 0.68 |
September | 0.503426E+10 | 0.00 | 0.00 | 11109837.51 | 0.00 | 0.00 | 0.704854E+10 | 0.00 | 0.38 |
October | 0.740418E+10 | 0.00 | 0.00 | 381438.06 | 0.00 | 0.345122E+09 | 0.554774E+09 | 0.00 | 0.28 |
November | 0.874654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443503E+10 | 0.00 | 0.00 | 0.28 |
December | 0.931526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674203E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.665344E+11 | 43569067.77 | 0.00 | 0.134935E+09 | 8217438.37 | 0.223308E+11 | 0.618575E+11 | 0.00 | 0.43 |
Minimum of Months | 0.144083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.931526E+10 | 38709072.63 | 0.00 | 32069350.36 | 8217438.37 | 0.674203E+10 | 0.142126E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102483E+11 | 0.00 | 0.00 | 0.25 |
February | 0.255684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671371E+10 | 0.00 | 0.00 | 0.27 |
March | 0.566781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301632E+10 | 0.00 | 0.00 | 0.29 |
April | 0.631897E+10 | 0.00 | 0.00 | 3163532.34 | 0.00 | 0.352404E+09 | 0.242926E+10 | 0.00 | 0.30 |
May | 0.325409E+10 | 0.00 | 0.00 | 20281835.95 | 0.00 | 0.00 | 0.120618E+11 | 0.00 | 0.57 |
June | 0.151721E+10 | 8440934.48 | 0.00 | 29756752.41 | 0.00 | 0.00 | 0.124604E+11 | 0.00 | 0.79 |
July | 0.169546E+10 | 36334908.13 | 0.00 | 27005226.68 | 5408643.97 | 0.00 | 0.898239E+10 | 0.00 | 0.73 |
August | 0.211411E+10 | 521897.49 | 0.00 | 23971511.19 | 0.00 | 0.00 | 0.107982E+11 | 0.00 | 0.63 |
September | 0.600384E+10 | 0.00 | 0.00 | 4497881.99 | 0.00 | 45312717.76 | 0.360807E+10 | 0.00 | 0.33 |
October | 0.544051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173201E+10 | 0.00 | 0.00 | 0.28 |
November | 0.226558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923957E+10 | 0.00 | 0.00 | 0.26 |
December | 0.127327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125707E+11 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.395444E+11 | 45297740.10 | 0.00 | 0.108677E+09 | 5408643.97 | 0.439184E+11 | 0.503401E+11 | 0.00 | 0.41 |
Minimum of Months | 0.127327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.631897E+10 | 36334908.13 | 0.00 | 29756752.41 | 5408643.97 | 0.125707E+11 | 0.124604E+11 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17009505.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413560E+10 | 0.00 | 0.00 | 0.39 |
February | 23766885.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291591E+10 | 0.00 | 0.00 | 0.35 |
March | 0.269209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197103E+10 | 0.00 | 0.00 | 0.34 |
April | 0.132704E+10 | 0.00 | 0.00 | 278353.32 | 0.00 | 0.401584E+09 | 0.240207E+09 | 0.00 | 0.31 |
May | 0.844020E+09 | 0.00 | 0.00 | 4618710.35 | 0.00 | 193500.71 | 0.269568E+10 | 0.00 | 0.64 |
June | 0.250233E+09 | 3148071.70 | 0.00 | 10104560.78 | 0.00 | 0.00 | 0.387880E+10 | 0.00 | 1.13 |
July | 0.331983E+09 | 11635136.90 | 0.00 | 8520895.72 | 1175019.50 | 0.00 | 0.261190E+10 | 0.00 | 1.01 |
August | 0.666389E+09 | 137964.44 | 0.00 | 5266524.29 | 0.00 | 822986.44 | 0.228609E+10 | 0.00 | 0.73 |
September | 0.154187E+10 | 0.00 | 0.00 | 311821.02 | 0.00 | 0.190609E+09 | 0.298222E+09 | 0.00 | 0.33 |
October | 0.439741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122822E+10 | 0.00 | 0.00 | 0.30 |
November | 13364887.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376616E+10 | 0.00 | 0.00 | 0.37 |
December | 20654950.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497408E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.574528E+10 | 14921173.04 | 0.00 | 29100865.48 | 1175019.50 | 0.195842E+11 | 0.120109E+11 | 0.00 | 0.53 |
Minimum of Months | 13364887.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.154187E+10 | 11635136.90 | 0.00 | 10104560.78 | 1175019.50 | 0.497408E+10 | 0.387880E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10442563.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268898E+10 | 0.00 | 0.00 | 0.39 |
February | 48637882.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171488E+10 | 0.00 | 0.00 | 0.34 |
March | 0.441448E+09 | 0.00 | 0.00 | 171060.77 | 0.00 | 0.852789E+09 | 64244614.69 | 0.00 | 0.32 |
April | 0.513880E+09 | 0.00 | 0.00 | 2516349.20 | 0.00 | 0.132091E+09 | 0.120231E+10 | 0.00 | 0.44 |
May | 0.276848E+09 | 0.00 | 0.00 | 9764567.48 | 0.00 | 0.00 | 0.488548E+10 | 0.00 | 1.39 |
June | 0.111034E+09 | 2602347.82 | 0.00 | 11348796.96 | 0.00 | 0.00 | 0.461255E+10 | 0.00 | 1.87 |
July | 0.129093E+09 | 8805490.14 | 0.00 | 11211001.92 | 703570.96 | 0.00 | 0.336008E+10 | 0.00 | 1.78 |
August | 0.225537E+09 | 95465.84 | 0.00 | 8061727.16 | 0.00 | 256599.49 | 0.344352E+10 | 0.00 | 1.30 |
September | 0.682871E+09 | 0.00 | 0.00 | 1723535.29 | 0.00 | 58537931.24 | 0.882858E+09 | 0.00 | 0.41 |
October | 0.398856E+09 | 0.00 | 0.00 | 43535.05 | 0.00 | 0.615792E+09 | 14044690.30 | 0.00 | 0.30 |
November | 8211537.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242414E+10 | 0.00 | 0.00 | 0.37 |
December | 12635154.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328358E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.285950E+10 | 11503303.80 | 0.00 | 44840573.82 | 703570.96 | 0.117711E+11 | 0.184651E+11 | 0.00 | 0.78 |
Minimum of Months | 8211537.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.682871E+09 | 8805490.14 | 0.00 | 11348796.96 | 703570.96 | 0.328358E+10 | 0.488548E+10 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 97489904.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369473E+10 | 0.00 | 0.00 | 0.36 |
February | 0.360289E+09 | 0.00 | 0.00 | 235431.25 | 0.00 | 0.213630E+10 | 87062724.97 | 0.00 | 0.32 |
March | 0.603064E+09 | 0.00 | 0.00 | 2802251.75 | 0.00 | 0.109607E+10 | 0.104660E+10 | 0.00 | 0.41 |
April | 0.586122E+09 | 0.00 | 0.00 | 8985726.83 | 0.00 | 0.185291E+09 | 0.440168E+10 | 0.00 | 0.73 |
May | 0.602614E+09 | 0.00 | 0.00 | 13230217.66 | 0.00 | 758102.10 | 0.676847E+10 | 0.00 | 1.36 |
June | 0.298416E+09 | 4970525.59 | 0.00 | 14229035.43 | 0.00 | 0.00 | 0.558004E+10 | 0.00 | 1.69 |
July | 0.325220E+09 | 21726923.34 | 0.00 | 14244605.44 | 705038.29 | 0.00 | 0.376355E+10 | 0.00 | 1.57 |
August | 0.443097E+09 | 183407.68 | 0.00 | 13547889.41 | 0.00 | 329640.37 | 0.517226E+10 | 0.00 | 1.46 |
September | 0.942097E+09 | 0.00 | 0.00 | 5604169.42 | 0.00 | 76795959.64 | 0.280107E+10 | 0.00 | 0.60 |
October | 0.619594E+09 | 0.00 | 0.00 | 1108147.36 | 0.00 | 0.757499E+09 | 0.501212E+09 | 0.00 | 0.33 |
November | 0.152558E+09 | 0.00 | 0.00 | 28815.86 | 0.00 | 0.319633E+10 | 11541430.31 | 0.00 | 0.33 |
December | 19947759.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474109E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.505051E+10 | 26880856.61 | 0.00 | 74016290.41 | 705038.29 | 0.158852E+11 | 0.301335E+11 | 0.00 | 0.80 |
Minimum of Months | 19947759.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.942097E+09 | 21726923.34 | 0.00 | 14244605.44 | 705038.29 | 0.474109E+10 | 0.676847E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10467733.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273998E+10 | 0.00 | 0.00 | 0.40 |
February | 37198234.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185514E+10 | 0.00 | 0.00 | 0.35 |
March | 0.289644E+09 | 0.00 | 0.00 | 30019.79 | 0.00 | 0.110529E+10 | 23412262.33 | 0.00 | 0.33 |
April | 0.543715E+09 | 0.00 | 0.00 | 2669929.01 | 0.00 | 0.183827E+09 | 0.142327E+10 | 0.00 | 0.51 |
May | 0.422138E+09 | 0.00 | 0.00 | 5738753.09 | 0.00 | 519836.94 | 0.288087E+10 | 0.00 | 0.99 |
June | 0.173304E+09 | 2994703.24 | 0.00 | 8413235.62 | 0.00 | 0.00 | 0.298169E+10 | 0.00 | 1.54 |
July | 0.208619E+09 | 14273123.85 | 0.00 | 6866426.12 | 404820.43 | 0.00 | 0.185159E+10 | 0.00 | 1.30 |
August | 0.347353E+09 | 142063.53 | 0.00 | 5472519.91 | 0.00 | 348550.40 | 0.205408E+10 | 0.00 | 1.05 |
September | 0.800851E+09 | 0.00 | 0.00 | 1105098.32 | 0.00 | 88821686.99 | 0.649499E+09 | 0.00 | 0.40 |
October | 0.309637E+09 | 0.00 | 0.00 | 7536.40 | 0.00 | 0.721940E+09 | 6259675.96 | 0.00 | 0.30 |
November | 11998039.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244194E+10 | 0.00 | 0.00 | 0.38 |
December | 12659921.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329465E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.316758E+10 | 17409890.61 | 0.00 | 30303518.24 | 404820.43 | 0.124325E+11 | 0.118707E+11 | 0.00 | 0.67 |
Minimum of Months | 10467733.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.800851E+09 | 14273123.85 | 0.00 | 8413235.62 | 404820.43 | 0.329465E+10 | 0.298169E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 41140498.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407087E+10 | 0.00 | 0.00 | 0.38 |
February | 35034285.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316112E+10 | 0.00 | 0.00 | 0.37 |
March | 97588907.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237267E+10 | 0.00 | 0.00 | 0.34 |
April | 0.143160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655451E+09 | 0.00 | 0.00 | 0.30 |
May | 0.153974E+10 | 0.00 | 0.00 | 1360328.16 | 0.00 | 0.00 | 0.938448E+09 | 0.00 | 0.42 |
June | 0.292785E+09 | 902909.68 | 0.00 | 6691980.52 | 0.00 | 0.00 | 0.260440E+10 | 0.00 | 0.79 |
July | 0.300498E+09 | 9792768.10 | 0.00 | 6695838.00 | 1159842.09 | 0.00 | 0.206490E+10 | 0.00 | 0.79 |
August | 0.632690E+09 | 30835.76 | 0.00 | 4754995.74 | 0.00 | 0.00 | 0.210054E+10 | 0.00 | 0.64 |
September | 0.178483E+10 | 0.00 | 0.00 | 387888.75 | 0.00 | 31312951.99 | 0.325302E+09 | 0.00 | 0.30 |
October | 0.874751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100595E+10 | 0.00 | 0.00 | 0.28 |
November | 18580188.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338288E+10 | 0.00 | 0.00 | 0.32 |
December | 39576371.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466142E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.708882E+10 | 10726513.54 | 0.00 | 19891031.17 | 1159842.09 | 0.193417E+11 | 0.803359E+10 | 0.00 | 0.44 |
Minimum of Months | 18580188.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.178483E+10 | 9792768.10 | 0.00 | 6695838.00 | 1159842.09 | 0.466142E+10 | 0.260440E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28446563.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283887E+10 | 0.00 | 0.00 | 0.41 |
February | 44676553.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205012E+10 | 0.00 | 0.00 | 0.37 |
March | 0.415843E+09 | 0.00 | 0.00 | 20531.80 | 0.00 | 0.107290E+10 | 9569263.44 | 0.00 | 0.32 |
April | 0.725360E+09 | 0.00 | 0.00 | 1416841.05 | 0.00 | 0.180081E+09 | 0.744091E+09 | 0.00 | 0.36 |
May | 0.297670E+09 | 0.00 | 0.00 | 7355493.06 | 0.00 | 0.00 | 0.372563E+10 | 0.00 | 1.07 |
June | 0.110911E+09 | 1156159.91 | 0.00 | 9134391.29 | 0.00 | 0.00 | 0.369604E+10 | 0.00 | 1.53 |
July | 0.119622E+09 | 10110149.49 | 0.00 | 9777043.24 | 632124.64 | 0.00 | 0.289618E+10 | 0.00 | 1.55 |
August | 0.157948E+09 | 25873.24 | 0.00 | 8181235.10 | 0.00 | 0.00 | 0.344060E+10 | 0.00 | 1.24 |
September | 0.741690E+09 | 0.00 | 0.00 | 2406886.32 | 0.00 | 10553339.78 | 0.111513E+10 | 0.00 | 0.40 |
October | 0.638691E+09 | 0.00 | 0.00 | 90411.31 | 0.00 | 0.527217E+09 | 39622471.75 | 0.00 | 0.29 |
November | 13221153.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225361E+10 | 0.00 | 0.00 | 0.33 |
December | 25135715.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318698E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.331921E+10 | 11292182.64 | 0.00 | 38382833.16 | 632124.64 | 0.121203E+11 | 0.156669E+11 | 0.00 | 0.69 |
Minimum of Months | 13221153.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.741690E+09 | 10110149.49 | 0.00 | 9777043.24 | 632124.64 | 0.318698E+10 | 0.372563E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 40876693.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779409E+10 | 0.00 | 0.00 | 0.70 |
February | 0.140364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498886E+10 | 0.00 | 0.00 | 0.59 |
March | 0.358822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337938E+10 | 0.00 | 0.00 | 0.50 |
April | 0.987126E+09 | 0.00 | 0.00 | 2065714.90 | 0.00 | 0.102139E+10 | 0.135624E+10 | 0.00 | 0.49 |
May | 0.115278E+10 | 0.00 | 0.00 | 4720744.13 | 0.00 | 0.336149E+09 | 0.256502E+10 | 0.00 | 0.75 |
June | 0.550087E+09 | 2036329.00 | 0.00 | 7692827.13 | 0.00 | 85395386.10 | 0.287467E+10 | 0.00 | 1.06 |
July | 0.506573E+09 | 21435487.60 | 0.00 | 9522380.32 | 700669.54 | 72142586.89 | 0.223218E+10 | 0.00 | 1.15 |
August | 0.673778E+09 | 54560.26 | 0.00 | 8972205.35 | 0.00 | 0.171884E+09 | 0.323880E+10 | 0.00 | 1.12 |
September | 0.121336E+10 | 0.00 | 0.00 | 2736855.36 | 0.00 | 0.711149E+09 | 0.148279E+10 | 0.00 | 0.49 |
October | 0.567376E+09 | 0.00 | 0.00 | 285763.67 | 0.00 | 0.212212E+10 | 0.186966E+09 | 0.00 | 0.43 |
November | 39373981.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700646E+10 | 0.00 | 0.00 | 0.64 |
December | 35997872.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976251E+10 | 0.00 | 0.00 | 0.73 |
Annual Sum or Average | 0.626651E+10 | 23526376.86 | 0.00 | 35996490.87 | 700669.54 | 0.374515E+11 | 0.139367E+11 | 0.00 | 0.72 |
Minimum of Months | 35997872.93 | 0.00 | 0.00 | 0.00 | 0.00 | 72142586.89 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.121336E+10 | 21435487.60 | 0.00 | 9522380.32 | 700669.54 | 0.976251E+10 | 0.323880E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28667144.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288710E+10 | 0.00 | 0.00 | 0.41 |
February | 34498925.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220599E+10 | 0.00 | 0.00 | 0.39 |
March | 0.191370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139365E+10 | 0.00 | 0.00 | 0.34 |
April | 0.798123E+09 | 0.00 | 0.00 | 1281039.69 | 0.00 | 0.201149E+09 | 0.712624E+09 | 0.00 | 0.39 |
May | 0.592891E+09 | 0.00 | 0.00 | 3046545.37 | 0.00 | 0.00 | 0.165912E+10 | 0.00 | 0.66 |
June | 0.182487E+09 | 679312.33 | 0.00 | 6134222.68 | 0.00 | 0.00 | 0.221874E+10 | 0.00 | 1.16 |
July | 0.208584E+09 | 12769002.88 | 0.00 | 5550865.94 | 673351.07 | 0.00 | 0.153605E+10 | 0.00 | 1.06 |
August | 0.287750E+09 | 33872.32 | 0.00 | 5305262.54 | 0.00 | 0.00 | 0.204686E+10 | 0.00 | 0.96 |
September | 0.876580E+09 | 0.00 | 0.00 | 1284694.43 | 0.00 | 17291019.18 | 0.685811E+09 | 0.00 | 0.36 |
October | 0.594811E+09 | 0.00 | 0.00 | 5216.56 | 0.00 | 0.593926E+09 | 6893041.91 | 0.00 | 0.28 |
November | 17944129.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225145E+10 | 0.00 | 0.00 | 0.33 |
December | 25192851.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319763E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.383890E+10 | 13482187.53 | 0.00 | 22607847.21 | 673351.07 | 0.127482E+11 | 0.886610E+10 | 0.00 | 0.56 |
Minimum of Months | 17944129.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.876580E+09 | 12769002.88 | 0.00 | 6134222.68 | 673351.07 | 0.319763E+10 | 0.221874E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24831656.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375964E+10 | 0.00 | 0.00 | 0.34 |
February | 80146908.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274126E+10 | 0.00 | 0.00 | 0.32 |
March | 0.489715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175653E+10 | 0.00 | 0.00 | 0.31 |
April | 0.145099E+10 | 0.00 | 0.00 | 553311.74 | 0.00 | 0.248651E+09 | 0.421763E+09 | 0.00 | 0.31 |
May | 0.623085E+09 | 0.00 | 0.00 | 5799706.31 | 0.00 | 0.00 | 0.319481E+10 | 0.00 | 0.68 |
June | 0.225598E+09 | 1610510.70 | 0.00 | 10879297.32 | 0.00 | 0.00 | 0.406127E+10 | 0.00 | 1.15 |
July | 0.277879E+09 | 12426420.85 | 0.00 | 9331324.71 | 1730112.12 | 0.00 | 0.281933E+10 | 0.00 | 1.02 |
August | 0.499919E+09 | 55183.05 | 0.00 | 6487914.72 | 0.00 | 0.00 | 0.274703E+10 | 0.00 | 0.77 |
September | 0.160840E+10 | 0.00 | 0.00 | 941749.93 | 0.00 | 34030303.98 | 0.678058E+09 | 0.00 | 0.34 |
October | 0.802633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987296E+09 | 0.00 | 0.00 | 0.29 |
November | 20123645.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335626E+10 | 0.00 | 0.00 | 0.32 |
December | 28973231.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436521E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.613229E+10 | 14092114.60 | 0.00 | 33993304.73 | 1730112.12 | 0.172489E+11 | 0.139223E+11 | 0.00 | 0.52 |
Minimum of Months | 20123645.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.160840E+10 | 12426420.85 | 0.00 | 10879297.32 | 1730112.12 | 0.436521E+10 | 0.406127E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 20202419.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240216E+10 | 0.00 | 0.00 | 0.33 |
February | 0.116942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149490E+10 | 0.00 | 0.00 | 0.28 |
March | 0.471868E+09 | 0.00 | 0.00 | 326071.79 | 0.00 | 0.686100E+09 | 0.111818E+09 | 0.00 | 0.27 |
April | 0.515423E+09 | 0.00 | 0.00 | 3016873.15 | 0.00 | 87995275.67 | 0.145614E+10 | 0.00 | 0.45 |
May | 0.235843E+09 | 0.00 | 0.00 | 10048522.36 | 0.00 | 0.00 | 0.499033E+10 | 0.00 | 1.38 |
June | 0.110958E+09 | 1485144.13 | 0.00 | 11396233.40 | 0.00 | 0.00 | 0.446806E+10 | 0.00 | 1.79 |
July | 0.119351E+09 | 9781073.80 | 0.00 | 11282172.62 | 997936.96 | 0.00 | 0.331149E+10 | 0.00 | 1.70 |
August | 0.172174E+09 | 38531.22 | 0.00 | 8583869.77 | 0.00 | 0.00 | 0.359251E+10 | 0.00 | 1.27 |
September | 0.636607E+09 | 0.00 | 0.00 | 2386635.83 | 0.00 | 15356241.27 | 0.121213E+10 | 0.00 | 0.43 |
October | 0.428685E+09 | 0.00 | 0.00 | 131897.01 | 0.00 | 0.472754E+09 | 67755278.08 | 0.00 | 0.25 |
November | 18962123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210003E+10 | 0.00 | 0.00 | 0.30 |
December | 20068892.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287493E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.286708E+10 | 11304749.14 | 0.00 | 47172275.93 | 997936.96 | 0.101342E+11 | 0.192102E+11 | 0.00 | 0.74 |
Minimum of Months | 18962123.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.636607E+09 | 9781073.80 | 0.00 | 11396233.40 | 997936.96 | 0.287493E+10 | 0.499033E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338627E+10 | 0.00 | 0.00 | 0.32 |
February | 0.522069E+09 | 0.00 | 0.00 | 491256.99 | 0.00 | 0.196687E+10 | 0.168331E+09 | 0.00 | 0.32 |
March | 0.820468E+09 | 0.00 | 0.00 | 3796587.49 | 0.00 | 0.919499E+09 | 0.127210E+10 | 0.00 | 0.43 |
April | 0.727023E+09 | 0.00 | 0.00 | 10209305.71 | 0.00 | 0.114543E+09 | 0.492824E+10 | 0.00 | 0.81 |
May | 0.547186E+09 | 0.00 | 0.00 | 13919904.42 | 0.00 | 0.00 | 0.694810E+10 | 0.00 | 1.40 |
June | 0.280066E+09 | 3507891.56 | 0.00 | 14690740.33 | 0.00 | 0.00 | 0.555864E+10 | 0.00 | 1.69 |
July | 0.309074E+09 | 24761525.13 | 0.00 | 14694885.61 | 1230467.46 | 0.00 | 0.376944E+10 | 0.00 | 1.56 |
August | 0.358180E+09 | 72490.31 | 0.00 | 14740744.95 | 0.00 | 0.00 | 0.546207E+10 | 0.00 | 1.50 |
September | 0.975102E+09 | 0.00 | 0.00 | 7096120.74 | 0.00 | 20654893.50 | 0.370380E+10 | 0.00 | 0.71 |
October | 0.879852E+09 | 0.00 | 0.00 | 1645326.93 | 0.00 | 0.638498E+09 | 0.719258E+09 | 0.00 | 0.35 |
November | 0.293322E+09 | 0.00 | 0.00 | 91847.58 | 0.00 | 0.290421E+10 | 28762371.44 | 0.00 | 0.31 |
December | 30844248.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422967E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.590880E+10 | 28341907.00 | 0.00 | 81376720.76 | 1230467.46 | 0.141802E+11 | 0.325587E+11 | 0.00 | 0.81 |
Minimum of Months | 30844248.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.975102E+09 | 24761525.13 | 0.00 | 14740744.95 | 1230467.46 | 0.422967E+10 | 0.694810E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17434165.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248549E+10 | 0.00 | 0.00 | 0.35 |
February | 93232427.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173270E+10 | 0.00 | 0.00 | 0.32 |
March | 0.434401E+09 | 0.00 | 0.00 | 113994.09 | 0.00 | 0.964846E+09 | 40097921.63 | 0.00 | 0.31 |
April | 0.642846E+09 | 0.00 | 0.00 | 3072658.29 | 0.00 | 0.113741E+09 | 0.160804E+10 | 0.00 | 0.54 |
May | 0.352949E+09 | 0.00 | 0.00 | 6300601.53 | 0.00 | 0.00 | 0.310956E+10 | 0.00 | 1.04 |
June | 0.168412E+09 | 1056333.87 | 0.00 | 8759009.77 | 0.00 | 0.00 | 0.301683E+10 | 0.00 | 1.54 |
July | 0.197576E+09 | 15187660.11 | 0.00 | 7176115.70 | 703039.92 | 0.00 | 0.191953E+10 | 0.00 | 1.29 |
August | 0.295081E+09 | 55755.13 | 0.00 | 6147426.99 | 0.00 | 0.00 | 0.229708E+10 | 0.00 | 1.09 |
September | 0.832311E+09 | 0.00 | 0.00 | 1710120.68 | 0.00 | 21461826.68 | 0.101249E+10 | 0.00 | 0.45 |
October | 0.540579E+09 | 0.00 | 0.00 | 14649.04 | 0.00 | 0.584461E+09 | 16573257.89 | 0.00 | 0.29 |
November | 20845756.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217855E+10 | 0.00 | 0.00 | 0.32 |
December | 19263559.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289898E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.361493E+10 | 16299749.11 | 0.00 | 33294576.10 | 703039.92 | 0.109802E+11 | 0.130202E+11 | 0.00 | 0.66 |
Minimum of Months | 17434165.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.832311E+09 | 15187660.11 | 0.00 | 8759009.77 | 703039.92 | 0.289898E+10 | 0.310956E+10 | 0.00 | 1.54 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.241614E+11 | 0.228074E+11 | 0.00 | 0.187483E+12 | 0.914728E+10 |
February | 0.336136E+11 | 0.185441E+11 | 0.00 | 0.163602E+12 | 0.548087E+10 |
March | 0.193779E+12 | 0.247159E+11 | 0.00 | 0.193343E+12 | 0.206266E+10 |
April | 0.344735E+12 | 0.219531E+11 | 0.00 | 0.204389E+12 | 0.132432E+10 |
May | 0.424273E+12 | 0.133476E+11 | 0.00 | 0.255070E+12 | 0.151580E+11 |
June | 0.435753E+12 | 0.737993E+10 | 0.00 | 0.222210E+12 | 0.691282E+11 |
July | 0.396019E+12 | 0.570802E+10 | 0.00 | 0.228234E+12 | 0.946608E+11 |
August | 0.298001E+12 | 0.789465E+10 | 0.00 | 0.231936E+12 | 0.516542E+11 |
September | 0.141045E+12 | 0.106104E+11 | 0.00 | 0.223033E+12 | 0.455173E+10 |
October | 0.562384E+11 | 0.202431E+11 | 0.00 | 0.184444E+12 | 0.659211E+09 |
November | -0.685997E+10 | 0.154451E+11 | 0.00 | 0.190778E+12 | 0.806033E+10 |
December | -0.340516E+11 | 0.197056E+11 | 0.00 | 0.197886E+12 | 0.120812E+11 |
Annual Sum or Average | 0.225839E+13 | 0.188355E+12 | 0.00 | 0.248241E+13 | 0.273969E+12 |
Minimum of Months | -0.340516E+11 | 0.570802E+10 | 0.00 | 0.163602E+12 | 0.659211E+09 |