Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:32:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1557.58 | 312.63 | 312.63 |
Net Site Energy | 1394.99 | 279.99 | 279.99 |
Total Source Energy | 4683.04 | 939.96 | 939.96 |
Net Source Energy | 4168.10 | 836.60 | 836.60 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 12.52 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 491.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 166.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 116.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1437.65 | 119.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 12.52 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 491.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 166.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 74.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 116.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 12.52 | 2.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 491.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 166.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 74.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 116.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 116.01 | 24.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 288.56 | 24.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 116.01 | 24.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 288.56 | 24.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 169.734 | 11.81 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -7.14 | -0.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 162.598 | 11.31 |
Electricity Coming From Utility | 1276.211 | 88.77 |
Surplus Electricity Going To Utility | 1.160 | 0.08 |
Net Electricity From Utility | 1275.051 | 88.69 |
Total On-Site and Utility Electric Sources | 1437.649 | 100.00 |
Total Electricity End Uses | 1437.649 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 71.00 |
Time Setpoint Not Met During Occupied Cooling | 339.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1653.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:39 | 05-JAN-07:49 | - | - | - | - | - | - | - | - | - | - | 06-JAN-12:09 |
Heating | 0.00 | 23081.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72243.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38454.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 823.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12675.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8769.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 138107.69 | 31850.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 23081.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 72243.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 13903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 3918.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 48.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 823.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12675.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8769.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 39.66 | 3.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1556.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 526.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 107.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 234.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 126.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4553.04 | 130.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 7.96 | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 312.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 913.86 | 26.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 7.96 | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 312.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 105.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 913.86 | 26.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.29 | 0.327326 | 0.278000 | 0.636518 | 0.872868 | 0.500000 | 0.001164 |
CORE_MID VAV BOX COMPONENT | 1.91 | 0.393112 | 0.334000 | 0.636760 | 1.00 | 0.500000 | 0.000969 |
CORE_TOP VAV BOX COMPONENT | 2.06 | 0.363851 | 0.309000 | 0.636474 | 0.970268 | 0.500000 | 0.001047 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.654068 | 0.241553 | 0.205000 | 0.134084 | 0.644140 | 0.500000 | 0.001577 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.662160 | 0.151054 | 0.128000 | 0.084756 | 0.402810 | 0.500000 | 0.002522 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.799801 | 0.197539 | 0.168000 | 0.134367 | 0.526770 | 0.500000 | 0.001929 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.736274 | 0.135840 | 0.115000 | 0.084672 | 0.362239 | 0.500000 | 0.002805 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.553644 | 0.285367 | 0.243000 | 0.134536 | 0.760978 | 0.500000 | 0.001335 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.587659 | 0.170204 | 0.145000 | 0.085211 | 0.453877 | 0.500000 | 0.002238 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.685473 | 0.230486 | 0.196000 | 0.134353 | 0.614629 | 0.500000 | 0.001653 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.613979 | 0.162897 | 0.138000 | 0.084729 | 0.434391 | 0.500000 | 0.002339 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.561623 | 0.281312 | 0.239000 | 0.134228 | 0.750167 | 0.500000 | 0.001354 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.637578 | 0.418341 | 0.500000 | 0.002429 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.705538 | 0.223931 | 0.190000 | 0.134052 | 0.597149 | 0.500000 | 0.001701 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.667285 | 0.149884 | 0.127000 | 0.084745 | 0.399690 | 0.500000 | 0.002542 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21241.37 |
CORE_MID VAV BOX REHEAT COIL | 21249.48 |
CORE_TOP VAV BOX REHEAT COIL | 26577.60 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11345.94 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7400.06 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11318.78 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7386.82 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7498.91 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4984.16 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7461.78 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4959.58 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8852.74 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5855.10 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8806.09 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5831.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.37 | 1.08 | 4.73 | 1.17 | 4.26 | 4.26 | 0.300000 | 0.275200 | 4.26 |
PACU_VAV_MID | 2.24 | 1.07 | 4.48 | 1.30 | 3.90 | 3.90 | 0.300000 | 0.334328 | 3.90 |
PACU_VAV_TOP | 2.46 | 1.07 | 4.91 | 1.98 | 4.60 | 4.60 | 0.300000 | 0.429943 | 4.60 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.26 |
PACU_VAV_MID_OA_CONTROLLER | 3.90 |
PACU_VAV_TOP_OA_CONTROLLER | 4.60 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.26 | 101287.34 | 0.714668 | 1.42 | 33759.07 | 0.714668 |
PACU_VAV_MID COOLING COIL | 3.90 | 95473.19 | 0.705642 | 1.30 | 31821.22 | 0.705642 |
PACU_VAV_TOP COOLING COIL | 4.60 | 107119.59 | 0.721084 | 1.53 | 35702.96 | 0.721084 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 6302.33 |
PACU_VAV_MID HEATING COIL | 7644.73 |
PACU_VAV_TOP HEATING COIL | 5290.19 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.26 |
PACU_VAV_MID FAN | 3.90 |
PACU_VAV_TOP FAN | 4.60 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.015 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7516 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7656 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5610 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27848788E-12 | 0.13637022E-14 | -0.81023097E-13 | 0.79216012E-16 |
43 | 6 | 0.25824895E-07 | 0.27625343E-09 | 0.59397345E-08 | -0.11998209E-12 |
44 | 5 | -0.17554640E-03 | 0.24097886E-05 | -0.90470599E-04 | 0.58795774E-08 |
45 | 4 | 0.27494803 | 0.11927753E-02 | 0.93505830E-01 | -0.31160983E-04 |
46 | 3 | -6.9253412 | 0.37505722E-01 | -2.2377579 | 0.27339040E-01 |
47 | 2 | 39.746130 | 0.13507978 | 14.849253 | -0.32081291 |
48 | 1 | -79.683230 | 0.61641880E-01 | -28.768593 | 1.0602386 |
49 | 0 | 46.824344 | 0.12537427E-02 | 16.300359 | |
50 | 7 | -0.27402251E-12 | 0.13062726E-14 | -0.81664977E-13 | 0.79643054E-16 |
51 | 6 | 0.25995733E-07 | 0.27297844E-09 | 0.59774430E-08 | -0.12089174E-12 |
52 | 5 | -0.17642699E-03 | 0.23783059E-05 | -0.90913883E-04 | 0.59164366E-08 |
53 | 4 | 0.27599802 | 0.11759213E-02 | 0.93882490E-01 | -0.31307097E-04 |
54 | 3 | -6.9461820 | 0.36940511E-01 | -2.2439388 | 0.27441040E-01 |
55 | 2 | 39.814917 | 0.13293308 | 14.874721 | -0.32157873 |
56 | 1 | -79.735998 | 0.60618496E-01 | -28.791459 | 1.0613631 |
57 | 0 | 46.824344 | 0.12320537E-02 | 16.299787 | |
58 | 7 | -0.27749376E-12 | 0.16893975E-14 | -0.84125370E-13 | 0.18079425E-15 |
59 | 6 | 0.22886636E-07 | 0.32835403E-09 | 0.52910653E-08 | -0.10444131E-12 |
60 | 5 | -0.16025164E-03 | 0.29299438E-05 | -0.82748939E-04 | 0.52444335E-08 |
61 | 4 | 0.25649379 | 0.14793778E-02 | 0.86896489E-01 | -0.28615133E-04 |
62 | 3 | -6.5585231 | 0.47340314E-01 | -2.1290029 | 0.25545250E-01 |
63 | 2 | 38.534810 | 0.17312159 | 14.399826 | -0.30733026 |
64 | 1 | -78.753333 | 0.80044855E-01 | -28.364722 | 1.0404251 |
65 | 0 | 46.824351 | 0.16491755E-02 | 16.310723 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4003E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4386E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7537E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.7852E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1459E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1701E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.1361E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9099E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1001 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1090E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3231E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8193E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4025E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4517E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7561E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.7996E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1484E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1812E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0725E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8337E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8295E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6288E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8510E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3853E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5465E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5614E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3494E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3603E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0998E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1039E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8425E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8791E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4109E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4404E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1149E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1365E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6036E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4634E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0308E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1279E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8540E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.8596E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8417E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8781E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4097E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4376E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1127E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1288E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8177E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2696E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3259E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9526E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6215E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8361E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7302E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7593E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3629E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3915E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3360E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3522E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.7680E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9234E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1064 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.1777E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.9586E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.6597E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9147E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7413E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6882E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5454E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7400E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3179E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.9965E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9420E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3838E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5450E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2035E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1688E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6967E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2027E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2292E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9003E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5453E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7926E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.7675E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.9228E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1064 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.1771E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.9580E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.6592E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.9146E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7411E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6880E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5452E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7396E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3177E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.9965E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9420E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3839E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5450E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2034E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1687E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6967E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2026E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2291E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9002E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5451E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7924E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 31772.11055 | 31772.11055 | 2.28963 | 2.28963 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5315.61970 | 5315.61970 | 0.22388 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26479.39845 | 26479.39845 | 1.90647 | 1.90647 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10008.48448 | 10008.48448 | 0.42168 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28326.32413 | 28326.32413 | 2.05979 | 2.05979 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66300 | 1.65359E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 18767.88216 | 18767.88216 | 0.79642 | 0.79642 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8994.10282 | 8994.10282 | 0.65407 | 0.65407 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8671.39458 | 8671.39458 | 0.33999 | 0.33999 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9105.41240 | 9105.41240 | 0.66216 | 0.66216 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5650.66551 | 5650.66551 | 0.22175 | 0.22175 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10998.13056 | 10998.13056 | 0.79980 | 0.79980 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8651.34784 | 8651.34784 | 0.33918 | 0.33918 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10124.59613 | 10124.59613 | 0.73627 | 0.73627 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5640.89441 | 5640.89441 | 0.22135 | 0.22135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7613.46947 | 7613.46947 | 0.55364 | 0.55364 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5282.77224 | 5282.77224 | 0.22471 | 0.22471 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8081.27220 | 8081.27220 | 0.58766 | 0.58766 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3510.18092 | 3510.18092 | 0.14935 | 0.14935 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9426.34012 | 9426.34012 | 0.68547 | 0.68547 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5256.77900 | 5256.77900 | 0.22360 | 0.22360 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8443.22655 | 8443.22655 | 0.61398 | 0.61398 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 32.53067 | 1.65338E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3492.97014 | 3492.97014 | 0.14862 | 0.14862 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7722.98856 | 7722.98856 | 0.56162 | 0.56162 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6231.70557 | 6231.70557 | 0.26528 | 0.26528 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8767.51022 | 8767.51022 | 0.63758 | 0.63758 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 30.89800 | 1.65307E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4120.84210 | 4120.84210 | 0.17545 | 0.17545 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9702.01572 | 9702.01572 | 0.70554 | 0.70554 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6199.01703 | 6199.01703 | 0.26388 | 0.26388 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9176.02668 | 9176.02668 | 0.66729 | 0.66729 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4104.40388 | 4104.40388 | 0.17475 | 0.17475 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 68947.93 | 4.25500 | 4.25500 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 9288.00 | 1.17098 | 1.17098 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 63971.20 | 3.90054 | 3.90054 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 9300.57 | 1.30406 | 1.30406 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73322.10 | 4.59534 | 4.59534 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 9201.27 | 1.97573 | 1.97573 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28963 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32733 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63652 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87287 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16398E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21241.37246 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.90647 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39311 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63676 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.69190E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21249.47667 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05979 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36385 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63647 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97027 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04713E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26577.60317 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65407 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24155 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13408 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64414 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57730E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11345.93943 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66216 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15105 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47564E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40281 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52228E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7400.06362 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79980 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19754 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16800 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13437 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52677 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92874E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11318.78083 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73627 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13584 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46715E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36224 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80478E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7386.82259 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55364 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28537 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13454 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76098 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33512E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7498.91137 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58766 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17020 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14500 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52106E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45388 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23849E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4984.15728 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68547 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23049 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13435 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61463 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65303E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7461.77715 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61398 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16290 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47292E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43439 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33891E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4959.57742 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56162 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28131 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13423 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75017 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35437E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8852.74166 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63758 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41834 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42864E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5855.10431 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70554 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22393 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13405 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59715 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70142E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8806.09064 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66729 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14988 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47452E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39969 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54197E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5831.65015 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.36519 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07535 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.73039 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.17098 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.25500 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.25500 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.27520 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.23925 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07458 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.47849 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30406 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.90054 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 3.90054 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.33433 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.45604 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07435 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.91209 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.97573 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.59534 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.59534 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.42994 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.25500 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 3.90054 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.59534 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.25500 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.25500 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 101287.34444 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71467 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.41819 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33759.07190 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71467 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 6302.33308 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.25500 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.90054 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 3.90054 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95473.19427 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70564 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.30005 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31821.21565 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70564 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 7644.73274 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 3.90054 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.59534 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.59534 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107119.59047 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72108 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53163 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35702.95950 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72108 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 5290.19252 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.59534 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 100985.69 | 344577.49 | 12.07 | 3.09 | 3.46 | 3.65 | 3.79 | 10.54 | 11.80 | 12.44 | 12.92 | 4.9173 | 3.8995 | 2.6250 | 1.1149 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 95274.09 | 325088.68 | 12.12 | 3.10 | 3.47 | 3.66 | 3.80 | 10.58 | 11.86 | 12.51 | 12.95 | 4.5077 | 3.5727 | 2.4061 | 1.0308 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 106726.85 | 364167.13 | 12.02 | 3.08 | 3.44 | 3.63 | 3.78 | 10.51 | 11.75 | 12.39 | 12.88 | 5.3106 | 4.2141 | 2.8365 | 1.1983 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1972299162 | 0.2382583884 | Pass | Pass | 0.2457903779 | 0.4286569303 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1510169006E-002 | 8.5948881261E-002 | Pass | Pass | 0.4208084324 | 2.3577287883 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.1568988833E-002 | 3.4661766857E-002 | Pass | Pass | 0.2122284114 | 0.4046517347 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.4130141637E-002 | 4.4819124694E-002 | Pass | Pass | 0.4303024934 | 2.0984719969 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1407302782 | 0.2087536689 | Pass | Pass | 0.2032757971 | 0.4017141059 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1466138713 | 0.2063494447 | Pass | Pass | 0.1953586739 | 0.3943741584 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1397559647 | 0.1877366012 | Pass | Pass | 0.1951837829 | 0.3937625871 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1772606574 | 0.2066317104 | Pass | Pass | 0.2111383431 | 0.4285833750 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3437925881 | 0.5553918025 | Pass | Pass | 0.2322035649 | 0.4713844092 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1948671921 | 0.3126934409 | Pass | Pass | 0.2167282748 | 0.4442098018 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1686772874 | 0.2017987319 | Pass | Pass | 0.2449904863 | 0.4281539202 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2037098356 | 0.2177175287 | Pass | Pass | 0.2454373374 | 0.4297774519 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3652182597 | 0.5166010429 | Pass | Pass | 0.2851313954 | 0.4898942465 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2013521336 | 0.2678234257 | Pass | Pass | 0.2508950482 | 0.4357515372 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1356078237 | 0.1915249007 | Pass | Pass | 0.2025898592 | 0.4013931424 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1749186415 | 0.2191968855 | Pass | Pass | 0.2030638968 | 0.4029643804 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3069465440 | 0.5447470298 | Pass | Pass | 0.2485142223 | 0.4971495745 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1759288191 | 0.2819424336 | Pass | Pass | 0.2156317666 | 0.4263606665 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3087.69 | -54.1 | 0.00 | 137.79 | 2546.65 | 5718.02 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.455_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.455_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.455_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.586 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.30 | 0.0000 | Y | 4.81 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.19 | 0.0000 | Y | 3.03 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.03 | 0.0000 | Y | 4.75 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.19 | 0.0000 | Y | 3.03 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.25 | 0.0000 | Y | 4.80 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.15 | 0.0000 | Y | 3.02 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.00 | 0.0000 | Y | 4.74 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.15 | 0.0000 | Y | 3.02 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.30 | 0.0000 | Y | 4.81 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.19 | 0.0000 | Y | 3.03 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.03 | 0.0000 | Y | 4.75 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.19 | 0.0000 | Y | 3.03 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 166.22 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 41.73 | 41.73 | 4.25 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.73 | 62.73 | 3.30 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.73 | 47.05 | 26.52 | |
Exterior Lighting Total | 3824.74 | 34.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 101287.34 | 72386.83 | 28900.52 | 0.71 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95473.19 | 67369.92 | 28103.27 | 0.71 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 107119.59 | 77242.25 | 29877.34 | 0.72 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 100985.7 | 3.09 | 10.54 | N/A | N/A | 12.07 | |
PACU_VAV_MID COOLING COIL | 95274.1 | 3.10 | 10.58 | N/A | N/A | 12.12 | |
PACU_VAV_TOP COOLING COIL | 106726.9 | 3.08 | 10.51 | N/A | N/A | 12.02 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21241.37 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21249.48 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26577.60 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11345.94 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7400.06 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11318.78 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7386.82 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7498.91 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4984.16 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7461.78 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4959.58 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8852.74 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5855.10 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8806.09 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5831.65 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 6302.33 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 7644.73 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 5290.19 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.26 | 9314.24 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 3.90 | 8538.32 | 2189.01 | 1.00 | 1.15 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.60 | 10059.25 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 100985.69 | 3.09 | 10.54 | 12.07 | 4.9173 | 3.46 | 11.80 | 3.8995 | 3.65 | 12.44 | 2.6250 | 3.79 | 12.92 | 1.1149 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95274.09 | 3.10 | 10.58 | 12.12 | 4.5077 | 3.47 | 11.86 | 3.5727 | 3.66 | 12.51 | 2.4061 | 3.80 | 12.95 | 1.0308 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106726.85 | 3.08 | 10.51 | 12.02 | 5.3106 | 3.44 | 11.75 | 4.2141 | 3.63 | 12.39 | 2.8365 | 3.78 | 12.88 | 1.1983 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 31772.11 | 31772.11 | 32.30 | 2.290 | 2.290 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_MID | 26479.40 | 26479.40 | 26.92 | 1.906 | 1.906 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_TOP | 28326.32 | 28326.32 | 28.80 | 2.060 | 2.060 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00892 | 33.66 | 0.01654 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8994.10 | 8994.10 | 43.38 | 0.654 | 0.654 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00903 | 33.82 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9105.41 | 9105.41 | 69.37 | 0.662 | 0.662 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00885 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10998.13 | 10998.13 | 53.04 | 0.800 | 0.800 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00894 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10124.60 | 10124.60 | 77.14 | 0.736 | 0.736 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00881 | 32.79 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7613.47 | 7613.47 | 36.72 | 0.554 | 0.554 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00899 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8081.27 | 8081.27 | 61.57 | 0.588 | 0.588 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00880 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9426.34 | 9426.34 | 45.46 | 0.685 | 0.685 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00890 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8443.23 | 8443.23 | 64.33 | 0.614 | 0.614 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 24.00 | 24.00 | 0.00879 | 32.53 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7722.99 | 7722.99 | 37.25 | 0.562 | 0.562 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00907 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8767.51 | 8767.51 | 66.79 | 0.638 | 0.638 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 24.00 | 24.00 | 0.00883 | 30.90 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9702.02 | 9702.02 | 46.79 | 0.706 | 0.706 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00896 | 33.83 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9176.03 | 9176.03 | 69.91 | 0.667 | 0.667 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00881 | 32.79 | 0.01653 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5315.62 | 5315.62 | 5.40 | 0.224 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_MID | 10008.48 | 10008.48 | 10.18 | 0.422 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_TOP | 18767.88 | 18767.88 | 19.08 | 0.796 | 0.796 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8671.39 | 8671.39 | 41.82 | 0.340 | 0.340 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00752 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5650.67 | 5650.67 | 43.05 | 0.222 | 0.222 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.69 | 0.00754 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8651.35 | 8651.35 | 41.73 | 0.339 | 0.339 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00751 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5640.89 | 5640.89 | 42.98 | 0.221 | 0.221 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.69 | 0.00754 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5282.77 | 5282.77 | 25.48 | 0.225 | 0.225 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3510.18 | 3510.18 | 26.74 | 0.149 | 0.149 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5256.78 | 5256.78 | 25.35 | 0.224 | 0.224 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3492.97 | 3492.97 | 26.61 | 0.149 | 0.149 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6231.71 | 6231.71 | 30.06 | 0.265 | 0.265 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00759 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4120.84 | 4120.84 | 31.39 | 0.175 | 0.175 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6199.02 | 6199.02 | 29.90 | 0.264 | 0.264 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4104.40 | 4104.40 | 31.27 | 0.175 | 0.175 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00759 | 4.60 | 0.00526 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.26 | 4.26 | 1.17 | 1.17 | 4.2550 | 1.1710 | 4.2550 | 0.2752 | 0.3000 |
PACU_VAV_MID | 3.90 | 3.90 | 1.30 | 1.30 | 3.9005 | 1.3041 | 3.9005 | 0.3343 | 0.3000 |
PACU_VAV_TOP | 4.60 | 4.60 | 1.98 | 1.98 | 4.5953 | 1.9757 | 4.5953 | 0.4299 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21241.372 | 21241.372 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21241.37 | 14172.46 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 5315.62 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21249.477 | 21249.477 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21249.48 | 14172.46 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 10008.48 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26577.603 | 26577.603 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26577.60 | 26577.60 | 0.796423 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 18767.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11345.939 | 11345.939 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11345.94 | 11345.94 | 0.339992 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00751549 | 49.5024 | 8671.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7400.064 | 7400.064 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7400.06 | 7400.06 | 0.221750 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.69 | 0.00753856 | 49.6532 | 5650.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11318.781 | 11318.781 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11318.78 | 11318.78 | 0.339178 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00751108 | 49.4737 | 8651.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7386.823 | 7386.823 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7386.82 | 7386.82 | 0.221353 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.69 | 0.00753533 | 49.6322 | 5640.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7498.911 | 7498.911 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7498.91 | 7498.91 | 0.224712 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00760550 | 49.1602 | 5282.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4984.157 | 4984.157 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4984.16 | 4984.16 | 0.149355 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00761428 | 49.2163 | 3510.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7461.777 | 7461.777 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7461.78 | 7461.78 | 0.223599 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00760296 | 49.1440 | 5256.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4959.577 | 4959.577 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4959.58 | 4959.58 | 0.148618 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00761174 | 49.2001 | 3492.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8852.742 | 8852.742 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8852.74 | 8852.74 | 0.265281 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00758522 | 49.0314 | 6231.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5855.104 | 5855.104 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5855.10 | 5855.10 | 0.175454 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00759607 | 49.1007 | 4120.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8806.091 | 8806.091 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8806.09 | 8806.09 | 0.263883 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00758217 | 49.0119 | 6199.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5831.650 | 5831.650 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5831.65 | 5831.65 | 0.174751 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00759378 | 49.0860 | 4104.40 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 101287.344 | 72386.827 | 4.255001 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 103652.12 | 76006.78 | 4.255001 | 26.23 | 18.88 | 0.01063179 | 11.02 | 11.02 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 22.4700 | 24.00 | 0.00891639 | 47.9304 | 58405.60 | 0.00 | 104440.85 | 73594.50 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 6302.333 | 6302.333 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6302.33 | 6302.33 | 1.276500 | 8.72 | 7.48 | 0.00592220 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 74.9001 | 21.00 | 0.00786661 | 50.8243 | 15888.17 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 95473.194 | 67369.923 | 3.900538 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 98330.27 | 70426.16 | 3.900538 | 26.41 | 19.11 | 0.01085164 | 11.03 | 11.03 | 0.00850000 | 33.82 | 0.01653623 | 25.11 | 24.5120 | 24.00 | 0.00899682 | 48.3572 | 53443.21 | 0.00 | 98445.68 | 68507.42 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 7644.733 | 7644.733 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7644.73 | 7644.73 | 1.170161 | 7.40 | 6.52 | 0.00565238 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 81.7067 | 19.60 | 0.00715037 | 50.4363 | 16653.17 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 107119.590 | 77242.246 | 4.595339 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 109378.50 | 81002.07 | 4.595339 | 26.01 | 18.73 | 0.01052321 | 11.02 | 11.02 | 0.00850000 | 33.66 | 0.01653594 | 25.07 | 20.8059 | 24.00 | 0.00894145 | 48.0639 | 63126.44 | 0.00 | 110454.68 | 78481.75 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 5290.193 | 5290.193 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5290.19 | 5290.19 | 1.378602 | 9.63 | 8.06 | 0.00604990 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 69.3529 | 19.01 | 0.00781750 | 57.1439 | 18511.12 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21241.372 | 21241.372 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21241.37 | 14172.46 | 1.0000 | 0.51097426 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21241.37 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.68 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 5315.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21249.477 | 21249.477 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21249.48 | 14172.46 | 1.0000 | 0.51097426 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21249.48 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.83 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 10008.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26577.603 | 26577.603 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26577.60 | 26577.60 | 1.0000 | 0.95822953 | 0.796423 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26577.60 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 18767.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11345.939 | 11345.939 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11345.94 | 11345.94 | 1.0000 | 0.40906677 | 0.339992 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11345.94 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00751549 | 20.70 | 0.00751549 | 49.5024 | 8671.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7400.064 | 7400.064 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7400.06 | 7400.06 | 1.0000 | 0.26680207 | 0.221750 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7400.06 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00753856 | 20.69 | 0.00753856 | 49.6532 | 5650.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11318.781 | 11318.781 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11318.78 | 11318.78 | 1.0000 | 0.40808759 | 0.339178 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11318.78 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00751108 | 20.70 | 0.00751108 | 49.4737 | 8651.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7386.823 | 7386.823 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7386.82 | 7386.82 | 1.0000 | 0.26632467 | 0.221353 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7386.82 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00753533 | 20.69 | 0.00753533 | 49.6322 | 5640.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7498.911 | 7498.911 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7498.91 | 7498.91 | 1.0000 | 0.27036593 | 0.224712 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7498.91 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00760550 | 21.00 | 0.00760550 | 49.1602 | 5282.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4984.157 | 4984.157 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4984.16 | 4984.16 | 1.0000 | 0.17969892 | 0.149355 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4984.16 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00761428 | 21.00 | 0.00761428 | 49.2163 | 3510.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7461.777 | 7461.777 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7461.78 | 7461.78 | 1.0000 | 0.26902709 | 0.223599 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7461.78 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00760296 | 21.00 | 0.00760296 | 49.1440 | 5256.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4959.577 | 4959.577 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4959.58 | 4959.58 | 1.0000 | 0.17881272 | 0.148618 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4959.58 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00761174 | 21.00 | 0.00761174 | 49.2001 | 3492.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8852.742 | 8852.742 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8852.74 | 8852.74 | 1.0000 | 0.31917695 | 0.265281 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8852.74 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00758522 | 21.00 | 0.00758522 | 49.0314 | 6231.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5855.104 | 5855.104 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5855.10 | 5855.10 | 1.0000 | 0.21110007 | 0.175454 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5855.10 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00759607 | 21.00 | 0.00759607 | 49.1007 | 4120.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8806.091 | 8806.091 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8806.09 | 8806.09 | 1.0000 | 0.31749500 | 0.263883 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8806.09 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00758217 | 21.00 | 0.00758217 | 49.0119 | 6199.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5831.650 | 5831.650 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5831.65 | 5831.65 | 1.0000 | 0.21025445 | 0.174751 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5831.65 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00759378 | 21.00 | 0.00759378 | 49.0860 | 4104.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 101287.344 | 72386.827 | 4.255001 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6040 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.255001 | 5.11947621 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 103652.12 | 76006.78 | 1.0233 | 5.11947621 | 4.255001 | 26.23 | 18.88 | 0.01063179 | 53462.3 | 11.02 | 11.02 | 0.00850000 | 32509.9 | -999.0 | -999.00 | -999.00 | -999.00 | 9314.244 | 94337.88 | 33.90 | 0.01653638 | 25.13 | 0.95610000 | 22.4700 | 24.00 | 0.00891639 | 24.00 | 0.00891639 | 47.9304 | 58405.60 | 0.00 | 104440.85 | 73594.50 | 4.91729560 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.01 | 12.00 | 0.00872515 | 34082.9 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6302.333 | 6302.333 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.255001 | 5.11947621 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6302.33 | 6302.33 | 1.0000 | 1.53584286 | 1.276500 | 8.72 | 7.48 | 0.00592220 | 23665.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6302.33 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 74.9001 | 21.00 | 0.00790678 | 21.00 | 0.00786661 | 50.8243 | 15888.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95473.194 | 67369.923 | 3.900538 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0126 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.900538 | 4.69299792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 98330.27 | 70426.16 | 1.0299 | 4.69299792 | 3.900538 | 26.41 | 19.11 | 0.01085164 | 54214.9 | 11.03 | 11.03 | 0.00850000 | 32510.6 | -999.0 | -999.00 | -999.00 | -999.00 | 8538.320 | 89791.95 | 33.82 | 0.01653623 | 25.11 | 0.95610000 | 24.5120 | 24.00 | 0.00899682 | 24.00 | 0.00899682 | 48.3572 | 53443.21 | 0.00 | 98445.68 | 68507.42 | 4.50765998 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.78 | 11.76 | 0.00858062 | 33482.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7644.733 | 7644.733 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.900538 | 4.69299792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7644.73 | 7644.73 | 1.0000 | 1.40789938 | 1.170161 | 7.40 | 6.52 | 0.00565238 | 21646.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7644.73 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 81.7067 | 19.89 | 0.00741768 | 19.60 | 0.00715037 | 50.4363 | 16653.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107119.590 | 77242.246 | 4.595339 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4021 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.595339 | 5.52895991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 109378.50 | 81002.07 | 1.0211 | 5.52895991 | 4.595339 | 26.01 | 18.73 | 0.01052321 | 52963.9 | 11.02 | 11.02 | 0.00850000 | 32509.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10059.248 | 99319.26 | 33.66 | 0.01653594 | 25.07 | 0.95610000 | 20.8059 | 24.00 | 0.00894145 | 24.00 | 0.00894145 | 48.0639 | 63126.44 | 0.00 | 110454.68 | 78481.75 | 5.31060779 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.20 | 12.17 | 0.00882413 | 34523.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5290.193 | 5290.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.595339 | 5.52895991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5290.19 | 5290.19 | 1.0000 | 1.65868797 | 1.378602 | 9.63 | 8.06 | 0.00604990 | 24911.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5290.19 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 69.3529 | 21.00 | 0.00784385 | 19.01 | 0.00781750 | 57.1439 | 18511.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.26 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 3.90 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.60 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 3877.67 | 967.00 | 0.00 |
CORE_MID | 3165.67 | 1724.67 | 0.83 |
CORE_TOP | 3194.17 | 2001.83 | 59.83 |
PERIMETER_TOP_ZN_3 | 3708.00 | 2410.00 | 591.33 |
PERIMETER_TOP_ZN_2 | 3945.33 | 2124.67 | 612.17 |
PERIMETER_TOP_ZN_1 | 4114.33 | 1763.83 | 546.67 |
PERIMETER_TOP_ZN_4 | 3955.67 | 2124.00 | 627.17 |
PERIMETER_BOT_ZN_3 | 3451.67 | 2224.00 | 174.67 |
PERIMETER_BOT_ZN_2 | 3903.67 | 1702.00 | 265.00 |
PERIMETER_BOT_ZN_1 | 4275.67 | 2267.17 | 1091.00 |
PERIMETER_BOT_ZN_4 | 3909.00 | 1683.83 | 233.50 |
PERIMETER_MID_ZN_3 | 3596.33 | 2158.33 | 305.17 |
PERIMETER_MID_ZN_2 | 3283.33 | 1728.50 | 429.50 |
PERIMETER_MID_ZN_1 | 4172.50 | 1462.17 | 365.50 |
PERIMETER_MID_ZN_4 | 3937.67 | 1865.17 | 412.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4897.17 | 3530.00 | 1653.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.33 | 20.33 | 0.33 | 16.50 |
PERIMETER_TOP_ZN_2 | 0.33 | 66.67 | 0.33 | 60.83 |
PERIMETER_TOP_ZN_1 | 0.17 | 57.33 | 0.17 | 53.33 |
PERIMETER_TOP_ZN_4 | 0.33 | 56.83 | 0.33 | 37.83 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 34.50 | 0.00 | 34.17 |
PERIMETER_BOT_ZN_1 | 70.67 | 218.17 | 70.67 | 217.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 32.17 | 0.00 | 23.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.83 | 0.00 | 0.83 |
PERIMETER_MID_ZN_2 | 0.00 | 50.00 | 0.00 | 49.33 |
PERIMETER_MID_ZN_1 | 0.00 | 41.17 | 0.00 | 40.17 |
PERIMETER_MID_ZN_4 | 0.00 | 43.67 | 0.00 | 30.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 71.00 | 366.17 | 71.00 | 339.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.524 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.463 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.458 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.565 | 0.065 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.715 | 0.069 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.770 | 0.065 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.713 | 0.069 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.511 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.661 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.735 | 1.274 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.650 | 0.037 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.567 | 0.054 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.662 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.783 | 0.054 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.722 | 0.057 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8246226.39 | 0.00 | 8246226.39 | 0.00 | 8246226.39 | 13393058.27 | 6421.06 | 236.11 | 2102.83 | 2.28 |
CORE_MID | 7287721.72 | 0.00 | 7287721.72 | 0.00 | 7287721.72 | 13393058.27 | 6914.22 | 260.88 | 1584.89 | 2.67 |
CORE_TOP | 7214521.07 | 0.00 | 7214521.07 | 0.00 | 7214521.07 | 13393058.27 | 6895.16 | 282.98 | 1581.87 | 3.00 |
PERIMETER_TOP_ZN_3 | 1874933.85 | 0.00 | 1874933.85 | 422189.62 | 2297123.47 | 2823374.22 | 4634.41 | 299.59 | 3826.00 | 3.00 |
PERIMETER_TOP_ZN_2 | 1500526.18 | 0.00 | 1500526.18 | 281458.05 | 1781984.23 | 1787429.43 | 4370.03 | 258.94 | 4131.03 | 3.00 |
PERIMETER_TOP_ZN_1 | 2556271.55 | 0.00 | 2556271.55 | 422189.62 | 2978461.17 | 2823374.22 | 4363.06 | 148.26 | 4248.69 | 3.00 |
PERIMETER_TOP_ZN_4 | 1497889.84 | 0.00 | 1497889.84 | 281458.05 | 1779347.90 | 1787312.18 | 4472.60 | 299.03 | 3988.38 | 3.00 |
PERIMETER_BOT_ZN_3 | 1697111.22 | 0.00 | 1697111.22 | 224477.40 | 1921588.62 | 2823374.22 | 5487.06 | 226.18 | 3046.76 | 2.28 |
PERIMETER_BOT_ZN_2 | 1388320.55 | 0.00 | 1388320.55 | 149650.70 | 1537971.25 | 1787429.43 | 4493.55 | 120.67 | 4145.78 | 2.28 |
PERIMETER_BOT_ZN_1 | 2434051.91 | 0.00 | 2434051.91 | 4323043.00 | 6757094.92 | 2823374.22 | 4594.13 | 151.18 | 4014.69 | 2.28 |
PERIMETER_BOT_ZN_4 | 1364607.89 | 0.00 | 1364607.89 | 149650.70 | 1514258.59 | 1787312.18 | 4666.16 | 247.57 | 3846.27 | 2.28 |
PERIMETER_MID_ZN_3 | 1883069.86 | 0.00 | 1883069.86 | 351441.55 | 2234511.41 | 2823374.22 | 4682.63 | 240.39 | 3836.98 | 2.67 |
PERIMETER_MID_ZN_2 | 1412473.98 | 0.00 | 1412473.98 | 234292.96 | 1646766.94 | 1601953.02 | 4361.63 | 209.94 | 4188.43 | 911.67 |
PERIMETER_MID_ZN_1 | 2597477.75 | 0.00 | 2597477.75 | 351441.55 | 2948919.30 | 2823374.22 | 4354.36 | 203.20 | 4202.43 | 2.67 |
PERIMETER_MID_ZN_4 | 1515255.99 | 0.00 | 1515255.99 | 234292.96 | 1749548.95 | 1787312.18 | 4472.47 | 235.35 | 4052.17 | 2.67 |
Total Facility | 44470459.75 | 0.00 | 44470459.75 | 7425586.18 | 51896045.92 | 67658168.57 | 7268.13 | 846.95 | 4469.65 | 912.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3852 | 0.0000 | 0.3852 | 0.0000 | 0.3852 | 0.4247 | 3606.34 | 236.11 | 2100.55 |
CORE_MID | 0.3403 | 0.0000 | 0.3403 | 0.0000 | 0.3403 | 0.4247 | 4099.89 | 260.88 | 1582.23 |
CORE_TOP | 0.3369 | 0.0000 | 0.3369 | 0.0000 | 0.3369 | 0.4247 | 4080.66 | 282.98 | 1579.37 |
PERIMETER_TOP_ZN_3 | 0.0876 | 0.0000 | 0.0876 | 0.0101 | 0.0977 | 0.0895 | 1819.91 | 299.59 | 3823.50 |
PERIMETER_TOP_ZN_2 | 0.0701 | 0.0000 | 0.0701 | 0.0067 | 0.0768 | 0.0567 | 1555.53 | 258.94 | 4128.53 |
PERIMETER_TOP_ZN_1 | 0.1194 | 0.0000 | 0.1194 | 0.0101 | 0.1295 | 0.0895 | 1548.56 | 148.26 | 4246.19 |
PERIMETER_TOP_ZN_4 | 0.0700 | 0.0000 | 0.0700 | 0.0067 | 0.0767 | 0.0567 | 1658.10 | 299.03 | 3985.88 |
PERIMETER_BOT_ZN_3 | 0.0793 | 0.0000 | 0.0793 | 0.0054 | 0.0847 | 0.0895 | 2672.33 | 226.18 | 3044.48 |
PERIMETER_BOT_ZN_2 | 0.0649 | 0.0000 | 0.0649 | 0.0036 | 0.0684 | 0.0567 | 1678.83 | 120.67 | 4143.50 |
PERIMETER_BOT_ZN_1 | 0.1137 | 0.0000 | 0.1137 | 0.1969 | 0.3107 | 0.0895 | 1779.40 | 151.18 | 4012.41 |
PERIMETER_BOT_ZN_4 | 0.0637 | 0.0000 | 0.0637 | 0.0036 | 0.0673 | 0.0567 | 1851.43 | 247.57 | 3843.99 |
PERIMETER_MID_ZN_3 | 0.0880 | 0.0000 | 0.0880 | 0.0084 | 0.0964 | 0.0895 | 1868.30 | 240.39 | 3834.31 |
PERIMETER_MID_ZN_2 | 0.0649 | 0.0000 | 0.0649 | 0.0060 | 0.0709 | 0.0567 | 1547.30 | 209.94 | 3276.76 |
PERIMETER_MID_ZN_1 | 0.1213 | 0.0000 | 0.1213 | 0.0084 | 0.1298 | 0.0895 | 1540.03 | 203.20 | 4199.77 |
PERIMETER_MID_ZN_4 | 0.0708 | 0.0000 | 0.0708 | 0.0056 | 0.0764 | 0.0567 | 1658.14 | 235.35 | 4049.51 |
Total Facility | 2.0761 | 0.0000 | 2.0761 | 0.2716 | 2.3477 | 2.1513 | 4452.79 | 846.95 | 4466.37 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21902802.49 | 0.00 | 21902802.49 | 22614548.33 | 4275.75 | 1.14 | 4483.11 | 2.28 |
PACU_VAV_MID | 21274127.32 | 0.00 | 21274127.32 | 22429071.92 | 4268.41 | 0.79 | 4490.80 | 2.67 |
PACU_VAV_TOP | 21198954.30 | 0.00 | 21198954.30 | 22614548.33 | 4283.62 | 0.37 | 4476.01 | 3.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.0231 | 0.0000 | 1.0231 | 0.7171 | 1461.02 | 1.14 | 4480.83 |
PACU_VAV_MID | 0.9936 | 0.0000 | 0.9936 | 0.7084 | 1454.08 | 0.79 | 4488.14 |
PACU_VAV_TOP | 0.9901 | 0.0000 | 0.9901 | 0.7171 | 1469.12 | 0.37 | 4473.51 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 182.03 | 1310.92 | 0.00 | 0.00 | 0.00 | 2997.24 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 175.98 | 1268.55 | 0.00 | 0.00 | 0.00 | 3051.59 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 134.56 | 1219.22 | 0.00 | 0.00 | 0.00 | 3137.16 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2980 | 1.8386 | 0.0000 | 0.0000 | 0.0000 | 1.1476 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3016 | 1.7006 | 0.0000 | 0.0000 | 0.0000 | 1.1557 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.3098 | 1.7082 | 0.0000 | 0.0000 | 0.0000 | 1.1577 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2232 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1437.65 | 11240.73 | 02-JUL-17:40 | 138107.69 | 03-AUG-15:40 |
Electricity:Building | 813.97 | 11072.20 | 23-APR-17:10 | 57296.77 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 813.97 | 11072.20 | 23-APR-17:10 | 57296.77 | 25-OCT-07:10 |
InteriorLights:Electricity | 166.22 | 772.31 | 01-JAN-09:10 | 16858.98 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 166.22 | 772.31 | 01-JAN-09:10 | 16858.98 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 166.22 | 772.31 | 01-JAN-09:10 | 16858.98 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 166.22 | 772.31 | 01-JAN-09:10 | 16858.98 | 25-OCT-07:10 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.14 | 405.59 | 26-MAR-17:10 | 2092.31 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.81 | 19.49 | 01-JAN-09:00 | 657.07 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.81 | 19.49 | 01-JAN-09:00 | 657.07 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.43 | 256.76 | 23-APR-17:10 | 1314.58 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.03 | 12.34 | 01-JAN-07:50 | 406.01 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.03 | 12.34 | 01-JAN-07:50 | 406.01 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.08 | 405.59 | 12-MAR-17:10 | 2087.37 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.75 | 19.49 | 01-JAN-07:50 | 652.14 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.75 | 19.49 | 01-JAN-07:50 | 652.14 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.43 | 256.75 | 26-FEB-18:10 | 1328.04 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.03 | 12.34 | 01-JAN-09:10 | 419.47 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.03 | 12.34 | 01-JAN-09:10 | 419.47 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.13 | 405.59 | 26-MAR-17:10 | 2089.28 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.80 | 19.49 | 01-JAN-09:00 | 654.04 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.80 | 19.49 | 01-JAN-09:00 | 654.04 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.43 | 256.76 | 26-MAR-17:10 | 1312.66 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.02 | 12.34 | 01-JAN-07:50 | 404.09 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.02 | 12.34 | 01-JAN-07:50 | 404.09 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.08 | 405.59 | 12-MAR-17:10 | 2084.10 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.74 | 19.49 | 01-JAN-07:50 | 648.87 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.74 | 19.49 | 01-JAN-07:50 | 648.87 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.43 | 256.75 | 26-FEB-18:10 | 1326.62 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.02 | 12.34 | 01-JAN-09:00 | 418.05 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.02 | 12.34 | 01-JAN-09:00 | 418.05 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.14 | 405.59 | 26-MAR-17:10 | 2092.31 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.81 | 19.49 | 01-JAN-09:00 | 657.06 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.81 | 19.49 | 01-JAN-09:00 | 657.06 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.43 | 256.76 | 23-APR-17:10 | 1314.58 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.03 | 12.34 | 01-JAN-07:50 | 406.00 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.03 | 12.34 | 01-JAN-07:50 | 406.00 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.08 | 405.59 | 12-MAR-17:10 | 2087.37 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.75 | 19.49 | 01-JAN-07:50 | 652.13 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.75 | 19.49 | 01-JAN-07:50 | 652.13 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.43 | 256.75 | 26-FEB-18:10 | 1328.03 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.03 | 12.34 | 01-JAN-09:10 | 419.47 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.03 | 12.34 | 01-JAN-09:10 | 419.47 | 25-OCT-07:10 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 162.60 | -0.00 | 27-JAN-07:30 | 25865.13 | 10-APR-12:30 |
ElectricityProduced:Plant | 162.60 | -0.00 | 27-JAN-07:30 | 25865.13 | 10-APR-12:30 |
Photovoltaic:ElectricityProduced | 169.73 | 0.00 | 01-JAN-00:10 | 26932.77 | 10-APR-12:30 |
PowerConversion:ElectricityProduced | -7.14 | -1067.64 | 10-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-12:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 589.47 | 168.34 | 01-JAN-00:10 | 94299.65 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.71 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.71 | 25-OCT-07:20 |
ElectricityPurchased:Facility | 1276.21 | 0.00 | 15-JAN-11:00 | 127276.07 | 21-JUL-16:00 |
ElectricityPurchased:Plant | 1276.21 | 0.00 | 15-JAN-11:00 | 127276.07 | 21-JUL-16:00 |
Cogeneration:ElectricityPurchased | 1276.21 | 0.00 | 15-JAN-11:00 | 127276.07 | 21-JUL-16:00 |
General:Cogeneration:ElectricityPurchased | 1276.21 | 0.00 | 15-JAN-11:00 | 127276.07 | 21-JUL-16:00 |
ElectricitySurplusSold:Facility | 1.16 | 0.00 | 01-JAN-00:10 | 12276.19 | 16-APR-12:30 |
ElectricitySurplusSold:Plant | 1.16 | 0.00 | 01-JAN-00:10 | 12276.19 | 16-APR-12:30 |
Cogeneration:ElectricitySurplusSold | 1.16 | 0.00 | 01-JAN-00:10 | 12276.19 | 16-APR-12:30 |
General:Cogeneration:ElectricitySurplusSold | 1.16 | 0.00 | 01-JAN-00:10 | 12276.19 | 16-APR-12:30 |
ElectricityNet:Facility | 1275.05 | -12276.19 | 16-APR-12:30 | 127276.07 | 21-JUL-16:00 |
ElectricityNet:Plant | 1275.05 | -12276.19 | 16-APR-12:30 | 127276.07 | 21-JUL-16:00 |
Cogeneration:ElectricityNet | 1275.05 | -12276.19 | 16-APR-12:30 | 127276.07 | 21-JUL-16:00 |
General:Cogeneration:ElectricityNet | 1275.05 | -12276.19 | 16-APR-12:30 | 127276.07 | 21-JUL-16:00 |
Heating:Electricity | 12.52 | 0.00 | 01-JAN-00:10 | 90588.55 | 06-FEB-07:10 |
General:Heating:Electricity | 12.52 | 0.00 | 01-JAN-00:10 | 90588.55 | 06-FEB-07:10 |
Fans:Electricity | 74.01 | 0.00 | 01-JAN-00:10 | 13942.09 | 10-OCT-14:10 |
General:Fans:Electricity | 74.01 | 0.00 | 01-JAN-00:10 | 13942.09 | 10-OCT-14:10 |
ExteriorLights:Electricity | 34.06 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.06 | 0.00 | 01-JAN-07:30 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 491.32 | 0.00 | 01-JAN-00:10 | 72924.54 | 21-JUL-16:00 |
General:Cooling:Electricity | 491.32 | 0.00 | 01-JAN-00:10 | 72924.54 | 21-JUL-16:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-12:10 |
WIRED_LTG_ELECTRICITY | 4.67 | 0.00 | 01-JAN-00:10 | 473.74 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 119.93 | 1886.44 | 09-JAN-17:10 | 31850.94 | 05-JAN-07:50 |
NaturalGas:HVAC | 2.94 | 0.00 | 01-JAN-00:10 | 23266.78 | 05-JAN-08:00 |
Heating:NaturalGas | 2.94 | 0.00 | 01-JAN-00:10 | 23266.78 | 05-JAN-08:00 |
General:Heating:NaturalGas | 2.94 | 0.00 | 01-JAN-00:10 | 23266.78 | 05-JAN-08:00 |
NaturalGas:Plant | 116.99 | 1886.44 | 09-JAN-17:10 | 9719.79 | 23-JAN-12:10 |
WaterSystems:NaturalGas | 116.99 | 1886.44 | 09-JAN-17:10 | 9719.79 | 23-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 116.99 | 1886.44 | 09-JAN-17:10 | 9719.79 | 23-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3453.49 | 0.00 | 01-JAN-00:10 | 424014.46 | 06-OCT-14:10 |
EnergyTransfer:Building | 1345.61 | 0.00 | 01-JAN-00:10 | 154386.48 | 10-OCT-13:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 230.57 | 0.00 | 01-JAN-00:10 | 22006.14 | 10-OCT-08:00 |
Heating:EnergyTransfer | 9.44 | 0.00 | 01-JAN-00:10 | 64536.30 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.44 | 0.00 | 01-JAN-00:10 | 64536.30 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1336.17 | 0.00 | 01-JAN-00:10 | 154386.48 | 10-OCT-13:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 230.57 | 0.00 | 01-JAN-00:10 | 22006.14 | 10-OCT-08:00 |
General:Cooling:EnergyTransfer | 1336.17 | 0.00 | 01-JAN-00:10 | 154386.48 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 230.57 | 0.00 | 01-JAN-00:10 | 22006.14 | 10-OCT-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.18 | 0.00 | 01-JAN-00:10 | 9815.55 | 18-JUL-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 3.03 | 0.00 | 01-JAN-00:10 | 7247.06 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 3.03 | 0.00 | 01-JAN-00:10 | 7247.06 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.15 | 0.00 | 01-JAN-00:10 | 9815.55 | 18-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.15 | 0.00 | 01-JAN-00:10 | 9815.55 | 18-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.57 | 0.00 | 01-JAN-00:10 | 4827.40 | 10-OCT-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.01 | 0.00 | 01-JAN-00:10 | 1934.64 | 31-DEC-12:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.01 | 0.00 | 01-JAN-00:10 | 1934.64 | 31-DEC-12:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.56 | 0.00 | 01-JAN-00:10 | 4827.40 | 10-OCT-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.56 | 0.00 | 01-JAN-00:10 | 4827.40 | 10-OCT-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 30.14 | 0.00 | 01-JAN-00:10 | 4753.01 | 10-OCT-15:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.47 | 0.00 | 01-JAN-00:10 | 1392.57 | 22-JAN-13:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.47 | 0.00 | 01-JAN-00:10 | 1392.57 | 22-JAN-13:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.67 | 0.00 | 01-JAN-00:10 | 4753.01 | 10-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.67 | 0.00 | 01-JAN-00:10 | 4753.01 | 10-OCT-15:10 |
EnergyTransfer:Zone:CORE_MID | 189.77 | 0.00 | 01-JAN-00:10 | 18925.57 | 10-OCT-07:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2568.53 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2568.53 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 189.77 | 0.00 | 01-JAN-00:10 | 18925.57 | 10-OCT-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 189.77 | 0.00 | 01-JAN-00:10 | 18925.57 | 10-OCT-07:30 |
EnergyTransfer:Zone:CORE_TOP | 193.81 | 0.00 | 01-JAN-00:10 | 19778.86 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.16 | 0.00 | 01-JAN-00:10 | 10954.60 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.16 | 0.00 | 01-JAN-00:10 | 10954.60 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 193.65 | 0.00 | 01-JAN-00:10 | 19778.86 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 193.65 | 0.00 | 01-JAN-00:10 | 19778.86 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.43 | 0.00 | 01-JAN-00:10 | 7432.80 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.89 | 0.00 | 01-JAN-00:10 | 7246.91 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.89 | 0.00 | 01-JAN-00:10 | 7246.91 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 52.55 | 0.00 | 01-JAN-00:10 | 7432.80 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 52.55 | 0.00 | 01-JAN-00:10 | 7432.80 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.75 | 0.00 | 01-JAN-00:10 | 7611.49 | 12-JUN-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.39 | 0.00 | 01-JAN-00:10 | 4513.81 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.39 | 0.00 | 01-JAN-00:10 | 4513.81 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.36 | 0.00 | 01-JAN-00:10 | 7611.49 | 12-JUN-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.36 | 0.00 | 01-JAN-00:10 | 7611.49 | 12-JUN-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.98 | 0.00 | 01-JAN-00:10 | 11475.36 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.49 | 0.00 | 01-JAN-00:10 | 6291.94 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.49 | 0.00 | 01-JAN-00:10 | 6291.94 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.49 | 0.00 | 01-JAN-00:10 | 11475.36 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.49 | 0.00 | 01-JAN-00:10 | 11475.36 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.74 | 0.00 | 01-JAN-00:10 | 8590.73 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.49 | 0.00 | 01-JAN-00:10 | 4311.66 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.49 | 0.00 | 01-JAN-00:10 | 4311.66 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.26 | 0.00 | 01-JAN-00:10 | 8590.73 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.26 | 0.00 | 01-JAN-00:10 | 8590.73 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 49.34 | 0.00 | 01-JAN-00:10 | 6863.96 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.07 | 0.00 | 01-JAN-00:10 | 2554.42 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.07 | 0.00 | 01-JAN-00:10 | 2554.42 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 49.27 | 0.00 | 01-JAN-00:10 | 6863.96 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 49.27 | 0.00 | 01-JAN-00:10 | 6863.96 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 42.44 | 0.00 | 01-JAN-00:10 | 6783.59 | 11-SEP-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1452.58 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1452.58 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 42.42 | 0.00 | 01-JAN-00:10 | 6783.59 | 11-SEP-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 42.42 | 0.00 | 01-JAN-00:10 | 6783.59 | 11-SEP-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 74.27 | 0.00 | 01-JAN-00:10 | 11911.96 | 30-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.02 | 0.00 | 01-JAN-00:10 | 6600.40 | 20-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.02 | 0.00 | 01-JAN-00:10 | 6600.40 | 20-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 72.25 | 0.00 | 01-JAN-00:10 | 11911.96 | 30-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 72.25 | 0.00 | 01-JAN-00:10 | 11911.96 | 30-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 40.91 | 0.00 | 01-JAN-00:10 | 7162.69 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1377.63 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1377.63 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 40.89 | 0.00 | 01-JAN-00:10 | 7162.69 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 40.89 | 0.00 | 01-JAN-00:10 | 7162.69 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.17 | 0.00 | 01-JAN-00:10 | 6807.10 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.16 | 0.00 | 01-JAN-00:10 | 3539.15 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.16 | 0.00 | 01-JAN-00:10 | 3539.15 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.01 | 0.00 | 01-JAN-00:10 | 6807.10 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.01 | 0.00 | 01-JAN-00:10 | 6807.10 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.88 | 0.00 | 01-JAN-00:10 | 7395.13 | 12-JUN-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.07 | 0.00 | 01-JAN-00:10 | 2157.37 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.07 | 0.00 | 01-JAN-00:10 | 2157.37 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.81 | 0.00 | 01-JAN-00:10 | 7395.13 | 12-JUN-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.81 | 0.00 | 01-JAN-00:10 | 7395.13 | 12-JUN-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 68.79 | 0.00 | 01-JAN-00:10 | 10399.53 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.08 | 0.00 | 01-JAN-00:10 | 2787.11 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.08 | 0.00 | 01-JAN-00:10 | 2787.11 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 68.71 | 0.00 | 01-JAN-00:10 | 10399.53 | 06-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 68.71 | 0.00 | 01-JAN-00:10 | 10399.53 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.85 | 0.00 | 01-JAN-00:10 | 7973.54 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2011.20 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2011.20 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.77 | 0.00 | 01-JAN-00:10 | 7973.54 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.77 | 0.00 | 01-JAN-00:10 | 7973.54 | 30-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 38.26 | 0.00 | 01-JAN-00:10 | 4953.43 | 20-JAN-12:40 |
PlantLoopHeatingDemand:Plant | 38.26 | 0.00 | 01-JAN-00:10 | 4953.43 | 20-JAN-12:40 |
WaterSystems:PlantLoopHeatingDemand | 38.26 | 0.00 | 01-JAN-00:10 | 4953.43 | 20-JAN-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 38.26 | 0.00 | 01-JAN-00:10 | 4953.43 | 20-JAN-12:40 |
EnergyTransfer:HVAC | 2069.62 | 0.00 | 01-JAN-00:10 | 280255.37 | 06-OCT-14:10 |
HeatingCoils:EnergyTransfer | 14.88 | 0.00 | 01-JAN-00:10 | 98295.40 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2054.74 | 0.00 | 01-JAN-00:10 | 280255.37 | 06-OCT-14:10 |
EnergyTransfer:Plant | 38.26 | 0.00 | 01-JAN-00:10 | 4953.43 | 20-JAN-12:40 |
WaterSystems:EnergyTransfer | 38.26 | 0.00 | 01-JAN-00:10 | 4953.43 | 20-JAN-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 38.26 | 0.00 | 01-JAN-00:10 | 4953.43 | 20-JAN-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -230.576 | 0.000 | 0.000 | 32.779 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.482 |
CORE_MID | 0.000 | 0.000 | 0.002 | -189.766 | 0.000 | 0.000 | 33.236 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 1.307 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.161 | -193.653 | 0.000 | 0.000 | 33.598 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 4.673 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.887 | -52.545 | 0.000 | 0.000 | 7.161 | 4.811 | 24.333 | 23.939 | 0.000 | 0.463 | 7.294 | 0.000 | -14.430 | 0.000 | -1.912 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.393 | -44.355 | 0.000 | 0.000 | 4.455 | 3.030 | 15.404 | 34.102 | 0.000 | 0.287 | 0.001 | 0.000 | -9.258 | 0.000 | -1.353 | -2.705 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.485 | -70.490 | 0.000 | 0.000 | 7.015 | 4.750 | 24.332 | 58.946 | 0.000 | 0.438 | 0.000 | 0.000 | -14.254 | 0.000 | -2.152 | -9.070 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.486 | -43.256 | 0.000 | 0.000 | 4.498 | 3.030 | 15.403 | 33.534 | 0.000 | 0.291 | 0.000 | 0.000 | -9.801 | 0.000 | -1.368 | -2.818 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.073 | -49.270 | 0.000 | 0.000 | 7.112 | 4.800 | 24.333 | 24.241 | 0.000 | 0.267 | 4.782 | 0.000 | -15.236 | 0.000 | -1.102 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.019 | -42.422 | 0.000 | 0.000 | 4.417 | 3.025 | 15.404 | 34.280 | 0.000 | 0.158 | 0.003 | 0.000 | -10.075 | 0.000 | -0.801 | -4.005 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.023 | -72.247 | 0.000 | 0.000 | 7.027 | 4.744 | 24.332 | 59.395 | 0.000 | 10.819 | 0.000 | 0.000 | -15.455 | 0.000 | -13.502 | -7.137 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.019 | -40.888 | 0.000 | 0.000 | 4.446 | 3.024 | 15.403 | 33.743 | 0.000 | 0.159 | 0.000 | 0.000 | -10.673 | 0.000 | -0.810 | -4.423 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.157 | -51.013 | 0.000 | 0.000 | 7.105 | 4.811 | 24.333 | 23.984 | 0.000 | 0.400 | 7.243 | 0.000 | -15.307 | 0.000 | -1.712 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.071 | -40.811 | 0.000 | 0.000 | 3.262 | 3.030 | 15.404 | 33.994 | 0.000 | 0.240 | 0.001 | 0.000 | -9.795 | 0.000 | -1.212 | -4.183 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.075 | -68.711 | 0.000 | 0.000 | 6.970 | 4.750 | 24.332 | 59.007 | 0.000 | 0.375 | 0.001 | 0.000 | -15.016 | 0.000 | -1.907 | -9.875 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.082 | -41.769 | 0.000 | 0.000 | 4.464 | 3.030 | 15.403 | 33.589 | 0.000 | 0.246 | 0.001 | 0.000 | -10.367 | 0.000 | -1.218 | -3.460 |
TOPFLOOR_PLENUM | 3.029 | -48.149 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.483 | 47.617 | 0.000 | 0.000 | 0.000 | -2.979 | 0.000 |
MIDFLOOR_PLENUM | 1.009 | -26.563 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.570 | 28.036 | 0.000 | 0.000 | 0.000 | -3.052 | 0.000 |
FIRSTFLOOR_PLENUM | 0.466 | -29.669 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.449 | 31.242 | 0.000 | 0.000 | 0.000 | -2.487 | 0.000 |
Total Facility | 4.503 | -104.381 | 4.934 | -1231.771 | 0.000 | 0.000 | 167.545 | 166.220 | 647.750 | 452.754 | 0.000 | 15.644 | 132.202 | 0.000 | -149.667 | 0.000 | -37.567 | -68.160 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 31-JUL-04:03 | 0.00 | 0.00 | 0.00 | -33883.09 | 0.00 | 0.00 | 0.00 | 387.63 | 3464.19 | 0.00 | 0.00 | 0.00 | 30031.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | -30993.89 | 0.00 | 0.00 | 320.70 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 27259.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 31-JUL-04:03 | 0.00 | 0.00 | 0.00 | -31430.26 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 28600.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-14:02 | 0.00 | 0.00 | 0.00 | -11107.69 | 0.00 | 0.00 | 26.85 | 19.49 | 478.42 | 3825.02 | 0.00 | 165.09 | 6592.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:42 | 0.00 | 0.00 | 0.00 | -12163.50 | 0.00 | 0.00 | 14.97 | 12.34 | 302.86 | 6122.64 | 0.00 | 18.61 | 5692.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-13:51 | 0.00 | 0.00 | 0.00 | -15969.59 | 0.00 | 0.00 | 21.23 | 19.49 | 478.41 | 12014.39 | 0.00 | 0.00 | 3479.54 | 0.00 | -0.00 | 0.00 | -43.47 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:52 | 0.00 | 0.00 | 0.00 | -13046.39 | 0.00 | 0.00 | 12.53 | 12.34 | 302.86 | 6891.15 | 0.00 | 62.25 | 5765.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 | -7463.79 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 7211.45 | 0.00 | -343.80 | 0.00 | -0.38 | 0.00 |
PERIMETER_BOT_ZN_2 | 03-SEP-09:42 | 0.00 | 0.00 | 0.00 | -10777.26 | 0.00 | 0.00 | 15.70 | 12.34 | 302.86 | 7198.54 | 0.00 | 16.82 | 3231.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-JAN-13:51 | 0.00 | 0.00 | 0.00 | -13478.19 | 0.00 | 0.00 | 22.47 | 19.49 | 478.41 | 12105.39 | 0.00 | 0.00 | 873.39 | 0.00 | -0.00 | 0.00 | -20.96 | 0.00 |
PERIMETER_BOT_ZN_4 | 08-OCT-16:02 | 0.00 | 0.00 | 0.00 | -11038.95 | 0.00 | 0.00 | 15.54 | 12.34 | 302.86 | 5092.39 | 0.00 | 76.20 | 5539.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 08-OCT-14:42 | 0.00 | 0.00 | 0.00 | -9313.61 | 0.00 | 0.00 | 28.99 | 19.49 | 478.42 | 2492.75 | 0.00 | 236.24 | 6057.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 03-SEP-09:42 | 0.00 | 0.00 | 0.00 | -11930.56 | 0.00 | 0.00 | 14.77 | 12.34 | 302.86 | 7136.65 | 0.00 | 22.15 | 4441.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 17-DEC-13:12 | 0.00 | 0.00 | 0.00 | -13147.25 | 0.00 | 0.00 | 24.28 | 19.49 | 478.41 | 11685.63 | 0.00 | 0.00 | 1327.09 | 0.00 | -0.00 | 0.00 | -387.65 | 0.00 |
PERIMETER_MID_ZN_4 | 24-SEP-16:32 | 0.00 | 0.00 | 0.00 | -12137.80 | 0.00 | 0.00 | 14.92 | 12.34 | 302.86 | 5801.81 | 0.00 | 31.86 | 5974.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 18-JUL-14:50 | 0.00 | -9815.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.76 | 9743.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-OCT-14:20 | 0.00 | -4827.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.49 | 4716.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-OCT-15:10 | 0.00 | -4753.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.21 | 4654.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-AUG-04:02 | 0.00 | 7349.13 | 0.00 | -188574.91 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 0.00 | 0.00 | 14.69 | 168569.62 | 0.00 | -2686.55 | 0.00 | -28.04 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-07:02 | 0.00 | 0.00 | 13250.21 | 0.00 | 0.00 | 0.00 | 896.70 | 1162.90 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18335.73 |
CORE_TOP | 06-FEB-06:11 | 0.00 | 0.00 | 18877.11 | 0.00 | 0.00 | 0.00 | 484.35 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22775.01 |
PERIMETER_TOP_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 9249.91 | 0.00 | 0.00 | 0.00 | 111.13 | 81.72 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1994.08 | 0.00 | -51.54 | -8035.02 |
PERIMETER_TOP_ZN_2 | 06-FEB-06:11 | 0.00 | 0.00 | 5828.03 | 0.00 | 0.00 | 0.00 | 70.11 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1342.65 | 0.00 | -34.64 | -4976.39 |
PERIMETER_TOP_ZN_1 | 06-FEB-06:11 | 0.00 | 0.00 | 9114.45 | 0.00 | 0.00 | 0.00 | 108.62 | 81.72 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2068.77 | 0.00 | -54.33 | -7819.56 |
PERIMETER_TOP_ZN_4 | 06-FEB-06:11 | 0.00 | 0.00 | 5548.38 | 0.00 | 0.00 | 0.00 | 69.64 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1366.88 | 0.00 | -35.15 | -4671.53 |
PERIMETER_BOT_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 5310.96 | 0.00 | 0.00 | 0.00 | 101.32 | 81.72 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2372.48 | 0.00 | -32.45 | -3726.96 |
PERIMETER_BOT_ZN_2 | 07-FEB-07:03 | 0.00 | 0.00 | 3354.74 | 0.00 | 0.00 | 0.00 | 122.37 | 155.20 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1351.78 | 0.00 | -46.51 | -2637.83 |
PERIMETER_BOT_ZN_1 | 21-DEC-07:10 | 0.00 | 0.00 | 6825.56 | 0.00 | 0.00 | 0.00 | 193.30 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 13845.35 | 0.00 | -2934.86 | 0.00 | -18812.38 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-06:11 | 0.00 | 0.00 | 3592.74 | 0.00 | 0.00 | 0.00 | 62.49 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1647.65 | 0.00 | -22.53 | -2440.59 |
PERIMETER_MID_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 6892.02 | 0.00 | 0.00 | 0.00 | 103.97 | 81.72 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2290.50 | 0.00 | -48.90 | -5376.19 |
PERIMETER_MID_ZN_2 | 21-DEC-06:03 | 0.00 | 0.00 | 4287.86 | 0.00 | 0.00 | 0.00 | 63.74 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1892.83 | 0.00 | -69.29 | -2821.55 |
PERIMETER_MID_ZN_1 | 21-DEC-06:01 | 0.00 | 0.00 | 6317.72 | 0.00 | 0.00 | 0.00 | 98.42 | 44.64 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2858.12 | 0.00 | -103.97 | -4136.58 |
PERIMETER_MID_ZN_4 | 27-JAN-07:03 | 0.00 | 0.00 | 3947.67 | 0.00 | 0.00 | 0.00 | 122.37 | 155.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1426.17 | 0.00 | -34.25 | -3168.61 |
TOPFLOOR_PLENUM | 06-FEB-07:03 | 8958.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -84.49 | -8874.41 |
MIDFLOOR_PLENUM | 31-DEC-13:33 | 3597.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3607.51 |
FIRSTFLOOR_PLENUM | 31-DEC-12:20 | 2595.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2597.69 |
Total Facility | 06-FEB-07:01 | 487.11 | 7393.52 | 87042.22 | -7393.52 | 0.00 | 0.00 | 4520.29 | 5890.77 | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23365.78 | 0.00 | -21794.76 | -71125.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.7304 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2550 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.4785 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9005 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.9121 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5953 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.3652 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0753 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2392 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0746 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4560 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0744 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2896 | 2.2896 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9065 | 1.9065 | 0.6368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0598 | 2.0598 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6541 | 0.6541 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6622 | 0.6622 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7998 | 0.7998 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7363 | 0.7363 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5536 | 0.5536 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5877 | 0.5877 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6855 | 0.6855 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6140 | 0.6140 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5616 | 0.5616 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6376 | 0.6376 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7055 | 0.7055 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6673 | 0.6673 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.7304 | 4.2550 | 4.7304 | 1.0753 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.4785 | 3.9005 | 4.4785 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.9121 | 4.5953 | 4.9121 | 1.0744 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1448 | 1.1448 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9532 | 0.9532 | 0.6368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0299 | 1.0299 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3270 | 0.3270 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3311 | 0.3311 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3999 | 0.3999 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3681 | 0.3681 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2768 | 0.2768 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2938 | 0.2938 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3427 | 0.3427 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3070 | 0.3070 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2808 | 0.2808 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3188 | 0.3188 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3528 | 0.3528 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3336 | 0.3336 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.3652 | 1.0753 | 1.0753 | 1.0753 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2392 | 1.0746 | 1.0746 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4560 | 1.0744 | 1.0744 | 1.0744 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 71.00 |
Number of hours cooling loads not met | 339.17 |
Number of hours not met | 410.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 12.52 | 90588.55 | 2.94 | 23266.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 491.32 | 72924.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 166.22 | 16858.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.06 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 828.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 74.01 | 13942.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 116.99 | 9719.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1437.65 |
Natural Gas | 0.00 | 119.93 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1557.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 169.73 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.36 |
Space Heating | 2.51 |
Space Cooling | 98.62 |
Fans (All) | 14.85 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 288.56 |
Subtotal | 288.56 |
Natural Gas [MJ/m2] | |
Space Heating | 0.59 |
Service Water Heating | 23.48 |
Miscellaneous (All) | 24.07 |
Subtotal | 24.07 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.67 |
Space Heating | 0.99 |
Space Cooling | 31.54 |
Fans (All) | 4.75 |
Service Water Heating | 7.51 |
Receptacle Equipment | 41.59 |
Miscellaneous | 2.94 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1050. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8561.00 | 199.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8395.33 | 364.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8441.33 | 318.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8324.33 | 435.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8693.33 | 66.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8494.67 | 265.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8538.33 | 221.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8469.00 | 291.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8619.83 | 140.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8416.00 | 344.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8479.33 | 280.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8368.00 | 392.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8384.17 | 375.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
Min | 8324.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 435.67 | 0.00 | 0.00 | 0.00 |
Average | 8552.93 | 207.07 | 0.00 | 0.00 | 0.00 |
Sum | 153952.67 | 3727.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24903.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 5.50 | 0.00 | 0.00 | 0.00 |
Average | 34143.03 | 0.31 | 0.00 | 0.00 | 0.00 |
Sum | 614574.50 | 5.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8689.67 | 70.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7008.83 | 1751.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6902.83 | 1857.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6927.83 | 1832.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6853.50 | 1906.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7477.00 | 1283.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7216.83 | 1543.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6327.67 | 2432.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7150.83 | 1609.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7018.83 | 1741.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6886.67 | 1873.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6924.83 | 1835.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6829.33 | 1930.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7157.17 | 1602.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7545.50 | 1214.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7861.83 | 898.17 | 0.00 | 0.00 | 0.00 |
Min | 6327.67 | 8.67 | 0.00 | 0.00 | 0.00 |
Max | 8751.33 | 2432.33 | 0.00 | 0.00 | 0.00 |
Average | 7348.86 | 1411.14 | 0.00 | 0.00 | 0.00 |
Sum | 132279.50 | 25400.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128283.67 | 20.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128298.00 | 6.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24833.00 | 76.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14012.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24831.83 | 77.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14012.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24879.50 | 29.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 19476.33 | 5432.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24840.00 | 69.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24838.50 | 70.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14014.17 | 1.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128298.00 | 5432.67 | 0.00 | 0.00 | 0.00 |
Average | 33821.22 | 322.11 | 0.00 | 0.00 | 0.00 |
Sum | 608782.00 | 5798.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147630E+11 | 33250.13 | 02-JAN-06:13 | 16.00 | 15.39 | 0.196890E+10 | 2606.67 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.134537E+11 | 16919.57 | 02-FEB-08:05 | 18.67 | 17.79 | 0.178788E+10 | 2606.62 | 27-FEB-10:20 | 21.63 | 19.26 |
March | 0.166253E+11 | 16820.92 | 30-MAR-08:00 | 21.60 | 19.44 | 0.213773E+10 | 2606.66 | 10-MAR-10:30 | 21.60 | 19.44 |
April | 0.174657E+11 | 19586.46 | 24-APR-06:03 | 20.50 | 20.22 | 0.191414E+10 | 2606.68 | 10-APR-13:00 | 20.50 | 20.22 |
May | 0.222557E+11 | 33703.43 | 27-MAY-05:03 | 25.00 | 23.72 | 0.207511E+10 | 2606.60 | 31-MAY-13:20 | 23.73 | 21.76 |
June | 0.223853E+11 | 33696.01 | 24-JUN-05:03 | 25.50 | 22.83 | 0.206842E+10 | 2606.60 | 01-JUN-13:20 | 25.50 | 22.83 |
July | 0.223913E+11 | 33874.97 | 31-JUL-04:03 | 24.40 | 23.27 | 0.192169E+10 | 2606.60 | 03-JUL-13:20 | 24.40 | 23.27 |
August | 0.238403E+11 | 33301.54 | 12-AUG-05:03 | 23.90 | 22.38 | 0.215794E+10 | 2606.60 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.217863E+11 | 32897.20 | 18-SEP-04:03 | 25.00 | 23.33 | 0.191560E+10 | 2606.60 | 18-SEP-13:20 | 28.47 | 25.99 |
October | 0.218273E+11 | 32985.66 | 23-OCT-04:03 | 24.92 | 24.16 | 0.199228E+10 | 2606.72 | 17-OCT-13:09 | 24.92 | 24.16 |
November | 0.180498E+11 | 29995.66 | 06-NOV-07:03 | 19.08 | 17.86 | 0.196826E+10 | 2606.65 | 10-NOV-10:20 | 23.30 | 18.40 |
December | 0.157307E+11 | 17563.75 | 15-DEC-17:00 | 28.00 | 21.24 | 0.190749E+10 | 2606.67 | 08-DEC-10:00 | 28.00 | 21.24 |
Annual Sum or Average | 0.230574E+12 | 0.238154E+11 | ||||||||
Minimum of Months | 0.134537E+11 | 16820.92 | 16.00 | 15.39 | 0.178788E+10 | 2606.60 | 14.17 | 9.63 | ||
Maximum of Months | 0.238403E+11 | 33874.97 | 28.00 | 24.16 | 0.215794E+10 | 2606.72 | 28.47 | 25.99 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121274E+10 | 5389.95 | 19-JAN-14:50 | 25.00 | 21.54 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 21.54 |
February | 0.161496E+10 | 6362.30 | 27-FEB-15:00 | 26.10 | 20.43 | 0.00 | 0.00 | 01-FEB-00:10 | 26.10 | 20.43 |
March | 0.217097E+10 | 6166.12 | 29-MAR-14:50 | 26.83 | 21.36 | 0.00 | 0.00 | 01-MAR-00:10 | 26.83 | 21.36 |
April | 0.364896E+10 | 8722.22 | 28-APR-15:00 | 33.30 | 23.06 | 0.00 | 0.00 | 01-APR-00:10 | 33.30 | 23.06 |
May | 0.610252E+10 | 9368.04 | 10-MAY-14:50 | 32.80 | 23.14 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 23.14 |
June | 0.678724E+10 | 9426.51 | 28-JUN-14:30 | 33.60 | 26.19 | 0.00 | 0.00 | 01-JUN-00:10 | 33.60 | 26.19 |
July | 0.644118E+10 | 9815.55 | 18-JUL-14:50 | 35.00 | 25.65 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.65 |
August | 0.652739E+10 | 9550.70 | 03-AUG-15:20 | 35.17 | 24.83 | 0.00 | 0.00 | 01-AUG-00:10 | 35.17 | 24.83 |
September | 0.499041E+10 | 8858.73 | 01-SEP-14:05 | 32.20 | 23.03 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 23.03 |
October | 0.484850E+10 | 9047.99 | 05-OCT-15:00 | 34.00 | 24.05 | 0.00 | 0.00 | 01-OCT-00:10 | 34.00 | 24.05 |
November | 0.228640E+10 | 7332.42 | 02-NOV-14:20 | 29.40 | 24.36 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.36 |
December | 0.151853E+10 | 6446.28 | 15-DEC-15:05 | 28.83 | 21.51 | 0.00 | 0.00 | 01-DEC-00:10 | 28.83 | 21.51 |
Annual Sum or Average | 0.481498E+11 | 0.00 | ||||||||
Minimum of Months | 0.121274E+10 | 5389.95 | 25.00 | 20.43 | 0.00 | 0.00 | 25.00 | 20.43 | ||
Maximum of Months | 0.678724E+10 | 9815.55 | 35.17 | 26.19 | 0.00 | 0.00 | 35.17 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.579724E+09 | 3147.36 | 04-JAN-07:01 | 1.17 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | -1.3 |
February | 0.743349E+09 | 2656.14 | 13-FEB-07:01 | 4.08 | 0.66 | 0.00 | 0.00 | 01-FEB-00:10 | 4.08 | 0.66 |
March | 0.100076E+10 | 3199.12 | 09-MAR-07:01 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.173268E+10 | 3180.63 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.342361E+10 | 4432.01 | 30-MAY-06:03 | 25.18 | 23.66 | 0.00 | 0.00 | 01-MAY-00:10 | 25.18 | 23.66 |
June | 0.362139E+10 | 4365.24 | 05-JUN-06:03 | 24.08 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 24.08 | 22.57 |
July | 0.364803E+10 | 4431.68 | 24-JUL-06:03 | 26.28 | 25.37 | 0.00 | 0.00 | 01-JUL-00:10 | 26.28 | 25.37 |
August | 0.372898E+10 | 4447.98 | 28-AUG-06:03 | 24.17 | 23.32 | 0.00 | 0.00 | 01-AUG-00:10 | 24.17 | 23.32 |
September | 0.305033E+10 | 4621.80 | 11-SEP-06:03 | 25.08 | 23.81 | 0.00 | 0.00 | 01-SEP-00:10 | 25.08 | 23.81 |
October | 0.294302E+10 | 4827.40 | 10-OCT-14:20 | 30.67 | 22.57 | 0.00 | 0.00 | 01-OCT-00:10 | 30.67 | 22.57 |
November | 0.127717E+10 | 3345.78 | 06-NOV-16:10 | 28.02 | 20.18 | 0.00 | 0.00 | 01-NOV-00:10 | 28.02 | 20.18 |
December | 0.814632E+09 | 2577.22 | 15-DEC-16:00 | 28.00 | 21.24 | 0.00 | 0.00 | 01-DEC-00:10 | 28.00 | 21.24 |
Annual Sum or Average | 0.265637E+11 | 0.00 | ||||||||
Minimum of Months | 0.579724E+09 | 2577.22 | 1.17 | -2.3 | 0.00 | 0.00 | 1.17 | -2.3 | ||
Maximum of Months | 0.372898E+10 | 4827.40 | 32.20 | 25.55 | 0.00 | 0.00 | 32.20 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.857050E+09 | 3218.31 | 03-JAN-07:08 | 2.33 | 0.16 | 0.00 | 0.00 | 01-JAN-00:10 | 2.33 | 0.16 |
February | 0.956615E+09 | 2875.14 | 17-FEB-07:01 | 1.28 | -1.4 | 0.00 | 0.00 | 01-FEB-00:10 | 1.28 | -1.4 |
March | 0.125916E+10 | 2959.35 | 09-MAR-07:10 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.190110E+10 | 3218.82 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.346668E+10 | 4166.05 | 30-MAY-06:03 | 25.18 | 23.66 | 0.00 | 0.00 | 01-MAY-00:10 | 25.18 | 23.66 |
June | 0.368452E+10 | 4004.75 | 05-JUN-06:03 | 24.08 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 24.08 | 22.57 |
July | 0.375905E+10 | 4593.69 | 05-JUL-12:10 | 32.20 | 26.46 | 0.00 | 0.00 | 01-JUL-00:10 | 32.20 | 26.46 |
August | 0.406815E+10 | 4412.67 | 28-AUG-15:30 | 33.00 | 24.29 | 0.00 | 0.00 | 01-AUG-00:10 | 33.00 | 24.29 |
September | 0.342946E+10 | 4466.93 | 05-SEP-12:15 | 29.07 | 25.55 | 0.00 | 0.00 | 01-SEP-00:10 | 29.07 | 25.55 |
October | 0.336119E+10 | 4753.01 | 10-OCT-15:10 | 30.00 | 22.39 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 22.39 |
November | 0.176611E+10 | 3740.09 | 06-NOV-17:00 | 26.60 | 19.72 | 0.00 | 0.00 | 01-NOV-00:10 | 26.60 | 19.72 |
December | 0.116056E+10 | 3025.67 | 18-DEC-07:09 | 2.50 | 0.21 | 0.00 | 0.00 | 01-DEC-00:10 | 2.50 | 0.21 |
Annual Sum or Average | 0.296696E+11 | 0.00 | ||||||||
Minimum of Months | 0.857050E+09 | 2875.14 | 1.18 | -2.3 | 0.00 | 0.00 | 1.18 | -2.3 | ||
Maximum of Months | 0.406815E+10 | 4753.01 | 33.00 | 26.46 | 0.00 | 0.00 | 33.00 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118704E+11 | 26391.27 | 02-JAN-06:13 | 16.00 | 15.39 | 0.183520E+10 | 2606.61 | 02-JAN-10:20 | 21.33 | 18.13 |
February | 0.110531E+11 | 13414.85 | 27-FEB-17:00 | 24.40 | 20.28 | 0.169742E+10 | 2606.64 | 27-FEB-10:20 | 24.40 | 20.28 |
March | 0.135343E+11 | 13104.39 | 27-MAR-16:00 | 28.30 | 21.14 | 0.206084E+10 | 2606.63 | 06-MAR-10:20 | 28.30 | 21.14 |
April | 0.143841E+11 | 14549.30 | 28-APR-16:00 | 32.20 | 25.55 | 0.189914E+10 | 2606.64 | 10-APR-13:00 | 32.20 | 25.55 |
May | 0.189062E+11 | 28050.05 | 08-MAY-04:03 | 24.32 | 22.06 | 0.207220E+10 | 2606.60 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.190588E+11 | 28428.69 | 19-JUN-04:03 | 25.50 | 24.30 | 0.206602E+10 | 2606.60 | 12-JUN-09:20 | 25.50 | 24.30 |
July | 0.192535E+11 | 28434.30 | 31-JUL-04:03 | 24.40 | 23.27 | 0.191928E+10 | 2606.60 | 24-JUL-09:20 | 24.40 | 23.27 |
August | 0.198055E+11 | 28116.55 | 12-AUG-05:03 | 23.90 | 22.38 | 0.215554E+10 | 2606.60 | 07-AUG-09:20 | 23.90 | 22.38 |
September | 0.180325E+11 | 30986.65 | 05-SEP-05:15 | 22.80 | 22.80 | 0.191183E+10 | 2606.60 | 25-SEP-09:20 | 25.17 | 23.40 |
October | 0.177044E+11 | 28597.55 | 10-OCT-06:05 | 21.92 | 19.97 | 0.198549E+10 | 2606.70 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.138453E+11 | 16621.67 | 06-NOV-06:13 | 18.80 | 17.70 | 0.194108E+10 | 2606.63 | 13-NOV-14:20 | 23.30 | 17.15 |
December | 0.123174E+11 | 13858.01 | 15-DEC-17:00 | 28.00 | 21.24 | 0.181442E+10 | 2606.63 | 18-DEC-14:20 | 16.33 | 10.42 |
Annual Sum or Average | 0.189765E+12 | 0.233585E+11 | ||||||||
Minimum of Months | 0.110531E+11 | 13104.39 | 16.00 | 15.39 | 0.169742E+10 | 2606.60 | 16.33 | 10.42 | ||
Maximum of Months | 0.198055E+11 | 30986.65 | 32.20 | 25.55 | 0.215554E+10 | 2606.70 | 32.20 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107616E+11 | 14989.88 | 02-JAN-14:20 | 26.33 | 18.48 | 0.174553E+10 | 2606.59 | 18-JAN-14:20 | 24.67 | 20.38 |
February | 0.104471E+11 | 14607.12 | 27-FEB-16:20 | 25.13 | 20.45 | 0.164119E+10 | 2606.65 | 27-FEB-10:20 | 25.13 | 20.45 |
March | 0.130122E+11 | 14603.56 | 29-MAR-16:00 | 26.60 | 21.18 | 0.200326E+10 | 2606.65 | 06-MAR-10:20 | 26.60 | 21.18 |
April | 0.146734E+11 | 17283.73 | 28-APR-15:50 | 32.38 | 25.18 | 0.188084E+10 | 2606.65 | 12-APR-13:00 | 32.38 | 25.18 |
May | 0.203912E+11 | 31219.86 | 08-MAY-04:03 | 24.32 | 22.06 | 0.207287E+10 | 2606.60 | 26-MAY-13:20 | 27.23 | 24.58 |
June | 0.208502E+11 | 31327.77 | 12-JUN-04:03 | 23.90 | 21.28 | 0.206710E+10 | 2606.61 | 07-JUN-09:20 | 23.90 | 21.28 |
July | 0.209485E+11 | 31424.02 | 31-JUL-04:03 | 24.40 | 23.27 | 0.192102E+10 | 2606.60 | 03-JUL-13:20 | 24.40 | 23.27 |
August | 0.212742E+11 | 30544.84 | 07-AUG-04:02 | 24.83 | 24.08 | 0.215612E+10 | 2606.60 | 22-AUG-13:20 | 31.47 | 25.51 |
September | 0.187540E+11 | 31278.84 | 18-SEP-04:03 | 25.00 | 23.33 | 0.191097E+10 | 2606.60 | 28-SEP-09:20 | 24.97 | 22.81 |
October | 0.179988E+11 | 30999.02 | 23-OCT-04:03 | 24.92 | 24.16 | 0.197717E+10 | 2606.70 | 17-OCT-13:09 | 24.92 | 24.16 |
November | 0.131914E+11 | 16447.79 | 06-NOV-15:00 | 28.30 | 20.44 | 0.189149E+10 | 2606.63 | 13-NOV-14:20 | 23.30 | 17.15 |
December | 0.113500E+11 | 14951.05 | 15-DEC-16:30 | 28.00 | 21.24 | 0.172870E+10 | 2606.62 | 11-DEC-10:20 | 28.00 | 21.24 |
Annual Sum or Average | 0.193653E+12 | 0.229963E+11 | ||||||||
Minimum of Months | 0.104471E+11 | 14603.56 | 23.90 | 18.48 | 0.164119E+10 | 2606.59 | 23.30 | 17.15 | ||
Maximum of Months | 0.212742E+11 | 31424.02 | 32.38 | 25.18 | 0.215612E+10 | 2606.70 | 32.38 | 25.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175647E+10 | 3935.28 | 02-JAN-13:40 | 26.00 | 18.55 | 0.349384E+09 | 549.49 | 17-JAN-14:20 | 25.00 | 20.04 |
February | 0.201843E+10 | 3892.01 | 28-FEB-15:00 | 25.00 | 20.38 | 0.333511E+09 | 549.49 | 28-FEB-10:20 | 25.00 | 20.38 |
March | 0.274207E+10 | 4929.54 | 30-MAR-13:30 | 28.55 | 22.55 | 0.407551E+09 | 549.49 | 30-MAR-09:20 | 28.55 | 22.55 |
April | 0.380089E+10 | 5959.48 | 28-APR-15:10 | 33.12 | 23.52 | 0.391309E+09 | 549.50 | 12-APR-13:00 | 33.12 | 23.52 |
May | 0.640350E+10 | 10882.56 | 07-MAY-15:02 | 32.80 | 23.03 | 0.437798E+09 | 549.49 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.695333E+10 | 10932.32 | 11-JUN-17:32 | 32.57 | 21.55 | 0.436495E+09 | 549.49 | 01-JUN-13:20 | 32.57 | 21.55 |
July | 0.683061E+10 | 11107.86 | 23-JUL-14:02 | 33.03 | 26.02 | 0.406176E+09 | 549.49 | 14-JUL-13:20 | 33.03 | 26.02 |
August | 0.676337E+10 | 10931.22 | 20-AUG-16:03 | 31.67 | 25.78 | 0.455222E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.542790E+10 | 10971.25 | 10-SEP-15:22 | 34.95 | 27.14 | 0.403577E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.491223E+10 | 9002.19 | 09-OCT-13:52 | 31.00 | 23.79 | 0.414348E+09 | 549.50 | 17-OCT-13:20 | 22.33 | 15.56 |
November | 0.285717E+10 | 4890.04 | 02-NOV-14:00 | 29.40 | 24.47 | 0.387644E+09 | 549.49 | 06-NOV-10:20 | 24.37 | 20.12 |
December | 0.208120E+10 | 4289.34 | 15-DEC-15:00 | 29.00 | 21.56 | 0.346146E+09 | 549.49 | 01-DEC-14:20 | 29.00 | 21.56 |
Annual Sum or Average | 0.525472E+11 | 0.476916E+10 | ||||||||
Minimum of Months | 0.175647E+10 | 3892.01 | 25.00 | 18.55 | 0.333511E+09 | 549.49 | 22.33 | 15.56 | ||
Maximum of Months | 0.695333E+10 | 11107.86 | 34.95 | 27.14 | 0.455222E+09 | 549.50 | 33.12 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145524E+10 | 4295.43 | 19-JAN-10:20 | 23.57 | 21.08 | 0.239106E+09 | 347.87 | 17-JAN-14:20 | 23.57 | 21.08 |
February | 0.173681E+10 | 4682.03 | 27-FEB-10:30 | 21.90 | 19.28 | 0.225101E+09 | 347.88 | 27-FEB-10:20 | 21.90 | 19.28 |
March | 0.251936E+10 | 6892.31 | 26-MAR-10:03 | 25.78 | 20.21 | 0.272453E+09 | 347.88 | 24-MAR-13:00 | 25.78 | 20.21 |
April | 0.359538E+10 | 11581.97 | 23-APR-08:32 | 23.67 | 20.14 | 0.252651E+09 | 347.88 | 10-APR-13:00 | 23.67 | 20.14 |
May | 0.549372E+10 | 12160.52 | 14-MAY-09:42 | 28.80 | 23.66 | 0.277503E+09 | 347.87 | 11-MAY-09:20 | 28.80 | 23.66 |
June | 0.575560E+10 | 12125.79 | 11-JUN-10:12 | 29.60 | 21.19 | 0.276564E+09 | 347.87 | 16-JUN-09:20 | 29.80 | 24.50 |
July | 0.564667E+10 | 12144.19 | 16-JUL-10:42 | 30.68 | 26.02 | 0.257425E+09 | 347.87 | 14-JUL-13:20 | 30.68 | 26.02 |
August | 0.553637E+10 | 11547.78 | 27-AUG-09:53 | 30.00 | 24.85 | 0.288432E+09 | 347.87 | 25-AUG-13:20 | 30.00 | 24.85 |
September | 0.443456E+10 | 11664.82 | 10-SEP-09:22 | 33.80 | 27.03 | 0.256011E+09 | 347.87 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.417834E+10 | 12042.31 | 09-OCT-10:32 | 29.67 | 22.84 | 0.264276E+09 | 347.88 | 02-OCT-09:39 | 29.67 | 22.84 |
November | 0.238570E+10 | 6022.16 | 11-NOV-09:53 | 24.40 | 21.68 | 0.256581E+09 | 347.87 | 10-NOV-10:20 | 24.40 | 21.68 |
December | 0.161908E+10 | 3615.14 | 16-DEC-10:10 | 24.33 | 21.30 | 0.231874E+09 | 347.87 | 18-DEC-10:20 | 9.67 | 4.87 |
Annual Sum or Average | 0.443568E+11 | 0.309798E+10 | ||||||||
Minimum of Months | 0.145524E+10 | 3615.14 | 21.90 | 19.28 | 0.225101E+09 | 347.87 | 9.67 | 4.87 | ||
Maximum of Months | 0.575560E+10 | 12160.52 | 33.80 | 27.03 | 0.288432E+09 | 347.88 | 30.68 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415110E+10 | 15970.35 | 01-JAN-13:51 | 26.00 | 17.88 | 0.393841E+09 | 552.49 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.420117E+10 | 14341.25 | 26-FEB-13:13 | 26.27 | 18.89 | 0.360635E+09 | 549.50 | 09-FEB-14:00 | 26.27 | 18.89 |
March | 0.425364E+10 | 11998.84 | 26-MAR-16:03 | 26.00 | 20.08 | 0.424113E+09 | 549.51 | 24-MAR-13:00 | 26.00 | 20.08 |
April | 0.480730E+10 | 10251.57 | 23-APR-13:53 | 27.70 | 20.99 | 0.393427E+09 | 549.51 | 10-APR-13:00 | 27.70 | 20.99 |
May | 0.655892E+10 | 13265.34 | 07-MAY-15:02 | 32.80 | 23.03 | 0.437726E+09 | 549.49 | 31-MAY-13:20 | 23.73 | 21.76 |
June | 0.672774E+10 | 12546.32 | 04-JUN-16:02 | 29.50 | 24.64 | 0.436323E+09 | 549.49 | 01-JUN-13:20 | 29.50 | 24.64 |
July | 0.679206E+10 | 13431.47 | 23-JUL-14:02 | 33.03 | 26.02 | 0.406078E+09 | 549.49 | 14-JUL-13:20 | 33.03 | 26.02 |
August | 0.750670E+10 | 13240.10 | 20-AUG-16:03 | 31.67 | 25.78 | 0.455305E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.681116E+10 | 14152.93 | 17-SEP-13:02 | 31.18 | 26.19 | 0.404078E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.785631E+10 | 14708.39 | 09-OCT-10:32 | 29.67 | 22.84 | 0.417736E+09 | 561.19 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.596580E+10 | 14245.28 | 05-NOV-12:43 | 26.83 | 20.53 | 0.407029E+09 | 574.18 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.486059E+10 | 15539.55 | 10-DEC-13:52 | 27.00 | 20.22 | 0.379525E+09 | 557.09 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.704925E+11 | 0.491582E+10 | ||||||||
Minimum of Months | 0.415110E+10 | 10251.57 | 26.00 | 17.88 | 0.360635E+09 | 549.49 | 23.30 | 18.89 | ||
Maximum of Months | 0.785631E+10 | 15970.35 | 33.03 | 26.19 | 0.455305E+09 | 574.18 | 33.03 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157312E+10 | 9218.01 | 01-JAN-14:31 | 25.33 | 18.34 | 0.231785E+09 | 347.84 | 02-JAN-14:20 | 26.33 | 18.48 |
February | 0.187587E+10 | 12585.76 | 26-FEB-16:33 | 24.77 | 19.88 | 0.217798E+09 | 347.85 | 27-FEB-10:20 | 21.63 | 19.26 |
March | 0.243978E+10 | 11186.63 | 26-MAR-16:03 | 26.00 | 20.08 | 0.262102E+09 | 347.85 | 06-MAR-10:20 | 26.00 | 20.08 |
April | 0.354906E+10 | 12269.49 | 23-APR-16:32 | 27.37 | 21.80 | 0.248972E+09 | 347.85 | 12-APR-13:00 | 27.37 | 21.80 |
May | 0.500736E+10 | 13046.49 | 29-MAY-16:52 | 30.60 | 23.80 | 0.277301E+09 | 347.84 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.537480E+10 | 12980.53 | 11-JUN-16:52 | 33.30 | 21.96 | 0.276461E+09 | 347.84 | 16-JUN-09:20 | 29.80 | 24.50 |
July | 0.513757E+10 | 12315.38 | 16-JUL-16:02 | 31.32 | 25.35 | 0.257277E+09 | 347.84 | 11-JUL-13:20 | 31.32 | 25.35 |
August | 0.535610E+10 | 11831.30 | 20-AUG-17:23 | 30.50 | 24.34 | 0.288380E+09 | 347.84 | 08-AUG-13:20 | 30.50 | 24.34 |
September | 0.437042E+10 | 13009.32 | 10-SEP-16:02 | 34.10 | 26.94 | 0.255808E+09 | 347.84 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.419926E+10 | 12613.75 | 08-OCT-15:32 | 31.00 | 25.40 | 0.263184E+09 | 347.85 | 02-OCT-09:20 | 31.00 | 25.40 |
November | 0.250141E+10 | 10749.43 | 05-NOV-16:03 | 27.02 | 19.59 | 0.248729E+09 | 347.85 | 06-NOV-10:20 | 24.37 | 20.12 |
December | 0.187250E+10 | 12571.62 | 10-DEC-15:52 | 27.00 | 20.22 | 0.226549E+09 | 347.84 | 11-DEC-10:20 | 23.67 | 21.83 |
Annual Sum or Average | 0.432573E+11 | 0.305435E+10 | ||||||||
Minimum of Months | 0.157312E+10 | 9218.01 | 24.77 | 18.34 | 0.217798E+09 | 347.84 | 21.63 | 18.48 | ||
Maximum of Months | 0.537480E+10 | 13046.49 | 34.10 | 26.94 | 0.288380E+09 | 347.85 | 31.32 | 25.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220025E+10 | 3532.84 | 02-JAN-13:30 | 26.00 | 18.64 | 0.361054E+09 | 549.49 | 02-JAN-10:20 | 26.00 | 18.64 |
February | 0.204366E+10 | 2901.97 | 28-FEB-15:00 | 25.00 | 20.38 | 0.336413E+09 | 549.49 | 28-FEB-10:20 | 25.00 | 20.38 |
March | 0.254393E+10 | 3670.22 | 30-MAR-13:10 | 29.12 | 22.70 | 0.408724E+09 | 549.49 | 30-MAR-09:20 | 29.12 | 22.70 |
April | 0.297676E+10 | 4274.40 | 28-APR-15:10 | 33.12 | 23.52 | 0.390790E+09 | 549.49 | 21-APR-09:20 | 33.12 | 23.52 |
May | 0.512876E+10 | 5900.31 | 31-MAY-05:02 | 23.80 | 21.58 | 0.437070E+09 | 549.49 | 30-MAY-09:20 | 23.80 | 21.58 |
June | 0.575232E+10 | 6489.81 | 26-JUN-04:02 | 25.00 | 23.68 | 0.436009E+09 | 549.49 | 01-JUN-13:20 | 25.00 | 23.68 |
July | 0.603823E+10 | 7466.33 | 05-JUL-04:02 | 25.68 | 24.39 | 0.405701E+09 | 549.49 | 11-JUL-13:20 | 25.60 | 23.64 |
August | 0.655353E+10 | 7431.04 | 14-AUG-04:02 | 26.10 | 24.05 | 0.455324E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.546554E+10 | 7233.95 | 11-SEP-04:02 | 24.83 | 23.63 | 0.404137E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.500102E+10 | 7229.34 | 08-OCT-14:42 | 31.33 | 25.84 | 0.418397E+09 | 549.51 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.305788E+10 | 4438.24 | 03-NOV-14:00 | 29.40 | 23.47 | 0.401729E+09 | 549.50 | 28-NOV-10:20 | 25.13 | 20.31 |
December | 0.250910E+10 | 3834.21 | 15-DEC-14:10 | 29.00 | 22.01 | 0.362886E+09 | 549.49 | 01-DEC-14:20 | 29.00 | 22.01 |
Annual Sum or Average | 0.492710E+11 | 0.481823E+10 | ||||||||
Minimum of Months | 0.204366E+10 | 2901.97 | 23.80 | 18.64 | 0.336413E+09 | 549.49 | 22.17 | 15.50 | ||
Maximum of Months | 0.655353E+10 | 7466.33 | 33.12 | 25.84 | 0.455324E+09 | 549.51 | 33.12 | 24.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174367E+10 | 3784.05 | 19-JAN-10:20 | 23.57 | 21.08 | 0.250413E+09 | 347.87 | 04-JAN-10:20 | 23.57 | 21.08 |
February | 0.171872E+10 | 3856.38 | 27-FEB-10:30 | 21.90 | 19.28 | 0.229812E+09 | 347.87 | 27-FEB-10:20 | 21.90 | 19.28 |
March | 0.230152E+10 | 4084.64 | 07-MAR-10:40 | 25.90 | 22.51 | 0.276438E+09 | 347.87 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.297974E+10 | 4907.33 | 23-APR-09:23 | 25.25 | 20.84 | 0.253444E+09 | 347.88 | 10-APR-13:00 | 25.25 | 20.84 |
May | 0.462569E+10 | 10095.65 | 29-MAY-09:32 | 28.53 | 23.16 | 0.277375E+09 | 347.87 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.494954E+10 | 6500.27 | 12-JUN-09:40 | 29.83 | 22.55 | 0.276470E+09 | 347.87 | 01-JUN-13:20 | 29.83 | 22.55 |
July | 0.511931E+10 | 10398.36 | 16-JUL-10:42 | 30.68 | 26.02 | 0.257362E+09 | 347.87 | 24-JUL-09:20 | 30.37 | 25.95 |
August | 0.545351E+10 | 9552.94 | 27-AUG-09:53 | 30.00 | 24.85 | 0.288615E+09 | 347.87 | 25-AUG-13:20 | 30.00 | 24.85 |
September | 0.453828E+10 | 10773.98 | 03-SEP-09:42 | 29.98 | 24.61 | 0.256372E+09 | 347.87 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.436423E+10 | 10525.62 | 09-OCT-10:22 | 29.50 | 22.78 | 0.265947E+09 | 347.88 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.269870E+10 | 5042.43 | 11-NOV-09:33 | 24.40 | 21.68 | 0.261245E+09 | 347.88 | 10-NOV-10:20 | 24.40 | 21.68 |
December | 0.192974E+10 | 3380.89 | 16-DEC-10:10 | 24.33 | 21.30 | 0.242767E+09 | 347.88 | 08-DEC-10:00 | 24.33 | 21.30 |
Annual Sum or Average | 0.424227E+11 | 0.313626E+10 | ||||||||
Minimum of Months | 0.171872E+10 | 3380.89 | 21.90 | 19.28 | 0.229812E+09 | 347.87 | 16.97 | 14.65 | ||
Maximum of Months | 0.545351E+10 | 10773.98 | 30.68 | 26.02 | 0.288615E+09 | 347.88 | 30.37 | 25.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349385E+10 | 13478.45 | 01-JAN-13:51 | 26.00 | 17.88 | 0.385231E+09 | 553.46 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.340308E+10 | 12035.31 | 26-FEB-13:13 | 26.27 | 18.89 | 0.353225E+09 | 567.69 | 02-FEB-13:09 | 26.27 | 18.89 |
March | 0.332882E+10 | 9592.90 | 06-MAR-13:00 | 27.20 | 21.71 | 0.410917E+09 | 549.50 | 24-MAR-13:00 | 25.50 | 16.44 |
April | 0.411997E+10 | 10552.09 | 28-APR-16:10 | 32.02 | 25.39 | 0.388175E+09 | 595.28 | 28-APR-12:09 | 32.02 | 25.39 |
May | 0.686025E+10 | 10786.52 | 19-MAY-12:00 | 32.20 | 23.63 | 0.439492E+09 | 613.25 | 19-MAY-12:09 | 32.30 | 23.64 |
June | 0.737810E+10 | 10938.62 | 28-JUN-12:00 | 32.80 | 25.51 | 0.438748E+09 | 621.50 | 28-JUN-12:09 | 32.80 | 25.64 |
July | 0.759385E+10 | 11490.27 | 21-JUL-16:10 | 35.45 | 25.77 | 0.409196E+09 | 652.66 | 20-JUL-12:09 | 35.45 | 25.77 |
August | 0.900016E+10 | 11986.76 | 30-AUG-16:20 | 35.83 | 23.47 | 0.459771E+09 | 645.83 | 10-AUG-12:09 | 35.83 | 23.47 |
September | 0.778049E+10 | 11905.67 | 24-SEP-12:32 | 30.90 | 25.13 | 0.406468E+09 | 632.96 | 01-SEP-12:09 | 30.90 | 25.13 |
October | 0.871750E+10 | 12652.19 | 08-OCT-14:42 | 31.33 | 25.84 | 0.425245E+09 | 655.12 | 06-OCT-12:09 | 31.33 | 25.84 |
November | 0.601495E+10 | 12192.38 | 11-NOV-15:32 | 26.27 | 22.90 | 0.410803E+09 | 616.28 | 02-NOV-12:09 | 26.27 | 22.90 |
December | 0.455770E+10 | 12550.41 | 17-DEC-13:42 | 19.00 | 12.50 | 0.376147E+09 | 588.35 | 15-DEC-13:09 | 19.00 | 12.50 |
Annual Sum or Average | 0.722487E+11 | 0.490342E+10 | ||||||||
Minimum of Months | 0.332882E+10 | 9592.90 | 19.00 | 12.50 | 0.353225E+09 | 549.50 | 19.00 | 12.50 | ||
Maximum of Months | 0.900016E+10 | 13478.45 | 35.83 | 25.84 | 0.459771E+09 | 655.12 | 35.83 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184452E+10 | 7249.44 | 01-JAN-17:12 | 22.67 | 19.00 | 0.242496E+09 | 347.85 | 02-JAN-10:20 | 21.33 | 18.13 |
February | 0.181896E+10 | 8558.91 | 26-FEB-16:33 | 24.77 | 19.88 | 0.223887E+09 | 347.85 | 27-FEB-10:20 | 21.63 | 19.26 |
March | 0.214295E+10 | 4879.39 | 06-MAR-16:30 | 25.55 | 21.32 | 0.268539E+09 | 347.85 | 06-MAR-10:20 | 25.55 | 21.32 |
April | 0.287344E+10 | 10714.00 | 23-APR-17:42 | 25.78 | 21.36 | 0.251545E+09 | 347.85 | 18-APR-09:20 | 25.78 | 21.36 |
May | 0.415232E+10 | 10683.37 | 29-MAY-16:52 | 30.60 | 23.80 | 0.277107E+09 | 347.85 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.456440E+10 | 10661.60 | 25-JUN-16:11 | 32.60 | 24.55 | 0.276385E+09 | 347.85 | 16-JUN-09:20 | 32.60 | 24.55 |
July | 0.460593E+10 | 8884.31 | 02-JUL-15:02 | 29.32 | 24.72 | 0.257206E+09 | 347.85 | 10-JUL-09:20 | 30.37 | 25.84 |
August | 0.525829E+10 | 8738.07 | 20-AUG-17:12 | 30.33 | 24.28 | 0.288583E+09 | 347.85 | 07-AUG-09:20 | 30.33 | 24.28 |
September | 0.445202E+10 | 11007.35 | 24-SEP-16:32 | 29.77 | 25.83 | 0.256291E+09 | 347.84 | 01-SEP-09:20 | 29.77 | 25.83 |
October | 0.434556E+10 | 11037.22 | 08-OCT-16:02 | 30.67 | 25.13 | 0.265874E+09 | 347.85 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.268695E+10 | 8855.58 | 05-NOV-16:03 | 27.02 | 19.59 | 0.258768E+09 | 347.85 | 10-NOV-10:20 | 23.30 | 18.40 |
December | 0.214389E+10 | 5245.57 | 15-DEC-16:30 | 28.00 | 21.24 | 0.239674E+09 | 347.84 | 18-DEC-14:20 | 16.33 | 10.42 |
Annual Sum or Average | 0.408892E+11 | 0.310635E+10 | ||||||||
Minimum of Months | 0.181896E+10 | 4879.39 | 22.67 | 19.00 | 0.223887E+09 | 347.84 | 16.33 | 10.42 | ||
Maximum of Months | 0.525829E+10 | 11037.22 | 32.60 | 25.83 | 0.288583E+09 | 347.85 | 32.60 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210956E+10 | 4020.49 | 02-JAN-13:30 | 26.00 | 18.64 | 0.359222E+09 | 549.49 | 17-JAN-14:20 | 25.00 | 20.04 |
February | 0.219468E+10 | 3616.03 | 28-FEB-15:00 | 25.00 | 20.38 | 0.341373E+09 | 549.50 | 27-FEB-10:20 | 25.00 | 20.38 |
March | 0.283968E+10 | 4575.67 | 30-MAR-13:10 | 29.12 | 22.70 | 0.417212E+09 | 549.49 | 20-MAR-13:20 | 29.12 | 22.70 |
April | 0.364782E+10 | 5218.98 | 26-APR-14:40 | 27.90 | 22.48 | 0.396117E+09 | 549.49 | 12-APR-13:20 | 27.90 | 22.48 |
May | 0.594387E+10 | 7554.56 | 31-MAY-05:02 | 23.80 | 21.58 | 0.437754E+09 | 549.49 | 30-MAY-09:20 | 23.80 | 21.58 |
June | 0.639706E+10 | 7610.47 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436437E+09 | 549.49 | 12-JUN-13:20 | 31.87 | 20.58 |
July | 0.629023E+10 | 9253.65 | 23-JUL-14:02 | 33.03 | 26.02 | 0.405993E+09 | 549.49 | 10-JUL-09:20 | 33.03 | 26.02 |
August | 0.630082E+10 | 7739.94 | 05-AUG-05:03 | 25.63 | 23.92 | 0.455224E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.516684E+10 | 9206.37 | 10-SEP-15:51 | 34.30 | 26.98 | 0.403875E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.476844E+10 | 9313.20 | 08-OCT-14:42 | 31.33 | 25.84 | 0.416926E+09 | 549.50 | 17-OCT-13:20 | 22.33 | 15.56 |
November | 0.298568E+10 | 4469.27 | 03-NOV-14:00 | 29.40 | 23.47 | 0.397401E+09 | 549.49 | 13-NOV-14:20 | 23.30 | 17.15 |
December | 0.236954E+10 | 3921.12 | 15-DEC-15:00 | 29.00 | 21.56 | 0.357752E+09 | 549.49 | 01-DEC-14:20 | 29.00 | 21.56 |
Annual Sum or Average | 0.510142E+11 | 0.482529E+10 | ||||||||
Minimum of Months | 0.210956E+10 | 3616.03 | 23.80 | 18.64 | 0.341373E+09 | 549.49 | 22.33 | 15.56 | ||
Maximum of Months | 0.639706E+10 | 9313.20 | 34.30 | 26.98 | 0.455224E+09 | 549.50 | 33.03 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143877E+10 | 6251.57 | 03-JAN-13:01 | 12.33 | 5.46 | 0.181949E+09 | 356.45 | 11-JAN-13:09 | 21.00 | 14.05 |
February | 0.166954E+10 | 5708.88 | 27-FEB-11:05 | 22.80 | 19.34 | 0.169288E+09 | 356.46 | 09-FEB-11:09 | 22.80 | 19.34 |
March | 0.240133E+10 | 7049.54 | 26-MAR-09:53 | 25.50 | 20.23 | 0.204072E+09 | 356.45 | 24-MAR-14:09 | 25.50 | 20.23 |
April | 0.330788E+10 | 11589.02 | 23-APR-09:42 | 25.82 | 20.99 | 0.188048E+09 | 356.46 | 10-APR-14:09 | 25.82 | 20.99 |
May | 0.493386E+10 | 11597.14 | 14-MAY-09:42 | 28.80 | 23.66 | 0.206024E+09 | 356.45 | 03-MAY-14:09 | 28.80 | 23.66 |
June | 0.513366E+10 | 11540.75 | 11-JUN-10:12 | 29.60 | 21.19 | 0.205065E+09 | 356.45 | 30-JUN-10:09 | 28.58 | 24.03 |
July | 0.503785E+10 | 11505.06 | 16-JUL-10:42 | 30.68 | 26.02 | 0.191487E+09 | 356.45 | 06-JUL-10:09 | 30.68 | 26.02 |
August | 0.498237E+10 | 11013.07 | 27-AUG-09:53 | 30.00 | 24.85 | 0.213824E+09 | 356.44 | 30-AUG-14:09 | 32.28 | 22.78 |
September | 0.405877E+10 | 11927.90 | 03-SEP-09:42 | 29.98 | 24.61 | 0.190274E+09 | 356.45 | 01-SEP-10:09 | 29.98 | 24.61 |
October | 0.388499E+10 | 11506.62 | 09-OCT-10:32 | 29.67 | 22.84 | 0.196833E+09 | 356.46 | 17-OCT-12:09 | 21.17 | 14.63 |
November | 0.234773E+10 | 6877.31 | 11-NOV-09:33 | 24.40 | 21.68 | 0.191791E+09 | 356.46 | 10-NOV-11:09 | 24.40 | 21.68 |
December | 0.161498E+10 | 6032.18 | 18-DEC-13:01 | 14.33 | 9.20 | 0.176547E+09 | 356.46 | 08-DEC-11:09 | 14.33 | 9.20 |
Annual Sum or Average | 0.408117E+11 | 0.231520E+10 | ||||||||
Minimum of Months | 0.143877E+10 | 5708.88 | 12.33 | 5.46 | 0.169288E+09 | 356.44 | 14.33 | 9.20 | ||
Maximum of Months | 0.513366E+10 | 11927.90 | 30.68 | 26.02 | 0.213824E+09 | 356.46 | 32.28 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453209E+10 | 12874.94 | 01-JAN-14:02 | 25.83 | 18.00 | 0.402163E+09 | 567.53 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.437075E+10 | 12924.04 | 26-FEB-13:42 | 26.52 | 19.51 | 0.367172E+09 | 561.87 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.429946E+10 | 10538.62 | 05-MAR-13:53 | 27.70 | 18.31 | 0.433069E+09 | 549.50 | 24-MAR-13:00 | 25.50 | 16.44 |
April | 0.460523E+10 | 8787.11 | 23-APR-14:23 | 28.25 | 21.28 | 0.397832E+09 | 549.51 | 10-APR-13:00 | 28.25 | 21.28 |
May | 0.607987E+10 | 9228.76 | 30-MAY-04:02 | 25.60 | 23.97 | 0.437765E+09 | 549.49 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.617898E+10 | 9403.37 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436307E+09 | 549.49 | 12-JUN-13:20 | 31.87 | 20.58 |
July | 0.625000E+10 | 11280.40 | 23-JUL-14:02 | 33.03 | 26.02 | 0.405931E+09 | 549.49 | 10-JUL-09:20 | 33.03 | 26.02 |
August | 0.699246E+10 | 9539.38 | 14-AUG-04:02 | 26.10 | 24.05 | 0.455363E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.648462E+10 | 12372.74 | 17-SEP-13:02 | 31.18 | 26.19 | 0.404439E+09 | 549.49 | 20-SEP-13:20 | 26.60 | 22.72 |
October | 0.761044E+10 | 13049.01 | 08-OCT-14:43 | 31.33 | 25.84 | 0.419958E+09 | 574.81 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.612740E+10 | 12641.32 | 05-NOV-12:43 | 26.83 | 20.53 | 0.412173E+09 | 590.46 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.518158E+10 | 13146.32 | 17-DEC-13:12 | 19.00 | 12.71 | 0.388045E+09 | 571.19 | 15-DEC-14:39 | 19.00 | 12.71 |
Annual Sum or Average | 0.687129E+11 | 0.496022E+10 | ||||||||
Minimum of Months | 0.429946E+10 | 8787.11 | 19.00 | 12.71 | 0.367172E+09 | 549.49 | 19.00 | 12.71 | ||
Maximum of Months | 0.761044E+10 | 13146.32 | 33.03 | 26.19 | 0.455363E+09 | 590.46 | 33.03 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178220E+10 | 9335.97 | 01-JAN-16:42 | 24.17 | 19.23 | 0.237626E+09 | 347.85 | 02-JAN-10:20 | 21.33 | 18.13 |
February | 0.196371E+10 | 11316.04 | 26-FEB-16:23 | 24.95 | 19.89 | 0.222727E+09 | 347.85 | 27-FEB-10:20 | 21.63 | 19.26 |
March | 0.245888E+10 | 9474.44 | 26-MAR-16:03 | 26.00 | 20.08 | 0.268419E+09 | 347.85 | 30-MAR-09:20 | 23.27 | 19.90 |
April | 0.339544E+10 | 11859.45 | 23-APR-17:42 | 25.78 | 21.36 | 0.252012E+09 | 347.85 | 18-APR-09:20 | 25.78 | 21.36 |
May | 0.465637E+10 | 11938.79 | 14-MAY-17:42 | 28.58 | 22.92 | 0.277317E+09 | 347.85 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.495444E+10 | 11793.70 | 11-JUN-16:52 | 33.30 | 21.96 | 0.276476E+09 | 347.85 | 16-JUN-09:20 | 29.80 | 24.50 |
July | 0.472962E+10 | 10502.83 | 16-JUL-16:02 | 31.32 | 25.35 | 0.257228E+09 | 347.85 | 10-JUL-09:20 | 31.32 | 25.35 |
August | 0.500141E+10 | 10077.75 | 20-AUG-17:12 | 30.33 | 24.28 | 0.288399E+09 | 347.85 | 07-AUG-09:20 | 30.33 | 24.28 |
September | 0.415376E+10 | 12135.58 | 24-SEP-16:32 | 29.77 | 25.83 | 0.256011E+09 | 347.84 | 07-SEP-13:20 | 29.77 | 25.83 |
October | 0.405945E+10 | 11991.95 | 08-OCT-16:02 | 30.67 | 25.13 | 0.264693E+09 | 347.85 | 17-OCT-13:20 | 22.33 | 15.56 |
November | 0.257497E+10 | 9716.90 | 05-NOV-16:03 | 27.02 | 19.59 | 0.254390E+09 | 347.85 | 28-NOV-10:20 | 25.13 | 20.31 |
December | 0.203974E+10 | 5677.58 | 15-DEC-15:40 | 28.33 | 21.35 | 0.233537E+09 | 347.84 | 18-DEC-14:20 | 16.33 | 10.42 |
Annual Sum or Average | 0.417700E+11 | 0.308883E+10 | ||||||||
Minimum of Months | 0.178220E+10 | 5677.58 | 24.17 | 19.23 | 0.222727E+09 | 347.84 | 16.33 | 10.42 | ||
Maximum of Months | 0.500141E+10 | 12135.58 | 33.30 | 25.83 | 0.288399E+09 | 347.85 | 31.32 | 25.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.824540E+09 | 8727.63 | 10-JAN-07:03 | 3.17 |
February | 0.472452E+09 | 8958.79 | 06-FEB-07:03 | 3.90 |
March | 0.527014E+09 | 6098.13 | 13-MAR-06:02 | 5.92 |
April | 0.154416E+09 | 2853.04 | 11-APR-05:03 | 10.63 |
May | 16421294.61 | 4719.11 | 30-MAY-04:02 | 25.60 |
June | 15961350.67 | 3977.59 | 26-JUN-04:02 | 25.00 |
July | 14138385.46 | 4213.35 | 10-JUL-04:02 | 25.40 |
August | 13459753.72 | 3914.76 | 31-AUG-05:03 | 24.13 |
September | 13669036.44 | 4683.88 | 11-SEP-04:02 | 24.83 |
October | 86660294.64 | 2951.91 | 23-OCT-04:03 | 24.92 |
November | 0.251832E+09 | 3103.92 | 15-NOV-06:02 | 7.70 |
December | 0.638371E+09 | 8671.16 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.302893E+10 | |||
Minimum of Months | 13459753.72 | 2853.04 | 0.50 | |
Maximum of Months | 0.824540E+09 | 8958.79 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329463E+09 | 3068.86 | 16-JAN-14:53 | 27.00 |
February | 0.204194E+09 | 3279.86 | 26-FEB-16:23 | 24.95 |
March | 0.132722E+09 | 1691.20 | 05-MAR-13:53 | 27.70 |
April | 10716912.93 | 1596.09 | 02-APR-15:10 | 18.72 |
May | 10655195.80 | 2002.95 | 22-MAY-04:03 | 26.10 |
June | 7862434.68 | 1752.45 | 23-JUN-05:03 | 25.60 |
July | 10194994.00 | 2159.75 | 13-JUL-05:03 | 26.93 |
August | 7790629.14 | 1822.56 | 21-AUG-04:02 | 26.08 |
September | 13232754.65 | 2077.03 | 03-SEP-15:41 | 32.28 |
October | 17779498.15 | 2251.47 | 29-OCT-12:13 | 22.33 |
November | 52463466.57 | 2809.40 | 26-NOV-12:13 | 19.37 |
December | 0.211544E+09 | 3597.15 | 31-DEC-13:33 | 22.33 |
Annual Sum or Average | 0.100862E+10 | |||
Minimum of Months | 7790629.14 | 1596.09 | 18.72 | |
Maximum of Months | 0.329463E+09 | 3597.15 | 32.28 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147376E+09 | 2382.65 | 16-JAN-14:43 | 26.83 |
February | 84486510.96 | 2050.66 | 26-FEB-16:33 | 24.77 |
March | 58829275.82 | 1598.85 | 05-MAR-12:07 | 26.78 |
April | 4910535.74 | 1287.10 | 02-APR-16:13 | 18.30 |
May | 7732501.57 | 1793.62 | 31-MAY-05:02 | 23.80 |
June | 7433278.70 | 1655.22 | 05-JUN-04:02 | 25.22 |
July | 9988986.65 | 2104.73 | 03-JUL-04:02 | 26.60 |
August | 10686678.75 | 2432.00 | 14-AUG-04:02 | 26.10 |
September | 14977700.94 | 2306.99 | 18-SEP-04:03 | 25.00 |
October | 17007286.91 | 2546.13 | 23-OCT-04:03 | 24.92 |
November | 20704664.62 | 2182.17 | 26-NOV-13:23 | 20.80 |
December | 81474520.99 | 2594.99 | 31-DEC-12:20 | 23.00 |
Annual Sum or Average | 0.465608E+09 | |||
Minimum of Months | 4910535.74 | 1287.10 | 18.30 | |
Maximum of Months | 0.147376E+09 | 2594.99 | 26.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 1584414.69 | 13250.38 | 06-FEB-07:02 | 3.90 |
March | 810969.18 | 12164.54 | 13-MAR-06:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 2395383.88 | |||
Minimum of Months | 0.00 | 0.00 | 3.90 | |
Maximum of Months | 1584414.69 | 13250.38 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57031407.93 | 17629.02 | 28-JAN-07:03 | 8.50 |
February | 58652417.64 | 18877.32 | 06-FEB-06:11 | 3.07 |
March | 16610950.16 | 17517.27 | 13-MAR-06:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 29005684.90 | 18144.55 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.161300E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 58652417.64 | 18877.32 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357317E+09 | 8891.66 | 10-JAN-06:11 | 3.00 |
February | 0.172549E+09 | 9249.96 | 06-FEB-06:11 | 3.07 |
March | 0.130625E+09 | 8478.94 | 13-MAR-05:12 | 6.57 |
April | 626183.89 | 3962.00 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 335912.00 | 1119.71 | 28-OCT-06:05 | 10.00 |
November | 12469907.39 | 7753.93 | 15-NOV-07:02 | 7.80 |
December | 0.212635E+09 | 8635.75 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.886559E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.357317E+09 | 9249.96 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146931E+09 | 5477.20 | 10-JAN-06:11 | 3.00 |
February | 63987608.73 | 5828.10 | 06-FEB-06:11 | 3.07 |
March | 69891075.41 | 5104.39 | 21-MAR-06:03 | 10.00 |
April | 253372.30 | 2111.44 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 220021.63 | 733.41 | 28-OCT-06:05 | 10.00 |
November | 3721928.79 | 4982.39 | 24-NOV-07:03 | 13.08 |
December | 0.108034E+09 | 5340.63 | 26-DEC-06:12 | 5.90 |
Annual Sum or Average | 0.393040E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.00 | |
Maximum of Months | 0.146931E+09 | 5828.10 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175149E+09 | 8756.05 | 10-JAN-06:11 | 3.00 |
February | 90224929.90 | 9114.52 | 06-FEB-06:11 | 3.07 |
March | 0.100509E+09 | 8215.87 | 13-MAR-05:12 | 6.57 |
April | 307858.51 | 2565.49 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 40549.15 | 135.16 | 28-OCT-06:05 | 10.00 |
November | 3948623.64 | 7471.10 | 15-NOV-07:02 | 7.80 |
December | 0.115067E+09 | 8709.39 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.485247E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.175149E+09 | 9114.52 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193950E+09 | 5424.99 | 25-JAN-06:12 | 9.00 |
February | 93790164.78 | 5548.46 | 06-FEB-06:11 | 3.07 |
March | 75122425.94 | 5207.41 | 13-MAR-05:13 | 6.57 |
April | 108012.09 | 900.10 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 105669.97 | 352.23 | 28-OCT-06:05 | 10.00 |
November | 6440820.12 | 4795.04 | 13-NOV-07:02 | 9.27 |
December | 0.116052E+09 | 5374.27 | 22-DEC-06:12 | 10.00 |
Annual Sum or Average | 0.485569E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.07 | |
Maximum of Months | 0.193950E+09 | 5548.46 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25157218.58 | 5229.97 | 14-JAN-07:03 | 7.02 |
February | 22525415.64 | 5310.96 | 06-FEB-06:11 | 3.07 |
March | 16774328.32 | 5298.46 | 13-MAR-05:12 | 6.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 8732831.00 | 5122.57 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 73189793.53 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 25157218.58 | 5310.96 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5233083.99 | 3313.45 | 09-JAN-07:02 | 5.00 |
February | 5211787.03 | 3354.76 | 07-FEB-07:03 | 7.88 |
March | 4790154.58 | 3134.49 | 13-MAR-06:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 3903569.43 | 2891.63 | 20-DEC-07:02 | 1.83 |
Annual Sum or Average | 19138595.05 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 5233083.99 | 3354.76 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526945E+09 | 6599.88 | 05-JAN-07:10 | 0.83 |
February | 0.321115E+09 | 6640.46 | 17-FEB-07:10 | 1.28 |
March | 0.481817E+09 | 6543.92 | 09-MAR-07:10 | 1.18 |
April | 96914807.81 | 5155.04 | 17-APR-06:50 | 14.12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 10319148.73 | 4132.74 | 27-OCT-06:07 | 14.83 |
November | 0.129414E+09 | 5122.26 | 24-NOV-07:20 | 13.47 |
December | 0.456621E+09 | 6825.62 | 21-DEC-07:10 | 0.50 |
Annual Sum or Average | 0.202315E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 0.526945E+09 | 6825.62 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4898845.80 | 3357.76 | 23-JAN-07:01 | 6.17 |
February | 5845136.79 | 3592.74 | 06-FEB-06:11 | 3.07 |
March | 5227178.56 | 3375.34 | 14-MAR-06:02 | 7.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 2703435.98 | 3056.36 | 20-DEC-07:02 | 1.83 |
Annual Sum or Average | 18674597.13 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 5845136.79 | 3592.74 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62261005.80 | 6695.48 | 10-JAN-06:11 | 3.00 |
February | 36116292.99 | 6892.03 | 06-FEB-06:11 | 3.07 |
March | 21995575.45 | 6423.49 | 13-MAR-05:12 | 6.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 359514.80 | 2995.96 | 16-NOV-07:02 | 9.77 |
December | 36563259.48 | 6600.44 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.157296E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 62261005.80 | 6892.03 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25660244.49 | 3985.44 | 27-JAN-07:03 | 5.33 |
February | 14259587.81 | 3919.37 | 07-FEB-07:03 | 7.88 |
March | 10915876.36 | 3590.03 | 13-MAR-06:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 20570263.72 | 4287.89 | 21-DEC-06:03 | 0.83 |
Annual Sum or Average | 71405972.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 25660244.49 | 4287.89 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27348785.39 | 6160.01 | 25-JAN-07:02 | 9.00 |
February | 16068919.92 | 6039.55 | 06-FEB-06:11 | 3.07 |
March | 13199122.80 | 5914.75 | 10-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 18425729.76 | 6317.73 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 75042557.88 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 27348785.39 | 6317.73 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33340447.26 | 3947.78 | 27-JAN-07:03 | 5.33 |
February | 18544064.99 | 3904.95 | 14-FEB-07:03 | 9.50 |
March | 11338950.09 | 3853.24 | 13-MAR-06:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 116204.93 | 968.37 | 16-NOV-07:02 | 9.77 |
December | 18439300.97 | 3897.71 | 04-DEC-07:01 | 5.17 |
Annual Sum or Average | 81778968.23 | |||
Minimum of Months | 0.00 | 0.00 | 5.17 | |
Maximum of Months | 33340447.26 | 3947.78 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430254E+09 | 605.66 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.375839E+09 | 626.73 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.431480E+09 | 577.00 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.376766E+09 | 593.30 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.393416E+09 | 409.91 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.386275E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.366254E+09 | 398.00 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.413860E+09 | 411.77 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.381336E+09 | 575.35 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.406470E+09 | 657.07 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.423270E+09 | 630.52 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.425656E+09 | 651.68 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.481088E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.366254E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.431480E+09 | 657.07 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.267506E+09 | 359.09 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.235001E+09 | 381.06 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.270705E+09 | 336.66 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.238009E+09 | 359.54 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.250530E+09 | 252.95 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.246869E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.233155E+09 | 236.85 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.262292E+09 | 250.56 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240870E+09 | 334.54 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.255393E+09 | 405.53 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.264165E+09 | 403.66 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.265534E+09 | 406.01 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303003E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.233155E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.270705E+09 | 406.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411033E+09 | 586.79 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.365525E+09 | 614.92 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.427103E+09 | 570.54 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.377845E+09 | 595.80 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.397260E+09 | 412.79 | 23-MAY-07:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.391355E+09 | 386.39 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.369558E+09 | 406.48 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.415686E+09 | 482.31 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.380251E+09 | 573.41 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.401499E+09 | 652.14 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.406673E+09 | 611.65 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.406378E+09 | 644.74 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.475017E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.365525E+09 | 386.39 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.427103E+09 | 652.14 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.265192E+09 | 388.84 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.234770E+09 | 399.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272976E+09 | 379.47 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.239621E+09 | 385.02 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.251269E+09 | 320.41 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.246887E+09 | 255.98 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.233783E+09 | 299.58 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.263646E+09 | 347.98 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242830E+09 | 379.86 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256537E+09 | 419.47 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.260948E+09 | 407.91 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.261269E+09 | 412.78 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.302973E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.233783E+09 | 255.98 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.272976E+09 | 419.47 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.428597E+09 | 600.66 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.374646E+09 | 622.57 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.430406E+09 | 570.73 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.376272E+09 | 587.78 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.393011E+09 | 407.82 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.385935E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.365809E+09 | 395.30 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.413353E+09 | 409.76 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.380757E+09 | 569.04 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.405581E+09 | 654.04 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.421473E+09 | 626.33 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.423869E+09 | 648.50 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.479971E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.365809E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.430406E+09 | 654.04 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.266906E+09 | 355.01 | 31-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.234552E+09 | 378.25 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.270284E+09 | 332.07 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.237765E+09 | 355.86 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.250211E+09 | 251.92 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.246571E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.232899E+09 | 222.09 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.262018E+09 | 248.86 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240520E+09 | 329.72 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.255027E+09 | 403.53 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.263480E+09 | 401.74 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.264643E+09 | 404.09 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.302488E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.232899E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.270284E+09 | 404.09 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.410757E+09 | 580.88 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.365451E+09 | 610.19 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.426393E+09 | 563.95 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.377272E+09 | 590.41 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.396595E+09 | 410.87 | 23-MAY-07:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.390767E+09 | 383.37 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.369035E+09 | 404.28 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.415121E+09 | 472.34 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.379786E+09 | 567.02 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.400870E+09 | 648.87 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.406222E+09 | 606.64 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.405821E+09 | 641.22 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.474409E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.365451E+09 | 383.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.426393E+09 | 648.87 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.264559E+09 | 386.48 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.234256E+09 | 397.93 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272304E+09 | 376.82 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.239240E+09 | 382.55 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.250865E+09 | 316.14 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.246439E+09 | 254.83 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.233403E+09 | 260.83 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.263231E+09 | 344.13 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242371E+09 | 377.23 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256073E+09 | 418.05 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.260382E+09 | 406.10 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.260629E+09 | 411.16 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.302375E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.233403E+09 | 254.83 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.272304E+09 | 418.05 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430253E+09 | 605.64 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.375826E+09 | 626.72 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.431479E+09 | 576.99 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.376766E+09 | 593.29 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.393416E+09 | 409.90 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.386274E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.366254E+09 | 398.00 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.413859E+09 | 411.77 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.381335E+09 | 575.33 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.406469E+09 | 657.06 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.423269E+09 | 630.51 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.425654E+09 | 651.67 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.481085E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.366254E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.431479E+09 | 657.06 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.267505E+09 | 359.09 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.235000E+09 | 381.06 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.270705E+09 | 336.65 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.238009E+09 | 359.54 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.250530E+09 | 252.94 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.246869E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.233155E+09 | 236.84 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.262291E+09 | 250.55 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240869E+09 | 334.53 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.255392E+09 | 405.53 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.264165E+09 | 403.65 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.265533E+09 | 406.00 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.303002E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.233155E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.270705E+09 | 406.00 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411033E+09 | 586.78 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.365524E+09 | 614.91 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.427103E+09 | 570.53 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.377845E+09 | 595.79 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.397259E+09 | 412.79 | 23-MAY-07:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.391354E+09 | 386.38 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.369558E+09 | 406.48 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.415685E+09 | 482.29 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.380251E+09 | 573.40 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.401498E+09 | 652.13 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.406672E+09 | 611.64 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.406378E+09 | 644.73 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.475016E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.365524E+09 | 386.38 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.427103E+09 | 652.13 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.265192E+09 | 388.83 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.234769E+09 | 399.94 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.272975E+09 | 379.46 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.239621E+09 | 385.01 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.251269E+09 | 320.40 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.246887E+09 | 255.98 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.233783E+09 | 299.56 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.263646E+09 | 347.97 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242830E+09 | 379.85 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.256536E+09 | 419.47 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.260947E+09 | 407.90 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.261268E+09 | 412.77 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.302972E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.233783E+09 | 255.98 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.272975E+09 | 419.47 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.430254E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2623894.92 | 0.378140E+09 |
February | 0.901968E+09 | 0.375839E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3336071.23 | 0.290014E+09 |
March | 0.107774E+10 | 0.431480E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9468864.39 | 0.315301E+09 |
April | 0.956342E+09 | 0.376766E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15324719.87 | 0.146166E+09 |
May | 0.103597E+10 | 0.393416E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64971555.47 | 26397694.70 |
June | 0.103308E+10 | 0.386275E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58894651.30 | 19865654.92 |
July | 0.959235E+09 | 0.366254E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80616907.52 | 9066574.80 |
August | 0.107774E+10 | 0.413860E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80320383.81 | 25573643.20 |
September | 0.956342E+09 | 0.381336E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73107727.48 | 39508317.26 |
October | 0.994195E+09 | 0.406470E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60361545.38 | 0.125537E+09 |
November | 0.984487E+09 | 0.423270E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8422370.95 | 0.197849E+09 |
December | 0.959235E+09 | 0.425656E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5684256.32 | 0.338767E+09 |
Annual Sum or Average | 0.119305E+11 | 0.481088E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463133E+09 | 0.191219E+10 |
Minimum of Months | 0.901968E+09 | 0.366254E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2623894.92 | 9066574.80 |
Maximum of Months | 0.107774E+10 | 0.431480E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80616907.52 | 0.378140E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.267506E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942081.70 | 0.266738E+09 |
February | 0.571020E+09 | 0.235001E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1523889.09 | 0.205372E+09 |
March | 0.682301E+09 | 0.270705E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4340657.25 | 0.222686E+09 |
April | 0.605444E+09 | 0.238009E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9412930.52 | 0.105073E+09 |
May | 0.655854E+09 | 0.250530E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40937936.72 | 18996973.25 |
June | 0.654023E+09 | 0.246869E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38256000.79 | 13863315.09 |
July | 0.607275E+09 | 0.233155E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51403274.85 | 6733182.94 |
August | 0.682301E+09 | 0.262292E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51763734.14 | 17807562.50 |
September | 0.605444E+09 | 0.240870E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45636671.75 | 27769997.33 |
October | 0.629407E+09 | 0.255393E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36229226.57 | 89647818.91 |
November | 0.623262E+09 | 0.264165E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3934992.82 | 0.142255E+09 |
December | 0.607275E+09 | 0.265534E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2576188.85 | 0.236048E+09 |
Annual Sum or Average | 0.755301E+10 | 0.303003E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286958E+09 | 0.135299E+10 |
Minimum of Months | 0.571020E+09 | 0.233155E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942081.70 | 6733182.94 |
Maximum of Months | 0.682301E+09 | 0.270705E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51763734.14 | 0.266738E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.411033E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 799067.77 | 0.437645E+09 |
February | 0.901968E+09 | 0.365525E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1874767.18 | 0.333006E+09 |
March | 0.107774E+10 | 0.427103E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6017466.79 | 0.337092E+09 |
April | 0.956342E+09 | 0.377845E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14179098.03 | 0.155330E+09 |
May | 0.103597E+10 | 0.397260E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65218229.16 | 26295549.51 |
June | 0.103308E+10 | 0.391355E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59920200.15 | 19157856.36 |
July | 0.959235E+09 | 0.369558E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81487022.78 | 8971334.67 |
August | 0.107774E+10 | 0.415686E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79396482.48 | 26121674.70 |
September | 0.956342E+09 | 0.380251E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69116788.60 | 42691863.84 |
October | 0.994195E+09 | 0.401499E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51658938.76 | 0.146410E+09 |
November | 0.984487E+09 | 0.406673E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5137078.17 | 0.230379E+09 |
December | 0.959235E+09 | 0.406378E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3305939.86 | 0.389232E+09 |
Annual Sum or Average | 0.119305E+11 | 0.475017E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438111E+09 | 0.215233E+10 |
Minimum of Months | 0.901968E+09 | 0.365525E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 799067.77 | 8971334.67 |
Maximum of Months | 0.107774E+10 | 0.427103E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81487022.78 | 0.437645E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.265192E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1058069.48 | 0.268413E+09 |
February | 0.570983E+09 | 0.234770E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1671077.93 | 0.206088E+09 |
March | 0.682256E+09 | 0.272976E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5421271.20 | 0.220891E+09 |
April | 0.605404E+09 | 0.239621E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9000026.31 | 0.107779E+09 |
May | 0.655811E+09 | 0.251269E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41945598.81 | 19744914.40 |
June | 0.653980E+09 | 0.246887E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37866919.88 | 15006227.64 |
July | 0.607235E+09 | 0.233783E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51438053.50 | 7404570.80 |
August | 0.682256E+09 | 0.263646E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51926691.81 | 19689745.00 |
September | 0.605404E+09 | 0.242830E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45744940.95 | 29701938.75 |
October | 0.629366E+09 | 0.256537E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37024050.70 | 93318191.39 |
November | 0.623221E+09 | 0.260948E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4578578.72 | 0.140313E+09 |
December | 0.607235E+09 | 0.261269E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3022894.23 | 0.239226E+09 |
Annual Sum or Average | 0.755252E+10 | 0.302973E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290698E+09 | 0.136758E+10 |
Minimum of Months | 0.570983E+09 | 0.233783E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1058069.48 | 7404570.80 |
Maximum of Months | 0.682256E+09 | 0.272976E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51926691.81 | 0.268413E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.428597E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1487113.35 | 0.223551E+09 |
February | 0.901968E+09 | 0.374646E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2050754.41 | 0.169709E+09 |
March | 0.107774E+10 | 0.430406E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6188704.13 | 0.174419E+09 |
April | 0.956342E+09 | 0.376272E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9477720.58 | 76283375.28 |
May | 0.103597E+10 | 0.393011E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38375545.57 | 9602954.55 |
June | 0.103308E+10 | 0.385935E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34281565.73 | 8776164.35 |
July | 0.959235E+09 | 0.365809E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47603320.63 | 3588067.55 |
August | 0.107774E+10 | 0.413353E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44742952.80 | 14364871.35 |
September | 0.956342E+09 | 0.380757E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41577080.40 | 23094561.26 |
October | 0.994195E+09 | 0.405581E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34223608.77 | 74337131.57 |
November | 0.984487E+09 | 0.421473E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4407133.85 | 0.120250E+09 |
December | 0.959235E+09 | 0.423869E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2999360.80 | 0.203599E+09 |
Annual Sum or Average | 0.119305E+11 | 0.479971E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267415E+09 | 0.110158E+10 |
Minimum of Months | 0.901968E+09 | 0.365809E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1487113.35 | 3588067.55 |
Maximum of Months | 0.107774E+10 | 0.430406E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47603320.63 | 0.223551E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.266906E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503797.77 | 0.161436E+09 |
February | 0.571020E+09 | 0.234552E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 937539.22 | 0.122514E+09 |
March | 0.682301E+09 | 0.270284E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2631816.24 | 0.126484E+09 |
April | 0.605444E+09 | 0.237765E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5401168.26 | 56837740.28 |
May | 0.655854E+09 | 0.250211E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22616672.16 | 8332802.26 |
June | 0.654023E+09 | 0.246571E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21319262.21 | 6855994.30 |
July | 0.607275E+09 | 0.232899E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28516578.14 | 3387072.35 |
August | 0.682301E+09 | 0.262018E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27986604.80 | 10992481.99 |
September | 0.605444E+09 | 0.240520E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24739713.96 | 17548510.73 |
October | 0.629407E+09 | 0.255027E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19807954.13 | 54707163.78 |
November | 0.623262E+09 | 0.263480E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2171729.47 | 87316762.97 |
December | 0.607275E+09 | 0.264643E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1465778.04 | 0.144178E+09 |
Annual Sum or Average | 0.755301E+10 | 0.302488E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158099E+09 | 0.800590E+09 |
Minimum of Months | 0.571020E+09 | 0.232899E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503797.77 | 3387072.35 |
Maximum of Months | 0.682301E+09 | 0.270284E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28516578.14 | 0.161436E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.410757E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35184483.46 | 0.339803E+10 |
February | 0.901968E+09 | 0.365451E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59928353.78 | 0.213746E+10 |
March | 0.107774E+10 | 0.426393E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160554E+09 | 0.223213E+10 |
April | 0.956342E+09 | 0.377272E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534073E+09 | 0.728304E+09 |
May | 0.103597E+10 | 0.396595E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174074E+10 | 25490303.21 |
June | 0.103308E+10 | 0.390767E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206448E+10 | 24265901.36 |
July | 0.959235E+09 | 0.369035E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181898E+10 | 12431498.10 |
August | 0.107774E+10 | 0.415121E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195826E+10 | 40068777.95 |
September | 0.956342E+09 | 0.379786E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101645E+10 | 0.105287E+09 |
October | 0.994195E+09 | 0.400870E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102460E+10 | 0.522057E+09 |
November | 0.984487E+09 | 0.406222E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276809E+09 | 0.153722E+10 |
December | 0.959235E+09 | 0.405821E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128523E+09 | 0.273879E+10 |
Annual Sum or Average | 0.119305E+11 | 0.474409E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108186E+11 | 0.135015E+11 |
Minimum of Months | 0.901968E+09 | 0.365451E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35184483.46 | 12431498.10 |
Maximum of Months | 0.107774E+10 | 0.426393E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206448E+10 | 0.339803E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.264559E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 510857.20 | 0.162018E+09 |
February | 0.570983E+09 | 0.234256E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 919069.88 | 0.122618E+09 |
March | 0.682256E+09 | 0.272304E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2936591.14 | 0.125979E+09 |
April | 0.605404E+09 | 0.239240E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5011634.51 | 58682663.01 |
May | 0.655811E+09 | 0.250865E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23538065.71 | 8335076.44 |
June | 0.653980E+09 | 0.246439E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21017317.15 | 7591482.21 |
July | 0.607235E+09 | 0.233403E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28542469.01 | 3552638.60 |
August | 0.682256E+09 | 0.263231E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28117907.77 | 11942139.98 |
September | 0.605404E+09 | 0.242371E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24659761.48 | 18578755.71 |
October | 0.629366E+09 | 0.256073E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20064284.96 | 57061854.49 |
November | 0.623221E+09 | 0.260382E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2288453.00 | 86902293.47 |
December | 0.607235E+09 | 0.260629E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1531601.56 | 0.146497E+09 |
Annual Sum or Average | 0.755252E+10 | 0.302375E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159138E+09 | 0.809759E+09 |
Minimum of Months | 0.570983E+09 | 0.233403E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 510857.20 | 3552638.60 |
Maximum of Months | 0.682256E+09 | 0.272304E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28542469.01 | 0.162018E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.430253E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2225299.54 | 0.341667E+09 |
February | 0.901968E+09 | 0.375826E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2827492.27 | 0.263039E+09 |
March | 0.107774E+10 | 0.431479E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8263678.49 | 0.279836E+09 |
April | 0.956342E+09 | 0.376766E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13553214.98 | 0.127410E+09 |
May | 0.103597E+10 | 0.393416E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55791294.02 | 21720483.53 |
June | 0.103308E+10 | 0.386274E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50767091.11 | 16717437.50 |
July | 0.959235E+09 | 0.366254E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70523955.65 | 7107277.87 |
August | 0.107774E+10 | 0.413859E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68726010.82 | 21460956.79 |
September | 0.956342E+09 | 0.381335E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62832760.85 | 34524866.68 |
October | 0.994195E+09 | 0.406469E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52328502.79 | 0.111786E+09 |
November | 0.984487E+09 | 0.423269E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6977055.61 | 0.180189E+09 |
December | 0.959235E+09 | 0.425654E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4747288.02 | 0.307021E+09 |
Annual Sum or Average | 0.119305E+11 | 0.481085E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399564E+09 | 0.171248E+10 |
Minimum of Months | 0.901968E+09 | 0.366254E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2225299.54 | 7107277.87 |
Maximum of Months | 0.107774E+10 | 0.431479E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70523955.65 | 0.341667E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.267505E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 691850.16 | 0.241816E+09 |
February | 0.421807E+09 | 0.235000E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1190039.63 | 0.186474E+09 |
March | 0.502994E+09 | 0.270705E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3556197.24 | 0.197246E+09 |
April | 0.447140E+09 | 0.238009E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7892799.15 | 91257591.99 |
May | 0.484071E+09 | 0.250530E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33948607.39 | 15863423.37 |
June | 0.482240E+09 | 0.246869E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32107229.62 | 11775044.57 |
July | 0.448971E+09 | 0.233155E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43561518.37 | 5458710.56 |
August | 0.502994E+09 | 0.262291E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43101873.31 | 15129573.40 |
September | 0.447140E+09 | 0.240869E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37831264.45 | 24450856.79 |
October | 0.465148E+09 | 0.255392E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30400075.40 | 79598845.43 |
November | 0.460569E+09 | 0.264165E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3186878.34 | 0.128561E+09 |
December | 0.448971E+09 | 0.265533E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2119499.81 | 0.214359E+09 |
Annual Sum or Average | 0.557719E+10 | 0.303002E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239588E+09 | 0.121199E+10 |
Minimum of Months | 0.421807E+09 | 0.233155E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 691850.16 | 5458710.56 |
Maximum of Months | 0.502994E+09 | 0.270705E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43561518.37 | 0.241816E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.411033E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 645085.88 | 0.390391E+09 |
February | 0.901968E+09 | 0.365524E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1581284.55 | 0.298308E+09 |
March | 0.107774E+10 | 0.427103E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5092352.60 | 0.297442E+09 |
April | 0.956342E+09 | 0.377845E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12342294.99 | 0.134801E+09 |
May | 0.103597E+10 | 0.397259E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55778713.41 | 21674496.69 |
June | 0.103308E+10 | 0.391354E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51697454.04 | 16124720.12 |
July | 0.959235E+09 | 0.369558E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71074194.13 | 7042692.54 |
August | 0.107774E+10 | 0.415685E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67469559.44 | 21967283.02 |
September | 0.956342E+09 | 0.380251E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58209956.30 | 37310327.05 |
October | 0.994195E+09 | 0.401498E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43648213.75 | 0.128709E+09 |
November | 0.984487E+09 | 0.406672E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4270217.00 | 0.205464E+09 |
December | 0.959235E+09 | 0.406378E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2775636.54 | 0.347793E+09 |
Annual Sum or Average | 0.119305E+11 | 0.475016E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374585E+09 | 0.190703E+10 |
Minimum of Months | 0.901968E+09 | 0.365524E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 645085.88 | 7042692.54 |
Maximum of Months | 0.107774E+10 | 0.427103E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71074194.13 | 0.390391E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.265192E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 868114.04 | 0.241115E+09 |
February | 0.570983E+09 | 0.234769E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1382191.10 | 0.185849E+09 |
March | 0.682256E+09 | 0.272975E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4555693.17 | 0.195397E+09 |
April | 0.605404E+09 | 0.239621E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7647830.60 | 93704965.42 |
May | 0.655811E+09 | 0.251269E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35587428.14 | 16318578.06 |
June | 0.653980E+09 | 0.246887E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32133571.23 | 12696959.22 |
July | 0.607235E+09 | 0.233783E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43970103.99 | 5882632.17 |
August | 0.682256E+09 | 0.263646E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43982550.68 | 16599564.48 |
September | 0.605404E+09 | 0.242830E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38505426.31 | 25900514.88 |
October | 0.629366E+09 | 0.256536E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31412257.60 | 82471841.10 |
November | 0.623221E+09 | 0.260947E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3748310.45 | 0.126765E+09 |
December | 0.607235E+09 | 0.261268E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2472848.40 | 0.215568E+09 |
Annual Sum or Average | 0.755252E+10 | 0.302972E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246266E+09 | 0.121827E+10 |
Minimum of Months | 0.570983E+09 | 0.233783E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 868114.04 | 5882632.17 |
Maximum of Months | 0.682256E+09 | 0.272975E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43982550.68 | 0.241115E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007457.86 | 0.509133E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1955091.05 | 0.390627E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7387249.34 | 0.402550E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13512416.89 | 0.179413E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64382987.92 | 21894353.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59196927.96 | 18684012.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87480159.13 | 6296564.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80288590.49 | 25753424.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71167448.40 | 44585929.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53429798.42 | 0.161329E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5175489.63 | 0.269968E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3527344.00 | 0.456773E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448511E+09 | 0.248701E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1007457.86 | 6296564.38 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87480159.13 | 0.509133E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1935687.26 | 0.614530E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3262408.23 | 0.474810E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10450994.88 | 0.499221E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17272324.56 | 0.226990E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80289614.64 | 30629500.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74064693.96 | 25595773.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109075E+09 | 9368748.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101984E+09 | 33079403.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90298796.41 | 56706772.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68876664.56 | 0.199591E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7514946.57 | 0.329284E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5410274.17 | 0.551948E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570435E+09 | 0.305175E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1935687.26 | 9368748.12 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109075E+09 | 0.614530E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334134.69 | 0.600625E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726521.66 | 0.464945E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4107805.35 | 0.498337E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9743339.76 | 0.236130E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68331989.25 | 28588226.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65751446.28 | 22729418.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95466164.81 | 9060479.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94753357.32 | 30376263.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82590751.57 | 50928062.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53506448.57 | 0.191785E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4509511.87 | 0.313015E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2736164.05 | 0.532932E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482558E+09 | 0.297945E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334134.69 | 9060479.84 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95466164.81 | 0.600625E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 605.66 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.70 | 16-JAN-14:55 | 728.34 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 626.73 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.00 | 20-FEB-15:00 | 979.88 | 05-FEB-07:55 |
March | 1306.65 | 01-MAR-10:09 | 577.00 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.76 | 05-MAR-12:43 | 924.45 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 593.30 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.39 | 29-APR-17:02 | 561.63 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 409.91 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.85 | 21-MAY-13:50 | 129.98 | 14-MAY-11:55 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.77 | 10-JUN-17:02 | 171.50 | 18-JUN-13:53 |
July | 1306.65 | 03-JUL-09:09 | 398.00 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.88 | 02-JUL-11:48 | 109.55 | 31-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 411.77 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 | 20-AUG-13:53 | 228.07 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 575.35 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 396.60 | 09-SEP-17:02 | 255.69 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 657.07 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.39 | 09-OCT-13:55 | 418.15 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 630.52 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.83 | 05-NOV-13:00 | 650.39 | 12-NOV-07:00 |
December | 1306.65 | 01-DEC-10:09 | 651.68 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.68 | 10-DEC-11:00 | 900.14 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 95.70 | 109.55 | |||||
Maximum of Months | 1306.65 | 657.07 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 473.39 | 979.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 359.09 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.99 | 16-JAN-15:00 | 482.54 | 21-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 381.06 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 | 20-FEB-15:00 | 712.19 | 05-FEB-10:00 |
March | 827.22 | 01-MAR-10:09 | 336.66 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.04 | 05-MAR-12:50 | 623.12 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 359.54 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.15 | 29-APR-17:02 | 384.69 | 01-APR-18:00 |
May | 827.22 | 01-MAY-09:09 | 252.95 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.04 | 21-MAY-13:50 | 107.62 | 14-MAY-12:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.80 | 10-JUN-17:02 | 126.47 | 18-JUN-13:53 |
July | 827.22 | 03-JUL-09:09 | 236.85 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.99 | 02-JUL-11:48 | 117.88 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 250.56 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.80 | 20-AUG-14:07 | 153.03 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 334.54 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.13 | 09-SEP-17:02 | 172.93 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 405.53 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.68 | 09-OCT-13:55 | 283.19 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 403.66 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 | 05-NOV-13:00 | 510.70 | 12-NOV-08:50 |
December | 827.22 | 01-DEC-10:09 | 406.01 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 10-DEC-15:00 | 600.15 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 | 107.62 | |||||
Maximum of Months | 827.22 | 406.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 323.68 | 712.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 586.79 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.86 | 19-JAN-12:05 | 824.99 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 614.92 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.29 | 02-FEB-13:00 | 1024.79 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 570.54 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 26-MAR-13:45 | 951.61 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 595.80 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.43 | 29-APR-17:02 | 593.33 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 412.79 | 23-MAY-07:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.99 | 21-MAY-13:50 | 137.98 | 14-MAY-11:55 |
June | 1306.65 | 01-JUN-09:09 | 386.39 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.02 | 10-JUN-17:02 | 173.69 | 18-JUN-13:53 |
July | 1306.65 | 03-JUL-09:09 | 406.48 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.64 | 22-JUL-18:50 | 111.22 | 30-JUL-11:10 |
August | 1306.65 | 01-AUG-09:09 | 482.31 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.59 | 20-AUG-13:53 | 229.98 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 573.41 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.04 | 09-SEP-17:10 | 261.53 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 652.14 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.64 | 09-OCT-13:55 | 450.77 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 611.65 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.11 | 07-NOV-13:00 | 791.28 | 12-NOV-11:00 |
December | 1306.65 | 01-DEC-10:09 | 644.74 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.11 | 13-DEC-14:00 | 917.88 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 386.39 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 22.86 | 111.22 | |||||
Maximum of Months | 1306.65 | 652.14 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 454.64 | 1024.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 388.84 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 16-JAN-12:53 | 509.67 | 22-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 399.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.19 | 02-FEB-13:00 | 652.55 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 379.47 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.61 | 05-MAR-12:43 | 634.68 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 385.02 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.20 | 29-APR-17:08 | 421.02 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 320.41 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.07 | 21-MAY-13:50 | 105.48 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 255.98 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.89 | 10-JUN-17:08 | 130.07 | 18-JUN-13:53 |
July | 827.17 | 03-JUL-09:09 | 299.58 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.85 | 02-JUL-11:48 | 81.10 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 347.98 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.25 | 20-AUG-13:53 | 158.91 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 379.86 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.40 | 09-SEP-17:07 | 173.81 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 419.47 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.28 | 09-OCT-13:53 | 291.78 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 407.91 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.71 | 11-NOV-12:00 | 438.24 | 12-NOV-07:00 |
December | 827.17 | 01-DEC-10:09 | 412.78 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 | 10-DEC-11:00 | 602.56 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 255.98 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 42.19 | 81.10 | |||||
Maximum of Months | 827.17 | 419.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 315.28 | 652.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 600.66 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 | 16-JAN-15:00 | 444.66 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 622.57 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 | 20-FEB-15:00 | 624.14 | 05-FEB-07:55 |
March | 1306.65 | 01-MAR-10:09 | 570.73 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.18 | 05-MAR-13:00 | 522.16 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 587.78 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.81 | 29-APR-17:02 | 298.15 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 407.82 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.14 | 21-MAY-13:50 | 47.80 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.92 | 10-JUN-17:02 | 86.85 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 395.30 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.22 | 22-JUL-18:50 | 49.66 | 31-JUL-02:40 |
August | 1306.65 | 01-AUG-09:09 | 409.76 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.33 | 20-AUG-14:00 | 132.36 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 569.04 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.88 | 09-SEP-23:00 | 138.02 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 654.04 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.24 | 09-OCT-14:00 | 264.86 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 626.33 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.89 | 11-NOV-13:00 | 383.24 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 648.50 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 10-DEC-15:00 | 566.58 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 54.85 | 47.80 | |||||
Maximum of Months | 1306.65 | 654.04 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 262.24 | 624.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 355.01 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 16-JAN-15:00 | 298.39 | 22-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 378.25 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 20-FEB-15:00 | 442.60 | 05-FEB-08:00 |
March | 827.22 | 01-MAR-10:09 | 332.07 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.46 | 05-MAR-13:00 | 360.31 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 355.86 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.97 | 29-APR-17:02 | 207.98 | 01-APR-21:00 |
May | 827.22 | 01-MAY-09:09 | 251.92 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.29 | 21-MAY-13:50 | 55.15 | 14-MAY-11:55 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.75 | 10-JUN-17:02 | 62.52 | 18-JUN-14:00 |
July | 827.22 | 03-JUL-09:09 | 222.09 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.17 | 22-JUL-18:50 | 53.06 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 248.86 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.43 | 20-AUG-13:58 | 92.03 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 329.72 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.43 | 09-SEP-23:00 | 102.30 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 403.53 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 | 09-OCT-13:44 | 182.95 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 401.74 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 05-NOV-13:00 | 296.03 | 12-NOV-08:30 |
December | 827.22 | 01-DEC-10:09 | 404.09 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.39 | 10-DEC-15:00 | 385.88 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 53.06 | |||||
Maximum of Months | 827.22 | 404.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 | 442.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 580.88 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2499.18 | 02-JAN-13:00 | 25090.06 | 05-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 610.19 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4526.64 | 02-FEB-13:00 | 24431.56 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 563.95 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5254.04 | 30-MAR-12:00 | 24852.86 | 09-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 590.41 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9221.58 | 28-APR-16:03 | 14500.86 | 11-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 410.87 | 23-MAY-07:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10127.82 | 25-MAY-16:03 | 1749.86 | 02-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 383.37 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10625.69 | 28-JUN-16:03 | 2133.25 | 07-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 404.28 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13190.15 | 21-JUL-16:02 | 1410.72 | 13-JUL-11:05 |
August | 1306.65 | 01-AUG-09:09 | 472.34 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13566.91 | 30-AUG-16:01 | 2613.20 | 29-AUG-06:05 |
September | 1306.65 | 01-SEP-09:09 | 567.02 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9397.78 | 06-SEP-16:03 | 3970.49 | 07-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 648.87 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9109.41 | 06-OCT-11:02 | 9668.83 | 27-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 606.64 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5467.37 | 02-NOV-11:03 | 17105.52 | 15-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 641.22 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4674.23 | 13-DEC-13:00 | 25582.52 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 383.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2499.18 | 1410.72 | |||||
Maximum of Months | 1306.65 | 648.87 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13566.91 | 25582.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 386.48 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 16-JAN-13:43 | 300.25 | 21-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 397.93 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.71 | 02-FEB-13:00 | 419.35 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 376.82 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 | 05-MAR-13:00 | 363.26 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 382.55 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 29-APR-17:08 | 218.53 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 316.14 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 | 21-MAY-13:50 | 42.06 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 254.83 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.99 | 10-JUN-17:08 | 65.86 | 06-JUN-21:20 |
July | 827.17 | 03-JUL-09:09 | 260.83 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.62 | 16-JUL-13:00 | 41.72 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 344.13 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.77 | 20-AUG-13:58 | 94.82 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 377.23 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.77 | 09-SEP-23:00 | 102.24 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 418.05 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.98 | 09-OCT-13:44 | 187.62 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 406.10 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 | 11-NOV-12:20 | 264.41 | 12-NOV-08:00 |
December | 827.17 | 01-DEC-10:09 | 411.16 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.29 | 10-DEC-11:10 | 387.87 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 254.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 41.72 | |||||
Maximum of Months | 827.17 | 418.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 162.98 | 419.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 605.64 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 | 16-JAN-15:00 | 662.84 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 626.72 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 | 20-FEB-14:53 | 920.74 | 05-FEB-07:55 |
March | 1306.65 | 01-MAR-10:09 | 576.99 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 152.80 | 05-MAR-12:53 | 812.76 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 593.29 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.38 | 29-APR-17:02 | 473.02 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 409.90 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.31 | 07-MAY-14:00 | 90.28 | 14-MAY-11:55 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.71 | 10-JUN-17:02 | 138.73 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 398.00 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.88 | 22-JUL-18:50 | 87.40 | 31-JUL-02:20 |
August | 1306.65 | 01-AUG-09:09 | 411.77 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.68 | 20-AUG-14:00 | 197.57 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 575.33 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.61 | 09-SEP-23:00 | 214.69 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 657.06 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.06 | 09-OCT-14:00 | 386.18 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 630.51 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 | 11-NOV-13:00 | 578.00 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 651.67 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.28 | 10-DEC-15:00 | 831.19 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 | 87.40 | |||||
Maximum of Months | 1306.65 | 657.06 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 399.06 | 920.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 359.09 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | 16-JAN-15:00 | 439.51 | 21-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 381.06 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.05 | 20-FEB-14:53 | 667.74 | 05-FEB-10:00 |
March | 805.43 | 01-MAR-08:09 | 336.65 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.41 | 05-MAR-13:00 | 546.65 | 20-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 359.54 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.76 | 29-APR-17:02 | 323.09 | 01-APR-18:00 |
May | 805.43 | 01-MAY-07:10 | 252.94 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.28 | 21-MAY-14:00 | 83.47 | 14-MAY-11:55 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.98 | 10-JUN-17:02 | 100.43 | 18-JUN-13:57 |
July | 805.43 | 03-JUL-07:10 | 236.84 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.49 | 22-JUL-18:50 | 90.18 | 30-JUL-11:10 |
August | 805.43 | 01-AUG-07:10 | 250.55 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.76 | 20-AUG-13:58 | 132.92 | 25-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 334.53 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.19 | 09-SEP-23:00 | 145.80 | 05-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 405.53 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.77 | 09-OCT-13:55 | 261.22 | 29-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 403.65 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 | 05-NOV-13:00 | 454.32 | 12-NOV-08:50 |
December | 805.43 | 01-DEC-08:09 | 406.00 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | 10-DEC-15:00 | 555.22 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 | 83.47 | |||||
Maximum of Months | 805.43 | 406.00 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 266.77 | 667.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 586.78 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 19-JAN-12:10 | 701.57 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 614.91 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 02-FEB-13:00 | 959.24 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 570.53 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.75 | 26-MAR-13:53 | 833.39 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 595.79 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.14 | 29-APR-17:02 | 495.91 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 412.79 | 23-MAY-07:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.39 | 21-MAY-14:00 | 97.53 | 14-MAY-11:55 |
June | 1306.65 | 01-JUN-09:09 | 386.38 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.12 | 10-JUN-17:02 | 138.25 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 406.48 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.68 | 22-JUL-18:50 | 89.20 | 31-JUL-02:70 |
August | 1306.65 | 01-AUG-09:09 | 482.29 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.90 | 20-AUG-13:58 | 199.16 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 573.40 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.71 | 09-SEP-23:00 | 220.45 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 652.13 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.87 | 09-OCT-13:55 | 411.46 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 611.64 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 | 07-NOV-13:00 | 668.28 | 12-NOV-10:53 |
December | 1306.65 | 01-DEC-10:09 | 644.73 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.58 | 13-DEC-14:00 | 848.44 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 386.38 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 | 89.20 | |||||
Maximum of Months | 1306.65 | 652.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 377.87 | 959.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 388.83 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 | 16-JAN-13:13 | 442.17 | 21-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 399.94 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 | 02-FEB-13:00 | 613.37 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 379.46 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.71 | 05-MAR-12:53 | 556.04 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 385.01 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 | 29-APR-17:08 | 351.62 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 320.40 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.30 | 21-MAY-13:50 | 73.50 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 255.98 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.93 | 10-JUN-17:08 | 103.48 | 18-JUN-13:57 |
July | 827.17 | 03-JUL-09:09 | 299.56 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.11 | 02-JUL-11:50 | 66.07 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 347.97 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.59 | 20-AUG-13:58 | 137.30 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 379.85 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.16 | 09-SEP-23:00 | 146.44 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 419.47 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.38 | 09-OCT-13:53 | 267.45 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 407.90 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.52 | 11-NOV-12:20 | 389.11 | 12-NOV-07:05 |
December | 827.17 | 01-DEC-10:09 | 412.77 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.34 | 10-DEC-11:00 | 556.90 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 255.98 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 | 66.07 | |||||
Maximum of Months | 827.17 | 419.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 261.38 | 613.37 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.42 | 16-JAN-15:00 | 964.11 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.78 | 20-FEB-15:00 | 1374.57 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.04 | 05-MAR-13:00 | 1174.29 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.73 | 29-APR-17:02 | 670.48 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.72 | 07-MAY-13:55 | 113.16 | 14-MAY-11:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.54 | 10-JUN-17:02 | 183.74 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.07 | 22-JUL-18:53 | 93.12 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.54 | 20-AUG-14:00 | 268.09 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.21 | 09-SEP-17:02 | 264.44 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.80 | 09-OCT-14:00 | 573.98 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 | 05-NOV-13:00 | 825.63 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 | 10-DEC-15:00 | 1260.65 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 | 93.12 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.80 | 1374.57 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.99 | 16-JAN-14:53 | 1205.10 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.95 | 20-FEB-14:53 | 1673.80 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.53 | 05-MAR-13:00 | 1481.30 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.62 | 29-APR-17:02 | 845.89 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.35 | 07-MAY-14:00 | 161.11 | 14-MAY-11:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.36 | 10-JUN-17:02 | 238.40 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.85 | 22-JUL-18:50 | 131.48 | 31-JUL-02:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.05 | 20-AUG-14:00 | 342.43 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.77 | 09-SEP-17:02 | 354.19 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.86 | 09-OCT-14:00 | 695.72 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.56 | 05-NOV-13:00 | 1041.68 | 12-NOV-07:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.51 | 10-DEC-15:00 | 1518.68 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.56 | 131.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.05 | 1673.80 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 16-JAN-15:00 | 1095.05 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.18 | 02-FEB-13:00 | 1493.76 | 04-FEB-18:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.13 | 26-MAR-13:53 | 1455.68 | 20-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.37 | 29-APR-17:02 | 935.11 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.37 | 07-MAY-14:00 | 331.07 | 14-MAY-11:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.98 | 10-JUN-17:02 | 269.44 | 18-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.31 | 02-JUL-10:53 | 263.67 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.17 | 20-AUG-13:53 | 327.84 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.04 | 09-SEP-22:53 | 359.44 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.93 | 08-OCT-14:00 | 625.15 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.23 | 07-NOV-22:03 | 975.23 | 12-NOV-07:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 | 13-DEC-14:05 | 1410.33 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 | 263.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.04 | 1493.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 33250.13 | 02-JAN-06:13 | 1905.79 | 1162.90 | 12144.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16919.57 | 02-FEB-08:05 | 24140.03 | 13954.80 | 51033.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16820.92 | 30-MAR-08:00 | 6035.01 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19586.46 | 24-APR-06:03 | 3811.58 | 3488.70 | 18132.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33703.43 | 27-MAY-05:03 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33696.01 | 24-JUN-05:03 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33874.97 | 31-JUL-04:03 | 0.00 | 1550.53 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33301.54 | 12-AUG-05:03 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32897.20 | 18-SEP-04:03 | 0.00 | 1550.53 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32985.66 | 23-OCT-04:03 | 0.00 | 1550.53 | 13856.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29995.66 | 06-NOV-07:03 | 5082.11 | 4651.60 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17563.75 | 15-DEC-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16820.92 | 0.00 | 1162.90 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33874.97 | 24140.03 | 13954.80 | 51033.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5389.95 | 19-JAN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 |
February | 6362.30 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
March | 6166.12 | 29-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 0.00 |
April | 8722.22 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.82 | 0.00 |
May | 9368.04 | 10-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 0.00 |
June | 9426.51 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.91 | 0.00 |
July | 9815.55 | 18-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.76 | 0.00 |
August | 9550.70 | 03-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.12 | 0.00 |
September | 8858.73 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.43 | 0.00 |
October | 9047.99 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.66 | 0.00 |
November | 7332.42 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 0.00 |
December | 6446.28 | 15-DEC-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5389.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9815.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.12 | 19.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3147.36 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.45 |
February | 2656.14 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.49 |
March | 3199.12 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.59 |
April | 3180.63 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.26 | 0.00 |
May | 4432.01 | 30-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 4365.24 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 |
July | 4431.68 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 | 0.00 |
August | 4447.98 | 28-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 |
September | 4621.80 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 |
October | 4827.40 | 10-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.49 | 0.00 |
November | 3345.78 | 06-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
December | 2577.22 | 15-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2577.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4827.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.49 | 291.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3218.31 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.62 |
February | 2875.14 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.97 |
March | 2959.35 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.01 |
April | 3218.82 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 | 0.00 |
May | 4166.05 | 30-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
June | 4004.75 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 |
July | 4593.69 | 05-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
August | 4412.67 | 28-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.39 | 0.00 |
September | 4466.93 | 05-SEP-12:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.81 | 0.00 |
October | 4753.01 | 10-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.21 | 0.00 |
November | 3740.09 | 06-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3025.67 | 18-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2875.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4753.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.21 | 229.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26391.27 | 02-JAN-06:13 | 1905.79 | 1162.90 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13414.85 | 27-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13104.39 | 27-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14549.30 | 28-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28050.05 | 08-MAY-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28428.69 | 19-JUN-04:03 | 0.00 | 1162.90 | 7326.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28434.30 | 31-JUL-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28116.55 | 12-AUG-05:03 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30986.65 | 05-SEP-05:15 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28597.55 | 10-OCT-06:05 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16621.67 | 06-NOV-06:13 | 1905.79 | 1162.90 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13858.01 | 15-DEC-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13104.39 | 0.00 | 1162.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30986.65 | 6035.01 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14989.88 | 02-JAN-14:20 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14607.12 | 27-FEB-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14603.56 | 29-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17283.73 | 28-APR-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31219.86 | 08-MAY-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31327.77 | 12-JUN-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31424.02 | 31-JUL-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30544.84 | 07-AUG-04:02 | 0.00 | 1938.17 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31278.84 | 18-SEP-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30999.02 | 23-OCT-04:03 | 0.00 | 1550.53 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16447.79 | 06-NOV-15:00 | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14951.05 | 15-DEC-16:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14603.56 | 0.00 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31424.02 | 6198.29 | 3488.70 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3935.28 | 02-JAN-13:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | 0.00 |
February | 3892.01 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 | 0.00 |
March | 4929.54 | 30-MAR-13:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 0.00 |
April | 5959.48 | 28-APR-15:10 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 81.15 | 0.00 |
May | 10882.56 | 07-MAY-15:02 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 131.84 | 0.00 |
June | 10932.32 | 11-JUN-17:32 | 0.00 | 116.92 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 141.82 | 0.00 |
July | 11107.86 | 23-JUL-14:02 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 165.09 | 0.00 |
August | 10931.22 | 20-AUG-16:03 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 155.31 | 0.00 |
September | 10971.25 | 10-SEP-15:22 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 149.06 | 0.00 |
October | 9002.19 | 09-OCT-13:52 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 430.16 | 0.00 |
November | 4890.04 | 02-NOV-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.26 | 0.00 |
December | 4289.34 | 15-DEC-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3892.01 | 0.00 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | 0.00 | |
Maximum of Months | 11107.86 | 1306.65 | 350.81 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 430.16 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4295.43 | 19-JAN-10:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 |
February | 4682.03 | 27-FEB-10:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 |
March | 6892.31 | 26-MAR-10:03 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 |
April | 11581.97 | 23-APR-08:32 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 |
May | 12160.52 | 14-MAY-09:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 0.00 |
June | 12125.79 | 11-JUN-10:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.20 | 0.00 |
July | 12144.19 | 16-JUL-10:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 | 0.00 |
August | 11547.78 | 27-AUG-09:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 64.78 | 0.00 |
September | 11664.82 | 10-SEP-09:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 136.43 | 0.00 |
October | 12042.31 | 09-OCT-10:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 111.46 | 0.00 |
November | 6022.16 | 11-NOV-09:53 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.90 |
December | 3615.14 | 16-DEC-10:10 | 522.45 | 148.06 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3615.14 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12160.52 | 827.22 | 222.09 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 136.43 | 63.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15970.35 | 01-JAN-13:51 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 |
February | 14341.25 | 26-FEB-13:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 |
March | 11998.84 | 26-MAR-16:03 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 |
April | 10251.57 | 23-APR-13:53 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 0.00 |
May | 13265.34 | 07-MAY-15:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 132.71 | 0.00 |
June | 12546.32 | 04-JUN-16:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 60.93 | 0.00 |
July | 13431.47 | 23-JUL-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 169.45 | 0.00 |
August | 13240.10 | 20-AUG-16:03 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 159.49 | 0.00 |
September | 14152.93 | 17-SEP-13:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 91.58 | 0.00 |
October | 14708.39 | 09-OCT-10:32 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 153.52 | 0.00 |
November | 14245.28 | 05-NOV-12:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 |
December | 15539.55 | 10-DEC-13:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10251.57 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15970.35 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 169.45 | 43.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9218.01 | 01-JAN-14:31 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 |
February | 12585.76 | 26-FEB-16:33 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 |
March | 11186.63 | 26-MAR-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.63 |
April | 12269.49 | 23-APR-16:32 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 0.00 |
May | 13046.49 | 29-MAY-16:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 62.25 | 0.00 |
June | 12980.53 | 11-JUN-16:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 70.96 | 0.00 |
July | 12315.38 | 16-JUL-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 131.17 | 0.00 |
August | 11831.30 | 20-AUG-17:23 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 88.16 | 0.00 |
September | 13009.32 | 10-SEP-16:02 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 84.16 | 0.00 |
October | 12613.75 | 08-OCT-15:32 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 185.28 | 0.00 |
November | 10749.43 | 05-NOV-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
December | 12571.62 | 10-DEC-15:52 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9218.01 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13046.49 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 185.28 | 33.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3532.84 | 02-JAN-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 0.00 |
February | 2901.97 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 0.00 |
March | 3670.22 | 30-MAR-13:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 0.00 |
April | 4274.40 | 28-APR-15:10 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 0.00 |
May | 5900.31 | 31-MAY-05:02 | 669.60 | 223.18 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
June | 6489.81 | 26-JUN-04:02 | 0.00 | 408.58 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7466.33 | 05-JUL-04:02 | 0.00 | 408.58 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 7431.04 | 14-AUG-04:02 | 0.00 | 408.58 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 | 0.00 |
September | 7233.95 | 11-SEP-04:02 | 0.00 | 408.58 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 |
October | 7229.34 | 08-OCT-14:42 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 157.78 | 0.00 |
November | 4438.24 | 03-NOV-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 0.00 |
December | 3834.21 | 15-DEC-14:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2901.97 | 0.00 | 116.92 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7466.33 | 2613.31 | 701.62 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 157.78 | 11.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3784.05 | 19-JAN-10:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
February | 3856.38 | 27-FEB-10:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
March | 4084.64 | 07-MAR-10:40 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
April | 4907.33 | 23-APR-09:23 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 |
May | 10095.65 | 29-MAY-09:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 |
June | 6500.27 | 12-JUN-09:40 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 0.00 |
July | 10398.36 | 16-JUL-10:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 | 0.00 |
August | 9552.94 | 27-AUG-09:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 | 0.00 |
September | 10773.98 | 03-SEP-09:42 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 0.00 |
October | 10525.62 | 09-OCT-10:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 62.70 | 0.00 |
November | 5042.43 | 11-NOV-09:33 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 |
December | 3380.89 | 16-DEC-10:10 | 522.45 | 148.06 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3380.89 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10773.98 | 827.22 | 222.09 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 62.70 | 18.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13478.45 | 01-JAN-13:51 | 468.72 | 136.41 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 |
February | 12035.31 | 26-FEB-13:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 |
March | 9592.90 | 06-MAR-13:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3829.62 | 0.00 |
April | 10552.09 | 28-APR-16:10 | 1205.27 | 584.68 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8299.45 | 0.00 |
May | 10786.52 | 19-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8168.88 | 0.00 |
June | 10938.62 | 28-JUN-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8731.91 | 0.00 |
July | 11490.27 | 21-JUL-16:10 | 2410.55 | 1169.36 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11042.45 | 0.00 |
August | 11986.76 | 30-AUG-16:20 | 1607.03 | 779.58 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 10690.77 | 0.00 |
September | 11905.67 | 24-SEP-12:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 | 0.00 |
October | 12652.19 | 08-OCT-14:42 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 105.66 | 0.00 |
November | 12192.38 | 11-NOV-15:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 |
December | 12550.41 | 17-DEC-13:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9592.90 | 267.84 | 77.95 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13478.45 | 2410.55 | 1169.36 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11042.45 | 263.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7249.44 | 01-JAN-17:12 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 |
February | 8558.91 | 26-FEB-16:33 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 |
March | 4879.39 | 06-MAR-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 0.00 |
April | 10714.00 | 23-APR-17:42 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 |
May | 10683.37 | 29-MAY-16:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 40.44 | 0.00 |
June | 10661.60 | 25-JUN-16:11 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 | 0.00 |
July | 8884.31 | 02-JUL-15:02 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 37.32 | 0.00 |
August | 8738.07 | 20-AUG-17:12 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 | 0.00 |
September | 11007.35 | 24-SEP-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 24.11 | 0.00 |
October | 11037.22 | 08-OCT-16:02 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 76.20 | 0.00 |
November | 8855.58 | 05-NOV-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
December | 5245.57 | 15-DEC-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4879.39 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11037.22 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 76.20 | 21.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4020.49 | 02-JAN-13:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 0.00 |
February | 3616.03 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
March | 4575.67 | 30-MAR-13:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 | 0.00 |
April | 5218.98 | 26-APR-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 | 0.00 |
May | 7554.56 | 31-MAY-05:02 | 669.60 | 223.18 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
June | 7610.47 | 05-JUN-04:02 | 0.00 | 408.58 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 |
July | 9253.65 | 23-JUL-14:02 | 267.84 | 77.95 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 | 0.00 |
August | 7739.94 | 05-AUG-05:03 | 535.68 | 326.87 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 0.00 |
September | 9206.37 | 10-SEP-15:51 | 535.68 | 155.89 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 128.49 | 0.00 |
October | 9313.20 | 08-OCT-14:42 | 401.76 | 116.92 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 236.24 | 0.00 |
November | 4469.27 | 03-NOV-14:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 | 0.00 |
December | 3921.12 | 15-DEC-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3616.03 | 0.00 | 77.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9313.20 | 2613.31 | 701.62 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 236.24 | 24.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6251.57 | 03-JAN-13:01 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.02 |
February | 5708.88 | 27-FEB-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
March | 7049.54 | 26-MAR-09:53 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 |
April | 11589.02 | 23-APR-09:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 |
May | 11597.14 | 14-MAY-09:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 0.00 |
June | 11540.75 | 11-JUN-10:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 37.48 | 0.00 |
July | 11505.06 | 16-JUL-10:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 | 0.00 |
August | 11013.07 | 27-AUG-09:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 56.17 | 0.00 |
September | 11927.90 | 03-SEP-09:42 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.15 | 0.00 |
October | 11506.62 | 09-OCT-10:32 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 | 0.00 |
November | 6877.31 | 11-NOV-09:33 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 |
December | 6032.18 | 18-DEC-13:01 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5708.88 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11927.90 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 | 45.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12874.94 | 01-JAN-14:02 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
February | 12924.04 | 26-FEB-13:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 |
March | 10538.62 | 05-MAR-13:53 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 0.00 |
April | 8787.11 | 23-APR-14:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 60.71 | 0.00 |
May | 9228.76 | 30-MAY-04:02 | 0.00 | 408.58 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9403.37 | 05-JUN-04:02 | 0.00 | 408.58 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 |
July | 11280.40 | 23-JUL-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 148.17 | 0.00 |
August | 9539.38 | 14-AUG-04:02 | 0.00 | 408.58 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 0.00 |
September | 12372.74 | 17-SEP-13:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 80.26 | 0.00 |
October | 13049.01 | 08-OCT-14:43 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 221.15 | 0.00 |
November | 12641.32 | 05-NOV-12:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 |
December | 13146.32 | 17-DEC-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8787.11 | 0.00 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13146.32 | 401.76 | 408.58 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 221.15 | 387.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9335.97 | 01-JAN-16:42 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 |
February | 11316.04 | 26-FEB-16:23 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 |
March | 9474.44 | 26-MAR-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
April | 11859.45 | 23-APR-17:42 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.65 |
May | 11938.79 | 14-MAY-17:42 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 0.00 |
June | 11793.70 | 11-JUN-16:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 61.54 | 0.00 |
July | 10502.83 | 16-JUL-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 111.40 | 0.00 |
August | 10077.75 | 20-AUG-17:12 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 | 0.00 |
September | 12135.58 | 24-SEP-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 | 0.00 |
October | 11991.95 | 08-OCT-16:02 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 108.07 | 0.00 |
November | 9716.90 | 05-NOV-16:03 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 | 0.00 |
December | 5677.58 | 15-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5677.58 | 0.00 | 49.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12135.58 | 805.38 | 222.08 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 111.40 | 40.65 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.924581E+11 | 102683.77 | 10-JAN-07:10 | 0.116292E+11 | 31850.94 | 05-JAN-07:49 |
February | 0.877365E+11 | 122368.03 | 06-FEB-07:10 | 0.996279E+10 | 27764.77 | 17-FEB-07:30 |
March | 0.102084E+12 | 101642.63 | 30-MAR-12:00 | 0.108957E+11 | 28637.30 | 09-MAR-07:40 |
April | 0.106377E+12 | 125296.40 | 28-APR-15:00 | 0.962291E+10 | 9581.38 | 04-APR-11:09 |
May | 0.140682E+12 | 127067.02 | 30-MAY-12:00 | 0.980096E+10 | 9493.58 | 01-MAY-11:20 |
June | 0.144756E+12 | 130948.35 | 28-JUN-15:09 | 0.934653E+10 | 9397.34 | 02-JUN-11:39 |
July | 0.146054E+12 | 137084.16 | 21-JUL-15:50 | 0.921641E+10 | 9337.54 | 07-JUL-11:09 |
August | 0.153714E+12 | 138107.69 | 03-AUG-15:39 | 0.960443E+10 | 9371.52 | 31-AUG-11:09 |
September | 0.134005E+12 | 129948.94 | 06-SEP-15:00 | 0.922136E+10 | 9435.30 | 29-SEP-11:30 |
October | 0.131035E+12 | 134065.18 | 06-OCT-12:09 | 0.978885E+10 | 9533.91 | 31-OCT-11:39 |
November | 0.102685E+12 | 119002.76 | 02-NOV-15:09 | 0.981797E+10 | 9626.62 | 30-NOV-12:30 |
December | 0.960626E+11 | 107471.39 | 15-DEC-13:00 | 0.110271E+11 | 30312.12 | 20-DEC-08:09 |
Annual Sum or Average | 0.143765E+13 | 0.119934E+12 | ||||
Minimum of Months | 0.877365E+11 | 101642.63 | 0.921641E+10 | 9337.54 | ||
Maximum of Months | 0.153714E+12 | 138107.69 | 0.116292E+11 | 31850.94 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.104561E+11 | 18815.75 | 23-JAN-12:50 | 0.00 | 0.00 |
February | 0.116588E+11 | 21783.28 | 13-FEB-12:30 | 0.00 | 0.00 |
March | 0.137456E+11 | 25279.54 | 22-MAR-12:30 | 0.00 | 0.00 |
April | 0.163910E+11 | 25865.13 | 10-APR-12:30 | 0.00 | 0.00 |
May | 0.158857E+11 | 25141.97 | 15-MAY-12:30 | 0.00 | 0.00 |
June | 0.168415E+11 | 25350.99 | 09-JUN-12:30 | 0.00 | 0.00 |
July | 0.163793E+11 | 23958.39 | 06-JUL-12:39 | 0.00 | 0.00 |
August | 0.154631E+11 | 24009.99 | 03-AUG-12:30 | 0.00 | 0.00 |
September | 0.129770E+11 | 22421.66 | 03-SEP-12:30 | 0.00 | 0.00 |
October | 0.128790E+11 | 21537.66 | 01-OCT-12:30 | 0.00 | 0.00 |
November | 0.104331E+11 | 19424.09 | 15-NOV-12:20 | 0.00 | 0.00 |
December | 0.948790E+10 | 17318.26 | 26-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.162598E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.948790E+10 | 17318.26 | 0.00 | 0.00 | |
Maximum of Months | 0.168415E+11 | 25865.13 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.140802E+11 | 0.347410E+10 | 0.545046E+11 | 0.976456E+09 | 0.361677E+10 | 12379742.02 | 0.414416E+10 | 0.116494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126670E+11 | 0.290952E+10 | 0.493409E+11 | 0.883666E+09 | 0.347884E+10 | 11196021.66 | 0.229377E+10 | 0.161517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149402E+11 | 0.293688E+10 | 0.567112E+11 | 0.102247E+10 | 0.411665E+10 | 12675672.10 | 0.255574E+10 | 0.197884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132858E+11 | 0.257474E+10 | 0.526212E+11 | 0.940478E+09 | 0.482803E+10 | 11960507.72 | 0.175906E+09 | 0.319390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142245E+11 | 0.241001E+10 | 0.556079E+11 | 0.999294E+09 | 0.789040E+10 | 12527707.06 | 0.00 | 0.595378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141111E+11 | 0.220682E+10 | 0.546110E+11 | 0.983628E+09 | 0.841886E+10 | 12231776.97 | 0.00 | 0.644119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132476E+11 | 0.236793E+10 | 0.536070E+11 | 0.955940E+09 | 0.845250E+10 | 12256437.81 | 0.00 | 0.674107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148010E+11 | 0.255894E+10 | 0.567112E+11 | 0.102238E+10 | 0.917200E+10 | 12675672.10 | 0.00 | 0.694361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133247E+11 | 0.271617E+10 | 0.525990E+11 | 0.940264E+09 | 0.747748E+10 | 11960507.72 | 0.00 | 0.569349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139188E+11 | 0.308529E+10 | 0.545158E+11 | 0.976484E+09 | 0.778125E+10 | 12379742.02 | 33799859.74 | 0.507115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139059E+11 | 0.327290E+10 | 0.533244E+11 | 0.958278E+09 | 0.479755E+10 | 12059151.09 | 0.324291E+09 | 0.260894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137136E+11 | 0.354983E+10 | 0.535958E+11 | 0.956121E+09 | 0.397905E+10 | 12256437.81 | 0.299607E+10 | 0.172599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166220E+12 | 0.340631E+11 | 0.647750E+12 | 0.116155E+11 | 0.740094E+11 | 0.146559E+09 | 0.125237E+11 | 0.491321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126670E+11 | 0.220682E+10 | 0.493409E+11 | 0.883666E+09 | 0.347884E+10 | 11196021.66 | 0.00 | 0.116494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149402E+11 | 0.354983E+10 | 0.567112E+11 | 0.102247E+10 | 0.917200E+10 | 12675672.10 | 0.414416E+10 | 0.694361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.120139E+10 | 0.00 | 0.104278E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.554837E+09 | 0.00 | 0.940795E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.352303E+09 | 0.00 | 0.105434E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.962291E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.980096E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.934653E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.921641E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.960443E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.922136E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.978885E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2154209.55 | 0.00 | 0.981581E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.831567E+09 | 0.00 | 0.101956E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.294226E+10 | 0.00 | 0.116992E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.921641E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.120139E+10 | 0.00 | 0.105434E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 16268.97 | 31-JAN-08:09 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 827.93 | 31-JAN-08:20 | 7177.23 | 02-JAN-13:30 | 6.85 | 03-JAN-12:09 | 71325.72 | 10-JAN-07:10 |
February | 16520.32 | 01-FEB-08:09 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 828.27 | 01-FEB-08:20 | 7930.47 | 27-FEB-15:30 | 6.85 | 03-FEB-12:09 | 90588.55 | 06-FEB-07:10 |
March | 16036.95 | 27-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 827.63 | 27-MAR-07:19 | 6517.15 | 29-MAR-15:20 | 6.85 | 08-MAR-12:09 | 66226.83 | 13-MAR-06:10 |
April | 16250.00 | 14-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 827.91 | 14-APR-07:19 | 9850.59 | 28-APR-15:30 | 6.85 | 01-APR-05:10 | 11165.01 | 11-APR-06:10 |
May | 14615.71 | 23-MAY-07:30 | 3824.74 | 01-MAY-05:10 | 40437.79 | 01-MAY-07:10 | 825.76 | 23-MAY-07:40 | 10639.07 | 04-MAY-15:00 | 6.85 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 14107.73 | 16-JUN-07:10 | 3824.74 | 01-JUN-05:10 | 40437.79 | 01-JUN-07:10 | 825.09 | 16-JUN-07:19 | 11527.17 | 12-JUN-15:00 | 6.85 | 11-JUN-16:49 | 0.00 | 01-JUN-00:10 |
July | 14430.39 | 14-JUL-07:10 | 3824.74 | 01-JUL-05:10 | 40437.79 | 03-JUL-07:10 | 825.51 | 14-JUL-07:19 | 12351.37 | 05-JUL-14:30 | 6.85 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 14883.09 | 21-AUG-07:10 | 3824.74 | 01-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 826.11 | 21-AUG-07:19 | 13157.10 | 30-AUG-15:00 | 6.85 | 30-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 16035.37 | 26-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 827.63 | 26-SEP-07:19 | 12498.06 | 11-SEP-14:30 | 6.85 | 10-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 16858.98 | 25-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 828.71 | 25-OCT-07:19 | 13942.09 | 10-OCT-14:09 | 6.85 | 01-OCT-05:10 | 4251.75 | 27-OCT-06:00 |
November | 16518.34 | 21-NOV-16:00 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 828.20 | 01-NOV-07:19 | 10527.34 | 06-NOV-15:30 | 6.85 | 01-NOV-05:10 | 20489.18 | 16-NOV-07:10 |
December | 16801.45 | 12-DEC-08:09 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.64 | 12-DEC-08:20 | 8703.36 | 15-DEC-15:30 | 6.85 | 04-DEC-07:10 | 73485.63 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14107.73 | 3824.74 | 40437.79 | 825.09 | 6517.15 | 6.85 | 0.00 | |||||||
Maximum of Months | 16858.98 | 3824.74 | 40437.79 | 828.71 | 13942.09 | 6.85 | 90588.55 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 39517.51 | 19-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 40038.04 | 24-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 42565.05 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 62516.05 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 63475.64 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 68066.67 | 28-JUN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 72924.54 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 72254.50 | 03-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 64982.70 | 06-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 69769.47 | 06-OCT-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 56137.86 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46775.33 | 14-DEC-13:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 39517.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 72924.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 102683.77 | 10-JAN-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3046.45 | 6.85 | 71325.72 | 0.00 | 0.00 |
February | 122368.03 | 06-FEB-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3437.76 | 6.85 | 90588.55 | 30.12 | 0.00 |
March | 101642.63 | 30-MAR-12:00 | 13903.46 | 38626.93 | 0.00 | 823.79 | 5716.55 | 6.85 | 0.00 | 42565.05 | 0.00 |
April | 125296.40 | 28-APR-15:00 | 13903.46 | 38454.47 | 0.00 | 823.69 | 9591.88 | 6.85 | 0.00 | 62516.05 | 0.00 |
May | 127067.02 | 30-MAY-12:00 | 13903.46 | 38626.93 | 0.00 | 823.79 | 10230.35 | 6.85 | 0.00 | 63475.64 | 0.00 |
June | 130948.35 | 28-JUN-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 10576.45 | 6.85 | 0.00 | 67183.43 | 0.00 |
July | 137084.16 | 21-JUL-15:50 | 13903.46 | 38454.47 | 0.00 | 823.69 | 11174.17 | 6.85 | 0.00 | 72721.52 | 0.00 |
August | 138107.69 | 03-AUG-15:39 | 13903.46 | 38454.47 | 0.00 | 823.69 | 12675.78 | 6.85 | 0.00 | 72243.43 | 0.00 |
September | 129948.94 | 06-SEP-15:00 | 13903.46 | 38454.47 | 0.00 | 823.69 | 11777.76 | 6.85 | 0.00 | 64982.70 | 0.00 |
October | 134065.18 | 06-OCT-12:09 | 13903.46 | 38626.93 | 0.00 | 823.79 | 10934.68 | 6.85 | 0.00 | 69769.47 | 0.00 |
November | 119002.76 | 02-NOV-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 10021.73 | 6.85 | 0.00 | 55792.56 | 0.00 |
December | 107471.39 | 15-DEC-13:00 | 13903.46 | 38626.93 | 0.00 | 823.79 | 7904.84 | 6.85 | 0.00 | 46205.52 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 101642.63 | 5890.77 | 18346.02 | 0.00 | 243.23 | 3046.45 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 138107.69 | 13903.46 | 38626.93 | 3824.74 | 823.79 | 12675.78 | 6.85 | 90588.55 | 72721.52 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 23266.78 | 05-JAN-07:00 | 0.00 | 9719.79 | 23-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 20228.85 | 17-FEB-07:19 | 0.00 | 9711.84 | 06-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 20197.58 | 09-MAR-07:19 | 0.00 | 9667.27 | 02-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 9581.38 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 9493.58 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9397.34 | 02-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9337.54 | 07-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9371.52 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 9435.30 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 9533.91 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 800.09 | 15-NOV-07:19 | 0.00 | 9626.62 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 22096.25 | 21-DEC-07:19 | 0.00 | 9693.54 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9337.54 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 23266.78 | 0.00 | 9719.79 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
February | 0.17 | 18.90 | 0.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.44 | 2.50 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.45 | 2.00 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.42 | 5.67 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.37 | 3.33 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.50 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.37 | 1.50 | 27.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.15 | 0.33 | 19.15 | 20.33 | 27.17 | 16.50 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.39 | 0.17 | 19.39 | 7.00 | 27.59 | 5.67 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.17 | 18.92 | 0.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.67 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.71 | 2.00 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.85 | 8.83 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.69 | 7.83 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.72 | 13.83 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.66 | 8.00 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.75 | 11.67 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.64 | 7.67 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.37 | 0.33 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.14 | 0.33 | 19.14 | 66.67 | 27.63 | 60.83 | 27.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.36 | 0.17 | 19.36 | 15.50 | 27.85 | 13.83 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.93 | 3.67 | 27.93 |
February | 0.17 | 19.31 | 0.17 | 19.31 | 1.50 | 26.30 | 1.50 | 27.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.53 | 1.67 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.45 | 0.83 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.49 | 4.00 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.41 | 2.17 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.42 | 6.50 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.54 | 5.00 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.84 | 8.33 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.01 | 9.00 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.77 | 6.33 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.91 | 4.33 | 27.91 |
Annual Sum or Average | 0.17 | 19.31 | 0.17 | 19.31 | 57.33 | 27.68 | 53.33 | 27.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.30 | 0.83 | 27.00 |
Maximum of Months | 0.17 | 19.31 | 0.17 | 19.31 | 10.00 | 28.01 | 9.00 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.38 | 0.17 | 19.38 | 0.67 | 24.95 | 0.67 | 26.07 |
February | 0.17 | 18.97 | 0.17 | 18.97 | 0.67 | 24.91 | 0.67 | 26.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.55 | 1.50 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.80 | 2.33 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.06 | 3.83 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.98 | 3.83 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.72 | 8.00 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.75 | 4.33 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.96 | 6.17 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.97 | 4.83 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.64 | 1.00 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.63 | 0.67 | 27.63 |
Annual Sum or Average | 0.33 | 19.18 | 0.33 | 19.18 | 56.83 | 27.76 | 37.83 | 27.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.91 | 0.67 | 26.07 |
Maximum of Months | 0.17 | 19.38 | 0.17 | 19.38 | 12.67 | 28.06 | 8.00 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.63 | 5.33 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.59 | 2.17 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.59 | 6.33 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.48 | 5.33 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.60 | 8.67 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.52 | 5.50 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.50 | 27.57 | 34.17 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.63 | 8.67 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.67 | 18.16 | 18.67 | 18.16 | 3.67 | 19.02 | 3.67 | 19.75 |
February | 10.33 | 18.44 | 10.33 | 18.44 | 1.67 | 19.07 | 1.67 | 19.62 |
March | 15.83 | 18.62 | 15.83 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
April | 2.67 | 19.61 | 2.67 | 19.61 | 2.50 | 21.30 | 2.50 | 22.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 24.93 | 25.83 | 24.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 24.99 | 31.50 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 25.37 | 26.50 | 25.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 25.40 | 32.50 | 25.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 25.95 | 19.50 | 25.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 | 25.63 | 48.67 | 25.62 |
November | 4.50 | 19.68 | 4.50 | 19.68 | 19.33 | 23.90 | 19.33 | 24.70 |
December | 18.67 | 18.82 | 18.67 | 18.82 | 5.50 | 19.89 | 5.50 | 20.71 |
Annual Sum or Average | 70.67 | 18.63 | 70.67 | 18.63 | 218.17 | 22.81 | 217.17 | 23.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 0.00 | 18.62 |
Maximum of Months | 18.67 | 19.68 | 18.67 | 19.68 | 49.50 | 25.95 | 48.67 | 25.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.52 | 0.50 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.52 | 1.33 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.77 | 1.83 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.73 | 2.33 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.45 | 4.33 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.50 | 3.17 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.82 | 3.83 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.73 | 4.00 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.83 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
Annual Sum or Average | 0.00 | 0.00 | 32.17 | 27.63 | 23.00 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.82 | 4.33 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.41 | 0.83 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.82 | 1.33 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.75 | 9.00 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.59 | 6.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.64 | 10.67 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.54 | 6.33 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.71 | 9.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.63 | 5.67 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.48 | 0.33 | 27.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
Annual Sum or Average | 0.00 | 0.00 | 50.00 | 27.65 | 49.33 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.82 | 10.67 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.86 | 3.83 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.67 | 1.83 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 1.00 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.38 | 2.17 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.71 | 7.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.85 | 9.17 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.99 | 9.67 | 26.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.82 | 4.83 | 27.82 |
Annual Sum or Average | 0.00 | 0.00 | 41.17 | 27.57 | 40.17 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.86 | 9.67 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.58 | 0.67 | 27.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.69 | 0.67 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.50 | 0.83 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.67 | 2.33 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.85 | 3.50 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.83 | 3.33 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.61 | 5.83 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.62 | 3.33 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.91 | 4.50 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.87 | 4.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 1.17 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.52 | 0.50 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 43.67 | 27.75 | 30.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.50 | 27.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.91 | 5.83 | 27.94 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 301.17 | 23.62 | 76.33 | 23.79 | 0.00 | 23.79 |
February | 193.50 | 23.61 | 122.33 | 23.90 | 0.00 | 23.90 |
March | 205.00 | 23.56 | 142.33 | 23.91 | 0.00 | 23.91 |
April | 21.83 | 23.83 | 286.17 | 24.45 | 0.00 | 24.45 |
May | 0.00 | 0.00 | 492.83 | 24.32 | 0.00 | 24.32 |
June | 0.00 | 0.00 | 487.50 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 486.83 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 513.00 | 24.29 | 0.00 | 24.29 |
September | 0.00 | 0.00 | 482.17 | 24.30 | 0.00 | 24.30 |
October | 10.50 | 23.83 | 423.00 | 24.39 | 0.00 | 24.39 |
November | 55.83 | 23.80 | 227.33 | 24.32 | 0.00 | 24.32 |
December | 179.17 | 23.58 | 137.83 | 23.97 | 0.00 | 23.97 |
Annual Sum or Average | 967.00 | 23.62 | 3877.67 | 24.20 | 0.00 | 24.20 |
Minimum of Months | 0.00 | 0.00 | 76.33 | 23.79 | 0.00 | 23.79 |
Maximum of Months | 301.17 | 23.83 | 513.00 | 24.45 | 0.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.67 | 22.71 | 50.83 | 22.89 | 0.00 | 22.89 |
February | 317.33 | 22.84 | 75.83 | 23.09 | 0.83 | 23.09 |
March | 315.83 | 22.97 | 99.33 | 23.28 | 0.00 | 23.28 |
April | 106.67 | 23.43 | 191.33 | 24.04 | 0.00 | 24.04 |
May | 0.00 | 0.00 | 449.00 | 24.28 | 0.00 | 24.28 |
June | 0.00 | 0.00 | 442.83 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 442.33 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 468.67 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 394.50 | 24.30 | 0.00 | 24.30 |
October | 45.50 | 23.52 | 356.67 | 24.25 | 0.00 | 24.25 |
November | 204.17 | 23.39 | 120.83 | 23.74 | 0.00 | 23.74 |
December | 329.50 | 22.86 | 73.50 | 23.13 | 0.00 | 23.13 |
Annual Sum or Average | 1724.67 | 22.96 | 3165.67 | 23.82 | 0.83 | 23.82 |
Minimum of Months | 0.00 | 0.00 | 50.83 | 22.89 | 0.00 | 22.89 |
Maximum of Months | 405.67 | 23.52 | 468.67 | 24.30 | 0.83 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.50 | 22.07 | 54.83 | 22.19 | 16.83 | 22.13 |
February | 346.83 | 22.35 | 75.83 | 22.46 | 21.83 | 22.36 |
March | 351.00 | 22.63 | 88.67 | 22.85 | 10.00 | 22.79 |
April | 147.00 | 23.30 | 198.50 | 23.88 | 0.00 | 23.88 |
May | 0.00 | 0.00 | 457.17 | 24.31 | 0.00 | 24.31 |
June | 0.00 | 0.00 | 462.50 | 24.29 | 0.00 | 24.29 |
July | 0.83 | 23.46 | 468.67 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 483.17 | 24.29 | 0.00 | 24.29 |
September | 1.00 | 23.44 | 401.83 | 24.31 | 0.00 | 24.31 |
October | 68.50 | 23.20 | 345.67 | 24.15 | 0.00 | 24.15 |
November | 280.83 | 23.01 | 89.33 | 23.28 | 0.00 | 23.28 |
December | 381.33 | 22.34 | 68.00 | 22.52 | 11.17 | 22.47 |
Annual Sum or Average | 2001.83 | 22.53 | 3194.17 | 23.57 | 59.83 | 23.54 |
Minimum of Months | 0.00 | 0.00 | 54.83 | 22.19 | 0.00 | 22.13 |
Maximum of Months | 424.50 | 23.46 | 483.17 | 24.35 | 21.83 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.00 | 21.46 | 151.33 | 21.45 | 111.67 | 21.29 |
February | 365.50 | 21.74 | 122.17 | 21.75 | 67.00 | 21.52 |
March | 365.17 | 22.10 | 134.00 | 22.28 | 46.83 | 22.11 |
April | 176.00 | 23.09 | 225.33 | 23.75 | 11.50 | 23.80 |
May | 39.83 | 25.89 | 504.33 | 24.52 | 39.83 | 24.62 |
June | 25.17 | 26.02 | 491.17 | 24.49 | 24.00 | 24.56 |
July | 57.33 | 26.29 | 489.50 | 24.73 | 57.33 | 24.87 |
August | 53.00 | 25.74 | 508.33 | 24.52 | 53.00 | 24.62 |
September | 52.00 | 25.50 | 447.17 | 24.53 | 49.83 | 24.62 |
October | 127.33 | 23.70 | 374.33 | 24.21 | 43.00 | 24.30 |
November | 307.00 | 22.38 | 123.50 | 22.78 | 13.17 | 22.73 |
December | 397.67 | 21.72 | 136.83 | 21.84 | 74.17 | 21.69 |
Annual Sum or Average | 2410.00 | 22.41 | 3708.00 | 23.40 | 591.33 | 23.36 |
Minimum of Months | 25.17 | 21.46 | 122.17 | 21.45 | 11.50 | 21.29 |
Maximum of Months | 444.00 | 26.29 | 508.33 | 24.73 | 111.67 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.83 | 21.95 | 131.83 | 22.04 | 69.00 | 21.86 |
February | 301.17 | 22.08 | 137.17 | 22.33 | 42.17 | 22.12 |
March | 267.67 | 22.23 | 192.50 | 22.82 | 36.33 | 22.67 |
April | 117.33 | 23.39 | 300.50 | 24.12 | 18.17 | 24.20 |
May | 62.67 | 26.42 | 507.17 | 24.71 | 62.67 | 24.88 |
June | 45.17 | 26.52 | 492.67 | 24.64 | 44.50 | 24.78 |
July | 76.00 | 26.62 | 491.67 | 24.88 | 76.00 | 25.08 |
August | 65.33 | 26.10 | 510.00 | 24.63 | 65.33 | 24.78 |
September | 75.67 | 26.21 | 464.33 | 24.73 | 74.83 | 24.92 |
October | 123.83 | 24.48 | 396.00 | 24.50 | 61.00 | 24.67 |
November | 230.17 | 22.77 | 175.50 | 23.40 | 10.50 | 23.38 |
December | 350.83 | 22.03 | 146.00 | 22.33 | 51.67 | 22.18 |
Annual Sum or Average | 2124.67 | 23.01 | 3945.33 | 23.82 | 612.17 | 23.87 |
Minimum of Months | 45.17 | 21.95 | 131.83 | 22.04 | 10.50 | 21.86 |
Maximum of Months | 408.83 | 26.62 | 510.00 | 24.88 | 76.00 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 289.17 | 22.12 | 165.67 | 22.64 | 60.83 | 22.53 |
February | 241.00 | 22.24 | 175.67 | 22.86 | 36.33 | 22.72 |
March | 275.33 | 22.26 | 189.67 | 22.79 | 40.67 | 22.64 |
April | 147.83 | 23.16 | 260.33 | 23.94 | 14.17 | 24.01 |
May | 43.50 | 25.93 | 500.17 | 24.53 | 43.50 | 24.64 |
June | 26.33 | 25.87 | 488.33 | 24.47 | 24.33 | 24.54 |
July | 59.50 | 26.27 | 487.67 | 24.72 | 59.50 | 24.87 |
August | 57.17 | 25.86 | 508.00 | 24.55 | 57.17 | 24.67 |
September | 70.33 | 26.02 | 455.50 | 24.68 | 69.00 | 24.84 |
October | 109.83 | 24.85 | 414.67 | 24.61 | 66.17 | 24.79 |
November | 184.00 | 23.10 | 249.67 | 23.95 | 22.50 | 24.05 |
December | 259.83 | 22.30 | 219.00 | 23.09 | 52.50 | 23.03 |
Annual Sum or Average | 1763.83 | 23.11 | 4114.33 | 23.96 | 546.67 | 24.01 |
Minimum of Months | 26.33 | 22.12 | 165.67 | 22.64 | 14.17 | 22.53 |
Maximum of Months | 289.17 | 26.27 | 508.00 | 24.72 | 69.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 382.17 | 21.71 | 152.17 | 21.85 | 89.00 | 21.68 |
February | 304.83 | 21.92 | 149.17 | 22.19 | 55.83 | 21.97 |
March | 303.50 | 22.18 | 175.00 | 22.60 | 46.33 | 22.44 |
April | 150.17 | 23.42 | 278.50 | 24.06 | 23.00 | 24.18 |
May | 50.50 | 26.08 | 502.83 | 24.61 | 50.50 | 24.73 |
June | 36.50 | 26.30 | 491.00 | 24.58 | 35.00 | 24.70 |
July | 69.33 | 26.41 | 491.17 | 24.81 | 69.33 | 24.98 |
August | 58.67 | 25.91 | 511.50 | 24.59 | 58.67 | 24.71 |
September | 66.33 | 25.91 | 460.00 | 24.65 | 65.00 | 24.80 |
October | 112.33 | 24.27 | 398.00 | 24.42 | 55.83 | 24.57 |
November | 255.33 | 22.57 | 177.33 | 23.24 | 16.00 | 23.24 |
December | 334.33 | 21.83 | 169.00 | 22.24 | 62.67 | 22.09 |
Annual Sum or Average | 2124.00 | 22.77 | 3955.67 | 23.70 | 627.17 | 23.71 |
Minimum of Months | 36.50 | 21.71 | 149.17 | 21.85 | 16.00 | 21.68 |
Maximum of Months | 382.17 | 26.41 | 511.50 | 24.81 | 89.00 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.50 | 21.91 | 49.83 | 22.00 | 17.33 | 21.95 |
February | 382.67 | 22.11 | 69.17 | 22.16 | 28.67 | 22.05 |
March | 413.00 | 22.36 | 70.17 | 22.48 | 15.17 | 22.42 |
April | 227.83 | 23.21 | 170.00 | 23.63 | 11.33 | 23.67 |
May | 17.83 | 25.81 | 489.83 | 24.36 | 17.83 | 24.41 |
June | 4.50 | 25.63 | 487.50 | 24.33 | 4.50 | 24.35 |
July | 17.17 | 25.86 | 492.67 | 24.49 | 17.17 | 24.54 |
August | 15.33 | 25.68 | 513.67 | 24.42 | 15.33 | 24.45 |
September | 15.00 | 25.50 | 481.17 | 24.42 | 15.00 | 24.45 |
October | 69.50 | 24.00 | 395.50 | 24.33 | 20.00 | 24.39 |
November | 257.83 | 23.03 | 151.33 | 23.44 | 0.67 | 23.45 |
December | 366.83 | 22.26 | 80.83 | 22.53 | 11.67 | 22.52 |
Annual Sum or Average | 2224.00 | 22.53 | 3451.67 | 23.58 | 174.67 | 23.58 |
Minimum of Months | 4.50 | 21.91 | 49.83 | 22.00 | 0.67 | 21.95 |
Maximum of Months | 436.50 | 25.86 | 513.67 | 24.49 | 28.67 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 365.67 | 22.58 | 83.00 | 22.88 | 5.50 | 22.86 |
February | 283.67 | 22.60 | 101.83 | 22.93 | 8.00 | 22.87 |
March | 273.50 | 22.65 | 148.17 | 23.19 | 6.67 | 23.15 |
April | 113.33 | 23.53 | 286.17 | 24.14 | 14.50 | 24.20 |
May | 36.67 | 26.56 | 506.50 | 24.61 | 36.67 | 24.73 |
June | 16.00 | 26.70 | 492.83 | 24.51 | 16.00 | 24.57 |
July | 44.33 | 26.73 | 495.17 | 24.76 | 44.33 | 24.91 |
August | 34.00 | 26.57 | 514.00 | 24.60 | 34.00 | 24.72 |
September | 49.50 | 26.62 | 484.67 | 24.72 | 49.50 | 24.88 |
October | 65.50 | 25.37 | 422.67 | 24.66 | 41.17 | 24.80 |
November | 136.83 | 23.39 | 234.50 | 24.03 | 1.50 | 24.04 |
December | 283.00 | 22.61 | 134.17 | 23.13 | 7.17 | 23.14 |
Annual Sum or Average | 1702.00 | 23.27 | 3903.67 | 24.09 | 265.00 | 24.17 |
Minimum of Months | 16.00 | 22.58 | 83.00 | 22.88 | 1.50 | 22.86 |
Maximum of Months | 365.67 | 26.73 | 514.00 | 24.76 | 49.50 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 286.17 | 22.23 | 162.00 | 22.90 | 42.33 | 22.84 |
February | 233.17 | 22.26 | 178.17 | 23.04 | 25.67 | 22.94 |
March | 313.00 | 22.09 | 173.50 | 22.65 | 46.00 | 22.55 |
April | 207.50 | 23.11 | 247.17 | 23.73 | 52.17 | 23.76 |
May | 129.50 | 24.34 | 504.00 | 24.36 | 129.50 | 24.35 |
June | 119.33 | 24.25 | 492.67 | 24.34 | 119.33 | 24.33 |
July | 154.17 | 24.47 | 495.00 | 24.51 | 154.17 | 24.50 |
August | 147.00 | 24.57 | 514.00 | 24.52 | 147.00 | 24.53 |
September | 149.67 | 24.82 | 484.83 | 24.60 | 149.67 | 24.64 |
October | 139.67 | 24.95 | 445.17 | 24.79 | 110.50 | 24.90 |
November | 135.33 | 23.53 | 325.83 | 24.31 | 50.67 | 24.38 |
December | 252.67 | 22.53 | 253.33 | 23.44 | 64.00 | 23.45 |
Annual Sum or Average | 2267.17 | 23.27 | 4275.67 | 24.02 | 1091.00 | 24.06 |
Minimum of Months | 119.33 | 22.09 | 162.00 | 22.65 | 25.67 | 22.55 |
Maximum of Months | 313.00 | 24.95 | 514.00 | 24.79 | 154.17 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 347.17 | 22.35 | 89.50 | 22.74 | 6.00 | 22.72 |
February | 278.50 | 22.43 | 119.00 | 22.82 | 16.50 | 22.73 |
March | 285.00 | 22.53 | 135.00 | 23.00 | 10.67 | 22.93 |
April | 125.67 | 23.60 | 268.00 | 24.15 | 15.17 | 24.22 |
May | 24.67 | 26.16 | 505.33 | 24.48 | 24.67 | 24.56 |
June | 15.83 | 26.57 | 492.00 | 24.48 | 15.83 | 24.55 |
July | 34.67 | 26.45 | 494.00 | 24.67 | 34.67 | 24.78 |
August | 27.33 | 26.36 | 514.00 | 24.56 | 27.33 | 24.65 |
September | 36.83 | 26.43 | 484.50 | 24.64 | 36.83 | 24.76 |
October | 63.00 | 25.20 | 431.83 | 24.61 | 37.33 | 24.73 |
November | 159.83 | 23.33 | 224.33 | 23.93 | 1.83 | 23.94 |
December | 285.33 | 22.60 | 151.50 | 23.19 | 6.67 | 23.20 |
Annual Sum or Average | 1683.83 | 23.06 | 3909.00 | 24.01 | 233.50 | 24.06 |
Minimum of Months | 15.83 | 22.35 | 89.50 | 22.74 | 1.83 | 22.72 |
Maximum of Months | 347.17 | 26.57 | 514.00 | 24.67 | 37.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.50 | 21.76 | 91.00 | 21.88 | 43.00 | 21.79 |
February | 348.00 | 22.06 | 90.67 | 22.16 | 33.17 | 22.01 |
March | 344.00 | 22.37 | 105.83 | 22.62 | 18.00 | 22.53 |
April | 149.50 | 23.38 | 236.83 | 23.92 | 11.33 | 23.97 |
May | 24.83 | 25.65 | 507.67 | 24.45 | 24.83 | 24.50 |
June | 10.50 | 25.88 | 493.67 | 24.42 | 10.50 | 24.45 |
July | 32.67 | 26.03 | 492.00 | 24.59 | 32.67 | 24.68 |
August | 29.33 | 25.44 | 510.00 | 24.43 | 29.33 | 24.48 |
September | 37.83 | 25.46 | 462.67 | 24.47 | 37.83 | 24.54 |
October | 102.17 | 23.90 | 383.83 | 24.28 | 35.17 | 24.36 |
November | 272.00 | 22.77 | 126.67 | 23.20 | 1.17 | 23.20 |
December | 379.00 | 22.08 | 95.50 | 22.30 | 28.17 | 22.23 |
Annual Sum or Average | 2158.33 | 22.54 | 3596.33 | 23.60 | 305.17 | 23.60 |
Minimum of Months | 10.50 | 21.76 | 90.67 | 21.88 | 1.17 | 21.79 |
Maximum of Months | 428.50 | 26.03 | 510.00 | 24.59 | 43.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 329.50 | 22.20 | 82.67 | 22.43 | 27.50 | 22.33 |
February | 247.17 | 22.37 | 98.50 | 22.70 | 18.67 | 22.58 |
March | 227.00 | 22.52 | 139.50 | 23.14 | 13.33 | 23.07 |
April | 91.67 | 23.70 | 252.83 | 24.29 | 16.33 | 24.37 |
May | 55.33 | 26.48 | 430.00 | 24.80 | 55.33 | 24.97 |
June | 33.83 | 26.62 | 417.00 | 24.69 | 33.83 | 24.83 |
July | 67.00 | 26.62 | 420.50 | 24.96 | 67.00 | 25.16 |
August | 53.83 | 26.23 | 431.50 | 24.71 | 53.83 | 24.86 |
September | 65.00 | 26.33 | 400.50 | 24.83 | 65.00 | 25.02 |
October | 94.67 | 24.78 | 339.50 | 24.65 | 52.00 | 24.81 |
November | 183.50 | 23.08 | 162.17 | 23.75 | 4.17 | 23.78 |
December | 280.00 | 22.33 | 108.67 | 22.73 | 22.50 | 22.67 |
Annual Sum or Average | 1728.50 | 23.28 | 3283.33 | 24.06 | 429.50 | 24.16 |
Minimum of Months | 33.83 | 22.20 | 82.67 | 22.43 | 4.17 | 22.33 |
Maximum of Months | 329.50 | 26.62 | 431.50 | 24.96 | 67.00 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.67 | 22.45 | 153.50 | 23.15 | 31.50 | 23.14 |
February | 204.00 | 22.56 | 174.50 | 23.30 | 18.83 | 23.25 |
March | 239.50 | 22.49 | 173.33 | 23.14 | 14.17 | 23.06 |
April | 116.33 | 23.42 | 279.17 | 24.10 | 11.50 | 24.14 |
May | 27.17 | 25.72 | 506.83 | 24.46 | 27.17 | 24.52 |
June | 10.50 | 25.73 | 492.67 | 24.40 | 10.50 | 24.42 |
July | 34.33 | 25.99 | 490.17 | 24.59 | 34.33 | 24.68 |
August | 41.17 | 25.82 | 510.83 | 24.50 | 41.17 | 24.59 |
September | 63.83 | 26.14 | 471.50 | 24.67 | 63.83 | 24.83 |
October | 93.83 | 25.27 | 425.17 | 24.70 | 62.83 | 24.87 |
November | 149.17 | 23.57 | 278.83 | 24.25 | 19.67 | 24.37 |
December | 230.67 | 22.73 | 216.00 | 23.58 | 30.00 | 23.64 |
Annual Sum or Average | 1462.17 | 23.31 | 4172.50 | 24.13 | 365.50 | 24.20 |
Minimum of Months | 10.50 | 22.45 | 153.50 | 23.14 | 10.50 | 23.06 |
Maximum of Months | 251.67 | 26.14 | 510.83 | 24.70 | 63.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 358.33 | 22.02 | 112.17 | 22.32 | 36.83 | 22.23 |
February | 275.83 | 22.24 | 133.17 | 22.66 | 25.67 | 22.54 |
March | 272.50 | 22.45 | 157.83 | 22.96 | 19.17 | 22.88 |
April | 115.17 | 23.76 | 298.67 | 24.23 | 20.33 | 24.33 |
May | 41.00 | 26.11 | 507.67 | 24.57 | 41.00 | 24.68 |
June | 27.50 | 26.46 | 493.33 | 24.55 | 27.50 | 24.64 |
July | 57.50 | 26.35 | 494.33 | 24.74 | 57.50 | 24.90 |
August | 45.67 | 25.95 | 512.67 | 24.55 | 45.67 | 24.66 |
September | 58.67 | 26.02 | 475.33 | 24.63 | 58.67 | 24.77 |
October | 92.33 | 24.63 | 410.17 | 24.50 | 50.67 | 24.63 |
November | 213.17 | 22.96 | 195.00 | 23.63 | 5.33 | 23.66 |
December | 307.50 | 22.20 | 147.33 | 22.75 | 24.17 | 22.69 |
Annual Sum or Average | 1865.17 | 23.00 | 3937.67 | 23.91 | 412.50 | 23.98 |
Minimum of Months | 27.50 | 22.02 | 112.17 | 22.32 | 5.33 | 22.23 |
Maximum of Months | 358.33 | 26.46 | 512.67 | 24.74 | 58.67 | 24.90 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87817 | 35.94329 | 0.27312 | 6.99435 |
February | 454.00000 | 23.94166 | 40.03854 | 0.31881 | 7.61119 |
March | 514.00000 | 23.97013 | 39.38644 | 0.33085 | 7.75501 |
April | 485.00000 | 24.28668 | 43.76293 | 0.45548 | 9.57523 |
May | 508.00000 | 24.31181 | 47.53393 | -0.3474 | 7.85604 |
June | 496.00000 | 24.28366 | 47.46235 | -0.3529 | 7.89048 |
July | 497.00000 | 24.31226 | 47.11142 | -0.3452 | 7.80539 |
August | 514.00000 | 24.29211 | 47.63415 | -0.3445 | 7.78188 |
September | 485.00000 | 24.29643 | 47.32398 | -0.3498 | 7.83066 |
October | 502.00000 | 24.33952 | 44.58979 | 0.50053 | 10.49281 |
November | 489.00000 | 24.22232 | 40.48074 | 0.42046 | 8.94409 |
December | 497.00000 | 24.00226 | 38.50867 | 0.33355 | 7.83519 |
Annual Sum or Average | 5943.00000 | 24.17912 | 43.33631 | 0.07162 | 8.19677 |
Minimum of Months | 454.00000 | 23.87817 | 35.94329 | -0.3529 | 6.99435 |
Maximum of Months | 514.00000 | 24.33952 | 47.63415 | 0.50053 | 10.49281 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.98570 | 38.27384 | 0.07208 | 6.19914 |
February | 454.00000 | 23.20523 | 41.89234 | 0.15350 | 6.75802 |
March | 514.00000 | 23.40053 | 41.20122 | 0.20337 | 6.90739 |
April | 485.00000 | 24.00760 | 44.91247 | 0.39199 | 8.51260 |
May | 508.00000 | 24.22281 | 48.38939 | -0.3765 | 8.24825 |
June | 496.00000 | 24.21180 | 48.19732 | -0.3778 | 8.24683 |
July | 497.00000 | 24.24131 | 48.00844 | -0.3680 | 8.14714 |
August | 514.00000 | 24.21994 | 48.55168 | -0.3716 | 8.16604 |
September | 485.00000 | 24.19842 | 48.45528 | -0.3851 | 8.40992 |
October | 502.00000 | 24.18473 | 45.61591 | 0.46190 | 9.82280 |
November | 489.00000 | 23.82143 | 41.82299 | 0.32069 | 7.60690 |
December | 497.00000 | 23.28014 | 40.69995 | 0.16678 | 6.78149 |
Annual Sum or Average | 5943.00000 | 23.83521 | 44.68708 | -0.0113 | 7.82200 |
Minimum of Months | 454.00000 | 22.98570 | 38.27384 | -0.3851 | 6.19914 |
Maximum of Months | 514.00000 | 24.24131 | 48.55168 | 0.46190 | 9.82280 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.38235 | 39.25513 | -0.0773 | 7.02091 |
February | 454.00000 | 22.73589 | 42.47097 | 0.03821 | 7.23197 |
March | 514.00000 | 23.08901 | 41.54327 | 0.12584 | 7.03717 |
April | 485.00000 | 23.90682 | 44.53616 | 0.36839 | 8.32861 |
May | 508.00000 | 24.26588 | 47.89879 | -0.3493 | 7.85814 |
June | 496.00000 | 24.26633 | 47.69854 | -0.3434 | 7.75117 |
July | 497.00000 | 24.31800 | 47.53045 | -0.3283 | 7.63280 |
August | 514.00000 | 24.25972 | 48.21420 | -0.3453 | 7.78685 |
September | 485.00000 | 24.22037 | 48.09004 | -0.3713 | 8.24343 |
October | 502.00000 | 24.11659 | 45.39765 | 0.44736 | 9.78234 |
November | 489.00000 | 23.44886 | 42.15745 | 0.22767 | 6.98766 |
December | 497.00000 | 22.73420 | 41.48691 | 0.03092 | 7.00844 |
Annual Sum or Average | 5943.00000 | 23.65104 | 44.70541 | -0.0497 | 7.72433 |
Minimum of Months | 454.00000 | 22.38235 | 39.25513 | -0.3713 | 6.98766 |
Maximum of Months | 514.00000 | 24.31800 | 48.21420 | 0.44736 | 9.78234 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.75884 | 43.44799 | -0.2284 | 9.17507 |
February | 454.00000 | 22.17656 | 45.14008 | -0.0935 | 9.15753 |
March | 514.00000 | 22.67120 | 43.99066 | 0.03158 | 8.17490 |
April | 485.00000 | 23.74716 | 47.45578 | 0.35768 | 8.88481 |
May | 508.00000 | 24.40902 | 51.28019 | -0.2318 | 7.08001 |
June | 496.00000 | 24.40459 | 49.99583 | -0.2198 | 6.88489 |
July | 497.00000 | 24.53162 | 51.07212 | -0.1750 | 7.09996 |
August | 514.00000 | 24.38223 | 52.00017 | -0.2283 | 7.05144 |
September | 485.00000 | 24.35762 | 52.70330 | -0.2640 | 7.68234 |
October | 502.00000 | 24.08293 | 50.20841 | 0.48544 | 11.43201 |
November | 489.00000 | 23.00091 | 45.41555 | 0.13330 | 7.44557 |
December | 497.00000 | 22.16985 | 45.73983 | -0.0984 | 8.51233 |
Annual Sum or Average | 5943.00000 | 23.48301 | 48.22439 | -0.0449 | 8.20721 |
Minimum of Months | 454.00000 | 21.75884 | 43.44799 | -0.2640 | 6.88489 |
Maximum of Months | 514.00000 | 24.53162 | 52.70330 | 0.48544 | 11.43201 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.38330 | 42.78243 | -0.0628 | 8.47065 |
February | 454.00000 | 22.75535 | 44.15318 | 0.06307 | 8.74210 |
March | 514.00000 | 23.18057 | 42.63944 | 0.17634 | 9.00425 |
April | 485.00000 | 24.01882 | 46.22201 | 0.45896 | 10.72901 |
May | 508.00000 | 24.49356 | 50.48968 | -0.1437 | 7.05542 |
June | 496.00000 | 24.45763 | 49.48773 | -0.1449 | 6.71305 |
July | 497.00000 | 24.60171 | 50.36388 | -0.0962 | 7.18908 |
August | 514.00000 | 24.43904 | 51.40693 | -0.1578 | 6.86784 |
September | 485.00000 | 24.46151 | 51.86053 | -0.1839 | 7.72479 |
October | 502.00000 | 24.26282 | 49.22505 | 0.55965 | 13.30130 |
November | 489.00000 | 23.53345 | 44.14011 | 0.27725 | 8.50760 |
December | 497.00000 | 22.65525 | 45.13789 | 0.02980 | 8.57227 |
Annual Sum or Average | 5943.00000 | 23.77671 | 47.34759 | 0.06371 | 8.56709 |
Minimum of Months | 454.00000 | 22.38330 | 42.63944 | -0.1839 | 6.71305 |
Maximum of Months | 514.00000 | 24.60171 | 51.86053 | 0.55965 | 13.30130 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.04519 | 39.39636 | 0.12318 | 9.80491 |
February | 454.00000 | 23.18118 | 41.67382 | 0.18812 | 9.93693 |
March | 514.00000 | 23.15261 | 41.99734 | 0.17239 | 9.09475 |
April | 485.00000 | 23.89202 | 46.58974 | 0.41117 | 9.95312 |
May | 508.00000 | 24.40347 | 51.28021 | -0.2296 | 7.11652 |
June | 496.00000 | 24.38343 | 50.16718 | -0.2338 | 6.99932 |
July | 497.00000 | 24.51708 | 51.14917 | -0.1811 | 7.13897 |
August | 514.00000 | 24.39732 | 51.72882 | -0.2032 | 6.95343 |
September | 485.00000 | 24.43341 | 51.85854 | -0.1979 | 7.64481 |
October | 502.00000 | 24.34345 | 48.32520 | 0.60216 | 14.39654 |
November | 489.00000 | 23.85469 | 41.87981 | 0.39189 | 10.78900 |
December | 497.00000 | 23.26766 | 41.94592 | 0.21412 | 10.53317 |
Annual Sum or Average | 5943.00000 | 23.90997 | 46.53534 | 0.08626 | 9.18560 |
Minimum of Months | 454.00000 | 23.04519 | 39.39636 | -0.2338 | 6.95343 |
Maximum of Months | 514.00000 | 24.51708 | 51.85854 | 0.60216 | 14.39654 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.29840 | 42.63247 | -0.0833 | 9.18843 |
February | 454.00000 | 22.65310 | 44.15870 | 0.04078 | 9.64980 |
March | 514.00000 | 22.98141 | 43.35187 | 0.12756 | 8.98348 |
April | 485.00000 | 23.94271 | 46.89866 | 0.44004 | 10.68962 |
May | 508.00000 | 24.45199 | 51.29900 | -0.1792 | 7.00703 |
June | 496.00000 | 24.44632 | 50.02386 | -0.1666 | 6.89533 |
July | 497.00000 | 24.57263 | 51.05280 | -0.1283 | 7.15690 |
August | 514.00000 | 24.43310 | 51.86359 | -0.1674 | 6.83046 |
September | 485.00000 | 24.43286 | 52.46013 | -0.1976 | 7.63606 |
October | 502.00000 | 24.22205 | 49.71427 | 0.55118 | 13.06006 |
November | 489.00000 | 23.34061 | 44.57722 | 0.23538 | 8.62950 |
December | 497.00000 | 22.60511 | 44.98685 | 0.02403 | 9.06343 |
Annual Sum or Average | 5943.00000 | 23.70501 | 47.77681 | 0.04039 | 8.72069 |
Minimum of Months | 454.00000 | 22.29840 | 42.63247 | -0.1976 | 6.83046 |
Maximum of Months | 514.00000 | 24.57263 | 52.46013 | 0.55118 | 13.06006 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.17804 | 42.10619 | -0.1112 | 7.18426 |
February | 454.00000 | 22.39228 | 45.14935 | -0.0380 | 7.37263 |
March | 514.00000 | 22.68082 | 44.32128 | 0.03117 | 6.96580 |
April | 485.00000 | 23.65039 | 48.41385 | 0.31418 | 7.83038 |
May | 508.00000 | 24.29290 | 50.90651 | -0.3191 | 7.61478 |
June | 496.00000 | 24.31401 | 49.55150 | -0.2962 | 7.23206 |
July | 497.00000 | 24.44163 | 49.94405 | -0.2406 | 6.95870 |
August | 514.00000 | 24.37779 | 50.15075 | -0.2513 | 6.93125 |
September | 485.00000 | 24.37931 | 50.56115 | -0.2720 | 7.18588 |
October | 502.00000 | 24.24605 | 48.41244 | 0.51346 | 11.24171 |
November | 489.00000 | 23.52561 | 44.42851 | 0.26180 | 7.36297 |
December | 497.00000 | 22.70426 | 44.10322 | 0.04234 | 7.11455 |
Annual Sum or Average | 5943.00000 | 23.60585 | 47.35062 | -0.0316 | 7.58426 |
Minimum of Months | 454.00000 | 22.17804 | 42.10619 | -0.3191 | 6.93125 |
Maximum of Months | 514.00000 | 24.44163 | 50.90651 | 0.51346 | 11.24171 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.03059 | 40.88018 | 0.10163 | 7.13783 |
February | 454.00000 | 23.15909 | 43.71412 | 0.15897 | 7.48479 |
March | 514.00000 | 23.37708 | 42.58041 | 0.21685 | 8.08808 |
April | 485.00000 | 24.05356 | 46.66516 | 0.44502 | 9.96336 |
May | 508.00000 | 24.46493 | 49.95707 | -0.2019 | 7.04919 |
June | 496.00000 | 24.43027 | 48.92530 | -0.2004 | 6.71120 |
July | 497.00000 | 24.58228 | 49.19017 | -0.1384 | 6.80936 |
August | 514.00000 | 24.47050 | 49.56471 | -0.1663 | 6.61452 |
September | 485.00000 | 24.52251 | 49.74816 | -0.1762 | 7.10683 |
October | 502.00000 | 24.43600 | 47.45072 | 0.59386 | 13.40288 |
November | 489.00000 | 24.02512 | 42.94603 | 0.40289 | 9.19878 |
December | 497.00000 | 23.27560 | 43.22335 | 0.18879 | 7.76792 |
Annual Sum or Average | 5943.00000 | 23.99037 | 46.25385 | 0.10059 | 8.11014 |
Minimum of Months | 454.00000 | 23.03059 | 40.88018 | -0.2019 | 6.61452 |
Maximum of Months | 514.00000 | 24.58228 | 49.95707 | 0.59386 | 13.40288 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17063 | 39.49672 | 0.20790 | 9.58596 |
February | 454.00000 | 23.27218 | 44.09181 | 0.25099 | 9.47851 |
March | 514.00000 | 22.93486 | 44.53583 | 0.15158 | 8.78658 |
April | 485.00000 | 23.73246 | 51.11248 | 0.38319 | 9.31428 |
May | 508.00000 | 24.35710 | 58.13541 | -0.2457 | 6.78587 |
June | 496.00000 | 24.36206 | 57.72008 | -0.2356 | 6.57816 |
July | 497.00000 | 24.51838 | 58.63714 | -0.1603 | 6.29323 |
August | 514.00000 | 24.51143 | 58.33881 | -0.1314 | 6.16437 |
September | 485.00000 | 24.53022 | 57.61378 | -0.1243 | 6.46473 |
October | 502.00000 | 24.58528 | 51.15829 | 0.68699 | 16.29772 |
November | 489.00000 | 24.19091 | 44.11329 | 0.51694 | 12.31981 |
December | 497.00000 | 23.48511 | 42.60695 | 0.31802 | 10.98606 |
Annual Sum or Average | 5943.00000 | 23.97407 | 50.67945 | 0.13270 | 9.07902 |
Minimum of Months | 454.00000 | 22.93486 | 39.49672 | -0.2457 | 6.16437 |
Maximum of Months | 514.00000 | 24.58528 | 58.63714 | 0.68699 | 16.29772 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.92942 | 40.77828 | 0.07988 | 7.36323 |
February | 454.00000 | 23.09868 | 43.59598 | 0.14686 | 7.99352 |
March | 514.00000 | 23.25152 | 43.10894 | 0.18261 | 7.81505 |
April | 485.00000 | 24.04514 | 47.08802 | 0.43943 | 9.95238 |
May | 508.00000 | 24.39633 | 50.65735 | -0.2455 | 7.10858 |
June | 496.00000 | 24.41180 | 49.34845 | -0.2237 | 6.86584 |
July | 497.00000 | 24.54493 | 49.73620 | -0.1731 | 6.82188 |
August | 514.00000 | 24.46444 | 49.84943 | -0.1762 | 6.57641 |
September | 485.00000 | 24.50370 | 50.11263 | -0.1867 | 6.99500 |
October | 502.00000 | 24.42400 | 47.69358 | 0.59081 | 13.21906 |
November | 489.00000 | 23.94492 | 43.25260 | 0.38360 | 8.98075 |
December | 497.00000 | 23.29431 | 42.94352 | 0.19841 | 7.97615 |
Annual Sum or Average | 5943.00000 | 23.94702 | 46.53399 | 0.08308 | 8.13409 |
Minimum of Months | 454.00000 | 22.92942 | 40.77828 | -0.2455 | 6.57641 |
Maximum of Months | 514.00000 | 24.54493 | 50.65735 | 0.59081 | 13.21906 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.08538 | 42.64880 | -0.1317 | 7.75744 |
February | 454.00000 | 22.50104 | 44.69799 | -0.0060 | 7.94310 |
March | 514.00000 | 22.91323 | 43.63186 | 0.09543 | 7.48558 |
April | 485.00000 | 23.87952 | 47.50715 | 0.38607 | 8.87465 |
May | 508.00000 | 24.39219 | 51.19104 | -0.2551 | 7.10787 |
June | 496.00000 | 24.38241 | 49.95592 | -0.2481 | 6.94124 |
July | 497.00000 | 24.49331 | 50.98719 | -0.2075 | 7.01787 |
August | 514.00000 | 24.36914 | 51.66723 | -0.2516 | 7.07728 |
September | 485.00000 | 24.36192 | 52.45213 | -0.2748 | 7.50861 |
October | 502.00000 | 24.16670 | 49.83868 | 0.49911 | 11.23633 |
November | 489.00000 | 23.33440 | 44.89871 | 0.21666 | 7.25415 |
December | 497.00000 | 22.52293 | 44.95602 | -0.0008 | 7.51923 |
Annual Sum or Average | 5943.00000 | 23.62389 | 47.88962 | -0.0160 | 7.80718 |
Minimum of Months | 454.00000 | 22.08538 | 42.64880 | -0.2748 | 6.94124 |
Maximum of Months | 514.00000 | 24.49331 | 52.45213 | 0.49911 | 11.23633 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.67699 | 42.07665 | 0.01876 | 7.77573 |
February | 385.00000 | 23.00306 | 43.48951 | 0.12270 | 8.01193 |
March | 433.00000 | 23.33732 | 42.20755 | 0.21155 | 8.57447 |
April | 410.00000 | 24.14734 | 46.31553 | 0.47276 | 10.75421 |
May | 430.00000 | 24.58695 | 50.39728 | -0.1521 | 7.20909 |
June | 418.00000 | 24.53679 | 49.32189 | -0.1643 | 6.87618 |
July | 422.00000 | 24.69347 | 50.27382 | -0.1094 | 7.28694 |
August | 433.00000 | 24.52276 | 51.18682 | -0.1707 | 7.01970 |
September | 410.00000 | 24.57156 | 51.68482 | -0.1790 | 7.75589 |
October | 427.00000 | 24.39807 | 49.08161 | 0.57363 | 13.40416 |
November | 417.00000 | 23.76605 | 43.44306 | 0.32990 | 8.68106 |
December | 422.00000 | 22.94770 | 44.45091 | 0.10793 | 8.04753 |
Annual Sum or Average | 5034.00000 | 23.93706 | 47.01329 | 0.08764 | 8.44957 |
Minimum of Months | 385.00000 | 22.67699 | 42.07665 | -0.1790 | 6.87618 |
Maximum of Months | 433.00000 | 24.69347 | 51.68482 | 0.57363 | 13.40416 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.37751 | 38.47294 | 0.21571 | 9.25586 |
February | 454.00000 | 23.49392 | 41.18557 | 0.26979 | 9.41650 |
March | 514.00000 | 23.39359 | 41.57623 | 0.23383 | 8.59890 |
April | 485.00000 | 24.02378 | 46.59353 | 0.43813 | 9.92356 |
May | 508.00000 | 24.39480 | 51.17305 | -0.2508 | 7.12453 |
June | 496.00000 | 24.36340 | 50.12376 | -0.2613 | 7.05586 |
July | 497.00000 | 24.48280 | 51.05661 | -0.2123 | 7.05942 |
August | 514.00000 | 24.39293 | 51.37992 | -0.2248 | 6.95542 |
September | 485.00000 | 24.45575 | 51.54713 | -0.2054 | 7.42917 |
October | 502.00000 | 24.42707 | 47.93916 | 0.61366 | 14.27240 |
November | 489.00000 | 24.09847 | 41.53462 | 0.45505 | 11.06740 |
December | 497.00000 | 23.58012 | 41.18373 | 0.29969 | 10.22601 |
Annual Sum or Average | 5943.00000 | 24.04294 | 46.18307 | 0.11194 | 9.02222 |
Minimum of Months | 454.00000 | 23.37751 | 38.47294 | -0.2613 | 6.95542 |
Maximum of Months | 514.00000 | 24.48280 | 51.54713 | 0.61366 | 14.27240 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.63796 | 41.74125 | 0.01344 | 8.02702 |
February | 454.00000 | 22.98579 | 43.66802 | 0.12810 | 8.65988 |
March | 514.00000 | 23.23997 | 42.92196 | 0.19310 | 8.38141 |
April | 485.00000 | 24.08751 | 46.87717 | 0.46954 | 10.70428 |
May | 508.00000 | 24.44580 | 51.17024 | -0.2004 | 6.95840 |
June | 496.00000 | 24.43732 | 49.94150 | -0.1920 | 6.85874 |
July | 497.00000 | 24.55414 | 50.92750 | -0.1559 | 7.02155 |
August | 514.00000 | 24.42815 | 51.50565 | -0.1895 | 6.79207 |
September | 485.00000 | 24.45124 | 52.17128 | -0.2058 | 7.41518 |
October | 502.00000 | 24.30829 | 49.32146 | 0.56413 | 12.88798 |
November | 489.00000 | 23.65358 | 44.08135 | 0.31339 | 8.56317 |
December | 497.00000 | 22.95943 | 44.16211 | 0.11988 | 8.27777 |
Annual Sum or Average | 5943.00000 | 23.85420 | 47.39927 | 0.07002 | 8.37052 |
Minimum of Months | 454.00000 | 22.63796 | 41.74125 | -0.2058 | 6.79207 |
Maximum of Months | 514.00000 | 24.55414 | 52.17128 | 0.56413 | 12.88798 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.172513E+11 | 0.406437E+10 | 251.06 | 0.112843E+11 | 0.596705E+10 | 0.00 | 1.00 | 02-JAN-09:40 | 0.00 | 01-JAN-00:10 | 60232.28 | 19-JAN-13:05 | 44176.40 | 02-JAN-13:30 | 23906.04 | 19-JAN-13:05 | 13427.35 | 19-JAN-13:05 | 0.00 |
February | 0.233961E+11 | 0.548256E+10 | 289.41 | 0.146385E+11 | 0.875759E+10 | 0.00 | 1.00 | 01-FEB-13:10 | 0.00 | 01-FEB-00:10 | 59409.88 | 24-FEB-13:05 | 41460.93 | 27-FEB-15:20 | 20554.57 | 24-FEB-11:05 | 13945.89 | 24-FEB-13:05 | 0.00 |
March | 0.283449E+11 | 0.666782E+10 | 351.94 | 0.186125E+11 | 0.973246E+10 | 0.00 | 1.00 | 06-MAR-09:30 | 0.00 | 01-MAR-00:10 | 63577.62 | 28-MAR-12:00 | 41027.73 | 30-MAR-12:00 | 25521.75 | 07-MAR-13:00 | 15013.36 | 30-MAR-12:00 | 0.00 |
April | 0.453104E+11 | 0.106312E+11 | 392.27 | 0.308959E+11 | 0.144145E+11 | 0.00 | 1.00 | 04-APR-12:05 | 0.00 | 01-APR-00:10 | 78321.75 | 28-APR-16:00 | 52251.64 | 28-APR-15:10 | 28638.76 | 28-APR-17:00 | 20165.00 | 28-APR-16:00 | 0.00 |
May | 0.826496E+11 | 0.199364E+11 | 445.28 | 0.535791E+11 | 0.290705E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:10 | 118247.68 | 22-MAY-04:03 | 69344.30 | 30-MAY-04:02 | 60884.29 | 22-MAY-04:03 | 25835.64 | 22-MAY-04:03 | 0.00 |
June | 0.889550E+11 | 0.217056E+11 | 447.64 | 0.572780E+11 | 0.316770E+11 | 0.00 | 1.00 | 01-JUN-06:10 | 0.00 | 01-JUN-00:10 | 90698.68 | 05-JUN-12:03 | 68230.29 | 26-JUN-04:02 | 40787.53 | 29-JUN-17:00 | 23224.07 | 29-JUN-12:04 | 0.00 |
July | 0.944798E+11 | 0.229846E+11 | 457.05 | 0.577897E+11 | 0.366901E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 111457.95 | 03-JUL-04:02 | 73488.97 | 05-JUL-04:02 | 39815.64 | 03-JUL-04:02 | 25578.10 | 05-JUL-12:02 | 0.00 |
August | 0.100678E+12 | 0.243896E+11 | 469.25 | 0.629532E+11 | 0.377249E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 97258.07 | 22-AUG-06:03 | 73163.89 | 21-AUG-04:02 | 41856.28 | 09-AUG-17:00 | 24450.65 | 03-AUG-16:00 | 0.00 |
September | 0.854708E+11 | 0.200841E+11 | 445.50 | 0.527322E+11 | 0.327386E+11 | 0.00 | 1.00 | 01-SEP-04:23 | 0.00 | 01-SEP-00:10 | 116078.46 | 05-SEP-05:12 | 73048.46 | 11-SEP-04:02 | 50306.98 | 05-SEP-05:12 | 24945.60 | 05-SEP-05:12 | 0.00 |
October | 0.755860E+11 | 0.179255E+11 | 436.08 | 0.500219E+11 | 0.255641E+11 | 0.00 | 1.00 | 01-OCT-15:13 | 0.00 | 01-OCT-00:10 | 100196.38 | 11-OCT-06:03 | 73798.95 | 10-OCT-05:12 | 46028.97 | 24-OCT-12:03 | 24822.04 | 06-OCT-12:02 | 0.00 |
November | 0.399557E+11 | 0.931484E+10 | 384.89 | 0.274390E+11 | 0.125167E+11 | 0.00 | 1.00 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 83571.47 | 07-NOV-13:05 | 52141.06 | 06-NOV-16:10 | 33989.23 | 07-NOV-13:05 | 19650.32 | 07-NOV-13:05 | 0.00 |
December | 0.260660E+11 | 0.608948E+10 | 290.00 | 0.171019E+11 | 0.896412E+10 | 0.00 | 1.00 | 01-DEC-15:00 | 0.00 | 01-DEC-00:10 | 72001.73 | 14-DEC-13:05 | 47398.23 | 15-DEC-15:00 | 28609.56 | 14-DEC-13:05 | 16829.67 | 14-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.708144E+12 | 0.169276E+12 | 4660.37 | 0.454326E+12 | 0.253818E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.172513E+11 | 0.406437E+10 | 251.06 | 0.112843E+11 | 0.596705E+10 | 0.00 | 1.00 | 0.00 | 59409.88 | 41027.73 | 20554.57 | 13427.35 | 0.00 | ||||||
Maximum of Months | 0.100678E+12 | 0.243896E+11 | 469.25 | 0.629532E+11 | 0.377249E+11 | 0.00 | 1.00 | 0.00 | 118247.68 | 73798.95 | 60884.29 | 25835.64 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.157581E+11 | 0.372323E+10 | 248.74 | 0.102366E+11 | 0.552148E+10 | 0.00 | 1.00 | 01-JAN-15:22 | 0.00 | 01-JAN-00:10 | 58294.18 | 19-JAN-15:05 | 38543.03 | 02-JAN-13:30 | 20420.80 | 19-JAN-15:05 | 13036.98 | 19-JAN-15:05 | 0.00 |
February | 0.222399E+11 | 0.521430E+10 | 292.69 | 0.141164E+11 | 0.812345E+10 | 0.00 | 1.00 | 01-FEB-13:10 | 0.00 | 01-FEB-00:10 | 57315.93 | 27-FEB-15:05 | 42149.27 | 27-FEB-15:05 | 18449.80 | 24-FEB-11:05 | 13111.79 | 27-FEB-15:05 | 0.00 |
March | 0.271497E+11 | 0.637774E+10 | 356.53 | 0.181135E+11 | 0.903617E+10 | 0.00 | 1.00 | 06-MAR-09:30 | 0.00 | 01-MAR-00:10 | 58400.93 | 07-MAR-11:05 | 38165.86 | 28-MAR-12:05 | 22766.95 | 07-MAR-11:05 | 13653.86 | 28-MAR-12:05 | 0.00 |
April | 0.437791E+11 | 0.102705E+11 | 400.57 | 0.299329E+11 | 0.138462E+11 | 0.00 | 1.00 | 04-APR-12:05 | 0.00 | 01-APR-00:10 | 77918.75 | 28-APR-16:00 | 51716.59 | 28-APR-15:00 | 27688.78 | 28-APR-16:10 | 19990.22 | 28-APR-16:00 | 0.00 |
May | 0.791542E+11 | 0.190264E+11 | 451.36 | 0.510725E+11 | 0.280817E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:10 | 110531.21 | 22-MAY-04:03 | 68235.13 | 30-MAY-04:02 | 53203.61 | 22-MAY-04:03 | 24286.83 | 22-MAY-04:03 | 0.00 |
June | 0.842685E+11 | 0.204724E+11 | 452.78 | 0.538952E+11 | 0.303733E+11 | 0.00 | 1.00 | 01-JUN-07:05 | 0.00 | 01-JUN-00:10 | 94088.18 | 05-JUN-04:02 | 67440.17 | 05-JUN-04:02 | 33827.36 | 29-JUN-15:00 | 22002.73 | 28-JUN-14:05 | 0.00 |
July | 0.883302E+11 | 0.213560E+11 | 460.67 | 0.532670E+11 | 0.350631E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 105947.23 | 03-JUL-04:02 | 68209.67 | 05-JUL-04:02 | 41706.39 | 31-JUL-04:03 | 24049.82 | 03-JUL-04:02 | 0.00 |
August | 0.903044E+11 | 0.217415E+11 | 465.50 | 0.550549E+11 | 0.352495E+11 | 0.00 | 1.00 | 01-AUG-04:53 | 0.00 | 01-AUG-00:10 | 101565.10 | 11-AUG-05:03 | 68072.45 | 28-AUG-04:02 | 46706.72 | 16-AUG-05:03 | 22716.96 | 14-AUG-04:02 | 0.00 |
September | 0.764674E+11 | 0.178997E+11 | 440.08 | 0.457842E+11 | 0.306832E+11 | 0.00 | 1.00 | 01-SEP-06:05 | 0.00 | 01-SEP-00:10 | 112208.80 | 05-SEP-05:12 | 68470.42 | 11-SEP-04:02 | 55493.07 | 05-SEP-05:12 | 23811.13 | 05-SEP-05:12 | 0.00 |
October | 0.674918E+11 | 0.159646E+11 | 430.92 | 0.434930E+11 | 0.239989E+11 | 0.00 | 1.00 | 01-OCT-15:13 | 0.00 | 01-OCT-00:10 | 100328.10 | 07-OCT-05:03 | 67089.92 | 10-OCT-05:12 | 42631.72 | 14-OCT-05:03 | 22909.26 | 06-OCT-12:02 | 0.00 |
November | 0.352446E+11 | 0.825215E+10 | 383.86 | 0.236021E+11 | 0.116425E+11 | 0.00 | 1.00 | 01-NOV-07:20 | 0.00 | 01-NOV-00:10 | 75682.65 | 02-NOV-14:05 | 50068.78 | 06-NOV-15:05 | 28043.16 | 07-NOV-13:05 | 18337.11 | 02-NOV-14:05 | 0.00 |
December | 0.234341E+11 | 0.548724E+10 | 287.58 | 0.151613E+11 | 0.827283E+10 | 0.00 | 1.00 | 08-DEC-13:05 | 0.00 | 01-DEC-00:10 | 64764.63 | 14-DEC-13:05 | 46446.25 | 15-DEC-15:05 | 26959.27 | 12-DEC-15:10 | 15167.06 | 14-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.653622E+12 | 0.155786E+12 | 4671.28 | 0.413730E+12 | 0.239892E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.157581E+11 | 0.372323E+10 | 248.74 | 0.102366E+11 | 0.552148E+10 | 0.00 | 1.00 | 0.00 | 57315.93 | 38165.86 | 18449.80 | 13036.98 | 0.00 | ||||||
Maximum of Months | 0.903044E+11 | 0.217415E+11 | 465.50 | 0.550549E+11 | 0.352495E+11 | 0.00 | 1.00 | 0.00 | 112208.80 | 68470.42 | 55493.07 | 24286.83 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.162079E+11 | 0.386184E+10 | 246.64 | 0.105016E+11 | 0.570634E+10 | 0.00 | 1.00 | 01-JAN-14:31 | 0.00 | 01-JAN-00:10 | 61734.88 | 19-JAN-15:00 | 42809.75 | 01-JAN-14:31 | 20405.42 | 19-JAN-14:40 | 13795.74 | 19-JAN-15:00 | 0.00 |
February | 0.230850E+11 | 0.545479E+10 | 291.17 | 0.147525E+11 | 0.833253E+10 | 0.00 | 1.00 | 01-FEB-13:50 | 0.00 | 01-FEB-00:10 | 60951.92 | 27-FEB-15:30 | 46275.06 | 27-FEB-15:00 | 17471.95 | 24-FEB-12:10 | 13910.36 | 24-FEB-14:10 | 0.00 |
March | 0.284959E+11 | 0.674288E+10 | 356.72 | 0.190887E+11 | 0.940719E+10 | 0.00 | 1.00 | 06-MAR-10:00 | 0.00 | 01-MAR-00:10 | 60847.05 | 28-MAR-12:30 | 44394.34 | 29-MAR-15:00 | 22431.71 | 07-MAR-11:30 | 14633.58 | 30-MAR-13:00 | 0.00 |
April | 0.466727E+11 | 0.110373E+11 | 401.02 | 0.323422E+11 | 0.143305E+11 | 0.00 | 1.00 | 04-APR-12:50 | 0.00 | 01-APR-00:10 | 86847.48 | 28-APR-16:00 | 61357.21 | 28-APR-15:00 | 27044.13 | 28-APR-16:00 | 22360.83 | 28-APR-16:00 | 0.00 |
May | 0.850884E+11 | 0.205749E+11 | 455.17 | 0.564408E+11 | 0.286476E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 123704.36 | 22-MAY-04:03 | 75172.28 | 30-MAY-04:02 | 57270.41 | 22-MAY-04:03 | 27226.09 | 22-MAY-04:03 | 0.00 |
June | 0.909839E+11 | 0.222339E+11 | 456.23 | 0.602109E+11 | 0.307730E+11 | 0.00 | 1.00 | 01-JUN-07:20 | 0.00 | 01-JUN-00:10 | 104871.89 | 05-JUN-04:02 | 77831.21 | 05-JUN-04:02 | 33338.89 | 29-JUN-15:00 | 24226.56 | 28-JUN-14:00 | 0.00 |
July | 0.948385E+11 | 0.230702E+11 | 468.17 | 0.591900E+11 | 0.356485E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 114511.54 | 03-JUL-04:02 | 78960.94 | 24-JUL-04:02 | 45777.41 | 31-JUL-04:03 | 26266.22 | 03-JUL-04:02 | 0.00 |
August | 0.962854E+11 | 0.233051E+11 | 469.42 | 0.604703E+11 | 0.358152E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 111066.31 | 15-AUG-05:03 | 79058.29 | 28-AUG-04:02 | 53270.03 | 15-AUG-05:03 | 25324.16 | 03-AUG-15:40 | 0.00 |
September | 0.804827E+11 | 0.189511E+11 | 444.58 | 0.491180E+11 | 0.313647E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 125896.71 | 05-SEP-05:12 | 76160.45 | 11-SEP-04:02 | 64942.90 | 05-SEP-05:12 | 26715.75 | 05-SEP-05:12 | 0.00 |
October | 0.707392E+11 | 0.168214E+11 | 430.67 | 0.462082E+11 | 0.245310E+11 | 0.00 | 1.00 | 01-OCT-14:13 | 0.00 | 01-OCT-00:10 | 97729.18 | 07-OCT-05:03 | 67451.03 | 05-OCT-15:00 | 43638.18 | 14-OCT-05:03 | 24039.59 | 06-OCT-14:00 | 0.00 |
November | 0.360582E+11 | 0.852240E+10 | 381.94 | 0.238634E+11 | 0.121948E+11 | 0.00 | 1.00 | 01-NOV-09:00 | 0.00 | 01-NOV-00:10 | 80998.60 | 02-NOV-14:30 | 55822.76 | 02-NOV-15:00 | 27889.81 | 07-NOV-13:00 | 19658.58 | 02-NOV-14:40 | 0.00 |
December | 0.240391E+11 | 0.568317E+10 | 286.80 | 0.154314E+11 | 0.860770E+10 | 0.00 | 1.00 | 08-DEC-13:40 | 0.00 | 01-DEC-00:10 | 66569.26 | 15-DEC-14:50 | 51128.39 | 15-DEC-15:00 | 26911.11 | 12-DEC-15:00 | 16186.67 | 15-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.692977E+12 | 0.166259E+12 | 4688.52 | 0.447618E+12 | 0.245359E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.162079E+11 | 0.386184E+10 | 246.64 | 0.105016E+11 | 0.570634E+10 | 0.00 | 1.00 | 0.00 | 60847.05 | 42809.75 | 17471.95 | 13795.74 | 0.00 | ||||||
Maximum of Months | 0.962854E+11 | 0.233051E+11 | 469.42 | 0.604703E+11 | 0.358152E+11 | 0.00 | 1.00 | 0.00 | 125896.71 | 79058.29 | 64942.90 | 27226.09 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.99 | 0.00 | 310.99 | 249.13 | 1017.56 | 0.00 | 0.00 | 0.00 |
February | 366.89 | 0.00 | 366.89 | 331.45 | 851.01 | 0.00 | 0.00 | 0.00 |
March | 425.62 | 0.00 | 425.62 | 462.78 | 734.93 | 0.00 | 0.00 | 0.00 |
April | 502.33 | 2.06 | 500.27 | 702.38 | 472.43 | 0.00 | 0.00 | 0.00 |
May | 568.98 | 20.81 | 548.17 | 1150.44 | 140.46 | 0.00 | 0.00 | 0.00 |
June | 647.06 | 44.80 | 602.25 | 1359.66 | 121.18 | 0.00 | 0.00 | 0.00 |
July | 627.93 | 23.92 | 604.00 | 1305.90 | 83.02 | 0.00 | 0.00 | 0.00 |
August | 562.32 | 4.42 | 557.90 | 1182.94 | 112.96 | 0.00 | 0.00 | 0.00 |
September | 485.72 | 0.04 | 485.68 | 939.82 | 159.16 | 0.00 | 0.00 | 0.00 |
October | 422.08 | 0.00 | 422.08 | 763.94 | 299.14 | 0.00 | 0.00 | 0.00 |
November | 320.43 | 0.00 | 320.43 | 365.99 | 658.44 | 0.00 | 0.00 | 0.00 |
December | 289.10 | 0.00 | 289.10 | 264.06 | 865.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 461.25 | 8.03 | 453.22 | 759.10 | 457.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.10 | 0.00 | 289.10 | 249.13 | 83.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.06 | 44.80 | 604.00 | 1359.66 | 1017.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 533.58 | 271.70 | 261.88 | 654.16 | 634.43 | 0.00 | 0.00 | 0.00 |
February | 594.16 | 286.84 | 307.31 | 765.28 | 535.02 | 0.00 | 0.00 | 0.00 |
March | 698.92 | 337.07 | 361.85 | 962.55 | 467.27 | 0.00 | 0.00 | 0.00 |
April | 766.99 | 346.89 | 420.10 | 1187.88 | 312.31 | 0.00 | 0.00 | 0.00 |
May | 790.56 | 342.80 | 447.76 | 1456.03 | 95.15 | 0.00 | 0.00 | 0.00 |
June | 801.76 | 317.95 | 483.80 | 1527.85 | 82.14 | 0.00 | 0.00 | 0.00 |
July | 773.01 | 282.88 | 490.13 | 1472.92 | 55.83 | 0.00 | 0.00 | 0.00 |
August | 712.30 | 244.90 | 467.41 | 1361.42 | 76.85 | 0.00 | 0.00 | 0.00 |
September | 630.97 | 216.93 | 414.04 | 1148.80 | 107.38 | 0.00 | 0.00 | 0.00 |
October | 623.53 | 263.13 | 360.40 | 1083.02 | 196.90 | 0.00 | 0.00 | 0.00 |
November | 552.04 | 281.62 | 270.42 | 781.17 | 419.93 | 0.00 | 0.00 | 0.00 |
December | 434.65 | 196.89 | 237.76 | 555.25 | 554.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 659.59 | 282.34 | 377.26 | 1081.38 | 293.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 434.65 | 196.89 | 237.76 | 555.25 | 55.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 801.76 | 346.89 | 490.13 | 1527.85 | 634.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1797.57 | 1281.98 | 515.59 | 2600.28 | 957.76 | 0.00 | 0.00 | 0.00 |
February | 1630.29 | 1055.26 | 575.03 | 2410.60 | 821.18 | 0.00 | 0.00 | 0.00 |
March | 1040.82 | 469.72 | 571.09 | 1582.02 | 729.46 | 0.00 | 0.00 | 0.00 |
April | 771.44 | 180.77 | 590.67 | 1286.61 | 490.30 | 0.00 | 0.00 | 0.00 |
May | 589.44 | 25.05 | 564.39 | 1205.67 | 144.29 | 0.00 | 0.00 | 0.00 |
June | 582.26 | 5.43 | 576.83 | 1227.48 | 124.99 | 0.00 | 0.00 | 0.00 |
July | 609.53 | 11.20 | 598.33 | 1274.50 | 80.84 | 0.00 | 0.00 | 0.00 |
August | 717.08 | 86.07 | 631.01 | 1511.74 | 118.15 | 0.00 | 0.00 | 0.00 |
September | 860.38 | 226.75 | 633.63 | 1675.68 | 168.88 | 0.00 | 0.00 | 0.00 |
October | 1334.89 | 695.35 | 639.54 | 2397.96 | 315.01 | 0.00 | 0.00 | 0.00 |
November | 1698.73 | 1169.59 | 529.14 | 2654.20 | 651.06 | 0.00 | 0.00 | 0.00 |
December | 1756.44 | 1261.38 | 495.06 | 2635.09 | 845.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1113.02 | 536.38 | 576.64 | 1869.15 | 451.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.26 | 5.43 | 495.06 | 1205.67 | 80.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1797.57 | 1281.98 | 639.54 | 2654.20 | 957.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 567.54 | 306.90 | 260.65 | 743.71 | 668.19 | 0.00 | 0.00 | 0.00 |
February | 642.58 | 325.24 | 317.35 | 871.25 | 566.62 | 0.00 | 0.00 | 0.00 |
March | 633.33 | 280.36 | 352.97 | 886.67 | 491.88 | 0.00 | 0.00 | 0.00 |
April | 786.62 | 361.86 | 424.76 | 1235.93 | 329.59 | 0.00 | 0.00 | 0.00 |
May | 654.16 | 213.10 | 441.07 | 1240.66 | 104.84 | 0.00 | 0.00 | 0.00 |
June | 726.70 | 254.82 | 471.89 | 1404.58 | 91.62 | 0.00 | 0.00 | 0.00 |
July | 663.34 | 184.00 | 479.34 | 1285.85 | 61.92 | 0.00 | 0.00 | 0.00 |
August | 670.72 | 205.32 | 465.41 | 1302.77 | 84.52 | 0.00 | 0.00 | 0.00 |
September | 617.62 | 211.87 | 405.75 | 1137.16 | 116.40 | 0.00 | 0.00 | 0.00 |
October | 632.32 | 273.22 | 359.10 | 1120.08 | 212.45 | 0.00 | 0.00 | 0.00 |
November | 541.97 | 272.37 | 269.60 | 804.22 | 446.32 | 0.00 | 0.00 | 0.00 |
December | 521.33 | 277.24 | 244.09 | 719.54 | 571.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 637.82 | 263.23 | 374.59 | 1063.37 | 310.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 521.33 | 184.00 | 244.09 | 719.54 | 61.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 786.62 | 361.86 | 479.34 | 1404.58 | 668.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 0.00 | 103.66 | 79.81 | 367.33 | 0.00 | 0.00 | 0.00 |
February | 122.29 | 0.00 | 122.29 | 111.39 | 300.16 | 0.00 | 0.00 | 0.00 |
March | 141.87 | 0.00 | 141.87 | 159.91 | 250.66 | 0.00 | 0.00 | 0.00 |
April | 167.44 | 0.69 | 166.75 | 243.13 | 153.61 | 0.00 | 0.00 | 0.00 |
May | 189.65 | 6.94 | 182.72 | 394.31 | 40.30 | 0.00 | 0.00 | 0.00 |
June | 215.68 | 14.93 | 200.74 | 463.24 | 35.63 | 0.00 | 0.00 | 0.00 |
July | 209.30 | 7.97 | 201.33 | 443.89 | 25.04 | 0.00 | 0.00 | 0.00 |
August | 187.43 | 1.47 | 185.96 | 397.29 | 39.10 | 0.00 | 0.00 | 0.00 |
September | 161.90 | 0.01 | 161.89 | 315.99 | 57.24 | 0.00 | 0.00 | 0.00 |
October | 140.69 | 0.00 | 140.69 | 254.67 | 108.60 | 0.00 | 0.00 | 0.00 |
November | 106.80 | 0.00 | 106.80 | 117.18 | 244.27 | 0.00 | 0.00 | 0.00 |
December | 96.36 | 0.00 | 96.36 | 83.45 | 319.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.74 | 2.68 | 151.07 | 256.21 | 161.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.36 | 0.00 | 96.36 | 79.81 | 25.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.68 | 14.93 | 201.33 | 463.24 | 367.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 0.00 | 103.66 | 79.81 | 367.35 | 0.00 | 0.00 | 0.00 |
February | 122.30 | 0.00 | 122.30 | 111.39 | 300.18 | 0.00 | 0.00 | 0.00 |
March | 141.87 | 0.00 | 141.87 | 159.91 | 250.68 | 0.00 | 0.00 | 0.00 |
April | 167.44 | 0.69 | 166.76 | 243.14 | 153.62 | 0.00 | 0.00 | 0.00 |
May | 189.66 | 6.94 | 182.72 | 394.32 | 40.30 | 0.00 | 0.00 | 0.00 |
June | 215.68 | 14.93 | 200.75 | 463.26 | 35.63 | 0.00 | 0.00 | 0.00 |
July | 209.31 | 7.97 | 201.33 | 443.91 | 25.04 | 0.00 | 0.00 | 0.00 |
August | 187.44 | 1.47 | 185.96 | 397.31 | 39.11 | 0.00 | 0.00 | 0.00 |
September | 161.90 | 0.01 | 161.89 | 316.01 | 57.24 | 0.00 | 0.00 | 0.00 |
October | 140.69 | 0.00 | 140.69 | 254.68 | 108.61 | 0.00 | 0.00 | 0.00 |
November | 106.81 | 0.00 | 106.81 | 117.18 | 244.28 | 0.00 | 0.00 | 0.00 |
December | 96.37 | 0.00 | 96.37 | 83.46 | 319.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.75 | 2.68 | 151.07 | 256.23 | 161.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.37 | 0.00 | 96.37 | 79.81 | 25.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.68 | 14.93 | 201.33 | 463.26 | 367.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 0.00 | 103.66 | 79.81 | 367.35 | 0.00 | 0.00 | 0.00 |
February | 122.30 | 0.00 | 122.30 | 111.39 | 300.18 | 0.00 | 0.00 | 0.00 |
March | 141.87 | 0.00 | 141.87 | 159.91 | 250.68 | 0.00 | 0.00 | 0.00 |
April | 167.44 | 0.69 | 166.76 | 243.14 | 153.62 | 0.00 | 0.00 | 0.00 |
May | 189.66 | 6.94 | 182.72 | 394.32 | 40.30 | 0.00 | 0.00 | 0.00 |
June | 215.68 | 14.93 | 200.75 | 463.26 | 35.63 | 0.00 | 0.00 | 0.00 |
July | 209.31 | 7.97 | 201.33 | 443.91 | 25.04 | 0.00 | 0.00 | 0.00 |
August | 187.44 | 1.47 | 185.96 | 397.31 | 39.11 | 0.00 | 0.00 | 0.00 |
September | 161.90 | 0.01 | 161.89 | 316.01 | 57.24 | 0.00 | 0.00 | 0.00 |
October | 140.69 | 0.00 | 140.69 | 254.68 | 108.61 | 0.00 | 0.00 | 0.00 |
November | 106.81 | 0.00 | 106.81 | 117.18 | 244.28 | 0.00 | 0.00 | 0.00 |
December | 96.37 | 0.00 | 96.37 | 83.46 | 319.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.75 | 2.68 | 151.07 | 256.23 | 161.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.37 | 0.00 | 96.37 | 79.81 | 25.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.68 | 14.93 | 201.33 | 463.26 | 367.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 513.27 | 261.36 | 251.91 | 617.49 | 678.89 | 0.00 | 0.00 | 0.00 |
February | 571.55 | 275.93 | 295.62 | 733.53 | 559.18 | 0.00 | 0.00 | 0.00 |
March | 672.33 | 324.24 | 348.08 | 935.22 | 474.57 | 0.00 | 0.00 | 0.00 |
April | 737.80 | 333.69 | 404.12 | 1159.99 | 304.84 | 0.00 | 0.00 | 0.00 |
May | 760.47 | 329.75 | 430.72 | 1422.01 | 86.32 | 0.00 | 0.00 | 0.00 |
June | 771.25 | 305.85 | 465.39 | 1489.05 | 75.05 | 0.00 | 0.00 | 0.00 |
July | 743.59 | 272.11 | 471.48 | 1432.10 | 54.21 | 0.00 | 0.00 | 0.00 |
August | 685.20 | 235.58 | 449.62 | 1316.66 | 81.80 | 0.00 | 0.00 | 0.00 |
September | 606.96 | 208.67 | 398.29 | 1111.21 | 117.77 | 0.00 | 0.00 | 0.00 |
October | 599.80 | 253.11 | 346.69 | 1044.90 | 212.88 | 0.00 | 0.00 | 0.00 |
November | 531.04 | 270.90 | 260.14 | 742.47 | 457.18 | 0.00 | 0.00 | 0.00 |
December | 418.11 | 189.39 | 228.72 | 523.43 | 600.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.50 | 271.59 | 362.90 | 1045.66 | 307.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 418.11 | 189.39 | 228.72 | 523.43 | 54.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 771.25 | 333.69 | 471.48 | 1489.05 | 678.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.29 | 10.33 | 9.96 | 24.41 | 26.84 | 0.00 | 0.00 | 0.00 |
February | 22.60 | 10.91 | 11.69 | 29.00 | 22.11 | 0.00 | 0.00 | 0.00 |
March | 26.58 | 12.82 | 13.76 | 36.98 | 18.76 | 0.00 | 0.00 | 0.00 |
April | 29.17 | 13.19 | 15.98 | 45.86 | 12.05 | 0.00 | 0.00 | 0.00 |
May | 30.07 | 13.04 | 17.03 | 56.22 | 3.41 | 0.00 | 0.00 | 0.00 |
June | 30.49 | 12.09 | 18.40 | 58.88 | 2.97 | 0.00 | 0.00 | 0.00 |
July | 29.40 | 10.76 | 18.64 | 56.62 | 2.14 | 0.00 | 0.00 | 0.00 |
August | 27.09 | 9.31 | 17.78 | 52.06 | 3.23 | 0.00 | 0.00 | 0.00 |
September | 24.00 | 8.25 | 15.75 | 43.94 | 4.66 | 0.00 | 0.00 | 0.00 |
October | 23.72 | 10.01 | 13.71 | 41.31 | 8.42 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 10.71 | 10.29 | 29.36 | 18.08 | 0.00 | 0.00 | 0.00 |
December | 16.53 | 7.49 | 9.04 | 20.70 | 23.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.09 | 10.74 | 14.35 | 41.34 | 12.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.53 | 7.49 | 9.04 | 20.70 | 2.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.49 | 13.19 | 18.64 | 58.88 | 26.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.18 | 427.32 | 171.86 | 869.46 | 357.38 | 0.00 | 0.00 | 0.00 |
February | 543.42 | 351.75 | 191.68 | 808.80 | 300.25 | 0.00 | 0.00 | 0.00 |
March | 346.93 | 156.57 | 190.36 | 537.55 | 252.16 | 0.00 | 0.00 | 0.00 |
April | 257.14 | 60.25 | 196.89 | 439.53 | 161.63 | 0.00 | 0.00 | 0.00 |
May | 196.48 | 8.35 | 188.13 | 411.25 | 42.16 | 0.00 | 0.00 | 0.00 |
June | 194.09 | 1.81 | 192.28 | 417.42 | 36.64 | 0.00 | 0.00 | 0.00 |
July | 203.18 | 3.73 | 199.44 | 431.58 | 24.91 | 0.00 | 0.00 | 0.00 |
August | 239.03 | 28.69 | 210.34 | 505.24 | 42.42 | 0.00 | 0.00 | 0.00 |
September | 286.79 | 75.58 | 211.21 | 560.83 | 63.79 | 0.00 | 0.00 | 0.00 |
October | 444.96 | 231.78 | 213.18 | 799.81 | 119.90 | 0.00 | 0.00 | 0.00 |
November | 566.23 | 389.86 | 176.38 | 883.66 | 248.87 | 0.00 | 0.00 | 0.00 |
December | 585.47 | 420.45 | 165.02 | 879.33 | 318.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.00 | 178.79 | 192.21 | 627.81 | 163.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.09 | 1.81 | 165.02 | 411.25 | 24.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.18 | 427.32 | 213.18 | 883.66 | 357.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.18 | 427.32 | 171.86 | 869.46 | 357.38 | 0.00 | 0.00 | 0.00 |
February | 543.42 | 351.75 | 191.68 | 808.80 | 300.25 | 0.00 | 0.00 | 0.00 |
March | 346.93 | 156.57 | 190.36 | 537.55 | 252.16 | 0.00 | 0.00 | 0.00 |
April | 257.14 | 60.25 | 196.89 | 439.53 | 161.63 | 0.00 | 0.00 | 0.00 |
May | 196.48 | 8.35 | 188.13 | 411.25 | 42.16 | 0.00 | 0.00 | 0.00 |
June | 194.09 | 1.81 | 192.28 | 417.42 | 36.64 | 0.00 | 0.00 | 0.00 |
July | 203.18 | 3.73 | 199.44 | 431.58 | 24.91 | 0.00 | 0.00 | 0.00 |
August | 239.03 | 28.69 | 210.34 | 505.24 | 42.42 | 0.00 | 0.00 | 0.00 |
September | 286.79 | 75.58 | 211.21 | 560.83 | 63.79 | 0.00 | 0.00 | 0.00 |
October | 444.96 | 231.78 | 213.18 | 799.81 | 119.90 | 0.00 | 0.00 | 0.00 |
November | 566.23 | 389.86 | 176.38 | 883.66 | 248.87 | 0.00 | 0.00 | 0.00 |
December | 585.47 | 420.45 | 165.02 | 879.33 | 318.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.00 | 178.79 | 192.21 | 627.81 | 163.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.09 | 1.81 | 165.02 | 411.25 | 24.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.18 | 427.32 | 213.18 | 883.66 | 357.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.14 | 427.29 | 171.85 | 869.41 | 357.36 | 0.00 | 0.00 | 0.00 |
February | 543.39 | 351.72 | 191.66 | 808.75 | 300.23 | 0.00 | 0.00 | 0.00 |
March | 346.91 | 156.56 | 190.35 | 537.51 | 252.15 | 0.00 | 0.00 | 0.00 |
April | 257.13 | 60.25 | 196.88 | 439.50 | 161.62 | 0.00 | 0.00 | 0.00 |
May | 196.46 | 8.35 | 188.12 | 411.22 | 42.16 | 0.00 | 0.00 | 0.00 |
June | 194.07 | 1.81 | 192.26 | 417.39 | 36.64 | 0.00 | 0.00 | 0.00 |
July | 203.16 | 3.73 | 199.43 | 431.55 | 24.91 | 0.00 | 0.00 | 0.00 |
August | 239.01 | 28.69 | 210.32 | 505.21 | 42.41 | 0.00 | 0.00 | 0.00 |
September | 286.77 | 75.58 | 211.20 | 560.80 | 63.78 | 0.00 | 0.00 | 0.00 |
October | 444.93 | 231.76 | 213.16 | 799.76 | 119.89 | 0.00 | 0.00 | 0.00 |
November | 566.20 | 389.83 | 176.37 | 883.61 | 248.85 | 0.00 | 0.00 | 0.00 |
December | 585.43 | 420.43 | 165.01 | 879.27 | 318.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 370.98 | 178.78 | 192.20 | 627.77 | 163.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.07 | 1.81 | 165.01 | 411.22 | 24.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.14 | 427.29 | 213.16 | 883.61 | 357.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 545.95 | 295.22 | 250.73 | 710.15 | 714.95 | 0.00 | 0.00 | 0.00 |
February | 618.14 | 312.86 | 305.27 | 840.63 | 594.15 | 0.00 | 0.00 | 0.00 |
March | 609.24 | 269.69 | 339.54 | 863.45 | 501.11 | 0.00 | 0.00 | 0.00 |
April | 756.69 | 348.09 | 408.60 | 1207.03 | 323.98 | 0.00 | 0.00 | 0.00 |
May | 629.27 | 204.99 | 424.29 | 1212.64 | 93.47 | 0.00 | 0.00 | 0.00 |
June | 699.05 | 245.12 | 453.93 | 1369.42 | 83.87 | 0.00 | 0.00 | 0.00 |
July | 638.10 | 177.00 | 461.10 | 1252.04 | 58.67 | 0.00 | 0.00 | 0.00 |
August | 645.20 | 197.50 | 447.70 | 1259.90 | 88.96 | 0.00 | 0.00 | 0.00 |
September | 594.12 | 203.81 | 390.31 | 1098.73 | 126.15 | 0.00 | 0.00 | 0.00 |
October | 608.26 | 262.82 | 345.44 | 1079.14 | 228.42 | 0.00 | 0.00 | 0.00 |
November | 521.35 | 262.01 | 259.34 | 766.02 | 487.67 | 0.00 | 0.00 | 0.00 |
December | 501.49 | 266.69 | 234.81 | 684.50 | 622.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.55 | 253.21 | 360.34 | 1029.29 | 325.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 501.49 | 177.00 | 234.81 | 684.50 | 58.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 756.69 | 348.09 | 461.10 | 1369.42 | 714.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.59 | 11.67 | 9.91 | 28.08 | 28.27 | 0.00 | 0.00 | 0.00 |
February | 24.44 | 12.37 | 12.07 | 33.24 | 23.49 | 0.00 | 0.00 | 0.00 |
March | 24.09 | 10.66 | 13.43 | 34.14 | 19.81 | 0.00 | 0.00 | 0.00 |
April | 29.92 | 13.76 | 16.16 | 47.72 | 12.81 | 0.00 | 0.00 | 0.00 |
May | 24.88 | 8.10 | 16.78 | 47.95 | 3.70 | 0.00 | 0.00 | 0.00 |
June | 27.64 | 9.69 | 17.95 | 54.15 | 3.32 | 0.00 | 0.00 | 0.00 |
July | 25.23 | 7.00 | 18.23 | 49.50 | 2.32 | 0.00 | 0.00 | 0.00 |
August | 25.51 | 7.81 | 17.70 | 49.82 | 3.52 | 0.00 | 0.00 | 0.00 |
September | 23.49 | 8.06 | 15.43 | 43.44 | 4.99 | 0.00 | 0.00 | 0.00 |
October | 24.05 | 10.39 | 13.66 | 42.67 | 9.03 | 0.00 | 0.00 | 0.00 |
November | 20.61 | 10.36 | 10.25 | 30.29 | 19.28 | 0.00 | 0.00 | 0.00 |
December | 19.83 | 10.54 | 9.28 | 27.06 | 24.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.26 | 10.01 | 14.25 | 40.70 | 12.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.83 | 7.00 | 9.28 | 27.06 | 2.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.92 | 13.76 | 18.23 | 54.15 | 28.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.99 | 0.00 | 310.99 | 237.31 | 1090.34 | 0.00 | 0.00 | 0.00 |
February | 366.89 | 0.00 | 366.89 | 321.08 | 912.43 | 0.00 | 0.00 | 0.00 |
March | 425.62 | 0.00 | 425.62 | 457.28 | 779.30 | 0.00 | 0.00 | 0.00 |
April | 502.33 | 2.06 | 500.27 | 703.02 | 492.75 | 0.00 | 0.00 | 0.00 |
May | 568.98 | 20.81 | 548.17 | 1162.12 | 140.34 | 0.00 | 0.00 | 0.00 |
June | 647.06 | 44.80 | 602.25 | 1373.50 | 120.36 | 0.00 | 0.00 | 0.00 |
July | 627.93 | 23.92 | 604.00 | 1321.38 | 81.19 | 0.00 | 0.00 | 0.00 |
August | 562.32 | 4.42 | 557.90 | 1194.46 | 113.60 | 0.00 | 0.00 | 0.00 |
September | 485.72 | 0.04 | 485.68 | 949.14 | 164.08 | 0.00 | 0.00 | 0.00 |
October | 422.08 | 0.00 | 422.08 | 767.17 | 313.91 | 0.00 | 0.00 | 0.00 |
November | 320.43 | 0.00 | 320.43 | 355.44 | 709.95 | 0.00 | 0.00 | 0.00 |
December | 289.10 | 0.00 | 289.10 | 252.76 | 932.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 461.25 | 8.03 | 453.22 | 760.52 | 485.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.10 | 0.00 | 289.10 | 237.31 | 81.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.06 | 44.80 | 604.00 | 1373.50 | 1090.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 533.58 | 271.70 | 261.88 | 637.20 | 679.93 | 0.00 | 0.00 | 0.00 |
February | 594.16 | 286.84 | 307.31 | 751.11 | 572.22 | 0.00 | 0.00 | 0.00 |
March | 698.92 | 337.07 | 361.85 | 954.88 | 493.57 | 0.00 | 0.00 | 0.00 |
April | 766.99 | 346.89 | 420.10 | 1185.73 | 324.28 | 0.00 | 0.00 | 0.00 |
May | 790.56 | 342.80 | 447.76 | 1460.81 | 95.75 | 0.00 | 0.00 | 0.00 |
June | 801.76 | 317.95 | 483.80 | 1533.39 | 81.98 | 0.00 | 0.00 | 0.00 |
July | 773.01 | 282.88 | 490.13 | 1479.38 | 55.18 | 0.00 | 0.00 | 0.00 |
August | 712.30 | 244.90 | 467.41 | 1365.57 | 77.69 | 0.00 | 0.00 | 0.00 |
September | 630.97 | 216.93 | 414.04 | 1151.48 | 111.16 | 0.00 | 0.00 | 0.00 |
October | 623.53 | 263.13 | 360.40 | 1082.64 | 206.09 | 0.00 | 0.00 | 0.00 |
November | 552.04 | 281.62 | 270.42 | 770.13 | 448.74 | 0.00 | 0.00 | 0.00 |
December | 434.65 | 196.89 | 237.76 | 542.05 | 597.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 659.59 | 282.34 | 377.26 | 1077.95 | 310.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 434.65 | 196.89 | 237.76 | 542.05 | 55.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 801.76 | 346.89 | 490.13 | 1533.39 | 679.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1797.57 | 1281.98 | 515.59 | 2586.24 | 1020.68 | 0.00 | 0.00 | 0.00 |
February | 1630.29 | 1055.26 | 575.03 | 2398.88 | 874.15 | 0.00 | 0.00 | 0.00 |
March | 1040.82 | 469.72 | 571.09 | 1577.52 | 770.48 | 0.00 | 0.00 | 0.00 |
April | 771.44 | 180.77 | 590.67 | 1289.38 | 510.50 | 0.00 | 0.00 | 0.00 |
May | 589.44 | 25.05 | 564.39 | 1217.40 | 144.51 | 0.00 | 0.00 | 0.00 |
June | 582.26 | 5.43 | 576.83 | 1240.96 | 123.99 | 0.00 | 0.00 | 0.00 |
July | 609.53 | 11.20 | 598.33 | 1290.09 | 79.35 | 0.00 | 0.00 | 0.00 |
August | 717.08 | 86.07 | 631.01 | 1523.92 | 118.84 | 0.00 | 0.00 | 0.00 |
September | 860.38 | 226.75 | 633.63 | 1685.41 | 173.86 | 0.00 | 0.00 | 0.00 |
October | 1334.89 | 695.35 | 639.54 | 2403.98 | 328.02 | 0.00 | 0.00 | 0.00 |
November | 1698.73 | 1169.59 | 529.14 | 2646.14 | 691.63 | 0.00 | 0.00 | 0.00 |
December | 1756.44 | 1261.38 | 495.06 | 2624.32 | 903.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1113.02 | 536.38 | 576.64 | 1871.10 | 476.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.26 | 5.43 | 495.06 | 1217.40 | 79.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1797.57 | 1281.98 | 639.54 | 2646.14 | 1020.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 567.54 | 306.90 | 260.65 | 736.51 | 714.90 | 0.00 | 0.00 | 0.00 |
February | 642.58 | 325.24 | 317.35 | 865.29 | 606.16 | 0.00 | 0.00 | 0.00 |
March | 633.33 | 280.36 | 352.97 | 884.53 | 521.17 | 0.00 | 0.00 | 0.00 |
April | 786.62 | 361.86 | 424.76 | 1238.44 | 343.58 | 0.00 | 0.00 | 0.00 |
May | 654.16 | 213.10 | 441.07 | 1248.76 | 105.07 | 0.00 | 0.00 | 0.00 |
June | 726.70 | 254.82 | 471.89 | 1413.94 | 91.36 | 0.00 | 0.00 | 0.00 |
July | 663.34 | 184.00 | 479.34 | 1296.04 | 61.04 | 0.00 | 0.00 | 0.00 |
August | 670.72 | 205.32 | 465.41 | 1311.02 | 84.89 | 0.00 | 0.00 | 0.00 |
September | 617.62 | 211.87 | 405.75 | 1143.35 | 119.58 | 0.00 | 0.00 | 0.00 |
October | 632.32 | 273.22 | 359.10 | 1123.25 | 221.76 | 0.00 | 0.00 | 0.00 |
November | 541.97 | 272.37 | 269.60 | 798.81 | 478.66 | 0.00 | 0.00 | 0.00 |
December | 521.33 | 277.24 | 244.09 | 712.67 | 614.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 637.82 | 263.23 | 374.59 | 1065.10 | 328.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 521.33 | 184.00 | 244.09 | 712.67 | 61.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 786.62 | 361.86 | 479.34 | 1413.94 | 714.90 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.667273E+09 | 0.272543E+10 |
February | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.801839E+09 | 0.205876E+10 |
March | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.123951E+10 | 0.196844E+10 |
April | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.182057E+10 | 0.122455E+10 |
May | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.308134E+10 | 0.376198E+09 |
June | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.352424E+10 | 0.314097E+09 |
July | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.349773E+10 | 0.222358E+09 |
August | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.316839E+10 | 0.302548E+09 |
September | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.243602E+10 | 0.412546E+09 |
October | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.204615E+10 | 0.801209E+09 |
November | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.948650E+09 | 0.170668E+10 |
December | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.707252E+09 | 0.231729E+10 |
Annual Sum or Average | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.239389E+11 | 0.144301E+11 |
Minimum of Months | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.667273E+09 | 0.222358E+09 |
Maximum of Months | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.352424E+10 | 0.272543E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.175211E+10 | 0.169925E+10 |
February | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.185138E+10 | 0.129432E+10 |
March | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.257810E+10 | 0.125153E+10 |
April | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.307897E+10 | 0.809519E+09 |
May | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.389982E+10 | 0.254845E+09 |
June | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.396018E+10 | 0.212913E+09 |
July | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.394508E+10 | 0.149528E+09 |
August | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.364642E+10 | 0.205839E+09 |
September | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.297770E+10 | 0.278340E+09 |
October | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.290077E+10 | 0.527366E+09 |
November | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.202478E+10 | 0.108846E+10 |
December | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.148718E+10 | 0.148574E+10 |
Annual Sum or Average | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.341025E+11 | 0.925765E+10 |
Minimum of Months | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.148718E+10 | 0.149528E+09 |
Maximum of Months | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.396018E+10 | 0.169925E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.696458E+10 | 0.256525E+10 |
February | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.583174E+10 | 0.198661E+10 |
March | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.423727E+10 | 0.195378E+10 |
April | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.333489E+10 | 0.127087E+10 |
May | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.322926E+10 | 0.386469E+09 |
June | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.318163E+10 | 0.323966E+09 |
July | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.341363E+10 | 0.216511E+09 |
August | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.404904E+10 | 0.316454E+09 |
September | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.434337E+10 | 0.437740E+09 |
October | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.642270E+10 | 0.843713E+09 |
November | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.687969E+10 | 0.168755E+10 |
December | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.705783E+10 | 0.226484E+10 |
Annual Sum or Average | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.589456E+11 | 0.142538E+11 |
Minimum of Months | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.318163E+10 | 0.216511E+09 |
Maximum of Months | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.705783E+10 | 0.256525E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.199196E+10 | 0.178968E+10 |
February | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.210773E+10 | 0.137076E+10 |
March | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.237485E+10 | 0.131746E+10 |
April | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.320352E+10 | 0.854294E+09 |
May | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.332299E+10 | 0.280814E+09 |
June | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.364067E+10 | 0.237481E+09 |
July | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.344403E+10 | 0.165834E+09 |
August | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.348935E+10 | 0.226377E+09 |
September | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.294752E+10 | 0.301721E+09 |
October | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.300001E+10 | 0.569028E+09 |
November | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.208454E+10 | 0.115687E+10 |
December | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.192721E+10 | 0.153029E+10 |
Annual Sum or Average | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.335344E+11 | 0.980061E+10 |
Minimum of Months | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.192721E+10 | 0.165834E+09 |
Maximum of Months | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.364067E+10 | 0.178968E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277636E+09 | 0.00 | 0.277636E+09 | 0.213761E+09 | 0.983852E+09 |
February | 0.295846E+09 | 0.00 | 0.295846E+09 | 0.269473E+09 | 0.726158E+09 |
March | 0.379980E+09 | 0.00 | 0.379980E+09 | 0.428298E+09 | 0.671379E+09 |
April | 0.433993E+09 | 1781259.17 | 0.432212E+09 | 0.630186E+09 | 0.398161E+09 |
May | 0.507966E+09 | 18580228.25 | 0.489386E+09 | 0.105611E+10 | 0.107938E+09 |
June | 0.559031E+09 | 38708565.56 | 0.520323E+09 | 0.120071E+10 | 92340554.01 |
July | 0.560587E+09 | 21357348.22 | 0.539230E+09 | 0.118891E+10 | 67075531.62 |
August | 0.502016E+09 | 3948420.61 | 0.498068E+09 | 0.106411E+10 | 0.104736E+09 |
September | 0.419641E+09 | 32320.61 | 0.419609E+09 | 0.819055E+09 | 0.148371E+09 |
October | 0.376815E+09 | 0.00 | 0.376815E+09 | 0.682116E+09 | 0.290882E+09 |
November | 0.276835E+09 | 0.00 | 0.276835E+09 | 0.303718E+09 | 0.633147E+09 |
December | 0.258095E+09 | 0.00 | 0.258095E+09 | 0.223519E+09 | 0.854490E+09 |
Annual Sum or Average | 0.484844E+10 | 84408142.43 | 0.476403E+10 | 0.807996E+10 | 0.507853E+10 |
Minimum of Months | 0.258095E+09 | 0.00 | 0.258095E+09 | 0.213761E+09 | 67075531.62 |
Maximum of Months | 0.560587E+09 | 38708565.56 | 0.539230E+09 | 0.120071E+10 | 0.983852E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277648E+09 | 0.00 | 0.277648E+09 | 0.213769E+09 | 0.983910E+09 |
February | 0.295859E+09 | 0.00 | 0.295859E+09 | 0.269484E+09 | 0.726200E+09 |
March | 0.379995E+09 | 0.00 | 0.379995E+09 | 0.428315E+09 | 0.671418E+09 |
April | 0.434011E+09 | 1781307.06 | 0.432230E+09 | 0.630214E+09 | 0.398182E+09 |
May | 0.507986E+09 | 18580727.69 | 0.489405E+09 | 0.105616E+10 | 0.107942E+09 |
June | 0.559053E+09 | 38709606.06 | 0.520344E+09 | 0.120076E+10 | 92343778.89 |
July | 0.560609E+09 | 21357922.31 | 0.539251E+09 | 0.118897E+10 | 67077306.65 |
August | 0.502036E+09 | 3948526.74 | 0.498087E+09 | 0.106416E+10 | 0.104740E+09 |
September | 0.419658E+09 | 32321.48 | 0.419625E+09 | 0.819092E+09 | 0.148378E+09 |
October | 0.376830E+09 | 0.00 | 0.376830E+09 | 0.682147E+09 | 0.290898E+09 |
November | 0.276846E+09 | 0.00 | 0.276846E+09 | 0.303732E+09 | 0.633182E+09 |
December | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.223528E+09 | 0.854541E+09 |
Annual Sum or Average | 0.484864E+10 | 84410411.34 | 0.476423E+10 | 0.808033E+10 | 0.507881E+10 |
Minimum of Months | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.213769E+09 | 67077306.65 |
Maximum of Months | 0.560609E+09 | 38709606.06 | 0.539251E+09 | 0.120076E+10 | 0.983910E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277648E+09 | 0.00 | 0.277648E+09 | 0.213769E+09 | 0.983910E+09 |
February | 0.295859E+09 | 0.00 | 0.295859E+09 | 0.269484E+09 | 0.726200E+09 |
March | 0.379995E+09 | 0.00 | 0.379995E+09 | 0.428315E+09 | 0.671418E+09 |
April | 0.434011E+09 | 1781307.06 | 0.432230E+09 | 0.630214E+09 | 0.398182E+09 |
May | 0.507986E+09 | 18580727.69 | 0.489405E+09 | 0.105616E+10 | 0.107942E+09 |
June | 0.559053E+09 | 38709606.06 | 0.520344E+09 | 0.120076E+10 | 92343778.89 |
July | 0.560609E+09 | 21357922.31 | 0.539251E+09 | 0.118897E+10 | 67077306.65 |
August | 0.502036E+09 | 3948526.74 | 0.498087E+09 | 0.106416E+10 | 0.104740E+09 |
September | 0.419658E+09 | 32321.48 | 0.419625E+09 | 0.819092E+09 | 0.148378E+09 |
October | 0.376830E+09 | 0.00 | 0.376830E+09 | 0.682147E+09 | 0.290898E+09 |
November | 0.276846E+09 | 0.00 | 0.276846E+09 | 0.303732E+09 | 0.633182E+09 |
December | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.223528E+09 | 0.854541E+09 |
Annual Sum or Average | 0.484864E+10 | 84410411.34 | 0.476423E+10 | 0.808033E+10 | 0.507881E+10 |
Minimum of Months | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.213769E+09 | 67077306.65 |
Maximum of Months | 0.560609E+09 | 38709606.06 | 0.539251E+09 | 0.120076E+10 | 0.983910E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137475E+10 | 0.700026E+09 | 0.674726E+09 | 0.165388E+10 | 0.181835E+10 |
February | 0.138269E+10 | 0.667522E+09 | 0.715166E+09 | 0.177456E+10 | 0.135276E+10 |
March | 0.180076E+10 | 0.868455E+09 | 0.932307E+09 | 0.250490E+10 | 0.127109E+10 |
April | 0.191238E+10 | 0.864914E+09 | 0.104747E+10 | 0.300668E+10 | 0.790140E+09 |
May | 0.203686E+10 | 0.883215E+09 | 0.115364E+10 | 0.380871E+10 | 0.231205E+09 |
June | 0.199908E+10 | 0.792776E+09 | 0.120630E+10 | 0.385961E+10 | 0.194541E+09 |
July | 0.199164E+10 | 0.728831E+09 | 0.126281E+10 | 0.383573E+10 | 0.145197E+09 |
August | 0.183524E+10 | 0.630966E+09 | 0.120427E+10 | 0.352656E+10 | 0.219082E+09 |
September | 0.157324E+10 | 0.540873E+09 | 0.103237E+10 | 0.288026E+10 | 0.305255E+09 |
October | 0.160651E+10 | 0.677939E+09 | 0.928571E+09 | 0.279867E+10 | 0.570178E+09 |
November | 0.137645E+10 | 0.702179E+09 | 0.674272E+09 | 0.192448E+10 | 0.118501E+10 |
December | 0.111986E+10 | 0.507271E+09 | 0.612592E+09 | 0.140195E+10 | 0.160876E+10 |
Annual Sum or Average | 0.200095E+11 | 0.856497E+10 | 0.114445E+11 | 0.329760E+11 | 0.969157E+10 |
Minimum of Months | 0.111986E+10 | 0.507271E+09 | 0.612592E+09 | 0.140195E+10 | 0.145197E+09 |
Maximum of Months | 0.203686E+10 | 0.883215E+09 | 0.126281E+10 | 0.385961E+10 | 0.181835E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54356471.35 | 27678409.29 | 26678062.06 | 65392838.55 | 71895765.90 |
February | 54670229.54 | 26393225.09 | 28277004.45 | 70164613.05 | 53486861.53 |
March | 71200526.16 | 34337934.61 | 36862591.55 | 99041688.06 | 50257865.76 |
April | 75613838.40 | 34197916.95 | 41415921.45 | 0.118882E+09 | 31241416.41 |
May | 80535422.58 | 34921542.05 | 45613880.53 | 0.150593E+09 | 9141653.03 |
June | 79041780.87 | 31345643.89 | 47696136.98 | 0.152605E+09 | 7691958.26 |
July | 78747816.69 | 28817334.57 | 49930482.12 | 0.151661E+09 | 5740941.35 |
August | 72563678.74 | 24947839.83 | 47615838.90 | 0.139437E+09 | 8662321.46 |
September | 62204597.61 | 21385642.69 | 40818954.92 | 0.113883E+09 | 12069511.48 |
October | 63519959.84 | 26805108.71 | 36714851.13 | 0.110657E+09 | 22544316.90 |
November | 54423616.40 | 27763514.35 | 26660102.05 | 76092277.93 | 46854181.08 |
December | 44278388.28 | 20057044.62 | 24221343.66 | 55432028.85 | 63609055.77 |
Annual Sum or Average | 0.791156E+09 | 0.338651E+09 | 0.452505E+09 | 0.130384E+10 | 0.383196E+09 |
Minimum of Months | 44278388.28 | 20057044.62 | 24221343.66 | 55432028.85 | 5740941.35 |
Maximum of Months | 80535422.58 | 34921542.05 | 49930482.12 | 0.152605E+09 | 71895765.90 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160484E+10 | 0.114453E+10 | 0.460314E+09 | 0.232877E+10 | 0.957219E+09 |
February | 0.131465E+10 | 0.850946E+09 | 0.463701E+09 | 0.195665E+10 | 0.726369E+09 |
March | 0.929226E+09 | 0.419358E+09 | 0.509868E+09 | 0.143977E+10 | 0.675395E+09 |
April | 0.666517E+09 | 0.156180E+09 | 0.510337E+09 | 0.113927E+10 | 0.418940E+09 |
May | 0.526244E+09 | 22364338.43 | 0.503879E+09 | 0.110149E+10 | 0.112917E+09 |
June | 0.503070E+09 | 4689036.20 | 0.498381E+09 | 0.108195E+10 | 94974928.80 |
July | 0.544187E+09 | 10001971.24 | 0.534185E+09 | 0.115594E+10 | 66713726.41 |
August | 0.640205E+09 | 76843168.97 | 0.563362E+09 | 0.135324E+10 | 0.113606E+09 |
September | 0.743358E+09 | 0.195905E+09 | 0.547453E+09 | 0.145368E+10 | 0.165339E+09 |
October | 0.119177E+10 | 0.620796E+09 | 0.570972E+09 | 0.214221E+10 | 0.321144E+09 |
November | 0.146768E+10 | 0.101051E+10 | 0.457169E+09 | 0.229045E+10 | 0.645067E+09 |
December | 0.156813E+10 | 0.112614E+10 | 0.441984E+09 | 0.235519E+10 | 0.854090E+09 |
Annual Sum or Average | 0.116999E+11 | 0.563826E+10 | 0.606161E+10 | 0.197986E+11 | 0.515178E+10 |
Minimum of Months | 0.503070E+09 | 4689036.20 | 0.441984E+09 | 0.108195E+10 | 66713726.41 |
Maximum of Months | 0.160484E+10 | 0.114453E+10 | 0.570972E+09 | 0.235519E+10 | 0.957219E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160484E+10 | 0.114453E+10 | 0.460314E+09 | 0.232877E+10 | 0.957219E+09 |
February | 0.131465E+10 | 0.850946E+09 | 0.463701E+09 | 0.195665E+10 | 0.726369E+09 |
March | 0.929226E+09 | 0.419358E+09 | 0.509868E+09 | 0.143977E+10 | 0.675395E+09 |
April | 0.666517E+09 | 0.156180E+09 | 0.510337E+09 | 0.113927E+10 | 0.418940E+09 |
May | 0.526244E+09 | 22364338.43 | 0.503879E+09 | 0.110149E+10 | 0.112917E+09 |
June | 0.503070E+09 | 4689036.20 | 0.498381E+09 | 0.108195E+10 | 94974928.80 |
July | 0.544187E+09 | 10001971.24 | 0.534185E+09 | 0.115594E+10 | 66713726.41 |
August | 0.640205E+09 | 76843168.97 | 0.563362E+09 | 0.135324E+10 | 0.113606E+09 |
September | 0.743358E+09 | 0.195905E+09 | 0.547453E+09 | 0.145368E+10 | 0.165339E+09 |
October | 0.119177E+10 | 0.620796E+09 | 0.570972E+09 | 0.214221E+10 | 0.321144E+09 |
November | 0.146768E+10 | 0.101051E+10 | 0.457169E+09 | 0.229045E+10 | 0.645067E+09 |
December | 0.156813E+10 | 0.112614E+10 | 0.441984E+09 | 0.235519E+10 | 0.854090E+09 |
Annual Sum or Average | 0.116999E+11 | 0.563826E+10 | 0.606161E+10 | 0.197986E+11 | 0.515178E+10 |
Minimum of Months | 0.503070E+09 | 4689036.20 | 0.441984E+09 | 0.108195E+10 | 66713726.41 |
Maximum of Months | 0.160484E+10 | 0.114453E+10 | 0.570972E+09 | 0.235519E+10 | 0.957219E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160474E+10 | 0.114446E+10 | 0.460285E+09 | 0.232862E+10 | 0.957159E+09 |
February | 0.131456E+10 | 0.850892E+09 | 0.463672E+09 | 0.195653E+10 | 0.726323E+09 |
March | 0.929168E+09 | 0.419332E+09 | 0.509836E+09 | 0.143968E+10 | 0.675353E+09 |
April | 0.666475E+09 | 0.156170E+09 | 0.510305E+09 | 0.113920E+10 | 0.418914E+09 |
May | 0.526210E+09 | 22362925.13 | 0.503848E+09 | 0.110142E+10 | 0.112909E+09 |
June | 0.503039E+09 | 4688739.88 | 0.498350E+09 | 0.108189E+10 | 94968926.92 |
July | 0.544152E+09 | 10001339.17 | 0.534151E+09 | 0.115587E+10 | 66709510.48 |
August | 0.640165E+09 | 76838312.92 | 0.563327E+09 | 0.135316E+10 | 0.113599E+09 |
September | 0.743311E+09 | 0.195893E+09 | 0.547419E+09 | 0.145359E+10 | 0.165329E+09 |
October | 0.119169E+10 | 0.620756E+09 | 0.570936E+09 | 0.214208E+10 | 0.321124E+09 |
November | 0.146758E+10 | 0.101044E+10 | 0.457140E+09 | 0.229031E+10 | 0.645026E+09 |
December | 0.156803E+10 | 0.112607E+10 | 0.441956E+09 | 0.235505E+10 | 0.854036E+09 |
Annual Sum or Average | 0.116991E+11 | 0.563790E+10 | 0.606122E+10 | 0.197974E+11 | 0.515145E+10 |
Minimum of Months | 0.503039E+09 | 4688739.88 | 0.441956E+09 | 0.108189E+10 | 66709510.48 |
Maximum of Months | 0.160474E+10 | 0.114446E+10 | 0.570936E+09 | 0.235505E+10 | 0.957159E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146227E+10 | 0.790712E+09 | 0.671557E+09 | 0.190207E+10 | 0.191491E+10 |
February | 0.149539E+10 | 0.756873E+09 | 0.738521E+09 | 0.203366E+10 | 0.143737E+10 |
March | 0.163178E+10 | 0.722344E+09 | 0.909433E+09 | 0.231267E+10 | 0.134217E+10 |
April | 0.196133E+10 | 0.902246E+09 | 0.105909E+10 | 0.312862E+10 | 0.839764E+09 |
May | 0.168545E+10 | 0.549036E+09 | 0.113641E+10 | 0.324793E+10 | 0.250346E+09 |
June | 0.181194E+10 | 0.635350E+09 | 0.117659E+10 | 0.354953E+10 | 0.217386E+09 |
July | 0.170910E+10 | 0.474075E+09 | 0.123502E+10 | 0.335347E+10 | 0.157151E+09 |
August | 0.172811E+10 | 0.528997E+09 | 0.119912E+10 | 0.337452E+10 | 0.238277E+09 |
September | 0.153997E+10 | 0.528281E+09 | 0.101169E+10 | 0.284790E+10 | 0.326969E+09 |
October | 0.162916E+10 | 0.703941E+09 | 0.925222E+09 | 0.289036E+10 | 0.611788E+09 |
November | 0.135134E+10 | 0.679128E+09 | 0.672214E+09 | 0.198552E+10 | 0.126404E+10 |
December | 0.134320E+10 | 0.714295E+09 | 0.628908E+09 | 0.183338E+10 | 0.166732E+10 |
Annual Sum or Average | 0.193491E+11 | 0.798528E+10 | 0.113638E+11 | 0.324596E+11 | 0.102675E+11 |
Minimum of Months | 0.134320E+10 | 0.474075E+09 | 0.628908E+09 | 0.183338E+10 | 0.157151E+09 |
Maximum of Months | 0.196133E+10 | 0.902246E+09 | 0.123502E+10 | 0.354953E+10 | 0.191491E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57816631.47 | 31263925.13 | 26552706.35 | 75205867.04 | 75713796.59 |
February | 59126367.15 | 29925980.13 | 29200387.02 | 80408940.67 | 56832231.17 |
March | 64518822.28 | 28560742.89 | 35958079.39 | 91440812.03 | 53068091.20 |
April | 77549088.27 | 35673885.36 | 41875202.92 | 0.123702E+09 | 33203505.77 |
May | 66641001.52 | 21708327.14 | 44932674.37 | 0.128420E+09 | 9898451.21 |
June | 71642423.28 | 25121088.99 | 46521334.29 | 0.140345E+09 | 8595239.33 |
July | 67576012.84 | 18744438.16 | 48831574.67 | 0.132593E+09 | 6213594.75 |
August | 68327895.74 | 20916000.03 | 47411895.71 | 0.133425E+09 | 9421256.75 |
September | 60888769.33 | 20887671.24 | 40001098.09 | 0.112603E+09 | 12928042.03 |
October | 64415458.14 | 27833093.60 | 36582364.54 | 0.114282E+09 | 24189511.45 |
November | 53430703.01 | 26852018.34 | 26578684.67 | 78505450.98 | 49978966.05 |
December | 53108910.18 | 28242496.52 | 24866413.65 | 72489826.82 | 65924357.29 |
Annual Sum or Average | 0.765042E+09 | 0.315730E+09 | 0.449312E+09 | 0.128342E+10 | 0.405967E+09 |
Minimum of Months | 53108910.18 | 18744438.16 | 24866413.65 | 72489826.82 | 6213594.75 |
Maximum of Months | 77549088.27 | 35673885.36 | 48831574.67 | 0.140345E+09 | 75713796.59 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.635619E+09 | 0.292036E+10 |
February | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.776756E+09 | 0.220734E+10 |
March | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.122478E+10 | 0.208729E+10 |
April | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.182223E+10 | 0.127720E+10 |
May | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.311262E+10 | 0.375898E+09 |
June | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.356012E+10 | 0.311979E+09 |
July | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.353918E+10 | 0.217456E+09 |
August | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.319925E+10 | 0.304264E+09 |
September | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.246016E+10 | 0.425284E+09 |
October | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.205480E+10 | 0.840777E+09 |
November | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.921288E+09 | 0.184020E+10 |
December | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.676980E+09 | 0.249881E+10 |
Annual Sum or Average | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.239838E+11 | 0.153069E+11 |
Minimum of Months | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.635619E+09 | 0.217456E+09 |
Maximum of Months | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.356012E+10 | 0.292036E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.170667E+10 | 0.182113E+10 |
February | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.181709E+10 | 0.138432E+10 |
March | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.255755E+10 | 0.132199E+10 |
April | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.307341E+10 | 0.840521E+09 |
May | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.391262E+10 | 0.256464E+09 |
June | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.397456E+10 | 0.212499E+09 |
July | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.396236E+10 | 0.147796E+09 |
August | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.365754E+10 | 0.208082E+09 |
September | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.298464E+10 | 0.288114E+09 |
October | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.289975E+10 | 0.551993E+09 |
November | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.199617E+10 | 0.116314E+10 |
December | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.145181E+10 | 0.159910E+10 |
Annual Sum or Average | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.339942E+11 | 0.979515E+10 |
Minimum of Months | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.145181E+10 | 0.147796E+09 |
Maximum of Months | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.397456E+10 | 0.182113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.692699E+10 | 0.273378E+10 |
February | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.580338E+10 | 0.211475E+10 |
March | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.422523E+10 | 0.206365E+10 |
April | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.334208E+10 | 0.132321E+10 |
May | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.326068E+10 | 0.387062E+09 |
June | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.321658E+10 | 0.321392E+09 |
July | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.345536E+10 | 0.212528E+09 |
August | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.408167E+10 | 0.318303E+09 |
September | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.436858E+10 | 0.450633E+09 |
October | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.643882E+10 | 0.878558E+09 |
November | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.685878E+10 | 0.179269E+10 |
December | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.702899E+10 | 0.241980E+10 |
Annual Sum or Average | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.590071E+11 | 0.150163E+11 |
Minimum of Months | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.321658E+10 | 0.212528E+09 |
Maximum of Months | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.702899E+10 | 0.273378E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.197266E+10 | 0.191478E+10 |
February | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.209331E+10 | 0.146643E+10 |
March | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.236913E+10 | 0.139591E+10 |
April | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.321003E+10 | 0.890572E+09 |
May | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.334467E+10 | 0.281417E+09 |
June | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.366494E+10 | 0.236804E+09 |
July | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.347132E+10 | 0.163494E+09 |
August | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.351143E+10 | 0.227380E+09 |
September | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.296357E+10 | 0.309948E+09 |
October | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.300852E+10 | 0.593961E+09 |
November | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.207051E+10 | 0.124068E+10 |
December | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.190883E+10 | 0.164537E+10 |
Annual Sum or Average | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.335889E+11 | 0.103667E+11 |
Minimum of Months | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.190883E+10 | 0.163494E+09 |
Maximum of Months | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.366494E+10 | 0.191478E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 249.13 | 1017.56 | 310.99 | 0.00 | 310.99 | 0.00 | 0.00 |
February | 331.45 | 851.01 | 366.89 | 0.00 | 366.89 | 0.00 | 0.00 |
March | 462.78 | 734.93 | 425.62 | 0.00 | 425.62 | 0.00 | 0.00 |
April | 702.38 | 472.43 | 502.33 | 2.06 | 500.27 | 0.00 | 0.00 |
May | 1150.44 | 140.46 | 568.98 | 20.81 | 548.17 | 0.00 | 0.00 |
June | 1359.66 | 121.18 | 647.06 | 44.80 | 602.25 | 0.00 | 0.00 |
July | 1305.90 | 83.02 | 627.93 | 23.92 | 604.00 | 0.00 | 0.00 |
August | 1182.94 | 112.96 | 562.32 | 4.42 | 557.90 | 0.00 | 0.00 |
September | 939.82 | 159.16 | 485.72 | 0.04 | 485.68 | 0.00 | 0.00 |
October | 763.94 | 299.14 | 422.08 | 0.00 | 422.08 | 0.00 | 0.00 |
November | 365.99 | 658.44 | 320.43 | 0.00 | 320.43 | 0.00 | 0.00 |
December | 264.06 | 865.18 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Annual Sum or Average | 759.10 | 457.58 | 461.25 | 8.03 | 453.22 | 0.00 | 0.00 |
Minimum of Months | 249.13 | 83.02 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Maximum of Months | 1359.66 | 1017.56 | 647.06 | 44.80 | 604.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 654.16 | 634.43 | 533.58 | 271.70 | 261.88 | 0.00 | 0.00 |
February | 765.28 | 535.02 | 594.16 | 286.84 | 307.31 | 0.00 | 0.00 |
March | 962.55 | 467.27 | 698.92 | 337.07 | 361.85 | 0.00 | 0.00 |
April | 1187.88 | 312.31 | 766.99 | 346.89 | 420.10 | 0.00 | 0.00 |
May | 1456.03 | 95.15 | 790.56 | 342.80 | 447.76 | 0.00 | 0.00 |
June | 1527.85 | 82.14 | 801.76 | 317.95 | 483.80 | 0.00 | 0.00 |
July | 1472.92 | 55.83 | 773.01 | 282.88 | 490.13 | 0.00 | 0.00 |
August | 1361.42 | 76.85 | 712.30 | 244.90 | 467.41 | 0.00 | 0.00 |
September | 1148.80 | 107.38 | 630.97 | 216.93 | 414.04 | 0.00 | 0.00 |
October | 1083.02 | 196.90 | 623.53 | 263.13 | 360.40 | 0.00 | 0.00 |
November | 781.17 | 419.93 | 552.04 | 281.62 | 270.42 | 0.00 | 0.00 |
December | 555.25 | 554.71 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Annual Sum or Average | 1081.38 | 293.56 | 659.59 | 282.34 | 377.26 | 0.00 | 0.00 |
Minimum of Months | 555.25 | 55.83 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Maximum of Months | 1527.85 | 634.43 | 801.76 | 346.89 | 490.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2600.28 | 957.76 | 1797.57 | 1281.98 | 515.59 | 0.00 | 0.00 |
February | 2410.60 | 821.18 | 1630.29 | 1055.26 | 575.03 | 0.00 | 0.00 |
March | 1582.02 | 729.46 | 1040.82 | 469.72 | 571.09 | 0.00 | 0.00 |
April | 1286.61 | 490.30 | 771.44 | 180.77 | 590.67 | 0.00 | 0.00 |
May | 1205.67 | 144.29 | 589.44 | 25.05 | 564.39 | 0.00 | 0.00 |
June | 1227.48 | 124.99 | 582.26 | 5.43 | 576.83 | 0.00 | 0.00 |
July | 1274.50 | 80.84 | 609.53 | 11.20 | 598.33 | 0.00 | 0.00 |
August | 1511.74 | 118.15 | 717.08 | 86.07 | 631.01 | 0.00 | 0.00 |
September | 1675.68 | 168.88 | 860.38 | 226.75 | 633.63 | 0.00 | 0.00 |
October | 2397.96 | 315.01 | 1334.89 | 695.35 | 639.54 | 0.00 | 0.00 |
November | 2654.20 | 651.06 | 1698.73 | 1169.59 | 529.14 | 0.00 | 0.00 |
December | 2635.09 | 845.59 | 1756.44 | 1261.38 | 495.06 | 0.00 | 0.00 |
Annual Sum or Average | 1869.15 | 451.98 | 1113.02 | 536.38 | 576.64 | 0.00 | 0.00 |
Minimum of Months | 1205.67 | 80.84 | 582.26 | 5.43 | 495.06 | 0.00 | 0.00 |
Maximum of Months | 2654.20 | 957.76 | 1797.57 | 1281.98 | 639.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 743.71 | 668.19 | 567.54 | 306.90 | 260.65 | 0.00 | 0.00 |
February | 871.25 | 566.62 | 642.58 | 325.24 | 317.35 | 0.00 | 0.00 |
March | 886.67 | 491.88 | 633.33 | 280.36 | 352.97 | 0.00 | 0.00 |
April | 1235.93 | 329.59 | 786.62 | 361.86 | 424.76 | 0.00 | 0.00 |
May | 1240.66 | 104.84 | 654.16 | 213.10 | 441.07 | 0.00 | 0.00 |
June | 1404.58 | 91.62 | 726.70 | 254.82 | 471.89 | 0.00 | 0.00 |
July | 1285.85 | 61.92 | 663.34 | 184.00 | 479.34 | 0.00 | 0.00 |
August | 1302.77 | 84.52 | 670.72 | 205.32 | 465.41 | 0.00 | 0.00 |
September | 1137.16 | 116.40 | 617.62 | 211.87 | 405.75 | 0.00 | 0.00 |
October | 1120.08 | 212.45 | 632.32 | 273.22 | 359.10 | 0.00 | 0.00 |
November | 804.22 | 446.32 | 541.97 | 272.37 | 269.60 | 0.00 | 0.00 |
December | 719.54 | 571.34 | 521.33 | 277.24 | 244.09 | 0.00 | 0.00 |
Annual Sum or Average | 1063.37 | 310.78 | 637.82 | 263.23 | 374.59 | 0.00 | 0.00 |
Minimum of Months | 719.54 | 61.92 | 521.33 | 184.00 | 244.09 | 0.00 | 0.00 |
Maximum of Months | 1404.58 | 668.19 | 786.62 | 361.86 | 479.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.43 | 1102.03 | 310.98 | 0.00 | 310.98 | 0.00 | 0.00 |
February | 334.18 | 900.53 | 366.88 | 0.00 | 366.88 | 0.00 | 0.00 |
March | 479.74 | 752.02 | 425.62 | 0.00 | 425.62 | 0.00 | 0.00 |
April | 729.40 | 460.85 | 502.32 | 2.06 | 500.26 | 0.00 | 0.00 |
May | 1182.95 | 120.90 | 568.97 | 20.81 | 548.16 | 0.00 | 0.00 |
June | 1389.75 | 106.88 | 647.04 | 44.80 | 602.24 | 0.00 | 0.00 |
July | 1331.71 | 75.13 | 627.91 | 23.92 | 603.99 | 0.00 | 0.00 |
August | 1191.91 | 117.31 | 562.31 | 4.42 | 557.89 | 0.00 | 0.00 |
September | 948.01 | 171.73 | 485.71 | 0.04 | 485.67 | 0.00 | 0.00 |
October | 764.04 | 325.82 | 422.07 | 0.00 | 422.07 | 0.00 | 0.00 |
November | 351.54 | 732.84 | 320.42 | 0.00 | 320.42 | 0.00 | 0.00 |
December | 250.36 | 957.13 | 289.09 | 0.00 | 289.09 | 0.00 | 0.00 |
Annual Sum or Average | 768.66 | 483.14 | 461.24 | 8.03 | 453.21 | 0.00 | 0.00 |
Minimum of Months | 239.43 | 75.13 | 289.09 | 0.00 | 289.09 | 0.00 | 0.00 |
Maximum of Months | 1389.75 | 1102.03 | 647.04 | 44.80 | 603.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 641.90 | 705.74 | 533.57 | 271.69 | 261.87 | 0.00 | 0.00 |
February | 762.54 | 581.29 | 594.15 | 286.84 | 307.31 | 0.00 | 0.00 |
March | 972.20 | 493.34 | 698.91 | 337.06 | 361.85 | 0.00 | 0.00 |
April | 1205.85 | 316.89 | 766.97 | 346.88 | 420.09 | 0.00 | 0.00 |
May | 1478.23 | 89.74 | 790.54 | 342.79 | 447.75 | 0.00 | 0.00 |
June | 1547.92 | 78.02 | 801.74 | 317.95 | 483.80 | 0.00 | 0.00 |
July | 1488.72 | 56.35 | 773.00 | 282.87 | 490.12 | 0.00 | 0.00 |
August | 1368.72 | 85.03 | 712.29 | 244.89 | 467.40 | 0.00 | 0.00 |
September | 1155.15 | 122.42 | 630.96 | 216.92 | 414.04 | 0.00 | 0.00 |
October | 1086.22 | 221.30 | 623.52 | 263.12 | 360.40 | 0.00 | 0.00 |
November | 771.83 | 475.26 | 552.03 | 281.61 | 270.42 | 0.00 | 0.00 |
December | 544.13 | 624.39 | 434.64 | 196.88 | 237.76 | 0.00 | 0.00 |
Annual Sum or Average | 1087.01 | 319.47 | 659.58 | 282.33 | 377.25 | 0.00 | 0.00 |
Minimum of Months | 544.13 | 56.35 | 434.64 | 196.88 | 237.76 | 0.00 | 0.00 |
Maximum of Months | 1547.92 | 705.74 | 801.74 | 346.88 | 490.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2608.33 | 1072.13 | 1797.50 | 1281.93 | 515.57 | 0.00 | 0.00 |
February | 2426.35 | 900.74 | 1630.23 | 1055.22 | 575.01 | 0.00 | 0.00 |
March | 1612.61 | 756.48 | 1040.78 | 469.70 | 571.08 | 0.00 | 0.00 |
April | 1318.57 | 484.87 | 771.42 | 180.76 | 590.66 | 0.00 | 0.00 |
May | 1233.72 | 126.47 | 589.42 | 25.05 | 564.37 | 0.00 | 0.00 |
June | 1252.23 | 109.92 | 582.25 | 5.43 | 576.82 | 0.00 | 0.00 |
July | 1294.71 | 74.72 | 609.52 | 11.20 | 598.31 | 0.00 | 0.00 |
August | 1515.70 | 127.24 | 717.06 | 86.07 | 630.99 | 0.00 | 0.00 |
September | 1682.46 | 191.36 | 860.35 | 226.74 | 633.61 | 0.00 | 0.00 |
October | 2399.38 | 359.70 | 1334.84 | 695.32 | 639.52 | 0.00 | 0.00 |
November | 2650.93 | 746.59 | 1698.66 | 1169.54 | 529.12 | 0.00 | 0.00 |
December | 2637.93 | 956.62 | 1756.38 | 1261.33 | 495.04 | 0.00 | 0.00 |
Annual Sum or Average | 1883.39 | 490.07 | 1112.98 | 536.35 | 576.62 | 0.00 | 0.00 |
Minimum of Months | 1233.72 | 74.72 | 582.25 | 5.43 | 495.04 | 0.00 | 0.00 |
Maximum of Months | 2650.93 | 1072.13 | 1797.50 | 1281.93 | 639.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 738.23 | 743.21 | 567.53 | 306.89 | 260.64 | 0.00 | 0.00 |
February | 873.87 | 617.64 | 642.58 | 325.23 | 317.35 | 0.00 | 0.00 |
March | 897.59 | 520.92 | 633.32 | 280.36 | 352.97 | 0.00 | 0.00 |
April | 1254.75 | 336.79 | 786.61 | 361.85 | 424.75 | 0.00 | 0.00 |
May | 1260.58 | 97.16 | 654.16 | 213.09 | 441.06 | 0.00 | 0.00 |
June | 1423.56 | 87.18 | 726.69 | 254.81 | 471.88 | 0.00 | 0.00 |
July | 1301.55 | 60.99 | 663.33 | 184.00 | 479.34 | 0.00 | 0.00 |
August | 1309.72 | 92.48 | 670.71 | 205.31 | 465.40 | 0.00 | 0.00 |
September | 1142.17 | 131.13 | 617.61 | 211.87 | 405.74 | 0.00 | 0.00 |
October | 1121.80 | 237.45 | 632.31 | 273.21 | 359.10 | 0.00 | 0.00 |
November | 796.31 | 506.95 | 541.96 | 272.37 | 269.60 | 0.00 | 0.00 |
December | 711.57 | 647.12 | 521.32 | 277.23 | 244.09 | 0.00 | 0.00 |
Annual Sum or Average | 1069.99 | 338.45 | 637.81 | 263.22 | 374.59 | 0.00 | 0.00 |
Minimum of Months | 711.57 | 60.99 | 521.32 | 184.00 | 244.09 | 0.00 | 0.00 |
Maximum of Months | 1423.56 | 743.21 | 786.61 | 361.85 | 479.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.31 | 1090.34 | 310.99 | 0.00 | 310.99 | 0.00 | 0.00 |
February | 321.08 | 912.43 | 366.89 | 0.00 | 366.89 | 0.00 | 0.00 |
March | 457.28 | 779.30 | 425.62 | 0.00 | 425.62 | 0.00 | 0.00 |
April | 703.02 | 492.75 | 502.33 | 2.06 | 500.27 | 0.00 | 0.00 |
May | 1162.12 | 140.34 | 568.98 | 20.81 | 548.17 | 0.00 | 0.00 |
June | 1373.50 | 120.36 | 647.06 | 44.80 | 602.25 | 0.00 | 0.00 |
July | 1321.38 | 81.19 | 627.93 | 23.92 | 604.00 | 0.00 | 0.00 |
August | 1194.46 | 113.60 | 562.32 | 4.42 | 557.90 | 0.00 | 0.00 |
September | 949.14 | 164.08 | 485.72 | 0.04 | 485.68 | 0.00 | 0.00 |
October | 767.17 | 313.91 | 422.08 | 0.00 | 422.08 | 0.00 | 0.00 |
November | 355.44 | 709.95 | 320.43 | 0.00 | 320.43 | 0.00 | 0.00 |
December | 252.76 | 932.95 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Annual Sum or Average | 760.52 | 485.38 | 461.25 | 8.03 | 453.22 | 0.00 | 0.00 |
Minimum of Months | 237.31 | 81.19 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Maximum of Months | 1373.50 | 1090.34 | 647.06 | 44.80 | 604.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 637.20 | 679.93 | 533.58 | 271.70 | 261.88 | 0.00 | 0.00 |
February | 751.11 | 572.22 | 594.16 | 286.84 | 307.31 | 0.00 | 0.00 |
March | 954.88 | 493.57 | 698.92 | 337.07 | 361.85 | 0.00 | 0.00 |
April | 1185.73 | 324.28 | 766.99 | 346.89 | 420.10 | 0.00 | 0.00 |
May | 1460.81 | 95.75 | 790.56 | 342.80 | 447.76 | 0.00 | 0.00 |
June | 1533.39 | 81.98 | 801.76 | 317.95 | 483.80 | 0.00 | 0.00 |
July | 1479.38 | 55.18 | 773.01 | 282.88 | 490.13 | 0.00 | 0.00 |
August | 1365.57 | 77.69 | 712.30 | 244.90 | 467.41 | 0.00 | 0.00 |
September | 1151.48 | 111.16 | 630.97 | 216.93 | 414.04 | 0.00 | 0.00 |
October | 1082.64 | 206.09 | 623.53 | 263.13 | 360.40 | 0.00 | 0.00 |
November | 770.13 | 448.74 | 552.04 | 281.62 | 270.42 | 0.00 | 0.00 |
December | 542.05 | 597.04 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Annual Sum or Average | 1077.95 | 310.60 | 659.59 | 282.34 | 377.26 | 0.00 | 0.00 |
Minimum of Months | 542.05 | 55.18 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Maximum of Months | 1533.39 | 679.93 | 801.76 | 346.89 | 490.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2586.24 | 1020.68 | 1797.57 | 1281.98 | 515.59 | 0.00 | 0.00 |
February | 2398.88 | 874.15 | 1630.29 | 1055.26 | 575.03 | 0.00 | 0.00 |
March | 1577.52 | 770.48 | 1040.82 | 469.72 | 571.09 | 0.00 | 0.00 |
April | 1289.38 | 510.50 | 771.44 | 180.77 | 590.67 | 0.00 | 0.00 |
May | 1217.40 | 144.51 | 589.44 | 25.05 | 564.39 | 0.00 | 0.00 |
June | 1240.96 | 123.99 | 582.26 | 5.43 | 576.83 | 0.00 | 0.00 |
July | 1290.09 | 79.35 | 609.53 | 11.20 | 598.33 | 0.00 | 0.00 |
August | 1523.92 | 118.84 | 717.08 | 86.07 | 631.01 | 0.00 | 0.00 |
September | 1685.41 | 173.86 | 860.38 | 226.75 | 633.63 | 0.00 | 0.00 |
October | 2403.98 | 328.02 | 1334.89 | 695.35 | 639.54 | 0.00 | 0.00 |
November | 2646.14 | 691.63 | 1698.73 | 1169.59 | 529.14 | 0.00 | 0.00 |
December | 2624.32 | 903.45 | 1756.44 | 1261.38 | 495.06 | 0.00 | 0.00 |
Annual Sum or Average | 1871.10 | 476.17 | 1113.02 | 536.38 | 576.64 | 0.00 | 0.00 |
Minimum of Months | 1217.40 | 79.35 | 582.26 | 5.43 | 495.06 | 0.00 | 0.00 |
Maximum of Months | 2646.14 | 1020.68 | 1797.57 | 1281.98 | 639.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 736.51 | 714.90 | 567.54 | 306.90 | 260.65 | 0.00 | 0.00 |
February | 865.29 | 606.16 | 642.58 | 325.24 | 317.35 | 0.00 | 0.00 |
March | 884.53 | 521.17 | 633.33 | 280.36 | 352.97 | 0.00 | 0.00 |
April | 1238.44 | 343.58 | 786.62 | 361.86 | 424.76 | 0.00 | 0.00 |
May | 1248.76 | 105.07 | 654.16 | 213.10 | 441.07 | 0.00 | 0.00 |
June | 1413.94 | 91.36 | 726.70 | 254.82 | 471.89 | 0.00 | 0.00 |
July | 1296.04 | 61.04 | 663.34 | 184.00 | 479.34 | 0.00 | 0.00 |
August | 1311.02 | 84.89 | 670.72 | 205.32 | 465.41 | 0.00 | 0.00 |
September | 1143.35 | 119.58 | 617.62 | 211.87 | 405.75 | 0.00 | 0.00 |
October | 1123.25 | 221.76 | 632.32 | 273.22 | 359.10 | 0.00 | 0.00 |
November | 798.81 | 478.66 | 541.97 | 272.37 | 269.60 | 0.00 | 0.00 |
December | 712.67 | 614.31 | 521.33 | 277.24 | 244.09 | 0.00 | 0.00 |
Annual Sum or Average | 1065.10 | 328.73 | 637.82 | 263.23 | 374.59 | 0.00 | 0.00 |
Minimum of Months | 712.67 | 61.04 | 521.33 | 184.00 | 244.09 | 0.00 | 0.00 |
Maximum of Months | 1413.94 | 714.90 | 786.62 | 361.86 | 479.34 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.667273E+09 | 0.272543E+10 | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.00 | 0.00 |
February | 0.801839E+09 | 0.205876E+10 | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.00 | 0.00 |
March | 0.123951E+10 | 0.196844E+10 | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.00 | 0.00 |
April | 0.182057E+10 | 0.122455E+10 | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.00 | 0.00 |
May | 0.308134E+10 | 0.376198E+09 | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.00 | 0.00 |
June | 0.352424E+10 | 0.314097E+09 | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.00 | 0.00 |
July | 0.349773E+10 | 0.222358E+09 | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.00 | 0.00 |
August | 0.316839E+10 | 0.302548E+09 | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.00 | 0.00 |
September | 0.243602E+10 | 0.412546E+09 | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.00 | 0.00 |
October | 0.204615E+10 | 0.801209E+09 | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.00 | 0.00 |
November | 0.948650E+09 | 0.170668E+10 | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.00 | 0.00 |
December | 0.707252E+09 | 0.231729E+10 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239389E+11 | 0.144301E+11 | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.667273E+09 | 0.222358E+09 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Maximum of Months | 0.352424E+10 | 0.272543E+10 | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175211E+10 | 0.169925E+10 | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.00 | 0.00 |
February | 0.185138E+10 | 0.129432E+10 | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.00 | 0.00 |
March | 0.257810E+10 | 0.125153E+10 | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.00 | 0.00 |
April | 0.307897E+10 | 0.809519E+09 | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.00 | 0.00 |
May | 0.389982E+10 | 0.254845E+09 | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.00 | 0.00 |
June | 0.396018E+10 | 0.212913E+09 | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.00 | 0.00 |
July | 0.394508E+10 | 0.149528E+09 | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.00 | 0.00 |
August | 0.364642E+10 | 0.205839E+09 | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.00 | 0.00 |
September | 0.297770E+10 | 0.278340E+09 | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.00 | 0.00 |
October | 0.290077E+10 | 0.527366E+09 | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.00 | 0.00 |
November | 0.202478E+10 | 0.108846E+10 | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.00 | 0.00 |
December | 0.148718E+10 | 0.148574E+10 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341025E+11 | 0.925765E+10 | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148718E+10 | 0.149528E+09 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Maximum of Months | 0.396018E+10 | 0.169925E+10 | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.696458E+10 | 0.256525E+10 | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.00 | 0.00 |
February | 0.583174E+10 | 0.198661E+10 | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.00 | 0.00 |
March | 0.423727E+10 | 0.195378E+10 | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.00 | 0.00 |
April | 0.333489E+10 | 0.127087E+10 | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.00 | 0.00 |
May | 0.322926E+10 | 0.386469E+09 | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.00 | 0.00 |
June | 0.318163E+10 | 0.323966E+09 | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.00 | 0.00 |
July | 0.341363E+10 | 0.216511E+09 | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.00 | 0.00 |
August | 0.404904E+10 | 0.316454E+09 | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.00 | 0.00 |
September | 0.434337E+10 | 0.437740E+09 | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.00 | 0.00 |
October | 0.642270E+10 | 0.843713E+09 | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.687969E+10 | 0.168755E+10 | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.00 | 0.00 |
December | 0.705783E+10 | 0.226484E+10 | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.589456E+11 | 0.142538E+11 | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.00 | 0.00 |
Minimum of Months | 0.318163E+10 | 0.216511E+09 | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.705783E+10 | 0.256525E+10 | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199196E+10 | 0.178968E+10 | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.00 | 0.00 |
February | 0.210773E+10 | 0.137076E+10 | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.00 | 0.00 |
March | 0.237485E+10 | 0.131746E+10 | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.00 | 0.00 |
April | 0.320352E+10 | 0.854294E+09 | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.00 | 0.00 |
May | 0.332299E+10 | 0.280814E+09 | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.00 | 0.00 |
June | 0.364067E+10 | 0.237481E+09 | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.00 | 0.00 |
July | 0.344403E+10 | 0.165834E+09 | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.00 | 0.00 |
August | 0.348935E+10 | 0.226377E+09 | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.00 | 0.00 |
September | 0.294752E+10 | 0.301721E+09 | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.00 | 0.00 |
October | 0.300001E+10 | 0.569028E+09 | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.00 | 0.00 |
November | 0.208454E+10 | 0.115687E+10 | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.00 | 0.00 |
December | 0.192721E+10 | 0.153029E+10 | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335344E+11 | 0.980061E+10 | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192721E+10 | 0.165834E+09 | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364067E+10 | 0.178968E+10 | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.641300E+09 | 0.295167E+10 | 0.832932E+09 | 0.00 | 0.832932E+09 | 0.00 | 0.00 |
February | 0.808440E+09 | 0.217856E+10 | 0.887563E+09 | 0.00 | 0.887563E+09 | 0.00 | 0.00 |
March | 0.128493E+10 | 0.201422E+10 | 0.113997E+10 | 0.00 | 0.113997E+10 | 0.00 | 0.00 |
April | 0.189061E+10 | 0.119453E+10 | 0.130202E+10 | 5343873.29 | 0.129667E+10 | 0.00 | 0.00 |
May | 0.316842E+10 | 0.323822E+09 | 0.152394E+10 | 55741683.63 | 0.146820E+10 | 0.00 | 0.00 |
June | 0.360224E+10 | 0.277028E+09 | 0.167714E+10 | 0.116128E+09 | 0.156101E+10 | 0.00 | 0.00 |
July | 0.356685E+10 | 0.201230E+09 | 0.168181E+10 | 64073192.84 | 0.161773E+10 | 0.00 | 0.00 |
August | 0.319242E+10 | 0.314216E+09 | 0.150609E+10 | 11845474.09 | 0.149424E+10 | 0.00 | 0.00 |
September | 0.245724E+10 | 0.445126E+09 | 0.125896E+10 | 96963.58 | 0.125886E+10 | 0.00 | 0.00 |
October | 0.204641E+10 | 0.872677E+09 | 0.113048E+10 | 0.00 | 0.113048E+10 | 0.00 | 0.00 |
November | 0.911181E+09 | 0.189951E+10 | 0.830528E+09 | 0.00 | 0.830528E+09 | 0.00 | 0.00 |
December | 0.670575E+09 | 0.256357E+10 | 0.774305E+09 | 0.00 | 0.774305E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.242406E+11 | 0.152362E+11 | 0.145457E+11 | 0.253229E+09 | 0.142925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.641300E+09 | 0.201230E+09 | 0.774305E+09 | 0.00 | 0.774305E+09 | 0.00 | 0.00 |
Maximum of Months | 0.360224E+10 | 0.295167E+10 | 0.168181E+10 | 0.116128E+09 | 0.161773E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171927E+10 | 0.189024E+10 | 0.142911E+10 | 0.727705E+09 | 0.701404E+09 | 0.00 | 0.00 |
February | 0.184473E+10 | 0.140625E+10 | 0.143736E+10 | 0.693915E+09 | 0.743443E+09 | 0.00 | 0.00 |
March | 0.260395E+10 | 0.132135E+10 | 0.187196E+10 | 0.902793E+09 | 0.969170E+09 | 0.00 | 0.00 |
April | 0.312557E+10 | 0.821381E+09 | 0.198800E+10 | 0.899112E+09 | 0.108888E+10 | 0.00 | 0.00 |
May | 0.395930E+10 | 0.240347E+09 | 0.211739E+10 | 0.918137E+09 | 0.119925E+10 | 0.00 | 0.00 |
June | 0.401221E+10 | 0.202233E+09 | 0.207812E+10 | 0.824122E+09 | 0.125400E+10 | 0.00 | 0.00 |
July | 0.398739E+10 | 0.150938E+09 | 0.207039E+10 | 0.757649E+09 | 0.131274E+10 | 0.00 | 0.00 |
August | 0.366599E+10 | 0.227745E+09 | 0.190780E+10 | 0.655914E+09 | 0.125189E+10 | 0.00 | 0.00 |
September | 0.299414E+10 | 0.317325E+09 | 0.163545E+10 | 0.562259E+09 | 0.107319E+10 | 0.00 | 0.00 |
October | 0.290933E+10 | 0.592722E+09 | 0.167003E+10 | 0.704744E+09 | 0.965286E+09 | 0.00 | 0.00 |
November | 0.200057E+10 | 0.123186E+10 | 0.143087E+10 | 0.729942E+09 | 0.700932E+09 | 0.00 | 0.00 |
December | 0.145739E+10 | 0.167237E+10 | 0.116414E+10 | 0.527328E+09 | 0.636814E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342798E+11 | 0.100748E+11 | 0.208006E+11 | 0.890362E+10 | 0.118970E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145739E+10 | 0.150938E+09 | 0.116414E+10 | 0.527328E+09 | 0.636814E+09 | 0.00 | 0.00 |
Maximum of Months | 0.401221E+10 | 0.189024E+10 | 0.211739E+10 | 0.918137E+09 | 0.131274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.698616E+10 | 0.287160E+10 | 0.481442E+10 | 0.343351E+10 | 0.138091E+10 | 0.00 | 0.00 |
February | 0.586983E+10 | 0.217906E+10 | 0.394386E+10 | 0.255278E+10 | 0.139107E+10 | 0.00 | 0.00 |
March | 0.431922E+10 | 0.202614E+10 | 0.278762E+10 | 0.125805E+10 | 0.152957E+10 | 0.00 | 0.00 |
April | 0.341773E+10 | 0.125679E+10 | 0.199951E+10 | 0.468529E+09 | 0.153098E+10 | 0.00 | 0.00 |
May | 0.330440E+10 | 0.338743E+09 | 0.157870E+10 | 67091601.99 | 0.151161E+10 | 0.00 | 0.00 |
June | 0.324579E+10 | 0.284919E+09 | 0.150918E+10 | 14066812.28 | 0.149511E+10 | 0.00 | 0.00 |
July | 0.346775E+10 | 0.200137E+09 | 0.163253E+10 | 30005281.65 | 0.160252E+10 | 0.00 | 0.00 |
August | 0.405964E+10 | 0.340810E+09 | 0.192058E+10 | 0.230525E+09 | 0.169005E+10 | 0.00 | 0.00 |
September | 0.436094E+10 | 0.496007E+09 | 0.223003E+10 | 0.587703E+09 | 0.164233E+10 | 0.00 | 0.00 |
October | 0.642650E+10 | 0.963413E+09 | 0.357523E+10 | 0.186235E+10 | 0.171288E+10 | 0.00 | 0.00 |
November | 0.687121E+10 | 0.193516E+10 | 0.440294E+10 | 0.303146E+10 | 0.137148E+10 | 0.00 | 0.00 |
December | 0.706543E+10 | 0.256222E+10 | 0.470428E+10 | 0.337835E+10 | 0.132592E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.593946E+11 | 0.154550E+11 | 0.350989E+11 | 0.169144E+11 | 0.181844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.324579E+10 | 0.200137E+09 | 0.150918E+10 | 14066812.28 | 0.132592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.706543E+10 | 0.287160E+10 | 0.481442E+10 | 0.343351E+10 | 0.171288E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197728E+10 | 0.199062E+10 | 0.152009E+10 | 0.821976E+09 | 0.698110E+09 | 0.00 | 0.00 |
February | 0.211407E+10 | 0.149420E+10 | 0.155452E+10 | 0.786799E+09 | 0.767721E+09 | 0.00 | 0.00 |
March | 0.240412E+10 | 0.139524E+10 | 0.169630E+10 | 0.750905E+09 | 0.945391E+09 | 0.00 | 0.00 |
April | 0.325232E+10 | 0.872968E+09 | 0.203888E+10 | 0.937920E+09 | 0.110096E+10 | 0.00 | 0.00 |
May | 0.337635E+10 | 0.260245E+09 | 0.175209E+10 | 0.570745E+09 | 0.118135E+10 | 0.00 | 0.00 |
June | 0.368988E+10 | 0.225982E+09 | 0.188359E+10 | 0.660471E+09 | 0.122311E+10 | 0.00 | 0.00 |
July | 0.348607E+10 | 0.163365E+09 | 0.177667E+10 | 0.492819E+09 | 0.128385E+10 | 0.00 | 0.00 |
August | 0.350794E+10 | 0.247699E+09 | 0.179644E+10 | 0.549913E+09 | 0.124653E+10 | 0.00 | 0.00 |
September | 0.296050E+10 | 0.339897E+09 | 0.160086E+10 | 0.549168E+09 | 0.105169E+10 | 0.00 | 0.00 |
October | 0.300464E+10 | 0.635977E+09 | 0.169358E+10 | 0.731774E+09 | 0.961804E+09 | 0.00 | 0.00 |
November | 0.206403E+10 | 0.131402E+10 | 0.140477E+10 | 0.705980E+09 | 0.698793E+09 | 0.00 | 0.00 |
December | 0.190587E+10 | 0.173325E+10 | 0.139631E+10 | 0.742538E+09 | 0.653775E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.337431E+11 | 0.106735E+11 | 0.201141E+11 | 0.830101E+10 | 0.118131E+11 | 0.00 | 0.00 |
Minimum of Months | 0.190587E+10 | 0.163365E+09 | 0.139631E+10 | 0.492819E+09 | 0.653775E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368988E+10 | 0.199062E+10 | 0.203888E+10 | 0.937920E+09 | 0.128385E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.635619E+09 | 0.292036E+10 | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.00 | 0.00 |
February | 0.776756E+09 | 0.220734E+10 | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.00 | 0.00 |
March | 0.122478E+10 | 0.208729E+10 | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.00 | 0.00 |
April | 0.182223E+10 | 0.127720E+10 | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.00 | 0.00 |
May | 0.311262E+10 | 0.375898E+09 | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.00 | 0.00 |
June | 0.356012E+10 | 0.311979E+09 | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.00 | 0.00 |
July | 0.353918E+10 | 0.217456E+09 | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.00 | 0.00 |
August | 0.319925E+10 | 0.304264E+09 | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.00 | 0.00 |
September | 0.246016E+10 | 0.425284E+09 | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.00 | 0.00 |
October | 0.205480E+10 | 0.840777E+09 | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.00 | 0.00 |
November | 0.921288E+09 | 0.184020E+10 | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.00 | 0.00 |
December | 0.676980E+09 | 0.249881E+10 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239838E+11 | 0.153069E+11 | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.635619E+09 | 0.217456E+09 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Maximum of Months | 0.356012E+10 | 0.292036E+10 | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170667E+10 | 0.182113E+10 | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.00 | 0.00 |
February | 0.181709E+10 | 0.138432E+10 | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.00 | 0.00 |
March | 0.255755E+10 | 0.132199E+10 | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.00 | 0.00 |
April | 0.307341E+10 | 0.840521E+09 | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.00 | 0.00 |
May | 0.391262E+10 | 0.256464E+09 | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.00 | 0.00 |
June | 0.397456E+10 | 0.212499E+09 | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.00 | 0.00 |
July | 0.396236E+10 | 0.147796E+09 | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.00 | 0.00 |
August | 0.365754E+10 | 0.208082E+09 | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.00 | 0.00 |
September | 0.298464E+10 | 0.288114E+09 | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.00 | 0.00 |
October | 0.289975E+10 | 0.551993E+09 | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.00 | 0.00 |
November | 0.199617E+10 | 0.116314E+10 | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.00 | 0.00 |
December | 0.145181E+10 | 0.159910E+10 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339942E+11 | 0.979515E+10 | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145181E+10 | 0.147796E+09 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Maximum of Months | 0.397456E+10 | 0.182113E+10 | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.692699E+10 | 0.273378E+10 | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.00 | 0.00 |
February | 0.580338E+10 | 0.211475E+10 | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.00 | 0.00 |
March | 0.422523E+10 | 0.206365E+10 | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.00 | 0.00 |
April | 0.334208E+10 | 0.132321E+10 | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.00 | 0.00 |
May | 0.326068E+10 | 0.387062E+09 | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.00 | 0.00 |
June | 0.321658E+10 | 0.321392E+09 | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.00 | 0.00 |
July | 0.345536E+10 | 0.212528E+09 | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.00 | 0.00 |
August | 0.408167E+10 | 0.318303E+09 | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.00 | 0.00 |
September | 0.436858E+10 | 0.450633E+09 | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.00 | 0.00 |
October | 0.643882E+10 | 0.878558E+09 | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.685878E+10 | 0.179269E+10 | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.00 | 0.00 |
December | 0.702899E+10 | 0.241980E+10 | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.590071E+11 | 0.150163E+11 | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321658E+10 | 0.212528E+09 | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.702899E+10 | 0.273378E+10 | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197266E+10 | 0.191478E+10 | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.00 | 0.00 |
February | 0.209331E+10 | 0.146643E+10 | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.00 | 0.00 |
March | 0.236913E+10 | 0.139591E+10 | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.00 | 0.00 |
April | 0.321003E+10 | 0.890572E+09 | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.00 | 0.00 |
May | 0.334467E+10 | 0.281417E+09 | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.00 | 0.00 |
June | 0.366494E+10 | 0.236804E+09 | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.00 | 0.00 |
July | 0.347132E+10 | 0.163494E+09 | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.00 | 0.00 |
August | 0.351143E+10 | 0.227380E+09 | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.00 | 0.00 |
September | 0.296357E+10 | 0.309948E+09 | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.00 | 0.00 |
October | 0.300852E+10 | 0.593961E+09 | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.00 | 0.00 |
November | 0.207051E+10 | 0.124068E+10 | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.00 | 0.00 |
December | 0.190883E+10 | 0.164537E+10 | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335889E+11 | 0.103667E+11 | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.190883E+10 | 0.163494E+09 | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.00 | 0.00 |
Maximum of Months | 0.366494E+10 | 0.191478E+10 | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.434287E+10 | -0.363798E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -704892467.6 | 58.99 | 0.00 | 0.00 |
February | 0.391501E+10 | -0.327964E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -635369709.1 | 58.98 | 0.00 | 0.00 |
March | 0.443536E+10 | -0.373322E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -702137535.2 | 58.98 | 0.00 | 0.00 |
April | 0.382439E+10 | -0.315319E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671200307.5 | 58.97 | 0.00 | 0.00 |
May | 0.383657E+10 | -0.314521E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691358862.0 | 58.98 | 0.00 | 0.00 |
June | 0.359929E+10 | -0.292935E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669940743.5 | 58.98 | 0.00 | 0.00 |
July | 0.336242E+10 | -0.267092E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691506733.4 | 58.98 | 0.00 | 0.00 |
August | 0.367893E+10 | -0.298683E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692106429.6 | 58.98 | 0.00 | 0.00 |
September | 0.349798E+10 | -0.282845E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669526837.4 | 58.98 | 0.00 | 0.00 |
October | 0.382644E+10 | -0.313547E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690969111.9 | 58.98 | 0.00 | 0.00 |
November | 0.398112E+10 | -0.330875E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -672373868.4 | 58.98 | 0.00 | 0.00 |
December | 0.415302E+10 | -0.345217E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -700845386.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.464534E+11 | -0.382612E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.819223E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.336242E+10 | -0.373322E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -704892467.6 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.443536E+10 | -0.267092E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -635369709.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7752.17 | 36.70 | 297.50 | 296.00 | 1463.51 | 25.13 | 176.33 | 279.17 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3354.93 | 27.25 | 165.50 | 279.00 | 1216.03 | 20.64 | 107.67 | 260.67 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1553.90 | 18.36 | 0.00 | 319.33 | 924.33 | 20.54 | 111.50 | 281.00 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1220.34 | 17.62 | 0.00 | 322.00 | 712.27 | 19.75 | 87.33 | 282.50 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:19 | 1084.81 | 17.86 | 0.00 | 347.83 | 616.06 | 20.03 | 62.67 | 297.83 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:00 | 1028.54 | 17.50 | 0.00 | 349.00 | 587.18 | 19.67 | 44.83 | 301.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1138.50 | 17.85 | 0.00 | 359.00 | 631.07 | 20.00 | 87.50 | 311.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1329.04 | 18.14 | 0.00 | 345.50 | 724.05 | 20.27 | 134.17 | 307.17 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1571.23 | 18.29 | 0.00 | 316.83 | 845.87 | 20.44 | 154.50 | 281.50 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2660.56 | 21.04 | 39.33 | 313.33 | 1159.99 | 21.60 | 186.83 | 283.67 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-08:20 | 7818.87 | 36.12 | 297.00 | 287.67 | 1313.55 | 22.82 | 143.50 | 268.33 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7903.44 | 37.49 | 279.33 | 284.17 | 1853.63 | 27.07 | 170.83 | 267.17 |
Annual Sum or Average | 4027.67 | 0.51 | 2993.28 | 23.07 | 1078.67 | 3819.67 | 968.87 | 21.33 | 1467.67 | 3422.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1028.54 | 17.50 | 0.00 | 279.00 | 587.18 | 19.67 | 44.83 | 260.67 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7903.44 | 37.49 | 297.50 | 359.00 | 1853.63 | 27.07 | 186.83 | 311.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1895.54 | 19.70 | 81.50 | 267.33 | 1067.49 | 22.40 | 74.67 | 214.50 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:39 | 2172.26 | 21.58 | 89.67 | 257.83 | 1160.69 | 22.44 | 66.33 | 223.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2227.11 | 20.17 | 74.33 | 313.00 | 1175.53 | 21.09 | 48.00 | 270.83 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:10 | 2314.44 | 20.42 | 95.83 | 323.00 | 1236.42 | 21.46 | 68.00 | 289.50 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2610.40 | 21.08 | 106.00 | 356.67 | 1048.11 | 20.58 | 49.50 | 310.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2336.78 | 20.52 | 114.00 | 355.83 | 996.87 | 21.11 | 62.67 | 317.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2257.38 | 20.78 | 112.33 | 362.33 | 978.77 | 20.53 | 53.67 | 314.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2081.18 | 20.69 | 105.17 | 345.83 | 1092.32 | 21.82 | 76.00 | 304.83 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 1983.51 | 20.76 | 95.00 | 312.50 | 1024.74 | 21.85 | 67.67 | 275.00 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-06:49 | 2048.79 | 20.23 | 79.17 | 299.33 | 1068.50 | 21.95 | 58.17 | 266.17 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-07:49 | 1721.23 | 20.55 | 84.00 | 261.83 | 890.18 | 21.31 | 57.00 | 224.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1853.89 | 21.40 | 89.17 | 252.83 | 996.52 | 22.12 | 66.50 | 202.33 |
Annual Sum or Average | 4027.67 | 0.51 | 2138.63 | 20.65 | 1126.17 | 3708.33 | 1059.89 | 21.52 | 748.17 | 3212.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1721.23 | 19.70 | 74.33 | 252.83 | 890.18 | 20.53 | 48.00 | 202.33 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2610.40 | 21.58 | 114.00 | 362.33 | 1236.42 | 22.44 | 76.00 | 317.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:00 | 515.56 | 14.55 | 0.00 | 247.00 | 336.83 | 17.05 | 0.00 | 149.50 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 595.04 | 15.75 | 0.00 | 245.00 | 390.01 | 18.17 | 0.00 | 177.50 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 698.48 | 16.85 | 0.00 | 304.00 | 442.33 | 19.06 | 0.00 | 230.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 834.98 | 17.31 | 0.00 | 325.00 | 512.20 | 19.42 | 14.50 | 282.50 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1033.76 | 19.60 | 27.17 | 369.67 | 596.40 | 20.65 | 83.17 | 326.00 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:19 | 1201.53 | 20.82 | 58.00 | 373.67 | 648.25 | 22.89 | 174.33 | 344.83 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:40 | 1174.53 | 19.37 | 23.67 | 376.17 | 643.72 | 21.49 | 142.67 | 339.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1027.59 | 18.04 | 0.00 | 352.67 | 582.48 | 20.14 | 61.83 | 316.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 858.27 | 17.24 | 0.00 | 314.33 | 497.55 | 19.33 | 8.83 | 263.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 735.29 | 16.97 | 0.00 | 294.83 | 453.89 | 19.23 | 0.00 | 240.50 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-09:50 | 529.45 | 15.13 | 0.00 | 238.50 | 347.87 | 17.63 | 0.00 | 157.67 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:39 | 515.80 | 14.78 | 0.00 | 238.33 | 338.97 | 17.35 | 0.00 | 138.83 |
Annual Sum or Average | 4027.67 | 0.52 | 835.41 | 17.39 | 108.83 | 3679.17 | 494.05 | 19.53 | 485.33 | 2967.50 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 515.56 | 14.55 | 0.00 | 238.33 | 336.83 | 17.05 | 0.00 | 138.83 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1201.53 | 20.82 | 58.00 | 376.17 | 648.25 | 22.89 | 174.33 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:00 | 2251.14 | 22.57 | 109.33 | 272.17 | 1257.22 | 23.11 | 82.33 | 222.83 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 1977.49 | 20.42 | 79.17 | 263.33 | 1040.03 | 21.18 | 51.33 | 230.00 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2103.07 | 19.41 | 68.83 | 308.50 | 1135.98 | 21.79 | 56.67 | 264.00 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:20 | 2428.10 | 19.12 | 82.00 | 324.67 | 1284.27 | 20.20 | 53.00 | 290.33 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:49 | 2004.58 | 14.74 | 0.00 | 354.00 | 889.67 | 18.06 | 0.00 | 313.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2116.81 | 14.64 | 0.00 | 355.50 | 908.81 | 17.90 | 0.00 | 314.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 1957.50 | 15.18 | 3.67 | 363.17 | 875.55 | 18.18 | 0.00 | 319.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2020.61 | 17.66 | 59.00 | 347.50 | 934.04 | 18.42 | 5.50 | 306.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1856.02 | 19.40 | 80.67 | 311.33 | 971.96 | 20.50 | 52.50 | 275.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:49 | 2415.04 | 22.44 | 108.83 | 307.33 | 1004.36 | 21.72 | 53.50 | 269.83 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1942.14 | 21.35 | 93.50 | 263.83 | 1055.75 | 22.27 | 66.67 | 225.67 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:39 | 2031.78 | 21.46 | 88.00 | 267.50 | 1142.70 | 23.62 | 75.67 | 215.17 |
Annual Sum or Average | 4027.67 | 0.51 | 2091.25 | 18.79 | 773.00 | 3738.83 | 1032.44 | 20.38 | 497.17 | 3246.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1856.02 | 14.64 | 0.00 | 263.33 | 875.55 | 17.90 | 0.00 | 215.17 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2428.10 | 22.57 | 109.33 | 363.17 | 1284.27 | 23.62 | 82.33 | 319.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7617.78 | 36.43 | 297.33 | 295.67 | 1355.13 | 22.68 | 92.17 | 276.50 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3236.74 | 25.18 | 165.33 | 277.83 | 1170.33 | 19.92 | 36.50 | 264.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1474.36 | 14.65 | 0.00 | 316.00 | 865.88 | 18.25 | 0.17 | 277.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1169.01 | 14.10 | 0.00 | 319.67 | 678.65 | 17.56 | 0.00 | 279.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:30 | 1044.37 | 14.25 | 0.00 | 344.67 | 592.09 | 17.75 | 0.00 | 293.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:00 | 991.09 | 13.89 | 0.00 | 347.33 | 565.47 | 17.37 | 0.00 | 296.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1096.40 | 14.15 | 0.00 | 356.83 | 606.07 | 17.60 | 0.00 | 306.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1276.43 | 14.46 | 0.00 | 344.00 | 690.97 | 17.87 | 0.00 | 302.83 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1503.38 | 14.52 | 0.00 | 314.83 | 800.80 | 17.94 | 0.00 | 278.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2555.17 | 17.54 | 39.33 | 312.33 | 1082.64 | 19.00 | 7.17 | 281.67 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-08:20 | 7693.55 | 35.84 | 296.17 | 286.67 | 1214.07 | 20.08 | 46.00 | 267.33 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7759.60 | 37.28 | 279.33 | 283.33 | 1737.31 | 24.82 | 111.00 | 265.50 |
Annual Sum or Average | 4027.67 | 0.51 | 2913.73 | 20.30 | 1077.50 | 3799.17 | 914.33 | 19.06 | 293.00 | 3389.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 991.09 | 13.89 | 0.00 | 277.83 | 565.47 | 17.37 | 0.00 | 264.83 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7759.60 | 37.28 | 297.33 | 356.83 | 1737.31 | 24.82 | 111.00 | 306.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1843.41 | 19.21 | 81.50 | 264.50 | 1026.57 | 22.19 | 72.33 | 210.83 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:39 | 2116.59 | 21.10 | 89.67 | 255.67 | 1118.40 | 22.24 | 65.17 | 220.50 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2163.22 | 19.69 | 74.33 | 310.50 | 1119.60 | 20.90 | 47.83 | 266.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:10 | 2244.30 | 19.97 | 95.83 | 320.83 | 1186.76 | 21.29 | 68.00 | 286.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2540.02 | 20.63 | 106.00 | 354.17 | 995.74 | 20.37 | 49.17 | 306.17 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2281.06 | 20.08 | 114.00 | 352.83 | 940.91 | 20.16 | 54.00 | 312.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2198.02 | 20.34 | 112.33 | 361.00 | 932.12 | 20.38 | 53.67 | 311.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2007.72 | 20.05 | 103.00 | 344.50 | 1048.00 | 21.65 | 75.83 | 300.50 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-06:49 | 1902.34 | 18.91 | 80.50 | 309.00 | 982.06 | 21.66 | 67.50 | 272.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-06:49 | 1986.68 | 19.74 | 79.17 | 298.33 | 1021.61 | 21.74 | 57.00 | 264.50 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-07:49 | 1668.72 | 20.06 | 84.00 | 258.50 | 850.18 | 21.09 | 55.50 | 221.33 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-07:49 | 1802.45 | 20.76 | 87.83 | 250.00 | 960.83 | 21.90 | 62.83 | 199.67 |
Annual Sum or Average | 4027.67 | 0.51 | 2075.89 | 20.04 | 1108.17 | 3679.83 | 1013.46 | 21.25 | 728.83 | 3171.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1668.72 | 18.91 | 74.33 | 250.00 | 850.18 | 20.16 | 47.83 | 199.67 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2540.02 | 21.10 | 114.00 | 361.00 | 1186.76 | 22.24 | 75.83 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:00 | 496.75 | 11.11 | 0.00 | 241.33 | 327.21 | 14.83 | 0.00 | 140.33 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 573.71 | 12.36 | 0.00 | 242.00 | 379.15 | 16.08 | 0.00 | 171.33 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 674.19 | 13.61 | 0.00 | 300.17 | 429.66 | 17.17 | 0.00 | 222.67 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:00 | 805.92 | 13.99 | 0.00 | 323.83 | 496.55 | 17.47 | 0.00 | 277.67 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:00 | 991.15 | 14.88 | 2.17 | 365.00 | 579.10 | 19.63 | 27.50 | 325.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:19 | 1159.29 | 17.78 | 58.00 | 372.00 | 623.12 | 20.94 | 59.83 | 340.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:40 | 1132.00 | 15.94 | 23.50 | 374.00 | 618.54 | 19.29 | 24.67 | 335.67 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 990.30 | 14.47 | 0.00 | 351.00 | 560.94 | 17.92 | 0.00 | 312.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:19 | 827.70 | 13.78 | 0.00 | 312.00 | 480.32 | 17.17 | 0.00 | 256.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:40 | 708.69 | 13.60 | 0.00 | 293.17 | 439.62 | 17.17 | 0.00 | 236.17 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-09:00 | 510.09 | 11.64 | 0.00 | 233.33 | 338.00 | 15.42 | 0.00 | 150.00 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:50 | 496.53 | 11.27 | 0.00 | 232.17 | 329.12 | 15.08 | 0.00 | 128.50 |
Annual Sum or Average | 4027.67 | 0.52 | 804.99 | 13.88 | 83.67 | 3640.00 | 477.71 | 17.52 | 112.00 | 2896.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 496.53 | 11.11 | 0.00 | 232.17 | 327.21 | 14.83 | 0.00 | 128.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1159.29 | 17.78 | 58.00 | 374.00 | 623.12 | 20.94 | 59.83 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-09:09 | 2200.22 | 22.19 | 109.33 | 270.33 | 1215.59 | 23.00 | 82.17 | 219.50 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 1913.97 | 20.00 | 79.17 | 261.17 | 991.28 | 21.06 | 51.17 | 226.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2045.92 | 18.95 | 68.83 | 306.33 | 1087.44 | 21.66 | 56.67 | 260.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:30 | 2358.98 | 18.66 | 82.00 | 323.00 | 1233.03 | 20.04 | 53.00 | 287.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:49 | 1943.34 | 14.18 | 0.00 | 352.17 | 848.55 | 17.86 | 0.00 | 309.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2062.41 | 14.08 | 0.00 | 354.00 | 861.25 | 17.69 | 0.00 | 309.00 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:10 | 1900.33 | 14.62 | 3.67 | 361.67 | 835.87 | 17.97 | 0.00 | 315.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 1957.67 | 17.17 | 59.00 | 346.00 | 891.49 | 18.24 | 5.50 | 302.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:49 | 1806.67 | 18.96 | 80.50 | 309.17 | 930.44 | 20.36 | 52.17 | 271.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:00 | 2346.74 | 21.75 | 105.67 | 305.50 | 957.38 | 21.60 | 53.50 | 267.00 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1837.22 | 19.49 | 80.00 | 261.00 | 1015.67 | 22.16 | 66.67 | 222.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1966.19 | 20.71 | 85.00 | 264.83 | 1098.81 | 23.53 | 75.33 | 211.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2027.94 | 18.16 | 753.17 | 3715.17 | 988.04 | 20.23 | 496.17 | 3201.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1806.67 | 14.08 | 0.00 | 261.00 | 835.87 | 17.69 | 0.00 | 211.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2358.98 | 22.19 | 109.33 | 361.67 | 1233.03 | 23.53 | 82.17 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7617.73 | 36.43 | 297.33 | 295.67 | 1355.06 | 22.68 | 92.17 | 276.50 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3236.67 | 25.19 | 165.33 | 277.83 | 1170.26 | 19.92 | 36.50 | 264.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1474.29 | 14.65 | 0.00 | 316.00 | 865.82 | 18.25 | 0.17 | 277.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1168.95 | 14.10 | 0.00 | 319.67 | 678.61 | 17.56 | 0.00 | 279.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:30 | 1044.32 | 14.25 | 0.00 | 344.67 | 592.04 | 17.75 | 0.00 | 293.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:00 | 991.03 | 13.89 | 0.00 | 347.33 | 565.43 | 17.37 | 0.00 | 296.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1096.34 | 14.15 | 0.00 | 356.83 | 606.03 | 17.60 | 0.00 | 306.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1276.35 | 14.46 | 0.00 | 344.00 | 690.92 | 17.87 | 0.00 | 302.83 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1503.28 | 14.52 | 0.00 | 314.83 | 800.73 | 17.94 | 0.00 | 278.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2555.07 | 17.54 | 39.33 | 312.33 | 1082.56 | 19.00 | 7.17 | 281.67 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-08:20 | 7693.48 | 35.84 | 296.17 | 286.67 | 1213.99 | 20.08 | 46.00 | 267.33 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7759.56 | 37.28 | 279.33 | 283.33 | 1737.23 | 24.82 | 111.00 | 265.50 |
Annual Sum or Average | 4027.67 | 0.51 | 2913.67 | 20.30 | 1077.50 | 3799.17 | 914.27 | 19.06 | 293.00 | 3389.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 991.03 | 13.89 | 0.00 | 277.83 | 565.43 | 17.37 | 0.00 | 264.83 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7759.56 | 37.28 | 297.33 | 356.83 | 1737.23 | 24.82 | 111.00 | 306.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1843.40 | 19.21 | 81.50 | 264.50 | 1026.53 | 22.19 | 72.33 | 210.83 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:39 | 2116.57 | 21.10 | 89.67 | 255.67 | 1118.36 | 22.24 | 65.17 | 220.50 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2163.19 | 19.69 | 74.33 | 310.50 | 1119.55 | 20.90 | 47.83 | 266.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:10 | 2244.26 | 19.98 | 95.83 | 320.83 | 1186.71 | 21.29 | 68.00 | 286.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2539.97 | 20.63 | 106.00 | 354.17 | 995.69 | 20.37 | 49.17 | 306.17 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2281.00 | 20.08 | 114.00 | 352.83 | 940.85 | 20.16 | 54.00 | 312.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2197.94 | 20.34 | 112.33 | 361.00 | 932.05 | 20.38 | 53.67 | 311.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2007.65 | 20.06 | 103.00 | 344.50 | 1047.94 | 21.65 | 75.83 | 300.50 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-06:49 | 1902.27 | 18.91 | 80.50 | 309.00 | 982.00 | 21.66 | 67.50 | 272.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-06:49 | 1986.64 | 19.74 | 79.17 | 298.33 | 1021.55 | 21.74 | 57.00 | 264.50 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-07:49 | 1668.70 | 20.07 | 84.00 | 258.50 | 850.14 | 21.09 | 55.50 | 221.33 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-07:49 | 1802.44 | 20.76 | 87.83 | 250.00 | 960.79 | 21.90 | 62.83 | 199.67 |
Annual Sum or Average | 4027.67 | 0.51 | 2075.85 | 20.04 | 1108.17 | 3679.83 | 1013.41 | 21.25 | 728.83 | 3171.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1668.70 | 18.91 | 74.33 | 250.00 | 850.14 | 20.16 | 47.83 | 199.67 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2539.97 | 21.10 | 114.00 | 361.00 | 1186.71 | 22.24 | 75.83 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:00 | 496.75 | 11.11 | 0.00 | 241.33 | 327.20 | 14.84 | 0.00 | 140.33 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 573.70 | 12.37 | 0.00 | 242.00 | 379.13 | 16.08 | 0.00 | 171.33 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 674.18 | 13.61 | 0.00 | 300.17 | 429.63 | 17.17 | 0.00 | 222.67 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:00 | 805.89 | 14.00 | 0.00 | 323.83 | 496.52 | 17.47 | 0.00 | 277.67 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:00 | 991.10 | 14.88 | 2.17 | 365.00 | 579.06 | 19.64 | 27.50 | 325.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:19 | 1159.24 | 17.78 | 58.00 | 372.00 | 623.07 | 20.95 | 59.83 | 340.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:40 | 1131.94 | 15.94 | 23.50 | 374.00 | 618.49 | 19.29 | 24.67 | 335.67 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 990.25 | 14.47 | 0.00 | 351.00 | 560.90 | 17.92 | 0.00 | 312.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:19 | 827.67 | 13.78 | 0.00 | 312.00 | 480.28 | 17.17 | 0.00 | 256.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:40 | 708.68 | 13.60 | 0.00 | 293.17 | 439.59 | 17.17 | 0.00 | 236.17 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-09:00 | 510.09 | 11.64 | 0.00 | 233.33 | 337.98 | 15.42 | 0.00 | 150.00 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:50 | 496.52 | 11.27 | 0.00 | 232.17 | 329.11 | 15.08 | 0.00 | 128.50 |
Annual Sum or Average | 4027.67 | 0.52 | 804.96 | 13.89 | 83.67 | 3640.00 | 477.67 | 17.52 | 112.00 | 2896.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 496.52 | 11.11 | 0.00 | 232.17 | 327.20 | 14.84 | 0.00 | 128.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1159.24 | 17.78 | 58.00 | 374.00 | 623.07 | 20.95 | 59.83 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-09:09 | 2200.20 | 22.19 | 109.33 | 270.33 | 1215.56 | 23.00 | 82.17 | 219.50 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 1913.95 | 20.01 | 79.17 | 261.17 | 991.23 | 21.06 | 51.17 | 226.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2045.89 | 18.96 | 68.83 | 306.33 | 1087.39 | 21.66 | 56.67 | 260.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:30 | 2358.94 | 18.66 | 82.00 | 323.00 | 1232.98 | 20.04 | 53.00 | 287.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:49 | 1943.29 | 14.18 | 0.00 | 352.17 | 848.49 | 17.86 | 0.00 | 309.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2062.35 | 14.09 | 0.00 | 354.00 | 861.19 | 17.69 | 0.00 | 309.00 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:10 | 1900.26 | 14.62 | 3.67 | 361.67 | 835.81 | 17.97 | 0.00 | 315.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 1957.60 | 17.17 | 59.00 | 346.00 | 891.43 | 18.24 | 5.50 | 302.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:49 | 1806.61 | 18.97 | 80.50 | 309.17 | 930.38 | 20.36 | 52.17 | 271.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:00 | 2346.71 | 21.75 | 105.67 | 305.50 | 957.32 | 21.60 | 53.50 | 267.00 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1837.20 | 19.49 | 80.00 | 261.00 | 1015.64 | 22.16 | 66.67 | 222.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1966.18 | 20.71 | 85.00 | 264.83 | 1098.77 | 23.53 | 75.50 | 211.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2027.89 | 18.16 | 753.17 | 3715.17 | 987.99 | 20.23 | 496.33 | 3201.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1806.61 | 14.09 | 0.00 | 261.00 | 835.81 | 17.69 | 0.00 | 211.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2358.94 | 22.19 | 109.33 | 361.67 | 1232.98 | 23.53 | 82.17 | 315.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.815008E+09 | 7461.78 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.523069E+09 | 7461.78 | 03-FEB-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.830876E+09 | 7461.78 | 02-MAR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168220E+09 | 7461.78 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21769993.24 | 5912.09 | 27-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215235E+09 | 7461.78 | 09-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.723884E+09 | 7461.78 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.830876E+09 | 7461.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22207265.86 | 4984.16 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17749737.30 | 4984.16 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42268752.70 | 4984.16 | 10-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21182858.52 | 4984.16 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42268752.70 | 4984.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160133E+09 | 7498.91 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122273E+09 | 7498.91 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116599E+09 | 7498.91 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 68772974.37 | 7498.91 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160133E+09 | 7498.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28938305.49 | 4959.58 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26439462.19 | 4959.58 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45079916.63 | 4959.58 | 10-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15089404.76 | 4959.58 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45079916.63 | 4959.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13026733.30 | 21249.48 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19570257.06 | 21249.48 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32596990.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19570257.06 | 21249.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 97267483.78 | 8806.09 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48802110.97 | 8806.09 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89967849.52 | 8806.09 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69978008.62 | 8806.09 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97267483.78 | 8806.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102301E+09 | 5855.10 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43180353.30 | 5855.10 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52617053.62 | 5855.10 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84388.62 | 703.24 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80519702.96 | 5855.10 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102301E+09 | 5855.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304505E+09 | 8852.74 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149999E+09 | 8852.74 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122114E+09 | 8852.74 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1920147.05 | 4337.55 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192862E+09 | 8852.74 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.771400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304505E+09 | 8852.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133483E+09 | 5831.65 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65519118.18 | 5831.65 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66829794.20 | 5831.65 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 723234.55 | 1815.54 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85638432.27 | 5831.65 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133483E+09 | 5831.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.406455E+09 | 26577.60 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276337E+09 | 26577.60 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232066E+09 | 26577.60 | 10-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287911E+09 | 26577.60 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406455E+09 | 26577.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376957E+09 | 11318.78 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195330E+09 | 11318.78 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255620E+09 | 11318.78 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2378501.78 | 3914.72 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2060515.91 | 1475.84 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14080725.90 | 11318.78 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288086E+09 | 11318.78 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.376957E+09 | 11318.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.340634E+09 | 7400.06 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150390E+09 | 7400.06 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162582E+09 | 7400.06 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 614251.59 | 3024.37 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1733759.86 | 1578.35 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12096799.89 | 7400.06 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271526E+09 | 7400.06 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.939576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340634E+09 | 7400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.902951E+09 | 11123.44 | 21-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440525E+09 | 10900.58 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331545E+09 | 11089.49 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3726529.51 | 5675.41 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5474545.92 | 2456.46 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54212614.59 | 10940.84 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590019E+09 | 10897.65 | 29-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.902951E+09 | 11123.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453324E+09 | 7386.82 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221127E+09 | 7386.82 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188009E+09 | 7386.82 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 967051.30 | 1750.20 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2761044.82 | 1196.77 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25938222.36 | 7386.82 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300599E+09 | 7386.82 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453324E+09 | 7386.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.227881E+09 | 6302.33 | 05-JAN-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105891E+09 | 5414.55 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 62125610.28 | 5318.83 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167224E+09 | 6302.33 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.563122E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227881E+09 | 6302.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305219E+09 | 7020.90 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138377E+09 | 5882.15 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88668237.58 | 5784.86 | 09-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216748E+09 | 6892.31 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.749012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305219E+09 | 7020.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428015E+09 | 5290.19 | 03-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199602E+09 | 5290.19 | 17-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131049E+09 | 5290.19 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1723367.64 | 750.28 | 15-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281281E+09 | 5290.19 | 18-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428015E+09 | 5290.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.172513E+11 | 0.112843E+11 | 60232.28 | 19-JAN-13:05 | 36326.24 | 0.00 |
February | 0.00 | 0.00 | 0.233961E+11 | 0.146385E+11 | 59409.88 | 24-FEB-13:05 | 39618.49 | 0.00 |
March | 0.00 | 0.00 | 0.283449E+11 | 0.186125E+11 | 63577.62 | 28-MAR-12:00 | 39414.84 | 0.00 |
April | 0.00 | 0.00 | 0.453104E+11 | 0.308959E+11 | 78321.75 | 28-APR-16:00 | 51097.26 | 0.00 |
May | 0.00 | 0.00 | 0.826496E+11 | 0.535791E+11 | 118247.68 | 22-MAY-04:03 | 57363.39 | 0.00 |
June | 0.00 | 0.00 | 0.889550E+11 | 0.572780E+11 | 90698.68 | 05-JUN-12:03 | 54583.08 | 0.00 |
July | 0.00 | 0.00 | 0.944798E+11 | 0.577897E+11 | 111457.95 | 03-JUL-04:02 | 71642.32 | 0.00 |
August | 0.00 | 0.00 | 0.100678E+12 | 0.629532E+11 | 97258.07 | 22-AUG-06:03 | 64668.54 | 0.00 |
September | 0.00 | 0.00 | 0.854708E+11 | 0.527322E+11 | 116078.46 | 05-SEP-05:12 | 65771.48 | 0.00 |
October | 0.00 | 0.00 | 0.755860E+11 | 0.500219E+11 | 100196.38 | 11-OCT-06:03 | 65178.96 | 0.00 |
November | 0.00 | 0.00 | 0.399557E+11 | 0.274390E+11 | 83571.47 | 07-NOV-13:05 | 49582.23 | 0.00 |
December | 0.00 | 0.00 | 0.260660E+11 | 0.171019E+11 | 72001.73 | 14-DEC-13:05 | 43392.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.708144E+12 | 0.454326E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.172513E+11 | 0.112843E+11 | 59409.88 | 36326.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100678E+12 | 0.629532E+11 | 118247.68 | 71642.32 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.157581E+11 | 0.102366E+11 | 58294.18 | 19-JAN-15:05 | 37873.38 | 0.00 |
February | 0.00 | 0.00 | 0.222399E+11 | 0.141164E+11 | 57315.93 | 27-FEB-15:05 | 42149.27 | 0.00 |
March | 0.00 | 0.00 | 0.271497E+11 | 0.181135E+11 | 58400.93 | 07-MAR-11:05 | 35633.98 | 0.00 |
April | 0.00 | 0.00 | 0.437791E+11 | 0.299329E+11 | 77918.75 | 28-APR-16:00 | 50400.39 | 0.00 |
May | 0.00 | 0.00 | 0.791542E+11 | 0.510725E+11 | 110531.21 | 22-MAY-04:03 | 57327.60 | 0.00 |
June | 0.00 | 0.00 | 0.842685E+11 | 0.538952E+11 | 94088.18 | 05-JUN-04:02 | 67440.17 | 0.00 |
July | 0.00 | 0.00 | 0.883302E+11 | 0.532670E+11 | 105947.23 | 03-JUL-04:02 | 65954.29 | 0.00 |
August | 0.00 | 0.00 | 0.903044E+11 | 0.550549E+11 | 101565.10 | 11-AUG-05:03 | 58871.86 | 0.00 |
September | 0.00 | 0.00 | 0.764674E+11 | 0.457842E+11 | 112208.80 | 05-SEP-05:12 | 56715.73 | 0.00 |
October | 0.00 | 0.00 | 0.674918E+11 | 0.434930E+11 | 100328.10 | 07-OCT-05:03 | 62866.41 | 0.00 |
November | 0.00 | 0.00 | 0.352446E+11 | 0.236021E+11 | 75682.65 | 02-NOV-14:05 | 48858.42 | 0.00 |
December | 0.00 | 0.00 | 0.234341E+11 | 0.151613E+11 | 64764.63 | 14-DEC-13:05 | 40066.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.653622E+12 | 0.413730E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.157581E+11 | 0.102366E+11 | 57315.93 | 35633.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.903044E+11 | 0.550549E+11 | 112208.80 | 67440.17 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.162079E+11 | 0.105016E+11 | 61734.88 | 19-JAN-15:00 | 41424.63 | 0.00 |
February | 0.00 | 0.00 | 0.230850E+11 | 0.147525E+11 | 60951.92 | 27-FEB-15:30 | 46157.43 | 0.00 |
March | 0.00 | 0.00 | 0.284959E+11 | 0.190887E+11 | 60847.05 | 28-MAR-12:30 | 42318.55 | 0.00 |
April | 0.00 | 0.00 | 0.466727E+11 | 0.323422E+11 | 86847.48 | 28-APR-16:00 | 59803.35 | 0.00 |
May | 0.00 | 0.00 | 0.850884E+11 | 0.564408E+11 | 123704.36 | 22-MAY-04:03 | 66433.96 | 0.00 |
June | 0.00 | 0.00 | 0.909839E+11 | 0.602109E+11 | 104871.89 | 05-JUN-04:02 | 77831.21 | 0.00 |
July | 0.00 | 0.00 | 0.948385E+11 | 0.591900E+11 | 114511.54 | 03-JUL-04:02 | 78223.73 | 0.00 |
August | 0.00 | 0.00 | 0.962854E+11 | 0.604703E+11 | 111066.31 | 15-AUG-05:03 | 57796.28 | 0.00 |
September | 0.00 | 0.00 | 0.804827E+11 | 0.491180E+11 | 125896.71 | 05-SEP-05:12 | 60953.81 | 0.00 |
October | 0.00 | 0.00 | 0.707392E+11 | 0.462082E+11 | 97729.18 | 07-OCT-05:03 | 57922.14 | 0.00 |
November | 0.00 | 0.00 | 0.360582E+11 | 0.238634E+11 | 80998.60 | 02-NOV-14:30 | 55391.64 | 0.00 |
December | 0.00 | 0.00 | 0.240391E+11 | 0.154314E+11 | 66569.26 | 15-DEC-14:50 | 50778.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.692977E+12 | 0.447618E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.162079E+11 | 0.105016E+11 | 60847.05 | 41424.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.962854E+11 | 0.604703E+11 | 125896.71 | 78223.73 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1512.26 | 5215.44 | 23-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1510.01 | 5190.88 | 03-FEB-12:05 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1551.10 | 5049.85 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1369.63 | 4778.89 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1330.36 | 4498.22 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1287.61 | 4204.56 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1150.41 | 4018.36 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1272.74 | 4091.79 | 30-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1245.48 | 4307.26 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1324.80 | 4655.93 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1431.79 | 4928.47 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1441.01 | 5143.72 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 1368.16 | ||||
Minimum of Months | 0.00 | 0.00 | 1150.41 | 4018.36 | ||
Maximum of Months | 0.00 | 0.00 | 1551.10 | 5215.44 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125817E+10 | 0.29 | 3252.89 | 02-JAN-06:13 | 0.93 |
February | 0.117816E+10 | 0.29 | 2563.63 | 27-FEB-16:10 | 0.81 |
March | 0.140221E+10 | 0.31 | 2232.56 | 30-MAR-12:00 | 0.75 |
April | 0.162230E+10 | 0.31 | 3078.12 | 28-APR-15:20 | 0.90 |
May | 0.272164E+10 | 0.40 | 8236.11 | 30-MAY-04:02 | 1.65 |
June | 0.294360E+10 | 0.43 | 8043.66 | 26-JUN-04:02 | 1.63 |
July | 0.305100E+10 | 0.43 | 9310.52 | 03-JUL-04:02 | 1.78 |
August | 0.350567E+10 | 0.46 | 9310.52 | 07-AUG-04:02 | 1.78 |
September | 0.287738E+10 | 0.42 | 9310.52 | 05-SEP-05:12 | 1.78 |
October | 0.298170E+10 | 0.41 | 9310.52 | 10-OCT-05:12 | 1.78 |
November | 0.183088E+10 | 0.33 | 3755.31 | 06-NOV-16:20 | 1.01 |
December | 0.143996E+10 | 0.30 | 3060.59 | 15-DEC-16:10 | 0.90 |
Annual Sum or Average | 0.268127E+11 | 0.37 | |||
Minimum of Months | 0.117816E+10 | 0.29 | 2232.56 | 0.75 | |
Maximum of Months | 0.350567E+10 | 0.46 | 9310.52 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117248E+10 | 0.29 | 2465.76 | 19-JAN-15:05 | 0.83 |
February | 0.114104E+10 | 0.29 | 2909.71 | 27-FEB-15:05 | 0.92 |
March | 0.133888E+10 | 0.31 | 2231.60 | 06-MAR-15:05 | 0.79 |
April | 0.158057E+10 | 0.32 | 3222.25 | 28-APR-15:30 | 0.97 |
May | 0.254661E+10 | 0.40 | 8534.90 | 22-MAY-04:03 | 1.78 |
June | 0.267911E+10 | 0.43 | 8534.90 | 05-JUN-04:02 | 1.78 |
July | 0.265888E+10 | 0.41 | 8534.90 | 03-JUL-04:02 | 1.78 |
August | 0.281160E+10 | 0.43 | 8534.90 | 07-AUG-04:02 | 1.78 |
September | 0.232093E+10 | 0.39 | 8534.90 | 05-SEP-05:12 | 1.78 |
October | 0.244509E+10 | 0.39 | 8534.90 | 10-OCT-06:03 | 1.78 |
November | 0.151719E+10 | 0.32 | 3733.99 | 06-NOV-15:05 | 1.06 |
December | 0.127191E+10 | 0.29 | 3084.36 | 15-DEC-15:05 | 0.95 |
Annual Sum or Average | 0.234843E+11 | 0.36 | |||
Minimum of Months | 0.114104E+10 | 0.29 | 2231.60 | 0.79 | |
Maximum of Months | 0.281160E+10 | 0.43 | 8534.90 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118612E+10 | 0.30 | 2253.16 | 19-JAN-15:30 | 0.73 |
February | 0.115964E+10 | 0.30 | 2627.76 | 27-FEB-15:30 | 0.79 |
March | 0.137556E+10 | 0.32 | 2258.50 | 29-MAR-15:20 | 0.73 |
April | 0.162516E+10 | 0.32 | 3550.46 | 28-APR-15:30 | 0.94 |
May | 0.262215E+10 | 0.39 | 10055.22 | 22-MAY-04:03 | 1.78 |
June | 0.279615E+10 | 0.41 | 10055.22 | 05-JUN-04:02 | 1.78 |
July | 0.274262E+10 | 0.40 | 10055.22 | 03-JUL-04:02 | 1.78 |
August | 0.285474E+10 | 0.41 | 10055.22 | 21-AUG-04:02 | 1.78 |
September | 0.227917E+10 | 0.38 | 9967.10 | 11-SEP-04:02 | 1.77 |
October | 0.235446E+10 | 0.37 | 7596.44 | 10-OCT-06:03 | 1.49 |
November | 0.144949E+10 | 0.31 | 3375.41 | 06-NOV-15:30 | 0.91 |
December | 0.126719E+10 | 0.30 | 2847.87 | 15-DEC-15:20 | 0.83 |
Annual Sum or Average | 0.237124E+11 | 0.35 | |||
Minimum of Months | 0.115964E+10 | 0.30 | 2253.16 | 0.73 | |
Maximum of Months | 0.285474E+10 | 0.41 | 10055.22 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.13 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.71 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.71 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.63 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.20 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.19 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.26 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.88 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.65 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.36 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.16 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.03 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.03 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.65 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.76 | 57.76 | 1512.26 | 5215.44 | 23-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.74 | 57.74 | 1510.01 | 5190.88 | 03-FEB-12:05 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.05 | 57.05 | 1551.10 | 5049.85 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.85 | 57.85 | 1369.63 | 4778.89 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.41 | 57.41 | 1330.36 | 4498.22 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.44 | 57.44 | 1287.61 | 4204.56 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.18 | 58.18 | 1150.41 | 4018.36 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.10 | 57.10 | 1272.74 | 4091.79 | 30-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.90 | 57.90 | 1245.48 | 4307.26 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.94 | 56.94 | 1324.80 | 4655.93 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.48 | 56.48 | 1431.79 | 4928.47 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.36 | 56.36 | 1441.01 | 5143.72 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 1368.16 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.36 | 56.36 | 1150.41 | 4018.36 | ||
Maximum of Months | 0.00 | 0.00 | 58.18 | 58.18 | 1551.10 | 5215.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.634883E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.735025E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.910486E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.124217E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.226581E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.246492E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.260356E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.278952E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.229615E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.209290E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113610E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.835837E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.200074E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.634883E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.278952E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.553327E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.667588E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.806772E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118511E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.215730E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.231515E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.240148E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.245530E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.202206E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.184096E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.977206E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.718814E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181011E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.553327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.245530E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.752828E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.789813E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.928826E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126701E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.231971E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.250300E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.258128E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261598E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.212303E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.191879E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100782E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.868849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.196769E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.752828E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.261598E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.125817E+10 | 0.172513E+11 | 0.125417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117816E+10 | 0.233961E+11 | 0.795423E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140221E+10 | 0.283449E+11 | 0.109695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162230E+10 | 0.453104E+11 | 0.168220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272164E+10 | 0.826496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294360E+10 | 0.889550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.305100E+10 | 0.944798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350567E+10 | 0.100678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287738E+10 | 0.854708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.298170E+10 | 0.755860E+11 | 21769993.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183088E+10 | 0.399557E+11 | 0.215235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143996E+10 | 0.260660E+11 | 0.996153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268127E+11 | 0.708144E+12 | 0.454792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117816E+10 | 0.172513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350567E+10 | 0.100678E+12 | 0.125417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117248E+10 | 0.157581E+11 | 0.942775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114104E+10 | 0.222399E+11 | 0.458904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133888E+10 | 0.271497E+11 | 0.439767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158057E+10 | 0.437791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254661E+10 | 0.791542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267911E+10 | 0.842685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.265888E+10 | 0.883302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.281160E+10 | 0.903044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.232093E+10 | 0.764674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244509E+10 | 0.674918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151719E+10 | 0.352446E+11 | 2727770.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127191E+10 | 0.234341E+11 | 0.645747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234843E+11 | 0.653622E+12 | 0.248992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114104E+10 | 0.157581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.281160E+10 | 0.903044E+11 | 0.942775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.118612E+10 | 0.162079E+11 | 0.290834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115964E+10 | 0.230850E+11 | 0.148331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137556E+10 | 0.284959E+11 | 0.130087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162516E+10 | 0.466727E+11 | 7686334.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.262215E+10 | 0.850884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.279615E+10 | 0.909839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.274262E+10 | 0.948385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.285474E+10 | 0.962854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227917E+10 | 0.804827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235446E+10 | 0.707392E+11 | 12029866.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144949E+10 | 0.360582E+11 | 0.108052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126719E+10 | 0.240391E+11 | 0.201942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237124E+11 | 0.692977E+12 | 0.783971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115964E+10 | 0.162079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.285474E+10 | 0.962854E+11 | 0.290834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.125817E+10 | 0.00 | 0.00 | 0.00 | 0.406437E+10 | 0.102629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117816E+10 | 0.00 | 0.00 | 0.00 | 0.548256E+10 | 0.689531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140221E+10 | 0.00 | 0.00 | 0.00 | 0.666782E+10 | 0.103482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162230E+10 | 0.00 | 0.00 | 0.00 | 0.106312E+11 | 0.168220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.272164E+10 | 0.00 | 0.00 | 0.00 | 0.199364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294360E+10 | 0.00 | 0.00 | 0.00 | 0.217056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.305100E+10 | 0.00 | 0.00 | 0.00 | 0.229846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350567E+10 | 0.00 | 0.00 | 0.00 | 0.243896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287738E+10 | 0.00 | 0.00 | 0.00 | 0.200841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.298170E+10 | 0.00 | 0.00 | 0.00 | 0.179255E+11 | 21769993.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183088E+10 | 0.00 | 0.00 | 0.00 | 0.931484E+10 | 0.215235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143996E+10 | 0.00 | 0.00 | 0.00 | 0.608948E+10 | 0.828929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268127E+11 | 0.00 | 0.00 | 0.00 | 0.169276E+12 | 0.398479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117816E+10 | 0.00 | 0.00 | 0.00 | 0.406437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350567E+10 | 0.00 | 0.00 | 0.00 | 0.243896E+11 | 0.103482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117248E+10 | 0.00 | 0.00 | 0.00 | 0.372323E+10 | 0.637557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114104E+10 | 0.00 | 0.00 | 0.00 | 0.521430E+10 | 0.320527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133888E+10 | 0.00 | 0.00 | 0.00 | 0.637774E+10 | 0.351099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158057E+10 | 0.00 | 0.00 | 0.00 | 0.102705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254661E+10 | 0.00 | 0.00 | 0.00 | 0.190264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267911E+10 | 0.00 | 0.00 | 0.00 | 0.204724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.265888E+10 | 0.00 | 0.00 | 0.00 | 0.213560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.281160E+10 | 0.00 | 0.00 | 0.00 | 0.217415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.232093E+10 | 0.00 | 0.00 | 0.00 | 0.178997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244509E+10 | 0.00 | 0.00 | 0.00 | 0.159646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151719E+10 | 0.00 | 0.00 | 0.00 | 0.825215E+10 | 2727770.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127191E+10 | 0.00 | 0.00 | 0.00 | 0.548724E+10 | 0.428999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234843E+11 | 0.00 | 0.00 | 0.00 | 0.155786E+12 | 0.174091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114104E+10 | 0.00 | 0.00 | 0.00 | 0.372323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.281160E+10 | 0.00 | 0.00 | 0.00 | 0.217415E+11 | 0.637557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.118612E+10 | 0.00 | 0.00 | 0.00 | 0.386184E+10 | 0.248032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115964E+10 | 0.00 | 0.00 | 0.00 | 0.545479E+10 | 0.128371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137556E+10 | 0.00 | 0.00 | 0.00 | 0.674288E+10 | 0.116982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162516E+10 | 0.00 | 0.00 | 0.00 | 0.110373E+11 | 7686334.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.262215E+10 | 0.00 | 0.00 | 0.00 | 0.205749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.279615E+10 | 0.00 | 0.00 | 0.00 | 0.222339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.274262E+10 | 0.00 | 0.00 | 0.00 | 0.230702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.285474E+10 | 0.00 | 0.00 | 0.00 | 0.233051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227917E+10 | 0.00 | 0.00 | 0.00 | 0.189511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235446E+10 | 0.00 | 0.00 | 0.00 | 0.168214E+11 | 12029866.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144949E+10 | 0.00 | 0.00 | 0.00 | 0.852240E+10 | 0.106328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126719E+10 | 0.00 | 0.00 | 0.00 | 0.568317E+10 | 0.173814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237124E+11 | 0.00 | 0.00 | 0.00 | 0.166259E+12 | 0.679804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115964E+10 | 0.00 | 0.00 | 0.00 | 0.386184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.285474E+10 | 0.00 | 0.00 | 0.00 | 0.233051E+11 | 0.248032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.331741E+10 | 0.111615E+10 | 0.00 | 16414914.27 | 90211045.65 | 0.00 | 0.649304E+10 | 0.00 | 0.42 |
February | 0.197153E+10 | 0.147187E+10 | 0.00 | 10216412.46 | 0.112279E+09 | 0.00 | 0.340946E+10 | 0.00 | 0.42 |
March | 0.170659E+10 | 0.239399E+10 | 0.00 | 14515633.61 | 0.142462E+09 | 0.00 | 0.551469E+10 | 0.00 | 0.47 |
April | 0.308825E+09 | 0.457728E+10 | 0.00 | 7413817.42 | 90048966.31 | 0.00 | 0.153278E+10 | 0.00 | 0.40 |
May | 0.00 | 0.122452E+11 | 0.00 | 0.00 | 0.146836E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.133862E+11 | 0.00 | 0.00 | 0.159390E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.145558E+11 | 0.00 | 0.00 | 0.264058E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.143957E+11 | 0.00 | 0.00 | 0.167435E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.117406E+11 | 0.00 | 0.00 | 0.215425E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.165416E+09 | 0.864914E+10 | 0.00 | 7338262.80 | 0.150008E+09 | 0.00 | 0.169206E+10 | 0.00 | 0.34 |
November | 0.712623E+09 | 0.329987E+10 | 0.00 | 17027983.05 | 32417974.67 | 0.00 | 0.437717E+10 | 0.00 | 0.48 |
December | 0.241407E+10 | 0.243226E+10 | 0.00 | 15835381.52 | 56695081.30 | 0.00 | 0.579363E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.105965E+11 | 0.902640E+11 | 0.00 | 88762405.13 | 0.162727E+10 | 0.00 | 0.288128E+11 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.111615E+10 | 0.00 | 0.00 | 32417974.67 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.331741E+10 | 0.145558E+11 | 0.00 | 17027983.05 | 0.264058E+09 | 0.00 | 0.649304E+10 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.683121E+10 | 0.773506E+09 | 0.00 | 2539216.21 | 0.369691E+09 | 0.00 | 0.141727E+10 | 0.00 | 0.37 |
February | 0.379631E+10 | 0.105525E+10 | 0.00 | 1392454.32 | 0.400051E+09 | 2300522.48 | 0.780926E+09 | 0.00 | 0.36 |
March | 0.390188E+10 | 0.171751E+10 | 0.00 | 3738398.61 | 0.539713E+09 | 701049.59 | 0.208249E+10 | 0.00 | 0.40 |
April | 0.693170E+09 | 0.362480E+10 | 0.00 | 3559304.58 | 0.552203E+09 | 0.00 | 0.823138E+09 | 0.00 | 0.33 |
May | 0.00 | 0.115171E+11 | 0.00 | 0.00 | 0.167481E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.130147E+11 | 0.00 | 0.00 | 0.158411E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.144489E+11 | 0.00 | 0.00 | 0.282831E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.144928E+11 | 0.00 | 0.00 | 0.167674E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.116708E+11 | 0.00 | 0.00 | 0.259155E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
October | 0.442335E+09 | 0.854897E+10 | 0.00 | 4066689.76 | 0.209487E+09 | 0.00 | 0.105027E+10 | 0.00 | 0.30 |
November | 0.188445E+10 | 0.302404E+10 | 0.00 | 5685619.54 | 0.271667E+09 | 0.00 | 0.186827E+10 | 0.00 | 0.38 |
December | 0.531598E+10 | 0.205150E+10 | 0.00 | 2303986.86 | 0.321190E+09 | 0.00 | 0.128290E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.228653E+11 | 0.859399E+11 | 0.00 | 23285669.88 | 0.369955E+10 | 3001572.07 | 0.930527E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.773506E+09 | 0.00 | 0.00 | 0.158411E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.683121E+10 | 0.144928E+11 | 0.00 | 5685619.54 | 0.552203E+09 | 2300522.48 | 0.208249E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.671438E+10 | 0.603215E+09 | 0.00 | 1086266.40 | 0.547161E+09 | 86449242.43 | 0.698387E+09 | 0.00 | 0.36 |
February | 0.354566E+10 | 0.879367E+09 | 0.00 | 887218.30 | 0.601101E+09 | 52399677.52 | 0.590508E+09 | 0.00 | 0.35 |
March | 0.420126E+10 | 0.159080E+10 | 0.00 | 2334101.29 | 0.617367E+09 | 33970313.42 | 0.125314E+10 | 0.00 | 0.39 |
April | 0.713604E+09 | 0.348496E+10 | 0.00 | 3503819.02 | 0.635857E+09 | 0.00 | 0.784141E+09 | 0.00 | 0.33 |
May | 0.00 | 0.112883E+11 | 0.00 | 0.00 | 0.144627E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.127105E+11 | 0.00 | 0.00 | 0.146031E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.141913E+11 | 0.00 | 0.00 | 0.271258E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.142028E+11 | 0.00 | 0.00 | 0.156807E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.114970E+11 | 0.00 | 0.00 | 0.241829E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.477431E+09 | 0.837003E+10 | 0.00 | 2910193.64 | 0.244540E+09 | 0.00 | 0.793497E+09 | 0.00 | 0.30 |
November | 0.213561E+10 | 0.273577E+10 | 0.00 | 3470238.88 | 0.619154E+09 | 0.00 | 0.115675E+10 | 0.00 | 0.37 |
December | 0.545641E+10 | 0.160503E+10 | 5678.38 | 812726.84 | 0.762568E+09 | 44972717.01 | 0.364087E+09 | 10956.67 | 0.35 |
Annual Sum or Average | 0.232444E+11 | 0.831591E+11 | 5678.38 | 15004564.38 | 0.498830E+10 | 0.217792E+09 | 0.564052E+10 | 10956.67 | 0.31 |
Minimum of Months | 0.00 | 0.603215E+09 | 0.00 | 0.00 | 0.144627E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.671438E+10 | 0.142028E+11 | 5678.38 | 3503819.02 | 0.762568E+09 | 86449242.43 | 0.125314E+10 | 10956.67 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117360E+10 | 0.146268E+09 | 0.00 | 22850.87 | 0.116951E+09 | 0.409164E+09 | 6402208.70 | 0.00 | 0.36 |
February | 0.667337E+09 | 0.205174E+09 | 0.00 | 73609.84 | 0.137996E+09 | 0.168605E+09 | 48964865.96 | 0.00 | 0.36 |
March | 0.887051E+09 | 0.441964E+09 | 0.00 | 347103.66 | 0.111686E+09 | 0.148657E+09 | 0.116506E+09 | 0.00 | 0.41 |
April | 0.193354E+09 | 0.994346E+09 | 0.00 | 853208.53 | 0.137322E+09 | 619833.36 | 0.136330E+09 | 0.00 | 0.40 |
May | 0.00 | 0.364169E+10 | 0.00 | 0.00 | 29106418.01 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.442616E+10 | 0.00 | 0.00 | 33984292.02 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.489512E+10 | 0.00 | 0.00 | 49919074.33 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.467031E+10 | 0.00 | 0.00 | 40179013.21 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.341939E+10 | 0.00 | 0.00 | 79900782.67 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.135886E+09 | 0.250363E+10 | 0.00 | 545619.62 | 62102155.79 | 488090.95 | 0.133178E+09 | 0.00 | 0.37 |
November | 0.542109E+09 | 0.682161E+09 | 665928.42 | 522938.75 | 0.141751E+09 | 14263618.87 | 0.131641E+09 | 10478.42 | 0.39 |
December | 0.940539E+09 | 0.396121E+09 | 611418.68 | 67288.15 | 0.158930E+09 | 0.285153E+09 | 17525393.86 | 17704.49 | 0.36 |
Annual Sum or Average | 0.453987E+10 | 0.264223E+11 | 1277347.10 | 2432619.43 | 0.109983E+10 | 0.102695E+10 | 0.590547E+09 | 28182.91 | 0.38 |
Minimum of Months | 0.00 | 0.146268E+09 | 0.00 | 0.00 | 29106418.01 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.117360E+10 | 0.489512E+10 | 665928.42 | 853208.53 | 0.158930E+09 | 0.409164E+09 | 0.136330E+09 | 17704.49 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.753210E+09 | 0.152397E+09 | 0.00 | 162690.57 | 52932501.97 | 0.148705E+09 | 0.111103E+09 | 0.00 | 0.38 |
February | 0.387791E+09 | 0.249760E+09 | 0.00 | 388549.44 | 52973324.57 | 50939741.43 | 0.138287E+09 | 0.00 | 0.42 |
March | 0.427284E+09 | 0.487562E+09 | 0.00 | 1157003.03 | 38922548.65 | 73480113.63 | 0.336781E+09 | 0.00 | 0.53 |
April | 75993417.11 | 0.101824E+10 | 0.00 | 1291685.29 | 52524837.23 | 98427.41 | 0.273984E+09 | 0.00 | 0.59 |
May | 0.00 | 0.309903E+10 | 0.00 | 0.00 | 18398607.84 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.364952E+10 | 0.00 | 0.00 | 20913966.32 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.410537E+10 | 0.00 | 0.00 | 28231664.43 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.385823E+10 | 0.00 | 0.00 | 22226330.63 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.282920E+10 | 0.00 | 0.00 | 34817650.26 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 67290115.02 | 0.215362E+10 | 0.00 | 622805.42 | 30936348.99 | 308529.68 | 0.140903E+09 | 0.00 | 0.49 |
November | 0.238515E+09 | 0.626728E+09 | 57393.20 | 980903.40 | 59985530.67 | 2432364.97 | 0.267822E+09 | 5246.47 | 0.48 |
December | 0.573922E+09 | 0.346267E+09 | 96027.64 | 327349.67 | 70954722.82 | 0.123358E+09 | 0.103508E+09 | 8692.69 | 0.39 |
Annual Sum or Average | 0.252401E+10 | 0.225759E+11 | 153420.84 | 4930986.81 | 0.483818E+09 | 0.399322E+09 | 0.137239E+10 | 13939.16 | 0.49 |
Minimum of Months | 0.00 | 0.152397E+09 | 0.00 | 0.00 | 18398607.84 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.753210E+09 | 0.410537E+10 | 96027.64 | 1291685.29 | 70954722.82 | 0.148705E+09 | 0.336781E+09 | 8692.69 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.724924E+09 | 0.387983E+09 | 0.00 | 4725017.18 | 60331670.95 | 0.162768E+09 | 0.157666E+10 | 0.00 | 0.60 |
February | 0.424338E+09 | 0.627070E+09 | 0.00 | 2714764.13 | 61481649.81 | 67015782.62 | 0.797297E+09 | 0.00 | 0.59 |
March | 0.645832E+09 | 0.727112E+09 | 0.00 | 2532875.61 | 71794683.89 | 0.120522E+09 | 0.746504E+09 | 0.00 | 0.58 |
April | 0.162263E+09 | 0.126064E+10 | 0.00 | 1503450.32 | 0.125127E+09 | 145410.15 | 0.254147E+09 | 0.00 | 0.49 |
May | 0.00 | 0.368895E+10 | 0.00 | 0.00 | 29167800.58 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.423597E+10 | 0.00 | 0.00 | 38930946.80 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.482419E+10 | 0.00 | 0.00 | 52096483.98 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.512549E+10 | 0.00 | 0.00 | 41020427.97 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.428529E+10 | 0.00 | 0.00 | 63330561.71 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.105526E+09 | 0.377293E+10 | 0.00 | 1395820.38 | 35538182.06 | 489120.29 | 0.280648E+09 | 0.00 | 0.57 |
November | 0.279102E+09 | 0.137987E+10 | 50880.99 | 4522259.64 | 81025557.20 | 3760908.48 | 0.103346E+10 | 4554.34 | 0.74 |
December | 0.639266E+09 | 0.984698E+09 | 65384.49 | 4297360.14 | 80972384.90 | 0.134080E+09 | 0.109571E+10 | 12273.47 | 0.65 |
Annual Sum or Average | 0.298125E+10 | 0.313002E+11 | 116265.48 | 21691547.39 | 0.740817E+09 | 0.488782E+09 | 0.578443E+10 | 16827.81 | 0.52 |
Minimum of Months | 0.00 | 0.387983E+09 | 0.00 | 0.00 | 29167800.58 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.724924E+09 | 0.512549E+10 | 65384.49 | 4725017.18 | 0.125127E+09 | 0.162768E+09 | 0.157666E+10 | 12273.47 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.627386E+09 | 0.169100E+09 | 0.00 | 714366.87 | 52936571.70 | 0.199355E+09 | 0.267479E+09 | 0.00 | 0.42 |
February | 0.345085E+09 | 0.247999E+09 | 0.00 | 656529.51 | 65359942.90 | 82033785.14 | 0.200127E+09 | 0.00 | 0.45 |
March | 0.447084E+09 | 0.379163E+09 | 0.00 | 1376146.94 | 53204286.10 | 87466938.89 | 0.404103E+09 | 0.00 | 0.55 |
April | 95284592.33 | 0.971833E+09 | 0.00 | 1260769.94 | 65473482.51 | 91630.64 | 0.208173E+09 | 0.00 | 0.57 |
May | 0.00 | 0.282196E+10 | 0.00 | 0.00 | 12305281.00 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.336208E+10 | 0.00 | 0.00 | 8198810.45 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.366264E+10 | 0.00 | 0.00 | 9918763.20 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.372227E+10 | 0.00 | 0.00 | 15878454.53 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.273989E+10 | 0.00 | 0.00 | 29434425.34 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 75590707.01 | 0.207720E+10 | 0.00 | 631281.57 | 22630065.52 | 308220.61 | 0.138775E+09 | 0.00 | 0.49 |
November | 0.285932E+09 | 0.606522E+09 | 215240.78 | 1100271.92 | 74557194.56 | 7906661.47 | 0.265517E+09 | 5079.83 | 0.50 |
December | 0.543951E+09 | 0.397953E+09 | 386165.61 | 630364.40 | 72944715.07 | 0.137691E+09 | 0.175800E+09 | 10668.10 | 0.44 |
Annual Sum or Average | 0.242031E+10 | 0.211586E+11 | 601406.39 | 6369731.14 | 0.482842E+09 | 0.514853E+09 | 0.165997E+10 | 15747.93 | 0.48 |
Minimum of Months | 0.00 | 0.169100E+09 | 0.00 | 0.00 | 8198810.45 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.627386E+09 | 0.372227E+10 | 386165.61 | 1376146.94 | 74557194.56 | 0.199355E+09 | 0.404103E+09 | 10668.10 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167503E+10 | 0.120769E+09 | 0.00 | 53273.46 | 91305043.52 | 61753366.52 | 67437460.65 | 0.00 | 0.36 |
February | 0.927275E+09 | 0.149204E+09 | 0.00 | 29925.81 | 0.117624E+09 | 41179948.35 | 42908221.98 | 0.00 | 0.36 |
March | 0.115742E+10 | 0.273079E+09 | 0.00 | 59452.65 | 0.177113E+09 | 43610296.29 | 49168110.89 | 0.00 | 0.39 |
April | 0.239502E+09 | 0.693137E+09 | 0.00 | 378664.75 | 0.187380E+09 | 0.00 | 56945757.21 | 0.00 | 0.32 |
May | 0.00 | 0.283732E+10 | 0.00 | 0.00 | 31621483.82 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.355263E+10 | 0.00 | 0.00 | 33972459.05 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.412577E+10 | 0.00 | 0.00 | 55811719.70 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.412826E+10 | 0.00 | 0.00 | 35389368.33 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.308373E+10 | 0.00 | 0.00 | 45532687.98 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.125952E+09 | 0.221970E+10 | 0.00 | 811038.51 | 35521214.97 | 0.00 | 0.193633E+09 | 0.00 | 0.35 |
November | 0.619282E+09 | 0.616477E+09 | 0.00 | 799515.58 | 47860300.17 | 0.00 | 0.208614E+09 | 0.00 | 0.38 |
December | 0.141156E+10 | 0.385111E+09 | 0.00 | 84017.57 | 82057957.44 | 21314590.81 | 32058575.90 | 0.00 | 0.36 |
Annual Sum or Average | 0.615603E+10 | 0.221852E+11 | 0.00 | 2215888.35 | 0.941189E+09 | 0.167858E+09 | 0.650764E+09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.120769E+09 | 0.00 | 0.00 | 31621483.82 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.167503E+10 | 0.412826E+10 | 0.00 | 811038.51 | 0.187380E+09 | 61753366.52 | 0.208614E+09 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.822380E+09 | 0.144659E+09 | 0.00 | 574177.65 | 28995632.19 | 9817036.28 | 0.346857E+09 | 0.00 | 0.39 |
February | 0.465451E+09 | 0.203800E+09 | 0.00 | 505404.70 | 32127826.32 | 9935421.31 | 0.186766E+09 | 0.00 | 0.41 |
March | 0.541709E+09 | 0.404141E+09 | 0.00 | 959666.59 | 32600388.34 | 16641450.87 | 0.317805E+09 | 0.00 | 0.49 |
April | 89661696.97 | 0.832412E+09 | 0.00 | 982654.15 | 47450855.94 | 0.00 | 0.205313E+09 | 0.00 | 0.50 |
May | 0.00 | 0.257143E+10 | 0.00 | 0.00 | 19656894.78 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.306526E+10 | 0.00 | 0.00 | 21337529.67 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.357854E+10 | 0.00 | 0.00 | 35349382.19 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.345687E+10 | 0.00 | 0.00 | 22414509.24 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.257518E+10 | 0.00 | 0.00 | 28838967.84 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 54854686.84 | 0.194180E+10 | 0.00 | 921032.43 | 20081516.17 | 0.00 | 0.203045E+09 | 0.00 | 0.47 |
November | 0.239305E+09 | 0.562268E+09 | 0.00 | 1787074.13 | 9361285.67 | 0.00 | 0.437538E+09 | 0.00 | 0.52 |
December | 0.731714E+09 | 0.343813E+09 | 0.00 | 745850.56 | 22227927.52 | 8419476.03 | 0.238485E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.294508E+10 | 0.196802E+11 | 0.00 | 6475860.21 | 0.320443E+09 | 44813384.50 | 0.193581E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.144659E+09 | 0.00 | 0.00 | 9361285.67 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.822380E+09 | 0.357854E+10 | 0.00 | 1787074.13 | 47450855.94 | 16641450.87 | 0.437538E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107388E+10 | 0.371755E+09 | 111674.11 | 2015046.04 | 23698510.70 | 0.515772E+09 | 0.732883E+09 | 1792.44 | 0.51 |
February | 0.675891E+09 | 0.558033E+09 | 290398.13 | 949232.70 | 25935997.97 | 0.299058E+09 | 0.237691E+09 | 1502.77 | 0.51 |
March | 0.841440E+09 | 0.672546E+09 | 14153.35 | 746224.04 | 63375669.97 | 0.474463E+09 | 0.187970E+09 | 4.24 | 0.50 |
April | 0.205006E+09 | 0.113418E+10 | 1717441.78 | 656760.84 | 0.154420E+09 | 76330971.93 | 75890924.25 | 7807.29 | 0.43 |
May | 0.00 | 0.367586E+10 | 0.00 | 0.00 | 39015271.98 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.443110E+10 | 0.00 | 0.00 | 43015569.03 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.511341E+10 | 0.00 | 0.00 | 55735828.09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.557368E+10 | 0.00 | 0.00 | 38299100.03 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.439329E+10 | 0.00 | 0.00 | 59470074.60 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.127417E+09 | 0.381133E+10 | 0.00 | 1244549.29 | 37200237.49 | 14071120.94 | 0.226948E+09 | 0.00 | 0.57 |
November | 0.312700E+09 | 0.130380E+10 | 0.00 | 4172222.28 | 31332860.04 | 0.130859E+09 | 0.874049E+09 | 0.00 | 0.70 |
December | 0.834525E+09 | 0.943199E+09 | 17703.93 | 2816451.21 | 48387764.24 | 0.479597E+09 | 0.704975E+09 | 1073.60 | 0.61 |
Annual Sum or Average | 0.407086E+10 | 0.319822E+11 | 2151371.31 | 12600486.40 | 0.619887E+09 | 0.199015E+10 | 0.304041E+10 | 12180.34 | 0.50 |
Minimum of Months | 0.00 | 0.371755E+09 | 0.00 | 0.00 | 23698510.70 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.107388E+10 | 0.557368E+10 | 1717441.78 | 4172222.28 | 0.154420E+09 | 0.515772E+09 | 0.874049E+09 | 7807.29 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.875200E+09 | 0.170176E+09 | 0.00 | 841170.03 | 20043255.67 | 13577507.35 | 0.331033E+09 | 0.00 | 0.41 |
February | 0.482257E+09 | 0.231486E+09 | 0.00 | 522883.24 | 32866320.70 | 13138544.43 | 0.175823E+09 | 0.00 | 0.42 |
March | 0.590140E+09 | 0.328258E+09 | 0.00 | 923294.78 | 41035177.12 | 18219236.06 | 0.275294E+09 | 0.00 | 0.47 |
April | 0.103407E+09 | 0.836348E+09 | 0.00 | 789705.62 | 43538231.60 | 0.00 | 0.130416E+09 | 0.00 | 0.47 |
May | 0.00 | 0.233622E+10 | 0.00 | 0.00 | 17382915.41 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.284526E+10 | 0.00 | 0.00 | 12219206.20 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.320538E+10 | 0.00 | 0.00 | 19210081.77 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.337761E+10 | 0.00 | 0.00 | 16918381.88 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.253654E+10 | 0.00 | 0.00 | 18471701.49 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 63395801.89 | 0.190940E+10 | 0.00 | 885461.01 | 14226763.83 | 0.00 | 0.183962E+09 | 0.00 | 0.48 |
November | 0.283812E+09 | 0.578494E+09 | 0.00 | 1534444.77 | 7808428.79 | 0.00 | 0.361253E+09 | 0.00 | 0.51 |
December | 0.765066E+09 | 0.402854E+09 | 0.00 | 741007.35 | 18423736.64 | 7945977.53 | 0.226834E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.316328E+10 | 0.187580E+11 | 0.00 | 6237966.79 | 0.262144E+09 | 52881265.37 | 0.168461E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.170176E+09 | 0.00 | 0.00 | 7808428.79 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.875200E+09 | 0.337761E+10 | 0.00 | 1534444.77 | 43538231.60 | 18219236.06 | 0.361253E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.149803E+10 | 0.174301E+09 | 0.00 | 56007.46 | 89951706.39 | 0.153445E+09 | 57455865.52 | 0.00 | 0.37 |
February | 0.837904E+09 | 0.240789E+09 | 0.00 | 82155.36 | 99281658.83 | 54061929.58 | 62652723.03 | 0.00 | 0.37 |
March | 0.104512E+10 | 0.480238E+09 | 0.00 | 292098.60 | 86381374.48 | 65986248.29 | 0.124956E+09 | 0.00 | 0.41 |
April | 0.204250E+09 | 0.106888E+10 | 0.00 | 706953.49 | 81601908.59 | 0.00 | 0.118298E+09 | 0.00 | 0.39 |
May | 0.00 | 0.377237E+10 | 0.00 | 0.00 | 30967626.98 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.462439E+10 | 0.00 | 0.00 | 33704947.36 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.506830E+10 | 0.00 | 0.00 | 55492789.05 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.484115E+10 | 0.00 | 0.00 | 35345438.64 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.351476E+10 | 0.00 | 0.00 | 45431809.93 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.147319E+09 | 0.257247E+10 | 0.00 | 627817.75 | 47289282.43 | 0.00 | 0.153642E+09 | 0.00 | 0.37 |
November | 0.617481E+09 | 0.735079E+09 | 0.00 | 616190.94 | 79208874.76 | 190898.75 | 0.152501E+09 | 0.00 | 0.39 |
December | 0.127175E+10 | 0.437992E+09 | 0.00 | 76179.39 | 0.115513E+09 | 92880323.86 | 17575545.52 | 0.00 | 0.36 |
Annual Sum or Average | 0.562185E+10 | 0.275307E+11 | 0.00 | 2457402.99 | 0.800170E+09 | 0.366564E+09 | 0.687082E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.174301E+09 | 0.00 | 0.00 | 30967626.98 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.149803E+10 | 0.506830E+10 | 0.00 | 706953.49 | 0.115513E+09 | 0.153445E+09 | 0.153642E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.668547E+09 | 0.147381E+09 | 0.00 | 470111.37 | 39529309.90 | 51943238.39 | 0.250000E+09 | 0.00 | 0.33 |
February | 0.372838E+09 | 0.241614E+09 | 0.00 | 520719.16 | 31187485.00 | 15925804.81 | 0.174355E+09 | 0.00 | 0.39 |
March | 0.428032E+09 | 0.461918E+09 | 0.00 | 1143279.42 | 29290983.43 | 27740425.35 | 0.366223E+09 | 0.00 | 0.49 |
April | 87917060.73 | 0.987647E+09 | 0.00 | 1087509.06 | 27595666.82 | 0.00 | 0.250254E+09 | 0.00 | 0.55 |
May | 0.00 | 0.304922E+10 | 0.00 | 0.00 | 19596359.20 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.363855E+10 | 0.00 | 0.00 | 21095702.30 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.405613E+10 | 0.00 | 0.00 | 35057281.79 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.379400E+10 | 0.00 | 0.00 | 22329297.62 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.271047E+10 | 0.00 | 0.00 | 28701310.39 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 70955946.78 | 0.206890E+10 | 0.00 | 688730.32 | 25284973.31 | 0.00 | 0.151907E+09 | 0.00 | 0.46 |
November | 0.262630E+09 | 0.590022E+09 | 0.00 | 1145505.18 | 35289818.81 | 0.00 | 0.303083E+09 | 0.00 | 0.46 |
December | 0.578220E+09 | 0.335076E+09 | 0.00 | 550581.03 | 42073050.25 | 46183814.31 | 0.173836E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.246914E+10 | 0.220809E+11 | 0.00 | 5606435.54 | 0.357031E+09 | 0.141793E+09 | 0.166966E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.147381E+09 | 0.00 | 0.00 | 19596359.20 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.668547E+09 | 0.405613E+10 | 0.00 | 1145505.18 | 42073050.25 | 51943238.39 | 0.366223E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.836758E+09 | 0.428411E+09 | 0.00 | 5410599.75 | 38903514.47 | 53200249.35 | 0.184290E+10 | 0.00 | 0.63 |
February | 0.506410E+09 | 0.696076E+09 | 0.00 | 3021550.56 | 29804209.31 | 23654710.75 | 0.849438E+09 | 0.00 | 0.61 |
March | 0.782094E+09 | 0.793853E+09 | 0.00 | 2470443.82 | 49904906.99 | 35486091.04 | 0.738633E+09 | 0.00 | 0.57 |
April | 0.179178E+09 | 0.137314E+10 | 0.00 | 1240019.16 | 70307930.92 | 0.00 | 0.210375E+09 | 0.00 | 0.48 |
May | 0.00 | 0.383571E+10 | 0.00 | 0.00 | 30927069.19 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.443618E+10 | 0.00 | 0.00 | 33660804.55 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.500916E+10 | 0.00 | 0.00 | 55420111.07 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.534682E+10 | 0.00 | 0.00 | 35299147.31 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.442134E+10 | 0.00 | 0.00 | 45372308.64 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.115318E+09 | 0.390919E+10 | 0.00 | 1524200.73 | 29656424.24 | 0.00 | 0.299664E+09 | 0.00 | 0.58 |
November | 0.315306E+09 | 0.142978E+10 | 0.00 | 4766014.48 | 34084356.97 | 0.00 | 0.110964E+10 | 0.00 | 0.75 |
December | 0.788524E+09 | 0.104413E+10 | 0.00 | 4999555.55 | 46938399.10 | 40835537.24 | 0.129526E+10 | 0.00 | 0.67 |
Annual Sum or Average | 0.352359E+10 | 0.327238E+11 | 0.00 | 23432384.05 | 0.500279E+09 | 0.153177E+09 | 0.634592E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.428411E+09 | 0.00 | 0.00 | 29656424.24 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.836758E+09 | 0.534682E+10 | 0.00 | 5410599.75 | 70307930.92 | 53200249.35 | 0.184290E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.784457E+09 | 0.196020E+09 | 0.00 | 848005.87 | 33734269.70 | 76204355.48 | 0.326911E+09 | 0.00 | 0.43 |
February | 0.434660E+09 | 0.288514E+09 | 0.00 | 688646.92 | 40362263.26 | 28288726.80 | 0.204403E+09 | 0.00 | 0.46 |
March | 0.548797E+09 | 0.418686E+09 | 0.00 | 1289268.10 | 35154957.94 | 38113890.46 | 0.367805E+09 | 0.00 | 0.54 |
April | 0.100926E+09 | 0.107245E+10 | 0.00 | 1084412.63 | 31533693.81 | 0.00 | 0.171306E+09 | 0.00 | 0.56 |
May | 0.00 | 0.298290E+10 | 0.00 | 0.00 | 14461631.72 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.358770E+10 | 0.00 | 0.00 | 7832974.95 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.00 | 0.385300E+10 | 0.00 | 0.00 | 13203040.69 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.393151E+10 | 0.00 | 0.00 | 12593774.96 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.284040E+10 | 0.00 | 0.00 | 16929975.64 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 81799553.69 | 0.216469E+10 | 0.00 | 697305.82 | 16717855.23 | 0.00 | 0.147227E+09 | 0.00 | 0.50 |
November | 0.325149E+09 | 0.656788E+09 | 0.00 | 1183843.48 | 32811943.68 | 120524.45 | 0.278524E+09 | 0.00 | 0.51 |
December | 0.716171E+09 | 0.433511E+09 | 0.00 | 704705.47 | 47620031.86 | 41704730.07 | 0.192332E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.299196E+10 | 0.224262E+11 | 0.00 | 6496188.28 | 0.302956E+09 | 0.184432E+09 | 0.168851E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.196020E+09 | 0.00 | 0.00 | 7832974.95 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.784457E+09 | 0.393151E+10 | 0.00 | 1289268.10 | 47620031.86 | 76204355.48 | 0.367805E+09 | 0.00 | 0.56 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.229647E+12 | 0.703190E+10 | 0.00 | 0.141997E+12 | 0.611070E+11 |
February | 0.241364E+12 | 0.467553E+10 | 0.00 | 0.968305E+11 | 0.849836E+11 |
March | 0.266442E+12 | 0.409007E+10 | 0.00 | 0.106765E+12 | 0.103849E+12 |
April | 0.295685E+12 | -0.134056E+10 | 0.00 | 0.295958E+11 | 0.167701E+12 |
May | 0.290792E+12 | -0.116285E+11 | 0.00 | -0.741148E+11 | 0.306430E+12 |
June | 0.288461E+12 | -0.112418E+11 | 0.00 | -0.856105E+11 | 0.328619E+12 |
July | 0.298529E+12 | -0.150537E+11 | 0.00 | -0.959766E+11 | 0.345059E+12 |
August | 0.278183E+12 | -0.150010E+11 | 0.00 | -0.950824E+11 | 0.356704E+12 |
September | 0.240967E+12 | -0.131769E+11 | 0.00 | -0.754705E+11 | 0.299356E+12 |
October | 0.250739E+12 | -0.879559E+10 | 0.00 | -0.219234E+11 | 0.264528E+12 |
November | 0.200669E+12 | 0.112366E+10 | 0.00 | 0.804598E+11 | 0.137348E+12 |
December | 0.206211E+12 | 0.519847E+10 | 0.00 | 0.130316E+12 | 0.909654E+11 |
Annual Sum or Average | 0.308769E+13 | -0.541184E+11 | 0.00 | 0.137786E+12 | 0.254665E+13 |
Minimum of Months | 0.200669E+12 | -0.150537E+11 | 0.00 | -0.959766E+11 | 0.611070E+11 |
Maximum of Months | 0.298529E+12 | 0.703190E+10 | 0.00 | 0.141997E+12 | 0.356704E+12 |