Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:32:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1435.16 | 288.06 | 288.06 |
Net Site Energy | 1245.75 | 250.04 | 250.04 |
Total Source Energy | 4212.55 | 845.52 | 845.52 |
Net Source Energy | 3612.71 | 725.12 | 725.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 25.99 | 37.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 273.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 169.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 33.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 113.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 122.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1275.49 | 159.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 25.99 | 37.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 273.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 169.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 33.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 113.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 122.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 25.99 | 37.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 273.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 169.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 33.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 113.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 122.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 82.97 | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.01 | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 82.97 | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.01 | 32.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 197.534 | 15.49 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -8.13 | -0.6 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 189.405 | 14.85 |
Electricity Coming From Utility | 1088.072 | 85.31 |
Surplus Electricity Going To Utility | 1.988 | 0.16 |
Net Electricity From Utility | 1086.084 | 85.15 |
Total On-Site and Utility Electric Sources | 1275.489 | 100.00 |
Total Electricity End Uses | 1275.489 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 68.83 |
Time Setpoint Not Met During Occupied Cooling | 261.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1591.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-15:09 | 27-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 09-JAN-12:09 |
Heating | 0.00 | 52152.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66893.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14115.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38454.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 823.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33167.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8836.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 153461.64 | 60988.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 52152.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 66893.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 14115.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 3918.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 48.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 823.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 33167.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8836.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 82.31 | 40.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 866.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 535.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 106.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 359.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 132.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4039.47 | 173.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 16.52 | 8.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 174.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 107.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 72.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 810.78 | 34.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 16.52 | 8.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 174.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 107.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 72.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 810.78 | 34.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.63 | 0.284596 | 0.242000 | 0.637282 | 0.758924 | 0.500000 | 0.001339 |
CORE_MID VAV BOX COMPONENT | 2.21 | 0.339555 | 0.289000 | 0.637871 | 0.905481 | 0.500000 | 0.001122 |
CORE_TOP VAV BOX COMPONENT | 2.45 | 0.306347 | 0.260000 | 0.636071 | 0.816925 | 0.500000 | 0.001244 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.841760 | 0.187692 | 0.160000 | 0.134682 | 0.500512 | 0.500000 | 0.002030 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.745969 | 0.134083 | 0.114000 | 0.085040 | 0.357555 | 0.500000 | 0.002842 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.930196 | 0.169848 | 0.144000 | 0.133948 | 0.452927 | 0.500000 | 0.002243 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.860183 | 0.116272 | 0.099000 | 0.085158 | 0.310059 | 0.500000 | 0.003277 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.667073 | 0.236843 | 0.201000 | 0.134082 | 0.631582 | 0.500000 | 0.001609 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.639717 | 0.156353 | 0.133000 | 0.085082 | 0.416942 | 0.500000 | 0.002437 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.746607 | 0.211613 | 0.180000 | 0.134389 | 0.564301 | 0.500000 | 0.001800 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.684564 | 0.146101 | 0.124000 | 0.084886 | 0.389602 | 0.500000 | 0.002608 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.718022 | 0.220037 | 0.187000 | 0.134270 | 0.586766 | 0.500000 | 0.001732 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.711532 | 0.374860 | 0.500000 | 0.002710 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.807392 | 0.195681 | 0.166000 | 0.134027 | 0.521817 | 0.500000 | 0.001947 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.769885 | 0.129909 | 0.110000 | 0.084687 | 0.346425 | 0.500000 | 0.002933 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18459.34 |
CORE_MID VAV BOX REHEAT COIL | 19583.37 |
CORE_TOP VAV BOX REHEAT COIL | 34611.87 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15343.76 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10027.11 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15247.26 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9970.56 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10869.95 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7199.96 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10783.56 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7142.69 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11967.25 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7874.28 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11875.43 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7822.82 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.69 | 1.08 | 5.37 | 1.67 | 4.93 | 4.93 | 0.300000 | 0.338173 | 4.93 |
PACU_VAV_MID | 2.61 | 1.08 | 5.21 | 2.04 | 4.68 | 4.68 | 0.300000 | 0.436108 | 4.68 |
PACU_VAV_TOP | 2.91 | 1.07 | 5.82 | 2.94 | 5.58 | 5.58 | 0.300000 | 0.526878 | 5.58 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.93 |
PACU_VAV_MID_OA_CONTROLLER | 4.68 |
PACU_VAV_TOP_OA_CONTROLLER | 5.58 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.93 | 86805.22 | 0.800691 | 1.64 | 28932.18 | 0.800691 |
PACU_VAV_MID COOLING COIL | 4.68 | 83148.00 | 0.800577 | 1.56 | 27713.23 | 0.800577 |
PACU_VAV_TOP COOLING COIL | 5.58 | 96103.55 | 0.800541 | 1.86 | 32031.31 | 0.800541 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 14524.84 |
PACU_VAV_MID HEATING COIL | 15147.80 |
PACU_VAV_TOP HEATING COIL | 14444.89 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.93 |
PACU_VAV_MID FAN | 4.68 |
PACU_VAV_TOP FAN | 5.58 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1525E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1962E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7029E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7403E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3968E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4269E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1033 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7704E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1154 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1963E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7776E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1171E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1523E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1970E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7026E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7411E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3967E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4275E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5329E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6261E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1664E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3686E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4503E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2313E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1986E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2151E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9154E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9272E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8430E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8471E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9297E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9667E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4633E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1530E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1732E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7185E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5459E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1009E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1811E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9268E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.1570E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9298E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9668E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4634E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4925E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1530E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1727E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4247E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5753E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0346E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3065E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3508E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1855E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1370E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1781E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8401E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8835E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7865E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8059E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1030 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.8701E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1131 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3739E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.2806E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9907E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3878E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5433E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0415E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2974E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3491E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1712E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1171E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0360E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4570E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6050E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2813E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2048E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2832E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4956E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9140E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2392E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2526E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1278E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1030 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.8694E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1131 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3732E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.2800E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9902E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3877E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5432E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0414E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2973E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3488E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1710E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1172E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0359E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4571E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6050E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2812E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2047E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2831E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4954E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9139E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2390E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2524E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1276E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 31702.60913 | 31702.60913 | 2.63340 | 2.63340 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7586.25430 | 7586.25430 | 0.36822 | 0.42469 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26592.20887 | 26592.20887 | 2.20717 | 2.20717 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 13844.85703 | 13844.85703 | 0.67609 | 0.67609 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29201.74178 | 29201.74178 | 2.44643 | 2.44643 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24369.21080 | 24369.21080 | 1.19492 | 1.19492 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10048.08902 | 10048.08902 | 0.84176 | 0.84176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10774.76983 | 10774.76983 | 0.52972 | 0.52972 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8904.67055 | 8904.67055 | 0.74597 | 0.74597 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7040.74357 | 7040.74357 | 0.34617 | 0.34617 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11103.75207 | 11103.75207 | 0.93020 | 0.93020 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10707.18714 | 10707.18714 | 0.52639 | 0.52639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10268.06540 | 10268.06540 | 0.86018 | 0.86018 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7001.13794 | 7001.13794 | 0.34422 | 0.34422 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7962.72737 | 7962.72737 | 0.66707 | 0.66707 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7640.34812 | 7640.34812 | 0.37527 | 0.37527 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7636.23670 | 7636.23670 | 0.63972 | 0.63972 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5059.97455 | 5059.97455 | 0.24857 | 0.24857 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8912.12485 | 8912.12485 | 0.74661 | 0.74661 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7579.84319 | 7579.84319 | 0.37229 | 0.37229 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8171.56896 | 8171.56896 | 0.68456 | 0.68456 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 36.45333 | 6.86884E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5019.86343 | 5019.86343 | 0.24659 | 0.24659 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8570.97340 | 8570.97340 | 0.71802 | 0.71802 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8409.50392 | 8409.50392 | 0.41315 | 0.41315 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8493.55338 | 8493.55338 | 0.71153 | 0.71153 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 32.79167 | 6.86302E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5532.65986 | 5532.65986 | 0.27185 | 0.27185 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9637.79032 | 9637.79032 | 0.80739 | 0.80739 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8345.20201 | 8345.20201 | 0.40998 | 0.40998 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9190.12055 | 9190.12055 | 0.76989 | 0.76989 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5496.61759 | 5496.61759 | 0.27007 | 0.27007 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 72013.09 | 4.93063 | 4.93063 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 17783.78 | 1.66741 | 1.66741 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 68946.97 | 4.68035 | 4.68035 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 17796.60 | 2.04114 | 2.04114 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 79432.80 | 5.58274 | 5.58274 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 17735.55 | 2.94142 | 2.94142 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.63340 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28460 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63728 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75892 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33874E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18459.34219 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20717 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33956 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63787 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90548 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12206E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19583.36584 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.44643 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30635 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63607 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81693 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24369E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 34611.87010 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84176 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18769 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13468 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50051 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02992E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15343.75827 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74597 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13408 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11400 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50404E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35755 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84152E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10027.10764 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93020 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16985 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14400 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13395 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45293 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24319E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15247.26393 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86018 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11627 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.90000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51581E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31006 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27680E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9970.56003 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66707 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23684 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13408 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63158 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60866E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10869.95120 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63972 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15635 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13300 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50824E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41694 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43679E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7199.95754 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74661 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21161 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13439 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56430 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80046E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10783.55799 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68456 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14610 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48859E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38960 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60779E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7142.68580 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71802 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22004 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13427 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58677 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73152E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11967.24810 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71153 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37486 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71034E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7874.28351 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80739 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19568 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16600 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13403 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52182 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94704E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11875.42940 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76989 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12991 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46874E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34642 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93282E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7822.81905 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68568 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07572 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.37136 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.66741 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.93063 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.93063 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.33817 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60700 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07553 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.21400 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04114 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.68035 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.68035 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.43611 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.91227 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07490 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.82453 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.94142 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.58274 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.58274 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.52688 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.93063 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.68035 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.58274 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.93063 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.93063 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86805.22337 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80069 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.64338 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28932.18095 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80069 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 14524.83817 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.93063 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.68035 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.68035 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 83147.99831 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80058 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.55996 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27713.22784 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80058 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 15147.80002 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.68035 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.58274 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.58274 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 96103.54574 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80054 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.86073 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32031.31179 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80054 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 14444.89055 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.58274 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 85553.78 | 291921.61 | 11.70 | 2.95 | 3.35 | 3.53 | 3.70 | 10.06 | 11.43 | 12.04 | 12.64 | 4.9459 | 3.9217 | 2.6318 | 1.0858 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 81982.18 | 279734.79 | 11.72 | 2.95 | 3.36 | 3.54 | 3.71 | 10.08 | 11.45 | 12.07 | 12.66 | 4.6948 | 3.7249 | 2.5002 | 1.0277 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 94622.19 | 322864.32 | 11.65 | 2.94 | 3.34 | 3.51 | 3.68 | 10.02 | 11.38 | 11.99 | 12.57 | 5.6000 | 4.4347 | 2.9748 | 1.2376 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.6876681961E-002 | 0.1230436796 | Pass | Pass | 7.1157261704E-002 | 0.2561056467 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9653493290E-002 | 7.7157695220E-002 | Pass | Pass | 3.1336947003E-002 | 0.2445847480 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.4727103768E-002 | 2.9373421247E-002 | Pass | Pass | 0.1129670035 | 0.4355687980 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0339246059E-002 | 2.2184423774E-002 | Pass | Pass | 0.3952726793 | 2.1080837774 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.1612608575E-002 | 8.7164117776E-002 | Pass | Pass | 6.3223207862E-002 | 0.2419692913 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.6240815391E-002 | 6.5205174782E-002 | Pass | Pass | 2.1062536894E-002 | 0.1389040686 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.2855298368E-002 | 4.7986766821E-002 | Pass | Pass | 2.1290310874E-002 | 0.1378689387 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9938217929E-002 | 9.1020059358E-002 | Pass | Pass | 2.1206433470E-002 | 0.1401892993 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1413057052 | 0.1394702855 | Pass | Pass | 5.1653558336E-002 | 0.3005838886 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.5630060817E-002 | 0.1080952314 | Pass | Pass | 2.0528575245E-002 | 0.1333094620 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.4221873116E-002 | 7.1166506618E-002 | Pass | Pass | 7.0418775824E-002 | 0.2549292646 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.5993993066E-002 | 9.7965144637E-002 | Pass | Pass | 7.0979437318E-002 | 0.2564363942 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1255703178 | 0.1570515271 | Pass | Pass | 7.0156049969E-002 | 0.2552688809 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.5276542423E-002 | 0.1203733861 | Pass | Pass | 6.8626641594E-002 | 0.2489248195 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9223612886E-002 | 5.8992035443E-002 | Pass | Pass | 6.3027456415E-002 | 0.2414462161 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.6190870247E-002 | 9.8260228589E-002 | Pass | Pass | 6.3558668189E-002 | 0.2435449119 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1391561029 | 0.1535145205 | Pass | Pass | 7.2570259845E-002 | 0.2781041027 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.6548660253E-002 | 0.1145950322 | Pass | Pass | 6.1086974293E-002 | 0.2326569340 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3260.01 | 50.68 | 0.00 | 1144.21 | 1358.59 | 5813.52 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 37.70 | 0.0000 | Y | 40.40 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 37.70 | 0.0000 | Y | 40.40 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 37.70 | 0.0000 | Y | 40.40 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.79 | 0.0000 | Y | 4.92 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.74 | 0.0000 | Y | 3.11 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.46 | 0.0000 | Y | 4.85 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.48 | 0.0000 | Y | 3.07 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.74 | 0.0000 | Y | 4.91 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.70 | 0.0000 | Y | 3.10 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.43 | 0.0000 | Y | 4.84 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.44 | 0.0000 | Y | 3.07 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.79 | 0.0000 | Y | 4.92 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.74 | 0.0000 | Y | 3.11 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.46 | 0.0000 | Y | 4.85 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.86 | 168.00 | 21.47 | 0.0000 | Y | 3.07 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 169.02 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 41.77 | 41.77 | 4.25 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.77 | 62.77 | 3.30 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.77 | 46.49 | 26.20 | |
Exterior Lighting Total | 3824.74 | 33.75 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86805.22 | 69504.17 | 17301.06 | 0.80 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 83148.00 | 66566.41 | 16581.59 | 0.80 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 96103.55 | 76934.84 | 19168.71 | 0.80 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 85553.8 | 2.95 | 10.06 | N/A | N/A | 11.70 | |
PACU_VAV_MID COOLING COIL | 81982.2 | 2.95 | 10.08 | N/A | N/A | 11.72 | |
PACU_VAV_TOP COOLING COIL | 94622.2 | 2.94 | 10.02 | N/A | N/A | 11.65 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 18459.34 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 19583.37 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 34611.87 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15343.76 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10027.11 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15247.26 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9970.56 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10869.95 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7199.96 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10783.56 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7142.69 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11967.25 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7874.28 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11875.43 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7822.82 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 14524.84 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 15147.80 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 14444.89 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.93 | 10793.19 | 2189.01 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.68 | 10245.34 | 2189.01 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.58 | 12141.83 | 2174.89 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85553.78 | 2.95 | 10.06 | 11.70 | 4.9459 | 3.35 | 11.43 | 3.9217 | 3.53 | 12.04 | 2.6318 | 3.70 | 12.64 | 1.0858 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 81982.18 | 2.95 | 10.08 | 11.72 | 4.6948 | 3.36 | 11.45 | 3.7249 | 3.54 | 12.07 | 2.5002 | 3.71 | 12.66 | 1.0277 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 94622.19 | 2.94 | 10.02 | 11.65 | 5.6000 | 3.34 | 11.38 | 4.4347 | 3.51 | 11.99 | 2.9748 | 3.68 | 12.57 | 1.2376 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 31702.61 | 31702.61 | 32.23 | 2.633 | 2.633 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_MID | 26592.21 | 26592.21 | 27.04 | 2.207 | 2.207 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_TOP | 29201.74 | 29201.74 | 29.69 | 2.446 | 2.446 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00891 | 37.71 | 0.00687 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10048.09 | 10048.09 | 48.46 | 0.842 | 0.842 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00869 | 37.84 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8904.67 | 8904.67 | 67.84 | 0.746 | 0.746 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00863 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11103.75 | 11103.75 | 53.55 | 0.930 | 0.930 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00867 | 38.10 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10268.07 | 10268.07 | 78.23 | 0.860 | 0.860 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00862 | 36.63 | 0.00687 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7962.73 | 7962.73 | 38.40 | 0.667 | 0.667 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00878 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7636.24 | 7636.24 | 58.18 | 0.640 | 0.640 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00868 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8912.12 | 8912.12 | 42.98 | 0.747 | 0.747 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00875 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8171.57 | 8171.57 | 62.26 | 0.685 | 0.685 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00867 | 36.45 | 0.00687 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8570.97 | 8570.97 | 41.34 | 0.718 | 0.718 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00873 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8493.55 | 8493.55 | 64.71 | 0.712 | 0.712 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00865 | 32.79 | 0.00686 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9637.79 | 9637.79 | 46.48 | 0.807 | 0.807 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00871 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9190.12 | 9190.12 | 70.02 | 0.770 | 0.770 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00864 | 36.63 | 0.00687 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7586.25 | 7586.25 | 7.71 | 0.368 | 0.425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_MID | 13844.86 | 13844.86 | 14.08 | 0.676 | 0.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_TOP | 24369.21 | 24369.21 | 24.78 | 1.195 | 1.195 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10774.77 | 10774.77 | 51.97 | 0.530 | 0.530 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7040.74 | 7040.74 | 53.64 | 0.346 | 0.346 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10707.19 | 10707.19 | 51.64 | 0.526 | 0.526 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7001.14 | 7001.14 | 53.34 | 0.344 | 0.344 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7640.35 | 7640.35 | 36.85 | 0.375 | 0.375 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5059.97 | 5059.97 | 38.55 | 0.249 | 0.249 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7579.84 | 7579.84 | 36.56 | 0.372 | 0.372 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5019.86 | 5019.86 | 38.25 | 0.247 | 0.247 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8409.50 | 8409.50 | 40.56 | 0.413 | 0.413 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5532.66 | 5532.66 | 42.15 | 0.272 | 0.272 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8345.20 | 8345.20 | 40.25 | 0.410 | 0.410 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5496.62 | 5496.62 | 41.88 | 0.270 | 0.270 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -5.20 | 0.00281 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.93 | 4.93 | 1.67 | 1.67 | 4.9306 | 1.6674 | 4.9306 | 0.3382 | 0.3000 |
PACU_VAV_MID | 4.68 | 4.68 | 2.04 | 2.04 | 4.6804 | 2.0411 | 4.6804 | 0.4361 | 0.3000 |
PACU_VAV_TOP | 5.58 | 5.58 | 2.94 | 2.94 | 5.5827 | 2.9414 | 5.5827 | 0.5269 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18459.342 | 18459.342 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18459.34 | 12301.49 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 7586.25 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 19583.366 | 19583.366 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19583.37 | 19583.37 | 0.676087 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 13844.86 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 34611.870 | 34611.870 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34611.87 | 34611.87 | 1.194924 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 24369.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 15343.758 | 15343.758 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15343.76 | 15343.76 | 0.529721 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00782047 | 43.8608 | 10774.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10027.108 | 10027.108 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10027.11 | 10027.11 | 0.346171 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781774 | 43.8458 | 7040.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 15247.264 | 15247.264 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15247.26 | 15247.26 | 0.526389 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781920 | 43.8538 | 10707.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9970.560 | 9970.560 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9970.56 | 9970.56 | 0.344219 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781662 | 43.8396 | 7001.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10869.951 | 10869.951 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10869.95 | 10869.95 | 0.375269 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781157 | 43.8114 | 7640.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7199.958 | 7199.958 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7199.96 | 7199.96 | 0.248568 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781905 | 43.8528 | 5059.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10783.558 | 10783.558 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10783.56 | 10783.56 | 0.372287 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00780849 | 43.7943 | 7579.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7142.686 | 7142.686 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7142.69 | 7142.69 | 0.246591 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00781618 | 43.8369 | 5019.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 11967.248 | 11967.248 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11967.25 | 11967.25 | 0.413152 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778350 | 43.6562 | 8409.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7874.284 | 7874.284 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7874.28 | 7874.28 | 0.271848 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778719 | 43.6766 | 5532.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 11875.429 | 11875.429 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11875.43 | 11875.43 | 0.409982 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778033 | 43.6387 | 8345.20 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7822.819 | 7822.819 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7822.82 | 7822.82 | 0.270071 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778475 | 43.6632 | 5496.62 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 86805.223 | 69504.166 | 4.930626 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 81428.28 | 81428.28 | 4.930626 | 26.74 | 15.81 | 0.00844615 | 10.75 | 9.94 | 0.00844615 | 38.10 | 0.00687148 | 18.17 | 19.3910 | 24.00 | 0.00882560 | 41.1846 | 58773.67 | 0.00 | 89507.84 | 65705.29 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 14524.838 | 14524.838 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14524.84 | 14524.84 | 1.479188 | 3.44 | 2.05 | 0.00449077 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 64.6368 | 19.60 | 0.00726009 | 44.4378 | 13263.38 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 83147.998 | 66566.405 | 4.680352 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 77997.60 | 77997.60 | 4.680352 | 26.89 | 15.84 | 0.00843089 | 10.75 | 9.92 | 0.00843089 | 38.10 | 0.00687148 | 18.17 | 20.4280 | 24.00 | 0.00883312 | 41.2190 | 55659.46 | 0.00 | 85736.75 | 62935.30 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 15147.800 | 15147.800 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15147.80 | 15147.80 | 1.404106 | 2.52 | 1.33 | 0.00431898 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 68.0932 | 19.40 | 0.00732391 | 45.3767 | 15777.84 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 96103.546 | 76934.835 | 5.582739 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 90266.06 | 90266.06 | 5.582739 | 26.40 | 15.70 | 0.00844770 | 10.76 | 9.95 | 0.00844770 | 37.97 | 0.00687126 | 18.13 | 17.1260 | 24.00 | 0.00877464 | 40.9498 | 66442.51 | 0.00 | 99095.66 | 72727.89 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 14444.891 | 14444.891 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14444.89 | 14444.89 | 1.674822 | 4.58 | 3.13 | 0.00487392 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 57.0867 | 17.64 | 0.00748044 | 51.7475 | 18389.45 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 18459.342 | 18459.342 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18459.34 | 12301.49 | 1.0000 | 0.44351838 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18459.34 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 7586.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 19583.366 | 19583.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19583.37 | 19583.37 | 1.0000 | 0.70605913 | 0.676087 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19583.37 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 13844.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 34611.870 | 34611.870 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34611.87 | 34611.87 | 1.0000 | 1.24789717 | 1.194924 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34611.87 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 24369.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15343.758 | 15343.758 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15343.76 | 15343.76 | 1.0000 | 0.55320422 | 0.529721 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15343.76 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782047 | 21.00 | 0.00782047 | 43.8608 | 10774.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10027.108 | 10027.108 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10027.11 | 10027.11 | 1.0000 | 0.36151757 | 0.346171 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10027.11 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781774 | 21.00 | 0.00781774 | 43.8458 | 7040.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15247.264 | 15247.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15247.26 | 15247.26 | 1.0000 | 0.54972521 | 0.526389 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15247.26 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781920 | 21.00 | 0.00781920 | 43.8538 | 10707.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9970.560 | 9970.560 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9970.56 | 9970.56 | 1.0000 | 0.35947880 | 0.344219 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9970.56 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781662 | 21.00 | 0.00781662 | 43.8396 | 7001.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10869.951 | 10869.951 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10869.95 | 10869.95 | 1.0000 | 0.39190547 | 0.375269 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10869.95 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781157 | 21.00 | 0.00781157 | 43.8114 | 7640.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7199.958 | 7199.958 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7199.96 | 7199.96 | 1.0000 | 0.25958744 | 0.248568 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7199.96 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781905 | 21.00 | 0.00781905 | 43.8528 | 5059.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10783.558 | 10783.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10783.56 | 10783.56 | 1.0000 | 0.38879065 | 0.372287 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10783.56 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00780849 | 21.00 | 0.00780849 | 43.7943 | 7579.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7142.686 | 7142.686 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7142.69 | 7142.69 | 1.0000 | 0.25752256 | 0.246591 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7142.69 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781618 | 21.00 | 0.00781618 | 43.8369 | 5019.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11967.248 | 11967.248 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11967.25 | 11967.25 | 1.0000 | 0.43146744 | 0.413152 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11967.25 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778350 | 21.00 | 0.00778350 | 43.6562 | 8409.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7874.284 | 7874.284 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7874.28 | 7874.28 | 1.0000 | 0.28389960 | 0.271848 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7874.28 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778719 | 21.00 | 0.00778719 | 43.6766 | 5532.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11875.429 | 11875.429 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11875.43 | 11875.43 | 1.0000 | 0.42815701 | 0.409982 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11875.43 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778033 | 21.00 | 0.00778033 | 43.6387 | 8345.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7822.819 | 7822.819 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7822.82 | 7822.82 | 1.0000 | 0.28204410 | 0.270071 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7822.82 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778475 | 21.00 | 0.00778475 | 43.6632 | 5496.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86805.223 | 69504.166 | 4.930626 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5410 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.930626 | 5.14920918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 81428.28 | 81428.28 | 0.9381 | 5.14920918 | 4.930626 | 26.74 | 15.81 | 0.00844615 | 48409.5 | 10.75 | 9.94 | 0.00844615 | 32090.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10793.194 | 70635.09 | 38.10 | 0.00687148 | 18.17 | 0.95610000 | 19.3910 | 24.00 | 0.00882560 | 24.00 | 0.00882560 | 41.1846 | 58773.67 | 0.00 | 89507.84 | 65705.29 | 4.94585434 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.67 | 13.23 | 0.00929774 | 37224.8 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14524.838 | 14524.838 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.930626 | 5.14920918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14524.84 | 14524.84 | 1.0000 | 1.54476275 | 1.479188 | 3.44 | 2.05 | 0.00449077 | 14719.4 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14524.84 | -5.20 | 0.00280840 | -5.20 | 0.95610000 | 64.6368 | 19.24 | 0.00756582 | 19.60 | 0.00726009 | 44.4378 | 13263.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 83147.998 | 66566.405 | 4.680352 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5126 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.680352 | 4.88784011 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 77997.60 | 77997.60 | 0.9381 | 4.88784011 | 4.680352 | 26.89 | 15.84 | 0.00843089 | 48527.0 | 10.75 | 9.92 | 0.00843089 | 32051.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10245.342 | 67752.26 | 38.10 | 0.00687148 | 18.17 | 0.95610000 | 20.4280 | 24.00 | 0.00883312 | 24.00 | 0.00883312 | 41.2190 | 55659.46 | 0.00 | 85736.75 | 62935.30 | 4.69480737 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.55 | 13.17 | 0.00928044 | 37060.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15147.800 | 15147.800 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.680352 | 4.88784011 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15147.80 | 15147.80 | 1.0000 | 1.46635203 | 1.404106 | 2.52 | 1.33 | 0.00431898 | 13353.6 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15147.80 | -5.20 | 0.00280840 | -5.20 | 0.95610000 | 68.0932 | 18.99 | 0.00754275 | 19.40 | 0.00732391 | 45.3767 | 15777.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 96103.546 | 76934.835 | 5.582739 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5439 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.582739 | 5.83023161 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 90266.06 | 90266.06 | 0.9393 | 5.83023161 | 5.582739 | 26.40 | 15.70 | 0.00844770 | 48068.2 | 10.76 | 9.95 | 0.00844770 | 32107.6 | -999.0 | -999.00 | -999.00 | -999.00 | 12141.834 | 78124.23 | 37.97 | 0.00687126 | 18.13 | 0.95610000 | 17.1260 | 24.00 | 0.00877464 | 24.00 | 0.00877464 | 40.9498 | 66442.51 | 0.00 | 99095.66 | 72727.89 | 5.59998153 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.96 | 13.39 | 0.00933855 | 37626.7 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14444.891 | 14444.891 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.582739 | 5.83023161 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14444.89 | 14444.89 | 1.0000 | 1.74906948 | 1.674822 | 4.58 | 3.13 | 0.00487392 | 16834.4 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14444.89 | -5.20 | 0.00280840 | -5.20 | 0.95610000 | 57.0867 | 17.59 | 0.00762164 | 17.64 | 0.00748044 | 51.7475 | 18389.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.93 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.68 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.58 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2226.33 | 2394.50 | 32.17 |
CORE_MID | 2049.50 | 2852.83 | 55.17 |
CORE_TOP | 2327.50 | 3079.50 | 382.83 |
PERIMETER_TOP_ZN_3 | 3164.33 | 3384.67 | 1256.83 |
PERIMETER_TOP_ZN_2 | 3155.83 | 3041.83 | 965.50 |
PERIMETER_TOP_ZN_1 | 3048.67 | 2556.67 | 784.33 |
PERIMETER_TOP_ZN_4 | 3282.83 | 3074.50 | 1143.67 |
PERIMETER_BOT_ZN_3 | 2659.50 | 3335.17 | 751.83 |
PERIMETER_BOT_ZN_2 | 2756.50 | 2860.17 | 457.50 |
PERIMETER_BOT_ZN_1 | 2604.50 | 2599.00 | 380.67 |
PERIMETER_BOT_ZN_4 | 2785.50 | 2876.33 | 509.67 |
PERIMETER_MID_ZN_3 | 2723.33 | 3214.00 | 744.83 |
PERIMETER_MID_ZN_2 | 2468.33 | 2534.33 | 604.33 |
PERIMETER_MID_ZN_1 | 2821.50 | 2289.67 | 445.83 |
PERIMETER_MID_ZN_4 | 2915.67 | 2906.33 | 696.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4253.33 | 3877.00 | 1591.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.83 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.33 | 0.00 | 0.33 |
PERIMETER_TOP_ZN_3 | 2.00 | 30.33 | 0.33 | 20.17 |
PERIMETER_TOP_ZN_2 | 1.50 | 75.50 | 0.00 | 63.67 |
PERIMETER_TOP_ZN_1 | 0.50 | 61.83 | 0.00 | 51.83 |
PERIMETER_TOP_ZN_4 | 1.00 | 66.83 | 0.00 | 39.50 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 48.67 | 0.00 | 46.83 |
PERIMETER_BOT_ZN_1 | 68.50 | 107.50 | 68.50 | 106.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 46.67 | 0.00 | 29.83 |
PERIMETER_MID_ZN_3 | 0.00 | 8.00 | 0.00 | 5.33 |
PERIMETER_MID_ZN_2 | 0.00 | 67.17 | 0.00 | 63.00 |
PERIMETER_MID_ZN_1 | 0.00 | 48.67 | 0.00 | 46.17 |
PERIMETER_MID_ZN_4 | 0.00 | 58.17 | 0.00 | 36.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 70.67 | 305.83 | 68.83 | 261.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.813 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.650 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.632 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.710 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 1.129 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 1.157 | 0.078 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 1.014 | 0.082 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.625 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 1.010 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.949 | 0.837 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.896 | 0.044 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.710 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 1.068 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 1.171 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 1.011 | 0.068 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.24 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12848362.78 | 0.00 | 12848362.78 | 0.00 | 12848362.78 | 13393058.27 | 5543.68 | 206.96 | 3009.36 | 24.53 |
CORE_MID | 10303085.25 | 0.00 | 10303085.25 | 0.00 | 10303085.25 | 13393058.27 | 5821.37 | 252.17 | 2686.47 | 28.00 |
CORE_TOP | 10067799.62 | 0.00 | 10067799.62 | 0.00 | 10067799.62 | 13393058.27 | 5759.96 | 408.59 | 2591.44 | 57.47 |
PERIMETER_TOP_ZN_3 | 2380734.06 | 0.00 | 2380734.06 | 511255.28 | 2891989.34 | 2823374.22 | 4298.03 | 246.23 | 4215.75 | 57.47 |
PERIMETER_TOP_ZN_2 | 2385420.94 | 0.00 | 2385420.94 | 340834.81 | 2726255.74 | 1787429.43 | 4212.37 | 324.35 | 4223.28 | 57.47 |
PERIMETER_TOP_ZN_1 | 3864940.22 | 0.00 | 3864940.22 | 511255.28 | 4376195.50 | 2823374.22 | 4148.57 | 433.26 | 4178.16 | 57.47 |
PERIMETER_TOP_ZN_4 | 2148523.58 | 0.00 | 2148523.58 | 340834.81 | 2489358.39 | 1787312.18 | 4226.25 | 279.24 | 4254.50 | 57.47 |
PERIMETER_BOT_ZN_3 | 2089718.01 | 0.00 | 2089718.01 | 271832.90 | 2361550.91 | 2823374.22 | 5484.91 | 358.61 | 2916.48 | 24.53 |
PERIMETER_BOT_ZN_2 | 2127236.41 | 0.00 | 2127236.41 | 181220.85 | 2308457.26 | 1787429.43 | 4614.36 | 215.86 | 3929.77 | 24.53 |
PERIMETER_BOT_ZN_1 | 3165160.40 | 0.00 | 3165160.40 | 2920111.07 | 6085271.47 | 2823374.22 | 4605.63 | 222.05 | 3932.32 | 24.53 |
PERIMETER_BOT_ZN_4 | 1889785.05 | 0.00 | 1889785.05 | 181220.85 | 2071005.89 | 1787312.18 | 4726.19 | 300.98 | 3732.84 | 24.53 |
PERIMETER_MID_ZN_3 | 2371735.52 | 0.00 | 2371735.52 | 425581.69 | 2797317.20 | 2823374.22 | 4427.31 | 333.59 | 3999.10 | 28.00 |
PERIMETER_MID_ZN_2 | 2243223.62 | 0.00 | 2243223.62 | 283719.42 | 2526943.04 | 1601953.02 | 4181.90 | 408.54 | 4169.56 | 937.00 |
PERIMETER_MID_ZN_1 | 3901924.36 | 0.00 | 3901924.36 | 425581.69 | 4327506.05 | 2823374.22 | 4150.49 | 373.87 | 4235.64 | 28.00 |
PERIMETER_MID_ZN_4 | 2133231.04 | 0.00 | 2133231.04 | 283719.42 | 2416950.45 | 1787312.18 | 4324.03 | 453.89 | 3982.07 | 28.00 |
Total Facility | 63920880.85 | 0.00 | 63920880.85 | 6677168.04 | 70598048.89 | 67658168.57 | 6422.37 | 852.01 | 4710.16 | 977.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5977 | 0.0000 | 0.5977 | 0.0000 | 0.5977 | 0.4247 | 2751.20 | 206.96 | 2984.84 |
CORE_MID | 0.4784 | 0.0000 | 0.4784 | 0.0000 | 0.4784 | 0.4247 | 3032.37 | 252.17 | 2658.47 |
CORE_TOP | 0.4657 | 0.0000 | 0.4657 | 0.0000 | 0.4657 | 0.4247 | 2986.35 | 408.59 | 2548.06 |
PERIMETER_TOP_ZN_3 | 0.1103 | 0.0000 | 0.1103 | 0.0120 | 0.1223 | 0.0895 | 1524.41 | 246.23 | 4172.36 |
PERIMETER_TOP_ZN_2 | 0.1108 | 0.0000 | 0.1108 | 0.0080 | 0.1189 | 0.0567 | 1438.75 | 324.35 | 4179.90 |
PERIMETER_TOP_ZN_1 | 0.1796 | 0.0000 | 0.1796 | 0.0120 | 0.1917 | 0.0895 | 1374.96 | 433.26 | 4134.78 |
PERIMETER_TOP_ZN_4 | 0.0996 | 0.0000 | 0.0996 | 0.0080 | 0.1076 | 0.0567 | 1452.64 | 279.24 | 4211.12 |
PERIMETER_BOT_ZN_3 | 0.0971 | 0.0000 | 0.0971 | 0.0064 | 0.1035 | 0.0895 | 2692.44 | 358.61 | 2891.95 |
PERIMETER_BOT_ZN_2 | 0.0991 | 0.0000 | 0.0991 | 0.0043 | 0.1033 | 0.0567 | 1821.89 | 215.86 | 3905.24 |
PERIMETER_BOT_ZN_1 | 0.1473 | 0.0000 | 0.1473 | 0.1302 | 0.2775 | 0.0895 | 1813.16 | 222.05 | 3907.79 |
PERIMETER_BOT_ZN_4 | 0.0879 | 0.0000 | 0.0879 | 0.0043 | 0.0922 | 0.0567 | 1933.71 | 300.98 | 3708.31 |
PERIMETER_MID_ZN_3 | 0.1102 | 0.0000 | 0.1102 | 0.0100 | 0.1202 | 0.0895 | 1638.31 | 333.59 | 3971.10 |
PERIMETER_MID_ZN_2 | 0.1047 | 0.0000 | 0.1047 | 0.0071 | 0.1119 | 0.0567 | 1392.90 | 408.54 | 3232.56 |
PERIMETER_MID_ZN_1 | 0.1817 | 0.0000 | 0.1817 | 0.0100 | 0.1917 | 0.0895 | 1361.49 | 373.87 | 4207.64 |
PERIMETER_MID_ZN_4 | 0.0992 | 0.0000 | 0.0992 | 0.0067 | 0.1059 | 0.0567 | 1535.03 | 453.89 | 3954.07 |
Total Facility | 2.9694 | 0.0000 | 2.9694 | 0.2191 | 3.1886 | 2.1513 | 3619.03 | 852.01 | 4655.99 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 24124957.53 | 0.00 | 24124957.53 | 22614548.33 | 4090.27 | 2.09 | 4667.63 | 24.53 |
PACU_VAV_MID | 22852127.68 | 0.00 | 22852127.68 | 22429071.92 | 4060.10 | 2.18 | 4697.72 | 28.00 |
PACU_VAV_TOP | 22736719.23 | 0.00 | 22736719.23 | 22614548.33 | 4055.81 | 1.35 | 4702.84 | 57.45 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1224 | 0.0000 | 1.1224 | 0.7171 | 1297.80 | 2.09 | 4643.11 |
PACU_VAV_MID | 1.0623 | 0.0000 | 1.0623 | 0.7084 | 1271.10 | 2.18 | 4669.72 |
PACU_VAV_TOP | 1.0536 | 0.0000 | 1.0536 | 0.7171 | 1282.19 | 1.35 | 4659.46 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 288.77 | 2442.90 | 0.00 | 0.00 | 0.00 | 2057.00 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 113.72 | 2514.52 | 0.00 | 0.00 | 0.00 | 2192.48 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 58.16 | 2550.56 | 0.00 | 0.00 | 0.00 | 2247.51 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.0143 | 1.9144 | 0.0000 | 0.0000 | 0.0000 | 0.8494 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.9885 | 1.7492 | 0.0000 | 0.0000 | 0.0000 | 0.8446 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.9584 | 1.7286 | 0.0000 | 0.0000 | 0.0000 | 0.8437 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1275.49 | 11254.15 | 16-JUL-17:30 | 153461.64 | 20-JUL-15:10 |
Electricity:Building | 816.77 | 11083.97 | 14-MAY-17:10 | 57297.77 | 13-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 218.88 | 3050.43 | 01-JAN-00:10 | 16300.18 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 816.77 | 11083.97 | 14-MAY-17:10 | 57297.77 | 13-OCT-07:10 |
InteriorLights:Electricity | 169.02 | 784.09 | 01-JAN-09:00 | 17941.79 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 40.40 | 196.75 | 01-JAN-00:10 | 3541.90 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 169.02 | 784.09 | 01-JAN-09:00 | 17941.79 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 169.02 | 784.09 | 01-JAN-09:00 | 17941.79 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 40.40 | 196.75 | 01-JAN-00:10 | 3541.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 169.02 | 784.09 | 01-JAN-09:00 | 17941.79 | 22-NOV-17:00 |
Electricity:Zone:CORE_MID | 155.82 | 2028.29 | 01-JAN-00:10 | 10350.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 40.40 | 196.75 | 01-JAN-00:10 | 3541.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 40.40 | 196.75 | 01-JAN-00:10 | 3541.90 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.82 | 2028.29 | 01-JAN-00:10 | 10350.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 40.40 | 196.75 | 01-JAN-00:10 | 3541.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 40.40 | 196.75 | 01-JAN-00:10 | 3541.90 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.26 | 405.89 | 16-APR-17:10 | 2181.91 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.92 | 19.78 | 01-JAN-09:00 | 746.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.92 | 19.78 | 01-JAN-09:00 | 746.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.51 | 256.94 | 14-MAY-17:10 | 1381.27 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.11 | 12.52 | 01-JAN-08:10 | 472.70 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.11 | 12.52 | 01-JAN-08:10 | 472.70 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.18 | 405.88 | 19-MAR-17:10 | 2181.90 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.85 | 19.78 | 01-JAN-08:10 | 746.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.85 | 19.78 | 01-JAN-08:10 | 746.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.47 | 256.94 | 12-MAR-17:10 | 1381.24 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.07 | 12.52 | 01-JAN-09:00 | 472.67 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.07 | 12.52 | 01-JAN-09:00 | 472.67 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.24 | 405.89 | 02-APR-17:10 | 2181.91 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.91 | 19.78 | 01-JAN-09:00 | 746.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.91 | 19.78 | 01-JAN-09:00 | 746.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.51 | 256.94 | 07-MAY-17:10 | 1381.27 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.10 | 12.52 | 01-JAN-08:10 | 472.70 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.10 | 12.52 | 01-JAN-08:10 | 472.70 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.17 | 405.88 | 12-MAR-17:10 | 2181.90 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.84 | 19.78 | 01-JAN-08:10 | 746.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.84 | 19.78 | 01-JAN-08:10 | 746.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.47 | 256.94 | 12-MAR-17:10 | 1381.24 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.07 | 12.52 | 01-JAN-09:00 | 472.67 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.07 | 12.52 | 01-JAN-09:00 | 472.67 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.26 | 405.89 | 16-APR-17:10 | 2181.91 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.92 | 19.78 | 01-JAN-09:00 | 746.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.92 | 19.78 | 01-JAN-09:00 | 746.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.51 | 256.94 | 14-MAY-17:10 | 1381.27 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.11 | 12.52 | 01-JAN-08:10 | 472.70 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.11 | 12.52 | 01-JAN-08:10 | 472.70 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.18 | 405.88 | 19-MAR-17:10 | 2181.90 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.85 | 19.78 | 01-JAN-08:10 | 746.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.85 | 19.78 | 01-JAN-08:10 | 746.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.47 | 256.94 | 12-MAR-17:10 | 1381.24 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.07 | 12.52 | 01-JAN-09:00 | 472.67 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.07 | 12.52 | 01-JAN-09:00 | 472.67 | 22-NOV-17:00 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 189.41 | -0.00 | 18-JAN-17:20 | 26813.75 | 05-MAY-12:30 |
ElectricityProduced:Plant | 189.41 | -0.00 | 18-JAN-17:20 | 26813.75 | 05-MAY-12:30 |
Photovoltaic:ElectricityProduced | 197.53 | 0.00 | 01-JAN-00:10 | 29076.50 | 22-APR-12:30 |
PowerConversion:ElectricityProduced | -8.13 | -2262.75 | 22-APR-12:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 424.82 | 168.34 | 01-JAN-00:10 | 100884.84 | 20-JUL-15:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.87 | 11-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 828.87 | 11-DEC-17:00 |
ElectricityPurchased:Facility | 1088.07 | 0.00 | 01-JAN-10:20 | 145937.95 | 20-JUL-15:10 |
ElectricityPurchased:Plant | 1088.07 | 0.00 | 01-JAN-10:20 | 145937.95 | 20-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1088.07 | 0.00 | 01-JAN-10:20 | 145937.95 | 20-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1088.07 | 0.00 | 01-JAN-10:20 | 145937.95 | 20-JUL-15:10 |
ElectricitySurplusSold:Facility | 1.99 | 0.00 | 01-JAN-00:10 | 12997.29 | 23-APR-12:00 |
ElectricitySurplusSold:Plant | 1.99 | 0.00 | 01-JAN-00:10 | 12997.29 | 23-APR-12:00 |
Cogeneration:ElectricitySurplusSold | 1.99 | 0.00 | 01-JAN-00:10 | 12997.29 | 23-APR-12:00 |
General:Cogeneration:ElectricitySurplusSold | 1.99 | 0.00 | 01-JAN-00:10 | 12997.29 | 23-APR-12:00 |
ElectricityNet:Facility | 1086.08 | -12997.29 | 23-APR-12:00 | 145937.95 | 20-JUL-15:10 |
ElectricityNet:Plant | 1086.08 | -12997.29 | 23-APR-12:00 | 145937.95 | 20-JUL-15:10 |
Cogeneration:ElectricityNet | 1086.08 | -12997.29 | 23-APR-12:00 | 145937.95 | 20-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1086.08 | -12997.29 | 23-APR-12:00 | 145937.95 | 20-JUL-15:10 |
Heating:Electricity | 25.99 | 0.00 | 01-JAN-00:10 | 95331.58 | 27-DEC-07:10 |
General:Heating:Electricity | 25.99 | 0.00 | 01-JAN-00:10 | 95331.58 | 27-DEC-07:10 |
Fans:Electricity | 113.49 | 0.00 | 01-JAN-00:10 | 33167.10 | 20-JUL-15:10 |
General:Fans:Electricity | 113.49 | 0.00 | 01-JAN-00:10 | 33167.10 | 20-JUL-15:10 |
ExteriorLights:Electricity | 33.75 | 0.00 | 01-JAN-07:20 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 33.75 | 0.00 | 01-JAN-07:20 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 273.72 | 0.00 | 01-JAN-00:10 | 69302.45 | 03-JUL-14:30 |
General:Cooling:Electricity | 273.72 | 0.00 | 01-JAN-00:10 | 69302.45 | 03-JUL-14:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 4.75 | 0.00 | 01-JAN-00:10 | 504.16 | 22-NOV-17:10 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 159.67 | 1886.44 | 17-JAN-06:20 | 60988.56 | 27-DEC-07:20 |
NaturalGas:HVAC | 37.17 | 0.00 | 01-JAN-00:10 | 53012.66 | 27-DEC-07:30 |
Heating:NaturalGas | 37.17 | 0.00 | 01-JAN-00:10 | 53012.66 | 27-DEC-07:30 |
General:Heating:NaturalGas | 37.17 | 0.00 | 01-JAN-00:10 | 53012.66 | 27-DEC-07:30 |
NaturalGas:Plant | 122.50 | 1886.44 | 06-JAN-08:10 | 9950.60 | 27-JAN-12:10 |
WaterSystems:NaturalGas | 122.50 | 1886.44 | 06-JAN-08:10 | 9950.60 | 27-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 122.50 | 1886.44 | 06-JAN-08:10 | 9950.60 | 27-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2324.70 | 0.00 | 01-JAN-00:10 | 400680.80 | 20-JUL-15:10 |
EnergyTransfer:Building | 1148.85 | 0.00 | 01-JAN-00:10 | 160199.31 | 03-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 201.94 | 0.00 | 01-JAN-00:10 | 23106.10 | 05-SEP-07:40 |
Heating:EnergyTransfer | 30.34 | 0.00 | 01-JAN-00:10 | 83635.88 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 30.34 | 0.00 | 01-JAN-00:10 | 83635.88 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1118.51 | 0.00 | 01-JAN-00:10 | 160199.31 | 03-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 201.94 | 0.00 | 01-JAN-00:10 | 23106.10 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer | 1118.51 | 0.00 | 01-JAN-00:10 | 160199.31 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 201.94 | 0.00 | 01-JAN-00:10 | 23106.10 | 05-SEP-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.53 | 0.00 | 01-JAN-00:10 | 11685.32 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.17 | 0.00 | 01-JAN-00:10 | 8371.03 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.17 | 0.00 | 01-JAN-00:10 | 8371.03 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.36 | 0.00 | 01-JAN-00:10 | 11685.32 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 45.36 | 0.00 | 01-JAN-00:10 | 11685.32 | 03-JUL-13:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.94 | 0.00 | 01-JAN-00:10 | 5722.32 | 03-JUL-10:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.26 | 0.00 | 01-JAN-00:10 | 2770.53 | 04-DEC-12:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.26 | 0.00 | 01-JAN-00:10 | 2770.53 | 04-DEC-12:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.69 | 0.00 | 01-JAN-00:10 | 5722.32 | 03-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.69 | 0.00 | 01-JAN-00:10 | 5722.32 | 03-JUL-10:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.75 | 0.00 | 01-JAN-00:10 | 5109.25 | 03-JUL-15:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.10 | 0.00 | 01-JAN-00:10 | 1740.84 | 04-DEC-08:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.10 | 0.00 | 01-JAN-00:10 | 1740.84 | 04-DEC-08:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.65 | 0.00 | 01-JAN-00:10 | 5109.25 | 03-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.65 | 0.00 | 01-JAN-00:10 | 5109.25 | 03-JUL-15:10 |
EnergyTransfer:Zone:CORE_MID | 155.61 | 0.00 | 01-JAN-00:10 | 18970.77 | 19-JUN-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 3838.33 | 17-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 3838.33 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 155.60 | 0.00 | 01-JAN-00:10 | 18970.77 | 19-JUN-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 155.60 | 0.00 | 01-JAN-00:10 | 18970.77 | 19-JUN-07:20 |
EnergyTransfer:Zone:CORE_TOP | 154.30 | 0.00 | 01-JAN-00:10 | 20677.57 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.76 | 0.00 | 01-JAN-00:10 | 15411.15 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.76 | 0.00 | 01-JAN-00:10 | 15411.15 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 153.54 | 0.00 | 01-JAN-00:10 | 20677.57 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 153.54 | 0.00 | 01-JAN-00:10 | 20677.57 | 03-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.57 | 0.00 | 01-JAN-00:10 | 7749.10 | 04-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.32 | 0.00 | 01-JAN-00:10 | 7749.10 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.32 | 0.00 | 01-JAN-00:10 | 7749.10 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.24 | 0.00 | 01-JAN-00:10 | 7746.43 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.24 | 0.00 | 01-JAN-00:10 | 7746.43 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.57 | 0.00 | 01-JAN-00:10 | 8331.97 | 03-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.39 | 0.00 | 01-JAN-00:10 | 5259.08 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.39 | 0.00 | 01-JAN-00:10 | 5259.08 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.18 | 0.00 | 01-JAN-00:10 | 8331.97 | 03-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.18 | 0.00 | 01-JAN-00:10 | 8331.97 | 03-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 62.27 | 0.00 | 01-JAN-00:10 | 11312.39 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.67 | 0.00 | 01-JAN-00:10 | 7455.51 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.67 | 0.00 | 01-JAN-00:10 | 7455.51 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.60 | 0.00 | 01-JAN-00:10 | 11312.39 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.60 | 0.00 | 01-JAN-00:10 | 11312.39 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.67 | 0.00 | 01-JAN-00:10 | 9202.15 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.84 | 0.00 | 01-JAN-00:10 | 5020.03 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.84 | 0.00 | 01-JAN-00:10 | 5020.03 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.83 | 0.00 | 01-JAN-00:10 | 9202.15 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.83 | 0.00 | 01-JAN-00:10 | 9202.15 | 15-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.38 | 0.00 | 01-JAN-00:10 | 6597.19 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.62 | 0.00 | 01-JAN-00:10 | 3399.66 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.62 | 0.00 | 01-JAN-00:10 | 3399.66 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.76 | 0.00 | 01-JAN-00:10 | 6597.19 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.76 | 0.00 | 01-JAN-00:10 | 6597.19 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 36.59 | 0.00 | 01-JAN-00:10 | 7299.82 | 03-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.16 | 0.00 | 01-JAN-00:10 | 2341.24 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.16 | 0.00 | 01-JAN-00:10 | 2341.24 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 36.42 | 0.00 | 01-JAN-00:10 | 7299.82 | 03-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 36.42 | 0.00 | 01-JAN-00:10 | 7299.82 | 03-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 58.65 | 0.00 | 01-JAN-00:10 | 10410.50 | 03-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.99 | 0.00 | 01-JAN-00:10 | 9440.21 | 27-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.99 | 0.00 | 01-JAN-00:10 | 9440.21 | 27-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.65 | 0.00 | 01-JAN-00:10 | 10410.50 | 03-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.65 | 0.00 | 01-JAN-00:10 | 10410.50 | 03-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 35.44 | 0.00 | 01-JAN-00:10 | 7607.73 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 2301.19 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 2301.19 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 35.25 | 0.00 | 01-JAN-00:10 | 7607.73 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 35.25 | 0.00 | 01-JAN-00:10 | 7607.73 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.63 | 0.00 | 01-JAN-00:10 | 7010.33 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.77 | 0.00 | 01-JAN-00:10 | 4734.82 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.77 | 0.00 | 01-JAN-00:10 | 4734.82 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 38.86 | 0.00 | 01-JAN-00:10 | 7010.33 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 38.86 | 0.00 | 01-JAN-00:10 | 7010.33 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.26 | 0.00 | 01-JAN-00:10 | 7993.27 | 30-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.34 | 0.00 | 01-JAN-00:10 | 3423.97 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.34 | 0.00 | 01-JAN-00:10 | 3423.97 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.92 | 0.00 | 01-JAN-00:10 | 7993.27 | 30-MAY-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.92 | 0.00 | 01-JAN-00:10 | 7993.27 | 30-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 61.20 | 0.00 | 01-JAN-00:10 | 10091.69 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.33 | 0.00 | 01-JAN-00:10 | 4729.02 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.33 | 0.00 | 01-JAN-00:10 | 4729.02 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 60.87 | 0.00 | 01-JAN-00:10 | 10091.69 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 60.87 | 0.00 | 01-JAN-00:10 | 10091.69 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.56 | 0.00 | 01-JAN-00:10 | 8525.68 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.41 | 0.00 | 01-JAN-00:10 | 3331.24 | 27-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.41 | 0.00 | 01-JAN-00:10 | 3331.24 | 27-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.15 | 0.00 | 01-JAN-00:10 | 8525.68 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.15 | 0.00 | 01-JAN-00:10 | 8525.68 | 15-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 42.69 | 0.00 | 01-JAN-00:10 | 5642.44 | 31-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5642.44 | 31-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5642.44 | 31-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5642.44 | 31-JAN-12:10 |
EnergyTransfer:HVAC | 1133.16 | 0.00 | 01-JAN-00:10 | 312062.70 | 20-JUL-15:10 |
HeatingCoils:EnergyTransfer | 55.72 | 0.00 | 01-JAN-00:10 | 134567.26 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 1077.44 | 0.00 | 01-JAN-00:10 | 312062.70 | 20-JUL-15:10 |
EnergyTransfer:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5642.44 | 31-JAN-12:10 |
WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5642.44 | 31-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5642.44 | 31-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -201.936 | 0.000 | 0.000 | 32.762 | 40.399 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.708 |
CORE_MID | 0.000 | 0.000 | 0.008 | -155.603 | 0.000 | 0.000 | 33.222 | 40.399 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -33.450 |
CORE_TOP | 0.000 | 0.000 | 0.764 | -153.536 | 0.000 | 0.000 | 33.794 | 40.399 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -36.846 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.323 | -39.242 | 0.000 | 0.000 | 7.302 | 4.923 | 24.333 | 19.093 | 0.000 | 0.482 | 6.675 | 0.000 | -23.594 | 0.000 | -3.296 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.386 | -39.180 | 0.000 | 0.000 | 4.508 | 3.108 | 15.404 | 38.141 | 0.000 | 0.312 | 0.001 | 0.000 | -14.856 | 0.000 | -2.297 | -6.525 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.672 | -60.597 | 0.000 | 0.000 | 7.064 | 4.848 | 24.332 | 65.238 | 0.000 | 0.472 | 0.001 | 0.000 | -22.794 | 0.000 | -3.601 | -16.635 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.844 | -38.826 | 0.000 | 0.000 | 4.569 | 3.071 | 15.403 | 38.400 | 0.000 | 0.302 | 0.001 | 0.000 | -15.911 | 0.000 | -2.322 | -6.530 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.625 | -34.759 | 0.000 | 0.000 | 7.270 | 4.912 | 24.333 | 19.466 | 0.000 | 0.285 | 4.321 | 0.000 | -24.604 | 0.000 | -1.847 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.161 | -36.425 | 0.000 | 0.000 | 4.466 | 3.103 | 15.404 | 38.305 | 0.000 | 0.173 | 0.001 | 0.000 | -15.910 | 0.000 | -1.326 | -7.951 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.990 | -54.653 | 0.000 | 0.000 | 7.092 | 4.841 | 24.332 | 65.748 | 0.000 | 5.287 | 0.003 | 0.000 | -24.523 | 0.000 | -18.008 | -14.107 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.194 | -35.247 | 0.000 | 0.000 | 4.518 | 3.066 | 15.403 | 38.662 | 0.000 | 0.167 | 0.000 | 0.000 | -17.081 | 0.000 | -1.340 | -8.343 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.772 | -38.856 | 0.000 | 0.000 | 7.219 | 4.923 | 24.333 | 18.998 | 0.000 | 0.415 | 10.273 | 0.000 | -25.127 | 0.000 | -2.949 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.338 | -36.922 | 0.000 | 0.000 | 3.291 | 3.108 | 15.404 | 37.914 | 0.000 | 0.262 | 0.001 | 0.000 | -15.763 | 0.000 | -2.052 | -5.581 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.328 | -60.873 | 0.000 | 0.000 | 6.999 | 4.848 | 24.332 | 65.092 | 0.000 | 0.403 | 0.001 | 0.000 | -24.108 | 0.000 | -3.193 | -13.828 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.414 | -38.147 | 0.000 | 0.000 | 4.520 | 3.071 | 15.403 | 38.363 | 0.000 | 0.255 | 0.000 | 0.000 | -16.896 | 0.000 | -2.068 | -4.916 |
TOPFLOOR_PLENUM | 8.169 | -45.363 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.569 | 41.716 | 0.000 | 0.000 | 0.000 | -5.092 | -0.000 |
MIDFLOOR_PLENUM | 4.255 | -22.686 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.633 | 23.035 | 0.000 | 0.000 | 0.000 | -5.237 | -0.000 |
FIRSTFLOOR_PLENUM | 2.097 | -25.653 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 27.284 | 0.000 | 0.000 | 0.000 | -4.229 | -0.000 |
Total Facility | 14.521 | -93.702 | 15.818 | -1024.803 | 0.000 | 0.000 | 168.595 | 169.021 | 647.750 | 483.420 | 0.000 | 10.518 | 113.314 | 0.000 | -241.167 | 0.000 | -58.855 | -204.422 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 09-JUN-05:03 | 0.00 | 0.00 | 0.00 | -34193.69 | 0.00 | 0.00 | 309.41 | 211.73 | 4048.06 | 0.00 | 0.00 | 0.00 | 29624.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 19-JUN-05:14 | 0.00 | 0.00 | 0.00 | -31603.64 | 0.00 | 0.00 | 310.15 | 393.54 | 3025.92 | 0.00 | 0.00 | 0.00 | 27874.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-MAY-04:03 | 0.00 | 0.00 | 0.00 | -32434.19 | 0.00 | 0.00 | 0.00 | 393.54 | 2442.06 | 0.00 | 0.00 | 0.00 | 29598.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-16:12 | 0.00 | 0.00 | 0.00 | -12344.58 | 0.00 | 0.00 | 25.20 | 19.78 | 478.42 | 3160.86 | 0.00 | 258.28 | 8402.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:32 | 0.00 | 0.00 | 0.00 | -11409.61 | 0.00 | 0.00 | 13.62 | 12.52 | 302.86 | 6757.95 | 0.00 | 0.00 | 4322.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-12:12 | 0.00 | 0.00 | 0.00 | -15366.89 | 0.00 | 0.00 | 22.64 | 19.78 | 478.41 | 11892.34 | 0.00 | 32.80 | 2920.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:42 | 0.00 | 0.00 | 0.00 | -13569.76 | 0.00 | 0.00 | 11.38 | 12.52 | 302.86 | 8818.69 | 0.00 | 179.76 | 4244.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -7844.93 | 0.00 | 0.00 | 144.47 | 133.37 | 637.89 | 350.32 | 0.00 | 1.76 | 6577.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:32 | 0.00 | 0.00 | 0.00 | -10177.65 | 0.00 | 0.00 | 15.62 | 12.52 | 302.86 | 6446.42 | 0.00 | 0.00 | 3401.38 | 0.00 | -0.00 | 0.00 | -1.15 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-14:32 | 0.00 | 0.00 | 0.00 | -11940.79 | 0.00 | 0.00 | 24.37 | 19.78 | 478.41 | 9345.49 | 0.00 | 0.00 | 2194.14 | 0.00 | -0.00 | 0.00 | -121.41 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:31 | 0.00 | 0.00 | 0.00 | -11207.07 | 0.00 | 0.00 | 14.25 | 12.52 | 302.86 | 7276.72 | 0.00 | 22.34 | 3578.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUN-16:11 | 0.00 | 0.00 | 0.00 | -10611.11 | 0.00 | 0.00 | 27.30 | 19.78 | 478.42 | 2998.31 | 0.00 | 173.12 | 6914.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:52 | 0.00 | 0.00 | 0.00 | -11653.38 | 0.00 | 0.00 | 14.39 | 12.52 | 302.86 | 7460.76 | 0.00 | 0.00 | 3876.41 | 0.00 | -0.00 | 0.00 | -13.56 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:22 | 0.00 | 0.00 | 0.00 | -13318.46 | 0.00 | 0.00 | 23.23 | 19.78 | 478.41 | 11821.89 | 0.00 | 0.00 | 1161.18 | 0.00 | -0.00 | 0.00 | -186.03 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-16:31 | 0.00 | 0.00 | 0.00 | -12709.57 | 0.00 | 0.00 | 13.02 | 12.52 | 302.86 | 7196.23 | 0.00 | 29.01 | 5155.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 03-JUL-13:00 | 0.00 | -11685.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.89 | 11618.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 03-JUL-10:10 | 0.00 | -6080.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 6071.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 03-JUL-12:08 | 0.00 | -6347.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 6339.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-06:03 | 0.00 | -11585.98 | 0.00 | -178513.65 | 0.00 | 0.00 | 3471.69 | 4834.95 | 18346.02 | 22759.99 | 0.00 | 2052.27 | 138634.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-JAN-07:03 | 0.00 | 0.00 | 15353.31 | 0.00 | 0.00 | 0.00 | 897.08 | 1180.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20456.95 |
CORE_TOP | 04-DEC-06:01 | 0.00 | 0.00 | 27857.55 | 0.00 | 0.00 | 0.00 | 497.18 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31592.38 |
PERIMETER_TOP_ZN_3 | 04-DEC-05:01 | 0.00 | 0.00 | 10507.61 | 0.00 | 0.00 | 0.00 | 0.00 | 82.96 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2324.62 | 0.00 | -37.53 | -8743.23 |
PERIMETER_TOP_ZN_2 | 04-DEC-05:01 | 0.00 | 0.00 | 9237.08 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1544.76 | 0.00 | -25.31 | -8045.43 |
PERIMETER_TOP_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 11380.39 | 0.00 | 0.00 | 0.00 | 0.00 | 82.96 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2254.06 | 0.00 | -635.87 | -9088.23 |
PERIMETER_TOP_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 9478.97 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1471.76 | 0.00 | -421.27 | -7964.35 |
PERIMETER_BOT_ZN_3 | 27-DEC-06:01 | 0.00 | 0.00 | 7342.63 | 0.00 | 0.00 | 0.00 | 102.05 | 44.64 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3068.08 | 0.00 | -66.62 | -4992.50 |
PERIMETER_BOT_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 5964.62 | 0.00 | 0.00 | 0.00 | 64.55 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2087.53 | 0.00 | -44.71 | -4329.00 |
PERIMETER_BOT_ZN_1 | 27-DEC-07:10 | 0.00 | 0.00 | 9660.64 | 0.00 | 0.00 | 0.00 | 193.30 | 248.89 | 637.88 | 0.00 | 0.00 | 0.00 | 8020.62 | 0.00 | -3218.80 | 0.00 | -15542.54 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 5815.55 | 0.00 | 0.00 | 0.00 | 64.48 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2052.98 | 0.00 | -44.73 | -4214.38 |
PERIMETER_MID_ZN_3 | 27-DEC-06:01 | 0.00 | 0.00 | 8261.19 | 0.00 | 0.00 | 0.00 | 105.95 | 44.64 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2958.43 | 0.00 | -100.03 | -5991.20 |
PERIMETER_MID_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 6930.96 | 0.00 | 0.00 | 0.00 | 67.48 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1999.77 | 0.00 | -66.67 | -5364.06 |
PERIMETER_MID_ZN_1 | 27-DEC-06:01 | 0.00 | 0.00 | 9223.09 | 0.00 | 0.00 | 0.00 | 105.59 | 44.64 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3032.42 | 0.00 | -100.75 | -6878.03 |
PERIMETER_MID_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 6783.60 | 0.00 | 0.00 | 0.00 | 67.33 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1964.95 | 0.00 | -66.81 | -5251.25 |
TOPFLOOR_PLENUM | 27-DEC-07:02 | 10965.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -160.31 | -10805.08 |
MIDFLOOR_PLENUM | 08-OCT-15:52 | 4421.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4489.39 |
FIRSTFLOOR_PLENUM | 08-OCT-16:22 | 2950.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6.48 | -2943.75 |
Total Facility | 27-DEC-07:01 | 7349.69 | 4899.07 | 127478.57 | -4899.07 | 0.00 | 0.00 | 4521.29 | 5980.60 | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31781.77 | 0.00 | -19962.14 | -111932.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.3714 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9306 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2140 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6804 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.8245 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5827 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6857 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6070 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0755 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9123 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0749 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6334 | 2.6334 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2072 | 2.2072 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4464 | 2.4464 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8418 | 0.8418 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7460 | 0.7460 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9302 | 0.9302 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8602 | 0.8602 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6671 | 0.6671 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6397 | 0.6397 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7466 | 0.7466 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6846 | 0.6846 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7180 | 0.7180 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7115 | 0.7115 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8074 | 0.8074 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7699 | 0.7699 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.3714 | 4.9306 | 5.3714 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2140 | 4.6804 | 5.2140 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.8245 | 5.5827 | 5.8245 | 1.0749 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3167 | 1.3167 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1036 | 1.1036 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2232 | 1.2232 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4209 | 0.4209 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3730 | 0.3730 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4651 | 0.4651 | 0.1339 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4301 | 0.4301 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3335 | 0.3335 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3199 | 0.3199 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3733 | 0.3733 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3423 | 0.3423 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3590 | 0.3590 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3558 | 0.3558 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4037 | 0.4037 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3849 | 0.3849 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6857 | 1.0757 | 1.0757 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6070 | 1.0755 | 1.0755 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9123 | 1.0749 | 1.0749 | 1.0749 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 68.83 |
Number of hours cooling loads not met | 261.17 |
Number of hours not met | 330.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 25.99 | 95331.58 | 37.17 | 53012.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 273.72 | 69302.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 169.02 | 17941.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 33.75 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 828.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 113.49 | 33167.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 122.50 | 9950.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1275.49 |
Natural Gas | 0.00 | 159.67 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1435.16 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 197.53 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.93 |
Space Heating | 5.22 |
Space Cooling | 54.94 |
Fans (All) | 22.78 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 256.01 |
Subtotal | 256.01 |
Natural Gas [MJ/m2] | |
Space Heating | 7.46 |
Service Water Heating | 24.59 |
Miscellaneous (All) | 32.05 |
Subtotal | 32.05 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.78 |
Space Heating | 4.40 |
Space Cooling | 19.07 |
Fans (All) | 7.91 |
Service Water Heating | 8.54 |
Receptacle Equipment | 45.13 |
Miscellaneous | 3.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2026. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 940. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8670.83 | 89.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8707.50 | 52.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8667.33 | 92.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8692.50 | 67.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8695.00 | 65.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8682.50 | 77.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8719.50 | 40.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8679.33 | 80.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8507.83 | 252.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8507.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 252.17 | 0.00 | 0.00 | 0.00 |
Average | 8709.94 | 50.06 | 0.00 | 0.00 | 0.00 |
Sum | 156779.00 | 901.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8568.17 | 191.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8610.00 | 150.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8722.17 | 37.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8523.17 | 236.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8455.33 | 304.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8491.17 | 268.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8447.17 | 312.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8575.67 | 184.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8455.33 | 304.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8482.83 | 277.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8431.00 | 329.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8498.67 | 261.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8423.00 | 337.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8454.67 | 305.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8421.00 | 339.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8484.33 | 275.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8627.17 | 132.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8664.17 | 95.83 | 0.00 | 0.00 | 0.00 |
Min | 8421.00 | 37.83 | 0.00 | 0.00 | 0.00 |
Max | 8722.17 | 339.00 | 0.00 | 0.00 | 0.00 |
Average | 8518.61 | 241.39 | 0.00 | 0.00 | 0.00 |
Sum | 153335.00 | 4345.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128223.00 | 81.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128248.67 | 55.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128262.00 | 42.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24887.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14006.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24887.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14007.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24903.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24766.83 | 142.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24900.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24899.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.33 | 0.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128262.00 | 142.17 | 0.00 | 0.00 | 0.00 |
Average | 34120.62 | 22.71 | 0.00 | 0.00 | 0.00 |
Sum | 614171.17 | 408.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.988648E+10 | 13043.71 | 12-JAN-08:07 | 5.05 | 2.36 | 0.196762E+10 | 2606.65 | 02-JAN-10:20 | 5.05 | 2.36 |
February | 0.102487E+11 | 13980.47 | 09-FEB-08:04 | 1.78 | -1.8 | 0.179298E+10 | 2608.11 | 02-FEB-14:30 | 1.78 | -1.8 |
March | 0.135478E+11 | 14883.05 | 16-MAR-16:00 | 22.20 | 8.37 | 0.215019E+10 | 2606.63 | 15-MAR-09:20 | 22.20 | 8.37 |
April | 0.164670E+11 | 27912.11 | 28-APR-06:02 | 13.77 | 8.62 | 0.191539E+10 | 2606.69 | 27-APR-09:39 | 13.77 | 8.62 |
May | 0.206677E+11 | 33732.83 | 31-MAY-05:03 | 24.22 | 11.57 | 0.207580E+10 | 2606.69 | 08-MAY-09:09 | 24.22 | 11.57 |
June | 0.222461E+11 | 34194.26 | 09-JUN-05:03 | 23.80 | 14.62 | 0.207034E+10 | 2606.67 | 12-JUN-09:20 | 27.40 | 12.38 |
July | 0.219787E+11 | 34076.60 | 05-JUL-05:12 | 19.27 | 16.46 | 0.192423E+10 | 2669.84 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.233532E+11 | 33346.24 | 14-AUG-05:12 | 17.40 | 16.29 | 0.215994E+10 | 2606.64 | 25-AUG-09:20 | 25.17 | 16.41 |
September | 0.207943E+11 | 33816.78 | 06-SEP-05:12 | 15.93 | 14.42 | 0.191809E+10 | 2606.67 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.189511E+11 | 31662.64 | 02-OCT-04:02 | 24.82 | 15.04 | 0.199231E+10 | 2606.72 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.140764E+11 | 30612.59 | 01-NOV-06:01 | 11.10 | 10.08 | 0.196752E+10 | 2608.46 | 30-NOV-10:09 | 10.47 | 6.35 |
December | 0.971878E+10 | 13804.96 | 08-DEC-08:07 | 4.13 | 0.72 | 0.189790E+10 | 2606.63 | 14-DEC-10:20 | 8.33 | 5.14 |
Annual Sum or Average | 0.201936E+12 | 0.238323E+11 | ||||||||
Minimum of Months | 0.971878E+10 | 13043.71 | 1.78 | -1.8 | 0.179298E+10 | 2606.63 | 1.78 | -1.8 | ||
Maximum of Months | 0.233532E+11 | 34194.26 | 24.82 | 16.46 | 0.215994E+10 | 2669.84 | 27.40 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243811E+09 | 2505.92 | 12-JAN-15:20 | 18.90 | 10.07 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.07 |
February | 0.592724E+09 | 4136.38 | 22-FEB-14:10 | 21.78 | 7.94 | 0.00 | 0.00 | 01-FEB-00:10 | 21.78 | 7.94 |
March | 0.148494E+10 | 5370.80 | 16-MAR-14:20 | 22.80 | 9.14 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 9.14 |
April | 0.364080E+10 | 8729.61 | 19-APR-14:30 | 31.10 | 14.32 | 0.00 | 0.00 | 01-APR-00:10 | 31.10 | 14.32 |
May | 0.609632E+10 | 10781.12 | 30-MAY-14:20 | 34.40 | 17.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.40 | 17.58 |
June | 0.839574E+10 | 11285.44 | 15-JUN-14:40 | 38.13 | 15.82 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 15.82 |
July | 0.779673E+10 | 11685.32 | 03-JUL-13:00 | 36.70 | 18.58 | 0.00 | 0.00 | 01-JUL-00:10 | 36.70 | 18.58 |
August | 0.720835E+10 | 11202.62 | 07-AUG-14:50 | 35.00 | 18.73 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.73 |
September | 0.574912E+10 | 9783.33 | 19-SEP-15:10 | 33.40 | 16.39 | 0.00 | 0.00 | 01-SEP-00:10 | 33.40 | 16.39 |
October | 0.304636E+10 | 8868.06 | 03-OCT-14:30 | 32.25 | 19.38 | 0.00 | 0.00 | 01-OCT-00:10 | 32.25 | 19.38 |
November | 0.961014E+09 | 4756.09 | 03-NOV-15:20 | 23.50 | 13.53 | 0.00 | 0.00 | 01-NOV-00:10 | 23.50 | 13.53 |
December | 0.147555E+09 | 1210.89 | 09-DEC-13:40 | 17.40 | 7.21 | 0.00 | 0.00 | 01-DEC-00:10 | 17.40 | 7.21 |
Annual Sum or Average | 0.453635E+11 | 0.00 | ||||||||
Minimum of Months | 0.147555E+09 | 1210.89 | 17.40 | 7.21 | 0.00 | 0.00 | 17.40 | 7.21 | ||
Maximum of Months | 0.839574E+10 | 11685.32 | 38.13 | 19.38 | 0.00 | 0.00 | 38.13 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53625600.85 | 1734.80 | 28-JAN-06:01 | -3.3 | -6.4 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -6.4 |
February | 0.105205E+09 | 1709.79 | 02-FEB-06:01 | -3.5 | -5.9 | 0.00 | 0.00 | 01-FEB-00:10 | -3.5 | -5.9 |
March | 0.301907E+09 | 1802.81 | 02-MAR-06:01 | -3.5 | -6.2 | 0.00 | 0.00 | 01-MAR-00:10 | -3.5 | -6.2 |
April | 0.144890E+10 | 3175.57 | 21-APR-15:20 | 31.83 | 15.27 | 0.00 | 0.00 | 01-APR-00:10 | 31.83 | 15.27 |
May | 0.310373E+10 | 5088.23 | 30-MAY-16:00 | 33.90 | 17.46 | 0.00 | 0.00 | 01-MAY-00:10 | 33.90 | 17.46 |
June | 0.442284E+10 | 5562.63 | 19-JUN-10:10 | 29.18 | 18.04 | 0.00 | 0.00 | 01-JUN-00:10 | 29.18 | 18.04 |
July | 0.426951E+10 | 6079.61 | 03-JUL-10:10 | 32.67 | 18.80 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 18.80 |
August | 0.403979E+10 | 5677.15 | 07-AUG-10:10 | 31.78 | 18.15 | 0.00 | 0.00 | 01-AUG-00:10 | 31.78 | 18.15 |
September | 0.308570E+10 | 4767.75 | 05-SEP-06:15 | 17.43 | 15.20 | 0.00 | 0.00 | 01-SEP-00:10 | 17.43 | 15.20 |
October | 0.157117E+10 | 3793.18 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.252021E+09 | 1823.03 | 10-NOV-15:50 | 15.10 | 9.99 | 0.00 | 0.00 | 01-NOV-00:10 | 15.10 | 9.99 |
December | 32139003.30 | 1623.99 | 30-DEC-06:01 | -2.9 | -4.1 | 0.00 | 0.00 | 01-DEC-00:10 | -2.9 | -4.1 |
Annual Sum or Average | 0.226865E+11 | 0.00 | ||||||||
Minimum of Months | 32139003.30 | 1623.99 | -3.5 | -6.4 | 0.00 | 0.00 | -3.5 | -6.4 | ||
Maximum of Months | 0.442284E+10 | 6079.61 | 33.90 | 18.80 | 0.00 | 0.00 | 33.90 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140814E+09 | 2066.72 | 05-JAN-07:03 | -0.9 | -5.5 | 0.00 | 0.00 | 01-JAN-00:10 | -0.9 | -5.5 |
February | 0.270448E+09 | 2253.08 | 16-FEB-07:02 | -1.5 | -2.6 | 0.00 | 0.00 | 01-FEB-00:10 | -1.5 | -2.6 |
March | 0.597116E+09 | 2201.83 | 30-MAR-06:02 | -0.1 | -3.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -3.7 |
April | 0.170818E+10 | 3089.61 | 21-APR-15:40 | 31.47 | 15.05 | 0.00 | 0.00 | 01-APR-00:10 | 31.47 | 15.05 |
May | 0.320854E+10 | 4754.31 | 30-MAY-16:00 | 33.90 | 17.46 | 0.00 | 0.00 | 01-MAY-00:10 | 33.90 | 17.46 |
June | 0.436908E+10 | 5524.35 | 05-JUN-12:07 | 34.68 | 16.27 | 0.00 | 0.00 | 01-JUN-00:10 | 34.68 | 16.27 |
July | 0.433615E+10 | 6347.38 | 03-JUL-12:08 | 35.78 | 18.54 | 0.00 | 0.00 | 01-JUL-00:10 | 35.78 | 18.54 |
August | 0.433635E+10 | 5067.24 | 07-AUG-06:10 | 25.18 | 16.26 | 0.00 | 0.00 | 01-AUG-00:10 | 25.18 | 16.26 |
September | 0.362760E+10 | 5511.04 | 05-SEP-06:15 | 17.43 | 15.20 | 0.00 | 0.00 | 01-SEP-00:10 | 17.43 | 15.20 |
October | 0.227217E+10 | 3818.24 | 02-OCT-12:10 | 26.70 | 16.86 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 16.86 |
November | 0.690980E+09 | 2374.32 | 10-NOV-16:00 | 15.00 | 9.95 | 0.00 | 0.00 | 01-NOV-00:10 | 15.00 | 9.95 |
December | 95359286.73 | 1970.80 | 22-DEC-07:02 | -3.0 | -4.9 | 0.00 | 0.00 | 01-DEC-00:10 | -3.0 | -4.9 |
Annual Sum or Average | 0.256528E+11 | 0.00 | ||||||||
Minimum of Months | 95359286.73 | 1970.80 | -3.0 | -5.5 | 0.00 | 0.00 | -3.0 | -5.5 | ||
Maximum of Months | 0.436908E+10 | 6347.38 | 35.78 | 18.54 | 0.00 | 0.00 | 35.78 | 18.54 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.690415E+10 | 7854.40 | 13-JAN-17:00 | 17.20 | 8.47 | 0.183580E+10 | 2606.60 | 13-JAN-14:20 | 17.20 | 8.47 |
February | 0.720828E+10 | 9760.03 | 22-FEB-17:00 | 21.70 | 8.09 | 0.172758E+10 | 2606.63 | 07-FEB-10:20 | 21.70 | 8.09 |
March | 0.973153E+10 | 11460.96 | 16-MAR-16:00 | 22.20 | 8.37 | 0.211314E+10 | 2607.59 | 17-MAR-09:20 | 7.57 | 1.14 |
April | 0.128037E+11 | 16075.15 | 17-APR-06:02 | 12.62 | 8.44 | 0.190813E+10 | 2606.68 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.168334E+11 | 28909.77 | 30-MAY-04:03 | 25.00 | 11.58 | 0.207389E+10 | 2606.67 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.187755E+11 | 31593.65 | 19-JUN-05:14 | 22.80 | 15.92 | 0.206963E+10 | 2606.67 | 12-JUN-09:20 | 22.80 | 15.92 |
July | 0.185652E+11 | 29166.00 | 05-JUL-05:12 | 19.27 | 16.46 | 0.192336E+10 | 2641.03 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.189951E+11 | 29043.57 | 14-AUG-05:12 | 17.40 | 16.29 | 0.215869E+10 | 2606.66 | 28-AUG-09:20 | 25.57 | 16.47 |
September | 0.162769E+11 | 29909.00 | 05-SEP-05:12 | 16.30 | 15.51 | 0.191607E+10 | 2606.68 | 05-SEP-09:20 | 23.53 | 17.86 |
October | 0.137938E+11 | 27440.42 | 02-OCT-04:02 | 24.82 | 15.04 | 0.198537E+10 | 2606.68 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.911754E+10 | 12909.08 | 10-NOV-16:50 | 14.50 | 9.32 | 0.191175E+10 | 2606.63 | 16-NOV-10:20 | 8.33 | 4.44 |
December | 0.659800E+10 | 6728.57 | 15-DEC-17:00 | 15.00 | 5.87 | 0.174893E+10 | 2606.54 | 01-DEC-14:30 | 15.00 | 5.87 |
Annual Sum or Average | 0.155603E+12 | 0.233723E+11 | ||||||||
Minimum of Months | 0.659800E+10 | 6728.57 | 12.62 | 5.87 | 0.172758E+10 | 2606.54 | 7.57 | 1.14 | ||
Maximum of Months | 0.189951E+11 | 31593.65 | 25.00 | 16.46 | 0.215869E+10 | 2641.03 | 25.57 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572130E+10 | 7267.82 | 12-JAN-16:40 | 18.17 | 9.93 | 0.170466E+10 | 2606.53 | 12-JAN-14:00 | 18.17 | 9.93 |
February | 0.629748E+10 | 9506.78 | 22-FEB-15:30 | 22.50 | 8.27 | 0.162978E+10 | 2606.58 | 07-FEB-14:20 | 22.50 | 8.27 |
March | 0.887030E+10 | 12681.74 | 16-MAR-16:00 | 22.20 | 8.37 | 0.203872E+10 | 2606.61 | 09-MAR-14:20 | 22.20 | 8.37 |
April | 0.126398E+11 | 15882.17 | 28-APR-15:40 | 28.50 | 13.78 | 0.189336E+10 | 2606.68 | 27-APR-09:39 | 28.50 | 13.78 |
May | 0.175573E+11 | 32440.73 | 30-MAY-04:03 | 25.00 | 11.58 | 0.207115E+10 | 2606.66 | 08-MAY-09:20 | 25.00 | 11.58 |
June | 0.204972E+11 | 31297.49 | 05-JUN-05:12 | 21.67 | 13.69 | 0.206981E+10 | 2606.66 | 12-JUN-09:20 | 27.40 | 12.38 |
July | 0.201535E+11 | 32101.27 | 10-JUL-04:03 | 24.32 | 16.38 | 0.192453E+10 | 2682.87 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.199784E+11 | 31880.60 | 14-AUG-05:12 | 17.40 | 16.29 | 0.215844E+10 | 2606.64 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.163208E+11 | 32010.43 | 05-SEP-05:12 | 16.30 | 15.51 | 0.191291E+10 | 2606.66 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.126487E+11 | 31184.93 | 02-OCT-04:02 | 24.82 | 15.04 | 0.196701E+10 | 2606.66 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.759867E+10 | 12779.29 | 10-NOV-15:00 | 15.60 | 10.20 | 0.182194E+10 | 2606.63 | 01-NOV-09:39 | 15.60 | 10.20 |
December | 0.525262E+10 | 5599.17 | 15-DEC-16:40 | 15.20 | 5.96 | 0.160800E+10 | 2555.29 | 01-DEC-14:00 | 15.20 | 5.96 |
Annual Sum or Average | 0.153536E+12 | 0.228003E+11 | ||||||||
Minimum of Months | 0.525262E+10 | 5599.17 | 15.20 | 5.96 | 0.160800E+10 | 2555.29 | 15.20 | 5.96 | ||
Maximum of Months | 0.204972E+11 | 32440.73 | 28.50 | 16.38 | 0.215844E+10 | 2682.87 | 28.50 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597069E+09 | 1178.49 | 12-JAN-14:30 | 18.60 | 9.87 | 0.325134E+09 | 522.08 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.867939E+09 | 1896.32 | 22-FEB-15:00 | 22.20 | 8.00 | 0.312429E+09 | 549.49 | 07-FEB-14:20 | 22.20 | 8.00 |
March | 0.153917E+10 | 3105.54 | 22-MAR-14:30 | 24.15 | 9.01 | 0.400682E+09 | 549.49 | 09-MAR-14:20 | 24.15 | 9.01 |
April | 0.298167E+10 | 5559.44 | 21-APR-15:00 | 32.20 | 15.49 | 0.389910E+09 | 549.50 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.514244E+10 | 10533.06 | 21-MAY-15:52 | 34.40 | 18.34 | 0.435657E+09 | 549.50 | 19-MAY-09:20 | 34.40 | 18.34 |
June | 0.692582E+10 | 12212.38 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436770E+09 | 549.51 | 12-JUN-09:20 | 37.12 | 16.83 |
July | 0.660555E+10 | 12344.60 | 02-JUL-16:12 | 38.13 | 18.77 | 0.406401E+09 | 557.13 | 20-JUL-15:30 | 25.25 | 22.87 |
August | 0.592489E+10 | 12155.25 | 06-AUG-16:52 | 36.10 | 18.82 | 0.454954E+09 | 549.50 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.435941E+10 | 6414.60 | 17-SEP-15:52 | 32.80 | 15.88 | 0.401163E+09 | 549.50 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.266549E+10 | 7181.23 | 02-OCT-04:02 | 24.82 | 15.04 | 0.402802E+09 | 549.50 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.115433E+10 | 2508.03 | 09-NOV-15:30 | 23.30 | 12.82 | 0.354842E+09 | 549.49 | 10-NOV-10:20 | 19.80 | 12.11 |
December | 0.478757E+09 | 1039.26 | 08-DEC-15:10 | 17.20 | 7.54 | 0.307635E+09 | 493.00 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.392425E+11 | 0.462838E+10 | ||||||||
Minimum of Months | 0.478757E+09 | 1039.26 | 17.20 | 7.54 | 0.307635E+09 | 493.00 | 17.20 | 7.54 | ||
Maximum of Months | 0.692582E+10 | 12344.60 | 38.13 | 18.82 | 0.454954E+09 | 557.13 | 37.12 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601087E+09 | 1243.25 | 04-JAN-10:10 | 9.60 | 3.11 | 0.226522E+09 | 347.87 | 12-JAN-10:20 | 11.70 | 6.12 |
February | 0.883690E+09 | 2767.84 | 21-FEB-10:30 | 18.35 | 7.04 | 0.219940E+09 | 347.87 | 24-FEB-10:20 | 7.77 | 2.42 |
March | 0.178260E+10 | 4019.39 | 16-MAR-10:10 | 19.18 | 7.83 | 0.273948E+09 | 347.88 | 06-MAR-10:20 | 19.18 | 7.83 |
April | 0.350529E+10 | 10502.60 | 30-APR-10:53 | 25.00 | 12.86 | 0.253942E+09 | 347.90 | 19-APR-09:09 | 25.00 | 12.86 |
May | 0.527531E+10 | 10961.21 | 29-MAY-09:22 | 23.60 | 15.91 | 0.277016E+09 | 348.26 | 17-MAY-09:50 | 23.60 | 15.91 |
June | 0.643749E+10 | 11342.22 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276853E+09 | 348.22 | 27-JUN-09:00 | 25.60 | 15.68 |
July | 0.600029E+10 | 11409.12 | 02-JUL-09:32 | 30.37 | 19.85 | 0.257662E+09 | 348.33 | 03-JUL-09:00 | 32.20 | 18.73 |
August | 0.568340E+10 | 11379.68 | 06-AUG-09:32 | 29.83 | 17.77 | 0.288444E+09 | 348.20 | 01-AUG-09:00 | 29.83 | 17.77 |
September | 0.460061E+10 | 10717.05 | 03-SEP-09:13 | 24.97 | 19.09 | 0.255544E+09 | 348.37 | 11-SEP-09:00 | 25.60 | 12.20 |
October | 0.273174E+10 | 8648.98 | 01-OCT-09:32 | 23.67 | 13.35 | 0.261070E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.116296E+10 | 4429.14 | 10-NOV-09:20 | 18.67 | 11.91 | 0.243481E+09 | 347.88 | 09-NOV-10:20 | 18.67 | 11.91 |
December | 0.515617E+09 | 738.31 | 01-DEC-10:40 | 13.33 | 5.28 | 0.210751E+09 | 340.87 | 01-DEC-10:50 | 13.62 | 5.49 |
Annual Sum or Average | 0.391801E+11 | 0.304517E+10 | ||||||||
Minimum of Months | 0.515617E+09 | 738.31 | 9.60 | 3.11 | 0.210751E+09 | 340.87 | 7.77 | 2.42 | ||
Maximum of Months | 0.643749E+10 | 11409.12 | 31.13 | 19.85 | 0.288444E+09 | 348.37 | 32.20 | 18.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272671E+10 | 8928.78 | 12-JAN-14:30 | 18.60 | 9.87 | 0.384925E+09 | 549.59 | 12-JAN-14:50 | 18.80 | 9.97 |
February | 0.284579E+10 | 13951.84 | 20-FEB-14:23 | 22.75 | 8.67 | 0.353357E+09 | 549.73 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.360223E+10 | 8418.90 | 16-MAR-13:30 | 22.50 | 9.16 | 0.426448E+09 | 549.70 | 16-MAR-13:00 | 22.80 | 9.34 |
April | 0.456176E+10 | 13977.69 | 30-APR-13:32 | 29.40 | 12.46 | 0.393648E+09 | 549.68 | 21-APR-13:39 | 29.40 | 12.46 |
May | 0.566004E+10 | 12267.67 | 21-MAY-15:12 | 34.40 | 17.95 | 0.435201E+09 | 549.50 | 03-MAY-13:00 | 34.40 | 17.95 |
June | 0.683707E+10 | 13425.73 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436613E+09 | 549.50 | 12-JUN-09:20 | 37.12 | 16.83 |
July | 0.678133E+10 | 13947.26 | 30-JUL-12:53 | 30.60 | 19.90 | 0.406321E+09 | 553.29 | 20-JUL-15:20 | 30.60 | 19.90 |
August | 0.726057E+10 | 13893.14 | 13-AUG-13:23 | 30.55 | 19.31 | 0.455134E+09 | 550.24 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.727118E+10 | 14220.42 | 03-SEP-11:53 | 28.30 | 19.12 | 0.402695E+09 | 549.90 | 15-SEP-13:00 | 32.20 | 17.96 |
October | 0.635062E+10 | 15366.63 | 01-OCT-12:12 | 30.37 | 14.43 | 0.412110E+09 | 560.02 | 03-OCT-13:39 | 32.07 | 19.44 |
November | 0.424083E+10 | 14176.90 | 11-NOV-12:32 | 17.93 | 8.04 | 0.391163E+09 | 549.85 | 08-NOV-14:50 | 17.93 | 8.04 |
December | 0.245967E+10 | 7044.26 | 07-DEC-14:10 | 15.68 | 6.76 | 0.369041E+09 | 549.49 | 01-DEC-14:09 | 15.68 | 6.76 |
Annual Sum or Average | 0.605978E+11 | 0.486666E+10 | ||||||||
Minimum of Months | 0.245967E+10 | 7044.26 | 15.68 | 6.76 | 0.353357E+09 | 549.49 | 15.68 | 6.76 | ||
Maximum of Months | 0.727118E+10 | 15366.63 | 37.12 | 19.90 | 0.455134E+09 | 560.02 | 37.12 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.691589E+09 | 3396.84 | 12-JAN-15:30 | 18.90 | 10.10 | 0.219531E+09 | 347.84 | 13-JAN-14:20 | 17.97 | 8.78 |
February | 0.928305E+09 | 5914.44 | 19-FEB-16:33 | 22.40 | 8.34 | 0.206321E+09 | 347.84 | 14-FEB-14:20 | 22.40 | 8.34 |
March | 0.188230E+10 | 6007.51 | 21-MAR-16:00 | 25.00 | 9.53 | 0.258617E+09 | 347.85 | 09-MAR-14:20 | 25.00 | 9.53 |
April | 0.339446E+10 | 13323.49 | 30-APR-16:52 | 30.00 | 12.57 | 0.247829E+09 | 347.86 | 27-APR-09:20 | 30.00 | 12.57 |
May | 0.510789E+10 | 13569.69 | 29-MAY-16:42 | 32.88 | 16.50 | 0.275826E+09 | 347.86 | 19-MAY-09:20 | 32.88 | 16.50 |
June | 0.615938E+10 | 13526.90 | 25-JUN-16:32 | 31.50 | 16.81 | 0.276658E+09 | 347.86 | 12-JUN-09:20 | 31.50 | 16.81 |
July | 0.574439E+10 | 13472.71 | 09-JUL-16:32 | 32.97 | 19.28 | 0.257420E+09 | 347.85 | 03-JUL-09:20 | 32.97 | 19.28 |
August | 0.545670E+10 | 13531.59 | 06-AUG-16:52 | 36.10 | 18.82 | 0.288251E+09 | 347.85 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.454841E+10 | 13266.86 | 17-SEP-15:52 | 32.80 | 15.88 | 0.254532E+09 | 347.86 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.296491E+10 | 13524.52 | 01-OCT-14:52 | 32.80 | 15.90 | 0.256899E+09 | 347.85 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.140033E+10 | 5527.35 | 09-NOV-15:30 | 23.30 | 12.82 | 0.232167E+09 | 347.85 | 10-NOV-10:20 | 19.80 | 12.11 |
December | 0.548562E+09 | 2447.52 | 15-DEC-16:00 | 15.60 | 6.14 | 0.209352E+09 | 347.83 | 01-DEC-14:00 | 15.60 | 6.14 |
Annual Sum or Average | 0.388272E+11 | 0.298340E+10 | ||||||||
Minimum of Months | 0.548562E+09 | 2447.52 | 15.60 | 6.14 | 0.206321E+09 | 347.83 | 15.60 | 6.14 | ||
Maximum of Months | 0.615938E+10 | 13569.69 | 36.10 | 19.28 | 0.288251E+09 | 347.86 | 32.97 | 19.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817704E+09 | 1274.78 | 04-JAN-13:06 | 11.70 | 3.67 | 0.329835E+09 | 507.53 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.882438E+09 | 1340.60 | 20-FEB-15:02 | 23.30 | 8.84 | 0.308497E+09 | 536.79 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.128392E+10 | 1284.99 | 22-MAR-14:30 | 24.15 | 9.01 | 0.388544E+09 | 549.47 | 09-MAR-14:00 | 24.15 | 9.01 |
April | 0.200089E+10 | 3587.16 | 21-APR-15:20 | 31.83 | 15.27 | 0.387688E+09 | 549.50 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.366495E+10 | 4873.00 | 30-MAY-15:20 | 34.23 | 17.67 | 0.435097E+09 | 549.50 | 19-MAY-09:20 | 34.23 | 17.67 |
June | 0.530671E+10 | 7488.13 | 19-JUN-06:03 | 23.07 | 16.06 | 0.436110E+09 | 549.50 | 12-JUN-09:20 | 23.07 | 16.06 |
July | 0.561151E+10 | 7799.78 | 03-JUL-06:03 | 26.88 | 16.13 | 0.405899E+09 | 555.33 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.553646E+10 | 7844.28 | 07-AUG-06:03 | 25.18 | 16.26 | 0.455221E+09 | 549.50 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.445503E+10 | 7064.90 | 05-SEP-06:03 | 17.07 | 15.07 | 0.403505E+09 | 549.50 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.287356E+10 | 5151.05 | 02-OCT-06:03 | 22.70 | 15.09 | 0.414506E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.148577E+10 | 2147.21 | 09-NOV-16:00 | 23.30 | 13.01 | 0.376049E+09 | 549.50 | 09-NOV-10:20 | 23.30 | 13.01 |
December | 0.840761E+09 | 1054.88 | 01-DEC-14:40 | 13.67 | 6.12 | 0.319365E+09 | 500.72 | 01-DEC-14:39 | 13.67 | 6.12 |
Annual Sum or Average | 0.347597E+11 | 0.466032E+10 | ||||||||
Minimum of Months | 0.817704E+09 | 1054.88 | 11.70 | 3.67 | 0.308497E+09 | 500.72 | 13.67 | 6.12 | ||
Maximum of Months | 0.561151E+10 | 7844.28 | 34.23 | 17.67 | 0.455221E+09 | 555.33 | 34.23 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763709E+09 | 1261.42 | 04-JAN-10:10 | 9.60 | 3.11 | 0.235085E+09 | 347.87 | 12-JAN-10:20 | 11.70 | 6.12 |
February | 0.888965E+09 | 2313.12 | 21-FEB-10:30 | 18.35 | 7.04 | 0.222380E+09 | 347.88 | 10-FEB-10:39 | 18.35 | 7.04 |
March | 0.142753E+10 | 2837.02 | 31-MAR-09:40 | 17.60 | 6.03 | 0.274760E+09 | 347.87 | 06-MAR-10:20 | 17.60 | 6.03 |
April | 0.267708E+10 | 6677.82 | 30-APR-10:53 | 25.00 | 12.86 | 0.254368E+09 | 347.89 | 27-APR-09:39 | 25.00 | 12.86 |
May | 0.424535E+10 | 7649.93 | 29-MAY-07:23 | 18.90 | 14.35 | 0.277081E+09 | 348.22 | 15-MAY-09:00 | 18.90 | 14.35 |
June | 0.535567E+10 | 8621.88 | 11-JUN-09:12 | 26.47 | 11.74 | 0.276737E+09 | 348.12 | 09-JUN-09:00 | 26.47 | 11.74 |
July | 0.535206E+10 | 10177.29 | 04-JUL-09:32 | 27.57 | 18.80 | 0.257639E+09 | 350.11 | 21-JUL-10:30 | 24.75 | 21.90 |
August | 0.552585E+10 | 10083.91 | 27-AUG-09:52 | 31.70 | 14.69 | 0.288727E+09 | 348.09 | 04-AUG-09:00 | 31.70 | 14.69 |
September | 0.480883E+10 | 9894.12 | 04-SEP-10:22 | 26.40 | 18.54 | 0.256282E+09 | 348.26 | 15-SEP-09:50 | 27.43 | 19.66 |
October | 0.307661E+10 | 5705.75 | 02-OCT-04:02 | 24.82 | 15.04 | 0.264839E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.154606E+10 | 4169.05 | 10-NOV-09:10 | 18.48 | 11.84 | 0.253391E+09 | 347.88 | 09-NOV-10:20 | 18.48 | 11.84 |
December | 0.757008E+09 | 1125.69 | 01-DEC-10:10 | 12.48 | 4.67 | 0.226122E+09 | 347.88 | 14-DEC-10:20 | 8.33 | 5.14 |
Annual Sum or Average | 0.364247E+11 | 0.308741E+10 | ||||||||
Minimum of Months | 0.757008E+09 | 1125.69 | 9.60 | 3.11 | 0.222380E+09 | 347.87 | 8.33 | 5.14 | ||
Maximum of Months | 0.552585E+10 | 10177.29 | 31.70 | 18.80 | 0.288727E+09 | 350.11 | 31.70 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202231E+10 | 8550.03 | 04-JAN-13:06 | 11.70 | 3.67 | 0.378422E+09 | 549.50 | 26-JAN-14:09 | 6.20 | -1.5 |
February | 0.185227E+10 | 11060.54 | 20-FEB-14:23 | 22.75 | 8.67 | 0.344275E+09 | 549.75 | 02-FEB-14:30 | 22.75 | 8.67 |
March | 0.215492E+10 | 5547.56 | 22-MAR-13:10 | 24.90 | 9.24 | 0.413819E+09 | 549.51 | 17-MAR-13:09 | 24.90 | 9.24 |
April | 0.316621E+10 | 8929.70 | 19-APR-12:00 | 30.60 | 14.04 | 0.386840E+09 | 549.51 | 24-APR-13:20 | 24.60 | 9.86 |
May | 0.461615E+10 | 9502.70 | 19-MAY-16:20 | 34.80 | 16.77 | 0.431727E+09 | 567.98 | 19-MAY-12:09 | 34.80 | 16.77 |
June | 0.632420E+10 | 10332.67 | 02-JUN-16:50 | 38.90 | 16.18 | 0.437173E+09 | 614.52 | 15-JUN-12:09 | 36.10 | 14.46 |
July | 0.667358E+10 | 10410.50 | 03-JUL-17:00 | 38.30 | 18.83 | 0.407175E+09 | 623.55 | 03-JUL-12:09 | 38.30 | 18.83 |
August | 0.756162E+10 | 11001.09 | 27-AUG-11:12 | 32.57 | 15.48 | 0.456363E+09 | 618.80 | 07-AUG-12:09 | 32.57 | 15.48 |
September | 0.780433E+10 | 11678.14 | 17-SEP-14:02 | 32.30 | 16.10 | 0.406092E+09 | 607.69 | 19-SEP-12:09 | 31.88 | 16.39 |
October | 0.641663E+10 | 11940.92 | 29-OCT-14:32 | 23.90 | 11.39 | 0.417236E+09 | 594.31 | 03-OCT-12:09 | 23.90 | 11.39 |
November | 0.411498E+10 | 11670.40 | 11-NOV-13:02 | 18.30 | 8.11 | 0.395002E+09 | 562.41 | 09-NOV-14:09 | 18.30 | 8.11 |
December | 0.194746E+10 | 6762.45 | 07-DEC-13:07 | 14.60 | 6.36 | 0.363987E+09 | 549.50 | 28-DEC-14:09 | 9.50 | 3.32 |
Annual Sum or Average | 0.546547E+11 | 0.483811E+10 | ||||||||
Minimum of Months | 0.185227E+10 | 5547.56 | 11.70 | 3.67 | 0.344275E+09 | 549.50 | 6.20 | -1.5 | ||
Maximum of Months | 0.780433E+10 | 11940.92 | 38.90 | 18.83 | 0.456363E+09 | 623.55 | 38.30 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.834978E+09 | 2383.60 | 30-JAN-16:30 | 15.60 | 6.05 | 0.226301E+09 | 347.84 | 13-JAN-14:20 | 15.60 | 6.05 |
February | 0.849177E+09 | 3584.70 | 21-FEB-16:50 | 22.30 | 7.87 | 0.209225E+09 | 347.84 | 22-FEB-14:20 | 21.87 | 7.95 |
March | 0.139134E+10 | 3694.29 | 21-MAR-16:00 | 25.00 | 9.53 | 0.261653E+09 | 347.84 | 09-MAR-14:20 | 25.00 | 9.53 |
April | 0.245252E+10 | 10491.12 | 16-APR-17:42 | 29.50 | 11.44 | 0.250531E+09 | 347.86 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.402419E+10 | 10466.56 | 29-MAY-17:22 | 31.95 | 15.92 | 0.276522E+09 | 347.86 | 19-MAY-09:20 | 31.95 | 15.92 |
June | 0.503718E+10 | 10622.48 | 11-JUN-16:31 | 32.40 | 15.05 | 0.276564E+09 | 347.86 | 12-JUN-09:20 | 27.40 | 12.38 |
July | 0.505444E+10 | 10468.79 | 04-JUL-15:31 | 34.23 | 18.80 | 0.257407E+09 | 347.86 | 03-JUL-09:09 | 34.23 | 18.80 |
August | 0.525085E+10 | 11208.13 | 13-AUG-16:31 | 31.30 | 18.50 | 0.288675E+09 | 347.85 | 23-AUG-09:20 | 27.03 | 14.81 |
September | 0.468203E+10 | 10953.31 | 17-SEP-16:42 | 31.88 | 15.56 | 0.256196E+09 | 347.86 | 12-SEP-09:20 | 31.88 | 15.56 |
October | 0.321835E+10 | 10578.85 | 08-OCT-16:22 | 25.25 | 17.49 | 0.264801E+09 | 347.85 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.164873E+10 | 4891.56 | 09-NOV-16:10 | 23.22 | 12.98 | 0.248563E+09 | 347.85 | 01-NOV-09:09 | 23.22 | 12.98 |
December | 0.803791E+09 | 2226.01 | 15-DEC-16:10 | 15.50 | 6.10 | 0.218558E+09 | 347.83 | 01-DEC-14:00 | 15.50 | 6.10 |
Annual Sum or Average | 0.352476E+11 | 0.303500E+10 | ||||||||
Minimum of Months | 0.803791E+09 | 2226.01 | 15.50 | 6.05 | 0.209225E+09 | 347.83 | 15.50 | 6.05 | ||
Maximum of Months | 0.525085E+10 | 11208.13 | 34.23 | 18.80 | 0.288675E+09 | 347.86 | 34.23 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.902374E+09 | 1332.85 | 12-JAN-14:10 | 18.40 | 9.78 | 0.336435E+09 | 537.30 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.111767E+10 | 1987.49 | 23-FEB-14:30 | 21.65 | 7.41 | 0.324596E+09 | 549.48 | 07-FEB-14:20 | 21.65 | 7.41 |
March | 0.170883E+10 | 2900.33 | 22-MAR-14:40 | 24.07 | 8.96 | 0.415096E+09 | 549.49 | 22-MAR-13:20 | 24.07 | 8.96 |
April | 0.293721E+10 | 4953.54 | 21-APR-15:00 | 32.20 | 15.49 | 0.396011E+09 | 549.50 | 27-APR-09:20 | 21.13 | 12.20 |
May | 0.486838E+10 | 8237.66 | 30-MAY-06:03 | 25.10 | 11.90 | 0.436805E+09 | 549.50 | 04-MAY-13:20 | 25.10 | 11.90 |
June | 0.638739E+10 | 10611.12 | 18-JUN-16:11 | 37.20 | 16.86 | 0.436837E+09 | 549.51 | 12-JUN-09:20 | 37.20 | 16.86 |
July | 0.608401E+10 | 10330.22 | 02-JUL-16:12 | 38.13 | 18.77 | 0.406346E+09 | 557.21 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.559698E+10 | 10173.32 | 13-AUG-16:31 | 31.30 | 18.50 | 0.455282E+09 | 549.50 | 28-AUG-09:20 | 25.57 | 16.47 |
September | 0.425437E+10 | 6437.78 | 10-SEP-15:51 | 31.10 | 16.68 | 0.402935E+09 | 549.51 | 05-SEP-09:20 | 31.10 | 16.68 |
October | 0.278962E+10 | 6814.89 | 02-OCT-04:02 | 24.82 | 15.04 | 0.411591E+09 | 549.50 | 17-OCT-09:20 | 19.23 | 14.83 |
November | 0.143250E+10 | 2466.25 | 09-NOV-16:00 | 23.30 | 13.01 | 0.370881E+09 | 549.50 | 09-NOV-10:20 | 23.30 | 13.01 |
December | 0.777479E+09 | 1092.97 | 08-DEC-15:00 | 17.20 | 7.54 | 0.318520E+09 | 513.25 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.388568E+11 | 0.471133E+10 | ||||||||
Minimum of Months | 0.777479E+09 | 1092.97 | 17.20 | 7.41 | 0.318520E+09 | 513.25 | 17.20 | 7.41 | ||
Maximum of Months | 0.638739E+10 | 10611.12 | 38.13 | 18.77 | 0.455282E+09 | 557.21 | 37.20 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.624919E+09 | 3319.94 | 13-JAN-13:02 | 16.88 | 8.23 | 0.174563E+09 | 356.46 | 02-JAN-11:09 | 16.88 | 8.23 |
February | 0.947505E+09 | 4606.93 | 08-FEB-13:02 | 12.20 | 4.98 | 0.166985E+09 | 356.46 | 03-FEB-11:09 | 12.20 | 4.98 |
March | 0.180576E+10 | 5256.78 | 16-MAR-10:05 | 19.18 | 7.83 | 0.205008E+09 | 356.46 | 17-MAR-10:09 | 8.48 | 2.02 |
April | 0.334883E+10 | 11212.08 | 30-APR-09:22 | 21.10 | 13.02 | 0.188927E+09 | 356.47 | 14-APR-10:09 | 21.10 | 13.02 |
May | 0.485556E+10 | 10697.44 | 29-MAY-09:02 | 22.67 | 15.59 | 0.205784E+09 | 356.47 | 08-MAY-10:09 | 22.67 | 15.59 |
June | 0.585343E+10 | 11507.27 | 04-JUN-09:02 | 26.38 | 17.02 | 0.205411E+09 | 356.47 | 12-JUN-10:09 | 30.10 | 14.01 |
July | 0.543867E+10 | 11652.34 | 04-JUL-08:52 | 26.10 | 18.11 | 0.191801E+09 | 356.47 | 03-JUL-10:09 | 26.10 | 18.11 |
August | 0.523069E+10 | 11412.41 | 20-AUG-09:12 | 26.83 | 16.55 | 0.213967E+09 | 356.47 | 30-AUG-10:09 | 25.18 | 16.45 |
September | 0.431063E+10 | 11563.30 | 04-SEP-08:32 | 22.57 | 17.97 | 0.190019E+09 | 356.46 | 12-SEP-10:09 | 26.88 | 15.77 |
October | 0.268517E+10 | 6834.64 | 05-OCT-10:05 | 27.30 | 18.49 | 0.195183E+09 | 356.47 | 17-OCT-10:09 | 21.47 | 16.47 |
November | 0.127883E+10 | 4843.06 | 10-NOV-08:50 | 18.22 | 11.69 | 0.184278E+09 | 356.46 | 09-NOV-11:09 | 18.22 | 11.69 |
December | 0.541625E+09 | 2663.23 | 15-DEC-13:02 | 14.08 | 5.59 | 0.164408E+09 | 356.46 | 07-DEC-11:09 | 14.08 | 5.59 |
Annual Sum or Average | 0.369216E+11 | 0.228634E+10 | ||||||||
Minimum of Months | 0.541625E+09 | 2663.23 | 12.20 | 4.98 | 0.164408E+09 | 356.46 | 8.48 | 2.02 | ||
Maximum of Months | 0.585343E+10 | 11652.34 | 27.30 | 18.49 | 0.213967E+09 | 356.47 | 30.10 | 18.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325888E+10 | 8776.72 | 12-JAN-14:05 | 18.40 | 9.78 | 0.395237E+09 | 549.55 | 04-JAN-14:00 | 18.40 | 9.78 |
February | 0.323168E+10 | 9141.27 | 19-FEB-14:43 | 22.70 | 8.52 | 0.362689E+09 | 549.81 | 22-FEB-14:20 | 21.87 | 7.95 |
March | 0.385447E+10 | 7973.93 | 16-MAR-13:05 | 22.30 | 9.05 | 0.437011E+09 | 550.04 | 22-MAR-13:20 | 24.80 | 9.22 |
April | 0.446933E+10 | 10418.99 | 30-APR-15:21 | 30.30 | 12.76 | 0.398610E+09 | 550.41 | 28-APR-13:20 | 30.30 | 12.76 |
May | 0.534116E+10 | 8315.22 | 21-MAY-12:53 | 33.90 | 17.16 | 0.436674E+09 | 549.91 | 30-MAY-13:20 | 32.60 | 16.36 |
June | 0.629958E+10 | 11842.97 | 18-JUN-16:11 | 37.20 | 16.86 | 0.436727E+09 | 549.50 | 12-JUN-09:20 | 37.20 | 16.86 |
July | 0.624548E+10 | 11982.82 | 30-JUL-12:53 | 30.60 | 19.90 | 0.406309E+09 | 553.77 | 20-JUL-15:20 | 30.60 | 19.90 |
August | 0.686870E+10 | 11937.95 | 27-AUG-11:12 | 32.57 | 15.48 | 0.455540E+09 | 550.55 | 03-AUG-13:20 | 32.57 | 15.48 |
September | 0.703633E+10 | 12721.51 | 04-SEP-12:32 | 29.83 | 18.72 | 0.404130E+09 | 560.33 | 29-SEP-13:20 | 27.97 | 14.59 |
October | 0.643786E+10 | 13316.57 | 29-OCT-13:22 | 23.90 | 11.32 | 0.417673E+09 | 579.08 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.478573E+10 | 12802.02 | 11-NOV-13:02 | 18.30 | 8.11 | 0.400891E+09 | 565.34 | 09-NOV-14:09 | 18.30 | 8.11 |
December | 0.304490E+10 | 7454.86 | 07-DEC-13:40 | 15.20 | 6.59 | 0.379894E+09 | 549.52 | 07-DEC-14:09 | 15.68 | 6.76 |
Annual Sum or Average | 0.608741E+11 | 0.493139E+10 | ||||||||
Minimum of Months | 0.304490E+10 | 7454.86 | 15.20 | 6.59 | 0.362689E+09 | 549.50 | 15.68 | 6.76 | ||
Maximum of Months | 0.703633E+10 | 13316.57 | 37.20 | 19.90 | 0.455540E+09 | 579.08 | 37.20 | 19.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.903219E+09 | 3387.72 | 12-JAN-15:30 | 18.90 | 10.10 | 0.226121E+09 | 347.84 | 13-JAN-14:20 | 17.97 | 8.78 |
February | 0.108970E+10 | 5521.86 | 19-FEB-16:43 | 22.30 | 8.28 | 0.213546E+09 | 347.84 | 14-FEB-14:20 | 22.30 | 8.28 |
March | 0.198584E+10 | 6007.79 | 26-MAR-15:53 | 22.20 | 8.76 | 0.267502E+09 | 347.85 | 09-MAR-14:20 | 22.20 | 8.76 |
April | 0.329278E+10 | 12163.97 | 30-APR-18:02 | 29.63 | 12.67 | 0.251634E+09 | 347.86 | 27-APR-09:20 | 29.63 | 12.67 |
May | 0.483585E+10 | 12043.00 | 29-MAY-16:22 | 33.05 | 16.61 | 0.276741E+09 | 347.86 | 05-MAY-13:00 | 33.05 | 16.61 |
June | 0.574605E+10 | 12554.02 | 25-JUN-18:21 | 30.85 | 16.43 | 0.276718E+09 | 347.86 | 12-JUN-09:20 | 30.85 | 16.43 |
July | 0.533087E+10 | 12127.38 | 09-JUL-16:21 | 33.05 | 19.34 | 0.257430E+09 | 347.86 | 03-JUL-09:20 | 33.05 | 19.34 |
August | 0.517496E+10 | 12710.13 | 13-AUG-16:31 | 31.30 | 18.50 | 0.288483E+09 | 347.86 | 28-AUG-09:20 | 25.57 | 16.47 |
September | 0.439315E+10 | 12422.67 | 10-SEP-15:51 | 31.10 | 16.68 | 0.255573E+09 | 347.86 | 05-SEP-09:20 | 31.10 | 16.68 |
October | 0.301737E+10 | 11763.11 | 08-OCT-16:32 | 24.97 | 17.46 | 0.262037E+09 | 347.85 | 17-OCT-09:20 | 19.23 | 14.83 |
November | 0.160957E+10 | 5407.21 | 09-NOV-15:30 | 23.30 | 12.82 | 0.241411E+09 | 347.85 | 09-NOV-10:20 | 23.30 | 12.82 |
December | 0.768707E+09 | 2681.86 | 15-DEC-15:50 | 15.60 | 6.12 | 0.215580E+09 | 347.83 | 01-DEC-14:00 | 15.60 | 6.12 |
Annual Sum or Average | 0.381480E+11 | 0.303278E+10 | ||||||||
Minimum of Months | 0.768707E+09 | 2681.86 | 15.60 | 6.12 | 0.213546E+09 | 347.83 | 15.60 | 6.12 | ||
Maximum of Months | 0.574605E+10 | 12710.13 | 33.05 | 19.34 | 0.288483E+09 | 347.86 | 33.05 | 19.34 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161102E+10 | 9395.20 | 28-JAN-07:03 | -2.9 |
February | 0.116152E+10 | 9781.17 | 03-FEB-07:01 | -5.1 |
March | 0.100334E+10 | 9265.68 | 02-MAR-07:01 | -1.6 |
April | 0.448063E+09 | 3320.31 | 30-APR-06:57 | 16.10 |
May | 0.195934E+09 | 4565.85 | 30-MAY-04:03 | 25.00 |
June | 57897925.39 | 4524.80 | 14-JUN-05:03 | 23.90 |
July | 34597349.71 | 4168.46 | 10-JUL-04:03 | 24.32 |
August | 64387048.96 | 3014.78 | 08-AUG-05:03 | 24.82 |
September | 0.198371E+09 | 4123.76 | 05-SEP-05:12 | 16.30 |
October | 0.474671E+09 | 3204.23 | 01-OCT-08:18 | 19.60 |
November | 0.102434E+10 | 8454.88 | 28-NOV-07:03 | 0.87 |
December | 0.189496E+10 | 10965.36 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.816910E+10 | |||
Minimum of Months | 34597349.71 | 3014.78 | -5.1 | |
Maximum of Months | 0.189496E+10 | 10965.36 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112172E+10 | 2591.73 | 29-JAN-13:30 | 13.05 |
February | 0.704895E+09 | 3930.90 | 20-FEB-15:53 | 23.30 |
March | 0.436735E+09 | 2117.64 | 26-MAR-15:53 | 22.20 |
April | 50640016.77 | 2804.75 | 30-APR-14:42 | 29.90 |
May | 20446071.89 | 2251.79 | 21-MAY-15:32 | 34.40 |
June | 16505536.50 | 2818.44 | 04-JUN-15:41 | 35.40 |
July | 20447568.17 | 2603.28 | 09-JUL-16:21 | 33.05 |
August | 17090433.61 | 2676.31 | 27-AUG-15:11 | 35.00 |
September | 18798396.79 | 2841.02 | 10-SEP-15:51 | 31.10 |
October | 50734412.09 | 4421.31 | 08-OCT-15:52 | 26.10 |
November | 0.561279E+09 | 4070.97 | 19-NOV-12:33 | 15.73 |
December | 0.123574E+10 | 2770.53 | 04-DEC-12:00 | 9.40 |
Annual Sum or Average | 0.425504E+10 | |||
Minimum of Months | 16505536.50 | 2117.64 | 9.40 | |
Maximum of Months | 0.123574E+10 | 4421.31 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.618924E+09 | 2338.31 | 06-JAN-08:06 | -0.6 |
February | 0.313379E+09 | 2407.40 | 20-FEB-13:02 | 21.28 |
March | 0.139276E+09 | 2298.21 | 02-MAR-08:09 | -0.9 |
April | 9768798.31 | 1492.32 | 02-APR-14:30 | 26.95 |
May | 10375924.82 | 1339.35 | 31-MAY-05:03 | 24.22 |
June | 11136776.26 | 1937.76 | 09-JUN-05:03 | 23.80 |
July | 15556628.19 | 1887.27 | 26-JUL-04:03 | 25.82 |
August | 16994164.99 | 1928.07 | 27-AUG-15:11 | 35.00 |
September | 19629001.68 | 2138.99 | 17-SEP-15:21 | 32.80 |
October | 33588812.98 | 2950.12 | 08-OCT-16:22 | 25.25 |
November | 0.221086E+09 | 2821.93 | 19-NOV-12:23 | 15.55 |
December | 0.687125E+09 | 2279.95 | 22-DEC-08:07 | -1.3 |
Annual Sum or Average | 0.209684E+10 | |||
Minimum of Months | 9768798.31 | 1339.35 | -1.3 | |
Maximum of Months | 0.687125E+09 | 2950.12 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2303982.95 | 15353.32 | 17-JAN-07:03 | 5.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 5200495.32 | 14147.66 | 26-DEC-07:02 | -0.7 |
Annual Sum or Average | 7504478.27 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 5200495.32 | 15353.32 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218889E+09 | 27002.21 | 17-JAN-06:11 | 4.60 |
February | 55020854.50 | 25351.29 | 03-FEB-07:01 | -5.1 |
March | 14171670.13 | 25235.73 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 70227386.02 | 26503.43 | 28-NOV-06:01 | 1.02 |
December | 0.405498E+09 | 27857.33 | 04-DEC-06:01 | -1.0 |
Annual Sum or Average | 0.763807E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.405498E+09 | 27857.33 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.961783E+09 | 10135.87 | 09-JAN-06:11 | 3.17 |
February | 0.490677E+09 | 9714.71 | 01-FEB-06:01 | -0.8 |
March | 0.214780E+09 | 9566.76 | 02-MAR-06:01 | -3.5 |
April | 6736924.90 | 7599.47 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 1017724.78 | 4509.56 | 25-OCT-06:03 | 6.88 |
November | 0.332881E+09 | 10122.94 | 27-NOV-06:11 | 3.30 |
December | 0.131521E+10 | 10508.24 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.332309E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.131521E+10 | 10508.24 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427816E+09 | 8899.90 | 09-JAN-06:11 | 3.17 |
February | 0.169633E+09 | 8499.98 | 01-FEB-06:01 | -0.8 |
March | 82076768.58 | 8381.81 | 02-MAR-06:01 | -3.5 |
April | 819294.41 | 2529.02 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 518692.43 | 3209.77 | 25-OCT-06:03 | 6.88 |
November | 0.129863E+09 | 8906.12 | 27-NOV-06:11 | 3.30 |
December | 0.574869E+09 | 9238.00 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.138560E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.574869E+09 | 9238.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489351E+09 | 10930.49 | 09-JAN-06:11 | 3.17 |
February | 0.241121E+09 | 10542.90 | 01-FEB-06:01 | -0.8 |
March | 0.130157E+09 | 10526.16 | 02-MAR-06:01 | -3.5 |
April | 6236086.45 | 7696.93 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 335844.15 | 2238.96 | 25-OCT-06:03 | 6.88 |
November | 0.163251E+09 | 11038.22 | 27-NOV-06:11 | 3.30 |
December | 0.641469E+09 | 11380.32 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.167192E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.641469E+09 | 11380.32 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536187E+09 | 9180.21 | 09-JAN-06:11 | 3.17 |
February | 0.279025E+09 | 8757.18 | 01-FEB-06:01 | -0.8 |
March | 0.112974E+09 | 8596.12 | 02-MAR-06:01 | -3.5 |
April | 4096635.71 | 4956.06 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 322875.84 | 1853.15 | 25-OCT-06:03 | 6.88 |
November | 0.187717E+09 | 9202.87 | 27-NOV-06:11 | 3.30 |
December | 0.723300E+09 | 9478.86 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.184362E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.723300E+09 | 9478.86 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191385E+09 | 7290.31 | 28-JAN-06:01 | -3.3 |
February | 0.132853E+09 | 7244.65 | 03-FEB-06:01 | -3.7 |
March | 66929737.79 | 7287.23 | 02-MAR-06:01 | -3.5 |
April | 79018.37 | 526.79 | 12-APR-06:03 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 10678099.12 | 6774.23 | 28-NOV-07:03 | 0.87 |
December | 0.222785E+09 | 7342.66 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.624710E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.222785E+09 | 7342.66 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57097419.80 | 5812.77 | 17-JAN-06:11 | 4.60 |
February | 22694702.78 | 5879.30 | 03-FEB-06:01 | -3.7 |
March | 12865977.58 | 5773.78 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1656150.87 | 3980.65 | 28-NOV-07:03 | 0.87 |
December | 66964519.99 | 5964.70 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.161279E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 66964519.99 | 5964.70 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.857164E+09 | 9259.34 | 27-JAN-07:10 | -4.3 |
February | 0.695326E+09 | 9442.23 | 03-FEB-07:10 | -5.1 |
March | 0.729853E+09 | 9089.06 | 02-MAR-07:10 | -1.6 |
April | 0.198483E+09 | 8080.68 | 12-APR-06:10 | 3.87 |
May | 16070285.57 | 7482.24 | 02-MAY-06:07 | 9.87 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 1450419.83 | 2766.40 | 25-SEP-06:07 | 10.55 |
October | 75043912.19 | 7645.34 | 25-OCT-06:05 | 6.88 |
November | 0.484699E+09 | 8598.78 | 28-NOV-07:10 | 0.87 |
December | 0.932462E+09 | 9661.08 | 27-DEC-07:10 | -4.3 |
Annual Sum or Average | 0.399055E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.932462E+09 | 9661.08 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61262575.72 | 5696.19 | 17-JAN-06:11 | 4.60 |
February | 39589380.62 | 5398.32 | 02-FEB-07:01 | -4.0 |
March | 14660077.75 | 5701.65 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 3274420.53 | 4914.11 | 28-NOV-07:03 | 0.87 |
December | 75340451.57 | 5815.63 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.194127E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 75340451.57 | 5815.63 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226187E+09 | 7995.62 | 28-JAN-06:01 | -3.3 |
February | 94474019.37 | 7848.72 | 02-FEB-06:01 | -3.5 |
March | 29486400.06 | 7787.12 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 50517502.79 | 7967.76 | 28-NOV-06:01 | 1.02 |
December | 0.371123E+09 | 8261.15 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.771789E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.371123E+09 | 8261.15 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108313E+09 | 6633.96 | 28-JAN-06:01 | -3.3 |
February | 32356669.34 | 6482.44 | 02-FEB-06:01 | -3.5 |
March | 12834938.21 | 6413.37 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 18903888.52 | 6622.23 | 28-NOV-06:01 | 1.02 |
December | 0.165101E+09 | 6930.96 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.337509E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.165101E+09 | 6930.96 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101041E+09 | 8755.93 | 17-JAN-06:11 | 4.60 |
February | 37090168.44 | 8569.10 | 02-FEB-06:01 | -3.5 |
March | 12904923.15 | 8516.29 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 18659141.70 | 8819.18 | 28-NOV-06:01 | 1.02 |
December | 0.158360E+09 | 9223.05 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.328055E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.158360E+09 | 9223.05 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124404E+09 | 6411.37 | 30-JAN-06:01 | -0.2 |
February | 52319792.23 | 6367.54 | 03-FEB-06:01 | -3.7 |
March | 13917237.44 | 6171.68 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 25930681.33 | 6388.65 | 28-NOV-06:01 | 1.02 |
December | 0.197697E+09 | 6783.60 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.414269E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.197697E+09 | 6783.60 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337086E+10 | 3541.90 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.305765E+10 | 3541.90 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.363307E+10 | 3541.90 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.324543E+10 | 3541.90 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.350197E+10 | 3541.90 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.348497E+10 | 3541.90 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.326242E+10 | 3541.90 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.363307E+10 | 3541.90 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.324543E+10 | 3541.90 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.337086E+10 | 3541.90 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.333119E+10 | 3541.90 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.326242E+10 | 3541.90 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.403994E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.305765E+10 | 3541.90 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.363307E+10 | 3541.90 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337086E+10 | 3541.90 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.305765E+10 | 3541.90 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.363307E+10 | 3541.90 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.324543E+10 | 3541.90 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.350197E+10 | 3541.90 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.348497E+10 | 3541.90 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.326242E+10 | 3541.90 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.363307E+10 | 3541.90 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.324543E+10 | 3541.90 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.337086E+10 | 3541.90 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.333119E+10 | 3541.90 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.326242E+10 | 3541.90 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.403994E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.305765E+10 | 3541.90 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.363307E+10 | 3541.90 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.337086E+10 | 3541.90 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.305765E+10 | 3541.90 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.363307E+10 | 3541.90 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.324543E+10 | 3541.90 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.350197E+10 | 3541.90 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.348497E+10 | 3541.90 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.326242E+10 | 3541.90 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.363307E+10 | 3541.90 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.324543E+10 | 3541.90 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.337086E+10 | 3541.90 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.333119E+10 | 3541.90 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.326242E+10 | 3541.90 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.403994E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.305765E+10 | 3541.90 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.363307E+10 | 3541.90 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.449713E+09 | 698.42 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.391931E+09 | 615.52 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.436915E+09 | 594.42 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.376284E+09 | 415.55 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.399381E+09 | 382.61 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.392346E+09 | 356.16 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.371179E+09 | 412.89 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.419993E+09 | 411.06 | 17-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.384055E+09 | 463.46 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.418213E+09 | 640.75 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.439948E+09 | 746.66 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.443037E+09 | 746.66 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.492300E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.371179E+09 | 356.16 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.449713E+09 | 746.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.279886E+09 | 442.59 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.245990E+09 | 400.46 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.275329E+09 | 381.95 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.239387E+09 | 254.21 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.255023E+09 | 247.49 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.250901E+09 | 225.48 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.237702E+09 | 256.49 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.267048E+09 | 259.37 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241953E+09 | 242.62 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.262510E+09 | 397.92 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.275655E+09 | 472.70 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.277057E+09 | 472.70 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.310844E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.237702E+09 | 225.48 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.279886E+09 | 472.70 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.427079E+09 | 695.09 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.379001E+09 | 587.85 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.432264E+09 | 587.05 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.378123E+09 | 415.49 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.403055E+09 | 385.70 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.396746E+09 | 356.16 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.375903E+09 | 415.21 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.422183E+09 | 413.01 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.382185E+09 | 391.52 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.409589E+09 | 636.46 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.419776E+09 | 746.66 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.422208E+09 | 746.66 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.484811E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.375903E+09 | 356.16 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.432264E+09 | 746.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.273977E+09 | 438.43 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241543E+09 | 367.81 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274317E+09 | 357.90 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.238219E+09 | 309.55 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252571E+09 | 253.86 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248506E+09 | 240.80 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.235143E+09 | 265.08 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.266028E+09 | 312.25 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242210E+09 | 300.32 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.261094E+09 | 407.19 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.267326E+09 | 472.67 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.269998E+09 | 472.67 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307093E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.235143E+09 | 240.80 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.274317E+09 | 472.67 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.447574E+09 | 696.58 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.390637E+09 | 609.41 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.435851E+09 | 588.59 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.375934E+09 | 413.41 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.399159E+09 | 379.11 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.392138E+09 | 356.16 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.370834E+09 | 410.62 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.419504E+09 | 408.71 | 17-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.383249E+09 | 403.12 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.417129E+09 | 636.73 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.438215E+09 | 746.66 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.441277E+09 | 746.66 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.491150E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.370834E+09 | 356.16 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.447574E+09 | 746.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.279276E+09 | 441.66 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.245426E+09 | 398.24 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274847E+09 | 379.17 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.239135E+09 | 252.47 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.254718E+09 | 246.00 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.250683E+09 | 225.48 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.237328E+09 | 255.00 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.266703E+09 | 258.00 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241636E+09 | 241.68 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.262128E+09 | 395.53 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.275042E+09 | 472.70 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.276409E+09 | 472.70 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.310333E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.237328E+09 | 225.48 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.279276E+09 | 472.70 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.425903E+09 | 693.08 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.378371E+09 | 581.60 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.431655E+09 | 580.87 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.377632E+09 | 413.35 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.402699E+09 | 382.18 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.396337E+09 | 356.16 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.375243E+09 | 413.08 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.421539E+09 | 410.78 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.381604E+09 | 388.94 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.409233E+09 | 632.23 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.419259E+09 | 746.66 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.421925E+09 | 746.66 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.484140E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.375243E+09 | 356.16 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.431655E+09 | 746.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.273238E+09 | 437.32 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241052E+09 | 364.59 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.273835E+09 | 354.23 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.237916E+09 | 304.58 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252365E+09 | 252.33 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248293E+09 | 238.83 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.234836E+09 | 263.95 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.265588E+09 | 307.61 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241773E+09 | 294.87 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.260586E+09 | 405.18 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.266703E+09 | 472.67 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.269511E+09 | 472.67 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306570E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.234836E+09 | 238.83 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.273835E+09 | 472.67 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.449712E+09 | 698.41 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.391930E+09 | 615.52 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.436914E+09 | 594.41 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.376284E+09 | 415.54 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.399381E+09 | 382.60 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.392346E+09 | 356.16 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.371179E+09 | 412.88 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.419992E+09 | 411.05 | 17-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.384054E+09 | 463.46 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.418212E+09 | 640.74 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.439947E+09 | 746.66 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.443024E+09 | 746.66 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.492298E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.371179E+09 | 356.16 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.449712E+09 | 746.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.279886E+09 | 442.59 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.245990E+09 | 400.46 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.275329E+09 | 381.94 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.239387E+09 | 254.20 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.255023E+09 | 247.48 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.250901E+09 | 225.48 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.237702E+09 | 256.48 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.267048E+09 | 259.37 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241953E+09 | 242.62 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.262510E+09 | 397.91 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.275654E+09 | 472.70 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.277056E+09 | 472.70 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.310844E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.237702E+09 | 225.48 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.279886E+09 | 472.70 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.427079E+09 | 695.08 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.379000E+09 | 587.84 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.432263E+09 | 587.04 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.378123E+09 | 415.48 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.403054E+09 | 385.69 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.396746E+09 | 356.16 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.375903E+09 | 415.21 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.422183E+09 | 413.01 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.382185E+09 | 391.52 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.409589E+09 | 636.45 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.419775E+09 | 746.66 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.422208E+09 | 746.66 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.484811E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.375903E+09 | 356.16 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.432263E+09 | 746.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.273977E+09 | 438.43 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241542E+09 | 367.80 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274317E+09 | 357.89 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.238219E+09 | 309.54 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.252571E+09 | 253.86 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.248505E+09 | 240.80 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.235143E+09 | 265.08 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.266027E+09 | 312.24 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.242210E+09 | 300.32 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.261093E+09 | 407.18 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.267326E+09 | 472.67 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.269998E+09 | 472.67 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307093E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.235143E+09 | 240.80 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.274317E+09 | 472.67 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.337086E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.305765E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.363307E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.324543E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.350197E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.348497E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.326242E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.363307E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.324543E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.337086E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.333119E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.326242E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.403994E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.305765E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.363307E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.337086E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.305765E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.363307E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.324543E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.350197E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.348497E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.326242E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.363307E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.324543E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.337086E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.333119E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.326242E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.403994E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.305765E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.363307E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.337086E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.305765E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.363307E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.324543E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.350197E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.348497E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.326242E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.363307E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.324543E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.337086E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.333119E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.326242E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.403994E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.305765E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.363307E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.449713E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530538E+09 |
February | 0.901968E+09 | 0.391931E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94661.31 | 0.459530E+09 |
March | 0.107774E+10 | 0.436915E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 225297.07 | 0.489345E+09 |
April | 0.956342E+09 | 0.376284E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29819845.23 | 0.274052E+09 |
May | 0.103597E+10 | 0.399381E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84251141.05 | 0.156306E+09 |
June | 0.103308E+10 | 0.392346E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132132E+09 | 59709049.00 |
July | 0.959235E+09 | 0.371179E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108885E+09 | 45883337.41 |
August | 0.107774E+10 | 0.419993E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88171585.26 | 59021612.99 |
September | 0.956342E+09 | 0.384055E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28198769.75 | 78308244.32 |
October | 0.994195E+09 | 0.418213E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10511109.71 | 0.240405E+09 |
November | 0.984487E+09 | 0.439948E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441874E+09 |
December | 0.959235E+09 | 0.443037E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460663E+09 |
Annual Sum or Average | 0.119305E+11 | 0.492300E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482289E+09 | 0.329564E+10 |
Minimum of Months | 0.901968E+09 | 0.371179E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45883337.41 |
Maximum of Months | 0.107774E+10 | 0.449713E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132132E+09 | 0.530538E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.279886E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364668E+09 |
February | 0.571020E+09 | 0.245990E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318926E+09 |
March | 0.682301E+09 | 0.275329E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108173.54 | 0.347110E+09 |
April | 0.605444E+09 | 0.239387E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17398406.93 | 0.192840E+09 |
May | 0.655854E+09 | 0.255023E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55022185.34 | 0.108990E+09 |
June | 0.654023E+09 | 0.250901E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86960398.82 | 41079646.09 |
July | 0.607275E+09 | 0.237702E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71380063.14 | 31993308.51 |
August | 0.682301E+09 | 0.267048E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57095893.19 | 41168142.92 |
September | 0.605444E+09 | 0.241953E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17737532.20 | 56209668.00 |
October | 0.629407E+09 | 0.262510E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6014461.11 | 0.169132E+09 |
November | 0.623262E+09 | 0.275655E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308706E+09 |
December | 0.607275E+09 | 0.277057E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316056E+09 |
Annual Sum or Average | 0.755301E+10 | 0.310844E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311717E+09 | 0.229688E+10 |
Minimum of Months | 0.571020E+09 | 0.237702E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31993308.51 |
Maximum of Months | 0.682301E+09 | 0.279886E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86960398.82 | 0.364668E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.427079E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590719E+09 |
February | 0.901968E+09 | 0.379001E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505913E+09 |
March | 0.107774E+10 | 0.432264E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162215.15 | 0.540026E+09 |
April | 0.956342E+09 | 0.378123E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25407052.43 | 0.286643E+09 |
May | 0.103597E+10 | 0.403055E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83675674.35 | 0.156155E+09 |
June | 0.103308E+10 | 0.396746E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133115E+09 | 58783202.14 |
July | 0.959235E+09 | 0.375903E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109404E+09 | 45057829.03 |
August | 0.107774E+10 | 0.422183E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86384043.09 | 60386870.97 |
September | 0.956342E+09 | 0.382185E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25951003.96 | 84985823.05 |
October | 0.994195E+09 | 0.409589E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8164141.40 | 0.268005E+09 |
November | 0.984487E+09 | 0.419776E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493832E+09 |
December | 0.959235E+09 | 0.422208E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510172E+09 |
Annual Sum or Average | 0.119305E+11 | 0.484811E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472263E+09 | 0.360068E+10 |
Minimum of Months | 0.901968E+09 | 0.375903E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45057829.03 |
Maximum of Months | 0.107774E+10 | 0.432264E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133115E+09 | 0.590719E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.273977E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368167E+09 |
February | 0.570983E+09 | 0.241543E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321269E+09 |
March | 0.682256E+09 | 0.274317E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108210.49 | 0.349919E+09 |
April | 0.605404E+09 | 0.238219E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16181110.18 | 0.195357E+09 |
May | 0.655811E+09 | 0.252571E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52385211.97 | 0.110632E+09 |
June | 0.653980E+09 | 0.248506E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85048625.07 | 42988212.71 |
July | 0.607235E+09 | 0.235143E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69731674.10 | 33687630.61 |
August | 0.682256E+09 | 0.266028E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55451937.54 | 42058170.68 |
September | 0.605404E+09 | 0.242210E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17547999.09 | 56818661.30 |
October | 0.629366E+09 | 0.261094E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5713298.81 | 0.172793E+09 |
November | 0.623221E+09 | 0.267326E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309901E+09 |
December | 0.607235E+09 | 0.269998E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318749E+09 |
Annual Sum or Average | 0.755252E+10 | 0.307093E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302168E+09 | 0.232234E+10 |
Minimum of Months | 0.570983E+09 | 0.235143E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33687630.61 |
Maximum of Months | 0.682256E+09 | 0.274317E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85048625.07 | 0.368167E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.447574E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307232E+09 |
February | 0.901968E+09 | 0.390637E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 363026.97 | 0.253243E+09 |
March | 0.107774E+10 | 0.435851E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 314191.81 | 0.257575E+09 |
April | 0.956342E+09 | 0.375934E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20053117.32 | 0.140306E+09 |
May | 0.103597E+10 | 0.399159E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52249049.53 | 77945266.36 |
June | 0.103308E+10 | 0.392138E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76793346.13 | 28220830.50 |
July | 0.959235E+09 | 0.370834E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62941568.22 | 22777691.55 |
August | 0.107774E+10 | 0.419504E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49893260.44 | 32032351.89 |
September | 0.956342E+09 | 0.383249E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16155817.01 | 44613293.91 |
October | 0.994195E+09 | 0.417129E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6563272.70 | 0.141400E+09 |
November | 0.984487E+09 | 0.438215E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267261E+09 |
December | 0.959235E+09 | 0.441277E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274312E+09 |
Annual Sum or Average | 0.119305E+11 | 0.491150E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285327E+09 | 0.184692E+10 |
Minimum of Months | 0.901968E+09 | 0.370834E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22777691.55 |
Maximum of Months | 0.107774E+10 | 0.447574E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76793346.13 | 0.307232E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.279276E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214970E+09 |
February | 0.571020E+09 | 0.245426E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180936E+09 |
March | 0.682301E+09 | 0.274847E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67365.77 | 0.189533E+09 |
April | 0.605444E+09 | 0.239135E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10243031.60 | 0.104527E+09 |
May | 0.655854E+09 | 0.254718E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31143698.72 | 58154876.63 |
June | 0.654023E+09 | 0.250683E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48213915.26 | 21106054.65 |
July | 0.607275E+09 | 0.237328E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39212113.13 | 17247381.15 |
August | 0.682301E+09 | 0.266703E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31001871.38 | 23739686.90 |
September | 0.605444E+09 | 0.241636E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9638610.25 | 33132943.79 |
October | 0.629407E+09 | 0.262128E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3538049.87 | 0.100947E+09 |
November | 0.623262E+09 | 0.275042E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189677E+09 |
December | 0.607275E+09 | 0.276409E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191879E+09 |
Annual Sum or Average | 0.755301E+10 | 0.310333E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173059E+09 | 0.132585E+10 |
Minimum of Months | 0.571020E+09 | 0.237328E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17247381.15 |
Maximum of Months | 0.682301E+09 | 0.279276E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48213915.26 | 0.214970E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.425903E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328449E+10 |
February | 0.901968E+09 | 0.378371E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264333E+10 |
March | 0.107774E+10 | 0.431655E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3924851.50 | 0.247390E+10 |
April | 0.956342E+09 | 0.377632E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257105E+09 | 0.107401E+10 |
May | 0.103597E+10 | 0.402699E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719847E+09 | 0.439877E+09 |
June | 0.103308E+10 | 0.396337E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139169E+10 | 0.160411E+09 |
July | 0.959235E+09 | 0.375243E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113958E+10 | 0.111662E+09 |
August | 0.107774E+10 | 0.421539E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968016E+09 | 0.263154E+09 |
September | 0.956342E+09 | 0.381604E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663832E+09 | 0.409424E+09 |
October | 0.994195E+09 | 0.409233E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143193E+09 | 0.118529E+10 |
November | 0.984487E+09 | 0.419259E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252091E+10 |
December | 0.959235E+09 | 0.421925E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344149E+10 |
Annual Sum or Average | 0.119305E+11 | 0.484140E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528719E+10 | 0.180079E+11 |
Minimum of Months | 0.901968E+09 | 0.375243E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111662E+09 |
Maximum of Months | 0.107774E+10 | 0.431655E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139169E+10 | 0.344149E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.273238E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216512E+09 |
February | 0.570983E+09 | 0.241052E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181023E+09 |
March | 0.682256E+09 | 0.273835E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65298.46 | 0.191345E+09 |
April | 0.605404E+09 | 0.237916E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9054508.79 | 0.105894E+09 |
May | 0.655811E+09 | 0.252365E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29461180.39 | 59548853.24 |
June | 0.653980E+09 | 0.248293E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46986889.00 | 22259881.80 |
July | 0.607235E+09 | 0.234836E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38204628.00 | 18289381.38 |
August | 0.682256E+09 | 0.265588E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29974762.23 | 24518136.73 |
September | 0.605404E+09 | 0.241773E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9504188.25 | 33759683.35 |
October | 0.629366E+09 | 0.260586E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3329724.51 | 0.103804E+09 |
November | 0.623221E+09 | 0.266703E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190796E+09 |
December | 0.607235E+09 | 0.269511E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192057E+09 |
Annual Sum or Average | 0.755252E+10 | 0.306570E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166581E+09 | 0.133981E+10 |
Minimum of Months | 0.570983E+09 | 0.234836E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18289381.38 |
Maximum of Months | 0.682256E+09 | 0.273835E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46986889.00 | 0.216512E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.449712E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479543E+09 |
February | 0.901968E+09 | 0.391930E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91857.95 | 0.411642E+09 |
March | 0.107774E+10 | 0.436914E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 179752.67 | 0.434470E+09 |
April | 0.956342E+09 | 0.376284E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26638232.48 | 0.240149E+09 |
May | 0.103597E+10 | 0.399381E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72862888.51 | 0.136280E+09 |
June | 0.103308E+10 | 0.392346E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112390E+09 | 50719637.48 |
July | 0.959235E+09 | 0.371179E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93081332.44 | 38753041.49 |
August | 0.107774E+10 | 0.419992E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75328677.62 | 50953685.48 |
September | 0.956342E+09 | 0.384054E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24725627.72 | 68249053.73 |
October | 0.994195E+09 | 0.418212E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9202822.09 | 0.214734E+09 |
November | 0.984487E+09 | 0.439947E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404467E+09 |
December | 0.959235E+09 | 0.443024E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418704E+09 |
Annual Sum or Average | 0.119305E+11 | 0.492298E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414502E+09 | 0.294866E+10 |
Minimum of Months | 0.901968E+09 | 0.371179E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38753041.49 |
Maximum of Months | 0.107774E+10 | 0.449712E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112390E+09 | 0.479543E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.279886E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330297E+09 |
February | 0.421807E+09 | 0.245990E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285572E+09 |
March | 0.502994E+09 | 0.275329E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74984.93 | 0.307130E+09 |
April | 0.447140E+09 | 0.239387E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14925669.46 | 0.167943E+09 |
May | 0.484071E+09 | 0.255023E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46228108.76 | 95034820.90 |
June | 0.482240E+09 | 0.250901E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72990224.67 | 34961419.19 |
July | 0.448971E+09 | 0.237702E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60090472.97 | 27094112.16 |
August | 0.502994E+09 | 0.267048E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48059053.33 | 35598844.04 |
September | 0.447140E+09 | 0.241953E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14844050.17 | 48765477.11 |
October | 0.465148E+09 | 0.262510E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5069602.44 | 0.150269E+09 |
November | 0.460569E+09 | 0.275654E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281230E+09 |
December | 0.448971E+09 | 0.277056E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288060E+09 |
Annual Sum or Average | 0.557719E+10 | 0.310844E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262282E+09 | 0.205195E+10 |
Minimum of Months | 0.421807E+09 | 0.237702E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27094112.16 |
Maximum of Months | 0.502994E+09 | 0.279886E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72990224.67 | 0.330297E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.427079E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528722E+09 |
February | 0.901968E+09 | 0.379000E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449198E+09 |
March | 0.107774E+10 | 0.432263E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142370.79 | 0.474661E+09 |
April | 0.956342E+09 | 0.378123E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21860596.68 | 0.249942E+09 |
May | 0.103597E+10 | 0.403054E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71758313.61 | 0.136371E+09 |
June | 0.103308E+10 | 0.396746E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113315E+09 | 49931724.86 |
July | 0.959235E+09 | 0.375903E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93474296.56 | 38052957.21 |
August | 0.107774E+10 | 0.422183E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73499154.69 | 52115865.85 |
September | 0.956342E+09 | 0.382185E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22085586.35 | 73840897.09 |
October | 0.994195E+09 | 0.409589E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6777547.77 | 0.236100E+09 |
November | 0.984487E+09 | 0.419775E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444320E+09 |
December | 0.959235E+09 | 0.422208E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459396E+09 |
Annual Sum or Average | 0.119305E+11 | 0.484811E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402913E+09 | 0.319265E+10 |
Minimum of Months | 0.901968E+09 | 0.375903E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38052957.21 |
Maximum of Months | 0.107774E+10 | 0.432263E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113315E+09 | 0.528722E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.273977E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331507E+09 |
February | 0.570983E+09 | 0.241542E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286582E+09 |
March | 0.682256E+09 | 0.274317E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95100.91 | 0.308882E+09 |
April | 0.605404E+09 | 0.238219E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13740087.78 | 0.170534E+09 |
May | 0.655811E+09 | 0.252571E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44408039.66 | 96528687.56 |
June | 0.653980E+09 | 0.248505E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71720758.17 | 36537831.43 |
July | 0.607235E+09 | 0.235143E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58961256.72 | 28539824.66 |
August | 0.682256E+09 | 0.266027E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46796202.98 | 36256129.13 |
September | 0.605404E+09 | 0.242210E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14880688.25 | 49445714.08 |
October | 0.629366E+09 | 0.261093E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4800871.20 | 0.152980E+09 |
November | 0.623221E+09 | 0.267326E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281444E+09 |
December | 0.607235E+09 | 0.269998E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288562E+09 |
Annual Sum or Average | 0.755252E+10 | 0.307093E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255403E+09 | 0.206780E+10 |
Minimum of Months | 0.570983E+09 | 0.235143E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28539824.66 |
Maximum of Months | 0.682256E+09 | 0.274317E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71720758.17 | 0.331507E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698241E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594845E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88217.40 | 0.621180E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29137617.07 | 0.335534E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87997047.80 | 0.184169E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140054E+09 | 63631497.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115860E+09 | 47159679.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91011293.62 | 67264430.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26487162.95 | 95374718.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9734411.01 | 0.310975E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596496E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613870E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500370E+09 | 0.422874E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47159679.74 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140054E+09 | 0.698241E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846502E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735338E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155790.81 | 0.777558E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37967788.72 | 0.429848E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110114E+09 | 0.240009E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176327E+09 | 85066266.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144907E+09 | 62856291.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115750E+09 | 87310650.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34545026.60 | 0.120770E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13077736.50 | 0.385726E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725681E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739865E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632844E+09 | 0.523653E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62856291.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176327E+09 | 0.846502E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822301E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718520E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784039E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24508703.74 | 0.425294E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91989878.84 | 0.224740E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172359E+09 | 79618810.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135241E+09 | 61266038.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109259E+09 | 81615117.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26102010.08 | 0.118615E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9837643.31 | 0.380318E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690179E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705855E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569296E+09 | 0.509236E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61266038.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172359E+09 | 0.822301E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3541.90 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3541.90 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3541.90 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3541.90 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3541.90 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3541.90 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3541.90 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3541.90 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3541.90 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3541.90 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3541.90 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3541.90 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3541.90 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3541.90 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3541.90 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3541.90 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3541.90 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3541.90 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3541.90 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3541.90 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3541.90 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3541.90 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3541.90 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3541.90 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3541.90 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3541.90 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3541.90 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3541.90 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3541.90 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3541.90 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3541.90 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3541.90 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3541.90 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3541.90 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3541.90 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3541.90 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3541.90 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3541.90 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 698.42 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1445.34 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 615.52 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 20-FEB-16:00 | 1855.75 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 594.42 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.19 | 19-MAR-13:53 | 1352.95 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 415.55 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.48 | 01-APR-17:03 | 1519.97 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 382.61 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 524.79 | 14-MAY-15:55 | 677.88 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 356.16 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.16 | 04-JUN-18:53 | 564.92 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 412.89 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.03 | 02-JUL-20:57 | 285.26 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 411.06 | 17-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.44 | 26-AUG-17:02 | 498.83 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 463.46 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.58 | 10-SEP-14:53 | 282.55 | 23-SEP-17:10 |
October | 1306.65 | 02-OCT-09:09 | 640.75 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.65 | 01-OCT-15:00 | 718.32 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 746.66 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 835.62 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 746.66 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1090.43 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.55 | |||||
Maximum of Months | 1306.65 | 746.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 601.03 | 1855.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 442.59 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 961.84 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 400.46 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1240.23 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 381.95 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 22-MAR-13:00 | 934.90 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 254.21 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.73 | 01-APR-17:03 | 1014.18 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 247.49 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.26 | 14-MAY-15:55 | 447.81 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 225.48 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.40 | 04-JUN-18:53 | 375.43 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 256.49 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.18 | 02-JUL-20:57 | 190.37 | 18-JUL-21:10 |
August | 827.22 | 01-AUG-09:09 | 259.37 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.00 | 27-AUG-13:00 | 337.03 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 242.62 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.06 | 10-SEP-15:26 | 225.61 | 24-SEP-10:30 |
October | 827.22 | 02-OCT-09:09 | 397.92 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.92 | 01-OCT-14:55 | 485.36 | 23-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 472.70 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 654.09 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 472.70 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 731.48 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.37 | |||||
Maximum of Months | 827.22 | 472.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 401.18 | 1240.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 695.09 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1470.93 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 587.85 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1902.08 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 587.05 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 22-MAR-13:00 | 1451.28 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 415.49 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.53 | 21-APR-15:00 | 1535.35 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 385.70 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 525.21 | 14-MAY-15:53 | 682.23 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 356.16 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.29 | 04-JUN-18:53 | 561.60 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 415.21 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 605.05 | 02-JUL-21:00 | 285.85 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 413.01 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.01 | 27-AUG-13:00 | 506.55 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 391.52 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.39 | 10-SEP-15:24 | 317.92 | 24-SEP-11:00 |
October | 1306.65 | 02-OCT-09:09 | 636.46 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.73 | 01-OCT-14:55 | 759.84 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 746.66 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 980.48 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 746.66 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1158.21 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 356.16 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.85 | |||||
Maximum of Months | 1306.65 | 746.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 605.05 | 1902.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 438.43 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 961.83 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 367.81 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1246.33 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 357.90 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22-MAR-13:00 | 938.07 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 309.55 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.69 | 21-APR-15:00 | 1018.97 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 253.86 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.11 | 14-MAY-16:00 | 460.23 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 240.80 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.24 | 04-JUN-18:53 | 389.05 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 265.08 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.65 | 02-JUL-20:57 | 244.59 | 04-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 312.25 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.01 | 27-AUG-13:00 | 345.27 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 300.32 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.84 | 10-SEP-14:58 | 204.98 | 24-SEP-16:00 |
October | 827.17 | 02-OCT-09:09 | 407.19 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.47 | 01-OCT-14:55 | 503.12 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 472.67 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 582.50 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 472.67 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 739.40 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 240.80 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.98 | |||||
Maximum of Months | 827.17 | 472.67 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 397.65 | 1246.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 696.58 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 845.53 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 609.41 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.93 | 20-FEB-16:00 | 1066.53 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 588.59 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 | 19-MAR-13:53 | 766.32 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 413.41 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.54 | 01-APR-17:03 | 862.42 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 379.11 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.37 | 14-MAY-15:43 | 368.01 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 356.16 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.90 | 04-JUN-19:00 | 296.67 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 410.62 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.37 | 02-JUL-21:20 | 152.13 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 408.71 | 17-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.48 | 26-AUG-18:00 | 259.10 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 403.12 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.35 | 10-SEP-15:10 | 158.19 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 636.73 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.17 | 01-OCT-14:52 | 418.20 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 746.66 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 543.29 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 746.66 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 697.61 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.13 | |||||
Maximum of Months | 1306.65 | 746.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 339.37 | 1066.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 441.66 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 571.18 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 398.24 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 732.12 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 379.17 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 22-MAR-13:00 | 555.63 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 252.47 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 | 01-APR-17:03 | 593.66 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 246.00 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.05 | 14-MAY-15:41 | 252.29 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 225.48 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.25 | 04-JUN-18:57 | 204.52 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 255.00 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.36 | 02-JUL-21:20 | 109.97 | 04-JUL-19:15 |
August | 827.22 | 01-AUG-09:09 | 258.00 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.67 | 26-AUG-18:00 | 185.56 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 241.68 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.65 | 10-SEP-15:05 | 126.00 | 24-SEP-10:20 |
October | 827.22 | 02-OCT-09:09 | 395.53 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.97 | 01-OCT-14:52 | 288.03 | 24-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 472.70 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 409.89 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 472.70 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 481.13 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 | |||||
Maximum of Months | 827.22 | 472.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 214.36 | 732.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 693.08 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18596.80 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 581.60 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 19212.33 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 580.87 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 635.19 | 21-MAR-16:10 | 16473.94 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 413.35 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4934.41 | 19-APR-16:10 | 12137.31 | 12-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 382.18 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7237.77 | 19-MAY-16:05 | 8258.40 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 356.16 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9706.53 | 02-JUN-16:03 | 4276.77 | 13-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 413.08 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9274.53 | 03-JUL-16:03 | 4075.23 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 410.78 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8531.01 | 07-AUG-16:03 | 4686.70 | 31-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 388.94 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6330.24 | 19-SEP-16:03 | 8994.25 | 25-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 632.23 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4233.56 | 04-OCT-16:05 | 10966.94 | 11-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 746.66 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15370.77 | 17-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 746.66 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18645.06 | 27-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 356.16 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4075.23 | |||||
Maximum of Months | 1306.65 | 746.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9706.53 | 19212.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 437.32 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 568.68 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 364.59 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 733.26 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 354.23 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 22-MAR-13:00 | 554.95 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 304.58 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.30 | 21-APR-15:00 | 594.81 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 252.33 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.21 | 14-MAY-15:50 | 261.78 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 238.83 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.31 | 04-JUN-18:53 | 213.43 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 263.95 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.32 | 02-JUL-21:10 | 121.56 | 04-JUL-19:10 |
August | 827.17 | 01-AUG-09:09 | 307.61 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.61 | 27-AUG-13:00 | 191.88 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 294.87 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.81 | 10-SEP-15:03 | 107.20 | 24-SEP-07:00 |
October | 827.17 | 02-OCT-09:09 | 405.18 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 | 01-OCT-14:52 | 294.09 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 472.67 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 377.28 | 26-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 472.67 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 486.25 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 238.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.20 | |||||
Maximum of Months | 827.17 | 472.67 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 212.32 | 733.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 698.41 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1295.11 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 615.52 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 20-FEB-15:33 | 1668.18 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 594.41 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 19-MAR-14:30 | 1239.08 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 415.54 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.77 | 01-APR-17:03 | 1357.81 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 382.60 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.32 | 14-MAY-15:55 | 611.21 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 356.16 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.96 | 10-JUN-17:02 | 478.59 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 412.88 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 505.43 | 02-JUL-21:00 | 236.89 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 411.05 | 17-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.49 | 26-AUG-17:30 | 412.37 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 463.46 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.30 | 10-SEP-15:00 | 233.97 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 640.74 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.49 | 01-OCT-14:52 | 627.26 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 746.66 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 801.23 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 746.66 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1036.72 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.97 | |||||
Maximum of Months | 1306.65 | 746.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 505.43 | 1668.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 442.59 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 862.90 | 25-JAN-23:00 |
February | 805.43 | 01-FEB-08:09 | 400.46 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1114.66 | 09-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 381.94 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 22-MAR-13:00 | 853.12 | 19-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 254.20 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.78 | 01-APR-17:03 | 906.46 | 10-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 247.48 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.38 | 14-MAY-15:55 | 404.73 | 04-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 225.48 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.91 | 10-JUN-17:02 | 318.68 | 28-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 256.48 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.66 | 02-JUL-21:00 | 158.46 | 18-JUL-21:10 |
August | 805.43 | 01-AUG-07:10 | 259.37 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.48 | 26-AUG-18:00 | 279.92 | 14-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 242.62 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.70 | 10-SEP-15:14 | 196.75 | 24-SEP-10:20 |
October | 805.43 | 02-OCT-07:10 | 397.91 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.82 | 01-OCT-14:52 | 423.37 | 23-OCT-21:10 |
November | 805.43 | 01-NOV-07:10 | 472.70 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 615.08 | 26-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 472.70 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 694.50 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.46 | |||||
Maximum of Months | 805.43 | 472.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 338.66 | 1114.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 695.08 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1318.01 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 587.84 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1707.39 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 587.04 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 22-MAR-13:00 | 1319.66 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 415.48 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.81 | 01-APR-17:03 | 1370.19 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 385.69 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.44 | 14-MAY-15:55 | 614.77 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 356.16 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.57 | 10-JUN-17:02 | 475.86 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 415.21 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.40 | 02-JUL-21:00 | 237.44 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 413.01 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.34 | 26-AUG-18:00 | 420.26 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 391.52 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.57 | 10-SEP-14:55 | 269.51 | 24-SEP-10:20 |
October | 1306.65 | 02-OCT-09:09 | 636.45 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.06 | 01-OCT-14:52 | 659.18 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 746.66 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 920.17 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 746.66 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1091.34 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 356.16 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.44 | |||||
Maximum of Months | 1306.65 | 746.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 507.40 | 1707.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 438.43 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 861.90 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 367.80 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1120.33 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 357.89 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 22-MAR-13:00 | 855.81 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 309.54 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.01 | 21-APR-15:00 | 909.66 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 253.86 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.93 | 14-MAY-16:00 | 414.20 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 240.80 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.87 | 04-JUN-18:53 | 329.38 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 265.08 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.90 | 02-JUL-20:57 | 206.03 | 04-JUL-18:55 |
August | 827.17 | 01-AUG-09:09 | 312.24 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.80 | 27-AUG-13:00 | 287.39 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 300.32 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 | 10-SEP-14:55 | 163.51 | 24-SEP-16:00 |
October | 827.17 | 02-OCT-09:09 | 407.18 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.35 | 01-OCT-15:05 | 436.35 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 472.67 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 542.55 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 472.67 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 700.69 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 240.80 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.51 | |||||
Maximum of Months | 827.17 | 472.67 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 333.90 | 1120.33 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1874.77 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2422.74 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 22-MAR-13:00 | 1849.35 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.47 | 01-APR-17:03 | 1944.02 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.92 | 14-MAY-15:52 | 862.95 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.59 | 04-JUN-19:00 | 649.27 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.53 | 02-JUL-20:53 | 323.17 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.55 | 26-AUG-17:02 | 546.27 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.37 | 10-SEP-14:53 | 327.47 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.58 | 01-OCT-14:52 | 899.83 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1185.20 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1568.84 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.17 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.53 | 2422.74 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2293.29 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3057.73 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 22-MAR-13:00 | 2289.65 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.23 | 01-APR-17:03 | 2478.11 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.48 | 14-MAY-16:00 | 1093.72 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.31 | 10-JUN-17:02 | 843.42 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.19 | 02-JUL-21:10 | 419.89 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.45 | 26-AUG-17:02 | 723.38 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.85 | 10-SEP-15:00 | 409.35 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.31 | 01-OCT-14:52 | 1132.67 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1415.14 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1873.71 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.19 | 3057.73 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2206.29 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2814.64 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2023.22 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.65 | 19-APR-21:03 | 2251.37 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.33 | 19-MAY-22:00 | 987.90 | 28-MAY-18:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.55 | 10-JUN-17:02 | 872.59 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.77 | 02-JUL-21:20 | 454.88 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.28 | 26-AUG-17:02 | 773.73 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.76 | 10-SEP-15:00 | 478.99 | 23-SEP-17:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.23 | 01-OCT-15:00 | 1132.71 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1335.38 | 26-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1646.63 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.88 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.77 | 2814.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13043.71 | 12-JAN-08:07 | 24140.03 | 14167.60 | 51033.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13980.47 | 09-FEB-08:04 | 42245.05 | 24793.30 | 89307.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14883.05 | 16-MAR-16:00 | 6035.01 | 3541.90 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27912.11 | 28-APR-06:02 | 6352.64 | 5903.17 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33732.83 | 31-MAY-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34194.26 | 09-JUN-05:03 | 2541.06 | 846.94 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34076.60 | 05-JUL-05:12 | 2541.06 | 1574.18 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33346.24 | 14-AUG-05:12 | 2541.06 | 1574.18 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33816.78 | 06-SEP-05:12 | 2541.06 | 1574.18 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31662.64 | 02-OCT-04:02 | 0.00 | 1967.72 | 17320.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30612.59 | 01-NOV-06:01 | 8893.70 | 8264.43 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13804.96 | 08-DEC-08:07 | 24140.03 | 14167.60 | 51033.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13043.71 | 0.00 | 846.94 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34194.26 | 42245.05 | 24793.30 | 89307.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2505.92 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 |
February | 4136.38 | 22-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5370.80 | 16-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.80 |
April | 8729.61 | 19-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 | 0.00 |
May | 10781.12 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.95 | 0.00 |
June | 11285.44 | 15-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.71 | 0.00 |
July | 11685.32 | 03-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.89 | 0.00 |
August | 11202.62 | 07-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.89 | 0.00 |
September | 9783.33 | 19-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 0.00 |
October | 8868.06 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 0.00 |
November | 4756.09 | 03-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 |
December | 1210.89 | 09-DEC-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1210.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11685.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.71 | 122.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1734.80 | 28-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.24 |
February | 1709.79 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.30 |
March | 1802.81 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.24 |
April | 3175.57 | 21-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 0.00 |
May | 5088.23 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.08 | 0.00 |
June | 5562.63 | 19-JUN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 | 0.00 |
July | 6079.61 | 03-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 0.00 |
August | 5677.15 | 07-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.24 | 0.00 |
September | 4767.75 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.44 |
October | 3793.18 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.66 | 0.00 |
November | 1823.03 | 10-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.21 |
December | 1623.99 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1623.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6079.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.02 | 320.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2066.72 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.35 |
February | 2253.08 | 16-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2201.83 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.30 |
April | 3089.61 | 21-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.51 | 0.00 |
May | 4754.31 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.69 | 0.00 |
June | 5524.35 | 05-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.35 | 0.00 |
July | 6347.38 | 03-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
August | 5067.24 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
September | 5511.04 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 |
October | 3818.24 | 02-OCT-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.71 | 0.00 |
November | 2374.32 | 10-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.94 |
December | 1970.80 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1970.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6347.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.51 | 193.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7854.40 | 13-JAN-17:00 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9760.03 | 22-FEB-17:00 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11460.96 | 16-MAR-16:00 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16075.15 | 17-APR-06:02 | 6352.64 | 5903.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28909.77 | 30-MAY-04:03 | 0.00 | 1574.18 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31593.65 | 19-JUN-05:14 | 3176.32 | 1967.72 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29166.00 | 05-JUL-05:12 | 2541.06 | 1574.18 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29043.57 | 14-AUG-05:12 | 2541.06 | 1574.18 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29909.00 | 05-SEP-05:12 | 3176.32 | 1967.72 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27440.42 | 02-OCT-04:02 | 0.00 | 1967.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12909.08 | 10-NOV-16:50 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6728.57 | 15-DEC-17:00 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6728.57 | 0.00 | 1574.18 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31593.65 | 6352.64 | 5903.17 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7267.82 | 12-JAN-16:40 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9506.78 | 22-FEB-15:30 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12681.74 | 16-MAR-16:00 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15882.17 | 28-APR-15:40 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32440.73 | 30-MAY-04:03 | 0.00 | 1574.18 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31297.49 | 05-JUN-05:12 | 2541.06 | 1574.18 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32101.27 | 10-JUL-04:03 | 0.00 | 1574.18 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31880.60 | 14-AUG-05:12 | 2541.06 | 1574.18 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32010.43 | 05-SEP-05:12 | 3176.32 | 1967.72 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31184.93 | 02-OCT-04:02 | 0.00 | 1967.72 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12779.29 | 10-NOV-15:00 | 6198.29 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5599.17 | 15-DEC-16:40 | 6035.01 | 3541.90 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5599.17 | 0.00 | 1574.18 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32440.73 | 6198.29 | 3541.90 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1178.49 | 12-JAN-14:30 | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
February | 1896.32 | 22-FEB-15:00 | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3105.54 | 22-MAR-14:30 | 1272.23 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
April | 5559.44 | 21-APR-15:00 | 1272.23 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 233.53 | 0.00 |
May | 10533.06 | 21-MAY-15:52 | 401.76 | 118.70 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 391.08 | 0.00 |
June | 12212.38 | 18-JUN-15:42 | 401.76 | 118.70 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 188.27 | 0.00 |
July | 12344.60 | 02-JUL-16:12 | 401.76 | 118.70 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 258.28 | 0.00 |
August | 12155.25 | 06-AUG-16:52 | 401.76 | 118.70 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 290.07 | 0.00 |
September | 6414.60 | 17-SEP-15:52 | 401.76 | 118.70 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 167.40 | 0.00 |
October | 7181.23 | 02-OCT-04:02 | 0.00 | 414.81 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 |
November | 2508.03 | 09-NOV-15:30 | 1272.23 | 390.58 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
December | 1039.26 | 08-DEC-15:10 | 2544.47 | 762.82 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1039.26 | 0.00 | 118.70 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12344.60 | 2544.47 | 762.82 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 391.08 | 43.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1243.25 | 04-JAN-10:10 | 1654.44 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.09 |
February | 2767.84 | 21-FEB-10:30 | 827.22 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 |
March | 4019.39 | 16-MAR-10:10 | 1610.86 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.45 |
April | 10502.60 | 30-APR-10:53 | 169.56 | 50.10 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10961.21 | 29-MAY-09:22 | 211.95 | 62.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 |
June | 11342.22 | 18-JUN-09:42 | 211.95 | 62.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 63.04 | 0.00 |
July | 11409.12 | 02-JUL-09:32 | 211.95 | 62.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11379.68 | 06-AUG-09:32 | 211.95 | 62.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 40.30 | 0.00 |
September | 10717.05 | 03-SEP-09:13 | 169.56 | 50.10 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 |
October | 8648.98 | 01-OCT-09:32 | 169.56 | 50.10 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4429.14 | 10-NOV-09:20 | 805.43 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.97 |
December | 738.31 | 01-DEC-10:40 | 827.22 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 738.31 | 169.56 | 50.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11409.12 | 1654.44 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 63.04 | 133.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8928.78 | 12-JAN-14:30 | 1306.65 | 356.16 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 |
February | 13951.84 | 20-FEB-14:23 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.74 |
March | 8418.90 | 16-MAR-13:30 | 1306.65 | 356.16 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 |
April | 13977.69 | 30-APR-13:32 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 32.99 | 0.00 |
May | 12267.67 | 21-MAY-15:12 | 401.76 | 118.70 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 308.75 | 0.00 |
June | 13425.73 | 18-JUN-15:42 | 401.76 | 118.70 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 189.58 | 0.00 |
July | 13947.26 | 30-JUL-12:53 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 69.65 | 0.00 |
August | 13893.14 | 13-AUG-13:23 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.91 | 0.00 |
September | 14220.42 | 03-SEP-11:53 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
October | 15366.63 | 01-OCT-12:12 | 401.76 | 118.70 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 32.80 | 0.00 |
November | 14176.90 | 11-NOV-12:32 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.82 |
December | 7044.26 | 07-DEC-14:10 | 1306.65 | 356.16 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7044.26 | 267.84 | 79.14 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15366.63 | 1306.65 | 356.16 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 308.75 | 285.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3396.84 | 12-JAN-15:30 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
February | 5914.44 | 19-FEB-16:33 | 127.16 | 37.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 |
March | 6007.51 | 21-MAR-16:00 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 | 0.00 |
April | 13323.49 | 30-APR-16:52 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 0.00 |
May | 13569.69 | 29-MAY-16:42 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 179.76 | 0.00 |
June | 13526.90 | 25-JUN-16:32 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 77.46 | 0.00 |
July | 13472.71 | 09-JUL-16:32 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 69.62 | 0.00 |
August | 13531.59 | 06-AUG-16:52 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 168.06 | 0.00 |
September | 13266.86 | 17-SEP-15:52 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 96.32 | 0.00 |
October | 13524.52 | 01-OCT-14:52 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 144.10 | 0.00 |
November | 5527.35 | 09-NOV-15:30 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
December | 2447.52 | 15-DEC-16:00 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2447.52 | 127.16 | 37.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13569.69 | 805.38 | 225.46 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 179.76 | 101.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1274.78 | 04-JAN-13:06 | 6361.16 | 1780.79 | 7176.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 |
February | 1340.60 | 20-FEB-15:02 | 267.84 | 79.14 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 0.00 |
March | 1284.99 | 22-MAR-14:30 | 1272.23 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 0.00 |
April | 3587.16 | 21-APR-15:20 | 1272.23 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 | 0.00 |
May | 4873.00 | 30-MAY-15:20 | 1272.23 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 0.00 |
June | 7488.13 | 19-JUN-06:03 | 803.52 | 356.16 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
July | 7799.78 | 03-JUL-06:03 | 803.52 | 356.16 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | 0.00 |
August | 7844.28 | 07-AUG-06:03 | 803.52 | 400.10 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 0.00 |
September | 7064.90 | 05-SEP-06:03 | 1071.35 | 753.64 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 |
October | 5151.05 | 02-OCT-06:03 | 803.52 | 746.66 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 |
November | 2147.21 | 09-NOV-16:00 | 1272.23 | 496.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
December | 1054.88 | 01-DEC-14:40 | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1054.88 | 267.84 | 79.14 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7844.28 | 6361.16 | 1780.79 | 7176.23 | 0.00 | 0.00 | 0.00 | 0.00 | 115.45 | 62.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1261.42 | 04-JAN-10:10 | 1654.44 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.51 |
February | 2313.12 | 21-FEB-10:30 | 827.22 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
March | 2837.02 | 31-MAR-09:40 | 827.22 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 |
April | 6677.82 | 30-APR-10:53 | 169.56 | 50.10 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7649.93 | 29-MAY-07:23 | 169.56 | 50.10 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.89 |
June | 8621.88 | 11-JUN-09:12 | 254.35 | 75.15 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
July | 10177.29 | 04-JUL-09:32 | 254.35 | 75.15 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 10083.91 | 27-AUG-09:52 | 254.35 | 75.15 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 0.00 |
September | 9894.12 | 04-SEP-10:22 | 211.95 | 62.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 |
October | 5705.75 | 02-OCT-04:02 | 0.00 | 262.61 | 1629.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 |
November | 4169.05 | 10-NOV-09:10 | 805.43 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.34 |
December | 1125.69 | 01-DEC-10:10 | 1654.44 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1125.69 | 0.00 | 50.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10177.29 | 1654.44 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 70.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8550.03 | 04-JAN-13:06 | 6361.16 | 1780.79 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1219.02 |
February | 11060.54 | 20-FEB-14:23 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.53 |
March | 5547.56 | 22-MAR-13:10 | 2613.31 | 712.32 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 89.58 | 0.00 |
April | 8929.70 | 19-APR-12:00 | 687.71 | 356.16 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4563.32 | 0.00 |
May | 9502.70 | 19-MAY-16:20 | 401.76 | 197.87 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6905.46 | 0.00 |
June | 10332.67 | 02-JUN-16:50 | 401.76 | 197.87 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8772.06 | 0.00 |
July | 10410.50 | 03-JUL-17:00 | 401.76 | 273.10 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8403.60 | 0.00 |
August | 11001.09 | 27-AUG-11:12 | 334.80 | 98.92 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 0.00 |
September | 11678.14 | 17-SEP-14:02 | 334.80 | 98.92 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 0.00 |
October | 11940.92 | 29-OCT-14:32 | 334.80 | 98.92 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 |
November | 11670.40 | 11-NOV-13:02 | 334.80 | 98.92 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.82 |
December | 6762.45 | 07-DEC-13:07 | 3816.70 | 1068.48 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5547.56 | 267.84 | 79.14 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11940.92 | 6361.16 | 1780.79 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8772.06 | 1219.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2383.60 | 30-JAN-16:30 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 |
February | 3584.70 | 21-FEB-16:50 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 |
March | 3694.29 | 21-MAR-16:00 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 |
April | 10491.12 | 16-APR-17:42 | 0.00 | 62.62 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 0.00 |
May | 10466.56 | 29-MAY-17:22 | 0.00 | 75.14 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 73.69 | 0.00 |
June | 10622.48 | 11-JUN-16:31 | 381.49 | 112.72 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 96.53 | 0.00 |
July | 10468.79 | 04-JUL-15:31 | 339.11 | 100.19 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 0.00 |
August | 11208.13 | 13-AUG-16:31 | 339.11 | 100.19 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 | 0.00 |
September | 10953.31 | 17-SEP-16:42 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 0.00 |
October | 10578.85 | 08-OCT-16:22 | 211.94 | 62.62 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.47 |
November | 4891.56 | 09-NOV-16:10 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 |
December | 2226.01 | 15-DEC-16:10 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2226.01 | 0.00 | 62.62 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11208.13 | 805.38 | 225.46 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 96.53 | 35.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1332.85 | 12-JAN-14:10 | 2613.31 | 712.32 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 |
February | 1987.49 | 23-FEB-14:30 | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 |
March | 2900.33 | 22-MAR-14:40 | 1272.23 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
April | 4953.54 | 21-APR-15:00 | 1272.23 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 195.01 | 0.00 |
May | 8237.66 | 30-MAY-06:03 | 803.52 | 356.16 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
June | 10611.12 | 18-JUN-16:11 | 468.72 | 138.49 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 173.12 | 0.00 |
July | 10330.22 | 02-JUL-16:12 | 401.76 | 118.70 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 219.78 | 0.00 |
August | 10173.32 | 13-AUG-16:31 | 535.68 | 158.27 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 85.36 | 0.00 |
September | 6437.78 | 10-SEP-15:51 | 468.72 | 138.49 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 | 0.00 |
October | 6814.89 | 02-OCT-04:02 | 0.00 | 414.81 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 |
November | 2466.25 | 09-NOV-16:00 | 1272.23 | 506.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
December | 1092.97 | 08-DEC-15:00 | 1306.65 | 356.16 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1092.97 | 0.00 | 118.70 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10611.12 | 2613.31 | 712.32 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 219.78 | 37.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3319.94 | 13-JAN-13:02 | 3221.71 | 901.91 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 |
February | 4606.93 | 08-FEB-13:02 | 4832.57 | 1352.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.99 |
March | 5256.78 | 16-MAR-10:05 | 1610.86 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.36 |
April | 11212.08 | 30-APR-09:22 | 211.95 | 62.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.20 |
May | 10697.44 | 29-MAY-09:02 | 211.95 | 62.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.22 |
June | 11507.27 | 04-JUN-09:02 | 254.35 | 75.15 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 |
July | 11652.34 | 04-JUL-08:52 | 254.35 | 75.15 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
August | 11412.41 | 20-AUG-09:12 | 254.35 | 75.15 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
September | 11563.30 | 04-SEP-08:32 | 254.35 | 75.15 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 |
October | 6834.64 | 05-OCT-10:05 | 1610.86 | 450.96 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 0.00 |
November | 4843.06 | 10-NOV-08:50 | 805.43 | 225.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.44 |
December | 2663.23 | 15-DEC-13:02 | 4832.57 | 1352.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2663.23 | 211.95 | 62.62 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11652.34 | 4832.57 | 1352.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 137.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8776.72 | 12-JAN-14:05 | 2613.31 | 712.32 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
February | 9141.27 | 19-FEB-14:43 | 200.88 | 59.35 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.58 |
March | 7973.93 | 16-MAR-13:05 | 2613.31 | 712.32 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
April | 10418.99 | 30-APR-15:21 | 468.72 | 138.49 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 0.00 |
May | 8315.22 | 21-MAY-12:53 | 200.88 | 59.35 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 260.01 | 0.00 |
June | 11842.97 | 18-JUN-16:11 | 468.72 | 138.49 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 174.94 | 0.00 |
July | 11982.82 | 30-JUL-12:53 | 267.84 | 79.14 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.32 | 0.00 |
August | 11937.95 | 27-AUG-11:12 | 334.80 | 98.92 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 179.67 | 0.00 |
September | 12721.51 | 04-SEP-12:32 | 334.80 | 98.92 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 0.00 |
October | 13316.57 | 29-OCT-13:22 | 401.76 | 118.70 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.03 |
November | 12802.02 | 11-NOV-13:02 | 334.80 | 98.92 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.22 |
December | 7454.86 | 07-DEC-13:40 | 2544.47 | 712.32 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7454.86 | 200.88 | 59.35 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13316.57 | 2613.31 | 712.32 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 260.01 | 276.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3387.72 | 12-JAN-15:30 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 |
February | 5521.86 | 19-FEB-16:43 | 127.16 | 37.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.64 |
March | 6007.79 | 26-MAR-15:53 | 127.16 | 37.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.56 |
April | 12163.97 | 30-APR-18:02 | 0.00 | 75.14 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 24.18 | 0.00 |
May | 12043.00 | 29-MAY-16:22 | 254.33 | 75.14 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 158.24 | 0.00 |
June | 12554.02 | 25-JUN-18:21 | 0.00 | 87.67 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 22.05 | 0.00 |
July | 12127.38 | 09-JUL-16:21 | 381.49 | 112.72 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 62.30 | 0.00 |
August | 12710.13 | 13-AUG-16:31 | 339.11 | 100.19 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 29.01 | 0.00 |
September | 12422.67 | 10-SEP-15:51 | 296.72 | 87.67 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 59.49 | 0.00 |
October | 11763.11 | 08-OCT-16:32 | 211.94 | 62.62 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 |
November | 5407.21 | 09-NOV-15:30 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
December | 2681.86 | 15-DEC-15:50 | 805.38 | 225.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2681.86 | 0.00 | 37.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12710.13 | 805.38 | 225.46 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 158.24 | 125.56 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.850755E+11 | 106529.90 | 17-JAN-07:10 | 0.206995E+11 | 58852.96 | 27-JAN-07:40 |
February | 0.758158E+11 | 98037.87 | 03-FEB-07:10 | 0.162326E+11 | 59290.96 | 03-FEB-07:19 |
March | 0.882132E+11 | 90499.96 | 02-MAR-07:10 | 0.150413E+11 | 52116.12 | 02-MAR-07:19 |
April | 0.943544E+11 | 114817.19 | 21-APR-15:09 | 0.105874E+11 | 29801.28 | 12-APR-06:10 |
May | 0.119801E+12 | 138426.71 | 30-MAY-14:39 | 0.103044E+11 | 9936.91 | 02-MAY-06:19 |
June | 0.140346E+12 | 145406.67 | 15-JUN-14:30 | 0.972909E+10 | 9538.05 | 01-JUN-11:39 |
July | 0.141926E+12 | 153461.64 | 20-JUL-15:09 | 0.950288E+10 | 9452.93 | 03-JUL-11:09 |
August | 0.140216E+12 | 140103.77 | 07-AUG-15:00 | 0.988702E+10 | 9455.52 | 31-AUG-11:09 |
September | 0.120582E+12 | 128521.89 | 05-SEP-15:30 | 0.949969E+10 | 9535.52 | 29-SEP-11:30 |
October | 0.997766E+11 | 117467.82 | 03-OCT-14:09 | 0.102747E+11 | 17832.91 | 25-OCT-06:49 |
November | 0.837630E+11 | 91770.69 | 28-NOV-07:10 | 0.140044E+11 | 41361.82 | 28-NOV-07:40 |
December | 0.856188E+11 | 123337.65 | 27-DEC-07:10 | 0.239034E+11 | 60988.56 | 27-DEC-07:19 |
Annual Sum or Average | 0.127549E+13 | 0.159666E+12 | ||||
Minimum of Months | 0.758158E+11 | 90499.96 | 0.949969E+10 | 9452.93 | ||
Maximum of Months | 0.141926E+12 | 153461.64 | 0.239034E+11 | 60988.56 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.101061E+11 | 19332.77 | 27-JAN-12:30 | 0.00 | 0.00 |
February | 0.114575E+11 | 22703.37 | 24-FEB-11:39 | 0.00 | 0.00 |
March | 0.170449E+11 | 26600.30 | 29-MAR-12:20 | 0.00 | 0.00 |
April | 0.196317E+11 | 26813.75 | 22-APR-11:39 | 0.00 | 0.00 |
May | 0.217403E+11 | 26813.75 | 05-MAY-12:30 | 0.00 | 0.00 |
June | 0.215527E+11 | 26028.55 | 10-JUN-11:00 | 0.00 | 0.00 |
July | 0.194272E+11 | 24940.68 | 22-JUL-11:00 | 0.00 | 0.00 |
August | 0.182215E+11 | 24463.84 | 09-AUG-12:30 | 0.00 | 0.00 |
September | 0.164546E+11 | 24544.87 | 09-SEP-12:30 | 0.00 | 0.00 |
October | 0.134651E+11 | 22200.77 | 05-OCT-11:30 | 0.00 | 0.00 |
November | 0.107912E+11 | 19702.32 | 05-NOV-11:39 | 0.00 | 0.00 |
December | 0.951236E+10 | 17163.80 | 29-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189405E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.951236E+10 | 17163.80 | 0.00 | 0.00 | |
Maximum of Months | 0.217403E+11 | 26813.75 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.143999E+11 | 0.360720E+10 | 0.545046E+11 | 0.976761E+09 | 0.371871E+10 | 12379742.02 | 0.735913E+10 | 0.496815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129454E+11 | 0.297607E+10 | 0.493409E+11 | 0.883928E+09 | 0.369018E+10 | 11196021.66 | 0.390674E+10 | 0.206144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151531E+11 | 0.290792E+10 | 0.567112E+11 | 0.102267E+10 | 0.494559E+10 | 12675672.10 | 0.227137E+10 | 0.518870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134309E+11 | 0.246562E+10 | 0.526212E+11 | 0.940640E+09 | 0.778956E+10 | 11960507.72 | 0.308930E+09 | 0.167856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144349E+11 | 0.225811E+10 | 0.556079E+11 | 0.999506E+09 | 0.128554E+11 | 12527707.06 | 27541395.10 | 0.336050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143194E+11 | 0.205614E+10 | 0.546110E+11 | 0.983843E+09 | 0.174604E+11 | 12231776.97 | 0.00 | 0.509034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134454E+11 | 0.220168E+10 | 0.536070E+11 | 0.956144E+09 | 0.167228E+11 | 12256437.81 | 0.00 | 0.549811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150231E+11 | 0.243377E+10 | 0.567112E+11 | 0.102261E+10 | 0.163806E+11 | 12675672.10 | 0.00 | 0.486319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134853E+11 | 0.264008E+10 | 0.525990E+11 | 0.940432E+09 | 0.127760E+11 | 11960507.72 | 3660636.19 | 0.381256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141645E+11 | 0.312987E+10 | 0.545158E+11 | 0.976694E+09 | 0.851753E+10 | 12379742.02 | 0.111723E+09 | 0.183482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141982E+11 | 0.338076E+10 | 0.533244E+11 | 0.958583E+09 | 0.498913E+10 | 12059151.09 | 0.249163E+10 | 0.440824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140210E+11 | 0.369441E+10 | 0.535958E+11 | 0.956435E+09 | 0.364352E+10 | 12256437.81 | 0.950958E+10 | 0.185824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169021E+12 | 0.337516E+11 | 0.647750E+12 | 0.116182E+11 | 0.113489E+12 | 0.146559E+09 | 0.259903E+11 | 0.273722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129454E+11 | 0.205614E+10 | 0.493409E+11 | 0.883928E+09 | 0.364352E+10 | 11196021.66 | 0.00 | 0.185824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151531E+11 | 0.369441E+10 | 0.567112E+11 | 0.102267E+10 | 0.174604E+11 | 12675672.10 | 0.950958E+10 | 0.549811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.964575E+10 | 0.00 | 0.110537E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.622919E+10 | 0.00 | 0.100035E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.381356E+10 | 0.00 | 0.112278E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.413236E+09 | 0.00 | 0.101742E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3310160.03 | 0.00 | 0.103011E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.972909E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.950288E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.988702E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 6050580.66 | 0.00 | 0.949364E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136710E+09 | 0.00 | 0.101380E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.375072E+10 | 0.00 | 0.102537E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.131689E+11 | 0.00 | 0.107345E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.371674E+11 | 0.00 | 0.122499E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.949364E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.131689E+11 | 0.00 | 0.112278E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17443.37 | 17-JAN-16:00 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 828.12 | 17-JAN-16:00 | 5125.54 | 12-JAN-15:39 | 6.85 | 02-JAN-06:10 | 74999.95 | 17-JAN-07:10 |
February | 16420.21 | 23-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 827.73 | 13-FEB-08:20 | 6885.45 | 21-FEB-16:30 | 6.85 | 01-FEB-06:10 | 70427.37 | 03-FEB-07:10 |
March | 16371.17 | 10-MAR-16:00 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 826.97 | 22-MAR-07:19 | 10394.13 | 16-MAR-15:30 | 6.85 | 01-MAR-08:09 | 63675.36 | 02-MAR-07:10 |
April | 14799.06 | 20-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 826.00 | 20-APR-07:19 | 18461.92 | 21-APR-14:39 | 6.85 | 15-APR-16:10 | 18443.38 | 11-APR-06:10 |
May | 14328.88 | 03-MAY-07:10 | 3824.74 | 01-MAY-05:10 | 40437.79 | 01-MAY-07:10 | 825.38 | 03-MAY-07:19 | 28227.74 | 30-MAY-14:39 | 6.85 | 14-MAY-15:50 | 5318.14 | 02-MAY-06:10 |
June | 14159.52 | 29-JUN-07:10 | 2323.70 | 01-JUN-19:10 | 40437.79 | 01-JUN-07:10 | 825.16 | 29-JUN-07:19 | 29057.81 | 19-JUN-14:30 | 6.85 | 04-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 14663.22 | 07-JUL-07:30 | 3824.74 | 06-JUL-05:10 | 40437.79 | 03-JUL-07:10 | 825.82 | 07-JUL-07:40 | 33167.10 | 20-JUL-15:09 | 6.85 | 01-JUL-16:10 | 0.00 | 01-JUL-00:10 |
August | 14688.06 | 17-AUG-07:10 | 3824.74 | 01-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 825.85 | 17-AUG-07:19 | 25207.02 | 21-AUG-15:00 | 6.85 | 06-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 14593.27 | 29-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 825.73 | 29-SEP-07:19 | 21033.09 | 05-SEP-15:30 | 6.85 | 17-SEP-15:50 | 1369.96 | 25-SEP-06:10 |
October | 16859.98 | 13-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 828.71 | 13-OCT-07:19 | 16865.33 | 03-OCT-15:39 | 6.85 | 01-OCT-05:10 | 11324.17 | 25-OCT-06:10 |
November | 17941.79 | 22-NOV-16:00 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 828.82 | 28-NOV-16:00 | 10681.72 | 09-NOV-16:10 | 6.85 | 28-NOV-08:09 | 65176.90 | 28-NOV-07:10 |
December | 17941.79 | 01-DEC-16:00 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 828.87 | 11-DEC-16:00 | 3947.59 | 07-DEC-15:09 | 6.85 | 04-DEC-12:09 | 95331.58 | 27-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14159.52 | 2323.70 | 40437.79 | 825.16 | 3947.59 | 6.85 | 0.00 | |||||||
Maximum of Months | 17941.79 | 3824.74 | 40437.79 | 828.87 | 33167.10 | 6.85 | 95331.58 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 8348.89 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 15757.32 | 21-FEB-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 19872.29 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 43271.92 | 21-APR-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57574.73 | 30-MAY-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 66698.29 | 15-JUN-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 69302.45 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 65695.65 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 54088.03 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 52605.93 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 21344.48 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 4111.65 | 20-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4111.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 69302.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 106529.90 | 17-JAN-07:10 | 5980.60 | 18346.02 | 3824.74 | 243.24 | 3128.49 | 6.85 | 74999.95 | 0.00 | 0.00 |
February | 98037.87 | 03-FEB-07:10 | 5980.60 | 18346.02 | 0.00 | 243.24 | 3033.78 | 6.85 | 70427.37 | 0.00 | 0.00 |
March | 90499.96 | 02-MAR-07:10 | 5254.84 | 18346.02 | 0.00 | 243.16 | 2973.72 | 6.85 | 63675.36 | 0.00 | 0.00 |
April | 114817.19 | 21-APR-15:09 | 14115.48 | 38454.47 | 0.00 | 823.97 | 18455.09 | 6.85 | 0.00 | 42961.33 | 0.00 |
May | 138426.71 | 30-MAY-14:39 | 14115.48 | 37678.39 | 0.00 | 823.52 | 28227.74 | 6.85 | 0.00 | 57574.73 | 0.00 |
June | 145406.67 | 15-JUN-14:30 | 14115.48 | 37678.39 | 0.00 | 823.52 | 26375.85 | 6.85 | 0.00 | 66406.58 | 0.00 |
July | 153461.64 | 20-JUL-15:09 | 14115.48 | 38454.47 | 0.00 | 823.97 | 33167.10 | 6.85 | 0.00 | 66893.77 | 0.00 |
August | 140103.77 | 07-AUG-15:00 | 14115.48 | 38454.47 | 0.00 | 823.97 | 21007.35 | 6.85 | 0.00 | 65695.65 | 0.00 |
September | 128521.89 | 05-SEP-15:30 | 14115.48 | 38454.47 | 0.00 | 823.97 | 21033.09 | 6.85 | 0.00 | 54088.03 | 0.00 |
October | 117467.82 | 03-OCT-14:09 | 14115.48 | 37678.39 | 0.00 | 823.52 | 12272.62 | 6.85 | 0.00 | 52570.96 | 0.00 |
November | 91770.69 | 28-NOV-07:10 | 4943.80 | 18346.02 | 0.00 | 243.11 | 3054.01 | 6.85 | 65176.90 | 0.00 | 0.00 |
December | 123337.65 | 27-DEC-07:10 | 5980.60 | 18346.02 | 0.00 | 243.24 | 3429.36 | 6.85 | 95331.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 90499.96 | 4943.80 | 18346.02 | 0.00 | 243.11 | 2973.72 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 153461.64 | 14115.48 | 38454.47 | 3824.74 | 823.97 | 33167.10 | 6.85 | 95331.58 | 66893.77 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 50451.39 | 27-JAN-07:19 | 0.00 | 9950.60 | 27-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 51330.25 | 03-FEB-07:19 | 0.00 | 9945.40 | 08-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 43276.25 | 02-MAR-07:19 | 0.00 | 9915.12 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 21006.22 | 12-APR-06:10 | 0.00 | 9789.45 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 1980.90 | 02-MAY-06:10 | 0.00 | 9667.96 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9538.05 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9452.93 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9455.52 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 3962.07 | 30-SEP-06:10 | 0.00 | 9535.52 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 10716.38 | 25-OCT-06:10 | 0.00 | 9668.95 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 34991.20 | 28-NOV-07:19 | 0.00 | 9803.97 | 28-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 53012.66 | 27-DEC-07:30 | 0.00 | 9908.90 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9452.93 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 53012.66 | 0.00 | 9950.60 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.24 | 0.00 | 26.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.23 | 0.00 | 26.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.28 | 0.00 | 26.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 26.25 | 0.00 | 26.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.28 | 0.00 | 26.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.60 | 0.33 | 24.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.60 | 0.33 | 24.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.60 | 0.33 | 24.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.88 | 0.17 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
February | 0.33 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.44 | 3.33 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.54 | 4.50 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.46 | 7.17 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.51 | 4.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.28 | 0.83 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.26 | 0.17 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
December | 0.83 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
Annual Sum or Average | 2.00 | 17.47 | 0.33 | 17.73 | 30.33 | 26.79 | 20.17 | 27.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 18.26 | 0.17 | 18.62 | 11.67 | 27.54 | 7.17 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
February | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.61 | 4.67 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.81 | 11.00 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.91 | 10.50 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.86 | 15.83 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.92 | 10.00 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.71 | 9.33 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.40 | 2.33 | 27.40 |
November | 0.17 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
December | 1.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
Annual Sum or Average | 1.50 | 17.06 | 0.00 | 17.06 | 75.50 | 27.61 | 63.67 | 27.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 17.20 | 0.00 | 17.20 | 20.17 | 27.92 | 15.83 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 2.17 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.52 | 4.00 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.57 | 5.33 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.55 | 5.33 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.56 | 9.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.78 | 6.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.87 | 7.33 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.99 | 7.33 | 28.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.55 | 4.67 | 27.55 |
December | 0.50 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
Annual Sum or Average | 0.50 | 17.00 | 0.00 | 17.00 | 61.83 | 27.60 | 51.83 | 27.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.00 | 0.00 | 17.00 | 12.50 | 27.99 | 9.00 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.41 | 0.83 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.00 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.10 | 4.33 | 28.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.30 | 5.50 | 28.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.27 | 5.33 | 28.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 28.11 | 7.83 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.21 | 5.67 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.13 | 5.17 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.92 | 3.83 | 27.92 |
November | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
December | 0.67 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
Annual Sum or Average | 1.00 | 17.05 | 0.00 | 17.05 | 66.83 | 27.99 | 39.50 | 28.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 0.00 | 16.97 |
Maximum of Months | 0.67 | 17.21 | 0.00 | 17.21 | 16.00 | 28.30 | 7.83 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.49 | 1.50 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.53 | 5.67 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.59 | 7.83 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.61 | 11.67 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.60 | 9.83 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.55 | 9.17 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.44 | 1.17 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 48.67 | 27.58 | 46.83 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.61 | 11.67 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.00 | 19.04 | 19.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
February | 11.67 | 18.73 | 11.67 | 18.73 | 0.83 | 19.03 | 0.83 | 19.31 |
March | 11.83 | 19.22 | 11.83 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 2.83 | 20.01 | 2.83 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.64 | 1.33 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 25.06 | 21.50 | 25.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 25.06 | 18.00 | 25.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 25.53 | 20.50 | 25.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 25.84 | 21.50 | 25.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 26.15 | 16.50 | 26.14 |
November | 4.50 | 19.52 | 4.50 | 19.52 | 6.33 | 22.84 | 6.33 | 24.22 |
December | 18.67 | 18.71 | 18.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
Annual Sum or Average | 68.50 | 19.00 | 68.50 | 19.00 | 107.50 | 21.92 | 106.50 | 23.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 0.00 | 18.71 |
Maximum of Months | 19.00 | 20.01 | 19.00 | 20.01 | 21.83 | 26.15 | 21.50 | 26.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.73 | 2.33 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.82 | 4.67 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.92 | 3.83 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.75 | 6.33 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.96 | 4.33 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.81 | 5.00 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.69 | 3.33 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.67 | 27.82 | 29.83 | 27.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.96 | 6.33 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.35 | 2.00 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.34 | 1.67 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.33 | 1.33 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.00 | 27.34 | 5.33 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.35 | 2.00 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.67 | 4.33 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.69 | 11.33 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.77 | 10.67 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.71 | 15.67 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.77 | 10.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.63 | 9.00 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.50 | 2.00 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 67.17 | 27.71 | 63.00 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.77 | 15.67 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.47 | 3.00 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.45 | 2.17 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.36 | 4.00 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.38 | 3.00 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.40 | 6.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.55 | 6.33 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 7.33 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.84 | 7.83 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.64 | 6.00 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 48.67 | 27.58 | 46.17 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.84 | 7.83 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.46 | 1.00 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.97 | 4.17 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.12 | 5.33 | 28.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.14 | 5.00 | 28.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.95 | 6.83 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.12 | 4.83 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.98 | 4.67 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.78 | 3.67 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 58.17 | 28.00 | 36.33 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 28.14 | 6.83 | 28.22 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.67 | 23.77 | 0.00 | 23.77 | 0.00 | 23.77 |
February | 430.33 | 23.92 | 0.00 | 23.92 | 0.00 | 23.92 |
March | 439.17 | 23.98 | 1.83 | 23.99 | 0.00 | 23.99 |
April | 179.17 | 24.02 | 27.17 | 24.20 | 0.00 | 24.20 |
May | 28.00 | 24.00 | 177.83 | 24.58 | 0.00 | 24.58 |
June | 1.00 | 24.00 | 317.83 | 24.46 | 0.00 | 24.46 |
July | 24.17 | 24.28 | 492.33 | 24.38 | 24.17 | 24.37 |
August | 1.33 | 24.00 | 494.50 | 24.35 | 1.33 | 24.35 |
September | 6.67 | 25.40 | 420.17 | 24.45 | 6.67 | 24.46 |
October | 17.00 | 24.00 | 260.17 | 24.52 | 0.00 | 24.52 |
November | 275.17 | 23.98 | 34.50 | 24.07 | 0.00 | 24.07 |
December | 494.83 | 23.78 | 0.00 | 23.78 | 0.00 | 23.78 |
Annual Sum or Average | 2394.50 | 23.90 | 2226.33 | 24.17 | 32.17 | 24.17 |
Minimum of Months | 1.00 | 23.77 | 0.00 | 23.77 | 0.00 | 23.77 |
Maximum of Months | 497.67 | 25.40 | 494.50 | 24.58 | 24.17 | 24.58 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
February | 453.33 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
March | 507.83 | 23.62 | 0.00 | 23.62 | 0.00 | 23.62 |
April | 268.50 | 23.94 | 13.50 | 24.01 | 0.00 | 24.01 |
May | 63.17 | 24.00 | 162.67 | 24.40 | 0.00 | 24.40 |
June | 3.50 | 24.00 | 308.00 | 24.44 | 0.00 | 24.44 |
July | 32.33 | 24.19 | 493.00 | 24.34 | 32.33 | 24.33 |
August | 4.67 | 24.00 | 485.00 | 24.31 | 4.67 | 24.31 |
September | 14.17 | 24.49 | 393.00 | 24.37 | 10.67 | 24.38 |
October | 97.00 | 23.80 | 182.33 | 24.14 | 1.83 | 24.14 |
November | 409.33 | 23.47 | 6.33 | 23.48 | 0.00 | 23.48 |
December | 497.00 | 22.66 | 5.67 | 22.64 | 5.67 | 22.62 |
Annual Sum or Average | 2852.83 | 23.28 | 2049.50 | 23.73 | 55.17 | 23.74 |
Minimum of Months | 3.50 | 22.66 | 0.00 | 22.64 | 0.00 | 22.62 |
Maximum of Months | 507.83 | 24.49 | 493.00 | 24.44 | 32.33 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.89 | 101.00 | 21.67 | 101.00 | 21.50 |
February | 454.00 | 22.49 | 46.67 | 22.34 | 46.67 | 22.21 |
March | 514.00 | 23.15 | 7.00 | 23.12 | 7.00 | 23.09 |
April | 290.17 | 23.76 | 17.00 | 23.81 | 0.00 | 23.81 |
May | 86.17 | 23.89 | 172.00 | 24.34 | 0.00 | 24.34 |
June | 5.33 | 24.00 | 326.17 | 24.45 | 0.00 | 24.45 |
July | 31.33 | 24.10 | 493.00 | 24.39 | 31.33 | 24.37 |
August | 4.33 | 24.00 | 479.17 | 24.33 | 4.33 | 24.32 |
September | 33.17 | 23.91 | 373.83 | 24.30 | 11.83 | 24.30 |
October | 215.17 | 23.56 | 132.50 | 23.80 | 1.50 | 23.80 |
November | 446.83 | 22.73 | 23.17 | 22.64 | 23.17 | 22.55 |
December | 497.00 | 21.65 | 156.00 | 21.39 | 156.00 | 21.24 |
Annual Sum or Average | 3079.50 | 22.67 | 2327.50 | 23.18 | 382.83 | 23.04 |
Minimum of Months | 4.33 | 21.65 | 7.00 | 21.39 | 0.00 | 21.24 |
Maximum of Months | 514.00 | 24.10 | 493.00 | 24.45 | 156.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.84 | 293.00 | 20.62 | 293.00 | 20.53 |
February | 454.00 | 21.47 | 178.67 | 21.19 | 178.67 | 21.03 |
March | 514.00 | 22.29 | 106.67 | 22.00 | 106.67 | 21.79 |
April | 298.33 | 23.21 | 51.50 | 23.30 | 10.67 | 23.23 |
May | 111.50 | 23.83 | 213.33 | 24.35 | 6.50 | 24.40 |
June | 18.00 | 25.90 | 395.67 | 24.59 | 11.17 | 24.65 |
July | 92.17 | 25.30 | 496.50 | 24.67 | 92.17 | 24.75 |
August | 36.33 | 24.88 | 478.17 | 24.43 | 28.50 | 24.48 |
September | 94.83 | 23.90 | 351.17 | 24.25 | 38.83 | 24.29 |
October | 298.33 | 22.92 | 118.33 | 23.29 | 9.33 | 23.30 |
November | 468.17 | 21.67 | 135.00 | 21.37 | 135.00 | 21.17 |
December | 497.00 | 20.63 | 346.33 | 20.47 | 346.33 | 20.40 |
Annual Sum or Average | 3384.67 | 22.00 | 3164.33 | 22.51 | 1256.83 | 22.28 |
Minimum of Months | 18.00 | 20.63 | 51.50 | 20.47 | 6.50 | 20.40 |
Maximum of Months | 514.00 | 25.90 | 496.50 | 24.67 | 346.33 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.44 | 180.67 | 21.08 | 180.67 | 20.88 |
February | 436.17 | 22.21 | 95.17 | 21.88 | 93.83 | 21.64 |
March | 413.00 | 22.73 | 62.33 | 22.50 | 56.83 | 22.28 |
April | 168.83 | 23.48 | 136.50 | 24.10 | 10.83 | 24.11 |
May | 78.67 | 24.99 | 322.17 | 24.71 | 30.50 | 24.87 |
June | 40.00 | 26.84 | 445.33 | 24.75 | 37.00 | 24.91 |
July | 118.83 | 25.85 | 497.00 | 24.88 | 118.83 | 25.03 |
August | 59.83 | 26.00 | 494.33 | 24.63 | 56.67 | 24.77 |
September | 88.67 | 25.30 | 407.50 | 24.62 | 61.67 | 24.79 |
October | 200.00 | 22.95 | 193.50 | 23.74 | 9.83 | 23.75 |
November | 438.83 | 22.32 | 88.00 | 22.06 | 75.50 | 21.83 |
December | 497.00 | 21.19 | 233.33 | 20.86 | 233.33 | 20.70 |
Annual Sum or Average | 3041.83 | 22.56 | 3155.83 | 23.13 | 965.50 | 23.01 |
Minimum of Months | 40.00 | 21.19 | 62.33 | 20.86 | 9.83 | 20.70 |
Maximum of Months | 502.00 | 26.84 | 497.00 | 24.88 | 233.33 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 383.50 | 21.73 | 160.50 | 21.50 | 134.50 | 21.23 |
February | 324.67 | 22.06 | 112.17 | 22.01 | 84.33 | 21.75 |
March | 348.67 | 22.49 | 93.00 | 22.40 | 69.00 | 22.15 |
April | 224.83 | 23.23 | 109.83 | 23.67 | 14.83 | 23.63 |
May | 117.67 | 23.93 | 233.67 | 24.38 | 13.00 | 24.47 |
June | 27.83 | 25.52 | 388.17 | 24.58 | 13.67 | 24.66 |
July | 96.83 | 25.36 | 495.50 | 24.67 | 96.83 | 24.77 |
August | 51.17 | 25.46 | 480.67 | 24.53 | 42.33 | 24.62 |
September | 91.17 | 24.82 | 393.17 | 24.53 | 58.00 | 24.67 |
October | 199.00 | 23.54 | 263.83 | 24.13 | 33.50 | 24.29 |
November | 298.50 | 22.14 | 152.17 | 22.43 | 69.33 | 22.18 |
December | 392.83 | 21.68 | 166.00 | 21.35 | 155.00 | 21.10 |
Annual Sum or Average | 2556.67 | 22.65 | 3048.67 | 23.31 | 784.33 | 23.17 |
Minimum of Months | 27.83 | 21.68 | 93.00 | 21.35 | 13.00 | 21.10 |
Maximum of Months | 392.83 | 25.52 | 495.50 | 24.67 | 155.00 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.83 | 21.30 | 227.67 | 20.95 | 227.67 | 20.77 |
February | 414.00 | 21.75 | 152.67 | 21.49 | 144.33 | 21.28 |
March | 405.67 | 22.30 | 113.00 | 22.13 | 93.00 | 21.90 |
April | 238.67 | 23.30 | 120.00 | 23.70 | 20.17 | 23.71 |
May | 122.17 | 24.33 | 282.33 | 24.53 | 25.67 | 24.68 |
June | 33.33 | 26.26 | 411.50 | 24.68 | 24.00 | 24.81 |
July | 103.50 | 25.48 | 496.17 | 24.75 | 103.50 | 24.86 |
August | 53.67 | 25.50 | 486.17 | 24.56 | 47.17 | 24.66 |
September | 91.83 | 24.56 | 387.17 | 24.46 | 58.67 | 24.56 |
October | 241.17 | 23.16 | 201.83 | 23.76 | 21.67 | 23.85 |
November | 394.00 | 21.83 | 134.50 | 21.66 | 108.00 | 21.43 |
December | 493.67 | 21.18 | 269.83 | 20.84 | 269.83 | 20.67 |
Annual Sum or Average | 3074.50 | 22.33 | 3282.83 | 22.91 | 1143.67 | 22.73 |
Minimum of Months | 33.33 | 21.18 | 113.00 | 20.84 | 20.17 | 20.67 |
Maximum of Months | 493.67 | 26.26 | 496.17 | 24.75 | 269.83 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.18 | 189.83 | 21.04 | 189.83 | 20.95 |
February | 454.00 | 21.46 | 157.83 | 21.27 | 157.83 | 21.15 |
March | 514.00 | 21.99 | 84.67 | 21.81 | 84.67 | 21.67 |
April | 417.00 | 23.30 | 6.17 | 23.27 | 5.33 | 23.24 |
May | 159.17 | 23.76 | 141.50 | 24.07 | 0.00 | 24.07 |
June | 9.17 | 24.04 | 328.00 | 24.43 | 0.00 | 24.43 |
July | 50.50 | 24.47 | 495.00 | 24.46 | 50.50 | 24.46 |
August | 12.00 | 24.22 | 496.33 | 24.36 | 12.00 | 24.36 |
September | 37.83 | 24.15 | 390.17 | 24.34 | 20.00 | 24.35 |
October | 224.00 | 23.60 | 143.33 | 23.83 | 5.00 | 23.83 |
November | 458.50 | 22.47 | 18.33 | 22.41 | 18.33 | 22.34 |
December | 497.00 | 21.23 | 208.33 | 21.06 | 208.33 | 20.97 |
Annual Sum or Average | 3335.17 | 22.18 | 2659.50 | 22.75 | 751.83 | 22.57 |
Minimum of Months | 9.17 | 21.18 | 6.17 | 21.04 | 0.00 | 20.95 |
Maximum of Months | 514.00 | 24.47 | 496.33 | 24.46 | 208.33 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.00 | 80.00 | 21.80 | 80.00 | 21.65 |
February | 443.00 | 22.49 | 48.00 | 22.31 | 48.00 | 22.16 |
March | 480.17 | 22.95 | 32.67 | 22.82 | 30.83 | 22.70 |
April | 204.67 | 23.65 | 90.17 | 24.15 | 0.83 | 24.16 |
May | 57.00 | 24.48 | 273.67 | 24.65 | 10.67 | 24.72 |
June | 17.67 | 26.93 | 428.00 | 24.63 | 16.67 | 24.72 |
July | 90.83 | 25.80 | 497.00 | 24.81 | 90.83 | 24.94 |
August | 37.67 | 26.29 | 509.67 | 24.61 | 37.67 | 24.72 |
September | 53.67 | 26.23 | 441.67 | 24.72 | 49.00 | 24.88 |
October | 100.50 | 23.72 | 243.83 | 24.30 | 3.67 | 24.31 |
November | 376.00 | 23.09 | 27.83 | 23.16 | 5.33 | 23.12 |
December | 497.00 | 22.07 | 84.00 | 21.86 | 84.00 | 21.70 |
Annual Sum or Average | 2860.17 | 22.91 | 2756.50 | 23.56 | 457.50 | 23.53 |
Minimum of Months | 17.67 | 22.00 | 27.83 | 21.80 | 0.83 | 21.65 |
Maximum of Months | 502.00 | 26.93 | 509.67 | 24.81 | 90.83 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 390.33 | 22.11 | 66.50 | 22.12 | 40.67 | 21.92 |
February | 365.83 | 22.30 | 53.33 | 22.40 | 27.33 | 22.23 |
March | 436.67 | 22.55 | 50.33 | 22.52 | 32.50 | 22.37 |
April | 302.67 | 23.17 | 57.17 | 23.43 | 5.33 | 23.39 |
May | 154.67 | 23.44 | 145.67 | 23.99 | 0.00 | 23.99 |
June | 25.83 | 23.52 | 311.33 | 24.45 | 1.83 | 24.44 |
July | 87.17 | 24.30 | 494.50 | 24.47 | 87.17 | 24.44 |
August | 41.33 | 24.42 | 497.83 | 24.45 | 38.33 | 24.45 |
September | 72.33 | 25.09 | 435.00 | 24.66 | 57.50 | 24.77 |
October | 95.67 | 24.07 | 313.00 | 24.52 | 33.33 | 24.67 |
November | 240.50 | 22.74 | 116.50 | 23.41 | 10.50 | 23.37 |
December | 386.00 | 22.14 | 63.33 | 22.07 | 46.17 | 21.85 |
Annual Sum or Average | 2599.00 | 22.76 | 2604.50 | 23.55 | 380.67 | 23.51 |
Minimum of Months | 25.83 | 22.11 | 50.33 | 22.07 | 0.00 | 21.85 |
Maximum of Months | 436.67 | 25.09 | 497.83 | 24.66 | 87.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.17 | 21.89 | 96.50 | 21.69 | 96.50 | 21.54 |
February | 442.17 | 22.15 | 76.50 | 21.98 | 72.83 | 21.82 |
March | 458.17 | 22.63 | 42.00 | 22.56 | 34.33 | 22.45 |
April | 263.17 | 23.54 | 78.00 | 23.87 | 2.00 | 23.90 |
May | 100.33 | 24.18 | 256.00 | 24.49 | 10.00 | 24.56 |
June | 16.50 | 26.47 | 398.33 | 24.60 | 13.33 | 24.68 |
July | 78.67 | 25.43 | 496.33 | 24.70 | 78.67 | 24.78 |
August | 34.33 | 25.90 | 509.33 | 24.57 | 34.33 | 24.65 |
September | 44.67 | 25.63 | 435.00 | 24.63 | 39.00 | 24.73 |
October | 88.67 | 24.04 | 245.83 | 24.38 | 12.83 | 24.44 |
November | 359.00 | 22.92 | 41.83 | 23.05 | 6.00 | 23.01 |
December | 496.50 | 21.93 | 109.83 | 21.70 | 109.83 | 21.54 |
Annual Sum or Average | 2876.33 | 22.71 | 2785.50 | 23.40 | 509.67 | 23.34 |
Minimum of Months | 16.50 | 21.89 | 41.83 | 21.69 | 2.00 | 21.54 |
Maximum of Months | 496.50 | 26.47 | 509.33 | 24.70 | 109.83 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.28 | 179.50 | 21.09 | 179.50 | 20.98 |
February | 454.00 | 21.91 | 95.33 | 21.69 | 95.33 | 21.54 |
March | 514.00 | 22.68 | 44.67 | 22.53 | 44.67 | 22.40 |
April | 292.50 | 23.53 | 28.17 | 23.63 | 0.00 | 23.63 |
May | 87.17 | 23.88 | 204.50 | 24.40 | 0.17 | 24.40 |
June | 3.83 | 26.16 | 378.33 | 24.57 | 2.50 | 24.58 |
July | 70.50 | 24.93 | 496.67 | 24.59 | 70.50 | 24.62 |
August | 18.33 | 24.46 | 490.00 | 24.40 | 18.33 | 24.40 |
September | 54.67 | 23.96 | 379.50 | 24.29 | 28.50 | 24.30 |
October | 259.83 | 23.37 | 129.17 | 23.64 | 7.83 | 23.65 |
November | 460.17 | 22.26 | 54.50 | 22.08 | 54.50 | 21.94 |
December | 497.00 | 21.13 | 243.00 | 20.93 | 243.00 | 20.83 |
Annual Sum or Average | 3214.00 | 22.30 | 2723.33 | 22.89 | 744.83 | 22.71 |
Minimum of Months | 3.83 | 21.13 | 28.17 | 20.93 | 0.00 | 20.83 |
Maximum of Months | 514.00 | 26.16 | 496.67 | 24.59 | 243.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.67 | 21.83 | 97.67 | 21.56 | 97.67 | 21.37 |
February | 359.50 | 22.48 | 52.17 | 22.32 | 46.00 | 22.14 |
March | 352.50 | 22.96 | 38.50 | 22.94 | 24.50 | 22.81 |
April | 146.17 | 23.72 | 109.00 | 24.36 | 5.33 | 24.42 |
May | 59.50 | 25.16 | 258.17 | 24.88 | 23.50 | 25.03 |
June | 32.33 | 27.01 | 364.83 | 24.87 | 32.00 | 25.03 |
July | 108.67 | 25.96 | 422.00 | 25.00 | 108.67 | 25.16 |
August | 50.50 | 26.19 | 421.50 | 24.73 | 50.50 | 24.87 |
September | 65.00 | 25.73 | 351.33 | 24.76 | 53.00 | 24.93 |
October | 162.50 | 23.49 | 181.17 | 24.10 | 8.83 | 24.14 |
November | 349.00 | 22.66 | 44.17 | 22.62 | 26.50 | 22.49 |
December | 422.00 | 21.68 | 127.83 | 21.39 | 127.83 | 21.20 |
Annual Sum or Average | 2534.33 | 22.90 | 2468.33 | 23.52 | 604.33 | 23.48 |
Minimum of Months | 32.33 | 21.68 | 38.50 | 21.39 | 5.33 | 21.20 |
Maximum of Months | 426.67 | 27.01 | 422.00 | 25.00 | 127.83 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.50 | 22.18 | 102.17 | 22.15 | 68.67 | 21.92 |
February | 306.33 | 22.53 | 66.67 | 22.67 | 35.17 | 22.50 |
March | 336.83 | 22.93 | 41.83 | 23.06 | 17.17 | 22.96 |
April | 203.83 | 23.52 | 93.50 | 23.98 | 1.17 | 23.99 |
May | 89.17 | 23.92 | 222.17 | 24.43 | 2.67 | 24.46 |
June | 9.33 | 25.08 | 375.33 | 24.54 | 3.00 | 24.56 |
July | 88.17 | 25.22 | 496.00 | 24.63 | 88.17 | 24.71 |
August | 36.17 | 25.75 | 493.83 | 24.51 | 36.17 | 24.59 |
September | 69.50 | 25.36 | 420.83 | 24.60 | 54.00 | 24.73 |
October | 156.00 | 24.06 | 289.17 | 24.39 | 31.33 | 24.55 |
November | 271.33 | 22.74 | 117.50 | 23.24 | 24.33 | 23.17 |
December | 362.50 | 22.15 | 102.50 | 21.99 | 84.00 | 21.75 |
Annual Sum or Average | 2289.67 | 23.00 | 2821.50 | 23.71 | 445.83 | 23.66 |
Minimum of Months | 9.33 | 22.15 | 41.83 | 21.99 | 1.17 | 21.75 |
Maximum of Months | 362.50 | 25.75 | 496.00 | 24.63 | 88.17 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.83 | 21.74 | 130.33 | 21.48 | 128.83 | 21.30 |
February | 409.83 | 22.22 | 77.50 | 22.08 | 68.33 | 21.90 |
March | 406.83 | 22.78 | 45.33 | 22.81 | 25.17 | 22.70 |
April | 222.83 | 23.65 | 104.83 | 24.04 | 7.50 | 24.12 |
May | 96.33 | 24.60 | 281.83 | 24.62 | 23.00 | 24.76 |
June | 24.00 | 26.65 | 409.17 | 24.68 | 20.33 | 24.79 |
July | 98.00 | 25.41 | 496.33 | 24.73 | 98.00 | 24.82 |
August | 43.17 | 25.70 | 499.67 | 24.55 | 43.17 | 24.64 |
September | 72.83 | 24.94 | 410.83 | 24.52 | 54.00 | 24.62 |
October | 188.17 | 23.62 | 220.00 | 24.07 | 19.00 | 24.15 |
November | 376.67 | 22.42 | 71.17 | 22.44 | 40.00 | 22.28 |
December | 491.83 | 21.68 | 168.67 | 21.37 | 168.67 | 21.18 |
Annual Sum or Average | 2906.33 | 22.70 | 2915.67 | 23.33 | 696.00 | 23.25 |
Minimum of Months | 24.00 | 21.68 | 45.33 | 21.37 | 7.50 | 21.18 |
Maximum of Months | 491.83 | 26.65 | 499.67 | 24.73 | 168.67 | 24.82 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78129 | 21.44690 | 0.10541 | 5.39105 |
February | 454.00000 | 23.95072 | 18.09154 | 0.13799 | 5.54250 |
March | 514.00000 | 24.10749 | 17.49928 | 0.18617 | 5.84171 |
April | 485.00000 | 24.29774 | 20.94111 | 0.29042 | 6.94216 |
May | 508.00000 | 24.32036 | 29.49799 | -0.4860 | 10.33751 |
June | 496.00000 | 24.32866 | 35.61889 | -0.4197 | 9.05702 |
July | 497.00000 | 24.37654 | 47.49465 | -0.3215 | 7.48947 |
August | 514.00000 | 24.33757 | 45.19887 | -0.3500 | 7.86363 |
September | 485.00000 | 24.37860 | 42.72289 | -0.3597 | 8.16121 |
October | 502.00000 | 24.33044 | 34.73392 | 0.41014 | 8.76730 |
November | 489.00000 | 24.19539 | 22.75563 | 0.25578 | 6.57594 |
December | 497.00000 | 23.78340 | 18.55599 | 0.08703 | 5.34756 |
Annual Sum or Average | 5943.00000 | 24.18363 | 29.63602 | -0.0409 | 7.29141 |
Minimum of Months | 454.00000 | 23.78129 | 17.49928 | -0.4860 | 5.34756 |
Maximum of Months | 514.00000 | 24.37860 | 47.49465 | 0.41014 | 10.33751 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.78613 | 23.63296 | -0.1229 | 5.84355 |
February | 454.00000 | 23.23132 | 19.54776 | -0.0303 | 5.51671 |
March | 514.00000 | 23.63742 | 18.34889 | 0.07259 | 5.42755 |
April | 485.00000 | 24.10047 | 21.47895 | 0.24092 | 6.43658 |
May | 508.00000 | 24.25816 | 30.14951 | -0.5125 | 10.90381 |
June | 496.00000 | 24.30801 | 36.33839 | -0.4303 | 9.25302 |
July | 497.00000 | 24.35026 | 48.94251 | -0.3286 | 7.57623 |
August | 514.00000 | 24.29702 | 46.45021 | -0.3682 | 8.10812 |
September | 485.00000 | 24.30908 | 43.86866 | -0.3941 | 8.64565 |
October | 502.00000 | 24.13799 | 35.72129 | 0.35299 | 7.81809 |
November | 489.00000 | 23.58765 | 24.00477 | 0.09875 | 5.83284 |
December | 497.00000 | 22.65972 | 20.61254 | -0.1730 | 6.26427 |
Annual Sum or Average | 5943.00000 | 23.80920 | 30.84601 | -0.1345 | 7.31862 |
Minimum of Months | 454.00000 | 22.65972 | 18.34889 | -0.5125 | 5.42755 |
Maximum of Months | 514.00000 | 24.35026 | 48.94251 | 0.35299 | 10.90381 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.89348 | 24.79253 | -0.3417 | 8.61546 |
February | 454.00000 | 22.48883 | 20.29076 | -0.2111 | 7.13968 |
March | 514.00000 | 23.15466 | 18.81562 | -0.0461 | 5.95143 |
April | 485.00000 | 23.94856 | 21.36614 | 0.20326 | 6.33480 |
May | 508.00000 | 24.23632 | 29.79655 | -0.5135 | 11.12148 |
June | 496.00000 | 24.32782 | 35.79393 | -0.4071 | 8.92191 |
July | 497.00000 | 24.40318 | 47.89368 | -0.3001 | 7.34073 |
August | 514.00000 | 24.30976 | 45.52845 | -0.3589 | 8.05080 |
September | 485.00000 | 24.26348 | 43.31704 | -0.4114 | 9.05570 |
October | 502.00000 | 23.88957 | 35.87996 | 0.28415 | 7.12192 |
November | 489.00000 | 22.84339 | 25.08638 | -0.0868 | 6.67012 |
December | 497.00000 | 21.65069 | 21.51326 | -0.4227 | 10.05607 |
Annual Sum or Average | 5943.00000 | 23.45792 | 30.92154 | -0.2185 | 8.04072 |
Minimum of Months | 454.00000 | 21.65069 | 18.81562 | -0.5135 | 5.95143 |
Maximum of Months | 514.00000 | 24.40318 | 47.89368 | 0.28415 | 11.12148 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.83668 | 26.36560 | -0.6108 | 14.32336 |
February | 454.00000 | 21.46531 | 22.48211 | -0.4593 | 11.31305 |
March | 514.00000 | 22.29273 | 20.25480 | -0.2505 | 8.36598 |
April | 485.00000 | 23.61824 | 22.04263 | 0.13017 | 6.85359 |
May | 508.00000 | 24.22899 | 29.56394 | -0.4886 | 11.60798 |
June | 496.00000 | 24.43503 | 35.55106 | -0.3129 | 8.02359 |
July | 497.00000 | 24.54922 | 48.79222 | -0.1903 | 6.89902 |
August | 514.00000 | 24.35731 | 46.07077 | -0.3064 | 7.89034 |
September | 485.00000 | 24.18035 | 44.46635 | -0.4191 | 10.13796 |
October | 502.00000 | 23.41357 | 38.24546 | 0.17675 | 6.99950 |
November | 489.00000 | 21.77170 | 27.16692 | -0.3451 | 10.04094 |
December | 497.00000 | 20.63315 | 23.58981 | -0.6873 | 16.61301 |
Annual Sum or Average | 5943.00000 | 22.99334 | 32.12185 | -0.3132 | 9.91232 |
Minimum of Months | 454.00000 | 20.63315 | 20.25480 | -0.6873 | 6.85359 |
Maximum of Months | 514.00000 | 24.54922 | 48.79222 | 0.17675 | 16.61301 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.43705 | 26.50308 | -0.4485 | 11.60891 |
February | 454.00000 | 22.30266 | 22.02533 | -0.2402 | 8.96495 |
March | 514.00000 | 23.02968 | 18.97411 | -0.0467 | 7.44798 |
April | 485.00000 | 24.09659 | 20.86567 | 0.29951 | 8.54150 |
May | 508.00000 | 24.40860 | 29.00683 | -0.3345 | 9.57949 |
June | 496.00000 | 24.51201 | 35.21893 | -0.1944 | 7.36524 |
July | 497.00000 | 24.64132 | 48.18958 | -0.0769 | 7.03766 |
August | 514.00000 | 24.44114 | 45.63647 | -0.1904 | 7.33136 |
September | 485.00000 | 24.37072 | 43.45031 | -0.2650 | 8.60057 |
October | 502.00000 | 23.79027 | 36.88081 | 0.30006 | 8.65925 |
November | 489.00000 | 22.50208 | 26.47966 | -0.1524 | 8.40262 |
December | 497.00000 | 21.18632 | 23.94300 | -0.5330 | 13.28460 |
Annual Sum or Average | 5943.00000 | 23.40124 | 31.50325 | -0.1569 | 8.89850 |
Minimum of Months | 454.00000 | 21.18632 | 18.97411 | -0.5330 | 7.03766 |
Maximum of Months | 514.00000 | 24.64132 | 48.18958 | 0.30006 | 13.28460 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.34754 | 23.02598 | -0.1996 | 10.54873 |
February | 454.00000 | 22.76832 | 19.54569 | -0.1028 | 9.44314 |
March | 514.00000 | 23.09701 | 17.95798 | -0.0186 | 8.18440 |
April | 485.00000 | 23.84849 | 21.16191 | 0.21920 | 7.99096 |
May | 508.00000 | 24.22676 | 29.48002 | -0.4738 | 11.69976 |
June | 496.00000 | 24.41297 | 35.61233 | -0.3239 | 8.26848 |
July | 497.00000 | 24.53572 | 48.81608 | -0.1897 | 7.02301 |
August | 514.00000 | 24.38546 | 45.78613 | -0.2578 | 7.64240 |
September | 485.00000 | 24.32988 | 43.40068 | -0.2789 | 8.93243 |
October | 502.00000 | 23.94658 | 35.70150 | 0.37639 | 10.28734 |
November | 489.00000 | 23.05697 | 23.77846 | 0.02475 | 9.54386 |
December | 497.00000 | 22.22274 | 20.51048 | -0.2550 | 11.17406 |
Annual Sum or Average | 5943.00000 | 23.60404 | 30.48205 | -0.1244 | 9.22855 |
Minimum of Months | 454.00000 | 22.22274 | 17.95798 | -0.4738 | 7.02301 |
Maximum of Months | 514.00000 | 24.53572 | 48.81608 | 0.37639 | 11.69976 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.40991 | 25.90360 | -0.4588 | 12.60739 |
February | 454.00000 | 22.01053 | 22.04703 | -0.3139 | 10.45825 |
March | 514.00000 | 22.73806 | 19.56068 | -0.1136 | 8.51462 |
April | 485.00000 | 23.82247 | 21.65253 | 0.22888 | 8.43458 |
May | 508.00000 | 24.29293 | 29.41771 | -0.3883 | 10.96945 |
June | 496.00000 | 24.47739 | 35.47868 | -0.2266 | 7.84115 |
July | 497.00000 | 24.59424 | 48.70603 | -0.1121 | 7.09792 |
August | 514.00000 | 24.41993 | 45.90178 | -0.2146 | 7.70196 |
September | 485.00000 | 24.28973 | 44.00649 | -0.3002 | 9.25385 |
October | 502.00000 | 23.71074 | 37.37673 | 0.28852 | 8.79925 |
November | 489.00000 | 22.31217 | 26.23842 | -0.1931 | 9.64248 |
December | 497.00000 | 21.20276 | 23.46580 | -0.5363 | 14.36847 |
Annual Sum or Average | 5943.00000 | 23.28291 | 31.71967 | -0.1948 | 9.63386 |
Minimum of Months | 454.00000 | 21.20276 | 19.56068 | -0.5363 | 7.09792 |
Maximum of Months | 514.00000 | 24.59424 | 48.70603 | 0.28852 | 14.36847 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.17993 | 26.11403 | -0.5057 | 10.93965 |
February | 454.00000 | 21.45888 | 22.90773 | -0.4538 | 10.19108 |
March | 514.00000 | 21.98748 | 21.65386 | -0.3277 | 8.24606 |
April | 485.00000 | 23.40979 | 23.59627 | 0.05407 | 5.96369 |
May | 508.00000 | 24.09801 | 30.52963 | -0.5832 | 12.89608 |
June | 496.00000 | 24.31900 | 35.99867 | -0.4058 | 8.86761 |
July | 497.00000 | 24.45737 | 48.42271 | -0.2593 | 6.93659 |
August | 514.00000 | 24.35519 | 45.79996 | -0.3239 | 7.65189 |
September | 485.00000 | 24.29680 | 43.74693 | -0.3807 | 8.65323 |
October | 502.00000 | 23.87145 | 37.31172 | 0.28941 | 7.18649 |
November | 489.00000 | 22.56827 | 26.79463 | -0.1363 | 6.64155 |
December | 497.00000 | 21.22692 | 23.04346 | -0.5094 | 11.14885 |
Annual Sum or Average | 5943.00000 | 23.11306 | 32.23258 | -0.2952 | 8.77882 |
Minimum of Months | 454.00000 | 21.17993 | 21.65386 | -0.5832 | 5.96369 |
Maximum of Months | 514.00000 | 24.45737 | 48.42271 | 0.28941 | 12.89608 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.99921 | 26.06233 | -0.2964 | 8.15202 |
February | 454.00000 | 22.54871 | 22.38764 | -0.1780 | 7.27936 |
March | 514.00000 | 23.04985 | 20.25472 | -0.0536 | 6.55827 |
April | 485.00000 | 24.12471 | 21.74918 | 0.27587 | 7.57616 |
May | 508.00000 | 24.40116 | 29.48753 | -0.3874 | 9.59781 |
June | 496.00000 | 24.47956 | 35.38450 | -0.2579 | 7.47629 |
July | 497.00000 | 24.62665 | 47.61454 | -0.1197 | 6.65327 |
August | 514.00000 | 24.48162 | 45.19858 | -0.1900 | 6.83798 |
September | 485.00000 | 24.49872 | 42.71029 | -0.2169 | 7.40678 |
October | 502.00000 | 24.20691 | 35.95709 | 0.40907 | 9.23983 |
November | 489.00000 | 23.36550 | 25.52970 | 0.07354 | 6.43219 |
December | 497.00000 | 22.07208 | 23.10719 | -0.2955 | 8.22560 |
Annual Sum or Average | 5943.00000 | 23.66124 | 31.35902 | -0.1037 | 7.62443 |
Minimum of Months | 454.00000 | 21.99921 | 20.25472 | -0.3874 | 6.43219 |
Maximum of Months | 514.00000 | 24.62665 | 47.61454 | 0.40907 | 9.59781 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.65432 | 21.46168 | -0.0829 | 7.93123 |
February | 454.00000 | 22.79854 | 18.97273 | -0.0714 | 7.80175 |
March | 514.00000 | 22.86659 | 18.04653 | -0.0701 | 7.19366 |
April | 485.00000 | 23.65925 | 21.44899 | 0.14870 | 6.90082 |
May | 508.00000 | 24.04759 | 29.74623 | -0.5834 | 13.47692 |
June | 496.00000 | 24.32420 | 35.31350 | -0.4157 | 9.23695 |
July | 497.00000 | 24.49346 | 49.25784 | -0.2399 | 6.86796 |
August | 514.00000 | 24.42426 | 45.73890 | -0.2587 | 7.23917 |
September | 485.00000 | 24.48454 | 42.71522 | -0.2213 | 7.62150 |
October | 502.00000 | 24.28321 | 35.00876 | 0.47730 | 11.11370 |
November | 489.00000 | 23.63353 | 22.65515 | 0.20520 | 8.41562 |
December | 497.00000 | 22.67387 | 18.75140 | -0.0937 | 7.91775 |
Annual Sum or Average | 5943.00000 | 23.70021 | 30.01391 | -0.1021 | 8.48997 |
Minimum of Months | 454.00000 | 22.65432 | 18.04653 | -0.5834 | 6.86796 |
Maximum of Months | 514.00000 | 24.49346 | 49.25784 | 0.47730 | 13.47692 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92716 | 25.62294 | -0.3128 | 8.61189 |
February | 454.00000 | 22.23046 | 22.50832 | -0.2565 | 8.16205 |
March | 514.00000 | 22.83505 | 20.66241 | -0.1061 | 6.97122 |
April | 485.00000 | 23.94338 | 22.35162 | 0.22274 | 7.24360 |
May | 508.00000 | 24.31730 | 29.80173 | -0.4295 | 10.37627 |
June | 496.00000 | 24.44099 | 35.62566 | -0.2895 | 7.80043 |
July | 497.00000 | 24.57938 | 48.04025 | -0.1525 | 6.63838 |
August | 514.00000 | 24.47900 | 45.37229 | -0.2072 | 6.99168 |
September | 485.00000 | 24.47823 | 42.98777 | -0.2336 | 7.37422 |
October | 502.00000 | 24.23661 | 36.00327 | 0.41990 | 9.42231 |
November | 489.00000 | 23.28023 | 25.49729 | 0.05539 | 6.66984 |
December | 497.00000 | 21.93777 | 22.83383 | -0.3271 | 8.80723 |
Annual Sum or Average | 5943.00000 | 23.56549 | 31.51418 | -0.1350 | 7.92588 |
Minimum of Months | 454.00000 | 21.92716 | 20.66241 | -0.4295 | 6.63838 |
Maximum of Months | 514.00000 | 24.57938 | 48.04025 | 0.41990 | 10.37627 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.28480 | 25.86101 | -0.4748 | 10.65623 |
February | 454.00000 | 21.90700 | 22.08805 | -0.3340 | 8.64214 |
March | 514.00000 | 22.67955 | 20.04250 | -0.1485 | 6.74558 |
April | 485.00000 | 23.81022 | 22.10340 | 0.17566 | 6.40963 |
May | 508.00000 | 24.27858 | 29.83553 | -0.4803 | 10.81063 |
June | 496.00000 | 24.43625 | 35.91339 | -0.3308 | 8.06542 |
July | 497.00000 | 24.53586 | 49.45042 | -0.2102 | 6.81605 |
August | 514.00000 | 24.37240 | 46.67018 | -0.3099 | 7.65920 |
September | 485.00000 | 24.25623 | 44.69859 | -0.3955 | 9.08677 |
October | 502.00000 | 23.72420 | 37.79226 | 0.25526 | 7.00524 |
November | 489.00000 | 22.36019 | 26.44722 | -0.1894 | 7.40043 |
December | 497.00000 | 21.12538 | 23.15955 | -0.5364 | 12.05249 |
Annual Sum or Average | 5943.00000 | 23.24060 | 32.08153 | -0.2483 | 8.44660 |
Minimum of Months | 454.00000 | 21.12538 | 20.04250 | -0.5364 | 6.40963 |
Maximum of Months | 514.00000 | 24.53586 | 49.45042 | 0.25526 | 12.05249 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.83590 | 25.85718 | -0.3321 | 9.11950 |
February | 385.00000 | 22.63297 | 21.05610 | -0.1488 | 7.57545 |
March | 433.00000 | 23.25572 | 18.46994 | 0.00987 | 6.81203 |
April | 410.00000 | 24.24213 | 20.69370 | 0.32059 | 8.47297 |
May | 430.00000 | 24.52657 | 28.88140 | -0.3272 | 9.33797 |
June | 418.00000 | 24.61326 | 34.91698 | -0.2065 | 7.55022 |
July | 422.00000 | 24.75210 | 48.26465 | -0.0799 | 7.08630 |
August | 433.00000 | 24.54396 | 45.55519 | -0.1916 | 7.30253 |
September | 410.00000 | 24.50403 | 43.26482 | -0.2487 | 8.27367 |
October | 427.00000 | 24.04131 | 36.39558 | 0.35440 | 8.87379 |
November | 417.00000 | 22.93928 | 25.22781 | -0.0365 | 7.09689 |
December | 422.00000 | 21.68411 | 23.31611 | -0.3911 | 10.07058 |
Annual Sum or Average | 5034.00000 | 23.63587 | 31.06392 | -0.1069 | 8.13435 |
Minimum of Months | 385.00000 | 21.68411 | 18.46994 | -0.3911 | 6.81203 |
Maximum of Months | 433.00000 | 24.75210 | 48.26465 | 0.35440 | 10.07058 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.80188 | 22.31138 | -0.0678 | 8.49279 |
February | 454.00000 | 23.18221 | 18.98072 | 0.01248 | 7.89518 |
March | 514.00000 | 23.42667 | 17.65162 | 0.06945 | 7.13117 |
April | 485.00000 | 24.03213 | 21.17746 | 0.26108 | 7.60093 |
May | 508.00000 | 24.29135 | 29.71608 | -0.4619 | 10.75648 |
June | 496.00000 | 24.41809 | 35.95788 | -0.3406 | 8.26489 |
July | 497.00000 | 24.52792 | 49.43978 | -0.2083 | 6.91093 |
August | 514.00000 | 24.40681 | 46.34270 | -0.2610 | 7.35698 |
September | 485.00000 | 24.40888 | 43.59552 | -0.2579 | 8.00315 |
October | 502.00000 | 24.18722 | 35.38237 | 0.43832 | 10.52104 |
November | 489.00000 | 23.51152 | 23.10013 | 0.15038 | 8.53616 |
December | 497.00000 | 22.74385 | 19.80448 | -0.1044 | 8.72642 |
Annual Sum or Average | 5943.00000 | 23.83243 | 30.37670 | -0.0657 | 8.35502 |
Minimum of Months | 454.00000 | 22.74385 | 17.65162 | -0.4619 | 6.91093 |
Maximum of Months | 514.00000 | 24.52792 | 49.43978 | 0.43832 | 10.75648 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.86633 | 25.30012 | -0.3238 | 9.40539 |
February | 454.00000 | 22.45221 | 21.57575 | -0.1907 | 8.10638 |
March | 514.00000 | 23.11774 | 19.27881 | -0.0148 | 7.08702 |
April | 485.00000 | 24.02713 | 21.62852 | 0.27480 | 8.02097 |
May | 508.00000 | 24.36119 | 29.61142 | -0.3762 | 9.97306 |
June | 496.00000 | 24.48593 | 35.79563 | -0.2434 | 7.70893 |
July | 497.00000 | 24.59065 | 49.31053 | -0.1302 | 6.87523 |
August | 514.00000 | 24.44258 | 46.46115 | -0.2175 | 7.35257 |
September | 485.00000 | 24.37462 | 44.19577 | -0.2767 | 8.21872 |
October | 502.00000 | 23.99616 | 36.93294 | 0.36024 | 8.89782 |
November | 489.00000 | 22.85713 | 25.51591 | -0.0480 | 7.58592 |
December | 497.00000 | 21.70210 | 22.89789 | -0.3868 | 10.42592 |
Annual Sum or Average | 5943.00000 | 23.53058 | 31.61932 | -0.1314 | 8.30638 |
Minimum of Months | 454.00000 | 21.70210 | 19.27881 | -0.3868 | 6.87523 |
Maximum of Months | 514.00000 | 24.59065 | 49.31053 | 0.36024 | 10.42592 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.670174E+09 | 0.177430E+09 | 49.11 | 0.658042E+09 | 12131367.17 | 0.00 | 0.48 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 12398.70 | 03-JAN-15:00 | 12398.70 | 03-JAN-15:00 | 566.06 | 12-JAN-17:03 | 3113.74 | 03-JAN-15:00 | 0.00 |
February | 0.295727E+10 | 0.742123E+09 | 111.69 | 0.293514E+10 | 22130581.87 | 0.00 | 0.89 | 21-FEB-16:30 | 0.00 | 01-FEB-00:10 | 25570.42 | 21-FEB-16:30 | 25570.42 | 21-FEB-16:30 | 762.88 | 27-FEB-14:10 | 5751.14 | 21-FEB-16:30 | 0.00 |
March | 0.741863E+10 | 0.185181E+10 | 234.28 | 0.739223E+10 | 26408770.31 | 0.00 | 0.95 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 28015.54 | 21-MAR-16:00 | 28015.54 | 21-MAR-16:00 | 532.59 | 03-MAR-18:30 | 6353.46 | 21-MAR-16:00 | 0.00 |
April | 0.217681E+11 | 0.535184E+10 | 333.95 | 0.215935E+11 | 0.174660E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 48458.25 | 21-APR-15:10 | 48458.25 | 21-APR-15:10 | 3167.12 | 18-APR-21:00 | 13100.23 | 21-APR-15:10 | 0.00 |
May | 0.432410E+11 | 0.108135E+11 | 440.51 | 0.420637E+11 | 0.117731E+10 | 0.00 | 1.00 | 02-MAY-14:30 | 0.00 | 01-MAY-00:10 | 62474.70 | 30-MAY-06:03 | 62474.70 | 30-MAY-06:03 | 8796.89 | 25-MAY-09:00 | 17961.50 | 30-MAY-15:10 | 0.00 |
June | 0.608295E+11 | 0.164334E+11 | 452.31 | 0.587061E+11 | 0.212343E+10 | 0.00 | 1.00 | 01-JUN-07:20 | 0.00 | 01-JUN-00:10 | 76012.61 | 19-JUN-06:03 | 68726.42 | 15-JUN-06:03 | 19337.53 | 19-JUN-18:00 | 21265.11 | 15-JUN-15:10 | 0.00 |
July | 0.717803E+11 | 0.184183E+11 | 465.74 | 0.582912E+11 | 0.134891E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 101815.39 | 20-JUL-15:05 | 80078.14 | 03-JUL-06:03 | 67669.71 | 21-JUL-06:03 | 21825.15 | 20-JUL-15:05 | 0.00 |
August | 0.665585E+11 | 0.167757E+11 | 479.41 | 0.575907E+11 | 0.896778E+10 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 96193.15 | 03-AUG-06:03 | 75564.88 | 07-AUG-06:03 | 54685.76 | 03-AUG-06:03 | 21518.67 | 07-AUG-16:00 | 0.00 |
September | 0.553819E+11 | 0.135340E+11 | 419.56 | 0.482391E+11 | 0.714278E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 93868.34 | 22-SEP-06:03 | 62313.61 | 18-SEP-16:00 | 58142.55 | 22-SEP-06:03 | 20504.64 | 22-SEP-06:03 | 0.00 |
October | 0.280851E+11 | 0.663428E+10 | 344.51 | 0.250563E+11 | 0.302880E+10 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 64921.85 | 04-OCT-10:40 | 60161.00 | 02-OCT-04:02 | 24056.25 | 04-OCT-10:40 | 17333.69 | 03-OCT-14:00 | 0.00 |
November | 0.811657E+10 | 0.195149E+10 | 188.57 | 0.797009E+10 | 0.146487E+09 | 0.00 | 1.00 | 03-NOV-14:05 | 0.00 | 01-NOV-00:10 | 35219.88 | 03-NOV-16:00 | 35219.88 | 03-NOV-16:00 | 2677.57 | 02-NOV-14:30 | 7679.16 | 03-NOV-16:00 | 0.00 |
December | 0.256661E+09 | 70181234.01 | 30.72 | 0.254086E+09 | 2574349.06 | 0.00 | 0.24 | 20-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5850.65 | 20-DEC-15:00 | 5850.65 | 20-DEC-15:00 | 416.24 | 10-DEC-13:20 | 1559.69 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.367064E+12 | 0.927541E+11 | 3550.36 | 0.330750E+12 | 0.363136E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.256661E+09 | 70181234.01 | 30.72 | 0.254086E+09 | 2574349.06 | 0.00 | 0.24 | 0.00 | 5850.65 | 5850.65 | 416.24 | 1559.69 | 0.00 | ||||||
Maximum of Months | 0.717803E+11 | 0.184183E+11 | 479.41 | 0.587061E+11 | 0.134891E+11 | 0.00 | 1.00 | 0.00 | 101815.39 | 80078.14 | 67669.71 | 21825.15 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.606924E+09 | 0.161107E+09 | 47.50 | 0.593471E+09 | 13453165.32 | 0.00 | 0.46 | 12-JAN-15:05 | 0.00 | 01-JAN-00:10 | 11378.57 | 12-JAN-15:05 | 11378.57 | 12-JAN-15:05 | 583.64 | 12-JAN-17:03 | 2870.75 | 12-JAN-15:05 | 0.00 |
February | 0.259415E+10 | 0.659846E+09 | 108.69 | 0.256994E+10 | 24210776.22 | 0.00 | 0.81 | 21-FEB-15:05 | 0.00 | 01-FEB-00:10 | 21939.56 | 21-FEB-15:05 | 21939.56 | 21-FEB-15:05 | 820.64 | 27-FEB-15:10 | 5041.03 | 21-FEB-15:05 | 0.00 |
March | 0.662495E+10 | 0.164104E+10 | 212.61 | 0.660083E+10 | 24111511.36 | 0.00 | 1.00 | 22-MAR-14:05 | 0.00 | 01-MAR-00:10 | 29091.51 | 22-MAR-14:05 | 29091.51 | 22-MAR-14:05 | 482.57 | 12-MAR-14:40 | 6405.78 | 22-MAR-14:05 | 0.00 |
April | 0.220103E+11 | 0.540384E+10 | 344.31 | 0.218537E+11 | 0.156552E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 51529.47 | 21-APR-14:05 | 51529.47 | 21-APR-14:05 | 3219.13 | 30-APR-08:62 | 14001.88 | 21-APR-14:05 | 0.00 |
May | 0.428991E+11 | 0.107160E+11 | 447.53 | 0.418816E+11 | 0.101745E+10 | 0.00 | 1.00 | 01-MAY-14:05 | 0.00 | 01-MAY-00:10 | 67966.06 | 30-MAY-06:03 | 67966.06 | 30-MAY-06:03 | 9533.86 | 22-MAY-06:03 | 18546.25 | 30-MAY-14:05 | 0.00 |
June | 0.597079E+11 | 0.161160E+11 | 459.50 | 0.578215E+11 | 0.188635E+10 | 0.00 | 1.00 | 01-JUN-07:20 | 0.00 | 01-JUN-00:10 | 75519.51 | 19-JUN-06:03 | 67832.66 | 15-JUN-06:03 | 18790.06 | 19-JUN-18:00 | 21114.67 | 15-JUN-14:05 | 0.00 |
July | 0.671828E+11 | 0.172254E+11 | 469.52 | 0.551944E+11 | 0.119884E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 97525.76 | 20-JUL-15:05 | 76953.58 | 03-JUL-06:03 | 64072.86 | 17-JUL-06:03 | 22549.38 | 03-JUL-14:05 | 0.00 |
August | 0.595644E+11 | 0.150699E+11 | 477.64 | 0.522102E+11 | 0.735425E+10 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 92140.40 | 03-AUG-06:03 | 69718.69 | 07-AUG-04:02 | 52999.52 | 03-AUG-06:03 | 20482.43 | 07-AUG-16:00 | 0.00 |
September | 0.477141E+11 | 0.117301E+11 | 417.66 | 0.419710E+11 | 0.574316E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 71825.96 | 14-SEP-09:50 | 59455.68 | 18-SEP-15:20 | 39908.95 | 22-SEP-06:03 | 16668.22 | 05-SEP-15:30 | 0.00 |
October | 0.239673E+11 | 0.570513E+10 | 336.83 | 0.213699E+11 | 0.259744E+10 | 0.00 | 1.00 | 01-OCT-13:42 | 0.00 | 01-OCT-00:10 | 62391.76 | 03-OCT-14:05 | 60585.87 | 02-OCT-04:02 | 19821.83 | 04-OCT-10:40 | 17028.20 | 03-OCT-14:05 | 0.00 |
November | 0.515487E+10 | 0.126914E+10 | 160.47 | 0.498099E+10 | 0.173878E+09 | 0.00 | 1.00 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 | 32603.04 | 09-NOV-15:05 | 32603.04 | 09-NOV-15:05 | 3635.37 | 03-NOV-11:00 | 7089.33 | 09-NOV-15:05 | 0.00 |
December | 0.212088E+09 | 58113812.37 | 27.25 | 0.209383E+09 | 2705220.04 | 0.00 | 0.20 | 20-DEC-15:00 | 0.00 | 01-DEC-00:10 | 4743.54 | 20-DEC-15:00 | 4743.54 | 20-DEC-15:00 | 353.70 | 10-DEC-12:35 | 1275.32 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.338239E+12 | 0.857557E+11 | 3509.51 | 0.307257E+12 | 0.309820E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.212088E+09 | 58113812.37 | 27.25 | 0.209383E+09 | 2705220.04 | 0.00 | 0.20 | 0.00 | 4743.54 | 4743.54 | 353.70 | 1275.32 | 0.00 | ||||||
Maximum of Months | 0.671828E+11 | 0.172254E+11 | 477.64 | 0.578215E+11 | 0.119884E+11 | 0.00 | 1.00 | 0.00 | 97525.76 | 76953.58 | 64072.86 | 22549.38 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.589995E+09 | 0.158278E+09 | 47.42 | 0.561197E+09 | 28798283.00 | 0.00 | 0.37 | 03-JAN-14:50 | 0.00 | 01-JAN-00:10 | 10327.75 | 03-JAN-14:50 | 10327.75 | 03-JAN-14:50 | 790.67 | 12-JAN-17:07 | 2666.10 | 03-JAN-14:50 | 0.00 |
February | 0.255748E+10 | 0.659473E+09 | 107.77 | 0.251358E+10 | 43896416.06 | 0.00 | 0.72 | 20-FEB-15:02 | 0.00 | 01-FEB-00:10 | 21881.65 | 20-FEB-15:02 | 21881.65 | 20-FEB-15:02 | 961.79 | 27-FEB-15:50 | 5158.90 | 20-FEB-15:02 | 0.00 |
March | 0.677185E+10 | 0.169586E+10 | 211.42 | 0.670292E+10 | 68925649.67 | 0.00 | 0.97 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 31755.19 | 21-MAR-16:00 | 31755.19 | 21-MAR-16:00 | 799.95 | 15-MAR-10:00 | 7164.24 | 21-MAR-16:00 | 0.00 |
April | 0.244033E+11 | 0.602990E+10 | 346.50 | 0.241465E+11 | 0.256820E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 59984.87 | 21-APR-14:40 | 59984.87 | 21-APR-14:40 | 3641.33 | 18-APR-21:00 | 16299.08 | 21-APR-14:40 | 0.00 |
May | 0.479918E+11 | 0.120755E+11 | 450.65 | 0.466146E+11 | 0.137717E+10 | 0.00 | 1.00 | 02-MAY-14:40 | 0.00 | 01-MAY-00:10 | 73770.30 | 30-MAY-14:50 | 73770.30 | 30-MAY-14:50 | 9641.49 | 25-MAY-09:00 | 21397.93 | 30-MAY-14:50 | 0.00 |
June | 0.674911E+11 | 0.183540E+11 | 462.30 | 0.651423E+11 | 0.234884E+10 | 0.00 | 1.00 | 01-JUN-08:00 | 0.00 | 01-JUN-00:10 | 77645.02 | 19-JUN-14:30 | 76979.68 | 15-JUN-14:40 | 20730.23 | 19-JUN-18:00 | 25058.76 | 15-JUN-14:40 | 0.00 |
July | 0.748320E+11 | 0.193374E+11 | 475.15 | 0.619230E+11 | 0.129090E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 112796.10 | 20-JUL-14:55 | 80401.66 | 03-JUL-14:30 | 74002.56 | 17-JUL-06:03 | 25654.68 | 03-JUL-14:30 | 0.00 |
August | 0.657425E+11 | 0.167863E+11 | 480.19 | 0.575248E+11 | 0.821765E+10 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 88115.04 | 05-AUG-05:03 | 76353.00 | 07-AUG-14:50 | 38412.40 | 03-AUG-06:03 | 23694.55 | 07-AUG-16:00 | 0.00 |
September | 0.518592E+11 | 0.128614E+11 | 418.79 | 0.455724E+11 | 0.628682E+10 | 0.00 | 1.00 | 01-SEP-07:20 | 0.00 | 01-SEP-00:10 | 79106.58 | 14-SEP-10:00 | 68525.18 | 18-SEP-15:20 | 39240.13 | 14-SEP-10:00 | 19040.45 | 18-SEP-15:20 | 0.00 |
October | 0.249468E+11 | 0.600876E+10 | 334.86 | 0.219968E+11 | 0.295000E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 70056.12 | 03-OCT-14:00 | 64233.36 | 02-OCT-04:02 | 18788.61 | 04-OCT-10:40 | 19191.89 | 03-OCT-14:00 | 0.00 |
November | 0.473923E+10 | 0.118761E+10 | 156.56 | 0.450613E+10 | 0.233094E+09 | 0.00 | 0.98 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 | 32125.49 | 09-NOV-15:00 | 32125.49 | 09-NOV-15:00 | 3374.35 | 03-NOV-12:10 | 7033.30 | 09-NOV-15:00 | 0.00 |
December | 0.209186E+09 | 57529394.20 | 28.67 | 0.200237E+09 | 8948517.84 | 0.00 | 0.18 | 20-DEC-15:00 | 0.00 | 01-DEC-00:10 | 4717.37 | 20-DEC-15:00 | 4717.37 | 20-DEC-15:00 | 351.30 | 08-DEC-16:00 | 1276.64 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.372134E+12 | 0.952120E+11 | 3520.27 | 0.337404E+12 | 0.347299E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.209186E+09 | 57529394.20 | 28.67 | 0.200237E+09 | 8948517.84 | 0.00 | 0.18 | 0.00 | 4717.37 | 4717.37 | 351.30 | 1276.64 | 0.00 | ||||||
Maximum of Months | 0.748320E+11 | 0.193374E+11 | 480.19 | 0.651423E+11 | 0.129090E+11 | 0.00 | 1.00 | 0.00 | 112796.10 | 80401.66 | 74002.56 | 25654.68 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 287.66 | 0.00 | 287.66 | 79.67 | 1342.87 | 0.00 | 0.00 | 0.00 |
February | 351.27 | 0.00 | 351.27 | 176.35 | 1222.17 | 0.00 | 0.00 | 0.00 |
March | 459.70 | 0.00 | 459.70 | 335.96 | 1049.34 | 0.00 | 0.00 | 0.00 |
April | 530.77 | 4.18 | 526.59 | 613.06 | 628.43 | 0.00 | 0.00 | 0.00 |
May | 629.52 | 45.52 | 583.99 | 1011.85 | 374.76 | 0.00 | 0.00 | 0.00 |
June | 669.38 | 82.41 | 586.97 | 1397.04 | 204.88 | 0.00 | 0.00 | 0.00 |
July | 618.64 | 60.22 | 558.42 | 1280.83 | 164.85 | 0.00 | 0.00 | 0.00 |
August | 521.65 | 10.67 | 510.98 | 998.81 | 219.97 | 0.00 | 0.00 | 0.00 |
September | 455.18 | 0.18 | 455.00 | 760.87 | 442.10 | 0.00 | 0.00 | 0.00 |
October | 377.93 | 0.00 | 377.93 | 405.24 | 701.26 | 0.00 | 0.00 | 0.00 |
November | 305.10 | 0.00 | 305.10 | 122.27 | 1170.41 | 0.00 | 0.00 | 0.00 |
December | 285.44 | 0.00 | 285.44 | 57.14 | 1485.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 458.21 | 17.02 | 441.19 | 605.45 | 748.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.44 | 0.00 | 285.44 | 57.14 | 164.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 669.38 | 82.41 | 586.97 | 1397.04 | 1485.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.94 | 278.25 | 234.69 | 518.59 | 833.29 | 0.00 | 0.00 | 0.00 |
February | 686.26 | 391.16 | 295.10 | 790.75 | 758.39 | 0.00 | 0.00 | 0.00 |
March | 847.31 | 466.84 | 380.47 | 1055.11 | 655.89 | 0.00 | 0.00 | 0.00 |
April | 1020.96 | 566.41 | 454.56 | 1489.98 | 403.72 | 0.00 | 0.00 | 0.00 |
May | 1053.58 | 572.58 | 481.00 | 1721.93 | 251.62 | 0.00 | 0.00 | 0.00 |
June | 1054.17 | 586.46 | 467.72 | 1936.38 | 134.98 | 0.00 | 0.00 | 0.00 |
July | 945.36 | 494.22 | 451.14 | 1740.07 | 110.58 | 0.00 | 0.00 | 0.00 |
August | 899.56 | 460.39 | 439.18 | 1599.70 | 146.90 | 0.00 | 0.00 | 0.00 |
September | 891.22 | 508.51 | 382.72 | 1484.97 | 280.32 | 0.00 | 0.00 | 0.00 |
October | 685.41 | 369.91 | 315.50 | 970.37 | 451.64 | 0.00 | 0.00 | 0.00 |
November | 614.41 | 357.69 | 256.72 | 696.28 | 728.48 | 0.00 | 0.00 | 0.00 |
December | 512.50 | 271.53 | 240.96 | 493.48 | 914.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 810.40 | 443.42 | 366.97 | 1209.44 | 471.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.50 | 271.53 | 234.69 | 493.48 | 110.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.17 | 586.46 | 481.00 | 1936.38 | 914.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1967.90 | 1490.89 | 477.01 | 2662.03 | 1250.19 | 0.00 | 0.00 | 0.00 |
February | 1825.45 | 1286.91 | 538.54 | 2506.87 | 1146.18 | 0.00 | 0.00 | 0.00 |
March | 1483.56 | 855.41 | 628.14 | 2095.72 | 1031.02 | 0.00 | 0.00 | 0.00 |
April | 1005.85 | 375.31 | 630.54 | 1593.52 | 657.21 | 0.00 | 0.00 | 0.00 |
May | 710.82 | 99.49 | 611.33 | 1245.29 | 399.71 | 0.00 | 0.00 | 0.00 |
June | 613.26 | 38.91 | 574.35 | 1319.59 | 209.23 | 0.00 | 0.00 | 0.00 |
July | 625.15 | 57.95 | 567.20 | 1331.80 | 170.70 | 0.00 | 0.00 | 0.00 |
August | 796.89 | 210.94 | 585.95 | 1603.61 | 232.41 | 0.00 | 0.00 | 0.00 |
September | 1243.86 | 646.23 | 597.63 | 2281.47 | 452.80 | 0.00 | 0.00 | 0.00 |
October | 1690.04 | 1142.58 | 547.46 | 2664.24 | 702.39 | 0.00 | 0.00 | 0.00 |
November | 2033.81 | 1550.53 | 483.28 | 2873.27 | 1097.56 | 0.00 | 0.00 | 0.00 |
December | 2015.58 | 1512.99 | 502.59 | 2682.55 | 1349.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1331.52 | 769.43 | 562.09 | 2068.69 | 722.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 613.26 | 38.91 | 477.01 | 1245.29 | 170.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2033.81 | 1550.53 | 630.54 | 2873.27 | 1349.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.32 | 304.29 | 236.03 | 604.20 | 877.95 | 0.00 | 0.00 | 0.00 |
February | 609.70 | 324.07 | 285.63 | 722.44 | 808.61 | 0.00 | 0.00 | 0.00 |
March | 830.84 | 445.30 | 385.54 | 1077.08 | 702.88 | 0.00 | 0.00 | 0.00 |
April | 954.99 | 515.80 | 439.18 | 1428.33 | 441.82 | 0.00 | 0.00 | 0.00 |
May | 1028.61 | 550.35 | 478.26 | 1708.03 | 278.61 | 0.00 | 0.00 | 0.00 |
June | 1001.27 | 537.79 | 463.48 | 1866.08 | 151.98 | 0.00 | 0.00 | 0.00 |
July | 888.56 | 441.54 | 447.02 | 1658.19 | 122.91 | 0.00 | 0.00 | 0.00 |
August | 860.52 | 438.56 | 421.97 | 1548.04 | 161.71 | 0.00 | 0.00 | 0.00 |
September | 880.02 | 490.26 | 389.76 | 1504.07 | 311.30 | 0.00 | 0.00 | 0.00 |
October | 757.55 | 442.13 | 315.42 | 1131.48 | 481.20 | 0.00 | 0.00 | 0.00 |
November | 635.85 | 387.17 | 248.69 | 793.54 | 773.27 | 0.00 | 0.00 | 0.00 |
December | 512.40 | 278.35 | 234.05 | 545.72 | 960.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 792.38 | 429.92 | 362.46 | 1217.66 | 504.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.40 | 278.35 | 234.05 | 545.72 | 122.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1028.61 | 550.35 | 478.26 | 1866.08 | 960.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.88 | 0.00 | 95.88 | 24.45 | 475.37 | 0.00 | 0.00 | 0.00 |
February | 117.08 | 0.00 | 117.08 | 61.57 | 415.25 | 0.00 | 0.00 | 0.00 |
March | 153.23 | 0.00 | 153.23 | 121.99 | 345.04 | 0.00 | 0.00 | 0.00 |
April | 176.92 | 1.39 | 175.52 | 217.08 | 201.33 | 0.00 | 0.00 | 0.00 |
May | 209.83 | 15.17 | 194.66 | 349.43 | 118.72 | 0.00 | 0.00 | 0.00 |
June | 223.12 | 27.47 | 195.65 | 477.36 | 62.66 | 0.00 | 0.00 | 0.00 |
July | 206.20 | 20.07 | 186.13 | 435.98 | 52.16 | 0.00 | 0.00 | 0.00 |
August | 173.87 | 3.56 | 170.32 | 336.76 | 74.85 | 0.00 | 0.00 | 0.00 |
September | 151.72 | 0.06 | 151.66 | 253.83 | 156.30 | 0.00 | 0.00 | 0.00 |
October | 125.97 | 0.00 | 125.97 | 131.89 | 254.98 | 0.00 | 0.00 | 0.00 |
November | 101.70 | 0.00 | 101.70 | 35.20 | 433.55 | 0.00 | 0.00 | 0.00 |
December | 95.14 | 0.00 | 95.14 | 14.64 | 539.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.73 | 5.67 | 147.06 | 205.75 | 260.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.14 | 0.00 | 95.14 | 14.64 | 52.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 223.12 | 27.47 | 195.65 | 477.36 | 539.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.89 | 0.00 | 95.89 | 24.45 | 475.40 | 0.00 | 0.00 | 0.00 |
February | 117.09 | 0.00 | 117.09 | 61.57 | 415.27 | 0.00 | 0.00 | 0.00 |
March | 153.23 | 0.00 | 153.23 | 121.99 | 345.06 | 0.00 | 0.00 | 0.00 |
April | 176.92 | 1.39 | 175.53 | 217.09 | 201.34 | 0.00 | 0.00 | 0.00 |
May | 209.84 | 15.17 | 194.66 | 349.45 | 118.72 | 0.00 | 0.00 | 0.00 |
June | 223.13 | 27.47 | 195.66 | 477.39 | 62.67 | 0.00 | 0.00 | 0.00 |
July | 206.21 | 20.07 | 186.14 | 436.00 | 52.17 | 0.00 | 0.00 | 0.00 |
August | 173.88 | 3.56 | 170.33 | 336.77 | 74.85 | 0.00 | 0.00 | 0.00 |
September | 151.73 | 0.06 | 151.67 | 253.85 | 156.31 | 0.00 | 0.00 | 0.00 |
October | 125.98 | 0.00 | 125.98 | 131.89 | 255.00 | 0.00 | 0.00 | 0.00 |
November | 101.70 | 0.00 | 101.70 | 35.20 | 433.58 | 0.00 | 0.00 | 0.00 |
December | 95.15 | 0.00 | 95.15 | 14.64 | 539.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.73 | 5.67 | 147.06 | 205.76 | 260.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.15 | 0.00 | 95.15 | 14.64 | 52.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 223.13 | 27.47 | 195.66 | 477.39 | 539.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.89 | 0.00 | 95.89 | 24.45 | 475.40 | 0.00 | 0.00 | 0.00 |
February | 117.09 | 0.00 | 117.09 | 61.57 | 415.27 | 0.00 | 0.00 | 0.00 |
March | 153.23 | 0.00 | 153.23 | 121.99 | 345.06 | 0.00 | 0.00 | 0.00 |
April | 176.92 | 1.39 | 175.53 | 217.09 | 201.34 | 0.00 | 0.00 | 0.00 |
May | 209.84 | 15.17 | 194.66 | 349.45 | 118.72 | 0.00 | 0.00 | 0.00 |
June | 223.13 | 27.47 | 195.66 | 477.39 | 62.67 | 0.00 | 0.00 | 0.00 |
July | 206.21 | 20.07 | 186.14 | 436.00 | 52.17 | 0.00 | 0.00 | 0.00 |
August | 173.88 | 3.56 | 170.33 | 336.77 | 74.85 | 0.00 | 0.00 | 0.00 |
September | 151.73 | 0.06 | 151.67 | 253.85 | 156.31 | 0.00 | 0.00 | 0.00 |
October | 125.98 | 0.00 | 125.98 | 131.89 | 255.00 | 0.00 | 0.00 | 0.00 |
November | 101.70 | 0.00 | 101.70 | 35.20 | 433.58 | 0.00 | 0.00 | 0.00 |
December | 95.15 | 0.00 | 95.15 | 14.64 | 539.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.73 | 5.67 | 147.06 | 205.76 | 260.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.15 | 0.00 | 95.15 | 14.64 | 52.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 223.13 | 27.47 | 195.66 | 477.39 | 539.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.42 | 267.66 | 225.76 | 491.01 | 869.13 | 0.00 | 0.00 | 0.00 |
February | 660.15 | 376.28 | 283.87 | 763.42 | 765.07 | 0.00 | 0.00 | 0.00 |
March | 815.07 | 449.07 | 365.99 | 1031.45 | 642.74 | 0.00 | 0.00 | 0.00 |
April | 982.12 | 544.85 | 437.26 | 1454.96 | 392.16 | 0.00 | 0.00 | 0.00 |
May | 1013.49 | 550.79 | 462.70 | 1678.25 | 242.37 | 0.00 | 0.00 | 0.00 |
June | 1014.06 | 564.14 | 449.92 | 1883.87 | 126.92 | 0.00 | 0.00 | 0.00 |
July | 909.39 | 475.41 | 433.98 | 1689.80 | 107.92 | 0.00 | 0.00 | 0.00 |
August | 865.34 | 442.87 | 422.47 | 1546.71 | 151.51 | 0.00 | 0.00 | 0.00 |
September | 857.31 | 489.16 | 368.15 | 1430.07 | 294.59 | 0.00 | 0.00 | 0.00 |
October | 659.33 | 355.83 | 303.50 | 929.19 | 481.05 | 0.00 | 0.00 | 0.00 |
November | 591.03 | 344.08 | 246.95 | 652.06 | 790.98 | 0.00 | 0.00 | 0.00 |
December | 493.00 | 261.20 | 231.80 | 455.39 | 975.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 779.56 | 426.55 | 353.01 | 1168.44 | 485.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 493.00 | 261.20 | 225.76 | 455.39 | 107.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1014.06 | 564.14 | 462.70 | 1883.87 | 975.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.51 | 10.58 | 8.93 | 19.41 | 34.36 | 0.00 | 0.00 | 0.00 |
February | 26.10 | 14.88 | 11.22 | 30.19 | 30.25 | 0.00 | 0.00 | 0.00 |
March | 32.23 | 17.76 | 14.47 | 40.78 | 25.41 | 0.00 | 0.00 | 0.00 |
April | 38.83 | 21.54 | 17.29 | 57.53 | 15.51 | 0.00 | 0.00 | 0.00 |
May | 40.07 | 21.78 | 18.29 | 66.36 | 9.58 | 0.00 | 0.00 | 0.00 |
June | 40.10 | 22.31 | 17.79 | 74.49 | 5.02 | 0.00 | 0.00 | 0.00 |
July | 35.96 | 18.80 | 17.16 | 66.81 | 4.27 | 0.00 | 0.00 | 0.00 |
August | 34.21 | 17.51 | 16.70 | 61.16 | 5.99 | 0.00 | 0.00 | 0.00 |
September | 33.90 | 19.34 | 14.56 | 56.54 | 11.65 | 0.00 | 0.00 | 0.00 |
October | 26.07 | 14.07 | 12.00 | 36.74 | 19.02 | 0.00 | 0.00 | 0.00 |
November | 23.37 | 13.60 | 9.76 | 25.78 | 31.27 | 0.00 | 0.00 | 0.00 |
December | 19.49 | 10.33 | 9.17 | 18.01 | 38.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.82 | 16.87 | 13.96 | 46.20 | 19.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.49 | 10.33 | 8.93 | 18.01 | 4.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.10 | 22.31 | 18.29 | 74.49 | 38.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 655.96 | 496.95 | 159.00 | 889.31 | 463.09 | 0.00 | 0.00 | 0.00 |
February | 608.47 | 428.96 | 179.51 | 843.07 | 409.47 | 0.00 | 0.00 | 0.00 |
March | 494.51 | 285.13 | 209.38 | 712.85 | 352.68 | 0.00 | 0.00 | 0.00 |
April | 335.28 | 125.10 | 210.18 | 544.99 | 216.97 | 0.00 | 0.00 | 0.00 |
May | 236.94 | 33.16 | 203.78 | 428.04 | 127.91 | 0.00 | 0.00 | 0.00 |
June | 204.42 | 12.97 | 191.45 | 450.21 | 64.08 | 0.00 | 0.00 | 0.00 |
July | 208.38 | 19.32 | 189.06 | 452.06 | 54.59 | 0.00 | 0.00 | 0.00 |
August | 265.63 | 70.31 | 195.32 | 538.12 | 81.04 | 0.00 | 0.00 | 0.00 |
September | 414.61 | 215.41 | 199.21 | 762.14 | 165.43 | 0.00 | 0.00 | 0.00 |
October | 563.34 | 380.85 | 182.49 | 888.15 | 261.88 | 0.00 | 0.00 | 0.00 |
November | 677.92 | 516.83 | 161.09 | 952.69 | 417.16 | 0.00 | 0.00 | 0.00 |
December | 671.85 | 504.32 | 167.53 | 890.05 | 505.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 443.83 | 256.47 | 187.36 | 694.97 | 259.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.42 | 12.97 | 159.00 | 428.04 | 54.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 677.92 | 516.83 | 210.18 | 952.69 | 505.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 655.96 | 496.95 | 159.00 | 889.31 | 463.09 | 0.00 | 0.00 | 0.00 |
February | 608.47 | 428.96 | 179.51 | 843.07 | 409.47 | 0.00 | 0.00 | 0.00 |
March | 494.51 | 285.13 | 209.38 | 712.85 | 352.68 | 0.00 | 0.00 | 0.00 |
April | 335.28 | 125.10 | 210.18 | 544.99 | 216.97 | 0.00 | 0.00 | 0.00 |
May | 236.94 | 33.16 | 203.78 | 428.04 | 127.91 | 0.00 | 0.00 | 0.00 |
June | 204.42 | 12.97 | 191.45 | 450.21 | 64.08 | 0.00 | 0.00 | 0.00 |
July | 208.38 | 19.32 | 189.06 | 452.06 | 54.59 | 0.00 | 0.00 | 0.00 |
August | 265.63 | 70.31 | 195.32 | 538.12 | 81.04 | 0.00 | 0.00 | 0.00 |
September | 414.61 | 215.41 | 199.21 | 762.14 | 165.43 | 0.00 | 0.00 | 0.00 |
October | 563.34 | 380.85 | 182.49 | 888.15 | 261.88 | 0.00 | 0.00 | 0.00 |
November | 677.92 | 516.83 | 161.09 | 952.69 | 417.16 | 0.00 | 0.00 | 0.00 |
December | 671.85 | 504.32 | 167.53 | 890.05 | 505.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 443.83 | 256.47 | 187.36 | 694.97 | 259.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.42 | 12.97 | 159.00 | 428.04 | 54.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 677.92 | 516.83 | 210.18 | 952.69 | 505.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 655.91 | 496.92 | 158.99 | 889.25 | 463.06 | 0.00 | 0.00 | 0.00 |
February | 608.43 | 428.94 | 179.50 | 843.02 | 409.44 | 0.00 | 0.00 | 0.00 |
March | 494.48 | 285.11 | 209.37 | 712.80 | 352.66 | 0.00 | 0.00 | 0.00 |
April | 335.26 | 125.09 | 210.17 | 544.96 | 216.96 | 0.00 | 0.00 | 0.00 |
May | 236.92 | 33.16 | 203.76 | 428.01 | 127.90 | 0.00 | 0.00 | 0.00 |
June | 204.41 | 12.97 | 191.44 | 450.18 | 64.08 | 0.00 | 0.00 | 0.00 |
July | 208.37 | 19.32 | 189.05 | 452.03 | 54.59 | 0.00 | 0.00 | 0.00 |
August | 265.61 | 70.31 | 195.30 | 538.08 | 81.04 | 0.00 | 0.00 | 0.00 |
September | 414.59 | 215.39 | 199.20 | 762.09 | 165.42 | 0.00 | 0.00 | 0.00 |
October | 563.30 | 380.83 | 182.47 | 888.09 | 261.86 | 0.00 | 0.00 | 0.00 |
November | 677.88 | 516.80 | 161.08 | 952.62 | 417.14 | 0.00 | 0.00 | 0.00 |
December | 671.81 | 504.29 | 167.52 | 889.99 | 505.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 443.80 | 256.45 | 187.35 | 694.92 | 259.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.41 | 12.97 | 158.99 | 428.01 | 54.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 677.88 | 516.80 | 210.17 | 952.62 | 505.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.76 | 292.72 | 227.05 | 580.31 | 916.84 | 0.00 | 0.00 | 0.00 |
February | 586.50 | 311.74 | 274.76 | 704.66 | 814.90 | 0.00 | 0.00 | 0.00 |
March | 799.23 | 428.36 | 370.87 | 1057.61 | 692.93 | 0.00 | 0.00 | 0.00 |
April | 918.65 | 496.18 | 422.47 | 1396.24 | 431.59 | 0.00 | 0.00 | 0.00 |
May | 989.47 | 529.41 | 460.06 | 1665.85 | 270.65 | 0.00 | 0.00 | 0.00 |
June | 963.18 | 517.33 | 445.85 | 1814.89 | 143.18 | 0.00 | 0.00 | 0.00 |
July | 854.75 | 424.74 | 430.01 | 1609.75 | 120.06 | 0.00 | 0.00 | 0.00 |
August | 827.78 | 421.87 | 405.91 | 1496.85 | 167.44 | 0.00 | 0.00 | 0.00 |
September | 846.54 | 471.60 | 374.93 | 1449.64 | 328.16 | 0.00 | 0.00 | 0.00 |
October | 728.73 | 425.31 | 303.42 | 1084.30 | 516.00 | 0.00 | 0.00 | 0.00 |
November | 611.66 | 372.44 | 239.23 | 752.43 | 844.64 | 0.00 | 0.00 | 0.00 |
December | 492.91 | 267.76 | 225.15 | 516.12 | 1023.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 762.23 | 413.56 | 348.67 | 1179.34 | 521.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 492.91 | 267.76 | 225.15 | 516.12 | 120.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.47 | 529.41 | 460.06 | 1814.89 | 1023.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.55 | 11.57 | 8.98 | 22.94 | 36.25 | 0.00 | 0.00 | 0.00 |
February | 23.19 | 12.33 | 10.86 | 27.86 | 32.22 | 0.00 | 0.00 | 0.00 |
March | 31.60 | 16.94 | 14.66 | 41.82 | 27.40 | 0.00 | 0.00 | 0.00 |
April | 36.32 | 19.62 | 16.70 | 55.21 | 17.06 | 0.00 | 0.00 | 0.00 |
May | 39.12 | 20.93 | 18.19 | 65.87 | 10.70 | 0.00 | 0.00 | 0.00 |
June | 38.08 | 20.45 | 17.63 | 71.76 | 5.66 | 0.00 | 0.00 | 0.00 |
July | 33.80 | 16.79 | 17.00 | 63.65 | 4.75 | 0.00 | 0.00 | 0.00 |
August | 32.73 | 16.68 | 16.05 | 59.18 | 6.62 | 0.00 | 0.00 | 0.00 |
September | 33.47 | 18.65 | 14.82 | 57.32 | 12.98 | 0.00 | 0.00 | 0.00 |
October | 28.81 | 16.82 | 12.00 | 42.87 | 20.40 | 0.00 | 0.00 | 0.00 |
November | 24.18 | 14.73 | 9.46 | 29.75 | 33.40 | 0.00 | 0.00 | 0.00 |
December | 19.49 | 10.59 | 8.90 | 20.41 | 40.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.14 | 16.35 | 13.79 | 46.63 | 20.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.49 | 10.59 | 8.90 | 20.41 | 4.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.12 | 20.93 | 18.19 | 71.76 | 40.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 287.66 | 0.00 | 287.66 | 67.28 | 1445.16 | 0.00 | 0.00 | 0.00 |
February | 351.27 | 0.00 | 351.27 | 162.64 | 1306.89 | 0.00 | 0.00 | 0.00 |
March | 459.70 | 0.00 | 459.70 | 323.24 | 1113.34 | 0.00 | 0.00 | 0.00 |
April | 530.77 | 4.18 | 526.59 | 611.41 | 659.62 | 0.00 | 0.00 | 0.00 |
May | 629.52 | 45.52 | 583.99 | 1016.05 | 386.11 | 0.00 | 0.00 | 0.00 |
June | 669.38 | 82.41 | 586.97 | 1407.65 | 206.84 | 0.00 | 0.00 | 0.00 |
July | 618.64 | 60.22 | 558.42 | 1293.60 | 165.79 | 0.00 | 0.00 | 0.00 |
August | 521.65 | 10.67 | 510.98 | 1007.27 | 225.85 | 0.00 | 0.00 | 0.00 |
September | 455.18 | 0.18 | 455.00 | 763.98 | 459.85 | 0.00 | 0.00 | 0.00 |
October | 377.93 | 0.00 | 377.93 | 397.17 | 747.59 | 0.00 | 0.00 | 0.00 |
November | 305.10 | 0.00 | 305.10 | 107.09 | 1273.56 | 0.00 | 0.00 | 0.00 |
December | 285.44 | 0.00 | 285.44 | 44.45 | 1600.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 458.21 | 17.02 | 441.19 | 602.41 | 796.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.44 | 0.00 | 285.44 | 44.45 | 165.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 669.38 | 82.41 | 586.97 | 1407.65 | 1600.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.94 | 278.25 | 234.69 | 500.13 | 897.54 | 0.00 | 0.00 | 0.00 |
February | 686.26 | 391.16 | 295.10 | 773.19 | 809.33 | 0.00 | 0.00 | 0.00 |
March | 847.31 | 466.84 | 380.47 | 1041.53 | 691.18 | 0.00 | 0.00 | 0.00 |
April | 1020.96 | 566.41 | 454.56 | 1486.75 | 419.56 | 0.00 | 0.00 | 0.00 |
May | 1053.58 | 572.58 | 481.00 | 1723.45 | 258.93 | 0.00 | 0.00 | 0.00 |
June | 1054.17 | 586.46 | 467.72 | 1941.27 | 136.76 | 0.00 | 0.00 | 0.00 |
July | 945.36 | 494.22 | 451.14 | 1746.22 | 111.73 | 0.00 | 0.00 | 0.00 |
August | 899.56 | 460.39 | 439.18 | 1602.90 | 150.87 | 0.00 | 0.00 | 0.00 |
September | 891.22 | 508.51 | 382.72 | 1484.18 | 290.24 | 0.00 | 0.00 | 0.00 |
October | 685.41 | 369.91 | 315.50 | 962.51 | 477.86 | 0.00 | 0.00 | 0.00 |
November | 614.41 | 357.69 | 256.72 | 677.07 | 786.40 | 0.00 | 0.00 | 0.00 |
December | 512.50 | 271.53 | 240.96 | 471.41 | 985.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 810.40 | 443.42 | 366.97 | 1202.25 | 499.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.50 | 271.53 | 234.69 | 471.41 | 111.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.17 | 586.46 | 481.00 | 1941.27 | 985.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1967.90 | 1490.89 | 477.01 | 2642.27 | 1338.37 | 0.00 | 0.00 | 0.00 |
February | 1825.45 | 1286.91 | 538.54 | 2489.80 | 1219.48 | 0.00 | 0.00 | 0.00 |
March | 1483.56 | 855.41 | 628.14 | 2084.92 | 1086.94 | 0.00 | 0.00 | 0.00 |
April | 1005.85 | 375.31 | 630.54 | 1594.76 | 687.29 | 0.00 | 0.00 | 0.00 |
May | 710.82 | 99.49 | 611.33 | 1251.69 | 413.53 | 0.00 | 0.00 | 0.00 |
June | 613.26 | 38.91 | 574.35 | 1330.11 | 212.01 | 0.00 | 0.00 | 0.00 |
July | 625.15 | 57.95 | 567.20 | 1344.92 | 172.25 | 0.00 | 0.00 | 0.00 |
August | 796.89 | 210.94 | 585.95 | 1613.44 | 238.75 | 0.00 | 0.00 | 0.00 |
September | 1243.86 | 646.23 | 597.63 | 2287.04 | 469.78 | 0.00 | 0.00 | 0.00 |
October | 1690.04 | 1142.58 | 547.46 | 2659.41 | 740.62 | 0.00 | 0.00 | 0.00 |
November | 2033.81 | 1550.53 | 483.28 | 2851.21 | 1176.25 | 0.00 | 0.00 | 0.00 |
December | 2015.58 | 1512.99 | 502.59 | 2653.89 | 1445.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1331.52 | 769.43 | 562.09 | 2064.04 | 764.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 613.26 | 38.91 | 477.01 | 1251.69 | 172.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2033.81 | 1550.53 | 630.54 | 2851.21 | 1445.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 540.32 | 304.29 | 236.03 | 595.12 | 943.24 | 0.00 | 0.00 | 0.00 |
February | 609.70 | 324.07 | 285.63 | 714.24 | 863.59 | 0.00 | 0.00 | 0.00 |
March | 830.84 | 445.30 | 385.54 | 1071.08 | 744.51 | 0.00 | 0.00 | 0.00 |
April | 954.99 | 515.80 | 439.18 | 1429.28 | 462.74 | 0.00 | 0.00 | 0.00 |
May | 1028.61 | 550.35 | 478.26 | 1713.72 | 288.23 | 0.00 | 0.00 | 0.00 |
June | 1001.27 | 537.79 | 463.48 | 1874.28 | 153.77 | 0.00 | 0.00 | 0.00 |
July | 888.56 | 441.54 | 447.02 | 1667.21 | 124.04 | 0.00 | 0.00 | 0.00 |
August | 860.52 | 438.56 | 421.97 | 1554.77 | 165.90 | 0.00 | 0.00 | 0.00 |
September | 880.02 | 490.26 | 389.76 | 1507.42 | 323.03 | 0.00 | 0.00 | 0.00 |
October | 757.55 | 442.13 | 315.42 | 1128.01 | 510.08 | 0.00 | 0.00 | 0.00 |
November | 635.85 | 387.17 | 248.69 | 783.08 | 836.48 | 0.00 | 0.00 | 0.00 |
December | 512.40 | 278.35 | 234.05 | 534.48 | 1033.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 792.38 | 429.92 | 362.46 | 1216.48 | 535.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 512.40 | 278.35 | 234.05 | 534.48 | 124.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1028.61 | 550.35 | 478.26 | 1874.28 | 1033.51 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.213380E+09 | 0.359674E+10 |
February | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.426623E+09 | 0.295668E+10 |
March | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.899837E+09 | 0.281055E+10 |
April | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.158906E+10 | 0.162889E+10 |
May | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.271013E+10 | 0.100375E+10 |
June | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.362112E+10 | 0.531059E+09 |
July | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.343058E+10 | 0.441547E+09 |
August | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.267521E+10 | 0.589158E+09 |
September | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.197219E+10 | 0.114591E+10 |
October | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.108540E+10 | 0.187826E+10 |
November | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.316912E+09 | 0.303371E+10 |
December | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.153056E+09 | 0.397785E+10 |
Annual Sum or Average | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.190935E+11 | 0.235941E+11 |
Minimum of Months | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.153056E+09 | 0.441547E+09 |
Maximum of Months | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.362112E+10 | 0.397785E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.138900E+10 | 0.223188E+10 |
February | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.191297E+10 | 0.183469E+10 |
March | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.282602E+10 | 0.175673E+10 |
April | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.386203E+10 | 0.104644E+10 |
May | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.461203E+10 | 0.673938E+09 |
June | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.501910E+10 | 0.349869E+09 |
July | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.466060E+10 | 0.296175E+09 |
August | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.428462E+10 | 0.393453E+09 |
September | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.384903E+10 | 0.726581E+09 |
October | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.259903E+10 | 0.120967E+10 |
November | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.180476E+10 | 0.188822E+10 |
December | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.132173E+10 | 0.244825E+10 |
Annual Sum or Average | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.381409E+11 | 0.148559E+11 |
Minimum of Months | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.132173E+10 | 0.296175E+09 |
Maximum of Months | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.501910E+10 | 0.244825E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.712997E+10 | 0.334850E+10 |
February | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.606463E+10 | 0.277283E+10 |
March | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.561318E+10 | 0.276148E+10 |
April | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.413040E+10 | 0.170348E+10 |
May | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.333538E+10 | 0.107059E+10 |
June | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.342039E+10 | 0.542322E+09 |
July | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.356708E+10 | 0.457200E+09 |
August | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.429511E+10 | 0.622487E+09 |
September | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.591357E+10 | 0.117367E+10 |
October | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.713591E+10 | 0.188128E+10 |
November | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.744751E+10 | 0.284489E+10 |
December | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.718495E+10 | 0.361560E+10 |
Annual Sum or Average | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.652381E+11 | 0.227943E+11 |
Minimum of Months | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.333538E+10 | 0.457200E+09 |
Maximum of Months | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.744751E+10 | 0.361560E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.161829E+10 | 0.235149E+10 |
February | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.174774E+10 | 0.195619E+10 |
March | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.288485E+10 | 0.188259E+10 |
April | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.370223E+10 | 0.114519E+10 |
May | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.457480E+10 | 0.746232E+09 |
June | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.483689E+10 | 0.393927E+09 |
July | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.444130E+10 | 0.329200E+09 |
August | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.414628E+10 | 0.433137E+09 |
September | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.389855E+10 | 0.806882E+09 |
October | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.303056E+10 | 0.128884E+10 |
November | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.205686E+10 | 0.200430E+10 |
December | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.146165E+10 | 0.257333E+10 |
Annual Sum or Average | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.384000E+11 | 0.159113E+11 |
Minimum of Months | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.146165E+10 | 0.329200E+09 |
Maximum of Months | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.483689E+10 | 0.257333E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256815E+09 | 0.00 | 0.256815E+09 | 65490480.28 | 0.127324E+10 |
February | 0.283250E+09 | 0.00 | 0.283250E+09 | 0.148955E+09 | 0.100457E+10 |
March | 0.410399E+09 | 0.00 | 0.410399E+09 | 0.326726E+09 | 0.924144E+09 |
April | 0.458566E+09 | 3612836.74 | 0.454953E+09 | 0.562662E+09 | 0.521838E+09 |
May | 0.562005E+09 | 40640821.64 | 0.521364E+09 | 0.935921E+09 | 0.317977E+09 |
June | 0.578319E+09 | 71197845.54 | 0.507121E+09 | 0.123732E+10 | 0.162426E+09 |
July | 0.552295E+09 | 53761700.40 | 0.498533E+09 | 0.116772E+10 | 0.139717E+09 |
August | 0.465705E+09 | 9522460.27 | 0.456183E+09 | 0.901968E+09 | 0.200471E+09 |
September | 0.393261E+09 | 156925.22 | 0.393104E+09 | 0.657937E+09 | 0.405123E+09 |
October | 0.337399E+09 | 0.00 | 0.337399E+09 | 0.353245E+09 | 0.682945E+09 |
November | 0.263594E+09 | 0.00 | 0.263594E+09 | 91235516.96 | 0.112376E+10 |
December | 0.254826E+09 | 0.00 | 0.254826E+09 | 39207139.38 | 0.144489E+10 |
Annual Sum or Average | 0.481644E+10 | 0.178893E+09 | 0.463754E+10 | 0.648839E+10 | 0.820110E+10 |
Minimum of Months | 0.254826E+09 | 0.00 | 0.254826E+09 | 39207139.38 | 0.139717E+09 |
Maximum of Months | 0.578319E+09 | 71197845.54 | 0.521364E+09 | 0.123732E+10 | 0.144489E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256826E+09 | 0.00 | 0.256826E+09 | 65491142.28 | 0.127332E+10 |
February | 0.283262E+09 | 0.00 | 0.283262E+09 | 0.148960E+09 | 0.100463E+10 |
March | 0.410417E+09 | 0.00 | 0.410417E+09 | 0.326739E+09 | 0.924197E+09 |
April | 0.458586E+09 | 3612933.85 | 0.454973E+09 | 0.562689E+09 | 0.521867E+09 |
May | 0.562029E+09 | 40641914.08 | 0.521387E+09 | 0.935965E+09 | 0.317992E+09 |
June | 0.578344E+09 | 71199759.36 | 0.507144E+09 | 0.123738E+10 | 0.162433E+09 |
July | 0.552318E+09 | 53763145.52 | 0.498555E+09 | 0.116778E+10 | 0.139723E+09 |
August | 0.465725E+09 | 9522716.23 | 0.456202E+09 | 0.902014E+09 | 0.200480E+09 |
September | 0.393278E+09 | 156929.44 | 0.393121E+09 | 0.657970E+09 | 0.405143E+09 |
October | 0.337414E+09 | 0.00 | 0.337414E+09 | 0.353261E+09 | 0.682983E+09 |
November | 0.263605E+09 | 0.00 | 0.263605E+09 | 91238457.46 | 0.112383E+10 |
December | 0.254837E+09 | 0.00 | 0.254837E+09 | 39207234.03 | 0.144497E+10 |
Annual Sum or Average | 0.481664E+10 | 0.178897E+09 | 0.463774E+10 | 0.648869E+10 | 0.820157E+10 |
Minimum of Months | 0.254837E+09 | 0.00 | 0.254837E+09 | 39207234.03 | 0.139723E+09 |
Maximum of Months | 0.578344E+09 | 71199759.36 | 0.521387E+09 | 0.123738E+10 | 0.144497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256826E+09 | 0.00 | 0.256826E+09 | 65491142.28 | 0.127332E+10 |
February | 0.283262E+09 | 0.00 | 0.283262E+09 | 0.148960E+09 | 0.100463E+10 |
March | 0.410417E+09 | 0.00 | 0.410417E+09 | 0.326739E+09 | 0.924197E+09 |
April | 0.458586E+09 | 3612933.85 | 0.454973E+09 | 0.562689E+09 | 0.521867E+09 |
May | 0.562029E+09 | 40641914.08 | 0.521387E+09 | 0.935965E+09 | 0.317992E+09 |
June | 0.578344E+09 | 71199759.36 | 0.507144E+09 | 0.123738E+10 | 0.162433E+09 |
July | 0.552318E+09 | 53763145.52 | 0.498555E+09 | 0.116778E+10 | 0.139723E+09 |
August | 0.465725E+09 | 9522716.23 | 0.456202E+09 | 0.902014E+09 | 0.200480E+09 |
September | 0.393278E+09 | 156929.44 | 0.393121E+09 | 0.657970E+09 | 0.405143E+09 |
October | 0.337414E+09 | 0.00 | 0.337414E+09 | 0.353261E+09 | 0.682983E+09 |
November | 0.263605E+09 | 0.00 | 0.263605E+09 | 91238457.46 | 0.112383E+10 |
December | 0.254837E+09 | 0.00 | 0.254837E+09 | 39207234.03 | 0.144497E+10 |
Annual Sum or Average | 0.481664E+10 | 0.178897E+09 | 0.463774E+10 | 0.648869E+10 | 0.820157E+10 |
Minimum of Months | 0.254837E+09 | 0.00 | 0.254837E+09 | 39207234.03 | 0.139723E+09 |
Maximum of Months | 0.578344E+09 | 71199759.36 | 0.521387E+09 | 0.123738E+10 | 0.144497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132158E+10 | 0.716905E+09 | 0.604671E+09 | 0.131513E+10 | 0.232788E+10 |
February | 0.159703E+10 | 0.910295E+09 | 0.686737E+09 | 0.184687E+10 | 0.185086E+10 |
March | 0.218308E+10 | 0.120280E+10 | 0.980276E+09 | 0.276263E+10 | 0.172150E+10 |
April | 0.254564E+10 | 0.141226E+10 | 0.113339E+10 | 0.377126E+10 | 0.101647E+10 |
May | 0.271453E+10 | 0.147524E+10 | 0.123929E+10 | 0.449502E+10 | 0.649175E+09 |
June | 0.262845E+10 | 0.146225E+10 | 0.116620E+10 | 0.488298E+10 | 0.328978E+09 |
July | 0.243571E+10 | 0.127334E+10 | 0.116237E+10 | 0.452597E+10 | 0.289062E+09 |
August | 0.231771E+10 | 0.118618E+10 | 0.113153E+10 | 0.414270E+10 | 0.405805E+09 |
September | 0.222215E+10 | 0.126790E+10 | 0.954257E+09 | 0.370674E+10 | 0.763578E+09 |
October | 0.176594E+10 | 0.953058E+09 | 0.812884E+09 | 0.248874E+10 | 0.128845E+10 |
November | 0.153195E+10 | 0.891847E+09 | 0.640099E+09 | 0.169015E+10 | 0.205021E+10 |
December | 0.132044E+10 | 0.699597E+09 | 0.620844E+09 | 0.121971E+10 | 0.261253E+10 |
Annual Sum or Average | 0.245842E+11 | 0.134517E+11 | 0.111325E+11 | 0.368479E+11 | 0.153045E+11 |
Minimum of Months | 0.132044E+10 | 0.699597E+09 | 0.604671E+09 | 0.121971E+10 | 0.289062E+09 |
Maximum of Months | 0.271453E+10 | 0.147524E+10 | 0.123929E+10 | 0.488298E+10 | 0.261253E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52253939.43 | 28345774.84 | 23908164.60 | 51999093.69 | 92042137.46 |
February | 63145188.07 | 35992234.95 | 27152953.12 | 73023615.88 | 73181326.19 |
March | 86316882.58 | 47557656.77 | 38759225.81 | 0.109232E+09 | 68066705.76 |
April | 0.100652E+09 | 55839413.91 | 44813068.32 | 0.149112E+09 | 40190409.33 |
May | 0.107330E+09 | 58329704.30 | 49000433.98 | 0.177729E+09 | 25667780.58 |
June | 0.103926E+09 | 57815999.01 | 46110385.16 | 0.193069E+09 | 13007481.13 |
July | 96305959.35 | 50346885.37 | 45959073.97 | 0.178953E+09 | 11429237.46 |
August | 91640328.22 | 46900482.29 | 44739845.93 | 0.163799E+09 | 16045149.85 |
September | 87861929.88 | 50131455.55 | 37730474.33 | 0.146561E+09 | 30191173.91 |
October | 69823766.24 | 37683058.67 | 32140707.57 | 98402604.68 | 50944228.58 |
November | 60571756.71 | 35262809.25 | 25308947.46 | 66826855.14 | 81063477.48 |
December | 52209059.66 | 27661427.61 | 24547632.05 | 48226287.52 | 0.103297E+09 |
Annual Sum or Average | 0.972038E+09 | 0.531867E+09 | 0.440171E+09 | 0.145693E+10 | 0.605126E+09 |
Minimum of Months | 52209059.66 | 27661427.61 | 23908164.60 | 48226287.52 | 11429237.46 |
Maximum of Months | 0.107330E+09 | 58329704.30 | 49000433.98 | 0.193069E+09 | 0.103297E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175691E+10 | 0.133104E+10 | 0.425871E+09 | 0.238192E+10 | 0.124035E+10 |
February | 0.147202E+10 | 0.103775E+10 | 0.434271E+09 | 0.203956E+10 | 0.990587E+09 |
March | 0.132450E+10 | 0.763698E+09 | 0.560800E+09 | 0.190930E+10 | 0.944623E+09 |
April | 0.869040E+09 | 0.324258E+09 | 0.544783E+09 | 0.141263E+10 | 0.562396E+09 |
May | 0.634616E+09 | 88824167.27 | 0.545792E+09 | 0.114645E+10 | 0.342583E+09 |
June | 0.529854E+09 | 33618785.83 | 0.496235E+09 | 0.116694E+10 | 0.166108E+09 |
July | 0.558130E+09 | 51738867.55 | 0.506391E+09 | 0.121079E+10 | 0.146222E+09 |
August | 0.711459E+09 | 0.188326E+09 | 0.523134E+09 | 0.144129E+10 | 0.217058E+09 |
September | 0.107468E+10 | 0.558330E+09 | 0.516350E+09 | 0.197547E+10 | 0.428804E+09 |
October | 0.150884E+10 | 0.102007E+10 | 0.488768E+09 | 0.237882E+10 | 0.701418E+09 |
November | 0.175718E+10 | 0.133963E+10 | 0.417549E+09 | 0.246936E+10 | 0.108129E+10 |
December | 0.179948E+10 | 0.135077E+10 | 0.448711E+09 | 0.238391E+10 | 0.135319E+10 |
Annual Sum or Average | 0.139967E+11 | 0.808805E+10 | 0.590865E+10 | 0.219164E+11 | 0.817463E+10 |
Minimum of Months | 0.529854E+09 | 33618785.83 | 0.417549E+09 | 0.114645E+10 | 0.146222E+09 |
Maximum of Months | 0.179948E+10 | 0.135077E+10 | 0.560800E+09 | 0.246936E+10 | 0.135319E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175691E+10 | 0.133104E+10 | 0.425871E+09 | 0.238192E+10 | 0.124035E+10 |
February | 0.147202E+10 | 0.103775E+10 | 0.434271E+09 | 0.203956E+10 | 0.990587E+09 |
March | 0.132450E+10 | 0.763698E+09 | 0.560800E+09 | 0.190930E+10 | 0.944623E+09 |
April | 0.869040E+09 | 0.324258E+09 | 0.544783E+09 | 0.141263E+10 | 0.562396E+09 |
May | 0.634616E+09 | 88824167.27 | 0.545792E+09 | 0.114645E+10 | 0.342583E+09 |
June | 0.529854E+09 | 33618785.83 | 0.496235E+09 | 0.116694E+10 | 0.166108E+09 |
July | 0.558130E+09 | 51738867.55 | 0.506391E+09 | 0.121079E+10 | 0.146222E+09 |
August | 0.711459E+09 | 0.188326E+09 | 0.523134E+09 | 0.144129E+10 | 0.217058E+09 |
September | 0.107468E+10 | 0.558330E+09 | 0.516350E+09 | 0.197547E+10 | 0.428804E+09 |
October | 0.150884E+10 | 0.102007E+10 | 0.488768E+09 | 0.237882E+10 | 0.701418E+09 |
November | 0.175718E+10 | 0.133963E+10 | 0.417549E+09 | 0.246936E+10 | 0.108129E+10 |
December | 0.179948E+10 | 0.135077E+10 | 0.448711E+09 | 0.238391E+10 | 0.135319E+10 |
Annual Sum or Average | 0.139967E+11 | 0.808805E+10 | 0.590865E+10 | 0.219164E+11 | 0.817463E+10 |
Minimum of Months | 0.529854E+09 | 33618785.83 | 0.417549E+09 | 0.114645E+10 | 0.146222E+09 |
Maximum of Months | 0.179948E+10 | 0.135077E+10 | 0.560800E+09 | 0.246936E+10 | 0.135319E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.175680E+10 | 0.133096E+10 | 0.425844E+09 | 0.238176E+10 | 0.124027E+10 |
February | 0.147192E+10 | 0.103768E+10 | 0.434243E+09 | 0.203943E+10 | 0.990524E+09 |
March | 0.132441E+10 | 0.763650E+09 | 0.560765E+09 | 0.190918E+10 | 0.944563E+09 |
April | 0.868986E+09 | 0.324237E+09 | 0.544748E+09 | 0.141254E+10 | 0.562360E+09 |
May | 0.634576E+09 | 88818554.08 | 0.545757E+09 | 0.114638E+10 | 0.342561E+09 |
June | 0.529820E+09 | 33616661.31 | 0.496203E+09 | 0.116687E+10 | 0.166097E+09 |
July | 0.558095E+09 | 51735597.94 | 0.506359E+09 | 0.121071E+10 | 0.146213E+09 |
August | 0.711414E+09 | 0.188314E+09 | 0.523101E+09 | 0.144120E+10 | 0.217044E+09 |
September | 0.107461E+10 | 0.558295E+09 | 0.516317E+09 | 0.197535E+10 | 0.428777E+09 |
October | 0.150875E+10 | 0.102001E+10 | 0.488737E+09 | 0.237867E+10 | 0.701374E+09 |
November | 0.175707E+10 | 0.133954E+10 | 0.417523E+09 | 0.246920E+10 | 0.108122E+10 |
December | 0.179936E+10 | 0.135068E+10 | 0.448683E+09 | 0.238376E+10 | 0.135310E+10 |
Annual Sum or Average | 0.139958E+11 | 0.808754E+10 | 0.590828E+10 | 0.219150E+11 | 0.817411E+10 |
Minimum of Months | 0.529820E+09 | 33616661.31 | 0.417523E+09 | 0.114638E+10 | 0.146213E+09 |
Maximum of Months | 0.179936E+10 | 0.135068E+10 | 0.560765E+09 | 0.246920E+10 | 0.135310E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139214E+10 | 0.784009E+09 | 0.608127E+09 | 0.155430E+10 | 0.245567E+10 |
February | 0.141886E+10 | 0.754152E+09 | 0.664708E+09 | 0.170472E+10 | 0.197142E+10 |
March | 0.214066E+10 | 0.114732E+10 | 0.993344E+09 | 0.283271E+10 | 0.185593E+10 |
April | 0.238114E+10 | 0.128609E+10 | 0.109505E+10 | 0.361904E+10 | 0.111869E+10 |
May | 0.265021E+10 | 0.141798E+10 | 0.123223E+10 | 0.446182E+10 | 0.724915E+09 |
June | 0.249655E+10 | 0.134092E+10 | 0.115563E+10 | 0.470421E+10 | 0.371124E+09 |
July | 0.228937E+10 | 0.113763E+10 | 0.115174E+10 | 0.431155E+10 | 0.321572E+09 |
August | 0.221713E+10 | 0.112993E+10 | 0.108720E+10 | 0.400916E+10 | 0.448467E+09 |
September | 0.219422E+10 | 0.122240E+10 | 0.971823E+09 | 0.375747E+10 | 0.850603E+09 |
October | 0.195183E+10 | 0.113915E+10 | 0.812681E+09 | 0.290418E+10 | 0.138205E+10 |
November | 0.158542E+10 | 0.965352E+09 | 0.620073E+09 | 0.195029E+10 | 0.218931E+10 |
December | 0.132021E+10 | 0.717177E+09 | 0.603031E+09 | 0.138238E+10 | 0.274111E+10 |
Annual Sum or Average | 0.240377E+11 | 0.130421E+11 | 0.109956E+11 | 0.371918E+11 | 0.164309E+11 |
Minimum of Months | 0.132021E+10 | 0.717177E+09 | 0.603031E+09 | 0.138238E+10 | 0.321572E+09 |
Maximum of Months | 0.265021E+10 | 0.141798E+10 | 0.123223E+10 | 0.470421E+10 | 0.274111E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55043652.16 | 30998916.52 | 24044735.65 | 61455365.10 | 97095047.78 |
February | 56100331.70 | 29818412.78 | 26281918.92 | 67402684.45 | 77947973.41 |
March | 84639537.56 | 45363691.56 | 39275846.00 | 0.112002E+09 | 73381899.14 |
April | 94147963.31 | 50850793.02 | 43297170.29 | 0.143093E+09 | 44232035.79 |
May | 0.104787E+09 | 56065315.14 | 48721237.05 | 0.176416E+09 | 28662448.59 |
June | 98711231.61 | 53018552.09 | 45692679.53 | 0.186000E+09 | 14673901.54 |
July | 90519227.34 | 44980594.47 | 45538632.87 | 0.170474E+09 | 12714656.34 |
August | 87663231.67 | 44676354.54 | 42986877.13 | 0.158518E+09 | 17731939.70 |
September | 86757331.28 | 48332410.25 | 38424921.03 | 0.148566E+09 | 33632063.75 |
October | 77173295.13 | 45040704.96 | 32132590.17 | 0.114828E+09 | 54644992.72 |
November | 62686080.96 | 38169018.84 | 24517062.12 | 77112426.96 | 86563145.35 |
December | 52199668.42 | 28356436.57 | 23843231.85 | 54657982.63 | 0.108381E+09 |
Annual Sum or Average | 0.950428E+09 | 0.515671E+09 | 0.434757E+09 | 0.147053E+10 | 0.649661E+09 |
Minimum of Months | 52199668.42 | 28356436.57 | 23843231.85 | 54657982.63 | 12714656.34 |
Maximum of Months | 0.104787E+09 | 56065315.14 | 48721237.05 | 0.186000E+09 | 0.108381E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.180201E+09 | 0.387073E+10 |
February | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.393449E+09 | 0.316163E+10 |
March | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.865762E+09 | 0.298198E+10 |
April | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.158478E+10 | 0.170974E+10 |
May | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.272140E+10 | 0.103416E+10 |
June | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.364863E+10 | 0.536133E+09 |
July | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.346478E+10 | 0.444057E+09 |
August | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.269787E+10 | 0.604917E+09 |
September | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.198024E+10 | 0.119194E+10 |
October | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.106378E+10 | 0.200236E+10 |
November | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.277580E+09 | 0.330107E+10 |
December | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.119046E+09 | 0.428789E+10 |
Annual Sum or Average | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.189975E+11 | 0.251266E+11 |
Minimum of Months | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.119046E+09 | 0.444057E+09 |
Maximum of Months | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.364863E+10 | 0.428789E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.133956E+10 | 0.240396E+10 |
February | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.187050E+10 | 0.195794E+10 |
March | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.278963E+10 | 0.185126E+10 |
April | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.385366E+10 | 0.108749E+10 |
May | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.461609E+10 | 0.693506E+09 |
June | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.503177E+10 | 0.354478E+09 |
July | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.467708E+10 | 0.299265E+09 |
August | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.429321E+10 | 0.404101E+09 |
September | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.384700E+10 | 0.752306E+09 |
October | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.257797E+10 | 0.127989E+10 |
November | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.175496E+10 | 0.203836E+10 |
December | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.126261E+10 | 0.263996E+10 |
Annual Sum or Average | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.379140E+11 | 0.157625E+11 |
Minimum of Months | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.126261E+10 | 0.299265E+09 |
Maximum of Months | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.503177E+10 | 0.263996E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.707706E+10 | 0.358469E+10 |
February | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.602331E+10 | 0.295017E+10 |
March | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.558424E+10 | 0.291126E+10 |
April | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.413361E+10 | 0.178147E+10 |
May | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.335253E+10 | 0.110759E+10 |
June | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.344765E+10 | 0.549517E+09 |
July | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.360224E+10 | 0.461356E+09 |
August | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.432145E+10 | 0.639455E+09 |
September | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.592801E+10 | 0.121766E+10 |
October | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.712295E+10 | 0.198369E+10 |
November | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.739034E+10 | 0.304883E+10 |
December | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.710819E+10 | 0.387281E+10 |
Annual Sum or Average | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.650916E+11 | 0.241085E+11 |
Minimum of Months | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.335253E+10 | 0.461356E+09 |
Maximum of Months | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.739034E+10 | 0.387281E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.159398E+10 | 0.252638E+10 |
February | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.172789E+10 | 0.208920E+10 |
March | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.286878E+10 | 0.199409E+10 |
April | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.370469E+10 | 0.119942E+10 |
May | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.459002E+10 | 0.772001E+09 |
June | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.485814E+10 | 0.398572E+09 |
July | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.446547E+10 | 0.332232E+09 |
August | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.416430E+10 | 0.444350E+09 |
September | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.390723E+10 | 0.837299E+09 |
October | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.302126E+10 | 0.136620E+10 |
November | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.202975E+10 | 0.216816E+10 |
December | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.143154E+10 | 0.276815E+10 |
Annual Sum or Average | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.383630E+11 | 0.168961E+11 |
Minimum of Months | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.143154E+10 | 0.332232E+09 |
Maximum of Months | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.485814E+10 | 0.276815E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 79.67 | 1342.87 | 287.66 | 0.00 | 287.66 | 0.00 | 0.00 |
February | 176.35 | 1222.17 | 351.27 | 0.00 | 351.27 | 0.00 | 0.00 |
March | 335.96 | 1049.34 | 459.70 | 0.00 | 459.70 | 0.00 | 0.00 |
April | 613.06 | 628.43 | 530.77 | 4.18 | 526.59 | 0.00 | 0.00 |
May | 1011.85 | 374.76 | 629.52 | 45.52 | 583.99 | 0.00 | 0.00 |
June | 1397.04 | 204.88 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
July | 1280.83 | 164.85 | 618.64 | 60.22 | 558.42 | 0.00 | 0.00 |
August | 998.81 | 219.97 | 521.65 | 10.67 | 510.98 | 0.00 | 0.00 |
September | 760.87 | 442.10 | 455.18 | 0.18 | 455.00 | 0.00 | 0.00 |
October | 405.24 | 701.26 | 377.93 | 0.00 | 377.93 | 0.00 | 0.00 |
November | 122.27 | 1170.41 | 305.10 | 0.00 | 305.10 | 0.00 | 0.00 |
December | 57.14 | 1485.16 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Annual Sum or Average | 605.45 | 748.16 | 458.21 | 17.02 | 441.19 | 0.00 | 0.00 |
Minimum of Months | 57.14 | 164.85 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Maximum of Months | 1397.04 | 1485.16 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 518.59 | 833.29 | 512.94 | 278.25 | 234.69 | 0.00 | 0.00 |
February | 790.75 | 758.39 | 686.26 | 391.16 | 295.10 | 0.00 | 0.00 |
March | 1055.11 | 655.89 | 847.31 | 466.84 | 380.47 | 0.00 | 0.00 |
April | 1489.98 | 403.72 | 1020.96 | 566.41 | 454.56 | 0.00 | 0.00 |
May | 1721.93 | 251.62 | 1053.58 | 572.58 | 481.00 | 0.00 | 0.00 |
June | 1936.38 | 134.98 | 1054.17 | 586.46 | 467.72 | 0.00 | 0.00 |
July | 1740.07 | 110.58 | 945.36 | 494.22 | 451.14 | 0.00 | 0.00 |
August | 1599.70 | 146.90 | 899.56 | 460.39 | 439.18 | 0.00 | 0.00 |
September | 1484.97 | 280.32 | 891.22 | 508.51 | 382.72 | 0.00 | 0.00 |
October | 970.37 | 451.64 | 685.41 | 369.91 | 315.50 | 0.00 | 0.00 |
November | 696.28 | 728.48 | 614.41 | 357.69 | 256.72 | 0.00 | 0.00 |
December | 493.48 | 914.07 | 512.50 | 271.53 | 240.96 | 0.00 | 0.00 |
Annual Sum or Average | 1209.44 | 471.08 | 810.40 | 443.42 | 366.97 | 0.00 | 0.00 |
Minimum of Months | 493.48 | 110.58 | 512.50 | 271.53 | 234.69 | 0.00 | 0.00 |
Maximum of Months | 1936.38 | 914.07 | 1054.17 | 586.46 | 481.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2662.03 | 1250.19 | 1967.90 | 1490.89 | 477.01 | 0.00 | 0.00 |
February | 2506.87 | 1146.18 | 1825.45 | 1286.91 | 538.54 | 0.00 | 0.00 |
March | 2095.72 | 1031.02 | 1483.56 | 855.41 | 628.14 | 0.00 | 0.00 |
April | 1593.52 | 657.21 | 1005.85 | 375.31 | 630.54 | 0.00 | 0.00 |
May | 1245.29 | 399.71 | 710.82 | 99.49 | 611.33 | 0.00 | 0.00 |
June | 1319.59 | 209.23 | 613.26 | 38.91 | 574.35 | 0.00 | 0.00 |
July | 1331.80 | 170.70 | 625.15 | 57.95 | 567.20 | 0.00 | 0.00 |
August | 1603.61 | 232.41 | 796.89 | 210.94 | 585.95 | 0.00 | 0.00 |
September | 2281.47 | 452.80 | 1243.86 | 646.23 | 597.63 | 0.00 | 0.00 |
October | 2664.24 | 702.39 | 1690.04 | 1142.58 | 547.46 | 0.00 | 0.00 |
November | 2873.27 | 1097.56 | 2033.81 | 1550.53 | 483.28 | 0.00 | 0.00 |
December | 2682.55 | 1349.91 | 2015.58 | 1512.99 | 502.59 | 0.00 | 0.00 |
Annual Sum or Average | 2068.69 | 722.80 | 1331.52 | 769.43 | 562.09 | 0.00 | 0.00 |
Minimum of Months | 1245.29 | 170.70 | 613.26 | 38.91 | 477.01 | 0.00 | 0.00 |
Maximum of Months | 2873.27 | 1349.91 | 2033.81 | 1550.53 | 630.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 604.20 | 877.95 | 540.32 | 304.29 | 236.03 | 0.00 | 0.00 |
February | 722.44 | 808.61 | 609.70 | 324.07 | 285.63 | 0.00 | 0.00 |
March | 1077.08 | 702.88 | 830.84 | 445.30 | 385.54 | 0.00 | 0.00 |
April | 1428.33 | 441.82 | 954.99 | 515.80 | 439.18 | 0.00 | 0.00 |
May | 1708.03 | 278.61 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
June | 1866.08 | 151.98 | 1001.27 | 537.79 | 463.48 | 0.00 | 0.00 |
July | 1658.19 | 122.91 | 888.56 | 441.54 | 447.02 | 0.00 | 0.00 |
August | 1548.04 | 161.71 | 860.52 | 438.56 | 421.97 | 0.00 | 0.00 |
September | 1504.07 | 311.30 | 880.02 | 490.26 | 389.76 | 0.00 | 0.00 |
October | 1131.48 | 481.20 | 757.55 | 442.13 | 315.42 | 0.00 | 0.00 |
November | 793.54 | 773.27 | 635.85 | 387.17 | 248.69 | 0.00 | 0.00 |
December | 545.72 | 960.77 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Annual Sum or Average | 1217.66 | 504.54 | 792.38 | 429.92 | 362.46 | 0.00 | 0.00 |
Minimum of Months | 545.72 | 122.91 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Maximum of Months | 1866.08 | 960.77 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 73.35 | 1426.18 | 287.66 | 0.00 | 287.66 | 0.00 | 0.00 |
February | 184.72 | 1245.79 | 351.26 | 0.00 | 351.26 | 0.00 | 0.00 |
March | 365.97 | 1035.15 | 459.69 | 0.00 | 459.69 | 0.00 | 0.00 |
April | 651.25 | 604.00 | 530.76 | 4.18 | 526.58 | 0.00 | 0.00 |
May | 1048.33 | 356.17 | 629.50 | 45.52 | 583.98 | 0.00 | 0.00 |
June | 1432.13 | 188.00 | 669.37 | 82.41 | 586.96 | 0.00 | 0.00 |
July | 1307.97 | 156.50 | 618.63 | 60.22 | 558.41 | 0.00 | 0.00 |
August | 1010.30 | 224.55 | 521.64 | 10.67 | 510.97 | 0.00 | 0.00 |
September | 761.53 | 468.91 | 455.18 | 0.18 | 454.99 | 0.00 | 0.00 |
October | 395.67 | 764.98 | 377.92 | 0.00 | 377.92 | 0.00 | 0.00 |
November | 105.60 | 1300.71 | 305.09 | 0.00 | 305.09 | 0.00 | 0.00 |
December | 43.91 | 1618.44 | 285.43 | 0.00 | 285.43 | 0.00 | 0.00 |
Annual Sum or Average | 617.26 | 780.20 | 458.20 | 17.02 | 441.18 | 0.00 | 0.00 |
Minimum of Months | 43.91 | 156.50 | 285.43 | 0.00 | 285.43 | 0.00 | 0.00 |
Maximum of Months | 1432.13 | 1618.44 | 669.37 | 82.41 | 586.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 510.43 | 903.49 | 512.93 | 278.24 | 234.68 | 0.00 | 0.00 |
February | 793.61 | 795.32 | 686.25 | 391.16 | 295.09 | 0.00 | 0.00 |
March | 1072.23 | 668.15 | 847.29 | 466.83 | 380.46 | 0.00 | 0.00 |
April | 1512.49 | 407.66 | 1020.95 | 566.40 | 454.55 | 0.00 | 0.00 |
May | 1744.61 | 251.96 | 1053.56 | 572.57 | 480.99 | 0.00 | 0.00 |
June | 1958.35 | 131.94 | 1054.16 | 586.44 | 467.71 | 0.00 | 0.00 |
July | 1756.62 | 112.19 | 945.35 | 494.21 | 451.14 | 0.00 | 0.00 |
August | 1607.86 | 157.50 | 899.55 | 460.38 | 439.17 | 0.00 | 0.00 |
September | 1486.61 | 306.24 | 891.21 | 508.50 | 382.71 | 0.00 | 0.00 |
October | 965.93 | 500.07 | 685.40 | 369.90 | 315.50 | 0.00 | 0.00 |
November | 677.84 | 822.25 | 614.40 | 357.68 | 256.72 | 0.00 | 0.00 |
December | 473.39 | 1013.97 | 512.49 | 271.53 | 240.96 | 0.00 | 0.00 |
Annual Sum or Average | 1214.64 | 504.49 | 810.38 | 443.42 | 366.97 | 0.00 | 0.00 |
Minimum of Months | 473.39 | 112.19 | 512.49 | 271.53 | 234.68 | 0.00 | 0.00 |
Maximum of Months | 1958.35 | 1013.97 | 1054.16 | 586.44 | 480.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2667.86 | 1389.25 | 1967.83 | 1490.83 | 477.00 | 0.00 | 0.00 |
February | 2529.16 | 1228.38 | 1825.38 | 1286.86 | 538.52 | 0.00 | 0.00 |
March | 2138.50 | 1058.02 | 1483.50 | 855.38 | 628.12 | 0.00 | 0.00 |
April | 1634.95 | 650.91 | 1005.81 | 375.29 | 630.52 | 0.00 | 0.00 |
May | 1284.08 | 383.71 | 710.80 | 99.49 | 611.31 | 0.00 | 0.00 |
June | 1350.60 | 192.25 | 613.24 | 38.91 | 574.33 | 0.00 | 0.00 |
July | 1356.14 | 163.78 | 625.13 | 57.95 | 567.18 | 0.00 | 0.00 |
August | 1614.32 | 243.12 | 796.87 | 210.93 | 585.93 | 0.00 | 0.00 |
September | 2286.38 | 496.29 | 1243.82 | 646.20 | 597.61 | 0.00 | 0.00 |
October | 2664.39 | 785.62 | 1689.98 | 1142.53 | 547.44 | 0.00 | 0.00 |
November | 2857.99 | 1251.46 | 2033.73 | 1550.46 | 483.26 | 0.00 | 0.00 |
December | 2670.10 | 1515.64 | 2015.50 | 1512.92 | 502.58 | 0.00 | 0.00 |
Annual Sum or Average | 2084.85 | 777.63 | 1331.47 | 769.40 | 562.07 | 0.00 | 0.00 |
Minimum of Months | 1284.08 | 163.78 | 613.24 | 38.91 | 477.00 | 0.00 | 0.00 |
Maximum of Months | 2857.99 | 1515.64 | 2033.73 | 1550.46 | 630.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 603.25 | 953.09 | 540.31 | 304.29 | 236.03 | 0.00 | 0.00 |
February | 732.52 | 847.12 | 609.69 | 324.06 | 285.63 | 0.00 | 0.00 |
March | 1099.43 | 720.32 | 830.83 | 445.30 | 385.54 | 0.00 | 0.00 |
April | 1451.44 | 448.66 | 954.97 | 515.80 | 439.18 | 0.00 | 0.00 |
May | 1731.72 | 281.35 | 1028.60 | 550.34 | 478.25 | 0.00 | 0.00 |
June | 1886.65 | 148.84 | 1001.26 | 537.78 | 463.48 | 0.00 | 0.00 |
July | 1673.40 | 124.81 | 888.55 | 441.54 | 447.01 | 0.00 | 0.00 |
August | 1556.03 | 174.06 | 860.51 | 438.55 | 421.96 | 0.00 | 0.00 |
September | 1506.96 | 341.14 | 880.01 | 490.25 | 389.76 | 0.00 | 0.00 |
October | 1127.17 | 536.40 | 757.54 | 442.13 | 315.42 | 0.00 | 0.00 |
November | 782.18 | 878.04 | 635.85 | 387.16 | 248.68 | 0.00 | 0.00 |
December | 536.53 | 1063.88 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Annual Sum or Average | 1225.98 | 541.62 | 792.37 | 429.91 | 362.46 | 0.00 | 0.00 |
Minimum of Months | 536.53 | 124.81 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Maximum of Months | 1886.65 | 1063.88 | 1028.60 | 550.34 | 478.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.28 | 1445.16 | 287.66 | 0.00 | 287.66 | 0.00 | 0.00 |
February | 162.64 | 1306.89 | 351.27 | 0.00 | 351.27 | 0.00 | 0.00 |
March | 323.24 | 1113.34 | 459.70 | 0.00 | 459.70 | 0.00 | 0.00 |
April | 611.41 | 659.62 | 530.77 | 4.18 | 526.59 | 0.00 | 0.00 |
May | 1016.05 | 386.11 | 629.52 | 45.52 | 583.99 | 0.00 | 0.00 |
June | 1407.65 | 206.84 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
July | 1293.60 | 165.79 | 618.64 | 60.22 | 558.42 | 0.00 | 0.00 |
August | 1007.27 | 225.85 | 521.65 | 10.67 | 510.98 | 0.00 | 0.00 |
September | 763.98 | 459.85 | 455.18 | 0.18 | 455.00 | 0.00 | 0.00 |
October | 397.17 | 747.59 | 377.93 | 0.00 | 377.93 | 0.00 | 0.00 |
November | 107.09 | 1273.56 | 305.10 | 0.00 | 305.10 | 0.00 | 0.00 |
December | 44.45 | 1600.91 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Annual Sum or Average | 602.41 | 796.76 | 458.21 | 17.02 | 441.19 | 0.00 | 0.00 |
Minimum of Months | 44.45 | 165.79 | 285.44 | 0.00 | 285.44 | 0.00 | 0.00 |
Maximum of Months | 1407.65 | 1600.91 | 669.38 | 82.41 | 586.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 500.13 | 897.54 | 512.94 | 278.25 | 234.69 | 0.00 | 0.00 |
February | 773.19 | 809.33 | 686.26 | 391.16 | 295.10 | 0.00 | 0.00 |
March | 1041.53 | 691.18 | 847.31 | 466.84 | 380.47 | 0.00 | 0.00 |
April | 1486.75 | 419.56 | 1020.96 | 566.41 | 454.56 | 0.00 | 0.00 |
May | 1723.45 | 258.93 | 1053.58 | 572.58 | 481.00 | 0.00 | 0.00 |
June | 1941.27 | 136.76 | 1054.17 | 586.46 | 467.72 | 0.00 | 0.00 |
July | 1746.22 | 111.73 | 945.36 | 494.22 | 451.14 | 0.00 | 0.00 |
August | 1602.90 | 150.87 | 899.56 | 460.39 | 439.18 | 0.00 | 0.00 |
September | 1484.18 | 290.24 | 891.22 | 508.51 | 382.72 | 0.00 | 0.00 |
October | 962.51 | 477.86 | 685.41 | 369.91 | 315.50 | 0.00 | 0.00 |
November | 677.07 | 786.40 | 614.41 | 357.69 | 256.72 | 0.00 | 0.00 |
December | 471.41 | 985.65 | 512.50 | 271.53 | 240.96 | 0.00 | 0.00 |
Annual Sum or Average | 1202.25 | 499.83 | 810.40 | 443.42 | 366.97 | 0.00 | 0.00 |
Minimum of Months | 471.41 | 111.73 | 512.50 | 271.53 | 234.69 | 0.00 | 0.00 |
Maximum of Months | 1941.27 | 985.65 | 1054.17 | 586.46 | 481.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2642.27 | 1338.37 | 1967.90 | 1490.89 | 477.01 | 0.00 | 0.00 |
February | 2489.80 | 1219.48 | 1825.45 | 1286.91 | 538.54 | 0.00 | 0.00 |
March | 2084.92 | 1086.94 | 1483.56 | 855.41 | 628.14 | 0.00 | 0.00 |
April | 1594.76 | 687.29 | 1005.85 | 375.31 | 630.54 | 0.00 | 0.00 |
May | 1251.69 | 413.53 | 710.82 | 99.49 | 611.33 | 0.00 | 0.00 |
June | 1330.11 | 212.01 | 613.26 | 38.91 | 574.35 | 0.00 | 0.00 |
July | 1344.92 | 172.25 | 625.15 | 57.95 | 567.20 | 0.00 | 0.00 |
August | 1613.44 | 238.75 | 796.89 | 210.94 | 585.95 | 0.00 | 0.00 |
September | 2287.04 | 469.78 | 1243.86 | 646.23 | 597.63 | 0.00 | 0.00 |
October | 2659.41 | 740.62 | 1690.04 | 1142.58 | 547.46 | 0.00 | 0.00 |
November | 2851.21 | 1176.25 | 2033.81 | 1550.53 | 483.28 | 0.00 | 0.00 |
December | 2653.89 | 1445.94 | 2015.58 | 1512.99 | 502.59 | 0.00 | 0.00 |
Annual Sum or Average | 2064.04 | 764.48 | 1331.52 | 769.43 | 562.09 | 0.00 | 0.00 |
Minimum of Months | 1251.69 | 172.25 | 613.26 | 38.91 | 477.01 | 0.00 | 0.00 |
Maximum of Months | 2851.21 | 1445.94 | 2033.81 | 1550.53 | 630.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 595.12 | 943.24 | 540.32 | 304.29 | 236.03 | 0.00 | 0.00 |
February | 714.24 | 863.59 | 609.70 | 324.07 | 285.63 | 0.00 | 0.00 |
March | 1071.08 | 744.51 | 830.84 | 445.30 | 385.54 | 0.00 | 0.00 |
April | 1429.28 | 462.74 | 954.99 | 515.80 | 439.18 | 0.00 | 0.00 |
May | 1713.72 | 288.23 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
June | 1874.28 | 153.77 | 1001.27 | 537.79 | 463.48 | 0.00 | 0.00 |
July | 1667.21 | 124.04 | 888.56 | 441.54 | 447.02 | 0.00 | 0.00 |
August | 1554.77 | 165.90 | 860.52 | 438.56 | 421.97 | 0.00 | 0.00 |
September | 1507.42 | 323.03 | 880.02 | 490.26 | 389.76 | 0.00 | 0.00 |
October | 1128.01 | 510.08 | 757.55 | 442.13 | 315.42 | 0.00 | 0.00 |
November | 783.08 | 836.48 | 635.85 | 387.17 | 248.69 | 0.00 | 0.00 |
December | 534.48 | 1033.51 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Annual Sum or Average | 1216.48 | 535.77 | 792.38 | 429.92 | 362.46 | 0.00 | 0.00 |
Minimum of Months | 534.48 | 124.04 | 512.40 | 278.35 | 234.05 | 0.00 | 0.00 |
Maximum of Months | 1874.28 | 1033.51 | 1028.61 | 550.35 | 478.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.213380E+09 | 0.359674E+10 | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.00 | 0.00 |
February | 0.426623E+09 | 0.295668E+10 | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.00 | 0.00 |
March | 0.899837E+09 | 0.281055E+10 | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.00 | 0.00 |
April | 0.158906E+10 | 0.162889E+10 | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.00 | 0.00 |
May | 0.271013E+10 | 0.100375E+10 | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.00 | 0.00 |
June | 0.362112E+10 | 0.531059E+09 | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.00 | 0.00 |
July | 0.343058E+10 | 0.441547E+09 | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.00 | 0.00 |
August | 0.267521E+10 | 0.589158E+09 | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.00 | 0.00 |
September | 0.197219E+10 | 0.114591E+10 | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.00 | 0.00 |
October | 0.108540E+10 | 0.187826E+10 | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.00 | 0.00 |
November | 0.316912E+09 | 0.303371E+10 | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.00 | 0.00 |
December | 0.153056E+09 | 0.397785E+10 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.190935E+11 | 0.235941E+11 | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153056E+09 | 0.441547E+09 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.362112E+10 | 0.397785E+10 | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138900E+10 | 0.223188E+10 | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.00 | 0.00 |
February | 0.191297E+10 | 0.183469E+10 | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.00 | 0.00 |
March | 0.282602E+10 | 0.175673E+10 | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.00 | 0.00 |
April | 0.386203E+10 | 0.104644E+10 | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.00 | 0.00 |
May | 0.461203E+10 | 0.673938E+09 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
June | 0.501910E+10 | 0.349869E+09 | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.00 | 0.00 |
July | 0.466060E+10 | 0.296175E+09 | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.00 | 0.00 |
August | 0.428462E+10 | 0.393453E+09 | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.00 | 0.00 |
September | 0.384903E+10 | 0.726581E+09 | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.00 | 0.00 |
October | 0.259903E+10 | 0.120967E+10 | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.00 | 0.00 |
November | 0.180476E+10 | 0.188822E+10 | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.00 | 0.00 |
December | 0.132173E+10 | 0.244825E+10 | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.381409E+11 | 0.148559E+11 | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.00 | 0.00 |
Minimum of Months | 0.132173E+10 | 0.296175E+09 | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.501910E+10 | 0.244825E+10 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.712997E+10 | 0.334850E+10 | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.00 | 0.00 |
February | 0.606463E+10 | 0.277283E+10 | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.00 | 0.00 |
March | 0.561318E+10 | 0.276148E+10 | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.00 | 0.00 |
April | 0.413040E+10 | 0.170348E+10 | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.00 | 0.00 |
May | 0.333538E+10 | 0.107059E+10 | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.00 | 0.00 |
June | 0.342039E+10 | 0.542322E+09 | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.00 | 0.00 |
July | 0.356708E+10 | 0.457200E+09 | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.00 | 0.00 |
August | 0.429511E+10 | 0.622487E+09 | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.00 | 0.00 |
September | 0.591357E+10 | 0.117367E+10 | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.00 | 0.00 |
October | 0.713591E+10 | 0.188128E+10 | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.00 | 0.00 |
November | 0.744751E+10 | 0.284489E+10 | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.00 | 0.00 |
December | 0.718495E+10 | 0.361560E+10 | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.652381E+11 | 0.227943E+11 | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333538E+10 | 0.457200E+09 | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.744751E+10 | 0.361560E+10 | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161829E+10 | 0.235149E+10 | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.00 | 0.00 |
February | 0.174774E+10 | 0.195619E+10 | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.00 | 0.00 |
March | 0.288485E+10 | 0.188259E+10 | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.00 | 0.00 |
April | 0.370223E+10 | 0.114519E+10 | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.00 | 0.00 |
May | 0.457480E+10 | 0.746232E+09 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
June | 0.483689E+10 | 0.393927E+09 | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.00 | 0.00 |
July | 0.444130E+10 | 0.329200E+09 | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.00 | 0.00 |
August | 0.414628E+10 | 0.433137E+09 | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.00 | 0.00 |
September | 0.389855E+10 | 0.806882E+09 | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.00 | 0.00 |
October | 0.303056E+10 | 0.128884E+10 | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.00 | 0.00 |
November | 0.205686E+10 | 0.200430E+10 | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.00 | 0.00 |
December | 0.146165E+10 | 0.257333E+10 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.384000E+11 | 0.159113E+11 | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146165E+10 | 0.329200E+09 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.483689E+10 | 0.257333E+10 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196473E+09 | 0.381989E+10 | 0.770467E+09 | 0.00 | 0.770467E+09 | 0.00 | 0.00 |
February | 0.446874E+09 | 0.301383E+10 | 0.849775E+09 | 0.00 | 0.849775E+09 | 0.00 | 0.00 |
March | 0.980203E+09 | 0.277254E+10 | 0.123123E+10 | 0.00 | 0.123123E+10 | 0.00 | 0.00 |
April | 0.168804E+10 | 0.156557E+10 | 0.137574E+10 | 10838704.44 | 0.136490E+10 | 0.00 | 0.00 |
May | 0.280785E+10 | 0.953960E+09 | 0.168606E+10 | 0.121925E+09 | 0.156414E+10 | 0.00 | 0.00 |
June | 0.371209E+10 | 0.487292E+09 | 0.173501E+10 | 0.213597E+09 | 0.152141E+10 | 0.00 | 0.00 |
July | 0.350327E+10 | 0.419163E+09 | 0.165693E+10 | 0.161288E+09 | 0.149564E+10 | 0.00 | 0.00 |
August | 0.270600E+10 | 0.601432E+09 | 0.139716E+10 | 28567892.73 | 0.136859E+10 | 0.00 | 0.00 |
September | 0.197388E+10 | 0.121541E+10 | 0.117982E+10 | 470784.09 | 0.117935E+10 | 0.00 | 0.00 |
October | 0.105977E+10 | 0.204891E+10 | 0.101223E+10 | 0.00 | 0.101223E+10 | 0.00 | 0.00 |
November | 0.273712E+09 | 0.337143E+10 | 0.790805E+09 | 0.00 | 0.790805E+09 | 0.00 | 0.00 |
December | 0.117622E+09 | 0.433484E+10 | 0.764500E+09 | 0.00 | 0.764500E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194658E+11 | 0.246043E+11 | 0.144497E+11 | 0.536687E+09 | 0.139130E+11 | 0.00 | 0.00 |
Minimum of Months | 0.117622E+09 | 0.419163E+09 | 0.764500E+09 | 0.00 | 0.764500E+09 | 0.00 | 0.00 |
Maximum of Months | 0.371209E+10 | 0.433484E+10 | 0.173501E+10 | 0.213597E+09 | 0.156414E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136713E+10 | 0.241992E+10 | 0.137383E+10 | 0.745251E+09 | 0.628580E+09 | 0.00 | 0.00 |
February | 0.191989E+10 | 0.192404E+10 | 0.166018E+10 | 0.946287E+09 | 0.713890E+09 | 0.00 | 0.00 |
March | 0.287186E+10 | 0.178957E+10 | 0.226939E+10 | 0.125036E+10 | 0.101904E+10 | 0.00 | 0.00 |
April | 0.392037E+10 | 0.105666E+10 | 0.264630E+10 | 0.146810E+10 | 0.117820E+10 | 0.00 | 0.00 |
May | 0.467275E+10 | 0.674842E+09 | 0.282186E+10 | 0.153357E+10 | 0.128829E+10 | 0.00 | 0.00 |
June | 0.507605E+10 | 0.341985E+09 | 0.273237E+10 | 0.152006E+10 | 0.121231E+10 | 0.00 | 0.00 |
July | 0.470492E+10 | 0.300491E+09 | 0.253202E+10 | 0.132369E+10 | 0.120833E+10 | 0.00 | 0.00 |
August | 0.430650E+10 | 0.421850E+09 | 0.240935E+10 | 0.123308E+10 | 0.117627E+10 | 0.00 | 0.00 |
September | 0.385330E+10 | 0.793769E+09 | 0.231001E+10 | 0.131803E+10 | 0.991988E+09 | 0.00 | 0.00 |
October | 0.258714E+10 | 0.133940E+10 | 0.183577E+10 | 0.990741E+09 | 0.845025E+09 | 0.00 | 0.00 |
November | 0.175697E+10 | 0.213127E+10 | 0.159252E+10 | 0.927109E+09 | 0.665408E+09 | 0.00 | 0.00 |
December | 0.126794E+10 | 0.271583E+10 | 0.137265E+10 | 0.727258E+09 | 0.645392E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383048E+11 | 0.159096E+11 | 0.255563E+11 | 0.139835E+11 | 0.115727E+11 | 0.00 | 0.00 |
Minimum of Months | 0.126794E+10 | 0.300491E+09 | 0.137265E+10 | 0.727258E+09 | 0.628580E+09 | 0.00 | 0.00 |
Maximum of Months | 0.507605E+10 | 0.271583E+10 | 0.282186E+10 | 0.153357E+10 | 0.128829E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.714559E+10 | 0.372098E+10 | 0.527062E+10 | 0.399304E+10 | 0.127758E+10 | 0.00 | 0.00 |
February | 0.611854E+10 | 0.297170E+10 | 0.441596E+10 | 0.311317E+10 | 0.130279E+10 | 0.00 | 0.00 |
March | 0.572777E+10 | 0.283381E+10 | 0.397341E+10 | 0.229105E+10 | 0.168237E+10 | 0.00 | 0.00 |
April | 0.423779E+10 | 0.168715E+10 | 0.260707E+10 | 0.972753E+09 | 0.163431E+10 | 0.00 | 0.00 |
May | 0.343928E+10 | 0.102773E+10 | 0.190381E+10 | 0.266467E+09 | 0.163734E+10 | 0.00 | 0.00 |
June | 0.350075E+10 | 0.498313E+09 | 0.158953E+10 | 0.100854E+09 | 0.148867E+10 | 0.00 | 0.00 |
July | 0.363228E+10 | 0.438658E+09 | 0.167436E+10 | 0.155213E+09 | 0.151914E+10 | 0.00 | 0.00 |
August | 0.432378E+10 | 0.651161E+09 | 0.213433E+10 | 0.564965E+09 | 0.156937E+10 | 0.00 | 0.00 |
September | 0.592629E+10 | 0.128638E+10 | 0.322397E+10 | 0.167495E+10 | 0.154902E+10 | 0.00 | 0.00 |
October | 0.713630E+10 | 0.210421E+10 | 0.452643E+10 | 0.306016E+10 | 0.146627E+10 | 0.00 | 0.00 |
November | 0.740792E+10 | 0.324379E+10 | 0.527142E+10 | 0.401880E+10 | 0.125262E+10 | 0.00 | 0.00 |
December | 0.715158E+10 | 0.405948E+10 | 0.539832E+10 | 0.405222E+10 | 0.134610E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.657479E+11 | 0.245234E+11 | 0.419892E+11 | 0.242636E+11 | 0.177256E+11 | 0.00 | 0.00 |
Minimum of Months | 0.343928E+10 | 0.438658E+09 | 0.158953E+10 | 0.100854E+09 | 0.125262E+10 | 0.00 | 0.00 |
Maximum of Months | 0.740792E+10 | 0.405948E+10 | 0.539832E+10 | 0.405222E+10 | 0.168237E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161575E+10 | 0.255277E+10 | 0.144718E+10 | 0.815008E+09 | 0.632172E+09 | 0.00 | 0.00 |
February | 0.177212E+10 | 0.204936E+10 | 0.147496E+10 | 0.783971E+09 | 0.690990E+09 | 0.00 | 0.00 |
March | 0.294471E+10 | 0.192932E+10 | 0.222530E+10 | 0.119268E+10 | 0.103262E+10 | 0.00 | 0.00 |
April | 0.376214E+10 | 0.116292E+10 | 0.247529E+10 | 0.133694E+10 | 0.113835E+10 | 0.00 | 0.00 |
May | 0.463824E+10 | 0.753577E+09 | 0.275499E+10 | 0.147404E+10 | 0.128095E+10 | 0.00 | 0.00 |
June | 0.489021E+10 | 0.385798E+09 | 0.259527E+10 | 0.139394E+10 | 0.120133E+10 | 0.00 | 0.00 |
July | 0.448202E+10 | 0.334287E+09 | 0.237989E+10 | 0.118261E+10 | 0.119728E+10 | 0.00 | 0.00 |
August | 0.416768E+10 | 0.466198E+09 | 0.230480E+10 | 0.117461E+10 | 0.113019E+10 | 0.00 | 0.00 |
September | 0.390603E+10 | 0.884236E+09 | 0.228098E+10 | 0.127073E+10 | 0.101025E+10 | 0.00 | 0.00 |
October | 0.301901E+10 | 0.143670E+10 | 0.202900E+10 | 0.118419E+10 | 0.844813E+09 | 0.00 | 0.00 |
November | 0.202740E+10 | 0.227587E+10 | 0.164811E+10 | 0.100352E+10 | 0.644590E+09 | 0.00 | 0.00 |
December | 0.143704E+10 | 0.284949E+10 | 0.137241E+10 | 0.745533E+09 | 0.626874E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.386623E+11 | 0.170805E+11 | 0.249882E+11 | 0.135578E+11 | 0.114304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143704E+10 | 0.334287E+09 | 0.137241E+10 | 0.745533E+09 | 0.626874E+09 | 0.00 | 0.00 |
Maximum of Months | 0.489021E+10 | 0.284949E+10 | 0.275499E+10 | 0.147404E+10 | 0.128095E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180201E+09 | 0.387073E+10 | 0.770482E+09 | 0.00 | 0.770482E+09 | 0.00 | 0.00 |
February | 0.393449E+09 | 0.316163E+10 | 0.849791E+09 | 0.00 | 0.849791E+09 | 0.00 | 0.00 |
March | 0.865762E+09 | 0.298198E+10 | 0.123126E+10 | 0.00 | 0.123126E+10 | 0.00 | 0.00 |
April | 0.158478E+10 | 0.170974E+10 | 0.137576E+10 | 10839023.03 | 0.136492E+10 | 0.00 | 0.00 |
May | 0.272140E+10 | 0.103416E+10 | 0.168610E+10 | 0.121928E+09 | 0.156417E+10 | 0.00 | 0.00 |
June | 0.364863E+10 | 0.536133E+09 | 0.173504E+10 | 0.213604E+09 | 0.152144E+10 | 0.00 | 0.00 |
July | 0.346478E+10 | 0.444057E+09 | 0.165696E+10 | 0.161293E+09 | 0.149567E+10 | 0.00 | 0.00 |
August | 0.269787E+10 | 0.604917E+09 | 0.139718E+10 | 28568732.44 | 0.136861E+10 | 0.00 | 0.00 |
September | 0.198024E+10 | 0.119194E+10 | 0.117984E+10 | 470797.93 | 0.117937E+10 | 0.00 | 0.00 |
October | 0.106378E+10 | 0.200236E+10 | 0.101224E+10 | 0.00 | 0.101224E+10 | 0.00 | 0.00 |
November | 0.277580E+09 | 0.330107E+10 | 0.790819E+09 | 0.00 | 0.790819E+09 | 0.00 | 0.00 |
December | 0.119046E+09 | 0.428789E+10 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189975E+11 | 0.251266E+11 | 0.144500E+11 | 0.536703E+09 | 0.139133E+11 | 0.00 | 0.00 |
Minimum of Months | 0.119046E+09 | 0.444057E+09 | 0.764515E+09 | 0.00 | 0.764515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364863E+10 | 0.428789E+10 | 0.173504E+10 | 0.213604E+09 | 0.156417E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133956E+10 | 0.240396E+10 | 0.137385E+10 | 0.745265E+09 | 0.628587E+09 | 0.00 | 0.00 |
February | 0.187050E+10 | 0.195794E+10 | 0.166020E+10 | 0.946305E+09 | 0.713898E+09 | 0.00 | 0.00 |
March | 0.278963E+10 | 0.185126E+10 | 0.226943E+10 | 0.125038E+10 | 0.101905E+10 | 0.00 | 0.00 |
April | 0.385366E+10 | 0.108749E+10 | 0.264634E+10 | 0.146813E+10 | 0.117821E+10 | 0.00 | 0.00 |
May | 0.461609E+10 | 0.693506E+09 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
June | 0.503177E+10 | 0.354478E+09 | 0.273241E+10 | 0.152009E+10 | 0.121232E+10 | 0.00 | 0.00 |
July | 0.467708E+10 | 0.299265E+09 | 0.253206E+10 | 0.132372E+10 | 0.120834E+10 | 0.00 | 0.00 |
August | 0.429321E+10 | 0.404101E+09 | 0.240939E+10 | 0.123310E+10 | 0.117629E+10 | 0.00 | 0.00 |
September | 0.384700E+10 | 0.752306E+09 | 0.231005E+10 | 0.131805E+10 | 0.991998E+09 | 0.00 | 0.00 |
October | 0.257797E+10 | 0.127989E+10 | 0.183579E+10 | 0.990761E+09 | 0.845034E+09 | 0.00 | 0.00 |
November | 0.175496E+10 | 0.203836E+10 | 0.159254E+10 | 0.927127E+09 | 0.665415E+09 | 0.00 | 0.00 |
December | 0.126261E+10 | 0.263996E+10 | 0.137267E+10 | 0.727272E+09 | 0.645400E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.379140E+11 | 0.157625E+11 | 0.255567E+11 | 0.139838E+11 | 0.115728E+11 | 0.00 | 0.00 |
Minimum of Months | 0.126261E+10 | 0.299265E+09 | 0.137267E+10 | 0.727272E+09 | 0.628587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.503177E+10 | 0.263996E+10 | 0.282191E+10 | 0.153360E+10 | 0.128830E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.707706E+10 | 0.358469E+10 | 0.527083E+10 | 0.399320E+10 | 0.127763E+10 | 0.00 | 0.00 |
February | 0.602331E+10 | 0.295017E+10 | 0.441613E+10 | 0.311330E+10 | 0.130283E+10 | 0.00 | 0.00 |
March | 0.558424E+10 | 0.291126E+10 | 0.397356E+10 | 0.229114E+10 | 0.168242E+10 | 0.00 | 0.00 |
April | 0.413361E+10 | 0.178147E+10 | 0.260715E+10 | 0.972794E+09 | 0.163436E+10 | 0.00 | 0.00 |
May | 0.335253E+10 | 0.110759E+10 | 0.190386E+10 | 0.266478E+09 | 0.163738E+10 | 0.00 | 0.00 |
June | 0.344765E+10 | 0.549517E+09 | 0.158957E+10 | 0.100858E+09 | 0.148871E+10 | 0.00 | 0.00 |
July | 0.360224E+10 | 0.461356E+09 | 0.167440E+10 | 0.155220E+09 | 0.151918E+10 | 0.00 | 0.00 |
August | 0.432145E+10 | 0.639455E+09 | 0.213440E+10 | 0.564988E+09 | 0.156941E+10 | 0.00 | 0.00 |
September | 0.592801E+10 | 0.121766E+10 | 0.322408E+10 | 0.167502E+10 | 0.154906E+10 | 0.00 | 0.00 |
October | 0.712295E+10 | 0.198369E+10 | 0.452660E+10 | 0.306029E+10 | 0.146632E+10 | 0.00 | 0.00 |
November | 0.739034E+10 | 0.304883E+10 | 0.527163E+10 | 0.401897E+10 | 0.125266E+10 | 0.00 | 0.00 |
December | 0.710819E+10 | 0.387281E+10 | 0.539854E+10 | 0.405239E+10 | 0.134615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650916E+11 | 0.241085E+11 | 0.419907E+11 | 0.242646E+11 | 0.177261E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335253E+10 | 0.461356E+09 | 0.158957E+10 | 0.100858E+09 | 0.125266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.739034E+10 | 0.387281E+10 | 0.539854E+10 | 0.405239E+10 | 0.168242E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159398E+10 | 0.252638E+10 | 0.144720E+10 | 0.815021E+09 | 0.632177E+09 | 0.00 | 0.00 |
February | 0.172789E+10 | 0.208920E+10 | 0.147498E+10 | 0.783984E+09 | 0.690996E+09 | 0.00 | 0.00 |
March | 0.286878E+10 | 0.199409E+10 | 0.222533E+10 | 0.119270E+10 | 0.103263E+10 | 0.00 | 0.00 |
April | 0.370469E+10 | 0.119942E+10 | 0.247532E+10 | 0.133697E+10 | 0.113836E+10 | 0.00 | 0.00 |
May | 0.459002E+10 | 0.772001E+09 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
June | 0.485814E+10 | 0.398572E+09 | 0.259530E+10 | 0.139396E+10 | 0.120134E+10 | 0.00 | 0.00 |
July | 0.446547E+10 | 0.332232E+09 | 0.237991E+10 | 0.118263E+10 | 0.119729E+10 | 0.00 | 0.00 |
August | 0.416430E+10 | 0.444350E+09 | 0.230483E+10 | 0.117463E+10 | 0.113020E+10 | 0.00 | 0.00 |
September | 0.390723E+10 | 0.837299E+09 | 0.228101E+10 | 0.127075E+10 | 0.101026E+10 | 0.00 | 0.00 |
October | 0.302126E+10 | 0.136620E+10 | 0.202903E+10 | 0.118421E+10 | 0.844821E+09 | 0.00 | 0.00 |
November | 0.202975E+10 | 0.216816E+10 | 0.164813E+10 | 0.100354E+10 | 0.644595E+09 | 0.00 | 0.00 |
December | 0.143154E+10 | 0.276815E+10 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383630E+11 | 0.168961E+11 | 0.249885E+11 | 0.135580E+11 | 0.114305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143154E+10 | 0.332232E+09 | 0.137243E+10 | 0.745546E+09 | 0.626880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.485814E+10 | 0.276815E+10 | 0.275503E+10 | 0.147407E+10 | 0.128096E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.484987E+10 | -0.413880E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -711062935.6 | 58.98 | 0.00 | 0.00 |
February | 0.439616E+10 | -0.375854E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -637614976.6 | 58.98 | 0.00 | 0.00 |
March | 0.498652E+10 | -0.428483E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -701694874.0 | 58.98 | 0.00 | 0.00 |
April | 0.427137E+10 | -0.359972E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671650822.9 | 58.98 | 0.00 | 0.00 |
May | 0.423836E+10 | -0.354638E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691979386.2 | 58.98 | 0.00 | 0.00 |
June | 0.391087E+10 | -0.324229E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668577707.5 | 58.98 | 0.00 | 0.00 |
July | 0.359434E+10 | -0.290442E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689915939.4 | 58.98 | 0.00 | 0.00 |
August | 0.390690E+10 | -0.321569E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691208914.0 | 58.98 | 0.00 | 0.00 |
September | 0.371638E+10 | -0.304921E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667176789.9 | 58.98 | 0.00 | 0.00 |
October | 0.410892E+10 | -0.341644E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692478148.0 | 58.98 | 0.00 | 0.00 |
November | 0.433576E+10 | -0.366004E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -675719155.1 | 58.98 | 0.00 | 0.00 |
December | 0.458758E+10 | -0.387685E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -710729986.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.509030E+11 | -0.426932E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.820981E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.359434E+10 | -0.428483E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -711062935.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.498652E+10 | -0.290442E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -637614976.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8786.70 | 38.51 | 276.00 | 279.17 | 1902.10 | 26.35 | 156.67 | 262.67 |
February | 268.33 | 0.49 | 0.48 | 01-FEB-07:00 | 9446.72 | 36.87 | 261.67 | 269.17 | 1392.03 | 22.43 | 122.00 | 246.33 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:10 | 1979.47 | 18.29 | 10.67 | 322.17 | 1041.48 | 20.00 | 105.50 | 291.67 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:49 | 1239.36 | 17.73 | 0.00 | 336.00 | 769.39 | 19.91 | 69.67 | 295.17 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:30 | 1010.19 | 17.46 | 0.00 | 360.67 | 621.84 | 19.64 | 34.83 | 321.67 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-06:30 | 903.03 | 17.35 | 0.00 | 351.33 | 569.42 | 19.63 | 11.83 | 312.00 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-06:30 | 963.89 | 17.38 | 0.00 | 358.83 | 585.76 | 19.60 | 29.17 | 301.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1144.12 | 17.72 | 0.00 | 346.17 | 695.36 | 19.88 | 58.17 | 298.33 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1472.73 | 18.09 | 11.00 | 318.33 | 876.71 | 19.82 | 82.00 | 281.50 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3594.03 | 24.78 | 131.00 | 311.50 | 1238.25 | 20.85 | 98.17 | 286.50 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8953.31 | 37.39 | 288.50 | 287.50 | 1556.03 | 24.73 | 129.17 | 274.00 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 7951.39 | 37.77 | 284.17 | 276.00 | 1873.02 | 26.39 | 166.00 | 269.33 |
Annual Sum or Average | 4125.67 | 0.51 | 3478.90 | 23.71 | 1263.00 | 3816.83 | 1030.19 | 21.29 | 1063.17 | 3440.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 903.03 | 17.35 | 0.00 | 269.17 | 569.42 | 19.60 | 11.83 | 246.33 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 9446.72 | 38.51 | 288.50 | 360.67 | 1902.10 | 26.39 | 166.00 | 321.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-08:09 | 2397.89 | 22.29 | 92.50 | 246.83 | 1317.98 | 22.74 | 68.00 | 197.50 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2882.19 | 22.18 | 89.67 | 249.00 | 1076.14 | 20.91 | 41.00 | 209.00 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-06:00 | 2621.03 | 21.06 | 101.33 | 308.83 | 1409.93 | 21.83 | 71.17 | 273.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3321.83 | 20.93 | 109.83 | 336.83 | 1279.27 | 20.20 | 50.83 | 307.33 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:49 | 2655.79 | 20.11 | 103.67 | 366.50 | 1465.55 | 21.27 | 72.67 | 334.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:49 | 2705.89 | 20.14 | 100.00 | 357.67 | 1501.26 | 21.34 | 70.00 | 326.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2394.68 | 19.99 | 99.33 | 365.83 | 1303.44 | 21.30 | 70.33 | 320.00 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 2999.62 | 20.63 | 109.67 | 348.33 | 1204.68 | 21.15 | 63.33 | 314.00 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-05:00 | 2889.53 | 21.38 | 114.50 | 319.00 | 1128.90 | 20.62 | 57.67 | 283.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2501.99 | 20.89 | 89.83 | 288.33 | 1376.23 | 22.00 | 63.67 | 249.17 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 2003.88 | 19.93 | 77.50 | 255.33 | 1104.16 | 21.90 | 61.83 | 209.33 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1812.91 | 21.10 | 81.33 | 249.17 | 939.45 | 21.52 | 60.33 | 210.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2624.54 | 20.82 | 1169.17 | 3691.67 | 1272.94 | 21.36 | 750.83 | 3234.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1812.91 | 19.93 | 77.50 | 246.83 | 939.45 | 20.20 | 41.00 | 197.50 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3321.83 | 22.29 | 114.50 | 366.50 | 1501.26 | 22.74 | 72.67 | 334.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:00 | 503.81 | 14.65 | 0.00 | 224.83 | 336.29 | 17.33 | 0.00 | 131.33 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-08:00 | 573.64 | 15.43 | 0.00 | 231.67 | 382.26 | 17.96 | 0.00 | 159.67 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:49 | 675.88 | 16.31 | 0.00 | 301.67 | 434.97 | 18.60 | 0.00 | 236.33 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 801.75 | 17.54 | 0.00 | 349.33 | 513.66 | 19.70 | 4.50 | 308.50 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-05:00 | 988.64 | 18.30 | 3.00 | 385.00 | 575.20 | 20.35 | 75.67 | 359.33 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1061.67 | 21.40 | 84.33 | 381.33 | 603.82 | 20.68 | 84.83 | 357.83 |
July | 400.17 | 0.49 | 0.48 | 01-JUL-05:00 | 1006.54 | 19.68 | 37.50 | 390.00 | 577.79 | 20.54 | 77.17 | 346.83 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 858.74 | 17.82 | 0.00 | 361.00 | 535.34 | 19.96 | 24.50 | 322.00 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:30 | 672.50 | 16.71 | 0.00 | 308.67 | 440.90 | 18.97 | 0.17 | 240.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:30 | 603.13 | 15.78 | 0.00 | 278.17 | 398.55 | 18.21 | 0.00 | 205.83 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 488.53 | 14.67 | 0.00 | 234.17 | 329.69 | 17.30 | 0.00 | 132.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-08:30 | 504.20 | 14.63 | 0.00 | 227.17 | 330.73 | 17.27 | 0.00 | 135.17 |
Annual Sum or Average | 4125.67 | 0.51 | 754.72 | 17.17 | 124.83 | 3673.00 | 468.13 | 19.08 | 266.83 | 2935.33 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 488.53 | 14.63 | 0.00 | 224.83 | 329.69 | 17.27 | 0.00 | 131.33 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 1061.67 | 21.40 | 84.33 | 390.00 | 603.82 | 20.68 | 84.83 | 359.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:00 | 1962.10 | 21.17 | 81.83 | 258.50 | 1097.81 | 23.02 | 65.83 | 208.83 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:00 | 2312.98 | 22.27 | 88.33 | 251.33 | 1255.44 | 22.83 | 61.33 | 209.83 |
March | 351.83 | 0.50 | 0.48 | 01-MAR-07:00 | 2921.47 | 21.51 | 111.33 | 320.33 | 1118.24 | 20.49 | 52.50 | 281.50 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:19 | 3246.84 | 20.93 | 111.83 | 342.33 | 1299.09 | 20.34 | 51.83 | 309.83 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:49 | 2551.24 | 13.78 | 0.00 | 374.50 | 1425.00 | 17.46 | 0.00 | 345.00 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:30 | 2646.23 | 13.89 | 0.00 | 371.50 | 1460.86 | 17.59 | 0.00 | 337.50 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:40 | 2367.05 | 14.23 | 3.67 | 378.83 | 1306.08 | 17.63 | 0.00 | 331.83 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-06:49 | 2419.83 | 17.37 | 57.17 | 350.83 | 1263.92 | 17.71 | 3.67 | 311.00 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:40 | 2860.72 | 20.94 | 110.33 | 317.67 | 1136.87 | 20.50 | 56.17 | 280.50 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:30 | 2417.72 | 20.60 | 86.17 | 298.83 | 1331.25 | 22.62 | 69.00 | 258.67 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 1857.93 | 20.97 | 86.33 | 265.17 | 934.83 | 21.26 | 54.50 | 216.50 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:30 | 2038.65 | 22.99 | 105.67 | 255.83 | 835.79 | 21.88 | 53.33 | 214.00 |
Annual Sum or Average | 4125.67 | 0.50 | 2501.52 | 18.84 | 842.67 | 3785.67 | 1222.33 | 20.00 | 468.17 | 3305.00 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 1857.93 | 13.78 | 0.00 | 251.33 | 835.79 | 17.46 | 0.00 | 208.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3246.84 | 22.99 | 111.83 | 378.83 | 1460.86 | 23.02 | 69.00 | 345.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8586.97 | 37.06 | 265.17 | 276.33 | 1770.19 | 23.88 | 97.17 | 261.50 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9310.46 | 36.61 | 261.50 | 268.17 | 1281.93 | 19.72 | 35.33 | 243.50 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 1884.79 | 14.50 | 10.67 | 318.67 | 967.75 | 17.54 | 2.17 | 288.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:00 | 1181.81 | 14.22 | 0.00 | 333.17 | 729.13 | 17.79 | 0.00 | 291.50 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:30 | 971.92 | 14.11 | 0.00 | 357.83 | 598.85 | 17.63 | 0.00 | 316.33 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-06:30 | 871.67 | 13.92 | 0.00 | 348.83 | 552.01 | 17.55 | 0.00 | 306.67 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-06:30 | 928.19 | 13.96 | 0.00 | 355.17 | 564.87 | 17.52 | 0.00 | 295.67 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1095.26 | 14.25 | 0.00 | 343.00 | 663.24 | 17.78 | 0.00 | 293.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1398.12 | 14.48 | 11.00 | 316.33 | 820.34 | 17.56 | 0.00 | 278.33 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3476.85 | 22.13 | 131.00 | 310.83 | 1142.72 | 18.24 | 14.50 | 283.33 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8812.42 | 37.10 | 288.33 | 287.00 | 1438.19 | 22.23 | 90.17 | 273.50 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 7791.94 | 37.52 | 284.00 | 275.17 | 1744.59 | 23.92 | 101.50 | 268.33 |
Annual Sum or Average | 4125.67 | 0.51 | 3391.63 | 21.08 | 1251.67 | 3790.50 | 965.47 | 19.00 | 340.83 | 3400.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 871.67 | 13.92 | 0.00 | 268.17 | 552.01 | 17.52 | 0.00 | 243.50 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 9310.46 | 37.52 | 288.33 | 357.83 | 1770.19 | 23.92 | 101.50 | 316.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-08:09 | 2345.58 | 21.81 | 92.50 | 243.50 | 1274.84 | 22.52 | 63.50 | 194.67 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2818.03 | 21.71 | 89.67 | 247.50 | 1026.25 | 20.70 | 41.00 | 207.17 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-06:00 | 2451.58 | 18.83 | 82.50 | 306.00 | 1353.26 | 21.65 | 71.17 | 271.67 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3239.44 | 20.47 | 109.83 | 334.33 | 1214.84 | 20.02 | 50.83 | 304.67 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:49 | 2498.32 | 18.37 | 87.50 | 363.00 | 1405.13 | 21.10 | 72.67 | 331.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:49 | 2633.79 | 19.63 | 99.50 | 356.50 | 1440.01 | 21.17 | 70.00 | 324.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2270.08 | 18.30 | 84.17 | 362.67 | 1246.41 | 21.13 | 70.33 | 317.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 2920.26 | 20.17 | 109.67 | 346.33 | 1148.28 | 20.97 | 63.33 | 311.83 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-06:10 | 2824.64 | 20.92 | 114.50 | 315.50 | 1075.27 | 20.43 | 57.67 | 281.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2440.20 | 20.41 | 89.83 | 286.67 | 1325.23 | 21.80 | 63.67 | 246.50 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 1946.62 | 19.41 | 77.50 | 252.83 | 1058.50 | 21.69 | 61.00 | 205.00 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1760.37 | 20.61 | 81.33 | 246.67 | 898.57 | 21.29 | 51.33 | 205.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2534.71 | 19.94 | 1118.50 | 3661.50 | 1218.70 | 21.17 | 736.50 | 3202.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1760.37 | 18.30 | 77.50 | 243.50 | 898.57 | 20.02 | 41.00 | 194.67 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3239.44 | 21.81 | 114.50 | 363.00 | 1440.01 | 22.52 | 72.67 | 331.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:00 | 485.65 | 11.04 | 0.00 | 220.00 | 327.21 | 14.99 | 0.00 | 121.33 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-08:00 | 553.68 | 12.01 | 0.00 | 227.00 | 372.34 | 15.82 | 0.00 | 152.33 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:00 | 653.94 | 12.96 | 0.00 | 298.00 | 423.85 | 16.60 | 0.00 | 230.17 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 775.50 | 14.34 | 0.00 | 348.50 | 500.21 | 17.94 | 0.00 | 303.67 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 956.15 | 14.91 | 3.00 | 383.83 | 557.46 | 18.43 | 1.83 | 357.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1026.97 | 18.58 | 83.17 | 380.50 | 586.06 | 18.60 | 2.00 | 354.00 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:49 | 972.37 | 16.47 | 37.33 | 388.50 | 589.76 | 19.94 | 37.50 | 348.67 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 829.53 | 14.51 | 0.00 | 359.17 | 519.89 | 18.11 | 0.00 | 316.50 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 650.06 | 13.49 | 0.00 | 305.83 | 429.66 | 17.13 | 0.00 | 235.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:30 | 582.62 | 12.44 | 0.00 | 275.17 | 388.32 | 16.17 | 0.00 | 198.00 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 471.44 | 11.10 | 0.00 | 226.67 | 321.29 | 15.03 | 0.00 | 124.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-08:30 | 485.36 | 11.06 | 0.00 | 223.83 | 321.10 | 14.92 | 0.00 | 121.00 |
Annual Sum or Average | 4125.67 | 0.51 | 729.27 | 13.85 | 123.50 | 3637.00 | 457.92 | 17.18 | 41.33 | 2862.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 471.44 | 11.04 | 0.00 | 220.00 | 321.10 | 14.92 | 0.00 | 121.00 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 1026.97 | 18.58 | 83.17 | 388.50 | 589.76 | 19.94 | 37.50 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:00 | 1905.45 | 20.76 | 81.83 | 256.67 | 995.43 | 21.55 | 54.33 | 203.83 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-08:00 | 2255.73 | 21.86 | 88.33 | 250.00 | 1210.76 | 22.71 | 61.33 | 208.33 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:00 | 2860.02 | 21.09 | 111.33 | 317.83 | 1066.47 | 20.36 | 52.67 | 279.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:30 | 3175.34 | 20.48 | 111.83 | 340.17 | 1240.95 | 20.18 | 51.83 | 306.33 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:49 | 2472.38 | 13.24 | 0.00 | 373.00 | 1368.22 | 17.27 | 0.00 | 341.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:40 | 2578.61 | 13.35 | 0.00 | 369.50 | 1405.99 | 17.39 | 0.00 | 335.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:49 | 2301.18 | 13.68 | 3.67 | 376.83 | 1255.99 | 17.43 | 0.00 | 328.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:00 | 2346.39 | 16.87 | 57.17 | 349.00 | 1210.32 | 17.53 | 3.67 | 307.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:49 | 2796.47 | 20.50 | 110.17 | 314.83 | 1083.67 | 20.35 | 56.17 | 277.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:30 | 2351.16 | 20.17 | 86.17 | 297.17 | 1277.03 | 22.50 | 69.00 | 256.33 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 1805.11 | 20.55 | 86.33 | 261.17 | 891.42 | 21.15 | 54.33 | 212.00 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:30 | 1990.34 | 22.61 | 105.67 | 254.00 | 797.71 | 21.79 | 53.00 | 211.00 |
Annual Sum or Average | 4125.67 | 0.51 | 2436.80 | 18.38 | 842.50 | 3760.17 | 1167.49 | 19.76 | 456.33 | 3267.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1805.11 | 13.24 | 0.00 | 250.00 | 797.71 | 17.27 | 0.00 | 203.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3175.34 | 22.61 | 111.83 | 376.83 | 1405.99 | 22.71 | 69.00 | 341.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.49 | 0.48 | 01-JAN-08:09 | 8586.94 | 37.06 | 265.17 | 276.33 | 1770.11 | 23.89 | 97.17 | 261.50 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9310.39 | 36.61 | 261.50 | 268.17 | 1281.86 | 19.72 | 35.33 | 243.50 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 1884.72 | 14.51 | 10.67 | 318.67 | 967.69 | 17.54 | 2.17 | 288.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:00 | 1181.76 | 14.22 | 0.00 | 333.17 | 729.09 | 17.79 | 0.00 | 291.50 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:30 | 971.88 | 14.11 | 0.00 | 357.83 | 598.81 | 17.63 | 0.00 | 316.33 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-06:30 | 871.64 | 13.92 | 0.00 | 348.83 | 551.98 | 17.55 | 0.00 | 306.67 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-06:30 | 928.15 | 13.96 | 0.00 | 355.17 | 564.83 | 17.52 | 0.00 | 295.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1095.21 | 14.26 | 0.00 | 343.00 | 663.20 | 17.78 | 0.00 | 293.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1398.07 | 14.48 | 11.00 | 316.33 | 820.29 | 17.56 | 0.00 | 278.33 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-06:00 | 3476.79 | 22.13 | 131.00 | 310.83 | 1142.66 | 18.24 | 14.50 | 283.33 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8812.39 | 37.10 | 288.33 | 287.00 | 1438.13 | 22.23 | 90.17 | 273.50 |
December | 289.50 | 0.49 | 0.48 | 01-DEC-07:19 | 7791.92 | 37.52 | 284.00 | 275.17 | 1744.51 | 23.92 | 101.50 | 268.33 |
Annual Sum or Average | 4125.67 | 0.51 | 3391.58 | 21.08 | 1251.67 | 3790.50 | 965.42 | 19.00 | 340.83 | 3400.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 871.64 | 13.92 | 0.00 | 268.17 | 551.98 | 17.52 | 0.00 | 243.50 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 9310.39 | 37.52 | 288.33 | 357.83 | 1770.11 | 23.92 | 101.50 | 316.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-08:09 | 2345.57 | 21.81 | 92.50 | 243.50 | 1274.81 | 22.52 | 63.50 | 194.67 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-07:40 | 2818.02 | 21.72 | 89.67 | 247.50 | 1026.21 | 20.70 | 41.00 | 207.17 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-06:00 | 2451.55 | 18.83 | 82.50 | 306.00 | 1353.21 | 21.65 | 71.17 | 271.67 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 3239.42 | 20.47 | 109.83 | 334.33 | 1214.79 | 20.02 | 50.83 | 304.67 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-05:49 | 2498.30 | 18.37 | 87.50 | 363.00 | 1405.09 | 21.10 | 72.67 | 331.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-05:49 | 2633.77 | 19.64 | 99.50 | 356.50 | 1439.97 | 21.17 | 70.00 | 324.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-05:49 | 2270.05 | 18.30 | 84.17 | 362.67 | 1246.36 | 21.13 | 70.33 | 317.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 2920.23 | 20.17 | 109.67 | 346.33 | 1148.23 | 20.97 | 63.33 | 311.83 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-06:10 | 2824.62 | 20.92 | 114.50 | 315.50 | 1075.22 | 20.43 | 57.67 | 281.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-06:40 | 2440.18 | 20.41 | 89.83 | 286.67 | 1325.19 | 21.80 | 63.67 | 246.50 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 1946.61 | 19.42 | 77.50 | 252.83 | 1058.47 | 21.69 | 61.00 | 205.00 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-07:10 | 1760.36 | 20.61 | 81.33 | 246.67 | 898.53 | 21.29 | 51.33 | 205.67 |
Annual Sum or Average | 4125.67 | 0.51 | 2534.69 | 19.94 | 1118.50 | 3661.50 | 1218.66 | 21.17 | 736.50 | 3202.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1760.36 | 18.30 | 77.50 | 243.50 | 898.53 | 20.02 | 41.00 | 194.67 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 3239.42 | 21.81 | 114.50 | 363.00 | 1439.97 | 22.52 | 72.67 | 331.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:00 | 485.65 | 11.05 | 0.00 | 220.00 | 327.19 | 14.99 | 0.00 | 121.33 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-08:00 | 553.68 | 12.02 | 0.00 | 227.00 | 372.32 | 15.82 | 0.00 | 152.33 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:00 | 653.93 | 12.96 | 0.00 | 298.00 | 423.83 | 16.60 | 0.00 | 230.17 |
April | 373.83 | 0.50 | 0.48 | 01-APR-06:30 | 775.48 | 14.34 | 0.00 | 348.50 | 500.19 | 17.94 | 0.00 | 303.67 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 956.13 | 14.91 | 3.00 | 383.83 | 557.43 | 18.43 | 1.83 | 357.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-05:00 | 1026.94 | 18.58 | 83.17 | 380.50 | 586.03 | 18.60 | 2.00 | 354.00 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:49 | 972.34 | 16.47 | 37.33 | 388.50 | 589.73 | 19.94 | 37.50 | 348.67 |
August | 377.83 | 0.50 | 0.48 | 01-AUG-05:00 | 829.51 | 14.51 | 0.00 | 359.17 | 519.86 | 18.11 | 0.00 | 316.50 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 650.05 | 13.49 | 0.00 | 305.83 | 429.64 | 17.13 | 0.00 | 235.17 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-07:30 | 582.61 | 12.44 | 0.00 | 275.17 | 388.30 | 16.17 | 0.00 | 198.00 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:39 | 471.44 | 11.10 | 0.00 | 226.67 | 321.28 | 15.03 | 0.00 | 124.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-08:30 | 485.35 | 11.06 | 0.00 | 223.83 | 321.08 | 14.92 | 0.00 | 120.83 |
Annual Sum or Average | 4125.67 | 0.51 | 729.26 | 13.85 | 123.50 | 3637.00 | 457.89 | 17.18 | 41.33 | 2862.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 471.44 | 11.05 | 0.00 | 220.00 | 321.08 | 14.92 | 0.00 | 120.83 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 1026.94 | 18.58 | 83.17 | 388.50 | 589.73 | 19.94 | 37.50 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.51 | 0.48 | 01-JAN-08:00 | 1905.44 | 20.76 | 81.83 | 256.67 | 995.39 | 21.55 | 54.33 | 203.83 |
February | 268.33 | 0.51 | 0.48 | 01-FEB-08:00 | 2255.71 | 21.86 | 88.33 | 250.00 | 1210.72 | 22.71 | 61.33 | 208.33 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:00 | 2859.99 | 21.09 | 111.33 | 317.83 | 1066.43 | 20.36 | 52.67 | 279.67 |
April | 373.83 | 0.50 | 0.48 | 01-APR-07:30 | 3175.31 | 20.48 | 111.83 | 340.17 | 1240.91 | 20.18 | 51.83 | 306.33 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:49 | 2472.35 | 13.24 | 0.00 | 373.00 | 1368.17 | 17.27 | 0.00 | 341.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:40 | 2578.59 | 13.35 | 0.00 | 369.50 | 1405.95 | 17.40 | 0.00 | 335.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:49 | 2301.15 | 13.68 | 3.67 | 376.83 | 1255.94 | 17.43 | 0.00 | 328.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:00 | 2346.36 | 16.87 | 57.17 | 349.00 | 1210.27 | 17.53 | 3.67 | 307.50 |
September | 365.83 | 0.51 | 0.48 | 01-SEP-07:49 | 2796.45 | 20.50 | 110.17 | 314.83 | 1083.63 | 20.36 | 56.17 | 277.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:30 | 2351.14 | 20.17 | 86.17 | 297.17 | 1276.99 | 22.50 | 69.00 | 256.33 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 1805.11 | 20.55 | 86.33 | 261.17 | 891.39 | 21.15 | 54.33 | 212.00 |
December | 289.50 | 0.51 | 0.48 | 01-DEC-08:30 | 1990.33 | 22.61 | 105.67 | 254.00 | 797.68 | 21.79 | 53.00 | 211.00 |
Annual Sum or Average | 4125.67 | 0.51 | 2436.78 | 18.38 | 842.50 | 3760.17 | 1167.45 | 19.76 | 456.33 | 3267.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1805.11 | 13.24 | 0.00 | 250.00 | 797.68 | 17.27 | 0.00 | 203.83 | |
Maximum of Months | 408.83 | 0.51 | 0.48 | 3175.31 | 22.61 | 111.83 | 376.83 | 1405.95 | 22.71 | 69.00 | 341.67 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107062E+10 | 9701.44 | 24-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.871665E+09 | 9754.49 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.919159E+09 | 9649.24 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260558E+09 | 9658.57 | 11-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27541395.10 | 9741.58 | 02-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3660636.19 | 3542.09 | 25-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104599E+09 | 9766.49 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.624339E+09 | 9730.30 | 13-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116380E+10 | 9807.68 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116380E+10 | 9807.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132297E+09 | 7199.96 | 17-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52823697.23 | 7199.96 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30513825.51 | 7199.96 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8086034.63 | 5095.99 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141420E+09 | 7199.96 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141420E+09 | 7199.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.514905E+09 | 8658.59 | 17-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350102E+09 | 8716.58 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162079E+09 | 8607.29 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 879413.24 | 1288.01 | 12-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38396999.05 | 8597.88 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.520438E+09 | 8765.32 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520438E+09 | 8765.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142241E+09 | 7142.69 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95660909.75 | 7142.69 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37499785.16 | 7142.69 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9382581.73 | 6287.31 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163876E+09 | 7142.69 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163876E+09 | 7142.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9199513.26 | 19576.57 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27710219.25 | 19583.37 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36909732.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27710219.25 | 19583.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196100E+09 | 10449.89 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71106345.01 | 10600.83 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30210461.65 | 10397.77 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 47600820.00 | 10389.83 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.268862E+09 | 10461.48 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.613880E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268862E+09 | 10600.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207091E+09 | 7874.28 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60614186.04 | 7874.28 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25007796.02 | 7874.28 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45298245.38 | 7874.28 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290166E+09 | 7874.28 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290166E+09 | 7874.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.506690E+09 | 9332.24 | 17-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209580E+09 | 9427.42 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74132441.80 | 9249.92 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121543E+09 | 9298.90 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733405E+09 | 9322.66 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.733405E+09 | 9427.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248356E+09 | 7822.82 | 09-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107758E+09 | 7822.82 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30918874.41 | 7822.82 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62150396.89 | 7822.82 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360296E+09 | 7822.82 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.809480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.360296E+09 | 7822.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.598068E+09 | 31735.08 | 17-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184255E+09 | 31558.13 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39915469.05 | 31183.43 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195793E+09 | 31532.59 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100027E+10 | 31715.44 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100027E+10 | 31735.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.728952E+09 | 12120.83 | 17-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375421E+09 | 12008.91 | 15-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.224533E+09 | 12001.88 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16648714.29 | 9937.26 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1110133.29 | 3018.53 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272299E+09 | 12065.23 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.924793E+09 | 12095.74 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.924793E+09 | 12120.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.647274E+09 | 9652.85 | 24-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273141E+09 | 9597.79 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134232E+09 | 9589.75 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1562838.48 | 3269.99 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1091722.19 | 4131.14 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209800E+09 | 9675.90 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.845396E+09 | 9700.55 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.845396E+09 | 9700.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153401E+10 | 10968.40 | 17-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811688E+09 | 10987.64 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367744E+09 | 10912.63 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18398384.76 | 9811.67 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3491245.97 | 5805.87 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551371E+09 | 10930.94 | 13-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199465E+10 | 10945.80 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199465E+10 | 10987.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.823334E+09 | 9970.56 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442921E+09 | 9970.56 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195428E+09 | 9970.56 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10882957.42 | 6398.13 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1430565.83 | 2386.72 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305573E+09 | 9970.56 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107449E+10 | 9970.56 | 01-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107449E+10 | 9970.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228325E+10 | 14524.84 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144820E+10 | 14524.84 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.819310E+09 | 11809.87 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53060567.72 | 5220.16 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 252114.75 | 840.38 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4632835.34 | 2473.54 | 25-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725270E+09 | 9295.38 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319342E+10 | 14524.84 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.852740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319342E+10 | 14524.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252252E+10 | 15147.80 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162247E+10 | 15147.80 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.991173E+09 | 12620.21 | 02-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100875E+09 | 5489.48 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 172801.76 | 514.89 | 02-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 798285.97 | 1212.92 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29688247.14 | 3112.21 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100578E+10 | 10565.33 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346270E+10 | 15054.08 | 27-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.973617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346270E+10 | 15147.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.291083E+10 | 14444.89 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191268E+10 | 14444.89 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124036E+10 | 14284.39 | 02-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176653E+09 | 7444.21 | 12-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2475326.26 | 1298.41 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3790063.81 | 2029.12 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75046696.93 | 4220.51 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126952E+10 | 12898.54 | 17-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387899E+10 | 14444.89 | 19-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387899E+10 | 14444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.670174E+09 | 0.658042E+09 | 12398.70 | 03-JAN-15:00 | 12398.70 | 0.00 |
February | 0.00 | 0.00 | 0.295727E+10 | 0.293514E+10 | 25570.42 | 21-FEB-16:30 | 25570.42 | 0.00 |
March | 0.00 | 0.00 | 0.741863E+10 | 0.739223E+10 | 28015.54 | 21-MAR-16:00 | 28015.54 | 0.00 |
April | 0.00 | 0.00 | 0.217681E+11 | 0.215935E+11 | 48458.25 | 21-APR-15:10 | 48458.25 | 0.00 |
May | 0.00 | 0.00 | 0.432410E+11 | 0.420637E+11 | 62474.70 | 30-MAY-06:03 | 62474.70 | 0.00 |
June | 0.00 | 0.00 | 0.608295E+11 | 0.587061E+11 | 76012.61 | 19-JUN-06:03 | 59402.54 | 0.00 |
July | 0.00 | 0.00 | 0.717803E+11 | 0.582912E+11 | 101815.39 | 20-JUL-15:05 | 36911.26 | 0.00 |
August | 0.00 | 0.00 | 0.665585E+11 | 0.575907E+11 | 96193.15 | 03-AUG-06:03 | 41507.39 | 0.00 |
September | 0.00 | 0.00 | 0.553819E+11 | 0.482391E+11 | 93868.34 | 22-SEP-06:03 | 35725.78 | 0.00 |
October | 0.00 | 0.00 | 0.280851E+11 | 0.250563E+11 | 64921.85 | 04-OCT-10:40 | 40865.60 | 0.00 |
November | 0.00 | 0.00 | 0.811657E+10 | 0.797009E+10 | 35219.88 | 03-NOV-16:00 | 35219.88 | 0.00 |
December | 0.00 | 0.00 | 0.256661E+09 | 0.254086E+09 | 5850.65 | 20-DEC-15:00 | 5850.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.367064E+12 | 0.330750E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.256661E+09 | 0.254086E+09 | 5850.65 | 5850.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.717803E+11 | 0.587061E+11 | 101815.39 | 62474.70 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.606924E+09 | 0.593471E+09 | 11378.57 | 12-JAN-15:05 | 11378.57 | 0.00 |
February | 0.00 | 0.00 | 0.259415E+10 | 0.256994E+10 | 21939.56 | 21-FEB-15:05 | 21939.56 | 0.00 |
March | 0.00 | 0.00 | 0.662495E+10 | 0.660083E+10 | 29091.51 | 22-MAR-14:05 | 29091.51 | 0.00 |
April | 0.00 | 0.00 | 0.220103E+11 | 0.218537E+11 | 51529.47 | 21-APR-14:05 | 51529.47 | 0.00 |
May | 0.00 | 0.00 | 0.428991E+11 | 0.418816E+11 | 67966.06 | 30-MAY-06:03 | 67966.06 | 0.00 |
June | 0.00 | 0.00 | 0.597079E+11 | 0.578215E+11 | 75519.51 | 19-JUN-06:03 | 58988.79 | 0.00 |
July | 0.00 | 0.00 | 0.671828E+11 | 0.551944E+11 | 97525.76 | 20-JUL-15:05 | 35359.88 | 0.00 |
August | 0.00 | 0.00 | 0.595644E+11 | 0.522102E+11 | 92140.40 | 03-AUG-06:03 | 39140.87 | 0.00 |
September | 0.00 | 0.00 | 0.477141E+11 | 0.419710E+11 | 71825.96 | 14-SEP-09:50 | 37064.42 | 0.00 |
October | 0.00 | 0.00 | 0.239673E+11 | 0.213699E+11 | 62391.76 | 03-OCT-14:05 | 54175.06 | 0.00 |
November | 0.00 | 0.00 | 0.515487E+10 | 0.498099E+10 | 32603.04 | 09-NOV-15:05 | 32603.04 | 0.00 |
December | 0.00 | 0.00 | 0.212088E+09 | 0.209383E+09 | 4743.54 | 20-DEC-15:00 | 4743.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.338239E+12 | 0.307257E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.212088E+09 | 0.209383E+09 | 4743.54 | 4743.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.671828E+11 | 0.578215E+11 | 97525.76 | 67966.06 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.589995E+09 | 0.561197E+09 | 10327.75 | 03-JAN-14:50 | 10327.75 | 0.00 |
February | 0.00 | 0.00 | 0.255748E+10 | 0.251358E+10 | 21881.65 | 20-FEB-15:02 | 21881.65 | 0.00 |
March | 0.00 | 0.00 | 0.677185E+10 | 0.670292E+10 | 31755.19 | 21-MAR-16:00 | 31755.19 | 0.00 |
April | 0.00 | 0.00 | 0.244033E+11 | 0.241465E+11 | 59984.87 | 21-APR-14:40 | 59984.87 | 0.00 |
May | 0.00 | 0.00 | 0.479918E+11 | 0.466146E+11 | 73770.30 | 30-MAY-14:50 | 73770.30 | 0.00 |
June | 0.00 | 0.00 | 0.674911E+11 | 0.651423E+11 | 77645.02 | 19-JUN-14:30 | 75172.17 | 0.00 |
July | 0.00 | 0.00 | 0.748320E+11 | 0.619230E+11 | 112796.10 | 20-JUL-14:55 | 39476.10 | 0.00 |
August | 0.00 | 0.00 | 0.657425E+11 | 0.575248E+11 | 88115.04 | 05-AUG-05:03 | 51343.38 | 0.00 |
September | 0.00 | 0.00 | 0.518592E+11 | 0.455724E+11 | 79106.58 | 14-SEP-10:00 | 39866.46 | 0.00 |
October | 0.00 | 0.00 | 0.249468E+11 | 0.219968E+11 | 70056.12 | 03-OCT-14:00 | 61537.84 | 0.00 |
November | 0.00 | 0.00 | 0.473923E+10 | 0.450613E+10 | 32125.49 | 09-NOV-15:00 | 32125.49 | 0.00 |
December | 0.00 | 0.00 | 0.209186E+09 | 0.200237E+09 | 4717.37 | 20-DEC-15:00 | 4717.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.372134E+12 | 0.337404E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.209186E+09 | 0.200237E+09 | 4717.37 | 4717.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.748320E+11 | 0.651423E+11 | 112796.10 | 75172.17 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1698.54 | 5905.15 | 26-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1707.04 | 5911.72 | 01-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1756.52 | 5801.16 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1541.99 | 5444.34 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1479.41 | 5055.84 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1407.98 | 4648.45 | 02-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1236.70 | 4355.67 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1358.41 | 4366.80 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1330.45 | 4644.05 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1429.78 | 5065.25 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1566.64 | 5483.54 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1599.32 | 5782.75 | 28-DEC-12:08 |
Annual Sum or Average | 0.00 | 1508.30 | ||||
Minimum of Months | 0.00 | 0.00 | 1236.70 | 4355.67 | ||
Maximum of Months | 0.00 | 0.00 | 1756.52 | 5911.72 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126852E+10 | 0.34 | 1916.90 | 12-JAN-15:00 | 0.75 |
February | 0.126854E+10 | 0.35 | 2441.05 | 21-FEB-16:30 | 0.85 |
March | 0.168053E+10 | 0.37 | 2898.27 | 16-MAR-15:30 | 0.93 |
April | 0.255792E+10 | 0.42 | 5518.87 | 21-APR-15:10 | 1.35 |
May | 0.428649E+10 | 0.54 | 8739.23 | 30-MAY-15:00 | 1.80 |
June | 0.580068E+10 | 0.65 | 9865.42 | 05-JUN-12:07 | 1.94 |
July | 0.574918E+10 | 0.64 | 10788.88 | 03-JUL-06:03 | 2.06 |
August | 0.576365E+10 | 0.64 | 10788.88 | 05-AUG-06:03 | 2.05 |
September | 0.471883E+10 | 0.57 | 10401.97 | 18-SEP-06:03 | 2.00 |
October | 0.336880E+10 | 0.47 | 9604.33 | 02-OCT-06:03 | 1.91 |
November | 0.198653E+10 | 0.38 | 4398.26 | 09-NOV-16:50 | 1.18 |
December | 0.124472E+10 | 0.33 | 1639.02 | 01-DEC-13:07 | 0.70 |
Annual Sum or Average | 0.396944E+11 | 0.48 | |||
Minimum of Months | 0.124472E+10 | 0.33 | 1639.02 | 0.70 | |
Maximum of Months | 0.580068E+10 | 0.65 | 10788.88 | 2.06 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116655E+10 | 0.33 | 1728.44 | 12-JAN-15:40 | 0.73 |
February | 0.116958E+10 | 0.35 | 2404.96 | 21-FEB-16:30 | 0.87 |
March | 0.161783E+10 | 0.38 | 3851.85 | 16-MAR-15:30 | 1.13 |
April | 0.265819E+10 | 0.45 | 6613.64 | 21-APR-14:40 | 1.56 |
May | 0.436123E+10 | 0.56 | 9864.07 | 30-MAY-14:20 | 2.01 |
June | 0.584584E+10 | 0.67 | 10241.24 | 15-JUN-04:03 | 2.07 |
July | 0.552113E+10 | 0.63 | 10241.24 | 03-JUL-05:03 | 2.06 |
August | 0.539511E+10 | 0.63 | 10241.24 | 07-AUG-10:10 | 2.05 |
September | 0.410857E+10 | 0.54 | 8554.54 | 05-SEP-10:10 | 1.82 |
October | 0.266808E+10 | 0.44 | 9207.93 | 02-OCT-04:02 | 1.92 |
November | 0.151015E+10 | 0.36 | 3945.98 | 09-NOV-16:10 | 1.14 |
December | 0.112779E+10 | 0.33 | 2359.36 | 04-DEC-07:02 | 0.86 |
Annual Sum or Average | 0.371501E+11 | 0.47 | |||
Minimum of Months | 0.112779E+10 | 0.33 | 1728.44 | 0.73 | |
Maximum of Months | 0.584584E+10 | 0.67 | 10241.24 | 2.07 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128363E+10 | 0.37 | 2438.46 | 27-JAN-07:01 | 0.80 |
February | 0.125207E+10 | 0.39 | 2438.46 | 01-FEB-07:02 | 0.79 |
March | 0.164722E+10 | 0.41 | 3644.00 | 16-MAR-15:30 | 0.99 |
April | 0.257345E+10 | 0.44 | 6543.95 | 21-APR-14:40 | 1.39 |
May | 0.420770E+10 | 0.52 | 9864.98 | 30-MAY-14:50 | 1.79 |
June | 0.581393E+10 | 0.62 | 11251.43 | 19-JUN-05:12 | 1.94 |
July | 0.545246E+10 | 0.59 | 12136.98 | 20-JUL-14:55 | 2.02 |
August | 0.522184E+10 | 0.58 | 10121.35 | 07-AUG-14:50 | 1.81 |
September | 0.394862E+10 | 0.50 | 7942.68 | 05-SEP-15:20 | 1.56 |
October | 0.248065E+10 | 0.43 | 7966.88 | 02-OCT-04:02 | 1.56 |
November | 0.149245E+10 | 0.39 | 3458.50 | 09-NOV-15:50 | 0.95 |
December | 0.127101E+10 | 0.37 | 2438.46 | 19-DEC-06:01 | 0.80 |
Annual Sum or Average | 0.366450E+11 | 0.47 | |||
Minimum of Months | 0.125207E+10 | 0.37 | 2438.46 | 0.79 | |
Maximum of Months | 0.581393E+10 | 0.62 | 12136.98 | 2.02 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 56.61 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.55 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 55.69 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.73 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.44 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 56.37 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.28 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 56.60 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.87 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.58 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.05 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 55.68 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.68 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.58 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.10 | 57.10 | 1698.54 | 5905.15 | 26-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.89 | 56.89 | 1707.04 | 5911.72 | 01-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.05 | 56.05 | 1756.52 | 5801.16 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.23 | 56.23 | 1541.99 | 5444.34 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.75 | 56.75 | 1479.41 | 5055.84 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.33 | 57.33 | 1407.98 | 4648.45 | 02-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.53 | 57.53 | 1236.70 | 4355.67 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.06 | 58.06 | 1358.41 | 4366.80 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.14 | 57.14 | 1330.45 | 4644.05 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.07 | 57.07 | 1429.78 | 5065.25 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.42 | 56.42 | 1566.64 | 5483.54 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.23 | 56.23 | 1599.32 | 5782.75 | 28-DEC-12:08 |
Annual Sum or Average | 0.00 | 1508.30 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.05 | 56.05 | 1236.70 | 4355.67 | ||
Maximum of Months | 0.00 | 0.00 | 58.06 | 58.06 | 1756.52 | 5911.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.330601E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.338091E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.468159E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.817119E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.151275E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.222340E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.241675E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.225394E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.182565E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101077E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.461823E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.330444E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.139895E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.330444E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.241675E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.249509E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.227848E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.341915E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.806204E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.150772E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.219618E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.227465E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.204651E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.158387E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.837321E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.305588E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.286634E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.126640E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.227848E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.227465E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.577355E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.399897E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.430493E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.865084E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.162832E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.241679E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.247899E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.220081E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168100E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.849653E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.421489E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.716814E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.146667E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.399897E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.247899E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126852E+10 | 0.670174E+09 | 0.414331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126854E+10 | 0.295727E+10 | 0.281845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168053E+10 | 0.741863E+10 | 0.196856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255792E+10 | 0.217681E+11 | 0.314498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.428649E+10 | 0.432410E+11 | 27541395.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580068E+10 | 0.608295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.574918E+10 | 0.717803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.576365E+10 | 0.665585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471883E+10 | 0.553819E+11 | 3912750.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336880E+10 | 0.280851E+11 | 0.109232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198653E+10 | 0.811657E+10 | 0.140547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124472E+10 | 0.256661E+09 | 0.518296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396944E+11 | 0.367064E+12 | 0.159739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124472E+10 | 0.256661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.580068E+10 | 0.717803E+11 | 0.518296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116655E+10 | 0.606924E+09 | 0.368996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116958E+10 | 0.259415E+10 | 0.207153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161783E+10 | 0.662495E+10 | 0.115144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265819E+10 | 0.220103E+11 | 0.100875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.436123E+10 | 0.428991E+11 | 172801.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.584584E+10 | 0.597079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.552113E+10 | 0.671828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.539511E+10 | 0.595644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410857E+10 | 0.477141E+11 | 798285.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266808E+10 | 0.239673E+11 | 29688247.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151015E+10 | 0.515487E+10 | 0.128237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112779E+10 | 0.212088E+09 | 0.514314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371501E+11 | 0.338239E+12 | 0.134700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112779E+10 | 0.212088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.584584E+10 | 0.671828E+11 | 0.514314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128363E+10 | 0.589995E+09 | 0.724247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125207E+10 | 0.255748E+10 | 0.400011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164722E+10 | 0.677185E+10 | 0.220222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257345E+10 | 0.244033E+11 | 0.224146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420770E+10 | 0.479918E+11 | 2475326.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.581393E+10 | 0.674911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.545246E+10 | 0.748320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.522184E+10 | 0.657425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394862E+10 | 0.518592E+11 | 3790063.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248065E+10 | 0.249468E+11 | 82170364.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149245E+10 | 0.473923E+10 | 0.280436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127101E+10 | 0.209186E+09 | 0.971859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366450E+11 | 0.372134E+12 | 0.262803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125207E+10 | 0.209186E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.581393E+10 | 0.748320E+11 | 0.971859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126852E+10 | 0.00 | 0.00 | 0.00 | 0.177430E+09 | 0.186006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126854E+10 | 0.00 | 0.00 | 0.00 | 0.742123E+09 | 0.137025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168053E+10 | 0.00 | 0.00 | 0.00 | 0.185181E+10 | 0.114925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255792E+10 | 0.00 | 0.00 | 0.00 | 0.535184E+10 | 0.261438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.428649E+10 | 0.00 | 0.00 | 0.00 | 0.108135E+11 | 27541395.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580068E+10 | 0.00 | 0.00 | 0.00 | 0.164334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.574918E+10 | 0.00 | 0.00 | 0.00 | 0.184183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.576365E+10 | 0.00 | 0.00 | 0.00 | 0.167757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471883E+10 | 0.00 | 0.00 | 0.00 | 0.135340E+11 | 3660636.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336880E+10 | 0.00 | 0.00 | 0.00 | 0.663428E+10 | 0.104599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198653E+10 | 0.00 | 0.00 | 0.00 | 0.195149E+10 | 0.680205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124472E+10 | 0.00 | 0.00 | 0.00 | 70181234.01 | 0.198954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.396944E+11 | 0.00 | 0.00 | 0.00 | 0.927541E+11 | 0.744655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124472E+10 | 0.00 | 0.00 | 0.00 | 70181234.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.580068E+10 | 0.00 | 0.00 | 0.00 | 0.184183E+11 | 0.198954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116655E+10 | 0.00 | 0.00 | 0.00 | 0.161107E+09 | 0.116744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116958E+10 | 0.00 | 0.00 | 0.00 | 0.659846E+09 | 0.449059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161783E+10 | 0.00 | 0.00 | 0.00 | 0.164104E+10 | 0.160270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265819E+10 | 0.00 | 0.00 | 0.00 | 0.540384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.436123E+10 | 0.00 | 0.00 | 0.00 | 0.107160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.584584E+10 | 0.00 | 0.00 | 0.00 | 0.161160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.552113E+10 | 0.00 | 0.00 | 0.00 | 0.172254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.539511E+10 | 0.00 | 0.00 | 0.00 | 0.150699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.410857E+10 | 0.00 | 0.00 | 0.00 | 0.117301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266808E+10 | 0.00 | 0.00 | 0.00 | 0.570513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151015E+10 | 0.00 | 0.00 | 0.00 | 0.126914E+10 | 0.276592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112779E+10 | 0.00 | 0.00 | 0.00 | 58113812.37 | 0.168044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371501E+11 | 0.00 | 0.00 | 0.00 | 0.857557E+11 | 0.373380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112779E+10 | 0.00 | 0.00 | 0.00 | 58113812.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.584584E+10 | 0.00 | 0.00 | 0.00 | 0.172254E+11 | 0.168044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.128363E+10 | 0.00 | 0.00 | 0.00 | 0.158278E+09 | 0.433164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125207E+10 | 0.00 | 0.00 | 0.00 | 0.659473E+09 | 0.208742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164722E+10 | 0.00 | 0.00 | 0.00 | 0.169586E+10 | 0.961853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257345E+10 | 0.00 | 0.00 | 0.00 | 0.602990E+10 | 47492894.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420770E+10 | 0.00 | 0.00 | 0.00 | 0.120755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.581393E+10 | 0.00 | 0.00 | 0.00 | 0.183540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.545246E+10 | 0.00 | 0.00 | 0.00 | 0.193374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.522184E+10 | 0.00 | 0.00 | 0.00 | 0.167863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394862E+10 | 0.00 | 0.00 | 0.00 | 0.128614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248065E+10 | 0.00 | 0.00 | 0.00 | 0.600876E+10 | 7123667.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149245E+10 | 0.00 | 0.00 | 0.00 | 0.118761E+10 | 0.153484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127101E+10 | 0.00 | 0.00 | 0.00 | 57529394.20 | 0.583960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366450E+11 | 0.00 | 0.00 | 0.00 | 0.952120E+11 | 0.148100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125207E+10 | 0.00 | 0.00 | 0.00 | 57529394.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.581393E+10 | 0.00 | 0.00 | 0.00 | 0.193374E+11 | 0.583960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.359405E+10 | 0.00 | 0.00 | 16001744.53 | 0.00 | 0.00 | 0.925959E+10 | 0.00 | 0.42 |
February | 0.224486E+10 | 0.00 | 0.00 | 18424924.87 | 0.00 | 0.00 | 0.942237E+10 | 0.00 | 0.48 |
March | 0.124420E+10 | 0.00 | 0.00 | 26118404.59 | 0.00 | 0.00 | 0.114201E+11 | 0.00 | 0.61 |
April | 0.636710E+09 | 0.144621E+09 | 0.00 | 27745830.12 | 14569076.70 | 0.00 | 0.794453E+10 | 0.00 | 0.67 |
May | 0.347458E+09 | 0.567525E+09 | 0.00 | 20683438.57 | 59499009.25 | 0.00 | 0.375516E+10 | 0.00 | 0.60 |
June | 0.116874E+09 | 0.180481E+10 | 0.00 | 10804568.34 | 61969877.33 | 0.00 | 0.878074E+09 | 0.00 | 0.45 |
July | 7880661.39 | 0.572585E+10 | 0.00 | 581492.87 | 0.242002E+09 | 0.00 | 40008457.08 | 0.00 | 0.42 |
August | 45113792.05 | 0.267692E+10 | 0.00 | 9660219.17 | 0.124568E+09 | 0.00 | 0.100954E+10 | 0.00 | 0.57 |
September | 0.221852E+09 | 0.176447E+10 | 0.00 | 15348810.78 | 0.145461E+09 | 0.00 | 0.220981E+10 | 0.00 | 0.58 |
October | 0.608434E+09 | 0.404084E+09 | 0.00 | 30744648.22 | 46730786.99 | 0.00 | 0.998073E+10 | 0.00 | 0.83 |
November | 0.158139E+10 | 0.00 | 0.00 | 27439379.96 | 0.00 | 0.00 | 0.116892E+11 | 0.00 | 0.61 |
December | 0.400698E+10 | 0.00 | 0.00 | 15783251.20 | 0.00 | 0.00 | 0.931959E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.146558E+11 | 0.130883E+11 | 0.00 | 0.219337E+09 | 0.694799E+09 | 0.00 | 0.769287E+11 | 0.00 | 0.55 |
Minimum of Months | 7880661.39 | 0.00 | 0.00 | 581492.87 | 0.00 | 0.00 | 40008457.08 | 0.00 | 0.40 |
Maximum of Months | 0.400698E+10 | 0.572585E+10 | 0.00 | 30744648.22 | 0.242002E+09 | 0.00 | 0.116892E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.788229E+10 | 0.00 | 0.00 | 1821914.01 | 0.00 | 913208.69 | 0.198455E+10 | 0.00 | 0.32 |
February | 0.544860E+10 | 0.00 | 0.00 | 4899940.84 | 0.00 | 0.00 | 0.340150E+10 | 0.00 | 0.39 |
March | 0.410993E+10 | 0.00 | 0.00 | 11482797.76 | 0.00 | 0.00 | 0.589815E+10 | 0.00 | 0.49 |
April | 0.104393E+10 | 89116080.35 | 0.00 | 18840038.03 | 35544762.11 | 0.00 | 0.576414E+10 | 0.00 | 0.53 |
May | 0.522285E+09 | 0.428039E+09 | 0.00 | 16832916.33 | 56992423.80 | 0.00 | 0.281005E+10 | 0.00 | 0.49 |
June | 0.154564E+09 | 0.147202E+10 | 0.00 | 9861031.87 | 65827686.36 | 0.00 | 0.756374E+09 | 0.00 | 0.40 |
July | 9272391.96 | 0.463557E+10 | 0.00 | 773629.78 | 0.288595E+09 | 0.00 | 49141894.09 | 0.00 | 0.37 |
August | 0.113743E+09 | 0.207956E+10 | 0.00 | 8844345.06 | 0.114426E+09 | 0.00 | 0.782223E+09 | 0.00 | 0.48 |
September | 0.313835E+09 | 0.130603E+10 | 0.00 | 12316134.64 | 0.123236E+09 | 0.00 | 0.159012E+10 | 0.00 | 0.47 |
October | 0.101343E+10 | 0.317781E+09 | 0.00 | 19397132.67 | 37745669.47 | 0.00 | 0.645489E+10 | 0.00 | 0.61 |
November | 0.458042E+10 | 0.00 | 0.00 | 10199669.67 | 0.00 | 0.00 | 0.518996E+10 | 0.00 | 0.46 |
December | 0.871438E+10 | 0.00 | 0.00 | 1212158.88 | 0.00 | 10531123.23 | 0.146851E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.339067E+11 | 0.103281E+11 | 0.00 | 0.116482E+09 | 0.722368E+09 | 11444331.92 | 0.361496E+11 | 0.00 | 0.44 |
Minimum of Months | 9272391.96 | 0.00 | 0.00 | 773629.78 | 0.00 | 0.00 | 49141894.09 | 0.00 | 0.31 |
Maximum of Months | 0.871438E+10 | 0.463557E+10 | 0.00 | 19397132.67 | 0.288595E+09 | 10531123.23 | 0.645489E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.807030E+10 | 0.00 | 0.00 | 618235.73 | 0.00 | 0.360730E+09 | 0.707003E+09 | 0.00 | 0.31 |
February | 0.610091E+10 | 0.00 | 0.00 | 2600449.78 | 0.00 | 0.109769E+09 | 0.203948E+10 | 0.00 | 0.37 |
March | 0.496604E+10 | 0.00 | 0.00 | 7745897.95 | 0.00 | 32966479.79 | 0.439795E+10 | 0.00 | 0.48 |
April | 0.146595E+10 | 52433264.88 | 0.00 | 17329572.94 | 16538079.50 | 0.00 | 0.482519E+10 | 0.00 | 0.54 |
May | 0.617870E+09 | 0.363861E+09 | 0.00 | 16758848.65 | 91582253.05 | 0.00 | 0.233214E+10 | 0.00 | 0.50 |
June | 0.164074E+09 | 0.135665E+10 | 0.00 | 9957164.04 | 79242341.93 | 0.00 | 0.527826E+09 | 0.00 | 0.39 |
July | 6956138.51 | 0.466885E+10 | 0.00 | 901106.09 | 0.420719E+09 | 0.00 | 24777318.41 | 0.00 | 0.37 |
August | 96997498.44 | 0.212749E+10 | 0.00 | 8508914.53 | 0.166950E+09 | 0.00 | 0.531780E+09 | 0.00 | 0.47 |
September | 0.386254E+09 | 0.132348E+10 | 0.00 | 10472026.43 | 0.224598E+09 | 0.00 | 0.103802E+10 | 0.00 | 0.45 |
October | 0.156124E+10 | 0.343434E+09 | 0.00 | 13931514.94 | 42602371.63 | 0.00 | 0.473838E+10 | 0.00 | 0.58 |
November | 0.537111E+10 | 0.00 | 0.00 | 5672028.78 | 0.00 | 88470345.24 | 0.323262E+10 | 0.00 | 0.42 |
December | 0.840069E+10 | 0.00 | 0.00 | 201462.84 | 0.00 | 0.616491E+09 | 0.395796E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.372084E+11 | 0.102362E+11 | 0.00 | 94697222.71 | 0.104223E+10 | 0.120843E+10 | 0.247910E+11 | 0.00 | 0.43 |
Minimum of Months | 6956138.51 | 0.00 | 0.00 | 201462.84 | 0.00 | 0.00 | 24777318.41 | 0.00 | 0.30 |
Maximum of Months | 0.840069E+10 | 0.466885E+10 | 0.00 | 17329572.94 | 0.420719E+09 | 0.616491E+09 | 0.482519E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115990E+10 | 0.00 | 0.00 | 96.02 | 0.00 | 0.835634E+09 | 3515643.11 | 0.00 | 0.32 |
February | 0.123933E+10 | 0.00 | 0.00 | 172906.02 | 0.00 | 0.424751E+09 | 78328407.84 | 0.00 | 0.37 |
March | 0.123968E+10 | 0.00 | 0.00 | 995288.44 | 0.00 | 0.212794E+09 | 0.472930E+09 | 0.00 | 0.47 |
April | 0.527451E+09 | 19727087.69 | 0.00 | 3610609.99 | 1923720.28 | 11042501.78 | 0.737851E+09 | 0.00 | 0.56 |
May | 0.162215E+09 | 0.124952E+09 | 0.00 | 4361678.79 | 19732629.72 | 0.00 | 0.492349E+09 | 0.00 | 0.62 |
June | 38532004.72 | 0.507195E+09 | 0.00 | 2928473.82 | 14870077.12 | 0.00 | 0.136344E+09 | 0.00 | 0.58 |
July | 2941876.66 | 0.149467E+10 | 0.00 | 252337.05 | 84389293.96 | 0.00 | 4104222.39 | 0.00 | 0.53 |
August | 27657528.66 | 0.628092E+09 | 0.00 | 2129029.33 | 35158069.09 | 0.00 | 0.116034E+09 | 0.00 | 0.60 |
September | 0.106917E+09 | 0.350075E+09 | 0.00 | 2362821.47 | 51215116.60 | 0.00 | 0.186695E+09 | 0.00 | 0.51 |
October | 0.593266E+09 | 88382581.99 | 0.00 | 2195926.04 | 9754934.91 | 3114809.28 | 0.606490E+09 | 0.00 | 0.56 |
November | 0.127987E+10 | 0.00 | 0.00 | 433326.57 | 0.00 | 0.277570E+09 | 0.193712E+09 | 0.00 | 0.40 |
December | 0.995029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109918E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.737279E+10 | 0.321309E+10 | 0.00 | 19442493.54 | 0.217044E+09 | 0.286408E+10 | 0.302835E+10 | 0.00 | 0.49 |
Minimum of Months | 2941876.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.127987E+10 | 0.149467E+10 | 0.00 | 4361678.79 | 84389293.96 | 0.109918E+10 | 0.737851E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.857054E+09 | 0.00 | 0.00 | 117396.29 | 0.00 | 0.304332E+09 | 0.100954E+09 | 0.00 | 0.32 |
February | 0.656365E+09 | 0.00 | 0.00 | 773888.74 | 0.00 | 0.114954E+09 | 0.464232E+09 | 0.00 | 0.43 |
March | 0.535195E+09 | 0.00 | 0.00 | 2722844.57 | 0.00 | 70542378.49 | 0.128037E+10 | 0.00 | 0.73 |
April | 0.169446E+09 | 18053575.15 | 0.00 | 6053954.92 | 996657.64 | 423129.95 | 0.154697E+10 | 0.00 | 1.13 |
May | 57436050.39 | 0.120302E+09 | 0.00 | 6123582.76 | 8892652.62 | 0.00 | 0.898542E+09 | 0.00 | 1.20 |
June | 20270467.50 | 0.424954E+09 | 0.00 | 3330282.22 | 7055425.71 | 0.00 | 0.168374E+09 | 0.00 | 0.92 |
July | 1144431.63 | 0.142323E+10 | 0.00 | 278504.60 | 36075700.59 | 0.00 | 5477736.68 | 0.00 | 0.80 |
August | 13754010.22 | 0.655241E+09 | 0.00 | 2179051.56 | 13674172.91 | 0.00 | 0.128132E+09 | 0.00 | 0.96 |
September | 49277525.19 | 0.459631E+09 | 0.00 | 3087162.09 | 18307871.21 | 0.00 | 0.329692E+09 | 0.00 | 0.99 |
October | 0.258921E+09 | 75684889.21 | 0.00 | 3390389.45 | 5056774.56 | 386838.26 | 0.107373E+10 | 0.00 | 0.92 |
November | 0.600009E+09 | 0.00 | 0.00 | 1373385.20 | 0.00 | 0.104215E+09 | 0.643963E+09 | 0.00 | 0.52 |
December | 0.878092E+09 | 0.00 | 0.00 | 1886.93 | 0.00 | 0.417630E+09 | 5989655.35 | 0.00 | 0.31 |
Annual Sum or Average | 0.409697E+10 | 0.317710E+10 | 0.00 | 29432329.32 | 90059255.23 | 0.101248E+10 | 0.664644E+10 | 0.00 | 0.77 |
Minimum of Months | 1144431.63 | 0.00 | 0.00 | 1886.93 | 0.00 | 0.00 | 5477736.68 | 0.00 | 0.31 |
Maximum of Months | 0.878092E+09 | 0.142323E+10 | 0.00 | 6123582.76 | 36075700.59 | 0.417630E+09 | 0.154697E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.787660E+09 | 0.00 | 0.00 | 5082164.88 | 0.00 | 0.311181E+09 | 0.277884E+10 | 0.00 | 0.66 |
February | 0.710290E+09 | 0.00 | 0.00 | 5440515.96 | 0.00 | 0.154949E+09 | 0.261606E+10 | 0.00 | 0.78 |
March | 0.726274E+09 | 0.00 | 0.00 | 6197449.38 | 0.00 | 0.123653E+09 | 0.285384E+10 | 0.00 | 0.95 |
April | 0.398547E+09 | 35279664.87 | 0.00 | 6688251.79 | 1585887.94 | 11396676.75 | 0.149701E+10 | 0.00 | 0.85 |
May | 0.173444E+09 | 0.142047E+09 | 0.00 | 4792433.35 | 19239177.88 | 0.00 | 0.543408E+09 | 0.00 | 0.67 |
June | 41804872.40 | 0.495139E+09 | 0.00 | 2824278.63 | 16653151.90 | 0.00 | 0.121896E+09 | 0.00 | 0.55 |
July | 3310278.31 | 0.148292E+10 | 0.00 | 262003.63 | 85981891.64 | 0.00 | 3323828.73 | 0.00 | 0.52 |
August | 27018867.33 | 0.737379E+09 | 0.00 | 2632948.82 | 33780395.49 | 0.00 | 0.138949E+09 | 0.00 | 0.69 |
September | 74330133.22 | 0.567019E+09 | 0.00 | 4675628.02 | 38398012.28 | 0.00 | 0.392912E+09 | 0.00 | 0.79 |
October | 0.346062E+09 | 0.168725E+09 | 0.00 | 9071469.65 | 3656033.66 | 208822.08 | 0.243067E+10 | 0.00 | 1.31 |
November | 0.670555E+09 | 0.00 | 0.00 | 7704321.59 | 0.00 | 0.143460E+09 | 0.353256E+10 | 0.00 | 1.11 |
December | 0.800979E+09 | 0.00 | 0.00 | 4619955.60 | 0.00 | 0.404218E+09 | 0.253669E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.476028E+10 | 0.362851E+10 | 0.00 | 59991421.30 | 0.199295E+09 | 0.114907E+10 | 0.194461E+11 | 0.00 | 0.79 |
Minimum of Months | 3310278.31 | 0.00 | 0.00 | 262003.63 | 0.00 | 0.00 | 3323828.73 | 0.00 | 0.52 |
Maximum of Months | 0.800979E+09 | 0.148292E+10 | 0.00 | 9071469.65 | 85981891.64 | 0.404218E+09 | 0.353256E+10 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.634470E+09 | 0.00 | 0.00 | 623608.21 | 0.00 | 0.419056E+09 | 0.424843E+09 | 0.00 | 0.39 |
February | 0.650928E+09 | 0.00 | 0.00 | 1046613.75 | 0.00 | 0.209081E+09 | 0.534216E+09 | 0.00 | 0.49 |
March | 0.598207E+09 | 0.00 | 0.00 | 2779600.82 | 0.00 | 0.109584E+09 | 0.123553E+10 | 0.00 | 0.82 |
April | 0.267936E+09 | 25230267.85 | 0.00 | 4957320.16 | 330490.23 | 6967792.11 | 0.103434E+10 | 0.00 | 0.93 |
May | 0.104022E+09 | 0.131415E+09 | 0.00 | 4081168.21 | 7597143.74 | 0.00 | 0.410019E+09 | 0.00 | 0.86 |
June | 23929674.16 | 0.469531E+09 | 0.00 | 2362234.72 | 7014277.62 | 0.00 | 94219401.88 | 0.00 | 0.72 |
July | 1492442.60 | 0.121810E+10 | 0.00 | 210222.64 | 44193241.10 | 0.00 | 2898311.45 | 0.00 | 0.65 |
August | 16972904.52 | 0.536385E+09 | 0.00 | 1838954.58 | 19494678.62 | 0.00 | 86998090.81 | 0.00 | 0.78 |
September | 54706818.50 | 0.324000E+09 | 0.00 | 2864058.73 | 25486682.34 | 0.00 | 0.220831E+09 | 0.00 | 0.73 |
October | 0.291140E+09 | 92090437.86 | 0.00 | 3605168.99 | 3095202.13 | 686962.69 | 0.913233E+09 | 0.00 | 0.96 |
November | 0.624054E+09 | 0.00 | 0.00 | 1730411.34 | 0.00 | 0.157934E+09 | 0.846699E+09 | 0.00 | 0.65 |
December | 0.583585E+09 | 0.00 | 0.00 | 382961.09 | 0.00 | 0.553038E+09 | 0.318830E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.385144E+10 | 0.279675E+10 | 0.00 | 26482323.24 | 0.107212E+09 | 0.145635E+10 | 0.612265E+10 | 0.00 | 0.69 |
Minimum of Months | 1492442.60 | 0.00 | 0.00 | 210222.64 | 0.00 | 0.00 | 2898311.45 | 0.00 | 0.35 |
Maximum of Months | 0.650928E+09 | 0.121810E+10 | 0.00 | 4957320.16 | 44193241.10 | 0.553038E+09 | 0.123553E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436831E+09 | 0.00 | 0.00 | 0.32 |
February | 0.145320E+10 | 0.00 | 0.00 | 2661.50 | 0.00 | 0.293788E+09 | 4440234.20 | 0.00 | 0.34 |
March | 0.152939E+10 | 0.00 | 0.00 | 109700.61 | 0.00 | 0.154632E+09 | 50935749.12 | 0.00 | 0.38 |
April | 0.682273E+09 | 19611037.14 | 0.00 | 1519321.80 | 10453424.68 | 243077.73 | 0.311143E+09 | 0.00 | 0.39 |
May | 0.214037E+09 | 0.125294E+09 | 0.00 | 2438320.43 | 13340120.08 | 0.00 | 0.319234E+09 | 0.00 | 0.44 |
June | 53999082.94 | 0.487038E+09 | 0.00 | 1877964.92 | 16203442.14 | 0.00 | 0.117608E+09 | 0.00 | 0.46 |
July | 2414741.47 | 0.138099E+10 | 0.00 | 75196.15 | 67405672.60 | 0.00 | 6239722.15 | 0.00 | 0.47 |
August | 30650598.73 | 0.656257E+09 | 0.00 | 1685433.36 | 26391269.93 | 0.00 | 0.146332E+09 | 0.00 | 0.57 |
September | 0.106131E+09 | 0.403262E+09 | 0.00 | 2240447.90 | 34999024.73 | 0.00 | 0.258770E+09 | 0.00 | 0.51 |
October | 0.497595E+09 | 88291781.30 | 0.00 | 2791075.85 | 10254050.57 | 0.00 | 0.850099E+09 | 0.00 | 0.56 |
November | 0.144438E+10 | 0.00 | 0.00 | 556821.87 | 0.00 | 28694247.13 | 0.288541E+09 | 0.00 | 0.37 |
December | 0.172555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492752E+09 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.941426E+10 | 0.316074E+10 | 0.00 | 13296944.39 | 0.179047E+09 | 0.140694E+10 | 0.235334E+10 | 0.00 | 0.43 |
Minimum of Months | 2414741.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.172555E+10 | 0.138099E+10 | 0.00 | 2791075.85 | 67405672.60 | 0.492752E+09 | 0.850099E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111191E+10 | 0.00 | 0.00 | 144327.92 | 0.00 | 0.110409E+09 | 0.128845E+09 | 0.00 | 0.32 |
February | 0.827131E+09 | 0.00 | 0.00 | 622098.87 | 0.00 | 36018621.90 | 0.326918E+09 | 0.00 | 0.37 |
March | 0.658496E+09 | 0.00 | 0.00 | 1900837.92 | 0.00 | 25570639.33 | 0.772081E+09 | 0.00 | 0.52 |
April | 0.192732E+09 | 27988314.51 | 0.00 | 4256898.19 | 1945092.66 | 0.00 | 0.113980E+10 | 0.00 | 0.83 |
May | 68471505.22 | 0.132560E+09 | 0.00 | 4403458.34 | 5882761.10 | 0.00 | 0.752724E+09 | 0.00 | 0.93 |
June | 23109050.90 | 0.446682E+09 | 0.00 | 2481637.90 | 6773987.03 | 0.00 | 0.166087E+09 | 0.00 | 0.78 |
July | 689536.31 | 0.133746E+10 | 0.00 | 145013.63 | 26822927.54 | 0.00 | 8577581.87 | 0.00 | 0.72 |
August | 15435504.17 | 0.672385E+09 | 0.00 | 1849782.61 | 10420791.70 | 0.00 | 0.167896E+09 | 0.00 | 0.93 |
September | 47061527.56 | 0.457489E+09 | 0.00 | 3233164.96 | 13076700.19 | 0.00 | 0.447631E+09 | 0.00 | 0.98 |
October | 0.187435E+09 | 79009074.06 | 0.00 | 4384117.90 | 5127017.50 | 0.00 | 0.138860E+10 | 0.00 | 0.99 |
November | 0.645781E+09 | 0.00 | 0.00 | 2268839.15 | 0.00 | 2913417.36 | 0.878614E+09 | 0.00 | 0.54 |
December | 0.112945E+10 | 0.00 | 0.00 | 135996.61 | 0.00 | 0.141391E+09 | 0.144365E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.490770E+10 | 0.315358E+10 | 0.00 | 25826174.00 | 70049277.71 | 0.316302E+09 | 0.632214E+10 | 0.00 | 0.69 |
Minimum of Months | 689536.31 | 0.00 | 0.00 | 135996.61 | 0.00 | 0.00 | 8577581.87 | 0.00 | 0.31 |
Maximum of Months | 0.112945E+10 | 0.133746E+10 | 0.00 | 4403458.34 | 26822927.54 | 0.141391E+09 | 0.138860E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119432E+10 | 0.00 | 0.00 | 2467600.16 | 0.00 | 0.575722E+09 | 0.150704E+10 | 0.00 | 0.53 |
February | 0.102068E+10 | 0.00 | 0.00 | 2311538.70 | 0.00 | 0.441917E+09 | 0.997069E+09 | 0.00 | 0.52 |
March | 0.108889E+10 | 0.00 | 0.00 | 2413639.37 | 0.00 | 0.447210E+09 | 0.881995E+09 | 0.00 | 0.58 |
April | 0.560898E+09 | 58858883.97 | 0.00 | 3316776.86 | 3072311.89 | 0.117454E+09 | 0.551077E+09 | 0.00 | 0.55 |
May | 0.256099E+09 | 0.177032E+09 | 0.00 | 2618062.92 | 13505164.66 | 14537275.32 | 0.266545E+09 | 0.00 | 0.49 |
June | 77717251.78 | 0.587571E+09 | 0.00 | 1675540.84 | 18030702.36 | 0.00 | 71733026.64 | 0.00 | 0.48 |
July | 5429912.62 | 0.150035E+10 | 0.00 | 24287.36 | 93485103.42 | 0.00 | 1100816.63 | 0.00 | 0.49 |
August | 49018251.72 | 0.881310E+09 | 0.00 | 1791976.83 | 32773711.80 | 0.00 | 0.127575E+09 | 0.00 | 0.68 |
September | 0.110667E+09 | 0.683090E+09 | 0.00 | 3991328.06 | 34001043.56 | 1462536.57 | 0.394394E+09 | 0.00 | 0.79 |
October | 0.331134E+09 | 0.187700E+09 | 0.00 | 8924046.53 | 3066715.01 | 45919432.92 | 0.223545E+10 | 0.00 | 1.22 |
November | 0.673979E+09 | 0.00 | 0.00 | 7435165.92 | 0.00 | 0.304184E+09 | 0.269887E+10 | 0.00 | 0.90 |
December | 0.120082E+10 | 0.00 | 0.00 | 2428808.69 | 0.00 | 0.697466E+09 | 0.152915E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.656967E+10 | 0.407591E+10 | 0.00 | 39398772.26 | 0.197935E+09 | 0.264587E+10 | 0.112620E+11 | 0.00 | 0.65 |
Minimum of Months | 5429912.62 | 0.00 | 0.00 | 24287.36 | 0.00 | 0.00 | 1100816.63 | 0.00 | 0.48 |
Maximum of Months | 0.120082E+10 | 0.150035E+10 | 0.00 | 8924046.53 | 93485103.42 | 0.697466E+09 | 0.269887E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103210E+10 | 0.00 | 0.00 | 447426.38 | 0.00 | 0.118034E+09 | 0.308311E+09 | 0.00 | 0.36 |
February | 0.876732E+09 | 0.00 | 0.00 | 574315.01 | 0.00 | 76089571.68 | 0.261979E+09 | 0.00 | 0.38 |
March | 0.783410E+09 | 0.00 | 0.00 | 1501471.85 | 0.00 | 28981565.09 | 0.574430E+09 | 0.00 | 0.54 |
April | 0.282417E+09 | 36816168.80 | 0.00 | 3072325.37 | 1885858.91 | 0.00 | 0.665787E+09 | 0.00 | 0.65 |
May | 0.104502E+09 | 0.153040E+09 | 0.00 | 2713807.64 | 4921768.53 | 0.00 | 0.344280E+09 | 0.00 | 0.69 |
June | 27144513.27 | 0.501955E+09 | 0.00 | 1562534.32 | 5817947.89 | 0.00 | 97343001.61 | 0.00 | 0.64 |
July | 937342.35 | 0.122228E+10 | 0.00 | 65816.75 | 29554190.14 | 0.00 | 4855744.13 | 0.00 | 0.61 |
August | 16511035.96 | 0.619562E+09 | 0.00 | 1394758.47 | 11034958.05 | 0.00 | 0.115290E+09 | 0.00 | 0.79 |
September | 40547309.66 | 0.404926E+09 | 0.00 | 2620593.34 | 14579515.23 | 0.00 | 0.298943E+09 | 0.00 | 0.77 |
October | 0.181016E+09 | 96586762.58 | 0.00 | 4231607.17 | 3406673.28 | 0.00 | 0.117152E+10 | 0.00 | 0.98 |
November | 0.672088E+09 | 0.00 | 0.00 | 2122145.49 | 0.00 | 6149844.87 | 0.837808E+09 | 0.00 | 0.57 |
December | 0.105246E+10 | 0.00 | 0.00 | 375710.72 | 0.00 | 0.162653E+09 | 0.298566E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.506987E+10 | 0.303516E+10 | 0.00 | 20682512.52 | 71200912.03 | 0.391908E+09 | 0.497911E+10 | 0.00 | 0.61 |
Minimum of Months | 937342.35 | 0.00 | 0.00 | 65816.75 | 0.00 | 0.00 | 4855744.13 | 0.00 | 0.34 |
Maximum of Months | 0.105246E+10 | 0.122228E+10 | 0.00 | 4231607.17 | 29554190.14 | 0.162653E+09 | 0.117152E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166665E+10 | 0.00 | 0.00 | 8408.61 | 0.00 | 0.388064E+09 | 18175025.75 | 0.00 | 0.32 |
February | 0.150542E+10 | 0.00 | 0.00 | 198492.82 | 0.00 | 0.177555E+09 | 0.109237E+09 | 0.00 | 0.37 |
March | 0.140577E+10 | 0.00 | 0.00 | 1110707.25 | 0.00 | 64290997.30 | 0.476470E+09 | 0.00 | 0.46 |
April | 0.514235E+09 | 34560744.69 | 0.00 | 3409860.80 | 3961783.25 | 0.00 | 0.778925E+09 | 0.00 | 0.53 |
May | 0.157894E+09 | 0.160460E+09 | 0.00 | 4049809.16 | 12071621.11 | 0.00 | 0.548985E+09 | 0.00 | 0.60 |
June | 46327885.59 | 0.580097E+09 | 0.00 | 2751084.82 | 13366881.07 | 0.00 | 0.175594E+09 | 0.00 | 0.59 |
July | 2412284.61 | 0.151414E+10 | 0.00 | 169882.93 | 59767642.34 | 0.00 | 9998660.79 | 0.00 | 0.54 |
August | 33152097.95 | 0.638463E+09 | 0.00 | 2087680.17 | 24427089.51 | 0.00 | 0.157214E+09 | 0.00 | 0.61 |
September | 0.119998E+09 | 0.365533E+09 | 0.00 | 2312346.30 | 29323581.83 | 0.00 | 0.233095E+09 | 0.00 | 0.51 |
October | 0.561802E+09 | 86394731.83 | 0.00 | 2661082.03 | 7968989.36 | 0.00 | 0.748779E+09 | 0.00 | 0.56 |
November | 0.144716E+10 | 0.00 | 0.00 | 588185.30 | 0.00 | 0.102599E+09 | 0.296252E+09 | 0.00 | 0.41 |
December | 0.154931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611681E+09 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.901013E+10 | 0.337965E+10 | 0.00 | 19347540.19 | 0.150888E+09 | 0.134419E+10 | 0.355273E+10 | 0.00 | 0.48 |
Minimum of Months | 2412284.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.166665E+10 | 0.151414E+10 | 0.00 | 4049809.16 | 59767642.34 | 0.611681E+09 | 0.778925E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.792063E+09 | 0.00 | 0.00 | 279500.86 | 0.00 | 0.146221E+09 | 0.193493E+09 | 0.00 | 0.28 |
February | 0.601411E+09 | 0.00 | 0.00 | 1073350.49 | 0.00 | 42022845.88 | 0.570344E+09 | 0.00 | 0.40 |
March | 0.535816E+09 | 0.00 | 0.00 | 2869924.78 | 0.00 | 20058672.12 | 0.127743E+10 | 0.00 | 0.68 |
April | 0.160745E+09 | 30220335.94 | 0.00 | 5722880.32 | 2015044.96 | 0.00 | 0.156584E+10 | 0.00 | 1.04 |
May | 63016730.88 | 0.135726E+09 | 0.00 | 5607415.17 | 5754900.12 | 0.00 | 0.934999E+09 | 0.00 | 1.10 |
June | 20563080.69 | 0.455232E+09 | 0.00 | 3287999.72 | 7170336.67 | 0.00 | 0.214374E+09 | 0.00 | 0.91 |
July | 1027318.46 | 0.134557E+10 | 0.00 | 233569.92 | 25593343.30 | 0.00 | 11348755.60 | 0.00 | 0.78 |
August | 17457841.90 | 0.611175E+09 | 0.00 | 2073745.07 | 9417084.55 | 0.00 | 0.167204E+09 | 0.00 | 0.93 |
September | 53566554.22 | 0.395434E+09 | 0.00 | 3157315.32 | 13408916.28 | 0.00 | 0.409773E+09 | 0.00 | 0.94 |
October | 0.245662E+09 | 67395921.98 | 0.00 | 3685233.86 | 4485637.06 | 0.00 | 0.113508E+10 | 0.00 | 0.87 |
November | 0.590523E+09 | 0.00 | 0.00 | 1819046.79 | 0.00 | 39778066.70 | 0.762308E+09 | 0.00 | 0.50 |
December | 0.814936E+09 | 0.00 | 0.00 | 136140.97 | 0.00 | 0.225223E+09 | 0.108915E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.389679E+10 | 0.304075E+10 | 0.00 | 29946123.28 | 67845262.94 | 0.473303E+09 | 0.735111E+10 | 0.00 | 0.73 |
Minimum of Months | 1027318.46 | 0.00 | 0.00 | 136140.97 | 0.00 | 0.00 | 11348755.60 | 0.00 | 0.26 |
Maximum of Months | 0.814936E+09 | 0.134557E+10 | 0.00 | 5722880.32 | 25593343.30 | 0.225223E+09 | 0.156584E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.960663E+09 | 0.00 | 0.00 | 6096155.54 | 0.00 | 0.151379E+09 | 0.314034E+10 | 0.00 | 0.72 |
February | 0.833194E+09 | 0.00 | 0.00 | 6232453.80 | 0.00 | 59831866.25 | 0.277207E+10 | 0.00 | 0.83 |
March | 0.830085E+09 | 0.00 | 0.00 | 6711278.82 | 0.00 | 19734283.05 | 0.279232E+10 | 0.00 | 0.95 |
April | 0.409653E+09 | 67273901.18 | 0.00 | 6012379.63 | 3182641.35 | 0.00 | 0.144458E+10 | 0.00 | 0.80 |
May | 0.175970E+09 | 0.187311E+09 | 0.00 | 4299653.64 | 12193217.05 | 0.00 | 0.564110E+09 | 0.00 | 0.64 |
June | 50906892.05 | 0.575805E+09 | 0.00 | 2567735.72 | 13959390.96 | 0.00 | 0.151441E+09 | 0.00 | 0.56 |
July | 2407919.11 | 0.151357E+10 | 0.00 | 160055.38 | 61734160.64 | 0.00 | 8838673.32 | 0.00 | 0.53 |
August | 32006298.39 | 0.764846E+09 | 0.00 | 2476705.45 | 25037006.77 | 0.00 | 0.176674E+09 | 0.00 | 0.70 |
September | 85303895.53 | 0.596729E+09 | 0.00 | 4248288.08 | 26623133.32 | 0.00 | 0.426209E+09 | 0.00 | 0.77 |
October | 0.350353E+09 | 0.169749E+09 | 0.00 | 9505703.44 | 4246539.38 | 0.00 | 0.241743E+10 | 0.00 | 1.26 |
November | 0.743872E+09 | 0.00 | 0.00 | 9131044.43 | 0.00 | 30485870.04 | 0.370703E+10 | 0.00 | 1.15 |
December | 0.102676E+10 | 0.00 | 0.00 | 5762734.46 | 0.00 | 0.205466E+09 | 0.298971E+10 | 0.00 | 0.67 |
Annual Sum or Average | 0.550118E+10 | 0.387528E+10 | 0.00 | 63204188.40 | 0.146976E+09 | 0.466897E+09 | 0.205908E+11 | 0.00 | 0.80 |
Minimum of Months | 2407919.11 | 0.00 | 0.00 | 160055.38 | 0.00 | 0.00 | 8838673.32 | 0.00 | 0.53 |
Maximum of Months | 0.102676E+10 | 0.151357E+10 | 0.00 | 9505703.44 | 61734160.64 | 0.205466E+09 | 0.370703E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.906291E+09 | 0.00 | 0.00 | 743206.36 | 0.00 | 0.185685E+09 | 0.456585E+09 | 0.00 | 0.40 |
February | 0.769791E+09 | 0.00 | 0.00 | 1165650.32 | 0.00 | 90821057.41 | 0.563742E+09 | 0.00 | 0.50 |
March | 0.692805E+09 | 0.00 | 0.00 | 2880110.90 | 0.00 | 23469963.39 | 0.114744E+10 | 0.00 | 0.79 |
April | 0.265135E+09 | 49640881.66 | 0.00 | 4371188.73 | 794045.23 | 0.00 | 0.989970E+09 | 0.00 | 0.87 |
May | 0.102857E+09 | 0.178426E+09 | 0.00 | 3516140.69 | 3513641.17 | 0.00 | 0.424172E+09 | 0.00 | 0.82 |
June | 28329078.33 | 0.566447E+09 | 0.00 | 2063669.06 | 4792166.17 | 0.00 | 0.115191E+09 | 0.00 | 0.75 |
July | 1296299.89 | 0.126390E+10 | 0.00 | 110827.47 | 30064727.04 | 0.00 | 6132277.88 | 0.00 | 0.67 |
August | 20478484.13 | 0.569929E+09 | 0.00 | 1701003.51 | 11384586.19 | 0.00 | 0.110338E+09 | 0.00 | 0.79 |
September | 61591307.36 | 0.346462E+09 | 0.00 | 2592072.67 | 13874718.69 | 0.00 | 0.242274E+09 | 0.00 | 0.73 |
October | 0.269726E+09 | 91442346.10 | 0.00 | 3744525.65 | 3247448.80 | 0.00 | 0.951703E+09 | 0.00 | 0.92 |
November | 0.731044E+09 | 0.00 | 0.00 | 2015054.70 | 0.00 | 49010822.03 | 0.883598E+09 | 0.00 | 0.66 |
December | 0.881651E+09 | 0.00 | 0.00 | 500428.26 | 0.00 | 0.287537E+09 | 0.369617E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.473100E+10 | 0.306624E+10 | 0.00 | 25403878.30 | 67671333.29 | 0.636523E+09 | 0.626076E+10 | 0.00 | 0.69 |
Minimum of Months | 1296299.89 | 0.00 | 0.00 | 110827.47 | 0.00 | 0.00 | 6132277.88 | 0.00 | 0.36 |
Maximum of Months | 0.906291E+09 | 0.126390E+10 | 0.00 | 4371188.73 | 30064727.04 | 0.287537E+09 | 0.114744E+10 | 0.00 | 0.92 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.213795E+12 | 0.109976E+11 | 0.00 | 0.166847E+12 | 0.429306E+10 |
February | 0.216816E+12 | 0.901122E+10 | 0.00 | 0.147776E+12 | 0.114162E+11 |
March | 0.310355E+12 | 0.951023E+10 | 0.00 | 0.179958E+12 | 0.267668E+11 |
April | 0.317965E+12 | 0.476691E+10 | 0.00 | 0.139561E+12 | 0.850500E+11 |
May | 0.329583E+12 | 0.168559E+10 | 0.00 | 0.958578E+11 | 0.167738E+12 |
June | 0.318244E+12 | -0.156145E+10 | 0.00 | 0.149811E+11 | 0.238932E+12 |
July | 0.316655E+12 | -0.436380E+10 | 0.00 | -0.774429E+11 | 0.268776E+12 |
August | 0.295661E+12 | -0.200231E+10 | 0.00 | -0.193481E+11 | 0.240497E+12 |
September | 0.279704E+12 | -262668600.2 | 0.00 | 0.129338E+11 | 0.193082E+12 |
October | 0.260592E+12 | 0.384944E+10 | 0.00 | 0.140132E+12 | 0.953747E+11 |
November | 0.215769E+12 | 0.898432E+10 | 0.00 | 0.184527E+12 | 0.231691E+11 |
December | 0.184876E+12 | 0.100684E+11 | 0.00 | 0.158371E+12 | 0.349754E+10 |
Annual Sum or Average | 0.326001E+13 | 0.506835E+11 | 0.00 | 0.114415E+13 | 0.135859E+13 |
Minimum of Months | 0.184876E+12 | -0.436380E+10 | 0.00 | -0.774429E+11 | 0.349754E+10 |
Maximum of Months | 0.329583E+12 | 0.109976E+11 | 0.00 | 0.184527E+12 | 0.268776E+12 |