Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:32:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1953.16 | 392.03 | 392.03 |
Net Site Energy | 1821.11 | 365.52 | 365.52 |
Total Source Energy | 5063.62 | 1016.34 | 1016.34 |
Net Source Energy | 4645.40 | 932.40 | 932.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 343.79 | 399.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 166.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 83.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 139.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1414.49 | 538.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 343.79 | 399.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 126.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 166.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 83.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 139.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 343.79 | 399.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 126.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 166.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 83.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 139.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.17 | 108.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 283.91 | 108.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.17 | 108.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 283.91 | 108.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 138.244 | 9.77 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -6.19 | -0.4 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 132.053 | 9.34 |
Electricity Coming From Utility | 1283.714 | 90.75 |
Surplus Electricity Going To Utility | 1.276 | 0.09 |
Net Electricity From Utility | 1282.439 | 90.66 |
Total On-Site and Utility Electric Sources | 1414.492 | 100.00 |
Total Electricity End Uses | 1414.492 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 557.83 |
Time Setpoint Not Met During Occupied Cooling | 110.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3137.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JAN-07:10 | 02-FEB-12:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 201872.72 | 142854.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7289.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12632.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 237473.55 | 155487.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 201872.72 | 142854.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2981.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 36.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7289.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 12632.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1088.78 | 433.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 399.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 528.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 108.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 150.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4479.70 | 583.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 218.54 | 86.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 80.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 899.14 | 117.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 218.54 | 86.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 80.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 899.14 | 117.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.45 | 0.305287 | 0.259000 | 0.635824 | 0.814099 | 0.500000 | 0.001248 |
CORE_MID VAV BOX COMPONENT | 2.06 | 0.364107 | 0.309000 | 0.636025 | 0.970953 | 0.500000 | 0.001046 |
CORE_TOP VAV BOX COMPONENT | 2.14 | 0.350140 | 0.298000 | 0.637852 | 0.933707 | 0.500000 | 0.001088 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.727959 | 0.217034 | 0.199000 | 0.144864 | 0.578757 | 0.500000 | 0.001755 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.817631 | 0.122331 | 0.104000 | 0.085034 | 0.326217 | 0.500000 | 0.003114 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.991158 | 0.159401 | 0.135000 | 0.133806 | 0.425070 | 0.500000 | 0.002390 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.893660 | 0.111916 | 0.095000 | 0.084898 | 0.300000 | 0.500000 | 0.003404 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.542733 | 0.291104 | 0.259000 | 0.140568 | 0.776277 | 0.500000 | 0.001309 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.659907 | 0.151570 | 0.129000 | 0.085128 | 0.404185 | 0.500000 | 0.002514 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.780481 | 0.202429 | 0.172000 | 0.134243 | 0.539810 | 0.500000 | 0.001882 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.700948 | 0.142686 | 0.121000 | 0.084815 | 0.380495 | 0.500000 | 0.002670 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.587167 | 0.269075 | 0.229000 | 0.134461 | 0.717532 | 0.500000 | 0.001416 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.809260 | 0.329591 | 0.500000 | 0.003083 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.906383 | 0.174310 | 0.148000 | 0.134145 | 0.464827 | 0.500000 | 0.002186 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.832816 | 0.120093 | 0.102000 | 0.084947 | 0.320248 | 0.500000 | 0.003173 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20255.14 |
CORE_MID VAV BOX REHEAT COIL | 25845.34 |
CORE_TOP VAV BOX REHEAT COIL | 45898.33 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23190.23 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15061.71 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22984.05 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15190.39 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17289.59 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11288.36 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17110.95 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11406.26 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 18263.86 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11914.55 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 18066.10 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 12035.34 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.57 | 1.08 | 5.14 | 2.27 | 4.45 | 4.45 | 0.300000 | 0.510127 | 4.45 |
PACU_VAV_MID | 2.60 | 1.07 | 5.19 | 2.70 | 4.29 | 4.29 | 0.300000 | 0.630843 | 4.29 |
PACU_VAV_TOP | 2.79 | 1.09 | 5.57 | 3.84 | 4.94 | 4.94 | 0.300000 | 0.776692 | 4.94 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.45 |
PACU_VAV_MID_OA_CONTROLLER | 4.29 |
PACU_VAV_TOP_OA_CONTROLLER | 4.94 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.45 | 95813.38 | 0.748629 | 1.48 | 31934.60 | 0.748629 |
PACU_VAV_MID COOLING COIL | 4.29 | 93757.87 | 0.742186 | 1.43 | 31249.50 | 0.742186 |
PACU_VAV_TOP COOLING COIL | 4.94 | 104560.13 | 0.754762 | 1.65 | 34849.89 | 0.754762 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 40607.16 |
PACU_VAV_MID HEATING COIL | 40223.93 |
PACU_VAV_TOP HEATING COIL | 39883.31 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.45 |
PACU_VAV_MID FAN | 4.29 |
PACU_VAV_TOP FAN | 4.94 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.4963 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.4907 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.6059 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.781 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.804 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.416 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.34899309E-12 | 0.71341365E-15 | -0.12063995E-12 | 0.11056198E-15 |
43 | 6 | 0.31964619E-07 | 0.14386379E-09 | 0.72949101E-08 | -0.15297586E-12 |
44 | 5 | -0.20668886E-03 | 0.12069764E-05 | -0.10606906E-03 | 0.72002597E-08 |
45 | 4 | 0.31134388 | 0.57707282E-03 | 0.10659731 | -0.36300877E-04 |
46 | 3 | -7.6460366 | 0.17597044E-01 | -2.4516196 | 0.30871179E-01 |
47 | 2 | 42.122891 | 0.61681621E-01 | 15.726221 | -0.34728460 |
48 | 1 | -81.504432 | 0.27489519E-01 | -29.554779 | 1.0990493 |
49 | 0 | 46.824333 | 0.54626793E-03 | 16.281579 | |
50 | 7 | -0.35248218E-12 | 0.86833836E-15 | -0.12082203E-12 | 0.11089560E-15 |
51 | 6 | 0.32029947E-07 | 0.14230652E-09 | 0.73093307E-08 | -0.15333007E-12 |
52 | 5 | -0.20701518E-03 | 0.11934730E-05 | -0.10623169E-03 | 0.72142720E-08 |
53 | 4 | 0.31171778 | 0.57042913E-03 | 0.10673215 | -0.36354454E-04 |
54 | 3 | -7.6534230 | 0.17389373E-01 | -2.4538128 | 0.30907429E-01 |
55 | 2 | 42.147231 | 0.60937802E-01 | 15.735171 | -0.34755580 |
56 | 1 | -81.523061 | 0.27151788E-01 | -29.562791 | 1.0994463 |
57 | 0 | 46.824333 | 0.53943493E-03 | 16.281396 | |
58 | 7 | -0.34003326E-12 | 0.10587728E-14 | -0.10362110E-12 | 0.10156885E-15 |
59 | 6 | 0.30685099E-07 | 0.17377759E-09 | 0.70124784E-08 | -0.14604764E-12 |
60 | 5 | -0.20027796E-03 | 0.14687154E-05 | -0.10287063E-03 | 0.69256609E-08 |
61 | 4 | 0.30396857 | 0.70685606E-03 | 0.10393882 | -0.35247175E-04 |
62 | 3 | -7.5002666 | 0.21681124E-01 | -2.4083433 | 0.30155984E-01 |
63 | 2 | 41.642471 | 0.76394252E-01 | 15.549432 | -0.34193213 |
64 | 1 | -81.136638 | 0.34202797E-01 | -29.396480 | 1.0912109 |
65 | 0 | 46.824335 | 0.68273867E-03 | 16.285225 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2394E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2460E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3767E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3823E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2411E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2870E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3624E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3867E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1708 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2019E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1948 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1049 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1170 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0052E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8200E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8082E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2396E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2471E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3768E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3836E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2426E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2948E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3621E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3864E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.7422E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4954E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3751E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2027E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4302E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7446E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6593E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6671E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9282E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.9549E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6202E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6395E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2150E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2217E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0914E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0997E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6891E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7473E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9172E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9641E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3994E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4341E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3621E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3864E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4956E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5757E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4661E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9646E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1861E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3440E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8200E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8082E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6889E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7478E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9165E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9629E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3980E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4286E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3624E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3867E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6951E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9834E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0577E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5557E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5985E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3517E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6593E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6671E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2657E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3430E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7826E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8682E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7100E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7406E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0916E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0999E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1701 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1107 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1908 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1254 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1254 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3337E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4952E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5650E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.4859E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3484E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1427E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0692E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2537E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6396E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5541E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6039E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.1179E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3521E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0190E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6319E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7391E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9541E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4952E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5650E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4730E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8600E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8687E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4523E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4470E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2637E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5542E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6040E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1701 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1106 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1908 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1254 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1254 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3329E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4947E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5647E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.4858E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3481E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1425E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0689E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2533E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6392E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5536E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6036E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.1181E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3520E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0191E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6317E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7389E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9540E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4947E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5647E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4730E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8598E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8687E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4521E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4466E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2634E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5536E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6037E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 32513.12796 | 32513.12796 | 2.45492 | 2.45492 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10811.30674 | 10811.30674 | 0.48584 | 0.48584 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27283.83100 | 27283.83100 | 2.05833 | 2.05833 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18246.67401 | 18246.67401 | 0.81130 | 0.81130 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28099.35446 | 28099.35446 | 2.14044 | 2.14044 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 32291.47135 | 32291.47135 | 1.44078 | 1.44078 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8842.49956 | 8842.49956 | 0.67366 | 0.67366 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 16275.32960 | 16275.32960 | 0.72796 | 0.72796 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10732.29116 | 10732.29116 | 0.81763 | 0.81763 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53543E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10570.17442 | 10570.17442 | 0.47280 | 0.47280 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13010.02335 | 13010.02335 | 0.99116 | 0.99116 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 16130.89815 | 16130.89815 | 0.72149 | 0.72149 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11730.28823 | 11730.28823 | 0.89366 | 0.89366 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10660.32276 | 10660.32276 | 0.47684 | 0.47684 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6805.06434 | 6805.06434 | 0.51841 | 0.51841 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12140.09349 | 12140.09349 | 0.54273 | 0.54273 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8662.56885 | 8662.56885 | 0.65991 | 0.65991 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53554E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7925.71159 | 7925.71159 | 0.35435 | 0.35435 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10245.30053 | 10245.30053 | 0.78048 | 0.78048 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12014.97222 | 12014.97222 | 0.53713 | 0.53713 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9201.34029 | 9201.34029 | 0.70095 | 0.70095 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 28.39100 | 1.53599E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8008.29174 | 8008.29174 | 0.35805 | 0.35805 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7707.30915 | 7707.30915 | 0.58717 | 0.58717 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12823.65887 | 12823.65887 | 0.57332 | 0.57332 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10622.68316 | 10622.68316 | 0.80926 | 0.80926 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53537E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8365.07861 | 8365.07861 | 0.37401 | 0.37401 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11897.51716 | 11897.51716 | 0.90638 | 0.90638 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12685.13192 | 12685.13192 | 0.56711 | 0.56711 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10931.88265 | 10931.88265 | 0.83282 | 0.83282 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8449.68289 | 8449.68289 | 0.37780 | 0.37780 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 65445.64 | 4.44950 | 4.44950 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 42639.91 | 2.26981 | 2.26981 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 63265.89 | 4.28559 | 4.28559 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 43008.41 | 2.70353 | 2.70353 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 71708.19 | 4.94387 | 4.94387 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 42991.82 | 3.83986 | 3.83986 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45492 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30529 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63582 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81410 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24801E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20255.14057 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.05833 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36411 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63603 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97095 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04639E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25845.33727 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14044 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35014 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63785 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93371 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08814E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 45898.33400 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72796 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21703 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19900 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14486 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57876 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75549E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23190.22810 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81763 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12233 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50336E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32622 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11449E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15061.70555 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99116 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15940 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13500 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13381 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42507 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39020E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22984.05121 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89366 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11192 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.50000E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48977E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40432E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15190.39356 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54273 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29110 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14057 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77628 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30881E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17289.58929 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65991 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15157 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12900 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51280E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40419 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51370E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11288.35976 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78048 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20243 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13424 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53981 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88214E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17110.94964 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70095 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14269 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48148E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38049 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67021E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11406.26236 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58717 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26907 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13446 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71753 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41596E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18263.86244 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80926 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32959 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.08261E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11914.55206 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90638 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17431 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14800 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13414 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46483 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18576E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18066.09898 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83282 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12009 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49472E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32025 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17254E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12035.33533 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56949 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08058 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.13899 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.26981 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.44950 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.44950 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.51013 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.59698 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07455 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.19396 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.70353 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.28559 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.28559 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.63084 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.78542 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08645 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.57085 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.83986 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.94387 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.94387 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.77669 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.44950 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.28559 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.94387 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.44950 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.44950 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95813.37691 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74863 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.48302 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31934.59853 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74863 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 40607.16239 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.44950 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.28559 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.28559 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93757.86750 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74219 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.42839 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31249.49724 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74219 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 40223.93483 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.28559 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.94387 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.94387 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 104560.13195 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75476 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.64779 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34849.89198 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75476 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 39883.31395 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.94387 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 95199.79 | 324835.17 | 12.43 | 3.17 | 3.56 | 3.75 | 3.92 | 10.83 | 12.15 | 12.79 | 13.38 | 4.9087 | 3.9137 | 2.6353 | 1.0863 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 93210.39 | 318047.04 | 12.47 | 3.18 | 3.57 | 3.76 | 3.93 | 10.86 | 12.19 | 12.84 | 13.41 | 4.7278 | 3.7642 | 2.5333 | 1.0530 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 103822.35 | 354256.56 | 12.39 | 3.17 | 3.55 | 3.73 | 3.91 | 10.80 | 12.11 | 12.74 | 13.36 | 5.4541 | 4.3486 | 2.9280 | 1.2012 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.606 | 0.556 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.496 | 0.462 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.491 | 0.457 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.8004759783E-002 | 1.6709656764E-002 | Pass | Pass | 0.4851981762 | 0.4909243944 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1224848738 | 8.2347966514E-002 | Pass | Pass | 0.4951569042 | 0.4813427760 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2807135726E-002 | 3.3332665722E-002 | Pass | Pass | 0.4947634129 | 0.4703683580 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.0214615587E-002 | 3.0933703212E-002 | Pass | Pass | 0.4958542315 | 0.4700968805 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.6441867652E-003 | 6.7352095745E-003 | Pass | Pass | 0.5571872986 | 0.5401911669 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 9.5221441310E-002 | 9.5443376614E-002 | Pass | Pass | 27.2058352309 | 69.6420344041 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4213069014 | 0.4110852629 | Pass | Pass | 22.0375475257 | 83.0961547026 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4472535068 | 0.4401870820 | Pass | Pass | 52.5092081618 | 238.5142337756 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3990601265 | 0.4106327282 | Pass | Pass | 68.8145677244 | 331.8228741060 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4524000064 | 0.4399010390 | Pass | Pass | 54.6981478797 | 208.0658233673 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3119471575 | 0.2960479592 | Pass | Pass | 30.3854565186 | 88.7455400874 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3310431378 | 0.3175516817 | Pass | Pass | 23.5371729965 | 54.6545339586 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2855679002 | 0.2878858643 | Pass | Pass | 26.6616956011 | 87.0247081075 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3385968693 | 0.3201080752 | Pass | Pass | 24.4015327206 | 56.5014249644 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3200681703 | 0.3025330067 | Pass | Pass | 27.1126590744 | 127.2106288868 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3320411603 | 0.3251181137 | Pass | Pass | 27.8058034571 | 109.6260149958 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2933501565 | 0.3035274294 | Pass | Pass | 25.0810906048 | 92.1090573934 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3375679418 | 0.3240451412 | Pass | Pass | 22.5707191753 | 75.8125253221 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3538.39 | 233.86 | 0.00 | 1649.40 | 753.95 | 6175.61 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.556 | 0.606 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.462 | 0.496 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.457 | 0.491 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.342_SHGC_EAST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.342_SHGC_WEST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.342_SHGC_WEST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 195.79 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.64 | 0.0000 | Y | 4.89 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.52 | 0.0000 | Y | 3.08 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.33 | 0.0000 | Y | 4.82 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.44 | 0.0000 | Y | 3.07 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.59 | 0.0000 | Y | 4.88 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.48 | 0.0000 | Y | 3.07 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.30 | 0.0000 | Y | 4.81 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.40 | 0.0000 | Y | 3.06 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.64 | 0.0000 | Y | 4.89 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.52 | 0.0000 | Y | 3.08 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.33 | 0.0000 | Y | 4.82 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.44 | 0.0000 | Y | 3.07 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 166.91 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.24 | 42.24 | 4.30 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.63 | 62.93 | 3.31 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.63 | 47.43 | 26.73 | |
Exterior Lighting Total | 3824.74 | 34.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95813.38 | 71728.72 | 24084.66 | 0.75 | 3.74 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93757.87 | 69585.75 | 24172.12 | 0.74 | 3.74 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 104560.13 | 78917.98 | 25642.15 | 0.75 | 3.74 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 95199.8 | 3.17 | 10.83 | N/A | N/A | 12.43 | |
PACU_VAV_MID COOLING COIL | 93210.4 | 3.18 | 10.86 | N/A | N/A | 12.47 | |
PACU_VAV_TOP COOLING COIL | 103822.3 | 3.17 | 10.80 | N/A | N/A | 12.39 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20255.14 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25845.34 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 45898.33 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23190.23 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15061.71 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22984.05 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15190.39 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17289.59 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11288.36 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17110.95 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11406.26 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18263.86 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11914.55 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18066.10 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12035.34 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 40607.16 | 0.84 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 40223.93 | 0.84 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 39883.31 | 0.84 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.45 | 10293.42 | 2313.39 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.29 | 9914.23 | 2313.39 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.94 | 11363.30 | 2298.46 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95199.79 | 3.17 | 10.83 | 12.43 | 4.9087 | 3.56 | 12.15 | 3.9137 | 3.75 | 12.79 | 2.6353 | 3.92 | 13.38 | 1.0863 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93210.39 | 3.18 | 10.86 | 12.47 | 4.7278 | 3.57 | 12.19 | 3.7642 | 3.76 | 12.84 | 2.5333 | 3.93 | 13.41 | 1.0530 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103822.35 | 3.17 | 10.80 | 12.39 | 5.4541 | 3.55 | 12.11 | 4.3486 | 3.73 | 12.74 | 2.9280 | 3.91 | 13.36 | 1.2012 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 32513.13 | 32513.13 | 33.06 | 2.455 | 2.455 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 27283.83 | 27283.83 | 27.74 | 2.058 | 2.058 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 28099.35 | 28099.35 | 28.57 | 2.140 | 2.140 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00893 | 31.09 | 0.01536 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8842.50 | 8842.50 | 42.65 | 0.674 | 0.674 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00922 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10732.29 | 10732.29 | 81.76 | 0.818 | 0.818 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00891 | 25.37 | 0.01535 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13010.02 | 13010.02 | 62.75 | 0.991 | 0.991 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00900 | 30.93 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11730.29 | 11730.29 | 89.37 | 0.894 | 0.894 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00887 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6805.06 | 6805.06 | 32.82 | 0.518 | 0.518 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00918 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8662.57 | 8662.57 | 65.99 | 0.660 | 0.660 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00886 | 25.97 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10245.30 | 10245.30 | 49.41 | 0.780 | 0.780 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00896 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9201.34 | 9201.34 | 70.10 | 0.701 | 0.701 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00883 | 28.39 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7707.31 | 7707.31 | 37.17 | 0.587 | 0.587 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00925 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10622.68 | 10622.68 | 80.93 | 0.809 | 0.809 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00887 | 25.03 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11897.52 | 11897.52 | 57.38 | 0.906 | 0.906 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00899 | 30.85 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10931.88 | 10931.88 | 83.29 | 0.833 | 0.833 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00885 | 29.54 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10811.31 | 10811.31 | 10.99 | 0.486 | 0.486 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 18246.67 | 18246.67 | 18.55 | 0.811 | 0.811 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 32291.47 | 32291.47 | 32.83 | 1.441 | 1.441 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 16275.33 | 16275.33 | 78.50 | 0.728 | 0.728 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10570.17 | 10570.17 | 80.53 | 0.473 | 0.473 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16130.90 | 16130.90 | 77.80 | 0.721 | 0.721 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10660.32 | 10660.32 | 81.22 | 0.477 | 0.477 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12140.09 | 12140.09 | 58.55 | 0.543 | 0.543 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7925.71 | 7925.71 | 60.38 | 0.354 | 0.354 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12014.97 | 12014.97 | 57.95 | 0.537 | 0.537 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8008.29 | 8008.29 | 61.01 | 0.358 | 0.358 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12823.66 | 12823.66 | 61.85 | 0.573 | 0.573 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00746 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8365.08 | 8365.08 | 63.73 | 0.374 | 0.374 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12685.13 | 12685.13 | 61.18 | 0.567 | 0.567 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8449.68 | 8449.68 | 64.38 | 0.378 | 0.378 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.45 | 4.45 | 2.27 | 2.27 | 4.4495 | 2.2698 | 4.4495 | 0.5101 | 0.3000 |
PACU_VAV_MID | 4.29 | 4.29 | 2.70 | 2.70 | 4.2856 | 2.7035 | 4.2856 | 0.6308 | 0.3000 |
PACU_VAV_TOP | 4.94 | 4.94 | 3.84 | 3.84 | 4.9439 | 3.8399 | 4.9439 | 0.7767 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20255.141 | 20255.141 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 20255.14 | 15477.24 | 0.485842 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 10811.31 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25845.337 | 25845.337 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25845.34 | 25845.34 | 0.811304 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 18246.67 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 45898.334 | 45898.334 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45898.33 | 45898.33 | 1.440783 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 32291.47 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23190.228 | 23190.228 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23190.23 | 23190.23 | 0.727959 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00748681 | 46.2115 | 16275.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15061.706 | 15061.706 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15061.71 | 15061.71 | 0.472798 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00747414 | 46.1345 | 10570.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22984.051 | 22984.051 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22984.05 | 22984.05 | 0.721486 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00748249 | 46.1851 | 16130.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15190.394 | 15190.394 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15190.39 | 15190.39 | 0.476838 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00747830 | 46.1599 | 10660.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17289.589 | 17289.589 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17289.59 | 17289.59 | 0.542733 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00762108 | 47.0264 | 12140.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11288.360 | 11288.360 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11288.36 | 11288.36 | 0.354350 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00761491 | 46.9890 | 7925.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17110.950 | 17110.950 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17110.95 | 17110.95 | 0.537125 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00761679 | 47.0002 | 12014.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11406.262 | 11406.262 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11406.26 | 11406.26 | 0.358051 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00761913 | 47.0146 | 8008.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 18263.862 | 18263.862 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18263.86 | 18263.86 | 0.573316 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00745676 | 46.0271 | 12823.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11914.552 | 11914.552 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11914.55 | 11914.55 | 0.374007 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00744653 | 45.9650 | 8365.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 18066.099 | 18066.099 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18066.10 | 18066.10 | 0.567108 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00745092 | 45.9915 | 12685.13 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 12035.335 | 12035.335 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12035.34 | 12035.34 | 0.377798 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00745192 | 45.9978 | 8449.68 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 95813.377 | 71728.719 | 4.449505 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 97641.56 | 74319.56 | 4.449505 | 25.55 | 17.93 | 0.01034249 | 10.83 | 10.83 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 21.4878 | 24.00 | 0.00896762 | 46.0147 | 58401.86 | 0.00 | 98796.45 | 71286.41 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 40607.162 | 40607.162 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40607.16 | 40607.16 | 1.334851 | -13.56 | -13.56 | 0.00232890 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 71.6260 | 18.19 | 0.00731540 | 53.7654 | 16219.97 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 93757.867 | 69585.751 | 4.285590 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 95779.95 | 71843.50 | 4.285590 | 25.61 | 18.05 | 0.01046421 | 10.83 | 10.83 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 22.3096 | 24.00 | 0.00905465 | 46.4558 | 56187.47 | 0.00 | 96676.95 | 69184.49 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 40223.935 | 40223.935 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40223.93 | 40223.93 | 1.285677 | -14.31 | -14.31 | 0.00215398 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 74.3655 | 16.66 | 0.00711119 | 57.6113 | 15703.98 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 104560.132 | 78917.978 | 4.943871 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 106277.22 | 81721.33 | 4.943871 | 25.39 | 17.81 | 0.01024611 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 19.3391 | 24.00 | 0.00901562 | 46.2588 | 64762.25 | 0.00 | 107815.53 | 78381.90 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 39883.314 | 39883.314 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39883.31 | 39883.31 | 1.483161 | -10.50 | -10.50 | 0.00277031 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 64.4637 | 16.40 | 0.00736611 | 60.6494 | 15393.72 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20255.141 | 20255.141 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 20255.14 | 15477.24 | 1.0000 | 0.55801675 | 0.485842 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20255.14 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 10811.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25845.337 | 25845.337 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25845.34 | 25845.34 | 1.0000 | 0.93182839 | 0.811304 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25845.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 18246.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 45898.334 | 45898.334 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 45898.33 | 45898.33 | 1.0000 | 1.65481961 | 1.440783 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45898.33 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 32291.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23190.228 | 23190.228 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23190.23 | 23190.23 | 1.0000 | 0.83610103 | 0.727959 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23190.23 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748681 | 21.00 | 0.00748681 | 46.2115 | 16275.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 15061.706 | 15061.706 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15061.71 | 15061.71 | 1.0000 | 0.54303508 | 0.472798 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15061.71 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00747414 | 21.00 | 0.00747414 | 46.1345 | 10570.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 22984.051 | 22984.051 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22984.05 | 22984.05 | 1.0000 | 0.82866752 | 0.721486 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22984.05 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00748249 | 21.00 | 0.00748249 | 46.1851 | 16130.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 15190.394 | 15190.394 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15190.39 | 15190.39 | 1.0000 | 0.54767480 | 0.476838 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15190.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00747830 | 21.00 | 0.00747830 | 46.1599 | 10660.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17289.589 | 17289.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17289.59 | 17289.59 | 1.0000 | 0.62335926 | 0.542733 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17289.59 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00762108 | 21.00 | 0.00762108 | 47.0264 | 12140.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11288.360 | 11288.360 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11288.36 | 11288.36 | 1.0000 | 0.40699079 | 0.354350 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11288.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00761491 | 21.00 | 0.00761491 | 46.9890 | 7925.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17110.950 | 17110.950 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17110.95 | 17110.95 | 1.0000 | 0.61691858 | 0.537125 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17110.95 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00761679 | 21.00 | 0.00761679 | 47.0002 | 12014.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11406.262 | 11406.262 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11406.26 | 11406.26 | 1.0000 | 0.41124165 | 0.358051 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11406.26 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00761913 | 21.00 | 0.00761913 | 47.0146 | 8008.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18263.862 | 18263.862 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18263.86 | 18263.86 | 1.0000 | 0.65848572 | 0.573316 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18263.86 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00745676 | 21.00 | 0.00745676 | 46.0271 | 12823.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11914.552 | 11914.552 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11914.55 | 11914.55 | 1.0000 | 0.42956754 | 0.374007 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11914.55 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00744653 | 21.00 | 0.00744653 | 45.9650 | 8365.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18066.099 | 18066.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18066.10 | 18066.10 | 1.0000 | 0.65135556 | 0.567108 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18066.10 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00745092 | 21.00 | 0.00745092 | 45.9915 | 12685.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12035.335 | 12035.335 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12035.34 | 12035.34 | 1.0000 | 0.43392226 | 0.377798 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12035.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00745192 | 21.00 | 0.00745192 | 45.9978 | 8449.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95813.377 | 71728.719 | 4.449505 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0662 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.449505 | 5.11050448 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 97641.56 | 74319.56 | 1.0191 | 5.11050448 | 4.449505 | 25.55 | 17.93 | 0.01034249 | 52026.7 | 10.83 | 10.83 | 0.00850000 | 32314.8 | -999.0 | -999.00 | -999.00 | -999.00 | 10293.424 | 87348.13 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 21.4878 | 24.00 | 0.00896762 | 24.00 | 0.00896762 | 46.0147 | 58401.86 | 0.00 | 98796.45 | 71286.41 | 4.90867819 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.45 | 12.44 | 0.00898731 | 35195.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40607.162 | 40607.162 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.449505 | 5.11050448 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40607.16 | 40607.16 | 1.0000 | 1.53315134 | 1.334851 | -13.56 | -13.56 | 0.00232890 | -7857.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40607.16 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 71.6260 | 18.35 | 0.00729572 | 18.19 | 0.00731540 | 53.7654 | 16219.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93757.867 | 69585.751 | 4.285590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2925 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.285590 | 4.92223924 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 95779.95 | 71843.50 | 1.0216 | 4.92223924 | 4.285590 | 25.61 | 18.05 | 0.01046421 | 52399.1 | 10.83 | 10.83 | 0.00850000 | 32315.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9914.226 | 85865.72 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 22.3096 | 24.00 | 0.00905465 | 24.00 | 0.00905465 | 46.4558 | 56187.47 | 0.00 | 96676.95 | 69184.49 | 4.72784800 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.34 | 12.31 | 0.00890473 | 34874.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40223.935 | 40223.935 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.285590 | 4.92223924 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40223.93 | 40223.93 | 1.0000 | 1.47667177 | 1.285677 | -14.31 | -14.31 | 0.00215398 | -9047.4 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40223.93 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 74.3655 | 20.19 | 0.00735442 | 16.66 | 0.00711119 | 57.6113 | 15703.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 104560.132 | 78917.978 | 4.943871 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8870 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.943871 | 5.67831132 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 106277.22 | 81721.33 | 1.0164 | 5.67831132 | 4.943871 | 25.39 | 17.81 | 0.01024611 | 51625.0 | 10.85 | 10.85 | 0.00850000 | 32327.4 | -999.0 | -999.00 | -999.00 | -999.00 | 11363.296 | 94913.93 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 19.3391 | 24.00 | 0.00901562 | 24.00 | 0.00901562 | 46.2588 | 64762.25 | 0.00 | 107815.53 | 78381.90 | 5.45406095 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.60 | 12.58 | 0.00906876 | 35554.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39883.314 | 39883.314 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.943871 | 5.67831132 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39883.31 | 39883.31 | 1.0000 | 1.70349340 | 1.483161 | -10.50 | -10.50 | 0.00277031 | -3676.0 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39883.31 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 64.4637 | 17.98 | 0.00714024 | 16.40 | 0.00736611 | 60.6494 | 15393.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.45 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.29 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.94 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2644.00 | 3293.50 | 712.17 |
CORE_MID | 3208.67 | 3640.67 | 1493.33 |
CORE_TOP | 3559.83 | 3837.67 | 1979.33 |
PERIMETER_TOP_ZN_3 | 4095.50 | 4153.50 | 2658.17 |
PERIMETER_TOP_ZN_2 | 4086.67 | 3961.83 | 2492.00 |
PERIMETER_TOP_ZN_1 | 3758.83 | 3815.33 | 2149.67 |
PERIMETER_TOP_ZN_4 | 4107.17 | 4000.17 | 2539.00 |
PERIMETER_BOT_ZN_3 | 3808.17 | 4250.67 | 2510.83 |
PERIMETER_BOT_ZN_2 | 3963.17 | 3914.50 | 2306.17 |
PERIMETER_BOT_ZN_1 | 3676.33 | 4195.17 | 2318.00 |
PERIMETER_BOT_ZN_4 | 3922.50 | 3935.33 | 2285.17 |
PERIMETER_MID_ZN_3 | 3914.67 | 3957.67 | 2335.83 |
PERIMETER_MID_ZN_2 | 3369.00 | 3302.00 | 1978.83 |
PERIMETER_MID_ZN_1 | 3604.67 | 3585.33 | 1828.83 |
PERIMETER_MID_ZN_4 | 3938.50 | 3809.83 | 2225.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4991.50 | 4762.67 | 3137.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.17 | 0.33 | 2.00 | 0.33 |
CORE_MID | 3.17 | 0.17 | 2.83 | 0.17 |
CORE_TOP | 18.33 | 0.00 | 13.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 253.83 | 5.17 | 117.67 | 3.33 |
PERIMETER_TOP_ZN_2 | 159.50 | 29.33 | 35.83 | 27.17 |
PERIMETER_TOP_ZN_1 | 139.50 | 27.33 | 32.00 | 24.83 |
PERIMETER_TOP_ZN_4 | 154.00 | 33.00 | 37.50 | 20.50 |
PERIMETER_BOT_ZN_3 | 157.83 | 0.00 | 110.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 41.83 | 15.83 | 5.17 | 15.83 |
PERIMETER_BOT_ZN_1 | 480.33 | 21.50 | 458.67 | 21.50 |
PERIMETER_BOT_ZN_4 | 41.50 | 22.50 | 6.83 | 13.33 |
PERIMETER_MID_ZN_3 | 142.17 | 1.50 | 74.17 | 0.50 |
PERIMETER_MID_ZN_2 | 75.33 | 26.17 | 12.67 | 25.50 |
PERIMETER_MID_ZN_1 | 52.83 | 25.50 | 8.17 | 24.83 |
PERIMETER_MID_ZN_4 | 76.17 | 30.33 | 15.00 | 18.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 763.17 | 133.67 | 557.83 | 110.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.737 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.619 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.615 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.772 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.053 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.991 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.015 | 0.129 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.645 | 0.065 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.902 | 0.069 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.854 | 0.888 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.860 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.726 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.960 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.978 | 0.103 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.978 | 0.108 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 11684716.55 | 0.00 | 11684716.55 | 0.00 | 11684716.55 | 13393058.27 | 5560.71 | 837.33 | 2361.95 | 259.17 |
CORE_MID | 9868734.78 | 0.00 | 9868734.78 | 0.00 | 9868734.78 | 13393058.27 | 5410.36 | 1241.42 | 2108.22 | 305.16 |
CORE_TOP | 9800053.14 | 0.00 | 9800053.14 | 0.00 | 9800053.14 | 13393058.27 | 5599.22 | 1070.83 | 2089.95 | 109.47 |
PERIMETER_TOP_ZN_3 | 2591692.39 | 0.00 | 2591692.39 | 834711.09 | 3426403.48 | 2823374.22 | 4197.35 | 40.74 | 4521.91 | 109.44 |
PERIMETER_TOP_ZN_2 | 2225730.37 | 0.00 | 2225730.37 | 556470.72 | 2782201.08 | 1787429.43 | 4550.18 | 1036.81 | 3173.01 | 109.44 |
PERIMETER_TOP_ZN_1 | 3310929.37 | 0.00 | 3310929.37 | 834711.09 | 4145640.46 | 2823374.22 | 4747.28 | 1035.83 | 2976.89 | 109.44 |
PERIMETER_TOP_ZN_4 | 2161770.18 | 0.00 | 2161770.18 | 556470.72 | 2718240.90 | 1787312.18 | 4559.13 | 1030.87 | 3170.00 | 109.44 |
PERIMETER_BOT_ZN_3 | 2172244.19 | 0.00 | 2172244.19 | 443809.51 | 2616053.70 | 2823374.22 | 5028.59 | 96.97 | 3634.44 | 259.17 |
PERIMETER_BOT_ZN_2 | 1908837.45 | 0.00 | 1908837.45 | 295871.23 | 2204708.67 | 1787429.43 | 4966.13 | 728.40 | 3065.47 | 259.17 |
PERIMETER_BOT_ZN_1 | 2867882.05 | 0.00 | 2867882.05 | 3202062.74 | 6069944.78 | 2823374.22 | 4589.98 | 716.48 | 3453.54 | 259.17 |
PERIMETER_BOT_ZN_4 | 1827534.44 | 0.00 | 1827534.44 | 295871.23 | 2123405.67 | 1787312.18 | 5008.44 | 817.58 | 2933.98 | 259.17 |
PERIMETER_MID_ZN_3 | 2439756.18 | 0.00 | 2439756.18 | 694831.36 | 3134587.54 | 2823374.22 | 4562.33 | 1064.88 | 3132.79 | 305.11 |
PERIMETER_MID_ZN_2 | 2032707.66 | 0.00 | 2032707.66 | 463218.12 | 2495925.78 | 1601953.02 | 4380.01 | 927.56 | 3452.43 | 1214.07 |
PERIMETER_MID_ZN_1 | 3270323.57 | 0.00 | 3270323.57 | 694831.36 | 3965154.93 | 2823374.22 | 4512.08 | 1205.44 | 3042.48 | 305.09 |
PERIMETER_MID_ZN_4 | 2081804.02 | 0.00 | 2081804.02 | 463218.12 | 2545022.14 | 1787312.18 | 4530.62 | 1156.66 | 3072.72 | 305.07 |
Total Facility | 60244716.32 | 0.00 | 60244716.32 | 9336077.29 | 69580793.62 | 67658168.57 | 6482.03 | 1798.95 | 4716.63 | 1345.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5403 | 0.0000 | 0.5403 | 0.0000 | 0.5403 | 0.4247 | 2779.46 | 837.33 | 2326.20 |
CORE_MID | 0.4545 | 0.0000 | 0.4545 | 0.0000 | 0.4545 | 0.4247 | 2641.19 | 1241.42 | 2060.39 |
CORE_TOP | 0.4519 | 0.0000 | 0.4519 | 0.0000 | 0.4519 | 0.4247 | 2838.21 | 1070.83 | 2033.96 |
PERIMETER_TOP_ZN_3 | 0.1197 | 0.0000 | 0.1197 | 0.0192 | 0.1389 | 0.0895 | 1436.37 | 40.74 | 4465.89 |
PERIMETER_TOP_ZN_2 | 0.1032 | 0.0000 | 0.1032 | 0.0128 | 0.1160 | 0.0567 | 1789.17 | 1036.81 | 3117.02 |
PERIMETER_TOP_ZN_1 | 0.1534 | 0.0000 | 0.1534 | 0.0192 | 0.1726 | 0.0895 | 1986.30 | 1035.83 | 2920.87 |
PERIMETER_TOP_ZN_4 | 0.0995 | 0.0000 | 0.0995 | 0.0128 | 0.1123 | 0.0567 | 1798.14 | 1030.87 | 3113.99 |
PERIMETER_BOT_ZN_3 | 0.1002 | 0.0000 | 0.1002 | 0.0102 | 0.1104 | 0.0895 | 2247.34 | 96.97 | 3598.69 |
PERIMETER_BOT_ZN_2 | 0.0884 | 0.0000 | 0.0884 | 0.0068 | 0.0952 | 0.0567 | 2184.98 | 728.40 | 3029.62 |
PERIMETER_BOT_ZN_1 | 0.1328 | 0.0000 | 0.1328 | 0.1391 | 0.2719 | 0.0895 | 1808.73 | 716.48 | 3417.79 |
PERIMETER_BOT_ZN_4 | 0.0843 | 0.0000 | 0.0843 | 0.0068 | 0.0911 | 0.0567 | 2227.39 | 817.53 | 2898.08 |
PERIMETER_MID_ZN_3 | 0.1125 | 0.0000 | 0.1125 | 0.0160 | 0.1285 | 0.0895 | 1793.17 | 1064.88 | 3084.95 |
PERIMETER_MID_ZN_2 | 0.0941 | 0.0000 | 0.0941 | 0.0113 | 0.1053 | 0.0567 | 1611.07 | 927.56 | 2495.37 |
PERIMETER_MID_ZN_1 | 0.1514 | 0.0000 | 0.1514 | 0.0160 | 0.1673 | 0.0895 | 1742.91 | 1205.44 | 2994.65 |
PERIMETER_MID_ZN_4 | 0.0958 | 0.0000 | 0.0958 | 0.0106 | 0.1064 | 0.0567 | 1761.77 | 1156.59 | 3024.63 |
Total Facility | 2.7819 | 0.0000 | 2.7819 | 0.2807 | 3.0626 | 2.1513 | 3687.94 | 1798.86 | 4647.52 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 26991959.77 | 0.00 | 26991959.77 | 22614548.33 | 4159.82 | 2.77 | 4597.41 | 258.84 |
PACU_VAV_MID | 25979038.70 | 0.00 | 25979038.70 | 22429071.92 | 4114.97 | 1.57 | 4643.46 | 303.66 |
PACU_VAV_TOP | 26502442.45 | 0.00 | 26502442.45 | 22614548.33 | 4099.18 | 0.75 | 4660.07 | 108.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2479 | 0.0000 | 1.2479 | 0.7171 | 1378.57 | 2.77 | 4561.66 |
PACU_VAV_MID | 1.1981 | 0.0000 | 1.1981 | 0.7084 | 1345.80 | 1.57 | 4595.63 |
PACU_VAV_TOP | 1.2237 | 0.0000 | 1.2237 | 0.7171 | 1338.19 | 0.75 | 4604.06 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 155.94 | 2392.47 | 0.00 | 0.00 | 0.00 | 2498.14 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 106.04 | 2448.24 | 0.00 | 0.00 | 0.00 | 2597.70 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 90.13 | 2208.53 | 0.00 | 0.00 | 0.00 | 2598.34 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2416 | 2.1690 | 0.0000 | 0.0000 | 0.0000 | 1.0390 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2171 | 2.0631 | 0.0000 | 0.0000 | 0.0000 | 0.9890 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1968 | 2.1630 | 0.0000 | 0.0000 | 0.0000 | 1.0100 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1414.49 | 11240.73 | 09-APR-17:10 | 237473.55 | 30-JAN-07:10 |
Electricity:Building | 814.66 | 11072.20 | 09-APR-17:10 | 57876.08 | 03-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 814.66 | 11072.20 | 09-APR-17:10 | 57876.08 | 03-NOV-07:10 |
InteriorLights:Electricity | 166.91 | 772.31 | 01-JAN-10:00 | 17672.30 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 166.91 | 772.31 | 01-JAN-10:00 | 17672.30 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 166.91 | 772.31 | 01-JAN-10:00 | 17672.30 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 166.91 | 772.31 | 01-JAN-10:00 | 17672.30 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.22 | 405.59 | 26-MAR-17:10 | 2170.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.89 | 19.49 | 01-JAN-10:00 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 4.89 | 19.49 | 01-JAN-10:00 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.48 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.08 | 12.34 | 01-JAN-09:40 | 465.60 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.08 | 12.34 | 01-JAN-09:40 | 465.60 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.15 | 405.59 | 26-MAR-17:10 | 2170.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.82 | 19.49 | 01-JAN-09:40 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.82 | 19.49 | 01-JAN-09:40 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.47 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.07 | 12.34 | 01-JAN-09:50 | 465.57 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.07 | 12.34 | 01-JAN-09:50 | 465.57 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.21 | 405.59 | 26-MAR-17:10 | 2170.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.88 | 19.49 | 01-JAN-10:00 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.88 | 19.49 | 01-JAN-10:00 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.48 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.07 | 12.34 | 01-JAN-09:40 | 465.60 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.07 | 12.34 | 01-JAN-09:40 | 465.60 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.14 | 405.59 | 26-MAR-17:10 | 2170.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.81 | 19.49 | 01-JAN-09:40 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.81 | 19.49 | 01-JAN-09:40 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.46 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.06 | 12.34 | 01-JAN-09:50 | 465.57 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.06 | 12.34 | 01-JAN-09:50 | 465.57 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.22 | 405.59 | 26-MAR-17:10 | 2170.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.89 | 19.49 | 01-JAN-10:00 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 4.89 | 19.49 | 01-JAN-10:00 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.48 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.08 | 12.34 | 01-JAN-09:40 | 465.60 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.08 | 12.34 | 01-JAN-09:40 | 465.60 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.15 | 405.59 | 26-MAR-17:10 | 2170.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.82 | 19.49 | 01-JAN-09:40 | 735.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.82 | 19.49 | 01-JAN-09:40 | 735.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.47 | 256.75 | 12-MAR-17:10 | 1374.14 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.07 | 12.34 | 01-JAN-09:50 | 465.57 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.07 | 12.34 | 01-JAN-09:50 | 465.57 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 132.05 | -0.00 | 11-APR-18:30 | 25966.78 | 25-APR-12:20 |
ElectricityProduced:Plant | 132.05 | -0.00 | 11-APR-18:30 | 25966.78 | 25-APR-12:20 |
Photovoltaic:ElectricityProduced | 138.24 | 0.00 | 01-JAN-00:10 | 27039.68 | 25-APR-12:20 |
PowerConversion:ElectricityProduced | -6.19 | -1072.90 | 25-APR-12:20 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-17:20 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 565.35 | 168.53 | 09-APR-17:10 | 209405.17 | 30-JAN-07:10 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.48 | 03-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.48 | 03-NOV-07:20 |
ElectricityPurchased:Facility | 1283.71 | 0.00 | 22-JAN-12:30 | 237473.55 | 30-JAN-07:10 |
ElectricityPurchased:Plant | 1283.71 | 0.00 | 22-JAN-12:30 | 237473.55 | 30-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1283.71 | 0.00 | 22-JAN-12:30 | 237473.55 | 30-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1283.71 | 0.00 | 22-JAN-12:30 | 237473.55 | 30-JAN-07:10 |
ElectricitySurplusSold:Facility | 1.28 | 0.00 | 01-JAN-00:10 | 11527.84 | 23-APR-12:10 |
ElectricitySurplusSold:Plant | 1.28 | 0.00 | 01-JAN-00:10 | 11527.84 | 23-APR-12:10 |
Cogeneration:ElectricitySurplusSold | 1.28 | 0.00 | 01-JAN-00:10 | 11527.84 | 23-APR-12:10 |
General:Cogeneration:ElectricitySurplusSold | 1.28 | 0.00 | 01-JAN-00:10 | 11527.84 | 23-APR-12:10 |
ElectricityNet:Facility | 1282.44 | -11527.84 | 23-APR-12:10 | 237473.55 | 30-JAN-07:10 |
ElectricityNet:Plant | 1282.44 | -11527.84 | 23-APR-12:10 | 237473.55 | 30-JAN-07:10 |
Cogeneration:ElectricityNet | 1282.44 | -11527.84 | 23-APR-12:10 | 237473.55 | 30-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1282.44 | -11527.84 | 23-APR-12:10 | 237473.55 | 30-JAN-07:10 |
Heating:Electricity | 343.79 | 0.00 | 01-JAN-00:40 | 201872.72 | 30-JAN-07:10 |
General:Heating:Electricity | 343.79 | 0.00 | 01-JAN-00:40 | 201872.72 | 30-JAN-07:10 |
Fans:Electricity | 83.70 | 0.00 | 01-JAN-00:40 | 30548.97 | 04-AUG-07:10 |
General:Fans:Electricity | 83.70 | 0.00 | 01-JAN-00:40 | 30548.97 | 04-AUG-07:10 |
ExteriorLights:Electricity | 34.34 | 0.00 | 01-JAN-08:00 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.34 | 0.00 | 01-JAN-08:00 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 126.24 | 0.00 | 01-JAN-00:10 | 70376.98 | 04-AUG-15:30 |
General:Cooling:Electricity | 126.24 | 0.00 | 01-JAN-00:10 | 70376.98 | 04-AUG-15:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-17:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-17:20 |
WIRED_LTG_ELECTRICITY | 4.69 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 538.67 | 1886.44 | 06-JAN-05:20 | 155487.14 | 02-FEB-12:20 |
NaturalGas:HVAC | 399.59 | 0.00 | 01-JAN-00:40 | 143707.63 | 06-JAN-07:20 |
Heating:NaturalGas | 399.59 | 0.00 | 01-JAN-00:40 | 143707.63 | 06-JAN-07:20 |
General:Heating:NaturalGas | 399.59 | 0.00 | 01-JAN-00:40 | 143707.63 | 06-JAN-07:20 |
NaturalGas:Plant | 139.09 | 1886.44 | 02-JAN-07:20 | 12793.64 | 21-FEB-12:40 |
WaterSystems:NaturalGas | 139.09 | 1886.44 | 02-JAN-07:20 | 12793.64 | 21-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 139.09 | 1886.44 | 02-JAN-07:20 | 12793.64 | 21-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2342.86 | 0.00 | 01-JAN-00:40 | 508906.00 | 30-JAN-07:10 |
EnergyTransfer:Building | 1043.81 | 0.00 | 01-JAN-00:40 | 197441.72 | 30-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 154.59 | 0.00 | 01-JAN-00:40 | 21762.79 | 03-AUG-07:30 |
Heating:EnergyTransfer | 314.49 | 0.00 | 01-JAN-00:40 | 197441.72 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.99 | 0.00 | 01-JAN-00:10 | 16159.99 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 314.49 | 0.00 | 01-JAN-00:40 | 197441.72 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.99 | 0.00 | 01-JAN-00:10 | 16159.99 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 729.32 | 0.00 | 01-JAN-00:40 | 151884.87 | 26-JUN-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 153.60 | 0.00 | 01-JAN-00:40 | 21762.79 | 03-AUG-07:30 |
General:Cooling:EnergyTransfer | 729.32 | 0.00 | 01-JAN-00:40 | 151884.87 | 26-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 153.60 | 0.00 | 01-JAN-00:40 | 21762.79 | 03-AUG-07:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 56.80 | 0.00 | 01-JAN-00:40 | 17297.61 | 02-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.17 | 0.00 | 01-JAN-00:40 | 17297.61 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.17 | 0.00 | 01-JAN-00:40 | 17297.61 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.63 | 0.00 | 01-JAN-00:10 | 10231.18 | 26-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.63 | 0.00 | 01-JAN-00:10 | 10231.18 | 26-JUN-13:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.27 | 0.00 | 01-JAN-00:40 | 9425.18 | 11-DEC-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.66 | 0.00 | 01-JAN-00:40 | 9425.18 | 11-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.66 | 0.00 | 01-JAN-00:40 | 9425.18 | 11-DEC-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.61 | 0.00 | 01-JAN-00:10 | 4938.91 | 26-JUN-07:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.61 | 0.00 | 01-JAN-00:10 | 4938.91 | 26-JUN-07:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.17 | 0.00 | 01-JAN-00:40 | 7966.76 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.31 | 0.00 | 01-JAN-00:40 | 7966.76 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.31 | 0.00 | 01-JAN-00:40 | 7966.76 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.86 | 0.00 | 01-JAN-00:10 | 4639.25 | 26-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.86 | 0.00 | 01-JAN-00:10 | 4639.25 | 26-JUN-15:30 |
EnergyTransfer:Zone:CORE_MID | 120.54 | 0.00 | 01-JAN-00:40 | 22359.44 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.38 | 0.00 | 01-JAN-00:20 | 22359.44 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.38 | 0.00 | 01-JAN-00:20 | 22359.44 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 115.16 | 0.00 | 01-JAN-00:40 | 17919.41 | 26-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 115.16 | 0.00 | 01-JAN-00:40 | 17919.41 | 26-JUN-08:10 |
EnergyTransfer:Zone:CORE_TOP | 124.19 | 0.00 | 01-JAN-00:40 | 26881.11 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 19.59 | 0.00 | 01-JAN-00:40 | 26881.11 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 19.59 | 0.00 | 01-JAN-00:40 | 26881.11 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 104.60 | 0.00 | 01-JAN-00:20 | 19280.82 | 26-JUN-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 104.60 | 0.00 | 01-JAN-00:20 | 19280.82 | 26-JUN-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 55.23 | 0.00 | 01-JAN-00:40 | 10614.63 | 29-JAN-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.56 | 0.00 | 01-JAN-00:40 | 10614.63 | 29-JAN-11:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.56 | 0.00 | 01-JAN-00:40 | 10614.63 | 29-JAN-11:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.67 | 0.00 | 01-JAN-00:10 | 7024.74 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.67 | 0.00 | 01-JAN-00:10 | 7024.74 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 41.93 | 0.00 | 01-JAN-00:40 | 10727.52 | 09-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 18.45 | 0.00 | 01-JAN-00:40 | 10727.52 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 18.45 | 0.00 | 01-JAN-00:40 | 10727.52 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.48 | 0.00 | 01-JAN-00:20 | 9048.86 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.48 | 0.00 | 01-JAN-00:20 | 9048.86 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.59 | 0.00 | 01-JAN-00:40 | 13780.32 | 09-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.32 | 0.00 | 01-JAN-00:40 | 13780.32 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.32 | 0.00 | 01-JAN-00:40 | 13780.32 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.27 | 0.00 | 01-JAN-00:20 | 13159.65 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.27 | 0.00 | 01-JAN-00:20 | 13159.65 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.02 | 0.00 | 01-JAN-00:40 | 11095.95 | 09-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 19.21 | 0.00 | 01-JAN-00:40 | 11095.95 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 19.21 | 0.00 | 01-JAN-00:40 | 11095.95 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.81 | 0.00 | 01-JAN-00:20 | 9342.09 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.81 | 0.00 | 01-JAN-00:20 | 9342.09 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.57 | 0.00 | 01-JAN-00:40 | 7619.84 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.25 | 0.00 | 01-JAN-00:40 | 7619.84 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.25 | 0.00 | 01-JAN-00:40 | 7619.84 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.32 | 0.00 | 01-JAN-00:10 | 5207.71 | 11-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.32 | 0.00 | 01-JAN-00:10 | 5207.71 | 11-SEP-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 32.24 | 0.00 | 01-JAN-00:40 | 7990.39 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 11.68 | 0.00 | 01-JAN-00:40 | 7990.39 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 11.68 | 0.00 | 01-JAN-00:40 | 7990.39 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.56 | 0.00 | 01-JAN-00:20 | 7243.35 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.56 | 0.00 | 01-JAN-00:20 | 7243.35 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 63.47 | 0.00 | 01-JAN-00:40 | 16300.17 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 35.87 | 0.00 | 01-JAN-00:40 | 16300.17 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 35.87 | 0.00 | 01-JAN-00:40 | 16300.17 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.60 | 0.00 | 01-JAN-00:20 | 11543.60 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.60 | 0.00 | 01-JAN-00:20 | 11543.60 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 32.38 | 0.00 | 01-JAN-00:40 | 8254.22 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 12.04 | 0.00 | 01-JAN-00:40 | 8254.22 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 12.04 | 0.00 | 01-JAN-00:40 | 8254.22 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.33 | 0.00 | 01-JAN-00:20 | 7289.49 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.33 | 0.00 | 01-JAN-00:20 | 7289.49 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.82 | 0.00 | 01-JAN-00:40 | 8514.60 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 19.56 | 0.00 | 01-JAN-00:40 | 8514.60 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 19.56 | 0.00 | 01-JAN-00:40 | 8514.60 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.26 | 0.00 | 01-JAN-00:10 | 6467.65 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.26 | 0.00 | 01-JAN-00:10 | 6467.65 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.19 | 0.00 | 01-JAN-00:40 | 9308.05 | 26-JUN-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 11.20 | 0.00 | 01-JAN-00:40 | 9046.53 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 11.20 | 0.00 | 01-JAN-00:40 | 9046.53 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.99 | 0.00 | 01-JAN-00:20 | 9308.05 | 26-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 22.99 | 0.00 | 01-JAN-00:20 | 9308.05 | 26-JUN-08:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.66 | 0.00 | 01-JAN-00:40 | 12246.99 | 07-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 12.55 | 0.00 | 01-JAN-00:40 | 11626.47 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 12.55 | 0.00 | 01-JAN-00:40 | 11626.47 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.11 | 0.00 | 01-JAN-00:20 | 12246.99 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.11 | 0.00 | 01-JAN-00:20 | 12246.99 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.14 | 0.00 | 01-JAN-00:40 | 9100.01 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.70 | 0.00 | 01-JAN-00:40 | 9100.01 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.70 | 0.00 | 01-JAN-00:40 | 9100.01 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.44 | 0.00 | 01-JAN-00:20 | 8944.09 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.44 | 0.00 | 01-JAN-00:20 | 8944.09 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 55.82 | 0.00 | 01-JAN-00:10 | 7150.23 | 24-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7150.23 | 24-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7150.23 | 24-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7150.23 | 24-FEB-12:20 |
EnergyTransfer:HVAC | 1243.23 | 0.00 | 01-JAN-00:40 | 345388.57 | 04-AUG-07:10 |
HeatingCoils:EnergyTransfer | 679.44 | 0.00 | 01-JAN-00:40 | 320057.74 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 563.78 | 0.00 | 01-JAN-00:10 | 345388.57 | 04-AUG-07:10 |
EnergyTransfer:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7150.23 | 24-FEB-12:20 |
WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7150.23 | 24-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7150.23 | 24-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.990 | -153.604 | 0.000 | 0.000 | 34.079 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -99.744 |
CORE_MID | 0.000 | 0.000 | 5.377 | -115.163 | 0.000 | 0.000 | 35.018 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -80.453 |
CORE_TOP | 0.000 | 0.000 | 19.593 | -104.598 | 0.000 | 0.000 | 35.579 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -105.795 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 31.561 | -23.671 | 0.000 | 0.000 | 7.652 | 4.889 | 24.333 | 17.271 | 0.000 | 0.106 | 0.001 | 0.000 | -40.842 | 0.000 | -15.326 | -5.973 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 18.453 | -23.480 | 0.000 | 0.000 | 4.771 | 3.077 | 15.404 | 32.557 | 0.000 | 0.066 | 0.001 | 0.000 | -25.417 | 0.000 | -10.363 | -15.068 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 22.321 | -38.268 | 0.000 | 0.000 | 7.442 | 4.817 | 24.332 | 67.180 | 0.000 | 0.098 | 0.001 | 0.000 | -37.114 | 0.000 | -15.825 | -34.983 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 19.207 | -23.812 | 0.000 | 0.000 | 4.800 | 3.065 | 15.403 | 33.979 | 0.000 | 0.064 | 0.001 | 0.000 | -26.309 | 0.000 | -10.403 | -15.995 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 21.247 | -19.322 | 0.000 | 0.000 | 7.648 | 4.878 | 24.333 | 17.728 | 0.000 | 0.072 | 0.000 | 0.000 | -41.322 | 0.000 | -8.367 | -6.894 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 11.675 | -20.565 | 0.000 | 0.000 | 4.754 | 3.072 | 15.404 | 32.828 | 0.000 | 0.039 | 0.000 | 0.000 | -26.063 | 0.000 | -5.714 | -15.430 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 35.874 | -27.598 | 0.000 | 0.000 | 7.713 | 4.811 | 24.332 | 68.243 | 0.000 | 1.104 | 0.000 | 0.000 | -37.832 | 0.000 | -53.305 | -23.342 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 12.043 | -20.334 | 0.000 | 0.000 | 4.775 | 3.060 | 15.403 | 34.318 | 0.000 | 0.037 | 0.001 | 0.000 | -27.016 | 0.000 | -5.743 | -16.545 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 19.564 | -24.258 | 0.000 | 0.000 | 7.577 | 4.889 | 24.333 | 17.085 | 0.000 | 0.091 | 6.186 | 0.000 | -42.278 | 0.000 | -13.189 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 11.197 | -22.994 | 0.000 | 0.000 | 3.495 | 3.077 | 15.404 | 32.344 | 0.000 | 0.055 | 0.001 | 0.000 | -26.286 | 0.000 | -8.914 | -7.379 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 12.549 | -40.107 | 0.000 | 0.000 | 7.361 | 4.817 | 24.332 | 66.942 | 0.000 | 0.084 | 0.000 | 0.000 | -38.517 | 0.000 | -13.644 | -23.818 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 11.698 | -24.442 | 0.000 | 0.000 | 4.755 | 3.065 | 15.403 | 33.878 | 0.000 | 0.054 | 0.001 | 0.000 | -27.248 | 0.000 | -8.944 | -8.220 |
TOPFLOOR_PLENUM | 35.167 | -21.630 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.086 | 9.595 | 0.000 | 0.000 | 0.000 | -23.218 | -0.004 |
MIDFLOOR_PLENUM | 15.664 | -11.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.135 | 18.339 | 0.000 | 0.000 | 0.000 | -22.527 | -0.001 |
FIRSTFLOOR_PLENUM | 10.314 | -13.859 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.109 | 21.439 | 0.000 | 0.000 | 0.000 | -18.003 | -0.001 |
Total Facility | 61.145 | -47.099 | 253.349 | -682.216 | 0.000 | 0.000 | 177.420 | 166.908 | 647.750 | 454.354 | 0.000 | 2.198 | 55.564 | 0.000 | -396.243 | 0.000 | -233.486 | -459.643 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-05:12 | 0.00 | 0.00 | 0.00 | -33990.61 | 0.00 | 0.00 | 322.22 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 29232.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-SEP-05:12 | 0.00 | 0.00 | 0.00 | -29188.63 | 0.00 | 0.00 | 324.66 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 25450.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-SEP-05:12 | 0.00 | 0.00 | 0.00 | -30346.70 | 0.00 | 0.00 | 333.40 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 26599.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 18-JUN-16:11 | 0.00 | 0.00 | 0.00 | -11787.92 | 0.00 | 0.00 | 27.61 | 19.49 | 478.42 | 2984.06 | 0.00 | 463.23 | 7815.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:42 | 0.00 | 0.00 | 0.00 | -13708.24 | 0.00 | 0.00 | 13.36 | 12.34 | 302.86 | 11184.79 | 0.00 | 0.00 | 2257.05 | 0.00 | -0.00 | 0.00 | -62.15 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:22 | 0.00 | 0.00 | 0.00 | -16630.01 | 0.00 | 0.00 | 22.43 | 19.49 | 478.41 | 14380.39 | 0.00 | 0.00 | 1889.91 | 0.00 | -0.00 | 0.00 | -160.62 | 0.00 |
PERIMETER_TOP_ZN_4 | 18-JUN-16:11 | 0.00 | 0.00 | 0.00 | -16413.17 | 0.00 | 0.00 | 12.18 | 12.34 | 302.86 | 10216.51 | 0.00 | 189.93 | 5679.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7143.71 | 0.00 | 0.00 | 145.38 | 116.94 | 637.89 | 2888.30 | 0.00 | 0.00 | 3374.52 | 0.00 | -0.00 | 0.00 | -19.31 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-09:22 | 0.00 | 0.00 | 0.00 | -9192.47 | 0.00 | 0.00 | 15.59 | 12.34 | 302.86 | 10021.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12.66 | -1147.55 |
PERIMETER_BOT_ZN_1 | 17-SEP-13:32 | 0.00 | 0.00 | 0.00 | -13742.73 | 0.00 | 0.00 | 24.59 | 19.49 | 478.41 | 13566.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -67.65 | -278.36 |
PERIMETER_BOT_ZN_4 | 16-APR-16:51 | 0.00 | 0.00 | 0.00 | -11954.78 | 0.00 | 0.00 | 16.32 | 12.34 | 302.86 | 9903.47 | 0.00 | 36.74 | 1683.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-19:12 | 0.00 | 0.00 | 0.00 | -9461.50 | 0.00 | 0.00 | 0.00 | 20.99 | 386.10 | 2564.83 | 0.00 | 99.01 | 6390.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:11 | 0.00 | 0.00 | 0.00 | -14989.42 | 0.00 | 0.00 | 13.37 | 12.34 | 302.86 | 10270.02 | 0.00 | 0.00 | 4467.48 | 0.00 | -0.00 | 0.00 | -76.65 | 0.00 |
PERIMETER_MID_ZN_1 | 17-SEP-12:52 | 0.00 | 0.00 | 0.00 | -16336.63 | 0.00 | 0.00 | 23.08 | 19.49 | 478.41 | 14249.92 | 0.00 | 0.00 | 1767.07 | 0.00 | -0.00 | 0.00 | -201.35 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:32 | 0.00 | 0.00 | 0.00 | -15548.00 | 0.00 | 0.00 | 12.01 | 12.34 | 302.86 | 11853.10 | 0.00 | 39.06 | 3328.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:40 | 0.00 | -10231.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 | 10131.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -6063.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6123.96 | 0.00 | -0.00 | 0.00 | -60.84 | 0.00 |
FIRSTFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -5632.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5679.14 | 0.00 | -0.00 | 0.00 | -46.30 | 0.00 |
Total Facility | 05-JUL-06:03 | 0.00 | -6473.18 | 0.00 | -167876.40 | 0.00 | 0.00 | 3482.87 | 4634.49 | 18346.02 | 33866.57 | 0.00 | 0.00 | 117913.15 | 0.00 | 0.00 | 0.00 | -3893.52 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 18893.45 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 3464.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22745.28 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 25511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 387.63 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28341.16 |
CORE_TOP | 23-JAN-05:11 | 0.00 | 0.00 | 30104.38 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32758.16 |
PERIMETER_TOP_ZN_3 | 11-DEC-05:21 | 0.00 | 0.00 | 11246.93 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3990.74 | 0.00 | -1523.81 | -6291.82 |
PERIMETER_TOP_ZN_2 | 06-MAR-05:11 | 0.00 | 0.00 | 12477.61 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2178.87 | 0.00 | -1531.70 | -9121.19 |
PERIMETER_TOP_ZN_1 | 06-MAR-05:11 | 0.00 | 0.00 | 15117.43 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3389.87 | 0.00 | -2298.69 | -9988.31 |
PERIMETER_TOP_ZN_4 | 06-MAR-05:11 | 0.00 | 0.00 | 13567.31 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2248.78 | 0.00 | -1538.94 | -10133.74 |
PERIMETER_BOT_ZN_3 | 30-JAN-05:11 | 0.00 | 0.00 | 7990.78 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4683.03 | 0.00 | -1457.15 | -2410.04 |
PERIMETER_BOT_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 9592.62 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3045.92 | 0.00 | -978.82 | -5922.03 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:10 | 0.00 | 0.00 | 17036.27 | 0.00 | 0.00 | 0.00 | 216.31 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 26186.52 | 0.00 | -5678.69 | 0.00 | -38643.43 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 10162.60 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3136.49 | 0.00 | -980.32 | -6399.93 |
PERIMETER_MID_ZN_3 | 30-JAN-05:21 | 0.00 | 0.00 | 9033.70 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4720.61 | 0.00 | -2195.40 | -2677.12 |
PERIMETER_MID_ZN_2 | 30-JAN-05:21 | 0.00 | 0.00 | 12022.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3086.97 | 0.00 | -1495.94 | -7793.92 |
PERIMETER_MID_ZN_1 | 30-JAN-05:21 | 0.00 | 0.00 | 13433.92 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4665.20 | 0.00 | -2247.11 | -7081.05 |
PERIMETER_MID_ZN_4 | 30-JAN-05:21 | 0.00 | 0.00 | 12363.78 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3183.31 | 0.00 | -1496.59 | -8038.03 |
TOPFLOOR_PLENUM | 02-FEB-06:13 | 18621.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -681.78 | -17939.46 |
MIDFLOOR_PLENUM | 02-JAN-07:11 | 9961.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -567.74 | -9394.14 |
FIRSTFLOOR_PLENUM | 02-JAN-08:15 | 8125.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -486.85 | -7638.44 |
Total Facility | 02-JAN-05:01 | 14564.27 | 0.00 | 201602.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1963.59 | 13392.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21506.08 | 0.00 | -13722.62 | -196293.78 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1390 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4495 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1940 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2856 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.5708 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9439 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5695 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0806 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5970 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0746 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7854 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0865 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4549 | 2.4549 | 0.6358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0583 | 2.0583 | 0.6360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1404 | 2.1404 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7280 | 0.7280 | 0.1449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8176 | 0.8176 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9912 | 0.9912 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8937 | 0.8937 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5427 | 0.5427 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6599 | 0.6599 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7805 | 0.7805 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7009 | 0.7009 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5872 | 0.5872 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8093 | 0.8093 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9064 | 0.9064 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8328 | 0.8328 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1390 | 4.4495 | 5.1390 | 1.0806 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1940 | 4.2856 | 5.1940 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.5708 | 4.9439 | 5.5708 | 1.0865 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2275 | 1.2275 | 0.6358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0292 | 1.0292 | 0.6360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0702 | 1.0702 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3640 | 0.3640 | 0.1449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4088 | 0.4088 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4956 | 0.4956 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4468 | 0.4468 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2714 | 0.2714 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3300 | 0.3300 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3902 | 0.3902 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3505 | 0.3505 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2936 | 0.2936 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4046 | 0.4046 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4532 | 0.4532 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4164 | 0.4164 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5695 | 1.0806 | 1.0806 | 1.0806 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5970 | 1.0746 | 1.0746 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7854 | 1.0865 | 1.0865 | 1.0865 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 557.83 |
Number of hours cooling loads not met | 110.00 |
Number of hours not met | 667.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 343.79 | 201872.72 | 399.59 | 143707.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 126.24 | 70376.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 166.91 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.34 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 829.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 83.70 | 30548.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 139.09 | 12793.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1414.49 |
Natural Gas | 0.00 | 538.67 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1953.16 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 138.24 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.50 |
Space Heating | 69.00 |
Space Cooling | 25.34 |
Fans (All) | 16.80 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 283.91 |
Subtotal | 283.91 |
Natural Gas [MJ/m2] | |
Space Heating | 80.20 |
Service Water Heating | 27.92 |
Miscellaneous (All) | 108.12 |
Subtotal | 108.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.55 |
Space Heating | 38.06 |
Space Cooling | 6.46 |
Fans (All) | 4.29 |
Service Water Heating | 7.12 |
Receptacle Equipment | 33.16 |
Miscellaneous | 2.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 831. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8650.67 | 109.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8682.83 | 77.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8632.33 | 127.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8694.83 | 65.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8672.50 | 87.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8747.17 | 12.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8653.67 | 106.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8690.17 | 69.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8632.83 | 127.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8630.17 | 129.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8630.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 129.83 | 0.00 | 0.00 | 0.00 |
Average | 8705.91 | 54.09 | 0.00 | 0.00 | 0.00 |
Sum | 156706.33 | 973.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8358.50 | 401.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8418.67 | 341.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8487.33 | 272.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8281.67 | 478.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8211.33 | 548.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8233.67 | 526.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8169.00 | 591.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8428.33 | 331.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8245.33 | 514.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8204.50 | 555.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8177.67 | 582.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8246.50 | 513.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8163.00 | 597.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8201.50 | 558.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8134.83 | 625.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7898.50 | 861.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8248.67 | 511.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8297.50 | 462.50 | 0.00 | 0.00 | 0.00 |
Min | 7898.50 | 272.67 | 0.00 | 0.00 | 0.00 |
Max | 8487.33 | 861.50 | 0.00 | 0.00 | 0.00 |
Average | 8244.81 | 515.19 | 0.00 | 0.00 | 0.00 |
Sum | 148406.50 | 9273.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128054.33 | 249.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128139.33 | 164.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128202.83 | 101.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24849.17 | 59.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13984.17 | 31.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24849.67 | 59.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13983.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24882.67 | 26.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14010.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24301.17 | 607.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14009.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24876.33 | 32.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10127.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24876.67 | 32.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14008.33 | 7.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128202.83 | 607.83 | 0.00 | 0.00 | 0.00 |
Average | 34064.16 | 79.18 | 0.00 | 0.00 | 0.00 |
Sum | 613154.83 | 1425.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:20
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588440E+10 | 5903.12 | 13-JAN-17:00 | 2.20 | 0.77 | 0.157869E+10 | 2455.88 | 13-JAN-14:09 | 2.20 | 0.77 |
February | 0.628737E+10 | 7638.28 | 02-FEB-09:00 | -35.6 | -35.7 | 0.151617E+10 | 2477.49 | 10-FEB-14:09 | 0.60 | -1.4 |
March | 0.860366E+10 | 10208.16 | 24-MAR-16:00 | 10.60 | 5.50 | 0.198570E+10 | 2606.64 | 28-MAR-09:20 | 8.13 | 5.04 |
April | 0.104854E+11 | 16778.03 | 17-APR-06:02 | 10.00 | 8.65 | 0.186301E+10 | 2606.66 | 13-APR-09:20 | 10.00 | 8.65 |
May | 0.156981E+11 | 32007.79 | 30-MAY-06:03 | 15.18 | 15.13 | 0.207215E+10 | 2608.36 | 01-MAY-13:50 | 15.18 | 15.13 |
June | 0.195158E+11 | 33923.16 | 12-JUN-05:12 | 17.80 | 17.26 | 0.206872E+10 | 2606.67 | 01-JUN-09:00 | 17.80 | 17.26 |
July | 0.203943E+11 | 33996.61 | 05-JUL-05:12 | 18.33 | 17.79 | 0.192375E+10 | 2606.66 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.214385E+11 | 32323.44 | 07-AUG-06:01 | 8.87 | 8.15 | 0.215964E+10 | 2784.73 | 04-AUG-07:40 | 8.87 | 8.15 |
September | 0.177852E+11 | 33917.41 | 11-SEP-05:12 | 19.80 | 17.33 | 0.191531E+10 | 2606.66 | 06-SEP-09:20 | 19.80 | 17.33 |
October | 0.118886E+11 | 14686.24 | 06-OCT-07:05 | 5.47 | 3.60 | 0.197832E+10 | 2608.59 | 13-OCT-13:00 | 8.10 | 3.96 |
November | 0.884358E+10 | 13844.87 | 07-NOV-08:10 | 10.18 | 9.48 | 0.183451E+10 | 2606.64 | 01-NOV-09:09 | 10.18 | 9.48 |
December | 0.677946E+10 | 6024.29 | 07-DEC-16:35 | -6.5 | -9.3 | 0.161893E+10 | 2509.61 | 07-DEC-14:00 | -6.5 | -9.3 |
Annual Sum or Average | 0.153604E+12 | 0.225149E+11 | ||||||||
Minimum of Months | 0.588440E+10 | 5903.12 | -35.6 | -35.7 | 0.151617E+10 | 2455.88 | -6.5 | -9.3 | ||
Maximum of Months | 0.214385E+11 | 33996.61 | 19.80 | 17.79 | 0.215964E+10 | 2784.73 | 21.47 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 4018585.94 | 266.90 | 24-FEB-15:10 | 8.30 | 5.66 | 0.00 | 0.00 | 01-FEB-00:10 | 8.30 | 5.66 |
March | 0.127189E+09 | 1643.42 | 24-MAR-14:30 | 13.05 | 6.50 | 0.00 | 0.00 | 01-MAR-00:10 | 13.05 | 6.50 |
April | 0.107577E+10 | 7824.60 | 18-APR-14:20 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.257097E+10 | 8763.58 | 31-MAY-13:50 | 29.50 | 19.49 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 19.49 |
June | 0.482020E+10 | 10231.18 | 26-JUN-13:40 | 31.50 | 21.88 | 0.00 | 0.00 | 01-JUN-00:10 | 31.50 | 21.88 |
July | 0.530282E+10 | 9675.85 | 05-JUL-13:50 | 27.12 | 19.90 | 0.00 | 0.00 | 01-JUL-00:10 | 27.12 | 19.90 |
August | 0.484662E+10 | 9836.69 | 04-AUG-15:00 | 33.90 | 25.31 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.31 |
September | 0.254231E+10 | 8756.50 | 07-SEP-14:50 | 31.78 | 18.51 | 0.00 | 0.00 | 01-SEP-00:10 | 31.78 | 18.51 |
October | 0.297817E+09 | 3447.35 | 20-OCT-14:50 | 23.18 | 13.31 | 0.00 | 0.00 | 01-OCT-00:10 | 23.18 | 13.31 |
November | 42400351.89 | 1602.29 | 03-NOV-14:30 | 16.10 | 10.04 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.216301E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.530282E+10 | 10231.18 | 33.90 | 25.31 | 0.00 | 0.00 | 33.90 | 25.31 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11921275.47 | 3489.35 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 14409711.92 | 3027.08 | 02-FEB-01:02 | -34.0 | -34.1 | 0.00 | 0.00 | 01-FEB-00:10 | -34.0 | -34.1 |
March | 44836061.45 | 2339.66 | 21-MAR-05:01 | -7.2 | -8.2 | 0.00 | 0.00 | 01-MAR-00:10 | -7.2 | -8.2 |
April | 0.417475E+09 | 3238.40 | 17-APR-15:50 | 19.40 | 11.39 | 0.00 | 0.00 | 01-APR-00:10 | 19.40 | 11.39 |
May | 0.106604E+10 | 3756.16 | 30-MAY-15:50 | 27.80 | 19.75 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.75 |
June | 0.260744E+10 | 5202.54 | 12-JUN-06:15 | 17.97 | 17.09 | 0.00 | 0.00 | 01-JUN-00:10 | 17.97 | 17.09 |
July | 0.302669E+10 | 6064.11 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.276600E+10 | 4120.86 | 04-AUG-15:30 | 33.90 | 25.83 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.83 |
September | 0.148032E+10 | 4067.93 | 11-SEP-14:20 | 28.70 | 20.20 | 0.00 | 0.00 | 01-SEP-00:10 | 28.70 | 20.20 |
October | 0.119455E+09 | 1646.74 | 26-OCT-06:02 | -0.9 | -2.2 | 0.00 | 0.00 | 01-OCT-00:10 | -0.9 | -2.2 |
November | 47005940.60 | 2536.18 | 25-NOV-05:11 | -15.6 | -16.0 | 0.00 | 0.00 | 01-NOV-00:10 | -15.6 | -16.0 |
December | 9082238.77 | 2841.87 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.116107E+11 | 0.00 | ||||||||
Minimum of Months | 9082238.77 | 1646.74 | -34.0 | -34.1 | 0.00 | 0.00 | -34.0 | -34.1 | ||
Maximum of Months | 0.302669E+10 | 6064.11 | 33.90 | 25.83 | 0.00 | 0.00 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73915907.05 | 2933.49 | 07-JAN-05:01 | -25.7 | -26.0 | 0.00 | 0.00 | 01-JAN-00:10 | -25.7 | -26.0 |
February | 80265928.22 | 3125.79 | 04-FEB-05:11 | -30.6 | -30.8 | 0.00 | 0.00 | 01-FEB-00:10 | -30.6 | -30.8 |
March | 0.146765E+09 | 2832.46 | 11-MAR-06:01 | -7.5 | -8.2 | 0.00 | 0.00 | 01-MAR-00:10 | -7.5 | -8.2 |
April | 0.546680E+09 | 2826.87 | 18-APR-15:10 | 27.75 | 20.46 | 0.00 | 0.00 | 01-APR-00:10 | 27.75 | 20.46 |
May | 0.130604E+10 | 3370.91 | 30-MAY-16:00 | 27.80 | 19.90 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.90 |
June | 0.274017E+10 | 5191.23 | 26-JUN-12:10 | 30.68 | 21.60 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 21.60 |
July | 0.325617E+10 | 5633.67 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.323136E+10 | 4050.03 | 04-AUG-16:00 | 33.90 | 26.33 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 26.33 |
September | 0.200244E+10 | 4320.54 | 11-SEP-12:10 | 27.88 | 20.86 | 0.00 | 0.00 | 01-SEP-00:10 | 27.88 | 20.86 |
October | 0.293161E+09 | 1935.06 | 27-OCT-06:02 | 0.25 | -1.1 | 0.00 | 0.00 | 01-OCT-00:10 | 0.25 | -1.1 |
November | 0.123507E+09 | 2411.15 | 10-NOV-07:01 | -2.2 | -2.8 | 0.00 | 0.00 | 01-NOV-00:10 | -2.2 | -2.8 |
December | 58574148.21 | 2194.45 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.138590E+11 | 0.00 | ||||||||
Minimum of Months | 58574148.21 | 1935.06 | -30.6 | -30.8 | 0.00 | 0.00 | -30.6 | -30.8 | ||
Maximum of Months | 0.325617E+10 | 5633.67 | 33.90 | 26.33 | 0.00 | 0.00 | 33.90 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334447E+10 | 5296.65 | 13-JAN-17:00 | 2.20 | 0.77 | 0.148477E+10 | 2272.29 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.403401E+10 | 5455.39 | 24-FEB-17:00 | 7.20 | 5.13 | 0.139072E+10 | 2288.28 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.647900E+10 | 6803.11 | 24-MAR-16:00 | 10.60 | 5.50 | 0.181118E+10 | 2606.18 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.849059E+10 | 19061.82 | 17-APR-06:02 | 10.00 | 8.65 | 0.176247E+10 | 2606.65 | 14-APR-09:30 | 10.00 | 8.65 |
May | 0.127180E+11 | 26375.03 | 30-MAY-06:03 | 15.18 | 15.13 | 0.205586E+10 | 2606.68 | 09-MAY-13:09 | 15.18 | 15.13 |
June | 0.157158E+11 | 28528.34 | 12-JUN-05:12 | 17.80 | 17.26 | 0.206400E+10 | 2606.66 | 26-JUN-09:20 | 27.57 | 22.45 |
July | 0.166329E+11 | 28430.79 | 03-JUL-05:12 | 18.50 | 17.39 | 0.192164E+10 | 2606.88 | 03-JUL-09:09 | 25.18 | 21.66 |
August | 0.167655E+11 | 26405.52 | 14-AUG-06:02 | 16.10 | 15.45 | 0.215673E+10 | 2695.67 | 04-AUG-07:30 | 16.10 | 15.45 |
September | 0.130935E+11 | 29185.67 | 11-SEP-05:12 | 19.80 | 17.33 | 0.190118E+10 | 2607.09 | 28-SEP-09:00 | 10.00 | 6.21 |
October | 0.809245E+10 | 8937.32 | 03-OCT-16:00 | 12.60 | 8.85 | 0.188726E+10 | 2606.61 | 02-OCT-13:20 | 12.60 | 8.85 |
November | 0.578330E+10 | 8658.47 | 03-NOV-16:00 | 15.00 | 9.33 | 0.167104E+10 | 2606.53 | 07-NOV-14:00 | 13.30 | 11.35 |
December | 0.401306E+10 | 5148.59 | 07-DEC-16:30 | -6.1 | -9.1 | 0.146878E+10 | 2237.62 | 07-DEC-14:00 | -6.1 | -9.1 |
Annual Sum or Average | 0.115163E+12 | 0.215756E+11 | ||||||||
Minimum of Months | 0.334447E+10 | 5148.59 | -6.1 | -9.1 | 0.139072E+10 | 2237.62 | -6.1 | -9.1 | ||
Maximum of Months | 0.167655E+11 | 29185.67 | 19.80 | 17.39 | 0.215673E+10 | 2695.67 | 27.57 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177817E+10 | 5030.84 | 13-JAN-16:40 | 2.77 | 1.17 | 0.146074E+10 | 2199.99 | 13-JAN-14:00 | 2.77 | 1.17 |
February | 0.258713E+10 | 5463.25 | 24-FEB-17:00 | 7.20 | 5.13 | 0.135047E+10 | 2287.82 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.508932E+10 | 6909.29 | 24-MAR-15:50 | 10.97 | 5.67 | 0.172962E+10 | 2591.55 | 24-MAR-13:00 | 10.97 | 5.67 |
April | 0.772197E+10 | 16025.82 | 17-APR-15:00 | 19.40 | 11.76 | 0.169676E+10 | 2606.66 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.124812E+11 | 20298.40 | 30-MAY-06:03 | 15.18 | 15.13 | 0.203694E+10 | 2606.68 | 09-MAY-13:09 | 15.18 | 15.13 |
June | 0.160320E+11 | 30247.99 | 12-JUN-05:12 | 17.80 | 17.26 | 0.205580E+10 | 2606.66 | 09-JUN-09:20 | 17.80 | 17.26 |
July | 0.169441E+11 | 30238.27 | 03-JUL-05:12 | 18.50 | 17.39 | 0.191905E+10 | 2606.66 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.166310E+11 | 25159.39 | 14-AUG-06:02 | 16.10 | 15.45 | 0.215163E+10 | 2606.72 | 08-AUG-09:09 | 16.10 | 15.45 |
September | 0.119833E+11 | 30343.75 | 11-SEP-05:12 | 19.80 | 17.33 | 0.186259E+10 | 2606.72 | 06-SEP-09:39 | 19.80 | 17.33 |
October | 0.694518E+10 | 8499.19 | 20-OCT-16:00 | 21.30 | 12.72 | 0.175600E+10 | 2606.50 | 03-OCT-13:50 | 21.30 | 12.72 |
November | 0.429749E+10 | 7805.73 | 03-NOV-16:00 | 15.00 | 9.33 | 0.157731E+10 | 2606.41 | 03-NOV-13:00 | 15.00 | 9.33 |
December | 0.210710E+10 | 4880.43 | 01-DEC-16:25 | -2.8 | -4.8 | 0.141806E+10 | 2148.81 | 01-DEC-14:00 | -2.8 | -4.8 |
Annual Sum or Average | 0.104598E+12 | 0.210150E+11 | ||||||||
Minimum of Months | 0.177817E+10 | 4880.43 | -2.8 | -4.8 | 0.135047E+10 | 2148.81 | -2.8 | -4.8 | ||
Maximum of Months | 0.169441E+11 | 30343.75 | 21.30 | 17.39 | 0.215163E+10 | 2606.72 | 23.68 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14030395.01 | 833.88 | 21-JAN-17:02 | -3.9 | -4.9 | 0.302311E+09 | 406.71 | 18-JAN-14:00 | -3.9 | -4.9 |
February | 42039935.88 | 1013.62 | 24-FEB-16:20 | 7.93 | 5.63 | 0.275657E+09 | 426.34 | 24-FEB-14:00 | 7.93 | 5.63 |
March | 0.446069E+09 | 1327.92 | 28-MAR-15:30 | 16.40 | 10.50 | 0.342146E+09 | 507.73 | 28-MAR-15:39 | 16.13 | 10.43 |
April | 0.133605E+10 | 5405.59 | 18-APR-15:00 | 28.30 | 20.65 | 0.331597E+09 | 549.50 | 18-APR-09:20 | 28.30 | 20.65 |
May | 0.305247E+10 | 5838.57 | 31-MAY-14:40 | 29.80 | 19.61 | 0.419413E+09 | 549.50 | 09-MAY-13:09 | 29.80 | 19.61 |
June | 0.478617E+10 | 11789.19 | 18-JUN-16:11 | 32.20 | 22.53 | 0.430054E+09 | 549.50 | 09-JUN-09:20 | 32.20 | 22.53 |
July | 0.502362E+10 | 9188.47 | 05-JUL-06:03 | 19.60 | 18.69 | 0.404376E+09 | 549.50 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.469800E+10 | 6392.24 | 04-AUG-15:20 | 33.90 | 25.66 | 0.451342E+09 | 549.51 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.280608E+10 | 5867.02 | 11-SEP-13:40 | 28.70 | 20.26 | 0.377379E+09 | 549.51 | 06-SEP-09:39 | 28.70 | 20.26 |
October | 0.102402E+10 | 1586.00 | 20-OCT-15:30 | 22.30 | 13.06 | 0.337498E+09 | 537.23 | 02-OCT-13:00 | 22.30 | 13.06 |
November | 0.434665E+09 | 1344.77 | 03-NOV-15:30 | 15.55 | 9.47 | 0.313998E+09 | 518.25 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 8387247.02 | 844.85 | 02-DEC-17:03 | 1.70 | 0.90 | 0.292999E+09 | 406.75 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.236716E+11 | 0.427877E+10 | ||||||||
Minimum of Months | 8387247.02 | 833.88 | -3.9 | -4.9 | 0.275657E+09 | 406.71 | -15.6 | -15.9 | ||
Maximum of Months | 0.502362E+10 | 11789.19 | 33.90 | 25.66 | 0.451342E+09 | 549.51 | 32.20 | 22.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33338665.37 | 594.93 | 12-JAN-10:30 | -1.4 | -2.2 | 0.192969E+09 | 274.88 | 12-JAN-10:39 | -0.9 | -1.9 |
February | 0.101851E+09 | 828.63 | 24-FEB-10:20 | 4.80 | 1.70 | 0.178191E+09 | 345.71 | 24-FEB-10:20 | 4.80 | 1.70 |
March | 0.502068E+09 | 2578.44 | 28-MAR-09:25 | 8.60 | 5.36 | 0.230797E+09 | 347.88 | 28-MAR-09:50 | 9.53 | 5.99 |
April | 0.138660E+10 | 7604.22 | 18-APR-09:20 | 23.73 | 19.27 | 0.222749E+09 | 347.88 | 13-APR-09:20 | 23.73 | 19.27 |
May | 0.309151E+10 | 11075.11 | 28-MAY-09:02 | 19.68 | 17.00 | 0.273709E+09 | 348.26 | 31-MAY-09:39 | 26.83 | 19.51 |
June | 0.471944E+10 | 13691.76 | 25-JUN-08:42 | 25.73 | 21.05 | 0.273528E+09 | 348.47 | 26-JUN-09:00 | 28.30 | 22.44 |
July | 0.503818E+10 | 13713.38 | 02-JUL-08:42 | 25.32 | 20.92 | 0.256852E+09 | 348.60 | 05-JUL-09:30 | 23.60 | 20.34 |
August | 0.456127E+10 | 11722.59 | 27-AUG-08:53 | 22.80 | 19.47 | 0.287234E+09 | 348.36 | 02-AUG-09:50 | 22.80 | 19.47 |
September | 0.291186E+10 | 12216.59 | 04-SEP-08:43 | 15.63 | 12.89 | 0.247270E+09 | 347.90 | 06-SEP-09:30 | 24.20 | 17.85 |
October | 0.814673E+09 | 3032.41 | 20-OCT-09:30 | 13.70 | 9.50 | 0.231238E+09 | 347.88 | 20-OCT-09:20 | 13.70 | 9.50 |
November | 0.299776E+09 | 1117.97 | 04-NOV-09:20 | 6.87 | 3.64 | 0.201754E+09 | 347.85 | 03-NOV-13:00 | 6.87 | 3.64 |
December | 19462451.67 | 561.51 | 01-DEC-10:15 | -2.9 | -4.5 | 0.186116E+09 | 265.31 | 01-DEC-10:20 | -2.9 | -4.5 |
Annual Sum or Average | 0.234800E+11 | 0.278241E+10 | ||||||||
Minimum of Months | 19462451.67 | 561.51 | -2.9 | -4.5 | 0.178191E+09 | 265.31 | -2.9 | -4.5 | ||
Maximum of Months | 0.503818E+10 | 13713.38 | 25.73 | 21.05 | 0.287234E+09 | 348.60 | 28.30 | 22.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494816E+09 | 4572.04 | 12-JAN-12:30 | 1.95 | 0.38 | 0.327816E+09 | 549.50 | 03-JAN-14:20 | 1.95 | 0.38 |
February | 0.747825E+09 | 7622.71 | 24-FEB-13:40 | 7.43 | 4.81 | 0.303590E+09 | 550.34 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.145228E+10 | 8024.07 | 24-MAR-13:30 | 12.75 | 6.50 | 0.377152E+09 | 549.50 | 22-MAR-13:00 | 12.75 | 6.50 |
April | 0.268728E+10 | 16395.60 | 16-APR-13:42 | 27.62 | 20.47 | 0.351313E+09 | 549.89 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.413484E+10 | 10201.98 | 29-MAY-12:03 | 24.08 | 18.40 | 0.424513E+09 | 549.79 | 30-MAY-13:39 | 26.70 | 19.86 |
June | 0.576237E+10 | 16078.30 | 18-JUN-16:11 | 32.20 | 22.53 | 0.430280E+09 | 550.21 | 26-JUN-13:50 | 31.60 | 21.99 |
July | 0.637519E+10 | 16375.12 | 30-JUL-13:12 | 26.87 | 20.18 | 0.404491E+09 | 549.99 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.685573E+10 | 16565.99 | 13-AUG-13:02 | 25.18 | 19.76 | 0.452360E+09 | 550.25 | 21-AUG-13:50 | 29.32 | 21.76 |
September | 0.546956E+10 | 16630.14 | 04-SEP-13:22 | 21.40 | 14.09 | 0.388261E+09 | 555.26 | 07-SEP-13:09 | 31.78 | 18.11 |
October | 0.270920E+10 | 11504.40 | 01-OCT-13:13 | 18.80 | 12.23 | 0.376916E+09 | 549.69 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.100607E+10 | 9937.71 | 03-NOV-13:30 | 15.85 | 10.76 | 0.334661E+09 | 549.62 | 03-NOV-13:50 | 16.02 | 10.57 |
December | 0.573176E+09 | 5499.30 | 01-DEC-13:30 | -0.9 | -3.3 | 0.317123E+09 | 549.49 | 20-DEC-14:20 | -6.9 | -8.3 |
Annual Sum or Average | 0.382683E+11 | 0.448848E+10 | ||||||||
Minimum of Months | 0.494816E+09 | 4572.04 | -0.9 | -3.3 | 0.303590E+09 | 549.49 | -6.9 | -8.3 | ||
Maximum of Months | 0.685573E+10 | 16630.14 | 32.20 | 22.53 | 0.452360E+09 | 555.26 | 31.78 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51266978.26 | 774.67 | 12-JAN-15:50 | 2.80 | 1.13 | 0.194059E+09 | 321.25 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.141478E+09 | 2644.49 | 24-FEB-16:30 | 7.75 | 5.51 | 0.179556E+09 | 348.07 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.510273E+09 | 3083.74 | 23-MAR-16:00 | 17.20 | 10.15 | 0.224238E+09 | 347.83 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.164726E+10 | 15013.43 | 16-APR-16:22 | 28.60 | 20.44 | 0.217230E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.292649E+10 | 14070.33 | 14-MAY-16:32 | 21.70 | 15.60 | 0.267331E+09 | 347.86 | 09-MAY-13:20 | 21.70 | 15.60 |
June | 0.457767E+10 | 16420.06 | 18-JUN-16:11 | 32.20 | 22.53 | 0.272510E+09 | 347.86 | 09-JUN-09:20 | 32.20 | 22.53 |
July | 0.499937E+10 | 15457.40 | 02-JUL-16:42 | 28.98 | 21.21 | 0.256296E+09 | 347.85 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.468781E+10 | 14113.38 | 05-AUG-17:05 | 25.32 | 17.94 | 0.286411E+09 | 347.86 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.285895E+10 | 13458.36 | 04-SEP-16:02 | 22.20 | 14.41 | 0.241141E+09 | 347.86 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.999666E+09 | 5423.91 | 20-OCT-15:30 | 22.30 | 13.06 | 0.223512E+09 | 347.84 | 11-OCT-13:20 | 22.30 | 13.06 |
November | 0.344572E+09 | 3579.94 | 03-NOV-15:30 | 15.55 | 9.47 | 0.202280E+09 | 347.83 | 03-NOV-13:20 | 15.55 | 9.47 |
December | 68252279.21 | 770.21 | 01-DEC-15:40 | -1.5 | -3.9 | 0.188040E+09 | 320.08 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.238131E+11 | 0.275260E+10 | ||||||||
Minimum of Months | 51266978.26 | 770.21 | -1.5 | -3.9 | 0.179556E+09 | 320.08 | -1.7 | -4.1 | ||
Maximum of Months | 0.499937E+10 | 16420.06 | 32.20 | 22.53 | 0.286411E+09 | 348.07 | 32.20 | 22.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9192029.38 | 817.24 | 14-JAN-17:03 | -7.4 | -8.6 | 0.300379E+09 | 406.72 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 16256216.90 | 822.74 | 25-FEB-17:05 | 4.63 | 1.87 | 0.274509E+09 | 406.70 | 01-FEB-14:39 | 4.63 | 1.87 |
March | 0.283940E+09 | 1084.29 | 28-MAR-15:30 | 16.40 | 10.50 | 0.336571E+09 | 455.53 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.825102E+09 | 2813.24 | 18-APR-15:00 | 28.30 | 20.65 | 0.317278E+09 | 549.49 | 18-APR-13:20 | 28.30 | 20.65 |
May | 0.194268E+10 | 3657.21 | 31-MAY-15:00 | 30.00 | 19.70 | 0.405251E+09 | 549.50 | 05-MAY-13:20 | 30.00 | 19.70 |
June | 0.343883E+10 | 5129.66 | 26-JUN-14:30 | 31.40 | 21.97 | 0.428975E+09 | 549.50 | 09-JUN-09:20 | 31.40 | 21.97 |
July | 0.394860E+10 | 7147.17 | 05-JUL-06:03 | 19.60 | 18.69 | 0.404103E+09 | 549.50 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.404961E+10 | 5196.03 | 04-AUG-15:30 | 33.90 | 25.83 | 0.453069E+09 | 563.14 | 04-AUG-07:40 | 33.90 | 25.83 |
September | 0.276964E+10 | 5335.42 | 11-SEP-06:03 | 19.50 | 17.29 | 0.389132E+09 | 549.50 | 06-SEP-09:20 | 19.50 | 17.29 |
October | 0.140891E+10 | 1486.10 | 20-OCT-13:50 | 22.47 | 12.96 | 0.356648E+09 | 538.50 | 02-OCT-13:00 | 22.47 | 12.96 |
November | 0.619405E+09 | 1287.26 | 03-NOV-15:00 | 16.10 | 9.59 | 0.322975E+09 | 518.66 | 03-NOV-13:00 | 16.10 | 9.59 |
December | 10482973.52 | 826.76 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293540E+09 | 406.72 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.193226E+11 | 0.428243E+10 | ||||||||
Minimum of Months | 9192029.38 | 817.24 | -7.4 | -8.6 | 0.274509E+09 | 406.70 | -17.2 | -17.5 | ||
Maximum of Months | 0.404961E+10 | 7147.17 | 33.90 | 25.83 | 0.453069E+09 | 563.14 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28333779.68 | 577.45 | 13-JAN-11:00 | 2.20 | 0.51 | 0.193141E+09 | 269.23 | 13-JAN-10:00 | 2.20 | 0.51 |
February | 70720137.12 | 712.65 | 24-FEB-10:05 | 4.60 | 1.53 | 0.176905E+09 | 309.76 | 24-FEB-10:20 | 4.80 | 1.70 |
March | 0.389696E+09 | 1103.88 | 28-MAR-09:35 | 9.07 | 5.68 | 0.225099E+09 | 347.88 | 28-MAR-09:20 | 9.07 | 5.68 |
April | 0.923286E+09 | 5034.65 | 18-APR-09:30 | 24.20 | 19.59 | 0.216891E+09 | 347.88 | 13-APR-09:20 | 24.20 | 19.59 |
May | 0.211432E+10 | 5900.52 | 31-MAY-09:20 | 26.47 | 19.61 | 0.272335E+09 | 347.88 | 09-MAY-09:20 | 26.47 | 19.61 |
June | 0.381146E+10 | 8606.06 | 25-JUN-09:22 | 26.95 | 21.50 | 0.273947E+09 | 359.58 | 26-JUN-07:00 | 25.00 | 21.93 |
July | 0.437231E+10 | 9193.52 | 02-JUL-09:22 | 26.15 | 21.26 | 0.256959E+09 | 348.25 | 05-JUL-09:09 | 23.07 | 20.39 |
August | 0.428829E+10 | 7510.98 | 02-AUG-06:03 | 17.15 | 16.66 | 0.287872E+09 | 366.65 | 04-AUG-07:40 | 25.03 | 24.26 |
September | 0.303032E+10 | 9174.46 | 04-SEP-10:13 | 18.67 | 13.05 | 0.252591E+09 | 347.88 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.106891E+10 | 2572.71 | 20-OCT-09:30 | 13.70 | 9.50 | 0.247122E+09 | 347.88 | 20-OCT-09:20 | 13.70 | 9.50 |
November | 0.432499E+09 | 1261.78 | 04-NOV-08:45 | 5.03 | 2.41 | 0.209121E+09 | 347.87 | 03-NOV-13:20 | 5.03 | 2.41 |
December | 34509430.80 | 587.43 | 05-DEC-09:30 | -6.4 | -8.4 | 0.186873E+09 | 270.20 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.205646E+11 | 0.279886E+10 | ||||||||
Minimum of Months | 28333779.68 | 577.45 | -6.4 | -8.4 | 0.176905E+09 | 269.23 | -5.9 | -8.1 | ||
Maximum of Months | 0.437231E+10 | 9193.52 | 26.95 | 21.50 | 0.287872E+09 | 366.65 | 26.47 | 24.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72041153.20 | 1105.52 | 13-JAN-14:30 | 3.90 | 1.72 | 0.274445E+09 | 483.75 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.159807E+09 | 1307.39 | 24-FEB-14:50 | 8.22 | 5.55 | 0.262492E+09 | 547.10 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.478592E+09 | 3360.41 | 24-MAR-14:00 | 13.30 | 6.51 | 0.335904E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.115582E+10 | 9377.14 | 16-APR-13:32 | 27.43 | 20.35 | 0.323361E+09 | 549.57 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.221302E+10 | 9620.57 | 31-MAY-12:00 | 29.40 | 19.85 | 0.397069E+09 | 549.51 | 03-MAY-13:20 | 29.40 | 19.85 |
June | 0.410122E+10 | 11050.86 | 26-JUN-16:10 | 31.60 | 21.99 | 0.419099E+09 | 561.43 | 26-JUN-12:09 | 31.60 | 21.99 |
July | 0.518441E+10 | 10520.57 | 30-JUL-13:12 | 26.87 | 20.18 | 0.401905E+09 | 549.63 | 05-JUL-13:50 | 26.87 | 20.18 |
August | 0.621200E+10 | 11070.04 | 04-AUG-12:00 | 31.10 | 26.10 | 0.450689E+09 | 574.12 | 04-AUG-12:09 | 31.20 | 26.19 |
September | 0.499856E+10 | 13742.23 | 17-SEP-13:32 | 26.67 | 18.01 | 0.385597E+09 | 606.88 | 07-SEP-12:09 | 26.67 | 18.01 |
October | 0.205316E+10 | 8822.00 | 20-OCT-13:40 | 22.33 | 12.89 | 0.372344E+09 | 549.57 | 20-OCT-13:50 | 22.47 | 12.96 |
November | 0.777883E+09 | 7475.52 | 04-NOV-13:30 | 14.15 | 6.81 | 0.316346E+09 | 549.49 | 03-NOV-13:20 | 14.15 | 6.81 |
December | 0.191808E+09 | 1239.07 | 02-DEC-12:40 | 5.40 | 2.84 | 0.278293E+09 | 501.85 | 01-DEC-14:39 | 5.40 | 2.84 |
Annual Sum or Average | 0.275983E+11 | 0.421754E+10 | ||||||||
Minimum of Months | 72041153.20 | 1105.52 | 3.90 | 1.72 | 0.262492E+09 | 483.75 | 3.90 | 1.72 | ||
Maximum of Months | 0.621200E+10 | 13742.23 | 31.60 | 26.10 | 0.450689E+09 | 606.88 | 31.60 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30279737.84 | 688.86 | 12-JAN-16:00 | 2.80 | 1.13 | 0.193584E+09 | 294.94 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 84838229.24 | 1303.02 | 24-FEB-16:40 | 7.57 | 5.38 | 0.177874E+09 | 338.68 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.355624E+09 | 1366.32 | 23-MAR-16:00 | 17.20 | 10.15 | 0.220130E+09 | 338.68 | 24-MAR-15:20 | 12.07 | 6.17 |
April | 0.105365E+10 | 11952.14 | 16-APR-16:51 | 28.30 | 20.28 | 0.215102E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.189164E+10 | 6854.39 | 21-MAY-17:02 | 17.70 | 9.59 | 0.265205E+09 | 347.85 | 09-MAY-13:20 | 17.70 | 9.59 |
June | 0.360995E+10 | 11879.21 | 25-JUN-17:21 | 31.40 | 21.75 | 0.272846E+09 | 347.86 | 20-JUN-13:00 | 31.40 | 21.75 |
July | 0.430632E+10 | 11833.85 | 23-JUL-18:32 | 22.20 | 14.56 | 0.256865E+09 | 347.86 | 19-JUL-09:20 | 22.20 | 14.56 |
August | 0.437139E+10 | 10700.81 | 13-AUG-16:01 | 25.50 | 20.53 | 0.287886E+09 | 347.87 | 08-AUG-09:09 | 25.50 | 20.53 |
September | 0.289057E+10 | 11617.32 | 04-SEP-16:51 | 22.20 | 14.41 | 0.249906E+09 | 347.86 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.120386E+10 | 4497.46 | 11-OCT-16:00 | 17.80 | 11.96 | 0.239701E+09 | 348.00 | 13-OCT-13:00 | 8.10 | 3.96 |
November | 0.468549E+09 | 2933.58 | 03-NOV-15:40 | 15.37 | 9.43 | 0.210074E+09 | 347.84 | 03-NOV-13:20 | 15.37 | 9.43 |
December | 67552452.75 | 722.37 | 01-DEC-15:50 | -1.6 | -4.0 | 0.188099E+09 | 305.52 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.203342E+11 | 0.277727E+10 | ||||||||
Minimum of Months | 30279737.84 | 688.86 | -1.6 | -4.0 | 0.177874E+09 | 294.94 | -1.7 | -4.1 | ||
Maximum of Months | 0.437139E+10 | 11952.14 | 31.40 | 21.75 | 0.287886E+09 | 348.00 | 31.40 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26070325.76 | 851.55 | 13-JAN-14:30 | 3.90 | 1.72 | 0.302888E+09 | 408.08 | 13-JAN-14:50 | 3.90 | 1.72 |
February | 65090873.68 | 951.51 | 24-FEB-16:30 | 7.75 | 5.51 | 0.276669E+09 | 430.23 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.581268E+09 | 1248.08 | 28-MAR-15:20 | 16.67 | 10.57 | 0.348193E+09 | 516.60 | 24-MAR-13:00 | 16.67 | 10.57 |
April | 0.146826E+10 | 4977.99 | 18-APR-15:00 | 28.30 | 20.65 | 0.342501E+09 | 549.49 | 18-APR-09:20 | 28.30 | 20.65 |
May | 0.303757E+10 | 5413.96 | 31-MAY-06:03 | 18.27 | 16.32 | 0.426691E+09 | 549.51 | 09-MAY-09:20 | 18.27 | 16.32 |
June | 0.464158E+10 | 9460.63 | 25-JUN-19:12 | 28.87 | 21.34 | 0.433512E+09 | 550.76 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.491447E+10 | 9409.44 | 02-JUL-18:31 | 27.57 | 20.99 | 0.405114E+09 | 550.47 | 03-JUL-13:20 | 29.07 | 24.32 |
August | 0.467004E+10 | 5789.03 | 04-AUG-15:20 | 33.90 | 25.66 | 0.453547E+09 | 563.05 | 04-AUG-07:30 | 33.90 | 25.66 |
September | 0.293907E+10 | 7256.11 | 11-SEP-06:03 | 19.50 | 17.29 | 0.389360E+09 | 549.54 | 11-SEP-13:20 | 28.50 | 20.29 |
October | 0.133156E+10 | 1801.80 | 02-OCT-15:00 | 18.30 | 14.84 | 0.357912E+09 | 549.49 | 03-OCT-13:20 | 12.97 | 9.14 |
November | 0.572717E+09 | 1449.17 | 03-NOV-13:10 | 15.68 | 10.94 | 0.323872E+09 | 531.32 | 07-NOV-14:20 | 12.97 | 11.23 |
December | 10105167.62 | 797.09 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293722E+09 | 406.72 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.242578E+11 | 0.435398E+10 | ||||||||
Minimum of Months | 10105167.62 | 797.09 | 1.70 | 0.90 | 0.276669E+09 | 406.72 | -15.6 | -15.9 | ||
Maximum of Months | 0.491447E+10 | 9460.63 | 33.90 | 25.66 | 0.453547E+09 | 563.05 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36198748.52 | 665.91 | 13-JAN-11:05 | 2.48 | 0.68 | 0.141781E+09 | 290.16 | 13-JAN-11:09 | 2.48 | 0.68 |
February | 0.110124E+09 | 1941.14 | 24-FEB-11:05 | 5.68 | 2.52 | 0.131733E+09 | 355.92 | 24-FEB-11:09 | 5.68 | 2.52 |
March | 0.509638E+09 | 4769.49 | 24-MAR-12:02 | 11.78 | 6.31 | 0.173387E+09 | 356.46 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.140359E+10 | 8045.88 | 18-APR-10:05 | 25.78 | 20.58 | 0.168805E+09 | 356.46 | 25-APR-12:09 | 5.68 | 1.74 |
May | 0.301885E+10 | 13585.71 | 29-MAY-09:12 | 22.77 | 18.33 | 0.203614E+09 | 356.47 | 04-MAY-10:09 | 22.77 | 18.33 |
June | 0.447536E+10 | 14947.93 | 25-JUN-08:31 | 25.37 | 20.95 | 0.203806E+09 | 374.10 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.483685E+10 | 14993.70 | 02-JUL-08:31 | 25.03 | 20.84 | 0.191214E+09 | 356.46 | 18-JUL-10:09 | 22.30 | 15.22 |
August | 0.439148E+10 | 13818.64 | 20-AUG-08:52 | 20.60 | 18.33 | 0.213119E+09 | 357.69 | 04-AUG-07:30 | 20.60 | 18.33 |
September | 0.295205E+10 | 11397.09 | 17-SEP-08:53 | 21.70 | 16.10 | 0.185927E+09 | 356.45 | 05-SEP-14:09 | 21.70 | 16.10 |
October | 0.886895E+09 | 4833.05 | 03-OCT-12:02 | 12.30 | 9.04 | 0.178871E+09 | 356.46 | 30-OCT-12:09 | 16.13 | 9.73 |
November | 0.331430E+09 | 2986.45 | 04-NOV-10:05 | 9.60 | 5.18 | 0.152974E+09 | 356.45 | 03-NOV-12:09 | 9.60 | 5.18 |
December | 41346833.45 | 631.71 | 05-DEC-09:50 | -6.2 | -8.3 | 0.136998E+09 | 278.72 | 05-DEC-09:00 | -6.1 | -8.3 |
Annual Sum or Average | 0.229938E+11 | 0.208223E+10 | ||||||||
Minimum of Months | 36198748.52 | 631.71 | -6.2 | -8.3 | 0.131733E+09 | 278.72 | -6.1 | -8.3 | ||
Maximum of Months | 0.483685E+10 | 14993.70 | 25.78 | 20.95 | 0.213119E+09 | 374.10 | 25.37 | 22.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607304E+09 | 5219.29 | 12-JAN-12:30 | 1.95 | 0.38 | 0.332927E+09 | 549.50 | 03-JAN-14:20 | 1.95 | 0.38 |
February | 0.878240E+09 | 7748.21 | 24-FEB-13:25 | 7.25 | 4.63 | 0.310093E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.171650E+10 | 8158.92 | 24-MAR-13:10 | 12.38 | 6.48 | 0.385497E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.289524E+10 | 15132.50 | 16-APR-13:32 | 27.43 | 20.35 | 0.361240E+09 | 550.38 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.419195E+10 | 9268.72 | 30-MAY-13:20 | 26.70 | 19.86 | 0.429807E+09 | 550.75 | 30-MAY-13:20 | 26.70 | 19.86 |
June | 0.563389E+10 | 14791.34 | 25-JUN-11:12 | 29.80 | 22.12 | 0.433421E+09 | 550.83 | 30-JUN-13:20 | 29.40 | 21.96 |
July | 0.627620E+10 | 15632.39 | 30-JUL-12:22 | 26.70 | 21.03 | 0.405336E+09 | 550.90 | 05-JUL-13:20 | 26.70 | 21.03 |
August | 0.684229E+10 | 15119.57 | 13-AUG-12:53 | 25.00 | 19.70 | 0.454142E+09 | 550.70 | 11-AUG-13:20 | 25.00 | 19.70 |
September | 0.575682E+10 | 16335.40 | 17-SEP-12:52 | 25.60 | 17.75 | 0.396477E+09 | 566.01 | 07-SEP-13:20 | 25.60 | 17.75 |
October | 0.329042E+10 | 15119.31 | 01-OCT-13:43 | 18.95 | 12.28 | 0.391776E+09 | 549.62 | 20-OCT-13:20 | 22.07 | 12.75 |
November | 0.128235E+10 | 10272.02 | 03-NOV-13:05 | 15.68 | 10.94 | 0.346884E+09 | 549.62 | 03-NOV-13:39 | 15.93 | 10.67 |
December | 0.736282E+09 | 6013.28 | 01-DEC-13:15 | -0.9 | -3.3 | 0.321454E+09 | 549.50 | 28-DEC-14:20 | -4.8 | -6.0 |
Annual Sum or Average | 0.401075E+11 | 0.456905E+10 | ||||||||
Minimum of Months | 0.607304E+09 | 5219.29 | -0.9 | -3.3 | 0.310093E+09 | 549.50 | -4.8 | -6.0 | ||
Maximum of Months | 0.684229E+10 | 16335.40 | 29.80 | 22.12 | 0.454142E+09 | 566.01 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70696432.98 | 795.40 | 12-JAN-16:00 | 2.80 | 1.13 | 0.194643E+09 | 327.11 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.180124E+09 | 2622.94 | 24-FEB-16:30 | 7.75 | 5.51 | 0.180714E+09 | 347.82 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.625063E+09 | 3178.29 | 22-MAR-15:40 | 6.70 | 3.37 | 0.228123E+09 | 347.83 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.176024E+10 | 14776.38 | 16-APR-16:51 | 28.30 | 20.28 | 0.223735E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.294608E+10 | 14584.63 | 21-MAY-16:32 | 18.17 | 10.08 | 0.271120E+09 | 347.86 | 09-MAY-09:20 | 18.17 | 10.08 |
June | 0.447846E+10 | 14828.48 | 25-JUN-16:32 | 31.87 | 21.81 | 0.274485E+09 | 347.86 | 20-JUN-13:00 | 31.87 | 21.81 |
July | 0.492427E+10 | 15550.57 | 02-JUL-16:32 | 29.07 | 21.24 | 0.256809E+09 | 347.91 | 03-JUL-09:09 | 25.18 | 21.66 |
August | 0.467301E+10 | 14873.11 | 13-AUG-16:11 | 25.40 | 20.51 | 0.287508E+09 | 347.87 | 08-AUG-09:09 | 25.40 | 20.51 |
September | 0.298948E+10 | 13683.71 | 17-SEP-16:52 | 26.10 | 17.62 | 0.247680E+09 | 347.86 | 06-SEP-09:20 | 26.10 | 17.62 |
October | 0.125504E+10 | 5447.82 | 20-OCT-15:30 | 22.30 | 13.06 | 0.234282E+09 | 347.84 | 19-OCT-13:20 | 22.30 | 13.06 |
November | 0.452014E+09 | 3751.33 | 03-NOV-15:30 | 15.55 | 9.47 | 0.208875E+09 | 347.83 | 03-NOV-13:20 | 15.55 | 9.47 |
December | 88390640.46 | 796.50 | 01-DEC-15:50 | -1.6 | -4.0 | 0.189413E+09 | 328.03 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.244429E+11 | 0.279739E+10 | ||||||||
Minimum of Months | 70696432.98 | 795.40 | -1.6 | -4.0 | 0.180714E+09 | 327.11 | -1.7 | -4.1 | ||
Maximum of Months | 0.492427E+10 | 15550.57 | 31.87 | 21.81 | 0.287508E+09 | 347.91 | 31.87 | 21.81 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.729169E+09 | 18893.49 | 02-JAN-05:01 | -4.5 |
February | 99300603.72 | 15830.74 | 06-FEB-06:01 | -15.0 |
March | 10208804.93 | 16616.44 | 06-MAR-06:01 | -14.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 35023191.54 | 15746.24 | 28-NOV-06:01 | -18.2 |
December | 0.116156E+09 | 15458.84 | 11-DEC-06:01 | -22.1 |
Annual Sum or Average | 0.989858E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.1 | |
Maximum of Months | 0.729169E+09 | 18893.49 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.989031E+10 | 17718.91 | 31-JAN-06:12 | -30.6 |
February | 0.623211E+10 | 18621.21 | 02-FEB-06:13 | -36.7 |
March | 0.330645E+10 | 15944.95 | 06-MAR-06:05 | -14.1 |
April | 0.136598E+10 | 12870.19 | 03-APR-05:13 | -7.2 |
May | 0.346043E+09 | 4240.99 | 21-MAY-07:27 | 9.20 |
June | 0.171820E+09 | 2687.76 | 03-JUN-05:05 | 5.78 |
July | 92333760.01 | 2910.31 | 23-JUL-08:23 | 17.50 |
August | 0.151748E+09 | 2612.22 | 27-AUG-07:37 | 17.97 |
September | 0.543395E+09 | 4939.85 | 04-SEP-08:62 | 13.77 |
October | 0.121223E+10 | 7627.24 | 23-OCT-06:02 | -3.0 |
November | 0.419611E+10 | 16013.65 | 28-NOV-06:12 | -18.1 |
December | 0.765837E+10 | 17538.53 | 09-DEC-06:12 | -22.8 |
Annual Sum or Average | 0.351669E+11 | |||
Minimum of Months | 92333760.01 | 2612.22 | -36.7 | |
Maximum of Months | 0.989031E+10 | 18621.21 | 17.97 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414750E+10 | 9961.90 | 02-JAN-07:11 | -6.1 |
February | 0.256872E+10 | 9049.35 | 06-FEB-07:05 | -15.0 |
March | 0.175607E+10 | 8046.25 | 06-MAR-07:11 | -12.6 |
April | 0.765146E+09 | 6110.42 | 03-APR-06:11 | -7.0 |
May | 0.115807E+09 | 3671.25 | 21-MAY-08:13 | 11.50 |
June | 39382239.05 | 4187.24 | 11-JUN-15:11 | 33.13 |
July | 34171038.15 | 3738.87 | 02-JUL-15:11 | 29.40 |
August | 23171303.02 | 3663.24 | 13-AUG-15:31 | 25.77 |
September | 0.175758E+09 | 4560.98 | 17-SEP-14:12 | 27.20 |
October | 0.898813E+09 | 5500.69 | 01-OCT-13:43 | 18.95 |
November | 0.190875E+10 | 9531.87 | 27-NOV-07:11 | -9.4 |
December | 0.323026E+10 | 9757.05 | 11-DEC-07:03 | -21.7 |
Annual Sum or Average | 0.156635E+11 | |||
Minimum of Months | 23171303.02 | 3663.24 | -21.7 | |
Maximum of Months | 0.414750E+10 | 9961.90 | 33.13 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303624E+10 | 8125.30 | 02-JAN-08:15 | -7.6 |
February | 0.179210E+10 | 6093.76 | 06-FEB-06:04 | -15.0 |
March | 0.117493E+10 | 4403.39 | 06-MAR-07:01 | -12.7 |
April | 0.417335E+09 | 2991.55 | 03-APR-07:18 | -6.5 |
May | 36776408.78 | 1676.68 | 21-MAY-15:10 | 17.98 |
June | 10338225.64 | 1533.64 | 25-JUN-15:22 | 32.20 |
July | 18259045.96 | 1714.39 | 02-JUL-14:42 | 29.32 |
August | 13182616.19 | 2195.76 | 13-AUG-15:22 | 25.85 |
September | 45111305.97 | 2983.44 | 17-SEP-14:12 | 27.20 |
October | 0.343736E+09 | 2662.46 | 29-OCT-12:10 | 11.88 |
November | 0.121371E+10 | 5811.24 | 27-NOV-07:01 | -9.4 |
December | 0.221238E+10 | 5951.37 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.103141E+11 | |||
Minimum of Months | 10338225.64 | 1533.64 | -21.7 | |
Maximum of Months | 0.303624E+10 | 8125.30 | 32.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240800E+10 | 25511.53 | 02-JAN-05:01 | -4.5 |
February | 0.904745E+09 | 24170.95 | 06-FEB-05:01 | -14.5 |
March | 0.246505E+09 | 22888.95 | 06-MAR-06:01 | -14.1 |
April | 45325376.89 | 21892.07 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.543789E+09 | 24200.91 | 27-NOV-05:01 | -9.4 |
December | 0.122818E+10 | 24472.12 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.537655E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.240800E+10 | 25511.53 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.693259E+10 | 30103.63 | 23-JAN-05:11 | -18.0 |
February | 0.374729E+10 | 29721.77 | 06-FEB-05:01 | -14.5 |
March | 0.143695E+10 | 29672.12 | 06-MAR-05:11 | -15.2 |
April | 0.306946E+09 | 28440.49 | 03-APR-04:11 | -6.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2406542.69 | 16043.62 | 30-SEP-06:03 | 0.60 |
October | 77803962.77 | 25303.65 | 16-OCT-05:01 | 0.48 |
November | 0.229866E+10 | 29729.17 | 27-NOV-05:01 | -9.4 |
December | 0.479011E+10 | 29980.21 | 26-DEC-05:01 | -4.2 |
Annual Sum or Average | 0.195928E+11 | |||
Minimum of Months | 0.00 | 0.00 | -18.0 | |
Maximum of Months | 0.693259E+10 | 30103.63 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101031E+11 | 11229.45 | 31-JAN-03:22 | -30.6 |
February | 0.607509E+10 | 11206.58 | 06-FEB-02:62 | -17.9 |
March | 0.286341E+10 | 11246.69 | 06-MAR-05:11 | -15.2 |
April | 0.703926E+09 | 10550.69 | 03-APR-02:13 | -6.1 |
May | 11178659.56 | 8524.84 | 02-MAY-05:12 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 55014580.67 | 9004.18 | 30-SEP-05:01 | 0.10 |
October | 0.429736E+09 | 9367.88 | 17-OCT-05:01 | 0.77 |
November | 0.369038E+10 | 11219.29 | 26-NOV-02:52 | -25.0 |
December | 0.762938E+10 | 11246.96 | 11-DEC-05:21 | -22.2 |
Annual Sum or Average | 0.315612E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.101031E+11 | 11246.96 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607946E+10 | 12438.12 | 23-JAN-05:11 | -18.0 |
February | 0.339616E+10 | 12348.96 | 04-FEB-23:22 | -17.5 |
March | 0.149725E+10 | 12477.96 | 06-MAR-05:11 | -15.2 |
April | 0.373853E+09 | 11607.91 | 03-APR-04:11 | -6.9 |
May | 2033293.88 | 5622.84 | 02-MAY-05:12 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 24481058.83 | 9884.83 | 30-SEP-05:01 | 0.10 |
October | 0.207376E+09 | 10362.87 | 23-OCT-05:01 | -2.7 |
November | 0.221372E+10 | 12355.17 | 26-NOV-02:52 | -25.0 |
December | 0.465867E+10 | 12348.54 | 09-DEC-21:22 | -20.0 |
Annual Sum or Average | 0.184530E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.607946E+10 | 12477.96 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.709241E+10 | 15059.21 | 23-JAN-05:11 | -18.0 |
February | 0.388860E+10 | 14968.81 | 06-FEB-02:62 | -17.9 |
March | 0.205628E+10 | 15117.78 | 06-MAR-05:11 | -15.2 |
April | 0.576959E+09 | 14152.47 | 03-APR-04:11 | -6.9 |
May | 10562564.95 | 9058.81 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 38822506.92 | 12034.85 | 30-SEP-05:01 | 0.10 |
October | 0.265041E+09 | 12572.55 | 23-OCT-05:01 | -2.7 |
November | 0.262185E+10 | 14932.88 | 26-NOV-02:52 | -25.0 |
December | 0.577092E+10 | 15051.00 | 09-DEC-21:22 | -20.0 |
Annual Sum or Average | 0.223214E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.709241E+10 | 15117.78 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.624466E+10 | 13531.30 | 23-JAN-05:11 | -18.0 |
February | 0.356378E+10 | 13443.64 | 02-FEB-01:02 | -34.0 |
March | 0.166984E+10 | 13567.71 | 06-MAR-05:11 | -15.2 |
April | 0.398607E+09 | 12654.81 | 03-APR-04:11 | -6.9 |
May | 7935909.16 | 6011.20 | 02-MAY-05:12 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 36671855.33 | 10853.38 | 30-SEP-05:01 | 0.10 |
October | 0.247420E+09 | 11286.28 | 23-OCT-05:01 | -2.7 |
November | 0.226849E+10 | 13455.10 | 26-NOV-02:52 | -25.0 |
December | 0.476961E+10 | 13454.13 | 09-DEC-21:22 | -20.0 |
Annual Sum or Average | 0.192070E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.0 | |
Maximum of Months | 0.624466E+10 | 13567.71 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720439E+10 | 7990.77 | 30-JAN-05:11 | -28.0 |
February | 0.465388E+10 | 7886.76 | 02-FEB-01:02 | -34.0 |
March | 0.237702E+10 | 7768.46 | 06-MAR-03:33 | -16.3 |
April | 0.634887E+09 | 7540.37 | 03-APR-04:01 | -6.8 |
May | 8912752.10 | 6091.24 | 01-MAY-06:03 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 1238963.45 | 4452.68 | 30-SEP-06:03 | 0.60 |
October | 24519479.82 | 6132.81 | 16-OCT-06:02 | -0.4 |
November | 0.173006E+10 | 7732.95 | 26-NOV-18:52 | -13.3 |
December | 0.461187E+10 | 7849.81 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.212468E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.0 | |
Maximum of Months | 0.720439E+10 | 7990.77 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423243E+10 | 9592.60 | 30-JAN-05:11 | -28.0 |
February | 0.242701E+10 | 9431.42 | 02-FEB-05:01 | -36.2 |
March | 0.107897E+10 | 9155.52 | 13-MAR-04:01 | -9.4 |
April | 0.262008E+09 | 9048.17 | 03-APR-04:01 | -6.8 |
May | 293163.47 | 1954.42 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4684.08 | 31.23 | 30-SEP-06:03 | 0.60 |
October | 5580180.17 | 5847.75 | 27-OCT-06:02 | 0.25 |
November | 0.963610E+09 | 9125.99 | 28-NOV-05:01 | -21.1 |
December | 0.270511E+10 | 9413.25 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.116750E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.2 | |
Maximum of Months | 0.423243E+10 | 9592.60 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.962151E+10 | 15581.86 | 31-JAN-07:10 | -30.5 |
February | 0.625869E+10 | 17036.58 | 02-FEB-07:10 | -36.7 |
March | 0.475073E+10 | 12775.07 | 06-MAR-08:00 | -12.2 |
April | 0.222776E+10 | 11984.57 | 03-APR-07:00 | -6.7 |
May | 0.551753E+09 | 9839.59 | 02-MAY-06:10 | 2.30 |
June | 0.172890E+09 | 8579.30 | 02-JUN-06:20 | 7.40 |
July | 1582559.20 | 3384.15 | 24-JUL-06:07 | 12.35 |
August | 22187557.58 | 7750.17 | 16-AUG-06:05 | 9.97 |
September | 0.369832E+09 | 9874.69 | 29-SEP-06:10 | 0.10 |
October | 0.103243E+10 | 10282.08 | 23-OCT-06:10 | -3.0 |
November | 0.365840E+10 | 13368.46 | 28-NOV-08:00 | -16.7 |
December | 0.720645E+10 | 14294.38 | 11-DEC-08:00 | -21.7 |
Annual Sum or Average | 0.358742E+11 | |||
Minimum of Months | 1582559.20 | 3384.15 | -36.7 | |
Maximum of Months | 0.962151E+10 | 17036.58 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435577E+10 | 10162.58 | 30-JAN-05:11 | -28.0 |
February | 0.247935E+10 | 9996.83 | 02-FEB-05:01 | -36.2 |
March | 0.120628E+10 | 9685.47 | 13-MAR-04:01 | -9.4 |
April | 0.230333E+09 | 9641.05 | 03-APR-04:01 | -6.8 |
May | 2944735.65 | 5361.61 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 850504.57 | 2963.15 | 30-SEP-06:03 | 0.60 |
October | 6031748.35 | 6597.38 | 16-OCT-06:02 | -0.4 |
November | 0.997235E+09 | 9703.50 | 28-NOV-05:01 | -21.1 |
December | 0.276464E+10 | 9992.75 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.120434E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.2 | |
Maximum of Months | 0.435577E+10 | 10162.58 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692621E+10 | 9033.75 | 30-JAN-05:21 | -28.1 |
February | 0.384456E+10 | 8776.48 | 06-FEB-02:62 | -17.9 |
March | 0.150980E+10 | 8508.33 | 06-MAR-05:01 | -15.4 |
April | 0.266711E+09 | 8210.52 | 03-APR-04:01 | -6.8 |
May | 882437.16 | 4954.88 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4651583.61 | 6565.90 | 30-SEP-06:03 | 0.60 |
October | 60881614.45 | 7011.61 | 16-OCT-05:01 | 0.48 |
November | 0.211263E+10 | 8488.96 | 26-NOV-04:01 | -25.0 |
December | 0.483760E+10 | 8649.46 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.195639E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.692621E+10 | 9033.75 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404445E+10 | 12022.85 | 30-JAN-05:21 | -28.1 |
February | 0.205611E+10 | 11810.48 | 06-FEB-02:62 | -17.9 |
March | 0.770552E+09 | 11533.52 | 06-MAR-05:01 | -15.4 |
April | 0.138181E+09 | 11096.19 | 03-APR-04:01 | -6.8 |
May | 73318.50 | 488.79 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2357051.71 | 5392.56 | 30-SEP-06:03 | 0.60 |
October | 33422968.08 | 8974.75 | 16-OCT-05:01 | 0.48 |
November | 0.124446E+10 | 11447.51 | 26-NOV-04:01 | -25.0 |
December | 0.290751E+10 | 11768.55 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.111971E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.404445E+10 | 12022.85 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438139E+10 | 13434.06 | 30-JAN-05:21 | -28.1 |
February | 0.212116E+10 | 13211.99 | 06-FEB-02:42 | -16.5 |
March | 0.983631E+09 | 12937.09 | 06-MAR-05:01 | -15.4 |
April | 0.198862E+09 | 12529.27 | 03-APR-04:01 | -6.8 |
May | 789403.26 | 4521.10 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 3320462.17 | 7824.98 | 30-SEP-06:03 | 0.60 |
October | 36212850.86 | 10566.21 | 16-OCT-05:01 | 0.48 |
November | 0.136409E+10 | 12894.54 | 27-NOV-01:22 | -11.4 |
December | 0.345989E+10 | 13213.54 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.125493E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.438139E+10 | 13434.06 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419443E+10 | 12363.97 | 30-JAN-05:21 | -28.1 |
February | 0.218024E+10 | 12106.64 | 06-FEB-02:62 | -17.9 |
March | 0.852336E+09 | 11848.24 | 06-MAR-05:01 | -15.4 |
April | 0.136894E+09 | 11416.45 | 03-APR-04:01 | -6.8 |
May | 752685.74 | 3629.80 | 02-MAY-06:03 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 3956312.14 | 5493.21 | 30-SEP-06:03 | 0.60 |
October | 38269175.26 | 9752.94 | 16-OCT-05:01 | 0.48 |
November | 0.128928E+10 | 11770.13 | 26-NOV-04:01 | -25.0 |
December | 0.300171E+10 | 12120.90 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.116979E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.1 | |
Maximum of Months | 0.419443E+10 | 12363.97 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462778E+09 | 735.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.389377E+09 | 608.76 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.427110E+09 | 504.22 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370888E+09 | 411.85 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.385196E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380777E+09 | 394.55 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359319E+09 | 395.04 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.402254E+09 | 377.95 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.377026E+09 | 412.02 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.412223E+09 | 706.71 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.449430E+09 | 735.45 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.473039E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.488942E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359319E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.473039E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.287481E+09 | 465.60 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243700E+09 | 391.42 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269748E+09 | 329.44 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234790E+09 | 253.81 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245519E+09 | 241.14 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242432E+09 | 241.85 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.228489E+09 | 242.17 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255798E+09 | 222.09 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238831E+09 | 254.10 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.257949E+09 | 409.34 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281002E+09 | 465.60 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.291691E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307743E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.228489E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.291691E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.444394E+09 | 735.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.378055E+09 | 587.89 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.424222E+09 | 413.01 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370753E+09 | 411.01 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.387523E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383060E+09 | 396.73 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360930E+09 | 397.36 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.404084E+09 | 371.35 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.375955E+09 | 409.46 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.403808E+09 | 663.25 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.436235E+09 | 735.45 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.448325E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.481734E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360930E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.448325E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285908E+09 | 465.57 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242201E+09 | 361.89 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269287E+09 | 315.38 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234452E+09 | 306.55 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.243983E+09 | 235.87 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241046E+09 | 253.98 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227629E+09 | 254.91 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.254784E+09 | 247.98 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237575E+09 | 311.97 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259304E+09 | 448.68 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279072E+09 | 465.57 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.290192E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306543E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227629E+09 | 235.87 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.290192E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.460811E+09 | 735.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.388134E+09 | 602.19 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.426278E+09 | 495.23 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370168E+09 | 409.89 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.384861E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380548E+09 | 391.75 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359132E+09 | 392.27 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.402003E+09 | 374.39 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.376502E+09 | 410.07 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.411156E+09 | 705.40 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.447817E+09 | 735.45 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.470409E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.487782E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359132E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.470409E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.286739E+09 | 465.60 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242993E+09 | 388.04 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269346E+09 | 325.23 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234542E+09 | 252.27 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245333E+09 | 239.59 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242286E+09 | 239.81 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.228324E+09 | 240.26 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255607E+09 | 222.09 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238588E+09 | 252.69 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.257563E+09 | 406.47 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.280485E+09 | 465.60 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.290602E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307241E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.228324E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.290602E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.443652E+09 | 735.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.377666E+09 | 581.97 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.423828E+09 | 411.06 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370274E+09 | 409.00 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.387121E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.382717E+09 | 394.06 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360647E+09 | 394.72 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.403660E+09 | 350.81 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.375546E+09 | 407.36 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.403463E+09 | 659.73 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.435591E+09 | 735.45 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.447172E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.481134E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360647E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.447172E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285222E+09 | 465.57 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.241709E+09 | 358.33 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269018E+09 | 308.92 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234069E+09 | 301.71 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.243792E+09 | 222.08 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240812E+09 | 252.56 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227505E+09 | 253.54 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.254587E+09 | 246.35 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237260E+09 | 307.28 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.258763E+09 | 448.04 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.278454E+09 | 465.57 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.289198E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306039E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227505E+09 | 222.08 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.289198E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462776E+09 | 735.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.389376E+09 | 608.76 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.427109E+09 | 504.20 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370888E+09 | 411.85 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.385196E+09 | 350.81 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.380777E+09 | 394.54 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.359318E+09 | 395.03 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.402254E+09 | 377.94 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.377025E+09 | 412.02 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.412223E+09 | 706.71 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.449428E+09 | 735.45 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.473036E+09 | 735.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.488941E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.359318E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.473036E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.287480E+09 | 465.60 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.243700E+09 | 391.42 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269748E+09 | 329.43 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234790E+09 | 253.80 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.245519E+09 | 241.13 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.242432E+09 | 241.85 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.228489E+09 | 242.16 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255797E+09 | 222.09 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.238831E+09 | 254.09 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.257949E+09 | 409.34 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.281001E+09 | 465.60 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.291682E+09 | 465.60 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.307742E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.228489E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.291682E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.444393E+09 | 735.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.378055E+09 | 587.88 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.424222E+09 | 413.01 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370753E+09 | 411.01 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.387522E+09 | 350.81 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.383060E+09 | 396.73 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360929E+09 | 397.36 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.404084E+09 | 371.34 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.375954E+09 | 409.46 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.403808E+09 | 663.25 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.436234E+09 | 735.45 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.448357E+09 | 735.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.481737E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360929E+09 | 350.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.448357E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.285908E+09 | 465.57 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.242200E+09 | 361.89 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.269286E+09 | 315.39 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234452E+09 | 306.53 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.243983E+09 | 235.86 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241046E+09 | 253.97 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227629E+09 | 254.90 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.254784E+09 | 247.97 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.237575E+09 | 311.95 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.259304E+09 | 448.68 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.279071E+09 | 465.57 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.290190E+09 | 465.57 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.306543E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227629E+09 | 235.86 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.290190E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.462778E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286033E+10 |
February | 0.901968E+09 | 0.389377E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208946E+10 |
March | 0.107774E+10 | 0.427110E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178660E+10 |
April | 0.956342E+09 | 0.370888E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10119501.32 | 0.112076E+10 |
May | 0.103597E+10 | 0.385196E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3524667.83 | 0.645565E+09 |
June | 0.103308E+10 | 0.380777E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45467349.92 | 0.376969E+09 |
July | 0.959235E+09 | 0.359319E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15717106.02 | 0.276034E+09 |
August | 0.107774E+10 | 0.402254E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17470600.19 | 0.370460E+09 |
September | 0.956342E+09 | 0.377026E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13717522.92 | 0.575461E+09 |
October | 0.994195E+09 | 0.412223E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106163E+10 |
November | 0.984487E+09 | 0.449430E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177222E+10 |
December | 0.959235E+09 | 0.473039E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239012E+10 |
Annual Sum or Average | 0.119305E+11 | 0.488942E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106017E+09 | 0.153256E+11 |
Minimum of Months | 0.901968E+09 | 0.359319E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276034E+09 |
Maximum of Months | 0.107774E+10 | 0.473039E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45467349.92 | 0.286033E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.287481E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191146E+10 |
February | 0.571020E+09 | 0.243700E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139831E+10 |
March | 0.682301E+09 | 0.269748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120716E+10 |
April | 0.605444E+09 | 0.234790E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6004341.87 | 0.773511E+09 |
May | 0.655854E+09 | 0.245519E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2349555.43 | 0.446480E+09 |
June | 0.654023E+09 | 0.242432E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28771436.65 | 0.257531E+09 |
July | 0.607275E+09 | 0.228489E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9724456.32 | 0.190697E+09 |
August | 0.682301E+09 | 0.255798E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11369960.14 | 0.253676E+09 |
September | 0.605444E+09 | 0.238831E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7754137.35 | 0.401275E+09 |
October | 0.629407E+09 | 0.257949E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735372E+09 |
November | 0.623262E+09 | 0.281002E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118887E+10 |
December | 0.607275E+09 | 0.291691E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159868E+10 |
Annual Sum or Average | 0.755301E+10 | 0.307743E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65973887.76 | 0.103630E+11 |
Minimum of Months | 0.571020E+09 | 0.228489E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190697E+09 |
Maximum of Months | 0.682301E+09 | 0.291691E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28771436.65 | 0.191146E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.444394E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289239E+10 |
February | 0.901968E+09 | 0.378055E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214073E+10 |
March | 0.107774E+10 | 0.424222E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185451E+10 |
April | 0.956342E+09 | 0.370753E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8102582.10 | 0.117625E+10 |
May | 0.103597E+10 | 0.387523E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3524558.81 | 0.664485E+09 |
June | 0.103308E+10 | 0.383060E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43575446.76 | 0.379537E+09 |
July | 0.959235E+09 | 0.360930E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14569091.09 | 0.281221E+09 |
August | 0.107774E+10 | 0.404084E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16984965.39 | 0.386173E+09 |
September | 0.956342E+09 | 0.375955E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10981803.94 | 0.617668E+09 |
October | 0.994195E+09 | 0.403808E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116061E+10 |
November | 0.984487E+09 | 0.436235E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182705E+10 |
December | 0.959235E+09 | 0.448325E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244475E+10 |
Annual Sum or Average | 0.119305E+11 | 0.481734E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97738448.10 | 0.158254E+11 |
Minimum of Months | 0.901968E+09 | 0.360930E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281221E+09 |
Maximum of Months | 0.107774E+10 | 0.448325E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43575446.76 | 0.289239E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.285908E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191270E+10 |
February | 0.570983E+09 | 0.242201E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140536E+10 |
March | 0.682256E+09 | 0.269287E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120984E+10 |
April | 0.605404E+09 | 0.234452E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4989063.90 | 0.782712E+09 |
May | 0.655811E+09 | 0.243983E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2349893.90 | 0.448671E+09 |
June | 0.653980E+09 | 0.241046E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28116997.05 | 0.258962E+09 |
July | 0.607235E+09 | 0.227629E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9640947.54 | 0.196592E+09 |
August | 0.682256E+09 | 0.254784E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11398056.42 | 0.261687E+09 |
September | 0.605404E+09 | 0.237575E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7394160.21 | 0.404664E+09 |
October | 0.629366E+09 | 0.259304E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731672E+09 |
November | 0.623221E+09 | 0.279072E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119047E+10 |
December | 0.607235E+09 | 0.290192E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159983E+10 |
Annual Sum or Average | 0.755252E+10 | 0.306543E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63889119.03 | 0.104031E+11 |
Minimum of Months | 0.570983E+09 | 0.227629E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196592E+09 |
Maximum of Months | 0.682256E+09 | 0.290192E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28116997.05 | 0.191270E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.460811E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153826E+10 |
February | 0.901968E+09 | 0.388134E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113650E+10 |
March | 0.107774E+10 | 0.426278E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963398E+09 |
April | 0.956342E+09 | 0.370168E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10081515.97 | 0.588494E+09 |
May | 0.103597E+10 | 0.384861E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2036378.82 | 0.325918E+09 |
June | 0.103308E+10 | 0.380548E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30221402.72 | 0.195557E+09 |
July | 0.959235E+09 | 0.359132E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10702231.84 | 0.142156E+09 |
August | 0.107774E+10 | 0.402003E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10048914.45 | 0.200567E+09 |
September | 0.956342E+09 | 0.376502E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8647095.00 | 0.326016E+09 |
October | 0.994195E+09 | 0.411156E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628959E+09 |
November | 0.984487E+09 | 0.447817E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100833E+10 |
December | 0.959235E+09 | 0.470409E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131266E+10 |
Annual Sum or Average | 0.119305E+11 | 0.487782E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71737538.81 | 0.836683E+10 |
Minimum of Months | 0.901968E+09 | 0.359132E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142156E+09 |
Maximum of Months | 0.107774E+10 | 0.470409E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30221402.72 | 0.153826E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.286739E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102890E+10 |
February | 0.571020E+09 | 0.242993E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763423E+09 |
March | 0.682301E+09 | 0.269346E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655324E+09 |
April | 0.605444E+09 | 0.234542E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4947305.50 | 0.413291E+09 |
May | 0.655854E+09 | 0.245333E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1275555.51 | 0.237307E+09 |
June | 0.654023E+09 | 0.242286E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16718010.90 | 0.138829E+09 |
July | 0.607275E+09 | 0.228324E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5550518.14 | 0.102993E+09 |
August | 0.682301E+09 | 0.255607E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6249945.37 | 0.141471E+09 |
September | 0.605444E+09 | 0.238588E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4343965.92 | 0.232643E+09 |
October | 0.629407E+09 | 0.257563E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442964E+09 |
November | 0.623262E+09 | 0.280485E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678595E+09 |
December | 0.607275E+09 | 0.290602E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878549E+09 |
Annual Sum or Average | 0.755301E+10 | 0.307241E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39085301.33 | 0.571429E+10 |
Minimum of Months | 0.571020E+09 | 0.228324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102993E+09 |
Maximum of Months | 0.682301E+09 | 0.290602E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16718010.90 | 0.102890E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.443652E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100034E+11 |
February | 0.901968E+09 | 0.377666E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758468E+10 |
March | 0.107774E+10 | 0.423828E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655257E+10 |
April | 0.956342E+09 | 0.370274E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24441510.09 | 0.408283E+10 |
May | 0.103597E+10 | 0.387121E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68344377.03 | 0.225837E+10 |
June | 0.103308E+10 | 0.382717E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274923E+09 | 0.124334E+10 |
July | 0.959235E+09 | 0.360647E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233779E+09 | 0.629060E+09 |
August | 0.107774E+10 | 0.403660E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329073E+09 | 0.938445E+09 |
September | 0.956342E+09 | 0.375546E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172955E+09 | 0.208999E+10 |
October | 0.994195E+09 | 0.403463E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411726E+10 |
November | 0.984487E+09 | 0.435591E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579996E+10 |
December | 0.959235E+09 | 0.447172E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800492E+10 |
Annual Sum or Average | 0.119305E+11 | 0.481134E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110351E+10 | 0.533049E+11 |
Minimum of Months | 0.901968E+09 | 0.360647E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629060E+09 |
Maximum of Months | 0.107774E+10 | 0.447172E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329073E+09 | 0.100034E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.285222E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102925E+10 |
February | 0.570983E+09 | 0.241709E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766630E+09 |
March | 0.682256E+09 | 0.269018E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656606E+09 |
April | 0.605404E+09 | 0.234069E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3199983.00 | 0.422301E+09 |
May | 0.655811E+09 | 0.243792E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1284152.61 | 0.237339E+09 |
June | 0.653980E+09 | 0.240812E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16286218.82 | 0.139721E+09 |
July | 0.607235E+09 | 0.227505E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5495972.62 | 0.108589E+09 |
August | 0.682256E+09 | 0.254587E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6222077.95 | 0.147811E+09 |
September | 0.605404E+09 | 0.237260E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4028261.69 | 0.235116E+09 |
October | 0.629366E+09 | 0.258763E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440298E+09 |
November | 0.623221E+09 | 0.278454E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680124E+09 |
December | 0.607235E+09 | 0.289198E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879200E+09 |
Annual Sum or Average | 0.755252E+10 | 0.306039E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36516666.68 | 0.574298E+10 |
Minimum of Months | 0.570983E+09 | 0.227505E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108589E+09 |
Maximum of Months | 0.682256E+09 | 0.289198E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16286218.82 | 0.102925E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.462776E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240257E+10 |
February | 0.901968E+09 | 0.389376E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178013E+10 |
March | 0.107774E+10 | 0.427109E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154061E+10 |
April | 0.956342E+09 | 0.370888E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9477204.41 | 0.979759E+09 |
May | 0.103597E+10 | 0.385196E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2964539.34 | 0.557368E+09 |
June | 0.103308E+10 | 0.380777E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38856065.43 | 0.326370E+09 |
July | 0.959235E+09 | 0.359318E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13556882.42 | 0.237159E+09 |
August | 0.107774E+10 | 0.402254E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14870713.45 | 0.320380E+09 |
September | 0.956342E+09 | 0.377025E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11610525.97 | 0.508881E+09 |
October | 0.994195E+09 | 0.412223E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961564E+09 |
November | 0.984487E+09 | 0.449428E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154101E+10 |
December | 0.959235E+09 | 0.473036E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203349E+10 |
Annual Sum or Average | 0.119305E+11 | 0.488941E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91335931.02 | 0.131893E+11 |
Minimum of Months | 0.901968E+09 | 0.359318E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237159E+09 |
Maximum of Months | 0.107774E+10 | 0.473036E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38856065.43 | 0.240257E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.287480E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160313E+10 |
February | 0.421807E+09 | 0.243700E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119171E+10 |
March | 0.502994E+09 | 0.269748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104427E+10 |
April | 0.447140E+09 | 0.234790E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5231411.73 | 0.675489E+09 |
May | 0.484071E+09 | 0.245519E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1896120.97 | 0.384497E+09 |
June | 0.482240E+09 | 0.242432E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24368804.06 | 0.223054E+09 |
July | 0.448971E+09 | 0.228489E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8002832.70 | 0.163707E+09 |
August | 0.502994E+09 | 0.255797E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9125961.61 | 0.219169E+09 |
September | 0.447140E+09 | 0.238831E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6376370.84 | 0.352639E+09 |
October | 0.465148E+09 | 0.257949E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665401E+09 |
November | 0.460569E+09 | 0.281001E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103291E+10 |
December | 0.448971E+09 | 0.291682E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135761E+10 |
Annual Sum or Average | 0.557719E+10 | 0.307742E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55001501.91 | 0.891357E+10 |
Minimum of Months | 0.421807E+09 | 0.228489E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163707E+09 |
Maximum of Months | 0.502994E+09 | 0.291682E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24368804.06 | 0.160313E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.444393E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244294E+10 |
February | 0.901968E+09 | 0.378055E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183409E+10 |
March | 0.107774E+10 | 0.424222E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160413E+10 |
April | 0.956342E+09 | 0.370753E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7134490.57 | 0.102549E+10 |
May | 0.103597E+10 | 0.387522E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2964188.65 | 0.571732E+09 |
June | 0.103308E+10 | 0.383060E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37434302.72 | 0.327989E+09 |
July | 0.959235E+09 | 0.360929E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12462769.35 | 0.241246E+09 |
August | 0.107774E+10 | 0.404084E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14290924.85 | 0.332915E+09 |
September | 0.956342E+09 | 0.375954E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9225450.59 | 0.541061E+09 |
October | 0.994195E+09 | 0.403808E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103988E+10 |
November | 0.984487E+09 | 0.436234E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159330E+10 |
December | 0.959235E+09 | 0.448357E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208947E+10 |
Annual Sum or Average | 0.119305E+11 | 0.481737E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83512126.72 | 0.136442E+11 |
Minimum of Months | 0.901968E+09 | 0.360929E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241246E+09 |
Maximum of Months | 0.107774E+10 | 0.448357E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37434302.72 | 0.244294E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.285908E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160547E+10 |
February | 0.570983E+09 | 0.242200E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119782E+10 |
March | 0.682256E+09 | 0.269286E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104375E+10 |
April | 0.605404E+09 | 0.234452E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4261667.26 | 0.681997E+09 |
May | 0.655811E+09 | 0.243983E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1976441.49 | 0.386225E+09 |
June | 0.653980E+09 | 0.241046E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23880421.85 | 0.223826E+09 |
July | 0.607235E+09 | 0.227629E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8148014.44 | 0.168813E+09 |
August | 0.682256E+09 | 0.254784E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9598763.81 | 0.225635E+09 |
September | 0.605404E+09 | 0.237575E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6199157.65 | 0.355541E+09 |
October | 0.629366E+09 | 0.259304E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659749E+09 |
November | 0.623221E+09 | 0.279071E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103471E+10 |
December | 0.607235E+09 | 0.290190E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136028E+10 |
Annual Sum or Average | 0.755252E+10 | 0.306543E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54064466.49 | 0.894381E+10 |
Minimum of Months | 0.570983E+09 | 0.227629E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168813E+09 |
Maximum of Months | 0.682256E+09 | 0.290190E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23880421.85 | 0.160547E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319596E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240943E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211215E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13196825.17 | 0.135752E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2873442.45 | 0.753612E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51853242.30 | 0.434676E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14905657.30 | 0.315417E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14468669.44 | 0.437440E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11697308.76 | 0.712144E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137951E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214239E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275323E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108995E+09 | 0.180035E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315417E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51853242.30 | 0.319596E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402327E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302247E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264721E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15124704.00 | 0.170672E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3635711.13 | 0.970174E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63580075.17 | 0.559407E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17997969.71 | 0.407720E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18666474.16 | 0.558153E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15778838.64 | 0.890095E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167378E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263111E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343718E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134784E+09 | 0.225273E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407720E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63580075.17 | 0.402327E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420615E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313005E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273348E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6935258.10 | 0.175745E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2693133.60 | 0.102454E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42455454.67 | 0.579226E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9040394.82 | 0.431166E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14625753.76 | 0.582441E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10224609.01 | 0.904331E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166406E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266613E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353925E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85974603.96 | 0.232183E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431166E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42455454.67 | 0.420615E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5599.65 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 608.76 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3916.29 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 504.22 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2977.18 | 20-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 411.85 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.56 | 15-APR-17:01 | 2238.36 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1491.39 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 394.55 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 573.31 | 11-JUN-15:24 | 1245.80 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 395.04 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.11 | 02-JUL-15:27 | 571.37 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 377.95 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 749.15 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 412.02 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.58 | 17-SEP-14:40 | 1130.72 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 706.71 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1533.20 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4289.90 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.10 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.37 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 573.31 | 6589.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3745.93 | 29-JAN-11:00 |
February | 827.22 | 01-FEB-10:09 | 391.42 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2608.99 | 10-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 329.44 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2007.63 | 06-MAR-06:00 |
April | 827.22 | 03-APR-09:09 | 253.81 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.97 | 15-APR-17:01 | 1492.23 | 02-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 241.14 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 1004.71 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 241.85 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.35 | 18-JUN-16:14 | 832.37 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 242.17 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.07 | 02-JUL-15:25 | 393.49 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 222.09 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 04-AUG-16:40 | 511.15 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 254.10 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 | 06-SEP-16:00 | 754.64 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 409.34 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1025.80 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2858.08 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.23 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.49 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 387.35 | 4393.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5644.25 | 29-JAN-10:53 |
February | 1306.65 | 01-FEB-10:09 | 587.89 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3918.39 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 413.01 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 3181.44 | 05-MAR-13:53 |
April | 1306.65 | 03-APR-09:09 | 411.01 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.27 | 15-APR-17:01 | 2238.36 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1516.44 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 396.73 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.82 | 11-JUN-15:24 | 1251.48 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 397.36 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.74 | 02-JUL-15:25 | 578.06 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 371.35 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 802.82 | 06-AUG-14:00 |
September | 1306.65 | 01-SEP-09:09 | 409.46 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 06-SEP-16:00 | 1141.56 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 663.25 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1586.29 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4293.19 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.89 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.06 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 576.82 | 6589.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3745.93 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 361.89 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2608.43 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 315.38 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2007.63 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 306.55 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.12 | 15-APR-17:09 | 1492.23 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 235.87 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 | 31-MAY-13:00 | 1002.14 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 253.98 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.43 | 11-JUN-14:53 | 825.31 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 254.91 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.50 | 02-JUL-14:44 | 398.29 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 247.98 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 04-AUG-16:40 | 512.95 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 311.97 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 | 06-SEP-16:00 | 801.77 | 24-SEP-16:25 |
October | 827.17 | 02-OCT-09:09 | 448.68 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1030.20 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2857.89 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.23 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 235.87 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.29 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 378.43 | 4393.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2983.42 | 29-JAN-10:53 |
February | 1306.65 | 01-FEB-10:09 | 602.19 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2091.75 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 495.23 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1598.59 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 409.89 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.15 | 15-APR-17:01 | 1201.93 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 31-MAY-13:00 | 798.54 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 391.75 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.14 | 18-JUN-15:52 | 712.57 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 392.27 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.02 | 02-JUL-15:40 | 295.54 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 374.39 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 04-AUG-16:40 | 416.27 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 410.07 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.75 | 17-SEP-15:00 | 654.85 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 705.40 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 962.49 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2294.32 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3478.30 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.54 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 381.15 | 3478.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1988.94 | 29-JAN-10:51 |
February | 827.22 | 01-FEB-10:09 | 388.04 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1394.46 | 10-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 325.23 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1078.34 | 05-MAR-09:53 |
April | 827.22 | 03-APR-09:09 | 252.27 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.10 | 15-APR-17:01 | 799.97 | 02-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 239.59 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 561.31 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 239.81 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.86 | 11-JUN-14:58 | 491.76 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 240.26 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 02-JUL-15:40 | 206.85 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 222.09 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 04-AUG-16:40 | 287.31 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 252.69 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 17-SEP-15:00 | 448.21 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 406.47 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 660.24 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1529.09 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2317.33 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.85 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 219.10 | 2317.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 44682.39 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 581.97 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 51478.20 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 411.06 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 28075.89 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 409.00 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2940.97 | 18-APR-12:00 | 23236.51 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4129.69 | 31-MAY-12:00 | 14741.83 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 394.06 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5832.04 | 26-JUN-16:10 | 11241.95 | 02-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 394.72 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4480.40 | 26-JUL-16:10 | 8156.69 | 24-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 350.81 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6597.27 | 04-AUG-16:05 | 11110.55 | 07-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 407.36 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5283.90 | 07-SEP-16:05 | 16528.92 | 29-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 659.73 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19507.10 | 23-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32399.98 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 36388.24 | 11-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8156.69 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6597.27 | 51478.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1988.94 | 29-JAN-10:51 |
February | 827.17 | 01-FEB-10:09 | 358.33 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1394.18 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 308.92 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1065.72 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 301.71 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.23 | 15-APR-17:06 | 795.10 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 222.08 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 548.30 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 252.56 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.58 | 11-JUN-14:55 | 479.60 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 253.54 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.31 | 02-JUL-15:23 | 217.21 | 09-JUL-10:00 |
August | 827.17 | 01-AUG-09:09 | 246.35 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 04-AUG-16:40 | 297.77 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 307.28 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.30 | 17-SEP-14:56 | 448.04 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 448.04 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 660.27 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1529.13 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2316.78 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.21 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 207.58 | 2316.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4674.09 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 608.76 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3273.09 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 504.20 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2504.77 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 411.85 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.48 | 15-APR-17:01 | 1843.18 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1313.99 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 394.54 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.96 | 11-JUN-15:14 | 1118.92 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 395.03 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.49 | 02-JUL-16:00 | 485.42 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 377.94 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 654.02 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 412.02 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.75 | 17-SEP-15:00 | 995.19 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 706.71 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1430.89 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3582.52 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5481.84 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.42 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 475.96 | 5481.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3116.06 | 29-JAN-10:51 |
February | 805.43 | 01-FEB-08:09 | 391.42 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2180.68 | 10-FEB-22:02 |
March | 805.43 | 01-MAR-08:09 | 329.43 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1737.84 | 05-MAR-09:53 |
April | 805.43 | 03-APR-07:10 | 253.80 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.31 | 15-APR-17:01 | 1222.53 | 02-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 241.13 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 883.89 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 241.85 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.31 | 11-JUN-15:14 | 747.60 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 242.16 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.54 | 02-JUL-15:53 | 347.21 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 222.09 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 04-AUG-16:40 | 446.13 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 254.09 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.40 | 10-SEP-15:00 | 664.24 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 409.34 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 957.69 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2386.95 | 20-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3654.54 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.21 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 329.31 | 3654.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4813.94 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 587.88 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3274.79 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 413.01 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2792.64 | 05-MAR-13:53 |
April | 1306.65 | 03-APR-09:09 | 411.01 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.26 | 15-APR-17:01 | 1852.00 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 350.81 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1333.29 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 396.73 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 474.37 | 11-JUN-15:14 | 1123.47 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 397.36 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.29 | 02-JUL-15:53 | 498.48 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 371.34 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 665.28 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 409.46 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.73 | 10-SEP-14:58 | 1004.61 | 24-SEP-13:30 |
October | 1306.65 | 02-OCT-09:09 | 663.25 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1475.22 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.58 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5481.84 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.48 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 474.37 | 5481.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3116.04 | 29-JAN-10:53 |
February | 827.17 | 01-FEB-10:09 | 361.89 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2180.34 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 315.39 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1669.85 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 306.53 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.51 | 15-APR-17:06 | 1219.60 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 235.86 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 881.95 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 253.97 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.25 | 11-JUN-14:53 | 741.39 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 254.90 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.51 | 02-JUL-15:53 | 338.12 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 247.97 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 04-AUG-16:40 | 447.58 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 311.95 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 | 10-SEP-14:55 | 669.58 | 24-SEP-16:20 |
October | 827.17 | 02-OCT-09:09 | 448.68 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 960.32 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2386.95 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3654.54 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 235.86 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.12 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 316.25 | 3654.54 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6136.30 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4317.19 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 3459.29 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.74 | 15-APR-17:01 | 2729.87 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.26 | 31-MAY-13:00 | 1837.36 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.61 | 11-JUN-15:00 | 1581.23 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.44 | 02-JUL-15:10 | 631.32 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.77 | 04-AUG-16:40 | 867.75 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.78 | 17-SEP-14:42 | 1389.28 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2127.91 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4530.43 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7448.95 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.32 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.61 | 7448.95 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7655.75 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5452.38 | 04-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4386.45 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.37 | 15-APR-17:01 | 3283.82 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.24 | 31-MAY-13:00 | 2344.63 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.70 | 11-JUN-15:00 | 1996.62 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.82 | 02-JUL-15:00 | 810.08 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.49 | 04-AUG-16:40 | 1102.95 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.81 | 17-SEP-14:42 | 1762.71 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2578.74 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5662.80 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9304.96 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 828.70 | 9304.96 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8027.42 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5669.15 | 10-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 4495.39 | 20-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.57 | 15-APR-17:01 | 3273.13 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 | 31-MAY-13:00 | 2288.68 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.19 | 18-JUN-16:00 | 1915.13 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.13 | 25-JUL-21:03 | 874.06 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.54 | 04-AUG-16:30 | 1148.75 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.67 | 06-SEP-16:00 | 1723.21 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2333.50 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6182.98 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9436.77 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.06 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.19 | 9436.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5903.12 | 13-JAN-17:00 | 12070.02 | 6977.40 | 21549.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7638.28 | 02-FEB-09:00 | 18105.02 | 10466.10 | 38274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10208.16 | 24-MAR-16:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16778.03 | 17-APR-06:02 | 6352.64 | 5814.50 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32007.79 | 30-MAY-06:03 | 5082.11 | 4651.60 | 24176.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33923.16 | 12-JUN-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33996.61 | 05-JUL-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32323.44 | 07-AUG-06:01 | 8893.70 | 8140.30 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33917.41 | 11-SEP-05:12 | 2541.06 | 1550.53 | 16192.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14686.24 | 06-OCT-07:05 | 24140.03 | 13954.80 | 51033.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13844.87 | 07-NOV-08:10 | 12070.02 | 6977.40 | 25516.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6024.29 | 07-DEC-16:35 | 12070.02 | 6977.40 | 21549.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5903.12 | 2541.06 | 1550.53 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33996.61 | 24140.03 | 13954.80 | 51033.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1332.65 |
February | 266.90 | 24-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.88 |
March | 1643.42 | 24-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.57 |
April | 7824.60 | 18-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.24 | 0.00 |
May | 8763.58 | 31-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.49 | 0.00 |
June | 10231.18 | 26-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 | 0.00 |
July | 9675.85 | 05-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 0.00 |
August | 9836.69 | 04-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 0.00 |
September | 8756.50 | 07-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.53 | 0.00 |
October | 3447.35 | 20-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.70 |
November | 1602.29 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.72 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1798.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10231.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 1798.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3489.35 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.37 |
February | 3027.08 | 02-FEB-01:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4402.52 |
March | 2339.66 | 21-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920.17 |
April | 3238.40 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 |
May | 3756.16 | 30-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 | 0.00 |
June | 5202.54 | 12-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.51 |
July | 6064.11 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 |
August | 4120.86 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.27 | 0.00 |
September | 4067.93 | 11-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.90 | 0.00 |
October | 1646.74 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.25 |
November | 2536.18 | 25-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3127.52 |
December | 2841.87 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1646.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6064.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.27 | 4402.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2933.49 | 07-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1501.61 |
February | 3125.79 | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.82 |
March | 2832.46 | 11-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.57 |
April | 2826.87 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.22 | 0.00 |
May | 3370.91 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 0.00 |
June | 5191.23 | 26-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.24 | 0.00 |
July | 5633.67 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.30 |
August | 4050.03 | 04-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.11 | 0.00 |
September | 4320.54 | 11-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | 0.00 |
October | 1935.06 | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.76 |
November | 2411.15 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.93 |
December | 2194.45 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1935.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5633.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.11 | 1501.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5296.65 | 13-JAN-17:00 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5455.39 | 24-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6803.11 | 24-MAR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19061.82 | 17-APR-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26375.03 | 30-MAY-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28528.34 | 12-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28430.79 | 03-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26405.52 | 14-AUG-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29185.67 | 11-SEP-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8937.32 | 03-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8658.47 | 03-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5148.59 | 07-DEC-16:30 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5148.59 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29185.67 | 12070.02 | 6977.40 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5030.84 | 13-JAN-16:40 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5463.25 | 24-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6909.29 | 24-MAR-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16025.82 | 17-APR-15:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20298.40 | 30-MAY-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30247.99 | 12-JUN-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30238.27 | 03-JUL-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25159.39 | 14-AUG-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30343.75 | 11-SEP-05:12 | 2541.06 | 1550.53 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8499.19 | 20-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7805.73 | 03-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4880.43 | 01-DEC-16:25 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4880.43 | 2541.06 | 1550.53 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30343.75 | 12070.02 | 6977.40 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 833.88 | 21-JAN-17:02 | 334.80 | 204.26 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.26 |
February | 1013.62 | 24-FEB-16:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.94 |
March | 1327.92 | 28-MAR-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.82 |
April | 5405.59 | 18-APR-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.87 | 0.00 |
May | 5838.57 | 31-MAY-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 | 0.00 |
June | 11789.19 | 18-JUN-16:11 | 535.68 | 155.89 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 463.23 | 0.00 |
July | 9188.47 | 05-JUL-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 |
August | 6392.24 | 04-AUG-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 95.02 | 0.00 |
September | 5867.02 | 11-SEP-13:40 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 92.94 | 0.00 |
October | 1586.00 | 20-OCT-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
November | 1344.77 | 03-NOV-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.49 |
December | 844.85 | 02-DEC-17:03 | 200.88 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 833.88 | 200.88 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11789.19 | 1306.65 | 350.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 463.23 | 683.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 594.93 | 12-JAN-10:30 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.26 |
February | 828.63 | 24-FEB-10:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.52 |
March | 2578.44 | 28-MAR-09:25 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.07 |
April | 7604.22 | 18-APR-09:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
May | 11075.11 | 28-MAY-09:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.18 |
June | 13691.76 | 25-JUN-08:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 |
July | 13713.38 | 02-JUL-08:42 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.15 |
August | 11722.59 | 27-AUG-08:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 |
September | 12216.59 | 04-SEP-08:43 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.12 |
October | 3032.41 | 20-OCT-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 |
November | 1117.97 | 04-NOV-09:20 | 261.23 | 74.03 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
December | 561.51 | 01-DEC-10:15 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 561.51 | 169.56 | 49.35 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | |
Maximum of Months | 13713.38 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4572.04 | 12-JAN-12:30 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.72 |
February | 7622.71 | 24-FEB-13:40 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.92 |
March | 8024.07 | 24-MAR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.14 |
April | 16395.60 | 16-APR-13:42 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 63.57 | 0.00 |
May | 10201.98 | 29-MAY-12:03 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.38 |
June | 16078.30 | 18-JUN-16:11 | 535.68 | 155.89 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 460.32 | 0.00 |
July | 16375.12 | 30-JUL-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 |
August | 16565.99 | 13-AUG-13:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.61 |
September | 16630.14 | 04-SEP-13:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.62 |
October | 11504.40 | 01-OCT-13:13 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.62 |
November | 9937.71 | 03-NOV-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 |
December | 5499.30 | 01-DEC-13:30 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4572.04 | 200.88 | 58.46 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16630.14 | 1306.65 | 350.81 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 460.32 | 571.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 774.67 | 12-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.85 |
February | 2644.49 | 24-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 |
March | 3083.74 | 23-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.36 |
April | 15013.43 | 16-APR-16:22 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 96.64 | 0.00 |
May | 14070.33 | 14-MAY-16:32 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.62 |
June | 16420.06 | 18-JUN-16:11 | 339.11 | 98.69 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 189.93 | 0.00 |
July | 15457.40 | 02-JUL-16:42 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 | 0.00 |
August | 14113.38 | 05-AUG-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.82 |
September | 13458.36 | 04-SEP-16:02 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 |
October | 5423.91 | 20-OCT-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
November | 3579.94 | 03-NOV-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 |
December | 770.21 | 01-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 770.21 | 211.94 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16420.06 | 805.38 | 222.08 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 189.93 | 236.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 817.24 | 14-JAN-17:03 | 267.84 | 163.41 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.21 |
February | 822.74 | 25-FEB-17:05 | 133.92 | 52.57 | 956.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.78 |
March | 1084.29 | 28-MAR-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.93 |
April | 2813.24 | 18-APR-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 0.00 |
May | 3657.21 | 31-MAY-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 | 0.00 |
June | 5129.66 | 26-JUN-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
July | 7147.17 | 05-JUL-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 |
August | 5196.03 | 04-AUG-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 |
September | 5335.42 | 11-SEP-06:03 | 1071.35 | 533.36 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 |
October | 1486.10 | 20-OCT-13:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 |
November | 1287.26 | 03-NOV-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 |
December | 826.76 | 02-DEC-17:03 | 200.88 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 817.24 | 133.92 | 52.57 | 956.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7147.17 | 1306.65 | 533.36 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 235.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 577.45 | 13-JAN-11:00 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.68 |
February | 712.65 | 24-FEB-10:05 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.71 |
March | 1103.88 | 28-MAR-09:35 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.03 |
April | 5034.65 | 18-APR-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 0.00 |
May | 5900.52 | 31-MAY-09:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 | 0.00 |
June | 8606.06 | 25-JUN-09:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 0.00 |
July | 9193.52 | 02-JUL-09:22 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 |
August | 7510.98 | 02-AUG-06:03 | 678.26 | 296.12 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 |
September | 9174.46 | 04-SEP-10:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.20 |
October | 2572.71 | 20-OCT-09:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 |
November | 1261.78 | 04-NOV-08:45 | 508.69 | 148.06 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.65 |
December | 587.43 | 05-DEC-09:30 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 577.45 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9193.52 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 | 357.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1105.52 | 13-JAN-14:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2169.27 |
February | 1307.39 | 24-FEB-14:50 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.68 |
March | 3360.41 | 24-MAR-14:00 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.42 |
April | 9377.14 | 16-APR-13:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 0.00 |
May | 9620.57 | 31-MAY-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4129.69 | 0.00 |
June | 11050.86 | 26-JUN-16:10 | 401.76 | 194.89 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5832.04 | 0.00 |
July | 10520.57 | 30-JUL-13:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 0.00 |
August | 11070.04 | 04-AUG-12:00 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4806.26 | 0.00 |
September | 13742.23 | 17-SEP-13:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.65 |
October | 8822.00 | 20-OCT-13:40 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 |
November | 7475.52 | 04-NOV-13:30 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.35 |
December | 1239.07 | 02-DEC-12:40 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1105.52 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13742.23 | 1306.65 | 350.81 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5832.04 | 2169.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 688.86 | 12-JAN-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.74 |
February | 1303.02 | 24-FEB-16:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 |
March | 1366.32 | 23-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.15 |
April | 11952.14 | 16-APR-16:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 36.74 | 0.00 |
May | 6854.39 | 21-MAY-17:02 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.98 |
June | 11879.21 | 25-JUN-17:21 | 0.00 | 86.35 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 125.47 | 0.00 |
July | 11833.85 | 23-JUL-18:32 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10700.81 | 13-AUG-16:01 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 |
September | 11617.32 | 04-SEP-16:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 |
October | 4497.46 | 11-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 |
November | 2933.58 | 03-NOV-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
December | 722.37 | 01-DEC-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 688.86 | 0.00 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11952.14 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 125.47 | 126.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 851.55 | 13-JAN-14:30 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.21 |
February | 951.51 | 24-FEB-16:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.29 |
March | 1248.08 | 28-MAR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.84 |
April | 4977.99 | 18-APR-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 0.00 |
May | 5413.96 | 31-MAY-06:03 | 803.52 | 350.81 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 |
June | 9460.63 | 25-JUN-19:12 | 0.00 | 125.92 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 0.00 |
July | 9409.44 | 02-JUL-18:31 | 0.00 | 136.41 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 | 0.00 |
August | 5789.03 | 04-AUG-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 79.30 | 0.00 |
September | 7256.11 | 11-SEP-06:03 | 1071.35 | 536.63 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 |
October | 1801.80 | 02-OCT-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 |
November | 1449.17 | 03-NOV-13:10 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.59 |
December | 797.09 | 02-DEC-17:03 | 200.88 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 797.09 | 0.00 | 122.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9460.63 | 2613.31 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 213.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 665.91 | 13-JAN-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 |
February | 1941.14 | 24-FEB-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.61 |
March | 4769.49 | 24-MAR-12:02 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.93 |
April | 8045.88 | 18-APR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 | 0.00 |
May | 13585.71 | 29-MAY-09:12 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.48 |
June | 14947.93 | 25-JUN-08:31 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.10 |
July | 14993.70 | 02-JUL-08:31 | 296.74 | 86.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.81 |
August | 13818.64 | 20-AUG-08:52 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.85 |
September | 11397.09 | 17-SEP-08:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.85 |
October | 4833.05 | 03-OCT-12:02 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.18 |
November | 2986.45 | 04-NOV-10:05 | 508.69 | 148.06 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.32 |
December | 631.71 | 05-DEC-09:50 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 631.71 | 169.56 | 49.35 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14993.70 | 4832.57 | 1332.55 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 | 565.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5219.29 | 12-JAN-12:30 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.95 |
February | 7748.21 | 24-FEB-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.60 |
March | 8158.92 | 24-MAR-13:10 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.04 |
April | 15132.50 | 16-APR-13:32 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 | 0.00 |
May | 9268.72 | 30-MAY-13:20 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18.29 | 0.00 |
June | 14791.34 | 25-JUN-11:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 | 0.00 |
July | 15632.39 | 30-JUL-12:22 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 |
August | 15119.57 | 13-AUG-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.39 |
September | 16335.40 | 17-SEP-12:52 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.35 |
October | 15119.31 | 01-OCT-13:43 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.37 |
November | 10272.02 | 03-NOV-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
December | 6013.28 | 01-DEC-13:15 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5219.29 | 267.84 | 77.95 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16335.40 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 | 482.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 795.40 | 12-JAN-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.71 |
February | 2622.94 | 24-FEB-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 |
March | 3178.29 | 22-MAR-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.36 |
April | 14776.38 | 16-APR-16:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 14584.63 | 21-MAY-16:32 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.56 |
June | 14828.48 | 25-JUN-16:32 | 423.88 | 123.36 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 238.95 | 0.00 |
July | 15550.57 | 02-JUL-16:32 | 381.49 | 111.02 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 0.00 |
August | 14873.11 | 13-AUG-16:11 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 |
September | 13683.71 | 17-SEP-16:52 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.13 |
October | 5447.82 | 20-OCT-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
November | 3751.33 | 03-NOV-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 |
December | 796.50 | 01-DEC-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 795.40 | 211.94 | 61.68 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15550.57 | 805.38 | 222.08 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 238.95 | 231.56 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.188656E+12 | 237473.55 | 30-JAN-07:10 | 0.124965E+12 | 153353.53 | 30-JAN-09:00 |
February | 0.136141E+12 | 234902.31 | 02-FEB-07:10 | 0.870289E+11 | 155487.14 | 02-FEB-12:20 |
March | 0.113669E+12 | 205158.86 | 06-MAR-07:10 | 0.605400E+11 | 102564.17 | 06-MAR-08:09 |
April | 0.877615E+11 | 170134.07 | 03-APR-06:10 | 0.328173E+11 | 79865.04 | 03-APR-06:49 |
May | 0.893356E+11 | 116351.87 | 31-MAY-15:09 | 0.133858E+11 | 38205.85 | 02-MAY-06:30 |
June | 0.110632E+12 | 149402.30 | 26-JUN-07:49 | 0.115648E+11 | 21182.02 | 03-JUN-06:40 |
July | 0.119331E+12 | 143806.07 | 05-JUL-10:50 | 0.109049E+11 | 9972.04 | 03-JUL-11:09 |
August | 0.122563E+12 | 155977.10 | 04-AUG-07:10 | 0.112962E+11 | 12064.30 | 07-AUG-06:10 |
September | 0.933313E+11 | 126006.19 | 11-SEP-09:50 | 0.129570E+11 | 44882.48 | 29-SEP-06:10 |
October | 0.816201E+11 | 98342.08 | 16-OCT-06:10 | 0.245329E+11 | 54705.23 | 23-OCT-06:10 |
November | 0.113787E+12 | 220732.26 | 27-NOV-07:10 | 0.535088E+11 | 120949.64 | 25-NOV-07:49 |
December | 0.157664E+12 | 231899.71 | 11-DEC-07:10 | 0.951699E+11 | 145628.94 | 09-DEC-08:39 |
Annual Sum or Average | 0.141449E+13 | 0.538672E+12 | ||||
Minimum of Months | 0.816201E+11 | 98342.08 | 0.109049E+11 | 9972.04 | ||
Maximum of Months | 0.188656E+12 | 237473.55 | 0.124965E+12 | 155487.14 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.557696E+10 | 16728.47 | 29-JAN-12:30 | 0.00 | 0.00 |
February | 0.683559E+10 | 17206.09 | 24-FEB-12:30 | 0.00 | 0.00 |
March | 0.108532E+11 | 23618.99 | 16-MAR-12:30 | 0.00 | 0.00 |
April | 0.135898E+11 | 25966.78 | 25-APR-12:20 | 0.00 | 0.00 |
May | 0.161352E+11 | 25270.73 | 18-MAY-11:30 | 0.00 | 0.00 |
June | 0.173277E+11 | 24922.93 | 22-JUN-11:00 | 0.00 | 0.00 |
July | 0.179250E+11 | 24298.87 | 15-JUL-12:30 | 0.00 | 0.00 |
August | 0.151339E+11 | 24128.02 | 07-AUG-12:30 | 0.00 | 0.00 |
September | 0.116867E+11 | 21186.50 | 04-SEP-11:00 | 0.00 | 0.00 |
October | 0.826717E+10 | 17267.49 | 01-OCT-12:39 | 0.00 | 0.00 |
November | 0.499286E+10 | 13769.00 | 04-NOV-11:50 | 0.00 | 0.00 |
December | 0.372915E+10 | 11143.31 | 01-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132053E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.372915E+10 | 11143.31 | 0.00 | 0.00 | |
Maximum of Months | 0.179250E+11 | 25966.78 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.143990E+11 | 0.404322E+10 | 0.545046E+11 | 0.976784E+09 | 0.534698E+10 | 12379742.02 | 0.109373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127930E+11 | 0.320785E+10 | 0.493409E+11 | 0.883747E+09 | 0.404848E+10 | 11196021.66 | 0.658563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149055E+11 | 0.295872E+10 | 0.567112E+11 | 0.102243E+10 | 0.395396E+10 | 12675672.10 | 0.340065E+11 | 97523377.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132215E+11 | 0.232977E+10 | 0.526212E+11 | 0.940436E+09 | 0.454858E+10 | 11960507.72 | 0.105339E+11 | 0.355402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141344E+11 | 0.201422E+10 | 0.556079E+11 | 0.999248E+09 | 0.663146E+10 | 12527707.06 | 0.831998E+09 | 0.910379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140396E+11 | 0.180021E+10 | 0.546110E+11 | 0.983596E+09 | 0.119080E+11 | 12231776.97 | 0.237048E+09 | 0.270403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131693E+11 | 0.191613E+10 | 0.536070E+11 | 0.955903E+09 | 0.133216E+11 | 12256437.81 | 4149296.91 | 0.363444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146860E+11 | 0.222274E+10 | 0.567112E+11 | 0.102232E+10 | 0.133260E+11 | 12675672.10 | 35683154.46 | 0.345462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132774E+11 | 0.260113E+10 | 0.525990E+11 | 0.940227E+09 | 0.842528E+10 | 11960507.72 | 0.833509E+09 | 0.146429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139589E+11 | 0.329740E+10 | 0.545158E+11 | 0.976491E+09 | 0.385688E+10 | 12379742.02 | 0.413196E+10 | 0.870327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141780E+11 | 0.375253E+10 | 0.533244E+11 | 0.958557E+09 | 0.386152E+10 | 12059151.09 | 0.376625E+11 | 37648159.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141448E+11 | 0.419698E+10 | 0.535958E+11 | 0.956615E+09 | 0.447459E+10 | 12256437.81 | 0.802832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166908E+12 | 0.343409E+11 | 0.647750E+12 | 0.116163E+11 | 0.837033E+11 | 0.146559E+09 | 0.343790E+12 | 0.126237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127930E+11 | 0.180021E+10 | 0.493409E+11 | 0.883747E+09 | 0.385688E+10 | 11196021.66 | 4149296.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149055E+11 | 0.419698E+10 | 0.567112E+11 | 0.102243E+10 | 0.133260E+11 | 12675672.10 | 0.109373E+12 | 0.363444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.112565E+12 | 0.00 | 0.124004E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.756886E+11 | 0.00 | 0.113403E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.476310E+11 | 0.00 | 0.129090E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.210604E+11 | 0.00 | 0.117569E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.139903E+10 | 0.00 | 0.119868E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.224187E+09 | 0.00 | 0.113406E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.109049E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5311872.82 | 0.00 | 0.112909E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.232700E+10 | 0.00 | 0.106300E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132813E+11 | 0.00 | 0.112515E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.421456E+11 | 0.00 | 0.113631E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.832590E+11 | 0.00 | 0.119109E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.399586E+12 | 0.00 | 0.139085E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.106300E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.112565E+12 | 0.00 | 0.129090E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-16:40 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 828.69 | 17-JAN-08:20 | 7289.21 | 30-JAN-07:10 | 6.85 | 03-JAN-17:19 | 201872.72 | 30-JAN-07:10 |
February | 16280.96 | 14-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 827.16 | 22-FEB-08:20 | 6961.80 | 06-FEB-07:10 | 6.85 | 02-FEB-22:10 | 200400.16 | 02-FEB-07:10 |
March | 14962.99 | 01-MAR-16:00 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 825.68 | 14-MAR-07:19 | 5938.60 | 06-MAR-07:10 | 6.85 | 03-MAR-18:19 | 175470.49 | 06-MAR-07:10 |
April | 14605.37 | 10-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 825.74 | 10-APR-07:19 | 19678.97 | 18-APR-14:00 | 6.85 | 03-APR-06:19 | 141801.86 | 03-APR-06:10 |
May | 13959.04 | 24-MAY-15:00 | 2323.70 | 01-MAY-19:10 | 40437.79 | 01-MAY-07:10 | 824.86 | 25-MAY-07:19 | 21557.98 | 30-MAY-15:30 | 6.85 | 02-MAY-07:10 | 33104.03 | 02-MAY-06:10 |
June | 14318.48 | 13-JUN-07:10 | 2323.70 | 01-JUN-19:40 | 40437.79 | 01-JUN-07:10 | 825.37 | 13-JUN-07:19 | 28391.27 | 26-JUN-15:30 | 6.85 | 11-JUN-15:20 | 11021.80 | 02-JUN-06:19 |
July | 14322.60 | 20-JUL-07:10 | 2323.70 | 01-JUL-19:00 | 40437.79 | 03-JUL-07:10 | 825.37 | 20-JUL-07:19 | 28385.71 | 03-JUL-15:20 | 6.85 | 02-JUL-15:20 | 1431.57 | 24-JUL-06:10 |
August | 14098.46 | 31-AUG-07:10 | 3824.74 | 08-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 825.08 | 31-AUG-07:19 | 30548.97 | 04-AUG-07:10 | 6.85 | 05-AUG-16:10 | 5255.93 | 16-AUG-06:19 |
September | 14611.38 | 21-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 825.75 | 21-SEP-07:19 | 22193.48 | 07-SEP-15:50 | 6.85 | 02-SEP-16:10 | 37022.63 | 30-SEP-06:10 |
October | 17141.70 | 31-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 829.09 | 31-OCT-07:19 | 8122.68 | 20-OCT-15:30 | 6.85 | 03-OCT-11:09 | 66929.87 | 16-OCT-06:10 |
November | 17672.30 | 06-NOV-16:00 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 829.48 | 03-NOV-07:19 | 6465.83 | 27-NOV-07:10 | 6.85 | 01-NOV-16:10 | 185954.81 | 27-NOV-07:10 |
December | 17672.30 | 01-DEC-16:30 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 829.00 | 22-DEC-08:20 | 7089.95 | 11-DEC-07:10 | 6.85 | 01-DEC-17:10 | 196498.15 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 13959.04 | 2323.70 | 40437.79 | 824.86 | 5938.60 | 6.85 | 1431.57 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 40437.79 | 829.48 | 30548.97 | 6.85 | 201872.72 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 5176.82 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 42270.53 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 43045.56 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 68470.69 | 26-JUN-07:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 65102.93 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 70376.98 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 54114.91 | 06-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 17458.84 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3210.51 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 70376.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 237473.55 | 30-JAN-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 7289.21 | 6.85 | 201872.72 | 0.00 | 0.00 |
February | 234902.31 | 02-FEB-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6190.54 | 6.85 | 200400.16 | 0.00 | 0.00 |
March | 205158.86 | 06-MAR-07:10 | 5153.75 | 18346.02 | 0.00 | 243.15 | 5938.60 | 6.85 | 175470.49 | 0.00 | 0.00 |
April | 170134.07 | 03-APR-06:10 | 5117.82 | 18346.02 | 0.00 | 243.15 | 4618.38 | 6.85 | 141801.86 | 0.00 | 0.00 |
May | 116351.87 | 31-MAY-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 20644.48 | 6.85 | 0.00 | 42518.92 | 0.00 |
June | 149402.30 | 26-JUN-07:49 | 13903.46 | 40437.79 | 0.00 | 824.82 | 25758.68 | 6.85 | 0.00 | 68470.69 | 0.00 |
July | 143806.07 | 05-JUL-10:50 | 13903.46 | 38195.78 | 0.00 | 823.54 | 25773.51 | 6.85 | 0.00 | 65102.93 | 0.00 |
August | 155977.10 | 04-AUG-07:10 | 13903.46 | 40437.79 | 0.00 | 812.71 | 30548.97 | 6.85 | 0.00 | 70267.31 | 0.00 |
September | 126006.19 | 11-SEP-09:50 | 13903.46 | 37678.39 | 0.00 | 823.25 | 21364.77 | 6.85 | 0.00 | 52229.47 | 0.00 |
October | 98342.08 | 16-OCT-06:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3100.60 | 6.85 | 66929.87 | 0.00 | 0.00 |
November | 220732.26 | 27-NOV-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6465.83 | 6.85 | 185954.81 | 0.00 | 0.00 |
December | 231899.71 | 11-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 7089.95 | 6.85 | 196498.15 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 98342.08 | 5117.82 | 18346.02 | 0.00 | 243.15 | 3100.60 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 237473.55 | 13903.46 | 40437.79 | 3824.74 | 824.82 | 30548.97 | 6.85 | 201872.72 | 70267.31 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 143707.63 | 06-JAN-07:19 | 0.00 | 12655.72 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 143707.63 | 01-FEB-07:19 | 0.00 | 12793.64 | 21-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 93009.15 | 06-MAR-08:09 | 0.00 | 12740.99 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 70998.25 | 03-APR-06:00 | 0.00 | 12003.94 | 04-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 29632.11 | 02-MAY-06:19 | 0.00 | 10694.95 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 13272.07 | 03-JUN-06:10 | 0.00 | 10120.20 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9972.04 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 3249.99 | 07-AUG-06:10 | 0.00 | 9896.12 | 01-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 36156.85 | 29-SEP-06:19 | 0.00 | 9950.70 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 48197.03 | 23-OCT-06:19 | 0.00 | 10082.54 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 116019.12 | 25-NOV-07:30 | 0.00 | 10237.57 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 138585.20 | 09-DEC-07:30 | 0.00 | 11572.75 | 28-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9896.12 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 143707.63 | 0.00 | 12793.64 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.33 | 2.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.96 | 0.33 | 24.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 19.33 | 2.00 | 19.42 | 0.33 | 19.83 | 0.33 | 20.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.33 | 2.00 | 19.42 | 0.33 | 24.96 | 0.33 | 24.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.17 | 2.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
March | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.18 | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 0.33 | 19.17 | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Annual Sum or Average | 3.17 | 19.18 | 2.83 | 19.31 | 0.17 | 19.45 | 0.17 | 19.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.42 | 2.00 | 19.42 | 0.17 | 24.61 | 0.17 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 18.70 | 6.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
February | 3.00 | 18.59 | 2.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
March | 0.83 | 18.09 | 0.50 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
April | 0.33 | 18.05 | 0.17 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.00 | 19.03 | 1.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 3.83 | 18.79 | 2.83 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 18.33 | 18.70 | 13.33 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.33 | 19.03 | 6.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 105.00 | 16.16 | 51.33 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
February | 52.17 | 16.43 | 24.50 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
March | 15.33 | 16.04 | 6.17 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
April | 3.00 | 15.84 | 0.50 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.48 | 2.67 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 0.67 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24.33 | 16.06 | 10.17 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
December | 54.00 | 16.04 | 25.00 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
Annual Sum or Average | 253.83 | 16.17 | 117.67 | 16.64 | 5.17 | 16.78 | 3.33 | 16.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 105.00 | 16.43 | 51.33 | 16.96 | 4.17 | 27.48 | 2.67 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.50 | 14.66 | 15.50 | 14.71 | 0.00 | 14.71 | 0.00 | 14.71 |
February | 28.67 | 14.75 | 4.50 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
March | 9.83 | 15.18 | 0.67 | 15.23 | 0.00 | 15.23 | 0.00 | 15.23 |
April | 2.50 | 15.12 | 0.00 | 15.12 | 1.33 | 19.36 | 1.33 | 21.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.63 | 4.67 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.94 | 6.67 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.91 | 8.50 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.66 | 3.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.70 | 3.00 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18.67 | 14.85 | 4.50 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
December | 37.33 | 14.79 | 10.67 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
Annual Sum or Average | 159.50 | 14.77 | 35.83 | 14.81 | 29.33 | 16.51 | 27.17 | 17.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.50 | 15.18 | 15.50 | 15.23 | 9.33 | 27.94 | 8.50 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.67 | 15.13 | 13.83 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
February | 24.50 | 15.35 | 4.50 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
March | 8.33 | 15.44 | 1.00 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
April | 2.50 | 15.33 | 0.17 | 15.59 | 1.83 | 20.61 | 1.67 | 22.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.40 | 2.00 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.81 | 4.33 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.76 | 5.67 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.58 | 5.17 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.97 | 5.17 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.50 | 0.83 | 27.50 |
November | 15.17 | 15.05 | 3.83 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
December | 32.33 | 15.29 | 8.67 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
Annual Sum or Average | 139.50 | 15.22 | 32.00 | 15.46 | 27.33 | 17.15 | 24.83 | 18.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 | 0.00 | 15.21 |
Maximum of Months | 56.67 | 15.44 | 13.83 | 15.68 | 6.67 | 27.97 | 5.67 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.17 | 14.64 | 17.00 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
February | 26.83 | 14.67 | 5.50 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
March | 9.17 | 15.09 | 1.33 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
April | 2.33 | 14.80 | 0.00 | 14.80 | 2.33 | 21.47 | 1.50 | 23.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.86 | 2.83 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.39 | 4.00 | 28.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.30 | 5.50 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.91 | 3.50 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.02 | 3.17 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17.50 | 14.80 | 4.17 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
December | 36.00 | 14.72 | 9.50 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
Annual Sum or Average | 154.00 | 14.71 | 37.50 | 14.73 | 33.00 | 16.70 | 20.50 | 17.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.17 | 15.09 | 17.00 | 15.04 | 10.67 | 28.39 | 5.50 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.83 | 18.16 | 53.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 47.67 | 18.39 | 34.67 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
March | 7.67 | 18.10 | 4.83 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
April | 0.50 | 18.82 | 0.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.17 | 17.72 | 3.83 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
December | 21.00 | 17.71 | 13.67 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
Annual Sum or Average | 157.83 | 18.15 | 110.33 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.83 | 18.82 | 53.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.33 | 15.36 | 3.83 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
February | 9.50 | 15.30 | 0.50 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
March | 1.67 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
April | 0.17 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.46 | 5.17 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.66 | 5.67 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.01 | 2.00 | 27.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.55 | 2.67 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.83 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
December | 7.33 | 15.36 | 0.83 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
Annual Sum or Average | 41.83 | 15.38 | 5.17 | 15.45 | 15.83 | 18.48 | 15.83 | 20.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.33 | 16.88 | 3.83 | 16.88 | 5.67 | 27.66 | 5.67 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 136.00 | 15.89 | 123.17 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
February | 86.50 | 16.34 | 83.00 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
March | 63.67 | 17.49 | 63.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
April | 29.17 | 18.25 | 29.00 | 18.25 | 0.50 | 18.33 | 0.50 | 18.41 |
May | 3.33 | 19.36 | 3.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.35 | 1.50 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.47 | 2.33 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.25 | 2.00 | 26.25 |
September | 2.83 | 19.59 | 2.83 | 19.59 | 14.50 | 24.03 | 14.50 | 24.76 |
October | 11.67 | 19.05 | 11.67 | 19.05 | 0.67 | 19.28 | 0.67 | 19.50 |
November | 49.83 | 17.44 | 49.17 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
December | 97.33 | 16.72 | 93.33 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
Annual Sum or Average | 480.33 | 16.78 | 458.67 | 16.81 | 21.50 | 17.02 | 21.50 | 17.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 0.00 | 15.91 |
Maximum of Months | 136.00 | 19.59 | 123.17 | 19.59 | 14.50 | 27.47 | 14.50 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.50 | 15.29 | 4.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
February | 8.33 | 15.25 | 0.83 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
March | 0.83 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
April | 0.17 | 16.83 | 0.00 | 16.83 | 1.17 | 26.28 | 0.83 | 26.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.49 | 0.50 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.90 | 3.00 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.82 | 4.17 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.59 | 2.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.67 | 2.83 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.00 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
December | 8.67 | 15.20 | 2.00 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
Annual Sum or Average | 41.50 | 15.29 | 6.83 | 15.30 | 22.50 | 19.26 | 13.33 | 20.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.50 | 16.83 | 4.00 | 16.83 | 8.83 | 27.90 | 4.17 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.83 | 17.04 | 32.67 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
February | 29.67 | 17.15 | 15.67 | 17.72 | 0.00 | 17.72 | 0.00 | 17.72 |
March | 5.50 | 17.01 | 2.17 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
April | 0.50 | 18.48 | 0.33 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.32 | 0.50 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.83 | 16.46 | 7.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
December | 31.83 | 16.61 | 16.33 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
Annual Sum or Average | 142.17 | 16.91 | 74.17 | 17.44 | 1.50 | 17.50 | 0.50 | 17.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.83 | 18.48 | 32.67 | 18.83 | 1.50 | 27.32 | 0.50 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.67 | 14.99 | 6.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
February | 13.67 | 15.17 | 1.33 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
March | 2.67 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
April | 0.17 | 16.69 | 0.00 | 16.69 | 0.67 | 25.23 | 0.67 | 26.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.73 | 4.33 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.60 | 7.17 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.93 | 7.83 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.84 | 2.33 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.84 | 3.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.50 | 15.12 | 2.17 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
December | 17.67 | 15.06 | 3.17 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
Annual Sum or Average | 75.33 | 15.07 | 12.67 | 15.11 | 26.17 | 18.01 | 25.50 | 19.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.67 | 16.69 | 6.00 | 16.69 | 8.00 | 27.93 | 7.83 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.67 | 15.47 | 4.33 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
February | 9.17 | 15.49 | 1.00 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
March | 1.17 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
April | 0.17 | 16.77 | 0.00 | 16.77 | 1.67 | 26.77 | 1.67 | 27.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.38 | 1.17 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.64 | 4.33 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.65 | 5.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.53 | 4.50 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.89 | 5.50 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.52 | 1.83 | 27.52 |
November | 7.00 | 15.21 | 1.17 | 15.24 | 0.33 | 15.72 | 0.33 | 16.15 |
December | 12.67 | 15.20 | 1.67 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
Annual Sum or Average | 52.83 | 15.39 | 8.17 | 15.53 | 25.50 | 19.11 | 24.83 | 21.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 | 15.29 |
Maximum of Months | 22.67 | 16.77 | 4.33 | 16.77 | 5.67 | 27.89 | 5.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.00 | 14.99 | 5.50 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
February | 14.17 | 15.21 | 2.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
March | 2.00 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
April | 0.17 | 16.67 | 0.00 | 16.67 | 2.17 | 27.21 | 1.50 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.89 | 2.17 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.27 | 3.50 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.17 | 5.33 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.86 | 3.17 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.91 | 3.17 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 15.03 | 3.00 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
December | 18.00 | 15.03 | 4.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 76.17 | 15.06 | 15.00 | 15.08 | 30.33 | 18.32 | 18.83 | 19.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.00 | 16.67 | 5.50 | 16.67 | 10.17 | 28.27 | 5.33 | 28.30 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.19 | 334.33 | 21.01 | 334.33 | 20.94 |
February | 454.00 | 21.80 | 131.00 | 21.59 | 131.00 | 21.46 |
March | 510.33 | 22.78 | 31.50 | 22.68 | 31.50 | 22.59 |
April | 385.33 | 23.41 | 31.00 | 23.50 | 0.00 | 23.50 |
May | 80.83 | 23.88 | 250.83 | 24.31 | 0.00 | 24.31 |
June | 0.17 | 23.79 | 405.33 | 24.35 | 0.00 | 24.35 |
July | 0.00 | 0.00 | 489.17 | 24.38 | 0.00 | 24.38 |
August | 1.00 | 24.49 | 495.83 | 24.33 | 1.00 | 24.33 |
September | 67.50 | 23.90 | 244.17 | 24.41 | 0.00 | 24.41 |
October | 384.83 | 23.91 | 12.50 | 23.94 | 0.00 | 23.94 |
November | 410.50 | 22.79 | 64.33 | 22.57 | 60.33 | 22.38 |
December | 497.00 | 21.77 | 154.00 | 21.56 | 154.00 | 21.43 |
Annual Sum or Average | 3293.50 | 22.51 | 2644.00 | 22.92 | 712.17 | 22.70 |
Minimum of Months | 0.00 | 0.00 | 12.50 | 21.01 | 0.00 | 20.94 |
Maximum of Months | 510.33 | 24.49 | 495.83 | 24.41 | 334.33 | 24.41 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.56 | 454.83 | 20.50 | 454.83 | 20.48 |
February | 454.00 | 20.98 | 295.67 | 20.84 | 295.67 | 20.78 |
March | 514.00 | 21.88 | 145.33 | 21.64 | 145.33 | 21.49 |
April | 406.33 | 22.59 | 65.00 | 22.58 | 34.33 | 22.47 |
May | 148.67 | 23.58 | 190.67 | 23.95 | 0.00 | 23.95 |
June | 26.83 | 23.40 | 358.17 | 24.22 | 0.00 | 24.22 |
July | 0.00 | 0.00 | 471.50 | 24.31 | 0.00 | 24.31 |
August | 0.83 | 24.19 | 472.33 | 24.26 | 0.83 | 24.26 |
September | 137.67 | 23.52 | 192.83 | 24.05 | 0.00 | 24.05 |
October | 481.00 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
November | 472.33 | 21.82 | 179.50 | 21.51 | 179.50 | 21.33 |
December | 497.00 | 20.84 | 382.83 | 20.73 | 382.83 | 20.68 |
Annual Sum or Average | 3640.67 | 21.82 | 3208.67 | 22.17 | 1493.33 | 21.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20.50 | 0.00 | 20.48 |
Maximum of Months | 514.00 | 24.19 | 472.33 | 24.31 | 454.83 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 479.67 | 20.14 | 479.67 | 20.13 |
February | 454.00 | 20.51 | 367.33 | 20.40 | 367.33 | 20.36 |
March | 514.00 | 21.38 | 252.67 | 21.13 | 252.67 | 21.00 |
April | 411.50 | 22.04 | 116.50 | 21.93 | 82.83 | 21.73 |
May | 188.33 | 23.31 | 165.17 | 23.72 | 0.00 | 23.72 |
June | 60.67 | 23.26 | 339.00 | 24.11 | 0.00 | 24.11 |
July | 5.67 | 23.48 | 454.83 | 24.28 | 0.00 | 24.28 |
August | 21.50 | 23.56 | 435.83 | 24.19 | 3.83 | 24.19 |
September | 200.17 | 23.06 | 157.83 | 23.60 | 2.00 | 23.59 |
October | 493.83 | 22.23 | 52.00 | 22.08 | 52.00 | 21.96 |
November | 489.00 | 21.12 | 269.50 | 20.81 | 269.50 | 20.66 |
December | 497.00 | 20.33 | 469.50 | 20.29 | 469.50 | 20.28 |
Annual Sum or Average | 3837.67 | 21.36 | 3559.83 | 21.69 | 1979.33 | 21.40 |
Minimum of Months | 5.67 | 20.17 | 52.00 | 20.14 | 0.00 | 20.13 |
Maximum of Months | 514.00 | 23.56 | 479.67 | 24.28 | 479.67 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 499.00 | 19.61 | 499.00 | 19.60 |
February | 454.00 | 19.82 | 439.33 | 19.79 | 439.33 | 19.79 |
March | 514.00 | 20.60 | 369.50 | 20.45 | 369.50 | 20.39 |
April | 424.50 | 21.16 | 207.67 | 21.03 | 174.17 | 20.82 |
May | 244.33 | 22.76 | 177.33 | 23.29 | 8.33 | 23.24 |
June | 117.83 | 23.61 | 350.00 | 24.13 | 37.00 | 24.23 |
July | 63.83 | 24.57 | 450.83 | 24.36 | 44.33 | 24.42 |
August | 84.33 | 23.61 | 400.00 | 24.07 | 37.50 | 24.08 |
September | 263.50 | 22.33 | 174.17 | 22.95 | 21.33 | 22.84 |
October | 499.17 | 21.18 | 186.33 | 20.90 | 186.33 | 20.74 |
November | 489.00 | 20.23 | 344.33 | 19.98 | 344.33 | 19.88 |
December | 497.00 | 19.72 | 497.00 | 19.72 | 497.00 | 19.72 |
Annual Sum or Average | 4153.50 | 20.82 | 4095.50 | 21.17 | 2658.17 | 20.90 |
Minimum of Months | 63.83 | 19.61 | 174.17 | 19.61 | 8.33 | 19.60 |
Maximum of Months | 514.00 | 24.57 | 499.00 | 24.36 | 499.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 486.83 | 19.69 | 486.83 | 19.68 |
February | 454.00 | 19.98 | 405.00 | 19.88 | 405.00 | 19.85 |
March | 504.00 | 20.92 | 287.83 | 20.63 | 287.83 | 20.50 |
April | 391.67 | 21.65 | 188.83 | 21.62 | 134.00 | 21.39 |
May | 170.17 | 23.41 | 252.50 | 24.04 | 23.33 | 24.14 |
June | 100.50 | 24.30 | 386.17 | 24.38 | 46.67 | 24.54 |
July | 85.00 | 25.78 | 470.83 | 24.69 | 77.17 | 24.86 |
August | 78.00 | 24.72 | 444.50 | 24.33 | 57.33 | 24.43 |
September | 213.67 | 22.83 | 220.17 | 23.60 | 30.67 | 23.63 |
October | 479.50 | 21.70 | 120.67 | 21.40 | 119.83 | 21.20 |
November | 486.33 | 20.40 | 328.67 | 20.13 | 328.67 | 20.01 |
December | 497.00 | 19.81 | 494.67 | 19.81 | 494.67 | 19.81 |
Annual Sum or Average | 3961.83 | 21.10 | 4086.67 | 21.50 | 2492.00 | 21.24 |
Minimum of Months | 78.00 | 19.71 | 120.67 | 19.69 | 23.33 | 19.68 |
Maximum of Months | 504.00 | 25.78 | 494.67 | 24.69 | 494.67 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.83 | 20.06 | 416.33 | 19.83 | 416.33 | 19.75 |
February | 438.50 | 20.44 | 333.67 | 20.18 | 329.17 | 20.06 |
March | 461.17 | 21.06 | 279.67 | 20.82 | 266.83 | 20.65 |
April | 356.83 | 21.44 | 206.67 | 21.53 | 139.33 | 21.28 |
May | 195.83 | 22.87 | 222.33 | 23.64 | 15.00 | 23.65 |
June | 123.50 | 23.74 | 348.00 | 24.18 | 42.33 | 24.31 |
July | 86.67 | 24.98 | 445.33 | 24.51 | 63.50 | 24.63 |
August | 96.50 | 24.38 | 423.50 | 24.29 | 57.50 | 24.40 |
September | 219.83 | 22.94 | 232.17 | 23.67 | 35.83 | 23.73 |
October | 388.33 | 21.74 | 157.00 | 21.77 | 102.67 | 21.55 |
November | 466.67 | 20.78 | 285.33 | 20.47 | 272.33 | 20.27 |
December | 486.67 | 20.29 | 408.83 | 20.06 | 408.83 | 19.98 |
Annual Sum or Average | 3815.33 | 21.29 | 3758.83 | 21.66 | 2149.67 | 21.38 |
Minimum of Months | 86.67 | 20.06 | 157.00 | 19.83 | 15.00 | 19.75 |
Maximum of Months | 494.83 | 24.98 | 445.33 | 24.51 | 416.33 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 486.83 | 19.71 | 486.83 | 19.70 |
February | 450.33 | 20.06 | 401.00 | 19.95 | 401.00 | 19.92 |
March | 491.50 | 20.81 | 318.83 | 20.58 | 317.33 | 20.48 |
April | 369.83 | 21.36 | 212.17 | 21.41 | 149.00 | 21.18 |
May | 208.00 | 23.03 | 228.33 | 23.68 | 25.00 | 23.75 |
June | 123.67 | 23.83 | 375.33 | 24.24 | 45.67 | 24.36 |
July | 91.00 | 25.22 | 457.17 | 24.58 | 71.50 | 24.72 |
August | 94.67 | 24.32 | 445.00 | 24.27 | 58.33 | 24.36 |
September | 243.17 | 22.70 | 214.67 | 23.39 | 35.50 | 23.41 |
October | 448.50 | 21.37 | 168.67 | 21.14 | 151.50 | 20.94 |
November | 480.50 | 20.37 | 325.83 | 20.10 | 324.00 | 19.98 |
December | 497.00 | 19.85 | 473.33 | 19.80 | 473.33 | 19.78 |
Annual Sum or Average | 4000.17 | 21.04 | 4107.17 | 21.44 | 2539.00 | 21.18 |
Minimum of Months | 91.00 | 19.74 | 168.67 | 19.71 | 25.00 | 19.70 |
Maximum of Months | 502.00 | 25.22 | 486.83 | 24.58 | 486.83 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.67 | 502.00 | 19.67 | 502.00 | 19.67 |
February | 454.00 | 19.95 | 450.50 | 19.95 | 450.50 | 19.95 |
March | 514.00 | 20.55 | 402.00 | 20.47 | 402.00 | 20.44 |
April | 470.17 | 21.11 | 233.00 | 20.92 | 224.83 | 20.80 |
May | 391.50 | 22.66 | 79.67 | 22.84 | 15.00 | 22.80 |
June | 129.50 | 23.23 | 289.00 | 23.91 | 22.33 | 23.93 |
July | 34.33 | 24.43 | 437.50 | 24.25 | 26.00 | 24.28 |
August | 47.00 | 23.94 | 415.50 | 24.13 | 23.67 | 24.14 |
September | 222.67 | 22.87 | 156.83 | 23.43 | 2.33 | 23.42 |
October | 499.50 | 21.90 | 51.00 | 21.78 | 51.00 | 21.68 |
November | 489.00 | 20.82 | 294.17 | 20.55 | 294.17 | 20.43 |
December | 497.00 | 19.99 | 497.00 | 19.99 | 497.00 | 19.99 |
Annual Sum or Average | 4250.67 | 21.03 | 3808.17 | 21.28 | 2510.83 | 21.02 |
Minimum of Months | 34.33 | 19.67 | 51.00 | 19.67 | 2.33 | 19.67 |
Maximum of Months | 514.00 | 24.43 | 502.00 | 24.25 | 502.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 493.00 | 19.83 | 493.00 | 19.83 |
February | 454.00 | 20.16 | 420.17 | 20.12 | 420.17 | 20.10 |
March | 514.00 | 20.93 | 321.50 | 20.71 | 321.50 | 20.62 |
April | 418.00 | 21.55 | 176.67 | 21.45 | 139.83 | 21.24 |
May | 218.00 | 23.14 | 183.83 | 23.81 | 7.83 | 23.83 |
June | 107.83 | 24.14 | 376.00 | 24.34 | 41.67 | 24.46 |
July | 53.67 | 26.16 | 482.67 | 24.65 | 53.00 | 24.79 |
August | 37.67 | 25.14 | 487.50 | 24.36 | 33.17 | 24.42 |
September | 161.50 | 23.44 | 232.67 | 24.12 | 12.00 | 24.20 |
October | 464.67 | 22.63 | 21.00 | 22.59 | 15.83 | 22.52 |
November | 486.17 | 21.07 | 274.83 | 20.75 | 274.83 | 20.61 |
December | 497.00 | 20.10 | 493.33 | 20.09 | 493.33 | 20.09 |
Annual Sum or Average | 3914.50 | 21.31 | 3963.17 | 21.69 | 2306.17 | 21.42 |
Minimum of Months | 37.67 | 19.84 | 21.00 | 19.83 | 7.83 | 19.83 |
Maximum of Months | 514.00 | 26.16 | 493.33 | 24.65 | 493.33 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.83 | 482.67 | 18.77 | 482.67 | 18.76 |
February | 453.67 | 19.65 | 382.17 | 19.48 | 382.17 | 19.41 |
March | 500.67 | 20.49 | 316.00 | 20.22 | 316.00 | 20.10 |
April | 421.67 | 21.14 | 209.00 | 21.05 | 171.83 | 20.85 |
May | 345.67 | 22.36 | 106.00 | 22.81 | 12.33 | 22.77 |
June | 195.50 | 23.00 | 289.50 | 23.76 | 62.33 | 23.81 |
July | 123.33 | 24.07 | 444.50 | 24.29 | 99.83 | 24.31 |
August | 114.17 | 23.78 | 463.50 | 24.19 | 85.00 | 24.21 |
September | 197.67 | 22.91 | 239.33 | 23.87 | 23.83 | 23.98 |
October | 388.33 | 22.24 | 65.67 | 22.41 | 20.50 | 22.30 |
November | 458.50 | 20.68 | 253.67 | 20.40 | 238.00 | 20.18 |
December | 494.00 | 19.63 | 424.33 | 19.47 | 423.50 | 19.41 |
Annual Sum or Average | 4195.17 | 20.93 | 3676.33 | 21.24 | 2318.00 | 20.94 |
Minimum of Months | 114.17 | 18.83 | 65.67 | 18.77 | 12.33 | 18.76 |
Maximum of Months | 502.00 | 24.07 | 482.67 | 24.29 | 482.67 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 493.17 | 19.84 | 493.17 | 19.83 |
February | 454.00 | 20.24 | 417.17 | 20.18 | 417.17 | 20.15 |
March | 513.17 | 20.89 | 337.83 | 20.69 | 337.83 | 20.61 |
April | 413.67 | 21.59 | 171.50 | 21.48 | 137.50 | 21.28 |
May | 264.67 | 22.90 | 153.67 | 23.42 | 13.33 | 23.40 |
June | 115.00 | 23.76 | 365.83 | 24.22 | 35.67 | 24.31 |
July | 49.00 | 26.01 | 480.33 | 24.62 | 45.67 | 24.75 |
August | 28.83 | 25.47 | 486.17 | 24.38 | 27.50 | 24.44 |
September | 171.00 | 23.30 | 237.17 | 24.01 | 15.50 | 24.08 |
October | 446.50 | 22.42 | 36.83 | 22.40 | 20.67 | 22.33 |
November | 480.50 | 21.05 | 265.67 | 20.73 | 264.00 | 20.57 |
December | 497.00 | 20.12 | 477.17 | 20.08 | 477.17 | 20.07 |
Annual Sum or Average | 3935.33 | 21.27 | 3922.50 | 21.66 | 2285.17 | 21.38 |
Minimum of Months | 28.83 | 19.85 | 36.83 | 19.84 | 13.33 | 19.83 |
Maximum of Months | 513.17 | 26.01 | 493.17 | 24.62 | 493.17 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 496.83 | 19.70 | 496.83 | 19.70 |
February | 454.00 | 20.01 | 421.67 | 19.98 | 421.67 | 19.96 |
March | 514.00 | 20.84 | 321.67 | 20.65 | 321.67 | 20.56 |
April | 417.83 | 21.53 | 154.00 | 21.44 | 117.67 | 21.23 |
May | 208.33 | 23.09 | 181.17 | 23.59 | 1.33 | 23.58 |
June | 82.83 | 23.94 | 373.83 | 24.25 | 28.83 | 24.33 |
July | 31.00 | 25.09 | 472.67 | 24.41 | 29.50 | 24.45 |
August | 51.17 | 24.10 | 437.33 | 24.19 | 32.17 | 24.21 |
September | 218.17 | 22.79 | 174.00 | 23.44 | 5.17 | 23.41 |
October | 492.33 | 21.80 | 84.17 | 21.60 | 83.67 | 21.46 |
November | 489.00 | 20.71 | 300.33 | 20.40 | 300.33 | 20.26 |
December | 497.00 | 19.92 | 497.00 | 19.92 | 497.00 | 19.92 |
Annual Sum or Average | 3957.67 | 21.03 | 3914.67 | 21.42 | 2335.83 | 21.13 |
Minimum of Months | 31.00 | 19.70 | 84.17 | 19.70 | 1.33 | 19.70 |
Maximum of Months | 514.00 | 25.09 | 497.00 | 24.41 | 497.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.60 | 414.33 | 19.57 | 414.33 | 19.56 |
February | 385.00 | 20.04 | 336.83 | 19.93 | 336.83 | 19.89 |
March | 425.17 | 21.09 | 227.00 | 20.78 | 227.00 | 20.63 |
April | 319.83 | 21.83 | 131.67 | 21.90 | 83.83 | 21.69 |
May | 137.50 | 23.76 | 212.33 | 24.27 | 22.50 | 24.42 |
June | 84.50 | 24.77 | 334.33 | 24.57 | 45.17 | 24.73 |
July | 69.83 | 26.30 | 413.17 | 24.85 | 69.67 | 25.03 |
August | 52.50 | 25.11 | 391.33 | 24.44 | 44.00 | 24.53 |
September | 168.50 | 23.25 | 186.67 | 23.98 | 19.50 | 24.08 |
October | 397.67 | 22.17 | 47.17 | 22.03 | 41.83 | 21.89 |
November | 412.50 | 20.72 | 257.00 | 20.40 | 257.00 | 20.26 |
December | 422.00 | 19.82 | 417.17 | 19.81 | 417.17 | 19.81 |
Annual Sum or Average | 3302.00 | 21.26 | 3369.00 | 21.66 | 1978.83 | 21.40 |
Minimum of Months | 52.50 | 19.60 | 47.17 | 19.57 | 19.50 | 19.56 |
Maximum of Months | 427.00 | 26.30 | 417.17 | 24.85 | 417.17 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.50 | 20.29 | 397.67 | 20.04 | 397.67 | 19.94 |
February | 436.50 | 20.79 | 298.67 | 20.49 | 294.33 | 20.35 |
March | 456.50 | 21.37 | 236.50 | 21.12 | 222.83 | 20.94 |
April | 347.67 | 21.83 | 163.67 | 22.00 | 90.33 | 21.79 |
May | 160.17 | 23.14 | 227.33 | 23.87 | 6.50 | 23.90 |
June | 95.50 | 24.19 | 365.83 | 24.32 | 38.33 | 24.44 |
July | 60.67 | 25.62 | 469.83 | 24.57 | 53.17 | 24.69 |
August | 68.00 | 24.92 | 461.00 | 24.38 | 49.67 | 24.48 |
September | 179.83 | 23.44 | 244.50 | 24.08 | 26.50 | 24.20 |
October | 362.33 | 22.35 | 102.33 | 22.57 | 36.83 | 22.45 |
November | 447.50 | 21.17 | 244.17 | 20.90 | 222.17 | 20.67 |
December | 477.17 | 20.52 | 393.17 | 20.31 | 390.50 | 20.22 |
Annual Sum or Average | 3585.33 | 21.55 | 3604.67 | 21.98 | 1828.83 | 21.70 |
Minimum of Months | 60.67 | 20.29 | 102.33 | 20.04 | 6.50 | 19.94 |
Maximum of Months | 493.50 | 25.62 | 469.83 | 24.57 | 397.67 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 481.33 | 19.79 | 481.33 | 19.78 |
February | 450.50 | 20.28 | 376.67 | 20.14 | 376.67 | 20.09 |
March | 490.00 | 21.07 | 276.00 | 20.82 | 274.33 | 20.69 |
April | 360.33 | 21.74 | 164.17 | 21.86 | 99.17 | 21.65 |
May | 171.67 | 23.31 | 239.00 | 23.92 | 13.83 | 23.99 |
June | 93.33 | 24.27 | 394.00 | 24.36 | 39.50 | 24.48 |
July | 64.67 | 25.94 | 479.50 | 24.65 | 61.17 | 24.79 |
August | 66.00 | 24.83 | 471.83 | 24.36 | 49.67 | 24.44 |
September | 198.50 | 23.14 | 222.83 | 23.83 | 21.17 | 23.90 |
October | 438.00 | 21.99 | 83.50 | 21.90 | 62.67 | 21.74 |
November | 477.83 | 20.83 | 282.67 | 20.52 | 279.00 | 20.36 |
December | 497.00 | 20.05 | 467.00 | 19.99 | 467.00 | 19.97 |
Annual Sum or Average | 3809.83 | 21.26 | 3938.50 | 21.69 | 2225.50 | 21.42 |
Minimum of Months | 64.67 | 19.84 | 83.50 | 19.79 | 13.83 | 19.78 |
Maximum of Months | 502.00 | 25.94 | 481.33 | 24.65 | 481.33 | 24.79 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.18565 | 14.04255 | -0.6101 | 13.96022 |
February | 454.00000 | 21.80197 | 17.93174 | -0.4244 | 9.76974 |
March | 514.00000 | 22.78551 | 22.81230 | -0.1445 | 6.69908 |
April | 485.00000 | 23.58058 | 29.22461 | 0.11849 | 6.23884 |
May | 508.00000 | 24.25378 | 41.34776 | -0.4815 | 10.44093 |
June | 496.00000 | 24.28549 | 48.20017 | -0.3750 | 8.27055 |
July | 497.00000 | 24.37043 | 52.40552 | -0.3052 | 7.31151 |
August | 514.00000 | 24.31895 | 51.47754 | -0.3279 | 7.56921 |
September | 485.00000 | 24.30986 | 37.94862 | -0.4521 | 9.92995 |
October | 502.00000 | 24.00011 | 27.85681 | 0.22298 | 6.23845 |
November | 489.00000 | 23.00134 | 24.40966 | -0.0705 | 7.43219 |
December | 497.00000 | 21.76875 | 16.23346 | -0.4425 | 9.96922 |
Annual Sum or Average | 5943.00000 | 23.31571 | 32.12188 | -0.2740 | 8.64547 |
Minimum of Months | 454.00000 | 21.18565 | 14.04255 | -0.6101 | 6.23845 |
Maximum of Months | 514.00000 | 24.37043 | 52.40552 | 0.22298 | 13.96022 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.55635 | 14.34874 | -0.7662 | 18.77500 |
February | 454.00000 | 20.98351 | 18.62670 | -0.6183 | 14.14312 |
March | 514.00000 | 21.87624 | 23.89777 | -0.3493 | 9.10476 |
April | 485.00000 | 22.84017 | 30.79405 | -0.0428 | 6.98567 |
May | 508.00000 | 23.95922 | 42.60567 | -0.5715 | 12.55589 |
June | 496.00000 | 24.17841 | 49.04156 | -0.4171 | 9.06791 |
July | 497.00000 | 24.29916 | 52.93498 | -0.3371 | 7.68830 |
August | 514.00000 | 24.23654 | 52.13118 | -0.3694 | 8.10093 |
September | 485.00000 | 24.05469 | 39.10329 | -0.5527 | 12.55157 |
October | 502.00000 | 23.15330 | 30.13376 | 0.02276 | 5.67532 |
November | 489.00000 | 21.89218 | 26.12830 | -0.3325 | 10.34803 |
December | 497.00000 | 20.84190 | 16.87324 | -0.6665 | 15.41179 |
Annual Sum or Average | 5943.00000 | 22.75263 | 33.18283 | -0.4157 | 10.84155 |
Minimum of Months | 454.00000 | 20.55635 | 14.34874 | -0.7662 | 5.67532 |
Maximum of Months | 514.00000 | 24.29916 | 52.93498 | 0.02276 | 18.77500 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17059 | 14.58122 | -0.8909 | 23.84363 |
February | 454.00000 | 20.50877 | 19.10169 | -0.7600 | 19.00667 |
March | 514.00000 | 21.37603 | 24.35843 | -0.4865 | 11.81283 |
April | 485.00000 | 22.35977 | 31.43532 | -0.1623 | 8.64337 |
May | 508.00000 | 23.79865 | 42.89736 | -0.6259 | 14.46992 |
June | 496.00000 | 24.09245 | 49.35138 | -0.4401 | 9.88721 |
July | 497.00000 | 24.25607 | 53.15970 | -0.3442 | 7.83608 |
August | 514.00000 | 24.15950 | 52.38844 | -0.3937 | 8.53434 |
September | 485.00000 | 23.72631 | 39.84442 | -0.6722 | 16.73051 |
October | 502.00000 | 22.26193 | 31.33854 | -0.1963 | 7.19811 |
November | 489.00000 | 21.12317 | 26.65513 | -0.5393 | 14.68645 |
December | 497.00000 | 20.32823 | 17.12893 | -0.8238 | 21.07825 |
Annual Sum or Average | 5943.00000 | 22.36182 | 33.64974 | -0.5264 | 13.59307 |
Minimum of Months | 454.00000 | 20.17059 | 14.58122 | -0.8909 | 7.19811 |
Maximum of Months | 514.00000 | 24.25607 | 53.15970 | -0.1623 | 23.84363 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.60921 | 14.41943 | -1.1132 | 33.19963 |
February | 454.00000 | 19.81554 | 19.47502 | -0.9868 | 28.08444 |
March | 514.00000 | 20.60273 | 25.51099 | -0.6926 | 17.46356 |
April | 485.00000 | 21.54552 | 32.80701 | -0.3512 | 12.57712 |
May | 508.00000 | 23.45406 | 43.83089 | -0.7176 | 18.80257 |
June | 496.00000 | 24.01309 | 50.39553 | -0.4198 | 11.06921 |
July | 497.00000 | 24.26959 | 54.50103 | -0.2922 | 7.77772 |
August | 514.00000 | 24.02872 | 53.77203 | -0.3987 | 9.25814 |
September | 485.00000 | 23.19375 | 41.59897 | -0.8301 | 24.00717 |
October | 502.00000 | 21.19473 | 33.42083 | -0.4415 | 11.24044 |
November | 489.00000 | 20.22692 | 28.14237 | -0.7777 | 22.09592 |
December | 497.00000 | 19.72323 | 17.54154 | -1.0432 | 30.12320 |
Annual Sum or Average | 5943.00000 | 21.82391 | 34.75095 | -0.6695 | 18.71467 |
Minimum of Months | 454.00000 | 19.60921 | 14.41943 | -1.1132 | 7.77772 |
Maximum of Months | 514.00000 | 24.26959 | 54.50103 | -0.2922 | 33.19963 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71263 | 15.38060 | -1.0632 | 31.20787 |
February | 454.00000 | 19.97673 | 20.40023 | -0.9150 | 25.68307 |
March | 514.00000 | 20.98449 | 25.97355 | -0.5718 | 15.44605 |
April | 485.00000 | 22.14787 | 32.36849 | -0.1835 | 11.85848 |
May | 508.00000 | 23.93223 | 42.60799 | -0.5021 | 13.76863 |
June | 496.00000 | 24.16814 | 49.73330 | -0.2900 | 9.92458 |
July | 497.00000 | 24.45682 | 53.60918 | -0.1433 | 7.48123 |
August | 514.00000 | 24.18751 | 52.96141 | -0.2737 | 8.00207 |
September | 485.00000 | 23.63731 | 40.56607 | -0.6239 | 19.00318 |
October | 502.00000 | 21.80220 | 33.36884 | -0.2847 | 9.27245 |
November | 489.00000 | 20.42363 | 28.90165 | -0.7185 | 20.41301 |
December | 497.00000 | 19.80956 | 18.34584 | -1.0048 | 28.55942 |
Annual Sum or Average | 5943.00000 | 22.12125 | 34.64360 | -0.5450 | 16.62674 |
Minimum of Months | 454.00000 | 19.71263 | 15.38060 | -1.0632 | 7.48123 |
Maximum of Months | 514.00000 | 24.45682 | 53.60918 | -0.1433 | 31.20787 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11530 | 14.63909 | -0.9095 | 27.28973 |
February | 454.00000 | 20.56560 | 18.96528 | -0.7335 | 21.48328 |
March | 514.00000 | 21.37999 | 24.27679 | -0.4658 | 14.32999 |
April | 485.00000 | 22.19483 | 31.25974 | -0.1661 | 12.37772 |
May | 508.00000 | 23.69228 | 42.93209 | -0.6061 | 16.63598 |
June | 496.00000 | 24.03031 | 50.16651 | -0.3849 | 11.01960 |
July | 497.00000 | 24.32642 | 54.11602 | -0.2319 | 7.93150 |
August | 514.00000 | 24.14686 | 52.95654 | -0.2970 | 8.63684 |
September | 485.00000 | 23.65709 | 39.98203 | -0.5931 | 18.83943 |
October | 502.00000 | 22.32284 | 30.70904 | -0.1369 | 9.62821 |
November | 489.00000 | 20.94630 | 27.32499 | -0.5707 | 17.86476 |
December | 497.00000 | 20.36697 | 17.04155 | -0.8336 | 24.32889 |
Annual Sum or Average | 5943.00000 | 22.32707 | 33.82879 | -0.4923 | 15.80306 |
Minimum of Months | 454.00000 | 20.11530 | 14.63909 | -0.9095 | 7.93150 |
Maximum of Months | 514.00000 | 24.32642 | 54.11602 | -0.1369 | 27.28973 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.74249 | 15.17788 | -1.0610 | 31.26829 |
February | 454.00000 | 20.09219 | 20.07923 | -0.8946 | 25.27704 |
March | 514.00000 | 20.95366 | 25.80876 | -0.5886 | 15.94435 |
April | 485.00000 | 22.04485 | 32.25758 | -0.2012 | 12.67568 |
May | 508.00000 | 23.66918 | 43.47876 | -0.6004 | 16.91190 |
June | 496.00000 | 24.07641 | 50.23824 | -0.3316 | 10.82400 |
July | 497.00000 | 24.38046 | 54.12029 | -0.1777 | 7.93770 |
August | 514.00000 | 24.15137 | 53.32087 | -0.2832 | 8.46082 |
September | 485.00000 | 23.46027 | 41.26741 | -0.6891 | 21.32356 |
October | 502.00000 | 21.66172 | 33.02323 | -0.3148 | 10.58063 |
November | 489.00000 | 20.43754 | 28.77064 | -0.7157 | 20.69997 |
December | 497.00000 | 19.84719 | 18.26551 | -0.9974 | 28.53482 |
Annual Sum or Average | 5943.00000 | 22.05985 | 34.77959 | -0.5688 | 17.45363 |
Minimum of Months | 454.00000 | 19.74249 | 15.17788 | -1.0610 | 7.93770 |
Maximum of Months | 514.00000 | 24.38046 | 54.12029 | -0.1777 | 31.26829 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.66911 | 14.62933 | -1.0873 | 31.74932 |
February | 454.00000 | 19.95233 | 19.68591 | -0.9592 | 26.27004 |
March | 514.00000 | 20.55190 | 26.12070 | -0.7250 | 17.48441 |
April | 485.00000 | 21.19737 | 34.26018 | -0.4631 | 12.20973 |
May | 508.00000 | 22.97967 | 46.17645 | -0.9287 | 25.49354 |
June | 496.00000 | 23.89527 | 51.09998 | -0.5126 | 11.93356 |
July | 497.00000 | 24.19374 | 54.71364 | -0.3602 | 8.11131 |
August | 514.00000 | 24.08594 | 53.59279 | -0.4052 | 8.76591 |
September | 485.00000 | 23.56418 | 41.02614 | -0.7101 | 18.19759 |
October | 502.00000 | 21.90673 | 32.50418 | -0.2561 | 7.50736 |
November | 489.00000 | 20.82139 | 27.67180 | -0.6087 | 16.16181 |
December | 497.00000 | 19.99338 | 17.73130 | -0.9508 | 25.68753 |
Annual Sum or Average | 5943.00000 | 21.91671 | 35.07065 | -0.6621 | 17.40612 |
Minimum of Months | 454.00000 | 19.66911 | 14.62933 | -1.0873 | 7.50736 |
Maximum of Months | 514.00000 | 24.19374 | 54.71364 | -0.2561 | 31.74932 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84324 | 15.59427 | -1.0256 | 29.14620 |
February | 454.00000 | 20.16490 | 20.63621 | -0.8772 | 23.09617 |
March | 514.00000 | 20.92601 | 26.67832 | -0.6020 | 14.80294 |
April | 485.00000 | 21.93412 | 33.61676 | -0.2618 | 10.56380 |
May | 508.00000 | 23.82810 | 43.94235 | -0.5972 | 15.20412 |
June | 496.00000 | 24.17124 | 49.79738 | -0.3389 | 9.57900 |
July | 497.00000 | 24.46959 | 53.34695 | -0.1776 | 7.01864 |
August | 514.00000 | 24.27505 | 52.48392 | -0.2619 | 7.18350 |
September | 485.00000 | 24.03483 | 39.72340 | -0.4885 | 13.35326 |
October | 502.00000 | 22.74131 | 31.95470 | -0.0505 | 6.41389 |
November | 489.00000 | 21.08506 | 28.34450 | -0.5338 | 14.79813 |
December | 497.00000 | 20.09512 | 18.62418 | -0.9094 | 24.07893 |
Annual Sum or Average | 5943.00000 | 22.31423 | 34.68789 | -0.5080 | 14.53883 |
Minimum of Months | 454.00000 | 19.84324 | 15.59427 | -1.0256 | 6.41389 |
Maximum of Months | 514.00000 | 24.46959 | 53.34695 | -0.0505 | 29.14620 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.82631 | 13.14279 | -1.1482 | 34.87651 |
February | 454.00000 | 19.65164 | 17.58463 | -0.9014 | 25.11350 |
March | 514.00000 | 20.58363 | 23.37375 | -0.6323 | 16.83500 |
April | 485.00000 | 21.55881 | 31.22601 | -0.3224 | 12.14645 |
May | 508.00000 | 22.99888 | 44.98710 | -0.8628 | 24.14748 |
June | 496.00000 | 23.72309 | 51.75299 | -0.5191 | 13.60833 |
July | 497.00000 | 24.22890 | 55.80686 | -0.2900 | 8.02340 |
August | 514.00000 | 24.15095 | 54.04048 | -0.2968 | 8.14866 |
September | 485.00000 | 23.78560 | 39.07923 | -0.5246 | 16.24178 |
October | 502.00000 | 22.73574 | 28.76624 | 0.00301 | 7.40406 |
November | 489.00000 | 20.93931 | 25.21717 | -0.5096 | 15.89994 |
December | 497.00000 | 19.66190 | 15.64255 | -0.9272 | 26.37198 |
Annual Sum or Average | 5943.00000 | 21.92070 | 33.53108 | -0.5759 | 17.35192 |
Minimum of Months | 454.00000 | 18.82631 | 13.14279 | -1.1482 | 7.40406 |
Maximum of Months | 514.00000 | 24.22890 | 55.80686 | 0.00301 | 34.87651 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.85227 | 15.44601 | -1.0278 | 29.31044 |
February | 454.00000 | 20.24085 | 20.48424 | -0.8621 | 22.80292 |
March | 514.00000 | 20.89687 | 26.65325 | -0.6165 | 15.26753 |
April | 485.00000 | 21.97782 | 33.28814 | -0.2446 | 10.68871 |
May | 508.00000 | 23.55219 | 44.87905 | -0.7017 | 18.32969 |
June | 496.00000 | 24.09666 | 50.24030 | -0.3755 | 10.24034 |
July | 497.00000 | 24.46006 | 53.53031 | -0.1879 | 7.04595 |
August | 514.00000 | 24.29802 | 52.55708 | -0.2521 | 7.09452 |
September | 485.00000 | 23.95121 | 40.13369 | -0.5255 | 14.41309 |
October | 502.00000 | 22.60793 | 31.66294 | -0.0781 | 6.81195 |
November | 489.00000 | 21.10663 | 28.20476 | -0.5283 | 14.97459 |
December | 497.00000 | 20.11656 | 18.60128 | -0.9048 | 24.06639 |
Annual Sum or Average | 5943.00000 | 22.27870 | 34.76889 | -0.5234 | 15.03122 |
Minimum of Months | 454.00000 | 19.85227 | 15.44601 | -1.0278 | 6.81195 |
Maximum of Months | 514.00000 | 24.46006 | 53.53031 | -0.0781 | 29.31044 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70440 | 14.87039 | -1.0468 | 30.30491 |
February | 454.00000 | 20.01445 | 19.67742 | -0.9016 | 24.31871 |
March | 514.00000 | 20.84463 | 25.51701 | -0.6057 | 14.89037 |
April | 485.00000 | 21.89742 | 32.53801 | -0.2537 | 10.12256 |
May | 508.00000 | 23.68377 | 43.42209 | -0.6436 | 15.61796 |
June | 496.00000 | 24.15172 | 49.94754 | -0.3818 | 9.50876 |
July | 497.00000 | 24.33852 | 54.05085 | -0.2777 | 7.31624 |
August | 514.00000 | 24.14116 | 53.28229 | -0.3651 | 8.23832 |
September | 485.00000 | 23.57293 | 40.85980 | -0.6979 | 18.35388 |
October | 502.00000 | 21.83985 | 32.62731 | -0.2689 | 8.13963 |
November | 489.00000 | 20.70711 | 27.74096 | -0.6322 | 17.55920 |
December | 497.00000 | 19.91817 | 17.79495 | -0.9531 | 26.13412 |
Annual Sum or Average | 5943.00000 | 22.08473 | 34.49155 | -0.5835 | 15.80021 |
Minimum of Months | 454.00000 | 19.70440 | 14.87039 | -1.0468 | 7.31624 |
Maximum of Months | 514.00000 | 24.33852 | 54.05085 | -0.2537 | 30.30491 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.59659 | 15.28975 | -1.0496 | 30.68769 |
February | 385.00000 | 20.03723 | 20.10730 | -0.8682 | 23.51383 |
March | 433.00000 | 21.14577 | 25.59023 | -0.5133 | 13.71536 |
April | 410.00000 | 22.41199 | 31.55809 | -0.1125 | 10.43756 |
May | 430.00000 | 24.07701 | 42.01399 | -0.4643 | 12.59243 |
June | 418.00000 | 24.32785 | 49.01456 | -0.2623 | 9.12042 |
July | 422.00000 | 24.59096 | 52.84115 | -0.1265 | 7.38697 |
August | 433.00000 | 24.30980 | 52.33800 | -0.2555 | 7.60211 |
September | 410.00000 | 23.89950 | 39.68448 | -0.5401 | 15.88514 |
October | 427.00000 | 22.30532 | 31.90542 | -0.1513 | 7.46308 |
November | 417.00000 | 20.75353 | 27.76161 | -0.6132 | 17.30642 |
December | 422.00000 | 19.81978 | 18.16818 | -0.9592 | 26.53322 |
Annual Sum or Average | 5034.00000 | 22.28727 | 33.95762 | -0.4908 | 15.12200 |
Minimum of Months | 385.00000 | 19.59659 | 15.28975 | -1.0496 | 7.38697 |
Maximum of Months | 433.00000 | 24.59096 | 52.84115 | -0.1125 | 30.68769 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35628 | 14.74500 | -0.8175 | 23.72889 |
February | 454.00000 | 20.91563 | 18.77437 | -0.6214 | 17.61586 |
March | 514.00000 | 21.69124 | 23.92942 | -0.3684 | 11.95730 |
April | 485.00000 | 22.53193 | 30.78007 | -0.0731 | 10.30013 |
May | 508.00000 | 23.87695 | 42.50949 | -0.5447 | 13.90321 |
June | 496.00000 | 24.15566 | 49.64915 | -0.3510 | 9.47302 |
July | 497.00000 | 24.39610 | 53.56346 | -0.2182 | 7.33653 |
August | 514.00000 | 24.24495 | 52.45522 | -0.2682 | 7.70403 |
September | 485.00000 | 23.94870 | 39.24903 | -0.4861 | 14.53042 |
October | 502.00000 | 22.89886 | 29.68499 | 0.01889 | 8.01057 |
November | 489.00000 | 21.47172 | 26.61743 | -0.4176 | 14.48582 |
December | 497.00000 | 20.66617 | 16.92601 | -0.7252 | 20.49612 |
Annual Sum or Average | 5943.00000 | 22.60986 | 33.37090 | -0.4047 | 13.25212 |
Minimum of Months | 454.00000 | 20.35628 | 14.74500 | -0.8175 | 7.33653 |
Maximum of Months | 514.00000 | 24.39610 | 53.56346 | 0.01889 | 23.72889 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83539 | 15.61657 | -0.9957 | 28.50423 |
February | 454.00000 | 20.30528 | 20.15604 | -0.8077 | 21.73078 |
March | 514.00000 | 21.21367 | 25.58586 | -0.5001 | 13.46889 |
April | 485.00000 | 22.38564 | 31.77859 | -0.1073 | 10.42482 |
May | 508.00000 | 23.86585 | 43.01938 | -0.5357 | 14.00268 |
June | 496.00000 | 24.20280 | 49.71996 | -0.2973 | 9.24179 |
July | 497.00000 | 24.45265 | 53.59504 | -0.1629 | 7.34811 |
August | 514.00000 | 24.24713 | 52.82015 | -0.2547 | 7.55304 |
September | 485.00000 | 23.78906 | 40.47633 | -0.5713 | 16.37283 |
October | 502.00000 | 22.27080 | 31.95279 | -0.1518 | 7.95359 |
November | 489.00000 | 20.91305 | 28.22535 | -0.5721 | 16.53820 |
December | 497.00000 | 20.04988 | 18.49521 | -0.9063 | 24.69562 |
Annual Sum or Average | 5943.00000 | 22.31031 | 34.41376 | -0.4864 | 14.75348 |
Minimum of Months | 454.00000 | 19.83539 | 15.61657 | -0.9957 | 7.34811 |
Maximum of Months | 514.00000 | 24.45265 | 53.59504 | -0.1073 | 28.50423 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.116292E+09 | 30313739.60 | 11.00 | 94216212.00 | 22075882.17 | 0.00 | 0.23 | 25-MAR-15:00 | 0.00 | 01-MAR-00:05 | 6111.36 | 25-MAR-15:00 | 5181.06 | 25-MAR-15:00 | 988.19 | 25-MAR-15:30 | 1559.74 | 25-MAR-15:00 | 0.00 |
April | 0.453814E+10 | 0.107040E+10 | 88.67 | 0.345747E+10 | 0.108067E+10 | 0.00 | 1.00 | 18-APR-08:50 | 0.00 | 01-APR-00:10 | 58380.17 | 18-APR-12:00 | 45089.10 | 18-APR-15:10 | 18606.63 | 18-APR-12:00 | 13142.20 | 18-APR-12:00 | 0.00 |
May | 0.115077E+11 | 0.267265E+10 | 216.51 | 0.857268E+10 | 0.293506E+10 | 0.00 | 1.00 | 05-MAY-14:05 | 0.00 | 01-MAY-00:10 | 57668.10 | 31-MAY-12:00 | 49705.96 | 31-MAY-15:10 | 23010.89 | 30-MAY-10:00 | 13600.68 | 31-MAY-12:00 | 0.00 |
June | 0.381478E+11 | 0.861439E+10 | 342.64 | 0.280170E+11 | 0.101309E+11 | 0.00 | 1.00 | 09-JUN-09:20 | 0.00 | 01-JUN-00:10 | 111510.90 | 26-JUN-07:50 | 62313.65 | 26-JUN-15:30 | 64549.61 | 26-JUN-06:03 | 22931.47 | 26-JUN-07:50 | 0.00 |
July | 0.547012E+11 | 0.119934E+11 | 429.18 | 0.366766E+11 | 0.180245E+11 | 0.00 | 1.00 | 02-JUL-08:42 | 0.00 | 01-JUL-00:10 | 102796.16 | 05-JUL-06:03 | 60673.29 | 03-JUL-15:10 | 61961.41 | 05-JUL-06:03 | 21445.70 | 05-JUL-06:03 | 0.00 |
August | 0.538375E+11 | 0.118767E+11 | 420.84 | 0.370471E+11 | 0.167904E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 112608.62 | 04-AUG-06:03 | 62316.49 | 04-AUG-15:30 | 81146.77 | 04-AUG-07:00 | 23168.77 | 04-AUG-12:03 | 0.00 |
September | 0.222536E+11 | 0.511587E+10 | 251.53 | 0.196330E+11 | 0.262059E+10 | 0.00 | 1.00 | 01-SEP-11:50 | 0.00 | 01-SEP-00:10 | 89334.05 | 11-SEP-09:50 | 59030.14 | 07-SEP-15:50 | 41113.87 | 11-SEP-06:03 | 18865.59 | 11-SEP-09:50 | 0.00 |
October | 0.125403E+10 | 0.305972E+09 | 53.03 | 0.106579E+10 | 0.188240E+09 | 0.00 | 0.88 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 27907.64 | 20-OCT-15:00 | 27907.64 | 20-OCT-15:00 | 4418.74 | 02-OCT-15:00 | 6005.14 | 20-OCT-15:00 | 0.00 |
November | 42421124.71 | 11153333.54 | 5.67 | 37773063.14 | 4648061.56 | 0.00 | 0.14 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3632.49 | 03-NOV-14:00 | 3457.58 | 03-NOV-15:00 | 486.95 | 03-NOV-12:10 | 947.13 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.186399E+12 | 0.416909E+11 | 1819.07 | 0.134602E+12 | 0.517971E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.547012E+11 | 0.119934E+11 | 429.18 | 0.370471E+11 | 0.180245E+11 | 0.00 | 1.00 | 0.00 | 112608.62 | 62316.49 | 81146.77 | 23168.77 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.127795E+09 | 33173470.33 | 11.00 | 0.109301E+09 | 18494391.10 | 0.00 | 0.27 | 25-MAR-15:00 | 0.00 | 01-MAR-00:05 | 7086.62 | 25-MAR-15:00 | 6596.12 | 25-MAR-15:00 | 916.90 | 25-MAR-15:50 | 1791.35 | 25-MAR-15:00 | 0.00 |
April | 0.511804E+10 | 0.118538E+10 | 80.33 | 0.398167E+10 | 0.113638E+10 | 0.00 | 1.00 | 15-APR-13:10 | 0.00 | 01-APR-00:10 | 64477.73 | 18-APR-12:30 | 52078.70 | 18-APR-15:00 | 22223.92 | 18-APR-09:30 | 14490.03 | 18-APR-12:30 | 0.00 |
May | 0.134609E+11 | 0.310255E+10 | 240.58 | 0.100100E+11 | 0.345096E+10 | 0.00 | 1.00 | 04-MAY-14:05 | 0.00 | 01-MAY-00:10 | 66525.00 | 30-MAY-11:00 | 54454.34 | 31-MAY-14:05 | 30046.83 | 30-MAY-10:05 | 14453.79 | 31-MAY-14:05 | 0.00 |
June | 0.394593E+11 | 0.887444E+10 | 347.90 | 0.291128E+11 | 0.103465E+11 | 0.00 | 1.00 | 08-JUN-15:20 | 0.00 | 01-JUN-00:10 | 109290.78 | 26-JUN-07:55 | 63821.56 | 26-JUN-14:05 | 63544.30 | 26-JUN-07:10 | 22524.58 | 26-JUN-07:55 | 0.00 |
July | 0.539496E+11 | 0.118224E+11 | 434.25 | 0.361654E+11 | 0.177842E+11 | 0.00 | 1.00 | 01-JUL-08:40 | 0.00 | 01-JUL-00:10 | 107279.89 | 03-JUL-08:50 | 63262.20 | 02-JUL-16:31 | 60894.58 | 05-JUL-06:03 | 22218.63 | 03-JUL-08:50 | 0.00 |
August | 0.502978E+11 | 0.111200E+11 | 423.73 | 0.346391E+11 | 0.156587E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 110192.79 | 04-AUG-06:03 | 64343.63 | 04-AUG-15:10 | 78472.02 | 04-AUG-07:05 | 22860.54 | 04-AUG-14:05 | 0.00 |
September | 0.203387E+11 | 0.468356E+10 | 237.05 | 0.178897E+11 | 0.244900E+10 | 0.00 | 1.00 | 01-SEP-11:00 | 0.00 | 01-SEP-00:10 | 80184.41 | 11-SEP-06:03 | 59929.26 | 07-SEP-16:00 | 40020.13 | 11-SEP-06:03 | 18159.19 | 06-SEP-14:05 | 0.00 |
October | 0.116070E+10 | 0.283993E+09 | 49.17 | 0.975088E+09 | 0.185609E+09 | 0.00 | 0.85 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 26446.31 | 20-OCT-15:00 | 26446.31 | 20-OCT-15:00 | 4144.92 | 02-OCT-15:00 | 5727.03 | 20-OCT-15:00 | 0.00 |
November | 64290289.50 | 16625296.99 | 5.50 | 54071156.88 | 10219132.62 | 0.00 | 0.23 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 | 5909.86 | 03-NOV-13:30 | 4869.43 | 03-NOV-14:05 | 1266.83 | 03-NOV-13:00 | 1509.24 | 03-NOV-13:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.183977E+12 | 0.411221E+11 | 1829.49 | 0.132937E+12 | 0.510401E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.539496E+11 | 0.118224E+11 | 434.25 | 0.361654E+11 | 0.177842E+11 | 0.00 | 1.00 | 0.00 | 110192.79 | 64343.63 | 78472.02 | 22860.54 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.130721E+09 | 34036167.74 | 11.00 | 0.107656E+09 | 23064909.02 | 0.00 | 0.24 | 25-MAR-15:00 | 0.00 | 01-MAR-00:05 | 7182.26 | 25-MAR-15:00 | 6334.82 | 25-MAR-15:00 | 1079.25 | 25-MAR-15:40 | 1825.73 | 25-MAR-15:00 | 0.00 |
April | 0.559596E+10 | 0.129824E+10 | 82.73 | 0.436753E+10 | 0.122843E+10 | 0.00 | 1.00 | 15-APR-13:20 | 0.00 | 01-APR-00:10 | 71540.00 | 16-APR-13:42 | 58620.72 | 18-APR-15:00 | 26659.85 | 16-APR-13:42 | 15798.99 | 16-APR-13:42 | 0.00 |
May | 0.144017E+11 | 0.332858E+10 | 241.27 | 0.107951E+11 | 0.360654E+10 | 0.00 | 1.00 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 | 68738.95 | 30-MAY-14:00 | 61655.48 | 31-MAY-15:00 | 27550.55 | 30-MAY-10:00 | 15972.36 | 31-MAY-15:00 | 0.00 |
June | 0.423218E+11 | 0.955151E+10 | 348.95 | 0.315991E+11 | 0.107227E+11 | 0.00 | 1.00 | 08-JUN-15:30 | 0.00 | 01-JUN-00:10 | 118246.47 | 26-JUN-06:03 | 78538.92 | 18-JUN-16:11 | 70369.63 | 26-JUN-06:03 | 24390.56 | 26-JUN-06:03 | 0.00 |
July | 0.569730E+11 | 0.125285E+11 | 434.80 | 0.383399E+11 | 0.186332E+11 | 0.00 | 1.00 | 01-JUL-12:50 | 0.00 | 01-JUL-00:10 | 108307.92 | 05-JUL-06:03 | 68352.63 | 02-JUL-15:22 | 65298.42 | 05-JUL-06:03 | 22599.30 | 05-JUL-06:03 | 0.00 |
August | 0.519366E+11 | 0.115496E+11 | 423.44 | 0.362458E+11 | 0.156907E+11 | 0.00 | 1.00 | 01-AUG-07:30 | 0.00 | 01-AUG-00:10 | 122888.60 | 04-AUG-06:03 | 73698.39 | 04-AUG-15:10 | 87527.30 | 04-AUG-07:10 | 24994.84 | 04-AUG-15:30 | 0.00 |
September | 0.208780E+11 | 0.484343E+10 | 233.54 | 0.182921E+11 | 0.258584E+10 | 0.00 | 1.00 | 01-SEP-12:05 | 0.00 | 01-SEP-00:10 | 80749.09 | 11-SEP-10:00 | 67297.08 | 07-SEP-15:50 | 30929.59 | 11-SEP-10:00 | 18930.86 | 06-SEP-14:00 | 0.00 |
October | 0.113308E+10 | 0.280362E+09 | 48.17 | 0.928267E+09 | 0.204808E+09 | 0.00 | 0.77 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 25795.55 | 20-OCT-15:00 | 25795.55 | 20-OCT-15:00 | 4065.06 | 02-OCT-15:00 | 5726.67 | 20-OCT-15:00 | 0.00 |
November | 37434905.75 | 9869529.05 | 4.67 | 31270865.11 | 6164040.64 | 0.00 | 0.12 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3346.37 | 03-NOV-14:00 | 2938.91 | 03-NOV-14:30 | 611.19 | 03-NOV-13:30 | 876.85 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.193408E+12 | 0.434241E+11 | 1828.56 | 0.140707E+12 | 0.527015E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.569730E+11 | 0.125285E+11 | 434.80 | 0.383399E+11 | 0.186332E+11 | 0.00 | 1.00 | 0.00 | 122888.60 | 78538.92 | 87527.30 | 24994.84 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.15 | 0.00 | 363.15 | 1.83 | 2897.32 | 0.00 | 0.00 | 0.00 |
February | 460.40 | 0.00 | 460.40 | 30.97 | 2317.47 | 0.00 | 0.00 | 0.00 |
March | 690.00 | 0.00 | 690.00 | 228.48 | 1468.91 | 0.00 | 0.00 | 0.00 |
April | 796.55 | 3.92 | 792.63 | 454.36 | 1012.47 | 0.00 | 0.00 | 0.00 |
May | 1038.72 | 39.04 | 999.68 | 917.41 | 603.18 | 0.00 | 0.00 | 0.00 |
June | 1214.03 | 110.19 | 1103.84 | 1387.36 | 415.55 | 0.00 | 0.00 | 0.00 |
July | 1138.57 | 76.16 | 1062.41 | 1358.82 | 363.45 | 0.00 | 0.00 | 0.00 |
August | 953.32 | 16.90 | 936.42 | 1132.46 | 425.29 | 0.00 | 0.00 | 0.00 |
September | 730.92 | 0.18 | 730.74 | 685.74 | 736.93 | 0.00 | 0.00 | 0.00 |
October | 543.45 | 0.00 | 543.45 | 269.30 | 1102.40 | 0.00 | 0.00 | 0.00 |
November | 380.15 | 0.00 | 380.15 | 67.61 | 1714.15 | 0.00 | 0.00 | 0.00 |
December | 246.59 | 0.00 | 246.59 | 0.54 | 2540.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 714.32 | 20.61 | 693.71 | 547.65 | 1295.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.59 | 0.00 | 246.59 | 0.54 | 363.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1214.03 | 110.19 | 1103.84 | 1387.36 | 2897.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.77 | 213.48 | 305.30 | 229.30 | 1743.36 | 0.00 | 0.00 | 0.00 |
February | 687.63 | 302.36 | 385.27 | 403.41 | 1372.69 | 0.00 | 0.00 | 0.00 |
March | 934.28 | 370.84 | 563.44 | 728.28 | 903.06 | 0.00 | 0.00 | 0.00 |
April | 1147.21 | 502.40 | 644.81 | 1105.72 | 654.16 | 0.00 | 0.00 | 0.00 |
May | 1440.80 | 629.56 | 811.23 | 1612.13 | 410.48 | 0.00 | 0.00 | 0.00 |
June | 1585.56 | 690.49 | 895.07 | 1975.24 | 281.77 | 0.00 | 0.00 | 0.00 |
July | 1602.59 | 739.47 | 863.12 | 2044.79 | 246.08 | 0.00 | 0.00 | 0.00 |
August | 1350.96 | 582.43 | 768.53 | 1727.12 | 285.40 | 0.00 | 0.00 | 0.00 |
September | 1204.93 | 569.39 | 635.54 | 1423.35 | 478.26 | 0.00 | 0.00 | 0.00 |
October | 767.87 | 320.73 | 447.13 | 690.89 | 695.80 | 0.00 | 0.00 | 0.00 |
November | 453.05 | 147.16 | 305.89 | 246.69 | 1064.44 | 0.00 | 0.00 | 0.00 |
December | 350.93 | 150.70 | 200.23 | 160.95 | 1566.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1005.28 | 435.54 | 569.74 | 1032.39 | 805.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 350.93 | 147.16 | 200.23 | 160.95 | 246.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1602.59 | 739.47 | 895.07 | 2044.79 | 1743.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2258.40 | 1545.48 | 712.93 | 2016.45 | 2364.25 | 0.00 | 0.00 | 0.00 |
February | 2419.84 | 1634.86 | 784.98 | 2253.86 | 1898.00 | 0.00 | 0.00 | 0.00 |
March | 2105.80 | 1108.85 | 996.96 | 2059.81 | 1374.32 | 0.00 | 0.00 | 0.00 |
April | 1897.19 | 886.97 | 1010.22 | 2062.90 | 1037.18 | 0.00 | 0.00 | 0.00 |
May | 1571.76 | 426.12 | 1145.63 | 1804.59 | 661.25 | 0.00 | 0.00 | 0.00 |
June | 1525.94 | 310.69 | 1215.25 | 1951.47 | 447.58 | 0.00 | 0.00 | 0.00 |
July | 1615.31 | 407.02 | 1208.30 | 2158.41 | 389.37 | 0.00 | 0.00 | 0.00 |
August | 1819.92 | 652.67 | 1167.25 | 2471.93 | 457.18 | 0.00 | 0.00 | 0.00 |
September | 2205.36 | 1162.04 | 1043.32 | 2796.45 | 750.57 | 0.00 | 0.00 | 0.00 |
October | 2302.86 | 1444.72 | 858.14 | 2567.11 | 1068.52 | 0.00 | 0.00 | 0.00 |
November | 1737.50 | 1087.71 | 649.79 | 1652.31 | 1527.36 | 0.00 | 0.00 | 0.00 |
December | 1852.79 | 1403.47 | 449.32 | 1777.94 | 2186.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1939.91 | 1002.29 | 937.62 | 2130.26 | 1176.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1525.94 | 310.69 | 449.32 | 1652.31 | 389.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2419.84 | 1634.86 | 1215.25 | 2796.45 | 2364.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.49 | 208.17 | 306.32 | 237.40 | 1785.45 | 0.00 | 0.00 | 0.00 |
February | 754.42 | 371.75 | 382.66 | 497.51 | 1423.05 | 0.00 | 0.00 | 0.00 |
March | 900.62 | 335.08 | 565.54 | 689.61 | 932.54 | 0.00 | 0.00 | 0.00 |
April | 1313.73 | 649.62 | 664.11 | 1348.98 | 680.14 | 0.00 | 0.00 | 0.00 |
May | 1317.53 | 526.32 | 791.21 | 1478.37 | 432.08 | 0.00 | 0.00 | 0.00 |
June | 1545.97 | 669.98 | 875.98 | 1936.78 | 301.43 | 0.00 | 0.00 | 0.00 |
July | 1659.90 | 788.48 | 871.42 | 2140.31 | 267.97 | 0.00 | 0.00 | 0.00 |
August | 1451.17 | 665.99 | 785.18 | 1882.00 | 306.57 | 0.00 | 0.00 | 0.00 |
September | 1174.68 | 557.56 | 617.12 | 1393.43 | 498.97 | 0.00 | 0.00 | 0.00 |
October | 818.57 | 363.93 | 454.64 | 773.39 | 725.32 | 0.00 | 0.00 | 0.00 |
November | 489.97 | 181.19 | 308.78 | 309.75 | 1089.20 | 0.00 | 0.00 | 0.00 |
December | 376.81 | 177.63 | 199.18 | 207.90 | 1600.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1027.58 | 458.06 | 569.51 | 1077.47 | 834.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.81 | 177.63 | 199.18 | 207.90 | 267.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.90 | 788.48 | 875.98 | 2140.31 | 1785.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.04 | 0.00 | 121.04 | 0.69 | 964.58 | 0.00 | 0.00 | 0.00 |
February | 153.46 | 0.00 | 153.46 | 10.74 | 773.18 | 0.00 | 0.00 | 0.00 |
March | 229.99 | 0.00 | 229.99 | 82.95 | 486.42 | 0.00 | 0.00 | 0.00 |
April | 265.51 | 1.31 | 264.20 | 165.19 | 327.06 | 0.00 | 0.00 | 0.00 |
May | 346.22 | 13.01 | 333.21 | 325.78 | 188.97 | 0.00 | 0.00 | 0.00 |
June | 404.66 | 36.73 | 367.93 | 474.69 | 134.09 | 0.00 | 0.00 | 0.00 |
July | 379.50 | 25.38 | 354.12 | 462.35 | 118.63 | 0.00 | 0.00 | 0.00 |
August | 317.76 | 5.63 | 312.13 | 381.75 | 143.75 | 0.00 | 0.00 | 0.00 |
September | 243.63 | 0.06 | 243.57 | 227.73 | 259.38 | 0.00 | 0.00 | 0.00 |
October | 181.14 | 0.00 | 181.14 | 83.82 | 397.59 | 0.00 | 0.00 | 0.00 |
November | 126.71 | 0.00 | 126.71 | 20.14 | 602.41 | 0.00 | 0.00 | 0.00 |
December | 82.19 | 0.00 | 82.19 | 0.09 | 863.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.10 | 6.87 | 231.23 | 187.38 | 436.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.19 | 0.00 | 82.19 | 0.09 | 118.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.66 | 36.73 | 367.93 | 474.69 | 964.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.05 | 0.00 | 121.05 | 0.69 | 964.65 | 0.00 | 0.00 | 0.00 |
February | 153.47 | 0.00 | 153.47 | 10.74 | 773.23 | 0.00 | 0.00 | 0.00 |
March | 230.00 | 0.00 | 230.00 | 82.95 | 486.45 | 0.00 | 0.00 | 0.00 |
April | 265.52 | 1.31 | 264.21 | 165.19 | 327.08 | 0.00 | 0.00 | 0.00 |
May | 346.24 | 13.01 | 333.22 | 325.79 | 188.98 | 0.00 | 0.00 | 0.00 |
June | 404.67 | 36.73 | 367.94 | 474.70 | 134.09 | 0.00 | 0.00 | 0.00 |
July | 379.52 | 25.39 | 354.13 | 462.37 | 118.63 | 0.00 | 0.00 | 0.00 |
August | 317.77 | 5.63 | 312.14 | 381.76 | 143.75 | 0.00 | 0.00 | 0.00 |
September | 243.64 | 0.06 | 243.58 | 227.74 | 259.40 | 0.00 | 0.00 | 0.00 |
October | 181.15 | 0.00 | 181.15 | 83.82 | 397.62 | 0.00 | 0.00 | 0.00 |
November | 126.72 | 0.00 | 126.72 | 20.14 | 602.45 | 0.00 | 0.00 | 0.00 |
December | 82.20 | 0.00 | 82.20 | 0.09 | 863.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.11 | 6.87 | 231.24 | 187.39 | 436.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.20 | 0.00 | 82.20 | 0.09 | 118.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.67 | 36.73 | 367.94 | 474.70 | 964.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.05 | 0.00 | 121.05 | 0.69 | 964.65 | 0.00 | 0.00 | 0.00 |
February | 153.47 | 0.00 | 153.47 | 10.74 | 773.23 | 0.00 | 0.00 | 0.00 |
March | 230.00 | 0.00 | 230.00 | 82.95 | 486.45 | 0.00 | 0.00 | 0.00 |
April | 265.52 | 1.31 | 264.21 | 165.19 | 327.08 | 0.00 | 0.00 | 0.00 |
May | 346.24 | 13.01 | 333.22 | 325.79 | 188.98 | 0.00 | 0.00 | 0.00 |
June | 404.67 | 36.73 | 367.94 | 474.70 | 134.09 | 0.00 | 0.00 | 0.00 |
July | 379.52 | 25.39 | 354.13 | 462.37 | 118.63 | 0.00 | 0.00 | 0.00 |
August | 317.77 | 5.63 | 312.14 | 381.76 | 143.75 | 0.00 | 0.00 | 0.00 |
September | 243.64 | 0.06 | 243.58 | 227.74 | 259.40 | 0.00 | 0.00 | 0.00 |
October | 181.15 | 0.00 | 181.15 | 83.82 | 397.62 | 0.00 | 0.00 | 0.00 |
November | 126.72 | 0.00 | 126.72 | 20.14 | 602.45 | 0.00 | 0.00 | 0.00 |
December | 82.20 | 0.00 | 82.20 | 0.09 | 863.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.11 | 6.87 | 231.24 | 187.39 | 436.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.20 | 0.00 | 82.20 | 0.09 | 118.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.67 | 36.73 | 367.94 | 474.70 | 964.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.03 | 205.35 | 293.68 | 224.29 | 1684.19 | 0.00 | 0.00 | 0.00 |
February | 661.47 | 290.86 | 370.61 | 393.80 | 1334.97 | 0.00 | 0.00 | 0.00 |
March | 898.73 | 356.73 | 542.00 | 718.86 | 872.65 | 0.00 | 0.00 | 0.00 |
April | 1103.55 | 483.28 | 620.27 | 1091.09 | 623.71 | 0.00 | 0.00 | 0.00 |
May | 1385.98 | 605.61 | 780.37 | 1579.45 | 388.04 | 0.00 | 0.00 | 0.00 |
June | 1525.23 | 664.21 | 861.02 | 1919.79 | 272.44 | 0.00 | 0.00 | 0.00 |
July | 1541.62 | 711.33 | 830.28 | 1982.12 | 241.29 | 0.00 | 0.00 | 0.00 |
August | 1299.55 | 560.26 | 739.29 | 1670.23 | 286.35 | 0.00 | 0.00 | 0.00 |
September | 1159.08 | 547.73 | 611.36 | 1367.79 | 496.89 | 0.00 | 0.00 | 0.00 |
October | 738.65 | 308.53 | 430.12 | 646.82 | 739.41 | 0.00 | 0.00 | 0.00 |
November | 435.81 | 141.56 | 294.25 | 228.58 | 1086.68 | 0.00 | 0.00 | 0.00 |
December | 337.58 | 144.97 | 192.62 | 154.13 | 1543.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 967.03 | 418.97 | 548.06 | 1001.36 | 795.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.58 | 141.56 | 192.62 | 154.13 | 241.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1541.62 | 711.33 | 861.02 | 1982.12 | 1684.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.73 | 8.12 | 11.61 | 8.87 | 66.59 | 0.00 | 0.00 | 0.00 |
February | 26.15 | 11.50 | 14.65 | 15.57 | 52.78 | 0.00 | 0.00 | 0.00 |
March | 35.53 | 14.10 | 21.43 | 28.42 | 34.50 | 0.00 | 0.00 | 0.00 |
April | 43.63 | 19.11 | 24.53 | 43.14 | 24.66 | 0.00 | 0.00 | 0.00 |
May | 54.80 | 23.95 | 30.86 | 62.45 | 15.34 | 0.00 | 0.00 | 0.00 |
June | 60.31 | 26.26 | 34.04 | 75.91 | 10.77 | 0.00 | 0.00 | 0.00 |
July | 60.95 | 28.13 | 32.83 | 78.37 | 9.54 | 0.00 | 0.00 | 0.00 |
August | 51.38 | 22.15 | 29.23 | 66.04 | 11.32 | 0.00 | 0.00 | 0.00 |
September | 45.83 | 21.66 | 24.17 | 54.08 | 19.65 | 0.00 | 0.00 | 0.00 |
October | 29.21 | 12.20 | 17.01 | 25.57 | 29.24 | 0.00 | 0.00 | 0.00 |
November | 17.23 | 5.60 | 11.63 | 9.04 | 42.97 | 0.00 | 0.00 | 0.00 |
December | 13.35 | 5.73 | 7.62 | 6.09 | 61.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.24 | 16.57 | 21.67 | 39.59 | 31.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.35 | 5.60 | 7.62 | 6.09 | 9.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.95 | 28.13 | 34.04 | 78.37 | 66.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.79 | 515.15 | 237.64 | 689.87 | 781.04 | 0.00 | 0.00 | 0.00 |
February | 806.60 | 544.94 | 261.66 | 769.12 | 639.07 | 0.00 | 0.00 | 0.00 |
March | 701.92 | 369.61 | 332.31 | 705.30 | 459.14 | 0.00 | 0.00 | 0.00 |
April | 632.39 | 295.65 | 336.74 | 705.74 | 341.56 | 0.00 | 0.00 | 0.00 |
May | 523.91 | 142.04 | 381.87 | 622.69 | 210.45 | 0.00 | 0.00 | 0.00 |
June | 508.64 | 103.56 | 405.08 | 664.78 | 145.14 | 0.00 | 0.00 | 0.00 |
July | 538.43 | 135.67 | 402.76 | 729.38 | 129.73 | 0.00 | 0.00 | 0.00 |
August | 606.63 | 217.55 | 389.08 | 830.50 | 158.99 | 0.00 | 0.00 | 0.00 |
September | 735.11 | 387.34 | 347.77 | 935.27 | 269.79 | 0.00 | 0.00 | 0.00 |
October | 767.61 | 481.56 | 286.04 | 854.84 | 395.56 | 0.00 | 0.00 | 0.00 |
November | 579.16 | 362.56 | 216.59 | 552.04 | 540.96 | 0.00 | 0.00 | 0.00 |
December | 617.59 | 467.81 | 149.77 | 600.26 | 740.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.63 | 334.09 | 312.54 | 721.34 | 399.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.64 | 103.56 | 149.77 | 552.04 | 129.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.60 | 544.94 | 405.08 | 935.27 | 781.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.79 | 515.15 | 237.64 | 689.87 | 781.04 | 0.00 | 0.00 | 0.00 |
February | 806.60 | 544.94 | 261.66 | 769.12 | 639.07 | 0.00 | 0.00 | 0.00 |
March | 701.92 | 369.61 | 332.31 | 705.30 | 459.14 | 0.00 | 0.00 | 0.00 |
April | 632.39 | 295.65 | 336.74 | 705.74 | 341.56 | 0.00 | 0.00 | 0.00 |
May | 523.91 | 142.04 | 381.87 | 622.69 | 210.45 | 0.00 | 0.00 | 0.00 |
June | 508.64 | 103.56 | 405.08 | 664.78 | 145.14 | 0.00 | 0.00 | 0.00 |
July | 538.43 | 135.67 | 402.76 | 729.38 | 129.73 | 0.00 | 0.00 | 0.00 |
August | 606.63 | 217.55 | 389.08 | 830.50 | 158.99 | 0.00 | 0.00 | 0.00 |
September | 735.11 | 387.34 | 347.77 | 935.27 | 269.79 | 0.00 | 0.00 | 0.00 |
October | 767.61 | 481.56 | 286.04 | 854.84 | 395.56 | 0.00 | 0.00 | 0.00 |
November | 579.16 | 362.56 | 216.59 | 552.04 | 540.96 | 0.00 | 0.00 | 0.00 |
December | 617.59 | 467.81 | 149.77 | 600.26 | 740.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.63 | 334.09 | 312.54 | 721.34 | 399.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.64 | 103.56 | 149.77 | 552.04 | 129.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.60 | 544.94 | 405.08 | 935.27 | 781.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.74 | 515.12 | 237.62 | 689.82 | 780.99 | 0.00 | 0.00 | 0.00 |
February | 806.55 | 544.91 | 261.64 | 769.07 | 639.03 | 0.00 | 0.00 | 0.00 |
March | 701.88 | 369.58 | 332.29 | 705.25 | 459.11 | 0.00 | 0.00 | 0.00 |
April | 632.35 | 295.63 | 336.71 | 705.70 | 341.54 | 0.00 | 0.00 | 0.00 |
May | 523.88 | 142.03 | 381.85 | 622.65 | 210.44 | 0.00 | 0.00 | 0.00 |
June | 508.61 | 103.55 | 405.05 | 664.74 | 145.13 | 0.00 | 0.00 | 0.00 |
July | 538.40 | 135.66 | 402.74 | 729.33 | 129.72 | 0.00 | 0.00 | 0.00 |
August | 606.59 | 217.54 | 389.06 | 830.45 | 158.98 | 0.00 | 0.00 | 0.00 |
September | 735.06 | 387.32 | 347.75 | 935.22 | 269.78 | 0.00 | 0.00 | 0.00 |
October | 767.56 | 481.53 | 286.02 | 854.78 | 395.53 | 0.00 | 0.00 | 0.00 |
November | 579.12 | 362.54 | 216.58 | 552.00 | 540.92 | 0.00 | 0.00 | 0.00 |
December | 617.55 | 467.78 | 149.76 | 600.22 | 740.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.59 | 334.07 | 312.52 | 721.29 | 399.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.61 | 103.55 | 149.76 | 552.00 | 129.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.55 | 544.91 | 405.05 | 935.22 | 780.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.92 | 200.25 | 294.67 | 234.73 | 1723.21 | 0.00 | 0.00 | 0.00 |
February | 725.71 | 357.61 | 368.10 | 489.48 | 1382.22 | 0.00 | 0.00 | 0.00 |
March | 866.35 | 322.33 | 544.02 | 684.92 | 901.34 | 0.00 | 0.00 | 0.00 |
April | 1263.75 | 624.90 | 638.85 | 1325.26 | 655.79 | 0.00 | 0.00 | 0.00 |
May | 1267.40 | 506.30 | 761.11 | 1452.50 | 408.20 | 0.00 | 0.00 | 0.00 |
June | 1487.15 | 644.49 | 842.66 | 1883.13 | 292.33 | 0.00 | 0.00 | 0.00 |
July | 1596.74 | 758.48 | 838.27 | 2073.49 | 266.68 | 0.00 | 0.00 | 0.00 |
August | 1395.96 | 640.65 | 755.31 | 1820.04 | 311.30 | 0.00 | 0.00 | 0.00 |
September | 1129.99 | 536.35 | 593.64 | 1339.29 | 519.45 | 0.00 | 0.00 | 0.00 |
October | 787.42 | 350.08 | 437.34 | 732.02 | 771.03 | 0.00 | 0.00 | 0.00 |
November | 471.32 | 174.29 | 297.03 | 292.01 | 1112.57 | 0.00 | 0.00 | 0.00 |
December | 362.47 | 170.87 | 191.60 | 202.28 | 1575.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 988.48 | 440.63 | 547.85 | 1046.84 | 824.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.47 | 170.87 | 191.60 | 202.28 | 266.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1596.74 | 758.48 | 842.66 | 2073.49 | 1723.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 7.92 | 11.65 | 9.28 | 68.13 | 0.00 | 0.00 | 0.00 |
February | 28.69 | 14.14 | 14.55 | 19.35 | 54.65 | 0.00 | 0.00 | 0.00 |
March | 34.25 | 12.74 | 21.51 | 27.08 | 35.64 | 0.00 | 0.00 | 0.00 |
April | 49.97 | 24.71 | 25.26 | 52.40 | 25.93 | 0.00 | 0.00 | 0.00 |
May | 50.11 | 20.02 | 30.09 | 57.43 | 16.14 | 0.00 | 0.00 | 0.00 |
June | 58.80 | 25.48 | 33.32 | 74.46 | 11.56 | 0.00 | 0.00 | 0.00 |
July | 63.13 | 29.99 | 33.14 | 81.98 | 10.54 | 0.00 | 0.00 | 0.00 |
August | 55.19 | 25.33 | 29.86 | 71.96 | 12.31 | 0.00 | 0.00 | 0.00 |
September | 44.68 | 21.21 | 23.47 | 52.95 | 20.54 | 0.00 | 0.00 | 0.00 |
October | 31.13 | 13.84 | 17.29 | 28.94 | 30.49 | 0.00 | 0.00 | 0.00 |
November | 18.64 | 6.89 | 11.74 | 11.55 | 43.99 | 0.00 | 0.00 | 0.00 |
December | 14.33 | 6.76 | 7.58 | 8.00 | 62.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.08 | 17.42 | 21.66 | 41.39 | 32.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.33 | 6.76 | 7.58 | 8.00 | 10.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.13 | 29.99 | 33.32 | 81.98 | 68.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.15 | 0.00 | 363.15 | 1.58 | 2942.33 | 0.00 | 0.00 | 0.00 |
February | 460.40 | 0.00 | 460.40 | 28.26 | 2376.75 | 0.00 | 0.00 | 0.00 |
March | 690.00 | 0.00 | 690.00 | 220.53 | 1524.06 | 0.00 | 0.00 | 0.00 |
April | 796.55 | 3.92 | 792.63 | 446.71 | 1065.21 | 0.00 | 0.00 | 0.00 |
May | 1038.72 | 39.04 | 999.68 | 910.64 | 626.01 | 0.00 | 0.00 | 0.00 |
June | 1214.03 | 110.19 | 1103.84 | 1385.48 | 430.17 | 0.00 | 0.00 | 0.00 |
July | 1138.57 | 76.16 | 1062.41 | 1360.19 | 373.28 | 0.00 | 0.00 | 0.00 |
August | 953.32 | 16.90 | 936.42 | 1130.92 | 440.20 | 0.00 | 0.00 | 0.00 |
September | 730.92 | 0.18 | 730.74 | 674.68 | 779.25 | 0.00 | 0.00 | 0.00 |
October | 543.45 | 0.00 | 543.45 | 246.93 | 1184.12 | 0.00 | 0.00 | 0.00 |
November | 380.15 | 0.00 | 380.15 | 58.32 | 1797.58 | 0.00 | 0.00 | 0.00 |
December | 246.59 | 0.00 | 246.59 | 0.20 | 2607.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 714.32 | 20.61 | 693.71 | 541.78 | 1340.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.59 | 0.00 | 246.59 | 0.20 | 373.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1214.03 | 110.19 | 1103.84 | 1385.48 | 2942.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.77 | 213.48 | 305.30 | 227.29 | 1769.00 | 0.00 | 0.00 | 0.00 |
February | 687.63 | 302.36 | 385.27 | 397.92 | 1408.78 | 0.00 | 0.00 | 0.00 |
March | 934.28 | 370.84 | 563.44 | 717.77 | 938.12 | 0.00 | 0.00 | 0.00 |
April | 1147.21 | 502.40 | 644.81 | 1097.44 | 686.53 | 0.00 | 0.00 | 0.00 |
May | 1440.80 | 629.56 | 811.23 | 1607.85 | 423.99 | 0.00 | 0.00 | 0.00 |
June | 1585.56 | 690.49 | 895.07 | 1972.62 | 291.33 | 0.00 | 0.00 | 0.00 |
July | 1602.59 | 739.47 | 863.12 | 2044.23 | 252.38 | 0.00 | 0.00 | 0.00 |
August | 1350.96 | 582.43 | 768.53 | 1724.61 | 294.60 | 0.00 | 0.00 | 0.00 |
September | 1204.93 | 569.39 | 635.54 | 1414.95 | 502.92 | 0.00 | 0.00 | 0.00 |
October | 767.87 | 320.73 | 447.13 | 668.98 | 745.83 | 0.00 | 0.00 | 0.00 |
November | 453.05 | 147.16 | 305.89 | 235.39 | 1114.94 | 0.00 | 0.00 | 0.00 |
December | 350.93 | 150.70 | 200.23 | 157.76 | 1605.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1005.28 | 435.54 | 569.74 | 1025.64 | 833.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 350.93 | 147.16 | 200.23 | 157.76 | 252.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1602.59 | 739.47 | 895.07 | 2044.23 | 1769.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2258.40 | 1545.48 | 712.93 | 2008.46 | 2411.54 | 0.00 | 0.00 | 0.00 |
February | 2419.84 | 1634.86 | 784.98 | 2241.53 | 1958.08 | 0.00 | 0.00 | 0.00 |
March | 2105.80 | 1108.85 | 996.96 | 2049.16 | 1428.99 | 0.00 | 0.00 | 0.00 |
April | 1897.19 | 886.97 | 1010.22 | 2057.00 | 1088.83 | 0.00 | 0.00 | 0.00 |
May | 1571.76 | 426.12 | 1145.63 | 1803.35 | 685.63 | 0.00 | 0.00 | 0.00 |
June | 1525.94 | 310.69 | 1215.25 | 1952.92 | 464.11 | 0.00 | 0.00 | 0.00 |
July | 1615.31 | 407.02 | 1208.30 | 2162.16 | 400.49 | 0.00 | 0.00 | 0.00 |
August | 1819.92 | 652.67 | 1167.25 | 2474.27 | 473.12 | 0.00 | 0.00 | 0.00 |
September | 2205.36 | 1162.04 | 1043.32 | 2789.84 | 789.32 | 0.00 | 0.00 | 0.00 |
October | 2302.86 | 1444.72 | 858.14 | 2544.58 | 1142.38 | 0.00 | 0.00 | 0.00 |
November | 1737.50 | 1087.71 | 649.79 | 1631.66 | 1603.58 | 0.00 | 0.00 | 0.00 |
December | 1852.79 | 1403.47 | 449.32 | 1767.33 | 2251.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1939.91 | 1002.29 | 937.62 | 2122.72 | 1221.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1525.94 | 310.69 | 449.32 | 1631.66 | 400.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2419.84 | 1634.86 | 1215.25 | 2789.84 | 2411.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.49 | 208.17 | 306.32 | 236.68 | 1814.11 | 0.00 | 0.00 | 0.00 |
February | 754.42 | 371.75 | 382.66 | 494.58 | 1461.18 | 0.00 | 0.00 | 0.00 |
March | 900.62 | 335.08 | 565.54 | 684.34 | 968.91 | 0.00 | 0.00 | 0.00 |
April | 1313.73 | 649.62 | 664.11 | 1345.60 | 715.07 | 0.00 | 0.00 | 0.00 |
May | 1317.53 | 526.32 | 791.21 | 1477.20 | 448.59 | 0.00 | 0.00 | 0.00 |
June | 1545.97 | 669.98 | 875.98 | 1938.02 | 312.55 | 0.00 | 0.00 | 0.00 |
July | 1659.90 | 788.48 | 871.42 | 2143.25 | 275.77 | 0.00 | 0.00 | 0.00 |
August | 1451.17 | 665.99 | 785.18 | 1883.60 | 317.21 | 0.00 | 0.00 | 0.00 |
September | 1174.68 | 557.56 | 617.12 | 1387.80 | 525.91 | 0.00 | 0.00 | 0.00 |
October | 818.57 | 363.93 | 454.64 | 758.84 | 777.92 | 0.00 | 0.00 | 0.00 |
November | 489.97 | 181.19 | 308.78 | 301.07 | 1141.68 | 0.00 | 0.00 | 0.00 |
December | 376.81 | 177.63 | 199.18 | 205.75 | 1642.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1027.58 | 458.06 | 569.51 | 1074.25 | 864.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.81 | 177.63 | 199.18 | 205.75 | 275.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.90 | 788.48 | 875.98 | 2143.25 | 1814.11 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972653E+09 | 0.00 | 0.972653E+09 | 4889264.93 | 0.776019E+10 |
February | 0.111380E+10 | 0.00 | 0.111380E+10 | 74927652.53 | 0.560641E+10 |
March | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.611950E+09 | 0.393433E+10 |
April | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.117769E+10 | 0.262433E+10 |
May | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.245718E+10 | 0.161555E+10 |
June | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.359603E+10 | 0.107711E+10 |
July | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.363947E+10 | 0.973468E+09 |
August | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.303317E+10 | 0.113908E+10 |
September | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.177745E+10 | 0.191012E+10 |
October | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.721289E+09 | 0.295267E+10 |
November | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.175240E+09 | 0.444308E+10 |
December | 0.660462E+09 | 0.00 | 0.660462E+09 | 1447740.26 | 0.680569E+10 |
Annual Sum or Average | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.172707E+11 | 0.408420E+11 |
Minimum of Months | 0.660462E+09 | 0.00 | 0.660462E+09 | 1447740.26 | 0.973468E+09 |
Maximum of Months | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.363947E+10 | 0.776019E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.614161E+09 | 0.466942E+10 |
February | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.975930E+09 | 0.332082E+10 |
March | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.195063E+10 | 0.241876E+10 |
April | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.286602E+10 | 0.169558E+10 |
May | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.431793E+10 | 0.109942E+10 |
June | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.511981E+10 | 0.730353E+09 |
July | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.547676E+10 | 0.659091E+09 |
August | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.462593E+10 | 0.764404E+09 |
September | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.368933E+10 | 0.123965E+10 |
October | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.185049E+10 | 0.186363E+10 |
November | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.639409E+09 | 0.275904E+10 |
December | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.431086E+09 | 0.419664E+10 |
Annual Sum or Average | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.325575E+11 | 0.254168E+11 |
Minimum of Months | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.431086E+09 | 0.659091E+09 |
Maximum of Months | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.547676E+10 | 0.466942E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.540086E+10 | 0.633240E+10 |
February | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.545255E+10 | 0.459164E+10 |
March | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.551701E+10 | 0.368099E+10 |
April | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.534703E+10 | 0.268836E+10 |
May | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.483340E+10 | 0.177110E+10 |
June | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.505821E+10 | 0.116013E+10 |
July | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.578108E+10 | 0.104289E+10 |
August | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.662082E+10 | 0.122452E+10 |
September | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.724840E+10 | 0.194547E+10 |
October | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.687575E+10 | 0.286192E+10 |
November | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.428279E+10 | 0.395891E+10 |
December | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.476204E+10 | 0.585599E+10 |
Annual Sum or Average | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.671799E+11 | 0.371143E+11 |
Minimum of Months | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.428279E+10 | 0.104289E+10 |
Maximum of Months | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.724840E+10 | 0.633240E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.635861E+09 | 0.478215E+10 |
February | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.120357E+10 | 0.344263E+10 |
March | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.184705E+10 | 0.249772E+10 |
April | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.349655E+10 | 0.176293E+10 |
May | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.395967E+10 | 0.115728E+10 |
June | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.502013E+10 | 0.781318E+09 |
July | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573261E+10 | 0.717741E+09 |
August | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.504074E+10 | 0.821122E+09 |
September | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.361177E+10 | 0.129332E+10 |
October | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.207144E+10 | 0.194270E+10 |
November | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.802864E+09 | 0.282320E+10 |
December | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.556841E+09 | 0.428643E+10 |
Annual Sum or Average | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.339791E+11 | 0.263085E+11 |
Minimum of Months | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.556841E+09 | 0.717741E+09 |
Maximum of Months | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573261E+10 | 0.478215E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324202E+09 | 0.00 | 0.324202E+09 | 1844928.57 | 0.258354E+10 |
February | 0.371248E+09 | 0.00 | 0.371248E+09 | 25992017.52 | 0.187048E+10 |
March | 0.616000E+09 | 0.00 | 0.616000E+09 | 0.222176E+09 | 0.130282E+10 |
April | 0.688190E+09 | 3390682.39 | 0.684800E+09 | 0.428163E+09 | 0.847742E+09 |
May | 0.927327E+09 | 34856080.88 | 0.892471E+09 | 0.872581E+09 | 0.506147E+09 |
June | 0.104887E+10 | 95198633.35 | 0.953672E+09 | 0.123039E+10 | 0.347550E+09 |
July | 0.101647E+10 | 67990399.01 | 0.948475E+09 | 0.123836E+10 | 0.317734E+09 |
August | 0.851080E+09 | 15083510.68 | 0.835996E+09 | 0.102247E+10 | 0.385009E+09 |
September | 0.631484E+09 | 156579.94 | 0.631328E+09 | 0.590287E+09 | 0.672320E+09 |
October | 0.485171E+09 | 0.00 | 0.485171E+09 | 0.224490E+09 | 0.106492E+10 |
November | 0.328434E+09 | 0.00 | 0.328434E+09 | 52198154.24 | 0.156144E+10 |
December | 0.220144E+09 | 0.00 | 0.220144E+09 | 234715.27 | 0.231375E+10 |
Annual Sum or Average | 0.750862E+10 | 0.216676E+09 | 0.729194E+10 | 0.590918E+10 | 0.137734E+11 |
Minimum of Months | 0.220144E+09 | 0.00 | 0.220144E+09 | 234715.27 | 0.317734E+09 |
Maximum of Months | 0.104887E+10 | 95198633.35 | 0.953672E+09 | 0.123836E+10 | 0.258354E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324215E+09 | 0.00 | 0.324215E+09 | 1844520.29 | 0.258371E+10 |
February | 0.371263E+09 | 0.00 | 0.371263E+09 | 25991039.50 | 0.187060E+10 |
March | 0.616024E+09 | 0.00 | 0.616024E+09 | 0.222177E+09 | 0.130291E+10 |
April | 0.688218E+09 | 3390773.53 | 0.684827E+09 | 0.428175E+09 | 0.847798E+09 |
May | 0.927363E+09 | 34857017.82 | 0.892506E+09 | 0.872608E+09 | 0.506177E+09 |
June | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123043E+10 | 0.347570E+09 |
July | 0.101651E+10 | 67992226.61 | 0.948514E+09 | 0.123841E+10 | 0.317751E+09 |
August | 0.851113E+09 | 15083916.13 | 0.836030E+09 | 0.102251E+10 | 0.385031E+09 |
September | 0.631510E+09 | 156584.15 | 0.631353E+09 | 0.590308E+09 | 0.672359E+09 |
October | 0.485190E+09 | 0.00 | 0.485190E+09 | 0.224493E+09 | 0.106498E+10 |
November | 0.328447E+09 | 0.00 | 0.328447E+09 | 52197319.53 | 0.156155E+10 |
December | 0.220152E+09 | 0.00 | 0.220152E+09 | 234667.02 | 0.231390E+10 |
Annual Sum or Average | 0.750891E+10 | 0.216682E+09 | 0.729223E+10 | 0.590938E+10 | 0.137743E+11 |
Minimum of Months | 0.220152E+09 | 0.00 | 0.220152E+09 | 234667.02 | 0.317751E+09 |
Maximum of Months | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123841E+10 | 0.258371E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324215E+09 | 0.00 | 0.324215E+09 | 1844520.29 | 0.258371E+10 |
February | 0.371263E+09 | 0.00 | 0.371263E+09 | 25991039.50 | 0.187060E+10 |
March | 0.616024E+09 | 0.00 | 0.616024E+09 | 0.222177E+09 | 0.130291E+10 |
April | 0.688218E+09 | 3390773.53 | 0.684827E+09 | 0.428175E+09 | 0.847798E+09 |
May | 0.927363E+09 | 34857017.82 | 0.892506E+09 | 0.872608E+09 | 0.506177E+09 |
June | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123043E+10 | 0.347570E+09 |
July | 0.101651E+10 | 67992226.61 | 0.948514E+09 | 0.123841E+10 | 0.317751E+09 |
August | 0.851113E+09 | 15083916.13 | 0.836030E+09 | 0.102251E+10 | 0.385031E+09 |
September | 0.631510E+09 | 156584.15 | 0.631353E+09 | 0.590308E+09 | 0.672359E+09 |
October | 0.485190E+09 | 0.00 | 0.485190E+09 | 0.224493E+09 | 0.106498E+10 |
November | 0.328447E+09 | 0.00 | 0.328447E+09 | 52197319.53 | 0.156155E+10 |
December | 0.220152E+09 | 0.00 | 0.220152E+09 | 234667.02 | 0.231390E+10 |
Annual Sum or Average | 0.750891E+10 | 0.216682E+09 | 0.729223E+10 | 0.590938E+10 | 0.137743E+11 |
Minimum of Months | 0.220152E+09 | 0.00 | 0.220152E+09 | 234667.02 | 0.317751E+09 |
Maximum of Months | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123841E+10 | 0.258371E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133661E+10 | 0.550017E+09 | 0.786592E+09 | 0.600735E+09 | 0.451095E+10 |
February | 0.160022E+10 | 0.703645E+09 | 0.896572E+09 | 0.952689E+09 | 0.322957E+10 |
March | 0.240716E+10 | 0.955469E+09 | 0.145169E+10 | 0.192538E+10 | 0.233731E+10 |
April | 0.286041E+10 | 0.125266E+10 | 0.160775E+10 | 0.282809E+10 | 0.161666E+10 |
May | 0.371220E+10 | 0.162206E+10 | 0.209014E+10 | 0.423041E+10 | 0.103932E+10 |
June | 0.395339E+10 | 0.172163E+10 | 0.223176E+10 | 0.497610E+10 | 0.706154E+09 |
July | 0.412906E+10 | 0.190524E+10 | 0.222383E+10 | 0.530891E+10 | 0.646272E+09 |
August | 0.348072E+10 | 0.150061E+10 | 0.198011E+10 | 0.447354E+10 | 0.766973E+09 |
September | 0.300435E+10 | 0.141970E+10 | 0.158464E+10 | 0.354531E+10 | 0.128793E+10 |
October | 0.197840E+10 | 0.826358E+09 | 0.115204E+10 | 0.173245E+10 | 0.198044E+10 |
November | 0.112962E+10 | 0.366919E+09 | 0.762698E+09 | 0.592482E+09 | 0.281666E+10 |
December | 0.904179E+09 | 0.388275E+09 | 0.515904E+09 | 0.412832E+09 | 0.413339E+10 |
Annual Sum or Average | 0.304963E+11 | 0.132126E+11 | 0.172837E+11 | 0.315789E+11 | 0.250716E+11 |
Minimum of Months | 0.904179E+09 | 0.366919E+09 | 0.515904E+09 | 0.412832E+09 | 0.646272E+09 |
Maximum of Months | 0.412906E+10 | 0.190524E+10 | 0.223176E+10 | 0.530891E+10 | 0.451095E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52848333.44 | 21747177.24 | 31101156.20 | 23752538.76 | 0.178359E+09 |
February | 63271121.83 | 27821483.10 | 35449638.73 | 37668468.89 | 0.127694E+09 |
March | 95176819.75 | 37778372.49 | 57398447.26 | 76127942.97 | 92415235.23 |
April | 0.113098E+09 | 49529090.55 | 63569016.08 | 0.111820E+09 | 63921122.18 |
May | 0.146777E+09 | 64134625.01 | 82642305.37 | 0.167266E+09 | 41093642.35 |
June | 0.156314E+09 | 68071882.56 | 88241725.46 | 0.196750E+09 | 27920684.59 |
July | 0.163259E+09 | 75331340.01 | 87928116.42 | 0.209910E+09 | 25553004.91 |
August | 0.137625E+09 | 59332787.70 | 78291826.23 | 0.176880E+09 | 30325423.70 |
September | 0.118789E+09 | 56133846.95 | 62655254.45 | 0.140178E+09 | 50923734.58 |
October | 78223966.07 | 32673432.69 | 45550533.38 | 68499466.10 | 78304672.28 |
November | 44664048.95 | 14507661.16 | 30156387.79 | 23426191.42 | 0.111368E+09 |
December | 35750404.86 | 15352039.08 | 20398365.78 | 16323016.00 | 0.163431E+09 |
Annual Sum or Average | 0.120580E+10 | 0.522414E+09 | 0.683383E+09 | 0.124860E+10 | 0.991310E+09 |
Minimum of Months | 35750404.86 | 14507661.16 | 20398365.78 | 16323016.00 | 25553004.91 |
Maximum of Months | 0.163259E+09 | 75331340.01 | 88241725.46 | 0.209910E+09 | 0.178359E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201627E+10 | 0.137977E+10 | 0.636494E+09 | 0.184774E+10 | 0.209193E+10 |
February | 0.195132E+10 | 0.131833E+10 | 0.632997E+09 | 0.186064E+10 | 0.154604E+10 |
March | 0.188003E+10 | 0.989958E+09 | 0.890072E+09 | 0.188907E+10 | 0.122976E+10 |
April | 0.163915E+10 | 0.766329E+09 | 0.872818E+09 | 0.182928E+10 | 0.885328E+09 |
May | 0.140325E+10 | 0.380436E+09 | 0.102281E+10 | 0.166782E+10 | 0.563679E+09 |
June | 0.131839E+10 | 0.268430E+09 | 0.104996E+10 | 0.172311E+10 | 0.376199E+09 |
July | 0.144213E+10 | 0.363376E+09 | 0.107876E+10 | 0.195356E+10 | 0.347459E+09 |
August | 0.162480E+10 | 0.582689E+09 | 0.104211E+10 | 0.222441E+10 | 0.425845E+09 |
September | 0.190540E+10 | 0.100398E+10 | 0.901415E+09 | 0.242423E+10 | 0.699304E+09 |
October | 0.205596E+10 | 0.128982E+10 | 0.766136E+09 | 0.228959E+10 | 0.105947E+10 |
November | 0.150117E+10 | 0.939761E+09 | 0.561413E+09 | 0.143088E+10 | 0.140216E+10 |
December | 0.165414E+10 | 0.125299E+10 | 0.401152E+09 | 0.160773E+10 | 0.198383E+10 |
Annual Sum or Average | 0.203920E+11 | 0.105359E+11 | 0.985614E+10 | 0.227481E+11 | 0.126110E+11 |
Minimum of Months | 0.131839E+10 | 0.268430E+09 | 0.401152E+09 | 0.143088E+10 | 0.347459E+09 |
Maximum of Months | 0.205596E+10 | 0.137977E+10 | 0.107876E+10 | 0.242423E+10 | 0.209193E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201627E+10 | 0.137977E+10 | 0.636494E+09 | 0.184774E+10 | 0.209193E+10 |
February | 0.195132E+10 | 0.131833E+10 | 0.632997E+09 | 0.186064E+10 | 0.154604E+10 |
March | 0.188003E+10 | 0.989958E+09 | 0.890072E+09 | 0.188907E+10 | 0.122976E+10 |
April | 0.163915E+10 | 0.766329E+09 | 0.872818E+09 | 0.182928E+10 | 0.885328E+09 |
May | 0.140325E+10 | 0.380436E+09 | 0.102281E+10 | 0.166782E+10 | 0.563679E+09 |
June | 0.131839E+10 | 0.268430E+09 | 0.104996E+10 | 0.172311E+10 | 0.376199E+09 |
July | 0.144213E+10 | 0.363376E+09 | 0.107876E+10 | 0.195356E+10 | 0.347459E+09 |
August | 0.162480E+10 | 0.582689E+09 | 0.104211E+10 | 0.222441E+10 | 0.425845E+09 |
September | 0.190540E+10 | 0.100398E+10 | 0.901415E+09 | 0.242423E+10 | 0.699304E+09 |
October | 0.205596E+10 | 0.128982E+10 | 0.766136E+09 | 0.228959E+10 | 0.105947E+10 |
November | 0.150117E+10 | 0.939761E+09 | 0.561413E+09 | 0.143088E+10 | 0.140216E+10 |
December | 0.165414E+10 | 0.125299E+10 | 0.401152E+09 | 0.160773E+10 | 0.198383E+10 |
Annual Sum or Average | 0.203920E+11 | 0.105359E+11 | 0.985614E+10 | 0.227481E+11 | 0.126110E+11 |
Minimum of Months | 0.131839E+10 | 0.268430E+09 | 0.401152E+09 | 0.143088E+10 | 0.347459E+09 |
Maximum of Months | 0.205596E+10 | 0.137977E+10 | 0.107876E+10 | 0.242423E+10 | 0.209193E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201614E+10 | 0.137968E+10 | 0.636454E+09 | 0.184763E+10 | 0.209180E+10 |
February | 0.195120E+10 | 0.131824E+10 | 0.632957E+09 | 0.186053E+10 | 0.154594E+10 |
March | 0.187991E+10 | 0.989895E+09 | 0.890015E+09 | 0.188895E+10 | 0.122968E+10 |
April | 0.163904E+10 | 0.766281E+09 | 0.872762E+09 | 0.182917E+10 | 0.885273E+09 |
May | 0.140316E+10 | 0.380412E+09 | 0.102275E+10 | 0.166772E+10 | 0.563643E+09 |
June | 0.131831E+10 | 0.268413E+09 | 0.104990E+10 | 0.172300E+10 | 0.376175E+09 |
July | 0.144204E+10 | 0.363353E+09 | 0.107869E+10 | 0.195344E+10 | 0.347437E+09 |
August | 0.162470E+10 | 0.582652E+09 | 0.104205E+10 | 0.222427E+10 | 0.425818E+09 |
September | 0.190528E+10 | 0.100392E+10 | 0.901358E+09 | 0.242408E+10 | 0.699260E+09 |
October | 0.205583E+10 | 0.128974E+10 | 0.766088E+09 | 0.228945E+10 | 0.105940E+10 |
November | 0.150108E+10 | 0.939702E+09 | 0.561378E+09 | 0.143079E+10 | 0.140208E+10 |
December | 0.165404E+10 | 0.125291E+10 | 0.401126E+09 | 0.160762E+10 | 0.198370E+10 |
Annual Sum or Average | 0.203907E+11 | 0.105352E+11 | 0.985552E+10 | 0.227466E+11 | 0.126102E+11 |
Minimum of Months | 0.131831E+10 | 0.268413E+09 | 0.401126E+09 | 0.143079E+10 | 0.347437E+09 |
Maximum of Months | 0.205583E+10 | 0.137968E+10 | 0.107869E+10 | 0.242408E+10 | 0.209180E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132559E+10 | 0.536349E+09 | 0.789243E+09 | 0.628700E+09 | 0.461545E+10 |
February | 0.175564E+10 | 0.865125E+09 | 0.890516E+09 | 0.118416E+10 | 0.334386E+10 |
March | 0.232043E+10 | 0.863325E+09 | 0.145711E+10 | 0.183448E+10 | 0.241416E+10 |
April | 0.327563E+10 | 0.161974E+10 | 0.165589E+10 | 0.343507E+10 | 0.169982E+10 |
May | 0.339461E+10 | 0.135606E+10 | 0.203855E+10 | 0.389038E+10 | 0.109332E+10 |
June | 0.385469E+10 | 0.167052E+10 | 0.218416E+10 | 0.488107E+10 | 0.757717E+09 |
July | 0.427672E+10 | 0.203150E+10 | 0.224522E+10 | 0.555364E+10 | 0.714266E+09 |
August | 0.373893E+10 | 0.171592E+10 | 0.202301E+10 | 0.487479E+10 | 0.833780E+09 |
September | 0.292893E+10 | 0.139021E+10 | 0.153871E+10 | 0.347143E+10 | 0.134643E+10 |
October | 0.210903E+10 | 0.937648E+09 | 0.117138E+10 | 0.196063E+10 | 0.206513E+10 |
November | 0.122167E+10 | 0.451772E+09 | 0.769899E+09 | 0.756887E+09 | 0.288378E+10 |
December | 0.970846E+09 | 0.457669E+09 | 0.513176E+09 | 0.541774E+09 | 0.422031E+10 |
Annual Sum or Average | 0.311727E+11 | 0.138958E+11 | 0.172769E+11 | 0.330130E+11 | 0.259880E+11 |
Minimum of Months | 0.970846E+09 | 0.451772E+09 | 0.513176E+09 | 0.541774E+09 | 0.714266E+09 |
Maximum of Months | 0.427672E+10 | 0.203150E+10 | 0.224522E+10 | 0.555364E+10 | 0.461545E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52412564.45 | 21206694.15 | 31205870.30 | 24858098.43 | 0.182491E+09 |
February | 69416280.03 | 34206148.70 | 35210131.33 | 46820443.86 | 0.132213E+09 |
March | 91747546.41 | 34134985.47 | 57612560.94 | 72533377.39 | 95453789.93 |
April | 0.129515E+09 | 64042755.41 | 65472401.82 | 0.135819E+09 | 67209187.01 |
May | 0.134220E+09 | 53617326.43 | 80602273.03 | 0.153822E+09 | 43228755.08 |
June | 0.152410E+09 | 66050663.64 | 86359703.28 | 0.192993E+09 | 29959444.00 |
July | 0.169097E+09 | 80323503.52 | 88773639.56 | 0.219585E+09 | 28241416.19 |
August | 0.147833E+09 | 67845650.47 | 79987783.28 | 0.192744E+09 | 32966906.61 |
September | 0.115807E+09 | 54967644.38 | 60839120.57 | 0.137257E+09 | 53236466.31 |
October | 83388869.09 | 37073632.29 | 46315236.80 | 77521252.61 | 81653528.61 |
November | 48303623.31 | 17862585.56 | 30441037.76 | 29926468.99 | 0.114022E+09 |
December | 38386251.97 | 18095774.92 | 20290477.05 | 21421166.95 | 0.166867E+09 |
Annual Sum or Average | 0.123254E+10 | 0.549427E+09 | 0.683110E+09 | 0.130530E+10 | 0.102754E+10 |
Minimum of Months | 38386251.97 | 17862585.56 | 20290477.05 | 21421166.95 | 28241416.19 |
Maximum of Months | 0.169097E+09 | 80323503.52 | 88773639.56 | 0.219585E+09 | 0.182491E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972653E+09 | 0.00 | 0.972653E+09 | 4236350.09 | 0.788074E+10 |
February | 0.111380E+10 | 0.00 | 0.111380E+10 | 68360093.94 | 0.574984E+10 |
March | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.590671E+09 | 0.408204E+10 |
April | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.115786E+10 | 0.276101E+10 |
May | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.243906E+10 | 0.167671E+10 |
June | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.359117E+10 | 0.111500E+10 |
July | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.364315E+10 | 0.999805E+09 |
August | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.302906E+10 | 0.117903E+10 |
September | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.174877E+10 | 0.201980E+10 |
October | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.661378E+09 | 0.317155E+10 |
November | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.151175E+09 | 0.465933E+10 |
December | 0.660462E+09 | 0.00 | 0.660462E+09 | 536309.60 | 0.698317E+10 |
Annual Sum or Average | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.170854E+11 | 0.422780E+11 |
Minimum of Months | 0.660462E+09 | 0.00 | 0.660462E+09 | 536309.60 | 0.999805E+09 |
Maximum of Months | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.364315E+10 | 0.788074E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.608786E+09 | 0.473808E+10 |
February | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.962639E+09 | 0.340811E+10 |
March | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.192248E+10 | 0.251266E+10 |
April | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.284457E+10 | 0.177950E+10 |
May | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.430646E+10 | 0.113561E+10 |
June | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.511302E+10 | 0.755127E+09 |
July | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.547527E+10 | 0.675966E+09 |
August | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.461921E+10 | 0.789055E+09 |
September | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.366756E+10 | 0.130358E+10 |
October | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.179179E+10 | 0.199762E+10 |
November | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.610121E+09 | 0.288993E+10 |
December | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.422547E+09 | 0.430039E+10 |
Annual Sum or Average | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.323445E+11 | 0.262856E+11 |
Minimum of Months | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.422547E+09 | 0.675966E+09 |
Maximum of Months | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.547527E+10 | 0.473808E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.537947E+10 | 0.645908E+10 |
February | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.542272E+10 | 0.473699E+10 |
March | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.548848E+10 | 0.382740E+10 |
April | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.533173E+10 | 0.282225E+10 |
May | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.483010E+10 | 0.183639E+10 |
June | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.506196E+10 | 0.120297E+10 |
July | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.579114E+10 | 0.107267E+10 |
August | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.662708E+10 | 0.126720E+10 |
September | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.723127E+10 | 0.204591E+10 |
October | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.681539E+10 | 0.305975E+10 |
November | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.422926E+10 | 0.415648E+10 |
December | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.473362E+10 | 0.603005E+10 |
Annual Sum or Average | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.669422E+11 | 0.385171E+11 |
Minimum of Months | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.422926E+10 | 0.107267E+10 |
Maximum of Months | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.723127E+10 | 0.645908E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.633922E+09 | 0.485892E+10 |
February | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.119649E+10 | 0.353489E+10 |
March | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.183294E+10 | 0.259514E+10 |
April | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.348779E+10 | 0.185346E+10 |
May | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.395654E+10 | 0.120149E+10 |
June | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.502336E+10 | 0.810139E+09 |
July | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.574048E+10 | 0.738615E+09 |
August | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.504504E+10 | 0.849615E+09 |
September | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.359718E+10 | 0.136317E+10 |
October | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.203247E+10 | 0.208359E+10 |
November | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.780381E+09 | 0.295923E+10 |
December | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.551081E+09 | 0.439927E+10 |
Annual Sum or Average | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.338777E+11 | 0.272475E+11 |
Minimum of Months | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.551081E+09 | 0.738615E+09 |
Maximum of Months | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.574048E+10 | 0.485892E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.83 | 2897.32 | 363.15 | 0.00 | 363.15 | 0.00 | 0.00 |
February | 30.97 | 2317.47 | 460.40 | 0.00 | 460.40 | 0.00 | 0.00 |
March | 228.48 | 1468.91 | 690.00 | 0.00 | 690.00 | 0.00 | 0.00 |
April | 454.36 | 1012.47 | 796.55 | 3.92 | 792.63 | 0.00 | 0.00 |
May | 917.41 | 603.18 | 1038.72 | 39.04 | 999.68 | 0.00 | 0.00 |
June | 1387.36 | 415.55 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
July | 1358.82 | 363.45 | 1138.57 | 76.16 | 1062.41 | 0.00 | 0.00 |
August | 1132.46 | 425.29 | 953.32 | 16.90 | 936.42 | 0.00 | 0.00 |
September | 685.74 | 736.93 | 730.92 | 0.18 | 730.74 | 0.00 | 0.00 |
October | 269.30 | 1102.40 | 543.45 | 0.00 | 543.45 | 0.00 | 0.00 |
November | 67.61 | 1714.15 | 380.15 | 0.00 | 380.15 | 0.00 | 0.00 |
December | 0.54 | 2540.95 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Annual Sum or Average | 547.65 | 1295.09 | 714.32 | 20.61 | 693.71 | 0.00 | 0.00 |
Minimum of Months | 0.54 | 363.45 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Maximum of Months | 1387.36 | 2897.32 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 229.30 | 1743.36 | 518.77 | 213.48 | 305.30 | 0.00 | 0.00 |
February | 403.41 | 1372.69 | 687.63 | 302.36 | 385.27 | 0.00 | 0.00 |
March | 728.28 | 903.06 | 934.28 | 370.84 | 563.44 | 0.00 | 0.00 |
April | 1105.72 | 654.16 | 1147.21 | 502.40 | 644.81 | 0.00 | 0.00 |
May | 1612.13 | 410.48 | 1440.80 | 629.56 | 811.23 | 0.00 | 0.00 |
June | 1975.24 | 281.77 | 1585.56 | 690.49 | 895.07 | 0.00 | 0.00 |
July | 2044.79 | 246.08 | 1602.59 | 739.47 | 863.12 | 0.00 | 0.00 |
August | 1727.12 | 285.40 | 1350.96 | 582.43 | 768.53 | 0.00 | 0.00 |
September | 1423.35 | 478.26 | 1204.93 | 569.39 | 635.54 | 0.00 | 0.00 |
October | 690.89 | 695.80 | 767.87 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 246.69 | 1064.44 | 453.05 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 160.95 | 1566.85 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1032.39 | 805.96 | 1005.28 | 435.54 | 569.74 | 0.00 | 0.00 |
Minimum of Months | 160.95 | 246.08 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2044.79 | 1743.36 | 1602.59 | 739.47 | 895.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2016.45 | 2364.25 | 2258.40 | 1545.48 | 712.93 | 0.00 | 0.00 |
February | 2253.86 | 1898.00 | 2419.84 | 1634.86 | 784.98 | 0.00 | 0.00 |
March | 2059.81 | 1374.32 | 2105.80 | 1108.85 | 996.96 | 0.00 | 0.00 |
April | 2062.90 | 1037.18 | 1897.19 | 886.97 | 1010.22 | 0.00 | 0.00 |
May | 1804.59 | 661.25 | 1571.76 | 426.12 | 1145.63 | 0.00 | 0.00 |
June | 1951.47 | 447.58 | 1525.94 | 310.69 | 1215.25 | 0.00 | 0.00 |
July | 2158.41 | 389.37 | 1615.31 | 407.02 | 1208.30 | 0.00 | 0.00 |
August | 2471.93 | 457.18 | 1819.92 | 652.67 | 1167.25 | 0.00 | 0.00 |
September | 2796.45 | 750.57 | 2205.36 | 1162.04 | 1043.32 | 0.00 | 0.00 |
October | 2567.11 | 1068.52 | 2302.86 | 1444.72 | 858.14 | 0.00 | 0.00 |
November | 1652.31 | 1527.36 | 1737.50 | 1087.71 | 649.79 | 0.00 | 0.00 |
December | 1777.94 | 2186.38 | 1852.79 | 1403.47 | 449.32 | 0.00 | 0.00 |
Annual Sum or Average | 2130.26 | 1176.89 | 1939.91 | 1002.29 | 937.62 | 0.00 | 0.00 |
Minimum of Months | 1652.31 | 389.37 | 1525.94 | 310.69 | 449.32 | 0.00 | 0.00 |
Maximum of Months | 2796.45 | 2364.25 | 2419.84 | 1634.86 | 1215.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.40 | 1785.45 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 497.51 | 1423.05 | 754.42 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 689.61 | 932.54 | 900.62 | 335.08 | 565.54 | 0.00 | 0.00 |
April | 1348.98 | 680.14 | 1313.73 | 649.62 | 664.11 | 0.00 | 0.00 |
May | 1478.37 | 432.08 | 1317.53 | 526.32 | 791.21 | 0.00 | 0.00 |
June | 1936.78 | 301.43 | 1545.97 | 669.98 | 875.98 | 0.00 | 0.00 |
July | 2140.31 | 267.97 | 1659.90 | 788.48 | 871.42 | 0.00 | 0.00 |
August | 1882.00 | 306.57 | 1451.17 | 665.99 | 785.18 | 0.00 | 0.00 |
September | 1393.43 | 498.97 | 1174.68 | 557.56 | 617.12 | 0.00 | 0.00 |
October | 773.39 | 725.32 | 818.57 | 363.93 | 454.64 | 0.00 | 0.00 |
November | 309.75 | 1089.20 | 489.97 | 181.19 | 308.78 | 0.00 | 0.00 |
December | 207.90 | 1600.37 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Annual Sum or Average | 1077.47 | 834.24 | 1027.58 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 207.90 | 267.97 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Maximum of Months | 2140.31 | 1785.45 | 1659.90 | 788.48 | 875.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.07 | 2893.88 | 363.14 | 0.00 | 363.14 | 0.00 | 0.00 |
February | 32.23 | 2319.64 | 460.39 | 0.00 | 460.39 | 0.00 | 0.00 |
March | 248.85 | 1459.32 | 689.98 | 0.00 | 689.98 | 0.00 | 0.00 |
April | 495.57 | 981.23 | 796.54 | 3.92 | 792.61 | 0.00 | 0.00 |
May | 977.37 | 566.94 | 1038.70 | 39.04 | 999.66 | 0.00 | 0.00 |
June | 1424.09 | 402.27 | 1214.00 | 110.19 | 1103.82 | 0.00 | 0.00 |
July | 1387.09 | 355.90 | 1138.54 | 76.16 | 1062.39 | 0.00 | 0.00 |
August | 1145.27 | 431.25 | 953.30 | 16.89 | 936.40 | 0.00 | 0.00 |
September | 683.22 | 778.18 | 730.90 | 0.18 | 730.72 | 0.00 | 0.00 |
October | 251.45 | 1192.83 | 543.44 | 0.00 | 543.44 | 0.00 | 0.00 |
November | 60.41 | 1807.31 | 380.14 | 0.00 | 380.14 | 0.00 | 0.00 |
December | 0.26 | 2591.67 | 246.58 | 0.00 | 246.58 | 0.00 | 0.00 |
Annual Sum or Average | 562.15 | 1310.31 | 714.31 | 20.61 | 693.70 | 0.00 | 0.00 |
Minimum of Months | 0.26 | 355.90 | 246.58 | 0.00 | 246.58 | 0.00 | 0.00 |
Maximum of Months | 1424.09 | 2893.88 | 1214.00 | 110.19 | 1103.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.16 | 1750.79 | 518.76 | 213.47 | 305.29 | 0.00 | 0.00 |
February | 409.37 | 1387.76 | 687.62 | 302.36 | 385.26 | 0.00 | 0.00 |
March | 747.28 | 907.16 | 934.26 | 370.84 | 563.43 | 0.00 | 0.00 |
April | 1134.23 | 648.37 | 1147.19 | 502.39 | 644.80 | 0.00 | 0.00 |
May | 1641.90 | 403.38 | 1440.78 | 629.55 | 811.22 | 0.00 | 0.00 |
June | 1995.70 | 283.21 | 1585.54 | 690.47 | 895.06 | 0.00 | 0.00 |
July | 2060.49 | 250.83 | 1602.57 | 739.46 | 863.11 | 0.00 | 0.00 |
August | 1736.27 | 297.68 | 1350.94 | 582.42 | 768.52 | 0.00 | 0.00 |
September | 1421.87 | 516.53 | 1204.91 | 569.38 | 635.53 | 0.00 | 0.00 |
October | 672.40 | 768.65 | 767.85 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 237.62 | 1129.64 | 453.04 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 160.23 | 1604.25 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1040.95 | 826.45 | 1005.27 | 435.53 | 569.73 | 0.00 | 0.00 |
Minimum of Months | 160.23 | 250.83 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2060.49 | 1750.79 | 1602.57 | 739.46 | 895.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2069.56 | 2343.06 | 2258.31 | 1545.41 | 712.90 | 0.00 | 0.00 |
February | 2307.30 | 1917.17 | 2419.74 | 1634.79 | 784.95 | 0.00 | 0.00 |
March | 2115.85 | 1377.39 | 2105.72 | 1108.80 | 996.92 | 0.00 | 0.00 |
April | 2117.18 | 1024.66 | 1897.12 | 886.94 | 1010.18 | 0.00 | 0.00 |
May | 1868.04 | 631.35 | 1571.70 | 426.11 | 1145.60 | 0.00 | 0.00 |
June | 1994.30 | 435.41 | 1525.89 | 310.68 | 1215.21 | 0.00 | 0.00 |
July | 2188.09 | 389.17 | 1615.26 | 407.00 | 1208.26 | 0.00 | 0.00 |
August | 2491.45 | 476.97 | 1819.86 | 652.64 | 1167.22 | 0.00 | 0.00 |
September | 2805.77 | 809.36 | 2205.28 | 1161.99 | 1043.28 | 0.00 | 0.00 |
October | 2564.45 | 1186.65 | 2302.77 | 1444.66 | 858.11 | 0.00 | 0.00 |
November | 1656.07 | 1622.84 | 1737.43 | 1087.66 | 649.77 | 0.00 | 0.00 |
December | 1800.73 | 2221.98 | 1852.72 | 1403.41 | 449.31 | 0.00 | 0.00 |
Annual Sum or Average | 2163.96 | 1199.65 | 1939.84 | 1002.25 | 937.59 | 0.00 | 0.00 |
Minimum of Months | 1656.07 | 389.17 | 1525.89 | 310.68 | 449.31 | 0.00 | 0.00 |
Maximum of Months | 2805.77 | 2343.06 | 2419.74 | 1634.79 | 1215.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.01 | 1791.34 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 508.84 | 1436.87 | 754.41 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 712.00 | 936.98 | 900.60 | 335.07 | 565.53 | 0.00 | 0.00 |
April | 1377.66 | 681.72 | 1313.71 | 649.61 | 664.11 | 0.00 | 0.00 |
May | 1509.93 | 424.34 | 1317.52 | 526.31 | 791.20 | 0.00 | 0.00 |
June | 1957.59 | 303.89 | 1545.95 | 669.97 | 875.97 | 0.00 | 0.00 |
July | 2155.48 | 277.22 | 1659.88 | 788.47 | 871.41 | 0.00 | 0.00 |
August | 1892.00 | 323.61 | 1451.15 | 665.98 | 785.17 | 0.00 | 0.00 |
September | 1392.24 | 539.99 | 1174.67 | 557.55 | 617.11 | 0.00 | 0.00 |
October | 760.96 | 801.52 | 818.55 | 363.92 | 454.64 | 0.00 | 0.00 |
November | 303.55 | 1156.56 | 489.96 | 181.19 | 308.77 | 0.00 | 0.00 |
December | 210.27 | 1637.98 | 376.80 | 177.63 | 199.17 | 0.00 | 0.00 |
Annual Sum or Average | 1088.23 | 856.66 | 1027.56 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 210.27 | 277.22 | 376.80 | 177.63 | 199.17 | 0.00 | 0.00 |
Maximum of Months | 2155.48 | 1791.34 | 1659.88 | 788.47 | 875.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.58 | 2942.33 | 363.15 | 0.00 | 363.15 | 0.00 | 0.00 |
February | 28.26 | 2376.75 | 460.40 | 0.00 | 460.40 | 0.00 | 0.00 |
March | 220.53 | 1524.06 | 690.00 | 0.00 | 690.00 | 0.00 | 0.00 |
April | 446.71 | 1065.21 | 796.55 | 3.92 | 792.63 | 0.00 | 0.00 |
May | 910.64 | 626.01 | 1038.72 | 39.04 | 999.68 | 0.00 | 0.00 |
June | 1385.48 | 430.17 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
July | 1360.19 | 373.28 | 1138.57 | 76.16 | 1062.41 | 0.00 | 0.00 |
August | 1130.92 | 440.20 | 953.32 | 16.90 | 936.42 | 0.00 | 0.00 |
September | 674.68 | 779.25 | 730.92 | 0.18 | 730.74 | 0.00 | 0.00 |
October | 246.93 | 1184.12 | 543.45 | 0.00 | 543.45 | 0.00 | 0.00 |
November | 58.32 | 1797.58 | 380.15 | 0.00 | 380.15 | 0.00 | 0.00 |
December | 0.20 | 2607.22 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Annual Sum or Average | 541.78 | 1340.63 | 714.32 | 20.61 | 693.71 | 0.00 | 0.00 |
Minimum of Months | 0.20 | 373.28 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Maximum of Months | 1385.48 | 2942.33 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 227.29 | 1769.00 | 518.77 | 213.48 | 305.30 | 0.00 | 0.00 |
February | 397.92 | 1408.78 | 687.63 | 302.36 | 385.27 | 0.00 | 0.00 |
March | 717.77 | 938.12 | 934.28 | 370.84 | 563.44 | 0.00 | 0.00 |
April | 1097.44 | 686.53 | 1147.21 | 502.40 | 644.81 | 0.00 | 0.00 |
May | 1607.85 | 423.99 | 1440.80 | 629.56 | 811.23 | 0.00 | 0.00 |
June | 1972.62 | 291.33 | 1585.56 | 690.49 | 895.07 | 0.00 | 0.00 |
July | 2044.23 | 252.38 | 1602.59 | 739.47 | 863.12 | 0.00 | 0.00 |
August | 1724.61 | 294.60 | 1350.96 | 582.43 | 768.53 | 0.00 | 0.00 |
September | 1414.95 | 502.92 | 1204.93 | 569.39 | 635.54 | 0.00 | 0.00 |
October | 668.98 | 745.83 | 767.87 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 235.39 | 1114.94 | 453.05 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 157.76 | 1605.58 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1025.64 | 833.51 | 1005.28 | 435.54 | 569.74 | 0.00 | 0.00 |
Minimum of Months | 157.76 | 252.38 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2044.23 | 1769.00 | 1602.59 | 739.47 | 895.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2008.46 | 2411.54 | 2258.40 | 1545.48 | 712.93 | 0.00 | 0.00 |
February | 2241.53 | 1958.08 | 2419.84 | 1634.86 | 784.98 | 0.00 | 0.00 |
March | 2049.16 | 1428.99 | 2105.80 | 1108.85 | 996.96 | 0.00 | 0.00 |
April | 2057.00 | 1088.83 | 1897.19 | 886.97 | 1010.22 | 0.00 | 0.00 |
May | 1803.35 | 685.63 | 1571.76 | 426.12 | 1145.63 | 0.00 | 0.00 |
June | 1952.92 | 464.11 | 1525.94 | 310.69 | 1215.25 | 0.00 | 0.00 |
July | 2162.16 | 400.49 | 1615.31 | 407.02 | 1208.30 | 0.00 | 0.00 |
August | 2474.27 | 473.12 | 1819.92 | 652.67 | 1167.25 | 0.00 | 0.00 |
September | 2789.84 | 789.32 | 2205.36 | 1162.04 | 1043.32 | 0.00 | 0.00 |
October | 2544.58 | 1142.38 | 2302.86 | 1444.72 | 858.14 | 0.00 | 0.00 |
November | 1631.66 | 1603.58 | 1737.50 | 1087.71 | 649.79 | 0.00 | 0.00 |
December | 1767.33 | 2251.36 | 1852.79 | 1403.47 | 449.32 | 0.00 | 0.00 |
Annual Sum or Average | 2122.72 | 1221.37 | 1939.91 | 1002.29 | 937.62 | 0.00 | 0.00 |
Minimum of Months | 1631.66 | 400.49 | 1525.94 | 310.69 | 449.32 | 0.00 | 0.00 |
Maximum of Months | 2789.84 | 2411.54 | 2419.84 | 1634.86 | 1215.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.68 | 1814.11 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 494.58 | 1461.18 | 754.42 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 684.34 | 968.91 | 900.62 | 335.08 | 565.54 | 0.00 | 0.00 |
April | 1345.60 | 715.07 | 1313.73 | 649.62 | 664.11 | 0.00 | 0.00 |
May | 1477.20 | 448.59 | 1317.53 | 526.32 | 791.21 | 0.00 | 0.00 |
June | 1938.02 | 312.55 | 1545.97 | 669.98 | 875.98 | 0.00 | 0.00 |
July | 2143.25 | 275.77 | 1659.90 | 788.48 | 871.42 | 0.00 | 0.00 |
August | 1883.60 | 317.21 | 1451.17 | 665.99 | 785.18 | 0.00 | 0.00 |
September | 1387.80 | 525.91 | 1174.68 | 557.56 | 617.12 | 0.00 | 0.00 |
October | 758.84 | 777.92 | 818.57 | 363.93 | 454.64 | 0.00 | 0.00 |
November | 301.07 | 1141.68 | 489.97 | 181.19 | 308.78 | 0.00 | 0.00 |
December | 205.75 | 1642.50 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Annual Sum or Average | 1074.25 | 864.01 | 1027.58 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 205.75 | 275.77 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Maximum of Months | 2143.25 | 1814.11 | 1659.90 | 788.48 | 875.98 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4889264.93 | 0.776019E+10 | 0.972653E+09 | 0.00 | 0.972653E+09 | 0.00 | 0.00 |
February | 74927652.53 | 0.560641E+10 | 0.111380E+10 | 0.00 | 0.111380E+10 | 0.00 | 0.00 |
March | 0.611950E+09 | 0.393433E+10 | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.00 | 0.00 |
April | 0.117769E+10 | 0.262433E+10 | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.00 | 0.00 |
May | 0.245718E+10 | 0.161555E+10 | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.00 | 0.00 |
June | 0.359603E+10 | 0.107711E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
July | 0.363947E+10 | 0.973468E+09 | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.00 | 0.00 |
August | 0.303317E+10 | 0.113908E+10 | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.00 | 0.00 |
September | 0.177745E+10 | 0.191012E+10 | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.00 | 0.00 |
October | 0.721289E+09 | 0.295267E+10 | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.00 | 0.00 |
November | 0.175240E+09 | 0.444308E+10 | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.00 | 0.00 |
December | 1447740.26 | 0.680569E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172707E+11 | 0.408420E+11 | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.00 | 0.00 |
Minimum of Months | 1447740.26 | 0.973468E+09 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363947E+10 | 0.776019E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.614161E+09 | 0.466942E+10 | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.00 | 0.00 |
February | 0.975930E+09 | 0.332082E+10 | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.00 | 0.00 |
March | 0.195063E+10 | 0.241876E+10 | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.00 | 0.00 |
April | 0.286602E+10 | 0.169558E+10 | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.00 | 0.00 |
May | 0.431793E+10 | 0.109942E+10 | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.00 | 0.00 |
June | 0.511981E+10 | 0.730353E+09 | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.00 | 0.00 |
July | 0.547676E+10 | 0.659091E+09 | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.00 | 0.00 |
August | 0.462593E+10 | 0.764404E+09 | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.00 | 0.00 |
September | 0.368933E+10 | 0.123965E+10 | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.00 | 0.00 |
October | 0.185049E+10 | 0.186363E+10 | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.00 | 0.00 |
November | 0.639409E+09 | 0.275904E+10 | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.00 | 0.00 |
December | 0.431086E+09 | 0.419664E+10 | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.325575E+11 | 0.254168E+11 | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.431086E+09 | 0.659091E+09 | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547676E+10 | 0.466942E+10 | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.540086E+10 | 0.633240E+10 | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.00 | 0.00 |
February | 0.545255E+10 | 0.459164E+10 | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.00 | 0.00 |
March | 0.551701E+10 | 0.368099E+10 | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.00 | 0.00 |
April | 0.534703E+10 | 0.268836E+10 | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.00 | 0.00 |
May | 0.483340E+10 | 0.177110E+10 | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.00 | 0.00 |
June | 0.505821E+10 | 0.116013E+10 | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.00 | 0.00 |
July | 0.578108E+10 | 0.104289E+10 | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.00 | 0.00 |
August | 0.662082E+10 | 0.122452E+10 | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.00 | 0.00 |
September | 0.724840E+10 | 0.194547E+10 | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.00 | 0.00 |
October | 0.687575E+10 | 0.286192E+10 | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.00 | 0.00 |
November | 0.428279E+10 | 0.395891E+10 | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.00 | 0.00 |
December | 0.476204E+10 | 0.585599E+10 | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.671799E+11 | 0.371143E+11 | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.428279E+10 | 0.104289E+10 | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.724840E+10 | 0.633240E+10 | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.635861E+09 | 0.478215E+10 | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.00 | 0.00 |
February | 0.120357E+10 | 0.344263E+10 | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.00 | 0.00 |
March | 0.184705E+10 | 0.249772E+10 | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.00 | 0.00 |
April | 0.349655E+10 | 0.176293E+10 | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.00 | 0.00 |
May | 0.395967E+10 | 0.115728E+10 | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.00 | 0.00 |
June | 0.502013E+10 | 0.781318E+09 | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.00 | 0.00 |
July | 0.573261E+10 | 0.717741E+09 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
August | 0.504074E+10 | 0.821122E+09 | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.00 | 0.00 |
September | 0.361177E+10 | 0.129332E+10 | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.00 | 0.00 |
October | 0.207144E+10 | 0.194270E+10 | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.00 | 0.00 |
November | 0.802864E+09 | 0.282320E+10 | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.00 | 0.00 |
December | 0.556841E+09 | 0.428643E+10 | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339791E+11 | 0.263085E+11 | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.556841E+09 | 0.717741E+09 | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.573261E+10 | 0.478215E+10 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5533969.15 | 0.775096E+10 | 0.972632E+09 | 0.00 | 0.972632E+09 | 0.00 | 0.00 |
February | 77974096.52 | 0.561167E+10 | 0.111377E+10 | 0.00 | 0.111377E+10 | 0.00 | 0.00 |
March | 0.666530E+09 | 0.390863E+10 | 0.184805E+10 | 0.00 | 0.184805E+10 | 0.00 | 0.00 |
April | 0.128451E+10 | 0.254334E+10 | 0.206463E+10 | 10172229.45 | 0.205445E+10 | 0.00 | 0.00 |
May | 0.261780E+10 | 0.151850E+10 | 0.278205E+10 | 0.104570E+09 | 0.267748E+10 | 0.00 | 0.00 |
June | 0.369125E+10 | 0.104269E+10 | 0.314669E+10 | 0.285601E+09 | 0.286109E+10 | 0.00 | 0.00 |
July | 0.371518E+10 | 0.953237E+09 | 0.304948E+10 | 0.203975E+09 | 0.284550E+10 | 0.00 | 0.00 |
August | 0.306749E+10 | 0.115507E+10 | 0.255331E+10 | 45251342.94 | 0.250806E+10 | 0.00 | 0.00 |
September | 0.177090E+10 | 0.201704E+10 | 0.189450E+10 | 469748.23 | 0.189403E+10 | 0.00 | 0.00 |
October | 0.673476E+09 | 0.319488E+10 | 0.145555E+10 | 0.00 | 0.145555E+10 | 0.00 | 0.00 |
November | 0.156593E+09 | 0.468454E+10 | 0.985328E+09 | 0.00 | 0.985328E+09 | 0.00 | 0.00 |
December | 704049.30 | 0.694154E+10 | 0.660448E+09 | 0.00 | 0.660448E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177279E+11 | 0.413221E+11 | 0.225264E+11 | 0.650039E+09 | 0.218764E+11 | 0.00 | 0.00 |
Minimum of Months | 704049.30 | 0.953237E+09 | 0.660448E+09 | 0.00 | 0.660448E+09 | 0.00 | 0.00 |
Maximum of Months | 0.371518E+10 | 0.775096E+10 | 0.314669E+10 | 0.285601E+09 | 0.286109E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.624488E+09 | 0.468930E+10 | 0.138946E+10 | 0.571764E+09 | 0.817694E+09 | 0.00 | 0.00 |
February | 0.990358E+09 | 0.335726E+10 | 0.166349E+10 | 0.731466E+09 | 0.932021E+09 | 0.00 | 0.00 |
March | 0.200151E+10 | 0.242973E+10 | 0.250233E+10 | 0.993247E+09 | 0.150909E+10 | 0.00 | 0.00 |
April | 0.293991E+10 | 0.168058E+10 | 0.297351E+10 | 0.130219E+10 | 0.167132E+10 | 0.00 | 0.00 |
May | 0.439767E+10 | 0.108041E+10 | 0.385897E+10 | 0.168619E+10 | 0.217278E+10 | 0.00 | 0.00 |
June | 0.517285E+10 | 0.734074E+09 | 0.410971E+10 | 0.178971E+10 | 0.232000E+10 | 0.00 | 0.00 |
July | 0.551882E+10 | 0.671825E+09 | 0.429232E+10 | 0.198057E+10 | 0.231176E+10 | 0.00 | 0.00 |
August | 0.465042E+10 | 0.797298E+09 | 0.361835E+10 | 0.155994E+10 | 0.205840E+10 | 0.00 | 0.00 |
September | 0.368548E+10 | 0.133886E+10 | 0.312313E+10 | 0.147584E+10 | 0.164730E+10 | 0.00 | 0.00 |
October | 0.180095E+10 | 0.205874E+10 | 0.205662E+10 | 0.859031E+09 | 0.119759E+10 | 0.00 | 0.00 |
November | 0.615908E+09 | 0.292803E+10 | 0.117428E+10 | 0.381427E+09 | 0.792854E+09 | 0.00 | 0.00 |
December | 0.429155E+09 | 0.429682E+10 | 0.939929E+09 | 0.403627E+09 | 0.536302E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328275E+11 | 0.260629E+11 | 0.317021E+11 | 0.137350E+11 | 0.179671E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429155E+09 | 0.671825E+09 | 0.939929E+09 | 0.381427E+09 | 0.536302E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551882E+10 | 0.468930E+10 | 0.429232E+10 | 0.198057E+10 | 0.232000E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.554311E+10 | 0.627566E+10 | 0.604867E+10 | 0.413923E+10 | 0.190944E+10 | 0.00 | 0.00 |
February | 0.558181E+10 | 0.463803E+10 | 0.585385E+10 | 0.395490E+10 | 0.189895E+10 | 0.00 | 0.00 |
March | 0.566710E+10 | 0.368919E+10 | 0.563997E+10 | 0.296981E+10 | 0.267016E+10 | 0.00 | 0.00 |
April | 0.548773E+10 | 0.265593E+10 | 0.491734E+10 | 0.229894E+10 | 0.261840E+10 | 0.00 | 0.00 |
May | 0.500336E+10 | 0.169100E+10 | 0.420965E+10 | 0.114128E+10 | 0.306837E+10 | 0.00 | 0.00 |
June | 0.516922E+10 | 0.112857E+10 | 0.395510E+10 | 0.805273E+09 | 0.314983E+10 | 0.00 | 0.00 |
July | 0.586057E+10 | 0.104236E+10 | 0.432631E+10 | 0.109011E+10 | 0.323620E+10 | 0.00 | 0.00 |
August | 0.667309E+10 | 0.127751E+10 | 0.487430E+10 | 0.174803E+10 | 0.312627E+10 | 0.00 | 0.00 |
September | 0.727254E+10 | 0.209787E+10 | 0.571608E+10 | 0.301189E+10 | 0.270419E+10 | 0.00 | 0.00 |
October | 0.686863E+10 | 0.317833E+10 | 0.616774E+10 | 0.386938E+10 | 0.229836E+10 | 0.00 | 0.00 |
November | 0.429254E+10 | 0.420641E+10 | 0.450343E+10 | 0.281922E+10 | 0.168420E+10 | 0.00 | 0.00 |
December | 0.482307E+10 | 0.595136E+10 | 0.496233E+10 | 0.375890E+10 | 0.120343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.682428E+11 | 0.378322E+11 | 0.611747E+11 | 0.316070E+11 | 0.295678E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429254E+10 | 0.104236E+10 | 0.395510E+10 | 0.805273E+09 | 0.120343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.727254E+10 | 0.627566E+10 | 0.616774E+10 | 0.413923E+10 | 0.323620E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.653558E+09 | 0.479794E+10 | 0.137800E+10 | 0.557556E+09 | 0.820449E+09 | 0.00 | 0.00 |
February | 0.123098E+10 | 0.347607E+10 | 0.182506E+10 | 0.899331E+09 | 0.925726E+09 | 0.00 | 0.00 |
March | 0.190701E+10 | 0.250962E+10 | 0.241218E+10 | 0.897460E+09 | 0.151472E+10 | 0.00 | 0.00 |
April | 0.357089E+10 | 0.176702E+10 | 0.340515E+10 | 0.168378E+10 | 0.172137E+10 | 0.00 | 0.00 |
May | 0.404420E+10 | 0.113655E+10 | 0.352883E+10 | 0.140968E+10 | 0.211915E+10 | 0.00 | 0.00 |
June | 0.507406E+10 | 0.787677E+09 | 0.400710E+10 | 0.173657E+10 | 0.227052E+10 | 0.00 | 0.00 |
July | 0.577323E+10 | 0.742507E+09 | 0.444582E+10 | 0.211183E+10 | 0.233399E+10 | 0.00 | 0.00 |
August | 0.506754E+10 | 0.866747E+09 | 0.388676E+10 | 0.178376E+10 | 0.210300E+10 | 0.00 | 0.00 |
September | 0.360869E+10 | 0.139966E+10 | 0.304473E+10 | 0.144518E+10 | 0.159955E+10 | 0.00 | 0.00 |
October | 0.203815E+10 | 0.214679E+10 | 0.219242E+10 | 0.974722E+09 | 0.121770E+10 | 0.00 | 0.00 |
November | 0.786813E+09 | 0.299781E+10 | 0.126997E+10 | 0.469634E+09 | 0.800340E+09 | 0.00 | 0.00 |
December | 0.563196E+09 | 0.438718E+10 | 0.100923E+10 | 0.475765E+09 | 0.533467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.343183E+11 | 0.270156E+11 | 0.324052E+11 | 0.144453E+11 | 0.179600E+11 | 0.00 | 0.00 |
Minimum of Months | 0.563196E+09 | 0.742507E+09 | 0.100923E+10 | 0.469634E+09 | 0.533467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.577323E+10 | 0.479794E+10 | 0.444582E+10 | 0.211183E+10 | 0.233399E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4236350.09 | 0.788074E+10 | 0.972653E+09 | 0.00 | 0.972653E+09 | 0.00 | 0.00 |
February | 68360093.94 | 0.574984E+10 | 0.111380E+10 | 0.00 | 0.111380E+10 | 0.00 | 0.00 |
March | 0.590671E+09 | 0.408204E+10 | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.00 | 0.00 |
April | 0.115786E+10 | 0.276101E+10 | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.00 | 0.00 |
May | 0.243906E+10 | 0.167671E+10 | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.00 | 0.00 |
June | 0.359117E+10 | 0.111500E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
July | 0.364315E+10 | 0.999805E+09 | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.00 | 0.00 |
August | 0.302906E+10 | 0.117903E+10 | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.00 | 0.00 |
September | 0.174877E+10 | 0.201980E+10 | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.00 | 0.00 |
October | 0.661378E+09 | 0.317155E+10 | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.00 | 0.00 |
November | 0.151175E+09 | 0.465933E+10 | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.00 | 0.00 |
December | 536309.60 | 0.698317E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170854E+11 | 0.422780E+11 | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.00 | 0.00 |
Minimum of Months | 536309.60 | 0.999805E+09 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364315E+10 | 0.788074E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.608786E+09 | 0.473808E+10 | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.00 | 0.00 |
February | 0.962639E+09 | 0.340811E+10 | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.00 | 0.00 |
March | 0.192248E+10 | 0.251266E+10 | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.00 | 0.00 |
April | 0.284457E+10 | 0.177950E+10 | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.00 | 0.00 |
May | 0.430646E+10 | 0.113561E+10 | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.00 | 0.00 |
June | 0.511302E+10 | 0.755127E+09 | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.00 | 0.00 |
July | 0.547527E+10 | 0.675966E+09 | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.00 | 0.00 |
August | 0.461921E+10 | 0.789055E+09 | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.00 | 0.00 |
September | 0.366756E+10 | 0.130358E+10 | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.00 | 0.00 |
October | 0.179179E+10 | 0.199762E+10 | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.00 | 0.00 |
November | 0.610121E+09 | 0.288993E+10 | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.00 | 0.00 |
December | 0.422547E+09 | 0.430039E+10 | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.323445E+11 | 0.262856E+11 | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.422547E+09 | 0.675966E+09 | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547527E+10 | 0.473808E+10 | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.537947E+10 | 0.645908E+10 | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.00 | 0.00 |
February | 0.542272E+10 | 0.473699E+10 | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.00 | 0.00 |
March | 0.548848E+10 | 0.382740E+10 | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.00 | 0.00 |
April | 0.533173E+10 | 0.282225E+10 | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.00 | 0.00 |
May | 0.483010E+10 | 0.183639E+10 | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.00 | 0.00 |
June | 0.506196E+10 | 0.120297E+10 | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.00 | 0.00 |
July | 0.579114E+10 | 0.107267E+10 | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.00 | 0.00 |
August | 0.662708E+10 | 0.126720E+10 | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.00 | 0.00 |
September | 0.723127E+10 | 0.204591E+10 | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.00 | 0.00 |
October | 0.681539E+10 | 0.305975E+10 | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.00 | 0.00 |
November | 0.422926E+10 | 0.415648E+10 | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.00 | 0.00 |
December | 0.473362E+10 | 0.603005E+10 | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.669422E+11 | 0.385171E+11 | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.422926E+10 | 0.107267E+10 | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.723127E+10 | 0.645908E+10 | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.633922E+09 | 0.485892E+10 | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.00 | 0.00 |
February | 0.119649E+10 | 0.353489E+10 | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.00 | 0.00 |
March | 0.183294E+10 | 0.259514E+10 | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.00 | 0.00 |
April | 0.348779E+10 | 0.185346E+10 | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.00 | 0.00 |
May | 0.395654E+10 | 0.120149E+10 | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.00 | 0.00 |
June | 0.502336E+10 | 0.810139E+09 | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.00 | 0.00 |
July | 0.574048E+10 | 0.738615E+09 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
August | 0.504504E+10 | 0.849615E+09 | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.00 | 0.00 |
September | 0.359718E+10 | 0.136317E+10 | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.00 | 0.00 |
October | 0.203247E+10 | 0.208359E+10 | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.00 | 0.00 |
November | 0.780381E+09 | 0.295923E+10 | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.00 | 0.00 |
December | 0.551081E+09 | 0.439927E+10 | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.338777E+11 | 0.272475E+11 | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.551081E+09 | 0.738615E+09 | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.574048E+10 | 0.485892E+10 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.593866E+10 | -0.516671E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -771954384.6 | 58.99 | 0.00 | 0.00 |
February | 0.547368E+10 | -0.479036E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -683318494.2 | 58.99 | 0.00 | 0.00 |
March | 0.634830E+10 | -0.561420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -734108772.7 | 58.98 | 0.00 | 0.00 |
April | 0.554890E+10 | -0.485746E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -691443064.4 | 58.98 | 0.00 | 0.00 |
May | 0.560039E+10 | -0.490390E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696482524.6 | 58.98 | 0.00 | 0.00 |
June | 0.521270E+10 | -0.454154E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671158688.5 | 58.98 | 0.00 | 0.00 |
July | 0.472734E+10 | -0.403667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690670966.3 | 58.98 | 0.00 | 0.00 |
August | 0.503880E+10 | -0.434692E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691875627.0 | 58.98 | 0.00 | 0.00 |
September | 0.463758E+10 | -0.396703E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670548406.6 | 58.98 | 0.00 | 0.00 |
October | 0.500852E+10 | -0.430393E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -704591208.7 | 58.99 | 0.00 | 0.00 |
November | 0.523172E+10 | -0.452657E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -705151690.3 | 58.98 | 0.00 | 0.00 |
December | 0.553925E+10 | -0.478206E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -757185920.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.643058E+11 | -0.558373E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.846849E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463758E+10 | -0.561420E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -771954384.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.634830E+10 | -0.396703E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -670548406.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7173.57 | 37.33 | 205.17 | 243.67 | 5918.12 | 38.14 | 202.83 | 221.00 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8488.30 | 37.55 | 222.33 | 255.33 | 2483.37 | 28.91 | 193.33 | 237.67 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7738.37 | 30.40 | 270.33 | 327.00 | 1484.78 | 21.70 | 208.00 | 293.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2331.30 | 19.15 | 9.50 | 346.67 | 1394.56 | 21.38 | 166.67 | 301.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1795.27 | 18.76 | 0.00 | 395.33 | 1005.10 | 20.96 | 210.17 | 351.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:40 | 1829.58 | 19.00 | 0.00 | 396.00 | 1039.59 | 21.22 | 234.00 | 354.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1900.00 | 19.30 | 2.33 | 406.00 | 1090.27 | 21.51 | 251.83 | 366.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2109.23 | 19.20 | 3.17 | 378.67 | 1187.54 | 21.40 | 252.00 | 345.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 3065.24 | 20.95 | 46.50 | 332.67 | 1510.84 | 21.92 | 215.00 | 303.17 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7307.99 | 33.26 | 293.33 | 305.83 | 1966.05 | 23.12 | 204.17 | 283.00 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5114.54 | 32.64 | 233.50 | 247.83 | 2785.27 | 31.00 | 227.67 | 226.00 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6237.10 | 36.22 | 168.83 | 219.17 | 5730.91 | 39.69 | 184.33 | 185.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4126.55 | 25.32 | 1455.00 | 3854.17 | 1949.07 | 24.49 | 2550.00 | 3469.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1795.27 | 18.76 | 0.00 | 219.17 | 1005.10 | 20.96 | 166.67 | 185.50 | |
Maximum of Months | 428.67 | 0.50 | 0.48 | 8488.30 | 37.55 | 293.33 | 406.00 | 5918.12 | 39.69 | 252.00 | 366.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 1884.87 | 22.26 | 66.17 | 229.00 | 964.71 | 22.74 | 94.33 | 185.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2331.30 | 23.30 | 78.50 | 241.50 | 1290.26 | 23.97 | 95.67 | 205.50 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:49 | 2957.87 | 21.74 | 103.33 | 320.83 | 1269.19 | 22.76 | 110.83 | 281.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:40 | 3481.23 | 21.43 | 77.33 | 347.67 | 2086.32 | 23.66 | 78.50 | 311.67 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3633.41 | 22.20 | 136.33 | 403.00 | 1567.50 | 22.21 | 81.50 | 361.83 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3284.43 | 20.96 | 95.67 | 404.50 | 1808.27 | 22.98 | 79.00 | 374.00 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4146.90 | 22.47 | 123.33 | 414.33 | 1811.64 | 22.64 | 73.17 | 380.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3295.14 | 21.25 | 110.83 | 381.00 | 1501.79 | 22.59 | 84.50 | 356.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3330.24 | 22.26 | 95.17 | 330.33 | 1883.19 | 23.52 | 101.67 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:30 | 2087.77 | 20.97 | 88.67 | 291.67 | 1148.28 | 23.05 | 111.50 | 261.33 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:40 | 1643.47 | 21.35 | 82.00 | 234.17 | 876.79 | 22.41 | 85.00 | 191.67 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1477.51 | 21.82 | 64.17 | 197.67 | 793.86 | 23.28 | 74.50 | 129.17 |
Annual Sum or Average | 3807.33 | 0.50 | 2972.75 | 21.79 | 1121.50 | 3795.67 | 1481.74 | 22.92 | 1070.17 | 3337.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1477.51 | 20.96 | 64.17 | 197.67 | 793.86 | 22.21 | 73.17 | 129.17 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4146.90 | 23.30 | 136.33 | 414.33 | 2086.32 | 23.97 | 111.50 | 380.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 659.94 | 15.79 | 0.00 | 211.67 | 404.37 | 18.30 | 0.50 | 134.00 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-08:00 | 695.93 | 16.16 | 0.00 | 226.50 | 434.22 | 18.63 | 0.00 | 164.67 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 943.38 | 17.67 | 0.00 | 317.67 | 550.12 | 19.88 | 8.00 | 263.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1111.14 | 18.63 | 0.00 | 349.00 | 686.60 | 20.80 | 89.00 | 292.33 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-05:00 | 1259.71 | 19.97 | 31.33 | 413.83 | 716.86 | 22.06 | 179.33 | 378.67 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1522.18 | 22.72 | 96.50 | 413.83 | 890.45 | 24.08 | 266.67 | 392.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1430.34 | 20.80 | 55.50 | 424.17 | 846.33 | 22.95 | 247.83 | 396.67 |
August | 410.83 | 0.49 | 0.48 | 01-AUG-05:49 | 1184.09 | 18.94 | 0.17 | 390.50 | 694.25 | 21.08 | 154.83 | 359.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 982.80 | 18.33 | 0.00 | 330.33 | 605.89 | 20.53 | 30.17 | 284.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:19 | 773.47 | 16.69 | 0.00 | 281.83 | 459.50 | 19.00 | 0.00 | 226.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:20 | 656.02 | 15.68 | 0.00 | 221.67 | 374.26 | 17.95 | 0.00 | 142.83 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:09 | 481.23 | 14.36 | 0.00 | 172.33 | 304.10 | 17.03 | 0.00 | 65.17 |
Annual Sum or Average | 3807.33 | 0.50 | 1047.75 | 18.49 | 183.50 | 3753.33 | 620.83 | 20.65 | 976.33 | 3100.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 481.23 | 14.36 | 0.00 | 172.33 | 304.10 | 17.03 | 0.00 | 65.17 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1522.18 | 22.72 | 96.50 | 424.17 | 890.45 | 24.08 | 266.67 | 396.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:50 | 2047.84 | 23.86 | 84.17 | 228.17 | 1187.38 | 24.35 | 94.50 | 185.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-08:00 | 2333.26 | 21.49 | 63.33 | 239.83 | 1320.39 | 23.60 | 84.00 | 208.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2532.25 | 21.43 | 94.50 | 323.17 | 1370.47 | 22.60 | 110.83 | 286.17 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4544.84 | 22.41 | 84.50 | 349.83 | 1894.47 | 21.81 | 51.83 | 301.67 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2718.55 | 17.76 | 50.50 | 402.67 | 1479.66 | 18.88 | 2.00 | 367.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:40 | 3474.50 | 18.23 | 50.33 | 405.50 | 1593.50 | 19.32 | 0.67 | 369.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3857.60 | 18.72 | 56.00 | 412.33 | 1712.69 | 19.54 | 5.83 | 380.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3239.17 | 20.13 | 84.67 | 386.33 | 1827.65 | 21.57 | 62.00 | 353.67 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3369.61 | 22.48 | 97.00 | 334.00 | 1985.55 | 23.86 | 90.50 | 301.67 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-07:30 | 2143.47 | 21.00 | 86.67 | 292.83 | 1171.44 | 22.87 | 97.50 | 260.33 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1697.18 | 21.16 | 83.83 | 235.50 | 924.62 | 22.10 | 78.00 | 194.33 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-08:00 | 1555.45 | 20.81 | 55.00 | 201.17 | 891.44 | 22.91 | 64.17 | 126.33 |
Annual Sum or Average | 3807.33 | 0.50 | 2919.37 | 20.46 | 890.50 | 3811.33 | 1501.23 | 21.60 | 741.83 | 3334.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1555.45 | 17.76 | 50.33 | 201.17 | 891.44 | 18.88 | 0.67 | 126.33 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4544.84 | 23.86 | 97.00 | 412.33 | 1985.55 | 24.35 | 110.83 | 380.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 6969.50 | 36.98 | 205.17 | 243.00 | 5762.31 | 37.76 | 200.17 | 219.33 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8300.74 | 37.32 | 222.33 | 254.33 | 2338.74 | 26.89 | 105.67 | 235.83 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7595.58 | 29.51 | 251.50 | 325.50 | 1382.71 | 18.89 | 14.33 | 290.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2208.95 | 15.48 | 0.00 | 345.00 | 1304.34 | 19.03 | 29.50 | 296.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1717.95 | 15.00 | 0.00 | 393.17 | 953.34 | 18.48 | 2.83 | 348.50 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 1753.34 | 15.45 | 0.00 | 393.17 | 990.42 | 18.94 | 2.17 | 352.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1818.04 | 15.77 | 0.00 | 404.67 | 1036.50 | 19.27 | 10.67 | 362.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2011.48 | 15.52 | 0.00 | 376.17 | 1120.05 | 19.01 | 18.67 | 342.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 2927.44 | 17.47 | 26.00 | 330.83 | 1408.27 | 19.46 | 44.50 | 300.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7158.20 | 32.70 | 290.83 | 304.00 | 1851.41 | 20.35 | 37.00 | 280.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4975.82 | 32.23 | 228.83 | 246.50 | 2682.88 | 29.91 | 184.83 | 224.50 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6046.15 | 35.39 | 167.50 | 217.33 | 5581.35 | 39.49 | 184.17 | 181.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4002.77 | 22.94 | 1392.17 | 3833.67 | 1859.09 | 22.37 | 834.50 | 3434.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1717.95 | 15.00 | 0.00 | 217.33 | 953.34 | 18.48 | 2.17 | 181.50 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8300.74 | 37.32 | 290.83 | 404.67 | 5762.31 | 39.49 | 200.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 1828.03 | 21.71 | 65.67 | 226.83 | 922.12 | 22.50 | 86.67 | 179.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2188.93 | 20.83 | 62.83 | 239.00 | 1239.91 | 23.76 | 89.17 | 203.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:49 | 2885.22 | 21.26 | 101.17 | 318.83 | 1212.62 | 22.56 | 94.50 | 279.00 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:49 | 3384.60 | 20.96 | 77.33 | 346.17 | 1974.74 | 22.63 | 64.67 | 308.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3546.58 | 21.76 | 135.83 | 401.17 | 1500.37 | 22.02 | 79.50 | 358.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3183.21 | 20.50 | 95.67 | 402.33 | 1720.22 | 22.19 | 68.33 | 368.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4044.51 | 22.02 | 123.33 | 412.50 | 1736.99 | 22.47 | 70.83 | 376.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3207.51 | 20.79 | 110.67 | 379.67 | 1434.73 | 22.41 | 77.50 | 353.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3238.12 | 21.80 | 95.17 | 327.67 | 1810.53 | 23.32 | 91.00 | 294.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2026.16 | 20.48 | 88.17 | 289.67 | 1100.56 | 22.84 | 98.33 | 258.67 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:49 | 1598.34 | 20.89 | 81.17 | 231.67 | 843.16 | 22.01 | 76.83 | 186.17 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1432.91 | 21.33 | 64.00 | 193.17 | 732.51 | 21.81 | 64.00 | 123.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2888.07 | 21.20 | 1101.00 | 3768.67 | 1415.29 | 22.52 | 961.33 | 3289.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1432.91 | 20.48 | 62.83 | 193.17 | 732.51 | 21.81 | 64.00 | 123.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4044.51 | 22.02 | 135.83 | 412.50 | 1974.74 | 23.76 | 98.33 | 376.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 634.11 | 12.16 | 0.00 | 208.83 | 390.41 | 15.89 | 0.00 | 127.67 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:09 | 669.88 | 12.67 | 0.00 | 224.83 | 420.40 | 16.38 | 0.00 | 159.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 910.06 | 14.15 | 0.00 | 315.00 | 531.70 | 17.63 | 0.00 | 257.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1072.15 | 15.46 | 0.00 | 347.33 | 666.05 | 18.97 | 13.00 | 285.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1209.69 | 15.43 | 3.17 | 411.83 | 692.06 | 19.98 | 45.50 | 375.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1457.50 | 19.31 | 75.50 | 412.50 | 859.04 | 22.28 | 111.83 | 390.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1379.26 | 17.69 | 30.67 | 422.67 | 817.66 | 21.06 | 91.50 | 394.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1141.95 | 15.59 | 0.00 | 388.83 | 671.05 | 19.10 | 12.67 | 356.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 947.06 | 15.19 | 0.00 | 327.67 | 586.90 | 18.67 | 0.00 | 276.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:19 | 745.30 | 13.11 | 0.00 | 279.00 | 444.10 | 16.68 | 0.00 | 219.83 |
November | 254.83 | 0.53 | 0.48 | 01-NOV-08:20 | 631.98 | 11.82 | 0.00 | 219.17 | 360.75 | 15.37 | 0.00 | 134.33 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:50 | 461.95 | 10.47 | 0.00 | 166.00 | 293.89 | 14.39 | 0.00 | 58.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1008.33 | 14.94 | 109.33 | 3723.67 | 600.00 | 18.54 | 274.50 | 3035.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 461.95 | 10.47 | 0.00 | 166.00 | 293.89 | 14.39 | 0.00 | 58.50 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1457.50 | 19.31 | 75.50 | 422.67 | 859.04 | 22.28 | 111.83 | 394.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:50 | 1992.72 | 23.50 | 84.17 | 226.33 | 1144.95 | 24.27 | 93.83 | 179.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-09:09 | 2262.91 | 21.08 | 63.33 | 238.00 | 1264.79 | 23.51 | 82.00 | 205.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2465.63 | 21.02 | 94.00 | 320.50 | 1318.44 | 22.47 | 105.67 | 282.33 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4342.73 | 21.97 | 84.50 | 347.83 | 1810.44 | 21.67 | 49.33 | 296.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2637.20 | 17.26 | 49.83 | 400.83 | 1419.11 | 18.70 | 0.50 | 364.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3334.18 | 17.74 | 50.33 | 403.33 | 1519.64 | 19.14 | 0.00 | 367.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3749.51 | 18.23 | 56.00 | 410.50 | 1630.93 | 19.37 | 3.67 | 378.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3146.76 | 19.67 | 84.50 | 384.00 | 1747.67 | 21.42 | 59.83 | 351.00 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3281.62 | 22.06 | 97.00 | 332.67 | 1882.86 | 23.72 | 87.50 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2059.45 | 20.28 | 83.00 | 290.50 | 1120.33 | 22.76 | 95.67 | 257.50 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:30 | 1598.00 | 19.49 | 70.17 | 233.00 | 888.57 | 21.99 | 77.33 | 190.83 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-09:09 | 1509.96 | 20.40 | 55.00 | 198.83 | 855.64 | 22.83 | 63.17 | 120.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2821.85 | 19.91 | 871.83 | 3786.33 | 1435.22 | 21.47 | 718.50 | 3290.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1509.96 | 17.26 | 49.83 | 198.83 | 855.64 | 18.70 | 0.00 | 120.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4342.73 | 23.50 | 97.00 | 410.50 | 1882.86 | 24.27 | 105.67 | 378.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 6969.51 | 36.98 | 205.17 | 243.00 | 5762.19 | 37.76 | 200.17 | 219.33 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8300.71 | 37.32 | 222.33 | 254.33 | 2338.62 | 26.89 | 105.67 | 235.83 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7595.45 | 29.51 | 251.50 | 325.50 | 1382.60 | 18.89 | 14.33 | 290.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2208.84 | 15.48 | 0.00 | 345.00 | 1304.25 | 19.03 | 29.67 | 296.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1717.85 | 15.00 | 0.00 | 393.17 | 953.26 | 18.48 | 2.83 | 348.50 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 1753.25 | 15.46 | 0.00 | 393.17 | 990.35 | 18.94 | 2.17 | 352.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.94 | 15.78 | 0.00 | 404.67 | 1036.42 | 19.27 | 10.67 | 362.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2011.36 | 15.53 | 0.00 | 376.17 | 1119.96 | 19.01 | 18.67 | 342.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 2927.32 | 17.47 | 26.00 | 330.83 | 1408.17 | 19.46 | 44.50 | 300.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7158.12 | 32.70 | 290.83 | 304.00 | 1851.31 | 20.35 | 37.17 | 280.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4975.78 | 32.24 | 228.83 | 246.50 | 2682.78 | 29.91 | 184.83 | 224.50 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6046.18 | 35.39 | 167.50 | 217.33 | 5581.28 | 39.49 | 184.17 | 181.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4002.69 | 22.94 | 1392.17 | 3833.67 | 1858.99 | 22.37 | 834.83 | 3434.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1717.85 | 15.00 | 0.00 | 217.33 | 953.26 | 18.48 | 2.17 | 181.50 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8300.71 | 37.32 | 290.83 | 404.67 | 5762.19 | 39.49 | 200.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 1828.01 | 21.71 | 65.67 | 226.83 | 922.08 | 22.50 | 86.83 | 179.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2188.91 | 20.83 | 62.83 | 239.00 | 1239.86 | 23.76 | 89.17 | 203.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:49 | 2885.16 | 21.26 | 101.17 | 318.83 | 1212.55 | 22.56 | 94.50 | 279.00 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:49 | 3384.56 | 20.96 | 77.33 | 346.17 | 1974.67 | 22.63 | 64.67 | 308.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3546.50 | 21.76 | 135.83 | 401.17 | 1500.29 | 22.02 | 79.50 | 358.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3183.14 | 20.50 | 95.67 | 402.33 | 1720.13 | 22.19 | 68.33 | 368.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4044.45 | 22.02 | 123.33 | 412.50 | 1736.91 | 22.47 | 71.00 | 376.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3207.45 | 20.79 | 110.67 | 379.67 | 1434.65 | 22.41 | 77.67 | 353.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3238.09 | 21.80 | 95.17 | 327.67 | 1810.45 | 23.32 | 91.00 | 294.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2026.12 | 20.48 | 88.17 | 289.67 | 1100.50 | 22.84 | 98.50 | 258.67 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:49 | 1598.30 | 20.90 | 81.17 | 231.67 | 843.11 | 22.01 | 76.83 | 186.17 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1432.90 | 21.33 | 64.00 | 193.17 | 732.48 | 21.81 | 64.00 | 123.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2888.03 | 21.20 | 1101.00 | 3768.67 | 1415.22 | 22.52 | 962.00 | 3289.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1432.90 | 20.48 | 62.83 | 193.17 | 732.48 | 21.81 | 64.00 | 123.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4044.45 | 22.02 | 135.83 | 412.50 | 1974.67 | 23.76 | 98.50 | 376.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 634.10 | 12.17 | 0.00 | 208.83 | 390.39 | 15.89 | 0.00 | 127.67 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:09 | 669.87 | 12.67 | 0.00 | 224.83 | 420.38 | 16.38 | 0.00 | 159.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 910.02 | 14.15 | 0.00 | 315.00 | 531.66 | 17.63 | 0.00 | 257.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1072.12 | 15.46 | 0.00 | 347.33 | 666.01 | 18.97 | 13.00 | 285.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1209.64 | 15.43 | 3.17 | 411.83 | 692.01 | 19.98 | 45.50 | 375.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1457.46 | 19.32 | 75.50 | 412.50 | 858.98 | 22.28 | 112.00 | 390.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1379.22 | 17.69 | 30.67 | 422.67 | 817.61 | 21.06 | 91.50 | 394.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1141.91 | 15.59 | 0.00 | 388.83 | 671.00 | 19.10 | 12.67 | 356.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 947.04 | 15.19 | 0.00 | 327.67 | 586.87 | 18.67 | 0.00 | 276.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:19 | 745.27 | 13.11 | 0.00 | 279.00 | 444.07 | 16.68 | 0.00 | 219.83 |
November | 254.83 | 0.53 | 0.48 | 01-NOV-08:20 | 631.95 | 11.82 | 0.00 | 219.17 | 360.72 | 15.37 | 0.00 | 134.33 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:50 | 461.94 | 10.47 | 0.00 | 166.00 | 293.88 | 14.39 | 0.00 | 58.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1008.30 | 14.94 | 109.33 | 3723.67 | 599.96 | 18.54 | 274.67 | 3035.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 461.94 | 10.47 | 0.00 | 166.00 | 293.88 | 14.39 | 0.00 | 58.50 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1457.46 | 19.32 | 75.50 | 422.67 | 858.98 | 22.28 | 112.00 | 394.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:50 | 1992.70 | 23.50 | 84.17 | 226.33 | 1144.90 | 24.27 | 93.83 | 179.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-09:09 | 2262.89 | 21.08 | 63.33 | 238.00 | 1264.74 | 23.51 | 82.00 | 205.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2465.57 | 21.02 | 94.00 | 320.50 | 1318.37 | 22.48 | 105.67 | 282.33 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4342.69 | 21.98 | 84.50 | 347.83 | 1810.36 | 21.67 | 49.33 | 296.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2637.14 | 17.26 | 49.83 | 400.83 | 1419.04 | 18.70 | 0.50 | 364.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3334.11 | 17.74 | 50.33 | 403.33 | 1519.56 | 19.14 | 0.00 | 367.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3749.44 | 18.23 | 56.00 | 410.50 | 1630.84 | 19.37 | 3.67 | 378.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3146.70 | 19.68 | 84.50 | 384.00 | 1747.59 | 21.42 | 59.83 | 351.00 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3281.59 | 22.06 | 97.00 | 332.67 | 1882.79 | 23.72 | 87.50 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2059.41 | 20.28 | 83.00 | 290.50 | 1120.27 | 22.76 | 95.67 | 257.50 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:30 | 1597.96 | 19.49 | 70.17 | 233.00 | 888.52 | 21.99 | 77.33 | 190.83 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-09:09 | 1509.95 | 20.40 | 55.00 | 198.83 | 855.61 | 22.83 | 63.17 | 120.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2821.80 | 19.91 | 871.83 | 3786.33 | 1435.15 | 21.47 | 718.50 | 3290.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1509.95 | 17.26 | 49.83 | 198.83 | 855.61 | 18.70 | 0.00 | 120.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4342.69 | 23.50 | 97.00 | 410.50 | 1882.79 | 24.27 | 105.67 | 378.17 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.199030E+10 | 20255.14 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641125E+09 | 20255.14 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49234258.29 | 20255.14 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161861E+09 | 20255.14 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.474794E+09 | 20255.14 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199030E+10 | 20255.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110171E+11 | 12418.00 | 31-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748313E+10 | 14003.85 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.583632E+10 | 11134.69 | 20-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295725E+10 | 11163.09 | 11-APR-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.717946E+09 | 11110.02 | 19-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.237048E+09 | 11021.80 | 02-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4149296.91 | 4330.01 | 24-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35683154.46 | 9958.34 | 16-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482679E+09 | 11308.65 | 19-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130828E+10 | 11124.13 | 03-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.446841E+10 | 11159.28 | 20-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.844781E+10 | 11169.37 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4149296.91 | 4330.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110171E+11 | 14003.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.532982E+10 | 10246.31 | 30-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327359E+10 | 11288.36 | 02-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158161E+10 | 9402.45 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.479298E+09 | 9353.50 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 375853.30 | 2505.69 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 267361.52 | 567.14 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14611899.42 | 7475.31 | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137993E+10 | 9389.78 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356486E+10 | 9407.18 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.532982E+10 | 11288.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.895145E+10 | 8637.42 | 31-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.610659E+10 | 9740.66 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348464E+10 | 7736.74 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118750E+10 | 7747.96 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32329309.28 | 7704.20 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6026103.13 | 5715.24 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95078426.69 | 7693.89 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246004E+10 | 7756.98 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.599624E+10 | 7767.16 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.895145E+10 | 9740.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550738E+10 | 10851.40 | 30-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.335334E+10 | 11015.69 | 02-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174769E+10 | 9987.20 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.425030E+09 | 9931.94 | 29-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7988534.19 | 6860.50 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3638997.02 | 3802.83 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18914212.83 | 8429.52 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141067E+10 | 9933.04 | 20-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360142E+10 | 9981.47 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.550738E+10 | 11015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561831E+10 | 25845.34 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279523E+10 | 25845.34 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993354E+09 | 25845.34 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161529E+09 | 25845.34 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155187E+10 | 25845.34 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346770E+10 | 25845.34 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561831E+10 | 25845.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.547950E+10 | 14142.97 | 31-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290852E+10 | 15653.91 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148291E+10 | 12975.21 | 13-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365282E+09 | 12937.12 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2804244.57 | 5803.06 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8231536.59 | 10003.81 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82560477.70 | 12789.56 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188322E+10 | 12976.64 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447834E+10 | 12968.89 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.547950E+10 | 15653.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.495792E+10 | 11501.94 | 12-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269420E+10 | 11914.55 | 02-FEB-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111067E+10 | 11452.21 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236879E+09 | 11457.98 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 153335.03 | 1022.23 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4707930.74 | 6891.56 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74323571.97 | 10853.58 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164583E+10 | 11573.66 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.367208E+10 | 11504.26 | 19-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.495792E+10 | 11914.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848953E+10 | 9262.09 | 31-JAN-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.511043E+10 | 10615.88 | 02-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229223E+10 | 8434.64 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.502740E+09 | 8424.07 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2966966.08 | 6358.97 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14069143.36 | 8301.27 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170413E+09 | 8331.50 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285699E+10 | 8406.35 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618117E+10 | 8407.33 | 27-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848953E+10 | 10615.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.518732E+10 | 11836.73 | 12-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290636E+10 | 11859.11 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127279E+10 | 11801.80 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251849E+09 | 11779.31 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2320990.88 | 4657.02 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10790357.28 | 7019.82 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88942023.54 | 11731.14 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173951E+10 | 11910.54 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382304E+10 | 11839.13 | 19-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.518732E+10 | 11910.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115623E+11 | 30945.01 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.718516E+10 | 33544.86 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325763E+10 | 30595.80 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766709E+09 | 30546.76 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12380003.25 | 20493.83 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233869E+09 | 30241.38 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440103E+10 | 30717.68 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877786E+10 | 30592.91 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115623E+11 | 33544.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848581E+10 | 15001.88 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492334E+10 | 17190.37 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274841E+10 | 14147.29 | 13-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.886105E+09 | 14119.78 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21758228.49 | 11622.13 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67490478.03 | 13968.07 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.437093E+09 | 14135.55 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334071E+10 | 14178.95 | 20-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704074E+10 | 14140.56 | 04-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848581E+10 | 17190.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.727043E+10 | 11820.44 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.428964E+10 | 13017.75 | 02-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199099E+10 | 11656.57 | 18-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570876E+09 | 11639.49 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3807471.94 | 6864.96 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42268756.35 | 11522.56 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352186E+09 | 11660.75 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280111E+10 | 11624.33 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.569949E+10 | 11620.05 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.727043E+10 | 13017.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120345E+11 | 11790.23 | 31-JAN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767797E+10 | 13349.04 | 02-FEB-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392679E+10 | 10410.70 | 14-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113538E+10 | 10388.53 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24173677.40 | 10340.69 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113437E+09 | 10387.13 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.830612E+09 | 10390.58 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.470046E+10 | 10453.83 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.926705E+10 | 10408.17 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120345E+11 | 13349.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.749168E+10 | 12919.58 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.450764E+10 | 14005.02 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223126E+10 | 12740.48 | 18-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607506E+09 | 12639.14 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15373805.62 | 7438.61 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67522344.68 | 12594.00 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.425071E+09 | 12745.04 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286085E+10 | 12705.21 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.579064E+10 | 12700.57 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.749168E+10 | 14005.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318093E+11 | 40607.16 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212542E+11 | 40607.16 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133155E+11 | 28287.89 | 06-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.574969E+10 | 22211.75 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.340413E+09 | 8248.30 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27294202.21 | 3260.41 | 03-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 60563.58 | 491.81 | 07-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471677E+09 | 9983.49 | 29-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.321656E+10 | 14147.86 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114854E+11 | 34817.00 | 25-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231312E+11 | 40607.16 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318093E+11 | 40607.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.295124E+11 | 40223.93 | 06-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203010E+11 | 40223.93 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129671E+11 | 27247.23 | 06-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578421E+10 | 21335.27 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377337E+09 | 8367.95 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57023934.33 | 3477.36 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 443459.00 | 1047.20 | 07-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.646346E+09 | 10576.62 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374047E+10 | 15725.39 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113438E+11 | 33055.56 | 25-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221301E+11 | 39129.44 | 09-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.295124E+11 | 40223.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332327E+11 | 39883.31 | 05-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220233E+11 | 39883.31 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137275E+11 | 26749.02 | 06-MAR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.615688E+10 | 20312.00 | 03-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457435E+09 | 10851.67 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103999E+09 | 4436.03 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3957950.58 | 2171.04 | 07-AUG-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.836657E+09 | 13851.69 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.419929E+10 | 16227.20 | 23-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125732E+11 | 34781.37 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246762E+11 | 39313.44 | 09-DEC-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332327E+11 | 39883.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.116292E+09 | 94216212.00 | 6111.36 | 25-MAR-15:00 | 5181.06 | 0.00 |
April | 0.00 | 0.00 | 0.453814E+10 | 0.345747E+10 | 58380.17 | 18-APR-12:00 | 39773.54 | 0.00 |
May | 0.00 | 0.00 | 0.115077E+11 | 0.857268E+10 | 57668.10 | 31-MAY-12:00 | 45645.92 | 0.00 |
June | 0.00 | 0.00 | 0.381478E+11 | 0.280170E+11 | 111510.90 | 26-JUN-07:50 | 49820.63 | 0.00 |
July | 0.00 | 0.00 | 0.547012E+11 | 0.366766E+11 | 102796.16 | 05-JUL-06:03 | 40834.76 | 0.00 |
August | 0.00 | 0.00 | 0.538375E+11 | 0.370471E+11 | 112608.62 | 04-AUG-06:03 | 32784.31 | 0.00 |
September | 0.00 | 0.00 | 0.222536E+11 | 0.196330E+11 | 89334.05 | 11-SEP-09:50 | 53256.16 | 0.00 |
October | 0.00 | 0.00 | 0.125403E+10 | 0.106579E+10 | 27907.64 | 20-OCT-15:00 | 27907.64 | 0.00 |
November | 0.00 | 0.00 | 42421124.71 | 37773063.14 | 3632.49 | 03-NOV-14:00 | 3342.29 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186399E+12 | 0.134602E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.547012E+11 | 0.370471E+11 | 112608.62 | 53256.16 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.127795E+09 | 0.109301E+09 | 7086.62 | 25-MAR-15:00 | 6596.12 | 0.00 |
April | 0.00 | 0.00 | 0.511804E+10 | 0.398167E+10 | 64477.73 | 18-APR-12:30 | 45651.37 | 0.00 |
May | 0.00 | 0.00 | 0.134609E+11 | 0.100100E+11 | 66525.00 | 30-MAY-11:00 | 41538.71 | 0.00 |
June | 0.00 | 0.00 | 0.394593E+11 | 0.291128E+11 | 109290.78 | 26-JUN-07:55 | 49557.63 | 0.00 |
July | 0.00 | 0.00 | 0.539496E+11 | 0.361654E+11 | 107279.89 | 03-JUL-08:50 | 50555.60 | 0.00 |
August | 0.00 | 0.00 | 0.502978E+11 | 0.346391E+11 | 110192.79 | 04-AUG-06:03 | 32147.34 | 0.00 |
September | 0.00 | 0.00 | 0.203387E+11 | 0.178897E+11 | 80184.41 | 11-SEP-06:03 | 40164.28 | 0.00 |
October | 0.00 | 0.00 | 0.116070E+10 | 0.975088E+09 | 26446.31 | 20-OCT-15:00 | 26446.31 | 0.00 |
November | 0.00 | 0.00 | 64290289.50 | 54071156.88 | 5909.86 | 03-NOV-13:30 | 4826.92 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.183977E+12 | 0.132937E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.539496E+11 | 0.361654E+11 | 110192.79 | 50555.60 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.130721E+09 | 0.107656E+09 | 7182.26 | 25-MAR-15:00 | 6334.82 | 0.00 |
April | 0.00 | 0.00 | 0.559596E+10 | 0.436753E+10 | 71540.00 | 16-APR-13:42 | 44880.16 | 0.00 |
May | 0.00 | 0.00 | 0.144017E+11 | 0.107951E+11 | 68738.95 | 30-MAY-14:00 | 59167.84 | 0.00 |
June | 0.00 | 0.00 | 0.423218E+11 | 0.315991E+11 | 118246.47 | 26-JUN-06:03 | 47876.83 | 0.00 |
July | 0.00 | 0.00 | 0.569730E+11 | 0.383399E+11 | 108307.92 | 05-JUL-06:03 | 43009.50 | 0.00 |
August | 0.00 | 0.00 | 0.519366E+11 | 0.362458E+11 | 122888.60 | 04-AUG-06:03 | 36204.39 | 0.00 |
September | 0.00 | 0.00 | 0.208780E+11 | 0.182921E+11 | 80749.09 | 11-SEP-10:00 | 49819.50 | 0.00 |
October | 0.00 | 0.00 | 0.113308E+10 | 0.928267E+09 | 25795.55 | 20-OCT-15:00 | 25795.55 | 0.00 |
November | 0.00 | 0.00 | 37434905.75 | 31270865.11 | 3346.37 | 03-NOV-14:00 | 2888.50 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193408E+12 | 0.140707E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.569730E+11 | 0.383399E+11 | 122888.60 | 59167.84 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2081.30 | 7364.41 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2132.67 | 7412.97 | 16-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2252.01 | 7403.02 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2025.99 | 7199.97 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1985.23 | 6841.54 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1908.26 | 6405.35 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1658.92 | 5967.51 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1779.04 | 5736.70 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1683.71 | 5899.77 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1760.09 | 6280.48 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1900.16 | 6707.46 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1936.21 | 7087.36 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1924.10 | ||||
Minimum of Months | 0.00 | 0.00 | 1658.92 | 5736.70 | ||
Maximum of Months | 0.00 | 0.00 | 2252.01 | 7412.97 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165289E+10 | 0.40 | 2563.51 | 05-JAN-07:02 | 0.86 |
February | 0.125644E+10 | 0.36 | 2563.51 | 01-FEB-07:01 | 0.86 |
March | 0.126478E+10 | 0.34 | 2563.51 | 06-MAR-07:01 | 0.86 |
April | 0.140401E+10 | 0.33 | 5245.25 | 18-APR-15:10 | 1.29 |
May | 0.204015E+10 | 0.37 | 6029.94 | 31-MAY-15:10 | 1.40 |
June | 0.383027E+10 | 0.50 | 10289.31 | 26-JUN-06:03 | 1.97 |
July | 0.457341E+10 | 0.53 | 9420.25 | 03-JUL-15:10 | 1.86 |
August | 0.483827E+10 | 0.55 | 10289.31 | 03-AUG-07:10 | 1.96 |
September | 0.317262E+10 | 0.45 | 10289.31 | 11-SEP-06:03 | 1.97 |
October | 0.139937E+10 | 0.32 | 3183.17 | 20-OCT-15:30 | 0.96 |
November | 0.124241E+10 | 0.33 | 2563.51 | 27-NOV-07:01 | 0.86 |
December | 0.135549E+10 | 0.35 | 2563.51 | 13-DEC-07:01 | 0.86 |
Annual Sum or Average | 0.280301E+11 | 0.40 | |||
Minimum of Months | 0.124241E+10 | 0.32 | 2563.51 | 0.86 | |
Maximum of Months | 0.483827E+10 | 0.55 | 10289.31 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161500E+10 | 0.42 | 2749.72 | 02-JAN-05:01 | 0.91 |
February | 0.120126E+10 | 0.36 | 2749.72 | 01-FEB-06:01 | 0.92 |
March | 0.123100E+10 | 0.35 | 2749.72 | 01-MAR-06:01 | 0.91 |
April | 0.153477E+10 | 0.35 | 7439.22 | 18-APR-15:00 | 1.64 |
May | 0.232414E+10 | 0.40 | 7969.70 | 30-MAY-14:05 | 1.71 |
June | 0.413657E+10 | 0.53 | 9910.26 | 12-JUN-06:03 | 1.97 |
July | 0.453746E+10 | 0.54 | 9910.26 | 03-JUL-08:50 | 1.96 |
August | 0.444265E+10 | 0.54 | 9910.26 | 04-AUG-06:03 | 1.96 |
September | 0.277129E+10 | 0.43 | 9691.36 | 11-SEP-06:03 | 1.94 |
October | 0.120596E+10 | 0.31 | 2853.08 | 20-OCT-15:10 | 0.93 |
November | 0.115972E+10 | 0.34 | 2749.72 | 13-NOV-06:01 | 0.91 |
December | 0.135024E+10 | 0.37 | 2749.72 | 01-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.275101E+11 | 0.41 | |||
Minimum of Months | 0.115972E+10 | 0.31 | 2749.72 | 0.91 | |
Maximum of Months | 0.453746E+10 | 0.54 | 9910.26 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207908E+10 | 0.50 | 2681.90 | 02-JAN-05:01 | 0.83 |
February | 0.159078E+10 | 0.45 | 2681.90 | 01-FEB-05:01 | 0.83 |
March | 0.145817E+10 | 0.40 | 2681.90 | 01-MAR-06:01 | 0.83 |
April | 0.160980E+10 | 0.37 | 7157.59 | 18-APR-15:00 | 1.46 |
May | 0.226717E+10 | 0.40 | 7878.45 | 30-MAY-15:20 | 1.55 |
June | 0.394113E+10 | 0.49 | 11358.75 | 26-JUN-06:03 | 1.95 |
July | 0.421070E+10 | 0.49 | 9487.27 | 03-JUL-15:00 | 1.74 |
August | 0.404510E+10 | 0.49 | 10470.54 | 04-AUG-07:10 | 1.84 |
September | 0.248137E+10 | 0.41 | 8775.92 | 07-SEP-15:50 | 1.66 |
October | 0.125156E+10 | 0.33 | 2681.90 | 16-OCT-05:01 | 0.83 |
November | 0.145939E+10 | 0.41 | 2681.90 | 10-NOV-07:01 | 0.83 |
December | 0.176887E+10 | 0.44 | 2681.90 | 01-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.281631E+11 | 0.43 | |||
Minimum of Months | 0.125156E+10 | 0.33 | 2681.90 | 0.83 | |
Maximum of Months | 0.421070E+10 | 0.50 | 11358.75 | 1.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 56.82 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 55.38 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.15 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.24 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 55.59 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 55.45 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.70 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.02 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.08 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.04 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 55.47 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 55.66 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.38 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.04 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.44 | 56.44 | 2081.30 | 7364.41 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.95 | 55.95 | 2132.67 | 7412.97 | 16-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 56.70 | 56.70 | 2252.01 | 7403.02 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.73 | 56.73 | 2025.99 | 7199.97 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.52 | 56.52 | 1985.23 | 6841.54 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.20 | 56.20 | 1908.26 | 6405.35 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.23 | 57.23 | 1658.92 | 5967.51 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.01 | 57.01 | 1779.04 | 5736.70 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.53 | 56.53 | 1683.71 | 5899.77 | 28-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.53 | 56.53 | 1760.09 | 6280.48 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.04 | 56.04 | 1900.16 | 6707.46 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.15 | 56.15 | 1936.21 | 7087.36 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1924.10 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.95 | 55.95 | 1658.92 | 5736.70 | ||
Maximum of Months | 0.00 | 0.00 | 57.23 | 57.23 | 2252.01 | 7412.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.344489E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.221142E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.139946E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.752349E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.547145E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.126817E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.165710E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.167506E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.878110E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.314223E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111345E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.234406E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176054E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.314223E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.344489E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.313476E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176160E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.841612E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.423843E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.543494E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.130110E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.163599E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.155626E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.749265E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.190619E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.108538E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.229726E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155212E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.190619E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.313476E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.489238E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.301745E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.156473E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.687461E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.566086E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.134926E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.167392E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.155947E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.762789E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.381075E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.195734E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.383446E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.222464E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.381075E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.489238E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165289E+10 | 0.00 | 0.646053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125644E+10 | 0.00 | 0.421119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126478E+10 | 0.116292E+09 | 0.260149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140401E+10 | 0.453814E+10 | 0.107988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204015E+10 | 0.115077E+11 | 0.109905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.383027E+10 | 0.381478E+11 | 0.264342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.457341E+10 | 0.547012E+11 | 4149296.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.483827E+10 | 0.538375E+11 | 35743718.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317262E+10 | 0.222536E+11 | 0.964288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139937E+10 | 0.125403E+10 | 0.465345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124241E+10 | 42421124.71 | 0.213663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135549E+10 | 0.00 | 0.452163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280301E+11 | 0.186399E+12 | 0.217135E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124241E+10 | 0.00 | 4149296.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.483827E+10 | 0.547012E+11 | 0.646053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161500E+10 | 0.00 | 0.592449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120126E+10 | 0.00 | 0.367157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123100E+10 | 0.127795E+09 | 0.201190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153477E+10 | 0.511804E+10 | 0.730249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232414E+10 | 0.134609E+11 | 0.385582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.413657E+10 | 0.394593E+11 | 57023934.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.453746E+10 | 0.539496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.444265E+10 | 0.502978E+11 | 443459.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.277129E+10 | 0.203387E+11 | 0.684145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120596E+10 | 0.116070E+10 | 0.415671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115972E+10 | 64290289.50 | 0.210212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135024E+10 | 0.00 | 0.437524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275101E+11 | 0.183977E+12 | 0.193440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.453746E+10 | 0.539496E+11 | 0.592449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207908E+10 | 0.00 | 0.800774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159078E+10 | 0.00 | 0.506071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145817E+10 | 0.130721E+09 | 0.278826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160980E+10 | 0.559596E+10 | 0.101235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226717E+10 | 0.144017E+11 | 0.522548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.394113E+10 | 0.423218E+11 | 0.103999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.421070E+10 | 0.569730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.404510E+10 | 0.519366E+11 | 3957950.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248137E+10 | 0.208780E+11 | 0.113976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125156E+10 | 0.113308E+10 | 0.647812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145939E+10 | 37434905.75 | 0.306773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176887E+10 | 0.00 | 0.612520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281631E+11 | 0.193408E+12 | 0.268868E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.421070E+10 | 0.569730E+11 | 0.800774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126478E+10 | 0.00 | 0.00 | 0.00 | 30313739.60 | 0.126995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140401E+10 | 0.00 | 0.00 | 0.00 | 0.107040E+10 | 0.504908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204015E+10 | 0.00 | 0.00 | 0.00 | 0.267265E+10 | 0.758640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.383027E+10 | 0.00 | 0.00 | 0.00 | 0.861439E+10 | 0.237048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.457341E+10 | 0.00 | 0.00 | 0.00 | 0.119934E+11 | 4149296.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.483827E+10 | 0.00 | 0.00 | 0.00 | 0.118767E+11 | 35683154.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317262E+10 | 0.00 | 0.00 | 0.00 | 0.511587E+10 | 0.492611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139937E+10 | 0.00 | 0.00 | 0.00 | 0.305972E+09 | 0.143689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124241E+10 | 0.00 | 0.00 | 0.00 | 11153333.54 | 0.988090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280301E+11 | 0.00 | 0.00 | 0.00 | 0.416909E+11 | 0.106333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4149296.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.483827E+10 | 0.00 | 0.00 | 0.00 | 0.119934E+11 | 0.327960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123100E+10 | 0.00 | 0.00 | 0.00 | 33173470.33 | 0.715195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153477E+10 | 0.00 | 0.00 | 0.00 | 0.118538E+10 | 0.151828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232414E+10 | 0.00 | 0.00 | 0.00 | 0.310255E+10 | 8245536.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.413657E+10 | 0.00 | 0.00 | 0.00 | 0.887444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.453746E+10 | 0.00 | 0.00 | 0.00 | 0.118224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.444265E+10 | 0.00 | 0.00 | 0.00 | 0.111200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.277129E+10 | 0.00 | 0.00 | 0.00 | 0.468356E+10 | 37798967.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120596E+10 | 0.00 | 0.00 | 0.00 | 0.283993E+09 | 0.416239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115972E+10 | 0.00 | 0.00 | 0.00 | 16625296.99 | 0.967742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275101E+11 | 0.00 | 0.00 | 0.00 | 0.411221E+11 | 0.865796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.453746E+10 | 0.00 | 0.00 | 0.00 | 0.118224E+11 | 0.297326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.207908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145817E+10 | 0.00 | 0.00 | 0.00 | 34036167.74 | 0.141551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160980E+10 | 0.00 | 0.00 | 0.00 | 0.129824E+10 | 0.396658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226717E+10 | 0.00 | 0.00 | 0.00 | 0.332858E+10 | 65113183.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.394113E+10 | 0.00 | 0.00 | 0.00 | 0.955151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.421070E+10 | 0.00 | 0.00 | 0.00 | 0.125285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.404510E+10 | 0.00 | 0.00 | 0.00 | 0.115496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.248137E+10 | 0.00 | 0.00 | 0.00 | 0.484343E+10 | 0.303099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125156E+10 | 0.00 | 0.00 | 0.00 | 0.280362E+09 | 0.227883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145939E+10 | 0.00 | 0.00 | 0.00 | 9869529.05 | 0.181042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281631E+11 | 0.00 | 0.00 | 0.00 | 0.434241E+11 | 0.150877E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.421070E+10 | 0.00 | 0.00 | 0.00 | 0.125285E+11 | 0.468447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182745E+10 | 0.00 | 0.00 | 0.27 |
February | 0.168669E+11 | 0.00 | 0.00 | 7872.64 | 0.00 | 0.502661E+09 | 48780529.53 | 0.00 | 0.28 |
March | 0.128446E+11 | 0.00 | 0.00 | 5425489.91 | 0.00 | 41188766.58 | 0.387915E+10 | 0.00 | 0.33 |
April | 0.578804E+10 | 0.209060E+09 | 0.00 | 12597514.68 | 26649108.47 | 0.00 | 0.785544E+10 | 0.00 | 0.39 |
May | 0.122585E+10 | 0.215274E+09 | 0.00 | 26879130.44 | 18255800.68 | 0.00 | 0.122109E+11 | 0.00 | 0.68 |
June | 0.456723E+09 | 0.250667E+10 | 0.00 | 22960333.38 | 0.124904E+09 | 0.00 | 0.797144E+10 | 0.00 | 0.77 |
July | 0.370231E+09 | 0.435022E+10 | 0.00 | 15356537.94 | 0.430089E+09 | 0.00 | 0.327015E+10 | 0.00 | 0.77 |
August | 0.488552E+09 | 0.438249E+10 | 0.00 | 22457819.63 | 0.183020E+09 | 0.00 | 0.498521E+10 | 0.00 | 0.82 |
September | 0.105750E+10 | 0.473921E+09 | 0.00 | 28451140.40 | 51899354.07 | 0.00 | 0.118634E+11 | 0.00 | 0.69 |
October | 0.272813E+10 | 0.00 | 0.00 | 21403344.41 | 652258.66 | 0.00 | 0.127846E+11 | 0.00 | 0.43 |
November | 0.931222E+10 | 0.00 | 0.00 | 8742819.07 | 0.00 | 96981857.22 | 0.683286E+10 | 0.00 | 0.35 |
December | 0.180143E+11 | 0.00 | 0.00 | 18203.99 | 0.00 | 0.630678E+09 | 0.162021E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.886838E+11 | 0.121376E+11 | 0.00 | 0.164300E+09 | 0.835469E+09 | 0.309896E+10 | 0.718640E+11 | 0.00 | 0.51 |
Minimum of Months | 0.370231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.195308E+11 | 0.438249E+10 | 0.00 | 28451140.40 | 0.430089E+09 | 0.182745E+10 | 0.127846E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847733E+10 | 0.00 | 0.00 | 0.27 |
February | 0.141811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333653E+10 | 0.00 | 0.00 | 0.28 |
March | 0.147208E+11 | 0.00 | 0.00 | 337889.52 | 0.00 | 0.702905E+09 | 0.658152E+09 | 0.00 | 0.31 |
April | 0.857011E+10 | 0.101562E+09 | 0.00 | 4973255.32 | 0.103267E+09 | 91242563.17 | 0.367077E+10 | 0.00 | 0.36 |
May | 0.250886E+10 | 0.198422E+09 | 0.00 | 15939364.58 | 95125069.54 | 0.00 | 0.834446E+10 | 0.00 | 0.56 |
June | 0.101392E+10 | 0.220448E+10 | 0.00 | 16223960.95 | 0.159404E+09 | 0.00 | 0.556161E+10 | 0.00 | 0.61 |
July | 0.491521E+09 | 0.377181E+10 | 0.00 | 11434981.91 | 0.409606E+09 | 0.00 | 0.236217E+10 | 0.00 | 0.63 |
August | 0.634059E+09 | 0.359130E+10 | 0.00 | 15933622.09 | 0.215335E+09 | 0.00 | 0.350413E+10 | 0.00 | 0.64 |
September | 0.257010E+10 | 0.396291E+09 | 0.00 | 16074279.52 | 50912454.64 | 0.00 | 0.692740E+10 | 0.00 | 0.52 |
October | 0.792964E+10 | 0.00 | 0.00 | 4220949.39 | 1440101.26 | 0.00 | 0.377530E+10 | 0.00 | 0.33 |
November | 0.108454E+11 | 0.00 | 0.00 | 1518396.96 | 0.00 | 0.182435E+10 | 0.172055E+10 | 0.00 | 0.30 |
December | 0.142454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435907E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.911955E+11 | 0.102639E+11 | 0.00 | 86656700.23 | 0.103509E+10 | 0.187914E+11 | 0.365246E+11 | 0.00 | 0.43 |
Minimum of Months | 0.491521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.147208E+11 | 0.377181E+10 | 0.00 | 16223960.95 | 0.409606E+09 | 0.847733E+10 | 0.834446E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.637788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135441E+11 | 0.00 | 0.00 | 0.26 |
February | 0.806819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804160E+10 | 0.00 | 0.00 | 0.27 |
March | 0.122251E+11 | 0.00 | 0.00 | 156487.16 | 0.00 | 0.276767E+10 | 0.236009E+09 | 0.00 | 0.31 |
April | 0.878583E+10 | 0.111972E+09 | 0.00 | 3676169.56 | 0.105330E+09 | 0.541899E+09 | 0.241931E+10 | 0.00 | 0.35 |
May | 0.332725E+10 | 0.159867E+09 | 0.00 | 14711103.20 | 52675503.55 | 0.00 | 0.725957E+10 | 0.00 | 0.56 |
June | 0.123879E+10 | 0.212089E+10 | 0.00 | 14399658.20 | 0.251932E+09 | 0.00 | 0.514327E+10 | 0.00 | 0.63 |
July | 0.605472E+09 | 0.384847E+10 | 0.00 | 10117997.82 | 0.512544E+09 | 0.00 | 0.217655E+10 | 0.00 | 0.67 |
August | 0.851672E+09 | 0.336478E+10 | 0.00 | 14243880.21 | 0.277092E+09 | 0.00 | 0.294635E+10 | 0.00 | 0.65 |
September | 0.354799E+10 | 0.335255E+09 | 0.00 | 10693654.68 | 65137110.03 | 1071504.55 | 0.469824E+10 | 0.00 | 0.49 |
October | 0.939091E+10 | 0.00 | 0.00 | 1122531.38 | 346641.99 | 0.155928E+09 | 0.127795E+10 | 0.00 | 0.32 |
November | 0.826811E+10 | 0.00 | 0.00 | 283028.09 | 0.00 | 0.434300E+10 | 0.598988E+09 | 117.64 | 0.29 |
December | 0.740581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945304E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.700930E+11 | 0.994123E+10 | 0.00 | 69404510.30 | 0.126506E+10 | 0.388482E+11 | 0.267562E+11 | 117.64 | 0.42 |
Minimum of Months | 0.605472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.122251E+11 | 0.384847E+10 | 0.00 | 14711103.20 | 0.512544E+09 | 0.135441E+11 | 0.725957E+10 | 117.64 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694395E+10 | 0.00 | 0.00 | 0.41 |
February | 0.182036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491920E+10 | 0.00 | 0.00 | 0.37 |
March | 0.114571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251043E+10 | 0.00 | 0.00 | 0.35 |
April | 0.151631E+10 | 44433734.43 | 0.00 | 539308.76 | 16977090.99 | 0.823388E+09 | 0.319217E+09 | 0.00 | 0.39 |
May | 0.101967E+10 | 51823795.37 | 0.00 | 3335789.65 | 10838557.79 | 15458385.24 | 0.143401E+10 | 0.00 | 0.66 |
June | 0.394629E+09 | 0.718504E+09 | 0.00 | 3787144.13 | 54322781.97 | 0.00 | 0.121320E+10 | 0.00 | 0.86 |
July | 0.157923E+09 | 0.123010E+10 | 0.00 | 2785670.93 | 0.101459E+09 | 0.00 | 0.566094E+09 | 0.00 | 0.90 |
August | 0.254398E+09 | 0.105549E+10 | 0.00 | 3379325.19 | 65011199.85 | 0.00 | 0.655593E+09 | 0.00 | 0.83 |
September | 0.107744E+10 | 0.102774E+09 | 0.00 | 1909787.13 | 14303395.48 | 70528164.64 | 0.684715E+09 | 0.00 | 0.54 |
October | 0.181253E+10 | 0.00 | 0.00 | 61807.09 | 78726.52 | 0.589238E+09 | 63468791.29 | 0.00 | 0.34 |
November | 0.811324E+09 | 0.00 | 0.00 | 68.74 | 0.00 | 0.264502E+10 | 6256410.38 | 40.01 | 0.35 |
December | 47501663.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500947E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.852535E+10 | 0.320312E+10 | 0.00 | 15798901.63 | 0.262991E+09 | 0.235267E+11 | 0.494256E+10 | 40.01 | 0.53 |
Minimum of Months | 47501663.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.181253E+10 | 0.123010E+10 | 0.00 | 3787144.13 | 0.101459E+09 | 0.694395E+10 | 0.143401E+10 | 40.01 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391296E+10 | 0.00 | 0.00 | 0.38 |
February | 0.281644E+09 | 0.00 | 0.00 | 5206.60 | 0.00 | 0.253289E+10 | 5891164.38 | 0.00 | 0.33 |
March | 0.924510E+09 | 0.00 | 0.00 | 271195.80 | 0.00 | 0.109536E+10 | 0.164537E+09 | 0.00 | 0.33 |
April | 0.789783E+09 | 71794242.94 | 0.00 | 1374525.03 | 4980963.93 | 0.378703E+09 | 0.797494E+09 | 0.00 | 0.50 |
May | 0.350915E+09 | 63483741.41 | 0.00 | 4836605.98 | 1403716.00 | 2220201.80 | 0.203184E+10 | 0.00 | 1.01 |
June | 0.166281E+09 | 0.686468E+09 | 0.00 | 4715476.97 | 21158642.53 | 0.00 | 0.150309E+10 | 0.00 | 1.38 |
July | 62248752.83 | 0.113026E+10 | 0.00 | 3981786.28 | 39115158.95 | 0.00 | 0.773673E+09 | 0.00 | 1.51 |
August | 99706053.95 | 0.968500E+09 | 0.00 | 4509958.63 | 22568518.84 | 0.00 | 0.895167E+09 | 0.00 | 1.31 |
September | 0.462104E+09 | 0.108022E+09 | 0.00 | 3563838.71 | 4978741.25 | 21226673.87 | 0.109528E+10 | 0.00 | 0.87 |
October | 0.106763E+10 | 0.00 | 0.00 | 315061.85 | 46211.70 | 0.218849E+09 | 0.201054E+09 | 0.00 | 0.33 |
November | 0.492446E+09 | 0.00 | 0.00 | 38944.01 | 0.00 | 0.149418E+10 | 31567318.27 | 44.94 | 0.32 |
December | 0.119179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299222E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.493314E+10 | 0.302853E+10 | 0.00 | 23612599.87 | 94251953.21 | 0.126486E+11 | 0.749959E+10 | 44.94 | 0.72 |
Minimum of Months | 62248752.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.106763E+10 | 0.113026E+10 | 0.00 | 4836605.98 | 39115158.95 | 0.391296E+10 | 0.203184E+10 | 44.94 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103867E+10 | 0.00 | 0.00 | 618481.43 | 0.00 | 0.414058E+10 | 0.502273E+09 | 0.00 | 0.34 |
February | 0.113321E+10 | 0.00 | 0.00 | 975181.56 | 0.00 | 0.258234E+10 | 0.624004E+09 | 0.00 | 0.34 |
March | 0.130217E+10 | 0.00 | 0.00 | 2298216.71 | 0.00 | 0.150491E+10 | 0.135481E+10 | 0.00 | 0.42 |
April | 0.120199E+10 | 0.124829E+09 | 0.00 | 3354519.13 | 8401944.81 | 0.565793E+09 | 0.182388E+10 | 0.00 | 0.58 |
May | 0.716818E+09 | 79778768.04 | 0.00 | 5841700.66 | 4928640.70 | 14572040.78 | 0.245679E+10 | 0.00 | 0.87 |
June | 0.342164E+09 | 0.852053E+09 | 0.00 | 4664398.09 | 48613583.50 | 0.00 | 0.151775E+10 | 0.00 | 1.01 |
July | 0.151462E+09 | 0.152980E+10 | 0.00 | 3708331.01 | 72937245.86 | 0.00 | 0.707453E+09 | 0.00 | 1.11 |
August | 0.201899E+09 | 0.141022E+10 | 0.00 | 5953480.25 | 33017635.35 | 0.00 | 0.111586E+10 | 0.00 | 1.16 |
September | 0.734855E+09 | 0.222066E+09 | 0.00 | 6454303.84 | 4745755.75 | 39221798.18 | 0.200284E+10 | 0.00 | 0.96 |
October | 0.129645E+10 | 0.00 | 0.00 | 4610028.74 | 72717.33 | 0.243570E+09 | 0.226881E+10 | 0.00 | 0.59 |
November | 0.107899E+10 | 0.00 | 0.00 | 1075768.85 | 0.00 | 0.168347E+10 | 0.658429E+09 | 54.47 | 0.38 |
December | 0.600439E+09 | 0.00 | 0.00 | 1010865.34 | 0.00 | 0.357332E+10 | 0.760045E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.979911E+10 | 0.421875E+10 | 0.00 | 40565275.61 | 0.172718E+09 | 0.143478E+11 | 0.157929E+11 | 54.47 | 0.68 |
Minimum of Months | 0.151462E+09 | 0.00 | 0.00 | 618481.43 | 0.00 | 0.00 | 0.502273E+09 | 0.00 | 0.34 |
Maximum of Months | 0.130217E+10 | 0.152980E+10 | 0.00 | 6454303.84 | 72937245.86 | 0.414058E+10 | 0.245679E+10 | 54.47 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405522E+10 | 0.00 | 0.00 | 0.40 |
February | 0.353213E+09 | 0.00 | 0.00 | 69994.59 | 0.00 | 0.261582E+10 | 58852919.82 | 0.00 | 0.35 |
March | 0.772090E+09 | 0.00 | 0.00 | 465561.18 | 0.00 | 0.126099E+10 | 0.305004E+09 | 0.00 | 0.36 |
April | 0.750831E+09 | 51880946.40 | 0.00 | 1994484.71 | 6368840.16 | 0.387233E+09 | 0.113592E+10 | 0.00 | 0.56 |
May | 0.437306E+09 | 54896502.51 | 0.00 | 4548526.25 | 3824540.33 | 11095465.89 | 0.170010E+10 | 0.00 | 0.94 |
June | 0.214809E+09 | 0.634163E+09 | 0.00 | 3858223.79 | 19319615.70 | 0.00 | 0.120705E+10 | 0.00 | 1.25 |
July | 85452081.50 | 0.125755E+10 | 0.00 | 3431026.32 | 24943899.82 | 0.00 | 0.550134E+09 | 0.00 | 1.33 |
August | 0.126923E+09 | 0.958991E+09 | 0.00 | 4277809.79 | 18953797.97 | 0.00 | 0.744102E+09 | 0.00 | 1.26 |
September | 0.546710E+09 | 0.121657E+09 | 0.00 | 2964950.48 | 4116173.33 | 42869086.22 | 0.850372E+09 | 0.00 | 0.81 |
October | 0.938832E+09 | 0.00 | 0.00 | 1006019.56 | 46137.82 | 0.254402E+09 | 0.567500E+09 | 0.00 | 0.41 |
November | 0.560142E+09 | 0.00 | 0.00 | 112868.54 | 0.00 | 0.148589E+10 | 73202836.55 | 49.12 | 0.34 |
December | 0.231066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294839E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.526102E+10 | 0.307914E+10 | 0.00 | 22729465.21 | 77573005.13 | 0.130619E+11 | 0.719224E+10 | 49.12 | 0.70 |
Minimum of Months | 85452081.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.938832E+09 | 0.125755E+10 | 0.00 | 4548526.25 | 24943899.82 | 0.405522E+10 | 0.170010E+10 | 49.12 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93103801.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692456E+10 | 0.00 | 0.00 | 0.40 |
February | 92330299.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499602E+10 | 0.00 | 0.00 | 0.36 |
March | 0.837647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292501E+10 | 0.00 | 0.00 | 0.34 |
April | 0.137172E+10 | 15230194.18 | 0.00 | 42554.06 | 26028314.56 | 0.110792E+10 | 37467986.86 | 0.00 | 0.33 |
May | 0.149756E+10 | 33603944.85 | 0.00 | 623940.19 | 5270430.23 | 29077600.95 | 0.357298E+09 | 0.00 | 0.45 |
June | 0.503043E+09 | 0.526738E+09 | 0.00 | 2379967.77 | 28477690.69 | 0.00 | 0.720531E+09 | 0.00 | 0.60 |
July | 0.145476E+09 | 0.900290E+09 | 0.00 | 2127059.57 | 95787982.89 | 0.00 | 0.443379E+09 | 0.00 | 0.66 |
August | 0.236108E+09 | 0.920570E+09 | 0.00 | 2894905.29 | 49022969.22 | 0.00 | 0.614995E+09 | 0.00 | 0.69 |
September | 0.105809E+10 | 0.105245E+09 | 0.00 | 2076823.24 | 11479066.26 | 6171601.07 | 0.795376E+09 | 0.00 | 0.50 |
October | 0.234921E+10 | 0.00 | 0.00 | 54842.20 | 144201.25 | 91796129.21 | 81492741.94 | 0.00 | 0.33 |
November | 0.125920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219158E+10 | 0.00 | 0.00 | 0.33 |
December | 62561595.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487189E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.950603E+10 | 0.250168E+10 | 0.00 | 10200092.33 | 0.216211E+09 | 0.231440E+11 | 0.305054E+10 | 0.00 | 0.44 |
Minimum of Months | 62561595.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.234921E+10 | 0.920570E+09 | 0.00 | 2894905.29 | 95787982.89 | 0.692456E+10 | 0.795376E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404012E+10 | 0.00 | 0.00 | 0.38 |
February | 0.276535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269715E+10 | 0.00 | 0.00 | 0.33 |
March | 0.936672E+09 | 0.00 | 0.00 | 32912.23 | 0.00 | 0.128982E+10 | 33274462.35 | 0.00 | 0.32 |
April | 0.884849E+09 | 45845925.00 | 0.00 | 562028.53 | 2464904.76 | 0.450585E+09 | 0.340749E+09 | 0.00 | 0.38 |
May | 0.497252E+09 | 46321764.29 | 0.00 | 2721147.10 | 1564287.68 | 198966.45 | 0.118764E+10 | 0.00 | 0.69 |
June | 0.205442E+09 | 0.575328E+09 | 0.00 | 3697589.68 | 10684859.10 | 0.00 | 0.113088E+10 | 0.00 | 1.07 |
July | 57457145.27 | 0.930795E+09 | 0.00 | 3325278.38 | 47632541.94 | 0.00 | 0.658081E+09 | 0.00 | 1.22 |
August | 94695610.56 | 0.906339E+09 | 0.00 | 4251068.66 | 21213914.08 | 0.00 | 0.899057E+09 | 0.00 | 1.17 |
September | 0.380762E+09 | 0.117221E+09 | 0.00 | 4041867.31 | 5317955.03 | 239225.86 | 0.135261E+10 | 0.00 | 0.85 |
October | 0.114844E+10 | 0.00 | 0.00 | 667928.76 | 87328.38 | 16155251.62 | 0.439557E+09 | 0.00 | 0.34 |
November | 0.777770E+09 | 0.00 | 0.00 | 63093.11 | 0.00 | 0.123717E+10 | 59265737.01 | 0.00 | 0.31 |
December | 0.215675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287176E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.560609E+10 | 0.262185E+10 | 0.00 | 19362913.77 | 88965790.98 | 0.126032E+11 | 0.610112E+10 | 0.00 | 0.62 |
Minimum of Months | 57457145.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.114844E+10 | 0.930795E+09 | 0.00 | 4251068.66 | 47632541.94 | 0.404012E+10 | 0.135261E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890581E+10 | 0.00 | 0.00 | 0.52 |
February | 0.455388E+09 | 0.00 | 0.00 | 11583.10 | 0.00 | 0.598297E+10 | 15078966.74 | 0.00 | 0.45 |
March | 0.871017E+09 | 0.00 | 0.00 | 197502.09 | 0.00 | 0.402140E+10 | 0.124108E+09 | 0.00 | 0.44 |
April | 0.877337E+09 | 0.104370E+09 | 0.00 | 573236.40 | 5722106.39 | 0.204592E+10 | 0.282511E+09 | 0.00 | 0.43 |
May | 0.132135E+10 | 62244146.61 | 0.00 | 1087274.14 | 3992127.82 | 0.322225E+09 | 0.402619E+09 | 0.00 | 0.52 |
June | 0.575053E+09 | 0.708712E+09 | 0.00 | 2082562.92 | 33586956.29 | 0.113825E+09 | 0.546179E+09 | 0.00 | 0.67 |
July | 0.199448E+09 | 0.122019E+10 | 0.00 | 2212104.16 | 97240500.46 | 1908031.65 | 0.404757E+09 | 0.00 | 0.79 |
August | 0.241601E+09 | 0.138178E+10 | 0.00 | 4421103.63 | 42094351.45 | 21239055.43 | 0.829331E+09 | 0.00 | 0.96 |
September | 0.850570E+09 | 0.250897E+09 | 0.00 | 4923680.44 | 6897628.98 | 0.232707E+09 | 0.136191E+10 | 0.00 | 0.83 |
October | 0.151880E+10 | 76326.65 | 0.00 | 2168481.54 | 78854.00 | 0.697336E+09 | 0.122780E+10 | 0.00 | 0.49 |
November | 0.107271E+10 | 0.00 | 0.00 | 546284.10 | 0.00 | 0.314202E+10 | 0.336752E+09 | 0.00 | 0.44 |
December | 0.579231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640723E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.882866E+10 | 0.372827E+10 | 0.00 | 18223812.54 | 0.189613E+09 | 0.318946E+11 | 0.553105E+10 | 0.00 | 0.58 |
Minimum of Months | 0.199448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1908031.65 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.151880E+10 | 0.138178E+10 | 0.00 | 4923680.44 | 97240500.46 | 0.890581E+10 | 0.136191E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424436E+10 | 0.00 | 0.00 | 0.40 |
February | 0.284385E+09 | 0.00 | 0.00 | 8476.34 | 0.00 | 0.278113E+10 | 7987926.71 | 0.00 | 0.34 |
March | 0.805498E+09 | 0.00 | 0.00 | 87408.42 | 0.00 | 0.141527E+10 | 64537204.41 | 0.00 | 0.33 |
April | 0.879339E+09 | 35968289.19 | 0.00 | 841302.47 | 8754134.01 | 0.413236E+09 | 0.457624E+09 | 0.00 | 0.40 |
May | 0.632261E+09 | 42680724.94 | 0.00 | 2096357.32 | 2505766.68 | 6154032.91 | 0.802945E+09 | 0.00 | 0.61 |
June | 0.246805E+09 | 0.528578E+09 | 0.00 | 3085667.68 | 12300422.10 | 0.00 | 0.859772E+09 | 0.00 | 0.97 |
July | 70185794.77 | 0.103537E+10 | 0.00 | 2851338.35 | 25621245.99 | 0.00 | 0.467108E+09 | 0.00 | 1.07 |
August | 92921512.80 | 0.922222E+09 | 0.00 | 3951880.13 | 14944443.69 | 0.00 | 0.770989E+09 | 0.00 | 1.14 |
September | 0.472519E+09 | 0.131470E+09 | 0.00 | 3223710.73 | 4114304.24 | 4717631.45 | 0.102476E+10 | 0.00 | 0.78 |
October | 0.116451E+10 | 0.00 | 0.00 | 1035381.58 | 87007.05 | 16717015.52 | 0.584554E+09 | 0.00 | 0.39 |
November | 0.836157E+09 | 0.00 | 0.00 | 97940.64 | 0.00 | 0.122178E+10 | 75357374.22 | 0.00 | 0.32 |
December | 0.268053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284377E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.589822E+10 | 0.269629E+10 | 0.00 | 17279463.66 | 68327323.76 | 0.129471E+11 | 0.511564E+10 | 0.00 | 0.59 |
Minimum of Months | 70185794.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.116451E+10 | 0.103537E+10 | 0.00 | 3951880.13 | 25621245.99 | 0.424436E+10 | 0.102476E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631501E+10 | 0.00 | 0.00 | 0.37 |
February | 0.315288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441208E+10 | 0.00 | 0.00 | 0.33 |
March | 0.146431E+10 | 0.00 | 0.00 | 294.07 | 0.00 | 0.202853E+10 | 4335696.53 | 0.00 | 0.32 |
April | 0.175442E+10 | 49413128.12 | 0.00 | 609617.31 | 9603993.31 | 0.483265E+09 | 0.334569E+09 | 0.00 | 0.36 |
May | 0.849860E+09 | 66168181.20 | 0.00 | 3581649.56 | 19358400.93 | 2579150.42 | 0.155358E+10 | 0.00 | 0.64 |
June | 0.289437E+09 | 0.762316E+09 | 0.00 | 4195387.44 | 33319536.33 | 0.00 | 0.128727E+10 | 0.00 | 0.82 |
July | 0.120952E+09 | 0.121309E+10 | 0.00 | 2993940.87 | 84084698.55 | 0.00 | 0.584971E+09 | 0.00 | 0.84 |
August | 0.210601E+09 | 0.114621E+10 | 0.00 | 3446848.67 | 39395840.87 | 0.00 | 0.700353E+09 | 0.00 | 0.80 |
September | 0.992360E+09 | 0.124892E+09 | 0.00 | 2384001.21 | 10385037.73 | 16579865.00 | 0.891243E+09 | 0.00 | 0.54 |
October | 0.214808E+10 | 0.00 | 0.00 | 178834.36 | 304449.63 | 0.143981E+09 | 0.144159E+09 | 0.00 | 0.32 |
November | 0.110602E+10 | 0.00 | 0.00 | 9637.32 | 0.00 | 0.217854E+10 | 26920168.27 | 0.00 | 0.32 |
December | 64881681.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461213E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.945144E+10 | 0.336209E+10 | 0.00 | 17400210.80 | 0.196452E+09 | 0.201927E+11 | 0.552740E+10 | 0.00 | 0.50 |
Minimum of Months | 64881681.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.214808E+10 | 0.121309E+10 | 0.00 | 4195387.44 | 84084698.55 | 0.631501E+10 | 0.155358E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348952E+10 | 0.00 | 0.00 | 0.33 |
February | 0.356252E+09 | 0.00 | 0.00 | 17705.31 | 0.00 | 0.212153E+10 | 9283685.55 | 0.00 | 0.28 |
March | 0.852088E+09 | 0.00 | 0.00 | 371147.14 | 0.00 | 0.879552E+09 | 0.217807E+09 | 0.00 | 0.29 |
April | 0.810108E+09 | 62307195.73 | 0.00 | 1525872.21 | 3768803.07 | 0.205117E+09 | 0.822687E+09 | 0.00 | 0.46 |
May | 0.327409E+09 | 77424541.29 | 0.00 | 4781959.61 | 4446512.16 | 202497.89 | 0.197773E+10 | 0.00 | 0.96 |
June | 0.133104E+09 | 0.679428E+09 | 0.00 | 4791725.04 | 15529146.57 | 0.00 | 0.145805E+10 | 0.00 | 1.27 |
July | 51926678.28 | 0.105396E+10 | 0.00 | 4034797.59 | 41989001.26 | 0.00 | 0.763998E+09 | 0.00 | 1.37 |
August | 99009189.05 | 0.962272E+09 | 0.00 | 4391971.65 | 19549403.55 | 0.00 | 0.925554E+09 | 0.00 | 1.21 |
September | 0.405250E+09 | 0.115667E+09 | 0.00 | 3992971.89 | 4668504.89 | 4838650.20 | 0.128342E+10 | 0.00 | 0.85 |
October | 0.976281E+09 | 0.00 | 0.00 | 647212.05 | 192395.95 | 60516712.07 | 0.380667E+09 | 0.00 | 0.30 |
November | 0.552999E+09 | 0.00 | 0.00 | 93506.76 | 0.00 | 0.115845E+10 | 75367601.11 | 0.00 | 0.27 |
December | 0.197444E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253838E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.490342E+10 | 0.295106E+10 | 0.00 | 24648869.26 | 90143767.45 | 0.104581E+11 | 0.791456E+10 | 0.00 | 0.66 |
Minimum of Months | 51926678.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.976281E+09 | 0.105396E+10 | 0.00 | 4791725.04 | 41989001.26 | 0.348952E+10 | 0.197773E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116936E+10 | 0.00 | 0.00 | 892589.33 | 0.00 | 0.384819E+10 | 0.703263E+09 | 0.00 | 0.34 |
February | 0.131614E+10 | 0.00 | 0.00 | 1223128.07 | 0.00 | 0.234020E+10 | 0.823923E+09 | 0.00 | 0.35 |
March | 0.159369E+10 | 0.00 | 0.00 | 2738501.66 | 0.00 | 0.127407E+10 | 0.151292E+10 | 0.00 | 0.44 |
April | 0.148701E+10 | 0.134897E+09 | 0.00 | 3562438.21 | 5967345.78 | 0.335232E+09 | 0.181933E+10 | 0.00 | 0.58 |
May | 0.697455E+09 | 0.109056E+09 | 0.00 | 5912195.93 | 10847905.19 | 2527615.03 | 0.243355E+10 | 0.00 | 0.87 |
June | 0.302189E+09 | 0.906928E+09 | 0.00 | 4909535.45 | 33340916.01 | 0.00 | 0.149904E+10 | 0.00 | 0.96 |
July | 0.134527E+09 | 0.149110E+10 | 0.00 | 3668740.14 | 73620511.36 | 0.00 | 0.656367E+09 | 0.00 | 1.01 |
August | 0.198571E+09 | 0.151579E+10 | 0.00 | 5509413.98 | 28995091.97 | 0.00 | 0.106604E+10 | 0.00 | 1.11 |
September | 0.696614E+09 | 0.262329E+09 | 0.00 | 7107877.46 | 6520018.91 | 10103137.22 | 0.227240E+10 | 0.00 | 0.98 |
October | 0.140980E+10 | 411429.15 | 0.00 | 5951460.84 | 0.00 | 75919519.53 | 0.276355E+10 | 0.00 | 0.65 |
November | 0.143394E+10 | 0.00 | 0.00 | 1537996.11 | 0.00 | 0.135658E+10 | 0.884372E+09 | 0.00 | 0.39 |
December | 0.733918E+09 | 0.00 | 0.00 | 1376179.61 | 0.00 | 0.331937E+10 | 0.103136E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.111732E+11 | 0.442051E+10 | 0.00 | 44390056.79 | 0.159292E+09 | 0.125622E+11 | 0.174661E+11 | 0.00 | 0.67 |
Minimum of Months | 0.134527E+09 | 0.00 | 0.00 | 892589.33 | 0.00 | 0.00 | 0.656367E+09 | 0.00 | 0.34 |
Maximum of Months | 0.159369E+10 | 0.151579E+10 | 0.00 | 7107877.46 | 73620511.36 | 0.384819E+10 | 0.276355E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306599E+09 | 0.00 | 0.00 | 72.13 | 0.00 | 0.374203E+10 | 1669291.03 | 0.00 | 0.36 |
February | 0.505537E+09 | 0.00 | 0.00 | 80054.85 | 0.00 | 0.236317E+10 | 68944928.48 | 0.00 | 0.33 |
March | 0.100351E+10 | 0.00 | 0.00 | 519545.63 | 0.00 | 0.106767E+10 | 0.322472E+09 | 0.00 | 0.36 |
April | 0.967345E+09 | 55449540.24 | 0.00 | 2082134.01 | 4626372.73 | 0.210240E+09 | 0.111137E+10 | 0.00 | 0.56 |
May | 0.423482E+09 | 73830680.56 | 0.00 | 4532568.84 | 9357791.80 | 1683161.93 | 0.165984E+10 | 0.00 | 0.93 |
June | 0.179934E+09 | 0.678741E+09 | 0.00 | 4031095.95 | 13646287.85 | 0.00 | 0.118373E+10 | 0.00 | 1.20 |
July | 73982937.44 | 0.122152E+10 | 0.00 | 3343239.55 | 22983503.59 | 0.00 | 0.503439E+09 | 0.00 | 1.21 |
August | 0.123104E+09 | 0.104674E+10 | 0.00 | 3952817.59 | 14143148.53 | 0.00 | 0.720770E+09 | 0.00 | 1.21 |
September | 0.534083E+09 | 0.147032E+09 | 0.00 | 3221764.28 | 3766539.62 | 12176886.78 | 0.977699E+09 | 0.00 | 0.82 |
October | 0.114590E+10 | 0.00 | 0.00 | 1258312.12 | 192339.11 | 78239022.08 | 0.672445E+09 | 0.00 | 0.43 |
November | 0.773848E+09 | 0.00 | 0.00 | 141362.87 | 0.00 | 0.126582E+10 | 0.101864E+09 | 0.00 | 0.33 |
December | 0.302195E+09 | 0.00 | 0.00 | 165.71 | 0.00 | 0.271753E+10 | 2065877.49 | 0.00 | 0.32 |
Annual Sum or Average | 0.633953E+10 | 0.322331E+10 | 0.00 | 23163133.53 | 68715983.22 | 0.114585E+11 | 0.732631E+10 | 0.00 | 0.67 |
Minimum of Months | 73982937.44 | 0.00 | 0.00 | 72.13 | 0.00 | 0.00 | 1669291.03 | 0.00 | 0.32 |
Maximum of Months | 0.114590E+10 | 0.122152E+10 | 0.00 | 4532568.84 | 22983503.59 | 0.374203E+10 | 0.165984E+10 | 0.00 | 1.21 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:20
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.194602E+12 | 0.441970E+11 | 0.00 | 0.152175E+12 | 0.180103E+11 |
February | 0.216474E+12 | 0.333115E+11 | 0.00 | 0.135803E+12 | 0.121102E+11 |
March | 0.317711E+12 | 0.295696E+11 | 0.00 | 0.154456E+12 | 0.809330E+10 |
April | 0.373357E+12 | 0.182041E+11 | 0.00 | 0.164272E+12 | 0.221758E+11 |
May | 0.426384E+12 | 0.103907E+11 | 0.00 | 0.192749E+12 | 0.486980E+11 |
June | 0.441378E+12 | 0.252709E+10 | 0.00 | 0.998496E+11 | 0.147005E+12 |
July | 0.444264E+12 | 0.323750E+09 | 0.00 | 0.406910E+11 | 0.201968E+12 |
August | 0.388704E+12 | 0.234623E+10 | 0.00 | 0.782331E+11 | 0.190619E+12 |
September | 0.277175E+12 | 0.900644E+10 | 0.00 | 0.161135E+12 | 0.784854E+11 |
October | 0.215888E+12 | 0.185870E+11 | 0.00 | 0.182776E+12 | 0.654314E+10 |
November | 0.134004E+12 | 0.281972E+11 | 0.00 | 0.145643E+12 | 0.692509E+10 |
December | 0.108448E+12 | 0.372019E+11 | 0.00 | 0.141616E+12 | 0.133214E+11 |
Annual Sum or Average | 0.353839E+13 | 0.233862E+12 | 0.00 | 0.164940E+13 | 0.753955E+12 |
Minimum of Months | 0.108448E+12 | 0.323750E+09 | 0.00 | 0.406910E+11 | 0.654314E+10 |
Maximum of Months | 0.444264E+12 | 0.441970E+11 | 0.00 | 0.192749E+12 | 0.201968E+12 |