Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:32:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1317.18 | 264.38 | 264.38 |
Net Site Energy | 1199.03 | 240.66 | 240.66 |
Total Source Energy | 3680.61 | 738.75 | 738.75 |
Net Source Energy | 3306.44 | 663.65 | 663.65 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 90.52 | 103.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 64.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 132.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1081.51 | 235.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 90.52 | 103.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 64.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 167.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 34.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 62.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 64.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 132.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 90.52 | 103.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 64.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 167.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 34.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 647.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 64.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 132.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 44.11 | 47.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 217.08 | 47.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 40.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 44.11 | 47.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 132.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 217.08 | 47.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 123.933 | 11.46 |
Wind Power | 0.000 | 0.00 |
Power Conversion | -5.79 | -0.5 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 118.146 | 10.92 |
Electricity Coming From Utility | 964.310 | 89.16 |
Surplus Electricity Going To Utility | 0.945 | 0.09 |
Net Electricity From Utility | 963.366 | 89.08 |
Total On-Site and Utility Electric Sources | 1081.511 | 100.00 |
Total Electricity End Uses | 1081.511 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 227.67 |
Time Setpoint Not Met During Occupied Cooling | 59.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1675.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionElectricityGeneratedPropaneMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:32 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 16.8375 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 5.8040 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 5.8040 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 5.8040 | 18.58 | 9.8007 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8040 | 18.58 | 16.8375 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.8040 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8040 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8040 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8040 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8040 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Conditioned Total | 4982.19 | 5.8040 | 9.29 | 9.8007 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.8040 | 18.58 | 9.8007 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 07-JAN-08:20 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 172473.38 | 51811.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 18346.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6870.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8756.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 207655.42 | 60568.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 172473.38 | 51811.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 5890.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2981.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 36.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6870.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8756.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 286.67 | 112.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 204.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 531.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 109.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2051.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 204.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 143.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3425.15 | 255.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 57.54 | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 687.48 | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 57.54 | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 106.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 411.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 41.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 687.48 | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.37 | 0.316495 | 0.269000 | 0.636988 | 0.843986 | 0.500000 | 0.001204 |
CORE_MID VAV BOX COMPONENT | 1.97 | 0.381103 | 0.324000 | 0.637160 | 1.00 | 0.500000 | 0.001000 |
CORE_TOP VAV BOX COMPONENT | 2.01 | 0.372887 | 0.317000 | 0.637129 | 0.994365 | 0.500000 | 0.001022 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.577368 | 0.273641 | 0.233000 | 0.134527 | 0.729710 | 0.500000 | 0.001392 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.751257 | 0.133139 | 0.113000 | 0.084892 | 0.355038 | 0.500000 | 0.002862 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.12 | 0.141237 | 0.120000 | 0.134236 | 0.376631 | 0.500000 | 0.002698 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.821402 | 0.121762 | 0.103000 | 0.084604 | 0.324698 | 0.500000 | 0.003129 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.456677 | 0.345960 | 0.294000 | 0.134263 | 0.922559 | 0.500000 | 0.001101 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.618174 | 0.161802 | 0.138000 | 0.085308 | 0.431472 | 0.500000 | 0.002355 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.915111 | 0.172648 | 0.147000 | 0.134521 | 0.460394 | 0.500000 | 0.002207 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.684764 | 0.146058 | 0.124000 | 0.084911 | 0.389488 | 0.500000 | 0.002609 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.508520 | 0.310689 | 0.264000 | 0.134249 | 0.828504 | 0.500000 | 0.001226 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.756318 | 0.352662 | 0.500000 | 0.002881 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.05 | 0.151102 | 0.128000 | 0.133836 | 0.402939 | 0.500000 | 0.002521 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.771503 | 0.129637 | 0.110000 | 0.084865 | 0.345698 | 0.500000 | 0.002939 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20971.27 |
CORE_MID VAV BOX REHEAT COIL | 20976.94 |
CORE_TOP VAV BOX REHEAT COIL | 29859.29 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 14024.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9175.24 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13951.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9133.27 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10285.72 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6818.64 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10214.27 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6771.87 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10997.23 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7249.96 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10919.91 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7207.54 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.52 | 1.08 | 5.04 | 1.46 | 4.37 | 4.37 | 0.300000 | 0.333828 | 4.37 |
PACU_VAV_MID | 2.52 | 1.07 | 5.05 | 1.61 | 4.16 | 4.16 | 0.300000 | 0.387019 | 4.16 |
PACU_VAV_TOP | 2.64 | 1.08 | 5.28 | 2.31 | 4.70 | 4.70 | 0.300000 | 0.491757 | 4.70 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.37 |
PACU_VAV_MID_OA_CONTROLLER | 4.16 |
PACU_VAV_TOP_OA_CONTROLLER | 4.70 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.37 | 76620.99 | 0.800427 | 1.46 | 25537.78 | 0.800427 |
PACU_VAV_MID COOLING COIL | 4.16 | 73313.28 | 0.800534 | 1.39 | 24435.32 | 0.800534 |
PACU_VAV_TOP COOLING COIL | 4.70 | 81781.10 | 0.800999 | 1.57 | 27257.64 | 0.800999 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 16418.46 |
PACU_VAV_MID HEATING COIL | 16525.08 |
PACU_VAV_TOP HEATING COIL | 16802.63 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.37 |
PACU_VAV_MID FAN | 4.16 |
PACU_VAV_TOP FAN | 4.70 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 16.837 | 0.000 | 0.000 | 0.000 | 0.000 | 22.641 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 13.873 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.804 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.874 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5708.430 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5708.430 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 761.844 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.844 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1203.387 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1203.387 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 761.794 | 5.804 | 107.831 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 761.794 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 8517.820 | 8.660 | 160.900 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1022.138 | 5877.296 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 105.310 | 0.107 | 1.989 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 72.664 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5960 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5902 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7087 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.444 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.460 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.177 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.34210526E-12 | 0.10412655E-14 | -0.10417952E-12 | 0.10409145E-15 |
43 | 6 | 0.30802088E-07 | 0.17108976E-09 | 0.70383009E-08 | -0.14667926E-12 |
44 | 5 | -0.20086572E-03 | 0.14450046E-05 | -0.10316412E-03 | 0.69507809E-08 |
45 | 4 | 0.30464713 | 0.69501731E-03 | 0.10418329 | -0.35343869E-04 |
46 | 3 | -7.5136835 | 0.21306369E-01 | -2.4123261 | 0.30221796E-01 |
47 | 2 | 41.686696 | 0.75037385E-01 | 15.565716 | -0.34242481 |
48 | 1 | -81.170502 | 0.33581009E-01 | -29.411065 | 1.0919325 |
49 | 0 | 46.824335 | 0.67004661E-03 | 16.284887 | |
50 | 7 | -0.34244365E-12 | 0.92212740E-15 | -0.10449257E-12 | 0.10448628E-15 |
51 | 6 | 0.30869821E-07 | 0.16952917E-09 | 0.70532514E-08 | -0.14704533E-12 |
52 | 5 | -0.20120586E-03 | 0.14312561E-05 | -0.10333395E-03 | 0.69653235E-08 |
53 | 4 | 0.30503960 | 0.68816038E-03 | 0.10432471 | -0.35399819E-04 |
54 | 3 | -7.5214432 | 0.21089521E-01 | -2.4146296 | 0.30259860E-01 |
55 | 2 | 41.712273 | 0.74252889E-01 | 15.575132 | -0.34270975 |
56 | 1 | -81.190086 | 0.33221761E-01 | -29.419498 | 1.0923499 |
57 | 0 | 46.824335 | 0.66271842E-03 | 16.284691 | |
58 | 7 | -0.32374075E-12 | 0.12045207E-14 | -0.10360241E-12 | 0.16221974E-15 |
59 | 6 | 0.29475593E-07 | 0.20098913E-09 | 0.67455071E-08 | -0.13952197E-12 |
60 | 5 | -0.19418177E-03 | 0.17111334E-05 | -0.99823337E-04 | 0.66657971E-08 |
61 | 4 | 0.29690150 | 0.82890285E-03 | 0.10139402 | -0.34243177E-04 |
62 | 3 | -7.3604632 | 0.25571829E-01 | -2.3668478 | 0.29470418E-01 |
63 | 2 | 41.181572 | 0.90565943E-01 | 15.379610 | -0.33679792 |
64 | 1 | -80.783638 | 0.40729985E-01 | -29.244332 | 1.0836880 |
65 | 0 | 46.824337 | 0.81662197E-03 | 16.288791 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.980 | 0.1802 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2573E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2641E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4284E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6471E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6944E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1337E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1567E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1623 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9225E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1866 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1161 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1060 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7045E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5658E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7130E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2572E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2644E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4288E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6472E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6962E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1335E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1565E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2304E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2846E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8309E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9927E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8970E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5043E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3611E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5268E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5254E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5531E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1996E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2197E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8087E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8154E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8245E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8324E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6869E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7449E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9509E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3474E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3809E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1335E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1565E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6058E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6401E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5557E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0181E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2282E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3531E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5658E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7130E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6871E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7454E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9508E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3472E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3794E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1337E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1567E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.9163E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1214E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4250E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7806E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6747E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3962E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3611E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5268E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3487E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4506E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9713E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0906E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6797E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7106E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8247E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8326E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1612 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1154 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1821 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1336 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1142 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9166E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2056E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4300E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.9837E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1443E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6075E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8659E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7319E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4067E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2614E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4669E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2170E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4103E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0968E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6778E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7687E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9509E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2056E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4300E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6810E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9904E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2167E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6662E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5169E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3039E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2615E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4670E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1613 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1154 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1821 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1336 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1142 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9159E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2051E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4297E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.9837E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1440E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6075E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8657E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7315E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4064E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2609E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4667E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2172E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4102E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0969E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6777E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7684E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9507E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2051E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4297E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6810E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9902E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2167E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6659E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5165E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3036E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2610E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4667E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 32415.20694 | 32415.20694 | 2.36798 | 2.36798 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6818.34416 | 6818.34416 | 0.29009 | 0.42469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26944.46507 | 26944.46507 | 1.96654 | 1.96654 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11818.86616 | 11818.86616 | 0.50607 | 0.50607 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27268.22880 | 27268.22880 | 2.00987 | 2.00987 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21060.83335 | 21060.83335 | 0.90696 | 0.90696 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 7833.34167 | 7833.34167 | 0.57737 | 0.57737 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9854.78545 | 9854.78545 | 0.42598 | 0.42598 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10192.62774 | 10192.62774 | 0.75126 | 0.75126 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6446.72745 | 6446.72745 | 0.27869 | 0.27869 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15176.94225 | 15176.94225 | 1.11863 | 1.11863 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9803.64221 | 9803.64221 | 0.42376 | 0.42376 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11144.32623 | 11144.32623 | 0.82140 | 0.82140 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6417.33171 | 6417.33171 | 0.27742 | 0.27742 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6195.86521 | 6195.86521 | 0.45668 | 0.45668 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7235.24840 | 7235.24840 | 0.31242 | 0.31242 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8447.76964 | 8447.76964 | 0.61817 | 0.61817 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4795.54877 | 4795.54877 | 0.20711 | 0.20711 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12415.66683 | 12415.66683 | 0.91511 | 0.91511 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7185.15551 | 7185.15551 | 0.31025 | 0.31025 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9290.48050 | 9290.48050 | 0.68476 | 0.68476 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4762.79197 | 4762.79197 | 0.20569 | 0.20569 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 6899.25809 | 6899.25809 | 0.50852 | 0.50852 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7734.31065 | 7734.31065 | 0.33403 | 0.33403 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10261.29781 | 10261.29781 | 0.75632 | 0.75632 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5098.05221 | 5098.05221 | 0.22021 | 0.22021 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14186.03722 | 14186.03722 | 1.04560 | 1.04560 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7680.16543 | 7680.16543 | 0.33168 | 0.33168 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10467.31958 | 10467.31958 | 0.77150 | 0.77150 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5068.34082 | 5068.34082 | 0.21892 | 0.21892 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 64585.07 | 4.37400 | 4.37400 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 19165.24 | 1.46017 | 1.46017 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 61758.36 | 4.16238 | 4.16238 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 19160.20 | 1.61092 | 1.61092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 68955.20 | 4.70314 | 4.70314 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 19283.47 | 2.31280 | 2.31280 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.36798 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31649 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63699 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84399 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20381E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20971.27305 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96654 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38110 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63716 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.99731E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20976.94446 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00987 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37289 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63713 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99437 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02176E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29859.29172 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57737 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27364 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23300 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13453 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72971 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39233E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14024.31821 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75126 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13314 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48920E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35504 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86167E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9175.24044 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11863 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14124 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13424 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37663 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69760E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13951.29253 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82140 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12176 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46044E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32470 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12907E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9133.26960 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.45668 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34596 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13426 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92256 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10128E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10285.71721 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61817 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16180 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53081E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43147 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35473E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6818.64237 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91511 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17265 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13452 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46039 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20681E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10214.27257 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68476 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14606 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49107E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38949 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60855E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6771.87119 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50852 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31069 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26400 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13425 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82850 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22631E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10997.22957 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75632 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35266 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88094E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7249.96153 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04560 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15110 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12800 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13384 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40294 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52148E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10919.91480 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77150 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12964 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48654E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34570 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93898E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7207.53619 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.52136 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07599 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.04271 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46017 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.37400 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.37400 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.33383 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.52424 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07482 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.04848 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.61092 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.16238 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.16238 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.38702 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.63926 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07539 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.27853 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.31280 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.70314 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.70314 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.49176 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.37400 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.16238 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.70314 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.37400 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.37400 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 76620.99033 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80043 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.45786 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25537.77608 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80043 |
152 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 16418.45924 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.37400 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.16238 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.16238 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 73313.27737 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80053 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.38732 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 24435.31535 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80053 |
161 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 16525.07905 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.16238 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.70314 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.70314 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 81781.09933 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80100 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56756 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27257.64041 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80100 |
170 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 16802.63479 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.70314 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 75499.47 | 257614.89 | 11.39 | 2.95 | 3.26 | 3.43 | 3.62 | 10.05 | 11.12 | 11.70 | 12.36 | 4.9869 | 3.9546 | 2.6532 | 1.0833 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 72257.80 | 246553.86 | 11.41 | 2.95 | 3.26 | 3.43 | 3.63 | 10.06 | 11.14 | 11.72 | 12.38 | 4.7456 | 3.7644 | 2.5262 | 1.0288 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 80557.32 | 274872.98 | 11.37 | 2.94 | 3.25 | 3.42 | 3.62 | 10.04 | 11.10 | 11.68 | 12.34 | 5.3621 | 4.2507 | 2.8520 | 1.1665 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.709 | 0.641 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.596 | 0.547 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.590 | 0.542 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.9553933620E-002 | 3.2264788310E-002 | Pass | Pass | 0.3456889320 | 0.4895794943 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.6393787480E-002 | 5.2841014143E-002 | Pass | Pass | 0.4224342297 | 0.4746994646 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.2164587442E-002 | 3.0761252148E-002 | Pass | Pass | 0.3526923106 | 0.4477205813 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.1845498711E-002 | 3.2006214295E-002 | Pass | Pass | 0.3150054289 | 0.4193852201 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.8745615715E-002 | 1.3591192281E-002 | Pass | Pass | 1.2100759950 | 3.4688390294 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.8240817581E-002 | 2.0386218175E-002 | Pass | Pass | 17.4778246713 | 100.7536542898 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2467457176 | 0.2275281735 | Pass | Pass | 21.9691686688 | 51.7458347633 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2544151775 | 0.2363442491 | Pass | Pass | 22.9501291539 | 54.0980027214 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2390478195 | 0.2227001476 | Pass | Pass | 22.0104368613 | 51.8950538637 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2577518947 | 0.2387868183 | Pass | Pass | 22.9626394238 | 54.1118321796 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1356170825 | 0.1505901885 | Pass | Pass | 2.8542750903 | 15.7336119229 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1465070970 | 0.1640556498 | Pass | Pass | 3.0449074381 | 19.2141616731 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1299583062 | 0.1429719972 | Pass | Pass | 12.6879519820 | 124.1463569054 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1482417586 | 0.1663363144 | Pass | Pass | 1.7380456511 | 4.9566923851 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1548738012 | 0.1661007452 | Pass | Pass | 8.9708848455 | 42.0597005407 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1634760526 | 0.1763957053 | Pass | Pass | 81.4790918802 | 901.2230537745 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1501977778 | 0.1629901005 | Pass | Pass | 18.1642352256 | 143.3864248911 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1656491750 | 0.1786579827 | Pass | Pass | 6.5443342876 | 21.0273176786 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2992.15 | 128.31 | 0.00 | 2162.13 | 355.02 | 5637.62 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.641 | 0.709 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.547 | 0.596 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.542 | 0.590 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8040 | 983.54 | 5708.43 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 37.14 | 0.0000 | Y | 39.80 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 22.12 | 0.0000 | Y | 5.00 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.89 | 0.0000 | Y | 3.13 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.68 | 0.0000 | Y | 4.90 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.86 | 0.0000 | Y | 3.13 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 22.05 | 0.0000 | Y | 4.98 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.85 | 0.0000 | Y | 3.12 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.64 | 0.0000 | Y | 4.89 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.81 | 0.0000 | Y | 3.12 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 22.12 | 0.0000 | Y | 5.00 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8040 | 131.26 | 761.84 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.89 | 0.0000 | Y | 3.13 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8040 | 207.34 | 1203.39 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.68 | 0.0000 | Y | 4.90 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8040 | 131.25 | 761.79 | LightsWired | LTG_SCH_OFFICE | 38.28 | 168.00 | 21.86 | 0.0000 | Y | 3.13 |
Interior Lighting Total | 5.8040 | 4982.19 | 28916.52 | 167.80 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.84 | 292.17 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.84 | 106.28 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1203.39 | 461.50 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1203.39 | 167.87 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 761.79 | 292.15 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 761.79 | 106.27 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 542.49 | AstronomicalClock | - | 42.59 | 42.59 | 4.34 | |
EXTERIOR_LIGHTS_B | 280.18 | AstronomicalClock | - | 83.55 | 63.07 | 3.32 | |
EXTERIOR_LIGHTS_C | 3002.07 | AstronomicalClock | - | 83.55 | 47.80 | 26.94 | |
Exterior Lighting Total | 3824.74 | 34.59 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 76620.99 | 61329.49 | 15291.50 | 0.80 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 73313.28 | 58689.78 | 14623.50 | 0.80 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 81781.10 | 65506.61 | 16274.49 | 0.80 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 75499.5 | 2.95 | 10.05 | N/A | N/A | 11.39 | |
PACU_VAV_MID COOLING COIL | 72257.8 | 2.95 | 10.06 | N/A | N/A | 11.41 | |
PACU_VAV_TOP COOLING COIL | 80557.3 | 2.94 | 10.04 | N/A | N/A | 11.37 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20971.27 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 20976.94 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 29859.29 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14024.32 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9175.24 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13951.29 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9133.27 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10285.72 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6818.64 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10214.27 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6771.87 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10997.23 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7249.96 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10919.91 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7207.54 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 16418.46 | 0.84 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 16525.08 | 0.84 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 16802.63 | 0.84 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.37 | 9574.74 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.16 | 9111.49 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.70 | 10295.23 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.98 | 0.18 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 75499.47 | 2.95 | 10.05 | 11.39 | 4.9869 | 3.26 | 11.12 | 3.9546 | 3.43 | 11.70 | 2.6532 | 3.62 | 12.36 | 1.0833 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 72257.80 | 2.95 | 10.06 | 11.41 | 4.7456 | 3.26 | 11.14 | 3.7644 | 3.43 | 11.72 | 2.5262 | 3.63 | 12.38 | 1.0288 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 80557.32 | 2.94 | 10.04 | 11.37 | 5.3621 | 3.25 | 11.10 | 4.2507 | 3.42 | 11.68 | 2.8520 | 3.62 | 12.34 | 1.1665 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 32415.21 | 32415.21 | 32.96 | 2.368 | 2.368 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_MID | 26944.47 | 26944.47 | 27.40 | 1.967 | 1.967 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_TOP | 27268.23 | 27268.23 | 27.72 | 2.010 | 2.010 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00894 | 29.30 | 0.00882 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7833.34 | 7833.34 | 37.78 | 0.577 | 0.577 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00882 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10192.63 | 10192.63 | 77.65 | 0.751 | 0.751 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00866 | 23.35 | 0.00881 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15176.94 | 15176.94 | 73.20 | 1.119 | 1.119 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00867 | 29.14 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11144.33 | 11144.33 | 84.91 | 0.821 | 0.821 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00865 | 27.94 | 0.00882 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6195.87 | 6195.87 | 29.88 | 0.457 | 0.457 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8447.77 | 8447.77 | 64.36 | 0.618 | 0.618 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00869 | 21.70 | 0.00881 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12415.67 | 12415.67 | 59.88 | 0.915 | 0.915 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00871 | 29.31 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9290.48 | 9290.48 | 70.78 | 0.685 | 0.685 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00867 | 26.90 | 0.00882 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6899.26 | 6899.26 | 33.28 | 0.509 | 0.509 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00886 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10261.30 | 10261.30 | 78.17 | 0.756 | 0.756 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 23.02 | 0.00881 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14186.04 | 14186.04 | 68.42 | 1.046 | 1.046 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00868 | 29.05 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10467.32 | 10467.32 | 79.75 | 0.772 | 0.772 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00866 | 27.94 | 0.00882 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6818.34 | 6818.34 | 6.93 | 0.290 | 0.425 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_MID | 11818.87 | 11818.87 | 12.02 | 0.506 | 0.506 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_TOP | 21060.83 | 21060.83 | 21.41 | 0.907 | 0.907 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9854.79 | 9854.79 | 47.53 | 0.426 | 0.426 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6446.73 | 6446.73 | 49.11 | 0.279 | 0.279 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9803.64 | 9803.64 | 47.28 | 0.424 | 0.424 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6417.33 | 6417.33 | 48.89 | 0.277 | 0.277 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7235.25 | 7235.25 | 34.90 | 0.312 | 0.312 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00745 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4795.55 | 4795.55 | 36.53 | 0.207 | 0.207 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7185.16 | 7185.16 | 34.65 | 0.310 | 0.310 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4762.79 | 4762.79 | 36.29 | 0.206 | 0.206 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7734.31 | 7734.31 | 37.30 | 0.334 | 0.334 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5098.05 | 5098.05 | 38.84 | 0.220 | 0.220 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00740 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7680.17 | 7680.17 | 37.04 | 0.332 | 0.332 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5068.34 | 5068.34 | 38.61 | 0.219 | 0.219 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -4.20 | 0.00269 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.37 | 4.37 | 1.46 | 1.46 | 4.3740 | 1.4602 | 4.3740 | 0.3338 | 0.3000 |
PACU_VAV_MID | 4.16 | 4.16 | 1.61 | 1.61 | 4.1624 | 1.6109 | 4.1624 | 0.3870 | 0.3000 |
PACU_VAV_TOP | 4.70 | 4.70 | 2.31 | 2.31 | 4.7031 | 2.3128 | 4.7031 | 0.4918 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20971.273 | 20971.273 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20971.27 | 13981.92 | 0.424691 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 6818.34 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 20976.944 | 20976.944 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20976.94 | 16660.98 | 0.506066 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 11818.87 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 29859.292 | 29859.292 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29859.29 | 29859.29 | 0.906955 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 21060.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 14024.318 | 14024.318 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14024.32 | 14024.32 | 0.425979 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00753254 | 48.0422 | 9854.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9175.240 | 9175.240 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9175.24 | 9175.24 | 0.278692 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00753078 | 48.0312 | 6446.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13951.293 | 13951.293 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13951.29 | 13951.29 | 0.423761 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00752925 | 48.0215 | 9803.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9133.270 | 9133.270 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9133.27 | 9133.27 | 0.277417 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00752801 | 48.0138 | 6417.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10285.717 | 10285.717 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10285.72 | 10285.72 | 0.312422 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00744897 | 47.5156 | 7235.25 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6818.642 | 6818.642 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6818.64 | 6818.64 | 0.207112 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00747307 | 47.6674 | 4795.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10214.273 | 10214.273 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10214.27 | 10214.27 | 0.310251 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00744179 | 47.4703 | 7185.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6771.871 | 6771.871 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6771.87 | 6771.87 | 0.205691 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00746599 | 47.6228 | 4762.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10997.230 | 10997.230 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10997.23 | 10997.23 | 0.334033 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00737626 | 47.0580 | 7734.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7249.962 | 7249.962 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7249.96 | 7249.96 | 0.220213 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00739738 | 47.1911 | 5098.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10919.915 | 10919.915 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10919.91 | 10919.91 | 0.331685 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00736783 | 47.0049 | 7680.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7207.536 | 7207.536 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7207.54 | 7207.54 | 0.218924 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00739044 | 47.1474 | 5068.34 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 76620.990 | 61329.490 | 4.374003 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 77453.34 | 73001.57 | 4.374003 | 25.18 | 16.94 | 0.00883708 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 21.8587 | 24.00 | 0.00884144 | 46.8933 | 59343.21 | 0.00 | 79006.53 | 61716.80 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 16418.459 | 16418.459 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16418.46 | 16418.46 | 1.312201 | 2.31 | 1.48 | 0.00392767 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 72.8623 | 19.62 | 0.00712738 | 49.5194 | 13283.33 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 73313.277 | 58689.781 | 4.162379 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 74150.42 | 69745.07 | 4.162379 | 25.24 | 16.97 | 0.00885064 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 22.9700 | 24.00 | 0.00885933 | 46.9869 | 56472.12 | 0.00 | 75595.83 | 59056.92 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 16525.079 | 16525.079 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16525.08 | 16525.08 | 1.248714 | 1.70 | 1.00 | 0.00383335 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 76.5668 | 18.84 | 0.00743581 | 54.2114 | 16635.44 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 81781.099 | 65506.613 | 4.703144 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 82609.03 | 78068.32 | 4.703144 | 25.10 | 16.90 | 0.00881961 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.3290 | 24.00 | 0.00881912 | 46.7765 | 63782.01 | 0.00 | 84327.29 | 65920.62 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 16802.635 | 16802.635 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16802.63 | 16802.63 | 1.410943 | 2.82 | 2.10 | 0.00416735 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 67.7632 | 17.60 | 0.00693674 | 54.7317 | 18425.01 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20971.273 | 20971.273 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20971.27 | 13981.92 | 1.0000 | 0.50410441 | 0.424691 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20971.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.59 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 6818.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 20976.944 | 20976.944 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20976.94 | 16660.98 | 1.0000 | 0.60069543 | 0.506066 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20976.94 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 11818.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 29859.292 | 29859.292 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29859.29 | 29859.29 | 1.0000 | 1.07654760 | 0.906955 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29859.29 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 21060.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14024.318 | 14024.318 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14024.32 | 14024.32 | 1.0000 | 0.50563310 | 0.425979 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14024.32 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753254 | 21.00 | 0.00753254 | 48.0422 | 9854.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9175.240 | 9175.240 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9175.24 | 9175.24 | 1.0000 | 0.33080433 | 0.278692 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9175.24 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753078 | 21.00 | 0.00753078 | 48.0312 | 6446.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13951.293 | 13951.293 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13951.29 | 13951.29 | 1.0000 | 0.50300023 | 0.423761 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13951.29 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00752925 | 21.00 | 0.00752925 | 48.0215 | 9803.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9133.270 | 9133.270 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9133.27 | 9133.27 | 1.0000 | 0.32929112 | 0.277417 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9133.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00752801 | 21.00 | 0.00752801 | 48.0138 | 6417.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10285.717 | 10285.717 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10285.72 | 10285.72 | 1.0000 | 0.37084149 | 0.312422 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10285.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00744897 | 21.00 | 0.00744897 | 47.5156 | 7235.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6818.642 | 6818.642 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6818.64 | 6818.64 | 1.0000 | 0.24583949 | 0.207112 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6818.64 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00747307 | 21.00 | 0.00747307 | 47.6674 | 4795.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10214.273 | 10214.273 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10214.27 | 10214.27 | 1.0000 | 0.36826562 | 0.310251 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10214.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00744179 | 21.00 | 0.00744179 | 47.4703 | 7185.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6771.871 | 6771.871 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6771.87 | 6771.87 | 1.0000 | 0.24415320 | 0.205691 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6771.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00746599 | 21.00 | 0.00746599 | 47.6228 | 4762.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10997.230 | 10997.230 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10997.23 | 10997.23 | 1.0000 | 0.39649437 | 0.334033 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10997.23 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00737626 | 21.00 | 0.00737626 | 47.0580 | 7734.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7249.962 | 7249.962 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7249.96 | 7249.96 | 1.0000 | 0.26139028 | 0.220213 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7249.96 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00739738 | 21.00 | 0.00739738 | 47.1911 | 5098.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10919.915 | 10919.915 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10919.91 | 10919.91 | 1.0000 | 0.39370686 | 0.331685 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10919.91 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00736783 | 21.00 | 0.00736783 | 47.0049 | 7680.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7207.536 | 7207.536 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7207.54 | 7207.54 | 1.0000 | 0.25986068 | 0.218924 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7207.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00739044 | 21.00 | 0.00739044 | 47.1474 | 5068.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 76620.990 | 61329.490 | 4.374003 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2677 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.374003 | 5.19190112 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 77453.34 | 73001.57 | 1.0109 | 5.19190112 | 4.374003 | 25.18 | 16.94 | 0.00883708 | 47815.9 | 10.99 | 10.99 | 0.00850000 | 32479.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9574.740 | 67878.60 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 21.8587 | 24.00 | 0.00884144 | 24.00 | 0.00884144 | 46.8933 | 59343.21 | 0.00 | 79006.53 | 61716.80 | 4.98686027 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.57 | 14.08 | 0.00982531 | 39479.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16418.459 | 16418.459 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.374003 | 5.19190112 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16418.46 | 16418.46 | 1.0000 | 1.55757034 | 1.312201 | 2.31 | 1.48 | 0.00392767 | 12160.8 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16418.46 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 72.8623 | 19.79 | 0.00724985 | 19.62 | 0.00712738 | 49.5194 | 13283.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 73313.277 | 58689.781 | 4.162379 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2929 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.162379 | 4.94070581 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 74150.42 | 69745.07 | 1.0114 | 4.94070581 | 4.162379 | 25.24 | 16.97 | 0.00885064 | 47911.8 | 10.99 | 10.99 | 0.00850000 | 32479.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9111.494 | 65038.93 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 22.9700 | 24.00 | 0.00885933 | 24.00 | 0.00885933 | 46.9869 | 56472.12 | 0.00 | 75595.83 | 59056.92 | 4.74558528 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.50 | 14.05 | 0.00981823 | 39392.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16525.079 | 16525.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.162379 | 4.94070581 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16525.08 | 16525.08 | 1.0000 | 1.48221174 | 1.248714 | 1.70 | 1.00 | 0.00383335 | 11312.3 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16525.08 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 76.5668 | 21.00 | 0.00756813 | 18.84 | 0.00743581 | 54.2114 | 16635.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 81781.099 | 65506.613 | 4.703144 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2352 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.703144 | 5.58258910 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 82609.03 | 78068.32 | 1.0101 | 5.58258910 | 4.703144 | 25.10 | 16.90 | 0.00881961 | 47687.5 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10295.235 | 72313.80 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 20.3290 | 24.00 | 0.00881912 | 24.00 | 0.00881912 | 46.7765 | 63782.01 | 0.00 | 84327.29 | 65920.62 | 5.36211903 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 14.13 | 0.00983877 | 39595.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16802.635 | 16802.635 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.703144 | 5.58258910 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16802.63 | 16802.63 | 1.0000 | 1.67477673 | 1.410943 | 2.82 | 2.10 | 0.00416735 | 13273.5 | 12.80 | 11.47 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16802.63 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 67.7632 | 17.56 | 0.00727215 | 17.60 | 0.00693674 | 54.7317 | 18425.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.37 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.16 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.70 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1419.67 | 2766.50 | 38.00 |
CORE_MID | 1162.00 | 3487.67 | 217.67 |
CORE_TOP | 1474.83 | 3945.50 | 708.33 |
PERIMETER_TOP_ZN_3 | 2249.33 | 4324.83 | 1484.50 |
PERIMETER_TOP_ZN_2 | 2560.17 | 3890.50 | 1336.00 |
PERIMETER_TOP_ZN_1 | 2470.50 | 3759.17 | 1143.17 |
PERIMETER_TOP_ZN_4 | 2566.33 | 4045.67 | 1409.67 |
PERIMETER_BOT_ZN_3 | 1700.83 | 4468.33 | 1155.17 |
PERIMETER_BOT_ZN_2 | 2202.83 | 3776.83 | 984.67 |
PERIMETER_BOT_ZN_1 | 2077.00 | 3996.67 | 934.00 |
PERIMETER_BOT_ZN_4 | 2247.17 | 3781.50 | 1010.17 |
PERIMETER_MID_ZN_3 | 1853.67 | 4028.67 | 1021.50 |
PERIMETER_MID_ZN_2 | 1930.17 | 3194.33 | 881.83 |
PERIMETER_MID_ZN_1 | 2207.00 | 3418.33 | 757.50 |
PERIMETER_MID_ZN_4 | 2232.33 | 3734.33 | 962.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 3860.83 | 4774.67 | 1675.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.17 | 0.00 | 1.17 | 0.00 |
CORE_MID | 2.17 | 0.00 | 2.17 | 0.00 |
CORE_TOP | 2.00 | 0.00 | 1.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 12.17 | 0.00 | 9.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 4.83 | 10.50 | 1.67 | 10.50 |
PERIMETER_TOP_ZN_1 | 2.00 | 13.83 | 1.00 | 13.67 |
PERIMETER_TOP_ZN_4 | 5.17 | 20.00 | 2.33 | 11.83 |
PERIMETER_BOT_ZN_3 | 3.50 | 0.00 | 3.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 1.00 | 6.83 | 1.00 | 6.83 |
PERIMETER_BOT_ZN_1 | 220.50 | 6.67 | 220.50 | 6.67 |
PERIMETER_BOT_ZN_4 | 1.00 | 11.67 | 1.00 | 6.00 |
PERIMETER_MID_ZN_3 | 2.50 | 0.00 | 2.33 | 0.00 |
PERIMETER_MID_ZN_2 | 0.67 | 10.67 | 0.50 | 10.67 |
PERIMETER_MID_ZN_1 | 0.67 | 14.00 | 0.50 | 14.00 |
PERIMETER_MID_ZN_4 | 0.67 | 18.67 | 0.50 | 11.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 231.67 | 74.00 | 227.67 | 59.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 0.820 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.658 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.645 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.702 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.009 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 1.098 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.010 | 0.083 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.613 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.903 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.879 | 0.853 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.888 | 0.044 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.704 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.921 | 0.074 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 1.107 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 1.004 | 0.069 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.56 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12934708.84 | 0.00 | 12934708.84 | 0.00 | 12934708.84 | 13393058.27 | 4683.52 | 821.13 | 3255.35 | 41.42 |
CORE_MID | 10428290.63 | 0.00 | 10428290.63 | 0.00 | 10428290.63 | 13393058.27 | 4599.37 | 1244.63 | 2915.99 | 47.04 |
CORE_TOP | 10231652.04 | 0.00 | 10231652.04 | 0.00 | 10231652.04 | 13393058.27 | 4638.69 | 1297.12 | 2824.19 | 47.09 |
PERIMETER_TOP_ZN_3 | 2347952.17 | 0.00 | 2347952.17 | 539250.78 | 2887202.96 | 2823374.22 | 4431.68 | 1210.17 | 3118.15 | 47.09 |
PERIMETER_TOP_ZN_2 | 2129352.37 | 0.00 | 2129352.37 | 359498.36 | 2488850.73 | 1787429.43 | 4446.97 | 1367.46 | 2945.57 | 47.09 |
PERIMETER_TOP_ZN_1 | 3657272.93 | 0.00 | 3657272.93 | 539250.78 | 4196523.72 | 2823374.22 | 4352.22 | 1309.01 | 3098.77 | 47.09 |
PERIMETER_TOP_ZN_4 | 2144291.67 | 0.00 | 2144291.67 | 359498.36 | 2503790.04 | 1787312.18 | 4598.12 | 1403.15 | 2758.73 | 47.09 |
PERIMETER_BOT_ZN_3 | 2048819.50 | 0.00 | 2048819.50 | 286716.78 | 2335536.28 | 2823374.22 | 5126.03 | 891.81 | 2742.16 | 41.42 |
PERIMETER_BOT_ZN_2 | 1903469.66 | 0.00 | 1903469.66 | 191143.37 | 2094613.03 | 1787429.43 | 4876.78 | 711.66 | 3171.56 | 41.42 |
PERIMETER_BOT_ZN_1 | 2932611.13 | 0.00 | 2932611.13 | 2993637.78 | 5926248.91 | 2823374.22 | 4586.72 | 777.26 | 3396.02 | 41.42 |
PERIMETER_BOT_ZN_4 | 1876150.07 | 0.00 | 1876150.07 | 191143.37 | 2067293.44 | 1787312.18 | 4997.24 | 926.49 | 2836.27 | 41.42 |
PERIMETER_MID_ZN_3 | 2350180.43 | 0.00 | 2350180.43 | 448884.86 | 2799065.29 | 2823374.22 | 4513.94 | 1292.53 | 2953.53 | 47.04 |
PERIMETER_MID_ZN_2 | 1962544.29 | 0.00 | 1962544.29 | 299254.78 | 2261799.06 | 1601953.02 | 4380.18 | 1158.02 | 3221.80 | 956.04 |
PERIMETER_MID_ZN_1 | 3682667.34 | 0.00 | 3682667.34 | 448884.86 | 4131552.20 | 2823374.22 | 4379.39 | 1364.67 | 3015.94 | 47.04 |
PERIMETER_MID_ZN_4 | 2126171.79 | 0.00 | 2126171.79 | 299254.78 | 2425426.56 | 1787312.18 | 4501.32 | 1339.13 | 2919.55 | 47.04 |
Total Facility | 62756134.86 | 0.00 | 62756134.86 | 6956418.86 | 69712553.72 | 67658168.57 | 5486.94 | 1810.44 | 4132.23 | 980.87 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6014 | 0.0000 | 0.6014 | 0.0000 | 0.6014 | 0.4247 | 1894.60 | 821.13 | 3227.27 |
CORE_MID | 0.4837 | 0.0000 | 0.4837 | 0.0000 | 0.4837 | 0.4247 | 1816.56 | 1244.63 | 2881.81 |
CORE_TOP | 0.4741 | 0.0000 | 0.4741 | 0.0000 | 0.4741 | 0.4247 | 1859.77 | 1297.12 | 2786.11 |
PERIMETER_TOP_ZN_3 | 0.1089 | 0.0000 | 0.1089 | 0.0123 | 0.1211 | 0.0895 | 1652.77 | 1210.17 | 3080.06 |
PERIMETER_TOP_ZN_2 | 0.0990 | 0.0000 | 0.0990 | 0.0082 | 0.1071 | 0.0567 | 1668.05 | 1367.46 | 2907.49 |
PERIMETER_TOP_ZN_1 | 0.1701 | 0.0000 | 0.1701 | 0.0123 | 0.1823 | 0.0895 | 1573.30 | 1309.01 | 3060.69 |
PERIMETER_TOP_ZN_4 | 0.0990 | 0.0000 | 0.0990 | 0.0082 | 0.1072 | 0.0567 | 1819.20 | 1403.15 | 2720.64 |
PERIMETER_BOT_ZN_3 | 0.0951 | 0.0000 | 0.0951 | 0.0065 | 0.1016 | 0.0895 | 2337.11 | 891.81 | 2714.07 |
PERIMETER_BOT_ZN_2 | 0.0885 | 0.0000 | 0.0885 | 0.0043 | 0.0929 | 0.0567 | 2087.89 | 711.66 | 3143.46 |
PERIMETER_BOT_ZN_1 | 0.1364 | 0.0000 | 0.1364 | 0.1330 | 0.2694 | 0.0895 | 1797.80 | 777.26 | 3367.94 |
PERIMETER_BOT_ZN_4 | 0.0870 | 0.0000 | 0.0870 | 0.0043 | 0.0913 | 0.0567 | 2208.35 | 926.49 | 2808.16 |
PERIMETER_MID_ZN_3 | 0.1091 | 0.0000 | 0.1091 | 0.0102 | 0.1193 | 0.0895 | 1731.13 | 1292.53 | 2919.34 |
PERIMETER_MID_ZN_2 | 0.0903 | 0.0000 | 0.0903 | 0.0072 | 0.0975 | 0.0567 | 1597.37 | 1158.02 | 2278.61 |
PERIMETER_MID_ZN_1 | 0.1714 | 0.0000 | 0.1714 | 0.0102 | 0.1816 | 0.0895 | 1596.58 | 1364.67 | 2981.75 |
PERIMETER_MID_ZN_4 | 0.0984 | 0.0000 | 0.0984 | 0.0068 | 0.1052 | 0.0567 | 1718.50 | 1339.13 | 2885.37 |
Total Facility | 2.9124 | 0.0000 | 2.9124 | 0.2235 | 3.1359 | 2.1513 | 2688.19 | 1810.44 | 4084.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 30568167.75 | 0.00 | 30568167.75 | 22614548.33 | 4113.46 | 4.96 | 4641.58 | 41.42 |
PACU_VAV_MID | 28953653.92 | 0.00 | 28953653.92 | 22429071.92 | 4084.37 | 2.77 | 4672.85 | 46.79 |
PACU_VAV_TOP | 28898188.44 | 0.00 | 28898188.44 | 22614548.33 | 4116.57 | 3.37 | 4640.06 | 47.09 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4209 | 0.0000 | 1.4209 | 0.7171 | 1324.54 | 4.96 | 4613.50 |
PACU_VAV_MID | 1.3438 | 0.0000 | 1.3438 | 0.7084 | 1301.58 | 2.77 | 4638.64 |
PACU_VAV_TOP | 1.3399 | 0.0000 | 1.3399 | 0.7171 | 1337.65 | 3.37 | 4601.97 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 58.53 | 2954.52 | 0.00 | 0.00 | 0.00 | 1752.60 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 37.84 | 2835.07 | 0.00 | 0.00 | 0.00 | 1934.15 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 24.69 | 2774.82 | 0.00 | 0.00 | 0.00 | 2005.94 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2800 | 2.2286 | 0.0000 | 0.0000 | 0.0000 | 1.0723 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2463 | 2.1377 | 0.0000 | 0.0000 | 0.0000 | 1.0239 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1834 | 2.1511 | 0.0000 | 0.0000 | 0.0000 | 1.0319 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 948 |
Defaulted Fields | 550 |
Fields with Defaults | 2244 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1081.51 | 11240.73 | 09-APR-17:10 | 207655.42 | 02-JAN-07:10 |
Electricity:Building | 815.55 | 11072.20 | 09-APR-17:10 | 58020.46 | 28-DEC-08:10 |
Electricity:Zone:CORE_BOTTOM | 218.28 | 3047.47 | 01-JAN-00:10 | 16246.98 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 815.55 | 11072.20 | 09-APR-17:10 | 58020.46 | 28-DEC-08:10 |
InteriorLights:Electricity | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 167.80 | 772.31 | 08-JAN-10:30 | 17672.30 | 02-JAN-16:30 |
Electricity:Zone:CORE_MID | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 155.22 | 2025.33 | 01-JAN-00:10 | 10297.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 39.80 | 193.79 | 01-JAN-00:10 | 3488.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 29.33 | 405.59 | 19-MAR-17:10 | 2170.70 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 18.53 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 29.23 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 18.53 | 256.75 | 19-MAR-17:10 | 1374.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 29.31 | 405.59 | 19-MAR-17:10 | 2170.70 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.98 | 19.49 | 08-JAN-10:20 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 4.98 | 19.49 | 08-JAN-10:20 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 18.53 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.12 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.12 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 29.22 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.89 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 4.89 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 18.52 | 256.75 | 19-MAR-17:10 | 1374.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.12 | 12.34 | 01-JAN-10:30 | 465.57 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.12 | 12.34 | 01-JAN-10:30 | 465.57 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 29.33 | 405.59 | 19-MAR-17:10 | 2170.70 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.00 | 19.49 | 08-JAN-10:30 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 18.53 | 256.76 | 09-APR-17:10 | 1374.17 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.13 | 12.34 | 01-JAN-09:50 | 465.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 29.23 | 405.59 | 19-MAR-17:10 | 2170.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 4.90 | 19.49 | 01-JAN-09:50 | 735.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 18.53 | 256.75 | 19-MAR-17:10 | 1374.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.13 | 12.34 | 01-JAN-13:00 | 465.57 | 02-JAN-16:30 |
InteriorEquipment:Electricity | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 178.48 | 2853.68 | 01-JAN-00:10 | 12758.28 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 647.75 | 10299.89 | 01-JAN-00:10 | 40437.79 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 62.52 | 1022.14 | 01-JAN-00:10 | 5877.30 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.54 | 0.00 | 01-JAN-00:10 | 72.66 | 02-JAN-08:10 |
ElectricityProduced:Facility | 118.15 | -0.00 | 15-FEB-07:30 | 26813.75 | 10-MAY-11:30 |
ElectricityProduced:Plant | 118.15 | -0.00 | 15-FEB-07:30 | 26813.75 | 10-MAY-11:30 |
Photovoltaic:ElectricityProduced | 123.93 | 0.00 | 01-JAN-00:10 | 28856.33 | 18-MAY-11:30 |
PowerConversion:ElectricityProduced | -5.79 | -2042.58 | 18-MAY-11:30 | 0.00 | 01-JAN-00:10 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:10 |
Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
DCtoACInverter Ancillary:Cogeneration:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 231.22 | 168.53 | 09-APR-17:10 | 180931.69 | 02-JAN-06:30 |
ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.67 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.62 | 168.34 | 01-JAN-00:10 | 829.67 | 28-DEC-08:20 |
ElectricityPurchased:Facility | 964.31 | 0.00 | 19-MAR-11:40 | 207655.42 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 964.31 | 0.00 | 19-MAR-11:40 | 207655.42 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 964.31 | 0.00 | 19-MAR-11:40 | 207655.42 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 964.31 | 0.00 | 19-MAR-11:40 | 207655.42 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.94 | 0.00 | 01-JAN-00:10 | 10865.06 | 21-MAY-12:20 |
ElectricitySurplusSold:Plant | 0.94 | 0.00 | 01-JAN-00:10 | 10865.06 | 21-MAY-12:20 |
Cogeneration:ElectricitySurplusSold | 0.94 | 0.00 | 01-JAN-00:10 | 10865.06 | 21-MAY-12:20 |
General:Cogeneration:ElectricitySurplusSold | 0.94 | 0.00 | 01-JAN-00:10 | 10865.06 | 21-MAY-12:20 |
ElectricityNet:Facility | 963.37 | -10865.06 | 21-MAY-12:20 | 207655.42 | 02-JAN-07:10 |
ElectricityNet:Plant | 963.37 | -10865.06 | 21-MAY-12:20 | 207655.42 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 963.37 | -10865.06 | 21-MAY-12:20 | 207655.42 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 963.37 | -10865.06 | 21-MAY-12:20 | 207655.42 | 02-JAN-07:10 |
Heating:Electricity | 90.52 | 0.00 | 01-JAN-08:40 | 173726.49 | 02-JAN-06:30 |
General:Heating:Electricity | 90.52 | 0.00 | 01-JAN-08:40 | 173726.49 | 02-JAN-06:30 |
Fans:Electricity | 64.56 | 0.00 | 01-JAN-08:40 | 23971.67 | 14-AUG-15:20 |
General:Fans:Electricity | 64.56 | 0.00 | 01-JAN-08:40 | 23971.67 | 14-AUG-15:20 |
ExteriorLights:Electricity | 34.59 | 0.00 | 01-JAN-08:10 | 3824.74 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 34.59 | 0.00 | 01-JAN-08:10 | 3824.74 | 01-JAN-06:10 |
Cooling:Electricity | 64.53 | 0.00 | 01-JAN-00:10 | 50066.71 | 29-AUG-15:20 |
General:Cooling:Electricity | 64.53 | 0.00 | 01-JAN-00:10 | 50066.71 | 29-AUG-15:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 4.72 | 0.00 | 01-JAN-00:10 | 496.59 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 585.23 | 9277.75 | 01-JAN-00:10 | 34560.50 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 235.66 | 1886.44 | 14-JAN-06:20 | 60568.34 | 07-JAN-08:20 |
NaturalGas:HVAC | 103.54 | 0.00 | 01-JAN-00:40 | 52966.75 | 07-JAN-08:00 |
Heating:NaturalGas | 103.54 | 0.00 | 01-JAN-00:40 | 52966.75 | 07-JAN-08:00 |
General:Heating:NaturalGas | 103.54 | 0.00 | 01-JAN-00:40 | 52966.75 | 07-JAN-08:00 |
NaturalGas:Plant | 132.12 | 1886.44 | 03-JAN-08:10 | 10122.84 | 07-FEB-12:10 |
WaterSystems:NaturalGas | 132.12 | 1886.44 | 03-JAN-08:10 | 10122.84 | 07-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 132.12 | 1886.44 | 03-JAN-08:10 | 10122.84 | 07-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1310.55 | 0.00 | 03-JAN-00:10 | 343428.47 | 02-JAN-07:10 |
EnergyTransfer:Building | 808.79 | 0.00 | 01-JAN-08:40 | 167645.37 | 02-JAN-06:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 160.88 | 0.00 | 01-JAN-00:10 | 19895.77 | 14-AUG-08:00 |
Heating:EnergyTransfer | 74.82 | 0.00 | 01-JAN-08:40 | 167645.37 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.39 | 0.00 | 01-JAN-00:10 | 16825.57 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 74.82 | 0.00 | 01-JAN-08:40 | 167645.37 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.39 | 0.00 | 01-JAN-00:10 | 16825.57 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 733.98 | 0.00 | 01-JAN-00:10 | 142449.63 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 160.49 | 0.00 | 01-JAN-00:10 | 19895.77 | 14-AUG-08:00 |
General:Cooling:EnergyTransfer | 733.98 | 0.00 | 01-JAN-00:10 | 142449.63 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 160.49 | 0.00 | 01-JAN-00:10 | 19895.77 | 14-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.33 | 0.00 | 01-JAN-00:40 | 9559.09 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.81 | 0.00 | 01-JAN-00:40 | 9559.09 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.81 | 0.00 | 01-JAN-00:40 | 9559.09 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 18.52 | 0.00 | 01-JAN-00:10 | 9124.01 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 18.52 | 0.00 | 01-JAN-00:10 | 9124.01 | 24-JUL-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.06 | 0.00 | 01-JAN-00:10 | 8533.26 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.77 | 0.00 | 01-JAN-00:10 | 8533.26 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.77 | 0.00 | 01-JAN-00:10 | 8533.26 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.29 | 0.00 | 01-JAN-00:10 | 4157.31 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.29 | 0.00 | 01-JAN-00:10 | 4157.31 | 14-AUG-15:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.82 | 0.00 | 01-JAN-00:10 | 6759.05 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.33 | 0.00 | 01-JAN-00:10 | 6759.05 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.33 | 0.00 | 01-JAN-00:10 | 6759.05 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.49 | 0.00 | 01-JAN-00:10 | 4233.61 | 14-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.49 | 0.00 | 01-JAN-00:10 | 4233.61 | 14-AUG-15:50 |
EnergyTransfer:Zone:CORE_MID | 121.85 | 0.00 | 01-JAN-00:10 | 18464.63 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.79 | 0.00 | 01-JAN-00:10 | 18464.63 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.79 | 0.00 | 01-JAN-00:10 | 18464.63 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 121.06 | 0.00 | 01-JAN-00:10 | 15993.93 | 14-AUG-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 121.06 | 0.00 | 01-JAN-00:10 | 15993.93 | 14-AUG-07:40 |
EnergyTransfer:Zone:CORE_TOP | 112.92 | 0.00 | 01-JAN-00:40 | 27015.97 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.11 | 0.00 | 01-JAN-00:40 | 27015.97 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.11 | 0.00 | 01-JAN-00:40 | 27015.97 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 109.81 | 0.00 | 01-JAN-00:10 | 17509.89 | 14-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 109.81 | 0.00 | 01-JAN-00:10 | 17509.89 | 14-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 27.86 | 0.00 | 01-JAN-00:40 | 7757.92 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.17 | 0.00 | 01-JAN-00:40 | 7757.92 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.17 | 0.00 | 01-JAN-00:40 | 7757.92 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.69 | 0.00 | 01-JAN-00:10 | 5977.13 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.69 | 0.00 | 01-JAN-00:10 | 5977.13 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.32 | 0.00 | 01-JAN-00:40 | 8656.33 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.66 | 0.00 | 01-JAN-00:40 | 7046.52 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.66 | 0.00 | 01-JAN-00:40 | 7046.52 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.66 | 0.00 | 01-JAN-00:10 | 8656.33 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 21.66 | 0.00 | 01-JAN-00:10 | 8656.33 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 43.80 | 0.00 | 01-JAN-00:40 | 13082.37 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.58 | 0.00 | 01-JAN-00:40 | 10810.16 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.58 | 0.00 | 01-JAN-00:40 | 10810.16 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.22 | 0.00 | 01-JAN-00:10 | 13082.37 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.22 | 0.00 | 01-JAN-00:10 | 13082.37 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.03 | 0.00 | 01-JAN-00:40 | 9321.90 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.86 | 0.00 | 01-JAN-00:40 | 6992.01 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.86 | 0.00 | 01-JAN-00:40 | 6992.01 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.18 | 0.00 | 01-JAN-00:10 | 9321.90 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.18 | 0.00 | 01-JAN-00:10 | 9321.90 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.49 | 0.00 | 01-JAN-00:10 | 6186.87 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.01 | 0.00 | 01-JAN-00:10 | 6186.87 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.01 | 0.00 | 01-JAN-00:10 | 6186.87 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.48 | 0.00 | 01-JAN-00:10 | 4506.96 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.48 | 0.00 | 01-JAN-00:10 | 4506.96 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.87 | 0.00 | 01-JAN-00:10 | 6992.51 | 24-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.74 | 0.00 | 01-JAN-00:10 | 5748.87 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.74 | 0.00 | 01-JAN-00:10 | 5748.87 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.13 | 0.00 | 01-JAN-00:10 | 6992.51 | 24-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.13 | 0.00 | 01-JAN-00:10 | 6992.51 | 24-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 41.61 | 0.00 | 01-JAN-00:10 | 12364.38 | 10-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.28 | 0.00 | 01-JAN-00:10 | 10369.93 | 26-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.28 | 0.00 | 01-JAN-00:10 | 10369.93 | 26-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.33 | 0.00 | 01-JAN-00:10 | 12364.38 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 27.33 | 0.00 | 01-JAN-00:10 | 12364.38 | 10-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.97 | 0.00 | 01-JAN-00:10 | 7533.00 | 31-JUL-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.76 | 0.00 | 01-JAN-00:10 | 5663.55 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.76 | 0.00 | 01-JAN-00:10 | 5663.55 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.21 | 0.00 | 01-JAN-00:10 | 7533.00 | 31-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.21 | 0.00 | 01-JAN-00:10 | 7533.00 | 31-JUL-17:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.24 | 0.00 | 01-JAN-00:10 | 6816.65 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.55 | 0.00 | 01-JAN-00:10 | 6816.65 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.55 | 0.00 | 01-JAN-00:10 | 6816.65 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.69 | 0.00 | 01-JAN-00:10 | 5472.82 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.69 | 0.00 | 01-JAN-00:10 | 5472.82 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.02 | 0.00 | 01-JAN-00:10 | 8717.77 | 31-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.57 | 0.00 | 01-JAN-00:10 | 5680.75 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.57 | 0.00 | 01-JAN-00:10 | 5680.75 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 21.44 | 0.00 | 01-JAN-00:10 | 8717.77 | 31-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 21.44 | 0.00 | 01-JAN-00:10 | 8717.77 | 31-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.68 | 0.00 | 01-JAN-00:10 | 13035.78 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.85 | 0.00 | 01-JAN-00:10 | 8778.31 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.85 | 0.00 | 01-JAN-00:10 | 8778.31 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.83 | 0.00 | 01-JAN-00:10 | 13035.78 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.83 | 0.00 | 01-JAN-00:10 | 13035.78 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.05 | 0.00 | 01-JAN-00:10 | 8928.03 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.60 | 0.00 | 01-JAN-00:10 | 5684.36 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.60 | 0.00 | 01-JAN-00:10 | 5684.36 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.45 | 0.00 | 01-JAN-00:10 | 8928.03 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.45 | 0.00 | 01-JAN-00:10 | 8928.03 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 50.33 | 0.00 | 01-JAN-00:10 | 6128.50 | 10-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 50.33 | 0.00 | 01-JAN-00:10 | 6128.50 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 50.33 | 0.00 | 01-JAN-00:10 | 6128.50 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 50.33 | 0.00 | 01-JAN-00:10 | 6128.50 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 451.42 | 0.00 | 01-JAN-08:40 | 193689.97 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 177.49 | 0.00 | 01-JAN-08:40 | 183454.58 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 273.93 | 0.00 | 01-JAN-00:10 | 193689.97 | 29-AUG-14:30 |
EnergyTransfer:Plant | 50.33 | 0.00 | 01-JAN-00:10 | 6128.50 | 10-FEB-12:10 |
WaterSystems:EnergyTransfer | 50.33 | 0.00 | 01-JAN-00:10 | 6128.50 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 50.33 | 0.00 | 01-JAN-00:10 | 6128.50 | 10-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.385 | -160.494 | 0.000 | 0.000 | 33.236 | 39.795 | 178.484 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -91.407 |
CORE_MID | 0.000 | 0.000 | 0.791 | -121.055 | 0.000 | 0.000 | 34.257 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -69.213 |
CORE_TOP | 0.000 | 0.000 | 3.107 | -109.808 | 0.000 | 0.000 | 34.956 | 39.795 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -83.476 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 6.170 | -21.691 | 0.000 | 0.000 | 7.564 | 4.998 | 24.333 | 13.900 | 0.000 | 0.019 | 0.002 | 0.000 | -28.198 | 0.000 | -6.966 | -0.129 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.657 | -21.663 | 0.000 | 0.000 | 4.721 | 3.131 | 15.404 | 26.319 | 0.000 | 0.011 | 0.000 | 0.000 | -18.264 | 0.000 | -4.712 | -8.605 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.583 | -39.218 | 0.000 | 0.000 | 7.395 | 4.897 | 24.332 | 56.925 | 0.000 | 0.016 | 0.001 | 0.000 | -28.003 | 0.000 | -7.254 | -23.673 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.856 | -22.176 | 0.000 | 0.000 | 4.756 | 3.126 | 15.403 | 28.426 | 0.000 | 0.010 | 0.000 | 0.000 | -18.845 | 0.000 | -4.761 | -9.796 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.008 | -19.482 | 0.000 | 0.000 | 7.533 | 4.982 | 24.333 | 14.192 | 0.000 | 0.013 | 0.000 | 0.000 | -29.188 | 0.000 | -3.872 | -1.517 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.741 | -20.127 | 0.000 | 0.000 | 4.690 | 3.124 | 15.404 | 26.452 | 0.000 | 0.006 | 0.000 | 0.000 | -19.146 | 0.000 | -2.657 | -9.486 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 14.278 | -27.328 | 0.000 | 0.000 | 7.559 | 4.887 | 24.332 | 57.570 | 0.000 | 0.388 | 0.001 | 0.000 | -29.292 | 0.000 | -35.352 | -17.042 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.759 | -20.212 | 0.000 | 0.000 | 4.713 | 3.118 | 15.403 | 28.645 | 0.000 | 0.006 | 0.000 | 0.000 | -19.836 | 0.000 | -2.688 | -10.909 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.549 | -23.694 | 0.000 | 0.000 | 7.466 | 4.997 | 24.333 | 13.654 | 0.000 | 0.017 | 6.660 | 0.000 | -29.850 | 0.000 | -6.132 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.574 | -21.442 | 0.000 | 0.000 | 3.445 | 3.131 | 15.404 | 26.050 | 0.000 | 0.009 | 0.001 | 0.000 | -19.299 | 0.000 | -4.151 | -4.721 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.852 | -41.833 | 0.000 | 0.000 | 7.296 | 4.897 | 24.332 | 56.639 | 0.000 | 0.013 | 0.001 | 0.000 | -29.563 | 0.000 | -6.375 | -17.259 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.600 | -23.447 | 0.000 | 0.000 | 4.693 | 3.126 | 15.403 | 28.282 | 0.000 | 0.009 | 0.001 | 0.000 | -19.927 | 0.000 | -4.185 | -5.555 |
TOPFLOOR_PLENUM | 12.811 | -18.515 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.012 | 16.491 | 0.000 | 0.000 | 0.000 | -10.799 | -0.003 |
MIDFLOOR_PLENUM | 6.768 | -9.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.021 | 13.109 | 0.000 | 0.000 | 0.000 | -10.607 | -0.000 |
FIRSTFLOOR_PLENUM | 4.327 | -12.494 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.016 | 16.692 | 0.000 | 0.000 | 0.000 | -8.541 | -0.000 |
Total Facility | 23.906 | -40.300 | 50.911 | -693.671 | 0.000 | 0.000 | 174.280 | 167.801 | 647.750 | 377.055 | 0.000 | 0.566 | 52.959 | 0.000 | -289.412 | 0.000 | -119.053 | -352.790 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-SEP-06:01 | 0.00 | 0.00 | 0.00 | -32702.36 | 0.00 | 0.00 | 696.92 | 1162.90 | 6044.02 | 0.00 | 0.00 | 0.00 | 24798.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-JUL-06:02 | 0.00 | 0.00 | 0.00 | -26304.58 | 0.00 | 0.00 | 715.86 | 1162.90 | 3025.92 | 0.00 | 0.00 | 0.00 | 21399.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -26476.06 | 0.00 | 0.00 | 715.56 | 1162.90 | 3025.92 | 0.00 | 0.00 | 0.00 | 21571.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6198.54 | 0.00 | 0.00 | 149.15 | 116.94 | 637.89 | 2191.35 | 0.00 | 0.00 | 3136.48 | 0.00 | -0.00 | 0.00 | -33.26 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-08:52 | 0.00 | 0.00 | 0.00 | -13192.21 | 0.00 | 0.00 | 15.54 | 12.34 | 302.86 | 10296.95 | 0.00 | 0.00 | 2760.46 | 0.00 | -0.00 | 0.00 | -195.93 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:22 | 0.00 | 0.00 | 0.00 | -20721.30 | 0.00 | 0.00 | 22.50 | 19.49 | 478.41 | 14108.08 | 0.00 | 0.00 | 6270.85 | 0.00 | -0.00 | 0.00 | -178.03 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -15629.84 | 0.00 | 0.00 | 13.12 | 12.34 | 302.86 | 11762.42 | 0.00 | 0.00 | 3688.01 | 0.00 | -0.00 | 0.00 | -148.90 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4506.97 | 0.00 | 0.00 | 737.22 | 350.81 | 1435.25 | 3627.70 | 0.00 | 23.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1668.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:42 | 0.00 | 0.00 | 0.00 | -10751.21 | 0.00 | 0.00 | 16.68 | 12.34 | 302.86 | 10475.47 | 0.00 | 0.00 | 69.38 | 0.00 | -0.00 | 0.00 | -125.50 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-12:23 | 0.00 | 0.00 | 0.00 | -15824.68 | 0.00 | 0.00 | 25.46 | 19.49 | 478.41 | 16144.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -90.72 | -752.58 |
PERIMETER_BOT_ZN_4 | 23-JUL-17:21 | 0.00 | 0.00 | 0.00 | -12752.20 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 11501.16 | 0.00 | 0.00 | 1027.29 | 0.00 | -0.00 | 0.00 | -33.01 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6740.92 | 0.00 | 0.00 | 145.90 | 116.94 | 637.89 | 2161.23 | 0.00 | 0.00 | 3707.59 | 0.00 | -0.00 | 0.00 | -28.62 | 0.00 |
PERIMETER_MID_ZN_2 | 30-JUL-08:52 | 0.00 | 0.00 | 0.00 | -13958.13 | 0.00 | 0.00 | 14.34 | 12.34 | 302.86 | 10334.36 | 0.00 | 0.00 | 3393.91 | 0.00 | -0.00 | 0.00 | -99.68 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:12 | 0.00 | 0.00 | 0.00 | -18329.75 | 0.00 | 0.00 | 24.80 | 19.49 | 478.41 | 13009.17 | 0.00 | 0.00 | 4838.91 | 0.00 | -0.00 | 0.00 | -41.03 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-17:21 | 0.00 | 0.00 | 0.00 | -15042.04 | 0.00 | 0.00 | 0.00 | 12.34 | 244.42 | 11393.60 | 0.00 | 0.00 | 3465.76 | 0.00 | -0.00 | 0.00 | -74.07 | 0.00 |
TOPFLOOR_PLENUM | 24-JUL-14:00 | 0.00 | -9123.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 9066.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-15:20 | 0.00 | -4157.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 4134.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 14-AUG-06:13 | 0.00 | -4275.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4335.26 | 0.00 | -0.00 | 0.00 | -60.16 | 0.00 |
Total Facility | 14-AUG-06:02 | 0.00 | -3775.14 | 0.00 | -145234.57 | 0.00 | 0.00 | 3582.83 | 4686.94 | 18346.02 | 18529.93 | 0.00 | 0.00 | 114150.23 | 0.00 | -2812.50 | 0.00 | -7473.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:11 | 0.00 | 0.00 | 18524.06 | 0.00 | 0.00 | 0.00 | 511.91 | 387.63 | 4048.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23471.66 |
CORE_MID | 02-JAN-06:11 | 0.00 | 0.00 | 20080.02 | 0.00 | 0.00 | 0.00 | 526.74 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24020.32 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 29159.87 | 0.00 | 0.00 | 0.00 | 536.24 | 387.63 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33109.66 |
PERIMETER_TOP_ZN_3 | 26-DEC-05:01 | 0.00 | 0.00 | 8526.66 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1742.82 | 0.00 | 0.00 | -7380.36 |
PERIMETER_TOP_ZN_2 | 26-DEC-05:01 | 0.00 | 0.00 | 9229.74 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.43 | 0.00 | 0.00 | -8447.94 |
PERIMETER_TOP_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 13972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1753.30 | 0.00 | 0.00 | -12815.32 |
PERIMETER_TOP_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 9191.87 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.45 | 0.00 | 0.00 | -8410.04 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 6621.65 | 0.00 | 0.00 | 0.00 | 112.69 | 81.72 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1084.70 | 0.00 | -77.67 | -6291.58 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 6637.39 | 0.00 | 0.00 | 0.00 | 71.33 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -737.39 | 0.00 | -52.68 | -6374.19 |
PERIMETER_BOT_ZN_1 | 26-DEC-08:00 | 0.00 | 0.00 | 10369.31 | 0.00 | 0.00 | 0.00 | 228.02 | 245.15 | 637.88 | 0.00 | 0.00 | 0.00 | 5174.43 | 0.00 | -2075.56 | 0.00 | -14579.23 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 6572.95 | 0.00 | 0.00 | 0.00 | 71.32 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -721.97 | 0.00 | -52.65 | -6325.18 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 7338.09 | 0.00 | 0.00 | 0.00 | 112.82 | 81.72 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1094.59 | 0.00 | -123.32 | -6952.61 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 7012.98 | 0.00 | 0.00 | 0.00 | 71.46 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -745.73 | 0.00 | -83.53 | -6710.72 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 10599.86 | 0.00 | 0.00 | 0.00 | 112.82 | 81.72 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1120.76 | 0.00 | -125.14 | -10186.39 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 6966.87 | 0.00 | 0.00 | 0.00 | 71.45 | 51.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -728.49 | 0.00 | -83.51 | -6681.86 |
TOPFLOOR_PLENUM | 09-JAN-06:12 | 11337.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -198.46 | -11139.21 |
MIDFLOOR_PLENUM | 02-JAN-07:02 | 8637.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -173.10 | -8464.33 |
FIRSTFLOOR_PLENUM | 02-JAN-07:02 | 7777.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -138.21 | -7639.04 |
Total Facility | 02-JAN-06:11 | 7868.19 | 0.00 | 169286.07 | 0.00 | 0.00 | 0.00 | 2681.62 | 1963.59 | 16350.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10941.64 | 0.00 | -2808.73 | -184399.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.0427 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3740 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.0485 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.1624 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2785 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7031 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5214 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0760 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5242 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0748 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6393 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0754 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3680 | 2.3680 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9665 | 1.9665 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0099 | 2.0099 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5774 | 0.5774 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7513 | 0.7513 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1186 | 1.1186 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8214 | 0.8214 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4567 | 0.4567 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6182 | 0.6182 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9151 | 0.9151 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6848 | 0.6848 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5085 | 0.5085 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7563 | 0.7563 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0456 | 1.0456 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7715 | 0.7715 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.0427 | 4.3740 | 5.0427 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.0485 | 4.1624 | 5.0485 | 1.0748 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2785 | 4.7031 | 5.2785 | 1.0754 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1840 | 1.1840 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9833 | 0.9833 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0049 | 1.0049 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2887 | 0.2887 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3756 | 0.3756 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5593 | 0.5593 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4107 | 0.4107 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2283 | 0.2283 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3091 | 0.3091 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4576 | 0.4576 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3424 | 0.3424 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2543 | 0.2543 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3782 | 0.3782 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5228 | 0.5228 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3858 | 0.3858 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5214 | 1.0760 | 1.0760 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5242 | 1.0748 | 1.0748 | 1.0748 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6393 | 1.0754 | 1.0754 | 1.0754 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 227.67 |
Number of hours cooling loads not met | 59.33 |
Number of hours not met | 287.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 90.52 | 173726.49 | 103.54 | 52966.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 64.53 | 50066.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 167.80 | 17672.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 34.59 | 3824.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 62.52 | 5877.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.54 | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.62 | 829.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 64.56 | 23971.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 132.12 | 10122.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- DCtoACInverter Ancillary | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 647.75 | 1081.51 |
Natural Gas | 0.00 | 235.66 |
Additional | 0.00 | 0.00 |
Total | 647.75 | 1317.18 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 123.93 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 33.68 |
Space Heating | 18.17 |
Space Cooling | 12.95 |
Fans (All) | 12.96 |
Service Water Heating | 0.00 |
Receptacle Equipment | 130.01 |
Miscellaneous (All) | 217.08 |
Subtotal | 217.08 |
Natural Gas [MJ/m2] | |
Space Heating | 20.78 |
Service Water Heating | 26.52 |
Miscellaneous (All) | 47.30 |
Subtotal | 47.30 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.74 |
Space Heating | 14.73 |
Space Cooling | 4.90 |
Fans (All) | 4.90 |
Service Water Heating | 10.03 |
Receptacle Equipment | 49.18 |
Miscellaneous | 3.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
PV_SCH | 8760. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 1996. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 886. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8743.83 | 16.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8725.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 34.17 | 0.00 | 0.00 | 0.00 |
Average | 8748.87 | 11.13 | 0.00 | 0.00 | 0.00 |
Sum | 157479.67 | 200.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8723.83 | 36.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8726.33 | 33.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8719.83 | 40.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8719.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 40.17 | 0.00 | 0.00 | 0.00 |
Average | 8741.47 | 18.53 | 0.00 | 0.00 | 0.00 |
Sum | 157346.50 | 333.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128280.83 | 23.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128302.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128302.00 | 23.17 | 0.00 | 0.00 | 0.00 |
Average | 34141.66 | 1.68 | 0.00 | 0.00 | 0.00 |
Sum | 614549.83 | 30.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:32:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692721E+10 | 6460.64 | 12-JAN-17:00 | 7.20 | 5.41 | 0.175624E+10 | 2583.96 | 13-JAN-14:09 | 5.00 | 3.51 |
February | 0.751240E+10 | 9250.32 | 09-FEB-17:00 | 5.00 | 2.69 | 0.171207E+10 | 2608.06 | 28-FEB-10:39 | 10.93 | 10.15 |
March | 0.112692E+11 | 12919.56 | 22-MAR-07:08 | 5.82 | 5.55 | 0.213057E+10 | 2606.65 | 02-MAR-10:20 | 5.82 | 5.55 |
April | 0.125790E+11 | 23115.58 | 28-APR-06:02 | 11.10 | 10.22 | 0.190647E+10 | 2606.68 | 04-APR-09:20 | 11.10 | 10.22 |
May | 0.167816E+11 | 28983.43 | 08-MAY-06:02 | 9.90 | 9.62 | 0.207345E+10 | 2606.67 | 05-MAY-09:09 | 9.90 | 9.62 |
June | 0.182820E+11 | 31942.99 | 12-JUN-06:02 | 14.60 | 13.50 | 0.206883E+10 | 2606.69 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.188182E+11 | 32623.39 | 10-JUL-06:02 | 12.88 | 11.52 | 0.192368E+10 | 2606.65 | 20-JUL-13:20 | 26.30 | 16.68 |
August | 0.206273E+11 | 32260.45 | 28-AUG-06:02 | 15.30 | 14.16 | 0.215889E+10 | 2606.81 | 09-AUG-09:00 | 15.30 | 14.16 |
September | 0.169753E+11 | 32703.38 | 05-SEP-06:01 | 11.02 | 9.56 | 0.191658E+10 | 2606.66 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.134636E+11 | 27521.66 | 10-OCT-06:02 | 12.12 | 10.88 | 0.198327E+10 | 2608.25 | 18-OCT-09:00 | 9.40 | 9.15 |
November | 0.937635E+10 | 13300.66 | 07-NOV-08:10 | 11.70 | 10.10 | 0.192495E+10 | 2606.63 | 10-NOV-10:09 | 6.88 | 5.74 |
December | 0.788229E+10 | 8752.78 | 06-DEC-16:10 | 2.93 | 2.59 | 0.180274E+10 | 2606.64 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.160494E+12 | 0.233578E+11 | ||||||||
Minimum of Months | 0.692721E+10 | 6460.64 | 2.93 | 2.59 | 0.171207E+10 | 2583.96 | 5.00 | 3.51 | ||
Maximum of Months | 0.206273E+11 | 32703.38 | 15.30 | 14.16 | 0.215889E+10 | 2608.25 | 26.30 | 16.68 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 40128517.77 | 1427.32 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.340680E+09 | 2405.10 | 14-MAR-14:40 | 15.93 | 10.38 | 0.00 | 0.00 | 01-MAR-00:10 | 15.93 | 10.38 |
April | 0.125775E+10 | 7660.50 | 27-APR-14:20 | 26.47 | 16.98 | 0.00 | 0.00 | 01-APR-00:10 | 26.47 | 16.98 |
May | 0.245665E+10 | 8146.08 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.322064E+10 | 7969.76 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.429786E+10 | 9124.01 | 24-JUL-14:00 | 29.40 | 18.12 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 18.12 |
August | 0.415750E+10 | 9114.26 | 10-AUG-14:40 | 29.93 | 18.99 | 0.00 | 0.00 | 01-AUG-00:10 | 29.93 | 18.99 |
September | 0.216517E+10 | 7080.56 | 14-SEP-14:30 | 23.90 | 17.04 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.04 |
October | 0.541971E+09 | 4809.71 | 04-OCT-14:40 | 21.50 | 11.47 | 0.00 | 0.00 | 01-OCT-00:10 | 21.50 | 11.47 |
November | 36392723.68 | 1935.57 | 04-NOV-14:30 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 666521.90 | 167.35 | 02-DEC-15:20 | 11.33 | 5.21 | 0.00 | 0.00 | 01-DEC-00:10 | 11.33 | 5.21 |
Annual Sum or Average | 0.185154E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 4.99 | 0.00 | 0.00 | 5.92 | 4.99 | ||
Maximum of Months | 0.429786E+10 | 9124.01 | 29.93 | 18.99 | 0.00 | 0.00 | 29.93 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5243530.38 | 1687.13 | 07-JAN-06:01 | -2.2 | -2.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.2 | -2.2 |
February | 48262051.84 | 1503.73 | 18-FEB-06:01 | -1.8 | -2.6 | 0.00 | 0.00 | 01-FEB-00:10 | -1.8 | -2.6 |
March | 0.167577E+09 | 2457.42 | 01-MAR-07:02 | -0.1 | -1.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.7 |
April | 0.423018E+09 | 2477.91 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.940312E+09 | 2847.56 | 15-MAY-15:20 | 23.50 | 12.70 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 12.70 |
June | 0.154033E+10 | 2916.21 | 28-JUN-15:50 | 26.10 | 16.17 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.17 |
July | 0.213738E+10 | 4030.96 | 31-JUL-15:20 | 28.50 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28.50 | 19.00 |
August | 0.239544E+10 | 4157.31 | 14-AUG-15:20 | 27.17 | 17.34 | 0.00 | 0.00 | 01-AUG-00:10 | 27.17 | 17.34 |
September | 0.123675E+10 | 3286.08 | 11-SEP-15:30 | 23.30 | 15.99 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 15.99 |
October | 0.333945E+09 | 1855.74 | 04-OCT-15:40 | 21.30 | 11.43 | 0.00 | 0.00 | 01-OCT-00:10 | 21.30 | 11.43 |
November | 54803775.95 | 1280.56 | 10-NOV-07:03 | 4.08 | 3.61 | 0.00 | 0.00 | 01-NOV-00:10 | 4.08 | 3.61 |
December | 7301071.27 | 1295.37 | 23-DEC-06:11 | 3.90 | 3.43 | 0.00 | 0.00 | 01-DEC-00:10 | 3.90 | 3.43 |
Annual Sum or Average | 0.929037E+10 | 0.00 | ||||||||
Minimum of Months | 5243530.38 | 1280.56 | -2.2 | -2.6 | 0.00 | 0.00 | -2.2 | -2.6 | ||
Maximum of Months | 0.239544E+10 | 4157.31 | 28.50 | 19.00 | 0.00 | 0.00 | 28.50 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42525054.75 | 2084.58 | 13-JAN-06:11 | 3.13 | 2.22 | 0.00 | 0.00 | 01-JAN-00:10 | 3.13 | 2.22 |
February | 0.118522E+09 | 2267.42 | 10-FEB-07:02 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.362746E+09 | 2840.44 | 01-MAR-07:02 | -0.1 | -1.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.7 |
April | 0.700354E+09 | 2581.90 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.135092E+10 | 2890.86 | 15-MAY-16:00 | 23.90 | 12.85 | 0.00 | 0.00 | 01-MAY-00:10 | 23.90 | 12.85 |
June | 0.192460E+10 | 3033.03 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.251638E+10 | 4064.72 | 24-JUL-15:10 | 30.32 | 18.75 | 0.00 | 0.00 | 01-JUL-00:10 | 30.32 | 18.75 |
August | 0.284813E+10 | 4275.01 | 14-AUG-06:13 | 15.73 | 13.91 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.91 |
September | 0.174360E+10 | 3657.37 | 11-SEP-15:40 | 23.30 | 16.04 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.04 |
October | 0.662973E+09 | 2440.76 | 04-OCT-16:00 | 21.10 | 11.40 | 0.00 | 0.00 | 01-OCT-00:10 | 21.10 | 11.40 |
November | 0.152105E+09 | 1875.03 | 16-NOV-07:03 | 3.48 | 2.25 | 0.00 | 0.00 | 01-NOV-00:10 | 3.48 | 2.25 |
December | 71681880.99 | 1953.36 | 06-DEC-07:02 | 0.18 | -0.1 | 0.00 | 0.00 | 01-DEC-00:10 | 0.18 | -0.1 |
Annual Sum or Average | 0.124945E+11 | 0.00 | ||||||||
Minimum of Months | 42525054.75 | 1875.03 | -0.1 | -1.7 | 0.00 | 0.00 | -0.1 | -1.7 | ||
Maximum of Months | 0.284813E+10 | 4275.01 | 30.32 | 18.75 | 0.00 | 0.00 | 30.32 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526337E+10 | 5645.34 | 12-JAN-17:00 | 7.20 | 5.41 | 0.158453E+10 | 2330.34 | 12-JAN-14:00 | 7.20 | 5.41 |
February | 0.598824E+10 | 6379.02 | 28-FEB-17:00 | 14.40 | 10.82 | 0.152904E+10 | 2542.81 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.843118E+10 | 7660.82 | 02-MAR-17:00 | 12.80 | 8.57 | 0.200500E+10 | 2606.56 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.935091E+10 | 12883.03 | 27-APR-16:00 | 27.20 | 16.90 | 0.186402E+10 | 2606.66 | 14-APR-09:20 | 27.20 | 16.90 |
May | 0.125664E+11 | 13676.43 | 15-MAY-16:00 | 23.90 | 12.85 | 0.205991E+10 | 2606.66 | 05-MAY-09:09 | 23.90 | 12.85 |
June | 0.140055E+11 | 26019.75 | 12-JUN-06:02 | 14.60 | 13.50 | 0.206225E+10 | 2606.67 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.146870E+11 | 26306.03 | 25-JUL-06:02 | 13.98 | 13.26 | 0.191963E+10 | 2606.65 | 07-JUL-13:20 | 13.98 | 13.26 |
August | 0.159491E+11 | 26207.35 | 15-AUG-06:02 | 14.72 | 12.01 | 0.215469E+10 | 2606.77 | 09-AUG-09:00 | 14.72 | 12.01 |
September | 0.124651E+11 | 26198.64 | 11-SEP-06:01 | 12.07 | 10.69 | 0.190655E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.938173E+10 | 12482.75 | 04-OCT-16:00 | 21.10 | 11.40 | 0.192327E+10 | 2606.65 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.693909E+10 | 6895.05 | 06-NOV-17:00 | 11.70 | 10.80 | 0.174108E+10 | 2606.59 | 06-NOV-14:50 | 11.70 | 10.80 |
December | 0.602800E+10 | 6023.26 | 06-DEC-16:20 | 2.57 | 2.27 | 0.158739E+10 | 2454.25 | 06-DEC-14:00 | 2.57 | 2.27 |
Annual Sum or Average | 0.121056E+12 | 0.223374E+11 | ||||||||
Minimum of Months | 0.526337E+10 | 5645.34 | 2.57 | 2.27 | 0.152904E+10 | 2330.34 | 2.57 | 2.27 | ||
Maximum of Months | 0.159491E+11 | 26306.03 | 27.20 | 16.90 | 0.215469E+10 | 2606.77 | 27.20 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361379E+10 | 5363.48 | 11-JAN-17:00 | 12.20 | 9.27 | 0.151807E+10 | 2243.62 | 11-JAN-14:00 | 12.20 | 9.27 |
February | 0.476070E+10 | 6311.43 | 28-FEB-17:00 | 14.40 | 10.82 | 0.144761E+10 | 2514.99 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.760169E+10 | 7231.86 | 02-MAR-17:00 | 12.80 | 8.57 | 0.189211E+10 | 2604.68 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.876479E+10 | 14390.36 | 27-APR-15:30 | 27.20 | 17.10 | 0.180287E+10 | 2606.66 | 27-APR-13:20 | 27.20 | 17.10 |
May | 0.119309E+11 | 15531.83 | 15-MAY-15:30 | 23.60 | 12.74 | 0.203577E+10 | 2607.44 | 23-MAY-09:20 | 10.57 | 8.99 |
June | 0.136577E+11 | 15756.05 | 28-JUN-15:50 | 26.10 | 16.17 | 0.205202E+10 | 2606.67 | 09-JUN-13:09 | 26.10 | 16.17 |
July | 0.146546E+11 | 21014.33 | 24-JUL-06:03 | 17.48 | 14.11 | 0.191282E+10 | 2606.65 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.156133E+11 | 26477.14 | 14-AUG-06:02 | 15.47 | 13.75 | 0.214762E+10 | 2606.75 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.114107E+11 | 15403.50 | 11-SEP-15:30 | 23.30 | 15.99 | 0.188302E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.819098E+10 | 12430.13 | 04-OCT-16:00 | 21.10 | 11.40 | 0.183324E+10 | 2606.62 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.550964E+10 | 6190.62 | 02-NOV-16:00 | 13.30 | 10.88 | 0.162218E+10 | 2491.45 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.409984E+10 | 5605.82 | 05-DEC-16:15 | 6.10 | 4.53 | 0.149066E+10 | 2324.21 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.109809E+12 | 0.216380E+11 | ||||||||
Minimum of Months | 0.361379E+10 | 5363.48 | 6.10 | 4.53 | 0.144761E+10 | 2243.62 | 5.00 | 4.36 | ||
Maximum of Months | 0.156133E+11 | 26477.14 | 27.20 | 17.10 | 0.214762E+10 | 2607.44 | 27.20 | 17.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134752E+09 | 982.94 | 11-JAN-16:10 | 14.03 | 10.30 | 0.305927E+09 | 432.83 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.412919E+09 | 1249.50 | 28-FEB-15:00 | 13.90 | 10.81 | 0.285433E+09 | 510.87 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.113905E+10 | 1325.19 | 10-MAR-14:50 | 16.20 | 11.59 | 0.366046E+09 | 535.87 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.166821E+10 | 4259.81 | 27-APR-15:20 | 27.20 | 17.16 | 0.359284E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.270280E+10 | 4595.82 | 15-MAY-14:30 | 23.30 | 13.06 | 0.418250E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.335091E+10 | 4897.16 | 21-JUN-15:30 | 24.70 | 15.68 | 0.428285E+09 | 549.50 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.386008E+10 | 6198.28 | 24-JUL-06:03 | 17.48 | 14.11 | 0.401139E+09 | 549.50 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.393476E+10 | 5355.28 | 09-AUG-15:20 | 28.47 | 18.71 | 0.449406E+09 | 549.53 | 09-AUG-09:00 | 28.47 | 18.71 |
September | 0.238246E+10 | 4097.05 | 12-SEP-14:40 | 24.40 | 16.65 | 0.385343E+09 | 549.49 | 15-SEP-09:20 | 16.70 | 14.42 |
October | 0.136195E+10 | 2507.58 | 04-OCT-15:20 | 21.50 | 11.47 | 0.357097E+09 | 549.49 | 03-OCT-13:20 | 21.50 | 11.47 |
November | 0.564609E+09 | 1190.36 | 02-NOV-14:40 | 13.67 | 11.26 | 0.314813E+09 | 491.31 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.178907E+09 | 929.46 | 05-DEC-14:50 | 10.10 | 6.91 | 0.295510E+09 | 420.15 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.216914E+11 | 0.436653E+10 | ||||||||
Minimum of Months | 0.134752E+09 | 929.46 | 10.10 | 6.91 | 0.285433E+09 | 420.15 | 10.00 | 7.01 | ||
Maximum of Months | 0.393476E+10 | 6198.28 | 28.47 | 18.71 | 0.449406E+09 | 549.53 | 28.47 | 18.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131886E+09 | 638.35 | 20-JAN-11:00 | 5.60 | 3.25 | 0.194271E+09 | 280.41 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.353524E+09 | 833.73 | 27-FEB-15:50 | 19.50 | 12.39 | 0.187102E+09 | 334.80 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.930463E+09 | 2597.72 | 14-MAR-09:40 | 9.27 | 7.14 | 0.247986E+09 | 347.88 | 02-MAR-10:20 | 9.27 | 7.14 |
April | 0.178593E+10 | 6507.23 | 27-APR-09:00 | 17.80 | 12.21 | 0.240845E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.264470E+10 | 10584.78 | 14-MAY-09:13 | 17.43 | 11.77 | 0.269320E+09 | 348.03 | 23-MAY-09:20 | 10.57 | 8.99 |
June | 0.354552E+10 | 12141.79 | 25-JUN-09:23 | 17.25 | 12.50 | 0.273650E+09 | 347.88 | 09-JUN-13:09 | 17.25 | 12.50 |
July | 0.382533E+10 | 12295.49 | 30-JUL-09:02 | 20.87 | 15.88 | 0.255282E+09 | 348.42 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.413986E+10 | 13194.55 | 06-AUG-08:52 | 15.30 | 12.83 | 0.286345E+09 | 348.40 | 10-AUG-09:00 | 23.20 | 17.13 |
September | 0.249446E+10 | 10536.19 | 10-SEP-10:02 | 17.48 | 13.63 | 0.248365E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.119716E+10 | 4650.69 | 04-OCT-09:10 | 15.87 | 10.58 | 0.237061E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.422339E+09 | 830.40 | 04-NOV-10:30 | 16.95 | 14.30 | 0.202836E+09 | 328.79 | 02-NOV-13:00 | 16.95 | 14.30 |
December | 0.191459E+09 | 683.76 | 05-DEC-10:30 | 7.50 | 5.28 | 0.188730E+09 | 293.61 | 05-DEC-10:50 | 8.03 | 5.37 |
Annual Sum or Average | 0.216626E+11 | 0.283179E+10 | ||||||||
Minimum of Months | 0.131886E+09 | 638.35 | 5.60 | 3.25 | 0.187102E+09 | 280.41 | 5.60 | 3.25 | ||
Maximum of Months | 0.413986E+10 | 13194.55 | 20.87 | 15.88 | 0.286345E+09 | 348.42 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542273E+09 | 6365.70 | 20-JAN-13:25 | 6.70 | 4.72 | 0.322224E+09 | 549.49 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.120754E+10 | 8192.29 | 27-FEB-14:30 | 19.15 | 11.80 | 0.313859E+09 | 549.49 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.256273E+10 | 9430.52 | 01-MAR-13:35 | 11.33 | 6.09 | 0.397337E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.336373E+10 | 11540.84 | 27-APR-13:05 | 26.10 | 16.37 | 0.375107E+09 | 549.96 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.425769E+10 | 17239.53 | 14-MAY-13:13 | 22.40 | 12.22 | 0.421297E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.463637E+10 | 11067.11 | 11-JUN-12:43 | 21.70 | 15.34 | 0.428267E+09 | 549.51 | 09-JUN-13:09 | 21.70 | 15.34 |
July | 0.569685E+10 | 18104.68 | 23-JUL-13:32 | 27.23 | 16.89 | 0.401388E+09 | 549.97 | 31-JUL-13:50 | 28.12 | 18.80 |
August | 0.654065E+10 | 19009.01 | 06-AUG-12:53 | 21.70 | 15.31 | 0.450449E+09 | 550.22 | 29-AUG-13:09 | 29.03 | 20.11 |
September | 0.531022E+10 | 20721.02 | 10-SEP-13:22 | 21.40 | 14.38 | 0.391351E+09 | 549.97 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.324913E+10 | 16582.57 | 08-OCT-13:02 | 18.17 | 13.70 | 0.379495E+09 | 549.81 | 04-OCT-13:00 | 18.17 | 13.70 |
November | 0.108467E+10 | 8657.67 | 04-NOV-13:30 | 20.85 | 16.00 | 0.336547E+09 | 549.49 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.767046E+09 | 6365.07 | 05-DEC-12:30 | 10.30 | 6.13 | 0.318177E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.392189E+11 | 0.453550E+10 | ||||||||
Minimum of Months | 0.542273E+09 | 6365.07 | 6.70 | 4.72 | 0.313859E+09 | 549.49 | 7.12 | 4.90 | ||
Maximum of Months | 0.654065E+10 | 20721.02 | 27.23 | 16.89 | 0.450449E+09 | 550.22 | 29.03 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140726E+09 | 775.87 | 05-JAN-15:50 | 6.20 | 4.71 | 0.195701E+09 | 314.09 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.354502E+09 | 3272.78 | 27-FEB-15:30 | 19.70 | 12.30 | 0.187350E+09 | 347.82 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.985035E+09 | 4977.59 | 14-MAR-16:00 | 17.20 | 10.94 | 0.238431E+09 | 347.84 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.175401E+10 | 7914.89 | 26-APR-16:00 | 24.40 | 14.49 | 0.230505E+09 | 347.85 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.284184E+10 | 15476.20 | 14-MAY-16:31 | 22.97 | 11.85 | 0.265654E+09 | 347.85 | 05-MAY-09:20 | 22.97 | 11.85 |
June | 0.326167E+10 | 14806.47 | 18-JUN-16:52 | 17.20 | 12.22 | 0.271088E+09 | 347.86 | 05-JUN-13:00 | 17.20 | 12.22 |
July | 0.429365E+10 | 14699.88 | 23-JUL-16:52 | 26.70 | 15.58 | 0.254411E+09 | 347.85 | 20-JUL-13:20 | 26.70 | 15.58 |
August | 0.412048E+10 | 15627.98 | 06-AUG-16:51 | 23.40 | 15.11 | 0.284963E+09 | 347.87 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.263042E+10 | 14897.10 | 10-SEP-16:02 | 22.20 | 14.43 | 0.245724E+09 | 347.85 | 05-SEP-09:20 | 22.20 | 14.43 |
October | 0.121164E+10 | 6390.00 | 04-OCT-16:00 | 21.10 | 11.40 | 0.229996E+09 | 347.85 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.408010E+09 | 2543.71 | 04-NOV-15:30 | 20.55 | 15.94 | 0.202398E+09 | 347.83 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.174659E+09 | 843.51 | 05-DEC-15:40 | 7.40 | 5.40 | 0.190574E+09 | 334.06 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.221766E+11 | 0.279680E+10 | ||||||||
Minimum of Months | 0.140726E+09 | 775.87 | 6.20 | 4.71 | 0.187350E+09 | 314.09 | 6.10 | 4.61 | ||
Maximum of Months | 0.429365E+10 | 15627.98 | 26.70 | 15.94 | 0.284963E+09 | 347.87 | 26.70 | 16.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182321E+09 | 942.62 | 11-JAN-15:00 | 14.40 | 10.49 | 0.306798E+09 | 424.55 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.443083E+09 | 1128.99 | 28-FEB-15:00 | 13.90 | 10.81 | 0.283851E+09 | 477.00 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.118866E+10 | 1187.71 | 10-MAR-14:40 | 16.30 | 11.68 | 0.361996E+09 | 494.71 | 10-MAR-14:50 | 16.20 | 11.59 |
April | 0.148298E+10 | 2411.14 | 27-APR-16:00 | 27.20 | 16.90 | 0.352400E+09 | 549.50 | 27-APR-13:20 | 27.20 | 16.90 |
May | 0.212975E+10 | 2920.58 | 05-MAY-15:30 | 24.70 | 17.20 | 0.419343E+09 | 549.50 | 05-MAY-09:20 | 24.70 | 17.20 |
June | 0.262258E+10 | 3618.59 | 21-JUN-15:40 | 24.80 | 15.84 | 0.429813E+09 | 549.50 | 09-JUN-13:20 | 24.80 | 15.84 |
July | 0.309407E+10 | 4506.96 | 24-JUL-15:00 | 30.60 | 18.78 | 0.402295E+09 | 549.50 | 20-JUL-13:20 | 30.60 | 18.78 |
August | 0.330200E+10 | 4157.17 | 09-AUG-15:30 | 28.70 | 18.83 | 0.451306E+09 | 549.52 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.217880E+10 | 3120.27 | 12-SEP-14:40 | 24.40 | 16.65 | 0.391939E+09 | 549.50 | 05-SEP-09:20 | 24.40 | 16.65 |
October | 0.156066E+10 | 1916.88 | 04-OCT-15:30 | 21.40 | 11.45 | 0.372785E+09 | 549.49 | 02-OCT-13:20 | 21.40 | 11.45 |
November | 0.934123E+09 | 1209.88 | 06-NOV-12:00 | 13.90 | 10.05 | 0.327096E+09 | 497.23 | 07-NOV-14:09 | 12.80 | 10.81 |
December | 0.363195E+09 | 939.99 | 05-DEC-14:40 | 10.20 | 6.81 | 0.297934E+09 | 422.55 | 05-DEC-14:20 | 10.20 | 6.81 |
Annual Sum or Average | 0.194822E+11 | 0.439756E+10 | ||||||||
Minimum of Months | 0.182321E+09 | 939.99 | 10.20 | 6.81 | 0.283851E+09 | 422.55 | 10.20 | 6.81 | ||
Maximum of Months | 0.330200E+10 | 4506.96 | 30.60 | 18.83 | 0.451306E+09 | 549.52 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168716E+09 | 626.55 | 20-JAN-10:45 | 5.32 | 3.17 | 0.194880E+09 | 277.21 | 20-JAN-10:50 | 5.32 | 3.17 |
February | 0.386625E+09 | 754.42 | 27-FEB-15:40 | 19.60 | 12.34 | 0.186344E+09 | 314.31 | 08-FEB-10:39 | 19.60 | 12.34 |
March | 0.942990E+09 | 1391.73 | 25-MAR-08:40 | 5.93 | 0.72 | 0.247440E+09 | 347.88 | 02-MAR-10:20 | 5.93 | 0.72 |
April | 0.150384E+10 | 4776.40 | 27-APR-09:20 | 18.17 | 12.47 | 0.242052E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.217111E+10 | 8210.36 | 15-MAY-06:02 | 11.97 | 9.44 | 0.271317E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.306525E+10 | 8155.57 | 19-JUN-06:02 | 11.88 | 9.64 | 0.274827E+09 | 347.88 | 09-JUN-13:09 | 11.88 | 9.64 |
July | 0.336621E+10 | 10751.31 | 23-JUL-08:42 | 18.72 | 13.76 | 0.255992E+09 | 348.14 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.384588E+10 | 9168.62 | 13-AUG-10:53 | 24.90 | 17.61 | 0.287324E+09 | 348.17 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.238464E+10 | 6693.08 | 10-SEP-07:43 | 14.03 | 12.57 | 0.252005E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.133632E+10 | 3927.53 | 04-OCT-08:30 | 14.75 | 10.13 | 0.246914E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.644723E+09 | 846.80 | 02-NOV-10:40 | 12.43 | 10.47 | 0.212379E+09 | 331.93 | 02-NOV-10:50 | 12.62 | 10.55 |
December | 0.310654E+09 | 720.14 | 05-DEC-10:30 | 7.50 | 5.28 | 0.191929E+09 | 303.89 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.201270E+11 | 0.286340E+10 | ||||||||
Minimum of Months | 0.168716E+09 | 626.55 | 5.32 | 0.72 | 0.186344E+09 | 277.21 | 5.32 | 0.72 | ||
Maximum of Months | 0.384588E+10 | 10751.31 | 24.90 | 17.61 | 0.287324E+09 | 348.17 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205523E+09 | 1348.69 | 20-JAN-13:50 | 6.70 | 4.72 | 0.303272E+09 | 540.32 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.601101E+09 | 4814.67 | 27-FEB-13:20 | 17.97 | 11.33 | 0.295226E+09 | 549.51 | 07-FEB-14:09 | 17.97 | 11.33 |
March | 0.138217E+10 | 5790.81 | 02-MAR-13:20 | 12.57 | 7.60 | 0.372106E+09 | 549.51 | 24-MAR-13:09 | 8.48 | 2.65 |
April | 0.195179E+10 | 8753.57 | 27-APR-13:30 | 26.10 | 16.55 | 0.354614E+09 | 549.51 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.251576E+10 | 9778.01 | 14-MAY-13:53 | 22.80 | 12.27 | 0.403288E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.293654E+10 | 6702.40 | 28-JUN-13:30 | 24.70 | 15.69 | 0.415398E+09 | 549.52 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.423859E+10 | 11347.35 | 23-JUL-14:02 | 27.70 | 16.80 | 0.396028E+09 | 549.58 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.559392E+10 | 15196.89 | 13-AUG-14:53 | 28.10 | 19.13 | 0.445688E+09 | 549.85 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.415626E+10 | 15824.94 | 10-SEP-12:23 | 20.00 | 13.75 | 0.384799E+09 | 549.91 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.248446E+10 | 10687.45 | 04-OCT-13:30 | 20.85 | 11.31 | 0.375057E+09 | 549.67 | 03-OCT-13:00 | 20.85 | 11.31 |
November | 0.827607E+09 | 6175.82 | 04-NOV-13:40 | 20.93 | 15.98 | 0.322753E+09 | 549.50 | 15-NOV-14:09 | 9.82 | 6.80 |
December | 0.434375E+09 | 3563.68 | 05-DEC-12:00 | 10.00 | 6.07 | 0.303335E+09 | 549.51 | 05-DEC-14:09 | 10.50 | 6.49 |
Annual Sum or Average | 0.273281E+11 | 0.437156E+10 | ||||||||
Minimum of Months | 0.205523E+09 | 1348.69 | 6.70 | 4.72 | 0.295226E+09 | 540.32 | 6.78 | 2.65 | ||
Maximum of Months | 0.559392E+10 | 15824.94 | 28.10 | 19.13 | 0.445688E+09 | 549.91 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167551E+09 | 711.65 | 20-JAN-15:50 | 5.87 | 4.23 | 0.195664E+09 | 294.30 | 20-JAN-15:00 | 5.60 | 4.08 |
February | 0.384326E+09 | 1801.80 | 27-FEB-15:40 | 19.60 | 12.34 | 0.186173E+09 | 347.82 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.947152E+09 | 2746.92 | 02-MAR-16:30 | 13.05 | 8.47 | 0.239699E+09 | 347.83 | 02-MAR-14:50 | 13.05 | 8.47 |
April | 0.142110E+10 | 5516.48 | 26-APR-17:30 | 23.60 | 13.73 | 0.233258E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.228577E+10 | 12080.17 | 14-MAY-16:31 | 22.97 | 11.85 | 0.270168E+09 | 347.85 | 05-MAY-09:20 | 22.97 | 11.85 |
June | 0.274537E+10 | 7534.74 | 18-JUN-17:22 | 16.95 | 12.25 | 0.273621E+09 | 347.85 | 20-JUN-09:20 | 18.87 | 13.67 |
July | 0.378624E+10 | 12752.54 | 23-JUL-17:21 | 26.40 | 15.75 | 0.256201E+09 | 347.85 | 03-JUL-09:20 | 26.40 | 15.75 |
August | 0.376001E+10 | 9513.47 | 12-AUG-17:05 | 24.38 | 16.49 | 0.287106E+09 | 347.88 | 09-AUG-09:00 | 24.38 | 16.49 |
September | 0.246528E+10 | 8394.40 | 10-SEP-15:02 | 22.70 | 14.34 | 0.251902E+09 | 347.86 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.132047E+10 | 5615.02 | 04-OCT-16:00 | 21.10 | 11.40 | 0.242942E+09 | 347.85 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.636497E+09 | 2023.31 | 04-NOV-15:30 | 20.55 | 15.94 | 0.210840E+09 | 346.23 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.292517E+09 | 813.97 | 05-DEC-15:30 | 8.05 | 5.82 | 0.192391E+09 | 324.19 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.202123E+11 | 0.283996E+10 | ||||||||
Minimum of Months | 0.167551E+09 | 711.65 | 5.87 | 4.23 | 0.186173E+09 | 294.30 | 5.60 | 4.08 | ||
Maximum of Months | 0.378624E+10 | 12752.54 | 26.40 | 16.49 | 0.287106E+09 | 347.88 | 26.40 | 16.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295926E+09 | 1022.17 | 11-JAN-16:10 | 14.03 | 10.30 | 0.307928E+09 | 445.53 | 11-JAN-14:00 | 14.03 | 10.30 |
February | 0.632440E+09 | 1265.23 | 28-FEB-15:00 | 13.90 | 10.81 | 0.290514E+09 | 517.00 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.143846E+10 | 1324.52 | 10-MAR-14:50 | 16.20 | 11.59 | 0.382230E+09 | 536.44 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.181537E+10 | 3884.11 | 27-APR-15:20 | 27.20 | 17.16 | 0.371964E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.280008E+10 | 4155.78 | 15-MAY-14:30 | 23.30 | 13.06 | 0.427077E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.341078E+10 | 4541.54 | 21-JUN-15:30 | 24.70 | 15.68 | 0.432423E+09 | 549.50 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.385295E+10 | 6741.03 | 24-JUL-06:03 | 17.48 | 14.11 | 0.403342E+09 | 550.37 | 24-JUL-13:20 | 28.67 | 18.27 |
August | 0.397786E+10 | 6502.62 | 14-AUG-06:02 | 15.47 | 13.75 | 0.452344E+09 | 549.53 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.253714E+10 | 3924.57 | 12-SEP-14:40 | 24.40 | 16.65 | 0.394553E+09 | 549.50 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.163047E+10 | 2552.49 | 04-OCT-15:20 | 21.50 | 11.47 | 0.376228E+09 | 549.49 | 05-OCT-13:20 | 16.10 | 10.57 |
November | 0.893330E+09 | 1233.30 | 02-NOV-14:10 | 14.22 | 11.35 | 0.326772E+09 | 507.18 | 02-NOV-13:00 | 14.22 | 11.35 |
December | 0.409709E+09 | 987.95 | 05-DEC-14:50 | 10.10 | 6.91 | 0.299370E+09 | 436.20 | 05-DEC-14:30 | 10.10 | 6.91 |
Annual Sum or Average | 0.236945E+11 | 0.446474E+10 | ||||||||
Minimum of Months | 0.295926E+09 | 987.95 | 10.10 | 6.91 | 0.290514E+09 | 436.20 | 10.10 | 6.91 | ||
Maximum of Months | 0.397786E+10 | 6741.03 | 27.20 | 17.16 | 0.452344E+09 | 550.37 | 28.67 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184586E+09 | 710.12 | 20-JAN-11:10 | 5.60 | 3.32 | 0.144545E+09 | 299.62 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.373208E+09 | 1636.17 | 08-FEB-11:05 | 4.08 | 2.58 | 0.141844E+09 | 351.56 | 08-FEB-11:09 | 4.08 | 2.58 |
March | 0.961037E+09 | 5434.47 | 01-MAR-13:01 | 10.78 | 5.75 | 0.189306E+09 | 356.46 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.178499E+10 | 7176.80 | 27-APR-10:05 | 19.27 | 13.13 | 0.181241E+09 | 356.46 | 20-APR-10:09 | 19.27 | 13.13 |
May | 0.256936E+10 | 12050.00 | 14-MAY-08:43 | 16.32 | 11.34 | 0.201400E+09 | 356.47 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.343270E+10 | 11837.18 | 25-JUN-07:42 | 15.32 | 11.39 | 0.203424E+09 | 356.46 | 07-JUN-10:09 | 15.32 | 11.39 |
July | 0.367772E+10 | 13959.47 | 30-JUL-08:52 | 20.60 | 15.79 | 0.190255E+09 | 356.46 | 07-JUL-12:09 | 20.60 | 15.79 |
August | 0.399354E+10 | 12846.46 | 13-AUG-08:52 | 20.90 | 15.90 | 0.212662E+09 | 356.51 | 09-AUG-10:09 | 20.90 | 15.90 |
September | 0.247358E+10 | 10636.11 | 10-SEP-10:13 | 17.77 | 13.72 | 0.186469E+09 | 356.46 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.126333E+10 | 5764.86 | 04-OCT-10:05 | 17.48 | 10.97 | 0.181564E+09 | 356.46 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.481598E+09 | 2383.20 | 04-NOV-10:05 | 16.38 | 13.96 | 0.156538E+09 | 356.45 | 02-NOV-10:09 | 16.38 | 13.96 |
December | 0.246430E+09 | 771.91 | 05-DEC-11:10 | 8.58 | 5.53 | 0.142525E+09 | 319.92 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.214421E+11 | 0.213177E+10 | ||||||||
Minimum of Months | 0.184586E+09 | 710.12 | 4.08 | 2.58 | 0.141844E+09 | 299.62 | 4.08 | 2.58 | ||
Maximum of Months | 0.399354E+10 | 13959.47 | 20.90 | 15.90 | 0.212662E+09 | 356.51 | 20.90 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.744572E+09 | 6792.19 | 20-JAN-13:20 | 6.70 | 4.72 | 0.328749E+09 | 549.49 | 20-JAN-14:39 | 7.03 | 4.87 |
February | 0.153534E+10 | 8234.89 | 27-FEB-14:10 | 18.58 | 11.55 | 0.321149E+09 | 549.50 | 08-FEB-10:09 | 18.58 | 11.55 |
March | 0.295433E+10 | 9732.44 | 01-MAR-13:25 | 11.15 | 5.98 | 0.411428E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.358605E+10 | 11081.34 | 27-APR-13:05 | 26.10 | 16.37 | 0.384674E+09 | 550.62 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.436658E+10 | 11597.85 | 14-MAY-12:03 | 21.28 | 12.49 | 0.428807E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.467911E+10 | 10122.19 | 11-JUN-12:33 | 21.70 | 15.39 | 0.432434E+09 | 549.52 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.567781E+10 | 18330.68 | 30-JUL-12:12 | 26.10 | 17.39 | 0.403768E+09 | 550.86 | 31-JUL-13:20 | 27.57 | 18.47 |
August | 0.654836E+10 | 17841.71 | 06-AUG-13:02 | 21.85 | 15.38 | 0.453112E+09 | 550.89 | 14-AUG-13:20 | 25.93 | 17.49 |
September | 0.551041E+10 | 17917.38 | 10-SEP-12:52 | 20.60 | 14.10 | 0.398153E+09 | 550.64 | 12-SEP-13:20 | 23.33 | 16.02 |
October | 0.368487E+10 | 17814.87 | 08-OCT-13:02 | 18.17 | 13.70 | 0.393707E+09 | 550.15 | 04-OCT-13:20 | 18.17 | 13.70 |
November | 0.146372E+10 | 8829.72 | 04-NOV-13:30 | 20.85 | 16.00 | 0.351348E+09 | 549.49 | 24-NOV-10:39 | 5.93 | 4.25 |
December | 0.108221E+10 | 7213.77 | 05-DEC-12:30 | 10.30 | 6.13 | 0.326956E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.418334E+11 | 0.463429E+10 | ||||||||
Minimum of Months | 0.744572E+09 | 6792.19 | 6.70 | 4.72 | 0.321149E+09 | 549.49 | 5.93 | 4.25 | ||
Maximum of Months | 0.654836E+10 | 18330.68 | 26.10 | 17.39 | 0.453112E+09 | 550.89 | 27.57 | 18.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239756E+09 | 800.17 | 05-JAN-15:50 | 6.20 | 4.71 | 0.197630E+09 | 320.20 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.510803E+09 | 3258.53 | 27-FEB-15:30 | 19.70 | 12.30 | 0.190908E+09 | 347.83 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.117927E+10 | 4823.12 | 14-MAR-16:00 | 17.20 | 10.94 | 0.248240E+09 | 347.84 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.185231E+10 | 7679.73 | 26-APR-16:00 | 24.40 | 14.49 | 0.238234E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.289706E+10 | 14537.00 | 07-MAY-16:51 | 21.70 | 16.17 | 0.271030E+09 | 347.85 | 05-MAY-09:20 | 21.70 | 16.17 |
June | 0.328580E+10 | 10952.16 | 18-JUN-18:23 | 16.40 | 12.43 | 0.273798E+09 | 347.86 | 05-JUN-13:00 | 16.40 | 12.43 |
July | 0.427717E+10 | 15042.21 | 23-JUL-17:21 | 26.40 | 15.75 | 0.255797E+09 | 347.85 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.412225E+10 | 13264.14 | 06-AUG-17:02 | 23.47 | 15.14 | 0.286776E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.274539E+10 | 12595.02 | 10-SEP-16:12 | 22.20 | 14.38 | 0.251027E+09 | 347.86 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.140508E+10 | 6385.12 | 04-OCT-16:00 | 21.10 | 11.40 | 0.241380E+09 | 347.85 | 25-OCT-13:20 | 13.50 | 10.37 |
November | 0.612558E+09 | 2647.16 | 04-NOV-15:30 | 20.55 | 15.94 | 0.210364E+09 | 347.84 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.320042E+09 | 1054.77 | 05-DEC-15:30 | 8.05 | 5.82 | 0.194027E+09 | 341.31 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.234475E+11 | 0.285921E+10 | ||||||||
Minimum of Months | 0.239756E+09 | 800.17 | 6.20 | 4.71 | 0.190908E+09 | 320.20 | 6.10 | 4.61 | ||
Maximum of Months | 0.427717E+10 | 15042.21 | 26.40 | 16.17 | 0.286776E+09 | 347.88 | 23.80 | 17.16 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383149E+09 | 18524.06 | 02-JAN-06:11 | 6.10 |
February | 1074811.64 | 12539.47 | 21-FEB-07:01 | 1.60 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 861947.75 | 13857.72 | 26-DEC-07:01 | -1.6 |
Annual Sum or Average | 0.385085E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.6 | |
Maximum of Months | 0.383149E+09 | 18524.06 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295604E+10 | 11337.71 | 09-JAN-06:12 | -1.3 |
February | 0.181300E+10 | 10528.32 | 21-FEB-06:12 | 1.70 |
March | 0.112711E+10 | 5887.58 | 06-MAR-07:03 | 6.70 |
April | 0.626009E+09 | 3514.40 | 19-APR-05:03 | 1.78 |
May | 0.386039E+09 | 3699.16 | 14-MAY-07:17 | 12.93 |
June | 0.228406E+09 | 2883.92 | 19-JUN-06:02 | 11.88 |
July | 0.161686E+09 | 3012.85 | 30-JUL-07:42 | 18.03 |
August | 0.196702E+09 | 3880.13 | 06-AUG-07:32 | 13.47 |
September | 0.378556E+09 | 3803.44 | 10-SEP-08:62 | 14.68 |
October | 0.821418E+09 | 2978.51 | 30-OCT-06:03 | 7.20 |
November | 0.160656E+10 | 8074.86 | 24-NOV-07:01 | 1.20 |
December | 0.250966E+10 | 10477.21 | 26-DEC-06:04 | -0.8 |
Annual Sum or Average | 0.128112E+11 | |||
Minimum of Months | 0.161686E+09 | 2883.92 | -1.3 | |
Maximum of Months | 0.295604E+10 | 11337.71 | 18.03 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169158E+10 | 8637.42 | 02-JAN-07:02 | 6.20 |
February | 0.106757E+10 | 5234.38 | 21-FEB-07:03 | 1.60 |
March | 0.798904E+09 | 2556.77 | 14-MAR-12:02 | 13.48 |
April | 0.353800E+09 | 2878.81 | 02-APR-13:33 | 18.90 |
May | 74521796.81 | 3140.72 | 21-MAY-15:43 | 16.10 |
June | 25722157.58 | 2714.67 | 25-JUN-07:42 | 15.32 |
July | 28630037.76 | 4243.61 | 30-JUL-10:53 | 23.90 |
August | 21692446.89 | 4277.15 | 06-AUG-15:02 | 23.72 |
September | 56291935.66 | 5033.08 | 10-SEP-10:13 | 17.77 |
October | 0.416758E+09 | 4610.17 | 08-OCT-13:02 | 18.17 |
November | 0.923747E+09 | 2472.69 | 24-NOV-11:10 | 6.20 |
December | 0.130835E+10 | 6346.39 | 26-DEC-07:03 | -1.6 |
Annual Sum or Average | 0.676757E+10 | |||
Minimum of Months | 21692446.89 | 2472.69 | -1.6 | |
Maximum of Months | 0.169158E+10 | 8637.42 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135338E+10 | 7777.24 | 02-JAN-07:02 | 6.20 |
February | 0.728846E+09 | 2566.15 | 21-FEB-08:08 | 1.28 |
March | 0.398334E+09 | 1798.59 | 24-MAR-07:09 | 2.48 |
April | 0.103216E+09 | 1709.12 | 18-APR-07:09 | 3.98 |
May | 12466764.89 | 2055.04 | 14-MAY-14:32 | 23.13 |
June | 12921212.42 | 1510.45 | 18-JUN-15:30 | 18.60 |
July | 16420918.28 | 2005.19 | 23-JUL-15:21 | 27.50 |
August | 12047604.09 | 2409.00 | 13-AUG-14:53 | 28.10 |
September | 12840979.44 | 2761.72 | 10-SEP-15:02 | 22.70 |
October | 0.153363E+09 | 1686.68 | 08-OCT-11:15 | 15.93 |
November | 0.585068E+09 | 1644.94 | 27-NOV-08:40 | 10.97 |
December | 0.937764E+09 | 2931.11 | 26-DEC-08:20 | -1.1 |
Annual Sum or Average | 0.432667E+10 | |||
Minimum of Months | 12047604.09 | 1510.45 | -1.1 | |
Maximum of Months | 0.135338E+10 | 7777.24 | 28.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612356E+09 | 20080.02 | 02-JAN-06:11 | 6.10 |
February | 60582745.98 | 16993.21 | 21-FEB-06:01 | 1.70 |
March | 2435355.44 | 16235.70 | 06-MAR-07:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 12060598.62 | 15439.74 | 27-NOV-07:03 | 11.70 |
December | 0.103157E+09 | 17491.40 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.790592E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.612356E+09 | 20080.02 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148589E+10 | 29159.85 | 02-JAN-06:11 | 6.10 |
February | 0.509207E+09 | 27460.98 | 21-FEB-06:01 | 1.70 |
March | 68140043.89 | 24938.16 | 06-MAR-06:11 | 6.70 |
April | 1299859.19 | 7058.24 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 10361938.46 | 23143.06 | 23-OCT-06:03 | 10.40 |
November | 0.244741E+09 | 25432.72 | 27-NOV-06:11 | 11.70 |
December | 0.787706E+09 | 27795.34 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.310734E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.148589E+10 | 29159.85 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226175E+10 | 8430.45 | 17-JAN-05:01 | 1.60 |
February | 0.111109E+10 | 8404.24 | 21-FEB-06:01 | 1.70 |
March | 0.265870E+09 | 7798.86 | 06-MAR-06:11 | 6.70 |
April | 55780637.08 | 7052.65 | 18-APR-05:12 | 3.30 |
May | 1290427.25 | 4863.49 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 394630.54 | 693.21 | 28-SEP-06:05 | 8.40 |
October | 75492045.28 | 7108.47 | 30-OCT-05:12 | 7.20 |
November | 0.719666E+09 | 7963.35 | 24-NOV-06:11 | 1.83 |
December | 0.167911E+10 | 8526.62 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.617045E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.226175E+10 | 8526.62 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137018E+10 | 9112.76 | 17-JAN-05:01 | 1.60 |
February | 0.622694E+09 | 8977.53 | 21-FEB-06:01 | 1.70 |
March | 0.134637E+09 | 8302.94 | 06-MAR-06:11 | 6.70 |
April | 24901259.68 | 6377.09 | 18-APR-05:12 | 3.30 |
May | 1029553.96 | 3422.27 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 258707.43 | 517.78 | 28-SEP-06:05 | 8.40 |
October | 47848600.13 | 6362.99 | 30-OCT-05:12 | 7.20 |
November | 0.436589E+09 | 8546.96 | 24-NOV-06:11 | 1.83 |
December | 0.101913E+10 | 9229.65 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.365727E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.137018E+10 | 9229.65 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170978E+10 | 13836.15 | 17-JAN-05:01 | 1.60 |
February | 0.741158E+09 | 13595.00 | 21-FEB-06:01 | 1.70 |
March | 0.200023E+09 | 12593.76 | 06-MAR-06:11 | 6.70 |
April | 49868639.84 | 10797.85 | 19-APR-06:02 | 2.48 |
May | 1360058.52 | 5097.25 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 130078.50 | 256.54 | 27-SEP-06:05 | 8.40 |
October | 56376255.32 | 9542.37 | 16-OCT-06:03 | 6.60 |
November | 0.539660E+09 | 12919.54 | 24-NOV-06:11 | 1.83 |
December | 0.128501E+10 | 13971.97 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.458337E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.170978E+10 | 13971.97 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141793E+10 | 9064.50 | 17-JAN-05:01 | 1.60 |
February | 0.661840E+09 | 8904.29 | 21-FEB-06:01 | 1.70 |
March | 0.170394E+09 | 8190.17 | 06-MAR-06:11 | 6.70 |
April | 37912846.58 | 7079.48 | 19-APR-06:02 | 2.48 |
May | 952985.56 | 3497.05 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 67839.07 | 226.13 | 28-SEP-06:05 | 8.40 |
October | 49258149.15 | 6150.19 | 16-OCT-06:03 | 6.60 |
November | 0.462524E+09 | 8435.40 | 24-NOV-06:11 | 1.83 |
December | 0.105542E+10 | 9191.76 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.385630E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.141793E+10 | 9191.76 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155101E+10 | 6621.64 | 02-JAN-06:11 | 6.10 |
February | 0.569859E+09 | 6106.45 | 21-FEB-05:53 | 1.70 |
March | 75275155.91 | 5686.17 | 06-MAR-06:11 | 6.70 |
April | 9116397.52 | 5326.70 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2271671.15 | 5176.16 | 30-OCT-06:03 | 7.20 |
November | 0.128123E+09 | 5637.21 | 24-NOV-06:11 | 1.83 |
December | 0.672000E+09 | 6142.06 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.300765E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.155101E+10 | 6621.64 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.933524E+09 | 6637.37 | 02-JAN-06:11 | 6.10 |
February | 0.275578E+09 | 5878.95 | 21-FEB-06:01 | 1.70 |
March | 28210690.33 | 5388.65 | 06-MAR-06:11 | 6.70 |
April | 2868862.04 | 4594.69 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 787511.49 | 1887.68 | 31-OCT-06:03 | 10.18 |
November | 77140173.57 | 5467.45 | 30-NOV-06:11 | 5.60 |
December | 0.422772E+09 | 6185.41 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.174088E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.933524E+09 | 6637.37 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365448E+10 | 10305.15 | 06-JAN-08:00 | -2.8 |
February | 0.206924E+10 | 9683.45 | 21-FEB-08:00 | 1.10 |
March | 0.144688E+10 | 9263.16 | 01-MAR-07:10 | -0.1 |
April | 0.811016E+09 | 8848.12 | 19-APR-06:10 | 2.48 |
May | 0.498590E+09 | 8059.83 | 18-MAY-06:20 | 5.77 |
June | 0.218558E+09 | 7865.62 | 01-JUN-06:05 | 10.18 |
July | 34360043.17 | 4641.78 | 06-JUL-06:07 | 12.80 |
August | 51762558.01 | 6692.00 | 03-AUG-06:06 | 11.82 |
September | 0.199652E+09 | 7945.82 | 27-SEP-07:00 | 8.90 |
October | 0.723011E+09 | 7964.95 | 24-OCT-06:10 | 6.28 |
November | 0.182225E+10 | 9576.19 | 24-NOV-07:10 | 1.20 |
December | 0.274886E+10 | 10369.93 | 26-DEC-08:00 | -1.1 |
Annual Sum or Average | 0.142787E+11 | |||
Minimum of Months | 34360043.17 | 4641.78 | -2.8 | |
Maximum of Months | 0.365448E+10 | 10369.93 | 12.80 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.943647E+09 | 6572.93 | 02-JAN-06:11 | 6.10 |
February | 0.283208E+09 | 5736.10 | 21-FEB-06:01 | 1.70 |
March | 37844285.38 | 5297.91 | 08-MAR-07:03 | 11.10 |
April | 4031229.24 | 5080.50 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 418852.39 | 893.02 | 31-OCT-06:03 | 10.18 |
November | 78897264.40 | 5481.62 | 28-NOV-06:11 | 4.23 |
December | 0.411428E+09 | 6132.30 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.175948E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.943647E+09 | 6572.93 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122532E+10 | 7338.08 | 02-JAN-06:11 | 6.10 |
February | 0.401516E+09 | 6891.62 | 21-FEB-05:53 | 1.70 |
March | 46333342.06 | 6372.43 | 06-MAR-06:11 | 6.70 |
April | 4857186.93 | 5849.17 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 5853850.47 | 5904.51 | 30-OCT-06:03 | 7.20 |
November | 0.195179E+09 | 6481.37 | 24-NOV-06:11 | 1.83 |
December | 0.670156E+09 | 7086.93 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.254921E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.122532E+10 | 7338.08 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.750449E+09 | 7012.96 | 02-JAN-06:11 | 6.10 |
February | 0.231640E+09 | 6374.94 | 21-FEB-05:53 | 1.70 |
March | 23498393.63 | 5911.78 | 06-MAR-06:12 | 6.70 |
April | 2358841.70 | 4400.31 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 4169284.80 | 4739.45 | 30-OCT-06:03 | 7.20 |
November | 0.127301E+09 | 5926.55 | 14-NOV-06:11 | 5.60 |
December | 0.435078E+09 | 6742.45 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.157450E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.750449E+09 | 7012.96 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.890721E+09 | 10599.83 | 02-JAN-06:11 | 6.10 |
February | 0.264491E+09 | 9454.02 | 21-FEB-06:01 | 1.70 |
March | 33149301.92 | 8678.11 | 06-MAR-06:11 | 6.70 |
April | 4124576.41 | 6361.66 | 18-APR-06:03 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3210863.13 | 4703.47 | 23-OCT-06:03 | 10.40 |
November | 0.138635E+09 | 8914.88 | 24-NOV-06:11 | 1.83 |
December | 0.517197E+09 | 10064.30 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.185153E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.890721E+09 | 10599.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761656E+09 | 6966.85 | 02-JAN-06:11 | 6.10 |
February | 0.240582E+09 | 6122.51 | 21-FEB-06:01 | 1.70 |
March | 30695958.39 | 5804.27 | 06-MAR-06:12 | 6.70 |
April | 3626400.21 | 5603.02 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3488153.03 | 4104.67 | 30-OCT-06:03 | 7.20 |
November | 0.130196E+09 | 5903.62 | 14-NOV-06:11 | 5.60 |
December | 0.429480E+09 | 6685.53 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.159973E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.761656E+09 | 6966.85 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.150159E+11 | 12758.28 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.135921E+11 | 12758.28 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.156433E+11 | 12758.28 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.144886E+11 | 12758.28 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.153296E+11 | 12758.28 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.150619E+11 | 12758.28 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.147541E+11 | 12758.28 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.156433E+11 | 12758.28 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.144842E+11 | 12758.28 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.150181E+11 | 12758.28 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.147007E+11 | 12758.28 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.147519E+11 | 12758.28 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.178484E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.135921E+11 | 12758.28 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.156433E+11 | 12758.28 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332047E+10 | 3488.70 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.301195E+10 | 3488.70 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.357877E+10 | 3488.70 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.319691E+10 | 3488.70 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.344962E+10 | 3488.70 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.343288E+10 | 3488.70 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.321365E+10 | 3488.70 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.357877E+10 | 3488.70 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.319691E+10 | 3488.70 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.332047E+10 | 3488.70 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.328140E+10 | 3488.70 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.321365E+10 | 3488.70 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.397954E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.301195E+10 | 3488.70 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.357877E+10 | 3488.70 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489237E+09 | 735.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.400063E+09 | 668.03 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.436247E+09 | 587.25 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370257E+09 | 471.46 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.388533E+09 | 382.52 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379498E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.357720E+09 | 409.74 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.403172E+09 | 405.84 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.382346E+09 | 591.74 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.427662E+09 | 726.22 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.472094E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.490688E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.499752E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.357720E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.490688E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300179E+09 | 465.60 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249773E+09 | 427.38 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274616E+09 | 355.50 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234471E+09 | 250.52 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247223E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241815E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227894E+09 | 240.19 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256560E+09 | 249.67 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240332E+09 | 359.41 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266844E+09 | 458.26 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.291999E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299474E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.313118E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227894E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300179E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462988E+09 | 735.45 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.385787E+09 | 652.24 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.431019E+09 | 580.54 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370433E+09 | 412.66 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.390385E+09 | 383.27 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381834E+09 | 375.11 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.361159E+09 | 406.11 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405725E+09 | 404.97 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.380090E+09 | 586.70 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.416659E+09 | 724.47 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.451318E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.459630E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.489703E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.361159E+09 | 375.11 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.462988E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300106E+09 | 465.57 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.247464E+09 | 411.77 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274487E+09 | 377.50 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234373E+09 | 320.97 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246292E+09 | 249.34 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240583E+09 | 245.05 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227802E+09 | 331.10 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255743E+09 | 327.17 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241861E+09 | 379.66 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.267118E+09 | 459.85 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.290920E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299203E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.312595E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227802E+09 | 245.05 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300106E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.486307E+09 | 735.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.398204E+09 | 665.37 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.434899E+09 | 581.53 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.369745E+09 | 412.20 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.388234E+09 | 379.16 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379296E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.357436E+09 | 407.75 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.402764E+09 | 403.59 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.381570E+09 | 586.24 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.425734E+09 | 725.87 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.469577E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.487815E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.498158E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.357436E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.487815E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.299115E+09 | 465.60 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249043E+09 | 426.19 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274101E+09 | 351.84 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234222E+09 | 248.89 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247002E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241615E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227672E+09 | 237.73 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256260E+09 | 247.97 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.239922E+09 | 355.90 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266123E+09 | 458.01 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.291105E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.298317E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.312450E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227672E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.299115E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.461325E+09 | 735.45 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.384872E+09 | 648.34 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.430254E+09 | 574.50 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370019E+09 | 410.72 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.390000E+09 | 379.95 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381455E+09 | 371.42 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.360762E+09 | 403.92 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405269E+09 | 402.67 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.379600E+09 | 580.95 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.415745E+09 | 724.03 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.450051E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.458102E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.488745E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.360762E+09 | 371.42 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.461325E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.298981E+09 | 465.57 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.246693E+09 | 410.11 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.273893E+09 | 374.81 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234031E+09 | 316.58 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246090E+09 | 247.76 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240318E+09 | 243.30 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227441E+09 | 327.21 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255448E+09 | 323.01 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241321E+09 | 377.04 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266356E+09 | 459.67 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.289839E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.297909E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.311832E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227441E+09 | 243.30 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.298981E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489234E+09 | 735.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.400061E+09 | 668.03 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.436245E+09 | 587.23 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.370256E+09 | 471.44 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.388533E+09 | 382.51 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.379498E+09 | 350.81 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.357720E+09 | 409.73 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.403172E+09 | 405.83 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.382345E+09 | 591.72 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.427660E+09 | 726.22 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.472091E+09 | 735.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.490685E+09 | 735.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.499750E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.357720E+09 | 350.81 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.490685E+09 | 735.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300178E+09 | 465.60 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.249773E+09 | 427.37 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274615E+09 | 355.50 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234470E+09 | 250.52 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.247222E+09 | 222.09 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.241815E+09 | 222.09 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227894E+09 | 240.18 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.256559E+09 | 249.66 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.240332E+09 | 359.40 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.266843E+09 | 458.26 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.291997E+09 | 465.60 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299473E+09 | 465.60 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.313117E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.227894E+09 | 222.09 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300178E+09 | 465.60 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.462986E+09 | 735.45 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.385786E+09 | 652.23 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.431018E+09 | 580.53 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.370433E+09 | 412.66 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.390385E+09 | 383.26 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.381834E+09 | 375.10 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.361159E+09 | 406.11 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.405724E+09 | 404.96 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.380090E+09 | 586.68 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.416658E+09 | 724.47 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.451316E+09 | 735.45 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.459629E+09 | 735.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.489702E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.361159E+09 | 375.10 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.462986E+09 | 735.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.300104E+09 | 465.57 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.247463E+09 | 411.76 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.274486E+09 | 377.49 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.234373E+09 | 320.96 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.246292E+09 | 249.33 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.240582E+09 | 245.05 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.227802E+09 | 331.09 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.255743E+09 | 327.16 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.241861E+09 | 379.65 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.267117E+09 | 459.85 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.290898E+09 | 465.57 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.299201E+09 | 465.57 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.312592E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.227802E+09 | 245.05 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.300104E+09 | 465.57 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.150159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.144886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.153296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.150619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.147541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.144842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.150181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.147007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.147519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.178484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.135921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.156433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.332047E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.319691E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.344962E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.343288E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.321365E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.319691E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.332047E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.328140E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.321365E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.397954E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.301195E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.357877E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.489237E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810668E+09 |
February | 0.901968E+09 | 0.400063E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728569E+09 |
March | 0.107774E+10 | 0.436247E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722901E+09 |
April | 0.956342E+09 | 0.370257E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1696521.34 | 0.711133E+09 |
May | 0.103597E+10 | 0.388533E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42236.52 | 0.583408E+09 |
June | 0.103308E+10 | 0.379498E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466741.90 | 0.488717E+09 |
July | 0.959235E+09 | 0.357720E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6408455.28 | 0.410227E+09 |
August | 0.107774E+10 | 0.403172E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10491463.96 | 0.332938E+09 |
September | 0.956342E+09 | 0.382346E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43169.18 | 0.269059E+09 |
October | 0.994195E+09 | 0.427662E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582644E+09 |
November | 0.984487E+09 | 0.472094E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636013E+09 |
December | 0.959235E+09 | 0.490688E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689562E+09 |
Annual Sum or Average | 0.119305E+11 | 0.499752E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19148588.17 | 0.696584E+10 |
Minimum of Months | 0.901968E+09 | 0.357720E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269059E+09 |
Maximum of Months | 0.107774E+10 | 0.490688E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10491463.96 | 0.810668E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.300179E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540235E+09 |
February | 0.571020E+09 | 0.249773E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492856E+09 |
March | 0.682301E+09 | 0.274616E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490052E+09 |
April | 0.605444E+09 | 0.234471E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 895249.68 | 0.485422E+09 |
May | 0.655854E+09 | 0.247223E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28161.26 | 0.397055E+09 |
June | 0.654023E+09 | 0.241815E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311170.84 | 0.334388E+09 |
July | 0.607275E+09 | 0.227894E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3023698.21 | 0.279635E+09 |
August | 0.682301E+09 | 0.256560E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6617172.96 | 0.228206E+09 |
September | 0.605444E+09 | 0.240332E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28781.72 | 0.183500E+09 |
October | 0.629407E+09 | 0.266844E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395874E+09 |
November | 0.623262E+09 | 0.291999E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424967E+09 |
December | 0.607275E+09 | 0.299474E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460038E+09 |
Annual Sum or Average | 0.755301E+10 | 0.313118E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10904234.68 | 0.471223E+10 |
Minimum of Months | 0.571020E+09 | 0.227894E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183500E+09 |
Maximum of Months | 0.682301E+09 | 0.300179E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6617172.96 | 0.540235E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.462988E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832456E+09 |
February | 0.901968E+09 | 0.385787E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778036E+09 |
March | 0.107774E+10 | 0.431019E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758335E+09 |
April | 0.956342E+09 | 0.370433E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1029909.50 | 0.740904E+09 |
May | 0.103597E+10 | 0.390385E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42228.06 | 0.599951E+09 |
June | 0.103308E+10 | 0.381834E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466710.30 | 0.499498E+09 |
July | 0.959235E+09 | 0.361159E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4291784.01 | 0.422044E+09 |
August | 0.107774E+10 | 0.405725E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9877036.20 | 0.345689E+09 |
September | 0.956342E+09 | 0.380090E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43067.36 | 0.284005E+09 |
October | 0.994195E+09 | 0.416659E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621763E+09 |
November | 0.984487E+09 | 0.451318E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657562E+09 |
December | 0.959235E+09 | 0.459630E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713790E+09 |
Annual Sum or Average | 0.119305E+11 | 0.489703E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15750735.42 | 0.725403E+10 |
Minimum of Months | 0.901968E+09 | 0.361159E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284005E+09 |
Maximum of Months | 0.107774E+10 | 0.462988E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9877036.20 | 0.832456E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.300106E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541883E+09 |
February | 0.570983E+09 | 0.247464E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495802E+09 |
March | 0.682256E+09 | 0.274487E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493076E+09 |
April | 0.605404E+09 | 0.234373E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 442547.10 | 0.488352E+09 |
May | 0.655811E+09 | 0.246292E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28161.99 | 0.405535E+09 |
June | 0.653980E+09 | 0.240583E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311159.96 | 0.336620E+09 |
July | 0.607235E+09 | 0.227802E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2880338.66 | 0.288962E+09 |
August | 0.682256E+09 | 0.255743E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6631145.06 | 0.233825E+09 |
September | 0.605404E+09 | 0.241861E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28781.33 | 0.189160E+09 |
October | 0.629366E+09 | 0.267118E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399395E+09 |
November | 0.623221E+09 | 0.290920E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426532E+09 |
December | 0.607235E+09 | 0.299203E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461734E+09 |
Annual Sum or Average | 0.755252E+10 | 0.312595E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10322134.10 | 0.476087E+10 |
Minimum of Months | 0.570983E+09 | 0.227802E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189160E+09 |
Maximum of Months | 0.682256E+09 | 0.300106E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6631145.06 | 0.541883E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.486307E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456533E+09 |
February | 0.901968E+09 | 0.398204E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411121E+09 |
March | 0.107774E+10 | 0.434899E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397215E+09 |
April | 0.956342E+09 | 0.369745E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1122447.73 | 0.382304E+09 |
May | 0.103597E+10 | 0.388234E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26257.36 | 0.311869E+09 |
June | 0.103308E+10 | 0.379296E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263726.79 | 0.261823E+09 |
July | 0.959235E+09 | 0.357436E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4908865.01 | 0.219707E+09 |
August | 0.107774E+10 | 0.402764E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6304990.43 | 0.178936E+09 |
September | 0.956342E+09 | 0.381570E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26159.42 | 0.147887E+09 |
October | 0.994195E+09 | 0.425734E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335522E+09 |
November | 0.984487E+09 | 0.469577E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371525E+09 |
December | 0.959235E+09 | 0.487815E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397906E+09 |
Annual Sum or Average | 0.119305E+11 | 0.498158E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12652446.75 | 0.387235E+10 |
Minimum of Months | 0.901968E+09 | 0.357436E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147887E+09 |
Maximum of Months | 0.107774E+10 | 0.487815E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6304990.43 | 0.456533E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.299115E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304512E+09 |
February | 0.571020E+09 | 0.249043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279319E+09 |
March | 0.682301E+09 | 0.274101E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273585E+09 |
April | 0.605444E+09 | 0.234222E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 549619.98 | 0.268622E+09 |
May | 0.655854E+09 | 0.247002E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17504.45 | 0.217160E+09 |
June | 0.654023E+09 | 0.241615E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175816.50 | 0.184362E+09 |
July | 0.607275E+09 | 0.227672E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1872884.47 | 0.153055E+09 |
August | 0.682301E+09 | 0.256260E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3624169.00 | 0.126726E+09 |
September | 0.605444E+09 | 0.239922E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17439.42 | 0.102977E+09 |
October | 0.629407E+09 | 0.266123E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231212E+09 |
November | 0.623262E+09 | 0.291105E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249516E+09 |
December | 0.607275E+09 | 0.298317E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266125E+09 |
Annual Sum or Average | 0.755301E+10 | 0.312450E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6257433.83 | 0.265717E+10 |
Minimum of Months | 0.571020E+09 | 0.227672E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102977E+09 |
Maximum of Months | 0.682301E+09 | 0.299115E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3624169.00 | 0.304512E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.461325E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434789E+10 |
February | 0.901968E+09 | 0.384872E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380133E+10 |
March | 0.107774E+10 | 0.430254E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399134E+10 |
April | 0.956342E+09 | 0.370019E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14547455.66 | 0.303518E+10 |
May | 0.103597E+10 | 0.390000E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1618998.41 | 0.265228E+10 |
June | 0.103308E+10 | 0.381455E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15903584.23 | 0.203219E+10 |
July | 0.959235E+09 | 0.360762E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94716068.65 | 0.134041E+10 |
August | 0.107774E+10 | 0.405269E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257783E+09 | 0.126992E+10 |
September | 0.956342E+09 | 0.379600E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3514791.87 | 0.186486E+10 |
October | 0.994195E+09 | 0.415745E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304130E+10 |
November | 0.984487E+09 | 0.450051E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379861E+10 |
December | 0.959235E+09 | 0.458102E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417667E+10 |
Annual Sum or Average | 0.119305E+11 | 0.488745E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388084E+09 | 0.353520E+11 |
Minimum of Months | 0.901968E+09 | 0.360762E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126992E+10 |
Maximum of Months | 0.107774E+10 | 0.461325E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257783E+09 | 0.434789E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.298981E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305408E+09 |
February | 0.570983E+09 | 0.246693E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280138E+09 |
March | 0.682256E+09 | 0.273893E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274793E+09 |
April | 0.605404E+09 | 0.234031E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 289979.18 | 0.268617E+09 |
May | 0.655811E+09 | 0.246090E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17505.37 | 0.224092E+09 |
June | 0.653980E+09 | 0.240318E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175817.70 | 0.185134E+09 |
July | 0.607235E+09 | 0.227441E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1672469.16 | 0.161628E+09 |
August | 0.682256E+09 | 0.255448E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3639739.81 | 0.130856E+09 |
September | 0.605404E+09 | 0.241321E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17439.45 | 0.107120E+09 |
October | 0.629366E+09 | 0.266356E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233248E+09 |
November | 0.623221E+09 | 0.289839E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250250E+09 |
December | 0.607235E+09 | 0.297909E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266882E+09 |
Annual Sum or Average | 0.755252E+10 | 0.311832E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5812950.68 | 0.268817E+10 |
Minimum of Months | 0.570983E+09 | 0.227441E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107120E+09 |
Maximum of Months | 0.682256E+09 | 0.298981E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3639739.81 | 0.305408E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.489234E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710929E+09 |
February | 0.901968E+09 | 0.400061E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645547E+09 |
March | 0.107774E+10 | 0.436245E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641566E+09 |
April | 0.956342E+09 | 0.370256E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1476523.32 | 0.624508E+09 |
May | 0.103597E+10 | 0.388533E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38098.78 | 0.505130E+09 |
June | 0.103308E+10 | 0.379498E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400597.44 | 0.419773E+09 |
July | 0.959235E+09 | 0.357720E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6077210.48 | 0.352209E+09 |
August | 0.107774E+10 | 0.403172E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9178409.70 | 0.287341E+09 |
September | 0.956342E+09 | 0.382345E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38410.14 | 0.235557E+09 |
October | 0.994195E+09 | 0.427660E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523804E+09 |
November | 0.984487E+09 | 0.472091E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570882E+09 |
December | 0.959235E+09 | 0.490685E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614360E+09 |
Annual Sum or Average | 0.119305E+11 | 0.499750E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17209249.86 | 0.613161E+10 |
Minimum of Months | 0.901968E+09 | 0.357720E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235557E+09 |
Maximum of Months | 0.107774E+10 | 0.490685E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9178409.70 | 0.710929E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.300178E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473573E+09 |
February | 0.421807E+09 | 0.249773E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437657E+09 |
March | 0.502994E+09 | 0.274615E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435821E+09 |
April | 0.447140E+09 | 0.234470E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 771704.17 | 0.426326E+09 |
May | 0.484071E+09 | 0.247222E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23770.48 | 0.343897E+09 |
June | 0.482240E+09 | 0.241815E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257147.76 | 0.287439E+09 |
July | 0.448971E+09 | 0.227894E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2602334.84 | 0.240454E+09 |
August | 0.502994E+09 | 0.256559E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5405207.84 | 0.197105E+09 |
September | 0.447140E+09 | 0.240332E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24371.38 | 0.160717E+09 |
October | 0.465148E+09 | 0.266843E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355909E+09 |
November | 0.460569E+09 | 0.291997E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382192E+09 |
December | 0.448971E+09 | 0.299473E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410294E+09 |
Annual Sum or Average | 0.557719E+10 | 0.313117E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9084536.46 | 0.415138E+10 |
Minimum of Months | 0.421807E+09 | 0.227894E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160717E+09 |
Maximum of Months | 0.502994E+09 | 0.300178E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5405207.84 | 0.473573E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.462986E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731482E+09 |
February | 0.901968E+09 | 0.385786E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689219E+09 |
March | 0.107774E+10 | 0.431018E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670611E+09 |
April | 0.956342E+09 | 0.370433E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 907474.22 | 0.648192E+09 |
May | 0.103597E+10 | 0.390385E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38090.98 | 0.518940E+09 |
June | 0.103308E+10 | 0.381834E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400567.15 | 0.429058E+09 |
July | 0.959235E+09 | 0.361159E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3646258.07 | 0.362122E+09 |
August | 0.107774E+10 | 0.405724E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8318015.29 | 0.297949E+09 |
September | 0.956342E+09 | 0.380090E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38181.94 | 0.247329E+09 |
October | 0.994195E+09 | 0.416658E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554228E+09 |
November | 0.984487E+09 | 0.451316E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589621E+09 |
December | 0.959235E+09 | 0.459629E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635985E+09 |
Annual Sum or Average | 0.119305E+11 | 0.489702E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13348587.66 | 0.637474E+10 |
Minimum of Months | 0.901968E+09 | 0.361159E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247329E+09 |
Maximum of Months | 0.107774E+10 | 0.462986E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8318015.29 | 0.731482E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.300104E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475197E+09 |
February | 0.570983E+09 | 0.247463E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438960E+09 |
March | 0.682256E+09 | 0.274486E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436875E+09 |
April | 0.605404E+09 | 0.234373E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375044.10 | 0.427978E+09 |
May | 0.655811E+09 | 0.246292E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25398.22 | 0.350871E+09 |
June | 0.653980E+09 | 0.240582E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 267066.45 | 0.289125E+09 |
July | 0.607235E+09 | 0.227802E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2458221.51 | 0.247973E+09 |
August | 0.682256E+09 | 0.255743E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5629303.98 | 0.201636E+09 |
September | 0.605404E+09 | 0.241861E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25606.53 | 0.164865E+09 |
October | 0.629366E+09 | 0.267117E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357793E+09 |
November | 0.623221E+09 | 0.290898E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382641E+09 |
December | 0.607235E+09 | 0.299201E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411396E+09 |
Annual Sum or Average | 0.755252E+10 | 0.312592E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8780640.77 | 0.418531E+10 |
Minimum of Months | 0.570983E+09 | 0.227802E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164865E+09 |
Maximum of Months | 0.682256E+09 | 0.300104E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5629303.98 | 0.475197E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983857E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910693E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900314E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1443829.53 | 0.861157E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.61 | 0.689509E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198841.31 | 0.570194E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5753992.61 | 0.478144E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8922651.19 | 0.395077E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.32 | 0.327496E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743930E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811677E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868689E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16324247.56 | 0.854074E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327496E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8922651.19 | 0.983857E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121010E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111538E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111842E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2100198.48 | 0.108250E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4723.13 | 0.875991E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254415.27 | 0.728353E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7160159.74 | 0.610206E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11429845.97 | 0.503506E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1550.11 | 0.412527E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911466E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982272E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105662E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20950892.70 | 0.106073E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412527E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11429845.97 | 0.121010E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121511E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112304E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112305E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997766.54 | 0.111581E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925624E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81612.47 | 0.775275E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2504063.24 | 0.653503E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8105757.19 | 0.523974E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423743E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910040E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967752E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104245E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11689199.44 | 0.107994E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423743E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8105757.19 | 0.121511E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 12758.28 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 12758.28 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 12758.28 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 12758.28 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 12758.28 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 12758.28 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 12758.28 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 12758.28 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 12758.28 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 12758.28 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 12758.28 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 12758.28 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 12758.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 3488.70 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 3488.70 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 3488.70 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 3488.70 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 3488.70 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 3488.70 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 3488.70 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 3488.70 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 3488.70 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 3488.70 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 3488.70 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 3488.70 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1353.52 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 668.03 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1273.75 | 16-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 587.25 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1191.76 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 471.46 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.33 | 01-APR-17:03 | 1294.03 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 382.52 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 05-MAY-16:00 | 965.18 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1261.51 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 409.74 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.81 | 23-JUL-14:00 | 643.51 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 405.84 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.54 | 08-AUG-17:00 | 899.98 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 591.74 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 614.08 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 726.22 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1166.08 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1274.56 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1053.10 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.08 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 201.33 | 1353.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 901.20 | 12-JAN-22:03 |
February | 827.22 | 01-FEB-10:09 | 427.38 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 848.46 | 16-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 355.50 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 807.86 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 250.52 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 01-APR-17:03 | 873.88 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 05-MAY-16:00 | 642.64 | 22-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 28-JUN-16:00 | 837.15 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 240.19 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.82 | 23-JUL-14:18 | 430.39 | 02-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 249.67 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 08-AUG-17:00 | 601.03 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 359.41 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 14-SEP-17:00 | 408.29 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 458.26 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 776.11 | 31-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 844.63 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 701.47 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.29 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 901.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1354.13 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 652.24 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1325.50 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 580.54 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1245.56 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 412.66 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 01-APR-17:30 | 1319.18 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 383.27 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 05-MAY-16:00 | 970.53 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 375.11 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1260.40 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 406.11 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.40 | 23-JUL-14:18 | 649.69 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 404.97 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.54 | 08-AUG-17:00 | 913.73 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 586.70 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 619.04 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 724.47 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1166.16 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1274.72 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1053.94 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 375.11 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.04 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 106.40 | 1354.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 901.19 | 12-JAN-22:03 |
February | 827.17 | 01-FEB-10:09 | 411.77 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 848.31 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 377.50 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 805.60 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 320.97 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 | 01-APR-16:00 | 863.06 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 249.34 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 05-MAY-16:00 | 646.33 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 245.05 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 28-JUN-16:00 | 834.25 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 331.10 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 | 23-JUL-14:15 | 434.97 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 327.17 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 08-AUG-17:00 | 616.67 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 379.66 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 | 14-SEP-17:00 | 408.85 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 459.85 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 775.75 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 843.17 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 701.65 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 245.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.85 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 | 901.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 764.41 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 665.37 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 704.39 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 581.53 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 663.67 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 412.20 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.60 | 01-APR-17:03 | 706.75 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 379.16 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 05-MAY-16:00 | 547.30 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 28-JUN-16:00 | 725.22 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 407.75 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.75 | 23-JUL-13:53 | 365.33 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 403.59 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 | 13-AUG-15:00 | 502.87 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 586.24 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 14-SEP-17:00 | 348.19 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 725.87 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 630.54 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 733.99 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 587.43 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.19 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 142.60 | 764.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 465.60 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 507.19 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 426.19 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 467.35 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 351.84 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 466.60 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 248.89 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.53 | 01-APR-17:03 | 498.36 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 05-MAY-16:00 | 364.83 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 495.10 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 237.73 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.59 | 30-JUL-16:00 | 245.45 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 247.97 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 08-AUG-17:00 | 349.64 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 355.90 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 232.81 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 458.01 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 420.53 | 31-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 487.17 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 390.56 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.81 | |||||
Maximum of Months | 827.22 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 75.53 | 507.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 19236.86 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 648.34 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 17726.12 | 09-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 574.50 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17299.89 | 01-MAR-07:02 |
April | 1306.65 | 03-APR-09:09 | 410.72 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.64 | 27-APR-16:10 | 14970.40 | 19-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 379.95 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 509.40 | 05-MAY-16:10 | 12410.00 | 11-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 371.42 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2158.32 | 28-JUN-17:00 | 9665.39 | 15-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 403.92 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3823.37 | 31-JUL-16:10 | 8579.95 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 402.67 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6069.02 | 10-AUG-17:00 | 9665.30 | 01-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 580.95 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 804.43 | 14-SEP-17:00 | 10598.72 | 27-SEP-06:05 |
October | 1306.65 | 02-OCT-09:09 | 724.03 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12417.33 | 13-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16178.08 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18721.26 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 371.42 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8579.95 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6069.02 | 19236.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 507.55 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 410.11 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 465.84 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 374.81 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 456.97 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 316.58 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 01-APR-16:00 | 476.44 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 247.76 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 05-MAY-16:00 | 366.61 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 243.30 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 484.29 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 327.21 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.43 | 23-JUL-13:53 | 254.35 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 323.01 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 08-AUG-17:00 | 361.89 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 377.04 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 233.24 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 459.67 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 421.12 | 31-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 486.42 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 391.14 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 243.30 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.24 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.43 | 507.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1184.88 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 668.03 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1090.95 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 587.23 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1068.06 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 471.44 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.96 | 01-APR-17:03 | 1136.83 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 382.51 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 05-MAY-16:00 | 850.01 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 350.81 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1124.75 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 409.73 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.04 | 23-JUL-13:53 | 572.52 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 405.83 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.60 | 13-AUG-15:00 | 785.36 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 591.72 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 544.09 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 726.22 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 983.54 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1120.61 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 910.33 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.09 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 178.96 | 1184.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 465.60 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 784.70 | 12-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 427.37 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 724.60 | 19-FEB-10:00 |
March | 805.43 | 01-MAR-08:09 | 355.50 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 722.74 | 28-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 250.52 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.15 | 01-APR-17:03 | 766.86 | 07-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 222.09 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 05-MAY-16:00 | 562.67 | 18-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 222.09 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 747.30 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 240.18 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.36 | 23-JUL-14:08 | 380.09 | 02-JUL-04:00 |
August | 805.43 | 01-AUG-07:10 | 249.66 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 | 08-AUG-17:00 | 524.86 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 359.40 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 14-SEP-17:00 | 362.06 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 458.26 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 654.76 | 31-OCT-21:05 |
November | 805.43 | 01-NOV-07:10 | 465.60 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 742.44 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 465.60 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 603.93 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.06 | |||||
Maximum of Months | 805.43 | 465.60 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 95.15 | 784.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 735.45 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1189.45 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 652.23 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1188.51 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 580.53 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1111.07 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 412.66 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.76 | 01-APR-17:30 | 1156.78 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 383.26 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 05-MAY-16:00 | 848.15 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 375.10 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1124.03 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 406.11 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 23-JUL-14:05 | 577.46 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 404.96 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 | 08-AUG-17:00 | 796.86 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 586.68 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 547.90 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 724.47 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 983.96 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 735.45 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1121.56 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 735.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 917.72 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 375.10 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.90 | |||||
Maximum of Months | 1306.65 | 735.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 1189.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 465.57 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 784.80 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 411.76 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 719.86 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 377.49 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 721.04 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 320.96 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.23 | 01-APR-16:00 | 758.15 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 249.33 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 05-MAY-16:00 | 563.10 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 245.05 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 744.09 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 331.09 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.27 | 23-JUL-14:05 | 386.52 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 327.16 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 | 08-AUG-17:00 | 537.51 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 379.65 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 14-SEP-17:00 | 362.19 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 459.85 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 654.41 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 465.57 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 741.33 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 465.57 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 605.43 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 245.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.19 | |||||
Maximum of Months | 827.17 | 465.57 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.27 | 784.80 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1689.56 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1573.36 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1529.09 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.77 | 01-APR-17:03 | 1597.51 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 05-MAY-16:00 | 1205.66 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 28-JUN-15:00 | 1593.32 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 23-JUL-13:53 | 803.29 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 | 13-AUG-15:10 | 1088.20 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 14-SEP-17:00 | 747.69 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1391.35 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1588.22 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1284.31 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.69 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.77 | 1689.56 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2095.79 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1929.48 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1909.38 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.19 | 01-APR-17:03 | 2025.98 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 05-MAY-16:00 | 1508.95 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.68 | 28-JUN-15:00 | 2019.64 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.21 | 23-JUL-13:53 | 1014.41 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.39 | 13-AUG-15:10 | 1389.13 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 14-SEP-17:00 | 926.52 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1705.70 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1951.48 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1591.69 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.19 | 2095.79 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2039.04 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1851.86 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1815.66 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.34 | 01-APR-17:03 | 2006.53 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1466.37 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 28-JUN-17:00 | 1909.06 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 24-JUL-14:00 | 969.33 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.52 | 08-AUG-17:00 | 1366.42 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 931.76 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1751.26 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1960.50 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1648.02 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 931.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.34 | 2039.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6460.64 | 12-JAN-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9250.32 | 09-FEB-17:00 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12919.56 | 22-MAR-07:08 | 30175.04 | 17443.51 | 63791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23115.58 | 28-APR-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28983.43 | 08-MAY-06:02 | 6352.64 | 5814.50 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31942.99 | 12-JUN-06:02 | 6352.64 | 5814.50 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32623.39 | 10-JUL-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32260.45 | 28-AUG-06:02 | 6352.64 | 5814.50 | 30220.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32703.38 | 05-SEP-06:01 | 8893.70 | 8140.30 | 42308.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27521.66 | 10-OCT-06:02 | 7623.17 | 6977.40 | 36264.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13300.66 | 07-NOV-08:10 | 12070.02 | 6977.40 | 25516.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8752.78 | 06-DEC-16:10 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6460.64 | 6035.01 | 3488.70 | 10774.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32703.38 | 30175.04 | 17443.51 | 63791.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.75 |
February | 1427.32 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 |
March | 2405.10 | 14-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.00 |
April | 7660.50 | 27-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | 0.00 |
May | 8146.08 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 |
June | 7969.76 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
July | 9124.01 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 0.00 |
August | 9114.26 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.77 | 0.00 |
September | 7080.56 | 14-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 |
October | 4809.71 | 04-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.30 |
November | 1935.57 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 |
December | 167.35 | 02-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 912.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1687.13 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.00 |
February | 1503.73 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.63 |
March | 2457.42 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.12 |
April | 2477.91 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 | 0.00 |
May | 2847.56 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 |
June | 2916.21 | 28-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 | 0.00 |
July | 4030.96 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 0.00 |
August | 4157.31 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 0.00 |
September | 3286.08 | 11-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
October | 1855.74 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.82 |
November | 1280.56 | 10-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.42 |
December | 1295.37 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1280.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4157.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 157.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2084.58 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.25 |
February | 2267.42 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.53 |
March | 2840.44 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.70 |
April | 2581.90 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 0.00 |
May | 2890.86 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 |
June | 3033.03 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
July | 4064.72 | 24-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.79 | 0.00 |
August | 4275.01 | 14-AUG-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.16 |
September | 3657.37 | 11-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 |
October | 2440.76 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.70 |
November | 1875.03 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 |
December | 1953.36 | 06-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1875.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4275.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.79 | 273.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5645.34 | 12-JAN-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6379.02 | 28-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7660.82 | 02-MAR-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12883.03 | 27-APR-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13676.43 | 15-MAY-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26019.75 | 12-JUN-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26306.03 | 25-JUL-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26207.35 | 15-AUG-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26198.64 | 11-SEP-06:01 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12482.75 | 04-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6895.05 | 06-NOV-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6023.26 | 06-DEC-16:20 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5645.34 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26306.03 | 8893.70 | 8140.30 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5363.48 | 11-JAN-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6311.43 | 28-FEB-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7231.86 | 02-MAR-17:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14390.36 | 27-APR-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15531.83 | 15-MAY-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15756.05 | 28-JUN-15:50 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21014.33 | 24-JUL-06:03 | 5082.11 | 4651.60 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26477.14 | 14-AUG-06:02 | 6352.64 | 5814.50 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15403.50 | 11-SEP-15:30 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12430.13 | 04-OCT-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6190.62 | 02-NOV-16:00 | 6035.01 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5605.82 | 05-DEC-16:15 | 12070.02 | 6977.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5363.48 | 5082.11 | 3488.70 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26477.14 | 12070.02 | 6977.40 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 982.94 | 11-JAN-16:10 | 1272.23 | 647.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.63 |
February | 1249.50 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1325.19 | 10-MAR-14:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 |
April | 4259.81 | 27-APR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 | 0.00 |
May | 4595.82 | 15-MAY-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
June | 4897.16 | 21-JUN-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
July | 6198.28 | 24-JUL-06:03 | 1071.35 | 467.75 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.26 |
August | 5355.28 | 09-AUG-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 0.00 |
September | 4097.05 | 12-SEP-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 0.00 |
October | 2507.58 | 04-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 |
November | 1190.36 | 02-NOV-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.46 |
December | 929.46 | 05-DEC-14:50 | 1306.65 | 396.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 929.46 | 1071.35 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6198.28 | 1306.65 | 647.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 107.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 638.35 | 20-JAN-11:00 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.58 |
February | 833.73 | 27-FEB-15:50 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 |
March | 2597.72 | 14-MAR-09:40 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.41 |
April | 6507.23 | 27-APR-09:00 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.99 |
May | 10584.78 | 14-MAY-09:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.29 |
June | 12141.79 | 25-JUN-09:23 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.01 |
July | 12295.49 | 30-JUL-09:02 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.82 |
August | 13194.55 | 06-AUG-08:52 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.93 |
September | 10536.19 | 10-SEP-10:02 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.63 |
October | 4650.69 | 04-OCT-09:10 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 |
November | 830.40 | 04-NOV-10:30 | 254.35 | 74.03 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 |
December | 683.76 | 05-DEC-10:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 638.35 | 169.56 | 49.35 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | |
Maximum of Months | 13194.55 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6365.70 | 20-JAN-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 |
February | 8192.29 | 27-FEB-14:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 |
March | 9430.52 | 01-MAR-13:35 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.71 |
April | 11540.84 | 27-APR-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 0.00 |
May | 17239.53 | 14-MAY-13:13 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.91 |
June | 11067.11 | 11-JUN-12:43 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.08 |
July | 18104.68 | 23-JUL-13:32 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 0.00 |
August | 19009.01 | 06-AUG-12:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.50 |
September | 20721.02 | 10-SEP-13:22 | 401.76 | 116.92 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.03 |
October | 16582.57 | 08-OCT-13:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.17 |
November | 8657.67 | 04-NOV-13:30 | 275.09 | 116.93 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6365.07 | 05-DEC-12:30 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6365.07 | 200.88 | 58.46 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20721.02 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 327.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 775.87 | 05-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 |
February | 3272.78 | 27-FEB-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 |
March | 4977.59 | 14-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
April | 7914.89 | 26-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
May | 15476.20 | 14-MAY-16:31 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.88 |
June | 14806.47 | 18-JUN-16:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.78 |
July | 14699.88 | 23-JUL-16:52 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.87 |
August | 15627.98 | 06-AUG-16:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.90 |
September | 14897.10 | 10-SEP-16:02 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.15 |
October | 6390.00 | 04-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 |
November | 2543.71 | 04-NOV-15:30 | 84.78 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
December | 843.51 | 05-DEC-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 775.87 | 84.78 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15627.98 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 341.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 942.62 | 11-JAN-15:00 | 1306.65 | 399.03 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.24 |
February | 1128.99 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1187.71 | 10-MAR-14:40 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 |
April | 2411.14 | 27-APR-16:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 0.00 |
May | 2920.58 | 05-MAY-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
June | 3618.59 | 21-JUN-15:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
July | 4506.96 | 24-JUL-15:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
August | 4157.17 | 09-AUG-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 0.00 |
September | 3120.27 | 12-SEP-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
October | 1916.88 | 04-OCT-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
November | 1209.88 | 06-NOV-12:00 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.65 |
December | 939.99 | 05-DEC-14:40 | 1306.65 | 390.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 939.99 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4506.96 | 1306.65 | 399.03 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 76.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 626.55 | 20-JAN-10:45 | 1654.44 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
February | 754.42 | 27-FEB-15:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 |
March | 1391.73 | 25-MAR-08:40 | 508.69 | 148.06 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.30 |
April | 4776.40 | 27-APR-09:20 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 |
May | 8210.36 | 15-MAY-06:02 | 1017.38 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 |
June | 8155.57 | 19-JUN-06:02 | 847.82 | 370.15 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.08 |
July | 10751.31 | 23-JUL-08:42 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 |
August | 9168.62 | 13-AUG-10:53 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 |
September | 6693.08 | 10-SEP-07:43 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3927.53 | 04-OCT-08:30 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
November | 846.80 | 02-NOV-10:40 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 |
December | 720.14 | 05-DEC-10:30 | 827.22 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 626.55 | 127.17 | 37.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10751.31 | 1654.44 | 444.18 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1348.69 | 20-JAN-13:50 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.17 |
February | 4814.67 | 27-FEB-13:20 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.10 |
March | 5790.81 | 02-MAR-13:20 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1281.20 |
April | 8753.57 | 27-APR-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 226.26 | 0.00 |
May | 9778.01 | 14-MAY-13:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.20 |
June | 6702.40 | 28-JUN-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 77.04 | 0.00 |
July | 11347.35 | 23-JUL-14:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 34.13 | 0.00 |
August | 15196.89 | 13-AUG-14:53 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 0.00 |
September | 15824.94 | 10-SEP-12:23 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.72 |
October | 10687.45 | 04-OCT-13:30 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.94 |
November | 6175.82 | 04-NOV-13:40 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3563.68 | 05-DEC-12:00 | 1272.23 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1348.69 | 137.54 | 58.47 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15824.94 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 226.26 | 1967.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 711.65 | 20-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.32 |
February | 1801.80 | 27-FEB-15:40 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 |
March | 2746.92 | 02-MAR-16:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 |
April | 5516.48 | 26-APR-17:30 | 84.78 | 74.03 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
May | 12080.17 | 14-MAY-16:31 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.63 |
June | 7534.74 | 18-JUN-17:22 | 0.00 | 74.02 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.36 |
July | 12752.54 | 23-JUL-17:21 | 0.00 | 98.69 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 |
August | 9513.47 | 12-AUG-17:05 | 254.33 | 74.02 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 |
September | 8394.40 | 10-SEP-15:02 | 169.55 | 49.34 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.97 |
October | 5615.02 | 04-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
November | 2023.31 | 04-NOV-15:30 | 84.78 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 |
December | 813.97 | 05-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 711.65 | 0.00 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | |
Maximum of Months | 12752.54 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1022.17 | 11-JAN-16:10 | 1272.23 | 647.40 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 |
February | 1265.23 | 28-FEB-15:00 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1324.52 | 10-MAR-14:50 | 1306.65 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.40 |
April | 3884.11 | 27-APR-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 0.00 |
May | 4155.78 | 15-MAY-14:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
June | 4541.54 | 21-JUN-15:30 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
July | 6741.03 | 24-JUL-06:03 | 1071.35 | 467.75 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.62 |
August | 6502.62 | 14-AUG-06:02 | 1339.19 | 584.68 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 |
September | 3924.57 | 12-SEP-14:40 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
October | 2552.49 | 04-OCT-15:20 | 1272.23 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 |
November | 1233.30 | 02-NOV-14:10 | 2544.47 | 701.62 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.95 |
December | 987.95 | 05-DEC-14:50 | 1306.65 | 396.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 987.95 | 1071.35 | 350.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6741.03 | 2544.47 | 701.62 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 92.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 710.12 | 20-JAN-11:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 |
February | 1636.17 | 08-FEB-11:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.62 |
March | 5434.47 | 01-MAR-13:01 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.27 |
April | 7176.80 | 27-APR-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
May | 12050.00 | 14-MAY-08:43 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 |
June | 11837.18 | 25-JUN-07:42 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.57 |
July | 13959.47 | 30-JUL-08:52 | 254.35 | 74.02 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.68 |
August | 12846.46 | 13-AUG-08:52 | 211.95 | 61.68 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.27 |
September | 10636.11 | 10-SEP-10:13 | 169.56 | 49.35 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.47 |
October | 5764.86 | 04-OCT-10:05 | 1610.86 | 444.18 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 |
November | 2383.20 | 04-NOV-10:05 | 508.69 | 148.06 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 |
December | 771.91 | 05-DEC-11:10 | 805.43 | 222.09 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 710.12 | 169.56 | 49.35 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | |
Maximum of Months | 13959.47 | 5638.00 | 1554.64 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6792.19 | 20-JAN-13:20 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
February | 8234.89 | 27-FEB-14:10 | 1306.65 | 350.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 |
March | 9732.44 | 01-MAR-13:25 | 2544.47 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 |
April | 11081.34 | 27-APR-13:05 | 2613.31 | 701.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 0.00 |
May | 11597.85 | 14-MAY-12:03 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.15 |
June | 10122.19 | 11-JUN-12:33 | 200.88 | 58.46 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.95 |
July | 18330.68 | 30-JUL-12:12 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 |
August | 17841.71 | 06-AUG-13:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.13 |
September | 17917.38 | 10-SEP-12:52 | 334.80 | 97.43 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.88 |
October | 17814.87 | 08-OCT-13:02 | 267.84 | 77.95 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.31 |
November | 8829.72 | 04-NOV-13:30 | 275.09 | 116.93 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7213.77 | 05-DEC-12:30 | 687.71 | 350.81 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6792.19 | 200.88 | 58.46 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18330.68 | 5088.93 | 1403.24 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 257.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 800.17 | 05-JAN-15:50 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.13 |
February | 3258.53 | 27-FEB-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
March | 4823.12 | 14-MAR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
April | 7679.73 | 26-APR-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
May | 14537.00 | 07-MAY-16:51 | 296.72 | 86.35 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.66 |
June | 10952.16 | 18-JUN-18:23 | 0.00 | 49.34 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.26 |
July | 15042.21 | 23-JUL-17:21 | 0.00 | 98.69 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 |
August | 13264.14 | 06-AUG-17:02 | 0.00 | 61.68 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 |
September | 12595.02 | 10-SEP-16:12 | 211.94 | 61.68 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.25 |
October | 6385.12 | 04-OCT-16:00 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.10 |
November | 2647.16 | 04-NOV-15:30 | 84.78 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
December | 1054.77 | 05-DEC-15:30 | 805.38 | 222.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 800.17 | 0.00 | 37.01 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15042.21 | 805.38 | 222.08 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 252.26 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.110776E+12 | 207655.42 | 02-JAN-07:10 | 0.397830E+11 | 60568.34 | 07-JAN-08:20 |
February | 0.844122E+11 | 160392.04 | 21-FEB-07:10 | 0.295079E+11 | 54884.01 | 18-FEB-07:30 |
March | 0.841605E+11 | 99413.02 | 06-MAR-07:10 | 0.220801E+11 | 47213.35 | 01-MAR-07:19 |
April | 0.771644E+11 | 102217.45 | 27-APR-15:09 | 0.153435E+11 | 38647.14 | 19-APR-06:10 |
May | 0.840781E+11 | 96865.72 | 15-MAY-15:20 | 0.123623E+11 | 26441.56 | 18-MAY-06:19 |
June | 0.878240E+11 | 103198.47 | 28-JUN-15:20 | 0.108991E+11 | 12649.96 | 15-JUN-06:10 |
July | 0.956345E+11 | 123005.78 | 31-JUL-15:09 | 0.106140E+11 | 9848.63 | 03-JUL-11:09 |
August | 0.107792E+12 | 126335.37 | 10-AUG-15:09 | 0.110727E+11 | 9816.14 | 31-AUG-11:09 |
September | 0.847575E+11 | 103900.49 | 14-SEP-15:09 | 0.105798E+11 | 16825.37 | 28-SEP-06:30 |
October | 0.798779E+11 | 85388.89 | 04-OCT-15:09 | 0.132863E+11 | 27132.11 | 16-OCT-06:00 |
November | 0.862183E+11 | 115189.22 | 24-NOV-07:10 | 0.247399E+11 | 47124.01 | 13-NOV-07:49 |
December | 0.988160E+11 | 169556.13 | 26-DEC-07:10 | 0.353960E+11 | 59555.72 | 26-DEC-07:40 |
Annual Sum or Average | 0.108151E+13 | 0.235665E+12 | ||||
Minimum of Months | 0.771644E+11 | 85388.89 | 0.105798E+11 | 9816.14 | ||
Maximum of Months | 0.110776E+12 | 207655.42 | 0.397830E+11 | 60568.34 |
Report: EnergyConsumptionElectricityGeneratedPropaneMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITYPRODUCED:FACILITY [J] | ELECTRICITYPRODUCED:FACILITY {Maximum} [W] | ELECTRICITYPRODUCED:FACILITY {TIMESTAMP} | PROPANE:FACILITY [] | PROPANE:FACILITY [] | |
January | 0.300844E+10 | 9871.73 | 30-JAN-11:30 | 0.00 | 0.00 |
February | 0.489241E+10 | 14029.42 | 27-FEB-12:30 | 0.00 | 0.00 |
March | 0.856267E+10 | 19758.56 | 24-MAR-12:30 | 0.00 | 0.00 |
April | 0.126577E+11 | 23186.09 | 25-APR-12:09 | 0.00 | 0.00 |
May | 0.163576E+11 | 26813.75 | 10-MAY-11:30 | 0.00 | 0.00 |
June | 0.169645E+11 | 24929.12 | 19-JUN-12:09 | 0.00 | 0.00 |
July | 0.180432E+11 | 25134.84 | 05-JUL-10:30 | 0.00 | 0.00 |
August | 0.146338E+11 | 22705.68 | 06-AUG-12:30 | 0.00 | 0.00 |
September | 0.104131E+11 | 19847.71 | 07-SEP-12:30 | 0.00 | 0.00 |
October | 0.671528E+10 | 16907.28 | 03-OCT-11:00 | 0.00 | 0.00 |
November | 0.332221E+10 | 10292.05 | 11-NOV-12:20 | 0.00 | 0.00 |
December | 0.257472E+10 | 8214.49 | 01-DEC-12:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.118146E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.257472E+10 | 8214.49 | 0.00 | 0.00 | |
Maximum of Months | 0.180432E+11 | 26813.75 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [J] | |
January | 0.146122E+11 | 0.422222E+10 | 0.545046E+11 | 0.977052E+09 | 0.327532E+10 | 12379742.02 | 0.331718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128808E+11 | 0.329965E+10 | 0.493409E+11 | 0.883838E+09 | 0.286409E+10 | 11196021.66 | 0.150001E+11 | 0.131630E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149822E+11 | 0.297020E+10 | 0.567112E+11 | 0.102249E+10 | 0.353882E+10 | 12675672.10 | 0.468909E+10 | 0.233893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132178E+11 | 0.227402E+10 | 0.526212E+11 | 0.940433E+09 | 0.421975E+10 | 11960507.72 | 0.159268E+10 | 0.228647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141651E+11 | 0.193555E+10 | 0.556079E+11 | 0.999262E+09 | 0.595165E+10 | 12527707.06 | 0.678551E+09 | 0.472762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140288E+11 | 0.169225E+10 | 0.546110E+11 | 0.983590E+09 | 0.739859E+10 | 12231776.97 | 0.302692E+09 | 0.879485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131634E+11 | 0.182237E+10 | 0.536070E+11 | 0.955904E+09 | 0.938649E+10 | 12256437.81 | 68359653.24 | 0.166187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146984E+11 | 0.214067E+10 | 0.567112E+11 | 0.102233E+10 | 0.108328E+11 | 12675672.10 | 76524321.63 | 0.222975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133224E+11 | 0.258687E+10 | 0.525990E+11 | 0.940264E+09 | 0.691012E+10 | 11960507.72 | 0.281809E+09 | 0.810511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140919E+11 | 0.336165E+10 | 0.545158E+11 | 0.976628E+09 | 0.413048E+10 | 12379742.02 | 0.168932E+10 | 0.109975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143574E+11 | 0.389481E+10 | 0.533244E+11 | 0.958774E+09 | 0.301116E+10 | 12059151.09 | 0.104259E+11 | 0.233837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142811E+11 | 0.438974E+10 | 0.535958E+11 | 0.956784E+09 | 0.303893E+10 | 12256437.81 | 0.225414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167801E+12 | 0.345900E+11 | 0.647750E+12 | 0.116173E+11 | 0.645582E+11 | 0.146559E+09 | 0.905183E+11 | 0.645294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128808E+11 | 0.169225E+10 | 0.493409E+11 | 0.883838E+09 | 0.286409E+10 | 11196021.66 | 68359653.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149822E+11 | 0.438974E+10 | 0.567112E+11 | 0.102249E+10 | 0.108328E+11 | 12675672.10 | 0.331718E+11 | 0.222975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.282526E+11 | 0.00 | 0.115304E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.190491E+11 | 0.00 | 0.104588E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.101972E+11 | 0.00 | 0.118829E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.440924E+10 | 0.00 | 0.109342E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.107068E+10 | 0.00 | 0.112916E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 38226617.54 | 0.00 | 0.108609E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.106140E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.110727E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.150043E+09 | 0.00 | 0.104298E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.234504E+10 | 0.00 | 0.109413E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.138599E+11 | 0.00 | 0.108801E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.241709E+11 | 0.00 | 0.112251E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103543E+12 | 0.00 | 0.132122E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.104298E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.282526E+11 | 0.00 | 0.118829E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 17672.30 | 02-JAN-16:30 | 3824.74 | 01-JAN-06:10 | 40437.79 | 02-JAN-08:09 | 829.15 | 04-JAN-08:20 | 6962.54 | 02-JAN-06:30 | 6.85 | 02-JAN-08:09 | 173726.49 | 02-JAN-06:30 |
February | 16912.03 | 02-FEB-16:00 | 3824.74 | 01-FEB-06:10 | 40437.79 | 01-FEB-08:09 | 828.53 | 02-FEB-08:20 | 4115.89 | 21-FEB-07:10 | 6.85 | 02-FEB-08:09 | 127964.54 | 21-FEB-07:10 |
March | 16150.34 | 22-MAR-07:10 | 3824.74 | 01-MAR-06:10 | 40437.79 | 01-MAR-08:09 | 827.78 | 22-MAR-07:19 | 4271.72 | 02-MAR-15:09 | 6.85 | 01-MAR-12:09 | 72994.88 | 06-MAR-07:10 |
April | 14765.68 | 03-APR-07:10 | 3824.74 | 01-APR-05:10 | 40437.79 | 03-APR-07:10 | 825.96 | 03-APR-07:19 | 16175.29 | 27-APR-14:30 | 6.85 | 12-APR-11:09 | 40158.53 | 18-APR-06:10 |
May | 14169.48 | 17-MAY-07:10 | 2323.70 | 01-MAY-19:19 | 40437.79 | 01-MAY-07:10 | 825.17 | 17-MAY-07:19 | 17458.79 | 15-MAY-14:30 | 6.85 | 09-MAY-16:10 | 17445.81 | 18-MAY-06:10 |
June | 14039.82 | 29-JUN-07:10 | 2323.70 | 01-JUN-19:00 | 40437.79 | 01-JUN-07:10 | 825.00 | 29-JUN-07:19 | 16938.27 | 28-JUN-15:20 | 6.85 | 01-JUN-05:10 | 8752.49 | 15-JUN-06:19 |
July | 14583.66 | 12-JUL-08:20 | 2323.70 | 01-JUL-20:10 | 40437.79 | 03-JUL-07:10 | 825.67 | 12-JUL-07:40 | 23563.60 | 31-JUL-15:09 | 6.85 | 15-JUL-16:10 | 3748.54 | 03-JUL-06:19 |
August | 14469.09 | 28-AUG-07:30 | 3824.74 | 16-AUG-05:10 | 40437.79 | 01-AUG-07:10 | 825.56 | 28-AUG-07:40 | 23971.67 | 14-AUG-15:20 | 6.85 | 12-AUG-16:10 | 5673.38 | 18-AUG-06:19 |
September | 16201.19 | 25-SEP-07:10 | 3824.74 | 01-SEP-05:10 | 40437.79 | 01-SEP-07:10 | 827.85 | 25-SEP-07:19 | 20185.01 | 11-SEP-15:30 | 6.85 | 01-SEP-05:10 | 12446.86 | 28-SEP-06:10 |
October | 17571.27 | 31-OCT-07:10 | 3824.74 | 01-OCT-05:10 | 40437.79 | 02-OCT-07:10 | 829.65 | 31-OCT-07:19 | 13636.80 | 04-OCT-15:30 | 6.85 | 30-OCT-16:10 | 39748.34 | 30-OCT-06:10 |
November | 17672.30 | 06-NOV-16:49 | 3824.74 | 01-NOV-05:10 | 40437.79 | 01-NOV-07:10 | 829.66 | 03-NOV-07:19 | 3552.44 | 04-NOV-14:20 | 6.85 | 15-NOV-08:09 | 83643.21 | 24-NOV-07:10 |
December | 17672.30 | 01-DEC-16:19 | 3824.74 | 01-DEC-06:10 | 40437.79 | 01-DEC-08:09 | 829.67 | 28-DEC-08:20 | 4575.05 | 26-DEC-07:10 | 6.85 | 02-DEC-06:19 | 136669.47 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 14039.82 | 2323.70 | 40437.79 | 825.00 | 3552.44 | 6.85 | 3748.54 | |||||||
Maximum of Months | 17672.30 | 3824.74 | 40437.79 | 829.67 | 23971.67 | 6.85 | 173726.49 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY {Maximum} [W] | COGENERATION:ELECTRICITY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 7967.70 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 7432.50 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33520.93 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 27181.22 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33071.73 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 47824.01 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 50066.71 | 29-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 32586.14 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 18974.72 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 12029.66 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 50066.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 207655.42 | 02-JAN-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 6870.43 | 6.85 | 172473.38 | 0.00 | 0.00 |
February | 160392.04 | 21-FEB-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 4115.89 | 6.85 | 127964.54 | 0.00 | 0.00 |
March | 99413.02 | 06-MAR-07:10 | 4856.24 | 18346.02 | 0.00 | 243.12 | 2965.91 | 6.85 | 72994.88 | 0.00 | 0.00 |
April | 102217.45 | 27-APR-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 15564.97 | 6.85 | 0.00 | 33464.01 | 0.00 |
May | 96865.72 | 15-MAY-15:20 | 13903.46 | 38454.47 | 0.00 | 823.69 | 17306.38 | 6.85 | 0.00 | 26370.86 | 0.00 |
June | 103198.47 | 28-JUN-15:20 | 13903.46 | 38454.47 | 0.00 | 823.69 | 16938.27 | 6.85 | 0.00 | 33071.73 | 0.00 |
July | 123005.78 | 31-JUL-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 23563.60 | 6.85 | 0.00 | 46253.71 | 0.00 |
August | 126335.37 | 10-AUG-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 23826.34 | 6.85 | 0.00 | 49320.56 | 0.00 |
September | 103900.49 | 14-SEP-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 19097.92 | 6.85 | 0.00 | 31614.09 | 0.00 |
October | 85388.89 | 04-OCT-15:09 | 13903.46 | 38454.47 | 0.00 | 823.69 | 13462.91 | 6.85 | 0.00 | 18737.51 | 0.00 |
November | 115189.22 | 24-NOV-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 3234.39 | 6.85 | 83643.21 | 0.00 | 0.00 |
December | 169556.13 | 26-DEC-07:10 | 5890.77 | 18346.02 | 3824.74 | 243.23 | 4575.05 | 6.85 | 136669.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 85388.89 | 4856.24 | 18346.02 | 0.00 | 243.12 | 2965.91 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 207655.42 | 13903.46 | 38454.47 | 3824.74 | 823.69 | 23826.34 | 6.85 | 172473.38 | 49320.56 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 52966.75 | 07-JAN-07:00 | 0.00 | 10113.75 | 26-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 46323.87 | 18-FEB-07:19 | 0.00 | 10122.84 | 07-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 38328.24 | 01-MAR-07:19 | 0.00 | 10113.22 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 29820.68 | 19-APR-06:19 | 0.00 | 10059.66 | 06-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 17944.87 | 18-MAY-06:10 | 0.00 | 9996.99 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 3868.05 | 15-JUN-06:10 | 0.00 | 9910.65 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9848.63 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9816.14 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 8511.84 | 28-SEP-06:10 | 0.00 | 9861.90 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 18311.60 | 16-OCT-06:00 | 0.00 | 9926.42 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 38649.33 | 13-NOV-07:00 | 0.00 | 10011.34 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 50706.81 | 26-DEC-07:40 | 0.00 | 10078.13 | 26-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9816.14 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 52966.75 | 0.00 | 10122.84 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.66 | 1.17 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.66 | 1.17 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.66 | 1.17 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.34 | 2.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 19.34 | 2.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.34 | 2.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.33 | 1.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.33 | 17.97 | 0.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.27 | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Annual Sum or Average | 2.00 | 19.10 | 1.83 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.33 | 1.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.37 | 4.50 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
February | 2.33 | 17.13 | 1.33 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
March | 0.17 | 19.32 | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.21 | 0.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
December | 3.83 | 18.44 | 2.83 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Annual Sum or Average | 12.17 | 18.19 | 9.17 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 19.32 | 4.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 16.36 | 1.00 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
February | 1.00 | 16.81 | 0.33 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.61 | 1.00 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.60 | 1.67 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.91 | 3.33 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.82 | 3.67 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.79 | 0.83 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
December | 1.00 | 15.96 | 0.17 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
Annual Sum or Average | 4.83 | 16.48 | 1.67 | 16.96 | 10.50 | 23.65 | 10.50 | 25.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.40 | 1.00 | 19.40 | 3.67 | 27.91 | 3.67 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 17.57 | 0.50 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
February | 0.33 | 17.21 | 0.17 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.56 | 2.33 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.44 | 1.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.78 | 3.50 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.91 | 3.17 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.12 | 1.83 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.66 | 0.50 | 27.66 |
November | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 0.33 | 17.92 | 0.17 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
Annual Sum or Average | 2.00 | 17.72 | 1.00 | 18.20 | 13.83 | 26.05 | 13.67 | 26.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.44 | 0.50 | 19.44 | 3.50 | 28.12 | 3.50 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 16.16 | 1.50 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
February | 0.83 | 17.18 | 0.50 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.17 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.99 | 2.67 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.79 | 2.00 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.26 | 3.00 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.06 | 2.33 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.89 | 1.67 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
December | 1.00 | 15.96 | 0.17 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
Annual Sum or Average | 5.17 | 16.39 | 2.33 | 16.71 | 20.00 | 24.94 | 11.83 | 25.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.40 | 1.50 | 19.40 | 5.50 | 28.26 | 3.00 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.28 | 3.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.21 | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Annual Sum or Average | 3.50 | 19.28 | 3.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.41 | 3.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.91 | 1.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.67 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.60 | 2.50 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.61 | 2.33 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.49 | 0.83 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 18.91 | 1.00 | 18.91 | 6.83 | 25.59 | 6.83 | 26.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 18.91 | 1.00 | 18.91 | 2.50 | 27.61 | 2.50 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.33 | 18.72 | 62.33 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
February | 33.50 | 18.71 | 33.50 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
March | 23.17 | 19.24 | 23.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 12.50 | 19.49 | 12.50 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
May | 2.67 | 20.03 | 2.67 | 20.03 | 0.33 | 20.46 | 0.33 | 20.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.46 | 1.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.56 | 2.50 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.82 | 1.67 | 27.82 |
October | 3.67 | 20.06 | 3.67 | 20.06 | 0.50 | 20.53 | 0.50 | 20.95 |
November | 31.67 | 19.32 | 31.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
December | 51.00 | 18.85 | 51.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Annual Sum or Average | 220.50 | 18.97 | 220.50 | 18.97 | 6.67 | 19.10 | 6.67 | 19.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.33 | 20.06 | 62.33 | 20.06 | 2.50 | 27.82 | 2.50 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.83 | 1.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 1.17 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.50 | 0.67 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.03 | 1.67 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 1.67 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.76 | 0.83 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 18.83 | 1.00 | 18.83 | 11.67 | 26.49 | 6.00 | 26.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 18.83 | 1.00 | 18.83 | 3.67 | 28.03 | 1.67 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.18 | 2.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
February | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.33 | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Annual Sum or Average | 2.50 | 19.20 | 2.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.34 | 2.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.82 | 0.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.77 | 1.00 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.61 | 2.17 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.08 | 2.83 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.85 | 3.50 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.84 | 1.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.82 | 0.50 | 19.07 | 10.67 | 26.99 | 10.67 | 27.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.82 | 0.50 | 19.07 | 3.50 | 28.08 | 3.50 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.84 | 0.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.39 | 0.83 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.50 | 2.17 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.39 | 1.50 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.68 | 3.33 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.85 | 3.00 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.02 | 2.00 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.62 | 0.83 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.84 | 0.50 | 19.07 | 14.00 | 27.01 | 14.00 | 27.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.84 | 0.50 | 19.07 | 3.33 | 28.02 | 3.33 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.80 | 0.50 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.17 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.95 | 2.67 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.81 | 1.50 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.14 | 2.83 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.04 | 2.17 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.78 | 2.00 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.80 | 0.50 | 19.04 | 18.67 | 27.45 | 11.33 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.80 | 0.50 | 19.04 | 5.33 | 28.14 | 2.83 | 28.13 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.24 | 37.50 | 22.06 | 37.50 | 21.90 |
February | 453.33 | 23.07 | 0.50 | 23.07 | 0.50 | 23.06 |
March | 481.17 | 23.74 | 0.00 | 23.74 | 0.00 | 23.74 |
April | 246.17 | 23.85 | 31.83 | 23.99 | 0.00 | 23.99 |
May | 31.83 | 23.93 | 106.50 | 24.68 | 0.00 | 24.68 |
June | 0.00 | 0.00 | 170.00 | 24.82 | 0.00 | 24.82 |
July | 0.00 | 0.00 | 335.33 | 24.55 | 0.00 | 24.55 |
August | 0.00 | 0.00 | 405.33 | 24.39 | 0.00 | 24.39 |
September | 0.00 | 0.00 | 269.67 | 24.62 | 0.00 | 24.62 |
October | 158.83 | 23.77 | 53.50 | 24.19 | 0.00 | 24.19 |
November | 396.17 | 23.44 | 9.50 | 23.47 | 0.00 | 23.47 |
December | 497.00 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
Annual Sum or Average | 2766.50 | 23.18 | 1419.67 | 23.63 | 38.00 | 23.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.06 | 0.00 | 21.90 |
Maximum of Months | 502.00 | 23.93 | 405.33 | 24.82 | 37.50 | 24.82 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.22 | 131.17 | 21.01 | 131.17 | 20.87 |
February | 454.00 | 21.89 | 47.17 | 21.77 | 47.17 | 21.66 |
March | 513.67 | 22.96 | 0.17 | 22.96 | 0.17 | 22.96 |
April | 377.00 | 23.43 | 24.83 | 23.52 | 0.00 | 23.52 |
May | 182.17 | 23.68 | 47.83 | 23.88 | 0.00 | 23.88 |
June | 56.67 | 23.70 | 94.50 | 24.33 | 0.00 | 24.33 |
July | 5.50 | 23.66 | 255.67 | 24.44 | 0.00 | 24.44 |
August | 13.17 | 23.62 | 339.00 | 24.31 | 0.00 | 24.31 |
September | 57.17 | 23.47 | 170.67 | 24.24 | 0.00 | 24.24 |
October | 351.50 | 23.20 | 11.83 | 23.26 | 0.00 | 23.26 |
November | 477.83 | 22.36 | 1.50 | 22.35 | 1.50 | 22.35 |
December | 497.00 | 21.65 | 37.67 | 21.57 | 37.67 | 21.50 |
Annual Sum or Average | 3487.67 | 22.44 | 1162.00 | 22.75 | 217.67 | 22.64 |
Minimum of Months | 5.50 | 21.22 | 0.17 | 21.01 | 0.00 | 20.87 |
Maximum of Months | 513.67 | 23.70 | 339.00 | 24.44 | 131.17 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.69 | 251.50 | 20.46 | 251.50 | 20.35 |
February | 454.00 | 21.24 | 147.00 | 21.00 | 147.00 | 20.85 |
March | 514.00 | 22.27 | 28.33 | 22.19 | 28.33 | 22.10 |
April | 400.33 | 22.96 | 16.67 | 23.02 | 0.00 | 23.02 |
May | 247.17 | 23.38 | 39.00 | 23.51 | 0.00 | 23.51 |
June | 117.00 | 23.54 | 81.00 | 23.90 | 0.00 | 23.90 |
July | 55.33 | 23.58 | 234.00 | 24.20 | 0.00 | 24.20 |
August | 50.00 | 23.46 | 288.00 | 24.14 | 0.00 | 24.14 |
September | 172.33 | 23.33 | 106.83 | 23.69 | 0.00 | 23.69 |
October | 447.33 | 22.70 | 1.83 | 22.70 | 0.83 | 22.70 |
November | 489.00 | 21.61 | 79.67 | 21.43 | 79.67 | 21.29 |
December | 497.00 | 20.96 | 201.00 | 20.76 | 201.00 | 20.65 |
Annual Sum or Average | 3945.50 | 22.01 | 1474.83 | 22.10 | 708.33 | 21.88 |
Minimum of Months | 50.00 | 20.69 | 1.83 | 20.46 | 0.00 | 20.35 |
Maximum of Months | 514.00 | 23.58 | 288.00 | 24.20 | 251.50 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.07 | 398.83 | 19.96 | 398.83 | 19.92 |
February | 454.00 | 20.46 | 270.00 | 20.25 | 270.00 | 20.16 |
March | 514.00 | 21.32 | 133.33 | 21.08 | 133.33 | 20.93 |
April | 426.50 | 22.22 | 52.67 | 22.13 | 38.50 | 22.00 |
May | 289.67 | 22.77 | 54.83 | 22.99 | 1.00 | 22.99 |
June | 166.50 | 23.19 | 95.00 | 23.59 | 0.00 | 23.59 |
July | 110.50 | 23.36 | 243.00 | 23.97 | 0.00 | 23.97 |
August | 125.33 | 23.25 | 273.00 | 23.89 | 0.00 | 23.89 |
September | 268.83 | 22.82 | 85.83 | 23.15 | 0.00 | 23.15 |
October | 481.50 | 21.84 | 45.83 | 21.68 | 45.83 | 21.56 |
November | 489.00 | 20.74 | 223.50 | 20.51 | 223.50 | 20.39 |
December | 497.00 | 20.24 | 373.50 | 20.13 | 373.50 | 20.09 |
Annual Sum or Average | 4324.83 | 21.41 | 2249.33 | 21.41 | 1484.50 | 21.14 |
Minimum of Months | 110.50 | 20.07 | 45.83 | 19.96 | 0.00 | 19.92 |
Maximum of Months | 514.00 | 23.36 | 398.83 | 23.97 | 398.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 367.83 | 19.97 | 367.83 | 19.91 |
February | 454.00 | 20.72 | 232.33 | 20.46 | 232.33 | 20.33 |
March | 506.67 | 21.75 | 98.83 | 21.46 | 98.83 | 21.26 |
April | 313.00 | 22.32 | 80.17 | 22.43 | 27.67 | 22.29 |
May | 217.17 | 22.79 | 138.83 | 23.42 | 3.83 | 23.44 |
June | 113.17 | 23.34 | 217.33 | 24.07 | 4.83 | 24.11 |
July | 91.67 | 23.95 | 322.50 | 24.31 | 13.67 | 24.40 |
August | 91.83 | 23.89 | 351.33 | 24.22 | 14.83 | 24.31 |
September | 206.83 | 22.87 | 170.33 | 23.54 | 3.50 | 23.57 |
October | 408.17 | 21.91 | 50.00 | 21.82 | 38.00 | 21.68 |
November | 489.00 | 20.87 | 193.83 | 20.61 | 193.83 | 20.47 |
December | 497.00 | 20.31 | 336.83 | 20.15 | 336.83 | 20.09 |
Annual Sum or Average | 3890.50 | 21.45 | 2560.17 | 21.72 | 1336.00 | 21.44 |
Minimum of Months | 91.67 | 20.11 | 50.00 | 19.97 | 3.50 | 19.91 |
Maximum of Months | 506.67 | 23.95 | 367.83 | 24.31 | 367.83 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.17 | 20.48 | 311.83 | 20.21 | 311.83 | 20.09 |
February | 408.17 | 20.99 | 195.83 | 20.76 | 185.67 | 20.60 |
March | 418.00 | 21.60 | 119.67 | 21.47 | 92.33 | 21.28 |
April | 304.33 | 22.21 | 110.67 | 22.53 | 29.83 | 22.40 |
May | 242.83 | 22.80 | 142.17 | 23.40 | 8.33 | 23.46 |
June | 163.50 | 23.21 | 178.67 | 23.85 | 5.17 | 23.90 |
July | 118.00 | 23.64 | 291.00 | 24.19 | 12.17 | 24.28 |
August | 122.17 | 23.63 | 325.67 | 24.14 | 12.67 | 24.22 |
September | 201.83 | 23.00 | 207.17 | 23.70 | 7.33 | 23.76 |
October | 355.50 | 22.00 | 117.83 | 22.37 | 30.83 | 22.25 |
November | 453.83 | 21.07 | 185.00 | 20.92 | 163.67 | 20.74 |
December | 473.83 | 20.64 | 285.00 | 20.38 | 283.33 | 20.26 |
Annual Sum or Average | 3759.17 | 21.64 | 2470.50 | 21.96 | 1143.17 | 21.69 |
Minimum of Months | 118.00 | 20.48 | 110.67 | 20.21 | 5.17 | 20.09 |
Maximum of Months | 497.17 | 23.64 | 325.67 | 24.19 | 311.83 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 374.67 | 20.00 | 374.67 | 19.94 |
February | 446.00 | 20.69 | 239.67 | 20.43 | 239.50 | 20.30 |
March | 478.67 | 21.46 | 127.83 | 21.25 | 119.67 | 21.07 |
April | 351.67 | 22.16 | 92.17 | 22.31 | 37.50 | 22.17 |
May | 252.00 | 22.89 | 131.17 | 23.43 | 13.33 | 23.53 |
June | 155.67 | 23.26 | 185.83 | 23.86 | 6.33 | 23.92 |
July | 111.17 | 23.79 | 308.33 | 24.25 | 15.17 | 24.34 |
August | 118.00 | 23.59 | 321.00 | 24.12 | 11.17 | 24.19 |
September | 221.83 | 23.01 | 172.67 | 23.62 | 10.00 | 23.70 |
October | 427.83 | 21.86 | 68.50 | 21.86 | 40.67 | 21.73 |
November | 483.83 | 20.85 | 202.17 | 20.62 | 199.33 | 20.48 |
December | 497.00 | 20.36 | 342.33 | 20.19 | 342.33 | 20.12 |
Annual Sum or Average | 4045.67 | 21.48 | 2566.33 | 21.70 | 1409.67 | 21.44 |
Minimum of Months | 111.17 | 20.15 | 68.50 | 20.00 | 6.33 | 19.94 |
Maximum of Months | 502.00 | 23.79 | 374.67 | 24.25 | 374.67 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.34 | 383.67 | 20.25 | 383.67 | 20.22 |
February | 454.00 | 20.66 | 249.67 | 20.52 | 249.67 | 20.45 |
March | 514.00 | 21.32 | 90.00 | 21.19 | 90.00 | 21.10 |
April | 467.17 | 22.22 | 8.17 | 22.20 | 7.33 | 22.17 |
May | 381.17 | 23.08 | 14.33 | 23.12 | 0.00 | 23.12 |
June | 210.50 | 23.45 | 40.33 | 23.58 | 0.00 | 23.58 |
July | 94.50 | 23.58 | 179.00 | 23.99 | 0.00 | 23.99 |
August | 104.67 | 23.47 | 244.50 | 23.96 | 0.00 | 23.96 |
September | 268.33 | 23.21 | 66.67 | 23.40 | 0.00 | 23.40 |
October | 486.00 | 22.41 | 0.83 | 22.41 | 0.83 | 22.40 |
November | 489.00 | 21.28 | 109.50 | 21.12 | 109.50 | 21.01 |
December | 497.00 | 20.61 | 314.17 | 20.51 | 314.17 | 20.47 |
Annual Sum or Average | 4468.33 | 21.74 | 1700.83 | 21.68 | 1155.17 | 21.46 |
Minimum of Months | 94.50 | 20.34 | 0.83 | 20.25 | 0.00 | 20.22 |
Maximum of Months | 514.00 | 23.58 | 383.67 | 23.99 | 383.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.38 | 358.33 | 20.27 | 358.33 | 20.23 |
February | 454.00 | 20.94 | 205.50 | 20.75 | 205.50 | 20.66 |
March | 514.00 | 21.90 | 45.83 | 21.77 | 45.83 | 21.66 |
April | 354.67 | 22.72 | 34.33 | 22.80 | 4.17 | 22.78 |
May | 231.17 | 23.10 | 97.50 | 23.53 | 0.00 | 23.53 |
June | 86.17 | 23.45 | 207.00 | 24.20 | 0.67 | 24.21 |
July | 48.83 | 24.19 | 325.67 | 24.40 | 8.33 | 24.46 |
August | 46.00 | 24.22 | 368.67 | 24.33 | 9.67 | 24.39 |
September | 165.50 | 23.31 | 192.00 | 23.89 | 2.83 | 23.92 |
October | 388.50 | 22.58 | 18.67 | 22.68 | 0.00 | 22.68 |
November | 489.00 | 21.46 | 90.17 | 21.29 | 90.17 | 21.16 |
December | 497.00 | 20.71 | 259.17 | 20.56 | 259.17 | 20.49 |
Annual Sum or Average | 3776.83 | 21.75 | 2202.83 | 22.06 | 984.67 | 21.82 |
Minimum of Months | 46.00 | 20.38 | 18.67 | 20.27 | 0.00 | 20.23 |
Maximum of Months | 514.00 | 24.22 | 368.67 | 24.40 | 358.33 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 20.35 | 345.17 | 20.17 | 345.17 | 20.09 |
February | 438.67 | 21.02 | 147.83 | 20.76 | 147.83 | 20.60 |
March | 470.33 | 21.53 | 57.33 | 21.38 | 54.17 | 21.24 |
April | 376.50 | 22.11 | 64.17 | 22.30 | 15.17 | 22.21 |
May | 324.83 | 22.53 | 77.17 | 22.94 | 1.00 | 22.93 |
June | 225.67 | 22.79 | 107.33 | 23.40 | 0.00 | 23.40 |
July | 104.83 | 23.02 | 274.67 | 24.05 | 3.50 | 24.08 |
August | 96.83 | 23.11 | 324.33 | 24.07 | 8.00 | 24.12 |
September | 169.67 | 22.77 | 222.17 | 23.75 | 6.50 | 23.81 |
October | 344.83 | 22.24 | 85.83 | 22.75 | 3.00 | 22.75 |
November | 459.67 | 21.19 | 108.50 | 21.13 | 89.67 | 20.98 |
December | 484.00 | 20.70 | 262.50 | 20.49 | 260.00 | 20.38 |
Annual Sum or Average | 3996.67 | 21.58 | 2077.00 | 21.90 | 934.00 | 21.66 |
Minimum of Months | 96.83 | 20.35 | 57.33 | 20.17 | 0.00 | 20.09 |
Maximum of Months | 500.83 | 23.11 | 345.17 | 24.07 | 345.17 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.41 | 358.00 | 20.29 | 358.00 | 20.24 |
February | 453.17 | 20.93 | 203.33 | 20.73 | 203.33 | 20.63 |
March | 499.50 | 21.73 | 60.33 | 21.59 | 60.17 | 21.47 |
April | 375.83 | 22.49 | 42.83 | 22.67 | 3.50 | 22.65 |
May | 239.50 | 23.25 | 108.17 | 23.67 | 2.67 | 23.69 |
June | 112.67 | 23.46 | 160.17 | 24.03 | 0.50 | 24.04 |
July | 37.67 | 24.41 | 350.33 | 24.47 | 8.17 | 24.52 |
August | 41.67 | 24.04 | 367.67 | 24.30 | 7.33 | 24.35 |
September | 132.00 | 23.43 | 208.67 | 24.05 | 4.17 | 24.09 |
October | 406.67 | 22.57 | 23.67 | 22.70 | 0.00 | 22.70 |
November | 483.83 | 21.43 | 95.33 | 21.27 | 93.67 | 21.14 |
December | 497.00 | 20.73 | 268.67 | 20.57 | 268.67 | 20.50 |
Annual Sum or Average | 3781.50 | 21.71 | 2247.17 | 22.04 | 1010.17 | 21.81 |
Minimum of Months | 37.67 | 20.41 | 23.67 | 20.29 | 0.00 | 20.24 |
Maximum of Months | 502.00 | 24.41 | 367.67 | 24.47 | 358.00 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 337.50 | 20.18 | 337.50 | 20.12 |
February | 454.00 | 20.78 | 202.50 | 20.57 | 202.50 | 20.45 |
March | 514.00 | 21.79 | 53.67 | 21.65 | 53.67 | 21.54 |
April | 414.33 | 22.64 | 21.67 | 22.69 | 4.00 | 22.67 |
May | 258.50 | 23.18 | 53.50 | 23.36 | 0.00 | 23.36 |
June | 115.00 | 23.47 | 93.83 | 23.83 | 0.00 | 23.83 |
July | 53.33 | 23.60 | 256.50 | 24.14 | 0.00 | 24.14 |
August | 61.33 | 23.45 | 304.00 | 24.07 | 0.00 | 24.07 |
September | 211.67 | 23.21 | 106.00 | 23.55 | 0.00 | 23.55 |
October | 458.50 | 22.37 | 6.50 | 22.35 | 5.83 | 22.32 |
November | 489.00 | 21.21 | 129.33 | 21.00 | 129.33 | 20.87 |
December | 497.00 | 20.57 | 288.67 | 20.43 | 288.67 | 20.37 |
Annual Sum or Average | 4028.67 | 21.69 | 1853.67 | 21.77 | 1021.50 | 21.53 |
Minimum of Months | 53.33 | 20.33 | 6.50 | 20.18 | 0.00 | 20.12 |
Maximum of Months | 514.00 | 23.60 | 337.50 | 24.14 | 337.50 | 24.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.26 | 286.00 | 20.09 | 286.00 | 20.02 |
February | 384.83 | 20.99 | 163.17 | 20.74 | 163.17 | 20.60 |
March | 419.33 | 22.04 | 40.00 | 21.88 | 40.00 | 21.75 |
April | 271.50 | 22.72 | 50.00 | 22.95 | 3.17 | 22.92 |
May | 183.17 | 23.21 | 108.33 | 23.73 | 3.67 | 23.77 |
June | 83.33 | 23.70 | 180.17 | 24.30 | 6.67 | 24.36 |
July | 41.83 | 24.57 | 272.83 | 24.54 | 11.50 | 24.63 |
August | 51.50 | 24.41 | 301.83 | 24.41 | 13.50 | 24.51 |
September | 156.67 | 23.32 | 155.67 | 23.90 | 4.50 | 23.95 |
October | 338.67 | 22.38 | 28.17 | 22.49 | 5.67 | 22.46 |
November | 414.50 | 21.27 | 108.67 | 21.04 | 108.67 | 20.89 |
December | 422.00 | 20.58 | 235.33 | 20.39 | 235.33 | 20.31 |
Annual Sum or Average | 3194.33 | 21.72 | 1930.17 | 22.03 | 881.83 | 21.78 |
Minimum of Months | 41.83 | 20.26 | 28.17 | 20.09 | 3.17 | 20.02 |
Maximum of Months | 427.00 | 24.57 | 301.83 | 24.54 | 286.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.50 | 20.78 | 253.33 | 20.51 | 251.50 | 20.37 |
February | 400.33 | 21.35 | 140.17 | 21.20 | 124.33 | 21.02 |
March | 402.00 | 22.07 | 67.67 | 22.08 | 35.83 | 21.96 |
April | 280.00 | 22.65 | 89.17 | 23.07 | 3.50 | 23.06 |
May | 210.33 | 23.22 | 145.33 | 23.73 | 6.00 | 23.79 |
June | 122.50 | 23.48 | 186.50 | 24.05 | 3.17 | 24.08 |
July | 70.83 | 24.07 | 310.50 | 24.36 | 11.00 | 24.44 |
August | 57.83 | 24.16 | 349.17 | 24.31 | 12.67 | 24.39 |
September | 146.83 | 23.44 | 234.83 | 24.03 | 7.67 | 24.09 |
October | 329.50 | 22.57 | 100.17 | 23.06 | 2.67 | 23.08 |
November | 443.17 | 21.55 | 118.33 | 21.49 | 92.17 | 21.32 |
December | 463.50 | 20.99 | 211.83 | 20.77 | 207.00 | 20.63 |
Annual Sum or Average | 3418.33 | 21.94 | 2207.00 | 22.37 | 757.50 | 22.15 |
Minimum of Months | 57.83 | 20.78 | 67.67 | 20.51 | 2.67 | 20.37 |
Maximum of Months | 491.50 | 24.16 | 349.17 | 24.36 | 251.50 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 311.33 | 20.23 | 311.33 | 20.15 |
February | 443.83 | 21.01 | 173.83 | 20.76 | 173.83 | 20.62 |
March | 473.50 | 21.94 | 55.83 | 21.83 | 47.83 | 21.71 |
April | 330.83 | 22.60 | 63.17 | 22.89 | 3.33 | 22.87 |
May | 217.67 | 23.34 | 134.17 | 23.79 | 11.17 | 23.89 |
June | 109.00 | 23.55 | 192.67 | 24.09 | 4.83 | 24.14 |
July | 60.67 | 24.36 | 332.33 | 24.42 | 13.83 | 24.51 |
August | 54.83 | 24.07 | 354.00 | 24.29 | 10.67 | 24.36 |
September | 162.50 | 23.44 | 201.00 | 23.98 | 9.83 | 24.06 |
October | 404.67 | 22.43 | 39.67 | 22.57 | 5.83 | 22.55 |
November | 477.83 | 21.30 | 119.67 | 21.11 | 115.17 | 20.96 |
December | 497.00 | 20.71 | 254.67 | 20.51 | 254.67 | 20.41 |
Annual Sum or Average | 3734.33 | 21.75 | 2232.33 | 22.09 | 962.33 | 21.86 |
Minimum of Months | 54.83 | 20.42 | 39.67 | 20.23 | 3.33 | 20.15 |
Maximum of Months | 502.00 | 24.36 | 354.00 | 24.42 | 311.33 | 24.51 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.24187 | 32.55672 | -0.2280 | 7.61320 |
February | 454.00000 | 23.06914 | 32.84009 | -0.0089 | 5.58773 |
March | 514.00000 | 23.76846 | 31.33682 | 0.17784 | 5.85415 |
April | 485.00000 | 24.10308 | 33.71170 | 0.29920 | 7.10169 |
May | 508.00000 | 24.26706 | 36.98323 | -0.4965 | 10.42439 |
June | 496.00000 | 24.30357 | 38.68473 | -0.4502 | 9.54211 |
July | 497.00000 | 24.38124 | 42.86806 | -0.3860 | 8.50245 |
August | 514.00000 | 24.31397 | 46.02285 | -0.3779 | 8.30513 |
September | 485.00000 | 24.34761 | 43.74093 | -0.4077 | 8.86656 |
October | 502.00000 | 24.14151 | 37.04557 | 0.33403 | 7.56051 |
November | 489.00000 | 23.58152 | 37.36555 | 0.16026 | 6.06793 |
December | 497.00000 | 22.93625 | 32.86732 | -0.0436 | 5.52935 |
Annual Sum or Average | 5943.00000 | 23.79290 | 37.19746 | -0.1206 | 7.59650 |
Minimum of Months | 454.00000 | 22.24187 | 31.33682 | -0.4965 | 5.52935 |
Maximum of Months | 514.00000 | 24.38124 | 46.02285 | 0.33403 | 10.42439 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.21816 | 34.25494 | -0.4554 | 10.69156 |
February | 454.00000 | 21.89468 | 34.86652 | -0.2694 | 7.51913 |
March | 514.00000 | 22.95999 | 33.54775 | -0.0043 | 5.52781 |
April | 485.00000 | 23.61250 | 35.44331 | 0.18618 | 6.22506 |
May | 508.00000 | 23.98863 | 38.23672 | -0.5959 | 12.82169 |
June | 496.00000 | 24.12733 | 39.70238 | -0.5167 | 10.82824 |
July | 497.00000 | 24.24532 | 43.59855 | -0.4414 | 9.35443 |
August | 514.00000 | 24.20144 | 46.82358 | -0.4280 | 9.09365 |
September | 485.00000 | 24.11169 | 44.98293 | -0.4991 | 10.56730 |
October | 502.00000 | 23.51429 | 39.41118 | 0.18452 | 6.26089 |
November | 489.00000 | 22.39575 | 40.14970 | -0.1092 | 6.27974 |
December | 497.00000 | 21.64700 | 35.15926 | -0.3337 | 7.91320 |
Annual Sum or Average | 5943.00000 | 23.16952 | 38.87260 | -0.2743 | 8.60181 |
Minimum of Months | 454.00000 | 21.21816 | 33.54775 | -0.5959 | 5.52781 |
Maximum of Months | 514.00000 | 24.24532 | 46.82358 | 0.18618 | 12.82169 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.68986 | 34.90997 | -0.6016 | 14.48638 |
February | 454.00000 | 21.23970 | 35.59774 | -0.4407 | 10.82813 |
March | 514.00000 | 22.27457 | 34.65091 | -0.1718 | 6.60687 |
April | 485.00000 | 23.16715 | 36.24798 | 0.07790 | 6.11849 |
May | 508.00000 | 23.75066 | 38.77570 | -0.6795 | 15.56483 |
June | 496.00000 | 24.00443 | 39.86625 | -0.5594 | 11.93775 |
July | 497.00000 | 24.14111 | 43.64173 | -0.4743 | 10.05282 |
August | 514.00000 | 24.09844 | 46.83536 | -0.4655 | 9.90444 |
September | 485.00000 | 23.83913 | 45.77069 | -0.6001 | 13.22497 |
October | 502.00000 | 22.85701 | 41.02349 | 0.02185 | 6.04189 |
November | 489.00000 | 21.60679 | 41.88369 | -0.3093 | 8.32228 |
December | 497.00000 | 20.96170 | 36.34798 | -0.5178 | 11.55584 |
Annual Sum or Average | 5943.00000 | 22.73102 | 39.65181 | -0.3936 | 10.38646 |
Minimum of Months | 454.00000 | 20.68986 | 34.65091 | -0.6795 | 6.04189 |
Maximum of Months | 514.00000 | 24.14111 | 46.83536 | 0.07790 | 15.56483 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06883 | 36.21431 | -0.7839 | 20.44706 |
February | 454.00000 | 20.46019 | 36.98072 | -0.6465 | 16.29351 |
March | 514.00000 | 21.31572 | 37.08014 | -0.3936 | 9.74386 |
April | 485.00000 | 22.44243 | 38.04084 | -0.0825 | 7.15104 |
May | 508.00000 | 23.32898 | 40.22777 | -0.8009 | 20.77238 |
June | 496.00000 | 23.79799 | 40.89926 | -0.6081 | 13.84464 |
July | 497.00000 | 23.99277 | 44.19966 | -0.4995 | 11.09698 |
August | 514.00000 | 23.92151 | 47.96482 | -0.5056 | 11.32377 |
September | 485.00000 | 23.37871 | 47.93740 | -0.7483 | 18.59020 |
October | 502.00000 | 21.92464 | 43.96680 | -0.1905 | 7.37831 |
November | 489.00000 | 20.73874 | 43.71031 | -0.5298 | 12.67057 |
December | 497.00000 | 20.24374 | 37.83797 | -0.7220 | 17.59002 |
Annual Sum or Average | 5943.00000 | 22.14817 | 41.27907 | -0.5422 | 13.89055 |
Minimum of Months | 454.00000 | 20.06883 | 36.21431 | -0.8009 | 7.15104 |
Maximum of Months | 514.00000 | 23.99277 | 47.96482 | -0.0825 | 20.77238 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11219 | 37.06971 | -0.7624 | 19.73120 |
February | 454.00000 | 20.72463 | 37.44340 | -0.5709 | 14.39154 |
March | 514.00000 | 21.77730 | 37.07642 | -0.2713 | 8.86863 |
April | 485.00000 | 22.95665 | 36.79033 | 0.06633 | 7.40738 |
May | 508.00000 | 23.59419 | 39.46224 | -0.6668 | 17.48245 |
June | 496.00000 | 24.02776 | 39.95805 | -0.4632 | 11.49251 |
July | 497.00000 | 24.18991 | 43.54876 | -0.3677 | 9.65710 |
August | 514.00000 | 24.11068 | 47.13410 | -0.3664 | 9.54693 |
September | 485.00000 | 23.62704 | 47.11414 | -0.6146 | 15.75650 |
October | 502.00000 | 22.31042 | 43.38048 | -0.0853 | 7.39540 |
November | 489.00000 | 20.87491 | 44.32252 | -0.4887 | 12.07396 |
December | 497.00000 | 20.30745 | 38.66069 | -0.6947 | 16.86711 |
Annual Sum or Average | 5943.00000 | 22.39800 | 41.01649 | -0.4398 | 12.53903 |
Minimum of Months | 454.00000 | 20.11219 | 36.79033 | -0.7624 | 7.39540 |
Maximum of Months | 514.00000 | 24.18991 | 47.13410 | 0.06633 | 19.73120 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.51494 | 35.44005 | -0.6534 | 17.38248 |
February | 454.00000 | 21.30963 | 35.08132 | -0.4174 | 12.64038 |
March | 514.00000 | 22.06071 | 34.85056 | -0.1880 | 9.03326 |
April | 485.00000 | 22.96627 | 35.88401 | 0.07546 | 8.07166 |
May | 508.00000 | 23.51899 | 39.06658 | -0.6911 | 18.79733 |
June | 496.00000 | 23.87736 | 40.20171 | -0.5421 | 13.39641 |
July | 497.00000 | 24.10210 | 43.53381 | -0.4073 | 10.63512 |
August | 514.00000 | 24.04328 | 47.00425 | -0.3902 | 10.33570 |
September | 485.00000 | 23.70598 | 45.99022 | -0.5501 | 14.94018 |
October | 502.00000 | 22.67638 | 41.13937 | 0.02323 | 8.20125 |
November | 489.00000 | 21.31704 | 42.27069 | -0.3765 | 11.21886 |
December | 497.00000 | 20.80102 | 36.61617 | -0.5644 | 15.02966 |
Annual Sum or Average | 5943.00000 | 22.58486 | 39.78512 | -0.3904 | 12.47404 |
Minimum of Months | 454.00000 | 20.51494 | 34.85056 | -0.6911 | 8.07166 |
Maximum of Months | 514.00000 | 24.10210 | 47.00425 | 0.07546 | 18.79733 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14603 | 37.01158 | -0.7555 | 19.68051 |
February | 454.00000 | 20.74395 | 37.27215 | -0.5690 | 14.91813 |
March | 514.00000 | 21.64635 | 36.98724 | -0.3032 | 9.46162 |
April | 485.00000 | 22.72735 | 37.50481 | 0.01013 | 7.87778 |
May | 508.00000 | 23.51376 | 39.87800 | -0.6871 | 19.00266 |
June | 496.00000 | 23.87895 | 40.78716 | -0.5275 | 13.05037 |
July | 497.00000 | 24.13363 | 43.73969 | -0.3705 | 10.27479 |
August | 514.00000 | 24.03596 | 47.58957 | -0.3972 | 10.44509 |
September | 485.00000 | 23.63491 | 47.20168 | -0.6077 | 16.05464 |
October | 502.00000 | 22.21012 | 43.61788 | -0.1093 | 7.57249 |
November | 489.00000 | 20.88729 | 44.30569 | -0.4880 | 12.17812 |
December | 497.00000 | 20.35840 | 38.57059 | -0.6851 | 16.85843 |
Annual Sum or Average | 5943.00000 | 22.33928 | 41.22746 | -0.4570 | 13.10109 |
Minimum of Months | 454.00000 | 20.14603 | 36.98724 | -0.7555 | 7.57249 |
Maximum of Months | 514.00000 | 24.13363 | 47.58957 | 0.01013 | 19.68051 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34417 | 36.16474 | -0.7097 | 17.04770 |
February | 454.00000 | 20.66387 | 37.11310 | -0.5907 | 13.51320 |
March | 514.00000 | 21.32412 | 37.31308 | -0.3908 | 8.81338 |
April | 485.00000 | 22.28839 | 38.89797 | -0.1282 | 6.44008 |
May | 508.00000 | 23.31371 | 41.06877 | -0.8352 | 20.89642 |
June | 496.00000 | 23.81083 | 41.60900 | -0.6357 | 14.00952 |
July | 497.00000 | 24.02108 | 44.71153 | -0.5204 | 11.01557 |
August | 514.00000 | 23.96517 | 48.40098 | -0.5136 | 10.93948 |
September | 485.00000 | 23.58159 | 47.78585 | -0.6905 | 15.85499 |
October | 502.00000 | 22.46511 | 42.84897 | -0.0588 | 5.91847 |
November | 489.00000 | 21.27901 | 42.90631 | -0.3741 | 8.98702 |
December | 497.00000 | 20.60915 | 37.50002 | -0.6081 | 13.29712 |
Annual Sum or Average | 5943.00000 | 22.31827 | 41.38554 | -0.5047 | 12.22821 |
Minimum of Months | 454.00000 | 20.34417 | 36.16474 | -0.8352 | 5.91847 |
Maximum of Months | 514.00000 | 24.02108 | 48.40098 | -0.0588 | 20.89642 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38490 | 37.07964 | -0.6893 | 16.41248 |
February | 454.00000 | 20.93829 | 37.62192 | -0.5110 | 11.68297 |
March | 514.00000 | 21.89664 | 37.27836 | -0.2424 | 7.39218 |
April | 485.00000 | 23.09528 | 37.23955 | 0.08549 | 6.59284 |
May | 508.00000 | 23.70814 | 39.80606 | -0.6590 | 15.96757 |
June | 496.00000 | 24.13646 | 40.06016 | -0.4558 | 10.55182 |
July | 497.00000 | 24.26999 | 43.70962 | -0.3682 | 8.92491 |
August | 514.00000 | 24.20864 | 47.13764 | -0.3488 | 8.60695 |
September | 485.00000 | 23.90235 | 46.58143 | -0.5303 | 12.42807 |
October | 502.00000 | 22.93387 | 42.00329 | 0.06637 | 6.30974 |
November | 489.00000 | 21.46321 | 43.46980 | -0.3232 | 8.49346 |
December | 497.00000 | 20.71061 | 38.31491 | -0.5739 | 12.57986 |
Annual Sum or Average | 5943.00000 | 22.65022 | 40.87788 | -0.3788 | 10.49061 |
Minimum of Months | 454.00000 | 20.38490 | 37.07964 | -0.6893 | 6.30974 |
Maximum of Months | 514.00000 | 24.26999 | 47.13764 | 0.08549 | 16.41248 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36143 | 33.74839 | -0.6633 | 16.12547 |
February | 454.00000 | 21.13390 | 33.90018 | -0.4247 | 10.94003 |
March | 514.00000 | 21.75890 | 33.92337 | -0.2335 | 7.93681 |
April | 485.00000 | 22.61213 | 35.88764 | 0.00097 | 7.14836 |
May | 508.00000 | 23.16991 | 39.61099 | -0.8066 | 21.55576 |
June | 496.00000 | 23.59528 | 40.85419 | -0.6447 | 15.86036 |
July | 497.00000 | 24.02651 | 43.96878 | -0.4497 | 11.00824 |
August | 514.00000 | 23.99085 | 47.39738 | -0.4097 | 10.25346 |
September | 485.00000 | 23.74689 | 45.57291 | -0.5205 | 13.68001 |
October | 502.00000 | 22.93638 | 39.33568 | 0.11218 | 7.47545 |
November | 489.00000 | 21.40614 | 40.06270 | -0.3071 | 9.09420 |
December | 497.00000 | 20.79917 | 34.71091 | -0.5218 | 12.61876 |
Annual Sum or Average | 5943.00000 | 22.47170 | 39.11604 | -0.4063 | 11.99272 |
Minimum of Months | 454.00000 | 20.36143 | 33.74839 | -0.8066 | 7.14836 |
Maximum of Months | 514.00000 | 24.02651 | 47.39738 | 0.11218 | 21.55576 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40793 | 37.05224 | -0.6840 | 16.33020 |
February | 454.00000 | 20.93863 | 37.55505 | -0.5114 | 12.06454 |
March | 514.00000 | 21.79509 | 37.23976 | -0.2674 | 7.79403 |
April | 485.00000 | 22.88357 | 37.81424 | 0.03186 | 6.74150 |
May | 508.00000 | 23.76280 | 39.74994 | -0.6377 | 15.53139 |
June | 496.00000 | 24.03591 | 40.75878 | -0.5058 | 11.40961 |
July | 497.00000 | 24.32862 | 43.41229 | -0.3323 | 8.46671 |
August | 514.00000 | 24.20383 | 47.29672 | -0.3578 | 8.71509 |
September | 485.00000 | 24.01551 | 46.22367 | -0.4911 | 11.56996 |
October | 502.00000 | 22.89218 | 42.15053 | 0.05562 | 6.34989 |
November | 489.00000 | 21.45554 | 43.49181 | -0.3258 | 8.60453 |
December | 497.00000 | 20.72829 | 38.28851 | -0.5700 | 12.61707 |
Annual Sum or Average | 5943.00000 | 22.63346 | 40.93926 | -0.3827 | 10.51065 |
Minimum of Months | 454.00000 | 20.40793 | 37.05224 | -0.6840 | 6.34989 |
Maximum of Months | 514.00000 | 24.32862 | 47.29672 | 0.05562 | 16.33020 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32836 | 35.92146 | -0.6929 | 16.87467 |
February | 454.00000 | 20.78196 | 36.53412 | -0.5411 | 12.89729 |
March | 514.00000 | 21.78926 | 36.31423 | -0.2656 | 7.50395 |
April | 485.00000 | 22.85233 | 37.32558 | 0.01945 | 6.32350 |
May | 508.00000 | 23.61704 | 39.56522 | -0.7040 | 16.60776 |
June | 496.00000 | 23.95385 | 40.55327 | -0.5561 | 11.96713 |
July | 497.00000 | 24.11514 | 44.01352 | -0.4606 | 9.82498 |
August | 514.00000 | 24.04947 | 47.73261 | -0.4619 | 9.92764 |
September | 485.00000 | 23.70337 | 46.99781 | -0.6349 | 14.39319 |
October | 502.00000 | 22.51805 | 42.56237 | -0.0408 | 6.18942 |
November | 489.00000 | 21.20631 | 42.79997 | -0.3910 | 9.56457 |
December | 497.00000 | 20.56986 | 37.29617 | -0.6092 | 13.62313 |
Annual Sum or Average | 5943.00000 | 22.47037 | 40.65892 | -0.4447 | 11.29803 |
Minimum of Months | 454.00000 | 20.32836 | 35.92146 | -0.7040 | 6.18942 |
Maximum of Months | 514.00000 | 24.11514 | 47.73261 | 0.01945 | 16.87467 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.25982 | 36.52073 | -0.7013 | 17.29031 |
February | 385.00000 | 20.99222 | 36.61116 | -0.4849 | 11.91881 |
March | 433.00000 | 22.10412 | 36.06122 | -0.1813 | 7.32061 |
April | 410.00000 | 23.22399 | 35.86238 | 0.12819 | 6.97658 |
May | 430.00000 | 23.80512 | 38.54577 | -0.6081 | 15.00937 |
June | 418.00000 | 24.16689 | 39.51183 | -0.4317 | 10.53544 |
July | 422.00000 | 24.34318 | 43.00829 | -0.3372 | 8.94972 |
August | 433.00000 | 24.24296 | 46.60433 | -0.3393 | 8.88929 |
September | 410.00000 | 23.88819 | 46.00200 | -0.5340 | 12.93683 |
October | 427.00000 | 22.75415 | 41.88886 | 0.02627 | 6.60953 |
November | 417.00000 | 21.28689 | 43.12698 | -0.3673 | 9.53249 |
December | 422.00000 | 20.58138 | 37.89324 | -0.5995 | 13.61996 |
Annual Sum or Average | 5034.00000 | 22.64720 | 40.15689 | -0.3689 | 10.79353 |
Minimum of Months | 385.00000 | 20.25982 | 35.86238 | -0.7013 | 6.60953 |
Maximum of Months | 433.00000 | 24.34318 | 46.60433 | 0.12819 | 17.29031 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.85223 | 35.01530 | -0.5476 | 14.17395 |
February | 454.00000 | 21.69919 | 34.46175 | -0.3004 | 10.17517 |
March | 514.00000 | 22.51399 | 34.00108 | -0.0657 | 7.40537 |
April | 485.00000 | 23.32641 | 35.17361 | 0.16683 | 7.55200 |
May | 508.00000 | 23.79059 | 38.42437 | -0.5995 | 14.88782 |
June | 496.00000 | 24.03787 | 39.84572 | -0.4896 | 11.39607 |
July | 497.00000 | 24.23258 | 43.30455 | -0.3671 | 9.22446 |
August | 514.00000 | 24.16867 | 46.76441 | -0.3483 | 8.96263 |
September | 485.00000 | 23.97860 | 45.19326 | -0.4522 | 11.54280 |
October | 502.00000 | 23.17998 | 39.85824 | 0.15430 | 7.74322 |
November | 489.00000 | 21.82711 | 41.23765 | -0.2305 | 8.88678 |
December | 497.00000 | 21.21597 | 35.87224 | -0.4360 | 11.60953 |
Annual Sum or Average | 5943.00000 | 22.91153 | 39.12547 | -0.2935 | 10.29979 |
Minimum of Months | 454.00000 | 20.85223 | 34.00108 | -0.5995 | 7.40537 |
Maximum of Months | 514.00000 | 24.23258 | 46.76441 | 0.16683 | 14.88782 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41605 | 36.71874 | -0.6627 | 16.19909 |
February | 454.00000 | 21.07868 | 36.76565 | -0.4619 | 11.82873 |
March | 514.00000 | 22.11486 | 36.14039 | -0.1772 | 7.43936 |
April | 485.00000 | 23.12820 | 36.74048 | 0.10967 | 7.17770 |
May | 508.00000 | 23.79797 | 39.16600 | -0.5918 | 14.92606 |
June | 496.00000 | 24.03964 | 40.38806 | -0.4747 | 11.06969 |
July | 497.00000 | 24.26281 | 43.48892 | -0.3304 | 8.91129 |
August | 514.00000 | 24.16463 | 47.31656 | -0.3539 | 9.05037 |
September | 485.00000 | 23.93169 | 46.26614 | -0.5028 | 12.33698 |
October | 502.00000 | 22.77714 | 42.21134 | 0.03464 | 6.65411 |
November | 489.00000 | 21.36083 | 43.34750 | -0.3487 | 9.30295 |
December | 497.00000 | 20.70627 | 37.98931 | -0.5689 | 13.03538 |
Annual Sum or Average | 5943.00000 | 22.66070 | 40.56705 | -0.3605 | 10.65330 |
Minimum of Months | 454.00000 | 20.41605 | 36.14039 | -0.6627 | 6.65411 |
Maximum of Months | 514.00000 | 24.26281 | 47.31656 | 0.10967 | 16.19909 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.153466E+09 | 40340009.80 | 8.04 | 0.129906E+09 | 23559664.53 | 0.00 | 0.41 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 9264.50 | 27-FEB-15:00 | 8747.95 | 27-FEB-15:00 | 1268.03 | 27-FEB-17:10 | 2366.49 | 27-FEB-15:00 | 0.00 |
March | 0.241679E+09 | 64704698.98 | 22.19 | 0.208106E+09 | 33573403.89 | 0.00 | 0.39 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 8669.36 | 18-MAR-16:00 | 8669.36 | 18-MAR-16:00 | 1256.25 | 09-MAR-12:00 | 2227.99 | 18-MAR-16:00 | 0.00 |
April | 0.299937E+10 | 0.721826E+09 | 72.24 | 0.286476E+10 | 0.134604E+09 | 0.00 | 1.00 | 26-APR-13:30 | 0.00 | 01-APR-00:10 | 43642.71 | 27-APR-15:10 | 43642.71 | 27-APR-15:10 | 3636.13 | 28-APR-13:00 | 10311.62 | 27-APR-15:10 | 0.00 |
May | 0.632180E+10 | 0.150837E+10 | 158.81 | 0.558671E+10 | 0.735090E+09 | 0.00 | 1.00 | 04-MAY-12:50 | 0.00 | 01-MAY-00:10 | 39122.75 | 15-MAY-16:00 | 39122.75 | 15-MAY-16:00 | 5238.81 | 05-MAY-18:00 | 8526.00 | 15-MAY-16:00 | 0.00 |
June | 0.120750E+11 | 0.286925E+10 | 261.29 | 0.111838E+11 | 0.891258E+09 | 0.00 | 1.00 | 09-JUN-14:00 | 0.00 | 01-JUN-00:10 | 45213.25 | 28-JUN-15:30 | 45213.25 | 28-JUN-15:30 | 8366.44 | 12-JUN-06:02 | 10383.91 | 28-JUN-15:30 | 0.00 |
July | 0.235073E+11 | 0.548968E+10 | 345.57 | 0.207453E+11 | 0.276205E+10 | 0.00 | 1.00 | 06-JUL-14:50 | 0.00 | 01-JUL-00:10 | 61655.09 | 31-JUL-16:00 | 57516.25 | 24-JUL-15:10 | 14243.80 | 31-JUL-06:03 | 15497.86 | 24-JUL-15:10 | 0.00 |
August | 0.322120E+11 | 0.756122E+10 | 374.35 | 0.281689E+11 | 0.404308E+10 | 0.00 | 1.00 | 07-AUG-09:00 | 0.00 | 01-AUG-00:10 | 62695.59 | 10-AUG-16:10 | 58989.82 | 10-AUG-15:50 | 15110.00 | 30-AUG-13:00 | 16399.66 | 10-AUG-16:10 | 0.00 |
September | 0.118529E+11 | 0.276043E+10 | 228.34 | 0.988592E+10 | 0.196695E+10 | 0.00 | 1.00 | 08-SEP-14:00 | 0.00 | 01-SEP-00:10 | 49895.81 | 14-SEP-13:00 | 47263.94 | 12-SEP-15:10 | 13425.33 | 14-SEP-13:00 | 10919.44 | 12-SEP-16:00 | 0.00 |
October | 0.167275E+10 | 0.416172E+09 | 69.69 | 0.156542E+10 | 0.107328E+09 | 0.00 | 1.00 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 | 29428.52 | 04-OCT-15:10 | 29428.52 | 04-OCT-15:10 | 2518.46 | 08-OCT-14:00 | 6399.29 | 04-OCT-15:10 | 0.00 |
November | 0.298228E+09 | 73664517.85 | 7.67 | 0.199938E+09 | 98289759.23 | 0.00 | 0.65 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 15619.93 | 04-NOV-14:30 | 11401.77 | 04-NOV-14:30 | 4716.17 | 04-NOV-13:00 | 3747.02 | 04-NOV-14:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.913345E+11 | 0.215057E+11 | 1548.19 | 0.805387E+11 | 0.107958E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.322120E+11 | 0.756122E+10 | 374.35 | 0.281689E+11 | 0.404308E+10 | 0.00 | 1.00 | 0.00 | 62695.59 | 58989.82 | 15110.00 | 16399.66 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.171996E+09 | 44644388.23 | 8.00 | 0.156607E+09 | 15389933.31 | 0.00 | 0.51 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 11209.27 | 27-FEB-15:10 | 11209.27 | 27-FEB-15:10 | 1176.68 | 27-FEB-17:13 | 2793.44 | 27-FEB-15:10 | 0.00 |
March | 0.263744E+09 | 69804412.57 | 22.64 | 0.234829E+09 | 28914669.66 | 0.00 | 0.47 | 18-MAR-14:05 | 0.00 | 01-MAR-00:10 | 10336.84 | 18-MAR-14:05 | 10336.84 | 18-MAR-14:05 | 1171.31 | 09-MAR-12:00 | 2599.61 | 18-MAR-14:05 | 0.00 |
April | 0.315794E+10 | 0.755381E+09 | 71.94 | 0.303555E+10 | 0.122393E+09 | 0.00 | 1.00 | 26-APR-13:10 | 0.00 | 01-APR-00:10 | 46804.27 | 27-APR-14:05 | 46804.27 | 27-APR-14:05 | 3931.95 | 28-APR-13:00 | 10825.34 | 27-APR-15:00 | 0.00 |
May | 0.658760E+10 | 0.156016E+10 | 162.09 | 0.590408E+10 | 0.683519E+09 | 0.00 | 1.00 | 04-MAY-12:30 | 0.00 | 01-MAY-00:10 | 40885.32 | 04-MAY-15:00 | 40885.32 | 04-MAY-15:00 | 6694.98 | 07-MAY-15:32 | 9011.58 | 04-MAY-15:00 | 0.00 |
June | 0.121103E+11 | 0.286885E+10 | 269.93 | 0.112738E+11 | 0.836532E+09 | 0.00 | 1.00 | 09-JUN-13:10 | 0.00 | 01-JUN-00:10 | 45571.99 | 28-JUN-15:20 | 45571.99 | 28-JUN-15:20 | 7875.93 | 12-JUN-06:02 | 10464.76 | 28-JUN-15:20 | 0.00 |
July | 0.230205E+11 | 0.536643E+10 | 353.52 | 0.204493E+11 | 0.257127E+10 | 0.00 | 1.00 | 06-JUL-14:30 | 0.00 | 01-JUL-00:10 | 63791.86 | 31-JUL-14:05 | 57029.56 | 31-JUL-14:05 | 15608.92 | 31-JUL-06:03 | 15425.55 | 31-JUL-14:05 | 0.00 |
August | 0.303617E+11 | 0.713226E+10 | 375.58 | 0.266374E+11 | 0.372428E+10 | 0.00 | 1.00 | 04-AUG-14:05 | 0.00 | 01-AUG-00:10 | 63286.44 | 10-AUG-14:05 | 57233.31 | 10-AUG-15:10 | 14694.97 | 30-AUG-13:00 | 16144.42 | 29-AUG-15:00 | 0.00 |
September | 0.113887E+11 | 0.265089E+10 | 231.81 | 0.951608E+10 | 0.187260E+10 | 0.00 | 1.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 | 50647.38 | 13-SEP-14:05 | 46725.21 | 12-SEP-14:05 | 13973.28 | 14-SEP-13:00 | 11055.94 | 13-SEP-14:05 | 0.00 |
October | 0.143027E+10 | 0.351827E+09 | 57.28 | 0.134291E+10 | 87359928.45 | 0.00 | 1.00 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 | 29245.80 | 04-OCT-15:00 | 29245.80 | 04-OCT-15:00 | 4064.68 | 08-OCT-13:02 | 6359.12 | 04-OCT-15:00 | 0.00 |
November | 0.324191E+09 | 78739226.66 | 7.67 | 0.227850E+09 | 96341430.64 | 0.00 | 0.74 | 04-NOV-14:05 | 0.00 | 01-NOV-00:10 | 17413.29 | 04-NOV-14:05 | 13606.47 | 04-NOV-14:05 | 4596.54 | 04-NOV-16:00 | 4076.52 | 04-NOV-14:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.888169E+11 | 0.208790E+11 | 1560.47 | 0.787783E+11 | 0.100386E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.303617E+11 | 0.713226E+10 | 375.58 | 0.266374E+11 | 0.372428E+10 | 0.00 | 1.00 | 0.00 | 63791.86 | 57233.31 | 15608.92 | 16144.42 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.178697E+09 | 46645749.08 | 8.00 | 0.157962E+09 | 20734364.43 | 0.00 | 0.47 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 11363.51 | 27-FEB-15:00 | 11363.51 | 27-FEB-15:00 | 1371.37 | 27-FEB-17:10 | 2862.31 | 27-FEB-15:00 | 0.00 |
March | 0.374237E+09 | 99383480.94 | 27.23 | 0.338995E+09 | 35241167.79 | 0.00 | 0.43 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 10258.88 | 18-MAR-16:00 | 10258.88 | 18-MAR-16:00 | 1288.18 | 09-MAR-12:00 | 2611.24 | 18-MAR-16:00 | 0.00 |
April | 0.337367E+10 | 0.809259E+09 | 71.08 | 0.321797E+10 | 0.155699E+09 | 0.00 | 1.00 | 26-APR-13:20 | 0.00 | 01-APR-00:10 | 53302.37 | 27-APR-14:40 | 53302.37 | 27-APR-14:40 | 3804.54 | 28-APR-13:00 | 12514.04 | 27-APR-15:00 | 0.00 |
May | 0.699082E+10 | 0.165909E+10 | 161.29 | 0.620557E+10 | 0.785255E+09 | 0.00 | 1.00 | 04-MAY-12:40 | 0.00 | 01-MAY-00:10 | 44774.13 | 04-MAY-15:00 | 44774.13 | 04-MAY-15:00 | 6126.32 | 07-MAY-17:02 | 9869.18 | 04-MAY-15:00 | 0.00 |
June | 0.128638E+11 | 0.305676E+10 | 268.75 | 0.118833E+11 | 0.980491E+09 | 0.00 | 1.00 | 09-JUN-13:20 | 0.00 | 01-JUN-00:10 | 53282.03 | 28-JUN-15:20 | 53282.03 | 28-JUN-15:20 | 5058.50 | 12-JUN-12:40 | 12233.53 | 28-JUN-15:20 | 0.00 |
July | 0.246341E+11 | 0.576260E+10 | 352.20 | 0.216866E+11 | 0.294751E+10 | 0.00 | 1.00 | 06-JUL-14:50 | 0.00 | 01-JUL-00:10 | 70028.74 | 31-JUL-14:40 | 63984.42 | 24-JUL-14:00 | 11974.56 | 31-JUL-10:30 | 17230.09 | 24-JUL-15:00 | 0.00 |
August | 0.321963E+11 | 0.760406E+10 | 375.06 | 0.281259E+11 | 0.407038E+10 | 0.00 | 1.00 | 06-AUG-15:32 | 0.00 | 01-AUG-00:10 | 70120.95 | 10-AUG-14:50 | 65732.51 | 10-AUG-15:20 | 14876.85 | 30-AUG-13:00 | 17888.28 | 29-AUG-15:20 | 0.00 |
September | 0.115020E+11 | 0.269379E+10 | 228.72 | 0.948223E+10 | 0.201973E+10 | 0.00 | 1.00 | 08-SEP-14:00 | 0.00 | 01-SEP-00:10 | 50356.14 | 14-SEP-13:30 | 46939.64 | 12-SEP-15:00 | 13529.28 | 14-SEP-13:00 | 11001.77 | 14-SEP-13:30 | 0.00 |
October | 0.132918E+10 | 0.331752E+09 | 54.67 | 0.122942E+10 | 99765641.27 | 0.00 | 1.00 | 04-OCT-14:50 | 0.00 | 01-OCT-00:10 | 28620.45 | 04-OCT-15:00 | 28620.45 | 04-OCT-15:00 | 3329.52 | 08-OCT-13:02 | 6224.55 | 04-OCT-15:00 | 0.00 |
November | 0.331765E+09 | 81432879.65 | 7.67 | 0.225674E+09 | 0.106091E+09 | 0.00 | 0.69 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 | 17781.58 | 04-NOV-14:10 | 13289.64 | 04-NOV-14:10 | 5126.77 | 04-NOV-13:00 | 4223.51 | 04-NOV-14:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.937745E+11 | 0.221448E+11 | 1554.68 | 0.825536E+11 | 0.112209E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.321963E+11 | 0.760406E+10 | 375.06 | 0.281259E+11 | 0.407038E+10 | 0.00 | 1.00 | 0.00 | 70120.95 | 65732.51 | 14876.85 | 17888.28 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 11.89 | 1383.33 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 86.62 | 1226.02 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 249.31 | 1021.07 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 520.74 | 833.78 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 823.66 | 687.85 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 952.30 | 534.00 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1023.35 | 481.14 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 844.18 | 470.27 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 489.41 | 699.28 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 208.28 | 908.97 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 46.47 | 1113.43 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 6.72 | 1390.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 440.77 | 894.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 6.72 | 470.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1023.35 | 1390.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 97.42 | 875.41 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 320.31 | 773.55 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 596.81 | 655.38 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1113.72 | 539.78 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1239.34 | 464.61 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1593.39 | 366.12 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1550.69 | 323.72 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1577.30 | 315.49 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1038.64 | 452.43 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 566.72 | 588.24 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 167.79 | 716.64 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 121.65 | 889.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 834.58 | 579.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 97.42 | 315.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1593.39 | 889.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 958.43 | 1255.72 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1678.56 | 1144.02 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1878.74 | 1015.86 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2092.76 | 879.04 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1926.43 | 746.42 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1797.44 | 593.34 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2165.91 | 537.62 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2407.58 | 518.51 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2505.39 | 717.83 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2081.33 | 906.74 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1044.11 | 1058.92 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1118.97 | 1296.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1805.07 | 887.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 958.43 | 518.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2505.39 | 1296.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 121.43 | 882.60 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 353.53 | 785.26 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 582.27 | 670.22 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1053.71 | 567.58 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1475.51 | 487.23 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1449.05 | 385.87 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1963.78 | 354.41 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1649.18 | 344.65 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1236.20 | 478.43 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 570.08 | 605.36 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 175.76 | 720.79 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 142.94 | 898.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 901.37 | 597.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 121.43 | 344.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1963.78 | 898.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.74 | 478.11 | 0.00 | 0.00 | 0.00 |
February | 124.59 | 0.00 | 124.59 | 29.11 | 422.86 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 86.61 | 345.83 | 0.00 | 0.00 | 0.00 |
April | 259.76 | 0.92 | 258.84 | 181.93 | 277.02 | 0.00 | 0.00 | 0.00 |
May | 334.25 | 9.93 | 324.32 | 283.48 | 229.42 | 0.00 | 0.00 | 0.00 |
June | 351.46 | 23.21 | 328.25 | 325.59 | 178.00 | 0.00 | 0.00 | 0.00 |
July | 334.04 | 26.19 | 307.85 | 348.02 | 160.86 | 0.00 | 0.00 | 0.00 |
August | 270.41 | 7.31 | 263.10 | 286.24 | 158.26 | 0.00 | 0.00 | 0.00 |
September | 210.04 | 0.06 | 209.98 | 164.92 | 240.72 | 0.00 | 0.00 | 0.00 |
October | 143.91 | 0.00 | 143.91 | 66.45 | 324.66 | 0.00 | 0.00 | 0.00 |
November | 90.65 | 0.00 | 90.65 | 13.40 | 401.92 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.62 | 491.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.63 | 5.68 | 198.95 | 150.00 | 308.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.62 | 158.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.46 | 26.19 | 328.25 | 348.02 | 491.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.74 | 478.14 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 29.11 | 422.88 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 86.61 | 345.85 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 181.94 | 277.04 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 283.49 | 229.44 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 325.60 | 178.01 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 348.03 | 160.87 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 286.25 | 158.27 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 164.93 | 240.73 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 66.45 | 324.68 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 13.40 | 401.95 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.62 | 491.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 150.01 | 308.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.62 | 158.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 348.03 | 491.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.74 | 478.14 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 29.11 | 422.88 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 86.61 | 345.85 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 181.94 | 277.04 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 283.49 | 229.44 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 325.60 | 178.01 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 348.03 | 160.87 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 286.25 | 158.27 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 164.93 | 240.73 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 66.45 | 324.68 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 13.40 | 401.95 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.62 | 491.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 150.01 | 308.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.62 | 158.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 348.03 | 491.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.55 | 62.76 | 184.78 | 92.43 | 873.48 | 0.00 | 0.00 | 0.00 |
February | 454.22 | 161.21 | 293.01 | 308.30 | 773.94 | 0.00 | 0.00 | 0.00 |
March | 678.19 | 245.51 | 432.68 | 580.97 | 650.66 | 0.00 | 0.00 | 0.00 |
April | 1051.30 | 436.83 | 614.47 | 1082.22 | 534.00 | 0.00 | 0.00 | 0.00 |
May | 1118.68 | 388.94 | 729.74 | 1205.45 | 457.33 | 0.00 | 0.00 | 0.00 |
June | 1339.75 | 582.93 | 756.82 | 1546.05 | 363.19 | 0.00 | 0.00 | 0.00 |
July | 1247.62 | 560.00 | 687.62 | 1503.56 | 319.89 | 0.00 | 0.00 | 0.00 |
August | 1226.23 | 613.43 | 612.80 | 1525.83 | 316.05 | 0.00 | 0.00 | 0.00 |
September | 906.62 | 418.14 | 488.48 | 1001.27 | 458.82 | 0.00 | 0.00 | 0.00 |
October | 590.93 | 251.09 | 339.84 | 538.36 | 615.57 | 0.00 | 0.00 | 0.00 |
November | 289.64 | 81.77 | 207.87 | 154.64 | 748.92 | 0.00 | 0.00 | 0.00 |
December | 237.57 | 76.48 | 161.09 | 113.26 | 907.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 783.80 | 323.97 | 459.83 | 806.89 | 584.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.57 | 62.76 | 161.09 | 92.43 | 316.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1339.75 | 613.43 | 756.82 | 1546.05 | 907.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.79 | 2.48 | 7.31 | 3.65 | 34.54 | 0.00 | 0.00 | 0.00 |
February | 17.96 | 6.37 | 11.59 | 12.19 | 30.60 | 0.00 | 0.00 | 0.00 |
March | 26.81 | 9.71 | 17.11 | 22.97 | 25.73 | 0.00 | 0.00 | 0.00 |
April | 41.57 | 17.27 | 24.30 | 42.79 | 21.11 | 0.00 | 0.00 | 0.00 |
May | 44.23 | 15.38 | 28.85 | 47.66 | 18.08 | 0.00 | 0.00 | 0.00 |
June | 52.97 | 23.05 | 29.92 | 61.13 | 14.36 | 0.00 | 0.00 | 0.00 |
July | 49.33 | 22.14 | 27.19 | 59.45 | 12.65 | 0.00 | 0.00 | 0.00 |
August | 48.48 | 24.25 | 24.23 | 60.33 | 12.50 | 0.00 | 0.00 | 0.00 |
September | 35.85 | 16.53 | 19.31 | 39.59 | 18.14 | 0.00 | 0.00 | 0.00 |
October | 23.36 | 9.93 | 13.44 | 21.29 | 24.34 | 0.00 | 0.00 | 0.00 |
November | 11.45 | 3.23 | 8.22 | 6.11 | 29.61 | 0.00 | 0.00 | 0.00 |
December | 9.39 | 3.02 | 6.37 | 4.48 | 35.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.99 | 12.81 | 18.18 | 31.90 | 23.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.39 | 2.48 | 6.37 | 3.65 | 12.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.97 | 24.25 | 29.92 | 61.13 | 35.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 322.86 | 434.03 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 564.85 | 400.98 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 635.84 | 352.26 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 710.31 | 298.28 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 656.01 | 250.60 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 612.33 | 198.55 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 731.63 | 182.99 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 810.07 | 179.50 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 839.64 | 253.96 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 695.19 | 330.68 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 347.83 | 381.60 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 373.91 | 457.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 608.52 | 309.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 322.86 | 179.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 839.64 | 457.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 322.86 | 434.03 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 564.85 | 400.98 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 635.84 | 352.26 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 710.31 | 298.28 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 656.01 | 250.60 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 612.33 | 198.55 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 731.63 | 182.99 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 810.07 | 179.50 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 839.64 | 253.96 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 695.19 | 330.68 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 347.83 | 381.60 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 373.91 | 457.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 608.52 | 309.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 322.86 | 179.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 839.64 | 457.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.76 | 210.07 | 143.70 | 322.84 | 434.01 | 0.00 | 0.00 | 0.00 |
February | 544.03 | 336.76 | 207.27 | 564.81 | 400.96 | 0.00 | 0.00 | 0.00 |
March | 585.22 | 312.09 | 273.13 | 635.80 | 352.24 | 0.00 | 0.00 | 0.00 |
April | 617.88 | 268.28 | 349.60 | 710.27 | 298.26 | 0.00 | 0.00 | 0.00 |
May | 564.98 | 168.31 | 396.67 | 655.97 | 250.59 | 0.00 | 0.00 | 0.00 |
June | 516.90 | 138.78 | 378.12 | 612.29 | 198.54 | 0.00 | 0.00 | 0.00 |
July | 563.70 | 206.46 | 357.25 | 731.59 | 182.97 | 0.00 | 0.00 | 0.00 |
August | 605.63 | 282.41 | 323.21 | 810.02 | 179.49 | 0.00 | 0.00 | 0.00 |
September | 671.01 | 370.55 | 300.46 | 839.59 | 253.95 | 0.00 | 0.00 | 0.00 |
October | 607.82 | 375.28 | 232.54 | 695.15 | 330.66 | 0.00 | 0.00 | 0.00 |
November | 359.36 | 205.94 | 153.42 | 347.81 | 381.57 | 0.00 | 0.00 | 0.00 |
December | 376.00 | 243.32 | 132.67 | 373.88 | 457.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.30 | 259.38 | 270.92 | 608.48 | 309.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.76 | 138.78 | 132.67 | 322.84 | 179.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.01 | 375.28 | 396.67 | 839.59 | 457.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 261.10 | 76.99 | 184.11 | 118.03 | 882.16 | 0.00 | 0.00 | 0.00 |
February | 468.13 | 175.94 | 292.20 | 344.15 | 787.92 | 0.00 | 0.00 | 0.00 |
March | 655.97 | 221.41 | 434.57 | 569.33 | 667.38 | 0.00 | 0.00 | 0.00 |
April | 998.00 | 381.57 | 616.42 | 1029.48 | 560.24 | 0.00 | 0.00 | 0.00 |
May | 1284.19 | 521.69 | 762.49 | 1435.33 | 485.91 | 0.00 | 0.00 | 0.00 |
June | 1235.04 | 479.52 | 755.51 | 1410.54 | 383.12 | 0.00 | 0.00 | 0.00 |
July | 1525.72 | 801.99 | 723.73 | 1903.25 | 358.00 | 0.00 | 0.00 | 0.00 |
August | 1262.13 | 644.48 | 617.65 | 1597.19 | 348.32 | 0.00 | 0.00 | 0.00 |
September | 1027.82 | 493.17 | 534.65 | 1192.47 | 490.08 | 0.00 | 0.00 | 0.00 |
October | 585.14 | 238.42 | 346.72 | 543.40 | 635.04 | 0.00 | 0.00 | 0.00 |
November | 291.40 | 82.19 | 209.21 | 164.13 | 754.27 | 0.00 | 0.00 | 0.00 |
December | 244.97 | 83.95 | 161.03 | 136.64 | 918.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.11 | 351.44 | 470.67 | 873.79 | 605.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 244.97 | 76.99 | 161.03 | 118.03 | 348.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1525.72 | 801.99 | 762.49 | 1903.25 | 918.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.32 | 3.04 | 7.28 | 4.67 | 34.88 | 0.00 | 0.00 | 0.00 |
February | 18.51 | 6.96 | 11.55 | 13.61 | 31.15 | 0.00 | 0.00 | 0.00 |
March | 25.94 | 8.75 | 17.18 | 22.51 | 26.39 | 0.00 | 0.00 | 0.00 |
April | 39.46 | 15.09 | 24.37 | 40.70 | 22.15 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 20.63 | 30.15 | 56.75 | 19.21 | 0.00 | 0.00 | 0.00 |
June | 48.83 | 18.96 | 29.87 | 55.77 | 15.15 | 0.00 | 0.00 | 0.00 |
July | 60.33 | 31.71 | 28.62 | 75.25 | 14.16 | 0.00 | 0.00 | 0.00 |
August | 49.90 | 25.48 | 24.42 | 63.15 | 13.77 | 0.00 | 0.00 | 0.00 |
September | 40.64 | 19.50 | 21.14 | 47.15 | 19.38 | 0.00 | 0.00 | 0.00 |
October | 23.14 | 9.43 | 13.71 | 21.49 | 25.11 | 0.00 | 0.00 | 0.00 |
November | 11.52 | 3.25 | 8.27 | 6.49 | 29.82 | 0.00 | 0.00 | 0.00 |
December | 9.69 | 3.32 | 6.37 | 5.40 | 36.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.51 | 13.90 | 18.61 | 34.55 | 23.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.69 | 3.04 | 6.37 | 4.67 | 13.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.33 | 31.71 | 30.15 | 75.25 | 36.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 9.69 | 1454.00 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 78.55 | 1300.04 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 234.45 | 1088.55 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 506.92 | 880.90 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 813.92 | 719.55 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 947.90 | 553.80 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1021.83 | 498.01 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 841.21 | 488.65 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 480.10 | 738.30 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 191.60 | 981.17 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 38.57 | 1199.42 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 4.44 | 1477.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 432.97 | 946.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 4.44 | 488.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1021.83 | 1477.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 92.72 | 919.34 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 308.64 | 820.21 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 581.89 | 698.25 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1101.28 | 567.72 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1231.32 | 484.57 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1589.47 | 378.85 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1547.24 | 334.05 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1573.51 | 326.66 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1029.92 | 475.82 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 551.96 | 632.74 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 157.54 | 772.30 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 115.32 | 944.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 826.03 | 611.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 92.72 | 326.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1589.47 | 944.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 945.73 | 1320.79 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1660.92 | 1211.10 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1864.77 | 1080.22 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2082.86 | 924.41 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1921.81 | 779.97 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1797.63 | 615.98 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2167.94 | 556.37 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2408.82 | 538.15 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2498.78 | 753.68 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2065.63 | 971.53 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1026.24 | 1136.74 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1105.19 | 1376.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1796.02 | 937.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 945.73 | 538.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2498.78 | 1376.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 118.09 | 927.79 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 346.05 | 832.16 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 572.60 | 714.14 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1045.92 | 598.51 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1472.17 | 509.71 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1449.45 | 400.94 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1965.92 | 367.11 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1649.96 | 357.91 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1231.66 | 503.31 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 559.41 | 651.86 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 168.13 | 775.51 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 139.21 | 954.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 896.83 | 631.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 118.09 | 357.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1965.92 | 954.86 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 31846178.33 | 0.370512E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.209557E+09 | 0.296599E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.667765E+09 | 0.273485E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.134976E+10 | 0.216115E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.220610E+10 | 0.184235E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.246837E+10 | 0.138412E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.274094E+10 | 0.128868E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.226106E+10 | 0.125958E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.126855E+10 | 0.181253E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.557849E+09 | 0.243460E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.120452E+09 | 0.288602E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 17992985.96 | 0.372311E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.139003E+11 | 0.281981E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 17992985.96 | 0.125958E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.274094E+10 | 0.372311E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.260942E+09 | 0.234470E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.774892E+09 | 0.187137E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.159851E+10 | 0.175538E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.288675E+10 | 0.139912E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.331945E+10 | 0.124442E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.413007E+10 | 0.948980E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.415337E+10 | 0.867052E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.422465E+10 | 0.845002E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.269215E+10 | 0.117270E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.151790E+10 | 0.157555E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.434921E+09 | 0.185754E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.325817E+09 | 0.238218E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.263194E+11 | 0.182640E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.260942E+09 | 0.845002E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.422465E+10 | 0.238218E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.256706E+10 | 0.336332E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.406078E+10 | 0.276762E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.503203E+10 | 0.272087E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.542444E+10 | 0.227847E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.515974E+10 | 0.199922E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.465896E+10 | 0.153795E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.580119E+10 | 0.143997E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.644846E+10 | 0.138879E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.649398E+10 | 0.186060E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.557463E+10 | 0.242861E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.270633E+10 | 0.274472E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.299705E+10 | 0.347314E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.569246E+11 | 0.280033E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.256706E+10 | 0.138879E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.649398E+10 | 0.347314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.325239E+09 | 0.236396E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.855269E+09 | 0.189971E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.155956E+10 | 0.179512E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.273122E+10 | 0.147118E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.395201E+10 | 0.130499E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.375593E+10 | 0.100018E+10 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.525980E+10 | 0.949258E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441717E+10 | 0.923113E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.320423E+10 | 0.124009E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.152689E+10 | 0.162140E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.455570E+09 | 0.186828E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.382844E+09 | 0.240751E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.284257E+11 | 0.188448E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.325239E+09 | 0.923113E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.525980E+10 | 0.240751E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214460E+09 | 0.00 | 0.214460E+09 | 10010576.24 | 0.128058E+10 |
February | 0.301411E+09 | 0.00 | 0.301411E+09 | 70430071.91 | 0.102297E+10 |
March | 0.491662E+09 | 0.00 | 0.491662E+09 | 0.231974E+09 | 0.926271E+09 |
April | 0.673308E+09 | 2388428.59 | 0.670920E+09 | 0.471566E+09 | 0.718038E+09 |
May | 0.895257E+09 | 26596794.15 | 0.868661E+09 | 0.759281E+09 | 0.614489E+09 |
June | 0.910975E+09 | 60156990.47 | 0.850818E+09 | 0.843936E+09 | 0.461378E+09 |
July | 0.894693E+09 | 70148169.12 | 0.824545E+09 | 0.932131E+09 | 0.430843E+09 |
August | 0.724260E+09 | 19578934.08 | 0.704681E+09 | 0.766673E+09 | 0.423890E+09 |
September | 0.544432E+09 | 160544.72 | 0.544271E+09 | 0.427473E+09 | 0.623936E+09 |
October | 0.385461E+09 | 0.00 | 0.385461E+09 | 0.177983E+09 | 0.869566E+09 |
November | 0.234970E+09 | 0.00 | 0.234970E+09 | 34741611.67 | 0.104178E+10 |
December | 0.182235E+09 | 0.00 | 0.182235E+09 | 4348955.88 | 0.131509E+10 |
Annual Sum or Average | 0.645312E+10 | 0.179030E+09 | 0.627410E+10 | 0.473055E+10 | 0.972883E+10 |
Minimum of Months | 0.182235E+09 | 0.00 | 0.182235E+09 | 4348955.88 | 0.423890E+09 |
Maximum of Months | 0.910975E+09 | 70148169.12 | 0.868661E+09 | 0.932131E+09 | 0.131509E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 10009644.36 | 0.128066E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 70429066.77 | 0.102304E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.231977E+09 | 0.926330E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.471578E+09 | 0.718083E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.759302E+09 | 0.614527E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.843962E+09 | 0.461406E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.932164E+09 | 0.430868E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.766702E+09 | 0.423915E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.427486E+09 | 0.623973E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.177986E+09 | 0.869620E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 34740397.65 | 0.104184E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 4348520.70 | 0.131517E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.473068E+10 | 0.972944E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 4348520.70 | 0.423915E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.932164E+09 | 0.131517E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 10009644.36 | 0.128066E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 70429066.77 | 0.102304E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.231977E+09 | 0.926330E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.471578E+09 | 0.718083E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.759302E+09 | 0.614527E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.843962E+09 | 0.461406E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.932164E+09 | 0.430868E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.766702E+09 | 0.423915E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.427486E+09 | 0.623973E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.177986E+09 | 0.869620E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 34740397.65 | 0.104184E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 4348520.70 | 0.131517E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.473068E+10 | 0.972944E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 4348520.70 | 0.423915E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.932164E+09 | 0.131517E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.663026E+09 | 0.168099E+09 | 0.494928E+09 | 0.247574E+09 | 0.233953E+10 |
February | 0.109885E+10 | 0.390005E+09 | 0.708849E+09 | 0.745847E+09 | 0.187232E+10 |
March | 0.181645E+10 | 0.657569E+09 | 0.115888E+10 | 0.155607E+10 | 0.174273E+10 |
April | 0.272498E+10 | 0.113226E+10 | 0.159271E+10 | 0.280512E+10 | 0.138414E+10 |
May | 0.299628E+10 | 0.104173E+10 | 0.195454E+10 | 0.322868E+10 | 0.122491E+10 |
June | 0.347262E+10 | 0.151096E+10 | 0.196167E+10 | 0.400737E+10 | 0.941377E+09 |
July | 0.334161E+10 | 0.149990E+10 | 0.184171E+10 | 0.402713E+10 | 0.856781E+09 |
August | 0.328434E+10 | 0.164301E+10 | 0.164133E+10 | 0.408679E+10 | 0.846498E+09 |
September | 0.234995E+10 | 0.108382E+10 | 0.126614E+10 | 0.259530E+10 | 0.118927E+10 |
October | 0.158275E+10 | 0.672519E+09 | 0.910234E+09 | 0.144195E+10 | 0.164875E+10 |
November | 0.750753E+09 | 0.211944E+09 | 0.538809E+09 | 0.400837E+09 | 0.194120E+10 |
December | 0.636312E+09 | 0.204847E+09 | 0.431465E+09 | 0.303350E+09 | 0.243059E+10 |
Annual Sum or Average | 0.247179E+11 | 0.102167E+11 | 0.145013E+11 | 0.254460E+11 | 0.184181E+11 |
Minimum of Months | 0.636312E+09 | 0.168099E+09 | 0.431465E+09 | 0.247574E+09 | 0.846498E+09 |
Maximum of Months | 0.347262E+10 | 0.164301E+10 | 0.196167E+10 | 0.408679E+10 | 0.243059E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 26215457.77 | 6646464.26 | 19568993.51 | 9788861.22 | 92502906.11 |
February | 43447695.55 | 15420448.04 | 28027247.51 | 29490113.57 | 74029881.16 |
March | 71820864.26 | 25999666.84 | 45821197.41 | 61525717.57 | 68905799.79 |
April | 0.107743E+09 | 44768711.23 | 62974500.44 | 0.110912E+09 | 54727507.96 |
May | 0.118470E+09 | 41189145.54 | 77280911.26 | 0.127659E+09 | 48431794.77 |
June | 0.137304E+09 | 59741882.25 | 77562527.03 | 0.158448E+09 | 37221208.72 |
July | 0.132124E+09 | 59304779.97 | 72819649.84 | 0.159229E+09 | 33876341.28 |
August | 0.129860E+09 | 64963042.56 | 64896715.45 | 0.161588E+09 | 33469770.51 |
September | 92915081.92 | 42853079.58 | 50062002.35 | 0.102616E+09 | 47022589.23 |
October | 62580638.09 | 26590795.31 | 35989842.77 | 57013516.24 | 65190228.40 |
November | 29684100.24 | 8380085.62 | 21304014.63 | 15848714.91 | 76753321.25 |
December | 25159213.77 | 8099466.92 | 17059746.85 | 11994175.78 | 96103415.37 |
Annual Sum or Average | 0.977325E+09 | 0.403958E+09 | 0.573367E+09 | 0.100611E+10 | 0.728235E+09 |
Minimum of Months | 25159213.77 | 6646464.26 | 17059746.85 | 9788861.22 | 33469770.51 |
Maximum of Months | 0.137304E+09 | 64963042.56 | 77562527.03 | 0.161588E+09 | 96103415.37 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.864737E+09 | 0.116251E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136648E+10 | 0.970062E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.170305E+10 | 0.943503E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.184113E+10 | 0.773130E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175705E+10 | 0.671213E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158716E+10 | 0.514650E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195961E+10 | 0.490111E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216969E+10 | 0.480778E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217635E+10 | 0.658271E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.186201E+10 | 0.885692E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.901581E+09 | 0.989104E+09 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.100147E+10 | 0.122525E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191903E+11 | 0.976427E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.864737E+09 | 0.480778E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217635E+10 | 0.122525E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.864737E+09 | 0.116251E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136648E+10 | 0.970062E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.170305E+10 | 0.943503E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.184113E+10 | 0.773130E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175705E+10 | 0.671213E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158716E+10 | 0.514650E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195961E+10 | 0.490111E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216969E+10 | 0.480778E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217635E+10 | 0.658271E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.186201E+10 | 0.885692E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.901581E+09 | 0.989104E+09 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.100147E+10 | 0.122525E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191903E+11 | 0.976427E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.864737E+09 | 0.480778E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217635E+10 | 0.122525E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947518E+09 | 0.562639E+09 | 0.384879E+09 | 0.864682E+09 | 0.116244E+10 |
February | 0.131612E+10 | 0.814697E+09 | 0.501427E+09 | 0.136639E+10 | 0.970000E+09 |
March | 0.156746E+10 | 0.835906E+09 | 0.731554E+09 | 0.170294E+10 | 0.943443E+09 |
April | 0.160156E+10 | 0.695384E+09 | 0.906174E+09 | 0.184102E+10 | 0.773081E+09 |
May | 0.151324E+10 | 0.450805E+09 | 0.106243E+10 | 0.175694E+10 | 0.671170E+09 |
June | 0.133981E+10 | 0.359718E+09 | 0.980087E+09 | 0.158706E+10 | 0.514617E+09 |
July | 0.150982E+10 | 0.552972E+09 | 0.956847E+09 | 0.195949E+10 | 0.490080E+09 |
August | 0.162211E+10 | 0.756411E+09 | 0.865696E+09 | 0.216956E+10 | 0.480748E+09 |
September | 0.173925E+10 | 0.960467E+09 | 0.778782E+09 | 0.217621E+10 | 0.658230E+09 |
October | 0.162798E+10 | 0.100515E+10 | 0.622825E+09 | 0.186189E+10 | 0.885636E+09 |
November | 0.931466E+09 | 0.533807E+09 | 0.397659E+09 | 0.901524E+09 | 0.989041E+09 |
December | 0.100707E+10 | 0.651711E+09 | 0.355355E+09 | 0.100141E+10 | 0.122517E+10 |
Annual Sum or Average | 0.167234E+11 | 0.817967E+10 | 0.854372E+10 | 0.191891E+11 | 0.976366E+10 |
Minimum of Months | 0.931466E+09 | 0.359718E+09 | 0.355355E+09 | 0.864682E+09 | 0.480748E+09 |
Maximum of Months | 0.173925E+10 | 0.100515E+10 | 0.106243E+10 | 0.217621E+10 | 0.122517E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699333E+09 | 0.206220E+09 | 0.493113E+09 | 0.316118E+09 | 0.236278E+10 |
February | 0.113251E+10 | 0.425627E+09 | 0.706881E+09 | 0.832575E+09 | 0.190614E+10 |
March | 0.175696E+10 | 0.593020E+09 | 0.116394E+10 | 0.152488E+10 | 0.178751E+10 |
April | 0.258680E+10 | 0.989031E+09 | 0.159777E+10 | 0.266840E+10 | 0.145214E+10 |
May | 0.343957E+10 | 0.139731E+10 | 0.204226E+10 | 0.384438E+10 | 0.130147E+10 |
June | 0.320122E+10 | 0.124292E+10 | 0.195829E+10 | 0.365612E+10 | 0.993051E+09 |
July | 0.408649E+10 | 0.214806E+10 | 0.193843E+10 | 0.509766E+10 | 0.958874E+09 |
August | 0.338050E+10 | 0.172618E+10 | 0.165433E+10 | 0.427791E+10 | 0.932935E+09 |
September | 0.266410E+10 | 0.127829E+10 | 0.138581E+10 | 0.309088E+10 | 0.127029E+10 |
October | 0.156724E+10 | 0.638572E+09 | 0.928664E+09 | 0.145543E+10 | 0.170089E+10 |
November | 0.755297E+09 | 0.213025E+09 | 0.542273E+09 | 0.425425E+09 | 0.195507E+10 |
December | 0.656139E+09 | 0.224842E+09 | 0.431298E+09 | 0.365988E+09 | 0.246043E+10 |
Annual Sum or Average | 0.259262E+11 | 0.110831E+11 | 0.148431E+11 | 0.275558E+11 | 0.190816E+11 |
Minimum of Months | 0.656139E+09 | 0.206220E+09 | 0.431298E+09 | 0.316118E+09 | 0.932935E+09 |
Maximum of Months | 0.408649E+10 | 0.214806E+10 | 0.204226E+10 | 0.509766E+10 | 0.246043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27650915.06 | 8153722.29 | 19497192.77 | 12498967.64 | 93422227.51 |
February | 44778247.18 | 16828866.23 | 27949380.95 | 32919101.08 | 75367130.04 |
March | 69468548.27 | 23447401.83 | 46021146.44 | 60292177.01 | 70676364.32 |
April | 0.102280E+09 | 39105269.61 | 63174340.74 | 0.105506E+09 | 57416438.10 |
May | 0.135997E+09 | 55248024.25 | 80749036.80 | 0.152003E+09 | 51458857.62 |
June | 0.126573E+09 | 49143820.67 | 77429023.39 | 0.144559E+09 | 39264352.42 |
July | 0.161576E+09 | 84932032.48 | 76643484.53 | 0.201556E+09 | 37913007.50 |
August | 0.133662E+09 | 68251229.16 | 65410395.83 | 0.169144E+09 | 36887376.87 |
September | 0.105336E+09 | 50542232.62 | 54793546.51 | 0.122210E+09 | 50225928.98 |
October | 61966936.11 | 25248478.46 | 36718457.65 | 57546316.84 | 67251810.24 |
November | 29863697.12 | 8422773.34 | 21440923.78 | 16820842.66 | 77301654.15 |
December | 25943078.99 | 8890003.39 | 17053075.60 | 14470784.82 | 97283299.86 |
Annual Sum or Average | 0.102509E+10 | 0.438214E+09 | 0.586880E+09 | 0.108953E+10 | 0.754468E+09 |
Minimum of Months | 25943078.99 | 8153722.29 | 17053075.60 | 12498967.64 | 36887376.87 |
Maximum of Months | 0.161576E+09 | 84932032.48 | 80749036.80 | 0.201556E+09 | 97283299.86 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 25947260.21 | 0.389439E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.190036E+09 | 0.314506E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.627960E+09 | 0.291557E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.131394E+10 | 0.228330E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.218000E+10 | 0.192723E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.245697E+10 | 0.143544E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.273687E+10 | 0.133388E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.225309E+10 | 0.130879E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.124441E+10 | 0.191368E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.513177E+09 | 0.262796E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 99980166.67 | 0.310889E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 11893173.35 | 0.395628E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.136543E+11 | 0.298505E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 11893173.35 | 0.130879E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.273687E+10 | 0.395628E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.248344E+09 | 0.246236E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.746660E+09 | 0.198425E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.155855E+10 | 0.187018E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.285453E+10 | 0.147153E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.329796E+10 | 0.129786E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.411990E+10 | 0.981975E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.414414E+10 | 0.894723E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.421449E+10 | 0.874933E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.266954E+10 | 0.123333E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.147838E+10 | 0.169474E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.408335E+09 | 0.200180E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.308872E+09 | 0.253094E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.260497E+11 | 0.192986E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.248344E+09 | 0.874933E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.421449E+10 | 0.253094E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.253306E+10 | 0.353759E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.401811E+10 | 0.292989E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.499460E+10 | 0.289325E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.539876E+10 | 0.239608E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.514737E+10 | 0.208908E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.465946E+10 | 0.159663E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.580662E+10 | 0.149019E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.645180E+10 | 0.144137E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.647683E+10 | 0.195354E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.553259E+10 | 0.260215E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.266001E+10 | 0.294642E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.296015E+10 | 0.368709E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.566394E+11 | 0.295633E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.253306E+10 | 0.144137E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.647683E+10 | 0.368709E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.316290E+09 | 0.248498E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.837175E+09 | 0.201315E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.153365E+10 | 0.191276E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.271102E+10 | 0.155135E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.394307E+10 | 0.136521E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.375699E+10 | 0.103924E+10 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.526552E+10 | 0.983269E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441926E+10 | 0.958622E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.319246E+10 | 0.130458E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.149831E+10 | 0.174593E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.435799E+09 | 0.201012E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.372871E+09 | 0.255750E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.282824E+11 | 0.199267E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.316290E+09 | 0.958622E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.526552E+10 | 0.255750E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.89 | 1383.33 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 86.62 | 1226.02 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 249.31 | 1021.07 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 520.74 | 833.78 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 823.66 | 687.85 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 952.30 | 534.00 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1023.35 | 481.14 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 844.18 | 470.27 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 489.41 | 699.28 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 208.28 | 908.97 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 46.47 | 1113.43 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 6.72 | 1390.05 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 440.77 | 894.16 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 6.72 | 470.27 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1023.35 | 1390.05 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 97.42 | 875.41 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 320.31 | 773.55 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 596.81 | 655.38 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1113.72 | 539.78 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1239.34 | 464.61 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1593.39 | 366.12 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1550.69 | 323.72 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1577.30 | 315.49 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1038.64 | 452.43 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 566.72 | 588.24 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 167.79 | 716.64 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 121.65 | 889.40 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 834.58 | 579.15 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 97.42 | 315.49 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1593.39 | 889.40 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 958.43 | 1255.72 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1678.56 | 1144.02 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1878.74 | 1015.86 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2092.76 | 879.04 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1926.43 | 746.42 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1797.44 | 593.34 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2165.91 | 537.62 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2407.58 | 518.51 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2505.39 | 717.83 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2081.33 | 906.74 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1044.11 | 1058.92 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1118.97 | 1296.72 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1805.07 | 887.98 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 958.43 | 518.51 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2505.39 | 1296.72 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.43 | 882.60 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 353.53 | 785.26 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 582.27 | 670.22 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1053.71 | 567.58 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1475.51 | 487.23 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1449.05 | 385.87 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1963.78 | 354.41 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1649.18 | 344.65 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1236.20 | 478.43 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 570.08 | 605.36 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 175.76 | 720.79 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 142.94 | 898.86 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 901.37 | 597.56 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 121.43 | 344.65 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1963.78 | 898.86 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.21 | 1434.40 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 87.34 | 1268.62 | 373.78 | 0.00 | 373.78 | 0.00 | 0.00 |
March | 259.83 | 1037.53 | 550.71 | 0.00 | 550.71 | 0.00 | 0.00 |
April | 545.80 | 831.10 | 779.31 | 2.76 | 776.55 | 0.00 | 0.00 |
May | 850.46 | 688.30 | 1002.78 | 29.79 | 972.99 | 0.00 | 0.00 |
June | 976.80 | 534.02 | 1054.40 | 69.63 | 984.77 | 0.00 | 0.00 |
July | 1044.08 | 482.59 | 1002.15 | 78.57 | 923.57 | 0.00 | 0.00 |
August | 858.75 | 474.81 | 811.25 | 21.93 | 789.32 | 0.00 | 0.00 |
September | 494.77 | 722.18 | 630.15 | 0.19 | 629.96 | 0.00 | 0.00 |
October | 199.36 | 974.02 | 431.75 | 0.00 | 431.75 | 0.00 | 0.00 |
November | 40.21 | 1205.81 | 271.96 | 0.00 | 271.96 | 0.00 | 0.00 |
December | 4.87 | 1473.06 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Annual Sum or Average | 450.02 | 925.54 | 613.90 | 17.03 | 596.87 | 0.00 | 0.00 |
Minimum of Months | 4.87 | 474.81 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Maximum of Months | 1044.08 | 1473.06 | 1054.40 | 78.57 | 984.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.09 | 908.02 | 257.33 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 320.49 | 804.54 | 472.18 | 167.59 | 304.59 | 0.00 | 0.00 |
March | 603.94 | 676.39 | 705.00 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1125.01 | 555.12 | 1092.87 | 454.10 | 638.77 | 0.00 | 0.00 |
May | 1253.11 | 475.41 | 1162.91 | 404.32 | 758.60 | 0.00 | 0.00 |
June | 1607.18 | 377.55 | 1392.72 | 605.98 | 786.74 | 0.00 | 0.00 |
July | 1563.01 | 332.53 | 1296.95 | 582.14 | 714.80 | 0.00 | 0.00 |
August | 1586.16 | 328.54 | 1274.72 | 637.68 | 637.03 | 0.00 | 0.00 |
September | 1040.86 | 476.96 | 942.47 | 434.67 | 507.79 | 0.00 | 0.00 |
October | 559.65 | 639.91 | 614.30 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 160.76 | 778.53 | 301.09 | 85.00 | 216.09 | 0.00 | 0.00 |
December | 117.74 | 943.36 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 838.79 | 607.13 | 814.79 | 336.78 | 478.01 | 0.00 | 0.00 |
Minimum of Months | 96.09 | 328.54 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1607.18 | 943.36 | 1392.72 | 637.68 | 786.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 968.55 | 1302.07 | 1061.33 | 630.22 | 431.11 | 0.00 | 0.00 |
February | 1694.51 | 1202.93 | 1632.17 | 1010.33 | 621.84 | 0.00 | 0.00 |
March | 1907.49 | 1056.77 | 1755.74 | 936.31 | 819.43 | 0.00 | 0.00 |
April | 2130.89 | 894.81 | 1853.73 | 804.88 | 1048.86 | 0.00 | 0.00 |
May | 1967.99 | 751.79 | 1695.00 | 504.96 | 1190.05 | 0.00 | 0.00 |
June | 1836.95 | 595.65 | 1550.77 | 416.36 | 1134.41 | 0.00 | 0.00 |
July | 2194.86 | 548.95 | 1691.18 | 619.39 | 1071.78 | 0.00 | 0.00 |
August | 2430.16 | 538.49 | 1816.95 | 847.27 | 969.68 | 0.00 | 0.00 |
September | 2518.87 | 761.87 | 2013.11 | 1111.70 | 901.41 | 0.00 | 0.00 |
October | 2085.54 | 992.02 | 1823.53 | 1125.89 | 697.64 | 0.00 | 0.00 |
November | 1043.47 | 1144.77 | 1078.13 | 617.86 | 460.27 | 0.00 | 0.00 |
December | 1121.70 | 1372.34 | 1128.03 | 729.99 | 398.04 | 0.00 | 0.00 |
Annual Sum or Average | 1825.53 | 928.85 | 1590.95 | 778.16 | 812.79 | 0.00 | 0.00 |
Minimum of Months | 968.55 | 538.49 | 1061.33 | 416.36 | 398.04 | 0.00 | 0.00 |
Maximum of Months | 2518.87 | 1372.34 | 2013.11 | 1125.89 | 1190.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.69 | 917.04 | 271.42 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 357.76 | 819.08 | 486.64 | 182.89 | 303.75 | 0.00 | 0.00 |
March | 591.84 | 693.77 | 681.91 | 230.16 | 451.75 | 0.00 | 0.00 |
April | 1070.18 | 582.39 | 1037.45 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1492.08 | 505.12 | 1334.96 | 542.32 | 792.64 | 0.00 | 0.00 |
June | 1466.31 | 398.27 | 1283.87 | 498.48 | 785.39 | 0.00 | 0.00 |
July | 1978.50 | 372.16 | 1586.04 | 833.70 | 752.34 | 0.00 | 0.00 |
August | 1660.34 | 362.09 | 1312.04 | 669.96 | 642.08 | 0.00 | 0.00 |
September | 1239.62 | 509.46 | 1068.45 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 564.88 | 660.15 | 608.27 | 247.84 | 360.43 | 0.00 | 0.00 |
November | 170.62 | 784.09 | 302.92 | 85.43 | 217.48 | 0.00 | 0.00 |
December | 142.05 | 954.94 | 254.66 | 87.27 | 167.39 | 0.00 | 0.00 |
Annual Sum or Average | 908.34 | 629.00 | 854.62 | 365.34 | 489.28 | 0.00 | 0.00 |
Minimum of Months | 122.69 | 362.09 | 254.66 | 80.04 | 167.39 | 0.00 | 0.00 |
Maximum of Months | 1978.50 | 954.94 | 1586.04 | 833.70 | 792.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.69 | 1454.00 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 78.55 | 1300.04 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 234.45 | 1088.55 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 506.92 | 880.90 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 813.92 | 719.55 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 947.90 | 553.80 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1021.83 | 498.01 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 841.21 | 488.65 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 480.10 | 738.30 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 191.60 | 981.17 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 38.57 | 1199.42 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 4.44 | 1477.11 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 432.97 | 946.55 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 4.44 | 488.65 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1021.83 | 1477.11 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.72 | 919.34 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 308.64 | 820.21 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 581.89 | 698.25 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1101.28 | 567.72 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1231.32 | 484.57 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1589.47 | 378.85 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1547.24 | 334.05 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1573.51 | 326.66 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1029.92 | 475.82 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 551.96 | 632.74 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 157.54 | 772.30 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 115.32 | 944.95 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 826.03 | 611.96 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 92.72 | 326.66 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1589.47 | 944.95 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 945.73 | 1320.79 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1660.92 | 1211.10 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1864.77 | 1080.22 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2082.86 | 924.41 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1921.81 | 779.97 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1797.63 | 615.98 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2167.94 | 556.37 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2408.82 | 538.15 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2498.78 | 753.68 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2065.63 | 971.53 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1026.24 | 1136.74 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1105.19 | 1376.60 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1796.02 | 937.45 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 945.73 | 538.15 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2498.78 | 1376.60 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.09 | 927.79 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 346.05 | 832.16 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 572.60 | 714.14 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1045.92 | 598.51 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1472.17 | 509.71 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1449.45 | 400.94 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1965.92 | 367.11 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1649.96 | 357.91 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1231.66 | 503.31 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 559.41 | 651.86 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 168.13 | 775.51 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 139.21 | 954.86 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 896.83 | 631.87 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 118.09 | 357.91 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1965.92 | 954.86 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 31846178.33 | 0.370512E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.209557E+09 | 0.296599E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.667765E+09 | 0.273485E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.134976E+10 | 0.216115E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.220610E+10 | 0.184235E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.246837E+10 | 0.138412E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.274094E+10 | 0.128868E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.226106E+10 | 0.125958E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.126855E+10 | 0.181253E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.557849E+09 | 0.243460E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 0.120452E+09 | 0.288602E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 17992985.96 | 0.372311E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139003E+11 | 0.281981E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 17992985.96 | 0.125958E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.274094E+10 | 0.372311E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.260942E+09 | 0.234470E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.774892E+09 | 0.187137E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.159851E+10 | 0.175538E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.288675E+10 | 0.139912E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.331945E+10 | 0.124442E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.413007E+10 | 0.948980E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.415337E+10 | 0.867052E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.422465E+10 | 0.845002E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.269215E+10 | 0.117270E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.151790E+10 | 0.157555E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.434921E+09 | 0.185754E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.325817E+09 | 0.238218E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.263194E+11 | 0.182640E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260942E+09 | 0.845002E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422465E+10 | 0.238218E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256706E+10 | 0.336332E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.406078E+10 | 0.276762E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.503203E+10 | 0.272087E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.542444E+10 | 0.227847E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.515974E+10 | 0.199922E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.465896E+10 | 0.153795E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.580119E+10 | 0.143997E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.644846E+10 | 0.138879E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.649398E+10 | 0.186060E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.557463E+10 | 0.242861E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.270633E+10 | 0.274472E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.299705E+10 | 0.347314E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.569246E+11 | 0.280033E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256706E+10 | 0.138879E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.649398E+10 | 0.347314E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325239E+09 | 0.236396E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.855269E+09 | 0.189971E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.155956E+10 | 0.179512E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.273122E+10 | 0.147118E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.395201E+10 | 0.130499E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.375593E+10 | 0.100018E+10 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.525980E+10 | 0.949258E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441717E+10 | 0.923113E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.320423E+10 | 0.124009E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.152689E+10 | 0.162140E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.455570E+09 | 0.186828E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.382844E+09 | 0.240751E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284257E+11 | 0.188448E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.325239E+09 | 0.923113E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.525980E+10 | 0.240751E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30029861.90 | 0.384190E+10 | 0.643395E+09 | 0.00 | 0.643395E+09 | 0.00 | 0.00 |
February | 0.211288E+09 | 0.306905E+10 | 0.904256E+09 | 0.00 | 0.904256E+09 | 0.00 | 0.00 |
March | 0.695927E+09 | 0.277893E+10 | 0.147502E+10 | 0.00 | 0.147502E+10 | 0.00 | 0.00 |
April | 0.141472E+10 | 0.215420E+10 | 0.201998E+10 | 7165414.18 | 0.201281E+10 | 0.00 | 0.00 |
May | 0.227788E+10 | 0.184354E+10 | 0.268584E+10 | 79791812.30 | 0.260605E+10 | 0.00 | 0.00 |
June | 0.253186E+10 | 0.138419E+10 | 0.273300E+10 | 0.180474E+09 | 0.255252E+10 | 0.00 | 0.00 |
July | 0.279646E+10 | 0.129258E+10 | 0.268415E+10 | 0.210448E+09 | 0.247370E+10 | 0.00 | 0.00 |
August | 0.230008E+10 | 0.127172E+10 | 0.217284E+10 | 58737854.82 | 0.211410E+10 | 0.00 | 0.00 |
September | 0.128244E+10 | 0.187188E+10 | 0.163334E+10 | 481642.78 | 0.163286E+10 | 0.00 | 0.00 |
October | 0.533954E+09 | 0.260881E+10 | 0.115641E+10 | 0.00 | 0.115641E+10 | 0.00 | 0.00 |
November | 0.104222E+09 | 0.312547E+10 | 0.704927E+09 | 0.00 | 0.704927E+09 | 0.00 | 0.00 |
December | 13045997.27 | 0.394544E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.141919E+11 | 0.291877E+11 | 0.193599E+11 | 0.537099E+09 | 0.188228E+11 | 0.00 | 0.00 |
Minimum of Months | 13045997.27 | 0.127172E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Maximum of Months | 0.279646E+10 | 0.394544E+10 | 0.273300E+10 | 0.210448E+09 | 0.260605E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257363E+09 | 0.243203E+10 | 0.689242E+09 | 0.174745E+09 | 0.514497E+09 | 0.00 | 0.00 |
February | 0.775337E+09 | 0.194635E+10 | 0.114230E+10 | 0.405425E+09 | 0.736876E+09 | 0.00 | 0.00 |
March | 0.161760E+10 | 0.181163E+10 | 0.188827E+10 | 0.683568E+09 | 0.120470E+10 | 0.00 | 0.00 |
April | 0.291603E+10 | 0.143886E+10 | 0.283272E+10 | 0.117703E+10 | 0.165569E+10 | 0.00 | 0.00 |
May | 0.335634E+10 | 0.127334E+10 | 0.311475E+10 | 0.108292E+10 | 0.203182E+10 | 0.00 | 0.00 |
June | 0.416581E+10 | 0.978598E+09 | 0.360993E+10 | 0.157070E+10 | 0.203923E+10 | 0.00 | 0.00 |
July | 0.418636E+10 | 0.890657E+09 | 0.347374E+10 | 0.155921E+10 | 0.191453E+10 | 0.00 | 0.00 |
August | 0.424838E+10 | 0.879968E+09 | 0.341420E+10 | 0.170797E+10 | 0.170623E+10 | 0.00 | 0.00 |
September | 0.269792E+10 | 0.123629E+10 | 0.244287E+10 | 0.112667E+10 | 0.131620E+10 | 0.00 | 0.00 |
October | 0.149897E+10 | 0.171394E+10 | 0.164533E+10 | 0.699110E+09 | 0.946224E+09 | 0.00 | 0.00 |
November | 0.416685E+09 | 0.201795E+10 | 0.780437E+09 | 0.220324E+09 | 0.560113E+09 | 0.00 | 0.00 |
December | 0.315344E+09 | 0.252670E+10 | 0.661471E+09 | 0.212946E+09 | 0.448525E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.264521E+11 | 0.191463E+11 | 0.256953E+11 | 0.106206E+11 | 0.150746E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257363E+09 | 0.879968E+09 | 0.661471E+09 | 0.174745E+09 | 0.448525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424838E+10 | 0.252670E+10 | 0.360993E+10 | 0.170797E+10 | 0.203923E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.259416E+10 | 0.348747E+10 | 0.284267E+10 | 0.168799E+10 | 0.115468E+10 | 0.00 | 0.00 |
February | 0.409936E+10 | 0.291012E+10 | 0.394854E+10 | 0.244419E+10 | 0.150435E+10 | 0.00 | 0.00 |
March | 0.510903E+10 | 0.283045E+10 | 0.470258E+10 | 0.250782E+10 | 0.219475E+10 | 0.00 | 0.00 |
April | 0.552328E+10 | 0.231934E+10 | 0.480488E+10 | 0.208624E+10 | 0.271864E+10 | 0.00 | 0.00 |
May | 0.527105E+10 | 0.201360E+10 | 0.453990E+10 | 0.135247E+10 | 0.318743E+10 | 0.00 | 0.00 |
June | 0.476138E+10 | 0.154392E+10 | 0.401958E+10 | 0.107920E+10 | 0.294039E+10 | 0.00 | 0.00 |
July | 0.587871E+10 | 0.147030E+10 | 0.452965E+10 | 0.165899E+10 | 0.287066E+10 | 0.00 | 0.00 |
August | 0.650895E+10 | 0.144230E+10 | 0.486653E+10 | 0.226933E+10 | 0.259720E+10 | 0.00 | 0.00 |
September | 0.652892E+10 | 0.197477E+10 | 0.521797E+10 | 0.288152E+10 | 0.233645E+10 | 0.00 | 0.00 |
October | 0.558591E+10 | 0.265702E+10 | 0.488414E+10 | 0.301559E+10 | 0.186855E+10 | 0.00 | 0.00 |
November | 0.270469E+10 | 0.296725E+10 | 0.279452E+10 | 0.160149E+10 | 0.119303E+10 | 0.00 | 0.00 |
December | 0.300435E+10 | 0.367566E+10 | 0.302132E+10 | 0.195522E+10 | 0.106611E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.575698E+11 | 0.292922E+11 | 0.501723E+11 | 0.245400E+11 | 0.256322E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259416E+10 | 0.144230E+10 | 0.279452E+10 | 0.107920E+10 | 0.106611E+10 | 0.00 | 0.00 |
Maximum of Months | 0.652892E+10 | 0.367566E+10 | 0.521797E+10 | 0.301559E+10 | 0.318743E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.328617E+09 | 0.245620E+10 | 0.726984E+09 | 0.214374E+09 | 0.512610E+09 | 0.00 | 0.00 |
February | 0.865494E+09 | 0.198151E+10 | 0.117729E+10 | 0.442456E+09 | 0.734831E+09 | 0.00 | 0.00 |
March | 0.158517E+10 | 0.185818E+10 | 0.182643E+10 | 0.616467E+09 | 0.120996E+10 | 0.00 | 0.00 |
April | 0.277391E+10 | 0.150956E+10 | 0.268908E+10 | 0.102814E+10 | 0.166095E+10 | 0.00 | 0.00 |
May | 0.399638E+10 | 0.135293E+10 | 0.357557E+10 | 0.145255E+10 | 0.212301E+10 | 0.00 | 0.00 |
June | 0.380068E+10 | 0.103232E+10 | 0.332779E+10 | 0.129206E+10 | 0.203572E+10 | 0.00 | 0.00 |
July | 0.529921E+10 | 0.996787E+09 | 0.424806E+10 | 0.223299E+10 | 0.201507E+10 | 0.00 | 0.00 |
August | 0.444705E+10 | 0.969822E+09 | 0.351416E+10 | 0.179443E+10 | 0.171974E+10 | 0.00 | 0.00 |
September | 0.321309E+10 | 0.132051E+10 | 0.276943E+10 | 0.132883E+10 | 0.144060E+10 | 0.00 | 0.00 |
October | 0.151298E+10 | 0.176815E+10 | 0.162920E+10 | 0.663820E+09 | 0.965383E+09 | 0.00 | 0.00 |
November | 0.442246E+09 | 0.203237E+10 | 0.785161E+09 | 0.221447E+09 | 0.563714E+09 | 0.00 | 0.00 |
December | 0.380459E+09 | 0.255772E+10 | 0.682082E+09 | 0.233732E+09 | 0.448351E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286453E+11 | 0.198360E+11 | 0.269512E+11 | 0.115213E+11 | 0.154299E+11 | 0.00 | 0.00 |
Minimum of Months | 0.328617E+09 | 0.969822E+09 | 0.682082E+09 | 0.214374E+09 | 0.448351E+09 | 0.00 | 0.00 |
Maximum of Months | 0.529921E+10 | 0.255772E+10 | 0.424806E+10 | 0.223299E+10 | 0.212301E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 25947260.21 | 0.389439E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.190036E+09 | 0.314506E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.627960E+09 | 0.291557E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.131394E+10 | 0.228330E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.218000E+10 | 0.192723E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.245697E+10 | 0.143544E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.273687E+10 | 0.133388E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.225309E+10 | 0.130879E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.124441E+10 | 0.191368E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.513177E+09 | 0.262796E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 99980166.67 | 0.310889E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 11893173.35 | 0.395628E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136543E+11 | 0.298505E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 11893173.35 | 0.130879E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273687E+10 | 0.395628E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248344E+09 | 0.246236E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.746660E+09 | 0.198425E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.155855E+10 | 0.187018E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.285453E+10 | 0.147153E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.329796E+10 | 0.129786E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.411990E+10 | 0.981975E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.414414E+10 | 0.894723E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.421449E+10 | 0.874933E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.266954E+10 | 0.123333E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.147838E+10 | 0.169474E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.408335E+09 | 0.200180E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.308872E+09 | 0.253094E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.260497E+11 | 0.192986E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248344E+09 | 0.874933E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421449E+10 | 0.253094E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.253306E+10 | 0.353759E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.401811E+10 | 0.292989E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.499460E+10 | 0.289325E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.539876E+10 | 0.239608E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.514737E+10 | 0.208908E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.465946E+10 | 0.159663E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.580662E+10 | 0.149019E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.645180E+10 | 0.144137E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.647683E+10 | 0.195354E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.553259E+10 | 0.260215E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.266001E+10 | 0.294642E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.296015E+10 | 0.368709E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.566394E+11 | 0.295633E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253306E+10 | 0.144137E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.647683E+10 | 0.368709E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.316290E+09 | 0.248498E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.837175E+09 | 0.201315E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.153365E+10 | 0.191276E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.271102E+10 | 0.155135E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.394307E+10 | 0.136521E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.375699E+10 | 0.103924E+10 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.526552E+10 | 0.983269E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441926E+10 | 0.958622E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.319246E+10 | 0.130458E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.149831E+10 | 0.174593E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.435799E+09 | 0.201012E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.372871E+09 | 0.255750E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282824E+11 | 0.199267E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.316290E+09 | 0.958622E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526552E+10 | 0.255750E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.523409E+10 | -0.448749E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -746605981.1 | 58.98 | 0.00 | 0.00 |
February | 0.476393E+10 | -0.410679E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -657139961.8 | 58.98 | 0.00 | 0.00 |
March | 0.551718E+10 | -0.480670E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -710487779.6 | 58.98 | 0.00 | 0.00 |
April | 0.488475E+10 | -0.420622E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -678528145.9 | 58.99 | 0.00 | 0.00 |
May | 0.503994E+10 | -0.434406E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695882963.9 | 58.98 | 0.00 | 0.00 |
June | 0.482392E+10 | -0.415271E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -671206650.0 | 58.98 | 0.00 | 0.00 |
July | 0.449434E+10 | -0.380330E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691043587.2 | 58.98 | 0.00 | 0.00 |
August | 0.486314E+10 | -0.417057E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692571018.2 | 58.98 | 0.00 | 0.00 |
September | 0.447569E+10 | -0.380561E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670085974.3 | 58.98 | 0.00 | 0.00 |
October | 0.475566E+10 | -0.405563E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -700023823.6 | 58.98 | 0.00 | 0.00 |
November | 0.484076E+10 | -0.414861E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -692149152.0 | 58.98 | 0.00 | 0.00 |
December | 0.498713E+10 | -0.425676E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -730371981.5 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.586805E+11 | -0.503444E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.833610E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.447569E+10 | -0.480670E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -746605981.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.551718E+10 | -0.380330E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -657139961.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:50 | 2744.45 | 32.28 | 222.33 | 218.83 | 2191.41 | 33.53 | 225.83 | 187.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4676.02 | 33.24 | 243.17 | 243.33 | 2064.71 | 29.38 | 222.17 | 221.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7743.27 | 33.05 | 208.83 | 311.67 | 1686.13 | 21.83 | 155.83 | 267.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2183.74 | 18.64 | 2.83 | 344.33 | 1216.73 | 20.87 | 212.67 | 307.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1995.02 | 18.53 | 4.83 | 384.83 | 1093.07 | 20.71 | 209.50 | 343.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1742.44 | 18.10 | 0.00 | 393.83 | 1003.97 | 20.32 | 190.50 | 343.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1552.52 | 16.89 | 0.00 | 392.83 | 913.22 | 19.11 | 150.83 | 337.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1846.74 | 17.94 | 2.67 | 372.67 | 1111.28 | 20.18 | 159.50 | 326.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2983.68 | 20.78 | 41.67 | 319.00 | 1478.49 | 21.66 | 186.50 | 287.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7195.48 | 34.58 | 220.50 | 284.67 | 1968.69 | 23.02 | 157.50 | 256.17 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-08:09 | 3058.65 | 31.81 | 224.67 | 224.17 | 2456.87 | 33.15 | 229.50 | 193.17 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3686.25 | 35.42 | 149.50 | 206.83 | 3141.89 | 36.90 | 149.67 | 167.17 |
Annual Sum or Average | 3714.00 | 0.51 | 3101.84 | 23.95 | 1321.00 | 3697.00 | 1520.01 | 23.68 | 2250.00 | 3236.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1552.52 | 16.89 | 0.00 | 206.83 | 913.22 | 19.11 | 149.67 | 167.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7743.27 | 35.42 | 243.17 | 393.83 | 3141.89 | 36.90 | 229.50 | 343.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 911.09 | 18.95 | 61.50 | 198.67 | 567.91 | 21.21 | 75.67 | 128.67 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1469.22 | 19.69 | 68.33 | 226.67 | 787.99 | 21.90 | 79.83 | 178.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2659.52 | 22.08 | 79.00 | 302.00 | 1191.45 | 23.02 | 90.67 | 252.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2796.72 | 21.11 | 105.50 | 346.33 | 1584.43 | 23.20 | 103.83 | 306.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2887.52 | 21.03 | 132.50 | 390.83 | 1263.95 | 21.35 | 91.67 | 349.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3031.04 | 20.26 | 89.00 | 402.67 | 1682.49 | 22.31 | 77.67 | 355.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2859.15 | 20.72 | 148.50 | 406.33 | 1302.06 | 21.66 | 101.67 | 370.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3343.46 | 22.20 | 116.33 | 377.50 | 1464.14 | 21.98 | 74.00 | 337.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2730.18 | 21.78 | 82.67 | 322.83 | 1531.78 | 23.01 | 77.67 | 284.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2444.16 | 21.98 | 83.00 | 270.50 | 1096.07 | 22.64 | 89.17 | 224.67 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1135.34 | 20.34 | 79.17 | 207.17 | 596.33 | 21.16 | 71.67 | 143.50 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1069.58 | 21.49 | 56.33 | 182.00 | 582.30 | 22.14 | 57.00 | 104.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2458.32 | 20.98 | 1101.83 | 3633.50 | 1218.50 | 22.12 | 990.50 | 3035.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 911.09 | 18.95 | 56.33 | 182.00 | 567.91 | 21.16 | 57.00 | 104.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3343.46 | 22.20 | 148.50 | 406.33 | 1682.49 | 23.20 | 103.83 | 370.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 02-JAN-10:00 | 490.08 | 14.23 | 0.00 | 176.83 | 269.03 | 16.43 | 0.00 | 45.33 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 620.74 | 15.47 | 0.00 | 213.83 | 353.27 | 17.73 | 0.00 | 126.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 834.48 | 17.01 | 0.00 | 297.33 | 497.24 | 19.27 | 4.00 | 214.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 980.20 | 17.76 | 0.00 | 347.83 | 570.78 | 19.89 | 31.83 | 300.33 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1222.56 | 20.01 | 40.00 | 399.33 | 700.78 | 22.06 | 162.17 | 366.67 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1281.10 | 21.20 | 60.83 | 412.67 | 757.07 | 23.27 | 193.50 | 383.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1083.92 | 20.32 | 79.33 | 423.50 | 651.77 | 22.39 | 180.00 | 382.17 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 951.82 | 17.84 | 0.00 | 390.67 | 584.43 | 20.03 | 53.83 | 344.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 906.39 | 17.88 | 0.00 | 313.17 | 553.58 | 20.10 | 16.50 | 254.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 675.74 | 16.03 | 0.00 | 258.50 | 412.10 | 18.37 | 0.33 | 163.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-09:00 | 527.98 | 14.57 | 0.00 | 189.67 | 289.61 | 16.71 | 0.00 | 64.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 456.51 | 14.21 | 0.00 | 151.17 | 269.27 | 16.68 | 0.00 | 35.50 |
Annual Sum or Average | 3714.00 | 0.52 | 904.42 | 17.80 | 180.17 | 3574.50 | 533.52 | 19.97 | 642.17 | 2682.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 456.51 | 14.21 | 0.00 | 151.17 | 269.03 | 16.43 | 0.00 | 35.50 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1281.10 | 21.20 | 79.33 | 423.50 | 757.07 | 23.27 | 193.50 | 383.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-10:30 | 1020.26 | 18.86 | 65.17 | 199.50 | 560.81 | 21.16 | 68.33 | 136.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1467.67 | 19.86 | 66.67 | 228.83 | 768.83 | 21.67 | 71.67 | 181.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2351.12 | 22.14 | 78.17 | 304.67 | 1270.38 | 23.10 | 93.67 | 251.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2820.83 | 20.83 | 105.50 | 344.17 | 1239.75 | 20.75 | 59.67 | 305.83 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2912.82 | 17.71 | 52.50 | 390.33 | 1579.16 | 18.62 | 11.67 | 354.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2981.49 | 17.33 | 42.83 | 401.67 | 1352.65 | 18.42 | 1.17 | 361.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:10 | 3282.06 | 16.47 | 58.83 | 402.67 | 1444.99 | 17.24 | 4.67 | 360.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3109.00 | 19.27 | 75.83 | 380.00 | 1798.21 | 20.73 | 54.50 | 341.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3432.57 | 22.97 | 100.50 | 314.67 | 1944.62 | 23.91 | 95.67 | 270.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2348.42 | 22.32 | 87.33 | 272.00 | 1070.48 | 23.22 | 84.83 | 224.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1090.60 | 18.82 | 63.33 | 208.50 | 583.82 | 20.51 | 59.83 | 140.17 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:00 | 1090.76 | 20.31 | 48.67 | 182.00 | 585.68 | 21.07 | 49.83 | 100.67 |
Annual Sum or Average | 3714.00 | 0.51 | 2524.17 | 19.42 | 845.33 | 3629.00 | 1271.95 | 20.49 | 655.50 | 3028.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1020.26 | 16.47 | 42.83 | 182.00 | 560.81 | 17.24 | 1.17 | 100.67 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3432.57 | 22.97 | 105.50 | 402.67 | 1944.62 | 23.91 | 95.67 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.31 | 30.49 | 207.17 | 216.17 | 2123.85 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.28 | 32.09 | 231.50 | 240.50 | 1973.39 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.42 | 32.25 | 207.67 | 309.83 | 1574.26 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.41 | 14.68 | 0.00 | 342.83 | 1140.44 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.79 | 14.64 | 0.00 | 382.67 | 1033.46 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.73 | 14.46 | 0.00 | 392.00 | 952.27 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.39 | 13.10 | 0.00 | 389.33 | 863.25 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.18 | 14.23 | 0.00 | 369.33 | 1040.53 | 17.80 | 5.67 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.76 | 17.24 | 27.00 | 317.83 | 1375.12 | 19.08 | 29.67 | 282.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.68 | 33.75 | 218.00 | 282.33 | 1850.18 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.99 | 30.64 | 215.33 | 222.17 | 2389.04 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.89 | 34.93 | 149.17 | 204.83 | 3041.51 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.81 | 21.19 | 1255.83 | 3669.83 | 1443.68 | 21.56 | 847.17 | 3189.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.39 | 13.10 | 0.00 | 204.83 | 863.25 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.42 | 34.93 | 231.50 | 392.00 | 3041.51 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.63 | 18.45 | 61.33 | 197.00 | 546.64 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.96 | 19.19 | 68.00 | 225.50 | 754.71 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.99 | 21.61 | 79.00 | 300.00 | 1137.92 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.69 | 20.65 | 105.33 | 344.50 | 1525.45 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.61 | 20.60 | 132.33 | 388.33 | 1209.34 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.69 | 19.80 | 89.00 | 400.67 | 1614.57 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.71 | 20.13 | 146.50 | 404.00 | 1243.00 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3196.03 | 20.22 | 98.50 | 373.50 | 1398.18 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.31 | 21.30 | 82.67 | 319.67 | 1474.21 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.30 | 21.29 | 81.00 | 267.83 | 1047.40 | 22.42 | 76.83 | 221.17 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.37 | 18.45 | 65.67 | 203.67 | 572.12 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.38 | 21.01 | 56.33 | 178.83 | 556.71 | 21.88 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.52 | 20.24 | 1065.67 | 3603.50 | 1167.51 | 21.81 | 909.33 | 2982.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.63 | 18.45 | 56.33 | 178.83 | 546.64 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3196.03 | 21.61 | 146.50 | 404.00 | 1614.57 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.86 | 10.05 | 0.00 | 172.50 | 258.54 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 598.02 | 11.55 | 0.00 | 210.33 | 340.49 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.54 | 13.48 | 0.00 | 293.00 | 480.87 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.73 | 14.26 | 0.00 | 346.00 | 551.71 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.28 | 16.05 | 26.67 | 397.83 | 676.44 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.96 | 18.31 | 59.00 | 411.00 | 732.10 | 21.51 | 73.17 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.28 | 15.66 | 44.67 | 420.83 | 631.63 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.73 | 14.48 | 0.00 | 389.17 | 567.23 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.52 | 14.66 | 0.00 | 311.17 | 535.98 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.67 | 12.50 | 0.00 | 255.67 | 398.59 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.67 | 10.41 | 0.00 | 184.00 | 278.51 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.08 | 10.25 | 0.00 | 145.00 | 259.03 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.66 | 14.06 | 130.33 | 3536.50 | 515.85 | 17.78 | 212.67 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.08 | 10.05 | 0.00 | 145.00 | 258.54 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.96 | 18.31 | 59.00 | 420.83 | 732.10 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.65 | 18.46 | 64.83 | 197.67 | 538.11 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.40 | 19.45 | 66.50 | 227.17 | 721.52 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.33 | 21.74 | 78.17 | 302.17 | 1215.08 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.70 | 20.40 | 105.50 | 342.00 | 1185.20 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2827.03 | 17.22 | 52.33 | 389.67 | 1514.42 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.82 | 16.84 | 42.83 | 398.50 | 1290.58 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.66 | 15.98 | 58.83 | 399.00 | 1377.42 | 17.07 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.21 | 18.82 | 75.83 | 376.67 | 1722.52 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.71 | 22.57 | 100.50 | 312.67 | 1840.65 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.19 | 21.93 | 87.33 | 269.00 | 991.96 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.57 | 18.40 | 62.83 | 206.83 | 559.45 | 20.38 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.11 | 19.91 | 48.67 | 180.50 | 560.32 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.21 | 18.98 | 844.17 | 3601.83 | 1211.87 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.65 | 15.98 | 42.83 | 180.50 | 538.11 | 17.07 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.71 | 22.57 | 105.50 | 399.00 | 1840.65 | 23.51 | 91.33 | 358.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.29 | 30.49 | 207.17 | 216.17 | 2123.78 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.23 | 32.09 | 231.50 | 240.50 | 1973.30 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.32 | 32.25 | 207.67 | 309.83 | 1574.14 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.28 | 14.68 | 0.00 | 342.83 | 1140.35 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.67 | 14.64 | 0.00 | 382.67 | 1033.37 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.64 | 14.46 | 0.00 | 392.00 | 952.20 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.30 | 13.10 | 0.00 | 389.33 | 863.19 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.09 | 14.23 | 0.00 | 369.33 | 1040.46 | 17.80 | 5.83 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.65 | 17.25 | 27.00 | 317.83 | 1375.02 | 19.08 | 29.67 | 282.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.63 | 33.75 | 218.00 | 282.33 | 1850.07 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.96 | 30.64 | 215.33 | 222.17 | 2388.97 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.91 | 34.93 | 149.17 | 204.83 | 3041.45 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.73 | 21.19 | 1255.83 | 3669.83 | 1443.60 | 21.56 | 847.33 | 3189.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.30 | 13.10 | 0.00 | 204.83 | 863.19 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.32 | 34.93 | 231.50 | 392.00 | 3041.45 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.60 | 18.45 | 61.33 | 197.00 | 546.60 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.92 | 19.19 | 68.00 | 225.50 | 754.66 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.95 | 21.61 | 79.00 | 300.00 | 1137.86 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.63 | 20.65 | 105.33 | 344.50 | 1525.38 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.53 | 20.60 | 132.33 | 388.33 | 1209.26 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.63 | 19.81 | 89.00 | 400.83 | 1614.50 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.66 | 20.14 | 146.50 | 404.00 | 1242.95 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3195.99 | 20.23 | 98.50 | 373.50 | 1398.12 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.27 | 21.30 | 82.67 | 319.67 | 1474.15 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.28 | 21.29 | 81.00 | 267.83 | 1047.35 | 22.42 | 76.83 | 221.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.33 | 18.45 | 65.67 | 203.67 | 572.09 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.36 | 21.01 | 56.33 | 178.83 | 556.68 | 21.89 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.47 | 20.24 | 1065.67 | 3603.67 | 1167.45 | 21.81 | 909.33 | 2981.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.60 | 18.45 | 56.33 | 178.83 | 546.60 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3195.99 | 21.61 | 146.50 | 404.00 | 1614.50 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.83 | 10.05 | 0.00 | 172.50 | 258.52 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 597.99 | 11.55 | 0.00 | 210.33 | 340.46 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.51 | 13.48 | 0.00 | 293.00 | 480.83 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.69 | 14.26 | 0.00 | 346.00 | 551.68 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.23 | 16.06 | 26.67 | 397.83 | 676.39 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.93 | 18.31 | 59.00 | 411.00 | 732.06 | 21.51 | 73.33 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.25 | 15.66 | 44.67 | 420.83 | 631.59 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.70 | 14.48 | 0.00 | 389.17 | 567.20 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.50 | 14.66 | 0.00 | 311.17 | 535.95 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.65 | 12.50 | 0.00 | 255.67 | 398.56 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.64 | 10.42 | 0.00 | 184.00 | 278.48 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.06 | 10.25 | 0.00 | 145.00 | 259.01 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.63 | 14.06 | 130.33 | 3536.50 | 515.82 | 17.78 | 212.83 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.06 | 10.05 | 0.00 | 145.00 | 258.52 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.93 | 18.31 | 59.00 | 420.83 | 732.06 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.62 | 18.46 | 64.83 | 197.67 | 538.07 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.37 | 19.45 | 66.50 | 227.17 | 721.47 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.28 | 21.75 | 78.17 | 302.17 | 1215.01 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.64 | 20.41 | 105.50 | 342.00 | 1185.12 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2826.95 | 17.22 | 52.33 | 389.67 | 1514.34 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.76 | 16.84 | 42.83 | 398.50 | 1290.51 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.60 | 15.98 | 58.83 | 399.00 | 1377.35 | 17.08 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.18 | 18.82 | 75.83 | 376.67 | 1722.46 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.68 | 22.57 | 100.50 | 312.67 | 1840.58 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.16 | 21.93 | 87.33 | 269.00 | 991.91 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.54 | 18.41 | 62.83 | 206.83 | 559.41 | 20.39 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.10 | 19.91 | 48.67 | 180.50 | 560.29 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.16 | 18.98 | 844.17 | 3601.83 | 1211.81 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.62 | 15.98 | 42.83 | 180.50 | 538.07 | 17.08 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.68 | 22.57 | 105.50 | 399.00 | 1840.58 | 23.51 | 91.33 | 358.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.736503E+09 | 20971.27 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1424102.87 | 16614.53 | 21-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2702330.79 | 20971.27 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.740629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.736503E+09 | 20971.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.493897E+10 | 10214.27 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287559E+10 | 10214.27 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197845E+10 | 10214.27 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109171E+10 | 10214.27 | 03-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.663574E+09 | 10214.27 | 10-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.302692E+09 | 10214.27 | 01-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68359653.24 | 5959.04 | 13-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76524321.63 | 8598.06 | 03-AUG-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.276305E+09 | 10214.27 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.956558E+09 | 10214.27 | 05-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257105E+10 | 10214.27 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383605E+10 | 10214.27 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 68359653.24 | 5959.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.493897E+10 | 10214.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155067E+10 | 6818.64 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.626692E+09 | 6818.64 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98185885.66 | 6818.64 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8427585.53 | 5876.98 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5372862.13 | 2444.33 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261237E+09 | 6818.64 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883976E+09 | 6818.64 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155067E+10 | 6818.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258267E+10 | 6776.40 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124349E+10 | 6738.54 | 25-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302740E+09 | 6733.45 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37039009.83 | 6721.35 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13750910.07 | 6639.60 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.458296E+09 | 6728.97 | 21-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149582E+10 | 6748.02 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.613381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258267E+10 | 6776.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156283E+10 | 6771.87 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.640378E+09 | 6771.87 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117484E+09 | 6771.87 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13389624.08 | 6771.87 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3839990.50 | 1446.57 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267510E+09 | 6771.87 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.889306E+09 | 6771.87 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156283E+10 | 6771.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160784E+10 | 20976.94 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296195E+09 | 20976.94 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9655555.15 | 20976.94 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91345454.28 | 20976.94 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.521501E+09 | 20976.94 | 11-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160784E+10 | 20976.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154933E+10 | 10919.91 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569472E+09 | 10919.91 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91020535.78 | 10919.91 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14762047.49 | 8146.92 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17101589.07 | 6034.92 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399041E+09 | 10919.91 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105187E+10 | 10919.91 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154933E+10 | 10919.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121546E+10 | 7249.96 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481900E+09 | 7249.96 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63196658.09 | 7249.96 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6681292.41 | 5633.50 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15542010.94 | 6073.36 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324609E+09 | 7249.96 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827417E+09 | 7249.96 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121546E+10 | 7249.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214245E+10 | 7549.04 | 03-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.920221E+09 | 7561.11 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140841E+09 | 7511.55 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17466170.17 | 7458.66 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25043754.23 | 7489.79 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.570861E+09 | 7548.70 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145759E+10 | 7564.94 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.527447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214245E+10 | 7564.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131050E+10 | 7207.54 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526930E+09 | 7207.54 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85361136.38 | 7207.54 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11802521.48 | 7175.25 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16938886.69 | 5262.19 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355407E+09 | 7207.54 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.890326E+09 | 7207.54 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131050E+10 | 7207.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390963E+10 | 29742.35 | 06-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159702E+10 | 29760.74 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210918E+09 | 29538.74 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8678882.53 | 11165.06 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35143181.63 | 29526.46 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106739E+10 | 29724.98 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266346E+10 | 29773.70 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.949224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390963E+10 | 29773.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255962E+10 | 13951.29 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124809E+10 | 13951.29 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398169E+09 | 13951.29 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111588E+09 | 13951.29 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4575101.28 | 6551.49 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1219752.63 | 1131.33 | 27-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143237E+09 | 12197.21 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102936E+10 | 13951.29 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203079E+10 | 13951.29 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.255962E+10 | 13951.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204243E+10 | 9175.24 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102782E+10 | 9175.24 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270393E+09 | 9175.24 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51480129.50 | 7840.51 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3106415.39 | 4397.77 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 590085.22 | 1069.66 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113549E+09 | 7968.45 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804200E+09 | 9175.24 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160988E+10 | 9175.24 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204243E+10 | 9175.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.337621E+10 | 8557.96 | 30-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185103E+10 | 8556.11 | 16-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.579559E+09 | 8548.50 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135439E+09 | 8500.28 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4377632.85 | 6251.77 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2594413.33 | 1568.03 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214524E+09 | 8528.61 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137429E+10 | 8558.97 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271285E+10 | 8558.88 | 01-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.337621E+10 | 8558.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208672E+10 | 9133.27 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109384E+10 | 9133.27 | 01-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343119E+09 | 9133.27 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84216936.89 | 9133.27 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2918606.35 | 4493.59 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1099472.56 | 776.65 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128718E+09 | 7860.78 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.851316E+09 | 9133.27 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166787E+10 | 9133.27 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208672E+10 | 9133.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.768264E+10 | 15773.11 | 07-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510813E+10 | 14377.88 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247508E+10 | 11290.60 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.950549E+09 | 8365.63 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169065E+09 | 4244.02 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9765936.32 | 1504.06 | 28-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358348E+09 | 4449.18 | 16-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348266E+10 | 11011.84 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643151E+10 | 15504.29 | 26-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.768264E+10 | 15773.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.778784E+10 | 14212.70 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526594E+10 | 13768.64 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283196E+10 | 11741.69 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123549E+10 | 8787.39 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.289710E+09 | 4890.69 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7821895.73 | 1198.97 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35986908.73 | 2446.95 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662002E+09 | 5066.95 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.389728E+10 | 10640.43 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.669622E+10 | 15038.67 | 26-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.778784E+10 | 15038.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.826169E+10 | 16261.38 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.562720E+10 | 15292.56 | 18-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325861E+10 | 14416.69 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151773E+10 | 11048.29 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.440601E+09 | 6119.75 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24288463.01 | 2050.19 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80283568.16 | 3402.47 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949481E+09 | 5867.46 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.426234E+10 | 13326.64 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717584E+10 | 14337.43 | 26-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.826169E+10 | 16261.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.153466E+09 | 0.129906E+09 | 9264.50 | 27-FEB-15:00 | 8747.95 | 0.00 |
March | 0.00 | 0.00 | 0.241679E+09 | 0.208106E+09 | 8669.36 | 18-MAR-16:00 | 8669.36 | 0.00 |
April | 0.00 | 0.00 | 0.299937E+10 | 0.286476E+10 | 43642.71 | 27-APR-15:10 | 43642.71 | 0.00 |
May | 0.00 | 0.00 | 0.632180E+10 | 0.558671E+10 | 39122.75 | 15-MAY-16:00 | 39122.75 | 0.00 |
June | 0.00 | 0.00 | 0.120750E+11 | 0.111838E+11 | 45213.25 | 28-JUN-15:30 | 45213.25 | 0.00 |
July | 0.00 | 0.00 | 0.235073E+11 | 0.207453E+11 | 61655.09 | 31-JUL-16:00 | 55528.19 | 0.00 |
August | 0.00 | 0.00 | 0.322120E+11 | 0.281689E+11 | 62695.59 | 10-AUG-16:10 | 52057.69 | 0.00 |
September | 0.00 | 0.00 | 0.118529E+11 | 0.988592E+10 | 49895.81 | 14-SEP-13:00 | 36470.49 | 0.00 |
October | 0.00 | 0.00 | 0.167275E+10 | 0.156542E+10 | 29428.52 | 04-OCT-15:10 | 29428.52 | 0.00 |
November | 0.00 | 0.00 | 0.298228E+09 | 0.199938E+09 | 15619.93 | 04-NOV-14:30 | 11401.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.913345E+11 | 0.805387E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.322120E+11 | 0.281689E+11 | 62695.59 | 55528.19 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.171996E+09 | 0.156607E+09 | 11209.27 | 27-FEB-15:10 | 11209.27 | 0.00 |
March | 0.00 | 0.00 | 0.263744E+09 | 0.234829E+09 | 10336.84 | 18-MAR-14:05 | 10336.84 | 0.00 |
April | 0.00 | 0.00 | 0.315794E+10 | 0.303555E+10 | 46804.27 | 27-APR-14:05 | 46804.27 | 0.00 |
May | 0.00 | 0.00 | 0.658760E+10 | 0.590408E+10 | 40885.32 | 04-MAY-15:00 | 40885.32 | 0.00 |
June | 0.00 | 0.00 | 0.121103E+11 | 0.112738E+11 | 45571.99 | 28-JUN-15:20 | 45571.99 | 0.00 |
July | 0.00 | 0.00 | 0.230205E+11 | 0.204493E+11 | 63791.86 | 31-JUL-14:05 | 57029.56 | 0.00 |
August | 0.00 | 0.00 | 0.303617E+11 | 0.266374E+11 | 63286.44 | 10-AUG-14:05 | 57193.13 | 0.00 |
September | 0.00 | 0.00 | 0.113887E+11 | 0.951608E+10 | 50647.38 | 13-SEP-14:05 | 39551.60 | 0.00 |
October | 0.00 | 0.00 | 0.143027E+10 | 0.134291E+10 | 29245.80 | 04-OCT-15:00 | 29245.80 | 0.00 |
November | 0.00 | 0.00 | 0.324191E+09 | 0.227850E+09 | 17413.29 | 04-NOV-14:05 | 13606.47 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.888169E+11 | 0.787783E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.303617E+11 | 0.266374E+11 | 63791.86 | 57193.13 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.178697E+09 | 0.157962E+09 | 11363.51 | 27-FEB-15:00 | 11363.51 | 0.00 |
March | 0.00 | 0.00 | 0.374237E+09 | 0.338995E+09 | 10258.88 | 18-MAR-16:00 | 10258.88 | 0.00 |
April | 0.00 | 0.00 | 0.337367E+10 | 0.321797E+10 | 53302.37 | 27-APR-14:40 | 53302.37 | 0.00 |
May | 0.00 | 0.00 | 0.699082E+10 | 0.620557E+10 | 44774.13 | 04-MAY-15:00 | 44774.13 | 0.00 |
June | 0.00 | 0.00 | 0.128638E+11 | 0.118833E+11 | 53282.03 | 28-JUN-15:20 | 53282.03 | 0.00 |
July | 0.00 | 0.00 | 0.246341E+11 | 0.216866E+11 | 70028.74 | 31-JUL-14:40 | 63423.45 | 0.00 |
August | 0.00 | 0.00 | 0.321963E+11 | 0.281259E+11 | 70120.95 | 10-AUG-14:50 | 65117.13 | 0.00 |
September | 0.00 | 0.00 | 0.115020E+11 | 0.948223E+10 | 50356.14 | 14-SEP-13:30 | 40122.58 | 0.00 |
October | 0.00 | 0.00 | 0.132918E+10 | 0.122942E+10 | 28620.45 | 04-OCT-15:00 | 28620.45 | 0.00 |
November | 0.00 | 0.00 | 0.331765E+09 | 0.225674E+09 | 17781.58 | 04-NOV-14:10 | 13289.64 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.937745E+11 | 0.825536E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.321963E+11 | 0.281259E+11 | 70120.95 | 65117.13 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1828.35 | 6360.54 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1850.49 | 6388.81 | 07-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1951.23 | 6362.41 | 02-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1776.09 | 6223.72 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1776.51 | 6038.96 | 01-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1758.93 | 5784.47 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1571.63 | 5610.38 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1714.12 | 5520.53 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1621.08 | 5637.34 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1667.86 | 5852.70 | 30-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1754.79 | 6071.77 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1741.08 | 6250.25 | 26-DEC-12:06 |
Annual Sum or Average | 0.00 | 1750.45 | ||||
Minimum of Months | 0.00 | 0.00 | 1571.63 | 5520.53 | ||
Maximum of Months | 0.00 | 0.00 | 1951.23 | 6388.81 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107202E+10 | 0.29 | 2375.13 | 02-JAN-06:11 | 0.78 |
February | 0.931973E+09 | 0.28 | 1459.75 | 06-FEB-06:11 | 0.61 |
March | 0.120599E+10 | 0.30 | 1459.75 | 01-MAR-07:02 | 0.62 |
April | 0.142450E+10 | 0.30 | 4615.47 | 27-APR-15:10 | 1.14 |
May | 0.200493E+10 | 0.34 | 5137.45 | 15-MAY-15:10 | 1.23 |
June | 0.252909E+10 | 0.38 | 5280.29 | 28-JUN-15:10 | 1.24 |
July | 0.323600E+10 | 0.41 | 7580.49 | 24-JUL-15:10 | 1.56 |
August | 0.386850E+10 | 0.46 | 8035.17 | 14-AUG-15:30 | 1.61 |
September | 0.251457E+10 | 0.37 | 7048.87 | 11-SEP-15:40 | 1.49 |
October | 0.154009E+10 | 0.30 | 5031.84 | 04-OCT-15:30 | 1.21 |
November | 0.104369E+10 | 0.27 | 1459.75 | 24-NOV-06:11 | 0.61 |
December | 0.100969E+10 | 0.27 | 2375.13 | 26-DEC-07:01 | 0.78 |
Annual Sum or Average | 0.223811E+11 | 0.33 | |||
Minimum of Months | 0.931973E+09 | 0.27 | 1459.75 | 0.61 | |
Maximum of Months | 0.386850E+10 | 0.46 | 8035.17 | 1.61 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.100802E+10 | 0.29 | 2531.46 | 02-JAN-06:11 | 0.83 |
February | 0.906073E+09 | 0.28 | 2531.46 | 06-FEB-07:02 | 0.83 |
March | 0.113703E+10 | 0.30 | 2174.23 | 01-MAR-13:01 | 0.77 |
April | 0.140420E+10 | 0.31 | 6102.50 | 27-APR-14:05 | 1.40 |
May | 0.201721E+10 | 0.35 | 6422.56 | 15-MAY-14:05 | 1.45 |
June | 0.250514E+10 | 0.40 | 5838.17 | 28-JUN-14:05 | 1.36 |
July | 0.315047E+10 | 0.42 | 8361.76 | 31-JUL-14:05 | 1.71 |
August | 0.360508E+10 | 0.46 | 8619.23 | 14-AUG-06:02 | 1.74 |
September | 0.231381E+10 | 0.37 | 7297.12 | 11-SEP-15:00 | 1.57 |
October | 0.132798E+10 | 0.29 | 4894.92 | 04-OCT-15:10 | 1.23 |
November | 0.940017E+09 | 0.28 | 2531.46 | 24-NOV-07:01 | 0.83 |
December | 0.955626E+09 | 0.27 | 2531.46 | 11-DEC-07:02 | 0.83 |
Annual Sum or Average | 0.212706E+11 | 0.34 | |||
Minimum of Months | 0.906073E+09 | 0.27 | 2174.23 | 0.77 | |
Maximum of Months | 0.360508E+10 | 0.46 | 8619.23 | 1.74 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119527E+10 | 0.33 | 2409.04 | 02-JAN-06:11 | 0.76 |
February | 0.102604E+10 | 0.31 | 2409.04 | 06-FEB-06:11 | 0.76 |
March | 0.119580E+10 | 0.32 | 2409.04 | 06-MAR-06:11 | 0.76 |
April | 0.139105E+10 | 0.31 | 5840.96 | 27-APR-14:30 | 1.26 |
May | 0.192951E+10 | 0.35 | 6357.33 | 15-MAY-14:40 | 1.34 |
June | 0.236436E+10 | 0.38 | 5972.65 | 28-JUN-15:20 | 1.28 |
July | 0.300003E+10 | 0.40 | 8138.86 | 31-JUL-14:40 | 1.55 |
August | 0.335926E+10 | 0.43 | 8127.68 | 10-AUG-15:20 | 1.55 |
September | 0.208173E+10 | 0.35 | 6571.33 | 11-SEP-14:40 | 1.36 |
October | 0.126242E+10 | 0.30 | 4228.45 | 04-OCT-14:50 | 1.05 |
November | 0.102745E+10 | 0.30 | 2409.04 | 13-NOV-06:01 | 0.76 |
December | 0.107361E+10 | 0.30 | 2409.04 | 04-DEC-06:11 | 0.76 |
Annual Sum or Average | 0.209065E+11 | 0.34 | |||
Minimum of Months | 0.102604E+10 | 0.30 | 2409.04 | 0.76 | |
Maximum of Months | 0.335926E+10 | 0.43 | 8138.86 | 1.55 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 57.70 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 56.52 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.03 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 55.22 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 56.36 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.93 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.02 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.34 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.55 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.48 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 55.48 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 55.94 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 55.22 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.70 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.78 | 57.78 | 1828.35 | 6360.54 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.22 | 57.22 | 1850.49 | 6388.81 | 07-FEB-12:06 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.58 | 56.58 | 1951.23 | 6362.41 | 02-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.88 | 55.88 | 1776.09 | 6223.72 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.93 | 56.93 | 1776.51 | 6038.96 | 01-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.40 | 57.40 | 1758.93 | 5784.47 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.51 | 57.51 | 1571.63 | 5610.38 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.75 | 56.75 | 1714.12 | 5520.53 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.98 | 56.98 | 1621.08 | 5637.34 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.12 | 56.12 | 1667.86 | 5852.70 | 30-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.09 | 56.09 | 1754.79 | 6071.77 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.66 | 56.66 | 1741.08 | 6250.25 | 26-DEC-12:06 |
Annual Sum or Average | 0.00 | 1750.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.88 | 55.88 | 1571.63 | 5520.53 | ||
Maximum of Months | 0.00 | 0.00 | 57.78 | 57.78 | 1951.23 | 6388.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124437E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.635989E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.376755E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.329690E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.417688E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.570103E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.879405E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.115062E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.555131E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.293578E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.467545E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.811755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.773263E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.293578E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.124437E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.883362E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.374544E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159691E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.221029E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.357737E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.537399E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.851689E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.107373E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.496470E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.175443E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.276002E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.570433E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.597753E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159691E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107373E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.151699E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.789049E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.309734E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.259171E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.360358E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.542112E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.876263E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.109633E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.478103E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.222934E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.623543E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.117585E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.825043E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.222934E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.151699E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107202E+10 | 0.00 | 0.190543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.931973E+09 | 0.153466E+09 | 0.104957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120599E+10 | 0.241679E+09 | 0.497194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142450E+10 | 0.299937E+10 | 0.210112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200493E+10 | 0.632180E+10 | 0.832639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252909E+10 | 0.120750E+11 | 0.302692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323600E+10 | 0.235073E+11 | 68359653.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.386850E+10 | 0.322120E+11 | 76524321.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251457E+10 | 0.118529E+11 | 0.286071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154009E+10 | 0.167275E+10 | 0.133787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104369E+10 | 0.298228E+09 | 0.704075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100969E+10 | 0.00 | 0.135394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223811E+11 | 0.913345E+11 | 0.601073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.931973E+09 | 0.00 | 68359653.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386850E+10 | 0.322120E+11 | 0.190543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.100802E+10 | 0.00 | 0.156134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906073E+09 | 0.171996E+09 | 0.806066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113703E+10 | 0.263744E+09 | 0.322204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140420E+10 | 0.315794E+10 | 0.128620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201721E+10 | 0.658760E+10 | 0.289710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250514E+10 | 0.121103E+11 | 7821895.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.315047E+10 | 0.230205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.360508E+10 | 0.303617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231381E+10 | 0.113887E+11 | 35986908.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132798E+10 | 0.143027E+10 | 0.736628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.940017E+09 | 0.324191E+09 | 0.563854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.955626E+09 | 0.00 | 0.114449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212706E+11 | 0.888169E+11 | 0.463359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.906073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.360508E+10 | 0.303617E+11 | 0.156134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119527E+10 | 0.00 | 0.222363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102604E+10 | 0.178697E+09 | 0.124450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119580E+10 | 0.374237E+09 | 0.506077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139105E+10 | 0.337367E+10 | 0.190913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192951E+10 | 0.699082E+10 | 0.455578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236436E+10 | 0.128638E+11 | 24288463.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300003E+10 | 0.246341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.335926E+10 | 0.321963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208173E+10 | 0.115020E+11 | 85787291.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126242E+10 | 0.132918E+10 | 0.158465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102745E+10 | 0.331765E+09 | 0.938889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107361E+10 | 0.00 | 0.178607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209065E+11 | 0.937745E+11 | 0.710511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.335926E+10 | 0.321963E+11 | 0.222363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.931973E+09 | 0.00 | 0.00 | 0.00 | 40340009.80 | 0.538758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120599E+10 | 0.00 | 0.00 | 0.00 | 64704698.98 | 0.249686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142450E+10 | 0.00 | 0.00 | 0.00 | 0.721826E+09 | 0.115057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200493E+10 | 0.00 | 0.00 | 0.00 | 0.150837E+10 | 0.663574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252909E+10 | 0.00 | 0.00 | 0.00 | 0.286925E+10 | 0.302692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323600E+10 | 0.00 | 0.00 | 0.00 | 0.548968E+10 | 68359653.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.386850E+10 | 0.00 | 0.00 | 0.00 | 0.756122E+10 | 76524321.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251457E+10 | 0.00 | 0.00 | 0.00 | 0.276043E+10 | 0.276305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154009E+10 | 0.00 | 0.00 | 0.00 | 0.416172E+09 | 0.979522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104369E+10 | 0.00 | 0.00 | 0.00 | 73664517.85 | 0.355809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223811E+11 | 0.00 | 0.00 | 0.00 | 0.215057E+11 | 0.334396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.931973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68359653.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386850E+10 | 0.00 | 0.00 | 0.00 | 0.756122E+10 | 0.113716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.100802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906073E+09 | 0.00 | 0.00 | 0.00 | 44644388.23 | 0.279472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113703E+10 | 0.00 | 0.00 | 0.00 | 69804412.57 | 0.390075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140420E+10 | 0.00 | 0.00 | 0.00 | 0.755381E+09 | 50712031.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201721E+10 | 0.00 | 0.00 | 0.00 | 0.156016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250514E+10 | 0.00 | 0.00 | 0.00 | 0.286885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.315047E+10 | 0.00 | 0.00 | 0.00 | 0.536643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.360508E+10 | 0.00 | 0.00 | 0.00 | 0.713226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231381E+10 | 0.00 | 0.00 | 0.00 | 0.265089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132798E+10 | 0.00 | 0.00 | 0.00 | 0.351827E+09 | 74626240.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.940017E+09 | 0.00 | 0.00 | 0.00 | 78739226.66 | 0.174126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.955626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212706E+11 | 0.00 | 0.00 | 0.00 | 0.208790E+11 | 0.176257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.906073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.360508E+10 | 0.00 | 0.00 | 0.00 | 0.713226E+10 | 0.782559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.119527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102604E+10 | 0.00 | 0.00 | 0.00 | 46645749.08 | 0.681781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119580E+10 | 0.00 | 0.00 | 0.00 | 99383480.94 | 0.180216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139105E+10 | 0.00 | 0.00 | 0.00 | 0.809259E+09 | 0.391403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192951E+10 | 0.00 | 0.00 | 0.00 | 0.165909E+10 | 14977755.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236436E+10 | 0.00 | 0.00 | 0.00 | 0.305676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300003E+10 | 0.00 | 0.00 | 0.00 | 0.576260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.335926E+10 | 0.00 | 0.00 | 0.00 | 0.760406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208173E+10 | 0.00 | 0.00 | 0.00 | 0.269379E+10 | 5503723.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126242E+10 | 0.00 | 0.00 | 0.00 | 0.331752E+09 | 0.635172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102745E+10 | 0.00 | 0.00 | 0.00 | 81432879.65 | 0.512655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209065E+11 | 0.00 | 0.00 | 0.00 | 0.221448E+11 | 0.394530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.335926E+10 | 0.00 | 0.00 | 0.00 | 0.760406E+10 | 0.139746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108745E+11 | 0.00 | 0.00 | 504095.78 | 0.00 | 0.355761E+09 | 0.112870E+10 | 0.00 | 0.28 |
February | 0.697504E+10 | 0.00 | 0.00 | 4600425.09 | 0.00 | 622545.54 | 0.437608E+10 | 0.00 | 0.31 |
March | 0.485896E+10 | 0.00 | 0.00 | 16298485.78 | 0.00 | 0.00 | 0.976203E+10 | 0.00 | 0.39 |
April | 0.176820E+10 | 6749974.69 | 0.00 | 22567569.14 | 5380217.24 | 0.00 | 0.126020E+11 | 0.00 | 0.48 |
May | 0.104637E+10 | 6734056.31 | 0.00 | 33987984.37 | 0.00 | 0.00 | 0.166822E+11 | 0.00 | 0.72 |
June | 0.904891E+09 | 6520882.68 | 0.00 | 36540933.09 | 1268881.39 | 0.00 | 0.158268E+11 | 0.00 | 0.87 |
July | 0.782023E+09 | 0.111532E+09 | 0.00 | 33014311.27 | 14817326.51 | 0.00 | 0.113245E+11 | 0.00 | 0.84 |
August | 0.639550E+09 | 0.339700E+09 | 0.00 | 32655032.77 | 13122239.30 | 0.00 | 0.998573E+10 | 0.00 | 0.83 |
September | 0.896746E+09 | 5364097.96 | 0.00 | 34205534.56 | 0.00 | 0.00 | 0.146247E+11 | 0.00 | 0.81 |
October | 0.177172E+10 | 0.00 | 0.00 | 24584289.38 | 0.00 | 0.00 | 0.140371E+11 | 0.00 | 0.53 |
November | 0.492414E+10 | 0.00 | 0.00 | 10300555.40 | 0.00 | 0.00 | 0.772199E+10 | 0.00 | 0.35 |
December | 0.856783E+10 | 0.00 | 0.00 | 3822002.57 | 0.00 | 1136471.76 | 0.383090E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.440100E+11 | 0.476600E+09 | 0.00 | 0.253081E+09 | 34588664.44 | 0.357520E+09 | 0.121903E+12 | 0.00 | 0.56 |
Minimum of Months | 0.639550E+09 | 0.00 | 0.00 | 504095.78 | 0.00 | 0.00 | 0.112870E+10 | 0.00 | 0.28 |
Maximum of Months | 0.108745E+11 | 0.339700E+09 | 0.00 | 36540933.09 | 14817326.51 | 0.355761E+09 | 0.166822E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786195E+09 | 0.00 | 0.00 | 0.29 |
February | 0.103966E+11 | 0.00 | 0.00 | 85128.50 | 0.00 | 67603953.83 | 0.254478E+09 | 0.00 | 0.30 |
March | 0.920259E+10 | 0.00 | 0.00 | 2289583.93 | 0.00 | 743776.00 | 0.294651E+10 | 0.00 | 0.33 |
April | 0.525553E+10 | 4892665.58 | 0.00 | 9169328.70 | 5850677.03 | 0.00 | 0.598314E+10 | 0.00 | 0.38 |
May | 0.281249E+10 | 4305974.20 | 0.00 | 19807218.67 | 0.00 | 0.00 | 0.106071E+11 | 0.00 | 0.55 |
June | 0.130018E+10 | 4343282.48 | 0.00 | 24485956.68 | 1296173.73 | 0.00 | 0.114814E+11 | 0.00 | 0.67 |
July | 0.102742E+10 | 90783830.91 | 0.00 | 23652738.45 | 8646878.06 | 0.00 | 0.828594E+10 | 0.00 | 0.65 |
August | 0.859464E+09 | 0.276884E+09 | 0.00 | 22819755.01 | 9348055.84 | 0.00 | 0.724963E+10 | 0.00 | 0.64 |
September | 0.206558E+10 | 3533285.27 | 0.00 | 20246945.80 | 661713.08 | 0.00 | 0.925955E+10 | 0.00 | 0.60 |
October | 0.536280E+10 | 0.00 | 0.00 | 8682163.85 | 0.00 | 0.00 | 0.628022E+10 | 0.00 | 0.39 |
November | 0.967048E+10 | 0.00 | 0.00 | 865131.18 | 0.00 | 17775709.50 | 0.124683E+10 | 0.00 | 0.30 |
December | 0.115779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263036E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.709283E+11 | 0.384743E+09 | 0.00 | 0.132104E+09 | 25803497.74 | 0.113535E+10 | 0.635947E+11 | 0.00 | 0.45 |
Minimum of Months | 0.859464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.115779E+11 | 0.276884E+09 | 0.00 | 24485956.68 | 9348055.84 | 0.786195E+09 | 0.114814E+11 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.917854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232498E+10 | 0.00 | 0.00 | 0.28 |
February | 0.916828E+10 | 0.00 | 0.00 | 42266.25 | 0.00 | 0.847952E+09 | 0.110525E+09 | 0.00 | 0.30 |
March | 0.102328E+11 | 0.00 | 0.00 | 858363.49 | 0.00 | 76114389.08 | 0.122536E+10 | 0.00 | 0.33 |
April | 0.613832E+10 | 1216928.31 | 0.00 | 6399647.47 | 149260.41 | 2824944.35 | 0.468490E+10 | 0.00 | 0.38 |
May | 0.371903E+10 | 1188898.35 | 0.00 | 16762975.44 | 0.00 | 0.00 | 0.929945E+10 | 0.00 | 0.54 |
June | 0.209328E+10 | 1355422.23 | 0.00 | 21770323.81 | 784856.30 | 0.00 | 0.104810E+11 | 0.00 | 0.67 |
July | 0.168392E+10 | 72980212.07 | 0.00 | 20954140.77 | 12982003.49 | 0.00 | 0.755387E+10 | 0.00 | 0.67 |
August | 0.131916E+10 | 0.212563E+09 | 0.00 | 20076668.34 | 22583316.37 | 0.00 | 0.609410E+10 | 0.00 | 0.63 |
September | 0.311579E+10 | 1014606.84 | 0.00 | 14841838.68 | 0.00 | 0.00 | 0.710186E+10 | 0.00 | 0.56 |
October | 0.694209E+10 | 0.00 | 0.00 | 4233887.39 | 0.00 | 3682033.37 | 0.343928E+10 | 0.00 | 0.36 |
November | 0.954365E+10 | 0.00 | 0.00 | 22222.89 | 0.00 | 0.312372E+09 | 0.215632E+09 | 0.00 | 0.30 |
December | 0.952886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145621E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.726637E+11 | 0.290319E+09 | 0.00 | 0.105962E+09 | 36499436.57 | 0.502414E+10 | 0.502060E+11 | 0.00 | 0.44 |
Minimum of Months | 0.131916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.102328E+11 | 0.212563E+09 | 0.00 | 21770323.81 | 22583316.37 | 0.232498E+10 | 0.104810E+11 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.529456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197337E+10 | 0.00 | 0.00 | 0.29 |
February | 0.930660E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124429E+10 | 0.00 | 0.00 | 0.30 |
March | 0.209002E+10 | 0.00 | 0.00 | 4784.56 | 0.00 | 0.338188E+09 | 14596328.94 | 0.00 | 0.33 |
April | 0.156838E+10 | 353998.59 | 0.00 | 1013788.07 | 31515.60 | 79789092.78 | 0.622235E+09 | 0.00 | 0.38 |
May | 0.105035E+10 | 532548.46 | 0.00 | 3664183.12 | 0.00 | 2951498.85 | 0.187997E+10 | 0.00 | 0.60 |
June | 0.594990E+09 | 419452.20 | 0.00 | 5320130.01 | 165718.56 | 0.00 | 0.234879E+10 | 0.00 | 0.79 |
July | 0.428002E+09 | 23097592.80 | 0.00 | 5433970.38 | 2741086.39 | 0.00 | 0.183577E+10 | 0.00 | 0.82 |
August | 0.404761E+09 | 66190058.74 | 0.00 | 4610840.34 | 4687627.42 | 0.00 | 0.127592E+10 | 0.00 | 0.73 |
September | 0.100274E+10 | 272608.46 | 0.00 | 2688175.89 | 0.00 | 924309.54 | 0.113288E+10 | 0.00 | 0.58 |
October | 0.173203E+10 | 0.00 | 0.00 | 341954.11 | 0.00 | 0.121009E+09 | 0.270409E+09 | 0.00 | 0.35 |
November | 0.118516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958030E+09 | 0.00 | 0.00 | 0.30 |
December | 0.631978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174007E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.121485E+11 | 90866259.25 | 0.00 | 23077826.47 | 7625947.98 | 0.645862E+10 | 0.938057E+10 | 0.00 | 0.48 |
Minimum of Months | 0.404761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.209002E+10 | 66190058.74 | 0.00 | 5433970.38 | 4687627.42 | 0.197337E+10 | 0.234879E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.455449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113122E+10 | 0.00 | 0.00 | 0.29 |
February | 0.703899E+09 | 0.00 | 0.00 | 2747.63 | 0.00 | 0.664530E+09 | 5864744.16 | 0.00 | 0.30 |
March | 0.113472E+10 | 0.00 | 0.00 | 511112.61 | 0.00 | 0.146775E+09 | 0.347970E+09 | 0.00 | 0.35 |
April | 0.705556E+09 | 324838.40 | 0.00 | 2714535.21 | 0.00 | 25193552.34 | 0.139597E+10 | 0.00 | 0.58 |
May | 0.498206E+09 | 474629.36 | 0.00 | 4714039.78 | 0.00 | 1898502.74 | 0.229255E+10 | 0.00 | 0.90 |
June | 0.255169E+09 | 290786.20 | 0.00 | 6849774.96 | 104575.41 | 0.00 | 0.299812E+10 | 0.00 | 1.30 |
July | 0.195689E+09 | 19823975.14 | 0.00 | 6783525.99 | 843436.06 | 0.00 | 0.212242E+10 | 0.00 | 1.29 |
August | 0.162652E+09 | 59490098.33 | 0.00 | 6651006.31 | 859930.84 | 0.00 | 0.164554E+10 | 0.00 | 1.27 |
September | 0.484675E+09 | 305769.29 | 0.00 | 4199257.67 | 0.00 | 583278.38 | 0.165690E+10 | 0.00 | 0.93 |
October | 0.873552E+09 | 0.00 | 0.00 | 1154478.73 | 0.00 | 64847713.69 | 0.693284E+09 | 0.00 | 0.43 |
November | 0.811944E+09 | 0.00 | 0.00 | 1124.25 | 0.00 | 0.539260E+09 | 3821383.52 | 0.00 | 0.30 |
December | 0.521706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985199E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.680322E+10 | 80710096.73 | 0.00 | 33581603.13 | 1807942.31 | 0.355950E+10 | 0.131624E+11 | 0.00 | 0.69 |
Minimum of Months | 0.162652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.113472E+10 | 59490098.33 | 0.00 | 6849774.96 | 859930.84 | 0.113122E+10 | 0.299812E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.973449E+09 | 0.00 | 0.00 | 301372.99 | 0.00 | 0.139994E+10 | 0.200561E+09 | 0.00 | 0.30 |
February | 0.103370E+10 | 0.00 | 0.00 | 1738350.21 | 0.00 | 0.757912E+09 | 0.925586E+09 | 0.00 | 0.38 |
March | 0.149396E+10 | 0.00 | 0.00 | 4144033.41 | 0.00 | 0.227796E+09 | 0.212274E+10 | 0.00 | 0.53 |
April | 0.106102E+10 | 1046552.17 | 0.00 | 5685904.64 | 0.00 | 65970559.03 | 0.285007E+10 | 0.00 | 0.71 |
May | 0.855004E+09 | 1006423.62 | 0.00 | 7726240.71 | 0.00 | 3473101.89 | 0.367430E+10 | 0.00 | 0.95 |
June | 0.560689E+09 | 526069.48 | 0.00 | 8172038.17 | 165360.16 | 0.00 | 0.347044E+10 | 0.00 | 1.09 |
July | 0.408491E+09 | 42296624.51 | 0.00 | 8663442.91 | 464914.23 | 0.00 | 0.272864E+10 | 0.00 | 1.20 |
August | 0.351721E+09 | 0.136263E+09 | 0.00 | 8321698.61 | 689534.59 | 0.00 | 0.206028E+10 | 0.00 | 1.15 |
September | 0.711378E+09 | 1463808.10 | 0.00 | 9649572.30 | 0.00 | 922310.52 | 0.344726E+10 | 0.00 | 1.27 |
October | 0.117893E+10 | 0.00 | 0.00 | 5052483.89 | 0.00 | 79840458.24 | 0.283897E+10 | 0.00 | 0.72 |
November | 0.125290E+10 | 0.00 | 0.00 | 975282.36 | 0.00 | 0.705279E+09 | 0.391213E+09 | 0.00 | 0.35 |
December | 0.925332E+09 | 0.00 | 0.00 | 867382.96 | 0.00 | 0.121434E+10 | 0.463629E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.108066E+11 | 0.182602E+09 | 0.00 | 61297803.15 | 1319808.98 | 0.445548E+10 | 0.251737E+11 | 0.00 | 0.75 |
Minimum of Months | 0.351721E+09 | 0.00 | 0.00 | 301372.99 | 0.00 | 0.00 | 0.200561E+09 | 0.00 | 0.30 |
Maximum of Months | 0.149396E+10 | 0.136263E+09 | 0.00 | 9649572.30 | 689534.59 | 0.139994E+10 | 0.367430E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117320E+10 | 0.00 | 0.00 | 0.29 |
February | 0.598445E+09 | 0.00 | 0.00 | 123563.57 | 0.00 | 0.704241E+09 | 97695016.76 | 0.00 | 0.31 |
March | 0.110003E+10 | 0.00 | 0.00 | 768612.29 | 0.00 | 0.202873E+09 | 0.479615E+09 | 0.00 | 0.39 |
April | 0.816324E+09 | 572787.43 | 0.00 | 2369987.07 | 0.00 | 50775828.18 | 0.120200E+10 | 0.00 | 0.59 |
May | 0.524810E+09 | 430851.81 | 0.00 | 5584445.82 | 0.00 | 1953749.85 | 0.228058E+10 | 0.00 | 0.99 |
June | 0.331399E+09 | 1087638.00 | 0.00 | 5949540.09 | 104221.10 | 0.00 | 0.223499E+10 | 0.00 | 1.20 |
July | 0.235449E+09 | 40738924.28 | 0.00 | 7003167.70 | 490474.45 | 0.00 | 0.191367E+10 | 0.00 | 1.40 |
August | 0.220625E+09 | 91929483.42 | 0.00 | 5481103.12 | 1424671.37 | 0.00 | 0.122427E+10 | 0.00 | 1.08 |
September | 0.489111E+09 | 531519.62 | 0.00 | 4403008.30 | 0.00 | 290001.27 | 0.153935E+10 | 0.00 | 0.99 |
October | 0.949802E+09 | 0.00 | 0.00 | 1082537.53 | 0.00 | 72347582.10 | 0.652975E+09 | 0.00 | 0.46 |
November | 0.749037E+09 | 0.00 | 0.00 | 54921.52 | 0.00 | 0.576705E+09 | 28464836.91 | 0.00 | 0.30 |
December | 0.465055E+09 | 0.00 | 0.00 | 2022.58 | 0.00 | 0.103243E+10 | 4206491.06 | 0.00 | 0.28 |
Annual Sum or Average | 0.689231E+10 | 0.135291E+09 | 0.00 | 32822909.62 | 2019366.92 | 0.381481E+10 | 0.116578E+11 | 0.00 | 0.69 |
Minimum of Months | 0.220625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.110003E+10 | 91929483.42 | 0.00 | 7003167.70 | 1424671.37 | 0.117320E+10 | 0.228058E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.682490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196528E+10 | 0.00 | 0.00 | 0.29 |
February | 0.119191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114536E+10 | 0.00 | 0.00 | 0.30 |
March | 0.234756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196487E+09 | 0.00 | 0.00 | 0.32 |
April | 0.200678E+10 | 960172.65 | 0.00 | 157200.37 | 1134030.70 | 26553986.95 | 0.102880E+09 | 0.00 | 0.33 |
May | 0.130750E+10 | 1487643.74 | 0.00 | 1879322.75 | 0.00 | 0.00 | 0.103708E+10 | 0.00 | 0.47 |
June | 0.654665E+09 | 1139268.09 | 0.00 | 3657238.61 | 267452.11 | 0.00 | 0.164479E+10 | 0.00 | 0.61 |
July | 0.387325E+09 | 23232114.61 | 0.00 | 4220143.10 | 3123164.45 | 0.00 | 0.142253E+10 | 0.00 | 0.65 |
August | 0.410668E+09 | 69599388.51 | 0.00 | 3646804.70 | 2765877.59 | 0.00 | 0.110274E+10 | 0.00 | 0.60 |
September | 0.103496E+10 | 822891.63 | 0.00 | 2207706.19 | 157047.47 | 0.00 | 0.978024E+09 | 0.00 | 0.52 |
October | 0.194808E+10 | 0.00 | 0.00 | 320120.57 | 0.00 | 3512377.31 | 0.269731E+09 | 0.00 | 0.35 |
November | 0.187284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463541E+09 | 0.00 | 0.00 | 0.30 |
December | 0.112326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145717E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.149680E+11 | 97241479.23 | 0.00 | 16088536.28 | 7447572.32 | 0.525791E+10 | 0.655777E+10 | 0.00 | 0.42 |
Minimum of Months | 0.387325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.234756E+10 | 69599388.51 | 0.00 | 4220143.10 | 3123164.45 | 0.196528E+10 | 0.164479E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111356E+10 | 0.00 | 0.00 | 0.29 |
February | 0.945546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542934E+09 | 0.00 | 0.00 | 0.30 |
March | 0.142794E+10 | 0.00 | 0.00 | 220525.22 | 0.00 | 62510011.37 | 0.153454E+09 | 0.00 | 0.33 |
April | 0.794650E+09 | 1285506.75 | 0.00 | 1935162.16 | 720541.12 | 5847147.55 | 0.969550E+09 | 0.00 | 0.46 |
May | 0.549117E+09 | 1726671.28 | 0.00 | 3556856.21 | 0.00 | 0.00 | 0.168038E+10 | 0.00 | 0.73 |
June | 0.240549E+09 | 1016802.33 | 0.00 | 5799578.05 | 169933.89 | 0.00 | 0.244772E+10 | 0.00 | 1.11 |
July | 0.148111E+09 | 25987691.48 | 0.00 | 5758122.77 | 1774152.13 | 0.00 | 0.179316E+10 | 0.00 | 1.10 |
August | 0.136955E+09 | 75326804.02 | 0.00 | 5812080.62 | 976870.91 | 0.00 | 0.156433E+10 | 0.00 | 1.12 |
September | 0.433670E+09 | 1187888.48 | 0.00 | 4086465.62 | 0.00 | 0.00 | 0.160335E+10 | 0.00 | 0.88 |
October | 0.954538E+09 | 0.00 | 0.00 | 1335119.74 | 0.00 | 699255.13 | 0.768990E+09 | 0.00 | 0.44 |
November | 0.122883E+10 | 0.00 | 0.00 | 3118.55 | 0.00 | 0.252485E+09 | 5742423.01 | 0.00 | 0.30 |
December | 0.808056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838626E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.824887E+10 | 0.106531E+09 | 0.00 | 28507028.94 | 3641498.05 | 0.281666E+10 | 0.109867E+11 | 0.00 | 0.62 |
Minimum of Months | 0.136955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.142794E+10 | 75326804.02 | 0.00 | 5812080.62 | 1774152.13 | 0.111356E+10 | 0.244772E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.533549E+09 | 0.00 | 0.00 | 4265.81 | 0.00 | 0.317856E+10 | 12593646.03 | 0.00 | 0.40 |
February | 0.105358E+10 | 0.00 | 0.00 | 196617.09 | 0.00 | 0.191541E+10 | 0.141596E+09 | 0.00 | 0.39 |
March | 0.171159E+10 | 0.00 | 0.00 | 869198.36 | 0.00 | 0.110156E+10 | 0.535415E+09 | 0.00 | 0.43 |
April | 0.143937E+10 | 6322390.85 | 0.00 | 1556161.88 | 0.00 | 0.585648E+09 | 0.756031E+09 | 0.00 | 0.47 |
May | 0.138001E+10 | 3372663.54 | 0.00 | 2650575.12 | 0.00 | 0.298335E+09 | 0.115764E+10 | 0.00 | 0.62 |
June | 0.987382E+09 | 1733128.19 | 0.00 | 3669360.22 | 267966.64 | 0.142053E+09 | 0.135863E+10 | 0.00 | 0.72 |
July | 0.519870E+09 | 51238957.40 | 0.00 | 5237628.34 | 2705758.95 | 46264521.76 | 0.149537E+10 | 0.00 | 0.85 |
August | 0.496719E+09 | 0.170890E+09 | 0.00 | 5495073.88 | 1519514.45 | 39712361.22 | 0.128663E+10 | 0.00 | 0.90 |
September | 0.874777E+09 | 5253831.11 | 0.00 | 6628544.20 | 0.00 | 0.134515E+09 | 0.210271E+10 | 0.00 | 1.01 |
October | 0.134775E+10 | 0.00 | 0.00 | 2938240.35 | 0.00 | 0.437984E+09 | 0.169432E+10 | 0.00 | 0.60 |
November | 0.136670E+10 | 0.00 | 0.00 | 294278.25 | 0.00 | 0.162061E+10 | 86347453.10 | 0.00 | 0.40 |
December | 0.815718E+09 | 0.00 | 0.00 | 164874.26 | 0.00 | 0.268624E+10 | 0.115939E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.125270E+11 | 0.238811E+09 | 0.00 | 29704817.76 | 4493240.04 | 0.121869E+11 | 0.107432E+11 | 0.00 | 0.60 |
Minimum of Months | 0.496719E+09 | 0.00 | 0.00 | 4265.81 | 0.00 | 39712361.22 | 12593646.03 | 0.00 | 0.39 |
Maximum of Months | 0.171159E+10 | 0.170890E+09 | 0.00 | 6628544.20 | 2705758.95 | 0.317856E+10 | 0.210271E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.533718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115426E+10 | 0.00 | 0.00 | 0.29 |
February | 0.915023E+09 | 0.00 | 0.00 | 37172.08 | 0.00 | 0.541531E+09 | 29747150.72 | 0.00 | 0.30 |
March | 0.138575E+10 | 0.00 | 0.00 | 330176.54 | 0.00 | 94632521.64 | 0.203352E+09 | 0.00 | 0.34 |
April | 0.957360E+09 | 2321554.12 | 0.00 | 1397993.23 | 266378.57 | 10512449.54 | 0.682207E+09 | 0.00 | 0.45 |
May | 0.516141E+09 | 1583234.76 | 0.00 | 4013280.72 | 0.00 | 0.00 | 0.166567E+10 | 0.00 | 0.78 |
June | 0.275071E+09 | 3105965.29 | 0.00 | 4845098.94 | 169142.35 | 0.00 | 0.181441E+10 | 0.00 | 0.98 |
July | 0.148100E+09 | 44577217.13 | 0.00 | 5668559.50 | 421147.40 | 0.00 | 0.170405E+10 | 0.00 | 1.20 |
August | 0.161257E+09 | 0.100872E+09 | 0.00 | 4926210.99 | 1185646.73 | 0.00 | 0.123036E+10 | 0.00 | 0.98 |
September | 0.386330E+09 | 1760218.43 | 0.00 | 4188308.62 | 0.00 | 0.00 | 0.150044E+10 | 0.00 | 0.90 |
October | 0.101650E+10 | 0.00 | 0.00 | 1126319.49 | 0.00 | 527830.76 | 0.668507E+09 | 0.00 | 0.45 |
November | 0.120807E+10 | 0.00 | 0.00 | 33508.54 | 0.00 | 0.250399E+09 | 22663779.80 | 0.00 | 0.30 |
December | 0.794038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845556E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.829737E+10 | 0.154220E+09 | 0.00 | 26566628.65 | 2042315.05 | 0.289742E+10 | 0.952140E+10 | 0.00 | 0.61 |
Minimum of Months | 0.148100E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.138575E+10 | 0.100872E+09 | 0.00 | 5668559.50 | 1185646.73 | 0.115426E+10 | 0.181441E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.934476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165797E+10 | 0.00 | 0.00 | 0.29 |
February | 0.146113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808038E+09 | 0.00 | 0.00 | 0.30 |
March | 0.242368E+10 | 0.00 | 0.00 | 7849.55 | 0.00 | 0.104441E+09 | 30873228.53 | 0.00 | 0.33 |
April | 0.159247E+10 | 1449813.10 | 0.00 | 1171287.13 | 1232735.42 | 11791371.58 | 0.710542E+09 | 0.00 | 0.37 |
May | 0.929734E+09 | 1791144.09 | 0.00 | 4087198.65 | 0.00 | 0.00 | 0.199985E+10 | 0.00 | 0.61 |
June | 0.469084E+09 | 1445336.09 | 0.00 | 5764201.56 | 273103.31 | 0.00 | 0.245710E+10 | 0.00 | 0.78 |
July | 0.318096E+09 | 29808695.03 | 0.00 | 5707656.68 | 1821893.92 | 0.00 | 0.190089E+10 | 0.00 | 0.80 |
August | 0.326482E+09 | 87982245.21 | 0.00 | 4891758.27 | 1969631.81 | 0.00 | 0.144572E+10 | 0.00 | 0.73 |
September | 0.881140E+09 | 1059707.01 | 0.00 | 3275796.27 | 0.00 | 0.00 | 0.136932E+10 | 0.00 | 0.60 |
October | 0.182828E+10 | 0.00 | 0.00 | 599888.21 | 0.00 | 13068350.92 | 0.441885E+09 | 0.00 | 0.36 |
November | 0.179632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511281E+09 | 0.00 | 0.00 | 0.30 |
December | 0.114816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136368E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.141090E+11 | 0.123537E+09 | 0.00 | 25505636.32 | 5297364.46 | 0.447026E+10 | 0.103562E+11 | 0.00 | 0.48 |
Minimum of Months | 0.318096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.242368E+10 | 87982245.21 | 0.00 | 5764201.56 | 1969631.81 | 0.165797E+10 | 0.245710E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.499766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867210E+09 | 0.00 | 0.00 | 0.24 |
February | 0.769626E+09 | 0.00 | 0.00 | 16457.78 | 0.00 | 0.391820E+09 | 21955816.63 | 0.00 | 0.25 |
March | 0.104661E+10 | 0.00 | 0.00 | 760247.37 | 0.00 | 32912347.01 | 0.443901E+09 | 0.00 | 0.31 |
April | 0.618323E+09 | 1817891.55 | 0.00 | 2820476.94 | 21851.55 | 5313123.57 | 0.141424E+10 | 0.00 | 0.54 |
May | 0.439891E+09 | 1507552.11 | 0.00 | 4681529.17 | 0.00 | 0.00 | 0.214904E+10 | 0.00 | 0.85 |
June | 0.223532E+09 | 993017.58 | 0.00 | 6755352.26 | 172320.60 | 0.00 | 0.281377E+10 | 0.00 | 1.22 |
July | 0.149960E+09 | 24649457.44 | 0.00 | 6772700.09 | 1026920.40 | 0.00 | 0.201287E+10 | 0.00 | 1.20 |
August | 0.137724E+09 | 73570221.47 | 0.00 | 6418889.14 | 569227.17 | 0.00 | 0.168002E+10 | 0.00 | 1.18 |
September | 0.397183E+09 | 918738.55 | 0.00 | 4404024.79 | 424.53 | 0.00 | 0.170501E+10 | 0.00 | 0.90 |
October | 0.813825E+09 | 0.00 | 0.00 | 1435624.00 | 0.00 | 7922854.05 | 0.796274E+09 | 0.00 | 0.42 |
November | 0.911060E+09 | 0.00 | 0.00 | 26732.63 | 0.00 | 0.280144E+09 | 15999316.69 | 0.00 | 0.25 |
December | 0.621215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706963E+09 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.662872E+10 | 0.103457E+09 | 0.00 | 34092034.16 | 1790744.26 | 0.229229E+10 | 0.130531E+11 | 0.00 | 0.64 |
Minimum of Months | 0.137724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.104661E+10 | 73570221.47 | 0.00 | 6772700.09 | 1026920.40 | 0.867210E+09 | 0.281377E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128155E+10 | 0.00 | 0.00 | 466650.32 | 0.00 | 0.113202E+10 | 0.294623E+09 | 0.00 | 0.30 |
February | 0.141301E+10 | 0.00 | 0.00 | 2106152.64 | 0.00 | 0.455689E+09 | 0.106300E+10 | 0.00 | 0.40 |
March | 0.171710E+10 | 0.00 | 0.00 | 4802710.97 | 0.00 | 58893491.76 | 0.233777E+10 | 0.00 | 0.56 |
April | 0.108933E+10 | 8900599.80 | 0.00 | 5966233.49 | 3212.44 | 8238779.62 | 0.289265E+10 | 0.00 | 0.71 |
May | 0.773789E+09 | 3383751.92 | 0.00 | 8070711.09 | 0.00 | 0.00 | 0.361756E+10 | 0.00 | 0.95 |
June | 0.493105E+09 | 1772812.65 | 0.00 | 8434832.86 | 272263.02 | 0.00 | 0.337906E+10 | 0.00 | 1.08 |
July | 0.348749E+09 | 51479336.75 | 0.00 | 8508362.00 | 1543909.99 | 0.00 | 0.258779E+10 | 0.00 | 1.15 |
August | 0.292792E+09 | 0.172974E+09 | 0.00 | 8146187.72 | 787752.77 | 0.00 | 0.212135E+10 | 0.00 | 1.11 |
September | 0.615296E+09 | 5643873.14 | 0.00 | 10176696.37 | 0.00 | 0.00 | 0.352961E+10 | 0.00 | 1.29 |
October | 0.123144E+10 | 0.00 | 0.00 | 5977688.40 | 0.00 | 4568721.05 | 0.317637E+10 | 0.00 | 0.77 |
November | 0.173959E+10 | 0.00 | 0.00 | 1307504.50 | 0.00 | 0.309787E+09 | 0.548829E+09 | 0.00 | 0.37 |
December | 0.136694E+10 | 0.00 | 0.00 | 1189513.34 | 0.00 | 0.870004E+09 | 0.623534E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.123627E+11 | 0.244155E+09 | 0.00 | 65153243.70 | 2607138.22 | 0.283920E+10 | 0.261721E+11 | 0.00 | 0.75 |
Minimum of Months | 0.292792E+09 | 0.00 | 0.00 | 466650.32 | 0.00 | 0.00 | 0.294623E+09 | 0.00 | 0.30 |
Maximum of Months | 0.173959E+10 | 0.172974E+09 | 0.00 | 10176696.37 | 1543909.99 | 0.113202E+10 | 0.361756E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.663792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985029E+09 | 0.00 | 0.00 | 0.29 |
February | 0.931680E+09 | 0.00 | 0.00 | 149915.78 | 0.00 | 0.429912E+09 | 0.112910E+09 | 0.00 | 0.31 |
March | 0.129177E+10 | 0.00 | 0.00 | 881100.36 | 0.00 | 63884881.63 | 0.524056E+09 | 0.00 | 0.40 |
April | 0.822579E+09 | 4049524.15 | 0.00 | 2470112.17 | 168937.04 | 10028915.35 | 0.122005E+10 | 0.00 | 0.57 |
May | 0.467758E+09 | 1554971.32 | 0.00 | 5817229.28 | 0.00 | 0.00 | 0.223561E+10 | 0.00 | 0.99 |
June | 0.270668E+09 | 3804588.95 | 0.00 | 6091294.78 | 172641.46 | 0.00 | 0.220173E+10 | 0.00 | 1.17 |
July | 0.192518E+09 | 50974252.24 | 0.00 | 6477957.32 | 251804.61 | 0.00 | 0.182407E+10 | 0.00 | 1.34 |
August | 0.177638E+09 | 0.120488E+09 | 0.00 | 5346105.13 | 970456.14 | 0.00 | 0.128630E+10 | 0.00 | 1.06 |
September | 0.422510E+09 | 2056647.34 | 0.00 | 4775623.07 | 0.00 | 0.00 | 0.163164E+10 | 0.00 | 1.01 |
October | 0.100367E+10 | 0.00 | 0.00 | 1345383.21 | 0.00 | 7952411.13 | 0.785335E+09 | 0.00 | 0.49 |
November | 0.111522E+10 | 0.00 | 0.00 | 84864.01 | 0.00 | 0.304148E+09 | 48986274.13 | 0.00 | 0.31 |
December | 0.810847E+09 | 0.00 | 0.00 | 8559.49 | 0.00 | 0.771772E+09 | 13258311.56 | 0.00 | 0.28 |
Annual Sum or Average | 0.817065E+10 | 0.182928E+09 | 0.00 | 33448144.60 | 1563839.24 | 0.257273E+10 | 0.118839E+11 | 0.00 | 0.69 |
Minimum of Months | 0.177638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.129177E+10 | 0.120488E+09 | 0.00 | 6477957.32 | 970456.14 | 0.985029E+09 | 0.223561E+10 | 0.00 | 1.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:32:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.582953E+11 | 0.152657E+11 | 0.00 | 0.129484E+12 | 0.452041E+10 |
February | 0.121078E+12 | 0.138231E+11 | 0.00 | 0.137712E+12 | 0.368365E+10 |
March | 0.215541E+12 | 0.138825E+11 | 0.00 | 0.177718E+12 | 0.274511E+10 |
April | 0.336030E+12 | 0.125695E+11 | 0.00 | 0.199678E+12 | 0.125229E+11 |
May | 0.439451E+12 | 0.103104E+11 | 0.00 | 0.219503E+12 | 0.247992E+11 |
June | 0.441939E+12 | 0.820241E+10 | 0.00 | 0.205225E+12 | 0.458501E+11 |
July | 0.469039E+12 | 0.623209E+10 | 0.00 | 0.203981E+12 | 0.877806E+11 |
August | 0.369345E+12 | 0.482394E+10 | 0.00 | 0.160401E+12 | 0.117067E+12 |
September | 0.263211E+12 | 0.543182E+10 | 0.00 | 0.212694E+12 | 0.428726E+11 |
October | 0.166312E+12 | 0.112161E+11 | 0.00 | 0.206784E+12 | 0.590716E+10 |
November | 0.676919E+11 | 0.128611E+11 | 0.00 | 0.164259E+12 | 0.340560E+10 |
December | 0.442182E+11 | 0.136915E+11 | 0.00 | 0.144690E+12 | 0.386735E+10 |
Annual Sum or Average | 0.299215E+13 | 0.128310E+12 | 0.00 | 0.216213E+13 | 0.355022E+12 |
Minimum of Months | 0.442182E+11 | 0.482394E+10 | 0.00 | 0.129484E+12 | 0.274511E+10 |
Maximum of Months | 0.469039E+12 | 0.152657E+11 | 0.00 | 0.219503E+12 | 0.117067E+12 |